HAT600N 600NI 600NB 600NBI en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

HAT600N SERIES

(HAT600N/HAT600NI/HAT600NB/HAT600NBI)
ATS CONTROLLER

USER MANUAL
Chinese trademark

English trademark
SmartGen — make your generator smart
SmartGen Technology Co., Ltd.
No. 28 Xuemei Street, Zhengzhou, Henan, China
Tel: +86-371-67988888/67981888/67992951
+86-371-67981000(overseas)
Fax: +86-371-67992952
Web: www.smartgen.com.cn/
www.smartgen.cn/
Email: [email protected]

All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this publication
should be addressed to Smartgen Technology at the address above.
Any reference to trademarked product names used within this publication is owned by their respective
companies.
SmartGen Technology reserves the right to change the contents of this document without prior notice.

Table 1 Software Version


Date Version Note
2017-04-06 1.0 Original release.
2019-09-05 1.1 Added communication function description in parameter settings.
Fixed current terminal number of breaker application diagram and
2020-05-12 1.3
optimized the diagram.
2020-12-16 1.4 Modified the event log record number.
1. Added the torque requirement for fixing clips below the installation
2021-08-05 1.5 dimension drawing;
2. Changed the font to “Roboto”
Updated the figures of back panel and case dimensions, updated the
2022-05-31 1.6
logo of SmartGen.
Changed terminal 27, 28 in Breaker Wiring Diagram as “normally open
contact”;
2022-10-24 1.7
Deleted power module supply way;
Modified format issues.

HAT600N Series ATS Controller User Manual Page 2 of 24


CONTENT

1. OVERVIEW .....................................................................................................................................................4
2. PERFORMANCE AND CHARACTERISTICS ..................................................................................................4
3. SPECIFICATION .............................................................................................................................................5
4. OPERATING ...................................................................................................................................................6
4.1. OPERATION PANEL ........................................................................................................................... 6
4.2. KEY FUNCTION DESCRIPTION ......................................................................................................... 6
5. LCD DISPLAY .................................................................................................................................................7
5.1. MAIN SCREEN.................................................................................................................................... 7
5.2. MAIN MENU INTERFACE .................................................................................................................. 8
6. COMMISSIONING ..........................................................................................................................................9
7. PARAMETERS CONFIGURATION .............................................................................................................. 10
7.1. PARAMETER CONFIGURATION DESCRIPTION ............................................................................. 10
7.2. PARAMETER CONFIGURATION TABLE.......................................................................................... 10
7.3. INPUT/OUTPUT FUNCTION DESCRIPTION ................................................................................... 13
8. EVENT LOG ................................................................................................................................................. 14
9. TIMING START ........................................................................................................................................... 15
10. DATE AND TIME SETTING ....................................................................................................................... 15
11. LANGUAGE SETTING ............................................................................................................................... 15
12. CONTROLLER INFORMATION ................................................................................................................. 16
13. ATS OPERATION ...................................................................................................................................... 17
13.1. MANUAL OPERATION ................................................................................................................... 17
13.2. AUTOMATIC OPERATION ............................................................................................................. 17
13.3. ATS POWER SUPPLY .................................................................................................................... 17
14. COMMUNICATION CONFIGURATION AND CONNECTION.................................................................... 18
15. DESCRIPTION OF CONNECTING TERMINALS ....................................................................................... 18
16. TYPICAL WIRING DIAGRAM .................................................................................................................... 20
17. INSTALLATION ......................................................................................................................................... 23
18. FAULT FINDING ........................................................................................................................................ 24

HAT600N Series ATS Controller User Manual Page 3 of 24


1. OVERVIEW

HAT600N series ATS controller is an intelligent dual-supply module with programmable function,
automatic measurement, LCD display, and digital communication. It combines digitalization,
intelligence and network together. Measurement and control process are automated, which greatly
reduces hand operation mistakes. It is an ideal option for ATS.
HAT600N series ATS controller is made of microprocessor as its core, which can accurately detect
2-way-3-phase voltage and also make accurate judgment for abnormal voltage (over voltage, under
voltage, loss of phase, over frequency, under frequency) and output passive control signal. This
controller has full consideration in various applications of ATS (automatic transfer system), which can
be directly used for Intelligent ATS, Contactor ATS, Circuit Break ATS etc. It has compact structure,
advanced circuits, simple wiring and high reliability, can be widely used in electric power,
telecommunications, petroleum, coal, metallurgy, railways, municipal administration, intelligent building,
electrical devices, automatic control and testing system etc.

2. PERFORMANCE AND CHARACTERISTICS

1) System type can be set to: Mains (1#) & Mains (2#), Mains (1#) & Generator (2#), Generator (1#) &
Mains (2#), Generator (1#) & Generator (2#).
2) Backlit 128x64 LCD, optional Chinese and English display, push-button operation.
3) Collect and display 2-way 3 phase Voltage and Frequency:
1# 2#
Line-Line voltage (Uab, Ubc, Uca) Line-Line voltage (Uab, Ubc, Uca)
Phase voltage (Ua, Ub, Uc) Phase voltage (Ua, Ub, Uc)
Frequency (F1) Frequency (F2)
4) Collect and display load active power, apparent power, power factor and 3 phase current.
5) Over current alarm function.
6) Over/under voltage, loss of phase, reverse phase sequence, over/under frequency protection.
7) Automatic/Manual mode transfer; In manual mode, switch can be forced to close or open;
8) All parameters can be set on site. Two level passwords ensure authorized staff operation only.
9) During genset testing ATS controller can be set to either in On-load or Off-load mode.
10) ATS Controller has function of automatic re-closing.
11) Closing output signal can be set as on intervals or as continuous output.
12) Applicable for ATS of one neutral position, two neutral position and change over.
13) Applicable for 2 isolated neutral line for Generator and Mains.
14) Real-time clock (RTC).
15) Event log can record 50 items circularly.
16) Timely schedule can be set on monthly or weekly basis and trial can be set as with on- load or off
-load.
17) Can control two generators to work in a cycle, even the genset running time and crank rest time
can be set.
18) Widely range of DC power supply (8V to 35V). Max.80V DC input can be endured in an instant, or be
supplied via HWS560 module (input AC 85V~560V, output DC 12V).
19) Wide space between connecting terminals of AC input. Max.625V input voltage.
20) With standard isolated RS485 communication interface. With "remote controlling, remote
measuring, remote communication" function by the ModBus communication protocol.
21) Can check the current status of controller (including switch digital input, over Voltage, and under
Voltage etc.).
22) Suitable for various AC systems (3 phase 4-wires, 3-phase 3-wires, single-phase 2-wire, and
2-phase 3-wire).
23) Modular design, flame-resisting ABS plastic shell, plug-in terminals and embedded installation.
Compact structure with easy installation.

HAT600N Series ATS Controller User Manual Page 4 of 24


Table 2 HAT600N Series Controller Models and Main Functions
Type DC Power Supply AC Power Supply AC Current and Power
HAT600N √ × ×
HAT600NI √ × √
HAT600NB √ √ (L-N220V) ×
HAT600NBI √ √ (L-N220V) √

3. SPECIFICATION

Table 3 Technical Parameters


Items Contents
DC 8.0V~35.0V, continuous power supply.
Operating Voltage HTS220/HWS560 power supply (without battery supply).
AC160V~280V (HAT600NB/HAT600NBI) during AC power L1N1/L2N2 supply.
Power Consumption <3W (Standby mode: ≤2W)
AC system HAT600N/HAT600NI HAT600NB/HAT600NBI
3P4W (L-L) (80~625)V (80~480)V
AC Voltage Input 3P3W (L-L) (80~625)V Not used
1P2W (L-N) (50~360)V (50~280)V
2P3W (A-B) (80~625)V (80~480)V
Rated Frequency 50/60Hz
Close/Open Trip
16A AC250V Free Voltage relay output
Relay Output
Programmable
16A/7A AC250V Free Voltage relay output
Relay Output
Digital Input Connecting to GND
Communication RS485 isolated interface, ModBus Protocol
Dimensions 209mmx153mmx55mm
Panel Cutout 186mm x 141mm
Operating Temp. (-25~+70)°C
Operating Humidity (20~93)%RH
Storage Temp. (-25~+70)°C
Protection Rank IP55: when waterproof gasket is installed between enclosure and control screen.
Apply AC2.2kV voltage between high voltage terminal and low voltage terminal
Insulation Strength
and the leakage current is not more than 3mA within 1min.
0.8kg (HAT600N/HAT600NI)
Weight
1.0kg (HAT600NB/HAT600NBI)

HAT600N Series ATS Controller User Manual Page 5 of 24


4. OPERATING

4.1. OPERATION PANEL

Fig.1 Operation Panel


4.2. KEY FUNCTION DESCRIPTION
Table 4 Key Function Description

Icon Keys Description


1# Close In Manual mode, switch on 1# power to load.

Open In Manual mode, switch off 1# or 2# power to off-load.

2# Close In Manual mode, switch on 2# power to load.

Manual Press and controller enters Manual mode.

Auto Press and controller enters Auto mode.

Test Pressing this key can directly enter commissioning interface.


Press the key to enter menu interface; pressing and holding it to
Menu/Confirm return to the main menu interface. When an alarm occurs,
pressing and holding the key can remove alarm.
Scroll the screen. In parameter editing, pressing this key can
Scroll Screen/Increase
increase values.

HAT600N Series ATS Controller User Manual Page 6 of 24


5. LCD DISPLAY

5.1. MAIN SCREEN

U1(L-L) 380 380 380V


U2(L-L) 380 380 380V This screen shows: line-line voltage (L1-L2, L2-L3, and
F1 50.0Hz F2 50.0Hz L3-L1), frequency and controller’s present working mode.
Present Status: MANUAL

U1(L-N) 219 219 219V


U2(L-N) 219 219 219V This screen shows: 1# and 2# 3 phase Voltage (L-N), 3 phase
AMP 500 500 500A current with load and controller status.
Present Status: MANUAL

PWR 329kW
PF 1.00 PS 329kVA This screen shows: total active power, total apparent power,
power factor and real-time clock and controller working
2010-06-10 (4) 20:25:36
status.
Present Status: MANUAL

1# Volt normal First line: 1# operating state of power supply.


2# Volt normal Second line: 2# operating state of power supply.
Gens Start signal Output Third line: other operating states.
Gens starting Fourth line: alarm type and information.

Table 5 Display of 1# Status (upper to lower)


No. Item Type Description
1 1# Gens Alarm Alarm When 1# genset occur failure, this will display.
When 1# breaker occur closing failure, this will
2 1# Fail to Close Alarm
display.
When 1# breaker occur opening failure, this will
3 1# Fail to Open Alarm
display.
When 1# power supply voltage is higher than the
4 1# Over Voltage Indication
setting value, this will display.
5 1# Miss Phase Indication Loss of any phase of A, B and C.
When 1# power supply frequency is higher than the
6 1# Over Freq Indication
setting value, this will display.
When 1# power supply frequency is lower than the
7 1# Under Freq Indication
setting value, this will display.
When 1# power supply voltage is lower than the
8 1# Under Volt Indication
setting value, this will display.
9 1# reverse phase Warning Phase sequence is not A-B-C.
10 1# Volt Normal Indication 1# source voltage is within the setting range.

HAT600N Series ATS Controller User Manual Page 7 of 24


Table 6 Display Priority of 2# Status (upper to lower)
No. Item Type Description
1 2# Gens Alarm Alarm When 2# genset occur failure, this will display.
When 2# breaker occur closing failure, this will
2 2# Fail to Close Alarm
display.
When 2# breaker occur opening failure, this will
3 2# Fail to Open Alarm
display.
When 2# power supply voltage is higher than the
4 2# Over Volt Indication
setting value, this will display.
5 2# Miss Phase Indication Loss of any phase of A, B and C.
When 2# power supply frequency is higher than the
6 2# Over Freq Indication
setting value, this will display.
When 2# power supply frequency is lower than the
7 2# Under Freq Indication
setting value, this will display.
When 2# power supply voltage is lower than the
8 2# Under Volt Indication
setting value, this will display.
9 2# reverse phase Warning Phase sequence is not A-B-C.
10 2# Volt Normal Indication 2# source voltage is within the setting range.
Table 7 Display Status of Other Items (upper to lower)
No. Item Type Description
1 Trip alarm Alarm Trip alarm input is active.
2 Breaking compulsorily Warning Breaking compulsorily input is active.
Load current is over the setting limit and exceed the
3 Overload Warning
setting delay.
4 Gens Start Output Indication Display that engine has been started.
5 Remote start input Indication This input is active when start the genset circularly.
Remark:
Alarm: when alarm occurs, indicators will flash and this alarm signal won’t be cut until it is reset by long pressing .
Warning: when warning occurs, alarm indicator will flash while extinguish when warning alarm is inactive.

5.2. MAIN MENU INTERFACE

In the main screen, press key, and enter the main menu interface.

1. Parameter Setting
2. Event Log
3. Timing Start
4. Date & Time Set
Press key to choose parameters (the current line was
highlighted with black) and then press key to confirm, and
enter the corresponding display screen.
3. Timing Start
4. Date & Time Set
5. Language
6. Information

HAT600N Series ATS Controller User Manual Page 8 of 24


6. COMMISSIONING

In the main screen, press to enter into the operation interface and the screen will show as below:

1 Exit
2 Stop to Test
3 Test Off-Load
4 Test On-Load
5 Cycle start

Fig.2 Commissioning Screen

Press key to select corresponding function, and press key to confirm.


TEST OFF-LOAD: It will send out a start signal immediately. After generator is normal, if mains is
normal, the ATS will not act. The ATS will transfer the load to generator only when mains is abnormal.
After mains return to normal, the ATS will transfer the load to mains. Here the start generator signal
output will keep.
TEST ON-LOAD: It will send out a start generator signal immediately. After generator voltage is normal,
the ATS will transfer the load to gens immediately regardless the main is normal or not.
STOP TO TEST: The start generator signal will turn off after pressing this key immediately.
CYCLE START: When this mode is active, generator start-signal will cyclic output according to mains
status. The cyclic time can be set by users. If generator fault occurs, start-signal won’t be sent out any
more by controller. If in manual mode, controller will keep the current status and cancel cycle start
function.
Conditions and procedures for cycle start mode:
1) In automatic mode.
2) Output setting: 1# engine start output (N/O Output) and 2 # engine start output (N/O Output).
3) Input setting: 1# generator fault input, 2# generator fault input and remote start input.
4) Option of <Cycle run times> and <Cycle shutdown times> should be programmed and run.
5) Set the system type as 1# Gens & 2# Gens.
6) Set the proper <generator start delay> time.
Remark: In manual mode, after choosing commissioning stage, generator will output start-signal immediately, but the
ATS will not transfer to load automatically except for operation manually by pressing key on the front panel.

HAT600N Series ATS Controller User Manual Page 9 of 24


7. PARAMETERS CONFIGURATION

7.1. PARAMETER CONFIGURATION DESCRIPTION

In the main interface, press key, choose 1. Parameter Setting and then press key, to enter the
password interface.
Input password value 0-9 by key, and shift Right by key. Press the again to confirm the
password when four number is OK. If password is correct, it will enter into the parameter main interface.
If it is wrong, it will directly exit and return to main interface. Factory Default Password is 1234.
Press to shift to next position and set the parameters. Under current parameter set screen, press
and enter current parameter set mode. Current value of the first line screen display was highlighted
with black. Press key to change the value and press key to shift position. Press key again
to confirm the settings. If the value number is within the setting range, the value will be saved into the
internal memory of the controller; If it is beyond the range, then the parameter settings will not be saved.
Long time pressing will go back to the main display screen.
7.2. PARAMETER CONFIGURATION TABLE
Table 8 Parameter Configuration Item
No. Item Range Default Description
It is the delay of 1# power from voltage abnormal
01 1# Normal Delay (0-9999)s 10
to voltage normal.
1# Abnormal It is the delay of 1# power from voltage normal to
02 (0-9999)s 5
Delay voltage abnormal.
It is the delay of 2# power from voltage abnormal
03 2# Normal Delay (0-9999)s 10
to voltage normal.
2# Abnormal It is the delay of 2# power from voltage normal to
04 (0-9999)s 5
Delay voltage abnormal.
Closing relay output pulse. If set as zero, it is
05 Close Breaker (0-20)s 5
continuous output.
06 Open Breaker (1-20)s 5 Opening relay output pulse.
It is the delay from 1# power open to 2# power
07 Transfer Interval (0-9999)s 1
close or from 2# power open to 1# power close.
When module receives a closing signal, closing
08 Exceed Transfer (0-20.0)s 0.0
relay output.
When the breaker fail to close for the first time, the
module will open breaker, and then attempt to
Again Close
09 (0-20.0)s 1.0 close for the second time, if still failed to close the
Time
second time, the module will send out closing
breaker failure signal.
When the breaker fail to open for the first time, the
module will close breaker, and then attempt to
Again Open
10 (0-20.0)s 1.0 open for the second time, if still failed to close the
Time
second time, the module will send out opening
breaker failure signal.
When voltage is abnormal, start delay begins and
starting signal is initiated.
In cycle start, starting signal is initiated, delay
11 Start Delay (0-9999)s 1 begins. After delay ends, if voltage abnormal, send
fault alarm and start another genset. Start delay
should be higher than total starting time, minimum
30 seconds.
It is the delay from #1 power is normal to send out
12 Stop Delay (0-9999)s 5
stop generator signal.

HAT600N Series ATS Controller User Manual Page 10 of 24


No. Item Range Default Description
13 Cycle Run Time (1-1440)min 720 Gens cycle start run time.
14 Cycle Stop Time (1-1440)min 720 Gens cycle stop time.
15 Rated Volt (100-600)V 230 AC system rated voltage.
The settings are used to configure the power over
voltage point in the event of the voltage rising
16 Over Voltage (100-150)% 120
above the setting value. This value can be adjusted
to suit user requirements.
Over Voltage
17 (100-150)% 115 Normal return value of over voltage.
Return
The settings are used to configure the power under
18 Under voltage (50-100)% 80 voltage point in the event of the voltage falling
below the setting value.
Under Voltage
19 (50-100)% 85 Normal return value of under voltage.
Return
When the frequency is over the point, over
20 Over Frequency (0.0-75.0)Hz 55.0
frequency is active.
Over Frequency
21 (0.0-75.0)Hz 52.0 Normal return value of over frequency.
Return
When the frequency is under the point, low
22 Under Frequency (0.0-75.0)Hz 45.0
frequency is active.
Under Frequency
23 (0.0-75.0)Hz 48.0 Normal return value of over frequency.
Return
24 CT Ratio (5-65000)/5 500 Current Transformer ratio.
Rated Load
25 (5-6000)A 500 Load rated current.
Current
Over Current
26 (50-150)% 120 Load over current value.
Value
Over Current
27 (0-9999)s 1296 Over current alarm delay
Delay
28 Module Address (1-254) 1 RS485 communication address
29 Password 1234 It applies to modify parameters.
1.1# Mains 2# Gens
2.1# Gens 2# Mains
30 System Type (1-4) 1
3.1# Mains 2# Mains
4.1# Gens 2# Gens
1) two OFF position;
31 Off Position (1-3) 1 2) one OFF position;
3) no OFF position
1. 3-phase 4 wires
2. 3-phase 3 wires
32 AC System (1-4) 1
3. Single phase 2 wire
4. 2-phase 3 wires
1. 1# Priority;
33 Priority Select (1-3) 1 2. 2# Priority;
3. No Priority
34 Aux. Output 1 (1-28) 25 01. Not Used
35 Aux. Output 2 (1-28) 28 02. Critical Failure
36 Aux. Output 3 (1-28) 13 03. Fail of Transfer
37 Aux. Output 4 (1-28) 16 04. Warning Output
05. Alarm Output(delay)
06. 1# Normal Volt
07. 1# Abnormal Volt
38 Aux. Output 5 (1-28) 18 08. 2# Normal Volt
09. 2# Abnormal Volt
10. Overcurrent Output

HAT600N Series ATS Controller User Manual Page 11 of 24


No. Item Range Default Description
11. Auto State Output
12. Manual State Output
13. Gens Start(N/O)
14. Gens Start(N/C)
15. 1# Shut Output
16. 1# Break Off Output
17. 2# Shut Output
18. 2# Break Off Output
19. Common Alarm Output
20. Time Test Gen Start
21. Shut State
22. 2# Shut State
23. 1# Gens Start(N/O)
24. 2# Gens Start(N/O)
25. ATS Power L1
26. ATS Power L2
27. ATS Power L3
28. ATS Power N
39 Aux. Input 1 (1-14) 02 01.Not used
40 Aux. Input 2 (1-14) 01 02.Breaking compulsorily
41 Aux. Input 3 (1-14) 01 03.Test off-load
04.Test on-load
05. Test Lamp
06. 1# Gens Alarm
07. 2# Gens Alarm
08. Remote start
42 Aux. Input 4 (1-14) 01 09. Trip alarm
10. Reserved
11. Reserved
12. Reserved
13. Reserved
14. Reserved
1. Enable COM Adj/Ctrl
Communication 2. Disable COM Control
43 (1-4) 1
Set 3. Disable COM Adjustment
4. Disable COM Adj/Ctrl

HAT600N Series ATS Controller User Manual Page 12 of 24


7.3. INPUT/OUTPUT FUNCTION DESCRIPTION
Table 9 Input Port Function Description
Item Description
01 Not used Invalid.
When active, this will force the breaker to transfer the ATS to OFF
02 Breaking compulsorily
position. “None OFF position” ATS is unavailable.
When active, controller will send a genset start signal immediately. When
03 Test Off-load
mains is normal, gens will not close the breaker.
When active, controller will send genset start signals immediately. When
04 Test On-Load
gens is normal, gens will close the breaker.
When active, all Led lights on the front panel of the controller will be bright
05 Test lamp
and the background of the LCD will be black in color.
06 1# Gens Alarm In Cycle start, if the input is active, 1# Gens will not start.
07 2# Gens Alarm In Cycle start, if the input is active, 2# Gens will not start.
08 Remote start This input is necessary for cycle start generator.
09 Trip alarm
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
Table 10 Output Port Function Descriptions
Item Description
01. Not used Invalid.
02. Critical failure Switch transfer failure also belongs to the critical failure alarm.
1# closed failure, 1# open failure, 2# closed failure, and 2# open failure
03.Fail of transfer
also belongs to the fail to transfer.
1# reverse phase sequence; 2# reverse phase sequence, and load over
04. Warning output
current and compulsory belongs to general warning output.
05. Alarm output (delay) When there is Serious fault then it will alarm for 60sec.
06. 1# Normal volt It will output when 1# voltage is normal.
07. 1# Abnormal volt It will output when 1# voltage is abnormal.
08. 2# Normal volt It will output when 2# voltage is normal.
09. 2# Abnormal volt It will output when 2# voltage is abnormal.
10. Over current output It will output when loaded current exceeds the limit.
11. Auto state output In will show output in automatic mode.
12. Manual state output In will show output in manual mode.
13. Gens start (NO) When generator starts output (Relay closed).
14. Gens start (NC) When generator starts output (Relay released).
15. 1# close output 1# Switch ON signal output.
16. 1# open output 1# Switch OFF signal output, for one breaking position breaks off output.
17. 2# close output 2# Switch ON signal output.
18. 2# open output 2# Switch OFF signal output.
19. Common alarm output It includes serious fault alarm and common alarm.
20. Timing Start Gen Schedulers start generator function.
21. 1# Shut state 1# Switch auxiliary shutdown output.
22. 2# Shut state 2# Switch auxiliary shutdown output.
23. 1#Gens start (NO) 1# Gens start output.
24. 2#Gens start (NO) 2# Gens start output.
25. ATS power L1
26. ATS power L2
ATS power supply.
27. ATS power L3
28. ATS power N

HAT600N Series ATS Controller User Manual Page 13 of 24


8. EVENT LOG

In the main screen, press key and select 2. Event Log, and then press key, the screen will
show the event log interface as below:
1# Shut
1# Volt normal
2# Under Volt
2010-02-18 21:15:07 1/99

Fig.3 Event Log Screen

Press key to select the corresponding record, and press key to enter into detailed information
interface.
In the detailed information interface, press key and it can display the record information circularly,
including the temporal voltage of #1 and #2, detailed voltage, current, frequency and date and time.
Press and it will exit the current interface, while pressing for a long time will return to main
screen.

1# Close 1# Close 1# Close


1# Volt normal U1(L-N) 220 220 220V AMP 501 502 503A
2# Below Volt U2(L-N) 0 100 220V F1 50.0Hz F2 50.1Hz
2010-02-18 21:15:07 2010-02-18 21:15:07 1/99 2010-02-18 21:15:07 1/99

Fig.4 Event Log Screen


Event log includes: record type, 1# power supply status, 2# power supply status, 1# 3-phase voltage, 2#
3-phase voltage, 3-phase current, 1# frequency, 2# frequency and time-to-event etc.
Table 11 Event Log Type
No. Type Description
1 1# Close 1# close signal output
2 2# Close 2# close signal output
3 1# Fail to Close 1# power supply cannot connect to load.
4 2# Fail to Close 2# power supply cannot connect to load.
5 1# Fail to Open 1# power supply cannot disconnect to load.
6 2# Fail to Open 2# power supply cannot disconnect to load.
7 Trip Alarm The input is active.
8 Forced Open Forced open input is active.

HAT600N Series ATS Controller User Manual Page 14 of 24


9. TIMING START

In the main screen, press key and select 3. Timing Start, and then press key, the screen will
show the time start interface as below:

1 Exit
2 Timing start cycle
3 Load set
4 Start time
5 Continue time
Fig.5 Timing Start Screen
Time start cycle: includes inhibit start; single time, weekly or monthly.
Load set: Starting generator with load or without load.
Start time: Generator start date and time.
Continue time: Generator continuously run time can be set on the duration of maximum time for 99
hours 59 minutes.

10. DATE AND TIME SETTING

In the main screen, press key and select 4. Date & Time Set, and then press key, the screen
will show the Date & Time Set interface as below:

Date& Time Set

10-06-25 (2) 10:00

Fig.6 Date & Time Set

Press key and input corresponding bit values 0-9, press key and make bit shift to right. At the
last bit press key, so date and time can be updated.
Date and time format set: year-month-date (week) and hour: minute.

11. LANGUAGE SETTING

In the main screen, press key and select 5. Language, press again to enter into language
setting interface and the screen will show the language interface as follow:

1. Simplified Chinese
2. English

Fig.7 Language Screen

Press to select the language and press to confirm the setting.


Language option: Simplified Chinese/English.

HAT600N Series ATS Controller User Manual Page 15 of 24


12. CONTROLLER INFORMATION

In the main screen, press key and select 6. Information, and then press key, the screen will
show the controller information interface as follow:

Information
One OFF Position
1# Priority
Ver1.0 2009-10-11

Fig.8 Information Screen


Display contents include off positions setting and switching priority choice and controller version, date.
Long press key and it will exit and return to main screen.

HAT600N Series ATS Controller User Manual Page 16 of 24


13. ATS OPERATION

13.1. MANUAL OPERATION

Press key and manual operation indicator goes light, and the manual mode is active.
1) Press , 1# close relay outputs immediately, if 1# closing input is active, its indicator lights, and
the 1# source connect to load.
2) Press , 2# close relay outputs immediately, if 2# closing input is active, its indicator lights, and
the 2# source connect to load.
3) Press , 1# or 2# open relay outputs immediately, if 1# or 2# closing input is inactive, the
indicators is black, the 1# or 2# power disconnect with load.
Remark: For the ATS of no OFF position, pressing key is invalid.

13.2. AUTOMATIC OPERATION

Press and the automatic LED will light. Controller enters AUTO mode and can automatically switch
load to 1# or 2#.
13.3. ATS POWER SUPPLY
The power of ATS is smartly controlled by controller. As long as one power is normal, it can ensure ATS
voltage power supply normally and can be transferred properly.
Users should select power supply voltage (phase voltage or line voltage) based on ATS type. If phase
voltage is chosen, connect the phase voltages (e.g. A phase) of #1 and #2 separately to N/C Pin 5 and
N/O Pin 7 of auxiliary output 1; and connect N phases of #1 and #2 separately to N/C Pin8 and N/O
Pin10 of auxiliary output 2. And then connect the common output of auxiliary output1&2 to ATS power
supply. Power on the controller, and enter the parameters set page. Set aux. output 1 to "ATS power L1"
and set output 2 to "ATS power N". If the ATS power is supplied by Line Voltage, setting way is the same
as above, and it only needs to change phase N to phase voltage. Aux. output 2 also needs to be
changed based on the settings. Wiring diagrams are shown as below:

Fig.9 ATS L-N and L-L Power Supply


Note: Normally Close (NC) input voltage must come from 1# voltage.

HAT600N Series ATS Controller User Manual Page 17 of 24


14. COMMUNICATION CONFIGURATION AND CONNECTION

HAT600N series controller has RS485 serial port, which can connect the local area network openly. It
uses Modbus protocol via PC or system software. It can also be applicable to dual power switching
management for factories, telecom, industrial and civil buildings, achieving “remote control, remote
measuring, remote communication” functions.
More information about communication protocol, please refer to HAT600 Communication Protocol.
Communication parameters:
Module address 1 (range: 1-254, User can set.)
Baud rate 9600bps
Data bit 8bit
Parity bit None
Stop bit 1 bit or 2bits (set via PC)

15. DESCRIPTION OF CONNECTING TERMINALS

Fig.10 Connecting Terminal Description

HAT600N Series ATS Controller User Manual Page 18 of 24


Table 12 Functional Description of Input/Output Ports
Pin Items Description Notes
1
1# close output Volt-free relay contact output 250V16A (relay capacity)
2
3
2# close output Volt-free relay contact output 250V16A (relay capacity)
4
5 NC
Default: ATS power Volt-free relay contact output:
6 Aux. output 1 Common
of L1 output 250V16A
7 NO
8 NC
Default: ATS power Volt-free relay contact output:
9 Aux. output 2 Common
of N output 250V16A
10 NO
11 A1
12 B1 1# AC 3-phase 4 wire voltage For single phase, only connect A1,
13 C1 input N1
14 N1
15 A2
16 B2 2# AC 3-phase 4 wire voltage For single phase, only connect A2,
17 C2 input N2
18 N2
19 B- Connect battery negative DC negative input
To start engine, connect the DC positive input (8-35)V
20 B+
terminal to battery positive controller power supply
Detection of 1# switch closing
21 1# close input connect GND
state, voltage free contact input
Detection of 2# switch closing
22 2# close input connect GND
state, voltage free contact input
23 Aux. input 1
24 Aux. input 2
connect GND
25 Aux. input 3
26 Aux. input 4
27
Aux. output 3 Voltage free relay contact output 250V7A
28
29
Aux. output 4 Voltage free relay contact output 250V7A
30
31
Aux. output 5 Voltage free relay contact output 250V7A
32
33 RS485 A+
34 RS485 B- RS485 communication port
35 RS485 GND
36 IA Input Sensing from Secondary phase
37 IA Output A current
38 IB Input Sensing from Secondary phase Only suitable for
39 IB Output B current HAT600NI/HAT600NBI
40 IC Input Sensing from Secondary phase
41 IC Output C current join
LCD
LCD Display Adjust the LCD contrast
Contrast
LINK Programming port Factory update

HAT600N Series ATS Controller User Manual Page 19 of 24


16. TYPICAL WIRING DIAGRAM

Fig.11 ATYS3 Wiring Diagram

Fig.12 SGQ-N/T Wiring Diagram

HAT600N Series ATS Controller User Manual Page 20 of 24


Fig.13 SGQ-M Wiring Diagram

Fig.14 VITZRO Wiring Diagram

HAT600N Series ATS Controller User Manual Page 21 of 24


Fig.15 Contactor Wiring Diagram

Fig.16 ATYSM3S Wiring Diagram

HAT600N Series ATS Controller User Manual Page 22 of 24


Fig.17 Breaker Wiring Diagram
Remark: all above are application diagrams of HAT600N series ATS controllers. However, HAT600N and HAT600NB
have no current sample input, please skip over the current part of the diagram.

17. INSTALLATION

Unit: mm

Fig.18 Case Dimension and Cutout Size


Note: The torque of 0.27N·m (2.75kgf·cm) is recommended.

HAT600N Series ATS Controller User Manual Page 23 of 24


18. FAULT FINDING

Table 13 Fault Finding


Fault Symptom Possible Remedy
Check battery voltage
Controller no operation
Check DC fuse.
Check whether RS485 negative and positive are right connected.
Check whether RS485 converter is abnormal.
Check whether module address in the parameter settings is correct.
RS485 communication failure If the above methods are not available, try to short connect GND of
controller with RS485 converter GND (or PC GND).
It is recommended that a 120Ω resistor is added between A and B of
RS485.
Check programmable output connections, and pay attention to N/O
Programmable output error and N/C.
Check output settings in parameters settings.
Check whether the programmable input is connected to GND reliably
Programmable input abnormal when it’s active, and hung it up when it is inactive.
(Note: The input will be possibly destroyed when connected with voltage.)
Check ATS.
ATS is not work while generator Check the connection wirings between the controller and the ATS.
running Check whether breaking positions of ATS are in accordance with the
set breakings.

____________________________________

HAT600N Series ATS Controller User Manual Page 24 of 24