Application of Surge Protection Devices
Application of Surge Protection Devices
Table of Contents
1. Lightning Protection for Rooftop Solar PV Plants
2. What are lightning conductors & how do they work?
3. Lightning Protection System Design and Products
As we described in our previous blog, ‘Lightning Protection System Design and
Products’, Surge Protection Devices or SPD’s are an important part of any building’s
Internal Lightning Protection System (LPS). SPD’s are designed to protect sensitive
electronic & electrical equipment by limiting transient overvoltage and diverting surge
currents. SPD’s are the most efficient and commonly used type of overvoltage
protection for an facility or load below low voltage range.
SPD’s are designed to limit the surge voltage in terms of amplitude so that the
dielectric strength of the device is not exceeded and additionally to discharge the
surge currents associated with surge voltages to a distant ground. They perform
these activities while connected either in parallel to the equipment, between the
active conductors or between the active conductor and the protective conductor.
Whenever there is excess charge or surge in the system, the SPD behaves like a
switch and turns off (i.e. has low resistance) so that the surge current bypasses the
sensitive equipment and flows to the earthing system. Once the surge is over, the
SPD opens up and the equipment and system will work smoothly again.
LPZ 0A: Unprotected zone outside of a building where direct lightning strikes are
possible.
LPZ 0B: Zone outside the building that is protected from direct lightning strikes, for
example, by an air terminal.
LPZ 1: Zone inside the building where high-energy surge voltages or surge currents
and strong electromagnetic fields are still to be expected.
LPZ 2,…., n: Zone inside a building where surge voltages or surge currents and
electromagnetic fields that have already been significantly weakened are to be
expected.
As per IEC 62305, standard SPD’s are divided into the following categories:
1) Type 1:
2) Type 2:
Type 2 SPD’s are the main protection system for all low voltage electrical
installations. Installed in each electrical switchboard, it prevents the spread of
overvoltages in the electrical installations and protects the loads. This means that
they are installed in Zone 1 or higher.
3) Type 3:
These SPDs have a low discharge capacity. They must therefore mandatorily be
installed as a supplement to Type 2 SPD and in the vicinity of sensitive loads. This
means that they are installed in Zone 2 or higher.
Characteristics of SPD:
IEC 61643 Part 11, defines the characteristics and tests for SPD’s connected to
lower voltage distribution systems.
The SPD becomes active above this A.C. or D.C. voltage. The rated voltage and the
system earthing arrangement helps determine this value.
When the SPD is active, this is the maximum voltage across its terminals. when the
current flowing in the SPD is equal to In the voltage reached is Up. The voltage
protection level chosen must be below the overvoltage withstand capability of the
loads. In the event of lightning strikes, the voltage across the terminals of the SPD
generally remains less than Up.