The purpose of this tech design exercise is to do a case study on the building services system installed in the Inorbit
Mall, Malad. To identify and understand the relevant information related to majorly fire protection system, water supply
system, electrical system and mechanical system.The aim of this study is to find how the building system are placed
in vertical and horizontal fashion, which indeed helps to understand the zoning of this mall.In order to learn and
comprehend the building system we have also looked through the NBC and attempted to analyse the functions.
CONTENTS
3. ELECTRICAL SYSTEM
4. MECHANICAL SYSTEM
PROJECT
1 INTRODUCTION
PROJECT INTRODUCTION
PLOT
The site chosen is Inorbit mall located at malad , Mumbai. Which is established in 2004. It was designed by Architectural firm PmG Patki
and Associates..It has footfall of 500,000 sq ft.It is three storey structure with basement . Building have one main entrance gate on north
side and the premise is well approachable for vehicles from east and north side main road.
WATER SUPPLY
FIRE SAFETY SYSTEM
1
INDEX
Panel Room
Fire Staircase
Smoke check lobby
Fire Tank
Fire Staircase
Fire escape Stairs
Fire Resistance
Wall
4.FireLift
Fire Lift
3.Fire Lift
1.Fire Tender access 2.Compartmentation
Fire Escape Corridor
Index
Mall Boundary
Road
Analysis -
Building have one main entrance gate on north side
In ideal case The fire control room should be accessible via 2
and the premise is well approachable for fire brigade
travel paths. one from front entrance and other from public
vehicles from east and north side main road.
place for a fire isolated passageway , and has 2hr frd. But in
case of inorbit mall ,malad the fire control room is located in
Width of the existing road - 6m
basement and it has only one access door.
Fire
Detection
system
The entire proposed premises is provided with smoke detection system along with the control panel & hooters as per BIS specification
and its panel is installed in the reception/security cabin.
Fire detection system provide warning of fire outbreak before the situation worsens hence allowing the appropriate fire fighting actions to
take place
● A smoke detector is an electronic fire-protection device that automatically senses the presence of smoke, as a key indication of fire,
and sounds a warning to building occupants-
●
● heat detectors -A heat detector is a fire alarm device designed to respond when the convected thermal energy of a fire increases the
temperature of a heat sensitive element.
Approx 9 m
Fire Alarm
System
Announcement Speaker
speakers is to assure able to provide clear effective communication while emergency happen is special in fire where there is a fire the
announcer will make announcement from the control room and tell about the situation and let the occupants to leave safely.
Water
Based
system
Fire
Pump
Room
Fire Water
Storage Tank
Hose Reel
Sprinkler
System
System
Pump
Required
Location of fire pump room and fire tank - Basement
● Fire sprinkler system consists of water supply system which provides pressure to water distribution piping system where the
sprinklers are connected .It requires Central control and test gear , there are four types of sprinkler system -Wet pipe , Dry pipe ,
Deluge and preaction.
●
● Automatic sprinkler system comprises of
● 1)Pipe works and valves
● 2)Pumping system
● 3)Sprinkler water tank
● 4)Control valve set
● 5)Sprinkler head
● 6)Flow and pressure switches
●
● The sprinkler system in mall is the wet pipe fire sprinkler system which is considered as common and implemented in todays
buildings.60 hp Main pump set for sprinkler system - 1set , 7.5 hp jockey pump set for sprinkler system - 1set
● The entire premises is provided with automatic sprinkler system as per standard IS specification.
● Hose reel system is designed for the occupants or firemen to use during
early stages of fire breakout.It consist of a series of pipes where high
pressure water is connected to hoses.
●
● Two pumps that are required in enabling this are duty pump and standby
pump.
●
● 40 no of Hose reel drums are used in entire mall premises.
● 10 hp jockey pump set for hydrant system , 1 set 75 hp Main pump set for
hydrant system - 1 set i used in fire hydrant system.
Fire Extinguisher
Portable fire extinguisher are manually operated appliances used to stop or limit the growth of small fires.
● Portable type
● ABC type 6 kgs capacity- 54 no.
● Co2 type 4.5 kgs capacity - 32no
● The staff shall be trained in basic fire fighting, use of fire extinguishers and for evacuation
● Two water type CO2 stored pressure fire extinguishers of capacity 9 ltrs. & Two dry chemical powder (ABC type) fire extinguishers of
09kgs. capacity each with BIS mark along with four buckets filled with dry clean sand shall be kept at every 100 sq.mtrs area on each
floor at prominent & easily accessible places.
Fire
Related
Door
Staircase
Staircase
Staircase
● The lift shall have a floor area of not less than 1.4 sq.mt. It shall have a
loading capacity of not less than 545 kg. (8 persons lift) with automatic
closing doors.
● The operation of a fire lift shall by a single toggle of two-button switch
situated in a glass-fronted box adjacent to the lift at the entrance level.
When the switch is on landing; call points will become inoperative and
the lift will be on car control only or on a priority control device. When
the switch is off, the lift will return to normal working. This lift can be
used by the occupants in normal times.
● The words 'F1RE LIFT' shall be conspicuously displayed in fluorescent
paint on the lift landing doors at each floor level.
● The speed of the fire lift shall be such that it can reach to the top floor
from ground level within one minute
Water is supplied from Bhandup complex water treatment plant from there it's supplied in Malad r reservoir. From there, with help of
underground system supplied on site in basement water tank from their with help of indirect water supply system it is transferred to
overhead tank and than to kitchen, toilets,fire fighting requirements etc.
ACCORDING TO DCPR
(a) RESTAURANTS (PER SEAT) 70
(b) OTHER BUSINESS BUILDINGS 45
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY TO
WATER COLLECTION WATER TREATMENT SITE
RESERVOIR{MALAD}}
TO WATER TANK
NON RETURN VALVE
BASEMENT METER BOX CUTOFF VALVE
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
WATER SUPPLY
DRAINAGE SYSTEM
For drainage every toilet area have ducts for drainage system so pipeline travel through ducts and gets connected to inspection
chamber and to main drainage system out side
WATER SUPPLY
DRAINAGE SYSTEM
WATER SUPPLY
ELECTRICAL SYSTEM
3
ELECTRIC SUPPLY
TRANSMISSION
RETAIL -
&
CONSUMERS
DISTRIBUTION
ELECTRICAL
SYSTEM
SAFETY POWER
EQUIPMENTS GENERATION
ELECTRICAL SERVICE
ELECTRICAL SPATIAL SUPPLY
ELECTRICAL ROOM
( DISTRIBUTION
BOARD AT EACH
FLOOR )
MAIN SUPPLY
DIESEL
GENERATOR SETS
BACKUP SUPPLY
Components of System :
SUBSTATION HIGH TENSION ROOM TRANSFORMER LOW TENSION ROOM RISER ROOM
ELECTRICAL SERVICE
ELECTRICAL ZONING
PARKING AREA
SERVICE YARD
PARKING AREA
ELECTRICAL SERVICE
ELECTRICAL ZONING
TS
D.G SE
SUBSTATION
SERVICE SHAFT
ENTRANCE
LIFT
ELECTRICAL SERVICE
ELECTRICAL DISTRIBUTION
SUBSTATION
DISTRIBUTION PANEL
METER
ROOM
MTNL TEL. ROOM
MAIN SWITCH
METER
PLANT ROOM ROOM
LIFT
RISER
MACHINE
RISER ROOM
ROOM
PANEL ROOM
ROOM
RISER
LIFT MACHINE ROOM ROOM
EQUIPMENTS
( Consumer Use )
BASEMENT PLAN
ELECTRICAL SERVICE
ELECTRICAL DISTRIBUTION
LIVE WIRE NEUTRAL WIRE
240
240
240
ELECTRICAL SERVICE
ELECTRICAL DISTRIBUTION
ELECTRICAL TRUNKING
Rising electrical mains are a type of electrical main which distributes power
Advantages :
and provides electricity at each level. An Electrical Distribution Board will
deliver the electricity to each storey & separate electric meters are installed - Occupies Less Space
at each level. This System enables Vertical Distribution of Power Supply. - Less Fire Hazard , as per NBC
- Additional Power can be tapped from rising main in future
- It is technically Superior
Earth Fault Relay associated with the protection C.Ts could be used to
achieve automatic disconnection within 5 seconds during an earth fault.
ELECTRICAL SERVICE
ELECTRICAL DISTRIBUTION
SMALL POWER
BUSBAR TRUNKING
TAP-OFF FEEDING
BUSBAR DISTRIBUTION
COPPER BUSBAR
Connection Diagram
Busbar Trunking System
Advantages :
Busbars, also known as busbar trunking systems, distribute electricity (a) Reduced, on site installation times when compared to
with greater ease and flexibility than some other more permanent forms hard-wired systems thus leading to cost savings.
of installation and distribution.
(b) Increased flexibility in design and versatility with regard to
Copper is a common conductive metal used in busbars and many future modifications.
electrical utilities around the world. Copper is chosen for it’s resilience
to higher temperatures, providing extra security during short circuit (c) Increased safety features brought about by the use of high
situations. quality, manufactured components, which provide greater safety
and peace of mind for specifiers, contractors and end-users.
ELECTRICAL SERVICE
ELECTRICAL DISTRIBUTION
ELECTRICAL SERVICE
ELECTRIC SUPPLY COMPONENTS
The high-tension line has an operating voltage of 33KV, so the operating voltage of this line will range from 11Kv
to 33KV and if it is above 33KV then it is called an extra high tension line. We can’t see many faults in high
tension lines because it is not directly connected to the load. The higher voltage transmission would need larger
structures with longer insulator chains
SUBSTATION
A substation is an electrical system with high-voltage capacity and can be used to control the apparatus, generators,
electrical circuits, etc. The Substations are mainly used to convert AC (alternating current) to DC (direct current). Some
types of substations are tiny in size with an inbuilt transformer as well as related switches. Other types of substations are
very huge with different types of transformers, equipment, circuit breakers, and switches.
TRANSFORMER
A power transformer is a static machine used for transforming power from one circuit to another without changing the frequency. As
there is no rotating or moving parts, a transformer is classified as a static device. Transformer operates on an AC supply. Transformers
operate based on the principle of mutual induction.
ELECTRICAL SERVICE
ELECTRICAL SPATIAL SUPPLY
ELECTRICAL SERVICE
ELECTRIC SUPPLY COMPONENTS
Low Tension Room Main Switch Board Arrangement Main Switch Board
The Low Tension Room and the Main Switch Board receive stepped Main switchboard – assembled unit of electrotechnical
down current from the transformer to allow electricity to further components. It is used for receiving, measuring and distribution of
distributed to Riser room. electrical energy and protects the network from overload,
short-circuit and current leak.
he Low Voltage Room, also known as the Low Tension Room,
houses the main switches of different facilities in a building. The The primary components of a switchboard structure are the frame,
transformers will then transfer the respective currents to each panel. bus, overcurrent protective devices, instrumentation, enclosures
and exterior covers.The bus, which is either copper or aluminum, is
LT Panels are used with low tension cables to obtain power from the mounted within this frame.
generator or transformer and distribute electricity to various electrical
devices and distribution boards
ELECTRICAL SERVICE
ELECTRIC SUPPLY COMPONENTS
The Meter Room is located in the Basement of the Mall. An electric meter, or energy meter, is a device that measures the amount of electric
energy consumed by a building, tenant space, or electrically powered equipment.
● Electric utilities use electric meters installed at customers' premises to measure electric energy delivered to their customers for billing
purposes.
● The Power supply from the Meter Room is distributed to various circuits or consumer points/Shops , Lighting , Ventilation etc.. The
Distribution Board Panel included fuses , circuit breakers and ground leakage protection units.
ELECTRICAL SERVICE
ELECTRIC SAFETY APPLIANCES
An air Circuit Breaker (ACB) is an electrical device used to provide When the circuit breaker is being opened, the main contacts open
Overcurrent and short-circuit protection for electric circuits over 800 first. When the main contacts opened the arcing contacts are still in
Amps to 10K Amps. These are usually used in low voltage applications touch with each other. As the current gets a parallel low resistive
below 450V. We can find these systems in Distribution Panels (below path through the arcing contact.
450V)
● During the opening of main contacts, there will not be any
● Air circuit breaker is circuit operation breaker that operates in the air arcing in the main contact. The arcing is only initiated when
as an arc extinguishing medium, at a given atmospheric pressure. finally the arcing contacts are separated. The each of the arc
contacts is fitted with an arc runner which helps. The arc
● The Air Circuit Breakers are installed in each panel of Main Switch discharge to move upward due to both thermal and
Board located in Low Tension Room electromagnetic effects
ELECTRICAL SERVICE
ELECTRIC SAFETY APPLIANCES
RCCB stands for Residual Current Circuit Breaker. This residual Moulded case circuit breaker (MCCB) is a type of electrical
current device is basically an electrical wiring device that protection device that is used to protect the electrical circuit
disconnects the circuit whenever there is leakage through the Human from excessive current, which can cause overload or short
body or the current is not balanced between the phase conductor. circuit. With a current rating of up to 2500A,
It is the safest device to detect and trip against electrical leakage MCCBs can be used for a wide range of voltages and
currents, thus ensure protection against electric shock caused by frequencies with adjustable trip settings. These breakers are
direct contacts. RCCB which protects them from over current and used instead of miniature circuit breakers (MCBs) in large scale
short circuit current. Both phase and neutral wires PV systems for system isolation and protection purposes.
are connected through a RCCB device.
ELECTRICAL SERVICE
ELECTRIC SUPPLY COMPONENTS
The Riser room are strategically located at every level in the malls to allow current to pass from Main Switch Board to the electrical
facilities . It has electrical distribution equipment such as side switch board with switchgear and panels that supply electricity mainly to
those higher voltage machines for instance lift and elevator
● The riser rom also allow vertical cables to carry electricity to the upper floors of the mall
For instance the plants and machine at the rooftop such as chiller plants, cooling towers and lift motor rooms.
● Electrical rooms in the inorbit mall share similar function with the riser room which it transfers to the electrical appliances in every
storey in the mall. The only difference is electrical room carries less amounts of voltage compared to the riser room.
● It has Electrical Distribution equipments such as Side Switch Board with switchgears and panels that supply electricity to those higher
voltage machines.
ELECTRICAL SERVICE
ELECTRIC SUPPLY BACK-UP
The diesel fuel tank is connected to the generator in order to power the operation of the machine after the engine is started. The fuel in
tank in gardens mall is elevated higher than the machine to avoid unnecessary collision and also to perform hydraulic system to supply
the diesel efficiently to the generator. The diesel fuel allows combustion of the motor and electric current is generated to further
distributed to low tension room and rest of the compartments to be used in the entire building
● Diesel generating sets are used in places without connection to a power grid, or as emergency power-supply if the grid fails, as well
as for more complex applications such as peak-lopping, grid support and export to the power grid.
● Proper sizing of diesel generators is critical to avoid low-load or a shortage of power. Sizing is complicated by the characteristics of
modern electronics, specifically non-linear loads.
ELECTRICAL SERVICE
MECHANICAL SYSTEM
4 TRANSPORTATION
MECHANICAL SYSTEM
Introduction :
The Mechanical Transportation System is a fundamental component of a building.
The System comprises of transport devices, to move the passengers and freight
vertically and horizontally by mechanical means. Besides accelerating people’s
movement, it increases productivity and efficiency of users.
TRANSPORTATION SERVICE
MECHANICAL SYSTEM ZONING
BASEMENT PLAN
TRANSPORTATION SERVICE
MECHANICAL SYSTEM
ENTRANCE
TRANSPORTATION SERVICE
MECHANICAL SYSTEM
TRANSPORTATION SERVICE
MECHANICAL SYSTEM
TRANSPORTATION SERVICE
MECHANICAL SYSTEM
TRANSPORTATION SERVICE
MECHANICAL SYSTEM
ESCALATORS
TRANSPORTATION SERVICE
MECHANICAL SYSTEM
ESCALATORS
TRANSPORTATION SERVICE
BIBLIOGRAPHY
https://electrical-engineering-portal.com/download-center/books-and-guides/electrical-engineering/lig
hting-electrical-systems-design
https://www.tugraz.at/en/tu-graz/services/news-stories/planet-research/singleview/article/to-integrate-
or-not-to-integrate/
https://passivehousebklyn.wordpress.com/passive-house-bklyn-i/systems/
https://www.legrand.co.za/download/solutions/shopping-centre-shops-solution.pdf
http://shodhbhagirathi.iitr.ac.in:8081/jspui/image/pdf/web/viewer.html?file=/jspui/bitstream/123456789
/1994/1/APDG21858.pdf
https://fire.nv.gov/uploadedfiles/firenvgov/content/bureaus/FST/4-ifipp-PSsm.pdf
https://www.designingbuildings.co.uk/wiki/Plant_room
https://www.gosheating.c
o.uk/commercial/plant-room-maintenance/
https://www.youtube.com/watch?v=x0wCJWMusz4
https://www.designingbuildings.co.uk/wiki/Plant_room
https://www.shutterstock.com/search/electric+panel+room
https://www.enecho.meti.go.jp/en/category/electricity_and_gas/electric/electricity_liberalization/supply
/#:~:text=The%20power%20supply%20system%20is,(3)%20the%20retail%20sector.&text=This%20s
ector%20operates%20hydroelectric%2C%20thermal,power%20plants%20and%20produces%20elec
tricity.
https://electrical-engineering-portal.com/planning-installation-low-voltage-switchgear
https://mohua.gov.in/upload/uploadfiles/files/Chap-7.pdf
https://www.youtube.com/watch?v=5ACimt3aXAo
https://www.scribd.com/document/88133987/Treatment-Plant