Sub-Control Unit (PCA-N3060-SCU)
Sub-Control Unit (PCA-N3060-SCU)
Sub-Control Unit (PCA-N3060-SCU)
N3060
TM
PCA-N3060-SCU
Sub Control Unit
Features
• UL 864, 9th edition listed
• Max. 127 or 255 addressable devices per SLC
• Two SLCs per PCA-N3060-SCU
• NFPA Class A (Style 6 & 7) and Class B (Style 4)
• Monitoring status LED
• Easy installation
Description
The PCA-N3060-SCU is a microprocessor-based circuit assembly that is equipped with two Signal Line Circuits. Each SLC supports maximum
127 or 255 addressable devices. The maximum number of devices per loop is selectable by the PC-based Configuration Program. The max. 127
devices with 50 ohms loop resistance and 0.5µF loop capacitance are suitable for those cases requiring long wiring. The max. 255 devices with
25 ohms loop resistance and 0.4µF loop capacitance are suitable for those cases where more devices are required rather than long wiring.
The PCA-N3060-SCU communicates with addressable devices on its SLCs and is applicable to NFPA Class A (Styles 6, 7) or Class B (Style 4). A
green LED per SLC on PCA-N3060-SCU flashes while the status monitoring function is working correctly. When the PCA-N3060-SCU detects an
abnormal condition, it sends such condition (Alarm, Supervisory, or Trouble) to the main control unit (PCA-N3060-MCU) through the power supply
unit (PCA-N3060-PSU) to alert the system operator of the condition.
Ordering Information
Part No. PCA-N3060-SCU
Specifications
No. Item Specification
1 Maximum 24 VDC standby current 70 mA
2 Maximum 24 VDC alarm current 70 mA
3 Operating temperature range 0 to 49 °C (32 to 120 °F)
4 SLC wiring style NFPA Class A (Style 6 &7), Class B (Style 4)
5 Maximum No. of addresses per loop 127 / 255 addresses
50 Ω (for 127 addresses)
6 Maximum SLC loop resistance
25 Ω (for 255 addresses)
0.5 µF (for 127 addresses)
7 Maximum SLC loop capacitance
0.4 µF (for 255 addresses)
8 Communication for PCA-N3060-MCU RS-485
9 Dimensions 78 mm (H) x 180 mm (W) x 15 mm (D)
Installation and Wiring Information
PCA-N3060-
SCU (No.1) PCA-N3060-
PSU (No.1)
PCA-N3060-
SCU (No.2)
PCA-N3060-
PCA-N3060-SCU SCU (No.3)
1S+2
CN1
PCA-N3060-
1S-2 SCU (No.6)
PCA-N3060-
PSU (No.2)
2S+1
CN2
2S-1 PCA-
one SLC 2706XA
2S+2 NIU
Battery Battery
S+2
S-1
S-2
FQIU004-SCI
Wiring in NFPA Class B (Style 4)
NO NO
NO1
C NO1 C C1
S+ C1 S+ S+ NC1
S- S+ NC1
S- S- NO2
S- NO2
C2
S-2
FRRU004-MCM C2
NC2 FRRU004-MCM NC2
S+1 LED
S+2 LED
S-1 S-1
S+1 S+2 FRRU004-TRM4 FRRU004-TRM4
S-2
FQIU004-SCI S+
JP1 JP1 S+
JP1
A+ JP1
A+ FQIU004-SCI S- A-
S- A- S+ S+
24+ B+ S- OUT+ 24+ B+ S- OUT+
24- B- 24+ OUT- 24- B- 24+ OUT-
S-2 24- 24-
S+2 LED LED
S-1 S+1 LED LED
S+1
FRRU004-CIZM4 S-1 FRRU004-CIZM4
S+2 FRRU004-MOM4 FRRU004-MOM4
S-2
FQIU004-SCI
FQIU004-SCI NO1 NO1
C1 C1
S+ Z1 S+ Z1
S- NO2 S- NO2
C2 C2
Z2 Z2
LED LED
S+1
S-1
S+2 FRRU004-DCM4 FRRU004-DCM4
S-2
FQIU004-SCI
Analog detector's base C Analog detector's base C
S+ NO S+ NO
S- Z S-
Z
LED LED
FRRU004-SCM4 FRRU004-SCM4
S+2
S+1
S+2
S+1
S+2
S+1
S+2
S+1
S-2
S-1
S-2
S-1
S-2
S-1
S-2
S-1
NOTE
・The information contained herein does not purport to cover all the details or variations of the equipment described, nor to provide for every
possible contingency that may be met in connection with its installation, operation or maintenance.
・Specifications are subject to change without notice. Contact Nohmi before relying on the information.
・Actual performance is based on proper application of the product by a qualified professional.
・Should further information be required or should particular concerns arise that are not covered sufficiently for the purchaser’s purposes, the
matter should be referred to Nohmi or your nearest distributor.
Contact