0% found this document useful (0 votes)
330 views61 pages

EE251 Notes1 - Short Circuit Calculations

The document discusses short circuit analysis and fault studies in electric power systems. It covers topics such as sources of fault currents, types of faults including three-phase, line-to-line and others, and modeling faults using sequence networks. An example problem is presented to calculate fault currents at different buses in a sample four-bus power system.

Uploaded by

Prime Mover
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
330 views61 pages

EE251 Notes1 - Short Circuit Calculations

The document discusses short circuit analysis and fault studies in electric power systems. It covers topics such as sources of fault currents, types of faults including three-phase, line-to-line and others, and modeling faults using sequence networks. An example problem is presented to calculate fault currents at different buses in a sample four-bus power system.

Uploaded by

Prime Mover
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 61

Competency Training and Certification Program in Electric Power System Engineering

Distribution System Modeling and Analysis

Training Course in

Short Circuit Analysis

U. P. NATIONAL ENGINEERING CENTER


NATIONAL ELECTRIFICATION ADMINISTRATION

Analysis of Faulted Power System


by Symmetrical Components

 Sources of Short Circuit Currents


 Types of Fault
 The Fault Point
 Three-Phase Fault
 Single-Line-to-Ground Fault
 Line-to-Line Fault
 Double-Line-to-Ground Fault

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 2

1
Sources of Short Circuit
Currents
G
Utility

MV Fault
LV

Fault Current Contributors


Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 3

Types of Fault
Shunt Fault: Unintentional Connection between
phases or between phase and ground.
1. Single Line-to-Ground Fault
2. Line-to-Line Fault
3. Double Line-to-Ground Fault
4. Three Phase Fault

Series Fault: Unintentional Opening of phase


conductors

Simultaneous Fault
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 4

2
Types of Fault

Three Phase Line-to-Line

Double Line-to-Ground Single Line-to-Ground


Shunt Faults
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 5

The Fault Point


The system is assumed to be balanced, with
regards to impedances, except at one point called
the fault point.
F
a
b
c
Line-to-    
  Ia Ib Ic
ground V a Vb Vc Fault
voltages Currents
Ground

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 6

3
The Fault Point

Since we mentioned that various power system


components behave/respond differently to the flow
of the currents’ sequence components, it follows
that the there will be a unique power system model
for each of the sequence component. These are
called the sequence networks.
• Positive-Sequence Network
• Negative-Sequence Network
• Zero-Sequence Network

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 7

The Fault Point


The Thevenin equivalent of the power system at
the fault point is called the sequence network.
Positive Negative Zero
Sequence Sequence Sequence
F1 F2 F0
  
Ia1 Z +  Ia2 +
 Ia0 +

+ 1 V Z2 Va2 Z0 Va0
V f  Vth a1

- - - -
N1 N2 N0
      
Va1  Vth  Ia1Z1 Va2   Ia2Z2 Va0   Ia0Z0
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 8

4
Three Phase Fault

 On a balanced three phase system, the


same magnitude of fault currents will
flow in each phase of the network if a
three phase fault occurs.

 Since faults currents are balanced, the


faulted system can, therefore, be
analyzed using the single phase
representation.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 9

Three-Phase Fault
a
b
c   
   I a Z f Ib Z f I c Z f
Va Vb Vc 
Zg Ig
Ground

Note: The system is still balanced. Currents and


voltagesare positive sequence only. The ground
current I g is zero.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 10

5
Sequence Network Interconnection:
F1 F2 F0
+   
I a1 + Ia2 + I a0
 Z1
Va1 +  
Zf Va 2 Z2 Va 0 Z0
Vf
- - - -

N1 N2 N0
Sequence currents

 Vf  
I a1  I a0  I a2  0
Z1  Z f

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 11

Three Phase Fault Currents:

Vf
I a  I a 0  I a1  I a 2 
Z1  Z f

a 2V f
I b  I a 0  a I a1  aI a 2 
2

Z1  Z f

aV f
I c  I a 0  aI a1  a 2 I a 2 
Z1  Z f

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 12

6
Example:

Determine the fault current for a three phase


bolted fault in each bus for the 4 bus system
below.
G
LINE FB TB Z(p.u.)
1 Line1 1 4 j0.2

e3
Lin Line2 1 3 j0.4
Line 2

e1
Li n
Line3 1 2 j0.3
Line 5 Line 4
Line4 3 4 j0.5
2 3 4
Line5 2 3 j0.6
4-bus system

The generator is rated 100 MVA, 6.9 kV and has a


subtransient reactance of 10%. Base Values: 100 MVA, 6.9 kV

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 13

Solution:
Draw the impedance diagram

E 1.0

0.1
1
0.3 0.2
0.4

2 4
0.6 0.5
3

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 14

7
a) Fault @ Bus 4 Reduce the network
X a  X12  X 23
 0.3  0.6
-
E 1.0
 0.9
+ X a X 13
Xb 
0.1
If X a  X 13
1 (0.9)(0.4)

0.3 0.2
0.9  0.4
0.4
 0.276923
2
0.6 0.5 X c  X b  X 34
4
3
 0.276923  0.5
 0.776923
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 15

d Xc X14
X 
Xc  X14
-
(0.776923) (0.2) E 1.0

0.776923  0.2 If
 0.159055
+

Xequiv  X gen  X d 0.25905



0.1  0.159055

0.259055 100 x1000
1.0 Ibase   8367.64 A
If  3(6.9)
0.259055
I  3.860184 x 8367.64
 3.860184 p.u. f
= 32,300.63 A

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 16

8
b) Fault @ Bus 3
Xa  X23  X12
 0.3  0.6
-
E 1.0  0.9
+
Xb  X14  X34
0.1
If  0.2  0.5
1
0.3 0.2  0.7
0.4

2 0.6
3
0.5 4 Xequiv  (Xa||Xb ) ||X13
 0.198425

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 17

X Xgen  Xequiv
= 0.1  0.198425
= 0.298425 -
E 1.0
If
1.0 +
If 
0.298425 0.298425
= 3.350923 p.u.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 18

9
c) Fault @ Bus 2

Xa  X14  X34
-
E 1.0  0.2  0.5
+
 0.7
0.1
If
1
b Xa X13
0.3 0.2 X  a
0.4 X  X13
(0.7)( 0.4)
0.6 0.5 
2 3 4
0.7  0.4
 0.254545
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 19

Xc  Xb  X23
 0.254545  0.6 -
 0.854545 E 1.0
Xc X12 If +
d
X  c
X  X12 0.322047
(0.854545)( 0.3)

0.854545  0.3
 0.222047
1.0
X  Xgen  Xd If 
0.322047
 0.322047  3.095525 p.u.
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 20

10
d) Fault @ Bus 1

X  X gen
-
E 1.0  0.1
+

0.1
If 1.0
If 
0.1
1

0.3
0.4
0.2
 10.0 p.u.

0.6 0.5
2 3 4

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 21

Example: A three-phase fault occurs at point F.


Assuming zero fault impedance, find the fault
currents at fault point F. Determine the phase
currents in the line and the generator. Assume Eg =
1.0 p.u.
T1 F T2
Line
G Open

G: X1 = 40% X2 = 40% X0 = 20%


T1, T2: X = 5%
Line: X1 = X2 = 15% X0 = 35%

Note: All reactances are in per-unit of a common MVA base.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 22

11
Positive-Sequence Network:

F1

IA1 F1
j0.05 j0.15
 j0.05
Open  +
IA1L j0.6 IA1 
j0.4
+ VA1
 +  1.0
Eg Ia1g -
- -
N1
N1

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 23

Sequence Network Interconnection:

F1
The sequence fault currents
 +
j0.6 IA1   Vf
Zf I a1  
+ VA1 Z1  Z f
1.0 
- - Ia2 

N1 I a0 
The phase fault currents
Ia1 = 1.0/j0.6 = -j1.67
Ia  Ia2 = Ia0 = 0
Ia = -j1.67 = 1.67-90o
Ib  Ib = 1.4434+j0.8333 = 1.6730o
Ic  Ic = -1.4434+j0.8333 = 1.67150o

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 24

12
Single Line-to-Ground Fault
Assuming the fault is in phase a,
a
b
c  
    Ib Ic
Va Vb Vc Ia Zf

Ground

 
Boundary Conditions: (1) Va  Z f I a
 
(2) I  I  0
b c

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 25

Transformation: From (2), we get


 
I 012  A1I abc
  
I a0 1 1 1 Ia Ia
 1 1 
I a1 =
 3
1 a a2 0 = 3 Ia
Ia2 1 a2 a 0 Ia
   
which means Ia0  Ia1  Ia2  1
3
Ia
From (1), we get
     
Va 0  Va1  Va 2  Z f ( I a 0  I a1  I a 2 )
or    
Va 0  Va1  Va 2  3Z f I a 0

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 26

13
Sequence Network Interconnection:

F1 F2 F0
+  +  + 
 Z1 I a1  Ia2  I a0
Va1 +  Va 2 Va0 Z0 3Zf
Z2
Vf
- - - -

N1 N2 N0

The sequence fault currents


   Vf
I a 0  I a1  I a 2 
Z 0  Z1  Z 2  3Z f

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 27

Single-Line-to-Ground Phase Fault Currents:

3V f
I a  I a 0  I a1  I a 2 
Z1  Z 2  Z 0  3Z f

Ib  0

Ic  0

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 28

14
Example 2: A single line-to-ground fault occurs at
point F. Assuming zero fault impedance, find the
phase currents in the line and the generator.
Assume Eg = 1.0 p.u.
T1 F T2
Line
G Open

G: X1 = 40% X2 = 40% X0 = 20%


T1, T2: X = 5%
Line: X1 = X2 = 15% X0 = 35%

Note: All reactances are in per-unit of a common


MVA base.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 29

Positive-Sequence Network:

F1

IA1 F1
j0.05 j0.15
 j0.05
Open  +
IA1L j0.6 IA1 
j0.4
+ VA1
 +  1.0
Eg Ia1g -
- -
N1
N1
   
Note: IA1L  IA1 but IA1L  Ia1g

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 30

15
Negative-Sequence Network:

F2

IA 2 F2
j0.05 j0.15
Open  +
 j0.05 IA 2
 IA2L 
Ia2g j0.4 j0.6 VA2

-
N2
N2

   
Note: IA2L  IA2 but IA2L  Ia2g

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 31

Zero-Sequence Network:

F0

IA 0 F0
j0.05 j0.35
 Open  +
Ia0g  j0.05 IA 0
IA0L 
j0.2 j0.044 VA0

N0 N0

  
Note: IA0L  IA0 and Ia0g  0

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 32

16
Sequence Network Interconnection:
F1 F2 F0
  
J0.6 IA1 IA 2 IA 0
+
J0.6 J0.044
1.0
-

N1 N2 N0

Sequence Fault Currents


   1.0
IA0  IA1  IA2 
j(0.6  0.6  0.044)
  j0.804 p.u.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 33

Phase Fault Currents


 
IA  3IA0   j2.411 p.u.
 
IB  IC  0
Sequence Currents in the Transmission Line
 
IA1L  IA1   j0.804 p.u.
 
IA2L  IA2   j0.804 p.u.
 0.05 
IA0L  IA0   j0.089 p.u.
0.05  0.4
Phase Currents in the Transmission Line
   
IAL  IA0L  IA1L  IA2L   j1.696 p.u.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 34

17
   
IBL  IA0L  a2IA1L  aIA2L  j0.714 p.u.
ICL  IA0L  a IA1L  a2 IA2L  j0.714 p.u.
Sequence Currents in the Generator: Using the 30o
phase shift,
 
Ia1g  IA1L   30o  0.804  120o p.u.
 0.402  j0.696 p.u.
 
Ia2g  IA2L   30o  0.804  60o p.u.
  0.402  j0.696 p.u.
Ia0g  0
Phase Currents in the Generator
   
Iag  Ia0g  Ia1g  Ia2g   j1.392 p.u.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 35

   
Ibg  Ia0g  a2 Ia1g  aIa2g  j1.392 p.u.
   
Icg  Ia0g  aIa1g  a2 Ia2g  0

Three-line Diagram:

j1.392 T1 j1.696 j0.714 T2


a a A A
X1 H1 H1
X3 j2.411
c
C C
0 X2 H3 H2 B j0.714 H3 H2 B
b b
j1.392
j0.714
0 j0.268 j2.143

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 36

18
Line-to-Line Fault
Assuming the fault is in phases b and c,
a
b
c   
   Ia Ib Ic
Va Vb Vc
Zf
Ground

Boundary Conditions: (1) a  0 
I
(2) I b   I c
  
(3) Vb  Vc  I b Z f

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 37

Transformation: From (1) and (2), we get



I 012  A1I abc

I a0 1 1 1 0 0
 1  1 
I a1 = 1 a a2 Ib = (a  a 2 ) I b
 3  3 
Ia2 1 a2 a  Ib (a 2  a) I b

which means 
I a0  0

   
I a1   I a 2  13 (a  a 2 ) I b  j 1
3
Ib

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 38

19
From (3), we get
  
(Va 0  a 2Va1  aVa 2 )
     
 (Va 0  aVa1  a 2Va 2 )  ( I a 0  a 2 I a1  aI a 2 )Z f
  
Since I a 0  0 and I a1   I a 2 , we get
  
(a 2  a)Va1  (a  a 2 )Va 2  (a 2  a) I a1Z f
or
  
Va1  Va 2  I a1Z f

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 39

Sequence Network Interconnection:


F1 Zf F2 F0
+  +  
 Z1 I a1  Ia2 I a0
Va1 + Va 2
Z2 Z0
Vf
- - -

N1 N2 N0
The sequence fault currents

I a0  0
  Vf
I a1   I a 2 
Z1  Z 2  Z f

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 40

20
Line-to-Line Phase Fault Currents:

Ia  0
I b  I a 0  a 2 I a1  aI a 2
 0  a 2 I a1  a I a1   (a 2  a) I a1   jI a1
Vf
Ib   j 3
Z1  Z 2  Z f

Vf
Ic   j 3
Z1  Z 2  Z f

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 41

Example: A line-to-line fault occurs at point F.


Assuming zero fault impedance, find the fault
currents at fault point F. Assume Eg = 1.0 p.u.

T1 F T2
Line
G Open

G: X1 = 40% X2 = 40% X0 = 20%


T1, T2: X = 5%
Line: X1 = X2 = 15% X0 = 35%

Note: All reactances are in per-unit of a common MVA base.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 42

21
Sequence Network Interconnection:
F1 F2 F0
  
J0.6 IA1 IA 2 IA 0
+
J0.6 J0.044
1.0
-

N1 N2 N0

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 43

Sequence Fault Currents:

IA0 = 0
IA1 = -IA2 = 1.0/( j0.6 + j0.6 + 0) = -j0.8333

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 44

22
Phase Fault Currents:

Ia = 0
Ib = -j3 (1.0)/(j0.6 + j0.6 + 0) = 1.4434+j0
Ic = j3 (1.0)/(j0.6 + j0.6 + 0) = -1.4434+j0

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 45

Double-Line-to-Ground Fault
Assuming the fault is in phases b and c,
a
b
c   
   Ia Ib Z f Z f Ic
Va Vb Vc  
Zg I  I
b c
Ground

Boundary Conditions: (1) Ia  0  
(2) Vb  (Z f  Z g ) I b  Z g I c
  
(3) c
V  ( Z f  Z g ) I c  Z I
g b

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 46

23
Transformation: From (1), we get
   
I a  0  I a 0  I a1  I a 2
From    
Vb  Va 0  a 2Va1  aVa 2
   
Vc  Va 0  aVa1  a 2Va 2
we get
   
Vb  Vc  (a 2  a)Va1  (a  a 2 )Va 2
Likewise, from
   
I b  I a 0  a 2 I a1  aI a 2
   
I c  I a 0  aI a1  a 2 I a 2

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 47

we get
   
I b  I c  (a 2  a) I a1  (a  a 2 ) I a 2
From boundary conditions (2) and (3), we get
   
Vb  Vc  Z f ( I b  I c )
Substitution gives
 
(a 2  a)Va1  (a  a 2 )Va 2
 
 Z f [(a 2  a) I a1  (a  a 2 ) I a 2 ]
Simplifying, we get
   
Va1  Z f I a1  Va 2  Z f I a 2

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 48

24
From boundary conditions (2) and (3), we get
   
Vb  Vc  (Z f  2Z g )(I b  I c )
We can also show
    
Vb  Vc  2Va 0  Va1  Va 2
    
I b  I c  2 I a 0  I a1  I a 2
Substitution gives
     
2Va 0  Va1  Va 2  Z f (2I a 0  I a1  I a 2 )
  
 2Z g (2I a 0  I a1  I a 2 )

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 49

Rearranging terms, we get


    
2Va 0  2Z f I a 0  4Z g I a 0  Va1  Z f I a1
   
 Va 2  Z f I a 2  2Z g ( I a1  I a 2 )
Earlier, we got
   
Va1  Z f I a1  Va 2  Z f I a 2
  
I a1  I a 2   I a 0
Substitution gives
    
2Va 0  2Z f I a 0  6Z g I a 0  2(Va1  Z f I a1 )
   
Va 0  Z f  3Z g I a 0  Va1  Z f I a1
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 50

25
Sequence Network Interconnection:

Zf Zf Zf+3Zg
+ F1  F2  F0 
 Z1 I a1 + Ia2 + I a0
Va1 +  
Va 2 Z2 Va 0 Z0
Vf
- - - -

N1 N2 N0

Let Z 0T  Z 0  Z f  3Z g
Z1T  Z1  Z f
Z 2T  Z 2  Z f
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 51

The sequence fault currents


 Vf
I a1 
Z Z
Z1T  0T 2T
Z 0T  Z 2T
From current division, we get
 Z 0T 
Ia2   I a1
Z 0T  Z 2T
From KCL, we get
    Z 2T 
I a 0   I a1  I a 2 or I a0   I a1
Z 0T  Z 2T

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 52

26
Double-Line-to-Ground Phase Fault Currents:

Ia  0

I b  I a 0  a 2 I a1  aI a 2
V f Z 0T  aZ 2T 
j 3
Z1T Z 2T  Z1T Z 0T  Z 2T Z 0T

I c  I a 0  aI a1  a 2 I a 2

j 3

V f Z 0 T  a 2 Z 2T 
Z1T Z 2T  Z1T Z 0T  Z 2T Z 0T
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 53

Example: A double-line-to-ground fault occurs at


point F. Assuming zero fault impedance, find the
fault currents at fault point F. Assume Eg = 1.0 p.u.

T1 F T2
Line
G Open

G: X1 = 40% X2 = 40% X0 = 20%


T1, T2: X = 5%
Line: X1 = X2 = 15% X0 = 35%

Note: All reactances are in per-unit of a common MVA base.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 54

27
Sequence Network Interconnection:
F1 F2 F0
  
J0.6 IA1 IA 2 IA 0
+
J0.6 J0.044
1.0
-

N1 N2 N0

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 55

Sequence Fault Currents:

Phase Fault Currents:

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 56

28
Bus Impedance Matrix Method

 Development of the Model


 Rake Equivalent
 Formation of Zbus
 Analysis of Shunt Fault

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 57

Development of the Model


Observations on Manual Network
Solution
The procedure is straight forward, yet tedious and
could be prone to hand-calculation error.

Is there a way for a computer to implement this


methodology?

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 58

29
Development of the Model
Consider the three-bus system shown below. Let us
analyze the system for a three-phase fault in any
bus.
1 2
L1
G2
G1
L2

G1, G2 : X1=X2=0.2 X0=0.1


L1 : X1=X2=0.6 X0=1.2
L2 : X1=X2=0.24 X0=0.5

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 59

Positive-Sequence Network:
1 j0.6 2

- 
j0.2 EG
j0.2
+ +
 + 3
EG1 EG2
- - j0.2 j0.2
j0.6
2
Combine the sources 1
and re-draw. Assume
EG = 1.0 per unit. j0.24 3

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 60

30
For a three-phase fault in bus 1 (or bus 2), we get
the positive-sequence impedance.
Z1  j[0.2 //(0.2  0.6)]  j0.16
 E 1
IF  G    j6.25
Z1 Z1
For a three-phase fault in bus 3, we get

Z1  j[0.24  0.2 //(0.2  0.6)]  j0.4


 E 1
IF  G    j2.5
Z1 Z1

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 61

Let us connect a fault switch to each bus. In order


to simulate a three-phase fault in any bus, close
the fault switch in that bus.
- 
EG
Next, use loop currents to +
describe the circuit with all
fault switches closed. j0.2 4 j0.2
Since there are four loops, j0.6
we need to define four 
loop currents. I4
1 3 2
  
I1 I3 I2

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 62

31
The loop equations are   
loop 1: 1.0  j 0.2( I1  I 3  I 4 )
 
loop 2: 1.0  j 0.2( I 2  I 4 )
   
loop 3: 1.0  j 0.2( I1  I 3  I 4 )  j 0.24I 3
     
loop 4: 0  j 0.2( I 2  I 4 )  j 0.6 I 4  j 0.2( I 4  I1  I 3 )

or 
1.0 0.2 0 0.2  0.2 I
1
1.0 0 0.2 0 0.2 I2
=j 
1.0 0.2 0 0.44  0.2 I
3
0  0.2 0.2  0.2 1.0 I4

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 63

Current I4 is not a fault current. It can be eliminated


using Kron’s reduction. We get
 
V  Z(bus
1)
I
where

Z(bus
1)
 Z1  Z2Z41Z3
and
0.2 0 0.2  0.2
Z1 = j 0 0.2 0 Z2 = j 0.2
0.2 0 0.44  0.2

Z3 = j[-0.2 0.2 -0.2 ] Z4 = j[1.0]

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 64

32
Substitution gives

1 .0 0.16 0.04 0.16 I
1
1.0 = j 0.04 0.16 0.04 I2

1 .0 0.16 0.04 0.40 I3
 
V  Z(bus
1)
I
Note:
(1) The equation can be used to analyze a three-
phase fault in any bus (one fault at a time).
(1)
(2) Zbus is called the positive-sequence bus-
impedance matrix, a complex symmetric matrix.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 65

Rake Equivalent
Consider the matrix voltage equation

1 .0 Z11 Z12 Z13 I
1
1 .0 = Z12 Z22 Z23 I2

1 .0 Z13 Z23 Z33 I3 -
Suppose we are asked to 1.0
find a circuit that satisfies +
the matrix equation. Z12 Z23
Z11 Z22 Z33
One possible equivalent   Z13 
circuit is shown. This circuit I I2 I3
1
is called a rake-equivalent.
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 66

33
Consider again the three-bus system. The circuit is
described by the matrix equation

1 .0 0.16 0.04 0.16 I
1
1.0 = j 0.04 0.16 0.04 I2

1 .0 0.16 0.04 0.40 I3 -
1.0
The rake equivalent is +
shown. The diagonal
j0.04 j0.04
elements of the matrix are
j0.16 j0.16 j0.4
self impedances while the
  j0.16

off-diagonal elements are
I1 I2 I3
mutual impedances.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 67

For the three-bus system, assume a fault in bus 3.


The equation for bus 3 is
  
1.0  j0.16I1  j0.04I2  j0.4I3 -
Since only bus 3 is faulted, 1.0
+
I1=I2=0. We get
 j0.04 j0.04
1.0  j0.4I3 j0.16 j0.16 j0.4
or + + j0.16
 1   
I3    j2.5 V1 V2 I3
j0.4 - -

From KVL, we get the voltage in bus 1.


  Z
V1  1.0  Z13I3  1.0  13  0.6
Z33
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 68

34
Similarly from KVL, we get the voltage in bus 2.
  Z
V2  1.0  Z23I3  1.0  23  0.9
Z33
Note: Once the voltages in all the buses are
known, the current in any line can be calculated.
In general, for a three-phase fault in bus k of a
system with n buses, the fault current is
 1
Ik  k=1,2,…n
Zkk
The voltage in any bus j is given by
 Z
Vj  1.0  jk j=1,2,…n
Zkk
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 69

The current in any line, which is connected from


bus m to bus n,
 canbe found using
 V  Vn
Imn  m
zmn 1 2
j0.6
where zmn is the actual
impedance of the line. -j0.5 j0.2
j0.2 -j2.0 +
For example, the  + 3
current in the line EG1 EG2
-j2.5 -
between buses 2 and -
1 is  
 V  V1 0.9  0.6
I21  2    j0.5
z21 j0.6

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 70

35
Formation of Zbus
Zbus can be built, one step at a time, by adding one
branch at a time until the entire network is formed.
The first branch to be added must be a generator
impedance. This is necessary in order to establish
the reference bus.
Subsequent additions, which may be done in any
order, fall under one of the following categories:
(1) Add a generator to a new bus;
(2) Add a generator to an old bus;
(3) Add a branch from an old bus to a new bus;
(4) Add a branch from an old bus to an old bus.
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 71

Assume that 
at the current 1.0 Z11 Z12 … Z1n I
1
stage, the 1.0 Z21 Z22 … Z2n I2
dimension of =

Zbus is n. 
1.0 Zn1 Zn2 … Znn In
- old
1.0 Zbus
+
Z12 Z2k Zkn Let us examine
Z11 Z22 Zkk Znn each category in
 1  2  k  n the addition of a
I1 I2 Ik In new branch.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 72

36
Type 1: Add a generator to a new bus
-
Let Zg be the impedance of
1.0
the generator to be added.
+
Z12 Z2k Zkn
Z11 Z22 Zkk Znn Zg
 1  2  k  n  n+1
I1 I2 Ik In In1

1.0 Z11 Z12 … Z1n 0 I1

1.0 Z21 Z22 … Z2n 0 I2
= Z 
1.0 n1 Zn2 … Znn 0 In The dimension

1.0 0 0 0 Z g In 1 is (n+1).

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 73

Type 2: Add a generator -


to an old bus k 1.0 
+ Iw
Let Zg be the
impedance of the Z12 Z2k
generator to be Z11 Z22 Zkk Zg Znn
added.   
1 2 k  n
I1 I2 Ik In

The new current in impedance Zkk is (Ik+Iw). The


new equations for buses 1 to n are
    
1.0  Z11 I1  Z12 I2  ...  Z1k (Ik  Iw )  ...  Z1n In
    
1.0  Z21 I1  Z22 I2  ...  Z2k (Ik  Iw )  ...  Z2n In
    
1.0  Zn1 I1  Zn2 I2  ...  Znk (Ik  Iw )  ...  Znn In
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 74

37
For the added generator loop, we get
     
0  Zk1I1  Zk2 I2  ...  Zkk (Ik  Iw )  ...  ZknIn  ZgIw
In matrix form, we get

1.0 Z11 Z12… Z1k … Z1n Z1k I
1
1.0 Z21 Z22… Z2k … Z2n Z2k I2
=




1.0 Zn1 Zn2… Znk … Znn Znk I
n
0 Zk1 Zk 2… Zkk … Zkn Zw Iw

where Zw=Zkk+Zg. The last row is eliminated using


Kron’s reduction. The dimension remains as n.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 75

Type 3: Add a branch -


from an old bus k to 1.0
a new bus +
Z12 Z2k Zkn
Z11 Z22 Zkk Zb Znn
 1  2  k  n  n+1
I1 I2 Ik In In1

The new current in impedance Zkk is (Ik+In+1). The


new equations for buses 1 to n are
    
1.0  Z11 I1  Z12 I2  ...  Z1k (Ik  In1 )  ...  Z1n In
    
1.0  Z21 I1  Z22 I2  ...  Z2k (Ik  In 1 )  ...  Z2n In
    
1.0  Zn1 I1  Zn2 I2  ...  Znk (Ik  In 1 )  ...  Znn In
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 76

38
For the new bus, we get  
1.0  Zk1 I1  Zk 2 I2  ...  Zkk (Ik  In 1 )  ...
 
 ZknIn  Zb In1
In matrix form, we get

1.0 Z11 Z12… Z1k … Z1n Z1k I
1
1.0 Z21 Z22… Z2k … Z2n Z2k I2
=



1.0 Zn1 Zn2… Znk … Znn Znk I
n
1.0 Zk1 Zk 2… Zkk … Zkn Zw In 1
where Zw=Zkk+Zb. Kron’s reduction is not required.
The dimension increases to (n+1).

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 77

Type 4: Add a
branch from an old -
bus j to an old bus k 1.0 
+ Iw
Z12 Z2j Zkn
Z11 Z22 Zjj Zb Zkk Znn
 1  2   k  n
I1 I2 Ij j Ik In

The new current in impedance Zjj is (Ij+Iw). The


new current in impedance Zkk is (Ik-Iw). The new
equations for buses 1 to n are
   
1.0  Z11I1  Z
 12I2  ...  Z1j(Ij  Iw )
 Z1k (Ik  Iw )  ...  Z1n In
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 78

39
   
1.0  Z21I1  Z I
 22 2
 ...  Z2 j Ij  Iw )
(
 Z2k (Ik  Iw )  ...  Z2n In
   
1.0  Zn1I1  Zn2 I2  ...  Znj(Ij  Iw )
  
 Znk (Ik  Iw )  ...  Znn In
For the added loop, we get
     
0  Zj1I1  Zj2 I2  ...  Zjj(Ij  Iw )  Zjk (Ik  Iw )
   
 ...  ZjnIn  Zb Iw  [Zk1I1  Zk2 I2  ...
    
 Zkj(Ij  Iw )  Zkk (Ik  Iw )  ...  ZknIn]

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 79

In matrix form, we get

… 
1.0 Z11 Z12 Z1n Z1j  Z1k I

1
1.0 Z21 Z22 Z2n Z2 j  Z2k I2
=


1.0 Zn1 Zn2 … Znn Znj  Znk I
n
0 Z j1  Zk1 Z j2  Zk2 … Z jn  Zkn Zv Iw

where Zv=Zjj+Zkk-2Zjk+Zb. The last row is


eliminated using Kron’s reduction. The dimension
remains as n.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 80

40
Example: For the network shown, use the step-by-
step building algorithm to form the bus impedance
matrix.
1 j0.6 2
Step 1. Add generator
G1 to bus 1.
j0.2
1 j0.2
+ +
Xbus = 1 [0.2] 3 1.0
1.0
- -

Step 2. Add generator G2 to bus 2.


1 2

1 0.2 0
Xbus =
2 0 0.2

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 81

Step 3. Add the line from bus 1 to bus 2.


1 2
*
1 0.2 0 0.2
Xnew = 2 0 0.2  0.2
* 0.2  0.2 1.0

Apply Kron’s reduction to eliminate the last row


and column. We get

0.2
X2X 41X3  [0.2 -0.2]
 0.2

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 82

41
0.04  0.04
X2X 41X3 
 0.04 0.04
We get 1 2

1
1 0.16 0.04
Xbus  X1  X2X X3 =
4 2 0.04 0.16
Step 4. Finally, add the line from bus 1 to bus 3.
1 2 3
1 0.16 0.04 0.16
No Kron
Xbus = 2 0.04 0.16 0.04 reduction is
3 0.16 0.04 0.4 required.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 83

Example: Determine the positive-sequence bus-


impedance matrix for the four-bus test system
shown. 1 T 2 3
L1
G1 G2

L2 L3

4
T: X=0.08
G1: X1=0.40 X2=0.40 X0=0.15
G2: X1=0.50 X2=0.50 X0=0.25
L1: X1=0.40 X2=0.40 X0=0.80
L2: X1=0.30 X2=0.30 X0=0.60
L3: X1=0.20 X2=0.20 X0=0.40

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 84

42
Positive-sequence network 4

1. Add G1 to bus 1. j0.3 j0.2


1
j0.08
Xbus = 1 [0.4]
1 2 j0.4 3
j0.4 j0.5
2. Add the transformer + +
from bus 1 to bus 2. 1.0 1.0
1 2 - N1 -

1 0.4 0.4
Xbus = 1 2 3
2 0.4 0.48
1 0.4 0.4 0.4
3. Add the line from X
bus =
2 0.4 0.48 0.48
bus 2 to bus 3.
3 0.4 0.48 0.88
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 85

Step 4. Add generator G2 to bus 3.


1 2 3
*
0.4 0.4 1 0.4 0.4
2 0.4 0.48 0.48 0.48
Xnew =
3 0.4 0.48 0.88 0.88
* 0.4 0.48 0.88 1.38

Apply Kron’s reduction.


0.4
X2X 41X3  1
1.38 0.48 [0.4 0.48 0.88]
0.88

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 86

43
We get
0.1159 0.1391 0.2551
1
X2X X3  0.1391 0.1670 0.3061
4

0.2551 0.3061 0.5612


The new bus impedance matrix is

Xbus  X1  X2X 41X3


1 2 3
1 0.2841 0.2609 0.1449
Xbus = 2 0.2609 0.3130 0.1739
3 0.1449 0.1739 0.3188

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 87

Step 5. Add the line from bus 2 to bus 4.


1 2 3 4
1 0.2841 0.2609 0.1449 0.2609
2 0.2609 0.3130 0.1739 0.3130
Xbus =
3 0.1449 0.1739 0.3188 0.1739
4 0.2609 0.3130 0.1739 0.6130
Step 6. Add the line from bus 3 to bus 4.
1 2 3 4
*
1 0.2841 0.2609 0.1449 0.2609 0.1159
2 0.2609 0.3130 0.1739 0.3130 0.1391
Xnew= 3 0.1449 0.1739 0.3188 0.1739  0.1449
4 0.2609 0.3130 0.1739 0.6130 0.4391
* 0.1159 0.1391  0.1449 0.4391 0.784

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 88

44
Apply Kron’s reduction. We get

1 2 3 4
1 0.2669 0.2403 0.1664 0.1959
2 0.2403 0.2884 0.1996 0.2351
X(bus
1)

3 0.1664 0.1996 0.2920 0.2551
4 0.1959 0.2351 0.2551 0.3671

Note: This is the positive-sequence bus-impedance


matrix for the four-bus test system.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 89

Negative- and Zero-Sequence Zbus


The same step-by-step algorithm can be applied to
build the negative-sequence and zero-sequence
bus impedance matrices.
The first branch to be added must be a generator
impedance. This is necessary in order to establish
the reference bus.
The negative-sequence and zero-sequence bus-
impedance matrices can also be described by a
rake equivalent circuit.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 90

45
Example: Find the zero-sequence bus-impedance
matrix for the four-bus test system.
4
Zero-sequence network
j0.6 j0.4
1. Add G1 to bus 1. 1 j0.08
1
2 j0.8 3
Xbus = 1 [0.15] j0.15 j0.25
2. Add the transformer N0
from bus 1 to bus 2.
1 2
Note: The impedance
is actually connected
1 0.15 0 from bus 2 to the
Xbus =
2 0 0.08 reference bus.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 91

3. Add the line from


1 2 3
bus 2 to bus 3.
1 0.15 0 0
Xbus = 2 0 0.08 0.08
3 0 0.08 0.88
Step 4. Add generator
G2 to bus 3. 1 2 3
*
0.15 0 1 0 0
2 0 0.08 0.08 0.08
Xnew =
3 0 0.08 0.88 0.88
* 0 0.08 0.88 1.13

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 92

46
Apply Kron’s reduction. We get

0 0 0
1
X2X X3  0 0.0057 0.0623
4

0 0.0623 0.6853
The new bus impedance matrix is
1 2 3
1 0.15 0 0
Xbus = 2 0 0.0743 0.0177
3 0 0.0177 0.1947

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 93

Step 5. Add the line from bus 2 to bus 4.


1 2 3 4
1 0.15 0 0 0
2 0 0.0743 0.0177 0.0743
Xbus =
3 0 0.0177 0.1947 0.0177
4 0 0.0743 0.0177 0.6743
Step 6. Add the line from bus 3 to bus 4.
1 2 3 4
*
1 0.15 0 0 0 0
2 0 0.0743 0.0177 0.0743 0.0566
Xnew= 3 0 0.0177 0.1946 0.0177  0.177
4 0 0.0743 0.0177 0.6743 0.6566
* 0 0.0566  0.177 0.6566 1.2336

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 94

47
Apply Kron’s reduction. We get

1 2 3 4
1 0.15 0 0 0
2 0 0.0717 0.0258 0.0442
X(bus
0)

3 0 0.0258 0.1693 0.1119
4 0 0.0442 0.1119 0.3248

Note: This is the zero-sequence bus-impedance


matrix for the four-bus test system.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 95

Positive-Sequence Zbus
(1) (1) …
The positive-sequence Z11 Z12 Z1(1n)
bus-impedance matrix 1) …
Z(21
1)
Z(22 Z(21n)
describes the positive- Z(bus
1)

sequence network.
Z(n11) Z(n12) … Z(nn
1)
- N1
1.0
+
(1)
Z12 Z(21k) Z(kn
1)
Rake
(1)
Z11 Z(22
1)
Z(kk1) Z(nn
1)
Equivalent
1 2 k n

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 96

48
Negative-Sequence Zbus
(2) (2) …
The negative-sequence Z11 Z12 Z1(2n)
bus-impedance matrix 2) …
(2) Z(21
2)
Z(22 Z(22n)
describes the negative- Zbus 


sequence network.
Z(n21) Z(n22) … Z(nn
2)

N2

(2)
Z12 Z(22k) Z(kn2) Rake
(2)
Z11 Z(22
2)
Z(kk2) Z(nn
2)
Equivalent
1 2 k n

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 97

Zero-Sequence Zbus
(0 ) (0 ) …
The zero-sequence Z11 Z12 Z1(0n)
bus-impedance matrix (0) 0) …
Z(21
0)
Z(22 Z(20n)
describes the zero- Zbus 

sequence network.
Z(n01) Z(n02) … Z(nn
0)

N0

(0)
Z12 Z(20k) Z(kn0) Rake
(0)
Z11 Z(22
0)
Z(kk0) Z(nn
0)
Equivalent
1 2 k n

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 98

49
Analysis of Shunt Faults
The bus-impedance matrices can be used for the
analysis of the following shunt faults:
1. Three-Phase Fault
2. Line-to-Line Fault
3. Single Line-to-Ground Fault
4. Double Line-to-Ground Fault
Since the bus-impedance matrix is a representation
of the power system as seen from the buses, only
bus faults can be investigated.

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 99

Three-phase Fault at Bus k


The fault current is N1
 1
Ik  (1)
Zkk (1)
Z11 Z(22
1)
Z(kk1) Z(nn
1)

The voltage at 1 2 k n

any bus is
 Z
Vj  1.0  jk
Zkk  
 Vm  Vn
The current in any line is Imn 
zmn

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 100

50
Example: Consider a three-phase fault at bus 4 of
the four-bus test system. Find all line currents.
The positive-sequence bus-impedance matrix is
1 2 3 4
1 0.2669 0.2403 0.1664 0.1959
2 0.2403 0.2884 0.1996 0.2351
X(bus
1)

3 0.1664 0.1996 0.2920 0.2551
4 0.1959 0.2351 0.2551 0.3671
The fault current is
 1 1
IF  (1)    j2.7241
Z44 j0.3671

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 101

The bus voltages are


 Z
Vj  1.0  jk j=1,2,…n
Zkk
 0.1959
V1  1   0.4663
0.3671
 0.2351
V2  1   0.3595
0.3671
 0.2551
V3  1   0.3051
 0.3671
V4  0

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 102

51
 
 Vm  Vn
The line currents are given by Imn 
zmn
 1  0.4663
IG1    j1.3344
j0.4
 1  0.3051
IG2    j1.3897
j0.5
 0.4663  0.3595
I12    j1.3342
j0.08
 0.3595  0.3051
I23    j0.1360
j0.4
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 103

 0.3595  0
I24    j1.1984
j0.3
 0.3051  0
I34    j1.5257
j0.2
 4 
IF I34

j0.3 I24 j0.2
1 j0.08 j0.4 3

  2
 
j0.4 IG1 I12 I23 IG2 j0.5
+ +
1.0 1.0
- N1 -

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 104

52
Line-to-Line Fault at Bus k
N1 N2

(1)
Z11 Z(22
1)
Z(kk1) Z(nn
1) (2)
Z11 Z(22
2)
Z(kk2) Z(nn
2)

1 2 k
 1
 n
Ia1n 2 k
Ia2

Sequence Fault Sequence Voltages at bus j


Currents 
 Va0  0
Ia0  0   (1)
  1 Va1  1  Ia1Zjk
Ia1  Ia2   
Z(kk1)  Z(kk2) Va2  Ia2Z(jk2)

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 105

Example: Consider a line-to-line fault at bus 4 of


the four-bus test system. Find the phase currents
in lines L2 and L3.
The positive-sequence bus-impedance matrices is
1 2 3 4
1 0.2669 0.2403 0.1664 0.1959
2 0.2403 0.2884 0.1996 0.2351
X(bus
1)

3 0.1664 0.1996 0.2920 0.2551
4 0.1959 0.2351 0.2551 0.3671

(1) (2)
For this power system, Xbus  Xbus

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 106

53
The sequence fault currents are

Ia0  0
  1 1
Ia1   Ia2  (1)    j1.362
Z44  Z(44
2)
j2(0.3671)
The sequence voltages in bus 4 are

Va0  4  0
  1)
Va1 4  1  Ia1Z(44
 1  ( j1.362)( j0.3671)  0.5
 
Va2  4   Ia2Z(44
2)
 0.5

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 107

The sequence voltages in bus 2 are



Va0 2  0
  1)
Va12  1  Ia1Z(24  0.6798
  (2)
Va2 2  Ia2Z24  0.3202

The sequence voltages in bus 3 are



Va0 3  0
  1)
Va13  1  Ia1Z(34  0.6526
  (2)
Va2 3  Ia2Z34  0.3474

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 108

54
The sequence currents in line L3 are

Ia0 L3  0
 0.653  0.5
Ia1L 3    j0.7628
j0.2
 0.347  0.5
Ia2 L3   j0.7628
j0.2
The phase currents in line L3 are
   
IaL3  Ia0 L3  Ia1L3  Ia2 L3  0
   
Ib L3  Ia0 L3  a2 Ia1L3  a Ia2 L3  1.3213
   
Ic L3  Ia0 L3  a Ia1L3  a2 Ia2 L3  1.3213

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 109

The sequence currents in line L2 are



Ia0 L2  0
 0.68  0.5
Ia1L 2    j0.5992
j0.3
 0.32  0.5
Ia2 L 2   j0.5992
j0.3
The phase currents in line L2 are
   
IaL2  Ia0 L2  Ia1L2  Ia2 L2  0
   
Ib L2  Ia0 L2  a2 Ia1L2  a Ia2 L2  1.0378
   
Ic L2  Ia0 L2  a Ia1L2  a2 Ia2 L2  1.0378

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 110

55
SLG Fault at Bus k N1
Sequence Fault Currents
  
Ia0  Ia1  Ia2 (1)
Z11 Z(22
1)
Z(kk1) Z(nn
1)

1 
 (0) (1) (2)
1 2 k
Ia1
n
Zkk  Zkk  Zkk N2
Sequence Voltages
(2)
at bus j Z11 Z(22
2)
Z(kk2) Z(nn
2)

  1 2 k  n
Va0  Ia0Z(jk0) N0
Ia2
 
Va1  1  Ia1Z(jk1)
  (0)
Va2  Ia2Z(jk2) Z11 Z(22
0)
Z(kk0) Z(nn
0)

1

2 k
Ia0 n

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 111

Example: Consider a single line-to-ground fault at


bus 4 of the four-bus test system. Find the phase
currents in lines L2 and L3.
The sequence
  fault
 currents are
Ia0  Ia1  Ia2
1
 (0)   j0.9443
Z44  Z(441)
 Z(44
2)

The sequence voltages in bus 4 are


 
Va0  4  Ia0Z(44
0)
 0.3067
  (1)
Va1 4  1  Ia1Z44  0.6534
 
Va2  4  Ia2Z(44
2)
 0.3466

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 112

56
The sequence voltages in bus 2 are
 
Va0 2  Ia0Z(24
0)
 0.0417
  (1)
Va12  1  Ia1Z24  0.778
 
Va2 2  Ia2Z(24
2)
 0.222

The sequence voltages in bus 3 are


 
Va0 3  Ia0Z(34
0)
 0.1057
  (1)
Va13  1  Ia1Z34  0.7591
 
Va2 3  Ia2Z(34
2)
 0.2409

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 113

The sequence currents in line L2 are


  0.0417  0.3067
Ia0 L 2    j0.4417
j0.6
 0.778  0.6534
Ia1L 2    j0.4154
j0.3
  0.222  0.3466
Ia2 L 2    j0.4154
j0.3
Thephase currents
 in line L2
 are
I I  Ia1L2  Ia2 L2   j1.2725
aL2 a0 L2  
Ib L2  Ia0 L2  a2 Ia1L2  a Ia2 L2   j0.0262
   
Ic L2  Ia0 L2  a Ia1L2  a2 Ia2 L2   j0.0262

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 114

57
The sequence currents in line L3 are
  0.1057  0.3067
Ia0 L 3    j0.5026
j0.4
 0.7591  0.6534
Ia1L 3    j0.5289
j0.2
  0.2409  0.3466
Ia2 L3    j0.5289
j0.2
Thephase currents
 in line L3
 are
I I  Ia1L3  Ia2 L3   j1.5603
aL3 a0 L3  
Ib L3  Ia0 L3  a2 Ia1L3  a Ia2 L3  j0.0262
   
Ic L3  Ia0 L3  a Ia1L3  a2 Ia2 L3  j0.0262

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 115

Double Line-to-Ground Fault at Bus k


N2
N1 N0

(1)
Z11 Z(kk1) Z(nn
1) (2)
Z11 Z(kk2) Z(nn
2) (0)
Z11 Z(kk0) Z(nn
0)

1 k n 1 k n 1 k  n
Ia1 Ia2 Ia0

Sequence Fault Currents


 1
Ia1 
Z(kk1)  (Z(kk2) // Z(kk0) )

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 116

58
 Z(kk0) 
Ia2   Ia1
Z(kk0)  Z(kk2)
 Z(kk2) 
Ia0   Ia1
Z(kk0)  Z(kk2)
Sequence Voltages at bus j
 
Va0  Ia0Z(jk0)
 
Va1  1  Ia1Z(jk1)
 
Va2  Ia2Z(jk2)

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 117

Example: Consider a double line-to-ground fault


at bus 4 of the four-bus test system. Find the
phase currents in lines L2 and L3.
Sequence Fault Currents
 1
Ia1    j1.8538
Z(kk1)  (Z(kk2) // Z(kk0) )
 Z(0) 
Ia2   (0) kk (2) Ia1  j0.8703
Z Z
  kk  kk
Ia0   Ia1  Ia2  j0.9835
The sequence voltages in bus 4 are
   
Va0  4  Va1 4  Va2  4  Ia0Z(44
0)
 0.3195

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 118

59
The sequence voltages in bus 2 are
 
Va0 2   Ia0Z(24
0)
 0.0435
  (1)
Va12  1  Ia1Z24  0.5641
 
Va2 2   Ia2Z(24
2)
 0.2046

The sequence voltages in bus 3 are


 
Va0 3  Ia0Z(34
0)
 0.1101
  (1)
Va13  1  Ia1Z34  0.5271
 
Va2 3  Ia2Z(34
2)
 0.222

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 119

The sequence currents in line L2 are


 0.0435  0.3195
Ia0 L 2   j0.46
j0.6
 0.5641  0.3195
Ia1L 2    j0.8155
j0.3
 0.2046  0.3195
Ia2 L2   j0.3828
j0.3
The phase
 currents
 in line L2are
I  Ia0 L2  Ia1L2  Ia2 L2  j0.0273
aL2
Ib L2  1.0378  j0.6764

Ic L2  1.0378  j0.6764

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 120

60
The sequence currents in line L3 are
 0.1101  0.3195
Ia0 L 3   j0.5235
j0.4
 0.5271  0.3195
Ia1L 3    j1.0383
j0.2
 0.222  0.3195
Ia2 L 3   j0.4874
j0.2
Thephase currentsin line L3
 are
IaL3  Ia0 L3  Ia1L3  Ia2 L3   j0.0273

Ib L3  1.3213  j0.799

Ic L3  1.3213  j0.799

Electrical & Electronics Engineering Institute EE 251 – Fault Studies


University of the Philippines Diliman 121

Reference: J. R. Neuenswander, Modern Power Systems, International


Textbook Co., New York, 1971
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 122

61

You might also like