PCS7 - Manual and Automatic Mode For Control Blocks
PCS7 - Manual and Automatic Mode For Control Blocks
0 SP2)
Manual and automatic mode for control blocks
Switchover initiated in the faceplate (ModLiOp = 0): The switchover between operating modes is
carried out in the standard view of the faceplate. In the function block, the parameters ManModOp for
"manual mode" and AutModOp for "automatic mode" are used.
If both signals (ManModOp =1, AutModOp = 1 ) are set, ManModOp = 1 has priority.
Switchover per interconnection (CFC or SFC instance) (ModLiOp = 1): The switchover between
the operating modes is carried out with an interconnection on the function block. The parameters
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the
completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties.
8/31/2020
ManModLi for "manual mode" and AutModLi for "automatic mode" are used in pushbutton operation.
In switching mode (requirement: Feature.Bit4 = 1, see Setting switch or button mode) connection
AutModLi is used exclusively.
If both signals (ManModLi =1, AutModLi = 1 ) are set, ManModLi = 1 has priority.
Note
You can access the variable parameters AutModOp and ManModOp from a normal SFC (in contrast to
the instance of an SFC type). The SFC can thus change the operating mode without revoking the access
rights of the operator (i.e. without setting ModLiOp = 1).
• Switchover without internal setpoint tracking process variable (SP_TrkPV = 0) means that the block
immediately recalculates the value of the manipulated variable based on the setpoint and process value (PV)
when the mode is changed. The Feature parameter is used to choose between the two variants:
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the
completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties.
8/31/2020
Note
Points to note about switchovers with a P step change:
― The P action must be active for the setting "Switchover with P step" (PropSel = 1)
― If the P action is in the feedback (PropFacSP = 0), the "Switchover with P step" setting has no
effect.
― If the switchover function with the internal setpoint tracking the process variable is active
(SP_TrkPV = 1), the "Switchover with P step" setting has no effect.
See also
→ Resetting the commands for changing the mode
→ Disabling bumpless switchover to automatic mode for controllers
→ Program mode for controllers
→ Setting switch or button mode
This document constitutes a free excerpt compiled by the user himself/herself from the documentation provided by Siemens for this product. Siemens disclaims all liability for the
completeness of this document. It shall only be used for the user's own internal purposes. It shall not be passed on to third parties.
8/31/2020