G60man w1 PDF
G60man w1 PDF
G60man w1 PDF
g
GE Multilin
830715A2.CDR
E83849
T
GIS ERE
RE
GE Multilin ISO9001:2000
LISTED EM I
G
*1601-0110-W1*
Addendum
g
GE Multilin
ADDENDUM
This addendum contains information that relates to the G60 Generator Protection System, version 5.9x. This addendum
lists a number of information items that appear in the instruction manual GEK-113381 (revision W1) but are not included
in the current G60 operations.
The following functions and items are not yet available with the current version of the G60 relay:
• Signal sources SRC 5 and SRC 6.
Version 4.0x and higher releases of the G60 relay includes new hardware (CPU and CT/VT modules).
• The new CPU modules are specified with the following order codes: 9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S.
• The new CT/VT modules are specified with the following order codes: 8F, 8G, 8H, 8J 8L, 8M, 8N, 8R.
The following table maps the relationship between the old CPU and CT/VT modules to the newer versions:
The new CT/VT modules can only be used with the new CPUs (9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S), and
the old CT/VT modules can only be used with the old CPU modules (9A, 9C, 9D). To prevent any hardware mis-
matches, the new CPU and CT/VT modules have blue labels and a warning sticker stating “Attn.: Ensure CPU and
DSP module label colors are the same!”. In the event that there is a mismatch between the CPU and CT/VT module,
the relay will not function and a DSP ERROR or HARDWARE MISMATCH error will be displayed.
All other input/output modules are compatible with the new hardware.
With respect to the firmware, firmware versions 4.0x and higher are only compatible with the new CPU and CT/VT mod-
ules. Previous versions of the firmware (3.4x and earlier) are only compatible with the older CPU and CT/VT modules.
Table of Contents
TABLE OF CONTENTS
5.8 INPUTS/OUTPUTS
5.8.1 CONTACT INPUTS ........................................................................................5-246
5.8.2 VIRTUAL INPUTS ..........................................................................................5-248
5.8.3 CONTACT OUTPUTS ....................................................................................5-249
5.8.4 VIRTUAL OUTPUTS ......................................................................................5-251
5.8.5 REMOTE DEVICES........................................................................................5-252
5.8.6 REMOTE INPUTS ..........................................................................................5-253
5.8.7 REMOTE DOUBLE-POINT STATUS INPUTS ...............................................5-254
5.8.8 REMOTE OUTPUTS ......................................................................................5-254
5.8.9 RESETTING ...................................................................................................5-255
5.8.10 DIRECT INPUTS AND OUTPUTS..................................................................5-256
5.8.11 TELEPROTECTION INPUTS AND OUTPUTS ..............................................5-259
5.8.12 IEC 61850 GOOSE ANALOGS ......................................................................5-261
5.8.13 IEC 61850 GOOSE INTEGERS .....................................................................5-262
5.9 TRANSDUCER INPUTS AND OUTPUTS
5.9.1 DCMA INPUTS ...............................................................................................5-263
5.9.2 RTD INPUTS ..................................................................................................5-264
5.9.3 RRTD INPUTS................................................................................................5-266
5.9.4 DCMA OUTPUTS ...........................................................................................5-270
5.10 TESTING
5.10.1 TEST MODE ...................................................................................................5-274
5.10.2 FORCE CONTACT INPUTS...........................................................................5-275
5.10.3 FORCE CONTACT OUTPUTS.......................................................................5-276
5.10.4 PHASOR MEASUREMENT UNIT TEST VALUES .........................................5-277
INDEX
Before attempting to install or use the relay, it is imperative that all NOTE, CAUTION and WARNING icons in this document
are reviewed to help prevent personal injury, equipment damage, or downtime.
WARNING CAUTION
1.1.2 INSPECTION CHECKLIST
1. Open the relay packaging and inspect the unit for physical damage.
2. View the rear nameplate and verify that the correct model has been ordered.
Model: G60D00HCHF8AH6AM6BP8BX7A
Technical Support:
Made in
Tel: (905) 294-6222 http://www.GEmultilin.com ®
®
Canada
Fax: (905) 201-2098 - M A A B 9 7 0 0 0 0 9 9 -
830742A1.CDR
1 Historically, substation protection, control, and metering functions were performed with electromechanical equipment. This
first generation of equipment was gradually replaced by analog electronic equipment, most of which emulated the single-
function approach of their electromechanical precursors. Both of these technologies required expensive cabling and auxil-
iary equipment to produce functioning systems.
Recently, digital electronic equipment has begun to provide protection, control, and metering functions. Initially, this equip-
ment was either single function or had very limited multi-function capability, and did not significantly reduce the cabling and
auxiliary equipment required. However, recent digital relays have become quite multi-functional, reducing cabling and aux-
iliaries significantly. These devices also transfer data to central control facilities and Human Machine Interfaces using elec-
tronic communications. The functions performed by these products have become so broad that many users now prefer the
term IED (Intelligent Electronic Device).
It is obvious to station designers that the amount of cabling and auxiliary equipment installed in stations can be even further
reduced, to 20% to 70% of the levels common in 1990, to achieve large cost reductions. This requires placing even more
functions within the IEDs.
Users of power equipment are also interested in reducing cost by improving power quality and personnel productivity, and
as always, in increasing system reliability and efficiency. These objectives are realized through software which is used to
perform functions at both the station and supervisory levels. The use of these systems is growing rapidly.
High speed communications are required to meet the data transfer rates required by modern automatic control and moni-
toring systems. In the near future, very high speed communications will be required to perform protection signaling with a
performance target response time for a command signal between two IEDs, from transmission to reception, of less than 3
milliseconds. This has been established by the IEC 61850 standard.
IEDs with the capabilities outlined above will also provide significantly more power system data than is presently available,
enhance operations and maintenance, and permit the use of adaptive system configuration for protection and control sys-
tems. This new generation of equipment must also be easily incorporated into automation systems, at both the station and
enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals.
a) UR BASIC DESIGN 1
The UR is a digital-based device containing a central processing unit (CPU) that handles multiple types of input and output
signals. The UR can communicate over a local area network (LAN) with an operator interface, a programming device, or
another UR device.
LAN
Programming Operator
Device Interface
827822A2.CDR
b) UR SIGNAL TYPES
The contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Both ‘wet’ and ‘dry’
contacts are supported.
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic™ equations used to customize
the device. Virtual outputs can also serve as virtual inputs to FlexLogic™ equations.
The analog inputs and outputs are signals that are associated with transducers, such as Resistance Temperature Detec-
tors (RTDs).
The CT and VT inputs refer to analog current transformer and voltage transformer signals used to monitor AC power lines.
The UR-series relays support 1 A and 5 A CTs.
The remote inputs and outputs provide a means of sharing digital point state information between remote UR-series
devices. The remote outputs interface to the remote inputs of other UR-series devices. Remote outputs are FlexLogic™
operands inserted into IEC 61850 GSSE and GOOSE messages.
The direct inputs and outputs provide a means of sharing digital point states between a number of UR-series IEDs over a
dedicated fiber (single or multimode), RS422, or G.703 interface. No switching equipment is required as the IEDs are con-
nected directly in a ring or redundant (dual) ring configuration. This feature is optimized for speed and intended for pilot-
aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis.
c) UR SCAN OPERATION
1 The UR-series devices operate in a cyclic scan fashion. The device reads the inputs into an input status table, solves the
logic program (FlexLogic™ equation), and then sets each output to the appropriate state in an output status table. Any
resulting task execution is priority interrupt-driven.
Read Inputs
Protection elements
serviced by sub-scan
Protective Elements
PKP
Solve Logic DPO
OP
Set Outputs
827823A1.CDR
The firmware (software embedded in the relay) is designed in functional modules which can be installed in any relay as
required. This is achieved with object-oriented design and programming (OOD/OOP) techniques.
Object-oriented techniques involve the use of objects and classes. An object is defined as “a logical entity that contains
both data and code that manipulates that data”. A class is the generalized form of similar objects. By using this concept,
one can create a protection class with the protection elements as objects of the class, such as time overcurrent, instanta-
neous overcurrent, current differential, undervoltage, overvoltage, underfrequency, and distance. These objects represent
completely self-contained software modules. The same object-class concept can be used for metering, input/output control,
hmi, communications, or any functional entity in the system.
Employing OOD/OOP in the software architecture of the G60 achieves the same features as the hardware architecture:
modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection,
transformer protection, distance protection) is constructed by combining objects from the various functionality classes. This
results in a common look and feel across the entire family of UR-series platform-based applications.
As described above, the architecture of the UR-series relays differ from previous devices. To achieve a general understand-
ing of this device, some sections of Chapter 5 are quite helpful. The most important functions of the relay are contained in
“elements”. A description of the UR-series elements can be found in the Introduction to elements section in chapter 5.
Examples of simple elements, and some of the organization of this manual, can be found in the Control elements section of
chapter 5. An explanation of the use of inputs from CTs and VTs is in the Introduction to AC sources section in chapter 5. A
description of how digital signals are used and routed within the relay is contained in the Introduction to FlexLogic™ section
in chapter 5.
The faceplate keypad and display or the EnerVista UR Setup software interface can be used to communicate with the relay.
1
The EnerVista UR Setup software interface is the preferred method to edit settings and view actual values because the PC
monitor can display more information in a simple comprehensible format.
The following minimum requirements must be met for the EnerVista UR Setup software to properly operate on a PC.
• Pentium class or higher processor (Pentium II 300 MHz or higher recommended)
• Windows 95, 98, 98SE, ME, NT 4.0 (Service Pack 4 or higher), 2000, XP
• Internet Explorer 4.0 or higher
• 128 MB of RAM (256 MB recommended)
• 200 MB of available space on system drive and 200 MB of available space on installation drive
• Video capable of displaying 800 x 600 or higher in high-color mode (16-bit color)
• RS232 and/or Ethernet port for communications to the relay
The following qualified modems have been tested to be compliant with the G60 and the EnerVista UR Setup software.
• US Robotics external 56K FaxModem 5686
• US Robotics external Sportster 56K X2
• PCTEL 2304WT V.92 MDC internal modem
1.3.2 INSTALLATION
After ensuring the minimum requirements for using EnerVista UR Setup are met (see previous section), use the following
procedure to install the EnerVista UR Setup from the enclosed GE EnerVista CD.
1. Insert the GE EnerVista CD into your CD-ROM drive.
2. Click the Install Now button and follow the installation instructions to install the no-charge EnerVista software.
3. When installation is complete, start the EnerVista Launchpad application.
4. Click the IED Setup section of the Launch Pad window.
5. In the EnerVista Launch Pad window, click the Add Product button and select the “G60 Generator Protection System”
from the Install Software window as shown below. Select the “Web” option to ensure the most recent software release,
1 or select “CD” if you do not have a web connection, then click the Add Now button to list software items for the G60.
6. EnerVista Launchpad will obtain the software from the Web or CD and automatically start the installation program.
7. Select the complete path, including the new directory name, where the EnerVista UR Setup will be installed.
8. Click on Next to begin the installation. The files will be installed in the directory indicated and the installation program
will automatically create icons and add EnerVista UR Setup to the Windows start menu.
9. Click Finish to end the installation. The UR-series device will be added to the list of installed IEDs in the EnerVista
Launchpad window, as shown below.
a) OVERVIEW 1
The user can connect remotely to the G60 through the rear RS485 port or the rear Ethernet port with a PC running the
EnerVista UR Setup software. The G60 can also be accessed locally with a laptop computer through the front panel RS232
port or the rear Ethernet port using the Quick Connect feature.
• To configure the G60 for remote access via the rear RS485 port(s), refer to the Configuring Serial Communications
section.
• To configure the G60 for remote access via the rear Ethernet port, refer to the Configuring Ethernet Communications
section. An Ethernet module must be specified at the time of ordering.
• To configure the G60 for local access with a laptop through either the front RS232 port or rear Ethernet port, refer to
the Using the Quick Connect Feature section. An Ethernet module must be specified at the time of ordering for Ether-
net communications.
8. Select “Serial” from the Interface drop-down list. This will display a number of interface parameters that must be
entered for proper serial communications.
1
8. Select “Ethernet” from the Interface drop-down list. This will display a number of interface parameters that must be
entered for proper Ethernet functionality.
1
11. Click the Read Order Code button to connect to the G60 device and upload the order code. If an communications
error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay
setting values.
12. Click OK when the relay order code has been received. The new device will be added to the Site List window (or
Online window) located in the top left corner of the main EnerVista UR Setup window.
The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the G60 section to
begin communications.
3. Click the Quick Connect button to open the Quick Connect dialog box.
4. Select the Serial interface and the correct COM Port, then click Connect.
5. The EnerVista UR Setup software will create a site named “Quick Connect” with a corresponding device also named
“Quick Connect” and display them on the upper-left corner of the screen. Expand the sections to view data directly
from the G60 device.
Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica-
tions to the G60. This ensures that configuration of the EnerVista UR Setup software matches the G60 model number.
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con-
nections window.
1
3. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
5. Enter an IP address with the first three numbers the same as the IP address of the G60 relay and the last number dif-
ferent (in this example, 1.1.1.2).
1 6. Enter a subnet mask equal to the one set in the G60 (in this example, 255.0.0.0).
7. Click OK to save the values.
Before continuing, it will be necessary to test the Ethernet connection.
1. Open a Windows console window by selecting Start > Run from the Windows Start menu and typing “cmd”.
2. Type the following command:
C:\WINNT>ping 1.1.1.1
3. If the connection is successful, the system will return four replies as follows:
Pinging 1.1.1.1 with 32 bytes of data:
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 4, Lost = 0 (0% loss),
Approximate round trip time in milli-seconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
4. Note that the values for time and TTL will vary depending on local network configuration.
If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data:
Request timed out.
Request timed out.
Request timed out.
Request timed out.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milli-seconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
Verify the physical connection between the G60 and the laptop computer, and double-check the programmed IP address in
the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK Ö IP ADDRESS setting, then repeat step 2 in the above procedure.
If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data:
Hardware error.
Hardware error.
Hardware error.
Hardware error.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milli-seconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
Verify the physical connection between the G60 and the laptop computer, and double-check the programmed IP address in
the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK Ö IP ADDRESS setting, then repeat step 2 in the above procedure.
If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
4. Ensure that the “Use a proxy server for your LAN” box is not checked.
If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon-
nected from the G60 relay.
1. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or
online from http://www.GEmultilin.com). See the Software Installation section for installation details.
2. Start the Internet Explorer software.
3. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
1 4. Click the Quick Connect button to open the Quick Connect dialog box.
5. Select the Ethernet interface and enter the IP address assigned to the G60, then click Connect.
6. The EnerVista UR Setup software will create a site named “Quick Connect” with a corresponding device also named
“Quick Connect” and display them on the upper-left corner of the screen. Expand the sections to view data directly
from the G60 device.
Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica-
tions to the G60. This ensures that configuration of the EnerVista UR Setup software matches the G60 model number.
When direct communications with the G60 via Ethernet is complete, make the following changes:
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con-
nections window.
2. Right-click the Local Area Connection icon and select the Properties item.
3. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
4. Set the computer to “Obtain a relay address automatically” as shown below.
If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon-
nected from the G60 relay.
AUTOMATIC DISCOVERY OF ETHERNET DEVICES
The EnerVista UR Setup software can automatically discover and communicate to all UR-series IEDs located on an Ether-
net network.
Using the Quick Connect feature, a single click of the mouse will trigger the software to automatically detect any UR-series
relays located on the network. The EnerVista UR Setup software will then proceed to configure all settings and order code
options in the Device Setup menu, for the purpose of communicating to multiple relays. This feature allows the user to
identify and interrogate, in seconds, all UR-series devices in a particular location.
1. Open the Display Properties window through the Site List tree as shown below:
1
842743A3.CDR
2. The Display Properties window will open with a status indicator on the lower left of the EnerVista UR Setup window.
3. If the status indicator is red, verify that the Ethernet network cable is properly connected to the Ethernet port on the
back of the relay and that the relay has been properly setup for communications (steps A and B earlier).
If a relay icon appears in place of the status indicator, than a report (such as an oscillography or event record) is open.
Close the report to re-display the green status indicator.
4. The Display Properties settings can now be edited, printed, or changed according to user specifications.
Refer to chapter 4 in this manual and the EnerVista UR Setup Help File for more information about the
using the EnerVista UR Setup software interface.
NOTE
1 Please refer to Chapter 3: Hardware for detailed mounting and wiring instructions. Review all WARNINGS and CAUTIONS
carefully.
1.4.2 COMMUNICATIONS
The EnerVista UR Setup software communicates to the relay via the faceplate RS232 port or the rear panel RS485 / Ether-
net ports. To communicate via the faceplate RS232 port, a standard straight-through serial cable is used. The DB-9 male
end is connected to the relay and the DB-9 or DB-25 female end is connected to the PC COM1 or COM2 port as described
in the CPU communications ports section of chapter 3.
All messages are displayed on a 2 × 20 backlit liquid crystal display (LCD) to make them visible under poor lighting condi-
tions. Messages are descriptive and should not require the aid of an instruction manual for deciphering. While the keypad
and display are not actively being used, the display will default to user-defined messages. Any high priority event driven
message will automatically override the default message and appear on the display.
Display messages are organized into pages under the following headings: actual values, settings, commands, and targets.
1
The MENU key navigates through these pages. Each heading page is broken down further into logical subgroups.
The MESSAGE keys navigate through the subgroups. The VALUE keys scroll increment or decrement numerical setting
values when in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alterna-
tively, values may also be entered with the numeric keypad.
The decimal key initiates and advance to the next character in text edit mode or enters a decimal point. The HELP key may
be pressed at any time for context sensitive help messages. The ENTER key stores altered setting values.
Press the MENU key to select the desired header display page (top-level menu). The header title appears momentarily fol-
lowed by a header display page menu item. Each press of the MENU key advances through the following main heading
pages:
• Actual values.
• Settings.
• Commands.
• Targets.
• User displays (when enabled).
The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double
scroll bar characters (), while sub-header pages are indicated by single scroll bar characters (). The header display
pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE
UP and DOWN keys move within a group of headers, sub-headers, setting values, or actual values. Continually pressing
the MESSAGE RIGHT key from a header display displays specific information for the header category. Conversely, contin-
ually pressing the MESSAGE LEFT key from a setting value or actual value display returns to the header display.
SETTINGS
SYSTEM SETUP
The relay is defaulted to the “Not Programmed” state when it leaves the factory. This safeguards against the installation of
a relay whose settings have not been entered. When powered up successfully, the Trouble LED will be on and the In Ser-
vice LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain
until the relay is explicitly put in the “Programmed” state.
Select the menu message SETTINGS Ö PRODUCT SETUP ÖØ INSTALLATION Ö RELAY SETTINGS
RELAY SETTINGS:
Not Programmed
To put the relay in the “Programmed” state, press either of the VALUE keys once and then press ENTER. The faceplate
Trouble LED will turn off and the In Service LED will turn on. The settings for the relay can be programmed manually (refer
1 to Chapter 5) via the faceplate keypad or remotely (refer to the EnerVista UR Setup help file) via the EnerVista UR Setup
software interface.
It is recommended that passwords be set up for each security level and assigned to specific personnel. There are two user
password security access levels, COMMAND and SETTING:
1. COMMAND
The COMMAND access level restricts the user from making any settings changes, but allows the user to perform the fol-
lowing operations:
• change state of virtual inputs
• clear event records
• clear oscillography records
• operate user-programmable pushbuttons
2. SETTING
The SETTING access level allows the user to make any changes to any of the setting values.
Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level
passwords.
NOTE
FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex-
Logic™ section in Chapter 5 for additional details.
1.5.7 COMMISSIONING
The G60 requires a minimum amount of maintenance when it is commissioned into service. Since the G60 is a micropro-
1
cessor-based relay, its characteristics do not change over time. As such, no further functional tests are required.
Furthermore, the G60 performs a number of continual self-tests and takes the necessary action in case of any major errors
(see the Relay Self-tests section in chapter 7 for details). However, it is recommended that G60 maintenance be scheduled
with other system maintenance. This maintenance may involve the in-service, out-of-service, or unscheduled maintenance.
In-service maintenance:
1. Visual verification of the analog values integrity such as voltage and current (in comparison to other devices on the cor-
responding system).
2. Visual verification of active alarms, relay display messages, and LED indications.
3. LED test.
4. Visual inspection for any damage, corrosion, dust, or loose wires.
5. Event recorder file download with further events analysis.
Out-of-service maintenance:
1. Check wiring connections for firmness.
2. Analog values (currents, voltages, RTDs, analog inputs) injection test and metering accuracy verification. Calibrated
test equipment is required.
3. Protection elements setting verification (analog values injection or visual verification of setting file entries against relay
settings schedule).
4. Contact inputs and outputs verification. This test can be conducted by direct change of state forcing or as part of the
system functional testing.
5. Visual inspection for any damage, corrosion, or dust.
6. Event recorder file download with further events analysis.
7. LED Test and pushbutton continuity check.
Unscheduled maintenance such as during a disturbance causing system interruption:
1. View the event recorder and oscillography or fault report for correct operation of inputs, outputs, and elements.
If it is concluded that the relay or one of its modules is of concern, contact GE Multilin for prompt service.
The G60 Generator Protection System is a microprocessor based relay that provides protection, monitoring, control, and
recording functions for AC generators driven by steam, gas, or hydraulic turbine. Current, voltage and frequency protection
are provided along with fault diagnostics.
Voltage, current, and power metering is built into the relay as a standard feature. Current parameters are available as total
waveform RMS magnitude, or as fundamental frequency only RMS magnitude and angle (phasor).
Diagnostic features include an event recorder capable of storing 1024 time-tagged events, oscillography capable of storing
2
up to 64 records with programmable trigger, content and sampling rate, and data logger acquisition of up to 16 channels,
with programmable content and sampling rate. The internal clock used for time-tagging can be synchronized with an IRIG-
B signal or via the SNTP protocol over the Ethernet port. This precise time stamping allows the sequence of events to be
determined throughout the system. Events can also be programmed (via FlexLogic™ equations) to trigger oscillography
data capture which may be set to record the measured parameters before and after the event for viewing on a personal
computer (PC). These tools significantly reduce troubleshooting time and simplify report generation in the event of a sys-
tem fault.
A faceplate RS232 port may be used to connect to a PC for the programming of settings and the monitoring of actual val-
ues. A variety of communications modules are available. Two rear RS485 ports allow independent access by operating and
engineering staff. All serial ports use the Modbus® RTU protocol. The RS485 ports may be connected to system computers
with baud rates up to 115.2 kbps. The RS232 port has a fixed baud rate of 19.2 kbps. Optional communications modules
include a 10Base-F Ethernet interface which can be used to provide fast, reliable communications in noisy environments.
Another option provides two 10Base-F fiber optic ports for redundancy. The Ethernet port supports IEC 61850, Modbus®/
TCP, and TFTP protocols, and allows access to the relay via any standard web browser (G60 web pages). The IEC 60870-
5-104 protocol is supported on the Ethernet port. DNP 3.0 and IEC 60870-5-104 cannot be enabled at the same time.
The G60 IEDs use flash memory technology which allows field upgrading as new features are added. The following Single
line diagram illustrates the relay functionality using ANSI (American National Standards Institute) device numbers.
Close
52
Trip 25
49
G EX GPM-F 64F
Metering
87S
R 64TN
64S
2.1.2 ORDERING
a) OVERVIEW
The G60 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod-
ules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications.
Each of these modules can be supplied in a number of configurations specified at the time of ordering. The information
required to completely specify the relay is provided in the following tables (see chapter 3 for full details of relay modules).
Order codes are subject to change without notice. Refer to the GE Multilin ordering page at 2
http://www.GEindustrial.com/multilin/order.htm for the latest details concerning G60 ordering options.
NOTE
The order code structure is dependent on the mounting option (horizontal or vertical) and the type of CT/VT modules (regu-
lar CT/VT modules or the HardFiber modules). The order code options are described in the following sub-sections.
2 K
L
M
S
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RS485 and multi-mode ST redundant 100Base-FX
RS485 and single mode SC 100Base-FX
RS485 and single mode SC redundant 100Base-FX
RS485 and six-port managed Ethernet switch
SOFTWARE 00 | | | | | | | | | No Software Options
01 | | | | | | | | | Ethernet Global Data (EGD); not available for Type E CPUs
03 | | | | | | | | | IEC 61850; not available for Type E CPUs
04 | | | | | | | | | Ethernet Global Data (EGD) and IEC 61850; not available for Type E CPUs
06 | | | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | | | IEC 61850 and phasor measurement unit (PMU)
MOUNT/COATING H | | | | | | | | Horizontal (19” rack)
A | | | | | | | | Horizontal (19” rack) with harsh environmental coating
FACEPLATE/ DISPLAY C | | | | | | | English display
D | | | | | | | French display
R | | | | | | | Russian display
A | | | | | | | Chinese display
P | | | | | | | English display with 4 small and 12 large programmable pushbuttons
G | | | | | | | French display with 4 small and 12 large programmable pushbuttons
S | | | | | | | Russian display with 4 small and 12 large programmable pushbuttons
B | | | | | | | Chinese display with 4 small and 12 large programmable pushbuttons
K | | | | | | | Enhanced front panel with English display
M | | | | | | | Enhanced front panel with French display
Q | | | | | | | Enhanced front panel with Russian display
U | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
POWER SUPPLY H | | | | | | 125 / 250 V AC/DC power supply
(redundant supply must H | | | | | RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
be same type as main supply) L | | | | | | 24 to 48 V (DC only) power supply
L | | | | | RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
CT/VT MODULES 8F | 8F | | | Standard 4CT/4VT
8G | 8G | | | Sensitive Ground 4CT/4VT
8H | 8H | | | Standard 8CT
8J | 8J | | | Sensitive Ground 8CT
8L | 8L | | | Standard 4CT/4VT with enhanced diagnostics
8M | 8M | | | Sensitive Ground 4CT/4VT with enhanced diagnostics
8N | 8N | | | Standard 8CT with enhanced diagnostics
8R | 8R | | | Sensitive Ground 8CT with enhanced diagnostics
DIGITAL INPUTS/OUTPUTS XX XX XX XX XX No Module
4A 4A 4A 4A 4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4B 4B 4B 4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C 4C 4C 4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D 4D 4D 4D 16 digital inputs with Auto-Burnishing
4L 4L 4L 4L 4L 14 Form-A (no monitoring) Latching outputs
67 67 67 67 67 8 Form-A (no monitoring) outputs
6A 6A 6A 6A 6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 6B 6B 6B 6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 6C 6C 6C 6C 8 Form-C outputs
6D 6D 6D 6D 6D 16 digital inputs
6E 6E 6E 6E 6E 4 Form-C outputs, 8 digital inputs
6F 6F 6F 6F 6F 8 Fast Form-C outputs
6G 6G 6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6H 6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 6K 6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 6M 6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 6N 6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6P 6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 6R 6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 6S 6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 6T 6T 6T 6T 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6U 6U 6U 6U 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 6V 6V 6V 6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
TRANSDUCER 5A 5A 5A 5A 5A 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS 5C 5C 5C 5C 5C 8 RTD inputs
(select a maximum of 3 per unit) 5D 5D 5D 5D 5D 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
5E 5E 5E 5E 5E 4 RTD inputs, 4 dcmA inputs
5F 5F 5F 5F 5F 8 dcmA inputs
INTER-RELAY 2A 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E 2E Bi-phase, single channel
2F 2F Bi-phase, dual channel
2G 2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H 2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 2S Six-port managed Ethernet switch with high voltage power supply (110 to 250 V DC / 100 to 240 V AC)
| 2T Six-port managed Ethernet switch with low voltage power supply (48 V DC)
72 72 1550 nm, single-mode, LASER, 1 Channel
73 73 1550 nm, single-mode, LASER, 2 Channel
74 74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 7A 820 nm, multi-mode, LED, 1 Channel
7B 7B 1300 nm, multi-mode, LED, 1 Channel
7C 7C 1300 nm, single-mode, ELED, 1 Channel
7D 7D 1300 nm, single-mode, LASER, 1 Channel
7E 7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F 7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G 7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 7H 820 nm, multi-mode, LED, 2 Channels
7I 7I 1300 nm, multi-mode, LED, 2 Channels
7J 7J 1300 nm, single-mode, ELED, 2 Channels
7K 7K 1300 nm, single-mode, LASER, 2 Channels
7L 7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M 7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N 7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P 7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q 7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R 7R G.703, 1 Channel
7S 7S G.703, 2 Channels
7T 7T RS422, 1 Channel
7W 7W RS422, 2 Channels
The order codes for the reduced size vertical mount units with traditional CTs and VTs are shown below.
|
No Software Options
Ethernet Global Data (EGD); not available for Type E CPUs
IEC 61850; not available for Type E CPUs
Ethernet Global Data (EGD) and IEC 61850; not available for Type E CPUs
2
06 | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | IEC 61850 and phasor measurement unit (PMU)
MOUNT/COATING V | | | | | | Vertical (3/4 rack)
B | | | | | | Vertical (3/4 rack) with harsh environmental coating
FACEPLATE/ DISPLAY F | | | | | English display
D | | | | | French display
R | | | | | Russian display
A | | | | | Chinese display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
POWER SUPPLY H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
CT/VT MODULES 8F | 8F | Standard 4CT/4VT
8G | 8G | Sensitive Ground 4CT/4VT
8H | 8H | Standard 8CT
8J | 8J | Sensitive Ground 8CT
8L | 8L | Standard 4CT/4VT with enhanced diagnostics
8M | 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
8N | 8N | Standard 8CT with enhanced diagnostics
8R | 8R | Sensitive Ground 8CT with enhanced diagnostics
DIGITAL INPUTS/OUTPUTS XX XX XX No Module
4A 4A 4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4B 4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C 4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D 4D 16 digital inputs with Auto-Burnishing
4L 4L 4L 14 Form-A (no monitoring) Latching outputs
67 67 67 8 Form-A (no monitoring) outputs
6A 6A 6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 6B 6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 6C 6C 8 Form-C outputs
6D 6D 6D 16 digital inputs
6E 6E 6E 4 Form-C outputs, 8 digital inputs
6F 6F 6F 8 Fast Form-C outputs
6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 6T 6T 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6U 6U 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 6V 6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
TRANSDUCER 5A 5A 5A 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS 5C 5C 5C 8 RTD inputs
5D 5D 5D 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
5E 5E 5E 4 RTD inputs, 4 dcmA inputs
5F 5F 5F 8 dcmA inputs
INTER-RELAY 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit 2E Bi-phase, single channel
For the last module, slot P is used for digital and transducer 2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
input/output modules; slot R is used for inter-relay
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
communications modules. 72 1550 nm, single-mode, LASER, 1 Channel
73 1550 nm, single-mode, LASER, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, LASER, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, LASER, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
Table 2–5: G60 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS)
G60 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount
BASE UNIT G60 | | | | | | | | | | | Base Unit
CPU E | | | | | | | | | | RS485 and RS485
G | | | | | | | | | | RS485 and multi-mode ST 10Base-F
H | | | | | | | | | | RS485 and multi-mode ST redundant 10Base-F
J | | | | | | | | | | RS485 and multi-mode ST 100Base-FX
2 SOFTWARE
K
L
M
|
|
|
00
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RS485 and multi-mode ST redundant 100Base-FX
RS485 and single mode SC 100Base-FX
RS485 and single mode SC redundant 100Base-FX
No Software Options
01 | | | | | | | | | Ethernet Global Data (EGD); not available for Type E CPUs
03 | | | | | | | | | IEC 61850; not available for Type E CPUs
04 | | | | | | | | | Ethernet Global Data (EGD) and IEC 61850; not available for Type E CPUs
06 | | | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | | | IEC 61850 and phasor measurement unit (PMU)
MOUNT/COATING H | | | | | | | | Horizontal (19” rack)
A | | | | | | | | Horizontal (19” rack) with harsh environmental coating
FACEPLATE/ DISPLAY C | | | | | | | English display
D | | | | | | | French display
R | | | | | | | Russian display
A | | | | | | | Chinese display
P | | | | | | | English display with 4 small and 12 large programmable pushbuttons
G | | | | | | | French display with 4 small and 12 large programmable pushbuttons
S | | | | | | | Russian display with 4 small and 12 large programmable pushbuttons
B | | | | | | | Chinese display with 4 small and 12 large programmable pushbuttons
K | | | | | | | Enhanced front panel with English display
M | | | | | | | Enhanced front panel with French display
Q | | | | | | | Enhanced front panel with Russian display
U | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
POWER SUPPLY H | | | | | | 125 / 250 V AC/DC power supply
(redundant supply must H | | | | | RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
be same type as main supply) L | | | | | | 24 to 48 V (DC only) power supply
L | | | | | RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
PROCESS BUS MODULE | 81 | | | | Eight-port digital process bus module
DIGITAL INPUTS/OUTPUTS XX XX XX XX XX No Module
4A 4A | 4 Solid-State (no monitoring) MOSFET outputs
4B 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D | 16 digital inputs with Auto-Burnishing
4L 4L | 14 Form-A (no monitoring) Latching outputs
67 67 | 8 Form-A (no monitoring) outputs
6A 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 6C | 8 Form-C outputs
6D 6D | 16 digital inputs
6E 6E | 4 Form-C outputs, 8 digital inputs
6F 6F | 8 Fast Form-C outputs
6G 6G | 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6H | 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 6K | 4 Form-C and 4 Fast Form-C outputs
6L 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 6N | 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6P | 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 6T | 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6U | 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
INTER-RELAY 2A 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E 2E Bi-phase, single channel
2F 2F Bi-phase, dual channel
2G 2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H 2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
72 72 1550 nm, single-mode, LASER, 1 Channel
73 73 1550 nm, single-mode, LASER, 2 Channel
74 74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 7A 820 nm, multi-mode, LED, 1 Channel
7B 7B 1300 nm, multi-mode, LED, 1 Channel
7C 7C 1300 nm, single-mode, ELED, 1 Channel
7D 7D 1300 nm, single-mode, LASER, 1 Channel
7E 7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F 7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G 7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 7H 820 nm, multi-mode, LED, 2 Channels
7I 7I 1300 nm, multi-mode, LED, 2 Channels
7J 7J 1300 nm, single-mode, ELED, 2 Channels
7K 7K 1300 nm, single-mode, LASER, 2 Channels
7L 7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M 7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N 7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P 7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q 7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R 7R G.703, 1 Channel
7S 7S G.703, 2 Channels
7T 7T RS422, 1 Channel
7W 7W RS422, 2 Channels
The order codes for the reduced size vertical mount units with the process bus module are shown below.
Table 2–6: G60 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS)
G60 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
BASE UNIT G60 | | | | | | | | | Base Unit
CPU E | | | | | | | | RS485 and RS485
G | | | | | | | | RS485 and multi-mode ST 10Base-F
H | | | | | | | | RS485 and multi-mode ST redundant 10Base-F
J | | | | | | | | RS485 and multi-mode ST 100Base-FX
K | | | | | | | | RS485 and multi-mode ST redundant 100Base-FX
L | | | | | | | | RS485 and single mode SC 100Base-FX
M | | | | | | | | RS485 and single mode SC redundant 100Base-FX
SOFTWARE 00
01
03
04
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
No Software Options
Ethernet Global Data (EGD); not available for Type E CPUs
IEC 61850; not available for Type E CPUs
Ethernet Global Data (EGD) and IEC 61850; not available for Type E CPUs
2
06 | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | IEC 61850 and phasor measurement unit (PMU)
MOUNT/COATING V | | | | | | Vertical (3/4 rack)
B | | | | | | Vertical (3/4 rack) with harsh environmental coating
FACEPLATE/ DISPLAY F | | | | | English display
D | | | | | French display
R | | | | | Russian display
A | | | | | Chinese display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
POWER SUPPLY H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
PROCESS BUS MODULE | 81 | | Eight-port digital process bus module
DIGITAL INPUTS/OUTPUTS XX XX XX No Module
4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 16 digital inputs with Auto-Burnishing
4L 14 Form-A (no monitoring) Latching outputs
67 8 Form-A (no monitoring) outputs
6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 8 Form-C outputs
6D 16 digital inputs
6E 4 Form-C outputs, 8 digital inputs
6F 8 Fast Form-C outputs
6G 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 4 Form-C and 4 Fast Form-C outputs
6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
INTER-RELAY 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit 2E Bi-phase, single channel
For the last module, slot P is used for digital 2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
input/output modules; slot R is used for inter-relay
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
communications modules. 72 1550 nm, single-mode, LASER, 1 Channel
73 1550 nm, single-mode, LASER, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, LASER, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, LASER, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels
Replacement modules can be ordered separately as shown below. When ordering a replacement CPU module or face-
plate, please provide the serial number of your existing unit.
Not all replacement modules may be applicable to the G60 relay. Only the modules specified in the order codes are
available as replacement modules.
NOTE
Replacement module codes are subject to change without notice. Refer to the GE Multilin ordering page at http://
www.GEindustrial.com/multilin/order.htm for the latest details concerning G60 ordering options.
NOTE
The replacement module order codes for the horizontal mount units are shown below.
2 |
|
|
|
9K
9L
9M
9N
|
|
|
|
RS485 and multi-mode ST redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
RS485 and single mode SC 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
RS485 and single mode SC redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
RS485 and 10/100Base-T
| 9S | RS485 and six-port managed Ethernet switch
FACEPLATE/DISPLAY | 3C | Horizontal faceplate with keypad and English display
| 3D | Horizontal faceplate with keypad and French display
| 3R | Horizontal faceplate with keypad and Russian display
| 3A | Horizontal faceplate with keypad and Chinese display
| 3P | Horizontal faceplate with keypad, user-programmable pushbuttons, and English display
| 3G | Horizontal faceplate with keypad, user-programmable pushbuttons, and French display
| 3S | Horizontal faceplate with keypad, user-programmable pushbuttons, and Russian display
| 3B | Horizontal faceplate with keypad, user-programmable pushbuttons, and Chinese display
| 3K | Enhanced front panel with English display
| 3M | Enhanced front panel with French display
| 3Q | Enhanced front panel with Russian display
| 3U | Enhanced front panel with Chinese display
| 3L | Enhanced front panel with English display and user-programmable pushbuttons
| 3N | Enhanced front panel with French display and user-programmable pushbuttons
| 3T | Enhanced front panel with Russian display and user-programmable pushbuttons
| 3V | Enhanced front panel with Chinese display and user-programmable pushbuttons
DIGITAL INPUTS AND OUTPUTS | 4A | 4 Solid-State (no monitoring) MOSFET outputs
| 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
| 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
| 4D | 16 digital inputs with Auto-Burnishing
| 4L | 14 Form-A (no monitoring) Latching outputs
| 67 | 8 Form-A (no monitoring) outputs
| 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
| 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
| 6C | 8 Form-C outputs
| 6D | 16 digital inputs
| 6E | 4 Form-C outputs, 8 digital inputs
| 6F | 8 Fast Form-C outputs
| 6G | 4 Form-A (voltage with optional current) outputs, 8 digital inputs
| 6H | 6 Form-A (voltage with optional current) outputs, 4 digital inputs
| 6K | 4 Form-C and 4 Fast Form-C outputs
| 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
| 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
| 6N | 4 Form-A (current with optional voltage) outputs, 8 digital inputs
| 6P | 6 Form-A (current with optional voltage) outputs, 4 digital inputs
| 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
| 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
| 6T | 4 Form-A (no monitoring) outputs, 8 digital inputs
| 6U | 6 Form-A (no monitoring) outputs, 4 digital inputs
| 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
CT/VT | 8F | Standard 4CT/4VT
MODULES | 8G | Sensitive Ground 4CT/4VT
(NOT AVAILABLE FOR THE C30) | 8H | Standard 8CT
| 8J | Sensitive Ground 8CT
| 8L | Standard 4CT/4VT with enhanced diagnostics
| 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
| 8N | Standard 8CT with enhanced diagnostics
| 8R | Sensitive Ground 8CT with enhanced diagnostics
INTER-RELAY COMMUNICATIONS | 2A | C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
| 2B | C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
| 2E | Bi-phase, single channel
| 2F | Bi-phase, dual channel
| 2G | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
| 2H | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 2S | Six-port managed Ethernet switch with high voltage power supply (110 to 250 V DC / 100 to 240 V AC)
| 2T | Six-port managed Ethernet switch with low voltage power supply (48 V DC)
| 72 | 1550 nm, single-mode, LASER, 1 Channel
| 73 | 1550 nm, single-mode, LASER, 2 Channel
| 74 | Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
| 75 | Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
| 76 | IEEE C37.94, 820 nm, multimode, LED, 1 Channel
| 77 | IEEE C37.94, 820 nm, multimode, LED, 2 Channels
| 7A | 820 nm, multi-mode, LED, 1 Channel
| 7B | 1300 nm, multi-mode, LED, 1 Channel
| 7C | 1300 nm, single-mode, ELED, 1 Channel
| 7D | 1300 nm, single-mode, LASER, 1 Channel
| 7E | Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
| 7F | Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
| 7G | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
| 7H | 820 nm, multi-mode, LED, 2 Channels
| 7I | 1300 nm, multi-mode, LED, 2 Channels
| 7J | 1300 nm, single-mode, ELED, 2 Channels
| 7K | 1300 nm, single-mode, LASER, 2 Channels
| 7L | Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
| 7M | Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
| 7N | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
| 7P | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
| 7Q | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
| 7R | G.703, 1 Channel
| 7S | G.703, 2 Channels
| 7T | RS422, 1 Channel
| 7W | RS422, 2 Channels
TRANSDUCER | 5A | 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS | 5C | 8 RTD inputs
| 5D | 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
| 5E | 4 dcmA inputs, 4 RTD inputs
| 5F | 8 dcmA inputs
The replacement module order codes for the reduced-size vertical mount units are shown below.
FACEPLATE/DISPLAY
|
|
|
|
9M
9N
3F
3D
|
|
|
|
RS485 and single mode SC redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
RS485 and 10/100Base-T
Vertical faceplate with keypad and English display
Vertical faceplate with keypad and French display
2
| 3R | Vertical faceplate with keypad and Russian display
| 3K | Vertical faceplate with keypad and Chinese display
| 3K | Enhanced front panel with English display
| 3M | Enhanced front panel with French display
| 3Q | Enhanced front panel with Russian display
| 3U | Enhanced front panel with Chinese display
| 3L | Enhanced front panel with English display and user-programmable pushbuttons
| 3N | Enhanced front panel with French display and user-programmable pushbuttons
| 3T | Enhanced front panel with Russian display and user-programmable pushbuttons
| 3V | Enhanced front panel with Chinese display and user-programmable pushbuttons
DIGITAL | 4A | 4 Solid-State (no monitoring) MOSFET outputs
INPUTS/OUTPUTS | 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
| 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
| 4D | 16 digital inputs with Auto-Burnishing
| 4L | 14 Form-A (no monitoring) Latching outputs
| 67 | 8 Form-A (no monitoring) outputs
| 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
| 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
| 6C | 8 Form-C outputs
| 6D | 16 digital inputs
| 6E | 4 Form-C outputs, 8 digital inputs
| 6F | 8 Fast Form-C outputs
| 6G | 4 Form-A (voltage with optional current) outputs, 8 digital inputs
| 6H | 6 Form-A (voltage with optional current) outputs, 4 digital inputs
| 6K | 4 Form-C and 4 Fast Form-C outputs
| 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
| 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
| 6N | 4 Form-A (current with optional voltage) outputs, 8 digital inputs
| 6P | 6 Form-A (current with optional voltage) outputs, 4 digital inputs
| 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
| 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
| 6T | 4 Form-A (no monitoring) outputs, 8 digital inputs
| 6U | 6 Form-A (no monitoring) outputs, 4 digital inputs
| 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
CT/VT | 8F | Standard 4CT/4VT
MODULES | 8G | Sensitive Ground 4CT/4VT
(NOT AVAILABLE FOR THE C30) | 8H | Standard 8CT
| 8J | Sensitive Ground 8CT
| 8L | Standard 4CT/4VT with enhanced diagnostics
| 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
| 8N | Standard 8CT with enhanced diagnostics
| 8R | Sensitive Ground 8CT with enhanced diagnostics
INTER-RELAY COMMUNICATIONS | 2A | C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
| 2B | C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
| 2E | Bi-phase, single channel
| 2F | Bi-phase, dual channel
| 2G | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
| 2H | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 72 | 1550 nm, single-mode, LASER, 1 Channel
| 73 | 1550 nm, single-mode, LASER, 2 Channel
| 74 | Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
| 75 | Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
| 76 | IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
| 77 | IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
| 7A | 820 nm, multi-mode, LED, 1 Channel
| 7B | 1300 nm, multi-mode, LED, 1 Channel
| 7C | 1300 nm, single-mode, ELED, 1 Channel
| 7D | 1300 nm, single-mode, LASER, 1 Channel
| 7E | Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
| 7F | Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
| 7G | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
| 7H | 820 nm, multi-mode, LED, 2 Channels
| 7I | 1300 nm, multi-mode, LED, 2 Channels
| 7J | 1300 nm, single-mode, ELED, 2 Channels
| 7K | 1300 nm, single-mode, LASER, 2 Channels
| 7L | Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
| 7M | Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
| 7N | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
| 7P | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
| 7Q | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
| 7R | G.703, 1 Channel
| 7S | G.703, 2 Channels
| 7T | RS422, 1 Channel
| 7W | RS422, 2 Channels
TRANSDUCER | 5A | 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS | 5C | 8 RTD inputs
| 5D | 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
| 5E | 4 dcmA inputs, 4 RTD inputs
| 5F | 8 dcmA inputs
The operating times below include the activation time of a trip rated form-A output contact unless otherwise indi-
cated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
NOTE FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
2 interfacing with other IEDs or power system devices via communications or different output contacts.
PHASE DISTANCE RESTRICTED GROUND FAULT
Characteristic: mho (memory polarized or offset) or Pickup: 0.005 to 30.000 pu in steps of 0.001
quad (memory polarized or non-direc- Dropout: 97 to 98% of pickup
tional), selectable individually per zone
Slope: 0 to 100% in steps of 1%
Number of zones: 3
Pickup delay: 0 to 600.00 s in steps of 0.01
Directionality: forward, reverse, or non-directional per
Dropout delay: 0 to 600.00 s in steps of 0.01
zone
Operate time: <1 power system cycle
Reach (secondary Ω): 0.02 to 500.00 Ω in steps of 0.01
Reach accuracy: ±5% including the effect of CVT tran- PHASE/NEUTRAL/GROUND TOC
sients up to an SIR of 30 Current: Phasor or RMS
Distance: Pickup level: 0.000 to 30.000 pu in steps of 0.001
Characteristic angle: 30 to 90° in steps of 1 Dropout level: 97% to 98% of pickup
Comparator limit angle: 30 to 90° in steps of 1 Level accuracy:
Directional supervision: for 0.1 to 2.0 × CT: ±0.5% of reading or ±0.4% of rated
(whichever is greater)
Characteristic angle: 30 to 90° in steps of 1
for > 2.0 × CT: ±1.5% of reading > 2.0 × CT rating
Limit angle: 30 to 90° in steps of 1
Curve shapes: IEEE Moderately/Very/Extremely
Right blinder (Quad only):
Inverse; IEC (and BS) A/B/C and Short
Reach: 0.02 to 500 Ω in steps of 0.01 Inverse; GE IAC Inverse, Short/Very/
Characteristic angle: 60 to 90° in steps of 1 Extremely Inverse; I2t; FlexCurves™
Left Blinder (Quad only): (programmable); Definite Time (0.01 s
Reach: 0.02 to 500 Ω in steps of 0.01 base curve)
Characteristic angle: 60 to 90° in steps of 1 Curve multiplier: Time Dial = 0.00 to 600.00 in steps of
0.01
Time delay: 0.000 to 65.535 s in steps of 0.001
Reset type: Instantaneous/Timed (per IEEE)
Timing accuracy: ±3% or 4 ms, whichever is greater
Timing accuracy: Operate at > 1.03 × actual pickup
Current supervision:
±3.5% of operate time or ±½ cycle
Level: line-to-line current (whichever is greater)
Pickup: 0.050 to 30.000 pu in steps of 0.001
Dropout: 97 to 98%
PHASE/NEUTRAL/GROUND IOC
Pickup level: 0.000 to 30.000 pu in steps of 0.001
Memory duration: 5 to 25 cycles in steps of 1
Dropout level: 97 to 98% of pickup
VT location: all delta-wye and wye-delta transformers
Level accuracy:
CT location: all delta-wye and wye-delta transformers
0.1 to 2.0 × CT rating: ±0.5% of reading or ±0.4% of rated
Voltage supervision pickup (series compensation applications): (whichever is greater)
0 to 5.000 pu in steps of 0.001
> 2.0 × CT rating ±1.5% of reading
Operation time: 1 to 1.5 cycles (typical)
Overreach: <2%
Reset time: 1 power cycle (typical)
Pickup delay: 0.00 to 600.00 s in steps of 0.01
STATOR DIFFERENTIAL Reset delay: 0.00 to 600.00 s in steps of 0.01
Pickup: 0.050 to 1.00 pu in steps of 0.01 Operate time: <16 ms at 3 × pickup at 60 Hz
Slope 1 and 2: 1 to 100% in steps of 1 (Phase/Ground IOC)
Break 1: 1.00 to 1.50 pu in steps of 0.01 <20 ms at 3 × pickup at 60 Hz
Break 2: 1.50 to 30.00 pu in steps of 0.01 (Neutral IOC)
Operate time: <¾ cycle at Idiff > 5 × pickup Timing accuracy: Operate at 1.5 × pickup
±3% or ±4 ms (whichever is greater)
2 Pickup level:
Dropout level:
0.000 to 1.200 pu in steps of 0.001
97 to 98% of pickup
TD Multiplier:
Reset delay:
0.05 to 600.00 s in steps of 0.01
0.0 to 1000.0 s in steps of 0.1
Accuracy: ±5% or ±0.01 pu, whichever is greater Timing accuracy: ±3% or ±15 cycles (whichever is greater)
for values greater than 1.1 × pickup
Undervoltage Inhibit
Level: 0.000 to 3.000 pu in steps of 0.001 pu 100% STATOR GROUND
V_neutral_3rd
Accuracy: ±0.5% of reading from 10 to 208 V Operating quantity: ----------------------------------------------------------------------------
V_neutral_3rd + V_zero_3rd
Pickup delay: 0 to 600.00 s in steps of 0.01 Pickup level: 0.000 to 0.900 pu in steps of 0.001
Time accuracy: ±3% or ±20 ms, whichever is greater Dropout level: 97 to 98% of pickup
Operate time: < 30 ms at 1.10 × pickup at 60 Hz Level accuracy: ±2% of reading from 1 to 120 V
Pickup delay: 0 to 600.00 s in steps of 0.01
PHASE OVERVOLTAGE
Voltage: Phasor only 3rd harmonic supervision level: 0.0010 to 0.1000 pu in steps of
0.0001
Pickup level: 0.000 to 3.000 pu in steps of 0.001
Time accuracy: ±3% or ±20 ms, whichever is greater
Dropout level: 97 to 98% of pickup
Operate time: < 30 ms at 1.10 × pickup at 60 Hz
Level accuracy: ±0.5% of reading from 10 to 208 V
Pickup delay: 0.00 to 600.00 in steps of 0.01 s SUB-HARMONIC STATOR GROUND
Stator ground resistance pickup accuracy: ±5% of reading from 1
Operate time: < 30 ms at 1.10 × pickup at 60 Hz
to 10 kΩ, ±10% of reading from 10 to 20
Timing accuracy: ±3% or ±4 ms (whichever is greater) kΩ
NEUTRAL OVERVOLTAGE Total stator capacitance to ground: 200 nF to 2 μF
Pickup level: 0.000 to 3.000 pu in steps of 0.001 Sub-harmonic voltage metering accuracy: ±2% of reading or 0.2 V
Dropout level: 97 to 98% of pickup from 0.5 to 25 V AC
Level accuracy: ±0.5% of reading from 10 to 208 V Sub-harmonic current metering accuracy: ±2% of reading or 5 mA
Pickup delay: 0.00 to 600.00 s in steps of 0.01 (definite from 5 to 200 mA
time) or user-defined curve Sub-harmonic element operating time: 0.6 to 1.2 s
Reset delay: 0.00 to 600.00 s in steps of 0.01 Sub-harmonic element dropout level accuracy: 102 to 103% of
Timing accuracy: ±3% or ±20 ms (whichever is greater) pickup
Operate time: < 30 ms at 1.10 × pickup at 60 Hz Time delay accuracy: ±3% of time delay setting or ± 4 ms,
whichever is greater
AUXILIARY OVERVOLTAGE
Pickup level: 0.000 to 3.000 pu in steps of 0.001 FIELD GROUND
Measured field ground resistance: 1 kΩ to 20 MΩ
Dropout level: 97 to 98% of pickup
Ground resistance accuracy:±5% of reading ±250 Ω from 1 to 500
Level accuracy: ±0.5% of reading from 10 to 208 V
kΩ
Pickup delay: 0 to 600.00 s in steps of 0.01
Field winding capacitance: 1 to 10 μF
Reset delay: 0 to 600.00 s in steps of 0.01
Maximum field voltage: 600 V DC rated field voltage / 1000 V
Timing accuracy: ±3% of operate time or ±4 ms
ripple peak for single box option; 800
(whichever is greater) V DC rated field voltage / 2000 V ripple
Operate time: < 30 ms at 1.10 × pickup at 60 Hz peak for external resistor box option
Operate time when 20 Hz injection is performed: 8 power system Field voltage measurement range: 15 to 800 V
cycles
Field voltage measurement accuracy: ±1 V or ±3% of reading (for
NEGATIVE SEQUENCE OVERVOLTAGE GPM-F-L); ±1 V or ±5% of reading (for
Pickup level: 0.000 to 1.250 pu in steps of 0.001 GPM-F-H)
Dropout level: 97 to 98% of pickup Field ground RMS current accuracy: ±5% of reading
Level accuracy: ±0.5% of reading from 10 to 208 V Fault location accuracy: ±5% of reading
Pickup delay: 0 to 600.00 s in steps of 0.01 Field ground resistance typical operating time: 1.1 s + (1 / injection
frequency)
Reset delay: 0 to 600.00 s in steps of 0.01
Field ground element dropout level accuracy: 102 to 103% of
Time accuracy: ±3% or ±20 ms, whichever is greater
pickup
Operate time: < 30 ms at 1.10 × pickup at 60 Hz
Time delay accuracy: ±3% of time delay setting or ±4ms,
whichever is greater
FLEXLOGIC™ FLEXELEMENTS™
Programming language: Reverse Polish Notation with graphical Number of elements: 16
visualization (keypad programmable) Operating signal: any analog actual value, or two values in
Lines of code: 512 differential mode
Internal variables: 64 Operating signal mode: signed or absolute value
Supported operations: NOT, XOR, OR (2 to 16 inputs), AND (2 Operating mode: level, delta
to 16 inputs), NOR (2 to 16 inputs), Comparator direction: over, under
NAND (2 to 16 inputs), latch (reset-domi- Pickup Level: –90.000 to 90.000 pu in steps of 0.001
nant), edge detectors, timers
Hysteresis: 0.1 to 50.0% in steps of 0.1
Inputs: any logical variable, contact, or virtual
Delta dt: 20 ms to 60 days
input
Pickup & dropout delay: 0.000 to 65.535 s in steps of 0.001
Number of timers: 32
Pickup delay: 0 to 60000 (ms, sec., min.) in steps of 1 NON-VOLATILE LATCHES
Dropout delay: 0 to 60000 (ms, sec., min.) in steps of 1 Type: set-dominant or reset-dominant
Number: 16 (individually programmed)
FLEXCURVES™
Number: 4 (A through D) Output: stored in non-volatile memory
Reset points: 40 (0 through 1 of pickup) Execution sequence: as input prior to protection, control, and
FlexLogic™
Operate points: 80 (1 through 20 of pickup)
Time delay: 0 to 65535 ms in steps of 1 USER-PROGRAMMABLE LEDs
Number: 48 plus trip and alarm
FLEX STATES Programmability: from any logical variable, contact, or vir-
Number: up to 256 logical variables grouped tual input
under 16 Modbus addresses
Reset mode: self-reset or latched
Programmability: any logical variable, contact, or virtual
input
2.2.3 MONITORING
2.2.4 METERING
2.2.5 INPUTS
TELEPROTECTION
Number of input points: 16
No. of remote devices: 3
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration: No
Data rate: 64 or 128 kbps
CRC: 32-bit
2 2.2.6 POWER SUPPLY
2.2.7 OUTPUTS
ETHERNET SWITCH (HIGH VOLTAGE, TYPE 2S) ETHERNET SWITCH (LOW VOLTAGE, TYPE 2T)
Nominal DC voltage: 110 to 240 V DC Nominal voltage: 48 V DC, 0.31 A/15 W
Minimum DC voltage: 88 V DC Minimum voltage: 30 V DC, 0.43 A/16 W
Maximum DC voltage: 300 V DC Maximum voltage: 60 V DC
Input Current: 0.9 A DC maximum Internal fuse: 5 A / 350 V AC, Ceramic, Axial SLO
Nominal AC voltage: 100 to 240 V AC, 0.26 to 0.16 A/26 to 39 BLO;
VA at 50/60 Hz Manufacturer: Conquer; Part number:
SCD-A 005
2 Minimum AC voltage:
Maximum AC voltage:
85 V AC, 0.31 A/22 VA at 50/60 Hz
265 V AC, 0.16 A/42 VA at 50/60 Hz
Internal fuse: 3 A / 350 V AC, Ceramic, Axial SLO
BLO;
Manufacturer: Conquer; Part number:
SCD-A 003
2.2.9 COMMUNICATIONS
2.2.11 ENVIRONMENTAL
2 Damped oscillatory
Electrostatic discharge
IEC61000-4-18 / IEC60255-22-1
EN61000-4-2 / IEC60255-22-2
2.5 kV CM, 1 kV DM
Level 3
RF immunity EN61000-4-3 / IEC60255-22-3 Level 3
Fast transient disturbance EN61000-4-4 / IEC60255-22-4 Class A and B
Surge immunity EN61000-4-5 / IEC60255-22-5 Level 3 and 4
Conducted RF immunity EN61000-4-6 / IEC60255-22-6 Level 3
Power frequency immunity EN61000-4-7 / IEC60255-22-7 Class A and B
Voltage interruption and ripple DC IEC60255-11 12% ripple, 200 ms interrupts
Radiated and conducted emissions CISPR11 / CISPR22 / IEC60255-25 Class A
Sinusoidal vibration IEC60255-21-1 Class 1
Shock and bump IEC60255-21-2 Class 1
Seismic IEC60255-21-3 Class 1
Power magnetic immunity IEC61000-4-8 Level 5
Pulse magnetic immunity IEC61000-4-9 Level 4
Damped magnetic immunity IEC61000-4-10 Level 4
Voltage dip and interruption IEC61000-4-11 0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory IEC61000-4-12 2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz IEC61000-4-16 Level 4
Voltage ripple IEC61000-4-17 15% ripple
Ingress protection IEC60529 IP40 front, IP10 back
Cold IEC60068-2-1 –40°C for 16 hours
Hot IEC60068-2-2 85°C for 16 hours
Humidity IEC60068-2-30 6 days, variant 1
Damped oscillatory IEEE/ANSI C37.90.1 2.5 kV, 1 MHz
RF immunity IEEE/ANSI C37.90.2 20 V/m, 80 MHz to 1 GHz
Safety UL508 e83849 NKCR
Safety UL C22.2-14 e83849 NKCR7
Safety UL1053 e83849 NKCR
THERMAL
Products go through an environmental test based upon an
Accepted Quality Level (AQL) sampling process.
2.2.14 APPROVALS
APPROVALS
COMPLIANCE APPLICABLE ACCORDING TO
COUNCIL DIRECTIVE
CE compliance Low voltage directive EN60255-5
EMC directive EN60255-26 / EN50263
EN61000-6-5 2
North America --- UL508
--- UL1053
--- C22.2 No. 14
2.2.15 MAINTENANCE
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds) of torque.
CLEANING
Normally, cleaning is not required; but for situations where dust has accumulated on the faceplate display, a dry cloth can be used.
Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to avoid deterioration
of electrolytic capacitors.
NOTE
a) HORIZONTAL UNITS
The G60 Generator Protection System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The
faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains addi-
tional user-programmable pushbuttons and LED indicators.
The modular design allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is
hinged to allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear
depth. There is also a removable dust cover that fits over the faceplate, which must be removed when attempting to access
the keypad or RS232 communications port.
The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of
your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent
equipment.
3
The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator
access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws
supplied with the relay.
11.016”
[279,81 mm]
9.687”
[246,05 mm]
17.56”
[446,02 mm]
7.460”
[189,48 mm]
6.995” 6.960”
[177,67 mm] [176,78 mm]
19.040”
[483,62 mm]
842807A1.CDR
18.370”
[466,60 mm]
0.280”
[7,11 mm]
Typ. x 4
CUT-OUT
4.000”
[101,60 mm]
17.750”
[450,85 mm] 842808A1.CDR
b) VERTICAL UNITS
The G60 Generator Protection System is available as a reduced size (¾) vertical mount unit, with a removable faceplate.
The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains
additional user-programmable pushbuttons and LED indicators.
The modular design allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is
hinged to allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear
depth. There is also a removable dust cover that fits over the faceplate, which must be removed when attempting to access
the keypad or RS232 communications port.
The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of
your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent
equipment.
The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator
access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws
supplied with the relay.
7.482” 11.015”
1.329”
13.560”
3
15.000” 14.025”
4.000”
9.780”
843809A1.CDR
e UR SERIES
Figure 3–7: G60 VERTICAL SIDE MOUNTING REAR DIMENSIONS (STANDARD PANEL)
Module withdrawal and insertion may only be performed when control power has been removed from the
unit. Inserting an incorrect module type into a slot may result in personal injury, damage to the unit or con-
WARNING
nected equipment, or undesired operation!
Proper electrostatic discharge protection (for example, a static strap) must be used when coming in con-
tact with modules while the relay is energized!
WARNING
The relay, being modular in design, allows for the withdrawal and insertion of modules. Modules must only be replaced with
like modules in their original factory configured slots.
The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows
for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens
completely and allows easy access to all modules in the G60.
842812A1.CDR
The 4.0x release of the G60 relay includes new hardware modules.The new CPU modules are specified with codes
9E and higher. The new CT/VT modules are specified with the codes 8F and higher.
NOTE
The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old
CPUs. To prevent hardware mismatches, the new modules have blue labels and a warning sticker stating “Attn.:
Ensure CPU and DSP module label colors are the same!”. In the event that there is a mismatch between the
CPU and CT/VT module, the relay will not function and a DSP ERROR or HARDWARE MISMATCH error will be dis-
played.
All other input and output modules are compatible with the new hardware. Firmware versions 4.0x and higher are
only compatible with the new hardware modules. Previous versions of the firmware (3.4x and earlier) are only com-
patible with the older hardware modules.
3
G60 Generator Management Relay RATINGS: Model: G60D00HCHF8AH6AM6BP8BX7A
Mods: 000
Control Power: 88-300V DC @ 35W / 77-265V AC @ 35VA Wiring Diagram: ZZZZZZ
Contact Inputs: 300V DC Max 10mA Inst. Manual: D
Contact Outputs: Standard Pilot Duty / 250V AC 7.5A Serial Number: MAZB98000029
360V A Resistive / 125V DC Break Firmware: D
GE Multilin 4A @ L/R = 40mS / 300W Mfg. Date: 1998/01/05
Technical Support:
Made in
Tel: (905) 294-6222 http://www.GEIndustrial.com/Multilin ®
®
Canada
Fax: (905) 201-2098 - M A A B 9 7 0 0 0 0 9 9 -
X W V U T S R P N M L K J H G F D B
c b a c b a c b a c b a
b a b a
Tx1 1 1
1 1
2 2
Rx1 2 2
3 Tx1 3
3 3
Tx1
4 4
CH1
4 4
Rx1 5
Tx2 CH1 5
Tx 6
Rx 6
CH2
Rx2 IN 7
Tx2
7
8
CH2
Tx2 8
OUT
Rx2
WARNING
The relay follows a convention with respect to terminal number assignments which are three characters long assigned in
order by module slot position, row number, and column letter. Two-slot wide modules take their slot designation from the
first slot position (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following
figure for an example of rear terminal assignments.
TYPICAL CONFIGURATION
THE AC SIGNAL PATH IS CONFIGURABLE
POSITIVE WATTS
OPEN DELTA
VT CONNECTION (ABC)
A
B
C
3
F 5a
F 6a
F 7a
F 5c
F 6c
F 7c
M1a
M1b
M2a
M2b
M3a
M3b
M4a
M4b
M1c
M2c
M3c
M4c
F5a
F6a
F7a
F8a
F1a
F1b
F2a
F2b
F3a
F3b
F4a
F4b
F5c
F6c
F7c
F8c
F1c
F2c
F3c
F4c
VX
VB
VC
VB
VC
VA
VA
VX
IG5
IG1
VB
VC
VB
VC
IG
IG5
IG1
VA
VA
IG
IA5
IA1
IB
IC
IA
IC5
IC1
IA5
IA1
IB5
IB1
IB
IC
IA
IC5
IC1
IB5
IB1
CURRENT SUPERVISION
VOLTAGE AND
CURRENT INPUTS VOLTAGE INPUTS VOLTAGE INPUTS CURRENT INPUTS
8F/8G or 8H/8J 8F / 8G
VOLTAGE SUPERVISION
V
H2c
H7a CONTACT INPUT H7a
I H3a
H7c CONTACT INPUT H7c
TC 2
H3
V
H3b
H8a CONTACT INPUT H8a
H3c
H8c CONTACT INPUT H8c I H4a
H7b COMMON H7b
H4
V
H4b
H8b SURGE H4c
( DC ONLY )
CRITICAL
B1a FAILURE
B2b
B3a 48 V DC G60 GENERATOR MANAGEMENT RELAY
B3b OUTPUT
DC
POWER SUPPLY
B5b HI
CONTROL
B6b LO
AC or DC POWER
B6a
RS-232
B8a SURGE (front)
B8b FILTER
DB-9
CPU 9E
Output
COM 2
COM 1
RS485
RS485
IRIG-B
IRIG-B
Input
CONTACTS SHOWN
WITH NO
CONTROL POWER
com
com
BNC
BNC
D1b
D2b
D3b
D1a
D2a
D3a
D4b
D4a
MODULE ARRANGEMENT
No. 10AWG
minimum
X W V U T S R P N M L K J H G F D B
GROUND 8 6 8 9 1
BUS
CT Inputs/ VT/CT CPU Power
outputs Supply
(Rear View)
CONNECTOR
twisted pairs
Co-axial *
Shielded
Co-axial
Co-axial
25 PIN
7 SGND
3 RXD
2 TXD
terminal as input
Co-axial * - For IRIG-B Input
COMPUTER
only use one
20
22
8
5
4
1
2
3
4
7
8
9
5
6
9 PIN
CONNECTOR
MODULES MUST BE
UR
1
2
3
4
7
8
9
5
6
GROUNDED IF
TERMINAL IS
Ground at
SGND
Remote
RXD
Device
TXD
PROVIDED
The dielectric strength of the UR-series module hardware is shown in the following table:
Table 3–1: DIELECTRIC STRENGTH OF UR-SERIES MODULE HARDWARE
MODULE MODULE FUNCTION TERMINALS DIELECTRIC STRENGTH
TYPE (AC)
FROM TO
1 Power supply High (+); Low (+); (–) Chassis 2000 V AC for 1 minute
1 Power supply 48 V DC (+) and (–) Chassis 2000 V AC for 1 minute
1 Power supply Relay terminals Chassis 2000 V AC for 1 minute
2 Reserved N/A N/A N/A
3 Reserved N/A N/A N/A
3 4
5
Reserved
Analog inputs/outputs
N/A
All except 8b
N/A
Chassis
N/A
< 50 V DC
6 Digital inputs/outputs All Chassis 2000 V AC for 1 minute
G.703 All except 2b, 3a, 7b, 8a Chassis 2000 V AC for 1 minute
7
RS422 All except 6a, 7b, 8a Chassis < 50 V DC
8 CT/VT All Chassis 2000 V AC for 1 minute
9 CPU All Chassis 2000 V AC for 1 minute
Filter networks and transient protection clamps are used in the hardware to prevent damage caused by high peak voltage
transients, radio frequency interference (RFI), and electromagnetic interference (EMI). These protective components can
be damaged by application of the ANSI/IEEE C37.90 specified test voltage for a period longer than the specified one min-
ute.
CONTROL POWER SUPPLIED TO THE RELAY MUST BE CONNECTED TO THE MATCHING POWER SUPPLY
RANGE OF THE RELAY. IF THE VOLTAGE IS APPLIED TO THE WRONG TERMINALS, DAMAGE MAY
CAUTION
OCCUR!
The G60 relay, like almost all electronic relays, contains electrolytic capacitors. These capacitors are well
known to be subject to deterioration over time if voltage is not applied periodically. Deterioration can be
NOTE
avoided by powering the relays up once a year.
The power supply module can be ordered for two possible voltage ranges, with or without a redundant power option. Each
range has a dedicated input connection for proper operation. The ranges are as shown below (see the Technical specifica-
tions section of chapter 2 for additional details):
• Low (LO) range: 24 to 48 V (DC only) nominal.
• High (HI) range: 125 to 250 V nominal.
The power supply module provides power to the relay and supplies power for dry contact input connections.
The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay (see the
Typical wiring diagram earlier). The critical failure relay is a form-C device that will be energized once control power is
applied and the relay has successfully booted up with no critical self-test failures. If on-going self-test diagnostic checks
detect a critical failure (see the Self-test errors section in chapter 7) or control power is lost, the relay will de-energize.
For high reliability systems, the G60 has a redundant option in which two G60 power supplies are placed in parallel on the
bus. If one of the power supplies become faulted, the second power supply will assume the full load of the relay without any
interruptions. Each power supply has a green LED on the front of the module to indicate it is functional. The critical fail relay
of the module will also indicate a faulted power supply.
An LED on the front of the control power module shows the status of the power supply:
LED INDICATION POWER SUPPLY
CONTINUOUS ON OK
ON / OFF CYCLING Failure
OFF Failure
NOTE:
AC or DC 14 gauge stranded AC or DC
wire with suitable
disconnect devices
is recommended.
Heavy copper conductor
or braided wire
3
GND
+ +
+ —
– LOW HIGH
FILTER SURGE
CONTROL OPTIONAL
POWER ETHERNET SWITCH
Switchgear UR-series
ground bus protection system
827759AA.CDR
A CT/VT module may have voltage inputs on channels 1 through 4 inclusive, or channels 5 through 8 inclusive. Channels 1
and 5 are intended for connection to phase A, and are labeled as such in the relay. Likewise, channels 2 and 6 are intended
for connection to phase B, and channels 3 and 7 are intended for connection to phase C.
Channels 4 and 8 are intended for connection to a single-phase source. For voltage inputs, these channel are labelled as
auxiliary voltage (VX). For current inputs, these channels are intended for connection to a CT between system neutral and
ground, and are labelled as ground current (IG).
Verify that the connection made to the relay nominal current of 1 A or 5 A matches the secondary rating of
the connected CTs. Unmatched CTs may result in equipment damage or inadequate protection.
CAUTION
CT/VT modules may be ordered with a standard ground current input that is the same as the phase current input. Each AC
current input has an isolating transformer and an automatic shorting mechanism that shorts the input when the module is
withdrawn from the chassis. There are no internal ground connections on the current inputs. Current transformers with 1 to
50000 A primaries and 1 A or 5 A secondaries may be used.
CT/VT modules with a sensitive ground input are also available. The ground CT input of the sensitive ground modules is
ten times more sensitive than the ground CT input of standard CT/VT modules. However, the phase CT inputs and phase
VT inputs are the same as those of regular CT/VT modules.
The above modules are available with enhanced diagnostics. These modules can automatically detect CT/VT hardware
failure and take the relay out of service.
CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram.
The exact placement of a zero-sequence core balance CT to detect ground fault current is shown below. Twisted-pair
cabling on the zero-sequence CT is recommended.
Ground
outside CT
3
To ground;
LOAD must be on
load side
LOAD 996630A5
NOTE
~ 1a
~ 1b
~ 2a
~ 2b
~ 3a
~ 3b
~ 4a
~ 4b
~ 5a
~ 6a
~ 7a
~ 8a
~ 1c
~ 2c
~ 3c
~ 4c
~ 5c
~ 6c
~ 7c
~ 8c
VC
VB
VA
VX
IG
IG1
IA
IC
IA1
IC1
IB
IB1
IG5
VC
VB
VA
IA5
VX
IC5
IB5
~ 1b
~ 2a
~ 2b
~ 3a
~ 3b
~ 4a
~ 4b
~ 5a
~ 5b
~ 6a
~ 6b
~ 7a
~ 7b
~ 8a
~ 8b
~ 1c
~ 2c
~ 3c
~ 4c
~ 5c
~ 6c
~ 7c
~ 8c
IG
IG
IG1
IG1
IA
IC
IA
IC
IA1
IA1
IC1
IB
IC1
IB
IB1
IB1
IG5
IG5
IA5
IC5
IA5
IC5
IB5
IB5
Current inputs
8H, 8J, 8N, and 8R modules (8 CTs)
842766A3.CDR
The G60 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin
HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units,
known as Bricks. The HardFiber system has been designed to integrate seamlessly with the existing UR-series applica-
tions, including protection functions, FlexLogic™, metering, and communications.
The IEC 61850 process bus system offers the following benefits.
• Drastically reduces labor associated with design, installation, and testing of protection and control applications using
the G60 by reducing the number of individual copper terminations.
• Integrates seamlessly with existing G60 applications, since the IEC 61850 process bus interface module replaces the
traditional CT/VT modules.
• Communicates using open standard IEC 61850 messaging.
For additional details on the HardFiber system, refer to GE publication GEK-113500: HardFiber System Instruction Manual.
3
3.2.6 CONTACT INPUTS AND OUTPUTS
Every contact input/output module has 24 terminal connections. They are arranged as three terminals per row, with eight
rows in total. A given row of three terminals may be used for the outputs of one relay. For example, for form-C relay outputs,
the terminals connect to the normally open (NO), normally closed (NC), and common contacts of the relay. For a form-A
output, there are options of using current or voltage detection for feature supervision, depending on the module ordered.
The terminal configuration for contact inputs is different for the two applications.
The contact inputs are grouped with a common return. The G60 has two versions of grouping: four inputs per common
return and two inputs per common return. When a contact input/output module is ordered, four inputs per common is used.
The four inputs per common allows for high-density inputs in combination with outputs, with a compromise of four inputs
sharing one common. If the inputs must be isolated per row, then two inputs per common return should be selected (4D
module).
The tables and diagrams on the following pages illustrate the module types (6A, etc.) and contact arrangements that may
be ordered for the relay. Since an entire row is used for a single contact output, the name is assigned using the module slot
position and row number. However, since there are two contact inputs per row, these names are assigned by module slot
position, row number, and column position.
Some form-A / solid-state relay outputs include circuits to monitor the DC voltage across the output contact when it is open,
and the DC current through the output contact when it is closed. Each of the monitors contains a level detector whose out-
put is set to logic “On = 1” when the current in the circuit is above the threshold setting. The voltage monitor is set to “On =
1” when the current is above about 1 to 2.5 mA, and the current monitor is set to “On = 1” when the current exceeds about
80 to 100 mA. The voltage monitor is intended to check the health of the overall trip circuit, and the current monitor can be
used to seal-in the output contact until an external contact has interrupted current flow.
Block diagrams are shown below for form-A and solid-state relay outputs with optional voltage monitor, optional current
monitor, and with no monitoring. The actual values shown for contact output 1 are the same for all contact outputs.
~#c + ~#c +
b) Current with optional
Current monitoring only Both voltage and current monitoring
voltage monitoring
(external jumper a-b is required)
~#a
~#b
Load
~#c +
c) No monitoring 827862A3.CDR
Figure 3–17: FORM-A AND SOLID-STATE CONTACT OUTPUTS WITH VOLTAGE AND CURRENT MONITORING
The operation of voltage and current monitors is reflected with the corresponding FlexLogic™ operands (CONT OP # VON,
CONT OP # VOFF, and CONT OP # ION) which can be used in protection, control, and alarm logic. The typical application of
the voltage monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is seal-in of the
control command.
Refer to the Digital elements section of chapter 5 for an example of how form-A and solid-state relay contacts can be
applied for breaker trip circuit integrity monitoring.
Relay contacts must be considered unsafe to touch when the unit is energized! If the relay contacts need to
be used for low voltage accessible applications, it is the customer’s responsibility to ensure proper insula-
WARNING
tion levels!
USE OF FORM-A AND SOLID-STATE RELAY OUTPUTS IN HIGH IMPEDANCE CIRCUITS
NOTE For form-A and solid-state relay output contacts internally equipped with a voltage measuring cIrcuit across the
contact, the circuit has an impedance that can cause a problem when used in conjunction with external high input
impedance monitoring equipment such as modern relay test set trigger circuits. These monitoring circuits may con-
tinue to read the form-A contact as being closed after it has closed and subsequently opened, when measured as
an impedance.
The solution to this problem is to use the voltage measuring trigger input of the relay test set, and connect the form-
A contact through a voltage-dropping resistor to a DC voltage source. If the 48 V DC output of the power supply is
used as a source, a 500 Ω, 10 W resistor is appropriate. In this configuration, the voltage across either the form-A
contact or the resistor can be used to monitor the state of the output.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module; wherever a number
sign “#” appears, substitute the contact number
NOTE
When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, the Flex-
Logic™ operand driving the contact output should be given a reset delay of 10 ms to prevent damage of
NOTE
the output contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).
3
~4B MODULE ~4C MODULE ~4D MODULE ~4L MODULE
TERMINAL OUTPUT TERMINAL OUTPUT TERMINAL OUTPUT TERMINAL OUTPUT
ASSIGNMENT ASSIGNMENT ASSIGNMENT ASSIGNMENT
~1 Not Used ~1 Not Used ~1a, ~1c 2 Inputs ~1 2 Outputs
~2 Solid-State ~2 Solid-State ~2a, ~2c 2 Inputs ~2 2 Outputs
~3 Not Used ~3 Not Used ~3a, ~3c 2 Inputs ~3 2 Outputs
~4 Solid-State ~4 Solid-State ~4a, ~4c 2 Inputs ~4 2 Outputs
~5 Not Used ~5 Not Used ~5a, ~5c 2 Inputs ~5 2 Outputs
~6 Solid-State ~6 Solid-State ~6a, ~6c 2 Inputs ~6 2 Outputs
~7 Not Used ~7 Not Used ~7a, ~7c 2 Inputs ~7 2 Outputs
~8 Solid-State ~8 Solid-State ~8a, ~8c 2 Inputs ~8 Not Used
842762A2.CDR
6K
I I
~ 1b ~1 ~ 5c CONTACT IN ~ 5c ~1 ~ 1b ~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 1c ~ 6a CONTACT IN ~ 6a ~ 1c ~ 8a CONTACT IN ~ 8a ~ 1c
~ 2a ~ 6c CONTACT IN ~ 6c V ~ 2a ~ 8c CONTACT IN ~ 8c V ~ 2a
I I
~ 2b ~2 ~ 5b COMMON ~ 5b ~2 ~ 2b ~ 7b COMMON ~ 7b ~2 ~ 2b
~ 2c ~ 2c ~ 2c
~ 7a CONTACT IN ~ 7a ~ 8b SURGE
~ 3a ~ 3a ~ 3a
~ 7c CONTACT IN ~ 7c
~ 3b ~3 ~3 ~ 3b ~3 ~ 3b
~ 8a CONTACT IN ~ 8a
~ 3c ~ 3c ~ 3c
~ 8c CONTACT IN ~ 8c
~ 4a ~ 4a ~ 4a
~ 7b COMMON ~ 7b
~ 4b ~4 ~4 ~ 4b ~4 ~ 4b
~ 4c ~ 8b SURGE ~ 4c ~ 4c
~ 5a ~ 5a
~ 5b ~5 ~5 ~ 5b
~ 5c ~ 5c
~ 6a ~ 6a
~ 6b ~6 ~6 ~ 6b
~ 6c ~ 6c
~ 7a
3
DIGITAL I/O
~ 7b ~7
~ 7c
~ 8a
~ 8b ~8
~ 8c
842763A2.CDR
CONTACT INPUTS:
A dry contact has one side connected to terminal B3b. This is the positive 48 V DC voltage rail supplied by the power sup-
ply module. The other side of the dry contact is connected to the required contact input terminal. Each contact input group
has its own common (negative) terminal which must be connected to the DC negative terminal (B3a) of the power supply
module. When a dry contact closes, a current of 1 to 3 mA will flow through the associated circuit.
A wet contact has one side connected to the positive terminal of an external DC power supply. The other side of this contact
is connected to the required contact input terminal. If a wet contact is used, then the negative side of the external source
must be connected to the relay common (negative) terminal of each contact group. The maximum external source voltage
for this arrangement is 300 V DC.
The voltage threshold at which each group of four contact inputs will detect a closed contact input is programmable as
17 V DC for 24 V sources, 33 V DC for 48 V sources, 84 V DC for 110 to 125 V sources, and 166 V DC for 250 V sources.
B 1b
1
B 1a CRITICAL
FAILURE
B 2b
B 3a -
POWER SUPPLY
48 VDC
B 3b + OUTPUT
B 5b HI+
CONTROL
B 6b LO+
POWER
B 6a -
B 8a SURGE
B 8b FILTER
827741A4.CDR
NOTE
Contact outputs may be ordered as form-a or form-C. The form-A contacts may be connected for external circuit supervi-
sion. These contacts are provided with voltage and current monitoring circuits used to detect the loss of DC voltage in the
circuit, and the presence of DC current flowing through the contacts when the form-A contact closes. If enabled, the current
monitoring can be used as a seal-in signal to ensure that the form-A contact does not attempt to break the energized induc-
tive coil circuit and weld the output contacts.
There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We
recommend using an external DC supply.
NOTE
50 to 70 mA
3 mA
time
25 to 50 ms 842749A1.CDR
842751A1.CDR
Transducer input modules can receive input signals from external dcmA output transducers (dcmA In) or resistance tem-
perature detectors (RTD). Hardware and software is provided to receive signals from these external transducers and con-
vert these signals into a digital format for use as required.
Transducer output modules provide DC current outputs in several standard dcmA ranges. Software is provided to configure
virtually any analog quantity used in the relay to drive the analog outputs.
Every transducer input/output module has a total of 24 terminal connections. These connections are arranged as three ter-
minals per row with a total of eight rows. A given row may be used for either inputs or outputs, with terminals in column "a"
having positive polarity and terminals in column "c" having negative polarity. Since an entire row is used for a single input/
output channel, the name of the channel is assigned using the module slot position and row number.
Each module also requires that a connection from an external ground bus be made to terminal 8b. The current outputs
require a twisted-pair shielded cable, where the shield is grounded at one end only. The figure below illustrates the trans- 3
ducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module.
NOTE
A 9-pin RS232C serial port is located on the G60 faceplate for programming with a personal computer. All that is required
to use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for
the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
The baud rate for this port is fixed at 19200 bps.
NOTE
a) OPTIONS
In addition to the faceplate RS232 port, the G60 provides two additional communication ports or a managed six-port Ether-
net switch, depending on the installed CPU module.
The CPU modules do not require a surge ground connection.
NOTE
9K
COM1
Rx1
D1b +
9E
RS485 Tx2 100Base-F ALTERNATE
D2b ― Shielded twisted-pairs
Rx2
COM1
Ground at D3b COMMON D1a +
remote
RS485
D1a + D2a ―
device RS485 COM2
D2a ― Ground at D3a COMMON
COM2 remote
D3a COMMON D4b +
device
D4b + D4a ― IRIG-B
D4a ― IRIG-B input
BNC
input Co-axial cable
BNC
CPU
Co-axial cable BNC IRIG-B output
CPU
BNC IRIG-B output Co-axial cable
Co-axial cable
MM fiber
Tx1 10Base-FL NORMAL
9G
optic cable
COM1
Rx1 Shielded twisted-pairs
D1a +
RS485
9S
10Base-T ―
Shielded twisted-pairs D2a COM2
+
Ground at
D1a
D2a
D3a
―
COMMON
RS485
COM2
Ground at
remote
device
D3a
D4b
D4a
COMMON
+
― IRIG-B
3
remote D4b + input
device ― BNC
D4a IRIG-B
Co-axial cable
input
CPU
BNC BNC IRIG-B output
Co-axial cable Co-axial cable
CPU
BNC IRIG-B output
Co-axial cable
MM fiber SM fiber
Tx1 10Base-FL NORMAL 100Base-FL NORMAL COM1
9H
9L
optic cable Rx1 optic cable
COM1
Tx2
Rx2 10Base-F ALTERNATE D1a +
RS485
D2a ―
Shielded 10Base-T
COM2
twisted-pairs Ground at D3a COMMON
D1a + remote D4b +
RS485 device
D2a ― D4a ― IRIG-B
COM2
Ground at D3a COMMON input
remote BNC
D4b + Co-axial cable
device
D4a ― IRIG-B
CPU
BNC IRIG-B output
input
BNC Co-axial cable
Co-axial cable
CPU
MM fiber
Tx1 100Base-FL NORMAL COM1 SM fiber optic cable 100Base-FL NORMAL
9M
COM1
9J
CPU
BNC IRIG-B output
Co-axial cable
842765A7.CDR
b) RS485 PORTS
RS485 data transmission and reception are accomplished over a single twisted pair with transmit and receive data alternat-
ing over the same two wires. Through the use of these ports, continuous monitoring and control from a remote computer,
SCADA system or PLC is possible.
To minimize errors from noise, the use of shielded twisted pair wire is recommended. Correct polarity must also be
observed. For instance, the relays must be connected with all RS485 “+” terminals connected together, and all RS485 “–”
terminals connected together. The COM terminal should be connected to the common wire inside the shield, when pro-
vided. To avoid loop currents, the shield should be grounded at one point only. Each relay should also be daisy chained to
the next one in the link. A maximum of 32 relays can be connected in this manner without exceeding driver capability. For
larger systems, additional serial channels must be added. It is also possible to use commercially available repeaters to
increase the number of relays on a single channel to more than 32. Star or stub connections should be avoided entirely.
To minimize errors from noise, the use of shielded twisted pair wire is recommended. Correct polarity must also be
observed. For instance, the relays must be connected with all RS485 “+” terminals connected together, and all RS485 “–”
terminals connected together. Though data is transmitted over a two-wire twisted pair, all RS485 devices require a shared
reference, or common voltage. This common voltage is implied to be a power supply common. Some systems allow the
shield (drain wire) to be used as common wire and to connect directly to the G60 COM terminal (#3); others function cor-
rectly only if the common wire is connected to the G60 COM terminal, but insulated from the shield.
To avoid loop currents, the shield should be grounded at only one point. If other system considerations require the shield to
be grounded at more than one point, install resistors (typically 100 ohms) between the shield and ground at each grounding
point. Each relay should also be daisy-chained to the next one in the link. A maximum of 32 relays can be connected in this
manner without exceeding driver capability. For larger systems, additional serial channels must be added. It is also possible
to use commercially available repeaters to have more than 32 relays on a single channel. Star or stub connections should
be avoided entirely.
Lightning strikes and ground surge currents can cause large momentary voltage differences between remote ends of the
communication link. For this reason, surge protection devices are internally provided at both communication ports. An iso-
lated power supply with an optocoupled data interface also acts to reduce noise coupling. To ensure maximum reliability, all
equipment should have similar transient protection devices installed.
3 Both ends of the RS485 circuit should also be terminated with an impedance as shown below.
CAUTION
The fiber optic communication ports allow for fast and efficient communications between relays at 10 Mbps or 100 Mbps.
Optical fiber may be connected to the relay supporting a wavelength of 820 nm in multi-mode or 1310 nm in multi-mode
and single-mode. The 10 Mbps rate is available for CPU modules 9G and 9H; 100Mbps is available for modules 9H, 9J, 9K,
9L, 9M, 9N, 9P, and 9R. The 9H, 9K, 9M, and 9R modules have a second pair of identical optical fiber transmitter and
receiver for redundancy.
The optical fiber sizes supported include 50/125 µm, 62.5/125 µm and 100/140 µm for 10 Mbps. The fiber optic port is
designed such that the response times will not vary for any core that is 100 µm or less in diameter, 62.5 µm for 100 Mbps. 3
For optical power budgeting, splices are required every 1 km for the transmitter/receiver pair. When splicing optical fibers,
the diameter and numerical aperture of each fiber must be the same. In order to engage or disengage the ST type connec-
tor, only a quarter turn of the coupling is required.
3.2.10 IRIG-B
IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices within
1 millisecond. The IRIG time code formats are serial, width-modulated codes which can be either DC level shifted or ampli-
tude modulated (AM). Third party equipment is available for generating the IRIG-B signal; this equipment may use a GPS
satellite system to obtain the time reference so that devices at different geographic locations can also be synchronized.
TO OTHER DEVICES
(DC-SHIFT ONLY)
827756A5.CDR
NOTE
Using an amplitude modulated receiver will also cause errors of up to 1 ms in metered synchrophasor values.
Using the IRIG-B repeater function in conjunction with synchrophasors is not recommended, as the repeater adds
NOTE a 40 μs delay to the IRIG-B signal. This results in a 1° error for each consecutive device in the string as reported in
synchrophasors.
The G60 direct inputs and outputs feature makes use of the type 7 series of communications modules. These modules are
also used by the L90 Line Differential Relay for inter-relay communications. The direct input and output feature uses the
communications channels provided by these modules to exchange digital state information between relays. This feature is
available on all UR-series relay models except for the L90 Line Differential relay.
The communications channels are normally connected in a ring configuration as shown below. The transmitter of one mod-
ule is connected to the receiver of the next module. The transmitter of this second module is then connected to the receiver
of the next module in the ring. This is continued to form a communications ring. The figure below illustrates a ring of four
UR-series relays with the following connections: UR1-Tx to UR2-Rx, UR2-Tx to UR3-Rx, UR3-Tx to UR4-Rx, and UR4-Tx
to UR1-Rx. A maximum of sixteen (16) UR-series relays can be connected in a single ring
Tx
UR #1
Rx 3
Tx
UR #2
Rx
Tx
UR #3
Rx
Tx
UR #4
Rx
842006A1.CDR
Rx1
UR #1
Tx2
Rx2
Tx1
Rx1
UR #2
Tx2
Rx2
Tx1
Rx1
UR #3
Tx2
Rx2
Tx1
Rx1
UR #4
Tx2
Rx2
842007A1.CDR
Tx
UR #1
Rx
Channel #1
Tx1
Rx1
UR #2
Tx2
Rx2
Channel #2
Tx
3 UR #3
Rx
842013A1.CDR
Figure 3–31: DIRECT INPUT AND OUTPUT SINGLE/DUAL CHANNEL COMBINATION CONNECTION
The interconnection requirements are described in further detail in this section for each specific variation of type 7 commu-
nications module. These modules are listed in the following table. All fiber modules use ST type connectors.
Not all the direct input and output communications modules may be applicable to the G60 relay. Only the modules
specified in the order codes are available as direct input and output communications modules.
NOTE
OBSERVING ANY FIBER TRANSMITTER OUTPUT MAY CAUSE INJURY TO THE EYE.
CAUTION
3.3.2 FIBER: LED AND ELED TRANSMITTERS
3
The following figure shows the configuration for the 7A, 7B, 7C, 7H, 7I, and 7J fiber-only modules.
Module: 7A / 7B / 7C 7H / 7I / 7J
Connection Location: Slot X Slot X
RX1 RX1
TX1 TX1
RX2
TX2
The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser module.
TX1 TX1
RX1 RX1
TX2
RX2
a) DESCRIPTION
The following figure shows the 64K ITU G.703 co-directional interface configuration.
The G.703 module is fixed at 64 kbps. The SETTINGS Ö PRODUCT SETUP ÖØ DIRECT I/O ÖØ DIRECT I/O DATA RATE
setting is not applicable to this module.
NOTE
AWG 24 twisted shielded pair is recommended for external connections, with the shield grounded only at one end. Con-
necting the shield to pin X1a or X6a grounds the shield since these pins are internally connected to ground. Thus, if pin X1a
or X6a is used, do not ground at the other end. This interface module is protected by surge suppression devices.
Shield X 1a
3
7S
Tx – X 1b
G.703
channel 1 Rx – X 2a
Inter-relay communications Tx + X 2b
Rx + X 3a
Surge X 3b
Shield X 6a
Tx – X 6b
G.703
channel 2
Rx – X 7a
Tx + X 7b
Rx + X 8a
Surge X 8b
842773A2.CDR
7S
Tx - X 1b X 1b Tx -
G.703 G.703
CHANNEL 1
Rx - X 2a X 2a Rx -
CHANNEL 1
Tx + X 2b X 2b Tx +
Rx + X 3a X 3a Rx +
SURGE X 3b X 3b SURGE
Shld. X 6a X 6a Shld.
Tx - X 6b X 6b Tx -
G.703 G.703
Rx - X 7a X 7a Rx -
COMM.
COMM.
CHANNEL 2 CHANNEL 2
Tx + X 7b X 7b Tx +
Rx + X 8a X 8a Rx +
SURGE X 8b X 8b SURGE
831727A3.CDR
6. Re-insert the G.703 module. Take care to ensure that the correct module type is inserted into the correct slot position.
The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged position as
the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the
clips simultaneously. When the clips have locked into position, the module will be fully inserted.
The switch settings for the internal and loop timing modes are shown below:
842752A1.CDR
3 In minimum remote loopback mode, the multiplexer is enabled to return the data from the external interface without any
processing to assist in diagnosing G.703 line-side problems irrespective of clock rate. Data enters from the G.703 inputs,
passes through the data stabilization latch which also restores the proper signal polarity, passes through the multiplexer
and then returns to the transmitter. The differential received data is processed and passed to the G.703 transmitter module
after which point the data is discarded. The G.703 receiver module is fully functional and continues to process data and
passes it to the differential Manchester transmitter module. Since timing is returned as it is received, the timing source is
expected to be from the G.703 line side of the interface.
DMX G7R
842774A1.CDR
DMX G7R
842775A1.CDR
a) DESCRIPTION
There are two RS422 inter-relay communications modules available: single-channel RS422 (module 7T) and dual-channel
RS422 (module 7W). The modules can be configured to run at 64 kbps or 128 kbps. AWG 24 twisted shielded pair cable is
recommended for external connections. These modules are protected by optically-isolated surge suppression devices.
The shield pins (6a and 7b) are internally connected to the ground pin (8a). Proper shield termination is as follows:
• Site 1: Terminate shield to pins 6a or 7b or both.
• Site 2: Terminate shield to COM pin 2b.
The clock terminating impedance should match the impedance of the line.
Single-channel RS422 module Dual-channel RS422 module
~ 3b Tx – ~ 3b Tx – 3
7W
7T
~ 3a Rx – ~ 3a Rx –
RS422
~ 2a Tx + RS422 ~ 2a Tx +
channel 1
Inter-relay comms.
~ 4b Rx + ~ 4b Rx +
~ 6a Shield ~ 6a Shield
Inter-relay communications
~ 7a ~ 5b Tx –
Clock
~ 8b ~ 5a Rx –
RS422
~ 2b COM ~ 4a Tx +
channel 2
~ 8a Surge ~ 6b Rx +
~ 7b Shield
~ 7a
Clock
~ 8b
~ 2b COM
Data module 1
Signal name
Tx1(+) W 2a SD(A) - Send data
7W
Tx1(-) W 3b SD(B) - Send data
RS422
CHANNEL 1
Rx1(+) W 4b RD(A) - Received data
Rx1(-) W 3a RD(B) - Received data
Shld. W 6a RS(A) - Request to send (RTS)
INTER-RELAY COMMUNICATIONS
+ W 7a RS(B) - Request to send (RTS)
CLOCK
– W 8b RT(A) - Receive timing
Tx2(+) W 4a RT(B) - Receive timing
Tx2(-) W 5b CS(A) - Clear To send
RS422
CHANNEL 2
Rx2(+) W 6b CS(B) - Clear To send
Rx2(-) W 5a Local loopback
Shld. W 7b Remote loopback
com W 2b Signal ground
SURGE W 8a ST(A) - Send timing
ST(B) - Send timing
3 Data module 2
Signal name
TT(A) - Terminal timing
TT(B) - Terminal timing
SD(A) - Send data
SD(B) - Send data
RD(A) - Received data
RD(B) - Received data
RS(A) - Request to send (RTS)
RS(B) - Request to send (RTS)
CS(A) - Clear To send
CS(B) - Clear To send
Local loopback
Remote loopback
Signal ground
ST(A) - Send timing
ST(B) - Send timing
831022A3.CDR
c) TRANSMIT TIMING
The RS422 interface accepts one clock input for transmit timing. It is important that the rising edge of the 64 kHz transmit
timing clock of the multiplexer interface is sampling the data in the center of the transmit data window. Therefore, it is impor-
tant to confirm clock and data transitions to ensure proper system operation. For example, the following figure shows the
positive edge of the Tx clock in the center of the Tx data bit.
Tx Clock
Tx Data
d) RECEIVE TIMING
The RS422 interface utilizes NRZI-MARK modulation code and; therefore, does not rely on an Rx clock to recapture data.
NRZI-MARK is an edge-type, invertible, self-clocking code.
To recover the Rx clock from the data-stream, an integrated DPLL (digital phase lock loop) circuit is utilized. The DPLL is
driven by an internal clock, which is 16-times over-sampled, and uses this clock along with the data-stream to generate a
data clock that can be used as the SCC (serial communication controller) receive clock.
The following figure shows the combined RS422 plus Fiber interface configuration at 64K baud. The 7L, 7M, 7N, 7P, and 74
modules are used in two-terminal with a redundant channel or three-terminal configurations where channel 1 is employed
via the RS422 interface (possibly with a multiplexer) and channel 2 via direct fiber.
AWG 24 twisted shielded pair is recommended for external RS422 connections and the shield should be grounded only at
one end. For the direct fiber channel, power budget issues should be addressed properly.
When using a LASER Interface, attenuators may be necessary to ensure that you do not exceed maximum
WARNING
optical input power to the receiver.
3
~ 1a Clock
Inter-relay comms.
~ 4b Rx1 +
~ 6a Shield
Fiber
Tx2 Rx2 channel 2
~ 8a Surge
842777A1.CDR
The figure below shows the combined G.703 plus fiber interface configuration at 64 kbps. The 7E, 7F, 7G, 7Q, and 75 mod-
ules are used in configurations where channel 1 is employed via the G.703 interface (possibly with a multiplexer) and chan-
nel 2 via direct fiber. AWG 24 twisted shielded pair is recommended for external G.703 connections connecting the shield to
pin 1a at one end only. For the direct fiber channel, power budget issues should be addressed properly. See previous sec-
tions for additional details on the G.703 and fiber interfaces.
When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maxi-
mum optical input power to the receiver.
WARNING
~ 1a
7E, 7F, 7G,
7Q,75
Shield
~ 1b Tx –
G.703
~ 2a Rx –
channel 1
~ 2b Tx +
communications
~ 3a Rx +
~ 3b Surge
Inter-relay
Tx2 Fiber
Rx2 channel 2
842778A1.CDR
The UR-series IEEE C37.94 communication modules (modules types 2G, 2H, 76, and 77) are designed to interface with
IEEE C37.94 compliant digital multiplexers or an IEEE C37.94 compliant interface converter for use with direct input and
output applications for firmware revisions 3.30 and higher. The IEEE C37.94 standard defines a point-to-point optical link
for synchronous data between a multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard
provides for speeds up to 64n kbps, where n = 1, 2,…, 12. The UR-series C37.94 communication modules are either
64 kbps (with n fixed at 1) for 128 kbps (with n fixed at 2). The frame is a valid International Telecommunications Union
(ITU-T) recommended G.704 pattern from the standpoint of framing and data rate. The frame is 256 bits and is repeated at
a frame rate of 8000 Hz, with a resultant bit rate of 2048 kbps.
The specifications for the module are as follows:.
• IEEE standard: C37.94 for 1 × 128 kbps optical fiber interface (for 2G and 2H modules) or C37.94 for 2 × 64 kbps opti-
3 •
cal fiber interface (for 76 and 77 modules).
Fiber optic cable type: 50 mm or 62.5 mm core diameter optical fiber.
• Fiber optic mode: multi-mode.
• Fiber optic cable length: up to 2 km.
• Fiber optic connector: type ST.
• Wavelength: 830 ±40 nm.
• Connection: as per all fiber optic connections, a Tx to Rx connection is required.
The UR-series C37.94 communication module can be connected directly to any compliant digital multiplexer that supports
the IEEE C37.94 standard as shown below.
The UR-series C37.94 communication module can be connected to the electrical interface (G.703, RS422, or X.21) of a
non-compliant digital multiplexer via an optical-to-electrical interface converter that supports the IEEE C37.94 standard, as
shown below.
The UR-series C37.94 communication module has six (6) switches that are used to set the clock configuration. The func-
tions of these control switches is shown below.
842753A1.CDR
For the internal timing mode, the system clock is generated internally. therefore, the timing switch selection should be inter-
nal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, the timing selection
should be in loop timing mode for connections to higher order systems.
The IEEE C37.94 communications module cover removal procedure is as follows:
1. Remove the IEEE C37.94 module (type 2G, 2H, 76 or 77 module):
The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order
to release the module for removal. Before performing this action, control power must be removed from the relay.
The original location of the module should be recorded to help ensure that the same or replacement module is inserted
into the correct slot.
2. Remove the module cover screw.
3. Remove the top cover by sliding it towards the rear and then lift it upwards. 3
4. Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above).
5. Replace the top cover and the cover screw.
6. Re-insert the IEEE C37.94 module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged posi-
tion as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.
The UR-series C37.94SM communication modules (2A and 2B) are designed to interface with modified IEEE C37.94 com-
pliant digital multiplexers or IEEE C37.94 compliant interface converters that have been converted from 820 nm multi-mode
fiber optics to 1300 nm ELED single-mode fiber optics. The IEEE C37.94 standard defines a point-to-point optical link for
synchronous data between a multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard pro-
vides for speeds up to 64n kbps, where n = 1, 2,…, 12. The UR-series C37.94SM communication module is 64 kbps only
with n fixed at 1. The frame is a valid International Telecommunications Union (ITU-T) recommended G.704 pattern from
the standpoint of framing and data rate. The frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit
rate of 2048 kbps.
The specifications for the module are as follows:
• Emulated IEEE standard: emulates C37.94 for 1 × 64 kbps optical fiber interface (modules set to n = 1 or 64 kbps).
3 • Fiber optic cable type: 9/125 μm core diameter optical fiber.
• Fiber optic mode: single-mode, ELED compatible with HP HFBR-1315T transmitter and HP HFBR-2316T receiver.
• Fiber optic cable length: up to 10 km.
• Fiber optic connector: type ST.
• Wavelength: 1300 ±40 nm.
• Connection: as per all fiber optic connections, a Tx to Rx connection is required.
The UR-series C37.94SM communication module can be connected directly to any compliant digital multiplexer that sup-
ports C37.94SM as shown below.
It can also can be connected directly to any other UR-series relay with a C37.94SM module as shown below.
The UR-series C37.94SM communication module has six (6) switches that are used to set the clock configuration. The
functions of these control switches is shown below.
842753A1.CDR
For the internal timing mode, the system clock is generated internally. Therefore, the timing switch selection should be
internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, the timing selection
should be in loop timing mode for connections to higher order systems.
The C37.94SM communications module cover removal procedure is as follows:
1. Remove the C37.94SM module (modules 2A or 2B):
The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order
to release the module for removal. Before performing this action, control power must be removed from the relay.
The original location of the module should be recorded to help ensure that the same or replacement module is inserted
into the correct slot.
2. Remove the module cover screw.
3. Remove the top cover by sliding it towards the rear and then lift it upwards.
4. Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above).
5. Replace the top cover and the cover screw. 3
6. Re-insert the C37.94SM module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged posi-
tion as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.
The field ground protection modules are used in the following protection sytems.
• Field low voltage protection system (order code GPM-F-L) for voltages up to 600 V DC.
• Field high voltage protection system (order code GPM-F-H) for voltages greater than 600 V DC.
• Stator protection system (order code GPM-S).
These systems are illustrated below for comparative purposes in the following figure.
GPM-F-L
Field ground
GPM-F-L: Field ground low-voltage protection module
low-voltage
3 protection system
GPM-F-H
Field ground
high-voltage
protection system
830755A2.CDR
The field ground low voltage protection system consists of one module: the field ground protection low-voltage module
(GPM-F-L). The mounting and dimension diagrams are shown below (all dimensions are in inches).
10.270
10.142
2.160
12.270 9.090
830017A1.CDR
1.000
10.072
7.574
11.770 10.142
2.306
12.270 9.090
830016A1.CDR
Nut Nylock
3 Screw 10-32×3/8”
Zinc 10-32
GE P/N 1422-1032
QTY: 4
Pan HD Zinc
Washer flat Zinc #10
GE P/N 1410-0006
GE P/N 1430-0006
QTY: 4
QTY: 4
Ø 0.220 10.813
1.000
2.200
0.600
11.520 830018A1.CDR
Ø 0.220
7.574 4×
11.520
3
Nut Nylock
Zinc 10-32
GE P/N 1422-1032
QTY: 4
Washer flat Zinc #10
GE P/N 1430-0006
QTY: 4
2 4 6 8 10 12
1 2 3 4
123 1 3 5 7 9 11
830023A1.CDR
The following diagram illustrates how to wire the GPM-F-L module for both single-point injection and double-point injection.
C1 C1
F1 F1
Field ground C2 Field ground C2
protection protection
module module F(–)
GPM-F-HM C3 GPM-F-HM C3
– –
F(+)
C4 EX C4 EX
+ +
Connection for Connection for
single-point injection double-point injection
830759A2.CDR
The field ground high-voltage protection system consists of two modules: the field ground protection high-voltage module
(GPM-F-HM) and the field ground protection high-voltage resistor box (GPM-F-R). The mounting and dimension diagrams
are shown below (all dimensions are in inches).
10.270
10.142
2.160
12.270 9.090
830017A1.CDR
1.000
10.072
7.574
11.770 10.142
2.306
12.270 9.090
830016A1.CDR
7.000
6.500
5.875
5.000
3.500
7.000
2.500
2.750
8.600
830753A1.CDR
Nut Nylock
Zinc 10-32
GE P/N 1422-1032
3
Screw 10-32×3/8” QTY: 4
Pan HD Zinc
Washer flat Zinc #10
GE P/N 1410-0006
GE P/N 1430-0006
QTY: 4
QTY: 4
Ø 0.220 10.813
1.000
2.200
0.600
11.520 830018A1.CDR
Ø 0.220
7.574 4×
3 11.520
Nut Nylock
Zinc 10-32
GE P/N 1422-1032
QTY: 4
Washer flat Zinc #10
GE P/N 1430-0006
QTY: 4
5.938
Screw 10-32×3/8”
Pan HD Zinc, GE P/N 1410-0006, QTY: 4 830019A1.CDR
2 4 6 8 10 12
1 2 3 4
123 1 3 5 7 9 11
830023A1.CDR
There are three connectors on the field ground protection high-voltage resistor box as shown below.
7 6 5 4 3 2 1
Connector A
3 2 1 3 2 1
Connector B Connector C
830026A2.CDR
The following diagram illustrates how to wire the GPM-F-HM module with the GPM-F-R resistor box for both single-point
injection and double-point injection.
F2+
A1 B1
C1
A2 B2 +
Field ground F2
F1 A3 B3 EX
Field ground C2 protection Connection for
protection high-voltage – single-point
A4
module F– resistor box injection
C3 F2–
GPM-F-HM A5 module C1
GPM-F-R
A6 C2
F+
C4
A7 C3
F2+
3
A1 B1
C1
A2 B2 +
Field ground F2
F1 A3 B3 EX
Field ground C2 protection Connection for
protection high-voltage – double-point
A4
module F– resistor box injection
C3 F2–
GPM-F-HM A5 module C1
GPM-F-R
A6 C2
F+
C4
A7 C3
830758A6.CDR
Figure 3–62: CONNECTING THE FIELD GROUND PROTECTION MODULE TO THE HIGH-VOLTAGE RESISTOR BOX
The connection between F1 (terminal C2) on the GPM-F-HM field ground protection module and terminal A3 on the
GPM-F-R high-voltage resistor box module should be shielded. The length should be kept as short as possible and
NOTE not exceed 10 meters.
The connection between the F+ and F– pair (terminals C3 and C4) on the GPM-F-HM field ground protection mod-
ule and terminals A5 and A7 on the GPM-F-R high-voltage resistor box module should be shielded. The length
NOTE should be kept as short as possible and not exceed 10 meters.
Terminals C1 and C3 must be externally shorted for both single-point and double-point injection.
NOTE
In the 100% stator ground fault protection based on sub-harmonic injection, a 20 Hz voltage is injected to detect ground
faults at any point across 100% of the winding. The stator ground module works in combination the G60 to provide 100%
stator ground fault protection that is operational during generator start-up, running and stopped conditions.
The stator ground protection system consists of three modules: the stator ground protection 20 Hz generator module
(GPM-S-G), the stator ground band pass filter module (GPM-S-B), and the stator ground protection CT (204-SD-43737).
The mounting and dimension diagrams are shown below (all dimensions are in inches).
17.760
8.451
5.250
19.160 7.250
830012A2.CDR
18.960
6.250
0.250
830754A2.CDR
7.500
11.870
8.300 3
7.310
7.869
9.370 830020A1.CDR
Nut Nylock
Zinc 10-32
GE P/N 1422-1032
QTY: 4
18.710
Ø 0.220
4×
6.250
830021A1.CDR
Screw 10-32×3/8”
Pan HD Zinc
GE P/N 1410-0006
QTY: 4
Nut Nylock
Zinc 10-32
GE P/N 1422-1032
3
QTY: 4
18.498
4.000 5.375
18.000 830022A1.CDR
10.870 Ø 0.220
4×
5.490
Figure 3–68: MOUNTING DIAGRAM FOR GPM-S-B BAND PASS FILTER MODULE
There are two connectors on the stator ground protection 20 Hz generator module as shown below.
A B
1 3 5 7 9 1 3 5 7 9
2 4 6 8 10 2 4 6 8 10
830025A1.CDR
There are two connectors on the stator ground protection band pass filter module as shown below.
1 1
2 2
3 3
4 4
5 5
6 6
7 7
A B
3
830024A2.CDR
The following diagram illustrates how to connect the stator ground 20 Hz generator module with the band pass filter module
where the NGT secondary voltage is less than or equal to 240 V.
to G60
A1 auxiliary VT
A2
A3
Stator A4 A1 B1
ground
20 Hz A5 A2 B2
generator Stator ground
A6 A3 band pass B3
module Rn
GPM-S-G A7 A4 filter module B4
GPM-S-B
A8 A5 B5
A9 A6 B6
A10 A7 B7
830756A1.CDR
3 Figure 3–71: STATOR GROUND PROTECTION SYSTEM CONNECTIONS (NGT SECONDARY ≤ 240 V)
The following diagram illustrates how to connect the stator ground 20 Hz generator module with the band pass filter module
where the NGT secondary voltage is greater than 240 V.
A1
A2
A3
Stator A4
ground
20 Hz A5
generator A6
module
GPM-S-G A7
A8 A1 B1
A9 A2 B2
A10 A3 Stator ground B3
band pass Rn
A4 B4
filter module
A5 GPM-S-B B5
to G60 A6 B6
auxiliary VT A7 B7
830757A2.CDR
Figure 3–72: STATOR GROUND PROTECTION SYSTEM CONNECTIONS (NGT SECONDARY > 240 V)
The type 2S and 2T embedded managed switch modules are supported by UR-series relays containing type 9S CPU mod-
ules with revisions 5.5x and higher. The modules communicate to the G60 through an internal Ethernet port (referred to as
the UR port or port 7) and provide an additional six external Ethernet ports: two 10/100Base-T ports and four multimode ST
100Base-FX ports.
The Ethernet switch module should be powered up before or at the same time as the G60. Otherwise, the switch
module will not be detected on power up and the EQUIPMENT MISMATCH: ORDERCODE XXX self-test warning will be
NOTE issued.
The type 2S and 2T managed Ethernet switch modules provide two 10/100Base-T and four multimode ST 100Base-FX
external Ethernet ports accessible through the rear of the module. In addition, a serial console port is accessible from the 3
front of the module (requires the front panel faceplate to be open).
The pin assignment for the console port signals is shown in the following table.
Two 10/100Base-T
ports
Four 100Base-FX
multimode ports
with ST connectors
RS232
console port
Independent power
supply. Options:
2S: high-voltage
2T: low-voltage
The wiring for the managed Ethernet switch module is shown below.
2S / 2T
Rx1
CPU
W1a GROUND
842835A1.CDR
The 10/100Base-T and 100Base-FX ports have LED indicators to indicate the port status.
The 10/100Base-T ports have three LEDs to indicate connection speed, duplex mode, and link activity. The 100Base-FX
ports have one LED to indicate linkup and activity.
842868A2.CDR
a) DESCRIPTION
Upon initial power up of a G60 device with an installed Ethernet switch, the front panel trouble LED will be illuminated and
the ENET MODULE OFFLINE error message will be displayed. It will be necessary to configure the Ethernet switch and then
place it online. This involves two steps:
1. Configuring the network settings on the local PC.
2. Configuring the G60 switch module through EnerVista UR Setup.
These procedures are described in the following sections. When the G60 is properly configured, the LED will be off and the
error message will be cleared.
2. Ensure that the PC and the G60 are on the same IP network.
If your computer is on another network or has a dynamic IP address assigned upon a network login, then setup your
own IP address as follows
2.1. From the Windows Start Menu, select the Settings > Network Connections menu item.
2.2. Right-click on the Local Area Connection icon and select the Properties item. This will open the LAN proper-
ties window.
2.3. Click the Properties button as shown below.
827790A1.CDR
2.4. The following window is displayed. Select the Use the Following IP Address option and enter appropriate IP
address, Subnet mask, and Default gateway values. It may be necessary to contact your network administra-
tor for assistance.
827803A1.CDR
Alternately, you can open a command window (type “cmd” from the Run item in the Start menu) and enter the ipconfig
command.
3
6. Now that the PC should be able to communicate to the UR relay through the UR Setup software.
New site
Old site
827804A1.CDR
5. Click the Read Order Code button. You should be able to communicate with the G60 device regardless of the value of
the Ethernet switch IP address and even though the front panel display states that the Ethernet module is offline.
6. Select the Settings > Product Setup > Communications > Ethernet Switch > Configure IP menu item as shown
below.
7. Enter (or verify) the MAC Address, IP Address, Subnet Mask, and Gateway IP Address settings.
8. Click the Save button. It will take few seconds to save the settings to the Ethernet switch module and the following
message displayed.
9. Verify that the target message is cleared and that the G60 displays the MAC address of the Ethernet switch in the
Actual Values > Status > Ethernet Switch window.
The G60 device and the Ethernet switch module communications setup is now complete.
A suitable IP/gateway and subnet mask must be assigned to both the switch and the UR relay for correct operation. The
Switch has been shipped with a default IP address of 192.168.1.2 and a subnet mask of 255.255.255.0. Consult your net-
work administrator to determine if the default IP address, subnet mask or default gateway needs to be modified.
Do not connect to network while configuring the switch module.
CAUTION
2. Enter “3.94.247.229” in the IP Address field and “255.255.252.0” in the Subnet Mask field, then click OK.
The software will send the new settings to the G60 and prompt as follows when complete.
3. Cycle power to the G60 and switch module to activate the new settings.
The system will request the name and destination path for the settings file.
1. Select the desired device from site tree in the online window.
2. Select the Settings > Product Setup > Communications > Ethernet Switch > Ethernet Switch Settings File >
Transfer Settings File item from the device settings tree.
The system will request the name and destination path for the settings file.
3. Navigate to the folder containing the Ethernet switch settings file, select the file, then click Open.
The settings file will be transferred to the Ethernet switch and the settings uploaded to the device.
a) DESCRIPTION
This section describes the process for upgrading firmware on a UR-2S or UR-2T switch module.
There are several ways of updating firmware on a switch module:
• Using the EnerVista UR Setup software.
• Serially using the G60 switch module console port.
• Using FTP or TFTP through the G60 switch module console port.
It is highly recommended to use the EnerVista UR Setup software to upgrade firmware on a G60 switch module.
Firmware upgrades using the serial port, TFTP, and FTP are described in detail in the switch module manual.
NOTE 3
b) SELECTING THE PROPER SWITCH FIRMWARE VERSION
The latest switch module firmware is available as a download from the GE Multilin web site. Use the following procedure to
determine the version of firmware currently installed on your switch
1. Log into the switch using the EnerVista web interface.
The default switch login ID is “manager” and the default password is “manager”.
NOTE
The firmware version installed on the switch will appear on the lower left corner of the screen.
2. Using the EnerVista UR Setup program, select the Settings > Product Setup > Communications > Ethernet Switch
> Firmware Upload menu item.
The following popup screen will appear warning that the settings will be lost when the firmware is upgraded.
It is highly recommended that you save the switch settings before upgrading the firmware.
NOTE
3. After saving the settings file, proceed with the firmware upload by selecting Yes to the above warning.
3 Another window will open, asking you to point to the location of the firmware file to be uploaded.
4. Select the firmware file to be loaded on to the Switch, and select the Open option.
The following window will pop up, indicating that the firmware file transfer is in progress.
If the firmware load was successful, the following window will appear:
Note
The switch will automatically reboot after a successful firmware file transfer.
NOTE
5. Once the firmware has been successfully uploaded to the switch module, load the settings file using the procedure
described earlier.
The following table provides details about Ethernet module self-test errors.
Be sure to enable the ETHERNET SWITCH FAIL setting in the PRODUCT SETUP ÖØ USER-PROGRAMMABLE SELF-TESTS menu
and the relevant PORT 1 EVENTS through PORT 6 EVENTS settings under the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ ETH-
ERNET SWITCH menu.
The EnerVista UR Setup software provides a graphical user interface (GUI) as one of two human interfaces to a UR device.
The alternate human interface is implemented via the device’s faceplate keypad and display (refer to the Faceplate inter-
face section in this chapter).
The EnerVista UR Setup software provides a single facility to configure, monitor, maintain, and trouble-shoot the operation
of relay functions, connected over local or wide area communication networks. It can be used while disconnected (off-line)
or connected (on-line) to a UR device. In off-line mode, settings files can be created for eventual downloading to the device.
In on-line mode, you can communicate with the device in real-time.
The EnerVista UR Setup software, provided with every G60 relay, can be run from any computer supporting Microsoft Win-
dows® 95, 98, NT, 2000, ME, and XP. This chapter provides a summary of the basic EnerVista UR Setup software interface
features. The EnerVista UR Setup Help File provides details for getting started and using the EnerVista UR Setup software
interface.
To start using the EnerVista UR Setup software, a site definition and device definition must first be created. See the EnerV-
ista UR Setup Help File or refer to the Connecting EnerVista UR Setup with the G60 section in Chapter 1 for details.
f) FILE SUPPORT
• Execution: Any EnerVista UR Setup file which is double clicked or opened will launch the application, or provide focus
to the already opened application. If the file was a settings file (has a URS extension) which had been removed from
the Settings List tree menu, it will be added back to the Settings List tree menu.
• Drag and Drop: The Site List and Settings List control bar windows are each mutually a drag source and a drop target
for device-order-code-compatible files or individual menu items. Also, the Settings List control bar window and any
Windows Explorer directory folder are each mutually a file drag source and drop target.
New files which are dropped into the Settings List window are added to the tree which is automatically sorted alphabet-
ically with respect to settings file names. Files or individual menu items which are dropped in the selected device menu
in the Site List window will automatically be sent to the on-line communicating device.
g) FIRMWARE UPGRADES
The firmware of a G60 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond-
ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (i.e. default
values, minimum/maximum values, data type, and item size) may change slightly from version to version of firm-
NOTE
ware. The addresses are rearranged when new features are added or existing features are enhanced or modified.
The EEPROM DATA ERROR message displayed after upgrading/downgrading the firmware is a resettable, self-test
message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This
message does not signal any problems when appearing after firmware upgrades.
The EnerVista UR Setup software main window supports the following primary display components:
1. Title bar which shows the pathname of the active data view.
2. Main window menu bar.
3. Main window tool bar.
4. Site list control bar window.
5. Settings list control bar window.
6. Device data view windows, with common tool bar.
7. Settings file data view windows, with common tool bar. 4
8. Workspace area with data view tabs.
9. Status bar.
10. Quick action hot links.
2 1 6 7
10
4
9 8 842786A2.CDR
Setting file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An exam-
ple of this is a substation that has ten similar feeders protected by ten UR-series F60 relays.
In these situations, typically 90% or greater of the settings are identical between all devices. The templates feature allows
engineers to configure and test these common settings, then lock them so they are not available to users. For example,
these locked down settings can be hidden from view for field engineers, allowing them to quickly identify and concentrate
on the specific settings.
The remaining settings (typically 10% or less) can be specified as editable and be made available to field engineers install-
ing the devices. These will be settings such as protection element pickup values and CT and VT ratios.
The settings template mode allows the user to define which settings will be visible in EnerVista UR Setup. Settings tem-
plates can be applied to both settings files (settings file templates) and online devices (online settings templates). The func-
tionality is identical for both purposes.
The settings template feature requires that both the EnerVista UR Setup software and the G60 firmware are at ver-
sions 5.40 or higher.
NOTE
The software will prompt for a template password. This password is required to use the template feature and must be
at least four characters in length.
3. Enter and re-enter the new password, then click OK to continue.
The online settings template is now enabled. The device is now in template editing mode.
By default, all settings are specified as locked and displayed against a grey background. The icon on the upper right of
the settings window will also indicate that EnerVista UR Setup is in EDIT mode. The following example shows the
phase time overcurrent settings window in edit mode.
The software will prompt for a template password. This password must be at least four characters in length.
Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND
Viewing the settings in template mode also modifies the settings tree, showing only the settings categories that contain
editable settings. The effect of applying the template to a typical settings tree view is shown below.
Typical settings tree view without template applied. Typical settings tree view with template applied via
the Template Mode > View In Template Mode
command.
842860A1.CDR
Figure 4–5: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE SETTINGS COMMAND
Use the following procedure to display settings available for editing and settings locked by the template. 4
1. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Apply the template by selecting the Template Mode > View All Settings option.
3. Enter the template password then click OK to apply the template.
Once the template has been applied, users will only be able to edit the settings specified by the template, but all settings
will be shown. The effect of applying the template to the phase time overcurrent settings is shown below.
Phase time overcurrent settings window without template applied. Phase time overcurrent window with template applied via
the Template Mode > View All Settings command.
The template specifies that only the Pickup and Curve
settings be available.
842859A1.CDR
Figure 4–6: APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COMMAND
4. Verify one more time that you wish to remove the template by clicking Yes.
The EnerVista software will remove all template information and all settings will be available.
The UR allows users to secure parts or all of a FlexLogic™ equation, preventing unauthorized viewing or modification of
critical FlexLogic™ applications. This is accomplished using the settings template feature to lock individual entries within
FlexLogic™ equations.
Secured FlexLogic™ equations will remain secure when files are sent to and retrieved from any UR-series device.
4 The following procedure describes how to lock individual entries of a FlexLogic™ equation.
1. Right-click the settings file or online device and select the Template Mode > Create Template item to enable the set-
tings template feature.
2. Select the FlexLogic > FlexLogic Equation Editor settings menu item.
By default, all FlexLogic™ entries are specified as viewable and displayed against a yellow background. The icon on
the upper right of the window will also indicate that EnerVista UR Setup is in EDIT mode.
3. Specify which entries to lock by clicking on them.
The locked entries will be displayed against a grey background as shown in the example below.
Once the template has been applied, users will only be able to view and edit the FlexLogic™ entries not locked by the tem-
plate. The effect of applying the template to the FlexLogic™ entries in the above procedure is shown below.
Typical FlexLogic™ entries without template applied. Typical FlexLogic™ entries locked with template via
the Template Mode > View In Template Mode command.
842861A1.CDR
4 3. Enter the serial number of the G60 device to lock to the settings file in the Serial # Lock field.
The settings file and corresponding secure FlexLogic™ equations are now locked to the G60 device specified by the serial
number.
A traceability feature for settings files allows the user to quickly determine if the settings in a G60 device have been
changed since the time of installation from a settings file. When a settings file is transfered to a G60 device, the date, time,
and serial number of the G60 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor-
mation can be compared with the G60 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the G60
device or obtained from the G60 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.
The serial number of the UR-series device and the file transfer
date are added to the settings file when settings files
are transferred to the device.
1. The transfer date of a setting file written to a G60 is logged in the relay and can be viewed via EnerVista UR Setup or
the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
2. Comparing the dates stored in the relay and on the settings file at any time in the future will indicate if any changes
have been made to the relay configuration since the settings file was saved.
4
842863A1.CDR
Traceability data
in settings report
842862A1.CDR
842865A1.CDR
a) ENHANCED FACEPLATE
The front panel interface is one of two supported interfaces, the other interface being EnerVista UR Setup software. The
front panel interface consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional user-
programmable pushbuttons.
The faceplate is hinged to allow easy access to the removable modules.
Display
Keypad
4
Front panel
RS232 port
b) STANDARD FACEPLATE
The front panel interface is one of two supported interfaces, the other interface being EnerVista UR Setup software. The
front panel interface consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional user-
programmable pushbuttons.
The faceplate is hinged to allow easy access to the removable modules. There is also a removable dust cover that fits over
the faceplate which must be removed in order to access the keypad panel. The following figure shows the horizontal
arrangement of the faceplate panels.
Display
Front panel
RS232 port
The following figure shows the vertical arrangement of the faceplate panels for relays ordered with the vertical option.
DISPLAY
MENU 7 8 9
HELP MESSAGE 4 5 6
ESCAPE 1 2 3 KEYPAD
ENTER VALUE 0 . +/-
LED PANEL 3
4 LED PANEL 2
USER 2
LED PANEL 1
827830A1.CDR
PHASE C
NEUTRAL/GROUND USER 3
a) ENHANCED FACEPLATE
The enhanced front panel display provides five columns of LED indicators. The first column contains 14 status and event
cause LEDs, and the next four columns contain the 48 user-programmable LEDs.
The RESET key is used to reset any latched LED indicator or target message, once the condition has been cleared (these
latched conditions can also be reset via the SETTINGS ÖØ INPUT/OUTPUTS ÖØ RESETTING menu). The RS232 port is
intended for connection to a portable PC.
The USER keys are not used in this unit.
842811A1.CDR
• TROUBLE: This LED indicates that the relay has detected an internal problem.
• TEST MODE: This LED indicates that the relay is in test mode.
• TRIP: This LED indicates that the FlexLogic™ operand serving as a trip switch has operated. This indicator always
latches; as such, a reset command must be initiated to allow the latch to be reset.
• ALARM: This LED indicates that the FlexLogic™ operand serving as an alarm switch has operated. This indicator is
never latched.
• PICKUP: This LED indicates that an element is picked up. This indicator is never latched.
The event cause indicators in the first column are described below.
Events cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched”. If a protection element target setting is “Enabled”, then the corresponding event cause LEDs
remain on as long as operate operand associated with the element remains asserted. If a protection element target setting
is “Latched”, then the corresponding event cause LEDs turn on when the operate operand associated with the element is
asserted and remain on until the RESET button on the front panel is pressed after the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, etc. This means that the phase A, B, and C operate oper-
ands for individual protection elements are ORed to turn on or off the phase A, B or C LEDs.
• VOLTAGE: This LED indicates voltage was involved. 4
• CURRENT: This LED indicates current was involved.
• FREQUENCY: This LED indicates frequency was involved.
• OTHER: This LED indicates a composite function was involved.
• PHASE A: This LED indicates phase A was involved.
• PHASE B: This LED indicates phase B was involved.
• PHASE C: This LED indicates phase C was involved.
• NEUTRAL/GROUND: This LED indicates that neutral or ground was involved.
The user-programmable LEDs consist of 48 amber LED indicators in four columns. The operation of these LEDs is user-
defined. Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack-
age of every G60, together with custom templates. The default labels can be replaced by user-printed labels.
User customization of LED operation is of maximum benefit in installations where languages other than English are used to
communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
b) STANDARD FACEPLATE
The standard faceplate consists of three panels with LED indicators, keys, and a communications port. The RESET key is
used to reset any latched LED indicator or target message, once the condition has been cleared (these latched conditions
can also be reset via the SETTINGS ÖØ INPUT/OUTPUTS ÖØ RESETTING menu). The RS232 port is intended for connection
to a portable PC.
The USER keys are not used in this unit.
842781A1.CDR
STATUS INDICATORS:
• IN SERVICE: Indicates that control power is applied; all monitored inputs/outputs and internal systems are OK; the
relay has been programmed.
• TROUBLE: Indicates that the relay has detected an internal problem.
• TEST MODE: Indicates that the relay is in test mode.
• TRIP: Indicates that the selected FlexLogic™ operand serving as a Trip switch has operated. This indicator always
latches; the reset command must be initiated to allow the latch to be reset.
• ALARM: Indicates that the selected FlexLogic™ operand serving as an Alarm switch has operated. This indicator is
never latched.
• PICKUP: Indicates that an element is picked up. This indicator is never latched.
EVENT CAUSE INDICATORS:
Events cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched”. If a protection element target setting is “Enabled”, then the corresponding event cause LEDs
remain on as long as operate operand associated with the element remains asserted. If a protection element target setting
is “Latched”, then the corresponding event cause LEDs turn on when the operate operand associated with the element is
asserted and remain on until the RESET button on the front panel is pressed after the operand is reset.
4 All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, etc. This means that the phase A, B, and C operate oper-
ands for individual protection elements are ORed to turn on or off the phase A, B or C LEDs.
• VOLTAGE: Indicates voltage was involved.
• CURRENT: Indicates current was involved.
• FREQUENCY: Indicates frequency was involved.
• OTHER: Indicates a composite function was involved.
• PHASE A: Indicates phase A was involved.
• PHASE B: Indicates phase B was involved.
• PHASE C: Indicates phase C was involved.
• NEUTRAL/GROUND: Indicates that neutral or ground was involved.
USER-PROGRAMMABLE INDICATORS:
The second and third provide 48 amber LED indicators whose operation is controlled by the user. Support for applying a
customized label beside every LED is provided.
User customization of LED operation is of maximum benefit in installations where languages other than English are used to
communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.
842782A1.CDR
4
842785A1.CDR
a) ENHANCED FACEPLATE
The following procedure requires the pre-requisites listed below.
• EnerVista UR Setup software is installed and operational.
• The G60 settings have been saved to a settings file.
• The G60 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http://
www.GEindustrial.com/multilin/support/ur and printed.
• Small-bladed knife.
This procedure describes how to create custom LED labels for the enhanced front panel display.
1. Start the EnerVista UR Setup software.
2. Select the Front Panel Report item at the bottom of the menu tree for the settings file. The front panel report window
will be displayed.
4
Figure 4–22: FRONT PANEL REPORT WINDOW
3. Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided.
4. Feed the G60 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
5. When printing is complete, fold the sheet along the perforated lines and punch out the labels.
6. Remove the G60 label insert tool from the package and bend the tabs as described in the following procedures. These
tabs will be used for removal of the default and custom LED labels.
It is important that the tool be used EXACTLY as shown below, with the printed side containing the GE part
number facing the user.
NOTE
The label package shipped with every G60 contains the three default labels shown below, the custom label template sheet,
and the label removal tool.
If the default labels are suitable for your application, insert them in the appropriate slots and program the LEDs to match
them. If you require custom labels, follow the procedures below to remove the original labels and insert the new ones.
The following procedure describes how to setup and use the label removal tool.
1. Bend the tabs at the left end of the tool upwards as shown below.
2. Bend the tab at the center of the tool tail as shown below.
The following procedure describes how to remove the LED labels from the G60 enhanced front panel and insert the custom
labels.
1. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from
the relay.
4
2. Slide the label tool under the LED label until the tabs snap out as shown below. This will attach the label tool to the LED
label.
4. Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below.
The following procedure describes how to remove the user-programmable pushbutton labels from the G60 enhanced front
panel and insert the custom labels.
1. Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown below. Make sure the
bent tab is pointing away from the relay.
2. Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This will
attach the label tool to the user-programmable pushbutton label.
3. Remove the tool and attached user-programmable pushbutton label as shown below.
4
4. Slide the new user-programmable pushbutton label inside the pocket until the text is properly aligned with the buttons,
as shown below.
b) STANDARD FACEPLATE
Custom labeling of an LED-only panel is facilitated through a Microsoft Word file available from the following URL:
http://www.GEindustrial.com/multilin/support/ur/
This file provides templates and instructions for creating appropriate labeling for the LED panel. The following procedures
are contained in the downloadable file. The panel templates provide relative LED locations and located example text (x)
edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling.
1. Remove the clear Lexan Front Cover (GE Multilin part number: 1501-0014).
Push in
and gently lift
up the cover.
842771A1.CDR
2. Pop out the LED module and/or the blank module with a screwdriver as shown below. Be careful not to damage the
plastic covers.
F60
R
842722A1.CDR
3. Place the left side of the customized module back to the front panel frame, then snap back the right side.
4. Put the clear Lexan front cover back into place.
The following items are required to customize the G60 display module:
• Black and white or color printer (color preferred).
• Microsoft Word 97 or later software for editing the template.
• 1 each of: 8.5" x 11" white paper, exacto knife, ruler, custom display module (GE Multilin Part Number: 1516-0069),
and a custom module cover (GE Multilin Part Number: 1502-0015).
The following procedure describes how to customize the G60 display module:
1. Open the LED panel customization template with Microsoft Word. Add text in places of the LED x text placeholders on
the template(s). Delete unused place holders as required.
2. When complete, save the Word file to your local PC for future use.
3. Print the template(s) to a local printer.
4. From the printout, cut-out the Background Template from the three windows, using the cropmarks as a guide.
5. Put the Background Template on top of the custom display module (GE Multilin Part Number: 1513-0069) and snap the
clear custom module cover (GE Multilin Part Number: 1502-0015) over it and the templates.
4.3.4 DISPLAY
All messages are displayed on a 2 × 20 backlit liquid crystal display (LCD) to make them visible under poor lighting condi-
4
tions. Messages are descriptive and should not require the aid of an instruction manual for deciphering. While the keypad
and display are not actively being used, the display will default to user-defined messages. Any high priority event driven
message will automatically override the default message and appear on the display.
4.3.5 KEYPAD
Display messages are organized into pages under the following headings: actual values, settings, commands, and targets.
The MENU key navigates through these pages. Each heading page is broken down further into logical subgroups.
The MESSAGE keys navigate through the subgroups. The VALUE keys scroll increment or decrement numerical setting
values when in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alterna-
tively, values may also be entered with the numeric keypad.
The decimal key initiates and advance to the next character in text edit mode or enters a decimal point. The HELP key may
be pressed at any time for context sensitive help messages. The ENTER key stores altered setting values.
a) INTRODUCTION
The G60 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker,
which can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually
initiated from faceplate keypad or automatically initiated from a FlexLogic™ operand. A setting is provided to assign names
to each breaker; this user-assigned name is used for the display of related flash messages. These features are provided for
two breakers; the user may use only those portions of the design relevant to a single breaker, which must be breaker 1.
For the following discussion it is assumed the SETTINGS ÖØ SYSTEM SETUP ÖØ BREAKERS Ö BREAKER 1(2) Ö BREAKER
FUNCTION setting is "Enabled" for each breaker.
ENTER COMMAND This message appears when the USER 1, USER 2, or USER 3 key is pressed and a
PASSWORD COMMAND PASSWORD is required; i.e. if COMMAND PASSWORD is enabled and no com-
mands have been issued within the last 30 minutes.
Press USER 1 This message appears if the correct password is entered or if none is required. This mes-
To Select Breaker sage will be maintained for 30 seconds or until the USER 1 key is pressed again.
BKR1-(Name) SELECTED This message is displayed after the USER 1 key is pressed for the second time. Three
4 USER 2=CLS/USER 3=OP possible actions can be performed from this state within 30 seconds as per items (1), (2)
and (3) below:
(1)
USER 2 OFF/ON If the USER 2 key is pressed, this message appears for 20 seconds. If the USER 2 key is
To Close BKR1-(Name) pressed again within that time, a signal is created that can be programmed to operate an
output relay to close breaker 1.
(2)
USER 3 OFF/ON If the USER 3 key is pressed, this message appears for 20 seconds. If the USER 3 key is
To Open BKR1-(Name) pressed again within that time, a signal is created that can be programmed to operate an
output relay to open breaker 1.
(3)
BKR2-(Name) SELECTED If the USER 1 key is pressed at this step, this message appears showing that a different
USER 2=CLS/USER 3=OP breaker is selected. Three possible actions can be performed from this state as per (1),
(2) and (3). Repeatedly pressing the USER 1 key alternates between available breakers.
Pressing keys other than USER 1, 2 or 3 at any time aborts the breaker control function.
4.3.7 MENUS
a) NAVIGATION
Press the MENU key to select the desired header display page (top-level menu). The header title appears momentarily fol-
lowed by a header display page menu item. Each press of the MENU key advances through the following main heading
pages:
• Actual values.
• Settings.
• Commands.
• Targets.
• User displays (when enabled).
b) HIERARCHY
The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double
scroll bar characters (), while sub-header pages are indicated by single scroll bar characters (). The header display
pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE
UP and DOWN keys move within a group of headers, sub-headers, setting values, or actual values. Continually pressing
the MESSAGE RIGHT key from a header display displays specific information for the header category. Conversely, contin-
ually pressing the MESSAGE LEFT key from a setting value or actual value display returns to the header display.
SETTINGS
SYSTEM SETUP
Ø
SETTINGS Press the MESSAGE DOWN key to move to the next Settings page. This page con-
SYSTEM SETUP tains settings for System Setup. Repeatedly press the MESSAGE UP and DOWN
keys to display the other setting headers and then back to the first Settings page
header.
Ø
PASSWORD From the Settings page one header (Product Setup), press the MESSAGE RIGHT
SECURITY key once to display the first sub-header (Password Security).
Ø
ACCESS LEVEL: Press the MESSAGE RIGHT key once more and this will display the first setting for
Restricted Password Security. Pressing the MESSAGE DOWN key repeatedly will display the
Ø remaining setting messages for this sub-header.
PASSWORD Press the MESSAGE LEFT key once to move back to the first sub-header message.
SECURITY
Ø
DISPLAY Pressing the MESSAGE DOWN key will display the second setting sub-header asso-
PROPERTIES ciated with the Product Setup header.
Ø
FLASH MESSAGE Press the MESSAGE RIGHT key once more and this will display the first setting for
TIME: 1.0 s Display Properties.
Ø
DEFAULT MESSAGE To view the remaining settings associated with the Display Properties subheader,
INTENSITY: 25% repeatedly press the MESSAGE DOWN key. The last message appears as shown.
FLASH MESSAGE For example, select the SETTINGS Ö PRODUCT SETUP ÖØ DISPLAY PROPERTIES Ö FLASH
TIME: 1.0 s MESSAGE TIME setting.
Ø
MINIMUM: 0.5 Press the HELP key to view the minimum and maximum values. Press the HELP key
MAXIMUM: 10.0 again to view the next context sensitive help message.
Two methods of editing and storing a numerical setting value are available.
• 0 to 9 and decimal point: The relay numeric keypad works the same as that of any electronic calculator. A number is
entered one digit at a time. The leftmost digit is entered first and the rightmost digit is entered last. Pressing the MES-
SAGE LEFT key or pressing the ESCAPE key, returns the original value to the display.
• VALUE keys: The VALUE UP key increments the displayed value by the step value, up to the maximum value allowed.
4 While at the maximum value, pressing the VALUE UP key again will allow the setting selection to continue upward
from the minimum value. The VALUE DOWN key decrements the displayed value by the step value, down to the mini-
mum value. While at the minimum value, pressing the VALUE DOWN key again will allow the setting selection to con-
tinue downward from the maximum value.
FLASH MESSAGE As an example, set the flash message time setting to 2.5 seconds. Press the appropriate
TIME: 2.5 s numeric keys in the sequence “2 . 5". The display message will change as the digits are
Ø being entered.
NEW SETTING Until ENTER is pressed, editing changes are not registered by the relay. Therefore, press
HAS BEEN STORED ENTER to store the new value in memory. This flash message will momentarily appear
as confirmation of the storing process. Numerical values which contain decimal places
will be rounded-off if more decimal place digits are entered than specified by the step
value.
ACCESS LEVEL: For example, the selections available for ACCESS LEVEL are "Restricted", "Command",
Restricted "Setting", and "Factory Service".
Enumeration type values are changed using the VALUE keys. The VALUE UP key displays the next selection while the
VALUE DOWN key displays the previous selection.
ACCESS LEVEL: If the ACCESS LEVEL needs to be "Setting", press the VALUE keys until the proper selec-
Setting tion is displayed. Press HELP at any time for the context sensitive help messages.
Ø
NEW SETTING Changes are not registered by the relay until the ENTER key is pressed. Pressing
HAS BEEN STORED ENTER stores the new value in memory. This flash message momentarily appears as
confirmation of the storing process.
There are several places where text messages may be programmed to allow the relay to be customized for specific appli-
cations. One example is the Message Scratchpad. Use the following procedure to enter alphanumeric text messages.
For example: to enter the text, “Breaker #1”.
1. Press the decimal to enter text edit mode.
2. Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position.
3. Repeat step 2 for the remaining characters: r,e,a,k,e,r, ,#,1.
4. Press ENTER to store the text.
5. If you have any problem, press HELP to view context sensitive help. Flash messages will sequentially appear for sev-
eral seconds each. For the case of a text setting message, pressing HELP displays how to edit and store new values.
RELAY SETTINGS: When the relay is powered up, the Trouble LED will be on, the In Service LED off, and
Not Programmed this message displayed, indicating the relay is in the "Not Programmed" state and is safe-
guarding (output relays blocked) against the installation of a relay whose settings have
not been entered. This message remains until the relay is explicitly put in the "Pro-
grammed" state.
4
To change the RELAY SETTINGS: "Not Programmed" mode to "Programmed", proceed as follows:
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on the
display.
2. Press the MESSAGE RIGHT key until the PASSWORD SECURITY message appears on the display.
3. Press the MESSAGE DOWN key until the INSTALLATION message appears on the display.
4. Press the MESSAGE RIGHT key until the RELAY SETTINGS: Not Programmed message is displayed.
SETTINGS
Ø
SETTINGS PASSWORD
PRODUCT SETUP SECURITY
DISPLAY
PROPERTIES
↓
5. After the RELAY SETTINGS: Not Programmed message appears on the display, press the VALUE keys change the
selection to "Programmed".
6. Press the ENTER key.
7. When the "NEW SETTING HAS BEEN STORED" message appears, the relay will be in "Programmed" state and the
In Service LED will turn on.
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the faceplate RS232 connection. Remote access is defined as any access to settings or commands via any rear com-
munications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
To enter the initial setting (or command) password, proceed as follows:
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on the
display.
2. Press the MESSAGE RIGHT key until the ACCESS LEVEL message appears on the display.
3. Press the MESSAGE DOWN key until the CHANGE LOCAL PASSWORDS message appears on the display.
4. Press the MESSAGE RIGHT key until the CHANGE SETTING PASSWORD or CHANGE COMMAND PASSWORD message
appears on the display.
PASSWORD ACCESS LEVEL:
SECURITY Restricted
CHANGE LOCAL CHANGE COMMAND
PASSWORDS PASSWORD: No
CHANGE SETTING
4 PASSWORD: No
ENCRYPTED COMMAND
PASSWORD: ---------
ENCRYPTED SETTING
PASSWORD: ---------
5. After the CHANGE...PASSWORD message appears on the display, press the VALUE UP or DOWN key to change the
selection to “Yes”.
6. Press the ENTER key and the display will prompt you to ENTER NEW PASSWORD.
7. Type in a numerical password (up to 10 characters) and press the ENTER key.
8. When the VERIFY NEW PASSWORD is displayed, re-type in the same password and press ENTER.
CHANGE SETTING
PASSWORD: No
NEW PASSWORD
HAS BEEN STORED
9. When the NEW PASSWORD HAS BEEN STORED message appears, your new Setting (or Command) Password will be
active.
ting password has been entered via the any external communications interface three times within a 3-minute time span, the
REMOTE ACCESS DENIED FlexLogic™ operand will be set to “On” and the G60 will not allow settings or command access
via the any external communications interface for the next five minutes.
In the event that an incorrect Command or Setting password has been entered via the any external communications inter-
face three times within a three-minute time span, the REMOTE ACCESS DENIED FlexLogic™ operand will be set to “On” and
the G60 will not allow Settings or Command access via the any external communications interface for the next ten minutes.
The REMOTE ACCESS DENIED FlexLogic™ operand will be set to “Off” after the expiration of the ten-minute timeout.
SETTINGS SECURITY
See page 5-8.
PRODUCT SETUP
DISPLAY
See page 5-12.
PROPERTIES
CLEAR RELAY
See page 5-14.
RECORDS
COMMUNICATIONS
See page 5-15.
MODBUS USER MAP
See page 5-39.
REAL TIME
See page 5-40.
CLOCK
USER-PROGRAMMABLE
See page 5-41.
FAULT REPORT
OSCILLOGRAPHY
See page 5-42.
DATA LOGGER
See page 5-44.
5
USER-PROGRAMMABLE
See page 5-46.
LEDS
USER-PROGRAMMABLE
See page 5-49.
SELF TESTS
CONTROL
See page 5-49.
PUSHBUTTONS
USER-PROGRAMMABLE
See page 5-51.
PUSHBUTTONS
FLEX STATE
See page 5-56.
PARAMETERS
USER-DEFINABLE
See page 5-57.
DISPLAYS
DIRECT I/O
See page 5-59.
TELEPROTECTION
See page 5-67.
INSTALLATION
See page 5-67.
SETTINGS AC INPUTS
See page 5-70.
SYSTEM SETUP
POWER SYSTEM
See page 5-71.
SIGNAL SOURCES
See page 5-72.
BREAKERS
See page 5-75.
SWITCHES
See page 5-79.
FLEXCURVES
See page 5-82.
PHASOR MEASUREMENT
See page 5-89.
UNIT
SETTINGS FLEXLOGIC
See page 5-122.
FLEXLOGIC EQUATION EDITOR
FLEXLOGIC
See page 5-122.
TIMERS
FLEXELEMENTS
See page 5-123.
NON-VOLATILE
See page 5-127.
LATCHES
5 SETTING GROUP 2
↓
SETTING GROUP 6
DIGITAL COUNTERS
See page 5-239.
MONITORING ELEMENTS
See page 5-241.
In the design of UR relays, the term element is used to describe a feature that is based around a comparator. The compar-
ator is provided with an input (or set of inputs) that is tested against a programmed setting (or group of settings) to deter-
mine if the input is within the defined range that will set the output to logic 1, also referred to as setting the flag. A single
comparator may make multiple tests and provide multiple outputs; for example, the time overcurrent comparator sets a
pickup flag when the current input is above the setting and sets an operate flag when the input current has been at a level
above the pickup setting for the time specified by the time-current curve settings. All comparators use analog parameter
actual values as the input.
The exception to the above rule are the digital elements, which use logic states as inputs.
5 NOTE
Elements are arranged into two classes, grouped and control. Each element classed as a grouped element is provided with
six alternate sets of settings, in setting groups numbered 1 through 6. The performance of a grouped element is defined by
the setting group that is active at a given time. The performance of a control element is independent of the selected active
setting group.
The main characteristics of an element are shown on the element logic diagram. This includes the inputs, settings, fixed
logic, and the output operands generated (abbreviations used on scheme logic diagrams are defined in Appendix F).
Some settings for current and voltage elements are specified in per-unit (pu) calculated quantities:
pu quantity = (actual quantity) / (base quantity)
For current elements, the base quantity is the nominal secondary or primary current of the CT.
Where the current source is the sum of two CTs with different ratios, the base quantity will be the common secondary or pri-
mary current to which the sum is scaled (that is, normalized to the larger of the two rated CT inputs). For example, if CT1 =
300 / 5 A and CT2 = 100 / 5 A, then in order to sum these, CT2 is scaled to the CT1 ratio. In this case, the base quantity will
be 5 A secondary or 300 A primary.
For voltage elements the base quantity is the nominal primary voltage of the protected system which corresponds (based
on VT ratio and connection) to secondary VT voltage applied to the relay.
For example, on a system with a 13.8 kV nominal primary voltage and with 14400:120 V delta-connected VTs, the second-
ary nominal voltage (1 pu) would be:
13800
---------------- × 120 = 115 V (EQ 5.1)
14400
For wye-connected VTs, the secondary nominal voltage (1 pu) would be:
13800
---------------- × 120
---------- = 66.4 V (EQ 5.2)
14400 3
Many settings are common to most elements and are discussed below:
• FUNCTION setting: This setting programs the element to be operational when selected as “Enabled”. The factory
default is “Disabled”. Once programmed to “Enabled”, any element associated with the function becomes active and all
options become available.
• NAME setting: This setting is used to uniquely identify the element.
• SOURCE setting: This setting is used to select the parameter or set of parameters to be monitored.
• PICKUP setting: For simple elements, this setting is used to program the level of the measured parameter above or
below which the pickup state is established. In more complex elements, a set of settings may be provided to define the
range of the measured parameters which will cause the element to pickup.
• PICKUP DELAY setting: This setting sets a time-delay-on-pickup, or on-delay, for the duration between the pickup
and operate output states.
• RESET DELAY setting: This setting is used to set a time-delay-on-dropout, or off-delay, for the duration between the
Operate output state and the return to logic 0 after the input transits outside the defined pickup range.
• BLOCK setting: The default output operand state of all comparators is a logic 0 or “flag not set”. The comparator
remains in this default state until a logic 1 is asserted at the RUN input, allowing the test to be performed. If the RUN
input changes to logic 0 at any time, the comparator returns to the default state. The RUN input is used to supervise
the comparator. The BLOCK input is used as one of the inputs to RUN control.
• TARGET setting: This setting is used to define the operation of an element target message. When set to “Disabled”,
no target message or illumination of a faceplate LED indicator is issued upon operation of the element. When set to
“Self-Reset”, the target message and LED indication follow the operate state of the element, and self-resets once the
operate element condition clears. When set to “Latched”, the target message and LED indication will remain visible
after the element output returns to logic 0 until a RESET command is received by the relay.
• EVENTS setting: This setting is used to control whether the pickup, dropout or operate states are recorded by the
event recorder. When set to “Disabled”, element pickup, dropout or operate are not recorded as events. When set to
“Enabled”, events are created for:
5
(Element) PKP (pickup)
(Element) DPO (dropout)
(Element) OP (operate)
The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to
the dropout state (logic 0). This could happen when the element is in the operate state if the reset delay time is not 0.
a) BACKGROUND
The G60 may be used on systems with breaker-and-a-half or ring bus configurations. In these applications, each of the two
three-phase sets of individual phase currents (one associated with each breaker) can be used as an input to a breaker fail-
ure element. The sum of both breaker phase currents and 3I_0 residual currents may be required for the circuit relaying
and metering functions. For a three-winding transformer application, it may be required to calculate watts and vars for each
of three windings, using voltage from different sets of VTs. These requirements can be satisfied with a single UR, equipped
with sufficient CT and VT input channels, by selecting the parameter to measure. A mechanism is provided to specify the
AC parameter (or group of parameters) used as the input to protection/control comparators and some metering elements.
Selection of the parameter(s) to measure is partially performed by the design of a measuring element or protection/control
comparator by identifying the type of parameter (fundamental frequency phasor, harmonic phasor, symmetrical component,
total waveform RMS magnitude, phase-phase or phase-ground voltage, etc.) to measure. The user completes the process
by selecting the instrument transformer input channels to use and some of the parameters calculated from these channels.
The input parameters available include the summation of currents from multiple input channels. For the summed currents of
phase, 3I_0, and ground current, current from CTs with different ratios are adjusted to a single ratio before summation.
A mechanism called a source configures the routing of CT and VT input channels to measurement sub-systems. Sources,
in the context of UR series relays, refer to the logical grouping of current and voltage signals such that one source contains
all the signals required to measure the load or fault in a particular power apparatus. A given source may contain all or some
of the following signals: three-phase currents, single-phase ground current, three-phase voltages and an auxiliary voltage
from a single VT for checking for synchronism.
To illustrate the concept of sources, as applied to current inputs only, consider the breaker-and-a-half scheme below. In this
application, the current flows as shown by the arrows. Some current flows through the upper bus bar to some other location
or power equipment, and some current flows into transformer winding 1. The current into winding 1 is the phasor sum (or
difference) of the currents in CT1 and CT2 (whether the sum or difference is used depends on the relative polarity of the CT
connections). The same considerations apply to transformer winding 2. The protection elements require access to the net
current for transformer protection, but some elements may need access to the individual currents from CT1 and CT2.
Winding 1
current
Winding 1
UR-series
relay Power
transformer
Winding 2
CT3 CT4
827791A3.CDR
Banks are ordered sequentially from the block of lower-numbered channels to the block of higher-numbered channels, and
from the CT/VT module with the lowest slot position letter to the module with the highest slot position letter, as follows:
INCREASING SLOT POSITION LETTER -->
CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3
< bank 1 > < bank 3 > < bank 5 >
< bank 2 > < bank 4 > < bank 6 >
The UR platform allows for a maximum of three sets of three-phase voltages and six sets of three-phase currents. The
result of these restrictions leads to the maximum number of CT/VT modules in a chassis to three. The maximum number of
sources is six. A summary of CT/VT module configurations is shown below.
ITEM MAXIMUM NUMBER
CT/VT Module 2
CT Bank (3 phase channels, 1 ground channel) 8
VT Bank (3 phase channels, 1 auxiliary channel) 4
a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY
CHANGE LOCAL
MESSAGE See page 5–9.
PASSWORDS
ACCESS
MESSAGE See page 5–10.
SUPERVISION
DUAL PERMISSION
MESSAGE See page 5–11.
SECURITY ACCESS
PASSWORD ACCESS Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
Two levels of password security are provided via the ACCESS LEVEL setting: command and setting. The factory service level
is not available and intended for factory use only.
The following operations are under command password supervision:
• Changing the state of virtual inputs.
• Clearing the event records.
• Clearing the oscillography records.
5 • Changing the date and time.
• Clearing energy records.
• Clearing the data logger.
• Clearing the user-programmable pushbutton states.
The following operations are under setting password supervision:
• Changing any setting.
• Test mode operation.
The command and setting passwords are defaulted to “0” when the relay is shipped from the factory. When a password is
set to “0”, the password security feature is disabled.
The G60 supports password entry from a local or remote connection.
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear
communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the G60, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password must be used.
The PASSWORD ACCESS EVENTS settings allows recording of password access events in the event recorder.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command ses-
sions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic™ operands.
• ACCESS LOC SETG OFF: Asserted when local setting access is disabled.
• ACCESS LOC SETG ON: Asserted when local setting access is enabled.
• ACCESS LOC CMND OFF: Asserted when local command access is disabled.
• ACCESS LOC CMND ON: Asserted when local command access is enabled.
• ACCESS REM SETG OFF: Asserted when remote setting access is disabled.
• ACCESS REM SETG ON: Asserted when remote setting access is enabled.
• ACCESS REM CMND OFF: Asserted when remote command access is disabled.
• ACCESS REM CMND ON: Asserted when remote command access is enabled.
The appropriate events are also logged in the Event Recorder as well. The FlexLogic™ operands and events are updated
every five seconds.
A command or setting write operation is required to update the state of all the remote and local security operands
shown above.
NOTE
b) LOCAL PASSWORDS
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ CHANGE LOCAL PASSWORDS
Proper password codes are required to enable each access level. A password consists of 1 to 10 numerical characters.
5
When a CHANGE COMMAND PASSWORD or CHANGE SETTING PASSWORD setting is programmed to “Yes” via the front panel
interface, the following message sequence is invoked:
1. ENTER NEW PASSWORD: ____________.
2. VERIFY NEW PASSWORD: ____________.
3. NEW PASSWORD HAS BEEN STORED.
To gain write access to a “Restricted” setting, program the ACCESS LEVEL setting in the main security menu to “Setting” and
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access will be allowed. Accessibility automatically reverts to the “Restricted” level according
to the access level timeout setting values.
If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD.
If the setting and command passwords are identical, then this one password allows access to both com-
mands and settings.
NOTE
c) REMOTE PASSWORDS
The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the
Settings > Product Setup > Password Security menu item to open the remote password settings window.
Proper passwords are required to enable each command or setting level access. A command or setting password consists
of 1 to 10 numerical characters and are initially programmed to “0”. The following procedure describes how the set the com-
mand or setting password.
1. Enter the new password in the Enter New Password field.
2. Re-enter the password in the Confirm New Password field.
3. Click the Change button. This button will not be active until the new password matches the confirmation password.
4. If the original password is not “0”, then enter the original password in the Enter Password field and click the Send
Password to Device button.
5. The new password is accepted and a value is assigned to the ENCRYPTED PASSWORD item.
If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password
value.
d) ACCESS SUPERVISION
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ ACCESS SUPERVISION
The UNAUTHORIZED ACCESS operand is reset with the COMMANDS ÖØ CLEAR RECORDS ÖØ RESET UNAUTHORIZED
ALARMS command. Therefore, to apply this feature with security, the command level should be password-protected. The
operand does not generate events or targets.
If events or targets are required, the UNAUTHORIZED ACCESS operand can be assigned to a digital element programmed
with event logs or targets enabled.
The access level timeout settings are shown below.
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ ACCESS SUPERVISION Ö ACCESS LEVEL TIMEOUTS
These settings allow the user to specify the length of inactivity required before returning to the restricted access level. Note
that the access level will set as restricted if control power is cycled.
• COMMAND LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
• SETTING LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
The dual permission security access feature provides a mechanism for customers to prevent unauthorized or unintended
upload of settings to a relay through the local or remote interfaces interface.
The following settings are available through the local (front panel) interface only.
• LOCAL SETTING AUTH: This setting is used for local (front panel or RS232 interface) setting access supervision.
Valid values for the FlexLogic™ operands are either “On” (default) or any physical “Contact Input ~~ On” value.
If this setting is “On“, then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing
the local setting password to gain setting access.
If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the UNAUTHORIZED ACCESS message is displayed on the front panel.
• REMOTE SETTING AUTH: This setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to pro-
viding the remote setting password to gain setting access.
• ACCESS AUTH TIMEOUT: This setting represents the timeout delay for local setting access. This setting is applicable
when the LOCAL SETTING AUTH setting is programmed to any operand except “On”. The state of the FlexLogic™ oper-
and is continuously monitored for an off-to-on transition. When this occurs, local access is permitted and the timer pro-
grammed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the time-
out is restarted. The status of this timer is updated every 5 seconds.
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product
Setup > Security menu item to display the security settings window.
The Remote Settings Authorization setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is pro-
vided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing the
remote setting password to gain setting access.
The Access Authorization Timeout setting represents the timeout delay remote setting access. This setting is applicable
when the Remote Settings Authorization setting is programmed to any operand except “On” or “Off”. The state of the
FlexLogic™ operand is continuously monitored for an off-to-on transition. When this occurs, remote setting access is per-
mitted and the timer programmed with the Access Authorization Timeout setting value is started. When this timer
expires, remote setting access is immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™
operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds.
Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
• LANGUAGE: This setting selects the language used to display settings, actual values, and targets. The range is
dependent on the order code of the relay.
• FLASH MESSAGE TIME: Flash messages are status, warning, error, or information messages displayed for several
seconds in response to certain key presses during setting programming. These messages override any normal mes-
sages. The duration of a flash message on the display can be changed to accommodate different reading rates.
• DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a
default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough
during programming or reading of actual values.
• DEFAULT MESSAGE INTENSITY: To extend phosphor life in the vacuum fluorescent display, the brightness can be
attenuated during default message display. During keypad interrogation, the display always operates at full brightness.
• SCREEN SAVER FEATURE and SCREEN SAVER WAIT TIME: These settings are only visible if the G60 has a liquid
crystal display (LCD) and control its backlighting. When the SCREEN SAVER FEATURE is “Enabled”, the LCD backlighting
is turned off after the DEFAULT MESSAGE TIMEOUT followed by the SCREEN SAVER WAIT TIME, providing that no keys
have been pressed and no target messages are active. When a keypress occurs or a target becomes active, the LCD
backlighting is turned on.
• CURRENT CUT-OFF LEVEL: This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the
rated value) are very susceptible to noise. Some customers prefer very low currents to display as zero, while others
prefer the current be displayed even when the value reflects noise rather than the actual signal. The G60 applies a cut-
off value to the magnitudes and angles of the measured currents. If the magnitude is below the cut-off level, it is substi-
tuted with zero. This applies to phase and ground current phasors as well as true RMS values and symmetrical compo-
nents. The cut-off operation applies to quantities used for metering, protection, and control, as well as those used by
communications protocols. Note that the cut-off level for the sensitive ground input is 10 times lower that the CURRENT
CUT-OFF LEVEL setting value. Raw current samples available via oscillography are not subject to cut-off.
• VOLTAGE CUT-OFF LEVEL: This setting modifies the voltage cut-off threshold. Very low secondary voltage measure-
ments (at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed
as zero, while others prefer the voltage to be displayed even when the value reflects noise rather than the actual sig-
nal. The G60 applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below
the cut-off level, it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical
components. The cut-off operation applies to quantities used for metering, protection, and control, as well as those
used by communications protocols. Raw samples of the voltages available via oscillography are not subject cut-off.
The CURRENT CUT-OFF LEVEL and the VOLTAGE CUT-OFF LEVEL are used to determine the metered power cut-off levels. The
power cut-off level is calculated as shown below. For Delta connections:
We have:
CT primary = “100 A”, and
VT primary = PHASE VT SECONDARY x PHASE VT RATIO = 66.4 V x 208 = 13811.2 V
The power cut-off is therefore:
power cut-off = (CURRENT CUT-OFF LEVEL × VOLTAGE CUT-OFF LEVEL × CT primary × VT primary)/VT secondary
= ( 3 × 0.02 pu × 1.0 V × 100 A × 13811.2 V) / 66.4 V
= 720.5 watts
Any calculated power value below this cut-off will not be displayed. As well, the three-phase energy data will not accumu-
late if the total power from all three phases does not exceed the power cut-off.
Lower the VOLTAGE CUT-OFF LEVEL and CURRENT CUT-OFF LEVEL with care as the relay accepts lower signals
as valid measurements. Unless dictated otherwise by a specific application, the default settings of “0.02
NOTE
pu” for CURRENT CUT-OFF LEVEL and “1.0 V” for VOLTAGE CUT-OFF LEVEL are recommended.
2. Set the properties for User-Programmable Pushbutton 1 by making the following changes in the SETTINGS Ö PRODUCT
SETUP ÖØ USER-PROGRAMMABLE PUSHBUTTONS Ö USER PUSHBUTTON 1 menu:
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.20 s”
5.2.4 COMMUNICATIONS
a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS
MESSAGE
IEC 60870-5-104
See page 5–36. 5
PROTOCOL
SNTP PROTOCOL
MESSAGE See page 5–37.
EGD PROTOCOL
MESSAGE See page 5–37.
ETHERNET SWITCH
MESSAGE See page 5–39.
b) SERIAL PORTS
The G60 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for
local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet
or RS485 port. The rear COM2 port be used for either RS485 or RRTD communications.
SERIAL PORTS RS485 COM1 BAUD Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
RATE: 19200 28800, 33600, 38400, 57600, 115200. Only
active if CPU Type E is ordered.
RS485 COM1 PARITY: Range: None, Odd, Even
MESSAGE Only active if CPU Type E is ordered
None
RS485 COM1 RESPONSE Range: 0 to 1000 ms in steps of 10
MESSAGE Only active if CPU Type E is ordered
MIN TIME: 0 ms
COM2 USAGE: Range: RS485, RRTD only, GPM-F only,
MESSAGE RRTD & GPM-F
RS485
RRTD SLAVE ADDRESS: Range: 1 to 254 in steps of 1. Shown only if the COM2
MESSAGE USAGE is “RRTD only” or “RRTD & GPM-F”.
254
RS485 COM2 BAUD Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
MESSAGE 28800, 33600, 38400, 57600, 115200. Shown
RATE: 19200
only if the COM2 USAGE is setting is “RS485”.
RRTD BAUD RATE: Range: 1200, 2400, 4800, 9600, 19200. Shown only if
MESSAGE the COM2 USAGE is setting is “RRTD”.
19200
RS485 COM2 PARITY: Range: None, Odd, Even.
MESSAGE
None
RS485 COM2 RESPONSE Range: 0 to 1000 ms in steps of 10
MESSAGE
MIN TIME: 0 ms
5 It is important that the baud rate and parity settings agree with the settings used on the computer or other equipment that is
connected to these ports.
The RS485 ports may be connected to a computer running EnerVista UR Setup. This software can download and upload
setting files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be daisy-chained
and connected to a DCS, PLC or PC using the RS485 ports.
The baud rate for standard RS485 communications can be selected as 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, or 115200 bps. If COM2 is used for both a field ground module (GPM-F) and remote RTD
unit (RRTD), then the RS482 COM2 BAUD RATE is fixed at 19200 bps.
For each RS485 port, the minimum time before the port will transmit after receiving data from a host can be
set. This feature allows operation with hosts which hold the RS485 transmitter active for some time after
NOTE
each transmission.
If the COM2 USAGE setting is “RRTD only”, then the COM2 port is used to monitor the RTDs on a remote RTD unit. The
remote RTD unit uses the Modbus RTU protocol over RS485. The RRTD device must have a unique address from 1 to
254. The baud rate for RRTD communications can be selected as 300, 1200, 2400, 4800, 9600, 14400, or 19200 bps.
If the RS485 COM2 port is used for an RRTD, GPM-F, or RRTD and GPM-F, then there must not be any other devices con-
nected in the daisy-chain for any other purpose. The port is strictly dedicated to RRTD or GPM-F usage when COM2 USAGE
is selected as “RRTD only”, “GPM-F only”, or “RRTD & GPM-F”.
The field ground module (GPM-F) has a fixed slave address of 1. Therefore, the RRTD SLAVE ADDRESS setting is appli-
cable only to the RRTD unit and has a setting rage of 2 to 254 if the COM2 USAGE is set as “RRTD & GPM-F”.
Power must be cycled to the G60 for changes to the COM2 USAGE setting to take effect.
NOTE
c) NETWORK
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK
These messages appear only if the G60 is ordered with an Ethernet card.
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, and HTTP protocols. The
NSAP address is used with the IEC 61850 protocol over the OSI (CLNP/TP4) stack only. Each network protocol has a set-
ting for the TCP/UDP port number. These settings are used only in advanced network configurations and should normally
be left at their default values, but may be changed if required (for example, to allow access to multiple UR-series relays
behind a router). By setting a different TCP/UDP PORT NUMBER for a given protocol on each UR-series relay, the router can
map the relays to the same external IP address. The client software (EnerVista UR Setup, for example) must be configured
to use the correct port number if these settings are used.
When the NSAP address, any TCP/UDP port number, or any user map setting (when used with DNP) is changed, it
will not become active until power to the relay has been cycled (off-on). 5
NOTE
Do not set more than one protocol to the same TCP/UDP PORT NUMBER, as this will result in unreliable opera-
tion of those protocols.
WARNING
d) MODBUS PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ MODBUS PROTOCOL
The serial communication ports utilize the Modbus protocol, unless configured for DNP or IEC 60870-5-104 operation (see
descriptions below). This allows the EnerVista UR Setup software to be used. The UR operates as a Modbus slave device
only. When using Modbus protocol on the RS232 port, the G60 will respond regardless of the MODBUS SLAVE ADDRESS pro-
grammed. For the RS485 ports each G60 must have a unique address from 1 to 254. Address 0 is the broadcast address
which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same
address or conflicts resulting in errors will occur. Generally, each device added to the link should use the next higher
address starting at 1. Refer to Appendix B for more information on the Modbus protocol.
Changes to the MODBUS TCP PORT NUMBER setting will not take effect until the G60 is restarted.
NOTE
e) DNP PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP PROTOCOL
The G60 supports the Distributed Network Protocol (DNP) version 3.0. The G60 can be used as a DNP slave device con-
nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the G60 maintains two sets of DNP
data change buffers and connection information, two DNP masters can actively communicate with the G60 at one time.
The IEC 60870-5-104 and DNP protocols cannot be simultaneously. When the IEC 60870-5-104 FUNCTION set-
ting is set to “Enabled”, the DNP protocol will not be operational. When this setting is changed it will not
NOTE
become active until power to the relay has been cycled (off-to-on).
The DNP Channels sub-menu is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP PROTOCOL Ö DNP CHANNELS
DNP CHANNELS DNP CHANNEL 1 PORT: Range: NONE, COM1 - RS485, COM2 - RS485,
NETWORK FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
DNP CHANNEL 2 PORT: Range: NONE, COM1 - RS485, COM2 - RS485,
MESSAGE FRONT PANEL - RS232, NETWORK - TCP,
COM2 - RS485
NETWORK - UDP
The DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings select the communications port assigned to the DNP protocol
for each channel. Once DNP is assigned to a serial port, the Modbus protocol is disabled on that port. Note that COM1 can
be used only in non-Ethernet UR relays. When this setting is set to “Network - TCP”, the DNP protocol can be used over
TCP/IP on channels 1 or 2. When this value is set to “Network - UDP”, the DNP protocol can be used over UDP/IP on chan-
nel 1 only. Refer to Appendix E for additional information on the DNP protocol.
Changes to the DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings will take effect only after power has
been cycled to the relay.
NOTE
The DNP NETWORK CLIENT ADDRESS settings can force the G60 to respond to a maximum of five specific DNP masters. The
settings in this sub-menu are shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP PROTOCOL Ö DNP NETWORK CLIENT ADDRESSES
The DNP UNSOL RESPONSE FUNCTION should be “Disabled” for RS485 applications since there is no collision avoidance
mechanism. The DNP UNSOL RESPONSE TIMEOUT sets the time the G60 waits for a DNP master to confirm an unsolicited
response. The DNP UNSOL RESPONSE MAX RETRIES setting determines the number of times the G60 retransmits an unsolic-
ited response without receiving confirmation from the master; a value of “255” allows infinite re-tries. The DNP UNSOL
RESPONSE DEST ADDRESS is the DNP address to which all unsolicited responses are sent. The IP address to which unsolic-
ited responses are sent is determined by the G60 from the current TCP connection or the most recent UDP message.
The DNP scale factor settings are numbers used to scale analog input point values. These settings group the G60 analog
input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the
scale factor for all analog input points of that type. For example, if the DNP VOLTAGE SCALE FACTOR setting is set to “1000”,
all DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000
5 V on the G60 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer-
tain ranges in DNP masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (that is, the value will be 10
times larger).
The DNP DEFAULT DEADBAND settings determine when to trigger unsolicited responses containing analog input data. These
settings group the G60 analog input data into the following types: current, voltage, power, energy, power factor, and other.
Each setting represents the default deadband value for all analog input points of that type. For example, to trigger unsolic-
ited responses from the G60 when any current values change by 15 A, the DNP CURRENT DEFAULT DEADBAND setting
should be set to “15”. Note that these settings are the deadband default values. DNP object 34 points can be used to
change deadband values, from the default, for each individual DNP analog input point. Whenever power is removed and
re-applied to the G60, the default deadbands will be in effect.
The DNP TIME SYNC IIN PERIOD setting determines how often the Need Time Internal Indication (IIN) bit is set by the G60.
Changing this time allows the DNP master to send time synchronization commands more or less often, as required.
The DNP MESSAGE FRAGMENT SIZE setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to be
necessary which can provide for more robust data transfer over noisy communication channels.
When the DNP data points (analog inputs and/or binary inputs) are configured for Ethernet-enabled relays,
check the “DNP Points Lists” G60 web page to view the points lists. This page can be viewed with a web
NOTE
browser by entering the G60 IP address to access the G60 “Main Menu”, then by selecting the “Device
Information Menu” > “DNP Points Lists” menu item.
The DNP OBJECT 1 DEFAULT VARIATION to DNP OBJECT 32 DEFAULT VARIATION settings allow the user to select the DNP
default variation number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation
response when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Refer to the DNP implementation section in
appendix E for additional details.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the G60 relay, DNP binary outputs are mapped to virtual inputs. However,
some legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to sup-
port the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the
DNP master can operate a single point for both trip and close, or raise and lower, operations. The G60 can be configured to
support paired control points, with each paired control point operating two virtual inputs. The DNP NUMBER OF PAIRED CON-
TROL POINTS setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired oper-
ate on a one-to-one basis.
The DNP ADDRESS setting is the DNP slave address. This number identifies the G60 on a DNP communications link. Each
DNP slave should be assigned a unique address.
The DNP TCP CONNECTION TIMEOUT setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection will be
aborted by the G60. This frees up the connection to be re-used by a client.
Relay power must be re-cycled after changing the DNP TCP CONNECTION TIMEOUT setting for the changes to take
effect.
NOTE
The binary and analog inputs points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104 protocol, can
configured to a maximum of 256 points. The value for each point is user-programmable and can be configured by assigning
FlexLogic™ operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT LISTS Ö BINARY INPUT / MSP POINTS 5
BINARY INPUT / MSP Point: 0 Range: FlexLogic™ operand
POINTS Off
Point: 1 Range: FlexLogic™ operand
MESSAGE
Off
↓
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic™ operand. Refer to the Introduction to FlexLogic™ section in this chapter for the full
range of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT LISTS ÖØ ANALOG INPUT / MME POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP /
IEC 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point
NOTE are ignored.
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the G60 is restarted.
NOTE
The G60 Generator Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
The G60 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The G60 operates as an IEC 61850
server. The Remote inputs and outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
Ö TRANSMISSION
TRANSMISSION GENERAL
GSSE
MESSAGE
FIXED GOOSE
MESSAGE
CONFIGURABLE
MESSAGE
GOOSE
The DEFAULT GSSE/GOOSE UPDATE TIME sets the time between GSSE or GOOSE messages when there are no remote out-
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state heartbeat time interval.
The DEFAULT GSSE/GOOSE UPDATE TIME setting is applicable to GSSE, fixed G60 GOOSE, and configurable GOOSE.
The GSSE settings are shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
5
Ö TRANSMISSION ÖØ GSEE
GSSE GSSE FUNCTION: Range: Enabled, Disabled
Enabled
GSSE ID: Range: 65-character ASCII string
MESSAGE
GSSEOut
DESTINATION MAC: Range: standard MAC address
MESSAGE
000000000000
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The GSSE ID setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
string identifies the GSSE message to the receiving device. In G60 releases previous to 5.0x, this name string was repre-
sented by the RELAY NAME setting.
The details about each scheme are shown in the following table.
The configurable GOOSE feature is recommended for applications that require GOOSE data transfer between UR-series
IEDs and devices from other manufacturers. Fixed GOOSE is recommended for applications that require GOOSE data
transfer between UR-series IEDs.
IEC 61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the
successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact
match in terms of data structure, and that the GOOSE addresses and name strings match exactly. Manual configuration is
possible, but third-party substation configuration software may be used to automate the process. The EnerVista UR Setup
software can produce IEC 61850 ICD files and import IEC 61850 SCD files produced by a substation configurator (refer to
the IEC 61850 IED configuration section later in this appendix).
The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. The
general steps required for transmission configuration are:
1. Configure the transmission dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
The general steps required for reception configuration are:
1. Configure the reception dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status
value, its associated quality flags, and a floating point analog value.
The following procedure illustrates the transmission configuration.
1. Configure the transmission dataset by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION ÖØ
IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLE
GOOSE 1 ÖØ CONFIG GSE 1 DATASET ITEMS settings menu:
– Set ITEM 1 to “GGIO1.ST.Ind1.q” to indicate quality flags for GGIO1 status indication 1.
– Set ITEM 2 to “GGIO1.ST.Ind1.stVal” to indicate the status value for GGIO1 status indication 1.
– Set ITEM 3 to “MMXU1.MX.Hz.mag.f” to indicate the analog frequency magnitude for MMXU1 (the metered fre-
quency for SRC1).
The transmission dataset now contains a quality flag, a single point status Boolean value, and a floating point analog
value. The reception dataset on the receiving device must exactly match this structure.
2. Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION
ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGU-
RABLE GOOSE 1 settings menu:
– Set ITEM 1 to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.
– Set ITEM 2 to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.
– Set ITEM 3 to “GGIO3.MX.AnIn1.mag.f” to indicate the analog magnitude for GGIO3 analog input 1.
The reception dataset now contains a quality flag, a single point status Boolean value, and a floating point analog
value. This matches the transmission dataset configuration above.
2. Configure the GOOSE service settings by making the following changes in the INPUTS/OUTPUTS ÖØ REMOTE DEVICES
ÖØ REMOTE DEVICE 1 settings menu:
– Set REMOTE DEVICE 1 ID to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.
– Set REMOTE DEVICE 1 ETYPE APPID to match the ETHERTYPE application ID from the transmitting device. This is
“0” in the example above.
– Set the REMOTE DEVICE 1 DATASET value. This value represents the dataset number in use. Since we are using
configurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.
3. Configure the Boolean data by making the following changes in the INPUTS/OUTPUTS ÖØ REMOTE INPUTS ÖØ REMOTE
INPUT 1settings menu:
– Set REMOTE IN 1 DEVICE to “GOOSEOut_1”.
– Set REMOTE IN 1 ITEM to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point status
item to remote input 1.
4. Configure the analog data by making the following changes in the INPUTS/OUTPUTS ÖØ IEC 61850 GOOSE ANALOG
INPUTS settings menu:
– Set the IEC61850 GOOSE ANALOG INPUT 1 DEFAULT VALUE to “60.000”.
– Enter “Hz” for the IEC61850 GOOSE ANALOG INPUT 1 UNITS setting.
The GOOSE analog input 1 can now be used as a FlexAnalog™ value in a FlexElement™ or in other settings. The G60
must be rebooted (control power removed and re-applied) before these settings take effect.
The value of GOOSE analog input 1 in the receiving device will be determined by the MMXU1.MX.Hz.mag.f value in the
sending device. This MMXU value is determined by the source 1 frequency value and the MMXU Hz deadband setting of
the sending device.
Remote input 1 can now be used in FlexLogic™ equations or other settings. The G60 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
5 in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
For intercommunication between G60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages. All GOOSE messages transmitted by the
G60 (DNA/UserSt dataset and configurable datasets) use the IEC 61850 GOOSE messaging services (for example, VLAN
support).
Set the CONFIG GSE 1 FUNCTION function to “Disabled” when configuration changes are required. Once changes are
entered, return the CONFIG GSE 1 FUNCTION to “Enabled” and restart the unit for changes to take effect.
NOTE
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLE GOOSE 1(8) ÖØ CONFIG GSE 1(64) DATA ITEMS
CONFIG GSE 1 ITEM 1: Range: all valid MMS data item references for
DATASET ITEMS GGIO1.ST.Ind1.stVal transmitted data
ITEM 64: Range: all valid MMS data item references for
MESSAGE transmitted data
None
To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status indication and its associated qual-
ity flags, the following dataset items can be selected: “GGIO1.ST.Ind1.stVal” and “GGIO1.ST.Ind1.q”. The G60 will then cre-
ate a dataset containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic™
operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con-
taining the defined dataset.
The main reception menu is applicable to configurable GOOSE only and contains the configurable GOOSE dataset items
for reception:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
Ö RECEPTION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLE GOOSE 1(16) ÖØ CONFIG GSE 1(32) DATA ITEMS
CONFIG GSE 1 ITEM 1: Range: all valid MMS data item references for
DATASET ITEMS GGIO3.ST.Ind1.stVal transmitted data
ITEM 32: Range: all valid MMS data item references for
MESSAGE transmitted data
None
The configurable GOOSE settings allow the G60 to be configured to receive a number of different datasets within IEC
61850 GOOSE messages. Up to sixteen different configurable datasets can be configured for reception. This is useful for
intercommunication between G60 IEDs and devices from other manufacturers that support IEC 61850.
For intercommunication between G60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages.
To set up a G60 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the
following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and
“GGIO3.ST.Ind2.stVal”. The G60 will then create a dataset containing these two data items. The Boolean status values
from these data items can be utilized as remote input FlexLogic™ operands. First, the REMOTE DEVICE 1(16) DATASET setting 5
must be set to contain dataset “GOOSEIn 1” (that is, the first configurable dataset). Then REMOTE IN 1(16) ITEM settings
must be set to “Dataset Item 1” and “Dataset Item 2”. These remote input FlexLogic™ operands will then change state in
accordance with the status values of the data items in the configured dataset.
Double-point status values may be included in the GOOSE dataset. Received values are populated in the
GGIO3.ST.IndPos1.stVal and higher items.
Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non-
instantaneous) values can be transmitted. Received values are used to populate the GGIO3.MX.AnIn1 and higher items.
Received values are also available as FlexAnalog™ parameters (GOOSE analog In1 and up).
GGIO3.MX.AnIn1 to GGIO3.MX.AnIn32 can only be used once for all sixteen reception datasets.
NOTE
The main menu for the IEC 61850 server configuration is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ SERVER CONFIGURATION
The IED NAME and LD INST settings represent the MMS domain name (IEC 61850 logical device) where all IEC/MMS logical
nodes are located. Valid characters for these values are upper and lowercase letters, numbers, and the underscore (_)
character, and the first character in the string must be a letter. This conforms to the IEC 61850 standard. The LOCATION is a
variable string and can be composed of ASCII characters. This string appears within the PhyName of the LPHD node.
The IEC/MMS TCP PORT NUMBER setting allows the user to change the TCP port number for MMS connections. The INCLUDE
NON-IEC DATA setting determines whether or not the “UR” MMS domain will be available. This domain contains a large num-
ber of UR-series specific data items that are not available in the IEC 61850 logical nodes. This data does not follow the IEC
61850 naming conventions. For communications schemes that strictly follow the IEC 61850 standard, this setting should be
“Disabled”.
The SERVER SCANNING feature should be set to “Disabled” when IEC 61850 client/server functionality is not required. IEC
61850 has two modes of functionality: GOOSE/GSSE inter-device communication and client/server communication. If the
GOOSE/GSSE functionality is required without the IEC 61850 client server feature, then server scanning can be disabled
to increase CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta-
tus values in the G60. Clients will still be able to connect to the server (G60 relay), but most data values will not be updated.
This setting does not affect GOOSE/GSSE operation.
Changes to the IED NAME setting, LD INST setting, and GOOSE dataset will not take effect until the G60 is restarted.
NOTE
The main menu for the IEC 61850 logical node name prefixes is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL
ÖØ IEC 61850 LOGICAL NODE NAME PREFIXES
IEC 61850 LOGICAL PIOC LOGICAL NODE
NODE NAME PREFIXES NAME PREFIXES
5 PTOC LOGICAL NODE
MESSAGE
NAME PREFIXES
↓
The IEC 61850 logical node name prefix settings are used to create name prefixes to uniquely identify each logical node.
For example, the logical node “PTOC1” may have the name prefix “abc”. The full logical node name will then be
“abcMMXU1”. Valid characters for the logical node name prefixes are upper and lowercase letters, numbers, and the
underscore (_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard.
Changes to the logical node prefixes will not take effect until the G60 is restarted.
The main menu for the IEC 61850 MMXU deadbands is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ MMXU DEADBANDS
MMXU2 DEADBANDS
MESSAGE
MMXU3 DEADBANDS
MESSAGE
MMXU4 DEADBANDS
MESSAGE
The MMXU deadband settings represent the deadband values used to determine when the update the MMXU “mag” and
“cVal” values from the associated “instmag” and “instcVal” values. The “mag” and “cVal” values are used for the IEC 61850
buffered and unbuffered reports. These settings correspond to the associated “db” data items in the CF functional con-
straint of the MMXU logical node, as per the IEC 61850 standard. According to IEC 61850-7-3, the db value “shall repre-
sent the percentage of difference between the maximum and minimum in units of 0.001%”. Thus, it is important to know the
maximum value for each MMXU measured quantity, since this represents the 100.00% value for the deadband.
The minimum value for all quantities is 0; the maximum values are as follows:
• phase current: 46 × phase CT primary setting
• neutral current: 46 × ground CT primary setting
• voltage: 275 × VT ratio setting
• power (real, reactive, and apparent): 46 × phase CT primary setting × 275 × VT ratio setting
• frequency: 90 Hz
• power factor: 2
The GGIO1 status configuration points are shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ GGIO1 STATUS CONFIGURATION
The NUMBER OF STATUS POINTS IN GGIO1 setting specifies the number of “Ind” (single point status indications) that are
instantiated in the GGIO1 logical node. Changes to the NUMBER OF STATUS POINTS IN GGIO1 setting will not take effect until
the G60 is restarted.
The GGIO2 control configuration points are shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ GGIO2 CONTROL CONFIGURATION
Ö GGIO2 CF SPSCO 1(64)
GGIO2 CF SPCSO 1 GGIO2 CF SPCSO 1 Range: 0, 1, or 2
CTLMODEL: 1
The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0”
(status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the G60
virtual inputs.
GGIO4 ANALOG 1
MESSAGE
MEASURED VALUE
GGIO4 ANALOG 2
MESSAGE
MEASURED VALUE
GGIO4 ANALOG 3
MESSAGE
MEASURED VALUE
↓
GGIO4 ANALOG 32
MESSAGE
MEASURED VALUE
The NUMBER OF ANALOG POINTS setting determines how many analog data points will exist in GGIO4. When this value is
changed, the G60 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly
configured number of analog points.
The measured value settings for each of the 32 analog values are shown below.
PATH: SETTINGS Ö PRODUCT... ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ GGIO4 ANALOG CONFIGURATION
Ö GGIO4 ANALOG 1(32) MEASURED VALUE
5 GGIO4 ANALOG 1
MEASURED VALUE
ANALOG IN
Off
1 VALUE: Range: any FlexAnalog value
The GGIO5 logical node allows IEC 61850 client access to integer data values. This allows access to as many as 16
unsigned integer value points, associated timestamps, and quality flags. The method of configuration is similar to that of
GGIO1 (binary status values). The settings allow the selection of FlexInteger™ values for each GGIO5 integer value point.
It is intended that clients use GGIO5 to access generic integer values from the G60. Additional settings are provided to
allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger™ values to the
GGIO5 integer inputs. The following setting is available for all GGIO5 configuration points.
• GGIO5 UINT IN 1 VALUE: This setting selects the FlexInteger™ value to drive each GGIO5 integer status value
(GGIO5.ST.UIntIn1). This setting is stored as an 32-bit unsigned integer value.
The report control configuration settings are shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ REPORT CONTROL CONFIGURATION
5
Ö CONFIGURABLE REPORT 1 Ö REPORT 1 DATASET ITEMS
REPORT 1 ITEM 1: Range: all valid MMS data item references
DATASET ITEMS
To create the dataset for logical node LN, program the ITEM 1 to ITEM 64 settings to a value from the list of IEC 61850 data
attributes supported by the G60. Changes to the dataset will only take effect when the G60 is restarted. It is recommended
to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1,
GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.
The breaker configuration settings are shown below. Changes to these values will not take effect until the UR is restarted:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ XCBR CONFIGURATION
The CLEAR XCBR1 OpCnt setting represents the breaker operating counter. As breakers operate by opening and closing, the
XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result
in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1.
The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is
restarted:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ XSWI CONFIGURATION
MESSAGE
CLEAR XSWI24 OpCnt: Range: No, Yes 5
No
The CLEAR XSWI1 OpCnt setting represents the disconnect switch operating counter. As disconnect switches operate by
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they will not usually be forwarded by net-
work routers. However, GOOSE messages may be fowarded by routers if the router has been configured for VLAN
NOTE functionality.
The G60 contains an embedded web server and is capable of transferring web pages to a web browser such as Microsoft
Internet Explorer or Mozilla Firefox. This feature is available only if the G60 has the ethernet option installed. The web
pages are organized as a series of menus that can be accessed starting at the G60 “Main Menu”. Web pages are available
showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, etc. The web pages can be
accessed by connecting the UR and a computer to an ethernet network. The main menu will be displayed in the web
browser on the computer simply by entering the IP address of the G60 into the “Address” box on the web browser.
i) TFTP PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ TFTP PROTOCOL
The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the G60 over a network. The G60 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file
obtained from the G60 contains a list and description of all available files (event records, oscillography, etc.).
The G60 supports the IEC 60870-5-104 protocol. The G60 can be used as an IEC 60870-5-104 slave device connected to
a maximum of two masters (usually either an RTU or a SCADA master station). Since the G60 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the G60 at one time.
The IEC ------- DEFAULT THRESHOLD settings are used to determine when to trigger spontaneous responses containing
M_ME_NC_1 analog data. These settings group the G60 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the G60 when any current values change by 15 A, the IEC CURRENT DEFAULT THRESHOLD set-
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the G60, the default thresholds will be in effect.
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC 60870-5-104 FUNCTION
setting is set to “Enabled”, the DNP protocol will not be operational. When this setting is changed it will not
NOTE
become active until power to the relay has been cycled (off-to-on).
k) SNTP PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ SNTP PROTOCOL
The G60 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the G60 can obtain clock time
over an Ethernet network. The G60 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a ded-
icated product using a GPS receiver to provide an accurate time. Both unicast and broadcast SNTP are supported.
If SNTP functionality is enabled at the same time as IRIG-B, the IRIG-B signal provides the time value to the G60 clock for
as long as a valid signal is present. If the IRIG-B signal is removed, the time obtained from the SNTP server is used. If
either SNTP or IRIG-B is enabled, the G60 clock value cannot be changed using the front panel keypad.
To use SNTP in unicast mode, SNTP SERVER IP ADDR must be set to the SNTP/NTP server IP address. Once this address is
set and SNTP FUNCTION is “Enabled”, the G60 attempts to obtain time values from the SNTP/NTP server. Since many time
values are obtained and averaged, it generally takes three to four minutes until the G60 clock is closely synchronized with
the SNTP/NTP server. It may take up to two minutes for the G60 to signal an SNTP self-test error if the server is offline.
To use SNTP in broadcast mode, set the SNTP SERVER IP ADDR setting to “0.0.0.0” and SNTP FUNCTION to “Enabled”. The
G60 then listens to SNTP messages sent to the “all ones” broadcast address for the subnet. The G60 waits up to eighteen
minutes (>1024 seconds) without receiving an SNTP broadcast message before signaling an SNTP self-test error.
The UR-series relays do not support the multicast or anycast SNTP functionality. 5
l) EGD PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ EGD PROTOCOL
The G60 Generator Protection System is provided with optional Ethernet Global Data (EGD) communica-
tions capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering
section of chapter 2 for additional details. The Ethernet Global Data (EGD) protocol feature is not available
if CPU Type E is ordered.
The relay supports one fast Ethernet Global Data (EGD) exchange and two slow EGD exchanges. There are 20 data items
in the fast-produced EGD exchange and 50 data items in each slow-produced exchange.
Ethernet Global Data (EGD) is a suite of protocols used for the real-time transfer of data for display and control purposes.
The relay can be configured to ‘produce’ EGD data exchanges, and other devices can be configured to ‘consume’ EGD
data exchanges. The number of produced exchanges (up to three), the data items in each exchange (up to 50), and the
exchange production rate can be configured.
EGD cannot be used to transfer data between UR-series relays. The relay supports EGD production only. An EGD
exchange will not be transmitted unless the destination address is non-zero, and at least the first data item address is set to
a valid Modbus register address. Note that the default setting value of “0” is considered invalid.
The settings menu for the fast EGD exchange is shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ EGD PROTOCOL Ö FAST PROD EXCH 1 CONFIGURATION
Fast exchanges (50 to 1000 ms) are generally used in control schemes. The G60 has one fast exchange (exchange 1) and
two slow exchanges (exchange 2 and 3).
5 The settings menu for the slow EGD exchanges is shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ EGD PROTOCOL Ö SLOW PROD EXCH 1(2) CONFIGURATION
Slow EGD exchanges (500 to 1000 ms) are generally used for the transfer and display of data items. The settings for the
fast and slow exchanges are described below:
• EXCH 1 DESTINATION: This setting specifies the destination IP address of the produced EGD exchange. This is usu-
ally unicast or broadcast.
• EXCH 1 DATA RATE: This setting specifies the rate at which this EGD exchange is transmitted. If the setting is 50 ms,
the exchange data will be updated and sent once every 50 ms. If the setting is 1000 ms, the exchange data will be
updated and sent once per second. EGD exchange 1 has a setting range of 50 to 1000 ms. Exchanges 2 and 3 have a
setting range of 500 to 1000 ms.
• EXCH 1 DATA ITEM 1 to 20/50: These settings specify the data items that are part of this EGD exchange. Almost any
data from the G60 memory map can be configured to be included in an EGD exchange. The settings are the starting
Modbus register address for the data item in decimal format. Refer to Appendix B for the complete Modbus memory
map. Note that the Modbus memory map displays shows addresses in hexadecimal format. as such, it will be neces-
sary to convert these values to decimal format before entering them as values for these setpoints.
To select a data item to be part of an exchange, it is only necessary to choose the starting Modbus address of the item.
That is, for items occupying more than one Modbus register (for example, 32 bit integers and floating point values),
only the first Modbus address is required. The EGD exchange configured with these settings contains the data items
up to the first setting that contains a Modbus address with no data, or 0. That is, if the first three settings contain valid
Modbus addresses and the fourth is 0, the produced EGD exchange will contain three data items.
m) ETHERNET SWITCH
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ ETHERNET SWITCH
These settings appear only if the G60 is ordered with an Ethernet switch module (type 2S or 2T).
The IP address and Modbus TCP port number for the Ethernet switch module are specified in this menu. These settings
are used in advanced network configurations. Please consult the network administrator before making changes to these
settings. The client software (EnerVista UR Setup, for example) is the preferred interface to configure these settings.
The PORT 1 EVENTS through PORT 6 EVENTS settings allow Ethernet switch module events to be logged in the event
recorder.
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the ADDRESS line (this value must be converted from hex to decimal format). The corresponding value is dis-
played in the VALUE line. A value of “0” in subsequent register ADDRESS lines automatically returns values for the previous
ADDRESS lines incremented by “1”. An address value of “0” in the initial register means “none” and values of “0” will be dis-
played for all registers. Different ADDRESS values can be entered as required in any of the register positions.
REAL TIME IRIG-B SIGNAL TYPE: Range: None, DC Shift, Amplitude Modulated
CLOCK None
REAL TIME CLOCK Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
LOCAL TIME OFFSET Range: –24.0 to 24.0 hrs in steps of 0.5
MESSAGE
FROM UTC: 0.0 hrs
DAYLIGHT SAVINGS Range: Disabled, Enabled
MESSAGE
TIME: Disabled
DST START MONTH: Range: January to December (all months)
MESSAGE
April
DST START DAY: Range: Sunday to Saturday (all days of the week)
MESSAGE
Sunday
DST START DAY Range: First, Second, Third, Fourth, Last
MESSAGE
INSTANCE: First
DST START HOUR: Range: 0:00 to 23:00
MESSAGE
2:00
DST STOP MONTH: Range: January to December (all months)
5 MESSAGE
April
DST STOP DAY: Range: Sunday to Saturday (all days of the week)
MESSAGE
Sunday
DST STOP DAY Range: First, Second, Third, Fourth, Last
MESSAGE
INSTANCE: First
DST STOP HOUR: Range: 0:00 to 23:00
MESSAGE
2:00
The date and time can be synchronized a known time base and to other relays using an IRIG-B signal. It has the same
accuracy as an electronic watch, approximately ±1 minute per month. If an IRIG-B signal is connected to the relay, only the
current year needs to be entered. See the COMMANDS ÖØ SET DATE AND TIME menu to manually set the relay clock.
The REAL TIME CLOCK EVENTS setting allows changes to the date and/or time to be captured in the event record.
The LOCAL TIME OFFSET FROM UTC setting is used to specify the local time zone offset from Universal Coordinated Time
(Greenwich Mean Time) in hours. This setting has two uses. When the G60 is time synchronized with IRIG-B, or has no
permanent time synchronization, the offset is used to calculate UTC time for IEC 61850 features. When the G60 is time
synchronized with SNTP, the offset is used to determine the local time for the G60 clock, since SNTP provides UTC time.
The daylight savings time (DST) settings can be used to allow the G60 clock can follow the DST rules of the local time
zone. Note that when IRIG-B time synchronization is active, the DST settings are ignored. The DST settings are used when
the G60 is synchronized with SNTP, or when neither SNTP nor IRIG-B is used.
Only timestamps in the event recorder and communications protocols are affected by the daylight savings time set-
tings. The reported real-time clock value does not change.
NOTE
PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE FAULT REPORT Ö USER-PROGRAMMABLE FAULT REPORT 1(2)
FAULT REPORT 1 #32: Range: Off, any actual value analog parameter
MESSAGE
Off
When enabled, this function monitors the pre-fault trigger. The pre-fault data are stored in the memory for prospective cre-
ation of the fault report on the rising edge of the pre-fault trigger. The element waits for the fault trigger as long as the pre-
fault trigger is asserted, but not shorter than 1 second. When the fault trigger occurs, the fault data is stored and the com- 5
plete report is created. If the fault trigger does not occur within 1 second after the pre-fault trigger drops out, the element
resets and no record is created.
The user programmable record contains the following information: the user-programmed relay name, detailed firmware
revision (5.9x, for example) and relay model (G60), the date and time of trigger, the name of pre-fault trigger (a specific
FlexLogic™ operand), the name of fault trigger (a specific FlexLogic™ operand), the active setting group at pre-fault trig-
ger, the active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault
trigger), and fault values of all programmed analog channels (at the fault trigger).
Each fault report is stored as a file to a maximum capacity of ten files. An eleventh trigger overwrites the oldest file. The
EnerVista UR Setup software is required to view all captured data. A FAULT RPT TRIG event is automatically created when
the report is triggered.
The relay includes two user-programmable fault reports to enable capture of two types of trips (for example, trip from ther-
mal protection with the report configured to include temperatures, and short-circuit trip with the report configured to include
voltages and currents). Both reports feed the same report file queue.
The last record is available as individual data items via communications protocols.
• PRE-FAULT 1 TRIGGER: Specifies the FlexLogic™ operand to capture the pre-fault data. The rising edge of this
operand stores one cycle-old data for subsequent reporting. The element waits for the fault trigger to actually create a
record as long as the operand selected as PRE-FAULT 1 TRIGGER is “On”. If the operand remains “Off” for 1 second, the
element resets and no record is created.
• FAULT 1 TRIGGER: Specifies the FlexLogic™ operand to capture the fault data. The rising edge of this operand
stores the data as fault data and results in a new report. The trigger (not the pre-fault trigger) controls the date and time
of the report.
• FAULT REPORT 1 #1 to FAULT REPORT 1 #32: These settings specify an actual value such as voltage or current
magnitude, true RMS, phase angle, frequency, temperature, etc., to be stored should the report be created. Up to 32
channels can be configured. Two reports are configurable to cope with variety of trip conditions and items of interest.
5.2.8 OSCILLOGRAPHY
a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ OSCILLOGRAPHY
Oscillography records contain waveforms captured at the sampling rate as well as other relay data at the point of trigger.
Oscillography records are triggered by a programmable FlexLogic™ operand. Multiple oscillography records may be cap-
5 tured simultaneously.
The NUMBER OF RECORDS is selectable, but the number of cycles captured in a single record varies considerably based on
other factors such as sample rate and the number of operational modules. There is a fixed amount of data storage for oscil-
lography; the more data captured, the less the number of cycles captured per record. See the ACTUAL VALUES ÖØ
RECORDS ÖØ OSCILLOGRAPHY menu to view the number of cycles captured per record. The following table provides sam-
ple configurations with corresponding cycles/record.
A new record may automatically overwrite an older record if TRIGGER MODE is set to “Automatic Overwrite”.
Set the TRIGGER POSITION to a percentage of the total buffer size (for example, 10%, 50%, 75%, etc.). A trigger position of
25% consists of 25% pre- and 75% post-trigger data. The TRIGGER SOURCE is always captured in oscillography and may be
any FlexLogic™ parameter (element state, contact input, virtual output, etc.). The relay sampling rate is 64 samples per
cycle.
The AC INPUT WAVEFORMS setting determines the sampling rate at which AC input signals (that is, current and voltage) are
stored. Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling
rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device.
When changes are made to the oscillography settings, all existing oscillography records will be CLEARED.
WARNING
b) DIGITAL CHANNELS
PATH: SETTINGS Ö PRODUCT SETUP ÖØ OSCILLOGRAPHY ÖØ DIGITAL CHANNELS
A DIGITAL 1(63) CHANNEL setting selects the FlexLogic™ operand state recorded in an oscillography trace. The length of
each oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored.
Upon startup, the relay will automatically prepare the parameter list.
c) ANALOG CHANNELS
PATH: SETTINGS Ö PRODUCT SETUP ÖØ OSCILLOGRAPHY ÖØ ANALOG CHANNELS
These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace
depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. The parameters available
in a given relay are dependent on:
• The type of relay,
• The type and number of CT/VT hardware modules installed, and
• The type and number of analog input hardware modules installed.
Upon startup, the relay will automatically prepare the parameter list. A list of all possible analog metering actual value
parameters is presented in Appendix A: FlexAnalog parameters. The parameter index number shown in any of the tables is
used to expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list
of parameters via the relay keypad and display - entering this number via the relay keypad will cause the corresponding
parameter to be displayed.
All eight CT/VT module channels are stored in the oscillography file. The CT/VT module channels are named as follows:
<slot_letter><terminal_number>—<I or V><phase A, B, or C, or 4th input>
The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB desig-
nates the IB signal on terminal 2 of the CT/VT module in slot F.
If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will
appear.
The source harmonic indices appear as oscillography analog channels numbered from 0 to 23. These correspond
directly to the to the 2nd to 25th harmonics in the relay as follows:
NOTE
Analog channel 0 ↔ 2nd harmonic
Analog channel 1 ↔ 3rd harmonic
...
Analog channel 23 ↔ 25th harmonic
The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data may
be downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis.
All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. Exam-
ple storage capacities for a system frequency of 60 Hz are shown in the following table.
Changing any setting affecting data logger operation will clear any data that is currently in the log.
NOTE
• DATA LOGGER MODE: This setting configures the mode in which the data logger will operate. When set to “Continu-
ous”, the data logger will actively record any configured channels at the rate as defined by the DATA LOGGER RATE. The
5
data logger will be idle in this mode if no channels are configured. When set to “Trigger”, the data logger will begin to
record any configured channels at the instance of the rising edge of the DATA LOGGER TRIGGER source FlexLogic™
operand. The data logger will ignore all subsequent triggers and will continue to record data until the active record is
full. Once the data logger is full a CLEAR DATA LOGGER command is required to clear the data logger record before a
new record can be started. Performing the CLEAR DATA LOGGER command will also stop the current record and reset
the data logger to be ready for the next trigger.
• DATA LOGGER TRIGGER: This setting selects the signal used to trigger the start of a new data logger record. Any
FlexLogic™ operand can be used as the trigger source. The DATA LOGGER TRIGGER setting only applies when the
mode is set to “Trigger”.
• DATA LOGGER RATE: This setting selects the time interval at which the actual value data will be recorded.
• DATA LOGGER CHNL 1(16): This setting selects the metering actual value that is to be recorded in Channel 1(16) of
the data log. The parameters available in a given relay are dependent on: the type of relay, the type and number of CT/
VT hardware modules installed, and the type and number of Analog Input hardware modules installed. Upon startup,
the relay will automatically prepare the parameter list. A list of all possible analog metering actual value parameters is
shown in Appendix A: FlexAnalog Parameters. The parameter index number shown in any of the tables is used to
expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list of
parameters via the relay keypad/display – entering this number via the relay keypad will cause the corresponding
parameter to be displayed.
• DATA LOGGER CONFIG: This display presents the total amount of time the Data Logger can record the channels not
selected to “Off” without over-writing old data.
a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS
USER-PROGRAMMABLE
MESSAGE
LED48
b) LED TEST
PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS Ö LED TEST
When enabled, the LED test can be initiated from any digital input or user-programmable condition such as user-program-
mable pushbutton. The control operand is configured under the LED TEST CONTROL setting. The test covers all LEDs,
including the LEDs of the optional user-programmable pushbuttons.
The test consists of three stages.
1. All 62 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is “burned”. This stage lasts as
long as the control input is on, up to a maximum of 1 minute. After 1 minute, the test will end.
2. All the LEDs are turned off, and then one LED at a time turns on for 1 second, then back off. The test routine starts at
the top left panel, moving from the top to bottom of each LED column. This test checks for hardware failures that lead
to more than one LED being turned on from a single logic point. This stage can be interrupted at any time.
3. All the LEDs are turned on. One LED at a time turns off for 1 second, then back on. The test routine starts at the top left
panel moving from top to bottom of each column of the LEDs. This test checks for hardware failures that lead to more
than one LED being turned off from a single logic point. This stage can be interrupted at any time.
When testing is in progress, the LEDs are controlled by the test sequence, rather than the protection, control, and monitor-
ing features. However, the LED control mechanism accepts all the changes to LED states generated by the relay and
stores the actual LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting from
relay response during testing. The reset pushbutton will not clear any targets when the LED Test is in progress.
A dedicated FlexLogic™ operand, LED TEST IN PROGRESS, is set for the duration of the test. When the test sequence is ini-
tiated, the LED TEST INITIATED event is stored in the event recorder.
The entire test procedure is user-controlled. In particular, stage 1 can last as long as necessary, and stages 2 and 3 can be
interrupted. The test responds to the position and rising edges of the control input defined by the LED TEST CONTROL set-
ting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed.
READY TO TEST
Reset the
LED TEST IN PROGRESS
rising edge of the
operand
control input
Set the
LED TEST IN PROGRESS
operand
control input is on
STAGE 1 time-out
(all LEDs on) (1 minute)
842011A1.CDR
Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the SETTINGS Ö
PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS Ö LED TEST menu:
The test will be initiated when the user-programmable pushbutton 1 is pressed. The pushbutton should remain pressed for
as long as the LEDs are being visually inspected. When finished, the pushbutton should be released. The relay will then
automatically start stage 2. At this point forward, test may be aborted by pressing the pushbutton.
APPLICATION EXAMPLE 2:
Assume one needs to check if any LEDs are “burned” as well as exercise one LED at a time to check for other failures. This
is to be performed via user-programmable pushbutton 1.
After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. Next,
release the pushbutton to automatically start stage 2. Once stage 2 has started, the pushbutton can be released. When
stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton.
TRIP & ALARM LEDS TRIP LED INPUT: Range: FlexLogic™ operand
Off
ALARM LED INPUT: Range: FlexLogic™ operand
MESSAGE
Off
The trip and alarm LEDs are in the first LED column (enhanced faceplate) and on LED panel 1 (standard faceplate). Each
indicator can be programmed to become illuminated when the selected FlexLogic™ operand is in the logic 1 state.
There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-
nate when the selected FlexLogic™ operand is in the logic 1 state.
For the standard faceplate, the LEDs are located as follows.
• LED Panel 2: user-programmable LEDs 1 through 24
Refer to the Control of setting groups example in the Control elements section of this chapter for group activation.
USER-PROGRAMMABLE DIRECT RING BREAK Range: Disabled, Enabled. Valid for units equipped with
SELF TESTS FUNCTION: Enabled Direct Input/Output module.
DIRECT DEVICE OFF Range: Disabled, Enabled. Valid for units equipped with
MESSAGE Direct Input/Output module.
FUNCTION: Enabled
REMOTE DEVICE OFF Range: Disabled, Enabled. Valid for units that contain a
MESSAGE CPU with Ethernet capability.
FUNCTION: Enabled
PRI. ETHERNET FAIL Range: Disabled, Enabled. Valid for units that contain a
MESSAGE CPU with a primary fiber port.
FUNCTION: Disabled
SEC. ETHERNET FAIL Range: Disabled, Enabled. Valid for units that contain a
MESSAGE CPU with a redundant fiber port.
FUNCTION: Disabled
BATTERY FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Enabled
SNTP FAIL Range: Disabled, Enabled. Valid for units that contain a
MESSAGE CPU with Ethernet capability.
FUNCTION: Enabled
IRIG-B FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Enabled
Range: Disabled, Enabled.
5
ETHERNET SWITCH FAIL
MESSAGE
FUNCTION: Disabled
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the minor alarms can be disabled if desired.
When in the “Disabled” mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, or display
target messages. Moreover, they will not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in the “Enabled”
mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section in
chapter 7 for additional information on major and minor self-test alarms.
To enable the Ethernet switch failure function, ensure that the ETHERNET SWITCH FAIL FUNCTION is “Enabled” in this
menu.
NOTE
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
The location of the control pushbuttons are shown in the following figures.
Control pushbuttons
842813A1.CDR
USER 4
5 USER 6
USER 7
OPTIONAL
CONTROL
PUSHBUTTONS
842733A2.CDR
SETTING
CONTROL PUSHBUTTON
{
1 FUNCTION:
Enabled=1
SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL:
When applicable
AND RUN
Enabled=1
OFF TIMER
SYSTEM SETUP/ FLEXLOGIC OPERAND
BREAKERS/BREAKER 2/ ON 0 CONTROL PUSHBTN 1 ON
BREAKER 2 PUSHBUTTON 100 msec
CONTROL:
842010A2.CDR
Enabled=1
The optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method of enter-
ing digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered
with the relay.
• Type P faceplate: standard horizontal faceplate with 12 user-programmable pushbuttons.
• Type Q faceplate: enhanced horizontal faceplate with 16 user-programmable pushbuttons.
The digital state can be entered locally (by directly pressing the front panel pushbutton) or remotely (via FlexLogic™ oper-
ands) into FlexLogic™ equations, protection elements, and control elements. Typical applications include breaker control,
autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of
password protection.
The user-configurable pushbuttons for the enhanced faceplate are shown below.
USER USER USER USER USER USER USER USER USER USER USER USER USER USER USER USER
LABEL 1 LABEL 2 LABEL 3 LABEL 4 LABEL 5 LABEL 6 LABEL 7 LABEL 8 LABEL 9 LABEL 10 LABEL 11 LABEL 12 LABEL 13 LABEL 14 LABEL 15 LABEL 16
842814A1.CDR
1 3 5 7 9 11
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL
2 4 6 8 10 12
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL
842779A1.CDR
The pushbuttons can be automatically controlled by activating the operands assigned to the PUSHBTN 1 SET (for latched and
self-reset mode) and PUSHBTN 1 RESET (for latched mode only) settings. The pushbutton reset status is declared when the
PUSHBUTTON 1 OFF operand is asserted. The activation and deactivation of user-programmable pushbuttons is dependent
on whether latched or self-reset mode is programmed.
• Latched mode: In latched mode, a pushbutton can be set (activated) by asserting the operand assigned to the PUSH-
BTN 1 SET setting or by directly pressing the associated front panel pushbutton. The pushbutton maintains the set state
until deactivated by the reset command or after a user-specified time delay. The state of each pushbutton is stored in
non-volatile memory and maintained through a loss of control power.
The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the PUSHBTN 1 RESET set-
ting or by directly pressing the associated active front panel pushbutton.
It can also be programmed to reset automatically through the PUSHBTN 1 AUTORST and PUSHBTN 1 AUTORST DELAY set-
tings. These settings enable the autoreset timer and specify the associated time delay. The autoreset timer can be
used in select-before-operate (SBO) breaker control applications, where the command type (close/open) or breaker
location (feeder number) must be selected prior to command execution. The selection must reset automatically if con-
trol is not executed within a specified time period.
• Self-reset mode: In self-reset mode, a pushbutton will remain active for the time it is pressed (the pulse duration) plus
the dropout time specified in the PUSHBTN 1 DROP-OUT TIME setting. If the pushbutton is activated via FlexLogic™, the
pulse duration is specified by the PUSHBTN 1 DROP-OUT TIME only. The time the operand remains assigned to the PUSH-
BTN 1 SET setting has no effect on the pulse duration.
The pushbutton is reset (deactivated) in self-reset mode when the dropout delay specified in the PUSHBTN 1 DROP-OUT
TIMEsetting expires.
The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the push-
button. This allows the user-programmable pushbuttons to properly operate during power cycling events and vari-
NOTE ous system disturbances that may cause transient assertion of the operating signals.
The local and remote operation of each user-programmable pushbutton can be inhibited through the PUSHBTN 1 LOCAL and
PUSHBTN 1 REMOTE settings, respectively. If local locking is applied, the pushbutton will ignore set and reset commands
executed through the front panel pushbuttons. If remote locking is applied, the pushbutton will ignore set and reset com-
mands executed through FlexLogic™ operands.
The locking functions are not applied to the autorestart feature. In this case, the inhibit function can be used in SBO control
operations to prevent the pushbutton function from being activated and ensuring “one-at-a-time” select operation.
The locking functions can also be used to prevent the accidental pressing of the front panel pushbuttons. The separate
inhibit of the local and remote operation simplifies the implementation of local/remote control supervision.
Pushbutton states can be logged by the event recorder and displayed as target messages. In latched mode, user-defined
messages can also be associated with each pushbutton and displayed when the pushbutton is on or changing to off.
• PUSHBUTTON 1 FUNCTION: This setting selects the characteristic of the pushbutton. If set to “Disabled”, the push-
button is not active and the corresponding FlexLogic™ operands (both “On” and “Off”) are de-asserted. If set to “Self-
Reset”, the control logic is activated by the pulse (longer than 100 ms) issued when the pushbutton is being physically
pressed or virtually pressed via a FlexLogic™ operand assigned to the PUSHBTN 1 SET setting.
When in “Self-Reset” mode and activated locally, the pushbutton control logic asserts the “On” corresponding Flex-
Logic™ operand as long as the pushbutton is being physically pressed, and after being released the deactivation of
the operand is delayed by the drop out timer. The “Off” operand is asserted when the pushbutton element is deacti-
vated. If the pushbutton is activated remotely, the control logic of the pushbutton asserts the corresponding “On” Flex-
Logic™ operand only for the time period specified by the PUSHBTN 1 DROP-OUT TIME setting.
If set to “Latched”, the control logic alternates the state of the corresponding FlexLogic™ operand between “On” and
“Off” on each button press or by virtually activating the pushbutton (assigning set and reset operands). When in the
“Latched” mode, the states of the FlexLogic™ operands are stored in a non-volatile memory. Should the power supply
be lost, the correct state of the pushbutton is retained upon subsequent power up of the relay.
• PUSHBTN 1 ID TEXT: This setting specifies the top 20-character line of the user-programmable message and is 5
intended to provide ID information of the pushbutton. Refer to the User-definable displays section for instructions on
how to enter alphanumeric characters from the keypad.
• PUSHBTN 1 ON TEXT: This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is in the “on” position. Refer to the User-definable displays section for instructions on
entering alphanumeric characters from the keypad.
• PUSHBTN 1 OFF TEXT: This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is activated from the on to the off position and the PUSHBUTTON 1 FUNCTION is
“Latched”. This message is not displayed when the PUSHBUTTON 1 FUNCTION is “Self-reset” as the pushbutton operand
status is implied to be “Off” upon its release. The length of the “Off” message is configured with the PRODUCT SETUP
ÖØ DISPLAY PROPERTIES Ö FLASH MESSAGE TIME setting.
• PUSHBTN 1 HOLD: This setting specifies the time required for a pushbutton to be pressed before it is deemed active.
This timer is reset upon release of the pushbutton. Note that any pushbutton operation will require the pushbutton to be
pressed a minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer.
• PUSHBTN 1 SET: This setting assigns the FlexLogic™ operand serving to operate the pushbutton element and to
assert PUSHBUTTON 1 ON operand. The duration of the incoming set signal must be at least 100 ms.
• PUSHBTN 1 RESET: This setting assigns the FlexLogic™ operand serving to reset pushbutton element and to assert
PUSHBUTTON 1 OFF operand. This setting is applicable only if pushbutton is in latched mode. The duration of the
incoming reset signal must be at least 50 ms.
• PUSHBTN 1 AUTORST: This setting enables the user-programmable pushbutton autoreset feature. This setting is
applicable only if the pushbutton is in the “Latched” mode.
• PUSHBTN 1 AUTORST DELAY: This setting specifies the time delay for automatic reset of the pushbutton when in
the latched mode.
• PUSHBTN 1 REMOTE: This setting assigns the FlexLogic™ operand serving to inhibit pushbutton operation from the
operand assigned to the PUSHBTN 1 SET or PUSHBTN 1 RESET settings.
• PUSHBTN 1 LOCAL: This setting assigns the FlexLogic™ operand serving to inhibit pushbutton operation from the
front panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset.
• PUSHBTN 1 DROP-OUT TIME: This setting applies only to “Self-Reset” mode and specifies the duration of the push-
button active status after the pushbutton has been released. When activated remotely, this setting specifies the entire
activation time of the pushbutton status; the length of time the operand remains on has no effect on the pulse duration.
This setting is required to set the duration of the pushbutton operating pulse.
• PUSHBTN 1 LED CTL: This setting assigns the FlexLogic™ operand serving to drive pushbutton LED. If this setting is
“Off”, then LED operation is directly linked to PUSHBUTTON 1 ON operand.
• PUSHBTN 1 MESSAGE: If pushbutton message is set to “High Priority”, the message programmed in the PUSHBTN 1
IDand PUSHBTN 1 ON TEXT settings will be displayed undisturbed as long as PUSHBUTTON 1 ON operand is asserted.
The high priority option is not applicable to the PUSHBTN 1 OFF TEXT setting.
This message can be temporary removed if any front panel keypad button is pressed. However, ten seconds of keypad
inactivity will restore the message if the PUSHBUTTON 1 ON operand is still active.
If the PUSHBTN 1 MESSAGE is set to “Normal”, the message programmed in the PUSHBTN 1 ID and PUSHBTN 1 ON TEXT
settings will be displayed as long as PUSHBUTTON 1 ON operand is asserted, but not longer than time period specified
by FLASH MESSAGE TIME setting. After the flash time is expired, the default message or other active target message is
displayed. The instantaneous reset of the flash message will be executed if any relay front panel button is pressed or
any new target or message becomes active.
The PUSHBTN 1 OFF TEXT setting is linked to PUSHBUTTON 1 OFF operand and will be displayed in conjunction with
PUSHBTN 1 ID only if pushbutton element is in the “Latched” mode. The PUSHBTN 1 OFF TEXT message will be displayed
as “Normal” if the PUSHBTN 1 MESSAGE setting is “High Priority” or “Normal”.
• PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into
event recorder.
SETTING
Function
LATCHED To user-programmable
= Enabled
pushbuttons logic
= Latched sheet 2, 842024A2
OR LATCHED/SELF-RESET
= Self-Reset
SETTING
Local Lock
Off = 0
Non-volatile latch
AND
S
TIMER
SETTING Latch
50 ms
Remote Lock R
Off = 0 AND
0
SETTING TIMER
OR
Hold 50 ms
TPKP
0
0
OR
SETTING
Set AND
Off = 0
To user-programmable
OR PUSHBUTTON ON pushbuttons logic
OR
sheet 2, 842024A2
SETTING
Reset AND
Off = 0
AND
5
SETTING
SETTING
Autoreset Delay
Autoreset Function
TPKP
= Enabled
AND
= Disabled
0
AND
SETTING
Drop-Out Timer
TIMER 0
FLEXLOGIC OPERAND 200 ms OR
TRST
PUSHBUTTON 1 ON
0
842021A3.CDR
AND
LCD MESSAGE
ENGAGE MESSAGE
SETTING
Flash Message Time
LATCHED SETTINGS
0 Top Text
AND
OR TRST = XXXXXXXXXX
On Text
= XXXXXXXXXX
Instantaneous
From user-programmable reset *
pushbuttons logic
sheet 1, 842021A3
FLEXLOGIC OPERAND
LATCHED/SELF-RESET
AND PUSHBUTTON 1 OFF
FLEXLOGIC OPERAND
PUSHBUTTON ON PUSHBUTTON 1 ON
Instantaneous
Instantaneous reset will be executed if any reset *
front panel button is pressed or any new
target or message becomes active.
This feature provides a mechanism where any of 256 selected FlexLogic™ operand states can be used for efficient moni-
toring. The feature allows user-customized access to the FlexLogic™ operand states in the relay. The state bits are packed
so that 16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states
which are of interest to the user are available in a minimum number of Modbus registers.
The state bits may be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. There are sixteen registers to accommo-
date the 256 state bits.
a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-DEFINABLE DISPLAYS
• USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL
setting. Any FlexLogic™ operand (in particular, the user-programmable pushbutton operands), can be used to navi-
gate the programmed displays.
On the rising edge of the configured operand (such as when the pushbutton is pressed), the displays are invoked by
showing the last user-definable display shown during the previous activity. From this moment onward, the operand
acts exactly as the down key and allows scrolling through the configured displays. The last display wraps up to the first
one. The INVOKE AND SCROLL input and the DOWN key operate concurrently.
When the default timer expires (set by the DEFAULT MESSAGE TIMEOUT setting), the relay will start to cycle through the
user displays. The next activity of the INVOKE AND SCROLL input stops the cycling at the currently displayed user dis-
play, not at the first user-defined display. The INVOKE AND SCROLL pulses must last for at least 250 ms to take effect.
Any existing system display can be automatically copied into an available user display by selecting the existing display and
pressing the ENTER key. The display will then prompt ADD TO USER DISPLAY LIST?. After selecting “Yes”, a message indi-
cates that the selected display has been added to the user display list. When this type of entry occurs, the sub-menus are
automatically configured with the proper content – this content may subsequently be edited.
5 This menu is used to enter user-defined text and user-selected Modbus-registered data fields into the particular user dis-
play. Each user display consists of two 20-character lines (top and bottom). The tilde (~) character is used to mark the start
of a data field – the length of the data field needs to be accounted for. Up to five separate data fields can be entered in a
user display – the nth tilde (~) refers to the nth item.
A user display may be entered from the faceplate keypad or the EnerVista UR Setup interface (preferred for convenience).
The following procedure shows how to enter text characters in the top and bottom lines from the faceplate keypad:
1. Select the line to be edited.
2. Press the decimal key to enter text edit mode.
3. Use either VALUE key to scroll through the characters. A space is selected like a character.
4. Press the decimal key to advance the cursor to the next position.
5. Repeat step 3 and continue entering characters until the desired text is displayed.
6. The HELP key may be pressed at any time for context sensitive help information.
7. Press the ENTER key to store the new settings.
To enter a numerical value for any of the five items (the decimal form of the selected Modbus address) from the faceplate
keypad, use the number keypad. Use the value of “0” for any items not being used. Use the HELP key at any selected sys-
tem display (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the Modbus
address, then manually convert it to decimal form before entering it (EnerVista UR Setup usage conveniently facilitates this
conversion).
Use the MENU key to go to the user displays menu to view the user-defined content. The current user displays will show in
sequence, changing every four seconds. While viewing a user display, press the ENTER key and then select the ‘Yes”
option to remove the display from the user display list. Use the MENU key again to exit the user displays menu.
USER DISPLAY 1 DISP 1 TOP LINE: Shows user-defined text with first tilde marker.
Current X ~ A
DISP 1 BOTTOM LINE: Shows user-defined text with second tilde marker.
MESSAGE
Current Y ~ A
DISP 1 ITEM 1: Shows decimal form of user-selected Modbus register
MESSAGE address, corresponding to first tilde marker.
6016
DISP 1 ITEM 2: Shows decimal form of user-selected Modbus register
MESSAGE address, corresponding to second tilde marker.
6357
DISP 1 ITEM 3: This item is not being used. There is no corresponding
MESSAGE tilde marker in top or bottom lines.
0
DISP 1 ITEM 4: This item is not being used. There is no corresponding
MESSAGE tilde marker in top or bottom lines.
0
DISP 1 ITEM 5: This item is not being used. There is no corresponding
MESSAGE
0 tilde marker in top or bottom lines.
If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the
NOTE
bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items 5
are different.
a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ DIRECT I/O
Direct inputs and outputs are intended for exchange of status information (inputs and outputs) between UR-series relays
connected directly via type 7 digital communications cards. The mechanism is very similar to IEC 61850 GSSE, except that
communications takes place over a non-switchable isolated network and is optimized for speed. On type 7 cards that sup-
port two channels, direct output messages are sent from both channels simultaneously. This effectively sends direct output
messages both ways around a ring configuration. On type 7 cards that support one channel, direct output messages are
sent only in one direction. Messages will be resent (forwarded) when it is determined that the message did not originate at
the receiver.
Direct output message timing is similar to GSSE message timing. Integrity messages (with no state changes) are sent at
least every 1000 ms. Messages with state changes are sent within the main pass scanning the inputs and asserting the
outputs unless the communication channel bandwidth has been exceeded. Two self-tests are performed and signaled by
the following FlexLogic™ operands:
1. DIRECT RING BREAK (direct input/output ring break). This FlexLogic™ operand indicates that direct output messages
sent from a UR-series relay are not being received back by the relay.
2. DIRECT DEVICE 1 OFF to DIRECT DEVICE 16 OFF (direct device offline). These FlexLogic™ operands indicate that direct
output messages from at least one direct device are not being received.
Direct input and output settings are similar to remote input and output settings. The equivalent of the remote device name
strings for direct inputs and outputs is the DIRECT OUTPUT DEVICE ID. The DIRECT OUTPUT DEVICE ID setting identifies the
relay in all direct output messages. All UR-series IEDs in a ring should have unique numbers assigned. The IED ID is used
to identify the sender of the direct input and output message.
If the direct input and output scheme is configured to operate in a ring (DIRECT I/O CH1 RING CONFIGURATION or DIRECT I/O
CH2 RING CONFIGURATION is “Yes”), all direct output messages should be received back. If not, the direct input/output ring
break self-test is triggered. The self-test error is signaled by the DIRECT RING BREAK FlexLogic™ operand.
Select the DIRECT I/O DATA RATE to match the data capabilities of the communications channel. All IEDs communicating
5 over direct inputs and outputs must be set to the same data rate. UR-series IEDs equipped with dual-channel communica-
tions cards apply the same data rate to both channels. Delivery time for direct input and output messages is approximately
0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each ‘bridge’.
The G.703 modules are fixed at 64 kbps. The DIRECT I/O DATA RATE setting is not applicable to these modules.
NOTE
The DIRECT I/O CHANNEL CROSSOVER setting applies to G60s with dual-channel communication cards and allows crossing
over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network
regardless of the physical media of the two communication channels.
The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the
Inputs and outputs section in this chapter for information on configuring FlexLogic™ operands (flags, bits) to be exchanged.
TX1
UR IED 1
RX1
TX1
UR IED 2
RX1
842711A1.CDR
Figure 5–11: INPUT AND OUTPUT EXTENSION VIA DIRECT INPUTS AND OUTPUTS
In the above application, the following settings should be applied. For UR-series IED 1:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O DATA RATE: “128 kbps”
The message delivery time is about 0.2 of power cycle in both ways (at 128 kbps); that is, from device 1 to device 2, and
from device 2 to device 1. Different communications cards can be selected by the user for this back-to-back connection (for
example: fiber, G.703, or RS422).
EXAMPLE 2: INTERLOCKING BUSBAR PROTECTION
A simple interlocking busbar protection scheme could be accomplished by sending a blocking signal from downstream
devices, say 2, 3, and 4, to the upstream device that monitors a single incomer of the busbar, as shown below.
UR IED 1 BLOCK
842712A1.CDR
TX1 RX1
UR IED 1
RX2 TX2
TX2 RX2
UR IED 3
RX1 TX1
842716A1.CDR
UR IED 1 UR IED 2
UR IED 3
842713A1.CDR
5
RX1
UR IED 3
TX1
842714A1.CDR
TX1 RX1
UR IED 3
RX2 TX2
842715A1.CDR
The G60 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is
available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The
monitoring function counts all incoming messages, including messages that failed the CRC check. A separate counter adds
up messages that failed the CRC check. When the failed CRC counter reaches the user-defined level specified by the CRC
ALARM CH1 THRESHOLD setting within the user-defined message count CRC ALARM 1 CH1 COUNT, the DIR IO CH1 CRC ALARM
FlexLogic™ operand is set.
When the total message counter reaches the user-defined maximum specified by the CRC ALARM CH1 MESSAGE COUNT set-
ting, both the counters reset and the monitoring process is restarted.
The operand shall be configured to drive an output contact, user-programmable LED, or selected communication-based
output. Latching and acknowledging conditions - if required - should be programmed accordingly.
The CRC alarm function is available on a per-channel basis. The total number of direct input and output messages that
failed the CRC check is available as the ACTUAL VALUES Ö STATUS ÖØ DIRECT INPUTS ÖØ CRC FAIL COUNT CH1 actual
value.
• Message count and length of the monitoring window: To monitor communications integrity, the relay sends 1 message
per second (at 64 kbps) or 2 messages per second (128 kbps) even if there is no change in the direct outputs. For
example, setting the CRC ALARM CH1 MESSAGE COUNT to “10000”, corresponds a time window of about 160 minutes at
64 kbps and 80 minutes at 128 kbps. If the messages are sent faster as a result of direct outputs activity, the monitor-
ing time interval will shorten. This should be taken into account when determining the CRC ALARM CH1 MESSAGE COUNT
setting. For example, if the requirement is a maximum monitoring time interval of 10 minutes at 64 kbps, then the CRC
ALARM CH1 MESSAGE COUNT should be set to 10 × 60 × 1 = 600.
• Correlation of failed CRC and bit error rate (BER): The CRC check may fail if one or more bits in a packet are cor-
rupted. Therefore, an exact correlation between the CRC fail rate and the BER is not possible. Under certain assump-
tions an approximation can be made as follows. A direct input and output packet containing 20 bytes results in 160 bits
of data being sent and therefore, a transmission of 63 packets is equivalent to 10,000 bits. A BER of 10–4 implies 1 bit
error for every 10000 bits sent or received. Assuming the best case of only 1 bit error in a failed packet, having 1 failed
packet for every 63 received is about equal to a BER of 10–4.
The G60 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring
configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned
messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unre-
turned messages. This function counts all the outgoing messages and a separate counter adds the messages have failed
to return. When the unreturned messages counter reaches the user-definable level specified by the UNRET MSGS ALARM
CH1 THRESHOLD setting and within the user-defined message count UNRET MSGS ALARM CH1 COUNT, the DIR IO CH1 UNRET
ALM FlexLogic™ operand is set.
When the total message counter reaches the user-defined maximum specified by the UNRET MSGS ALARM CH1 MESSAGE
COUNT setting, both the counters reset and the monitoring process is restarted.
The operand shall be configured to drive an output contact, user-programmable LED, or selected communication-based
output. Latching and acknowledging conditions, if required, should be programmed accordingly.
The unreturned messages alarm function is available on a per-channel basis and is active only in the ring configuration.
The total number of unreturned input and output messages is available as the ACTUAL VALUES Ö STATUS ÖØ DIRECT
INPUTS ÖØ UNRETURNED MSG COUNT CH1 actual value.
5.2.17 TELEPROTECTION
Digital teleprotection functionality is designed to transfer protection commands between two or three relays in a secure,
fast, dependable, and deterministic fashion. Possible applications are permissive or blocking pilot schemes and direct
transfer trip (DTT). Teleprotection can be applied over any analog or digital channels and any communications media, such
as direct fiber, copper wires, optical networks, or microwave radio links. A mixture of communication media is possible.
Once teleprotection is enabled and the teleprotection input/outputs are configured, data packets are transmitted continu-
ously every 1/4 cycle (3/8 cycle if using C37.94 modules) from peer-to-peer. Security of communication channel data is
achieved by using CRC-32 on the data packet.
5
Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive – as such, they cannot be used simu-
latneously. Once teleprotection inputs and outputs are enabled, direct inputs and outputs are blocked, and vice
NOTE versa.
• NUMBER OF TERMINALS: Specifies whether the teleprotection system operates between two peers or three peers.
• NUMBER OF CHANNELS: Specifies how many channels are used. If the NUMBER OF TERMINALS is “3” (three-terminal
system), set the NUMBER OF CHANNELS to “2”. For a two-terminal system, the NUMBER OF CHANNELS can set to “1” or
“2” (redundant channels).
• LOCAL RELAY ID NUMBER, TERMINAL 1 RELAY ID NUMBER, and TERMINAL 2 RELAY ID NUMBER: In installa-
tions that use multiplexers or modems, it is desirable to ensure that the data used by the relays protecting a given line
is from the correct relays. The teleprotection function performs this check by reading the message ID sent by transmit-
ting relays and comparing it to the programmed ID in the receiving relay. This check is also used to block inputs if inad-
vertently set to loopback mode or data is being received from a wrong relay by checking the ID on a received channel.
If an incorrect ID is found on a channel during normal operation, the TELEPROT CH1 ID FAIL or TELEPROT CH2 ID FAIL
FlexLogic™ operand is set, driving the event with the same name and blocking the teleprotection inputs. For commis-
sioning purposes, the result of channel identification is also shown in the STATUS ÖØ CHANNEL TESTS ÖØ VALIDITY OF
CHANNEL CONFIGURATION actual value. The default value of “0” for the LOCAL RELAY ID NUMBER indicates that relay ID
is not to be checked. On two- terminals two-channel systems, the same LOCAL RELAY ID NUMBER is transmitted over
both channels; as such, only the TERMINAL 1 ID NUMBER has to be programmed on the receiving end.
5.2.18 INSTALLATION
To safeguard against the installation of a relay without any entered settings, the unit will not allow signaling of any output
relay until RELAY SETTINGS is set to "Programmed". This setting is defaulted to "Not Programmed" when at the factory. The
UNIT NOT PROGRAMMED self-test error message is displayed until the relay is put into the "Programmed" state.
The RELAY NAME setting allows the user to uniquely identify a relay. This name will appear on generated reports. This name
is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com-
munications channel using the IEC 61850 protocol.
When G60 is ordered with a process card module as a part of HardFiber system, then an additional Remote Resources
menu tree is available in EnerVista UR Setup software to allow configuring HardFiber system.
a) CURRENT BANKS
PATH: SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS Ö CURRENT BANK F1(M5)
Because energy parameters are accumulated, these values should be recorded and then reset immediately
prior to changing CT characteristics.
NOTE
Four banks of phase and ground CTs can be set, where the current banks are denoted in the following format (X represents
the module slot position letter):
Xa, where X = {F, M} and a = {1, 5}.
See the Introduction to AC Sources section at the beginning of this chapter for additional details.
These settings are critical for all features that have settings dependent on current measurements. When the relay is
5 ordered, the CT module must be specified to include a standard or sensitive ground input. As the phase CTs are connected
in wye (star), the calculated phasor sum of the three phase currents (IA + IB + IC = neutral current = 3Io) is used as the
input for the neutral overcurrent elements. In addition, a zero-sequence (core balance) CT which senses current in all of the
circuit primary conductors, or a CT in a neutral grounding conductor may also be used. For this configuration, the ground
CT primary rating must be entered. To detect low level ground fault currents, the sensitive ground input may be used. In this
case, the sensitive ground CT primary rating must be entered. Refer to chapter 3 for more details on CT connections.
Enter the rated CT primary current values. For both 1000:5 and 1000:1 CTs, the entry would be 1000. For correct opera-
tion, the CT secondary rating must match the setting (which must also correspond to the specific CT connections used).
The following example illustrates how multiple CT inputs (current banks) are summed as one source current. Given If the
following current banks:
• F1: CT bank with 500:1 ratio.
• F5: CT bank with 1000: ratio.
• M1: CT bank with 800:1 ratio.
The following rule applies:
SRC 1 = F1 + F5 + M1 (EQ 5.6)
1 pu is the highest primary current. In this case, 1000 is entered and the secondary current from the 500:1 ratio CT will be
adjusted to that created by a 1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then
a pickup level of 1 pu will operate on 1000 A primary.
The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A).
b) VOLTAGE BANKS
PATH: SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE BANK F5(M5)
Because energy parameters are accumulated, these values should be recorded and then reset immediately
prior to changing VT characteristics.
CAUTION
Two banks of phase/auxiliary VTs can be set, where voltage banks are denoted in the following format (X represents the
module slot position letter):
Xa, where X = {F, M} and a = {5}.
See the Introduction to AC sources section at the beginning of this chapter for additional details.
5
With VTs installed, the relay can perform voltage measurements as well as power calculations. Enter the PHASE VT F5 CON-
NECTION made to the system as “Wye” or “Delta”. An open-delta source VT connection would be entered as “Delta”.
The nominal PHASE VT F5 SECONDARY voltage setting is the voltage across the relay input terminals when nominal
voltage is applied to the VT primary.
NOTE
For example, on a system with a 13.8 kV nominal primary voltage and with a 14400:120 volt VT in a delta connec-
tion, the secondary voltage would be 115; that is, (13800 / 14400) × 120. For a wye connection, the voltage value
entered must be the phase to neutral voltage which would be 115 / 3 = 66.4.
On a 14.4 kV system with a delta connection and a VT primary to secondary turns ratio of 14400:120, the voltage
value entered would be 120; that is, 14400 / 120.
The power system NOMINAL FREQUENCY value is used as a default to set the digital sampling rate if the system frequency
cannot be measured from available signals. This may happen if the signals are not present or are heavily distorted. Before
reverting to the nominal frequency, the frequency tracking algorithm holds the last valid frequency measurement for a safe
period of time while waiting for the signals to reappear or for the distortions to decay.
The phase sequence of the power system is required to properly calculate sequence components and power parameters.
The PHASE ROTATION setting matches the power system phase sequence. Note that this setting informs the relay of the
actual system phase sequence, either ABC or ACB. CT and VT inputs on the relay, labeled as A, B, and C, must be con-
nected to system phases A, B, and C for correct operation.
The REVERSE PH ROTATION setting allows the user to dynamically change the phase rotation used for phasor calculations.
This allows the G60 to follow the current phase rotation of the protected generator. For example, if the PHASE ROTATION set-
ting is “ABC” but the condition defined for opposite phase rotation is true, then the phase rotation used for phasor calcula-
tion will switch to “ACB”. This feature is only intended for use in special applications, such as pumped storage schemes
The FREQUENCY AND PHASE REFERENCE setting determines which signal source is used (and hence which AC signal) for
phase angle reference. The AC signal used is prioritized based on the AC inputs that are configured for the signal source:
phase voltages takes precedence, followed by auxiliary voltage, then phase currents, and finally ground current.
For three phase selection, phase A is used for angle referencing ( V ANGLE REF = V A ), while Clarke transformation of the
phase signals is used for frequency metering and tracking ( V FREQUENCY = ( 2V A – V B – V C ) ⁄ 3 ) for better performance dur-
ing fault, open pole, and VT and CT fail conditions.
The phase reference and frequency tracking AC signals are selected based upon the Source configuration, regardless of
whether or not a particular signal is actually applied to the relay.
Phase angle of the reference signal will always display zero degrees and all other phase angles will be relative to this sig-
nal. If the pre-selected reference signal is not measurable at a given time, the phase angles are not referenced.
The phase angle referencing is done via a phase locked loop, which can synchronize independent UR-series relays if they
5 have the same AC signal reference. These results in very precise correlation of time tagging in the event recorder between
different UR-series relays provided the relays have an IRIG-B connection.
FREQUENCY TRACKING should only be set to “Disabled” in very unusual circumstances; consult the factory for spe-
cial variable-frequency applications.
NOTE
The frequency tracking feature will function only when the G60 is in the “Programmed” mode. If the G60 is “Not Pro-
grammed”, then metering values will be available but may exhibit significant errors.
NOTE
Identical menus are available for each source. The "SRC 1" text can be replaced by with a user-defined name appropriate
for the associated source.
The first letter in the source identifier represents the module slot position. The number directly following this letter repre-
sents either the first bank of four channels (1, 2, 3, 4) called “1” or the second bank of four channels (5, 6, 7, 8) called “5” in
a particular CT/VT module. Refer to the Introduction to AC sources section at the beginning of this chapter for additional
details on this concept.
It is possible to select the sum of all CT combinations. The first channel displayed is the CT to which all others will be
referred. For example, the selection “F1+F5” indicates the sum of each phase from channels “F1” and “F5”, scaled to
whichever CT has the higher ratio. Selecting “None” hides the associated actual values.
The approach used to configure the AC sources consists of several steps; first step is to specify the information about each
CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type,
ratio and nominal secondary voltage. Once the inputs have been specified, the configuration for each source is entered,
including specifying which CTs will be summed together.
User selection of AC parameters for comparator elements:
CT/VT modules automatically calculate all current and voltage parameters from the available inputs. Users must select the
specific input parameters to be measured by every element in the relevant settings menu. The internal design of the ele-
ment specifies which type of parameter to use and provides a setting for source selection. In elements where the parameter
may be either fundamental or RMS magnitude, such as phase time overcurrent, two settings are provided. One setting
specifies the source, the second setting selects between fundamental phasor and RMS.
AC input actual values:
The calculated parameters associated with the configured voltage and current inputs are displayed in the current and volt-
age sections of actual values. Only the phasor quantities associated with the actual AC physical input channels will be dis-
played here. All parameters contained within a configured source are displayed in the sources section of the actual values.
DISTURBANCE DETECTORS (INTERNAL):
The disturbance detector (ANSI 50DD) element is a sensitive current disturbance detector that detects any disturbance on
the protected system. The 50DD function is intended for use in conjunction with measuring elements, blocking of current
5
based elements (to prevent maloperation as a result of the wrong settings), and starting oscillography data capture. A dis-
turbance detector is provided for each source.
The 50DD function responds to the changes in magnitude of the sequence currents. The disturbance detector scheme
logic is as follows:
SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 1 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 1 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old
SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 2 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 2 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old
SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 6 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 6 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old 827092A3.CDR
This configuration could be used on a two-winding transformer, with one winding connected into a breaker-and-a-half sys-
tem. The following figure shows the arrangement of sources used to provide the functions required in this application, and
the CT/VT inputs that are used to provide the data.
F1 DSP Bank
F5
Source 1 Source 2
Amps Amps
Source 3
51BF-1 51BF-2
U1 Volts Amps
A W Var 87T
A W Var 51P
Volts Amps
5 M1
M1
Source 4
UR Relay
M5
5.4.4 BREAKERS
A description of the operation of the breaker control and status monitoring features is provided in chapter 4. Only informa-
tion concerning programming of the associated settings is covered here. These features are provided for two or more
breakers; a user may use only those portions of the design relevant to a single breaker, which must be breaker 1.
The number of breaker control elements is dependent on the number of CT/VT modules specified with the G60. The follow-
ing settings are available for each breaker control element.
• BREAKER 1 FUNCTION: This setting enables and disables the operation of the breaker control feature.
• BREAKER1 PUSH BUTTON CONTROL: Set to “Enable” to allow faceplate push button operations.
• BREAKER 1 NAME: Assign a user-defined name (up to six characters) to the breaker. This name will be used in flash
messages related to breaker 1.
• BREAKER 1 MODE: This setting selects “3-Pole” mode, where all breaker poles are operated simultaneously, or “1-
Pole” mode where all breaker poles are operated either independently or simultaneously.
• BREAKER 1 OPEN: This setting selects an operand that creates a programmable signal to operate an output relay to
open breaker 1.
• BREAKER 1 BLK OPEN: This setting selects an operand that prevents opening of the breaker. This setting can be
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• BREAKER 1 CLOSE: This setting selects an operand that creates a programmable signal to operate an output relay
to close breaker 1.
• BREAKER 1 BLK CLOSE: This setting selects an operand that prevents closing of the breaker. This setting can be
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• BREAKER 1 ΦA/3P CLOSED: This setting selects an operand, usually a contact input connected to a breaker auxil-
iary position tracking mechanism. This input should be a normally-open 52/a status input to create a logic 1 when the
5 breaker is closed. If the BREAKER 1 MODE setting is selected as “3-Pole”, this setting selects a single input as the oper-
and used to track the breaker open or closed position. If the mode is selected as “1-Pole”, the input mentioned above
is used to track phase A and the BREAKER 1 ΦB and BREAKER 1 ΦC settings select operands to track phases B and C,
respectively.
• BREAKER 1 ΦA/3P OPND: This setting selects an operand, usually a contact input, that should be a normally-closed
52/b status input to create a logic 1 when the breaker is open. If a separate 52/b contact input is not available, then the
inverted BREAKER 1 CLOSED status signal can be used.
• BREAKER 1 ΦB CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase B closed position as above for phase A.
• BREAKER 1 ΦB OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase B opened position as above for phase A.
• BREAKER 1 ΦC CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase C closed position as above for phase A.
• BREAKER 1 ΦC OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase C opened position as above for phase A.
• BREAKER 1 Toperate: This setting specifies the required interval to overcome transient disagreement between the
52/a and 52/b auxiliary contacts during breaker operation. If transient disagreement still exists after this time has
expired, the BREAKER 1 BAD STATUS FlexLogic™ operand is asserted from alarm or blocking purposes.
• BREAKER 1 EXT ALARM: This setting selects an operand, usually an external contact input, connected to a breaker
alarm reporting contact.
• BREAKER 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among
the three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous oper-
ation of the poles.
• MANUAL CLOSE RECAL1 TIME: This setting specifies the interval required to maintain setting changes in effect after
an operator has initiated a manual close command to operate a circuit breaker.
• BREAKER 1 OUT OF SV: Selects an operand indicating that breaker 1 is out-of-service.
SETTING
BREAKER 1 FUNCTION
FLEXLOGIC OPERANDS
= Enabled
AND BREAKER 1 OFF CMD
= Disabled
BREAKER 1 TRIP A
BREAKER 1 TRIP B
AND
SETTING BREAKER 1 TRIP C
BREAKER 1 BLOCK OPEN
Off = 0 AND
TRIP PHASE A
TRIP PHASE B
TRIP PHASE C
TRIP 3-POLE
SETTING
BREAKER 1 OPEN
Off = 0
OR
SETTING
BREAKER 1 PUSHBUTTON
CONTROL
= Enabled
AND
USER 2 OFF/ON
To open BRK1-(Name)
OR
SETTING AND
BREAKER 1 CLOSE
Off = 0
OR
5
FLEXLOGIC OPERAND
AND BREAKER 1 MNL CLS
61850 Select & Close SETTING
MANUAL CLOSE RECAL1 TIME AND
FLEXLOGIC OPERAND
SETTING
OR AND BREAKER 1 ON CMD
BREAKER 1 BLOCK CLOSE
Off = 0 827061AS.CDR
NOTE
from breaker
controlsheetlogic1, BKR ENABLED
827061AS FLEXLOGIC OPERAND BREAKER 1
AND AND BREAKER 1 CLOSED CLOSED
OR (DEFAULT)
FLEXLOGIC OPERAND
SETTING SETTING OR BREAKER 1 BAD STATUS
AND
BREAKER 1 ΦA/3P CLSD BREAKER 1 Toperate
= Off FLEXLOGIC OPERANDS
AND AND
BREAKER 1 ΦA BAD ST
0 OR
BREAKER 1 ΦA CLSD
SETTING
AND BREAKER 1 ΦA OPEN
BREAKER 1 ΦA/3P OPND
AND BREAKER 1 ΦA INTERM
= Off
AND
AND
AND
SETTING SETTING
AND
BREAKER 1 ΦB CLSD BREAKER 1 Toperate
FLEXLOGIC OPERANDS
5 = Off
AND
0 OR
AND BREAKER 1 ΦB BAD ST
BREAKER 1 ΦB CLSD
SETTING BREAKER 1 ΦB OPEN
AND
BREAKER 1 ΦB OPND BREAKER 1 ΦB INTERM
AND
= Off
AND
AND
AND
SETTING SETTING
AND
BREAKER 1 ΦC CLSD BREAKER 1 Toperate
FLEXLOGIC OPERANDS
= Off AND
AND BREAKER 1 ΦC BAD ST
0 OR BREAKER 1 ΦC CLSD
SETTING BREAKER 1 ΦC OPEN
AND
BREAKER 1 ΦC OPND BREAKER 1 ΦC INTERM
AND
= Off
AND
AND
AND
XOR AND
SETTING
BREAKER 1 OUT OF SV AND
= Off 842025A2.CDR
The disconnect switch element contains the auxiliary logic for status and serves as the interface for opening and closing of
disconnect switches from SCADA or through the front panel interface. The disconnect switch element can be used to cre-
ate an interlocking functionality. For greater security in determination of the switch pole position, both the 52/a and 52/b
auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches
depends on the number of the CT/VT modules ordered with the G60.
• SWITCH 1 FUNCTION: This setting enables and disables the operation of the disconnect switch element.
• SWITCH 1 NAME: Assign a user-defined name (up to six characters) to the disconnect switch. This name will be used
in flash messages related to disconnect switch 1.
• SWITCH 1 MODE: This setting selects “3-Pole” mode, where all disconnect switch poles are operated simultaneously,
or “1-Pole” mode where all disconnect switch poles are operated either independently or simultaneously.
• SWITCH 1 OPEN: This setting selects an operand that creates a programmable signal to operate an output relay to
open disconnect switch 1.
• SWITCH 1 BLK OPEN: This setting selects an operand that prevents opening of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• SWITCH 1 CLOSE: This setting selects an operand that creates a programmable signal to operate an output relay to
close disconnect switch 1.
• SWITCH 1 BLK CLOSE: This setting selects an operand that prevents closing of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• SWTCH 1 ΦA/3P CLSD: This setting selects an operand, usually a contact input connected to a disconnect switch
auxiliary position tracking mechanism. This input should be a normally-open 52/a status input to create a logic 1 when
the disconnect switch is closed. If the SWITCH 1 MODE setting is selected as “3-Pole”, this setting selects a single input
as the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole”, the
input mentioned above is used to track phase A and the SWITCH 1 ΦB and SWITCH 1 ΦC settings select operands to
track phases B and C, respectively.
• SWITCH 1 ΦA/3P OPND: This setting selects an operand, usually a contact input, that should be a normally-closed
52/b status input to create a logic 1 when the disconnect switch is open. If a separate 52/b contact input is not avail-
able, then the inverted SWITCH 1 CLOSED status signal can be used.
• SWITCH 1 ΦB CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B closed position as above for phase A.
• SWITCH 1 ΦB OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B opened position as above for phase A.
• SWITCH 1 ΦC CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
5 single-pole, this input is used to track the disconnect switch phase C closed position as above for phase A.
• SWITCH 1 ΦC OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C opened position as above for phase A.
• SWITCH 1 Toperate: This setting specifies the required interval to overcome transient disagreement between the 52/a
and 52/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the SWITCH 1 BAD STATUS FlexLogic™ operand is asserted from alarm or blocking purposes.
• SWITCH 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among the
three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation
of the poles.
IEC 61850 functionality is permitted when the G60 is in “Programmed” mode and not in the local control mode.
NOTE
SETTINGS
SWITCH 1 FUNCTION
= Disabled
= Enabled
SWITCH 1 OPEN FLEXLOGIC OPERAND
= Off SWITCH 1 OFF CMD
OR AND
SETTING 61850 Select & Open
SWITCH 1 BLK OPEN
= Off
SETTING
SWITCH 1 CLOSE
= Off FLEXLOGIC OPERAND
OR AND SWITCH 1 ON CMD
SETTING 61850 Select & Close
SWITCH 1 BLK CLOSE
= Off
FLEXLOGIC OPERAND
AND AND SWITCH 1 CLOSED
OR
FLEXLOGIC OPERAND
SETTING SETTING OR SWITCH 1 BAD STATUS
AND
SWITCH 1 ΦA/3P CLSD SWITCH 1 Toperate
= Off FLEXLOGIC OPERANDS
SETTING
AND
0 OR
AND
SWITCH 1 ΦA BAD ST
SWITCH 1 ΦA CLSD
5
AND SWITCH 1 ΦA OPEN
SWITCH 1 ΦA/3P OPND
AND SWITCH 1 ΦA INTERM
= Off
AND
AND
AND
SETTING SETTING
AND
SWITCH 1 ΦB CLSD SWITCH 1 Toperate
FLEXLOGIC OPERANDS
= Off AND
AND SWITCH 1 ΦB BAD ST
0 OR SWITCH 1 ΦB CLSD
SETTING SWITCH 1 ΦB OPEN
AND
SWITCH 1 ΦB OPND SWITCH 1 ΦB INTERM
AND
= Off
AND
AND
AND
SETTING SETTING
AND
SWITCH 1 ΦC CLSD SWITCH 1 Toperate
FLEXLOGIC OPERANDS
= Off AND
AND SWITCH 1 ΦC BAD ST
0 OR SWITCH 1 ΦC CLSD
SETTING SWITCH 1 ΦC OPEN
AND
SWITCH 1 ΦC OPND SWITCH 1 ΦC INTERM
AND
= Off
AND
AND
AND
842026A4.CDR
5.4.6 FLEXCURVES
a) SETTINGS
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ FLEXCURVES Ö FLEXCURVE A(D)
FlexCurves™ A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter a
custom FlexCurve™, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using the
MESSAGE UP/DOWN keys) for the desired protection curve (A, B, C, or D).
The relay using a given FlexCurve™ applies linear approximation for times between the user-entered
points. Special care must be applied when setting the two points that are close to the multiple of pickup of
NOTE
1; that is, 0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the lin-
ear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu.
Addr: Adds the time specified in this field (in ms) to each
curve operating time value.
d) EXAMPLE
A composite curve can be created from the GE_111 standard with MRT = 200 ms and HCT initially disabled and then
enabled at eight (8) times pickup with an operating time of 30 ms. At approximately four (4) times pickup, the curve operat-
ing time is equal to the MRT and from then onwards the operating time remains at 200 ms (see below).
842719A1.CDR
842720A1.CDR
1 GE106
0.5
0.2
TIME (sec)
GE103
GE104 GE105
0.1
0.05
GE101 GE102
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842723A1.CDR
5
Figure 5–26: RECLOSER CURVES GE101 TO GE106
50
20 GE142
10
5
GE138
TIME (sec)
1 GE120
GE113
0.5
0.2
0.1
0.05
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842725A1.CDR
50
20
10
GE201
TIME (sec)
GE151
2
GE134 GE140
1
GE137
0.5
50
GE152
20
TIME (sec)
GE141
10
GE131
5
GE200
2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842728A1.CDR
50
20
GE164
10
2
TIME (sec)
GE162
1
0.5
GE133
0.2
GE165
0.1
0.05
GE161
0.02 GE163
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842729A1.CDR
Figure 5–30: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 5
20
GE132
10
1
TIME (sec)
0.5 GE139
0.2
GE136
0.1
GE116
0.05
GE118 GE117
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842726A1.CDR
Figure 5–31: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139
20
10
5
GE122
2
1
TIME (sec)
0.5
GE114
0.2
GE111
GE121
0.1
0.02
0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842724A1.CDR
5 Figure 5–32: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122
50
20
GE202
10
TIME (sec)
GE135
2 GE119
0.5
0.2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842727A1.CDR
a) MAIN MENU
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT UNIT
The G60 Generator Protection System is provided with an optional phasor measurement unit feature. This
feature is specified as a software option at the time of ordering. The number of phasor measurement units
available is also dependent on this option. Refer to the Ordering section of chapter 2 for additional details.
The PHASOR MEASUREMENT UNIT menu allows specifying basic parameters of the measurements process such as signal
source, ID and station name, calibration data, triggering, recording, and content for transmission on each of the supported
ports. The reporting ports menus allow specifying the content and rate of reporting on each of the supported ports.
Precise IRIG-B input is vital for correct synchrophasor measurement and reporting. A DC level shift IRIG-B receiver
must be used for the phasor measurement unit to output proper synchrophasor values.
NOTE
b) BASIC CONFIGURATION
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1 Ö PMU 1 BASIC CONFIGURATION 1
This section contains basic phasor measurement unit (PMU) data, such as functions, source settings, and names.
• PMU 1 FUNCTION: This setting enables the PMU 1 functionality. Any associated functions (such as the recorder or
triggering comparators) will not function if this setting is “Disabled”. Use the command frame to force the communica-
tion portion of the feature to start/stop transmission of data. When the transmission is turned off, the PMU is fully oper-
ational in terms of calculating and recording the phasors.
• PMU 1 IDCODE: This setting assigns a numerical ID to the PMU. It corresponds to the IDCODE field of the data, con-
figuration, header, and command frames of the C37.118 protocol. The PMU uses this value when sending data, config-
uration, and header frames and responds to this value when receiving the command frame.
5 • PMU 1 STN: This setting assigns an alphanumeric ID to the PMU station. It corresponds to the STN field of the config-
uration frame of the C37.118 protocol. This value is a 16-character ASCII string as per the C37.118 standard.
• PMU 1 SIGNAL SOURCE: This setting specifies one of the available G60 signal sources for processing in the PMU.
Note that any combination of voltages and currents can be configured as a source. The current channels could be con-
figured as sums of physically connected currents. This facilitates PMU applications in breaker-and-a-half, ring-bus, and
similar arrangements. The PMU feature calculates voltage phasors for actual voltage (A, B, C, and auxiliary) and cur-
rent (A, B, C, and ground) channels of the source, as well as symmetrical components (0, 1, and 2) of both voltages
and currents. When configuring communication and recording features of the PMU, the user could select – from the
above superset – the content to be sent out or recorded.
• PMU 1 POST-FILTER: This setting specifies amount of post-filtering applied to raw synchrophasor measurements.
The raw measurements are produced at the rate of nominal system frequency using one-cycle data windows. This set-
ting is provided to deal with interfering frequencies and to balance speed and accuracy of synchrophasor measure-
ments for different applications. The following filtering choices are available:
Table 5–7: POST-FILTER CHOICES
SELECTION CHARACTERISTIC OF THE FILTER
None No post-filtering
Symm-3-point Symmetrical 3-point filter (1 historical point, 1 present point, 1 future point)
Symm-5-point Symmetrical 5-point filter (2 historical points, 1 present point, 2 future points)
Symm-7-point Symmetrical 7-point filter (3 historical points, 1 present point, 3 future points)
Class M Symmetrical FIR filter on samples
Class P 21-tap symmetrical FIR filter on current input channels
This setting applies to all channels of the PMU. It is effectively for recording and transmission on all ports configured to
use data of this PMU.
Class M filtering functionality is derived from the draft C37.118 specification and may be subject to change
when the standard is published.
NOTE
c) CALIBRATION
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1(4) ÖØ PMU 1 CALIBRATION
This menu contains user angle calibration data for the phasor measurement unit (PMU). This data is combined with the fac-
tory adjustments to shift the phasors for better accuracy.
• PMU 1 VA... IG CALIBRATION ANGLE: These settings recognize applications with protection class voltage and cur-
rent sources, and allow the user to calibrate each channel (four voltages and four currents) individually to offset errors
introduced by VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter
a positive correction of the secondary signal lags the true signal; and negative value if the secondary signal leads the
true signal.
• PMU 1 SEQ VOLT SHIFT ANGLE: This setting allows correcting positive- and negative-sequence voltages for vector
groups of power transformers located between the PMU voltage point, and the reference node. This angle is effectively
added to the positive-sequence voltage angle, and subtracted from the negative-sequence voltage angle. Note that:
1. When this setting is not “0°”, the phase and sequence voltages will not agree. Unlike sequence voltages, the
phase voltages cannot be corrected in a general case, and therefore are reported as measured.
2. When receiving synchrophasor date at multiple locations, with possibly different reference nodes, it may be more
beneficial to allow the central locations to perform the compensation of sequence voltages.
3. This setting applies to PMU data only. The G60 calculates symmetrical voltages independently for protection and
control purposes without applying this correction.
4. When connected to line-to-line voltages, the PMU calculates symmetrical voltages with the reference to the AG
voltage, and not to the physically connected AB voltage (see the Metering Conventions section in Chapter 6).
• PMU 1 SEQ CURR SHIFT ANGLE: This setting allows correcting positive and negative-sequence currents for vector
groups of power transformers located between the PMU current point and the reference node. The setting has the
same meaning for currents as the PMU 1 SEQ VOLT SHIFT ANGLE setting has for voltages. Normally, the two correcting
angles are set identically, except rare applications when the voltage and current measuring points are located at differ-
ent windings of a power transformer.
d) PMU COMMUNICATION
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 COMMUNICATION ÖØ PMU 1 COMM PORT
5 Off
PMU1 PORT A-CH-8 Range: 16 alphanumeric characters
MESSAGE
NM: AnalogChannel8
PMU1 PORT D-CH-1: Range: FlexLogic™ operands
MESSAGE
Off
PMU1 PORT D-CH-1 Range: 16 alphanumeric characters
MESSAGE
NM: DigitalChannel1
PMU1 PORT D-CH-1 Range: On, Off
MESSAGE
NORMAL STATE: Off
↓
This section configures the phasor measurement unit (PMU) communication functions.
• PMU1 COMM PORT: This setting specifies the communication port for transmission of the PMU data.
• PMU1 PORT PHS-1 to PMU1 PORT PHS-14: These settings specify synchrophasors to be transmitted from the
superset of all synchronized measurements. The available synchrophasor values are tabulated below.
SELECTION MEANING
Va First voltage channel, either Va or Vab
Vb Second voltage channel, either Vb or Vbc
Vc Third voltage channel, either Vc or Vca
Vx Fourth voltage channel
Ia Phase A current, physical channel or summation as per the source settings
Ib Phase B current, physical channel or summation as per the source settings
Ic Phase C current, physical channel or summation as per the source settings
Ig Fourth current channel, physical or summation as per the source settings
V1 Positive-sequence voltage, referenced to Va
V2 Negative-sequence voltage, referenced to Va
V0 Zero-sequence voltage
I1 Positive-sequence current, referenced to Ia
I2 Negative-sequence current, referenced to Ia
I0 Zero-sequence current
These settings allow for optimizing the frame size and maximizing transmission channel usage, depending on a given
application. Select “Off” to suppress transmission of a given value.
• PMU1 PORT PHS-1 NM to PMU1 PORT PHS-14 NM: These settings allow for custom naming of the synchrophasor
channels. Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame. These names
are typically based on station, bus, or breaker names.
5
• PMU1 PORT A-CH-1 to PMU1 PORT A-CH-8: These settings specify any analog data measured by the relay to be
included as a user-selectable analog channel of the data frame. Up to eight analog channels can be configured to send
any FlexAnalog value from the relay. Examples include active and reactive power, per phase or three-phase power,
power factor, temperature via RTD inputs, and THD. The configured analog values are sampled concurrently with the
synchrophasor instant and sent as 32-bit floating point values.
• PMU1 PORT A-CH-1 NM to PMU1 PORT A-CH-8 NM: These settings allow for custom naming of the analog chan-
nels. Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame.
• PMU1 PORT D-CH-1 to PMU1 PORT D-CH-16: These settings specify any digital flag measured by the relay to be
included as a user-selectable digital channel of the data frame. Up to sixteen digital channels can be configured to
send any FlexLogic™ operand from the relay. The configured digital flags are sampled concurrently with the synchro-
phasor instant. The values are mapped into a two-byte integer number, with byte 1 LSB corresponding to the digital
channel 1 and byte 2 MSB corresponding to digital channel 16.
• PMU1 PORT D-CH-1 NM to PMU1 PORT D-CH-16 NM: These settings allow for custom naming of the digital chan-
nels. Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame.
• PMU1 PORT D-CH-1 NORMAL STATE to PMU1 PORT D-CH-16 NORMAL STATE: These settings allow for specify-
ing a normal state for each digital channel. These states are transmitted in configuration frames to the data concentra-
tor.
Each logical phasor measurement unit (PMU) contains five triggering mechanisms to facilitate triggering of the associated
PMU recorder, or cross-triggering of other PMUs of the system. They are:
• Overfrequency and underfrequency.
• Overvoltage and undervoltage.
• Overcurrent.
5 • Overpower.
• High rate of change of frequency.
The pre-configured triggers could be augmented with a user-specified condition built freely using programmable logic of the
relay. The entire triggering logic is refreshed once every two power system cycles.
All five triggering functions and the user-definable condition are consolidated (ORed) and connected to the PMU recorder.
Each trigger can be programmed to log its operation into the event recorder, and to signal its operation via targets. The five
triggers drive the STAT bits of the data frame to inform the destination of the synchrophasor data regarding the cause of
trigger. The following convention is adopted to drive bits 11, 3, 2, 1, and 0 of the STAT word.
SETTING
PMU 1 USER TRIGGER:
Off = 0
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER FLEXLOGIC OPERAND
OR
bit 0
OR
f) USER TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 USER TRIGGER
The user trigger allows customized triggering logic to be constructed from FlexLogic™. The entire triggering logic is
refreshed once every two power system cycles.
g) FREQUENCY TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 FREQUENCY TRIGGER
The trigger responds to the frequency signal of the phasor measurement unit (PMU) source. The frequency is calculated
from either phase voltages, auxiliary voltage, phase currents and ground current, in this hierarchy, depending on the source
configuration as per G60 standards. This element requires the frequency is above the minimum measurable value. If the 5
frequency is below this value, such as when the circuit is de-energized, the trigger will drop out.
• PMU 1 FREQ TRIGGER LOW-FREQ: This setting specifies the low threshold for the abnormal frequency trigger. The
comparator applies a 0.03 Hz hysteresis.
• PMU 1 FREQ TRIGGER HIGH-FREQ: This setting specifies the high threshold for the abnormal frequency trigger. The
comparator applies a 0.03 Hz hysteresis.
• PMU 1 FREQ TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
• PMU 1 FREQ TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
FLEXLOGIC OPERANDS
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER
PMU 1 POWER TRIGGER
PMU 1 TRIGGERED
PMU 1 FREQ TRIGGER SETTING
FUNCTION:
PMU 1 USER TRIGGER:
Enabled = 1
Off = 0
AND
h) VOLTAGE TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 VOLTAGE TRIGGER
This element responds to abnormal voltage. Separate thresholds are provided for low and high voltage. In terms of signal-
ing its operation, the element does not differentiate between the undervoltage and overvoltage events. The trigger
5 responds to the phase voltage signal of the phasor measurement unit (PMU) source. All voltage channels (A, B, and C or
AB, BC, and CA) are processed independently and could trigger the recorder. A minimum voltage supervision of 0.1 pu is
implemented to prevent pickup on a de-energized circuit, similarly to the undervoltage protection element.
• PMU 1 VOLT TRIGGER LOW-VOLT: This setting specifies the low threshold for the abnormal voltage trigger, in per-
unit of the PMU source. 1 pu is a nominal voltage value defined as the nominal secondary voltage times VT ratio. The
comparator applies a 3% hysteresis.
• PMU 1 VOLT TRIGGER HIGH-VOLT: This setting specifies the high threshold for the abnormal voltage trigger, in per-
unit of the PMU source. 1 pu is a nominal voltage value defined as the nominal secondary voltage times VT ratio. The
comparator applies a 3% hysteresis.
• PMU 1 VOLT TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
• PMU 1 VOLT TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
FLEXLOGIC OPERANDS
SETTINGS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER PMU 1 CURR TRIGGER
FUNCTION:
PMU 1 POWER TRIGGER
Enabled = 1
PMU 1 ROCOF TRIGGER FLEXLOGIC OPERAND
AND
PMU 1 VOLT TRIG BLK:
OR
PMU 1 TRIGGERED
Off = 0 SETTING
OR
(V > HIGH-VOLT) tPKP
VB VBC PMU 1 VOLT TRIGGER
(0.1pu < V < LOW-VOLT) OR
VC VCA (V > HIGH-VOLT) tDPO
847005A1.CDR
i) CURRENT TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 CURRENT TRIGGER
This element responds to elevated current. The trigger responds to the phase current signal of the phasor measurement
unit (PMU) source. All current channel (A, B, and C) are processed independently and could trigger the recorder.
• PMU 1 CURR TRIGGER PICKUP: This setting specifies the pickup threshold for the overcurrent trigger, in per unit of
the PMU source. A value of 1 pu is a nominal primary current. The comparator applies a 3% hysteresis.
• PMU 1 CURR TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unneces-
sary triggering of the recorder.
• PMU 1 CURR TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
SETTINGS
PMU 1 POWER TRIGGER
PMU 1 CURR TRIGGER
PMU 1 ROCOF TRIGGER FLEXLOGIC OPERAND
FUNCTION:
OR
PMU 1 TRIGGERED
Enabled = 1 SETTING
PMU 1 CURR TRIG BLK: AND PMU 1 USER TRIGGER:
Off = 0 Off = 0
SETTINGS
SETTINGS SETTINGS
PMU 1 CURR TRIGGER PICKUP:
to STAT bits of
PMU 1 SIGNAL PMU 1 CURR TRIGGER PKP TIME: the data frame
RUN
SOURCE:
PMU 1 CURR TRIGGER DPO TIME:
IA I > PICKUP FLEXLOGIC OPERAND
tPKP
OR
IB I > PICKUP PMU 1 CURR TRIGGER
IC I > PICKUP tDPO
847000A1.CDR
j) POWER TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 POWER TRIGGER
This element responds to abnormal power. Separate thresholds are provided for active, reactive, and apparent powers. In
terms of signaling its operation the element does not differentiate between the three types of power. The trigger responds to
the single-phase and three-phase power signals of the phasor measurement unit (PMU) source.
• PMU 1 POWER TRIGGER ACTIVE: This setting specifies the pickup threshold for the active power of the source. For
single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage,
the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase
power. The comparator applies a 3% hysteresis.
• PMU 1 POWER TRIGGER REACTIVE: This setting specifies the pickup threshold for the reactive power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power. The comparator applies a 3% hysteresis.
• PMU 1 POWER TRIGGER APPARENT: This setting specifies the pickup threshold for the apparent power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power. The comparator applies a 3% hysteresis.
• PMU 1 POWER TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unneces-
sary triggering of the recorder.
• PMU 1 POWER TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to
normal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the
triggering condition is asserted).
SETTINGS
PMU 1 POWER
TRIGGER FUNCTION: FLEXLOGIC OPERANDS
Enabled = 1 PMU 1 FREQ TRIGGER
AND
OR
PMU 1 TRIGGERED
PMU 1 POWER TRIGGER APPARENT: SETTING
SETTINGS
RUN PMU 1 USER TRIGGER:
PMU 1 SIGNAL SOURCE:
Off = 0
ACTIVE POWER, PA abs(P) > ACTIVE PICKUP
ACTIVE POWER, PB abs(P) > ACTIVE PICKUP
SETTINGS
ACTIVE POWER, PC abs(P) > ACTIVE PICKUP to STAT bits of
PMU 1 POWER TRIGGER PKP TIME: the data frame
3P ACTIVE POWER, P abs(P) > 3*(ACTIVE PICKUP)
REACTIVE POWER, QA
REACTIVE POWER, QB
abs(Q) > REACTIVE PICKUP
abs(Q) > REACTIVE PICKUP
PMU 1 POWER TRIGGER DPO TIME:
tPKP
FLEXLOGIC OPERAND 5
OR
k) DF/DT TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 df/dt TRIGGER
This element responds to frequency rate of change. Separate thresholds are provided for rising and dropping frequency.
The trigger responds to the rate of change of frequency (df/dt) of the phasor measurement unit (PMU) source.
5 • PMU 1 df/dt TRIGGER RAISE: This setting specifies the pickup threshold for the rate of change of frequency in the
raising direction (positive df/dt). The comparator applies a 3% hysteresis.
• PMU 1 df/dt TRIGGER FALL: This setting specifies the pickup threshold for the rate of change of frequency in the fall-
ing direction (negative df/dt). The comparator applies a 3% hysteresis.
• PMU 1 df/dt TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
• PMU 1 df/dt TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER
PMU 1 TRIGGERED
PMU 1 df/dt TRIGGER SETTING
FUNCTION:
PMU 1 USER TRIGGER:
Enabled = 1
Off = 0
AND
l) PMU RECORDING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1 ÖØ PMU 1 RECORDING
PMU 1 PMU 1 RECORDING Range: 1, 2, 4, 5, 10, 12, 15, 20, 25, 30, 50, or 60 times
RECORDING RATE: 10/sec per second
Each logical phasor measurement unit (PMU) is associated with a recorder. The triggering condition is programmed via the
PMU 1 TRIGGERING menu. The recorder works with polar values using resolution as in the PMU actual values.
TRIGGER
REC
847709A2.CDR
• PMU 1 TIMED TRIGGER POSITION: This setting specifies the amount of pre-trigger data in percent of the entire
record.
• PMU1 PORT 1 PHS-1 to PMU1 PORT 1 PHS-14: These settings specify synchrophasors to be recorded from the
superset of all synchronized measurements as indicated in the following table. These settings allow for optimizing the
record size and content depending on a given application. Select “Off” to suppress recording of a given value.
VALUE DESCRIPTION
Va First voltage channel, either Va or Vab
Vb Second voltage channel, either Vb or Vbc
Vc Third voltage channel, either Vc or Vca
Vx Fourth voltage channel
Ia Phase A current, physical channel or summation as per the source settings
Ib Phase B current, physical channel or summation as per the source settings
Ic Phase C current, physical channel or summation as per the source settings
Ig Fourth current channel, physical or summation as per the source settings
V1 Positive-sequence voltage, referenced to Va
V2 Negative-sequence voltage, referenced to Va
V0 Zero-sequence voltage
I1 Positive-sequence current, referenced to Ia
I2 Negative-sequence current, referenced to Ia
I0 Zero-sequence current
• PMU 1 REC PHS-1 NM to PMU 1 REC PHS-14 NM: These settings allow for custom naming of the synchrophasor
channels. Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame. Typically
these names would be based on station, bus, or breaker names.
5
• PMU 1 REC A-CH-1 to PMU 1 REC A-CH-8: These settings specify analog data measured by the relay to be included
as a user-selectable analog channel of the record. Up to eight analog channels can be configured to record any Flex-
Analog™ value from the relay. Examples include active and reactive power, per phase or three-phase power, power
factor, temperature via RTD inputs, and THD. The configured analogs are sampled concurrently with the synchropha-
sor instant.
• PMU 1 REC A-CH-1 NM to PMU 1 REC A-CH-8 NM: These settings allow for custom naming of the analog channels.
Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame.
• PMU 1 REC D-CH-1 to PMU 1 REC D-CH-16: These settings specify any digital flag measured by the relay to be
included as a user-selectable digital channel in the record. Up to digital analog channels can be configured to record
any FlexLogic™ operand from the relay. The configured digital flags are sampled concurrently with the synchrophasor
instant.
• PMU 1 REC D-CH-1 NM to PMU 1 REC D-CH-16 NM: This setting allows custom naming of the digital channels. Six-
teen-character ASCII strings are allowed as in the CHNAM field of the configuration frame.
m) NETWORK CONNECTION
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1(4) ÖØ REPORTING OVER NETWORK
To provide maximum flexibility to the user, the arrangement of internal digital logic combines fixed and user-programmed
parameters. Logic upon which individual features are designed is fixed, and all other logic, from digital input signals through
elements or combinations of elements to digital outputs, is variable. The user has complete control of all variable logic
through FlexLogic™. In general, the system receives analog and digital inputs which it uses to produce analog and digital
outputs. The major sub-systems of a generic UR-series relay involved in this process are shown below.
The logic that determines the interaction of inputs, elements, schemes and outputs is field programmable through the use
of logic equations that are sequentially processed. The use of virtual inputs and outputs in addition to hardware is available
internally and on the communication ports for other relays to use (distributed FlexLogic™).
FlexLogic™ allows users to customize the relay through a series of equations that consist of operators and operands. The
operands are the states of inputs, elements, schemes and outputs. The operators are logic gates, timers and latches (with
set and reset inputs). A system of sequential operations allows any combination of specified operands to be assigned as
inputs to specified operators to create an output. The final output of an equation is a numbered register called a virtual out-
put. Virtual outputs can be used as an input operand in any equation, including the equation that generates the output, as a
seal-in or other type of feedback.
A FlexLogic™ equation consists of parameters that are either operands or operators. Operands have a logic state of 1 or 0.
Operators provide a defined function, such as an AND gate or a Timer. Each equation defines the combinations of parame-
ters to be used to set a Virtual Output flag. Evaluation of an equation results in either a 1 (=ON, i.e. flag set) or 0 (=OFF, i.e.
flag not set). Each equation is evaluated at least 4 times every power system cycle.
Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper-
ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different
types of operands are listed in the table below.
The operands available for this relay are listed alphabetically by types in the following table.
Table 5–9: G60 FLEXLOGIC™ OPERANDS (Sheet 1 of 9)
OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed
PUSHBUTTONS CONTROL PUSHBTN 2 ON Control pushbutton 2 is being pressed
CONTROL PUSHBTN 3 ON Control pushbutton 3 is being pressed
CONTROL PUSHBTN 4 ON Control pushbutton 4 is being pressed
CONTROL PUSHBTN 5 ON Control pushbutton 5 is being pressed
CONTROL PUSHBTN 6 ON Control pushbutton 6 is being pressed
CONTROL PUSHBTN 7 ON Control pushbutton 7 is being pressed
DIRECT DEVICES DIRECT DEVICE 1On Flag is set, logic=1
↓ ↓
DIRECT DEVICE 16On Flag is set, logic=1
DIRECT DEVICE 1Off Flag is set, logic=1
↓ ↓
DIRECT DEVICE 16Off Flag is set, logic=1
DIRECT INPUT/ DIR IO CH1 CRC ALARM The rate of direct input messages received on channel 1 and failing the CRC
OUTPUT exceeded the user-specified level.
CHANNEL DIR IO CH2 CRC ALARM The rate of direct input messages received on channel 2 and failing the CRC
MONITORING exceeded the user-specified level.
DIR IO CH1 UNRET ALM The rate of returned direct input/output messages on channel 1 exceeded the
user-specified level (ring configurations only).
DIR IO CH2 UNRET ALM The rate of returned direct input/output messages on channel 2 exceeded the
user-specified level (ring configurations only).
ELEMENT: 100% STATOR STG1 PKP Stage 1 of the 100% stator ground element has picked up
100% stator ground 100% STATOR STG1 OP Stage 1 of the 100% stator ground element has operated
100% STATOR STG1 DPO Stage 1 of the 100% stator ground element has dropped out
100% STATOR STG2 PKP Stage 2 of the 100% stator ground element has picked up
100% STATOR STG2 OP Stage 2 of the 100% stator ground element has operated
100% STATOR STG2 DPO Stage 2 of the 100% stator ground element has dropped out
100% STATOR PKP The 100% stator ground element has picked up
100% STATOR OP
100% STATOR DPO
The 100% stator ground element has operated
The 100% stator ground element has dropped out
5
ELEMENT: 3RD HARM NTRL UV PKP Third harmonic neutral undervoltage element has picked up
Third harmonic 3RD HARM NTRL UV OP Third harmonic neutral undervoltage element has operated
neutral undervoltage 3RD HARM NTRL UV DPO Third harmonic neutral undervoltage element has dropped out
ELEMENT: ACCDNT ENRG ARMED The accidental energization element is armed
Accidental ACCDNT ENRG DPO The accidental energization element has dropped out
energization ACCDNT ENRG OP The accidental energization element has operated
ELEMENT: AUX OV1 PKP Auxiliary overvoltage element has picked up
Auxiliary AUX OV1 DPO Auxiliary overvoltage element has dropped out
overvoltage AUX OV1 OP Auxiliary overvoltage element has operated
AUX OV2 to AUX OV3 Same set of operands as shown for AUX OV1
ELEMENT: AUX UV1 PKP Auxiliary undervoltage element has picked up
Auxiliary AUX UV1 DPO Auxiliary undervoltage element has dropped out
undervoltage AUX UV1 OP Auxiliary undervoltage element has operated
AUX UV2 to AUX UV3 Same set of operands as shown for AUX UV1
RESETTING RESET OP Reset command is operated (set by all three operands below).
RESET OP (COMMS) Communications source of the reset command.
RESET OP (OPERAND) Operand (assigned in the INPUTS/OUTPUTS ÖØ RESETTING menu) source
of the reset command.
RESET OP (PUSHBUTTON) Reset key (pushbutton) source of the reset command.
SELF- ANY MAJOR ERROR Any of the major self-test errors generated (major error)
DIAGNOSTICS ANY MINOR ERROR Any of the minor self-test errors generated (minor error)
ANY SELF-TESTS
BATTERY FAIL
Any self-test errors generated (generic, any error)
See description in Chapter 7: Commands and targets 5
DIRECT DEVICE OFF See description in Chapter 7: Commands and targets
DIRECT RING BREAK See description in Chapter 7: Commands and targets
EQUIPMENT MISMATCH See description in Chapter 7: Commands and targets
ETHERNET SWITCH FAIL See description in Chapter 7: Commands and targets
FLEXLOGIC ERR TOKEN See description in Chapter 7: Commands and targets
IRIG-B FAILURE See description in Chapter 7: Commands and targets
LATCHING OUT ERROR See description in Chapter 7: Commands and targets
MAINTENANCE ALERT See description in Chapter 7: Commands and targets
PORT 1 OFFLINE See description in Chapter 7: Commands and targets
PORT 2 OFFLINE See description in Chapter 7: Commands and targets
PORT 3 OFFLINE See description in Chapter 7: Commands and targets
PORT 4 OFFLINE See description in Chapter 7: Commands and targets
PORT 5 OFFLINE See description in Chapter 7: Commands and targets
PORT 6 OFFLINE See description in Chapter 7: Commands and targets
PRI ETHERNET FAIL See description in Chapter 7: Commands and targets
PROCESS BUS FAILURE See description in Chapter 7: Commands and targets
REMOTE DEVICE OFF See description in Chapter 7: Commands and targets
RRTD COMM FAIL See description in Chapter 7: Commands and targets
SEC ETHERNET FAIL See description in Chapter 7: Commands and targets
SNTP FAILURE See description in Chapter 7: Commands and targets
SYSTEM EXCEPTION See description in Chapter 7: Commands and targets
TEMP MONITOR See description in Chapter 7: Commands and targets
UNIT NOT PROGRAMMED See description in Chapter 7: Commands and targets
TEMPERATURE TEMP MONITOR Asserted while the ambient temperature is greater than the maximum
MONITOR operating temperature (80°C)
USER- PUSHBUTTON 1 ON Pushbutton number 1 is in the “On” position
PROGRAMMABLE PUSHBUTTON 1 OFF Pushbutton number 1 is in the “Off” position
PUSHBUTTONS ANY PB ON Any of twelve pushbuttons is in the “On” position
PUSHBUTTON 2 to 12 Same set of operands as PUSHBUTTON 1
Some operands can be re-named by the user. These are the names of the breakers in the breaker control feature, the ID
(identification) of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name
or ID of any of these operands, the assigned name will appear in the relay list of operands. The default names are shown in
the FlexLogic™ operands table above.
The characteristics of the logic gates are tabulated below, and the operators available in FlexLogic™ are listed in the Flex-
Logic™ operators table.
When forming a FlexLogic™ equation, the sequence in the linear array of parameters must follow these general rules:
1. Operands must precede the operator which uses the operands as inputs.
2. Operators have only one output. The output of an operator must be used to create a virtual output if it is to be used as
an input to two or more operators.
3. Assigning the output of an operator to a virtual output terminates the equation.
4. A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") may only be used
once. If this rule is broken, a syntax error will be declared.
Each equation is evaluated in the order in which the parameters have been entered.
FlexLogic™ provides latches which by definition have a memory action, remaining in the set state after the
set input has been asserted. However, they are volatile; that is, they reset on the re-application of control
NOTE power.
When making changes to settings, all FlexLogic™ equations are re-compiled whenever any new setting
value is entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic™ during
testing, for example, it is suggested to power the unit down and then back up.
This section provides an example of implementing logic for a typical application. The sequence of the steps is quite impor-
tant as it should minimize the work necessary to develop the relay settings. Note that the example presented in the figure
below is intended to demonstrate the procedure, not to solve a specific application situation.
In the example below, it is assumed that logic has already been programmed to produce virtual outputs 1 and 2, and is only
a part of the full set of equations used. When using FlexLogic™, it is important to make a note of each virtual output used –
a virtual output designation (1 to 96) can only be properly assigned once.
VIRTUAL OUTPUT 1
State=ON
VIRTUAL OUTPUT 2
Set
State=ON
LATCH
OR #1 Reset
VIRTUAL INPUT 1
State=ON
XOR
Timer 2 5
Time Delay Operate Output
OR #2
DIGITAL ELEMENT 1 on Dropout Relay H1
State=Pickup
(200 ms)
Therefore, the required logic can be implemented with two FlexLogic™ equations with outputs of virtual output 3 and
virtual output 4 as shown below.
VIRTUAL OUTPUT 1
State=ON
VIRTUAL OUTPUT 2
Set
State=ON
LATCH
VIRTUAL INPUT 1 OR #1 Reset
State=ON Timer 2
XOR Time Delay
OR #2 VIRTUAL OUTPUT 4
DIGITAL ELEMENT 1 on Dropout
State=Pickup (200 ms)
827026A2.VSD
DIGITAL ELEMENT 2
State=Operated
827027A2.VSD
VIRTUAL OUTPUT 1
State=ON
VIRTUAL OUTPUT 2
Set
State=ON
LATCH
VIRTUAL INPUT 1 OR #1 Reset
State=ON Timer 2
XOR Time Delay VIRTUAL
OR #2
DIGITAL ELEMENT 1 on Dropout OUTPUT 4
State=Pickup
(200 ms)
Timer 1
VIRTUAL OUTPUT 3 Time Delay
State=ON on Pickup
(800 ms)
CONTACT INPUT H1c
State=Closed 827028A2.VSD
01
02
03
04
05
.....
97
98
99
827029A1.VSD
97: The operator preceding timer 2 is OR #2, a 3-input OR, which is parameter “OR(3)”.
96: The lowest input to OR #2 is operand “Cont Ip H1c On”.
95: The center input to OR #2 is operand “TIMER 1".
94: The input to timer 1 is operand “Virt Op 3 On".
93: The upper input to OR #2 is operand “LATCH (S,R)”.
92: There are two inputs to a latch, and the input immediately preceding the latch reset is OR #1, a 4-input OR, which
is parameter “OR(4)”.
91: The lowest input to OR #1 is operand “Virt Op 3 On".
90: The input just above the lowest input to OR #1 is operand “XOR(2)”.
89: The lower input to the XOR is operand “DIG ELEM 1 PKP”.
88: The upper input to the XOR is operand “Virt Ip 1 On".
87: The input just below the upper input to OR #1 is operand “Virt Op 2 On".
86: The upper input to OR #1 is operand “Virt Op 1 On".
85: The last parameter is used to set the latch, and is operand “Virt Op 4 On".
The equation for virtual output 4 is:
[85] Virt Op 4 On
[86] Virt Op 1 On
[87] Virt Op 2 On
[88] Virt Ip 1 On
5 [89]
[90]
DIG ELEM 1 PKP
XOR(2)
[91] Virt Op 3 On
[92] OR(4)
[93] LATCH (S,R)
[94] Virt Op 3 On
[95] TIMER 1
[96] Cont Ip H1c On
[97] OR(3)
[98] TIMER 2
[99] = Virt Op 4
It is now possible to check that the selection of parameters will produce the required logic by converting the set of parame-
ters into a logic diagram. The result of this process is shown below, which is compared to the logic for virtual output 4 dia-
gram as a check.
FLEXLOGIC ENTRY n:
85 Virt Op 4 On
FLEXLOGIC ENTRY n:
86 Virt Op 1 On
FLEXLOGIC ENTRY n:
87 Virt Op 2 On
Set
FLEXLOGIC ENTRY n:
88 Virt Ip 1 On
LATCH
XOR OR Reset
FLEXLOGIC ENTRY n:
89 DIG ELEM 1 PKP
FLEXLOGIC ENTRY n:
90 XOR
FLEXLOGIC ENTRY n:
91 Virt Op 3 On VIRTUAL
OR T2
FLEXLOGIC ENTRY n: OUTPUT 4
92 OR (4)
FLEXLOGIC ENTRY n:
93 LATCH (S,R)
FLEXLOGIC ENTRY n:
94 Virt Op 3 On T1
FLEXLOGIC ENTRY n:
95 TIMER 1
FLEXLOGIC ENTRY n:
96 Cont Ip H1c On
FLEXLOGIC ENTRY n:
97 OR (3)
FLEXLOGIC ENTRY n:
98 TIMER 2
FLEXLOGIC ENTRY n:
99 =Virt Op 4 827031A2.VSD
8. The logic should always be tested after it is loaded into the relay, in the same fashion as has been used in the past.
Testing can be simplified by placing an "END" operator within the overall set of FlexLogic™ equations. The equations
will then only be evaluated up to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.
There are 512 FlexLogic™ entries available, numbered from 1 to 512, with default END entry settings. If a "Disabled" Ele-
ment is selected as a FlexLogic™ entry, the associated state flag will never be set to ‘1’. The ‘+/–‘ key may be used when
editing FlexLogic™ equations from the keypad to quickly scan through the major parameter types.
There are 32 identical FlexLogic™ timers available. These timers can be used as operators for FlexLogic™ equations.
• TIMER 1 TYPE: This setting is used to select the time measuring unit.
• TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0".
• TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0".
5.5.7 FLEXELEMENTS™
A FlexElement™ is a universal comparator that can be used to monitor any analog actual value calculated by the relay or a
net difference of any two analog actual values of the same type. The effective operating signal could be treated as a signed
number or its absolute value could be used as per user's choice.
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period
of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as
per user's choice.
SETTING
SETTINGS
FLEXELEMENT 1
FUNCTION: FLEXELEMENT 1 INPUT
MODE:
Enabled = 1
FLEXELEMENT 1 COMP
MODE:
Disabled = 0
FLEXELEMENT 1
DIRECTION:
SETTING
FLEXELEMENT 1 PICKUP:
FLEXELEMENT 1 BLK:
FLEXELEMENT 1 INPUT
AND HYSTERESIS:
Off = 0
FLEXELEMENT 1 dt UNIT: SETTINGS
FxE 1 PKP
ACTUAL VALUE
The FLEXELEMENT 1 DIRECTION setting enables the relay to respond to either high or low values of the operating signal. The
following figure explains the application of the FLEXELEMENT 1 DIRECTION, FLEXELEMENT 1 PICKUP and FLEXELEMENT 1 HYS-
TERESIS settings.
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over
HYSTERESIS = % of PICKUP
FlexElement 1 OpSig
PICKUP
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under
HYSTERESIS = % of PICKUP
FlexElement 1 OpSig
PICKUP
842705A1.CDR
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
5
MODE = Signed;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Absolute;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Signed;
FlexElement 1 OpSig
FLEXELEMENT 1 PKP
FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Absolute;
FlexElement 1 OpSig
842706A2.CDR
The FLEXELEMENT 1 PICKUP setting specifies the operating threshold for the effective operating signal of the element. If set
to “Over”, the element picks up when the operating signal exceeds the FLEXELEMENT 1 PICKUP value. If set to “Under”, the
element picks up when the operating signal falls below the FLEXELEMENT 1 PICKUP value.
The FLEXELEMENT 1 HYSTERESIS setting controls the element dropout. It should be noticed that both the operating signal
and the pickup threshold can be negative facilitating applications such as reverse power alarm protection. The FlexEle-
ment™ can be programmed to work with all analog actual values measured by the relay. The FLEXELEMENT 1 PICKUP set-
ting is entered in per-unit values using the following definitions of the base units:
The FLEXELEMENT 1 HYSTERESIS setting defines the pickup–dropout relation of the element by specifying the width of the
hysteresis loop as a percentage of the pickup value as shown in the FlexElement™ direction, pickup, and hysteresis dia-
gram.
The FLEXELEMENT 1 DT UNIT setting specifies the time unit for the setting FLEXELEMENT 1 dt. This setting is applicable only if
FLEXELEMENT 1 COMP MODE is set to “Delta”. The FLEXELEMENT 1 DT setting specifies duration of the time interval for the
rate of change mode of operation. This setting is applicable only if FLEXELEMENT 1 COMP MODE is set to “Delta”.
This FLEXELEMENT 1 PKP DELAY setting specifies the pickup delay of the element. The FLEXELEMENT 1 RST DELAY setting
specifies the reset delay of the element.
The non-volatile latches provide a permanent logical flag that is stored safely and will not reset upon reboot after the relay
5
is powered down. Typical applications include sustaining operator commands or permanently block relay functions, such as
Autorecloser, until a deliberate interface action resets the latch. The settings element operation is described below:
• LATCH 1 TYPE: This setting characterizes Latch 1 to be Set- or Reset-dominant.
• LATCH 1 SET: If asserted, the specified FlexLogic™ operands 'sets' Latch 1.
• LATCH 1 RESET: If asserted, the specified FlexLogic™ operand 'resets' Latch 1.
SETTING
SETTING
LATCH N LATCH N LATCH N LATCH N LATCH N LATCH 1 FUNCTION:
TYPE SET RESET ON OFF
LATCH 1 TYPE:
Reset ON OFF ON OFF Disabled=0
Dominant Enabled=1 RUN
OFF OFF Previous Previous
State State
ON ON OFF ON SETTING
Each protection element can be assigned up to six different sets of settings according to setting group designations 1 to 6.
The performance of these elements is defined by the active setting group at a given time. Multiple setting groups allow the
user to conveniently change protection settings for different operating situations (for example, altered power system config-
uration, season of the year, etc.). The active setting group can be preset or selected via the SETTING GROUPS menu (see the
Control elements section later in this chapter). See also the Introduction to elements section at the beginning of this chap-
ter.
Each of the six setting group menus is identical. Setting group 1 (the default active group) automatically becomes active if
no other group is active (see the Control elements section for additional details).
5.6.3 DISTANCE
a) MAIN MENU
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE
Four common settings are available for distance protection. The DISTANCE SOURCE identifies the signal source for all dis-
tance functions. The mho distance functions use a dynamic characteristic: the positive-sequence voltage – either memo-
rized or actual – is used as a polarizing signal. The memory voltage is also used by the built-in directional supervising
functions applied for both the mho and quad characteristics.
5
The MEMORY DURATION setting specifies the length of time a memorized positive-sequence voltage should be used in the
distance calculations. After this interval expires, the relay checks the magnitude of the actual positive-sequence voltage. If
it is higher than 10% of the nominal, the actual voltage is used, if lower – the memory voltage continues to be used.
The memory is established when the positive-sequence voltage stays above 80% of its nominal value for five power system
cycles. For this reason it is important to ensure that the nominal secondary voltage of the VT is entered correctly under the
SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE BANK menu.
Set MEMORY DURATION long enough to ensure stability on close-in reverse three-phase faults. For this purpose, the maxi-
mum fault clearing time (breaker fail time) in the substation should be considered. On the other hand, the MEMORY DURA-
TION cannot be too long as the power system may experience power swing conditions rotating the voltage and current
phasors slowly while the memory voltage is static, as frozen at the beginning of the fault. Keeping the memory in effect for
too long may eventually lead to incorrect operation of the distance functions.
The distance zones can be forced to become self-polarized through the FORCE SELF-POLAR setting. Any user-selected con-
dition (FlexLogic™ operand) can be configured to force self-polarization. When the selected operand is asserted (logic 1),
the distance functions become self-polarized regardless of other memory voltage logic conditions. When the selected oper-
and is de-asserted (logic 0), the distance functions follow other conditions of the memory voltage logic as shown below.
The distance zones can be forced to become memory-polarized through the FORCE MEM-POLAR setting. Any user-selected
condition (any FlexLogic™ operand) can be configured to force memory polarization. When the selected operand is
asserted (logic 1), the distance functions become memory-polarized regardless of the positive-sequence voltage magni-
tude at this time. When the selected operand is de-asserted (logic 0), the distance functions follow other conditions of the
memory voltage logic.
The FORCE SELF-POLAR and FORCE MEM-POLAR settings should never be asserted simultaneously. If this happens, the logic
will give higher priority to forcing self-polarization as indicated in the logic below. This is consistent with the overall philoso-
phy of distance memory polarization.
The memory polarization cannot be applied permanently but for a limited time only; the self-polarization may be
applied permanently and therefore should take higher priority.
NOTE
SETTING
Force Memory Polarization
Update memory
Off = 0
AND RUN
SETTING
Memory duration
SETTING TIMER 0
Distance Source | V_1 | < 1.15 pu 5 cycles AND
= VA, Vrms_A | Vrms – | V | | < Vrms / 8 AND Treset
S Q
= VB, Vrms_B | Vrms – | V | | < Vrms / 8 0 AND
= VC, Vrms_C | Vrms – | V | | < Vrms / 8
= V_1 | V_1 | > 0.80 pu TIMER Use V_1 memory
6 cycles OR
= IA | IA | < 0.05 pu
| IB | < 0.05 pu
AND
R Use V_1
= IB OR
0
= IC | IC | < 0.05 pu AND
| V_1 | < 0.10 pu
SETTING
Force Self Polarization
Off = 0 827842A7.CDR
b) PHASE DISTANCE
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE ÖØ PHASE DISTANCE Z1(Z3)
5 MESSAGE
PHS DIST Z1
SHAPE: Mho
Range: Mho. This value is fixed and cannot be changed.
PHS DIST Z1 XFMR VOL Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1, Yd3,
MESSAGE Yd5, Yd7, Yd9, Yd11
CONNECTION: None
PHS DIST Z1 XFMR CUR Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1, Yd3,
MESSAGE Yd5, Yd7, Yd9, Yd11
CONNECTION: None
PHS DIST Z1 Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
REACH: 2.00 ohms
PHS DIST Z1 Range: 30 to 90° in steps of 1
MESSAGE
RCA: 85°
PHS DIST Z1 REV Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
REACH: 2.00 ohms
PHS DIST Z1 REV Range: 30 to 90° in steps of 1
MESSAGE
REACH RCA: 85°
PHS DIST Z1 Range: 30 to 90° in steps of 1
MESSAGE
COMP LIMIT: 90°
PHS DIST Z1 Range: 30 to 90° in steps of 1
MESSAGE
DIR RCA: 85°
PHS DIST Z1 Range: 30 to 90° in steps of 1
MESSAGE
DIR COMP LIMIT: 90°
PHS DIST Z1 Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
SUPV: 0.200 pu
PHS DIST Z1 VOLT Range: 0.000 to 5.000 pu in steps of 0.001
MESSAGE
LEVEL: 0.000 pu
PHS DIST Z1 Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.000 s
The phase mho distance function uses a dynamic 100% memory-polarized mho characteristic with additional reactance,
directional, and overcurrent supervising characteristics. When set to “Non-directional”, the mho function becomes an offset
mho with the reverse reach controlled independently from the forward reach, and all the directional characteristics
removed.
Each phase distance zone is configured individually through its own setting menu. All of the settings can be independently
modified for each of the zones except:
1. The SIGNAL SOURCE setting (common for the distance elements of all zones as entered under SETTINGS ÖØ GROUPED
ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE).
2. The MEMORY DURATION setting (common for the distance elements of all zones as entered under SETTINGS ÖØ
GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE).
The common distance settings described earlier must be properly chosen for correct operation of the phase distance ele-
ments. Additional details may be found in chapter 8: Theory of operation.
Ensure that the PHASE VT SECONDARY VOLTAGE setting (see the SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ
VOLTAGE BANK menu) is set correctly to prevent improper operation of associated memory action.
WARNING
• PHS DIST Z1 DIR: All phase distance zones are reversible. The forward direction is defined by the PHS DIST Z1 RCA 5
setting, whereas the reverse direction is shifted 180° from that angle. The non-directional zone spans between the for-
ward reach impedance defined by the PHS DIST Z1 REACH and PHS DIST Z1 RCA settings, and the reverse reach imped-
ance defined by PHS DIST Z1 REV REACH and PHS DIST Z1 REV REACH RCA as illustrated below.
COMP LIMIT
DIR RCA
RCA
837720A1.CDR
COMP LIMIT
R E AC H
RCA
REV REACH
RCA
HE AC
REV R
837802A1.CDR
X X
5
RCA = 80o RCA = 80o
COMP LIMIT = 90o COMP LIMIT = 90o
DIR RCA = 80o DIR RCA = 80o
DIR COMP LIMIT = 90o DIR COMP LIMIT = 60o
H
H
REAC
REAC
R R
H
REAC
R R
837722A1.CDR
This setting specifies the location of the voltage source with respect to the involved power transformer in the direction
of the zone. The following figure illustrates the usage of this setting. In section (a), zone 1 is looking through a trans-
former from the delta into the wye winding. Therefore, the Z1 setting shall be set to “Dy11”. In section (b), Zone 3 is
looking through a transformer from the wye into the delta winding. Therefore, the Z3 setting shall be set to “Yd1”. The
zone is restricted by the potential point (location of the VTs) as illustrated in Figure (e).
• PHS DIST Z1 XFMR CUR CONNECTION: This setting specifies the location of the current source with respect to the
involved power transformer in the direction of the zone. In section (a) of the following figure, zone 1 is looking through
a transformer from the delta into the wye winding. Therefore, the Z1 setting shall be set to “Dy11”. In section (b), the
CTs are located at the same side as the read point. Therefore, the Z3 setting shall be set to “None”.
See the Theory of operation chapter for more details, and the Application of settings chapter for information on calcu-
lating distance reach settings in applications involving power transformers.
(a) (b)
delta wye, 330o lag delta wye, 330o lag
Z3 Z3
Z1 Z1
5
(c) (e)
delta wye, 330o lag
L1 L2
Z3 Zone 3
Zone 1
Z3 XFRM VOL CONNECTION = None
Z3 XFRM CUR CONNECTION = Yd1 ZL1 ZT ZL2
Z1
• PHS DIST Z1 REV REACH RCA: This setting defines the angle of the reverse reach impedance if the zone is set to
non-directional (PHS DIST Z1 DIR setting). This setting does not apply when the zone direction is set to “Forward” or
“Reverse”.
• PHS DIST Z1 COMP LIMIT: This setting shapes the operating characteristic, producing the lens-type characteristic of
the mho function. The same limit angle applies to both the mho and supervising reactance comparators. This setting
improves loadability of the protected line.
• PHS DIST Z1 DIR RCA: This setting selects the characteristic angle (or maximum torque angle) of the directional
supervising function. The directional function is an extra supervising function as the dynamic mho characteristic itself is
a directional one. The directional function uses the memory voltage for polarization. This setting typically equals the
distance characteristic angle PHS DIST Z1 RCA.
• PHS DIST Z1 DIR COMP LIMIT: Selects the comparator limit angle for the directional supervising function.
• PHS DIST Z1 SUPV: The phase distance elements are supervised by the magnitude of the line-to-line current (fault
loop current used for the distance calculations). For convenience, 3 is accommodated by the pickup (that is, before
being used, the entered value of the threshold setting is multiplied by 3 ).
If the minimum fault current level is sufficient, the current supervision pickup should be set above maximum full load
current preventing maloperation under VT fuse fail conditions. This requirement may be difficult to meet for remote
faults at the end of zones 2 and above. If this is the case, the current supervision pickup would be set below the full
load current, but this may result in maloperation during fuse fail conditions.
• PHS DIST Z1 VOLT LEVEL: This setting is relevant for applications on series-compensated lines, or in general, if
series capacitors are located between the relaying point and a point where the zone shall not overreach. For plain
(non-compensated) lines, set to zero. Otherwise, the setting is entered in per unit of the phase VT bank configured
under the DISTANCE SOURCE. Effectively, this setting facilitates dynamic current-based reach reduction. In non-direc-
tional applications (PHS DIST Z1 DIR set to “Non-directional”), this setting applies only to the forward reach of the non-
5 directional zone. See chapters 8 and 9 for information on calculating this setting for series compensated lines.
• PHS DIST Z1 DELAY: This setting allows the user to delay operation of the distance elements and implement stepped
distance protection. The distance element timers for zones 2 and higher apply a short dropout delay to cope with faults
located close to the zone boundary when small oscillations in the voltages or currents could inadvertently reset the
timer. Zone 1 does not need any drop out delay since it is sealed-in by the presence of current.
• PHS DIST Z1 BLK: This setting enables the user to select a FlexLogic™ operand to block a given distance element.
VT fuse fail detection is one of the applications for this setting.
AND
OR
SETTING
PH DIST Z1 DELAY AND FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND TPKP OR OR PH DIST Z1 OP
PH DIST Z1 PKP AB
0
FLEXLOGIC OPERAND TPKP
PH DIST Z1 PKP BC
0 AND
FLEXLOGIC OPERAND TPKP OR
PH DIST Z1 PKP CA
0 FLEXLOGIC OPERANDS
PH DIST Z1 OP AB
PH DIST Z1 OP BC
AND
FLEXLOGIC OPERANDS PH DIST Z1 OP CA
PH DIST Z1 SUPN IAB
AND
PH DIST Z1 SUPN IBC
PH DIST Z1 SUPN ICA
AND
OPEN POLE OP **
** D60, L60, and L90 only. Other UR-series models apply regular current seal-in for zone 1. 837017A8.CDR
from the open pole element (D60, L60, and L90 only)
FLEXLOGIC OPERAND
OPEN POLE OP
FLEXLOGIC OPERAND
TIMER FLEXLOGIC OPERAND
PH DIST Z2 PKP CA SETTING
0 ms AND AND PH DIST Z2 OP CA
PH DIST Z2 DELAY
OR
from the trip output element OR
TPKP
20 ms
FLEXLOGIC OPERAND 0
FLEXLOGIC OPERAND
TRIP Z2 PH TMR INIT
OR PH DIST Z2 OP
837036A1.CDR
FLEXLOGIC OPERAND
OPEN POLE OP **
5
TIMER SETTING
FLEXLOGIC OPERAND 0 ms PH DIST Z3 DELAY
AND
PH DIST Z3 PKP AB TPKP FLEXLOGIC OPERAND
20 ms OR PH DIST Z3 OP AB
0
TIMER SETTING
FLEXLOGIC OPERAND 0 ms PH DIST Z3 DELAY
AND
PH DIST Z3 PKP BC TPKP FLEXLOGIC OPERAND
20 ms OR PH DIST Z3 OP BC
0
TIMER SETTING
FLEXLOGIC OPERAND 0 ms PH DIST Z3 DELAY
AND
PH DIST Z3 PKP CA TPKP FLEXLOGIC OPERAND
20 ms OR PH DIST Z3 OP CA
0
FLEXLOGIC OPERAND
OR PH DIST Z3 OP
SETTINGS
PH DIST Z1 DIR
PH DIST Z1 SHAPE
PH DIST Z1 XFMR
VOL CONNECTION
SETTING PH DIST Z1 XFMR
PH DIST Z1 FUNCTION CUR CONNECTION
Enabled = 1 PH DIST Z1 REACH
Disabled = 0 PH DIST Z1 RCA
PH DIST Z1 REV REACH
AND PH DIST Z1 REV REACH RCA
SETTING
PH DIST Z1 COMP LIMIT
PH DIST Z1 BLK
PH DIST Z1 QUAD RGT BLD
Off = 0
PH DIST Z1 QUAD RGT BLD RCA Quadrilateral
PH DIST Z1 QUAD LFT BLD characteristic only
PH DIST Z1 QUAD LFT BLD RCA
SETTING PH DIST Z1 VOLT LEVEL FLEXLOGIC OPERANDS
DISTANCE SOURCE RUN AND PH DIST Z1 PKP AB
IA-IB PH DIST Z1 DPO AB
A-B ELEMENT
IB-IC
IC-IA RUN FLEXLOGIC OPERANDS
VAG-VBG B-C ELEMENT AND PH DIST Z1 PKP BC
Wye
VTs
SETTING
PHS DIST Z1 SUPV
RUN FLEXLOGIC OPERAND
| IA – IB | > 3 × Pickup PH DIST Z1 SUPN IAB
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ POWER SWING DETECT
The power swing detect element provides both power swing blocking and out-of-step tripping functions. The element mea-
sures the positive-sequence apparent impedance and traces its locus with respect to either two or three user-selectable
operating characteristic boundaries. Upon detecting appropriate timing relations, the blocking and tripping indications are
given through FlexLogic™ operands. The element incorporates an adaptive disturbance detector. This function does not
trigger on power swings, but is capable of detecting faster disturbances – faults in particular – that may occur during power
swings. Operation of this dedicated disturbance detector is signaled via the POWER SWING 50DD operand.
The power swing detect element asserts two outputs intended for blocking selected protection elements on power swings:
POWER SWING BLOCK is a traditional signal that is safely asserted for the entire duration of the power swing, and POWER
SWING UN/BLOCK is established in the same way, but resets when an extra disturbance is detected during the power swing.
The POWER SWING UN/BLOCK operand may be used for blocking selected protection elements if the intent is to respond to
faults during power swing conditions.
Different protection elements respond differently to power swings. If tripping is required for faults during power swing condi-
tions, some elements may be blocked permanently (using the POWER SWING BLOCK operand), and others may be blocked
and dynamically unblocked upon fault detection (using the POWER SWING UN/BLOCK operand).
The operating characteristic and logic figures should be viewed along with the following discussion to develop an under-
standing of the operation of the element.
The power swing detect element operates in three-step or two-step mode:
• Three-step operation: The power swing blocking sequence essentially times the passage of the locus of the positive-
sequence impedance between the outer and the middle characteristic boundaries. If the locus enters the outer charac-
teristic (indicated by the POWER SWING OUTER FlexLogic™ operand) but stays outside the middle characteristic (indi-
cated by the POWER SWING MIDDLE FlexLogic™ operand) for an interval longer than POWER SWING PICKUP DELAY 1,
the power swing blocking signal (POWER SWING BLOCK FlexLogic™ operand) is established and sealed-in. The block-
ing signal resets when the locus leaves the outer characteristic, but not sooner than the POWER SWING RESET DELAY 1
time.
• Two-step operation: If the two-step mode is selected, the sequence is identical, but it is the outer and inner character-
istics that are used to time the power swing locus.
The out-of-step tripping feature operates as follows for three-step and two-step power swing detection modes:
• Three-step operation: The out-of-step trip sequence identifies unstable power swings by determining if the imped-
ance locus spends a finite time between the outer and middle characteristics and then a finite time between the middle
and inner characteristics. The first step is similar to the power swing blocking sequence. After timer POWER SWING
PICKUP DELAY 1 times out, latch 1 is set as long as the impedance stays within the outer characteristic.
If afterwards, at any time (given the impedance stays within the outer characteristic), the locus enters the middle char-
acteristic but stays outside the inner characteristic for a period of time defined as POWER SWING PICKUP DELAY 2, latch
2 is set as long as the impedance stays inside the outer characteristic. If afterwards, at any time (given the impedance
stays within the outer characteristic), the locus enters the inner characteristic and stays there for a period of time
defined as POWER SWING PICKUP DELAY 3, latch 2 is set as long as the impedance stays inside the outer characteristic;
the element is now ready to trip.
If the "Early" trip mode is selected, the POWER SWING TRIP operand is set immediately and sealed-in for the interval
set by the POWER SWING SEAL-IN DELAY. If the "Delayed" trip mode is selected, the element waits until the impedance
locus leaves the inner characteristic, then times out the POWER SWING PICKUP DELAY 2 and sets Latch 4; the element is
now ready to trip. The trip operand is set later, when the impedance locus leaves the outer characteristic.
• Two-step operation: The two-step mode of operation is similar to the three-step mode with two exceptions. First, the
initial stage monitors the time spent by the impedance locus between the outer and inner characteristics. Second, the
stage involving the POWER SWING PICKUP DELAY 2 timer is bypassed. It is up to the user to integrate the blocking
(POWER SWING BLOCK) and tripping (POWER SWING TRIP) FlexLogic™ operands with other protection functions and
output contacts in order to make this element fully operational.
The element can be set to use either lens (mho) or rectangular (quadrilateral) characteristics as illustrated below. When set
to “Mho”, the element applies the right and left blinders as well. If the blinders are not required, their settings should be set
high enough to effectively disable the blinders.
5
X
R
TE
OU
ACH
E
DL
FWD RE
ID
M
R
NE
IN
FW
LE
DR
NG
TA
CA
E I
GL LIM
AN LE
R
RE
IT DD
LIM MI
VR
R
CA
E
INN
H
REV REAC
827843A2.CDR
842734A1.CDR
INNER LFT BL
D INNER RGT BL
D
MIDDLE LFT BL
ACH OUT
ACH MID
D MIDDLE RGT
BLD
OUTER LFT BL
D OUTER RGT BL
D
QUAD FWD RE
QUAD FWD RE
FWD REACH
FWD RCA
R
CH MID
REV REACH
H OUT
QUAD REV REA
AC
QUAD REV RE
842735A1.CDR
• The POWER SWING UN/BLOCK FlexLogic™ operand shall be used to block those protection elements that are intended
to be blocked under power swings, but subsequently unblocked should a fault occur after the power swing blocking
condition has been established.
• The POWER SWING 50DD FlexLogic™ operand indicates that an adaptive disturbance detector integrated with the ele-
ment has picked up. This operand will trigger on faults occurring during power swing conditions. This includes both
three-phase and single-pole-open conditions.
• The POWER SWING INCOMING FlexLogic™ operand indicates an unstable power swing with an incoming locus (the
locus enters the inner characteristic).
• The POWER SWING OUTGOING FlexLogic™ operand indicates an unstable power swing with an outgoing locus (the
locus leaving the outer characteristic). This operand can be used to count unstable swings and take certain action only
after pre-defined number of unstable power swings.
• The POWER SWING TRIP FlexLogic™ operand is a trip command.
The settings for the power swing detect element are described below:
• POWER SWING FUNCTION: This setting enables and disables the entire power swing detection element. The setting
applies to both power swing blocking and out-of-step tripping functions.
• POWER SWING SOURCE: The source setting identifies the signal source for both blocking and tripping functions.
• POWER SWING SHAPE: This setting selects the shapes (either “Mho” or “Quad”) of the outer, middle and, inner char-
acteristics of the power swing detect element. The operating principle is not affected. The “Mho” characteristics use the
left and right blinders.
• POWER SWING MODE: This setting selects between the two-step and three-step operating modes and applies to
both power swing blocking and out-of-step tripping functions. The three-step mode applies if there is enough space
between the maximum load impedances and distance characteristics of the relay that all three (outer, middle, and
inner) characteristics can be placed between the load and the distance characteristics. Whether the spans between 5
the outer and middle as well as the middle and inner characteristics are sufficient should be determined by analysis of
the fastest power swings expected in correlation with settings of the power swing timers.
The two-step mode uses only the outer and inner characteristics for both blocking and tripping functions. This leaves
more space in heavily loaded systems to place two power swing characteristics between the distance characteristics
and the maximum load, but allows for only one determination of the impedance trajectory.
• POWER SWING SUPV: A common overcurrent pickup level supervises all three power swing characteristics. The
supervision responds to the positive sequence current.
• POWER SWING FWD REACH: This setting specifies the forward reach of all three mho characteristics and the inner
quadrilateral characteristic. For a simple system consisting of a line and two equivalent sources, this reach should be
higher than the sum of the line and remote source positive-sequence impedances. Detailed transient stability studies
may be needed for complex systems in order to determine this setting. The angle of this reach impedance is specified
by the POWER SWING FWD RCA setting.
• POWER SWING QUAD FWD REACH MID: This setting specifies the forward reach of the middle quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING QUAD FWD REACH OUT: This setting specifies the forward reach of the outer quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING FWD RCA: This setting specifies the angle of the forward reach impedance for the mho characteris-
tics, angles of all the blinders, and both forward and reverse reach impedances of the quadrilateral characteristics.
• POWER SWING REV REACH: This setting specifies the reverse reach of all three mho characteristics and the inner
quadrilateral characteristic. For a simple system of a line and two equivalent sources, this reach should be higher than
the positive-sequence impedance of the local source. Detailed transient stability studies may be needed for complex
systems to determine this setting. The angle of this reach impedance is specified by the POWER SWING REV RCA setting
for “Mho”, and the POWER SWING FWD RCA setting for “Quad”.
• POWER SWING QUAD REV REACH MID: This setting specifies the reverse reach of the middle quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING QUAD REV REACH OUT: This setting specifies the reverse reach of the outer quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING REV RCA: This setting specifies the angle of the reverse reach impedance for the mho characteris-
tics. This setting applies to mho shapes only.
• POWER SWING OUTER LIMIT ANGLE: This setting defines the outer power swing characteristic. The convention
depicted in the Power swing detect characteristic diagram should be observed: values greater than 90° result in an
apple-shaped characteristic; values less than 90° result in a lens shaped characteristic. This angle must be selected in
consideration of the maximum expected load. If the maximum load angle is known, the outer limit angle should be
coordinated with a 20° security margin. Detailed studies may be needed for complex systems to determine this setting.
This setting applies to mho shapes only.
• POWER SWING MIDDLE LIMIT ANGLE: This setting defines the middle power swing detect characteristic. It is rele-
vant only for the 3-step mode. A typical value would be close to the average of the outer and inner limit angles. This
setting applies to mho shapes only.
• POWER SWING INNER LIMIT ANGLE: This setting defines the inner power swing detect characteristic. The inner
characteristic is used by the out-of-step tripping function: beyond the inner characteristic out-of-step trip action is defi-
nite (the actual trip may be delayed as per the TRIP MODE setting). Therefore, this angle must be selected in consider-
ation to the power swing angle beyond which the system becomes unstable and cannot recover.
The inner characteristic is also used by the power swing blocking function in the two-step mode. In this case, set this
angle large enough so that the characteristics of the distance elements are safely enclosed by the inner characteristic.
This setting applies to mho shapes only.
• POWER SWING OUTER, MIDDLE, and INNER RGT BLD: These settings specify the resistive reach of the right
blinder. The blinder applies to both “Mho” and “Quad” characteristics. Set these value high if no blinder is required for
5 the “Mho” characteristic.
• POWER SWING OUTER, MIDDLE, and INNER LFT BLD: These settings specify the resistive reach of the left blinder.
Enter a positive value; the relay automatically uses a negative value. The blinder applies to both “Mho” and “Quad”
characteristics. Set this value high if no blinder is required for the “Mho” characteristic.
• POWER SWING PICKUP DELAY 1: All the coordinating timers are related to each other and should be set to detect
the fastest expected power swing and produce out-of-step tripping in a secure manner. The timers should be set in
consideration to the power swing detect characteristics, mode of power swing detect operation and mode of out-of-
step tripping. This timer defines the interval that the impedance locus must spend between the outer and inner charac-
teristics (two-step operating mode), or between the outer and middle characteristics (three-step operating mode)
before the power swing blocking signal is established. This time delay must be set shorter than the time required for
the impedance locus to travel between the two selected characteristics during the fastest expected power swing. This
setting is relevant for both power swing blocking and out-of-step tripping.
• POWER SWING RESET DELAY 1: This setting defines the dropout delay for the power swing blocking signal. Detec-
tion of a condition requiring a block output sets latch 1 after PICKUP DELAY 1 time. When the impedance locus leaves
the outer characteristic, timer POWER SWING RESET DELAY 1 is started. When the timer times-out the latch is reset. This
setting should be selected to give extra security for the power swing blocking action.
• POWER SWING PICKUP DELAY 2: Controls the out-of-step tripping function in the three-step mode only. This timer
defines the interval the impedance locus must spend between the middle and inner characteristics before the second
step of the out-of-step tripping sequence is completed. This time delay must be set shorter than the time required for
the impedance locus to travel between the two characteristics during the fastest expected power swing.
• POWER SWING PICKUP DELAY 3: Controls the out-of-step tripping function only. It defines the interval the imped-
ance locus must spend within the inner characteristic before the last step of the out-of-step tripping sequence is com-
pleted and the element is armed to trip. The actual moment of tripping is controlled by the TRIP MODE setting. This time
delay is provided for extra security before the out-of-step trip action is executed.
• POWER SWING PICKUP DELAY 4: Controls the out-of-step tripping function in “Delayed” trip mode only. This timer
defines the interval the impedance locus must spend outside the inner characteristic but within the outer characteristic
before the element is armed for the delayed trip. The delayed trip occurs when the impedance leaves the outer charac-
teristic. This time delay is provided for extra security and should be set considering the fastest expected power swing.
• POWER SWING SEAL-IN DELAY: The out-of-step trip FlexLogic™ operand (POWER SWING TRIP) is sealed-in for the
specified period of time. The sealing-in is crucial in the delayed trip mode, as the original trip signal is a very short
pulse occurring when the impedance locus leaves the outer characteristic after the out-of-step sequence is completed.
• POWER SWING TRIP MODE: Selection of the “Early” trip mode results in an instantaneous trip after the last step in
the out-of-step tripping sequence is completed. The early trip mode will stress the circuit breakers as the currents at
that moment are high (the electromotive forces of the two equivalent systems are approximately 180° apart). Selection
of the “Delayed” trip mode results in a trip at the moment when the impedance locus leaves the outer characteristic.
delayed trip mode will relax the operating conditions for the breakers as the currents at that moment are low. The
selection should be made considering the capability of the breakers in the system.
• POWER SWING BLK: This setting specifies the FlexLogic™ operand used for blocking the out-of-step function only.
The power swing blocking function is operational all the time as long as the element is enabled. The blocking signal
resets the output POWER SWING TRIP operand but does not stop the out-of-step tripping sequence.
SETTINGS
POWER SWING POWER SWING OUTER
SHAPE: LIMIT ANGLE:
POWER SWING FWD POWER SWING MIDDLE
REACH: LIMIT ANGLE:
POWER SWING QUAD POWER SWING INNER
FWD REACH MID: LIMIT ANGLE:
POWER SWING QUAD POWER SWING OUTER
FWD REACH OUT: RGT BLD:
POWER SWING FWD POWER SWING OUTER
RCA: LFT BLD:
SETTING POWER SWING REV POWER SWING MIDDLE
POWER SWING REACH: RGT BLD:
FUNCTION: POWER SWING QUAD REV POWER SWING MIDDLE
Disabled = 0 REACH MID: LFT BLD:
Enabled = 1 POWER SWING QUAD REV POWER SWING INNER
REACH OUT: RGT BLD:
5
SETTING POWER SWING REV POWER SWING INNER
RCA: LFT BLD:
POWER SWING SOURCE:
RUN
FLEXLOGIC OPERAND
V_1 OUTER IMPEDANCE
AND POWER SWING OUTER
I_1 REGION
RUN
FLEXLOGIC OPERAND
MIDDLE IMPEDANCE
AND POWER SWING MIDDLE
REGION
RUN
FLEXLOGIC OPERAND
INNER IMPEDANCE
AND POWER SWING INNER
REGION
SETTING
POWER SWING
SUPV:
RUN
SETTING
POWER SWING FUNCTION:
Disabled = 0
TIMER
Enabled = 1
0
SETTING 10 cycles
SETTING SETTINGS
POWER SWING
POWER SWING MODE:
DELAY 1 PICKUP:
POWER SWING
3-step
AND DELAY 1 RESET:
FLEXLOGIC OPERANDS
tPKP
S Q1 POWER SWING BLOCK
tRST
POWER SWING UN/BLOCK
AND L1 S Q5
2-step FLEXLOGIC OPERAND
L5
R POWER SWING 50DD
R
OR
OR
SETTING
POWER SWING FLEXLOGIC OPERAND
DELAY 2 PICKUP:
POWER SWING TMR2 PKP
tPKP
AND S Q2
0
L2
R
3-step
2-step
FLEXLOGIC OPERAND
SETTING POWER SWING TMR3 PKP
POWER SWING
DELAY 3 PICKUP: FLEXLOGIC OPERAND
tPKP POWER SWING INCOMING
5 AND
0 S Q3
R
L3 SETTING
POWER SWING TRIP
MODE:
SETTING SETTING
POWER SWING POWER SWING
DELAY 4 PICKUP: Early
SEAL-IN DELAY:
tPKP 0
AND S Q4 FLEXLOGIC OPERAND
0 tRST
L4 AND POWER SWING TRIP
R AND
Delayed
FLEXLOGIC OPERAND
POWER SWING OUTGOING
827841A4.CDR
The stator differential protection element is intended for use on the stator windings of rotating machinery.
differential
Operate Block
Slope 2
Slope 1
Pickup
Break 1
Break 2
restraining
830735A1.CDR
2. CT saturation
The characteristic allows for very sensitive settings when fault current is low and less sensitive settings when fault current is
high and CT performance may produce incorrect operate signals.
• STATOR DIFF LINE END SOURCE: This setting selects the source connected to CTs in the end of the machine stator
winding closest to the load and furthest from the winding neutral point. Both line and neutral-side CTs should be wired
to measure their currents in the same direction with respect to the neutral point of the winding.
• STATOR DIFF NEUTRAL END SOURCE: This setting selects the source connected to CTs in the end of the machine
stator winding furthest from the load and closest to the winding neutral point. Both line and neutral-side CTs should be
wired to measure their currents in the same direction with respect to the neutral point of the winding.
• STATOR DIFF PICKUP: This setting defines the minimum differential current required for operation. This setting is
based on the amount of differential current that might be seen under normal operating conditions. A setting of 0.1 to
0.3 pu is generally recommended.
• STATOR DIFF SLOPE 1: This setting is applicable for restraint currents from zero to STATOR DIFF BREAK 1, and defines
the ratio of differential to restraint current above which the element will operate. This slope is set to ensure sensitivity to
internal faults at normal operating current levels. The criteria for setting this slope is to allow for maximum expected CT
mismatch error when operating at the maximum permitted current. This maximum error is generally in the range of 5 to
10% of CT rating.
• STATOR DIFF BREAK 1: This setting defines the end of the Slope 1 region and the start of the transition region. It
should be set just above the maximum normal operating current level of the machine.
• STATOR DIFF SLOPE 2: This setting is applicable for restraint currents above the STATOR DIFF BREAK 2 setting when
the element is applied to generator stator windings. This slope is set to ensure stability under heavy external fault con-
ditions that could lead to high differential currents as a result of CT saturation. A setting of 80 to 100% is recom-
mended. The transition region (as shown on the characteristic plot) is a cubic spline, automatically calculated by the
5 relay to result in a smooth transition between STATOR DIFF SLOPE 1 and STATOR DIFF SLOPE 2 with no discontinuities.
• STATOR DIFF BREAK 2: This setting defines the end of the transition region and the start of the Slope 2 region. It
should be set to the level at which any of the protection CTs are expected to begin to saturate.
SETTING
STATOR DIFF SETTINGS
FUNCTION:
STATOR DIFF
Disabled = 0 PICKUP:
Enabled = 1
STATOR DIFF
SLOPE 1:
SETTING
AND STATOR DIFF
BREAK 1:
STATOR DIFF BLOCK:
STATOR DIFF
Off = 0 SLOPE 2:
STATOR DIFF
SETTING BREAK 2:
STATOR DIFF RUN
LINE END SOURCE: Differential Phasors FLEXLOGIC OPERANDS
Iad
IA Iad STATOR DIFF PKP A
IB Ibd STATOR DIFF DPO A
IC Icd Iar
RUN
DC Offset
Ibd FLEXLOGIC OPERANDS
Removal
D.F.T. STATOR DIFF PKP B
SETTING
and STATOR DIFF DPO B
STATOR DIFF Differential Ibr
NEUTRAL END SOURCE: and Restraint Restraint Phasors RUN
IA Iar Icd FLEXLOGIC OPERANDS
IB Ibr STATOR DIFF PKP C
IC Icr STATOR DIFF DPO C
Icr
The saturation detector is implemented as a state machine (see below). "NORMAL" is the initial state of the machine. When
in "NORMAL" state, the saturation flag is not set (SAT = 0). The algorithm calculates the saturation condition, SC. If SC = 1
while the state machine is "NORMAL", the saturation detector goes into the "EXTERNAL FAULT" state and sets the satura-
tion flag (SAT = 1). The algorithm returns to the "NORMAL" state if the differential current is below the first slope, SL, for
more than 200 ms. When in the "EXTERNAL FAULT" state, the algorithm goes into the "EXTERNAL FAULT & CT SATU-
RATION" state if the differential flag is set (DIF = 1). When in the "EXTERNAL FAULT & CT SATURATION" state, the algo-
rithm keeps the saturation flag set (SAT = 1). The state machine returns to the "EXTERNAL FAULT" state if the differential
flag is reset (DIF = 0) for 100 ms.
SAT := 1
DIF = 0
for 100 ms
EXTERNAL FAULT
AND CT SATURATION
SAT := 1 5
830736A1.CDR
else DIR = 1
where: IR = restraining current, DIR = flag indicating that the phase comparison principle is satisfied
BL = breakpoint 1 setting, ITS, INS = current at the terminal and neutral sources, respectively
K = factory constant of 0.25
FLEXLOGIC OPERANDS
STATOR DIFF PKP A FLEXLOGIC OPERAND
STATOR DIFF SAT A AND STATOR DIFF OP A
OR
STATOR DIFF DIR A
FLEXLOGIC OPERANDS
STATOR DIFF PKP B FLEXLOGIC OPERAND
STATOR DIFF SAT B AND STATOR DIFF OP B
OR
STATOR DIFF DIR B
FLEXLOGIC OPERANDS
STATOR DIFF PKP C FLEXLOGIC OPERAND
STATOR DIFF SAT C AND STATOR DIFF OP C
OR
STATOR DIFF DIR C
FLEXLOGIC OPERAND
OR STATOR DIFF OP
842707A1.CDR
a) MAIN MENU
PATH: SETTINGS Ø GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ PHASE CURRENT
A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (CURVE) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
to the time multiplier (TD MULTIPLIER) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal energy capacity memory variable. When this variable indi-
cates that the energy capacity has reached 100%, a time overcurrent element will operate. If less than 100% energy capac-
ity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value, the
variable must be reduced. Two methods of this resetting operation are available: “Instantaneous” and “Timed”. The “Instan-
taneous” selection is intended for applications with other relays, such as most static relays, which set the energy capacity
directly to zero when the current falls below the reset threshold. The “Timed” selection can be used where the relay must
coordinate with electromechanical relays.
IEEE CURVES:
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications
for extremely, very, and moderately inverse. The IEEE curves are derived from the formulae:
A tr
---------------------------------- + B -----------------------------------
-
T = TDM × ⎛ ---------------
I -⎞ p T TDM × 2
1 – ⎛ ---------------- ⎞
, = I (EQ 5.8)
⎝ I pickup⎠ – 1
RESET
⎝ I pickup ⎠
where: T = operate time (in seconds), TDM = Multiplier setting, I = input current, Ipickup = Pickup Current setting
A, B, p = constants, TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”),
tr = characteristic constant
IEC CURVES
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142. These
are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The formulae for these curves are:
K tr
--------------------------------------- --------------------------------------
-
T = TDM × ( I ⁄ I pickup ) E – 1 , T RESET = TDM × 1 – ( I ⁄ I 2 (EQ 5.9)
pickup )
where: T = operate time (in seconds), TDM = Multiplier setting, I = input current, Ipickup = Pickup Current setting, K, E =
constants, tr = characteristic constant, and TRESET = reset time in seconds (assuming energy capacity is 100%
and RESET is “Timed”)
IAC CURVES:
The curves for the General Electric type IAC relay family are derived from the formulae:
⎛ B D E ⎞ tr
T = TDM × ⎜ A + ------------------------------ + -------------------------------------2- + -------------------------------------3-⎟ , T RESET = TDM × -------------------------------
- (EQ 5.10)
⎝ ( I ⁄ I ) – C ( ( I ⁄ I ) – C ) ( ( I ⁄ I ) – C ) ⎠ 2
pkp pkp pkp 1 – ( I ⁄ I pkp )
where: T = operate time (in seconds), TDM = Multiplier setting, I = Input current, Ipkp = Pickup Current setting, A to E =
constants, tr = characteristic constant, and TRESET = reset time in seconds (assuming energy capacity is 100%
and RESET is “Timed”)
I2t CURVES:
The curves for the I2t are derived from the formulae:
100 100
-------------------------- ----------------------------
T = TDM × ⎛ ---------------
I ⎞ 2 , T RESET = TDM × ⎛ I ⎞ –2
- ---------------- (EQ 5.11)
⎝ I pickup ⎠ ⎝ I pickup ⎠
where: T = Operate Time (sec.); TDM = Multiplier Setting; I = Input Current; Ipickup = Pickup Current Setting;
TRESET = Reset Time in sec. (assuming energy capacity is 100% and RESET: Timed)
FLEXCURVES™:
The custom FlexCurves™ are described in detail in the FlexCurves™ section of this chapter. The curve shapes for the
FlexCurves™ are derived from the formulae:
The phase time overcurrent element can provide a desired time-delay operating characteristic versus the applied current or
be used as a simple definite time element. The phase current input quantities may be programmed as fundamental phasor
magnitude or total waveform RMS magnitude as required by the application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to the Inverse Time overcurrent
curves characteristic sub-section earlier for details on curve setup, trip times, and reset operation). When the element is
blocked, the time accumulator will reset according to the reset characteristic. For example, if the element reset characteris-
tic is set to “Instantaneous” and the element is blocked, the time accumulator will be cleared immediately.
The PHASE TOC1 PICKUP setting can be dynamically reduced by a voltage restraint feature (when enabled). This is accom-
plished via the multipliers (Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic curve (see
the figure below); the pickup level is calculated as ‘Mvr’ times the PHASE TOC1 PICKUP setting. If the voltage restraint feature
is disabled, the pickup level always remains at the setting value.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Phase-Phase Voltage ÷ VT Nominal Phase-phase Voltage
818784A4.CDR
SETTING
PHASE TOC1
FUNCTION:
Disabled=0
Enabled=1
SETTING
PHASE TOC1
BLOCK-A :
Off=0
5 SETTING
PHASE TOC1
BLOCK-B:
Off=0
SETTING
SETTING
PHASE TOC1
PHASE TOC1 INPUT:
BLOCK-C:
PHASE TOC1
Off=0 PICKUP:
PHASE TOC1
SETTING CURVE:
PHASE TOC1 PHASE TOC1
SOURCE: TD MULTIPLIER:
IA
PHASE TOC1
IB RESET: FLEXLOGIC OPERAND
IC AND RUN PHASE TOC1 A PKP
IA PICKUP
Seq=ABC Seq=ACB PHASE TOC1 A DPO
MULTIPLY INPUTS
RUN
t PHASE TOC1 A OP
VAB VAC Set
Calculate Multiplier Set Pickup AND RUN PHASE TOC1 B PKP
RUN
Multiplier-Phase A IB PICKUP
Set PHASE TOC1 B DPO
VBC VBA Set Pickup
Calculate Multiplier t PHASE TOC1 B OP
RUN
Multiplier-Phase B
Set AND RUN PHASE TOC1 C PKP
VCA VCB IC PICKUP
Calculate Multiplier Set Pickup PHASE TOC1 C DPO
Multiplier-Phase C
t PHASE TOC1 C OP
SETTING OR PHASE TOC1 PKP
PHASE TOC1 VOLT
RESTRAINT: OR PHASE TOC1 OP
Enabled
827072A4.CDR
The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude. The phase instantaneous overcurrent timing
curves are shown below for form-A contacts in a 60 Hz system.
35
30
25
20
Milliseconds
15
Maximum
10 Minimum
0
1.05 1.1 1.2 1.5 2 5 10 15 20
SETTING
827033A6.VSD
PHASE IOC1
BLOCK-C:
Off = 0
The phase directional elements (one for each of phases A, B, and C) determine the phase current flow direction for steady
state and fault conditions and can be used to control the operation of the phase overcurrent elements via the BLOCK inputs
of these elements. 5
S
UT 0
TP
OU
–90°
VPol
VAG(Faulted) IA
ECA
set at 30°
VBC
VBC
VCG VBG +90°
To increase security for three phase faults very close to the VTs used to measure the polarizing voltage, a voltage memory
feature is incorporated. This feature stores the polarizing voltage the moment before the voltage collapses, and uses it to
determine direction. The voltage memory remains valid for one second after the voltage has collapsed.
The main component of the phase directional element is the phase angle comparator with two inputs: the operating signal
(phase current) and the polarizing signal (the line voltage, shifted in the leading direction by the characteristic angle, ECA).
The following table shows the operating and polarizing signals used for phase directional control:
PHASE OPERATING POLARIZING SIGNAL Vpol
SIGNAL
ABC PHASE SEQUENCE ACB PHASE SEQUENCE
A angle of IA angle of VBC × (1∠ECA) angle of VCB × (1∠ECA)
B angle of IB angle of VCA × (1∠ECA) angle of VAC × 1∠ECA)
C angle of IC angle of VAB × (1∠ECA) angle of VBA × (1∠ECA)
MODE OF OPERATION:
• When the function is “Disabled”, or the operating current is below 5% × CT nominal, the element output is “0”.
• When the function is “Enabled”, the operating current is above 5% × CT nominal, and the polarizing voltage is above
the PRODUCT SETUP ÖØ DISPLAY PROPERTIES ÖØ VOLTAGE CUT-OFF LEVEL value, the element output is dependent on
the phase angle between the operating and polarizing signals:
– The element output is logic “0” when the operating current is within polarizing voltage ±90°.
– For all other angles, the element output is logic “1”.
• Once the voltage memory has expired, the phase overcurrent elements under directional control can be set to block or
trip on overcurrent as follows:
5 – When BLOCK WHEN V MEM EXP is set to “Yes”, the directional element will block the operation of any phase
overcurrent element under directional control when voltage memory expires.
– When BLOCK WHEN V MEM EXP is set to “No”, the directional element allows tripping of phase overcurrent elements
under directional control when voltage memory expires.
In all cases, directional blocking will be permitted to resume when the polarizing voltage becomes greater than the ‘polariz-
ing voltage threshold’.
SETTINGS:
• PHASE DIR 1 SIGNAL SOURCE: This setting is used to select the source for the operating and polarizing signals.
The operating current for the phase directional element is the phase current for the selected current source. The polar-
izing voltage is the line voltage from the phase VTs, based on the 90° or ‘quadrature’ connection and shifted in the
leading direction by the element characteristic angle (ECA).
• PHASE DIR 1 ECA: This setting is used to select the element characteristic angle, i.e. the angle by which the polariz-
ing voltage is shifted in the leading direction to achieve dependable operation. In the design of the UR-series elements,
a block is applied to an element by asserting logic 1 at the blocking input. This element should be programmed via the
ECA setting so that the output is logic 1 for current in the non-tripping direction.
• PHASE DIR 1 POL V THRESHOLD: This setting is used to establish the minimum level of voltage for which the phase
angle measurement is reliable. The setting is based on VT accuracy. The default value is “0.700 pu”.
• PHASE DIR 1 BLOCK WHEN V MEM EXP: This setting is used to select the required operation upon expiration of
voltage memory. When set to "Yes", the directional element blocks the operation of any phase overcurrent element
under directional control, when voltage memory expires; when set to "No", the directional element allows tripping of
phase overcurrent elements under directional control.
The phase directional element responds to the forward load current. In the case of a following reverse fault,
the element needs some time – in the order of 8 ms – to establish a blocking signal. Some protection ele-
NOTE
ments such as instantaneous overcurrent may respond to reverse faults before the blocking signal is
established. Therefore, a coordination time of at least 10 ms must be added to all the instantaneous protec-
tion elements under the supervision of the phase directional element. If current reversal is of a concern, a
longer delay – in the order of 20 ms – may be needed.
SETTING
PHASE DIR 1
FUNCTION:
Disabled=0
Enabled=1
SETTING
AND
PHASE DIR 1
BLOCK:
Off=0
SETTING
FLEXLOGIC OPERAND
PHASE B LOGIC SIMILAR TO PHASE A PH DIR1 BLK B
5
FLEXLOGIC OPERAND
PHASE C LOGIC SIMILAR TO PHASE A PH DIR1 BLK C
827078A6.CDR
a) MAIN MENU
PATH: SETTINGS Ø GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ NEUTRAL CURRENT
The neutral time overcurrent element can provide a desired time-delay operating characteristic versus the applied current
or be used as a simple definite time element. The neutral current input value is a quantity calculated as 3Io from the phase
currents and may be programmed as fundamental phasor magnitude or total waveform RMS magnitude as required by the
application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to the Inverse time overcurrent curve
characteristics section for details on curve setup, trip times and reset operation). When the element is blocked, the time
accumulator will reset according to the reset characteristic. For example, if the element reset characteristic is set to “Instan-
taneous” and the element is blocked, the time accumulator will be cleared immediately.
SETTINGS
NEUTRAL TOC1
SETTING INPUT:
NEUTRAL TOC1 NEUTRAL TOC1
FUNCTION: PICKUP:
Disabled = 0 NEUTRAL TOC1
Enabled = 1 CURVE:
NEUTRAL TOC1
TD MULTIPLIER:
NEUTRAL TOC 1 FLEXLOGIC OPERANDS
SETTING
RESET: NEUTRAL TOC1 PKP
NEUTRAL TOC1
AND RUN IN ≥ PICKUP NEUTRAL TOC1 DPO
SOURCE:
NEUTRAL TOC1 OP
IN t
I
SETTING
NEUTRAL TOC1
BLOCK:
Off = 0 827034A3.VSD
The neutral instantaneous overcurrent element may be used as an instantaneous function with no intentional delay or as a
definite time function. The element essentially responds to the magnitude of a neutral current fundamental frequency pha-
sor calculated from the phase currents. A positive-sequence restraint is applied for better performance. A small portion 5
(6.25%) of the positive-sequence current magnitude is subtracted from the zero-sequence current magnitude when forming
the operating quantity of the element as follows:
I op = 3 × ( I_0 – K ⋅ I_1 ) where K = 1 ⁄ 16 (EQ 5.16)
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from:
• System unbalances under heavy load conditions
• Transformation errors of current transformers (CTs) during double-line and three-phase faults.
• Switch-off transients during double-line and three-phase faults.
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on how test currents are injected into the relay (single-phase injection:
I op = 0.9375 ⋅ I injected ; three-phase pure zero-sequence injection: I op = 3 × I injected ).
SETTING
Off=0
SETTING
The neutral directional overcurrent element provides both forward and reverse fault direction indications the NEUTRAL DIR
OC1 FWD and NEUTRAL DIR OC1 REV operands, respectively. The output operand is asserted if the magnitude of the oper-
ating current is above a pickup level (overcurrent unit) and the fault direction is seen as forward or reverse, respectively
(directional unit).
The overcurrent unit responds to the magnitude of a fundamental frequency phasor of the either the neutral current calcu-
lated from the phase currents or the ground current. There are separate pickup settings for the forward-looking and
reverse-looking functions. If set to use the calculated 3I_0, the element applies a positive-sequence restraint for better per-
formance: a small user-programmable portion of the positive-sequence current magnitude is subtracted from the zero-
sequence current magnitude when forming the operating quantity.
I op = 3 × ( I_0 – K × I_1 ) (EQ 5.17)
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from:
• System unbalances under heavy load conditions.
• Transformation errors of current transformers (CTs) during double-line and three-phase faults.
• Switch-off transients during double-line and three-phase faults.
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase injection:
Iop = (1 – K) × Iinjected ; three-phase pure zero-sequence injection: Iop = 3 × Iinjected).
The positive-sequence restraint is removed for low currents. If the positive-sequence current is below 0.8 pu, the restraint is
removed by changing the constant K to zero. This facilitates better response to high-resistance faults when the unbalance
is very small and there is no danger of excessive CT errors as the current is low.
The directional unit uses the zero-sequence current (I_0) or ground current (IG) for fault direction discrimination and may
be programmed to use either zero-sequence voltage (“Calculated V0” or “Measured VX”), ground current (IG), or both for
polarizing. The following tables define the neutral directional overcurrent element.
1
where: V_0 = --- ( VAG + VBG + VCG ) = zero sequence voltage ,
3
1 1
I_0 = --- IN = --- ( IA + IB + IC ) = zero sequence current ,
3 3
ECA = element characteristic angle and IG = ground current
When NEUTRAL DIR OC1 POL VOLT is set to “Measured VX”, one-third of this voltage is used in place of V_0. The following
figure explains the usage of the voltage polarized directional unit of the element.
The figure below shows the voltage-polarized phase angle comparator characteristics for a phase A to ground fault, with:
• ECA = 90° (element characteristic angle = centerline of operating characteristic)
• FWD LA = 80° (forward limit angle = the ± angular limit with the ECA for operation)
• REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation)
The above bias should be taken into account when using the neutral directional overcurrent element to directionalize other
protection elements.
REV LA FWD LA
line –3V_0 line line
VAG
(reference)
LA
LA
3I_0 line
ECA
ECA line
–ECA line
–3I_0 line LA
VCG LA
VBG
FWD LA
REV LA line
3V_0 line
line 827805A1.CDR
For a choice of current polarizing, it is recommended that the polarizing signal be analyzed to ensure that a known
direction is maintained irrespective of the fault location. For example, if using an autotransformer neutral current
as a polarizing source, it should be ensured that a reversal of the ground current does not occur for a high-side
fault. The low-side system impedance should be assumed minimal when checking for this condition. A similar sit-
uation arises for a wye/delta/wye transformer, where current in one transformer winding neutral may reverse when
faults on both sides of the transformer are considered.
– If “Dual” polarizing is selected, the element performs both directional comparisons as described above. A given
direction is confirmed if either voltage or current comparators indicate so. If a conflicting (simultaneous forward
and reverse) indication occurs, the forward direction overrides the reverse direction.
• NEUTRAL DIR OC1 POL VOLT: Selects the polarizing voltage used by the directional unit when "Voltage" or "Dual"
polarizing mode is set. The polarizing voltage can be programmed to be either the zero-sequence voltage calculated
from the phase voltages ("Calculated V0") or supplied externally as an auxiliary voltage ("Measured VX").
• NEUTRAL DIR OC1 OP CURR: This setting indicates whether the 3I_0 current calculated from the phase currents, or
the ground current shall be used by this protection. This setting acts as a switch between the neutral and ground
modes of operation (67N and 67G). If set to “Calculated 3I0” the element uses the phase currents and applies the pos-
itive-sequence restraint; if set to “Measured IG” the element uses ground current supplied to the ground CT of the CT
bank configured as NEUTRAL DIR OC1 SOURCE. If this setting is “Measured IG”, then the NEUTRAL DIR OC1 POLARIZING
setting must be “Voltage”, as it is not possible to use the ground current as an operating and polarizing signal simulta-
neously.
• NEUTRAL DIR OC1 POS-SEQ RESTRAINT: This setting controls the amount of the positive-sequence restraint. Set
to 0.063 for backward compatibility with firmware revision 3.40 and older. Set to zero to remove the restraint. Set
higher if large system unbalances or poor CT performance are expected.
• NEUTRAL DIR OC1 OFFSET: This setting specifies the offset impedance used by this protection. The primary appli-
cation for the offset impedance is to guarantee correct identification of fault direction on series compensated lines. In
regular applications, the offset impedance ensures proper operation even if the zero-sequence voltage at the relaying
point is very small. If this is the intent, the offset impedance shall not be larger than the zero-sequence impedance of
the protected circuit. Practically, it shall be several times smaller. The offset impedance shall be entered in secondary
ohms.
• NEUTRAL DIR OC1 FWD ECA: This setting defines the characteristic angle (ECA) for the forward direction in the
"Voltage" polarizing mode. The "Current" polarizing mode uses a fixed ECA of 0°. The ECA in the reverse direction is
the angle set for the forward direction shifted by 180°.
• NEUTRAL DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the forward direction.
• NEUTRAL DIR OC1 FWD PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the
forward direction. When selecting this setting it must be kept in mind that the design uses a ‘positive-sequence
restraint’ technique for the “Calculated 3I0” mode of operation.
5
• NEUTRAL DIR OC1 REV LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
• NEUTRAL DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the
reverse direction. When selecting this setting it must be kept in mind that the design uses a positive-sequence restraint
technique for the “Calculated 3I0” mode of operation.
Proper application of this element requires that the operating current and the polarizing voltage (or current) be mea-
sured from the same side of the transformer.
NOTE
SETTING
NEUTRAL DIR OC1 FWD
PICKUP:
NEUTRAL DIR OC1 OP
CURR:
SETTING
AND SETTINGS
NEUTRAL DIR OC1 BLK: AND
NEUTRAL DIR OC1 FWD
ECA:
Off=0
NEUTRAL DIR OC1 FWD FLEXLOGIC OPERAND
LIMIT ANGLE:
SETTING AND NEUTRAL DIR OC1 FWD
NEUTRAL DIR OC1 NEUTRAL DIR OC1 REV
SOURCE: LIMIT ANGLE:
}
Measured VX OR
Calculated V_0 FWD
1.25 cy
}
-3V_0 AND
Zero Seq Crt (I_0) 1.5 cy
Ground Crt (IG) REV
3I_0 REV
Voltage Polarization
5 Current
Dual OR
REV
OR
NOTE:
1) CURRENT POLARIZING IS POSSIBLE ONLY IN RELAYS WITH
THE GROUND CURRENT INPUTS CONNECTED TO
AN ADEQUATE CURRENT POLARIZING SOURCE SETTING
NEUTRAL DIR OC1 REV
2) GROUND CURRENT CAN NOT BE USED FOR POLARIZATION PICKUP:
AND OPERATION SIMULTANEOUSLY AND FLEXLOGIC OPERAND
NEUTRAL DIR OC1 OP
3) POSITIVE SEQUENCE RESTRAINT IS NOT APPLIED WHEN CURR: NEUTRAL DIR OC1 REV
I_1 IS BELOW 0.8pu NEUTRAL DIR OC1 POS-
SEQ RESTRAINT:
RUN
3( I_0 - K I_1 ) PICKUP 827077AB.CDR
OR
IG PICKUP
a) MAIN MENU
PATH: SETTINGS Ø GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ GROUND CURRENT
RESTRICTED GROUND
MESSAGE
FAULT 4
The G60 relay contains one Ground Time Overcurrent, one Ground Instantaneous Overcurrent, and four Restricted Ground
Fault elements. Refer to Inverse Time Overcurrent Characteristics on page 5–148 for additional information.
This element can provide a desired time-delay operating characteristic versus the applied current or be used as a simple
definite time element. The ground current input value is the quantity measured by the ground input CT and is the funda-
mental phasor or RMS magnitude. Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to
the Inverse time overcurrent curve characteristics section for details). When the element is blocked, the time accumulator
will reset according to the reset characteristic. For example, if the element reset characteristic is set to “Instantaneous” and
the element is blocked, the time accumulator will be cleared immediately.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel may be also equipped with a sensitive input. The conversion range of a sensitive channel is from
0.002 to 4.6 times the CT rating.
NOTE
SETTINGS
GROUND TOC1
SETTING INPUT:
GROUND TOC1 GROUND TOC1
FUNCTION: PICKUP:
Disabled = 0 GROUND TOC1
Enabled = 1 CURVE:
GROUND TOC1
TD MULTIPLIER:
GROUND TOC 1 FLEXLOGIC OPERANDS
SETTING
RESET: GROUND TOC1 PKP
GROUND TOC1
AND RUN IG ≥ PICKUP GROUND TOC1 DPO
SOURCE:
GROUND TOC1 OP
IG t
I
SETTING
GROUND TOC1
BLOCK:
827036A3.VSD
Off = 0
The ground instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental
5 phasor magnitude.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel may be equipped with a standard or sensitive input. The conversion range of a sensitive channel is
from 0.002 to 4.6 times the CT rating.
NOTE
FLEXLOGIC OPERANDS
SETTING GROUND IOC1 PKP
GROUND IOC1
GROUND IOIC DPO
FUNCTION:
Disabled = 0 SETTINGS GROUND IOC1 OP
WINDING
35%
842731A1.CDR
IB IB
IC IC
IG IG
IB
IB
IC
IC
5 IG IA IB IC
IG
2 2 2
842732A1.CDR
The relay automatically matches the CT ratios between the phase and ground CTs by re-scaling the ground CT to the
phase CT level. The restraining signal ensures stability of protection during CT saturation conditions and is produced as a
maximum value between three components related to zero, negative, and positive-sequence currents of the three phase
CTs as follows:
Irest = max ( IR0, IR1, IR2 ) (EQ 5.19)
The zero-sequence component of the restraining signal (IR0) is meant to provide maximum restraint during external ground
faults, and therefore is calculated as a vectorial difference of the ground and neutral currents:
IR0 = IG – IN = IG – ( IA + IB + IC ) (EQ 5.20)
The equation above brings an advantage of generating the restraining signal of twice the external ground fault current,
while reducing the restraint below the internal ground fault current. The negative-sequence component of the restraining
signal (IR2) is meant to provide maximum restraint during external phase-to-phase faults and is calculated as follows:
IR2 = I_2 or IR2 = 3 × I_2 (EQ 5.21)
The multiplier of 1 is used by the relay for first two cycles following complete de-energization of the winding (all three phase
currents below 5% of nominal for at least five cycles). The multiplier of 3 is used during normal operation; that is, two cycles
after the winding has been energized. The lower multiplier is used to ensure better sensitivity when energizing a faulty
winding.
The positive-sequence component of the restraining signal (IR1) is meant to provide restraint during symmetrical condi-
tions, either symmetrical faults or load, and is calculated according to the following algorithm:
1 If I_1 > 1.5 pu of phase CT, then
2 If I_1 > I_0 , then IR1 = 3 × ( I_1 – I_0 )
3 else IR1 = 0
4 else IR1 = I_1 ⁄ 8
Under load-level currents (below 150% of nominal), the positive-sequence restraint is set to 1/8th of the positive-sequence
current (line 4). This is to ensure maximum sensitivity during low-current faults under full load conditions. Under fault-level
currents (above 150% of nominal), the positive-sequence restraint is removed if the zero-sequence component is greater
than the positive-sequence (line 3), or set at the net difference of the two (line 2).
The raw restraining signal (Irest) is further post-filtered for better performance during external faults with heavy CT satura-
tion and for better switch-off transient control:
Igr ( k ) = max ( Irest ( k ), α × Igr ( k – 1 ) ) (EQ 5.22)
where k represents a present sample, k – 1 represents the previous sample, and α is a factory constant (α < 1). The equa-
tion above introduces a decaying memory to the restraining signal. Should the raw restraining signal (Irest) disappear or
5
drop significantly, such as when an external fault gets cleared or a CT saturates heavily, the actual restraining signal (Igr(k))
will not reduce instantly but will keep decaying decreasing its value by 50% each 15.5 power system cycles.
Having the differential and restraining signals developed, the element applies a single slope differential characteristic with a
minimum pickup as shown in the logic diagram below.
SETTING
RESTD GND FT1
FUNCTION:
Disabled=0
SETTING
Enabled=1
RESTD GND FT1
PICKUP: SETTINGS
SETTING
AND RUN RESTD GND FT1 PICKUP
RESTD GND FT1 Igd > PICKUP DELAY:
BLOCK: FLEXLOGIC OPERANDS
RESTD GND FT1 RESET
Off=0 RESTD GND FT1 PKP
DELAY:
SETTING RESTD GND FT1 DPO
t PKP
SETTING AND t RST RESTD GND FT1 OP
RESTD GND FT1
RESTD GND FT1 SLOPE:
SOURCE: RUN
IG
IN Differential Igd > SLOPE * Igr
and
I_0
Restraining
I_1 Currents
I_2
ACTUAL VALUES
RGF 1 Igd Mag
RGF 1 Igr Mag 828002A2.CDR
The following examples explain how the restraining signal is created for maximum sensitivity and security. These examples
clarify the operating principle and provide guidance for testing of the element.
EXAMPLE 1: EXTERNAL SINGLE-LINE-TO-GROUND FAULT
Given the following inputs: IA = 1 pu ∠0°, IB = 0, IC = 0, and IG = 1 pu ∠180°
The relay calculates the following values:
1⁄3
Igd = 0, IR0 = abs ⎛ 3 × --- – ( – 1 )⎞ = 2 pu , IR2 = 3 × --- = 1 pu , IR1 = ---------- = 0.042 pu , and Igr = 2 pu
1 1
⎝ 3 ⎠ 3 8
The restraining signal is twice the fault current. This gives extra margin should the phase or neutral CT saturate.
EXAMPLE 2: EXTERNAL HIGH-CURRENT SLG FAULT
Given the following inputs: IA = 10 pu ∠0°, IB = 0, IC = 0, and IG = 10 pu ∠–180°
The relay calculates the following values:
Igd = 0, IR0 = abs ⎛ 3 × --- – ( – 10 )⎞ = 20 pu , IR2 = 3 × ------ = 10 pu , IR1 = 3 × ⎛ 10 ------⎞⎠ = 0 , and Igr = 20 pu.
1 10
- – 10
⎝ 3 ⎠ 3 ⎝ -----
3 3
NEG SEQ DIR OC1 NEG SEQ DIR OC1 Range: Disabled, Enabled
FUNCTION: Disabled
NEG SEQ DIR OC1 Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
NEG SEQ DIR OC1 Range: 0.00 to 250.00 ohms in steps of 0.01
MESSAGE
OFFSET: 0.00 Ω
NEG SEQ DIR OC1 Range: Neg Sequence, Zero Sequence
MESSAGE
TYPE: Neg Sequence
NEG SEQ DIR OC1 POS- Range: 0.000 to 0.500 in steps of 0.001
MESSAGE
SEQ RESTRAINT: 0.063
NEG SEQ DIR OC1 FWD Range: 0 to 90° Lag in steps of 1
MESSAGE
ECA: 75° Lag
NEG SEQ DIR OC1 FWD Range: 40 to 90° in steps of 1
MESSAGE
LIMIT ANGLE: 90°
NEG SEQ DIR OC1 FWD Range: 0.015 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.050 pu
MESSAGE
NEG SEQ DIR OC1 REV Range: 40 to 90° in steps of 1
5
LIMIT ANGLE: 90°
NEG SEQ DIR OC1 REV Range: 0.015 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.050 pu
NEG SEQ DIR OC1 BLK: Range: FlexLogic™ operand
MESSAGE
Off
NEG SEQ DIR OC1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
NEG SEQ DIR OC1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
There are two negative-sequence directional overcurrent protection elements available. The element provides both forward
and reverse fault direction indications through its output operands NEG SEQ DIR OC1 FWD and NEG SEQ DIR OC1 REV,
respectively. The output operand is asserted if the magnitude of the operating current is above a pickup level (overcurrent
unit) and the fault direction is seen as forward or reverse, respectively (directional unit).
The overcurrent unit of the element essentially responds to the magnitude of a fundamental frequency phasor of either
the negative-sequence or zero-sequence current as per user selection. The zero-sequence current should not be mistaken
with the neutral current (factor 3 difference).
A positive-sequence restraint is applied for better performance: a small user-programmable portion of the positive-
sequence current magnitude is subtracted from the negative or zero-sequence current magnitude, respectively, when form-
ing the element operating quantity.
I op = I_2 – K × I_1 or I op = 3 × ( I_0 – K × I_1 ) (EQ 5.23)
The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence and
zero-sequence currents resulting from:
• System unbalances under heavy load conditions.
• Transformation errors of current transformers (CTs).
• Fault inception and switch-off transients.
The positive-sequence restraint must be considered when testing for pick-up accuracy and response time (multiple of
pickup). The positive-sequence restraint is removed for low currents. If the positive-sequence current is less than 0.8 pu,
then the restraint is removed by changing the constant K to zero. This results in better response to high-resistance faults
when the unbalance is very small and there is no danger of excessive CT errors, since the current is low.
The operating quantity depends on the way the test currents are injected into the G60. For single phase injection:
• Iop = ⅓ × (1 – K) × Iinjected for I_2 mode.
• Iop = (1 – K) × Iinjected for I_0 mode if I_1 > 0.8 pu.
The directional unit uses the negative-sequence current (I_2) and negative-sequence voltage (V_2).
The following tables define the negative-sequence directional overcurrent element.
Table 5–23: NEGATIVE-SEQUENCE DIRECTIONAL OVERCURRENT UNIT
MODE OPERATING CURRENT
Negative-sequence Iop = |I_2| – K × I_1|
Zero-sequence Iop = 3 × (|I_0| – K × |I_1|) if |I_1| > 0.8 pu
Iop = 3 × |I_0| if |I_1| ≤ 0.8 pu
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power system
cycle, the prospective forward indication will be delayed by 1.5 of a power system cycle. The element is designed to emu-
late an electromechanical directional device. Larger operating and polarizing signals will result in faster directional discrimi-
nation bringing more security to the element operation.
–V_2 line
REV FWD
LA LA VAG (reference)
REV Operating
Region
LA
ECA line
LA ECA
I_2 line
–I_2 line LA
FWD Operating
Region
–ECA line
LA
VCG VBG
V_2 line
REV
LA
FWD
LA
5
827806A2.CDR
• NEG SEQ DIR OC1 OFFSET: This setting specifies the offset impedance used by this protection. The primary applica-
tion for the offset impedance is to guarantee correct identification of fault direction on series compensated lines (see
the Application of settings chapter for information on how to calculate this setting). In regular applications, the offset
impedance ensures proper operation even if the negative-sequence voltage at the relaying point is very small. If this is
the intent, the offset impedance shall not be larger than the negative-sequence impedance of the protected circuit.
Practically, it shall be several times smaller. The offset impedance shall be entered in secondary ohms. See the Theory
of operation chapter for additional details.
• NEG SEQ DIR OC1 TYPE: This setting selects the operating mode for the overcurrent unit of the element. The
choices are “Neg Sequence” and “Zero Sequence”. In some applications it is advantageous to use a directional nega-
tive-sequence overcurrent function instead of a directional zero-sequence overcurrent function as inter-circuit mutual
effects are minimized.
• NEG SEQ DIR OC1 POS-SEQ RESTRAINT: This setting controls the positive-sequence restraint. Set to 0.063 (in
“Zero Sequence” mode) or 0.125 (in “Neg Sequence” mode) for backward compatibility with revisions 3.40 and earlier.
Set to zero to remove the restraint. Set higher if large system unbalances or poor CT performance are expected.
• NEG SEQ DIR OC1 FWD ECA: This setting select the element characteristic angle (ECA) for the forward direction.
The element characteristic angle in the reverse direction is the angle set for the forward direction shifted by 180°.
• NEG SEQ DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the forward direction.
• NEG SEQ DIR OC1 FWD PICKUP: This setting defines the pickup level for the overcurrent unit in the forward direc-
tion. Upon NEG SEQ DIR OC1 TYPE selection, this pickup threshold applies to zero- or negative-sequence current. When
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
• NEG SEQ DIR OC1 REV LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
• NEG SEQ DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit in the reverse direc-
tion. Upon NEG SEQ DIR OC1 TYPE selection, this pickup threshold applies to zero- or negative-sequence current. When
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
SETTINGS
Forward Pickup
Positive-Sequence Restraint
AND RUN
5 NOTE:
V_2 is negative-sequence voltage
I_2 is negative-sequence current
Voltage Polarization
The generator unbalance element protects the machine from rotor damage due to excessive negative-sequence current.
The element has an inverse time stage which is typically used for tripping and a definite time stage typically used for alarm
purposes. The inverse time stage operating characteristic is defined by the following equation:
K where Inom is the generator rated current and K is the negative-sequence capability constant nor-
T = --------------------------
- mally provided by the generator manufacturer.
2
( I 2 ⁄ I nom )
• GEN UNBAL INOM: This setting is the rated full load current of the machine.
• GEN UNBAL STG1 PICKUP: This setting defines the pickup of the stage 1 element expressed as a percentage of the
nominal current as specified by GEN UNBAL INOM setting. It is typically set at the maximum continuous negative
sequence current rating of the machine.
• GEN UNBAL STG1 K-VALUE: This setting is the negative sequence capability constant. This value is normally pro-
vided by the generator manufacturer (refer to ANSI C50.13 for details).
• GEN UNBAL STG1 TMIN: This is the minimum operate time of the stage 1 element. The stage will not operate before
this time expires. This is set to prevent false trips for faults that would be cleared normally by system protections.
• GEN UNBAL STG1 TMAX: This is the maximum operate time of the stage 1 element. This setting can be applied to
limit the maximum tripping time for low level unbalances.
• GEN UNBAL STG1 K-RESET: This setting defines the linear reset rate of the stage 1 element. It is the maximum reset
time from the threshold of tripping. This feature provides a thermal memory of previous unbalance conditions.
• GEN UNBAL STG2 PICKUP: This setting defines the pickup of the stage 2 element expressed as a percentage of the
nominal current as specified by GEN UNBAL INOM setting. The definite time element would normally be used to generate
an alarm to prompt an operator to take some corrective action. The stage 2 element would typically be set at a safe
margin below the stage 1 pickup setting.
• GEN UNBAL STG2 PKP DELAY: This is the minimum operate time of the stage 2 element. This is set to prevent nui-
sance alarms during system faults.
1000
K=1 K=4 K=15 K=40 K=100
Tmax
100
10
Tmin
5 0.1
0.01 0.1 1 10 100
830714A1.CDR
SETTINGS
GEN UNBAL
INOM:
GEN UNBAL
STG1 PICKUP:
GEN UNBAL
STG1 TMIN:
GEN UNBAL
STG1 TMAX:
SETTING
GEN UNBAL
GEN UNBAL STG1 K-VALUE:
FUNCTION:
GEN UNBAL
Disabled=0
STG1 K-RESET:
Enabled=1
AND RUN
SETTING t
GEN UNBAL
BLK:
FLEXLOGIC OPERANDS
Off=0
GEN UNBAL STG1 OP
I_2 GEN UNBAL STG1 PKP
SETTINGS
GEN UNBAL STG1 DPO
GEN UNBAL STG2
GEN UNBAL STG2 OP
PICKUP: SETTING
GEN UNBAL STG2 PKP
GEN UNBAL STG2
GEN UNBAL INOM: GEN UNBAL STG2 DPO
SETTING PKP DELAY:
OR GEN UNBAL PKP
GEN UNBAL AND RUN TPKP
SOURCE: 0 FLEXLOGIC OPERAND
I_2 > PICKUP x INOM
I_2 100 OR GEN UNBAL OP
FLEXLOGIC OPERAND
OR GEN UNBAL DPO
830713A4.CDR
SPLIT PHASE SPLIT PHASE SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4
SRC 1
SPLIT PHASE LOAD Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 2
SPLIT PHASE A Range: 0.020 to 1.500 pu in steps of 0.001
MESSAGE
PICKUP: 0.200 pu
SPLIT PHASE A Range: 0.000 to 1.000 pu in steps of 0.001
MESSAGE
OFFSET: 0.000 pu
SPLIT PHASE A SLOPE: Range: 0.0 to 100% in steps of 0.1
MESSAGE
0.0%
SPLIT PHASE B Range: 0.020 to 1.500 pu in steps of 0.001
MESSAGE
PICKUP: 0.200 pu
SPLIT PHASE B Range: 0.000 to 1.000 pu in steps of 0.001
MESSAGE
OFFSET: 0.000 pu
SPLIT PHASE B SLOPE: Range: 0.0 to 100% in steps of 0.1
MESSAGE
0.0%
SPLIT PHASE C Range: 0.020 to 1.500 pu in steps of 0.001
MESSAGE
PICKUP: 0.200 pu 5
SPLIT PHASE C Range: 0.000 to 1.000 pu in steps of 0.001
MESSAGE
OFFSET: 0.000 pu
SPLIT PHASE C SLOPE: Range: 0.0 to 100% in steps of 0.1
MESSAGE
0.0%
SPLIT PHASE MIN Range: 0.00 to 1.00 pu in steps of 0.01
MESSAGE
LOAD: 0.00 pu
SPLIT PHASE MODE: Range: Over, Over-Under
MESSAGE
Over
SPLIT PHASE DELAY: Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
0.000 s
SPLIT PHASE BLK: Range: FlexLogic™ operand
MESSAGE
Off
SPLIT PHASE TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-Reset
SPLIT PHASE EVENTS: Range: Enabled, Disabled
MESSAGE
Disabled
Some generators, due to physical construction, have windings that consist of multiple adjacent turns. It is therefore possible
for faults to develop between turns on the same phase (inter-turn faults). These faults are not detected by the stator differ-
ential protection, as there is no difference between the neutral and at the terminal currents. Split phase protection may be
applied to detect inter-turn faults in the case that the generator is wound with two three-phase windings, each brought sep-
arately out of the machine and connected in parallel. The currents in the two windings are compared, any difference indicat-
ing an inter-turn fault.
The split phase element allows a separate pickup setting to be applied for each phase. Additionally, the pickup can be
biased by the load current (slope characteristic). Two modes of operation are supported (over and over-under).
where:
I split Load CT Primary Split Phase CT Secondary
slope = ----------- × ----------------------------------------------------- × ---------------------------------------------------------------------- (EQ 5.25)
I load Load CT Secondary Split Phase CT Primary
and offset is the split phase current at no-load. In “Over” mode, the element will pickup if:
( I split – I bias > pickup ) and ( I load ≥ min_load ) (EQ 5.26)
Slope
Offset
Operate
Min Load
Iload (pu)
Operating Characteristic
I splt phs (pu)
Operate
5
Iload (pu)
Operating Characteristic (mode = over, Min Load = 0, Slope = 0)
I splt phs (pu)
Min Load
Operate
Slope
Offset
Iload (pu)
Operating Characteristic (mode = over)
830729A1.CDR
per-unit split phase current over the per-unit load current. The user should assign the split phase current and the load
current (positive sequence) to the data logger to identify the optimum value for this setting.
• SPLIT PHASE MIN LOAD: This setting specifies the minimum load (positive-sequence current) supervision level.
• SPLIT PHASE MODE: This setting specifies the mode of operation. If the “Over” mode is chosen, the element will
pickup when the split phase current is rises above the biased offset current plus the pickup setting. If “Over-under”
mode is chosen, the element will also pickup if the split phase current is falls below the biased offset current minus the
pickup setting. See the earlier description for further details.
• SPLIT PHASE DELAY: This setting specifies a time delay required to operate after the pickup condition is established.
During an external disturbance the CTs may saturate. CT saturation can cause a spurious split phase current, espe-
cially in the case where the split phase current is derived from the external summation of two split phase CTs (first fig-
ure above). In this instance, a time delay can be used to ride through the saturation event. Alternately, the CT
saturation flag can also be used to supervise the function.
SETTINGS
SPLIT PHASE A PICKUP
SPLIT PHASE A OFFSET
SETTINGS
SPLIT PHASE A SLOPE
SPLIT PHASE FUNCTION
SPLIT PHASE MIN LOAD
Enabled =1
SPLIT PHASE MODE
SPLIT PHASE BLOCK AND FLEXLOGIC OPERANDS
START
Off = 0 SETTING SPLIT PHASE PKP A
SPLIT PHASE DELAY SPLIT PHASE DPO A
t
SPLIT PHASE OP A
0
5 SETTING
SPLIT PHASE LOAD SOURCE: SETTINGS
I_1 SPLIT PHASE B PICKUP
SPLIT PHASE B OFFSET
SPLIT PHASE B SLOPE
SPLIT PHASE MIN LOAD
SETTING
SPLIT PHASE MODE
SPLIT PHASE SOURCE: FLEXLOGIC OPERANDS
START
I_A SETTING SPLIT PHASE PKP B
I_B SPLIT PHASE DELAY SPLIT PHASE DPO B
t
I_C SPLIT PHASE OP B
0
FLEXLOGIC OPERANDS
SETTINGS
OR SPLIT PHASE OP
SPLIT PHASE C PICKUP
SPLIT PHASE C OFFSET
SPLIT PHASE C SLOPE
SPLIT PHASE MIN LOAD
SPLIT PHASE MODE
FLEXLOGIC OPERANDS
START
SETTING SPLIT PHASE PKP C
SPLIT PHASE DELAY SPLIT PHASE DPO C
t
SPLIT PHASE OP C
0
ACTUAL VALUES
SPLIT PHASE A CURRENT (PU)
SPLIT PHASE B CURRENT (PU)
SPLIT PHASE C CURRENT (PU)
LOAD CURRENT (PU) 830007A1.CDR
a) MAIN MENU
PATH: SETTINGS Ø GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ VOLTAGE ELEMENTS
MESSAGE
NEG SEQ OV3
See page 5–188. 5
AUXILIARY UV1
MESSAGE See page 5–189.
AUXILIARY UV2
MESSAGE See page 5–189.
AUXILIARY OV1
MESSAGE See page 5–190.
AUXILIARY OV2
MESSAGE See page 5–190.
VOLTS/HZ 1
MESSAGE See page 5–191.
VOLTS/HZ 2
MESSAGE See page 5–191.
These protection elements can be used for a variety of applications such as:
• Undervoltage Protection: For voltage sensitive loads, such as induction motors, a drop in voltage increases the
drawn current which may cause dangerous overheating in the motor. The undervoltage protection feature can be used
to either cause a trip or generate an alarm when the voltage drops below a specified voltage setting for a specified time
delay.
• Permissive Functions: The undervoltage feature may be used to block the functioning of external devices by operat-
ing an output relay when the voltage falls below the specified voltage setting. The undervoltage feature may also be
used to block the functioning of other elements through the block feature of those elements.
• Source Transfer Schemes: In the event of an undervoltage, a transfer signal may be generated to transfer a load
from its normal source to a standby or emergency power source.
The undervoltage elements can be programmed to have a definite time delay characteristic. The definite time curve oper-
ates when the voltage drops below the pickup level for a specified period of time. The time delay is adjustable from 0 to
600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delay char-
acteristic.
The undervoltage delay setting defines the family of curves shown below.
D
T = ---------------------------------
- (EQ 5.28)
⎛ 1 – ------------------
V ⎞
⎝ V ⎠
pickup
% of voltage pickup
842788A1.CDR
NOTE
This element may be used to give a desired time-delay operating characteristic versus the applied fundamental voltage
(phase-to-ground or phase-to-phase for wye VT connection, or phase-to-phase for delta VT connection) or as a definite
time element. The element resets instantaneously if the applied voltage exceeds the dropout voltage. The delay setting
selects the minimum operating time of the phase undervoltage. The minimum voltage setting selects the operating voltage
below which the element is blocked (a setting of “0” will allow a dead source to be considered a fault condition).
SETTING SETTING
PHASE UV1 PHASE UV1
FUNCTION: PICKUP:
Disabled = 0 PHASE UV1
Enabled = 1 CURVE:
PHASE UV1
SETTING DELAY: FLEXLOGIC OPERANDS
AND
PHASE UV1 AND RUN VAG or VAB < PICKUP PHASE UV1 A PKP
BLOCK: t PHASE UV1 A DPO
Off = 0 PHASE UV1 A OP
V
SETTING
SETTING AND RUN VBG or VBC< PICKUP PHASE UV1 B PKP
}
PHASE UV1
t PHASE UV1 B DPO
PHASE UV1 SOURCE: MINIMUM VOLTAGE:
PHASE UV1 B OP
VAG or VAB < Minimum
Source VT = Delta V
VBG or VBC < Minimum
VAB AND RUN VCG or VCA < PICKUP PHASE UV1 C PKP
VCG or VCA < Minimum
VBC t PHASE UV1 C DPO
VCA PHASE UV1 C OP
Source VT = Wye V
FLEXLOGIC OPERAND
SETTING OR PHASE UV1 PKP
827039AB.CDR
The phase overvoltage element may be used as an instantaneous element with no intentional time delay or as a definite
time element. The input voltage is the phase-to-phase voltage, either measured directly from delta-connected VTs or as cal-
5 culated from phase-to-ground (wye) connected VTs. The specific voltages to be used for each phase are shown below.
SETTINGS
SETTING
PHASE OV1 PICKUP
PHASE OV1 SETTING DELAY:
FUNCTION: FLEXLOGIC OPERANDS
PHASE OV1 PHASE OV1 RESET
Disabled = 0 PICKUP: DELAY: PHASE OV1 A PKP
Enabled = 1 PHASE OV1 A DPO
RUN tPKP
VAB ≥ PICKUP PHASE OV1 A OP
tRST
PHASE OV1 B PKP
SETTING
AND RUN tPKP PHASE OV1 B DPO
PHASE OV1 VBC ≥ PICKUP
BLOCK: PHASE OV1 B OP
tRST
RUN PHASE OV1 C PKP
Off = 0
VCA ≥ PICKUP tPKP PHASE OV1 C DPO
PHASE OV1 C OP
tRST
SETTING
PHASE OV1
SOURCE: FLEXLOGIC OPERAND
Source VT = Delta OR PHASE OV1 OP
VAB
VBC
FLEXLOGIC OPERAND
VCA
AND PHASE OV1 DPO
Source VT = Wye
FLEXLOGIC OPERAND
OR PHASE OV1 PKP
827066A7.CDR
5 The negative-sequence overvoltage element may be used to detect loss of one or two phases of the source, a reversed
phase sequence of voltage, or a non-symmetrical system voltage condition.
SETTING
NEG SEQ OV1
FUNCTION:
Disabled = 0
SETTING
Enabled = 1
NEG SEQ OV1 PICKUP: SETTINGS
SETTING NEG SEQ OV1 PICKUP
AND RUN DELAY:
NEG SEQ OV1 BLOCK: FLEXLOGIC OPERANDS
NEG SEQ OV1 RESET
NEG SEQ OV1 PKP
DELAY:
Off = 0 NEG SEQ OV1 DPO
t PKP
t RST NEG SEQ OV1 OP
SETTING
V_2 or 3 × V_2 ≥ PKP
NEG SEQ OV1 SIGNAL
SOURCE:
Wye VT Delta VT
V_2 3 × V_2 827839A3.CDR
827849A2.CDR
The G60 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage
conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM
5 SETUP Ö AC INPUTS ØÖ VOLTAGE BANK X5 ØÖ AUXILIARY VT X5 SECONDARY is the per-unit (pu) base used when setting the
pickup level.
In the G60, this element is used to detect stator ground faults by measuring the voltage across the neutral resistor.
SETTING
AUX OV1
FUNCTION:
Disabled=0
SETTING
Enabled=1
AUX OV1 PICKUP: SETTING
SETTING
AND RUN AUX OV1 PICKUP
DELAY :
AUX OV1 BLOCK:
AUX OV1 RESET
Off=0 DELAY :
FLEXLOGIC OPERANDS
Vx < Pickup tPKP
SETTING tRST AUX OV1 OP
AUX OV1 DPO
AUX OV1 SIGNAL
SOURCE: AUX OV1 PKP
AUXILIARY VOLT (Vx)
827836A2.CDR
The per-unit volts-per-hertz (V/Hz) value is calculated using the maximum of the three-phase voltage inputs or the auxiliary
voltage channel Vx input, if the source is not configured with phase voltages. To use the V/Hz element with auxiliary volt-
age, set SYSTEM SETUP ÖØ SIGNAL SOURCES Ö SOURCE 1(6) ÖØ SOURCE 1(6) PHASE VT to “None” and SOURCE 1(6) AUX VT
to the corresponding voltage input bank. If there is no voltage on the relay terminals in either case, the per-unit V/Hz value
is automatically set to “0”. The per unit value is established as per voltage and nominal frequency power system settings as
follows:
1. If the phase voltage inputs defined in the source menu are used for V/Hz operation, then “1 pu” is the selected SYSTEM
SETUP Ö AC INPUTS ÖØ VOLTAGE BANK N ÖØ PHASE VT N SECONDARY setting, divided by the divided by the SYSTEM
SETUP ÖØ POWER SYSTEM Ö NOMINAL FREQUENCY setting.
2. If the voltage bank connection value is selected as “Delta”, then the phase-to-phase nominal voltage is used to define
the per-unit value. If the voltage bank connection value is selected as “Wye”, then the VOLTS/HZ 1 VOLTAGE MODE set-
ting further defines the operating quantity and per-unit value for this element. If the voltage mode is set as “Phase-
phase”, then the operating quantity for this element will be phase-to-phase nominal voltage. Likewise, if the voltage
mode is set to “Phase-ground”, then the operating quantity for this element will be the phase-to-ground nominal volt-
age. It is beneficial to use the phase-to-phase voltage mode for this element when the G60 device is applied on an iso-
lated or resistance-grounded system.
3. When the auxiliary voltage Vx is used (regarding the condition for “None” phase voltage setting mentioned above),
then the 1 pu value is the SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE BANK N ÖØ AUXILIARY VT N SECONDARY setting
divided by the SYSTEM SETUP ÖØ POWER SYSTEM Ö NOMINAL FREQUENCY setting.
4. If V/Hz source is configured with both phase and auxiliary voltages, the maximum phase among the three voltage
channels at any given point in time is the input voltage signal for element operation, and therefore the per-unit value
will be calculated as described in Step 1 above. If the measured voltage of all three phase voltages is 0, than the per-
unit value becomes automatically 0 regardless of the presence of auxiliary voltage.
SETTINGS
Pickup
Voltage Mode
SETTINGS
Curve
Function
TD Multiplier
Enabled = 1
T-Reset
Disabled = 0
AND RUN
Block
t
Off = 0 FLEXLOGIC OPERANDS
VOLTS PER HERTZ 1 PKP
VOLTS PER HERTZ 1 DPO
SETTING
VOLTS PER HERTZ 1 OP
Source
V/Hz
V/Hz 828003A6.CDR
Time
delay
setting
INVERSE CURVE B:
The curve for the Volts/Hertz Inverse Curve B shape is derived from the formula:
TDM V
T = ---------------------------------------------- when ---- > Pickup (EQ 5.30)
⎛V F
----⎞
⎝ F⎠ ⁄ Pickup – 1
Time
delay
setting 5
Time
delay
setting
The operating characteristic is shaped out of two offset mho circles shifted down along the imaginary axis as shown below.
X
X’d
2
C1 = Center of element 1 = (Zb + X’d) / 2
C1
C2
R1 = Radius of element 1 = Zb / 2
Zb
C2 = Center of element 2 = (Xd + X’d) / 2
R1
R2 = Radius of element 2 = Xd / 2
Xd
Zb = Base impedance of the machine
830711A1.CDR
SETTING SETTINGS
LOSS EXCIT BLK: LOSS OF EXCITATION
FUNCTION:
Off=0 BLOCK (See description) FLEXLOGIC OPERANDS
LOSS OF EXCITATION
CENTER 1: LOSS EXCIT STG1 PKP
COMPARATOR
SETTING LOSS EXCIT STG1 DPO
RUN LOSS OF EXCITATION
I_1 > 0.05 pu SETTING
LOSS OF EXCITATION UV RADIUS 1:
SUPV 1 : LOSS OF EXCITATION
AND RUN
PKP DELAY 1:
Disabled=1 FLEXLOGIC OPERAND
OR 0 ms
Enabled=0 LOSS EXCIT STG1 OP
20 ms 0 ms
This element provides protection against energization while the generator is at standstill or reduced speed. The feature is
armed using either the AND or OR combination of the undervoltage and machine off-line conditions, selected with the
ACCDNT ENRG ARMING MODE setting (see below). The undervoltage condition is determined from the measured voltages.
The machine off-line status is indicated by a dedicated FlexLogic™ operand. Once armed, the accidental energization fea-
ture operates upon detecting an overcurrent condition in any of the stator phases.
RUN
SETTING IC > Pickup
ACCDNT ENRG
SOURCE: SETTINGS
IA ACCDNT ENRG UV
IB PICKUP:
FLEXLOGIC OPERANDS
IC RUN
AND ACCDNT ENRG OP
VT CONNECTION VAB < Pickup
ACCDNT ENRG DPO
WYE DELTA RUN
VBC < Pickup AND
VAG - VBG VAB
VBG - VCG VBC RUN
VCA < Pickup AND
VCG - VAG VCA
SETTING
5s
ACCDNT ENRG OR
0.25 s FLEXLOGIC OPERAND
OFFLINE: OR
ACCDNT ENRG ARMED
Off = 0
SETTING AND
ACCDNT ENRG
ARMING MODE:
UV or Offline = 1 830004A3.CDR
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ POWER ÖØ SENSITIVE DIRECTIONAL POWER
Ö DIRECTIONAL POWER 1(2)
DIRECTIONAL DIR POWER 1 Range: Disabled, Enabled
POWER 1 FUNCTION: Disabled
DIR POWER 1 Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
DIR POWER 1 Range: 0 to 359° in steps of 1
MESSAGE
RCA: 0°
DIR POWER 1 Range: 0 to 0.95° in steps of 0.05
MESSAGE
CALIBRATION: 0.00°
DIR POWER 1 STG1 Range: –1.200 to 1.200 pu in steps of 0.001
MESSAGE
SMIN: 0.100 pu
DIR POWER 1 STG1 Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.50 s
DIR POWER 1 STG2 Range: –1.200 to 1.200 pu in steps of 0.001
MESSAGE
SMIN: 0.100 pu
DIR POWER 1 STG2 Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 20.00 s
5 MESSAGE
DIR POWER 1 BLK:
Off
Range: FlexLogic™ operand
The sensitive directional power element responds to three-phase directional power and is designed for reverse power and
low forward power applications for synchronous machines or interconnections involving co-generation. The relay measures
the three-phase power from either full set of wye-connected VTs or full-set of delta-connected VTs. In the latter case, the
two-wattmeter method is used. Refer to the UR-series metering conventions section in chapter 6 for details regarding the
active and reactive powers used by the sensitive directional power element.
The element has an adjustable characteristic angle and minimum operating power as shown in the Directional power char-
acteristic diagram. The element responds to the following condition:
P cos θ + Q sin θ > SMIN (EQ 5.34)
where: P and Q are active and reactive powers as measured per the UR-series metering convention,
θ is a sum of the element characteristic (DIR POWER 1 RCA) and calibration (DIR POWER 1 CALIBRATION) angles, and
SMIN is the minimum operating power
The operating quantity is displayed in the ACTUAL VALUES Ö METERING ÖØ SENSITIVE DIRECTIONAL POWER 1(2) actual
value. The element has two independent (as to the pickup and delay settings) stages for alarm and trip, respectively.
n
io
ct
re
Di
OPERATE
RCA+
CALIBRATION
SMIN
P
+
RESTRAIN
-
(a) Q (b) Q
RESTRAIN
OPERATE RESTRAIN OPERATE
P P
(c) Q (d) Q
OPERATE OPERATE
P P
RESTRAIN RESTRAIN
RCA = 0o RCA = 0o
SMIN < 0 SMIN > 0
(e) Q
OPERATE
(f) Q
RESTRAIN
RESTRAIN OPERATE
P P
842702A1.CDR
• DIR POWER 1 RCA: Specifies the relay characteristic angle (RCA) for the sensitive directional power function. Appli-
cation of this setting is threefold:
1. It allows the element to respond to active or reactive power in any direction (active overpower/underpower, etc.).
2. Together with a precise calibration angle, it allows compensation for any CT and VT angular errors to permit more
sensitive settings.
3. It allows for required direction in situations when the voltage signal is taken from behind a delta-wye connected
power transformer and the phase angle compensation is required.
For example, the active overpower characteristic is achieved by setting DIR POWER 1 RCA to “0°”, reactive overpower by
setting DIR POWER 1 RCA to “90°”, active underpower by setting DIR POWER 1 RCA to “180°”, and reactive underpower by
setting DIR POWER 1 RCA to “270°”.
• DIR POWER 1 CALIBRATION: This setting allows the relay characteristic angle to change in steps of 0.05°. This may
be useful when a small difference in VT and CT angular errors is to be compensated to permit more sensitive settings.
This setting virtually enables calibration of the directional power function in terms of the angular error of applied VTs
and CTs. The element responds to the sum of the DIR POWER 1 RCA and DIR POWER 1 CALIBRATION settings.
• DIR POWER 1 STG1 SMIN: This setting specifies the minimum power as defined along the relay characteristic angle
(RCA) for the stage 1 of the element. The positive values imply a shift towards the operate region along the RCA line;
the negative values imply a shift towards the restrain region along the RCA line. Refer to the Directional power sample
applications figure for details. Together with the RCA, this setting enables a wide range of operating characteristics.
This setting applies to three-phase power and is entered in per-unit (pu) values. The base quantity is 3 × VT pu
base × CT pu base.
For example, a setting of 2% for a 200 MW machine is 0.02 × 200 MW = 4 MW. If 7.967 kV is a primary VT voltage and
10 kA is a primary CT current, the source pu quantity is 239 MVA, and thus, SMIN should be set at 4 MW / 239 MVA =
0.0167 pu ≈ 0.017 pu. If the reverse power application is considered, RCA = 180° and SMIN = 0.017 pu.
5 The element drops out if the magnitude of the positive-sequence current becomes virtually zero, that is, it drops below
the cutoff level.
• DIR POWER 1 STG1 DELAY: This setting specifies a time delay for stage 1. For reverse power or low forward power
applications for a synchronous machine, stage 1 is typically applied for alarming and stage 2 for tripping.
SETTING
DIR POWER 1
FUNCTION:
Enabled = 1
SETTINGS SETTING
SETTING DIR POWER 1 RCA: DIR POWER 1 STG1
DIR POWER 1 BLK: DELAY:
AND
DIR POWER 1 OP
Three-phase reactive power (Q)
DIR POWER 1 STG2 DPO
DIR POWER 1 STG2 OP
SETTING
DIR POWER 1 STG2
DELAY:
tPKP
100 ms
842003A3.CDR
a) MAIN MENU
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ STATOR GROUND
• In addition the relay should be set properly with frequency tracking enabled and the source used as FREQUENCY AND
PHASE REFERENCE should be the one connected to generator terminal VTs. The tracking frequency, which is essen-
tially the generator frequency, will be used to block the sub-harmonic stator ground protection and auxiliary over volt-
age protection in the frequency range of 15 to 25 Hz.
The 100% stator ground function responds to third harmonic voltage measured at the generator neutral and output termi-
nals. When used in conjunction with the neutral overvoltage (fundamental frequency) element, it provides 100% ground
fault protection of the stator windings. Since the amount of third harmonic voltage that appears in the neutral is both load
and machine dependent, the protection method of choice is an adaptive method. The following formula is used to create an
adaptive operating quantity based on the amount of third harmonic that appears at the generator terminals.
V N ( 3rd ) V 0 ( 3rd )
--------------------------------------------- < Pickup and --------------------------------------------- > 1 – Pickup and V N ( 3rd ) + V 0 ( 3rd ) > Supervision (EQ 5.35)
V N ( 3rd ) + V 0 ( 3rd ) V N ( 3rd ) + V 0 ( 3rd )
where: VN(3rd) is a magnitude of the 3rd harmonic in the voltage measured at the machine neutral point measured via an
auxiliary channel of the VT bank, and
V0(3rd) is a magnitude of the 3rd harmonic in the zero-sequence voltage measured at the machine terminals.
This element requires wye-connected VTs for measurement of the third harmonic in the zero-sequence
voltage at the generator output terminals.
NOTE
E3
E3
E3
k
Vn
Va Vb Vc
Vn (3rd)
< Pickup
Vn (3rd) + V0 (3rd)
Va (3rd)
and
V0 (3rd) Vb (3rd)
Vn (3rd) > 1 - Pickup S
Vn (3rd) + V0 (3rd) 3V0 (3rd) Vc (3rd)
and
830737A1.CDR
Therefore, under the normal conditions described above, we set the operating quantities as follows:
VN
Pickup > ----------------------- = 7.07
----------- = 0.707 pu
VN + V0 10 (EQ 5.38)
Supervision < V N + V 0 = 10 pu
In actual practice, the |VN| / |VN + V0| ratio may vary from 0.4 to 0.85 under normal conditions. The pickup and supervision
setpoints are determined by evaluating the operating quantities during a fault condition (refer to example 2 for details).
Example 2: Operating quantities for a fault at a fraction k from the neutral grounding point.
For analysis, consider the above figure and assume that E 3 = 10 V , R = 5Ω, X c = 5Ω, and k = 0.15 .
In this case, we have the magnitude of the neutral voltage at:
V N = k × E 3 = 0.15 × 10 = 1.5 (EQ 5.39)
( 1 – k )E 3 + ( 1 – k )E 3 + ( 1 – k )E 3 3 × 0.85 × 10
- = ---------------------------------- = 8.5 ⇒ V N + V 0 = 8.5 + 1.5 = 10
V 0 = ------------------------------------------------------------------------------------
3 3 (EQ 5.40)
⇒ V N + V 0 = 10 pu
Therefore, for faults at a fraction k = 0.15 from the neutral grounding point, we set the operating quantities as follows:
VN 1.5
Pickup > ----------------------- = -------- = 0.15 pu
VN + V0 10 (EQ 5.41)
Supervision < V N + V 0 = 10 pu
SETTING
100% STATOR GND STG1
5 SETTING
PICKUP:
100% STATOR GND STG1
100% STATOR GROUND SUPV:
FUNCTION:
100% STATOR GND STG2 SETTING
Disabled=0
PICKUP: 100% STATOR GND STG1
Enabled=1
100% STATOR GND STG2 DELAY:
FLEXLOGIC OPERAND
SUPV: t PKP
SETTING 100% STATOR STG1 OP
AND RUN 20 ms
100% STATOR GND BLK: Vaux
< Pickup FLEXLOGIC OPERAND
Vaux + V_0 FLEXLOGIC OPERANDS
Off=0 100% STATOR DPO
& 100% STATOR STG1 DPO
V_0 AND 100% STATOR STG1 PKP
SETTING < 1-Pickup
Vaux + V_0 FLEXLOGIC OPERAND
STATOR GROUND
SOURCE: & OR 100% STATOR PKP
Vaux (3rd harmonic) Vaux + V_0 < Supv FLEXLOGIC OPERANDS
V_0 (3rd harmonic) AND 100% STATOR STG2 PKP
V_1 (fundamental) 100% STATOR STG2 DPO
V_1 > 0.5 pu
FLEXLOGIC OPERAND
SETTING
OR 100% STATOR OP
100% STATOR GND STG2
DELAY:
FLEXLOGIC OPERAND
t PKP
100% STATOR STG2 OP
20 ms
830003A5.CDR
SETTING
3RD HARM NTRL UV
FUNCTION:
Disabled = 0
SETTINGS
Enabled = 1
3RD HARM NTRL UV
PICKUP:
SETTING
AND RUN
Vaux < Pickup
3RD HARM NTRL UV BLK:
Off = 0
SETTINGS SETTINGS
FLEXLOGIC OPERANDS
3RD HARM NTRL UV 3RD HARM NTRL UV
3RD HARM NTRL UV PKP
MAX POWER: PKP DELAY:
SETTING 3RD HARM NTRL UV DPO
3RD HARM NTRL UV
STATOR GROUND AND 3RD HARM NTRL UV OP
MIN POWER: 20 ms
SOURCE:
RUN
Vaux (3rd harmonic)
3 Phase Real Power Min < 3 Phase Power < Max
V_1
SETTINGS
3RD HARM NTRL UV
VOLT SUPV:
830005A4.CDR
RUN
V_1 > Pickup
A voltage source placed at the neutral of the generator will produce a current for ground faults anywhere on the stator wind-
ing. This source is coupled to the primary circuit using the existing neutral grounding transformer. The following figure
shows a typical high impedance grounded generator that is protected against ground faults using the sub-harmonic injec-
tion method. The neutral resistor is chosen to limit the ground fault current to a low value (less than 25 A) in order to mini-
mize damage. A sub-harmonic frequency voltage signal is injected into the neutral of the generator. Under normal
conditions a resulting current flows through the surge capacitors (Cs) and through the stray capacitance of the stator and
step-up transformer windings. When a ground fault develops on the stator winding, an additional current flows through the
resistance RG. The value of RG is derived from the measurement of the injected voltage and the resulting current.
An AC signal is injected so that it can be coupled through an injection transformer to the primary circuit. The signal is of a
low frequency in order to minimize the effects of the capacitance of the primary circuit. A frequency of 20 Hz is chosen.
Referring to the following figure, the admittance seen looking into the grounding transformer is:
2 IG 1
Y = N × ------- = -------- + jωC T (EQ 5.42)
VX RG
Stator Step Up
winding Transformer
Grounding
IG transformer
20 Hz
injection
Coupling VX Neutral
module
filter resistor
The difference in angle can be used as the SH CT ANGLE COMPEN setting. The preferred method of doing this is by
inserting a resistance equal to the SH STATOR GND STG2 PICKUP setting at the neutral of the generator and compensat-
ing the angle at this setting.
• SH STATOR GND OC PICKUP: This setting specifies the backup overcurrent pickup level based on sub-harmonic cur-
rent. This protection can be used in addition to the sub-harmonic injection based 100% ground fault and fundamental
phasor over voltage based 95% ground fault protection. One per-unit value of current is the sensitive ground CT sec-
ondary rating setting, which is always 5 A since the CT used is rated for 5 A secondary.
• SH STATOR GND OC DELAY: This setting specifies a time delay for sub-harmonic current based backup over current
protection. Thermal capabilities of the loading resistor or neutral grounding transformer should be considered while
setting this delay.
• SH STATOR GND Vsupv: The 20 Hz source can be monitored using this voltage supervision. This setting in pu pro-
vides the voltage level below which if the sub-harmonic voltage phasor magnitude remains for a period of 10 seconds,
the SH STATOR GND TRB OP operand will be asserted. One per-unit value of voltage is the auxiliary VT nominal sec-
ondary voltage setting or the equivalent primary voltage if used in primary. A typical setting of 1 V is suggested. How-
ever, when the neutral grounding transformer’s load resistance is less than 0.5 ohms, the use of voltage supervision is
not recommended.
• SH STATOR GND Isupv: The 20 Hz source can be monitored using this current supervision. This setting in per-unit
values provides the current level below which if the sub-harmonic current phasor magnitude remains for a period of 10
seconds, the SH STATOR GND TRB OP operand will be asserted. One per-unit current is the sensitive ground CT sec-
ondary rating setting or the primary rating if used in primary. A typical setting of 0.002 pu (=10 mA in secondary) is rec-
ommended with the provided 5 A secondary CT.
The logic for the sub-harmonic stator ground fault feature is shown below.
SETTINGS
Function
5
= Enabled
Block SETTING SETTING
= Off Stage 1 Pickup Stage 1 Pickup Delay
AND RUN TPKP FLEXLOGIC OPERANDS
ACTUAL VALUE COMPARATOR Rg ≤ Pickup SH STATOR GND STG1 OP
Tracking Frequency 15 Hz < f < 25 Hz 0
SH STATOR GND STG1 PKP
SH STATOR GND STG1 DPO
SETTINGS CALCULATE SETTING SETTING
Function Stage 2 Pickup Stage 2 Pickup Delay
= <Rs> RUN TPKP FLEXLOGIC OPERANDS
Function
Rg ≤ Pickup SH STATOR GND STG2 OP
= <Rp> 0
Calculate SH STATOR GND STG2 PKP
resistance SH STATOR GND STG2 DPO
ACTUAL VALUES
SETTING SETTING
Vaux (SH)
Ground OC Pickup Ground OC Delay
Ignd (SH)
RUN TPKP FLEXLOGIC OPERANDS
Ignd ≥ Pickup SH STATOR GND OC OP
0
SH STATOR GND OC PKP
SH STATOR GND OC DPO
SETTING
Current Supervision
RUN
Ignd ≤ Pickup
TIMER
10 sec. FLEXLOGIC OPERANDS
SETTING OR SH STATOR GND TRB OP
0
Voltage Supervision SH STATOR GND TRB PKP
RUN SH STATOR GND TRB DPO
Vx ≤ Pickup
ACTUAL VALUES
Stator Ground Resistance
SH Injection Amps
SH Injection Volts
830009A1.CDR
A block diagram of the field ground detection scheme using the G60 and the GPM-F is shown below. The field winding of a
synchronous generator is represented electrically by the impedance ZF = ZF1 + ZF2. Under normal conditions the field cir-
cuit is ungrounded. The capacitance CF is the stray capacitance of the field, distributed along the field winding. This capac-
itance represents the only path for current to flow to ground under normal conditions.
dcmA
IFLD
UR -series
G60 device Hall-effect CT
RS485 CF
communications Field IG
ground RG ZF1 VFLD Exciter
module
ZF2
830751A3.CDR
Measurement of RG is accomplished by injecting a voltage, VINJ and measuring the resulting current, IG. The measurement
algorithm must be capable of discriminating between capacitive current due to CF (which can be significant) and resistive
current due to a fault. The exciter voltage, VFLD is a DC value with a small ripple such that the impedance of the field is
essentially resistive. The current IFLD is a DC current with a range of tens, hundreds, or thousands of amps.
IEXC RC IEXC
ZF1 ZF1
RG RG
LOC VEXC LOC VEXC
ZF2 ZF2
RCL RC
Where IG1 is the current flowing due to VINJ1 and IG2 is the current flowing due to VINJ2. Solving for RG we get:
( V INJ1 – V INJ2 ) – ( I G1 – I G2 ) × R CL
R G = -----------------------------------------------------------------------------------------
- (EQ 5.44)
I G1 – I G2
b) FIELD GROUND
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö FIELD GROUND PROTECTION ÖØ FIELD GROUND
The following settings are available for the field ground fault detector function.
• FIELD GROUND INJECTION FREQUENCY: This setting specifies the frequency of the signal to be injected into the
field winding for detecting ground faults. The injection frequency selection will depend on the value of field winding
capacitance to ground. The following simple formula can be used to set the injection frequency when the field winding
capacitance is known in μF.
F inj = 2.5
-------- (EQ 5.46)
CF
Where CF is in microfarads. Some example injection frequency settings are given in the table below for various field
winding capacitance values. For field winding capacitances greater than 10 μF, resistance measurements will be less
accurate.
Table 5–25: EXAMPLE INJECTION FREQUENCY SETTINGS
CF FINJ
1 μF 2.50 Hz
2 μF 1.50 Hz
3 μF 0.83 Hz
4 μF 0.63 Hz
5 μF 0.50 Hz
6 μF 0.42 Hz
7 μF 0.36 Hz
8 μF 0.31 Hz
9 μF 0.28 Hz
10 μF 0.25 Hz
• INJ CONNECTION TYPE: Field ground protection can be implemented by injecting a low frequency signal either into
both positive and negative terminals of the field winding or only into the negative terminal of the field winding. Refer to
the instruction manual of the field ground module for wiring difference between single point and double point injections.
For single point injection, the G60 provides the feature of fault location. In case of a field ground fault, the G60 displays
the location of the fault in the field winding as a percentage of the winding from the negative terminal. If the preference
is to keep the injection symmetrical into the field winding, then double point injection has to be done but the fault loca-
tion feature is not available. This setting has to match the type of connection on the field ground module.
• FIELD GROUND STG1 PICKUP: If the measured ground resistance is less than the value specified by this setting, 5
then the stage 1 element will pickup. Normally stage 1 is used to raise alarms and typical settings may fall in the range
of 10 to 40 kΩ.
• FIELD GROUND STG1 DELAY: This setting specifies a time delay for stage 1. Typical settings are in the range of 10
to 15 seconds. This delay will have to be added to the operating time of the element to obtain the overall delay.
• FIELD GROUND STG2 PICKUP: If the measured ground resistance is less than the value specified by this setting,
then the stage 2 element will pickup. Normally stage 2 is used to raise trip signals and typical settings may fall in the
range of 2 to 5 kΩ.
• FIELD GROUND STG2 DELAY: This setting specifies a time delay for stage 2. Typical settings are in the range of 3 to
5 seconds. This delay will have to be added to the operating time of the element to obtain the overall delay.
• FIELD GROUND UC PICKUP: This setting specifies the ground undercurrent level below which a brush open condi-
tion shall be detected. A brush lift-off condition will prevent the field ground detector from operating. This is detected by
calculating the RMS value of the ground current. It will normally have a non-zero value due to the capacitance of the
field winding. A drop in this signal indicates an open circuit in the injection path. To set this value, the ground current in
a healthy operating condition preferably with zero field voltage should be recorded from G60 actual values display
(performed during commissioning). Configure this setting to be 60 to 70% of that normal value.
• FIELD GROUND UC DELAY: This setting specifies a time delay for field ground undercurrent element. Typical settings
are in the range of 20 to 30 seconds. This delay will have to be added to the operating time of the element to obtain the
overall delay.
• FIELD GROUND FUNCTION BLK: This setting selects a FlexLogic™ operand to block the field ground function.
COMMAND TO GPM-F
SETTINGS Block 0.1 to 3.0 Hz Injection
Function
= Enabled
Block SETTING SETTING
= Off Stage 1 Pickup Stage 1 Pickup Delay
AND RUN TPKP FLEXLOGIC OPERANDS
Rg ≤ Pickup EIELD GND STG1 OP
0
EIELD GND STG1 PKP
EIELD GND STG1 DPO
SETTING SETTING
Stage 2 Pickup Stage 2 Pickup Delay
RUN TPKP FLEXLOGIC OPERANDS
Rg ≤ Pickup EIELD GND STG2 OP
0
EIELD GND STG2 PKP
EIELD GND STG2 DPO
SETTING SETTING
Ground UC Pickup Ground UC Delay
RUN TPKP FLEXLOGIC OPERANDS
Ig_RMS ≤ Pickup FIELD GND INJ UC OP
0
FIELD GND INJ UC PKP
FIELD GND INJ UC DPO
ACTUAL VALUES
Field Ground Resistance
Field Ground Current
Injected Voltage
From Fault Location
injection Field Voltage
unit
TIMER
5 sec. SELF-TEST MESSAGE
GPM-F failure GPM-F FAILURE
5 sec.
5
830010A2.CDR
c) FIELD CURRENT
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö FIELD GROUND PROTECTION ÖØ FIELD CURRENT
The following settings are available for the field current fault detector function.
• FIELD CURRENT ORIGIN: This setting selects the dcmA input to be used for the field current protection element. A
dcmA input can be selected from up to 24 possible inputs, depending on the number of installed transducer modules.
In a HardFiber G60 device, this setting can point to one of the TRD inputs mapped to a Brick dcmA input. In both
cases, the minimum and maximum scaling settings of that transducer input are used to perform the per-unit conver-
sion. The unit setting shall be configured as “Amps” if the transducer input is used.
These minimum and maximum settings are set as per the Hall sensor current rating. The per-unit computation is
scaled to a base equal to the maximum value setting, with a zero per-unit value corresponding to zero in the unit sys-
tem used by the maximum value setting. For example, in the case where the maximum value setting is 100 A, a trip
level of 75 A is achieved by setting the operate level at 0.75 pu, regardless of the range (for example, 4 to 20 mA, 0 to
20 mA etc.) and regardless of the minimum value setting.
• FIELD OVER CURRENT PICKUP: This setting specifies the field current level above which the overcurrent element
picks up.
• FIELD OVER CURRENT DELAY: This setting specifies a time delay for the overcurrent element. This delay is added
to the operating time of the element to obtain the overall delay.
• FIELD UNDER CURRENT PICKUP: This setting specifies the field current level above which the undercurrent ele-
ment picks up.
• FIELD UNDER CURRENT DELAY: This setting specifies a time delay for undercurrent element. This delay is added to
the operating time of the element to obtain the overall delay.
• FIELD CURRENT BLK: This setting allows the user to select a FlexLogic™ operand to block the field ground function.
The field current fault detector function logic is shown below.
SETTINGS
Function SETTING SETTING
= Enabled Field OC Pickup Field OC Delay
Block AND RUN TPKP FLEXLOGIC OPERANDS
= Off IFLD ≥ Pickup FIELD OC OP
0
FIELD OC PKP
FIELD OC DPO 5
SETTING SETTING
Field UC Pickup Field UC Delay
RUN TPKP FLEXLOGIC OPERANDS
IFLD ≤ Pickup FIELD UC OP
0
FIELD UC PKP
FIELD UC DPO
SETTINGS
Field Current Origin ACTUAL VALUE
= <Value> Field Current
830011A1.CDR
Control elements are generally used for control rather than protection. See the Introduction to Elements section at the
beginning of this chapter for further information.
The trip bus element allows aggregating outputs of protection and control elements without using FlexLogic™ and assign-
ing them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip condition-
ing such as latch, delay, and seal-in delay are available.
The easiest way to assign element outputs to a trip bus is through the EnerVista UR Setup software A protection summary
is displayed by navigating to a specific protection or control protection element and checking the desired bus box. Once the
desired element is selected for a specific bus, a list of element operate-type operands are displayed and can be assigned
to a trip bus. If more than one operate-type operand is required, it may be assigned directly from the trip bus menu.
SETTINGS
TRIP BUS 1 INPUT 1
SETTINGS
= Off
TRIP BUS 1 PICKUP
TRIP BUS 1 INPUT 2
DELAY
= Off Non-volatile,
TRIP BUS 1 RESET
OR set-dominant
***
DELAY
AND S TPKP FLEXLOGIC OPERAND
TRIP BUS 1 INPUT 16 TRIP BUS 1 OP
Latch
= Off TRST
R
SETTINGS
TRIP BUS 1 FLEXLOGIC OPERAND
FUNCTION
TRIP BUS 1 PKP
= Enabled
TRIP BUS 1 BLOCK AND
= Off
SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
OR
FLEXLOGIC OPERAND
RESET OP 842023A1.CDR
5 MESSAGE
GROUP 6 NAME: Range: up to 16 alphanumeric characters
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the GROUPED
ELEMENTS settings menu. The faceplate Settings In Use LEDs indicate which active group (with a non-flashing energized
LED) is in service.
The SETTING GROUPS BLK setting prevents the active setting group from changing when the FlexLogic™ parameter is set to
"On". This can be useful in applications where it is undesirable to change the settings under certain conditions, such as the
breaker being open.
The GROUP 2 ACTIVATE ON to GROUP 6 ACTIVATE ON settings select a FlexLogic™ operand which, when set, will make the
particular setting group active for use by any grouped element. A priority scheme ensures that only one group is active at a
given time – the highest-numbered group which is activated by its ACTIVATE ON parameter takes priority over the lower-
numbered groups. There is no activate on setting for group 1 (the default active group), because group 1 automatically
becomes active if no other group is active.
The SETTING GROUP 1 NAME to SETTING GROUP 6 NAME settings allows to user to assign a name to each of the six settings
groups. Once programmed, this name will appear on the second line of the GROUPED ELEMENTS Ö SETTING GROUP 1(6)
menu display.
The relay can be set up via a FlexLogic™ equation to receive requests to activate or de-activate a particular non-default
settings group. The following FlexLogic™ equation (see the figure below) illustrates requests via remote communications
(for example, VIRTUAL INPUT 1 ON) or from a local contact input (for example, CONTACT IP 1 ON) to initiate the use of a par-
ticular settings group, and requests from several overcurrent pickup measuring elements to inhibit the use of the particular
settings group. The assigned VIRTUAL OUTPUT 1 operand is used to control the “On” state of a particular settings group.
1 VIRT IP 1 ON (VI1)
OR (2)
2 CONT IP 1 ON (H5A)
3 OR (2)
AND (3) = VIRT OP 1 (VO1)
4 PHASE TOC1 PKP
5 NOT
7 NOT
8 AND (3)
9 = VIRT OP 1 (VO1)
10 END
842789A1.CDR
The selector switch element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic.
The element provides for two control inputs. The step-up control allows stepping through selector position one step at a
time with each pulse of the control input, such as a user-programmable pushbutton. The three-bit control input allows set-
ting the selector to the position defined by a three-bit word.
The element allows pre-selecting a new position without applying it. The pre-selected position gets applied either after time-
out or upon acknowledgement via separate inputs (user setting). The selector position is stored in non-volatile memory.
Upon power-up, either the previous position is restored or the relay synchronizes to the current three-bit word (user set-
ting). Basic alarm functionality alerts the user under abnormal conditions; for example, the three-bit control input being out
of range.
• SELECTOR 1 FULL RANGE: This setting defines the upper position of the selector. When stepping up through avail-
able positions of the selector, the upper position wraps up to the lower position (position 1). When using a direct three-
bit control word for programming the selector to a desired position, the change would take place only if the control word
is within the range of 1 to the SELECTOR FULL RANGE. If the control word is outside the range, an alarm is established
by setting the SELECTOR ALARM FlexLogic™ operand for 3 seconds.
• SELECTOR 1 TIME-OUT: This setting defines the time-out period for the selector. This value is used by the relay in
the following two ways. When the SELECTOR STEP-UP MODE is “Time-out”, the setting specifies the required period of
inactivity of the control input after which the pre-selected position is automatically applied. When the SELECTOR STEP-
UP MODE is “Acknowledge”, the setting specifies the period of time for the acknowledging input to appear. The timer is
re-started by any activity of the control input. The acknowledging input must come before the SELECTOR 1 TIME-OUT
timer expires; otherwise, the change will not take place and an alarm will be set.
• SELECTOR 1 STEP-UP: This setting specifies a control input for the selector switch. The switch is shifted to a new
position at each rising edge of this signal. The position changes incrementally, wrapping up from the last (SELECTOR 1
5 FULL RANGE) to the first (position 1). Consecutive pulses of this control operand must not occur faster than every
50 ms. After each rising edge of the assigned operand, the time-out timer is restarted and the SELECTOR SWITCH 1:
POS Z CHNG INITIATED target message is displayed, where Z the pre-selected position. The message is displayed for
the time specified by the FLASH MESSAGE TIME setting. The pre-selected position is applied after the selector times out
(“Time-out” mode), or when the acknowledging signal appears before the element times out (“Acknowledge” mode).
When the new position is applied, the relay displays the SELECTOR SWITCH 1: POSITION Z IN USE message. Typically,
a user-programmable pushbutton is configured as the stepping up control input.
• SELECTOR 1 STEP-UP MODE: This setting defines the selector mode of operation. When set to “Time-out”, the
selector will change its position after a pre-defined period of inactivity at the control input. The change is automatic and
does not require any explicit confirmation of the intent to change the selector's position. When set to “Acknowledge”,
the selector will change its position only after the intent is confirmed through a separate acknowledging signal. If the
acknowledging signal does not appear within a pre-defined period of time, the selector does not accept the change
and an alarm is established by setting the SELECTOR STP ALARM output FlexLogic™ operand for 3 seconds.
• SELECTOR 1 ACK: This setting specifies an acknowledging input for the stepping up control input. The pre-selected
position is applied on the rising edge of the assigned operand. This setting is active only under “Acknowledge” mode of
operation. The acknowledging signal must appear within the time defined by the SELECTOR 1 TIME-OUT setting after the
last activity of the control input. A user-programmable pushbutton is typically configured as the acknowledging input.
• SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con-
trol word pre-selects the position using the following encoding convention:
A2 A1 A0 POSITION
0 0 0 rest
0 0 1 1
0 1 0 2
0 1 1 3
1 0 0 4
1 0 1 5
1 1 0 6
1 1 1 7
The “rest” position (0, 0, 0) does not generate an action and is intended for situations when the device generating the
three-bit control word is having a problem. When SELECTOR 1 3BIT MODE is “Time-out”, the pre-selected position is
applied in SELECTOR 1 TIME-OUT seconds after the last activity of the three-bit input. When SELECTOR 1 3BIT MODE is
“Acknowledge”, the pre-selected position is applied on the rising edge of the SELECTOR 1 3BIT ACK acknowledging
input.
The stepping up control input (SELECTOR 1 STEP-UP) and the three-bit control inputs (SELECTOR 1 3BIT A0 through A2)
lock-out mutually: once the stepping up sequence is initiated, the three-bit control input is inactive; once the three-bit
control sequence is initiated, the stepping up input is inactive.
• SELECTOR 1 3BIT MODE: This setting defines the selector mode of operation. When set to “Time-out”, the selector
changes its position after a pre-defined period of inactivity at the control input. The change is automatic and does not
require explicit confirmation to change the selector position. When set to “Acknowledge”, the selector changes its posi-
tion only after confirmation via a separate acknowledging signal. If the acknowledging signal does not appear within a
pre-defined period of time, the selector rejects the change and an alarm established by invoking the SELECTOR BIT
ALARM FlexLogic™ operand for 3 seconds.
• SELECTOR 1 3BIT ACK: This setting specifies an acknowledging input for the three-bit control input. The pre-
selected position is applied on the rising edge of the assigned FlexLogic™ operand. This setting is active only under
the “Acknowledge” mode of operation. The acknowledging signal must appear within the time defined by the SELEC-
TOR TIME-OUT setting after the last activity of the three-bit control inputs. Note that the stepping up control input and
three-bit control input have independent acknowledging signals (SELECTOR 1 ACK and SELECTOR 1 3BIT ACK, accord-
ingly).
• SELECTOR 1 POWER-UP MODE: This setting specifies the element behavior on power up of the relay.
When set to “Restore”, the last position of the selector (stored in the non-volatile memory) is restored after powering up
the relay. If the position restored from memory is out of range, position 0 (no output operand selected) is applied and
an alarm is set (SELECTOR 1 PWR ALARM).
5
When set to “Synchronize” selector switch acts as follows. For two power cycles, the selector applies position 0 to the
switch and activates SELECTOR 1 PWR ALARM. After two power cycles expire, the selector synchronizes to the position
dictated by the three-bit control input. This operation does not wait for time-out or the acknowledging input. When the
synchronization attempt is unsuccessful (that is, the three-bit input is not available (0,0,0) or out of range) then the
selector switch output is set to position 0 (no output operand selected) and an alarm is established (SELECTOR 1 PWR
ALARM).
The operation of “Synch/Restore” mode is similar to the “Synchronize” mode. The only difference is that after an
unsuccessful synchronization attempt, the switch will attempt to restore the position stored in the relay memory. The
“Synch/Restore” mode is useful for applications where the selector switch is employed to change the setting group in
redundant (two relay) protection schemes.
• SELECTOR 1 EVENTS: If enabled, the following events are logged:
The following figures illustrate the operation of the selector switch. In these diagrams, “T” represents a time-out setting.
STEP-UP
T T
3BIT A0
3BIT A1
3BIT A2
T T
POS 1
POS 2
POS 3
POS 4
POS 5
5 POS 6
POS 7
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
842737A1.CDR
STEP-UP
ACK
3BIT A0
3BIT A1
3BIT A2
3BIT ACK
POS 1
POS 2
POS 3
POS 4
POS 5
POS 6
POS 7
5
BIT 0
BIT 1
BIT 2
STP ALARM
BIT ALARM
ALARM
842736A1.CDR
Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the following
changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUTS menu:
OUTPUT H1 OPERATE: “SELECTOR 1 BIT 0"
OUTPUT H2 OPERATE: “SELECTOR 1 BIT 1"
OUTPUT H3 OPERATE: “SELECTOR 1 BIT 2"
Finally, assign configure user-programmable pushbutton 1 by making the following changes in the SETTINGS Ö PRODUCT
SETUP ÖØ USER-PROGRAMMABLE PUSHBUTTONS Ö USER PUSHBUTTON 1 menu:
SETTINGS
SELECTOR 1 FULL RANGE:
5 SELECTOR 1 FUNCTION:
Enabled = 1
SELECTOR 1 POWER-UP MODE:
RUN
SELECTOR 1 STEP-UP: FLEXLOGIC™ OPERANDS
Off = 0 step up SELECTOR 1 POS 1
2
SELECTOR 1 ACK: 1 SELECTOR 1 POS 2
3
Off = 0 acknowledge SELECTOR 1 POS 3
SELECTOR 1 3BIT A0: 4
SELECTOR 1 POS 4
three-bit control input
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
842012A2.CDR
5.7.5 UNDERFREQUENCY
UNDERFREQ 1 FUNCTION:
Disabled = 0
Enabled = 1
5.7.6 OVERFREQUENCY
OVERFREQ 1 FUNCTION:
Disabled = 0
SETTING
Enabled = 1
OVERFREQ 1 PICKUP : SETTING
SETTING OVERFREQ 1 PICKUP
AND RUN DELAY :
OVERFREQ 1 BLOCK: FLEXLOGIC OPERANDS
OVERFREQ 1 RESET
OVERFREQ 1 PKP
DELAY :
Off = 0 OVERFREQ 1 DPO
tPKP
tRST OVERFREQ 1 OP
SETTING f ≥ PICKUP
OVERFREQ 1 SOURCE:
Frequency 827832A5.CDR
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ FREQUENCY RATE OF CHANGE Ö FREQUENCY RATE OF CHANGE 1(4)
Four (4) independent rate of change of frequency elements are available. The element responds to rate of change of fre-
quency with voltage, current and frequency supervision.
• FREQ RATE 1 TREND: This setting allows configuring the element to respond to increasing or decreasing frequency,
or to frequency change in either direction.
• FREQ RATE 1 PICKUP: This setting specifies an intended df ⁄ dt pickup threshold. For applications monitoring a
decreasing trend, set FREQ RATE 1 TREND to “Decreasing” and specify the pickup threshold accordingly. The operating
condition is: – df ⁄ dt > Pickup .
For applications monitoring an increasing trend, set FREQ RATE 1 TREND to “Increasing” and specify the pickup thresh-
old accordingly. The operating condition is: df ⁄ dt > Pickup .
For applications monitoring rate of change of frequency in any direction set FREQ RATE 1 TREND to “Bi-Directional” and
specify the pickup threshold accordingly. The operating condition is: abs ( df ⁄ dt ) > Pickup
• FREQ RATE 1 OV SUPV PICKUP: This setting defines minimum voltage level required for operation of the element.
The supervising function responds to the positive-sequence voltage. Overvoltage supervision should be used to pre-
vent operation under specific system conditions such as faults.
• FREQ RATE 1 OC SUPV PICKUP: This setting defines minimum current level required for operation of the element.
The supervising function responds to the positive-sequence current. Typical application includes load shedding. Set
the pickup threshold to zero if no overcurrent supervision is required.
• FREQ RATE 1 MIN FREQUENCY: This setting defines minimum frequency level required for operation of the element.
The setting may be used to effectively block the feature based on frequency. For example, if the intent is to monitor an
increasing trend but only if the frequency is already above certain level, this setting should be set to the required fre-
quency level.
• FREQ RATE 1 MAX FREQUENCY: This setting defines maximum frequency level required for operation of the ele-
ment. The setting may be used to effectively block the feature based on frequency. For example, if the intent is to mon-
itor a decreasing trend but only if the frequency is already below certain level (such as for load shedding), this setting
should be set to the required frequency level.
If the signal source assigned to the frequency rate of change element is only set to auxiliary VT, then the minimum
voltage supervision is 3 V.
NOTE
SETTINGS
SETTING
FREQ RATE 1 FUNCTION:
FREQ RATE 1 OV SUPV
Enabled = 1 PICKUP:
AND
5 FREQUENCY:
RUN
Calculate df/dt
832023A2.CDR
a) GENERAL SETTINGS
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ FREQUENCY OOB ACCUMULATION
FREQUENCY OOB FREQ OOB ACCUM Range: SRC 1, SRC 2, SRC 3, SRC 4
ACCUMULATION SOURCE: SRC 1
FREQ OOB ACCUM MIN Range: 0.10 to 1.25 pu in steps of 0.01
MESSAGE
VOLT/AMP: 0.10 pu
FREQ ACCUM BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
FREQ OOB ACCUM Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
FREQ OOB ACCUM Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled
FREQUENCY OOB
MESSAGE See following section.
ACCUMULATOR 1
FREQUENCY OOB
MESSAGE See following section.
ACCUMULATOR 2
↓
FREQUENCY OOB
MESSAGE See following section.
ACCUMULATOR 7 5
The turbine portion of a generator is designed to operate in a narrow frequency range around the nominal, typically ±5%.
As the turbine overspeeds (typically due to load rejection) or coasts down, the turbine will pass through operating frequen-
cies where the turbine blades find stimulus at their natural frequencies. Blade vibrations at these natural frequencies result
is stress on the blades that is accumulated and can result in cracking in some parts of the blade structure, most likely the tie
wires or blade covers. Though typically not catastrophic, the stress can change the vibration behavior of the blade so that
they can have natural resonances closer to the normal operating frequency. This element will provide diagnostic informa-
tion and alarms to the customer based on the accumulated off-nominal frequency operation time of a turbine over several
frequency bands and can then be used to schedule maintenance or other actions as desired by the customer.
The available setting of an upper and lower frequency for each band enables the user to overlap bands of frequencies in
the accumulation function. The accumulation function in any band can be blocked as desired. For example, accumulation
may be blocked during an out-of-service condition as set via an input to the relay.
The following settings are available and apply to all accumulators.
• FREQ OOB ACCUM SOURCE: This setting selects the source for the signal to be measured. The element first checks
for a live phase voltage available from the selected source. If voltage is not available, the element attempts to use a
phase current. If neither voltage nor current is available, the element will not operate, as it will not measure a parame-
ter below the minimum voltage/current setting.
• FREQ OOB ACCUM MIN VOLT/AMP: This setting specifies the minimum per-unit positive-sequence voltage or cur-
rent level required to allow the frequency out-of-band accumulators to operate. This threshold is used to prevent an
incorrect accumulation when operating quantity is too low.
• FREQ ACCUM BLOCK: This setting selects a FlexLogic™ operand to block out-of-band frequency accumulation in all
bands. This is typically required to avoid unnecessary accumulation when relay testing is being performed.
b) ACCUMULATORS 1 TO 7
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ FREQUENCY OOB ACCUMULATION Ö FREQUENCY OOB ACCUMULATOR 1(7)
Seven frequency out-of-band accumulators are available. The following settings are available for each accumulator.
• FREQ ACCUM 1 FUNCTION: This setting enables and disabled a particular frequency band.
• FREQ ACCUM 1 UPPER FREQ: This setting specifies the upper frequency value, in Hz, below which band 1 values
start to accumulate. This upper frequency value must be greater than the lower frequency value.
• FREQ ACCUM 1 LOWER FREQ: This setting specifies the lower frequency value, in Hz, above which band 1 values
start to accumulate. This lower frequency value must be less than the upper frequency value.
• FREQ ACCUM 1 TIME LIMIT: This value specifies the accumulation time, in seconds, at which the overfrequency
accumulation band exceeds the overfrequency accumulation limit and operates.
5 • FREQ ACCUM 1 TIME PRESET: This setting allows the user to either transfer accumulated frequency time of opera-
tion values from a previous hardware platform to a new platform, or, given that some knowledge of the operation of the
turbine is known, to start accumulation at a user-specified value.
SETTING
SETTINGS SETTINGS
FREQ ACCUM BLOCK
FREQ ACCUM 1 UPPER FREQ ACCUM 1 TIME
= Off FREQ LIMIT
FREQ ACCUM 1 LOWER FREQ ACCUM 1 TIME
SETTING SETTING AND
FREQ PRESET
FREQ OOB ACCUM FREQ OOB ACCUM MIN AND RUN RUN
Accumulating
SOURCE VOLT/AMP
fLOWER < f ≤ f UPPER tACCUM > tLIMIT
= Volt/amp mag V/A > MINIMUM
= Frequency
ACTUAL VALUE
FLEXLOGIC OPERANDS
SETTING FREQ OOB BAND 1 FREQ OOB BAND 1 OP
FREQ ACCUM 1 ACCUMULATION
FUNCTION FREQ OOB BAND 1 DPO
= Enabled FREQ OOB BAND 1 PKP
FLEXLOGIC OPERANDS
COMMANDS FREQ OOB BAND 2 OP
RESET FREQ OOB FREQ OOB BAND 3 OP FLEXLOGIC OPERAND
ACCUMULATORS FREQ OOB BAND 4 OP OR FREQ OOB ACCUM OP
PRESET FREQ OOB FREQ OOB BAND 5 OP
ACCUMULATORS FREQ OOB BAND 6 OP
FREQ OOB BAND 7 OP
FLEXLOGIC OPERANDS
FREQ OOB BAND 2 PKP
FLEXLOGIC OPERAND
FREQ OOB BAND 3 PKP
OR FREQ OOB ACCUM PKP
FREQ OOB BAND 4 PKP
FREQ OOB BAND 5 PKP
FREQ OOB BAND 6 PKP
FREQ OOB BAND 7 PKP 830008A1.CDR
5.7.9 SYNCHROCHECK
a) SETTINGS
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ SYNCHROCHECK Ö SYNCHROCHECK 1(2)
MESSAGE
SYNCHK1 DEAD SOURCE Range: None, LV1 and DV2, DV1 and LV2, DV1 or DV2,
DV1 Xor DV2, DV1 and DV2
5
SELECT: LV1 and DV2
SYNCHK1 DEAD V1 Range: 0.00 to 1.25 pu in steps of 0.01
MESSAGE
MAX VOLT: 0.30 pu
SYNCHK1 DEAD V2 Range: 0.00 to 1.25 pu in steps of 0.01
MESSAGE
MAX VOLT: 0.30 pu
SYNCHK1 LIVE V1 Range: 0.00 to 1.25 pu in steps of 0.01
MESSAGE
MIN VOLT: 0.70 pu
SYNCHK1 LIVE V2 Range: 0.00 to 1.25 pu in steps of 0.01
MESSAGE
MIN VOLT: 0.70 pu
SYNCHK1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
SYNCHK1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled
The voltages V1 and V2 will be matched automatically so that the corresponding voltages from the two sources will be
used to measure conditions. A phase to phase voltage will be used if available in both sources; if one or both of the
Sources have only an auxiliary voltage, this voltage will be used. For example, if an auxiliary voltage is programmed to
VAG, the synchrocheck element will automatically select VAG from the other source. If the comparison is required on a
specific voltage, the user can externally connect that specific voltage to auxiliary voltage terminals and then use this
"Auxiliary Voltage" to check the synchronism conditions.
If using a single CT/VT module with both phase voltages and an auxiliary voltage, ensure that only the auxiliary voltage
is programmed in one of the sources to be used for synchrocheck.
Exception: Synchronism cannot be checked between Delta connected phase VTs and a Wye con-
nected auxiliary voltage.
NOTE
2. The relay measures frequency and Volts/Hz from an input on a given source with priorities as established by the con-
figuration of input channels to the source. The relay will use the phase channel of a three-phase set of voltages if pro-
grammed as part of that source. The relay will use the auxiliary voltage channel only if that channel is programmed as
part of the Source and a three-phase set is not.
FLEXLOGIC OPERAND
AND SYNC1 V2 ABOVE MIN
FLEXLOGIC OPERAND
AND SYNC1 V1 ABOVE MIN
FLEXLOGIC OPERAND
AND SYNC1 V1 BELOW MAX
SETTINGS
FLEXLOGIC OPERAND
Function
AND SYNC1 V2 BELOW MAX
Enabled = 1
Disabled = 0
AND
Block
Off = 0
AND
FLEXLOGIC OPERANDS
AND SYNC1 DEAD S OP
AND SYNC1 DEAD S DPO
SETTING
Dead Source Select FLEXLOGIC OPERANDS
AND OR OR SYNC1 CLS OP
None
LV1 and DV2 SYNC1 CLS DPO
DV1 and LV2
AND
DV1 or DV2
DV1 xor DV2
DV1 and DV2
AND
SETTING
Dead V1 Max Volt
V1 ≤ Maximum
XOR
SETTING
Dead V2 Max Volt
OR
V2 ≤ Maximum
5 SETTING
Live V1 Min Volt
AND
V1 ≥ Minimum
SETTING
Live V2 Min Volt
AND
V2 ≥ Minimum
SETTING
CALCULATE Max Volt Diff
SETTING Magnitude V1 Calculate
ΔV ≤ Maximum
V1 Source Angle Φ1 I V1 – V2 I = ΔV
= SRC 1 Frequency F1 FLEXLOGIC OPERANDS
AND SYNC1 SYNC OP
SETTING
SYNC1 SYNC DPO
Max Angle Diff
Calculate
ΔΦ ≤ Maximum
I Φ1 – Φ2 I = ΔΦ
SETTINGS SYNCHROCHECK 1
CALCULATE Max Freq Diff
SETTING Magnitude V2 Freq Hysteresis
V2 Source Angle Φ2 Calculate
ΔF ≤ Maximum
= SRC 2 Frequency F2 I F1 – F2 I = ΔF
ACTUAL VALUE
Synchrocheck 1 ΔV
Synchrocheck 1 ΔΦ
Synchrocheck 1 ΔF
827076AB.CDR
a A
c
C
UR-series device
5
843808A2.CDR
5 MESSAGE
EVENTS: Disabled
There are 48 identical digital elements available, numbered 1 to 48. A digital element can monitor any FlexLogic™ operand
and present a target message and/or enable events recording depending on the output operand state. The digital element
settings include a name which will be referenced in any target message, a blocking input from any selected FlexLogic™
operand, and a timer for pickup and reset delays for the output operand.
• DIGITAL ELEMENT 1 INPUT: Selects a FlexLogic™ operand to be monitored by the digital element.
• DIGITAL ELEMENT 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set to "0".
• DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”.
• DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to
“Disabled”, the operation of the pickup LED is blocked.
SETTING
DIGITAL ELEMENT 01
FUNCTION:
Disabled = 0 SETTINGS
Enabled = 1 DIGITAL ELEMENT 01
SETTING PICKUP DELAY:
DIGITAL ELEMENT 01 DIGITAL ELEMENT 01 FLEXLOGIC OPERANDS
SETTING
NAME: RESET DELAY:
DIGITAL ELEMENT 01 DIG ELEM 01 DPO
AND RUN tPKP
INPUT: DIG ELEM 01 PKP
Off = 0 DIG ELEM 01 OP
INPUT = 1 tRST
SETTING
DIGITAL ELEMENT 01
BLOCK:
827042A1.VSD
Off = 0
As long as the current through the voltage monitor is above a threshold (see technical specifications for form-A), the “Cont
Op 1 VOn” FlexLogic™ operand will be set (for contact input 1 – corresponding operands exist for each contact output). If
the output circuit has a high resistance or the DC current is interrupted, the trickle current will drop below the threshold and
the “Cont Op 1 VOff” FlexLogic™ operand will be set. Consequently, the state of these operands can be used as indicators
of the integrity of the circuits in which form-A contacts are inserted.
EXAMPLE 1: BREAKER TRIP CIRCUIT INTEGRITY MONITORING
In many applications it is desired to monitor the breaker trip circuit integrity so problems can be detected before a trip oper-
ation is required. The circuit is considered to be healthy when the voltage monitor connected across the trip output contact
detects a low level of current, well below the operating current of the breaker trip coil. If the circuit presents a high resis-
tance, the trickle current will fall below the monitor threshold and an alarm would be declared.
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the
breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must
include the breaker position.
UR-series device
with form-A contacts
H1a
I
H1b DC–
V DC+
H1c 52a Trip coil
5
I = current monitor
V = voltage monitor 827073A2.CDR
The PICKUP DELAY setting should be greater than the operating time of the breaker to avoid nuisance
alarms.
NOTE
UR-series device
with form-A contacts
5 H1a
Values for resistor “R”
Power supply Resistance Power
I
24 V DC 1000 Ω 2W
H1b DC– 30 V DC 5000 Ω 2W
48 V DC 10000 Ω 2W
V DC+
110 V DC 25000 Ω 5W
H1c 52a Trip coil
125 V DC 25000 Ω 5W
R
250 V DC 50000 Ω 5W
Bypass
I = current monitor resistor
V = voltage monitor 827074A3.CDR
There are 8 identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions from
Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of an
external contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter.
• COUNTER 1 UNITS: Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted.
The units label will appear in the corresponding actual values status.
• COUNTER 1 PRESET: Sets the count to a required preset value before counting operations begin, as in the case
where a substitute relay is to be installed in place of an in-service relay, or while the counter is running.
• COUNTER 1 COMPARE: Sets the value to which the accumulated count value is compared. Three FlexLogic™ output
operands are provided to indicate if the present value is ‘more than (HI)’, ‘equal to (EQL)’, or ‘less than (LO)’ the set
value.
• COUNTER 1 UP: Selects the FlexLogic™ operand for incrementing the counter. If an enabled UP input is received
when the accumulated value is at the limit of +2,147,483,647 counts, the counter will rollover to –2,147,483,648.
• COUNTER 1 DOWN: Selects the FlexLogic™ operand for decrementing the counter. If an enabled DOWN input is
received when the accumulated value is at the limit of –2,147,483,648 counts, the counter will rollover to
+2,147,483,647.
• COUNTER 1 BLOCK: Selects the FlexLogic™ operand for blocking the counting operation. All counter operands are
blocked.
• CNT1 SET TO PRESET: Selects the FlexLogic™ operand used to set the count to the preset value. The counter will
be set to the preset value in the following situations:
1. When the counter is enabled and the CNT1 SET TO PRESET operand has the value 1 (when the counter is enabled
and CNT1 SET TO PRESET operand is 0, the counter will be set to 0).
2. When the counter is running and the CNT1 SET TO PRESET operand changes the state from 0 to 1 (CNT1 SET TO
PRESET changing from 1 to 0 while the counter is running has no effect on the count).
3. When a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the value
1 (when a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the
value 0, the counter will be set to 0).
• COUNTER 1 RESET: Selects the FlexLogic™ operand for setting the count to either “0” or the preset value depending
on the state of the CNT1 SET TO PRESET operand.
• COUNTER 1 FREEZE/RESET: Selects the FlexLogic™ operand for capturing (freezing) the accumulated count value
into a separate register with the date and time of the operation, and resetting the count to “0”.
• COUNTER 1 FREEZE/COUNT: Selects the FlexLogic™ operand for capturing (freezing) the accumulated count value
into a separate register with the date and time of the operation, and continuing counting. The present accumulated
value and captured frozen value with the associated date/time stamp are available as actual values. If control power is
interrupted, the accumulated and frozen values are saved into non-volatile memory during the power down operation.
SETTING
COUNTER 1 FUNCTION:
Disabled = 0
SETTINGS
Enabled = 1
COUNTER 1 NAME:
5 SETTING
COUNTER 1 UP:
AND COUNTER 1 UNITS:
COUNTER 1 PRESET:
RUN
Off = 0 SETTING
FLEXLOGIC
COUNTER 1 COMPARE: OPERANDS
SETTING
CALCULATE Count more than Comp. COUNTER 1 HI
COUNTER 1 DOWN: VALUE Count equal to Comp. COUNTER 1 EQL
Off = 0 Count less than Comp. COUNTER 1 LO
SETTING
COUNTER 1 BLOCK:
Off = 0 SET TO PRESET VALUE
a) MAIN MENU
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTS
b) VT FUSE FAILURE
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTS ÖØ VT FUSE FAILURE 1(4)
AND
Reset-dominant
OR SET
FAULT
Latch
AND
RESET
SETTING
Function
Disabled = 0
Enabled = 1
AND
COMPARATORS
SOURCE 1 Run
V_2 V_2 > 0.1 pu
Run AND
TIMER
V_1 < 0.80 pu
2 cycles
FLEXLOGIC OPERANDS
Run AND
I_1 < 0.05 pu Latch SRC1 VT FUSE FAIL OP
20 cycles
SRC1 VT FUSE FAIL DPO
FLEXLOGIC OPERANDS
SRC1 50DD OP
OPEN POLE OP
The OPEN POLE OP operand is applicable
AND
to the D60, L60, and L90 only.
RESET
OR
Reset-dominant
AND
FLEXLOGIC OPERAND
The thermal overload protection element corresponds to the IEC 255-8 standard and is used to detect thermal overload
conditions in protected power system elements. Choosing an appropriate time constant element can be used to protect dif-
ferent elements of the power system. The cold curve characteristic is applied when the previous averaged load current over
the last 5 cycles is less than 10% of the base current. If this current is greater or equal than 10% than the base current, then
the hot curve characteristic is applied.
The IEC255-8 cold curve is defined as follows:
⎛ I
2 ⎞
t op = τ op × ln ⎜ -------------------------
-⎟ (EQ 5.48)
⎝ I – ( kI B ) ⎠
2 2
The reset time of the thermal overload protection element is also time delayed using following formula:
2
⎛ ( kI B ) ⎞
t rst = τ rst × ln ⎜ ----------------------------
-⎟ + T min (EQ 5.50)
⎝ I – ( kI B ) ⎠
2 2
100
Tmin = 10
10
τrst = 30
τop = 30
5
t (min)
0.1
0.01
0.1 1 10 100
I / Ipkp
827724A1.CDR
When current is less than the dropout level, In > 0.97 × k × IB, the element starts decreasing the thermal energy:
Δt -
E n = E n – 1 – -------------- (EQ 5.52)
t rst ( In )
The logic for the thermal overload protection element is shown below.
SETTINGS
Function
Enabled = 1
Block AND
Off = 0
SETTINGS
Reset Time Constant
Minimum Reset Time
RUN
E < 0.1
SETTING
Reset
Off = 0 Reset E to 0 827013A1.CDR
CONTACT INPUTS
CONTACT INPUT
THRESHOLDS
5 THRESHOLD: 33 Vdc
The contact inputs menu contains configuration settings for each contact input as well as voltage thresholds for each group
of four contact inputs. Upon startup, the relay processor determines (from an assessment of the installed modules) which
contact inputs are available and then display settings for only those inputs.
An alphanumeric ID may be assigned to a contact input for diagnostic, setting, and event recording purposes. The CON-
TACT IP X On” (Logic 1) FlexLogic™ operand corresponds to contact input “X” being closed, while CONTACT IP X Off corre-
sponds to contact input “X” being open. The CONTACT INPUT DEBNCE TIME defines the time required for the contact to
overcome ‘contact bouncing’ conditions. As this time differs for different contact types and manufacturers, set it as a maxi-
mum contact debounce time (per manufacturer specifications) plus some margin to ensure proper operation. If CONTACT
INPUT EVENTS is set to “Enabled”, every change in the contact input state will trigger an event.
A raw status is scanned for all Contact Inputs synchronously at the constant rate of 0.5 ms as shown in the figure below.
The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user-
settable debounce time in order for the G60 to validate the new contact state. In the figure below, the debounce time is set
at 2.5 ms; thus the 6th sample in a row validates the change of state (mark no. 1 in the diagram). Once validated (de-
bounced), the contact input asserts a corresponding FlexLogic™ operand and logs an event as per user setting.
A time stamp of the first sample in the sequence that validates the new state is used when logging the change of the con-
tact input into the Event Recorder (mark no. 2 in the diagram).
Protection and control elements, as well as FlexLogic™ equations and timers, are executed eight times in a power system
cycle. The protection pass duration is controlled by the frequency tracking mechanism. The FlexLogic™ operand reflecting
the debounced state of the contact is updated at the protection pass following the validation (marks no. 3 and 4 on the fig-
ure below). The update is performed at the beginning of the protection pass so all protection and control functions, as well
as FlexLogic™ equations, are fed with the updated states of the contact inputs.
The FlexLogic™ operand response time to the contact input change is equal to the debounce time setting plus up to one
protection pass (variable and depending on system frequency if frequency tracking enabled). If the change of state occurs
just after a protection pass, the recognition is delayed until the subsequent protection pass; that is, by the entire duration of
the protection pass. If the change occurs just prior to a protection pass, the state is recognized immediately. Statistically a
delay of half the protection pass is expected. Owing to the 0.5 ms scan rate, the time resolution for the input contact is
below 1msec.
For example, 8 protection passes per cycle on a 60 Hz system correspond to a protection pass every 2.1 ms. With a con-
tact debounce time setting of 3.0 ms, the FlexLogic™ operand-assert time limits are: 3.0 + 0.0 = 3.0 ms and 3.0 + 2.1 = 5.1
ms. These time limits depend on how soon the protection pass runs after the debouncing time.
Regardless of the contact debounce time setting, the contact input event is time-stamped with a 1 μs accuracy using the
time of the first scan corresponding to the new state (mark no. 2 below). Therefore, the time stamp reflects a change in the
DC voltage across the contact input terminals that was not accidental as it was subsequently validated using the debounce
timer. Keep in mind that the associated FlexLogic™ operand is asserted/de-asserted later, after validating the change.
The debounce algorithm is symmetrical: the same procedure and debounce time are used to filter the LOW-HIGH (marks
no.1, 2, 3, and 4 in the figure below) and HIGH-LOW (marks no. 5, 6, 7, and 8 below) transitions.
VOLTAGE
INPUT
USER-PROGRAMMABLE THRESHOLD
6
2 1 3 5
Time stamp of the first
TM
Time stamp of the first At this time, the The FlexLogic scan corresponding to the
scan corresponding to
the new validated state is
logged in the SOE record
new (HIGH)
contact state is
validated
operand is going to
be asserted at this
protection pass
new validated state is
logged in the SOE record
At this time, the new
(LOW) contact state is
validated
5
7
RAW CONTACT
The FlexLogicTM
operand is going to be
STATE
de-asserted at this
protection pass
DEBOUNCE TIME
(user setting)
4
The FlexLogicTM operand
DEBOUNCE TIME
The FlexLogicTM operand changes reflecting the
SCAN TIME (user setting)
changes reflecting the validated contact state
FLEXLOGICTM
PROTECTION PASS
(8 times a cycle controlled by the
frequency tracking mechanism)
842709A1.cdr
Figure 5–142: INPUT CONTACT DEBOUNCING MECHANISM AND TIME-STAMPING SAMPLE TIMING
Contact inputs are isolated in groups of four to allow connection of wet contacts from different voltage sources for each
group. The CONTACT INPUT THRESHOLDS determine the minimum voltage required to detect a closed contact input. This
value should be selected according to the following criteria: 17 for 24 V sources, 33 for 48 V sources, 84 for 110 to 125 V
sources and 166 for 250 V sources.
For example, to use contact input H5a as a status input from the breaker 52b contact to seal-in the trip relay and record it in
the Event Records menu, make the following settings changes:
CONTACT INPUT H5A ID: "Breaker Closed (52b)"
CONTACT INPUT H5A EVENTS: "Enabled"
Note that the 52b contact is closed when the breaker is open and open when the breaker is closed.
There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the COM-
MANDS menu) and communications protocols. All virtual input operands are defaulted to “Off” (logic 0) unless the appropri-
ate input signal is received.
If the VIRTUAL INPUT x FUNCTION is to “Disabled”, the input will be forced to off (logic 0) regardless of any attempt to alter the
input. If set to “Enabled”, the input operates as shown on the logic diagram and generates output FlexLogic™ operands in
response to received input signals and the applied settings.
There are two types of operation: self-reset and latched. If VIRTUAL INPUT x TYPE is “Self-Reset”, when the input signal tran-
sits from off to on, the output operand will be set to on for only one evaluation of the FlexLogic™ equations and then return
to off. If set to “Latched”, the virtual input sets the state of the output operand to the same state as the most recent received
input.
5 The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic™
equations. If the operand is to be used anywhere other than internally in a FlexLogic™ equation, it will
NOTE
likely have to be lengthened in time. A FlexLogic™ timer with a delayed reset can perform this function.
SETTING
VIRTUAL INPUT 1
FUNCTION:
Disabled=0
Enabled=1 S
AND
Latch
“Virtual Input 1 to ON = 1”
SETTING
“Virtual Input 1 to OFF = 0” R VIRTUAL INPUT 1 ID:
AND
SETTING (Flexlogic Operand)
OR
Virt Ip 1
VIRTUAL INPUT 1
TYPE:
Latched AND
Self - Reset 827080A2.CDR
a) DIGITAL OUTPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUTS Ö CONTACT OUTPUT H1
Upon startup of the relay, the main processor will determine from an assessment of the modules installed in the chassis
which contact outputs are available and present the settings for only these outputs.
An ID may be assigned to each contact output. The signal that can OPERATE a contact output may be any FlexLogic™
operand (virtual output, element state, contact input, or virtual input). An additional FlexLogic™ operand may be used to
SEAL-IN the relay. Any change of state of a contact output can be logged as an Event if programmed to do so.
For example, the trip circuit current is monitored by providing a current threshold detector in series with some Form-A con-
tacts (see the trip circuit example in the Digital elements section). The monitor will set a flag (see the specifications for
Form-A). The name of the FlexLogic™ operand set by the monitor, consists of the output relay designation, followed by the
name of the flag; for example, CONT OP 1 ION.
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact used to interrupt current 5
flow after the breaker has tripped, to prevent damage to the less robust initiating contact. This can be done by monitoring
an auxiliary contact on the breaker which opens when the breaker has tripped, but this scheme is subject to incorrect oper-
ation caused by differences in timing between breaker auxiliary contact change-of-state and interruption of current in the
trip circuit. The most dependable protection of the initiating contact is provided by directly measuring current in the tripping
circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in.
This can be realized in the G60 using the CONT OP 1 ION FlexLogic™ operand to seal-in the contact output as follows:
CONTACT OUTPUT H1 ID: “Cont Op 1"
OUTPUT H1 OPERATE: any suitable FlexLogic™ operand
OUTPUT H1 SEAL-IN: “Cont Op 1 IOn”
CONTACT OUTPUT H1 EVENTS: “Enabled”
b) LATCHING OUTPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUTS Ö CONTACT OUTPUT H1a
The G60 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such
they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop-
ulates the setting menu accordingly. On power up, the relay reads positions of the latching contacts from the hardware
before executing any other functions of the relay (such as protection and control features or FlexLogic™).
The latching output modules, either as a part of the relay or as individual modules, are shipped from the factory with all
latching contacts opened. It is highly recommended to double-check the programming and positions of the latching con-
tacts when replacing a module.
Since the relay asserts the output contact and reads back its position, it is possible to incorporate self-monitoring capabili-
ties for the latching outputs. If any latching outputs exhibits a discrepancy, the LATCHING OUTPUT ERROR self-test error is
declared. The error is signaled by the LATCHING OUT ERROR FlexLogic™ operand, event, and target message.
• OUTPUT H1a OPERATE: This setting specifies a FlexLogic™ operand to operate the ‘close coil’ of the contact. The
relay will seal-in this input to safely close the contact. Once the contact is closed and the RESET input is logic 0 (off),
any activity of the OPERATE input, such as subsequent chattering, will not have any effect. With both the OPERATE and
RESET inputs active (logic 1), the response of the latching contact is specified by the OUTPUT H1A TYPE setting.
• OUTPUT H1a RESET: This setting specifies a FlexLogic™ operand to operate the ‘trip coil’ of the contact. The relay
will seal-in this input to safely open the contact. Once the contact is opened and the OPERATE input is logic 0 (off), any
activity of the RESET input, such as subsequent chattering, will not have any effect. With both the OPERATE and RESET
inputs active (logic 1), the response of the latching contact is specified by the OUTPUT H1A TYPE setting.
• OUTPUT H1a TYPE: This setting specifies the contact response under conflicting control inputs; that is, when both the
OPERATE and RESET signals are applied. With both control inputs applied simultaneously, the contact will close if set to
“Operate-dominant” and will open if set to “Reset-dominant”.
Application Example 1:
5 A latching output contact H1a is to be controlled from two user-programmable pushbuttons (buttons number 1 and 2). The
following settings should be applied.
Program the Latching Outputs by making the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUT-
PUTS Ö CONTACT OUTPUT H1a menu (assuming an H4L module):
Program the pushbuttons by making the following changes in the PRODUCT SETUP ÖØ USER-PROGRAMMABLE PUSHBUT-
TONS ÖØ USER PUSHBUTTON 1 and USER PUSHBUTTON 2 menus:
Application Example 2:
A relay, having two latching contacts H1a and H1c, is to be programmed. The H1a contact is to be a Type-a contact, while
the H1c contact is to be a Type-b contact (Type-a means closed after exercising the operate input; Type-b means closed
after exercising the reset input). The relay is to be controlled from virtual outputs: VO1 to operate and VO2 to reset.
Program the Latching Outputs by making the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUT-
PUTS Ö CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):
Since the two physical contacts in this example are mechanically separated and have individual control inputs, they will not
operate at exactly the same time. A discrepancy in the range of a fraction of a maximum operating time may occur. There-
fore, a pair of contacts programmed to be a multi-contact relay will not guarantee any specific sequence of operation (such
as make before break). If required, the sequence of operation must be programmed explicitly by delaying some of the con-
trol inputs as shown in the next application example.
Application Example 3:
A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement
this functionality as described below:
Both timers (Timer 1 and Timer 2) should be set to 20 ms pickup and 0 ms dropout.
Program the Latching Outputs by making the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUT-
PUTS Ö CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1” OUTPUT H1c OPERATE: “VO2”
OUTPUT H1a RESET: “VO4” OUTPUT H1c RESET: “VO3”
Application Example 4:
A latching contact H1a is to be controlled from a single virtual output VO1. The contact should stay closed as long as VO1
is high, and should stay opened when VO1 is low. Program the relay as follows.
Write the following FlexLogic™ equation (EnerVista UR Setup example shown):
5
Program the Latching Outputs by making the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUT-
PUTS Ö CONTACT OUTPUT H1a menu (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1”
OUTPUT H1a RESET: “VO2”
There are 96 virtual outputs that may be assigned via FlexLogic™. If not assigned, the output will be forced to ‘OFF’ (Logic
0). An ID may be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the
FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings
would be programmed as follows:
The sharing of digital point state information between GSSE/GOOSE equipped relays is essentially an extension to Flex-
Logic™, allowing distributed FlexLogic™ by making operands available to/from devices on a common communications net-
work. In addition to digital point states, GSSE/GOOSE messages identify the originator of the message and provide other
information required by the communication specification. All devices listen to network messages and capture data only from
messages that have originated in selected devices.
IEC 61850 GSSE messages are compatible with UCA GOOSE messages and contain a fixed set of digital points. IEC
61850 GOOSE messages can, in general, contain any configurable data items. When used by the remote input/output fea-
ture, IEC 61850 GOOSE messages contain the same data as GSSE messages.
Both GSSE and GOOSE messages are designed to be short, reliable, and high priority. GOOSE messages have additional
advantages over GSSE messages due to their support of VLAN (virtual LAN) and Ethernet priority tagging functionality.
The GSSE message structure contains space for 128 bit pairs representing digital point state information. The IEC 61850
specification provides 32 “DNA” bit pairs that represent the state of two pre-defined events and 30 user-defined events. All
5 remaining bit pairs are “UserSt” bit pairs, which are status bits representing user-definable events. The G60 implementation
provides 32 of the 96 available UserSt bit pairs.
The IEC 61850 specification includes features that are used to cope with the loss of communication between transmitting
and receiving devices. Each transmitting device will send a GSSE/GOOSE message upon a successful power-up, when
the state of any included point changes, or after a specified interval (the default update time) if a change-of-state has not
occurred. The transmitting device also sends a ‘hold time’ which is set greater than three times the programmed default
time required by the receiving device.
Receiving devices are constantly monitoring the communications network for messages they require, as recognized by the
identification of the originating device carried in the message. Messages received from remote devices include the mes-
sage time allowed to live. The receiving relay sets a timer assigned to the originating device to this time interval, and if it
has not received another message from this device at time-out, the remote device is declared to be non-communicating, so
it will use the programmed default state for all points from that specific remote device. If a message is received from a
remote device before the time allowed to live expires, all points for that device are updated to the states contained in the
message and the hold timer is restarted. The status of a remote device, where “Offline” indicates non-communicating, can
be displayed.
The remote input/output facility provides for 32 remote inputs and 64 remote outputs.
Likewise, the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE mes-
sage is programmed in the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE
CONFIGURATION Ö TRANSMISSION ÖØ GSSE ÖØ GSSE ID setting.
In G60 releases previous to 5.0x, these name strings were represented by the RELAY NAME setting.
Remote devices are available for setting purposes. A receiving relay must be programmed to capture messages from only
those originating remote devices of interest. This setting is used to select specific remote devices by entering (bottom row)
the exact identification (ID) assigned to those devices.
The REMOTE DEVICE 1 ETYPE APPID setting is only used with GOOSE messages; they are not applicable to GSSE mes-
sages. This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre-
sponding settings on the sending device.
The REMOTE DEVICE 1 DATASET setting provides for the choice of the G60 fixed (DNA/UserSt) dataset (that is, containing
DNA and UserSt bit pairs), or one of the configurable datasets.
Note that the dataset for the received data items must be made up of existing items in an existing logical node. For this rea-
son, logical node GGIO3 is instantiated to hold the incoming data items. GGIO3 is not necessary to make use of the
received data. The remote input data item mapping takes care of the mapping of the inputs to remote input FlexLogic™
operands. However, GGIO3 data can be read by IEC 61850 clients.
Remote Inputs that create FlexLogic™ operands at the receiving relay are extracted from GSSE/GOOSE messages origi-
nating in remote devices. Each remote input can be selected from a list consisting of: DNA-1 through DNA-32, UserSt-1
through UserSt-32, and Dataset Item 1 through Dataset Item 32. The function of DNA inputs is defined in the IEC 61850
specification and is presented in the IEC 61850 DNA Assignments table in the Remote outputs section. The function of
UserSt inputs is defined by the user selection of the FlexLogic™ operand whose state is represented in the GSSE/GOOSE
message. A user must program a DNA point from the appropriate FlexLogic™ operand.
Remote input 1 must be programmed to replicate the logic state of a specific signal from a specific remote device for local
use. This programming is performed via the three settings shown above.
The REMOTE INPUT 1 ID setting allows the user to assign descriptive text to the remote input. The REMOTE IN 1 DEVICE setting
selects the remote device which originates the required signal, as previously assigned to the remote device via the setting
REMOTE DEVICE (16) ID (see the Remote devices section). The REMOTE IN 1 ITEM setting selects the specific bits of the
GSSE/GOOSE message required.
The REMOTE IN 1 DEFAULT STATE setting selects the logic state for this point if the local relay has just completed startup or
the remote device sending the point is declared to be non-communicating. The following choices are available:
• Setting REMOTE IN 1 DEFAULT STATE to “On” value defaults the input to logic 1.
• Setting REMOTE IN 1 DEFAULT STATE to “Off” value defaults the input to logic 0.
• Setting REMOTE IN 1 DEFAULT STATE to “Latest/On” freezes the input in case of lost communications. If the latest state is
not known, such as after relay power-up but before the first communication exchange, the input will default to logic 1.
When communication resumes, the input becomes fully operational.
• Setting REMOTE IN 1 DEFAULT STATE to “Latest/Off” freezes the input in case of lost communications. If the latest state is
not known, such as after relay power-up but before the first communication exchange, the input will default to logic 0.
When communication resumes, the input becomes fully operational.
For additional information on GSSE/GOOOSE messaging, refer to the Remote devices section in this chap-
ter.
NOTE
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ REMOTE DPS INPUTS Ö REMOTE DPS INPUT 1(5)
5 MESSAGE
REM DPS IN 1
EVENTS: Disabled
Range: Enabled, Disabled
Remote double-point status inputs are extracted from GOOSE messages originating in the remote device. Each remote
double point status input must be programmed to replicate the logic state of a specific signal from a specific remote device
for local use. This functionality is accomplished with the five remote double-point status input settings.
• REM DPS IN 1 ID: This setting assigns descriptive text to the remote double-point status input.
• REM DPS IN 1 DEV: This setting selects a remote device ID to indicate the origin of a GOOSE message. The range is
selected from the remote device IDs specified in the Remote devices section.
• REM DPS IN 1 ITEM: This setting specifies the required bits of the GOOSE message.
The configurable GOOSE dataset items must be changed to accept a double-point status item from a GOOSE dataset
(changes are made in the SETTINGS ÖØ COMMUNICATION ÖØ IEC 61850 PROTOCOL ÖØ GSSE/GOOSE CONFIGURATION ÖØ
RECEPTION ÖØ CONFIGURABLE GOOSE Ö CONFIGIGURABLE GOOSE 1(16) Ö CONFIG GSE 1 DATASET ITEMS menus). Dataset
items configured to receive any of “GGIO3.ST.IndPos1.stV” to “GGIO3.ST.IndPos5.stV” will accept double-point status
information that will be decoded by the remote double-point status inputs configured to this dataset item.
The remote double point status is recovered from the received IEC 61850 dataset and is available as through the RemDPS
Ip 1 BAD, RemDPS Ip 1 INTERM, RemDPS Ip 1 OFF, and RemDPS Ip 1 ON FlexLogic™ operands. These operands can then be
used in breaker or disconnect control schemes.
Remote outputs (1 to 32) are FlexLogic™ operands inserted into GSSE/GOOSE messages that are transmitted to remote
devices on a LAN. Each digital point in the message must be programmed to carry the state of a specific FlexLogic™ oper-
and. The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted.
Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote devices. Each digital point in the
message must be programmed to carry the state of a specific FlexLogic™ operand. The setting above is used to select the
operand which represents a specific UserSt function (as selected by the user) to be transmitted.
The following setting represents the time between sending GSSE/GOOSE messages when there has been no change of
state of any selected digital point. This setting is located in the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTO-
COL ÖØ GSSE/GOOSE CONFIGURATION settings menu.
For more information on GSSE/GOOSE messaging, refer to Remote Inputs/Outputs Overview in the
Remote Devices section.
NOTE
5.8.9 RESETTING
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition
has cleared until a RESET command is received to return these latches (not including FlexLogic™ latches) to the reset
state. The RESET command can be sent from the faceplate Reset button, a remote device via a communications channel,
or any programmed operand.
When the RESET command is received by the relay, two FlexLogic™ operands are created. These operands, which are
stored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each cre-
ate the RESET OP FlexLogic™ operand. Each individual source of a RESET command also creates its individual operand
RESET OP (PUSHBUTTON), RESET OP (COMMS) or RESET OP (OPERAND) to identify the source of the command. The setting
shown above selects the operand that will create the RESET OP (OPERAND) operand.
a) DIRECT INPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ DIRECT INPUTS Ö DIRECT INPUT 1(32)
These settings specify how the direct input information is processed. The DIRECT INPUT 1 NAME setting allows the user to
assign a descriptive name to the direct input. The DIRECT INPUT 1 DEVICE ID represents the source of direct input 1. The
specified direct input is driven by the device identified here.
The DIRECT INPUT 1 BIT NUMBER is the bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
identified as DIRECT INPUT 1 BIT NUMBER. This corresponds to the direct output number of the sending device.
The DIRECT INPUT 1 DEFAULT STATE represents the state of the direct input when the associated direct device is offline. The
following choices are available:
5 • Setting DIRECT INPUT 1 DEFAULT STATE to “On” value defaults the input to Logic 1.
• Setting DIRECT INPUT 1 DEFAULT STATE to “Off” value defaults the input to Logic 0.
• Setting DIRECT INPUT 1 DEFAULT STATE to “Latest/On” freezes the input in case of lost communications. If the latest
state is not known, such as after relay power-up but before the first communication exchange, the input will default to
Logic 1. When communication resumes, the input becomes fully operational.
• Setting DIRECT INPUT 1 DEFAULT STATE to “Latest/Off” freezes the input in case of lost communications. If the latest
state is not known, such as after relay power-up but before the first communication exchange, the input will default to
Logic 0. When communication resumes, the input becomes fully operational.
b) DIRECT OUTPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ DIRECT OUTPUTS Ö DIRECT OUTPUT 1(32)
The DIRECT OUT 1 NAME setting allows the user to assign a descriptive name to the direct output. The DIR OUT 1 OPERAND is
the FlexLogic™ operand that determines the state of this direct output.
c) APPLICATION EXAMPLES
The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued
below to illustrate usage of the direct inputs and outputs.
TX1
UR IED 1
RX1
TX1
UR IED 2
RX1
Figure 5–144: INPUT AND OUTPUT EXTENSION VIA DIRECT INPUTS AND OUTPUTS
Assume contact input 1 from UR IED 2 is to be used by UR IED 1. The following settings should be applied (Direct Input 5
and bit number 12 are used, as an example):
UR IED 1: DIRECT INPUT 5 DEVICE ID = “2” UR IED 2: DIRECT OUT 12 OPERAND = “Cont Ip 1 On”
DIRECT INPUT 5 BIT NUMBER = “12”
The Cont Ip 1 On operand of UR IED 2 is now available in UR IED 1 as DIRECT INPUT 5 ON.
EXAMPLE 2: INTERLOCKING BUSBAR PROTECTION
A simple interlocking busbar protection scheme can be accomplished by sending a blocking signal from downstream
devices, say 2, 3 and 4, to the upstream device that monitors a single incomer of the busbar, as shown in the figure below.
5
UR IED 1 BLOCK
842712A1.CDR
UR IED 1 UR IED 2
UR IED 3
842713A1.CDR
RX1
UR IED 3
TX1
842714A1.CDR
UR IED 1 UR IED 2
DIRECT OUT 2 = HYB POTT TX1 DIRECT INPUT 5
DIRECT INPUT 5 DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 6 DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 6
842717A1.CDR
Figure 5–148: SIGNAL FLOW FOR DIRECT INPUT AND OUTPUT – EXAMPLE 3
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 should be ANDed in FlexLogic™ and the resulting operand configured as the permission to trip (HYB POTT
RX1 setting).
a) OVERVIEW
5
The relay provides sixteen teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and sixteen
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only, num-
bered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by assigning
FlexLogic™ operands to be sent via the selected communications channel. This allows the user to create distributed pro-
tection and control schemes via dedicated communications channels. Some examples are directional comparison pilot
schemes and direct transfer tripping. It should be noted that failures of communications channels will affect teleprotection
functionality. The teleprotection function must be enabled to utilize the inputs.
b) TELEPROTECTION INPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ TELEPROTECTION Ö TELEPROT INPUTS
TELEPROT INPUTS TELEPROT INPUT 1-1 Range: Off, On, Latest/Off, Latest/On
DEFAULT: Off
TELEPROT INPUT 1-2 Range: Off, On, Latest/Off, Latest/On
MESSAGE
DEFAULT: Off
↓
Setting the TELEPROT INPUT ~~ DEFAULT setting to “On” defaults the input to logic 1 when the channel fails. A value of “Off”
defaults the input to logic 0 when the channel fails.
The “Latest/On” and “Latest/Off” values freeze the input in case of lost communications. If the latest state is not known,
such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for “Latest/On”
and logic 0 for “Latest/Off”.
c) TELEPROTECTION OUTPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ TELEPROTECTION ÖØ TELEPROT OUTPUTS
5 MESSAGE
TELEPROT OUTPUT 2-16:
Off
Range: FlexLogic™ operand
As the following figure demonstrates, processing of the teleprotection inputs/outputs is dependent on the number of com-
munication channels and terminals. On two-terminal two-channel systems, they are processed continuously on each chan-
nel and mapped separately per channel. Therefore, to achieve redundancy, the user must assign the same operand on
both channels (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On
three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel
failure between any pair of relays.
UR-1 UR-2
ACTUAL VALUES SETTING
CHANNEL 1 STATUS: TELEPROT INPUT 1-1
DEFAULT:
SETTING (same for 1-2...1-16)
TELEPROT OUTPUT 1-1:
(same for 1-2...1-16) On FLEXLOGIC OPERAND
Fail
Off (Flexlogic Operand) Off TELEPRO INPUT 1-1 On
OK OR
(same for 1-2...1-16)
UR-2 or UR-3
ACTUAL VALUES SETTING
CHANNEL 2 STATUS: TELEPROT INPUT 2-1
DEFAULT:
SETTING (same for 2-2...2-16)
TELEPROT OUTPUT 2-1:
(same for 1-2...1-16) On FLEXLOGIC OPERAND
Fail
Off TELEPRO INPUT 2-1 On
Off (Flexlogic Operand) OK OR
(same for 2-2...2-16)
842750A2.CDR
The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-series
devices. The following settings are available for each GOOSE analog input.
• ANALOG 1 DEFAULT: This setting specifies the value of the GOOSE analog input when the sending device is offline
and the ANALOG 1 DEFAULT MODE is set to “Default Value”.This setting is stored as an IEEE 754 / IEC 60559 floating
point number. Because of the large range of this setting, not all possible values can be stored. Some values may be
rounded to the closest possible floating point number.
• ANALOG 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE analog input remains at the last received value. When the sending device is offline and this setting value is
“Default Value”, then the value of the GOOSE analog input is defined by the ANALOG 1 DEFAULT setting.
• GOOSE ANALOG 1 UNITS: This setting specifies a four-character alphanumeric string that can is used in the actual
values display of the corresponding GOOSE analog input value.
• GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-
log™ values in other G60 features, such as FlexElements™. The base factor is applied to the GOOSE analog input
FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
5 STATOR RESTRAINING
CURRENT
IBASE = maximum primary RMS value of the +IN and –IN inputs
(CT primary for source currents, and bus reference primary current for bus differential currents)
(Stator Diff Iad, Ibd, and Icd)
SYNCHROCHECK VBASE = maximum primary RMS value of all the sources related to the +IN and –IN inputs
(Max Delta Volts)
VOLTS PER HERTZ BASE = 1.00 pu
The GOOSE analog input FlexAnalog™ values are available for use in other G60 functions that use FlexAnalog™ values.
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ IEC 61850 GOOSE UINTEGERS ÖØ GOOSE UINTEGER INPUT 1(16)
The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger™ values between any two UR-
series devices. The following settings are available for each GOOSE uinteger input.
• UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device is
offline and the UINTEGER 1 DEFAULT MODE is set to “Default Value”.This setting is stored as a 32-bit unsigned integer
number.
• UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is
“Default Value”, then the value of the GOOSE uinteger input is defined by the UINTEGER 1 DEFAULT setting.
The GOOSE integer input FlexInteger™ values are available for use in other G60 functions that use FlexInteger™ values.
Hardware and software is provided to receive signals from external transducers and convert these signals into a digital for-
mat for use as required. The relay will accept inputs in the range of –1 to +20 mA DC, suitable for use with most common
transducer output ranges; all inputs are assumed to be linear over the complete range. Specific hardware details are con-
tained in chapter 3.
Before the dcmA input signal can be used, the value of the signal measured by the relay must be converted to the range
and quantity of the external transducer primary input parameter, such as DC voltage or temperature. The relay simplifies
this process by internally scaling the output from the external transducer and displaying the actual primary parameter.
5
dcmA input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels
with the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay will automatically generate configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclu-
sive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel of
a type 5F transducer module installed in slot H.
The function of the channel may be either “Enabled” or “Disabled”. If “Disabled”, no actual values are created for the chan-
nel. An alphanumeric “ID” is assigned to each channel; this ID will be included in the channel actual value, along with the
programmed units associated with the parameter measured by the transducer, such as volts, °C, megawatts, etc. This ID is
also used to reference the channel as the input parameter to features designed to measure this type of parameter. The
DCMA INPUT H1 RANGE setting specifies the mA DC range of the transducer connected to the input channel.
The DCMA INPUT H1 MIN VALUE and DCMA INPUT H1 MAX VALUE settings are used to program the span of the transducer in
primary units. For example, a temperature transducer might have a span from 0 to 250°C; in this case the DCMA INPUT H1
MIN VALUE value is “0” and the DCMA INPUT H1 MAX VALUE value is “250”. Another example would be a watts transducer with
a span from –20 to +180 MW; in this case the DCMA INPUT H1 MIN VALUE value would be “–20” and the DCMA INPUT H1 MAX
VALUE value “180”. Intermediate values between the min and max values are scaled linearly.
5 MESSAGE
RST DELAY: 0.00 s
RTD INPUT H1 TRIP Range: None, Group, RTD Inp H1, RTD Inp H2,...,
MESSAGE RTD Inp W8
VOTING: None
RTD INPUT H1 OPEN: Range: None, Alarm, Block
MESSAGE
None
RTD INPUT H1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
RTD INPUT H1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
RTD INPUT H1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled
The RTD inputs convert values of input resistance into temperature for further operations. These channels are intended to
be connected to any of the RTD types in common use. Specific hardware details are contained in chapter 3.
RTD input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels with
the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay will automatically generate configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclu-
sive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel of
a type 5C transducer module installed in the first available slot.
• RTD INPUT H1 FUNCTION: The function of the channel may be either “Enabled” or “Disabled”. If set to “Disabled”,
there will not be an actual value created for the channel.
• RTD INPUT H1 ID: An alphanumeric ID is assigned to the channel. This ID will be included in the channel actual val-
ues. It is also used to reference the channel as the input parameter to features designed to measure this type of
parameter.
• RTD INPUT H1 TYPE: This setting specifies the RTD type. Four different RTD types are available: 100 Ω Nickel, 10 Ω
Copper, 100 Ω Platinum, and 120 Ω Nickel. Refer the table below for reference temperature values for each type.
• RTD INPUT H1 APPLICATION: This setting allows each individual RTD to be assigned to a group application. This is
useful for applications that require group measurement for voting. A value of “None” specifies that the RTD will operate
individually and not part of any RTD group. All RTDs programmed to “Stator” are used for RTD biasing of the G60 ther-
mal model. Common groups are provided for rotating machines applications such as ambient, bearing, group 1, or
group 2. If the RTD INPUT H1 TRIP VOTING setting value is “Group”, then it is allowed to issue a trip if N – 1 RTDs from the
same group also pick up, where N is the number of enabled RTDs from the group.
• RTD INPUT H1 ALARM TEMPERATURE: This setting specifies the temperature pickup level for the alarm stage.
• RTD INPUT H1 ALARM PKP DELAY: This setting specifies time delay for the alarm stage until the output can be
asserted.
• RTD INPUT H1 TRIP TEMPERATURE: This setting specifies the temperature pickup level for the trip stage.
• RTD INPUT H1 TRIP PKP DELAY: This setting specifies time delay for the trip stage until the output can be asserted.
• RTD INPUT H1 TRIP RST DELAY: This setting specifies the reset delay to seal-in the trip signal.
• RTD INPUT H1 TRIP VOTING: This setting allows securing trip signal by voting with other RTDs. A value of “None”
indicates that element operates individually and no voting takes place.
A value of “Group” indicates that element is allowed to issue a trip if N – 1 of other RTDs of the same group pick up as
well (where N is the number of enabled RTDs from the group). For example, if three RTDs are assigned to the same
group, there should be at least one additional RTD of the same group picked up to issue a trip command.
The “RTD Inp H1” through “RTD Inp W8” values indicate that element is allowed to issue a trip if the corresponding
peer RTD is also picked up.
• RTD INPUT H1 OPEN: This setting allows monitoring an open RTD sensor circuit. If this functionality is not required,
then a value of “None” will disable monitoring and assertion of output operands.
If set to “Alarm”, the monitor will set an alarm when a broken sensor is detected.
If set to “Block”, the monitor will set an alarm and simultaneously block RTD operation when a broken sensor is
detected.
If targets are enabled, a message will appear on the display identifying the broken RTD. If this feature is used, it is rec-
ommended that the alarm be programmed as latched so that intermittent RTDs are detected and corrective action may
be taken.
• RTD INPUT H1 BLOCK: This setting is used to block RTD operation.
SETTINGS
RTD INPUT H1 FUNCTION
= Enabled
RTD INPUT H1 BLOCK AND To other RTDs for voting
Off = 0
5 SETTINGS
SETTINGS
RTD INPUT H1 TRIP
PKP DELAY SETTINGS
SETTINGS RTD INPUT H1 TRIP RTD INPUT H1 TRIP RTD INPUT H1
RTD INPUT H1 ID TEMPERATURE RST DELAY APPLICATION
= RTD Inp H1 RTD INPUT H1 ALARM RTD INPUT H1 ALARM RTD INPUT H1 TRIP
TEMPERATURE PKP DELAY VOTING
RTD INPUT H1 TYPE
RUN TPKP FLEXLOGIC OPERAND
Resistance to Voting logic RTD Ip TRIP OP
temperature > TRIP PICKUP TDPO
temperature conversion
RUN TPKP
AND temperature > ALARM PICKUP From other RTDs for voting FLEXLOGIC OPERANDS
0
RTD Ip ALARM OP
SETTING
RTD Ip TRIP PKP
RTD INPUT H1 OPEN
Block RTD Ip TRIP DPO
RUN
Alarm RTD Ip ALARM PKP
R ³ 250°C OR
None RTD Ip ALARM DPO
RUN RTD Ip OPEN
RTD Ip SHORTED
R £ –50°C
833019A2.CDR
a) MAIN MENU
PATH: SETTINGS ÖØ TRANSDUCER I/O ÖØ RRTD INPUTS
RRTD 12
MESSAGE See page 5-267.
It is recommended to use the G60 to configure the RRTD parameters. If the RRTDPC software is used to change the
RRTD settings directly (the application and type settings), then one of the following two operations is required for changes
to be reflected in the G60.
• Cycle power to G60.
• Break then re-establish the communication link between the RRTD unit and the G60. This will cause the RRTD COMM
FAIL operand to be asserted then de-asserted.
The remote RTD inputs convert values of input resistance into temperature for further operations. These inputs are
intended to be connected to any of the RTD types in common use. Specific hardware details are contained in chapter 3.
On power up, the G60 reads and saves all application and type settings from the RRTD. This synchronizes the RRTD and
G60. Any changes to RRTD settings (function, application, or type) from the G60 interface are immediately reflected in the
RRTD. The following rules are followed.
• If the RRTD 1 FUNCTION setting is “Enabled”, then the RRTD 1 APPLICATION setting value will be written to RRTD device.
• If the RRTD 1 FUNCTION setting is “Disabled”, then RRTD1 APPLICATION setting value is set as “None”.
• If the RRTD 1 APPLICATION or RRTD 1 TYPE settings are changes, then these settings are immediately written to the
RRTD device.
• If the RRTD 1 APPLICATION setting is “Group 1” or “Group 2”, then a value of “Other” is written to the RRTD device.
An RRTD actual value of –43°C implies that the RRTD 1 FUNCTION setting is “Enabled” but the corresponding RRTD 1 APPLI-
CATION setting is “None”.
If the RRTD communication link with the G60 is broken, then the last temperature actual values are retained until the RRTD
communication failure is detected. When this occurs, a RRTD COMM FAILURE self-test alarm and target message is gen-
erated, and an event is logged in the event recorder and the temperature actual values reset to 0. When the link is re-estab-
lished, the RRTD 1 APPLICATION and RRTD 1 TYPE settings are read from the RRTD to re-synchronize the device.
• RRTD 1 FUNCTION: This setting enables and disables the remote RTD. If set to “Disabled”, no actual value is created
for the remote RTD.
• RRTD 1 ID: This setting is used to assign alphanumeric ID is assigned to the remote RTD. This ID will be included in
the remote RTD actual values. It is also used to reference the remote RTD input to features using the remote RTD.
• RRTD 1 TYPE: This setting specifies the remote RTD type. Four different RTD types are available: 100 Ω Nickel, 10 Ω
Copper, 100 Ω Platinum, and 120 Ω Nickel.
The RRTD converts resistance to temperature as per the values in the following table. The G60 reads the RTD temper-
atures from the RRTD once every five seconds and applies protection accordingly. The RRTDs can be used to provide
RTD bias in the existing thermal model.
An RRTD open condition is detected when actual RRTD resistance is greater than 1000 ohms and RRTD open is dis-
played as “250°C” in the G60.
An RRTD short condition is detected when actual RRTD temperature is less than –40°C and RRTD short is displayed
as is “–50°C”. in the G60.
• RRTD 1 APPLICATION: This setting allows each remote RTD to be assigned to a group application. This is useful for
applications that require group measurement for voting. A value of “None” specifies that the remote RTD will operate
individually and not part of any RTD group. All remote RTDs programmed to “Stator” are used for RTD biasing of the
G60 thermal model. Common groups are provided for rotating machines applications such as ambient, bearing, group
1, or group 2. If the REMOTE RTD 1 TRIP VOTING setting value is “Group”, then it is allowed to issue a trip if N – 1 RTDs
from the same group also pick up, where N is the number of enabled RTDs from the group.
• RRTD 1 ALARM TEMPERATURE: This setting specifies the temperature pickup level for the alarm stage. The range
of 1 to 200°C differs from the existing RTD settings to correspond to the range of the RRTD unit.
• RRTD 1 ALARM PKP DELAY: This setting specifies time delay for the alarm stage until the output can be asserted.
The range of 5 to 600 seconds differs from the existing RTD settings to correspond to the range of the RRTD unit.
• RRTD 1 TRIP TEMPERATURE: This setting specifies the temperature pickup level for the trip stage. The range of 1 to
200°C differs from the existing RTD settings to correspond to the range of the RRTD unit.
• RRTD 1 TRIP PKP DELAY: This setting specifies time delay for the trip stage until the output can be asserted. The
range of 5 to 600 seconds differs from the existing RTD settings to correspond to the range of the RRTD unit.
• RRTD 1 TRIP RST DELAY: This setting specifies the reset delay to seal-in the trip signal.
• RRTD 1 TRIP VOTING: This setting allows securing trip signal by voting with other RTDs. A value of “None” indicates
that element operates individually and no voting takes place.
A value of “Group” indicates that element is allowed to issue a trip if N – 1 of other RTDs of the same group pick up as
well (where N is the number of enabled RTDs from the group). For example, if three RTDs are assigned to the same
group, there should be at least one additional RTD of the same group picked up to issue a trip command.
The “Remote RTD 1” through “Remote RTD 12” values indicate that element is allowed to issue a trip if the corre- 5
sponding peer RTD is also picked up.
• RRTD 1 OPEN: This setting allows monitoring an open remote RTD sensor circuit. If this functionality is not required,
then a value of “None” will disable monitoring and assertion of output operands.
If set to “Alarm”, the monitor will set an alarm when a broken sensor is detected.
If set to “Block”, the monitor will set an alarm and simultaneously block remote RTD operation when a broken sensor is
detected.
If targets are enabled, a message will appear on the display identifying the broken RTD. If this feature is used, it is rec-
ommended that the alarm be programmed as latched so that intermittent RTDs are detected and corrective action may
be taken.
• RRTD 1 BLOCK: This setting is used to block remote RTD operation.
SETTINGS
Function
Enabled = 1
Block AND
Off = 0
SETTINGS
SETTINGS Trip Pickup Delay SETTINGS
AND
Trip Temperature Trip Reset Delay Application
SETTING
Alarm Temperature Alarm Pickup Delay Trip Voting
Type
RUN TPKP FLEXLOGIC OPERAND
Temperature read Voting logic REMOTE RTD 1 TRIP OP
temperature > Trip Pickup TDPO
from RRTD
RUN TPKP
temperature > Alarm Pickup From other remote FLEXLOGIC OPERANDS
0 RTDs for voting
RRTD 1 ALARM OP
SETTING
RRTD 1 TRIP PKP
Open
Block RRTD 1 TRIP DPO
RUN
Alarm RRTD 1 ALARM PKP
R > 1000 ohms OR
None RRTD 1 ALARM DPO
RUN RRTD 1 OPEN
RRTD 1 SHORTED
T £ –40°C
833026A1.CDR
Hardware and software is provided to generate dcmA signals that allow interfacing with external equipment. Specific hard-
ware details are contained in chapter 3. The dcmA output channels are arranged in a manner similar to transducer input or
CT and VT channels. The user configures individual channels with the settings shown below.
The channels are arranged in sub-modules of two channels, numbered 1 through 8 from top to bottom. On power-up, the
relay automatically generates configuration settings for every channel, based on the order code, in the same manner used
for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as
the channel number.
Both the output range and a signal driving a given output are user-programmable via the following settings menu (an exam-
ple for channel M5 is shown).
The relay checks the driving signal (x in equations below) for the minimum and maximum limits, and subsequently re-
scales so the limits defined as MIN VAL and MAX VAL match the output range of the hardware defined as RANGE. The follow-
ing equation is applied:
The feature is intentionally inhibited if the MAX VAL and MIN VAL settings are entered incorrectly, e.g. when MAX VAL – MIN
VAL< 0.1 pu. The resulting characteristic is illustrated in the following figure.
Imax
OUTPUT CURRENT
Imin
DRIVING SIGNAL
MIN VAL MAX VAL 842739A1.CDR
The base unit for power (refer to the FlexElements section in this chapter for additional details) is:
P BASE = 115 V × 120 × 1.2 kA = 16.56 MW (EQ 5.57)
The minimum and maximum power values to be monitored (in pu) are:
20.65 MW = – 1.247 pu, maximum power = 20.65 MW- = 1.247 pu
minimum power = –------------------------------ -------------------------- (EQ 5.58)
16.56 MW 16.56 MW
The following settings should be entered:
DCMA OUTPUT H1 SOURCE: “SRC 1 P”
DCMA OUTPUT H1 RANGE: “–1 to 1 mA”
DCMA OUTPUT H1 MIN VAL: “–1.247 pu”
DCMA OUTPUT H1 MAX VAL: “1.247 pu”
With the above settings, the output will represent the power with the scale of 1 mA per 20.65 MW. The worst-case error for
this application can be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or ± 0.005 × ( 1 – ( – 1 ) ) × 20.65 MW = ± 0.207 MW
• ±1% of reading error for the active power at power factor of 0.9
For example at the reading of 20 MW, the worst-case error is 0.01 × 20 MW + 0.207 MW = 0.407 MW.
EXAMPLE: CURRENT MONITORING
The phase A current (true RMS value) is to be monitored via the H2 current output working with the range from 4 to 20 mA.
The CT ratio is 5000:5 and the maximum load current is 4200 A. The current should be monitored from 0 A upwards, allow-
ing for 50% overload.
The phase current with the 50% overload margin is:
5 I max = 1.5 × 4.2 kA = 6.3 kA (EQ 5.59)
The base unit for current (refer to the FlexElements section in this chapter for additional details) is:
I BASE = 5 kA (EQ 5.60)
The minimum and maximum power values to be monitored (in pu) are:
The worst-case error for this application could be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or ± 0.005 × ( 20 – 4 ) × 6.3 kA = ± 0.504 kA
• ±0.25% of reading or ±0.1% of rated (whichever is greater) for currents between 0.1 and 2.0 of nominal
For example, at the reading of 4.2 kA, the worst-case error is max(0.0025 × 4.2 kA, 0.001 × 5 kA) + 0.504 kA = 0.515 kA.
EXAMPLE: VOLTAGE MONITORING
A positive-sequence voltage on a 400 kV system measured via source 2 is to be monitored by the dcmA H3 output with a
range of 0 to 1 mA. The VT secondary setting is 66.4 V, the VT ratio setting is 6024, and the VT connection setting is
“Delta”. The voltage should be monitored in the range from 70% to 110% of nominal.
The minimum and maximum positive-sequence voltages to be monitored are:
400 kV 400 kV
V min = 0.7 × ------------------- = 161.66 kV, V max = 1.1 × ------------------- = 254.03 kV (EQ 5.62)
3 3
The base unit for voltage (refer to the FlexElements section in this chapter for additional details) is:
The minimum and maximum voltage values to be monitored (in pu) are:
minimum voltage = 161.66 kV- = 0.404 pu, maximum voltage = 254.03 kV- = 0.635 pu
-------------------------- -------------------------- (EQ 5.64)
400 kV 400 kV
The following settings should be entered:
DCMA OUTPUT H3 SOURCE: “SRC 2 V_1 mag”
DCMA OUTPUT H3 RANGE: “0 to 1 mA”
DCMA OUTPUT H3 MIN VAL: “0.404 pu”
DCMA OUTPUT H3 MAX VAL: “0.635 pu”
The limit settings differ from the expected 0.7 pu and 1.1 pu because the relay calculates the positive-sequence quantities
scaled to the phase-to-ground voltages, even if the VTs are connected in “Delta” (refer to the Metering conventions section
in chapter 6), while at the same time the VT nominal voltage is 1 pu for the settings. Consequently the settings required in
this example differ from naturally expected by the factor of 3 .
The worst-case error for this application could be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or ± 0.005 × ( 1 – 0 ) × 254.03 kV = ± 1.27 kV
• ±0.5% of reading
For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is
0.005 x 230.94 kV + 1.27 kV = 2.42 kV.
The G60 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and
the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face-
plate by a Test Mode LED indicator.
The test mode may be in any of three states: disabled, isolated, or forcible.
In the “Disabled” mode, G60 operation is normal and all test features are disabled.
In the “Isolated” mode, the G60 is prevented from performing certain control actions, including tripping via contact outputs.
All relay contact outputs, including latching outputs, are disabled. Channel tests and phasor measurement unit tests remain
usable on applicable UR-series models.
In the “Forcible” mode, the operand selected by the TEST MODE FORCING setting controls the relay inputs and outputs. If the
test mode is forcible, and the operand assigned to the TEST MODE FORCING setting is “Off”, the G60 inputs and outputs oper-
ate normally. If the test mode is forcible, and the operand assigned to the TEST MODE FORCING setting is “On”, the G60 con-
tact inputs and outputs are forced to the values specified in the following sections. Forcing may be controlled by manually
changing the operand selected by the TEST MODE FORCING setting between on and off, or by selecting a user-programma-
ble pushbutton, contact input, or communication-based input operand. Channel tests and phasor measurement unit tests
When in “Forcible” mode, the operand selected by the TEST MODE FORCING setting dictates further response of the G60 to
testing conditions. To force contact inputs and outputs through relay settings, set TEST MODE FORCING to “On”. To force con-
tact inputs and outputs through a user-programmable condition, such as FlexLogic™ operand (pushbutton, digital input,
communication-based input, or a combination of these), set TEST MODE FORCING to the desired operand. The contact input
or output is forced when the selected operand assumes a logic 1 state.
The G60 remains fully operational in test mode, allowing for various testing procedures. In particular, the protection and
control elements, FlexLogic™, and communication-based inputs and outputs function normally.
The only difference between the normal operation and the test mode is the behavior of the input and output contacts. The
contact inputs can be forced to report as open or closed or remain fully operational, whereas the contact outputs can be
forced to open, close, freeze, or remain fully operational. The response of the digital input and output contacts to the test
mode is programmed individually for each input and output using the force contact inputs and force contact outputs test
functions described in the following sections.
The test mode state is indicated on the relay faceplate by a combination of the Test Mode LED indicator, the In-Service LED
indicator, and by the critical fail relay, as shown in the following table.
The TEST MODE FUNCTION setting can only be changed by a direct user command. Following a restart, power up, settings
upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a G60 that has been
placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING
setting and the force contact input and force contact output settings all revert to their default states.
The relay digital inputs (contact inputs) could be pre-programmed to respond to the test mode in the following ways:
• If set to “Disabled”, the input remains fully operational. It is controlled by the voltage across its input terminals and can
be turned on and off by external circuitry. This value should be selected if a given input must be operational during the
test. This includes, for example, an input initiating the test, or being a part of a user pre-programmed test sequence.
• If set to “Open”, the input is forced to report as opened (Logic 0) for the entire duration of the test mode regardless of
the voltage across the input terminals.
• If set to “Closed”, the input is forced to report as closed (Logic 1) for the entire duration of the test mode regardless of
the voltage across the input terminals.
The force contact inputs feature provides a method of performing checks on the function of all contact inputs. Once
enabled, the relay is placed into test mode, allowing this feature to override the normal function of contact inputs. The Test
Mode LED will be on, indicating that the relay is in test mode. The state of each contact input may be programmed as “Dis-
abled”, “Open”, or “Closed”. All contact input operations return to normal when all settings for this feature are disabled.
The relay contact outputs can be pre-programmed to respond to the test mode.
If set to “Disabled”, the contact output remains fully operational. If operates when its control operand is logic 1 and will
resets when its control operand is logic 0. If set to “Energized”, the output will close and remain closed for the entire dura-
tion of the test mode, regardless of the status of the operand configured to control the output contact. If set to “De-ener-
gized”, the output will open and remain opened for the entire duration of the test mode regardless of the status of the
operand configured to control the output contact. If set to “Freeze”, the output retains its position from before entering the
test mode, regardless of the status of the operand configured to control the output contact.
These settings are applied two ways. First, external circuits may be tested by energizing or de-energizing contacts. Sec-
ond, by controlling the output contact state, relay logic may be tested and undesirable effects on external circuits avoided.
Example 1: Initiating test mode through user-programmable pushbutton 1
5 For example, the test mode can be initiated from user-programmable pushbutton 1. The pushbutton will be programmed as
“Latched” (pushbutton pressed to initiate the test, and pressed again to terminate the test). During the test, digital input 1
should remain operational, digital inputs 2 and 3 should open, and digital input 4 should close. Also, contact output 1 should
freeze, contact output 2 should open, contact output 3 should close, and contact output 4 should remain fully operational.
The required settings are shown below.
To enable user-programmable pushbutton 1 to initiate the test mode, make the following changes in the SETTINGS ÖØ
TESTING Ö TEST MODE menu: TEST MODE FUNCTION: “Enabled” and TEST MODE INITIATE: “PUSHBUTTON 1 ON”
Make the following changes to configure the contact inputs and outputs. In the SETTINGS ÖØ TESTING ÖØ FORCE CONTACT
INPUTS and FORCE CONTACT OUTPUTS menus, set:
FORCE Cont Ip 1: “Disabled”, FORCE Cont Ip 2: “Open”, FORCE Cont Ip 3: “Open”, and FORCE Cont Ip 4: “Closed”
FORCE Cont Op 1: “Freeze”, FORCE Cont Op 2: “De-energized”, FORCE Cont Op 3: “Energized”,
and FORCE Cont Op 4: “Disabled”
Example 2: Initiating a test from user-programmable pushbutton 1 or through remote input 1
In this example, the test can be initiated locally from user-programmable pushbutton 1 or remotely through remote input 1.
Both the pushbutton and the remote input will be programmed as “Latched”. Write the following FlexLogic™ equation:
Set the user-programmable pushbutton as latching by changing SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE
PUSHBUTTONS Ö USER PUSHBUTTON 1 Ö PUSHBUTTON 1 FUNCTION to “Latched”. To enable either pushbutton 1 or remote
input 1 to initiate the Test mode, make the following changes in the SETTINGS ÖØ TESTING Ö TEST MODE menu:
TEST MODE FUNCTION: “Enabled” and TEST MODE INITIATE: “VO1”
The relay must be in test mode to use the PMU test mode. That is, the TESTING Ö TEST MODE FUNCTION setting must be
“Enabled” and the TESTING ÖØ TEST MODE INITIATE initiating signal must be “On”.
During the PMU test mode, the physical channels (VA, VB, VC, VX, IA, IB, IC, and IG), frequency, and rate of change of fre-
quency are substituted with user values, while the symmetrical components are calculated from the physical channels. The
test values are not explicitly marked in the outgoing data frames. When required, it is recommended to use the user-pro-
grammable digital channels to signal the C37.118 client that test values are being sent in place of the real measurements.
SOURCE SRC 2
SOURCE SRC 3
SOURCE SRC 4
SYNCHROCHECK
See page 6-19.
TRACKING FREQUENCY
See page 6-20.
FREQUENCY RATE
See page 6-20.
OF CHANGE
FREQUENCY OOB
See page 6-20.
ACCUMULATION
FLEXELEMENTS
See page 6-21.
IEC 61850
See page 6-22.
GOOSE ANALOGS
SENSITIVE
See page 6-22.
DIRECTIONAL POWER
STATOR
See page 6-22.
GROUND
SUB-HARMONIC
See page 6-23.
STATOR GROUND
6 FIELD
GROUND
See page 6-23.
DATA LOGGER
See page 6-27.
PMU RECORDS
See page 6-27.
6.2STATUS
For status reporting, ‘On’ represents Logic 1 and ‘Off’ represents Logic 0.
NOTE
The present status of the contact inputs is shown here. The first line of a message display indicates the ID of the contact
input. For example, ‘Cont Ip 1’ refers to the contact input in terms of the default name-array index. The second line of the
display indicates the logic state of the contact input.
The present status of the 64 virtual inputs is shown here. The first line of a message display indicates the ID of the virtual
input. For example, ‘Virt Ip 1’ refers to the virtual input in terms of the default name. The second line of the display indicates
the logic state of the virtual input.
REMOTE DPS INPUTS REMOTE DPS INPUT 1 Range: On, Off, Intermediate, Bad
STATUS: Bad
REMOTE DPS INPUT 2 Range: On, Off, Intermediate, Bad
MESSAGE
STATUS: Bad
↓
The present state of the remote double-point status inputs is shown here. The actual values indicate if the remote double-
point status inputs are in the on (close), off (open), intermediate, or bad state.
The present state of teleprotection inputs from communication channels 1 and 2 are shown here. The state displayed will
be that of corresponding remote output unless the channel is declared failed.
CONTACT OUTPUTS Cont Op 1 Range: On, Off, VOff, VOn, IOn, IOff
Off
Cont Op 2 Range: On, Off, VOff, VOn, IOn, IOff
MESSAGE
Off
↓
The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff,
On, IOn, and VOn. For form-C contact outputs, the state is displayed as Off or On.
NOTE
The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic™ equation for that output.
a) STATUS
PATH: ACTUAL VALUES Ö STATUS ÖØ REMOTE DEVICES STATUS
6 MESSAGE
REMOTE DEVICE 2
STATUS: Offline
Range: Online, Offline
The present state of the programmed remote devices is shown here. The ALL REMOTE DEVICES ONLINE message indicates
whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required
remote device is not online.
b) STATISTICS
PATH: ACTUAL VALUES Ö STATUS ÖØ REMOTE DEVICES STATISTICS Ö REMOTE DEVICE 1(16)
Statistical data (two types) for up to 16 programmed remote devices is shown here.
The StNum number is obtained from the indicated remote device and is incremented whenever a change of state of at
least one DNA or UserSt bit occurs. The SqNum number is obtained from the indicated remote device and is incremented
whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented.
PATH: ACTUAL VALUES Ö STATUS ÖØ DIGITAL COUNTERS Ö DIGITAL COUNTERS Counter 1(8)
The present status of the eight digital counters is shown here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label will also appear). Also included, is the date and
time stamp for the frozen count. The COUNTER 1 MICROS value refers to the microsecond portion of the time stamp.
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
There are 256 FlexState bits available. The second line value indicates the state of the given FlexState bit.
6.2.12 ETHERNET
These values indicate the status of the primary and secondary Ethernet links.
The AVERAGE MSG RETURN TIME is the time taken for direct output messages to return to the sender in a direct input/output
ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last
ten messages. There are two return times for dual-channel communications modules.
6 The UNRETURNED MSG COUNT values (one per communications channel) count the direct output messages that do not
make the trip around the communications ring. The CRC FAIL COUNT values (one per communications channel) count the
direct output messages that have been received but fail the CRC check. High values for either of these counts may indicate
on a problem with wiring, the communication channel, or one or more relays. The UNRETURNED MSG COUNT and CRC FAIL
COUNT values can be cleared using the CLEAR DIRECT I/O COUNTERS command.
The DIRECT INPUT 1 to DIRECT INPUT (32) values represent the state of each direct input.
These actual values represent the state of direct devices 1 through 16.
UINT INPUT 16
MESSAGE
0
The G60 Generator Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received
via IEC 61850 GOOSE messages sent from other devices.
a) FAST EXCHANGE
PATH: ACTUAL VALUES Ö STATUS ÖØ EGD PROTOCOL STATUS Ö PRODUCER STATUS Ö FAST EXCHANGE 1
These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size
6
for the fast EGD exchange is displayed.
b) SLOW EXCHANGE
PATH: ACTUAL VALUES Ö STATUS ÖØ EGD PROTOCOL STATUS Ö PRODUCER STATUS ÖØ SLOW EXCHANGE 1(2)
These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size
for the slow EGD exchanges are displayed.
• VALIDITY OF CHANNEL CONFIGURATION: This value displays the current state of the communications channel
identification check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the
“FAIL” message will be displayed. The “N/A” value appears if the local relay ID is set to a default value of “0”, the chan-
nel is failed, or if the teleprotection inputs/outputs are not enabled.
These actual values appear only if the G60 is ordered with an Ethernet switch module (type 2S or 2T). The status informa-
tion for the Ethernet switch is shown in this menu.
• SWITCH 1 PORT STATUS to SWITCH 6 PORT STATUS: These values represents the receiver status of each port on
the Ethernet switch. If the value is “OK”, then data is being received from the remote terminal; If the value is “FAIL”,
then data is not being received from the remote terminal or the port is not connected.
• SWITCH MAC ADDRESS: This value displays the MAC address assigned to the Ethernet switch module.
Voltage +Q
VCG
WATTS = Positive IC
PF = Lead PF = Lag
VARS = Positive
PF = Lag IA
VAG -P +P
Current
IB IA
PF = Lag PF = Lead
UR RELAY
VBG -Q
M LOAD
- 1
Inductive Resistive S=VI
Generator
VCG
+Q
Voltage
PF = Lead PF = Lag
WATTS = Positive
IA
VARS = Negative IC
PF = Lead VAG -P +P
IA
Current
PF = Lag PF = Lead
IB
UR RELAY
VBG -Q
LOAD S=VI
-
Inductive
Resistive
Resistive
2
6
M LOAD
VCG +Q
Voltage
PF = Lead PF = Lag
IB
IA
WATTS = Negative
VAG
VARS = Negative -P +P
PF = Lag
IA
IC PF = Lag PF = Lead
Current
VBG
-Q
UR RELAY
G S=VI
- 3
Generator
Resistive
LOAD
VCG
+Q
Voltage IB
PF = Lead PF = Lag
WATTS = Negative IA
VARS = Positive VAG -P +P
PF = Lead
IC
IA
Current
PF = Lag PF = Lead
VBG -Q
UR RELAY
G 827239AC.CDR
- 4
S=VI
Generator
Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS
-270o
-225o -315o
positive
angle
direction
-180o 0o
UR phase angle
reference
-135o -45o
6 -90o 827845A1.CDR
The zero-sequence voltage is not measurable under the Delta connection of instrument transformers and is defaulted to
zero. The table below shows an example of symmetrical components calculations for the ABC phase rotation.
Table 6–1: SYMMETRICAL COMPONENTS CALCULATION EXAMPLE
SYSTEM VOLTAGES, SEC. V * VT RELAY INPUTS, SEC. V SYMM. COMP, SEC. V
CONN.
VAG VBG VCG VAB VBC VCA F5AC F6AC F7AC V0 V1 V2
13.9 76.2 79.7 84.9 138.3 85.4 WYE 13.9 76.2 79.7 19.5 56.5 23.3
∠0° ∠–125° ∠–250° ∠–313° ∠–97° ∠–241° ∠0° ∠–125° ∠–250° ∠–192° ∠–7° ∠–187°
UNKNOWN (only V1 and V2 84.9 138.3 85.4 DELTA 84.9 138.3 85.4 N/A 56.5 23.3
can be determined) ∠0° ∠–144° ∠–288° ∠0° ∠–144° ∠–288° ∠–54° ∠–234°
* The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a
relative matter. It is important to remember that the G60 displays are always referenced as specified under SETTINGS
ÖØ SYSTEM SETUP ÖØ POWER SYSTEM ÖØ FREQUENCY AND PHASE REFERENCE.
The example above is illustrated in the following figure.
6
reference
1
UR phase angle
A
reference
WYE VTs
C
B
0
2
U
re R ph
fe a
re se
nc a
e ng
le
A U
1
re R ph
fe a
re se
nc a
e ng
DELTA VTs le
C
B
2
827844A1.CDR
The phasors of differential and restraint currents are displayed in primary amperes.
6.3.3 SOURCES
a) MAIN MENU
PATH: ACTUAL VALUES ÖØ METERING ÖØ SOURCE SRC1
This menu displays the metered values available for each source.
Metered values presented for each source depend on the phase and auxiliary VTs and phase and ground CTs assignments
for this particular source. For example, if no phase VT is assigned to this source, then any voltage, energy, and power val-
ues will be unavailable.
MESSAGE
SRC 1 NEG SEQ I2:
0.000 A 0.0°
6
The metered phase current values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
The metered ground current values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
6 MESSAGE
SRC 1 PHASOR Vca:
0.000 V 0.0°
SRC 1 ZERO SEQ V0:
MESSAGE
0.000 V 0.0°
SRC 1 POS SEQ V1:
MESSAGE
0.000 V 0.0°
SRC 1 NEG SEQ V2:
MESSAGE
0.000 V 0.0°
The metered phase voltage values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
The metered auxiliary voltage values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
f) POWER METERING
PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ POWER
MESSAGE
SRC 1 APPARENT PWR
φc: 0.000 VA
6
SRC 1 POWER FACTOR
MESSAGE
3φ: 1.000
SRC 1 POWER FACTOR
MESSAGE
φa: 1.000
SRC 1 POWER FACTOR
MESSAGE
φb: 1.000
SRC 1 POWER FACTOR
MESSAGE
φc: 1.000
The metered values for real, reactive, and apparent power, as well as power factor, are displayed in this menu. The "SRC
1" text will be replaced by whatever name was programmed by the user for the associated source (see SETTINGS ÖØ SYS-
TEM SETUP ÖØ SIGNAL SOURCES).
g) ENERGY METERING
PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ ENERGY
The metered values for real and reactive energy are displayed in this menu. The "SRC 1" text will be replaced by whatever
name was programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
Because energy values are accumulated, these values should be recorded and then reset immediately prior to changing
CT or VT characteristics.
h) FREQUENCY METERING
PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ FREQUENCY
The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
SOURCE FREQUENCY is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the SYSTEM SETUP ÖØ POWER SYSTEM settings). The signal used for frequency estimation is low-pass filtered. The
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
6
i) CURRENT HARMONICS AND THD METERING
PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ CURRENT HARMONICS
The metered current harmonics values are displayed in this menu. The "SRC 1" text will be replaced by whatever name
was programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES). Current
harmonics are measured for each source for the total harmonic distortion (THD) and 2nd to 25th harmonics per phase.
The metered current harmonics values are displayed in this menu. The “SRC 1” text will be replaced by the programmed
name for the associated source (see the SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES menu).
To extract the 2nd to 25th voltage harmonics, each harmonic is computed on a per-phase basis, where:
N = 64 is the number of samples per cycle
ω0 = 2πf is the angular frequency based on the system frequency (50 or 60 Hz)
k = 1, 2,..., N – 1 is the index over one cycle for the Fast Fourier Transform (FFT)
m is the last sample number for the sliding window
h = 1, 2,..., 25 is the harmonic number
The short-time Fourier transform is applied to the unfiltered signal:
2
F real ( m, h ) = ---- ∑ ( f ( m – k ) ⋅ cos ( h ⋅ ω 0 ⋅ t ( k ) ) )
N
k
2
F imag ( m, h ) = ---- ∑ ( f ( m – k ) ⋅ sin ( h ⋅ ω 0 ⋅ t ( k ) ) ) (EQ 6.1)
N
k
F ampl ( m, h ) =
2
F real ( m, h ) + F imag ( m, h )
2 6
The harmonics are a percentage of the fundamental signal obtained as a ratio of harmonic amplitude to fundamental ampli-
tude multiplied by 100%. The total harmonic distortion (THD) is the ratio of the total harmonic content to the fundamental:
2 2 2
THD = F 2 + F 3 + … + F 25 (EQ 6.2)
Voltage harmonics are calculated only for Wye connected phase VTs. Ensure the SYSTEM SETUP Ö AC INPUTS ÖØ
VOLTAGE BANK F5 ÖØ PHASE VT XX CONNECTION setting is “Wye” to enable voltage harmonics metering.
NOTE
6.3.4 SYNCHROCHECK
The actual values menu for synchrocheck 2 is identical to that of synchrocheck 1. If a synchrocheck function setting is "Dis-
abled", the corresponding actual values menu item will not be displayed.
The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE setting in the SETTINGS ÖØ SYSTEM SETUP ÖØ POWER SYSTEM menu. Refer to the
Power System section of chapter 5 for additional details.
The metered frequency rate of change for the frequency rate of change elements is shown here.
6 FREQUENCY OOB
ACCUMULATION
FREQUENCY OOB BAND 1
ACCUMULATION: 0.0%
FREQUENCY OOB BAND 2
MESSAGE
ACCUMULATION: 0.0%
↓
FREQUENCY OOB BAND 7
MESSAGE
ACCUMULATION: 0.0%
The frequency out-of-band accumulation metered values are displayed to the nearest percent as a ratio of the present
accumulation to the user-specified limit. Note that this value can be greater than 100%.
6.3.8 FLEXELEMENTS™
FLEXELEMENT 1 FLEXELEMENT 1
OpSig: 0.000 pu
The operating signals for the FlexElements™ are displayed in pu values using the following definitions of the base units.
ANALOG INPUT 32
MESSAGE
0.000
The G60 Generator Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received
via IEC 61850 GOOSE messages sent from other devices.
The effective operating quantities of the sensitive directional power elements are displayed here. The display may be useful
to calibrate the feature by compensating the angular errors of the CTs and VTs with the use of the RCA and CALIBRATION
settings.
Magnitudes of the third harmonic components of the machine neutral point voltage (VN), the zero-sequence voltage at the
machine terminals (V0), and in the vector sum of the neutral point voltage and zero-sequence voltage (VN + V0) are avail-
able for display. The values are calculated for a signal source specified under the stator ground settings menu.
These readings may be useful when selecting a pickup and supervision setting for the 100% stator ground and third har-
monic neutral undervoltage protection elements.
Actual values related to sub-harmonic stator ground protection are displayed in this menu.
Actual values related to field ground protection are displayed in this menu.
The volts per hertz actual values are displayed in this menu.
PATH: ACTUAL VALUES ÖØ METERING ÖØ RESTRICTED GROUND FAULT CURRENTS Ö RESTRICTED GROUND FAULT 1(4)
The differential and restraint current values for the restricted ground fault element are displayed in this menu.
The above actual values are displayed without the corresponding time stamp as they become available per the recording
rate setting. Also, the recording post-filtering setting is applied to these values.
PATH: ACTUAL VALUES ÖØ METERING ÖØ TRANSDUCER I/O DCMA INPUTS Ö DCMA INPUT xx
Actual values for each dcmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
PATH: ACTUAL VALUES ÖØ METERING ÖØ TRANSDUCER I/O RTD INPUTS Ö RTD INPUT xx
Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and
the bottom line as the value.
This menu displays the user-programmable fault report actual values. See the User-Programmable Fault Report section in
chapter 5 for additional information on this feature.
EVENT: 3 EVENT 3
MESSAGE
POWER ON DATE: 2000/07/14
EVENT: 2 EVENT 3
MESSAGE
POWER OFF TIME: 14:53:00.03405
EVENT: 1
MESSAGE Date and Time Stamps
EVENTS CLEARED
6 The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological order
from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record is
added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the
event trigger. Refer to the COMMANDS Ø CLEAR RECORDS menu for clearing event records.
6.4.3 OSCILLOGRAPHY
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
CYCLES PER RECORD value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog-
raphy section of chapter 5 for additional details.
A trigger can be forced here at any time by setting “Yes” to the FORCE TRIGGER? command. Refer to the COMMANDS ÖØ
CLEAR RECORDS menu for information on clearing the oscillography records.
The OLDEST SAMPLE TIME represents the time at which the oldest available samples were taken. It will be static until the log
gets full, at which time it will start counting at the defined sampling rate. The NEWEST SAMPLE TIME represents the time the
most recent samples were taken. It counts up at the defined sampling rate. If the data logger channels are defined, then
both values are static.
Refer to the COMMANDS ÖØ CLEAR RECORDS menu for clearing data logger records.
The number of triggers applicable to the phasor measurement unit recorder is indicated by the NUMBER OF TRIGGERS value.
The status of the phasor measurement unit recorder is indicated as follows:
PATH: ACTUAL VALUES Ö RECORDS ÖØ PMU RECORDS Ö PMU 1 RECORDING
MESSAGE
PUM 1 AVAILABLE Range: 0 to 65535 in steps of 1 6
RECORDS: 0
PUM 1 SECONDS Range: 0 to 6553.5 in steps of 0.1
MESSAGE
PER RECORD: 0.0
PUM 1 LAST CLEARED: Range: date and time in format shown
MESSAGE
2005/07/14 015:40:16
MODEL INFORMATION ORDER CODE LINE 1: Range: standard GE multilin order code format;
G60-E00-HCH-F8G-H6B example order code shown
The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been
installed.
COMMANDS
Ø
COMMANDS
MESSAGE
VIRTUAL INPUTS
COMMANDS
MESSAGE
CLEAR RECORDS
COMMANDS
MESSAGE
SET DATE AND TIME
COMMANDS
MESSAGE
PMU ONE-SHOT
The commands menu contains relay directives intended for operations personnel. All commands can be protected from
unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash mes-
sage appears after successfully command entry:
COMMAND
EXECUTED
MESSAGE
Virt Ip 64
Off
Range: Off, On
7
The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The
second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1).
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-
mand setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to “No”.
The date and time can be entered here via the faceplate keypad only if the IRIG-B or SNTP signal is not in use. The time
setting is based on the 24-hour clock. The complete date, as a minimum, must be entered to allow execution of this com-
mand. The new time will take effect at the moment the ENTER key is clicked.
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are activated
by changing a command setting to “Yes” and pressing the ENTER key. The command setting will then automatically revert
to “No”. The service command is activated by entering a numerical code and pressing the ENTER key.
The PERFORM LAMPTEST command turns on all faceplate LEDs and display pixels for a short duration. The UPDATE
ORDER CODE command causes the relay to scan the backplane for the hardware modules and update the order code to
match. If an update occurs, the following message is shown.
UPDATING...
PLEASE WAIT
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER
CODE NOT UPDATED message will be shown.
The SERVICE COMMAND is used to perform specific G60 service actions. Presently, there is only one service action avail-
able. Code “101” is used to clear factory diagnostic information stored in the non-volatile memory. If a code other than “101”
is entered, the command will be ignored and no actions will be taken. Various self-checking diagnostics are performed in
the background while the G60 is running, and diagnostic information is stored on the non-volatile memory from time to time
based on the self-checking result. Although the diagnostic information is cleared before the G60 is shipped from the factory,
the user may want to clear the diagnostic information for themselves under certain circumstances. For example, it may be
desirable to clear diagnostic information after replacement of hardware. Once the diagnostic information is cleared, all self-
checking variables are reset to their initial state and diagnostics will restart from scratch.
This feature allows pre-scheduling a PMU measurement at a specific point in time. This functionality can be used to test for
accuracy of the PMU, and for manual collection of synchronized measurements through the system, as explained below.
When enabled, the function continuously compares the present time with the pre-set PMU ONE-SHOT TIME. When the two
times match, the function compares the present sequence number of the measured synchrophasors with the pre-set PMU
ONE-SHOT SEQUENCE NUMBER. When the two numbers match, the function freezes the synchrophasor actual values and
the corresponding protocol data items for 30 seconds. This allows manual read-out of the synchrophasor values for the pre-
set time and pre-set sequence number (via the faceplate display, supported communication protocols such as Modbus or
DNP, and the EnerVista UR Setup software).
When freezing the actual values the function also asserts a PMU ONE-SHOT OP FlexLogic™ operand. This operand may be
configured to drive an output contact and trigger an external measuring device such as a digital scope with the intent to ver-
ify the accuracy of the PMU under test.
With reference to the figure below, the PMU one-shot function (when enabled) controls three FlexLogic™ operands:
• The PMU ONE-SHOT EXPIRED operand indicates that the one-shot operation has been executed, and the present time
is at least 30 seconds past the scheduled one-shot time.
• The PMU ONE-SHOT PENDING operand indicates that the one-shot operation is pending; that is, the present time is
before the scheduled one-shot time.
• The PMU ONE-SHOT OP operand indicates the one-shot operation and remains asserted for 30 seconds afterwards.
When the function is disabled, all three operands are de-asserted. The one-shot function applies to all logical PMUs of a
given G60 relay.
sured signals are raw inputs to the PMU under test, their independently captured record, processed using third-party soft-
ware, is a good reference point for accuracy calculations. Such a record proves useful when discussing the test results, and
should be retained as a part of the testing documentation.
Note that the PMU under such test does not have to be connected to a real GPS receiver as the accuracy is measured with
respect to the timing reference provided to the PMU and not to the absolute UTC time. Therefore a simple IRIG-B genera-
tor could be used instead. Also, the test set does not have to support GPS synchronization. Any stable signal source can
be used. If both the PMU under test and the test set use the timing reference, they should be driven from the same IRIG-B
signal: either the same GPS receiver or IRIG-B generator. Otherwise, the setpoints of the test set and the PMU measure-
ments should not be compared as they are referenced to different time scales.
Figure 7–2: USING THE PMU ONE-SHOT FEATURE TO TEST SYNCHROPHASOR MEASUREMENT ACCURACY
COLLECTING SYNCHRONIZED MEASUREMENTS AD HOC:
The one-shot feature can be used for ad hoc collection of synchronized measurements in the network. Two or more PMU
can be pre-scheduled to freeze their measurements at the same time. When frozen the measurements could be collected
using EnerVista UR Setup or a protocol client.
TARGETS
Ø
DIGITAL ELEMENT 1: Displayed only if targets for this element are active.
MESSAGE Example shown.
LATCHED
DIGITAL ELEMENT 48: Displayed only if targets for this element are active.
MESSAGE Example shown.
LATCHED
MESSAGE
↓
↓
The status of any active targets will be displayed in the targets menu. If no targets are active, the display will read NO
ACTIVE TARGETS:
When there are no active targets, the first target to become active will cause the display to immediately default to that mes-
sage. If there are active targets and the user is navigating through other messages, and when the default message timer
times out (i.e. the keypad has not been used for a determined period of time), the display will again default back to the tar-
get message.
The range of variables for the target messages is described below. Phase information will be included if applicable. If a tar-
get message status changes, the status with the highest priority will be displayed.
If a self test error is detected, a message appears indicating the cause of the error. For example UNIT NOT PROGRAMMED
indicates that the minimal relay settings have not been programmed.
7
7.2.3 RELAY SELF-TESTS
a) DESCRIPTION
The relay performs a number of self-test diagnostic checks to ensure device integrity. The two types of self-tests (major and
minor) are listed in the tables below. When either type of self-test error occurs, the Trouble LED Indicator will turn on and a
target message displayed. All errors record an event in the event recorder. Latched errors can be cleared by pressing the
RESET key, providing the condition is no longer present.
Major self-test errors also result in the following:
• The critical fail relay on the power supply module is de-energized.
• All other output relays are de-energized and are prevented from further operation.
• The faceplate In Service LED indicator is turned off.
• A RELAY OUT OF SERVICE event is recorded.
MODULE FAILURE___:
Contact Factory (xxx)
INCOMPATIBLE H/W:
Contact Factory (xxx)
• Latched target message: Yes.
• Description of problem: One or more installed hardware modules is not compatible with the G60 order code.
• How often the test is performed: Module dependent.
• What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod-
ule (for example, F8L).
EQUIPMENT MISMATCH:
with 2nd line detail
• Latched target message: No.
• Description of problem: The configuration of modules does not match the order code stored in the G60.
• How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every five sec-
onds.
• What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If
the problem persists, contact the factory.
FLEXLOGIC ERROR:
with 2nd line detail 7
• Latched target message: No.
• Description of problem: A FlexLogic™ equation is incorrect.
• How often the test is performed: The test is event driven, performed whenever FlexLogic™ equations are modified.
• What to do: Finish all equation editing and use self tests to debug any errors.
MAINTENANCE ALERT:
Replace Battery
• Latched target message: Yes.
• Description of problem: The battery is not functioning.
• How often the test is performed: The battery is monitored every five seconds. The error message is displayed after 60
seconds if the problem persists.
• What to do: Replace the battery located in the power supply module (1H or 1L).
MAINTENANCE ALERT:
7 Direct I/O Ring Break
• Latched target message: No.
• Description of problem: Direct input and output settings are configured for a ring, but the connection is not in a ring.
• How often the test is performed: Every second.
• What to do: Check direct input and output configuration and wiring.
MAINTENANCE ALERT:
ENET MODULE OFFLINE
• Latched target message: No.
• Description of problem: The G60 has failed to detect the Ethernet switch.
• How often the test is performed: Monitored every five seconds. An error is issued after five consecutive failures.
• What to do: Check the G60 device and switch IP configuration settings. Check for incorrect UR port (port 7) settings on
the Ethernet switch. Check the power to the switch.
MAINTENANCE ALERT:
ENET PORT # OFFLINE
MAINTENANCE ALERT:
**Bad IRIG-B Signal**
MAINTENANCE ALERT:
Port ## Failure
MAINTENANCE ALERT:
SNTP Failure
MAINTENANCE ALERT:
4L Discrepancy
MAINTENANCE ALERT:
GGIO Ind xxx oscill
• How often the test is performed: Upon scanning of each configurable GOOSE data set.
• What to do: The “xxx” text denotes the data item that has been detected as oscillating. Evaluate all logic pertaining to
this item.
TEMP MONITOR:
OVER TEMPERATURE
UNEXPECTED RESTART:
Press “RESET” key
• Latched target message: Yes.
7 • Description of problem: Abnormal restart from modules being removed or inserted while the G60 is powered-up, when
there is an abnormal DC supply, or as a result of internal relay failure.
• How often the test is performed: Event driven.
• What to do: Contact the factory.
GPM-F FAILURE:
TROUBLE 01
• Latched target message: No.
• Description of problem: The G60 detects loss of communication with the field ground module on the RS485 link.
• How often the test is performed: Every five seconds.
• What to do: Check the field ground module and its RS485 connection to G60.
GPM-F FAILURE:
TROUBLE 02
GPM-F FAILURE:
TROUBLE 03
GPM-F FAILURE:
TROUBLE 04
• Latched target message: No.
• Description of problem: The setting for field ground module injection frequency does not match the injection frequency
reported by the module.
• How often the test is performed: Every second.
• What to do: The field ground module may be connected to another G60 through its alternate RS485 port and it might
be receiving another frequency setting. Please ensure both G60 devices connected to the same field ground module
have the same injection frequency setting.
GPM-F FAILURE:
TROUBLE 05
GPM-F FAILURE:
TROUBLE 06
• Latched target message: No.
• Description of problem: The firmware revision of the field ground module is not supported by the present revision of
G60 device. Please contact the factory.
• How often the test is performed: Every second.
• What to do: Check the firmware revision of the field ground module in the G60 actual values and contact the factory.
Two levels of password security are provided via the ACCESS LEVEL setting: command and setting. The factory service level
is not available and intended for factory use only.
The following operations are under command password supervision:
• Changing the state of virtual inputs.
• Clearing the event records.
• Clearing the oscillography records.
• Changing the date and time.
• Clearing energy records.
• Clearing the data logger.
• Clearing the user-programmable pushbutton states.
The following operations are under setting password supervision:
• Changing any setting.
• Test mode operation.
The command and setting passwords are defaulted to “0” when the relay is shipped from the factory. When a password is
set to “0”, the password security feature is disabled.
The G60 supports password entry from a local or remote connection.
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear
communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the G60, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password must be used.
The PASSWORD ACCESS EVENTS settings allows recording of password access events in the event recorder.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command ses-
sions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic™ operands.
• ACCESS LOC SETG OFF: Asserted when local setting access is disabled.
• ACCESS LOC SETG ON: Asserted when local setting access is enabled.
• ACCESS LOC CMND OFF: Asserted when local command access is disabled.
• ACCESS LOC CMND ON: Asserted when local command access is enabled.
• ACCESS REM SETG OFF: Asserted when remote setting access is disabled.
8
• ACCESS REM SETG ON: Asserted when remote setting access is enabled.
• ACCESS REM CMND OFF: Asserted when remote command access is disabled.
• ACCESS REM CMND ON: Asserted when remote command access is enabled.
The appropriate events are also logged in the Event Recorder as well. The FlexLogic™ operands and events are updated
every five seconds.
A command or setting write operation is required to update the state of all the remote and local security operands
shown above.
NOTE
CHANGE LOCAL
MESSAGE See page 8–2.
PASSWORDS
ACCESS
MESSAGE See page 8–3.
SUPERVISION
DUAL PERMISSION
MESSAGE See page 8–4.
SECURITY ACCESS
PASSWORD ACCESS Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
Proper password codes are required to enable each access level. A password consists of 1 to 10 numerical characters.
When a CHANGE COMMAND PASSWORD or CHANGE SETTING PASSWORD setting is programmed to “Yes” via the front panel
interface, the following message sequence is invoked:
1. ENTER NEW PASSWORD: ____________.
2. VERIFY NEW PASSWORD: ____________.
3. NEW PASSWORD HAS BEEN STORED.
To gain write access to a “Restricted” setting, program the ACCESS LEVEL setting in the main security menu to “Setting” and
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access will be allowed. Accessibility automatically reverts to the “Restricted” level according
to the access level timeout setting values.
8 If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD.
If the setting and command passwords are identical, then this one password allows access to both com-
mands and settings.
NOTE
The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the
Settings > Product Setup > Password Security menu item to open the remote password settings window.
5. The new password is accepted and a value is assigned to the ENCRYPTED PASSWORD item.
If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password 8
value.
These settings allow the user to specify the length of inactivity required before returning to the restricted access level. Note
that the access level will set as restricted if control power is cycled.
• COMMAND LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
• SETTING LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
DUAL PERMISSION LOCAL SETTING AUTH: Range: selected FlexLogic™ operands (see below)
SECURITY ACCESS On
REMOTE SETTING AUTH: Range: FlexLogic™ operand
MESSAGE
On
8 MESSAGE
ACCESS AUTH Range: 5 to 480 minutes in steps of 1
TIMEOUT: 30 min.
The dual permission security access feature provides a mechanism for customers to prevent unauthorized or unintended
upload of settings to a relay through the local or remote interfaces interface.
The following settings are available through the local (front panel) interface only.
• LOCAL SETTING AUTH: This setting is used for local (front panel or RS232 interface) setting access supervision.
Valid values for the FlexLogic™ operands are either “On” (default) or any physical “Contact Input ~~ On” value.
If this setting is “On“, then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing
the local setting password to gain setting access.
If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the UNAUTHORIZED ACCESS message is displayed on the front panel.
• REMOTE SETTING AUTH: This setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to pro-
viding the remote setting password to gain setting access.
• ACCESS AUTH TIMEOUT: This setting represents the timeout delay for local setting access. This setting is applicable
when the LOCAL SETTING AUTH setting is programmed to any operand except “On”. The state of the FlexLogic™ oper-
and is continuously monitored for an off-to-on transition. When this occurs, local access is permitted and the timer pro-
grammed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the time-
out is restarted. The status of this timer is updated every 5 seconds.
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product
Setup > Security menu item to display the security settings window.
The Remote Settings Authorization setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is pro-
vided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing the
remote setting password to gain setting access.
The Access Authorization Timeout setting represents the timeout delay remote setting access. This setting is applicable
when the Remote Settings Authorization setting is programmed to any operand except “On” or “Off”. The state of the
FlexLogic™ operand is continuously monitored for an off-to-on transition. When this occurs, remote setting access is per-
mitted and the timer programmed with the Access Authorization Timeout setting value is started. When this timer
expires, remote setting access is immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™
operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds.
Setting file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An exam-
ple of this is a substation that has ten similar feeders protected by ten UR-series F60 relays.
In these situations, typically 90% or greater of the settings are identical between all devices. The templates feature allows
engineers to configure and test these common settings, then lock them so they are not available to users. For example,
these locked down settings can be hidden from view for field engineers, allowing them to quickly identify and concentrate
on the specific settings.
The remaining settings (typically 10% or less) can be specified as editable and be made available to field engineers install-
ing the devices. These will be settings such as protection element pickup values and CT and VT ratios.
The settings template mode allows the user to define which settings will be visible in EnerVista UR Setup. Settings tem-
plates can be applied to both settings files (settings file templates) and online devices (online settings templates). The func-
tionality is identical for both purposes.
The settings template feature requires that both the EnerVista UR Setup software and the G60 firmware are at ver-
sions 5.40 or higher.
NOTE
The software will prompt for a template password. This password is required to use the template feature and must be
at least four characters in length.
8 3. Enter and re-enter the new password, then click OK to continue.
The online settings template is now enabled. The device is now in template editing mode.
By default, all settings are specified as locked and displayed against a grey background. The icon on the upper right of
the settings window will also indicate that EnerVista UR Setup is in EDIT mode. The following example shows the
phase time overcurrent settings window in edit mode.
The software will prompt for a template password. This password must be at least four characters in length.
8
Phase time overcurrent window with template applied via
the Template Mode > View In Template Mode command.
The template specifies that only the Pickup and Curve
Phase time overcurrent settings window without template applied.
settings be available.
842858A1.CDR
Figure 8–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND
Viewing the settings in template mode also modifies the settings tree, showing only the settings categories that contain
editable settings. The effect of applying the template to a typical settings tree view is shown below.
Typical settings tree view without template applied. Typical settings tree view with template applied via
the Template Mode > View In Template Mode
command.
842860A1.CDR
Figure 8–5: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE SETTINGS COMMAND
Use the following procedure to display settings available for editing and settings locked by the template.
1. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Apply the template by selecting the Template Mode > View All Settings option.
3. Enter the template password then click OK to apply the template.
Once the template has been applied, users will only be able to edit the settings specified by the template, but all settings
will be shown. The effect of applying the template to the phase time overcurrent settings is shown below.
Phase time overcurrent settings window without template applied. Phase time overcurrent window with template applied via
the Template Mode > View All Settings command.
8
The template specifies that only the Pickup and Curve
settings be available.
842859A1.CDR
Figure 8–6: APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COMMAND
4. Verify one more time that you wish to remove the template by clicking Yes.
The EnerVista software will remove all template information and all settings will be available.
The UR allows users to secure parts or all of a FlexLogic™ equation, preventing unauthorized viewing or modification of
critical FlexLogic™ applications. This is accomplished using the settings template feature to lock individual entries within
FlexLogic™ equations.
Secured FlexLogic™ equations will remain secure when files are sent to and retrieved from any UR-series device.
Once the template has been applied, users will only be able to view and edit the FlexLogic™ entries not locked by the tem-
plate. The effect of applying the template to the FlexLogic™ entries in the above procedure is shown below.
Typical FlexLogic™ entries without template applied. Typical FlexLogic™ entries locked with template via
the Template Mode > View In Template Mode command.
842861A1.CDR
8
Figure 8–9: SECURED FLEXLOGIC™ IN GRAPHICAL VIEW
A traceability feature for settings files allows the user to quickly determine if the settings in a G60 device have been
changed since the time of installation from a settings file. When a settings file is transfered to a G60 device, the date, time,
and serial number of the G60 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor-
mation can be compared with the G60 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the G60
device or obtained from the G60 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.
The serial number of the UR-series device and the file transfer
date are added to the settings file when settings files
are transferred to the device.
1. The transfer date of a setting file written to a G60 is logged in the relay and can be viewed via EnerVista UR Setup or
the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
2. Comparing the dates stored in the relay and on the settings file at any time in the future will indicate if any changes
have been made to the relay configuration since the settings file was saved.
842863A1.CDR
Traceability data
in settings report
842862A1.CDR
8
Figure 8–13: SETTINGS FILE REPORT SHOWING TRACEABILITY DATA
842865A1.CDR
The EnerVista security management system is a role-based access control (RBAC) system that allows a security adminis-
trator to easily manage the security privileges of multiple users. This allows for access control of URPlus-series devices by
multiple personnel within a substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The
EnerVista security management system is disabled by default to allow the administrator direct access to the EnerVista soft-
ware after installation. It is recommended that security be enabled before placing the device in service.
The EnerVista security management system is disabled by default. This allows access to the device immediately after
installation. When security is disabled, all users are granted administrator access.
1. Select the Security > User Management menu item to open the user management configuration window.
2. Check the Enable Security box in the lower-left corner to enable the security management system.
Security is now enabled for the EnerVista UR Setup software. It will now be necessary to enter a username and password
upon starting the software.
The following pre-requisites are required to add new users to the EnerVista security management system.
• The user adding the new user must have administrator rights.
• The EnerVista security management system must be enabled.
8
The following procedure describes how to add new users.
1. Select the Security > User Management menu item to open the user management configuration window.
2. Enter a username in the User field. The username must be between 4 and 20 characters in length.
3. Select the user access rights by checking one or more of the fields shown.
The following pre-requisites are required to modify user privileges in the EnerVista security management system.
8 • The user modifying the privileges must have administrator rights.
• The EnerVista security management system must be enabled.
The following procedure describes how to modify user privileges.
1. Select the Security > User Management menu item to open the user management configuration window.
2. Locate the username in the User field.
3. Modify the user access rights by checking or clearing one or more of the fields shown.
As a Wye-Delta transformer introduces discontinuity for the zero-sequence circuit, the ground distance protection cannot
be applied, except special circumstances, to respond to faults behind the transformer.
The phase distance elements, however, could be developed so that both accurate reach and correct fault phase identifica-
tion is retained for faults behind the power transformer as seen from the relaying point. Without appropriate compensation,
the relay's reach would depend on a type of fault, creating considerable difficulties in applying the relay.
The G60 provides for any location of the VTs and CTs with respect to the involved power transformer and the direction of
any given zone.
In the following equations, the VT and CT locations are referenced as “None” if the transformer is not present between the
CT/VT and the intended reach point. Otherwise, the location is to be selected as a type of a transformer as seen from the
VT/CT position towards the intended reach point. The following figure explains the adopted rules.
(a) (b)
delta wye, 330o lag delta wye, 330o lag
Z3 Z3
Z1 Z1
(c) (e)
delta wye, 330o lag
L1 L2
Z3 Zone 3
Zone 1
Z3 XFRM VOL CONNECTION = None
Z3 XFRM CUR CONNECTION = Yd1 ZL1 ZT ZL2
Z1
Figure 9–1: APPLICATIONS OF THE “PHS DIST XFMR VOL/CUR CONNECTION” SETTINGS
CA
3
9
1
I CA_21P = ------- ( I B + I C – 2I A ) V CA_21P = – 3V A
3
Equations from the “Current Transformation” and “Voltage Transformation” columns are used to derive inputs to the three
(AB, BC, and CA) phase distance elements. For example, if the CTs are located at the delta side of the Delta-Wye 11 trans-
former, and a given zone is set to look through the transformer into the system connected to the Wye winding, the CT loca-
tion setting for that zone shall be set to Dy11 and the relay would use – 3I B instead of a traditional I A – I B for the AB
phase distance element.
The current supervision pickup setting applies to the currents specified in the “Current Transformation” columns.
A distance zone originates at the location of the VTs (regardless of the location of the CTs). For more information on set-
tings please refer to Chapter 9: Application of Settings.
9.1.2 EXAMPLE
H X
VT = 13.8kV/120V VT = 315kV/120V
CT = 8000:5 CT = 300:5
0.688Ω∠85°
2.57Ω∠88.4°
837727A2.CDR
If installed at the location X, the relay would use the following input signals for its phase AB distance element:
V = VAB = 77.402 kV ∠57.5° primary or 29.49 V ∠57.5° secondary
I = IA – IB = 2.576 kA ∠–27.6° primary or 42.93 A ∠–27.6° secondary
9 And consequently it would see an apparent impedance of:
Zapp = V / I = 30.05 Ω ∠85° primary or 0.687 Ω ∠85° secondary
Consequently, the following signals are applied to the phase AB distance element:
1
V = ------- V AB – V BC = 10.861 kV ∠59.9° primary or 94.45 V ∠59.9° secondary (EQ 9.1)
3
Thus, 0.127 Ω ∠90° + 0.05779 Ω ∠85° = 0.1847 Ω ∠88.4° primary side or 2.569 Ω ∠88.4° on the secondary side.
The above example illustrates how the relay maintains correct reach for fault behind power transformers. When installed at
X, the relay shall be set to 0.687 Ω ∠85° secondary in order to reach to the fault shown in the figure. When installed at H,
the relay shall be set to 2.569 Ω ∠88.4° to ensure exactly same coverage.
See Chapter 9: Application of Settings for more information on setting calculations.
This section provides an example of the settings required for an example system configuration. Consider the generator pro-
tection system shown below:
GENERATOR:
211.765 MVA, 18 kV, ABC GSU: TX LINE:
x’d = 0.216 pu 200 MVA 138 kV
xd = 1.967 pu 18 : 138 kV Z1 = 15 + j75 ohm
2
I2T capability = 10 X1 = 10%
I2 capability = 8%
Motoring Power = 22000 kW X2
H2
X1 H0
X3 H1 H3
8000 : 5 A 8000 : 5 A X1 H1
A
A
B X2 H2 Power
52G 52 B
C X3 H3 system
C
H0
18900 : 120 V
12000 : 240 V
Yd1
R
M1a
M1b
M2a
M2b
M3a
M3b
M4a
M4b
M1c
M2c
M3c
M4c
F5a
F6a
F7a
F8a
F1a
F1b
F2a
F2b
F3a
F3b
F4a
F4b
F5c
F6c
F7c
F8c
F1c
F2c
F3c
F4c
VX
VB
VC
VA
VX
IG5
IG1
VB
VC
IG
IG5
IG1
VA
IG
IA5
IA1
IB
IC
IA
IC5
IC1
IA5
IA1
IB5
IB1
IB
IC
IA
IC5
IC1
IB5
IB1
“+”
830712A7.CDR
Ideally, the CTs should be selected so the generator nominal current is 80 to 85% of CT primary. The following settings are
entered for the example system. The M5 bank and the ground CT input on each of the groups are unused in this example.
The nominal current is given by:
6
S nom 212 × 10 VA - = 6800 A
I nom = --------------------
- = ----------------------------------------- (EQ 10.1)
3
3V nom 3 × 18 × 10 V
Make the following settings changes in EnerVista UR Setup (or alternately, via the front panel through the SYSTEM SETUP Ö
AC INPUTS Ö CURRENT BANK F1 and the SYSTEM SETUP Ö AC INPUTS ÖØ CURRENT BANK M1 menus).
10
For the example system, the voltage settings are calculated as follows:
18000 V- ---------------------
120 V -
PHASE VT SECONDARY = --------------------- × = 66 V (EQ 10.2)
3 18900 V
18900 V- = 157.5
PHASE VT RATIO = --------------------- (EQ 10.3)
120 V
12000 V
NEUTRAL VT RATIO = ---------------------- = 50 (EQ 10.4)
240 V
Enter the following values through EnerVista UR Setup (or alternately, through the front panel SETTINGS ÖØ SYSTEM SETUP
Ö AC INPUTS ÖØ VOLTAGE BANK F5 Ö menu):
Frequency tracking should always be enabled for generator applications. Make the following power system parameters
changes via EnerVista UR Setup or through the SETTINGS ÖØ SYSTEM SETUP ÖØ POWER SYSTEM ÖØ VOLTAGE BANK F5 Ö
menu:
Two sources are required for this application example. The “LINE” source uses the phase and auxiliary VT inputs and the
CT input wired to the generator output CT. The “NEUTRL” source uses the phase VT inputs and the CT input wired to the
generator neutral CT. Including the phase VT inputs for both sources allows the user to choose the location of elements that
use both voltage and current. Elements using the auxiliary VT input are assigned to the “NEUTRL” source.
Make the following changes through EnerVista UR Setup or through the SETTINGS ÖØ SYSTEM SETUP ÖØ SOURCE 1 and
the SETTINGS ÖØ SYSTEM SETUP ÖØ SOURCE 2 menus:
10
The “LINE” and “NEUTRL” sources are both required for the stator differential element. The minimum pickup can usually be
set as low as 0.05 pu (corresponding to 0.25 A secondary or 400 A primary in this example). Set the STATOR DIFF SLOPE 1
setting to accommodate for CT errors; a setting of 10% is adequate in most instances. Set the STATOR DIFF SLOPE 2 setting
to accommodate for errors due to CT saturation; a setting of 80% is recommended for most applications. The STATOR DIFF
BREAK 1 setting must be greater than the maximum load expected for the machine. The STATOR DIFF BREAK 2 setting should
be set at the level where CT saturation is expected to occur.
Make the following parameter changes in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS ÖØ SET-
TING GROUP 1 ÖØ STATOR DIFFERENTIAL Ö menu:
Stage 1 of the generator unbalance element is typically used to trip the generator. In this example, the I2 capability of the
machine is 8% and the I22T capability is 10. The generator nominal current is:
I nom primary
- = 6800 A- = 0.85 pu
I nom ( pu ) = -------------------------------- ------------------ (EQ 10.5)
CT primary 8000 A
The minimum operate time of stage 1 will be set to 0.25 seconds, the maximum operating time will be 10 minutes, and the
reset time will be set to 4 minutes.
Stage 2 is typically set lower than stage 1 with a time delay to prevent nuisance alarms for external faults that are normally
cleared by system protection. For the application example, the pickup setting is:
Pickup = 70% × I 2 capability = 0.70 × 8% = 5.6% (EQ 10.6)
Source 2 will be chosen for this element. The settings are as follows:
10
Z b ( sec ) + X d ′(sec)
- = 15.54Ω + 3.36Ω- = 9.45 Ω
CENTER 1 = ------------------------------------------------ ------------------------------------------ (EQ 10.10)
2 2
Z b ( sec ) Ω- = 7.77 Ω
RADIUS 1 = -------------------- = 15.54
--------------------- (EQ 10.11)
2 2
X d ( sec ) Ω- = 15.28 Ω
- = 30.57
RADIUS 2 = -------------------- --------------------- (EQ 10.14)
2 2
The voltage supervision setting will be determined by a system study and may be disabled on either element if required. VT
fuse failure should supervise this element.
The choice of source is not critical for this application. The NEUTRL source is chosen for the following setting changes.
Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP
1 ÖØ LOSS OF EXCITATION menu:
The reverse power element should be set at ½ the rated motoring power. The pickup is calculated as follows:
1 Rated Motoring Power (primary watts)
S min = --- × -------------------------------------------------------------------------------------------------------------------------------------------------------------------------- (EQ 10.15)
2 3 × Phase CT Primary × Phase VT Ratio × Phase VT Secondary
6
1 22 × 10 W
For the example system: S min = --- × --------------------------------------------------------------------- = 0.044 pu
2 3 × 8000 A × 157.5 × 66 V
10
To prevent maloperation for power swings the element is typically time delayed by 20 to 30 seconds. For sequential tripping
applications the time delay will be 2 to 3 seconds. The element may be blocked when the generator is offline. The line
source will be used for this application. Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ
GROUPED ELEMENTS ÖØ SETTING GROUP 1 ÖØ SENSITIVE DIRECTIONAL POWER Ö DIRECTIONAL POWER 1 menu:
56 AND(2)
System backup protection is implemented using a phase time overcurrent element with voltage restraint enabled. The
NEUTRL source will be chosen for this element. The pickup of this element should be set at a safe margin above the max-
imum load expected on the machine.
Generator Nominal Current 6800
PICKUP = 1.5 × ------------------------------------------------------------------------ = 1.5 × ------------- = 1.275 pu (EQ 10.16)
CT Primary 8000
The selection of all standard curves (and FlexCurves™) is allowed for easy coordination with system relaying. For the
example system, an IEEE extremely inverse curve will be used and a setting will be chosen such that the operate time for a
three phase fault on the high side of the transformer is 0.75 seconds. For simplicity, the power system contribution is not
considered.
211.765
Transformer Impedance = 0.10 × --------------------- = 0.106 pu on machine base (EQ 10.17)
200
1 6800
Fault Current = V
---- = --------------- × ------------- = 2.64 pu (EQ 10.19)
X 0.322 8000
A -+B
--------------------------------------------------------------------------------------
T = TDM × ⎛ --------------------------------------------------------------------
⎝ I pickup × Pickup Reduction⎠
I p
-⎞ – 1 (EQ 10.22) 10
Since this element will coordinate with system protections a timed reset is chosen. The element must be blocked for a VT
fuse failure. The neutral source will be chosen. Make the following changes in EnerVista UR Setup or through the SETTINGS
ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP 1 ÖØ PHASE CURRENT Ö PHASE TOC1 menu:
This function provides time-delayed protection for system faults that have not been cleared by system protections and to
provide backup protection for stator faults.
The “Line” source will be used in this example to permit the application of a forward and reverse zone. The memory dura-
tion will be left at the default setting (10 cycles).
Zone 1 will look forward and cover the GSU and the transmission line leaving the station. Zone 3 will look in the reverse
direction and cover the stator winding. Zone 2 will not be used in this example. Both the VTs and the CTs are located on the
low voltage side of the GSU. The transformer vector diagram (see figure 9-1) shows this transformer to be Yd1. Conse-
quently, due to the location of instrument transformers, Dy11 is chosen for both the XFMR VOL CONNECTION and XFMR CUR
CONNECTION settings. There are no transformers in the reverse direction. Therefore “None” is chosen for both of the zone 3
transformer connection settings. The reach of the zone 1 element will be set at 120% of impedance of the GSU and the
transmission line. In the instance that there are multiple lines and/or multiple generators, the zone 1 reach must be
increased to compensate for the infeed effect.
2 2
VL ( 18 )
Transformer impedance = X T × --------------- = j0.1 × -------------- = j0.162 primary ohms (EQ 10.24)
MVA T 200
2 2
VL ( 18 )
Line impedance = X L × ------2- = ( 15 + j75 ) × ----------------2- = 0.255 + j1.276 primary ohms (EQ 10.25)
VH ( 138 )
CT ratio
Zone 1 reach = 1.2 × ( Transformer impedance + Line impedance ) × ---------------------
VT ratio
(EQ 10.26)
1600
= 1.2 × ( j0.162 + 0.255 + j1.276 ) × --------------- = 17.8 ∠80° secondary ohms
157.5
10
The zone 3 reach will be set at 120% of the generator transient reactance. The time delay of this element should be com-
pared to the generator decrement curve to verify the adequacy of this setting.
2 2
VL ( 18 )
Generator impedance = X d × ---------------- = j1.967 × -------------- = j3.01 primary ohms (EQ 10.27)
MVA G 211
CT ratio
Zone 3 reach = 1.2 × Generator impedance × ---------------------
VT ratio
(EQ 10.28)
1600
= 1.2 × j3.01 × --------------- = j36.68 secondary ohms
157.5
An mho shape has been chosen for this example. Therefore, the quadrilateral settings are left at their default values. Make
the following changes in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP 1 ÖØ
DISTANCE Ö PHASE DISTANCE Z1(3) menus:
a) AUXILIARY OVERVOLTAGE
Stator ground fault protection is implemented with an overvoltage element connected at the generator neutral resistor. The
auxiliary overvoltage element will be used in this example. The auxiliary voltage input has previously been assigned to the
NEUTRL source. In this example the element will be set to protect 97% of the stator against ground faults.
10
The time delay should be longer than the longest normal clearing time for faults outside the generator zone. If the phase
VTs are wye-connected then this element should also be coordinated with VT secondary fuses to prevent false operations
for VT secondary ground faults. For the sample system a time delay of 1 second will be used. Make the following changes
in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1 ÖØ VOLTAGE ELEMENTS ÖØ
AUXILIARY OV1 menu:
10
Third harmonic
neutral voltage
Megawatts
830733A1.CDR
10
10.1.12 OVEREXCITATION
This protection should be set to coordinate with the manufacturers excitation capability curves. For example system, the
combined generator/GSU limit curve is shown below:
Time (seconds)
830734A1.CDR
10
10.1.13 INPUTS/OUTPUTS
The following inputs and outputs will be used in this example. Make the following changes in EnerVista UR Setup or
through the SETTINGS ÖØ INPUTS/OUTPUTS Ö CONTACT INPUTS Ö CONTACT INPUT H7a(H7c) menus:
Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ VIRTUAL OUTPUTS Ö
VIRTUAL OUTPUT 1(4) menus:
Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUTS Ö
CONTACT OUTPUT H1(H4) menus:
10
10.1.14 FREQUENCY
The pickup and delay settings are dependent on operating practices and system characteristics. In this example, two over-
frequency and two underfrequency elements will be used. The elements will be blocked when offline. Underfrequency will
initiate a trip. Overfrequency will alarm only. Either source may be assigned.
Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ CONTROL ELEMENTS ÖØ UNDERFRE-
QUENCY Ö UNDERFREQUENCY 1(2) and the SETTINGS ÖØ CONTROL ELEMENTS ÖØ OVERFREQUENCY Ö OVERFREQUENCY 1(2)
menus:
In this example, the ACCDNT ENRG ARMING MODE is selected as “UV and Offline”. The ACCDNT ENRG OC PICKUP setting
should be set at ½ the minimum expected fault current. In this case, 1.0 pu (8000 A primary) is selected. In cases where it
is possible to re-energize the machine through its auxiliary transformer, a lower setting may be required. The undervoltage
pickup setting must be set above the maximum expected fault voltage.
Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP
1 ÖØ ACCIDENTAL ENERGIZATION menu:
10
10.1.16 FLEXLOGIC™
The following logic as given as an example only. The logic for each specific application will be dependant on system design,
protection philosophies, and operating practices.
5 sec.
1 SEQ TRIP ON (VO9) 33 VOLTS PER HERTZ 1 PKP
0 sec.
8 UNDERFREQ ON (VO5)
9 AUX OV1 OP
40 UNDERFREQ 1 OP
OR(2) = UNDERFREQ (VO5)
10 STATOR GND STG1 OP
41 UNDERFREQ 2 OP
11 ACCDNT ENRG OP
42 OR(2)
12 OR(11)
43 = UNDERFREQ (VO5)
44 OVERFREQ 1 OP
14 SEQ TRIP ON (VO9) OR(2) = OVERFREQ (VO6)
45 OVERFREQ 2 OP
15 STATOR DIFF OP
46 OR(2)
16 LOSS EXCIT OP
47 = OVERFREQ (VO6)
17 DIR POWER STG1 OP OR(7) = FLD BKR TRIP (VO2)
18 OVEREXCIT ON (VO7)
48 VOLTS PER HERTZ 1 OP
19 AUX OV1 OP OR(2) = OVEREXCIT (VO7)
49 VOLTS PER HERTZ 2 OP
20 STATOR GND STG1 OP
50 OR(2)
21 OR(7)
51 = OVEREXCIT (VO7)
22 = FLD BKR TRIP (VO2)
23 STATOR DIFF OP
53 = ONLINE (VO8)
24 LOSS EXCIT OP
10
a) APPLICATION DESCRIPTION
Phase distance elements of the G60 could be set to respond to faults beyond any three-phase power transformer. The
relay guarantees accurate reach and targeting for any phase fault. Moreover, the current and voltage transformers may be
located independently on different sides of the transformer.
The following setting rules apply to this feature:
1. A given distance zone is terminated by location of the VTs, not the CTs.
2. Consequently, the positive-sequence impedance of a transformer must be included in the reach setting only if the
transformer is located between the potential source and the intended reach point.
3. The current signals require compensation if the transformer is located between the CTs and the intended reach point.
If this is the case the CT connection setting shall be set to transformer connection and vector group as seen from the
CTs toward the reach point. Otherwise, the CT connection setting shall be set to "None".
4. The voltage signals require compensation if the transformer is located between the VTs and the intended reach point.
If this is the case the VT connection setting shall be set to transformer connection and vector group as seen from the
VTs toward the reach point. Otherwise, the VT connection setting shall be set to "None".
5. The reach setting is entered in secondary ohms and as such must take into account location and ratios of VTs and CTs
as well as voltage ratio of the involved power transformer.
The following equations explain the setting rules. Consider two applications as shown in the figure below:
(a)
ZH ZT ZX
H X
Z3 Z1
(b)
ZH ZT ZX
H X
Z3 Z1
830718A1.CDR
10.2.2 EXAMPLE
Given the following for the system shown in the previous section:
ZX = 30 Ω ∠85° (intended reach of Zone 1)
ZH = 0.06 Ω ∠88° (intended reach of Zone 3)
nCT = 8000:5 = 1600 (located at H)
nVT = 315000:120 = 2625 (located at X)
Transformer: 13.8/315 kV, 150 MVA, 10%, delta/wye, 315 kV side lagging 30°
Transformer impedance:
2
10 ( 13.8 )
Z T ( at H ) = ---------- × ------------------- = 0.127Ω ∠90° (EQ 10.38)
100 150
The Zone 1 settings are:
13.8 1600
Z 1 = 30 × ----------- × ------------- = 0.8011Ω ∠85° (EQ 10.39)
315 2625
PHS DIST Z1 REACH: "0.80"
PHS DIST Z1 RCA: "85"
PHS DIST Z1 XMFR VOL CONNECTION: "None"
PHS DIST Z1 XMFR CUR CONNECTION: "Dy1" 10
10
Underfreqency and overfrequency protection requires techniques with subtle testing implications. Whereas most protection
11
is designed to detect changes from normal to fault conditions that occur virtually instantaneously, power system inertia
requires frequency protection to pickup while the frequency is changing slowly. Frequency measurement is inherently sen-
sitive to noise, making high precision in combination with high speed challenging for both relays and test equipment.
Injection to a particular G60 frequency element must be to its configured source and to the channels the source uses for
frequency measurement. For frequency measurement, a source will use the first quantity configured in the following order:
1. Phase voltages.
2. Auxiliary voltage.
3. Phase currents.
4. Ground current.
For example, if only auxiliary voltage and phase currents are configured, the source will use the auxiliary voltage, not the
phase voltages or any of the currents.
When phase voltages or phase currents are used, the source applies a filter that rejects the zero-sequence component. As
such, the same signal must not be injected to all three phases, or the injected signal will be completely filtered out. For an
underfrequency element using phase quantities, the phase A signal must be above the MIN VOLT/AMP setting value. There-
fore, either inject into phase A only, or inject a balanced three-phase signal.
Frequency
Injection frequency
Source frequency
Tracking frequency
Pickup
frequency
Time
Underfrequency element detection time
The desired delay time is the interval from the point the frequency crosses the set threshold to the point the element oper-
ates. Some test sets can measure only the time from the ramp start to element operation, necessitating the subtraction of
11 the pre-threshold ramp time from the reading. For example, with a ramp rate of 0.20 Hz/s, start the ramp 0.20 Hz before the
threshold and subtract 1 second from test set time reading of ramp start to relay operation.
Note that the G60 event records only show the “pickup delay” component, a definite time timer. This is exclusive of the time
taken by the frequency responding component to pickup.
The G60 oscillography can be used to measure the time between the calculated source frequency crossing the threshold
and element operation; however, this method omits the delay in the calculated source frequency. The security features of
the source frequency measurement algorithm result in the calculated frequency being delayed by 2 to 4 cycles (or longer
with noise on the input). In addition, oscillography resolution is 0.004 Hz, which at 0.20 Hz/s corresponds to a delay of
20 ms. The tracking frequency should not be used in timing measurements, as its algorithm involves phase locking, which
purposely sets its frequency high or low to allow the G60 sample clock to catch-up or wait as necessary to reach synchro-
nism with the power system.
A
Table A–1: FLEXANALOG DATA ITEMS (Sheet 1 of 23)
ADDRESS FLEXANALOG NAME UNITS DESCRIPTION
5728 Stator Diff Iad Amps Stator differential phase A current (Iad)
5730 Stator Rest Iar Amps Stator restraint phase A current (Iar)
5732 Stator Diff Ibd Amps Stator differential phase B current (Ibd)
5734 Stator Rest Ibr Amps Stator restraint phase B current (Ibr)
5736 Stator Diff Icd Amps Stator differential phase C current (Icd)
5738 Stator Rest Icr Amps Stator restraint phase C current (Icr)
5744 Stator Gnd Vn 3rd Volts Stator ground Vn third harmonic voltage
5746 Stator Gnd Vn+V0 3rd Volts Stator ground Vn+V0 third harmonic voltage
5748 Stator Gnd V0 3rd Volts Stator ground V0 third harmonic voltage
5760 Sns Dir Power 1 Watts Sensitive directional power 1 actual value
5762 Sns Dir Power 2 Watts Sensitive directional power 2 actual value
5792 RGF 1 Igd Mag Amps Restricted ground fault 1 differential ground current magnitude
5794 RGF 1 Igr Mag Amps Restricted ground fault 1 restricted ground current magnitude
5796 RGF 2 Igd Mag Amps Restricted ground fault 2 differential ground current magnitude
5798 RGF 2 Igr Mag Amps Restricted ground fault 2 restricted ground current magnitude
5800 RGF 3 Igd Mag Amps Restricted ground fault 3 differential ground current magnitude
5802 RGF 3 Igr Mag Amps Restricted ground fault 3 restricted ground current magnitude
5804 RGF 4 Igd Mag Amps Restricted ground fault 4 differential ground current magnitude
5806 RGF 4 Igr Mag Amps Restricted ground fault 4 restricted ground current magnitude
5808 RGF 5 Igd Mag Amps Restricted ground fault 5 differential ground current magnitude
5810 RGF 5 Igr Mag Amps Restricted ground fault 5 restricted ground current magnitude
5812 RGF 6 Igd Mag Amps Restricted ground fault 6 differential ground current magnitude
5814 RGF 6 Igr Mag Amps Restricted ground fault 6 restricted ground current magnitude
5856 Freq Rate 1 Value Hz/s Frequency rate of change 1 actual value
5860 Freq Rate 2 Value Hz/s Frequency rate of change 2 actual value
5864 Freq Rate 3 Value Hz/s Frequency rate of change 3 actual value
5868 Freq Rate 4 Value Hz/s Frequency rate of change 4 actual value
6144 SRC 1 Ia RMS Amps Source 1 phase A current RMS
6146 SRC 1 Ib RMS Amps Source 1 phase B current RMS
6148 SRC 1 Ic RMS Amps Source 1 phase C current RMS
6150 SRC 1 In RMS Amps Source 1 neutral current RMS
6152 SRC 1 Ia Mag Amps Source 1 phase A current magnitude
6154 SRC 1 Ia Angle Degrees Source 1 phase A current angle
6155 SRC 1 Ib Mag Amps Source 1 phase B current magnitude
6157 SRC 1 Ib Angle Degrees Source 1 phase B current angle
6158 SRC 1 Ic Mag Amps Source 1 phase C current magnitude
6160 SRC 1 Ic Angle Degrees Source 1 phase C current angle
6161 SRC 1 In Mag Amps Source 1 neutral current magnitude
6163 SRC 1 In Angle Degrees Source 1 neutral current angle
6164 SRC 1 Ig RMS Amps Source 1 ground current RMS
6166 SRC 1 Ig Mag Degrees Source 1 ground current magnitude
6168 SRC 1 Ig Angle Amps Source 1 ground current angle
6169 SRC 1 I_0 Mag Degrees Source 1 zero-sequence current magnitude
6171 SRC 1 I_0 Angle Amps Source 1 zero-sequence current angle
6172 SRC 1 I_1 Mag Degrees Source 1 positive-sequence current magnitude
A ADDRESS
6174
FLEXANALOG NAME
SRC 1 I_1 Angle
UNITS
Amps
DESCRIPTION
Source 1 positive-sequence current angle
6175 SRC 1 I_2 Mag Degrees Source 1 negative-sequence current magnitude
6177 SRC 1 I_2 Angle Amps Source 1 negative-sequence current angle
6178 SRC 1 Igd Mag Degrees Source 1 differential ground current magnitude
6180 SRC 1 Igd Angle Amps Source 1 differential ground current angle
6208 SRC 2 Ia RMS Amps Source 2 phase A current RMS
6210 SRC 2 Ib RMS Amps Source 2 phase B current RMS
6212 SRC 2 Ic RMS Amps Source 2 phase C current RMS
6214 SRC 2 In RMS Amps Source 2 neutral current RMS
6216 SRC 2 Ia Mag Amps Source 2 phase A current magnitude
6218 SRC 2 Ia Angle Degrees Source 2 phase A current angle
6219 SRC 2 Ib Mag Amps Source 2 phase B current magnitude
6221 SRC 2 Ib Angle Degrees Source 2 phase B current angle
6222 SRC 2 Ic Mag Amps Source 2 phase C current magnitude
6224 SRC 2 Ic Angle Degrees Source 2 phase C current angle
6225 SRC 2 In Mag Amps Source 2 neutral current magnitude
6227 SRC 2 In Angle Degrees Source 2 neutral current angle
6228 SRC 2 Ig RMS Amps Source 2 ground current RMS
6230 SRC 2 Ig Mag Degrees Source 2 ground current magnitude
6232 SRC 2 Ig Angle Amps Source 2 ground current angle
6233 SRC 2 I_0 Mag Degrees Source 2 zero-sequence current magnitude
6235 SRC 2 I_0 Angle Amps Source 2 zero-sequence current angle
6236 SRC 2 I_1 Mag Degrees Source 2 positive-sequence current magnitude
6238 SRC 2 I_1 Angle Amps Source 2 positive-sequence current angle
6239 SRC 2 I_2 Mag Degrees Source 2 negative-sequence current magnitude
6241 SRC 2 I_2 Angle Amps Source 2 negative-sequence current angle
6242 SRC 2 Igd Mag Degrees Source 2 differential ground current magnitude
6244 SRC 2 Igd Angle Amps Source 2 differential ground current angle
6272 SRC 3 Ia RMS Amps Source 3 phase A current RMS
6274 SRC 3 Ib RMS Amps Source 3 phase B current RMS
6276 SRC 3 Ic RMS Amps Source 3 phase C current RMS
6278 SRC 3 In RMS Amps Source 3 neutral current RMS
6280 SRC 3 Ia Mag Amps Source 3 phase A current magnitude
6282 SRC 3 Ia Angle Degrees Source 3 phase A current angle
6283 SRC 3 Ib Mag Amps Source 3 phase B current magnitude
6285 SRC 3 Ib Angle Degrees Source 3 phase B current angle
6286 SRC 3 Ic Mag Amps Source 3 phase C current magnitude
6288 SRC 3 Ic Angle Degrees Source 3 phase C current angle
6289 SRC 3 In Mag Amps Source 3 neutral current magnitude
6291 SRC 3 In Angle Degrees Source 3 neutral current angle
6292 SRC 3 Ig RMS Amps Source 3 ground current RMS
6294 SRC 3 Ig Mag Degrees Source 3 ground current magnitude
6296 SRC 3 Ig Angle Amps Source 3 ground current angle
6297 SRC 3 I_0 Mag Degrees Source 3 zero-sequence current magnitude
6299 SRC 3 I_0 Angle Amps Source 3 zero-sequence current angle
6300 SRC 3 I_1 Mag Degrees Source 3 positive-sequence current magnitude
6302 SRC 3 I_1 Angle Amps Source 3 positive-sequence current angle
A ADDRESS
6690
FLEXANALOG NAME
SRC 1 Vx Angle
UNITS
Degrees
DESCRIPTION
Source 1 auxiliary voltage angle
6691 SRC 1 V_0 Mag Volts Source 1 zero-sequence voltage magnitude
6693 SRC 1 V_0 Angle Degrees Source 1 zero-sequence voltage angle
6694 SRC 1 V_1 Mag Volts Source 1 positive-sequence voltage magnitude
6696 SRC 1 V_1 Angle Degrees Source 1 positive-sequence voltage angle
6697 SRC 1 V_2 Mag Volts Source 1 negative-sequence voltage magnitude
6699 SRC 1 V_2 Angle Degrees Source 1 negative-sequence voltage angle
6720 SRC 2 Vag RMS Volts Source 2 phase AG voltage RMS
6722 SRC 2 Vbg RMS Volts Source 2 phase BG voltage RMS
6724 SRC 2 Vcg RMS Volts Source 2 phase CG voltage RMS
6726 SRC 2 Vag Mag Volts Source 2 phase AG voltage magnitude
6728 SRC 2 Vag Angle Degrees Source 2 phase AG voltage angle
6729 SRC 2 Vbg Mag Volts Source 2 phase BG voltage magnitude
6731 SRC 2 Vbg Angle Degrees Source 2 phase BG voltage angle
6732 SRC 2 Vcg Mag Volts Source 2 phase CG voltage magnitude
6734 SRC 2 Vcg Angle Degrees Source 2 phase CG voltage angle
6735 SRC 2 Vab RMS Volts Source 2 phase AB voltage RMS
6737 SRC 2 Vbc RMS Volts Source 2 phase BC voltage RMS
6739 SRC 2 Vca RMS Volts Source 2 phase CA voltage RMS
6741 SRC 2 Vab Mag Volts Source 2 phase AB voltage magnitude
6743 SRC 2 Vab Angle Degrees Source 2 phase AB voltage angle
6744 SRC 2 Vbc Mag Volts Source 2 phase BC voltage magnitude
6746 SRC 2 Vbc Angle Degrees Source 2 phase BC voltage angle
6747 SRC 2 Vca Mag Volts Source 2 phase CA voltage magnitude
6749 SRC 2 Vca Angle Degrees Source 2 phase CA voltage angle
6750 SRC 2 Vx RMS Volts Source 2 auxiliary voltage RMS
6752 SRC 2 Vx Mag Volts Source 2 auxiliary voltage magnitude
6754 SRC 2 Vx Angle Degrees Source 2 auxiliary voltage angle
6755 SRC 2 V_0 Mag Volts Source 2 zero-sequence voltage magnitude
6757 SRC 2 V_0 Angle Degrees Source 2 zero-sequence voltage angle
6758 SRC 2 V_1 Mag Volts Source 2 positive-sequence voltage magnitude
6760 SRC 2 V_1 Angle Degrees Source 2 positive-sequence voltage angle
6761 SRC 2 V_2 Mag Volts Source 2 negative-sequence voltage magnitude
6763 SRC 2 V_2 Angle Degrees Source 2 negative-sequence voltage angle
6784 SRC 3 Vag RMS Volts Source 3 phase AG voltage RMS
6786 SRC 3 Vbg RMS Volts Source 3 phase BG voltage RMS
6788 SRC 3 Vcg RMS Volts Source 3 phase CG voltage RMS
6790 SRC 3 Vag Mag Volts Source 3 phase AG voltage magnitude
6792 SRC 3 Vag Angle Degrees Source 3 phase AG voltage angle
6793 SRC 3 Vbg Mag Volts Source 3 phase BG voltage magnitude
6795 SRC 3 Vbg Angle Degrees Source 3 phase BG voltage angle
6796 SRC 3 Vcg Mag Volts Source 3 phase CG voltage magnitude
6798 SRC 3 Vcg Angle Degrees Source 3 phase CG voltage angle
6799 SRC 3 Vab RMS Volts Source 3 phase AB voltage RMS
6801 SRC 3 Vbc RMS Volts Source 3 phase BC voltage RMS
6803 SRC 3 Vca RMS Volts Source 3 phase CA voltage RMS
6805 SRC 3 Vab Mag Volts Source 3 phase AB voltage magnitude
A ADDRESS
7180
FLEXANALOG NAME
SRC 1 Qb
UNITS
Vars
DESCRIPTION
Source 1 phase B reactive power
7182 SRC 1 Qc Vars Source 1 phase C reactive power
7184 SRC 1 S VA Source 1 three-phase apparent power
7186 SRC 1 Sa VA Source 1 phase A apparent power
7188 SRC 1 Sb VA Source 1 phase B apparent power
7190 SRC 1 Sc VA Source 1 phase C apparent power
7192 SRC 1 PF --- Source 1 three-phase power factor
7193 SRC 1 Phase A PF --- Source 1 phase A power factor
7194 SRC 1 Phase B PF --- Source 1 phase B power factor
7195 SRC 1 Phase C PF --- Source 1 phase C power factor
7200 SRC 2 P Watts Source 2 three-phase real power
7202 SRC 2 Pa Watts Source 2 phase A real power
7204 SRC 2 Pb Watts Source 2 phase B real power
7206 SRC 2 Pc Watts Source 2 phase C real power
7208 SRC 2 Q Vars Source 2 three-phase reactive power
7210 SRC 2 Qa Vars Source 2 phase A reactive power
7212 SRC 2 Qb Vars Source 2 phase B reactive power
7214 SRC 2 Qc Vars Source 2 phase C reactive power
7216 SRC 2 S VA Source 2 three-phase apparent power
7218 SRC 2 Sa VA Source 2 phase A apparent power
7220 SRC 2 Sb VA Source 2 phase B apparent power
7222 SRC 2 Sc VA Source 2 phase C apparent power
7224 SRC 2 PF --- Source 2 three-phase power factor
7225 SRC 2 Phase A PF --- Source 2 phase A power factor
7226 SRC 2 Phase B PF --- Source 2 phase B power factor
7227 SRC 2 Phase C PF --- Source 2 phase C power factor
7232 SRC 3 P Watts Source 3 three-phase real power
7234 SRC 3 Pa Watts Source 3 phase A real power
7236 SRC 3 Pb Watts Source 3 phase B real power
7238 SRC 3 Pc Watts Source 3 phase C real power
7240 SRC 3 Q Vars Source 3 three-phase reactive power
7242 SRC 3 Qa Vars Source 3 phase A reactive power
7244 SRC 3 Qb Vars Source 3 phase B reactive power
7246 SRC 3 Qc Vars Source 3 phase C reactive power
7248 SRC 3 S VA Source 3 three-phase apparent power
7250 SRC 3 Sa VA Source 3 phase A apparent power
7252 SRC 3 Sb VA Source 3 phase B apparent power
7254 SRC 3 Sc VA Source 3 phase C apparent power
7256 SRC 3 PF --- Source 3 three-phase power factor
7257 SRC 3 Phase A PF --- Source 3 phase A power factor
7258 SRC 3 Phase B PF --- Source 3 phase B power factor
7259 SRC 3 Phase C PF --- Source 3 phase C power factor
7264 SRC 4 P Watts Source 4 three-phase real power
7266 SRC 4 Pa Watts Source 4 phase A real power
7268 SRC 4 Pb Watts Source 4 phase B real power
7270 SRC 4 Pc Watts Source 4 phase C real power
7272 SRC 4 Q Vars Source 4 three-phase reactive power
A ADDRESS
8096
FLEXANALOG NAME
SRC 1 Vb Harm[6]
UNITS
Volts
DESCRIPTION
Source 1 phase B voltage eighth harmonic
8097 SRC 1 Vb Harm[7] Volts Source 1 phase B voltage ninth harmonic
8098 SRC 1 Vb Harm[8] Volts Source 1 phase B voltage tenth harmonic
8099 SRC 1 Vb Harm[9] Volts Source 1 phase B voltage eleventh harmonic
8100 SRC 1 Vb Harm[10] Volts Source 1 phase B voltage twelfth harmonic
8101 SRC 1 Vb Harm[11] Volts Source 1 phase B voltage thirteenth harmonic
8102 SRC 1 Vb Harm[12] Volts Source 1 phase B voltage fourteenth harmonic
8103 SRC 1 Vb Harm[13] Volts Source 1 phase B voltage fifteenth harmonic
8104 SRC 1 Vb Harm[14] Volts Source 1 phase B voltage sixteenth harmonic
8105 SRC 1 Vb Harm[15] Volts Source 1 phase B voltage seventeenth harmonic
8106 SRC 1 Vb Harm[16] Volts Source 1 phase B voltage eighteenth harmonic
8107 SRC 1 Vb Harm[17] Volts Source 1 phase B voltage nineteenth harmonic
8108 SRC 1 Vb Harm[18] Volts Source 1 phase B voltage twentieth harmonic
8109 SRC 1 Vb Harm[19] Volts Source 1 phase B voltage twenty-first harmonic
8110 SRC 1 Vb Harm[20] Volts Source 1 phase B voltage twenty-second harmonic
8111 SRC 1 Vb Harm[21] Volts Source 1 phase B voltage twenty-third harmonic
8112 SRC 1 Vb Harm[22] Volts Source 1 phase B voltage twenty-fourth harmonic
8113 SRC 1 Vb Harm[23] Volts Source 1 phase B voltage twenty-fifth harmonic
8114 SRC 1 Vc THD --- Source 1 phase C voltage total harmonic distortion (THD)
8115 SRC 1 Vc Harm[0] Volts Source 1 phase C voltage second harmonic
8116 SRC 1 Vc Harm[1] Volts Source 1 phase C voltage third harmonic
8117 SRC 1 Vc Harm[2] Volts Source 1 phase C voltage fourth harmonic
8118 SRC 1 Vc Harm[3] Volts Source 1 phase C voltage fifth harmonic
8119 SRC 1 Vc Harm[4] Volts Source 1 phase C voltage sixth harmonic
8120 SRC 1 Vc Harm[5] Volts Source 1 phase C voltage seventh harmonic
8121 SRC 1 Vc Harm[6] Volts Source 1 phase C voltage eighth harmonic
8122 SRC 1 Vc Harm[7] Volts Source 1 phase C voltage ninth harmonic
8123 SRC 1 Vc Harm[8] Volts Source 1 phase C voltage tenth harmonic
8124 SRC 1 Vc Harm[9] Volts Source 1 phase C voltage eleventh harmonic
8125 SRC 1 Vc Harm[10] Volts Source 1 phase C voltage twelfth harmonic
8126 SRC 1 Vc Harm[11] Volts Source 1 phase C voltage thirteenth harmonic
8127 SRC 1 Vc Harm[12] Volts Source 1 phase C voltage fourteenth harmonic
8128 SRC 1 Vc Harm[13] Volts Source 1 phase C voltage fifteenth harmonic
8129 SRC 1 Vc Harm[14] Volts Source 1 phase C voltage sixteenth harmonic
8130 SRC 1 Vc Harm[15] Volts Source 1 phase C voltage seventeenth harmonic
8131 SRC 1 Vc Harm[16] Volts Source 1 phase C voltage eighteenth harmonic
8132 SRC 1 Vc Harm[17] Volts Source 1 phase C voltage nineteenth harmonic
8133 SRC 1 Vc Harm[18] Volts Source 1 phase C voltage twentieth harmonic
8134 SRC 1 Vc Harm[19] Volts Source 1 phase C voltage twenty-first harmonic
8135 SRC 1 Vc Harm[20] Volts Source 1 phase C voltage twenty-second harmonic
8136 SRC 1 Vc Harm[21] Volts Source 1 phase C voltage twenty-third harmonic
8137 SRC 1 Vc Harm[22] Volts Source 1 phase C voltage twenty-fourth harmonic
8138 SRC 1 Vc Harm[23] Volts Source 1 phase C voltage twenty-fifth harmonic
8139 SRC 2 Va THD --- Source 2 phase A voltage total harmonic distortion (THD)
8140 SRC 2 Va Harm[0] Volts Source 2 phase A voltage second harmonic
8141 SRC 2 Va Harm[1] Volts Source 2 phase A voltage third harmonic
8142 SRC 2 Va Harm[2] Volts Source 2 phase A voltage fourth harmonic
A ADDRESS
8190
FLEXANALOG NAME
SRC 2 Vc Harm[0]
UNITS
Volts
DESCRIPTION
Source 2 phase C voltage second harmonic
8191 SRC 2 Vc Harm[1] Volts Source 2 phase C voltage third harmonic
8192 SRC 2 Vc Harm[2] Volts Source 2 phase C voltage fourth harmonic
8193 SRC 2 Vc Harm[3] Volts Source 2 phase C voltage fifth harmonic
8194 SRC 2 Vc Harm[4] Volts Source 2 phase C voltage sixth harmonic
8195 SRC 2 Vc Harm[5] Volts Source 2 phase C voltage seventh harmonic
8196 SRC 2 Vc Harm[6] Volts Source 2 phase C voltage eighth harmonic
8197 SRC 2 Vc Harm[7] Volts Source 2 phase C voltage ninth harmonic
8198 SRC 2 Vc Harm[8] Volts Source 2 phase C voltage tenth harmonic
8199 SRC 2 Vc Harm[9] Volts Source 2 phase C voltage eleventh harmonic
8200 SRC 2 Vc Harm[10] Volts Source 2 phase C voltage twelfth harmonic
8201 SRC 2 Vc Harm[11] Volts Source 2 phase C voltage thirteenth harmonic
8202 SRC 2 Vc Harm[12] Volts Source 2 phase C voltage fourteenth harmonic
8203 SRC 2 Vc Harm[13] Volts Source 2 phase C voltage fifteenth harmonic
8204 SRC 2 Vc Harm[14] Volts Source 2 phase C voltage sixteenth harmonic
8205 SRC 2 Vc Harm[15] Volts Source 2 phase C voltage seventeenth harmonic
8206 SRC 2 Vc Harm[16] Volts Source 2 phase C voltage eighteenth harmonic
8207 SRC 2 Vc Harm[17] Volts Source 2 phase C voltage nineteenth harmonic
8208 SRC 2 Vc Harm[18] Volts Source 2 phase C voltage twentieth harmonic
8209 SRC 2 Vc Harm[19] Volts Source 2 phase C voltage twenty-first harmonic
8210 SRC 2 Vc Harm[20] Volts Source 2 phase C voltage twenty-second harmonic
8211 SRC 2 Vc Harm[21] Volts Source 2 phase C voltage twenty-third harmonic
8212 SRC 2 Vc Harm[22] Volts Source 2 phase C voltage twenty-fourth harmonic
8213 SRC 2 Vc Harm[23] Volts Source 2 phase C voltage twenty-fifth harmonic
8214 SRC 3 Va THD --- Source 3 phase A voltage total harmonic distortion (THD)
8215 SRC 3 Va Harm[0] Volts Source 3 phase A voltage second harmonic
8216 SRC 3 Va Harm[1] Volts Source 3 phase A voltage third harmonic
8217 SRC 3 Va Harm[2] Volts Source 3 phase A voltage fourth harmonic
8218 SRC 3 Va Harm[3] Volts Source 3 phase A voltage fifth harmonic
8219 SRC 3 Va Harm[4] Volts Source 3 phase A voltage sixth harmonic
8220 SRC 3 Va Harm[5] Volts Source 3 phase A voltage seventh harmonic
8221 SRC 3 Va Harm[6] Volts Source 3 phase A voltage eighth harmonic
8222 SRC 3 Va Harm[7] Volts Source 3 phase A voltage ninth harmonic
8223 SRC 3 Va Harm[8] Volts Source 3 phase A voltage tenth harmonic
8224 SRC 3 Va Harm[9] Volts Source 3 phase A voltage eleventh harmonic
8225 SRC 3 Va Harm[10] Volts Source 3 phase A voltage twelfth harmonic
8226 SRC 3 Va Harm[11] Volts Source 3 phase A voltage thirteenth harmonic
8227 SRC 3 Va Harm[12] Volts Source 3 phase A voltage fourteenth harmonic
8228 SRC 3 Va Harm[13] Volts Source 3 phase A voltage fifteenth harmonic
8229 SRC 3 Va Harm[14] Volts Source 3 phase A voltage sixteenth harmonic
8230 SRC 3 Va Harm[15] Volts Source 3 phase A voltage seventeenth harmonic
8231 SRC 3 Va Harm[16] Volts Source 3 phase A voltage eighteenth harmonic
8232 SRC 3 Va Harm[17] Volts Source 3 phase A voltage nineteenth harmonic
8233 SRC 3 Va Harm[18] Volts Source 3 phase A voltage twentieth harmonic
8234 SRC 3 Va Harm[19] Volts Source 3 phase A voltage twenty-first harmonic
8235 SRC 3 Va Harm[20] Volts Source 3 phase A voltage twenty-second harmonic
8236 SRC 3 Va Harm[21] Volts Source 3 phase A voltage twenty-third harmonic
A ADDRESS
8284
FLEXANALOG NAME
SRC 3 Vc Harm[19]
UNITS
Volts
DESCRIPTION
Source 3 phase C voltage twenty-first harmonic
8285 SRC 3 Vc Harm[20] Volts Source 3 phase C voltage twenty-second harmonic
8286 SRC 3 Vc Harm[21] Volts Source 3 phase C voltage twenty-third harmonic
8287 SRC 3 Vc Harm[22] Volts Source 3 phase C voltage twenty-fourth harmonic
8288 SRC 3 Vc Harm[23] Volts Source 3 phase C voltage twenty-fifth harmonic
8289 SRC 4 Va THD --- Source 4 phase A voltage total harmonic distortion (THD)
8290 SRC 4 Va Harm[0] Volts Source 4 phase A voltage second harmonic
8291 SRC 4 Va Harm[1] Volts Source 4 phase A voltage third harmonic
8292 SRC 4 Va Harm[2] Volts Source 4 phase A voltage fourth harmonic
8293 SRC 4 Va Harm[3] Volts Source 4 phase A voltage fifth harmonic
8294 SRC 4 Va Harm[4] Volts Source 4 phase A voltage sixth harmonic
8295 SRC 4 Va Harm[5] Volts Source 4 phase A voltage seventh harmonic
8296 SRC 4 Va Harm[6] Volts Source 4 phase A voltage eighth harmonic
8297 SRC 4 Va Harm[7] Volts Source 4 phase A voltage ninth harmonic
8298 SRC 4 Va Harm[8] Volts Source 4 phase A voltage tenth harmonic
8299 SRC 4 Va Harm[9] Volts Source 4 phase A voltage eleventh harmonic
8300 SRC 4 Va Harm[10] Volts Source 4 phase A voltage twelfth harmonic
8301 SRC 4 Va Harm[11] Volts Source 4 phase A voltage thirteenth harmonic
8302 SRC 4 Va Harm[12] Volts Source 4 phase A voltage fourteenth harmonic
8303 SRC 4 Va Harm[13] Volts Source 4 phase A voltage fifteenth harmonic
8304 SRC 4 Va Harm[14] Volts Source 4 phase A voltage sixteenth harmonic
8305 SRC 4 Va Harm[15] Volts Source 4 phase A voltage seventeenth harmonic
8306 SRC 4 Va Harm[16] Volts Source 4 phase A voltage eighteenth harmonic
8307 SRC 4 Va Harm[17] Volts Source 4 phase A voltage nineteenth harmonic
8308 SRC 4 Va Harm[18] Volts Source 4 phase A voltage twentieth harmonic
8309 SRC 4 Va Harm[19] Volts Source 4 phase A voltage twenty-first harmonic
8310 SRC 4 Va Harm[20] Volts Source 4 phase A voltage twenty-second harmonic
8311 SRC 4 Va Harm[21] Volts Source 4 phase A voltage twenty-third harmonic
8312 SRC 4 Va Harm[22] Volts Source 4 phase A voltage twenty-fourth harmonic
8313 SRC 4 Va Harm[23] Volts Source 4 phase A voltage twenty-fifth harmonic
8314 SRC 4 Vb THD --- Source 4 phase B voltage total harmonic distortion (THD)
8315 SRC 4 Vb Harm[0] Volts Source 4 phase B voltage second harmonic
8316 SRC 4 Vb Harm[1] Volts Source 4 phase B voltage third harmonic
8317 SRC 4 Vb Harm[2] Volts Source 4 phase B voltage fourth harmonic
8318 SRC 4 Vb Harm[3] Volts Source 4 phase B voltage fifth harmonic
8319 SRC 4 Vb Harm[4] Volts Source 4 phase B voltage sixth harmonic
8320 SRC 4 Vb Harm[5] Volts Source 4 phase B voltage seventh harmonic
8321 SRC 4 Vb Harm[6] Volts Source 4 phase B voltage eighth harmonic
8322 SRC 4 Vb Harm[7] Volts Source 4 phase B voltage ninth harmonic
8323 SRC 4 Vb Harm[8] Volts Source 4 phase B voltage tenth harmonic
8324 SRC 4 Vb Harm[9] Volts Source 4 phase B voltage eleventh harmonic
8325 SRC 4 Vb Harm[10] Volts Source 4 phase B voltage twelfth harmonic
8326 SRC 4 Vb Harm[11] Volts Source 4 phase B voltage thirteenth harmonic
8327 SRC 4 Vb Harm[12] Volts Source 4 phase B voltage fourteenth harmonic
8328 SRC 4 Vb Harm[13] Volts Source 4 phase B voltage fifteenth harmonic
8329 SRC 4 Vb Harm[14] Volts Source 4 phase B voltage sixteenth harmonic
8330 SRC 4 Vb Harm[15] Volts Source 4 phase B voltage seventeenth harmonic
A ADDRESS
9548
FLEXANALOG NAME
PMU 1 V1 Mag
UNITS
Volts
DESCRIPTION
Phasor measurement unit 1 positive-sequence voltage magnitude
9550 PMU 1 V1 Angle Degrees Phasor measurement unit 1 positive-sequence voltage angle
9551 PMU 1 V2 Mag Volts Phasor measurement unit 1 negative-sequence voltage magnitude
9553 PMU 1 V2 Angle Degrees Phasor measurement unit 1 negative-sequence voltage angle
9554 PMU 1 V0 Mag Volts Phasor measurement unit 1 zero-sequence voltage magnitude
9556 PMU 1 V0 Angle Degrees Phasor measurement unit 1 zero-sequence voltage angle
9557 PMU 1 Ia Mag Amps Phasor measurement unit 1 phase A current magnitude
9559 PMU 1 Ia Angle Degrees Phasor measurement unit 1 phase A current angle
9560 PMU 1 Ib Mag Amps Phasor measurement unit 1 phase B current magnitude
9562 PMU 1 Ib Angle Degrees Phasor measurement unit 1 phase B current angle
9563 PMU 1 Ic Mag Amps Phasor measurement unit 1 phase C current magnitude
9565 PMU 1 Ic Angle Degrees Phasor measurement unit 1 phase C current angle
9566 PMU 1 Ig Mag Amps Phasor measurement unit 1 ground current magnitude
9568 PMU 1 Ig Angle Degrees Phasor measurement unit 1 ground current angle
9569 PMU 1 I1 Mag Amps Phasor measurement unit 1 positive-sequence current magnitude
9571 PMU 1 I1 Angle Degrees Phasor measurement unit 1 positive-sequence current angle
9572 PMU 1 I2 Mag Amps Phasor measurement unit 1 negative-sequence current magnitude
9574 PMU 1 I2 Angle Degrees Phasor measurement unit 1 negative-sequence current angle
9575 PMU 1 I0 Mag Amps Phasor measurement unit 1 zero-sequence current magnitude
9577 PMU 1 I0 Angle Degrees Phasor measurement unit 1 zero-sequence current angle
9578 PMU 1 Freq Hz Phasor measurement unit 1 frequency
9580 PMU 1 df dt Hz/s Phasor measurement unit 1 rate of change of frequency
9581 PMU 1 Conf Ch --- Phasor measurement unit 1 configuration change counter
10240 SRC 1 Ia THD --- Source 1 phase A current total harmonic distortion
10241 SRC 1 Ia Harm[0] Amps Source 1 phase A current second harmonic
10242 SRC 1 Ia Harm[1] Amps Source 1 phase A current third harmonic
10243 SRC 1 Ia Harm[2] Amps Source 1 phase A current fourth harmonic
10244 SRC 1 Ia Harm[3] Amps Source 1 phase A current fifth harmonic
10245 SRC 1 Ia Harm[4] Amps Source 1 phase A current sixth harmonic
10246 SRC 1 Ia Harm[5] Amps Source 1 phase A current seventh harmonic
10247 SRC 1 Ia Harm[6] Amps Source 1 phase A current eighth harmonic
10248 SRC 1 Ia Harm[7] Amps Source 1 phase A current ninth harmonic
10249 SRC 1 Ia Harm[8] Amps Source 1 phase A current tenth harmonic
10250 SRC 1 Ia Harm[9] Amps Source 1 phase A current eleventh harmonic
10251 SRC 1 Ia Harm[10] Amps Source 1 phase A current twelfth harmonic
10252 SRC 1 Ia Harm[11] Amps Source 1 phase A current thirteenth harmonic
10253 SRC 1 Ia Harm[12] Amps Source 1 phase A current fourteenth harmonic
10254 SRC 1 Ia Harm[13] Amps Source 1 phase A current fifteenth harmonic
10255 SRC 1 Ia Harm[14] Amps Source 1 phase A current sixteenth harmonic
10256 SRC 1 Ia Harm[15] Amps Source 1 phase A current seventeenth harmonic
10257 SRC 1 Ia Harm[16] Amps Source 1 phase A current eighteenth harmonic
10258 SRC 1 Ia Harm[17] Amps Source 1 phase A current nineteenth harmonic
10259 SRC 1 Ia Harm[18] Amps Source 1 phase A current twentieth harmonic
10260 SRC 1 Ia Harm[19] Amps Source 1 phase A current twenty-first harmonic
10261 SRC 1 Ia Harm[20] Amps Source 1 phase A current twenty-second harmonic
10262 SRC 1 Ia Harm[21] Amps Source 1 phase A current twenty-third harmonic
10263 SRC 1 Ia Harm[22] Amps Source 1 phase A current twenty-fourth harmonic
A ADDRESS
10327
FLEXANALOG NAME
SRC 1 Ic Harm[20]
UNITS
Amps
DESCRIPTION
Source 1 phase C current twenty-second harmonic
10328 SRC 1 Ic Harm[21] Amps Source 1 phase C current twenty-third harmonic
10329 SRC 1 Ic Harm[22] Amps Source 1 phase C current twenty-fourth harmonic
10330 SRC 1 Ic Harm[23] Amps Source 1 phase C current twenty-fifth harmonic
10339 SRC 2 Ia THD --- Source 2 phase A current total harmonic distortion
10340 SRC 2 Ia Harm[0] Amps Source 2 phase A current second harmonic
10341 SRC 2 Ia Harm[1] Amps Source 2 phase A current third harmonic
10342 SRC 2 Ia Harm[2] Amps Source 2 phase A current fourth harmonic
10343 SRC 2 Ia Harm[3] Amps Source 2 phase A current fifth harmonic
10344 SRC 2 Ia Harm[4] Amps Source 2 phase A current sixth harmonic
10345 SRC 2 Ia Harm[5] Amps Source 2 phase A current seventh harmonic
10346 SRC 2 Ia Harm[6] Amps Source 2 phase A current eighth harmonic
10347 SRC 2 Ia Harm[7] Amps Source 2 phase A current ninth harmonic
10348 SRC 2 Ia Harm[8] Amps Source 2 phase A current tenth harmonic
10349 SRC 2 Ia Harm[9] Amps Source 2 phase A current eleventh harmonic
10350 SRC 2 Ia Harm[10] Amps Source 2 phase A current twelfth harmonic
10351 SRC 2 Ia Harm[11] Amps Source 2 phase A current thirteenth harmonic
10352 SRC 2 Ia Harm[12] Amps Source 2 phase A current fourteenth harmonic
10353 SRC 2 Ia Harm[13] Amps Source 2 phase A current fifteenth harmonic
10354 SRC 2 Ia Harm[14] Amps Source 2 phase A current sixteenth harmonic
10355 SRC 2 Ia Harm[15] Amps Source 2 phase A current seventeenth harmonic
10356 SRC 2 Ia Harm[16] Amps Source 2 phase A current eighteenth harmonic
10357 SRC 2 Ia Harm[17] Amps Source 2 phase A current nineteenth harmonic
10358 SRC 2 Ia Harm[18] Amps Source 2 phase A current twentieth harmonic
10359 SRC 2 Ia Harm[19] Amps Source 2 phase A current twenty-first harmonic
10360 SRC 2 Ia Harm[20] Amps Source 2 phase A current twenty-second harmonic
10361 SRC 2 Ia Harm[21] Amps Source 2 phase A current twenty-third harmonic
10362 SRC 2 Ia Harm[22] Amps Source 2 phase A current twenty-fourth harmonic
10363 SRC 2 Ia Harm[23] Amps Source 2 phase A current twenty-fifth harmonic
10372 SRC 2 Ib THD --- Source 2 phase B current total harmonic distortion
10373 SRC 2 Ib Harm[0] Amps Source 2 phase B current second harmonic
10374 SRC 2 Ib Harm[1] Amps Source 2 phase B current third harmonic
10375 SRC 2 Ib Harm[2] Amps Source 2 phase B current fourth harmonic
10376 SRC 2 Ib Harm[3] Amps Source 2 phase B current fifth harmonic
10377 SRC 2 Ib Harm[4] Amps Source 2 phase B current sixth harmonic
10378 SRC 2 Ib Harm[5] Amps Source 2 phase B current seventh harmonic
10379 SRC 2 Ib Harm[6] Amps Source 2 phase B current eighth harmonic
10380 SRC 2 Ib Harm[7] Amps Source 2 phase B current ninth harmonic
10381 SRC 2 Ib Harm[8] Amps Source 2 phase B current tenth harmonic
10382 SRC 2 Ib Harm[9] Amps Source 2 phase B current eleventh harmonic
10383 SRC 2 Ib Harm[10] Amps Source 2 phase B current twelfth harmonic
10384 SRC 2 Ib Harm[11] Amps Source 2 phase B current thirteenth harmonic
10385 SRC 2 Ib Harm[12] Amps Source 2 phase B current fourteenth harmonic
10386 SRC 2 Ib Harm[13] Amps Source 2 phase B current fifteenth harmonic
10387 SRC 2 Ib Harm[14] Amps Source 2 phase B current sixteenth harmonic
10388 SRC 2 Ib Harm[15] Amps Source 2 phase B current seventeenth harmonic
10389 SRC 2 Ib Harm[16] Amps Source 2 phase B current eighteenth harmonic
A ADDRESS
10453
FLEXANALOG NAME
SRC 3 Ia Harm[14]
UNITS
Amps
DESCRIPTION
Source 3 phase A current sixteenth harmonic
10454 SRC 3 Ia Harm[15] Amps Source 3 phase A current seventeenth harmonic
10455 SRC 3 Ia Harm[16] Amps Source 3 phase A current eighteenth harmonic
10456 SRC 3 Ia Harm[17] Amps Source 3 phase A current nineteenth harmonic
10457 SRC 3 Ia Harm[18] Amps Source 3 phase A current twentieth harmonic
10458 SRC 3 Ia Harm[19] Amps Source 3 phase A current twenty-first harmonic
10459 SRC 3 Ia Harm[20] Amps Source 3 phase A current twenty-second harmonic
10460 SRC 3 Ia Harm[21] Amps Source 3 phase A current twenty-third harmonic
10461 SRC 3 Ia Harm[22] Amps Source 3 phase A current twenty-fourth harmonic
10462 SRC 3 Ia Harm[23] Amps Source 3 phase A current twenty-fifth harmonic
10471 SRC 3 Ib THD --- Source 3 phase B current total harmonic distortion
10472 SRC 3 Ib Harm[0] Amps Source 3 phase B current second harmonic
10473 SRC 3 Ib Harm[1] Amps Source 3 phase B current third harmonic
10474 SRC 3 Ib Harm[2] Amps Source 3 phase B current fourth harmonic
10475 SRC 3 Ib Harm[3] Amps Source 3 phase B current fifth harmonic
10476 SRC 3 Ib Harm[4] Amps Source 3 phase B current sixth harmonic
10477 SRC 3 Ib Harm[5] Amps Source 3 phase B current seventh harmonic
10478 SRC 3 Ib Harm[6] Amps Source 3 phase B current eighth harmonic
10479 SRC 3 Ib Harm[7] Amps Source 3 phase B current ninth harmonic
10480 SRC 3 Ib Harm[8] Amps Source 3 phase B current tenth harmonic
10481 SRC 3 Ib Harm[9] Amps Source 3 phase B current eleventh harmonic
10482 SRC 3 Ib Harm[10] Amps Source 3 phase B current twelfth harmonic
10483 SRC 3 Ib Harm[11] Amps Source 3 phase B current thirteenth harmonic
10484 SRC 3 Ib Harm[12] Amps Source 3 phase B current fourteenth harmonic
10485 SRC 3 Ib Harm[13] Amps Source 3 phase B current fifteenth harmonic
10486 SRC 3 Ib Harm[14] Amps Source 3 phase B current sixteenth harmonic
10487 SRC 3 Ib Harm[15] Amps Source 3 phase B current seventeenth harmonic
10488 SRC 3 Ib Harm[16] Amps Source 3 phase B current eighteenth harmonic
10489 SRC 3 Ib Harm[17] Amps Source 3 phase B current nineteenth harmonic
10490 SRC 3 Ib Harm[18] Amps Source 3 phase B current twentieth harmonic
10491 SRC 3 Ib Harm[19] Amps Source 3 phase B current twenty-first harmonic
10492 SRC 3 Ib Harm[20] Amps Source 3 phase B current twenty-second harmonic
10493 SRC 3 Ib Harm[21] Amps Source 3 phase B current twenty-third harmonic
10494 SRC 3 Ib Harm[22] Amps Source 3 phase B current twenty-fourth harmonic
10495 SRC 3 Ib Harm[23] Amps Source 3 phase B current twenty-fifth harmonic
10504 SRC 3 Ic THD --- Source 3 phase C current total harmonic distortion
10505 SRC 3 Ic Harm[0] Amps Source 3 phase C current second harmonic
10506 SRC 3 Ic Harm[1] Amps Source 3 phase C current third harmonic
10507 SRC 3 Ic Harm[2] Amps Source 3 phase C current fourth harmonic
10508 SRC 3 Ic Harm[3] Amps Source 3 phase C current fifth harmonic
10509 SRC 3 Ic Harm[4] Amps Source 3 phase C current sixth harmonic
10510 SRC 3 Ic Harm[5] Amps Source 3 phase C current seventh harmonic
10511 SRC 3 Ic Harm[6] Amps Source 3 phase C current eighth harmonic
10512 SRC 3 Ic Harm[7] Amps Source 3 phase C current ninth harmonic
10513 SRC 3 Ic Harm[8] Amps Source 3 phase C current tenth harmonic
10514 SRC 3 Ic Harm[9] Amps Source 3 phase C current eleventh harmonic
10515 SRC 3 Ic Harm[10] Amps Source 3 phase C current twelfth harmonic
A ADDRESS
10579
FLEXANALOG NAME
SRC 4 Ib Harm[8]
UNITS
Amps
DESCRIPTION
Source 4 phase B current tenth harmonic
10580 SRC 4 Ib Harm[9] Amps Source 4 phase B current eleventh harmonic
10581 SRC 4 Ib Harm[10] Amps Source 4 phase B current twelfth harmonic
10582 SRC 4 Ib Harm[11] Amps Source 4 phase B current thirteenth harmonic
10583 SRC 4 Ib Harm[12] Amps Source 4 phase B current fourteenth harmonic
10584 SRC 4 Ib Harm[13] Amps Source 4 phase B current fifteenth harmonic
10585 SRC 4 Ib Harm[14] Amps Source 4 phase B current sixteenth harmonic
10586 SRC 4 Ib Harm[15] Amps Source 4 phase B current seventeenth harmonic
10587 SRC 4 Ib Harm[16] Amps Source 4 phase B current eighteenth harmonic
10588 SRC 4 Ib Harm[17] Amps Source 4 phase B current nineteenth harmonic
10589 SRC 4 Ib Harm[18] Amps Source 4 phase B current twentieth harmonic
10590 SRC 4 Ib Harm[19] Amps Source 4 phase B current twenty-first harmonic
10591 SRC 4 Ib Harm[20] Amps Source 4 phase B current twenty-second harmonic
10592 SRC 4 Ib Harm[21] Amps Source 4 phase B current twenty-third harmonic
10593 SRC 4 Ib Harm[22] Amps Source 4 phase B current twenty-fourth harmonic
10594 SRC 4 Ib Harm[23] Amps Source 4 phase B current twenty-fifth harmonic
10603 SRC 4 Ic THD --- Source 4 phase C current total harmonic distortion
10604 SRC 4 Ic Harm[0] Amps Source 4 phase C current second harmonic
10605 SRC 4 Ic Harm[1] Amps Source 4 phase C current third harmonic
10606 SRC 4 Ic Harm[2] Amps Source 4 phase C current fourth harmonic
10607 SRC 4 Ic Harm[3] Amps Source 4 phase C current fifth harmonic
10608 SRC 4 Ic Harm[4] Amps Source 4 phase C current sixth harmonic
10609 SRC 4 Ic Harm[5] Amps Source 4 phase C current seventh harmonic
10610 SRC 4 Ic Harm[6] Amps Source 4 phase C current eighth harmonic
10611 SRC 4 Ic Harm[7] Amps Source 4 phase C current ninth harmonic
10612 SRC 4 Ic Harm[8] Amps Source 4 phase C current tenth harmonic
10613 SRC 4 Ic Harm[9] Amps Source 4 phase C current eleventh harmonic
10614 SRC 4 Ic Harm[10] Amps Source 4 phase C current twelfth harmonic
10615 SRC 4 Ic Harm[11] Amps Source 4 phase C current thirteenth harmonic
10616 SRC 4 Ic Harm[12] Amps Source 4 phase C current fourteenth harmonic
10617 SRC 4 Ic Harm[13] Amps Source 4 phase C current fifteenth harmonic
10618 SRC 4 Ic Harm[14] Amps Source 4 phase C current sixteenth harmonic
10619 SRC 4 Ic Harm[15] Amps Source 4 phase C current seventeenth harmonic
10620 SRC 4 Ic Harm[16] Amps Source 4 phase C current eighteenth harmonic
10621 SRC 4 Ic Harm[17] Amps Source 4 phase C current nineteenth harmonic
10622 SRC 4 Ic Harm[18] Amps Source 4 phase C current twentieth harmonic
10623 SRC 4 Ic Harm[19] Amps Source 4 phase C current twenty-first harmonic
10624 SRC 4 Ic Harm[20] Amps Source 4 phase C current twenty-second harmonic
10625 SRC 4 Ic Harm[21] Amps Source 4 phase C current twenty-third harmonic
10626 SRC 4 Ic Harm[22] Amps Source 4 phase C current twenty-fourth harmonic
10627 SRC 4 Ic Harm[23] Amps Source 4 phase C current twenty-fifth harmonic
13504 DCMA Inputs 1 Value mA dcmA input 1 actual value
13506 DCMA Inputs 2 Value mA dcmA input 2 actual value
13508 DCMA Inputs 3 Value mA dcmA input 3 actual value
13510 DCMA Inputs 4 Value mA dcmA input 4 actual value
13512 DCMA Inputs 5 Value mA dcmA input 5 actual value
13514 DCMA Inputs 6 Value mA dcmA input 6 actual value
A ADDRESS
13581
FLEXANALOG NAME
RTD Inputs 30 Value
UNITS
---
DESCRIPTION
RTD input 30 actual value
13582 RTD Inputs 31 Value --- RTD input 31 actual value
13583 RTD Inputs 32 Value --- RTD input 32 actual value
13584 RTD Inputs 33 Value --- RTD input 33 actual value
13585 RTD Inputs 34 Value --- RTD input 34 actual value
13586 RTD Inputs 35 Value --- RTD input 35 actual value
13587 RTD Inputs 36 Value --- RTD input 36 actual value
13588 RTD Inputs 37 Value --- RTD input 37 actual value
13589 RTD Inputs 38 Value --- RTD input 38 actual value
13590 RTD Inputs 39 Value --- RTD input 39 actual value
13591 RTD Inputs 40 Value --- RTD input 40 actual value
13592 RTD Inputs 41 Value --- RTD input 41 actual value
13593 RTD Inputs 42 Value --- RTD input 42 actual value
13594 RTD Inputs 43 Value --- RTD input 43 actual value
13595 RTD Inputs 44 Value --- RTD input 44 actual value
13596 RTD Inputs 45 Value --- RTD input 45 actual value
13597 RTD Inputs 46 Value --- RTD input 46 actual value
13598 RTD Inputs 47 Value --- RTD input 47 actual value
13599 RTD Inputs 48 Value --- RTD input 48 actual value
24459 Active Setting Group --- Current setting group
32768 Tracking Frequency Hz Tracking frequency
34752 RRTD RTD 1 Value °C Remote RTD input 1 actual value
34753 RRTD RTD 2 Value °C Remote RTD input 2 actual value
34754 RRTD RTD 3 Value °C Remote RTD input 3 actual value
34755 RRTD RTD 4 Value °C Remote RTD input 4 actual value
34756 RRTD RTD 5 Value °C Remote RTD input 5 actual value
34757 RRTD RTD 6 Value °C Remote RTD input 6 actual value
34758 RRTD RTD 7 Value °C Remote RTD input 7 actual value
34759 RRTD RTD 8 Value °C Remote RTD input 8 actual value
34760 RRTD RTD 9 Value °C Remote RTD input 9 actual value
34761 RRTD RTD 10 Value °C Remote RTD input 10 actual value
34762 RRTD RTD 11 Value °C Remote RTD input 11 actual value
34763 RRTD RTD 12 Value °C Remote RTD input 12 actual value
39425 FlexElement 1 Value --- FlexElement™ 1 actual value
39427 FlexElement 2 Value --- FlexElement™ 2 actual value
39429 FlexElement 3 Value --- FlexElement™ 3 actual value
39431 FlexElement 4 Value --- FlexElement™ 4 actual value
39433 FlexElement 5 Value --- FlexElement™ 5 actual value
39435 FlexElement 6 Value --- FlexElement™ 6 actual value
39437 FlexElement 7 Value --- FlexElement™ 7 actual value
39439 FlexElement 8 Value --- FlexElement™ 8 actual value
39441 FlexElement 9 Value --- FlexElement™ 9 actual value
39443 FlexElement 10 Value --- FlexElement™ 10 actual value
39445 FlexElement 11 Value --- FlexElement™ 11 actual value
39447 FlexElement 12 Value --- FlexElement™ 12 actual value
39449 FlexElement 13 Value --- FlexElement™ 13 actual value
39451 FlexElement 14 Value --- FlexElement™ 14 actual value
A
Table A–2: FLEXINTEGER DATA ITEMS
ADDRESS FLEXINTEGER NAME UNITS DESCRIPTION
9736 PMU 1 SOC seconds PMU 1 SOC timestamps
9738 PMU 1 FRACSEC seconds PMU 1 FRACSEC timestamps
9740 PMU 1 STAT --- PMU 1 STAT flags
9968 GOOSE UInt Input 1 --- IEC61850 GOOSE UInteger input 1
9970 GOOSE UInt Input 2 --- IEC61850 GOOSE UInteger input 2
9972 GOOSE UInt Input 3 --- IEC61850 GOOSE UInteger input 3
9974 GOOSE UInt Input 4 --- IEC61850 GOOSE UInteger input 4
9976 GOOSE UInt Input 5 --- IEC61850 GOOSE UInteger input 5
9978 GOOSE UInt Input 6 --- IEC61850 GOOSE UInteger input 6
9980 GOOSE UInt Input 7 --- IEC61850 GOOSE UInteger input 7
9982 GOOSE UInt Input 8 --- IEC61850 GOOSE UInteger input 8
9984 GOOSE UInt Input 9 --- IEC61850 GOOSE UInteger input 9
9986 GOOSE UInt Input 10 --- IEC61850 GOOSE UInteger input 10
9988 GOOSE UInt Input 11 --- IEC61850 GOOSE UInteger input 11
9990 GOOSE UInt Input 12 --- IEC61850 GOOSE UInteger input 12
9992 GOOSE UInt Input 13 --- IEC61850 GOOSE UInteger input 13
9994 GOOSE UInt Input 14 --- IEC61850 GOOSE UInteger input 14
9996 GOOSE UInt Input 15 --- IEC61850 GOOSE UInteger input 15
9998 GOOSE UInt Input 16 --- IEC61850 GOOSE UInteger input 16
The UR-series relays support a number of communications protocols to allow connection to equipment such as personal
computers, RTUs, SCADA masters, and programmable logic controllers. The Modicon Modbus RTU protocol is the most
basic protocol supported by the UR. Modbus is available via RS232 or RS485 serial links or via ethernet (using the Mod-
bus/TCP specification). The following description is intended primarily for users who wish to develop their own master com-
munication drivers and applies to the serial Modbus RTU protocol. Note that:
• The UR always acts as a slave device, meaning that it never initiates communications; it only listens and responds to B
requests issued by a master computer.
• For Modbus®, a subset of the Remote Terminal Unit (RTU) protocol format is supported that allows extensive monitor-
ing, programming, and control functions using read and write register commands.
The Modbus® RTU protocol is hardware-independent so that the physical layer can be any of a variety of standard hard-
ware configurations including RS232 and RS485. The relay includes a faceplate (front panel) RS232 port and two rear ter-
minal communications ports that may be configured as RS485, fiber optic, 10Base-T, or 10Base-F. Data flow is half-duplex
in all configurations. See chapter 3 for details on communications wiring.
Each data byte is transmitted in an asynchronous format consisting of 1 start bit, 8 data bits, 1 stop bit, and possibly 1 parity
bit. This produces a 10 or 11 bit data frame. This can be important for transmission through modems at high bit rates (11 bit
data frames are not supported by many modems at baud rates greater than 300).
The baud rate and parity are independently programmable for each communications port. Baud rates of 300, 1200, 2400,
4800, 9600, 14400, 19200, 28800, 33600, 38400, 57600, or 115200 bps are available. Even, odd, and no parity are avail-
able. Refer to the Communications section of chapter 5 for further details.
The master device in any system must know the address of the slave device with which it is to communicate. The relay will
not act on a request from a master if the address in the request does not match the relay’s slave address (unless the
address is the broadcast address – see below).
A single setting selects the slave address used for all ports, with the exception that for the faceplate port, the relay will
accept any address when the Modbus® RTU protocol is used.
Communications takes place in packets which are groups of asynchronously framed byte data. The master transmits a
packet to the slave and the slave responds with a packet. The end of a packet is marked by dead-time on the communica-
tions line. The following describes general format for both transmit and receive packets. For exact details on packet format-
ting, refer to subsequent sections describing each function code.
• SLAVE ADDRESS: This is the address of the slave device that is intended to receive the packet sent by the master
and to perform the desired action. Each slave device on a communications bus must have a unique address to prevent
bus contention. All of the relay’s ports have the same address which is programmable from 1 to 254; see chapter 5 for
details. Only the addressed slave will respond to a packet that starts with its address. Note that the faceplate port is an
exception to this rule; it will act on a message containing any slave address.
A master transmit packet with slave address 0 indicates a broadcast command. All slaves on the communication link
take action based on the packet, but none respond to the master. Broadcast mode is only recognized when associated
with function code 05h. For any other function code, a packet with broadcast mode slave address 0 will be ignored.
• FUNCTION CODE: This is one of the supported functions codes of the unit which tells the slave what action to per-
form. See the Supported Function Codes section for complete details. An exception response from the slave is indi-
cated by setting the high order bit of the function code in the response packet. See the Exception Responses section
for further details.
• DATA: This will be a variable number of bytes depending on the function code. This may include actual values, set-
tings, or addresses sent by the master to the slave or by the slave to the master.
• CRC: This is a two byte error checking code. The RTU version of Modbus® includes a 16-bit cyclic redundancy check
B (CRC-16) with every packet which is an industry standard method used for error detection. If a Modbus slave device
receives a packet in which an error is indicated by the CRC, the slave device will not act upon or respond to the packet
thus preventing any erroneous operations. See the CRC-16 Algorithm section for details on calculating the CRC.
• DEAD TIME: A packet is terminated when no data is received for a period of 3.5 byte transmission times (about 15 ms
at 2400 bps, 2 ms at 19200 bps, and 300 µs at 115200 bps). Consequently, the transmitting device must not allow gaps
between bytes longer than this interval. Once the dead time has expired without a new byte transmission, all slaves
start listening for a new packet from the master except for the addressed slave.
The CRC-16 algorithm essentially treats the entire data stream (data bits only; start, stop and parity ignored) as one contin-
uous binary number. This number is first shifted left 16 bits and then divided by a characteristic polynomial
(11000000000000101B). The 16-bit remainder of the division is appended to the end of the packet, MSByte first. The
resulting packet including CRC, when divided by the same polynomial at the receiver will give a zero remainder if no trans-
mission errors have occurred. This algorithm requires the characteristic polynomial to be reverse bit ordered. The most sig-
nificant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder.
A C programming language implementation of the CRC algorithm will be provided upon request.
Modbus® officially defines function codes from 1 to 127 though only a small subset is generally needed. The relay supports
some of these functions, as summarized in the following table. Subsequent sections describe each function code in detail.
This function code allows the master to read one or more consecutive data registers (actual values or settings) from a relay.
Data registers are always 16-bit (two-byte) values transmitted with high order byte first. The maximum number of registers
that can be read in a single packet is 125. See the Modbus memory map table for exact details on the data registers.
Since some PLC implementations of Modbus only support one of function codes 03h and 04h. The G60 interpretation
allows either function code to be used for reading one or more consecutive data registers. The data starting address will
determine the type of data being read. Function codes 03h and 04h are therefore identical.
The following table shows the format of the master and slave packets. The example shows a master device requesting
three register values starting at address 4050h from slave device 11h (17 decimal); the slave device responds with the val-
ues 40, 300, and 0 from registers 4050h, 4051h, and 4052h, respectively.
This function code allows the master to perform various operations in the relay. Available operations are shown in the Sum-
mary of operation codes table below.
The following table shows the format of the master and slave packets. The example shows a master device requesting the
slave device 11h (17 decimal) to perform a reset. The high and low code value bytes always have the values “FF” and “00”
respectively and are a remnant of the original Modbus definition of this function code.
B
Table B–4: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE
MASTER TRANSMISSION SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX) PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11 SLAVE ADDRESS 11
FUNCTION CODE 05 FUNCTION CODE 05
OPERATION CODE - high 00 OPERATION CODE - high 00
OPERATION CODE - low 01 OPERATION CODE - low 01
CODE VALUE - high FF CODE VALUE - high FF
CODE VALUE - low 00 CODE VALUE - low 00
CRC - low DF CRC - low DF
CRC - high 6A CRC - high 6A
This function code allows the master to modify the contents of a single setting register in an relay. Setting registers are
always 16 bit (two byte) values transmitted high order byte first. The following table shows the format of the master and
slave packets. The example shows a master device storing the value 200 at memory map address 4051h to slave device
11h (17 dec).
This function code allows the master to modify the contents of a one or more consecutive setting registers in a relay. Setting
registers are 16-bit (two byte) values transmitted high order byte first. The maximum number of setting registers that can be
stored in a single packet is 60. The following table shows the format of the master and slave packets. The example shows
a master device storing the value 200 at memory map address 4051h, and the value 1 at memory map address 4052h to
slave device 11h (17 decimal).
B
Table B–7: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE
MASTER TRANSMISSION SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX) PACKET FORMAT EXMAPLE (HEX)
SLAVE ADDRESS 11 SLAVE ADDRESS 11
FUNCTION CODE 10 FUNCTION CODE 10
DATA STARTING ADDRESS - hi 40 DATA STARTING ADDRESS - hi 40
DATA STARTING ADDRESS - lo 51 DATA STARTING ADDRESS - lo 51
NUMBER OF SETTINGS - hi 00 NUMBER OF SETTINGS - hi 00
NUMBER OF SETTINGS - lo 02 NUMBER OF SETTINGS - lo 02
BYTE COUNT 04 CRC - lo 07
DATA #1 - high order byte 00 CRC - hi 64
DATA #1 - low order byte C8
DATA #2 - high order byte 00
DATA #2 - low order byte 01
CRC - low order byte 12
CRC - high order byte 62
Programming or operation errors usually happen because of illegal data in a packet. These errors result in an exception
response from the slave. The slave detecting one of these errors sends a response packet to the master with the high order
bit of the function code set to 1.
The following table shows the format of the master and slave packets. The example shows a master device sending the
unsupported function code 39h to slave device 11.
a) DESCRIPTION
The UR relay has a generic file transfer facility, meaning that you use the same method to obtain all of the different types of
files from the unit. The Modbus registers that implement file transfer are found in the "Modbus File Transfer (Read/Write)"
and "Modbus File Transfer (Read Only)" modules, starting at address 3100 in the Modbus Memory Map. To read a file from
the UR relay, use the following steps:
B 1. Write the filename to the "Name of file to read" register using a write multiple registers command. If the name is shorter
than 80 characters, you may write only enough registers to include all the text of the filename. Filenames are not case
sensitive.
2. Repeatedly read all the registers in "Modbus File Transfer (Read Only)" using a read multiple registers command. It is
not necessary to read the entire data block, since the UR relay will remember which was the last register you read. The
"position" register is initially zero and thereafter indicates how many bytes (2 times the number of registers) you have
read so far. The "size of..." register indicates the number of bytes of data remaining to read, to a maximum of 244.
3. Keep reading until the "size of..." register is smaller than the number of bytes you are transferring. This condition indi-
cates end of file. Discard any bytes you have read beyond the indicated block size.
4. If you need to re-try a block, read only the "size of.." and "block of data", without reading the position. The file pointer is
only incremented when you read the position register, so the same data block will be returned as was read in the pre-
vious operation. On the next read, check to see if the position is where you expect it to be, and discard the previous
block if it is not (this condition would indicate that the UR relay did not process your original read request).
The UR relay retains connection-specific file transfer information, so files may be read simultaneously on multiple Modbus
connections.
b) OTHER PROTOCOLS
All the files available via Modbus may also be retrieved using the standard file transfer mechanisms in other protocols (for
example, TFTP or MMS).
B 14C0
14C1
Target Sequence
Number of Targets
0 to 65535
0 to 65535
---
---
1
1
F001
F001
0
0
Element Targets (Read/Write)
14C2 Target to Read 0 to 65535 --- 1 F001 0
Element Targets (Read Only)
14C3 Target Message --- --- --- F200 “.”
Digital Input/Output States (Read Only)
1500 Contact Input States (6 items) 0 to 65535 --- 1 F500 0
1508 Virtual Input States (8 items) 0 to 65535 --- 1 F500 0
1510 Contact Output States (4 items) 0 to 65535 --- 1 F500 0
1518 Contact Output Current States (4 items) 0 to 65535 --- 1 F500 0
1520 Contact Output Voltage States (4 items) 0 to 65535 --- 1 F500 0
1528 Virtual Output States (6 items) 0 to 65535 --- 1 F500 0
1530 Contact Output Detectors (4 items) 0 to 65535 --- 1 F500 0
Remote Input/Output States (Read Only)
1540 Remote Device States 0 to 65535 --- 1 F500 0
1542 Remote Input States (4 items) 0 to 65535 --- 1 F500 0
1550 Remote Devices Online 0 to 1 --- 1 F126 0 (No)
1551 Remote Double-Point Status Input 1 State 0 to 3 --- 1 F605 3 (Bad)
1552 Remote Double-Point Status Input 2 State 0 to 3 --- 1 F605 3 (Bad)
1553 Remote Double-Point Status Input 3 State 0 to 3 --- 1 F605 3 (Bad)
1554 Remote Double-Point Status Input 4 State 0 to 3 --- 1 F605 3 (Bad)
1555 Remote Double-Point Status Input 5 State 0 to 3 --- 1 F605 3 (Bad)
Platform Direct Input/Output States (Read Only)
15C0 Direct input states (6 items) 0 to 65535 --- 1 F500 0
15C8 Direct outputs average message return time 1 0 to 65535 ms 1 F001 0
15C9 Direct outputs average message return time 2 0 to 65535 ms 1 F001 0
15CA Direct inputs/outputs unreturned message count - Ch. 1 0 to 65535 --- 1 F001 0
15CB Direct inputs/outputs unreturned message count - Ch. 2 0 to 65535 --- 1 F001 0
15D0 Direct device states 0 to 65535 --- 1 F500 0
15D1 Reserved 0 to 65535 --- 1 F001 0
15D2 Direct inputs/outputs CRC fail count 1 0 to 65535 --- 1 F001 0
15D3 Direct inputs/outputs CRC fail count 2 0 to 65535 --- 1 F001 0
Ethernet Fibre Channel Status (Read/Write)
1610 Ethernet primary fibre channel status 0 to 2 --- 1 F134 0 (Fail)
1611 Ethernet secondary fibre channel status 0 to 2 --- 1 F134 0 (Fail)
Data Logger Actuals (Read Only)
1618 Data logger channel count 0 to 16 channel 1 F001 0
1619 Time of oldest available samples 0 to 4294967295 seconds 1 F050 0
161B Time of newest available samples 0 to 4294967295 seconds 1 F050 0
161D Data logger duration 0 to 999.9 days 0.1 F001 0
Stator Differential Actuals (Read Only)
1660 Generator Differential Iad 0 to 999999.999 A 0.001 F060 0
1662 Generator Restraint Iar 0 to 999999.999 A 0.001 F060 0
1664 Generator Differential Ibd 0 to 999999.999 A 0.001 F060 0
1666 Generator Restraint Ibr 0 to 999999.999 A 0.001 F060 0
1668 Generator Differential Icd 0 to 999999.999 A 0.001 F060 0
166A Generator Restraint Icr 0 to 999999.999 A 0.001 F060 0
166C Stator Differential CT Primary 0 to 50000 --- 1 F060 1
B 1A0C
1A0E
Source 1 Phase CG Voltage Magnitude
Source 1 Phase CG Voltage Angle
0 to 999999.999
-359.9 to 0
V
degrees
0.001
0.1
F060
F002
0
0
1A0F Source 1 Phase AB or AC Voltage RMS 0 to 999999.999 V 0.001 F060 0
1A11 Source 1 Phase BC or BA Voltage RMS 0 to 999999.999 V 0.001 F060 0
1A13 Source 1 Phase CA or CB Voltage RMS 0 to 999999.999 V 0.001 F060 0
1A15 Source 1 Phase AB or AC Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A17 Source 1 Phase AB or AC Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A18 Source 1 Phase BC or BA Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A1A Source 1 Phase BC or BA Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A1B Source 1 Phase CA or CB Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A1D Source 1 Phase CA or CB Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A1E Source 1 Auxiliary Voltage RMS V F060 0
1A20 Source 1 Auxiliary Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A22 Source 1 Auxiliary Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A23 Source 1 Zero Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A25 Source 1 Zero Sequence Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A26 Source 1 Positive Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A28 Source 1 Positive Sequence Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A29 Source 1 Negative Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A2B Source 1 Negative Sequence Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A2C Reserved (20 items) --- --- --- F001 0
1A40 ...Repeated for Source 2
1A80 ...Repeated for Source 3
1AC0 ...Repeated for Source 4
1B00 ...Repeated for Source 5
1B40 ...Repeated for Source 6
Source Power (Read Only) (6 modules)
1C00 Source 1 Three Phase Real Power -1000000000000 to W 0.001 F060 0
1000000000000
1C02 Source 1 Phase A Real Power -1000000000000 to W 0.001 F060 0
1000000000000
1C04 Source 1 Phase B Real Power -1000000000000 to W 0.001 F060 0
1000000000000
1C06 Source 1 Phase C Real Power -1000000000000 to W 0.001 F060 0
1000000000000
1C08 Source 1 Three Phase Reactive Power -1000000000000 to var 0.001 F060 0
1000000000000
1C0A Source 1 Phase A Reactive Power -1000000000000 to var 0.001 F060 0
1000000000000
1C0C Source 1 Phase B Reactive Power -1000000000000 to var 0.001 F060 0
1000000000000
1C0E Source 1 Phase C Reactive Power -1000000000000 to var 0.001 F060 0
1000000000000
1C10 Source 1 Three Phase Apparent Power -1000000000000 to VA 0.001 F060 0
1000000000000
1C12 Source 1 Phase A Apparent Power -1000000000000 to VA 0.001 F060 0
1000000000000
1C14 Source 1 Phase B Apparent Power -1000000000000 to VA 0.001 F060 0
1000000000000
1C16 Source 1 Phase C Apparent Power -1000000000000 to VA 0.001 F060 0
1000000000000
1C18 Source 1 Three Phase Power Factor -0.999 to 1 --- 0.001 F013 0
1C19 Source 1 Phase A Power Factor -0.999 to 1 --- 0.001 F013 0
B 2554
2555
PMU 1 Zero Sequence Voltage Angle
PMU 1 Phase A Current Magnitude
-359.9 to 0
0 to 999999.999 A
° 0.1
0.001
F002
F060
0
0
2557 PMU 1 Phase A Current Angle -359.9 to 0 ° 0.1 F002 0
2558 PMU 1 Phase B Current Magnitude 0 to 999999.999 A 0.001 F060 0
255A PMU 1 Phase B Current Angle -359.9 to 0 ° 0.1 F002 0
255B PMU 1 Phase C Current Magnitude 0 to 999999.999 A 0.001 F060 0
255D PMU 1 Phase C Current Angle -359.9 to 0 ° 0.1 F002 0
255E PMU 1 Ground Current Magnitude 0 to 999999.999 A 0.001 F060 0
2560 PMU 1 Ground Current Angle -359.9 to 0 ° 0.1 F002 0
2561 PMU 1 Positive Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
2563 PMU 1 Positive Sequence Current Angle -359.9 to 0 ° 0.1 F002 0
2564 PMU 1 Negative Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
2566 PMU 1 Negative Sequence Current Angle -359.9 to 0 ° 0.1 F002 0
2567 PMU 1 Zero Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
2569 PMU 1 Zero Sequence Current Angle -359.9 to 0 ° 0.1 F002 0
256A PMU 1 Frequency 2 to 90 Hz 0.001 F003 0
256C PMU 1 df/dt -327.67 to 327.67 Hz/s 0.01 F002 0
256D PMU 1 Configuration Change Counter 0 to 655.35 0.01 F001 0
256E Reserved (4 items) 0 to 1 --- 1 F001 0
Phasor measurement unit integer values (read only actual value registers)
2608 PMU 1 SOC timestamp 0 to 4294967295 seconds 1 F003 0
260A PMU 1 FRAMESEC timestamp 0 to 4294967295 seconds 1 F003 0
260C PMU 1 STAT flags 0 to 4294967295 --- 1 F003 0
Remote double-point status inputs (read/write setting registers)
2620 Remote double-point status input 1 device 1 to 32 --- 1 F001 1
2621 Remote double-point status input 1 item 0 to 128 --- 1 F156 0 (None)
2622 Remote double-point status input 1 name 1 to 64 --- 1 F205 "Rem Ip 1"
2628 Remote double-point status input 1 events 0 to 1 --- 1 F102 0 (Disabled)
2629 ... Repeated for double-point status input 2
2632 ... Repeated for double-point status input 3
263B ... Repeated for double-point status input 4
2644 ... Repeated for double-point status input 5
IEC 61850 GGIO5 configuration (read/write setting registers)
26B0 IEC 61850 GGIO5 uinteger input 1 operand --- --- --- F612 0
26B1 IEC 61850 GGIO5 uinteger input 2 operand --- --- --- F612 0
26B2 IEC 61850 GGIO5 uinteger input 3 operand --- --- --- F612 0
26B3 IEC 61850 GGIO5 uinteger input 4 operand --- --- --- F612 0
26B4 IEC 61850 GGIO5 uinteger input 5 operand --- --- --- F612 0
26B5 IEC 61850 GGIO5 uinteger input 6 operand --- --- --- F612 0
26B6 IEC 61850 GGIO5 uinteger input 7 operand --- --- --- F612 0
26B7 IEC 61850 GGIO5 uinteger input 8 operand --- --- --- F612 0
26B8 IEC 61850 GGIO5 uinteger input 9 operand --- --- --- F612 0
26B9 IEC 61850 GGIO5 uinteger input 10 operand --- --- --- F612 0
26BA IEC 61850 GGIO5 uinteger input 11 operand --- --- --- F612 0
26BB IEC 61850 GGIO5 uinteger input 12 operand --- --- --- F612 0
26BC IEC 61850 GGIO5 uinteger input 13 operand --- --- --- F612 0
26BD IEC 61850 GGIO5 uinteger input 14 operand --- --- --- F612 0
26BE IEC 61850 GGIO5 uinteger input 15 operand --- --- --- F612 0
26BF IEC 61850 GGIO5 uinteger input 16 operand --- --- --- F612 0
B 30B3
30B8
Fault Report 1 Reserved (5 items)
...Repeated for Fault Report 2
--- --- --- F001 0
B 4008
400A
Command Password Entry
Setting Password Entry
0 to 4294967295
0 to 4294967295
---
---
1
1
F003
F003
0
0
Passwords (read only actual values)
4010 Command password status 0 to 1 --- 1 F102 0 (Disabled)
4011 Setting password status 0 to 1 --- 1 F102 0 (Disabled)
Passwords (read/write settings)
4012 Control password access timeout 5 to 480 minutes 1 F001 5
4013 Setting password access timeout 5 to 480 minutes 1 F001 30
4014 Invalid password attempts 2 to 5 --- 1 F001 3
4015 Password lockout duration 5 to 60 minutes 1 F001 5
4016 Password access events 0 to 1 --- 1 F102 0 (Disabled)
4017 Local setting authorization 1 to 65535 --- 1 F300 1
4018 Remote setting authorization 0 to 65535 --- 1 F300 1
4019 Access authorization timeout 5 to 480 minutes 1 F001 30
User Display Invoke (Read/Write Setting)
4040 Invoke and Scroll Through User Display Menu Operand 0 to 65535 --- 1 F300 0
LED Test (Read/Write Setting)
4048 LED Test Function 0 to 1 --- 1 F102 0 (Disabled)
4049 LED Test Control 0 to 65535 --- 1 F300 0
Preferences (Read/Write Setting)
404F Language 0 to 3 --- 1 F531 0 (English)
4050 Flash Message Time 0.5 to 10 s 0.1 F001 10
4051 Default Message Timeout 10 to 900 s 1 F001 300
4052 Default Message Intensity 0 to 3 --- 1 F101 0 (25%)
4053 Screen Saver Feature 0 to 1 --- 1 F102 0 (Disabled)
4054 Screen Saver Wait Time 1 to 65535 min 1 F001 30
4055 Current Cutoff Level 0.002 to 0.02 pu 0.001 F001 20
4056 Voltage Cutoff Level 0.1 to 1 V 0.1 F001 10
Remote RTD Communications (Read/Write Setting)
407A RRTD Slave Address 1 to 254 --- 1 F001 254
407B RRTD Baud Rate 0 to 4 --- 1 F602 4 (19200)
407D COM2 Selection 0 to 1 --- 1 F601 0 (RS485)
Communications (Read/Write Setting)
407E COM1 minimum response time 0 to 1000 ms 10 F001 0
407F COM2 minimum response time 0 to 1000 ms 10 F001 0
4080 Modbus Slave Address 1 to 254 --- 1 F001 254
4083 RS485 Com1 Baud Rate 0 to 11 --- 1 F112 8 (115200)
4084 RS485 Com1 Parity 0 to 2 --- 1 F113 0 (None)
4085 RS485 Com2 Baud Rate 0 to 11 --- 1 F112 8 (115200)
4086 RS485 Com2 Parity 0 to 2 --- 1 F113 0 (None)
4087 IP Address 0 to 4294967295 --- 1 F003 56554706
4089 IP Subnet Mask 0 to 4294967295 --- 1 F003 4294966272
408B Gateway IP Address 0 to 4294967295 --- 1 F003 56554497
408D Network Address NSAP --- --- --- F074 0
409A DNP Channel 1 Port 0 to 4 --- 1 F177 0 (None)
409B DNP Channel 2 Port 0 to 4 --- 1 F177 0 (None)
409C DNP Address 0 to 65519 --- 1 F001 1
409D Reserved 0 to 1 --- 1 F001 0
409E DNP Client Addresses (2 items) 0 to 4294967295 --- 1 F003 0
40A9
(zero means “automatic”) (2 items)
DNP Unsolicited Responses Function 0 to 1 --- 1 F102 0 (Disabled)
B
40AA DNP Unsolicited Responses Timeout 0 to 60 s 1 F001 5
40AB DNP unsolicited responses maximum retries 1 to 255 --- 1 F001 10
40AC DNP unsolicited responses destination address 0 to 65519 --- 1 F001 1
40AD Ethernet operation mode 0 to 1 --- 1 F192 0 (Half-Duplex)
40AE DNP current scale factor 0 to 8 --- 1 F194 2 (1)
40AF DNP voltage scale factor 0 to 8 --- 1 F194 2 (1)
40B0 DNP power scale factor 0 to 8 --- 1 F194 2 (1)
40B1 DNP energy scale factor 0 to 8 --- 1 F194 2 (1)
40B2 DNP power scale factor 0 to 8 --- 1 F194 2 (1)
40B3 DNP other scale factor 0 to 8 --- 1 F194 2 (1)
40B4 DNP current default deadband 0 to 65535 --- 1 F001 30000
40B6 DNP voltage default deadband 0 to 65535 --- 1 F001 30000
40B8 DNP power default deadband 0 to 65535 --- 1 F001 30000
40BA DNP energy default deadband 0 to 65535 --- 1 F001 30000
40BE DNP other default deadband 0 to 65535 --- 1 F001 30000
40C0 DNP IIN time synchronization bit period 1 to 10080 min 1 F001 1440
40C1 DNP message fragment size 30 to 2048 --- 1 F001 240
40C2 DNP client address 3 0 to 4294967295 --- 1 F003 0
40C4 DNP client address 4 0 to 4294967295 --- 1 F003 0
40C6 DNP client address 5 0 to 4294967295 --- 1 F003 0
40C8 DNP number of paired binary output control points 0 to 32 --- 1 F001 0
40C9 DNP TCP connection timeout 10 to 65535 --- 1 F001 120
40CA Reserved (22 items) 0 to 1 --- 1 F001 0
40E0 TCP port number for the IEC 60870-5-104 protocol 1 to 65535 --- 1 F001 2404
40E1 IEC 60870-5-104 protocol function 0 to 1 --- 1 F102 0 (Disabled)
40E2 IEC 60870-5-104 protocol common address of ASDU 0 to 65535 --- 1 F001 0
40E3 IEC 60870-5-104 protocol cyclic data transmit period 1 to 65535 s 1 F001 60
40E4 IEC 60870-5-104 current default threshold 0 to 65535 --- 1 F001 30000
40E6 IEC 60870-5-104 voltage default threshold 0 to 65535 --- 1 F001 30000
40E8 IEC 60870-5-104 power default threshold 0 to 65535 --- 1 F001 30000
40EA IEC 60870-5-104 energy default threshold 0 to 65535 --- 1 F001 30000
40EC IEC 60870-5-104 power default threshold 0 to 65535 --- 1 F001 30000
40EE IEC 60870-5-104 other default threshold 0 to 65535 --- 1 F001 30000
40F0 IEC 60870-5-104 client address (5 items) 0 to 4294967295 --- 1 F003 0
4104 IEC 60870-5-104 redundancy port 0 to 1 --- 1 F126 0 (No)
4005 Reserved (59 items) 0 to 1 --- 1 F001 0
4140 DNP object 1 default variation 1 to 2 --- 1 F001 2
4141 DNP object 2 default variation 1 to 3 --- 1 F001 2
4142 DNP object 20 default variation 0 to 3 --- 1 F523 0 (1)
4143 DNP object 21 default variation 0 to 3 --- 1 F524 0 (1)
4144 DNP object 22 default variation 0 to 3 --- 1 F523 0 (1)
4145 DNP object 23 default variation 0 to 3 --- 1 F523 0 (1)
4146 DNP object 30 default variation 1 to 5 --- 1 F001 1
4147 DNP object 32 default variation 0 to 5 --- 1 F525 0 (1)
Ethernet switch (Read/Write Setting)
4148 Ethernet switch IP address 0 to 4294967295 --- 1 F003 3232235778
414A Ethernet switch Modbus IP port number 1 to 65535 --- 1 F001 502
B 4445
4446
User Programmable Secondary Ethernet Fail Function
User Programmable Battery Fail Function
0 to 1
0 to 1
---
---
1
1
F102
F102
0 (Disabled)
1 (Enabled)
4447 User Programmable SNTP Fail Function 0 to 1 --- 1 F102 1 (Enabled)
4448 User Programmable IRIG-B Fail Function 0 to 1 --- 1 F102 1 (Enabled)
4449 User Programmable Ethernet Switch Fail Function 0 to 1 --- 1 F102 0 (Disabled)
CT Settings (Read/Write Setting) (6 modules)
4480 Phase CT 1 Primary 1 to 65000 A 1 F001 1
4481 Phase CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
4482 Ground CT 1 Primary 1 to 65000 A 1 F001 1
4483 Ground CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
4484 ...Repeated for CT Bank 2
4488 ...Repeated for CT Bank 3
448C ...Repeated for CT Bank 4
4490 ...Repeated for CT Bank 5
4494 ...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (3 modules)
4500 Phase VT 1 Connection 0 to 1 --- 1 F100 0 (Wye)
4501 Phase VT 1 Secondary 50 to 240 V 0.1 F001 664
4502 Phase VT 1 Ratio 1 to 24000 :1 1 F060 1
4504 Auxiliary VT 1 Connection 0 to 6 --- 1 F166 1 (Vag)
4505 Auxiliary VT 1 Secondary 50 to 240 V 0.1 F001 664
4506 Auxiliary VT 1 Ratio 1 to 24000 :1 1 F060 1
4508 ...Repeated for VT Bank 2
4510 ...Repeated for VT Bank 3
Source Settings (Read/Write Setting) (6 modules)
4580 Source 1 Name --- --- --- F206 “SRC 1"
4583 Source 1 Phase CT 0 to 63 --- 1 F400 0
4584 Source 1 Ground CT 0 to 63 --- 1 F400 0
4585 Source 1 Phase VT 0 to 63 --- 1 F400 0
4586 Source 1 Auxiliary VT 0 to 63 --- 1 F400 0
4587 ...Repeated for Source 2
458E ...Repeated for Source 3
4595 ...Repeated for Source 4
459C ...Repeated for Source 5
45A3 ...Repeated for Source 6
Power System (Read/Write Setting)
4600 Nominal Frequency 25 to 60 Hz 1 F001 60
4601 Phase Rotation 0 to 1 --- 1 F106 0 (ABC)
4602 Frequency And Phase Reference 0 to 5 --- 1 F167 0 (SRC 1)
4603 Frequency Tracking Function 0 to 1 --- 1 F102 1 (Enabled)
4604 Reverse Phase Rotation 0 to 65535 --- 1 F300 0
Breaker control (read/write settings)
4700 Breaker 1 function 0 to 1 --- 1 F102 0 (Disabled)
4701 Breaker 1 name --- --- --- F206 “Bkr 1"
4704 Breaker 1 mode 0 to 1 --- 1 F157 0 (3-Pole)
4705 Breaker 1 open 0 to 65535 --- 1 F300 0
4706 Breaker 1 close 0 to 65535 --- 1 F300 0
4707 Breaker 1 phase A / three-pole closed 0 to 65535 --- 1 F300 0
4708 Breaker 1 phase B closed 0 to 65535 --- 1 F300 0
B 5868
5870
...Repeated for FlexLogic™ Timer 14
...Repeated for FlexLogic™ Timer 15
5878 ...Repeated for FlexLogic™ Timer 16
5880 ...Repeated for FlexLogic™ Timer 17
5888 ...Repeated for FlexLogic™ Timer 18
5890 ...Repeated for FlexLogic™ Timer 19
5898 ...Repeated for FlexLogic™ Timer 20
58A0 ...Repeated for FlexLogic™ Timer 21
58A8 ...Repeated for FlexLogic™ Timer 22
58B0 ...Repeated for FlexLogic™ Timer 23
58B8 ...Repeated for FlexLogic™ Timer 24
58C0 ...Repeated for FlexLogic™ Timer 25
58C8 ...Repeated for FlexLogic™ Timer 26
58D0 ...Repeated for FlexLogic™ Timer 27
58D8 ...Repeated for FlexLogic™ Timer 28
58E0 ...Repeated for FlexLogic™ Timer 29
58E8 ...Repeated for FlexLogic™ Timer 30
58F0 ...Repeated for FlexLogic™ Timer 31
58F8 ...Repeated for FlexLogic™ Timer 32
Phase Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5900 Phase Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5901 Phase Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5902 Phase Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5903 Phase Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5904 Phase Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5905 Phase Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5906 Phase Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5907 Phase Time Overcurrent 1 Voltage Restraint 0 to 1 --- 1 F102 0 (Disabled)
5908 Phase TOC 1 Block For Each Phase (3 items) 0 to 65535 --- 1 F300 0
590B Phase Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
590C Phase Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
590D Reserved (3 items) 0 to 1 --- 1 F001 0
5910 ...Repeated for Phase Time Overcurrent 2
5920 ...Repeated for Phase Time Overcurrent 3
5930 ...Repeated for Phase Time Overcurrent 4
5940 ...Repeated for Phase Time Overcurrent 5
5950 ...Repeated for Phase Time Overcurrent 6
Phase Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5A00 Phase Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5A01 Phase Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5A02 Phase Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5A03 Phase Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5A04 Phase Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5A05 Phase IOC1 Block For Phase A 0 to 65535 --- 1 F300 0
5A06 Phase IOC1 Block For Phase B 0 to 65535 --- 1 F300 0
5A07 Phase IOC1 Block For Phase C 0 to 65535 --- 1 F300 0
5A08 Phase Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5A09 Phase Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5A0A Reserved (6 items) 0 to 1 --- 1 F001 0
B 5D09
5D0A
Ground Time Overcurrent 1 Events
Reserved (6 items)
0 to 1
0 to 1
---
---
1
1
F102
F001
0 (Disabled)
0
5D10 ...Repeated for Ground Time Overcurrent 2
5D20 ...Repeated for Ground Time Overcurrent 3
5D30 ...Repeated for Ground Time Overcurrent 4
5D40 ...Repeated for Ground Time Overcurrent 5
5D50 ...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5E00 Ground Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5E01 Ground Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5E02 Ground Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5E03 Ground Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5E04 Ground Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5E05 Ground Instantaneous Overcurrent 1 Block 0 to 65535 --- 1 F300 0
5E06 Ground Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5E07 Ground Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5E08 Reserved (8 items) 0 to 1 --- 1 F001 0
5E10 ...Repeated for Ground Instantaneous Overcurrent 2
5E20 ...Repeated for Ground Instantaneous Overcurrent 3
5E30 ...Repeated for Ground Instantaneous Overcurrent 4
5E40 ...Repeated for Ground Instantaneous Overcurrent 5
5E50 ...Repeated for Ground Instantaneous Overcurrent 6
5E60 ...Repeated for Ground Instantaneous Overcurrent 7
5E70 ...Repeated for Ground Instantaneous Overcurrent 8
5E80 ...Repeated for Ground Instantaneous Overcurrent 9
5E90 ...Repeated for Ground Instantaneous Overcurrent 10
5EA0 ...Repeated for Ground Instantaneous Overcurrent 11
5EB0 ...Repeated for Ground Instantaneous Overcurrent 12
Frequency Out-Of-Band Accumulation (Read/Write Setting)
5F40 Frequency Out-Of-Band Accumulation Block 0 to 65535 --- 1 F300 0
5F41 Frequency Out-Of-Band Accumulation Events 0 to 1 --- 1 F102 0 (Disabled)
5F42 Frequency Out-Of-Band Accumulator 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5F43 Frequency Out-Of-Band Accumulator 2 Function 0 to 1 --- 1 F102 0 (Disabled)
5F44 Frequency Out-Of-Band Accumulator 3 Function 0 to 1 --- 1 F102 0 (Disabled)
5F45 Frequency Out-Of-Band Accumulator 4 Function 0 to 1 --- 1 F102 0 (Disabled)
5F46 Frequency Out-Of-Band Accumulator 5 Function 0 to 1 --- 1 F102 0 (Disabled)
5F47 Frequency Out-Of-Band Accumulator 6 Function 0 to 1 --- 1 F102 0 (Disabled)
5F48 Frequency Out-Of-Band Accumulator 7 Function 0 to 1 --- 1 F102 0 (Disabled)
5F49 Frequency Out-Of-Band Accumulator 1 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F4A Frequency Out-Of-Band Accumulator 2 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F4B Frequency Out-Of-Band Accumulator 3 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F4C Frequency Out-Of-Band Accumulator 4 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F4D Frequency Out-Of-Band Accumulator 5 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F4E Frequency Out-Of-Band Accumulator 6 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F4F Frequency Out-Of-Band Accumulator 7 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F50 Frequency OOB Accumulation Minimum Volts/Amps 0.10 to 1.25 pu 0.01 F001 10
5F51 Frequency Out-Of-Band Accumulation Source 0 to 5 --- 1 F167 0 (SRC 1)
5F52 Frequency Out-Of-Band Accumulation Target 0 to 2 --- 1 F109 0 (Self-reset)
5F53 Frequency Out-Of-Band Accumulator 1 Time Limit 1 to 65535 s 1 F001 200
B 64D2
64D3
Overfrequency 1 Source
Overfrequency 1 Pickup
0 to 5
20 to 65
---
Hz
1
0.01
F167
F001
0 (SRC 1)
6050
64D4 Overfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 500
64D5 Overfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 500
64D6 Overfrequency 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
64D7 Overfrequency 1 Events 0 to 1 --- 1 F102 0 (Disabled)
64D8 Reserved (4 items) 0 to 1 --- 1 F001 0
64DC ...Repeated for Overfrequency 2
64E8 ...Repeated for Overfrequency 3
64F4 ...Repeated for Overfrequency 4
Power Swing Detect (Read/Write Grouped Setting)
65C0 Power Swing Detect Function 0 to 1 --- 1 F102 0 (Disabled)
65C1 Power Swing Detect Source 0 to 5 --- 1 F167 0 (SRC 1)
65C2 Power Swing Detect Mode 0 to 1 --- 1 F513 0 (Two Step)
65C3 Power Swing Detect Supervision 0.05 to 30 pu 0.001 F001 600
65C4 Power Swing Detect Forward Reach 0.1 to 500 ohms 0.01 F001 5000
65C5 Power Swing Detect Forward RCA 40 to 90 degrees 1 F001 75
65C6 Power Swing Detect Reverse Reach 0.1 to 500 ohms 0.01 F001 5000
65C7 Power Swing Detect Reverse RCA 40 to 90 degrees 1 F001 75
65C8 Power Swing Detect Outer Limit Angle 40 to 140 degrees 1 F001 120
65C9 Power Swing Detect Middle Limit Angle 40 to 140 degrees 1 F001 90
65CA Power Swing Detect Inner Limit Angle 40 to 140 degrees 1 F001 60
65CB Power Swing Detect Delay 1 Pickup 0 to 65.535 s 0.001 F001 30
65CC Power Swing Detect Delay 1 Reset 0 to 65.535 s 0.001 F001 50
65CD Power Swing Detect Delay 2 Pickup 0 to 65.535 s 0.001 F001 17
65CE Power Swing Detect Delay 3 Pickup 0 to 65.535 s 0.001 F001 9
65CF Power Swing Detect Delay 4 Pickup 0 to 65.535 s 0.001 F001 17
65D0 Power Swing Detect Seal In Delay 0 to 65.535 s 0.001 F001 400
65D1 Power Swing Detect Trip Mode 0 to 1 --- 1 F514 0 (Delayed)
65D2 Power Swing Detect Block 0 to 65535 --- 1 F300 0
65D3 Power Swing Detect Target 0 to 2 --- 1 F109 0 (Self-reset)
65D4 Power Swing Detect Event 0 to 1 --- 1 F102 0 (Disabled)
65D5 Power Swing Detect Shape 0 to 1 --- 1 F085 0 (Mho Shape)
65D6 Power Swing Detect Quad Forward Middle 0.1 to 500 ohms 0.01 F001 6000
65D7 Power Swing Detect Quad Forward Outer 0.1 to 500 ohms 0.01 F001 7000
65D8 Power Swing Detect Quad Reverse Middle 0.1 to 500 ohms 0.01 F001 6000
65D9 Power Swing Detect Quad Reverse Outer 0.1 to 500 ohms 0.01 F001 7000
65DA Power Swing Detect Outer Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DB Power Swing Detect Outer Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DC Power Swing Detect Middle Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DD Power Swing Detect Middle Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DE Power Swing Detect Inner Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DF Power Swing Detect Inner Left Blinder 0.1 to 500 ohms 0.01 F001 10000
Accidental Energization (Read/Write Grouped Setting)
6660 Accidental Energization Function 0 to 1 --- 1 F102 0 (Disabled)
6661 Accidental Energization Source 0 to 5 --- 1 F167 0 (SRC 1)
6662 Accidental Energization Arming Mode 0 to 1 --- 1 F193 0 (UV AND OFFLINE)
6663 Accidental Energization OC Pickup 0 to 3 --- 0.001 F003 300
6665 Accidental Energization UV Pickup 0 to 3 --- 0.001 F003 500
B 674C
674D
Generator Unbalance Events
Reserved (3 items)
0 to 1
0 to 65535
---
---
1
1
F102
F001
0 (Disabled)
0
Stator Ground Source (Read/Write Grouped Setting)
6750 Stator Ground Source 0 to 5 --- 1 F167 0 (SRC 1)
Stator Ground (Read/Write Grouped Setting)
6780 Stator Ground Function 0 to 1 --- 1 F102 0 (Disabled)
6781 Stator Ground Stage 1 Pickup 0 to 0.900 pu 0.001 F001 150
6782 Stator Ground Stage 1 Pickup Delay 0 to 600 s 0.01 F001 100
6783 Stator Ground Stage 1 Supervision 0.001 to 0.100 pu 0.0001 F001 57
6784 Stator Ground Stage 2 Pickup 0 to 0.900 pu 0.001 F001 150
6785 Stator Ground Stage 2 Pickup Delay 0 to 600 s 0.01 F001 0
6786 Stator Ground Stage 2 Supervision 0.001 to 0.100 pu 0.0001 F001 45
6787 Stator Ground Block --- --- --- F001 0
6788 Stator Ground Target 0 to 2 --- 1 F109 0 (Self-reset)
6789 Stator Ground Event 0 to 1 --- 1 F102 0 (Disabled)
678A Reserved (5 items) 0 to 65535 --- 1 F001 0
Split Phase Protection (Read/Write Grouped Setting)
67A0 Split Phase Protection Function 0 to 1 --- 1 F102 0 (Disabled)
67A1 Split Phase Protection Source 0 to 5 --- 1 F167 0 (SRC1)
67A2 Split Phase Protection Load Source 0 to 5 --- 1 F167 0 (SRC1)
67A3 Split Phase Protection Phase A Pickup 0.020 to 1.500 pu 0.001 F001 200
67A4 Split Phase Protection Phase A Offset 0 to 1 pu 0.001 F001 0
67A5 Split Phase Protection Phase A Slope 0 to 100 % 0.1 F001 0
67A6 Split Phase Protection Phase B Pickup 0.020 to 1.500 pu 0.001 F001 200
67A7 Split Phase Protection Phase B Offset 0 to 1 pu 0.001 F001 0
67A8 Split Phase Protection Phase B Slope 0 to 100 % 0.1 F001 0
67A9 Split Phase Protection Phase C Pickup 0.020 to 1.500 pu 0.001 F001 200
67AA Split Phase Protection Phase C Offset 0 to 1 pu 0.001 F001 0
67AB Split Phase Protection Phase C Slope 0 to 100 % 0.1 F001 0
67AC Split Phase Protection Minimum Load 0 to 1 pu 0.01 F001 0
67AD Split Phase Protection Mode 0 to 1 --- 1 F225 0 (Over)
67AE Split Phase Protection Delay 0 to 65.535 s 0.001 F001 0
67AF Split Phase Protection Block 0 to 65535 --- 1 F300 0
67B0 Split Phase Protection Target 0 to 2 --- 1 F109 0 (Self-Reset)
67B1 Split Phase Protection Events 0 to 1 --- 1 F102 0 (Disabled)
67B2 Reserved (6 items) 0 to 65535 --- 1 F001 0
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000 Phase Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7001 Phase Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7002 Phase Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7003 Phase Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)
7004 Phase Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7005 Phase Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
7006 Phase Undervoltage 1 Block 0 to 65535 --- 1 F300 0
7007 Phase Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7008 Phase Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7009 Phase Undervoltage 1 Measurement Mode 0 to 1 --- 1 F186 0 (Phase to Ground)
700A Reserved (6 items) 0 to 1 --- 1 F001 0
7013 ...Repeated for Phase Undervoltage 2
B 728B
728C
Neutral Directional Overcurrent 1 Polarizing Voltage
Neutral Directional Overcurrent 1 Op Current
0 to 1
0 to 1
---
---
1
1
F231
F196
0 (Calculated V0)
0 (Calculated 3I0)
728D Neutral Directional Overcurrent 1 Offset 0 to 250 ohms 0.01 F001 0
728E Neutral Directional Overcurrent 1 Pos Seq Restraint 0 to 0.5 --- 0.001 F001 63
728F Reserved 0 to 1 --- 1 F001 0
7290 ...Repeated for Neutral Directional Overcurrent 2
Negative-sequence directional overcurrent (read/write grouped settings) (2 modules)
72A0 Negative Sequence Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
72A1 Negative Sequence Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
72A2 Negative Sequence Directional Overcurrent 1 Type 0 to 1 --- 1 F179 0 (Neg Sequence)
72A3 Neg Sequence Directional Overcurrent 1 Forward ECA 0 to 90 ° Lag 1 F002 75
72A4 Neg Seq Directional Overcurrent 1 Forward Limit Angle 40 to 90 degrees 1 F001 90
72A5 Neg Sequence Directional Overcurrent 1 Forward Pickup 0.015 to 30 pu 0.05 F001 5
72A6 Neg Seq Directional Overcurrent 1 Reverse Limit Angle 40 to 90 degrees 1 F001 90
72A7 Neg Sequence Directional Overcurrent 1 Reverse Pickup 0.015 to 30 pu 0.05 F001 5
72A8 Negative Sequence Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
72A9 Negative Sequence Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 0
72AA Negative Sequence Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
72AB Negative Sequence Directional Overcurrent 1 Offset 0 to 250 ohms 0.01 F001 0
72AC Neg Seq Directional Overcurrent 1 Pos Seq Restraint 0 to 0.5 --- 0.001 F001 63
72AD Reserved (3 items) 0 to 1 --- 1 F001 0
72B0 ...Repeated for Neg Seq Directional Overcurrent 2
dcmA Inputs (Read/Write Setting) (24 modules)
7300 dcmA Inputs 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7301 dcmA Inputs 1 ID --- --- --- F205 “DCMA I 1"
7307 Reserved 1 (4 items) 0 to 65535 --- 1 F001 0
730B dcmA Inputs 1 Units --- --- --- F206 “mA”
730E dcmA Inputs 1 Range 0 to 6 --- 1 F173 6 (4 to 20 mA)
730F dcmA Inputs 1 Minimum Value -9999.999 to 9999.999 --- 0.001 F004 4000
7311 dcmA Inputs 1 Maximum Value -9999.999 to 9999.999 --- 0.001 F004 20000
7313 Reserved (5 items) 0 to 65535 --- 1 F001 0
7318 ...Repeated for dcmA Inputs 2
7330 ...Repeated for dcmA Inputs 3
7348 ...Repeated for dcmA Inputs 4
7360 ...Repeated for dcmA Inputs 5
7378 ...Repeated for dcmA Inputs 6
7390 ...Repeated for dcmA Inputs 7
73A8 ...Repeated for dcmA Inputs 8
73C0 ...Repeated for dcmA Inputs 9
73D8 ...Repeated for dcmA Inputs 10
73F0 ...Repeated for dcmA Inputs 11
7408 ...Repeated for dcmA Inputs 12
7420 ...Repeated for dcmA Inputs 13
7438 ...Repeated for dcmA Inputs 14
7450 ...Repeated for dcmA Inputs 15
7468 ...Repeated for dcmA Inputs 16
7480 ...Repeated for dcmA Inputs 17
7498 ...Repeated for dcmA Inputs 18
74B0 ...Repeated for dcmA Inputs 19
B 7866
7869
PMU 1 Power Trigger Block (3 items)
PMU 1 Power Trigger Target
0 to 65535
0 to 2
---
---
1
1
F300
F109
0
0 (Self-reset)
786A PMU 1 Power Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
786B ...Repeated for PMU 2
7876 ...Repeated for PMU 3
7881 ...Repeated for PMU 4
Phasor Measurement Unit Voltage Trigger (Read/Write Setting)
788C PMU 1 Voltage Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
788D PMU 1 Voltage Trigger Low Voltage 0.25 to 1.25 pu 0.001 F001 800
788E PMU 1 Voltage Trigger High Voltage 0.75 to 1.75 pu 0.001 F001 1200
788F PMU 1 Voltage Trigger Pickup Time 0 to 600 s 0.01 F001 10
7890 PMU 1 Voltage Trigger Dropout Time 0 to 600 s 0.01 F001 100
7891 PMU 1 Voltage Trigger Block (3 items) 0 to 65535 --- 1 F300 0
7894 PMU 1 Voltage Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
7895 PMU 1 Voltage Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit One-shot Command (Read/Write Setting)
78B4 PMU One-shot Function 0 to 1 --- 1 F102 0 (Disabled)
78B5 PMU One-shot Sequence Number 0 to 59 --- 1 F001 1
78B6 PMU One-shot Time 0 to 235959 --- 1 F050 0
Phasor Measurement Unit Test Values (Read/Write Setting)
78B8 PMU 1 Test Function 0 to 1 --- 1 F102 0 (Disabled)
78B9 PMU 1 Phase A Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
78BB PMU 1 Phase A Voltage Test Angle -180 to 180 ° 0.05 F002 0
78BC PMU 1 Phase B Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
78BE PMU 1 Phase B Voltage Test Angle -180 to 180 ° 0.05 F002 -120
78BF PMU 1 Phase C Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
78C1 PMU 1 Phase C Voltage Test Angle -180 to 180 ° 0.05 F002 120
78C2 PMU 1 Auxiliary Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
78C4 PMU 1 Auxiliary Voltage Test Angle -180 to 180 ° 0.05 F002 0
78C5 PMU 1 Phase A Current Test Magnitude 0 to 9.999 kA 0.001 F004 1000
78C7 PMU 1 Phase A Current Test Angle -180 to 180 ° 0.05 F002 -10
78C8 PMU 1 Phase B Current Test Magnitude 0 to 9.999 kA 0.001 F004 1000
78CA PMU 1 Phase B Current Test Angle -180 to 180 ° 0.05 F002 -130
78CB PMU 1 Phase C Current Test Magnitude 0 to 9.999 kA 0.001 F003 1000
78CD PMU 1 Phase C Current Test Angle -180 to 180 ° 0.05 F002 110
78CE PMU 1 Ground Current Test Magnitude 0 to 9.999 kA 0.001 F004 0
78D0 PMU 1 Ground Current Test Angle -180 to 180 ° 0.05 F002 0
78D1 PMU 1 Test Frequency 20 to 70 Hz 0.001 F003 60000
78D3 PMU 1 Test df/dt -10 to 10 Hz/s 0.001 F002 0
Phasor Measurement Unit Recorder Configuration Counter Command (Read/Write Command)
7928 PMU 1 Recorder Clear Configuration Counter 0 to 1 --- 1 F126 0 (No)
Phasor Measurement Unit Recording Values (Read Only)
792C PMU 1 Available Records 0 to 65535 --- 1 F001 0
792D PMU 1 Second Per Record 0 to 6553.5 --- 0.1 F001 0
792F PMU 1 Last Cleared Date 0 to 400000000 --- 1 F050 0
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
7940 PMU Network Reporting Function 0 to 1 --- 1 F102 0 (Disabled)
7941 PMU Network Reporting ID Code 1 to 65534 --- 1 F001 1
7942 PMU Network Reporting Rate 0 to 11 --- 1 F544 3 (10/sec.)
B 7A6D
7A6E
Field Ground STG1 Pickup
Field Ground STG1 Delay
1 to 500
0.1 to 600
kohms
s
1
0.1
F001
F001
20
100
7A6F Field Ground STG2 Pickup 1 to 500 kohms 1 F001 5
7A70 Field Ground STG2 Delay 0.1 to 600 s 0.1 F001 30
7A71 Field Ground UC Pickup 0.05 to 100 mA 0.01 F001 100
7A72 Field Ground UC Delay 0.1 to 600 s 0.01 F001 100
7A73 Field Ground Block 0 to 65535 --- 1 F300 0
7A74 Field Ground Target 0 to 2 --- 1 F109 0 (Self-reset)
7A75 Field Ground Events 0 to 1 --- 1 F102 0 (Disabled)
User Programmable Pushbuttons (Read/Write Setting) (16 modules)
7B60 User Programmable Pushbutton 1 Function 0 to 2 --- 1 F109 2 (Disabled)
7B61 User Programmable Pushbutton 1 Top Line --- --- --- F202 (none)
7B6B User Programmable Pushbutton 1 On Text --- --- --- F202 (none)
7B75 User Programmable Pushbutton 1 Off Text --- --- --- F202 (none)
7B7F User Programmable Pushbutton 1 Drop-Out Time 0 to 60 s 0.05 F001 0
7B80 User Programmable Pushbutton 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7B81 User Programmable Pushbutton 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7B82 User Programmable Pushbutton 1 LED Operand 0 to 65535 --- 1 F300 0
7B83 User Programmable Pushbutton 1 Autoreset Delay 0 to 600 s 0.05 F001 0
7B84 User Programmable Pushbutton 1 Autoreset Function 0 to 1 --- 1 F102 0 (Disabled)
7B85 User Programmable Pushbutton 1 Local Lock 0 to 65535 --- 1 F300 0
7B86 User Programmable Pushbutton 1 Message Priority 0 to 2 --- 1 F220 0 (Disabled)
7B87 User Programmable Pushbutton 1 Remote Lock 0 to 65535 --- 1 F300 0
7B88 User Programmable Pushbutton 1 Reset 0 to 65535 --- 1 F300 0
7B89 User Programmable Pushbutton 1 Set 0 to 65535 --- 1 F300 0
7B8A User Programmable Pushbutton 1 Hold 0 to 10 s 0.1 F001 1
7B8B ...Repeated for User Programmable Pushbutton 2
7BB6 ...Repeated for User Programmable Pushbutton 3
7BE1 ...Repeated for User Programmable Pushbutton 4
7C0C ...Repeated for User Programmable Pushbutton 5
7C37 ...Repeated for User Programmable Pushbutton 6
7C62 ...Repeated for User Programmable Pushbutton 7
7C8D ...Repeated for User Programmable Pushbutton 8
7CB8 ...Repeated for User Programmable Pushbutton 9
7CE3 ...Repeated for User Programmable Pushbutton 10
7D0E ...Repeated for User Programmable Pushbutton 11
7D39 ...Repeated for User Programmable Pushbutton 12
7D64 ...Repeated for User Programmable Pushbutton 13
7D8F ...Repeated for User Programmable Pushbutton 14
7DBA ...Repeated for User Programmable Pushbutton 15
7DE5 ...Repeated for User Programmable Pushbutton 16
Underfrequency (Read/Write Setting) (6 modules)
7E10 Underfrequency Function 0 to 1 --- 1 F102 0 (Disabled)
7E11 Underfrequency 1 Block 0 to 65535 --- 1 F300 0
7E12 Underfrequency 1 Minimum Current 0.1 to 1.25 pu 0.01 F001 10
7E13 Underfrequency 1 Pickup 20 to 65 Hz 0.01 F001 5950
7E14 Underfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 2000
7E15 Underfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 2000
7E16 Underfrequency 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
B 8401
8403
EGD Fast Producer Exchange 1 Destination
EGD Fast Producer Exchange 1 Data Rate
0 to 4294967295
50 to 1000
---
ms
1
50
F003
F001
0
1000
8404 EGD Fast Producer Exchange 1 Data Item 1 (20 items) 0 to 65535 --- 1 F001 0
8418 Reserved (80 items) --- --- --- F001 0
EGD Slow Production (Read/Write Setting) (2 modules)
8500 EGD Slow Producer Exchange 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8501 EGD Fast Producer Exchange 1 Destination 0 to 4294967295 --- 1 F003 0
8503 EGD Slow Producer Exchange 1 Data Rate 500 to 1000 ms 50 F001 1000
8504 EGD Slow Producer Exchange 1 Data Item 1 (50 items) 0 to 65535 --- 1 F001 0
8536 Reserved (50 items) --- --- --- F001 0
8568 ...Repeated for EGD Exchange 2
Remote RTD inputs (Read/Write Grouped Setting) (12 modules)
86D0 Remote RTD 1 Function 0 to 1 --- 1 F102 0 (Disabled)
86D1 Remote RTD 1 ID --- --- --- F205 "RRTD 1"
86D7 Remote RTD 1 Type 0 to 3 --- 1 F174 0 (100 ohm Platinum)
86D8 Remote RTD 1 Application 0 to 5 --- 1 F550 0 (None)
86D9 Remote RTD 1 Alarm Temperature 1 to 200 °C 1 F001 130
86DA Remote RTD 1 Alarm Pickup Delay 5 to 600 seconds 5 F001 5
86DB Remote RTD 1 Trip Temperature 1 to 200 °C 1 F001 130
86DC Remote RTD 1 Trip Pickup Delay 5 to 600 seconds 5 F001 5
86DD Remote RTD 1 Trip Reset Delay 5 to 600 seconds 5 F001 5
86DE Remote RTD 1 Trip Voting 0 to 13 --- 1 F603 0 (None)
86DF Remote RTD 1 Block 0 to 65535 --- 1 F300 0
86E0 Remote RTD 1 Open 0 to 2 --- 1 F552 0 (None)
86E1 Remote RTD 1 Target 0 to 2 --- 1 F109 0 (Self-Reset)
86E2 Remote RTD 1 Events 0 to 1 --- 1 F102 0 (Disabled)
86E3 Repeatead for remote RTD input 2
86F6 Repeatead for remote RTD input 3
8709 Repeatead for remote RTD input 4
871C Repeatead for remote RTD input 5
872F Repeatead for remote RTD input 6
8742 Repeatead for remote RTD input 7
8755 Repeatead for remote RTD input 8
8768 Repeatead for remote RTD input 9
877B Repeatead for remote RTD input 10
878E Repeatead for remote RTD input 11
87A1 Repeatead for remote RTD input 12
Remote RTD inputs (Read Only Actual Values)
87C0 Remote RTD 1 Value 0 to 200 °C 1 F002 0
87C1 Remote RTD 2 Value 0 to 200 °C 1 F002 0
87C2 Remote RTD 3 Value 0 to 200 °C 1 F002 0
87C3 Remote RTD 4 Value 0 to 200 °C 1 F002 0
87C4 Remote RTD 5 Value 0 to 200 °C 1 F002 0
87C5 Remote RTD 6 Value 0 to 200 °C 1 F002 0
87C6 Remote RTD 7 Value 0 to 200 °C 1 F002 0
87C7 Remote RTD 8 Value 0 to 200 °C 1 F002 0
87C8 Remote RTD 9 Value 0 to 200 °C 1 F002 0
87C9 Remote RTD 10 Value 0 to 200 °C 1 F002 0
87CA Remote RTD 11 Value 0 to 200 °C 1 F002 0
B 8D98
8DAC
...Repeated for Digital Element 47
...Repeated for Digital Element 48
Trip Bus (Read/Write Setting)
8E00 Trip Bus 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8E01 Trip Bus 1 Block --- --- --- F300 0
8E02 Trip Bus 1 Pickup Delay 0 to 600 s 0.01 F001 0
8E03 Trip Bus 1 Reset Delay 0 to 600 s 0.01 F001 0
8E04 Trip Bus 1 Input 1 0 to 65535 --- 1 F300 0
8E05 Trip Bus 1 Input 2 0 to 65535 --- 1 F300 0
8E06 Trip Bus 1 Input 3 0 to 65535 --- 1 F300 0
8E07 Trip Bus 1 Input 4 0 to 65535 --- 1 F300 0
8E08 Trip Bus 1 Input 5 0 to 65535 --- 1 F300 0
8E09 Trip Bus 1 Input 6 0 to 65535 --- 1 F300 0
8E0A Trip Bus 1 Input 7 0 to 65535 --- 1 F300 0
8E0B Trip Bus 1 Input 8 0 to 65535 --- 1 F300 0
8E0C Trip Bus 1 Input 9 0 to 65535 --- 1 F300 0
8E0D Trip Bus 1 Input 10 0 to 65535 --- 1 F300 0
8E0E Trip Bus 1 Input 11 0 to 65535 --- 1 F300 0
8E0F Trip Bus 1 Input 12 0 to 65535 --- 1 F300 0
8E10 Trip Bus 1 Input 13 0 to 65535 --- 1 F300 0
8E11 Trip Bus 1 Input 14 0 to 65535 --- 1 F300 0
8E12 Trip Bus 1 Input 15 0 to 65535 --- 1 F300 0
8E13 Trip Bus 1 Input 16 0 to 65535 --- 1 F300 0
8E14 Trip Bus 1 Latching 0 to 1 --- 1 F102 0 (Disabled)
8E15 Trip Bus 1 Reset 0 to 65535 --- 1 F300 0
8E16 Trip Bus 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
8E16 Trip Bus 1 Events 0 to 1 --- 1 F102 0 (Disabled)
8E18 Reserved (8 items) --- --- --- F001 0
8E20 ...Repeated for Trip Bus 2
8E40 ...Repeated for Trip Bus 3
8E60 ...Repeated for Trip Bus 4
8E80 ...Repeated for Trip Bus 5
8EA0 ...Repeated for Trip Bus 6
FlexElement (Read/Write Setting) (16 modules)
9000 FlexElement™ 1 Function 0 to 1 --- 1 F102 0 (Disabled)
9001 FlexElement™ 1 Name --- --- --- F206 “FxE 1”
9004 FlexElement™ 1 InputP 0 to 65535 --- 1 F600 0
9005 FlexElement™ 1 InputM 0 to 65535 --- 1 F600 0
9006 FlexElement™ 1 Compare 0 to 1 --- 1 F516 0 (LEVEL)
9007 FlexElement™ 1 Input 0 to 1 --- 1 F515 0 (SIGNED)
9008 FlexElement™ 1 Direction 0 to 1 --- 1 F517 0 (OVER)
9009 FlexElement™ 1 Hysteresis 0.1 to 50 % 0.1 F001 30
900A FlexElement™ 1 Pickup -90 to 90 pu 0.001 F004 1000
900C FlexElement™ 1 DeltaT Units 0 to 2 --- 1 F518 0 (Milliseconds)
900D FlexElement™ 1 DeltaT 20 to 86400 --- 1 F003 20
900F FlexElement™ 1 Pickup Delay 0 to 65.535 s 0.001 F001 0
9010 FlexElement™ 1 Reset Delay 0 to 65.535 s 0.001 F001 0
9011 FlexElement™ 1 Block 0 to 65535 --- 1 F300 0
9012 FlexElement™ 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
B 949C
94A8
...Repeated for Direct Input/Output 14
...Repeated for Direct Input/Output 15
94B4 ...Repeated for Direct Input/Output 16
94C0 ...Repeated for Direct Input/Output 17
94CC ...Repeated for Direct Input/Output 18
94D8 ...Repeated for Direct Input/Output 19
94E4 ...Repeated for Direct Input/Output 20
94F0 ...Repeated for Direct Input/Output 21
94FC ...Repeated for Direct Input/Output 22
9508 ...Repeated for Direct Input/Output 23
9514 ...Repeated for Direct Input/Output 24
9520 ...Repeated for Direct Input/Output 25
952C ...Repeated for Direct Input/Output 26
9538 ...Repeated for Direct Input/Output 27
9544 ...Repeated for Direct Input/Output 28
9550 ...Repeated for Direct Input/Output 29
955C ...Repeated for Direct Input/Output 30
9568 ...Repeated for Direct Input/Output 31
9574 ...Repeated for Direct Input/Output 32
IEC 61850 received integers (read/write setting registers)
9910 IEC61850 GOOSE UInteger 1 default value 0 to 429496295 --- 1 F003 1000
9912 IEC61850 GOOSE UInteger input 1 mode 0 to 1 --- 1 F491 0 (Default Value)
9913 ...Repeated for IEC61850 GOOSE UInteger 2
9916 ...Repeated for IEC61850 GOOSE UInteger 3
9919 ...Repeated for IEC61850 GOOSE UInteger 4
991C ...Repeated for IEC61850 GOOSE UInteger 5
991F ...Repeated for IEC61850 GOOSE UInteger 6
9922 ...Repeated for IEC61850 GOOSE UInteger 7
9925 ...Repeated for IEC61850 GOOSE UInteger 8
9928 ...Repeated for IEC61850 GOOSE UInteger 9
992B ...Repeated for IEC61850 GOOSE UInteger 10
992E ...Repeated for IEC61850 GOOSE UInteger 11
9931 ...Repeated for IEC61850 GOOSE UInteger 12
9934 ...Repeated for IEC61850 GOOSE UInteger 13
9937 ...Repeated for IEC61850 GOOSE UInteger 14
993A ...Repeated for IEC61850 GOOSE UInteger 15
993D ...Repeated for IEC61850 GOOSE UInteger 16
FlexElement Actuals (Read Only) (16 modules)
9A01 FlexElement™ 1 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A03 FlexElement™ 2 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A05 FlexElement™ 3 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A07 FlexElement™ 4 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A09 FlexElement™ 5 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A0B FlexElement™ 6 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A0D FlexElement™ 7 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A0F FlexElement™ 8 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A11 FlexElement™ 9 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A13 FlexElement™ 10 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A15 FlexElement™ 11 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
B AA31
AA38
...Repeated for IEC 61850 GOOSE analog input 8
...Repeated for IEC 61850 GOOSE analog input 9
AA3F ...Repeated for IEC 61850 GOOSE analog input 10
AA46 ...Repeated for IEC 61850 GOOSE analog input 11
AA4D ...Repeated for IEC 61850 GOOSE analog input 12
AA54 ...Repeated for IEC 61850 GOOSE analog input 13
AA5B ...Repeated for IEC 61850 GOOSE analog input 14
AA62 ...Repeated for IEC 61850 GOOSE analog input 15
AA69 ...Repeated for IEC 61850 GOOSE analog input 16
IEC 61850 XCBR configuration (read/write settings)
AB24 Operand for IEC 61850 XCBR1.ST.Loc status 0 to 65535 --- 1 F300 0
AB25 Command to clear XCBR1 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB26 Operand for IEC 61850 XCBR2.ST.Loc status 0 to 65535 --- 1 F300 0
AB27 Command to clear XCBR2 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB28 Operand for IEC 61850 XCBR3.ST.Loc status 0 to 65535 --- 1 F300 0
AB29 Command to clear XCBR3 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB2A Operand for IEC 61850 XCBR4.ST.Loc status 0 to 65535 --- 1 F300 0
AB2B Command to clear XCBR4 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB2C Operand for IEC 61850 XCBR5.ST.Loc status 0 to 65535 --- 1 F300 0
AB2D Command to clear XCBR5 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB2E Operand for IEC 61850 XCBR6.ST.Loc status 0 to 65535 --- 1 F300 0
AB2F Command to clear XCBR6 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
IEC 61850 LN name prefixes (read/write settings)
AB30 IEC 61850 logical node LPHD1 name prefix 0 to 65534 --- 1 F206 (none)
AB33 IEC 61850 logical node PIOCx name prefix (72 items) 0 to 65534 --- 1 F206 (none)
AC0B IEC 61850 logical node PTOCx name prefix (24 items) 0 to 65534 --- 1 F206 (none)
AC53 IEC 61850 logical node PTUVx name prefix (13 items) 0 to 65534 --- 1 F206 (none)
AC7A IEC 61850 logical node PTOVx name prefix (10 items) 0 to 65534 --- 1 F206 (none)
AC98 IEC 61850 logical node PDISx name prefix (10 items) 0 to 65534 --- 1 F206 (none)
ACB6 IEC 61850 logical node RBRFx name prefix (24 items) 0 to 65534 --- 1 F206 (none)
ACFE IEC 61850 logical node RPSBx name prefix 0 to 65534 --- 1 F206 (none)
AD01 IEC 61850 logical node RRECx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD13 IEC 61850 logical node MMXUx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD25 IEC 61850 logical node GGIOx name prefix (5 items) 0 to 65534 --- 1 F206 (none)
AD34 IEC 61850 logical node RFLOx name prefix (5 items) 0 to 65534 --- 1 F206 (none)
AD43 IEC 61850 logical node XCBRx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD55 IEC 61850 logical node PTRCx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD67 IEC 61850 logical node PDIFx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD73 IEC 61850 logical node MMXNx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
ADE2 IEC 61850 logical node CSWIx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AE3C IEC 61850 logical node XSWIx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
IEC 61850 XSWI configuration (read/write settings)
AECF Operand for IEC 61850 XSWI1.ST.Loc status 0 to 65535 --- 1 F300 0
AED0 Command to clear XSWI1 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AED1 Repeated for IEC 61850 XSWI2
AED3 Repeated for IEC 61850 XSWI3
AED5 Repeated for IEC 61850 XSWI4
AED7 Repeated for IEC 61850 XSWI5
AED9 Repeated for IEC 61850 XSWI6
B AB33
AC0B
IEC 61850 Logical Node PIOCx Name Prefix (72 items)
IEC 61850 Logical Node PTOCx Name Prefix (24 items)
0 to 65534
0 to 65534
---
---
1
1
F206
F206
(None)
(None)
AC53 IEC 61850 Logical Node PTUVx Name Prefix (12 items) 0 to 65534 --- 1 F206 (None)
AC77 IEC 61850 Logical Node PTOVx Name Prefix (8 items) 0 to 65534 --- 1 F206 (None)
AC8F IEC 61850 Logical Node PDISx Name Prefix (10 items) 0 to 65534 --- 1 F206 (None)
ACAD IEC 61850 Logical Node RRBFx Name Prefix (24 items) 0 to 65534 --- 1 F206 (None)
ACF5 IEC 61850 Logical Node RPSBx Name Prefix 0 to 65534 --- 1 F206 (None)
ACF8 IEC 61850 Logical Node RRECx Name Prefix (6 items) 0 to 65534 --- 1 F206 (None)
AD0A IEC 61850 Logical Node MMXUx Name Prefix (6 items) 0 to 65534 --- 1 F206 (None)
AD1C IEC 61850 Logical Node GGIOx Name Prefix (4 items) 0 to 65534 --- 1 F206 (None)
AD28 IEC 61850 Logical Node RFLOx Name Prefix (5 items) 0 to 65534 --- 1 F206 (None)
AD37 IEC 61850 Logical Node XCBRx Name Prefix (2 items) 0 to 65534 --- 1 F206 (None)
AD3D IEC 61850 Logical Node PTRCx Name Prefix (2 items) 0 to 65534 --- 1 F206 (None)
AD43 IEC 61850 Logical Node PDIFx Name Prefix (4 items) 0 to 65534 --- 1 F206 (None)
AD4F IEC 61850 Logical Node MMXNx Name Prefix (37 items) 0 to 65534 --- 1 F206 (None)
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
B01C Default GOOSE/GSSE Update Time 1 to 60 s 1 F001 60
B01D IEC 61850 GSSE Function (GsEna) 0 to 1 --- 1 F102 1 (Enabled)
B013 IEC 61850 GSSE ID --- --- --- F209 “GSSEOut”
B03F IEC 61850 GOOSE Function (GoEna) 0 to 1 --- 1 F102 0 (Disabled)
B040 IEC 61850 GSSE Destination MAC Address --- --- --- F072 0
B043 IEC 61850 Standard GOOSE ID --- --- --- F209 “GOOSEOut”
B064 IEC 61850 Standard GOOSE Destination MAC Address --- --- --- F072 0
B067 IEC 61850 GOOSE VLAN Transmit Priority 0 to 7 --- 1 F001 4
B068 IEC 61850 GOOSE VLAN ID 0 to 4095 --- 1 F001 0
B069 IEC 61850 GOOSE ETYPE APPID 0 to 16383 --- 1 F001 0
B06A Reserved (2 items) 0 to 1 --- 1 F001 0
IEC 61850 Server Configuration (Read/Write Settings/Commands)
B06C TCP Port Number for the IEC 61850 / MMS Protocol 1 to 65535 --- 1 F001 102
B06D IEC 61850 Logical Device Name --- --- --- F213 “IECName”
B07D IEC 61850 Logical Device Instance --- --- --- F213 “LDInst”
B08D IEC 61850 LPHD Location --- --- --- F204 “Location”
B0B5 Include non-IEC 61850 Data 0 to 1 --- 1 F102 0 (Disabled)
B06B IEC 61850 Server Data Scanning Function 0 to 1 --- 1 F102 0 (Disabled)
B0B7 Reserved (15 items)
IEC 61850 MMXU Deadbands (Read/Write Setting) (6 modules)
B0C0 IEC 61850 MMXU TotW Deadband 1 0.001 to 100 % 0.001 F003 10000
B0C2 IEC 61850 MMXU TotVAr Deadband 1 0.001 to 100 % 0.001 F003 10000
B0C4 IEC 61850 MMXU TotVA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0C6 IEC 61850 MMXU TotPF Deadband 1 0.001 to 100 % 0.001 F003 10000
B0C8 IEC 61850 MMXU Hz Deadband 1 0.001 to 100 % 0.001 F003 10000
B0CA IEC 61850 MMXU PPV.phsAB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0CC IEC 61850 MMXU PPV.phsBC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0CE IEC 61850 MMXU PPV.phsCA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0D0 IEC 61850 MMXU PhV.phsADeadband 1 0.001 to 100 % 0.001 F003 10000
B0D2 IEC 61850 MMXU PhV.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0D4 IEC 61850 MMXU PhV.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0D6 IEC 61850 MMXU A.phsA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0D8 IEC 61850 MMXU A.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B BB28
BB30
...Repeated for Contact Input 6
...Repeated for Contact Input 7
BB38 ...Repeated for Contact Input 8
BB40 ...Repeated for Contact Input 9
BB48 ...Repeated for Contact Input 10
BB50 ...Repeated for Contact Input 11
BB58 ...Repeated for Contact Input 12
BB60 ...Repeated for Contact Input 13
BB68 ...Repeated for Contact Input 14
BB70 ...Repeated for Contact Input 15
BB78 ...Repeated for Contact Input 16
BB80 ...Repeated for Contact Input 17
BB88 ...Repeated for Contact Input 18
BB90 ...Repeated for Contact Input 19
BB98 ...Repeated for Contact Input 20
BBA0 ...Repeated for Contact Input 21
BBA8 ...Repeated for Contact Input 22
BBB0 ...Repeated for Contact Input 23
BBB8 ...Repeated for Contact Input 24
BBC0 ...Repeated for Contact Input 25
BBC8 ...Repeated for Contact Input 26
BBD0 ...Repeated for Contact Input 27
BBD8 ...Repeated for Contact Input 28
BBE0 ...Repeated for Contact Input 29
BBE8 ...Repeated for Contact Input 30
BBF0 ...Repeated for Contact Input 31
BBF8 ...Repeated for Contact Input 32
BC00 ...Repeated for Contact Input 33
BC08 ...Repeated for Contact Input 34
BC10 ...Repeated for Contact Input 35
BC18 ...Repeated for Contact Input 36
BC20 ...Repeated for Contact Input 37
BC28 ...Repeated for Contact Input 38
BC30 ...Repeated for Contact Input 39
BC38 ...Repeated for Contact Input 40
BC40 ...Repeated for Contact Input 41
BC48 ...Repeated for Contact Input 42
BC50 ...Repeated for Contact Input 43
BC58 ...Repeated for Contact Input 44
BC60 ...Repeated for Contact Input 45
BC68 ...Repeated for Contact Input 46
BC70 ...Repeated for Contact Input 47
BC78 ...Repeated for Contact Input 48
BC80 ...Repeated for Contact Input 49
BC88 ...Repeated for Contact Input 50
BC90 ...Repeated for Contact Input 51
BC98 ...Repeated for Contact Input 52
BCA0 ...Repeated for Contact Input 53
BCA8 ...Repeated for Contact Input 54
B BEA8
BEB4
...Repeated for Virtual Input 11
...Repeated for Virtual Input 12
BEC0 ...Repeated for Virtual Input 13
BECC ...Repeated for Virtual Input 14
BED8 ...Repeated for Virtual Input 15
BEE4 ...Repeated for Virtual Input 16
BEF0 ...Repeated for Virtual Input 17
BEFC ...Repeated for Virtual Input 18
BF08 ...Repeated for Virtual Input 19
BF14 ...Repeated for Virtual Input 20
BF20 ...Repeated for Virtual Input 21
BF2C ...Repeated for Virtual Input 22
BF38 ...Repeated for Virtual Input 23
BF44 ...Repeated for Virtual Input 24
BF50 ...Repeated for Virtual Input 25
BF5C ...Repeated for Virtual Input 26
BF68 ...Repeated for Virtual Input 27
BF74 ...Repeated for Virtual Input 28
BF80 ...Repeated for Virtual Input 29
BF8C ...Repeated for Virtual Input 30
BF98 ...Repeated for Virtual Input 31
BFA4 ...Repeated for Virtual Input 32
BFB0 ...Repeated for Virtual Input 33
BFBC ...Repeated for Virtual Input 34
BFC8 ...Repeated for Virtual Input 35
BFD4 ...Repeated for Virtual Input 36
BFE0 ...Repeated for Virtual Input 37
BFEC ...Repeated for Virtual Input 38
BFF8 ...Repeated for Virtual Input 39
C004 ...Repeated for Virtual Input 40
C010 ...Repeated for Virtual Input 41
C01C ...Repeated for Virtual Input 42
C028 ...Repeated for Virtual Input 43
C034 ...Repeated for Virtual Input 44
C040 ...Repeated for Virtual Input 45
C04C ...Repeated for Virtual Input 46
C058 ...Repeated for Virtual Input 47
C064 ...Repeated for Virtual Input 48
C070 ...Repeated for Virtual Input 49
C07C ...Repeated for Virtual Input 50
C088 ...Repeated for Virtual Input 51
C094 ...Repeated for Virtual Input 52
C0A0 ...Repeated for Virtual Input 53
C0AC ...Repeated for Virtual Input 54
C0B8 ...Repeated for Virtual Input 55
C0C4 ...Repeated for Virtual Input 56
C0D0 ...Repeated for Virtual Input 57
C0DC ...Repeated for Virtual Input 58
C0E8 ...Repeated for Virtual Input 59
B C2C8
C2D0
...Repeated for Virtual Output 52
...Repeated for Virtual Output 53
C2D8 ...Repeated for Virtual Output 54
C2E0 ...Repeated for Virtual Output 55
C2E8 ...Repeated for Virtual Output 56
C2F0 ...Repeated for Virtual Output 57
C2F8 ...Repeated for Virtual Output 58
C300 ...Repeated for Virtual Output 59
C308 ...Repeated for Virtual Output 60
C310 ...Repeated for Virtual Output 61
C318 ...Repeated for Virtual Output 62
C320 ...Repeated for Virtual Output 63
C328 ...Repeated for Virtual Output 64
C330 ...Repeated for Virtual Output 65
C338 ...Repeated for Virtual Output 66
C340 ...Repeated for Virtual Output 67
C348 ...Repeated for Virtual Output 68
C350 ...Repeated for Virtual Output 69
C358 ...Repeated for Virtual Output 70
C360 ...Repeated for Virtual Output 71
C368 ...Repeated for Virtual Output 72
C370 ...Repeated for Virtual Output 73
C378 ...Repeated for Virtual Output 74
C380 ...Repeated for Virtual Output 75
C388 ...Repeated for Virtual Output 76
C390 ...Repeated for Virtual Output 77
C398 ...Repeated for Virtual Output 78
C3A0 ...Repeated for Virtual Output 79
C3A8 ...Repeated for Virtual Output 80
C3B0 ...Repeated for Virtual Output 81
C3B8 ...Repeated for Virtual Output 82
C3C0 ...Repeated for Virtual Output 83
C3C8 ...Repeated for Virtual Output 84
C3D0 ...Repeated for Virtual Output 85
C3D8 ...Repeated for Virtual Output 86
C3E0 ...Repeated for Virtual Output 87
C3E8 ...Repeated for Virtual Output 88
C3F0 ...Repeated for Virtual Output 89
C3F8 ...Repeated for Virtual Output 90
C400 ...Repeated for Virtual Output 91
C408 ...Repeated for Virtual Output 92
C410 ...Repeated for Virtual Output 93
C418 ...Repeated for Virtual Output 94
C420 ...Repeated for Virtual Output 95
C428 ...Repeated for Virtual Output 96
Mandatory (Read/Write Setting)
C430 Test Mode Function 0 to 1 --- 1 F245 0 (Disabled)
C431 Force VFD and LED 0 to 1 --- 1 F126 0 (No)
C432 Test Mode Forcing 0 to 65535 --- 1 F300 1
B C698
C6A4
...Repeated for Contact Output 51
...Repeated for Contact Output 52
C6B0 ...Repeated for Contact Output 53
C6BC ...Repeated for Contact Output 54
C6C8 ...Repeated for Contact Output 55
C6D4 ...Repeated for Contact Output 56
C6E0 ...Repeated for Contact Output 57
C6EC ...Repeated for Contact Output 58
C6F8 ...Repeated for Contact Output 59
C704 ...Repeated for Contact Output 60
C710 ...Repeated for Contact Output 61
C71C ...Repeated for Contact Output 62
C728 ...Repeated for Contact Output 63
C734 ...Repeated for Contact Output 64
Reset (Read/Write Setting)
C750 FlexLogic™ operand which initiates a reset 0 to 65535 --- 1 F300 0
Control Pushbuttons (Read/Write Setting) (7 modules)
C760 Control Pushbutton 1 Function 0 to 1 --- 1 F102 0 (Disabled)
C761 Control Pushbutton 1 Events 0 to 1 --- 1 F102 0 (Disabled)
C762 ...Repeated for Control Pushbutton 2
C764 ...Repeated for Control Pushbutton 3
C766 ...Repeated for Control Pushbutton 4
C768 ...Repeated for Control Pushbutton 5
C76A ...Repeated for Control Pushbutton 6
C76C ...Repeated for Control Pushbutton 7
Clear Records (Read/Write Setting)
C771 Clear User Fault Reports operand 0 to 65535 --- 1 F300 0
C772 Clear Event Records operand 0 to 65535 --- 1 F300 0
C773 Clear Oscillography operand 0 to 65535 --- 1 F300 0
C774 Clear Data Logger operand 0 to 65535 --- 1 F300 0
C77D Clear Energy operand 0 to 65535 --- 1 F300 0
C77F Clear Unauthorized Access operand 0 to 65535 --- 1 F300 0
C781 Clear Platform Direct Input/Output Statistics operand 0 to 65535 --- 1 F300 0
C782 Reserved (13 items) --- --- --- F001 0
Force Contact Inputs/Outputs (Read/Write Settings)
C7A0 Force Contact Input x State (96 items) 0 to 2 --- 1 F144 0 (Disabled)
C800 Force Contact Output x State (64 items) 0 to 3 --- 1 F131 0 (Disabled)
Direct Inputs/Outputs (Read/Write Setting)
C880 Direct Device ID 1 to 16 --- 1 F001 1
C881 Direct I/O Channel 1 Ring Configuration Function 0 to 1 --- 1 F126 0 (No)
C882 Platform Direct I/O Data Rate 64 to 128 kbps 64 F001 64
C883 Direct I/O Channel 2 Ring Configuration Function 0 to 1 --- 1 F126 0 (No)
C884 Platform Direct I/O Crossover Function 0 to 1 --- 1 F102 0 (Disabled)
Direct input/output commands (Read/Write Command)
C888 Direct input/output clear counters command 0 to 1 --- 1 F126 0 (No)
Direct inputs (Read/Write Setting) (96 modules)
C890 Direct Input 1 Device Number 0 to 16 --- 1 F001 0
C891 Direct Input 1 Number 0 to 96 --- 1 F001 0
C892 Direct Input 1 Default State 0 to 3 --- 1 F086 0 (Off)
B CA42
CA44
...Repeated for Direct Output 26
...Repeated for Direct Output 27
CA46 ...Repeated for Direct Output 28
CA48 ...Repeated for Direct Output 29
CA4A ...Repeated for Direct Output 30
CA4C ...Repeated for Direct Output 31
CA4E ...Repeated for Direct Output 32
Direct Input/Output Alarms (Read/Write Setting)
CAD0 Direct Input/Output Channel 1 CRC Alarm Function 0 to 1 --- 1 F102 0 (Disabled)
CAD1 Direct I/O Channel 1 CRC Alarm Message Count 100 to 10000 --- 1 F001 600
CAD2 Direct Input/Output Channel 1 CRC Alarm Threshold 1 to 1000 --- 1 F001 10
CAD3 Direct Input/Output Channel 1 CRC Alarm Events 0 to 1 --- 1 F102 0 (Disabled)
CAD4 Reserved (4 items) 1 to 1000 --- 1 F001 10
CAD8 Direct Input/Output Channel 2 CRC Alarm Function 0 to 1 --- 1 F102 0 (Disabled)
CAD9 Direct I/O Channel 2 CRC Alarm Message Count 100 to 10000 --- 1 F001 600
CADA Direct Input/Output Channel 2 CRC Alarm Threshold 1 to 1000 --- 1 F001 10
CADB Direct Input/Output Channel 2 CRC Alarm Events 0 to 1 --- 1 F102 0 (Disabled)
CADC Reserved (4 items) 1 to 1000 --- 1 F001 10
CAE0 Direct I/O Ch 1 Unreturned Messages Alarm Function 0 to 1 --- 1 F102 0 (Disabled)
CAE1 Direct I/O Ch 1 Unreturned Messages Alarm Msg Count 100 to 10000 --- 1 F001 600
CAE2 Direct I/O Ch 1 Unreturned Messages Alarm Threshold 1 to 1000 --- 1 F001 10
CAE3 Direct I/O Ch 1 Unreturned Messages Alarm Events 0 to 1 --- 1 F102 0 (Disabled)
CAE4 Reserved (4 items) 1 to 1000 --- 1 F001 10
CAE8 Direct IO Ch 2 Unreturned Messages Alarm Function 0 to 1 --- 1 F102 0 (Disabled)
CAE9 Direct I/O Ch 2 Unreturned Messages Alarm Msg Count 100 to 10000 --- 1 F001 600
CAEA Direct I/O Ch 2 Unreturned Messages Alarm Threshold 1 to 1000 --- 1 F001 10
CAEB Direct I/O Channel 2 Unreturned Messages Alarm Events 0 to 1 --- 1 F102 0 (Disabled)
CAEC Reserved (4 items) --- --- 1 F001 10
Remote Devices (Read/Write Setting) (16 modules)
CB00 Remote Device 1 GSSE/GOOSE Application ID --- --- --- F209 “Remote Device 1“
CB21 Remote Device 1 GOOSE Ethernet APPID 0 to 16383 --- 1 F001 0
CB22 Remote Device 1 GOOSE Dataset 0 to 16 --- 1 F184 0 (Fixed)
CB23 Remote Device 1 in PMU Scheme 0 to 1 --- 1 F126 0 (No)
CB24 ...Repeated for Device 2
CB48 ...Repeated for Device 3
CB6C ...Repeated for Device 4
CB90 ...Repeated for Device 5
CBB4 ...Repeated for Device 6
CBD8 ...Repeated for Device 7
CBFC ...Repeated for Device 8
CC20 ...Repeated for Device 9
CC44 ...Repeated for Device 10
CC68 ...Repeated for Device 11
CC8C ...Repeated for Device 12
CCB0 ...Repeated for Device 13
CCD4 ...Repeated for Device 14
CCF8 ...Repeated for Device 15
CD1C ...Repeated for Device 16
B D26C
D270
...Repeated for Remote Output 20
...Repeated for Remote Output 21
D274 ...Repeated for Remote Output 22
D278 ...Repeated for Remote Output 23
D27C ...Repeated for Remote Output 24
D280 ...Repeated for Remote Output 25
D284 ...Repeated for Remote Output 26
D288 ...Repeated for Remote Output 27
D28C ...Repeated for Remote Output 28
D290 ...Repeated for Remote Output 29
D294 ...Repeated for Remote Output 30
D298 ...Repeated for Remote Output 31
D29C ...Repeated for Remote Output 32
Remote Output UserSt Pairs (Read/Write Setting) (32 modules)
D2A0 Remote Output UserSt 1 Operand 0 to 65535 --- 1 F300 0
D2A1 Remote Output UserSt 1 Events 0 to 1 --- 1 F102 0 (Disabled)
D2A2 Reserved (2 items) 0 to 1 --- 1 F001 0
D2A4 ...Repeated for Remote Output 2
D2A8 ...Repeated for Remote Output 3
D2AC ...Repeated for Remote Output 4
D2B0 ...Repeated for Remote Output 5
D2B4 ...Repeated for Remote Output 6
D2B8 ...Repeated for Remote Output 7
D2BC ...Repeated for Remote Output 8
D2C0 ...Repeated for Remote Output 9
D2C4 ...Repeated for Remote Output 10
D2C8 ...Repeated for Remote Output 11
D2CC ...Repeated for Remote Output 12
D2D0 ...Repeated for Remote Output 13
D2D4 ...Repeated for Remote Output 14
D2D8 ...Repeated for Remote Output 15
D2DC ...Repeated for Remote Output 16
D2E0 ...Repeated for Remote Output 17
D2E4 ...Repeated for Remote Output 18
D2E8 ...Repeated for Remote Output 19
D2EC ...Repeated for Remote Output 20
D2F0 ...Repeated for Remote Output 21
D2F4 ...Repeated for Remote Output 22
D2F8 ...Repeated for Remote Output 23
D2FC ...Repeated for Remote Output 24
D300 ...Repeated for Remote Output 25
D304 ...Repeated for Remote Output 26
D308 ...Repeated for Remote Output 27
D30C ...Repeated for Remote Output 28
D310 ...Repeated for Remote Output 29
D314 ...Repeated for Remote Output 30
D318 ...Repeated for Remote Output 31
D31C ...Repeated for Remote Output 32
B D35A
D35B
IEC 61850 GGIO2.CF.SPCSO59.ctlModel Value
IEC 61850 GGIO2.CF.SPCSO60.ctlModel Value
0 to 2
0 to 2
---
---
1
1
F001
F001
2
2
D35C IEC 61850 GGIO2.CF.SPCSO61.ctlModel Value 0 to 2 --- 1 F001 2
D35D IEC 61850 GGIO2.CF.SPCSO62.ctlModel Value 0 to 2 --- 1 F001 2
D35E IEC 61850 GGIO2.CF.SPCSO63.ctlModel Value 0 to 2 --- 1 F001 2
Remote Device Status (Read Only) (16 modules)
D380 Remote Device 1 StNum 0 to 4294967295 --- 1 F003 0
D382 Remote Device 1 SqNum 0 to 4294967295 --- 1 F003 0
D384 ...Repeated for Remote Device 2
D388 ...Repeated for Remote Device 3
D38C ...Repeated for Remote Device 4
D390 ...Repeated for Remote Device 5
D394 ...Repeated for Remote Device 6
D398 ...Repeated for Remote Device 7
D39C ...Repeated for Remote Device 8
D3A0 ...Repeated for Remote Device 9
D3A4 ...Repeated for Remote Device 10
D3A8 ...Repeated for Remote Device 11
D3AC ...Repeated for Remote Device 12
D3B0 ...Repeated for Remote Device 13
D3B4 ...Repeated for Remote Device 14
D3B8 ...Repeated for Remote Device 15
D3BC ...Repeated for Remote Device 16
D3C0 ...Repeated for Remote Device 17
D3C4 ...Repeated for Remote Device 18
D3C8 ...Repeated for Remote Device 19
D3CC ...Repeated for Remote Device 20
D3D0 ...Repeated for Remote Device 21
D3D4 ...Repeated for Remote Device 22
D3D8 ...Repeated for Remote Device 23
D3DC ...Repeated for Remote Device 24
D3E0 ...Repeated for Remote Device 25
D3E4 ...Repeated for Remote Device 26
D3E8 ...Repeated for Remote Device 27
D3EC ...Repeated for Remote Device 28
D3F0 ...Repeated for Remote Device 29
D3F4 ...Repeated for Remote Device 30
D3F8 ...Repeated for Remote Device 31
D3FC ...Repeated for Remote Device 32
Phasor Measurement Unit Communication (Read/Write Setting)
D400 PMU 1 Communication Port 1 Type 0 to 3 --- 1 F545 0 (Network)
D401 PMU 1 Communication Port 2 Type 0 to 3 --- 1 F545 0 (Network)
D402 PMU 1 Communication Port 3 Type 0 to 3 --- 1 F545 0 (Network)
D403 PMU 1 Port 1 PHS-x (14 items) 0 to 14 --- 1 F543 1 (Va)
D411 PMU 1 Port 2 PHS-x (14 items) 0 to 14 --- 1 F543 1 (Va)
D41F PMU 1 Port 3 PHS-x (14 items) 0 to 14 --- 1 F543 1 (Va)
D42D PMU 1 Communication Port 1 PHS-x Name (14 items) --- --- --- F203 “GE-UR-PMU-PHS 1”
D49D PMU 1 Port 2 PHS-x Name (14 items) --- --- --- F203 “GE-UR-PMU-PHS 1”
D50D PMU 1 Port 3 PHS-x Name (14 items) --- --- --- F203 “GE-UR-PMU-PHS 1”
F001 F040
UR_UINT16 UNSIGNED 16 BIT INTEGER UR_UINT48 48-BIT UNSIGNED INTEGER
B F002
UR_SINT16 SIGNED 16 BIT INTEGER
F050
UR_UINT32 TIME and DATE (UNSIGNED 32 BIT INTEGER)
Gives the current time in seconds elapsed since 00:00:00 January
1, 1970.
F003
UR_UINT32 UNSIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register. F051
Low order word is stored in the second register. UR_UINT32 DATE in SR format (alternate format for F050)
First 16 bits are Month/Day (MM/DD/xxxx). Month: 1=January,
2=February,...,12=December; Day: 1 to 31 in steps of 1
F004
Last 16 bits are Year (xx/xx/YYYY): 1970 to 2106 in steps of 1
UR_SINT32 SIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register/
Low order word is stored in the second register. F052
UR_UINT32 TIME in SR format (alternate format for F050)
First 16 bits are Hours/Minutes (HH:MM:xx.xxx).
F005
Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm;
UR_UINT8 UNSIGNED 8 BIT INTEGER
Minutes: 0 to 59 in steps of 1
Last 16 bits are Seconds (xx:xx:.SS.SSS): 0=00.000s,
F006 1=00.001,...,59999=59.999s)
UR_SINT8 SIGNED 8 BIT INTEGER
F060
F011 FLOATING_POINT IEEE FLOATING POINT (32 bits)
UR_UINT16 FLEXCURVE DATA (120 points)
A FlexCurve is an array of 120 consecutive data points (x, y) which
F070
are interpolated to generate a smooth curve. The y-axis is the user
HEX2 2 BYTES - 4 ASCII DIGITS
defined trip or operation time setting; the x-axis is the pickup ratio
and is pre-defined. Refer to format F119 for a listing of the pickup
ratios; the enumeration value for the pickup ratio indicates the off-
F071
set into the FlexCurve base address where the corresponding time HEX4 4 BYTES - 8 ASCII DIGITS
value is stored.
F072
F012
HEX6 6 BYTES - 12 ASCII DIGITS
DISPLAY_SCALE DISPLAY SCALING
(unsigned 16-bit integer)
MSB indicates the SI units as a power of ten. LSB indicates the F073
number of decimal points to display. HEX8 8 BYTES - 16 ASCII DIGITS
Example: Current values are stored as 32 bit numbers with three
decimal places and base units in Amps. If the retrieved value is
F074
12345.678 A and the display scale equals 0x0302 then the dis-
HEX20 20 BYTES - 40 ASCII DIGITS
played value on the unit is 12.35 kA.
F083
F013
ENUMERATION: SELECTOR MODES
POWER_FACTOR (SIGNED 16 BIT INTEGER)
0 = Time-Out, 1 = Acknowledge
Positive values indicate lagging power factor; negative values
indicate leading.
F084
ENUMERATION: SELECTOR POWER UP
0 = Restore, 1 = Synchronize, 2 = Sync/Restore
F085 F106
ENUMERATION: POWER SWING SHAPE ENUMERATION: PHASE ROTATION
0 = Mho Shape, 1 = Quad Shape 0 = ABC, 1 = ACB
F086 F108
ENUMERATION: DIGITAL INPUT DEFAULT STATE ENUMERATION: OFF/ON
0 = Off, 1 = On, 2= Latest/Off, 3 = Latest/On 0 = Off, 1 = On B
F090 F109
ENUMERATION: LATCHING OUTPUT TYPE ENUMERATION: CONTACT OUTPUT OPERATION
0 = Operate-dominant, 1 = Reset-dominant 0 = Self-reset, 1 = Latched, 2 = Disabled
F100 F110
ENUMERATION: VT CONNECTION TYPE ENUMERATION: CONTACT OUTPUT LED CONTROL
0 = Wye; 1 = Delta 0 = Trip, 1 = Alarm, 2 = None
F101 F111
ENUMERATION: MESSAGE DISPLAY INTENSITY ENUMERATION: UNDERVOLTAGE CURVE SHAPES
0 = 25%, 1 = 50%, 2 = 75%, 3 = 100% 0 = Definite Time, 1 = Inverse Time
F102 F112
ENUMERATION: DISABLED/ENABLED ENUMERATION: RS485 BAUD RATES
0 = Disabled; 1 = Enabled
bitmask value bitmask value bitmask value
0 300 4 9600 8 115200
F103 1 1200 5 19200 9 14400
ENUMERATION: CURVE SHAPES 2 2400 6 38400 10 28800
3 4800 7 57600 11 33600
bitmask curve shape bitmask curve shape
0 IEEE Mod Inv 9 IAC Inverse
1 IEEE Very Inv 10 IAC Short Inv F113
2 IEEE Ext Inv 11 I2t ENUMERATION: PARITY
3 IEC Curve A 12 Definite Time 0 = None, 1 = Odd, 2 = Even
4 IEC Curve B 13 FlexCurve™ A
5 IEC Curve C 14 FlexCurve™ B
F114
6 IEC Short Inv 15 FlexCurve™ C
ENUMERATION: IRIG-B SIGNAL TYPE
7 IAC Ext Inv 16 FlexCurve™ D
0 = None, 1 = DC Shift, 2 = Amplitude Modulated
8 IAC Very Inv
F115
F104
ENUMERATION: BREAKER STATUS
ENUMERATION: RESET TYPE
0 = Auxiliary A, 1 = Auxiliary B
0 = Instantaneous, 1 = Timed, 2 = Linear
F116
F105
ENUMERATION: NEUTRAL OVERVOLTAGE CURVES
ENUMERATION: LOGIC INPUT
0 = Definite Time, 1 = FlexCurve™ A, 2 = FlexCurve™ B,
0 = Disabled, 1 = Input 1, 2 = Input 2
3 = FlexCurve™ C
F117 F123
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS ENUMERATION: CT SECONDARY
0 = 1×72 cycles, 1 = 3×36 cycles, 2 = 7×18 cycles, 3 = 15×9 cycles 0 = 1 A, 1 = 5 A
F118 F124
ENUMERATION: OSCILLOGRAPHY MODE ENUMERATION: LIST OF ELEMENTS
B 0 = Automatic Overwrite, 1 = Protected
bitmask element
0 Phase Instantaneous Overcurrent 1
F119 1 Phase Instantaneous Overcurrent 2
ENUMERATION: FLEXCURVE™ PICKUP RATIOS 2 Phase Instantaneous Overcurrent 3
3 Phase Instantaneous Overcurrent 4
mask value mask value mask value mask value
4 Phase Instantaneous Overcurrent 5
0 0.00 30 0.88 60 2.90 90 5.90
5 Phase Instantaneous Overcurrent 6
1 0.05 31 0.90 61 3.00 91 6.00
6 Phase Instantaneous Overcurrent 7
2 0.10 32 0.91 62 3.10 92 6.50
7 Phase Instantaneous Overcurrent 8
3 0.15 33 0.92 63 3.20 93 7.00
8 Phase Instantaneous Overcurrent 9
4 0.20 34 0.93 64 3.30 94 7.50
9 Phase Instantaneous Overcurrent 10
5 0.25 35 0.94 65 3.40 95 8.00
10 Phase Instantaneous Overcurrent 11
6 0.30 36 0.95 66 3.50 96 8.50
11 Phase Instantaneous Overcurrent 12
7 0.35 37 0.96 67 3.60 97 9.00
16 Phase Time Overcurrent 1
8 0.40 38 0.97 68 3.70 98 9.50
17 Phase Time Overcurrent 2
9 0.45 39 0.98 69 3.80 99 10.00
18 Phase Time Overcurrent 3
10 0.48 40 1.03 70 3.90 100 10.50
19 Phase Time Overcurrent 4
11 0.50 41 1.05 71 4.00 101 11.00
20 Phase Time Overcurrent 5
12 0.52 42 1.10 72 4.10 102 11.50
21 Phase Time Overcurrent 6
13 0.54 43 1.20 73 4.20 103 12.00
24 Phase Directional Overcurrent 1
14 0.56 44 1.30 74 4.30 104 12.50
25 Phase Directional Overcurrent 2
15 0.58 45 1.40 75 4.40 105 13.00
32 Neutral Instantaneous Overcurrent 1
16 0.60 46 1.50 76 4.50 106 13.50
33 Neutral Instantaneous Overcurrent 2
17 0.62 47 1.60 77 4.60 107 14.00
34 Neutral Instantaneous Overcurrent 3
18 0.64 48 1.70 78 4.70 108 14.50
35 Neutral Instantaneous Overcurrent 4
19 0.66 49 1.80 79 4.80 109 15.00
36 Neutral Instantaneous Overcurrent 5
20 0.68 50 1.90 80 4.90 110 15.50
37 Neutral Instantaneous Overcurrent 6
21 0.70 51 2.00 81 5.00 111 16.00
38 Neutral Instantaneous Overcurrent 7
22 0.72 52 2.10 82 5.10 112 16.50
39 Neutral Instantaneous Overcurrent 8
23 0.74 53 2.20 83 5.20 113 17.00
40 Neutral Instantaneous Overcurrent 9
24 0.76 54 2.30 84 5.30 114 17.50
41 Neutral Instantaneous Overcurrent 10
25 0.78 55 2.40 85 5.40 115 18.00
42 Neutral Instantaneous Overcurrent 11
26 0.80 56 2.50 86 5.50 116 18.50
43 Neutral Instantaneous Overcurrent 12
27 0.82 57 2.60 87 5.60 117 19.00
48 Neutral Time Overcurrent 1
28 0.84 58 2.70 88 5.70 118 19.50
49 Neutral Time Overcurrent 2
29 0.86 59 2.80 89 5.80 119 20.00
50 Neutral Time Overcurrent 3
51 Neutral Time Overcurrent 4
F120 52 Neutral Time Overcurrent 5
ENUMERATION: DISTANCE SHAPE 53 Neutral Time Overcurrent 6
0 = Mho, 1 = Quad 56 Neutral Directional Overcurrent 1
57 Neutral Directional Overcurrent 2
60 Negative Sequence Directional Overcurrent 1
F122
61 Negative Sequence Directional Overcurrent 2
ENUMERATION: ELEMENT INPUT SIGNAL TYPE
64 Ground Instantaneous Overcurrent 1
0 = Phasor, 1 = RMS 65 Ground Instantaneous Overcurrent 2
66 Ground Instantaneous Overcurrent 3
Bitmask Error
F134
15 Latching Output Discrepancy
ENUMERATION: PASS/FAIL
16 Ethernet Switch Fail
0 = Fail, 1 = OK, 2 = n/a 17 Maintenance Alert 01
18 SNTP Failure
F135 19 ---
ENUMERATION: GAIN CALIBRATION 20 Primary Ethernet Fail
B 0 = 0x1, 1 = 1x16 21 Secondary Ethernet Fail
22 Temperature Monitor
23 Process Bus Trouble
F136 24 Brick Trouble
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS
25 Field RTD Trouble
0 = 31 x 8 cycles, 1 = 15 x 16 cycles, 2 = 7 x 32 cycles 26 Field TDR Trouble
3 = 3 x 64 cycles, 4 = 1 x 128 cycles 27 Remote Device Offline
28 Direct Device Offline
bitmask definition
F145
33 System Integrity Recovery 06
ENUMERATION: ALPHABET LETTER
34 System Integrity Recovery 07
bitmask type bitmask type bitmask type bitmask type
0 null 7 G 14 N 21 U
F151
1 A 8 H 15 O 22 V ENUMERATION: RTD SELECTION
2 B 9 I 16 P 23 W
3 C 10 J 17 Q 24 X
bitmask
0
RTD#
NONE
bitmask
17
RTD#
RTD 17
bitmask
33
RTD#
RTD 33
B
4 D 11 K 18 R 25 Y
1 RTD 1 18 RTD 18 34 RTD 34
5 E 12 L 19 S 26 Z
2 RTD 2 19 RTD 19 35 RTD 35
6 F 13 M 20 T
3 RTD 3 20 RTD 20 36 RTD 36
4 RTD 4 21 RTD 21 37 RTD 37
F146 5 RTD 5 22 RTD 22 38 RTD 38
ENUMERATION: MISCELLANEOUS EVENT CAUSES 6 RTD 6 23 RTD 23 39 RTD 39
7 RTD 7 24 RTD 24 40 RTD 40
bitmask definition
8 RTD 8 25 RTD 25 41 RTD 41
0 Events Cleared
9 RTD 9 26 RTD 26 42 RTD 42
1 Oscillography Triggered
10 RTD 10 27 RTD 27 43 RTD 43
2 Date/time Changed
11 RTD 11 28 RTD 28 44 RTD 44
3 Default Settings Loaded
12 RTD 12 29 RTD 29 45 RTD 45
4 Test Mode Forcing On
13 RTD 13 30 RTD 30 46 RTD 46
5 Test Mode Forcing Off
14 RTD 14 31 RTD 31 47 RTD 47
6 Power On
15 RTD 15 32 RTD 32 48 RTD 48
7 Power Off
16 RTD 16
8 Relay In Service
9 Relay Out Of Service
10 Watchdog Reset F152
11 Oscillography Clear ENUMERATION: SETTING GROUP
12 Reboot Command 0 = Active Group, 1 = Group 1, 2 = Group 2, 3 = Group 3
13 Led Test Initiated 4 = Group 4, 5 = Group 5, 6 = Group 6
14 Flash Programming
15 Fault Report Trigger
F153
16 User Programmable Fault Report Trigger
ENUMERATION: DISTANCE TRANSFORMER CONNECTION
17 ---
bitmask type bitmask type bitmask type
18 Reload CT/VT module Settings
0 None 5 Dy9 10 Yd7
19 ---
1 Dy1 6 Dy11 11 Yd9
20 Ethernet Port 1 Offline
2 Dy3 7 Yd1 12 Yd11
21 Ethernet Port 2 Offline
3 Dy5 8 Yd3
22 Ethernet Port 3 Offline
4 Dy7 9 Yd5
23 Ethernet Port 4 Offline
24 Ethernet Port 5 Offline
25 Ethernet Port 6 Offline
F154
26 Test Mode Isolated ENUMERATION: DISTANCE DIRECTION
27 Test Mode Forcible
0 = Forward, 1 = Reverse, 2 = Non-Directional
28 Test Mode Disabled
29 Temperature Warning On
30 Temperature Warning Off F155
31 Unauthorized Access ENUMERATION: REMOTE DEVICE STATE
32 System Integrity Recovery 0 = Offline, 1 = Online
F156 F167
ENUMERATION: REMOTE INPUT BIT PAIRS ENUMERATION: SIGNAL SOURCE
0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4,
bitmask value bitmask value
4 = SRC 5, 5 = SRC 6
0 NONE 35 UserSt-3
1 DNA-1 36 UserSt-4
2 DNA-2 37 UserSt-5 F168
B 3 DNA-3 38 UserSt-6 ENUMERATION: INRUSH INHIBIT FUNCTION
4 DNA-4 39 UserSt-7 0 = Disabled, 1 = Adapt. 2nd, 2 = Trad. 2nd
5 DNA-5 40 UserSt-8
6 DNA-6 41 UserSt-9
F170
7 DNA-7 42 UserSt-10
ENUMERATION: LOW/HIGH OFFSET and GAIN
8 DNA-8 43 UserSt-11 TRANSDUCER INPUT/OUTPUT SELECTION
9 DNA-9 44 UserSt-12
0 = LOW, 1 = HIGH
10 DNA-10 45 UserSt-13
11 DNA-11 46 UserSt-14
12 DNA-12 47 UserSt-15 F171
13 DNA-13 48 UserSt-16 ENUMERATION: TRANSDUCER CHANNEL INPUT TYPE
14 DNA-14 49 UserSt-17 0 = dcmA IN, 1 = Ohms IN, 2 = RTD IN, 3 = dcmA OUT,
15 DNA-15 50 UserSt-18 4 = RRTD IN
16 DNA-16 51 UserSt-19
17 DNA-17 52 UserSt-20
F172
18 DNA-18 53 UserSt-21 ENUMERATION: SLOT LETTERS
19 DNA-19 54 UserSt-22
20 DNA-20 55 UserSt-23 bitmask slot bitmask slot bitmask slot bitmask slot
21 DNA-21 56 UserSt-24 0 F 4 K 8 P 12 U
22 DNA-22 57 UserSt-25 1 G 5 L 9 R 13 V
23 DNA-23 58 UserSt-26 2 H 6 M 10 S 14 W
24 DNA-24 59 UserSt-27 3 J 7 N 11 T 15 X
25 DNA-25 60 UserSt-28
26 DNA-26 61 UserSt-29
F173
27 DNA-27 62 UserSt-30 ENUMERATION: DCMA INPUT/OUTPUT RANGE
28 DNA-28 63 UserSt-31
29 DNA-29 64 UserSt-32 bitmask dcmA input/output range
33 UserSt-1 ↓ ↓ 3 0 to 5 mA
F176 F184
ENUMERATION: SYNCHROCHECK DEAD SOURCE SELECT ENUMERATION: REMOTE DEVICE GOOSE DATASET
F185
F179 ENUMERATION: PHASE A,B,C, GROUND SELECTOR
ENUMERATION: NEGATIVE SEQUENCE DIRECTIONAL
OVERCURRENT TYPE 0 = A, 1 = B, 2 = C, 3 = G
0 = PHASE, 1 = GROUND
F190
ENUMERATION: SIMULATED KEYPRESS
F181
ENUMERATION: ODD/EVEN/NONE bitmsk keypress bitmsk keypress
0 = ODD, 1 = EVEN, 2 = NONE 0 --- 23 Reset
use between real keys
24 User 1
1 1 25 User 2
F183
2 2 26 User 3
ENUMERATION: AC INPUT WAVEFORMS
3 3 27 User-programmable key 1
F193
ENUMERATION: ACCIDENTAL ENERG. ARMING MODE F213
0 = UV and Offline, 1 = UV or Offline TEXT32: 32-CHARACTER ASCII TEXT
F194 F220
ENUMERATION: PUSHBUTTON MESSAGE PRIORITY
ENUMERATION: DNP SCALE
0 = 0.01, 1 = 0.1, 2 = 1, 3 = 10, 4 = 100, 5 = 1000, 6 = 10000, value priority
7 = 100000, 8 = 0.001 0 Disabled
1 Normal
F230
F204 ENUMERATION: DIRECTIONAL POLARIZING
TEXT80: 80-CHARACTER ASCII TEXT 0 = Voltage, 1 = Current, 2 = Dual
501 GGIO4.MX.AnIn23.mag.f ↓ ↓
F260
ENUMERATION: DATA LOGGER MODE F491
ENUMERATION: ANALOG INPUT MODE
0 = Continuous, 1 = Trigger
0 = Default Value, 1 = Last Known
F300
UR_UINT16: FLEXLOGIC™ BASE TYPE (6-bit type)
F500
The FlexLogic™ BASE type is 6 bits and is combined with a 9 bit UR_UINT16: PACKED BITFIELD
descriptor and 1 bit for protection element to form a 16 bit value.
First register indicates input/output state with bits 0 (MSB) to 15
The combined bits are of the form: PTTTTTTDDDDDDDDD,
(LSB) corresponding to input/output state 1 to 16. The second reg-
where P bit if set, indicates that the FlexLogic™ type is associated
ister indicates input/output state with bits 0 to 15 corresponding to
with a protection element state and T represents bits for the BASE
input/output state 17 to 32 (if required) The third register indicates
type, and D represents bits for the descriptor.
input/output state with bits 0 to 15 corresponding to input/output
The values in square brackets indicate the base type with P prefix state 33 to 48 (if required). The fourth register indicates input/out-
[PTTTTTT] and the values in round brackets indicate the descrip- put state with bits 0 to 15 corresponding to input/output state 49 to
tor range. 64 (if required).
[0] Off(0) – this is boolean FALSE value The number of registers required is determined by the specific
[0] On (1) – this is boolean TRUE value data item. A bit value of 0 = Off and 1 = On.
[2] CONTACT INPUTS (1 to 96)
[3] CONTACT INPUTS OFF (1 to 96)
[4] VIRTUAL INPUTS (1 to 64) F501
[6] VIRTUAL OUTPUTS (1 to 96) UR_UINT16: LED STATUS
[10] CONTACT OUTPUTS VOLTAGE DETECTED (1 to 64)
[11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1 to 64) Low byte of register indicates LED status with bit 0 representing
the top LED and bit 7 the bottom LED. A bit value of 1 indicates
[12] CONTACT OUTPUTS CURRENT DETECTED (1 to 64)
the LED is on, 0 indicates the LED is off.
[13] CONTACT OUTPUTS CURRENT OFF DETECTED (1 to 64)
[14] REMOTE INPUTS (1 to 32)
[28] INSERT (via keypad only)
F502
[32] END
[34] NOT (1 INPUT) BITFIELD: ELEMENT OPERATE STATES
[36] 2 INPUT XOR (0) Each bit contains the operate state for an element. See the F124
[38] LATCH SET/RESET (2 inputs) format code for a list of element IDs. The operate bit for element ID
[40] OR (2 to 16 inputs) X is bit [X mod 16] in register [X/16].
F504 F514
BITFIELD: 3-PHASE ELEMENT STATE ENUMERATION: POWER SWING TRIP MODE
bitmask element state 0 = Delayed, 1 = Early
0 Pickup
1 Operate
F515
2 Pickup Phase A
ENUMERATION ELEMENT INPUT MODE
B 3
4
Pickup Phase B
Pickup Phase C
0 = Signed, 1 = Absolute
5 Operate Phase A
6 Operate Phase B F516
7 Operate Phase C ENUMERATION ELEMENT COMPARE MODE
0 = Level, 1 = Delta
F505
BITFIELD: CONTACT OUTPUT STATE F517
0 = Contact State, 1 = Voltage Detected, 2 = Current Detected ENUMERATION: ELEMENT DIRECTION OPERATION
0 = Over, 1 = Under
F507
BITFIELD: COUNTER ELEMENT STATE F518
0 = Count Greater Than, 1 = Count Equal To, 2 = Count Less Than ENUMERATION: FLEXELEMENT™ UNITS
0 = Milliseconds, 1 = Seconds, 2 = Minutes
F508
BITFIELD: DISTANCE ELEMENT STATE F519
bitmask distance element state ENUMERATION: NON-VOLATILE LATCH
0 Pickup 0 = Reset-Dominant, 1 = Set-Dominant
1 Operate
2 Pickup AB
F522
3 Pickup BC
ENUMERATION: TRANSDUCER DCMA OUTPUT RANGE
4 Pickup CA
5 Operate AB 0 = –1 to 1 mA; 1 = 0 to 1 mA; 2 = 4 to 20 mA
6 Operate BC
7 Operate CA F523
8 Timed ENUMERATION: DNP OBJECTS 20, 22, AND 23 DEFAULT
9 Operate IAB VARIATION
10 Operate IBC
bitmask default variation
11 Operate ICA
0 1
1 2
F509 2 5
BITFIELD: SIMPLE ELEMENT STATE 3 6
0 = Operate
F524
ENUMERATION: DNP OBJECT 21 DEFAULT VARIATION
F511
BITFIELD: 3-PHASE SIMPLE ELEMENT STATE
bitmask Default Variation
0 = Operate, 1 = Operate A, 2 = Operate B, 3 = Operate C 0 1
1 2
2 9
F513
ENUMERATION: POWER SWING MODE 3 10
F525 F543
ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION ENUMERATION: PMU PHASORS
3 7 ~
18 0 ~
36 User PB 6 1 2/second 7 20second
8 4 23 Reset 41 User PB 11
9 5 24 User 1 42 User PB 12
F545
10 6 25 User 2 44 User 4 ENUMERATION: PMU COM PORT TYPE
11 Escape 26 User 3 45 User 5
0 = Network, 1 = RS485, 2 = Dir Comm Ch1, 3 = Dir Comm Ch2,
12 Message 31 User PB 1 46 User 6 4 = GOOSE, 5 = None
Right
13 1 32 User PB 2 47 User 7
14 2 F546
ENUMERATION: PMU REPORTING STYLE
0 = Polar, 1 = Rectangular
F531
ENUMERATION: LANGUAGE
0 = English, 1 = French, 2 = Chinese, 3 = Russian F547
ENUMERATION: PMU REPORTING FORMAT
0 = Integer, 1 = Floating
F540
ENUMERATION: PMU POST-FILTER
0 = None, 1 = Symm-3-Point, 2 = Symm-5-Point, F550
3 = Symm-7-Point, 4 = Class M, 5 = Class P ENUMERATION: RTD INPUT APPLICATION
F551 F603
ENUMERATION: RTD TRIP VOTING ENUMERATION: RRTD TRIP VOTING
F552 F605
ENUMERATION: RTD INPUT OPEN ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT
STATUS
Enumeration RTD open
0 None Enumeration Remote DPS input status
1 Alarm 0 Intermediate
2 Block 1 Off
2 On
3 Bad
F600
UR_UINT16: FLEXANALOG PARAMETER
Corresponds to the Modbus address of the value used when this F606
parameter is selected. Only certain values may be used as Flex- ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT
Analogs (basically all metering quantities used in protection).
Enumeration Remote double-point status input
0 None
F601 1 Remote input 1
ENUMERATION: COM2 PORT USAGE 2 Remote input 2
3 Remote input 3
Enumeration COM2 port usage
↓ ↓
0 RS485
64 Remote input 64
1 RRTD
F611
F602
ENUMERATION: GOOSE RETRANSMISSION SCHEME
ENUMERATION: RRTD BAUD RATE
Enumeration Configurable GOOSE retransmission scheme
Enumeration RRTD baud rate
0 Heartbeat
0 1200 bps
1 Aggressive
1 2400 bps
2 Medium
2 4800 bps
3 Relaxed
3 9600 bps
4 19200 bps
F612
UR_UINT16: FLEXINTEGER PARAMETER
This 16-bit value corresponds to the Modbus address of the
selected FlexInteger paramter. Only certain values may be used
as FlexIntegers.
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
95 PIOC34.ST.Str.general 148 PIOC60.ST.Op.general
96 PIOC34.ST.Op.general 149 PIOC61.ST.Str.general
97 PIOC35.ST.Str.general 150 PIOC61.ST.Op.general
98 PIOC35.ST.Op.general 151 PIOC62.ST.Str.general
99 PIOC36.ST.Str.general 152 PIOC62.ST.Op.general
100 PIOC36.ST.Op.general 153 PIOC63.ST.Str.general
B 101 PIOC37.ST.Str.general 154 PIOC63.ST.Op.general
102 PIOC37.ST.Op.general 155 PIOC64.ST.Str.general
103 PIOC38.ST.Str.general 156 PIOC64.ST.Op.general
104 PIOC38.ST.Op.general 157 PIOC65.ST.Str.general
105 PIOC39.ST.Str.general 158 PIOC65.ST.Op.general
106 PIOC39.ST.Op.general 159 PIOC66.ST.Str.general
107 PIOC40.ST.Str.general 160 PIOC66.ST.Op.general
108 PIOC40.ST.Op.general 161 PIOC67.ST.Str.general
109 PIOC41.ST.Str.general 162 PIOC67.ST.Op.general
110 PIOC41.ST.Op.general 163 PIOC68.ST.Str.general
111 PIOC42.ST.Str.general 164 PIOC68.ST.Op.general
112 PIOC42.ST.Op.general 165 PIOC69.ST.Str.general
113 PIOC43.ST.Str.general 166 PIOC69.ST.Op.general
114 PIOC43.ST.Op.general 167 PIOC70.ST.Str.general
115 PIOC44.ST.Str.general 168 PIOC70.ST.Op.general
116 PIOC44.ST.Op.general 169 PIOC71.ST.Str.general
117 PIOC45.ST.Str.general 170 PIOC71.ST.Op.general
118 PIOC45.ST.Op.general 171 PIOC72.ST.Str.general
119 PIOC46.ST.Str.general 172 PIOC72.ST.Op.general
120 PIOC46.ST.Op.general 173 PTOC1.ST.Str.general
121 PIOC47.ST.Str.general 174 PTOC1.ST.Op.general
122 PIOC47.ST.Op.general 175 PTOC2.ST.Str.general
123 PIOC48.ST.Str.general 176 PTOC2.ST.Op.general
124 PIOC48.ST.Op.general 177 PTOC3.ST.Str.general
125 PIOC49.ST.Str.general 178 PTOC3.ST.Op.general
126 PIOC49.ST.Op.general 179 PTOC4.ST.Str.general
127 PIOC50.ST.Str.general 180 PTOC4.ST.Op.general
128 PIOC50.ST.Op.general 181 PTOC5.ST.Str.general
129 PIOC51.ST.Str.general 182 PTOC5.ST.Op.general
130 PIOC51.ST.Op.general 183 PTOC6.ST.Str.general
131 PIOC52.ST.Str.general 184 PTOC6.ST.Op.general
132 PIOC52.ST.Op.general 185 PTOC7.ST.Str.general
133 PIOC53.ST.Str.general 186 PTOC7.ST.Op.general
134 PIOC53.ST.Op.general 187 PTOC8.ST.Str.general
135 PIOC54.ST.Str.general 188 PTOC8.ST.Op.general
136 PIOC54.ST.Op.general 189 PTOC9.ST.Str.general
137 PIOC55.ST.Str.general 190 PTOC9.ST.Op.general
138 PIOC55.ST.Op.general 191 PTOC10.ST.Str.general
139 PIOC56.ST.Str.general 192 PTOC10.ST.Op.general
140 PIOC56.ST.Op.general 193 PTOC11.ST.Str.general
141 PIOC57.ST.Str.general 194 PTOC11.ST.Op.general
142 PIOC57.ST.Op.general 195 PTOC12.ST.Str.general
143 PIOC58.ST.Str.general 196 PTOC12.ST.Op.general
144 PIOC58.ST.Op.general 197 PTOC13.ST.Str.general
145 PIOC59.ST.Str.general 198 PTOC13.ST.Op.general
146 PIOC59.ST.Op.general 199 PTOC14.ST.Str.general
147 PIOC60.ST.Str.general 200 PTOC14.ST.Op.general
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
201 PTOC15.ST.Str.general 254 PTUV1.ST.Op.general
202 PTOC15.ST.Op.general 255 PTUV2.ST.Str.general
203 PTOC16.ST.Str.general 256 PTUV2.ST.Op.general
204 PTOC16.ST.Op.general 257 PTUV3.ST.Str.general
205 PTOC17.ST.Str.general 258 PTUV3.ST.Op.general
206 PTOC17.ST.Op.general 259 PTUV4.ST.Str.general
207 PTOC18.ST.Str.general 260 PTUV4.ST.Op.general B
208 PTOC18.ST.Op.general 261 PTUV5.ST.Str.general
209 PTOC19.ST.Str.general 262 PTUV5.ST.Op.general
210 PTOC19.ST.Op.general 263 PTUV6.ST.Str.general
211 PTOC20.ST.Str.general 264 PTUV6.ST.Op.general
212 PTOC20.ST.Op.general 265 PTUV7.ST.Str.general
213 PTOC21.ST.Str.general 266 PTUV7.ST.Op.general
214 PTOC21.ST.Op.general 267 PTUV8.ST.Str.general
215 PTOC22.ST.Str.general 268 PTUV8.ST.Op.general
216 PTOC22.ST.Op.general 269 PTUV9.ST.Str.general
217 PTOC23.ST.Str.general 270 PTUV9.ST.Op.general
218 PTOC23.ST.Op.general 271 PTUV10.ST.Str.general
219 PTOC24.ST.Str.general 272 PTUV10.ST.Op.general
220 PTOC24.ST.Op.general 273 PTUV11.ST.Str.general
221 PTOV1.ST.Str.general 274 PTUV11.ST.Op.general
222 PTOV1.ST.Op.general 275 PTUV12.ST.Str.general
223 PTOV2.ST.Str.general 276 PTUV12.ST.Op.general
224 PTOV2.ST.Op.general 277 PTUV13.ST.Str.general
225 PTOV3.ST.Str.general 278 PTUV13.ST.Op.general
226 PTOV3.ST.Op.general 279 RBRF1.ST.OpEx.general
227 PTOV4.ST.Str.general 280 RBRF1.ST.OpIn.general
228 PTOV4.ST.Op.general 281 RBRF2.ST.OpEx.general
229 PTOV5.ST.Str.general 282 RBRF2.ST.OpIn.general
230 PTOV5.ST.Op.general 283 RBRF3.ST.OpEx.general
231 PTOV6.ST.Str.general 284 RBRF3.ST.OpIn.general
232 PTOV6.ST.Op.general 285 RBRF4.ST.OpEx.general
233 PTOV7.ST.Str.general 286 RBRF4.ST.OpIn.general
234 PTOV7.ST.Op.general 287 RBRF5.ST.OpEx.general
235 PTOV8.ST.Str.general 288 RBRF5.ST.OpIn.general
236 PTOV8.ST.Op.general 289 RBRF6.ST.OpEx.general
237 PTOV9.ST.Str.general 290 RBRF6.ST.OpIn.general
238 PTOV9.ST.Op.general 291 RBRF7.ST.OpEx.general
239 PTOV10.ST.Str.general 292 RBRF7.ST.OpIn.general
240 PTOV10.ST.Op.general 293 RBRF8.ST.OpEx.general
241 PTRC1.ST.Tr.general 294 RBRF8.ST.OpIn.general
242 PTRC1.ST.Op.general 295 RBRF9.ST.OpEx.general
243 PTRC2.ST.Tr.general 296 RBRF9.ST.OpIn.general
244 PTRC2.ST.Op.general 297 RBRF10.ST.OpEx.general
245 PTRC3.ST.Tr.general 298 RBRF10.ST.OpIn.general
246 PTRC3.ST.Op.general 299 RBRF11.ST.OpEx.general
247 PTRC4.ST.Tr.general 300 RBRF11.ST.OpIn.general
248 PTRC4.ST.Op.general 301 RBRF12.ST.OpEx.general
249 PTRC5.ST.Tr.general 302 RBRF12.ST.OpIn.general
250 PTRC5.ST.Op.general 303 RBRF13.ST.OpEx.general
251 PTRC6.ST.Tr.general 304 RBRF13.ST.OpIn.general
252 PTRC6.ST.Op.general 305 RBRF14.ST.OpEx.general
253 PTUV1.ST.Str.general 306 RBRF14.ST.OpIn.general
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
307 RBRF15.ST.OpEx.general 360 CSWI7.ST.Pos.stVal
308 RBRF15.ST.OpIn.general 361 CSWI8.ST.Loc.stVal
309 RBRF16.ST.OpEx.general 362 CSWI8.ST.Pos.stVal
310 RBRF16.ST.OpIn.general 363 CSWI9.ST.Loc.stVal
311 RBRF17.ST.OpEx.general 364 CSWI9.ST.Pos.stVal
312 RBRF17.ST.OpIn.general 365 CSWI10.ST.Loc.stVal
B 313 RBRF18.ST.OpEx.general 366 CSWI10.ST.Pos.stVal
314 RBRF18.ST.OpIn.general 367 CSWI11.ST.Loc.stVal
315 RBRF19.ST.OpEx.general 368 CSWI11.ST.Pos.stVal
316 RBRF19.ST.OpIn.general 369 CSWI12.ST.Loc.stVal
317 RBRF20.ST.OpEx.general 370 CSWI12.ST.Pos.stVal
318 RBRF20.ST.OpIn.general 371 CSWI13.ST.Loc.stVal
319 RBRF21.ST.OpEx.general 372 CSWI13.ST.Pos.stVal
320 RBRF21.ST.OpIn.general 373 CSWI14.ST.Loc.stVal
321 RBRF22.ST.OpEx.general 374 CSWI14.ST.Pos.stVal
322 RBRF22.ST.OpIn.general 375 CSWI15.ST.Loc.stVal
323 RBRF23.ST.OpEx.general 376 CSWI15.ST.Pos.stVal
324 RBRF23.ST.OpIn.general 377 CSWI16.ST.Loc.stVal
325 RBRF24.ST.OpEx.general 378 CSWI16.ST.Pos.stVal
326 RBRF24.ST.OpIn.general 379 CSWI17.ST.Loc.stVal
327 RFLO1.MX.FltDiskm.mag.f 380 CSWI17.ST.Pos.stVal
328 RFLO2.MX.FltDiskm.mag.f 381 CSWI18.ST.Loc.stVal
329 RFLO3.MX.FltDiskm.mag.f 382 CSWI18.ST.Pos.stVal
330 RFLO4.MX.FltDiskm.mag.f 383 CSWI19.ST.Loc.stVal
331 RFLO5.MX.FltDiskm.mag.f 384 CSWI19.ST.Pos.stVal
332 RPSB1.ST.Str.general 385 CSWI20.ST.Loc.stVal
333 RPSB1.ST.Op.general 386 CSWI20.ST.Pos.stVal
334 RPSB1.ST.BlkZn.stVal 387 CSWI21.ST.Loc.stVal
335 RREC1.ST.Op.general 388 CSWI21.ST.Pos.stVal
336 RREC1.ST.AutoRecSt.stVal 389 CSWI22.ST.Loc.stVal
337 RREC2.ST.Op.general 390 CSWI22.ST.Pos.stVal
338 RREC2.ST.AutoRecSt.stVal 391 CSWI23.ST.Loc.stVal
339 RREC3.ST.Op.general 392 CSWI23.ST.Pos.stVal
340 RREC3.ST.AutoRecSt.stVal 393 CSWI24.ST.Loc.stVal
341 RREC4.ST.Op.general 394 CSWI24.ST.Pos.stVal
342 RREC4.ST.AutoRecSt.stVal 395 CSWI25.ST.Loc.stVal
343 RREC5.ST.Op.general 396 CSWI25.ST.Pos.stVal
344 RREC5.ST.AutoRecSt.stVal 397 CSWI26.ST.Loc.stVal
345 RREC6.ST.Op.general 398 CSWI26.ST.Pos.stVal
346 RREC6.ST.AutoRecSt.stVal 399 CSWI27.ST.Loc.stVal
347 CSWI1.ST.Loc.stVal 400 CSWI27.ST.Pos.stVal
348 CSWI1.ST.Pos.stVal 401 CSWI28.ST.Loc.stVal
349 CSWI2.ST.Loc.stVal 402 CSWI28.ST.Pos.stVal
350 CSWI2.ST.Pos.stVal 403 CSWI29.ST.Loc.stVal
351 CSWI3.ST.Loc.stVal 404 CSWI29.ST.Pos.stVal
352 CSWI3.ST.Pos.stVal 405 CSWI30.ST.Loc.stVal
353 CSWI4.ST.Loc.stVal 406 CSWI30.ST.Pos.stVal
354 CSWI4.ST.Pos.stVal 407 GGIO1.ST.Ind1.stVal
355 CSWI5.ST.Loc.stVal 408 GGIO1.ST.Ind2.stVal
356 CSWI5.ST.Pos.stVal 409 GGIO1.ST.Ind3.stVal
357 CSWI6.ST.Loc.stVal 410 GGIO1.ST.Ind4.stVal
358 CSWI6.ST.Pos.stVal 411 GGIO1.ST.Ind5.stVal
359 CSWI7.ST.Loc.stVal 412 GGIO1.ST.Ind6.stVal
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
413 GGIO1.ST.Ind7.stVal 466 GGIO1.ST.Ind60.stVal
414 GGIO1.ST.Ind8.stVal 467 GGIO1.ST.Ind61.stVal
415 GGIO1.ST.Ind9.stVal 468 GGIO1.ST.Ind62.stVal
416 GGIO1.ST.Ind10.stVal 469 GGIO1.ST.Ind63.stVal
417 GGIO1.ST.Ind11.stVal 470 GGIO1.ST.Ind64.stVal
418 GGIO1.ST.Ind12.stVal 471 GGIO1.ST.Ind65.stVal
419 GGIO1.ST.Ind13.stVal 472 GGIO1.ST.Ind66.stVal B
420 GGIO1.ST.Ind14.stVal 473 GGIO1.ST.Ind67.stVal
421 GGIO1.ST.Ind15.stVal 474 GGIO1.ST.Ind68.stVal
422 GGIO1.ST.Ind16.stVal 475 GGIO1.ST.Ind69.stVal
423 GGIO1.ST.Ind17.stVal 476 GGIO1.ST.Ind70.stVal
424 GGIO1.ST.Ind18.stVal 477 GGIO1.ST.Ind71.stVal
425 GGIO1.ST.Ind19.stVal 478 GGIO1.ST.Ind72.stVal
426 GGIO1.ST.Ind20.stVal 479 GGIO1.ST.Ind73.stVal
427 GGIO1.ST.Ind21.stVal 480 GGIO1.ST.Ind74.stVal
428 GGIO1.ST.Ind22.stVal 481 GGIO1.ST.Ind75.stVal
429 GGIO1.ST.Ind23.stVal 482 GGIO1.ST.Ind76.stVal
430 GGIO1.ST.Ind24.stVal 483 GGIO1.ST.Ind77.stVal
431 GGIO1.ST.Ind25.stVal 484 GGIO1.ST.Ind78.stVal
432 GGIO1.ST.Ind26.stVal 485 GGIO1.ST.Ind79.stVal
433 GGIO1.ST.Ind27.stVal 486 GGIO1.ST.Ind80.stVal
434 GGIO1.ST.Ind28.stVal 487 GGIO1.ST.Ind81.stVal
435 GGIO1.ST.Ind29.stVal 488 GGIO1.ST.Ind82.stVal
436 GGIO1.ST.Ind30.stVal 489 GGIO1.ST.Ind83.stVal
437 GGIO1.ST.Ind31.stVal 490 GGIO1.ST.Ind84.stVal
438 GGIO1.ST.Ind32.stVal 491 GGIO1.ST.Ind85.stVal
439 GGIO1.ST.Ind33.stVal 492 GGIO1.ST.Ind86.stVal
440 GGIO1.ST.Ind34.stVal 493 GGIO1.ST.Ind87.stVal
441 GGIO1.ST.Ind35.stVal 494 GGIO1.ST.Ind88.stVal
442 GGIO1.ST.Ind36.stVal 495 GGIO1.ST.Ind89.stVal
443 GGIO1.ST.Ind37.stVal 496 GGIO1.ST.Ind90.stVal
444 GGIO1.ST.Ind38.stVal 497 GGIO1.ST.Ind91.stVal
445 GGIO1.ST.Ind39.stVal 498 GGIO1.ST.Ind92.stVal
446 GGIO1.ST.Ind40.stVal 499 GGIO1.ST.Ind93.stVal
447 GGIO1.ST.Ind41.stVal 500 GGIO1.ST.Ind94.stVal
448 GGIO1.ST.Ind42.stVal 501 GGIO1.ST.Ind95.stVal
449 GGIO1.ST.Ind43.stVal 502 GGIO1.ST.Ind96.stVal
450 GGIO1.ST.Ind44.stVal 503 GGIO1.ST.Ind97.stVal
451 GGIO1.ST.Ind45.stVal 504 GGIO1.ST.Ind98.stVal
452 GGIO1.ST.Ind46.stVal 505 GGIO1.ST.Ind99.stVal
453 GGIO1.ST.Ind47.stVal 506 GGIO1.ST.Ind100.stVal
454 GGIO1.ST.Ind48.stVal 507 GGIO1.ST.Ind101.stVal
455 GGIO1.ST.Ind49.stVal 508 GGIO1.ST.Ind102.stVal
456 GGIO1.ST.Ind50.stVal 509 GGIO1.ST.Ind103.stVal
457 GGIO1.ST.Ind51.stVal 510 GGIO1.ST.Ind104.stVal
458 GGIO1.ST.Ind52.stVal 511 GGIO1.ST.Ind105.stVal
459 GGIO1.ST.Ind53.stVal 512 GGIO1.ST.Ind106.stVal
460 GGIO1.ST.Ind54.stVal 513 GGIO1.ST.Ind107.stVal
461 GGIO1.ST.Ind55.stVal 514 GGIO1.ST.Ind108.stVal
462 GGIO1.ST.Ind56.stVal 515 GGIO1.ST.Ind109.stVal
463 GGIO1.ST.Ind57.stVal 516 GGIO1.ST.Ind110.stVal
464 GGIO1.ST.Ind58.stVal 517 GGIO1.ST.Ind111.stVal
465 GGIO1.ST.Ind59.stVal 518 GGIO1.ST.Ind112.stVal
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
519 GGIO1.ST.Ind113.stVal 572 MMXU2.MX.TotW.mag.f
520 GGIO1.ST.Ind114.stVal 573 MMXU2.MX.TotVAr.mag.f
521 GGIO1.ST.Ind115.stVal 574 MMXU2.MX.TotVA.mag.f
522 GGIO1.ST.Ind116.stVal 575 MMXU2.MX.TotPF.mag.f
523 GGIO1.ST.Ind117.stVal 576 MMXU2.MX.Hz.mag.f
524 GGIO1.ST.Ind118.stVal 577 MMXU2.MX.PPV.phsAB.cVal.mag.f
B 525 GGIO1.ST.Ind119.stVal 578 MMXU2.MX.PPV.phsAB.cVal.ang.f
526 GGIO1.ST.Ind120.stVal 579 MMXU2.MX.PPV.phsBC.cVal.mag.f
527 GGIO1.ST.Ind121.stVal 580 MMXU2.MX.PPV.phsBC.cVal.ang.f
528 GGIO1.ST.Ind122.stVal 581 MMXU2.MX.PPV.phsCA.cVal.mag.f
529 GGIO1.ST.Ind123.stVal 582 MMXU2.MX.PPV.phsCA.cVal.ang.f
530 GGIO1.ST.Ind124.stVal 583 MMXU2.MX.PhV.phsA.cVal.mag.f
531 GGIO1.ST.Ind125.stVal 584 MMXU2.MX.PhV.phsA.cVal.ang.f
532 GGIO1.ST.Ind126.stVal 585 MMXU2.MX.PhV.phsB.cVal.mag.f
533 GGIO1.ST.Ind127.stVal 586 MMXU2.MX.PhV.phsB.cVal.ang.f
534 GGIO1.ST.Ind128.stVal 587 MMXU2.MX.PhV.phsC.cVal.mag.f
535 MMXU1.MX.TotW.mag.f 588 MMXU2.MX.PhV.phsC.cVal.ang.f
536 MMXU1.MX.TotVAr.mag.f 589 MMXU2.MX.A.phsA.cVal.mag.f
537 MMXU1.MX.TotVA.mag.f 590 MMXU2.MX.A.phsA.cVal.ang.f
538 MMXU1.MX.TotPF.mag.f 591 MMXU2.MX.A.phsB.cVal.mag.f
539 MMXU1.MX.Hz.mag.f 592 MMXU2.MX.A.phsB.cVal.ang.f
540 MMXU1.MX.PPV.phsAB.cVal.mag.f 593 MMXU2.MX.A.phsC.cVal.mag.f
541 MMXU1.MX.PPV.phsAB.cVal.ang.f 594 MMXU2.MX.A.phsC.cVal.ang.f
542 MMXU1.MX.PPV.phsBC.cVal.mag.f 595 MMXU2.MX.A.neut.cVal.mag.f
543 MMXU1.MX.PPV.phsBC.cVal.ang.f 596 MMXU2.MX.A.neut.cVal.ang.f
544 MMXU1.MX.PPV.phsCA.cVal.mag.f 597 MMXU2.MX.W.phsA.cVal.mag.f
545 MMXU1.MX.PPV.phsCA.cVal.ang.f 598 MMXU2.MX.W.phsB.cVal.mag.f
546 MMXU1.MX.PhV.phsA.cVal.mag.f 599 MMXU2.MX.W.phsC.cVal.mag.f
547 MMXU1.MX.PhV.phsA.cVal.ang.f 600 MMXU2.MX.VAr.phsA.cVal.mag.f
548 MMXU1.MX.PhV.phsB.cVal.mag.f 601 MMXU2.MX.VAr.phsB.cVal.mag.f
549 MMXU1.MX.PhV.phsB.cVal.ang.f 602 MMXU2.MX.VAr.phsC.cVal.mag.f
550 MMXU1.MX.PhV.phsC.cVal.mag.f 603 MMXU2.MX.VA.phsA.cVal.mag.f
551 MMXU1.MX.PhV.phsC.cVal.ang.f 604 MMXU2.MX.VA.phsB.cVal.mag.f
552 MMXU1.MX.A.phsA.cVal.mag.f 605 MMXU2.MX.VA.phsC.cVal.mag.f
553 MMXU1.MX.A.phsA.cVal.ang.f 606 MMXU2.MX.PF.phsA.cVal.mag.f
554 MMXU1.MX.A.phsB.cVal.mag.f 607 MMXU2.MX.PF.phsB.cVal.mag.f
555 MMXU1.MX.A.phsB.cVal.ang.f 608 MMXU2.MX.PF.phsC.cVal.mag.f
556 MMXU1.MX.A.phsC.cVal.mag.f 609 MMXU3.MX.TotW.mag.f
557 MMXU1.MX.A.phsC.cVal.ang.f 610 MMXU3.MX.TotVAr.mag.f
558 MMXU1.MX.A.neut.cVal.mag.f 611 MMXU3.MX.TotVA.mag.f
559 MMXU1.MX.A.neut.cVal.ang.f 612 MMXU3.MX.TotPF.mag.f
560 MMXU1.MX.W.phsA.cVal.mag.f 613 MMXU3.MX.Hz.mag.f
561 MMXU1.MX.W.phsB.cVal.mag.f 614 MMXU3.MX.PPV.phsAB.cVal.mag.f
562 MMXU1.MX.W.phsC.cVal.mag.f 615 MMXU3.MX.PPV.phsAB.cVal.ang.f
563 MMXU1.MX.VAr.phsA.cVal.mag.f 616 MMXU3.MX.PPV.phsBC.cVal.mag.f
564 MMXU1.MX.VAr.phsB.cVal.mag.f 617 MMXU3.MX.PPV.phsBC.cVal.ang.f
565 MMXU1.MX.VAr.phsC.cVal.mag.f 618 MMXU3.MX.PPV.phsCA.cVal.mag.f
566 MMXU1.MX.VA.phsA.cVal.mag.f 619 MMXU3.MX.PPV.phsCA.cVal.ang.f
567 MMXU1.MX.VA.phsB.cVal.mag.f 620 MMXU3.MX.PhV.phsA.cVal.mag.f
568 MMXU1.MX.VA.phsC.cVal.mag.f 621 MMXU3.MX.PhV.phsA.cVal.ang.f
569 MMXU1.MX.PF.phsA.cVal.mag.f 622 MMXU3.MX.PhV.phsB.cVal.mag.f
570 MMXU1.MX.PF.phsB.cVal.mag.f 623 MMXU3.MX.PhV.phsB.cVal.ang.f
571 MMXU1.MX.PF.phsC.cVal.mag.f 624 MMXU3.MX.PhV.phsC.cVal.mag.f
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
625 MMXU3.MX.PhV.phsC.cVal.ang.f 678 MMXU4.MX.VA.phsB.cVal.mag.f
626 MMXU3.MX.A.phsA.cVal.mag.f 679 MMXU4.MX.VA.phsC.cVal.mag.f
627 MMXU3.MX.A.phsA.cVal.ang.f 680 MMXU4.MX.PF.phsA.cVal.mag.f
628 MMXU3.MX.A.phsB.cVal.mag.f 681 MMXU4.MX.PF.phsB.cVal.mag.f
629 MMXU3.MX.A.phsB.cVal.ang.f 682 MMXU4.MX.PF.phsC.cVal.mag.f
630 MMXU3.MX.A.phsC.cVal.mag.f 683 MMXU5.MX.TotW.mag.f
631 MMXU3.MX.A.phsC.cVal.ang.f 684 MMXU5.MX.TotVAr.mag.f B
632 MMXU3.MX.A.neut.cVal.mag.f 685 MMXU5.MX.TotVA.mag.f
633 MMXU3.MX.A.neut.cVal.ang.f 686 MMXU5.MX.TotPF.mag.f
634 MMXU3.MX.W.phsA.cVal.mag.f 687 MMXU5.MX.Hz.mag.f
635 MMXU3.MX.W.phsB.cVal.mag.f 688 MMXU5.MX.PPV.phsAB.cVal.mag.f
636 MMXU3.MX.W.phsC.cVal.mag.f 689 MMXU5.MX.PPV.phsAB.cVal.ang.f
637 MMXU3.MX.VAr.phsA.cVal.mag.f 690 MMXU5.MX.PPV.phsBC.cVal.mag.f
638 MMXU3.MX.VAr.phsB.cVal.mag.f 691 MMXU5.MX.PPV.phsBC.cVal.ang.f
639 MMXU3.MX.VAr.phsC.cVal.mag.f 692 MMXU5.MX.PPV.phsCA.cVal.mag.f
640 MMXU3.MX.VA.phsA.cVal.mag.f 693 MMXU5.MX.PPV.phsCA.cVal.ang.f
641 MMXU3.MX.VA.phsB.cVal.mag.f 694 MMXU5.MX.PhV.phsA.cVal.mag.f
642 MMXU3.MX.VA.phsC.cVal.mag.f 695 MMXU5.MX.PhV.phsA.cVal.ang.f
643 MMXU3.MX.PF.phsA.cVal.mag.f 696 MMXU5.MX.PhV.phsB.cVal.mag.f
644 MMXU3.MX.PF.phsB.cVal.mag.f 697 MMXU5.MX.PhV.phsB.cVal.ang.f
645 MMXU3.MX.PF.phsC.cVal.mag.f 698 MMXU5.MX.PhV.phsC.cVal.mag.f
646 MMXU4.MX.TotW.mag.f 699 MMXU5.MX.PhV.phsC.cVal.ang.f
647 MMXU4.MX.TotVAr.mag.f 700 MMXU5.MX.A.phsA.cVal.mag.f
648 MMXU4.MX.TotVA.mag.f 701 MMXU5.MX.A.phsA.cVal.ang.f
649 MMXU4.MX.TotPF.mag.f 702 MMXU5.MX.A.phsB.cVal.mag.f
650 MMXU4.MX.Hz.mag.f 703 MMXU5.MX.A.phsB.cVal.ang.f
651 MMXU4.MX.PPV.phsAB.cVal.mag.f 704 MMXU5.MX.A.phsC.cVal.mag.f
652 MMXU4.MX.PPV.phsAB.cVal.ang.f 705 MMXU5.MX.A.phsC.cVal.ang.f
653 MMXU4.MX.PPV.phsBC.cVal.mag.f 706 MMXU5.MX.A.neut.cVal.mag.f
654 MMXU4.MX.PPV.phsBC.cVal.ang.f 707 MMXU5.MX.A.neut.cVal.ang.f
655 MMXU4.MX.PPV.phsCA.cVal.mag.f 708 MMXU5.MX.W.phsA.cVal.mag.f
656 MMXU4.MX.PPV.phsCA.cVal.ang.f 709 MMXU5.MX.W.phsB.cVal.mag.f
657 MMXU4.MX.PhV.phsA.cVal.mag.f 710 MMXU5.MX.W.phsC.cVal.mag.f
658 MMXU4.MX.PhV.phsA.cVal.ang.f 711 MMXU5.MX.VAr.phsA.cVal.mag.f
659 MMXU4.MX.PhV.phsB.cVal.mag.f 712 MMXU5.MX.VAr.phsB.cVal.mag.f
660 MMXU4.MX.PhV.phsB.cVal.ang.f 713 MMXU5.MX.VAr.phsC.cVal.mag.f
661 MMXU4.MX.PhV.phsC.cVal.mag.f 714 MMXU5.MX.VA.phsA.cVal.mag.f
662 MMXU4.MX.PhV.phsC.cVal.ang.f 715 MMXU5.MX.VA.phsB.cVal.mag.f
663 MMXU4.MX.A.phsA.cVal.mag.f 716 MMXU5.MX.VA.phsC.cVal.mag.f
664 MMXU4.MX.A.phsA.cVal.ang.f 717 MMXU5.MX.PF.phsA.cVal.mag.f
665 MMXU4.MX.A.phsB.cVal.mag.f 718 MMXU5.MX.PF.phsB.cVal.mag.f
666 MMXU4.MX.A.phsB.cVal.ang.f 719 MMXU5.MX.PF.phsC.cVal.mag.f
667 MMXU4.MX.A.phsC.cVal.mag.f 720 MMXU6.MX.TotW.mag.f
668 MMXU4.MX.A.phsC.cVal.ang.f 721 MMXU6.MX.TotVAr.mag.f
669 MMXU4.MX.A.neut.cVal.mag.f 722 MMXU6.MX.TotVA.mag.f
670 MMXU4.MX.A.neut.cVal.ang.f 723 MMXU6.MX.TotPF.mag.f
671 MMXU4.MX.W.phsA.cVal.mag.f 724 MMXU6.MX.Hz.mag.f
672 MMXU4.MX.W.phsB.cVal.mag.f 725 MMXU6.MX.PPV.phsAB.cVal.mag.f
673 MMXU4.MX.W.phsC.cVal.mag.f 726 MMXU6.MX.PPV.phsAB.cVal.ang.f
674 MMXU4.MX.VAr.phsA.cVal.mag.f 727 MMXU6.MX.PPV.phsBC.cVal.mag.f
675 MMXU4.MX.VAr.phsB.cVal.mag.f 728 MMXU6.MX.PPV.phsBC.cVal.ang.f
676 MMXU4.MX.VAr.phsC.cVal.mag.f 729 MMXU6.MX.PPV.phsCA.cVal.mag.f
677 MMXU4.MX.VA.phsA.cVal.mag.f 730 MMXU6.MX.PPV.phsCA.cVal.ang.f
Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
731 MMXU6.MX.PhV.phsA.cVal.mag.f 784 GGIO4.MX.AnIn28.mag.f
732 MMXU6.MX.PhV.phsA.cVal.ang.f 785 GGIO4.MX.AnIn29.mag.f
733 MMXU6.MX.PhV.phsB.cVal.mag.f 786 GGIO4.MX.AnIn30.mag.f
734 MMXU6.MX.PhV.phsB.cVal.ang.f 787 GGIO4.MX.AnIn31.mag.f
735 MMXU6.MX.PhV.phsC.cVal.mag.f 788 GGIO4.MX.AnIn32.mag.f
736 MMXU6.MX.PhV.phsC.cVal.ang.f 789 XSWI1.ST.Loc.stVal
B 737 MMXU6.MX.A.phsA.cVal.mag.f 790 XSWI1.ST.Pos.stVal
738 MMXU6.MX.A.phsA.cVal.ang.f 791 XSWI2.ST.Loc.stVal
739 MMXU6.MX.A.phsB.cVal.mag.f 792 XSWI2.ST.Pos.stVal
740 MMXU6.MX.A.phsB.cVal.ang.f 793 XSWI3.ST.Loc.stVal
741 MMXU6.MX.A.phsC.cVal.mag.f 794 XSWI3.ST.Pos.stVal
742 MMXU6.MX.A.phsC.cVal.ang.f 795 XSWI4.ST.Loc.stVal
743 MMXU6.MX.A.neut.cVal.mag.f 796 XSWI4.ST.Pos.stVal
744 MMXU6.MX.A.neut.cVal.ang.f 797 XSWI5.ST.Loc.stVal
745 MMXU6.MX.W.phsA.cVal.mag.f 798 XSWI5.ST.Pos.stVal
746 MMXU6.MX.W.phsB.cVal.mag.f 799 XSWI6.ST.Loc.stVal
747 MMXU6.MX.W.phsC.cVal.mag.f 800 XSWI6.ST.Pos.stVal
748 MMXU6.MX.VAr.phsA.cVal.mag.f 801 XSWI7.ST.Loc.stVal
749 MMXU6.MX.VAr.phsB.cVal.mag.f 802 XSWI7.ST.Pos.stVal
750 MMXU6.MX.VAr.phsC.cVal.mag.f 803 XSWI8.ST.Loc.stVal
751 MMXU6.MX.VA.phsA.cVal.mag.f 804 XSWI8.ST.Pos.stVal
752 MMXU6.MX.VA.phsB.cVal.mag.f 805 XSWI9.ST.Loc.stVal
753 MMXU6.MX.VA.phsC.cVal.mag.f 806 XSWI9.ST.Pos.stVal
754 MMXU6.MX.PF.phsA.cVal.mag.f 807 XSWI10.ST.Loc.stVal
755 MMXU6.MX.PF.phsB.cVal.mag.f 808 XSWI10.ST.Pos.stVal
756 MMXU6.MX.PF.phsC.cVal.mag.f 809 XSWI11.ST.Loc.stVal
757 GGIO4.MX.AnIn1.mag.f 810 XSWI11.ST.Pos.stVal
758 GGIO4.MX.AnIn2.mag.f 811 XSWI12.ST.Loc.stVal
759 GGIO4.MX.AnIn3.mag.f 812 XSWI12.ST.Pos.stVal
760 GGIO4.MX.AnIn4.mag.f 813 XSWI13.ST.Loc.stVal
761 GGIO4.MX.AnIn5.mag.f 814 XSWI13.ST.Pos.stVal
762 GGIO4.MX.AnIn6.mag.f 815 XSWI14.ST.Loc.stVal
763 GGIO4.MX.AnIn7.mag.f 816 XSWI14.ST.Pos.stVal
764 GGIO4.MX.AnIn8.mag.f 817 XSWI15.ST.Loc.stVal
765 GGIO4.MX.AnIn9.mag.f 818 XSWI15.ST.Pos.stVal
766 GGIO4.MX.AnIn10.mag.f 819 XSWI16.ST.Loc.stVal
767 GGIO4.MX.AnIn11.mag.f 820 XSWI16.ST.Pos.stVal
768 GGIO4.MX.AnIn12.mag.f 821 XSWI17.ST.Loc.stVal
769 GGIO4.MX.AnIn13.mag.f 822 XSWI17.ST.Pos.stVal
770 GGIO4.MX.AnIn14.mag.f 823 XSWI18.ST.Loc.stVal
771 GGIO4.MX.AnIn15.mag.f 824 XSWI18.ST.Pos.stVal
772 GGIO4.MX.AnIn16.mag.f 825 XSWI19.ST.Loc.stVal
773 GGIO4.MX.AnIn17.mag.f 826 XSWI19.ST.Pos.stVal
774 GGIO4.MX.AnIn18.mag.f 827 XSWI20.ST.Loc.stVal
775 GGIO4.MX.AnIn19.mag.f 828 XSWI20.ST.Pos.stVal
776 GGIO4.MX.AnIn20.mag.f 829 XSWI21.ST.Loc.stVal
777 GGIO4.MX.AnIn21.mag.f 830 XSWI21.ST.Pos.stVal
778 GGIO4.MX.AnIn22.mag.f 831 XSWI22.ST.Loc.stVal
779 GGIO4.MX.AnIn23.mag.f 832 XSWI22.ST.Pos.stVal
780 GGIO4.MX.AnIn24.mag.f 833 XSWI23.ST.Loc.stVal
781 GGIO4.MX.AnIn25.mag.f 834 XSWI23.ST.Pos.stVal
782 GGIO4.MX.AnIn26.mag.f 835 XSWI24.ST.Loc.stVal
783 GGIO4.MX.AnIn27.mag.f 836 XSWI24.ST.Pos.stVal
Enumeration IEC 61850 report dataset items Enumeration GOOSE dataset items
837 XCBR1.ST.Loc.stVal 36 GGIO1.ST.Ind18.stVal
838 XCBR1.ST.Pos.stVal 37 GGIO1.ST.Ind19.q
839 XCBR2.ST.Loc.stVal 38 GGIO1.ST.Ind19.stVal
840 XCBR2.ST.Pos.stVal 39 GGIO1.ST.Ind20.q
841 XCBR3.ST.Loc.stVal 40 GGIO1.ST.Ind20.stVal
842 XCBR3.ST.Pos.stVal 41 GGIO1.ST.Ind21.q
843 XCBR4.ST.Loc.stVal 42 GGIO1.ST.Ind21.stVal B
844 XCBR4.ST.Pos.stVal 43 GGIO1.ST.Ind22.q
845 XCBR5.ST.Loc.stVal 44 GGIO1.ST.Ind22.stVal
846 XCBR5.ST.Pos.stVal 45 GGIO1.ST.Ind23.q
847 XCBR6.ST.Loc.stVal 46 GGIO1.ST.Ind23.stVal
848 XCBR6.ST.Pos.stVal 47 GGIO1.ST.Ind24.q
48 GGIO1.ST.Ind24.stVal
49 GGIO1.ST.Ind25.q
F616
50 GGIO1.ST.Ind25.stVal
ENUMERATION: IEC 61850 GOOSE DATASET ITEMS
51 GGIO1.ST.Ind26.q
Enumeration GOOSE dataset items 52 GGIO1.ST.Ind26.stVal
0 None 53 GGIO1.ST.Ind27.q
1 GGIO1.ST.Ind1.q 54 GGIO1.ST.Ind27.stVal
2 GGIO1.ST.Ind1.stVal 55 GGIO1.ST.Ind28.q
3 GGIO1.ST.Ind2.q 56 GGIO1.ST.Ind28.stVal
4 GGIO1.ST.Ind2.stVal 57 GGIO1.ST.Ind29.q
5 GGIO1.ST.Ind3.q 58 GGIO1.ST.Ind29.stVal
6 GGIO1.ST.Ind3.stVal 59 GGIO1.ST.Ind30.q
7 GGIO1.ST.Ind4.q 60 GGIO1.ST.Ind30.stVal
8 GGIO1.ST.Ind4.stVal 61 GGIO1.ST.Ind31.q
9 GGIO1.ST.Ind5.q 62 GGIO1.ST.Ind31.stVal
10 GGIO1.ST.Ind5.stVal 63 GGIO1.ST.Ind32.q
11 GGIO1.ST.Ind6.q 64 GGIO1.ST.Ind32.stVal
12 GGIO1.ST.Ind6.stVal 65 GGIO1.ST.Ind33.q
13 GGIO1.ST.Ind7.q 66 GGIO1.ST.Ind33.stVal
14 GGIO1.ST.Ind7.stVal 67 GGIO1.ST.Ind34.q
15 GGIO1.ST.Ind8.q 68 GGIO1.ST.Ind34.stVal
16 GGIO1.ST.Ind8.stVal 69 GGIO1.ST.Ind35.q
17 GGIO1.ST.Ind9.q 70 GGIO1.ST.Ind35.stVal
18 GGIO1.ST.Ind9.stVal 71 GGIO1.ST.Ind36.q
19 GGIO1.ST.Ind10.q 72 GGIO1.ST.Ind36.stVal
20 GGIO1.ST.Ind10.stVal 73 GGIO1.ST.Ind37.q
21 GGIO1.ST.Ind11.q 74 GGIO1.ST.Ind37.stVal
22 GGIO1.ST.Ind11.stVal 75 GGIO1.ST.Ind38.q
23 GGIO1.ST.Ind12.q 76 GGIO1.ST.Ind38.stVal
24 GGIO1.ST.Ind12.stVal 77 GGIO1.ST.Ind39.q
25 GGIO1.ST.Ind13.q 78 GGIO1.ST.Ind39.stVal
26 GGIO1.ST.Ind13.stVal 79 GGIO1.ST.Ind40.q
27 GGIO1.ST.Ind14.q 80 GGIO1.ST.Ind40.stVal
28 GGIO1.ST.Ind14.stVal 81 GGIO1.ST.Ind41.q
29 GGIO1.ST.Ind15.q 82 GGIO1.ST.Ind41.stVal
30 GGIO1.ST.Ind15.stVal 83 GGIO1.ST.Ind42.q
31 GGIO1.ST.Ind16.q 84 GGIO1.ST.Ind42.stVal
32 GGIO1.ST.Ind16.stVal 85 GGIO1.ST.Ind43.q
33 GGIO1.ST.Ind17.q 86 GGIO1.ST.Ind43.stVal
34 GGIO1.ST.Ind17.stVal 87 GGIO1.ST.Ind44.q
35 GGIO1.ST.Ind18.q 88 GGIO1.ST.Ind44.stVal
The IEC 61850 standard is the result of electric utilities and vendors of electronic equipment to produce standardized com-
munications systems. IEC 61850 is a series of standards describing client/server and peer-to-peer communications, sub-
station design and configuration, testing, environmental and project standards. The complete set includes:
• IEC 61850-1: Introduction and overview
• IEC 61850-2: Glossary
• IEC 61850-3: General requirements
• IEC 61850-4: System and project management
• IEC 61850-5: Communications and requirements for functions and device models
• IEC 61850-6: Configuration description language for communication in electrical substations related to IEDs
• IEC 61850-7-1: Basic communication structure for substation and feeder equipment - Principles and models
C
• IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract communication service
interface (ACSI)
• IEC 61850-7-3: Basic communication structure for substation and feeder equipment – Common data classes
• IEC 61850-7-4: Basic communication structure for substation and feeder equipment – Compatible logical node classes
and data classes
• IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO 9506-1 and ISO 9506-2)
and to ISO/IEC 8802-3
• IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over serial unidirectional multi-
drop point to point link
• IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over ISO/IEC 8802-3
• IEC 61850-10: Conformance testing
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended that all those involved with
any IEC 61850 implementation obtain this document set.
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper (application) layer for transfer
of real-time data. This protocol has been in existence for several of years and provides a set of services suitable for the
transfer of data within a substation LAN environment. Actual MMS protocol services are mapped to IEC 61850 abstract ser-
vices in IEC 61850-8-1.
The G60 relay supports IEC 61850 server services over both TCP/IP and TP4/CLNP (OSI) communication protocol stacks.
The TP4/CLNP profile requires the G60 to have a network address or Network Service Access Point (NSAP) to establish a
communication link. The TCP/IP profile requires the G60 to have an IP address to establish communications. These
addresses are located in the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK menu. Note that the G60
supports IEC 61850 over the TP4/CLNP or TCP/IP stacks, and also operation over both stacks simultaneously. It is possi-
ble to have up to five simultaneous connections (in addition to DNP and Modbus/TCP (non-IEC 61850) connections).
• Client/server: This is a connection-oriented type of communication. The connection is initiated by the client, and com-
munication activity is controlled by the client. IEC 61850 clients are often substation computers running HMI programs
or SOE logging software. Servers are usually substation equipment such as protection relays, meters, RTUs, trans-
former tap changers, or bay controllers.
• Peer-to-peer: This is a non-connection-oriented, high speed type of communication usually between substation equip-
ment such as protection relays. GSSE and GOOSE are methods of peer-to-peer communication.
• Substation configuration language (SCL): A substation configuration language is a number of files used to describe
the configuration of substation equipment. Each configured device has an IEC Capability Description (ICD) file. The
substation single line information is stored in a System Specification Description (SSD) file. The entire substation con-
figuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the combination of the individ-
ual ICD files and the SSD file.
IEC 61850 defines an object-oriented approach to data and services. An IEC 61850 physical device can contain one or
more logical device(s). Each logical device can contain many logical nodes. Each logical node can contain many data
objects. Each data object is composed of data attributes and data attribute components. Services are available at each
level for performing various functions, such as reading, writing, control commands, and reporting.
Each G60 IED represents one IEC 61850 physical device. The physical device contains one logical device, and the logical
device contains many logical nodes. The logical node LPHD1 contains information about the G60 IED physical device. The
logical node LLN0 contains information about the G60 IED logical device.
C The GGIO1 logical node is available in the G60 to provide access to as many 128 digital status points and associated time-
stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status
points for access by clients.
It is intended that clients use GGIO1 in order to access digital status values from the G60. Configuration settings are pro-
vided to allow the selection of the number of digital status indications available in GGIO1 (8 to 128), and to allow the choice
of the G60 FlexLogic™ operands that drive the status of the GGIO1 status indications. Clients can utilize the IEC 61850
buffered and unbuffered reporting features available from GGIO1 in order to build sequence of events (SOE) logs and HMI
display screens. Buffered reporting should generally be used for SOE logs since the buffering capability reduces the
chances of missing data state changes. Unbuffered reporting should generally be used for local status display.
The GGIO2 logical node is available to provide access to the G60 virtual inputs. Virtual inputs are single-point control
(binary) values that can be written by clients. They are generally used as control inputs. GGIO2 provides access to the vir-
tual inputs through the IEC 61850 standard control model (ctlModel) services:
• Status only.
• Direct control with normal security.
• SBO control with normal security.
Configuration settings are available to select the control model for each point. Each virtual input used through GGIO2
should have its VIRTUAL INPUT 1(64) FUNCTION setting programmed as “Enabled” and its corresponding GGIO2 CF SPSCO1(64)
CTLMODEL setting programmed to the appropriate control configuration.
C.2.4 GGIO3: DIGITAL STATUS AND ANALOG VALUES FROM RECEIVED GOOSE DATA
The GGIO3 logical node is available to provide access for clients to values received via configurable GOOSE messages.
The values of the digital status indications and analog values in GGIO3 originate in GOOSE messages sent from other
devices.
The GGIO4 logical node provides access to as many as 32 analog value points, as well as associated timestamps and
quality flags. The data content must be configured before the data can be used. GGIO4 provides analog values for access
by clients.
It is intended that clients use GGIO4 to access generic analog values from the G60. Configuration settings allow the selec-
tion of the number of analog values available in GGIO4 (4 to 32) and the choice of the FlexAnalog™ values that determine
the value of the GGIO4 analog inputs. Clients can utilize polling or the IEC 61850 unbuffered reporting feature available
from GGIO4 in order to obtain the analog values provided by GGIO4.
A limited number of measured analog values are available through the MMXU logical nodes.
Each MMXU logical node provides data from a G60 current and voltage source. There is one MMXU available for each
configurable source (programmed in the SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES menu). MMXU1 provides data
from G60 source 1, and MMXU2 provides data from G60 source 2.
MMXU data is provided in two forms: instantaneous and deadband. The instantaneous values are updated every time a
read operation is performed by a client. The deadband values are calculated as described in IEC 61850 parts 7-1 and 7-3.
The selection of appropriate deadband settings for the G60 is described in chapter 5 of this manual.
IEC 61850 buffered and unbuffered reporting capability is available in all MMXU logical nodes. MMXUx logical nodes pro-
vide the following data for each source:
• MMXU1.MX.TotW: three-phase real power
• MMXU1.MX.TotVAr: three-phase reactive power
C
• MMXU1.MX.TotVA: three-phase apparent power
• MMXU1.MX.TotPF: three-phase power factor
• MMXU1.MX.Hz: frequency
• MMXU1.MX.PPV.phsAB: phase AB voltage magnitude and angle
• MMXU1.MX.PPV.phsBC: phase BC voltage magnitude and angle
• MMXU1.MX.PPV.phsCA: Phase CA voltage magnitude and angle
• MMXU1.MX.PhV.phsA: phase AG voltage magnitude and angle
• MMXU1.MX.PhV.phsB: phase BG voltage magnitude and angle
• MMXU1.MX.PhV.phsC: phase CG voltage magnitude and angle
• MMXU1.MX.A.phsA: phase A current magnitude and angle
• MMXU1.MX.A.phsB: phase B current magnitude and angle
• MMXU1.MX.A.phsC: phase C current magnitude and angle
• MMXU1.MX.A.neut: ground current magnitude and angle
• MMXU1.MX.W.phsA: phase A real power
• MMXU1.MX.W.phsB: phase B real power
• MMXU1.MX.W.phsC: phase C real power
• MMXU1.MX.VAr.phsA: phase A reactive power
• MMXU1.MX.VAr.phsB: phase B reactive power
• MMXU1.MX.VAr.phsC: phase C reactive power
• MMXU1.MX.VA.phsA: phase A apparent power
• MMXU1.MX.VA.phsB: phase B apparent power
• MMXU1.MX.VA.phsC: phase C apparent power
• MMXU1.MX.PF.phsA: phase A power factor
• MMXU1.MX.PF.phsB: phase B power factor
• MMXU1.MX.PF.phsC: phase C power factor
The following list describes the protection elements for all UR-series relays. The G60 relay will contain a subset of protec-
tion elements from this list.
• PDIF: bus differential, transformer instantaneous differential, transformer percent differential, current differential
IEC 61850 buffered and unbuffered reporting is provided in the GGIO1 logical nodes (for binary status values) and MMXU1
to MMXU6 (for analog measured values). Report settings can be configured using the EnerVista UR Setup software, sub-
station configurator software, or via an IEC 61850 client. The following items can be configured:
• TrgOps: Trigger options. The following bits are supported by the G60:
– Bit 1: data-change
– Bit 4: integrity
– Bit 5: general interrogation
• OptFlds: Option Fields. The following bits are supported by the G60:
– Bit 1: sequence-number
– Bit 2: report-time-stamp
C
– Bit 3: reason-for-inclusion
– Bit 4: data-set-name
– Bit 5: data-reference
– Bit 6: buffer-overflow (for buffered reports only)
– Bit 7: entryID (for buffered reports only)
– Bit 8: conf-revision
– Bit 9: segmentation
• IntgPd: Integrity period.
• BufTm: Buffer time.
MMS file services are supported to allow transfer of oscillography, event record, or other files from a G60 relay.
The timestamp values associated with all IEC 61850 data items represent the time of the last change of either the value or
quality flags of the data item. To accomplish this functionality, all IEC 61850 data items must be regularly scanned for data
changes, and the timestamp updated when a change is detected, regardless of the connection status of any IEC 61850 cli-
ents. For applications where there is no IEC 61850 client in use, the IEC 61850 SERVER SCANNING setting can be pro-
grammed as “Disabled”. If a client is in use, this setting should be programmed as “Enabled” to ensure the proper
generation of IEC 61850 timestamps.
The logical device name is used to identify the IEC 61850 logical device that exists within the G60. This name is composed
of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of
the two character strings programmed in the IEDNAME and LD INST settings. The default values for these strings are “IED-
Name” and “LDInst”. These values should be changed to reflect a logical naming convention for all IEC 61850 logical
devices in the system.
C.3.5 LOCATION
The LPHD1 logical node contains a data attribute called location (LPHD1.DC.PhyNam.location). This is a character string
meant to describe the physical location of the G60. This attribute is programmed through the LOCATION setting and its
default value is “Location”. This value should be changed to describe the actual physical location of the G60.
IEC 61850 specifies that each logical node can have a name with a total length of 11 characters. The name is composed of:
• A five or six-character name prefix.
• A four-character standard name (for example, MMXU, GGIO, PIOC, etc.).
• A one or two-character instantiation index.
Complete names are of the form xxxxxxPIOC1, where the xxxxxx character string is configurable. Details regarding the
logical node naming rules are given in IEC 61850 parts 6 and 7-2. It is recommended that a consistent naming convention
be used for an entire substation project.
C A built-in TCP/IP connection timeout of two minutes is employed by the G60 to detect ‘dead’ connections. If there is no data
traffic on a TCP connection for greater than two minutes, the connection will be aborted by the G60. This frees up the con-
nection to be used by other clients. Therefore, when using IEC 61850 reporting, clients should configure report control
block items such that an integrity report will be issued at least every 2 minutes (120000 ms). This ensures that the G60 will
not abort the connection. If other MMS data is being polled on the same connection at least once every 2 minutes, this tim-
eout will not apply.
The G60 relay makes available a number of non-IEC 61850 data items. These data items can be accessed through the
“UR” MMS domain. IEC 61850 data can be accessed through the standard IEC 61850 logical device. To access the non-
IEC data items, the INCLUDE NON-IEC DATA setting must be “Enabled”.
The exact structure and values of the supported IEC 61850 logical nodes can be seen by connecting to a G60 relay with an
MMS browser, such as the “MMS Object Explorer and AXS4-MMS” DDE/OPC server from Sisco Inc.
IEC 61850 specifies two types of peer-to-peer data transfer services: Generic Substation State Events (GSSE) and Generic
Object Oriented Substation Events (GOOSE). GSSE services are compatible with UCA 2.0 GOOSE. IEC 61850 GOOSE
services provide virtual LAN (VLAN) support, Ethernet priority tagging, and Ethertype Application ID configuration. The sup-
port for VLANs and priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be given
a higher priority than standard Ethernet traffic, and they can be separated onto specific VLANs. Because of the additional
features of GOOSE services versus GSSE services, it is recommended that GOOSE be used wherever backwards com-
patibility with GSSE (or UCA 2.0 GOOSE) is not required.
Devices that transmit GSSE and/or GOOSE messages also function as servers. Each GSSE publisher contains a “GSSE
control block” to configure and control the transmission. Each GOOSE publisher contains a “GOOSE control block” to con-
figure and control the transmission. The transmission is also controlled via device settings. These settings can be seen in
the ICD and/or SCD files, or in the device configuration software or files.
IEC 61850 recommends a default priority value of 4 for GOOSE. Ethernet traffic that does not contain a priority tag has a
C
default priority of 1. More details are specified in IEC 61850 part 8-1.
IEC 61850 recommends that the Ethertype Application ID number be configured according to the GOOSE source. In the
G60, the transmitted GOOSE Application ID number must match the configured receive Application ID number in the
receiver. A common number may be used for all GOOSE transmitters in a system. More details are specified in IEC 61850
part 8-1.
IEC 61850 Generic Substation Status Event (GSSE) communication is compatible with UCA GOOSE communication.
GSSE messages contain a number of double point status data items. These items are transmitted in two pre-defined data
structures named DNA and UserSt. Each DNA and UserSt item is referred to as a ‘bit pair’. GSSE messages are transmit-
ted in response to state changes in any of the data points contained in the message. GSSE messages always contain the
same number of DNA and UserSt bit pairs. Depending the on the configuration, only some of these bit pairs may have val-
ues that are of interest to receiving devices.
The GSSE FUNCTION, GSSE ID, and GSSE DESTINATION MAC ADDRESS settings are used to configure GSSE transmission.
GSSE FUNCTION is set to “Enabled” to enable the transmission. If a valid multicast Ethernet MAC address is entered for the
GSSE DESTINATION MAC ADDRESS setting, this address will be used as the destination MAC address for GSSE messages. If
a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the G60 will use the source Ether-
net MAC address as the destination, with the multicast bit set.
The G60 supports two types of IEC 61850 Generic Object Oriented Substation Event (GOOSE) communication: fixed
GOOSE and configurable GOOSE. All GOOSE messages contain IEC 61850 data collected into a dataset. It is this dataset
that is transferred using GOOSE message services. The dataset transferred using the G60 fixed GOOSE is the same data
that is transferred using the GSSE feature; that is, the DNA and UserSt bit pairs. The FlexLogic™ operands that determine
the state of the DNA and UserSt bit pairs are configurable via settings, but the fixed GOOSE dataset always contains the
same DNA/UserSt data structure. Upgrading from GSSE to GOOSE services is simply a matter of enabling fixed GOOSE
and disabling GSSE. The remote inputs and outputs are configured in the same manner for both GSSE and fixed GOOSE.
It is recommended that the fixed GOOSE be used for implementations that require GOOSE data transfer between UR-
series IEDs. Configurable GOOSE may be used for implementations that require GOOSE data transfer between UR-series
IEDs and devices from other manufacturers.
The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the G60.
The G60 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data
transfer between devices.
Items programmed for dataset 1 and 2 will have changes in their status transmitted as soon as the change is detected.
Dataset 1 should be used for high-speed transmission of data that is required for applications such as transfer tripping,
blocking, and breaker fail initiate. At least one digital status value needs to be configured in dataset 1 to enable transmis-
sion of all data configured for dataset 1. Configuring analog data only to dataset 1 will not activate transmission.
Items programmed for datasets 3 through 8 will have changes in their status transmitted at a maximum rate of every
100 ms. Datasets 3 through 8 will regularly analyze each data item configured within them every 100 ms to identify if any
changes have been made. If any changes in the data items are detected, these changes will be transmitted through a
GOOSE message. If there are no changes detected during this 100 ms period, no GOOSE message will be sent.
For all datasets 1 through 8, the integrity GOOSE message will still continue to be sent at the pre-configured rate even if no
changes in the data items are detected.
The GOOSE functionality was enhanced to prevent the relay from flooding a communications network with GOOSE mes-
sages due to an oscillation being created that is triggering a message.
C The G60 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be
caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station
components. If erroneously oscillation is detected, the G60 will stop sending GOOSE messages from the dataset for a min-
imum period of one second. Should the oscillation persist after the one second time-out period, the G60 will continue to
block transmission of the dataset. The G60 will assert the MAINTENANCE ALERT: GGIO Ind XXX oscill self-test error mes-
sage on the front panel display, where XXX denotes the data item detected as oscillating.
The configurable GOOSE feature is recommended for applications that require GOOSE data transfer between UR-series
IEDs and devices from other manufacturers. Fixed GOOSE is recommended for applications that require GOOSE data
transfer between UR-series IEDs.
IEC 61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the
successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact
match in terms of data structure, and that the GOOSE addresses and name strings match exactly. Manual configuration is
possible, but third-party substation configuration software may be used to automate the process. The EnerVista UR Setup-
software can produce IEC 61850 ICD files and import IEC 61850 SCD files produced by a substation configurator (refer to
the IEC 61850 IED configuration section later in this appendix).
The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. The
general steps required for transmission configuration are:
1. Configure the transmission dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
The general steps required for reception configuration are:
1. Configure the reception dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status
value, its associated quality flags, and a floating point analog value.
The following procedure illustrates the transmission configuration.
1. Configure the transmission dataset by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION ÖØ
IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLE
GOOSE 1 ÖØ CONFIG GSE 1 DATASET ITEMS settings menu:
– Set ITEM 1 to “GGIO1.ST.Ind1.q” to indicate quality flags for GGIO1 status indication 1.
– Set ITEM 2 to “GGIO1.ST.Ind1.stVal” to indicate the status value for GGIO1 status indication 1.
The transmission dataset now contains a set of quality flags and a single point status Boolean value. The reception
dataset on the receiving device must exactly match this structure.
2. Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION
ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGU-
RABLE GOOSE 1 settings menu:
– Set ITEM 1 to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.
– Set ITEM 2 to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.
The reception dataset now contains a set of quality flags, a single point status Boolean value, and a floating point ana-
log value. This matches the transmission dataset configuration above.
2. Configure the GOOSE service settings by making the following changes in the INPUTS/OUTPUTS ÖØ REMOTE DEVICES
ÖØ REMOTE DEVICE 1 settings menu:
– Set REMOTE DEVICE 1 ID to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.
– Set REMOTE DEVICE 1 ETYPE APPID to match the Ethertype application ID from the transmitting device. This is “0” in
the example above.
– Set the REMOTE DEVICE 1 DATASET value. This value represents the dataset number in use. Since we are using
configurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.
3. Configure the data by making the following changes in the INPUTS/OUTPUTS ÖØ REMOTE INPUTS ÖØ REMOTE INPUT 1
settings menu:
– Set REMOTE IN 1 DEVICE to “GOOSEOut_1”.
– Set REMOTE IN 1 ITEM to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point status
item to remote input 1.
Remote input 1 can now be used in FlexLogic™ equations or other settings. The G60 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
Ethernet capable devices each contain a unique identifying address called a Media Access Control (MAC) address. This
address cannot be changed and is unique for each Ethernet device produced worldwide. The address is six bytes in length
and is usually represented as six hexadecimal values (for example, 00 A0 F4 01 02 03). It is used in all Ethernet frames as
the ‘source’ address of the frame. Each Ethernet frame also contains a destination address. The destination address can
be different for each Ethernet frame depending on the intended destination of the frame.
A special type of destination address called a multicast address is used when the Ethernet frame can be received by more
than one device. An Ethernet MAC address is multicast when the least significant bit of the first byte is set (for example, 01
00 00 00 00 00 is a multicast address).
GSSE and GOOSE messages must have multicast destination MAC addresses.
By default, the G60 is configured to use an automated multicast MAC scheme. If the G60 destination MAC address setting
is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina-
tion MAC will be the same as the local MAC address, but with the multicast bit set. Thus, if the local MAC address is 00 A0
F4 01 02 03, then the destination MAC address will be 01 A0 F4 01 02 03.
GSSE messages contain an identifier string used by receiving devices to identify the sender of the message, defined in IEC
C 61850 part 8-1 as GsID. This is a programmable 65-character string. This string should be chosen to provide a descriptive
name of the originator of the GSSE message.
GOOSE messages contain an identifier string used by receiving devices to identify the sender of the message, defined in
IEC 61850 part 8-1 as GoID. This programmable 65-character string should be a descriptive name of the originator of the
GOOSE message. GOOSE messages also contain two additional character strings used for identification of the message:
DatSet - the name of the associated dataset, and GoCBRef - the reference (name) of the associated GOOSE control block.
These strings are automatically populated and interpreted by the G60; no settings are required.
The G60 can be configured for IEC 61850 via the EnerVista UR Setup software as follows.
1. An ICD file is generated for the G60 by the EnerVista UR Setup software that describe the capabilities of the IED.
2. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven-
dors) for system configuration.
3. The result is saved to a SCD file, which is then imported back to EnerVista UR Setup to create one or more settings
file(s). The settings file(s) can then be used to update the relay(s) with the new configuration information.
The configuration process is illustrated below.
Import
System
specification data SSD file
System specification tool
System configurator
System Configuration
(network, cross-
communications, IED setting
modification, etc.)
SCD file
EnerVista UR Setup
Ethernet
842790A1.CDR
Before creating an ICD file, the user can customize the IEC 61850 related settings for the IED. For example, the IED name
and logical device instance can be specified to uniquely identify the IED within the substation, or transmission GOOSE
datasets created so that the system configurator can configure the cross-communication links to send GOOSE messages
from the IED. Once the IEC 61850 settings are configured, the ICD creation process will recognize the changes and gener-
ate an ICD file that contains the updated settings.
Some of the IED settings will be modified during they system configuration process. For example, a new IP address may be
assigned, line items in a Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be
changed. While all new configurations will be mapped to the G60 settings file when importing an SCD file, all unchanged
settings will preserve the same values in the new settings file.
These settings can be configured either directly through the relay panel or through the EnerVista UR Setup software (pre-
ferred method). The full list of IEC 61850 related settings for are as follows:
• Network configuration: IP address, IP subnet mask, and default gateway IP address (access through the Settings >
Product Setup > Communications > Network menu tree in EnerVista UR Setup).
• Server configuration: IED name and logical device instance (access through the Settings > Product Setup > Com-
munications > IEC 61850 > Server Configuration menu tree in EnerVista UR Setup).
• Logical node prefixes, which includes prefixes for all logical nodes except LLN0 (access through the Settings > Prod-
uct Setup > Communications > IEC 61850 > Logical Node Prefixes menu tree in EnerVista UR Setup).
• MMXU deadbands, which includes deadbands for all available MMXUs. The number of MMXUs is related to the num-
ber of CT/VT modules in the relay. There are two MMXUs for each CT/VT module. For example, if a relay contains two
CT/VT modules, there will be four MMXUs available (access through the Settings > Product Setup > Communica-
tions > IEC 61850 > MMXU Deadbands menu tree in EnerVista UR Setup).
• GGIO1 status configuration, which includes the number of status points in GGIO1 as well as the potential internal map-
pings for each GGIO1 indication. However only the number of status points will be used in the ICD creation process
(access through the Settings > Product Setup > Communications > IEC 61850 > GGIO1 Status Configuration
menu tree in EnerVista UR Setup).
• GGIO2 control configuration, which includes ctlModels for all SPCSOs within GGIO2 (access through the Settings >
Product Setup > Communications > IEC 61850 > GGIO2 Control Configuration menu tree in EnerVista UR
Setup).
• Configurable transmission GOOSE, which includes eight configurable datasets that can be used for GOOSE transmis-
sion. The GOOSE ID can be specified for each dataset (it must be unique within the IED as well as across the whole
substation), as well as the destination MAC address, VLAN priority, VLAN ID, ETYPE APPID, and the dataset items.
C
The selection of the dataset item is restricted by firmware version; for version 5.9x, only GGIO1.ST.Indx.stVal and
GGIO1.ST.Indx.q are valid selection (where x is between 1 to N, and N is determined by number of GGIO1 status
points). Although configurable transmission GOOSE can also be created and altered by some third-party system con-
figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly
within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com-
munications > IEC 61850 > GSSE/GOOSE Configuration > Transmission > Tx Configurable GOOSE menu tree
in EnerVista UR Setup).
• Configurable reception GOOSE, which includes eight configurable datasets that can be used for GOOSE reception.
However, unlike datasets for transmission, datasets for reception only contains dataset items, and they are usually cre-
ated automatically by process of importing the SCD file (access through the Settings > Product Setup > Communi-
cations > IEC 61850 > GSSE/GOOSE Configuration > Reception > Rx Configurable GOOSE menu tree in
EnerVista UR Setup).
• Remote devices configuration, which includes remote device ID (GOOSE ID or GoID of the incoming transmission
GOOSE dataset), ETYPE APPID (of the GSE communication block for the incoming transmission GOOSE), and
DATASET (which is the name of the associated reception GOOSE dataset). These settings are usually done automat-
ically by process of importing SCD file (access through the Settings > Inputs/Outputs > Remote Devices menu tree
in EnerVista UR Setup).
• Remote inputs configuration, which includes device (remote device ID) and item (which dataset item in the associated
reception GOOSE dataset to map) values. Only the items with cross-communication link created in SCD file should be
mapped. These configurations are usually done automatically by process of importing SCD file (access through the
Settings > Inputs/Outputs > Remote Inputs menu tree in EnerVista UR Setup).
The SCL language is based on XML, and its syntax definition is described as a W3C XML Schema. ICD is one type of SCL
file (which also includes SSD, CID and SCD files). The ICD file describes the capabilities of an IED and consists of four
major sections:
• Header
• Communication
• IEDs
• DataTypeTemplates
SCL
Communication
DataTypeTemplates
842795A1.CDR
Communication
SubNetwork (name)
Address
P (type)
Text
Other P elements
Address
P (type)
Text
Services
AccessPoint (name)
Server
Authentication (none) C
LDevice (inst)
DataSet (name)
DOI (name)
DataSet (name)
DOI (name)
The DataTypeTemplates node defines instantiable logical node types. A logical node type is an instantiable template of the
data of a logical node. A LnodeType is referenced each time that this instantiable type is needed with an IED. A logical
node type template is built from DATA (DO) elements, which again have a DO type, which is derived from the DATA classes
(CDC). DOs consist of attributes (DA) or of elements of already defined DO types (SDO). The attribute (DA) has a func-
tional constraint, and can either have a basic type, be an enumeration, or a structure of a DAType. The DAType is built from
BDA elements, defining the structure elements, which again can be BDA elements of have a base type such as DA.
DataTypeTemplates
DO (name, type)
Other DO elements
DAType (id)
EnumType (id)
An ICD file can be created directly from a connected G60 IED or from an offline G60 settings file with the EnerVista UR
Setup software using the following procedure:
1. Right-click the connected UR-series relay or settings file and select Create ICD File.
2. The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click
OK to generate the file.
The time to create an ICD file from the offline G60 settings file is typically much quicker than create an ICD file directly from
the relay.
System configuration is performed in the system configurator. While many vendors (including GE Multilin) are working their
own system configuration tools, there are some system configurators available in the market (for example, Siemens DIGSI
version 4.6 or above and ASE Visual SCL Beta 0.12).
Although the configuration tools vary from one vendor to another, the procedure is pretty much the same. First, a substation
project must be created, either as an empty template or with some system information by importing a system specification
file (SSD). Then, IEDs are added to the substation. Since each IED is represented by its associated ICD, the ICD files are
imported into the substation project, and the system configurator validates the ICD files during the importing process. If the
ICD files are successfully imported into the substation project, it may be necessary to perform some additional minor steps
to attach the IEDs to the substation (see the system configurator manual for details).
Once all IEDs are inserted into the substation, further configuration is possible, such as:
• Assigning network addresses to individual IEDs.
• Customizing the prefixes of logical nodes.
• Creating cross-communication links (configuring GOOSE messages to send from one IED to others).
When system configurations are complete, the results are saved to an SCD file, which contains not only the configuration
for each IED in the substation, but also the system configuration for the entire substation. Finally, the SCD file is passed
back to the IED configurator (vendor specific tool) to update the new configuration into the IED.
The SCD file consists of at least five major sections:
• Header.
• Substation.
• Communication.
• IED section (one or more).
• DataTypeTemplates.
The root file structure of an SCD file is illustrated below.
SCL
C Substation
Communication
DataTypeTemplates
842791A1.CDR
Substation
PowerSystemResource
GeneralEquipment
EquipmentContainer
VoltageLevel Bay
Voltage
PowerSystemResource
Function SubFunction
GeneralEquipment
842792A1.CDR
The Communication node describes the direct communication connection possibilities between logical nodes by means of
logical buses (sub-networks) and IED access ports. The communication section is structured as follows.
Communication
SubNetwork (name)
ConnectedAP (IED 1)
Address
P (type)
Text
Other P elements
P (type)
Other P elements
ConnectedAP (IED 2)
Address
P (type)
Text
Other P elements
Address
P (type)
Text
Other P elements
Other GSE elements
AccessPoint (name)
Server
Authentication (none)
LDevice (inst)
DataSet elements
C ReportControl elements
DOI elements
Inputs
GSEControl elements
842794A1.CDR
The following procedure describes how to update the G60 with the new configuration from an SCD file with the EnerVista
UR Setup software.
1. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
3. The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and
name for the URS (UR-series relay settings) file.
If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set-
tings file for each IED.
4. After the URS file is created, modify any settings (if required).
5. To update the relay with the new settings, right-click on the settings file in the settings tree and select the Write Set-
tings File to Device item.
6. The software will prompt for the target device. Select the target device from the list provided and click Send. The new
settings will be updated to the selected device.
c1: shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
NOTE M: Mandatory
c2: shall be "M" if support for LOGICAL-NODE model has been declared
c3: shall be "M" if support for DATA model has been declared
NOTE c4: shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has been declared
c5: shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
In the table below, the acronym AA refers to Application Associations (TP: Two Party / MC: Multicast). The c6 to c10 entries
are defined in the notes following the table.
The UR-series of relays supports IEC 61850 logical nodes as indicated in the following table. Note that the actual instantia-
tion of each logical node is determined by the product order code. For example. the logical node “PDIS” (distance protec-
tion) is available only in the D60 Line Distance Relay.
This document is adapted from the IEC 60870-5-104 standard. For ths section the boxes indicate the following: 4 – used in
standard direction;
– not used; – cannot be selected in IEC 60870-5-104 standard.
1. SYSTEM OR DEVICE:
System Definition
Controlling Station Definition (Master)
4 Controlled Station Definition (Slave)
2. NETWORK CONFIGURATION:
Point-to-Point Multipoint
Multiple Point-to-Point Multipoint Star
3. PHYSICAL LAYER
Transmission Speed (control direction):
Unbalanced Interchange Unbalanced Interchange Balanced Interchange Circuit
Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:
if >1200 bits/s: D
100 bits/sec. 2400 bits/sec. 2400 bits/sec.
200 bits/sec. 4800 bits/sec. 4800 bits/sec.
300 bits/sec. 9600 bits/sec. 9600 bits/sec.
600 bits/sec. 19200 bits/sec.
1200 bits/sec. 38400 bits/sec.
56000 bits/sec.
64000 bits/sec.
Transmission Speed (monitor direction):
Unbalanced Interchange Unbalanced Interchange Balanced Interchange Circuit
Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:
if >1200 bits/s:
100 bits/sec. 2400 bits/sec. 2400 bits/sec.
200 bits/sec. 4800 bits/sec. 4800 bits/sec.
300 bits/sec. 9600 bits/sec. 9600 bits/sec.
600 bits/sec. 19200 bits/sec.
1200 bits/sec. 38400 bits/sec.
56000 bits/sec.
64000 bits/sec.
4. LINK LAYER
Link Transmission Procedure: Address Field of the Link:
Balanced Transmision Not Present (Balanced Transmission Only)
Unbalanced Transmission One Octet
Two Octets
Structured
Unstructured
Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard
When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low priority) with the
indicated causes of transmission:
The standard assignment of ADSUs to class 2 messages is used as follows:
5. APPLICATION LAYER
Transmission Mode for Application Data:
Mode 1 (least significant octet first), as defined in Clause 4.10 of IEC 60870-5-4, is used exclusively in this companion
stanadard.
Common Address of ADSU:
One Octet
4 Two Octets
Information Object Address:
One Octet 4 Structured
Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the set
<30> to <40> are used.
Process information in control direction
4 <45> := Single command C_SC_NA_1
D
<46> := Double command C_DC_NA_1
<47> := Regulating step command C_RC_NA_1
<48> := Set point command, normalized value C_SE_NA_1
<49> := Set point command, scaled value C_SE_NB_1
<50> := Set point command, short floating point value C_SE_NC_1
<51> := Bitstring of 32 bits C_BO_NA_1
Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
System information in monitor direction
4 <70> := End of initialization M_EI_NA_1
File transfer
<120> := File Ready F_FR_NA_1
<121> := Section Ready F_SR_NA_1
<122> := Call directory, select file, call file, call section F_SC_NA_1
<123> := Last section, last segment F_LS_NA_1
<124> := Ack file, ack section F_AF_NA_1
<125> := Segment F_SG_NA_1
<126> := Directory (blank or X, available only in monitor [standard] direction) C_CD_NA_1
ACTIVATION TERMINATION
REQUEST OR REQUESTED
BACKGROUND SCAN
PERIODIC, CYCLIC
FILE TRANSFER
SPONTANEOUS
DEACTIVATION
ACTIVATION
INITIALIZED
20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
<1> M_SP_NA_1 X X X X X
<2> M_SP_TA_1
<3> M_DP_NA_1
<4> M_DP_TA_1
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1
ACTIVATION TERMINATION
REQUEST OR REQUESTED
BACKGROUND SCAN
PERIODIC, CYCLIC
FILE TRANSFER
SPONTANEOUS
DEACTIVATION
ACTIVATION
INITIALIZED
20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
<10> M_ME_TA_1 D
<11> M_ME_NB_1
<12> M_ME_TB_1
<13> M_ME_NC_1 X X X X
<14> M_ME_TC_1
<15> M_IT_NA_1 X X
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 X X X
<31> M_DP_TB_1
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1
<35> M_ME_TE_1
<36> M_ME_TF_1
<37> M_IT_TB_1 X X
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X
<46> C_DC_NA_1
<47> C_RC_NA_1
<48> C_SE_NA_1
<49> C_SE_NB_1
<50> C_SE_NC_1
<51> C_BO_NA_1
<58> C_SC_TA_1 X X X X X
<59> C_DC_TA_1
<60> C_RC_TA_1
ACTIVATION TERMINATION
REQUEST OR REQUESTED
BACKGROUND SCAN
PERIODIC, CYCLIC
FILE TRANSFER
SPONTANEOUS
DEACTIVATION
ACTIVATION
INITIALIZED
20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
D <61>
<62>
C_SE_TA_1
C_SE_TB_1
<63> C_SE_TC_1
<64> C_BO_TA_1
<70> M_EI_NA_1*) X
<100> C_IC_NA_1 X X X X X
<101> C_CI_NA_1 X X X
<102> C_RD_NA_1 X
<103> C_CS_NA_1 X X X
<104> C_TS_NA_1
<105> C_RP_NA_1 X X
<106> C_CD_NA_1
<107> C_TS_TA_1
<110> P_ME_NA_1
<111> P_ME_NB_1
<112> P_ME_NC_1 X X X
<113> P_AC_NA_1
<120> F_FR_NA_1
<121> F_SR_NA_1
<122> F_SC_NA_1
<123> F_LS_NA_1
<124> F_AF_NA_1
<125> F_SG_NA_1
<126> F_DR_TA_1*)
Spontaneous Transmission:
4 Spontaneous transmission
Double transmission of information objects with cause of transmission spontaneous:
The following type identifications may be transmitted in succession caused by a single status change of an information
object. The particular information object addresses for which double transmission is enabled are defined in a project-
specific list.
Single point information: M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, and M_PS_NA_1
Double point information: M_DP_NA_1, M_DP_TA_1, and M_DP_TB_1
Step position information: M_ST_NA_1, M_ST_TA_1, and M_ST_TB_1
Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project)
Measured value, normalized value: M_ME_NA_1, M_ME_TA_1, M_ME_ND_1, and M_ME_TD_1
Measured value, scaled value: M_ME_NB_1, M_ME_TB_1, and M_ME_TE_1
Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1
Station interrogation:
4 Global D
4 Group 1 4 Group 5 4 Group 9 4 Group 13
4 Group 2 4 Group 6 4 Group 10 4 Group 14
4 Group 3 4 Group 7 4 Group 11 4 Group 15
4 Group 4 4 Group 8 4 Group 12 4 Group 16
Clock synchronization:
4 Clock synchronization (optional, see Clause 7.6)
Command transmission:
4 Direct command transmission
Direct setpoint command transmission
4 Select and execute command
Select and execute setpoint command
4 C_SE ACTTERM used
4 No additional definition
4 Short pulse duration (duration determined by a system parameter in the outstation)
4 Long pulse duration (duration determined by a system parameter in the outstation)
4 Persistent output
4 Counter read
4 Counter freeze without reset
APPENDIX E DNP COMMUNICATIONSE.1DEVICE PROFILE DOCUMENT E.1.1 DNP V3.00 DEVICE PROFILE
The following table provides a ‘Device Profile Document’ in the standard format defined in the DNP 3.0 Subset Definitions
Document.
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
Binary Inputs (Object 1)
Binary Input Changes (Object 2)
Binary Outputs (Object 10)
Control Relay Output Block (Object 12)
Binary Counters (Object 20)
E
Frozen Counters (Object 21)
Counter Change Event (Object 22)
Frozen Counter Event (Object 23)
Analog Inputs (Object 30)
Analog Input Changes (Object 32)
Analog Deadbands (Object 34)
Time and Date (Object 50)
File Transfer (Object 70)
Internal Indications (Object 80)
Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted: 292 Transmitted: configurable up to 2048
Received: 292 Received: 2048
Others:
Transmission Delay: No intentional delay
Need Time Interval: Configurable (default = 24 hrs.)
Select/Operate Arm Timeout: 10 s
Binary input change scanning period: 8 times per power system cycle
Analog input change scanning period: 500 ms
Explanation of ‘Sometimes’: Object 12 points are mapped to UR Virtual Inputs. The persistence of Virtual Inputs is
determined by the VIRTUAL INPUT X TYPE settings. Both “Pulse On” and “Latch On” operations perform the same func-
tion in the UR; that is, the appropriate Virtual Input is put into the “On” state. If the Virtual Input is set to “Self-Reset”,
it will reset after one pass of FlexLogic™. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off”
operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate
Virtual Input into the “On” state.
Reports Binary Input Change Events when no Reports time-tagged Binary Input Change Events when no
specific variation requested: specific variation requested:
Never
Never
4 Only time-tagged 4 Binary Input Change With Time
Only non-time-tagged
Binary Input Change With Relative Time
Configurable
Configurable (attach explanation)
The following table identifies the variations, function codes, and qualifiers supported by the G60 in both request messages
and in response messages. For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be
responded with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or
28. For change-event objects, qualifiers 17 or 28 are always responded.
3 Binary Input Change with Relative Time 1 (read) 06 (no range, or all)
07, 08 (limited quantity)
10 0 Binary Output Status (Variation 0 is used to 1 (read) 00, 01(start-stop)
request default variation) 06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
12 1 Control Relay Output Block 3 (select) 00, 01 (start-stop) 129 (response) echo of request
4 (operate) 07, 08 (limited quantity)
5 (direct op) 17, 28 (index)
6 (dir. op, noack)
20 0 Binary Counter 1 (read) 00, 01(start-stop)
(Variation 0 is used to request default 7 (freeze) 06(no range, or all)
variation) 8 (freeze noack) 07, 08(limited quantity)
9 (freeze clear) 17, 28(index)
10 (frz. cl. noack)
22 (assign class)
1 32-Bit Binary Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
7 (freeze) 06 (no range, or all) 17, 28 (index)
8 (freeze noack) 07, 08 (limited quantity) (see Note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
22 (assign class)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default varia-
tions for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5
for details. This optimizes the class 0 poll data size.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3: Cold restarts are implemented the same as warm restarts – the G60 is not restarted, but the DNP process is restarted.
The DNP binary input data points are configured through the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT
LISTS Ö BINARY INPUT / MSP POINTS menu. Refer to the Communications section of Chapter 5 for additional details. When a
freeze function is performed on a binary counter point, the frozen value is available in the corresponding frozen counter
point.
Supported Control Relay Output Block fields: Pulse On, Pulse Off, Latch On, Latch Off, Paired Trip, Paired Close.
E.2.3 COUNTERS
The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21). When a freeze function is per-
formed on a Binary Counter point, the frozen value is available in the corresponding Frozen Counter point.
BINARY COUNTERS
Static (Steady-State) Object Number: 20
Change Event Object Number: 22
Request Function Codes supported: 1 (read), 7 (freeze), 8 (freeze noack), 9 (freeze and clear),
10 (freeze and clear, noack), 22 (assign class)
Static Variation reported when variation 0 requested: 1 (32-Bit Binary Counter with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter Change Event without time)
Change Event Buffer Size: 10
Default Class for all points: 3
FROZEN COUNTERS
Static (Steady-State) Object Number: 21
Change Event Object Number: 23
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter with Flag)
E Change Event Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter Event without time)
Change Event Buffer Size: 10
Default Class for all points: 3
A counter freeze command has no meaning for counters 8 and 9. G60 Digital Counter values are represented as 32-bit
integers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative
counter values.
The DNP analog input data points are configured through the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT
LISTS Ö ANALOG INPUT / MME POINTS menu. Refer to the Communications section of Chapter 5 for additional details.
It is important to note that 16-bit and 32-bit variations of analog inputs are transmitted through DNP as signed numbers.
Even for analog input points that are not valid as negative values, the maximum positive representation is 32767 for 16-bit
values and 2147483647 for 32-bit values. This is a DNP requirement.
The deadbands for all Analog Input points are in the same units as the Analog Input quantity. For example, an Analog Input
quantity measured in volts has a corresponding deadband in units of volts. This is in conformance with DNP Technical Bul-
letin 9809-001: Analog Input Reporting Deadband. Relay settings are available to set default deadband values according to
data type. Deadbands for individual Analog Input Points can be set using DNP Object 34.
--- 3-64 Update Added INITIAL SETUP OF THE ETHERNET SWITCH MODULE section
C-3 C-3 Update Updated PROTECTION AND OTHER LOGICAL NODES section
--- 7-10 Add Added EXTERNAL DEVICE SELF-TEST ERROR MESSAGES section
5-8 5-8 Update Updated PASSWORD SECURITY section (now titled SECURITY)
--- 5-32 Add Added ETHERNET SWITCH sub-section
5-42 5-43 Update Updated USER-PROGRAMMABLE PUSHBUTTONS section
5-60 5-63 Update Updated SIGNAL SOURCES section
F --- 5-66 Add Added BREAKERS section
--- 5-70 Add Added DISCONNECT SWITCHES section
5-87 5-98 Update Updated FLEXLOGIC OPERANDS table
B-8 B-8 Update Update MODBUS MEMORY MAP section for revision 5.5x
--- C-2 Add Added GGIO4: GENERIC ANALOG MEASURED VALUES section
C-7 C-7 Update Updated CONFIGURABLE GOOSE section
3-20 3-20 Update Updated CPU MODULE COMMUNICATIONS WIRING diagram to 842765A2
5-139 5-139 Update Updated NEGATIVE-SEQUENCE OVERVOLTAGE SCHEME LOGIC diagram to 827839A3
3-30 3-30 Update Updated TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, 3-TERMINAL APPLICATION
drawing to 831022A3
In the event of a failure covered by warranty, GE Multilin will undertake to repair or replace the relay
providing the warrantor determined that it is defective and it is returned with all transportation
charges prepaid to an authorized service centre or the factory. Repairs or replacement under war-
ranty will be made without charge.
Warranty shall not apply to any relay which has been subject to misuse, negligence, accident,
incorrect installation or use not in accordance with instructions nor any unit that has been altered
outside a GE Multilin authorized factory outlet.
GE Multilin is not liable for special, indirect or consequential damages or for loss of profit or for
F
expenses sustained as a result of a relay malfunction, incorrect application or adjustment.
For complete text of Warranty (including limitations and disclaimers), refer to GE Multilin Standard
Conditions of Sale.
INDEX