Transmission Line
Short Length<80 km or 50 miles
Medium 80 km < Length < 240 km or line length
within 50-150 miles
Long Length > 240 km or above 150 miles
Lumped parameter: IS IR IS IR
VS VR Load VS VR
Distributed parameter: IS IR
VS VR
(2) Transmission efficiency. The power obtained at the receiving end of a transmission line is
generally less than the sending end power due to losses in the line resistance.
M7/Page 3 of 7
Few nomenclatures
z = series impedance per unit length per phase
y = shunt admittance per unit length per phase to neutral; [y= 1
jb C ]
jX C
l = total length of line
Z = zl = total series impedance per phase
Y = yl = total shunt admittance per phase to neutral
The short transmission line:
Due to small length shunt admittance(Y) is omitted. Z= R + j XL IR
IS = IR IS
VS = VR + IR Z VS VR
A= 1; B= Z; C= 0; D=1
IS Z IR
The Medium transmission line:
Nominal π model: VR
Y VS Load
Current through the capacitor near to the load is
VR Y/2 Y/2
2
M7/Page 4 of 7
Y
V
Current through the series impedance is (IR + R )
2
Y
V
VS = (IR + R ) Z + VR
2
= (1+ YZ ) VR + Z IR
2
Y
V
Current in the shunt capacitance at the sending end is S 2
Y Y Y Y
V V YZ
IS = S 2 + (IR + R 2 ) = [(1+ ) VR + Z IR] 2 + (IR + R 2
V )
2
Y2Z
YZ
= [Y+ ] VR + [1+ 2 ] IR
4
Y2Z YZ YZ
A= (1+ YZ ); B= Z; C= [Y+ ] = Y [1+ ]; D= [1+ ]
2 4 4 2
M7/Page 5 of 7
Nominal T model:
IS Z/2 Z/2 IR
YZ 2 YZ VR
A= (1+ YZ ); B= [Z+ ] = Z [1+ ]; C= Y; Y V1 Load
2 4 4 VS IC
YZ
D= [1+ ]
2
Math examples
1. A 3-phase, 50 Hz, 16 km long overhead line supplies 1000 kW at 11kV, 0·8 p.f.
lagging. The line resistance is 0·03 Ω per phase per km and line inductance is 0·7 mH per
phase per km. Calculate the sending end voltage, voltage regulation and efficiency of
transmission.
Problem_1: A three-phase 60 Hz, 200km long transmission line has the following constants:
Resistance per phase per kilo meter is 0.15Ω,
Reactance per phase per kilo meter is 0.45Ω,
M7/Page 6 of 7
Solution:
VR = 600000
= 205.28 41.40
P
IR
3VL cosθ
R = Total resistance of line = 200*0.15 = 30Ω.
XL = Total reactance of line = 200*0.45 = 90Ω.
Y = Total susceptance of line = 200*10-5= 2*10-3mho.
Z = (R + j XL ) = (30 + j90)
Y = j2*10-3
Z/2
A= (1+ YZ ) = 0.91+j0.03 = 0.9101.888 IS Z/2 IR
2
Y VR
YZ 2 VS IC
V1 Load
B= [Z+ ] = 27.3+j86.4 ohm
4
C= Y = j2*10-3 mho
M7/Page 7 of 7
YZ
D= [1+ ] = 0.91 + j0.03
2
71,447.909.179
VS = AVR + BIR = 69,916.95 + j 11,941.04 =
IS = CVR + DIR = 144.19 + j1.0832 = 144.200.430
Sending end power factor = cos (θVs – θIs) = 0.988
VS 71.447 * 10 3
VR.fullload 60 * 10 3
VR.noload VR.fullload A 0.910
% Regulation = * 100 * 100 * 100
VR.fullload VR.fullload 60 * 10 3
= 30.855 %