SAT Support Info 1110a PDF
SAT Support Info 1110a PDF
SAT Support Info 1110a PDF
1 November 2010
Contents
1. Indoor Coil Sensor
2. Indoor Fan Operation
3. Temperature Control
4. Remote Sensors/Averaging of Sensors/Twin Wall Plaques
5. Hot Start
6. Hot Keep (Heat Mode or Heat Cycle in Auto Mode)
7. Cooling Only System
8. Indoor Freeze Protection
9. External Time Clock or Remote Switching Capability
10. BMS Interface
11. Dip Switch Changing
12. Dip Switch Settings
13. Voltage Selection
14. Auto Restart
15. Sleep Mode
16. Temporary Cancellation of Time Clock Functions (For Holiday)
17. Boost Heat
18. Error Codes
19. Activating A Remote Fresh Air and/or Exhaust Fan
20. Remote Indication
21. Calibration of Sensors
22. Reset Procedure
23. Zone Control
24. Troubleshooting
25. Over-ride Outside Time Clock Hours
26. Key Lock
27. On/Off Indication
28. Display of Sensor Temperatures
29. Swing Motor Operation
30. Compatibility of Versions
31. Identification
-1-
temperzone SAT Support Information
-2-
temperzone SAT Support Information
COOL MODE + SELECTED FAN SPEED Compressor runs only in cooling and fan runs on
selected speed with the fan running or stopping in dead zone being selectable (by dip switch 4
on the SAT-2 or 2.1, or dip switch 5 on the SAT-1). In cool modes only, on initial start up, the
fan may run immediately.
AUTO MODE + AUTO FAN Compressor is able to operate both in cooling and heating cycles,
fan ramps up and down, runs continuously and continues to run in dead zone. There is a 10
minute delay when changing between heat and cool cycles or vice versa.
Note: On initial start up, the indoor fan will not run if heating cycle is being called for, until
the indoor coil warms up.
AUTO MODE + SELECTED FAN SPEED Compressor runs both in cooling and heating and
fan runs continuously on selected speed and continues running in dead zone. There is a 10
minute delay when changing between heat and cool cycles or vice versa. Note: On heating the
selected speed may be overridden and moved to a higher speed if the coil temperature becomes
too hot, to prevent HP trips.
Note: On initial start up, the indoor fan will not run if heating cycle is being called for, until
the indoor coil warms up.
CONTINUOUS FAN OPERATION The only way to achieve the indoor fan running
continuously under all conditions, including initial start up, is to wire the fan via a contactor
that is then connected to the OUT6 terminal (normally utilised for the Zone Control operation).
This terminal has a voltage (230V or 24V depending on the voltage input on OUT5 terminal)
at all times the controller is turned on. Some larger units (generally 24 Volt) must have the fan
running before the compressor is allowed to start so continuous fan operation is imperative.
3. Temperature Control
The differential is +/- 0.5°C of set point with 10 minute minimum changeover delay between heat
and cool cycles in Auto Mode. Do not expect this to control a space temperature this closely. Expect
control to within +/- 1.0°C where the controller wall plaque (or remote sensor) is located.
-3-
temperzone SAT Support Information
5. Hot Start
Operates on initial power up in Heat mode and on the Heat cycle in Auto Mode unless one of the
constant fan modes is selected.
In Auto mode as the mode crosses from Cool to Heat, fan will stop unless a constant fan mode is
selected.
Indoor fan starts (on Low speed) only once 33°C is reached at indoor coil sensor
Indoor fan changes to Med speed when 39°C is reached at indoor coil sensor
Indoor fan changes to High speed when 45°C is reached at indoor coil sensor
-4-
temperzone SAT Support Information
10. BMS
No specific facility is provided to allow for connection to a BMS system.
On the upgraded 2009 version of the SAT-2 controller, on and off control will be available via the
terminals ‘COM’ and ‘DI-1’ – refer 9(c) above.
On the SAT-1 and earlier versions of SAT-2 the same could be achieved by using the terminals
described in 9(a) above with the same drawbacks.
External fault alarm can be achieved by fitting an external alarm relay (part no 201 000 105) to the
pins provided on the PC board.
There is no intention of providing for the BMS to be able to alter any control parameters.
-5-
temperzone SAT Support Information
SAT-2:
OFF ON Factory Setting
DIP 1 Cool only operation Heat pump r/c operation On
DIP 2 No electric heat operation Electric heat operation Off
DIP 3 1.5°C diff control 1.0°C diff control On
DIP 4 Fan on in dead zone in cool mode Fan off in dead zone cool mode Off
DIP 5 Air cooled unit Hydronic unit To suit
DIP 6 Two stage operation Single stage operation -
DIP 7 Alarm relay activated on lockout only Alarm relay on every fault Off
DIP 8 Indoor fan runs on low speed in heat dead band Indoor fan off in heat dead band (cold draft prevention)
-6-
temperzone SAT Support Information
SAT-1:
ER 1 – Room Sensor #1 failure
ER 2 – Room Sensor #2 failure
ER 3 – Room Sensor #3 failure
ER 4 – Room Sensor #4 failure
ER 5 - Indoor Coil Sensor #1 failure
ER 6 - Outdoor Coil Sensor #1 failure
ER 7 – Low Refrigerant Charge
ER 8 – Compressor Overload
Heat Cycle Indoor Coil Sensor cuts out compressor at 68°C
Cool Cycle Outdoor Coil Sensor cuts out compressor at 68°C (unless outdoor board or
hydronic selected)
ER 9 – Low Pressure (LP) failure
ER 10 – High Pressure failure (HP)
ER 11 – Room Sensor #5 failure at Wallpad B
SAT-1 (cont’d):
ER 12 – Room Sensor #6 failure at Wallpad A
ER 13 – All Room Sensors failure
ER 14 – Water Pump/Float Switch failure
ER 15 – Low Safety Thermostat failure
ER 16 – Communication failure
ER 17 – Hydronic Pump Switch failure
-7-
temperzone SAT Support Information
SAT-2:
Sensors highlighted are applicable to ‘Hydronic’ HWP units only. Should these highlighted error
codes appear on an air cooled system, check and change dip switch 5 to OFF position.
ER 1 – Room Sensor #1 failure
ER 2 – Room Sensor #2 failure or LST Sensor #2 failure if set on 2 stage
ER 3 – Room Sensor #3 failure or Indoor Coil Sensor #2 failure if set on 2 stage
ER 4 – Room Sensor #4 failure
ER 5 - Indoor Coil Sensor #1 failure
ER 6 – LST Sensor #1 failure
ER 7 – Low Refrigerant Charge system #1
ER 8 – Compressor #1 Overload
Heat Cycle Indoor Coil Sensor cuts out compressor at 68°C
Cool Cycle has no function as no outdoor coil sensor fitted
ER 9 – Low Pressure (LP) failure
ER 10 – High Pressure (HP) failure
ER 11 – Room Sensor #5 failure at Wallpad B
ER 12 – Room Sensor #6 failure at Wallpad A
ER 13 – All Room Sensors failure
ER 14 – Water Pump/Float Switch failure
ER 15 – LST #1 failure
ER 16 – Communication failure
ER 17 – Hydronic Pump Switch failure
ER 18 – Insufficient Refrigerant system #2
ER 19 – Compressor #2 Overload
ER 20 – LST #2 failure
ER 21 – Discharge Sensor #1 failure
ER 22 – Discharge Sensor #2 failure
ER 23 – Discharge Temperature #1 failure
ER 24 – Discharge Temperature #2 failure
Note: ‘LST’ is Low Suction Thermostat
-8-
temperzone SAT Support Information
-9-
temperzone SAT Support Information
24. Troubleshooting
Controller Dormant (Sleeping – fault)
There have negligible incidences of this occurring on either the SAT-1 or SAT-2 controller. If this
should occur use the reset procedure detailed in clause 22 above. If the problem persists contact
temperzone Engineering.
- 10 -
temperzone SAT Support Information
Once in this mode use the – and + buttons to scroll through the available parameters: -
C0 Dip Switch setting in Hexadecimal form
C1 Zone 1 temperature
C2 Zone 2 temperature (If Connected)
C3 Zone 3 temperature (If Connected)
C4 Zone 4 temperature (If Connected)
C5 Indoor Coil Temperature
C6 Outdoor Coil Temperature (Not Connected)
There is no compatibility at all between the SAT-1 controller and either the SAT-2 or SAT-2.1.
- 11 -
temperzone SAT Support Information
30. Identification
SAT-1: Wall plaque has temperzone logo in grey colour on cover and a 4 pin socket bottom right
of PC board.
‘SAT 1’ label on main board chip.
SAT-2: Wall plaque has temperzone logo in silver colour on cover and ‘SAT-2-LCD’
on chip label.
‘SAT 2’ part no. label on main board.
SAT-2.1: Wall plaque has temperzone logo in silver on cover and ‘SAT 2.1’ on chip label
‘SAT 2.1’ part no. label on main board and chip.
- 12 -