3rd Party Soft Point List PDF
3rd Party Soft Point List PDF
3rd Party Soft Point List PDF
S.No. Third Party Soft Integration Soft Point Description Soft Points
VRF On/Off status
VRF On/Off Command
VRF Run/Trip status
1 VRF Integration Fan Speed status 7
Fan speed control
Setpoint Temp
Return air temp
PAC Unit On/Off Status
PAC Unit Run/Trip status
Temperature
Humidity
High temp alarm
Low temp alarm
High humidity alarm
Low humidity alarm
Compressor run hours
Fan run hours
2 PAC integration 20
Humidifier run hours
Reheat run hours
Working /standby status
Compressor overload status
Main fan overload status
Humidifier fail status
Fan fail status
Filter status
High head pressure
Low suction pressure
CHW Supply temperature
CHW Return temperature
3 BTU meter CHW flow (gpm) 5
BTU in (KW)
Communication fail alarm
Pump On/Off status
Pump Run/trip status
4 Chemical Dosing Working/standby status 5
Chemial dosing tank level
Water pH
Temperature
Relative Humidity
CO2
5 Indoor Air Quality sensor 6
PM2.5
TVOC
Communicatio fail alarm
6 Chiller Plant Manager As per Basebuild IO summary 300
CO sensor
PLC Auto/Manual status
Fan On/Off status
Fan Run/Trip status 150 (as per BB
7 Basement Ventilation Panel PLC
VFD / Bypass mode details)
Normal mode
Timer mode
Fire alarm status
ADOBE PTP, BANGALORE .
S.No. Third Party Soft Integration Soft Point Description Soft Points
Eff temp set point
Eff flow set point
Actual zone temp
Actual flow in cfm
1 VAV Integration - Bacnet/IP 8
Velocity Minimum (Vmin)
Velocity Maximum (Vmax)
Damper actuator position
Temp set back
VRF Auto/ Manual status
VRF units Duty change over status
Fan speed input
Fan speed control
Total run hours
2 Auto Sync Panel Integration 10
Power consumed
Overload status
Temperature
Humidity
Air flow
Fire dmaper open status
3 Fire damper panel integration Fire dmaper close status 3
Fire alarm status
Speed Reference
Measured speed
Bus voltage
Motor Current
4 EC Fan (AHU) Integration 8
Motor voltage
Module temperature
Run status
Measured power
Hydrogen Monitoring Panel Hydrogen level (ppm)
5 Exhaust run/trip status 3
High level alarm
Drain Pump Integration Drain pump On/off status
Drain pump On/Off Command
6 4
Drain pump Run/Trip status
Drain tank level
Kitchen Exhaust Fans/Fresh air fan VFD Integration Frequency
Voltage
Current
Energy consumed in kWh
Power consumed by motor n kW
7 10
Fault Identification
Percentage torque
Percent Power
RPM
Motor run time in hours
ADOBE PTP, BANGALORE .
S. No. Third party Integration Soft Point Description Soft Points
Input AC voltage line-to-line 1
Input AC current for each phase 1
Input frequency 1
Battery voltage 1
Battery charge/discharge current 1
Output AC voltage line-to-line 1
Output AC current for each phase 1
Output frequency 1
Apparent power 1
Active power 1
Battery time left during battery operation 1
Mains Voltage Abnormal 1
Mains Undervoltage 1
Mains Freq. Abnormal 1
Charger Fault 1
Battery Reversed 1
No Battery 1
Control Power 1 Fail 1
Parallel Comm. Fail 1
Bypass Unable To Track 1
Bypass Abnormal 1
Inverter Asynchronous 1
1 UPS integration
Fan Fault 1
Control Power 2 Fail 1
Unit Over Load 1
System Over Load 1
Bypass Phase Reversed 1
Transfer Time-Out 1
Load Sharing Fault 1
Bypass Over Current 1
Output Ground Fault 1
Rectifier (Off / Soft Start / Main Input On / Battery Input On) 1
Input Supply (Normal Mode / Battery Mode / All Off) 1
Battery Self Test (True / False) 1
Input Disconnect (Open / Closed) 1
EPO (True / False) 1
Charger (On / Off) 1
Output Disconnect (Open / Closed) 1
Maint. Disconnect (Open / Closed) 1
Bypass Disconnect (Open / Closed) 1
Inverter (Off / Soft Start / On) 1
Bypass (Normal / Unable To Trace / Abnormal) 1
Output Supply (All Off / Bypass Mode / Inverter Mode / Output Disable) 1
Inverter On (Enable / Disable) 1
Total Soft Points 44
Cell voltage measurement
Cell Voltage control
Contactor control
Isolation monitoring
2 Battery (Lithium-Ion) Monitoring System Integration Temeperature measurement 9
Temeperature control
Charging status
Overcharging alarm
Battery health status
Voltage (V) per phase
Current (A) per phase
Resistance(Ω)
Power factor (ø)
3 Electrical Energy Meters integration Power consumption(KW) 13
Energy usage (KWh)
Reactive power (kVAR)
Apparent Power (kVA)
Meter Alarm status
Breaker On/Off status
Breaker Trip staus
Energy meter parameters
Voltage (V) per phase
Current (A) per phase
Resistance(Ω)
4 MER PLC 4890
Power factor (ø)
Power consumption(KW)
Energy usage (KWh)
Reactive power (kVAR)
Apparent Power (kVA)
Meter Alarm status
High Water temperature
Lockout relay Engine fault
Lockout relay Electrical fault
Restricted Earth fault relay 100 (As per BB
5 DG PLC
Reverse power relay details)
Engine control switch
Control supply
ACB ON /Trip feedback
ADOBE PTP, BANGALORE .
S.No. Third Party Soft Integration Soft Point Description Soft Points
Solar water tank level status
Differential temeperature measurement
Circulating pump On/Off command
1 Integrated Solar hot water system Integration 6
3 way motorised valve status
3 way motorised valve control
Heat Pump On/Off Command