01 02 03 04 Merged

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

MAX UDAIPUR

CELEBRATIONS MALL
75F SUBMITTAL DRAWINGS

IoT-Powered Building Management Solution

TM
Saving our future never felt better. linkedin.com/company/75-fahrenheit
twitter.com/75f_io
instagram.com/75f_io
APAC Primary Office: youtube.com/c/75fvideos
Bellandur Road
WeWork Vaishnavi Signature, 4th Floor,
Outer Ring Road
Bengaluru, Karnataka 560103, IN
75F SYMBOLS LEGEND AND ABBREVIATION

SYMBOL ABBR. DESCRIPTION

CCU CENTRAL CONTROL UNIT

HS HYPERSTAT
0V O D0/- D1/+

EM ENERGY METER
N N' L1 L1' L2 L2' L3 L3'

CHW CHILLED WATER VALVE ACTUATOR


VLV

BTU BTU BTU METER

T1 T THERMISTOR FOR CHW INLET & OUTLET TEMPERATURE

RTH REMOTE TEMPERATURE & RH SENSOR


R Y B

L1 L2 L3

CONT 3 PHASE CONTACTOR


NO NC A1

NO NC A2
L1' L2' L3'
COM

RLY DPDT RELAY


NC
NO

OTN OCCUPANCY AND TEMPERATURE NODE

SMPS:

SMPS SWITCHED MODE POWER SUPPLY


INPUT: 100-240VAC
OUTPUT:24VDC

L N +V -V

GND
CON RS485 TO USB CONVERTER
USB

A+
B-

ROUT INTERNET ROUTER FOR CCU


RF SIGNAL
928MHz

CSU:01

HYPERSTAT-01

RF SIGNAL
928MHz

CSU:02 UPP

WIFI
HYPERSTAT-02
0V O D0/- D1/+

INTERNET
ROUTER
N N' L1 L1' L2 L2' L3 L3'

RF SIGNAL
928MHz
ENERGY
GND
METER

USB
A+
B-
1ST FLOOR

CSU:03 UPS POWER SUPPLY


SMPS:
INPUT: 100-240VAC
OUTPUT:24VDC
E N L
RTH
L N -V +V
(ROOM TEMP. &
HUMIDITY SENSOR)
HYPERSTAT-03

RF SIGNAL CENTRAL CONTROL UNIT (CCU)


928MHz

CSU:04

HYPERSTAT-04

RF SIGNAL
928MHz

CSU:05

HYPERSTAT-05

RF SIGNAL
928MHz

CSU:06

REFER DWG NO : 75F-MAX-CLBM-UDP-002 HYPERSTAT-06


1F UNIT:
06 NO OF CSU
UNLESS OTHERWISE SPECIFIED: DESCRIPTION:
NOTE / OPERATION SEQUENCES:
1. HYPERSTAT (WITH EXTERNAL ANTENNA) PROVIDED FOR
REF. CSU IN EACH FLOOR.
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN
THIS DRAWING IS THE SOLE
75F RISER DIAGRAM
2. CCU WITH EXTERNAL ANTENNA WILL BE PROVIDED. PROPERTY OF 75F. ANY
REPRODUCTION IN THE PART OR AS
3. UPS POWER REQUIRED FOR HYPERSTAT & CCU A WHOLE WITHOUT THE WRITTEN
NAME DATE SIZE REV. DWG. NO. PROJECT:
PERMISSION OF 75F IS PROHIBITED DRAWN AKHILESH 16-11-2022
SCALE: NTS CHECKED NITHESH 16-11-2022
A4 0 75F-MAX-CLBM-UDP-001 MAX UDAIPUR CELEBRATIONS MAL
TAG NO: DESCRIPTION: (EQUIPMENT)

1 8" TABLET OF CENTRAL CONTROL UNIT

2 REMOTE TEMPERATURE & RH SENSOR

TYPICAL FOR ALL CEILING SUSPENDED UNITS 3 RS485 TO USB CONVERTER

4 HYPERSTAT

CEILING SUSPENDED UNIT


5 HYPERSTAT INTERNAL DETAILS
CHW
6 SMPS

RETURN AIR SUPPLY AIR


7 FAN LOW SPEED (CSU ON/OFF COMMAND) 

8 ANALOG-OUT 1 (CSU FAN SPEED CONTROL)

CONTROL PANEL 9 9
AO1 ANALOG-OUT 2 (CHW ACTUATOR CONTROL)
G1' Y2' 3
CHW VALVE
3 2 T1
10 BTU METER
0V O D0/- D1/+

G AO1 BTU CHWR


T2 11 THERMISTOR FOR CHW INLET & OUTLET TEMP
N N' L1 L1' L2 L2' L3 L3' CHWS
10 12 ENERGY METER
7 8 11
12 13 INTERNET ROUTER FOR CCU

13 TAG NO: DESCRIPTION: (CABLE SPECS)


UPP
RF SIGNAL
928MHz 1 3-PIN CABLE CONNECTOR

6 6 2 CONTROL SHIELDED CABLE-2CX1.0 SQMM


INTERNET ROUTER
SMPS:
UPS POWER SUPPLY 4
INPUT: 100-240VAC
OUTPUT:24VDC
POWER SUPPLY SMPS: WIFI 3 RS485 SHIELDED CABLE- 2CX1.5 SQMM
L N E INPUT: 100-240VAC
OUTPUT:24VDC
-V +V N L E N L

L N +V -V
4 POWER CABLE- 3CX1.0 SQMM
1
C
4 2 HYPERSTAT (EXTERNAL) 4 R

RC 10 GND

USB
A+
B-
C 5 12
3 1 2
7 G
CENTRAL CONTROL UNIT
8 A01

9 A02
RTH FOR RETURN AIR
HYPERSTAT (INTERNAL DETAILS) TEMPERATURE & RH
2

UNLESS OTHERWISE SPECIFIED: DESCRIPTION:


NOTE / OPERATION SEQUENCES:
1.
2.
THIS TERMINATION DRAWING IS TYPICAL FOR ALL CSU
UPS POWER REQUIRED FOR HYPERSTAT, CCU AND ROUTER
PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN
THIS DRAWING IS THE SOLE
75F TERMINATION DRAWING FOR CSU
3. EACH CCU WILL BE PROVIDED WITH 1NO. OF INTERNET PROPERTY OF 75F. ANY
REPRODUCTION IN THE PART OR AS
ROUTER A WHOLE WITHOUT THE WRITTEN
NAME DATE SIZE REV. FLOOR DWG. NO. PROJECT:
4. EACH CSU WILL BE PROVIDED WITH 1NOS. OF RELAY FOR PERMISSION OF 75F IS PROHIBITED AKHILESH 17-11-2022
ON/OFF SCALE: NTS
DRAWN
CHECKED NITHESH 17-11-2022
A4 0 1F 75F-MAX-CLBM-UDP-002 MAX UDAIPUR CELEBRATIONS MALL