Unit 3 Three Phase Alternator PDF
Unit 3 Three Phase Alternator PDF
3.3 E.M.F. equation of Alternator with numerical by considering short pitch factor
and distribution factor.
3.5 Armature resistance and leakage reactance drops. Armature reaction at various
power factors and synchronous impedance.
The working principle of an alternator is very simple. It is just like the basic
principle of DC generator. It also depends upon Faraday’s law of electromagnetic
induction which says the current is induced in the conductor inside a magnetic
field when there is a relative motion between that conductor and the magnetic
field.
After another clockwise rotation of 90 o the turn again comes to horizontal position,
and here conductor AB comes under N-pole and CD comes under S-pole, and here
if we again apply Fleming right-hand rule, we will see that induced current in
conductor AB, is from point B to A and induced current in the conductor CD is
from D to C.
As at this position the turn comes at a horizontal position from its vertical position,
the current in the conductors comes to its maximum value from zero. That means
current is circulating in the close turn from point B to A, from A to D, from D to C
and from C to B, provided the loop is closed although it is not shown here. That
means the current is in reverse of that of the previous horizontal position when the
current was circulating as A → B → C → D → A.
While the turn further proceeds to its vertical position the current is again reduced
to zero. So if the turn continues to rotate the current in turn continually alternate its
direction. During every full revolution of the turn, the current in turn gradually
reaches to its maximum value then reduces to zero and then again it comes to its
maximum value but in opposite direction and again it comes to zero. In this way,
the current completes one full sine wave cycle during each 360 o revolution of the
turn. So, we have seen how alternating current is produced in a turn is rotated
inside a magnetic field. From this, we will now come to the actual working
principle of an alternator.
Now we place one stationary brush on each slip ring. If we connect two terminals
of an external load with these two brushes, we will get an alternating current in the
load. This is our elementary model of an alternator.
Having understood the very basic principle of an alternator, let us now have an
insight into its basic operational principle of a practical alternator. During the
discussion of the basic working principle of an alternator, we have considered that
the magnetic field is stationary and conductors (armature) is rotating. But generally
in practical construction of alternator, armature conductors are stationary and field
magnets rotate between them. The rotor of an alternator or a synchronous
generator is mechanically coupled to the shaft or the turbine blades, which is made
to rotate at synchronous speed N s under some mechanical force results in magnetic
flux cutting of the stationary armature conductors housed on the stator.
As a direct consequence of this flux cutting an induced emf and current starts to
flow through the armature conductors which first flow in one direction for the first
half cycle and then in the other direction for the second half cycle for each winding
with a definite time lag of 120o due to the space displaced arrangement of 120 o
between them as shown in the figure below. This particular phenomenon results in
three-phase power flow out of the alternator which is then transmitted to the
distribution stations for domestic and industrial uses.
An alternator is basically a type of AC generator. The field poles are made to rotate
at synchronous speed Ns = 120 f/P for effective power generation. Where, f signifies
the alternating current frequency and the P represents the number of poles.
In most practical construction of alternator, it is installed with a stationary armature
winding and a rotating field unlike in the case of DC generator where the
arrangement is exactly opposite. This modification is made to cope with the very
high power of the order of few 100 Megawatts produced in an AC generator
contrary to that of a DC generator. To accommodate such high power the
conductor weighs and dimensions naturally have to be increased for optimum
performance. For this reason is it beneficial to replace these high power armature
windings by low power field windings, which is also consequently of much lighter
weight, thus reducing the centrifugal force required to turn the rotor and
permitting higher speed limits.
There are mainly two types of rotors used in construction of alternator:
The cylindrical rotor alternators are generally designed for 2-pole type giving very
high speed of
These rotors have small diameters and large axial lengths.This is to keep
peripheral speed within limits.The main advantage of this type is that these are
mechanically very strong and thus preferred for high-
speed alternators ranging between 1500 to 3000 r.p.m. Such high-
speed alternators are called 'turbo-alternators'.The prime movers used to drive
such type of rotors are generally steam turbines, electric motors.
Working Principle of Synchronous generator :
Let conductor starts rotating from position 1.at this instant, the entire
velocity component is parallel to the flux lines. Hence there is no cutting of flux
lines by the conductor. So d@/dt at this instant is zero and hence induced emf in the
conductor is also zero. As the conductor moves from position 1 to position 2, the
part of the velocity component becomes perpendicular to the flux lines and
proportional to that, emf gets induced in the conductor. The magnitude of such an
induced emf increases as conductor moves from position 1 to 2.
If a slot consists of only one coil side, winding is said to be a single layer. This
is shown in figure(a). While there are two coil sides per slot, one, at the bottom and
one at the top the winding is called double layer as shown in figure(b).A lot of
space gets wasted in single layer hence in practice generally double layer
winding is preferred.
2) Short pitching eliminates high frequency harmonics which distort the sinusoidal
nature of e.m.f. Hence waveform of an induced e.m.f. is more sinusoidal due to
short pitching.
3) As high frequency harmonics get eliminated, eddy current and hysteresis losses
which depend on frequency also get minimised. This increases the efficiency.
3) Concentrated and distributed winding:
In three phase alternators, we have seen that there are three different sets of
windings, each for a phase. So depending upon the total number of slots and
number of poles, we have certain slots per phase available under each pole. This is
denoted as 'm'.
So we have 3 slots per pole per phase available. Now let 'x' number of
conductors per phase are to be placed under one pole. And we have 3 slots per pole
per phase available. But if all 'x' conductors per phase are placed in one slot
keeping remaining 2 slots per pole per phase empty then the winding is
called concentrated winding.
Key Point: So in practice, double layer, short pitched and distributed type
of armature winding is preferred for the alternators.
So from slot No.7 we have to connect it to coil slot No.2 and slot No.2
second end to slot No.8 and so on.After finishing all slots per phase available under
the first pair of pole, we will connect the coil to slot No.13 under next pole and
winding will be repeated in a similar fashion. The starting end Rs and final end Rf
winding for R-phase are taken out finally. Connections for R-phase only are shown
in the below figure.
Now, we want to have a phase difference of 120° between 'R' and 'Y'. Each
slot contributes 30° as β = 30°.So start of 'Y' phase should be 120° apart from the
start of 'R' i.e. 4 slots away from the start of R. So start of 'Y' will be in slot 5 and
will get connected to slot No.11 to have full pitch coil. Similarly, the start of 'B' will
be further 120° apart from 'Y' i.e. 4 slots apart start of 'Y' i.e. will be in slot No.9 and
will continue similar to 'R'.
Finally, all six terminals of three sets will be brought out which are connected
either in star or delta to get three ends R, Y and B outside to get three phase supply.
The entire winding diagram with star connected windings is shown in the below
figure.
3.3 E.M.F. equation of Alternator with numerical by considering short pitch
factor and distribution factor.
Pitch Factor or Coil Span Factor (Kc):
In practice, short pitch coils are preferred. So coil is formed by connecting one coil
side to another which is less than one pole pitch away. So actual coil span is less than 180°.
The coil is generally shorted by one or two slots.
Key Point: The angle by which coils are short pitched is called angle of short pitch denoted
as 'α'.
α = Angle by which coils are short pitched.
Angle of short p
As coils are shorted in terms of the number of slots i.e. either by one slot, two slots and so
on and slot angle is β then the angle of short pitch is always a multiple of the slot angle β.
α = β x Number of slots by which coils are short pitched
or α = (180° - Actual coil span of the coils)
This is shown on the left side figure.
Now let E be the induced emf in each coil side. If the coil is full pitch coil, the induced emf
in each coil side help each other. Coil connections are such that both will try to set up a
current in the same direction in the external circuit. Hence the resultant emf across a coil
will be algebraic sum of the two.
ER = E+ E = 2E
Now the coil is short pitched by angle α, the two emf in two coil sides r longer remains in
phase from external, circuit point of view. Hence the resultant emf is also no longer remains
the algebraic sum of the two but becomes a phasor sum of the two as shown in the figure to
the left. Obviously, ER in such a case will be less than what it is in case of full pitch coil.
This is the resultant emf in case of a short pitch coil which depends on the angle of short
pitch 'α'.
Key Point: Now the factor by which, induced emf gets reduced due to short pitching called
pitch factor or coil span factor denoted by Kc.
It is defined as the ratio of resultant emf when the coil is short pitch to the result emf when
the coil is full pitched. It is always less than one.
1.The wave form of induced emf will be improved i.e. the wave form willbe very
close with perfect (ideal sine wave).
2.The harmonic contents of the induced emf reduces
3.As a length required for armature winding decreases, the copper material will be
saved, hence it is economical.
4.As the high frequency harmonics are illuminated, Hysteresis & eddy current
losses will be reduced and this increases the efficiency
As against this, in distributed type, coil sides will be distributed, one each in the 3
slots per phase available under a pole as shown in the below figure.
Though the magnitude of emf in each coil will be same as 'E', as each slot contributes
phase difference of β° i.e. 20° in this case, there will exist a phase difference of β° with
respect to each other as shown in the above figure(b). Hence resultant emf will be phasor
sum of all of them as shown in the figure to the left side. So due to distributed
winding resultant emf decreases.
Key Point: The factor by which there is a reduction in the e.mf. due to the distribution of
coils is called distribution factor denoted as Kd.
The distribution factor is defined as the ratio of the resultant emf when coils are distributed
to the resultant emf when coils are concentrated. It is always less than one.
One complete cycle of voltage is generated in an armature coil when a pair of field poles passes over the
coil, the number of cycles generated in one revolution of the rotor will be equal to the number of pairs of
field poles.
1) Load current
6) Speed
7) Load power factor OR when load power factor is unity or lagging, the terminal voltage drops with
increase in load, when the load power factor is leading, the terminal voltage increase with increase in
load.
3.5 Armature resistance and leakage reactance drops. Armature reaction at various
power factors and synchronous impedance.
In case of an alternator, we supply electricity to pole to produce magnetic field and output
power is taken from the armature. Due to relative motion between field and armature, the
conductor of armatures cut the flux of magnetic field and hence there would be changing
flux linkage with these armature conductors. According to Faraday’s law of electromagnetic
induction there would be an emf induced in the armature. Thus, as soon as the load is
connected with armature terminals, there is a current flowing in the armature coil.
As soon as current starts flowing through the armature conductor there is one reverse effect
of this current on the main field flux of the alternator (or synchronous generator). This
reverse effect is referred as armature reaction in alternator or synchronous generator.
In other words, the effect of armature (stator) flux on the flux produced by the rotor field
poles is called armature reaction.
It has two undesirable effects, either it distorts the main field, or it reduces the main field
flux or both. They deteriorate the performance of the machine. When the field gets
distorted, it is known as a cross magnetizing effect. And when the field flux gets reduced, it
is known as the demagnetizing effect.
Due to armature reaction, flux is reduced or distorted, the net emf induced is also affected
and hence the performance of the machine degrades.
Reactive power (lagging) is the magnetic field energy, so if the generator supplies a lagging
load, this implies that it is supplying magnetic energy to the load. Since this power comes
from excitation of synchronous machine, the net reactive power gets reduced in the
generator.
Hence, the armature reaction is demagnetizing.
Similarly, the armature reaction has magnetizing effect when the generator supplies a
leading load (as leading load takes the leading VAR) and in return gives lagging VAR
(magnetic energy) to the generator.
In case of purely resistive load, the armature reaction is cross magnetizing only.
The armature reaction of alternator or synchronous generator, depends upon the phase angle
between, stator armature current and induced voltage across the armature winding of
alternator.
The phase difference between these two quantities, i.e. Armature current and voltage may
vary from – 90o to + 90o
If this angle is θ, then,
To understand actual effect of this angle on armature reaction of alternator, we will consider
three standard cases,
1. When θ = 0
2. When θ = 90o
3. When θ = – 90o
As the field is excited by DC, the main field flux is constant in respect to field
magnets, but it would be alternating in respect of armature as there is a relative
motion between field and armature in the alternator. If main field flux of the
alternator in respect of armature can be represented as
Hence, from these above equations (1) and (2) it is clear that the angle between, φf
and induced emf E will be 90o.
Now, armature flux φa is proportional to armature current I. Hence, armature flux
φa is in phase with armature current I.
Again at unity electrical power factor I and E are in same phase. So, at unity power
factor, φa is phase with E. So at this condition, armature flux is in phase with
induced emf E and field flux is in quadrature with E. Hence, armature flux φa is in
quadrature with main field flux φf.
As this two fluxes are perpendicular to each other, the armature reaction of the
alternator at unity power factor is purely distorting or cross-magnetising type.
As the armature flux pushes the main field flux perpendicularly, distribution of
main field flux under a pole face does not remain uniformly distributed. The flux
density under the trailing pole tips increases somewhat while under the leading
pole tips it decreases.
Now, armature current I is proportional to armature flux φa, and I lags E by 90o.
Hence, φa lags E by 90o.
So, it can be concluded that, field flux φf leads E by 90o.
Therefore, armature flux and field flux act directly opposite to each other. Thus,
armature reaction of the alternator at lagging zero power factor is a purely
demagnetising type. That means, armature flux directly weakens main field flux.
The effect of armature reaction depends upon power factor the load:
Voltage Regulation of Alternator: It is defined as the rise in voltage when full load is
removed, keeping excitation & speed of alternator constant, expressed as percentage of
rated terminal voltage is called “Voltage regulation”.
OR
It is defined as the ratio of sudden rise or fall in voltage when the load is removed suddenly
to the rated terminal voltage, keeping speed & excitation of alternator constant.
1.Armature resistance per phase: As armature resistance increases IaRa drop increases,
which make voltage regulation poor.
2. Armature Leakage flux: If leakage flux is more, the leakage reactance XL increases
which increases IaXL drop. Hence regulation becomes poor.
3. Magnitude of load current: If load current increases IaRa and IaXL drop increases and
armature reaction effect also increases. Therefore terminals voltage drops which makes
regulation poor.
4. Load Power factor :i) For lagging power factor the effect of armature reaction is
demagnetizing and therefore the main flux reduces, considerably which causes poor
regulation.
ii)For unity P.f, the effect of armature reaction is cross magnetizing, therefore distortion in
main flux will be resulted & hence regulation is comparatively less.
iii) For leading P.f, the effect of armature reaction is strong magnetizing therefore main flux
will be more stronger and so terminal voltage actually increases which gives negative
regulation.
Here are some methods below used to determine voltage regulation of an alternator.
After giving the D.C supply to the field winding, the field current is adjusted in order
to adjust flux so that rated voltage appears across the terminals. This is observed on a
voltmeter connected across the terminals. Next load is connected by using the TPST switch.
The load is increased in steps so that ammeter reads rated current. This is the full condition
of the alternator. Again adjust the voltage to its rated value by field excitation using the
rheostat.
Then disconnect the entire load by opening TPST switch, keeping the speed and field
excitation constant. As load is disconnected there will be no armature current and associated
drops. Now the voltmeter shows a reading which is the actual value of internally induced
e.m.f called no load terminal voltage. Next convert both the readings into phase values.
The voltage on full load is Vph and voltage when load is thrown off is Eph. So voltage
regulation of alternator or synchronous generator can be determined by using the
formula
The voltmeter is connected between two line terminals to measure o.c voltage of
the alternator. For the purpose of excitation, a DC supply is connected field winding. A
rheostat is also connected in series with DC supply which is used to vary the field current
i.e field excitation.
The value of regulation of alternator or synchronous
generator obtained by this Direct loading method is accurate because a particular load
at required power factor is actually connected to note down the readings.
2. Open Circuit characteristics which are a graph between open circuit voltage [Voc] and
field current.
3. Short circuit characteristics which is a graph between short circuit current [Isc] and field
current.
The circuit diagram to perform this O.C test and S.C test is given below.
The alternator or synchronous generator is coupled with the prime mover to drive
alternator at synchronous speed. The armature of the alternator or synchronous
generator is connected to TPST switch. The three terminals of the switch are short
circuited by an ammeter.
Voltage Regulation Of Alternator Using Synchronous Impedance Method
1. O.C test
Procedure:
1) By using the prime mover start the alternator or synchronous generator and adjust its
speed to the Synchronous speed.
2) Note that rheostat should be in maximum position and switch on the D.C supply.
4) Field current is varied from its min. value to the rated value using the rheostat. So now
flux increases, which leads to increase in the induced e.m.f. The voltmeter now the actual
line value of open circuit voltage. For various values of field currents, voltmeter readings
are noted in a table.
Now plot a graph between o.c phase voltage and field current. The graph obtained is
called o.c.c .
2. S.C test
Procedure:
1) After the o.c test, the field rheostat should be kept at max. Position, reducing field current
to min. value.
2) Now the T.P.S.T switch is closed.
3) The armature gets short circuited because ammeter has negligible resistance. Now
increase the field excitation is increased gradually till full load current is obtained through
armature windings.
This is observed on the ammeter connected in the armature circuit. Tabulate the values
of field current and armature current values obtained.
4) Now plot a graph between s.c armature current and field current. The graph obtained is
called S.C.C.
The S.C.C. is a straight line passing through origin but o.c.c resembles a B.H curve of a
magnetic material.
A 3 phase star connected alternator is rated at 1500 kVA, 13.5 kV. The armature
resistance and synchronous reactance are 1.4 ohm and 25 ohm respectively per
phase. Calculate percentage voltage regulation for a load 1200 kW at 0.8 leading
pf.
A 3-phase, star connected alternator rated at 1600 kVA 13500 V; The armature
resistance and synchronous reactance are 1.5 ohms and 30 ohms respectively per
phase -calculate percentage voltage regulation for a load of 1280 kW at a power
factor:(i) 0.8 leading (ii) unity
Calculate the value of pitch factor for a 3 phase winding of a 4 pole alternator
having 36 slots and the coil is spread from 1stslot up to 7thslot.
A 3-phase, 6 pole, star connected alternator revolves at 1000 r.p.m. The stator has
90 slots and 8 conductors per slot. The flux per pole is 0.05 wb (sinusoidally
distributed) calculate the value of phase voltage and line voltage generated by the
machine, if the winding factor is 0.96.