0% found this document useful (0 votes)
91 views27 pages

Column K PDF

This document summarizes the design of three columns (K-1, K-2, K-3). It includes load calculations, design procedures, and reinforcement details. The columns are designed to support a 4 story building with 21 MPa concrete strength and 413 MPa steel yield strength. Column K-1 is designed with 16-Ø20 mm vertical bars and Ø10 mm ties at varying spacings. Column K-2 uses the same reinforcement as K-1. Column K-3 is also designed but some load values are shown as #REF!.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
91 views27 pages

Column K PDF

This document summarizes the design of three columns (K-1, K-2, K-3). It includes load calculations, design procedures, and reinforcement details. The columns are designed to support a 4 story building with 21 MPa concrete strength and 413 MPa steel yield strength. Column K-1 is designed with 16-Ø20 mm vertical bars and Ø10 mm ties at varying spacings. Column K-2 uses the same reinforcement as K-1. Column K-3 is also designed but some load values are shown as #REF!.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 27

DESIGN OF COLUMN

COLUMN K-1
Design Requirements:
f'c = 21 MPa LIVE LOAD
fy = 413 MPa Live load pressure = 4.8 kPa
Øc = 0.7 Total floor area = 2260 m2
ϒc = 23.54 kN/m³ Number of floors = 4
storey = 4

Load Calculation:
Column Tributary Area = 8.06 m2

DEAD LOAD (DL) Rebar cross-section area


Weight of Structure = 107094.40 kN Ø12 = 113.1 mm²
Carried by Column = 0.36 % Ø16 = 201.06 mm²
Dead Load = 381.94 kN Ø20 = 314.16 mm²
Ø25 = 490.88 mm²
LIVE LOAD (LL) Ø32 = 804.25 mm²
Total Live load = 43392 kN
Live Load Carried = 154.75 kN

SEISMIC LOAD (E)


Seismic Load = 291.85 kN

Ultimate Limit State (ULS)


factored load 1 = 1.2DL + 1.6LL
= 705.929 kN

factored load 2 = 1.2DL + 1.0LLL + 1.0E


= 904.928 kN

DESIGN LOAD
Pr = 904.93 kN

DESIGN PROCEDURE

Assume!
Po = 0.85 f'c An + fy Ast dim. = 0.7 x 0.7 m
where: vert. bars = 16-Ø20 mm
An = Agross - Ast lat. Ties = Ø10 mm
An = 487486.72 mm²

Solve for Po:


Po = 10466.212 kN

Pu = Ø 0.85 Po
Pu = 6227.396 kN
Conditon:
Pu > Pr SAFE

CHECK SLENDERNESS RATIO

𝐿𝑢 Data 1:
S.R.= 𝑟
< 34 − 12𝑀1
𝑀2
Lu = 4.5 m
S.R. = 6.429 r = 0.7 m
S.R. < 34 Good M1 = 0 kN-m
M2 = 0 kN-m
CHECK STEEL RATIO
Ast
P g= =0.01-0.08
Ag
Pg = 0.01026 GOOD

TIES
25 bar diameter = 500 mm
48 tie diameter = 480 mm
Least Dimension = 700 mm
or 300mm spacing = 300 mm USE!
DETAILING OF COLUMN
Check for Sc (vertical bar spacing )
if: Sc > 150 mm Cross Ties
Sc < 150 mm No need Cross Ties
Sc = 250 mm Cross Ties!

USE 16-20MMØ VERT. BARS, 10MMØ O.C SPACED @ 1-10, 2-50, 3-100, REST @ 300MM O.C

USE CROSS TIES


DESIGN OF COLUMN
COLUMN K-2
Design Requirements:
f'c = 21 MPa LIVE LOAD
fy = 413 MPa Live load pressure = 4.8 kPa
Øc = 0.7 Total floor area = 2260 m2
ϒc = 23.54 kN/m³ Number of floors = 4
storey = 4

Load Calculation:
2
Column Tributary Area = 18 m

DEAD LOAD (DL) Rebar cross-section area


Weight of Structure = 107094.40 kN Ø12 = 113.1 mm²
Carried by Column = 0.80 % Ø16 = 201.06 mm²
Dead Load = 852.96 kN Ø20 = 314.16 mm²
Ø25 = 490.88 mm²
LIVE LOAD (LL) Ø32 = 804.25 mm²
Total Live load = 43392 kN
Live Load Carried = 345.60 kN

SEISMIC LOAD (E)


Seismic Load = 0.00 kN

Ultimate Limit State (ULS)


factored load 1 = 1.2DL + 1.6LL
= 1576.517 kN

factored load 2 = 1.2DL + 1.0LLL + 1.0E


= 1369.157 kN

DESIGN LOAD
Pr = 1576.52 kN
DESIGN PROCEDURE

Assume!
Po = 0.85 f'c An + fy Ast dim. = 0.7 x 0.7 m
where: vert. bars = 16-Ø20 mm
An = Agross - Ast lat. Ties = Ø10 mm
An = 487486.72 mm²

Solve for Po:


Po = 10466.212 kN

Pu = Ø 0.85 Po
Pu = 6227.396 kN

Conditon:
Pu > Pr SAFE

CHECK SLENDERNESS RATIO

𝐿𝑢 Data 1:
S.R.= 𝑟
< 34 − 12𝑀1
𝑀2
Lu = 4.5 m
S.R. = 6.429 r = 0.7 m
S.R. < 34 Good M1 = 0 kN-m
M2 = 0 kN-m
CHECK STEEL RATIO
Ast
P g= =0.01-0.08
Ag
Pg = 0.01026 GOOD

TIES
25 bar diameter = 500 mm
48 tie diameter = 480 mm
Least Dimension = 700 mm
or 300mm spacing = 300 mm USE!
DETAILING OF COLUMN
Check for Sc (vertical bar spacing )
if: Sc > 150 mm Cross Ties
Sc < 150 mm No need Cross Ties
Sc = 250 mm Cross Ties!
USE 16-20MMØ VERT. BARS, 10MMØ O.C SPACED @ 1-10, 2-50, 3-100, REST @ 300MM O.C

USE CROSS TIES


DESIGN OF COLUMN
COLUMN K-3
Design Requirements:
f'c = 21 MPa LIVE LOAD
fy = 413 MPa Live load pressure = 4.8 kPa
Øc = 0.7 Total floor area = 2260 m2
ϒc = 23.54 kN/m³ Number of floors = 4
storey = 4

Load Calculation:
2
Column Tributary Area = 18 m

DEAD LOAD (DL) Rebar cross-section area


Weight of Structure = #REF! kN Ø12 = 113.1 mm²
Carried by Column = 0.80 % Ø16 = 201.06 mm²
Dead Load = #REF! kN Ø20 = 314.16 mm²
Ø25 = 490.88 mm²
LIVE LOAD (LL) Ø32 = 804.25 mm²
Total Live load = 43392 kN
Live Load Carried = 345.60 kN

SEISMIC LOAD (E)


Seismic Load = 0.00 kN

Ultimate Limit State (ULS)


factored load 1 = 1.2DL + 1.6LL
= #REF! kN

factored load 2 = 1.2DL + 1.0LLL + 1.0E


= #REF! kN

DESIGN LOAD
Pr = #REF! kN
DESIGN PROCEDURE

Assume!
Po = 0.85 f'c An + fy Ast dim. = 0.7 x 0.7 m
where: vert. bars = 16-Ø20 mm
An = Agross - Ast lat. Ties = Ø10 mm
An = 487486.72 mm²

Solve for Po:


Po = 10466.212 kN

Pu = Ø 0.85 Po
Pu = 6227.396 kN

Conditon:
Pu > Pr #REF!

CHECK SLENDERNESS RATIO

𝐿𝑢 Data 1:
S.R.= 𝑟
< 34 − 12𝑀1
𝑀2
Lu = 4.5 m
S.R. = 6.429 r = 0.7 m
S.R. < 34 Good M1 = 0 kN-m
M2 = 0 kN-m
CHECK STEEL RATIO
Ast
P g= =0.01-0.08
Ag
Pg = 0.01026 GOOD

TIES
25 bar diameter = 500 mm
48 tie diameter = 480 mm
Least Dimension = 700 mm
or 300mm spacing = 300 mm USE!
DETAILING OF COLUMN
Check for Sc (vertical bar spacing )
if: Sc > 150 mm Cross Ties
Sc < 150 mm No need Cross Ties
Sc = 250 mm Cross Ties!
USE 16-20MMØ VERT. BARS, 10MMØ O.C SPACED @ 1-10, 2-50, 3-100, REST @ 300MM O.C

USE CROSS TIES


DESIGN OF COLUMN
COLUMN K-4
Design Requirements:
f'c = 21 MPa LIVE LOAD
fy = 413 MPa Live load pressure = 4.8 kPa
Øc = 0.7 Total floor area = 2260 m2
ϒc = 23.54 kN/m³ Number of floors = 4
storey = 4

Load Calculation:
2
Column Tributary Area = 18 m

DEAD LOAD (DL) Rebar cross-section area


Weight of Structure = #REF! kN Ø12 = 113.1 mm²
Carried by Column = 0.80 % Ø16 = 201.06 mm²
Dead Load = #REF! kN Ø20 = 314.16 mm²
Ø25 = 490.88 mm²
LIVE LOAD (LL) Ø32 = 804.25 mm²
Total Live load = 43392 kN
Live Load Carried = 345.60 kN

SEISMIC LOAD (E)


Seismic Load = 0.00 kN

Ultimate Limit State (ULS)


factored load 1 = 1.2DL + 1.6LL
= #REF! kN

factored load 2 = 1.2DL + 1.0LLL + 1.0E


= #REF! kN

DESIGN LOAD
Pr = #REF! kN
DESIGN PROCEDURE

Assume!
Po = 0.85 f'c An + fy Ast dim. = 0.7 x 0.7 m
where: vert. bars = 16-Ø20 mm
An = Agross - Ast lat. Ties = Ø10 mm
An = 487486.72 mm²

Solve for Po:


Po = 10466.212 kN

Pu = Ø 0.85 Po
Pu = 6227.396 kN

Conditon:
Pu > Pr #REF!

CHECK SLENDERNESS RATIO

𝐿𝑢 Data 1:
S.R.= 𝑟
< 34 − 12𝑀1
𝑀2
Lu = 4.5 m
S.R. = 6.429 r = 0.7 m
S.R. < 34 Good M1 = 0 kN-m
M2 = 0 kN-m
CHECK STEEL RATIO
Ast
P g= =0.01-0.08
Ag
Pg = 0.01026 GOOD

TIES
25 bar diameter = 500 mm
48 tie diameter = 480 mm
Least Dimension = 700 mm
or 300mm spacing = 300 mm USE!
DETAILING OF COLUMN
Check for Sc (vertical bar spacing )
if: Sc > 150 mm Cross Ties
Sc < 150 mm No need Cross Ties
Sc = 250 mm Cross Ties!
USE 16-20MMØ VERT. BARS, 10MMØ O.C SPACED @ 1-10, 2-50, 3-100, REST @ 300MM O.C

USE CROSS TIES


DESIGN OF COLUMN
COLUMN K-5
Design Requirements:
f'c = 21 MPa LIVE LOAD
fy = 413 MPa Live load pressure = 4.8 kPa
Øc = 0.7 Total floor area = 2260 m2
ϒc = 23.54 kN/m³ Number of floors = 4
storey = 4

Load Calculation:
2
Column Tributary Area = 18 m

DEAD LOAD (DL) Rebar cross-section area


Weight of Structure = 107094.40 kN Ø12 = 113.1 mm²
Carried by Column = 0.80 % Ø16 = 201.06 mm²
Dead Load = 852.96 kN Ø20 = 314.16 mm²
Ø25 = 490.88 mm²
LIVE LOAD (LL) Ø32 = 804.25 mm²
Total Live load = 43392 kN
Live Load Carried = 345.60 kN

SEISMIC LOAD (E)


Seismic Load = 0.00 kN

Ultimate Limit State (ULS)


factored load 1 = 1.2DL + 1.6LL
= 1576.517 kN

factored load 2 = 1.2DL + 1.0LLL + 1.0E


= 1369.157 kN

DESIGN LOAD
Pr = 1576.52 kN
DESIGN PROCEDURE

Assume!
Po = 0.85 f'c An + fy Ast dim. = 0.7 x 0.7 m
where: vert. bars = 16-Ø20 mm
An = Agross - Ast lat. Ties = Ø10 mm
An = 487486.72 mm²

Solve for Po:


Po = 10466.212 kN

Pu = Ø 0.85 Po
Pu = 6227.396 kN

Conditon:
Pu > Pr SAFE

CHECK SLENDERNESS RATIO

𝐿𝑢 Data 1:
S.R.= 𝑟
< 34 − 12𝑀1
𝑀2
Lu = 4.5 m
S.R. = 6.429 r = 0.7 m
S.R. < 34 Good M1 = 0 kN-m
M2 = 0 kN-m
CHECK STEEL RATIO
Ast
P g= =0.01-0.08
Ag
Pg = 0.01026 GOOD

TIES
25 bar diameter = 500 mm
48 tie diameter = 480 mm
Least Dimension = 700 mm
or 300mm spacing = 300 mm USE!
DETAILING OF COLUMN
Check for Sc (vertical bar spacing )
if: Sc > 150 mm Cross Ties
Sc < 150 mm No need Cross Ties
Sc = 250 mm Cross Ties!
USE 16-20MMØ VERT. BARS, 10MMØ O.C SPACED @ 1-10, 2-50, 3-100, REST @ 300MM O.C

USE CROSS TIES


DESIGN OF COLUMN
COLUMN K-6
Design Requirements:
f'c = 21 MPa LIVE LOAD
fy = 413 MPa Live load pressure = 4.8 kPa
Øc = 0.7 Total floor area = 2260 m2
ϒc = 23.54 kN/m³ Number of floors = 4
storey = 4

Load Calculation:
2
Column Tributary Area = 18 m

DEAD LOAD (DL) Rebar cross-section area


Weight of Structure = #REF! kN Ø12 = 113.1 mm²
Carried by Column = 0.80 % Ø16 = 201.06 mm²
Dead Load = #REF! kN Ø20 = 314.16 mm²
Ø25 = 490.88 mm²
LIVE LOAD (LL) Ø32 = 804.25 mm²
Total Live load = 43392 kN
Live Load Carried = 345.60 kN

SEISMIC LOAD (E)


Seismic Load = 0.00 kN

Ultimate Limit State (ULS)


factored load 1 = 1.2DL + 1.6LL
= #REF! kN

factored load 2 = 1.2DL + 1.0LLL + 1.0E


= #REF! kN

DESIGN LOAD
Pr = #REF! kN
DESIGN PROCEDURE

Assume!
Po = 0.85 f'c An + fy Ast dim. = 0.7 x 0.7 m
where: vert. bars = 16-Ø20 mm
An = Agross - Ast lat. Ties = Ø10 mm
An = 487486.72 mm²

Solve for Po:


Po = 10466.212 kN

Pu = Ø 0.85 Po
Pu = 6227.396 kN

Conditon:
Pu > Pr #REF!

CHECK SLENDERNESS RATIO

𝐿𝑢 Data 1:
S.R.= 𝑟
< 34 − 12𝑀1
𝑀2
Lu = 4.5 m
S.R. = 6.429 r = 0.7 m
S.R. < 34 Good M1 = 0 kN-m
M2 = 0 kN-m
CHECK STEEL RATIO
Ast
P g= =0.01-0.08
Ag
Pg = 0.01026 GOOD

TIES
25 bar diameter = 500 mm
48 tie diameter = 480 mm
Least Dimension = 700 mm
or 300mm spacing = 300 mm USE!
DETAILING OF COLUMN
Check for Sc (vertical bar spacing )
if: Sc > 150 mm Cross Ties
Sc < 150 mm No need Cross Ties
Sc = 250 mm Cross Ties!
USE 16-20MMØ VERT. BARS, 10MMØ O.C SPACED @ 1-10, 2-50, 3-100, REST @ 300MM O.C

USE CROSS TIES


DESIGN OF COLUMN
COLUMN K-7
Design Requirements:
f'c = 21 MPa LIVE LOAD
fy = 413 MPa Live load pressure = 4.8 kPa
Øc = 0.7 Total floor area = 2260 m2
ϒc = 23.54 kN/m³ Number of floors = 4
storey = 4

Load Calculation:
2
Column Tributary Area = 18 m

DEAD LOAD (DL) Rebar cross-section area


Weight of Structure = 107094.40 kN Ø12 = 113.1 mm²
Carried by Column = 0.80 % Ø16 = 201.06 mm²
Dead Load = 852.96 kN Ø20 = 314.16 mm²
Ø25 = 490.88 mm²
LIVE LOAD (LL) Ø32 = 804.25 mm²
Total Live load = 43392 kN
Live Load Carried = 345.60 kN

SEISMIC LOAD (E)


Seismic Load = 0.00 kN

Ultimate Limit State (ULS)


factored load 1 = 1.2DL + 1.6LL
= 1576.517 kN

factored load 2 = 1.2DL + 1.0LLL + 1.0E


= 1369.157 kN

DESIGN LOAD
Pr = 1576.52 kN
DESIGN PROCEDURE

Assume!
Po = 0.85 f'c An + fy Ast dim. = 0.7 x 0.7 m
where: vert. bars = 16-Ø20 mm
An = Agross - Ast lat. Ties = Ø10 mm
An = 487486.72 mm²

Solve for Po:


Po = 10466.212 kN

Pu = Ø 0.85 Po
Pu = 6227.396 kN

Conditon:
Pu > Pr SAFE

CHECK SLENDERNESS RATIO

𝐿𝑢 Data 1:
S.R.= 𝑟
< 34 − 12𝑀1
𝑀2
Lu = 4.5 m
S.R. = 6.429 r = 0.7 m
S.R. < 34 Good M1 = 0 kN-m
M2 = 0 kN-m
CHECK STEEL RATIO
Ast
P g= =0.01-0.08
Ag
Pg = 0.01026 GOOD

TIES
25 bar diameter = 500 mm
48 tie diameter = 480 mm
Least Dimension = 700 mm
or 300mm spacing = 300 mm USE!
DETAILING OF COLUMN
Check for Sc (vertical bar spacing )
if: Sc > 150 mm Cross Ties
Sc < 150 mm No need Cross Ties
Sc = 250 mm Cross Ties!
USE 16-20MMØ VERT. BARS, 10MMØ O.C SPACED @ 1-10, 2-50, 3-100, REST @ 300MM O.C

USE CROSS TIES


DESIGN OF COLUMN
COLUMN K-8
Design Requirements:
f'c = 21 MPa LIVE LOAD
fy = 413 MPa Live load pressure = 4.8 kPa
Øc = 0.7 Total floor area = 2260 m2
ϒc = 23.54 kN/m³ Number of floors = 4
storey = 4

Load Calculation:
2
Column Tributary Area = 18 m

DEAD LOAD (DL) Rebar cross-section area


Weight of Structure = 107094.40 kN Ø12 = 113.1 mm²
Carried by Column = 0.80 % Ø16 = 201.06 mm²
Dead Load = 852.96 kN Ø20 = 314.16 mm²
Ø25 = 490.88 mm²
LIVE LOAD (LL) Ø32 = 804.25 mm²
Total Live load = 43392 kN
Live Load Carried = 345.60 kN

SEISMIC LOAD (E)


Seismic Load = 0.00 kN

Ultimate Limit State (ULS)


factored load 1 = 1.2DL + 1.6LL
= 1576.517 kN

factored load 2 = 1.2DL + 1.0LLL + 1.0E


= 1369.157 kN

DESIGN LOAD
Pr = 1576.52 kN
DESIGN PROCEDURE

Assume!
Po = 0.85 f'c An + fy Ast dim. = 0.7 x 0.7 m
where: vert. bars = 16-Ø20 mm
An = Agross - Ast lat. Ties = Ø10 mm
An = 487486.72 mm²

Solve for Po:


Po = 10466.212 kN

Pu = Ø 0.85 Po
Pu = 6227.396 kN

Conditon:
Pu > Pr SAFE

CHECK SLENDERNESS RATIO

𝐿𝑢 Data 1:
S.R.= 𝑟
< 34 − 12𝑀1
𝑀2
Lu = 4.5 m
S.R. = 6.429 r = 0.7 m
S.R. < 34 Good M1 = 0 kN-m
M2 = 0 kN-m
CHECK STEEL RATIO
Ast
P g= =0.01-0.08
Ag
Pg = 0.01026 GOOD

TIES
25 bar diameter = 500 mm
48 tie diameter = 480 mm
Least Dimension = 700 mm
or 300mm spacing = 300 mm USE!
DETAILING OF COLUMN
Check for Sc (vertical bar spacing )
if: Sc > 150 mm Cross Ties
Sc < 150 mm No need Cross Ties
Sc = 250 mm Cross Ties!
USE 16-20MMØ VERT. BARS, 10MMØ O.C SPACED @ 1-10, 2-50, 3-100, REST @ 300MM O.C

USE CROSS TIES


DESIGN OF COLUMN
COLUMN K-9
Design Requirements:
f'c = 21 MPa LIVE LOAD
fy = 413 MPa Live load pressure = 4.8 kPa
Øc = 0.7 Total floor area = 2260 m2
ϒc = 23.54 kN/m³ Number of floors = 4
storey = 4

Load Calculation:
2
Column Tributary Area = 18 m

DEAD LOAD (DL) Rebar cross-section area


Weight of Structure = 107094.40 kN Ø12 = 113.1 mm²
Carried by Column = 0.80 % Ø16 = 201.06 mm²
Dead Load = 852.96 kN Ø20 = 314.16 mm²
Ø25 = 490.88 mm²
LIVE LOAD (LL) Ø32 = 804.25 mm²
Total Live load = 43392 kN
Live Load Carried = 345.60 kN

SEISMIC LOAD (E)


Seismic Load = 0.00 kN

Ultimate Limit State (ULS)


factored load 1 = 1.2DL + 1.6LL
= 1576.517 kN

factored load 2 = 1.2DL + 1.0LLL + 1.0E


= 1369.157 kN

DESIGN LOAD
Pr = 1576.52 kN
DESIGN PROCEDURE

Assume!
Po = 0.85 f'c An + fy Ast dim. = 0.7 x 0.7 m
where: vert. bars = 16-Ø20 mm
An = Agross - Ast lat. Ties = Ø10 mm
An = 487486.72 mm²

Solve for Po:


Po = 10466.212 kN

Pu = Ø 0.85 Po
Pu = 6227.396 kN

Conditon:
Pu > Pr SAFE

CHECK SLENDERNESS RATIO

𝐿𝑢 Data 1:
S.R.= 𝑟
< 34 − 12𝑀1
𝑀2
Lu = 4.5 m
S.R. = 6.429 r = 0.7 m
S.R. < 34 Good M1 = 0 kN-m
M2 = 0 kN-m
CHECK STEEL RATIO
Ast
P g= =0.01-0.08
Ag
Pg = 0.01026 GOOD

TIES
25 bar diameter = 500 mm
48 tie diameter = 480 mm
Least Dimension = 700 mm
or 300mm spacing = 300 mm USE!
DETAILING OF COLUMN
Check for Sc (vertical bar spacing )
if: Sc > 150 mm Cross Ties
Sc < 150 mm No need Cross Ties
Sc = 250 mm Cross Ties!
USE 16-20MMØ VERT. BARS, 10MMØ O.C SPACED @ 1-10, 2-50, 3-100, REST @ 300MM O.C

USE CROSS TIES


Calculated Dead weight (from Seismic Analysis)
WT = W1 + W2 + W3 + W4
WT = 28704.08 + 27962.82 + 27428.82 + 22998.69
WT = 107094.4 KN

Calculated Dead weight (from Seismic Analysis)


WT = W1 + W2 + W3 + W4
WT = 28704.08 + 27962.82 + 27428.82 + 22998.69
WT = 107094.4 KN

Calculated Dead weight (from Seismic Analysis)


WT = W1 + W2 + W3 + W4
WT = 28704.08 + 27962.82 + 27428.82 + 22998.69
WT = 107094.4 KN

Calculated Dead weight (from Seismic Analysis)


WT = W1 + W2 + W3 + W4
WT = 28704.08 + 27962.82 + 27428.82 + 22998.69
WT = 107094.4 KN

Calculated Dead weight (from Seismic Analysis)


WT = W1 + W2 + W3 + W4
WT = 28704.08 + 27962.82 + 27428.82 + 22998.69
WT = 107094.4 KN

Calculated Dead weight (from Seismic Analysis)


WT = W1 + W2 + W3 + W4
WT = 28704.08 + 27962.82 + 27428.82 + 22998.69
WT = 107094.4 KN