Process Design of Heat Exchanger

Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

Module #1

PROCESS DESIGN OF HEAT EXCHANGER: TYPES OF HEAT EXCHANGER,


PROCESS DESIGN OF SHELL AND TUBE HEAT EXCHANGER, CONDENSER AND
REBOILERS

1. PROCESS DESIGN OF SHELL AND TUBE EXCHANGER FOR SINGLE


PHASE HEAT TRANSFER

1.1. Classification of heat exchangers


1.2. Thermal design considerations
1.2.1. Shell
1.2.2. Tube
1.2.3. Tube pitch, tube-layout and tube-count
1.2.4. Tube passes
1.2.5. Tube sheet
1.2.6. Baffles
1.2.7. Fouling Considerations
1.2.8. Selection of fluids for tube and the shell side
1.3. Process (thermal) design procedure
1.4. Design problem

2. PROCESS DESIGN OF SHELL AND TUBE EXCHANGER FOR TWO


PHASE HEAT TRANSFER

2.1. Condenser
2.1.1. Types of condensers
2.1.2. Condenser design
2.1.2.1. Mean temperature difference
2.1.2.2. Calculation of heat transfer co-efficient during
condensation
2.1.2.3. Pressure drop calculation
2.1.3. De-superheating and sub-cooling

2.2. Reboilers
2.2.1. Classification of reboilers
2.2.2. Design of Kettle reboiler
Lecture 1: Heat Exchangers Classifications
1. PROCESS DESIGN OF SHELL AND TUBE
EXCHANGER FOR SINGLE PHASE HEAT
TRANSFER
1.1. Classification of heat exchangers
Transfer of heat from one fluid to another is an important operation for most of the
chemical industries. The most common application of heat transfer is in designing of heat
transfer equipment for exchanging heat from one fluid to another fluid. Such devices for
efficient transfer of heat are generally called Heat Exchanger. Heat exchangers are
normally classified depending on the transfer process occurring in them. General
classification of heat exchangers is shown in the Figure 1.1.
Amongst of all type of exchangers, shell and tube exchangers are most commonly used
heat exchange equipment. The common types of shell and tube exchangers are:
Fixed tube-sheet exchanger (non-removable tube bundle): The simplest and cheapest
type of shell and tube exchanger is with fixed tube sheet design. In this type of
exchangers the tube sheet is welded to the shell and no relative movement between the
shell and tube bundle is possible (Figure 1.2).
Removable tube bundle: Tube bundle may be removed for ease of cleaning and
replacement. Removable tube bundle exchangers further can be categorized in floating-
head and U-tube exchanger.
 Floating-head exchanger: It consists of a stationery tube sheet which is
clamped with the shell flange. At the opposite end of the bundle, the tubes
may expand into a freely riding floating-head or floating tube sheet. A
floating head cover is bolted to the tube sheet and the entire bundle can be
removed for cleaning and inspection of the interior. This type of exchanger
is shown in Figure 1.3.
 U-tube exchanger: This type of exchangers consists of tubes which are bent
in the form of a „U‟ and rolled back into the tube sheet shown in the Figure
1.4. This means that it will omit some tubes at the centre of the tube bundle
depending on the tube arrangement. The tubes can expand freely towards
the „U‟ bend end.
The different operational and constructional advantages and limitations depending on
applications of shell and tube exchangers are summarized in Table 1.1. TEMA (USA)
and IS: 4503-1967 (India) standards provide the guidelines for the mechanical design of
unfired shell and tube heat exchangers. As shown in the Table 1.1, TEMA 3-digit codes
specify the types of front-end, shell, and rear-end of shell and tube exchangers.
Heat exchanger may have singe
or two phase flow on each side
Fixed tubesheet
Flow
Shell & tube U-tube

Cross Parallel Counter Removable bundle

Tubular Spiral tube Floating head

Double pipe

Finned tube

Indirect Extended
contact-type surface

Finned plate

Recuperative Gasketed plate

Plate Spiral plate

Lamella
Direct
contact-type

Heat
Exchanger
Disk type

Rotary
regenerator

Regenerative
Drum type

Fixed-matrix
regenerator

Figure 1.1. Classification of heat exchangers depending on their applications.


Table 1.1. Features of shell and tube type exchangers.
Shell and Typical Advantages Limitations
Tube TEMA code
Exchangers
Fixed tube BEM, AEM, Provides maximum heat Shell side / out side of the tubes are
sheet NEN transfer area for a given inaccessible for mechanical cleaning.
shell and tube diameter.
No provision to allow for differential thermal
Provides for single and expansion developed between the tube and
multiple tube passes to the shell side. This can be taken care by
assure proper velocity. providing expansion joint on the shell side.

Less costly than


removable bundle designs.

Floating- AEW, BEW, Floating tube sheet allows To provide the floating-head cover it is
head BEP, AEP, for differential thermal necessary to bolt it to the tube sheet. The bolt
AES, BES expansion between the circle requires the use of space where it
shell and the tube bundle. would be possible to place a large number of
tubes.
Both the tube bundle and
the shell side can be Tubes cannot expand independently so that
inspected and cleaned huge thermal shock applications should be
mechanically. avoided.

Packing materials produce limits on design


pressure and temperature.

U-tube BEU, AEU U-tube design allows for Because of U-bend some tubes are omitted at
differential thermal the centre of the tube bundle.
expansion between the
shell and the tube bundle Because of U-bend, tubes can be cleaned only
as well as for individual by chemical methods.
tubes.
Due to U-tube nesting, individual tube is
Both the tube bundle difficult to replace.
and the shell side can be
inspected and cleaned No single tube pass or true countercurrent
mechanically. flow is possible.

Less costly than floating Tube wall thickness at the U-bend is thinner
head or packed floating than at straight portion of the tubes.
head designs.
Draining of tube circuit is difficult when
positioned with the vertical position with the
head side upward.
Figure 1.2. Fixed-tube heat exchanger ([1]).

Figure 1.3. Floating-head heat exchanger (non-pull through type) [1].


Figure 1.4. Removable U-tube heat exchanger [1].
Typical parts and connections shown in Figures 1.2, 1.3 and 1.4 (IS: 4503-1967) are
summarized below.
1. Shell 16. Tubes (U-type)
2. Shell cover 17. Tie rods and spacers
3. Shell flange (channel end) 18. Transverse (or cross) baffles or support plates
4. Shell flange (cover end) 19. Longitudinal baffles
5. Shell nozzle or branch 20. Impingement baffles
6. Floating tube sheet 21. Floating head support
7. Floating head cover 22. Pass partition
8. Floating head flange 23. Vent connection
9. Floating head gland 24. Drain connection
10. Floating head backing ring 25. Instrument connection
11. Stationary tube sheet 26. Expansion bellows
12. Channel or stationary head 27. Support saddles
13. Channel cover 28. Lifting lugs
14. Channel nozzle or branch 29. Weir
15. Tube (straight) 30. Liquid level connection
Lecture 2: Thermal Design Considerations
The flow rates of both hot and cold streams, their terminal temperatures and fluid
properties are the primary inputs of thermal design of heat exchangers.
1.2. Thermal design considerations
Thermal design of a shell and tube heat exchanger typically includes the determination of
heat transfer area, number of tubes, tube length and diameter, tube layout, number of
shell and tube passes, type of heat exchanger (fixed tube sheet, removable tube bundle
etc), tube pitch, number of baffles, its type and size, shell and tube side pressure drop etc.
1.2.1. Shell
Shell is the container for the shell fluid and the tube bundle is placed inside the shell.
Shell diameter should be selected in such a way to give a close fit of the tube bundle.
The clearance between the tube bundle and inner shell wall depends on the type of
exchanger ([2]; page 647). Shells are usually fabricated from standard steel pipe with
satisfactory corrosion allowance. The shell thickness of 3/8 inch for the shell ID of 12-24
inch can be satisfactorily used up to 300 psi of operating pressure. (20 barg)
1.2.2. Tube
Tube OD of ¾ and 1‟‟ are very common to design a compact heat exchanger. The most
efficient condition for heat transfer is to have the maximum number of tubes in the shell
to increase turbulence. The tube thickness should be enough to withstand the internal
pressure along with the adequate corrosion allowance. The tube thickness is expressed in
terms of BWG (Birmingham Wire Gauge) and true outside diameter (OD). The tube
length of 6, 8, 12, 16, 20 and 24 ft are preferably used. Longer tube reduces shell
diameter at the expense of higher shell pressure drop. Finned tubes are also used when
fluid with low heat transfer coefficient flows in the shell side. Stainless steel, admiralty
brass, copper, bronze and alloys of copper-nickel are the commonly used tube materials:
1.2.3. Tube pitch, tube-layout and tube-count
Tube pitch is the shortest centre to centre distance between the adjacent tubes. The tubes
are generally placed in square or triangular patterns (pitch) as shown in the Figure 1.5.
The widely used tube layouts are illustrated in Table 1.2.
The number of tubes that can be accommodated in a given shell ID is called tube count.
The tube count depends on the factors like shell ID, OD of tube, tube pitch, tube layout,
number of tube passes, type of heat exchanger and design pressure.
1.2.4. Tube passes
The number of passes is chosen to get the required tube side fluid velocity to obtain
greater heat transfer co-efficient and also to reduce scale formation. The tube passes vary
from 1 to 16. The tube passes of 1, 2 and 4 are common in application. The partition built
into exchanger head known as partition plate (also called pass partition) is used to direct
the tube side flow.
Table 1.2. Common tube layouts.

Tube OD, in Pitch type Tube pitch, in


34 Square 1
1 11
4
34 Triangular 15
16
34 1

+
+ + +
Flow Flow Flow + +

+ + + + +
Pitch

Pitch Pitch

a). Square b). Triangular c). Rotated square

Figure 1.5. Heat exchanger tube-layouts.


1.2.5. Tube sheet
The tubes are fixed with tube sheet that form the barrier between the tube and shell fluids.
The tubes can be fixed with the tube sheet using ferrule and a soft metal packing ring.
The tubes are attached to tube sheet with two or more grooves in the tube sheet wall by
„tube rolling‟. The tube metal is forced to move into the grooves forming an excellent
tight seal. This is the most common type of fixing arrangement in large industrial
exchangers. The tube sheet thickness should be greater than the tube outside diameter to
make a good seal. The recommended standards (IS:4503 or TEMA) should be followed
to select the minimum tube sheet thickness.
1.2.6. Baffles
Baffles are used to increase the fluid velocity by diverting the flow across the tube bundle
to obtain higher transfer co-efficient. The distance between adjacent baffles is called
baffle-spacing. The baffle spacing of 0.2 to 1 times of the inside shell diameter is
commonly used. Baffles are held in positioned by means of baffle spacers. Closer baffle
spacing gives greater transfer co-efficient by inducing higher turbulence. The pressure
drop is more with closer baffle spacing. The various types of baffles are shown in Figure
1.6. In case of cut-segmental baffle, a segment (called baffle cut) is removed to form the
baffle expressed as a percentage of the baffle diameter. Baffle cuts from 15 to 45% are
normally used. A baffle cut of 20 to 25% provide a good heat-transfer with the reasonable
pressure drop. The % cut for segmental baffle refers to the cut away height from its
diameter. Figure 1.6 also shows two other types of baffles.

Shell

a). Cut-segmental baffle

Shell Doughnut
Disc

b). Disc and doughnut baffle

Baffle
Orifice

c). Orifice baffle


Figure 1.6. Different type of heat exchanger baffles: a). Cut-segmental baffle, b). Disc and doughnut baffle, c). Orifice baffle
1.2.7. Fouling Considerations
The most of the process fluids in the exchanger foul the heat transfer surface. The
material deposited reduces the effective heat transfer rate due to relatively low thermal
conductivity. Therefore, net heat transfer with clean surface should be higher to
compensate the reduction in performance during operation. Fouling of exchanger
increases the cost of (i) construction due to oversizing, (ii) additional energy due to poor
exchanger performance and (iii) cleaning to remove deposited materials. A spare
exchanger may be considered in design for uninterrupted services to allow cleaning of
exchanger.
The effect of fouling is considered in heat exchanger design by including the tube side
and shell side fouling resistances. Typical values for the fouling coefficients and
resistances are summarized in Table 1.3. The fouling resistance (fouling factor) for
petroleum fractions are available in the text book ([3]; page 845).
Table 1.3. Typical values of fouling coefficients and resistances ([2]; page 640).

Fluid Coefficient (W.m .°C ) Resistance (m .°C.W-1)


-2 -1 2

River water 3000-12,000 0.0003-0.0001


Sea water 1000-3000 0.001-0.0003
Cooling water (towers) 3000-6000 0.0003-0.00017
Towns water (soft) 3000-5000 0.0003-0.0002
Towns water (hard) 1000-2000 0.001-0.0005
Steam condensate 1500-5000 0.00067-0.0002
Steam (oil free) 4000- 10,000 0.0025-0.0001
Steam (oil traces) 2000-5000 0.0005-0.0002
Refrigerated brine 3000-5000 0.0003-0.0002
Air and industrial gases 5000-10,000 0.0002-0.000-1
Flue gases 2000-5000 0.0005-0.0002
Organic vapors 5000 0.0002
Organic liquids 5000 0.0002
Light hydrocarbons 5000 0.0002
Heavy hydrocarbons 2000 0.0005
Boiling organics 2500 0.0004
Condensing organics 5000 0.0002
Heat transfer fluids 5000 0.0002
Aqueous salt solutions 3000-5000 0.0003-0.0002
1.2.8. Selection of fluids for tube and the shell side
The routing of the shell side and tube side fluids has considerable effects on the heat
exchanger design. Some general guidelines for positioning the fluids are given in Table
1.4. It should be understood that these guidelines are not ironclad rules and the optimal
fluid placement depends on many factors that are service specific.
Table 1.4. Guidelines for placing the fluid in order of priority
Tube-side fluid Shell-side fluid
Corrosive fluid Condensing vapor (unless corrosive)
Cooling water Fluid with large temperature difference (>40°C)
Fouling fluid
Less viscous fluid
High-pressure steam
Hotter fluid
Lecture 3: Process (Thermal) Design Procedure
1.3. Process (thermal) design procedure
Shell and tube heat exchanger is designed by trial and error calculations. The main steps
of design following the Kern method are summarized as follows:
Step #1. Obtain the required thermophysical properties of hot and cold fluids at the
caloric temperature or arithmetic mean temperature. Calculate these properties at the
caloric temperature if the variation of viscosity with temperature is large. The detailed
calculation procedure of caloric temperature available is in reference [3] (page 93-99).
Step #2. Perform energy balance and find out the heat duty ( Q ) of the exchanger.
Step #3. Assume a reasonable value of overall heat transfer coefficient (Uo,assm). The
value of Uo,assm with respect to the process hot and cold fluids can be taken from the
books ([3] page 840 Table 8; [4] page 297 Table 8.2.)
Step #4. Decide tentative number of shell and tube passes ( n p ). Determine the LMTD

and the correction factor FT ([3] page 828-833 Figs. 18-23; [4] page 292 Figs. 8.10a &
8.10b). FT normally should be greater than 0.75 for the steady operation of the
exchangers. Otherwise it is required to increase the number of passes to obtain higher F T
values.

Step #5. Calculate heat transfer area (A) required: A  Uo ,assm .LMTD
Q
. FT (1.1)

Step #6. Select tube material, decide the tube diameter (ID= d i , OD = d o ), its wall
thickness (in terms of BWG or SWG) and tube length ( L ). Calculate the number of tubes
A
( nt ) required to provide the heat transfer area (A): nt  (1.2)
 do L
.
4m(n p / nt )
Calculate tube side fluid velocity, u  (1.3)
 di 2
.
4 m(n p / nt )
If u <1 m/s, fix n p so that, Re   104 (1.4)
 di 
.
Where, m,  and  are mass flow rate, density and viscosity of tube side fluid. However,
this is subject to allowable pressure drop in the tube side of the heat exchanger.
Step #7. Decide type of shell and tube exchanger (fixed tubesheet, U-tube etc.). Select
the tube pitch (PT), determine inside shell diameter ( Ds ) that can accommodate the

calculated number of tubes ( nt ). Use the standard tube counts table for this purpose. Tube
counts are available in standard text books ([3] page 841-842 Table 9; [4] page 308
Table 8.3).
Step #9. Assign fluid to shell side or tube side (a general guideline for placing the fluids
is summarized in Table 1.4). Select the type of baffle (segmental, doughnut etc.), its size
(i.e. percentage cut, 25% baffles are widely used), spacing ( B ) and number. The baffle
spacing is usually chosen to be within 0.2 Ds to Ds .

Step #10. Determine the tube side film heat transfer coefficient ( hi ) using the suitable
form of Sieder-Tate equation in laminar and turbulent flow regimes.
Estimate the shell-side film heat transfer coefficient ( ho ) from:
1 0.14

h D  c  3   
jH  o e     (1.5)
k  k   w 


You may consider,  1.0
w
Select the outside tube (shell side) dirt factor ( Rdo ) and inside tube (tube side) dirt factor

( Rdi ) ([3] page 845 Table 12).

Calculate overall heat transfer coefficient ( U o,cal ) based on the outside tube area (you

may neglect the tube-wall resistance) including dirt factors:


1
1 A  d d  A0  1  A0 
U o,cal    Rdo  0  0 i      Rdi  (1.6)
 ho Ai  2kw  Ai  hi  Ai 
U o,cal  U o,assm
Step #11. If 0   30% , go the next step # 12. Otherwise go to step #5,
U o ,assm

calculate heat transfer area (A) required using U o,cal and repeat the calculations starting

from step #5.


If the calculated shell side heat transfer coefficient ( ho ) is too low, assume closer baffle

spacing ( B ) close to 0.2 Ds and recalculate shell side heat transfer coefficient. However,
this is subject to allowable pressure drop across the heat exchanger.
Step #12. Calculate % overdesign. Overdesign represents extra surface area provided
beyond that required to compensate for fouling. Typical value of 10% or less is
acceptable.
A - Areqd
% Overdesign = 100 (1.7)
Areqd

A = design area of heat transfer in the exchanger; Areqd = required heat transfer area.

Step #13. Calculate the tube-side pressure drop ( PT ): (i) pressure drop in the straight

section of the tube (frictional loss) ( Pt ) and (ii) return loss ( Prt ) due to change of
direction of fluid in a „multi-pass exchanger‟.
Total tube side pressure drop: PT = Pt + Prt (1.8)

Step #14. Calculate shell side pressure drop ( PS ): (i) pressure drop for flow across the

tube bundle (frictional loss) ( Ps ) and (ii) return loss ( Prs ) due to change of direction of
fluid.
Total shell side pressure drop: PS = Ps + Prs (1.9)
If the tube-side pressure drop exceeds the allowable pressure drop for the process system,
decrease the number of tube passes or increase number of tubes per pass. Go back to step
#6 and repeat the calculations steps.
If the shell-side pressure drop exceeds the allowable pressure drop, go back to step #7
and repeat the calculations steps.
Step #15. Upon fulfillment of pressure drop criteria, go mechanical design. Refer
module # 2 for the details of mechanical design.
1.4. Design problem
The above design procedure is elaborated through the calculation of the following
example
Lecture 4: Design Problem
Problem Statement:
150000 lb per hour of kerosene will be heated from 75 to 120°F by cooling a gasoline
stream from 160 to 120°F. Inlet pressure will be 50 psia for each stream and the
maximum pressure drop of 7 psi for gasoline and 10 psi for kerosene are permissible.
Published fouling factors for oil refinery streams should be used for this application.
Design a shell and tube heat exchanger for this service.
PART 1: THERMAL DESIGN:
(PART 2: Mechanical design provided in module #2)
Given data:
Hot fluid inlet temperature (T1)= 160°F
Hot fluid outlet temperature (T2) = 120°F
Cold fluid inlet temperature (t1) = 75°F
Cold fluid outlet temperature (t2) = 120°F
Fouling factor of hot fluid (Rdg) = 0.0005 (for gasoline)
Fouling factor of cold fluid (Rdk) = 0.001 (for kerosene)
Pinlet (for hot fluid) = 50 psia
Pinlet (for cold fluid) = 50 psia
∆pmax (for hot fluid) = 7 psi
∆pmax (for cold fluid) = 10 psia
.
Mass flow rate of cold fluid ( m k ) = 150000 lb.h-1
(Subscripts „k’ for kerosene and „g‟ for gasoline)
I. Calculation of caloric temperature

For the calculation of caloric temperature please refer [3] (page 827).
t T t 120  70
r c  2 1  1.25
th T1  t2 160  120
°API of hot fluid=76°; Therefore Kc = 1; Fc = 0.455
(The caloric temperature factor, Fc with °API as a function Kc is available in reference
[3] (page 827).
Caloric temperature of the hot fluid, Thc  T2  FC (T1  T2 )
=120+0.455×(160-120)
=138.2°F
Caloric temperature of the cold fluid, Tcc  t1  FC (t2  t1 )
=75+0.455×(120-75)
=95.475°F
II. Fluid properties at caloric temperature
Viscosity:
76°API gasoline, μg=0.2cp (0.484 lb.ft-1.h-1)
46°API kerosene, μk =1.6 cp (3.872 lb.ft-1.h-1)
Density:
ρg=685 kg.m-3 (42.7 lb.ft-3)
ρk=800 kg.m-3 (49.8 lb.ft-3)
Thermal conductivity:
kg=0.075 Btu h-1ft-1 °F-1
kk=0.083 Btu h-1ft-1 °F-1
Specific heat capacity:
Cg = 0.57 Btu lb-1ft-1
Ck = 0.48 Btu lb-1ft-1
Specific gravity:
Sg = 0.685
Sk = 0.80
III. Energy balance
Assume no heat loss to the surrounding.
. .
Qg  Qk  mk Ck (t2  t1 )  mg Cg (T1  T2 ) =3240000 Btu/h
.
⇒150000×0.48×(120-75)= m g ×0.57×(160-120)
.
⇒ mg = 142105 lb h-1
IV. Calculation of heat transfer area and tube numbers
Iteration #1:
The first iteration is started assuming 1 shell pass and 2 tube pass shell and tube
exchanger with following dimensions and considerations.
 Fixed tube plate
 1´´ OD tubes (do) (14 BWG) on 1¼´´ square pitch (PT)
 Outer diameter of tube= 1´´
 Tube length (Lt) =16´
 Tube ID (di) = 0.834´´
 Fluid arrangement: Kerosene is placed in tube side because it has the higher
fouling tendency
The log mean temperature correction factor (FT) for 1-2 shell and tube exchanger:

= 0.802
T1  T2 160  120 t  t 120  75
where, R    0.889 ; S  2 1   0.529
t2  t1 120  75 T1  t1 160  75

LMTD
T2  T1    t2  t1 
 T  T1 
ln  2 
 t2  t1 


160  120   120  75 
 160  120 
ln  
 120  75 
= 42.75 °F
Determining the heat transfer area (‘A’):
The value of overall heat transfer coefficient (Uo,assm) of 45 Btu h-1ft-2 °F-1 is assumed to
initiate the design calculation for the kerosene and gasoline heat exchanger. The
approximate range of overall heat transfer coefficient depending on the hot and cold fluid
can be found out from text books ([3] page 845).
Q
A
U assm LMTD  FT (1.1)
.
m g C g T1  T2 

U assm  LMTD  FT
142105  0.57  160  120 

45  42.75  0.802
= 2100 ft2
Calculating no. of tubes (nt):
A
nt  (1.2)
 d o Lt
2100
nt  = 502
 1 
    16
 12 
n t = 518 is taken corresponding to the closest standard shell ID of 35΄΄ for fixed tube
sheet, 1-shell and 2-tube pass exchanger with 1΄΄ tube OD on 1¼΄΄ square pitch. You
may refer to standard heat transfer books ([3] page 841-842) for the selection of suitable
shell ID.
Check for fluid velocity:
.
4 mk (n p / nt )
Re  (1.4)
 di 

4  (150000)  2
Re  518
  0.834 12
 3.872

= 2740.2<104
As Re<<104, the design parameters and considerations needs to be revised to meet
the Reynolds number criteria subject to allowable pressure drop in the tube side of
the heat exchanger.
Iteration #2:
Assumptions:
 Fixed tube plate type
 1΄΄ OD tubes (14 BWG) on 1¼΄΄ square pitch (PT)
 Tube length (Lt) = 24΄ (the tube length is increased from 16΄)
 1 shell pass-6 tube pass (tube passes is increased to 6 from 2)

Tube ID=0.834΄΄

Flow area per tube=0.546 inch2
No. of tubes:
A
nt  (1.2)
 d o Lt
2100
nt  =335
 1 
     24
 12 
n t = 368 is taken corresponding to the closest standard shell ID of 31΄΄ for fixed tube
sheet, 1-shell and 6-tube pass exchanger with 1΄΄ tube OD on 1¼΄΄ square pitch. The
tube-counts are available in heat transfer text book ([3] Table 9 & 10 page 841-843).
Fluid velocity:
.
4 mk (n p / nt )
Re  (1.4)
 di 

4  (150000)  6
Re  368
  0.834 12
 3.872

= 11571.4>104 corresponding to np=6.


Re k
u (1.3)
di  k

11571.4  3.872

0.834  49.8
12
= 12945.15 ft/h (3.59 ft/s)
= 1.04 m/s (so the design velocity is within the acceptable range).
V. Determination of heat transfer co-efficient
Tube side heat transfer co-efficient (hi):
1 0.14
hd  C  3  
jH  i i  k k    (1.5)
k  kk   w 

jH=42 for the tube side fluid at Re=11571.4 ([3] page 834)

(Let‟s consider t  = 1,  = viscosity of the tube side fluid;  w = viscosity of tube
w
side fluid at wall temperature)

42 

hi 0.834
12  1
 0.48  3.872  3
 
0.083  0.083 
hi= 141.3 Btu h-1ft-1 oF-1
Shell side heat transfer co-efficient (ho):
Assumptions:
 25% cut segmental baffles
 Baffles spacing, B= 0.5DS=15.5΄΄ (half of the shell ID is selected)
  
4  PT 2  do 2 
Equivalent diameter for the shell side: De    for square pitch
4
 do
=0.082 ft
 1 1  2 
 4  PT  0.86 PT  do  
 For triangular pitch, De   
2 24
 1
 do 
 2 

CBDS
Shell side cross flow area, as  (please refer to Figure 1.6).
PT
C= Tube clearance
=PT - do
=1¼ -1=0.25″
 0.25  15.5  31 
   
as  
12  12  12 
=0.675 ft2
 1.25 
 
 12 
.
mg 142105
Mass velocity, GS  
as 0.675
=210526 lb. h-1.ft-2
DeGS
Re 
g

0.082   210526 

0.484
=35668
1/ 3 0.14
h D  C    
Now for the shell side, jH  o e  g g    (1.5)
k g  k g   w 

jH=110 for the shell side fluid at Re=35668 with 25% cut segmental baffles ([3] page

838)
1/ 3
h0 (0.082)  0.57  0.484 
110   
(0.075)  0.075 

( s  = 1 is considered for the shell side fluid)
w

ho=155.3 Btu h-1 ft-2 °F-1


Overall heat transfer co-efficient ( U o,cal ):

Fouling factor, Rdk=0.001 h ft2 °F Btu-1 for kerosene and Rdg= 0.0005 h ft2 °F Btu-1 for
gasoline is taken for this service.
1
1 A  d  di  A0  1  A0 
U o,cal    Rdg  0  0      Rdk  (1.6)
 ho Ai  2kw  Ai  hi  Ai 

Let select, Admirality brass as tube material with thermal conductivity, kw=70 Btu h-1 ft-1
°F-1.
1
  1 0.834  
 1  (1)2  12  12   (1)2  1   (1) 2 
  0.0005       
 (0.834)2  2  70   (0.834)2  141.3   (0.834)2
U o,cal 0.001
155.3 
   

U o,cal  53.5 Btu h-1 ft-2 °F-1

U o ,cal  U o ,assm 53.5  45


 100
Now, U o ,assm 45
 18.9%  30%
Therefore, the calculated overall heat transfer co-efficient is well within the design
criteria.
VI. Pressure drop calculation
VI.1. Tube side pressure drop:
Friction factor f  0.00028 144  0.04032 ft2/ft2 for Re=11571.4 ([3] page 836]

at = (no. of tubes)×(flow area per tube)/(no. of passes)

368  0.546 2
 ft
6 144
=0.232 ft2
m k 150000
Tube side mass velocity: Gt  
at 0.232
=646552 lb. h-1.ft-2
fGt 2 Lt n p
Frictional pressure drop: Pt 
7.5 1012  di Skt

0.04032  6465522  24  6

0.834
7.5 1012   0.8 1
12
=5.81 psi
Return loss Prt : (due to change in flow direction of the tube side fluid)

Gt 2
ptr  1.334 1013  2n p  1.5
Sk

 646552 
2

 1.334 10 13


 2  6  1.5
 0.8
=0.73 psi
Total tube side drop neglecting nozzle loss:
PT  Pt  Ptr (1.8)
=5.81+0.73
=6.54 psi<10 psi
Therefore the tube side pressure drop is within the maximum allowable pressure
drop of 10 psi.
VI.2. Shell side pressure drop calculation
Tube clearance, C=0.25″
Spacing, B=15.5″
as  0.675 ft2

Mass velocity, GS  210526 lb. h-1.ft-2


Re=35668
tube length 24
No of baffles, nb  =  18.6  19
baffle spacing 15.5/12
Friction factor, f  0.0017 144  0.2448 ft2/ft2 with 25% cut segmental baffles ([3]
page 839)
Shell side frictional pressure drop Ps :

fGs 2 DS  nb  1
Ps 
7.5 1012  De Skk

31
0.2376  2105262  19  1 
 12
7.5 10  0.082  0.685 1
12

=1.4 psi <7 psi

Prs  0 (in case of single shell pass flow)


Total shell side drop neglecting nozzle loss:
PS  Ps  Psr =1.4 psi (1.9)

Therefore the shell side pressure drop is within the maximum allowable pressure
drop of 7 psi.
VII. Over surface and over design
U C  U o ,cal
Over surface =
UC
ho  hio
The clean overall heat fransfer co-efficient: U C 
ho  hio
di
hio  hi  =141.3×0.834=117.8 Btu h -1 ft-2 °F-1
do

U C =66.98 Btu h -1 ft-2 °F-1

66.98  53.5
% Over surface = 100
66.98
=20% (acceptable)
Over design:
A - Areqd
% Overdesign = 100 (1.7)
Areqd

The design area of heat transfer in the exchanger ( nt =318):

1
A   do Lt nt =π× ×24×368=2312 ft2
12
The required heat transfer area (where, nt =335):

1
Areqd   do Lt nt = π× ×24×335=2105 ft2
12
% Overdesign =9.8% which is within the acceptable limit.
Refer module # 2 for the mechanical design of shell and tube heat exchanger.
Lecture 5: Shell and Tube Exchanger for Two Phase Heat Transfer

2. PROCESS DESIGN OF SHELL AND TUBE


EXCHANGER FOR TWO PHASE HEAT TRANSFER
2.1. Condenser
The change from liquid phase to vapor phase is called vaporization and the reverse phase
transfer is condensation. The change from liquid to vapor or vapor to liquid occurs at one
temperature (called saturation or equilibrium temperature) for a pure fluid compound at a
given pressure. The industrial practice of vaporization and condensation occurs at almost
constant pressure; therefore the phase change occurs isothermally.
Condensation occurs by two different physical mechanisms i.e. drop-wise condensation
and film condensation.
The nature of the condensation depends upon whether the condensate (liquid formed
from vapor) wets or does not wet the solid surface. If the condensate wets the surface and
flows on the surface in the form of a film, it is called film condensation. When the
condensate does not wet the solid surface and the condensate is accumulated in the form
of droplets, is drop-wise condensation. Heat transfer coefficient is about 4 to 8 times
higher for drop wise condensation. The condensate forms a liquid film on the bare-
surface in case of film condensation. The heat transfer coefficient is lower for film
condensation due to the resistance of this liquid film.
Dropwise condensation occurs usually on new, clean and polished surfaces. The heat
exchanger used for condensation is called condenser. In industrial condensers, film
condensation normally occurs.
2.1.1. Types of condensers
There two general types of condensers:
i. Vertical condenser
Downflow vertical condenser: The vapor enters at the top of condenser and flows
down inside tubes. The condensate drains from the tubes by gravity and vapor
induced shear (Figure 1.7).
Upflow vertical condenser: In case of upflow condenser, the vapor enters at the
bottom and flows upwards inside the tubes. The condensate drains down the tubes
by gravity only.
ii. Horizontal condenser: The condensation may occur inside or outside the
horizontal tubes (Figure 1.8). Condensation in the tube-side is common in air-
cooled condensers. The main disadvantage of this type of condenser is that the
liquid tends to build up in the tubes. Therefore the effective heat transfer co-
efficient is reduced significantly.
Figure 1.7. Downflow vertical condenser with condensation inside tube [5].
Figure 1.8. Horizontal condenser with condensation outside horizontal tubes [5].

2.1.2. Condenser design


The design of condenser is similar to a typical shell and tube exchangers. A condenser
must have a vent for removal of non-condensable gas. The non-condensable gas
decreases the heat transfer rate. Condenser usually use a wider baffle spacing of
B  D s (ID of shell) as the allowable pressure drop in shell side vapor is usually less.
Vertical cut-segmental baffles are generally used in condensers for side-to-side vapor
flow and not for top to bottom. An opening at the bottom of the baffles is provided to
allow draining of condensate.
2.1.2.1. Mean temperature difference
The condensation occurs almost at a fixed temperature (isothermally) at constant pressure
for a pure saturated vapor compound. The logarithmic mean temperature difference can
be used for condenser design. No correction factor for multiple pass condensers is
required. The logarithmic mean temperature difference:
(Tsat  t1 )  (Tsat  t2 ) (t2  t1 )
LMTD  
(T  t ) (T  t )
ln sat 1 ln sat 1
(Tsat  t2 ) (Tsat  t2 ) (1.10)
Where, Tsat= Saturation vapor temperature
t1 = Coolant inlet temperature
t2 = Coolant outlet temperature
2.1.2.2. Calculation of heat transfer co-efficient during condensation
Calculation of tube side heat transfer co-efficient (hi): The calculation of heat transfer
co-efficient for the cold fluid (coolant) can be performed similarly as discussed in design
of shell and tube heat exchanger (heat transfer without phase change). Here it is assumed
that the coolant flows the in tube side and the condensing saturated vapor flows in the
shell side. If the condensation occurs in the tube side, follow the procedure discussed in
next section for shell side calculation.
Calculation of shell-side heat transfer coefficient (condensing film heat transfer
coefficient) (ho): The Kern method is discussed here to calculate the individual heat
transfer co-efficient of the condensing fluid by trial and error calculation.
i. Assume, ho ( assm ) in the range from 100 to 300 BTU.h-1.ft-2.°F-1. The film

coefficient of condensing hydrocarbons generally varies in this range. Air-free


condensing steam has a coefficient of 1500 BTU.h-1.ft-2.°F-1.
ii. Calculate the tube wall temperature ( Tw ):

ho (Tv  TC ( avg ) )
Tw  TC ( avg ) 
(hio  ho ) (1.11)
or
ho (Tv  Tcc )
Tw  Tcc 
(hio  ho ) (1.12)
di
Where, hio  hi  ( d i tube ID and d o tube OD)
dio

TC ( avg ) = Average temperature of the cold fluid

Tcc =Caloric temperature of the cold fluid

(Tw  Tv )
iii. Calculate condensate film temperature, T f  (1.13)
2
Tv =Condensation temperature (For pure fluid compound Tv is the saturation temperature.
Average of condensation over a temperature range also can be used for non-isothermal
condensation).
iv. Calculate all thermophysical property of the condensing fluid at film temperature
( T f ).

v. Recalculate, ho ( cal ) from jH factor.

Now again set, ho ( assm)  ho (cal ) and continue the calculation till ho ( assm)  ho( cal ) .

vi. Calculate the overall heat transfer-coefficient ( U d ) including the dirt factors.
Lecture 6: Condenser and Reboiler Design
2.1.2.3. Pressure drop calculation
i. Tube side pressure drop
In case of tube side condensation:
For condensation in the tube side by taking one-half of the conventional pressure drop
relation can be used.

1 fGt 2 Lt n p 
Pt    , psi (1.14)
2  7.5 1012  di Stt 
Where,
f = friction factor
Gt =mass velocity [lb. h-1.ft-2]
Lt =Tube length [ft]
n p =Number of tube passes
d i =Tube ID [ft]
St =Specific gravity of the tube side fluid
t =Viscosity correction factor

( t  = 1,  = viscosity of the tube side fluid;  w = viscosity of water)
w
ii. Shell side pressure drop
In case of shell side condensation: Similarly for condensation in the shell side:

1  fGs DS  nb  1 
2

Ps    , psi (1.15)


2  7.5 1012  De S ss 
Subscript „s‟ indicates shell side fluid.
nb = number of baffles

De = Equivalent diameter for the shell [ft]


Calculate all fluid property at film temperature T f . No return loss calculation is

required for the condensing fluid.


In case of non-condensing fluid (single phase flow), use the conventional pressure
drop relation.
2.1.3. De-superheating and sub-cooling
De-superheating is different from condensation of a saturated vapor. The sensible heat
should be removed first to de-superheat the vapor to obtain the saturated vapor. Similarly,
the saturated liquid is to be further cooled down (sub-cooled) by extracting sensible heat
below the boiling point. The temperature profile is shown in Figure 1.9 for the
condensation of superheated vapor to obtain the sub-cooled liquid from the same
exchanger. The mean temperature difference and heat transfer coefficient should be
calculated individually for each section if the degree of superheat/ sub-cool is large. The
weighted mean temperature difference and overall transfer co-efficient can be used to
design the condensers if heat load due to sensible heat transfer in each unit about 25% of
latent heat transfer. Otherwise, it is convenient to design separate de-superheater and sub-
cooling exchangers. The calculations for detail study can be found out in reference [3]
(page 283-285).

Tsuperheat

Tsat
Temperature

Tsub-cool

Desuper

Condensation Sub-
-heating cooling

LMTDdesuperh LMTDcondensatio LMTDsubcooli


eat n ng
Heat transfer 

Figure 1.9. Condensation with de-superheating and sub-cooling [2].


Practice problem:
Design a horizontal condenser for the condensation of 45,000 lb/h of almost pure normal
propyl alcohol available at 15 psig. At this pressure, the boiling point of n-propyl alcohol
is 244°F. Water available in the temperature range of 95 to 120°F can be as the coolant.
The maximum pressure drop of 2 psi and 10 psi is permissible for the vapor phase and
water respectively.
2.2. Reboilers
2.2.1. Classification of reboilers
There are three major types of reboilers:
i. Thermosyphon natural circulation reboiler: The boiling occurs inside the tubes
in vertical thermosyphon reboiler and inside shell in horizontal thermosyphon
reboiler (Figure 1.10). In vertical thermosyphon reboiler, the liquid circulation
occurs due to density difference between vapor-liquid mixture (two phase) in the
exchanger from the reboiler and the liquid through the downcomer to the reboiler.
Advantages: most economical because no pump is required.
Limitations: not suitable for heavily viscous fluid; high construction cost for the
installation of the column base at suitable elevation to get thermosyphon effect;
not suitable for low temperature difference processes due to boiling point
elevation imposed by static head.

Figure 1.10. Thermosyphon reboiler [5]. (a) Horizontal thermosyphon reboiler. (b) Vertical thermosyphon reboiler
ii. Forced circulation reboiler: The liquid is fed by means of a pump. Forced
circulation reboilers with vertical or horizontal tubes boiling may be designed.
Forced circulation reboilers are similar to vertical thermosiphon reboilers, except
the pump is used for the circulation of the liquid and the hot liquid flows inside
column. To calculate the heat transfer coefficient it is generally assumed that, heat
is transferred only by forced convection. The usual method of shell and tube
exchanger design can be used.
Advantage: suitable for viscous and highly fouling fluids.
Disadvantage: high pumping and maintenance cost; pump is required to circulate
the boiling liquid through the tubes and back into the column.
iii. Kettle reboiler: The tube bundle is immerged in a pool of liquid at the base of the
column in an oversize shell (Figure 1.11). Kettle reboiler is also called a
“submerged bundle reboiler”. The height of the tube bundle is usually 40-60% of
the shell ID. The submergence of the tube bundle is assured by an overflow weir
at height of typically 5-15 cm from the upper surface of topmost tubes.
Advantage: suitable for vacuum operation and high vaporization rate up to about
80% of the feed.
Limitations: low heat transfer rate than other types as there is no liquid circulation
(low velocity); not appropriate for fouling fluids; kettle reboiler is not suitable for
heat sensitive materials as it has higher residence time.
The bundle diameter Db, can be obtained from the empirical equation ([2] page
647-649 ):
1/ n1
n 
Db  do  t  (1.16)
 K1 
where, Db = bundle diameter [mm], nt = number of tubes, d o = tube outside

diameter [mm]. The values of the constants K1 and n1 are in Table 1.5.
Table 1.5. Constants used to calculate the tube bundle diameter.

Pitch type Constants Number of tube passes ( nt )


1 2 4 6 8
Triangular K1 0.319 0.249 0.175 0.0743 0.0365
( PT  1.25do ) n1 2.142 2.207 2.285 2.499 2.675
Square K1 0.215 0.156 0.158 0.0402 0.0331
( PT  1.25do ) n1 2.207 2.291 2.263 2.617 2.643

Figure 1.11. Kettle type reboiler [1].

2.2.2. Design of kettle reboiler


The Kern method for designing of Kettle reboiler for isothermal boiling is summarized
below. It is assumed that the degree of sub-cooling and super-heating of the cold fluid is
negligible i.e. vaporization of close boiling compounds with negligible super-heating of
vapors formed.
i. Make energy balance and determine the heat duty.
ii. Calculate of fluid property at the caloric temperature (or at arithmetic mean
temperature) as already shown.
iii. Follow the same guideline and design requirements for shell containing the
vaporing liquid.
iv. Calculation of heat transfer co-efficient
Calculation of individual heat transfer co-efficient hot fluid: The calculation
of heat transfer co-efficient of the hot fluid can be performed similarly as in case
of design of shell and tube heat exchanger for single phase.
Calculation of individual heat transfer coefficient of the boiling liquid: The
Kern method is discussed here to calculate the individual heat transfer co-efficient
of the boiling liquid by trial and error procedure.
Kern [2] recommends that the maximum allowable vaporizing film coefficients:
- 300 Btu/h.ft2 °F for natural or forced circulation vaporizing organics.
- 1000 Btu/h.ft2 °F for natural or forced circulation vaporizing aqueous solution
of low concentration.
The maximum allowable heat flux:
- 20000 Btu/(h)ft2) for forced circulation reboilers and 12000 Btu/(h)ft2) for
natural circulation reboilers vaporizing organics.

- 30000 Btu/(h)ft2) for both forced or natural circulation reboilers vaporizing


aqueous solution.
Assume that h(assm) = 300 Btu/h.ft2 °F for organics or 1000 Btu/h.ft2 °F for water.
With this assumed value, calculate the tube wall temperature ( Tw ):

hio (Thc  Th ( avg ) )


Tw  Th ( avg ) 
(hio  ho ) (1.17)
di
Where, hio  hi  ( d i tube ID and d o tube OD)
dio

Th ( avg ) = Average temperature of the hot fluid

Thc =Caloric temperature of the hot fluid


Now, re-determine hcal (latent heat transfer) from the Figure 1.12 corresponding
to (Tw  t ) . ( t is the cold fluid boiling temperature).

Continue the calculation till, hcal  h( assm ) .

If the calculated hcal is greater than the maximum heat transfer co-efficient of 300

Btu/h.ft2 °F for organics and 1000 Btu/h.ft2 °F for water, take hcal = 300 Btu/h.ft2

°F for organics and hcal =1000 Btu/h.ft2 °F for water.

Calculate the overall heat transfer-coefficient ( U d ) including the dirt factors.


1000

Heat transfer co-efficient (h), Btu/(hr)(ft )( F)


Maximum for water

o
500

2
Maximum for organics

r
s fe
an
t tr
100

ea
th n
e c t io
te n

nv
c e d co
La

y fo r
a n s fe r b
a t tr
s i b le h e
Sen

20
4 10 50 100 200
o
(Tw-t), F
Temperature difference between tube wall and boiling liquid
Figure 1.12. Natural circulation boiling and sensible heat transfer [3].

v. Decide type of exchanger i.e. fixed tube sheet or U- shell (use U-tube reboiler for
large temperature difference), tube size (diameter, length, tube pitch), layout,
effective tube length. A tube pitch of between 1.5 to 2 times the tubes OD should
be used to avoid vapor blanketing.
Q A
vi. Calculate exchanger area ( A  ) and number of tubes ( nt  ).
U d ( LMTD)  do Lt
The number of tubes should be calculated based on the effective tube length for
U-tube reboilers. The effective tube length is less than physical tube length due to
U-bend.
Q
vii. Calculate the heat flux= [Btu/(h.ft2)]. This value should be less than the
A
maximum heat flux of 20000 Btu/(h)ft2) for forced circulation reboilers
vaporizing organics and 30000 Btu/(h)ft2) for both forced or natural circulation
reboilers vaporizing aqueous solution. Otherwise, go to step # v, repeat the
calculation until within the allowable limits.
viii. Check for allowable vapor velocity ( uv ) ([3] page 749):

The maximum vapor velocity uv (m/s) at the liquid surface should be less than
that given by the expression below to avoid too much entrainment.
1/ 2
   v 
uv  0.2  l 
 v  (1.18)
where, l = liquid density and, l = vapor density
If this criterion is not satisfied, go to step # v and revise the calculation.
ix. Pressure drop calculation
Tube side pressure drop (hot fluid): The pressure drop calculation of the hot fluid
can be carried out as already presented.
Shell side pressure drop (vaporizing liquid): There will be negligible hydrostatic
head for the flow of liquid from the column to reboilers (low circulation velocity) if
the liquid level above the tube bundle is not too high. Therefore, shell side pressure
drop may be considered negligible.
x. Calculate over surface and over design
xi. Go for mechanical design
Design problem:
Gasoline (65°API gravity) flow rate of 60,000 lb/h with a small boiling range at 400°F is
to be vaporized to form 37,050 lb/h vapor at an operating pressure of 200 psig. Use gas
oil (30°API gravity) in the temperature range from 600 to 500°F at 120 psig operating
pressure as the heating medium. A tube side pressure drop of 10 psi is allowable. Design
a suitable Kettle reboiler to serve the purpose.

You might also like