Title Page

g
GE Multilin

G60 Generator Protection System


UR Series Instruction Manual
G60 revision: 5.9x

Manual P/N: 1601-0110-W1 (GEK-113381)


Copyright © 2011 GE Multilin

830715A2.CDR

E83849
T
GIS ERE
RE

GE Multilin ISO9001:2000
LISTED EM I
G

215 Anderson Avenue, Markham, Ontario


IND.CONT. EQ. U LT I L
Canada L6E 1B3 52TL
GE Multilin's Quality Management
Tel: (905) 294-6222 Fax: (905) 201-2098 System is registered to
ISO9001:2000
Internet: http://www.GEmultilin.com QMI # 005094
UL # A3775

*1601-0110-W1*
Addendum

g
GE Multilin

ADDENDUM
This addendum contains information that relates to the G60 Generator Protection System, version 5.9x. This addendum
lists a number of information items that appear in the instruction manual GEK-113381 (revision W1) but are not included
in the current G60 operations.
The following functions and items are not yet available with the current version of the G60 relay:
• Signal sources SRC 5 and SRC 6.
Version 4.0x and higher releases of the G60 relay includes new hardware (CPU and CT/VT modules).
• The new CPU modules are specified with the following order codes: 9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S.
• The new CT/VT modules are specified with the following order codes: 8F, 8G, 8H, 8J 8L, 8M, 8N, 8R.
The following table maps the relationship between the old CPU and CT/VT modules to the newer versions:

MODULE OLD NEW DESCRIPTION


CPU 9A 9E RS485 and RS485 (Modbus RTU, DNP)
9C 9G RS485 and 10Base-F (Ethernet, Modbus TCP/IP, DNP)
9D 9H RS485 and redundant 10Base-F (Ethernet, Modbus TCP/IP, DNP)
--- 9J RS485 and multi-mode ST 100Base-FX
--- 9K RS485 and multi-mode ST redundant 100Base-FX
--- 9L RS485 and single mode SC 100Base-FX
--- 9M RS485 and single mode SC redundant 100Base-FX
--- 9N RS485 and 10/100Base-T
--- 9P RS485 and single mode ST 100Base-FX
--- 9R RS485 and single mode ST redundant 100Base-FX
--- 9S RS485 and six-port managed Ethernet switch
CT/VT 8A 8F Standard 4CT/4VT
8B 8G Sensitive ground 4CT/4VT
8C 8H Standard 8CT
8D 8J Sensitive ground 8CT
-- 8L Standard 4CT/4VT with enhanced diagnostics
-- 8M Sensitive ground 4CT/4VT with enhanced diagnostics
-- 8N Standard 8CT with enhanced diagnostics
-- 8R Sensitive ground 8CT with enhanced diagnostics

The new CT/VT modules can only be used with the new CPUs (9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, and 9S), and
the old CT/VT modules can only be used with the old CPU modules (9A, 9C, 9D). To prevent any hardware mis-
matches, the new CPU and CT/VT modules have blue labels and a warning sticker stating “Attn.: Ensure CPU and
DSP module label colors are the same!”. In the event that there is a mismatch between the CPU and CT/VT module,
the relay will not function and a DSP ERROR or HARDWARE MISMATCH error will be displayed.
All other input/output modules are compatible with the new hardware.
With respect to the firmware, firmware versions 4.0x and higher are only compatible with the new CPU and CT/VT mod-
ules. Previous versions of the firmware (3.4x and earlier) are only compatible with the older CPU and CT/VT modules.
Table of Contents

TABLE OF CONTENTS

1. GETTING STARTED 1.1 IMPORTANT PROCEDURES


1.1.1 CAUTIONS AND WARNINGS ........................................................................... 1-1
1.1.2 INSPECTION CHECKLIST ................................................................................ 1-1
1.2 UR OVERVIEW
1.2.1 INTRODUCTION TO THE UR ........................................................................... 1-2
1.2.2 HARDWARE ARCHITECTURE ......................................................................... 1-3
1.2.3 SOFTWARE ARCHITECTURE.......................................................................... 1-4
1.2.4 IMPORTANT CONCEPTS ................................................................................. 1-4
1.3 ENERVISTA UR SETUP SOFTWARE
1.3.1 PC REQUIREMENTS ........................................................................................ 1-5
1.3.2 INSTALLATION.................................................................................................. 1-5
1.3.3 CONFIGURING THE G60 FOR SOFTWARE ACCESS .................................... 1-7
1.3.4 USING THE QUICK CONNECT FEATURE....................................................... 1-9
1.3.5 CONNECTING TO THE G60 RELAY .............................................................. 1-15
1.4 UR HARDWARE
1.4.1 MOUNTING AND WIRING............................................................................... 1-16
1.4.2 COMMUNICATIONS........................................................................................ 1-16
1.4.3 FACEPLATE DISPLAY .................................................................................... 1-16
1.5 USING THE RELAY
1.5.1 FACEPLATE KEYPAD..................................................................................... 1-17
1.5.2 MENU NAVIGATION ....................................................................................... 1-17
1.5.3 MENU HIERARCHY ........................................................................................ 1-17
1.5.4 RELAY ACTIVATION....................................................................................... 1-17
1.5.5 RELAY PASSWORDS ..................................................................................... 1-18
1.5.6 FLEXLOGIC™ CUSTOMIZATION................................................................... 1-18
1.5.7 COMMISSIONING ........................................................................................... 1-19

2. PRODUCT DESCRIPTION 2.1 INTRODUCTION


2.1.1 OVERVIEW........................................................................................................ 2-1
2.1.2 ORDERING........................................................................................................ 2-3
2.1.3 REPLACEMENT MODULES ............................................................................. 2-7
2.2 SPECIFICATIONS
2.2.1 PROTECTION ELEMENTS ............................................................................. 2-10
2.2.2 USER-PROGRAMMABLE ELEMENTS ........................................................... 2-14
2.2.3 MONITORING .................................................................................................. 2-15
2.2.4 METERING ...................................................................................................... 2-16
2.2.5 INPUTS ............................................................................................................ 2-17
2.2.6 POWER SUPPLY ............................................................................................ 2-18
2.2.7 OUTPUTS ........................................................................................................ 2-19
2.2.8 FIELD AND STATOR GROUND MODULES ................................................... 2-20
2.2.9 COMMUNICATIONS........................................................................................ 2-22
2.2.10 INTER-RELAY COMMUNICATIONS ............................................................... 2-23
2.2.11 ENVIRONMENTAL .......................................................................................... 2-23
2.2.12 TYPE TESTS ................................................................................................... 2-24
2.2.13 PRODUCTION TESTS .................................................................................... 2-24
2.2.14 APPROVALS ................................................................................................... 2-25
2.2.15 MAINTENANCE ............................................................................................... 2-25

3. HARDWARE 3.1 DESCRIPTION


3.1.1 PANEL CUTOUT ............................................................................................... 3-1
3.1.2 MODULE WITHDRAWAL AND INSERTION ..................................................... 3-6
3.1.3 REAR TERMINAL LAYOUT............................................................................... 3-8
3.2 WIRING
3.2.1 TYPICAL WIRING............................................................................................ 3-10
3.2.2 DIELECTRIC STRENGTH ............................................................................... 3-12
3.2.3 CONTROL POWER ......................................................................................... 3-12
3.2.4 CT/VT MODULES ............................................................................................ 3-13
3.2.5 PROCESS BUS MODULES ............................................................................ 3-15

GE Multilin G60 Generator Protection System v


TABLE OF CONTENTS

3.2.6 CONTACT INPUTS AND OUTPUTS................................................................3-15


3.2.7 TRANSDUCER INPUTS/OUTPUTS.................................................................3-23
3.2.8 RS232 FACEPLATE PORT ..............................................................................3-24
3.2.9 CPU COMMUNICATION PORTS.....................................................................3-24
3.2.10 IRIG-B ...............................................................................................................3-28
3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES
3.3.1 DESCRIPTION .................................................................................................3-29
3.3.2 FIBER: LED AND ELED TRANSMITTERS ......................................................3-31
3.3.3 FIBER-LASER TRANSMITTERS .....................................................................3-31
3.3.4 G.703 INTERFACE...........................................................................................3-32
3.3.5 RS422 INTERFACE .........................................................................................3-35
3.3.6 RS422 AND FIBER INTERFACE .....................................................................3-37
3.3.7 G.703 AND FIBER INTERFACE ......................................................................3-37
3.3.8 IEEE C37.94 INTERFACE................................................................................3-38
3.3.9 C37.94SM INTERFACE ...................................................................................3-40
3.4 FIELD AND STATOR GROUND MODULES
3.4.1 OVERVIEW ......................................................................................................3-42
3.4.2 FIELD GROUND LOW-VOLTAGE PROTECTION SYSTEM ...........................3-43
3.4.3 FIELD GROUND HIGH-VOLTAGE PROTECTION SYSTEM ..........................3-46
3.4.4 STATOR GROUND PROTECTION SYSTEM ..................................................3-53
3.4.5 UPGRADING FIRMWARE ...............................................................................3-60
3.5 MANAGED ETHERNET SWITCH MODULES
3.5.1 OVERVIEW ......................................................................................................3-63
3.5.2 MANAGED ETHERNET SWITCH MODULE HARDWARE..............................3-63
3.5.3 MANAGED SWITCH LED INDICATORS .........................................................3-64
3.5.4 INITIAL SETUP OF THE ETHERNET SWITCH MODULE...............................3-64
3.5.5 CONFIGURING THE MANAGED ETHERNET SWITCH MODULE .................3-68
3.5.6 UPLOADING G60 SWITCH MODULE FIRMWARE.........................................3-71
3.5.7 ETHERNET SWITCH SELF-TEST ERRORS...................................................3-73

4. HUMAN INTERFACES 4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE


4.1.1 INTRODUCTION ................................................................................................4-1
4.1.2 CREATING A SITE LIST ....................................................................................4-1
4.1.3 ENERVISTA UR SETUP OVERVIEW ................................................................4-1
4.1.4 ENERVISTA UR SETUP MAIN WINDOW..........................................................4-3
4.2 EXTENDED ENERVISTA UR SETUP FEATURES
4.2.1 SETTINGS TEMPLATES ...................................................................................4-4
4.2.2 SECURING AND LOCKING FLEXLOGIC™ EQUATIONS ................................4-8
4.2.3 SETTINGS FILE TRACEABILITY.....................................................................4-10
4.3 FACEPLATE INTERFACE
4.3.1 FACEPLATE .....................................................................................................4-13
4.3.2 LED INDICATORS............................................................................................4-14
4.3.3 CUSTOM LABELING OF LEDS .......................................................................4-17
4.3.4 DISPLAY...........................................................................................................4-23
4.3.5 KEYPAD ...........................................................................................................4-23
4.3.6 BREAKER CONTROL ......................................................................................4-23
4.3.7 MENUS .............................................................................................................4-24
4.3.8 CHANGING SETTINGS ...................................................................................4-26

5. SETTINGS 5.1 OVERVIEW


5.1.1 SETTINGS MAIN MENU ....................................................................................5-1
5.1.2 INTRODUCTION TO ELEMENTS ......................................................................5-4
5.1.3 INTRODUCTION TO AC SOURCES..................................................................5-5
5.2 PRODUCT SETUP
5.2.1 SECURITY..........................................................................................................5-8
5.2.2 DISPLAY PROPERTIES ..................................................................................5-12
5.2.3 CLEAR RELAY RECORDS ..............................................................................5-14
5.2.4 COMMUNICATIONS ........................................................................................5-15
5.2.5 MODBUS USER MAP ......................................................................................5-39

vi G60 Generator Protection System GE Multilin


TABLE OF CONTENTS

5.2.6 REAL TIME CLOCK......................................................................................... 5-40


5.2.7 USER-PROGRAMMABLE FAULT REPORT ................................................... 5-41
5.2.8 OSCILLOGRAPHY .......................................................................................... 5-42
5.2.9 DATA LOGGER ............................................................................................... 5-44
5.2.10 USER-PROGRAMMABLE LEDS..................................................................... 5-46
5.2.11 USER-PROGRAMMABLE SELF TESTS......................................................... 5-49
5.2.12 CONTROL PUSHBUTTONS ........................................................................... 5-49
5.2.13 USER-PROGRAMMABLE PUSHBUTTONS ................................................... 5-51
5.2.14 FLEX STATE PARAMETERS .......................................................................... 5-56
5.2.15 USER-DEFINABLE DISPLAYS ....................................................................... 5-57
5.2.16 DIRECT INPUTS/OUTPUTS ........................................................................... 5-59
5.2.17 TELEPROTECTION......................................................................................... 5-67
5.2.18 INSTALLATION................................................................................................ 5-67
5.3 REMOTE RESOURCES
5.3.1 REMOTE RESOURCES CONFIGURATION ................................................... 5-69
5.4 SYSTEM SETUP
5.4.1 AC INPUTS ...................................................................................................... 5-70
5.4.2 POWER SYSTEM............................................................................................ 5-71
5.4.3 SIGNAL SOURCES ......................................................................................... 5-72
5.4.4 BREAKERS...................................................................................................... 5-75
5.4.5 DISCONNECT SWITCHES ............................................................................. 5-79
5.4.6 FLEXCURVES ................................................................................................. 5-82
5.4.7 PHASOR MEASUREMENT UNIT.................................................................... 5-89
5.5 FLEXLOGIC™
5.5.1 INTRODUCTION TO FLEXLOGIC™ ............................................................. 5-105
5.5.2 FLEXLOGIC™ RULES .................................................................................. 5-116
5.5.3 FLEXLOGIC™ EVALUATION........................................................................ 5-117
5.5.4 FLEXLOGIC™ EXAMPLE ............................................................................. 5-117
5.5.5 FLEXLOGIC™ EQUATION EDITOR ............................................................. 5-122
5.5.6 FLEXLOGIC™ TIMERS................................................................................. 5-122
5.5.7 FLEXELEMENTS™ ....................................................................................... 5-123
5.5.8 NON-VOLATILE LATCHES ........................................................................... 5-127
5.6 GROUPED ELEMENTS
5.6.1 OVERVIEW.................................................................................................... 5-128
5.6.2 SETTING GROUP ......................................................................................... 5-128
5.6.3 DISTANCE ..................................................................................................... 5-129
5.6.4 POWER SWING DETECT ............................................................................. 5-137
5.6.5 STATOR DIFFERENTIAL .............................................................................. 5-145
5.6.6 PHASE CURRENT ........................................................................................ 5-148
5.6.7 NEUTRAL CURRENT.................................................................................... 5-159
5.6.8 GROUND CURRENT..................................................................................... 5-166
5.6.9 NEGATIVE SEQUENCE CURRENT ............................................................. 5-173
5.6.10 GENERATOR UNBALANCE ......................................................................... 5-177
5.6.11 SPLIT PHASE PROTECTION ....................................................................... 5-179
5.6.12 VOLTAGE ELEMENTS .................................................................................. 5-183
5.6.13 LOSS OF EXCITATION ................................................................................. 5-194
5.6.14 ACCIDENTAL ENERGIZATION .................................................................... 5-196
5.6.15 SENSITIVE DIRECTIONAL POWER............................................................. 5-198
5.6.16 STATOR GROUND........................................................................................ 5-201
5.6.17 FIELD GROUND FAULT PROTECTION ....................................................... 5-210
5.7 CONTROL ELEMENTS
5.7.1 OVERVIEW.................................................................................................... 5-216
5.7.2 TRIP BUS....................................................................................................... 5-216
5.7.3 SETTING GROUPS ....................................................................................... 5-218
5.7.4 SELECTOR SWITCH..................................................................................... 5-219
5.7.5 UNDERFREQUENCY.................................................................................... 5-225
5.7.6 OVERFREQUENCY ...................................................................................... 5-226
5.7.7 FREQUENCY RATE OF CHANGE................................................................ 5-227
5.7.8 FREQUENCY OUT-OF-BAND ACCUMULATION ......................................... 5-229
5.7.9 SYNCHROCHECK......................................................................................... 5-231
5.7.10 DIGITAL ELEMENTS..................................................................................... 5-236
5.7.11 DIGITAL COUNTERS .................................................................................... 5-239
5.7.12 MONITORING ELEMENTS ........................................................................... 5-241

GE Multilin G60 Generator Protection System vii


TABLE OF CONTENTS

5.8 INPUTS/OUTPUTS
5.8.1 CONTACT INPUTS ........................................................................................5-246
5.8.2 VIRTUAL INPUTS ..........................................................................................5-248
5.8.3 CONTACT OUTPUTS ....................................................................................5-249
5.8.4 VIRTUAL OUTPUTS ......................................................................................5-251
5.8.5 REMOTE DEVICES........................................................................................5-252
5.8.6 REMOTE INPUTS ..........................................................................................5-253
5.8.7 REMOTE DOUBLE-POINT STATUS INPUTS ...............................................5-254
5.8.8 REMOTE OUTPUTS ......................................................................................5-254
5.8.9 RESETTING ...................................................................................................5-255
5.8.10 DIRECT INPUTS AND OUTPUTS..................................................................5-256
5.8.11 TELEPROTECTION INPUTS AND OUTPUTS ..............................................5-259
5.8.12 IEC 61850 GOOSE ANALOGS ......................................................................5-261
5.8.13 IEC 61850 GOOSE INTEGERS .....................................................................5-262
5.9 TRANSDUCER INPUTS AND OUTPUTS
5.9.1 DCMA INPUTS ...............................................................................................5-263
5.9.2 RTD INPUTS ..................................................................................................5-264
5.9.3 RRTD INPUTS................................................................................................5-266
5.9.4 DCMA OUTPUTS ...........................................................................................5-270
5.10 TESTING
5.10.1 TEST MODE ...................................................................................................5-274
5.10.2 FORCE CONTACT INPUTS...........................................................................5-275
5.10.3 FORCE CONTACT OUTPUTS.......................................................................5-276
5.10.4 PHASOR MEASUREMENT UNIT TEST VALUES .........................................5-277

6. ACTUAL VALUES 6.1 OVERVIEW


6.1.1 ACTUAL VALUES MAIN MENU .........................................................................6-1
6.2 STATUS
6.2.1 CONTACT INPUTS ............................................................................................6-4
6.2.2 VIRTUAL INPUTS ..............................................................................................6-4
6.2.3 REMOTE INPUTS ..............................................................................................6-4
6.2.4 REMOTE DOUBLE-POINT STATUS INPUTS ...................................................6-5
6.2.5 TELEPROTECTION INPUTS .............................................................................6-5
6.2.6 CONTACT OUTPUTS ........................................................................................6-5
6.2.7 VIRTUAL OUTPUTS ..........................................................................................6-6
6.2.8 REMOTE DEVICES............................................................................................6-6
6.2.9 DIGITAL COUNTERS.........................................................................................6-7
6.2.10 SELECTOR SWITCHES ....................................................................................6-7
6.2.11 FLEX STATES ....................................................................................................6-7
6.2.12 ETHERNET ........................................................................................................6-7
6.2.13 DIRECT INPUTS ................................................................................................6-8
6.2.14 DIRECT DEVICES STATUS ..............................................................................6-8
6.2.15 IEC 61850 GOOSE INTEGERS .........................................................................6-9
6.2.16 EGD PROTOCOL STATUS................................................................................6-9
6.2.17 TELEPROTECTION CHANNEL TESTS...........................................................6-10
6.2.18 ETHERNET SWITCH .......................................................................................6-10
6.3 METERING
6.3.1 METERING CONVENTIONS ...........................................................................6-11
6.3.2 STATOR DIFFERENTIAL.................................................................................6-14
6.3.3 SOURCES ........................................................................................................6-14
6.3.4 SYNCHROCHECK ...........................................................................................6-19
6.3.5 TRACKING FREQUENCY................................................................................6-20
6.3.6 FREQUENCY RATE OF CHANGE ..................................................................6-20
6.3.7 FREQUENCY OUT-OF-BAND ACCUMULATION............................................6-20
6.3.8 FLEXELEMENTS™ ..........................................................................................6-21
6.3.9 IEC 61580 GOOSE ANALOG VALUES ...........................................................6-22
6.3.10 SENSITIVE DIRECTIONAL POWER ...............................................................6-22
6.3.11 STATOR GROUND ..........................................................................................6-22
6.3.12 SUB-HARMONIC STATOR GROUND .............................................................6-23
6.3.13 FIELD GROUND...............................................................................................6-23
6.3.14 VOLTS PER HERTZ.........................................................................................6-23
6.3.15 RESTRICTED GROUND FAULT......................................................................6-23
6.3.16 PHASOR MEASUREMENT UNIT ....................................................................6-24

viii G60 Generator Protection System GE Multilin


TABLE OF CONTENTS

6.3.17 TRANSDUCER INPUTS AND OUTPUTS ....................................................... 6-25


6.4 RECORDS
6.4.1 USER-PROGRAMMABLE FAULT REPORTS ................................................ 6-26
6.4.2 EVENT RECORDS .......................................................................................... 6-26
6.4.3 OSCILLOGRAPHY .......................................................................................... 6-26
6.4.4 DATA LOGGER ............................................................................................... 6-27
6.4.5 PHASOR MEASUREMENT UNIT RECORDS................................................. 6-27
6.5 PRODUCT INFORMATION
6.5.1 MODEL INFORMATION .................................................................................. 6-28
6.5.2 FIRMWARE REVISIONS ................................................................................. 6-28

7. COMMANDS AND 7.1 COMMANDS


TARGETS 7.1.1 COMMANDS MENU .......................................................................................... 7-1
7.1.2 VIRTUAL INPUTS.............................................................................................. 7-1
7.1.3 CLEAR RECORDS ............................................................................................ 7-2
7.1.4 SET DATE AND TIME ....................................................................................... 7-2
7.1.5 RELAY MAINTENANCE .................................................................................... 7-3
7.1.6 PHASOR MEASUREMENT UNIT ONE-SHOT.................................................. 7-4
7.2 TARGETS
7.2.1 TARGETS MENU............................................................................................... 7-6
7.2.2 TARGET MESSAGES ....................................................................................... 7-6
7.2.3 RELAY SELF-TESTS......................................................................................... 7-6

8. SECURITY 8.1 PASSWORD SECURITY


8.1.1 OVERVIEW........................................................................................................ 8-1
8.1.2 PASSWORD SECURITY MENU ....................................................................... 8-2
8.1.3 LOCAL PASSWORDS ....................................................................................... 8-2
8.1.4 REMOTE PASSWORDS ................................................................................... 8-3
8.1.5 ACCESS SUPERVISION ................................................................................... 8-3
8.1.6 DUAL PERMISSION SECURITY ACCESS ....................................................... 8-4
8.2 SETTINGS SECURITY
8.2.1 SETTINGS TEMPLATES ................................................................................... 8-6
8.2.2 SECURING AND LOCKING FLEXLOGIC™ EQUATIONS ............................. 8-10
8.2.3 SETTINGS FILE TRACEABILITY .................................................................... 8-12
8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM
8.3.1 OVERVIEW...................................................................................................... 8-15
8.3.2 ENABLING THE SECURITY MANAGEMENT SYSTEM ................................. 8-15
8.3.3 ADDING A NEW USER ................................................................................... 8-15
8.3.4 MODIFYING USER PRIVILEGES ................................................................... 8-16

9. THEORY OF OPERATION 9.1 PHASE DISTANCE THROUGH POWER TRANSFORMERS


9.1.1 DESCRIPTION................................................................................................... 9-1
9.1.2 EXAMPLE .......................................................................................................... 9-4

10. APPLICATION OF 10.1 SETTING EXAMPLE


SETTINGS 10.1.1 DESCRIPTION................................................................................................. 10-1
10.1.2 SYSTEM SETUP ............................................................................................. 10-1
10.1.3 POWER SYSTEM............................................................................................ 10-2
10.1.4 SIGNAL SOURCES ......................................................................................... 10-2
10.1.5 STATOR DIFFERENTIAL ................................................................................ 10-3
10.1.6 GENERATOR UNBALANCE ........................................................................... 10-3
10.1.7 LOSS OF EXCITATION ................................................................................... 10-4
10.1.8 REVERSE POWER ......................................................................................... 10-4
10.1.9 SYSTEM BACKUP OVERCURRENT .............................................................. 10-5

GE Multilin G60 Generator Protection System ix


TABLE OF CONTENTS

10.1.10 BACKUP DISTANCE ........................................................................................10-6


10.1.11 STATOR GROUND FAULT ..............................................................................10-7
10.1.12 OVEREXCITATION ........................................................................................10-10
10.1.13 INPUTS/OUTPUTS ........................................................................................10-11
10.1.14 FREQUENCY .................................................................................................10-12
10.1.15 ACCIDENTAL ENERGIZATION .....................................................................10-12
10.1.16 FLEXLOGIC™ ................................................................................................10-13
10.2 PHASE DISTANCE THROUGH POWER TRANSFORMERS
10.2.1 OVERVIEW ....................................................................................................10-14
10.2.2 EXAMPLE .......................................................................................................10-15

11. COMMISSIONING 11.1 TESTING


11.1.1 TESTING UNDERFREQUENCY AND OVERFREQUENCY ELEMENTS .......11-1

A. FLEXANALOG AND A.1 PARAMETER LISTS


FLEXINTEGER A.1.1 FLEXANALOG ITEMS ....................................................................................... A-1
A.1.2 FLEXINTEGER ITEMS .................................................................................... A-24
PARAMETERS

B. MODBUS B.1 MODBUS RTU PROTOCOL


COMMUNICATIONS B.1.1 INTRODUCTION ............................................................................................... B-1
B.1.2 PHYSICAL LAYER ............................................................................................ B-1
B.1.3 DATA LINK LAYER ........................................................................................... B-1
B.1.4 CRC-16 ALGORITHM ....................................................................................... B-2
B.2 MODBUS FUNCTION CODES
B.2.1 SUPPORTED FUNCTION CODES ................................................................... B-3
B.2.2 READ ACTUAL VALUES OR SETTINGS (FUNCTION CODE 03/04H) ........... B-3
B.2.3 EXECUTE OPERATION (FUNCTION CODE 05H)........................................... B-4
B.2.4 STORE SINGLE SETTING (FUNCTION CODE 06H)....................................... B-4
B.2.5 STORE MULTIPLE SETTINGS (FUNCTION CODE 10H) ................................ B-5
B.2.6 EXCEPTION RESPONSES............................................................................... B-5
B.3 FILE TRANSFERS
B.3.1 OBTAINING RELAY FILES VIA MODBUS........................................................ B-6
B.3.2 MODBUS PASSWORD OPERATION ............................................................... B-7
B.4 MEMORY MAPPING
B.4.1 MODBUS MEMORY MAP ................................................................................. B-8
B.4.2 DATA FORMATS............................................................................................. B-66

C. IEC 61850 C.1 OVERVIEW


COMMUNICATIONS C.1.1 INTRODUCTION ............................................................................................... C-1
C.1.2 COMMUNICATION PROFILES ......................................................................... C-1
C.2 SERVER DATA ORGANIZATION
C.2.1 OVERVIEW ....................................................................................................... C-2
C.2.2 GGIO1: DIGITAL STATUS VALUES ................................................................. C-2
C.2.3 GGIO2: DIGITAL CONTROL VALUES.............................................................. C-2
C.2.4 GGIO3: DIGITAL STATUS AND ANALOG VALUES FROM RECEIVED GOOSE
DATAC-2
C.2.5 GGIO4: GENERIC ANALOG MEASURED VALUES......................................... C-2
C.2.6 MMXU: ANALOG MEASURED VALUES .......................................................... C-3
C.2.7 PROTECTION AND OTHER LOGICAL NODES............................................... C-3
C.3 SERVER FEATURES AND CONFIGURATION
C.3.1 BUFFERED/UNBUFFERED REPORTING........................................................ C-5
C.3.2 FILE TRANSFER ............................................................................................... C-5
C.3.3 TIMESTAMPS AND SCANNING ....................................................................... C-5

x G60 Generator Protection System GE Multilin


TABLE OF CONTENTS

C.3.4 LOGICAL DEVICE NAME..................................................................................C-5


C.3.5 LOCATION.........................................................................................................C-5
C.3.6 LOGICAL NODE NAME PREFIXES ..................................................................C-6
C.3.7 CONNECTION TIMING .....................................................................................C-6
C.3.8 NON-IEC 61850 DATA ......................................................................................C-6
C.3.9 COMMUNICATION SOFTWARE UTILITIES .....................................................C-6
C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE
C.4.1 OVERVIEW........................................................................................................C-7
C.4.2 GSSE CONFIGURATION ..................................................................................C-7
C.4.3 FIXED GOOSE ..................................................................................................C-7
C.4.4 CONFIGURABLE GOOSE.................................................................................C-7
C.4.5 ETHERNET MAC ADDRESS FOR GSSE/GOOSE...........................................C-9
C.4.6 GSSE ID AND GOOSE ID SETTINGS ............................................................C-10
C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
C.5.1 OVERVIEW......................................................................................................C-11
C.5.2 CONFIGURING IEC 61850 SETTINGS...........................................................C-12
C.5.3 ABOUT ICD FILES...........................................................................................C-13
C.5.4 CREATING AN ICD FILE WITH ENERVISTA UR SETUP ..............................C-17
C.5.5 ABOUT SCD FILES .........................................................................................C-17
C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP ...........................C-20
C.6 ACSI CONFORMANCE
C.6.1 ACSI BASIC CONFORMANCE STATEMENT.................................................C-22
C.6.2 ACSI MODELS CONFORMANCE STATEMENT ............................................C-22
C.6.3 ACSI SERVICES CONFORMANCE STATEMENT .........................................C-23
C.7 LOGICAL NODES
C.7.1 LOGICAL NODES TABLE ...............................................................................C-26

D. IEC 60870-5-104 D.1 IEC 60870-5-104


COMMUNICATIONS D.1.1 INTEROPERABILITY DOCUMENT ...................................................................D-1
D.1.2 IEC 60870-5-104 POINT LIST ...........................................................................D-9

E. DNP COMMUNICATIONS E.1 DEVICE PROFILE DOCUMENT


E.1.1 DNP V3.00 DEVICE PROFILE ..........................................................................E-1
E.1.2 IMPLEMENTATION TABLE ...............................................................................E-4
E.2 DNP POINT LISTS
E.2.1 BINARY INPUT POINTS....................................................................................E-8
E.2.2 BINARY AND CONTROL RELAY OUTPUT ......................................................E-9
E.2.3 COUNTERS .....................................................................................................E-10
E.2.4 ANALOG INPUTS ............................................................................................E-11

F. MISCELLANEOUS F.1 CHANGE NOTES


F.1.1 REVISION HISTORY ......................................................................................... F-1
F.1.2 CHANGES TO THE G60 MANUAL ................................................................... F-2
F.2 ABBREVIATIONS
F.2.1 STANDARD ABBREVIATIONS ......................................................................... F-9
F.3 WARRANTY
F.3.1 GE MULTILIN WARRANTY ............................................................................. F-11

INDEX

GE Multilin G60 Generator Protection System xi


TABLE OF CONTENTS

xii G60 Generator Protection System GE Multilin


1 GETTING STARTED 1.1 IMPORTANT PROCEDURES

1 GETTING STARTED 1.1IMPORTANT PROCEDURES


Please read this chapter to help guide you through the initial setup of your new GE Mutilin structured template. 1
1.1.1 CAUTIONS AND WARNINGS

Before attempting to install or use the relay, it is imperative that all NOTE, CAUTION and WARNING icons in this document
are reviewed to help prevent personal injury, equipment damage, or downtime.

WARNING CAUTION
1.1.2 INSPECTION CHECKLIST

1. Open the relay packaging and inspect the unit for physical damage.
2. View the rear nameplate and verify that the correct model has been ordered.

Model: G60D00HCHF8AH6AM6BP8BX7A

G60 Generator Management Relay RATINGS:


Control Power: 88-300V DC @ 35W / 77-265V AC @ 35VA
Contact Inputs: 300V DC Max 10mA
Contact Outputs: Standard Pilot Duty / 250V AC 7.5A
Mods:
Wiring Diagram:
Inst. Manual:
Serial Number:
000
830721A3
GEK-113274
MAZB98000029
360V A Resistive / 125V DC Break Firmware: D
GE Multilin 4A @ L/R = 40mS / 300W Mfg. Date: 2005/01/05

Technical Support:
Made in
Tel: (905) 294-6222 http://www.GEmultilin.com ®
®
Canada
Fax: (905) 201-2098 - M A A B 9 7 0 0 0 0 9 9 -

830742A1.CDR

Figure 1–1: REAR NAMEPLATE (EXAMPLE)


3. Ensure that the following items are included:
• Instruction manual.
• GE EnerVista CD (includes the EnerVista UR Setup software and manuals in PDF format).
• Mounting screws.
For product information, instruction manual updates, and the latest software updates, please visit the GE Multilin website at
http://www.GEmultilin.com.
If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE
Multilin immediately.
NOTE

GE MULTILIN CONTACT INFORMATION AND CALL CENTER FOR PRODUCT SUPPORT:


GE Multilin
215 Anderson Avenue
Markham, Ontario
Canada L6E 1B3
TELEPHONE: (905) 294-6222, 1-800-547-8629 (North America only)
FAX: (905) 201-2098
E-MAIL: [email protected]
HOME PAGE: http://www.GEmultilin.com

GE Multilin G60 Generator Protection System 1-1


1.2 UR OVERVIEW 1 GETTING STARTED

1.2UR OVERVIEW 1.2.1 INTRODUCTION TO THE UR

1 Historically, substation protection, control, and metering functions were performed with electromechanical equipment. This
first generation of equipment was gradually replaced by analog electronic equipment, most of which emulated the single-
function approach of their electromechanical precursors. Both of these technologies required expensive cabling and auxil-
iary equipment to produce functioning systems.
Recently, digital electronic equipment has begun to provide protection, control, and metering functions. Initially, this equip-
ment was either single function or had very limited multi-function capability, and did not significantly reduce the cabling and
auxiliary equipment required. However, recent digital relays have become quite multi-functional, reducing cabling and aux-
iliaries significantly. These devices also transfer data to central control facilities and Human Machine Interfaces using elec-
tronic communications. The functions performed by these products have become so broad that many users now prefer the
term IED (Intelligent Electronic Device).
It is obvious to station designers that the amount of cabling and auxiliary equipment installed in stations can be even further
reduced, to 20% to 70% of the levels common in 1990, to achieve large cost reductions. This requires placing even more
functions within the IEDs.
Users of power equipment are also interested in reducing cost by improving power quality and personnel productivity, and
as always, in increasing system reliability and efficiency. These objectives are realized through software which is used to
perform functions at both the station and supervisory levels. The use of these systems is growing rapidly.
High speed communications are required to meet the data transfer rates required by modern automatic control and moni-
toring systems. In the near future, very high speed communications will be required to perform protection signaling with a
performance target response time for a command signal between two IEDs, from transmission to reception, of less than 3
milliseconds. This has been established by the IEC 61850 standard.
IEDs with the capabilities outlined above will also provide significantly more power system data than is presently available,
enhance operations and maintenance, and permit the use of adaptive system configuration for protection and control sys-
tems. This new generation of equipment must also be easily incorporated into automation systems, at both the station and
enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals.

1-2 G60 Generator Protection System GE Multilin


1 GETTING STARTED 1.2 UR OVERVIEW

1.2.2 HARDWARE ARCHITECTURE

a) UR BASIC DESIGN 1
The UR is a digital-based device containing a central processing unit (CPU) that handles multiple types of input and output
signals. The UR can communicate over a local area network (LAN) with an operator interface, a programming device, or
another UR device.

Input Elements CPU Module Output Elements


Contact Inputs Protective Elements Contact Outputs
Virtual Inputs Pickup Virtual Outputs
Dropout
Input Output
Analog Inputs Operate Analog Outputs
CT Inputs Status Status Remote Outputs
VT Inputs Table Logic Gates Table -DNA
-USER
Remote Inputs
Direct Inputs Direct Outputs

LAN

Programming Operator
Device Interface
827822A2.CDR

Figure 1–2: UR CONCEPT BLOCK DIAGRAM


The CPU module contains firmware that provides protection elements in the form of logic algorithms, as well as program-
mable logic gates, timers, and latches for control features.
Input elements accept a variety of analog or digital signals from the field. The UR isolates and converts these signals into
logic signals used by the relay.
Output elements convert and isolate the logic signals generated by the relay into digital or analog signals that can be used
to control field devices.

b) UR SIGNAL TYPES
The contact inputs and outputs are digital signals associated with connections to hard-wired contacts. Both ‘wet’ and ‘dry’
contacts are supported.
The virtual inputs and outputs are digital signals associated with UR-series internal logic signals. Virtual inputs include
signals generated by the local user interface. The virtual outputs are outputs of FlexLogic™ equations used to customize
the device. Virtual outputs can also serve as virtual inputs to FlexLogic™ equations.
The analog inputs and outputs are signals that are associated with transducers, such as Resistance Temperature Detec-
tors (RTDs).
The CT and VT inputs refer to analog current transformer and voltage transformer signals used to monitor AC power lines.
The UR-series relays support 1 A and 5 A CTs.
The remote inputs and outputs provide a means of sharing digital point state information between remote UR-series
devices. The remote outputs interface to the remote inputs of other UR-series devices. Remote outputs are FlexLogic™
operands inserted into IEC 61850 GSSE and GOOSE messages.
The direct inputs and outputs provide a means of sharing digital point states between a number of UR-series IEDs over a
dedicated fiber (single or multimode), RS422, or G.703 interface. No switching equipment is required as the IEDs are con-
nected directly in a ring or redundant (dual) ring configuration. This feature is optimized for speed and intended for pilot-
aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis.

GE Multilin G60 Generator Protection System 1-3


1.2 UR OVERVIEW 1 GETTING STARTED

c) UR SCAN OPERATION

1 The UR-series devices operate in a cyclic scan fashion. The device reads the inputs into an input status table, solves the
logic program (FlexLogic™ equation), and then sets each output to the appropriate state in an output status table. Any
resulting task execution is priority interrupt-driven.

Read Inputs
Protection elements
serviced by sub-scan

Protective Elements
PKP
Solve Logic DPO
OP

Set Outputs

827823A1.CDR

Figure 1–3: UR-SERIES SCAN OPERATION

1.2.3 SOFTWARE ARCHITECTURE

The firmware (software embedded in the relay) is designed in functional modules which can be installed in any relay as
required. This is achieved with object-oriented design and programming (OOD/OOP) techniques.
Object-oriented techniques involve the use of objects and classes. An object is defined as “a logical entity that contains
both data and code that manipulates that data”. A class is the generalized form of similar objects. By using this concept,
one can create a protection class with the protection elements as objects of the class, such as time overcurrent, instanta-
neous overcurrent, current differential, undervoltage, overvoltage, underfrequency, and distance. These objects represent
completely self-contained software modules. The same object-class concept can be used for metering, input/output control,
hmi, communications, or any functional entity in the system.
Employing OOD/OOP in the software architecture of the G60 achieves the same features as the hardware architecture:
modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection,
transformer protection, distance protection) is constructed by combining objects from the various functionality classes. This
results in a common look and feel across the entire family of UR-series platform-based applications.

1.2.4 IMPORTANT CONCEPTS

As described above, the architecture of the UR-series relays differ from previous devices. To achieve a general understand-
ing of this device, some sections of Chapter 5 are quite helpful. The most important functions of the relay are contained in
“elements”. A description of the UR-series elements can be found in the Introduction to elements section in chapter 5.
Examples of simple elements, and some of the organization of this manual, can be found in the Control elements section of
chapter 5. An explanation of the use of inputs from CTs and VTs is in the Introduction to AC sources section in chapter 5. A
description of how digital signals are used and routed within the relay is contained in the Introduction to FlexLogic™ section
in chapter 5.

1-4 G60 Generator Protection System GE Multilin


1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE

1.3ENERVISTA UR SETUP SOFTWARE 1.3.1 PC REQUIREMENTS

The faceplate keypad and display or the EnerVista UR Setup software interface can be used to communicate with the relay.
1
The EnerVista UR Setup software interface is the preferred method to edit settings and view actual values because the PC
monitor can display more information in a simple comprehensible format.
The following minimum requirements must be met for the EnerVista UR Setup software to properly operate on a PC.
• Pentium class or higher processor (Pentium II 300 MHz or higher recommended)
• Windows 95, 98, 98SE, ME, NT 4.0 (Service Pack 4 or higher), 2000, XP
• Internet Explorer 4.0 or higher
• 128 MB of RAM (256 MB recommended)
• 200 MB of available space on system drive and 200 MB of available space on installation drive
• Video capable of displaying 800 x 600 or higher in high-color mode (16-bit color)
• RS232 and/or Ethernet port for communications to the relay
The following qualified modems have been tested to be compliant with the G60 and the EnerVista UR Setup software.
• US Robotics external 56K FaxModem 5686
• US Robotics external Sportster 56K X2
• PCTEL 2304WT V.92 MDC internal modem

1.3.2 INSTALLATION

After ensuring the minimum requirements for using EnerVista UR Setup are met (see previous section), use the following
procedure to install the EnerVista UR Setup from the enclosed GE EnerVista CD.
1. Insert the GE EnerVista CD into your CD-ROM drive.
2. Click the Install Now button and follow the installation instructions to install the no-charge EnerVista software.
3. When installation is complete, start the EnerVista Launchpad application.
4. Click the IED Setup section of the Launch Pad window.

GE Multilin G60 Generator Protection System 1-5


1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED

5. In the EnerVista Launch Pad window, click the Add Product button and select the “G60 Generator Protection System”
from the Install Software window as shown below. Select the “Web” option to ensure the most recent software release,
1 or select “CD” if you do not have a web connection, then click the Add Now button to list software items for the G60.

6. EnerVista Launchpad will obtain the software from the Web or CD and automatically start the installation program.
7. Select the complete path, including the new directory name, where the EnerVista UR Setup will be installed.
8. Click on Next to begin the installation. The files will be installed in the directory indicated and the installation program
will automatically create icons and add EnerVista UR Setup to the Windows start menu.
9. Click Finish to end the installation. The UR-series device will be added to the list of installed IEDs in the EnerVista
Launchpad window, as shown below.

1-6 G60 Generator Protection System GE Multilin


1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE

1.3.3 CONFIGURING THE G60 FOR SOFTWARE ACCESS

a) OVERVIEW 1
The user can connect remotely to the G60 through the rear RS485 port or the rear Ethernet port with a PC running the
EnerVista UR Setup software. The G60 can also be accessed locally with a laptop computer through the front panel RS232
port or the rear Ethernet port using the Quick Connect feature.
• To configure the G60 for remote access via the rear RS485 port(s), refer to the Configuring Serial Communications
section.
• To configure the G60 for remote access via the rear Ethernet port, refer to the Configuring Ethernet Communications
section. An Ethernet module must be specified at the time of ordering.
• To configure the G60 for local access with a laptop through either the front RS232 port or rear Ethernet port, refer to
the Using the Quick Connect Feature section. An Ethernet module must be specified at the time of ordering for Ether-
net communications.

b) CONFIGURING SERIAL COMMUNICATIONS


Before starting, verify that the serial cable is properly connected to the RS485 terminals on the back of the device. The
faceplate RS232 port is intended for local use and is not described in this section; see the Using the Quick Connect Feature
section for details on configuring the RS232 port.
A GE Multilin F485 converter (or compatible RS232-to-RS485 converter) is will be required. Refer to the F485 instruction
manual for additional details.
1. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or
online from http://www.GEmultilin.com). See the Software Installation section for installation details.
2. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
3. Click the Device Setup button to open the Device Setup window and click the Add Site button to define a new site.
4. Enter the desired site name in the “Site Name” field. If desired, a short description of site can also be entered along
with the display order of devices defined for the site. In this example, we will use “Location 1” as the site name. Click
the OK button when complete.
5. The new site will appear in the upper-left list in the EnerVista UR Setup window. Click the Device Setup button then
select the new site to re-open the Device Setup window.
6. Click the Add Device button to define the new device.
7. Enter the desired name in the “Device Name” field and a description (optional) of the site.

GE Multilin G60 Generator Protection System 1-7


1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED

8. Select “Serial” from the Interface drop-down list. This will display a number of interface parameters that must be
entered for proper serial communications.
1

Figure 1–4: CONFIGURING SERIAL COMMUNICATIONS


9. Enter the relay slave address, COM port, baud rate, and parity settings from the SETTINGS Ö PRODUCT SETUP ÖØ COM-
MUNICATIONS ÖØ SERIAL PORTS menu in their respective fields.
10. Click the Read Order Code button to connect to the G60 device and upload the order code. If an communications
error occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step corre-
spond to the relay setting values.
11. Click “OK” when the relay order code has been received. The new device will be added to the Site List window (or
Online window) located in the top left corner of the main EnerVista UR Setup window.
The Site Device has now been configured for RS232 communications. Proceed to the Connecting to the G60 section to
begin communications.

c) CONFIGURING ETHERNET COMMUNICATIONS


Before starting, verify that the Ethernet network cable is properly connected to the Ethernet port on the back of the relay. To
setup the relay for Ethernet communications, it will be necessary to define a Site, then add the relay as a Device at that site.
1. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or
online from http://www.GEmultilin.com). See the Software Installation section for installation details.
2. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.
3. Click the Device Setup button to open the Device Setup window, then click the Add Site button to define a new site.
4. Enter the desired site name in the “Site Name” field. If desired, a short description of site can also be entered along
with the display order of devices defined for the site. In this example, we will use “Location 2” as the site name. Click
the OK button when complete.
5. The new site will appear in the upper-left list in the EnerVista UR Setup window. Click the Device Setup button then
select the new site to re-open the Device Setup window.
6. Click the Add Device button to define the new device.
7. Enter the desired name in the “Device Name” field and a description (optional) of the site.

1-8 G60 Generator Protection System GE Multilin


1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE

8. Select “Ethernet” from the Interface drop-down list. This will display a number of interface parameters that must be
entered for proper Ethernet functionality.
1

Figure 1–5: CONFIGURING ETHERNET COMMUNICATIONS


9. Enter the relay IP address specified in the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK Ö IP
ADDRESS) in the “IP Address” field.
10. Enter the relay slave address and Modbus port address values from the respective settings in the SETTINGS Ö PROD-
UCT SETUP ÖØ COMMUNICATIONS ÖØ MODBUS PROTOCOL menu.

11. Click the Read Order Code button to connect to the G60 device and upload the order code. If an communications
error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay
setting values.
12. Click OK when the relay order code has been received. The new device will be added to the Site List window (or
Online window) located in the top left corner of the main EnerVista UR Setup window.
The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the G60 section to
begin communications.

1.3.4 USING THE QUICK CONNECT FEATURE

a) USING QUICK CONNECT VIA THE FRONT PANEL RS232 PORT


Before starting, verify that the serial cable is properly connected from the laptop computer to the front panel RS232 port
with a straight-through 9-pin to 9-pin RS232 cable.
1. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD or
online from http://www.GEmultilin.com). See the Software Installation section for installation details.
2. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.

GE Multilin G60 Generator Protection System 1-9


1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED

3. Click the Quick Connect button to open the Quick Connect dialog box.

4. Select the Serial interface and the correct COM Port, then click Connect.
5. The EnerVista UR Setup software will create a site named “Quick Connect” with a corresponding device also named
“Quick Connect” and display them on the upper-left corner of the screen. Expand the sections to view data directly
from the G60 device.
Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica-
tions to the G60. This ensures that configuration of the EnerVista UR Setup software matches the G60 model number.

b) USING QUICK CONNECT VIA THE REAR ETHERNET PORTS


To use the Quick Connect feature to access the G60 from a laptop through Ethernet, first assign an IP address to the relay
from the front panel keyboard.
1. Press the MENU key until the SETTINGS menu is displayed.
2. Navigate to the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK Ö IP ADDRESS setting.
3. Enter an IP address of “1.1.1.1” and select the ENTER key to save the value.
4. In the same menu, select the SUBNET IP MASK setting.
5. Enter a subnet IP address of “255.0.0.0” and press the ENTER key to save the value.
Next, use an Ethernet cross-over cable to connect the laptop to the rear Ethernet port. The pinout for an Ethernet cross-
over cable is shown below.
4 5 6
3 END 1 END 2
2 7 Pin Wire color Diagram Pin Wire color Diagram
1 8 1 White/orange 1 White/green
2 Orange 2 Green
3 White/green 3 White/orange
4 Blue 4 Blue
5 White/blue 5 White/blue
6 Green 6 Orange
7 White/brown 7 White/brown
8 Brown 8 Brown
842799A1.CDR

Figure 1–6: ETHERNET CROSS-OVER CABLE PIN LAYOUT


Now, assign the laptop computer an IP address compatible with the relay’s IP address.

1-10 G60 Generator Protection System GE Multilin


1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE

1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con-
nections window.
1

2. Right-click the Local Area Connection icon and select Properties.

3. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.

4. Click on the “Use the following IP address” box.

GE Multilin G60 Generator Protection System 1-11


1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED

5. Enter an IP address with the first three numbers the same as the IP address of the G60 relay and the last number dif-
ferent (in this example, 1.1.1.2).
1 6. Enter a subnet mask equal to the one set in the G60 (in this example, 255.0.0.0).
7. Click OK to save the values.
Before continuing, it will be necessary to test the Ethernet connection.
1. Open a Windows console window by selecting Start > Run from the Windows Start menu and typing “cmd”.
2. Type the following command:
C:\WINNT>ping 1.1.1.1
3. If the connection is successful, the system will return four replies as follows:
Pinging 1.1.1.1 with 32 bytes of data:
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 4, Lost = 0 (0% loss),
Approximate round trip time in milli-seconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
4. Note that the values for time and TTL will vary depending on local network configuration.
If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data:
Request timed out.
Request timed out.
Request timed out.
Request timed out.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milli-seconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
Verify the physical connection between the G60 and the laptop computer, and double-check the programmed IP address in
the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK Ö IP ADDRESS setting, then repeat step 2 in the above procedure.
If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:
Pinging 1.1.1.1 with 32 bytes of data:
Hardware error.
Hardware error.
Hardware error.
Hardware error.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milli-seconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
Verify the physical connection between the G60 and the laptop computer, and double-check the programmed IP address in
the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK Ö IP ADDRESS setting, then repeat step 2 in the above procedure.
If the following sequence of messages appears when entering the C:\WINNT>ping 1.1.1.1 command:

1-12 G60 Generator Protection System GE Multilin


1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE

Pinging 1.1.1.1 with 32 bytes of data:


Destination
Destination
host
host
unreachable.
unreachable.
1
Destination host unreachable.
Destination host unreachable.
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip time in milli-seconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
Pinging 1.1.1.1 with 32 bytes of data:
Verify the IP address is programmed in the local PC by entering the ipconfig command in the command window.
C:\WINNT>ipconfig
Windows 2000 IP Configuration
Ethernet adapter <F4FE223E-5EB6-4BFB-9E34-1BD7BE7F59FF>:
Connection-specific DNS suffix. . :
IP Address. . . . . . . . . . . . : 0.0.0.0
Subnet Mask . . . . . . . . . . . : 0.0.0.0
Default Gateway . . . . . . . . . :
Ethernet adapter Local Area Connection:
Connection-specific DNS suffix . :
IP Address. . . . . . . . . . . . : 1.1.1.2
Subnet Mask . . . . . . . . . . . : 255.0.0.0
Default Gateway . . . . . . . . . :
C:\WINNT>
It may be necessary to restart the laptop for the change in IP address to take effect (Windows 98 or NT).
Before using the Quick Connect feature through the Ethernet port, it is necessary to disable any configured proxy settings
in Internet Explorer.
1. Start the Internet Explorer software.
2. Select the Tools > Internet Options menu item and click on Connections tab.
3. Click on the LAN Settings button to open the following window.

4. Ensure that the “Use a proxy server for your LAN” box is not checked.
If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon-
nected from the G60 relay.
1. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or
online from http://www.GEmultilin.com). See the Software Installation section for installation details.
2. Start the Internet Explorer software.

GE Multilin G60 Generator Protection System 1-13


1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED

3. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.

1 4. Click the Quick Connect button to open the Quick Connect dialog box.

5. Select the Ethernet interface and enter the IP address assigned to the G60, then click Connect.
6. The EnerVista UR Setup software will create a site named “Quick Connect” with a corresponding device also named
“Quick Connect” and display them on the upper-left corner of the screen. Expand the sections to view data directly
from the G60 device.
Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica-
tions to the G60. This ensures that configuration of the EnerVista UR Setup software matches the G60 model number.
When direct communications with the G60 via Ethernet is complete, make the following changes:
1. From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con-
nections window.
2. Right-click the Local Area Connection icon and select the Properties item.
3. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button.
4. Set the computer to “Obtain a relay address automatically” as shown below.

If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon-
nected from the G60 relay.
AUTOMATIC DISCOVERY OF ETHERNET DEVICES
The EnerVista UR Setup software can automatically discover and communicate to all UR-series IEDs located on an Ether-
net network.
Using the Quick Connect feature, a single click of the mouse will trigger the software to automatically detect any UR-series
relays located on the network. The EnerVista UR Setup software will then proceed to configure all settings and order code
options in the Device Setup menu, for the purpose of communicating to multiple relays. This feature allows the user to
identify and interrogate, in seconds, all UR-series devices in a particular location.

1-14 G60 Generator Protection System GE Multilin


1 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE

1.3.5 CONNECTING TO THE G60 RELAY

1. Open the Display Properties window through the Site List tree as shown below:
1

Quick action hot links

Expand the site list by double-clicking


or selecting the +/– box.

Communications status indicators:


Green = OK
Red = No communications
UR icon = report is open

842743A3.CDR

2. The Display Properties window will open with a status indicator on the lower left of the EnerVista UR Setup window.
3. If the status indicator is red, verify that the Ethernet network cable is properly connected to the Ethernet port on the
back of the relay and that the relay has been properly setup for communications (steps A and B earlier).
If a relay icon appears in place of the status indicator, than a report (such as an oscillography or event record) is open.
Close the report to re-display the green status indicator.
4. The Display Properties settings can now be edited, printed, or changed according to user specifications.
Refer to chapter 4 in this manual and the EnerVista UR Setup Help File for more information about the
using the EnerVista UR Setup software interface.
NOTE

QUICK ACTION HOT LINKS


The EnerVista UR Setup software has several new quick action buttons that provide users with instant access to several
functions that are often performed when using G60 relays. From the online window, users can select which relay to interro-
gate from a pull-down window, then click on the button for the action they wish to perform. The following quick action func-
tions are available:
• View the G60 event record.
• View the last recorded oscillography record.
• View the status of all G60 inputs and outputs.
• View all of the G60 metering values.
• View the G60 protection summary.

GE Multilin G60 Generator Protection System 1-15


1.4 UR HARDWARE 1 GETTING STARTED

1.4UR HARDWARE 1.4.1 MOUNTING AND WIRING

1 Please refer to Chapter 3: Hardware for detailed mounting and wiring instructions. Review all WARNINGS and CAUTIONS
carefully.

1.4.2 COMMUNICATIONS

The EnerVista UR Setup software communicates to the relay via the faceplate RS232 port or the rear panel RS485 / Ether-
net ports. To communicate via the faceplate RS232 port, a standard straight-through serial cable is used. The DB-9 male
end is connected to the relay and the DB-9 or DB-25 female end is connected to the PC COM1 or COM2 port as described
in the CPU communications ports section of chapter 3.

Figure 1–7: RELAY COMMUNICATIONS OPTIONS


To communicate through the G60 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is
required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shielded
twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the G60 rear communications port. The converter termi-
nals (+, –, GND) are connected to the G60 communication module (+, –, COM) terminals. Refer to the CPU communica-
tions ports section in chapter 3 for option details. The line should be terminated with an R-C network (that is, 120 Ω, 1 nF)
as described in the chapter 3.

1.4.3 FACEPLATE DISPLAY

All messages are displayed on a 2 × 20 backlit liquid crystal display (LCD) to make them visible under poor lighting condi-
tions. Messages are descriptive and should not require the aid of an instruction manual for deciphering. While the keypad
and display are not actively being used, the display will default to user-defined messages. Any high priority event driven
message will automatically override the default message and appear on the display.

1-16 G60 Generator Protection System GE Multilin


1 GETTING STARTED 1.5 USING THE RELAY

1.5USING THE RELAY 1.5.1 FACEPLATE KEYPAD

Display messages are organized into pages under the following headings: actual values, settings, commands, and targets.
1
The MENU key navigates through these pages. Each heading page is broken down further into logical subgroups.
The MESSAGE keys navigate through the subgroups. The VALUE keys scroll increment or decrement numerical setting
values when in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alterna-
tively, values may also be entered with the numeric keypad.
The decimal key initiates and advance to the next character in text edit mode or enters a decimal point. The HELP key may
be pressed at any time for context sensitive help messages. The ENTER key stores altered setting values.

1.5.2 MENU NAVIGATION

Press the MENU key to select the desired header display page (top-level menu). The header title appears momentarily fol-
lowed by a header display page menu item. Each press of the MENU key advances through the following main heading
pages:
• Actual values.
• Settings.
• Commands.
• Targets.
• User displays (when enabled).

1.5.3 MENU HIERARCHY

The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double
scroll bar characters („„), while sub-header pages are indicated by single scroll bar characters („). The header display
pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE
UP and DOWN keys move within a group of headers, sub-headers, setting values, or actual values. Continually pressing
the MESSAGE RIGHT key from a header display displays specific information for the header category. Conversely, contin-
ually pressing the MESSAGE LEFT key from a setting value or actual value display returns to the header display.

HIGHEST LEVEL LOWEST LEVEL (SETTING VALUE)

„„ SETTINGS „ PASSWORD ACCESS LEVEL:


„„ PRODUCT SETUP „ SECURITY Restricted

„„ SETTINGS
„„ SYSTEM SETUP

1.5.4 RELAY ACTIVATION

The relay is defaulted to the “Not Programmed” state when it leaves the factory. This safeguards against the installation of
a relay whose settings have not been entered. When powered up successfully, the Trouble LED will be on and the In Ser-
vice LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain
until the relay is explicitly put in the “Programmed” state.
Select the menu message SETTINGS Ö PRODUCT SETUP ÖØ INSTALLATION Ö RELAY SETTINGS
RELAY SETTINGS:
Not Programmed

GE Multilin G60 Generator Protection System 1-17


1.5 USING THE RELAY 1 GETTING STARTED

To put the relay in the “Programmed” state, press either of the VALUE keys once and then press ENTER. The faceplate
Trouble LED will turn off and the In Service LED will turn on. The settings for the relay can be programmed manually (refer
1 to Chapter 5) via the faceplate keypad or remotely (refer to the EnerVista UR Setup help file) via the EnerVista UR Setup
software interface.

1.5.5 RELAY PASSWORDS

It is recommended that passwords be set up for each security level and assigned to specific personnel. There are two user
password security access levels, COMMAND and SETTING:
1. COMMAND
The COMMAND access level restricts the user from making any settings changes, but allows the user to perform the fol-
lowing operations:
• change state of virtual inputs
• clear event records
• clear oscillography records
• operate user-programmable pushbuttons
2. SETTING
The SETTING access level allows the user to make any changes to any of the setting values.
Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level
passwords.
NOTE

1.5.6 FLEXLOGIC™ CUSTOMIZATION

FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex-
Logic™ section in Chapter 5 for additional details.

1-18 G60 Generator Protection System GE Multilin


1 GETTING STARTED 1.5 USING THE RELAY

1.5.7 COMMISSIONING

The G60 requires a minimum amount of maintenance when it is commissioned into service. Since the G60 is a micropro-
1
cessor-based relay, its characteristics do not change over time. As such, no further functional tests are required.
Furthermore, the G60 performs a number of continual self-tests and takes the necessary action in case of any major errors
(see the Relay Self-tests section in chapter 7 for details). However, it is recommended that G60 maintenance be scheduled
with other system maintenance. This maintenance may involve the in-service, out-of-service, or unscheduled maintenance.
In-service maintenance:
1. Visual verification of the analog values integrity such as voltage and current (in comparison to other devices on the cor-
responding system).
2. Visual verification of active alarms, relay display messages, and LED indications.
3. LED test.
4. Visual inspection for any damage, corrosion, dust, or loose wires.
5. Event recorder file download with further events analysis.
Out-of-service maintenance:
1. Check wiring connections for firmness.
2. Analog values (currents, voltages, RTDs, analog inputs) injection test and metering accuracy verification. Calibrated
test equipment is required.
3. Protection elements setting verification (analog values injection or visual verification of setting file entries against relay
settings schedule).
4. Contact inputs and outputs verification. This test can be conducted by direct change of state forcing or as part of the
system functional testing.
5. Visual inspection for any damage, corrosion, or dust.
6. Event recorder file download with further events analysis.
7. LED Test and pushbutton continuity check.
Unscheduled maintenance such as during a disturbance causing system interruption:
1. View the event recorder and oscillography or fault report for correct operation of inputs, outputs, and elements.
If it is concluded that the relay or one of its modules is of concern, contact GE Multilin for prompt service.

GE Multilin G60 Generator Protection System 1-19


1.5 USING THE RELAY 1 GETTING STARTED

1-20 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.1 INTRODUCTION

2 PRODUCT DESCRIPTION 2.1INTRODUCTION 2.1.1 OVERVIEW

The G60 Generator Protection System is a microprocessor based relay that provides protection, monitoring, control, and
recording functions for AC generators driven by steam, gas, or hydraulic turbine. Current, voltage and frequency protection
are provided along with fault diagnostics.
Voltage, current, and power metering is built into the relay as a standard feature. Current parameters are available as total
waveform RMS magnitude, or as fundamental frequency only RMS magnitude and angle (phasor).
Diagnostic features include an event recorder capable of storing 1024 time-tagged events, oscillography capable of storing
2
up to 64 records with programmable trigger, content and sampling rate, and data logger acquisition of up to 16 channels,
with programmable content and sampling rate. The internal clock used for time-tagging can be synchronized with an IRIG-
B signal or via the SNTP protocol over the Ethernet port. This precise time stamping allows the sequence of events to be
determined throughout the system. Events can also be programmed (via FlexLogic™ equations) to trigger oscillography
data capture which may be set to record the measured parameters before and after the event for viewing on a personal
computer (PC). These tools significantly reduce troubleshooting time and simplify report generation in the event of a sys-
tem fault.
A faceplate RS232 port may be used to connect to a PC for the programming of settings and the monitoring of actual val-
ues. A variety of communications modules are available. Two rear RS485 ports allow independent access by operating and
engineering staff. All serial ports use the Modbus® RTU protocol. The RS485 ports may be connected to system computers
with baud rates up to 115.2 kbps. The RS232 port has a fixed baud rate of 19.2 kbps. Optional communications modules
include a 10Base-F Ethernet interface which can be used to provide fast, reliable communications in noisy environments.
Another option provides two 10Base-F fiber optic ports for redundancy. The Ethernet port supports IEC 61850, Modbus®/
TCP, and TFTP protocols, and allows access to the relay via any standard web browser (G60 web pages). The IEC 60870-
5-104 protocol is supported on the Ethernet port. DNP 3.0 and IEC 60870-5-104 cannot be enabled at the same time.
The G60 IEDs use flash memory technology which allows field upgrading as new features are added. The following Single
line diagram illustrates the relay functionality using ANSI (American National Standards Institute) device numbers.

Table 2–1: ANSI DEVICE NUMBERS AND FUNCTIONS


DEVICE FUNCTION DEVICE FUNCTION
NUMBER NUMBER
21P Phase distance backup 59N Neutral overvoltage
24 Volts per hertz 59P Phase overvoltage
25 Synchrocheck 59X Auxiliary overvoltage
27P Phase undervoltage 59_2 Negative-sequence overvoltage
27TN Third harmonic neutral undervoltage 64F Field ground protection
27X Auxiliary undervoltage 64S Sub-harmonic stator ground protection
32 Sensitive directional power 64TN 100% stator ground
40 Loss of excitation 67_2 Negative-sequence directional overcurrent
46 Generator unbalance 67N Neutral directional overcurrent
49 Thermal overload (RTD) 67P Phase directional overcurrent
50G Ground instantaneous overcurrent 68/78 Power swing detection
50N Neutral instantaneous overcurrent 81A Frequency out-of-band accumulation
50P Phase instantaneous overcurrent 81O Overfrequency
50SP Split phase protection 81R Rate of change of frequency
50/27 Accidental energization 81U Underfrequency
51G Ground time overcurrent 87G Restricted ground fault
51P Phase time overcurrent 87S Stator differential

GE Multilin G60 Generator Protection System 2-1


2.1 INTRODUCTION 2 PRODUCT DESCRIPTION

Close
52
Trip 25

24 27P 59P 59_2 59N 81O 81U 81R


2

32 40 50/27 21P 50P 50N 51P 51N 46 67P 67_2 67N 68 78

49

G EX GPM-F 64F

Metering
87S

87G 50G 51G


27TN 27X 59X

R 64TN

64S

G60 Generator Protection System


830710B1.CDR

Figure 2–1: SINGLE LINE DIAGRAM

Table 2–2: OTHER DEVICE FUNCTIONS


FUNCTION FUNCTION FUNCTION
Breaker control FlexElements™ (16) Stator differential
Contact inputs (up to 96) Generator unbalance Synchrophasors
Contact outputs (up to 96) IEC 61850 communications (optional) Time synchronization over SNTP
Control pushbuttons Metering: current, voltage, power, Transducer inputs and outputs
frequency
Data logger Trip output
Digital counters (8) Oscillography User-definable displays
Digital elements (48) Modbus communications User-programmable fault reports
Direct inputs and outputs (32) Modbus user map User-programmable LEDs
Disconnect switches Non-volatile latches User-programmable pushbuttons
DNP 3.0 or IEC 60870-5-104 protocol Non-volatile selector switch User-programmable self-tests
Ethernet Global Data protocol (optional) RTD protection Virtual inputs (64)
Event recorder Remote RTD protection Virtual outputs (96)
FlexLogic™ equations Setting groups (6) VT fuse failure

2-2 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.1 INTRODUCTION

2.1.2 ORDERING

a) OVERVIEW
The G60 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following mod-
ules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications.
Each of these modules can be supplied in a number of configurations specified at the time of ordering. The information
required to completely specify the relay is provided in the following tables (see chapter 3 for full details of relay modules).
Order codes are subject to change without notice. Refer to the GE Multilin ordering page at 2
http://www.GEindustrial.com/multilin/order.htm for the latest details concerning G60 ordering options.
NOTE

The order code structure is dependent on the mounting option (horizontal or vertical) and the type of CT/VT modules (regu-
lar CT/VT modules or the HardFiber modules). The order code options are described in the following sub-sections.

GE Multilin G60 Generator Protection System 2-3


2.1 INTRODUCTION 2 PRODUCT DESCRIPTION

b) ORDER CODES WITH TRADITIONAL CTS AND VTS


The order codes for the horizontal mount units with traditional CTs and VTs are shown below.

Table 2–3: G60 ORDER CODES (HORIZONTAL UNITS)


G60 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount
BASE UNIT G60 | | | | | | | | | | | Base Unit
CPU E | | | | | | | | | | RS485 and RS485
G | | | | | | | | | | RS485 and multi-mode ST 10Base-F
H | | | | | | | | | | RS485 and multi-mode ST redundant 10Base-F
J | | | | | | | | | | RS485 and multi-mode ST 100Base-FX

2 K
L
M
S
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RS485 and multi-mode ST redundant 100Base-FX
RS485 and single mode SC 100Base-FX
RS485 and single mode SC redundant 100Base-FX
RS485 and six-port managed Ethernet switch
SOFTWARE 00 | | | | | | | | | No Software Options
01 | | | | | | | | | Ethernet Global Data (EGD); not available for Type E CPUs
03 | | | | | | | | | IEC 61850; not available for Type E CPUs
04 | | | | | | | | | Ethernet Global Data (EGD) and IEC 61850; not available for Type E CPUs
06 | | | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | | | IEC 61850 and phasor measurement unit (PMU)
MOUNT/COATING H | | | | | | | | Horizontal (19” rack)
A | | | | | | | | Horizontal (19” rack) with harsh environmental coating
FACEPLATE/ DISPLAY C | | | | | | | English display
D | | | | | | | French display
R | | | | | | | Russian display
A | | | | | | | Chinese display
P | | | | | | | English display with 4 small and 12 large programmable pushbuttons
G | | | | | | | French display with 4 small and 12 large programmable pushbuttons
S | | | | | | | Russian display with 4 small and 12 large programmable pushbuttons
B | | | | | | | Chinese display with 4 small and 12 large programmable pushbuttons
K | | | | | | | Enhanced front panel with English display
M | | | | | | | Enhanced front panel with French display
Q | | | | | | | Enhanced front panel with Russian display
U | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
POWER SUPPLY H | | | | | | 125 / 250 V AC/DC power supply
(redundant supply must H | | | | | RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
be same type as main supply) L | | | | | | 24 to 48 V (DC only) power supply
L | | | | | RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
CT/VT MODULES 8F | 8F | | | Standard 4CT/4VT
8G | 8G | | | Sensitive Ground 4CT/4VT
8H | 8H | | | Standard 8CT
8J | 8J | | | Sensitive Ground 8CT
8L | 8L | | | Standard 4CT/4VT with enhanced diagnostics
8M | 8M | | | Sensitive Ground 4CT/4VT with enhanced diagnostics
8N | 8N | | | Standard 8CT with enhanced diagnostics
8R | 8R | | | Sensitive Ground 8CT with enhanced diagnostics
DIGITAL INPUTS/OUTPUTS XX XX XX XX XX No Module
4A 4A 4A 4A 4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4B 4B 4B 4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C 4C 4C 4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D 4D 4D 4D 16 digital inputs with Auto-Burnishing
4L 4L 4L 4L 4L 14 Form-A (no monitoring) Latching outputs
67 67 67 67 67 8 Form-A (no monitoring) outputs
6A 6A 6A 6A 6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 6B 6B 6B 6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 6C 6C 6C 6C 8 Form-C outputs
6D 6D 6D 6D 6D 16 digital inputs
6E 6E 6E 6E 6E 4 Form-C outputs, 8 digital inputs
6F 6F 6F 6F 6F 8 Fast Form-C outputs
6G 6G 6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6H 6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 6K 6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 6M 6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 6N 6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6P 6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 6R 6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 6S 6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 6T 6T 6T 6T 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6U 6U 6U 6U 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 6V 6V 6V 6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
TRANSDUCER 5A 5A 5A 5A 5A 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS 5C 5C 5C 5C 5C 8 RTD inputs
(select a maximum of 3 per unit) 5D 5D 5D 5D 5D 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
5E 5E 5E 5E 5E 4 RTD inputs, 4 dcmA inputs
5F 5F 5F 5F 5F 8 dcmA inputs
INTER-RELAY 2A 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E 2E Bi-phase, single channel
2F 2F Bi-phase, dual channel
2G 2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H 2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 2S Six-port managed Ethernet switch with high voltage power supply (110 to 250 V DC / 100 to 240 V AC)
| 2T Six-port managed Ethernet switch with low voltage power supply (48 V DC)
72 72 1550 nm, single-mode, LASER, 1 Channel
73 73 1550 nm, single-mode, LASER, 2 Channel
74 74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 7A 820 nm, multi-mode, LED, 1 Channel
7B 7B 1300 nm, multi-mode, LED, 1 Channel
7C 7C 1300 nm, single-mode, ELED, 1 Channel
7D 7D 1300 nm, single-mode, LASER, 1 Channel
7E 7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F 7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G 7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 7H 820 nm, multi-mode, LED, 2 Channels
7I 7I 1300 nm, multi-mode, LED, 2 Channels
7J 7J 1300 nm, single-mode, ELED, 2 Channels
7K 7K 1300 nm, single-mode, LASER, 2 Channels
7L 7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M 7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N 7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P 7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q 7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R 7R G.703, 1 Channel
7S 7S G.703, 2 Channels
7T 7T RS422, 1 Channel
7W 7W RS422, 2 Channels

2-4 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.1 INTRODUCTION

The order codes for the reduced size vertical mount units with traditional CTs and VTs are shown below.

Table 2–4: G60 ORDER CODES (REDUCED SIZE VERTICAL UNITS)


G60 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
BASE UNIT G60 | | | | | | | | | Base Unit
CPU E | | | | | | | | RS485 and RS485
G | | | | | | | | RS485 and multi-mode ST 10Base-F
H | | | | | | | | RS485 and multi-mode ST redundant 10Base-F
J | | | | | | | | RS485 and multi-mode ST 100Base-FX
K | | | | | | | | RS485 and multi-mode ST redundant 100Base-FX
L | | | | | | | | RS485 and single mode SC 100Base-FX
M | | | | | | | | RS485 and single mode SC redundant 100Base-FX
SOFTWARE 00
01
03
04
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

|
No Software Options
Ethernet Global Data (EGD); not available for Type E CPUs
IEC 61850; not available for Type E CPUs
Ethernet Global Data (EGD) and IEC 61850; not available for Type E CPUs
2
06 | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | IEC 61850 and phasor measurement unit (PMU)
MOUNT/COATING V | | | | | | Vertical (3/4 rack)
B | | | | | | Vertical (3/4 rack) with harsh environmental coating
FACEPLATE/ DISPLAY F | | | | | English display
D | | | | | French display
R | | | | | Russian display
A | | | | | Chinese display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
POWER SUPPLY H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
CT/VT MODULES 8F | 8F | Standard 4CT/4VT
8G | 8G | Sensitive Ground 4CT/4VT
8H | 8H | Standard 8CT
8J | 8J | Sensitive Ground 8CT
8L | 8L | Standard 4CT/4VT with enhanced diagnostics
8M | 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
8N | 8N | Standard 8CT with enhanced diagnostics
8R | 8R | Sensitive Ground 8CT with enhanced diagnostics
DIGITAL INPUTS/OUTPUTS XX XX XX No Module
4A 4A 4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4B 4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C 4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D 4D 16 digital inputs with Auto-Burnishing
4L 4L 4L 14 Form-A (no monitoring) Latching outputs
67 67 67 8 Form-A (no monitoring) outputs
6A 6A 6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 6B 6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 6C 6C 8 Form-C outputs
6D 6D 6D 16 digital inputs
6E 6E 6E 4 Form-C outputs, 8 digital inputs
6F 6F 6F 8 Fast Form-C outputs
6G 6G 6G 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6H 6H 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 6K 6K 4 Form-C and 4 Fast Form-C outputs
6L 6L 6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 6M 6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 6N 6N 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6P 6P 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 6R 6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 6S 6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 6T 6T 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6U 6U 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 6V 6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
TRANSDUCER 5A 5A 5A 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS 5C 5C 5C 8 RTD inputs
5D 5D 5D 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
5E 5E 5E 4 RTD inputs, 4 dcmA inputs
5F 5F 5F 8 dcmA inputs
INTER-RELAY 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit 2E Bi-phase, single channel
For the last module, slot P is used for digital and transducer 2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
input/output modules; slot R is used for inter-relay
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
communications modules. 72 1550 nm, single-mode, LASER, 1 Channel
73 1550 nm, single-mode, LASER, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, LASER, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, LASER, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels

GE Multilin G60 Generator Protection System 2-5


2.1 INTRODUCTION 2 PRODUCT DESCRIPTION

c) ORDER CODES WITH PROCESS BUS MODULES


The order codes for the horizontal mount units with the process bus module are shown below.

Table 2–5: G60 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS)
G60 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount
BASE UNIT G60 | | | | | | | | | | | Base Unit
CPU E | | | | | | | | | | RS485 and RS485
G | | | | | | | | | | RS485 and multi-mode ST 10Base-F
H | | | | | | | | | | RS485 and multi-mode ST redundant 10Base-F
J | | | | | | | | | | RS485 and multi-mode ST 100Base-FX

2 SOFTWARE
K
L
M
|
|
|
00
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RS485 and multi-mode ST redundant 100Base-FX
RS485 and single mode SC 100Base-FX
RS485 and single mode SC redundant 100Base-FX
No Software Options
01 | | | | | | | | | Ethernet Global Data (EGD); not available for Type E CPUs
03 | | | | | | | | | IEC 61850; not available for Type E CPUs
04 | | | | | | | | | Ethernet Global Data (EGD) and IEC 61850; not available for Type E CPUs
06 | | | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | | | IEC 61850 and phasor measurement unit (PMU)
MOUNT/COATING H | | | | | | | | Horizontal (19” rack)
A | | | | | | | | Horizontal (19” rack) with harsh environmental coating
FACEPLATE/ DISPLAY C | | | | | | | English display
D | | | | | | | French display
R | | | | | | | Russian display
A | | | | | | | Chinese display
P | | | | | | | English display with 4 small and 12 large programmable pushbuttons
G | | | | | | | French display with 4 small and 12 large programmable pushbuttons
S | | | | | | | Russian display with 4 small and 12 large programmable pushbuttons
B | | | | | | | Chinese display with 4 small and 12 large programmable pushbuttons
K | | | | | | | Enhanced front panel with English display
M | | | | | | | Enhanced front panel with French display
Q | | | | | | | Enhanced front panel with Russian display
U | | | | | | | Enhanced front panel with Chinese display
L | | | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
POWER SUPPLY H | | | | | | 125 / 250 V AC/DC power supply
(redundant supply must H | | | | | RH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
be same type as main supply) L | | | | | | 24 to 48 V (DC only) power supply
L | | | | | RL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
PROCESS BUS MODULE | 81 | | | | Eight-port digital process bus module
DIGITAL INPUTS/OUTPUTS XX XX XX XX XX No Module
4A 4A | 4 Solid-State (no monitoring) MOSFET outputs
4B 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
4D 4D | 16 digital inputs with Auto-Burnishing
4L 4L | 14 Form-A (no monitoring) Latching outputs
67 67 | 8 Form-A (no monitoring) outputs
6A 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 6C | 8 Form-C outputs
6D 6D | 16 digital inputs
6E 6E | 4 Form-C outputs, 8 digital inputs
6F 6F | 8 Fast Form-C outputs
6G 6G | 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6H | 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 6K | 4 Form-C and 4 Fast Form-C outputs
6L 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 6N | 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6P | 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 6T | 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6U | 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
INTER-RELAY 2A 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit) 2E 2E Bi-phase, single channel
2F 2F Bi-phase, dual channel
2G 2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
2H 2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
72 72 1550 nm, single-mode, LASER, 1 Channel
73 73 1550 nm, single-mode, LASER, 2 Channel
74 74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 7A 820 nm, multi-mode, LED, 1 Channel
7B 7B 1300 nm, multi-mode, LED, 1 Channel
7C 7C 1300 nm, single-mode, ELED, 1 Channel
7D 7D 1300 nm, single-mode, LASER, 1 Channel
7E 7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F 7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G 7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 7H 820 nm, multi-mode, LED, 2 Channels
7I 7I 1300 nm, multi-mode, LED, 2 Channels
7J 7J 1300 nm, single-mode, ELED, 2 Channels
7K 7K 1300 nm, single-mode, LASER, 2 Channels
7L 7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M 7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N 7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P 7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q 7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R 7R G.703, 1 Channel
7S 7S G.703, 2 Channels
7T 7T RS422, 1 Channel
7W 7W RS422, 2 Channels

2-6 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.1 INTRODUCTION

The order codes for the reduced size vertical mount units with the process bus module are shown below.

Table 2–6: G60 ORDER CODES (REDUCED SIZE VERTICAL UNITS WITH PROCESS BUS)
G60 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see note regarding P/R slot below)
BASE UNIT G60 | | | | | | | | | Base Unit
CPU E | | | | | | | | RS485 and RS485
G | | | | | | | | RS485 and multi-mode ST 10Base-F
H | | | | | | | | RS485 and multi-mode ST redundant 10Base-F
J | | | | | | | | RS485 and multi-mode ST 100Base-FX
K | | | | | | | | RS485 and multi-mode ST redundant 100Base-FX
L | | | | | | | | RS485 and single mode SC 100Base-FX
M | | | | | | | | RS485 and single mode SC redundant 100Base-FX
SOFTWARE 00
01
03
04
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
No Software Options
Ethernet Global Data (EGD); not available for Type E CPUs
IEC 61850; not available for Type E CPUs
Ethernet Global Data (EGD) and IEC 61850; not available for Type E CPUs
2
06 | | | | | | | Phasor measurement unit (PMU)
07 | | | | | | | IEC 61850 and phasor measurement unit (PMU)
MOUNT/COATING V | | | | | | Vertical (3/4 rack)
B | | | | | | Vertical (3/4 rack) with harsh environmental coating
FACEPLATE/ DISPLAY F | | | | | English display
D | | | | | French display
R | | | | | Russian display
A | | | | | Chinese display
K | | | | | Enhanced front panel with English display
M | | | | | Enhanced front panel with French display
Q | | | | | Enhanced front panel with Russian display
U | | | | | Enhanced front panel with Chinese display
L | | | | | Enhanced front panel with English display and user-programmable pushbuttons
N | | | | | Enhanced front panel with French display and user-programmable pushbuttons
T | | | | | Enhanced front panel with Russian display and user-programmable pushbuttons
V | | | | | Enhanced front panel with Chinese display and user-programmable pushbuttons
POWER SUPPLY H | | | | 125 / 250 V AC/DC power supply
L | | | | 24 to 48 V (DC only) power supply
PROCESS BUS MODULE | 81 | | Eight-port digital process bus module
DIGITAL INPUTS/OUTPUTS XX XX XX No Module
4A 4 Solid-State (no monitoring) MOSFET outputs
4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D 16 digital inputs with Auto-Burnishing
4L 14 Form-A (no monitoring) Latching outputs
67 8 Form-A (no monitoring) outputs
6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
6C 8 Form-C outputs
6D 16 digital inputs
6E 4 Form-C outputs, 8 digital inputs
6F 8 Fast Form-C outputs
6G 4 Form-A (voltage with optional current) outputs, 8 digital inputs
6H 6 Form-A (voltage with optional current) outputs, 4 digital inputs
6K 4 Form-C and 4 Fast Form-C outputs
6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
6N 4 Form-A (current with optional voltage) outputs, 8 digital inputs
6P 6 Form-A (current with optional voltage) outputs, 4 digital inputs
6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
6T 4 Form-A (no monitoring) outputs, 8 digital inputs
6U 6 Form-A (no monitoring) outputs, 4 digital inputs
6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
INTER-RELAY 2A C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
COMMUNICATIONS 2B C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
(select a maximum of 1 per unit 2E Bi-phase, single channel
For the last module, slot P is used for digital 2F Bi-phase, dual channel
2G IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
input/output modules; slot R is used for inter-relay
2H IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
communications modules. 72 1550 nm, single-mode, LASER, 1 Channel
73 1550 nm, single-mode, LASER, 2 Channel
74 Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
75 Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
76 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
7A 820 nm, multi-mode, LED, 1 Channel
7B 1300 nm, multi-mode, LED, 1 Channel
7C 1300 nm, single-mode, ELED, 1 Channel
7D 1300 nm, single-mode, LASER, 1 Channel
7E Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
7F Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
7G Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
7H 820 nm, multi-mode, LED, 2 Channels
7I 1300 nm, multi-mode, LED, 2 Channels
7J 1300 nm, single-mode, ELED, 2 Channels
7K 1300 nm, single-mode, LASER, 2 Channels
7L Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
7M Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
7N Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
7P Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
7Q Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
7R G.703, 1 Channel
7S G.703, 2 Channels
7T RS422, 1 Channel
7W RS422, 2 Channels

2.1.3 REPLACEMENT MODULES

Replacement modules can be ordered separately as shown below. When ordering a replacement CPU module or face-
plate, please provide the serial number of your existing unit.
Not all replacement modules may be applicable to the G60 relay. Only the modules specified in the order codes are
available as replacement modules.
NOTE
Replacement module codes are subject to change without notice. Refer to the GE Multilin ordering page at http://
www.GEindustrial.com/multilin/order.htm for the latest details concerning G60 ordering options.
NOTE

GE Multilin G60 Generator Protection System 2-7


2.1 INTRODUCTION 2 PRODUCT DESCRIPTION

The replacement module order codes for the horizontal mount units are shown below.

Table 2–7: ORDER CODES FOR REPLACEMENT MODULES, HORIZONTAL UNITS


UR - ** - *
POWER SUPPLY | 1H | 125 / 250 V AC/DC
(redundant supply only available in horizontal units; | 1L | 24 to 48 V (DC only)
must be same type as main supply) | RH | redundant 125 / 250 V AC/DC
| RH | redundant 24 to 48 V (DC only)
CPU | 9E | RS485 and RS485 (Modbus RTU, DNP 3.0)
| 9G | RS485 and 10Base-F (Ethernet, Modbus TCP/IP, DNP 3.0)
| 9H | RS485 and Redundant 10Base-F (Ethernet, Modbus TCP/IP, DNP 3.0)
| 9J | RS485 and multi-mode ST 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)

2 |
|
|
|
9K
9L
9M
9N
|
|
|
|
RS485 and multi-mode ST redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
RS485 and single mode SC 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
RS485 and single mode SC redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
RS485 and 10/100Base-T
| 9S | RS485 and six-port managed Ethernet switch
FACEPLATE/DISPLAY | 3C | Horizontal faceplate with keypad and English display
| 3D | Horizontal faceplate with keypad and French display
| 3R | Horizontal faceplate with keypad and Russian display
| 3A | Horizontal faceplate with keypad and Chinese display
| 3P | Horizontal faceplate with keypad, user-programmable pushbuttons, and English display
| 3G | Horizontal faceplate with keypad, user-programmable pushbuttons, and French display
| 3S | Horizontal faceplate with keypad, user-programmable pushbuttons, and Russian display
| 3B | Horizontal faceplate with keypad, user-programmable pushbuttons, and Chinese display
| 3K | Enhanced front panel with English display
| 3M | Enhanced front panel with French display
| 3Q | Enhanced front panel with Russian display
| 3U | Enhanced front panel with Chinese display
| 3L | Enhanced front panel with English display and user-programmable pushbuttons
| 3N | Enhanced front panel with French display and user-programmable pushbuttons
| 3T | Enhanced front panel with Russian display and user-programmable pushbuttons
| 3V | Enhanced front panel with Chinese display and user-programmable pushbuttons
DIGITAL INPUTS AND OUTPUTS | 4A | 4 Solid-State (no monitoring) MOSFET outputs
| 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
| 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
| 4D | 16 digital inputs with Auto-Burnishing
| 4L | 14 Form-A (no monitoring) Latching outputs
| 67 | 8 Form-A (no monitoring) outputs
| 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
| 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
| 6C | 8 Form-C outputs
| 6D | 16 digital inputs
| 6E | 4 Form-C outputs, 8 digital inputs
| 6F | 8 Fast Form-C outputs
| 6G | 4 Form-A (voltage with optional current) outputs, 8 digital inputs
| 6H | 6 Form-A (voltage with optional current) outputs, 4 digital inputs
| 6K | 4 Form-C and 4 Fast Form-C outputs
| 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
| 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
| 6N | 4 Form-A (current with optional voltage) outputs, 8 digital inputs
| 6P | 6 Form-A (current with optional voltage) outputs, 4 digital inputs
| 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
| 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
| 6T | 4 Form-A (no monitoring) outputs, 8 digital inputs
| 6U | 6 Form-A (no monitoring) outputs, 4 digital inputs
| 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
CT/VT | 8F | Standard 4CT/4VT
MODULES | 8G | Sensitive Ground 4CT/4VT
(NOT AVAILABLE FOR THE C30) | 8H | Standard 8CT
| 8J | Sensitive Ground 8CT
| 8L | Standard 4CT/4VT with enhanced diagnostics
| 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
| 8N | Standard 8CT with enhanced diagnostics
| 8R | Sensitive Ground 8CT with enhanced diagnostics
INTER-RELAY COMMUNICATIONS | 2A | C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
| 2B | C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
| 2E | Bi-phase, single channel
| 2F | Bi-phase, dual channel
| 2G | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
| 2H | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 2S | Six-port managed Ethernet switch with high voltage power supply (110 to 250 V DC / 100 to 240 V AC)
| 2T | Six-port managed Ethernet switch with low voltage power supply (48 V DC)
| 72 | 1550 nm, single-mode, LASER, 1 Channel
| 73 | 1550 nm, single-mode, LASER, 2 Channel
| 74 | Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
| 75 | Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
| 76 | IEEE C37.94, 820 nm, multimode, LED, 1 Channel
| 77 | IEEE C37.94, 820 nm, multimode, LED, 2 Channels
| 7A | 820 nm, multi-mode, LED, 1 Channel
| 7B | 1300 nm, multi-mode, LED, 1 Channel
| 7C | 1300 nm, single-mode, ELED, 1 Channel
| 7D | 1300 nm, single-mode, LASER, 1 Channel
| 7E | Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
| 7F | Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
| 7G | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
| 7H | 820 nm, multi-mode, LED, 2 Channels
| 7I | 1300 nm, multi-mode, LED, 2 Channels
| 7J | 1300 nm, single-mode, ELED, 2 Channels
| 7K | 1300 nm, single-mode, LASER, 2 Channels
| 7L | Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
| 7M | Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
| 7N | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
| 7P | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
| 7Q | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
| 7R | G.703, 1 Channel
| 7S | G.703, 2 Channels
| 7T | RS422, 1 Channel
| 7W | RS422, 2 Channels
TRANSDUCER | 5A | 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS | 5C | 8 RTD inputs
| 5D | 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
| 5E | 4 dcmA inputs, 4 RTD inputs
| 5F | 8 dcmA inputs

2-8 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.1 INTRODUCTION

The replacement module order codes for the reduced-size vertical mount units are shown below.

Table 2–8: ORDER CODES FOR REPLACEMENT MODULES, VERTICAL UNITS


UR - ** - *
POWER SUPPLY | 1H | 125 / 250 V AC/DC
| 1L | 24 to 48 V (DC only)
CPU | 9E | RS485 and RS485 (Modbus RTU, DNP 3.0)
| 9G | RS485 and 10Base-F (Ethernet, Modbus TCP/IP, DNP 3.0)
| 9H | RS485 and Redundant 10Base-F (Ethernet, Modbus TCP/IP, DNP 3.0)
| 9J | RS485 and multi-mode ST 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
| 9K | RS485 and multi-mode ST redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
| 9L | RS485 and single mode SC 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)

FACEPLATE/DISPLAY
|
|
|
|
9M
9N
3F
3D
|
|
|
|
RS485 and single mode SC redundant 100Base-FX (Ethernet, Modbus TCP/IP, DNP 3.0)
RS485 and 10/100Base-T
Vertical faceplate with keypad and English display
Vertical faceplate with keypad and French display
2
| 3R | Vertical faceplate with keypad and Russian display
| 3K | Vertical faceplate with keypad and Chinese display
| 3K | Enhanced front panel with English display
| 3M | Enhanced front panel with French display
| 3Q | Enhanced front panel with Russian display
| 3U | Enhanced front panel with Chinese display
| 3L | Enhanced front panel with English display and user-programmable pushbuttons
| 3N | Enhanced front panel with French display and user-programmable pushbuttons
| 3T | Enhanced front panel with Russian display and user-programmable pushbuttons
| 3V | Enhanced front panel with Chinese display and user-programmable pushbuttons
DIGITAL | 4A | 4 Solid-State (no monitoring) MOSFET outputs
INPUTS/OUTPUTS | 4B | 4 Solid-State (voltage with optional current) MOSFET outputs
| 4C | 4 Solid-State (current with optional voltage) MOSFET outputs
| 4D | 16 digital inputs with Auto-Burnishing
| 4L | 14 Form-A (no monitoring) Latching outputs
| 67 | 8 Form-A (no monitoring) outputs
| 6A | 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 digital inputs
| 6B | 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 digital inputs
| 6C | 8 Form-C outputs
| 6D | 16 digital inputs
| 6E | 4 Form-C outputs, 8 digital inputs
| 6F | 8 Fast Form-C outputs
| 6G | 4 Form-A (voltage with optional current) outputs, 8 digital inputs
| 6H | 6 Form-A (voltage with optional current) outputs, 4 digital inputs
| 6K | 4 Form-C and 4 Fast Form-C outputs
| 6L | 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 digital inputs
| 6M | 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 digital inputs
| 6N | 4 Form-A (current with optional voltage) outputs, 8 digital inputs
| 6P | 6 Form-A (current with optional voltage) outputs, 4 digital inputs
| 6R | 2 Form-A (no monitoring) and 2 Form-C outputs, 8 digital inputs
| 6S | 2 Form-A (no monitoring) and 4 Form-C outputs, 4 digital inputs
| 6T | 4 Form-A (no monitoring) outputs, 8 digital inputs
| 6U | 6 Form-A (no monitoring) outputs, 4 digital inputs
| 6V | 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs
CT/VT | 8F | Standard 4CT/4VT
MODULES | 8G | Sensitive Ground 4CT/4VT
(NOT AVAILABLE FOR THE C30) | 8H | Standard 8CT
| 8J | Sensitive Ground 8CT
| 8L | Standard 4CT/4VT with enhanced diagnostics
| 8M | Sensitive Ground 4CT/4VT with enhanced diagnostics
| 8N | Standard 8CT with enhanced diagnostics
| 8R | Sensitive Ground 8CT with enhanced diagnostics
INTER-RELAY COMMUNICATIONS | 2A | C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode
| 2B | C37.94SM, 1300nm single-mode, ELED, 2 channel single-mode
| 2E | Bi-phase, single channel
| 2F | Bi-phase, dual channel
| 2G | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 1 Channel
| 2H | IEEE C37.94, 820 nm, 128 kbps, multimode, LED, 2 Channels
| 72 | 1550 nm, single-mode, LASER, 1 Channel
| 73 | 1550 nm, single-mode, LASER, 2 Channel
| 74 | Channel 1 - RS422; Channel 2 - 1550 nm, single-mode, LASER
| 75 | Channel 1 - G.703; Channel 2 - 1550 nm, Single-mode LASER
| 76 | IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 1 Channel
| 77 | IEEE C37.94, 820 nm, 64 kbps, multimode, LED, 2 Channels
| 7A | 820 nm, multi-mode, LED, 1 Channel
| 7B | 1300 nm, multi-mode, LED, 1 Channel
| 7C | 1300 nm, single-mode, ELED, 1 Channel
| 7D | 1300 nm, single-mode, LASER, 1 Channel
| 7E | Channel 1 - G.703; Channel 2 - 820 nm, multi-mode
| 7F | Channel 1 - G.703; Channel 2 - 1300 nm, multi-mode
| 7G | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode ELED
| 7H | 820 nm, multi-mode, LED, 2 Channels
| 7I | 1300 nm, multi-mode, LED, 2 Channels
| 7J | 1300 nm, single-mode, ELED, 2 Channels
| 7K | 1300 nm, single-mode, LASER, 2 Channels
| 7L | Channel 1 - RS422; Channel 2 - 820 nm, multi-mode, LED
| 7M | Channel 1 - RS422; Channel 2 - 1300 nm, multi-mode, LED
| 7N | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, ELED
| 7P | Channel 1 - RS422; Channel 2 - 1300 nm, single-mode, LASER
| 7Q | Channel 1 - G.703; Channel 2 - 1300 nm, single-mode LASER
| 7R | G.703, 1 Channel
| 7S | G.703, 2 Channels
| 7T | RS422, 1 Channel
| 7W | RS422, 2 Channels
TRANSDUCER | 5A | 4 dcmA inputs, 4 dcmA outputs (only one 5A module is allowed)
INPUTS/OUTPUTS | 5C | 8 RTD inputs
| 5D | 4 RTD inputs, 4 dcmA outputs (only one 5D module is allowed)
| 5E | 4 dcmA inputs, 4 RTD inputs
| 5F | 8 dcmA inputs

GE Multilin G60 Generator Protection System 2-9


2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION

2.2SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE

2.2.1 PROTECTION ELEMENTS

The operating times below include the activation time of a trip rated form-A output contact unless otherwise indi-
cated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
NOTE FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
2 interfacing with other IEDs or power system devices via communications or different output contacts.
PHASE DISTANCE RESTRICTED GROUND FAULT
Characteristic: mho (memory polarized or offset) or Pickup: 0.005 to 30.000 pu in steps of 0.001
quad (memory polarized or non-direc- Dropout: 97 to 98% of pickup
tional), selectable individually per zone
Slope: 0 to 100% in steps of 1%
Number of zones: 3
Pickup delay: 0 to 600.00 s in steps of 0.01
Directionality: forward, reverse, or non-directional per
Dropout delay: 0 to 600.00 s in steps of 0.01
zone
Operate time: <1 power system cycle
Reach (secondary Ω): 0.02 to 500.00 Ω in steps of 0.01
Reach accuracy: ±5% including the effect of CVT tran- PHASE/NEUTRAL/GROUND TOC
sients up to an SIR of 30 Current: Phasor or RMS
Distance: Pickup level: 0.000 to 30.000 pu in steps of 0.001
Characteristic angle: 30 to 90° in steps of 1 Dropout level: 97% to 98% of pickup
Comparator limit angle: 30 to 90° in steps of 1 Level accuracy:
Directional supervision: for 0.1 to 2.0 × CT: ±0.5% of reading or ±0.4% of rated
(whichever is greater)
Characteristic angle: 30 to 90° in steps of 1
for > 2.0 × CT: ±1.5% of reading > 2.0 × CT rating
Limit angle: 30 to 90° in steps of 1
Curve shapes: IEEE Moderately/Very/Extremely
Right blinder (Quad only):
Inverse; IEC (and BS) A/B/C and Short
Reach: 0.02 to 500 Ω in steps of 0.01 Inverse; GE IAC Inverse, Short/Very/
Characteristic angle: 60 to 90° in steps of 1 Extremely Inverse; I2t; FlexCurves™
Left Blinder (Quad only): (programmable); Definite Time (0.01 s
Reach: 0.02 to 500 Ω in steps of 0.01 base curve)
Characteristic angle: 60 to 90° in steps of 1 Curve multiplier: Time Dial = 0.00 to 600.00 in steps of
0.01
Time delay: 0.000 to 65.535 s in steps of 0.001
Reset type: Instantaneous/Timed (per IEEE)
Timing accuracy: ±3% or 4 ms, whichever is greater
Timing accuracy: Operate at > 1.03 × actual pickup
Current supervision:
±3.5% of operate time or ±½ cycle
Level: line-to-line current (whichever is greater)
Pickup: 0.050 to 30.000 pu in steps of 0.001
Dropout: 97 to 98%
PHASE/NEUTRAL/GROUND IOC
Pickup level: 0.000 to 30.000 pu in steps of 0.001
Memory duration: 5 to 25 cycles in steps of 1
Dropout level: 97 to 98% of pickup
VT location: all delta-wye and wye-delta transformers
Level accuracy:
CT location: all delta-wye and wye-delta transformers
0.1 to 2.0 × CT rating: ±0.5% of reading or ±0.4% of rated
Voltage supervision pickup (series compensation applications): (whichever is greater)
0 to 5.000 pu in steps of 0.001
> 2.0 × CT rating ±1.5% of reading
Operation time: 1 to 1.5 cycles (typical)
Overreach: <2%
Reset time: 1 power cycle (typical)
Pickup delay: 0.00 to 600.00 s in steps of 0.01
STATOR DIFFERENTIAL Reset delay: 0.00 to 600.00 s in steps of 0.01
Pickup: 0.050 to 1.00 pu in steps of 0.01 Operate time: <16 ms at 3 × pickup at 60 Hz
Slope 1 and 2: 1 to 100% in steps of 1 (Phase/Ground IOC)
Break 1: 1.00 to 1.50 pu in steps of 0.01 <20 ms at 3 × pickup at 60 Hz
Break 2: 1.50 to 30.00 pu in steps of 0.01 (Neutral IOC)
Operate time: <¾ cycle at Idiff > 5 × pickup Timing accuracy: Operate at 1.5 × pickup
±3% or ±4 ms (whichever is greater)

2-10 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS

PHASE DIRECTIONAL OVERCURRENT GENERATOR UNBALANCE


Relay connection: 90° (quadrature) Gen. nominal current: 0.000 to 1.250 pu in steps of 0.001
Quadrature voltage: ABC phase seq.: phase A (VBC), phase Stages: 2 (I2t with linear reset and definite time)
B (VCA), phase C (VAB); ACB phase Pickup level: 0.00 to 100.00% in steps of 0.01
seq.: phase A (VCB), phase B (VAC),
Dropout level: 97 to 98% of pickup
phase C (VBA)
Level accuracy:
Polarizing voltage threshold: 0.000 to 3.000 pu in steps of 0.001
0.1 to 2 x CT rating: ±0.5% of reading or 1% of rated
Current sensitivity threshold: 0.05 pu
Characteristic angle: 0 to 359° in steps of 1
> 2.0 x CT rating:
(whichever is greater)
±1.5% of reading
2
Angle accuracy: ±2°
Time dial (K-value): 0.00 to 100.00 in steps of 0.01
Operation time (FlexLogic™ operands):
Pickup delay: 0.0 to 1000.0 s in steps of 0.1
Tripping (reverse load, forward fault):<
12 ms, typically Reset delay: 0.0 to 1000.0 s in steps of 0.1
Blocking (forward load, reverse fault):< Time accuracy: ±3% or ±20 ms, whichever is greater
8 ms, typically Operate time: < 50 ms at 60 Hz
NEUTRAL DIRECTIONAL OVERCURRENT SPLIT PHASE PROTECTION
Directionality: Co-existing forward and reverse Operating quantity: split phase CT current biased by genera-
Polarizing: Voltage, Current, Dual tor load current
Polarizing voltage: V_0 or VX Pickup level: 0.020 to 1.500 pu in steps of 0.001
Polarizing current: IG Dropout level: 97 to 98% of pickup
Operating current: I_0 Level accuracy: ±0.5% of reading or ±1% of rated
Level sensing: 3 × (|I_0| – K × |I_1|), IG Pickup delay: 0.000 to 65.535 s in steps of 0.001
Restraint, K: 0.000 to 0.500 in steps of 0.001 Time accuracy: ±3% or ±5 cycles, whichever is greater
Characteristic angle: –90 to 90° in steps of 1 Operate time: < 5 cycles at 1.10 × pickup at 60 Hz
Limit angle: 40 to 90° in steps of 1, independent for SENSITIVE DIRECTIONAL POWER
forward and reverse Measured power: 3-phase, true RMS
Angle accuracy: ±2° Number of stages: 2
Offset impedance: 0.00 to 250.00 Ω in steps of 0.01 Characteristic angle: 0 to 359° in steps of 1
Pickup level: 0.002 to 30.000 pu in steps of 0.01 Calibration angle: 0.00 to 0.95° in steps of 0.05
Dropout level: 97 to 98% Minimum power: –1.200 to 1.200 pu in steps of 0.001
Operation time: < 16 ms at 3 × pickup at 60 Hz Pickup level accuracy: ±1% or ±0.001 pu, whichever is greater
NEGATIVE SEQUENCE DIRECTIONAL OC Hysteresis: 2% or 0.001 pu, whichever is greater
Directionality: Co-existing forward and reverse Pickup delay: 0 to 600.00 s in steps of 0.01
Polarizing: Voltage Time accuracy: ±3% or ±4 ms, whichever is greater
Polarizing voltage: V_2 Operate time: 50 ms
Operating current: I_2 PHASE UNDERVOLTAGE
Level sensing: Pickup level: 0.000 to 3.000 pu in steps of 0.001
Zero-sequence:|I_0| – K × |I_1|
Dropout level: 102 to 103% of pickup
Negative-sequence:|I_2| – K × |I_1|
Level accuracy: ±0.5% of reading from 10 to 208 V
Restraint, K: 0.000 to 0.500 in steps of 0.001
Curve shapes: GE IAV Inverse;
Characteristic angle: 0 to 90° in steps of 1 Definite Time (0.1s base curve)
Limit angle: 40 to 90° in steps of 1, independent for Curve multiplier: Time dial = 0.00 to 600.00 in steps of
forward and reverse
0.01
Angle accuracy: ±2°
Timing accuracy: Operate at < 0.90 × pickup
Offset impedance: 0.00 to 250.00 Ω in steps of 0.01 ±3.5% of operate time or ±4 ms (which-
Pickup level: 0.015 to 30.000 pu in steps of 0.01 ever is greater)
Dropout level: 97 to 98% AUXILIARY UNDERVOLTAGE
Operation time: < 16 ms at 3 × pickup at 60 Hz Pickup level: 0.000 to 3.000 pu in steps of 0.001
Dropout level: 102 to 103% of pickup
Level accuracy: ±0.5% of reading from 10 to 208 V
Curve shapes: GE IAV Inverse, Definite Time
Curve multiplier: Time Dial = 0 to 600.00 in steps of 0.01
Timing accuracy: ±3% of operate time or ±4 ms
(whichever is greater)

GE Multilin G60 Generator Protection System 2-11


2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION

THIRD HARMONIC NEUTRAL UNDERVOLTAGE VOLTS PER HERTZ


Operating quantity: 3rd harmonic of auxiliary undervoltage Voltage: Phasor only
Undervoltage: Pickup level: 0.80 to 4.00 in steps of 0.01 pu V/Hz
Pickup level: 0.000 to 3.000 pu in steps of 0.001 Dropout level: 97 to 98% of pickup
Dropout level: 102 to 103% of pickup Level accuracy: ±0.02 pu
Accuracy: ±2% of reading from 1 to 120 V Timing curves: Definite Time; Inverse A, B, and C,
Power: FlexCurves™ A, B, C, and D

2 Pickup level:
Dropout level:
0.000 to 1.200 pu in steps of 0.001
97 to 98% of pickup
TD Multiplier:
Reset delay:
0.05 to 600.00 s in steps of 0.01
0.0 to 1000.0 s in steps of 0.1
Accuracy: ±5% or ±0.01 pu, whichever is greater Timing accuracy: ±3% or ±15 cycles (whichever is greater)
for values greater than 1.1 × pickup
Undervoltage Inhibit
Level: 0.000 to 3.000 pu in steps of 0.001 pu 100% STATOR GROUND
V_neutral_3rd
Accuracy: ±0.5% of reading from 10 to 208 V Operating quantity: ----------------------------------------------------------------------------
V_neutral_3rd + V_zero_3rd
Pickup delay: 0 to 600.00 s in steps of 0.01 Pickup level: 0.000 to 0.900 pu in steps of 0.001
Time accuracy: ±3% or ±20 ms, whichever is greater Dropout level: 97 to 98% of pickup
Operate time: < 30 ms at 1.10 × pickup at 60 Hz Level accuracy: ±2% of reading from 1 to 120 V
Pickup delay: 0 to 600.00 s in steps of 0.01
PHASE OVERVOLTAGE
Voltage: Phasor only 3rd harmonic supervision level: 0.0010 to 0.1000 pu in steps of
0.0001
Pickup level: 0.000 to 3.000 pu in steps of 0.001
Time accuracy: ±3% or ±20 ms, whichever is greater
Dropout level: 97 to 98% of pickup
Operate time: < 30 ms at 1.10 × pickup at 60 Hz
Level accuracy: ±0.5% of reading from 10 to 208 V
Pickup delay: 0.00 to 600.00 in steps of 0.01 s SUB-HARMONIC STATOR GROUND
Stator ground resistance pickup accuracy: ±5% of reading from 1
Operate time: < 30 ms at 1.10 × pickup at 60 Hz
to 10 kΩ, ±10% of reading from 10 to 20
Timing accuracy: ±3% or ±4 ms (whichever is greater) kΩ
NEUTRAL OVERVOLTAGE Total stator capacitance to ground: 200 nF to 2 μF
Pickup level: 0.000 to 3.000 pu in steps of 0.001 Sub-harmonic voltage metering accuracy: ±2% of reading or 0.2 V
Dropout level: 97 to 98% of pickup from 0.5 to 25 V AC
Level accuracy: ±0.5% of reading from 10 to 208 V Sub-harmonic current metering accuracy: ±2% of reading or 5 mA
Pickup delay: 0.00 to 600.00 s in steps of 0.01 (definite from 5 to 200 mA
time) or user-defined curve Sub-harmonic element operating time: 0.6 to 1.2 s
Reset delay: 0.00 to 600.00 s in steps of 0.01 Sub-harmonic element dropout level accuracy: 102 to 103% of
Timing accuracy: ±3% or ±20 ms (whichever is greater) pickup
Operate time: < 30 ms at 1.10 × pickup at 60 Hz Time delay accuracy: ±3% of time delay setting or ± 4 ms,
whichever is greater
AUXILIARY OVERVOLTAGE
Pickup level: 0.000 to 3.000 pu in steps of 0.001 FIELD GROUND
Measured field ground resistance: 1 kΩ to 20 MΩ
Dropout level: 97 to 98% of pickup
Ground resistance accuracy:±5% of reading ±250 Ω from 1 to 500
Level accuracy: ±0.5% of reading from 10 to 208 V
kΩ
Pickup delay: 0 to 600.00 s in steps of 0.01
Field winding capacitance: 1 to 10 μF
Reset delay: 0 to 600.00 s in steps of 0.01
Maximum field voltage: 600 V DC rated field voltage / 1000 V
Timing accuracy: ±3% of operate time or ±4 ms
ripple peak for single box option; 800
(whichever is greater) V DC rated field voltage / 2000 V ripple
Operate time: < 30 ms at 1.10 × pickup at 60 Hz peak for external resistor box option
Operate time when 20 Hz injection is performed: 8 power system Field voltage measurement range: 15 to 800 V
cycles
Field voltage measurement accuracy: ±1 V or ±3% of reading (for
NEGATIVE SEQUENCE OVERVOLTAGE GPM-F-L); ±1 V or ±5% of reading (for
Pickup level: 0.000 to 1.250 pu in steps of 0.001 GPM-F-H)
Dropout level: 97 to 98% of pickup Field ground RMS current accuracy: ±5% of reading
Level accuracy: ±0.5% of reading from 10 to 208 V Fault location accuracy: ±5% of reading
Pickup delay: 0 to 600.00 s in steps of 0.01 Field ground resistance typical operating time: 1.1 s + (1 / injection
frequency)
Reset delay: 0 to 600.00 s in steps of 0.01
Field ground element dropout level accuracy: 102 to 103% of
Time accuracy: ±3% or ±20 ms, whichever is greater
pickup
Operate time: < 30 ms at 1.10 × pickup at 60 Hz
Time delay accuracy: ±3% of time delay setting or ±4ms,
whichever is greater

2-12 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS

FIELD CURRENT TURBINE FREQUENCY OUT-OF-BAND (OOB)


Field current measurement (dcmA) accuracy: ±0.2% of full scale ACCUMULATED OPERATING TIME
Field overcurrent and undercurrent operating time: 1 power sys- Frequency OOB accumulation: 7 sets; 20 to 70 Hz in steps of 0.01
tem cycle Frequency OOB accumulation pickup: 1 to 65536 s in steps of 1
Field current element dropout level accuracy: 102 to 103% of Frequency OOB accumulator preset: 1 to 65536 s in steps of 1
pickup for undercurrent and 97 to 98% of Level accuracy: ±0.01 Hz
pickup for overcurrent
Minimum volt/amp supervision: 0.1 to 1.25 pu of V_1 or I_1
Time delay accuracy: ±3% of time delay setting or ±4 ms which-
ever is greater
Timing accuracy of accumulation: ±1% or 1 second, whichever is
greater
2
UNDERFREQUENCY
SYNCHROCHECK
Minimum signal: 0.10 to 1.25 pu in steps of 0.01
Max voltage difference: 0 to 400000 V in steps of 1
Pickup level: 20.00 to 65.00 Hz in steps of 0.01
Max angle difference: 0 to 100° in steps of 1
Dropout level: pickup + 0.03 Hz
Max freq. difference: 0.00 to 2.00 Hz in steps of 0.01
Level accuracy: ±0.001 Hz
Hysteresis for max. freq. diff.: 0.00 to 0.10 Hz in steps of 0.01
Time delay: 0 to 65.535 s in steps of 0.001
Dead source function: None, LV1 & DV2, DV1 & LV2, DV1 or
Timer accuracy: ±3% or 4 ms, whichever is greater DV2, DV1 xor DV2, DV1 & DV2
Operate time: typically 4 cycles at 0.1 Hz/s change (L = Live, D = Dead)
typically 3.5 cycles at 0.3 Hz/s change
typically 3 cycles at 0.5 Hz/s change POWER SWING DETECT
Functions: Power swing block, Out-of-step trip
Typical times are average operate times including variables such
as frequency change instance, test method, etc., and may vary by Characteristic: Mho or Quad
±0.5 cycles. Measured impedance: Positive-sequence
Blocking / tripping modes: 2-step or 3-step
OVERFREQUENCY
Pickup level: 20.00 to 65.00 Hz in steps of 0.01 Tripping mode: Early or Delayed
Dropout level: pickup – 0.03 Hz Current supervision:
Level accuracy: ±0.001 Hz Pickup level: 0.050 to 30.000 pu in steps of 0.001
Time delay: 0 to 65.535 s in steps of 0.001 Dropout level: 97 to 98% of pickup
Timer accuracy: ±3% or 4 ms, whichever is greater Fwd / reverse reach (sec. Ω): 0.10 to 500.00 Ω in steps of 0.01
Operate time: typically 4 cycles at 0.1 Hz/s change Left and right blinders (sec. Ω): 0.10 to 500.00 Ω in steps of 0.01
typically 3.5 cycles at 0.3 Hz/s change Impedance accuracy: ±5%
typically 3 cycles at 0.5 Hz/s change Fwd / reverse angle impedances: 40 to 90° in steps of 1
Typical times are average operate times including variables such Angle accuracy: ±2°
as frequency change instance, test method, etc., and may vary by Characteristic limit angles: 40 to 140° in steps of 1
±0.5 cycles.
Timers: 0.000 to 65.535 s in steps of 0.001
RATE OF CHANGE OF FREQUENCY Timing accuracy: ±3% or 4 ms, whichever is greater
df/dt trend: increasing, decreasing, bi-directional
ACCIDENTAL ENERGIZATION
df/dt pickup level: 0.10 to 15.00 Hz/s in steps of 0.01
Operating condition: Overcurrent
df/dt dropout level: 96% of pickup
Arming condition: Undervoltage and/or Machine Offline
df/dt level accuracy: 80 mHz/s or 3.5%, whichever is greater
Overcurrent:
Overvoltage supv.: 0.100 to 3.000 pu in steps of 0.001
Pickup level: 0.000 to 3.000 pu in steps of 0.001
Overcurrent supv.: 0.000 to 30.000 pu in steps of 0.001
Dropout level: 97 to 98% of pickup
Pickup delay: 0 to 65.535 s in steps of 0.001
Level accuracy: ±0.5% of reading from
Reset delay: 0 to 65.535 s in steps of 0.001 0.1 to 2.0 × CT rating
Time accuracy: ±3% or ±4 ms, whichever is greater Undervoltage:
95% settling time for df/dt: < 24 cycles Pickup level: 0.000 to 3.000 pu in steps of 0.001
Operate time: typically 6.5 cycles at 2 × pickup Dropout level: 102 to 103% of pickup
typically 5.5 cycles at 3 × pickup
Level accuracy: ±0.5% of reading 10 to 208 V
typically 4.5 cycles at 5 × pickup
Operate Time: < 30 ms at 1.10 × pickup at 60 Hz

GE Multilin G60 Generator Protection System 2-13


2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION

LOSS OF EXCITATION RTD PROTECTION


Operating condition: Positive-sequence impedance Pickup: 1 to 249°C in steps of 1
Characteristic: 2 independent offset mho circles Dropout level: 2°C of pickup
Center: 0.10 to 300.0 Ω (sec.) in steps of 0.01 Timing accuracy: <1 s
Radius: 0.10 to 300.0 Ω (sec.) in steps of 0.01 Elements: trip and alarm
Reach accuracy: ±3% REMOTE RTD PROTECTION
Undervoltage supervision Pickup level: 1 to 200°C
2 Level:
Accuracy:
0.000 to 1.250 pu in steps of 0.001
±0.5% of reading from 10 to 208 V
Dropout level: 2°C of pickup
Time delay: <10 s
Pickup delay: 0 to 65.535 s in steps of 0.001 Elements: trip and alarm
Timing accuracy: ±3% or ±20 ms, whichever is greater
TRIP BUS (TRIP WITHOUT FLEXLOGIC™)
Operate time: <50 ms
Number of elements: 6
THERMAL OVERLOAD PROTECTION Number of inputs: 16
Thermal overload curves: IEC 255-8 curve Operate time: <2 ms at 60 Hz
Base current: 0.20 to 3.00 pu in steps of 0.01 Time accuracy: ±3% or 10 ms, whichever is greater
Overload (k) factor: 1.00 to 1.20 pu in steps of 0.05
Trip time constant: 0 to 1000 min. in steps of 1
Reset time constant: 0 to 1000 min. in steps of 1
Minimum reset time: 0 to 1000 min. in steps of 1
Timing accuracy (cold curve): ±100 ms or 2%, whichever is
greater
Timing accuracy (hot curve): ±500 ms or 2%, whichever is greater
for Ip < 0.9 × k × Ib and I / (k × Ib) > 1.1

2.2.2 USER-PROGRAMMABLE ELEMENTS

FLEXLOGIC™ FLEXELEMENTS™
Programming language: Reverse Polish Notation with graphical Number of elements: 16
visualization (keypad programmable) Operating signal: any analog actual value, or two values in
Lines of code: 512 differential mode
Internal variables: 64 Operating signal mode: signed or absolute value
Supported operations: NOT, XOR, OR (2 to 16 inputs), AND (2 Operating mode: level, delta
to 16 inputs), NOR (2 to 16 inputs), Comparator direction: over, under
NAND (2 to 16 inputs), latch (reset-domi- Pickup Level: –90.000 to 90.000 pu in steps of 0.001
nant), edge detectors, timers
Hysteresis: 0.1 to 50.0% in steps of 0.1
Inputs: any logical variable, contact, or virtual
Delta dt: 20 ms to 60 days
input
Pickup & dropout delay: 0.000 to 65.535 s in steps of 0.001
Number of timers: 32
Pickup delay: 0 to 60000 (ms, sec., min.) in steps of 1 NON-VOLATILE LATCHES
Dropout delay: 0 to 60000 (ms, sec., min.) in steps of 1 Type: set-dominant or reset-dominant
Number: 16 (individually programmed)
FLEXCURVES™
Number: 4 (A through D) Output: stored in non-volatile memory
Reset points: 40 (0 through 1 of pickup) Execution sequence: as input prior to protection, control, and
FlexLogic™
Operate points: 80 (1 through 20 of pickup)
Time delay: 0 to 65535 ms in steps of 1 USER-PROGRAMMABLE LEDs
Number: 48 plus trip and alarm
FLEX STATES Programmability: from any logical variable, contact, or vir-
Number: up to 256 logical variables grouped tual input
under 16 Modbus addresses
Reset mode: self-reset or latched
Programmability: any logical variable, contact, or virtual
input

2-14 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS

LED TEST USER-PROGRAMMABLE PUSHBUTTONS (OPTIONAL)


Initiation: from any digital input or user-program- Number of pushbuttons: 12 (standard faceplate);
mable condition 16 (enhanced faceplate)
Number of tests: 3, interruptible at any time Mode: self-reset, latched
Duration of full test: approximately 3 minutes Display message: 2 lines of 20 characters each
Test sequence 1: all LEDs on Drop-out timer: 0.00 to 60.00 s in steps of 0.05
Test sequence 2: all LEDs off, one LED at a time on for 1 s Autoreset timer: 0.2 to 600.0 s in steps of 0.1
Test sequence 3: all LEDs on, one LED at a time off for 1 s Hold timer: 0.0 to 10.0 s in steps of 0.1
2
USER-DEFINABLE DISPLAYS SELECTOR SWITCH
Number of displays: 16 Number of elements: 2
Lines of display: 2 × 20 alphanumeric characters Upper position limit: 1 to 7 in steps of 1
Parameters: up to 5, any Modbus register addresses Selecting mode: time-out or acknowledge
Invoking and scrolling: keypad, or any user-programmable con- Time-out timer: 3.0 to 60.0 s in steps of 0.1
dition, including pushbuttons Control inputs: step-up and 3-bit
CONTROL PUSHBUTTONS Power-up mode: restore from non-volatile memory or syn-
Number of pushbuttons: 7 chronize to a 3-bit control input or synch/
restore mode
Operation: drive FlexLogic™ operands
DIGITAL ELEMENTS
Number of elements: 48
Operating signal: any FlexLogic™ operand
Pickup delay: 0.000 to 999999.999 s in steps of 0.001
Dropout delay: 0.000 to 999999.999 s in steps of 0.001
Timing accuracy: ±3% or ±4 ms, whichever is greater

2.2.3 MONITORING

OSCILLOGRAPHY USER-PROGRAMMABLE FAULT REPORT


Maximum records: 64 Number of elements: 2
Sampling rate: 64 samples per power cycle Pre-fault trigger: any FlexLogic™ operand
Triggers: any element pickup, dropout, or operate; Fault trigger: any FlexLogic™ operand
digital input change of state; digital out- Recorder quantities: 32 (any FlexAnalog value)
put change of state; FlexLogic™ equa-
tion DATA LOGGER
Number of channels: 1 to 16
Data: AC input channels; element state; digital
input state; digital output state Parameters: any available analog actual value
Data storage: in non-volatile memory Sampling rate: 15 to 3600000 ms in steps of 1
Trigger: any FlexLogic™ operand
EVENT RECORDER
Mode: continuous or triggered
Capacity: 1024 events
Storage capacity: (NN is dependent on memory)
Time-tag: to 1 microsecond
1-second rate:
Triggers: any element pickup, dropout, or operate;
digital input change of state; digital out- 01 channel for NN days
16 channels for NN days
put change of state; self-test events

Data storage: in non-volatile memory
60-minute rate:
01 channel for NN days
16 channels for NN days

GE Multilin G60 Generator Protection System 2-15


2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION

PHASOR MEASUREMENT UNIT


Output format: per IEEE C37.118 standard
Number of channels: 14 synchrophasors, 8 analogs, 16 digi-
tals
TVE (total vector error) <1%
Triggering: frequency, voltage, current, power, rate
of change of frequency, user-defined

2 Reporting rate: 1, 2, 5, 10, 12, 15, 20, 25, 30, 50, or 60


times per second
Number of clients: One over TCP/IP port, two over UDP/IP
ports
AC ranges: As indicated in appropriate specifications
sections
Network reporting format: 16-bit integer or 32-bit IEEE floating
point numbers
Network reporting style: rectangular (real and imaginary) or polar
(magnitude and angle) coordinates
Post-filtering: none, 3-point, 5-point, 7-point
Calibration: ±5°

2.2.4 METERING

RMS CURRENT: PHASE, NEUTRAL, AND GROUND CURRENT HARMONICS


Accuracy at Harmonics: 2nd to 25th harmonic: per phase, dis-
0.1 to 2.0 × CT rating: ±0.25% of reading or ±0.1% of rated played as a % of f1 (fundamental fre-
(whichever is greater) quency phasor)
> 2.0 × CT rating: ±1.0% of reading THD: per phase, displayed as a % of f1
RMS VOLTAGE Accuracy:
HARMONICS: 1. f1 > 0.4pu: (0.20% + 0.035% / harmonic) of
Accuracy: ±0.5% of reading from 10 to 208 V
reading or 0.15% of 100%, whichever is
REAL POWER (WATTS) greater
Accuracy: ±1.0% of reading at 2. f1 < 0.4pu: as above plus %error of f1
–0.8 < PF ≤ –1.0 and 0.8 < PF ≤ 1.0 THD: 1. f1 > 0.4pu: (0.25% + 0.035% / harmonic) of
reading or 0.20% of 100%, whichever is
REACTIVE POWER (VARS) greater
Accuracy: ±1.0% of reading at –0.2 ≤ PF ≤ 0.2
2. f1 < 0.4pu: as above plus %error of f1
APPARENT POWER (VA) VOLTAGE HARMONICS
Accuracy: ±1.0% of reading Harmonics: 2nd to 25th harmonic: per phase, dis-
WATT-HOURS (POSITIVE AND NEGATIVE) played as a % of f1 (fundamental fre-
Accuracy: ±2.0% of reading quency phasor)
THD: per phase, displayed as a % of f1
Range: ±0 to 1 × 106 MWh
Accuracy:
Parameters: three-phase only
HARMONICS: 1. f1 > 0.4pu: (0.20% + 0.035% / harmonic) of
Update rate: 50 ms
reading or 0.15% of 100%, whichever is
VAR-HOURS (POSITIVE AND NEGATIVE) greater
Accuracy: ±2.0% of reading 2. f1 < 0.4pu: as above plus %error of f1
Range: ±0 to 1 × 106 Mvarh THD: 1. f1 > 0.4pu: (0.25% + 0.035% / harmonic) of
reading or 0.20% of 100%, whichever is
Parameters: three-phase only
greater
Update rate: 50 ms 2. f1 < 0.4pu: as above plus %error of f1
FREQUENCY
Accuracy at
V = 0.8 to 1.2 pu: ±0.001 Hz (when voltage signal is used
for frequency measurement)
I = 0.1 to 0.25 pu: ±0.05 Hz
I > 0.25 pu: ±0.001 Hz (when current signal is used
for frequency measurement)

2-16 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS

2.2.5 INPUTS

AC CURRENT DCMA INPUTS


CT rated primary: 1 to 50000 A Current input (mA DC): 0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10,
CT rated secondary: 1 A or 5 A by connection 0 to 20, 4 to 20 (programmable)
Nominal frequency: 20 to 65 Hz Input impedance: 379 Ω ±10%
Relay burden: < 0.2 VA at rated secondary Conversion range: –1 to + 20 mA DC
Conversion range:
Standard CT: 0.02 to 46 × CT rating RMS symmetrical
Accuracy:
Type:
±0.2% of full scale
Passive
2
Sensitive Ground CT module:
0.002 to 4.6 × CT rating RMS symmetrical
RTD INPUTS
Types (3-wire): 100 Ω Platinum, 100 & 120 Ω Nickel, 10
Current withstand: 20 ms at 250 times rated
Ω Copper
1 sec. at 100 times rated
Sensing current: 5 mA
continuous at 3 times rated
Range: –50 to +250°C
Short circuit rating: 150000 RMS symmetrical amperes, 250
V maximum (primary current to external Accuracy: ±2°C
CT) Isolation: 36 V pk-pk
AC VOLTAGE REMOTE RTD INPUTS
VT rated secondary: 50.0 to 240.0 V Wire type: three-wire
VT ratio: 1.00 to 24000.00 Sensor type: 100 Ω platinum (DIN 43760), 100 Ω
Nominal frequency: 20 to 65 Hz nickel, 120 Ω nickel, 10 Ω copper
Relay burden: < 0.25 VA at 120 V RTD sensing current: 3 mA
Conversion range: 1 to 275 V Range: –40 to 200°C
Voltage withstand: continuous at 260 V to neutral Accuracy: ±2°C
1 min./hr at 420 V to neutral Lead resistance: 25 Ω maximum for Pt and Ni type; 3 Ω
max. for Cu type
CONTACT INPUTS
Isolation: 36 Vpk
Dry contacts: 1000 Ω maximum
Wet contacts: 300 V DC maximum IRIG-B INPUT
Selectable thresholds: 17 V, 33 V, 84 V, 166 V Amplitude modulation: 1 to 10 V pk-pk
Tolerance: ±10% DC shift: TTL
Contacts per common return: 4 Input impedance: 22 kΩ
Recognition time: < 1 ms Isolation: 2 kV
Debounce time: 0.0 to 16.0 ms in steps of 0.5 REMOTE INPUTS (IEC 61850 GSSE/GOOSE)
Continuous current draw:3 mA (when energized) Number of input points: 32, configured from 64 incoming bit pairs
CONTACT INPUTS WITH AUTO-BURNISHING Number of remote devices: 16
Dry contacts: 1000 Ω maximum Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Wet contacts: 300 V DC maximum Number of remote DPS inputs: 5
Selectable thresholds: 17 V, 33 V, 84 V, 166 V DIRECT INPUTS
Tolerance: ±10% Number of input points: 32
Contacts per common return: 2 No. of remote devices: 16
Recognition time: < 1 ms Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Debounce time: 0.0 to 16.0 ms in steps of 0.5 Ring configuration: Yes, No
Continuous current draw:3 mA (when energized) Data rate: 64 or 128 kbps
Auto-burnish impulse current: 50 to 70 mA CRC: 32-bit
Duration of auto-burnish impulse: 25 to 50 ms CRC alarm:
Responding to: Rate of messages failing the CRC
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold: 1 to 1000 in steps of 1
Unreturned message alarm:
Responding to: Rate of unreturned messages in the ring
configuration
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold: 1 to 1000 in steps of 1

GE Multilin G60 Generator Protection System 2-17


2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION

TELEPROTECTION
Number of input points: 16
No. of remote devices: 3
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration: No
Data rate: 64 or 128 kbps
CRC: 32-bit
2 2.2.6 POWER SUPPLY

LOW RANGE ALL RANGES


Nominal DC voltage: 24 to 48 V Volt withstand: 2 × Highest Nominal Voltage for 10 ms
Minimum DC voltage: 20 V Power consumption: typical = 15 to 20 W/VA
Maximum DC voltage: 60 V maximum = 50 W/VA
contact factory for exact order code con-
Voltage loss hold-up: 20 ms duration at nominal
sumption
NOTE: Low range is DC only.
INTERNAL FUSE
HIGH RANGE
RATINGS
Nominal DC voltage: 125 to 250 V
Low range power supply: 8 A / 250 V
Minimum DC voltage: 88 V High range power supply: 4 A / 250 V
Maximum DC voltage: 300 V INTERRUPTING CAPACITY
Nominal AC voltage: 100 to 240 V at 50/60 Hz AC: 100 000 A RMS symmetrical
Minimum AC voltage: 88 V at 25 to 100 Hz DC: 10 000 A
Maximum AC voltage: 265 V at 25 to 100 Hz
Voltage loss hold-up: 200 ms duration at nominal

2-18 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS

2.2.7 OUTPUTS

FORM-A RELAY SOLID-STATE OUTPUT RELAY


Operate and release time: <100 μs
Make and carry for 0.2 s: 30 A as per ANSI C37.90
Maximum voltage: 265 V DC
Carry continuous: 6A
Maximum continuous current: 5 A at 45°C; 4 A at 65°C
Break (DC inductive, L/R = 40 ms):
Make and carry:
VOLTAGE CURRENT
24 V 1A
for 0.2 s:
for 0.03 s
30 A as per ANSI C37.90
300 A
2
48 V 0.5 A Breaking capacity:
125 V 0.3 A
UL508 Utility Industrial
250 V 0.2 A application application
(autoreclose
Operate time: < 4 ms scheme)
Contact material: silver alloy Operations/ 5000 ops / 5 ops /
interval 1 s-On, 9 s-Off 0.2 s-On, 10000 ops /
LATCHING RELAY 0.2 s-Off 0.2 s-On,
Make and carry for 0.2 s: 30 A as per ANSI C37.90 1000 ops / within 1 30 s-Off
0.5 s-On, 0.5 s-Off minute
Carry continuous: 6A
Break 3.2 A
Break at L/R of 40 ms: 0.25 A DC max. capability L/R = 10 ms
Operate time: < 4 ms (0 to 250 V
DC) 1.6 A 10 A 10 A
Contact material: silver alloy L/R = 20 ms L/R = 40 ms L/R = 40 ms
Control: separate operate and reset inputs 0.8 A
L/R = 40 ms
Control mode: operate-dominant or reset-dominant
FORM-A VOLTAGE MONITOR IRIG-B OUTPUT
Applicable voltage: approx. 15 to 250 V DC Amplitude: 10 V peak-peak RS485 level
Trickle current: approx. 1 to 2.5 mA Maximum load: 100 ohms
Time delay: 1 ms for AM input
FORM-A CURRENT MONITOR 40 μs for DC-shift input
Threshold current: approx. 80 to 100 mA
Isolation: 2 kV
FORM-C AND CRITICAL FAILURE RELAY CONTROL POWER EXTERNAL OUTPUT
Make and carry for 0.2 s: 30 A as per ANSI C37.90
(FOR DRY CONTACT INPUT)
Carry continuous: 8A Capacity: 100 mA DC at 48 V DC
Break (DC inductive, L/R = 40 ms): Isolation: ±300 Vpk
VOLTAGE CURRENT
REMOTE OUTPUTS (IEC 61850 GSSE/GOOSE)
24 V 1A
Standard output points: 32
48 V 0.5 A
User output points: 32
125 V 0.3 A
250 V 0.2 A
DIRECT OUTPUTS
Output points: 32
Operate time: < 8 ms
Contact material: silver alloy DCMA OUTPUTS
Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
FAST FORM-C RELAY Max. load resistance: 12 kΩ for –1 to 1 mA range
Make and carry: 0.1 A max. (resistive load) 12 kΩ for 0 to 1 mA range
Minimum load impedance: 600 Ω for 4 to 20 mA range
INPUT IMPEDANCE Accuracy: ±0.75% of full-scale for 0 to 1 mA range
VOLTAGE ±0.5% of full-scale for –1 to 1 mA range
2 W RESISTOR 1 W RESISTOR
±0.75% of full-scale for 0 to 20 mA range
250 V DC 20 KΩ 50 KΩ
99% Settling time to a step change: 100 ms
120 V DC 5 KΩ 2 KΩ
Isolation: 1.5 kV
48 V DC 2 KΩ 2 KΩ
Driving signal: any FlexAnalog quantity
24 V DC 2 KΩ 2 KΩ
Upper and lower limit for the driving signal: –90 to 90 pu in steps of
Note: values for 24 V and 48 V are the same due to a 0.001
required 95% voltage drop across the load impedance.
Operate time: < 0.6 ms
Internal Limiting Resistor: 100 Ω, 2 W

GE Multilin G60 Generator Protection System 2-19


2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION

ETHERNET SWITCH (HIGH VOLTAGE, TYPE 2S) ETHERNET SWITCH (LOW VOLTAGE, TYPE 2T)
Nominal DC voltage: 110 to 240 V DC Nominal voltage: 48 V DC, 0.31 A/15 W
Minimum DC voltage: 88 V DC Minimum voltage: 30 V DC, 0.43 A/16 W
Maximum DC voltage: 300 V DC Maximum voltage: 60 V DC
Input Current: 0.9 A DC maximum Internal fuse: 5 A / 350 V AC, Ceramic, Axial SLO
Nominal AC voltage: 100 to 240 V AC, 0.26 to 0.16 A/26 to 39 BLO;
VA at 50/60 Hz Manufacturer: Conquer; Part number:
SCD-A 005
2 Minimum AC voltage:
Maximum AC voltage:
85 V AC, 0.31 A/22 VA at 50/60 Hz
265 V AC, 0.16 A/42 VA at 50/60 Hz
Internal fuse: 3 A / 350 V AC, Ceramic, Axial SLO
BLO;
Manufacturer: Conquer; Part number:
SCD-A 003

2.2.8 FIELD AND STATOR GROUND MODULES

GPM-F MODULE CONTACT INPUTS GPM-S-G MODULE


Internal wetting: 24 V DC Power supply: 100 to 240 V AC at 50/60 Hz and 110VA
Input comparator threshold: 6 V DC 125 to 250 V DC at 110W
External contact: dry Output ratings: 26 V rectangular at 20 Hz, load capabil-
Current when energized: < 10 mA ity 80 VA
Debounce time: 10 ms GPM-S-B MODULE
Power rating: 80VA
GPM-F MODULE CRITICAL FAILURE RELAY
Input ratings: maximum 30 V rectangular at 20 Hz
Make and carry: 30 A for 0.2 s as per ANSI C37.90
Continuous carry: 8A GPM-F-R MODULE
Break (DC inductive, L/R = 40 ms): 1 A at 24 V, 0.5 A at 48 V, Current limiting resistor: 12.5 Ω × 4
0.3 A at 125 V, 0.2 A at 250 V Voltage divider resistor: 5 Ω × 3
Operate time: < 8 ms STATOR GROUND PROTECTION CT
Contact material: silver alloy Part number: 204-SD-43737
GPM-F MODULE POWER SUPPLY Turns ratio: 400:5A
GPM-F-L: 100 to 240V AC at 50/60Hz and 10 VA Rating factor (RF): 3.0
125 to 250V DC at 10W Frequency: 20 Hz
GPM-F-HM: 100 to 240V AC at 50/60Hz and 10 VA Voltage insulation: 600 V
125 to 250V DC at 10W
Basic impulse level (BIL): 10 kV

2-20 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS

GPM-F-HM, GPM-F-L, GPM-F-R, GPM-S-B, AND GPM-S-G MODULE TYPE TESTS


TEST REFERENCE STANDARD TEST LEVEL
GPM-F TYPES GPM-S TYPES
Dielectric voltage withstand EN60255-5 2.3 kV AC / 4.6 kV DC 2.3 kV AC / 3.3 kV DC
Impulse voltage withstand EN60255-5 5 kV 5 kV
Insulation EN60255-5 500 V DC 500 V DC
Damped oscillatory IEC61000-4-18IEC60255-22-1 2.5 kV CM, 1 kV DM 2.5 kV CM, 1 kV DM 2
Electrostatic discharge EN61000-4-2/IEC60255-22-2 Level 4 Level 4
RF immunity EN61000-4-3/IEC60255-22-3 20 V/m 20 V/m
Fast Transient Disturbance EN61000-4-4/IEC60255-22-4 Class A and B Class A and B
Surge Immunity EN61000-4-5/IEC60255-22-5 Level 4 Level 4
Conducted RF Immunity EN61000-4-6/IEC60255-22-6 Level 3 Level 3
Voltage interruption and ripple DC IEC60255-11 15% ripple, 15% ripple,
1 ms to 5 s interrupts 1 ms to 5 s interrupts
Radiated and conducted emissions CISPR11 / CISPR22 / IEC60255-25 Class A Class A
Sinusoidal vibration IEC60255-21-1 Class 2 Class 1
Shock and Bump IEC60255-21-2 Class 2 Class 1
Seismic IEC60255-21-3 Class 2 Class 1
Power magnetic immunity IEC61000-4-8 Level 5 Level 5
Pulse magnetic immunity IEC61000-4-9 Level 4 Level 4
Damped magnetic immunity IEC61000-4-10 Level 4 Level 4
Voltage dip and interruption IEC61000-4-11 0%, 40%, 70%, 80% dips; 0%, 40%, 70%, 80% dips;
250/300 cycle interrupts 250/300 cycle interrupts
Voltage ripple IEC61000-4-17 15% ripple 15% ripple
Ingress protection IEC60529 IP10 IP10
Environmental (cold) IEC60068-2-1 –40°C, 16 hrs –40°C, 16 hrs
Environmental (dry heat) IEC60068-2-2 85°C, 16hrs 85°C, 16hrs
Relative humidity cyclic IEC60068-2-30 6 day, variant 1 6 day, variant 1
SWC oscillatory IEEE/ANSI C37.90.1 2.5 kV,1 MHz 2.5 kV,1 MHz
SWC transients IEEE/ANSI C37.90.1 4 kV 2.5 kHz 4 kV 2.5 kHz
RF immunity IEEE/ANSIC37.90.2 20 V/m 20 V/m
ESD IEEE/ANSIC37.90.3 15 kV air / 8 kV contact 15 kV air / 8 kV contact
Safety UL508 e83849 NKCR2 e83849 NKCR2
UL C22.2-14 e83849 NKCR8 e83849 NKCR8

GE Multilin G60 Generator Protection System 2-21


2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION

2.2.9 COMMUNICATIONS

RS232 ETHERNET SWITCH FIBER OPTIC PORTS


Front port: 19.2 kbps, Modbus® RTU Maximum fiber segment length calculation:
RS485 The maximum fiber segment length between two adjacent
® switches or between a switch and a device is calculated as fol-
1 or 2 rear ports: Up to 115 kbps, Modbus RTU, isolated
together at 36 Vpk lows. First, calculate the optical power budget (OPB) of each

2 Typical distance: 1200 m


device using the manufacturer’s data sheets.
OPB = P T ( MIN ) – P R ( MIN )
Isolation: 2 kV
where OPB = optical power budget, PT = transmitter output power,
ETHERNET (FIBER) and PR = receiver sensitivity.
PARAMETER FIBER TYPE The worst case optical power budget (OPBWORST) is then calcu-
10MB MULTI- 100MB MULTI- 100MB SINGLE- lated by taking the lower of the two calculated power budgets, sub-
MODE MODE MODE tracting 1 dB for LED aging, and then subtracting the total insertion
Wavelength 820 nm 1310 nm 1310 nm loss. The total insertion loss is calculated by multiplying the num-
ber of connectors in each single fiber path by 0.5 dB. For example,
Connector ST ST SC
with a single fiber cable between the two devices, there will be a
Transmit power –20 dBm –20 dBm –15 dBm
minimum of two connections in either transmit or receive fiber
Receiver sensitivity –30 dBm –30 dBm –30 dBm paths for a total insertion loss of 1db for either direction:
Power budget 10 dB 10 dB 15 dB Total insertion loss = number of connectors × 0.5 dB
Maximum input –7.6 dBm –14 dBm –7 dBm = 2 × 0.5 dB = 1.0 dB
power
The worst-case optical power budget between two type 2T or 2S
Typical distance 1.65 km 2 km 15 km
modules using a single fiber cable is:
Duplex full/half full/half full/half
OPB WORST = OPB – 1 dB (LED aging) – total insertion loss
Redundancy yes yes yes
10dB – 1dB – 1dB = 8dB
The UR-2S and UR-2T only support 100 Mb multimode To calculate the maximum fiber length, divide the worst-case opti-
ETHERNET (10/100 MB TWISTED PAIR) cal power budget by the cable attenuation per unit distance speci-
Modes: 10 MB, 10/100 MB (auto-detect) fied in the manufacturer data sheets. For example, typical
attenuation for 62.5/125 μm glass fiber optic cable is approxi-
Connector: RJ45
mately 2.8 dB per km. In our example, this would result in the fol-
SNTP clock synchronization error: <10 ms (typical) lowing maximum fiber length:
OPB WORST (in dB)
Maximum fiber length = ------------------------------------------------------
-
cable loss (in dB/km)
8 dB
= --------------------------- = 2.8km
2.8 dB/km
The customer must use the attenuation specified within the manu-
facturer data sheets for accurate calculation of the maximum fiber
length.
ETHERNET SWITCH 10/100BASE-T PORTS
Connector type: RJ45
MAXIMUM 10 MBPS ETHERNET SEGMENT LENGTHS
Unshielded twisted pair: 100 m (328 ft.)
Shielded twisted pair: 150 m (492 ft.)
MAXIMUM STANDARD FAST ETHERNET SEGMENT LENGTHS
10Base-T (CAT 3, 4, 5 UTP): 100 m (328 ft.)
100Base-TX (CAT 5 UTP):100 m (328 ft.)
Shielded twisted pair: 150 m (492 ft.)

2-22 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS

2.2.10 INTER-RELAY COMMUNICATIONS

SHIELDED TWISTED-PAIR INTERFACE OPTIONS TYPICAL LINK DISTANCE


INTERFACE TYPE TYPICAL DISTANCE EMITTER TYPE CABLE CONNECTOR TYPICAL
TYPE TYPE DISTANCE
RS422 1200 m
820 nm LED, 62.5/125 μm ST 1.65 km
G.703 100 m multimode
RS422 distance is based on transmitter power 1300 nm LED,
multimode
62.5/125 μm ST 3.8 km 2
NOTE and does not take into consideration the clock
source provided by the user. 1300 nm ELED, 9/125 μm ST 11.4 km
single mode
LINK POWER BUDGET 1300 nm Laser, 9/125 μm ST 64 km
single mode
EMITTER, TRANSMIT RECEIVED POWER
FIBER TYPE POWER SENSITIVITY BUDGET 1550 nm Laser, 9/125 μm ST 105 km
single-mode
820 nm LED, –20 dBm –30 dBm 10 dB
Multimode
1300 nm LED, –21 dBm –30 dBm 9 dB Typical distances listed are based on the fol-
Multimode lowing assumptions for system loss. As
NOTE actual losses will vary from one installation to
1300 nm ELED, –23 dBm –32 dBm 9 dB
Singlemode another, the distance covered by your system
1300 nm Laser, –1 dBm –30 dBm 29 dB may vary.
Singlemode
CONNECTOR LOSSES (TOTAL OF BOTH ENDS)
1550 nm Laser, +5 dBm –30 dBm 35 dB
Singlemode ST connector 2 dB
FIBER LOSSES
These power budgets are calculated from the
820 nm multimode 3 dB/km
NOTE manufacturer’s worst-case transmitter power
1300 nm multimode 1 dB/km
and worst case receiver sensitivity.
1300 nm singlemode 0.35 dB/km
The power budgets for the 1300nm ELED are cal- 1550 nm singlemode 0.25 dB/km
NOTE culated from the manufacturer's transmitter Splice losses: One splice every 2 km,
power and receiver sensitivity at ambient temper- at 0.05 dB loss per splice.
ature. At extreme temperatures these values will
deviate based on component tolerance. On aver- SYSTEM MARGIN
age, the output power will decrease as the tem- 3 dB additional loss added to calculations to compensate for
all other losses.
perature is increased by a factor 1dB / 5°C.
MAXIMUM OPTICAL INPUT POWER Compensated difference in transmitting and receiving (channel
asymmetry) channel delays using GPS satellite clock: 10 ms
EMITTER, FIBER TYPE MAX. OPTICAL
INPUT POWER
820 nm LED, Multimode –7.6 dBm
1300 nm LED, Multimode –11 dBm
1300 nm ELED, Singlemode –14 dBm
1300 nm Laser, Singlemode –14 dBm
1550 nm Laser, Singlemode –14 dBm

2.2.11 ENVIRONMENTAL

AMBIENT TEMPERATURES OTHER


Storage temperature: –40 to 85°C Altitude: 2000 m (maximum)
Operating temperature: –40 to 60°C; the LCD contrast may be Pollution degree: II
impaired at temperatures less than – Overvoltage category: II
20°C
Ingress protection: IP20 front, IP10 back
HUMIDITY
Humidity: operating up to 95% (non-condensing) at
55°C (as per IEC60068-2-30 variant 1,
6days).

GE Multilin G60 Generator Protection System 2-23


2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION

2.2.12 TYPE TESTS

G60 TYPE TESTS


TEST REFERENCE STANDARD TEST LEVEL
Dielectric voltage withstand EN60255-5 2.2 kV
Impulse voltage withstand EN60255-5 5 kV

2 Damped oscillatory
Electrostatic discharge
IEC61000-4-18 / IEC60255-22-1
EN61000-4-2 / IEC60255-22-2
2.5 kV CM, 1 kV DM
Level 3
RF immunity EN61000-4-3 / IEC60255-22-3 Level 3
Fast transient disturbance EN61000-4-4 / IEC60255-22-4 Class A and B
Surge immunity EN61000-4-5 / IEC60255-22-5 Level 3 and 4
Conducted RF immunity EN61000-4-6 / IEC60255-22-6 Level 3
Power frequency immunity EN61000-4-7 / IEC60255-22-7 Class A and B
Voltage interruption and ripple DC IEC60255-11 12% ripple, 200 ms interrupts
Radiated and conducted emissions CISPR11 / CISPR22 / IEC60255-25 Class A
Sinusoidal vibration IEC60255-21-1 Class 1
Shock and bump IEC60255-21-2 Class 1
Seismic IEC60255-21-3 Class 1
Power magnetic immunity IEC61000-4-8 Level 5
Pulse magnetic immunity IEC61000-4-9 Level 4
Damped magnetic immunity IEC61000-4-10 Level 4
Voltage dip and interruption IEC61000-4-11 0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory IEC61000-4-12 2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz IEC61000-4-16 Level 4
Voltage ripple IEC61000-4-17 15% ripple
Ingress protection IEC60529 IP40 front, IP10 back
Cold IEC60068-2-1 –40°C for 16 hours
Hot IEC60068-2-2 85°C for 16 hours
Humidity IEC60068-2-30 6 days, variant 1
Damped oscillatory IEEE/ANSI C37.90.1 2.5 kV, 1 MHz
RF immunity IEEE/ANSI C37.90.2 20 V/m, 80 MHz to 1 GHz
Safety UL508 e83849 NKCR
Safety UL C22.2-14 e83849 NKCR7
Safety UL1053 e83849 NKCR

2.2.13 PRODUCTION TESTS

THERMAL
Products go through an environmental test based upon an
Accepted Quality Level (AQL) sampling process.

2-24 G60 Generator Protection System GE Multilin


2 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS

2.2.14 APPROVALS

APPROVALS
COMPLIANCE APPLICABLE ACCORDING TO
COUNCIL DIRECTIVE
CE compliance Low voltage directive EN60255-5
EMC directive EN60255-26 / EN50263
EN61000-6-5 2
North America --- UL508
--- UL1053
--- C22.2 No. 14

2.2.15 MAINTENANCE

MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds) of torque.
CLEANING
Normally, cleaning is not required; but for situations where dust has accumulated on the faceplate display, a dry cloth can be used.
Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to avoid deterioration
of electrolytic capacitors.
NOTE

GE Multilin G60 Generator Protection System 2-25


2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION

2-26 G60 Generator Protection System GE Multilin


3 HARDWARE 3.1 DESCRIPTION

3 HARDWARE 3.1DESCRIPTION 3.1.1 PANEL CUTOUT

a) HORIZONTAL UNITS
The G60 Generator Protection System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The
faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains addi-
tional user-programmable pushbuttons and LED indicators.
The modular design allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is
hinged to allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear
depth. There is also a removable dust cover that fits over the faceplate, which must be removed when attempting to access
the keypad or RS232 communications port.
The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of
your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent
equipment.
3
The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator
access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws
supplied with the relay.

11.016”
[279,81 mm]

9.687”
[246,05 mm]

17.56”
[446,02 mm]

7.460”
[189,48 mm]
6.995” 6.960”
[177,67 mm] [176,78 mm]

19.040”
[483,62 mm]
842807A1.CDR

Figure 3–1: G60 HORIZONTAL DIMENSIONS (ENHANCED PANEL)

GE Multilin G60 Generator Protection System 3-1


3.1 DESCRIPTION 3 HARDWARE

18.370”
[466,60 mm]

0.280”
[7,11 mm]
Typ. x 4
CUT-OUT

4.000”
[101,60 mm]

17.750”
[450,85 mm] 842808A1.CDR

3 Figure 3–2: G60 HORIZONTAL MOUNTING (ENHANCED PANEL)

Figure 3–3: G60 HORIZONTAL MOUNTING AND DIMENSIONS (STANDARD PANEL)

b) VERTICAL UNITS
The G60 Generator Protection System is available as a reduced size (¾) vertical mount unit, with a removable faceplate.
The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains
additional user-programmable pushbuttons and LED indicators.
The modular design allows the relay to be easily upgraded or repaired by a qualified service person. The faceplate is
hinged to allow easy access to the removable modules, and is itself removable to allow mounting on doors with limited rear
depth. There is also a removable dust cover that fits over the faceplate, which must be removed when attempting to access
the keypad or RS232 communications port.
The case dimensions are shown below, along with panel cutout details for panel mounting. When planning the location of
your panel cutout, ensure that provision is made for the faceplate to swing open without interference to or from adjacent
equipment.

3-2 G60 Generator Protection System GE Multilin


3 HARDWARE 3.1 DESCRIPTION

The relay must be mounted such that the faceplate sits semi-flush with the panel or switchgear door, allowing the operator
access to the keypad and the RS232 communications port. The relay is secured to the panel with the use of four screws
supplied with the relay.

7.482” 11.015”
1.329”

13.560”
3
15.000” 14.025”

4.000”

9.780”

843809A1.CDR

Figure 3–4: G60 VERTICAL DIMENSIONS (ENHANCED PANEL)

GE Multilin G60 Generator Protection System 3-3


3.1 DESCRIPTION 3 HARDWARE

e UR SERIES

Figure 3–5: G60 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL)


For details on side mounting G60 devices with the enhanced front panel, refer to the following documents available online
from the GE Multilin website.
• GEK-113180: UR-series UR-V side-mounting front panel assembly instructions.
• GEK-113181: Connecting the side-mounted UR-V enhanced front panel to a vertical UR-series device.
• GEK-113182: Connecting the side-mounted UR-V enhanced front panel to a vertically-mounted horizontal UR-series
device.
For details on side mounting G60 devices with the standard front panel, refer to the figures below.

3-4 G60 Generator Protection System GE Multilin


3 HARDWARE 3.1 DESCRIPTION

Figure 3–6: G60 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL)

GE Multilin G60 Generator Protection System 3-5


3.1 DESCRIPTION 3 HARDWARE

Figure 3–7: G60 VERTICAL SIDE MOUNTING REAR DIMENSIONS (STANDARD PANEL)

3.1.2 MODULE WITHDRAWAL AND INSERTION

Module withdrawal and insertion may only be performed when control power has been removed from the
unit. Inserting an incorrect module type into a slot may result in personal injury, damage to the unit or con-
WARNING
nected equipment, or undesired operation!
Proper electrostatic discharge protection (for example, a static strap) must be used when coming in con-
tact with modules while the relay is energized!
WARNING

The relay, being modular in design, allows for the withdrawal and insertion of modules. Modules must only be replaced with
like modules in their original factory configured slots.
The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows
for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens
completely and allows easy access to all modules in the G60.

3-6 G60 Generator Protection System GE Multilin


3 HARDWARE 3.1 DESCRIPTION

842812A1.CDR

Figure 3–8: UR MODULE WITHDRAWAL AND INSERTION (ENHANCED FACEPLATE)


3
The standard faceplate can be opened to the left, once the sliding latch on the right side has been pushed up, as shown
below. This allows for easy accessibility of the modules for withdrawal.

Figure 3–9: UR MODULE WITHDRAWAL AND INSERTION (STANDARD FACEPLATE)


To properly remove a module, the ejector/inserter clips, located at the top and bottom of each module, must be pulled
simultaneously. Before performing this action, control power must be removed from the relay. Record the original loca-
tion of the module to ensure that the same or replacement module is inserted into the correct slot. Modules with current
input provide automatic shorting of external CT circuits.
To properly insert a module, ensure that the correct module type is inserted into the correct slot position. The ejector/
inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module is
smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously.
When the clips have locked into position, the module will be fully inserted.
All CPU modules except the 9E are equipped with 10/100Base-T or 100Base-F Ethernet connectors. These con-
nectors must be individually disconnected from the module before it can be removed from the chassis.
NOTE

GE Multilin G60 Generator Protection System 3-7


3.1 DESCRIPTION 3 HARDWARE

The 4.0x release of the G60 relay includes new hardware modules.The new CPU modules are specified with codes
9E and higher. The new CT/VT modules are specified with the codes 8F and higher.
NOTE
The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old
CPUs. To prevent hardware mismatches, the new modules have blue labels and a warning sticker stating “Attn.:
Ensure CPU and DSP module label colors are the same!”. In the event that there is a mismatch between the
CPU and CT/VT module, the relay will not function and a DSP ERROR or HARDWARE MISMATCH error will be dis-
played.
All other input and output modules are compatible with the new hardware. Firmware versions 4.0x and higher are
only compatible with the new hardware modules. Previous versions of the firmware (3.4x and earlier) are only com-
patible with the older hardware modules.

3.1.3 REAR TERMINAL LAYOUT

3
G60 Generator Management Relay RATINGS: Model: G60D00HCHF8AH6AM6BP8BX7A
Mods: 000
Control Power: 88-300V DC @ 35W / 77-265V AC @ 35VA Wiring Diagram: ZZZZZZ
Contact Inputs: 300V DC Max 10mA Inst. Manual: D
Contact Outputs: Standard Pilot Duty / 250V AC 7.5A Serial Number: MAZB98000029
360V A Resistive / 125V DC Break Firmware: D
GE Multilin 4A @ L/R = 40mS / 300W Mfg. Date: 1998/01/05

Technical Support:
Made in
Tel: (905) 294-6222 http://www.GEIndustrial.com/Multilin ®
®
Canada
Fax: (905) 201-2098 - M A A B 9 7 0 0 0 0 9 9 -

X W V U T S R P N M L K J H G F D B

c b a c b a c b a c b a

b a b a
Tx1 1 1
1 1
2 2
Rx1 2 2
3 Tx1 3
3 3
Tx1
4 4

CH1
4 4
Rx1 5
Tx2 CH1 5
Tx 6
Rx 6
CH2
Rx2 IN 7
Tx2
7
8

CH2
Tx2 8
OUT
Rx2

Optional Optional Optional Optional Optional CT/VT CPU module Power


Ethernet direct contact CT/VT or contact module (Ethernet not supply
switch input/output input/output contact input/output available when module
module module input/output module ordered with
module Ethernet switch)
830720A3.CDR

Figure 3–10: REAR TERMINAL VIEW


Do not touch any rear terminals while the relay is energized!

WARNING

The relay follows a convention with respect to terminal number assignments which are three characters long assigned in
order by module slot position, row number, and column letter. Two-slot wide modules take their slot designation from the
first slot position (nearest to CPU module) which is indicated by an arrow marker on the terminal block. See the following
figure for an example of rear terminal assignments.

3-8 G60 Generator Protection System GE Multilin


3 HARDWARE 3.1 DESCRIPTION

Figure 3–11: EXAMPLE OF MODULES IN F AND H SLOTS

GE Multilin G60 Generator Protection System 3-9


3.2 WIRING 3 HARDWARE

3.2WIRING 3.2.1 TYPICAL WIRING

TYPICAL CONFIGURATION
THE AC SIGNAL PATH IS CONFIGURABLE
POSITIVE WATTS
OPEN DELTA
VT CONNECTION (ABC)

A
B
C

3
F 5a

F 6a

F 7a
F 5c

F 6c

F 7c
M1a

M1b

M2a

M2b

M3a

M3b

M4a

M4b
M1c

M2c

M3c

M4c

F5a

F6a

F7a

F8a

F1a

F1b

F2a

F2b

F3a

F3b

F4a

F4b
F5c

F6c

F7c

F8c

F1c

F2c

F3c

F4c
VX
VB

VC

VB

VC
VA

VA

VX

IG5

IG1
VB

VC

VB

VC

IG
IG5

IG1

VA

VA
IG

IA5

IA1

IB

IC
IA

IC5

IC1
IA5

IA1

IB5

IB1
IB

IC
IA

IC5

IC1
IB5

IB1

CURRENT SUPERVISION
VOLTAGE AND
CURRENT INPUTS VOLTAGE INPUTS VOLTAGE INPUTS CURRENT INPUTS
8F/8G or 8H/8J 8F / 8G

H5a CONTACT INPUT H5a DIGITAL INPUTS/OUTPUTS 6G I H1a TC 1


H5c CONTACT INPUT H5c H1
V
H1b
H6a CONTACT INPUT H6a H1c
H6c CONTACT INPUT H6c I H2a
H5b COMMON H5b H2 H2b

VOLTAGE SUPERVISION
V
H2c
H7a CONTACT INPUT H7a
I H3a
H7c CONTACT INPUT H7c
TC 2
H3
V
H3b
H8a CONTACT INPUT H8a
H3c
H8c CONTACT INPUT H8c I H4a
H7b COMMON H7b
H4
V
H4b
H8b SURGE H4c
( DC ONLY )

GE Consumer & Industrial


B1b Multilin
1

CRITICAL
B1a FAILURE
B2b
B3a 48 V DC G60 GENERATOR MANAGEMENT RELAY
B3b OUTPUT
DC
POWER SUPPLY

B5b HI
CONTROL
B6b LO
AC or DC POWER
B6a
RS-232
B8a SURGE (front)
B8b FILTER
DB-9

CPU 9E
Output
COM 2
COM 1

RS485
RS485

IRIG-B

IRIG-B
Input

CONTACTS SHOWN
WITH NO
CONTROL POWER
com

com

BNC

BNC
D1b
D2b
D3b
D1a
D2a
D3a
D4b
D4a

MODULE ARRANGEMENT
No. 10AWG
minimum
X W V U T S R P N M L K J H G F D B
GROUND 8 6 8 9 1
BUS
CT Inputs/ VT/CT CPU Power
outputs Supply
(Rear View)
CONNECTOR
twisted pairs

Co-axial *
Shielded

Co-axial

Co-axial

25 PIN
7 SGND
3 RXD
2 TXD
terminal as input
Co-axial * - For IRIG-B Input

COMPUTER
only use one

20

22
8

5
4
1
2
3
4

7
8
9
5
6

9 PIN
CONNECTOR

MODULES MUST BE
UR
1
2
3
4

7
8
9
5
6

GROUNDED IF
TERMINAL IS
Ground at

SGND
Remote

RXD
Device

TXD

PROVIDED

This diagram is based on the following order code:


G60-H00-HCH-F8F-H6G-M8H-PXX-UXX-WXX
This diagram provides an example of how the device
is wired, not specifically how to wire the device. Please
refer to the Instruction Manual for additional details on
wiring based on various configurations.
830721A4.CDR

Figure 3–12: TYPICAL WIRING DIAGRAM

3-10 G60 Generator Protection System GE Multilin


3 HARDWARE 3.2 WIRING

Figure 3–13: TYPICAL WIRING WITH GPM-F AND GPM-S MODULES

GE Multilin G60 Generator Protection System 3-11


3.2 WIRING 3 HARDWARE

3.2.2 DIELECTRIC STRENGTH

The dielectric strength of the UR-series module hardware is shown in the following table:
Table 3–1: DIELECTRIC STRENGTH OF UR-SERIES MODULE HARDWARE
MODULE MODULE FUNCTION TERMINALS DIELECTRIC STRENGTH
TYPE (AC)
FROM TO
1 Power supply High (+); Low (+); (–) Chassis 2000 V AC for 1 minute
1 Power supply 48 V DC (+) and (–) Chassis 2000 V AC for 1 minute
1 Power supply Relay terminals Chassis 2000 V AC for 1 minute
2 Reserved N/A N/A N/A
3 Reserved N/A N/A N/A

3 4
5
Reserved
Analog inputs/outputs
N/A
All except 8b
N/A
Chassis
N/A
< 50 V DC
6 Digital inputs/outputs All Chassis 2000 V AC for 1 minute
G.703 All except 2b, 3a, 7b, 8a Chassis 2000 V AC for 1 minute
7
RS422 All except 6a, 7b, 8a Chassis < 50 V DC
8 CT/VT All Chassis 2000 V AC for 1 minute
9 CPU All Chassis 2000 V AC for 1 minute

Filter networks and transient protection clamps are used in the hardware to prevent damage caused by high peak voltage
transients, radio frequency interference (RFI), and electromagnetic interference (EMI). These protective components can
be damaged by application of the ANSI/IEEE C37.90 specified test voltage for a period longer than the specified one min-
ute.

3.2.3 CONTROL POWER

CONTROL POWER SUPPLIED TO THE RELAY MUST BE CONNECTED TO THE MATCHING POWER SUPPLY
RANGE OF THE RELAY. IF THE VOLTAGE IS APPLIED TO THE WRONG TERMINALS, DAMAGE MAY
CAUTION
OCCUR!
The G60 relay, like almost all electronic relays, contains electrolytic capacitors. These capacitors are well
known to be subject to deterioration over time if voltage is not applied periodically. Deterioration can be
NOTE
avoided by powering the relays up once a year.
The power supply module can be ordered for two possible voltage ranges, with or without a redundant power option. Each
range has a dedicated input connection for proper operation. The ranges are as shown below (see the Technical specifica-
tions section of chapter 2 for additional details):
• Low (LO) range: 24 to 48 V (DC only) nominal.
• High (HI) range: 125 to 250 V nominal.
The power supply module provides power to the relay and supplies power for dry contact input connections.
The power supply module provides 48 V DC power for dry contact input connections and a critical failure relay (see the
Typical wiring diagram earlier). The critical failure relay is a form-C device that will be energized once control power is
applied and the relay has successfully booted up with no critical self-test failures. If on-going self-test diagnostic checks
detect a critical failure (see the Self-test errors section in chapter 7) or control power is lost, the relay will de-energize.
For high reliability systems, the G60 has a redundant option in which two G60 power supplies are placed in parallel on the
bus. If one of the power supplies become faulted, the second power supply will assume the full load of the relay without any
interruptions. Each power supply has a green LED on the front of the module to indicate it is functional. The critical fail relay
of the module will also indicate a faulted power supply.

3-12 G60 Generator Protection System GE Multilin


3 HARDWARE 3.2 WIRING

An LED on the front of the control power module shows the status of the power supply:
LED INDICATION POWER SUPPLY
CONTINUOUS ON OK
ON / OFF CYCLING Failure
OFF Failure

NOTE:
AC or DC 14 gauge stranded AC or DC
wire with suitable
disconnect devices
is recommended.
Heavy copper conductor
or braided wire
3

B8b B8a B6a B6b B5b

GND
+ +
+ —
– LOW HIGH
FILTER SURGE
CONTROL OPTIONAL
POWER ETHERNET SWITCH
Switchgear UR-series
ground bus protection system

827759AA.CDR

Figure 3–14: CONTROL POWER CONNECTION

3.2.4 CT/VT MODULES

A CT/VT module may have voltage inputs on channels 1 through 4 inclusive, or channels 5 through 8 inclusive. Channels 1
and 5 are intended for connection to phase A, and are labeled as such in the relay. Likewise, channels 2 and 6 are intended
for connection to phase B, and channels 3 and 7 are intended for connection to phase C.
Channels 4 and 8 are intended for connection to a single-phase source. For voltage inputs, these channel are labelled as
auxiliary voltage (VX). For current inputs, these channels are intended for connection to a CT between system neutral and
ground, and are labelled as ground current (IG).
Verify that the connection made to the relay nominal current of 1 A or 5 A matches the secondary rating of
the connected CTs. Unmatched CTs may result in equipment damage or inadequate protection.
CAUTION

CT/VT modules may be ordered with a standard ground current input that is the same as the phase current input. Each AC
current input has an isolating transformer and an automatic shorting mechanism that shorts the input when the module is
withdrawn from the chassis. There are no internal ground connections on the current inputs. Current transformers with 1 to
50000 A primaries and 1 A or 5 A secondaries may be used.
CT/VT modules with a sensitive ground input are also available. The ground CT input of the sensitive ground modules is
ten times more sensitive than the ground CT input of standard CT/VT modules. However, the phase CT inputs and phase
VT inputs are the same as those of regular CT/VT modules.
The above modules are available with enhanced diagnostics. These modules can automatically detect CT/VT hardware
failure and take the relay out of service.
CT connections for both ABC and ACB phase rotations are identical as shown in the Typical wiring diagram.
The exact placement of a zero-sequence core balance CT to detect ground fault current is shown below. Twisted-pair
cabling on the zero-sequence CT is recommended.

GE Multilin G60 Generator Protection System 3-13


3.2 WIRING 3 HARDWARE

UNSHIELDED CABLE SHIELDED CABLE


Ground connection to neutral
must be on the source side Stress cone
Source Source shields
A B C N G A B C

Ground
outside CT

3
To ground;
LOAD must be on
load side

LOAD 996630A5

Figure 3–15: ZERO-SEQUENCE CORE BALANCE CT INSTALLATION


The phase voltage channels are used for most metering and protection purposes. The auxiliary voltage channel is used as
input for the synchrocheck and volts-per-hertz features.
Substitute the tilde “~” symbol with the slot position of the module in the following figure.

NOTE
~ 1a

~ 1b

~ 2a

~ 2b

~ 3a

~ 3b

~ 4a

~ 4b

~ 5a

~ 6a

~ 7a

~ 8a
~ 1c

~ 2c

~ 3c

~ 4c

~ 5c

~ 6c

~ 7c

~ 8c
VC
VB
VA

VX
IG

IG1
IA

IC
IA1

IC1
IB

IB1

IG5

VC
VB
VA
IA5

VX
IC5
IB5

Current inputs Voltage inputs


8F, 8G, 8L, and 8M modules (4 CTs and 4 VTs)
~ 1a

~ 1b

~ 2a

~ 2b

~ 3a

~ 3b

~ 4a

~ 4b

~ 5a

~ 5b

~ 6a

~ 6b

~ 7a

~ 7b

~ 8a

~ 8b
~ 1c

~ 2c

~ 3c

~ 4c

~ 5c

~ 6c

~ 7c

~ 8c
IG

IG
IG1

IG1
IA

IC

IA

IC
IA1

IA1

IC1
IB

IC1

IB
IB1

IB1
IG5

IG5
IA5

IC5

IA5

IC5
IB5

IB5

Current inputs
8H, 8J, 8N, and 8R modules (8 CTs)
842766A3.CDR

Figure 3–16: CT/VT MODULE WIRING

3-14 G60 Generator Protection System GE Multilin


3 HARDWARE 3.2 WIRING

3.2.5 PROCESS BUS MODULES

The G60 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin
HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units,
known as Bricks. The HardFiber system has been designed to integrate seamlessly with the existing UR-series applica-
tions, including protection functions, FlexLogic™, metering, and communications.
The IEC 61850 process bus system offers the following benefits.
• Drastically reduces labor associated with design, installation, and testing of protection and control applications using
the G60 by reducing the number of individual copper terminations.
• Integrates seamlessly with existing G60 applications, since the IEC 61850 process bus interface module replaces the
traditional CT/VT modules.
• Communicates using open standard IEC 61850 messaging.
For additional details on the HardFiber system, refer to GE publication GEK-113500: HardFiber System Instruction Manual.
3
3.2.6 CONTACT INPUTS AND OUTPUTS

Every contact input/output module has 24 terminal connections. They are arranged as three terminals per row, with eight
rows in total. A given row of three terminals may be used for the outputs of one relay. For example, for form-C relay outputs,
the terminals connect to the normally open (NO), normally closed (NC), and common contacts of the relay. For a form-A
output, there are options of using current or voltage detection for feature supervision, depending on the module ordered.
The terminal configuration for contact inputs is different for the two applications.
The contact inputs are grouped with a common return. The G60 has two versions of grouping: four inputs per common
return and two inputs per common return. When a contact input/output module is ordered, four inputs per common is used.
The four inputs per common allows for high-density inputs in combination with outputs, with a compromise of four inputs
sharing one common. If the inputs must be isolated per row, then two inputs per common return should be selected (4D
module).
The tables and diagrams on the following pages illustrate the module types (6A, etc.) and contact arrangements that may
be ordered for the relay. Since an entire row is used for a single contact output, the name is assigned using the module slot
position and row number. However, since there are two contact inputs per row, these names are assigned by module slot
position, row number, and column position.
Some form-A / solid-state relay outputs include circuits to monitor the DC voltage across the output contact when it is open,
and the DC current through the output contact when it is closed. Each of the monitors contains a level detector whose out-
put is set to logic “On = 1” when the current in the circuit is above the threshold setting. The voltage monitor is set to “On =
1” when the current is above about 1 to 2.5 mA, and the current monitor is set to “On = 1” when the current exceeds about
80 to 100 mA. The voltage monitor is intended to check the health of the overall trip circuit, and the current monitor can be
used to seal-in the output contact until an external contact has interrupted current flow.
Block diagrams are shown below for form-A and solid-state relay outputs with optional voltage monitor, optional current
monitor, and with no monitoring. The actual values shown for contact output 1 are the same for all contact outputs.

GE Multilin G60 Generator Protection System 3-15


3.2 WIRING 3 HARDWARE

If Idc 80mA, Cont Op 1 = “IOn”


~#a ~#a otherwise Cont Op 1 = “IOff”

I I If Idc 1mA, Cont Op 1 = “VOn”


otherwise Cont Op 1 = “VOff”
If Idc 1mA, Cont Op 1 = “VOn”
~#b ~#b Load
otherwise Cont Op 1 = “VOff”
V Load V
~#c + ~#c +
a) Voltage with optional
Voltage monitoring only Both voltage and current monitoring
current monitoring

If Idc 80mA, Cont Op 1 = “IOn”


~#a ~#a otherwise Cont Op 1 = “IOff”
V V If Idc 1mA, Cont Op 1 = “VOn”
otherwise Cont Op 1 = “VOff”
If Idc 80mA, Cont Op 1 = “IOn”
3 I ~#b
otherwise Cont Op 1 = “IOff”
Load
I ~#b Load

~#c + ~#c +
b) Current with optional
Current monitoring only Both voltage and current monitoring
voltage monitoring
(external jumper a-b is required)

~#a

~#b

Load
~#c +
c) No monitoring 827862A3.CDR

Figure 3–17: FORM-A AND SOLID-STATE CONTACT OUTPUTS WITH VOLTAGE AND CURRENT MONITORING
The operation of voltage and current monitors is reflected with the corresponding FlexLogic™ operands (CONT OP # VON,
CONT OP # VOFF, and CONT OP # ION) which can be used in protection, control, and alarm logic. The typical application of
the voltage monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is seal-in of the
control command.
Refer to the Digital elements section of chapter 5 for an example of how form-A and solid-state relay contacts can be
applied for breaker trip circuit integrity monitoring.
Relay contacts must be considered unsafe to touch when the unit is energized! If the relay contacts need to
be used for low voltage accessible applications, it is the customer’s responsibility to ensure proper insula-
WARNING
tion levels!
USE OF FORM-A AND SOLID-STATE RELAY OUTPUTS IN HIGH IMPEDANCE CIRCUITS

NOTE For form-A and solid-state relay output contacts internally equipped with a voltage measuring cIrcuit across the
contact, the circuit has an impedance that can cause a problem when used in conjunction with external high input
impedance monitoring equipment such as modern relay test set trigger circuits. These monitoring circuits may con-
tinue to read the form-A contact as being closed after it has closed and subsequently opened, when measured as
an impedance.
The solution to this problem is to use the voltage measuring trigger input of the relay test set, and connect the form-
A contact through a voltage-dropping resistor to a DC voltage source. If the 48 V DC output of the power supply is
used as a source, a 500 Ω, 10 W resistor is appropriate. In this configuration, the voltage across either the form-A
contact or the resistor can be used to monitor the state of the output.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module; wherever a number
sign “#” appears, substitute the contact number
NOTE

When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, the Flex-
Logic™ operand driving the contact output should be given a reset delay of 10 ms to prevent damage of
NOTE
the output contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).

3-16 G60 Generator Protection System GE Multilin


3 HARDWARE 3.2 WIRING

Table 3–2: CONTACT INPUT AND OUTPUT MODULE ASSIGNMENTS


~6A MODULE ~6B MODULE ~6C MODULE ~6D MODULE
TERMINAL OUTPUT OR TERMINAL OUTPUT OR TERMINAL OUTPUT TERMINAL OUTPUT
ASSIGNMENT INPUT ASSIGNMENT INPUT ASSIGNMENT ASSIGNMENT
~1 Form-A ~1 Form-A ~1 Form-C ~1a, ~1c 2 Inputs
~2 Form-A ~2 Form-A ~2 Form-C ~2a, ~2c 2 Inputs
~3 Form-C ~3 Form-C ~3 Form-C ~3a, ~3c 2 Inputs
~4 Form-C ~4 Form-C ~4 Form-C ~4a, ~4c 2 Inputs
~5a, ~5c 2 Inputs ~5 Form-C ~5 Form-C ~5a, ~5c 2 Inputs
~6a, ~6c 2 Inputs ~6 Form-C ~6 Form-C ~6a, ~6c 2 Inputs
~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7 Form-C ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8 Form-C ~8a, ~8c 2 Inputs
3
~6E MODULE ~6F MODULE ~6G MODULE ~6H MODULE
TERMINAL OUTPUT OR TERMINAL OUTPUT TERMINAL OUTPUT OR TERMINAL OUTPUT OR
ASSIGNMENT INPUT ASSIGNMENT ASSIGNMENT INPUT ASSIGNMENT INPUT
~1 Form-C ~1 Fast Form-C ~1 Form-A ~1 Form-A
~2 Form-C ~2 Fast Form-C ~2 Form-A ~2 Form-A
~3 Form-C ~3 Fast Form-C ~3 Form-A ~3 Form-A
~4 Form-C ~4 Fast Form-C ~4 Form-A ~4 Form-A
~5a, ~5c 2 Inputs ~5 Fast Form-C ~5a, ~5c 2 Inputs ~5 Form-A
~6a, ~6c 2 Inputs ~6 Fast Form-C ~6a, ~6c 2 Inputs ~6 Form-A
~7a, ~7c 2 Inputs ~7 Fast Form-C ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8 Fast Form-C ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs

~6K MODULE ~6L MODULE ~6M MODULE ~6N MODULE


TERMINAL OUTPUT TERMINAL OUTPUT OR TERMINAL OUTPUT OR TERMINAL OUTPUT OR
ASSIGNMENT ASSIGNMENT INPUT ASSIGNMENT INPUT ASSIGNMENT INPUT
~1 Form-C ~1 Form-A ~1 Form-A ~1 Form-A
~2 Form-C ~2 Form-A ~2 Form-A ~2 Form-A
~3 Form-C ~3 Form-C ~3 Form-C ~3 Form-A
~4 Form-C ~4 Form-C ~4 Form-C ~4 Form-A
~5 Fast Form-C ~5a, ~5c 2 Inputs ~5 Form-C ~5a, ~5c 2 Inputs
~6 Fast Form-C ~6a, ~6c 2 Inputs ~6 Form-C ~6a, ~6c 2 Inputs
~7 Fast Form-C ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs
~8 Fast Form-C ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs

~6P MODULE ~6R MODULE ~6S MODULE ~6T MODULE


TERMINAL OUTPUT OR TERMINAL OUTPUT OR TERMINAL OUTPUT OR TERMINAL OUTPUT OR
ASSIGNMENT INPUT ASSIGNMENT INPUT ASSIGNMENT INPUT ASSIGNMENT INPUT
~1 Form-A ~1 Form-A ~1 Form-A ~1 Form-A
~2 Form-A ~2 Form-A ~2 Form-A ~2 Form-A
~3 Form-A ~3 Form-C ~3 Form-C ~3 Form-A
~4 Form-A ~4 Form-C ~4 Form-C ~4 Form-A
~5 Form-A ~5a, ~5c 2 Inputs ~5 Form-C ~5a, ~5c 2 Inputs
~6 Form-A ~6a, ~6c 2 Inputs ~6 Form-C ~6a, ~6c 2 Inputs
~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs

GE Multilin G60 Generator Protection System 3-17


3.2 WIRING 3 HARDWARE

~6U MODULE ~6V MODULE ~67 MODULE ~4A MODULE


TERMINAL OUTPUT OR TERMINAL OUTPUT OR TERMINAL OUTPUT TERMINAL OUTPUT
ASSIGNMENT INPUT ASSIGNMENT INPUT ASSIGNMENT ASSIGNMENT
~1 Form-A ~1 Form-A ~1 Form-A ~1 Not Used
~2 Form-A ~2 Form-A ~2 Form-A ~2 Solid-State
~3 Form-A ~3 Form-C ~3 Form-A ~3 Not Used
~4 Form-A ~4 2 Outputs ~4 Form-A ~4 Solid-State
~5 Form-A ~5a, ~5c 2 Inputs ~5 Form-A ~5 Not Used
~6 Form-A ~6a, ~6c 2 Inputs ~6 Form-A ~6 Solid-State
~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7 Form-A ~7 Not Used
~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8 Form-A ~8 Solid-State

3
~4B MODULE ~4C MODULE ~4D MODULE ~4L MODULE
TERMINAL OUTPUT TERMINAL OUTPUT TERMINAL OUTPUT TERMINAL OUTPUT
ASSIGNMENT ASSIGNMENT ASSIGNMENT ASSIGNMENT
~1 Not Used ~1 Not Used ~1a, ~1c 2 Inputs ~1 2 Outputs
~2 Solid-State ~2 Solid-State ~2a, ~2c 2 Inputs ~2 2 Outputs
~3 Not Used ~3 Not Used ~3a, ~3c 2 Inputs ~3 2 Outputs
~4 Solid-State ~4 Solid-State ~4a, ~4c 2 Inputs ~4 2 Outputs
~5 Not Used ~5 Not Used ~5a, ~5c 2 Inputs ~5 2 Outputs
~6 Solid-State ~6 Solid-State ~6a, ~6c 2 Inputs ~6 2 Outputs
~7 Not Used ~7 Not Used ~7a, ~7c 2 Inputs ~7 2 Outputs
~8 Solid-State ~8 Solid-State ~8a, ~8c 2 Inputs ~8 Not Used

3-18 G60 Generator Protection System GE Multilin


3 HARDWARE 3.2 WIRING

842762A2.CDR

Figure 3–18: CONTACT INPUT AND OUTPUT MODULE WIRING (1 of 2)

GE Multilin G60 Generator Protection System 3-19


3.2 WIRING 3 HARDWARE

~ 1a ~ 5a CONTACT IN ~ 5a DIGITAL I/O 6L V ~ 1a ~ 7a CONTACT IN ~ 7a DIGITAL I/O 6M V ~ 1a

6K
I I
~ 1b ~1 ~ 5c CONTACT IN ~ 5c ~1 ~ 1b ~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 1c ~ 6a CONTACT IN ~ 6a ~ 1c ~ 8a CONTACT IN ~ 8a ~ 1c
~ 2a ~ 6c CONTACT IN ~ 6c V ~ 2a ~ 8c CONTACT IN ~ 8c V ~ 2a
I I
~ 2b ~2 ~ 5b COMMON ~ 5b ~2 ~ 2b ~ 7b COMMON ~ 7b ~2 ~ 2b
~ 2c ~ 2c ~ 2c
~ 7a CONTACT IN ~ 7a ~ 8b SURGE
~ 3a ~ 3a ~ 3a
~ 7c CONTACT IN ~ 7c
~ 3b ~3 ~3 ~ 3b ~3 ~ 3b
~ 8a CONTACT IN ~ 8a
~ 3c ~ 3c ~ 3c
~ 8c CONTACT IN ~ 8c
~ 4a ~ 4a ~ 4a
~ 7b COMMON ~ 7b
~ 4b ~4 ~4 ~ 4b ~4 ~ 4b
~ 4c ~ 8b SURGE ~ 4c ~ 4c
~ 5a ~ 5a
~ 5b ~5 ~5 ~ 5b
~ 5c ~ 5c
~ 6a ~ 6a
~ 6b ~6 ~6 ~ 6b
~ 6c ~ 6c
~ 7a

3
DIGITAL I/O

~ 7b ~7
~ 7c
~ 8a
~ 8b ~8
~ 8c

~ 5a CONTACT IN ~ 5a DIGITAL I/O 6N V ~ 1a ~ 7a CONTACT IN ~ 7a DIGITAL I/O 6P V ~ 1a


I I
~ 5c CONTACT IN ~ 5c ~1 ~ 1b ~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 6a CONTACT IN ~ 6a ~ 1c ~ 8a CONTACT IN ~ 8a ~ 1c
~ 6c CONTACT IN ~ 6c V ~ 2a ~ 8c CONTACT IN ~ 8c V ~ 2a
I I
~ 5b COMMON ~ 5b ~2 ~ 2b ~ 7b COMMON ~ 7b ~2 ~ 2b
~ 2c ~ 2c
~ 7a CONTACT IN ~ 7a ~ 8b SURGE
V ~ 3a V ~ 3a
~ 7c CONTACT IN ~ 7c I I
~3 ~ 3b ~3 ~ 3b
~ 8a CONTACT IN ~ 8a
~ 3c ~ 3c
~ 8c CONTACT IN ~ 8c
V ~ 4a V ~ 4a
~ 7b COMMON ~ 7b I I
~4 ~ 4b ~4 ~ 4b
~ 8b SURGE ~ 4c ~ 4c
V ~ 5a
I
~5 ~ 5b
~ 5c
V ~ 6a
I
~6 ~ 6b
~ 5a CONTACT IN ~ 5a DIGITAL I/O 6R ~ 1a
~ 6c
~ 5c CONTACT IN ~ 5c ~1 ~ 1b
~ 6a CONTACT IN ~ 6a ~ 1c
~ 6c CONTACT IN ~ 6c ~ 2a
~ 5b COMMON ~ 5b ~2 ~ 2b
~ 2c ~ 7a CONTACT IN ~ 7a DIGITAL I/O 6S ~ 1a
~ 7a CONTACT IN ~ 7a
~ 3a ~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 7c CONTACT IN ~ 7c
~3 ~ 3b ~ 8a CONTACT IN ~ 8a ~ 1c
~ 8a CONTACT IN ~ 8a
~ 3c ~ 8c CONTACT IN ~ 8c ~ 2a
~ 8c CONTACT IN ~ 8c
~ 4a ~ 7b COMMON ~ 7b ~2 ~ 2b
~ 7b COMMON ~ 7b
~4 ~ 4b ~ 2c
~ 8b SURGE ~ 4c ~ 8b SURGE
~ 3a
~3 ~ 3b
~ 3c
~ 4a
~4 ~ 4b
~ 5a CONTACT IN ~ 5a DIGITAL I/O 6T ~ 1a ~ 4c
~ 5c CONTACT IN ~ 5c ~1 ~ 1b ~ 5a
~ 6a CONTACT IN ~ 6a ~ 1c ~5 ~ 5b
~ 6c CONTACT IN ~ 6c ~ 2a ~ 5c
~ 5b COMMON ~ 5b ~2 ~ 2b ~ 6a
~ 2c ~6 ~ 6b
~ 7a CONTACT IN ~ 7a ~ 6c
~ 3a
~ 7c CONTACT IN ~ 7c
~3 ~ 3b
~ 8a CONTACT IN ~ 8a
~ 3c
~ 8c CONTACT IN ~ 8c
~ 4a
~ 7b COMMON ~ 7b
~4 ~ 4b
~ 7a CONTACT IN ~ 7a DIGITAL I/O 6U ~ 1a
~ 8b SURGE ~ 4c
~ 7c CONTACT IN ~ 7c ~1 ~ 1b
~ 8a CONTACT IN ~ 8a ~ 1c
~ 8c CONTACT IN ~ 8c ~ 2a
~ 7b COMMON ~ 7b ~2 ~ 2b
~ 2c
~ 8b SURGE
~ 3a
~3 ~ 3b
~ 3c
~ 4a
~4 ~ 4b
~ 4c
~ 5a
~5 ~ 5b
~ 5c
~ 6a
~6 ~ 6b
~ 6c

842763A2.CDR

Figure 3–19: CONTACT INPUT AND OUTPUT MODULE WIRING (2 of 2)


CORRECT POLARITY MUST BE OBSERVED FOR ALL CONTACT INPUT AND SOLID STATE OUTPUT CON-
NECTIONS FOR PROPER FUNCTIONALITY.
CAUTION

3-20 G60 Generator Protection System GE Multilin


3 HARDWARE 3.2 WIRING

CONTACT INPUTS:
A dry contact has one side connected to terminal B3b. This is the positive 48 V DC voltage rail supplied by the power sup-
ply module. The other side of the dry contact is connected to the required contact input terminal. Each contact input group
has its own common (negative) terminal which must be connected to the DC negative terminal (B3a) of the power supply
module. When a dry contact closes, a current of 1 to 3 mA will flow through the associated circuit.
A wet contact has one side connected to the positive terminal of an external DC power supply. The other side of this contact
is connected to the required contact input terminal. If a wet contact is used, then the negative side of the external source
must be connected to the relay common (negative) terminal of each contact group. The maximum external source voltage
for this arrangement is 300 V DC.
The voltage threshold at which each group of four contact inputs will detect a closed contact input is programmable as
17 V DC for 24 V sources, 33 V DC for 48 V sources, 84 V DC for 110 to 125 V sources, and 166 V DC for 250 V sources.

(Dry) DIGITAL I/O


~ 7a + CONTACT IN
6B
~ 7a
(Wet) DIGITAL I/O 6B
~ 7a + CONTACT IN ~ 7a
3
~ 7c + CONTACT IN ~ 7c ~ 7c + CONTACT IN ~ 7c
~ 8a + CONTACT IN ~ 8a ~ 8a + CONTACT IN ~ 8a
~ 8c + CONTACT IN ~ 8c 24-250V ~ 8c + CONTACT IN ~ 8c
~ 7b - COMMON ~ 7b ~ 7b - COMMON ~ 7b
~ 8b SURGE ~ 8b SURGE

B 1b
1

B 1a CRITICAL
FAILURE
B 2b
B 3a -
POWER SUPPLY

48 VDC
B 3b + OUTPUT
B 5b HI+
CONTROL
B 6b LO+
POWER
B 6a -
B 8a SURGE
B 8b FILTER

827741A4.CDR

Figure 3–20: DRY AND WET CONTACT INPUT CONNECTIONS


Wherever a tilde “~” symbol appears, substitute with the slot position of the module.

NOTE

Contact outputs may be ordered as form-a or form-C. The form-A contacts may be connected for external circuit supervi-
sion. These contacts are provided with voltage and current monitoring circuits used to detect the loss of DC voltage in the
circuit, and the presence of DC current flowing through the contacts when the form-A contact closes. If enabled, the current
monitoring can be used as a seal-in signal to ensure that the form-A contact does not attempt to break the energized induc-
tive coil circuit and weld the output contacts.
There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We
recommend using an external DC supply.
NOTE

GE Multilin G60 Generator Protection System 3-21


3.2 WIRING 3 HARDWARE

USE OF CONTACT INPUTS WITH AUTO-BURNISHING:


The contact inputs sense a change of the state of the external device contact based on the measured current. When exter-
nal devices are located in a harsh industrial environment (either outdoor or indoor), their contacts can be exposed to vari-
ous types of contamination. Normally, there is a thin film of insulating sulfidation, oxidation, or contaminates on the surface
of the contacts, sometimes making it difficult or impossible to detect a change of the state. This film must be removed to
establish circuit continuity – an impulse of higher than normal current can accomplish this.
The contact inputs with auto-burnish create a high current impulse when the threshold is reached to burn off this oxidation
layer as a maintenance to the contacts. Afterwards the contact input current is reduced to a steady-state current. The
impulse will have a 5 second delay after a contact input changes state.
current

50 to 70 mA

3 mA
time

25 to 50 ms 842749A1.CDR

Figure 3–21: CURRENT THROUGH CONTACT INPUTS WITH AUTO-BURNISHING


Regular contact inputs limit current to less than 3 mA to reduce station battery burden. In contrast, contact inputs with auto-
burnishing allow currents up to 50 to 70 mA at the first instance when the change of state was sensed. Then, within 25 to
50 ms, this current is slowly reduced to 3 mA as indicated above. The 50 to 70 mA peak current burns any film on the con-
tacts, allowing for proper sensing of state changes. If the external device contact is bouncing, the auto-burnishing starts
when external device contact bouncing is over.
Another important difference between the auto-burnishing input module and the regular input modules is that only two con-
tact inputs have common ground, as opposed to four contact inputs sharing one common ground (refer to the Contact Input
and Output Module Wiring diagrams). This is beneficial when connecting contact inputs to separate voltage sources. Con-
sequently, the threshold voltage setting is also defined per group of two contact inputs.
The auto-burnish feature can be disabled or enabled using the DIP switches found on each daughter card. There is a DIP
switch for each contact, for a total of 16 inputs.

CONTACT INPUT 1 AUTO-BURNISH = OFF


CONTACT INPUT 2 AUTO-BURNISH = OFF

CONTACT INPUT 1 AUTO-BURNISH = ON


CONTACT INPUT 2 AUTO-BURNISH = OFF

CONTACT INPUT 1 AUTO-BURNISH = OFF


CONTACT INPUT 2 AUTO-BURNISH = ON

CONTACT INPUT 1 AUTO-BURNISH = ON


CONTACT INPUT 2 AUTO-BURNISH = ON

842751A1.CDR

Figure 3–22: AUTO-BURNISH DIP SWITCHES


The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, the auto-burnish
functionality can be checked using an oscilloscope.
NOTE

3-22 G60 Generator Protection System GE Multilin


3 HARDWARE 3.2 WIRING

3.2.7 TRANSDUCER INPUTS/OUTPUTS

Transducer input modules can receive input signals from external dcmA output transducers (dcmA In) or resistance tem-
perature detectors (RTD). Hardware and software is provided to receive signals from these external transducers and con-
vert these signals into a digital format for use as required.
Transducer output modules provide DC current outputs in several standard dcmA ranges. Software is provided to configure
virtually any analog quantity used in the relay to drive the analog outputs.
Every transducer input/output module has a total of 24 terminal connections. These connections are arranged as three ter-
minals per row with a total of eight rows. A given row may be used for either inputs or outputs, with terminals in column "a"
having positive polarity and terminals in column "c" having negative polarity. Since an entire row is used for a single input/
output channel, the name of the channel is assigned using the module slot position and row number.
Each module also requires that a connection from an external ground bus be made to terminal 8b. The current outputs
require a twisted-pair shielded cable, where the shield is grounded at one end only. The figure below illustrates the trans- 3
ducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay.
Wherever a tilde “~” symbol appears, substitute with the slot position of the module.

NOTE

Figure 3–23: TRANSDUCER INPUT/OUTPUT MODULE WIRING

GE Multilin G60 Generator Protection System 3-23


3.2 WIRING 3 HARDWARE

3.2.8 RS232 FACEPLATE PORT

A 9-pin RS232C serial port is located on the G60 faceplate for programming with a personal computer. All that is required
to use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for
the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
The baud rate for this port is fixed at 19200 bps.

NOTE

Figure 3–24: RS232 FACEPLATE PORT CONNECTION

3.2.9 CPU COMMUNICATION PORTS

a) OPTIONS
In addition to the faceplate RS232 port, the G60 provides two additional communication ports or a managed six-port Ether-
net switch, depending on the installed CPU module.
The CPU modules do not require a surge ground connection.

NOTE

Table 3–3: CPU MODULE COMMUNICATIONS


CPU TYPE COM1 COM2
9E RS485 RS485
9G 10Base-F and 10Base-T RS485
9H Redundant 10Base-F RS485
9J 100Base-FX RS485
9K Redundant 100Base-FX RS485
9L 100Base-FX RS485
9M Redundant 100Base-FX RS485

3-24 G60 Generator Protection System GE Multilin


3 HARDWARE 3.2 WIRING

Shielded twisted-pairs MM fiber optic cable Tx1 100Base-FL NORMAL

9K
COM1
Rx1
D1b +

9E
RS485 Tx2 100Base-F ALTERNATE
D2b ― Shielded twisted-pairs
Rx2
COM1
Ground at D3b COMMON D1a +
remote
RS485
D1a + D2a ―
device RS485 COM2
D2a ― Ground at D3a COMMON
COM2 remote
D3a COMMON D4b +
device
D4b + D4a ― IRIG-B
D4a ― IRIG-B input
BNC
input Co-axial cable
BNC

CPU
Co-axial cable BNC IRIG-B output

CPU
BNC IRIG-B output Co-axial cable
Co-axial cable

MM fiber
Tx1 10Base-FL NORMAL

9G
optic cable

COM1
Rx1 Shielded twisted-pairs
D1a +
RS485

9S
10Base-T ―
Shielded twisted-pairs D2a COM2
+

Ground at
D1a
D2a
D3a

COMMON
RS485
COM2
Ground at
remote
device
D3a
D4b
D4a
COMMON
+
― IRIG-B
3
remote D4b + input
device ― BNC
D4a IRIG-B
Co-axial cable
input

CPU
BNC BNC IRIG-B output
Co-axial cable Co-axial cable

CPU
BNC IRIG-B output
Co-axial cable

MM fiber SM fiber
Tx1 10Base-FL NORMAL 100Base-FL NORMAL COM1
9H

9L
optic cable Rx1 optic cable
COM1

Tx2
Rx2 10Base-F ALTERNATE D1a +
RS485
D2a ―
Shielded 10Base-T
COM2
twisted-pairs Ground at D3a COMMON
D1a + remote D4b +
RS485 device
D2a ― D4a ― IRIG-B
COM2
Ground at D3a COMMON input
remote BNC
D4b + Co-axial cable
device
D4a ― IRIG-B

CPU
BNC IRIG-B output
input
BNC Co-axial cable
Co-axial cable
CPU

BNC IRIG-B output


Co-axial cable

MM fiber
Tx1 100Base-FL NORMAL COM1 SM fiber optic cable 100Base-FL NORMAL

9M
COM1
9J

optic cable Rx1

D1a + 100Base-F ALTERNATE


RS485 Shielded twisted-pairs
D2a ―
COM2 D1a +
Ground at D3a COMMON RS485
remote D2a ―
D4b + COM2
device
― IRIG-B
Ground at D3a COMMON
D4a remote
input D4b +
device
BNC D4a ― IRIG-B
Co-axial cable input
CPU

IRIG-B output BNC


BNC
Co-axial cable
Co-axial cable

CPU
BNC IRIG-B output
Co-axial cable
842765A7.CDR

Figure 3–25: CPU MODULE COMMUNICATIONS WIRING

b) RS485 PORTS
RS485 data transmission and reception are accomplished over a single twisted pair with transmit and receive data alternat-
ing over the same two wires. Through the use of these ports, continuous monitoring and control from a remote computer,
SCADA system or PLC is possible.
To minimize errors from noise, the use of shielded twisted pair wire is recommended. Correct polarity must also be
observed. For instance, the relays must be connected with all RS485 “+” terminals connected together, and all RS485 “–”
terminals connected together. The COM terminal should be connected to the common wire inside the shield, when pro-
vided. To avoid loop currents, the shield should be grounded at one point only. Each relay should also be daisy chained to
the next one in the link. A maximum of 32 relays can be connected in this manner without exceeding driver capability. For
larger systems, additional serial channels must be added. It is also possible to use commercially available repeaters to
increase the number of relays on a single channel to more than 32. Star or stub connections should be avoided entirely.
To minimize errors from noise, the use of shielded twisted pair wire is recommended. Correct polarity must also be
observed. For instance, the relays must be connected with all RS485 “+” terminals connected together, and all RS485 “–”
terminals connected together. Though data is transmitted over a two-wire twisted pair, all RS485 devices require a shared

GE Multilin G60 Generator Protection System 3-25


3.2 WIRING 3 HARDWARE

reference, or common voltage. This common voltage is implied to be a power supply common. Some systems allow the
shield (drain wire) to be used as common wire and to connect directly to the G60 COM terminal (#3); others function cor-
rectly only if the common wire is connected to the G60 COM terminal, but insulated from the shield.
To avoid loop currents, the shield should be grounded at only one point. If other system considerations require the shield to
be grounded at more than one point, install resistors (typically 100 ohms) between the shield and ground at each grounding
point. Each relay should also be daisy-chained to the next one in the link. A maximum of 32 relays can be connected in this
manner without exceeding driver capability. For larger systems, additional serial channels must be added. It is also possible
to use commercially available repeaters to have more than 32 relays on a single channel. Star or stub connections should
be avoided entirely.
Lightning strikes and ground surge currents can cause large momentary voltage differences between remote ends of the
communication link. For this reason, surge protection devices are internally provided at both communication ports. An iso-
lated power supply with an optocoupled data interface also acts to reduce noise coupling. To ensure maximum reliability, all
equipment should have similar transient protection devices installed.
3 Both ends of the RS485 circuit should also be terminated with an impedance as shown below.

Figure 3–26: RS485 SERIAL CONNECTION

3-26 G60 Generator Protection System GE Multilin


3 HARDWARE 3.2 WIRING

c) 10BASE-FL AND 100BASE-FX FIBER OPTIC PORTS


ENSURE THE DUST COVERS ARE INSTALLED WHEN THE FIBER IS NOT IN USE. DIRTY OR SCRATCHED
CONNECTORS CAN LEAD TO HIGH LOSSES ON A FIBER LINK.
CAUTION
OBSERVING ANY FIBER TRANSMITTER OUTPUT MAY CAUSE INJURY TO THE EYE.

CAUTION

The fiber optic communication ports allow for fast and efficient communications between relays at 10 Mbps or 100 Mbps.
Optical fiber may be connected to the relay supporting a wavelength of 820 nm in multi-mode or 1310 nm in multi-mode
and single-mode. The 10 Mbps rate is available for CPU modules 9G and 9H; 100Mbps is available for modules 9H, 9J, 9K,
9L, 9M, 9N, 9P, and 9R. The 9H, 9K, 9M, and 9R modules have a second pair of identical optical fiber transmitter and
receiver for redundancy.
The optical fiber sizes supported include 50/125 µm, 62.5/125 µm and 100/140 µm for 10 Mbps. The fiber optic port is
designed such that the response times will not vary for any core that is 100 µm or less in diameter, 62.5 µm for 100 Mbps. 3
For optical power budgeting, splices are required every 1 km for the transmitter/receiver pair. When splicing optical fibers,
the diameter and numerical aperture of each fiber must be the same. In order to engage or disengage the ST type connec-
tor, only a quarter turn of the coupling is required.

GE Multilin G60 Generator Protection System 3-27


3.2 WIRING 3 HARDWARE

3.2.10 IRIG-B

IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices within
1 millisecond. The IRIG time code formats are serial, width-modulated codes which can be either DC level shifted or ampli-
tude modulated (AM). Third party equipment is available for generating the IRIG-B signal; this equipment may use a GPS
satellite system to obtain the time reference so that devices at different geographic locations can also be synchronized.

GPS SATELLITE SYSTEM


GPS CONNECTION
OPTIONAL
RELAY
3 4B IRIG-B(+)
4A IRIG-B(-)
IRIG-B
RG58/59 COAXIAL CABLE RECEIVER
TIME CODE
GENERATOR + BNC (IN)
(DC SHIFT OR
AMPLITUDE MODULATED
SIGNAL CAN BE USED)
-
BNC (OUT) REPEATER

TO OTHER DEVICES
(DC-SHIFT ONLY)
827756A5.CDR

Figure 3–27: IRIG-B CONNECTION


The IRIG-B repeater provides an amplified DC-shift IRIG-B signal to other equipment. By using one IRIG-B serial connec-
tion, several UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal
even when a relay in the series is powered down.

Figure 3–28: IRIG-B REPEATER


Using an amplitude modulated receiver will cause errors up to 1 ms in event time-stamping.

NOTE

Using an amplitude modulated receiver will also cause errors of up to 1 ms in metered synchrophasor values.
Using the IRIG-B repeater function in conjunction with synchrophasors is not recommended, as the repeater adds
NOTE a 40 μs delay to the IRIG-B signal. This results in a 1° error for each consecutive device in the string as reported in
synchrophasors.

3-28 G60 Generator Protection System GE Multilin


3 HARDWARE 3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES

3.3DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES 3.3.1 DESCRIPTION

The G60 direct inputs and outputs feature makes use of the type 7 series of communications modules. These modules are
also used by the L90 Line Differential Relay for inter-relay communications. The direct input and output feature uses the
communications channels provided by these modules to exchange digital state information between relays. This feature is
available on all UR-series relay models except for the L90 Line Differential relay.
The communications channels are normally connected in a ring configuration as shown below. The transmitter of one mod-
ule is connected to the receiver of the next module. The transmitter of this second module is then connected to the receiver
of the next module in the ring. This is continued to form a communications ring. The figure below illustrates a ring of four
UR-series relays with the following connections: UR1-Tx to UR2-Rx, UR2-Tx to UR3-Rx, UR3-Tx to UR4-Rx, and UR4-Tx
to UR1-Rx. A maximum of sixteen (16) UR-series relays can be connected in a single ring

Tx
UR #1
Rx 3
Tx
UR #2
Rx

Tx
UR #3
Rx

Tx
UR #4
Rx
842006A1.CDR

Figure 3–29: DIRECT INPUT AND OUTPUT SINGLE CHANNEL CONNECTION


The interconnection for dual-channel Type 7 communications modules is shown below. Two channel modules allow for a
redundant ring configuration. That is, two rings can be created to provide an additional independent data path. The required
connections are: UR1-Tx1 to UR2-Rx1, UR2-Tx1 to UR3-Rx1, UR3-Tx1 to UR4-Rx1, and UR4-Tx1 to UR1-Rx1 for the first
ring; and UR1-Tx2 to UR4-Rx2, UR4-Tx2 to UR3-Rx2, UR3-Tx2 to UR2-Rx2, and UR2-Tx2 to UR1-Rx2 for the second
ring.
Tx1

Rx1
UR #1
Tx2

Rx2

Tx1

Rx1
UR #2
Tx2

Rx2

Tx1

Rx1
UR #3
Tx2

Rx2

Tx1

Rx1
UR #4
Tx2

Rx2
842007A1.CDR

Figure 3–30: DIRECT INPUT AND OUTPUT DUAL CHANNEL CONNECTION


The following diagram shows the connection for three UR-series relays using two independent communication channels.
UR1 and UR3 have single type 7 communication modules; UR2 has a dual-channel module. The two communication chan-
nels can be of different types, depending on the Type 7 modules used. To allow the direct input and output data to cross-
over from channel 1 to channel 2 on UR2, the DIRECT I/O CHANNEL CROSSOVER setting should be “Enabled” on UR2. This
forces UR2 to forward messages received on Rx1 out Tx2, and messages received on Rx2 out Tx1.

GE Multilin G60 Generator Protection System 3-29


3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES 3 HARDWARE

Tx
UR #1
Rx

Channel #1

Tx1

Rx1
UR #2
Tx2

Rx2

Channel #2

Tx
3 UR #3
Rx
842013A1.CDR

Figure 3–31: DIRECT INPUT AND OUTPUT SINGLE/DUAL CHANNEL COMBINATION CONNECTION
The interconnection requirements are described in further detail in this section for each specific variation of type 7 commu-
nications module. These modules are listed in the following table. All fiber modules use ST type connectors.
Not all the direct input and output communications modules may be applicable to the G60 relay. Only the modules
specified in the order codes are available as direct input and output communications modules.
NOTE

Table 3–4: CHANNEL COMMUNICATION OPTIONS (Sheet 1 of 2)


MODULE SPECIFICATION
2A C37.94SM, 1300 nm, single-mode, ELED, 1 channel single-mode
2B C37.94SM, 1300 nm, single-mode, ELED, 2 channel single-mode
2E Bi-phase, 1 channel
2F Bi-phase, 2 channel
2G IEEE C37.94, 820 nm, 128 kbps, multi-mode, LED, 1 channel
2H IEEE C37.94, 820 nm, 128 kbps, multi-mode, LED, 2 channels
2S Six-port managed Ethernet switch with high voltage power supply
2T Six-port managed Ethernet switch with low voltage power supply
72 1550 nm, single-mode, laser, 1 channel
73 1550 nm, single-mode, laser, 2 channels
74 Channel 1 - RS422; channel 2 - 1550 nm, single-mode, laser
75 Channel 1 - G.703; channel 2 - 1550 nm, single-mode, laser
76 IEEE C37.94, 820 nm, 64 kbps, multi-mode, LED, 1 channel
77 IEEE C37.94, 820 nm, 64 kbps, multi-mode, LED, 2 channels
7A 820 nm, multi-mode, LED, 1 channel
7B 1300 nm, multi-mode, LED, 1 channel
7C 1300 nm, single-mode, ELED, 1 channel
7D 1300 nm, single-mode, laser, 1 channel
7E Channel 1: G.703, Channel 2: 820 nm, multi-mode
7F Channel 1: G.703, Channel 2: 1300 nm, multi-mode
7G Channel 1: G.703, Channel 2: 1300 nm, single-mode ELED
7H 820 nm, multi-mode, LED, 2 channels
7I 1300 nm, multi-mode, LED, 2 channels
7J 1300 nm, single-mode, ELED, 2 channels
7K 1300 nm, single-mode, LASER, 2 channels
7L Channel 1: RS422, channel: 820 nm, multi-mode, LED
7M Channel 1: RS422, channel 2: 1300 nm, multi-mode, LED

3-30 G60 Generator Protection System GE Multilin


3 HARDWARE 3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES

Table 3–4: CHANNEL COMMUNICATION OPTIONS (Sheet 2 of 2)


MODULE SPECIFICATION
7N Channel 1: RS422, channel 2: 1300 nm, single-mode, ELED
7P Channel 1: RS422, channel 2: 1300 nm, single-mode, laser
7Q Channel 1: G.703, channel 2: 1300 nm, single-mode, laser
7R G.703, 1 channel
7S G.703, 2 channels
7T RS422, 1 channel
7V RS422, 2 channels, 2 clock inputs
7W RS422, 2 channels

OBSERVING ANY FIBER TRANSMITTER OUTPUT MAY CAUSE INJURY TO THE EYE.

CAUTION
3.3.2 FIBER: LED AND ELED TRANSMITTERS
3
The following figure shows the configuration for the 7A, 7B, 7C, 7H, 7I, and 7J fiber-only modules.
Module: 7A / 7B / 7C 7H / 7I / 7J
Connection Location: Slot X Slot X

RX1 RX1

TX1 TX1

RX2

TX2

1 Channel 2 Channels 831719A2.CDR

Figure 3–32: LED AND ELED FIBER MODULES

3.3.3 FIBER-LASER TRANSMITTERS

The following figure shows the configuration for the 72, 73, 7D, and 7K fiber-laser module.

Module: 72/ 7D 73/ 7K


Connection Location: Slot X Slot X

TX1 TX1

RX1 RX1

TX2

RX2

1 Channel 2 Channels 831720A3.CDR

Figure 3–33: LASER FIBER MODULES


When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maxi-
mum optical input power to the receiver.
WARNING

GE Multilin G60 Generator Protection System 3-31


3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES 3 HARDWARE

3.3.4 G.703 INTERFACE

a) DESCRIPTION
The following figure shows the 64K ITU G.703 co-directional interface configuration.
The G.703 module is fixed at 64 kbps. The SETTINGS Ö PRODUCT SETUP ÖØ DIRECT I/O ÖØ DIRECT I/O DATA RATE
setting is not applicable to this module.
NOTE

AWG 24 twisted shielded pair is recommended for external connections, with the shield grounded only at one end. Con-
necting the shield to pin X1a or X6a grounds the shield since these pins are internally connected to ground. Thus, if pin X1a
or X6a is used, do not ground at the other end. This interface module is protected by surge suppression devices.

Shield X 1a
3
7S
Tx – X 1b
G.703
channel 1 Rx – X 2a
Inter-relay communications Tx + X 2b
Rx + X 3a
Surge X 3b
Shield X 6a
Tx – X 6b
G.703
channel 2
Rx – X 7a
Tx + X 7b
Rx + X 8a
Surge X 8b
842773A2.CDR

Figure 3–34: G.703 INTERFACE CONFIGURATION


The following figure shows the typical pin interconnection between two G.703 interfaces. For the actual physical arrange-
ment of these pins, see the Rear terminal assignments section earlier in this chapter. All pin interconnections are to be
maintained for a connection to a multiplexer.
Shld. X 1a X 1a Shld.
7S

7S
Tx - X 1b X 1b Tx -
G.703 G.703
CHANNEL 1
Rx - X 2a X 2a Rx -
CHANNEL 1
Tx + X 2b X 2b Tx +
Rx + X 3a X 3a Rx +
SURGE X 3b X 3b SURGE
Shld. X 6a X 6a Shld.
Tx - X 6b X 6b Tx -
G.703 G.703
Rx - X 7a X 7a Rx -
COMM.

COMM.

CHANNEL 2 CHANNEL 2
Tx + X 7b X 7b Tx +
Rx + X 8a X 8a Rx +
SURGE X 8b X 8b SURGE
831727A3.CDR

Figure 3–35: TYPICAL PIN INTERCONNECTION BETWEEN TWO G.703 INTERFACES


Pin nomenclature may differ from one manufacturer to another. Therefore, it is not uncommon to see pin-
outs numbered TxA, TxB, RxA and RxB. In such cases, it can be assumed that “A” is equivalent to “+” and
NOTE
“B” is equivalent to “–”.

b) G.703 SELECTION SWITCH PROCEDURES


1. Remove the G.703 module (7R or 7S). The ejector/inserter clips located at the top and at the bottom of each module,
must be pulled simultaneously in order to release the module for removal. Before performing this action, control
power must be removed from the relay. The original location of the module should be recorded to help ensure that
the same or replacement module is inserted into the correct slot.
2. Remove the module cover screw.
3. Remove the top cover by sliding it towards the rear and then lift it upwards.
4. Set the timing selection switches (channel 1, channel 2) to the desired timing modes.
5. Replace the top cover and the cover screw.

3-32 G60 Generator Protection System GE Multilin


3 HARDWARE 3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES

6. Re-insert the G.703 module. Take care to ensure that the correct module type is inserted into the correct slot position.
The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged position as
the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the
clips simultaneously. When the clips have locked into position, the module will be fully inserted.

Figure 3–36: G.703 TIMING SELECTION SWITCH SETTING

Table 3–5: G.703 TIMING SELECTIONS


SWITCHES FUNCTION
S1 OFF → octet timing disabled
ON → octet timing 8 kHz
S5 and S6 S5 = OFF and S6 = OFF → loop timing mode
S5 = ON and S6 = OFF → internal timing mode
S5 = OFF and S6 = ON → minimum remote loopback mode
S5 = ON and S6 = ON → dual loopback mode

c) G.703 OCTET TIMING


If octet timing is enabled (on), this 8 kHz signal will be asserted during the violation of bit 8 (LSB) necessary for connecting
to higher order systems. When G60s are connected back to back, octet timing should be disabled (off).

d) G.703 TIMING MODES


There are two timing modes for the G.703 module: internal timing mode and loop timing mode (default).
• Internal Timing Mode: The system clock is generated internally. Therefore, the G.703 timing selection should be in
the internal timing mode for back-to-back (UR-to-UR) connections. For back-to-back connections, set for octet timing
(S1 = OFF) and timing mode to internal timing (S5 = ON and S6 = OFF).
• Loop Timing Mode: The system clock is derived from the received line signal. Therefore, the G.703 timing selection
should be in loop timing mode for connections to higher order systems. For connection to a higher order system (UR-
to-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 =
OFF).

GE Multilin G60 Generator Protection System 3-33


3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES 3 HARDWARE

The switch settings for the internal and loop timing modes are shown below:

842752A1.CDR

e) G.703 TEST MODES

3 In minimum remote loopback mode, the multiplexer is enabled to return the data from the external interface without any
processing to assist in diagnosing G.703 line-side problems irrespective of clock rate. Data enters from the G.703 inputs,
passes through the data stabilization latch which also restores the proper signal polarity, passes through the multiplexer
and then returns to the transmitter. The differential received data is processed and passed to the G.703 transmitter module
after which point the data is discarded. The G.703 receiver module is fully functional and continues to process data and
passes it to the differential Manchester transmitter module. Since timing is returned as it is received, the timing source is
expected to be from the G.703 line side of the interface.

DMR = Differential Manchester Receiver


DMR G7X DMX = Differential Manchester Transmitter
G7X = G.703 Transmitter
G7R = G.703 Receiver

DMX G7R
842774A1.CDR

Figure 3–37: G.703 MINIMUM REMOTE LOOPBACK MODE


In dual loopback mode, the multiplexers are active and the functions of the circuit are divided into two with each receiver/
transmitter pair linked together to deconstruct and then reconstruct their respective signals. Differential Manchester data
enters the Differential Manchester receiver module and then is returned to the differential Manchester transmitter module.
Likewise, G.703 data enters the G.703 receiver module and is passed through to the G.703 transmitter module to be
returned as G.703 data. Because of the complete split in the communications path and because, in each case, the clocks
are extracted and reconstructed with the outgoing data, in this mode there must be two independent sources of timing. One
source lies on the G.703 line side of the interface while the other lies on the differential Manchester side of the interface.

DMR = Differential Manchester Receiver


DMR G7X DMX = Differential Manchester Transmitter
G7X = G.703 Transmitter
G7R = G.703 Receiver

DMX G7R
842775A1.CDR

Figure 3–38: G.703 DUAL LOOPBACK MODE

3-34 G60 Generator Protection System GE Multilin


3 HARDWARE 3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES

3.3.5 RS422 INTERFACE

a) DESCRIPTION
There are two RS422 inter-relay communications modules available: single-channel RS422 (module 7T) and dual-channel
RS422 (module 7W). The modules can be configured to run at 64 kbps or 128 kbps. AWG 24 twisted shielded pair cable is
recommended for external connections. These modules are protected by optically-isolated surge suppression devices.
The shield pins (6a and 7b) are internally connected to the ground pin (8a). Proper shield termination is as follows:
• Site 1: Terminate shield to pins 6a or 7b or both.
• Site 2: Terminate shield to COM pin 2b.
The clock terminating impedance should match the impedance of the line.
Single-channel RS422 module Dual-channel RS422 module
~ 3b Tx – ~ 3b Tx – 3

7W
7T
~ 3a Rx – ~ 3a Rx –
RS422
~ 2a Tx + RS422 ~ 2a Tx +
channel 1

Inter-relay comms.
~ 4b Rx + ~ 4b Rx +
~ 6a Shield ~ 6a Shield

Inter-relay communications
~ 7a ~ 5b Tx –
Clock
~ 8b ~ 5a Rx –
RS422
~ 2b COM ~ 4a Tx +
channel 2
~ 8a Surge ~ 6b Rx +
~ 7b Shield
~ 7a
Clock
~ 8b
~ 2b COM

~ indicates the slot position ~ 8a Surge


842776A3.CDR

Figure 3–39: RS422 INTERFACE CONNECTIONS


The following figure shows the typical pin interconnection between two single-channel RS422 interfaces installed in slot W.
All pin interconnections are to be maintained for a connection to a multiplexer.

Figure 3–40: TYPICAL PIN INTERCONNECTION BETWEEN TWO RS422 INTERFACES

b) TWO-CHANNEL APPLICATION VIA MULTIPLEXERS


The RS422 interface may be used for single channel or two channel applications over SONET/SDH or multiplexed sys-
tems. When used in single-channel applications, the RS422 interface links to higher order systems in a typical fashion
observing transmit (Tx), receive (Rx), and send timing (ST) connections. However, when used in two-channel applications,
certain criteria must be followed since there is one clock input for the two RS422 channels. The system will function cor-
rectly if the following connections are observed and your data module has a terminal timing feature. Terminal timing is a
common feature to most synchronous data units that allows the module to accept timing from an external source. Using the
terminal timing feature, two channel applications can be achieved if these connections are followed: The send timing out-
puts from the multiplexer (data module 1), will connect to the clock inputs of the UR–RS422 interface in the usual fashion.
In addition, the send timing outputs of data module 1 will also be paralleled to the terminal timing inputs of data module 2.
By using this configuration, the timing for both data modules and both UR–RS422 channels will be derived from a single
clock source. As a result, data sampling for both of the UR–RS422 channels will be synchronized via the send timing leads
on data module 1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the
G.703 interface is a viable option that does not impose timing restrictions.

GE Multilin G60 Generator Protection System 3-35


3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES 3 HARDWARE

Data module 1
Signal name
Tx1(+) W 2a SD(A) - Send data

7W
Tx1(-) W 3b SD(B) - Send data
RS422
CHANNEL 1
Rx1(+) W 4b RD(A) - Received data
Rx1(-) W 3a RD(B) - Received data
Shld. W 6a RS(A) - Request to send (RTS)

INTER-RELAY COMMUNICATIONS
+ W 7a RS(B) - Request to send (RTS)
CLOCK
– W 8b RT(A) - Receive timing
Tx2(+) W 4a RT(B) - Receive timing
Tx2(-) W 5b CS(A) - Clear To send
RS422
CHANNEL 2
Rx2(+) W 6b CS(B) - Clear To send
Rx2(-) W 5a Local loopback
Shld. W 7b Remote loopback
com W 2b Signal ground
SURGE W 8a ST(A) - Send timing
ST(B) - Send timing

3 Data module 2
Signal name
TT(A) - Terminal timing
TT(B) - Terminal timing
SD(A) - Send data
SD(B) - Send data
RD(A) - Received data
RD(B) - Received data
RS(A) - Request to send (RTS)
RS(B) - Request to send (RTS)
CS(A) - Clear To send
CS(B) - Clear To send
Local loopback
Remote loopback
Signal ground
ST(A) - Send timing
ST(B) - Send timing

831022A3.CDR

Figure 3–41: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, 3-TERMINAL APPLICATION


Data module 1 provides timing to the G60 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides
timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been
omitted in the figure above since they may vary depending on the manufacturer.

c) TRANSMIT TIMING
The RS422 interface accepts one clock input for transmit timing. It is important that the rising edge of the 64 kHz transmit
timing clock of the multiplexer interface is sampling the data in the center of the transmit data window. Therefore, it is impor-
tant to confirm clock and data transitions to ensure proper system operation. For example, the following figure shows the
positive edge of the Tx clock in the center of the Tx data bit.

Tx Clock

Tx Data

Figure 3–42: CLOCK AND DATA TRANSITIONS

d) RECEIVE TIMING
The RS422 interface utilizes NRZI-MARK modulation code and; therefore, does not rely on an Rx clock to recapture data.
NRZI-MARK is an edge-type, invertible, self-clocking code.

3-36 G60 Generator Protection System GE Multilin


3 HARDWARE 3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES

To recover the Rx clock from the data-stream, an integrated DPLL (digital phase lock loop) circuit is utilized. The DPLL is
driven by an internal clock, which is 16-times over-sampled, and uses this clock along with the data-stream to generate a
data clock that can be used as the SCC (serial communication controller) receive clock.

3.3.6 RS422 AND FIBER INTERFACE

The following figure shows the combined RS422 plus Fiber interface configuration at 64K baud. The 7L, 7M, 7N, 7P, and 74
modules are used in two-terminal with a redundant channel or three-terminal configurations where channel 1 is employed
via the RS422 interface (possibly with a multiplexer) and channel 2 via direct fiber.
AWG 24 twisted shielded pair is recommended for external RS422 connections and the shield should be grounded only at
one end. For the direct fiber channel, power budget issues should be addressed properly.
When using a LASER Interface, attenuators may be necessary to ensure that you do not exceed maximum

WARNING
optical input power to the receiver.
3
~ 1a Clock

7L, 7M, 7N, 7P, 74


~ 1b (channel 1)
~ 2b COM
~ 2a Tx1 +
~ 3a Rx1 –
RS422
~ 3b Tx1 –
channel 1

Inter-relay comms.
~ 4b Rx1 +
~ 6a Shield
Fiber
Tx2 Rx2 channel 2
~ 8a Surge
842777A1.CDR

Figure 3–43: RS422 AND FIBER INTERFACE CONNECTION


Connections shown above are for multiplexers configured as DCE (data communications equipment) units.

3.3.7 G.703 AND FIBER INTERFACE

The figure below shows the combined G.703 plus fiber interface configuration at 64 kbps. The 7E, 7F, 7G, 7Q, and 75 mod-
ules are used in configurations where channel 1 is employed via the G.703 interface (possibly with a multiplexer) and chan-
nel 2 via direct fiber. AWG 24 twisted shielded pair is recommended for external G.703 connections connecting the shield to
pin 1a at one end only. For the direct fiber channel, power budget issues should be addressed properly. See previous sec-
tions for additional details on the G.703 and fiber interfaces.
When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maxi-
mum optical input power to the receiver.
WARNING

~ 1a
7E, 7F, 7G,
7Q,75

Shield
~ 1b Tx –
G.703
~ 2a Rx –
channel 1
~ 2b Tx +
communications

~ 3a Rx +
~ 3b Surge
Inter-relay

Tx2 Fiber
Rx2 channel 2

842778A1.CDR

Figure 3–44: G.703 AND FIBER INTERFACE CONNECTION

GE Multilin G60 Generator Protection System 3-37


3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES 3 HARDWARE

3.3.8 IEEE C37.94 INTERFACE

The UR-series IEEE C37.94 communication modules (modules types 2G, 2H, 76, and 77) are designed to interface with
IEEE C37.94 compliant digital multiplexers or an IEEE C37.94 compliant interface converter for use with direct input and
output applications for firmware revisions 3.30 and higher. The IEEE C37.94 standard defines a point-to-point optical link
for synchronous data between a multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard
provides for speeds up to 64n kbps, where n = 1, 2,…, 12. The UR-series C37.94 communication modules are either
64 kbps (with n fixed at 1) for 128 kbps (with n fixed at 2). The frame is a valid International Telecommunications Union
(ITU-T) recommended G.704 pattern from the standpoint of framing and data rate. The frame is 256 bits and is repeated at
a frame rate of 8000 Hz, with a resultant bit rate of 2048 kbps.
The specifications for the module are as follows:.
• IEEE standard: C37.94 for 1 × 128 kbps optical fiber interface (for 2G and 2H modules) or C37.94 for 2 × 64 kbps opti-
3 •
cal fiber interface (for 76 and 77 modules).
Fiber optic cable type: 50 mm or 62.5 mm core diameter optical fiber.
• Fiber optic mode: multi-mode.
• Fiber optic cable length: up to 2 km.
• Fiber optic connector: type ST.
• Wavelength: 830 ±40 nm.
• Connection: as per all fiber optic connections, a Tx to Rx connection is required.
The UR-series C37.94 communication module can be connected directly to any compliant digital multiplexer that supports
the IEEE C37.94 standard as shown below.

The UR-series C37.94 communication module can be connected to the electrical interface (G.703, RS422, or X.21) of a
non-compliant digital multiplexer via an optical-to-electrical interface converter that supports the IEEE C37.94 standard, as
shown below.

The UR-series C37.94 communication module has six (6) switches that are used to set the clock configuration. The func-
tions of these control switches is shown below.

842753A1.CDR

3-38 G60 Generator Protection System GE Multilin


3 HARDWARE 3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES

For the internal timing mode, the system clock is generated internally. therefore, the timing switch selection should be inter-
nal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.
For the looped timing mode, the system clock is derived from the received line signal. Therefore, the timing selection
should be in loop timing mode for connections to higher order systems.
The IEEE C37.94 communications module cover removal procedure is as follows:
1. Remove the IEEE C37.94 module (type 2G, 2H, 76 or 77 module):
The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order
to release the module for removal. Before performing this action, control power must be removed from the relay.
The original location of the module should be recorded to help ensure that the same or replacement module is inserted
into the correct slot.
2. Remove the module cover screw.
3. Remove the top cover by sliding it towards the rear and then lift it upwards. 3
4. Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above).
5. Replace the top cover and the cover screw.
6. Re-insert the IEEE C37.94 module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged posi-
tion as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.

Figure 3–45: IEEE C37.94 TIMING SELECTION SWITCH SETTING

GE Multilin G60 Generator Protection System 3-39


3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES 3 HARDWARE

3.3.9 C37.94SM INTERFACE

The UR-series C37.94SM communication modules (2A and 2B) are designed to interface with modified IEEE C37.94 com-
pliant digital multiplexers or IEEE C37.94 compliant interface converters that have been converted from 820 nm multi-mode
fiber optics to 1300 nm ELED single-mode fiber optics. The IEEE C37.94 standard defines a point-to-point optical link for
synchronous data between a multiplexer and a teleprotection device. This data is typically 64 kbps, but the standard pro-
vides for speeds up to 64n kbps, where n = 1, 2,…, 12. The UR-series C37.94SM communication module is 64 kbps only
with n fixed at 1. The frame is a valid International Telecommunications Union (ITU-T) recommended G.704 pattern from
the standpoint of framing and data rate. The frame is 256 bits and is repeated at a frame rate of 8000 Hz, with a resultant bit
rate of 2048 kbps.
The specifications for the module are as follows:
• Emulated IEEE standard: emulates C37.94 for 1 × 64 kbps optical fiber interface (modules set to n = 1 or 64 kbps).
3 • Fiber optic cable type: 9/125 μm core diameter optical fiber.
• Fiber optic mode: single-mode, ELED compatible with HP HFBR-1315T transmitter and HP HFBR-2316T receiver.
• Fiber optic cable length: up to 10 km.
• Fiber optic connector: type ST.
• Wavelength: 1300 ±40 nm.
• Connection: as per all fiber optic connections, a Tx to Rx connection is required.
The UR-series C37.94SM communication module can be connected directly to any compliant digital multiplexer that sup-
ports C37.94SM as shown below.

It can also can be connected directly to any other UR-series relay with a C37.94SM module as shown below.

The UR-series C37.94SM communication module has six (6) switches that are used to set the clock configuration. The
functions of these control switches is shown below.

842753A1.CDR

For the internal timing mode, the system clock is generated internally. Therefore, the timing switch selection should be
internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured.

3-40 G60 Generator Protection System GE Multilin


3 HARDWARE 3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS MODULES

For the looped timing mode, the system clock is derived from the received line signal. Therefore, the timing selection
should be in loop timing mode for connections to higher order systems.
The C37.94SM communications module cover removal procedure is as follows:
1. Remove the C37.94SM module (modules 2A or 2B):
The ejector/inserter clips located at the top and at the bottom of each module, must be pulled simultaneously in order
to release the module for removal. Before performing this action, control power must be removed from the relay.
The original location of the module should be recorded to help ensure that the same or replacement module is inserted
into the correct slot.
2. Remove the module cover screw.
3. Remove the top cover by sliding it towards the rear and then lift it upwards.
4. Set the timing selection switches (channel 1, channel 2) to the desired timing modes (see description above).
5. Replace the top cover and the cover screw. 3
6. Re-insert the C37.94SM module. Take care to ensure that the correct module type is inserted into the correct slot
position. The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged posi-
tion as the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis,
engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted.

Figure 3–46: C37.94SM TIMING SELECTION SWITCH SETTING

GE Multilin G60 Generator Protection System 3-41


3.4 FIELD AND STATOR GROUND MODULES 3 HARDWARE

3.4FIELD AND STATOR GROUND MODULES 3.4.1 OVERVIEW

The field ground protection modules are used in the following protection sytems.
• Field low voltage protection system (order code GPM-F-L) for voltages up to 600 V DC.
• Field high voltage protection system (order code GPM-F-H) for voltages greater than 600 V DC.
• Stator protection system (order code GPM-S).
These systems are illustrated below for comparative purposes in the following figure.

GPM-F-L
Field ground
GPM-F-L: Field ground low-voltage protection module
low-voltage
3 protection system

GPM-F-HM: Field ground high-voltage protection module

GPM-F-H
Field ground
high-voltage
protection system

GPM-F-R: Field ground protection high-voltage resistor box

GPM-S-G: Stator ground 20 Hz generator module

GPM-S-B: Stator ground band pass filter module


GPM-S
Stator ground
protection system

204-SD-43737: Stator ground protection CT

830755A2.CDR

Figure 3–47: GENERATOR GROUND PROTECTION COMPONENTS

3-42 G60 Generator Protection System GE Multilin


3 HARDWARE 3.4 FIELD AND STATOR GROUND MODULES

3.4.2 FIELD GROUND LOW-VOLTAGE PROTECTION SYSTEM

The field ground low voltage protection system consists of one module: the field ground protection low-voltage module
(GPM-F-L). The mounting and dimension diagrams are shown below (all dimensions are in inches).

10.270

10.142

2.160

12.270 9.090
830017A1.CDR

Figure 3–48: DIMENSIONS FOR GPM-F-L PANEL-MOUNTED UNIT

1.000

10.072
7.574

11.770 10.142

2.306

12.270 9.090
830016A1.CDR

Figure 3–49: DIMENSIONS FOR GPM-F-L WALL-MOUNTED UNIT

GE Multilin G60 Generator Protection System 3-43


3.4 FIELD AND STATOR GROUND MODULES 3 HARDWARE

Nut Nylock
3 Screw 10-32×3/8”
Zinc 10-32
GE P/N 1422-1032
QTY: 4
Pan HD Zinc
Washer flat Zinc #10
GE P/N 1410-0006
GE P/N 1430-0006
QTY: 4
QTY: 4

Ø 0.220 10.813

1.000

2.200

0.600

11.520 830018A1.CDR

Figure 3–50: MOUNTING DIAGRAM FOR GPM-F-L PANEL-MOUNTED UNIT

3-44 G60 Generator Protection System GE Multilin


3 HARDWARE 3.4 FIELD AND STATOR GROUND MODULES

Ø 0.220
7.574 4×

11.520
3
Nut Nylock
Zinc 10-32
GE P/N 1422-1032
QTY: 4
Washer flat Zinc #10
GE P/N 1430-0006
QTY: 4

Screw 10-32×3/8”, Pan HD Zinc


GE P/N 1410-0006, QTY: 4 830013A1.CDR

Figure 3–51: MOUNTING DIAGRAM FOR GPM-F-L WALL-MOUNTED UNIT


There are three connectors on the field protection low-voltage module as shown below.

Connector A Connector B Connector C

2 4 6 8 10 12

1 2 3 4
123 1 3 5 7 9 11

830023A1.CDR

Figure 3–52: REAR VIEW OF GPM-F-L MODULE SHOWING TERMINAL BLOCKS


The pin assignments are described in the following tables.

Table 3–6: GPM-F-L PIN ASSIGNMENTS FOR CONNECTOR A


PIN LABEL DEFINITION
1 L(+) AC-L (DC+)
2 N(–) AC-N (DC–)
3 GND Ground

GE Multilin G60 Generator Protection System 3-45


3.4 FIELD AND STATOR GROUND MODULES 3 HARDWARE

Table 3–7: GPM-F-L PIN ASSIGNMENTS FOR CONNECTOR B


PIN LABEL DEFINITION
1 CH1(+) RS485 channel 1 positive
2 CH1(–) RS485 channel 1 negative
3 COM RS485 common
4 CH2(+) RS485 channel 2 positive
5 CH2(–) RS485 channel 2 negative
6 IN3 Contact input 3
7 IN2 Contact input 2
8 IN1 Contact input 1
9 COM Contact input common
3 10 NC Relay NC (normally closed)
11 COM Relay common
12 NO Relay NO (normally open)

Table 3–8: GPM-F-L PIN ASSIGNMENTS FOR CONNECTOR C


PIN LABEL DEFINITION
1 FGND Field ground
2 F1 Injection to excitation positive
3 F(–) Injection to excitation negative / excitation negative
4 F(+) Excitation positive

The following diagram illustrates how to wire the GPM-F-L module for both single-point injection and double-point injection.

C1 C1

F1 F1
Field ground C2 Field ground C2
protection protection
module module F(–)
GPM-F-HM C3 GPM-F-HM C3
– –
F(+)
C4 EX C4 EX
+ +
Connection for Connection for
single-point injection double-point injection
830759A2.CDR

Figure 3–53: CONNECTING THE FIELD GROUND PROTECTION MODULE

3.4.3 FIELD GROUND HIGH-VOLTAGE PROTECTION SYSTEM

The field ground high-voltage protection system consists of two modules: the field ground protection high-voltage module
(GPM-F-HM) and the field ground protection high-voltage resistor box (GPM-F-R). The mounting and dimension diagrams
are shown below (all dimensions are in inches).

3-46 G60 Generator Protection System GE Multilin


3 HARDWARE 3.4 FIELD AND STATOR GROUND MODULES

10.270

10.142

2.160

12.270 9.090
830017A1.CDR

Figure 3–54: DIMENSIONS FOR GPM-F-HM PANEL-MOUNTED UNIT

1.000

10.072
7.574

11.770 10.142

2.306

12.270 9.090
830016A1.CDR

Figure 3–55: DIMENSIONS FOR GPM-F-HM WALL-MOUNTED UNIT

GE Multilin G60 Generator Protection System 3-47


3.4 FIELD AND STATOR GROUND MODULES 3 HARDWARE

7.000

6.500

5.875
5.000

3.500

7.000

2.500
2.750

8.600
830753A1.CDR

Figure 3–56: DIMENSIONS FOR GPM-F-R HIGH-VOLTAGE RESISTOR BOX

3-48 G60 Generator Protection System GE Multilin


3 HARDWARE 3.4 FIELD AND STATOR GROUND MODULES

Nut Nylock
Zinc 10-32
GE P/N 1422-1032
3
Screw 10-32×3/8” QTY: 4
Pan HD Zinc
Washer flat Zinc #10
GE P/N 1410-0006
GE P/N 1430-0006
QTY: 4
QTY: 4

Ø 0.220 10.813

1.000

2.200

0.600

11.520 830018A1.CDR

Figure 3–57: MOUNTING DIAGRAM FOR GPM-F-HM PANEL-MOUNTED UNIT

GE Multilin G60 Generator Protection System 3-49


3.4 FIELD AND STATOR GROUND MODULES 3 HARDWARE

Ø 0.220
7.574 4×

3 11.520

Nut Nylock
Zinc 10-32
GE P/N 1422-1032
QTY: 4
Washer flat Zinc #10
GE P/N 1430-0006
QTY: 4

Screw 10-32×3/8”, Pan HD Zinc


GE P/N 1410-0006, QTY: 4 830013A1.CDR

Figure 3–58: MOUNTING DIAGRAM FOR GPM-F-HM WALL-MOUNTED UNIT

Washer flat Zinc #10 Nut Nylock, Zinc 10-32


GE P/N 1430-0006 GE P/N 1422-1032 3.500 Ø 0.220
QTY: 4 QTY: 4

5.938

Screw 10-32×3/8”
Pan HD Zinc, GE P/N 1410-0006, QTY: 4 830019A1.CDR

Figure 3–59: MOUNTING DIAGRAM FOR GPM-F-R HIGH-VOLTAGE RESISTOR BOX


There are three connectors on the field ground protection high-voltage module as shown below.

3-50 G60 Generator Protection System GE Multilin


3 HARDWARE 3.4 FIELD AND STATOR GROUND MODULES

Connector A Connector B Connector C

2 4 6 8 10 12

1 2 3 4
123 1 3 5 7 9 11

830023A1.CDR

Figure 3–60: REAR VIEW OF GPM-F-HM MODULE SHOWING TERMINAL BLOCKS


The pin assignments are described in the following tables.

Table 3–9: GPM-F-HM PIN ASSIGNMENTS FOR CONNECTOR A


PIN LABEL DEFINITION 3
1 L(+) AC-L (DC+)
2 N(–) AC-N (DC–)
3 GND Ground

Table 3–10: GPM-F-HM PIN ASSIGNMENTS FOR CONNECTOR B


PIN LABEL DEFINITION
1 CH1(+) RS485 channel 1 positive
2 CH1(–) RS485 channel 1 negative
3 COM RS485 common
4 CH2(+) RS485 channel 2 positive
5 CH2(–) RS485 channel 2 negative
6 IN3 Contact input 3
7 IN2 Contact input 2
8 IN1 Contact input 1
9 COM Contact input common
10 NC Relay NC (normally closed)
11 COM Relay common
12 NO Relay NO (normally open)

Table 3–11: GPM-F-HM PIN ASSIGNMENTS FOR CONNECTOR C


PIN LABEL DEFINITION
1 FGND Field ground
2 F1 Injection to excitation positive
3 F(–) Injection to excitation negative / excitation negative
4 F(+) Excitation positive

There are three connectors on the field ground protection high-voltage resistor box as shown below.

GE Multilin G60 Generator Protection System 3-51


3.4 FIELD AND STATOR GROUND MODULES 3 HARDWARE

7 6 5 4 3 2 1

Connector A

3 2 1 3 2 1

Connector B Connector C
830026A2.CDR

Figure 3–61: GPM-F-R MODULE SHOWING TERMINAL BLOCKS


The pin assignments are described in the following tables.

Table 3–12: GPM-F-R PIN ASSIGNMENTS FOR CONNECTOR A


PIN LABEL DEFINITION
1 A1 Not used
2 A2 Not used
3 A3 Injection secondary (F1)
4 A4 Not used
5 A5 Excitation secondary negative (F–)
6 A6 Not used
7 A7 Excitation secondary positive (F+)

Table 3–13: GPM-F-R PIN ASSIGNMENTS FOR CONNECTOR B


PIN LABEL DEFINITION
1 B1 Excitation primary positive (F2+)
2 B2 Not used
3 B3 Injection to excitation positive (F2)

Table 3–14: GPM-F-R PIN ASSIGNMENTS FOR CONNECTOR C


PIN LABEL DEFINITION
1 C1 Injection to excitation negative / Excitation primary negative (F2–)
2 C2 Not used
3 C3 Not used

3-52 G60 Generator Protection System GE Multilin


3 HARDWARE 3.4 FIELD AND STATOR GROUND MODULES

The following diagram illustrates how to wire the GPM-F-HM module with the GPM-F-R resistor box for both single-point
injection and double-point injection.

F2+
A1 B1
C1
A2 B2 +
Field ground F2
F1 A3 B3 EX
Field ground C2 protection Connection for
protection high-voltage – single-point
A4
module F– resistor box injection
C3 F2–
GPM-F-HM A5 module C1
GPM-F-R
A6 C2
F+
C4
A7 C3

F2+
3
A1 B1
C1
A2 B2 +
Field ground F2
F1 A3 B3 EX
Field ground C2 protection Connection for
protection high-voltage – double-point
A4
module F– resistor box injection
C3 F2–
GPM-F-HM A5 module C1
GPM-F-R
A6 C2
F+
C4
A7 C3

830758A6.CDR

Figure 3–62: CONNECTING THE FIELD GROUND PROTECTION MODULE TO THE HIGH-VOLTAGE RESISTOR BOX
The connection between F1 (terminal C2) on the GPM-F-HM field ground protection module and terminal A3 on the
GPM-F-R high-voltage resistor box module should be shielded. The length should be kept as short as possible and
NOTE not exceed 10 meters.
The connection between the F+ and F– pair (terminals C3 and C4) on the GPM-F-HM field ground protection mod-
ule and terminals A5 and A7 on the GPM-F-R high-voltage resistor box module should be shielded. The length
NOTE should be kept as short as possible and not exceed 10 meters.
Terminals C1 and C3 must be externally shorted for both single-point and double-point injection.

NOTE

3.4.4 STATOR GROUND PROTECTION SYSTEM

In the 100% stator ground fault protection based on sub-harmonic injection, a 20 Hz voltage is injected to detect ground
faults at any point across 100% of the winding. The stator ground module works in combination the G60 to provide 100%
stator ground fault protection that is operational during generator start-up, running and stopped conditions.
The stator ground protection system consists of three modules: the stator ground protection 20 Hz generator module
(GPM-S-G), the stator ground band pass filter module (GPM-S-B), and the stator ground protection CT (204-SD-43737).
The mounting and dimension diagrams are shown below (all dimensions are in inches).

GE Multilin G60 Generator Protection System 3-53


3.4 FIELD AND STATOR GROUND MODULES 3 HARDWARE

17.760

8.451

5.250

19.160 7.250
830012A2.CDR

Figure 3–63: DIMENSIONS FOR GPM-S-G PANEL-MOUNTED UNIT

18.960

6.250

0.250

830754A2.CDR

Figure 3–64: DIMENSIONS FOR GPM-S-G WALL-MOUNTED UNIT

3-54 G60 Generator Protection System GE Multilin


3 HARDWARE 3.4 FIELD AND STATOR GROUND MODULES

7.500

11.870

8.300 3

7.310

7.869

9.370 830020A1.CDR

Figure 3–65: DIMENSIONS FOR GPM-S-B BAND PASS FILTER MODULE

GE Multilin G60 Generator Protection System 3-55


3.4 FIELD AND STATOR GROUND MODULES 3 HARDWARE

Nut Nylock
Zinc 10-32
GE P/N 1422-1032
QTY: 4

Washer flat Zinc #10


GE P/N 1430-0006
QTY: 4
3
Screw 10-32×3/8”
Pan HD Zinc
GE P/N 1410-0006
QTY: 4

18.710

Ø 0.220

6.250

830021A1.CDR

Figure 3–66: MOUNTING DIAGRAM FOR GPM-S-G PANEL-MOUNTED UNIT

3-56 G60 Generator Protection System GE Multilin


3 HARDWARE 3.4 FIELD AND STATOR GROUND MODULES

Washer flat Zinc #10


GE P/N 1430-0006
QTY: 4

Screw 10-32×3/8”
Pan HD Zinc
GE P/N 1410-0006
QTY: 4

Nut Nylock
Zinc 10-32
GE P/N 1422-1032
3
QTY: 4

18.498

4.000 5.375

18.000 830022A1.CDR

Figure 3–67: MOUNTING DIAGRAM FOR GPM-S-G WALL-MOUNTED UNIT

10.870 Ø 0.220

5.490

Screw 10-32×3/8” Pan HD Zinc


GE P/N 1410-0006, QTY: 4

Washer flat Zinc #10 Nut Nylock Zinc 10-32


GE P/N 1430-0006, QTY: 4 GE P/N 1422-1032, QTY: 4 830015A1.CDR

Figure 3–68: MOUNTING DIAGRAM FOR GPM-S-B BAND PASS FILTER MODULE
There are two connectors on the stator ground protection 20 Hz generator module as shown below.

GE Multilin G60 Generator Protection System 3-57


3.4 FIELD AND STATOR GROUND MODULES 3 HARDWARE

A B

1 3 5 7 9 1 3 5 7 9

2 4 6 8 10 2 4 6 8 10

830025A1.CDR

Figure 3–69: REAR VIEW OF GPM-S-G MODULE SHOWING TERMINAL BLOCKS


The pin assignments for the stator ground 20 Hz generator module are described in the following tables.
3
Table 3–15: GPM-S-G PIN ASSIGNMENTS FOR CONNECTOR A
PIN LABEL DEFINITION
1 A1 Contact input 1
2 A2 Contact input 2
3 A3 Alarm relay NC (normally closed)
4 A4 Not used
5 A5 Output 1
6 A6 Contact input common
7 A7 Alarm relay NO (normally open)
8 A8 Alarm relay common
9 A9 Not used
10 A10 Output 2

Table 3–16: GPM-S-G PIN ASSIGNMENTS FOR CONNECTOR B


PIN LABEL DEFINITION
1 B1 Not used
2 B2 Not used
3 B3 Not used
4 B4 Not used
5 B5 Not used
6 B6 Not used
7 B7 Not used
8 B8 Ground
9 B9 Power neutral / DC negative
10 B10 Power line / DC positive

There are two connectors on the stator ground protection band pass filter module as shown below.

3-58 G60 Generator Protection System GE Multilin


3 HARDWARE 3.4 FIELD AND STATOR GROUND MODULES

1 1
2 2
3 3
4 4
5 5
6 6
7 7

A B
3

830024A2.CDR

Figure 3–70: GPM-S-B MODULE SHOWING TERMINAL BLOCKS


The pin assignments are described in the following tables.

Table 3–17: GPM-S-B PIN ASSIGNMENTS FOR CONNECTOR A


PIN LABEL DEFINITION
1 A1 Input 1
2 A2 Not used
3 A3 Input 2
4 A4 Not used
5 A5 Reserved
6 A6 Divider out
7 A7 Divider low

Table 3–18: GPM-S-B PIN ASSIGNMENTS FOR CONNECTOR B


PIN LABEL DEFINITION
1 B1 Output 1
2 B2 Not used
3 B3 Output 2
4 B4 Not used
5 B5 Reserved
6 B6 Divider high
7 B7 Divider low

The following diagram illustrates how to connect the stator ground 20 Hz generator module with the band pass filter module
where the NGT secondary voltage is less than or equal to 240 V.

GE Multilin G60 Generator Protection System 3-59


3.4 FIELD AND STATOR GROUND MODULES 3 HARDWARE

to G60
A1 auxiliary VT
A2
A3
Stator A4 A1 B1
ground
20 Hz A5 A2 B2
generator Stator ground
A6 A3 band pass B3
module Rn
GPM-S-G A7 A4 filter module B4
GPM-S-B
A8 A5 B5
A9 A6 B6
A10 A7 B7
830756A1.CDR

3 Figure 3–71: STATOR GROUND PROTECTION SYSTEM CONNECTIONS (NGT SECONDARY ≤ 240 V)
The following diagram illustrates how to connect the stator ground 20 Hz generator module with the band pass filter module
where the NGT secondary voltage is greater than 240 V.

A1
A2
A3
Stator A4
ground
20 Hz A5
generator A6
module
GPM-S-G A7
A8 A1 B1
A9 A2 B2
A10 A3 Stator ground B3
band pass Rn
A4 B4
filter module
A5 GPM-S-B B5

to G60 A6 B6
auxiliary VT A7 B7
830757A2.CDR

Figure 3–72: STATOR GROUND PROTECTION SYSTEM CONNECTIONS (NGT SECONDARY > 240 V)

3.4.5 UPGRADING FIRMWARE

a) UPGRADING THE GPM-F FIRMWARE


The following procedure describes how the upgrade the firmware for the GPM-F modules.

3-60 G60 Generator Protection System GE Multilin


3 HARDWARE 3.4 FIELD AND STATOR GROUND MODULES

1. Open the G60 device so that it appears in the online window.

GE Multilin G60 Generator Protection System 3-61


3.4 FIELD AND STATOR GROUND MODULES 3 HARDWARE

2. Select the Maintenance > Update GPM-F Firmware tree node.


The following dialog will appear which allows the user to browse to the location of the firmware file.

3. Click Open to start the firmware upgrade process will start.


Note that this process will also work for a serial-port device but will take a longer time to complete (approximately 5 min-
utes).

3-62 G60 Generator Protection System GE Multilin


3 HARDWARE 3.5 MANAGED ETHERNET SWITCH MODULES

3.5MANAGED ETHERNET SWITCH MODULES 3.5.1 OVERVIEW

The type 2S and 2T embedded managed switch modules are supported by UR-series relays containing type 9S CPU mod-
ules with revisions 5.5x and higher. The modules communicate to the G60 through an internal Ethernet port (referred to as
the UR port or port 7) and provide an additional six external Ethernet ports: two 10/100Base-T ports and four multimode ST
100Base-FX ports.
The Ethernet switch module should be powered up before or at the same time as the G60. Otherwise, the switch
module will not be detected on power up and the EQUIPMENT MISMATCH: ORDERCODE XXX self-test warning will be
NOTE issued.

3.5.2 MANAGED ETHERNET SWITCH MODULE HARDWARE

The type 2S and 2T managed Ethernet switch modules provide two 10/100Base-T and four multimode ST 100Base-FX
external Ethernet ports accessible through the rear of the module. In addition, a serial console port is accessible from the 3
front of the module (requires the front panel faceplate to be open).
The pin assignment for the console port signals is shown in the following table.

Table 3–19: CONSOLE PORT PIN ASSIGNMENT


PIN SIGNAL DESCRIPTION
1 CD Carrier detect (not used)
2 RXD Receive data (input)
3 TXD Transmit data (output)
4 N/A Not used
5 GND Signal ground
6 to 9 N/A Not used

Two 10/100Base-T
ports

Four 100Base-FX
multimode ports
with ST connectors

RS232
console port
Independent power
supply. Options:
2S: high-voltage
2T: low-voltage

FRONT VIEW REAR VIEW


842867A2.CDR

Figure 3–73: MANAGED ETHERNET SWITCHES HARDWARE

GE Multilin G60 Generator Protection System 3-63


3.5 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE

The wiring for the managed Ethernet switch module is shown below.

MM fiber optic cable Tx1 100Base-FX

2S / 2T
Rx1

MM fiber optic cable Tx2 100Base-FX


Rx2 Fiber
MM fiber optic cable Tx1 100Base-FX ports
Rx1

MM fiber optic cable Tx1


Rx1 100Base-FX

100Base-T cable 10/100Base-T Copper


10/100Base-T
ports
100Base-T cable
110 to 250 V DC + W1a +
100 to 240 V AC – W2b ― Power supply

CPU
W1a GROUND
842835A1.CDR

3 Figure 3–74: MANAGED ETHERNET SWITCH MODULE WIRING

3.5.3 MANAGED SWITCH LED INDICATORS

The 10/100Base-T and 100Base-FX ports have LED indicators to indicate the port status.
The 10/100Base-T ports have three LEDs to indicate connection speed, duplex mode, and link activity. The 100Base-FX
ports have one LED to indicate linkup and activity.

Connection speed indicator (OFF = 10 Mbps; ON = 100 Mbps)


Link indicator (ON = link active; FLASHING = activity)
Duplex mode indicator (OFF = half-duplex; ON = full-duplex)

Link indicator (ON = link active; FLASHING = activity)

842868A2.CDR

Figure 3–75: ETHERNET SWITCH LED INDICATORS

3.5.4 INITIAL SETUP OF THE ETHERNET SWITCH MODULE

a) DESCRIPTION
Upon initial power up of a G60 device with an installed Ethernet switch, the front panel trouble LED will be illuminated and
the ENET MODULE OFFLINE error message will be displayed. It will be necessary to configure the Ethernet switch and then
place it online. This involves two steps:
1. Configuring the network settings on the local PC.
2. Configuring the G60 switch module through EnerVista UR Setup.
These procedures are described in the following sections. When the G60 is properly configured, the LED will be off and the
error message will be cleared.

3-64 G60 Generator Protection System GE Multilin


3 HARDWARE 3.5 MANAGED ETHERNET SWITCH MODULES

b) CONFIGURING LAN COMMUNICATIONS


The following procedure describes how to initially configure the Ethernet switch to work on your LAN.
1. Initiate communications from a PC to the G60 through a front panel serial connection (refer to the Configuring serial
communications section in chapter 1 for details), or if you are familiar with the UR keypad you can use it to set up the
network IP address and check the Modbus slave address and Modbus TCP port.

2. Ensure that the PC and the G60 are on the same IP network.
If your computer is on another network or has a dynamic IP address assigned upon a network login, then setup your
own IP address as follows
2.1. From the Windows Start Menu, select the Settings > Network Connections menu item.
2.2. Right-click on the Local Area Connection icon and select the Properties item. This will open the LAN proper-
ties window.
2.3. Click the Properties button as shown below.

Click the Properties button

827790A1.CDR

GE Multilin G60 Generator Protection System 3-65


3.5 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE

2.4. The following window is displayed. Select the Use the Following IP Address option and enter appropriate IP
address, Subnet mask, and Default gateway values. It may be necessary to contact your network administra-
tor for assistance.

Click here to setup IP


address

827803A1.CDR

2.5. Save the settings by clicking the OK button.


2.6. Click the Close button to exit the LAN properties window.
3. Connect your PC to port 1 or port 2 of the Ethernet switch module (with an RJ-45 – CAT5 cable).
4. Verify that the two LEDs beside the connected port turn green.
5. After few seconds you should see your local area connection attempting to connect to the switch. Once connected,
check your IP address by going to bottom of your screen and right-clicking the Local Area Connection icon as shown
below.

3-66 G60 Generator Protection System GE Multilin


3 HARDWARE 3.5 MANAGED ETHERNET SWITCH MODULES

Alternately, you can open a command window (type “cmd” from the Run item in the Start menu) and enter the ipconfig
command.

3
6. Now that the PC should be able to communicate to the UR relay through the UR Setup software.

c) INITIAL ETHERNET SWITCH MODULE SETUP


This procedure describes how to configure the G60 switch module through EnerVista UR Setup. Before starting this proce-
dure, ensure that the local PC is properly configured on the same network as the G60 device as shown in the previous sec-
tion.
1. Launch the EnerVista UR Setup software.
2. Click the Device Setup button.
3. Click the Add Site button. This will launch the Device Setup window.
4. Set the Interface option to “Ethernet” and enter the IP Address, Slave Address, and Modbus Port values as shown
below.

New site
Old site

Interface is Ethernet now

Make sure these settings


are correct

827804A1.CDR

5. Click the Read Order Code button. You should be able to communicate with the G60 device regardless of the value of
the Ethernet switch IP address and even though the front panel display states that the Ethernet module is offline.

GE Multilin G60 Generator Protection System 3-67


3.5 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE

6. Select the Settings > Product Setup > Communications > Ethernet Switch > Configure IP menu item as shown
below.

7. Enter (or verify) the MAC Address, IP Address, Subnet Mask, and Gateway IP Address settings.
8. Click the Save button. It will take few seconds to save the settings to the Ethernet switch module and the following
message displayed.

9. Verify that the target message is cleared and that the G60 displays the MAC address of the Ethernet switch in the
Actual Values > Status > Ethernet Switch window.

The G60 device and the Ethernet switch module communications setup is now complete.

3.5.5 CONFIGURING THE MANAGED ETHERNET SWITCH MODULE

A suitable IP/gateway and subnet mask must be assigned to both the switch and the UR relay for correct operation. The
Switch has been shipped with a default IP address of 192.168.1.2 and a subnet mask of 255.255.255.0. Consult your net-
work administrator to determine if the default IP address, subnet mask or default gateway needs to be modified.
Do not connect to network while configuring the switch module.

CAUTION

3-68 G60 Generator Protection System GE Multilin


3 HARDWARE 3.5 MANAGED ETHERNET SWITCH MODULES

a) CONFIGURING THE SWITCH MODULE IP SETTINGS


In our example configuration of both the Switch’s IP address and subnet mask must be changed to 3.94.247.229 and
255.255.252.0 respectively. The IP address, subnet mask and default gateway can be configured using either EnerVista
UR Setup software, the Switch’s Secure Web Management (SWM), or through the console port using CLI.
1. Select the Settings > Product Setup > Communications > Ethernet Switch > Configure IP menu item to open the
Ethernet switch configuration window.

2. Enter “3.94.247.229” in the IP Address field and “255.255.252.0” in the Subnet Mask field, then click OK.
The software will send the new settings to the G60 and prompt as follows when complete.

3. Cycle power to the G60 and switch module to activate the new settings.

b) SAVING THE ETHERNET SWITCH SETTINGS TO A SETTINGS FILE


The G60 allows the settings information for the Ethernet switch module to be saved locally as a settings file. This file con-
tains the advanced configuration details for the switch not contained within the standard G60 settings file.
This feature allows the switch module settings to be saved locally before performing firmware upgrades. Saving settings
files is also highly recommended before making any change to the module configuration or creating new setting files.
The following procedure describes how to save local settings files for the Ethernet switch module.
1. Select the desired device from site tree in the online window.
2. Select the Settings > Product Setup > Communications > Ethernet Switch > Ethernet Switch Settings File >
Retreive Settings File item from the device settings tree.

GE Multilin G60 Generator Protection System 3-69


3.5 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE

The system will request the name and destination path for the settings file.

3. Enter an appropriate folder and file name and click Save.


All settings files will be saved as text files and the corresponding file extension automatically assigned.

c) UPLOADING ETHERNET SWITCH SETTINGS FILES TO THE MODULE


The following procedure describes how to upload local settings files to the Ethernet switch module. It is highly recom-
mended that the current settings are saved to a settings file before uploading a new settings file.
It is highly recommended to place the switch offline while transferring setting files to the switch. When transferring
settings files from one switch to another, the user must reconfigure the IP address.
NOTE

1. Select the desired device from site tree in the online window.
2. Select the Settings > Product Setup > Communications > Ethernet Switch > Ethernet Switch Settings File >
Transfer Settings File item from the device settings tree.
The system will request the name and destination path for the settings file.

3. Navigate to the folder containing the Ethernet switch settings file, select the file, then click Open.
The settings file will be transferred to the Ethernet switch and the settings uploaded to the device.

3-70 G60 Generator Protection System GE Multilin


3 HARDWARE 3.5 MANAGED ETHERNET SWITCH MODULES

3.5.6 UPLOADING G60 SWITCH MODULE FIRMWARE

a) DESCRIPTION
This section describes the process for upgrading firmware on a UR-2S or UR-2T switch module.
There are several ways of updating firmware on a switch module:
• Using the EnerVista UR Setup software.
• Serially using the G60 switch module console port.
• Using FTP or TFTP through the G60 switch module console port.
It is highly recommended to use the EnerVista UR Setup software to upgrade firmware on a G60 switch module.
Firmware upgrades using the serial port, TFTP, and FTP are described in detail in the switch module manual.

NOTE 3
b) SELECTING THE PROPER SWITCH FIRMWARE VERSION
The latest switch module firmware is available as a download from the GE Multilin web site. Use the following procedure to
determine the version of firmware currently installed on your switch
1. Log into the switch using the EnerVista web interface.
The default switch login ID is “manager” and the default password is “manager”.

NOTE

The firmware version installed on the switch will appear on the lower left corner of the screen.

Version: 2.1 beta 842869A1.CDR

2. Using the EnerVista UR Setup program, select the Settings > Product Setup > Communications > Ethernet Switch
> Firmware Upload menu item.

GE Multilin G60 Generator Protection System 3-71


3.5 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE

The following popup screen will appear warning that the settings will be lost when the firmware is upgraded.

It is highly recommended that you save the switch settings before upgrading the firmware.

NOTE

3. After saving the settings file, proceed with the firmware upload by selecting Yes to the above warning.

3 Another window will open, asking you to point to the location of the firmware file to be uploaded.
4. Select the firmware file to be loaded on to the Switch, and select the Open option.

The following window will pop up, indicating that the firmware file transfer is in progress.

If the firmware load was successful, the following window will appear:

Note

3-72 G60 Generator Protection System GE Multilin


3 HARDWARE 3.5 MANAGED ETHERNET SWITCH MODULES

The switch will automatically reboot after a successful firmware file transfer.

NOTE

5. Once the firmware has been successfully uploaded to the switch module, load the settings file using the procedure
described earlier.

3.5.7 ETHERNET SWITCH SELF-TEST ERRORS

The following table provides details about Ethernet module self-test errors.
Be sure to enable the ETHERNET SWITCH FAIL setting in the PRODUCT SETUP ÖØ USER-PROGRAMMABLE SELF-TESTS menu
and the relevant PORT 1 EVENTS through PORT 6 EVENTS settings under the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ ETH-
ERNET SWITCH menu.

Table 3–20: ETHERNET SWITCH SELF-TEST ERRORS


3
ACTIVATION SETTING (SET EVENT NAME EVENT CAUSE POSSIBLE CAUSES
AS ENABLED)
ETHERNET SWITCH FAIL ETHERNET MODULE No response has been • Loss of switch power.
OFFLINE received from the Ethernet • IP/gateway/subnet.
module after five successive • Incompatibility between the CPU and
polling attempts. the switch module.
• UR port (port 7) configured incorrectly
or blocked
• Switch IP address assigned to another
device in the same network.
PORT 1 EVENTS to PORT 6 ETHERNET PORT 1 An active Ethernet port has • Ethernet connection broken.
EVENTS OFFLINE to ETHERNET returned a FAILED status. • An inactive port’s events have been
PORT 6 OFFLINE enabled.
No setting required; the G60 EQUIPMENT The G60 has not detected the The G60 failed to see the switch module
will read the state of a general MISMATCH: Card XXX presence of the Ethernet on power-up, because switch won’t
purpose input/output port on Missing switch via the bus board. power up or is still powering up. To clear
the main CPU upon power-up the fault, cycle power to the G60.
and create the error if there is a
conflict between the input/
output state and the order
code.

GE Multilin G60 Generator Protection System 3-73


3.5 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE

3-74 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE

4 HUMAN INTERFACES 4.1ENERVISTA UR SETUP SOFTWARE INTERFACE 4.1.1 INTRODUCTION

The EnerVista UR Setup software provides a graphical user interface (GUI) as one of two human interfaces to a UR device.
The alternate human interface is implemented via the device’s faceplate keypad and display (refer to the Faceplate inter-
face section in this chapter).
The EnerVista UR Setup software provides a single facility to configure, monitor, maintain, and trouble-shoot the operation
of relay functions, connected over local or wide area communication networks. It can be used while disconnected (off-line)
or connected (on-line) to a UR device. In off-line mode, settings files can be created for eventual downloading to the device.
In on-line mode, you can communicate with the device in real-time.
The EnerVista UR Setup software, provided with every G60 relay, can be run from any computer supporting Microsoft Win-
dows® 95, 98, NT, 2000, ME, and XP. This chapter provides a summary of the basic EnerVista UR Setup software interface
features. The EnerVista UR Setup Help File provides details for getting started and using the EnerVista UR Setup software
interface.

4.1.2 CREATING A SITE LIST

To start using the EnerVista UR Setup software, a site definition and device definition must first be created. See the EnerV-
ista UR Setup Help File or refer to the Connecting EnerVista UR Setup with the G60 section in Chapter 1 for details.

4.1.3 ENERVISTA UR SETUP OVERVIEW


4
a) ENGAGING A DEVICE
The EnerVista UR Setup software may be used in on-line mode (relay connected) to directly communicate with the G60
relay. Communicating relays are organized and grouped by communication interfaces and into sites. Sites may contain any
number of relays selected from the UR-series of relays.

b) USING SETTINGS FILES


The EnerVista UR Setup software interface supports three ways of handling changes to relay settings:
• In off-line mode (relay disconnected) to create or edit relay settings files for later download to communicating relays.
• While connected to a communicating relay to directly modify any relay settings via relay data view windows, and then
save the settings to the relay.
• You can create/edit settings files and then write them to the relay while the interface is connected to the relay.
Settings files are organized on the basis of file names assigned by the user. A settings file contains data pertaining to the
following types of relay settings:
• Device definition
• Product setup
• System setup
• FlexLogic™
• Grouped elements
• Control elements
• Inputs/outputs
• Testing
Factory default values are supplied and can be restored after any changes.
The following communications settings are not transferred to the G60 with settings files.
Modbus Slave Address
Modbus IP Port Number
RS485 COM1 Baud Rate
RS485 COM1 Parity
COM1 Minimum Response Time

GE Multilin G60 Generator Protection System 4-1


4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE 4 HUMAN INTERFACES

RS485 COM2 Baud Rate


RS485 COM2 Parity
COM2 Minimum Response Time
COM2 Selection
RRTD Slave Address
RRTD Baud Rate
IP Address
IP Subnet Mask
Gateway IP Address
Ethernet Sub Module Serial Number
Network Address NSAP
IEC61850 Config GOOSE ConfRev
When a settings file is loaded to a G60 that is in-service, the following sequence will occur.
1. The G60 will take itself out of service.
2. The G60 will issue a UNIT NOT PROGRAMMED major self-test error.
3. The G60 will close the critical fail contact.
4
c) CREATING AND EDITING FLEXLOGIC™
You can create or edit a FlexLogic™ equation in order to customize the relay. You can subsequently view the automatically
generated logic diagram.

d) VIEWING ACTUAL VALUES


You can view real-time relay data such as input/output status and measured parameters.

e) VIEWING TRIGGERED EVENTS


While the interface is in either on-line or off-line mode, you can view and analyze data generated by triggered specified
parameters, via one of the following
• Event recorder
The event recorder captures contextual data associated with the last 1024 events, listed in chronological order from
most recent to oldest.
• Oscillography
The oscillography waveform traces and digital states are used to provide a visual display of power system and relay
operation data captured during specific triggered events.

f) FILE SUPPORT
• Execution: Any EnerVista UR Setup file which is double clicked or opened will launch the application, or provide focus
to the already opened application. If the file was a settings file (has a URS extension) which had been removed from
the Settings List tree menu, it will be added back to the Settings List tree menu.
• Drag and Drop: The Site List and Settings List control bar windows are each mutually a drag source and a drop target
for device-order-code-compatible files or individual menu items. Also, the Settings List control bar window and any
Windows Explorer directory folder are each mutually a file drag source and drop target.
New files which are dropped into the Settings List window are added to the tree which is automatically sorted alphabet-
ically with respect to settings file names. Files or individual menu items which are dropped in the selected device menu
in the Site List window will automatically be sent to the on-line communicating device.

g) FIRMWARE UPGRADES
The firmware of a G60 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond-
ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.

4-2 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE

Modbus addresses assigned to firmware modules, features, settings, and corresponding data items (i.e. default
values, minimum/maximum values, data type, and item size) may change slightly from version to version of firm-
NOTE
ware. The addresses are rearranged when new features are added or existing features are enhanced or modified.
The EEPROM DATA ERROR message displayed after upgrading/downgrading the firmware is a resettable, self-test
message intended to inform users that the Modbus addresses have changed with the upgraded firmware. This
message does not signal any problems when appearing after firmware upgrades.

4.1.4 ENERVISTA UR SETUP MAIN WINDOW

The EnerVista UR Setup software main window supports the following primary display components:
1. Title bar which shows the pathname of the active data view.
2. Main window menu bar.
3. Main window tool bar.
4. Site list control bar window.
5. Settings list control bar window.
6. Device data view windows, with common tool bar.
7. Settings file data view windows, with common tool bar. 4
8. Workspace area with data view tabs.
9. Status bar.
10. Quick action hot links.

2 1 6 7

10
4

9 8 842786A2.CDR

Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW

GE Multilin G60 Generator Protection System 4-3


4.2 EXTENDED ENERVISTA UR SETUP FEATURES 4 HUMAN INTERFACES

4.2EXTENDED ENERVISTA UR SETUP FEATURES 4.2.1 SETTINGS TEMPLATES

Setting file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An exam-
ple of this is a substation that has ten similar feeders protected by ten UR-series F60 relays.
In these situations, typically 90% or greater of the settings are identical between all devices. The templates feature allows
engineers to configure and test these common settings, then lock them so they are not available to users. For example,
these locked down settings can be hidden from view for field engineers, allowing them to quickly identify and concentrate
on the specific settings.
The remaining settings (typically 10% or less) can be specified as editable and be made available to field engineers install-
ing the devices. These will be settings such as protection element pickup values and CT and VT ratios.
The settings template mode allows the user to define which settings will be visible in EnerVista UR Setup. Settings tem-
plates can be applied to both settings files (settings file templates) and online devices (online settings templates). The func-
tionality is identical for both purposes.
The settings template feature requires that both the EnerVista UR Setup software and the G60 firmware are at ver-
sions 5.40 or higher.
NOTE

4 a) ENABLING THE SETTINGS TEMPLATE


The settings file template feature is disabled by default. The following procedure describes how to enable the settings tem-
plate for UR-series settings files.
1. Select a settings file from the offline window of the EnerVista UR Setup main screen.
2. Right-click on the selected device or settings file and select the Template Mode > Create Template option.
The settings file template is now enabled and the file tree displayed in light blue. The settings file is now in template editing
mode.
Alternatively, the settings template can also be applied to online settings. The following procedure describes this process.
1. Select an installed device from the online window of the EnerVista UR Setup main screen.
2. Right-click on the selected device and select the Template Mode > Create Template option.

The software will prompt for a template password. This password is required to use the template feature and must be
at least four characters in length.
3. Enter and re-enter the new password, then click OK to continue.
The online settings template is now enabled. The device is now in template editing mode.

b) EDITING THE SETTINGS TEMPLATE


The settings template editing feature allows the user to specify which settings are available for viewing and modification in
EnerVista UR Setup. By default, all settings except the FlexLogic™ equation editor settings are locked.
1. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Select the Template Mode > Edit Template option to place the device in template editing mode.
3. Enter the template password then click OK.
4. Open the relevant settings windows that contain settings to be specified as viewable.

4-4 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.2 EXTENDED ENERVISTA UR SETUP FEATURES

By default, all settings are specified as locked and displayed against a grey background. The icon on the upper right of
the settings window will also indicate that EnerVista UR Setup is in EDIT mode. The following example shows the
phase time overcurrent settings window in edit mode.

Figure 4–2: SETTINGS TEMPLATE VIEW, ALL SETTINGS SPECIFIED AS LOCKED


5. Specify which settings to make viewable by clicking on them. 4
The setting available to view will be displayed against a yellow background as shown below.

Figure 4–3: SETTINGS TEMPLATE VIEW, TWO SETTINGS SPECIFIED AS EDITABLE


6. Click on Save to save changes to the settings template.
7. Proceed through the settings tree to specify all viewable settings.

c) ADDING PASSWORD PROTECTION TO A TEMPLATE


It is highly recommended that templates be saved with password protection to maximize security.
The following procedure describes how to add password protection to a settings file template.
1. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen.
2. Selecting the Template Mode > Password Protect Template option.

GE Multilin G60 Generator Protection System 4-5


4.2 EXTENDED ENERVISTA UR SETUP FEATURES 4 HUMAN INTERFACES

The software will prompt for a template password. This password must be at least four characters in length.

3. Enter and re-enter the new password, then click OK to continue.


The settings file template is now secured with password protection.
When templates are created for online settings, the password is added during the initial template creation step. It
does not need to be added after the template is created.
NOTE

d) VIEWING THE SETTINGS TEMPLATE


Once all necessary settings are specified for viewing, users are able to view the settings template on the online device or
4 settings file. There are two ways to specify the settings view with the settings template feature:
• Display only those settings available for editing.
• Display all settings, with settings not available for editing greyed-out.
Use the following procedure to only display settings available for editing.
1. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Apply the template by selecting the Template Mode > View In Template Mode option.
3. Enter the template password then click OK to apply the template.
Once the template has been applied, users will only be able to view and edit the settings specified by the template. The
effect of applying the template to the phase time overcurrent settings is shown below.

Phase time overcurrent window with template applied via


the Template Mode > View In Template Mode command.
The template specifies that only the Pickup and Curve
Phase time overcurrent settings window without template applied.
settings be available.
842858A1.CDR

Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND

4-6 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.2 EXTENDED ENERVISTA UR SETUP FEATURES

Viewing the settings in template mode also modifies the settings tree, showing only the settings categories that contain
editable settings. The effect of applying the template to a typical settings tree view is shown below.

Typical settings tree view without template applied. Typical settings tree view with template applied via
the Template Mode > View In Template Mode
command.
842860A1.CDR

Figure 4–5: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE SETTINGS COMMAND
Use the following procedure to display settings available for editing and settings locked by the template. 4
1. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Apply the template by selecting the Template Mode > View All Settings option.
3. Enter the template password then click OK to apply the template.
Once the template has been applied, users will only be able to edit the settings specified by the template, but all settings
will be shown. The effect of applying the template to the phase time overcurrent settings is shown below.

Phase time overcurrent settings window without template applied. Phase time overcurrent window with template applied via
the Template Mode > View All Settings command.
The template specifies that only the Pickup and Curve
settings be available.
842859A1.CDR

Figure 4–6: APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COMMAND

e) REMOVING THE SETTINGS TEMPLATE


It may be necessary at some point to remove a settings template. Once a template is removed, it cannot be reapplied and
it will be necessary to define a new settings template.
1. Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Select the Template Mode > Remove Settings Template option.
3. Enter the template password and click OK to continue.

GE Multilin G60 Generator Protection System 4-7


4.2 EXTENDED ENERVISTA UR SETUP FEATURES 4 HUMAN INTERFACES

4. Verify one more time that you wish to remove the template by clicking Yes.

The EnerVista software will remove all template information and all settings will be available.

4.2.2 SECURING AND LOCKING FLEXLOGIC™ EQUATIONS

The UR allows users to secure parts or all of a FlexLogic™ equation, preventing unauthorized viewing or modification of
critical FlexLogic™ applications. This is accomplished using the settings template feature to lock individual entries within
FlexLogic™ equations.
Secured FlexLogic™ equations will remain secure when files are sent to and retrieved from any UR-series device.

a) LOCKING FLEXLOGIC™ EQUATION ENTRIES

4 The following procedure describes how to lock individual entries of a FlexLogic™ equation.
1. Right-click the settings file or online device and select the Template Mode > Create Template item to enable the set-
tings template feature.
2. Select the FlexLogic > FlexLogic Equation Editor settings menu item.
By default, all FlexLogic™ entries are specified as viewable and displayed against a yellow background. The icon on
the upper right of the window will also indicate that EnerVista UR Setup is in EDIT mode.
3. Specify which entries to lock by clicking on them.
The locked entries will be displayed against a grey background as shown in the example below.

Figure 4–7: LOCKING FLEXLOGIC™ ENTRIES IN EDIT MODE


4. Click on Save to save and apply changes to the settings template.
5. Select the Template Mode > View In Template Mode option to view the template.
6. Apply a password to the template then click OK to secure the FlexLogic™ equation.

4-8 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.2 EXTENDED ENERVISTA UR SETUP FEATURES

Once the template has been applied, users will only be able to view and edit the FlexLogic™ entries not locked by the tem-
plate. The effect of applying the template to the FlexLogic™ entries in the above procedure is shown below.

Typical FlexLogic™ entries without template applied. Typical FlexLogic™ entries locked with template via
the Template Mode > View In Template Mode command.
842861A1.CDR

Figure 4–8: LOCKING FLEXLOGIC ENTRIES THROUGH SETTING TEMPLATES 4


The FlexLogic™ entries are also shown as locked in the graphical view (as shown below) and on the front panel display.

Figure 4–9: SECURED FLEXLOGIC™ IN GRAPHICAL VIEW

b) LOCKING FLEXLOGIC™ EQUATIONS TO A SERIAL NUMBER


A settings file and associated FlexLogic™ equations can also be locked to a specific UR serial number. Once the desired
FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific
serial number.
1. Select the settings file in the offline window.
2. Right-click on the file and select the Edit Settings File Properties item.

GE Multilin G60 Generator Protection System 4-9


4.2 EXTENDED ENERVISTA UR SETUP FEATURES 4 HUMAN INTERFACES

The following window is displayed.

Figure 4–10: TYPICAL SETTINGS FILE PROPERTIES WINDOW

4 3. Enter the serial number of the G60 device to lock to the settings file in the Serial # Lock field.
The settings file and corresponding secure FlexLogic™ equations are now locked to the G60 device specified by the serial
number.

4.2.3 SETTINGS FILE TRACEABILITY

A traceability feature for settings files allows the user to quickly determine if the settings in a G60 device have been
changed since the time of installation from a settings file. When a settings file is transfered to a G60 device, the date, time,
and serial number of the G60 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor-
mation can be compared with the G60 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the G60
device or obtained from the G60 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.

1 SETTINGS FILE TRANSFERRED


TO UR-SERIES DEVICE

The serial number and last setting change date


are stored in the UR-series device.

The serial number of the UR-series device and the file transfer
date are added to the settings file when settings files
are transferred to the device.

Compare transfer dates in the settings file and the


SERIAL NUMBER AND TRANSFER DATE
2
UR-series device to determine if security
has been compromised. SENT BACK TO ENERVISTA AND
ADDED TO SETTINGS FILE. 842864A1.CDR

Figure 4–11: SETTINGS FILE TRACEABILITY MECHANISM


With respect to the above diagram, the traceability feature is used as follows.

4-10 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.2 EXTENDED ENERVISTA UR SETUP FEATURES

1. The transfer date of a setting file written to a G60 is logged in the relay and can be viewed via EnerVista UR Setup or
the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
2. Comparing the dates stored in the relay and on the settings file at any time in the future will indicate if any changes
have been made to the relay configuration since the settings file was saved.

a) SETTINGS FILE TRACEABILITY INFORMATION


The serial number and file transfer date are saved in the settings files when they sent to an G60 device.
The G60 serial number and file transfer date are included in the settings file device definition within the EnerVista UR Setup
offline window as shown in the example below.

Traceability data in settings


file device definition

4
842863A1.CDR

Figure 4–12: DEVICE DEFINITION SHOWING TRACEABILITY DATA


This information is also available in printed settings file reports as shown in the example below.

Traceability data
in settings report

842862A1.CDR

Figure 4–13: SETTINGS FILE REPORT SHOWING TRACEABILITY DATA

GE Multilin G60 Generator Protection System 4-11


4.2 EXTENDED ENERVISTA UR SETUP FEATURES 4 HUMAN INTERFACES

b) ONLINE DEVICE TRACEABILITY INFORMATION


The G60 serial number and file transfer date are available for an online device through the actual values. Select the Actual
Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the
example below.

Traceability data in online


device actual values page

842865A1.CDR

Figure 4–14: TRACEABILITY DATA IN ACTUAL VALUES WINDOW


This infomormation if also available from the front panel display through the following actual values:
ACTUAL VALUES ÖØ PRODUCT INFO Ö MODEL INFORMATION ÖØ SERIAL NUMBER
ACTUAL VALUES ÖØ PRODUCT INFO Ö MODEL INFORMATION ÖØ LAST SETTING CHANGE

c) ADDITIONAL TRACEABILITY RULES

4 The following additional rules apply for the traceability feature


• If the user changes any settings within the settings file in the offline window, then the traceability information is
removed from the settings file.
• If the user creates a new settings file, then no traceability information is included in the settings file.
• If the user converts an existing settings file to another revision, then any existing traceability information is removed
from the settings file.
• If the user duplicates an existing settings file, then any traceability information is transferred to the duplicate settings
file.

4-12 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE

4.3FACEPLATE INTERFACE 4.3.1 FACEPLATE

a) ENHANCED FACEPLATE
The front panel interface is one of two supported interfaces, the other interface being EnerVista UR Setup software. The
front panel interface consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional user-
programmable pushbuttons.
The faceplate is hinged to allow easy access to the removable modules.

Five column LED indicator panel

Display

Keypad

4
Front panel
RS232 port

User-programmable pushbuttons 1 to 16 842810A1.CDR


Figure 4–15: UR-SERIES ENHANCED FACEPLATE

b) STANDARD FACEPLATE
The front panel interface is one of two supported interfaces, the other interface being EnerVista UR Setup software. The
front panel interface consists of LED panels, an RS232 port, keypad, LCD display, control pushbuttons, and optional user-
programmable pushbuttons.
The faceplate is hinged to allow easy access to the removable modules. There is also a removable dust cover that fits over
the faceplate which must be removed in order to access the keypad panel. The following figure shows the horizontal
arrangement of the faceplate panels.

LED panel 1 LED panel 2 LED panel 3

Display
Front panel
RS232 port

Small user-programmable User-programmable


(control) pushbuttons 1 to 7 Keypad
pushbuttons 1 to 12
827801A7.CDR

Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS

GE Multilin G60 Generator Protection System 4-13


4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES

The following figure shows the vertical arrangement of the faceplate panels for relays ordered with the vertical option.

DISPLAY

MENU 7 8 9

HELP MESSAGE 4 5 6

ESCAPE 1 2 3 KEYPAD
ENTER VALUE 0 . +/-

LED PANEL 3

4 LED PANEL 2

STATUS EVENT CAUSE


IN SERVICE VOLTAGE
TROUBLE CURRENT RESET
TEST MODE FREQUENCY
TRIP
ALARM
PICKUP
OTHER
PHASE A
PHASE B
USER 1

USER 2
LED PANEL 1
827830A1.CDR

PHASE C
NEUTRAL/GROUND USER 3

Figure 4–17: UR-SERIES STANDARD VERTICAL FACEPLATE PANELS

4.3.2 LED INDICATORS

a) ENHANCED FACEPLATE
The enhanced front panel display provides five columns of LED indicators. The first column contains 14 status and event
cause LEDs, and the next four columns contain the 48 user-programmable LEDs.
The RESET key is used to reset any latched LED indicator or target message, once the condition has been cleared (these
latched conditions can also be reset via the SETTINGS ÖØ INPUT/OUTPUTS ÖØ RESETTING menu). The RS232 port is
intended for connection to a portable PC.
The USER keys are not used in this unit.

842811A1.CDR

Figure 4–18: TYPICAL LED INDICATOR PANEL FOR ENHANCED FACEPLATE


The status indicators in the first column are described below.
• IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are
OK, and that the device has been programmed.

4-14 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE

• TROUBLE: This LED indicates that the relay has detected an internal problem.
• TEST MODE: This LED indicates that the relay is in test mode.
• TRIP: This LED indicates that the FlexLogic™ operand serving as a trip switch has operated. This indicator always
latches; as such, a reset command must be initiated to allow the latch to be reset.
• ALARM: This LED indicates that the FlexLogic™ operand serving as an alarm switch has operated. This indicator is
never latched.
• PICKUP: This LED indicates that an element is picked up. This indicator is never latched.
The event cause indicators in the first column are described below.
Events cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched”. If a protection element target setting is “Enabled”, then the corresponding event cause LEDs
remain on as long as operate operand associated with the element remains asserted. If a protection element target setting
is “Latched”, then the corresponding event cause LEDs turn on when the operate operand associated with the element is
asserted and remain on until the RESET button on the front panel is pressed after the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, etc. This means that the phase A, B, and C operate oper-
ands for individual protection elements are ORed to turn on or off the phase A, B or C LEDs.
• VOLTAGE: This LED indicates voltage was involved. 4
• CURRENT: This LED indicates current was involved.
• FREQUENCY: This LED indicates frequency was involved.
• OTHER: This LED indicates a composite function was involved.
• PHASE A: This LED indicates phase A was involved.
• PHASE B: This LED indicates phase B was involved.
• PHASE C: This LED indicates phase C was involved.
• NEUTRAL/GROUND: This LED indicates that neutral or ground was involved.
The user-programmable LEDs consist of 48 amber LED indicators in four columns. The operation of these LEDs is user-
defined. Support for applying a customized label beside every LED is provided. Default labels are shipped in the label pack-
age of every G60, together with custom templates. The default labels can be replaced by user-printed labels.
User customization of LED operation is of maximum benefit in installations where languages other than English are used to
communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.

b) STANDARD FACEPLATE
The standard faceplate consists of three panels with LED indicators, keys, and a communications port. The RESET key is
used to reset any latched LED indicator or target message, once the condition has been cleared (these latched conditions
can also be reset via the SETTINGS ÖØ INPUT/OUTPUTS ÖØ RESETTING menu). The RS232 port is intended for connection
to a portable PC.
The USER keys are not used in this unit.

STATUS EVENT CAUSE


IN SERVICE VOLTAGE
TROUBLE CURRENT RESET
TEST MODE FREQUENCY
TRIP OTHER USER 1
ALARM PHASE A
PICKUP PHASE B USER 2
PHASE C
NEUTRAL/GROUND USER 3

842781A1.CDR

Figure 4–19: LED PANEL 1

GE Multilin G60 Generator Protection System 4-15


4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES

STATUS INDICATORS:
• IN SERVICE: Indicates that control power is applied; all monitored inputs/outputs and internal systems are OK; the
relay has been programmed.
• TROUBLE: Indicates that the relay has detected an internal problem.
• TEST MODE: Indicates that the relay is in test mode.
• TRIP: Indicates that the selected FlexLogic™ operand serving as a Trip switch has operated. This indicator always
latches; the reset command must be initiated to allow the latch to be reset.
• ALARM: Indicates that the selected FlexLogic™ operand serving as an Alarm switch has operated. This indicator is
never latched.
• PICKUP: Indicates that an element is picked up. This indicator is never latched.
EVENT CAUSE INDICATORS:
Events cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched”. If a protection element target setting is “Enabled”, then the corresponding event cause LEDs
remain on as long as operate operand associated with the element remains asserted. If a protection element target setting
is “Latched”, then the corresponding event cause LEDs turn on when the operate operand associated with the element is
asserted and remain on until the RESET button on the front panel is pressed after the operand is reset.
4 All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, etc. This means that the phase A, B, and C operate oper-
ands for individual protection elements are ORed to turn on or off the phase A, B or C LEDs.
• VOLTAGE: Indicates voltage was involved.
• CURRENT: Indicates current was involved.
• FREQUENCY: Indicates frequency was involved.
• OTHER: Indicates a composite function was involved.
• PHASE A: Indicates phase A was involved.
• PHASE B: Indicates phase B was involved.
• PHASE C: Indicates phase C was involved.
• NEUTRAL/GROUND: Indicates that neutral or ground was involved.
USER-PROGRAMMABLE INDICATORS:
The second and third provide 48 amber LED indicators whose operation is controlled by the user. Support for applying a
customized label beside every LED is provided.
User customization of LED operation is of maximum benefit in installations where languages other than English are used to
communicate with operators. Refer to the User-programmable LEDs section in chapter 5 for the settings used to program
the operation of the LEDs on these panels.

USER-PROGRAMMABLE LEDS USER-PROGRAMMABLE LEDS

842782A1.CDR

Figure 4–20: LED PANELS 2 AND 3 (INDEX TEMPLATE)


DEFAULT LABELS FOR LED PANEL 2:
The default labels are intended to represent:

4-16 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE

• GROUP 1...6: The illuminated GROUP is the active settings group.


• SYNCHROCHECK NO1(2) IN-SYNCH: Voltages have satisfied the synchrocheck element.
Firmware revisions 2.9x and earlier support eight user setting groups; revisions 3.0x and higher support
six setting groups. For convenience of users using earlier firmware revisions, the relay panel shows eight
NOTE
setting groups. Please note that the LEDs, despite their default labels, are fully user-programmable.
The relay is shipped with the default label for the LED panel 2. The LEDs, however, are not pre-programmed. To match the
pre-printed label, the LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. The
LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explained
in the following section.

4
842785A1.CDR

Figure 4–21: LED PANEL 2 (DEFAULT LABELS)

4.3.3 CUSTOM LABELING OF LEDS

a) ENHANCED FACEPLATE
The following procedure requires the pre-requisites listed below.
• EnerVista UR Setup software is installed and operational.
• The G60 settings have been saved to a settings file.
• The G60 front panel label cutout sheet (GE Multilin part number 1006-0047) has been downloaded from http://
www.GEindustrial.com/multilin/support/ur and printed.
• Small-bladed knife.
This procedure describes how to create custom LED labels for the enhanced front panel display.
1. Start the EnerVista UR Setup software.

GE Multilin G60 Generator Protection System 4-17


4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES

2. Select the Front Panel Report item at the bottom of the menu tree for the settings file. The front panel report window
will be displayed.

4
Figure 4–22: FRONT PANEL REPORT WINDOW
3. Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided.
4. Feed the G60 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
5. When printing is complete, fold the sheet along the perforated lines and punch out the labels.
6. Remove the G60 label insert tool from the package and bend the tabs as described in the following procedures. These
tabs will be used for removal of the default and custom LED labels.
It is important that the tool be used EXACTLY as shown below, with the printed side containing the GE part
number facing the user.
NOTE

The label package shipped with every G60 contains the three default labels shown below, the custom label template sheet,
and the label removal tool.
If the default labels are suitable for your application, insert them in the appropriate slots and program the LEDs to match
them. If you require custom labels, follow the procedures below to remove the original labels and insert the new ones.
The following procedure describes how to setup and use the label removal tool.
1. Bend the tabs at the left end of the tool upwards as shown below.

4-18 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE

2. Bend the tab at the center of the tool tail as shown below.

The following procedure describes how to remove the LED labels from the G60 enhanced front panel and insert the custom
labels.
1. Use the knife to lift the LED label and slide the label tool underneath. Make sure the bent tabs are pointing away from
the relay.
4

2. Slide the label tool under the LED label until the tabs snap out as shown below. This will attach the label tool to the LED
label.

GE Multilin G60 Generator Protection System 4-19


4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES

3. Remove the tool and attached LED label as shown below.

4. Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below.

The following procedure describes how to remove the user-programmable pushbutton labels from the G60 enhanced front
panel and insert the custom labels.
1. Use the knife to lift the pushbutton label and slide the tail of the label tool underneath, as shown below. Make sure the
bent tab is pointing away from the relay.

4-20 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE

2. Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This will
attach the label tool to the user-programmable pushbutton label.

3. Remove the tool and attached user-programmable pushbutton label as shown below.
4

GE Multilin G60 Generator Protection System 4-21


4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES

4. Slide the new user-programmable pushbutton label inside the pocket until the text is properly aligned with the buttons,
as shown below.

b) STANDARD FACEPLATE
Custom labeling of an LED-only panel is facilitated through a Microsoft Word file available from the following URL:
http://www.GEindustrial.com/multilin/support/ur/
This file provides templates and instructions for creating appropriate labeling for the LED panel. The following procedures
are contained in the downloadable file. The panel templates provide relative LED locations and located example text (x)
edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling.
1. Remove the clear Lexan Front Cover (GE Multilin part number: 1501-0014).

F60 FEEDER MANAGEMENT RELAY


R

Push in
and gently lift
up the cover.
842771A1.CDR

2. Pop out the LED module and/or the blank module with a screwdriver as shown below. Be careful not to damage the
plastic covers.

( LED MODULE ) ( BLANK MODULE )

F60
R

FEEDER MANAGEMENT RELAY

842722A1.CDR

3. Place the left side of the customized module back to the front panel frame, then snap back the right side.
4. Put the clear Lexan front cover back into place.

4-22 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE

The following items are required to customize the G60 display module:
• Black and white or color printer (color preferred).
• Microsoft Word 97 or later software for editing the template.
• 1 each of: 8.5" x 11" white paper, exacto knife, ruler, custom display module (GE Multilin Part Number: 1516-0069),
and a custom module cover (GE Multilin Part Number: 1502-0015).
The following procedure describes how to customize the G60 display module:
1. Open the LED panel customization template with Microsoft Word. Add text in places of the LED x text placeholders on
the template(s). Delete unused place holders as required.
2. When complete, save the Word file to your local PC for future use.
3. Print the template(s) to a local printer.
4. From the printout, cut-out the Background Template from the three windows, using the cropmarks as a guide.
5. Put the Background Template on top of the custom display module (GE Multilin Part Number: 1513-0069) and snap the
clear custom module cover (GE Multilin Part Number: 1502-0015) over it and the templates.

4.3.4 DISPLAY

All messages are displayed on a 2 × 20 backlit liquid crystal display (LCD) to make them visible under poor lighting condi-
4
tions. Messages are descriptive and should not require the aid of an instruction manual for deciphering. While the keypad
and display are not actively being used, the display will default to user-defined messages. Any high priority event driven
message will automatically override the default message and appear on the display.

4.3.5 KEYPAD

Display messages are organized into pages under the following headings: actual values, settings, commands, and targets.
The MENU key navigates through these pages. Each heading page is broken down further into logical subgroups.
The MESSAGE keys navigate through the subgroups. The VALUE keys scroll increment or decrement numerical setting
values when in programming mode. These keys also scroll through alphanumeric values in the text edit mode. Alterna-
tively, values may also be entered with the numeric keypad.
The decimal key initiates and advance to the next character in text edit mode or enters a decimal point. The HELP key may
be pressed at any time for context sensitive help messages. The ENTER key stores altered setting values.

4.3.6 BREAKER CONTROL

a) INTRODUCTION
The G60 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker,
which can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually
initiated from faceplate keypad or automatically initiated from a FlexLogic™ operand. A setting is provided to assign names
to each breaker; this user-assigned name is used for the display of related flash messages. These features are provided for
two breakers; the user may use only those portions of the design relevant to a single breaker, which must be breaker 1.
For the following discussion it is assumed the SETTINGS ÖØ SYSTEM SETUP ÖØ BREAKERS Ö BREAKER 1(2) Ö BREAKER
FUNCTION setting is "Enabled" for each breaker.

b) CONTROL MODE SELECTION AND MONITORING


Installations may require that a breaker is operated in the three-pole only mode (3-pole), or in the one and three-pole (1-
pole) mode, selected by setting. If the mode is selected as three-pole, a single input tracks the breaker open or closed posi-
tion. If the mode is selected as one-pole, all three breaker pole states must be input to the relay. These inputs must be in
agreement to indicate the position of the breaker.
For the following discussion it is assumed the SETTINGS ÖØ SYSTEM SETUP ÖØ BREAKERS Ö BREAKER 1(2) ÖØ BREAKER
1(2) PUSH BUTTON CONTROL setting is “Enabled” for each breaker.

GE Multilin G60 Generator Protection System 4-23


4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES

c) FACEPLATE (USER KEY) CONTROL


After the 30 minute interval during which command functions are permitted after a correct command password, the user
cannot open or close a breaker via the keypad. The following discussions begin from the not-permitted state.

d) CONTROL OF TWO BREAKERS


For the following example setup, the (Name) field represents the user-programmed variable name.
For this application (setup shown below), the relay is connected and programmed for both breaker 1 and breaker 2. The
USER 1 key performs the selection of which breaker is to be operated by the USER 2 and USER 3 keys. The USER 2 key
is used to manually close the breaker and the USER 3 key is used to manually open the breaker.

ENTER COMMAND This message appears when the USER 1, USER 2, or USER 3 key is pressed and a
PASSWORD COMMAND PASSWORD is required; i.e. if COMMAND PASSWORD is enabled and no com-
mands have been issued within the last 30 minutes.

Press USER 1 This message appears if the correct password is entered or if none is required. This mes-
To Select Breaker sage will be maintained for 30 seconds or until the USER 1 key is pressed again.

BKR1-(Name) SELECTED This message is displayed after the USER 1 key is pressed for the second time. Three
4 USER 2=CLS/USER 3=OP possible actions can be performed from this state within 30 seconds as per items (1), (2)
and (3) below:
(1)
USER 2 OFF/ON If the USER 2 key is pressed, this message appears for 20 seconds. If the USER 2 key is
To Close BKR1-(Name) pressed again within that time, a signal is created that can be programmed to operate an
output relay to close breaker 1.
(2)
USER 3 OFF/ON If the USER 3 key is pressed, this message appears for 20 seconds. If the USER 3 key is
To Open BKR1-(Name) pressed again within that time, a signal is created that can be programmed to operate an
output relay to open breaker 1.
(3)
BKR2-(Name) SELECTED If the USER 1 key is pressed at this step, this message appears showing that a different
USER 2=CLS/USER 3=OP breaker is selected. Three possible actions can be performed from this state as per (1),
(2) and (3). Repeatedly pressing the USER 1 key alternates between available breakers.
Pressing keys other than USER 1, 2 or 3 at any time aborts the breaker control function.

e) CONTROL OF ONE BREAKER


For this application the relay is connected and programmed for breaker 1 only. Operation for this application is identical to
that described above for two breakers.

4.3.7 MENUS

a) NAVIGATION
Press the MENU key to select the desired header display page (top-level menu). The header title appears momentarily fol-
lowed by a header display page menu item. Each press of the MENU key advances through the following main heading
pages:
• Actual values.
• Settings.
• Commands.
• Targets.
• User displays (when enabled).

4-24 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE

b) HIERARCHY
The setting and actual value messages are arranged hierarchically. The header display pages are indicated by double
scroll bar characters („„), while sub-header pages are indicated by single scroll bar characters („). The header display
pages represent the highest level of the hierarchy and the sub-header display pages fall below this level. The MESSAGE
UP and DOWN keys move within a group of headers, sub-headers, setting values, or actual values. Continually pressing
the MESSAGE RIGHT key from a header display displays specific information for the header category. Conversely, contin-
ually pressing the MESSAGE LEFT key from a setting value or actual value display returns to the header display.

HIGHEST LEVEL LOWEST LEVEL (SETTING VALUE)

„„ SETTINGS „ PASSWORD ACCESS LEVEL:


„„ PRODUCT SETUP „ SECURITY Restricted

„„ SETTINGS
„„ SYSTEM SETUP

c) EXAMPLE MENU NAVIGATION


4
„„ ACTUAL VALUES Press the MENU key until the header for the first Actual Values page appears. This
„„ STATUS page contains system and relay status information. Repeatedly press the MESSAGE
keys to display the other actual value headers.
Ø
„„ SETTINGS Press the MENU key until the header for the first page of Settings appears. This page
„„ PRODUCT SETUP contains settings to configure the relay.

Ø
„„ SETTINGS Press the MESSAGE DOWN key to move to the next Settings page. This page con-
„„ SYSTEM SETUP tains settings for System Setup. Repeatedly press the MESSAGE UP and DOWN
keys to display the other setting headers and then back to the first Settings page
header.
Ø
„ PASSWORD From the Settings page one header (Product Setup), press the MESSAGE RIGHT
„ SECURITY key once to display the first sub-header (Password Security).
Ø
ACCESS LEVEL: Press the MESSAGE RIGHT key once more and this will display the first setting for
Restricted Password Security. Pressing the MESSAGE DOWN key repeatedly will display the
Ø remaining setting messages for this sub-header.
„ PASSWORD Press the MESSAGE LEFT key once to move back to the first sub-header message.
„ SECURITY
Ø
„ DISPLAY Pressing the MESSAGE DOWN key will display the second setting sub-header asso-
„ PROPERTIES ciated with the Product Setup header.
Ø
FLASH MESSAGE Press the MESSAGE RIGHT key once more and this will display the first setting for
TIME: 1.0 s Display Properties.
Ø
DEFAULT MESSAGE To view the remaining settings associated with the Display Properties subheader,
INTENSITY: 25% repeatedly press the MESSAGE DOWN key. The last message appears as shown.

GE Multilin G60 Generator Protection System 4-25


4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES

4.3.8 CHANGING SETTINGS

a) ENTERING NUMERICAL DATA


Each numerical setting has its own minimum, maximum, and increment value associated with it. These parameters define
what values are acceptable for a setting.

FLASH MESSAGE For example, select the SETTINGS Ö PRODUCT SETUP ÖØ DISPLAY PROPERTIES Ö FLASH
TIME: 1.0 s MESSAGE TIME setting.
Ø
MINIMUM: 0.5 Press the HELP key to view the minimum and maximum values. Press the HELP key
MAXIMUM: 10.0 again to view the next context sensitive help message.

Two methods of editing and storing a numerical setting value are available.
• 0 to 9 and decimal point: The relay numeric keypad works the same as that of any electronic calculator. A number is
entered one digit at a time. The leftmost digit is entered first and the rightmost digit is entered last. Pressing the MES-
SAGE LEFT key or pressing the ESCAPE key, returns the original value to the display.
• VALUE keys: The VALUE UP key increments the displayed value by the step value, up to the maximum value allowed.
4 While at the maximum value, pressing the VALUE UP key again will allow the setting selection to continue upward
from the minimum value. The VALUE DOWN key decrements the displayed value by the step value, down to the mini-
mum value. While at the minimum value, pressing the VALUE DOWN key again will allow the setting selection to con-
tinue downward from the maximum value.

FLASH MESSAGE As an example, set the flash message time setting to 2.5 seconds. Press the appropriate
TIME: 2.5 s numeric keys in the sequence “2 . 5". The display message will change as the digits are
Ø being entered.
NEW SETTING Until ENTER is pressed, editing changes are not registered by the relay. Therefore, press
HAS BEEN STORED ENTER to store the new value in memory. This flash message will momentarily appear
as confirmation of the storing process. Numerical values which contain decimal places
will be rounded-off if more decimal place digits are entered than specified by the step
value.

b) ENTERING ENUMERATION DATA


Enumeration settings have data values which are part of a set, whose members are explicitly defined by a name. A set is
comprised of two or more members.

ACCESS LEVEL: For example, the selections available for ACCESS LEVEL are "Restricted", "Command",
Restricted "Setting", and "Factory Service".

Enumeration type values are changed using the VALUE keys. The VALUE UP key displays the next selection while the
VALUE DOWN key displays the previous selection.

ACCESS LEVEL: If the ACCESS LEVEL needs to be "Setting", press the VALUE keys until the proper selec-
Setting tion is displayed. Press HELP at any time for the context sensitive help messages.
Ø
NEW SETTING Changes are not registered by the relay until the ENTER key is pressed. Pressing
HAS BEEN STORED ENTER stores the new value in memory. This flash message momentarily appears as
confirmation of the storing process.

c) ENTERING ALPHANUMERIC TEXT


Text settings have data values which are fixed in length, but user-defined in character. They may be comprised of upper
case letters, lower case letters, numerals, and a selection of special characters.

4-26 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE

There are several places where text messages may be programmed to allow the relay to be customized for specific appli-
cations. One example is the Message Scratchpad. Use the following procedure to enter alphanumeric text messages.
For example: to enter the text, “Breaker #1”.
1. Press the decimal to enter text edit mode.
2. Press the VALUE keys until the character 'B' appears; press the decimal key to advance the cursor to the next position.
3. Repeat step 2 for the remaining characters: r,e,a,k,e,r, ,#,1.
4. Press ENTER to store the text.
5. If you have any problem, press HELP to view context sensitive help. Flash messages will sequentially appear for sev-
eral seconds each. For the case of a text setting message, pressing HELP displays how to edit and store new values.

d) ACTIVATING THE RELAY

RELAY SETTINGS: When the relay is powered up, the Trouble LED will be on, the In Service LED off, and
Not Programmed this message displayed, indicating the relay is in the "Not Programmed" state and is safe-
guarding (output relays blocked) against the installation of a relay whose settings have
not been entered. This message remains until the relay is explicitly put in the "Pro-
grammed" state.
4
To change the RELAY SETTINGS: "Not Programmed" mode to "Programmed", proceed as follows:
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on the
display.
2. Press the MESSAGE RIGHT key until the PASSWORD SECURITY message appears on the display.
3. Press the MESSAGE DOWN key until the INSTALLATION message appears on the display.
4. Press the MESSAGE RIGHT key until the RELAY SETTINGS: Not Programmed message is displayed.

SETTINGS

Ø
„„ SETTINGS „ PASSWORD
„„ PRODUCT SETUP „ SECURITY
„ DISPLAY
„ PROPERTIES

„ INSTALLATION RELAY SETTINGS:


„ Not Programmed

5. After the RELAY SETTINGS: Not Programmed message appears on the display, press the VALUE keys change the
selection to "Programmed".
6. Press the ENTER key.

RELAY SETTINGS: RELAY SETTINGS: NEW SETTING


Not Programmed Programmed HAS BEEN STORED

7. When the "NEW SETTING HAS BEEN STORED" message appears, the relay will be in "Programmed" state and the
In Service LED will turn on.

e) ENTERING INITIAL PASSWORDS


The G60 supports password entry from a local or remote connection.

GE Multilin G60 Generator Protection System 4-27


4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES

Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the faceplate RS232 connection. Remote access is defined as any access to settings or commands via any rear com-
munications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
To enter the initial setting (or command) password, proceed as follows:
1. Press the MENU key until the SETTINGS header flashes momentarily and the PRODUCT SETUP message appears on the
display.
2. Press the MESSAGE RIGHT key until the ACCESS LEVEL message appears on the display.
3. Press the MESSAGE DOWN key until the CHANGE LOCAL PASSWORDS message appears on the display.
4. Press the MESSAGE RIGHT key until the CHANGE SETTING PASSWORD or CHANGE COMMAND PASSWORD message
appears on the display.
„„ PASSWORD ACCESS LEVEL:
„„ SECURITY Restricted
„ CHANGE LOCAL CHANGE COMMAND
„ PASSWORDS PASSWORD: No
CHANGE SETTING
4 PASSWORD: No
ENCRYPTED COMMAND
PASSWORD: ---------
ENCRYPTED SETTING
PASSWORD: ---------

5. After the CHANGE...PASSWORD message appears on the display, press the VALUE UP or DOWN key to change the
selection to “Yes”.
6. Press the ENTER key and the display will prompt you to ENTER NEW PASSWORD.
7. Type in a numerical password (up to 10 characters) and press the ENTER key.
8. When the VERIFY NEW PASSWORD is displayed, re-type in the same password and press ENTER.
CHANGE SETTING
PASSWORD: No

CHANGE SETTING ENTER NEW VERIFY NEW


PASSWORD: Yes PASSWORD: ########## PASSWORD: ##########

NEW PASSWORD
HAS BEEN STORED
9. When the NEW PASSWORD HAS BEEN STORED message appears, your new Setting (or Command) Password will be
active.

f) CHANGING EXISTING PASSWORD


To change an existing password, follow the instructions in the previous section with the following exception. A message will
prompt you to type in the existing password (for each security level) before a new password can be entered.
In the event that a password has been lost (forgotten), submit the corresponding encrypted password from the PASSWORD
SECURITY menu to the Factory for decoding.

g) INVALID PASSWORD ENTRY


When an incorrect command or setting password has been entered via the faceplate interface three times within a 3-minute
time span, the LOCAL ACCESS DENIED FlexLogic™ operand will be set to “On” and the G60 will not allow settings or com-
mand level access via the faceplate interface for the next five minutes, or in the event that an incorrect Command Or Set-

4-28 G60 Generator Protection System GE Multilin


4 HUMAN INTERFACES 4.3 FACEPLATE INTERFACE

ting password has been entered via the any external communications interface three times within a 3-minute time span, the
REMOTE ACCESS DENIED FlexLogic™ operand will be set to “On” and the G60 will not allow settings or command access
via the any external communications interface for the next five minutes.
In the event that an incorrect Command or Setting password has been entered via the any external communications inter-
face three times within a three-minute time span, the REMOTE ACCESS DENIED FlexLogic™ operand will be set to “On” and
the G60 will not allow Settings or Command access via the any external communications interface for the next ten minutes.
The REMOTE ACCESS DENIED FlexLogic™ operand will be set to “Off” after the expiration of the ten-minute timeout.

GE Multilin G60 Generator Protection System 4-29


4.3 FACEPLATE INTERFACE 4 HUMAN INTERFACES

4-30 G60 Generator Protection System GE Multilin


5 SETTINGS 5.1 OVERVIEW

5 SETTINGS 5.1OVERVIEW 5.1.1 SETTINGS MAIN MENU

„„ SETTINGS „ SECURITY
See page 5-8.
„„ PRODUCT SETUP „
„ DISPLAY
See page 5-12.
„ PROPERTIES
„ CLEAR RELAY
See page 5-14.
„ RECORDS
„ COMMUNICATIONS
See page 5-15.
„
„ MODBUS USER MAP
See page 5-39.
„
„ REAL TIME
See page 5-40.
„ CLOCK
„ USER-PROGRAMMABLE
See page 5-41.
„ FAULT REPORT
„ OSCILLOGRAPHY
See page 5-42.
„
„ DATA LOGGER
See page 5-44.
„
5
„ USER-PROGRAMMABLE
See page 5-46.
„ LEDS
„ USER-PROGRAMMABLE
See page 5-49.
„ SELF TESTS
„ CONTROL
See page 5-49.
„ PUSHBUTTONS
„ USER-PROGRAMMABLE
See page 5-51.
„ PUSHBUTTONS
„ FLEX STATE
See page 5-56.
„ PARAMETERS
„ USER-DEFINABLE
See page 5-57.
„ DISPLAYS
„ DIRECT I/O
See page 5-59.
„
„ TELEPROTECTION
See page 5-67.
„
„ INSTALLATION
See page 5-67.
„

„„ SETTINGS „ AC INPUTS
See page 5-70.
„„ SYSTEM SETUP „
„ POWER SYSTEM
See page 5-71.
„
„ SIGNAL SOURCES
See page 5-72.
„

GE Multilin G60 Generator Protection System 5-1


5.1 OVERVIEW 5 SETTINGS

„ BREAKERS
See page 5-75.
„
„ SWITCHES
See page 5-79.
„
„ FLEXCURVES
See page 5-82.
„
„ PHASOR MEASUREMENT
See page 5-89.
„ UNIT

„„ SETTINGS „ FLEXLOGIC
See page 5-122.
„„ FLEXLOGIC „ EQUATION EDITOR
„ FLEXLOGIC
See page 5-122.
„ TIMERS
„ FLEXELEMENTS
See page 5-123.
„
„ NON-VOLATILE
See page 5-127.
„ LATCHES

„„ SETTINGS „ SETTING GROUP 1


See page 5-128.
„„ GROUPED ELEMENTS „

5 „ SETTING GROUP 2
„

„ SETTING GROUP 6
„

„„ SETTINGS „ TRIP BUS


See page 5-216.
„„ CONTROL ELEMENTS „
„ SETTING GROUPS
See page 5-218.
„
„ SELECTOR SWITCH
See page 5-219.
„
„ UNDERFREQUENCY
See page 5-225.
„
„ OVERFREQUENCY
See page 5-226.
„
„ FREQUENCY RATE
See page 5-227.
„ OF CHANGE
„ FREQUENCY OOB
See page 5-229.
„ ACCUMULATION
„ SYNCHROCHECK
See page 5-231.
„
„ DIGITAL ELEMENTS
See page 5-236.
„

5-2 G60 Generator Protection System GE Multilin


5 SETTINGS 5.1 OVERVIEW

„ DIGITAL COUNTERS
See page 5-239.
„
„ MONITORING ELEMENTS
See page 5-241.
„

„„ SETTINGS „ CONTACT INPUTS


See page 5-246.
„„ INPUTS / OUTPUTS „
„ VIRTUAL INPUTS
See page 5-248.
„
„ CONTACT OUTPUTS
See page 5-249.
„
„ VIRTUAL OUTPUTS
See page 5-251.
„
„ REMOTE DEVICES
See page 5-252.
„
„ REMOTE INPUTS
See page 5-253.
„
„ REMOTE DPS INPUTS
See page 5-254.
„
„ REMOTE OUTPUTS
„ DNA BIT PAIRS
See page 5-254.
5
„ REMOTE OUTPUTS
See page 5-255.
„ UserSt BIT PAIRS
„ RESETTING
See page 5-255.
„
„ DIRECT INPUTS
See page 5-256.
„
„ DIRECT OUTPUTS
See page 5-256.
„
„ TELEPROTECTION
See page 5-259.
„
„ IEC 61850
See page 5-261.
„ GOOSE ANALOGS
„ IEC 61850
See page 5-262.
„ GOOSE UINTEGERS

„„ SETTINGS „ DCMA INPUTS


See page 5-263.
„„ TRANSDUCER I/O „
„ RTD INPUTS
See page 5-264.
„
„ RRTD INPUTS
See page 5-266.
„
„ DCMA OUTPUTS
See page 5-270.
„

GE Multilin G60 Generator Protection System 5-3


5.1 OVERVIEW 5 SETTINGS

„„ SETTINGS TEST MODE


See page 5-274.
„„ TESTING FUNCTION: Disabled
TEST MODE INITIATE:
See page 5-274.
On
„ FORCE CONTACT
See page 5-275.
„ INPUTS
„ FORCE CONTACT
See page 5-276.
„ OUTPUTS
„ PMU TEST VALUES
See page 5-277.
„

5.1.2 INTRODUCTION TO ELEMENTS

In the design of UR relays, the term element is used to describe a feature that is based around a comparator. The compar-
ator is provided with an input (or set of inputs) that is tested against a programmed setting (or group of settings) to deter-
mine if the input is within the defined range that will set the output to logic 1, also referred to as setting the flag. A single
comparator may make multiple tests and provide multiple outputs; for example, the time overcurrent comparator sets a
pickup flag when the current input is above the setting and sets an operate flag when the input current has been at a level
above the pickup setting for the time specified by the time-current curve settings. All comparators use analog parameter
actual values as the input.
The exception to the above rule are the digital elements, which use logic states as inputs.

5 NOTE

Elements are arranged into two classes, grouped and control. Each element classed as a grouped element is provided with
six alternate sets of settings, in setting groups numbered 1 through 6. The performance of a grouped element is defined by
the setting group that is active at a given time. The performance of a control element is independent of the selected active
setting group.
The main characteristics of an element are shown on the element logic diagram. This includes the inputs, settings, fixed
logic, and the output operands generated (abbreviations used on scheme logic diagrams are defined in Appendix F).
Some settings for current and voltage elements are specified in per-unit (pu) calculated quantities:
pu quantity = (actual quantity) / (base quantity)
For current elements, the base quantity is the nominal secondary or primary current of the CT.
Where the current source is the sum of two CTs with different ratios, the base quantity will be the common secondary or pri-
mary current to which the sum is scaled (that is, normalized to the larger of the two rated CT inputs). For example, if CT1 =
300 / 5 A and CT2 = 100 / 5 A, then in order to sum these, CT2 is scaled to the CT1 ratio. In this case, the base quantity will
be 5 A secondary or 300 A primary.
For voltage elements the base quantity is the nominal primary voltage of the protected system which corresponds (based
on VT ratio and connection) to secondary VT voltage applied to the relay.
For example, on a system with a 13.8 kV nominal primary voltage and with 14400:120 V delta-connected VTs, the second-
ary nominal voltage (1 pu) would be:
13800
---------------- × 120 = 115 V (EQ 5.1)
14400
For wye-connected VTs, the secondary nominal voltage (1 pu) would be:
13800
---------------- × 120
---------- = 66.4 V (EQ 5.2)
14400 3
Many settings are common to most elements and are discussed below:

5-4 G60 Generator Protection System GE Multilin


5 SETTINGS 5.1 OVERVIEW

• FUNCTION setting: This setting programs the element to be operational when selected as “Enabled”. The factory
default is “Disabled”. Once programmed to “Enabled”, any element associated with the function becomes active and all
options become available.
• NAME setting: This setting is used to uniquely identify the element.
• SOURCE setting: This setting is used to select the parameter or set of parameters to be monitored.
• PICKUP setting: For simple elements, this setting is used to program the level of the measured parameter above or
below which the pickup state is established. In more complex elements, a set of settings may be provided to define the
range of the measured parameters which will cause the element to pickup.
• PICKUP DELAY setting: This setting sets a time-delay-on-pickup, or on-delay, for the duration between the pickup
and operate output states.
• RESET DELAY setting: This setting is used to set a time-delay-on-dropout, or off-delay, for the duration between the
Operate output state and the return to logic 0 after the input transits outside the defined pickup range.
• BLOCK setting: The default output operand state of all comparators is a logic 0 or “flag not set”. The comparator
remains in this default state until a logic 1 is asserted at the RUN input, allowing the test to be performed. If the RUN
input changes to logic 0 at any time, the comparator returns to the default state. The RUN input is used to supervise
the comparator. The BLOCK input is used as one of the inputs to RUN control.
• TARGET setting: This setting is used to define the operation of an element target message. When set to “Disabled”,
no target message or illumination of a faceplate LED indicator is issued upon operation of the element. When set to
“Self-Reset”, the target message and LED indication follow the operate state of the element, and self-resets once the
operate element condition clears. When set to “Latched”, the target message and LED indication will remain visible
after the element output returns to logic 0 until a RESET command is received by the relay.
• EVENTS setting: This setting is used to control whether the pickup, dropout or operate states are recorded by the
event recorder. When set to “Disabled”, element pickup, dropout or operate are not recorded as events. When set to
“Enabled”, events are created for:
5
(Element) PKP (pickup)
(Element) DPO (dropout)
(Element) OP (operate)
The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to
the dropout state (logic 0). This could happen when the element is in the operate state if the reset delay time is not 0.

5.1.3 INTRODUCTION TO AC SOURCES

a) BACKGROUND
The G60 may be used on systems with breaker-and-a-half or ring bus configurations. In these applications, each of the two
three-phase sets of individual phase currents (one associated with each breaker) can be used as an input to a breaker fail-
ure element. The sum of both breaker phase currents and 3I_0 residual currents may be required for the circuit relaying
and metering functions. For a three-winding transformer application, it may be required to calculate watts and vars for each
of three windings, using voltage from different sets of VTs. These requirements can be satisfied with a single UR, equipped
with sufficient CT and VT input channels, by selecting the parameter to measure. A mechanism is provided to specify the
AC parameter (or group of parameters) used as the input to protection/control comparators and some metering elements.
Selection of the parameter(s) to measure is partially performed by the design of a measuring element or protection/control
comparator by identifying the type of parameter (fundamental frequency phasor, harmonic phasor, symmetrical component,
total waveform RMS magnitude, phase-phase or phase-ground voltage, etc.) to measure. The user completes the process
by selecting the instrument transformer input channels to use and some of the parameters calculated from these channels.
The input parameters available include the summation of currents from multiple input channels. For the summed currents of
phase, 3I_0, and ground current, current from CTs with different ratios are adjusted to a single ratio before summation.
A mechanism called a source configures the routing of CT and VT input channels to measurement sub-systems. Sources,
in the context of UR series relays, refer to the logical grouping of current and voltage signals such that one source contains
all the signals required to measure the load or fault in a particular power apparatus. A given source may contain all or some
of the following signals: three-phase currents, single-phase ground current, three-phase voltages and an auxiliary voltage
from a single VT for checking for synchronism.

GE Multilin G60 Generator Protection System 5-5


5.1 OVERVIEW 5 SETTINGS

To illustrate the concept of sources, as applied to current inputs only, consider the breaker-and-a-half scheme below. In this
application, the current flows as shown by the arrows. Some current flows through the upper bus bar to some other location
or power equipment, and some current flows into transformer winding 1. The current into winding 1 is the phasor sum (or
difference) of the currents in CT1 and CT2 (whether the sum or difference is used depends on the relative polarity of the CT
connections). The same considerations apply to transformer winding 2. The protection elements require access to the net
current for transformer protection, but some elements may need access to the individual currents from CT1 and CT2.

CT1 through current CT2

Winding 1
current
Winding 1
UR-series
relay Power
transformer
Winding 2

CT3 CT4
827791A3.CDR

Figure 5–1: BREAKER-AND-A-HALF SCHEME


In conventional analog or electronic relays, the sum of the currents is obtained from an appropriate external connection of
5 all CTs through which any portion of the current for the element being protected could flow. Auxiliary CTs are required to
perform ratio matching if the ratios of the primary CTs to be summed are not identical. In the UR series of relays, provisions
have been included for all the current signals to be brought to the UR device where grouping, ratio correction and summa-
tion are applied internally via configuration settings.
A major advantage of using internal summation is that the individual currents are available to the protection device; for
example, as additional information to calculate a restraint current, or to allow the provision of additional protection features
that operate on the individual currents such as breaker failure.
Given the flexibility of this approach, it becomes necessary to add configuration settings to the platform to allow the user to
select which sets of CT inputs will be added to form the net current into the protected device.
The internal grouping of current and voltage signals forms an internal source. This source can be given a specific name
through the settings, and becomes available to protection and metering elements in the UR platform. Individual names can
be given to each source to help identify them more clearly for later use. For example, in the scheme shown in the above
diagram, the user configures one source to be the sum of CT1 and CT2 and can name this source as “Wdg1 I”.
Once the sources have been configured, the user has them available as selections for the choice of input signal for the pro-
tection elements and as metered quantities.

b) CT/VT MODULE CONFIGURATION


CT and VT input channels are contained in CT/VT modules. The type of input channel can be phase/neutral/other voltage,
phase/ground current, or sensitive ground current. The CT/VT modules calculate total waveform RMS levels, fundamental
frequency phasors, symmetrical components and harmonics for voltage or current, as allowed by the hardware in each
channel. These modules may calculate other parameters as directed by the CPU module.
A CT/VT module contains up to eight input channels, numbered 1 through 8. The channel numbering corresponds to the
module terminal numbering 1 through 8 and is arranged as follows: Channels 1, 2, 3 and 4 are always provided as a group,
hereafter called a “bank,” and all four are either current or voltage, as are channels 5, 6, 7 and 8. Channels 1, 2, 3 and 5, 6,
7 are arranged as phase A, B and C respectively. Channels 4 and 8 are either another current or voltage.

5-6 G60 Generator Protection System GE Multilin


5 SETTINGS 5.1 OVERVIEW

Banks are ordered sequentially from the block of lower-numbered channels to the block of higher-numbered channels, and
from the CT/VT module with the lowest slot position letter to the module with the highest slot position letter, as follows:
INCREASING SLOT POSITION LETTER -->
CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3
< bank 1 > < bank 3 > < bank 5 >
< bank 2 > < bank 4 > < bank 6 >

The UR platform allows for a maximum of three sets of three-phase voltages and six sets of three-phase currents. The
result of these restrictions leads to the maximum number of CT/VT modules in a chassis to three. The maximum number of
sources is six. A summary of CT/VT module configurations is shown below.
ITEM MAXIMUM NUMBER
CT/VT Module 2
CT Bank (3 phase channels, 1 ground channel) 8
VT Bank (3 phase channels, 1 auxiliary channel) 4

c) CT/VT INPUT CHANNEL CONFIGURATION


Upon relay startup, configuration settings for every bank of current or voltage input channels in the relay are automatically
generated from the order code. Within each bank, a channel identification label is automatically assigned to each bank of
channels in a given product. The bank naming convention is based on the physical location of the channels, required by the
user to know how to connect the relay to external circuits. Bank identification consists of the letter designation of the slot in
which the CT/VT module is mounted as the first character, followed by numbers indicating the channel, either 1 or 5.
For three-phase channel sets, the number of the lowest numbered channel identifies the set. For example, F1 represents
the three-phase channel set of F1/F2/F3, where F is the slot letter and 1 is the first channel of the set of three channels.
Upon startup, the CPU configures the settings required to characterize the current and voltage inputs, and will display them
5
in the appropriate section in the sequence of the banks (as described above) as follows for a maximum configuration: F1,
F5, M1, M5, U1, and U5.
The above section explains how the input channels are identified and configured to the specific application instrument
transformers and the connections of these transformers. The specific parameters to be used by each measuring element
and comparator, and some actual values are controlled by selecting a specific source. The source is a group of current and
voltage input channels selected by the user to facilitate this selection. With this mechanism, a user does not have to make
multiple selections of voltage and current for those elements that need both parameters, such as a distance element or a
watt calculation. It also gathers associated parameters for display purposes.
The basic idea of arranging a source is to select a point on the power system where information is of interest. An applica-
tion example of the grouping of parameters in a source is a transformer winding, on which a three phase voltage is mea-
sured, and the sum of the currents from CTs on each of two breakers is required to measure the winding current flow.

GE Multilin G60 Generator Protection System 5-7


5.2 PRODUCT SETUP 5 SETTINGS

5.2PRODUCT SETUP 5.2.1 SECURITY

a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY

„ SECURITY ACCESS LEVEL: Range: Restricted, Command, Setting,


„ Restricted Factory Service (for factory use only)

„ CHANGE LOCAL
MESSAGE See page 5–9.
„ PASSWORDS
„ ACCESS
MESSAGE See page 5–10.
„ SUPERVISION
„ DUAL PERMISSION
MESSAGE See page 5–11.
„ SECURITY ACCESS
PASSWORD ACCESS Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

Two levels of password security are provided via the ACCESS LEVEL setting: command and setting. The factory service level
is not available and intended for factory use only.
The following operations are under command password supervision:
• Changing the state of virtual inputs.
• Clearing the event records.
• Clearing the oscillography records.
5 • Changing the date and time.
• Clearing energy records.
• Clearing the data logger.
• Clearing the user-programmable pushbutton states.
The following operations are under setting password supervision:
• Changing any setting.
• Test mode operation.
The command and setting passwords are defaulted to “0” when the relay is shipped from the factory. When a password is
set to “0”, the password security feature is disabled.
The G60 supports password entry from a local or remote connection.
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear
communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the G60, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password must be used.
The PASSWORD ACCESS EVENTS settings allows recording of password access events in the event recorder.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command ses-
sions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic™ operands.
• ACCESS LOC SETG OFF: Asserted when local setting access is disabled.
• ACCESS LOC SETG ON: Asserted when local setting access is enabled.
• ACCESS LOC CMND OFF: Asserted when local command access is disabled.

5-8 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

• ACCESS LOC CMND ON: Asserted when local command access is enabled.
• ACCESS REM SETG OFF: Asserted when remote setting access is disabled.
• ACCESS REM SETG ON: Asserted when remote setting access is enabled.
• ACCESS REM CMND OFF: Asserted when remote command access is disabled.
• ACCESS REM CMND ON: Asserted when remote command access is enabled.
The appropriate events are also logged in the Event Recorder as well. The FlexLogic™ operands and events are updated
every five seconds.
A command or setting write operation is required to update the state of all the remote and local security operands
shown above.
NOTE

b) LOCAL PASSWORDS
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ CHANGE LOCAL PASSWORDS

„ CHANGE LOCAL CHANGE COMMAND Range: No, Yes


„ PASSWORDS PASSWORD: No
CHANGE SETTING Range: No, Yes
MESSAGE
PASSWORD: No
ENCRYPTED COMMAND Range: 0 to 9999999999
MESSAGE Note: ---------- indicates no password
PASSWORD: ----------
ENCRYPTED SETTING Range: 0 to 9999999999
MESSAGE Note: ---------- indicates no password
PASSWORD: ----------

Proper password codes are required to enable each access level. A password consists of 1 to 10 numerical characters.
5
When a CHANGE COMMAND PASSWORD or CHANGE SETTING PASSWORD setting is programmed to “Yes” via the front panel
interface, the following message sequence is invoked:
1. ENTER NEW PASSWORD: ____________.
2. VERIFY NEW PASSWORD: ____________.
3. NEW PASSWORD HAS BEEN STORED.
To gain write access to a “Restricted” setting, program the ACCESS LEVEL setting in the main security menu to “Setting” and
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access will be allowed. Accessibility automatically reverts to the “Restricted” level according
to the access level timeout setting values.
If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD.
If the setting and command passwords are identical, then this one password allows access to both com-
mands and settings.
NOTE

c) REMOTE PASSWORDS
The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the
Settings > Product Setup > Password Security menu item to open the remote password settings window.

Figure 5–2: REMOTE PASSWORD SETTINGS WINDOW

GE Multilin G60 Generator Protection System 5-9


5.2 PRODUCT SETUP 5 SETTINGS

Proper passwords are required to enable each command or setting level access. A command or setting password consists
of 1 to 10 numerical characters and are initially programmed to “0”. The following procedure describes how the set the com-
mand or setting password.
1. Enter the new password in the Enter New Password field.
2. Re-enter the password in the Confirm New Password field.
3. Click the Change button. This button will not be active until the new password matches the confirmation password.
4. If the original password is not “0”, then enter the original password in the Enter Password field and click the Send
Password to Device button.

5. The new password is accepted and a value is assigned to the ENCRYPTED PASSWORD item.

If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password
value.

d) ACCESS SUPERVISION
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ ACCESS SUPERVISION

„ ACCESS „ ACCESS LEVEL


„ SUPERVISION „ TIMEOUTS
INVALID ATTEMPTS Range: 2 to 5 in steps of 1
MESSAGE
BEFORE LOCKOUT: 3
PASSWORD LOCKOUT Range: 5 to 60 minutes in steps of 1
MESSAGE
DURATION: 5 min

The following access supervision settings are available.


• INVALID ATTEMPTS BEFORE LOCKOUT: This setting specifies the number of times an incorrect password can be
entered within a three-minute time span before lockout occurs. When lockout occurs, the LOCAL ACCESS DENIED or
REMOTE ACCESS DENIED FlexLogic™ operands are set to “On”. These operands are returned to the “Off” state upon
expiration of the lockout.
• PASSWORD LOCKOUT DURATION: This setting specifies the time that the G60 will lockout password access after
the number of invalid password entries specified by the INVALID ATTEMPS BEFORE LOCKOUT setting has occurred.
The G60 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing
a password-protected level of the relay (either settings or commands), the UNAUTHORIZED ACCESS FlexLogic™ operand is
asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be
used to protect against both unauthorized and accidental access attempts.

5-10 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

The UNAUTHORIZED ACCESS operand is reset with the COMMANDS ÖØ CLEAR RECORDS ÖØ RESET UNAUTHORIZED
ALARMS command. Therefore, to apply this feature with security, the command level should be password-protected. The
operand does not generate events or targets.
If events or targets are required, the UNAUTHORIZED ACCESS operand can be assigned to a digital element programmed
with event logs or targets enabled.
The access level timeout settings are shown below.
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ ACCESS SUPERVISION Ö ACCESS LEVEL TIMEOUTS

„ ACCESS LEVEL COMMAND LEVEL ACCESS Range: 5 to 480 minutes in steps of 1


„ TIMEOUTS TIMEOUT: 5 min
SETTING LEVEL ACCESS Range: 5 to 480 minutes in steps of 1
MESSAGE
TIMEOUT: 30 min

These settings allow the user to specify the length of inactivity required before returning to the restricted access level. Note
that the access level will set as restricted if control power is cycled.
• COMMAND LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
• SETTING LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.

e) DUAL PERMISSION SECURITY ACCESS


PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ DUAL PERMISSION SECURITY ACCESS

„ DUAL PERMISSION Range: selected FlexLogic™ operands (see below)


„ SECURITY ACCESS
LOCAL SETTING AUTH:
On
5
REMOTE SETTING AUTH: Range: FlexLogic™ operand
MESSAGE
On
ACCESS AUTH Range: 5 to 480 minutes in steps of 1
MESSAGE
TIMEOUT: 30 min.

The dual permission security access feature provides a mechanism for customers to prevent unauthorized or unintended
upload of settings to a relay through the local or remote interfaces interface.
The following settings are available through the local (front panel) interface only.
• LOCAL SETTING AUTH: This setting is used for local (front panel or RS232 interface) setting access supervision.
Valid values for the FlexLogic™ operands are either “On” (default) or any physical “Contact Input ~~ On” value.
If this setting is “On“, then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing
the local setting password to gain setting access.
If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the UNAUTHORIZED ACCESS message is displayed on the front panel.
• REMOTE SETTING AUTH: This setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to pro-
viding the remote setting password to gain setting access.
• ACCESS AUTH TIMEOUT: This setting represents the timeout delay for local setting access. This setting is applicable
when the LOCAL SETTING AUTH setting is programmed to any operand except “On”. The state of the FlexLogic™ oper-
and is continuously monitored for an off-to-on transition. When this occurs, local access is permitted and the timer pro-
grammed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the time-
out is restarted. The status of this timer is updated every 5 seconds.

GE Multilin G60 Generator Protection System 5-11


5.2 PRODUCT SETUP 5 SETTINGS

The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product
Setup > Security menu item to display the security settings window.

The Remote Settings Authorization setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is pro-
vided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing the
remote setting password to gain setting access.
The Access Authorization Timeout setting represents the timeout delay remote setting access. This setting is applicable
when the Remote Settings Authorization setting is programmed to any operand except “On” or “Off”. The state of the
FlexLogic™ operand is continuously monitored for an off-to-on transition. When this occurs, remote setting access is per-
mitted and the timer programmed with the Access Authorization Timeout setting value is started. When this timer
expires, remote setting access is immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™
operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds.

5.2.2 DISPLAY PROPERTIES

PATH: SETTINGS Ö PRODUCT SETUP ÖØ DISPLAY PROPERTIES


5 „ DISPLAY LANGUAGE: Range: English; English, French; English, Russian;
„ PROPERTIES English English, Chinese
(range dependent on order code)
FLASH MESSAGE Range: 0.5 to 10.0 s in steps of 0.1
MESSAGE
TIME: 1.0 s
DEFAULT MESSAGE Range: 10 to 900 s in steps of 1
MESSAGE
TIMEOUT: 300 s
DEFAULT MESSAGE Range: 25%, 50%, 75%, 100%
MESSAGE Visible only if a VFD is installed
INTENSITY: 25 %
SCREEN SAVER Range: Disabled, Enabled
MESSAGE Visible only if an LCD is installed
FEATURE: Disabled
SCREEN SAVER WAIT Range: 1 to 65535 min. in steps of 1
MESSAGE Visible only if an LCD is installed
TIME: 30 min
CURRENT CUT-OFF Range: 0.002 to 0.020 pu in steps of 0.001
MESSAGE
LEVEL: 0.020 pu
VOLTAGE CUT-OFF Range: 0.1 to 1.0 V secondary in steps of 0.1
MESSAGE
LEVEL: 1.0 V

Some relay messaging characteristics can be modified to suit different situations using the display properties settings.
• LANGUAGE: This setting selects the language used to display settings, actual values, and targets. The range is
dependent on the order code of the relay.
• FLASH MESSAGE TIME: Flash messages are status, warning, error, or information messages displayed for several
seconds in response to certain key presses during setting programming. These messages override any normal mes-
sages. The duration of a flash message on the display can be changed to accommodate different reading rates.
• DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a
default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough
during programming or reading of actual values.

5-12 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

• DEFAULT MESSAGE INTENSITY: To extend phosphor life in the vacuum fluorescent display, the brightness can be
attenuated during default message display. During keypad interrogation, the display always operates at full brightness.
• SCREEN SAVER FEATURE and SCREEN SAVER WAIT TIME: These settings are only visible if the G60 has a liquid
crystal display (LCD) and control its backlighting. When the SCREEN SAVER FEATURE is “Enabled”, the LCD backlighting
is turned off after the DEFAULT MESSAGE TIMEOUT followed by the SCREEN SAVER WAIT TIME, providing that no keys
have been pressed and no target messages are active. When a keypress occurs or a target becomes active, the LCD
backlighting is turned on.
• CURRENT CUT-OFF LEVEL: This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the
rated value) are very susceptible to noise. Some customers prefer very low currents to display as zero, while others
prefer the current be displayed even when the value reflects noise rather than the actual signal. The G60 applies a cut-
off value to the magnitudes and angles of the measured currents. If the magnitude is below the cut-off level, it is substi-
tuted with zero. This applies to phase and ground current phasors as well as true RMS values and symmetrical compo-
nents. The cut-off operation applies to quantities used for metering, protection, and control, as well as those used by
communications protocols. Note that the cut-off level for the sensitive ground input is 10 times lower that the CURRENT
CUT-OFF LEVEL setting value. Raw current samples available via oscillography are not subject to cut-off.

• VOLTAGE CUT-OFF LEVEL: This setting modifies the voltage cut-off threshold. Very low secondary voltage measure-
ments (at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed
as zero, while others prefer the voltage to be displayed even when the value reflects noise rather than the actual sig-
nal. The G60 applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below
the cut-off level, it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical
components. The cut-off operation applies to quantities used for metering, protection, and control, as well as those
used by communications protocols. Raw samples of the voltages available via oscillography are not subject cut-off.
The CURRENT CUT-OFF LEVEL and the VOLTAGE CUT-OFF LEVEL are used to determine the metered power cut-off levels. The
power cut-off level is calculated as shown below. For Delta connections:

3 × CURRENT CUT-OFF LEVEL × VOLTAGE CUT-OFF LEVEL × VT primary × CT primary-


5
3-phase power cut-off = ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- (EQ 5.3)
VT secondary
For Wye connections:
× CURRENT CUT-OFF LEVEL × VOLTAGE CUT-OFF LEVEL × VT primary × CT primary-
3-phase power cut-off = 3
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- (EQ 5.4)
VT secondary

CUT-OFF LEVEL × VOLTAGE CUT-OFF LEVEL × VT primary × CT primary


per-phase power cut-off = CURRENT
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
- (EQ 5.5)
VT secondary
where VT primary = VT secondary × VT ratio and CT primary = CT secondary × CT ratio.
For example, given the following settings:
CURRENT CUT-OFF LEVEL: “0.02 pu”
VOLTAGE CUT-OFF LEVEL: “1.0 V”
PHASE CT PRIMARY: “100 A”
PHASE VT SECONDARY: “66.4 V”
PHASE VT RATIO: “208.00 : 1"
PHASE VT CONNECTION: “Delta”.

We have:
CT primary = “100 A”, and
VT primary = PHASE VT SECONDARY x PHASE VT RATIO = 66.4 V x 208 = 13811.2 V
The power cut-off is therefore:
power cut-off = (CURRENT CUT-OFF LEVEL × VOLTAGE CUT-OFF LEVEL × CT primary × VT primary)/VT secondary
= ( 3 × 0.02 pu × 1.0 V × 100 A × 13811.2 V) / 66.4 V
= 720.5 watts
Any calculated power value below this cut-off will not be displayed. As well, the three-phase energy data will not accumu-
late if the total power from all three phases does not exceed the power cut-off.

GE Multilin G60 Generator Protection System 5-13


5.2 PRODUCT SETUP 5 SETTINGS

Lower the VOLTAGE CUT-OFF LEVEL and CURRENT CUT-OFF LEVEL with care as the relay accepts lower signals
as valid measurements. Unless dictated otherwise by a specific application, the default settings of “0.02
NOTE
pu” for CURRENT CUT-OFF LEVEL and “1.0 V” for VOLTAGE CUT-OFF LEVEL are recommended.

5.2.3 CLEAR RELAY RECORDS

PATH: SETTINGS Ö PRODUCT SETUP ÖØ CLEAR RELAY RECORDS

„ CLEAR RELAY CLEAR USER REPORTS: Range: FlexLogic™ operand


„ RECORDS Off
CLEAR EVENT RECORDS: Range: FlexLogic™ operand
MESSAGE
Off
CLEAR OSCILLOGRAPHY? Range: FlexLogic™ operand
MESSAGE
No
CLEAR DATA LOGGER: Range: FlexLogic™ operand
MESSAGE
Off
CLEAR ENERGY: Range: FlexLogic™ operand
MESSAGE
Off
RESET UNAUTH ACCESS: Range: FlexLogic™ operand
MESSAGE
Off
CLEAR DIR I/O STATS: Range: FlexLogic™ operand.
MESSAGE Valid only for units with Direct I/O module.
Off
5 Selected records can be cleared from user-programmable conditions with FlexLogic™ operands. Assigning user-program-
mable pushbuttons to clear specific records are typical applications for these commands. Since the G60 responds to rising
edges of the configured FlexLogic™ operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-program-
mable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-programma-
ble pushbuttons can provide extra security if required.
For example, to assign User-Programmable Pushbutton 1 to clear demand records, the following settings should be
applied.
1. Assign the clear demand function to Pushbutton 1 by making the following change in the SETTINGS Ö PRODUCT SETUP
ÖØ CLEAR RELAY RECORDS menu:
CLEAR DEMAND: “PUSHBUTTON 1 ON”

2. Set the properties for User-Programmable Pushbutton 1 by making the following changes in the SETTINGS Ö PRODUCT
SETUP ÖØ USER-PROGRAMMABLE PUSHBUTTONS Ö USER PUSHBUTTON 1 menu:
PUSHBUTTON 1 FUNCTION: “Self-reset”
PUSHBTN 1 DROP-OUT TIME: “0.20 s”

5-14 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

5.2.4 COMMUNICATIONS

a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS

„ COMMUNICATIONS „ SERIAL PORTS


See below.
„ „
„ NETWORK
MESSAGE See page 5–17.
„
„ MODBUS PROTOCOL
MESSAGE See page 5–17.
„
„ DNP PROTOCOL
MESSAGE See page 5–18.
„
„ DNP / IEC104
MESSAGE See page 5–21.
„ POINT LISTS
„ IEC 61850 PROTOCOL
MESSAGE See page 5–22.
„
„ WEB SERVER
MESSAGE See page 5–35.
„ HTTP PROTOCOL
„ TFTP PROTOCOL
MESSAGE See page 5–36.
„

MESSAGE
„ IEC 60870-5-104
See page 5–36. 5
„ PROTOCOL
„ SNTP PROTOCOL
MESSAGE See page 5–37.
„
„ EGD PROTOCOL
MESSAGE See page 5–37.
„
„ ETHERNET SWITCH
MESSAGE See page 5–39.
„

b) SERIAL PORTS
The G60 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for
local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet
or RS485 port. The rear COM2 port be used for either RS485 or RRTD communications.

GE Multilin G60 Generator Protection System 5-15


5.2 PRODUCT SETUP 5 SETTINGS

PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS Ö SERIAL PORTS

„ SERIAL PORTS RS485 COM1 BAUD Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
„ RATE: 19200 28800, 33600, 38400, 57600, 115200. Only
active if CPU Type E is ordered.
RS485 COM1 PARITY: Range: None, Odd, Even
MESSAGE Only active if CPU Type E is ordered
None
RS485 COM1 RESPONSE Range: 0 to 1000 ms in steps of 10
MESSAGE Only active if CPU Type E is ordered
MIN TIME: 0 ms
COM2 USAGE: Range: RS485, RRTD only, GPM-F only,
MESSAGE RRTD & GPM-F
RS485
RRTD SLAVE ADDRESS: Range: 1 to 254 in steps of 1. Shown only if the COM2
MESSAGE USAGE is “RRTD only” or “RRTD & GPM-F”.
254
RS485 COM2 BAUD Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
MESSAGE 28800, 33600, 38400, 57600, 115200. Shown
RATE: 19200
only if the COM2 USAGE is setting is “RS485”.
RRTD BAUD RATE: Range: 1200, 2400, 4800, 9600, 19200. Shown only if
MESSAGE the COM2 USAGE is setting is “RRTD”.
19200
RS485 COM2 PARITY: Range: None, Odd, Even.
MESSAGE
None
RS485 COM2 RESPONSE Range: 0 to 1000 ms in steps of 10
MESSAGE
MIN TIME: 0 ms

5 It is important that the baud rate and parity settings agree with the settings used on the computer or other equipment that is
connected to these ports.
The RS485 ports may be connected to a computer running EnerVista UR Setup. This software can download and upload
setting files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be daisy-chained
and connected to a DCS, PLC or PC using the RS485 ports.
The baud rate for standard RS485 communications can be selected as 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, or 115200 bps. If COM2 is used for both a field ground module (GPM-F) and remote RTD
unit (RRTD), then the RS482 COM2 BAUD RATE is fixed at 19200 bps.
For each RS485 port, the minimum time before the port will transmit after receiving data from a host can be
set. This feature allows operation with hosts which hold the RS485 transmitter active for some time after
NOTE
each transmission.
If the COM2 USAGE setting is “RRTD only”, then the COM2 port is used to monitor the RTDs on a remote RTD unit. The
remote RTD unit uses the Modbus RTU protocol over RS485. The RRTD device must have a unique address from 1 to
254. The baud rate for RRTD communications can be selected as 300, 1200, 2400, 4800, 9600, 14400, or 19200 bps.
If the RS485 COM2 port is used for an RRTD, GPM-F, or RRTD and GPM-F, then there must not be any other devices con-
nected in the daisy-chain for any other purpose. The port is strictly dedicated to RRTD or GPM-F usage when COM2 USAGE
is selected as “RRTD only”, “GPM-F only”, or “RRTD & GPM-F”.
The field ground module (GPM-F) has a fixed slave address of 1. Therefore, the RRTD SLAVE ADDRESS setting is appli-
cable only to the RRTD unit and has a setting rage of 2 to 254 if the COM2 USAGE is set as “RRTD & GPM-F”.
Power must be cycled to the G60 for changes to the COM2 USAGE setting to take effect.

NOTE

5-16 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

c) NETWORK
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK

„ NETWORK IP ADDRESS: Range: Standard IP address format


„ 0.0.0.0 Not shown if CPU Type E is ordered.

SUBNET IP MASK: Range: Standard IP address format


MESSAGE Not shown if CPU Type E is ordered.
0.0.0.0
GATEWAY IP ADDRESS: Range: Standard IP address format
MESSAGE Not shown if CPU Type E is ordered.
0.0.0.0
„ OSI NETWORK Range: Select to enter the OSI NETWORK ADDRESS.
MESSAGE Not shown if CPU Type E is ordered.
„ ADDRESS (NSAP)
ETHERNET OPERATION Range: Half-Duplex, Full-Duplex
MESSAGE Not shown if CPU Type E or N is ordered.
MODE: Full-Duplex

These messages appear only if the G60 is ordered with an Ethernet card.
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, and HTTP protocols. The
NSAP address is used with the IEC 61850 protocol over the OSI (CLNP/TP4) stack only. Each network protocol has a set-
ting for the TCP/UDP port number. These settings are used only in advanced network configurations and should normally
be left at their default values, but may be changed if required (for example, to allow access to multiple UR-series relays
behind a router). By setting a different TCP/UDP PORT NUMBER for a given protocol on each UR-series relay, the router can
map the relays to the same external IP address. The client software (EnerVista UR Setup, for example) must be configured
to use the correct port number if these settings are used.
When the NSAP address, any TCP/UDP port number, or any user map setting (when used with DNP) is changed, it
will not become active until power to the relay has been cycled (off-on). 5
NOTE
Do not set more than one protocol to the same TCP/UDP PORT NUMBER, as this will result in unreliable opera-
tion of those protocols.
WARNING

d) MODBUS PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ MODBUS PROTOCOL

„ MODBUS PROTOCOL MODBUS SLAVE Range: 1 to 254 in steps of 1


„ ADDRESS: 254
MODBUS TCP PORT Range: 1 to 65535 in steps of 1
MESSAGE
NUMBER: 502

The serial communication ports utilize the Modbus protocol, unless configured for DNP or IEC 60870-5-104 operation (see
descriptions below). This allows the EnerVista UR Setup software to be used. The UR operates as a Modbus slave device
only. When using Modbus protocol on the RS232 port, the G60 will respond regardless of the MODBUS SLAVE ADDRESS pro-
grammed. For the RS485 ports each G60 must have a unique address from 1 to 254. Address 0 is the broadcast address
which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same
address or conflicts resulting in errors will occur. Generally, each device added to the link should use the next higher
address starting at 1. Refer to Appendix B for more information on the Modbus protocol.
Changes to the MODBUS TCP PORT NUMBER setting will not take effect until the G60 is restarted.

NOTE

GE Multilin G60 Generator Protection System 5-17


5.2 PRODUCT SETUP 5 SETTINGS

e) DNP PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP PROTOCOL

„ DNP PROTOCOL „ DNP CHANNELS Range: see sub-menu below


„ „
DNP ADDRESS: Range: 0 to 65519 in steps of 1
MESSAGE
65519
„ DNP NETWORK Range: see sub-menu below
MESSAGE
„ CLIENT ADDRESSES
DNP TCP/UDP PORT Range: 1 to 65535 in steps of 1
MESSAGE
NUMBER: 20000
DNP UNSOL RESPONSE Range: Enabled, Disabled
MESSAGE
FUNCTION: Disabled
DNP UNSOL RESPONSE Range: 0 to 60 s in steps of 1
MESSAGE
TIMEOUT: 5 s
DNP UNSOL RESPONSE Range: 1 to 255 in steps of 1
MESSAGE
MAX RETRIES: 10
DNP UNSOL RESPONSE Range: 0 to 65519 in steps of 1
MESSAGE
DEST ADDRESS: 1
DNP CURRENT SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
MESSAGE 100000
FACTOR: 1
5 DNP VOLTAGE SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
MESSAGE 100000
FACTOR: 1
DNP POWER SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
MESSAGE 100000
FACTOR: 1
DNP ENERGY SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
MESSAGE 100000
FACTOR: 1
DNP PF SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
MESSAGE 100000
FACTOR: 1
DNP OTHER SCALE Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
MESSAGE 100000
FACTOR: 1
DNP CURRENT DEFAULT Range: 0 to 100000000 in steps of 1
MESSAGE
DEADBAND: 30000
DNP VOLTAGE DEFAULT Range: 0 to 100000000 in steps of 1
MESSAGE
DEADBAND: 30000
DNP POWER DEFAULT Range: 0 to 100000000 in steps of 1
MESSAGE
DEADBAND: 30000
DNP ENERGY DEFAULT Range: 0 to 100000000 in steps of 1
MESSAGE
DEADBAND: 30000
DNP PF DEFAULT Range: 0 to 100000000 in steps of 1
MESSAGE
DEADBAND: 30000
DNP OTHER DEFAULT Range: 0 to 100000000 in steps of 1
MESSAGE
DEADBAND: 30000
DNP TIME SYNC IIN Range: 1 to 10080 min. in steps of 1
MESSAGE
PERIOD: 1440 min

5-18 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

DNP MESSAGE FRAGMENT Range: 30 to 2048 in steps of 1


MESSAGE
SIZE: 240
DNP OBJECT 1 Range: 1, 2
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 2 Range: 1, 2
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 20 Range: 1, 2, 5, 6
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 21 Range: 1, 2, 9, 10
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 22 Range: 1, 2, 5, 6
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 23 Range: 1, 2, 5, 6
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 30 Range: 1, 2, 3, 4, 5
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 32 Range: 1, 2, 3, 4, 5, 7
MESSAGE
DEFAULT VARIATION: 1
DNP NUMBER OF PAIRED Range: 0 to 32 in steps of 1
MESSAGE
CONTROL POINTS: 0
DNP TCP CONNECTION Range: 10 to 300 s in steps of 1 5
MESSAGE
TIMEOUT: 120 s

The G60 supports the Distributed Network Protocol (DNP) version 3.0. The G60 can be used as a DNP slave device con-
nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the G60 maintains two sets of DNP
data change buffers and connection information, two DNP masters can actively communicate with the G60 at one time.
The IEC 60870-5-104 and DNP protocols cannot be simultaneously. When the IEC 60870-5-104 FUNCTION set-
ting is set to “Enabled”, the DNP protocol will not be operational. When this setting is changed it will not
NOTE
become active until power to the relay has been cycled (off-to-on).
The DNP Channels sub-menu is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP PROTOCOL Ö DNP CHANNELS

„ DNP CHANNELS DNP CHANNEL 1 PORT: Range: NONE, COM1 - RS485, COM2 - RS485,
„ NETWORK FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
DNP CHANNEL 2 PORT: Range: NONE, COM1 - RS485, COM2 - RS485,
MESSAGE FRONT PANEL - RS232, NETWORK - TCP,
COM2 - RS485
NETWORK - UDP

The DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings select the communications port assigned to the DNP protocol
for each channel. Once DNP is assigned to a serial port, the Modbus protocol is disabled on that port. Note that COM1 can
be used only in non-Ethernet UR relays. When this setting is set to “Network - TCP”, the DNP protocol can be used over
TCP/IP on channels 1 or 2. When this value is set to “Network - UDP”, the DNP protocol can be used over UDP/IP on chan-
nel 1 only. Refer to Appendix E for additional information on the DNP protocol.
Changes to the DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings will take effect only after power has
been cycled to the relay.
NOTE

The DNP NETWORK CLIENT ADDRESS settings can force the G60 to respond to a maximum of five specific DNP masters. The
settings in this sub-menu are shown below.

GE Multilin G60 Generator Protection System 5-19


5.2 PRODUCT SETUP 5 SETTINGS

PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP PROTOCOL Ö DNP NETWORK CLIENT ADDRESSES

„ DNP NETWORK CLIENT ADDRESS 1: Range: standard IP address


„ CLIENT ADDRESSES 0.0.0.0
CLIENT ADDRESS 2: Range: standard IP address
MESSAGE
0.0.0.0
CLIENT ADDRESS 3: Range: standard IP address
MESSAGE
0.0.0.0
CLIENT ADDRESS 4: Range: standard IP address
MESSAGE
0.0.0.0
CLIENT ADDRESS 5: Range: standard IP address
MESSAGE
0.0.0.0

The DNP UNSOL RESPONSE FUNCTION should be “Disabled” for RS485 applications since there is no collision avoidance
mechanism. The DNP UNSOL RESPONSE TIMEOUT sets the time the G60 waits for a DNP master to confirm an unsolicited
response. The DNP UNSOL RESPONSE MAX RETRIES setting determines the number of times the G60 retransmits an unsolic-
ited response without receiving confirmation from the master; a value of “255” allows infinite re-tries. The DNP UNSOL
RESPONSE DEST ADDRESS is the DNP address to which all unsolicited responses are sent. The IP address to which unsolic-
ited responses are sent is determined by the G60 from the current TCP connection or the most recent UDP message.
The DNP scale factor settings are numbers used to scale analog input point values. These settings group the G60 analog
input data into the following types: current, voltage, power, energy, power factor, and other. Each setting represents the
scale factor for all analog input points of that type. For example, if the DNP VOLTAGE SCALE FACTOR setting is set to “1000”,
all DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000
5 V on the G60 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer-
tain ranges in DNP masters. Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (that is, the value will be 10
times larger).
The DNP DEFAULT DEADBAND settings determine when to trigger unsolicited responses containing analog input data. These
settings group the G60 analog input data into the following types: current, voltage, power, energy, power factor, and other.
Each setting represents the default deadband value for all analog input points of that type. For example, to trigger unsolic-
ited responses from the G60 when any current values change by 15 A, the DNP CURRENT DEFAULT DEADBAND setting
should be set to “15”. Note that these settings are the deadband default values. DNP object 34 points can be used to
change deadband values, from the default, for each individual DNP analog input point. Whenever power is removed and
re-applied to the G60, the default deadbands will be in effect.
The DNP TIME SYNC IIN PERIOD setting determines how often the Need Time Internal Indication (IIN) bit is set by the G60.
Changing this time allows the DNP master to send time synchronization commands more or less often, as required.
The DNP MESSAGE FRAGMENT SIZE setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer confirmations to be
necessary which can provide for more robust data transfer over noisy communication channels.
When the DNP data points (analog inputs and/or binary inputs) are configured for Ethernet-enabled relays,
check the “DNP Points Lists” G60 web page to view the points lists. This page can be viewed with a web
NOTE
browser by entering the G60 IP address to access the G60 “Main Menu”, then by selecting the “Device
Information Menu” > “DNP Points Lists” menu item.
The DNP OBJECT 1 DEFAULT VARIATION to DNP OBJECT 32 DEFAULT VARIATION settings allow the user to select the DNP
default variation number for object types 1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation
response when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Refer to the DNP implementation section in
appendix E for additional details.
The DNP binary outputs typically map one-to-one to IED data points. That is, each DNP binary output controls a single
physical or virtual control point in an IED. In the G60 relay, DNP binary outputs are mapped to virtual inputs. However,
some legacy DNP implementations use a mapping of one DNP binary output to two physical or virtual control points to sup-
port the concept of trip/close (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the
DNP master can operate a single point for both trip and close, or raise and lower, operations. The G60 can be configured to

5-20 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

support paired control points, with each paired control point operating two virtual inputs. The DNP NUMBER OF PAIRED CON-
TROL POINTS setting allows configuration of from 0 to 32 binary output paired controls. Points not configured as paired oper-
ate on a one-to-one basis.
The DNP ADDRESS setting is the DNP slave address. This number identifies the G60 on a DNP communications link. Each
DNP slave should be assigned a unique address.
The DNP TCP CONNECTION TIMEOUT setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by this setting, the connection will be
aborted by the G60. This frees up the connection to be re-used by a client.
Relay power must be re-cycled after changing the DNP TCP CONNECTION TIMEOUT setting for the changes to take
effect.
NOTE

f) DNP / IEC 60870-5-104 POINT LISTS


PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT LISTS

„ DNP / IEC104 „ BINARY INPUT / MSP Range: see sub-menu below


„ POINT LISTS „ POINTS
„ ANALOG INPUT / MME Range: see sub-menu below
MESSAGE
„ POINTS

The binary and analog inputs points for the DNP protocol, or the MSP and MME points for IEC 60870-5-104 protocol, can
configured to a maximum of 256 points. The value for each point is user-programmable and can be configured by assigning
FlexLogic™ operands for binary inputs / MSP points or FlexAnalog parameters for analog inputs / MME points.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT LISTS Ö BINARY INPUT / MSP POINTS 5
„ BINARY INPUT / MSP Point: 0 Range: FlexLogic™ operand
„ POINTS Off
Point: 1 Range: FlexLogic™ operand
MESSAGE
Off

Point: 255 Range: FlexLogic™ operand


MESSAGE
Off

Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic™ operand. Refer to the Introduction to FlexLogic™ section in this chapter for the full
range of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT LISTS ÖØ ANALOG INPUT / MME POINTS

„ ANALOG INPUT / MME Point: 0 Range: any FlexAnalog parameter


„ POINTS Off
Point: 1 Range: any FlexAnalog parameter
MESSAGE
Off

Point: 255 Range: any FlexAnalog parameter


MESSAGE
Off

Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.

GE Multilin G60 Generator Protection System 5-21


5.2 PRODUCT SETUP 5 SETTINGS

The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP /
IEC 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point
NOTE are ignored.
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the G60 is restarted.

NOTE

g) IEC 61850 PROTOCOL


PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL

„ IEC 61850 PROTOCOL „ GSSE / GOOSE


„ „ CONFIGURATION
„ SERVER
MESSAGE
„ CONFIGURATION
„ IEC 61850 LOGICAL
MESSAGE
„ NODE NAME PREFIXES
„ MMXU DEADBANDS
MESSAGE
„
„ GGIO1 STATUS
MESSAGE
„ CONFIGURATION
„ GGIO2 CONTROL
MESSAGE
„ CONFIGURATION
5 MESSAGE
„ GGIO4 ANALOG
„ CONFIGURATION
„ GGIO5 UINTEGER
MESSAGE
„ CONFIGURATION
„ REPORT CONTROL
MESSAGE
„ CONFIGURATION
„ XCBR
MESSAGE
„ CONFIGURATION
„ XSWI
MESSAGE
„ CONFIGURATION

The G60 Generator Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.

The G60 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The G60 operates as an IEC 61850
server. The Remote inputs and outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION

„ GSSE / GOOSE „ TRANSMISSION


„ CONFIGURATION „
„ RECEPTION
MESSAGE
„

The main transmission menu is shown below:

5-22 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
Ö TRANSMISSION
„ TRANSMISSION „ GENERAL
„ „
„ GSSE
MESSAGE
„
„ FIXED GOOSE
MESSAGE
„
„ CONFIGURABLE
MESSAGE
„ GOOSE

The general transmission settings are shown below:


PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
Ö TRANSMISSION Ö GENERAL
„ GENERAL DEFAULT GSSE/GOOSE Range: 1 to 60 s in steps of 1
„ UPDATE TIME: 60 s

The DEFAULT GSSE/GOOSE UPDATE TIME sets the time between GSSE or GOOSE messages when there are no remote out-
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state heartbeat time interval.
The DEFAULT GSSE/GOOSE UPDATE TIME setting is applicable to GSSE, fixed G60 GOOSE, and configurable GOOSE.
The GSSE settings are shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
5
Ö TRANSMISSION ÖØ GSEE
„ GSSE GSSE FUNCTION: Range: Enabled, Disabled
„ Enabled
GSSE ID: Range: 65-character ASCII string
MESSAGE
GSSEOut
DESTINATION MAC: Range: standard MAC address
MESSAGE
000000000000

These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The GSSE ID setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
string identifies the GSSE message to the receiving device. In G60 releases previous to 5.0x, this name string was repre-
sented by the RELAY NAME setting.

GE Multilin G60 Generator Protection System 5-23


5.2 PRODUCT SETUP 5 SETTINGS

The fixed GOOSE settings are shown below:


PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
Ö TRANSMISSION ÖØ FIXED GOOSE
„ FIXED GOOSE GOOSE FUNCTION: Range: Enabled, Disabled
„ Disabled
GOOSE ID: Range: 65-character ASCII string
MESSAGE
GOOSEOut
DESTINATION MAC: Range: standard MAC address
MESSAGE
000000000000
GOOSE VLAN PRIORITY: Range: 0 to 7 in steps of 1
MESSAGE
4
GOOSE VLAN ID: Range: 0 to 4095 in steps of 1
MESSAGE
0
GOOSE ETYPE APPID: Range: 0 to 16383 in steps of 1
MESSAGE
0

These settings are applicable to fixed (DNA/UserSt) GOOSE only.


The GOOSE ID setting represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE
message. This string identifies the GOOSE message to the receiving device. In revisions previous to 5.0x, this name string
was represented by the RELAY NAME setting.
The DESTINATION MAC setting allows the destination Ethernet MAC address to be set. This address must be a multicast
5 address; the least significant bit of the first byte must be set. In G60 releases previous to 5.0x, the destination Ethernet
MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of
the G60) and setting the multicast bit.
The GOOSE VLAN PRIORITY setting indicates the Ethernet priority of GOOSE messages. This allows GOOSE messages to
have higher priority than other Ethernet data. The GOOSE ETYPE APPID setting allows the selection of a specific application
ID for each GOOSE sending device. This value can be left at its default if the feature is not required. Both the GOOSE VLAN
PRIORITY and GOOSE ETYPE APPID settings are required by IEC 61850.

5-24 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

The configurable GOOSE settings are shown below.


PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLE GOOSE 1(8)
„ CONFIGURABLE CONFIG GSE 1 Range: Enabled, Disabled
„ GOOSE 1 FUNCTION: Enabled
CONFIG GSE 1 ID: Range: 65-character ASCII string
MESSAGE
GOOSEOut_1
CONFIG GSE 1 DST MAC: Range: standard MAC address
MESSAGE
010CDC010000
CONFIG GSE 1 Range: 0 to 7 in steps of 1
MESSAGE
VLAN PRIORITY: 4
CONFIG GSE 1 Range: 0 to 4095 in steps of 1
MESSAGE
VLAN ID: 0
CONFIG GSE 1 Range: 0 to 16383 in steps of 1
MESSAGE
ETYPE APPID: 0
CONFIG GSE 1 Range: 0 to 4294967295 in steps of 1
MESSAGE
CONFREV: 1
CONFIG GSE 1 RESTRANS Range: Aggressive, Medium, Relaxed, Heartbeat
MESSAGE
CURVE: Relaxed
„ CONFIG GSE 1 Range: 64 data items; each can be set to all valid MMS
MESSAGE
„ DATASET ITEMS data item references for transmitted data
5
The configurable GOOSE settings allow the G60 to be configured to transmit a number of different datasets within IEC
61850 GOOSE messages. Up to eight different configurable datasets can be configured and transmitted. This is useful for
intercommunication between G60 IEDs and devices from other manufacturers that support IEC 61850.
The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the G60.
The G60 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data
transfer between devices.
Items programmed for dataset 1 and 2 will have changes in their status transmitted as soon as the change is detected.
Datasets 1 and 2 should be used for high-speed transmission of data that is required for applications such as transfer trip-
ping, blocking, and breaker fail initiate. At least one digital status value needs to be configured in the required dataset to
enable transmission of configured data. Configuring analog data only to dataset 1 or 2 will not activate transmission.
Items programmed for datasets 3 through 8 will have changes in their status transmitted at a maximum rate of every
100 ms. Datasets 3 through 8 will regularly analyze each data item configured within them every 100 ms to identify if any
changes have been made. If any changes in the data items are detected, these changes will be transmitted through a
GOOSE message. If there are no changes detected during this 100 ms period, no GOOSE message will be sent.
For all datasets 1 through 8, the integrity GOOSE message will still continue to be sent at the pre-configured rate even if no
changes in the data items are detected.
The GOOSE functionality was enhanced to prevent the relay from flooding a communications network with GOOSE mes-
sages due to an oscillation being created that is triggering a message.
The G60 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be
caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station
components. If erroneously oscillation is detected, the G60 will stop sending GOOSE messages from the dataset for a min-
imum period of one second. Should the oscillation persist after the one second time-out period, the G60 will continue to
block transmission of the dataset. The G60 will assert the MAINTENANCE ALERT: GGIO Ind XXX oscill self-test error mes-
sage on the front panel display, where XXX denotes the data item detected as oscillating.
For versions 5.70 and higher, the G60 supports four retransmission schemes: aggressive, medium, relaxed, and heartbeat.
The aggressive scheme is only supported in fast type 1A GOOSE messages (GOOSEOut 1 and GOOSEOut 2). For slow
GOOSE messages (GOOSEOut 3 to GOOSEOut 8) the aggressive scheme is the same as the medium scheme.

GE Multilin G60 Generator Protection System 5-25


5.2 PRODUCT SETUP 5 SETTINGS

The details about each scheme are shown in the following table.

Table 5–1: GOOSE RETRANSMISSION SCHEMES


SCHEME SQ NUM TIME FROM THE TIME BETWEEN COMMENT TIME ALLOWED TO LIVE
EVENT MESSAGES IN MESSAGE
Aggressive 0 0 ms 0 ms Event 2000 ms
1 4 ms 4 ms T1 2000 ms
2 8 ms 4 ms T1 2000 ms
3 16 ms 8 ms T2 Heartbeat * 4, 5
4 Heartbeat Heartbeat T0 Heartbeat * 4, 5
5 Heartbeat Heartbeat T0 Heartbeat * 4, 5
Medium 0 0 ms 0 ms Event 2000 ms
1 16 ms 16 ms T1 2000 ms
2 32 ms 16 ms T1 2000 ms
3 64 ms 32 ms T2 Heartbeat * 4, 5
4 Heartbeat Heartbeat T0 Heartbeat * 4, 5
5 Heartbeat Heartbeat T0 Heartbeat * 4, 5
Relaxed 0 0 ms 0 ms Event 2000 ms
1 100 ms 100 ms T1 2000 ms
2 200 ms 100 ms T1 2000 ms
3 700 ms 500 ms T2 Heartbeat * 4, 5
4 Heartbeat Heartbeat T0 Heartbeat * 4, 5
5 5 Heartbeat Heartbeat T0 Heartbeat * 4, 5
Heartbeat 0 0 ms 0 ms Event 2000 ms
1 Heartbeat Heartbeat T1 2000 ms
2 Heartbeat Heartbeat T1 2000 ms
3 Heartbeat Heartbeat T2 Heartbeat * 4, 5
4 Heartbeat Heartbeat T0 Heartbeat * 4, 5
5 Heartbeat Heartbeat T0 Heartbeat * 4, 5

The configurable GOOSE feature is recommended for applications that require GOOSE data transfer between UR-series
IEDs and devices from other manufacturers. Fixed GOOSE is recommended for applications that require GOOSE data
transfer between UR-series IEDs.
IEC 61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the
successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact
match in terms of data structure, and that the GOOSE addresses and name strings match exactly. Manual configuration is
possible, but third-party substation configuration software may be used to automate the process. The EnerVista UR Setup
software can produce IEC 61850 ICD files and import IEC 61850 SCD files produced by a substation configurator (refer to
the IEC 61850 IED configuration section later in this appendix).
The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. The
general steps required for transmission configuration are:
1. Configure the transmission dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
The general steps required for reception configuration are:
1. Configure the reception dataset.
2. Configure the GOOSE service settings.
3. Configure the data.

5-26 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status
value, its associated quality flags, and a floating point analog value.
The following procedure illustrates the transmission configuration.
1. Configure the transmission dataset by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION ÖØ
IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLE
GOOSE 1 ÖØ CONFIG GSE 1 DATASET ITEMS settings menu:

– Set ITEM 1 to “GGIO1.ST.Ind1.q” to indicate quality flags for GGIO1 status indication 1.
– Set ITEM 2 to “GGIO1.ST.Ind1.stVal” to indicate the status value for GGIO1 status indication 1.
– Set ITEM 3 to “MMXU1.MX.Hz.mag.f” to indicate the analog frequency magnitude for MMXU1 (the metered fre-
quency for SRC1).
The transmission dataset now contains a quality flag, a single point status Boolean value, and a floating point analog
value. The reception dataset on the receiving device must exactly match this structure.
2. Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION
ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGU-
RABLE GOOSE 1 settings menu:

– Set CONFIG GSE 1 FUNCTION to “Enabled”.


– Set CONFIG GSE 1 ID to an appropriate descriptive string (the default value is “GOOSEOut_1”).
– Set CONFIG GSE 1 DST MAC to a multicast address (for example, 01 00 00 12 34 56).
– Set the CONFIG GSE 1 VLAN PRIORITY; the default value of “4” is OK for this example.
– Set the CONFIG GSE 1 VLAN ID value; the default value is “0”, but some switches may require this value to be “1”.
– Set the CONFIG GSE 1 ETYPE APPID value. This setting represents the ETHERTYPE application ID and must match 5
the configuration on the receiver (the default value is “0”).
– Set the CONFIG GSE 1 CONFREV value. This value changes automatically as described in IEC 61850 part 7-2. For
this example it can be left at its default value.
3. Configure the data by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION ÖØ IEC 61850 PROTO-
COL Ö GGIO1 STATUS CONFIGURATION settings menu:
– Set GGIO1 INDICATION 1 to a FlexLogic™ operand used to provide the status of GGIO1.ST.Ind1.stVal (for example,
a contact input, virtual input, a protection element status, etc.).
4. Configure the MMXU1 Hz Deadband by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION ÖØ
IEC 61850 PROTOCOL ÖØ MMXU DEADBANDSÖØ MMXU1 DEADBANDS settings menu:
– Set MMXU1 HZ DEADBAND to “0.050%”. This will result in an update to the MMXU1.MX.mag.f analog value with a
change greater than 45 mHz, from the previous MMXU1.MX.mag.f value, in the source frequency.
The G60 must be rebooted (control power removed and re-applied) before these settings take effect.
The following procedure illustrates the reception configuration.
1. Configure the reception dataset by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION ÖØ IEC
61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION ÖØ RECEPTION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLE GOOSE
1 ÖØ CONFIG GSE 1 DATASET ITEMS settings menu:

– Set ITEM 1 to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.
– Set ITEM 2 to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.
– Set ITEM 3 to “GGIO3.MX.AnIn1.mag.f” to indicate the analog magnitude for GGIO3 analog input 1.
The reception dataset now contains a quality flag, a single point status Boolean value, and a floating point analog
value. This matches the transmission dataset configuration above.
2. Configure the GOOSE service settings by making the following changes in the INPUTS/OUTPUTS ÖØ REMOTE DEVICES
ÖØ REMOTE DEVICE 1 settings menu:
– Set REMOTE DEVICE 1 ID to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.

GE Multilin G60 Generator Protection System 5-27


5.2 PRODUCT SETUP 5 SETTINGS

– Set REMOTE DEVICE 1 ETYPE APPID to match the ETHERTYPE application ID from the transmitting device. This is
“0” in the example above.
– Set the REMOTE DEVICE 1 DATASET value. This value represents the dataset number in use. Since we are using
configurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.
3. Configure the Boolean data by making the following changes in the INPUTS/OUTPUTS ÖØ REMOTE INPUTS ÖØ REMOTE
INPUT 1settings menu:
– Set REMOTE IN 1 DEVICE to “GOOSEOut_1”.
– Set REMOTE IN 1 ITEM to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point status
item to remote input 1.
4. Configure the analog data by making the following changes in the INPUTS/OUTPUTS ÖØ IEC 61850 GOOSE ANALOG
INPUTS settings menu:
– Set the IEC61850 GOOSE ANALOG INPUT 1 DEFAULT VALUE to “60.000”.
– Enter “Hz” for the IEC61850 GOOSE ANALOG INPUT 1 UNITS setting.
The GOOSE analog input 1 can now be used as a FlexAnalog™ value in a FlexElement™ or in other settings. The G60
must be rebooted (control power removed and re-applied) before these settings take effect.
The value of GOOSE analog input 1 in the receiving device will be determined by the MMXU1.MX.Hz.mag.f value in the
sending device. This MMXU value is determined by the source 1 frequency value and the MMXU Hz deadband setting of
the sending device.
Remote input 1 can now be used in FlexLogic™ equations or other settings. The G60 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
5 in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
For intercommunication between G60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages. All GOOSE messages transmitted by the
G60 (DNA/UserSt dataset and configurable datasets) use the IEC 61850 GOOSE messaging services (for example, VLAN
support).
Set the CONFIG GSE 1 FUNCTION function to “Disabled” when configuration changes are required. Once changes are
entered, return the CONFIG GSE 1 FUNCTION to “Enabled” and restart the unit for changes to take effect.
NOTE

PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLE GOOSE 1(8) ÖØ CONFIG GSE 1(64) DATA ITEMS
„ CONFIG GSE 1 ITEM 1: Range: all valid MMS data item references for
„ DATASET ITEMS GGIO1.ST.Ind1.stVal transmitted data

ITEM 2: Range: all valid MMS data item references for


MESSAGE transmitted data
GGIO1.ST.IndPos1.stV
ITEM 3: Range: all valid MMS data item references for
MESSAGE transmitted data
None

ITEM 64: Range: all valid MMS data item references for
MESSAGE transmitted data
None

To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status indication and its associated qual-
ity flags, the following dataset items can be selected: “GGIO1.ST.Ind1.stVal” and “GGIO1.ST.Ind1.q”. The G60 will then cre-
ate a dataset containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic™
operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con-
taining the defined dataset.

5-28 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

The main reception menu is applicable to configurable GOOSE only and contains the configurable GOOSE dataset items
for reception:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION
Ö RECEPTION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLE GOOSE 1(16) ÖØ CONFIG GSE 1(32) DATA ITEMS
„ CONFIG GSE 1 ITEM 1: Range: all valid MMS data item references for
„ DATASET ITEMS GGIO3.ST.Ind1.stVal transmitted data

ITEM 2: Range: all valid MMS data item references for


MESSAGE transmitted data
GGIO3.ST.IndPos1.stV
ITEM 3: Range: all valid MMS data item references for
MESSAGE transmitted data
None

ITEM 32: Range: all valid MMS data item references for
MESSAGE transmitted data
None

The configurable GOOSE settings allow the G60 to be configured to receive a number of different datasets within IEC
61850 GOOSE messages. Up to sixteen different configurable datasets can be configured for reception. This is useful for
intercommunication between G60 IEDs and devices from other manufacturers that support IEC 61850.
For intercommunication between G60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages.
To set up a G60 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the
following dataset items can be selected (for example, for configurable GOOSE dataset 1): “GGIO3.ST.Ind1.stVal” and
“GGIO3.ST.Ind2.stVal”. The G60 will then create a dataset containing these two data items. The Boolean status values
from these data items can be utilized as remote input FlexLogic™ operands. First, the REMOTE DEVICE 1(16) DATASET setting 5
must be set to contain dataset “GOOSEIn 1” (that is, the first configurable dataset). Then REMOTE IN 1(16) ITEM settings
must be set to “Dataset Item 1” and “Dataset Item 2”. These remote input FlexLogic™ operands will then change state in
accordance with the status values of the data items in the configured dataset.
Double-point status values may be included in the GOOSE dataset. Received values are populated in the
GGIO3.ST.IndPos1.stVal and higher items.
Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non-
instantaneous) values can be transmitted. Received values are used to populate the GGIO3.MX.AnIn1 and higher items.
Received values are also available as FlexAnalog™ parameters (GOOSE analog In1 and up).
GGIO3.MX.AnIn1 to GGIO3.MX.AnIn32 can only be used once for all sixteen reception datasets.

NOTE

The main menu for the IEC 61850 server configuration is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ SERVER CONFIGURATION

„ SERVER IED NAME: IECDevice Range: up to 32 alphanumeric characters


„ CONFIGURATION

LD INST: LDInst Range: up to 32 alphanumeric characters


MESSAGE

LOCATION: Location Range: up to 80 alphanumeric characters


MESSAGE

IEC/MMS TCP PORT Range: 1 to 65535 in steps of 1


MESSAGE
NUMBER: 102

INCLUDE NON-IEC Range: Disabled, Enabled


MESSAGE
DATA: Enabled

SERVER SCANNING: Range: Disabled, Enabled


MESSAGE
Disabled

GE Multilin G60 Generator Protection System 5-29


5.2 PRODUCT SETUP 5 SETTINGS

The IED NAME and LD INST settings represent the MMS domain name (IEC 61850 logical device) where all IEC/MMS logical
nodes are located. Valid characters for these values are upper and lowercase letters, numbers, and the underscore (_)
character, and the first character in the string must be a letter. This conforms to the IEC 61850 standard. The LOCATION is a
variable string and can be composed of ASCII characters. This string appears within the PhyName of the LPHD node.
The IEC/MMS TCP PORT NUMBER setting allows the user to change the TCP port number for MMS connections. The INCLUDE
NON-IEC DATA setting determines whether or not the “UR” MMS domain will be available. This domain contains a large num-
ber of UR-series specific data items that are not available in the IEC 61850 logical nodes. This data does not follow the IEC
61850 naming conventions. For communications schemes that strictly follow the IEC 61850 standard, this setting should be
“Disabled”.
The SERVER SCANNING feature should be set to “Disabled” when IEC 61850 client/server functionality is not required. IEC
61850 has two modes of functionality: GOOSE/GSSE inter-device communication and client/server communication. If the
GOOSE/GSSE functionality is required without the IEC 61850 client server feature, then server scanning can be disabled
to increase CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta-
tus values in the G60. Clients will still be able to connect to the server (G60 relay), but most data values will not be updated.
This setting does not affect GOOSE/GSSE operation.
Changes to the IED NAME setting, LD INST setting, and GOOSE dataset will not take effect until the G60 is restarted.

NOTE

The main menu for the IEC 61850 logical node name prefixes is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL
ÖØ IEC 61850 LOGICAL NODE NAME PREFIXES
„ IEC 61850 LOGICAL „ PIOC LOGICAL NODE
„ NODE NAME PREFIXES „ NAME PREFIXES
5 „ PTOC LOGICAL NODE
MESSAGE
„ NAME PREFIXES

„ PTRC LOGICAL NODE


MESSAGE
„ NAME PREFIXES

The IEC 61850 logical node name prefix settings are used to create name prefixes to uniquely identify each logical node.
For example, the logical node “PTOC1” may have the name prefix “abc”. The full logical node name will then be
“abcMMXU1”. Valid characters for the logical node name prefixes are upper and lowercase letters, numbers, and the
underscore (_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard.
Changes to the logical node prefixes will not take effect until the G60 is restarted.
The main menu for the IEC 61850 MMXU deadbands is shown below.
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ MMXU DEADBANDS

„ MMXU DEADBANDS „ MMXU1 DEADBANDS


„ „

„ MMXU2 DEADBANDS
MESSAGE
„

„ MMXU3 DEADBANDS
MESSAGE
„

„ MMXU4 DEADBANDS
MESSAGE
„

The MMXU deadband settings represent the deadband values used to determine when the update the MMXU “mag” and
“cVal” values from the associated “instmag” and “instcVal” values. The “mag” and “cVal” values are used for the IEC 61850
buffered and unbuffered reports. These settings correspond to the associated “db” data items in the CF functional con-

5-30 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

straint of the MMXU logical node, as per the IEC 61850 standard. According to IEC 61850-7-3, the db value “shall repre-
sent the percentage of difference between the maximum and minimum in units of 0.001%”. Thus, it is important to know the
maximum value for each MMXU measured quantity, since this represents the 100.00% value for the deadband.
The minimum value for all quantities is 0; the maximum values are as follows:
• phase current: 46 × phase CT primary setting
• neutral current: 46 × ground CT primary setting
• voltage: 275 × VT ratio setting
• power (real, reactive, and apparent): 46 × phase CT primary setting × 275 × VT ratio setting
• frequency: 90 Hz
• power factor: 2
The GGIO1 status configuration points are shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ GGIO1 STATUS CONFIGURATION

„ GGIO1 STATUS NUMBER OF STATUS Range: 8 to 128 in steps of 8


„ CONFIGURATION POINTS IN GGIO1: 8

GGIO1 INDICATION 1 Range: FlexLogic™ operand


MESSAGE
Off

GGIO1 INDICATION 2 Range: FlexLogic™ operand


MESSAGE
Off

GGIO1 INDICATION 3 Range: FlexLogic™ operand


MESSAGE
Off 5

GGIO1 INDICATION 128 Range: FlexLogic™ operand


MESSAGE
Off

The NUMBER OF STATUS POINTS IN GGIO1 setting specifies the number of “Ind” (single point status indications) that are
instantiated in the GGIO1 logical node. Changes to the NUMBER OF STATUS POINTS IN GGIO1 setting will not take effect until
the G60 is restarted.
The GGIO2 control configuration points are shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ GGIO2 CONTROL CONFIGURATION
Ö GGIO2 CF SPSCO 1(64)
„ GGIO2 CF SPCSO 1 GGIO2 CF SPCSO 1 Range: 0, 1, or 2
„ CTLMODEL: 1

The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0”
(status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the G60
virtual inputs.

GE Multilin G60 Generator Protection System 5-31


5.2 PRODUCT SETUP 5 SETTINGS

The GGIO4 analog configuration points are shown below:


PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ GGIO4 ANALOG CONFIGURATION

„ GGIO4 ANALOG NUMBER OF ANALOG Range: 4 to 32 in steps of 4


„ CONFIGURATION POINTS IN GGIO4: 8

„ GGIO4 ANALOG 1
MESSAGE
„ MEASURED VALUE

„ GGIO4 ANALOG 2
MESSAGE
„ MEASURED VALUE

„ GGIO4 ANALOG 3
MESSAGE
„ MEASURED VALUE

„ GGIO4 ANALOG 32
MESSAGE
„ MEASURED VALUE

The NUMBER OF ANALOG POINTS setting determines how many analog data points will exist in GGIO4. When this value is
changed, the G60 must be rebooted in order to allow the GGIO4 logical node to be re-instantiated and contain the newly
configured number of analog points.
The measured value settings for each of the 32 analog values are shown below.
PATH: SETTINGS Ö PRODUCT... ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ GGIO4 ANALOG CONFIGURATION
Ö GGIO4 ANALOG 1(32) MEASURED VALUE

5 „ GGIO4 ANALOG 1
„ MEASURED VALUE
ANALOG IN
Off
1 VALUE: Range: any FlexAnalog value

ANALOG IN 1 DB: Range: 0.000 to 100.000 in steps of 0.001


MESSAGE
0.000

ANALOG IN 1 MIN: Range: –1000000000.000 to 1000000000.000 in steps


MESSAGE of 0.001
0.000

ANALOG IN 1 MAX: Range: –1000000000.000 to 1000000000.000 in steps


MESSAGE of 0.001
0.000

These settings are configured as follows.


• ANALOG IN 1 VALUE: This setting selects the FlexAnalog value to drive the instantaneous value of each GGIO4 ana-
log status value (GGIO4.MX.AnIn1.instMag.f).
• ANALOG IN 1 DB: This setting specifies the deadband for each analog value. Refer to IEC 61850-7-1 and 61850-7-3
for details. The deadband is used to determine when to update the deadbanded magnitude from the instantaneous
magnitude. The deadband is a percentage of the difference between the maximum and minimum values.
• ANALOG IN 1 MIN: This setting specifies the minimum value for each analog value. Refer to IEC 61850-7-1 and
61850-7-3 for details. This minimum value is used to determine the deadband. The deadband is used in the determina-
tion of the deadbanded magnitude from the instantaneous magnitude.
• ANALOG IN 1 MAX: This setting defines the maximum value for each analog value. Refer to IEC 61850-7-1 and
61850-7-3 for details. This maximum value is used to determine the deadband. The deadband is used in the determi-
nation of the deadbanded magnitude from the instantaneous magnitude.
Note that the ANALOG IN 1 MIN and ANALOG IN 1 MAX settings are stored as IEEE 754 / IEC 60559 floating point
numbers. Because of the large range of these settings, not all values can be stored. Some values may be rounded
NOTE to the closest possible floating point number.

5-32 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

The GGIO5 integer configuration points are shown below:


PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ GGIO5 ANALOG CONFIGURATION

„ GGIO5 UINTEGER GGIO5 UINT In 1: Range: Off, any FlexInteger parameter


„ CONFIGURATION Off

GGIO5 UINT In 2: Range: Off, any FlexInteger parameter


MESSAGE
Off

GGIO5 UINT In 3: Range: Off, any FlexInteger parameter


MESSAGE
Off

GGIO5 UINT 1n 16: Range: Off, any FlexInteger parameter


MESSAGE
Off

The GGIO5 logical node allows IEC 61850 client access to integer data values. This allows access to as many as 16
unsigned integer value points, associated timestamps, and quality flags. The method of configuration is similar to that of
GGIO1 (binary status values). The settings allow the selection of FlexInteger™ values for each GGIO5 integer value point.
It is intended that clients use GGIO5 to access generic integer values from the G60. Additional settings are provided to
allow the selection of the number of integer values available in GGIO5 (1 to 16), and to assign FlexInteger™ values to the
GGIO5 integer inputs. The following setting is available for all GGIO5 configuration points.
• GGIO5 UINT IN 1 VALUE: This setting selects the FlexInteger™ value to drive each GGIO5 integer status value
(GGIO5.ST.UIntIn1). This setting is stored as an 32-bit unsigned integer value.
The report control configuration settings are shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ REPORT CONTROL CONFIGURATION
5
Ö CONFIGURABLE REPORT 1 Ö REPORT 1 DATASET ITEMS
„ REPORT 1 ITEM 1: Range: all valid MMS data item references
„ DATASET ITEMS

ITEM 2: Range: as shown above


MESSAGE

ITEM 3: Range: as shown above


MESSAGE

ITEM 64: Range: as shown above


MESSAGE

To create the dataset for logical node LN, program the ITEM 1 to ITEM 64 settings to a value from the list of IEC 61850 data
attributes supported by the G60. Changes to the dataset will only take effect when the G60 is restarted. It is recommended
to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1,
GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.

GE Multilin G60 Generator Protection System 5-33


5.2 PRODUCT SETUP 5 SETTINGS

The breaker configuration settings are shown below. Changes to these values will not take effect until the UR is restarted:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ XCBR CONFIGURATION

„ XCBR XCBR1 ST.LOC OPERAND Range: FlexLogic™ operand


„ CONFIGURATION Off

XCBR2 ST.LOC OPERAND Range: FlexLogic™ operand


MESSAGE
Off

XCBR3 ST.LOC OPERAND Range: FlexLogic™ operand


MESSAGE
Off

XCBR6 ST.LOC OPERAND Range: FlexLogic™ operand


MESSAGE
Off

CLEAR XCBR1 OpCnt: Range: No, Yes


MESSAGE
No

CLEAR XCBR2 OpCnt: Range: No, Yes


MESSAGE
No

CLEAR XCBR3 OpCnt: Range: No, Yes


MESSAGE
No

CLEAR XCBR6 OpCnt: Range: No, Yes


5 MESSAGE
No

The CLEAR XCBR1 OpCnt setting represents the breaker operating counter. As breakers operate by opening and closing, the
XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result
in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XCBR1.

5-34 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is
restarted:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL ÖØ XSWI CONFIGURATION

„ XSWI XSWI1 ST.LOC OPERAND Range: FlexLogic™ operand


„ CONFIGURATION Off

XSWI2 ST.LOC OPERAND Range: FlexLogic™ operand


MESSAGE
Off

XSWI3 ST.LOC OPERAND Range: FlexLogic™ operand


MESSAGE
Off

XSWI24 ST.LOC OPERAND Range: FlexLogic™ operand


MESSAGE
Off

CLEAR XSWI1 OpCnt: Range: No, Yes


MESSAGE
No

CLEAR XSWI2 OpCnt: Range: No, Yes


MESSAGE
No

CLEAR XSWI3 OpCnt: Range: No, Yes


MESSAGE
No

MESSAGE
CLEAR XSWI24 OpCnt: Range: No, Yes 5
No

The CLEAR XSWI1 OpCnt setting represents the disconnect switch operating counter. As disconnect switches operate by
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to “0” for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they will not usually be forwarded by net-
work routers. However, GOOSE messages may be fowarded by routers if the router has been configured for VLAN
NOTE functionality.

h) WEB SERVER HTTP PROTOCOL


PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ WEB SERVER HTTP PROTOCOL

„ WEB SERVER HTTP TCP PORT Range: 1 to 65535 in steps of 1


„ HTTP PROTOCOL NUMBER: 80

The G60 contains an embedded web server and is capable of transferring web pages to a web browser such as Microsoft
Internet Explorer or Mozilla Firefox. This feature is available only if the G60 has the ethernet option installed. The web
pages are organized as a series of menus that can be accessed starting at the G60 “Main Menu”. Web pages are available
showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, etc. The web pages can be
accessed by connecting the UR and a computer to an ethernet network. The main menu will be displayed in the web
browser on the computer simply by entering the IP address of the G60 into the “Address” box on the web browser.

GE Multilin G60 Generator Protection System 5-35


5.2 PRODUCT SETUP 5 SETTINGS

i) TFTP PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ TFTP PROTOCOL

„ TFTP PROTOCOL TFTP MAIN UDP PORT Range: 1 to 65535 in steps of 1


„ NUMBER: 69
TFTP DATA UDP PORT 1 Range: 0 to 65535 in steps of 1
MESSAGE
NUMBER: 0
TFTP DATA UDP PORT 2 Range: 0 to 65535 in steps of 1
MESSAGE
NUMBER: 0

The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the G60 over a network. The G60 operates as a
TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file
obtained from the G60 contains a list and description of all available files (event records, oscillography, etc.).

j) IEC 60870-5-104 PROTOCOL


PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 60870-5-104 PROTOCOL

„ IEC 60870-5-104 IEC 60870-5-104 Range: Enabled, Disabled


„ PROTOCOL FUNCTION: Disabled
IEC TCP PORT Range: 1 to 65535 in steps of 1
MESSAGE
NUMBER: 2404
„ IEC NETWORK
MESSAGE
„ CLIENT ADDRESSES
5 MESSAGE
IEC COMMON ADDRESS Range: 0 to 65535 in steps of 1
OF ASDU: 0
IEC CYCLIC DATA Range: 1 to 65535 s in steps of 1
MESSAGE
PERIOD: 60 s
IEC CURRENT DEFAULT Range: 0 to 65535 in steps of 1
MESSAGE
THRESHOLD: 30000
IEC VOLTAGE DEFAULT Range: 0 to 65535 in steps of 1
MESSAGE
THRESHOLD: 30000
IEC POWER DEFAULT Range: 0 to 65535 in steps of 1
MESSAGE
THRESHOLD: 30000
IEC ENERGY DEFAULT Range: 0 to 65535 in steps of 1
MESSAGE
THRESHOLD: 30000
IEC OTHER DEFAULT Range: 0 to 65535 in steps of 1
MESSAGE
THRESHOLD: 30000

The G60 supports the IEC 60870-5-104 protocol. The G60 can be used as an IEC 60870-5-104 slave device connected to
a maximum of two masters (usually either an RTU or a SCADA master station). Since the G60 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the G60 at one time.
The IEC ------- DEFAULT THRESHOLD settings are used to determine when to trigger spontaneous responses containing
M_ME_NC_1 analog data. These settings group the G60 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the G60 when any current values change by 15 A, the IEC CURRENT DEFAULT THRESHOLD set-
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the G60, the default thresholds will be in effect.
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC 60870-5-104 FUNCTION
setting is set to “Enabled”, the DNP protocol will not be operational. When this setting is changed it will not
NOTE
become active until power to the relay has been cycled (off-to-on).

5-36 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

k) SNTP PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ SNTP PROTOCOL

„ SNTP PROTOCOL SNTP FUNCTION: Range: Enabled, Disabled


„ Disabled
SNTP SERVER IP ADDR: Range: Standard IP address format
MESSAGE
0.0.0.0
SNTP UDP PORT Range: 0 to 65535 in steps of 1
MESSAGE
NUMBER: 123

The G60 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the G60 can obtain clock time
over an Ethernet network. The G60 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a ded-
icated product using a GPS receiver to provide an accurate time. Both unicast and broadcast SNTP are supported.
If SNTP functionality is enabled at the same time as IRIG-B, the IRIG-B signal provides the time value to the G60 clock for
as long as a valid signal is present. If the IRIG-B signal is removed, the time obtained from the SNTP server is used. If
either SNTP or IRIG-B is enabled, the G60 clock value cannot be changed using the front panel keypad.
To use SNTP in unicast mode, SNTP SERVER IP ADDR must be set to the SNTP/NTP server IP address. Once this address is
set and SNTP FUNCTION is “Enabled”, the G60 attempts to obtain time values from the SNTP/NTP server. Since many time
values are obtained and averaged, it generally takes three to four minutes until the G60 clock is closely synchronized with
the SNTP/NTP server. It may take up to two minutes for the G60 to signal an SNTP self-test error if the server is offline.
To use SNTP in broadcast mode, set the SNTP SERVER IP ADDR setting to “0.0.0.0” and SNTP FUNCTION to “Enabled”. The
G60 then listens to SNTP messages sent to the “all ones” broadcast address for the subnet. The G60 waits up to eighteen
minutes (>1024 seconds) without receiving an SNTP broadcast message before signaling an SNTP self-test error.
The UR-series relays do not support the multicast or anycast SNTP functionality. 5
l) EGD PROTOCOL
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ EGD PROTOCOL

„ EGD PROTOCOL „ FAST PROD EXCH 1


„ „ CONFIGURATION
„ SLOW PROD EXCH 1
MESSAGE
„ CONFIGURATION
„ SLOW PROD EXCH 2
MESSAGE
„ CONFIGURATION

The G60 Generator Protection System is provided with optional Ethernet Global Data (EGD) communica-
tions capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering
section of chapter 2 for additional details. The Ethernet Global Data (EGD) protocol feature is not available
if CPU Type E is ordered.

The relay supports one fast Ethernet Global Data (EGD) exchange and two slow EGD exchanges. There are 20 data items
in the fast-produced EGD exchange and 50 data items in each slow-produced exchange.
Ethernet Global Data (EGD) is a suite of protocols used for the real-time transfer of data for display and control purposes.
The relay can be configured to ‘produce’ EGD data exchanges, and other devices can be configured to ‘consume’ EGD
data exchanges. The number of produced exchanges (up to three), the data items in each exchange (up to 50), and the
exchange production rate can be configured.
EGD cannot be used to transfer data between UR-series relays. The relay supports EGD production only. An EGD
exchange will not be transmitted unless the destination address is non-zero, and at least the first data item address is set to
a valid Modbus register address. Note that the default setting value of “0” is considered invalid.

GE Multilin G60 Generator Protection System 5-37


5.2 PRODUCT SETUP 5 SETTINGS

The settings menu for the fast EGD exchange is shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ EGD PROTOCOL Ö FAST PROD EXCH 1 CONFIGURATION

„ FAST PROD EXCH 1 EXCH 1 FUNCTION: Range: Disable, Enable


„ CONFIGURATION Disable
EXCH 1 DESTINATION: Range: standard IP address
MESSAGE
0.0.0.0
EXCH 1 DATA RATE: Range: 50 to 1000 ms in steps of 1
MESSAGE
1000 ms
EXCH 1 DATA ITEM 1: Range: 0 to 65535 in steps of 1
MESSAGE (Modbus register address range)
0
EXCH 1 DATA ITEM 2: Range: 0 to 65535 in steps of 1
MESSAGE (Modbus register address range)
0
EXCH 1 DATA ITEM 3: Range: 0 to 65535 in steps of 1
MESSAGE (Modbus register address range)
0

EXCH 1 DATA ITEM 20: Range: 0 to 65535 in steps of 1


MESSAGE (Modbus register address range)
0

Fast exchanges (50 to 1000 ms) are generally used in control schemes. The G60 has one fast exchange (exchange 1) and
two slow exchanges (exchange 2 and 3).

5 The settings menu for the slow EGD exchanges is shown below:
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ EGD PROTOCOL Ö SLOW PROD EXCH 1(2) CONFIGURATION

„ SLOW PROD EXCH 1 EXCH 1 FUNCTION: Range: Disable, Enable


„ CONFIGURATION Disable
EXCH 1 DESTINATION: Range: standard IP address
MESSAGE
0.0.0.0
EXCH 1 DATA RATE: Range: 500 to 1000 ms in steps of 1
MESSAGE
1000 ms
EXCH 1 DATA ITEM 1: Range: 0 to 65535 in steps of 1
MESSAGE (Modbus register address range in decimal)
0
EXCH 1 DATA ITEM 2: Range: 0 to 65535 in steps of 1
MESSAGE (Modbus register address range in decimal)
0
EXCH 1 DATA ITEM 3: Range: 0 to 65535 in steps of 1
MESSAGE (Modbus register address range in decimal)
0

EXCH 1 DATA ITEM 50: Range: 0 to 65535 in steps of 1


MESSAGE (Modbus register address range in decimal)
0

Slow EGD exchanges (500 to 1000 ms) are generally used for the transfer and display of data items. The settings for the
fast and slow exchanges are described below:
• EXCH 1 DESTINATION: This setting specifies the destination IP address of the produced EGD exchange. This is usu-
ally unicast or broadcast.
• EXCH 1 DATA RATE: This setting specifies the rate at which this EGD exchange is transmitted. If the setting is 50 ms,
the exchange data will be updated and sent once every 50 ms. If the setting is 1000 ms, the exchange data will be
updated and sent once per second. EGD exchange 1 has a setting range of 50 to 1000 ms. Exchanges 2 and 3 have a
setting range of 500 to 1000 ms.

5-38 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

• EXCH 1 DATA ITEM 1 to 20/50: These settings specify the data items that are part of this EGD exchange. Almost any
data from the G60 memory map can be configured to be included in an EGD exchange. The settings are the starting
Modbus register address for the data item in decimal format. Refer to Appendix B for the complete Modbus memory
map. Note that the Modbus memory map displays shows addresses in hexadecimal format. as such, it will be neces-
sary to convert these values to decimal format before entering them as values for these setpoints.
To select a data item to be part of an exchange, it is only necessary to choose the starting Modbus address of the item.
That is, for items occupying more than one Modbus register (for example, 32 bit integers and floating point values),
only the first Modbus address is required. The EGD exchange configured with these settings contains the data items
up to the first setting that contains a Modbus address with no data, or 0. That is, if the first three settings contain valid
Modbus addresses and the fourth is 0, the produced EGD exchange will contain three data items.

m) ETHERNET SWITCH
PATH: SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ ETHERNET SWITCH

„ ETHERNET SWITCH SWITCH IP ADDRESS: Range: standard IP address format


„ 127.0.0.1
SWITCH MODBUS TCP Range: 1 to 65535 in steps of 1
MESSAGE
PORT NUMBER: 502
PORT 1 EVENTS: Range: Enabled, Disabled
MESSAGE
Disabled
PORT 2 EVENTS: Range: Enabled, Disabled
MESSAGE
Disabled

PORT 6 EVENTS: Range: Enabled, Disabled 5


MESSAGE
Disabled

These settings appear only if the G60 is ordered with an Ethernet switch module (type 2S or 2T).
The IP address and Modbus TCP port number for the Ethernet switch module are specified in this menu. These settings
are used in advanced network configurations. Please consult the network administrator before making changes to these
settings. The client software (EnerVista UR Setup, for example) is the preferred interface to configure these settings.
The PORT 1 EVENTS through PORT 6 EVENTS settings allow Ethernet switch module events to be logged in the event
recorder.

5.2.5 MODBUS USER MAP

PATH: SETTINGS Ö PRODUCT SETUP ÖØ MODBUS USER MAP

„ MODBUS USER MAP ADDRESS 1: 0 Range: 0 to 65535 in steps of 1


„ VALUE: 0
ADDRESS 2: 0 Range: 0 to 65535 in steps of 1
MESSAGE
VALUE: 0
ADDRESS 3: 0 Range: 0 to 65535 in steps of 1
MESSAGE
VALUE: 0

ADDRESS 256: 0 Range: 0 to 65535 in steps of 1


MESSAGE
VALUE: 0

The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the ADDRESS line (this value must be converted from hex to decimal format). The corresponding value is dis-
played in the VALUE line. A value of “0” in subsequent register ADDRESS lines automatically returns values for the previous
ADDRESS lines incremented by “1”. An address value of “0” in the initial register means “none” and values of “0” will be dis-
played for all registers. Different ADDRESS values can be entered as required in any of the register positions.

GE Multilin G60 Generator Protection System 5-39


5.2 PRODUCT SETUP 5 SETTINGS

5.2.6 REAL TIME CLOCK

PATH: SETTINGS Ö PRODUCT SETUP ÖØ REAL TIME CLOCK

„ REAL TIME IRIG-B SIGNAL TYPE: Range: None, DC Shift, Amplitude Modulated
„ CLOCK None
REAL TIME CLOCK Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
LOCAL TIME OFFSET Range: –24.0 to 24.0 hrs in steps of 0.5
MESSAGE
FROM UTC: 0.0 hrs
DAYLIGHT SAVINGS Range: Disabled, Enabled
MESSAGE
TIME: Disabled
DST START MONTH: Range: January to December (all months)
MESSAGE
April
DST START DAY: Range: Sunday to Saturday (all days of the week)
MESSAGE
Sunday
DST START DAY Range: First, Second, Third, Fourth, Last
MESSAGE
INSTANCE: First
DST START HOUR: Range: 0:00 to 23:00
MESSAGE
2:00
DST STOP MONTH: Range: January to December (all months)

5 MESSAGE
April
DST STOP DAY: Range: Sunday to Saturday (all days of the week)
MESSAGE
Sunday
DST STOP DAY Range: First, Second, Third, Fourth, Last
MESSAGE
INSTANCE: First
DST STOP HOUR: Range: 0:00 to 23:00
MESSAGE
2:00

The date and time can be synchronized a known time base and to other relays using an IRIG-B signal. It has the same
accuracy as an electronic watch, approximately ±1 minute per month. If an IRIG-B signal is connected to the relay, only the
current year needs to be entered. See the COMMANDS ÖØ SET DATE AND TIME menu to manually set the relay clock.
The REAL TIME CLOCK EVENTS setting allows changes to the date and/or time to be captured in the event record.
The LOCAL TIME OFFSET FROM UTC setting is used to specify the local time zone offset from Universal Coordinated Time
(Greenwich Mean Time) in hours. This setting has two uses. When the G60 is time synchronized with IRIG-B, or has no
permanent time synchronization, the offset is used to calculate UTC time for IEC 61850 features. When the G60 is time
synchronized with SNTP, the offset is used to determine the local time for the G60 clock, since SNTP provides UTC time.
The daylight savings time (DST) settings can be used to allow the G60 clock can follow the DST rules of the local time
zone. Note that when IRIG-B time synchronization is active, the DST settings are ignored. The DST settings are used when
the G60 is synchronized with SNTP, or when neither SNTP nor IRIG-B is used.
Only timestamps in the event recorder and communications protocols are affected by the daylight savings time set-
tings. The reported real-time clock value does not change.
NOTE

5-40 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

5.2.7 USER-PROGRAMMABLE FAULT REPORT

PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE FAULT REPORT Ö USER-PROGRAMMABLE FAULT REPORT 1(2)

„ USER-PROGRAMMABLE FAULT REPORT 1 Range: Disabled, Enabled


„ FAULT REPORT 1 FUNCTION: Disabled
PRE-FAULT 1 TRIGGER: Range: FlexLogic™ operand
MESSAGE
Off
FAULT 1 TRIGGER: Range: FlexLogic™ operand
MESSAGE
Off
FAULT REPORT 1 #1: Range: Off, any actual value analog parameter
MESSAGE
Off
FAULT REPORT 1 #2: Range: Off, any actual value analog parameter
MESSAGE
Off
FAULT REPORT 1 #3: Range: Off, any actual value analog parameter
MESSAGE
Off

FAULT REPORT 1 #32: Range: Off, any actual value analog parameter
MESSAGE
Off

When enabled, this function monitors the pre-fault trigger. The pre-fault data are stored in the memory for prospective cre-
ation of the fault report on the rising edge of the pre-fault trigger. The element waits for the fault trigger as long as the pre-
fault trigger is asserted, but not shorter than 1 second. When the fault trigger occurs, the fault data is stored and the com- 5
plete report is created. If the fault trigger does not occur within 1 second after the pre-fault trigger drops out, the element
resets and no record is created.
The user programmable record contains the following information: the user-programmed relay name, detailed firmware
revision (5.9x, for example) and relay model (G60), the date and time of trigger, the name of pre-fault trigger (a specific
FlexLogic™ operand), the name of fault trigger (a specific FlexLogic™ operand), the active setting group at pre-fault trig-
ger, the active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault
trigger), and fault values of all programmed analog channels (at the fault trigger).
Each fault report is stored as a file to a maximum capacity of ten files. An eleventh trigger overwrites the oldest file. The
EnerVista UR Setup software is required to view all captured data. A FAULT RPT TRIG event is automatically created when
the report is triggered.
The relay includes two user-programmable fault reports to enable capture of two types of trips (for example, trip from ther-
mal protection with the report configured to include temperatures, and short-circuit trip with the report configured to include
voltages and currents). Both reports feed the same report file queue.
The last record is available as individual data items via communications protocols.
• PRE-FAULT 1 TRIGGER: Specifies the FlexLogic™ operand to capture the pre-fault data. The rising edge of this
operand stores one cycle-old data for subsequent reporting. The element waits for the fault trigger to actually create a
record as long as the operand selected as PRE-FAULT 1 TRIGGER is “On”. If the operand remains “Off” for 1 second, the
element resets and no record is created.
• FAULT 1 TRIGGER: Specifies the FlexLogic™ operand to capture the fault data. The rising edge of this operand
stores the data as fault data and results in a new report. The trigger (not the pre-fault trigger) controls the date and time
of the report.
• FAULT REPORT 1 #1 to FAULT REPORT 1 #32: These settings specify an actual value such as voltage or current
magnitude, true RMS, phase angle, frequency, temperature, etc., to be stored should the report be created. Up to 32
channels can be configured. Two reports are configurable to cope with variety of trip conditions and items of interest.

GE Multilin G60 Generator Protection System 5-41


5.2 PRODUCT SETUP 5 SETTINGS

5.2.8 OSCILLOGRAPHY

a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ OSCILLOGRAPHY

„ OSCILLOGRAPHY NUMBER OF RECORDS: Range: 1 to 64 in steps of 1


„ 5
TRIGGER MODE: Range: Automatic Overwrite, Protected
MESSAGE
Automatic Overwrite
TRIGGER POSITION: Range: 0 to 100% in steps of 1
MESSAGE
50%
TRIGGER SOURCE: Range: FlexLogic™ operand
MESSAGE
Off
AC INPUT WAVEFORMS: Range: Off; 8, 16, 32, 64 samples/cycle
MESSAGE
16 samples/cycle
„ DIGITAL CHANNELS
MESSAGE
„
„ ANALOG CHANNELS
MESSAGE
„

Oscillography records contain waveforms captured at the sampling rate as well as other relay data at the point of trigger.
Oscillography records are triggered by a programmable FlexLogic™ operand. Multiple oscillography records may be cap-
5 tured simultaneously.
The NUMBER OF RECORDS is selectable, but the number of cycles captured in a single record varies considerably based on
other factors such as sample rate and the number of operational modules. There is a fixed amount of data storage for oscil-
lography; the more data captured, the less the number of cycles captured per record. See the ACTUAL VALUES ÖØ
RECORDS ÖØ OSCILLOGRAPHY menu to view the number of cycles captured per record. The following table provides sam-
ple configurations with corresponding cycles/record.

Table 5–2: OSCILLOGRAPHY CYCLES/RECORD EXAMPLE


RECORDS CT/VTS SAMPLE DIGITALS ANALOGS CYCLES/
RATE RECORD
1 1 8 0 0 1872.0
1 1 16 16 0 1685.0
8 1 16 16 0 276.0
8 1 16 16 4 219.5
8 2 16 16 4 93.5
8 2 16 63 16 93.5
8 2 32 63 16 57.6
8 2 64 63 16 32.3
32 2 64 63 16 9.5

A new record may automatically overwrite an older record if TRIGGER MODE is set to “Automatic Overwrite”.
Set the TRIGGER POSITION to a percentage of the total buffer size (for example, 10%, 50%, 75%, etc.). A trigger position of
25% consists of 25% pre- and 75% post-trigger data. The TRIGGER SOURCE is always captured in oscillography and may be
any FlexLogic™ parameter (element state, contact input, virtual output, etc.). The relay sampling rate is 64 samples per
cycle.
The AC INPUT WAVEFORMS setting determines the sampling rate at which AC input signals (that is, current and voltage) are
stored. Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling
rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device.

5-42 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

When changes are made to the oscillography settings, all existing oscillography records will be CLEARED.

WARNING

b) DIGITAL CHANNELS
PATH: SETTINGS Ö PRODUCT SETUP ÖØ OSCILLOGRAPHY ÖØ DIGITAL CHANNELS

„ DIGITAL CHANNELS DIGITAL CHANNEL 1: Range: FlexLogic™ operand


„ Off
DIGITAL CHANNEL 2: Range: FlexLogic™ operand
MESSAGE
Off
DIGITAL CHANNEL 3: Range: FlexLogic™ operand
MESSAGE
Off

DIGITAL CHANNEL 63: Range: FlexLogic™ operand


MESSAGE
Off

A DIGITAL 1(63) CHANNEL setting selects the FlexLogic™ operand state recorded in an oscillography trace. The length of
each oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored.
Upon startup, the relay will automatically prepare the parameter list.

c) ANALOG CHANNELS
PATH: SETTINGS Ö PRODUCT SETUP ÖØ OSCILLOGRAPHY ÖØ ANALOG CHANNELS

„ ANALOG CHANNELS Range: Off, any FlexAnalog parameter


„
ANALOG CHANNEL
Off
1:
See Appendix A for complete list. 5
ANALOG CHANNEL 2: Range: Off, any FlexAnalog parameter
MESSAGE See Appendix A for complete list.
Off
ANALOG CHANNEL 3: Range: Off, any FlexAnalog parameter
MESSAGE See Appendix A for complete list.
Off

ANALOG CHANNEL 16: Range: Off, any FlexAnalog parameter


MESSAGE See Appendix A for complete list.
Off

These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace
depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. The parameters available
in a given relay are dependent on:
• The type of relay,
• The type and number of CT/VT hardware modules installed, and
• The type and number of analog input hardware modules installed.
Upon startup, the relay will automatically prepare the parameter list. A list of all possible analog metering actual value
parameters is presented in Appendix A: FlexAnalog parameters. The parameter index number shown in any of the tables is
used to expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list
of parameters via the relay keypad and display - entering this number via the relay keypad will cause the corresponding
parameter to be displayed.
All eight CT/VT module channels are stored in the oscillography file. The CT/VT module channels are named as follows:
<slot_letter><terminal_number>—<I or V><phase A, B, or C, or 4th input>
The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB desig-
nates the IB signal on terminal 2 of the CT/VT module in slot F.
If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will
appear.

GE Multilin G60 Generator Protection System 5-43


5.2 PRODUCT SETUP 5 SETTINGS

The source harmonic indices appear as oscillography analog channels numbered from 0 to 23. These correspond
directly to the to the 2nd to 25th harmonics in the relay as follows:
NOTE
Analog channel 0 ↔ 2nd harmonic
Analog channel 1 ↔ 3rd harmonic
...
Analog channel 23 ↔ 25th harmonic

5.2.9 DATA LOGGER

PATH: SETTINGS ÖØ PRODUCT SETUP ÖØ DATA LOGGER

„ DATA LOGGER DATA LOGGER MODE: Range: Continuous, Trigger


„ Continuous
DATA LOGGER TRIGGER: Range: FlexLogic™ operand
MESSAGE
Off
DATA LOGGER RATE: Range: 15 to 3600000 ms in steps of 1
MESSAGE
60000 ms
DATA LOGGER CHNL 1: Range: Off, any FlexAnalog parameter. See Appendix A:
MESSAGE FlexAnalog Parameters for complete list.
Off
DATA LOGGER CHNL 2: Range: Off, any FlexAnalog parameter. See Appendix A:
MESSAGE FlexAnalog Parameters for complete list.
Off
DATA LOGGER CHNL 3: Range: Off, any FlexAnalog parameter. See Appendix A:
MESSAGE FlexAnalog Parameters for complete list.
5 Off

DATA LOGGER CHNL 16: Range: Off, any FlexAnalog parameter. See Appendix A:
MESSAGE FlexAnalog Parameters for complete list.
Off
DATA LOGGER CONFIG: Range: Not applicable - shows computed data only
MESSAGE
0 CHNL x 0.0 DAYS

The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data may
be downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis.
All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. Exam-
ple storage capacities for a system frequency of 60 Hz are shown in the following table.

5-44 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

Table 5–3: DATA LOGGER STORAGE CAPACITY EXAMPLE


SAMPLING RATE CHANNELS DAYS STORAGE CAPACITY
15 ms 1 0.1 954 s
8 0.1 120 s
9 0.1 107 s
16 0.1 60 s
1000 ms 1 0.7 65457 s
8 0.1 8182 s
9 0.1 7273 s
16 0.1 4091 s
60000 ms 1 45.4 3927420 s
8 5.6 490920 s
9 5 436380 s
16 2.8 254460 s
3600000 ms 1 2727.5 235645200 s
8 340.9 29455200 s
9 303 26182800 s

Changing any setting affecting data logger operation will clear any data that is currently in the log.

NOTE

• DATA LOGGER MODE: This setting configures the mode in which the data logger will operate. When set to “Continu-
ous”, the data logger will actively record any configured channels at the rate as defined by the DATA LOGGER RATE. The
5
data logger will be idle in this mode if no channels are configured. When set to “Trigger”, the data logger will begin to
record any configured channels at the instance of the rising edge of the DATA LOGGER TRIGGER source FlexLogic™
operand. The data logger will ignore all subsequent triggers and will continue to record data until the active record is
full. Once the data logger is full a CLEAR DATA LOGGER command is required to clear the data logger record before a
new record can be started. Performing the CLEAR DATA LOGGER command will also stop the current record and reset
the data logger to be ready for the next trigger.
• DATA LOGGER TRIGGER: This setting selects the signal used to trigger the start of a new data logger record. Any
FlexLogic™ operand can be used as the trigger source. The DATA LOGGER TRIGGER setting only applies when the
mode is set to “Trigger”.
• DATA LOGGER RATE: This setting selects the time interval at which the actual value data will be recorded.
• DATA LOGGER CHNL 1(16): This setting selects the metering actual value that is to be recorded in Channel 1(16) of
the data log. The parameters available in a given relay are dependent on: the type of relay, the type and number of CT/
VT hardware modules installed, and the type and number of Analog Input hardware modules installed. Upon startup,
the relay will automatically prepare the parameter list. A list of all possible analog metering actual value parameters is
shown in Appendix A: FlexAnalog Parameters. The parameter index number shown in any of the tables is used to
expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list of
parameters via the relay keypad/display – entering this number via the relay keypad will cause the corresponding
parameter to be displayed.
• DATA LOGGER CONFIG: This display presents the total amount of time the Data Logger can record the channels not
selected to “Off” without over-writing old data.

GE Multilin G60 Generator Protection System 5-45


5.2 PRODUCT SETUP 5 SETTINGS

5.2.10 USER-PROGRAMMABLE LEDS

a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS

„ USER-PROGRAMMABLE „ LED TEST


See below
„ LEDS „
„ TRIP & ALARM
MESSAGE See page 5–48.
„ LEDS
„ USER-PROGRAMMABLE
MESSAGE See page 5–48.
„ LED1
„ USER-PROGRAMMABLE
MESSAGE
„ LED2

„ USER-PROGRAMMABLE
MESSAGE
„ LED48

b) LED TEST
PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS Ö LED TEST

„ LED TEST LED TEST FUNCTION: Range: Disabled, Enabled.


„ Disabled
5 MESSAGE
LED TEST CONTROL: Range: FlexLogic™ operand
Off

When enabled, the LED test can be initiated from any digital input or user-programmable condition such as user-program-
mable pushbutton. The control operand is configured under the LED TEST CONTROL setting. The test covers all LEDs,
including the LEDs of the optional user-programmable pushbuttons.
The test consists of three stages.
1. All 62 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is “burned”. This stage lasts as
long as the control input is on, up to a maximum of 1 minute. After 1 minute, the test will end.
2. All the LEDs are turned off, and then one LED at a time turns on for 1 second, then back off. The test routine starts at
the top left panel, moving from the top to bottom of each LED column. This test checks for hardware failures that lead
to more than one LED being turned on from a single logic point. This stage can be interrupted at any time.
3. All the LEDs are turned on. One LED at a time turns off for 1 second, then back on. The test routine starts at the top left
panel moving from top to bottom of each column of the LEDs. This test checks for hardware failures that lead to more
than one LED being turned off from a single logic point. This stage can be interrupted at any time.
When testing is in progress, the LEDs are controlled by the test sequence, rather than the protection, control, and monitor-
ing features. However, the LED control mechanism accepts all the changes to LED states generated by the relay and
stores the actual LED states (on or off) in memory. When the test completes, the LEDs reflect the actual state resulting from
relay response during testing. The reset pushbutton will not clear any targets when the LED Test is in progress.
A dedicated FlexLogic™ operand, LED TEST IN PROGRESS, is set for the duration of the test. When the test sequence is ini-
tiated, the LED TEST INITIATED event is stored in the event recorder.
The entire test procedure is user-controlled. In particular, stage 1 can last as long as necessary, and stages 2 and 3 can be
interrupted. The test responds to the position and rising edges of the control input defined by the LED TEST CONTROL set-
ting. The control pulses must last at least 250 ms to take effect. The following diagram explains how the test is executed.

5-46 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

READY TO TEST

Reset the
LED TEST IN PROGRESS
rising edge of the
operand
control input

Start the software image of Restore the LED states


the LEDs from the software image

Set the
LED TEST IN PROGRESS
operand

control input is on

STAGE 1 time-out
(all LEDs on) (1 minute)

dropping edge of the


control input

rising edge of the


Wait 1 second
control input

STAGE 2 rising edge of the


(one LED on at a time) control input

rising edge of the


Wait 1 second
control input
5
rising edge
STAGE 3
of the control
(one LED off at a time) input

842011A1.CDR

Figure 5–3: LED TEST SEQUENCE


APPLICATION EXAMPLE 1:
Assume one needs to check if any of the LEDs is “burned” through user-programmable pushbutton 1. The following set-
tings should be applied. Configure user-programmable pushbutton 1 by making the following entries in the SETTINGS Ö
PRODUCT SETUP ÖØ USER-PROGRAMMABLE PUSHBUTTONS Ö USER PUSHBUTTON 1 menu:

PUSHBUTTON 1 FUNCTION: “Self-reset”


PUSHBTN 1 DROP-OUT TIME: “0.10 s”

Configure the LED test to recognize user-programmable pushbutton 1 by making the following entries in the SETTINGS Ö
PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS Ö LED TEST menu:

LED TEST FUNCTION: “Enabled”


LED TEST CONTROL: “PUSHBUTTON 1 ON”

The test will be initiated when the user-programmable pushbutton 1 is pressed. The pushbutton should remain pressed for
as long as the LEDs are being visually inspected. When finished, the pushbutton should be released. The relay will then
automatically start stage 2. At this point forward, test may be aborted by pressing the pushbutton.

APPLICATION EXAMPLE 2:
Assume one needs to check if any LEDs are “burned” as well as exercise one LED at a time to check for other failures. This
is to be performed via user-programmable pushbutton 1.
After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. Next,
release the pushbutton to automatically start stage 2. Once stage 2 has started, the pushbutton can be released. When
stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton.

GE Multilin G60 Generator Protection System 5-47


5.2 PRODUCT SETUP 5 SETTINGS

c) TRIP AND ALARM LEDS


PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS ÖØ TRIP & ALARM LEDS

„ TRIP & ALARM LEDS TRIP LED INPUT: Range: FlexLogic™ operand
„ Off
ALARM LED INPUT: Range: FlexLogic™ operand
MESSAGE
Off

The trip and alarm LEDs are in the first LED column (enhanced faceplate) and on LED panel 1 (standard faceplate). Each
indicator can be programmed to become illuminated when the selected FlexLogic™ operand is in the logic 1 state.

d) USER-PROGRAMMABLE LED 1(48)


PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS ÖØ USER-PROGRAMMABLE LED 1(48)

„ USER-PROGRAMMABLE LED 1 OPERAND: Range: FlexLogic™ operand


„ LED 1 Off
LED 1 TYPE: Range: Self-Reset, Latched
MESSAGE
Self-Reset

There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-
nate when the selected FlexLogic™ operand is in the logic 1 state.
For the standard faceplate, the LEDs are located as follows.
• LED Panel 2: user-programmable LEDs 1 through 24

5 • LED Panel 3: user programmable LEDs 25 through 48


For the enhanced faceplate, the LEDs are located as follows.
• LED column 2: user-programmable LEDs 1 through 12
• LED column 3: user-programmable LEDs 13 through 24
• LED column 4: user-programmable LEDs 25 through 36
• LED column 5: user-programmable LEDs 37 through 48
Refer to the LED indicators section in chapter 4 for additional information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic™ operands that control the LEDs. If the LED 1 TYPE setting is
“Self-Reset” (the default setting), the LED illumination will track the state of the selected LED operand. If the LED 1 TYPE set-
ting is “Latched”, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a com-
munications channel, or from any programmed operand, even if the LED operand state de-asserts.

Table 5–4: RECOMMENDED SETTINGS FOR USER-PROGRAMMABLE LEDS


SETTING PARAMETER SETTING PARAMETER
LED 1 operand SETTING GROUP ACT 1 LED 13 operand Off
LED 2 operand SETTING GROUP ACT 2 LED 14 operand Off
LED 3 operand SETTING GROUP ACT 3 LED 15 operand Off
LED 4 operand SETTING GROUP ACT 4 LED 16 operand Off
LED 5 operand SETTING GROUP ACT 5 LED 17 operand SYNC 1 SYNC OP
LED 6 operand SETTING GROUP ACT 6 LED 18 operand SYNC 2 SYNC OP
LED 7 operand Off LED 19 operand Off
LED 8 operand Off LED 20 operand Off
LED 9 operand Off LED 21 operand Off
LED 10 operand Off LED 22 operand Off
LED 11 operand Off LED 23 operand Off
LED 12 operand Off LED 24 operand Off

5-48 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

Refer to the Control of setting groups example in the Control elements section of this chapter for group activation.

5.2.11 USER-PROGRAMMABLE SELF TESTS

PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE SELF TESTS

„ USER-PROGRAMMABLE DIRECT RING BREAK Range: Disabled, Enabled. Valid for units equipped with
„ SELF TESTS FUNCTION: Enabled Direct Input/Output module.

DIRECT DEVICE OFF Range: Disabled, Enabled. Valid for units equipped with
MESSAGE Direct Input/Output module.
FUNCTION: Enabled
REMOTE DEVICE OFF Range: Disabled, Enabled. Valid for units that contain a
MESSAGE CPU with Ethernet capability.
FUNCTION: Enabled
PRI. ETHERNET FAIL Range: Disabled, Enabled. Valid for units that contain a
MESSAGE CPU with a primary fiber port.
FUNCTION: Disabled
SEC. ETHERNET FAIL Range: Disabled, Enabled. Valid for units that contain a
MESSAGE CPU with a redundant fiber port.
FUNCTION: Disabled
BATTERY FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Enabled
SNTP FAIL Range: Disabled, Enabled. Valid for units that contain a
MESSAGE CPU with Ethernet capability.
FUNCTION: Enabled
IRIG-B FAIL Range: Disabled, Enabled.
MESSAGE
FUNCTION: Enabled
Range: Disabled, Enabled.
5
ETHERNET SWITCH FAIL
MESSAGE
FUNCTION: Disabled

All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the minor alarms can be disabled if desired.
When in the “Disabled” mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, or display
target messages. Moreover, they will not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in the “Enabled”
mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section in
chapter 7 for additional information on major and minor self-test alarms.
To enable the Ethernet switch failure function, ensure that the ETHERNET SWITCH FAIL FUNCTION is “Enabled” in this
menu.
NOTE

5.2.12 CONTROL PUSHBUTTONS

PATH: SETTINGS Ö PRODUCT SETUP ÖØ CONTROL PUSHBUTTONS Ö CONTROL PUSHBUTTON 1(7)

„ CONTROL CONTROL PUSHBUTTON 1 Range: Disabled, Enabled


„ PUSHBUTTON 1 FUNCTION: Disabled
CONTROL PUSHBUTTON 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.

GE Multilin G60 Generator Protection System 5-49


5.2 PRODUCT SETUP 5 SETTINGS

The location of the control pushbuttons are shown in the following figures.

Control pushbuttons
842813A1.CDR

Figure 5–4: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE)


An additional four control pushbuttons are included on the standard faceplate when the G60 is ordered with the twelve
user-programmable pushbutton option.

STATUS EVENT CAUSE


IN SERVICE VOLTAGE
TROUBLE CURRENT RESET
TEST MODE FREQUENCY
TRIP OTHER USER 1 THREE
ALARM PHASE A STANDARD
PICKUP PHASE B USER 2
PHASE C
CONTROL
NEUTRAL/GROUND USER 3 PUSHBUTTONS

USER 4

USER 5 FOUR EXTRA

5 USER 6

USER 7
OPTIONAL
CONTROL
PUSHBUTTONS

842733A2.CDR

Figure 5–5: CONTROL PUSHBUTTONS (STANDARD FACEPLATE)


Control pushbuttons are not typically used for critical operations and are not protected by the control password. However,
by supervising their output operands, the user can dynamically enable or disable control pushbuttons for security reasons.
Each control pushbutton asserts its own FlexLogic™ operand. These operands should be configured appropriately to per-
form the desired function. The operand remains asserted as long as the pushbutton is pressed and resets when the push-
button is released. A dropout delay of 100 ms is incorporated to ensure fast pushbutton manipulation will be recognized by
various features that may use control pushbuttons as inputs.
An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when
the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously – a given key
must be released before the next one can be pressed.

SETTING
CONTROL PUSHBUTTON

{
1 FUNCTION:
Enabled=1

SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL:
When applicable

AND RUN
Enabled=1
OFF TIMER
SYSTEM SETUP/ FLEXLOGIC OPERAND
BREAKERS/BREAKER 2/ ON 0 CONTROL PUSHBTN 1 ON
BREAKER 2 PUSHBUTTON 100 msec
CONTROL:
842010A2.CDR
Enabled=1

Figure 5–6: CONTROL PUSHBUTTON LOGIC

5-50 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

5.2.13 USER-PROGRAMMABLE PUSHBUTTONS

PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE PUSHBUTTONS Ö USER PUSHBUTTON 1(16)

„ USER PUSHBUTTON 1 PUSHBUTTON 1 Range: Self-Reset, Latched, Disabled


„ FUNCTION: Disabled
PUSHBTN 1 ID TEXT: Range: Up to 20 alphanumeric characters
MESSAGE

PUSHBTN 1 ON TEXT: Range: Up to 20 alphanumeric characters


MESSAGE

PUSHBTN 1 OFF TEXT: Range: Up to 20 alphanumeric characters


MESSAGE

PUSHBTN 1 HOLD: Range: 0.0 to 10.0 s in steps of 0.1


MESSAGE
0.0 s
PUSHBTN 1 SET: Range: FlexLogic™ operand
MESSAGE
Off
PUSHBTN 1 RESET: Range: FlexLogic™ operand
MESSAGE
Off
PUSHBTN 1 AUTORST: Range: Disabled, Enabled
MESSAGE
Disabled
PUSHBTN 1 AUTORST Range: 0.2 to 600.0 s in steps of 0.1
MESSAGE
DELAY: 1.0 s 5
PUSHBTN 1 REMOTE: Range: FlexLogic™ operand
MESSAGE
Off
PUSHBTN 1 LOCAL: Range: FlexLogic™ operand
MESSAGE
Off
PUSHBTN 1 DROP-OUT Range: 0 to 60.00 s in steps of 0.05
MESSAGE
TIME: 0.00 s
PUSHBTN 1 LED CTL: Range: FlexLogic™ operand
MESSAGE
Off
PUSHBTN 1 MESSAGE: Range: Disabled, Normal, High Priority
MESSAGE
Disabled
PUSHBUTTON 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The optional user-programmable pushbuttons (specified in the order code) provide an easy and error-free method of enter-
ing digital state (on, off) information. The number of available pushbuttons is dependent on the faceplate module ordered
with the relay.
• Type P faceplate: standard horizontal faceplate with 12 user-programmable pushbuttons.
• Type Q faceplate: enhanced horizontal faceplate with 16 user-programmable pushbuttons.
The digital state can be entered locally (by directly pressing the front panel pushbutton) or remotely (via FlexLogic™ oper-
ands) into FlexLogic™ equations, protection elements, and control elements. Typical applications include breaker control,
autorecloser blocking, and setting groups changes. The user-programmable pushbuttons are under the control level of
password protection.
The user-configurable pushbuttons for the enhanced faceplate are shown below.

GE Multilin G60 Generator Protection System 5-51


5.2 PRODUCT SETUP 5 SETTINGS

USER USER USER USER USER USER USER USER USER USER USER USER USER USER USER USER
LABEL 1 LABEL 2 LABEL 3 LABEL 4 LABEL 5 LABEL 6 LABEL 7 LABEL 8 LABEL 9 LABEL 10 LABEL 11 LABEL 12 LABEL 13 LABEL 14 LABEL 15 LABEL 16

842814A1.CDR

Figure 5–7: USER-PROGRAMMABLE PUSHBUTTONS (ENHANCED FACEPLATE)


The user-configurable pushbuttons for the standard faceplate are shown below.

1 3 5 7 9 11
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL

2 4 6 8 10 12
USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL USER LABEL

842779A1.CDR

Figure 5–8: USER-PROGRAMMABLE PUSHBUTTONS (STANDARD FACEPLATE)


Both the standard and enhanced faceplate pushbuttons can be custom labeled with a factory-provided template, available
online at http://www.GEmultilin.com. The EnerVista UR Setup software can also be used to create labels for the enhanced
faceplate.
Each pushbutton asserts its own “On” and “Off” FlexLogic™ operands (for example, PUSHBUTTON 1 ON and PUSHBUTTON
5 1 OFF). These operands are available for each pushbutton and are used to program specific actions. If any pushbutton is
active, the ANY PB ON operand will be asserted.
Each pushbutton has an associated LED indicator. By default, this indicator displays the present status of the correspond-
ing pushbutton (on or off). However, each LED indicator can be assigned to any FlexLogic™ operand through the PUSHBTN
1 LED CTL setting.

The pushbuttons can be automatically controlled by activating the operands assigned to the PUSHBTN 1 SET (for latched and
self-reset mode) and PUSHBTN 1 RESET (for latched mode only) settings. The pushbutton reset status is declared when the
PUSHBUTTON 1 OFF operand is asserted. The activation and deactivation of user-programmable pushbuttons is dependent
on whether latched or self-reset mode is programmed.
• Latched mode: In latched mode, a pushbutton can be set (activated) by asserting the operand assigned to the PUSH-
BTN 1 SET setting or by directly pressing the associated front panel pushbutton. The pushbutton maintains the set state
until deactivated by the reset command or after a user-specified time delay. The state of each pushbutton is stored in
non-volatile memory and maintained through a loss of control power.
The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the PUSHBTN 1 RESET set-
ting or by directly pressing the associated active front panel pushbutton.
It can also be programmed to reset automatically through the PUSHBTN 1 AUTORST and PUSHBTN 1 AUTORST DELAY set-
tings. These settings enable the autoreset timer and specify the associated time delay. The autoreset timer can be
used in select-before-operate (SBO) breaker control applications, where the command type (close/open) or breaker
location (feeder number) must be selected prior to command execution. The selection must reset automatically if con-
trol is not executed within a specified time period.
• Self-reset mode: In self-reset mode, a pushbutton will remain active for the time it is pressed (the pulse duration) plus
the dropout time specified in the PUSHBTN 1 DROP-OUT TIME setting. If the pushbutton is activated via FlexLogic™, the
pulse duration is specified by the PUSHBTN 1 DROP-OUT TIME only. The time the operand remains assigned to the PUSH-
BTN 1 SET setting has no effect on the pulse duration.

The pushbutton is reset (deactivated) in self-reset mode when the dropout delay specified in the PUSHBTN 1 DROP-OUT
TIMEsetting expires.
The pulse duration of the remote set, remote reset, or local pushbutton must be at least 50 ms to operate the push-
button. This allows the user-programmable pushbuttons to properly operate during power cycling events and vari-
NOTE ous system disturbances that may cause transient assertion of the operating signals.

5-52 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

The local and remote operation of each user-programmable pushbutton can be inhibited through the PUSHBTN 1 LOCAL and
PUSHBTN 1 REMOTE settings, respectively. If local locking is applied, the pushbutton will ignore set and reset commands
executed through the front panel pushbuttons. If remote locking is applied, the pushbutton will ignore set and reset com-
mands executed through FlexLogic™ operands.
The locking functions are not applied to the autorestart feature. In this case, the inhibit function can be used in SBO control
operations to prevent the pushbutton function from being activated and ensuring “one-at-a-time” select operation.
The locking functions can also be used to prevent the accidental pressing of the front panel pushbuttons. The separate
inhibit of the local and remote operation simplifies the implementation of local/remote control supervision.
Pushbutton states can be logged by the event recorder and displayed as target messages. In latched mode, user-defined
messages can also be associated with each pushbutton and displayed when the pushbutton is on or changing to off.
• PUSHBUTTON 1 FUNCTION: This setting selects the characteristic of the pushbutton. If set to “Disabled”, the push-
button is not active and the corresponding FlexLogic™ operands (both “On” and “Off”) are de-asserted. If set to “Self-
Reset”, the control logic is activated by the pulse (longer than 100 ms) issued when the pushbutton is being physically
pressed or virtually pressed via a FlexLogic™ operand assigned to the PUSHBTN 1 SET setting.
When in “Self-Reset” mode and activated locally, the pushbutton control logic asserts the “On” corresponding Flex-
Logic™ operand as long as the pushbutton is being physically pressed, and after being released the deactivation of
the operand is delayed by the drop out timer. The “Off” operand is asserted when the pushbutton element is deacti-
vated. If the pushbutton is activated remotely, the control logic of the pushbutton asserts the corresponding “On” Flex-
Logic™ operand only for the time period specified by the PUSHBTN 1 DROP-OUT TIME setting.
If set to “Latched”, the control logic alternates the state of the corresponding FlexLogic™ operand between “On” and
“Off” on each button press or by virtually activating the pushbutton (assigning set and reset operands). When in the
“Latched” mode, the states of the FlexLogic™ operands are stored in a non-volatile memory. Should the power supply
be lost, the correct state of the pushbutton is retained upon subsequent power up of the relay.
• PUSHBTN 1 ID TEXT: This setting specifies the top 20-character line of the user-programmable message and is 5
intended to provide ID information of the pushbutton. Refer to the User-definable displays section for instructions on
how to enter alphanumeric characters from the keypad.
• PUSHBTN 1 ON TEXT: This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is in the “on” position. Refer to the User-definable displays section for instructions on
entering alphanumeric characters from the keypad.
• PUSHBTN 1 OFF TEXT: This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is activated from the on to the off position and the PUSHBUTTON 1 FUNCTION is
“Latched”. This message is not displayed when the PUSHBUTTON 1 FUNCTION is “Self-reset” as the pushbutton operand
status is implied to be “Off” upon its release. The length of the “Off” message is configured with the PRODUCT SETUP
ÖØ DISPLAY PROPERTIES Ö FLASH MESSAGE TIME setting.
• PUSHBTN 1 HOLD: This setting specifies the time required for a pushbutton to be pressed before it is deemed active.
This timer is reset upon release of the pushbutton. Note that any pushbutton operation will require the pushbutton to be
pressed a minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer.
• PUSHBTN 1 SET: This setting assigns the FlexLogic™ operand serving to operate the pushbutton element and to
assert PUSHBUTTON 1 ON operand. The duration of the incoming set signal must be at least 100 ms.
• PUSHBTN 1 RESET: This setting assigns the FlexLogic™ operand serving to reset pushbutton element and to assert
PUSHBUTTON 1 OFF operand. This setting is applicable only if pushbutton is in latched mode. The duration of the
incoming reset signal must be at least 50 ms.
• PUSHBTN 1 AUTORST: This setting enables the user-programmable pushbutton autoreset feature. This setting is
applicable only if the pushbutton is in the “Latched” mode.
• PUSHBTN 1 AUTORST DELAY: This setting specifies the time delay for automatic reset of the pushbutton when in
the latched mode.
• PUSHBTN 1 REMOTE: This setting assigns the FlexLogic™ operand serving to inhibit pushbutton operation from the
operand assigned to the PUSHBTN 1 SET or PUSHBTN 1 RESET settings.
• PUSHBTN 1 LOCAL: This setting assigns the FlexLogic™ operand serving to inhibit pushbutton operation from the
front panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset.

GE Multilin G60 Generator Protection System 5-53


5.2 PRODUCT SETUP 5 SETTINGS

• PUSHBTN 1 DROP-OUT TIME: This setting applies only to “Self-Reset” mode and specifies the duration of the push-
button active status after the pushbutton has been released. When activated remotely, this setting specifies the entire
activation time of the pushbutton status; the length of time the operand remains on has no effect on the pulse duration.
This setting is required to set the duration of the pushbutton operating pulse.
• PUSHBTN 1 LED CTL: This setting assigns the FlexLogic™ operand serving to drive pushbutton LED. If this setting is
“Off”, then LED operation is directly linked to PUSHBUTTON 1 ON operand.
• PUSHBTN 1 MESSAGE: If pushbutton message is set to “High Priority”, the message programmed in the PUSHBTN 1
IDand PUSHBTN 1 ON TEXT settings will be displayed undisturbed as long as PUSHBUTTON 1 ON operand is asserted.
The high priority option is not applicable to the PUSHBTN 1 OFF TEXT setting.
This message can be temporary removed if any front panel keypad button is pressed. However, ten seconds of keypad
inactivity will restore the message if the PUSHBUTTON 1 ON operand is still active.
If the PUSHBTN 1 MESSAGE is set to “Normal”, the message programmed in the PUSHBTN 1 ID and PUSHBTN 1 ON TEXT
settings will be displayed as long as PUSHBUTTON 1 ON operand is asserted, but not longer than time period specified
by FLASH MESSAGE TIME setting. After the flash time is expired, the default message or other active target message is
displayed. The instantaneous reset of the flash message will be executed if any relay front panel button is pressed or
any new target or message becomes active.
The PUSHBTN 1 OFF TEXT setting is linked to PUSHBUTTON 1 OFF operand and will be displayed in conjunction with
PUSHBTN 1 ID only if pushbutton element is in the “Latched” mode. The PUSHBTN 1 OFF TEXT message will be displayed
as “Normal” if the PUSHBTN 1 MESSAGE setting is “High Priority” or “Normal”.
• PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into
event recorder.

5-54 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

The user-programmable pushbutton logic is shown below.


TIMER
FLEXLOGIC OPERAND 200 ms
PUSHBUTTON 1 OFF
0

SETTING
Function
LATCHED To user-programmable
= Enabled
pushbuttons logic
= Latched sheet 2, 842024A2
OR LATCHED/SELF-RESET
= Self-Reset

SETTING
Local Lock
Off = 0
Non-volatile latch
AND
S
TIMER
SETTING Latch
50 ms
Remote Lock R
Off = 0 AND
0

SETTING TIMER
OR
Hold 50 ms
TPKP
0
0

OR
SETTING
Set AND
Off = 0
To user-programmable
OR PUSHBUTTON ON pushbuttons logic
OR
sheet 2, 842024A2
SETTING
Reset AND
Off = 0
AND
5
SETTING
SETTING
Autoreset Delay
Autoreset Function
TPKP
= Enabled
AND
= Disabled
0
AND
SETTING
Drop-Out Timer

TIMER 0
FLEXLOGIC OPERAND 200 ms OR
TRST
PUSHBUTTON 1 ON
0
842021A3.CDR

AND

Figure 5–9: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2)

GE Multilin G60 Generator Protection System 5-55


5.2 PRODUCT SETUP 5 SETTINGS

LCD MESSAGE
ENGAGE MESSAGE
SETTING
Flash Message Time
LATCHED SETTINGS
0 Top Text
AND
OR TRST = XXXXXXXXXX
On Text
= XXXXXXXXXX
Instantaneous
From user-programmable reset *
pushbuttons logic
sheet 1, 842021A3
FLEXLOGIC OPERAND
LATCHED/SELF-RESET
AND PUSHBUTTON 1 OFF

FLEXLOGIC OPERAND
PUSHBUTTON ON PUSHBUTTON 1 ON

The message is temporarily removed if


any keypad button is pressed. Ten (10)
seconds of keypad inactivity restores LCD MESSAGE
SETTING the message.
ENGAGE MESSAGE
Message Priority
AND
= Disabled
= High Priority SETTINGS
= Normal Top Text
= XXXXXXXXXX
OR
On Text
SETTING
= XXXXXXXXXX
Flash Message Time
0
AND
TRST

Instantaneous
Instantaneous reset will be executed if any reset *
front panel button is pressed or any new
target or message becomes active.

5 PUSHBUTTON 1 LED LOGIC


1. If pushbutton 1 LED control is set to off.
Pushbutton 1
FLEXLOGIC OPERAND LED
FLEXLOGIC OPERAND PUSHBUTTON 1 ON
PUSHBUTTON 1 ON
PUSHBUTTON 2 ON 2. If pushbutton 1 LED control is not set to off.
FLEXLOGIC OPERAND
PUSHBUTTON 3 ON SETTING Pushbutton 1
OR ANY PB ON
PUSHBTN 1 LED CTL LED

= any FlexLogic operand


PUSHBUTTON 16 ON
The enhanced front panel has 16 operands;
the standard front panel has 12 842024A2.CDR

Figure 5–10: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 2 of 2)


User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered
separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via
NOTE
EnerVista UR Setup with the Maintenance > Enable Pushbutton command.

5.2.14 FLEX STATE PARAMETERS

PATH: SETTINGS Ö PRODUCT SETUP ÖØ FLEX STATE PARAMETERS

„ FLEX STATE PARAMETER 1: Range: FlexLogic™ operand


„ PARAMETERS Off
PARAMETER 2: Range: FlexLogic™ operand
MESSAGE
Off
PARAMETER 3: Range: FlexLogic™ operand
MESSAGE
Off

PARAMETER 256: Range: FlexLogic™ operand


MESSAGE
Off

5-56 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

This feature provides a mechanism where any of 256 selected FlexLogic™ operand states can be used for efficient moni-
toring. The feature allows user-customized access to the FlexLogic™ operand states in the relay. The state bits are packed
so that 16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states
which are of interest to the user are available in a minimum number of Modbus registers.
The state bits may be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. There are sixteen registers to accommo-
date the 256 state bits.

5.2.15 USER-DEFINABLE DISPLAYS

a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-DEFINABLE DISPLAYS

„ USER-DEFINABLE INVOKE AND SCROLL: Range: FlexLogic™ operand


„ DISPLAYS Off
„ USER DISPLAY 1 Range: up to 20 alphanumeric characters
MESSAGE
„
„ USER DISPLAY 3 Range: up to 20 alphanumeric characters
MESSAGE
„
„ USER DISPLAY 2 Range: up to 20 alphanumeric characters
MESSAGE
„

„ USER DISPLAY 16 Range: up to 20 alphanumeric characters


MESSAGE
„ 5
This menu provides a mechanism for manually creating up to 16 user-defined information displays in a convenient viewing
sequence in the USER DISPLAYS menu (between the TARGETS and ACTUAL VALUES top-level menus). The sub-menus facili-
tate text entry and Modbus register data pointer options for defining the user display content.
Once programmed, the user-definable displays can be viewed in two ways.
• KEYPAD: Use the MENU key to select the USER DISPLAYS menu item to access the first user-definable display (note
that only the programmed screens are displayed). The screens can be scrolled using the UP and DOWN keys. The
display disappears after the default message time-out period specified by the PRODUCT SETUP ÖØ DISPLAY PROPER-
TIES ÖØ DEFAULT MESSAGE TIMEOUT setting.

• USER-PROGRAMMABLE CONTROL INPUT: The user-definable displays also respond to the INVOKE AND SCROLL
setting. Any FlexLogic™ operand (in particular, the user-programmable pushbutton operands), can be used to navi-
gate the programmed displays.
On the rising edge of the configured operand (such as when the pushbutton is pressed), the displays are invoked by
showing the last user-definable display shown during the previous activity. From this moment onward, the operand
acts exactly as the down key and allows scrolling through the configured displays. The last display wraps up to the first
one. The INVOKE AND SCROLL input and the DOWN key operate concurrently.
When the default timer expires (set by the DEFAULT MESSAGE TIMEOUT setting), the relay will start to cycle through the
user displays. The next activity of the INVOKE AND SCROLL input stops the cycling at the currently displayed user dis-
play, not at the first user-defined display. The INVOKE AND SCROLL pulses must last for at least 250 ms to take effect.

GE Multilin G60 Generator Protection System 5-57


5.2 PRODUCT SETUP 5 SETTINGS

b) USER DISPLAY 1(16)


PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-DEFINABLE DISPLAYS Ö USER DISPLAY 1(16)

„ USER DISPLAY 1 DISP 1 TOP LINE: Range: up to 20 alphanumeric characters


„
DISP 1 BOTTOM LINE: Range: up to 20 alphanumeric characters
MESSAGE

DISP 1 ITEM 1 Range: 0 to 65535 in steps of 1


MESSAGE
0
DISP 1 ITEM 2 Range: 0 to 65535 in steps of 1
MESSAGE
0
DISP 1 ITEM 3 Range: 0 to 65535 in steps of 1
MESSAGE
0
DISP 1 ITEM 4 Range: 0 to 65535 in steps of 1
MESSAGE
0
DISP 1 ITEM 5: Range: 0 to 65535 in steps of 1
MESSAGE
0

Any existing system display can be automatically copied into an available user display by selecting the existing display and
pressing the ENTER key. The display will then prompt ADD TO USER DISPLAY LIST?. After selecting “Yes”, a message indi-
cates that the selected display has been added to the user display list. When this type of entry occurs, the sub-menus are
automatically configured with the proper content – this content may subsequently be edited.
5 This menu is used to enter user-defined text and user-selected Modbus-registered data fields into the particular user dis-
play. Each user display consists of two 20-character lines (top and bottom). The tilde (~) character is used to mark the start
of a data field – the length of the data field needs to be accounted for. Up to five separate data fields can be entered in a
user display – the nth tilde (~) refers to the nth item.
A user display may be entered from the faceplate keypad or the EnerVista UR Setup interface (preferred for convenience).
The following procedure shows how to enter text characters in the top and bottom lines from the faceplate keypad:
1. Select the line to be edited.
2. Press the decimal key to enter text edit mode.
3. Use either VALUE key to scroll through the characters. A space is selected like a character.
4. Press the decimal key to advance the cursor to the next position.
5. Repeat step 3 and continue entering characters until the desired text is displayed.
6. The HELP key may be pressed at any time for context sensitive help information.
7. Press the ENTER key to store the new settings.
To enter a numerical value for any of the five items (the decimal form of the selected Modbus address) from the faceplate
keypad, use the number keypad. Use the value of “0” for any items not being used. Use the HELP key at any selected sys-
tem display (setting, actual value, or command) which has a Modbus address, to view the hexadecimal form of the Modbus
address, then manually convert it to decimal form before entering it (EnerVista UR Setup usage conveniently facilitates this
conversion).
Use the MENU key to go to the user displays menu to view the user-defined content. The current user displays will show in
sequence, changing every four seconds. While viewing a user display, press the ENTER key and then select the ‘Yes”
option to remove the display from the user display list. Use the MENU key again to exit the user displays menu.

5-58 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

An example user display setup and result is shown below:

„ USER DISPLAY 1 DISP 1 TOP LINE: Shows user-defined text with first tilde marker.
„ Current X ~ A
DISP 1 BOTTOM LINE: Shows user-defined text with second tilde marker.
MESSAGE
Current Y ~ A
DISP 1 ITEM 1: Shows decimal form of user-selected Modbus register
MESSAGE address, corresponding to first tilde marker.
6016
DISP 1 ITEM 2: Shows decimal form of user-selected Modbus register
MESSAGE address, corresponding to second tilde marker.
6357
DISP 1 ITEM 3: This item is not being used. There is no corresponding
MESSAGE tilde marker in top or bottom lines.
0
DISP 1 ITEM 4: This item is not being used. There is no corresponding
MESSAGE tilde marker in top or bottom lines.
0
DISP 1 ITEM 5: This item is not being used. There is no corresponding
MESSAGE
0 tilde marker in top or bottom lines.

USER DISPLAYS Current X 0.850 Shows the resultant display content.



Current Y 0.327 A

If the parameters for the top line and the bottom line items have the same units, then the unit is displayed on the

NOTE
bottom line only. The units are only displayed on both lines if the units specified both the top and bottom line items 5
are different.

5.2.16 DIRECT INPUTS/OUTPUTS

a) MAIN MENU
PATH: SETTINGS Ö PRODUCT SETUP ÖØ DIRECT I/O

„ DIRECT I/O DIRECT OUTPUT Range: 1 to 16


„ DEVICE ID: 1
DIRECT I/O CH1 RING Range: Yes, No
MESSAGE
CONFIGURATION: Yes
DIRECT I/O CH2 RING Range: Yes, No
MESSAGE
CONFIGURATION: Yes
DIRECT I/O DATA Range: 64 kbps, 128 kbps
MESSAGE
RATE: 64 kbps
DIRECT I/O CHANNEL Range: Disabled, Enabled
MESSAGE
CROSSOVER: Disabled
„ CRC ALARM CH1
MESSAGE See page 5–65.
„
„ CRC ALARM CH2
MESSAGE See page 5–65.
„
„ UNRETURNED
MESSAGE See page 5–66.
„ MESSAGES ALARM CH1
„ UNRETURNED
MESSAGE See page 5–66.
„ MESSAGES ALARM CH2

GE Multilin G60 Generator Protection System 5-59


5.2 PRODUCT SETUP 5 SETTINGS

Direct inputs and outputs are intended for exchange of status information (inputs and outputs) between UR-series relays
connected directly via type 7 digital communications cards. The mechanism is very similar to IEC 61850 GSSE, except that
communications takes place over a non-switchable isolated network and is optimized for speed. On type 7 cards that sup-
port two channels, direct output messages are sent from both channels simultaneously. This effectively sends direct output
messages both ways around a ring configuration. On type 7 cards that support one channel, direct output messages are
sent only in one direction. Messages will be resent (forwarded) when it is determined that the message did not originate at
the receiver.
Direct output message timing is similar to GSSE message timing. Integrity messages (with no state changes) are sent at
least every 1000 ms. Messages with state changes are sent within the main pass scanning the inputs and asserting the
outputs unless the communication channel bandwidth has been exceeded. Two self-tests are performed and signaled by
the following FlexLogic™ operands:
1. DIRECT RING BREAK (direct input/output ring break). This FlexLogic™ operand indicates that direct output messages
sent from a UR-series relay are not being received back by the relay.
2. DIRECT DEVICE 1 OFF to DIRECT DEVICE 16 OFF (direct device offline). These FlexLogic™ operands indicate that direct
output messages from at least one direct device are not being received.
Direct input and output settings are similar to remote input and output settings. The equivalent of the remote device name
strings for direct inputs and outputs is the DIRECT OUTPUT DEVICE ID. The DIRECT OUTPUT DEVICE ID setting identifies the
relay in all direct output messages. All UR-series IEDs in a ring should have unique numbers assigned. The IED ID is used
to identify the sender of the direct input and output message.
If the direct input and output scheme is configured to operate in a ring (DIRECT I/O CH1 RING CONFIGURATION or DIRECT I/O
CH2 RING CONFIGURATION is “Yes”), all direct output messages should be received back. If not, the direct input/output ring
break self-test is triggered. The self-test error is signaled by the DIRECT RING BREAK FlexLogic™ operand.
Select the DIRECT I/O DATA RATE to match the data capabilities of the communications channel. All IEDs communicating
5 over direct inputs and outputs must be set to the same data rate. UR-series IEDs equipped with dual-channel communica-
tions cards apply the same data rate to both channels. Delivery time for direct input and output messages is approximately
0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each ‘bridge’.

5-60 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

Table 5–5: DIRECT INPUT AND OUTPUT DATA RATES


MODULE CHANNEL SUPPORTED DATA RATES
74 Channel 1 64 kbps
Channel 2 64 kbps
7L Channel 1 64 kbps, 128 kbps
Channel 2 64 kbps, 128 kbps
7M Channel 1 64 kbps, 128 kbps
Channel 2 64 kbps, 128 kbps
7P Channel 1 64 kbps, 128 kbps
Channel 2 64 kbps, 128 kbps
7T Channel 1 64 kbps, 128 kbps
7W Channel 1 64 kbps, 128 kbps
Channel 2 64 kbps, 128 kbps
7V Channel 1 64 kbps, 128 kbps
Channel 2 64 kbps, 128 kbps
2A Channel 1 64 kbps
2B Channel 1 64 kbps
Channel 2 64 kbps
2G Channel 1 128 kbps
2H Channel 1 128 kbps
76 Channel 1 64 kbps
77 Channel 1 64 kbps 5
Channel 2 64 kbps
75 Channel 1 64 kbps
Channel 2 64 kbps
7E Channel 1 64 kbps
Channel 2 64 kbps
7F Channel 1 64 kbps
Channel 2 64 kbps
7G Channel 1 64 kbps
Channel 2 64 kbps
7Q Channel 1 64 kbps
Channel 2 64 kbps
7R Channel 1 64 kbps
7S Channel 1 64 kbps
Channel 2 64 kbps

The G.703 modules are fixed at 64 kbps. The DIRECT I/O DATA RATE setting is not applicable to these modules.

NOTE

The DIRECT I/O CHANNEL CROSSOVER setting applies to G60s with dual-channel communication cards and allows crossing
over messages from channel 1 to channel 2. This places all UR-series IEDs into one direct input and output network
regardless of the physical media of the two communication channels.
The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the
Inputs and outputs section in this chapter for information on configuring FlexLogic™ operands (flags, bits) to be exchanged.

GE Multilin G60 Generator Protection System 5-61


5.2 PRODUCT SETUP 5 SETTINGS

EXAMPLE 1: EXTENDING THE INPUT/OUTPUT CAPABILITIES OF A UR-SERIES RELAY


Consider an application that requires additional quantities of digital inputs or output contacts or lines of programmable logic
that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such
as the C30, to satisfy the additional input and output and programmable logic requirements. The two IEDs are connected
via single-channel digital communication cards as shown in the figure below.

TX1
UR IED 1
RX1

TX1
UR IED 2
RX1

842711A1.CDR

Figure 5–11: INPUT AND OUTPUT EXTENSION VIA DIRECT INPUTS AND OUTPUTS
In the above application, the following settings should be applied. For UR-series IED 1:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O DATA RATE: “128 kbps”

For UR-series IED 2:


DIRECT OUTPUT DEVICE ID: “2”
“Yes”
5 DIRECT I/O CH1 RING CONFIGURATION:
DIRECT I/O DATA RATE: “128 kbps”

The message delivery time is about 0.2 of power cycle in both ways (at 128 kbps); that is, from device 1 to device 2, and
from device 2 to device 1. Different communications cards can be selected by the user for this back-to-back connection (for
example: fiber, G.703, or RS422).
EXAMPLE 2: INTERLOCKING BUSBAR PROTECTION
A simple interlocking busbar protection scheme could be accomplished by sending a blocking signal from downstream
devices, say 2, 3, and 4, to the upstream device that monitors a single incomer of the busbar, as shown below.

UR IED 1 BLOCK

UR IED 2 UR IED 3 UR IED 4

842712A1.CDR

Figure 5–12: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME


For increased reliability, a dual-ring configuration (shown below) is recommended for this application.

5-62 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

TX1 RX1
UR IED 1
RX2 TX2

RX1 TX2 RX2 TX1


UR IED 2 UR IED 4
TX1 RX2 TX2 RX1

TX2 RX2
UR IED 3
RX1 TX1
842716A1.CDR

Figure 5–13: INTERLOCKING BUS PROTECTION SCHEME VIA DIRECT INPUTS/OUTPUTS


In the above application, the following settings should be applied. For UR-series IED 1:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 2:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 3:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes” 5
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 4:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
Message delivery time is approximately 0.2 of power system cycle (at 128 kbps) times number of ‘bridges’ between the ori-
gin and destination. Dual-ring configuration effectively reduces the maximum ‘communications distance’ by a factor of two.
In this configuration the following delivery times are expected (at 128 kbps) if both rings are healthy:
IED 1 to IED 2: 0.2 of power system cycle;
IED 1 to IED 3: 0.4 of power system cycle;
IED 1 to IED 4: 0.2 of power system cycle;
IED 2 to IED 3: 0.2 of power system cycle;
IED 2 to IED 4: 0.4 of power system cycle;
IED 3 to IED 4: 0.2 of power system cycle.
If one ring is broken (say TX2-RX2) the delivery times are as follows:
IED 1 to IED 2: 0.2 of power system cycle;
IED 1 to IED 3: 0.4 of power system cycle;
IED 1 to IED 4: 0.6 of power system cycle;
IED 2 to IED 3: 0.2 of power system cycle;
IED 2 to IED 4: 0.4 of power system cycle;
IED 3 to IED 4: 0.2 of power system cycle.
A coordinating timer for this bus protection scheme could be selected to cover the worst case scenario (0.4 of a power sys-
tem cycle). Upon detecting a broken ring, the coordination time should be adaptively increased to 0.6 of a power system
cycle. The complete application requires addressing a number of issues such as failure of both the communications rings,
failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature
would be primarily used to address these concerns.

GE Multilin G60 Generator Protection System 5-63


5.2 PRODUCT SETUP 5 SETTINGS

EXAMPLE 3: PILOT-AIDED SCHEMES


Consider the three-terminal line protection application shown below:

UR IED 1 UR IED 2

UR IED 3
842713A1.CDR

Figure 5–14: THREE-TERMINAL LINE APPLICATION


A permissive pilot-aided scheme could be implemented in a two-ring configuration as shown below (IEDs 1 and 2 constitute
a first ring, while IEDs 2 and 3 constitute a second ring):

TX1 RX1 RX2


UR IED 1 UR IED 2
RX1 TX1 TX2

5
RX1
UR IED 3
TX1
842714A1.CDR

Figure 5–15: SINGLE-CHANNEL OPEN LOOP CONFIGURATION


In the above application, the following settings should be applied. For UR-series IED 1:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 2:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 3:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
In this configuration the following delivery times are expected (at 128 kbps):
IED 1 to IED 2: 0.2 of power system cycle;
IED 1 to IED 3: 0.5 of power system cycle;
IED 2 to IED 3: 0.2 of power system cycle.
In the above scheme, IEDs 1 and 3 do not communicate directly. IED 2 must be configured to forward the messages as
explained in the Inputs and outputs section. A blocking pilot-aided scheme should be implemented with more security and,
ideally, faster message delivery time. This could be accomplished using a dual-ring configuration as shown below.

5-64 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

TX2 TX1 RX1 RX2


UR IED 1 UR IED 2
RX1 RX2 TX2 TX1

TX1 RX1
UR IED 3
RX2 TX2
842715A1.CDR

Figure 5–16: DUAL-CHANNEL CLOSED LOOP (DUAL-RING) CONFIGURATION


In the above application, the following settings should be applied. For UR-series IED 1:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 2:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION: “Yes”
DIRECT I/O CH2 RING CONFIGURATION: “Yes”
For UR-series IED 3:
DIRECT OUTPUT DEVICE ID: “1”
DIRECT I/O CH1 RING CONFIGURATION:
DIRECT I/O CH2 RING CONFIGURATION:
“Yes”
“Yes”
5
In this configuration the following delivery times are expected (at 128 kbps) if both the rings are healthy:
IED 1 to IED 2: 0.2 of power system cycle;
IED 1 to IED 3: 0.2 of power system cycle;
IED 2 to IED 3: 0.2 of power system cycle.
The two communications configurations could be applied to both permissive and blocking schemes. Speed, reliability and
cost should be taken into account when selecting the required architecture.

b) CRC ALARM CH1(2)


PATH: SETTINGS Ö PRODUCT SETUP ÖØ DIRECT I/O ÖØ CRC ALARM CH1(2)

„ CRC ALARM CH1 CRC ALARM CH1 Range: Enabled, Disabled


„ FUNCTION: Disabled
CRC ALARM CH1 Range: 100 to 10000 in steps of 1
MESSAGE
MESSAGE COUNT: 600
CRC ALARM CH1 Range: 1 to 1000 in steps of 1
MESSAGE
THRESHOLD: 10
CRC ALARM CH1 Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled

The G60 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is
available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The
monitoring function counts all incoming messages, including messages that failed the CRC check. A separate counter adds
up messages that failed the CRC check. When the failed CRC counter reaches the user-defined level specified by the CRC
ALARM CH1 THRESHOLD setting within the user-defined message count CRC ALARM 1 CH1 COUNT, the DIR IO CH1 CRC ALARM
FlexLogic™ operand is set.
When the total message counter reaches the user-defined maximum specified by the CRC ALARM CH1 MESSAGE COUNT set-
ting, both the counters reset and the monitoring process is restarted.

GE Multilin G60 Generator Protection System 5-65


5.2 PRODUCT SETUP 5 SETTINGS

The operand shall be configured to drive an output contact, user-programmable LED, or selected communication-based
output. Latching and acknowledging conditions - if required - should be programmed accordingly.
The CRC alarm function is available on a per-channel basis. The total number of direct input and output messages that
failed the CRC check is available as the ACTUAL VALUES Ö STATUS ÖØ DIRECT INPUTS ÖØ CRC FAIL COUNT CH1 actual
value.
• Message count and length of the monitoring window: To monitor communications integrity, the relay sends 1 message
per second (at 64 kbps) or 2 messages per second (128 kbps) even if there is no change in the direct outputs. For
example, setting the CRC ALARM CH1 MESSAGE COUNT to “10000”, corresponds a time window of about 160 minutes at
64 kbps and 80 minutes at 128 kbps. If the messages are sent faster as a result of direct outputs activity, the monitor-
ing time interval will shorten. This should be taken into account when determining the CRC ALARM CH1 MESSAGE COUNT
setting. For example, if the requirement is a maximum monitoring time interval of 10 minutes at 64 kbps, then the CRC
ALARM CH1 MESSAGE COUNT should be set to 10 × 60 × 1 = 600.

• Correlation of failed CRC and bit error rate (BER): The CRC check may fail if one or more bits in a packet are cor-
rupted. Therefore, an exact correlation between the CRC fail rate and the BER is not possible. Under certain assump-
tions an approximation can be made as follows. A direct input and output packet containing 20 bytes results in 160 bits
of data being sent and therefore, a transmission of 63 packets is equivalent to 10,000 bits. A BER of 10–4 implies 1 bit
error for every 10000 bits sent or received. Assuming the best case of only 1 bit error in a failed packet, having 1 failed
packet for every 63 received is about equal to a BER of 10–4.

c) UNRETURNED MESSAGES ALARM CH1(2)


PATH: SETTINGS Ö PRODUCT SETUP ÖØ DIRECT I/O ÖØ UNRETURNED MESSAGES ALARM CH1(2)

„ UNRETURNED UNRET MSGS ALARM CH1 Range: Enabled, Disabled


„ MESSAGES ALARM CH1 FUNCTION: Disabled
5 MESSAGE
UNRET MSGS ALARM CH1 Range: 100 to 10000 in steps of 1
MESSAGE COUNT: 600
UNRET MSGS ALARM CH1 Range: 1 to 1000 in steps of 1
MESSAGE
THRESHOLD: 10
UNRET MSGS ALARM CH1 Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled

The G60 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring
configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned
messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unre-
turned messages. This function counts all the outgoing messages and a separate counter adds the messages have failed
to return. When the unreturned messages counter reaches the user-definable level specified by the UNRET MSGS ALARM
CH1 THRESHOLD setting and within the user-defined message count UNRET MSGS ALARM CH1 COUNT, the DIR IO CH1 UNRET
ALM FlexLogic™ operand is set.

When the total message counter reaches the user-defined maximum specified by the UNRET MSGS ALARM CH1 MESSAGE
COUNT setting, both the counters reset and the monitoring process is restarted.

The operand shall be configured to drive an output contact, user-programmable LED, or selected communication-based
output. Latching and acknowledging conditions, if required, should be programmed accordingly.
The unreturned messages alarm function is available on a per-channel basis and is active only in the ring configuration.
The total number of unreturned input and output messages is available as the ACTUAL VALUES Ö STATUS ÖØ DIRECT
INPUTS ÖØ UNRETURNED MSG COUNT CH1 actual value.

5-66 G60 Generator Protection System GE Multilin


5 SETTINGS 5.2 PRODUCT SETUP

5.2.17 TELEPROTECTION

PATH: SETTINGS Ö PRODUCT SETUP ÖØ TELEPROTECTION

„ TELEPROTECTION TELEPROTECTION Range: Disabled, Enabled


„ FUNCTION: Disabled
NUMBER OF TERMINALS: Range: 2, 3
MESSAGE
2
NUMBER OF COMM Range: 1, 2
MESSAGE
CHANNELS: 1
LOCAL RELAY ID Range: 0 to 255 in steps of 1
MESSAGE
NUMBER: 0
TERMINAL 1 RELAY ID Range: 0 to 255 in steps of 1
MESSAGE
NUMBER: 0
TERMINAL 2 RELAY ID Range: 0 to 255 in steps of 1
MESSAGE
NUMBER: 0

Digital teleprotection functionality is designed to transfer protection commands between two or three relays in a secure,
fast, dependable, and deterministic fashion. Possible applications are permissive or blocking pilot schemes and direct
transfer trip (DTT). Teleprotection can be applied over any analog or digital channels and any communications media, such
as direct fiber, copper wires, optical networks, or microwave radio links. A mixture of communication media is possible.
Once teleprotection is enabled and the teleprotection input/outputs are configured, data packets are transmitted continu-
ously every 1/4 cycle (3/8 cycle if using C37.94 modules) from peer-to-peer. Security of communication channel data is
achieved by using CRC-32 on the data packet.
5
Teleprotection inputs/outputs and direct inputs/outputs are mutually exclusive – as such, they cannot be used simu-
latneously. Once teleprotection inputs and outputs are enabled, direct inputs and outputs are blocked, and vice
NOTE versa.
• NUMBER OF TERMINALS: Specifies whether the teleprotection system operates between two peers or three peers.
• NUMBER OF CHANNELS: Specifies how many channels are used. If the NUMBER OF TERMINALS is “3” (three-terminal
system), set the NUMBER OF CHANNELS to “2”. For a two-terminal system, the NUMBER OF CHANNELS can set to “1” or
“2” (redundant channels).
• LOCAL RELAY ID NUMBER, TERMINAL 1 RELAY ID NUMBER, and TERMINAL 2 RELAY ID NUMBER: In installa-
tions that use multiplexers or modems, it is desirable to ensure that the data used by the relays protecting a given line
is from the correct relays. The teleprotection function performs this check by reading the message ID sent by transmit-
ting relays and comparing it to the programmed ID in the receiving relay. This check is also used to block inputs if inad-
vertently set to loopback mode or data is being received from a wrong relay by checking the ID on a received channel.
If an incorrect ID is found on a channel during normal operation, the TELEPROT CH1 ID FAIL or TELEPROT CH2 ID FAIL
FlexLogic™ operand is set, driving the event with the same name and blocking the teleprotection inputs. For commis-
sioning purposes, the result of channel identification is also shown in the STATUS ÖØ CHANNEL TESTS ÖØ VALIDITY OF
CHANNEL CONFIGURATION actual value. The default value of “0” for the LOCAL RELAY ID NUMBER indicates that relay ID
is not to be checked. On two- terminals two-channel systems, the same LOCAL RELAY ID NUMBER is transmitted over
both channels; as such, only the TERMINAL 1 ID NUMBER has to be programmed on the receiving end.

5.2.18 INSTALLATION

PATH: SETTINGS Ö PRODUCT SETUP ÖØ INSTALLATION

„ INSTALLATION RELAY SETTINGS: Range: Not Programmed, Programmed


„ Not Programmed
RELAY NAME: Range: up to 20 alphanumeric characters
MESSAGE
Relay-1

GE Multilin G60 Generator Protection System 5-67


5.2 PRODUCT SETUP 5 SETTINGS

To safeguard against the installation of a relay without any entered settings, the unit will not allow signaling of any output
relay until RELAY SETTINGS is set to "Programmed". This setting is defaulted to "Not Programmed" when at the factory. The
UNIT NOT PROGRAMMED self-test error message is displayed until the relay is put into the "Programmed" state.

The RELAY NAME setting allows the user to uniquely identify a relay. This name will appear on generated reports. This name
is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com-
munications channel using the IEC 61850 protocol.

5-68 G60 Generator Protection System GE Multilin


5 SETTINGS 5.3 REMOTE RESOURCES

5.3REMOTE RESOURCES 5.3.1 REMOTE RESOURCES CONFIGURATION

When G60 is ordered with a process card module as a part of HardFiber system, then an additional Remote Resources
menu tree is available in EnerVista UR Setup software to allow configuring HardFiber system.

Figure 5–17: REMOTE RESOURCES CONFIGURATION MENU


The remote resources settings configure a G60 with a process bus module to work with devices called Bricks. Remote
resources configuration is only available through the EnerVista UR Setup software, and is not available through the G60
front panel. A Brick provides eight AC measurements, along with contact inputs, DC analog inputs, and contact outputs, to 5
be the remote interface to field equipment such as circuit breakers and transformers. The G60 with a process bus module
has access to all of the capabilities of up to eight Bricks. Remote resources settings configure the point-to-point connection
between specific fiber optic ports on the G60 process card and specific Brick. The relay is then configured to measure spe-
cific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
The configuration process for remote resources is straightforward and consists of the following steps.
• Configure the field units. This establishes the point-to-point connection between a specific port on the relay process
bus module, and a specific digital core on a specific Brick. This is a necessary first step in configuring a process bus
relay.
• Configure the AC banks. This sets the primary and secondary quantities and connections for currents and voltages.
AC bank configuration also provides a provision for redundant measurements for currents and voltages, a powerful
reliability improvement possible with process bus.
• Configure signal sources. This functionality of the G60 has not changed other than the requirement to use currents and
voltages established by AC bank configuration under the remote resources menu.
• Configure field contact inputs, field contact outputs, RTDs, and transducers as required for the application's functional-
ity. These inputs and outputs are the physical interface to circuit breakers, transformers, and other equipment. They
replace the traditional contact inputs and outputs located at the relay to virtually eliminate copper wiring.
• Configure shared inputs and outputs as required for the application's functionality. Shared inputs and outputs are dis-
tinct binary channels that provide high-speed protection quality signaling between relays through a Brick.
For additional information on how to configure a relay with a process bus module, please refer to GE publication number
GEK-113500: HardFiber System Instruction Manual.

GE Multilin G60 Generator Protection System 5-69


5.4 SYSTEM SETUP 5 SETTINGS

5.4SYSTEM SETUP 5.4.1 AC INPUTS

a) CURRENT BANKS
PATH: SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS Ö CURRENT BANK F1(M5)

„ CURRENT BANK F1 PHASE CT F1 Range: 1 to 65000 A in steps of 1


„ PRIMARY: 1 A
PHASE CT F1 Range: 1 A, 5 A
MESSAGE
SECONDARY: 1 A
GROUND CT F1 Range: 1 to 65000 A in steps of 1
MESSAGE
PRIMARY: 1 A
GROUND CT F1 Range: 1 A, 5 A
MESSAGE
SECONDARY: 1 A

Because energy parameters are accumulated, these values should be recorded and then reset immediately
prior to changing CT characteristics.
NOTE

Four banks of phase and ground CTs can be set, where the current banks are denoted in the following format (X represents
the module slot position letter):
Xa, where X = {F, M} and a = {1, 5}.
See the Introduction to AC Sources section at the beginning of this chapter for additional details.
These settings are critical for all features that have settings dependent on current measurements. When the relay is
5 ordered, the CT module must be specified to include a standard or sensitive ground input. As the phase CTs are connected
in wye (star), the calculated phasor sum of the three phase currents (IA + IB + IC = neutral current = 3Io) is used as the
input for the neutral overcurrent elements. In addition, a zero-sequence (core balance) CT which senses current in all of the
circuit primary conductors, or a CT in a neutral grounding conductor may also be used. For this configuration, the ground
CT primary rating must be entered. To detect low level ground fault currents, the sensitive ground input may be used. In this
case, the sensitive ground CT primary rating must be entered. Refer to chapter 3 for more details on CT connections.
Enter the rated CT primary current values. For both 1000:5 and 1000:1 CTs, the entry would be 1000. For correct opera-
tion, the CT secondary rating must match the setting (which must also correspond to the specific CT connections used).
The following example illustrates how multiple CT inputs (current banks) are summed as one source current. Given If the
following current banks:
• F1: CT bank with 500:1 ratio.
• F5: CT bank with 1000: ratio.
• M1: CT bank with 800:1 ratio.
The following rule applies:
SRC 1 = F1 + F5 + M1 (EQ 5.6)

1 pu is the highest primary current. In this case, 1000 is entered and the secondary current from the 500:1 ratio CT will be
adjusted to that created by a 1000:1 CT before summation. If a protection element is set up to act on SRC 1 currents, then
a pickup level of 1 pu will operate on 1000 A primary.
The same rule applies for current sums from CTs with different secondary taps (5 A and 1 A).

5-70 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

b) VOLTAGE BANKS
PATH: SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE BANK F5(M5)

„ VOLTAGE BANK F5 PHASE VT F5 Range: Wye, Delta


„ CONNECTION: Wye
PHASE VT F5 Range: 25.0 to 240.0 V in steps of 0.1
MESSAGE
SECONDARY: 66.4 V
PHASE VT F5 Range: 1.00 to 24000.00 in steps of 0.01
MESSAGE
RATIO: 1.00 :1
AUXILIARY VT F5 Range: Vn, Vag, Vbg, Vcg, Vab, Vbc, Vca
MESSAGE
CONNECTION: Vag
AUXILIARY VT F5 Range: 25.0 to 240.0 V in steps of 0.1
MESSAGE
SECONDARY: 66.4 V
AUXILIARY VT F5 Range: 1.00 to 24000.00 in steps of 0.01
MESSAGE
RATIO: 1.00 :1

Because energy parameters are accumulated, these values should be recorded and then reset immediately
prior to changing VT characteristics.
CAUTION

Two banks of phase/auxiliary VTs can be set, where voltage banks are denoted in the following format (X represents the
module slot position letter):
Xa, where X = {F, M} and a = {5}.
See the Introduction to AC sources section at the beginning of this chapter for additional details.
5
With VTs installed, the relay can perform voltage measurements as well as power calculations. Enter the PHASE VT F5 CON-
NECTION made to the system as “Wye” or “Delta”. An open-delta source VT connection would be entered as “Delta”.

The nominal PHASE VT F5 SECONDARY voltage setting is the voltage across the relay input terminals when nominal
voltage is applied to the VT primary.
NOTE
For example, on a system with a 13.8 kV nominal primary voltage and with a 14400:120 volt VT in a delta connec-
tion, the secondary voltage would be 115; that is, (13800 / 14400) × 120. For a wye connection, the voltage value
entered must be the phase to neutral voltage which would be 115 / 3 = 66.4.
On a 14.4 kV system with a delta connection and a VT primary to secondary turns ratio of 14400:120, the voltage
value entered would be 120; that is, 14400 / 120.

5.4.2 POWER SYSTEM

PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ POWER SYSTEM

„ POWER SYSTEM NOMINAL FREQUENCY: Range: 25 to 60 Hz in steps of 1


„ 60 Hz
PHASE ROTATION: Range: ABC, ACB
MESSAGE
ABC
REVERSE PH ROTATION: Range: FlexLogic™ operand
MESSAGE
Off
FREQUENCY AND PHASE Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
REFERENCE: SRC 1
FREQUENCY TRACKING: Range: Disabled, Enabled
MESSAGE
Enabled

GE Multilin G60 Generator Protection System 5-71


5.4 SYSTEM SETUP 5 SETTINGS

The power system NOMINAL FREQUENCY value is used as a default to set the digital sampling rate if the system frequency
cannot be measured from available signals. This may happen if the signals are not present or are heavily distorted. Before
reverting to the nominal frequency, the frequency tracking algorithm holds the last valid frequency measurement for a safe
period of time while waiting for the signals to reappear or for the distortions to decay.
The phase sequence of the power system is required to properly calculate sequence components and power parameters.
The PHASE ROTATION setting matches the power system phase sequence. Note that this setting informs the relay of the
actual system phase sequence, either ABC or ACB. CT and VT inputs on the relay, labeled as A, B, and C, must be con-
nected to system phases A, B, and C for correct operation.
The REVERSE PH ROTATION setting allows the user to dynamically change the phase rotation used for phasor calculations.
This allows the G60 to follow the current phase rotation of the protected generator. For example, if the PHASE ROTATION set-
ting is “ABC” but the condition defined for opposite phase rotation is true, then the phase rotation used for phasor calcula-
tion will switch to “ACB”. This feature is only intended for use in special applications, such as pumped storage schemes
The FREQUENCY AND PHASE REFERENCE setting determines which signal source is used (and hence which AC signal) for
phase angle reference. The AC signal used is prioritized based on the AC inputs that are configured for the signal source:
phase voltages takes precedence, followed by auxiliary voltage, then phase currents, and finally ground current.
For three phase selection, phase A is used for angle referencing ( V ANGLE REF = V A ), while Clarke transformation of the
phase signals is used for frequency metering and tracking ( V FREQUENCY = ( 2V A – V B – V C ) ⁄ 3 ) for better performance dur-
ing fault, open pole, and VT and CT fail conditions.
The phase reference and frequency tracking AC signals are selected based upon the Source configuration, regardless of
whether or not a particular signal is actually applied to the relay.
Phase angle of the reference signal will always display zero degrees and all other phase angles will be relative to this sig-
nal. If the pre-selected reference signal is not measurable at a given time, the phase angles are not referenced.
The phase angle referencing is done via a phase locked loop, which can synchronize independent UR-series relays if they
5 have the same AC signal reference. These results in very precise correlation of time tagging in the event recorder between
different UR-series relays provided the relays have an IRIG-B connection.
FREQUENCY TRACKING should only be set to “Disabled” in very unusual circumstances; consult the factory for spe-
cial variable-frequency applications.
NOTE

The frequency tracking feature will function only when the G60 is in the “Programmed” mode. If the G60 is “Not Pro-
grammed”, then metering values will be available but may exhibit significant errors.
NOTE

5.4.3 SIGNAL SOURCES

PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES Ö SOURCE 1(4)

„ SOURCE 1 SOURCE 1 NAME: Range: up to six alphanumeric characters


„ SRC 1
SOURCE 1 PHASE CT: Range: None, F1, F5, F1+F5,... up to a combination of
MESSAGE any 6 CTs. Only Phase CT inputs are displayed.
None
SOURCE 1 GROUND CT: Range: None, F1, F5, F1+F5,... up to a combination of
MESSAGE any 6 CTs. Only Ground CT inputs are displayed.
None
SOURCE 1 PHASE VT: Range: None, F5, M5
MESSAGE Only phase voltage inputs will be displayed.
None
SOURCE 1 AUX VT: Range: None, F5, M5
MESSAGE Only auxiliary voltage inputs will be displayed.
None

Identical menus are available for each source. The "SRC 1" text can be replaced by with a user-defined name appropriate
for the associated source.

5-72 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

The first letter in the source identifier represents the module slot position. The number directly following this letter repre-
sents either the first bank of four channels (1, 2, 3, 4) called “1” or the second bank of four channels (5, 6, 7, 8) called “5” in
a particular CT/VT module. Refer to the Introduction to AC sources section at the beginning of this chapter for additional
details on this concept.
It is possible to select the sum of all CT combinations. The first channel displayed is the CT to which all others will be
referred. For example, the selection “F1+F5” indicates the sum of each phase from channels “F1” and “F5”, scaled to
whichever CT has the higher ratio. Selecting “None” hides the associated actual values.
The approach used to configure the AC sources consists of several steps; first step is to specify the information about each
CT and VT input. For CT inputs, this is the nominal primary and secondary current. For VTs, this is the connection type,
ratio and nominal secondary voltage. Once the inputs have been specified, the configuration for each source is entered,
including specifying which CTs will be summed together.
User selection of AC parameters for comparator elements:
CT/VT modules automatically calculate all current and voltage parameters from the available inputs. Users must select the
specific input parameters to be measured by every element in the relevant settings menu. The internal design of the ele-
ment specifies which type of parameter to use and provides a setting for source selection. In elements where the parameter
may be either fundamental or RMS magnitude, such as phase time overcurrent, two settings are provided. One setting
specifies the source, the second setting selects between fundamental phasor and RMS.
AC input actual values:
The calculated parameters associated with the configured voltage and current inputs are displayed in the current and volt-
age sections of actual values. Only the phasor quantities associated with the actual AC physical input channels will be dis-
played here. All parameters contained within a configured source are displayed in the sources section of the actual values.
DISTURBANCE DETECTORS (INTERNAL):
The disturbance detector (ANSI 50DD) element is a sensitive current disturbance detector that detects any disturbance on
the protected system. The 50DD function is intended for use in conjunction with measuring elements, blocking of current
5
based elements (to prevent maloperation as a result of the wrong settings), and starting oscillography data capture. A dis-
turbance detector is provided for each source.
The 50DD function responds to the changes in magnitude of the sequence currents. The disturbance detector scheme
logic is as follows:

SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 1 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 1 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old

SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 2 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 2 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old

SETTING
ACTUAL
PRODUCT SETUP/DISPLAY
SOURCE 6 PROPERTIES/CURRENT
CURRENT PHASOR CUT-OFF LEVEL
I_1 I_1 - I_1’ >2*CUT-OFF FLEXLOGIC OPERAND
I_2 I_2 - I_2’ >2*CUT-OFF OR SRC 6 50DD OP
I_0 I_0 - I_0’ >2*CUT-OFF
Where I’ is 2 cycles old 827092A3.CDR

Figure 5–18: DISTURBANCE DETECTOR LOGIC DIAGRAM


The disturbance detector responds to the change in currents of twice the current cut-off level. The default cut-off threshold
is 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting (PROD-
UCT SETUP ÖØ DISPLAY PROPERTIES ÖØ CURRENT CUT-OFF LEVEL) controls the sensitivity of the disturbance detector
accordingly.

GE Multilin G60 Generator Protection System 5-73


5.4 SYSTEM SETUP 5 SETTINGS

EXAMPLE USE OF SOURCES:


An example of the use of sources is shown in the diagram below. A relay could have the following hardware configuration:
INCREASING SLOT POSITION LETTER -->
CT/VT MODULE 1 CT/VT MODULE 2 CT/VT MODULE 3
CTs VTs not applicable

This configuration could be used on a two-winding transformer, with one winding connected into a breaker-and-a-half sys-
tem. The following figure shows the arrangement of sources used to provide the functions required in this application, and
the CT/VT inputs that are used to provide the data.

F1 DSP Bank

F5
Source 1 Source 2
Amps Amps

Source 3
51BF-1 51BF-2
U1 Volts Amps

A W Var 87T

A W Var 51P

Volts Amps

5 M1
M1

Source 4

UR Relay
M5

Figure 5–19: EXAMPLE USE OF SOURCES

5-74 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

5.4.4 BREAKERS

PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ BREAKERS Ö BREAKER 1

„ BREAKER 1 BREAKER 1 Range: Disabled, Enabled


„ FUNCTION: Disabled
BREAKER1 PUSH BUTTON Range: Disabled, Enabled
MESSAGE
CONTROL: Disabled
BREAKER 1 NAME: Range: up to 6 alphanumeric characters
MESSAGE
Bkr 1
BREAKER 1 MODE: Range: 3-Pole, 1-Pole
MESSAGE
3-Pole
BREAKER 1 OPEN: Range: FlexLogic™ operand
MESSAGE
Off
BREAKER 1 BLK OPEN: Range: FlexLogic™ operand
MESSAGE
Off
BREAKER 1 CLOSE: Range: FlexLogic™ operand
MESSAGE
Off
BREAKER 1 BLK CLOSE: Range: FlexLogic™ operand
MESSAGE
Off
BREAKER 1 ΦA/3P CLSD: Range: FlexLogic™ operand
MESSAGE
Off 5
BREAKER 1 ΦA/3P OPND: Range: FlexLogic™ operand
MESSAGE
Off
BREAKER 1 ΦB CLOSED: Range: FlexLogic™ operand
MESSAGE
Off
BREAKER 1 ΦB OPENED: Range: FlexLogic™ operand
MESSAGE
Off
BREAKER 1 ΦC CLOSED: Range: FlexLogic™ operand
MESSAGE
Off
BREAKER 1 ΦC OPENED: Range: FlexLogic™ operand
MESSAGE
Off
BREAKER 1 Toperate: Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
0.070 s
BREAKER 1 EXT ALARM: Range: FlexLogic™ operand
MESSAGE
Off
BREAKER 1 ALARM Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.000 s
MANUAL CLOSE RECAL1 Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
TIME: 0.000 s
BREAKER 1 OUT OF SV: Range: FlexLogic™ operand
MESSAGE
Off
BREAKER 1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

GE Multilin G60 Generator Protection System 5-75


5.4 SYSTEM SETUP 5 SETTINGS

A description of the operation of the breaker control and status monitoring features is provided in chapter 4. Only informa-
tion concerning programming of the associated settings is covered here. These features are provided for two or more
breakers; a user may use only those portions of the design relevant to a single breaker, which must be breaker 1.
The number of breaker control elements is dependent on the number of CT/VT modules specified with the G60. The follow-
ing settings are available for each breaker control element.
• BREAKER 1 FUNCTION: This setting enables and disables the operation of the breaker control feature.
• BREAKER1 PUSH BUTTON CONTROL: Set to “Enable” to allow faceplate push button operations.
• BREAKER 1 NAME: Assign a user-defined name (up to six characters) to the breaker. This name will be used in flash
messages related to breaker 1.
• BREAKER 1 MODE: This setting selects “3-Pole” mode, where all breaker poles are operated simultaneously, or “1-
Pole” mode where all breaker poles are operated either independently or simultaneously.
• BREAKER 1 OPEN: This setting selects an operand that creates a programmable signal to operate an output relay to
open breaker 1.
• BREAKER 1 BLK OPEN: This setting selects an operand that prevents opening of the breaker. This setting can be
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• BREAKER 1 CLOSE: This setting selects an operand that creates a programmable signal to operate an output relay
to close breaker 1.
• BREAKER 1 BLK CLOSE: This setting selects an operand that prevents closing of the breaker. This setting can be
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• BREAKER 1 ΦA/3P CLOSED: This setting selects an operand, usually a contact input connected to a breaker auxil-
iary position tracking mechanism. This input should be a normally-open 52/a status input to create a logic 1 when the
5 breaker is closed. If the BREAKER 1 MODE setting is selected as “3-Pole”, this setting selects a single input as the oper-
and used to track the breaker open or closed position. If the mode is selected as “1-Pole”, the input mentioned above
is used to track phase A and the BREAKER 1 ΦB and BREAKER 1 ΦC settings select operands to track phases B and C,
respectively.
• BREAKER 1 ΦA/3P OPND: This setting selects an operand, usually a contact input, that should be a normally-closed
52/b status input to create a logic 1 when the breaker is open. If a separate 52/b contact input is not available, then the
inverted BREAKER 1 CLOSED status signal can be used.
• BREAKER 1 ΦB CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase B closed position as above for phase A.
• BREAKER 1 ΦB OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase B opened position as above for phase A.
• BREAKER 1 ΦC CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase C closed position as above for phase A.
• BREAKER 1 ΦC OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected
as single-pole, this input is used to track the breaker phase C opened position as above for phase A.
• BREAKER 1 Toperate: This setting specifies the required interval to overcome transient disagreement between the
52/a and 52/b auxiliary contacts during breaker operation. If transient disagreement still exists after this time has
expired, the BREAKER 1 BAD STATUS FlexLogic™ operand is asserted from alarm or blocking purposes.
• BREAKER 1 EXT ALARM: This setting selects an operand, usually an external contact input, connected to a breaker
alarm reporting contact.
• BREAKER 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among
the three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous oper-
ation of the poles.
• MANUAL CLOSE RECAL1 TIME: This setting specifies the interval required to maintain setting changes in effect after
an operator has initiated a manual close command to operate a circuit breaker.
• BREAKER 1 OUT OF SV: Selects an operand indicating that breaker 1 is out-of-service.

5-76 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

SETTING
BREAKER 1 FUNCTION
FLEXLOGIC OPERANDS
= Enabled
AND BREAKER 1 OFF CMD
= Disabled
BREAKER 1 TRIP A
BREAKER 1 TRIP B
AND
SETTING BREAKER 1 TRIP C
BREAKER 1 BLOCK OPEN
Off = 0 AND

D60, L60, and L90 devices only from trip output


FLEXLOGIC OPERANDS AND

TRIP PHASE A
TRIP PHASE B
TRIP PHASE C
TRIP 3-POLE

SETTING
BREAKER 1 OPEN
Off = 0
OR

61850 Select & Open


To breaker control
BKR ENABLED logic sheet 2,
USER 3 OFF/ON 842025A1
To open BRK1-(Name)
AND

SETTING
BREAKER 1 PUSHBUTTON
CONTROL
= Enabled

AND
USER 2 OFF/ON
To open BRK1-(Name)

OR
SETTING AND
BREAKER 1 CLOSE
Off = 0
OR
5
FLEXLOGIC OPERAND
AND BREAKER 1 MNL CLS
61850 Select & Close SETTING
MANUAL CLOSE RECAL1 TIME AND

C60, D60, L60, and L90 relays from recloser


FLEXLOGIC OPERAND
0
AR CLOSE BKR 1

FLEXLOGIC OPERAND
SETTING
OR AND BREAKER 1 ON CMD
BREAKER 1 BLOCK CLOSE
Off = 0 827061AS.CDR

Figure 5–20: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2)


IEC 61850 functionality is permitted when the G60 is in “Programmed” mode and not in the local control mode.

NOTE

GE Multilin G60 Generator Protection System 5-77


5.4 SYSTEM SETUP 5 SETTINGS

from breaker
controlsheetlogic1, BKR ENABLED
827061AS FLEXLOGIC OPERAND BREAKER 1
AND AND BREAKER 1 CLOSED CLOSED
OR (DEFAULT)

AND OR FLEXLOGIC OPERANDS BREAKER 1


AND BREAKER 1 OPEN OPEN
BREAKER 1 DISCREP (DEFAULT)
SETTING
BREAKER 1 ALARM DELAY AND
SETTING
AND
BREAKER 1 MODE AND
= 3-Pole 0
= 1-Pole
OR FLEXLOGIC OPERAND BREAKER 1
AND
SETTING AND BREAKER 1 TROUBLE TROUBLE
(DEFAULT)
BREAKER 1 EXT ALARM Note: the BREAKER 1 TROUBLE LED
= Off can be latched using FlexLogic™

FLEXLOGIC OPERAND
SETTING SETTING OR BREAKER 1 BAD STATUS
AND
BREAKER 1 ΦA/3P CLSD BREAKER 1 Toperate
= Off FLEXLOGIC OPERANDS
AND AND
BREAKER 1 ΦA BAD ST
0 OR
BREAKER 1 ΦA CLSD
SETTING
AND BREAKER 1 ΦA OPEN
BREAKER 1 ΦA/3P OPND
AND BREAKER 1 ΦA INTERM
= Off
AND

AND

AND

SETTING SETTING
AND
BREAKER 1 ΦB CLSD BREAKER 1 Toperate
FLEXLOGIC OPERANDS

5 = Off
AND
0 OR
AND BREAKER 1 ΦB BAD ST
BREAKER 1 ΦB CLSD
SETTING BREAKER 1 ΦB OPEN
AND
BREAKER 1 ΦB OPND BREAKER 1 ΦB INTERM
AND
= Off

AND
AND

AND

SETTING SETTING
AND
BREAKER 1 ΦC CLSD BREAKER 1 Toperate
FLEXLOGIC OPERANDS
= Off AND
AND BREAKER 1 ΦC BAD ST
0 OR BREAKER 1 ΦC CLSD
SETTING BREAKER 1 ΦC OPEN
AND
BREAKER 1 ΦC OPND BREAKER 1 ΦC INTERM
AND
= Off

AND
AND

AND

AND FLEXLOGIC OPERANDS


AND BREAKER 1 ANY P OPEN
BREAKER 1 1P OPEN
BREAKER 1 OOS

XOR AND

SETTING
BREAKER 1 OUT OF SV AND
= Off 842025A2.CDR

Figure 5–21: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 2 of 2)

5-78 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

5.4.5 DISCONNECT SWITCHES

PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ SWITCHES Ö SWITCH 1

„ SWITCH 1 SWITCH 1 Range: Disabled, Enabled


„ FUNCTION: Disabled
SWITCH 1 NAME: Range: up to 6 alphanumeric characters
MESSAGE
SW 1
SWITCH 1 MODE: Range: 3-Pole, 1-Pole
MESSAGE
3-Pole
SWITCH 1 OPEN: Range: FlexLogic™ operand
MESSAGE
Off
SWITCH 1 BLK OPEN: Range: FlexLogic™ operand
MESSAGE
Off
SWITCH 1 CLOSE: Range: FlexLogic™ operand
MESSAGE
Off
SWITCH 1 BLK CLOSE: Range: FlexLogic™ operand
MESSAGE
Off
SWTCH 1 ΦA/3P CLSD: Range: FlexLogic™ operand
MESSAGE
Off
SWTCH 1 ΦA/3P OPND: Range: FlexLogic™ operand
MESSAGE
Off 5
SWITCH 1 ΦB CLOSED: Range: FlexLogic™ operand
MESSAGE
Off
SWITCH 1 ΦB OPENED: Range: FlexLogic™ operand
MESSAGE
Off
SWITCH 1 ΦC CLOSED: Range: FlexLogic™ operand
MESSAGE
Off
SWITCH 1 ΦC OPENED: Range: FlexLogic™ operand
MESSAGE
Off
SWITCH 1 Toperate: Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
0.070 s
SWITCH 1 ALARM Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.000 s
SWITCH 1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

The disconnect switch element contains the auxiliary logic for status and serves as the interface for opening and closing of
disconnect switches from SCADA or through the front panel interface. The disconnect switch element can be used to cre-
ate an interlocking functionality. For greater security in determination of the switch pole position, both the 52/a and 52/b
auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches
depends on the number of the CT/VT modules ordered with the G60.
• SWITCH 1 FUNCTION: This setting enables and disables the operation of the disconnect switch element.
• SWITCH 1 NAME: Assign a user-defined name (up to six characters) to the disconnect switch. This name will be used
in flash messages related to disconnect switch 1.
• SWITCH 1 MODE: This setting selects “3-Pole” mode, where all disconnect switch poles are operated simultaneously,
or “1-Pole” mode where all disconnect switch poles are operated either independently or simultaneously.

GE Multilin G60 Generator Protection System 5-79


5.4 SYSTEM SETUP 5 SETTINGS

• SWITCH 1 OPEN: This setting selects an operand that creates a programmable signal to operate an output relay to
open disconnect switch 1.
• SWITCH 1 BLK OPEN: This setting selects an operand that prevents opening of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• SWITCH 1 CLOSE: This setting selects an operand that creates a programmable signal to operate an output relay to
close disconnect switch 1.
• SWITCH 1 BLK CLOSE: This setting selects an operand that prevents closing of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
• SWTCH 1 ΦA/3P CLSD: This setting selects an operand, usually a contact input connected to a disconnect switch
auxiliary position tracking mechanism. This input should be a normally-open 52/a status input to create a logic 1 when
the disconnect switch is closed. If the SWITCH 1 MODE setting is selected as “3-Pole”, this setting selects a single input
as the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole”, the
input mentioned above is used to track phase A and the SWITCH 1 ΦB and SWITCH 1 ΦC settings select operands to
track phases B and C, respectively.
• SWITCH 1 ΦA/3P OPND: This setting selects an operand, usually a contact input, that should be a normally-closed
52/b status input to create a logic 1 when the disconnect switch is open. If a separate 52/b contact input is not avail-
able, then the inverted SWITCH 1 CLOSED status signal can be used.
• SWITCH 1 ΦB CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B closed position as above for phase A.
• SWITCH 1 ΦB OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B opened position as above for phase A.
• SWITCH 1 ΦC CLOSED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
5 single-pole, this input is used to track the disconnect switch phase C closed position as above for phase A.
• SWITCH 1 ΦC OPENED: If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C opened position as above for phase A.
• SWITCH 1 Toperate: This setting specifies the required interval to overcome transient disagreement between the 52/a
and 52/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the SWITCH 1 BAD STATUS FlexLogic™ operand is asserted from alarm or blocking purposes.
• SWITCH 1 ALARM DELAY: This setting specifies the delay interval during which a disagreement of status among the
three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation
of the poles.
IEC 61850 functionality is permitted when the G60 is in “Programmed” mode and not in the local control mode.

NOTE

5-80 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

SETTINGS
SWITCH 1 FUNCTION
= Disabled
= Enabled
SWITCH 1 OPEN FLEXLOGIC OPERAND
= Off SWITCH 1 OFF CMD
OR AND
SETTING 61850 Select & Open
SWITCH 1 BLK OPEN
= Off

SETTING
SWITCH 1 CLOSE
= Off FLEXLOGIC OPERAND
OR AND SWITCH 1 ON CMD
SETTING 61850 Select & Close
SWITCH 1 BLK CLOSE
= Off
FLEXLOGIC OPERAND
AND AND SWITCH 1 CLOSED
OR

AND OR FLEXLOGIC OPERANDS


AND SWITCH 1 OPEN
SWITCH 1 DISCREP
SETTING
SWITCH 1 ALARM DELAY AND
SETTING
AND
SWITCH 1 MODE AND
= 3-Pole 0 FLEXLOGIC OPERAND
OR
= 1-Pole AND SWITCH 1 TROUBLE
AND

FLEXLOGIC OPERAND
SETTING SETTING OR SWITCH 1 BAD STATUS
AND
SWITCH 1 ΦA/3P CLSD SWITCH 1 Toperate
= Off FLEXLOGIC OPERANDS

SETTING
AND
0 OR
AND
SWITCH 1 ΦA BAD ST
SWITCH 1 ΦA CLSD
5
AND SWITCH 1 ΦA OPEN
SWITCH 1 ΦA/3P OPND
AND SWITCH 1 ΦA INTERM
= Off

AND
AND

AND

SETTING SETTING
AND
SWITCH 1 ΦB CLSD SWITCH 1 Toperate
FLEXLOGIC OPERANDS
= Off AND
AND SWITCH 1 ΦB BAD ST
0 OR SWITCH 1 ΦB CLSD
SETTING SWITCH 1 ΦB OPEN
AND
SWITCH 1 ΦB OPND SWITCH 1 ΦB INTERM
AND
= Off

AND
AND

AND

SETTING SETTING
AND
SWITCH 1 ΦC CLSD SWITCH 1 Toperate
FLEXLOGIC OPERANDS
= Off AND
AND SWITCH 1 ΦC BAD ST
0 OR SWITCH 1 ΦC CLSD
SETTING SWITCH 1 ΦC OPEN
AND
SWITCH 1 ΦC OPND SWITCH 1 ΦC INTERM
AND
= Off

AND
AND

AND

842026A4.CDR

Figure 5–22: DISCONNECT SWITCH SCHEME LOGIC

GE Multilin G60 Generator Protection System 5-81


5.4 SYSTEM SETUP 5 SETTINGS

5.4.6 FLEXCURVES

a) SETTINGS
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ FLEXCURVES Ö FLEXCURVE A(D)

„ FLEXCURVE A FLEXCURVE A TIME AT Range: 0 to 65535 ms in steps of 1


„ 0.00 xPKP: 0 ms

FlexCurves™ A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter a
custom FlexCurve™, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using the
MESSAGE UP/DOWN keys) for the desired protection curve (A, B, C, or D).

Table 5–6: FLEXCURVE™ TABLE


RESET TIME RESET TIME OPERATE TIME OPERATE TIME OPERATE TIME OPERATE TIME
MS MS MS MS MS MS
0.00 0.68 1.03 2.9 4.9 10.5

0.05 0.70 1.05 3.0 5.0 11.0

0.10 0.72 1.1 3.1 5.1 11.5

0.15 0.74 1.2 3.2 5.2 12.0

0.20 0.76 1.3 3.3 5.3 12.5

5 0.25 0.78 1.4 3.4 5.4 13.0

0.30 0.80 1.5 3.5 5.5 13.5

0.35 0.82 1.6 3.6 5.6 14.0

0.40 0.84 1.7 3.7 5.7 14.5

0.45 0.86 1.8 3.8 5.8 15.0

0.48 0.88 1.9 3.9 5.9 15.5

0.50 0.90 2.0 4.0 6.0 16.0

0.52 0.91 2.1 4.1 6.5 16.5

0.54 0.92 2.2 4.2 7.0 17.0

0.56 0.93 2.3 4.3 7.5 17.5

0.58 0.94 2.4 4.4 8.0 18.0

0.60 0.95 2.5 4.5 8.5 18.5

0.62 0.96 2.6 4.6 9.0 19.0

0.64 0.97 2.7 4.7 9.5 19.5

0.66 0.98 2.8 4.8 10.0 20.0

The relay using a given FlexCurve™ applies linear approximation for times between the user-entered
points. Special care must be applied when setting the two points that are close to the multiple of pickup of
NOTE
1; that is, 0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the lin-
ear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu.

5-82 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

b) FLEXCURVE™ CONFIGURATION WITH ENERVISTA UR SETUP


The EnerVista UR Setup software allows for easy configuration and management of FlexCurves™ and their associated
data points. Prospective FlexCurves™ can be configured from a selection of standard curves to provide the best approxi-
mate fit, then specific data points can be edited afterwards. Alternately, curve data can be imported from a specified file
(.csv format) by selecting the Import Data From EnerVista UR Setup setting.
Curves and data can be exported, viewed, and cleared by clicking the appropriate buttons. FlexCurves™ are customized
by editing the operating time (ms) values at pre-defined per-unit current multiples. Note that the pickup multiples start at
zero (implying the "reset time"), operating time below pickup, and operating time above pickup.

c) RECLOSER CURVE EDITING


Recloser curve selection is special in that recloser curves can be shaped into a composite curve with a minimum response
time and a fixed time above a specified pickup multiples. There are 41 recloser curve types supported. These definite oper-
ating times are useful to coordinate operating times, typically at higher currents and where upstream and downstream pro-
tective devices have different operating characteristics. The recloser curve configuration window shown below appears
when the Initialize From EnerVista UR Setup setting is set to “Recloser Curve” and the Initialize FlexCurve button is
clicked.

Multiplier: Scales (multiplies) the curve operating times

Addr: Adds the time specified in this field (in ms) to each
curve operating time value.

Minimum Response Time (MRT): If enabled, the MRT setting


defines the shortest operating time even if the curve suggests
a shorter time at higher current multiples. A composite operating
characteristic is effectively defined. For current multiples lower
5
than the intersection point, the curve dictates the operating time;
otherwise, the MRT does. An information message appears
when attempting to apply an MRT shorter than the minimum
curve time.

High Current Time: Allows the user to set a pickup multiple


from which point onwards the operating time is fixed. This is
normally only required at higher current levels. The HCT Ratio
defines the high current pickup multiple; the HCT defines the
operating time.
842721A1.CDR

Figure 5–23: RECLOSER CURVE INITIALIZATION


The multiplier and adder settings only affect the curve portion of the characteristic and not the MRT and HCT set-
tings. The HCT settings override the MRT settings for multiples of pickup greater than the HCT ratio.
NOTE

GE Multilin G60 Generator Protection System 5-83


5.4 SYSTEM SETUP 5 SETTINGS

d) EXAMPLE
A composite curve can be created from the GE_111 standard with MRT = 200 ms and HCT initially disabled and then
enabled at eight (8) times pickup with an operating time of 30 ms. At approximately four (4) times pickup, the curve operat-
ing time is equal to the MRT and from then onwards the operating time remains at 200 ms (see below).

842719A1.CDR

Figure 5–24: COMPOSITE RECLOSER CURVE WITH HCT DISABLED


With the HCT feature enabled, the operating time reduces to 30 ms for pickup multiples exceeding 8 times pickup.

842720A1.CDR

Figure 5–25: COMPOSITE RECLOSER CURVE WITH HCT ENABLED


Configuring a composite curve with an increase in operating time at increased pickup multiples is not allowed. If this
is attempted, the EnerVista UR Setup software generates an error message and discards the proposed changes.
NOTE

e) STANDARD RECLOSER CURVES


The standard recloser curves available for the G60 are displayed in the following graphs.

5-84 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

1 GE106

0.5

0.2
TIME (sec)

GE103

GE104 GE105
0.1

0.05
GE101 GE102

0.02

0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842723A1.CDR
5
Figure 5–26: RECLOSER CURVES GE101 TO GE106

50

20 GE142

10

5
GE138
TIME (sec)

1 GE120
GE113
0.5

0.2

0.1

0.05
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842725A1.CDR

Figure 5–27: RECLOSER CURVES GE113, GE120, GE138 AND GE142

GE Multilin G60 Generator Protection System 5-85


5.4 SYSTEM SETUP 5 SETTINGS

50

20

10
GE201
TIME (sec)

GE151
2

GE134 GE140
1
GE137

0.5

1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20


CURRENT (multiple of pickup)
5 Figure 5–28: RECLOSER CURVES GE134, GE137, GE140, GE151 AND GE201
842730A1.CDR

50

GE152

20
TIME (sec)

GE141
10

GE131
5

GE200

2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842728A1.CDR

Figure 5–29: RECLOSER CURVES GE131, GE141, GE152, AND GE200

5-86 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

50

20
GE164
10

2
TIME (sec)

GE162
1

0.5
GE133
0.2
GE165
0.1

0.05
GE161
0.02 GE163

0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842729A1.CDR

Figure 5–30: RECLOSER CURVES GE133, GE161, GE162, GE163, GE164 AND GE165 5
20
GE132
10

1
TIME (sec)

0.5 GE139

0.2
GE136
0.1
GE116
0.05
GE118 GE117

0.02

0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842726A1.CDR

Figure 5–31: RECLOSER CURVES GE116, GE117, GE118, GE132, GE136, AND GE139

GE Multilin G60 Generator Protection System 5-87


5.4 SYSTEM SETUP 5 SETTINGS

20

10

5
GE122
2

1
TIME (sec)

0.5
GE114
0.2
GE111
GE121
0.1

0.05 GE115 GE112


GE107

0.02

0.01
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842724A1.CDR

5 Figure 5–32: RECLOSER CURVES GE107, GE111, GE112, GE114, GE115, GE121, AND GE122

50

20
GE202
10
TIME (sec)

GE135
2 GE119

0.5

0.2
1 1.2 1.5 2 2.5 3 4 5 6 7 8 9 10 12 15 20
CURRENT (multiple of pickup) 842727A1.CDR

Figure 5–33: RECLOSER CURVES GE119, GE135, AND GE202

5-88 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

5.4.7 PHASOR MEASUREMENT UNIT

a) MAIN MENU
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT UNIT

„ PHASOR MEASUREMENT „ PHASOR MEASUREMENT


See below.
„ UNIT „ UNIT 1
„ REPORTING OVER
MESSAGE See page 5-104.
„ NETWORK

The G60 Generator Protection System is provided with an optional phasor measurement unit feature. This
feature is specified as a software option at the time of ordering. The number of phasor measurement units
available is also dependent on this option. Refer to the Ordering section of chapter 2 for additional details.

The PHASOR MEASUREMENT UNIT menu allows specifying basic parameters of the measurements process such as signal
source, ID and station name, calibration data, triggering, recording, and content for transmission on each of the supported
ports. The reporting ports menus allow specifying the content and rate of reporting on each of the supported ports.
Precise IRIG-B input is vital for correct synchrophasor measurement and reporting. A DC level shift IRIG-B receiver
must be used for the phasor measurement unit to output proper synchrophasor values.
NOTE

The PMU settings are organized in five logical groups as follows.


PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT UNIT ÖØ PHASOR MEASUREMENT UNIT 1

„ PHASOR MEASUREMENT „ PMU 1 BASIC


See page 5-90.
5
„ UNIT 1 „ CONFIGURATION
„ PMU 1
MESSAGE See page 5-91.
„ CALIBRATION
„ PMU 1
MESSAGE See page 5-92.
„ COMMUNICATION
„ PMU 1
MESSAGE See page 5-94.
„ TRIGGERING
„ PMU 1
MESSAGE See page 5-101.
„ RECORDING

GE Multilin G60 Generator Protection System 5-89


5.4 SYSTEM SETUP 5 SETTINGS

b) BASIC CONFIGURATION
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1 Ö PMU 1 BASIC CONFIGURATION 1

„ PMU 1 BASIC PMU 1 Range: Enabled, Disabled


„ CONFIGURATION FUNCTION: Disabled
PMU 1 IDCODE: 1 Range: 1 to 65534 in steps of 1
MESSAGE

PMU 1 STN: Range: 16 alphanumeric characters


MESSAGE
GE-UR-PMU
PMU 1 SIGNAL SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SRC 1
PMU 1 POST-FILTER: Range: None, Symm-3-point, Symm-5-point,
MESSAGE Symm-7-point, Class M, Class P
Symm-3-point

This section contains basic phasor measurement unit (PMU) data, such as functions, source settings, and names.
• PMU 1 FUNCTION: This setting enables the PMU 1 functionality. Any associated functions (such as the recorder or
triggering comparators) will not function if this setting is “Disabled”. Use the command frame to force the communica-
tion portion of the feature to start/stop transmission of data. When the transmission is turned off, the PMU is fully oper-
ational in terms of calculating and recording the phasors.
• PMU 1 IDCODE: This setting assigns a numerical ID to the PMU. It corresponds to the IDCODE field of the data, con-
figuration, header, and command frames of the C37.118 protocol. The PMU uses this value when sending data, config-
uration, and header frames and responds to this value when receiving the command frame.

5 • PMU 1 STN: This setting assigns an alphanumeric ID to the PMU station. It corresponds to the STN field of the config-
uration frame of the C37.118 protocol. This value is a 16-character ASCII string as per the C37.118 standard.
• PMU 1 SIGNAL SOURCE: This setting specifies one of the available G60 signal sources for processing in the PMU.
Note that any combination of voltages and currents can be configured as a source. The current channels could be con-
figured as sums of physically connected currents. This facilitates PMU applications in breaker-and-a-half, ring-bus, and
similar arrangements. The PMU feature calculates voltage phasors for actual voltage (A, B, C, and auxiliary) and cur-
rent (A, B, C, and ground) channels of the source, as well as symmetrical components (0, 1, and 2) of both voltages
and currents. When configuring communication and recording features of the PMU, the user could select – from the
above superset – the content to be sent out or recorded.
• PMU 1 POST-FILTER: This setting specifies amount of post-filtering applied to raw synchrophasor measurements.
The raw measurements are produced at the rate of nominal system frequency using one-cycle data windows. This set-
ting is provided to deal with interfering frequencies and to balance speed and accuracy of synchrophasor measure-
ments for different applications. The following filtering choices are available:
Table 5–7: POST-FILTER CHOICES
SELECTION CHARACTERISTIC OF THE FILTER
None No post-filtering
Symm-3-point Symmetrical 3-point filter (1 historical point, 1 present point, 1 future point)
Symm-5-point Symmetrical 5-point filter (2 historical points, 1 present point, 2 future points)
Symm-7-point Symmetrical 7-point filter (3 historical points, 1 present point, 3 future points)
Class M Symmetrical FIR filter on samples
Class P 21-tap symmetrical FIR filter on current input channels

This setting applies to all channels of the PMU. It is effectively for recording and transmission on all ports configured to
use data of this PMU.
Class M filtering functionality is derived from the draft C37.118 specification and may be subject to change
when the standard is published.
NOTE

5-90 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

c) CALIBRATION
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1(4) ÖØ PMU 1 CALIBRATION

„ PMU 1 PMU 1 VA CALIBRATION Range: –5.00 to 5.00° in steps of 0.05


„ CALIBRATION ANGLE: 0.00°
PMU 1 VB CALIBRATION Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
ANGLE: 0.00°
PMU 1 VC CALIBRATION Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
ANGLE: 0.00°
PMU 1 VX CALIBRATION Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
ANGLE: 0.00°
PMU 1 IA CALIBRATION Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
ANGLE: 0.00°
PMU 1 IB CALIBRATION Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
ANGLE: 0.00°
PMU 1 IC CALIBRATION Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
ANGLE: 0.00°
PMU 1 IG CALIBRATION Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
ANGLE: 0.00°
PMU 1 SEQ VOLT SHIFT Range: –180 to 180° in steps of 30
MESSAGE
ANGLE: 0°
PMU 1 SEQ CURR SHIFT Range: –180 to 180° in steps of 30 5
MESSAGE
ANGLE: 0°

This menu contains user angle calibration data for the phasor measurement unit (PMU). This data is combined with the fac-
tory adjustments to shift the phasors for better accuracy.
• PMU 1 VA... IG CALIBRATION ANGLE: These settings recognize applications with protection class voltage and cur-
rent sources, and allow the user to calibrate each channel (four voltages and four currents) individually to offset errors
introduced by VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter
a positive correction of the secondary signal lags the true signal; and negative value if the secondary signal leads the
true signal.
• PMU 1 SEQ VOLT SHIFT ANGLE: This setting allows correcting positive- and negative-sequence voltages for vector
groups of power transformers located between the PMU voltage point, and the reference node. This angle is effectively
added to the positive-sequence voltage angle, and subtracted from the negative-sequence voltage angle. Note that:
1. When this setting is not “0°”, the phase and sequence voltages will not agree. Unlike sequence voltages, the
phase voltages cannot be corrected in a general case, and therefore are reported as measured.
2. When receiving synchrophasor date at multiple locations, with possibly different reference nodes, it may be more
beneficial to allow the central locations to perform the compensation of sequence voltages.
3. This setting applies to PMU data only. The G60 calculates symmetrical voltages independently for protection and
control purposes without applying this correction.
4. When connected to line-to-line voltages, the PMU calculates symmetrical voltages with the reference to the AG
voltage, and not to the physically connected AB voltage (see the Metering Conventions section in Chapter 6).
• PMU 1 SEQ CURR SHIFT ANGLE: This setting allows correcting positive and negative-sequence currents for vector
groups of power transformers located between the PMU current point and the reference node. The setting has the
same meaning for currents as the PMU 1 SEQ VOLT SHIFT ANGLE setting has for voltages. Normally, the two correcting
angles are set identically, except rare applications when the voltage and current measuring points are located at differ-
ent windings of a power transformer.

GE Multilin G60 Generator Protection System 5-91


5.4 SYSTEM SETUP 5 SETTINGS

d) PMU COMMUNICATION
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 COMMUNICATION ÖØ PMU 1 COMM PORT

„ PMU 1 PMU1 COMM PORT: Range: None, Network, GOOSE


„ COMM PORT 1 None
PMU1 PORT PHS-1 Range: available synchrophasor values
MESSAGE
PMU 1 V1
PMU1 PORT PHS-1 Range: 16-character ASCII string
MESSAGE
NM: GE-UR-PMU1-V1

PMU1 PORT PHS-14 Range: available synchrophasor values


MESSAGE
PMU 1 V1
PMU1 PORT PHS-14 Range: 16 alphanumeric characters
MESSAGE
NM: GE-UR-PMU1-V1
PMU1 PORT A-CH-1: Range: available FlexAnalog values
MESSAGE
Off
PMU1 PORT A-CH-1 Range: 16 alphanumeric characters
MESSAGE
NM: AnalogChannel1

PMU1 PORT A-CH-8: Range: available FlexAnalog values


MESSAGE

5 Off
PMU1 PORT A-CH-8 Range: 16 alphanumeric characters
MESSAGE
NM: AnalogChannel8
PMU1 PORT D-CH-1: Range: FlexLogic™ operands
MESSAGE
Off
PMU1 PORT D-CH-1 Range: 16 alphanumeric characters
MESSAGE
NM: DigitalChannel1
PMU1 PORT D-CH-1 Range: On, Off
MESSAGE
NORMAL STATE: Off

PMU1 PORT D-CH-16: Range: FlexLogic™ operands


MESSAGE
Off
PMU1 PORT D-CH-16 Range: 16 alphanumeric characters
MESSAGE
NM: DigitalChannel16
PMU1 PORT D-CH-16 Range: On, Off
MESSAGE
NORMAL STATE: Off

This section configures the phasor measurement unit (PMU) communication functions.
• PMU1 COMM PORT: This setting specifies the communication port for transmission of the PMU data.

5-92 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

• PMU1 PORT PHS-1 to PMU1 PORT PHS-14: These settings specify synchrophasors to be transmitted from the
superset of all synchronized measurements. The available synchrophasor values are tabulated below.
SELECTION MEANING
Va First voltage channel, either Va or Vab
Vb Second voltage channel, either Vb or Vbc
Vc Third voltage channel, either Vc or Vca
Vx Fourth voltage channel
Ia Phase A current, physical channel or summation as per the source settings
Ib Phase B current, physical channel or summation as per the source settings
Ic Phase C current, physical channel or summation as per the source settings
Ig Fourth current channel, physical or summation as per the source settings
V1 Positive-sequence voltage, referenced to Va
V2 Negative-sequence voltage, referenced to Va
V0 Zero-sequence voltage
I1 Positive-sequence current, referenced to Ia
I2 Negative-sequence current, referenced to Ia
I0 Zero-sequence current

These settings allow for optimizing the frame size and maximizing transmission channel usage, depending on a given
application. Select “Off” to suppress transmission of a given value.
• PMU1 PORT PHS-1 NM to PMU1 PORT PHS-14 NM: These settings allow for custom naming of the synchrophasor
channels. Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame. These names
are typically based on station, bus, or breaker names.
5
• PMU1 PORT A-CH-1 to PMU1 PORT A-CH-8: These settings specify any analog data measured by the relay to be
included as a user-selectable analog channel of the data frame. Up to eight analog channels can be configured to send
any FlexAnalog value from the relay. Examples include active and reactive power, per phase or three-phase power,
power factor, temperature via RTD inputs, and THD. The configured analog values are sampled concurrently with the
synchrophasor instant and sent as 32-bit floating point values.
• PMU1 PORT A-CH-1 NM to PMU1 PORT A-CH-8 NM: These settings allow for custom naming of the analog chan-
nels. Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame.
• PMU1 PORT D-CH-1 to PMU1 PORT D-CH-16: These settings specify any digital flag measured by the relay to be
included as a user-selectable digital channel of the data frame. Up to sixteen digital channels can be configured to
send any FlexLogic™ operand from the relay. The configured digital flags are sampled concurrently with the synchro-
phasor instant. The values are mapped into a two-byte integer number, with byte 1 LSB corresponding to the digital
channel 1 and byte 2 MSB corresponding to digital channel 16.
• PMU1 PORT D-CH-1 NM to PMU1 PORT D-CH-16 NM: These settings allow for custom naming of the digital chan-
nels. Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame.
• PMU1 PORT D-CH-1 NORMAL STATE to PMU1 PORT D-CH-16 NORMAL STATE: These settings allow for specify-
ing a normal state for each digital channel. These states are transmitted in configuration frames to the data concentra-
tor.

GE Multilin G60 Generator Protection System 5-93


5.4 SYSTEM SETUP 5 SETTINGS

e) PMU TRIGGERING OVERVIEW


PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1 ÖØ PMU 1 TRIGGERING

„ PMU 1 „ PMU 1 USER


See page 5-94.
„ TRIGGERING „ TRIGGER
„ PMU 1 FREQUENCY
MESSAGE See page 5-95.
„ TRIGGER
„ PMU 1 VOLTAGE
MESSAGE See page 5-96.
„ TRIGGER
„ PMU 1 CURRENT
MESSAGE See page 5-97.
„ TRIGGER
„ PMU 1 POWER
MESSAGE See page 5-98.
„ TRIGGER
„ PMU 1 df/dt
MESSAGE See page 5-100.
„ TRIGGER

Each logical phasor measurement unit (PMU) contains five triggering mechanisms to facilitate triggering of the associated
PMU recorder, or cross-triggering of other PMUs of the system. They are:
• Overfrequency and underfrequency.
• Overvoltage and undervoltage.
• Overcurrent.
5 • Overpower.
• High rate of change of frequency.
The pre-configured triggers could be augmented with a user-specified condition built freely using programmable logic of the
relay. The entire triggering logic is refreshed once every two power system cycles.
All five triggering functions and the user-definable condition are consolidated (ORed) and connected to the PMU recorder.
Each trigger can be programmed to log its operation into the event recorder, and to signal its operation via targets. The five
triggers drive the STAT bits of the data frame to inform the destination of the synchrophasor data regarding the cause of
trigger. The following convention is adopted to drive bits 11, 3, 2, 1, and 0 of the STAT word.

SETTING
PMU 1 USER TRIGGER:
Off = 0

FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER FLEXLOGIC OPERAND
OR

bit 0
OR

PMU 1 ROCOF TRIGGER bit 3, bit 11 PMU 1 TRIGGERED

PMU 1 VOLT TRIGGER


OR

bit 1 PMU 1 recorder


PMU 1 CURR TRIGGER
PMU 1 POWER TRIGGER bit 2
847004A1.CDR

Figure 5–34: STAT BITS LOGIC

f) USER TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 USER TRIGGER

„ PMU 1 USER PMU1 USER TRIGGER: Range: FlexLogic™ operands


„ TRIGGER Off

The user trigger allows customized triggering logic to be constructed from FlexLogic™. The entire triggering logic is
refreshed once every two power system cycles.

5-94 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

g) FREQUENCY TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 FREQUENCY TRIGGER

„ PMU 1 FREQUENCY PMU 1 FREQ TRIGGER Range: Enabled, Disabled


„ TRIGGER FUNCTION: Disabled
PMU 1 FREQ TRIGGER Range: 20.00 to 70.00 Hz in steps of 0.01
MESSAGE
LOW-FREQ: 49.00 Hz
PMU 1 FREQ TRIGGER Range: 20.00 to 70.00 Hz in steps of 0.01
MESSAGE
HIGH-FREQ: 61.00 Hz
PMU 1 FREQ TRIGGER Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PKP TIME: 0.10 s
PMU 1 FREQ TRIGGER Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DPO TIME: 1.00 s
PMU 1 FREQ TRIG BLK: Range: FlexLogic™ operand
MESSAGE
Off
PMU 1 FREQ TRIGGER Range: Self-Reset, Latched, Disabled
MESSAGE
TARGET: Self-Reset
PMU 1 FREQ TRIGGER Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled

The trigger responds to the frequency signal of the phasor measurement unit (PMU) source. The frequency is calculated
from either phase voltages, auxiliary voltage, phase currents and ground current, in this hierarchy, depending on the source
configuration as per G60 standards. This element requires the frequency is above the minimum measurable value. If the 5
frequency is below this value, such as when the circuit is de-energized, the trigger will drop out.
• PMU 1 FREQ TRIGGER LOW-FREQ: This setting specifies the low threshold for the abnormal frequency trigger. The
comparator applies a 0.03 Hz hysteresis.
• PMU 1 FREQ TRIGGER HIGH-FREQ: This setting specifies the high threshold for the abnormal frequency trigger. The
comparator applies a 0.03 Hz hysteresis.
• PMU 1 FREQ TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
• PMU 1 FREQ TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).

FLEXLOGIC OPERANDS
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER
PMU 1 POWER TRIGGER

SETTINGS PMU 1 ROCOF TRIGGER FLEXLOGIC OPERAND


OR

PMU 1 TRIGGERED
PMU 1 FREQ TRIGGER SETTING
FUNCTION:
PMU 1 USER TRIGGER:
Enabled = 1
Off = 0
AND

PMU 1 FREQ TRIG BLK:


Off = 0
SETTINGS SETTINGS
to STAT bits of
PMU 1 FREQ TRIGGER LOW-FREQ: PMU 1 FREQ TRIGGER PKP TIME: the data frame
SETTING
PMU 1 FREQ TRIGGER HIGH-FREQ: PMU 1 FREQ TRIGGER DPO TIME:
PMU 1 SIGNAL FLEXLOGIC OPERAND
RUN
SOURCE: 0< f < LOW-FREQ tPKP
OR PMU 1 FREQ TRIGGER
FREQUENCY, f f > HIGH-FREQ tDPO
847002A2.CDR

Figure 5–35: FREQUENCY TRIGGER SCHEME LOGIC

GE Multilin G60 Generator Protection System 5-95


5.4 SYSTEM SETUP 5 SETTINGS

h) VOLTAGE TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 VOLTAGE TRIGGER

„ PMU 1 VOLTAGE PMU 1 VOLT TRIGGER Range: Enabled, Disabled


„ TRIGGER FUNCTION: Disabled
PMU 1 VOLT TRIGGER Range: 0.250 to 1.250 pu in steps of 0.001
MESSAGE
LOW-VOLT: 0.800 pu
PMU 1 VOLT TRIGGER Range: 0.750 to 1.750 pu in steps of 0.001
MESSAGE
HIGH-VOLT: 1.200 pu
PMU 1 VOLT TRIGGER Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PKP TIME: 0.10 s
PMU 1 VOLT TRIGGER Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DPO TIME: 1.00 s
PMU 1 VOLT TRIG BLK: Range: FlexLogic™ operand
MESSAGE
Off
PMU 1 VOLT TRIGGER Range: Self-Reset, Latched, Disabled
MESSAGE
TARGET: Self-Reset
PMU 1 VOLT TRIGGER Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled

This element responds to abnormal voltage. Separate thresholds are provided for low and high voltage. In terms of signal-
ing its operation, the element does not differentiate between the undervoltage and overvoltage events. The trigger
5 responds to the phase voltage signal of the phasor measurement unit (PMU) source. All voltage channels (A, B, and C or
AB, BC, and CA) are processed independently and could trigger the recorder. A minimum voltage supervision of 0.1 pu is
implemented to prevent pickup on a de-energized circuit, similarly to the undervoltage protection element.
• PMU 1 VOLT TRIGGER LOW-VOLT: This setting specifies the low threshold for the abnormal voltage trigger, in per-
unit of the PMU source. 1 pu is a nominal voltage value defined as the nominal secondary voltage times VT ratio. The
comparator applies a 3% hysteresis.
• PMU 1 VOLT TRIGGER HIGH-VOLT: This setting specifies the high threshold for the abnormal voltage trigger, in per-
unit of the PMU source. 1 pu is a nominal voltage value defined as the nominal secondary voltage times VT ratio. The
comparator applies a 3% hysteresis.
• PMU 1 VOLT TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
• PMU 1 VOLT TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).

5-96 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

FLEXLOGIC OPERANDS
SETTINGS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER PMU 1 CURR TRIGGER
FUNCTION:
PMU 1 POWER TRIGGER
Enabled = 1
PMU 1 ROCOF TRIGGER FLEXLOGIC OPERAND

AND
PMU 1 VOLT TRIG BLK:

OR
PMU 1 TRIGGERED
Off = 0 SETTING

SETTINGS PMU 1 USER TRIGGER:


SETTINGS PMU 1 VOLT TRIGGER LOW-VOLT: Off = 0

PMU 1 SIGNAL PMU 1 VOLT TRIGGER HIGH-VOLT:


SOURCE:
RUN SETTINGS
VT CONNECTION: PMU 1 VOLT TRIGGER PKP TIME: to STAT bits of
(0.1pu < V < LOW-VOLT) OR the data frame
WYE DELTA (V > HIGH-VOLT) PMU 1 VOLT TRIGGER DPO TIME:
VA VAB (0.1pu < V < LOW-VOLT) OR FLEXLOGIC OPERAND

OR
(V > HIGH-VOLT) tPKP
VB VBC PMU 1 VOLT TRIGGER
(0.1pu < V < LOW-VOLT) OR
VC VCA (V > HIGH-VOLT) tDPO
847005A1.CDR

Figure 5–36: VOLTAGE TRIGGER SCHEME LOGIC

i) CURRENT TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 CURRENT TRIGGER

„ PMU 1 CURRENT PMU 1 CURR TRIGGER Range: Enabled, Disabled


„ TRIGGER FUNCTION: Disabled
PMU 1 CURR TRIGGER Range: 0.100 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 1.800 pu 5
PMU 1 CURR TRIGGER Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PKP TIME: 0.10 s
PMU 1 CURR TRIGGER Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DPO TIME: 1.00 s
PMU 1 CURR TRIG BLK: Range: FlexLogic™ operand
MESSAGE
Off
PMU 1 CURR TRIGGER Range: Self-Reset, Latched, Disabled
MESSAGE
TARGET: Self-Reset
PMU 1 CURR TRIGGER Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled

This element responds to elevated current. The trigger responds to the phase current signal of the phasor measurement
unit (PMU) source. All current channel (A, B, and C) are processed independently and could trigger the recorder.
• PMU 1 CURR TRIGGER PICKUP: This setting specifies the pickup threshold for the overcurrent trigger, in per unit of
the PMU source. A value of 1 pu is a nominal primary current. The comparator applies a 3% hysteresis.
• PMU 1 CURR TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unneces-
sary triggering of the recorder.
• PMU 1 CURR TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).

GE Multilin G60 Generator Protection System 5-97


5.4 SYSTEM SETUP 5 SETTINGS

FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
SETTINGS
PMU 1 POWER TRIGGER
PMU 1 CURR TRIGGER
PMU 1 ROCOF TRIGGER FLEXLOGIC OPERAND
FUNCTION:

OR
PMU 1 TRIGGERED
Enabled = 1 SETTING
PMU 1 CURR TRIG BLK: AND PMU 1 USER TRIGGER:
Off = 0 Off = 0

SETTINGS
SETTINGS SETTINGS
PMU 1 CURR TRIGGER PICKUP:
to STAT bits of
PMU 1 SIGNAL PMU 1 CURR TRIGGER PKP TIME: the data frame
RUN
SOURCE:
PMU 1 CURR TRIGGER DPO TIME:
IA I > PICKUP FLEXLOGIC OPERAND
tPKP

OR
IB I > PICKUP PMU 1 CURR TRIGGER
IC I > PICKUP tDPO
847000A1.CDR

Figure 5–37: CURRENT TRIGGER SCHEME LOGIC

j) POWER TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 POWER TRIGGER

„ PMU 1 POWER PMU 1 POWER TRIGGER Range: Enabled, Disabled


„ TRIGGER FUNCTION: Disabled
PMU 1 POWER TRIGGER Range: 0.250 to 3.000 pu in steps of 0.001
5 MESSAGE
ACTIVE: 1.250 pu
PMU 1 POWER TRIGGER Range: 0.250 to 3.000 pu in steps of 0.001
MESSAGE
REACTIVE: 1.250 pu
PMU 1 POWER TRIGGER Range: 0.250 to 3.000 pu in steps of 0.001
MESSAGE
APPARENT: 1.250 pu
PMU 1 POWER TRIGGER Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PKP TIME: 0.10 s
PMU 1 POWER TRIGGER Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DPO TIME: 1.00 s
PMU 1 PWR TRIG BLK: Range: FlexLogic™ operand
MESSAGE
Off
PMU 1 POWER TRIGGER Range: Self-Reset, Latched, Disabled
MESSAGE
TARGET: Self-Reset
PMU 1 POWER TRIGGER Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled

This element responds to abnormal power. Separate thresholds are provided for active, reactive, and apparent powers. In
terms of signaling its operation the element does not differentiate between the three types of power. The trigger responds to
the single-phase and three-phase power signals of the phasor measurement unit (PMU) source.
• PMU 1 POWER TRIGGER ACTIVE: This setting specifies the pickup threshold for the active power of the source. For
single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage,
the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase
power. The comparator applies a 3% hysteresis.
• PMU 1 POWER TRIGGER REACTIVE: This setting specifies the pickup threshold for the reactive power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power. The comparator applies a 3% hysteresis.

5-98 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

• PMU 1 POWER TRIGGER APPARENT: This setting specifies the pickup threshold for the apparent power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power. The comparator applies a 3% hysteresis.
• PMU 1 POWER TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unneces-
sary triggering of the recorder.
• PMU 1 POWER TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to
normal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the
triggering condition is asserted).

SETTINGS

PMU 1 POWER
TRIGGER FUNCTION: FLEXLOGIC OPERANDS
Enabled = 1 PMU 1 FREQ TRIGGER
AND

PMU 1 PWR TRIG BLK: PMU 1 VOLT TRIGGER


SETTINGS
Off = 0 PMU 1 CURR TRIGGER
PMU 1 POWER TRIGGER ACTIVE:
PMU 1 ROCOF TRIGGER FLEXLOGIC OPERAND
PMU 1 POWER TRIGGER REACTIVE:

OR
PMU 1 TRIGGERED
PMU 1 POWER TRIGGER APPARENT: SETTING
SETTINGS
RUN PMU 1 USER TRIGGER:
PMU 1 SIGNAL SOURCE:
Off = 0
ACTIVE POWER, PA abs(P) > ACTIVE PICKUP
ACTIVE POWER, PB abs(P) > ACTIVE PICKUP
SETTINGS
ACTIVE POWER, PC abs(P) > ACTIVE PICKUP to STAT bits of
PMU 1 POWER TRIGGER PKP TIME: the data frame
3P ACTIVE POWER, P abs(P) > 3*(ACTIVE PICKUP)
REACTIVE POWER, QA
REACTIVE POWER, QB
abs(Q) > REACTIVE PICKUP
abs(Q) > REACTIVE PICKUP
PMU 1 POWER TRIGGER DPO TIME:

tPKP
FLEXLOGIC OPERAND 5
OR

PMU 1 POWER TRIGGER


REACTIVE POWER, QC abs(Q) > REACTIVE PICKUP
tDPO
3P REACTIVE POWER, Q abs(Q) > 3*(REACTIVE PICKUP)
APPARENT POWER, SA S > APPARENT PICKUP
APPARENT POWER, SB S > APPARENT PICKUP
APPARENT POWER, SC S > APPARENT PICKUP
3P APPARENT POWER, S S > 3*(APPARENT PICKUP)
847003A1.CDR

Figure 5–38: POWER TRIGGER SCHEME LOGIC

GE Multilin G60 Generator Protection System 5-99


5.4 SYSTEM SETUP 5 SETTINGS

k) DF/DT TRIGGERING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR MEASUREMENT... ÖØ PMU 1 TRIGGERING ÖØ PMU 1 df/dt TRIGGER

„ PMU 1 df/dt PMU 1 df/dt TRIGGER Range: Enabled, Disabled


„ TRIGGER FUNCTION: Disabled
PMU 1 df/dt TRIGGER Range: 0.10 to 15.00 Hz/s in steps of 0.01
MESSAGE
RAISE: 0.25 Hz/s
PMU 1 df/dt TRIGGER Range: 0.10 to 15.00 Hz/s in steps of 0.01
MESSAGE
FALL: 0.25 Hz/s
PMU 1 df/dt TRIGGER Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PKP TIME: 0.10 s
PMU 1 df/dt TRIGGER Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DPO TIME: 1.00 s
PMU 1 df/dt TRG BLK: Range: FlexLogic™ operand
MESSAGE
Off
PMU 1 df/dt TRIGGER Range: Self-Reset, Latched, Disabled
MESSAGE
TARGET: Self-Reset
PMU 1 df/dt TRIGGER Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled

This element responds to frequency rate of change. Separate thresholds are provided for rising and dropping frequency.
The trigger responds to the rate of change of frequency (df/dt) of the phasor measurement unit (PMU) source.
5 • PMU 1 df/dt TRIGGER RAISE: This setting specifies the pickup threshold for the rate of change of frequency in the
raising direction (positive df/dt). The comparator applies a 3% hysteresis.
• PMU 1 df/dt TRIGGER FALL: This setting specifies the pickup threshold for the rate of change of frequency in the fall-
ing direction (negative df/dt). The comparator applies a 3% hysteresis.
• PMU 1 df/dt TRIGGER PKP TIME: This setting could be used to filter out spurious conditions and avoid unnecessary
triggering of the recorder.
• PMU 1 df/dt TRIGGER DPO TIME: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).

FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER

SETTINGS PMU 1 POWER TRIGGER FLEXLOGIC OPERAND


OR

PMU 1 TRIGGERED
PMU 1 df/dt TRIGGER SETTING
FUNCTION:
PMU 1 USER TRIGGER:
Enabled = 1
Off = 0
AND

PMU 1 df/dt TRG BLK:


Off = 0
SETTINGS SETTINGS
to STAT bits of
PMU 1 df/dt TRIGGER RAISE: PMU 1 df/dt TRIGGER PKP TIME: the data frame
SETTING
PMU 1 df/dt TRIGGER FALL: PMU 1 df/dt TRIGGER DPO TIME:
PMU 1 SIGNAL FLEXLOGIC OPERAND
RUN
SOURCE: df/dt > RAISE tPKP
OR PMU 1 ROCOF TRIGGER
ROCOF, df/dt –df/dt > FALL tDPO
847000A1.CDR

Figure 5–39: RATE OF CHANGE OF FREQUENCY TRIGGER SCHEME LOGIC

5-100 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

l) PMU RECORDING
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1 ÖØ PMU 1 RECORDING

„ PMU 1 PMU 1 RECORDING Range: 1, 2, 4, 5, 10, 12, 15, 20, 25, 30, 50, or 60 times
„ RECORDING RATE: 10/sec per second

PMU 1 NO OF TIMED Range: 2 to 128 in steps of 1


MESSAGE
RECORDS: 10
PMU 1 TRIGGER MODE: Range: Automatic Overwrite, Protected
MESSAGE
Automatic Overwrite
PMU 1 TIMED TRIGGER Range: 1 to 50% in steps of 1
MESSAGE
POSITION: 10%
PMU 1 REC PHS-1: Range: available synchrophasor values
MESSAGE
PMU 1 V1
PMU 1 REC PHS-1 Range: 16 character ASCII string
MESSAGE
NM: GE-UR-PMU-V1

PMU 1 REC PHS-14: Range: available synchrophasor values


MESSAGE
Off
PMU 1 REC PHS-14 Range: 16 character ASCII string
MESSAGE
NM: GE-UR-PMU-PHS-14
Range: available FlexAnalog values
MESSAGE
PMU 1 REC A-CH-1:
Off
5
PMU 1 REC A-CH-1 Range: 16 character ASCII string
MESSAGE
NM: AnalogChannel1

PMU 1 REC A-CH-8: Range: available FlexAnalog values


MESSAGE
Off
PMU 1 REC A-CH-8 Range: 16 character ASCII string
MESSAGE
NM: AnalogChannel8
PMU 1 REC D-CH-1: Range: FlexLogic™ operand
MESSAGE
Off
PMU 1 REC D-CH-1 Range: 16 character ASCII string
MESSAGE
NM: DigitalChannel1

PMU 1 REC D-CH-16: Range: FlexLogic™ operand


MESSAGE
Off
PMU 1 REC D-CH-16 Range: 16 character ASCII string
MESSAGE
NM: DigitalChannel16

Each logical phasor measurement unit (PMU) is associated with a recorder. The triggering condition is programmed via the
PMU 1 TRIGGERING menu. The recorder works with polar values using resolution as in the PMU actual values.

GE Multilin G60 Generator Protection System 5-101


5.4 SYSTEM SETUP 5 SETTINGS

TRIGGER

REC

847709A2.CDR

Figure 5–40: PMU RECORDING


• PMU 1 RECORDING RATE: This setting specifies the recording rate for the record content. Not all recording rates are
applicable to either 50 or 60 Hz systems (for example, recording at 25 phasors a second in a 60 Hz system). The relay
supports decimation by integer number of phasors from the nominal system frequency. If the rate of 25 is selected for
the 60 Hz system, the relay would decimate the rate of 60 phasors a second by round (60 / 25) = 2; that is, it would
record at 60 / 2 = 30 phasors a second.
• PMU 1 NO OF TIMED RECORDS: This setting specifies how many timed records are available for a given logical
PMU. The length of each record equals available memory divided by the content size and number of records. The
higher the number of records, the shorter each record. The relay supports a maximum of 128 records.
• PMU 1 TRIGGER MODE: This setting specifies what happens when the recorder uses its entire available memory
storage. If set to “Automatic Overwrite”, the last record is erased to facilitate new recording, when triggered.
If set to “Protected”, the recorder stops creating new records when the entire memory is used up by the old un-cleared
records. Refer to chapter 7 for more information on clearing PMU records.
The following set of figures illustrate the concept of memory management via the PMU 1 TRIGGER MODE setting.
Total memory for all logical PMUs
5 Memory available for the logical PMU

Record Record Record Free Free


Other logical PMUs
1 2 3 memory memory

Record Record Record Record Free


Other logical PMUs
1 2 3 4 memory

Record Record Record Record Record


Other logical PMUs
1 2 3 4 5

Record Record Record Record Record


Other logical PMUs
6 2 3 4 5
847705A1.CDR

Figure 5–41: “AUTOMATIC OVERWRITE” MODE

Total memory for all logical PMUs

Memory available for the logical PMU

Record Record Record Free Free


Other logical PMUs
1 2 3 memory memory

Record Record Record Record Free


Other logical PMUs
1 2 3 4 memory

Record Record Record Record Record


Other logical PMUs
1 2 3 4 5

No further recording after all allocated memory is used 847706A1.CDR

Figure 5–42: “PROTECTED” MODE

5-102 G60 Generator Protection System GE Multilin


5 SETTINGS 5.4 SYSTEM SETUP

• PMU 1 TIMED TRIGGER POSITION: This setting specifies the amount of pre-trigger data in percent of the entire
record.
• PMU1 PORT 1 PHS-1 to PMU1 PORT 1 PHS-14: These settings specify synchrophasors to be recorded from the
superset of all synchronized measurements as indicated in the following table. These settings allow for optimizing the
record size and content depending on a given application. Select “Off” to suppress recording of a given value.
VALUE DESCRIPTION
Va First voltage channel, either Va or Vab
Vb Second voltage channel, either Vb or Vbc
Vc Third voltage channel, either Vc or Vca
Vx Fourth voltage channel
Ia Phase A current, physical channel or summation as per the source settings
Ib Phase B current, physical channel or summation as per the source settings
Ic Phase C current, physical channel or summation as per the source settings
Ig Fourth current channel, physical or summation as per the source settings
V1 Positive-sequence voltage, referenced to Va
V2 Negative-sequence voltage, referenced to Va
V0 Zero-sequence voltage
I1 Positive-sequence current, referenced to Ia
I2 Negative-sequence current, referenced to Ia
I0 Zero-sequence current

• PMU 1 REC PHS-1 NM to PMU 1 REC PHS-14 NM: These settings allow for custom naming of the synchrophasor
channels. Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame. Typically
these names would be based on station, bus, or breaker names.
5
• PMU 1 REC A-CH-1 to PMU 1 REC A-CH-8: These settings specify analog data measured by the relay to be included
as a user-selectable analog channel of the record. Up to eight analog channels can be configured to record any Flex-
Analog™ value from the relay. Examples include active and reactive power, per phase or three-phase power, power
factor, temperature via RTD inputs, and THD. The configured analogs are sampled concurrently with the synchropha-
sor instant.
• PMU 1 REC A-CH-1 NM to PMU 1 REC A-CH-8 NM: These settings allow for custom naming of the analog channels.
Sixteen-character ASCII strings are allowed as in the CHNAM field of the configuration frame.
• PMU 1 REC D-CH-1 to PMU 1 REC D-CH-16: These settings specify any digital flag measured by the relay to be
included as a user-selectable digital channel in the record. Up to digital analog channels can be configured to record
any FlexLogic™ operand from the relay. The configured digital flags are sampled concurrently with the synchrophasor
instant.
• PMU 1 REC D-CH-1 NM to PMU 1 REC D-CH-16 NM: This setting allows custom naming of the digital channels. Six-
teen-character ASCII strings are allowed as in the CHNAM field of the configuration frame.

GE Multilin G60 Generator Protection System 5-103


5.4 SYSTEM SETUP 5 SETTINGS

m) NETWORK CONNECTION
PATH: SETTINGS ÖØ SYSTEM SETUP ÖØ PHASOR... ÖØ PHASOR MEASUREMENT UNIT 1(4) ÖØ REPORTING OVER NETWORK

„ REPORTING OVER NETWORK REPORTING Range: Enabled, Disabled


„ NETWORK FUNCTION: Disabled
NETWORK REPORTING Range: 1 to 65534 in steps of 1
MESSAGE
IDCODE: 1
NETWORK REPORTING Range: 1, 2, 5, 10, 12, 15, 20, 25, 30, 50, or 60 times per
MESSAGE second
RATE: 10 per sec
NETWORK REPORTING Range: Polar, Rectangular
MESSAGE
STYLE: Polar
NETWORK REPORTING Range: Integer, Floating
MESSAGE
FORMAT: Integer
NETWORK PDC CONTROL: Range: Enabled, Disabled
MESSAGE
Disabled
NETWORK TCP PORT: Range: 1 to 65535 in steps of 1
MESSAGE
4712
NETWORK UDP PORT 1: Range: 1 to 65535 in steps of 1
MESSAGE
4713
NETWORK UDP PORT 2: Range: 1 to 65535 in steps of 1
MESSAGE
4714
5 The Ethernet connection works simultaneously with other communication means working over the Ethernet and is config-
ured as follows. Up to three clients can be simultaneously supported.
• NETWORK REPORTING IDCODE: This setting specifies an IDCODE for the entire port. Individual PMU streams
transmitted over this port are identified via their own IDCODES as per the device settings. This IDCODE is to be used
by the command frame to start or stop transmission, and request configuration or header frames.
• NETWORK REPORTING RATE: This setting specifies the reporting rate for the network (Ethernet) port. This value
applies to all PMU streams of the device that are assigned to transmit over this port.
• NETWORK REPORTING STYLE: This setting selects between reporting synchrophasors in rectangular (real and
imaginary) or in polar (magnitude and angle) coordinates. This setting complies with bit-0 of the format field of the
C37.118 configuration frame.
• NETWORK REPORTING FORMAT: This setting selects between reporting synchrophasors as 16-bit integer or 32-bit
IEEE floating point numbers. This setting complies with bit 1 of the format field of the C37.118 configuration frame.
Note that this setting applies to synchrophasors only – the user-selectable FlexAnalog channels are always transmit-
ted as 32-bit floating point numbers.
• NETWORK PDC CONTROL: The synchrophasor standard allows for user-defined controls originating at the PDC, to
be executed on the PMU. The control is accomplished via an extended command frame. The relay decodes the first
word of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands: PDC NETWORK CNTRL 1 (from the
least significant bit) to PDC NETWORK CNTRL 16 (from the most significant bit). Other words, if any, in the EXTFRAME
are ignored. The operands are asserted for 5 seconds following reception of the command frame. If the new command
frame arrives within the 5 second period, the FlexLogic™ operands are updated, and the 5 second timer is re-started.
This setting enables or disables the control. When enabled, all 16 operands are active; when disabled all 16 operands
remain reset.
• NETWORK TCP PORT: This setting selects the TCP port number that will be used for network reporting.
• NETWORK UDP PORT 1: This setting selects the first UDP port that will be used for network reporting.
• NETWORK UDP PORT 2: This setting selects the second UDP port that will be used for network reporting.

5-104 G60 Generator Protection System GE Multilin


5 SETTINGS 5.5 FLEXLOGIC™

5.5FLEXLOGIC™ 5.5.1 INTRODUCTION TO FLEXLOGIC™

To provide maximum flexibility to the user, the arrangement of internal digital logic combines fixed and user-programmed
parameters. Logic upon which individual features are designed is fixed, and all other logic, from digital input signals through
elements or combinations of elements to digital outputs, is variable. The user has complete control of all variable logic
through FlexLogic™. In general, the system receives analog and digital inputs which it uses to produce analog and digital
outputs. The major sub-systems of a generic UR-series relay involved in this process are shown below.

Figure 5–43: UR ARCHITECTURE OVERVIEW


The states of all digital signals used in the G60 are represented by flags (or FlexLogic™ operands, which are described
later in this section). A digital “1” is represented by a 'set' flag. Any external contact change-of-state can be used to block an
element from operating, as an input to a control feature in a FlexLogic™ equation, or to operate a contact output. The state
of the contact input can be displayed locally or viewed remotely via the communications facilities provided. If a simple
scheme where a contact input is used to block an element is desired, this selection is made when programming the ele-
ment. This capability also applies to the other features that set flags: elements, virtual inputs, remote inputs, schemes, and
human operators.
If more complex logic than presented above is required, it is implemented via FlexLogic™. For example, if it is desired to
have the closed state of contact input H7a and the operated state of the phase undervoltage element block the operation of
the phase time overcurrent element, the two control input states are programmed in a FlexLogic™ equation. This equation
ANDs the two control inputs to produce a virtual output which is then selected when programming the phase time overcur-
rent to be used as a blocking input. Virtual outputs can only be created by FlexLogic™ equations.
Traditionally, protective relay logic has been relatively limited. Any unusual applications involving interlocks, blocking, or
supervisory functions had to be hard-wired using contact inputs and outputs. FlexLogic™ minimizes the requirement for
auxiliary components and wiring while making more complex schemes possible.

GE Multilin G60 Generator Protection System 5-105


5.5 FLEXLOGIC™ 5 SETTINGS

The logic that determines the interaction of inputs, elements, schemes and outputs is field programmable through the use
of logic equations that are sequentially processed. The use of virtual inputs and outputs in addition to hardware is available
internally and on the communication ports for other relays to use (distributed FlexLogic™).
FlexLogic™ allows users to customize the relay through a series of equations that consist of operators and operands. The
operands are the states of inputs, elements, schemes and outputs. The operators are logic gates, timers and latches (with
set and reset inputs). A system of sequential operations allows any combination of specified operands to be assigned as
inputs to specified operators to create an output. The final output of an equation is a numbered register called a virtual out-
put. Virtual outputs can be used as an input operand in any equation, including the equation that generates the output, as a
seal-in or other type of feedback.
A FlexLogic™ equation consists of parameters that are either operands or operators. Operands have a logic state of 1 or 0.
Operators provide a defined function, such as an AND gate or a Timer. Each equation defines the combinations of parame-
ters to be used to set a Virtual Output flag. Evaluation of an equation results in either a 1 (=ON, i.e. flag set) or 0 (=OFF, i.e.
flag not set). Each equation is evaluated at least 4 times every power system cycle.
Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper-
ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different
types of operands are listed in the table below.

Table 5–8: G60 FLEXLOGIC™ OPERAND TYPES


OPERAND TYPE STATE EXAMPLE FORMAT CHARACTERISTICS
[INPUT IS ‘1’ (= ON) IF...]
Contact Input On Cont Ip On Voltage is presently applied to the input (external contact
closed).
Off Cont Ip Off Voltage is presently not applied to the input (external
contact open).
5 Contact Output
(type Form-A contact
Current On Cont Op 1 Ion Current is flowing through the contact.

only) Voltage On Cont Op 1 VOn Voltage exists across the contact.


Voltage Off Cont Op 1 VOff Voltage does not exists across the contact.
Direct Input On DIRECT INPUT 1 On The direct input is presently in the ON state.
Element Pickup PHASE TOC1 PKP The tested parameter is presently above the pickup setting
(Analog) of an element which responds to rising values or below the
pickup setting of an element which responds to falling
values.
Dropout PHASE TOC1 DPO This operand is the logical inverse of the above PKP
operand.
Operate PHASE TOC1 OP The tested parameter has been above/below the pickup
setting of the element for the programmed delay time, or
has been at logic 1 and is now at logic 0 but the reset timer
has not finished timing.
Block PHASE TOC1 BLK The output of the comparator is set to the block function.
Element Pickup Dig Element 1 PKP The input operand is at logic 1.
(Digital)
Dropout Dig Element 1 DPO This operand is the logical inverse of the above PKP
operand.
Operate Dig Element 1 OP The input operand has been at logic 1 for the programmed
pickup delay time, or has been at logic 1 for this period and
is now at logic 0 but the reset timer has not finished timing.
Element Higher than Counter 1 HI The number of pulses counted is above the set number.
(Digital Counter)
Equal to Counter 1 EQL The number of pulses counted is equal to the set number.
Lower than Counter 1 LO The number of pulses counted is below the set number.
Fixed On On Logic 1
Off Off Logic 0
Remote Input On REMOTE INPUT 1 On The remote input is presently in the ON state.
Virtual Input On Virt Ip 1 On The virtual input is presently in the ON state.
Virtual Output On Virt Op 1 On The virtual output is presently in the set state (i.e.
evaluation of the equation which produces this virtual
output results in a "1").

5-106 G60 Generator Protection System GE Multilin


5 SETTINGS 5.5 FLEXLOGIC™

The operands available for this relay are listed alphabetically by types in the following table.
Table 5–9: G60 FLEXLOGIC™ OPERANDS (Sheet 1 of 9)
OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed
PUSHBUTTONS CONTROL PUSHBTN 2 ON Control pushbutton 2 is being pressed
CONTROL PUSHBTN 3 ON Control pushbutton 3 is being pressed
CONTROL PUSHBTN 4 ON Control pushbutton 4 is being pressed
CONTROL PUSHBTN 5 ON Control pushbutton 5 is being pressed
CONTROL PUSHBTN 6 ON Control pushbutton 6 is being pressed
CONTROL PUSHBTN 7 ON Control pushbutton 7 is being pressed
DIRECT DEVICES DIRECT DEVICE 1On Flag is set, logic=1
↓ ↓
DIRECT DEVICE 16On Flag is set, logic=1
DIRECT DEVICE 1Off Flag is set, logic=1
↓ ↓
DIRECT DEVICE 16Off Flag is set, logic=1
DIRECT INPUT/ DIR IO CH1 CRC ALARM The rate of direct input messages received on channel 1 and failing the CRC
OUTPUT exceeded the user-specified level.
CHANNEL DIR IO CH2 CRC ALARM The rate of direct input messages received on channel 2 and failing the CRC
MONITORING exceeded the user-specified level.
DIR IO CH1 UNRET ALM The rate of returned direct input/output messages on channel 1 exceeded the
user-specified level (ring configurations only).
DIR IO CH2 UNRET ALM The rate of returned direct input/output messages on channel 2 exceeded the
user-specified level (ring configurations only).
ELEMENT: 100% STATOR STG1 PKP Stage 1 of the 100% stator ground element has picked up
100% stator ground 100% STATOR STG1 OP Stage 1 of the 100% stator ground element has operated
100% STATOR STG1 DPO Stage 1 of the 100% stator ground element has dropped out
100% STATOR STG2 PKP Stage 2 of the 100% stator ground element has picked up
100% STATOR STG2 OP Stage 2 of the 100% stator ground element has operated
100% STATOR STG2 DPO Stage 2 of the 100% stator ground element has dropped out
100% STATOR PKP The 100% stator ground element has picked up
100% STATOR OP
100% STATOR DPO
The 100% stator ground element has operated
The 100% stator ground element has dropped out
5
ELEMENT: 3RD HARM NTRL UV PKP Third harmonic neutral undervoltage element has picked up
Third harmonic 3RD HARM NTRL UV OP Third harmonic neutral undervoltage element has operated
neutral undervoltage 3RD HARM NTRL UV DPO Third harmonic neutral undervoltage element has dropped out
ELEMENT: ACCDNT ENRG ARMED The accidental energization element is armed
Accidental ACCDNT ENRG DPO The accidental energization element has dropped out
energization ACCDNT ENRG OP The accidental energization element has operated
ELEMENT: AUX OV1 PKP Auxiliary overvoltage element has picked up
Auxiliary AUX OV1 DPO Auxiliary overvoltage element has dropped out
overvoltage AUX OV1 OP Auxiliary overvoltage element has operated
AUX OV2 to AUX OV3 Same set of operands as shown for AUX OV1
ELEMENT: AUX UV1 PKP Auxiliary undervoltage element has picked up
Auxiliary AUX UV1 DPO Auxiliary undervoltage element has dropped out
undervoltage AUX UV1 OP Auxiliary undervoltage element has operated
AUX UV2 to AUX UV3 Same set of operands as shown for AUX UV1

GE Multilin G60 Generator Protection System 5-107


5.5 FLEXLOGIC™ 5 SETTINGS

Table 5–9: G60 FLEXLOGIC™ OPERANDS (Sheet 2 of 9)


OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
ELEMENT: BREAKER 1 OFF CMD Breaker 1 open command initiated
Breaker control BREAKER 1 ON CMD Breaker 1 close command initiated
BREAKER 1 ΦA BAD ST Breaker 1 phase A bad status is detected (discrepancy between the 52/a and
52/b contacts)
BREAKER 1 ΦA INTERM Breaker 1 phase A intermediate status is detected (transition from one
position to another)
BREAKER 1 ΦA CLSD Breaker 1 phase A is closed
BREAKER 1 ΦA OPEN Breaker 1 phase A is open
BREAKER 1 ΦB BAD ST Breaker 1 phase B bad status is detected (discrepancy between the 52/a and
52/b contacts)
BREAKER 1 ΦA INTERM Breaker 1 phase A intermediate status is detected (transition from one
position to another)
BREAKER 1 ΦB CLSD Breaker 1 phase B is closed
BREAKER 1 ΦB OPEN Breaker 1 phase B is open
BREAKER 1 ΦC BAD ST Breaker 1 phase C bad status is detected (discrepancy between the 52/a and
52/b contacts)
BREAKER 1 ΦA INTERM Breaker 1 phase A intermediate status is detected (transition from one
position to another)
BREAKER 1 ΦC CLSD Breaker 1 phase C is closed
BREAKER 1 ΦC OPEN Breaker 1 phase C is open
BREAKER 1 BAD STATUS Breaker 1 bad status is detected on any pole
BREAKER 1 CLOSED Breaker 1 is closed
BREAKER 1 OPEN Breaker 1 is open
BREAKER 1 DISCREP Breaker 1 has discrepancy
BREAKER 1 TROUBLE Breaker 1 trouble alarm
BREAKER 1 MNL CLS Breaker 1 manual close
BREAKER 1 TRIP A Breaker 1 trip phase A command
BREAKER 1 TRIP B Breaker 1 trip phase B command
BREAKER 1 TRIP C Breaker 1 trip phase C command
BREAKER 1 ANY P OPEN At least one pole of breaker 1 is open
BREAKER 1 ONE P OPEN Only one pole of breaker 1 is open
BREAKER 1 OOS Breaker 1 is out of service
5 BREAKER 2... Same set of operands as shown for BREAKER 1
ELEMENT: Counter 1 HI Digital counter 1 output is ‘more than’ comparison value
Digital counters Counter 1 EQL Digital counter 1 output is ‘equal to’ comparison value
Counter 1 LO Digital counter 1 output is ‘less than’ comparison value
Counter 2 to Counter 8 Same set of operands as shown for Counter 1
ELEMENT: Dig Element 1 PKP Digital Element 1 is picked up
Digital elements Dig Element 1 OP Digital Element 1 is operated
Dig Element 1 DPO Digital Element 1 is dropped out
Dig Element 2 to Dig Element 48 Same set of operands as shown for Dig Element 1
ELEMENT: DIR POWER 1 STG1 PKP Stage 1 of the directional power element 1 has picked up
Sensitive directional DIR POWER 1 STG2 PKP Stage 2 of the directional power element 1 has picked up
power DIR POWER 1 STG1 DPO Stage 1 of the directional power element 1 has dropped out
DIR POWER 1 STG2 DPO Stage 2 of the directional power element 1 has dropped out
DIR POWER 1 STG1 OP Stage 1 of the directional power element 1 has operated
DIR POWER 1 STG2 OP Stage 2 of the directional power element 1 has operated
DIR POWER 1 PKP The directional power element has picked up
DIR POWER 1 DPO The directional power element has dropped out
DIR POWER 1 OP The directional power element has operated
DIR POWER 2 Same set of operands as DIR POWER 1
ELEMENT: FIELD GND STG1 PKP ---
Field ground fault FIELD GND STG1 DPO ---
FIELD GND STG1 OP ---
FIELD GND STG2 PKP ---
FIELD GND STG2 DPO ---
FIELD GND STG2 OP ---
FIELD GND INJ UC PKP ---
FIELD GND INJ UC DPO ---
FIELD GND INJ UC OP ---
FIELD OC PKP ---
FIELD OC DPO ---
FIELD OC OP ---
FIELD UC PKP ---
FIELD UC DPO ---
FIELD UC OP ---
GPM-F FAILURE ---

5-108 G60 Generator Protection System GE Multilin


5 SETTINGS 5.5 FLEXLOGIC™

Table 5–9: G60 FLEXLOGIC™ OPERANDS (Sheet 3 of 9)


OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
ELEMENT: FREQ OOB BAND 1 PKP Asserted when the frequency accumulation in band 1 is active.
Frequency out-of- FREQ OOB BAND 1 DPO Asserted when the frequency accumulation in band 1 is inactive.
band accumulation FREQ OOB BAND 1 OP Asserted when the frequency accumulator in band 1 operates.
FREQ OOB ACCUM PKP Asserted when the frequency accumulator in any band is active.
FREQ OOB ACCUM OP Asserted when The frequency accumulator in any band operates.
FREQ OOB BAND 2... The set of operands shown for band 1 above are available for bands 2
through 7.
ELEMENT FREQ RATE 1 PKP The frequency rate of change 1 element has picked up
Frequency rate of FREQ RATE 1 DPO The frequency rate of change 1 element has dropped out
change FREQ RATE 1 OP The frequency rate of change 1 element has operated
FREQ RATE 2 to FREQ RATE 4 Same set of operands as shown for FREQ RATE 1
ELEMENT: FxE 1 PKP FlexElement™ 1 has picked up
FlexElements™ FxE 1 OP FlexElement™ 1 has operated
FxE 1 DPO FlexElement™ 1 has dropped out
FxE 2 to FxE 16 Same set of operands as shown for FxE 1
ELEMENT: GEN UNBAL STG1 PKP The Generator Unbalance Stage 1 element has picked up
Generator GEN UNBAL STG1 DPO The Generator Unbalance Stage 1 element has dropped out
unbalance GEN UNBAL STG1 OP The Generator Unbalance Stage 1 element has operated
GEN UNBAL STG2 PKP The Generator Unbalance Stage 2 element has picked up
GEN UNBAL STG2 DPO The Generator Unbalance Stage 2 element has dropped out
GEN UNBAL STG2 OP The Generator Unbalance Stage 2 element has operated
GEN UNBAL PKP The Generator Unbalance element has picked up
GEN UNBAL DPO The Generator Unbalance element has dropped out
GEN UNBAL OP The Generator Unbalance element has operated
ELEMENT: GROUND IOC1 PKP Ground instantaneous overcurrent 1 has picked up
Ground GROUND IOC1 OP Ground instantaneous overcurrent 1 has operated
instantaneous GROUND IOC1 DPO Ground instantaneous overcurrent 1 has dropped out
overcurrent
ELEMENT: GROUND TOC1 PKP Ground time overcurrent 1 has picked up
5
Ground time GROUND TOC1 OP Ground time overcurrent 1 has operated
overcurrent GROUND TOC1 DPO Ground time overcurrent 1 has dropped out
ELEMENT LATCH 1 ON Non-volatile latch 1 is ON (Logic = 1)
Non-volatile latches LATCH 1 OFF Non-volatile latch 1 is OFF (Logic = 0)
LATCH 2 to LATCH 16 Same set of operands as shown for LATCH 1
ELEMENT: LOSS EXCIT STG1 PKP Stage 1 of the loss of excitation element has picked up
Loss of excitation LOSS EXCIT STG2 PKP Stage 2 of the loss of excitation element has picked up
LOSS EXCIT STG1 DPO Stage 1 of the loss of excitation element has dropped out
LOSS EXCIT STG2 DPO Stage 2 of the loss of excitation element has dropped out
LOSS EXCIT STG1 OP Stage 1 of the loss of excitation element has operated
LOSS EXCIT STG2 OP Stage 2 of the loss of excitation element has operated
LOSS EXCIT PKP The loss of excitation element has picked up
LOSS EXCIT DPO The loss of excitation element has dropped out
LOSS EXCIT OP The loss of excitation element has operated
ELEMENT: NEG SEQ DIR OC1 FWD Negative-sequence directional overcurrent 1 forward has operated
Negative-sequence NEG SEQ DIR OC1 REV Negative-sequence directional overcurrent 1 reverse has operated
directional NEG SEQ DIR OC2 FWD Negative-sequence directional overcurrent 2 forward has operated
overcurrent NEG SEQ DIR OC2 REV Negative-sequence directional overcurrent 2 reverse has operated
ELEMENT: NEG SEQ OV1 PKP Negative-sequence overvoltage element has picked up
Negative-sequence NEG SEQ OV1 DPO Negative-sequence overvoltage element has dropped out
overvoltage NEG SEQ OV1 OP Negative-sequence overvoltage element has operated
NEG SEQ OV2... Same set of operands as shown for NEG SEQ OV1
ELEMENT: NEUTRAL IOC1 PKP Neutral instantaneous overcurrent 1 has picked up
Neutral NEUTRAL IOC1 OP Neutral instantaneous overcurrent 1 has operated
instantaneous NEUTRAL IOC1 DPO Neutral instantaneous overcurrent 1 has dropped out
overcurrent
ELEMENT: NEUTRAL OV1 PKP Neutral overvoltage element 1 has picked up
Neutral overvoltage NEUTRAL OV1 DPO Neutral overvoltage element 1 has dropped out
NEUTRAL OV1 OP Neutral overvoltage element 1 has operated
ELEMENT: NEUTRAL TOC1 PKP Neutral time overcurrent 1 has picked up
Neutral time NEUTRAL TOC1 OP Neutral time overcurrent 1 has operated
overcurrent NEUTRAL TOC1 DPO Neutral time overcurrent 1 has dropped out
ELEMENT: NTRL DIR OC1 FWD Neutral directional overcurrent 1 forward has operated
Neutral directional NTRL DIR OC1 REV Neutral directional overcurrent 1 reverse has operated
overcurrent
NTRL DIR OC2 Same set of operands as shown for NTRL DIR OC1

GE Multilin G60 Generator Protection System 5-109


5.5 FLEXLOGIC™ 5 SETTINGS

Table 5–9: G60 FLEXLOGIC™ OPERANDS (Sheet 4 of 9)


OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
ELEMENT: OVERFREQ 1 PKP Overfrequency 1 has picked up
Overfrequency OVERFREQ 1 OP Overfrequency 1 has operated
OVERFREQ 1 DPO Overfrequency 1 has dropped out
OVERFREQ 2 to 4 Same set of operands as shown for OVERFREQ 1
ELEMENT: PDC NETWORK CNTRL 1 Phasor data concentrator asserts control bit 1 as received via the network
Synchrophasor PDC NETWORK CNTRL 2 Phasor data concentrator asserts control bit 2 as received via the network
phasor data ↓ ↓
concentrator PDC NETWORK CNTRL 16 Phasor data concentrator asserts control bit 16 as received via the network
ELEMENT: PH DIR1 BLK A Phase A directional 1 block
Phase directional PH DIR1 BLK B Phase B directional 1 block
overcurrent PH DIR1 BLK C Phase C directional 1 block
PH DIR1 BLK Phase directional 1 block
ELEMENT: PH DIST Z1 PKP Phase distance zone 1 has picked up
Phase distance PH DIST Z1 OP Phase distance zone 1 has operated
PH DIST Z1 OP AB Phase distance zone 1 phase AB has operated
PH DIST Z1 OP BC Phase distance zone 1 phase BC has operated
PH DIST Z1 OP CA Phase distance zone 1 phase CA has operated
PH DIST Z1 PKP AB Phase distance zone 1 phase AB has picked up
PH DIST Z1 PKP BC Phase distance zone 1 phase BC has picked up
PH DIST Z1 PKP CA Phase distance zone 1 phase CA has picked up
PH DIST Z1 SUPN IAB Phase distance zone 1 phase AB IOC is supervising
PH DIST Z1 SUPN IBC Phase distance zone 1 phase BC IOC is supervising
PH DIST Z1 SUPN ICA Phase distance zone 1 phase CA IOC is supervising
PH DIST Z1 DPO AB Phase distance zone 1 phase AB has dropped out
PH DIST Z1 DPO BC Phase distance zone 1 phase BC has dropped out
PH DIST Z1 DPO CA Phase distance zone 1 phase CA has dropped out
PH DIST Z2 to Z3 Same set of operands as shown for PH DIST Z1
ELEMENT: PHASE IOC1 PKP At least one phase of phase instantaneous overcurrent 1 has picked up
5 Phase
instantaneous
PHASE IOC1 OP
PHASE IOC1 DPO
At least one phase of phase instantaneous overcurrent 1 has operated
All phases of phase instantaneous overcurrent 1 have dropped out
overcurrent PHASE IOC1 PKP A Phase A of phase instantaneous overcurrent 1 has picked up
PHASE IOC1 PKP B Phase B of phase instantaneous overcurrent 1 has picked up
PHASE IOC1 PKP C Phase C of phase instantaneous overcurrent 1 has picked up
PHASE IOC1 OP A Phase A of phase instantaneous overcurrent 1 has operated
PHASE IOC1 OP B Phase B of phase instantaneous overcurrent 1 has operated
PHASE IOC1 OP C Phase C of phase instantaneous overcurrent 1 has operated
PHASE IOC1 DPO A Phase A of phase instantaneous overcurrent 1 has dropped out
PHASE IOC1 DPO B Phase B of phase instantaneous overcurrent 1 has dropped out
PHASE IOC1 DPO C Phase C of phase instantaneous overcurrent 1 has dropped out
PHASE IOC2 and higher Same set of operands as shown for PHASE IOC1
ELEMENT: PHASE OV1 PKP At least one phase of overvoltage 1 has picked up
Phase overvoltage PHASE OV1 OP At least one phase of overvoltage 1 has operated
PHASE OV1 DPO All phases of overvoltage 1 have dropped out
PHASE OV1 PKP A Phase A of overvoltage 1 has picked up
PHASE OV1 PKP B Phase B of overvoltage 1 has picked up
PHASE OV1 PKP C Phase C of overvoltage 1 has picked up
PHASE OV1 OP A Phase A of overvoltage 1 has operated
PHASE OV1 OP B Phase B of overvoltage 1 has operated
PHASE OV1 OP C Phase C of overvoltage 1 has operated
PHASE OV1 DPO A Phase A of overvoltage 1 has dropped out
PHASE OV1 DPO B Phase B of overvoltage 1 has dropped out
PHASE OV1 DPO C Phase C of overvoltage 1 has dropped out
ELEMENT: PHASE TOC1 PKP At least one phase of phase time overcurrent 1 has picked up
Phase time PHASE TOC1 OP At least one phase of phase time overcurrent 1 has operated
overcurrent PHASE TOC1 DPO All phases of phase time overcurrent 1 have dropped out
PHASE TOC1 PKP A Phase A of phase time overcurrent 1 has picked up
PHASE TOC1 PKP B Phase B of phase time overcurrent 1 has picked up
PHASE TOC1 PKP C Phase C of phase time overcurrent 1 has picked up
PHASE TOC1 OP A Phase A of phase time overcurrent 1 has operated
PHASE TOC1 OP B Phase B of phase time overcurrent 1 has operated
PHASE TOC1 OP C Phase C of phase time overcurrent 1 has operated
PHASE TOC1 DPO A Phase A of phase time overcurrent 1 has dropped out
PHASE TOC1 DPO B Phase B of phase time overcurrent 1 has dropped out
PHASE TOC1 DPO C Phase C of phase time overcurrent 1 has dropped out

5-110 G60 Generator Protection System GE Multilin


5 SETTINGS 5.5 FLEXLOGIC™

Table 5–9: G60 FLEXLOGIC™ OPERANDS (Sheet 5 of 9)


OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
ELEMENT: PHASE UV1 PKP At least one phase of phase undervoltage 1 has picked up
Phase undervoltage PHASE UV1 OP At least one phase of phase undervoltage 1 has operated
PHASE UV1 DPO All phases of phase undervoltage 1 have dropped out
PHASE UV1 PKP A Phase A of phase undervoltage 1 has picked up
PHASE UV1 PKP B Phase B of phase undervoltage 1 has picked up
PHASE UV1 PKP C Phase C of phase undervoltage 1 has picked up
PHASE UV1 OP A Phase A of phase undervoltage 1 has operated
PHASE UV1 OP B Phase B of phase undervoltage 1 has operated
PHASE UV1 OP C Phase C of phase undervoltage 1 has operated
PHASE UV1 DPO A Phase A of phase undervoltage 1 has dropped out
PHASE UV1 DPO B Phase B of phase undervoltage 1 has dropped out
PHASE UV1 DPO C Phase C of phase undervoltage 1 has dropped out
PHASE UV2 Same set of operands as shown for PHASE UV1
ELEMENT: PMU 1 CURR TRIGGER Overcurrent trigger of phasor measurement unit 1 has operated
Synchrophasor PMU 1 FREQ TRIGGER Abnormal frequency trigger of phasor measurement unit 1 has operated
phasor PMU 1 POWER TRIGGER Overpower trigger of phasor measurement unit 1 has operated
measurement unit PMU 1 ROCOF TRIGGER Rate of change of frequency trigger of phasor measurement unit 1 has
(PMU) operated
PMU 1 VOLT TRIGGER Abnormal voltage trigger of phasor measurement unit 1 has operated
PMU 1 TRIGGERED Phasor measurement unit 1 triggered; no events or targets are generated by
this operand
ELEMENT: PMU ONE-SHOT EXPIRED Indicates the one-shot operation has been executed, and the present time is
Synchrophasor one- at least 30 seconds past the scheduled one-shot time
shot PMU ONE-SHOT OP Indicates the one-shot operation and remains asserted for 30 seconds
afterwards
PMU ONE-SHOT PENDING Indicates the one-shot operation is pending; that is, the present time is before
the scheduled one-shot time
ELEMENT: POWER SWING OUTER Positive-sequence impedance in outer characteristic
Power swing detect POWER SWING MIDDLE Positive-sequence impedance in middle characteristic
POWER SWING INNER
POWER SWING BLOCK
Positive-sequence impedance in inner characteristic
Power swing blocking element operated 5
POWER SWING TMR1 PKP Power swing timer 1 picked up
POWER SWING TMR2 PKP Power swing timer 2 picked up
POWER SWING TMR3 PKP Power swing timer 3 picked up
POWER SWING TMR4 PKP Power swing timer 4 picked up
POWER SWING TRIP Out-of-step tripping operated
POWER SWING 50DD The power swing element detected a disturbance other than power swing
POWER SWING INCOMING An unstable power swing has been detected (incoming locus)
POWER SWING OUTGOING An unstable power swing has been detected (outgoing locus)
POWER SWING UN/BLOCK Asserted when a fault occurs after the power swing blocking condition has
been established
ELEMENT: RESTD GND FT1 PKP Restricted ground fault 1 has picked up.
Restricted ground RESTD GND FT1 OP Restricted ground fault 1 has operated.
fault RESTD GND FT1 DPO Restricted ground fault 1 has dropped out.
RESTD GND FT2 to FT4 Same set of operands as shown for RESTD GND FT1
ELEMENT: RRTD COMM FAIL Asserted when RRTD loss of communications is detected.
Remote RTD RRTD RTD 1 ALARM DPO Asserted when the RRTD RTD 1 alarm stage drops out.
protection RRTD RTD 1 ALARM OP Asserted when the RRTD RTD 1 alarm stage operates.
RRTD RTD 1 ALARM PKP Asserted when the RRTD RTD 1 alarm stage picks up.
RRTD RTD 1 OPEN Asserted when the RRTD RTD 1 detects an open circuit.
RRTD RTD 1 SHORTED Asserted when the RRTD RTD 1 detects an short/low circuit.
RRTD RTD 1 TRIP DPO Asserted when the RRTD RTD 1 trip stage drops out.
RRTD RTD 1 TRIP OP Asserted when the RRTD RTD 1 trip stage operates.
RRTD RTD 1 TRIP PKP Asserted when the RRTD RTD 1 trip stage picks up.
RRTD RTD 2... The set of operands shown above are available for RRTD RTD 2 and higher
ELEMENT: RTD Ip 1 ALARM DPO Asserted when the alarm stage of RTD input 1 protection picks up.
RTD protection RTD Ip 1 ALARM OP Asserted when the alarm stage of RTD input 1 protection operates.
RTD Ip 1 ALARM PKP Asserted when the alarm stage of RTD input 1 protection drops out.
RTD Ip 1 OPEN Asserted when RTD input 1 detects an open circuit.
RTD Ip 1 SHORTED Asserted when RTD input 1 detects a shorted or low circuit.
RTD Ip 1 TRIP DPO Asserted when the trip stage of RTD input 1 protection picks up.
RTD Ip 1 TRIP OP Asserted when the trip stage of RTD input 1 protection operates.
RTD Ip 1 TRIP PKP Asserted when the trip stage of RTD input 1 protection drops out.
RTD Ip 2... The set of operands shown above are available for the RTD Ip 2 and higher
elements

GE Multilin G60 Generator Protection System 5-111


5.5 FLEXLOGIC™ 5 SETTINGS

Table 5–9: G60 FLEXLOGIC™ OPERANDS (Sheet 6 of 9)


OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
ELEMENT: SELECTOR 1 POS Y Selector switch 1 is in Position Y (mutually exclusive operands)
Selector switch SELECTOR 1 BIT 0 First bit of the 3-bit word encoding position of selector 1
SELECTOR 1 BIT 1 Second bit of the 3-bit word encoding position of selector 1
SELECTOR 1 BIT 2 Third bit of the 3-bit word encoding position of selector 1
SELECTOR 1 STP ALARM Position of selector 1 has been pre-selected with the stepping up control
input but not acknowledged
SELECTOR 1 BIT ALARM Position of selector 1 has been pre-selected with the 3-bit control input but
not acknowledged
SELECTOR 1 ALARM Position of selector 1 has been pre-selected but not acknowledged
SELECTOR 1 PWR ALARM Position of selector switch 1 is undetermined or restored from memory when
the relay powers up and synchronizes to the three-bit input
SELECTOR 2 Same set of operands as shown above for SELECTOR 1
ELEMENT: SETTING GROUP ACT 1 Setting group 1 is active
Setting group SETTING GROUP ACT 2 Setting group 2 is active
SETTING GROUP ACT 3 Setting group 3 is active
SETTING GROUP ACT 4 Setting group 4 is active
SETTING GROUP ACT 5 Setting group 5 is active
SETTING GROUP ACT 6 Setting group 6 is active
ELEMENT: SH STAT GND STG1 PKP ---
Sub-harmonic stator SH STAT GND STG1 DPO ---
ground fault detector SH STAT GND STG1 OP ---
SH STAT GND STG2 PKP ---
SH STAT GND STG2 DPO ---
SH STAT GND STG2 OP ---
SH STAT GND OC PKP ---
SH STAT GND OC DPO ---
SH STAT GND OC OP ---
SH STAT GND TRB PKP ---
SH STAT GND TRB DPO ---
SH STAT GND TRB OP ---
5 ELEMENT: SPLIT PHASE A PKP Phase A of the split phase protection has picked up
Split phase SPLIT PHASE A DPO Phase A of the split phase protection has dropped out
protection SPLIT PHASE A OP Phase A of the split phase protection has operated
SPLIT PHASE B PKP Phase B of the split phase protection has picked up
SPLIT PHASE B DPO Phase B of the split phase protection has dropped out
SPLIT PHASE B OP Phase B of the split phase protection has operated
SPLIT PHASE C PKP Phase C of the split phase protection has picked up
SPLIT PHASE C DPO Phase C of the split phase protection has dropped out
SPLIT PHASE C OP Phase C of the split phase protection has operated
SPLIT PHASE OP The split phase protection has operated
SPLIT PHASE PKP The split phase protection has picked up
SPLIT PHASE DPO The split phase protection has dropped out
ELEMENT: SRC1 VT FUSE FAIL OP Source 1 VT fuse failure detector has operated
VTFF (Voltage SRC1 VT FUSE FAIL DPO Source 1 VT fuse failure detector has dropped out
transformer fuse SRC1 VT FUSE FAIL VOL LOSS Source 1 has lost voltage signals (V2 below 15% AND V1 below 5%
failure) of nominal)
SRC2 VT FUSE FAIL to Same set of operands as shown for SRC1 VT FUSE FAIL
SRC4 VT FUSE FAIL
ELEMENT: STATOR DIFF OP At least one phase of stator differential has operated
Stator differential STATOR DIFF PKP A Phase A of stator differential has picked up
STATOR DIFF PKP B Phase B of stator differential has picked up
STATOR DIFF PKP C Phase C of stator differential has picked up
STATOR DIFF OP A Phase A of stator differential has operated
STATOR DIFF OP B Phase B of stator differential has operated
STATOR DIFF OP C Phase C of stator differential has operated
STATOR DIFF DPO A Phase A of stator differential has dropped out
STATOR DIFF DPO B Phase B of stator differential has dropped out
STATOR DIFF DPO C Phase C of stator differential has dropped out
STATOR DIFF SAT A Phase A of stator differential has is saturated
STATOR DIFF SAT B Phase B of stator differential has is saturated
STATOR DIFF SAT C Phase C of stator differential has is saturated
STATOR DIFF DIR A Phase A of stator differential phase comparison has been satisfied
STATOR DIFF DIR B Phase B of stator differential phase comparison has been satisfied
STATOR DIFF DIR C Phase C of stator differential phase comparison has been satisfied

5-112 G60 Generator Protection System GE Multilin


5 SETTINGS 5.5 FLEXLOGIC™

Table 5–9: G60 FLEXLOGIC™ OPERANDS (Sheet 7 of 9)


OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
ELEMENT: SWITCH 1 OFF CMD Disconnect switch 1 open command initiated
Disconnect switch SWITCH 1 ON CMD Disconnect switch 1 close command initiated
SWITCH 1 ΦA BAD ST Disconnect switch 1 phase A bad status is detected (discrepancy between
the 52/a and 52/b contacts)
SWITCH 1 ΦA INTERM Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
SWITCH 1 ΦA CLSD Disconnect switch 1 phase A is closed
SWITCH 1 ΦA OPEN Disconnect switch 1 phase A is open
SWITCH 1 ΦB BAD ST Disconnect switch 1 phase B bad status is detected (discrepancy between
the 52/a and 52/b contacts)
SWITCH 1 ΦA INTERM Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
SWITCH 1 ΦB CLSD Disconnect switch 1 phase B is closed
SWITCH 1 ΦB OPEN Disconnect switch 1 phase B is open
SWITCH 1 ΦC BAD ST Disconnect switch 1 phase C bad status is detected (discrepancy between
the 52/a and 52/b contacts)
SWITCH 1 ΦA INTERM Disconnect switch 1 phase A intermediate status is detected (transition from
one position to another)
SWITCH 1 ΦC CLSD Disconnect switch 1 phase C is closed
SWITCH 1 ΦC OPEN Disconnect switch 1 phase C is open
SWITCH 1 BAD STATUS Disconnect switch 1 bad status is detected on any pole
SWITCH 1 CLOSED Disconnect switch 1 is closed
SWITCH 1 OPEN Disconnect switch 1 is open
SWITCH 1 DISCREP Disconnect switch 1 has discrepancy
SWITCH 1 TROUBLE Disconnect switch 1 trouble alarm
SWITCH 2... Same set of operands as shown for SWITCH 1
ELEMENT: SYNC 1 DEAD S OP Synchrocheck 1 dead source has operated
Synchrocheck SYNC 1 DEAD S DPO Synchrocheck 1 dead source has dropped out
SYNC 1 SYNC OP Synchrocheck 1 in synchronization has operated
SYNC 1 SYNC DPO Synchrocheck 1 in synchronization has dropped out
SYNC 1 CLS OP
SYNC 1 CLS DPO
Synchrocheck 1 close has operated
Synchrocheck 1 close has dropped out 5
SYNC 1 V1 ABOVE MIN Synchrocheck 1 V1 is above the minimum live voltage
SYNC 1 V1 BELOW MAX Synchrocheck 1 V1 is below the maximum dead voltage
SYNC 1 V2 ABOVE MIN Synchrocheck 1 V2 is above the minimum live voltage
SYNC 1 V2 BELOW MAX Synchrocheck 1 V2 is below the maximum dead voltage
SYNC 2 Same set of operands as shown for SYNC 1
ELEMENT: TELEPRO CH1 FAIL Channel 1 failed
Teleprotection TELEPRO CH2 FAIL Channel 2 failed
channel tests TELEPRO CH1 ID FAIL The ID check for a peer relay on channel 1 has failed
TELEPRO CH2 ID FAIL The ID check for a peer relay on channel 2 has failed
TELEPRO CH1 CRC FAIL CRC detected packet corruption on channel 1
TELEPRO CH2 CRC FAIL CRC detected packet corruption on channel 2
TELEPRO CH1 PKT LOST CRC detected lost packet on channel 1
TELEPRO CH2 PKT LOST CRC detected lost packet on channel 2
ELEMENT: TELEPRO INPUT 1-1 On Flag is set, Logic =1
Teleprotection ↓ ↓
inputs/outputs TELEPRO INPUT 1-16 On Flag is set, Logic =1
TELEPRO INPUT 2-1 On Flag is set, Logic =1
↓ ↓
TELEPRO INPUT 2-16 On Flag is set, Logic =1
ELEMENT TRIP BUS 1 PKP Asserted when the trip bus 1 element picks up.
Trip bus TRIP BUS 1 OP Asserted when the trip bus 1 element operates.
TRIP BUS 2... Same set of operands as shown for TRIP BUS 1
ELEMENT: UNDERFREQ 1 PKP Underfrequency 1 has picked up
Underfrequency UNDERFREQ 1 OP Underfrequency 1 has operated
UNDERFREQ 1 DPO Underfrequency 1 has dropped out
UNDERFREQ 2 to 6 Same set of operands as shown for UNDERFREQ 1 above
ELEMENT: VOLT PER HERTZ 1 PKP The volts per hertz element 1 has picked up
Volts per hertz VOLT PER HERTZ 1 OP The volts per hertz element 1 has operated
VOLT PER HERTZ 1 DPO The volts per hertz element 1 has dropped out
VOLT PER HERTZ 2 Same set of operands as VOLT PER HERTZ 1 above
FIXED OPERANDS Off Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as ‘Disable’ by other features.
On Logic = 1. Can be used as a test setting.

GE Multilin G60 Generator Protection System 5-113


5.5 FLEXLOGIC™ 5 SETTINGS

Table 5–9: G60 FLEXLOGIC™ OPERANDS (Sheet 8 of 9)


OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
INPUTS/OUTPUTS: Cont Ip 1 On (will not appear unless ordered)
Contact inputs Cont Ip 2 On (will not appear unless ordered)
↓ ↓
Cont Ip 1 Off (will not appear unless ordered)
Cont Ip 2 Off (will not appear unless ordered)
↓ ↓
INPUTS/OUTPUTS: Cont Op 1 IOn (will not appear unless ordered)
Contact outputs, Cont Op 2 IOn (will not appear unless ordered)
current ↓ ↓
(from detector on
form-A output only)
INPUTS/OUTPUTS: Cont Op 1 VOn (will not appear unless ordered)
Contact outputs, Cont Op 2 VOn (will not appear unless ordered)
voltage ↓ ↓
(from detector on
form-A output only) Cont Op 1 VOff (will not appear unless ordered)
Cont Op 2 VOff (will not appear unless ordered)
↓ ↓
INPUTS/OUTPUTS DIRECT INPUT 1 On Flag is set, logic=1
Direct inputs ↓ ↓
DIRECT INPUT 32 On Flag is set, logic=1
INPUTS/OUTPUTS: RemDPS Ip 1 BAD Asserted while the remote double-point status input is in the bad state.
Remote double- RemDPS Ip 1 INTERM Asserted while the remote double-point status input is in the intermediate
point status inputs state.
RemDPS Ip 1 OFF Asserted while the remote double-point status input is off.
RemDPS Ip 1 ON Asserted while the remote double-point status input is on.
REMDPS Ip 2... Same set of operands as per REMDPS 1 above
INPUTS/OUTPUTS: REMOTE INPUT 1 On Flag is set, logic=1
5 Remote inputs REMOTE INPUT 2 On
REMOTE INPUT 2 On
Flag is set, logic=1
Flag is set, logic=1
↓ ↓
REMOTE INPUT 32 On Flag is set, logic=1

INPUTS/OUTPUTS: Virt Ip 1 On Flag is set, logic=1


Virtual inputs Virt Ip 2 On Flag is set, logic=1
Virt Ip 3 On Flag is set, logic=1
↓ ↓
Virt Ip 64 On Flag is set, logic=1
INPUTS/OUTPUTS: Virt Op 1 On Flag is set, logic=1
Virtual outputs Virt Op 2 On Flag is set, logic=1
Virt Op 3 On Flag is set, logic=1
↓ ↓
Virt Op 96 On Flag is set, logic=1
LED INDICATORS: LED IN SERVICE Asserted when the front panel IN SERVICE LED is on.
Fixed front panel LED TROUBLE Asserted when the front panel TROUBLE LED is on.
LEDs LED TEST MODE Asserted when the front panel TEST MODE LED is on.
LED TRIP Asserted when the front panel TRIP LED is on.
LED ALARM Asserted when the front panel ALARM LED is on.
LED PICKUP Asserted when the front panel PICKUP LED is on.
LED VOLTAGE Asserted when the front panel VOLTAGE LED is on.
LED CURRENT Asserted when the front panel CURRENT LED is on.
LED FREQUENCY Asserted when the front panel FREQUENCY LED is on.
LED OTHER Asserted when the front panel OTHER LED is on.
LED PHASE A Asserted when the front panel PHASE A LED is on.
LED PHASE B Asserted when the front panel PHASE B LED is on.
LED PHASE C Asserted when the front panel PHASE C LED is on.
LED NEUTRAL/GROUND Asserted when the front panel NEUTRAL/GROUND LED is on.
LED INDICATORS: LED TEST IN PROGRESS An LED test has been initiated and has not finished.
LED test
LED INDICATORS: LED USER 1 Asserted when user-programmable LED 1 is on.
User-programmable
LEDs LED USER 2 to 48 The operand above is available for user-programmable LEDs 2 through 48.

5-114 G60 Generator Protection System GE Multilin


5 SETTINGS 5.5 FLEXLOGIC™

Table 5–9: G60 FLEXLOGIC™ OPERANDS (Sheet 9 of 9)


OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION
PASSWORD ACCESS LOC SETG OFF Asserted when local setting access is disabled.
SECURITY ACCESS LOC SETG ON Asserted when local setting access is enabled.
ACCESS LOC CMND OFF Asserted when local command access is disabled.
ACCESS LOC CMND ON Asserted when local command access is enabled.
ACCESS REM SETG OFF Asserted when remote setting access is disabled.
ACCESS REM SETG ON Asserted when remote setting access is enabled.
ACCESS REM CMND OFF Asserted when remote command access is disabled.
ACCESS REM CMND ON Asserted when remote command access is enabled.
UNAUTHORIZED ACCESS Asserted when a password entry fails while accessing a password protected
level of the G60.
REMOTE DEVICES REMOTE DEVICE 1 On Flag is set, logic=1
REMOTE DEVICE 2 On Flag is set, logic=1
REMOTE DEVICE 2 On Flag is set, logic=1
↓ ↓
REMOTE DEVICE 16 On Flag is set, logic=1

REMOTE DEVICE 1 Off Flag is set, logic=1


REMOTE DEVICE 2 Off Flag is set, logic=1
REMOTE DEVICE 3 Off Flag is set, logic=1
↓ ↓
REMOTE DEVICE 16 Off Flag is set, logic=1

RESETTING RESET OP Reset command is operated (set by all three operands below).
RESET OP (COMMS) Communications source of the reset command.
RESET OP (OPERAND) Operand (assigned in the INPUTS/OUTPUTS ÖØ RESETTING menu) source
of the reset command.
RESET OP (PUSHBUTTON) Reset key (pushbutton) source of the reset command.
SELF- ANY MAJOR ERROR Any of the major self-test errors generated (major error)
DIAGNOSTICS ANY MINOR ERROR Any of the minor self-test errors generated (minor error)
ANY SELF-TESTS
BATTERY FAIL
Any self-test errors generated (generic, any error)
See description in Chapter 7: Commands and targets 5
DIRECT DEVICE OFF See description in Chapter 7: Commands and targets
DIRECT RING BREAK See description in Chapter 7: Commands and targets
EQUIPMENT MISMATCH See description in Chapter 7: Commands and targets
ETHERNET SWITCH FAIL See description in Chapter 7: Commands and targets
FLEXLOGIC ERR TOKEN See description in Chapter 7: Commands and targets
IRIG-B FAILURE See description in Chapter 7: Commands and targets
LATCHING OUT ERROR See description in Chapter 7: Commands and targets
MAINTENANCE ALERT See description in Chapter 7: Commands and targets
PORT 1 OFFLINE See description in Chapter 7: Commands and targets
PORT 2 OFFLINE See description in Chapter 7: Commands and targets
PORT 3 OFFLINE See description in Chapter 7: Commands and targets
PORT 4 OFFLINE See description in Chapter 7: Commands and targets
PORT 5 OFFLINE See description in Chapter 7: Commands and targets
PORT 6 OFFLINE See description in Chapter 7: Commands and targets
PRI ETHERNET FAIL See description in Chapter 7: Commands and targets
PROCESS BUS FAILURE See description in Chapter 7: Commands and targets
REMOTE DEVICE OFF See description in Chapter 7: Commands and targets
RRTD COMM FAIL See description in Chapter 7: Commands and targets
SEC ETHERNET FAIL See description in Chapter 7: Commands and targets
SNTP FAILURE See description in Chapter 7: Commands and targets
SYSTEM EXCEPTION See description in Chapter 7: Commands and targets
TEMP MONITOR See description in Chapter 7: Commands and targets
UNIT NOT PROGRAMMED See description in Chapter 7: Commands and targets
TEMPERATURE TEMP MONITOR Asserted while the ambient temperature is greater than the maximum
MONITOR operating temperature (80°C)
USER- PUSHBUTTON 1 ON Pushbutton number 1 is in the “On” position
PROGRAMMABLE PUSHBUTTON 1 OFF Pushbutton number 1 is in the “Off” position
PUSHBUTTONS ANY PB ON Any of twelve pushbuttons is in the “On” position
PUSHBUTTON 2 to 12 Same set of operands as PUSHBUTTON 1

Some operands can be re-named by the user. These are the names of the breakers in the breaker control feature, the ID
(identification) of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name
or ID of any of these operands, the assigned name will appear in the relay list of operands. The default names are shown in
the FlexLogic™ operands table above.
The characteristics of the logic gates are tabulated below, and the operators available in FlexLogic™ are listed in the Flex-
Logic™ operators table.

GE Multilin G60 Generator Protection System 5-115


5.5 FLEXLOGIC™ 5 SETTINGS

Table 5–10: FLEXLOGIC™ GATE CHARACTERISTICS


GATES NUMBER OF INPUTS OUTPUT IS ‘1’ (= ON) IF...
NOT 1 input is ‘0’
OR 2 to 16 any input is ‘1’
AND 2 to 16 all inputs are ‘1’
NOR 2 to 16 all inputs are ‘0’
NAND 2 to 16 any input is ‘0’
XOR 2 only one input is ‘1’

Table 5–11: FLEXLOGIC™ OPERATORS


TYPE SYNTAX DESCRIPTION NOTES
Editor INSERT Insert a parameter in an equation list.
DELETE Delete a parameter from an equation list.
End END The first END encountered signifies the last entry in
the list of processed FlexLogic™ parameters.
One-shot POSITIVE ONE SHOT One shot that responds to a positive going edge. A ‘one shot’ refers to a single input gate
that generates a pulse in response to an
NEGATIVE ONE One shot that responds to a negative going edge. edge on the input. The output from a ‘one
SHOT shot’ is True (positive) for only one pass
DUAL ONE SHOT One shot that responds to both the positive and through the FlexLogic™ equation. There is
negative going edges. a maximum of 64 ‘one shots’.
Logic NOT Logical NOT Operates on the previous parameter.
gate
OR(2) 2 input OR gate Operates on the 2 previous parameters.
5 ↓
OR(16)

16 input OR gate

Operates on the 16 previous parameters.
AND(2) 2 input AND gate Operates on the 2 previous parameters.
↓ ↓ ↓
AND(16) 16 input AND gate Operates on the 16 previous parameters.
NOR(2) 2 input NOR gate Operates on the 2 previous parameters.
↓ ↓ ↓
NOR(16) 16 input NOR gate Operates on the 16 previous parameters.
NAND(2) 2 input NAND gate Operates on the 2 previous parameters.
↓ ↓ ↓
NAND(16) 16 input NAND gate Operates on the 16 previous parameters.
XOR(2) 2 input Exclusive OR gate Operates on the 2 previous parameters.
LATCH (S,R) Latch (set, reset): reset-dominant The parameter preceding LATCH(S,R) is
the reset input. The parameter preceding
the reset input is the set input.
Timer TIMER 1 Timer set with FlexLogic™ timer 1 settings. The timer is started by the preceding
↓ ↓ parameter. The output of the timer is
TIMER 32 Timer set with FlexLogic™ timer 32 settings. TIMER #.
Assign = Virt Op 1 Assigns previous FlexLogic™ operand to virtual The virtual output is set by the preceding
virtual ↓ output 1. parameter
output = Virt Op 96 ↓
Assigns previous FlexLogic™ operand to virtual
output 96.

5.5.2 FLEXLOGIC™ RULES

When forming a FlexLogic™ equation, the sequence in the linear array of parameters must follow these general rules:
1. Operands must precede the operator which uses the operands as inputs.
2. Operators have only one output. The output of an operator must be used to create a virtual output if it is to be used as
an input to two or more operators.
3. Assigning the output of an operator to a virtual output terminates the equation.
4. A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") may only be used
once. If this rule is broken, a syntax error will be declared.

5-116 G60 Generator Protection System GE Multilin


5 SETTINGS 5.5 FLEXLOGIC™

5.5.3 FLEXLOGIC™ EVALUATION

Each equation is evaluated in the order in which the parameters have been entered.
FlexLogic™ provides latches which by definition have a memory action, remaining in the set state after the
set input has been asserted. However, they are volatile; that is, they reset on the re-application of control
NOTE power.
When making changes to settings, all FlexLogic™ equations are re-compiled whenever any new setting
value is entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic™ during
testing, for example, it is suggested to power the unit down and then back up.

5.5.4 FLEXLOGIC™ EXAMPLE

This section provides an example of implementing logic for a typical application. The sequence of the steps is quite impor-
tant as it should minimize the work necessary to develop the relay settings. Note that the example presented in the figure
below is intended to demonstrate the procedure, not to solve a specific application situation.
In the example below, it is assumed that logic has already been programmed to produce virtual outputs 1 and 2, and is only
a part of the full set of equations used. When using FlexLogic™, it is important to make a note of each virtual output used –
a virtual output designation (1 to 96) can only be properly assigned once.

VIRTUAL OUTPUT 1
State=ON

VIRTUAL OUTPUT 2
Set
State=ON
LATCH
OR #1 Reset
VIRTUAL INPUT 1
State=ON
XOR
Timer 2 5
Time Delay Operate Output
OR #2
DIGITAL ELEMENT 1 on Dropout Relay H1
State=Pickup
(200 ms)

DIGITAL ELEMENT 2 Timer 1


State=Operated Time Delay
AND
on Pickup
(800 ms)
CONTACT INPUT H1c 827025A2.vsd
State=Closed

Figure 5–44: EXAMPLE LOGIC SCHEME


1. Inspect the example logic diagram to determine if the required logic can be implemented with the FlexLogic™ opera-
tors. If this is not possible, the logic must be altered until this condition is satisfied. Once this is done, count the inputs
to each gate to verify that the number of inputs does not exceed the FlexLogic™ limits, which is unlikely but possible. If
the number of inputs is too high, subdivide the inputs into multiple gates to produce an equivalent. For example, if 25
inputs to an AND gate are required, connect Inputs 1 through 16 to AND(16), 17 through 25 to AND(9), and the outputs
from these two gates to AND(2).
Inspect each operator between the initial operands and final virtual outputs to determine if the output from the operator
is used as an input to more than one following operator. If so, the operator output must be assigned as a virtual output.
For the example shown above, the output of the AND gate is used as an input to both OR#1 and Timer 1, and must
therefore be made a virtual output and assigned the next available number (i.e. Virtual Output 3). The final output must
also be assigned to a virtual output as virtual output 4, which will be programmed in the contact output section to oper-
ate relay H1 (that is, contact output H1).

GE Multilin G60 Generator Protection System 5-117


5.5 FLEXLOGIC™ 5 SETTINGS

Therefore, the required logic can be implemented with two FlexLogic™ equations with outputs of virtual output 3 and
virtual output 4 as shown below.

VIRTUAL OUTPUT 1
State=ON

VIRTUAL OUTPUT 2
Set
State=ON
LATCH
VIRTUAL INPUT 1 OR #1 Reset
State=ON Timer 2
XOR Time Delay
OR #2 VIRTUAL OUTPUT 4
DIGITAL ELEMENT 1 on Dropout
State=Pickup (200 ms)

DIGITAL ELEMENT 2 Timer 1


State=Operated Time Delay
AND
on Pickup
(800 ms)
CONTACT INPUT H1c
State=Closed VIRTUAL OUTPUT 3

827026A2.VSD

Figure 5–45: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS


2. Prepare a logic diagram for the equation to produce virtual output 3, as this output will be used as an operand in the
virtual output 4 equation (create the equation for every output that will be used as an operand first, so that when these
operands are required they will already have been evaluated and assigned to a specific virtual output). The logic for
virtual output 3 is shown below with the final output assigned.

DIGITAL ELEMENT 2
State=Operated

5 AND(2) VIRTUAL OUTPUT 3

CONTACT INPUT H1c


State=Closed

827027A2.VSD

Figure 5–46: LOGIC FOR VIRTUAL OUTPUT 3


3. Prepare a logic diagram for virtual output 4, replacing the logic ahead of virtual output 3 with a symbol identified as vir-
tual output 3, as shown below.

VIRTUAL OUTPUT 1
State=ON

VIRTUAL OUTPUT 2
Set
State=ON
LATCH
VIRTUAL INPUT 1 OR #1 Reset
State=ON Timer 2
XOR Time Delay VIRTUAL
OR #2
DIGITAL ELEMENT 1 on Dropout OUTPUT 4
State=Pickup
(200 ms)

Timer 1
VIRTUAL OUTPUT 3 Time Delay
State=ON on Pickup
(800 ms)
CONTACT INPUT H1c
State=Closed 827028A2.VSD

Figure 5–47: LOGIC FOR VIRTUAL OUTPUT 4


4. Program the FlexLogic™ equation for virtual output 3 by translating the logic into available FlexLogic™ parameters.
The equation is formed one parameter at a time until the required logic is complete. It is generally easier to start at the
output end of the equation and work back towards the input, as shown in the following steps. It is also recommended to
list operator inputs from bottom to top. For demonstration, the final output will be arbitrarily identified as parameter 99,
and each preceding parameter decremented by one in turn. Until accustomed to using FlexLogic™, it is suggested that
a worksheet with a series of cells marked with the arbitrary parameter numbers be prepared, as shown below.

5-118 G60 Generator Protection System GE Multilin


5 SETTINGS 5.5 FLEXLOGIC™

01
02
03
04
05

.....
97
98
99
827029A1.VSD

Figure 5–48: FLEXLOGIC™ WORKSHEET


5. Following the procedure outlined, start with parameter 99, as follows:
99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is
therefore "= Virt Op 3."
98: The gate preceding the output is an AND, which in this case requires two inputs. The operator for this gate is a 2-
input AND so the parameter is “AND(2)”. Note that FlexLogic™ rules require that the number of inputs to most
types of operators must be specified to identify the operands for the gate. As the 2-input AND will operate on the
two operands preceding it, these inputs must be specified, starting with the lower.
97: This lower input to the AND gate must be passed through an inverter (the NOT operator) so the next parameter is
“NOT”. The NOT operator acts upon the operand immediately preceding it, so specify the inverter input next.
5
96: The input to the NOT gate is to be contact input H1c. The ON state of a contact input can be programmed to be
set when the contact is either open or closed. Assume for this example the state is to be ON for a closed contact.
The operand is therefore “Cont Ip H1c On”.
95: The last step in the procedure is to specify the upper input to the AND gate, the operated state of digital element 2.
This operand is "DIG ELEM 2 OP".
Writing the parameters in numerical order can now form the equation for virtual output 3:
[95] DIG ELEM 2 OP
[96] Cont Ip H1c On
[97] NOT
[98] AND(2)
[99] = Virt Op 3
It is now possible to check that this selection of parameters will produce the required logic by converting the set of parame-
ters into a logic diagram. The result of this process is shown below, which is compared to the logic for virtual output 3 dia-
gram as a check.
FLEXLOGIC ENTRY n:
95 DIG ELEM 2 OP VIRTUAL
AND
FLEXLOGIC ENTRY n: OUTPUT 3
96 Cont Ip H1c On
FLEXLOGIC ENTRY n:
97 NOT
FLEXLOGIC ENTRY n:
98 AND (2)
FLEXLOGIC ENTRY n:
99 =Virt Op 3
827030A2.VSD

Figure 5–49: FLEXLOGIC™ EQUATION FOR VIRTUAL OUTPUT 3


6. Repeating the process described for virtual output 3, select the FlexLogic™ parameters for Virtual Output 4.
99: The final output of the equation is virtual output 4 which is parameter “= Virt Op 4".
98: The operator preceding the output is timer 2, which is operand “TIMER 2". Note that the settings required for the
timer are established in the timer programming section.

GE Multilin G60 Generator Protection System 5-119


5.5 FLEXLOGIC™ 5 SETTINGS

97: The operator preceding timer 2 is OR #2, a 3-input OR, which is parameter “OR(3)”.
96: The lowest input to OR #2 is operand “Cont Ip H1c On”.
95: The center input to OR #2 is operand “TIMER 1".
94: The input to timer 1 is operand “Virt Op 3 On".
93: The upper input to OR #2 is operand “LATCH (S,R)”.
92: There are two inputs to a latch, and the input immediately preceding the latch reset is OR #1, a 4-input OR, which
is parameter “OR(4)”.
91: The lowest input to OR #1 is operand “Virt Op 3 On".
90: The input just above the lowest input to OR #1 is operand “XOR(2)”.
89: The lower input to the XOR is operand “DIG ELEM 1 PKP”.
88: The upper input to the XOR is operand “Virt Ip 1 On".
87: The input just below the upper input to OR #1 is operand “Virt Op 2 On".
86: The upper input to OR #1 is operand “Virt Op 1 On".
85: The last parameter is used to set the latch, and is operand “Virt Op 4 On".
The equation for virtual output 4 is:
[85] Virt Op 4 On
[86] Virt Op 1 On
[87] Virt Op 2 On
[88] Virt Ip 1 On
5 [89]
[90]
DIG ELEM 1 PKP
XOR(2)
[91] Virt Op 3 On
[92] OR(4)
[93] LATCH (S,R)
[94] Virt Op 3 On
[95] TIMER 1
[96] Cont Ip H1c On
[97] OR(3)
[98] TIMER 2
[99] = Virt Op 4
It is now possible to check that the selection of parameters will produce the required logic by converting the set of parame-
ters into a logic diagram. The result of this process is shown below, which is compared to the logic for virtual output 4 dia-
gram as a check.

5-120 G60 Generator Protection System GE Multilin


5 SETTINGS 5.5 FLEXLOGIC™

FLEXLOGIC ENTRY n:
85 Virt Op 4 On
FLEXLOGIC ENTRY n:
86 Virt Op 1 On
FLEXLOGIC ENTRY n:
87 Virt Op 2 On
Set
FLEXLOGIC ENTRY n:
88 Virt Ip 1 On
LATCH
XOR OR Reset
FLEXLOGIC ENTRY n:
89 DIG ELEM 1 PKP
FLEXLOGIC ENTRY n:
90 XOR
FLEXLOGIC ENTRY n:
91 Virt Op 3 On VIRTUAL
OR T2
FLEXLOGIC ENTRY n: OUTPUT 4
92 OR (4)
FLEXLOGIC ENTRY n:
93 LATCH (S,R)
FLEXLOGIC ENTRY n:
94 Virt Op 3 On T1
FLEXLOGIC ENTRY n:
95 TIMER 1
FLEXLOGIC ENTRY n:
96 Cont Ip H1c On
FLEXLOGIC ENTRY n:
97 OR (3)
FLEXLOGIC ENTRY n:
98 TIMER 2
FLEXLOGIC ENTRY n:
99 =Virt Op 4 827031A2.VSD

Figure 5–50: FLEXLOGIC™ EQUATION FOR VIRTUAL OUTPUT 4


5
7. Now write the complete FlexLogic™ expression required to implement the logic, making an effort to assemble the
equation in an order where Virtual Outputs that will be used as inputs to operators are created before needed. In cases
where a lot of processing is required to perform logic, this may be difficult to achieve, but in most cases will not cause
problems as all logic is calculated at least four times per power frequency cycle. The possibility of a problem caused by
sequential processing emphasizes the necessity to test the performance of FlexLogic™ before it is placed in service.
In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown
below:
DIG ELEM 2 OP
Cont Ip H1c On
NOT
AND(2)
= Virt Op 3
Virt Op 4 On
Virt Op 1 On
Virt Op 2 On
Virt Ip 1 On
DIG ELEM 1 PKP
XOR(2)
Virt Op 3 On
OR(4)
LATCH (S,R)
Virt Op 3 On
TIMER 1
Cont Ip H1c On
OR(3)
TIMER 2
= Virt Op 4
END
In the expression above, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a
form of feedback, in this case, used to create a seal-in effect with the latch, and is correct.

GE Multilin G60 Generator Protection System 5-121


5.5 FLEXLOGIC™ 5 SETTINGS

8. The logic should always be tested after it is loaded into the relay, in the same fashion as has been used in the past.
Testing can be simplified by placing an "END" operator within the overall set of FlexLogic™ equations. The equations
will then only be evaluated up to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.

5.5.5 FLEXLOGIC™ EQUATION EDITOR

PATH: SETTINGS ÖØ FLEXLOGIC Ö FLEXLOGIC EQUATION EDITOR

„ FLEXLOGIC FLEXLOGIC ENTRY 1: Range: FlexLogic™ operands


„ EQUATION EDITOR END
FLEXLOGIC ENTRY 2: Range: FlexLogic™ operands
MESSAGE
END

FLEXLOGIC ENTRY 512: Range: FlexLogic™ operands


MESSAGE
END

There are 512 FlexLogic™ entries available, numbered from 1 to 512, with default END entry settings. If a "Disabled" Ele-
ment is selected as a FlexLogic™ entry, the associated state flag will never be set to ‘1’. The ‘+/–‘ key may be used when
editing FlexLogic™ equations from the keypad to quickly scan through the major parameter types.

5.5.6 FLEXLOGIC™ TIMERS

5 PATH: SETTINGS ÖØ FLEXLOGIC ÖØ FLEXLOGIC TIMERS Ö FLEXLOGIC TIMER 1(32)

„ FLEXLOGIC TIMER 1 Range: millisecond, second, minute


„ TIMER 1 TYPE: millisecond
TIMER 1 PICKUP Range: 0 to 60000 in steps of 1
MESSAGE
DELAY: 0
TIMER 1 DROPOUT Range: 0 to 60000 in steps of 1
MESSAGE
DELAY: 0

There are 32 identical FlexLogic™ timers available. These timers can be used as operators for FlexLogic™ equations.
• TIMER 1 TYPE: This setting is used to select the time measuring unit.
• TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0".
• TIMER 1 DROPOUT DELAY: Sets the time delay to dropout. If a dropout delay is not required, set this function to "0".

5-122 G60 Generator Protection System GE Multilin


5 SETTINGS 5.5 FLEXLOGIC™

5.5.7 FLEXELEMENTS™

PATH: SETTING ÖØ FLEXLOGIC ÖØ FLEXELEMENTS Ö FLEXELEMENT 1(16)

„ FLEXELEMENT 1 FLEXELEMENT 1 Range: Disabled, Enabled


„ FUNCTION: Disabled
FLEXELEMENT 1 NAME: Range: up to 6 alphanumeric characters
MESSAGE
FxE1
FLEXELEMENT 1 +IN: Range: Off, any analog actual value parameter
MESSAGE
Off
FLEXELEMENT 1 -IN: Range: Off, any analog actual value parameter
MESSAGE
Off
FLEXELEMENT 1 INPUT Range: Signed, Absolute
MESSAGE
MODE: Signed
FLEXELEMENT 1 COMP Range: Level, Delta
MESSAGE
MODE: Level
FLEXELEMENT 1 Range: Over, Under
MESSAGE
DIRECTION: Over
FLEXELEMENT 1 Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
PICKUP: 1.000 pu
FLEXELEMENT 1 Range: 0.1 to 50.0% in steps of 0.1
MESSAGE
HYSTERESIS: 3.0% 5
FLEXELEMENT 1 dt Range: milliseconds, seconds, minutes
MESSAGE
UNIT: milliseconds
FLEXELEMENT 1 dt: Range: 20 to 86400 in steps of 1
MESSAGE
20
FLEXELEMENT 1 PKP Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.000 s
FLEXELEMENT 1 RST Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.000 s
FLEXELEMENT 1 BLK: Range: FlexLogic™ operand
MESSAGE
Off
FLEXELEMENT 1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
FLEXELEMENT 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

A FlexElement™ is a universal comparator that can be used to monitor any analog actual value calculated by the relay or a
net difference of any two analog actual values of the same type. The effective operating signal could be treated as a signed
number or its absolute value could be used as per user's choice.
The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period
of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as
per user's choice.

GE Multilin G60 Generator Protection System 5-123


5.5 FLEXLOGIC™ 5 SETTINGS

SETTING
SETTINGS
FLEXELEMENT 1
FUNCTION: FLEXELEMENT 1 INPUT
MODE:
Enabled = 1
FLEXELEMENT 1 COMP
MODE:
Disabled = 0
FLEXELEMENT 1
DIRECTION:
SETTING
FLEXELEMENT 1 PICKUP:
FLEXELEMENT 1 BLK:
FLEXELEMENT 1 INPUT
AND HYSTERESIS:
Off = 0
FLEXELEMENT 1 dt UNIT: SETTINGS

SETTINGS FLEXELEMENT 1 PKP


FLEXELEMENT 1 dt: DELAY:
FLEXELEMENT 1 +IN: FLEXELEMENT 1 RST
RUN DELAY:
Actual Value FLEXLOGIC OPERANDS
+ tPKP
FLEXELEMENT 1 -IN: FxE 1 OP
- tRST
Actual Value FxE 1 DPO

FxE 1 PKP

ACTUAL VALUE

FlexElement 1 OpSig 842004A3.CDR

Figure 5–51: FLEXELEMENT™ SCHEME LOGIC


The FLEXELEMENT 1 +IN setting specifies the first (non-inverted) input to the FlexElement™. Zero is assumed as the input if
this setting is set to “Off”. For proper operation of the element at least one input must be selected. Otherwise, the element
5 will not assert its output operands.
This FLEXELEMENT 1 –IN setting specifies the second (inverted) input to the FlexElement™. Zero is assumed as the input if
this setting is set to “Off”. For proper operation of the element at least one input must be selected. Otherwise, the element
will not assert its output operands. This input should be used to invert the signal if needed for convenience, or to make the
element respond to a differential signal such as for a top-bottom oil temperature differential alarm. The element will not
operate if the two input signals are of different types, for example if one tries to use active power and phase angle to build
the effective operating signal.
The element responds directly to the differential signal if the FLEXELEMENT 1 INPUT MODE setting is set to “Signed”. The ele-
ment responds to the absolute value of the differential signal if this setting is set to “Absolute”. Sample applications for the
“Absolute” setting include monitoring the angular difference between two phasors with a symmetrical limit angle in both
directions; monitoring power regardless of its direction, or monitoring a trend regardless of whether the signal increases of
decreases.
The element responds directly to its operating signal – as defined by the FLEXELEMENT 1 +IN, FLEXELEMENT 1 –IN and FLEX-
ELEMENT 1 INPUT MODE settings – if the FLEXELEMENT 1 COMP MODE setting is set to “Level”. The element responds to the
rate of change of its operating signal if the FLEXELEMENT 1 COMP MODE setting is set to “Delta”. In this case the FLEXELE-
MENT 1 dt UNIT and FLEXELEMENT 1 dt settings specify how the rate of change is derived.

The FLEXELEMENT 1 DIRECTION setting enables the relay to respond to either high or low values of the operating signal. The
following figure explains the application of the FLEXELEMENT 1 DIRECTION, FLEXELEMENT 1 PICKUP and FLEXELEMENT 1 HYS-
TERESIS settings.

5-124 G60 Generator Protection System GE Multilin


5 SETTINGS 5.5 FLEXLOGIC™

FLEXELEMENT 1 PKP

FLEXELEMENT
DIRECTION = Over

HYSTERESIS = % of PICKUP

FlexElement 1 OpSig

PICKUP
FLEXELEMENT 1 PKP

FLEXELEMENT
DIRECTION = Under

HYSTERESIS = % of PICKUP

FlexElement 1 OpSig

PICKUP
842705A1.CDR

Figure 5–52: FLEXELEMENT™ DIRECTION, PICKUP, AND HYSTERESIS


In conjunction with the FLEXELEMENT 1 INPUT MODE setting the element could be programmed to provide two extra charac-
teristics as shown in the figure below.

FLEXELEMENT 1 PKP

FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
5
MODE = Signed;

FlexElement 1 OpSig

FLEXELEMENT 1 PKP

FLEXELEMENT
DIRECTION = Over;
FLEXELEMENT INPUT
MODE = Absolute;

FlexElement 1 OpSig

FLEXELEMENT 1 PKP

FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Signed;

FlexElement 1 OpSig

FLEXELEMENT 1 PKP

FLEXELEMENT
DIRECTION = Under;
FLEXELEMENT INPUT
MODE = Absolute;

FlexElement 1 OpSig
842706A2.CDR

Figure 5–53: FLEXELEMENT™ INPUT MODE SETTING

GE Multilin G60 Generator Protection System 5-125


5.5 FLEXLOGIC™ 5 SETTINGS

The FLEXELEMENT 1 PICKUP setting specifies the operating threshold for the effective operating signal of the element. If set
to “Over”, the element picks up when the operating signal exceeds the FLEXELEMENT 1 PICKUP value. If set to “Under”, the
element picks up when the operating signal falls below the FLEXELEMENT 1 PICKUP value.
The FLEXELEMENT 1 HYSTERESIS setting controls the element dropout. It should be noticed that both the operating signal
and the pickup threshold can be negative facilitating applications such as reverse power alarm protection. The FlexEle-
ment™ can be programmed to work with all analog actual values measured by the relay. The FLEXELEMENT 1 PICKUP set-
ting is entered in per-unit values using the following definitions of the base units:

Table 5–12: FLEXELEMENT™ BASE UNITS


dcmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
FIELD CURRENT IBASE = maximum value setting defined for the specific transducer input configured
FIELD GROUND CURRENT IBASE = 5 mA
FIELD GROUND FAULT BASE = 100%
LOCATION
FIELD GROUND INJECTED VBASE = 15 V
VOLTAGE
FIELD GROUND RESISTANCE RBASE = 250 KΩ
FIELD VOLTAGE VBASE = 500 V
FREQUENCY fBASE = 1 Hz
FREQUENCY RATE OF CHANGE df/dtBASE = 1 Hz/s
PHASE ANGLE ϕBASE = 360 degrees (see the UR angle referencing convention)
POWER FACTOR PFBASE = 1.00
5 RTDs BASE = 100°C
SENSITIVE DIR POWER PBASE = maximum value of 3 × VBASE × IBASE for the +IN and –IN inputs of the sources
(Sns Dir Power) configured for the sensitive power directional element(s).
SOURCE CURRENT IBASE = maximum nominal primary RMS value of the +IN and –IN inputs
SOURCE ENERGY EBASE = 10000 MWh or MVAh, respectively
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER PBASE = maximum value of VBASE × IBASE for the +IN and –IN inputs
SOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputs
STATOR DIFFERENTIAL IBASE = maximum primary RMS value of the +IN and –IN inputs
CURRENT (CT primary for source currents, and bus reference primary current for bus differential currents)
(Stator Diff Iar, Ibr, and Icr)
STATOR GROUND 3RD VBASE = Primary auxiliary voltage of the STATOR GROUND SOURCE
HARMONIC VOLTAGES
(Stator Gnd Vn/V0 3rd)
STATOR GROUND RESISTANCE RBASE = 10 KΩ
STATOR GROUND SUB- VBASE = nominal secondary voltage of auxiliary VT for the stator ground source
HARMONIC VOLTAGE
STATOR GROUND SUB- IBASE = ground CT primary current of stator ground source
HARMONIC CURRENT
STATOR RESTRAINING IBASE = maximum primary RMS value of the +IN and –IN inputs
CURRENT (CT primary for source currents, and bus reference primary current for bus differential currents)
(Stator Diff Iad, Ibd, and Icd)
SYNCHROCHECK VBASE = maximum primary RMS value of all the sources related to the +IN and –IN inputs
(Max Delta Volts)
VOLTS PER HERTZ BASE = 1.00 pu

The FLEXELEMENT 1 HYSTERESIS setting defines the pickup–dropout relation of the element by specifying the width of the
hysteresis loop as a percentage of the pickup value as shown in the FlexElement™ direction, pickup, and hysteresis dia-
gram.

5-126 G60 Generator Protection System GE Multilin


5 SETTINGS 5.5 FLEXLOGIC™

The FLEXELEMENT 1 DT UNIT setting specifies the time unit for the setting FLEXELEMENT 1 dt. This setting is applicable only if
FLEXELEMENT 1 COMP MODE is set to “Delta”. The FLEXELEMENT 1 DT setting specifies duration of the time interval for the
rate of change mode of operation. This setting is applicable only if FLEXELEMENT 1 COMP MODE is set to “Delta”.
This FLEXELEMENT 1 PKP DELAY setting specifies the pickup delay of the element. The FLEXELEMENT 1 RST DELAY setting
specifies the reset delay of the element.

5.5.8 NON-VOLATILE LATCHES

PATH: SETTINGS ÖØ FLEXLOGIC ÖØ NON-VOLATILE LATCHES Ö LATCH 1(16)

„ LATCH 1 LATCH 1 Range: Disabled, Enabled


„ FUNCTION: Disabled
LATCH 1 TYPE: Range: Reset Dominant, Set Dominant
MESSAGE
Reset Dominant
LATCH 1 SET: Range: FlexLogic™ operand
MESSAGE
Off
LATCH 1 RESET: Range: FlexLogic™ operand
MESSAGE
Off
LATCH 1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
LATCH 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The non-volatile latches provide a permanent logical flag that is stored safely and will not reset upon reboot after the relay
5
is powered down. Typical applications include sustaining operator commands or permanently block relay functions, such as
Autorecloser, until a deliberate interface action resets the latch. The settings element operation is described below:
• LATCH 1 TYPE: This setting characterizes Latch 1 to be Set- or Reset-dominant.
• LATCH 1 SET: If asserted, the specified FlexLogic™ operands 'sets' Latch 1.
• LATCH 1 RESET: If asserted, the specified FlexLogic™ operand 'resets' Latch 1.

SETTING
SETTING
LATCH N LATCH N LATCH N LATCH N LATCH N LATCH 1 FUNCTION:
TYPE SET RESET ON OFF
LATCH 1 TYPE:
Reset ON OFF ON OFF Disabled=0
Dominant Enabled=1 RUN
OFF OFF Previous Previous
State State
ON ON OFF ON SETTING

OFF ON OFF ON LATCH 1 SET:


FLEXLOGIC OPERANDS
Set ON OFF ON OFF
Dominant Off=0 SET LATCH 1 ON
ON ON ON OFF LATCH 1 OFF
OFF OFF Previous Previous SETTING
State State
LATCH 1 SET:
OFF ON OFF ON
Off=0 RESET
842005A1.CDR

Figure 5–54: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC

GE Multilin G60 Generator Protection System 5-127


5.6 GROUPED ELEMENTS 5 SETTINGS

5.6GROUPED ELEMENTS 5.6.1 OVERVIEW

Each protection element can be assigned up to six different sets of settings according to setting group designations 1 to 6.
The performance of these elements is defined by the active setting group at a given time. Multiple setting groups allow the
user to conveniently change protection settings for different operating situations (for example, altered power system config-
uration, season of the year, etc.). The active setting group can be preset or selected via the SETTING GROUPS menu (see the
Control elements section later in this chapter). See also the Introduction to elements section at the beginning of this chap-
ter.

5.6.2 SETTING GROUP

PATH: SETTINGS Ø GROUPED ELEMENTS Ö SETTING GROUP 1(6)

„ SETTING GROUP 1 „ DISTANCE


See page 5–129.
„ „
„ POWER SWING
MESSAGE See page 5–137.
„ DETECT
„ STATOR
MESSAGE See page 5–145.
„ DIFFERENTIAL
„ PHASE CURRENT
MESSAGE See page 5–148.
„
„ NEUTRAL CURRENT
MESSAGE See page 5–159.
„
5 MESSAGE
„ GROUND CURRENT
See page 5–166.
„
„ NEGATIVE SEQUENCE
MESSAGE See page 5–173.
„ CURRENT
„ GENERATOR
MESSAGE See page 5–177.
„ UNBALANCE
„ SPLIT PHASE
MESSAGE See page 5–179.
„
„ VOLTAGE ELEMENTS
MESSAGE See page 5–183.
„
„ LOSS OF
MESSAGE See page 5–194.
„ EXCITATION
„ ACCIDENTAL
MESSAGE See page 5-196.
„ ENERGIZATION
„ POWER
MESSAGE See page 5-198.
„
„ STATOR
MESSAGE See page 5-201.
„ GROUND
„ FIELD
MESSAGE See page 5-210.
„ GROUND

Each of the six setting group menus is identical. Setting group 1 (the default active group) automatically becomes active if
no other group is active (see the Control elements section for additional details).

5-128 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

5.6.3 DISTANCE

a) MAIN MENU
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE

„ DISTANCE DISTANCE Range: SRC 1, SRC 2, SRC 3, SRC 4


„ SOURCE: SRC 1
MEMORY Range: 5 to 25 cycles in steps of 1
MESSAGE
DURATION: 10 cycles
FORCE SELF-POLAR: Range: FlexLogic™ operand
MESSAGE
Off
FORCE MEM-POLAR: Range: FlexLogic™ operand
MESSAGE
Off
„ PHASE DISTANCE Z1
MESSAGE See page 5–130.
„
„ PHASE DISTANCE Z2
MESSAGE See page 5–130.
„
„ PHASE DISTANCE Z3
MESSAGE See page 5–130.
„

Four common settings are available for distance protection. The DISTANCE SOURCE identifies the signal source for all dis-
tance functions. The mho distance functions use a dynamic characteristic: the positive-sequence voltage – either memo-
rized or actual – is used as a polarizing signal. The memory voltage is also used by the built-in directional supervising
functions applied for both the mho and quad characteristics.
5
The MEMORY DURATION setting specifies the length of time a memorized positive-sequence voltage should be used in the
distance calculations. After this interval expires, the relay checks the magnitude of the actual positive-sequence voltage. If
it is higher than 10% of the nominal, the actual voltage is used, if lower – the memory voltage continues to be used.
The memory is established when the positive-sequence voltage stays above 80% of its nominal value for five power system
cycles. For this reason it is important to ensure that the nominal secondary voltage of the VT is entered correctly under the
SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE BANK menu.

Set MEMORY DURATION long enough to ensure stability on close-in reverse three-phase faults. For this purpose, the maxi-
mum fault clearing time (breaker fail time) in the substation should be considered. On the other hand, the MEMORY DURA-
TION cannot be too long as the power system may experience power swing conditions rotating the voltage and current
phasors slowly while the memory voltage is static, as frozen at the beginning of the fault. Keeping the memory in effect for
too long may eventually lead to incorrect operation of the distance functions.
The distance zones can be forced to become self-polarized through the FORCE SELF-POLAR setting. Any user-selected con-
dition (FlexLogic™ operand) can be configured to force self-polarization. When the selected operand is asserted (logic 1),
the distance functions become self-polarized regardless of other memory voltage logic conditions. When the selected oper-
and is de-asserted (logic 0), the distance functions follow other conditions of the memory voltage logic as shown below.
The distance zones can be forced to become memory-polarized through the FORCE MEM-POLAR setting. Any user-selected
condition (any FlexLogic™ operand) can be configured to force memory polarization. When the selected operand is
asserted (logic 1), the distance functions become memory-polarized regardless of the positive-sequence voltage magni-
tude at this time. When the selected operand is de-asserted (logic 0), the distance functions follow other conditions of the
memory voltage logic.
The FORCE SELF-POLAR and FORCE MEM-POLAR settings should never be asserted simultaneously. If this happens, the logic
will give higher priority to forcing self-polarization as indicated in the logic below. This is consistent with the overall philoso-
phy of distance memory polarization.
The memory polarization cannot be applied permanently but for a limited time only; the self-polarization may be
applied permanently and therefore should take higher priority.
NOTE

GE Multilin G60 Generator Protection System 5-129


5.6 GROUPED ELEMENTS 5 SETTINGS

SETTING
Force Memory Polarization
Update memory
Off = 0
AND RUN

SETTING
Memory duration
SETTING TIMER 0
Distance Source | V_1 | < 1.15 pu 5 cycles AND
= VA, Vrms_A | Vrms – | V | | < Vrms / 8 AND Treset
S Q
= VB, Vrms_B | Vrms – | V | | < Vrms / 8 0 AND
= VC, Vrms_C | Vrms – | V | | < Vrms / 8
= V_1 | V_1 | > 0.80 pu TIMER Use V_1 memory
6 cycles OR
= IA | IA | < 0.05 pu
| IB | < 0.05 pu
AND
R Use V_1
= IB OR
0
= IC | IC | < 0.05 pu AND
| V_1 | < 0.10 pu

SETTING
Force Self Polarization
Off = 0 827842A7.CDR

Figure 5–55: MEMORY VOLTAGE LOGIC

b) PHASE DISTANCE
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE ÖØ PHASE DISTANCE Z1(Z3)

„ PHASE DISTANCE Z1 PHS DIST Z1 Range: Disabled, Enabled


„ FUNCTION: Disabled
PHS DIST Z1 DIR: Range: Forward, Reverse, Non-directional
MESSAGE
Forward

5 MESSAGE
PHS DIST Z1
SHAPE: Mho
Range: Mho. This value is fixed and cannot be changed.

PHS DIST Z1 XFMR VOL Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1, Yd3,
MESSAGE Yd5, Yd7, Yd9, Yd11
CONNECTION: None
PHS DIST Z1 XFMR CUR Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1, Yd3,
MESSAGE Yd5, Yd7, Yd9, Yd11
CONNECTION: None
PHS DIST Z1 Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
REACH: 2.00 ohms
PHS DIST Z1 Range: 30 to 90° in steps of 1
MESSAGE
RCA: 85°
PHS DIST Z1 REV Range: 0.02 to 500.00 ohms in steps of 0.01
MESSAGE
REACH: 2.00 ohms
PHS DIST Z1 REV Range: 30 to 90° in steps of 1
MESSAGE
REACH RCA: 85°
PHS DIST Z1 Range: 30 to 90° in steps of 1
MESSAGE
COMP LIMIT: 90°
PHS DIST Z1 Range: 30 to 90° in steps of 1
MESSAGE
DIR RCA: 85°
PHS DIST Z1 Range: 30 to 90° in steps of 1
MESSAGE
DIR COMP LIMIT: 90°
PHS DIST Z1 Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
SUPV: 0.200 pu
PHS DIST Z1 VOLT Range: 0.000 to 5.000 pu in steps of 0.001
MESSAGE
LEVEL: 0.000 pu
PHS DIST Z1 Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.000 s

5-130 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

PHS DIST Z1 BLK: Range: FlexLogic™ operand


MESSAGE
Off
PHS DIST Z1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
PHS DIST Z1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The phase mho distance function uses a dynamic 100% memory-polarized mho characteristic with additional reactance,
directional, and overcurrent supervising characteristics. When set to “Non-directional”, the mho function becomes an offset
mho with the reverse reach controlled independently from the forward reach, and all the directional characteristics
removed.
Each phase distance zone is configured individually through its own setting menu. All of the settings can be independently
modified for each of the zones except:
1. The SIGNAL SOURCE setting (common for the distance elements of all zones as entered under SETTINGS ÖØ GROUPED
ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE).

2. The MEMORY DURATION setting (common for the distance elements of all zones as entered under SETTINGS ÖØ
GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ DISTANCE).

The common distance settings described earlier must be properly chosen for correct operation of the phase distance ele-
ments. Additional details may be found in chapter 8: Theory of operation.
Ensure that the PHASE VT SECONDARY VOLTAGE setting (see the SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ
VOLTAGE BANK menu) is set correctly to prevent improper operation of associated memory action.
WARNING

• PHS DIST Z1 DIR: All phase distance zones are reversible. The forward direction is defined by the PHS DIST Z1 RCA 5
setting, whereas the reverse direction is shifted 180° from that angle. The non-directional zone spans between the for-
ward reach impedance defined by the PHS DIST Z1 REACH and PHS DIST Z1 RCA settings, and the reverse reach imped-
ance defined by PHS DIST Z1 REV REACH and PHS DIST Z1 REV REACH RCA as illustrated below.

COMP LIMIT

DIR COMP LIMIT


H
REAC

DIR COMP LIMIT

DIR RCA
RCA

837720A1.CDR

Figure 5–56: DIRECTIONAL MHO DISTANCE CHARACTERISTIC

GE Multilin G60 Generator Protection System 5-131


5.6 GROUPED ELEMENTS 5 SETTINGS

COMP LIMIT

R E AC H
RCA

REV REACH
RCA

HE AC
REV R

837802A1.CDR

Figure 5–57: NON-DIRECTIONAL MHO DISTANCE CHARACTERISTIC

X X
5
RCA = 80o RCA = 80o
COMP LIMIT = 90o COMP LIMIT = 90o
DIR RCA = 80o DIR RCA = 80o
DIR COMP LIMIT = 90o DIR COMP LIMIT = 60o
H

H
REAC

REAC

R R

X RCA = 90o X RCA = 80o


COMP LIMIT = 90o COMP LIMIT = 60o
DIR RCA = 45o DIR RCA = 80o
DIR COMP LIMIT = 90o DIR COMP LIMIT = 60o
REACH

H
REAC

R R

837722A1.CDR

Figure 5–58: MHO DISTANCE CHARACTERISTIC SAMPLE SHAPES


• PHS DIST Z1 XFMR VOL CONNECTION: The phase distance elements can be applied to look through a three-phase
delta-wye or wye-delta power transformer. In addition, VTs and CTs could be located independently from one another
at different windings of the transformer. If the potential source is located at the correct side of the transformer, this set-
ting shall be set to “None”.

5-132 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

This setting specifies the location of the voltage source with respect to the involved power transformer in the direction
of the zone. The following figure illustrates the usage of this setting. In section (a), zone 1 is looking through a trans-
former from the delta into the wye winding. Therefore, the Z1 setting shall be set to “Dy11”. In section (b), Zone 3 is
looking through a transformer from the wye into the delta winding. Therefore, the Z3 setting shall be set to “Yd1”. The
zone is restricted by the potential point (location of the VTs) as illustrated in Figure (e).
• PHS DIST Z1 XFMR CUR CONNECTION: This setting specifies the location of the current source with respect to the
involved power transformer in the direction of the zone. In section (a) of the following figure, zone 1 is looking through
a transformer from the delta into the wye winding. Therefore, the Z1 setting shall be set to “Dy11”. In section (b), the
CTs are located at the same side as the read point. Therefore, the Z3 setting shall be set to “None”.
See the Theory of operation chapter for more details, and the Application of settings chapter for information on calcu-
lating distance reach settings in applications involving power transformers.

(a) (b)
delta wye, 330o lag delta wye, 330o lag

Z3 Z3

Z3 XFRM VOL CONNECTION = None Z3 XFRM VOL CONNECTION = Yd1


Z3 XFRM CUR CONNECTION = None Z3 XFRM CUR CONNECTION = None

Z1 Z1

Z1 XFRM VOL CONNECTION = Dy11 Z1 XFRM VOL CONNECTION = None


Z1 XFRM CUR CONNECTION = Dy11 Z1 XFRM CUR CONNECTION = Dy11

5
(c) (e)
delta wye, 330o lag

L1 L2

Z3 Zone 3
Zone 1
Z3 XFRM VOL CONNECTION = None
Z3 XFRM CUR CONNECTION = Yd1 ZL1 ZT ZL2

Z1

Z1 XFRM VOL CONNECTION = Dy11


Z1 XFRM CUR CONNECTION = None
830717A1.CDR

Figure 5–59: APPLICATIONS OF THE PH DIST XFMR VOL/CUR CONNECTION SETTINGS


• PHS DIST Z1 REACH: This setting defines the zone reach for the forward and reverse applications. In the non-direc-
tional applications, this setting defines the forward reach of the zone. The reverse reach impedance in non-directional
applications is set independently. The reach impedance is entered in secondary ohms. The reach impedance angle is
entered as the PHS DIST Z1 RCA setting.
• PHS DIST Z1 RCA: This setting specifies the characteristic angle (similar to the ‘maximum torque angle’ in previous
technologies) of the phase distance characteristic for the forward and reverse applications. In the non-directional appli-
cations, this setting defines the angle of the forward reach impedance. The reverse reach impedance in the non-direc-
tional applications is set independently. The setting is an angle of reach impedance as shown in the distance
characteristic figures shown earlier. This setting is independent from PHS DIST Z1 DIR RCA, the characteristic angle of an
extra directional supervising function.
• PHS DIST Z1 REV REACH: This setting defines the reverse reach of the zone set to non-directional (PHS DIST Z1 DIR
setting). The value must be entered in secondary ohms. This setting does not apply when the zone direction is set to
“Forward” or “Reverse”.

GE Multilin G60 Generator Protection System 5-133


5.6 GROUPED ELEMENTS 5 SETTINGS

• PHS DIST Z1 REV REACH RCA: This setting defines the angle of the reverse reach impedance if the zone is set to
non-directional (PHS DIST Z1 DIR setting). This setting does not apply when the zone direction is set to “Forward” or
“Reverse”.
• PHS DIST Z1 COMP LIMIT: This setting shapes the operating characteristic, producing the lens-type characteristic of
the mho function. The same limit angle applies to both the mho and supervising reactance comparators. This setting
improves loadability of the protected line.
• PHS DIST Z1 DIR RCA: This setting selects the characteristic angle (or maximum torque angle) of the directional
supervising function. The directional function is an extra supervising function as the dynamic mho characteristic itself is
a directional one. The directional function uses the memory voltage for polarization. This setting typically equals the
distance characteristic angle PHS DIST Z1 RCA.
• PHS DIST Z1 DIR COMP LIMIT: Selects the comparator limit angle for the directional supervising function.
• PHS DIST Z1 SUPV: The phase distance elements are supervised by the magnitude of the line-to-line current (fault
loop current used for the distance calculations). For convenience, 3 is accommodated by the pickup (that is, before
being used, the entered value of the threshold setting is multiplied by 3 ).
If the minimum fault current level is sufficient, the current supervision pickup should be set above maximum full load
current preventing maloperation under VT fuse fail conditions. This requirement may be difficult to meet for remote
faults at the end of zones 2 and above. If this is the case, the current supervision pickup would be set below the full
load current, but this may result in maloperation during fuse fail conditions.
• PHS DIST Z1 VOLT LEVEL: This setting is relevant for applications on series-compensated lines, or in general, if
series capacitors are located between the relaying point and a point where the zone shall not overreach. For plain
(non-compensated) lines, set to zero. Otherwise, the setting is entered in per unit of the phase VT bank configured
under the DISTANCE SOURCE. Effectively, this setting facilitates dynamic current-based reach reduction. In non-direc-
tional applications (PHS DIST Z1 DIR set to “Non-directional”), this setting applies only to the forward reach of the non-
5 directional zone. See chapters 8 and 9 for information on calculating this setting for series compensated lines.
• PHS DIST Z1 DELAY: This setting allows the user to delay operation of the distance elements and implement stepped
distance protection. The distance element timers for zones 2 and higher apply a short dropout delay to cope with faults
located close to the zone boundary when small oscillations in the voltages or currents could inadvertently reset the
timer. Zone 1 does not need any drop out delay since it is sealed-in by the presence of current.
• PHS DIST Z1 BLK: This setting enables the user to select a FlexLogic™ operand to block a given distance element.
VT fuse fail detection is one of the applications for this setting.

AND
OR

SETTING
PH DIST Z1 DELAY AND FLEXLOGIC OPERANDS
FLEXLOGIC OPERAND TPKP OR OR PH DIST Z1 OP
PH DIST Z1 PKP AB
0
FLEXLOGIC OPERAND TPKP
PH DIST Z1 PKP BC
0 AND
FLEXLOGIC OPERAND TPKP OR
PH DIST Z1 PKP CA
0 FLEXLOGIC OPERANDS
PH DIST Z1 OP AB
PH DIST Z1 OP BC
AND
FLEXLOGIC OPERANDS PH DIST Z1 OP CA
PH DIST Z1 SUPN IAB
AND
PH DIST Z1 SUPN IBC
PH DIST Z1 SUPN ICA
AND
OPEN POLE OP **

** D60, L60, and L90 only. Other UR-series models apply regular current seal-in for zone 1. 837017A8.CDR

Figure 5–60: PHASE DISTANCE ZONE 1 OP SCHEME

5-134 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

from the open pole element (D60, L60, and L90 only)
FLEXLOGIC OPERAND
OPEN POLE OP

FLEXLOGIC OPERAND SETTING FLEXLOGIC OPERAND


TIMER PH DIST Z2 DELAY AND PH DIST Z2 OP AB
PH DIST Z2 PKP AB
0 ms AND
TPKP
OR
OR
20 ms 0

FLEXLOGIC OPERAND SETTING FLEXLOGIC OPERAND


TIMER
PH DIST Z2 PKP BC PH DIST Z2 DELAY AND PH DIST Z2 OP BC
0 ms AND
OR TPKP
20 ms OR
0

FLEXLOGIC OPERAND
TIMER FLEXLOGIC OPERAND
PH DIST Z2 PKP CA SETTING
0 ms AND AND PH DIST Z2 OP CA
PH DIST Z2 DELAY
OR
from the trip output element OR
TPKP
20 ms
FLEXLOGIC OPERAND 0
FLEXLOGIC OPERAND
TRIP Z2 PH TMR INIT
OR PH DIST Z2 OP

837036A1.CDR

Figure 5–61: PHASE DISTANCE ZONE 2 OP SCHEME


For phase distance zone 2, there is a provision to start the zone timer with other distance zones or loop the pickup
flag to avoid prolonging phase distance zone 2 operation when the fault evolves from one type to another or
NOTE migrates from the initial zone to zone 2. Desired zones in the trip output function should be assigned to accomplish
this functionality.

FLEXLOGIC OPERAND
OPEN POLE OP **
5
TIMER SETTING
FLEXLOGIC OPERAND 0 ms PH DIST Z3 DELAY
AND
PH DIST Z3 PKP AB TPKP FLEXLOGIC OPERAND
20 ms OR PH DIST Z3 OP AB
0

TIMER SETTING
FLEXLOGIC OPERAND 0 ms PH DIST Z3 DELAY
AND
PH DIST Z3 PKP BC TPKP FLEXLOGIC OPERAND
20 ms OR PH DIST Z3 OP BC
0

TIMER SETTING
FLEXLOGIC OPERAND 0 ms PH DIST Z3 DELAY
AND
PH DIST Z3 PKP CA TPKP FLEXLOGIC OPERAND
20 ms OR PH DIST Z3 OP CA
0
FLEXLOGIC OPERAND
OR PH DIST Z3 OP

** D60, L60, and L90 only. 837020AA.CDR

Figure 5–62: PHASE DISTANCE ZONES 3 AND HIGHER OP SCHEME

GE Multilin G60 Generator Protection System 5-135


5.6 GROUPED ELEMENTS 5 SETTINGS

D60, L60, and L90 only


FLEXLOGIC OPERANDS
OPEN POLE BLK AB
OPEN POLE BLK BC
OPEN POLE BLK CA

SETTINGS
PH DIST Z1 DIR
PH DIST Z1 SHAPE
PH DIST Z1 XFMR
VOL CONNECTION
SETTING PH DIST Z1 XFMR
PH DIST Z1 FUNCTION CUR CONNECTION
Enabled = 1 PH DIST Z1 REACH
Disabled = 0 PH DIST Z1 RCA
PH DIST Z1 REV REACH
AND PH DIST Z1 REV REACH RCA
SETTING
PH DIST Z1 COMP LIMIT
PH DIST Z1 BLK
PH DIST Z1 QUAD RGT BLD
Off = 0
PH DIST Z1 QUAD RGT BLD RCA Quadrilateral
PH DIST Z1 QUAD LFT BLD characteristic only
PH DIST Z1 QUAD LFT BLD RCA
SETTING PH DIST Z1 VOLT LEVEL FLEXLOGIC OPERANDS
DISTANCE SOURCE RUN AND PH DIST Z1 PKP AB
IA-IB PH DIST Z1 DPO AB
A-B ELEMENT
IB-IC
IC-IA RUN FLEXLOGIC OPERANDS
VAG-VBG B-C ELEMENT AND PH DIST Z1 PKP BC
Wye
VTs

VBG-VCG PH DIST Z1 DPO BC


VCG-VAG RUN
VAB C-A ELEMENT FLEXLOGIC OPERANDS
Delta
VTs

VBC AND PH DIST Z1 PKP CA


VCA PH DIST Z1 DPO CA
V_1 MEMORY
I_1
TIMER FLEXLOGIC OPERAND
V_1 > 0.80 pu 1 cycle OR PH DIST Z1 PKP
OR

5 I_1 > 0.025 pu 1 cycle

SETTING
PHS DIST Z1 SUPV
RUN FLEXLOGIC OPERAND
| IA – IB | > 3 × Pickup PH DIST Z1 SUPN IAB

RUN FLEXLOGIC OPERAND


| IB – IC | > 3 × Pickup PH DIST Z1 SUPN IBC

RUN FLEXLOGIC OPERAND


| IC – IA | > 3 × Pickup PH DIST Z1 SUPN ICA
837002AL.CDR

Figure 5–63: PHASE DISTANCE SCHEME LOGIC

5-136 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

5.6.4 POWER SWING DETECT

PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ POWER SWING DETECT

„ POWER SWING POWER SWING Range: Disabled, Enabled


„ DETECT FUNCTION: Disabled
POWER SWING Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
POWER SWING Range: Mho Shape, Quad Shape
MESSAGE
SHAPE: Mho Shape
POWER SWING Range: Two Step, Three Step
MESSAGE
MODE: Two Step
POWER SWING Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
SUPV: 0.600 pu
POWER SWING FWD Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
REACH: 50.00 Ω
POWER SWING QUAD FWD Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
REACH MID: 60.00 Ω
POWER SWING QUAD FWD Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
REACH OUT: 70.00 Ω
POWER SWING FWD Range: 40 to 90° in steps of 1
MESSAGE
RCA: 75° 5
POWER SWING REV Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
REACH: 50.00 Ω
POWER SWING QUAD REV Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
REACH MID: 60.00 Ω
POWER SWING QUAD REV Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
REACH OUT: 70.00 Ω
POWER SWING REV Range: 40 to 90° in steps of 1
MESSAGE
RCA: 75°
POWER SWING OUTER Range: 40 to 140° in steps of 1
MESSAGE
LIMIT ANGLE: 120°
POWER SWING MIDDLE Range: 40 to 140° in steps of 1
MESSAGE
LIMIT ANGLE: 90°
POWER SWING INNER Range: 40 to 140° in steps of 1
MESSAGE
LIMIT ANGLE: 60°
POWER SWING OUTER Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
RGT BLD: 100.00 Ω
POWER SWING OUTER Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
LFT BLD: 100.00 Ω
POWER SWING MIDDLE Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
RGT BLD: 100.00 Ω
POWER SWING MIDDLE Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
LFT BLD: 100.00 Ω
POWER SWING INNER Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
RGT BLD: 100.00 Ω

GE Multilin G60 Generator Protection System 5-137


5.6 GROUPED ELEMENTS 5 SETTINGS

POWER SWING INNER Range: 0.10 to 500.00 ohms in steps of 0.01


MESSAGE
LFT BLD: 100.00 Ω
POWER SWING PICKUP Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY 1: 0.030 s
POWER SWING RESET Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY 1: 0.050 s
POWER SWING PICKUP Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY 2: 0.017 s
POWER SWING PICKUP Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY 3: 0.009 s
POWER SWING PICKUP Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY 4: 0.017 s
POWER SWING SEAL-IN Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.400 s
POWER SWING TRIP Range: Early, Delayed
MESSAGE
MODE: Delayed
POWER SWING BLK: Range: Flexlogic™ operand
MESSAGE
Off
POWER SWING Range: Self-Reset, Latched, Disabled
MESSAGE
TARGET: Self-Reset
5 MESSAGE
POWER SWING Range: Disabled, Enabled
EVENTS: Disabled

The power swing detect element provides both power swing blocking and out-of-step tripping functions. The element mea-
sures the positive-sequence apparent impedance and traces its locus with respect to either two or three user-selectable
operating characteristic boundaries. Upon detecting appropriate timing relations, the blocking and tripping indications are
given through FlexLogic™ operands. The element incorporates an adaptive disturbance detector. This function does not
trigger on power swings, but is capable of detecting faster disturbances – faults in particular – that may occur during power
swings. Operation of this dedicated disturbance detector is signaled via the POWER SWING 50DD operand.
The power swing detect element asserts two outputs intended for blocking selected protection elements on power swings:
POWER SWING BLOCK is a traditional signal that is safely asserted for the entire duration of the power swing, and POWER
SWING UN/BLOCK is established in the same way, but resets when an extra disturbance is detected during the power swing.
The POWER SWING UN/BLOCK operand may be used for blocking selected protection elements if the intent is to respond to
faults during power swing conditions.
Different protection elements respond differently to power swings. If tripping is required for faults during power swing condi-
tions, some elements may be blocked permanently (using the POWER SWING BLOCK operand), and others may be blocked
and dynamically unblocked upon fault detection (using the POWER SWING UN/BLOCK operand).
The operating characteristic and logic figures should be viewed along with the following discussion to develop an under-
standing of the operation of the element.
The power swing detect element operates in three-step or two-step mode:
• Three-step operation: The power swing blocking sequence essentially times the passage of the locus of the positive-
sequence impedance between the outer and the middle characteristic boundaries. If the locus enters the outer charac-
teristic (indicated by the POWER SWING OUTER FlexLogic™ operand) but stays outside the middle characteristic (indi-
cated by the POWER SWING MIDDLE FlexLogic™ operand) for an interval longer than POWER SWING PICKUP DELAY 1,
the power swing blocking signal (POWER SWING BLOCK FlexLogic™ operand) is established and sealed-in. The block-
ing signal resets when the locus leaves the outer characteristic, but not sooner than the POWER SWING RESET DELAY 1
time.
• Two-step operation: If the two-step mode is selected, the sequence is identical, but it is the outer and inner character-
istics that are used to time the power swing locus.

5-138 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

The out-of-step tripping feature operates as follows for three-step and two-step power swing detection modes:
• Three-step operation: The out-of-step trip sequence identifies unstable power swings by determining if the imped-
ance locus spends a finite time between the outer and middle characteristics and then a finite time between the middle
and inner characteristics. The first step is similar to the power swing blocking sequence. After timer POWER SWING
PICKUP DELAY 1 times out, latch 1 is set as long as the impedance stays within the outer characteristic.

If afterwards, at any time (given the impedance stays within the outer characteristic), the locus enters the middle char-
acteristic but stays outside the inner characteristic for a period of time defined as POWER SWING PICKUP DELAY 2, latch
2 is set as long as the impedance stays inside the outer characteristic. If afterwards, at any time (given the impedance
stays within the outer characteristic), the locus enters the inner characteristic and stays there for a period of time
defined as POWER SWING PICKUP DELAY 3, latch 2 is set as long as the impedance stays inside the outer characteristic;
the element is now ready to trip.
If the "Early" trip mode is selected, the POWER SWING TRIP operand is set immediately and sealed-in for the interval
set by the POWER SWING SEAL-IN DELAY. If the "Delayed" trip mode is selected, the element waits until the impedance
locus leaves the inner characteristic, then times out the POWER SWING PICKUP DELAY 2 and sets Latch 4; the element is
now ready to trip. The trip operand is set later, when the impedance locus leaves the outer characteristic.
• Two-step operation: The two-step mode of operation is similar to the three-step mode with two exceptions. First, the
initial stage monitors the time spent by the impedance locus between the outer and inner characteristics. Second, the
stage involving the POWER SWING PICKUP DELAY 2 timer is bypassed. It is up to the user to integrate the blocking
(POWER SWING BLOCK) and tripping (POWER SWING TRIP) FlexLogic™ operands with other protection functions and
output contacts in order to make this element fully operational.
The element can be set to use either lens (mho) or rectangular (quadrilateral) characteristics as illustrated below. When set
to “Mho”, the element applies the right and left blinders as well. If the blinders are not required, their settings should be set
high enough to effectively disable the blinders.
5
X

R
TE
OU
ACH
E
DL

FWD RE
ID
M

R
NE
IN

FW

LE
DR

NG
TA
CA

E I
GL LIM
AN LE
R
RE

IT DD
LIM MI
VR

R
CA

E
INN
H
REV REAC

OUTER LIMIT ANGLE

827843A2.CDR

Figure 5–64: POWER SWING DETECT MHO OPERATING CHARACTERISTICS

GE Multilin G60 Generator Protection System 5-139


5.6 GROUPED ELEMENTS 5 SETTINGS

842734A1.CDR

Figure 5–65: EFFECTS OF BLINDERS ON THE MHO CHARACTERISTICS

INNER LFT BL
D INNER RGT BL
D
MIDDLE LFT BL
ACH OUT
ACH MID

D MIDDLE RGT
BLD
OUTER LFT BL
D OUTER RGT BL
D
QUAD FWD RE
QUAD FWD RE
FWD REACH

FWD RCA

R
CH MID
REV REACH

H OUT
QUAD REV REA

AC
QUAD REV RE

842735A1.CDR

Figure 5–66: POWER SWING DETECT QUADRILATERAL OPERATING CHARACTERISTICS


The FlexLogic™ output operands for the power swing detect element are described below:
• The POWER SWING OUTER, POWER SWING MIDDLE, POWER SWING INNER, POWER SWING TMR2 PKP, POWER SWING
TMR3 PKP, and POWER SWING TMR4 PKP FlexLogic™ operands are auxiliary operands that could be used to facilitate
testing and special applications.
• The POWER SWING BLOCK FlexLogic™ operand shall be used to block selected protection elements such as distance
functions.

5-140 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

• The POWER SWING UN/BLOCK FlexLogic™ operand shall be used to block those protection elements that are intended
to be blocked under power swings, but subsequently unblocked should a fault occur after the power swing blocking
condition has been established.
• The POWER SWING 50DD FlexLogic™ operand indicates that an adaptive disturbance detector integrated with the ele-
ment has picked up. This operand will trigger on faults occurring during power swing conditions. This includes both
three-phase and single-pole-open conditions.
• The POWER SWING INCOMING FlexLogic™ operand indicates an unstable power swing with an incoming locus (the
locus enters the inner characteristic).
• The POWER SWING OUTGOING FlexLogic™ operand indicates an unstable power swing with an outgoing locus (the
locus leaving the outer characteristic). This operand can be used to count unstable swings and take certain action only
after pre-defined number of unstable power swings.
• The POWER SWING TRIP FlexLogic™ operand is a trip command.
The settings for the power swing detect element are described below:
• POWER SWING FUNCTION: This setting enables and disables the entire power swing detection element. The setting
applies to both power swing blocking and out-of-step tripping functions.
• POWER SWING SOURCE: The source setting identifies the signal source for both blocking and tripping functions.
• POWER SWING SHAPE: This setting selects the shapes (either “Mho” or “Quad”) of the outer, middle and, inner char-
acteristics of the power swing detect element. The operating principle is not affected. The “Mho” characteristics use the
left and right blinders.
• POWER SWING MODE: This setting selects between the two-step and three-step operating modes and applies to
both power swing blocking and out-of-step tripping functions. The three-step mode applies if there is enough space
between the maximum load impedances and distance characteristics of the relay that all three (outer, middle, and
inner) characteristics can be placed between the load and the distance characteristics. Whether the spans between 5
the outer and middle as well as the middle and inner characteristics are sufficient should be determined by analysis of
the fastest power swings expected in correlation with settings of the power swing timers.
The two-step mode uses only the outer and inner characteristics for both blocking and tripping functions. This leaves
more space in heavily loaded systems to place two power swing characteristics between the distance characteristics
and the maximum load, but allows for only one determination of the impedance trajectory.
• POWER SWING SUPV: A common overcurrent pickup level supervises all three power swing characteristics. The
supervision responds to the positive sequence current.
• POWER SWING FWD REACH: This setting specifies the forward reach of all three mho characteristics and the inner
quadrilateral characteristic. For a simple system consisting of a line and two equivalent sources, this reach should be
higher than the sum of the line and remote source positive-sequence impedances. Detailed transient stability studies
may be needed for complex systems in order to determine this setting. The angle of this reach impedance is specified
by the POWER SWING FWD RCA setting.
• POWER SWING QUAD FWD REACH MID: This setting specifies the forward reach of the middle quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING QUAD FWD REACH OUT: This setting specifies the forward reach of the outer quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING FWD RCA: This setting specifies the angle of the forward reach impedance for the mho characteris-
tics, angles of all the blinders, and both forward and reverse reach impedances of the quadrilateral characteristics.
• POWER SWING REV REACH: This setting specifies the reverse reach of all three mho characteristics and the inner
quadrilateral characteristic. For a simple system of a line and two equivalent sources, this reach should be higher than
the positive-sequence impedance of the local source. Detailed transient stability studies may be needed for complex
systems to determine this setting. The angle of this reach impedance is specified by the POWER SWING REV RCA setting
for “Mho”, and the POWER SWING FWD RCA setting for “Quad”.
• POWER SWING QUAD REV REACH MID: This setting specifies the reverse reach of the middle quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.

GE Multilin G60 Generator Protection System 5-141


5.6 GROUPED ELEMENTS 5 SETTINGS

• POWER SWING QUAD REV REACH OUT: This setting specifies the reverse reach of the outer quadrilateral charac-
teristic. The angle of this reach impedance is specified by the POWER SWING FWD RCA setting. The setting is not used if
the shape setting is “Mho”.
• POWER SWING REV RCA: This setting specifies the angle of the reverse reach impedance for the mho characteris-
tics. This setting applies to mho shapes only.
• POWER SWING OUTER LIMIT ANGLE: This setting defines the outer power swing characteristic. The convention
depicted in the Power swing detect characteristic diagram should be observed: values greater than 90° result in an
apple-shaped characteristic; values less than 90° result in a lens shaped characteristic. This angle must be selected in
consideration of the maximum expected load. If the maximum load angle is known, the outer limit angle should be
coordinated with a 20° security margin. Detailed studies may be needed for complex systems to determine this setting.
This setting applies to mho shapes only.
• POWER SWING MIDDLE LIMIT ANGLE: This setting defines the middle power swing detect characteristic. It is rele-
vant only for the 3-step mode. A typical value would be close to the average of the outer and inner limit angles. This
setting applies to mho shapes only.
• POWER SWING INNER LIMIT ANGLE: This setting defines the inner power swing detect characteristic. The inner
characteristic is used by the out-of-step tripping function: beyond the inner characteristic out-of-step trip action is defi-
nite (the actual trip may be delayed as per the TRIP MODE setting). Therefore, this angle must be selected in consider-
ation to the power swing angle beyond which the system becomes unstable and cannot recover.
The inner characteristic is also used by the power swing blocking function in the two-step mode. In this case, set this
angle large enough so that the characteristics of the distance elements are safely enclosed by the inner characteristic.
This setting applies to mho shapes only.
• POWER SWING OUTER, MIDDLE, and INNER RGT BLD: These settings specify the resistive reach of the right
blinder. The blinder applies to both “Mho” and “Quad” characteristics. Set these value high if no blinder is required for
5 the “Mho” characteristic.
• POWER SWING OUTER, MIDDLE, and INNER LFT BLD: These settings specify the resistive reach of the left blinder.
Enter a positive value; the relay automatically uses a negative value. The blinder applies to both “Mho” and “Quad”
characteristics. Set this value high if no blinder is required for the “Mho” characteristic.
• POWER SWING PICKUP DELAY 1: All the coordinating timers are related to each other and should be set to detect
the fastest expected power swing and produce out-of-step tripping in a secure manner. The timers should be set in
consideration to the power swing detect characteristics, mode of power swing detect operation and mode of out-of-
step tripping. This timer defines the interval that the impedance locus must spend between the outer and inner charac-
teristics (two-step operating mode), or between the outer and middle characteristics (three-step operating mode)
before the power swing blocking signal is established. This time delay must be set shorter than the time required for
the impedance locus to travel between the two selected characteristics during the fastest expected power swing. This
setting is relevant for both power swing blocking and out-of-step tripping.
• POWER SWING RESET DELAY 1: This setting defines the dropout delay for the power swing blocking signal. Detec-
tion of a condition requiring a block output sets latch 1 after PICKUP DELAY 1 time. When the impedance locus leaves
the outer characteristic, timer POWER SWING RESET DELAY 1 is started. When the timer times-out the latch is reset. This
setting should be selected to give extra security for the power swing blocking action.
• POWER SWING PICKUP DELAY 2: Controls the out-of-step tripping function in the three-step mode only. This timer
defines the interval the impedance locus must spend between the middle and inner characteristics before the second
step of the out-of-step tripping sequence is completed. This time delay must be set shorter than the time required for
the impedance locus to travel between the two characteristics during the fastest expected power swing.
• POWER SWING PICKUP DELAY 3: Controls the out-of-step tripping function only. It defines the interval the imped-
ance locus must spend within the inner characteristic before the last step of the out-of-step tripping sequence is com-
pleted and the element is armed to trip. The actual moment of tripping is controlled by the TRIP MODE setting. This time
delay is provided for extra security before the out-of-step trip action is executed.
• POWER SWING PICKUP DELAY 4: Controls the out-of-step tripping function in “Delayed” trip mode only. This timer
defines the interval the impedance locus must spend outside the inner characteristic but within the outer characteristic
before the element is armed for the delayed trip. The delayed trip occurs when the impedance leaves the outer charac-
teristic. This time delay is provided for extra security and should be set considering the fastest expected power swing.

5-142 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

• POWER SWING SEAL-IN DELAY: The out-of-step trip FlexLogic™ operand (POWER SWING TRIP) is sealed-in for the
specified period of time. The sealing-in is crucial in the delayed trip mode, as the original trip signal is a very short
pulse occurring when the impedance locus leaves the outer characteristic after the out-of-step sequence is completed.
• POWER SWING TRIP MODE: Selection of the “Early” trip mode results in an instantaneous trip after the last step in
the out-of-step tripping sequence is completed. The early trip mode will stress the circuit breakers as the currents at
that moment are high (the electromotive forces of the two equivalent systems are approximately 180° apart). Selection
of the “Delayed” trip mode results in a trip at the moment when the impedance locus leaves the outer characteristic.
delayed trip mode will relax the operating conditions for the breakers as the currents at that moment are low. The
selection should be made considering the capability of the breakers in the system.
• POWER SWING BLK: This setting specifies the FlexLogic™ operand used for blocking the out-of-step function only.
The power swing blocking function is operational all the time as long as the element is enabled. The blocking signal
resets the output POWER SWING TRIP operand but does not stop the out-of-step tripping sequence.

SETTINGS
POWER SWING POWER SWING OUTER
SHAPE: LIMIT ANGLE:
POWER SWING FWD POWER SWING MIDDLE
REACH: LIMIT ANGLE:
POWER SWING QUAD POWER SWING INNER
FWD REACH MID: LIMIT ANGLE:
POWER SWING QUAD POWER SWING OUTER
FWD REACH OUT: RGT BLD:
POWER SWING FWD POWER SWING OUTER
RCA: LFT BLD:
SETTING POWER SWING REV POWER SWING MIDDLE
POWER SWING REACH: RGT BLD:
FUNCTION: POWER SWING QUAD REV POWER SWING MIDDLE
Disabled = 0 REACH MID: LFT BLD:
Enabled = 1 POWER SWING QUAD REV POWER SWING INNER
REACH OUT: RGT BLD:
5
SETTING POWER SWING REV POWER SWING INNER
RCA: LFT BLD:
POWER SWING SOURCE:
RUN
FLEXLOGIC OPERAND
V_1 OUTER IMPEDANCE
AND POWER SWING OUTER
I_1 REGION
RUN
FLEXLOGIC OPERAND
MIDDLE IMPEDANCE
AND POWER SWING MIDDLE
REGION
RUN
FLEXLOGIC OPERAND
INNER IMPEDANCE
AND POWER SWING INNER
REGION

SETTING
POWER SWING
SUPV:
RUN

I_1 > PICKUP


827840A3.CDR

Figure 5–67: POWER SWING DETECT SCHEME LOGIC (1 of 3)

SETTING
POWER SWING FUNCTION:

Disabled = 0
TIMER
Enabled = 1
0

SETTING 10 cycles

POWER SWING SOURCE: RUN TIMER


FLEXLOGIC OPERAND
0
AND

I_0 | |I_0| - |I_0'|| > K_0


POWER SWING 50DD
4 cycles
OR

I_1 | |I_1| - |I_1'|| > K_1

I_2 | |I_2| - |I_2'|| > K_2

I_0, I_1, I_2 - present values


I_0', I_1', I_2' - half-a-cycle old values
K_0, K_2 - three times the average change over last power cycle 842008A1.CDR
K_1 - four times the average change over last power cycle

Figure 5–68: POWER SWING DETECT SCHEME LOGIC (2 of 3)

GE Multilin G60 Generator Protection System 5-143


5.6 GROUPED ELEMENTS 5 SETTINGS
POWER SWING OUTER
POWER SWING MIDDLE
POWER SWING INNER
FLEXLOGIC OPERANDS

SETTING SETTINGS
POWER SWING
POWER SWING MODE:
DELAY 1 PICKUP:
POWER SWING
3-step
AND DELAY 1 RESET:
FLEXLOGIC OPERANDS
tPKP
S Q1 POWER SWING BLOCK
tRST
POWER SWING UN/BLOCK
AND L1 S Q5
2-step FLEXLOGIC OPERAND
L5
R POWER SWING 50DD
R
OR
OR

SETTING
POWER SWING FLEXLOGIC OPERAND
DELAY 2 PICKUP:
POWER SWING TMR2 PKP
tPKP
AND S Q2
0
L2
R
3-step

2-step
FLEXLOGIC OPERAND
SETTING POWER SWING TMR3 PKP
POWER SWING
DELAY 3 PICKUP: FLEXLOGIC OPERAND
tPKP POWER SWING INCOMING

5 AND
0 S Q3

R
L3 SETTING
POWER SWING TRIP
MODE:

SETTING SETTING
POWER SWING POWER SWING
DELAY 4 PICKUP: Early
SEAL-IN DELAY:
tPKP 0
AND S Q4 FLEXLOGIC OPERAND
0 tRST
L4 AND POWER SWING TRIP
R AND
Delayed

SETTING FLEXLOGIC OPERAND


NOTE: POWER SWING TMR4 PKP
POWER SWING BLK:
L1 AND L4 LATCHES ARE SET DOMINANT
L2, L3 AND L5 LATCHES ARE RESET DOMINANT Off=0

FLEXLOGIC OPERAND
POWER SWING OUTGOING
827841A4.CDR

Figure 5–69: POWER SWING DETECT SCHEME LOGIC (3 of 3)

5-144 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

5.6.5 STATOR DIFFERENTIAL

PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ STATOR DIFFERENTIAL

„ STATOR STATOR DIFF Range: Disabled, Enabled


„ DIFFERENTIAL FUNCTION: Disabled
STATOR DIFF LINE Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
END SOURCE: SRC 1
STATOR DIFF NEUTRAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
END SOURCE: SRC 1
STATOR DIFF Range: 0.050 to 1.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.100 pu
STATOR DIFF Range: 1 to 100% in steps of 1
MESSAGE
SLOPE 1: 10 %
STATOR DIFF Range: 1.00 to 1.50 pu in steps of 0.01
MESSAGE
BREAK 1: 1.15 pu
STATOR DIFF Range: 1 to 100% in steps of 1
MESSAGE
SLOPE 2: 80 %
STATOR DIFF Range: 1.50 to 30.00 pu in steps of 0.01
MESSAGE
BREAK 2: 8.00 pu
STATOR DIFF Range: FlexLogic™ operand
MESSAGE
BLK: Off 5
STATOR DIFF Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
STATOR DIFF Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The stator differential protection element is intended for use on the stator windings of rotating machinery.
differential

Operate Block

Slope 2

Slope 1
Pickup
Break 1

Break 2

restraining

830735A1.CDR

Figure 5–70: STATOR DIFFERENTIAL CHARACTERISTIC


This element has a dual slope characteristic. The main purpose of the percent-slope characteristic is to prevent a maloper-
ation caused by unbalances between CTs during external faults. CT unbalances arise as a result of the following factors:
1. CT accuracy errors

GE Multilin G60 Generator Protection System 5-145


5.6 GROUPED ELEMENTS 5 SETTINGS

2. CT saturation
The characteristic allows for very sensitive settings when fault current is low and less sensitive settings when fault current is
high and CT performance may produce incorrect operate signals.
• STATOR DIFF LINE END SOURCE: This setting selects the source connected to CTs in the end of the machine stator
winding closest to the load and furthest from the winding neutral point. Both line and neutral-side CTs should be wired
to measure their currents in the same direction with respect to the neutral point of the winding.
• STATOR DIFF NEUTRAL END SOURCE: This setting selects the source connected to CTs in the end of the machine
stator winding furthest from the load and closest to the winding neutral point. Both line and neutral-side CTs should be
wired to measure their currents in the same direction with respect to the neutral point of the winding.
• STATOR DIFF PICKUP: This setting defines the minimum differential current required for operation. This setting is
based on the amount of differential current that might be seen under normal operating conditions. A setting of 0.1 to
0.3 pu is generally recommended.
• STATOR DIFF SLOPE 1: This setting is applicable for restraint currents from zero to STATOR DIFF BREAK 1, and defines
the ratio of differential to restraint current above which the element will operate. This slope is set to ensure sensitivity to
internal faults at normal operating current levels. The criteria for setting this slope is to allow for maximum expected CT
mismatch error when operating at the maximum permitted current. This maximum error is generally in the range of 5 to
10% of CT rating.
• STATOR DIFF BREAK 1: This setting defines the end of the Slope 1 region and the start of the transition region. It
should be set just above the maximum normal operating current level of the machine.
• STATOR DIFF SLOPE 2: This setting is applicable for restraint currents above the STATOR DIFF BREAK 2 setting when
the element is applied to generator stator windings. This slope is set to ensure stability under heavy external fault con-
ditions that could lead to high differential currents as a result of CT saturation. A setting of 80 to 100% is recom-
mended. The transition region (as shown on the characteristic plot) is a cubic spline, automatically calculated by the
5 relay to result in a smooth transition between STATOR DIFF SLOPE 1 and STATOR DIFF SLOPE 2 with no discontinuities.
• STATOR DIFF BREAK 2: This setting defines the end of the transition region and the start of the Slope 2 region. It
should be set to the level at which any of the protection CTs are expected to begin to saturate.
SETTING
STATOR DIFF SETTINGS
FUNCTION:
STATOR DIFF
Disabled = 0 PICKUP:
Enabled = 1
STATOR DIFF
SLOPE 1:
SETTING
AND STATOR DIFF
BREAK 1:
STATOR DIFF BLOCK:
STATOR DIFF
Off = 0 SLOPE 2:
STATOR DIFF
SETTING BREAK 2:
STATOR DIFF RUN
LINE END SOURCE: Differential Phasors FLEXLOGIC OPERANDS
Iad
IA Iad STATOR DIFF PKP A
IB Ibd STATOR DIFF DPO A
IC Icd Iar
RUN
DC Offset
Ibd FLEXLOGIC OPERANDS
Removal
D.F.T. STATOR DIFF PKP B
SETTING
and STATOR DIFF DPO B
STATOR DIFF Differential Ibr
NEUTRAL END SOURCE: and Restraint Restraint Phasors RUN
IA Iar Icd FLEXLOGIC OPERANDS
IB Ibr STATOR DIFF PKP C
IC Icr STATOR DIFF DPO C
Icr

Figure 5–71: STATOR DIFFERENTIAL SCHEME LOGIC


SATURATION DETECTION:
External faults near generators typically result in very large time constants of DC components in the fault currents. Also,
when energizing a step-up transformer, the inrush current being limited only by the machine impedance may be significant
and may last for a very long time. In order to provide additional security against maloperations during these events, the G60
incorporates saturation detection logic. When saturation is detected the element will make an additional check on the angle
between the neutral and output current. If this angle indicates an internal fault then tripping is permitted.

5-146 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

The saturation detector is implemented as a state machine (see below). "NORMAL" is the initial state of the machine. When
in "NORMAL" state, the saturation flag is not set (SAT = 0). The algorithm calculates the saturation condition, SC. If SC = 1
while the state machine is "NORMAL", the saturation detector goes into the "EXTERNAL FAULT" state and sets the satura-
tion flag (SAT = 1). The algorithm returns to the "NORMAL" state if the differential current is below the first slope, SL, for
more than 200 ms. When in the "EXTERNAL FAULT" state, the algorithm goes into the "EXTERNAL FAULT & CT SATU-
RATION" state if the differential flag is set (DIF = 1). When in the "EXTERNAL FAULT & CT SATURATION" state, the algo-
rithm keeps the saturation flag set (SAT = 1). The state machine returns to the "EXTERNAL FAULT" state if the differential
flag is reset (DIF = 0) for 100 ms.

NORMAL SC = (|ID| < SL x IR) and (IR > BL)


SAT := 0 where:
IR = restraint current
(|ID| < SL x IR) or (|ID| < PICKUP) ID = differential current
SC
AND DIF = stator differential pickup flag
(saturation condition)
(NOT (SC)) for 200 ms SL = slope 1 setting
BL = break point 1 setting
EXTERNAL FAULT PICKUP = pickup setting

SAT := 1

DIF = 0
for 100 ms

EXTERNAL FAULT
AND CT SATURATION

SAT := 1 5
830736A1.CDR

Figure 5–72: SATURATION DETECTION STATE MACHINE


PHASE COMPARISON PRINCIPLE:
The test for direction can be summarized by the following equation:
If ( I TS > B L or ( I TS > K ⋅ I R and I TS > 0.1 pu ) ) and ( I NS > B L or ( I NS > K ⋅ I R and I NS > 0.1 pu ) )
then DIR = abs ( ∠I TS – ∠I NS ) > 90° (EQ 5.7)

else DIR = 1
where: IR = restraining current, DIR = flag indicating that the phase comparison principle is satisfied
BL = breakpoint 1 setting, ITS, INS = current at the terminal and neutral sources, respectively
K = factory constant of 0.25

FLEXLOGIC OPERANDS
STATOR DIFF PKP A FLEXLOGIC OPERAND
STATOR DIFF SAT A AND STATOR DIFF OP A
OR
STATOR DIFF DIR A

FLEXLOGIC OPERANDS
STATOR DIFF PKP B FLEXLOGIC OPERAND
STATOR DIFF SAT B AND STATOR DIFF OP B
OR
STATOR DIFF DIR B

FLEXLOGIC OPERANDS
STATOR DIFF PKP C FLEXLOGIC OPERAND
STATOR DIFF SAT C AND STATOR DIFF OP C
OR
STATOR DIFF DIR C

FLEXLOGIC OPERAND
OR STATOR DIFF OP
842707A1.CDR

Figure 5–73: STATOR DIFFERENTIAL FINAL OUTPUT LOGIC

GE Multilin G60 Generator Protection System 5-147


5.6 GROUPED ELEMENTS 5 SETTINGS

5.6.6 PHASE CURRENT

a) MAIN MENU
PATH: SETTINGS Ø GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ PHASE CURRENT

„ PHASE CURRENT „ PHASE TOC1


See page 5–153.
„ „
„ PHASE IOC1
MESSAGE See page 5–155.
„
„ PHASE IOC2
MESSAGE See page 5–155.
„
„ PHASE
MESSAGE See page 5–157.
„ DIRECTIONAL 1

b) INVERSE TIME OVERCURRENT CHARACTERISTICS


The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I2t stan-
dard curve shapes. This allows for simplified coordination with downstream devices.
If none of these curve shapes is adequate, FlexCurves™ may be used to customize the inverse time curve characteristics.
The definite time curve is also an option that may be appropriate if only simple protection is required.

Table 5–13: OVERCURRENT CURVE TYPES


IEEE IEC GE TYPE IAC OTHER
5 IEEE Extremely Inverse IEC Curve A (BS142) IAC Extremely Inverse I2t
IEEE Very Inverse IEC Curve B (BS142) IAC Very Inverse FlexCurves™ A, B, C, and D
IEEE Moderately Inverse IEC Curve C (BS142) IAC Inverse Recloser Curves
IEC Short Inverse IAC Short Inverse Definite Time

A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (CURVE) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
to the time multiplier (TD MULTIPLIER) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal energy capacity memory variable. When this variable indi-
cates that the energy capacity has reached 100%, a time overcurrent element will operate. If less than 100% energy capac-
ity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value, the
variable must be reduced. Two methods of this resetting operation are available: “Instantaneous” and “Timed”. The “Instan-
taneous” selection is intended for applications with other relays, such as most static relays, which set the energy capacity
directly to zero when the current falls below the reset threshold. The “Timed” selection can be used where the relay must
coordinate with electromechanical relays.

5-148 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

IEEE CURVES:
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications
for extremely, very, and moderately inverse. The IEEE curves are derived from the formulae:

A tr
---------------------------------- + B -----------------------------------
-
T = TDM × ⎛ ---------------
I -⎞ p T TDM × 2
1 – ⎛ ---------------- ⎞
, = I (EQ 5.8)
⎝ I pickup⎠ – 1
RESET
⎝ I pickup ⎠

where: T = operate time (in seconds), TDM = Multiplier setting, I = input current, Ipickup = Pickup Current setting
A, B, p = constants, TRESET = reset time in seconds (assuming energy capacity is 100% and RESET is “Timed”),
tr = characteristic constant

Table 5–14: IEEE INVERSE TIME CURVE CONSTANTS


IEEE CURVE SHAPE A B P TR
IEEE Extremely Inverse 28.2 0.1217 2.0000 29.1
IEEE Very Inverse 19.61 0.491 2.0000 21.6
IEEE Moderately Inverse 0.0515 0.1140 0.02000 4.85

Table 5–15: IEEE CURVE TRIP TIMES (IN SECONDS)


MULTIPLIER CURRENT ( I / Ipickup)
(TDM)
1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
IEEE EXTREMELY INVERSE
0.5 11.341 4.761 1.823 1.001 0.648 0.464 0.355 0.285 0.237 0.203
1.0 22.682 9.522 3.647 2.002 1.297 0.927 0.709 0.569 0.474 0.407 5
2.0 45.363 19.043 7.293 4.003 2.593 1.855 1.418 1.139 0.948 0.813
4.0 90.727 38.087 14.587 8.007 5.187 3.710 2.837 2.277 1.897 1.626
6.0 136.090 57.130 21.880 12.010 7.780 5.564 4.255 3.416 2.845 2.439
8.0 181.454 76.174 29.174 16.014 10.374 7.419 5.674 4.555 3.794 3.252
10.0 226.817 95.217 36.467 20.017 12.967 9.274 7.092 5.693 4.742 4.065
IEEE VERY INVERSE
0.5 8.090 3.514 1.471 0.899 0.654 0.526 0.450 0.401 0.368 0.345
1.0 16.179 7.028 2.942 1.798 1.308 1.051 0.900 0.802 0.736 0.689
2.0 32.358 14.055 5.885 3.597 2.616 2.103 1.799 1.605 1.472 1.378
4.0 64.716 28.111 11.769 7.193 5.232 4.205 3.598 3.209 2.945 2.756
6.0 97.074 42.166 17.654 10.790 7.849 6.308 5.397 4.814 4.417 4.134
8.0 129.432 56.221 23.538 14.387 10.465 8.410 7.196 6.418 5.889 5.513
10.0 161.790 70.277 29.423 17.983 13.081 10.513 8.995 8.023 7.361 6.891
IEEE MODERATELY INVERSE
0.5 3.220 1.902 1.216 0.973 0.844 0.763 0.706 0.663 0.630 0.603
1.0 6.439 3.803 2.432 1.946 1.688 1.526 1.412 1.327 1.260 1.207
2.0 12.878 7.606 4.864 3.892 3.377 3.051 2.823 2.653 2.521 2.414
4.0 25.756 15.213 9.729 7.783 6.753 6.102 5.647 5.307 5.041 4.827
6.0 38.634 22.819 14.593 11.675 10.130 9.153 8.470 7.960 7.562 7.241
8.0 51.512 30.426 19.458 15.567 13.507 12.204 11.294 10.614 10.083 9.654
10.0 64.390 38.032 24.322 19.458 16.883 15.255 14.117 13.267 12.604 12.068

GE Multilin G60 Generator Protection System 5-149


5.6 GROUPED ELEMENTS 5 SETTINGS

IEC CURVES
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142. These
are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The formulae for these curves are:
K tr
--------------------------------------- --------------------------------------
-
T = TDM × ( I ⁄ I pickup ) E – 1 , T RESET = TDM × 1 – ( I ⁄ I 2 (EQ 5.9)
pickup )

where: T = operate time (in seconds), TDM = Multiplier setting, I = input current, Ipickup = Pickup Current setting, K, E =
constants, tr = characteristic constant, and TRESET = reset time in seconds (assuming energy capacity is 100%
and RESET is “Timed”)

Table 5–16: IEC (BS) INVERSE TIME CURVE CONSTANTS


IEC (BS) CURVE SHAPE K E TR
IEC Curve A (BS142) 0.140 0.020 9.7
IEC Curve B (BS142) 13.500 1.000 43.2
IEC Curve C (BS142) 80.000 2.000 58.2
IEC Short Inverse 0.050 0.040 0.500

Table 5–17: IEC CURVE TRIP TIMES (IN SECONDS)


MULTIPLIER CURRENT ( I / Ipickup)
(TDM)
1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
IEC CURVE A
0.05 0.860 0.501 0.315 0.249 0.214 0.192 0.176 0.165 0.156 0.149
5 0.10
0.20
1.719
3.439
1.003
2.006
0.630
1.260
0.498
0.996
0.428
0.856
0.384
0.767
0.353
0.706
0.330
0.659
0.312
0.623
0.297
0.594
0.40 6.878 4.012 2.521 1.992 1.712 1.535 1.411 1.319 1.247 1.188
0.60 10.317 6.017 3.781 2.988 2.568 2.302 2.117 1.978 1.870 1.782
0.80 13.755 8.023 5.042 3.984 3.424 3.070 2.822 2.637 2.493 2.376
1.00 17.194 10.029 6.302 4.980 4.280 3.837 3.528 3.297 3.116 2.971
IEC CURVE B
0.05 1.350 0.675 0.338 0.225 0.169 0.135 0.113 0.096 0.084 0.075
0.10 2.700 1.350 0.675 0.450 0.338 0.270 0.225 0.193 0.169 0.150
0.20 5.400 2.700 1.350 0.900 0.675 0.540 0.450 0.386 0.338 0.300
0.40 10.800 5.400 2.700 1.800 1.350 1.080 0.900 0.771 0.675 0.600
0.60 16.200 8.100 4.050 2.700 2.025 1.620 1.350 1.157 1.013 0.900
0.80 21.600 10.800 5.400 3.600 2.700 2.160 1.800 1.543 1.350 1.200
1.00 27.000 13.500 6.750 4.500 3.375 2.700 2.250 1.929 1.688 1.500
IEC CURVE C
0.05 3.200 1.333 0.500 0.267 0.167 0.114 0.083 0.063 0.050 0.040
0.10 6.400 2.667 1.000 0.533 0.333 0.229 0.167 0.127 0.100 0.081
0.20 12.800 5.333 2.000 1.067 0.667 0.457 0.333 0.254 0.200 0.162
0.40 25.600 10.667 4.000 2.133 1.333 0.914 0.667 0.508 0.400 0.323
0.60 38.400 16.000 6.000 3.200 2.000 1.371 1.000 0.762 0.600 0.485
0.80 51.200 21.333 8.000 4.267 2.667 1.829 1.333 1.016 0.800 0.646
1.00 64.000 26.667 10.000 5.333 3.333 2.286 1.667 1.270 1.000 0.808
IEC SHORT TIME
0.05 0.153 0.089 0.056 0.044 0.038 0.034 0.031 0.029 0.027 0.026
0.10 0.306 0.178 0.111 0.088 0.075 0.067 0.062 0.058 0.054 0.052
0.20 0.612 0.356 0.223 0.175 0.150 0.135 0.124 0.115 0.109 0.104
0.40 1.223 0.711 0.445 0.351 0.301 0.269 0.247 0.231 0.218 0.207
0.60 1.835 1.067 0.668 0.526 0.451 0.404 0.371 0.346 0.327 0.311
0.80 2.446 1.423 0.890 0.702 0.602 0.538 0.494 0.461 0.435 0.415
1.00 3.058 1.778 1.113 0.877 0.752 0.673 0.618 0.576 0.544 0.518

5-150 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

IAC CURVES:
The curves for the General Electric type IAC relay family are derived from the formulae:

⎛ B D E ⎞ tr
T = TDM × ⎜ A + ------------------------------ + -------------------------------------2- + -------------------------------------3-⎟ , T RESET = TDM × -------------------------------
- (EQ 5.10)
⎝ ( I ⁄ I ) – C ( ( I ⁄ I ) – C ) ( ( I ⁄ I ) – C ) ⎠ 2
pkp pkp pkp 1 – ( I ⁄ I pkp )

where: T = operate time (in seconds), TDM = Multiplier setting, I = Input current, Ipkp = Pickup Current setting, A to E =
constants, tr = characteristic constant, and TRESET = reset time in seconds (assuming energy capacity is 100%
and RESET is “Timed”)

Table 5–18: GE TYPE IAC INVERSE TIME CURVE CONSTANTS


IAC CURVE SHAPE A B C D E TR
IAC Extreme Inverse 0.0040 0.6379 0.6200 1.7872 0.2461 6.008
IAC Very Inverse 0.0900 0.7955 0.1000 –1.2885 7.9586 4.678
IAC Inverse 0.2078 0.8630 0.8000 –0.4180 0.1947 0.990
IAC Short Inverse 0.0428 0.0609 0.6200 –0.0010 0.0221 0.222

Table 5–19: IAC CURVE TRIP TIMES


MULTIPLIER CURRENT ( I / Ipickup)
(TDM)
1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
IAC EXTREMELY INVERSE
0.5 1.699 0.749 0.303 0.178 0.123 0.093 0.074 0.062 0.053 0.046
1.0
2.0
3.398
6.796
1.498
2.997
0.606
1.212
0.356
0.711
0.246
0.491
0.186
0.372
0.149
0.298
0.124
0.248
0.106
0.212
0.093
0.185
5
4.0 13.591 5.993 2.423 1.422 0.983 0.744 0.595 0.495 0.424 0.370
6.0 20.387 8.990 3.635 2.133 1.474 1.115 0.893 0.743 0.636 0.556
8.0 27.183 11.987 4.846 2.844 1.966 1.487 1.191 0.991 0.848 0.741
10.0 33.979 14.983 6.058 3.555 2.457 1.859 1.488 1.239 1.060 0.926
IAC VERY INVERSE
0.5 1.451 0.656 0.269 0.172 0.133 0.113 0.101 0.093 0.087 0.083
1.0 2.901 1.312 0.537 0.343 0.266 0.227 0.202 0.186 0.174 0.165
2.0 5.802 2.624 1.075 0.687 0.533 0.453 0.405 0.372 0.349 0.331
4.0 11.605 5.248 2.150 1.374 1.065 0.906 0.810 0.745 0.698 0.662
6.0 17.407 7.872 3.225 2.061 1.598 1.359 1.215 1.117 1.046 0.992
8.0 23.209 10.497 4.299 2.747 2.131 1.813 1.620 1.490 1.395 1.323
10.0 29.012 13.121 5.374 3.434 2.663 2.266 2.025 1.862 1.744 1.654
IAC INVERSE
0.5 0.578 0.375 0.266 0.221 0.196 0.180 0.168 0.160 0.154 0.148
1.0 1.155 0.749 0.532 0.443 0.392 0.360 0.337 0.320 0.307 0.297
2.0 2.310 1.499 1.064 0.885 0.784 0.719 0.674 0.640 0.614 0.594
4.0 4.621 2.997 2.128 1.770 1.569 1.439 1.348 1.280 1.229 1.188
6.0 6.931 4.496 3.192 2.656 2.353 2.158 2.022 1.921 1.843 1.781
8.0 9.242 5.995 4.256 3.541 3.138 2.878 2.695 2.561 2.457 2.375
10.0 11.552 7.494 5.320 4.426 3.922 3.597 3.369 3.201 3.072 2.969
IAC SHORT INVERSE
0.5 0.072 0.047 0.035 0.031 0.028 0.027 0.026 0.026 0.025 0.025
1.0 0.143 0.095 0.070 0.061 0.057 0.054 0.052 0.051 0.050 0.049
2.0 0.286 0.190 0.140 0.123 0.114 0.108 0.105 0.102 0.100 0.099
4.0 0.573 0.379 0.279 0.245 0.228 0.217 0.210 0.204 0.200 0.197
6.0 0.859 0.569 0.419 0.368 0.341 0.325 0.314 0.307 0.301 0.296
8.0 1.145 0.759 0.559 0.490 0.455 0.434 0.419 0.409 0.401 0.394
10.0 1.431 0.948 0.699 0.613 0.569 0.542 0.524 0.511 0.501 0.493

GE Multilin G60 Generator Protection System 5-151


5.6 GROUPED ELEMENTS 5 SETTINGS

I2t CURVES:
The curves for the I2t are derived from the formulae:

100 100
-------------------------- ----------------------------
T = TDM × ⎛ ---------------
I ⎞ 2 , T RESET = TDM × ⎛ I ⎞ –2
- ---------------- (EQ 5.11)
⎝ I pickup ⎠ ⎝ I pickup ⎠

where: T = Operate Time (sec.); TDM = Multiplier Setting; I = Input Current; Ipickup = Pickup Current Setting;
TRESET = Reset Time in sec. (assuming energy capacity is 100% and RESET: Timed)

Table 5–20: I2T CURVE TRIP TIMES


MULTIPLIER CURRENT ( I / Ipickup)
(TDM)
1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
0.01 0.44 0.25 0.11 0.06 0.04 0.03 0.02 0.02 0.01 0.01
0.10 4.44 2.50 1.11 0.63 0.40 0.28 0.20 0.16 0.12 0.10
1.00 44.44 25.00 11.11 6.25 4.00 2.78 2.04 1.56 1.23 1.00
10.00 444.44 250.00 111.11 62.50 40.00 27.78 20.41 15.63 12.35 10.00
100.00 4444.4 2500.0 1111.1 625.00 400.00 277.78 204.08 156.25 123.46 100.00
600.00 26666.7 15000.0 6666.7 3750.0 2400.0 1666.7 1224.5 937.50 740.74 600.00

FLEXCURVES™:
The custom FlexCurves™ are described in detail in the FlexCurves™ section of this chapter. The curve shapes for the
FlexCurves™ are derived from the formulae:

5 T = TDM × FlexCurve Time at ⎛⎝ ----------------⎞⎠


I
when ⎛⎝ ----------------⎞⎠ ≥ 1.00
I
(EQ 5.12)
I pickup I pickup

T RESET = TDM × FlexCurve Time at ⎛⎝ ----------------⎞⎠ when ⎛⎝ ----------------⎞⎠ ≤ 0.98


I I
(EQ 5.13)
I pickup I pickup

where: T = Operate Time (sec.), TDM = Multiplier setting


I = Input Current, Ipickup = Pickup Current setting
TRESET = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)
DEFINITE TIME CURVE:
The Definite Time curve shape operates as soon as the pickup level is exceeded for a specified period of time. The base
definite time curve delay is in seconds. The curve multiplier of 0.00 to 600.00 makes this delay adjustable from instanta-
neous to 600.00 seconds in steps of 10 ms.
T = TDM in seconds, when I > I pickup (EQ 5.14)

T RESET = TDM in seconds (EQ 5.15)

where: T = Operate Time (sec.), TDM = Multiplier setting


I = Input Current, Ipickup = Pickup Current setting
TRESET = Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)
RECLOSER CURVES:
The G60 uses the FlexCurve™ feature to facilitate programming of 41 recloser curves. Please refer to the FlexCurve™
section in this chapter for additional details.

5-152 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

c) PHASE TIME OVERCURRENT (ANSI 51P)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö PHASE CURRENT Ö PHASE TOC1

„ PHASE TOC1 PHASE TOC1 Range: Disabled, Enabled


„ FUNCTION: Disabled
PHASE TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
PHASE TOC1 Range: Phasor, RMS
MESSAGE
INPUT: Phasor
PHASE TOC1 Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 1.000 pu
PHASE TOC1 Range: See Overcurrent Curve Types table
MESSAGE
CURVE: IEEE Mod Inv
PHASE TOC1 Range: 0.00 to 600.00 in steps of 0.01
MESSAGE
TD MULTIPLIER: 1.00
PHASE TOC1 Range: Instantaneous, Timed
MESSAGE
RESET: Instantaneous
PHASE TOC1 VOLTAGE Range: Disabled, Enabled
MESSAGE
RESTRAINT: Disabled
PHASE TOC1 BLOCK A: Range: FlexLogic™ operand
MESSAGE
Off
PHASE TOC1 BLOCK B: Range: FlexLogic™ operand 5
MESSAGE
Off
PHASE TOC1 BLOCK C: Range: FlexLogic™ operand
MESSAGE
Off
PHASE TOC1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
PHASE TOC1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The phase time overcurrent element can provide a desired time-delay operating characteristic versus the applied current or
be used as a simple definite time element. The phase current input quantities may be programmed as fundamental phasor
magnitude or total waveform RMS magnitude as required by the application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to the Inverse Time overcurrent
curves characteristic sub-section earlier for details on curve setup, trip times, and reset operation). When the element is
blocked, the time accumulator will reset according to the reset characteristic. For example, if the element reset characteris-
tic is set to “Instantaneous” and the element is blocked, the time accumulator will be cleared immediately.
The PHASE TOC1 PICKUP setting can be dynamically reduced by a voltage restraint feature (when enabled). This is accom-
plished via the multipliers (Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic curve (see
the figure below); the pickup level is calculated as ‘Mvr’ times the PHASE TOC1 PICKUP setting. If the voltage restraint feature
is disabled, the pickup level always remains at the setting value.

GE Multilin G60 Generator Protection System 5-153


5.6 GROUPED ELEMENTS 5 SETTINGS

Multiplier for Pickup Current


1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Phase-Phase Voltage ÷ VT Nominal Phase-phase Voltage
818784A4.CDR

Figure 5–74: PHASE TIME OVERCURRENT VOLTAGE RESTRAINT CHARACTERISTIC

SETTING
PHASE TOC1
FUNCTION:
Disabled=0
Enabled=1

SETTING
PHASE TOC1
BLOCK-A :
Off=0

5 SETTING
PHASE TOC1
BLOCK-B:
Off=0
SETTING
SETTING
PHASE TOC1
PHASE TOC1 INPUT:
BLOCK-C:
PHASE TOC1
Off=0 PICKUP:
PHASE TOC1
SETTING CURVE:
PHASE TOC1 PHASE TOC1
SOURCE: TD MULTIPLIER:
IA
PHASE TOC1
IB RESET: FLEXLOGIC OPERAND
IC AND RUN PHASE TOC1 A PKP
IA PICKUP
Seq=ABC Seq=ACB PHASE TOC1 A DPO
MULTIPLY INPUTS
RUN
t PHASE TOC1 A OP
VAB VAC Set
Calculate Multiplier Set Pickup AND RUN PHASE TOC1 B PKP
RUN
Multiplier-Phase A IB PICKUP
Set PHASE TOC1 B DPO
VBC VBA Set Pickup
Calculate Multiplier t PHASE TOC1 B OP
RUN
Multiplier-Phase B
Set AND RUN PHASE TOC1 C PKP
VCA VCB IC PICKUP
Calculate Multiplier Set Pickup PHASE TOC1 C DPO
Multiplier-Phase C
t PHASE TOC1 C OP
SETTING OR PHASE TOC1 PKP
PHASE TOC1 VOLT
RESTRAINT: OR PHASE TOC1 OP
Enabled

AND PHASE TOC1 DPO

827072A4.CDR

Figure 5–75: PHASE TIME OVERCURRENT 1 SCHEME LOGIC

5-154 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

d) PHASE INSTANTANEOUS OVERCURRENT (ANSI 50P)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö PHASE CURRENT Ö PHASE IOC 1(2)

„ PHASE IOC1 PHASE IOC1 Range: Disabled, Enabled


„ FUNCTION: Disabled
PHASE IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
PHASE IOC1 Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 1.000 pu
PHASE IOC1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.00 s
PHASE IOC1 RESET Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.00 s
PHASE IOC1 BLOCK A: Range: FlexLogic™ operand
MESSAGE
Off
PHASE IOC1 BLOCK B: Range: FlexLogic™ operand
MESSAGE
Off
PHASE IOC1 BLOCK C: Range: FlexLogic™ operand
MESSAGE
Off
PHASE IOC1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
PHASE IOC1 Range: Disabled, Enabled 5
MESSAGE
EVENTS: Disabled

The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude. The phase instantaneous overcurrent timing
curves are shown below for form-A contacts in a 60 Hz system.

GE Multilin G60 Generator Protection System 5-155


5.6 GROUPED ELEMENTS 5 SETTINGS

35

30

25

20
Milliseconds

15

Maximum

10 Minimum

0
1.05 1.1 1.2 1.5 2 5 10 15 20

5 Multiple of pickup 843807A1.CDR

Figure 5–76: PHASE INSTANTANEOUS OVERCURRENT TIMING CURVES

SETTING SETTING SETTINGS FLEXLOGIC


PHASE IOC1 PHASE IOC1 PHASE IOC1 OPERANDS
FUNCTION: PICKUP: PICKUPDELAY: PHASE IOC1 A PKP
Enabled = 1 AND RUN PHASE IOC1 RESET
Disabled = 0 DELAY: PHASE IOC1 A DPO
IA PICKUP tPKP
SETTING tRST PHASE IOC1 B PKP
AND RUN
PHASE IOC1 PHASE IOC1 B DPO
SOURCE: tPKP
IB PICKUP
IA tRST PHASE IOC1 C PKP
AND RUN
IB
tPKP PHASE IOC1 C DPO
IC tRST
IC PICKUP
PHASE IOC1 A OP

SETTING PHASE IOC1 B OP


PHASE IOC1
BLOCK-A: PHASE IOC1 C OP
Off = 0
OR PHASE IOC1 PKP

SETTING OR PHASE IOC1 OP


PHASE IOC1
BLOCK-B:
AND PHASE IOC1 DPO
Off = 0

SETTING
827033A6.VSD
PHASE IOC1
BLOCK-C:
Off = 0

Figure 5–77: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC

5-156 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

e) PHASE DIRECTIONAL OVERCURRENT (ANSI 67P)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö PHASE CURRENT Ö PHASE DIRECTIONAL 1

„ PHASE PHASE DIR 1 Range: Disabled, Enabled


„ DIRECTIONAL 1 FUNCTION: Disabled
PHASE DIR 1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
PHASE DIR 1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
PHASE DIR 1 Range: 0 to 359° in steps of 1
MESSAGE
ECA: 30
PHASE DIR POL V1 Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
THRESHOLD: 0.700 pu
PHASE DIR 1 BLOCK Range: No, Yes
MESSAGE
WHEN V MEM EXP: No
PHASE DIR 1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
PHASE DIR 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The phase directional elements (one for each of phases A, B, and C) determine the phase current flow direction for steady
state and fault conditions and can be used to control the operation of the phase overcurrent elements via the BLOCK inputs
of these elements. 5
S
UT 0
TP
OU
–90°

VAG (Unfaulted) Fault angle


set at 60° Lag

VPol

VAG(Faulted) IA
ECA
set at 30°

VBC

VBC
VCG VBG +90°

Phasors for Phase A Polarization:

VPol = VBC × (1/_ECA) = polarizing voltage


IA = operating current
ECA = Element Characteristic Angle at 30° 827800A2.CDR

Figure 5–78: PHASE A DIRECTIONAL POLARIZATION


This element is intended to apply a block signal to an overcurrent element to prevent an operation when current is flowing
in a particular direction. The direction of current flow is determined by measuring the phase angle between the current from
the phase CTs and the line-line voltage from the VTs, based on the 90° or quadrature connection. If there is a requirement
to supervise overcurrent elements for flows in opposite directions, such as can happen through a bus-tie breaker, two
phase directional elements should be programmed with opposite element characteristic angle (ECA) settings.

GE Multilin G60 Generator Protection System 5-157


5.6 GROUPED ELEMENTS 5 SETTINGS

To increase security for three phase faults very close to the VTs used to measure the polarizing voltage, a voltage memory
feature is incorporated. This feature stores the polarizing voltage the moment before the voltage collapses, and uses it to
determine direction. The voltage memory remains valid for one second after the voltage has collapsed.
The main component of the phase directional element is the phase angle comparator with two inputs: the operating signal
(phase current) and the polarizing signal (the line voltage, shifted in the leading direction by the characteristic angle, ECA).
The following table shows the operating and polarizing signals used for phase directional control:
PHASE OPERATING POLARIZING SIGNAL Vpol
SIGNAL
ABC PHASE SEQUENCE ACB PHASE SEQUENCE
A angle of IA angle of VBC × (1∠ECA) angle of VCB × (1∠ECA)
B angle of IB angle of VCA × (1∠ECA) angle of VAC × 1∠ECA)
C angle of IC angle of VAB × (1∠ECA) angle of VBA × (1∠ECA)

MODE OF OPERATION:
• When the function is “Disabled”, or the operating current is below 5% × CT nominal, the element output is “0”.
• When the function is “Enabled”, the operating current is above 5% × CT nominal, and the polarizing voltage is above
the PRODUCT SETUP ÖØ DISPLAY PROPERTIES ÖØ VOLTAGE CUT-OFF LEVEL value, the element output is dependent on
the phase angle between the operating and polarizing signals:
– The element output is logic “0” when the operating current is within polarizing voltage ±90°.
– For all other angles, the element output is logic “1”.
• Once the voltage memory has expired, the phase overcurrent elements under directional control can be set to block or
trip on overcurrent as follows:

5 – When BLOCK WHEN V MEM EXP is set to “Yes”, the directional element will block the operation of any phase
overcurrent element under directional control when voltage memory expires.
– When BLOCK WHEN V MEM EXP is set to “No”, the directional element allows tripping of phase overcurrent elements
under directional control when voltage memory expires.
In all cases, directional blocking will be permitted to resume when the polarizing voltage becomes greater than the ‘polariz-
ing voltage threshold’.
SETTINGS:
• PHASE DIR 1 SIGNAL SOURCE: This setting is used to select the source for the operating and polarizing signals.
The operating current for the phase directional element is the phase current for the selected current source. The polar-
izing voltage is the line voltage from the phase VTs, based on the 90° or ‘quadrature’ connection and shifted in the
leading direction by the element characteristic angle (ECA).
• PHASE DIR 1 ECA: This setting is used to select the element characteristic angle, i.e. the angle by which the polariz-
ing voltage is shifted in the leading direction to achieve dependable operation. In the design of the UR-series elements,
a block is applied to an element by asserting logic 1 at the blocking input. This element should be programmed via the
ECA setting so that the output is logic 1 for current in the non-tripping direction.
• PHASE DIR 1 POL V THRESHOLD: This setting is used to establish the minimum level of voltage for which the phase
angle measurement is reliable. The setting is based on VT accuracy. The default value is “0.700 pu”.
• PHASE DIR 1 BLOCK WHEN V MEM EXP: This setting is used to select the required operation upon expiration of
voltage memory. When set to "Yes", the directional element blocks the operation of any phase overcurrent element
under directional control, when voltage memory expires; when set to "No", the directional element allows tripping of
phase overcurrent elements under directional control.
The phase directional element responds to the forward load current. In the case of a following reverse fault,
the element needs some time – in the order of 8 ms – to establish a blocking signal. Some protection ele-
NOTE
ments such as instantaneous overcurrent may respond to reverse faults before the blocking signal is
established. Therefore, a coordination time of at least 10 ms must be added to all the instantaneous protec-
tion elements under the supervision of the phase directional element. If current reversal is of a concern, a
longer delay – in the order of 20 ms – may be needed.

5-158 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

SETTING
PHASE DIR 1
FUNCTION:
Disabled=0
Enabled=1

SETTING
AND
PHASE DIR 1
BLOCK:
Off=0
SETTING

SETTING PHASE DIR 1 ECA:

PHASE DIR 1 SOURCE: I 0.05 pu AND RUN 0


IA Vpol
1 FLEXLOGIC OPERAND
Seq=ABC Seq=ACB I OR PH DIR1 BLK
SETTING
VBC VCB
PHASE DIR 1 POL V
THRESHOLD: FLEXLOGIC OPERAND
OR PH DIR1 BLK A
-Use V when V Min
-Use V memory when
V < Min MEMORY TIMER
1 cycle
V MINIMUM
1 sec
AND

SETTING USE ACTUAL VOLTAGE

PHASE DIR 1 BLOCK OC


WHEN V MEM EXP:
USE MEMORIZED VOLTAGE
No
Yes

FLEXLOGIC OPERAND
PHASE B LOGIC SIMILAR TO PHASE A PH DIR1 BLK B
5
FLEXLOGIC OPERAND
PHASE C LOGIC SIMILAR TO PHASE A PH DIR1 BLK C

827078A6.CDR

Figure 5–79: PHASE DIRECTIONAL SCHEME LOGIC

5.6.7 NEUTRAL CURRENT

a) MAIN MENU
PATH: SETTINGS Ø GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ NEUTRAL CURRENT

„ NEUTRAL CURRENT „ NEUTRAL TOC1


See page 5–160.
„ „
„ NEUTRAL IOC1
MESSAGE See page 5–161.
„
„ NEUTRAL
MESSAGE See page 5–162.
„ DIRECTIONAL OC1
„ NEUTRAL
MESSAGE See page 5–162.
„ DIRECTIONAL OC2

GE Multilin G60 Generator Protection System 5-159


5.6 GROUPED ELEMENTS 5 SETTINGS

b) NEUTRAL TIME OVERCURRENT (ANSI 51N)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ NEUTRAL CURRENT Ö NEUTRAL TOC1

„ NEUTRAL TOC1 NEUTRAL TOC1 Range: Disabled, Enabled


„ FUNCTION: Disabled
NEUTRAL TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
NEUTRAL TOC1 Range: Phasor, RMS
MESSAGE
INPUT: Phasor
NEUTRAL TOC1 Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 1.000 pu
NEUTRAL TOC1 Range: See OVERCURRENT CURVE TYPES table
MESSAGE
CURVE: IEEE Mod Inv
NEUTRAL TOC1 Range: 0.00 to 600.00 in steps of 0.01
MESSAGE
TD MULTIPLIER: 1.00
NEUTRAL TOC1 Range: Instantaneous, Timed
MESSAGE
RESET: Instantaneous
NEUTRAL TOC1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
NEUTRAL TOC1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
5 NEUTRAL TOC1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The neutral time overcurrent element can provide a desired time-delay operating characteristic versus the applied current
or be used as a simple definite time element. The neutral current input value is a quantity calculated as 3Io from the phase
currents and may be programmed as fundamental phasor magnitude or total waveform RMS magnitude as required by the
application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to the Inverse time overcurrent curve
characteristics section for details on curve setup, trip times and reset operation). When the element is blocked, the time
accumulator will reset according to the reset characteristic. For example, if the element reset characteristic is set to “Instan-
taneous” and the element is blocked, the time accumulator will be cleared immediately.

SETTINGS
NEUTRAL TOC1
SETTING INPUT:
NEUTRAL TOC1 NEUTRAL TOC1
FUNCTION: PICKUP:
Disabled = 0 NEUTRAL TOC1
Enabled = 1 CURVE:
NEUTRAL TOC1
TD MULTIPLIER:
NEUTRAL TOC 1 FLEXLOGIC OPERANDS
SETTING
RESET: NEUTRAL TOC1 PKP
NEUTRAL TOC1
AND RUN IN ≥ PICKUP NEUTRAL TOC1 DPO
SOURCE:
NEUTRAL TOC1 OP
IN t
I
SETTING
NEUTRAL TOC1
BLOCK:
Off = 0 827034A3.VSD

Figure 5–80: NEUTRAL TIME OVERCURRENT 1 SCHEME LOGIC

5-160 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

c) NEUTRAL INSTANTANEOUS OVERCURRENT (ANSI 50N)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ NEUTRAL CURRENT ÖØ NEUTRAL IOC1

„ NEUTRAL IOC1 NEUTRAL IOC1 Range: Disabled, Enabled


„ FUNCTION: Disabled
NEUTRAL IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
NEUTRAL IOC1 Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 1.000 pu
NEUTRAL IOC1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.00 s
NEUTRAL IOC1 RESET Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.00 s
NEUTRAL IOC1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
NEUTRAL IOC1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
NEUTRAL IOC1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The neutral instantaneous overcurrent element may be used as an instantaneous function with no intentional delay or as a
definite time function. The element essentially responds to the magnitude of a neutral current fundamental frequency pha-
sor calculated from the phase currents. A positive-sequence restraint is applied for better performance. A small portion 5
(6.25%) of the positive-sequence current magnitude is subtracted from the zero-sequence current magnitude when forming
the operating quantity of the element as follows:
I op = 3 × ( I_0 – K ⋅ I_1 ) where K = 1 ⁄ 16 (EQ 5.16)

The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from:
• System unbalances under heavy load conditions
• Transformation errors of current transformers (CTs) during double-line and three-phase faults.
• Switch-off transients during double-line and three-phase faults.
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on how test currents are injected into the relay (single-phase injection:
I op = 0.9375 ⋅ I injected ; three-phase pure zero-sequence injection: I op = 3 × I injected ).

SETTING

NEUTRAL IOC1 FUNCTION: SETTINGS

Disabled=0 NEUTRAL IOC1


SETTING PICKUP DELAY :
Enabled=1 FLEXLOGIC OPERANDS
NEUTRAL IOC1
NEUTRAL IOC1 PICKUP: NEUTRAL IOC1 PKP
RESET DELAY :
SETTING NEUTRAL IOC1 DPO
AND RUN tPKP
tRST NEUTRAL IOC1 OP
NEUTRAL IOC1 BLOCK: 3( I_0 - K I_1 ) PICKUP

Off=0

SETTING

NEUTRAL IOC1 SOURCE:


827035A4.CDR
I_0

Figure 5–81: NEUTRAL IOC1 SCHEME LOGIC

GE Multilin G60 Generator Protection System 5-161


5.6 GROUPED ELEMENTS 5 SETTINGS

d) NEUTRAL DIRECTIONAL OVERCURRENT (ANSI 67N)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö NEUTRAL CURRENT ÖØ NEUTRAL DIRECTIONAL OC1(2)

„ NEUTRAL NEUTRAL DIR OC1 Range: Disabled, Enabled


„ DIRECTIONAL OC1 FUNCTION: Disabled
NEUTRAL DIR OC1 Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
NEUTRAL DIR OC1 Range: Voltage, Current, Dual
MESSAGE
POLARIZING: Voltage
NEUTRAL DIR OC1 POL Range: Calculated V0, Measured VX
MESSAGE
VOLT: Calculated V0
NEUTRAL DIR OC1 OP Range: Calculated 3I0, Measured IG
MESSAGE
CURR: Calculated 3I0
NEUTRAL DIR OC1 POS- Range: 0.000 to 0.500 in steps of 0.001
MESSAGE
SEQ RESTRAINT: 0.063
NEUTRAL DIR OC1 Range: 0.00 to 250.00 Ω in steps of 0.01
MESSAGE
OFFSET: 0.00 Ω
NEUTRAL DIR OC1 FWD Range: –90 to 90° in steps of 1
MESSAGE
ECA: 75° Lag
NEUTRAL DIR OC1 FWD Range: 40 to 90° in steps of 1
MESSAGE
LIMIT ANGLE: 90°
5 NEUTRAL DIR OC1 FWD Range: 0.006 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.050 pu
NEUTRAL DIR OC1 REV Range: 40 to 90° in steps of 1
MESSAGE
LIMIT ANGLE: 90°
NEUTRAL DIR OC1 REV Range: 0.006 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.050 pu
NEUTRAL DIR OC1 BLK: Range: FlexLogic™ operand
MESSAGE
Off
NEUTRAL DIR OC1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
NEUTRAL DIR OC1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The neutral directional overcurrent element provides both forward and reverse fault direction indications the NEUTRAL DIR
OC1 FWD and NEUTRAL DIR OC1 REV operands, respectively. The output operand is asserted if the magnitude of the oper-
ating current is above a pickup level (overcurrent unit) and the fault direction is seen as forward or reverse, respectively
(directional unit).
The overcurrent unit responds to the magnitude of a fundamental frequency phasor of the either the neutral current calcu-
lated from the phase currents or the ground current. There are separate pickup settings for the forward-looking and
reverse-looking functions. If set to use the calculated 3I_0, the element applies a positive-sequence restraint for better per-
formance: a small user-programmable portion of the positive-sequence current magnitude is subtracted from the zero-
sequence current magnitude when forming the operating quantity.
I op = 3 × ( I_0 – K × I_1 ) (EQ 5.17)

The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious zero-sequence currents
resulting from:
• System unbalances under heavy load conditions.

5-162 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

• Transformation errors of current transformers (CTs) during double-line and three-phase faults.
• Switch-off transients during double-line and three-phase faults.
The positive-sequence restraint must be considered when testing for pickup accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay (single-phase injection:
Iop = (1 – K) × Iinjected ; three-phase pure zero-sequence injection: Iop = 3 × Iinjected).
The positive-sequence restraint is removed for low currents. If the positive-sequence current is below 0.8 pu, the restraint is
removed by changing the constant K to zero. This facilitates better response to high-resistance faults when the unbalance
is very small and there is no danger of excessive CT errors as the current is low.
The directional unit uses the zero-sequence current (I_0) or ground current (IG) for fault direction discrimination and may
be programmed to use either zero-sequence voltage (“Calculated V0” or “Measured VX”), ground current (IG), or both for
polarizing. The following tables define the neutral directional overcurrent element.

Table 5–21: QUANTITIES FOR "CALCULATED 3I0" CONFIGURATION


DIRECTIONAL UNIT
OVERCURRENT UNIT
POLARIZING MODE DIRECTION COMPARED PHASORS
Forward –V_0 + Z_offset × I_0 I_0 × 1∠ECA
Voltage
Reverse –V_0 + Z_offset × I_0 –I_0 × 1∠ECA
Forward IG I_0
Current
Reverse IG –I_0
–V_0 + Z_offset × I_0 I_0 × 1∠ECA Iop = 3 × (|I_0| – K × |I_1|) if |I1| > 0.8 pu
Forward or Iop = 3 × (|I_0|) if |I1| ≤ 0.8 pu
IG I_0
Dual
–V_0 + Z_offset × I_0 –I_0 × 1∠ECA 5
Reverse or
IG –I_0

Table 5–22: QUANTITIES FOR "MEASURED IG" CONFIGURATION


DIRECTIONAL UNIT
OVERCURRENT UNIT
POLARIZING MODE DIRECTION COMPARED PHASORS
Forward –V_0 + Z_offset × IG/3 IG × 1∠ECA
Voltage Iop = |IG|
Reverse –V_0 + Z_offset × IG/3 –IG × 1∠ECA

1
where: V_0 = --- ( VAG + VBG + VCG ) = zero sequence voltage ,
3
1 1
I_0 = --- IN = --- ( IA + IB + IC ) = zero sequence current ,
3 3
ECA = element characteristic angle and IG = ground current
When NEUTRAL DIR OC1 POL VOLT is set to “Measured VX”, one-third of this voltage is used in place of V_0. The following
figure explains the usage of the voltage polarized directional unit of the element.
The figure below shows the voltage-polarized phase angle comparator characteristics for a phase A to ground fault, with:
• ECA = 90° (element characteristic angle = centerline of operating characteristic)
• FWD LA = 80° (forward limit angle = the ± angular limit with the ECA for operation)
• REV LA = 80° (reverse limit angle = the ± angular limit with the ECA for operation)
The above bias should be taken into account when using the neutral directional overcurrent element to directionalize other
protection elements.

GE Multilin G60 Generator Protection System 5-163


5.6 GROUPED ELEMENTS 5 SETTINGS

REV LA FWD LA
line –3V_0 line line
VAG
(reference)

REV Operating FWD Operating


Region Region

LA
LA
3I_0 line
ECA

ECA line

–ECA line

–3I_0 line LA

VCG LA

VBG

FWD LA
REV LA line
3V_0 line
line 827805A1.CDR

5 Figure 5–82: NEUTRAL DIRECTIONAL VOLTAGE-POLARIZED CHARACTERISTICS


• NEUTRAL DIR OC1 POLARIZING: This setting selects the polarizing mode for the directional unit.
– If “Voltage” polarizing is selected, the element uses the zero-sequence voltage angle for polarization. The user
can use either the zero-sequence voltage V_0 calculated from the phase voltages, or the zero-sequence voltage
supplied externally as the auxiliary voltage V_X, both from the NEUTRAL DIR OC1 SOURCE.
The calculated V_0 can be used as polarizing voltage only if the voltage transformers are connected in Wye. The
auxiliary voltage can be used as the polarizing voltage provided SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE BANK
ÖØ AUXILIARY VT CONNECTION is set to “Vn” and the auxiliary voltage is connected to a zero-sequence voltage
source (such as open delta connected secondary of VTs).
The zero-sequence (V_0) or auxiliary voltage (V_X), accordingly, must be greater than 0.02 pu to be validated for
use as a polarizing signal. If the polarizing signal is invalid, neither forward nor reverse indication is given.
– If “Current” polarizing is selected, the element uses the ground current angle connected externally and configured
under NEUTRAL OC1 SOURCE for polarization. The ground CT must be connected between the ground and neutral
point of an adequate local source of ground current. The ground current must be greater than 0.05 pu to be vali-
dated as a polarizing signal. If the polarizing signal is not valid, neither forward nor reverse indication is given. In
addition, the zero-sequence current (I_0) must be greater than the PRODUCT SETUP ÖØ DISPLAY PROPERTIES ÖØ
CURRENT CUT-OFF LEVEL setting value.

For a choice of current polarizing, it is recommended that the polarizing signal be analyzed to ensure that a known
direction is maintained irrespective of the fault location. For example, if using an autotransformer neutral current
as a polarizing source, it should be ensured that a reversal of the ground current does not occur for a high-side
fault. The low-side system impedance should be assumed minimal when checking for this condition. A similar sit-
uation arises for a wye/delta/wye transformer, where current in one transformer winding neutral may reverse when
faults on both sides of the transformer are considered.
– If “Dual” polarizing is selected, the element performs both directional comparisons as described above. A given
direction is confirmed if either voltage or current comparators indicate so. If a conflicting (simultaneous forward
and reverse) indication occurs, the forward direction overrides the reverse direction.
• NEUTRAL DIR OC1 POL VOLT: Selects the polarizing voltage used by the directional unit when "Voltage" or "Dual"
polarizing mode is set. The polarizing voltage can be programmed to be either the zero-sequence voltage calculated
from the phase voltages ("Calculated V0") or supplied externally as an auxiliary voltage ("Measured VX").

5-164 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

• NEUTRAL DIR OC1 OP CURR: This setting indicates whether the 3I_0 current calculated from the phase currents, or
the ground current shall be used by this protection. This setting acts as a switch between the neutral and ground
modes of operation (67N and 67G). If set to “Calculated 3I0” the element uses the phase currents and applies the pos-
itive-sequence restraint; if set to “Measured IG” the element uses ground current supplied to the ground CT of the CT
bank configured as NEUTRAL DIR OC1 SOURCE. If this setting is “Measured IG”, then the NEUTRAL DIR OC1 POLARIZING
setting must be “Voltage”, as it is not possible to use the ground current as an operating and polarizing signal simulta-
neously.
• NEUTRAL DIR OC1 POS-SEQ RESTRAINT: This setting controls the amount of the positive-sequence restraint. Set
to 0.063 for backward compatibility with firmware revision 3.40 and older. Set to zero to remove the restraint. Set
higher if large system unbalances or poor CT performance are expected.
• NEUTRAL DIR OC1 OFFSET: This setting specifies the offset impedance used by this protection. The primary appli-
cation for the offset impedance is to guarantee correct identification of fault direction on series compensated lines. In
regular applications, the offset impedance ensures proper operation even if the zero-sequence voltage at the relaying
point is very small. If this is the intent, the offset impedance shall not be larger than the zero-sequence impedance of
the protected circuit. Practically, it shall be several times smaller. The offset impedance shall be entered in secondary
ohms.
• NEUTRAL DIR OC1 FWD ECA: This setting defines the characteristic angle (ECA) for the forward direction in the
"Voltage" polarizing mode. The "Current" polarizing mode uses a fixed ECA of 0°. The ECA in the reverse direction is
the angle set for the forward direction shifted by 180°.
• NEUTRAL DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the forward direction.
• NEUTRAL DIR OC1 FWD PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the
forward direction. When selecting this setting it must be kept in mind that the design uses a ‘positive-sequence
restraint’ technique for the “Calculated 3I0” mode of operation.
5
• NEUTRAL DIR OC1 REV LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
• NEUTRAL DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit of the element in the
reverse direction. When selecting this setting it must be kept in mind that the design uses a positive-sequence restraint
technique for the “Calculated 3I0” mode of operation.
Proper application of this element requires that the operating current and the polarizing voltage (or current) be mea-
sured from the same side of the transformer.
NOTE

GE Multilin G60 Generator Protection System 5-165


5.6 GROUPED ELEMENTS 5 SETTINGS

SETTING
NEUTRAL DIR OC1 FWD
PICKUP:
NEUTRAL DIR OC1 OP
CURR:

NEUTRAL DIR OC1 POS-


SETTING SEQ RESTRAINT:
RUN
NEUTRAL DIR OC1
FUNCTION: 3( I_0 - K I_1 ) PICKUP
Disabled=0 OR
Enabled=1 IG PICKUP AND

SETTING
AND SETTINGS
NEUTRAL DIR OC1 BLK: AND
NEUTRAL DIR OC1 FWD
ECA:
Off=0
NEUTRAL DIR OC1 FWD FLEXLOGIC OPERAND
LIMIT ANGLE:
SETTING AND NEUTRAL DIR OC1 FWD
NEUTRAL DIR OC1 NEUTRAL DIR OC1 REV
SOURCE: LIMIT ANGLE:

NEUTRAL DIR OC1 POL NEUTRAL DIR OC1


VOLT: OFFSET:
RUN
NEUTRAL DIR OC1 OP
CURR:
FWD

}
Measured VX OR
Calculated V_0 FWD
1.25 cy

}
-3V_0 AND
Zero Seq Crt (I_0) 1.5 cy
Ground Crt (IG) REV
3I_0 REV

Voltage Polarization

SETTING IG 0.05 pu AND RUN


NEUTRAL DIR OC1 FWD
POLARIZING:
Voltage OR Current Polarization

5 Current
Dual OR
REV
OR

NOTE:
1) CURRENT POLARIZING IS POSSIBLE ONLY IN RELAYS WITH
THE GROUND CURRENT INPUTS CONNECTED TO
AN ADEQUATE CURRENT POLARIZING SOURCE SETTING
NEUTRAL DIR OC1 REV
2) GROUND CURRENT CAN NOT BE USED FOR POLARIZATION PICKUP:
AND OPERATION SIMULTANEOUSLY AND FLEXLOGIC OPERAND
NEUTRAL DIR OC1 OP
3) POSITIVE SEQUENCE RESTRAINT IS NOT APPLIED WHEN CURR: NEUTRAL DIR OC1 REV
I_1 IS BELOW 0.8pu NEUTRAL DIR OC1 POS-
SEQ RESTRAINT:
RUN
3( I_0 - K I_1 ) PICKUP 827077AB.CDR
OR
IG PICKUP

Figure 5–83: NEUTRAL DIRECTIONAL OVERCURRENT LOGIC

5.6.8 GROUND CURRENT

a) MAIN MENU
PATH: SETTINGS Ø GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ GROUND CURRENT

„ GROUND CURRENT „ GROUND TOC1


See page 5–167.
„ „
„ GROUND IOC1
MESSAGE See page 5–168.
„
„ RESTRICTED GROUND
MESSAGE See page 5–169.
„ FAULT 1

„ RESTRICTED GROUND
MESSAGE
„ FAULT 4

The G60 relay contains one Ground Time Overcurrent, one Ground Instantaneous Overcurrent, and four Restricted Ground
Fault elements. Refer to Inverse Time Overcurrent Characteristics on page 5–148 for additional information.

5-166 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

b) GROUND TIME OVERCURRENT (ANSI 51G)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ GROUND CURRENT Ö GROUND TOC1

„ GROUND TOC1 GROUND TOC1 Range: Disabled, Enabled


„ FUNCTION: Disabled
GROUND TOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
GROUND TOC1 Range: Phasor, RMS
MESSAGE
INPUT: Phasor
GROUND TOC1 Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 1.000 pu
GROUND TOC1 Range: see the Overcurrent Curve Types table
MESSAGE
CURVE: IEEE Mod Inv
GROUND TOC1 Range: 0.00 to 600.00 in steps of 0.01
MESSAGE
TD MULTIPLIER: 1.00
GROUND TOC1 Range: Instantaneous, Timed
MESSAGE
RESET: Instantaneous
GROUND TOC1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
GROUND TOC1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
GROUND TOC1 Range: Disabled, Enabled 5
MESSAGE
EVENTS: Disabled

This element can provide a desired time-delay operating characteristic versus the applied current or be used as a simple
definite time element. The ground current input value is the quantity measured by the ground input CT and is the funda-
mental phasor or RMS magnitude. Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to
the Inverse time overcurrent curve characteristics section for details). When the element is blocked, the time accumulator
will reset according to the reset characteristic. For example, if the element reset characteristic is set to “Instantaneous” and
the element is blocked, the time accumulator will be cleared immediately.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel may be also equipped with a sensitive input. The conversion range of a sensitive channel is from
0.002 to 4.6 times the CT rating.
NOTE

SETTINGS
GROUND TOC1
SETTING INPUT:
GROUND TOC1 GROUND TOC1
FUNCTION: PICKUP:
Disabled = 0 GROUND TOC1
Enabled = 1 CURVE:
GROUND TOC1
TD MULTIPLIER:
GROUND TOC 1 FLEXLOGIC OPERANDS
SETTING
RESET: GROUND TOC1 PKP
GROUND TOC1
AND RUN IG ≥ PICKUP GROUND TOC1 DPO
SOURCE:
GROUND TOC1 OP
IG t
I
SETTING
GROUND TOC1
BLOCK:
827036A3.VSD
Off = 0

Figure 5–84: GROUND TOC1 SCHEME LOGIC

GE Multilin G60 Generator Protection System 5-167


5.6 GROUPED ELEMENTS 5 SETTINGS

c) GROUND INSTANTANEOUS OVERCURRENT (ANSI 50G)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ GROUND CURRENT ÖØ GROUND IOC1

„ GROUND IOC1 GROUND IOC1 Range: Disabled, Enabled


„ FUNCTION: Disabled
GROUND IOC1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
GROUND IOC1 Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 1.000 pu
GROUND IOC1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.00 s
GROUND IOC1 RESET Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.00 s
GROUND IOC1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
GROUND IOC1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
GROUND IOC1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The ground instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The ground current input is the quantity measured by the ground input CT and is the fundamental
5 phasor magnitude.
These elements measure the current that is connected to the ground channel of a CT/VT module. The conversion
range of a standard channel is from 0.02 to 46 times the CT rating.
NOTE
This channel may be equipped with a standard or sensitive input. The conversion range of a sensitive channel is
from 0.002 to 4.6 times the CT rating.
NOTE

FLEXLOGIC OPERANDS
SETTING GROUND IOC1 PKP
GROUND IOC1
GROUND IOIC DPO
FUNCTION:
Disabled = 0 SETTINGS GROUND IOC1 OP

Enabled = 1 GROUND IOC1 PICKUP


SETTING DELAY:
GROUND IOC1 GROUND IOC1 RESET
SETTING
PICKUP: DELAY:
GROUND IOC1
AND RUN tPKP
SOURCE:
IG
IG ≥ PICKUP tRST
SETTING
GROUND IOC1
BLOCK:
827037A4.VSD
Off = 0

Figure 5–85: GROUND IOC1 SCHEME LOGIC

5-168 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

d) RESTRICTED GROUND FAULT (ANSI 87G)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ GROUND CURRENT ÖØ RESTRICTED GROUND FAULT 1(4)

„ RESTRICTED GROUND RESTD GND FT1 Range: Disabled, Enabled


„ FAULT 1 FUNCTION: Disabled
RESTD GND FT1 Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
RESTD GND FT1 Range: 0.005 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.080 pu
RESTD GND FT1 Range: 0 to 100% in steps of 1
MESSAGE
SLOPE: 40%
RESTD GND FT1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.10 s
RESTD GND FT1 RESET Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.00 s
RESTD GND FT1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
RESTD GND FT1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
RESTD GND FT1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
5
Restricted ground fault (RGF) protection provides sensitive ground fault detection for low-magnitude fault currents, primar-
ily faults close to the neutral point of a wye-connected winding. An internal ground fault on an impedance grounded wye
winding will produce a fault current dependent on the ground impedance value and the fault position on the winding with
respect to the neutral point. The resultant primary current will be negligible for faults on the lower 30% of the winding since
the fault voltage is not the system voltage, but rather the result of the transformation ratio between the primary windings
and the percentage of shorted turns on the secondary. Therefore, the resultant differential currents may be below the slope
threshold of the main differential element and the fault could go undetected. Application of the restricted ground fault pro-
tection extends the coverage towards the neutral point (see the RGF and Percent Differential Zones of Protection diagram).

WINDING

35%

RGF DIFFERENTIAL ZONE


Rg
ZONE

842731A1.CDR

Figure 5–86: RGF AND PERCENT DIFFERENTIAL ZONES OF PROTECTION


This protection is often applied to transformers having impedance-grounded wye windings. The element may also be
applied to the stator winding of a generator having the neutral point grounded with a CT installed in the grounding path, or
the ground current obtained by external summation of the neutral-side stator CTs. The Typical Applications of RGF Protec-
tion diagram explains the basic application and wiring rules.

GE Multilin G60 Generator Protection System 5-169


5.6 GROUPED ELEMENTS 5 SETTINGS

(A) Transformer (C) Stator


Transformer Winding Stator Winding
IA IA

IB IB

IC IC

IG IG

(B) Transformer in a Breaker-and-a-Half (D) Stator without a Ground CT


1 1 1

Transformer Winding IA IB IC Stator Winding


IA
IA

IB
IB

IC
IC

5 IG IA IB IC
IG
2 2 2

842732A1.CDR

Figure 5–87: TYPICAL APPLICATIONS OF RGF PROTECTION


The relay incorporates low-impedance restricted ground fault protection. This low-impedance form of protection faces
potential stability problems. An external phase-to-phase fault is an ultimate case. Ideally, there is neither ground (IG) nor
neutral (IN = IA + IB + IC) current present. If one or more of the phase CTs saturate, a spurious neutral current is seen by
the relay. This is similar to a single infeed situation and may be mistaken for an internal fault. Similar difficulties occur in a
breaker-and-a-half application of the restricted ground fault, where any through fault with a weak infeed from the winding
itself may cause problems.
The UR uses a novel definition of the restraining signal to cope with the above stability problems while providing for fast
and sensitive protection. Even with the improved definition of the restraining signal, the breaker-and-a-half application of
the restricted ground fault must be approached with care, and is not recommended unless the settings are carefully
selected to avoid maloperation due to CT saturation.
The differential current is produced as an unbalance current between the ground current of the neutral CT (IG) and the neu-
tral current derived from the phase CTs (IN = IA + IB + IC):
Igd = IG + IN = IG + IA + IB + IC (EQ 5.18)

The relay automatically matches the CT ratios between the phase and ground CTs by re-scaling the ground CT to the
phase CT level. The restraining signal ensures stability of protection during CT saturation conditions and is produced as a
maximum value between three components related to zero, negative, and positive-sequence currents of the three phase
CTs as follows:
Irest = max ( IR0, IR1, IR2 ) (EQ 5.19)

The zero-sequence component of the restraining signal (IR0) is meant to provide maximum restraint during external ground
faults, and therefore is calculated as a vectorial difference of the ground and neutral currents:
IR0 = IG – IN = IG – ( IA + IB + IC ) (EQ 5.20)

5-170 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

The equation above brings an advantage of generating the restraining signal of twice the external ground fault current,
while reducing the restraint below the internal ground fault current. The negative-sequence component of the restraining
signal (IR2) is meant to provide maximum restraint during external phase-to-phase faults and is calculated as follows:
IR2 = I_2 or IR2 = 3 × I_2 (EQ 5.21)

The multiplier of 1 is used by the relay for first two cycles following complete de-energization of the winding (all three phase
currents below 5% of nominal for at least five cycles). The multiplier of 3 is used during normal operation; that is, two cycles
after the winding has been energized. The lower multiplier is used to ensure better sensitivity when energizing a faulty
winding.
The positive-sequence component of the restraining signal (IR1) is meant to provide restraint during symmetrical condi-
tions, either symmetrical faults or load, and is calculated according to the following algorithm:
1 If I_1 > 1.5 pu of phase CT, then
2 If I_1 > I_0 , then IR1 = 3 × ( I_1 – I_0 )
3 else IR1 = 0
4 else IR1 = I_1 ⁄ 8
Under load-level currents (below 150% of nominal), the positive-sequence restraint is set to 1/8th of the positive-sequence
current (line 4). This is to ensure maximum sensitivity during low-current faults under full load conditions. Under fault-level
currents (above 150% of nominal), the positive-sequence restraint is removed if the zero-sequence component is greater
than the positive-sequence (line 3), or set at the net difference of the two (line 2).
The raw restraining signal (Irest) is further post-filtered for better performance during external faults with heavy CT satura-
tion and for better switch-off transient control:
Igr ( k ) = max ( Irest ( k ), α × Igr ( k – 1 ) ) (EQ 5.22)

where k represents a present sample, k – 1 represents the previous sample, and α is a factory constant (α < 1). The equa-
tion above introduces a decaying memory to the restraining signal. Should the raw restraining signal (Irest) disappear or
5
drop significantly, such as when an external fault gets cleared or a CT saturates heavily, the actual restraining signal (Igr(k))
will not reduce instantly but will keep decaying decreasing its value by 50% each 15.5 power system cycles.
Having the differential and restraining signals developed, the element applies a single slope differential characteristic with a
minimum pickup as shown in the logic diagram below.

SETTING
RESTD GND FT1
FUNCTION:
Disabled=0
SETTING
Enabled=1
RESTD GND FT1
PICKUP: SETTINGS
SETTING
AND RUN RESTD GND FT1 PICKUP
RESTD GND FT1 Igd > PICKUP DELAY:
BLOCK: FLEXLOGIC OPERANDS
RESTD GND FT1 RESET
Off=0 RESTD GND FT1 PKP
DELAY:
SETTING RESTD GND FT1 DPO
t PKP
SETTING AND t RST RESTD GND FT1 OP
RESTD GND FT1
RESTD GND FT1 SLOPE:
SOURCE: RUN
IG
IN Differential Igd > SLOPE * Igr
and
I_0
Restraining
I_1 Currents
I_2
ACTUAL VALUES
RGF 1 Igd Mag
RGF 1 Igr Mag 828002A2.CDR

Figure 5–88: RESTRICTED GROUND FAULT SCHEME LOGIC

GE Multilin G60 Generator Protection System 5-171


5.6 GROUPED ELEMENTS 5 SETTINGS

The following examples explain how the restraining signal is created for maximum sensitivity and security. These examples
clarify the operating principle and provide guidance for testing of the element.
EXAMPLE 1: EXTERNAL SINGLE-LINE-TO-GROUND FAULT
Given the following inputs: IA = 1 pu ∠0°, IB = 0, IC = 0, and IG = 1 pu ∠180°
The relay calculates the following values:

1⁄3
Igd = 0, IR0 = abs ⎛ 3 × --- – ( – 1 )⎞ = 2 pu , IR2 = 3 × --- = 1 pu , IR1 = ---------- = 0.042 pu , and Igr = 2 pu
1 1
⎝ 3 ⎠ 3 8

The restraining signal is twice the fault current. This gives extra margin should the phase or neutral CT saturate.
EXAMPLE 2: EXTERNAL HIGH-CURRENT SLG FAULT
Given the following inputs: IA = 10 pu ∠0°, IB = 0, IC = 0, and IG = 10 pu ∠–180°
The relay calculates the following values:

Igd = 0, IR0 = abs ⎛ 3 × --- – ( – 10 )⎞ = 20 pu , IR2 = 3 × ------ = 10 pu , IR1 = 3 × ⎛ 10 ------⎞⎠ = 0 , and Igr = 20 pu.
1 10
- – 10
⎝ 3 ⎠ 3 ⎝ -----
3 3

EXAMPLE 3: EXTERNAL HIGH-CURRENT THREE-PHASE SYMMETRICAL FAULT


Given the following inputs: IA = 10 pu ∠0°, IB = 10 pu ∠–120°, IC = 10 pu ∠120°, and IG = 0 pu
The relay calculates the following values:

Igd = 0, IR0 = abs ( 3 × 0 – ( 0 ) ) = 0 pu , IR2 = 3 × 0 = 0 pu , IR1 = 3 × ⎛ 10


------ – 0⎞ = 10 pu , and Igr = 10 pu.
⎝3 ⎠

5 EXAMPLE 4: INTERNAL LOW-CURRENT SINGLE-LINE-TO-GROUND FAULT UNDER FULL LOAD


Given the following inputs: IA = 1.10 pu ∠0°, IB = 1.0 pu ∠–120°, IC = 1.0 pu ∠120°, and IG = 0.05 pu ∠0°
The relay calculates the following values:
I_0 = 0.033 pu ∠0°, I_2 = 0.033 pu ∠0°, and I_1 = 1.033 pu ∠0°
Igd = abs(3 × 0.0333 + 0.05) = 0.15 pu, IR0 = abs(3 × 0.033 – (0.05)) = 0.05 pu, IR2 = 3 × 0.033 = 0.10 pu,
IR1 = 1.033 / 8 = 0.1292 pu, and Igr = 0.1292 pu
Despite very low fault current level the differential current is above 100% of the restraining current.
EXAMPLE 5: INTERNAL LOW-CURRENT, HIGH-LOAD SINGLE-LINE-TO-GROUND FAULT WITH NO FEED FROM
THE GROUND
Given the following inputs: IA = 1.10 pu ∠0°, IB = 1.0 pu ∠–120°, IC = 1.0 pu ∠120°, and IG = 0.0 pu ∠0°
The relay calculates the following values:
I_0 = 0.033 pu ∠0°, I_2 = 0.033 pu ∠0°, and I_1 = 1.033 pu ∠0°
Igd = abs(3 × 0.0333 + 0.0) = 0.10 pu, IR0 = abs(3 × 0.033 – (0.0)) = 0.10 pu, IR2 = 3 × 0.033 = 0.10 pu,
IR1 = 1.033 / 8 = 0.1292 pu, and Igr = 0.1292 pu
Despite very low fault current level the differential current is above 75% of the restraining current.
EXAMPLE 6: INTERNAL HIGH-CURRENT SINGLE-LINE-TO-GROUND FAULT WITH NO FEED FROM THE GROUND
Given the following inputs: IA = 10 pu ∠0°, IB = 0 pu, IC = 0 pu, and IG = 0 pu
The relay calculates the following values:
I_0 = 3.3 pu ∠0°, I_2 = 3.3 pu ∠0°, and I_1 = 3.3 pu ∠0°
Igd = abs(3 × 3.3 + 0.0) = 10 pu, IR0 = abs(3 × 3.3 – (0.0)) = 10 pu, IR2 = 3 × 3.3 = 10 pu, IR1 = 3 × (3.33 – 3.33) = 0
pu, and Igr = 10 pu
The differential current is 100% of the restraining current.

5-172 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

5.6.9 NEGATIVE SEQUENCE CURRENT

a) NEGATIVE SEQUENCE DIRECTIONAL OVERCURRENT (ANSI 67_2)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ NEGATIVE SEQUENCE CURRENT ÖØ NEG SEQ DIR OC1(2)

„ NEG SEQ DIR OC1 NEG SEQ DIR OC1 Range: Disabled, Enabled
„ FUNCTION: Disabled
NEG SEQ DIR OC1 Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
NEG SEQ DIR OC1 Range: 0.00 to 250.00 ohms in steps of 0.01
MESSAGE
OFFSET: 0.00 Ω
NEG SEQ DIR OC1 Range: Neg Sequence, Zero Sequence
MESSAGE
TYPE: Neg Sequence
NEG SEQ DIR OC1 POS- Range: 0.000 to 0.500 in steps of 0.001
MESSAGE
SEQ RESTRAINT: 0.063
NEG SEQ DIR OC1 FWD Range: 0 to 90° Lag in steps of 1
MESSAGE
ECA: 75° Lag
NEG SEQ DIR OC1 FWD Range: 40 to 90° in steps of 1
MESSAGE
LIMIT ANGLE: 90°
NEG SEQ DIR OC1 FWD Range: 0.015 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.050 pu

MESSAGE
NEG SEQ DIR OC1 REV Range: 40 to 90° in steps of 1
5
LIMIT ANGLE: 90°
NEG SEQ DIR OC1 REV Range: 0.015 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.050 pu
NEG SEQ DIR OC1 BLK: Range: FlexLogic™ operand
MESSAGE
Off
NEG SEQ DIR OC1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
NEG SEQ DIR OC1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

There are two negative-sequence directional overcurrent protection elements available. The element provides both forward
and reverse fault direction indications through its output operands NEG SEQ DIR OC1 FWD and NEG SEQ DIR OC1 REV,
respectively. The output operand is asserted if the magnitude of the operating current is above a pickup level (overcurrent
unit) and the fault direction is seen as forward or reverse, respectively (directional unit).
The overcurrent unit of the element essentially responds to the magnitude of a fundamental frequency phasor of either
the negative-sequence or zero-sequence current as per user selection. The zero-sequence current should not be mistaken
with the neutral current (factor 3 difference).
A positive-sequence restraint is applied for better performance: a small user-programmable portion of the positive-
sequence current magnitude is subtracted from the negative or zero-sequence current magnitude, respectively, when form-
ing the element operating quantity.
I op = I_2 – K × I_1 or I op = 3 × ( I_0 – K × I_1 ) (EQ 5.23)

The positive-sequence restraint allows for more sensitive settings by counterbalancing spurious negative-sequence and
zero-sequence currents resulting from:
• System unbalances under heavy load conditions.
• Transformation errors of current transformers (CTs).
• Fault inception and switch-off transients.

GE Multilin G60 Generator Protection System 5-173


5.6 GROUPED ELEMENTS 5 SETTINGS

The positive-sequence restraint must be considered when testing for pick-up accuracy and response time (multiple of
pickup). The positive-sequence restraint is removed for low currents. If the positive-sequence current is less than 0.8 pu,
then the restraint is removed by changing the constant K to zero. This results in better response to high-resistance faults
when the unbalance is very small and there is no danger of excessive CT errors, since the current is low.
The operating quantity depends on the way the test currents are injected into the G60. For single phase injection:
• Iop = ⅓ × (1 – K) × Iinjected for I_2 mode.
• Iop = (1 – K) × Iinjected for I_0 mode if I_1 > 0.8 pu.
The directional unit uses the negative-sequence current (I_2) and negative-sequence voltage (V_2).
The following tables define the negative-sequence directional overcurrent element.
Table 5–23: NEGATIVE-SEQUENCE DIRECTIONAL OVERCURRENT UNIT
MODE OPERATING CURRENT
Negative-sequence Iop = |I_2| – K × I_1|
Zero-sequence Iop = 3 × (|I_0| – K × |I_1|) if |I_1| > 0.8 pu
Iop = 3 × |I_0| if |I_1| ≤ 0.8 pu

Table 5–24: NEGATIVE-SEQUENCE DIRECTIONAL UNIT


DIRECTION COMPARED PHASORS
Forward –V_2 + Z_offset × I_2 I_2 × 1∠ECA
Reverse –V_2 + Z_offset × I_2 –(I_2 × 1∠ECA)
Forward –V_2 + Z_offset × I_2 I_2 × 1∠ECA
Reverse –V_2 + Z_offset × I_2 –(I_2 × 1∠ECA)
5
The negative-sequence voltage must be greater than 0.02 pu to be validated for use as a polarizing signal. If the polarizing
signal is not validated neither forward nor reverse indication is given. The following figure explains the usage of the voltage
polarized directional unit of the element.
The figure below shows the phase angle comparator characteristics for a phase A to ground fault, with settings of:
ECA = 75° (element characteristic angle = centerline of operating characteristic)
FWD LA = 80° (forward limit angle = ± the angular limit with the ECA for operation)
REV LA = 80° (reverse limit angle = ± the angular limit with the ECA for operation)

5-174 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power system
cycle, the prospective forward indication will be delayed by 1.5 of a power system cycle. The element is designed to emu-
late an electromechanical directional device. Larger operating and polarizing signals will result in faster directional discrimi-
nation bringing more security to the element operation.

–V_2 line

REV FWD
LA LA VAG (reference)

REV Operating
Region

LA

ECA line
LA ECA

I_2 line

–I_2 line LA
FWD Operating
Region

–ECA line

LA

VCG VBG

V_2 line
REV
LA
FWD
LA
5
827806A2.CDR

Figure 5–89: NEGATIVE-SEQUENCE DIRECTIONAL CHARACTERISTIC


The forward-looking function is designed to be more secure as compared to the reverse-looking function, and therefore
should be used for the tripping direction. The reverse-looking function is designed to be faster as compared to the forward-
looking function and should be used for the blocking direction. This allows for better protection coordination. The above
bias should be taken into account when using the negative-sequence directional overcurrent element to directionalize other
protection elements. The negative-sequence directional pickup must be greater than the PRODUCT SETUP ÖØ DISPLAY
PROPERTIES ÖØ CURRENT CUT-OFF LEVEL setting value.

• NEG SEQ DIR OC1 OFFSET: This setting specifies the offset impedance used by this protection. The primary applica-
tion for the offset impedance is to guarantee correct identification of fault direction on series compensated lines (see
the Application of settings chapter for information on how to calculate this setting). In regular applications, the offset
impedance ensures proper operation even if the negative-sequence voltage at the relaying point is very small. If this is
the intent, the offset impedance shall not be larger than the negative-sequence impedance of the protected circuit.
Practically, it shall be several times smaller. The offset impedance shall be entered in secondary ohms. See the Theory
of operation chapter for additional details.
• NEG SEQ DIR OC1 TYPE: This setting selects the operating mode for the overcurrent unit of the element. The
choices are “Neg Sequence” and “Zero Sequence”. In some applications it is advantageous to use a directional nega-
tive-sequence overcurrent function instead of a directional zero-sequence overcurrent function as inter-circuit mutual
effects are minimized.
• NEG SEQ DIR OC1 POS-SEQ RESTRAINT: This setting controls the positive-sequence restraint. Set to 0.063 (in
“Zero Sequence” mode) or 0.125 (in “Neg Sequence” mode) for backward compatibility with revisions 3.40 and earlier.
Set to zero to remove the restraint. Set higher if large system unbalances or poor CT performance are expected.
• NEG SEQ DIR OC1 FWD ECA: This setting select the element characteristic angle (ECA) for the forward direction.
The element characteristic angle in the reverse direction is the angle set for the forward direction shifted by 180°.
• NEG SEQ DIR OC1 FWD LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the forward direction.

GE Multilin G60 Generator Protection System 5-175


5.6 GROUPED ELEMENTS 5 SETTINGS

• NEG SEQ DIR OC1 FWD PICKUP: This setting defines the pickup level for the overcurrent unit in the forward direc-
tion. Upon NEG SEQ DIR OC1 TYPE selection, this pickup threshold applies to zero- or negative-sequence current. When
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.
• NEG SEQ DIR OC1 REV LIMIT ANGLE: This setting defines a symmetrical (in both directions from the ECA) limit
angle for the reverse direction.
• NEG SEQ DIR OC1 REV PICKUP: This setting defines the pickup level for the overcurrent unit in the reverse direc-
tion. Upon NEG SEQ DIR OC1 TYPE selection, this pickup threshold applies to zero- or negative-sequence current. When
selecting this setting it must be kept in mind that the design uses a positive-sequence restraint technique.

SETTINGS
Forward Pickup
Positive-Sequence Restraint
AND RUN

( |3I_0| – K × |I_1| ) ≥ Pickup


OR
AND RUN

( |I_2| – K × |I_1| ) ≥ Pickup AND


SETTING
Function
Disabled = 0 FLEXLOGIC OPERAND
Enabled = 1 SETTINGS AND NEG SEQ DIR OC1 FWD
Forward ECA
SETTING AND Forward Limit Angle
Block Reverse Limit Angle
Off = 0 Offset
TIMER
RUN
1.25 cycles
Forward AND
ACTUAL VALUES 1.5 cycles
V_2
I_2
I_0 Reverse

5 NOTE:
V_2 is negative-sequence voltage
I_2 is negative-sequence current
Voltage Polarization

I_0 is zero-sequence current


SETTINGS
Reverse Pickup
Pos Seq Restraint AND
AND RUN
SETTING
Type ( |I_2| – K × |I_1| ) ≥ Pickup
= Neg Sequence OR FLEXLOGIC OPERAND
AND RUN
= Zero Sequence NEG SEQ DIR OC1 REV
( |3I_0| – K × |I_1| ) ≥ Pickup
827091A6.CDR

Figure 5–90: NEGATIVE SEQUENCE DIRECTIONAL OC1 SCHEME LOGIC

5-176 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

5.6.10 GENERATOR UNBALANCE

PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ GENERATOR UNBALANCE

„ GENERATOR GENERATOR UNBAL Range: Disabled, Enabled


„ UNBALANCE FUNCTION: Disabled
GEN UNBAL SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SRC 1
GEN UNBAL INOM: Range: 0.000 to 1.250 pu in steps of 0.001
MESSAGE
0.800 pu
GEN UNBAL STG1 Range: 0.00 to 100.00% in steps of 0.01
MESSAGE
PICKUP: 8.00%
GEN UNBAL STG1 Range: 0.00 to 100.00 in steps of 0.01
MESSAGE
K-VALUE: 1.00
GEN UNBAL STG1 TMIN: Range: 0.000 to 50.000 s in steps of 0.001
MESSAGE
0.250 s
GEN UNBAL STG1 TMAX: Range: 0.0 to 1000.0 s in steps of 0.1
MESSAGE
600.00 s
GEN UNBAL STG1 Range: 0.0 to 1000.0 s in steps of 0.1
MESSAGE
K-RESET: 240.00 s
GEN UNBAL STG2 Range: 0.00 to 100.00% in steps of 0.01
MESSAGE
PICKUP: 3.0% 5
GEN UNBAL STG2 PKP Range: 0.0 to 1000.0 s in steps of 0.1
MESSAGE
DELAY: 5.0 s
GEN UNBAL BLK: Range: FlexLogic™ operand
MESSAGE
Off
GEN UNBAL TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-Reset
GEN UNBAL EVENTS: Range: Enabled, Disabled
MESSAGE
Disabled

The generator unbalance element protects the machine from rotor damage due to excessive negative-sequence current.
The element has an inverse time stage which is typically used for tripping and a definite time stage typically used for alarm
purposes. The inverse time stage operating characteristic is defined by the following equation:

K where Inom is the generator rated current and K is the negative-sequence capability constant nor-
T = --------------------------
- mally provided by the generator manufacturer.
2
( I 2 ⁄ I nom )

• GEN UNBAL INOM: This setting is the rated full load current of the machine.
• GEN UNBAL STG1 PICKUP: This setting defines the pickup of the stage 1 element expressed as a percentage of the
nominal current as specified by GEN UNBAL INOM setting. It is typically set at the maximum continuous negative
sequence current rating of the machine.
• GEN UNBAL STG1 K-VALUE: This setting is the negative sequence capability constant. This value is normally pro-
vided by the generator manufacturer (refer to ANSI C50.13 for details).
• GEN UNBAL STG1 TMIN: This is the minimum operate time of the stage 1 element. The stage will not operate before
this time expires. This is set to prevent false trips for faults that would be cleared normally by system protections.
• GEN UNBAL STG1 TMAX: This is the maximum operate time of the stage 1 element. This setting can be applied to
limit the maximum tripping time for low level unbalances.

GE Multilin G60 Generator Protection System 5-177


5.6 GROUPED ELEMENTS 5 SETTINGS

• GEN UNBAL STG1 K-RESET: This setting defines the linear reset rate of the stage 1 element. It is the maximum reset
time from the threshold of tripping. This feature provides a thermal memory of previous unbalance conditions.
• GEN UNBAL STG2 PICKUP: This setting defines the pickup of the stage 2 element expressed as a percentage of the
nominal current as specified by GEN UNBAL INOM setting. The definite time element would normally be used to generate
an alarm to prompt an operator to take some corrective action. The stage 2 element would typically be set at a safe
margin below the stage 1 pickup setting.
• GEN UNBAL STG2 PKP DELAY: This is the minimum operate time of the stage 2 element. This is set to prevent nui-
sance alarms during system faults.
1000
K=1 K=4 K=15 K=40 K=100
Tmax

100

10

Tmin
5 0.1
0.01 0.1 1 10 100

830714A1.CDR

Figure 5–91: GENERATOR UNBALANCE INVERSE TIME CURVES

SETTINGS
GEN UNBAL
INOM:
GEN UNBAL
STG1 PICKUP:
GEN UNBAL
STG1 TMIN:
GEN UNBAL
STG1 TMAX:
SETTING
GEN UNBAL
GEN UNBAL STG1 K-VALUE:
FUNCTION:
GEN UNBAL
Disabled=0
STG1 K-RESET:
Enabled=1
AND RUN

SETTING t

GEN UNBAL
BLK:
FLEXLOGIC OPERANDS
Off=0
GEN UNBAL STG1 OP
I_2 GEN UNBAL STG1 PKP
SETTINGS
GEN UNBAL STG1 DPO
GEN UNBAL STG2
GEN UNBAL STG2 OP
PICKUP: SETTING
GEN UNBAL STG2 PKP
GEN UNBAL STG2
GEN UNBAL INOM: GEN UNBAL STG2 DPO
SETTING PKP DELAY:
OR GEN UNBAL PKP
GEN UNBAL AND RUN TPKP
SOURCE: 0 FLEXLOGIC OPERAND
I_2 > PICKUP x INOM
I_2 100 OR GEN UNBAL OP

FLEXLOGIC OPERAND
OR GEN UNBAL DPO
830713A4.CDR

Figure 5–92: GENERATOR UNBALANCE SCHEME LOGIC

5-178 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

5.6.11 SPLIT PHASE PROTECTION

PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ SPLIT PHASE

„ SPLIT PHASE SPLIT PHASE SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4
„ SRC 1
SPLIT PHASE LOAD Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 2
SPLIT PHASE A Range: 0.020 to 1.500 pu in steps of 0.001
MESSAGE
PICKUP: 0.200 pu
SPLIT PHASE A Range: 0.000 to 1.000 pu in steps of 0.001
MESSAGE
OFFSET: 0.000 pu
SPLIT PHASE A SLOPE: Range: 0.0 to 100% in steps of 0.1
MESSAGE
0.0%
SPLIT PHASE B Range: 0.020 to 1.500 pu in steps of 0.001
MESSAGE
PICKUP: 0.200 pu
SPLIT PHASE B Range: 0.000 to 1.000 pu in steps of 0.001
MESSAGE
OFFSET: 0.000 pu
SPLIT PHASE B SLOPE: Range: 0.0 to 100% in steps of 0.1
MESSAGE
0.0%
SPLIT PHASE C Range: 0.020 to 1.500 pu in steps of 0.001
MESSAGE
PICKUP: 0.200 pu 5
SPLIT PHASE C Range: 0.000 to 1.000 pu in steps of 0.001
MESSAGE
OFFSET: 0.000 pu
SPLIT PHASE C SLOPE: Range: 0.0 to 100% in steps of 0.1
MESSAGE
0.0%
SPLIT PHASE MIN Range: 0.00 to 1.00 pu in steps of 0.01
MESSAGE
LOAD: 0.00 pu
SPLIT PHASE MODE: Range: Over, Over-Under
MESSAGE
Over
SPLIT PHASE DELAY: Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
0.000 s
SPLIT PHASE BLK: Range: FlexLogic™ operand
MESSAGE
Off
SPLIT PHASE TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-Reset
SPLIT PHASE EVENTS: Range: Enabled, Disabled
MESSAGE
Disabled

Some generators, due to physical construction, have windings that consist of multiple adjacent turns. It is therefore possible
for faults to develop between turns on the same phase (inter-turn faults). These faults are not detected by the stator differ-
ential protection, as there is no difference between the neutral and at the terminal currents. Split phase protection may be
applied to detect inter-turn faults in the case that the generator is wound with two three-phase windings, each brought sep-
arately out of the machine and connected in parallel. The currents in the two windings are compared, any difference indicat-
ing an inter-turn fault.
The split phase element allows a separate pickup setting to be applied for each phase. Additionally, the pickup can be
biased by the load current (slope characteristic). Two modes of operation are supported (over and over-under).

GE Multilin G60 Generator Protection System 5-179


5.6 GROUPED ELEMENTS 5 SETTINGS

Split Phase Load


830728A1.CDR Source Source

Figure 5–93: SPLIT PHASE PROTECTION FOR 2 CTS

Split Phase Load


830727A1.CDR Source Source

Figure 5–94: SPLIT PHASE PROTECTION FOR 1 CT


The split phase element principle of operation is as follows. First, define the following parameters:
Isplit: split-phase current, Iload: load current, pickup: pickup setting, min_load: minimum load supervision setting
Then, the expected value of the steady state unbalance (defined as bias current) is expressed as follows:
I bias = slope × I load + offset (EQ 5.24)

where:
I split Load CT Primary Split Phase CT Secondary
slope = ----------- × ----------------------------------------------------- × ---------------------------------------------------------------------- (EQ 5.25)
I load Load CT Secondary Split Phase CT Primary

and offset is the split phase current at no-load. In “Over” mode, the element will pickup if:
( I split – I bias > pickup ) and ( I load ≥ min_load ) (EQ 5.26)

In “Over-under”, mode, the element will pickup if:


( I split – I bias > pickup ) and ( I load ≥ min_load ) (EQ 5.27)

5-180 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

I splt phs (pu)


Operate

Slope

Offset

Operate
Min Load

Iload (pu)
Operating Characteristic
I splt phs (pu)

Operate

5
Iload (pu)
Operating Characteristic (mode = over, Min Load = 0, Slope = 0)
I splt phs (pu)

Min Load
Operate

Slope

Offset

Iload (pu)
Operating Characteristic (mode = over)
830729A1.CDR

Figure 5–95: SPLIT PHASE PROTECTION OPERATING CHARACTERISTICS


• SPLIT PHASE SOURCE: This setting specifies a signal source used to provide current from the split phase CT to the
split phase protection.
• SPLIT PHASE LOAD SOURCE: This setting specifies a signal source used to provide current from the load CT to the
split phase protection.
• SPLIT PHASE A(C) PICKUP: This setting specifies a pickup level for each phase. This should be set less than the
minimum expected unbalance (split phase) current due to an inter-turn fault.
• SPLIT PHASE A(C) OFFSET: This setting specifies the steady-state split phase current at no-load for the each phase.
This should be set equal to the split phase current during normal (unfaulted) operation. The user should assign the split
phase current and the load current (positive sequence) to the data logger to identify the optimum value for this setting.
• SPLIT PHASE A(C) SLOPE: This setting specifies the slope of split phase characteristic for each phase. This setting
is used to bias the pickup of the element due to variations in generator loading. The slope is defined as the ratio of the

GE Multilin G60 Generator Protection System 5-181


5.6 GROUPED ELEMENTS 5 SETTINGS

per-unit split phase current over the per-unit load current. The user should assign the split phase current and the load
current (positive sequence) to the data logger to identify the optimum value for this setting.
• SPLIT PHASE MIN LOAD: This setting specifies the minimum load (positive-sequence current) supervision level.
• SPLIT PHASE MODE: This setting specifies the mode of operation. If the “Over” mode is chosen, the element will
pickup when the split phase current is rises above the biased offset current plus the pickup setting. If “Over-under”
mode is chosen, the element will also pickup if the split phase current is falls below the biased offset current minus the
pickup setting. See the earlier description for further details.
• SPLIT PHASE DELAY: This setting specifies a time delay required to operate after the pickup condition is established.
During an external disturbance the CTs may saturate. CT saturation can cause a spurious split phase current, espe-
cially in the case where the split phase current is derived from the external summation of two split phase CTs (first fig-
ure above). In this instance, a time delay can be used to ride through the saturation event. Alternately, the CT
saturation flag can also be used to supervise the function.

SETTINGS
SPLIT PHASE A PICKUP
SPLIT PHASE A OFFSET
SETTINGS
SPLIT PHASE A SLOPE
SPLIT PHASE FUNCTION
SPLIT PHASE MIN LOAD
Enabled =1
SPLIT PHASE MODE
SPLIT PHASE BLOCK AND FLEXLOGIC OPERANDS
START
Off = 0 SETTING SPLIT PHASE PKP A
SPLIT PHASE DELAY SPLIT PHASE DPO A
t
SPLIT PHASE OP A
0

5 SETTING
SPLIT PHASE LOAD SOURCE: SETTINGS
I_1 SPLIT PHASE B PICKUP
SPLIT PHASE B OFFSET
SPLIT PHASE B SLOPE
SPLIT PHASE MIN LOAD
SETTING
SPLIT PHASE MODE
SPLIT PHASE SOURCE: FLEXLOGIC OPERANDS
START
I_A SETTING SPLIT PHASE PKP B
I_B SPLIT PHASE DELAY SPLIT PHASE DPO B
t
I_C SPLIT PHASE OP B
0

FLEXLOGIC OPERANDS
SETTINGS
OR SPLIT PHASE OP
SPLIT PHASE C PICKUP
SPLIT PHASE C OFFSET
SPLIT PHASE C SLOPE
SPLIT PHASE MIN LOAD
SPLIT PHASE MODE
FLEXLOGIC OPERANDS
START
SETTING SPLIT PHASE PKP C
SPLIT PHASE DELAY SPLIT PHASE DPO C
t
SPLIT PHASE OP C
0

ACTUAL VALUES
SPLIT PHASE A CURRENT (PU)
SPLIT PHASE B CURRENT (PU)
SPLIT PHASE C CURRENT (PU)
LOAD CURRENT (PU) 830007A1.CDR

Figure 5–96: SPLIT PHASE PROTECTION LOGIC

5-182 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

5.6.12 VOLTAGE ELEMENTS

a) MAIN MENU
PATH: SETTINGS Ø GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ VOLTAGE ELEMENTS

„ VOLTAGE ELEMENTS „ PHASE


See page 5–185.
„ „ UNDERVOLTAGE1
„ PHASE
MESSAGE See page 5–185.
„ UNDERVOLTAGE2
„ PHASE
MESSAGE See page 5–186.
„ OVERVOLTAGE1
„ NEUTRAL OV1
MESSAGE See page 5–187.
„
„ NEUTRAL OV2
MESSAGE See page 5–187.
„
„ NEUTRAL OV3
MESSAGE See page 5–187.
„
„ NEG SEQ OV1
MESSAGE See page 5–188.
„
„ NEG SEQ OV2
MESSAGE See page 5–188.
„

MESSAGE
„ NEG SEQ OV3
See page 5–188. 5
„
„ AUXILIARY UV1
MESSAGE See page 5–189.
„
„ AUXILIARY UV2
MESSAGE See page 5–189.
„
„ AUXILIARY OV1
MESSAGE See page 5–190.
„
„ AUXILIARY OV2
MESSAGE See page 5–190.
„
„ VOLTS/HZ 1
MESSAGE See page 5–191.
„
„ VOLTS/HZ 2
MESSAGE See page 5–191.
„

These protection elements can be used for a variety of applications such as:
• Undervoltage Protection: For voltage sensitive loads, such as induction motors, a drop in voltage increases the
drawn current which may cause dangerous overheating in the motor. The undervoltage protection feature can be used
to either cause a trip or generate an alarm when the voltage drops below a specified voltage setting for a specified time
delay.
• Permissive Functions: The undervoltage feature may be used to block the functioning of external devices by operat-
ing an output relay when the voltage falls below the specified voltage setting. The undervoltage feature may also be
used to block the functioning of other elements through the block feature of those elements.
• Source Transfer Schemes: In the event of an undervoltage, a transfer signal may be generated to transfer a load
from its normal source to a standby or emergency power source.

GE Multilin G60 Generator Protection System 5-183


5.6 GROUPED ELEMENTS 5 SETTINGS

The undervoltage elements can be programmed to have a definite time delay characteristic. The definite time curve oper-
ates when the voltage drops below the pickup level for a specified period of time. The time delay is adjustable from 0 to
600.00 seconds in steps of 0.01. The undervoltage elements can also be programmed to have an inverse time delay char-
acteristic.
The undervoltage delay setting defines the family of curves shown below.
D
T = ---------------------------------
- (EQ 5.28)
⎛ 1 – ------------------
V ⎞
⎝ V ⎠
pickup

where: T = operating time


D = undervoltage delay setting (D = 0.00 operates instantaneously)
V = secondary voltage applied to the relay
Vpickup = pickup level
Time (seconds)

% of voltage pickup
842788A1.CDR

Figure 5–97: INVERSE TIME UNDERVOLTAGE CURVES


At 0% of pickup, the operating time equals the UNDERVOLTAGE DELAY setting.

NOTE

5-184 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

b) PHASE UNDERVOLTAGE (ANSI 27P)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ VOLTAGE ELEMENTS Ö PHASE UNDERVOLTAGE1(3)

„ PHASE PHASE UV1 Range: Disabled, Enabled


„ UNDERVOLTAGE1 FUNCTION: Disabled
PHASE UV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
PHASE UV1 MODE: Range: Phase to Ground, Phase to Phase
MESSAGE
Phase to Ground
PHASE UV1 Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
PICKUP: 1.000 pu
PHASE UV1 Range: Definite Time, Inverse Time
MESSAGE
CURVE: Definite Time
PHASE UV1 Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 1.00 s
PHASE UV1 MINIMUM Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
VOLTAGE: 0.100 pu
PHASE UV1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
PHASE UV1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
PHASE UV1 Range: Disabled, Enabled 5
MESSAGE
EVENTS: Disabled

This element may be used to give a desired time-delay operating characteristic versus the applied fundamental voltage
(phase-to-ground or phase-to-phase for wye VT connection, or phase-to-phase for delta VT connection) or as a definite
time element. The element resets instantaneously if the applied voltage exceeds the dropout voltage. The delay setting
selects the minimum operating time of the phase undervoltage. The minimum voltage setting selects the operating voltage
below which the element is blocked (a setting of “0” will allow a dead source to be considered a fault condition).

SETTING SETTING
PHASE UV1 PHASE UV1
FUNCTION: PICKUP:
Disabled = 0 PHASE UV1
Enabled = 1 CURVE:
PHASE UV1
SETTING DELAY: FLEXLOGIC OPERANDS
AND
PHASE UV1 AND RUN VAG or VAB < PICKUP PHASE UV1 A PKP
BLOCK: t PHASE UV1 A DPO
Off = 0 PHASE UV1 A OP
V
SETTING
SETTING AND RUN VBG or VBC< PICKUP PHASE UV1 B PKP

}
PHASE UV1
t PHASE UV1 B DPO
PHASE UV1 SOURCE: MINIMUM VOLTAGE:
PHASE UV1 B OP
VAG or VAB < Minimum
Source VT = Delta V
VBG or VBC < Minimum
VAB AND RUN VCG or VCA < PICKUP PHASE UV1 C PKP
VCG or VCA < Minimum
VBC t PHASE UV1 C DPO
VCA PHASE UV1 C OP
Source VT = Wye V
FLEXLOGIC OPERAND
SETTING OR PHASE UV1 PKP

PHASE UV1 MODE:

Phase to Ground Phase to Phase FLEXLOGIC OPERAND


VAG VAB OR PHASE UV1 OP
VBG VBC
VCG VCA
FLEXLOGIC OPERAND
AND PHASE UV1 DPO

827039AB.CDR

Figure 5–98: PHASE UNDERVOLTAGE1 SCHEME LOGIC

GE Multilin G60 Generator Protection System 5-185


5.6 GROUPED ELEMENTS 5 SETTINGS

c) PHASE OVERVOLTAGE (ANSI 59P)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ VOLTAGE ELEMENTS ÖØ PHASE OVERVOLTAGE1

„ PHASE PHASE OV1 Range: Disabled, Enabled


„ OVERVOLTAGE1 FUNCTION: Disabled
PHASE OV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
PHASE OV1 Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
PICKUP: 1.000 pu
PHASE OV1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 1.00 s
PHASE OV1 RESET Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 1.00 s
PHASE OV1 BLOCK: Range: FlexLogic™ Operand
MESSAGE
Off
PHASE OV1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
PHASE OV1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The phase overvoltage element may be used as an instantaneous element with no intentional time delay or as a definite
time element. The input voltage is the phase-to-phase voltage, either measured directly from delta-connected VTs or as cal-
5 culated from phase-to-ground (wye) connected VTs. The specific voltages to be used for each phase are shown below.

SETTINGS
SETTING
PHASE OV1 PICKUP
PHASE OV1 SETTING DELAY:
FUNCTION: FLEXLOGIC OPERANDS
PHASE OV1 PHASE OV1 RESET
Disabled = 0 PICKUP: DELAY: PHASE OV1 A PKP
Enabled = 1 PHASE OV1 A DPO
RUN tPKP
VAB ≥ PICKUP PHASE OV1 A OP
tRST
PHASE OV1 B PKP
SETTING
AND RUN tPKP PHASE OV1 B DPO
PHASE OV1 VBC ≥ PICKUP
BLOCK: PHASE OV1 B OP
tRST
RUN PHASE OV1 C PKP
Off = 0
VCA ≥ PICKUP tPKP PHASE OV1 C DPO
PHASE OV1 C OP
tRST
SETTING
PHASE OV1
SOURCE: FLEXLOGIC OPERAND
Source VT = Delta OR PHASE OV1 OP
VAB
VBC
FLEXLOGIC OPERAND
VCA
AND PHASE OV1 DPO
Source VT = Wye

FLEXLOGIC OPERAND
OR PHASE OV1 PKP
827066A7.CDR

Figure 5–99: PHASE OVERVOLTAGE SCHEME LOGIC


If the source VT is wye-connected, then the phase overvoltage pickup condition is V > 3 × Pickup for VAB, VBC,
and VCA.
NOTE

5-186 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

d) NEUTRAL OVERVOLTAGE (ANSI 59N)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ VOLTAGE ELEMENTS ÖØ NEUTRAL OV1(3)

„ NEUTRAL OV1 NEUTRAL OV1 Range: Disabled, Enabled


„ FUNCTION: Disabled
NEUTRAL OV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
NEUTRAL OV1 PICKUP: Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
0.300 pu
NEUTRAL OV1 CURVE: Range: Definite time, FlexCurve A, FlexCurve B,
MESSAGE FlexCurve C
Definite time
NEUTRAL OV1 PICKUP: Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 1.00 s
NEUTRAL OV1 RESET: Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 1.00 s
NEUTRAL OV1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
NEUTRAL OV1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
NEUTRAL OV1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled
5
There are three neutral overvoltage elements available. The neutral overvoltage element can be used to detect asymmetri-
cal system voltage condition due to a ground fault or to the loss of one or two phases of the source. The element responds
to the system neutral voltage (3V_0), calculated from the phase voltages. The nominal secondary voltage of the phase volt-
age channels entered under SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE BANK Ö PHASE VT SECONDARY is the
p.u. base used when setting the pickup level.
The neutral overvoltage element can provide a time-delayed operating characteristic versus the applied voltage (initialized
from FlexCurves A, B, or C) or be used as a definite time element. The NEUTRAL OV1 PICKUP DELAY setting applies only if
the NEUTRAL OV1 CURVE setting is “Definite time”. The source assigned to this element must be configured for a phase VT.
VT errors and normal voltage unbalance must be considered when setting this element. This function requires the VTs to
be wye-connected.

Figure 5–100: NEUTRAL OVERVOLTAGE1 SCHEME LOGIC

GE Multilin G60 Generator Protection System 5-187


5.6 GROUPED ELEMENTS 5 SETTINGS

e) NEGATIVE-SEQUENCE OVERVOLTAGE (ANSI 59_2)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ VOLTAGE ELEMENTS ÖØ NEG SEQ OV1(3)

„ NEG SEQ OV1 NEG SEQ OV1 Range: Disabled, Enabled


„ FUNCTION: Disabled
NEG SEQ OV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
NEG SEQ OV1 PICKUP: Range: 0.000 to 1.250 pu in steps of 0.001
MESSAGE
0.300 pu
NEG SEQ OV1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.50 s
NEG SEQ OV1 RESET Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.50 s
NEG SEQ OV1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
NEG SEQ OV1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
NEG SEQ OV1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

There are three negative-sequence overvoltage elements available.

5 The negative-sequence overvoltage element may be used to detect loss of one or two phases of the source, a reversed
phase sequence of voltage, or a non-symmetrical system voltage condition.

SETTING
NEG SEQ OV1
FUNCTION:
Disabled = 0
SETTING
Enabled = 1
NEG SEQ OV1 PICKUP: SETTINGS
SETTING NEG SEQ OV1 PICKUP
AND RUN DELAY:
NEG SEQ OV1 BLOCK: FLEXLOGIC OPERANDS
NEG SEQ OV1 RESET
NEG SEQ OV1 PKP
DELAY:
Off = 0 NEG SEQ OV1 DPO
t PKP
t RST NEG SEQ OV1 OP
SETTING
V_2 or 3 × V_2 ≥ PKP
NEG SEQ OV1 SIGNAL
SOURCE:
Wye VT Delta VT
V_2 3 × V_2 827839A3.CDR

Figure 5–101: NEGATIVE-SEQUENCE OVERVOLTAGE SCHEME LOGIC

5-188 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

f) AUXILIARY UNDERVOLTAGE (ANSI 27X)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ VOLTAGE ELEMENTS ÖØ AUXILIARY UV1(2)

„ AUXILIARY UV1 AUX UV1 Range: Disabled, Enabled


„ FUNCTION: Disabled
AUX UV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
AUX UV1 PICKUP: Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
0.700 pu
AUX UV1 CURVE: Range: Definite Time, Inverse Time
MESSAGE
Definite Time
AUX UV1 DELAY: Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
1.00 s
AUX UV1 MINIMUM: Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
VOLTAGE: 0.100 pu
AUX UV1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
AUX UV1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
AUX UV1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled
5
The G60 contains one auxiliary undervoltage element for each VT bank. This element is intended for monitoring undervolt-
age conditions of the auxiliary voltage. The AUX UV1 PICKUP selects the voltage level at which the time undervoltage ele-
ment starts timing. The nominal secondary voltage of the auxiliary voltage channel entered under SETTINGS ÖØ SYSTEM
SETUP Ö AC INPUTS ÖØ VOLTAGE BANK X5 ÖØ AUXILIARY VT X5 SECONDARY is the per-unit base used when setting the
pickup level.
The AUX UV1 DELAY setting selects the minimum operating time of the auxiliary undervoltage element. Both AUX UV1 PICKUP
and AUX UV1 DELAY settings establish the operating curve of the undervoltage element. The auxiliary undervoltage element
can be programmed to use either definite time delay or inverse time delay characteristics. The operating characteristics
and equations for both definite and inverse time delay are as for the phase undervoltage element.
The element resets instantaneously. The minimum voltage setting selects the operating voltage below which the element is
blocked.
SETTING
AUX UV1
FUNCTION: SETTING
Disabled=0
AUX UV1 PICKUP:
Enabled=1

AUX UV1 CURVE:


SETTING

AUX UV1 BLOCK: AUX UV1 DELAY:


FLEXLOGIC OPERANDS
Off=0 AND RUN Vx < Pickup AUX UV1 PKP
AUX UV1 DPO
SETTING
SETTING t AUX UV1 OP
AUX UV1 MINIMUM
AUX UV1 SIGNAL VOLTAGE:
SOURCE:
AUX VOLT Vx Vx < Minimum
V

827849A2.CDR

Figure 5–102: AUXILIARY UNDERVOLTAGE SCHEME LOGIC

GE Multilin G60 Generator Protection System 5-189


5.6 GROUPED ELEMENTS 5 SETTINGS

g) AUXILIARY OVERVOLTAGE (ANSI 59X)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ VOLTAGE ELEMENTS ÖØ AUXILIARY OV1(2)

„ AUXILIARY OV1 AUX OV1 Range: Disabled, Enabled


„ FUNCTION: Disabled
AUX OV1 SIGNAL Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
AUX OV1 PICKUP: Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
0.300 pu
AUX OV1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 1.00 s
AUX OV1 RESET Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 1.00 s
AUX OV1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
AUX OV1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
AUX OV1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

The G60 contains one auxiliary overvoltage element for each VT bank. This element is intended for monitoring overvoltage
conditions of the auxiliary voltage. The nominal secondary voltage of the auxiliary voltage channel entered under SYSTEM
5 SETUP Ö AC INPUTS ØÖ VOLTAGE BANK X5 ØÖ AUXILIARY VT X5 SECONDARY is the per-unit (pu) base used when setting the
pickup level.
In the G60, this element is used to detect stator ground faults by measuring the voltage across the neutral resistor.

SETTING
AUX OV1
FUNCTION:
Disabled=0
SETTING
Enabled=1
AUX OV1 PICKUP: SETTING
SETTING
AND RUN AUX OV1 PICKUP
DELAY :
AUX OV1 BLOCK:
AUX OV1 RESET
Off=0 DELAY :
FLEXLOGIC OPERANDS
Vx < Pickup tPKP
SETTING tRST AUX OV1 OP
AUX OV1 DPO
AUX OV1 SIGNAL
SOURCE: AUX OV1 PKP
AUXILIARY VOLT (Vx)
827836A2.CDR

Figure 5–103: AUXILIARY OVERVOLTAGE SCHEME LOGIC

5-190 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

h) VOLTS PER HERTZ (ANSI 24)


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ VOLTAGE ELEMENTS ÖØ VOLTS/HZ 1(2)

„ VOLTS/HZ 1 VOLTS/HZ 1 FUNCTION: Range: Disabled, Enabled


„ Disabled
VOLTS/HZ 1 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SRC 1
VOLTS/HZ 1 VOLTAGE: Range: Phase-ground, Phase-phase
MESSAGE
MODE: Phase-ground
VOLTS/HZ 1 PICKUP: Range: 0.80 to 4.00 pu in steps of 0.01
MESSAGE
1.00 pu
VOLTS/HZ 1 CURVE: Range: Definite Time, Inverse A, Inverse B, Inverse C,
MESSAGE FlexCurve A, FlexCurve B, FlexCurve C,
Definite Time
FlexCurve D
VOLTS/HZ 1 TD Range: 0.05 to 600.00 in steps of 0.01
MESSAGE
MULTIPLIER: 1.00
VOLTS/HZ 1 Range: 0.0 to 1000.0 s in steps of 0.1
MESSAGE
T-RESET: 1.0 s
VOLTS/HZ 1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
VOLTS/HZ 1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
VOLTS/HZ 1 EVENTS: Range: Disabled, Enabled 5
MESSAGE
Disabled

The per-unit volts-per-hertz (V/Hz) value is calculated using the maximum of the three-phase voltage inputs or the auxiliary
voltage channel Vx input, if the source is not configured with phase voltages. To use the V/Hz element with auxiliary volt-
age, set SYSTEM SETUP ÖØ SIGNAL SOURCES Ö SOURCE 1(6) ÖØ SOURCE 1(6) PHASE VT to “None” and SOURCE 1(6) AUX VT
to the corresponding voltage input bank. If there is no voltage on the relay terminals in either case, the per-unit V/Hz value
is automatically set to “0”. The per unit value is established as per voltage and nominal frequency power system settings as
follows:
1. If the phase voltage inputs defined in the source menu are used for V/Hz operation, then “1 pu” is the selected SYSTEM
SETUP Ö AC INPUTS ÖØ VOLTAGE BANK N ÖØ PHASE VT N SECONDARY setting, divided by the divided by the SYSTEM
SETUP ÖØ POWER SYSTEM Ö NOMINAL FREQUENCY setting.

2. If the voltage bank connection value is selected as “Delta”, then the phase-to-phase nominal voltage is used to define
the per-unit value. If the voltage bank connection value is selected as “Wye”, then the VOLTS/HZ 1 VOLTAGE MODE set-
ting further defines the operating quantity and per-unit value for this element. If the voltage mode is set as “Phase-
phase”, then the operating quantity for this element will be phase-to-phase nominal voltage. Likewise, if the voltage
mode is set to “Phase-ground”, then the operating quantity for this element will be the phase-to-ground nominal volt-
age. It is beneficial to use the phase-to-phase voltage mode for this element when the G60 device is applied on an iso-
lated or resistance-grounded system.
3. When the auxiliary voltage Vx is used (regarding the condition for “None” phase voltage setting mentioned above),
then the 1 pu value is the SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE BANK N ÖØ AUXILIARY VT N SECONDARY setting
divided by the SYSTEM SETUP ÖØ POWER SYSTEM Ö NOMINAL FREQUENCY setting.
4. If V/Hz source is configured with both phase and auxiliary voltages, the maximum phase among the three voltage
channels at any given point in time is the input voltage signal for element operation, and therefore the per-unit value
will be calculated as described in Step 1 above. If the measured voltage of all three phase voltages is 0, than the per-
unit value becomes automatically 0 regardless of the presence of auxiliary voltage.

GE Multilin G60 Generator Protection System 5-191


5.6 GROUPED ELEMENTS 5 SETTINGS

SETTINGS
Pickup
Voltage Mode
SETTINGS
Curve
Function
TD Multiplier
Enabled = 1
T-Reset
Disabled = 0
AND RUN
Block
t
Off = 0 FLEXLOGIC OPERANDS
VOLTS PER HERTZ 1 PKP
VOLTS PER HERTZ 1 DPO
SETTING
VOLTS PER HERTZ 1 OP
Source
V/Hz
V/Hz 828003A6.CDR

Figure 5–104: VOLTS PER HERTZ SCHEME LOGIC


The element has a linear reset characteristic. The reset time can be programmed to match the cooling characteristics of the
protected equipment. The element will fully reset from the trip threshold in VOLTS/HZ T-RESET seconds. The V/Hz element
may be used as an instantaneous element with no intentional time delay or as a Definite or Inverse timed element.
The characteristics of the inverse curves are shown below.
DEFINITE TIME:
For the definite time curve, T(sec.) = TD multiplier. For example, setting the TD multiplier to 20 results a time delay of 20
seconds to operate when above the Volts/Hz pickup setting. Instantaneous operation can be obtained the same way by set-
ting the TD multiplier to “0”.
INVERSE CURVE A:
The curve for the volts/hertz inverse curve A shape is derived from the formula:
TDM - when V
---- > Pickup
5 T = ------------------------------------------------
⎛ ----⎞ ⁄ Pickup – 1
V
⎝ F⎠
2 F
(EQ 5.29)

where: T = Operating Time


TDM = Time Delay Multiplier (delay in seconds)
V = fundamental RMS value of voltage (pu)
F = frequency of voltage signal (pu)
Pickup = volts-per-hertz pickup setpoint (pu)
The volts/hertz inverse A curves are shown below.
Time to trip (in seconds)

Time
delay
setting

Multiples of volts per hertz pickup


830738A1.CDR

Figure 5–105: VOLTS-PER-HERTZ CURVES, INVERSE CURVE A

5-192 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

INVERSE CURVE B:
The curve for the Volts/Hertz Inverse Curve B shape is derived from the formula:
TDM V
T = ---------------------------------------------- when ---- > Pickup (EQ 5.30)
⎛V F
----⎞
⎝ F⎠ ⁄ Pickup – 1

where: T = Operating Time


TDM = Time Delay Multiplier (delay in sec.)
V = fundamental RMS value of voltage (pu)
F = frequency of voltage signal (pu)
Pickup = volts-per-hertz pickup setpoint (pu)
The volts/hertz inverse B curves are shown below.
Time to trip (in seconds)

Time
delay
setting 5

Multiples of volts per hertz pickup


830739A1.CDR

Figure 5–106: VOLTS-PER-HERTZ CURVES, INVERSE CURVE B


INVERSE CURVE C:
The curve for the Volts/Hertz Inverse Curve C shape is derived from the formula:
TDM - when V
---- > Pickup
T = ----------------------------------------------------
0.5
(EQ 5.31)
⎛ ----⎞ ⁄ Pickup
V F
–1
⎝ F⎠

where: T = Operating Time


TDM = Time Delay Multiplier (delay in sec.)
V = fundamental RMS value of voltage (pu)
F = frequency of voltage signal (pu)
Pickup = volts-per-hertz pickup setpoint (pu)

GE Multilin G60 Generator Protection System 5-193


5.6 GROUPED ELEMENTS 5 SETTINGS

The volts/hertz inverse C curves are shown below.

Time to trip (in seconds)

Time
delay
setting

Multiples of volts per hertz pickup


830740A1.CDR

Figure 5–107: VOLTS-PER-HERTZ CURVES, INVERSE CURVE C

5.6.13 LOSS OF EXCITATION

PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ LOSS OF EXCITATION


5
„ LOSS OF LOSS OF EXCITATION Range: Disabled, Enabled
„ EXCITATION FUNCTION: Disabled
LOSS OF EXCITATION Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
LOSS OF EXCITATION Range: 0.10 to 300.00 ohms in steps of 0.01
MESSAGE
CENTER 1: 10.00 ohm
LOSS OF EXCITATION Range: 0.10 to 300.00 ohms in steps of 0.01
MESSAGE
RADIUS 1: 8.00 ohm
EXCITATION V SUPV 1: Range: Disabled, Enabled
MESSAGE
Enabled
LOSS OF EXCITATION Range: 0.000 to 65.535 s in steps of 0.01
MESSAGE
PKP DELAY1: 0.050 s
LOSS OF EXCITATION Range: 0.10 to 300.00 ohms in steps of 0.01
MESSAGE
CENTER 2: 12.00 ohm
LOSS OF EXCITATION Range: 0.10 to 300.00 ohms in steps of 0.01
MESSAGE
RADIUS 2: 10.00 ohm
LOSS OF EXCITATION Range: Disabled, Enabled
MESSAGE
V SUPV 2: Enabled
LOSS OF EXCITATION Range: 0.000 to 65.535 s in steps of 0.01
MESSAGE
PKP DELAY2: 0.500 s
LOSS OF EXCITATION Range: 0.000 to 1.250 pu in steps of 0.001
MESSAGE
UV SUPV: 0.700 pu
LOSS OF EXCIT BLK: Range: FlexLogic™ operand
MESSAGE
Off

5-194 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

LOSS OF EXCITATION Range: Self-reset, Latched, Disabled


MESSAGE
TARGET: Self-reset
LOSS OF EXCITATION Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The operating characteristic is shaped out of two offset mho circles shifted down along the imaginary axis as shown below.
X

X’d
2
C1 = Center of element 1 = (Zb + X’d) / 2
C1
C2

R1 = Radius of element 1 = Zb / 2

Zb
C2 = Center of element 2 = (Xd + X’d) / 2

R1
R2 = Radius of element 2 = Xd / 2

Xd
Zb = Base impedance of the machine

R2 X’d = Transient reactance of the machine

Xd = Synchronous reactance of the machine

830711A1.CDR

Figure 5–108: LOSS OF EXCITATION OPERATING CHARACTERISTICS


STAGE 1 SETTINGS:
The stage 1 characteristic is typically set to detect a loss of excitation for load conditions of 30% of the nominal or higher.
This is achieved with a mho element with a diameter equal to the base impedance of the machine and an offset equal to
5
half the machine transient reactance (X′d).
Zb + X′d
CENTER 1 = ----------------------- , RADIUS 1 = Zb
------- (EQ 5.32)
2 2
The stage 1 element should be time delayed to allow for blocking by the VT fuse failure element (50 ms).
STAGE 2 SETTINGS:
The stage 2 characteristic is typically set to detect a loss of excitation for all load conditions. This is achieved with a mho
element with a diameter equal to the synchronous reactance of the machine and an offset equal to half the machine tran-
sient reactance (X′d).
Xd + X′d
CENTER 2 = ----------------------- , RADIUS 1 = Xd
------- (EQ 5.33)
2 2
During stable power swing conditions the positive-sequence impedance may momentarily enter the stage 2 characteristic.
For security of the function under such conditions, it is recommended to delay stage 2 by a minimum of 0.5 seconds.
The LOSS OF EXCIT BLK setting specifies a FlexLogic™ operand for blocking the feature based on user-programmable con-
ditions. When the blocking input is asserted, the element resets its timers, de-asserts the PKP and OP operands (if
asserted), clears self-reset targets, logs a ‘blocked’ event if events are enabled, and becomes inactive. When unblocked,
the element will start functioning instantly. If exposed to pickup conditions for an extended period of time and unblocked, the
element will pickup and start timing out at the moment of unblocking.

GE Multilin G60 Generator Protection System 5-195


5.6 GROUPED ELEMENTS 5 SETTINGS

The element responds to the positive sequence impedance as shown below.


SETTING
LOSS OF EXCITATION
FUNCTION:
Disabled=0
Generator=1, Motor=1

SETTING SETTINGS
LOSS EXCIT BLK: LOSS OF EXCITATION
FUNCTION:
Off=0 BLOCK (See description) FLEXLOGIC OPERANDS
LOSS OF EXCITATION
CENTER 1: LOSS EXCIT STG1 PKP
COMPARATOR
SETTING LOSS EXCIT STG1 DPO
RUN LOSS OF EXCITATION
I_1 > 0.05 pu SETTING
LOSS OF EXCITATION UV RADIUS 1:
SUPV 1 : LOSS OF EXCITATION
AND RUN
PKP DELAY 1:
Disabled=1 FLEXLOGIC OPERAND
OR 0 ms
Enabled=0 LOSS EXCIT STG1 OP
20 ms 0 ms

LOSS OF EXCITATION FLEXLOGIC OPERANDS


SETTING
CENTER 2: LOSS EXCIT STG2 PKP
LOSS OF EXCITATION
LOSS OF EXCITATION LOSS EXCIT STG2 DPO
UV SUPV : SETTING
SETTING RADIUS 2:
RUN LOSS OF EXCITATION
LOSS OF EXCITATION UV |V_1| < PICKUP AND RUN
PKP DELAY 2:
SUPV 2 : OR FLEXLOGIC OPERAND
0 ms
Disabled=1 20 ms 0 ms LOSS EXCIT STG2 OP
Enabled=0
FLEXLOGIC OPERAND
SETTING OR LOSS EXCIT OP
LOSS OF EXCITATION
SOURCE: FLEXLOGIC OPERAND
I_1 OR LOSS EXCIT PKP
V_1
FLEXLOGIC OPERAND
830001AB.CDR LOSS EXCIT DPO

Figure 5–109: LOSS OF EXCITATION SCHEME LOGIC


5 5.6.14 ACCIDENTAL ENERGIZATION

PATH: SETTINGS Ø GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ ACCIDENTAL ENERGIZATION

„ ACCIDENTAL ACCDNT ENRG Range: Disabled, Enabled


„ ENERGIZATION FUNCTION: Disabled
ACCDNT ENRG SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SRC 1
ACCDNT ENRG ARMING Range: UV and Offline, UV or Offline
MESSAGE
MODE: UV and Offline
ACCDNT ENRG OC Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.300 pu
ACCDNT ENRG UV Range: 0.000 to 3.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.500 pu
ACCDNT ENRG OFFLINE: Range: FlexLogic™ operand
MESSAGE
Off
ACCDNT ENRG BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
ACCDNT ENRG TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
ACCDNT ENRG EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

This element provides protection against energization while the generator is at standstill or reduced speed. The feature is
armed using either the AND or OR combination of the undervoltage and machine off-line conditions, selected with the
ACCDNT ENRG ARMING MODE setting (see below). The undervoltage condition is determined from the measured voltages.
The machine off-line status is indicated by a dedicated FlexLogic™ operand. Once armed, the accidental energization fea-
ture operates upon detecting an overcurrent condition in any of the stator phases.

5-196 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

This feature can also provide protection against poor synchronization.


• ACCDNT ENRG ARMING MODE: This setting specifies whether the feature gets armed by either of the undervoltage
or machine off-line conditions (“UV or Off-line” value), or by both the conditions (“UV and Off-line” value). In both
cases, the element is armed after 5 seconds of the appropriate condition and de-armed 250 ms after the arming condi-
tion (UV and/or Off-line) ceases.
The “UV or Off-line” selection shall be made when the VTs are on the power system side of the disconnecting device.
If this is the case, the measured voltages may be normal regardless of the status of the protected machine, thus the
need for an OR condition. The “UV or Off-line” value provides protection against poor synchronization. During normal
synchronization, there should be relatively low current measured. If however, synchronization is attempted when con-
ditions are not appropriate, a large current would be measured shortly after closing the breaker. Since this feature does
not de-arm immediately, but after a 250 ms time delay, this will result in operation under imprecise synchronization.
The ACCDNT ENRG OC PICKUP setting can control the required precision of synchronization.
The “UV and Off-line” value shall be made when the VTs are on the generator side of the disconnecting device. If this
is the case, both the undervoltage and machine off-line conditions are required to indicate that the protected generator
is not energized.
• ACCDNT ENRG OC PICKUP: This setting specifies the current level required to operate the armed Accidental Energi-
zation element. If any of the phase current is above the ACCDNT ENRG OC PICKUP level, the feature operates.
• ACCDNT ENRG UV PICKUP: This setting specifies the voltage level required to arm the Accidental Energization ele-
ment. All of the line-to-line voltages must drop below the ACCDNT ENRG UV PICKUP level in order to detect the undervolt-
age condition. The setting is entered in voltage pu values. As the element always responds to the line-to-line voltages,
care must be applied in picking up the value depending on the VT connection.
• ACCDNT ENRG OFFLINE: This setting specifies the FlexLogic™ operand indicating that the protected generator is
off-line.
5
SETTING
ACCDNT ENRG
FUNCTION:
Disabled = 0
SETTINGS
Enabled = 1
ACCDNT ENRG OC
PICKUP:
SETTING
AND RUN
ACCDNT ENRG IA > Pickup
BLOCK:
RUN
Off = 0 IB > Pickup OR

RUN
SETTING IC > Pickup

ACCDNT ENRG
SOURCE: SETTINGS
IA ACCDNT ENRG UV
IB PICKUP:
FLEXLOGIC OPERANDS
IC RUN
AND ACCDNT ENRG OP
VT CONNECTION VAB < Pickup
ACCDNT ENRG DPO
WYE DELTA RUN
VBC < Pickup AND
VAG - VBG VAB
VBG - VCG VBC RUN
VCA < Pickup AND
VCG - VAG VCA

SETTING
5s
ACCDNT ENRG OR
0.25 s FLEXLOGIC OPERAND
OFFLINE: OR
ACCDNT ENRG ARMED
Off = 0

SETTING AND
ACCDNT ENRG
ARMING MODE:
UV or Offline = 1 830004A3.CDR

Figure 5–110: ACCIDENTAL ENERGIZATION SCHEME LOGIC

GE Multilin G60 Generator Protection System 5-197


5.6 GROUPED ELEMENTS 5 SETTINGS

5.6.15 SENSITIVE DIRECTIONAL POWER

PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ POWER ÖØ SENSITIVE DIRECTIONAL POWER
Ö DIRECTIONAL POWER 1(2)
„ DIRECTIONAL DIR POWER 1 Range: Disabled, Enabled
„ POWER 1 FUNCTION: Disabled
DIR POWER 1 Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC 1
DIR POWER 1 Range: 0 to 359° in steps of 1
MESSAGE
RCA: 0°
DIR POWER 1 Range: 0 to 0.95° in steps of 0.05
MESSAGE
CALIBRATION: 0.00°
DIR POWER 1 STG1 Range: –1.200 to 1.200 pu in steps of 0.001
MESSAGE
SMIN: 0.100 pu
DIR POWER 1 STG1 Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.50 s
DIR POWER 1 STG2 Range: –1.200 to 1.200 pu in steps of 0.001
MESSAGE
SMIN: 0.100 pu
DIR POWER 1 STG2 Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 20.00 s

5 MESSAGE
DIR POWER 1 BLK:
Off
Range: FlexLogic™ operand

DIR POWER 1 Range: Self-Reset, Latched, Disabled


MESSAGE
TARGET: Self-Reset
DIR POWER 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The sensitive directional power element responds to three-phase directional power and is designed for reverse power and
low forward power applications for synchronous machines or interconnections involving co-generation. The relay measures
the three-phase power from either full set of wye-connected VTs or full-set of delta-connected VTs. In the latter case, the
two-wattmeter method is used. Refer to the UR-series metering conventions section in chapter 6 for details regarding the
active and reactive powers used by the sensitive directional power element.
The element has an adjustable characteristic angle and minimum operating power as shown in the Directional power char-
acteristic diagram. The element responds to the following condition:
P cos θ + Q sin θ > SMIN (EQ 5.34)

where: P and Q are active and reactive powers as measured per the UR-series metering convention,
θ is a sum of the element characteristic (DIR POWER 1 RCA) and calibration (DIR POWER 1 CALIBRATION) angles, and
SMIN is the minimum operating power
The operating quantity is displayed in the ACTUAL VALUES Ö METERING ÖØ SENSITIVE DIRECTIONAL POWER 1(2) actual
value. The element has two independent (as to the pickup and delay settings) stages for alarm and trip, respectively.

5-198 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

n
io
ct
re
Di
OPERATE
RCA+
CALIBRATION
SMIN
P
+
RESTRAIN
-

Figure 5–111: DIRECTIONAL POWER CHARACTERISTIC


By making the characteristic angle adjustable and providing for both negative and positive values of the minimum operating
power a variety of operating characteristics can be achieved as presented in the figure below. For example, section (a) in
the figure below shows settings for reverse power, while section (b) shows settings for low forward power applications.

(a) Q (b) Q

RESTRAIN
OPERATE RESTRAIN OPERATE
P P

RCA = 180o RCA = 180o


5
SMIN > 0 SMIN < 0

(c) Q (d) Q

OPERATE OPERATE

P P

RESTRAIN RESTRAIN
RCA = 0o RCA = 0o
SMIN < 0 SMIN > 0

(e) Q
OPERATE
(f) Q
RESTRAIN

RESTRAIN OPERATE

P P

RCA = 90o RCA = 270o


SMIN > 0 SMIN < 0

842702A1.CDR

Figure 5–112: DIRECTIONAL POWER ELEMENT SAMPLE APPLICATIONS

GE Multilin G60 Generator Protection System 5-199


5.6 GROUPED ELEMENTS 5 SETTINGS

• DIR POWER 1 RCA: Specifies the relay characteristic angle (RCA) for the sensitive directional power function. Appli-
cation of this setting is threefold:
1. It allows the element to respond to active or reactive power in any direction (active overpower/underpower, etc.).
2. Together with a precise calibration angle, it allows compensation for any CT and VT angular errors to permit more
sensitive settings.
3. It allows for required direction in situations when the voltage signal is taken from behind a delta-wye connected
power transformer and the phase angle compensation is required.
For example, the active overpower characteristic is achieved by setting DIR POWER 1 RCA to “0°”, reactive overpower by
setting DIR POWER 1 RCA to “90°”, active underpower by setting DIR POWER 1 RCA to “180°”, and reactive underpower by
setting DIR POWER 1 RCA to “270°”.
• DIR POWER 1 CALIBRATION: This setting allows the relay characteristic angle to change in steps of 0.05°. This may
be useful when a small difference in VT and CT angular errors is to be compensated to permit more sensitive settings.
This setting virtually enables calibration of the directional power function in terms of the angular error of applied VTs
and CTs. The element responds to the sum of the DIR POWER 1 RCA and DIR POWER 1 CALIBRATION settings.
• DIR POWER 1 STG1 SMIN: This setting specifies the minimum power as defined along the relay characteristic angle
(RCA) for the stage 1 of the element. The positive values imply a shift towards the operate region along the RCA line;
the negative values imply a shift towards the restrain region along the RCA line. Refer to the Directional power sample
applications figure for details. Together with the RCA, this setting enables a wide range of operating characteristics.
This setting applies to three-phase power and is entered in per-unit (pu) values. The base quantity is 3 × VT pu
base × CT pu base.
For example, a setting of 2% for a 200 MW machine is 0.02 × 200 MW = 4 MW. If 7.967 kV is a primary VT voltage and
10 kA is a primary CT current, the source pu quantity is 239 MVA, and thus, SMIN should be set at 4 MW / 239 MVA =
0.0167 pu ≈ 0.017 pu. If the reverse power application is considered, RCA = 180° and SMIN = 0.017 pu.
5 The element drops out if the magnitude of the positive-sequence current becomes virtually zero, that is, it drops below
the cutoff level.
• DIR POWER 1 STG1 DELAY: This setting specifies a time delay for stage 1. For reverse power or low forward power
applications for a synchronous machine, stage 1 is typically applied for alarming and stage 2 for tripping.

SETTING
DIR POWER 1
FUNCTION:
Enabled = 1
SETTINGS SETTING
SETTING DIR POWER 1 RCA: DIR POWER 1 STG1
DIR POWER 1 BLK: DELAY:
AND

DIR POWER 1 tPKP


CALIBRATION:
Off = 0
DIR POWER 1 STG1 100 ms
SMIN:
FLEXLOGIC OPERANDS
DIR POWER 1 STG2 FLEXLOGIC™ OPERANDS
SETTING SMIN: DIR POWER 1 STG1 OP
RUN DIR POWER 1 STG1 DPO
DIR POWER 1 SOURCE: DIR POWER 1 DPO
DIR POWER 1 STG1 PKP
OR

DIRECTIONAL POWER DIR POWER 1 PKP


Three-phase active power (P)
CHARACTERISTICS DIR POWER 1 STG2 PKP
OR

DIR POWER 1 OP
Three-phase reactive power (Q)
DIR POWER 1 STG2 DPO
DIR POWER 1 STG2 OP

SETTING
DIR POWER 1 STG2
DELAY:
tPKP

100 ms
842003A3.CDR

Figure 5–113: SENSITIVE DIRECTIONAL POWER SCHEME LOGIC

5-200 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

5.6.16 STATOR GROUND

a) MAIN MENU
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ STATOR GROUND

„ STATOR STATOR GROUND Range: SRC 1, SRC 2, SRC 3, SRC 4


„ GROUND SOURCE: SRC1
„ 100% STATOR
MESSAGE See page 5–202.
„ GROUND
„ 3RD HARM NTRL
MESSAGE See page 5–205.
„ UNDERVOLTAGE
„ SH STATOR
MESSAGE See page 5–207.
„ GROUND

Three means of stator ground fault protection are provided:


• 100% stator ground protection that uses third harmonic signals at the neutral of the machine and in the zero-sequence
voltage of the machine terminals.
• Third harmonic neutral undervoltage protection that responds to the third harmonic in the voltage at the machine neu-
tral point.
• 100% stator ground protection based on sub-harmonic injection.
The three protection elements are configured through their individual setting menus. They share the STATOR GROUND
SOURCE setting. This setting specifies a signal source used to provide current and voltage signals for stator ground fault
protection. 5
For the 100% stator ground protection function, the stator ground source shall be configured as follows:
• Phase voltages measured at the terminal of the machine shall be configured as phase VT banks. The element extracts
the third harmonic of the zero-sequence voltage from the phase voltages in order to operate. The VTs must be con-
nected in wye.
• Voltage measured at the neutral of the machine shall be configured as the auxiliary VT bank. The element extracts the
third harmonic of the auxiliary voltage from the source in order to operate.
For the third harmonic neutral undervoltage protection function, the stator ground source shall be configured as follows:
• Phase voltages measured at the terminal of the machine shall be configured as phase VT banks. The element uses
the voltages to measure the power at the machine terminals for power supervision.
• Phase currents measured at the terminal of the machine shall be configured as phase CT banks. The element uses
the currents to measures the power at the machine terminals for power supervision.
• Voltage measured at the neutral of the machine shall be configured as the auxiliary VT bank. The element extracts the
third harmonic of the auxiliary voltage from the source in order to operate.
For the sub-harmonic injection based 100% stator ground protection, the stator ground source shall be configured as fol-
lows:
• Voltage measured at the neutral of the machine shall be configured as the auxiliary VT bank. The element extracts the
20 Hz component of the auxiliary voltage from the source in order to calculate resistance. The fundamental frequency
component from the same input is extracted when the same source is configured for auxiliary overvoltage protection
element to provide 95% stator ground fault protection. The auxiliary VT connection setting should be chosen as “Vn”
for this element.
• Current measured at the secondary of the neutral grounding transformer of the machine shall be configured as the
sensitive ground CT bank. The element extracts the 20 Hz component of the ground current from the source in order to
calculate resistance.
• This source can be independent of any of the other inputs from the generator such as neutral end CTs, terminal end
CTs and terminal VTs. Or these auxiliary VT and sensitive ground CT can be combined with either neutral side or ter-
minal side inputs within the same source settings.

GE Multilin G60 Generator Protection System 5-201


5.6 GROUPED ELEMENTS 5 SETTINGS

• In addition the relay should be set properly with frequency tracking enabled and the source used as FREQUENCY AND
PHASE REFERENCE should be the one connected to generator terminal VTs. The tracking frequency, which is essen-
tially the generator frequency, will be used to block the sub-harmonic stator ground protection and auxiliary over volt-
age protection in the frequency range of 15 to 25 Hz.

b) 100% STATOR GROUND


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö STATOR GROUND ÖØ 100% STATOR GROUND

„ 100% STATOR 100% STATOR GROUND Range: Disabled, Enabled


„ GROUND FUNCTION: Disabled
100% STATOR GND STG1 Range: 0.000 to 0.900 pu in steps of 0.001
MESSAGE
PICKUP: 0.150 pu
100% STATOR GND STG1 Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 1.00 s
100% STATOR GND STG1 Range: 0.0010 to 0.1000 pu in steps of 0.0001
MESSAGE
SUPV: 0.0057 pu
100% STATOR GND STG2 Range: 0.000 to 0.900 pu in steps of 0.001
MESSAGE
PICKUP: 0.150 pu
100% STATOR GND STG2 Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.00 s
100% STATOR GND STG2 Range: 0.0010 to 0.1000 pu in steps of 0.0001
MESSAGE
SUPV: 0.0045 pu
5 MESSAGE
100% STATOR GND BLK: Range: FlexLogic™ operand
Off
100% STATOR GROUND Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
100% STATOR GROUND Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The 100% stator ground function responds to third harmonic voltage measured at the generator neutral and output termi-
nals. When used in conjunction with the neutral overvoltage (fundamental frequency) element, it provides 100% ground
fault protection of the stator windings. Since the amount of third harmonic voltage that appears in the neutral is both load
and machine dependent, the protection method of choice is an adaptive method. The following formula is used to create an
adaptive operating quantity based on the amount of third harmonic that appears at the generator terminals.
V N ( 3rd ) V 0 ( 3rd )
--------------------------------------------- < Pickup and --------------------------------------------- > 1 – Pickup and V N ( 3rd ) + V 0 ( 3rd ) > Supervision (EQ 5.35)
V N ( 3rd ) + V 0 ( 3rd ) V N ( 3rd ) + V 0 ( 3rd )

where: VN(3rd) is a magnitude of the 3rd harmonic in the voltage measured at the machine neutral point measured via an
auxiliary channel of the VT bank, and
V0(3rd) is a magnitude of the 3rd harmonic in the zero-sequence voltage measured at the machine terminals.
This element requires wye-connected VTs for measurement of the third harmonic in the zero-sequence
voltage at the generator output terminals.
NOTE

Example 1: Operating quantities under normal conditions.


Consider the figure shown below. In the case of a high impedance grounded machine, the neutral resistor is typically cho-
sen such that power dissipated in the resistor during a single line to ground fault is approximately equal to the reactive
power produced by the zero sequence capacitance of the stator winding and the GSU LV winding ( X oc ). At power system
frequencies, the neutral resistance is therefore equal to X oc ⁄ 3 , and at 3 × F n , the neutral resistance is X oc .
For analysis, assume that E 3 = 10 V , R = 5Ω, and X c = 5Ω .

5-202 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

E3
E3
E3

k
Vn
Va Vb Vc

Vn (3rd)
< Pickup
Vn (3rd) + V0 (3rd)
Va (3rd)
and

V0 (3rd) Vb (3rd)
Vn (3rd) > 1 - Pickup S
Vn (3rd) + V0 (3rd) 3V0 (3rd) Vc (3rd)
and

Vn (3rd) + V0 (3rd) > Supervision

830737A1.CDR

Figure 5–114: 100% STATOR GROUND APPLICATION EXAMPLE 5


We have the magnitude of neutral voltage VN as:
R×E 10 × 5 10
V N = -----------------3- = ---------------- V = ---------- V
R – jX c 5 – j5 1–j (EQ 5.36)
⇒ V N = 7.07 V

and the magnitude of the neutral and zero-sequence voltages V N + V 0 as:


– jX c × E 3 – j50 – j10
- = -------------- = ----------- ⇒ V N + V 0 = 10 – j10-
V 0 = ----------------------- --------------------
R – jX c 5 – j5 1 – j 1–j (EQ 5.37)
⇒ V N + V 0 = 10 pu

Therefore, under the normal conditions described above, we set the operating quantities as follows:
VN
Pickup > ----------------------- = 7.07
----------- = 0.707 pu
VN + V0 10 (EQ 5.38)
Supervision < V N + V 0 = 10 pu

In actual practice, the |VN| / |VN + V0| ratio may vary from 0.4 to 0.85 under normal conditions. The pickup and supervision
setpoints are determined by evaluating the operating quantities during a fault condition (refer to example 2 for details).

Example 2: Operating quantities for a fault at a fraction k from the neutral grounding point.
For analysis, consider the above figure and assume that E 3 = 10 V , R = 5Ω, X c = 5Ω, and k = 0.15 .
In this case, we have the magnitude of the neutral voltage at:
V N = k × E 3 = 0.15 × 10 = 1.5 (EQ 5.39)

and the magnitude of the neutral and zero-sequence voltages V N + V 0 as:

GE Multilin G60 Generator Protection System 5-203


5.6 GROUPED ELEMENTS 5 SETTINGS

( 1 – k )E 3 + ( 1 – k )E 3 + ( 1 – k )E 3 3 × 0.85 × 10
- = ---------------------------------- = 8.5 ⇒ V N + V 0 = 8.5 + 1.5 = 10
V 0 = ------------------------------------------------------------------------------------
3 3 (EQ 5.40)
⇒ V N + V 0 = 10 pu

Therefore, for faults at a fraction k = 0.15 from the neutral grounding point, we set the operating quantities as follows:
VN 1.5
Pickup > ----------------------- = -------- = 0.15 pu
VN + V0 10 (EQ 5.41)
Supervision < V N + V 0 = 10 pu

The 100% stator ground settings are described below.


• 100% STATOR GND STG1 PICKUP: This setting specifies a pickup level for the operating quantity. It may be benefi-
cial to measure the operating quantity under various load conditions for a particular machine in order to optimize this
setting. This can be achieved using the actual values menu of the G60.
• 100% STATOR GND STG1 DELAY: This setting specifies a time delay required to operate after the pickup condition is
established.
• 100% STATOR GND STG1 SUPV: This setting specifies a signal level supervision for the vectorial sum of the third
harmonic at the machine neutral and in the zero-sequence terminal voltage. The setting is entered as a per-unit value
of the terminal voltages. Different settings may be considered for stages 1 and 2 as one of them could be used for
alarm and the other for trip. The safe value of this setting could be established after putting a given machine into ser-
vice and reading the quantity from the relay under ACTUAL VALUES menu.

SETTING
100% STATOR GND STG1
5 SETTING
PICKUP:
100% STATOR GND STG1
100% STATOR GROUND SUPV:
FUNCTION:
100% STATOR GND STG2 SETTING
Disabled=0
PICKUP: 100% STATOR GND STG1
Enabled=1
100% STATOR GND STG2 DELAY:
FLEXLOGIC OPERAND
SUPV: t PKP
SETTING 100% STATOR STG1 OP
AND RUN 20 ms
100% STATOR GND BLK: Vaux
< Pickup FLEXLOGIC OPERAND
Vaux + V_0 FLEXLOGIC OPERANDS
Off=0 100% STATOR DPO
& 100% STATOR STG1 DPO
V_0 AND 100% STATOR STG1 PKP
SETTING < 1-Pickup
Vaux + V_0 FLEXLOGIC OPERAND
STATOR GROUND
SOURCE: & OR 100% STATOR PKP
Vaux (3rd harmonic) Vaux + V_0 < Supv FLEXLOGIC OPERANDS
V_0 (3rd harmonic) AND 100% STATOR STG2 PKP
V_1 (fundamental) 100% STATOR STG2 DPO
V_1 > 0.5 pu
FLEXLOGIC OPERAND
SETTING
OR 100% STATOR OP
100% STATOR GND STG2
DELAY:
FLEXLOGIC OPERAND
t PKP
100% STATOR STG2 OP
20 ms
830003A5.CDR

Figure 5–115: 100% STATOR GROUND SCHEME LOGIC

5-204 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

c) THIRD HARMONIC NEUTRAL UNDERVOLTAGE


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ STATOR GROUND ÖØ 3RD HARM NTRL UNDERVOLTAGE

„ 3RD HARM NTRL 3RD HARM NTRL UV Range: Disabled, Enabled


„ UNDERVOLTAGE FUNCTION: Disabled
3RD HARM NTRL UV Range: 0.0000 to 3.0000 pu in steps of 0.0001
MESSAGE
PICKUP: 0.3000 pu
3RD HARM NTRL UV PKP Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.00 s
3RD HARM NTRL UV MAX Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
POWER: 0.200 pu
3RD HARM NTRL UV MIN Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
POWER: 0.200 pu
3RD HARM NTRL UV Range: 0.000 to 1.250 pu in steps of 0.001
MESSAGE
VOLT SUPV: 0.500 pu
3RD HARM NTRL UV BLK: Range: FlexLogic™ operand
MESSAGE
Off
3RD HARM NTRL UV Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
3RD HARM NTRL UV Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled
5
The third harmonic neutral undervoltage function detects a loss of third harmonic voltage at the generator neutral. The per-
centage of stator winding covered by this function depends on the pickup setting and the amount of third harmonic gener-
ated by the machine at the time of the fault. A settable window of forward power can supervise this element for enhanced
security. The element is also supervised by positive-sequence voltage measured at the generator output terminals. This
element can be used with either wye or delta connected VTs on the terminal side and requires the machine neutral voltage
to be connected via an auxiliary voltage channel of a relay VT bank.
• 3RD HARM NTRL UV PICKUP: This setting specifies the pickup level for the magnitude of the third harmonic of the
neutral voltage. This setting is entered in pu of the nominal auxiliary voltage.
The magnitude of the third harmonic voltage at the neutral point is monitored in the ACTUAL VALUES ÖØ METERING ÖØ
STATOR GROUND menu. Measuring the actual value of the operating quantity for a specific machine under variety of
load conditions may be helpful when selecting the pickup threshold for this feature.
• 3RD HARM NTRL UV MAX POWER: This setting specifies the maximum active power that inhibits this protection
function. If the measured power is below this setting but above the 3RD HARM NTRL UV MIN POWER setting the element
shall not operate. This setting applies to three-phase power and is entered in pu. The base quantity is 3 × VT pu
base × CT pu base.
For example, a setting of 20% for a 200 MW machine, is 0.20 × 200 MW = 40 MW. If 7.967 kV is a primary VT voltage
and 10 kA is a primary CT current, the source pu quantity is 239 MVA, and thus, the pu power setting is 40 MW /
239 MVA = 0.167 pu.
• 3RD HARM NTRL UV MIN POWER: This setting specifies the minimum active power that inhibits this protection func-
tion. If the measured power is above this setting but below the 3RD HARM NTRL UV MAX POWER setting the element shall
not operate. If the 3RD HARMONIC NTRL UV MIN POWER is set to “0.00 pu”, then the element will not operate for all power
values less than the 3RD HARM NTRL UV MAX POWER setting.
This setting applies to three-phase power and is entered in pu. The base quantity is 3 × VT pu base × CT pu base.

GE Multilin G60 Generator Protection System 5-205


5.6 GROUPED ELEMENTS 5 SETTINGS

SETTING
3RD HARM NTRL UV
FUNCTION:
Disabled = 0
SETTINGS
Enabled = 1
3RD HARM NTRL UV
PICKUP:
SETTING
AND RUN
Vaux < Pickup
3RD HARM NTRL UV BLK:

Off = 0
SETTINGS SETTINGS
FLEXLOGIC OPERANDS
3RD HARM NTRL UV 3RD HARM NTRL UV
3RD HARM NTRL UV PKP
MAX POWER: PKP DELAY:
SETTING 3RD HARM NTRL UV DPO
3RD HARM NTRL UV
STATOR GROUND AND 3RD HARM NTRL UV OP
MIN POWER: 20 ms
SOURCE:
RUN
Vaux (3rd harmonic)
3 Phase Real Power Min < 3 Phase Power < Max
V_1

SETTINGS
3RD HARM NTRL UV
VOLT SUPV:
830005A4.CDR
RUN
V_1 > Pickup

Figure 5–116: THIRD HARMONIC NEUTRAL UNDERVOLTAGE SCHEME LOGIC

5-206 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

d) SUB-HARMONIC STATOR GROUND FAULT


PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö STATOR GROUND ÖØ SH STATOR GROUND

„ SH STATOR SH STATOR GROUND Range: Disabled, Enabled


„ GROUND FUNCTION: Disabled
SH STATOR GND STG1 Range: 1 to 20 kΩ in steps of 1
MESSAGE
PICKUP: 10 kΩ
SH STATOR GND STG1 Range: 0.1 to 600.0 s in steps of 0.1
MESSAGE
DELAY: 10.0 s
SH STATOR GND STG2 Range: 1 to 20 kΩ in steps of 1
MESSAGE
PICKUP: 10 kΩ
SH STATOR GND STG2 Range: 0.1 to 600.0 s in steps of 0.1
MESSAGE
DELAY: 10.0 s
SH CT ANGLE COMPEN: Range: –30.00 to 30.00° in steps of 0.01
MESSAGE
0.00°
SH STATOR GND OC Range: 0.001 to 1.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.010 pu
SH STATOR GND OC Range: 0.10 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 1.00 s
SH STATOR GND Vsupv: Range: 0.000 to 0.100 pu in steps of 0.001
MESSAGE
0.000 pu
SH STATOR GND Isupv: Range: 0.000 to 0.100 pu in steps of 0.001 5
MESSAGE
0.000 pu
SH STATOR GND BLK: Range: FlexLogic™ operand
MESSAGE
Off
SH STATOR GROUND Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
SH STATOR GROUND Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

A voltage source placed at the neutral of the generator will produce a current for ground faults anywhere on the stator wind-
ing. This source is coupled to the primary circuit using the existing neutral grounding transformer. The following figure
shows a typical high impedance grounded generator that is protected against ground faults using the sub-harmonic injec-
tion method. The neutral resistor is chosen to limit the ground fault current to a low value (less than 25 A) in order to mini-
mize damage. A sub-harmonic frequency voltage signal is injected into the neutral of the generator. Under normal
conditions a resulting current flows through the surge capacitors (Cs) and through the stray capacitance of the stator and
step-up transformer windings. When a ground fault develops on the stator winding, an additional current flows through the
resistance RG. The value of RG is derived from the measurement of the injected voltage and the resulting current.
An AC signal is injected so that it can be coupled through an injection transformer to the primary circuit. The signal is of a
low frequency in order to minimize the effects of the capacitance of the primary circuit. A frequency of 20 Hz is chosen.
Referring to the following figure, the admittance seen looking into the grounding transformer is:

2 IG 1
Y = N × ------- = -------- + jωC T (EQ 5.42)
VX RG

In the above equation:


• RG is the ground fault resistance.
• CT is the total capacitance to ground.
• N is the neutral grounding transformer ratio.

GE Multilin G60 Generator Protection System 5-207


5.6 GROUPED ELEMENTS 5 SETTINGS

• VX is the measured sub-harmonic voltage.


• IG is the measured sub-harmonic current.
The ground fault resistance can be easily calculated by measuring the 20 Hz voltage and current phasors at the secondary
of the grounding transformer. This is done by the G60. An overcurrent element responding to the sub-harmonic provides
backup protection.
For machines that may operate at sub-synchronous frequencies (for instance a gas turbine that employs static starting), the
function is blocked at frequencies between 15 and 25 Hz. This ensures that the voltage and current produced by the gener-
ator does not leak into the sub-harmonic ground fault measurements.

Stator Step Up
winding Transformer
Grounding
IG transformer

20 Hz
injection
Coupling VX Neutral
module
filter resistor

RG Cst Csurge Cst

UR-series Auxiliary Sensitive


G60 IED voltage ground
input input CT
830750A1.CDR

Figure 5–117: STATOR GROUND FAULT DETECTION BY SUB-HARMONIC INJECTION


In addition, a check for minimum values of injected voltage and current guards against a failure of the injection unit or a
5 short or open circuit in the external circuit. In addition, the critical-fail relay contact of the 20 Hz generator can also be con-
nected to one of the contact inputs of G60 and the sub-harmonic stator ground element may be blocked.
The stator ground source settings determine the signals that are applied for VX, IG, and frequency. The resistance is
reported in primary ohms. Therefore the VT ratio setting of the auxiliary VT input must match the turns ratio of the neutral
grounding transformer and the CT primary setting of the ground CT input must match that of the CT used to measure
ground current.
When the magnitude of RG is large the resulting current IG will be very small therefore the G60 sensitive ground input
should be used to make this measurement. Thus a CT/VT module with sensitive ground current input should be present in
a G60 if it were to be used for sub-harmonic stator ground protection.
Accessory modules required for sub-harmonic injection based stator ground protection:
• 20 Hz injection module (GE Multilin order code): GPM-S-G.
• Coupling filter (GE Multilin order code): GPM-S-B.
• Current transformer (GE order code): 204-SD-43737.
The following settings are available for the sub-harmonic stator ground fault feature.
• SH STATOR GND STG1 PICKUP: If the measured stator ground primary resistance is less than the value specified by
this setting, the stage 1 element will pickup. Normally stage 1 is used to raise alarms and typical settings may fall in the
range of 5 to 10 kΩ. This setting is given in primary ohms.
• SH STATOR GND STG1 DELAY: This setting specifies a time delay for stage 1. Typical settings are in the range of 5
to 10 seconds. This delay will have to be added to the operating time of the element to obtain the overall delay.
• SH STATOR GND STG2 PICKUP: If the measured stator ground primary resistance is less than the value specified
this setting, stage 2 element will pickup. Normally stage 2 is used to raise trip signals and typical settings may fall in the
range of 1 to 5 kΩ. This setting is given in primary ohms.
• SH STATOR GND STG2 DELAY: This setting specifies a time delay for stage 2. Typical settings are in the range of 1
to 2 seconds. This delay will have to be added to the operating time of the element to obtain the overall delay.
• SH CT ANGLE COMPEN: The CT used may introduce phase shifts and this should be compensated for accurate fault
resistance calculations. Perform a test during commissioning at no fault condition by measuring the SH CURRENT
ANGLE reported by the G60. In a healthy machine, the SH impedance is purely capacitive and the angle should be 90°.

5-208 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

The difference in angle can be used as the SH CT ANGLE COMPEN setting. The preferred method of doing this is by
inserting a resistance equal to the SH STATOR GND STG2 PICKUP setting at the neutral of the generator and compensat-
ing the angle at this setting.
• SH STATOR GND OC PICKUP: This setting specifies the backup overcurrent pickup level based on sub-harmonic cur-
rent. This protection can be used in addition to the sub-harmonic injection based 100% ground fault and fundamental
phasor over voltage based 95% ground fault protection. One per-unit value of current is the sensitive ground CT sec-
ondary rating setting, which is always 5 A since the CT used is rated for 5 A secondary.
• SH STATOR GND OC DELAY: This setting specifies a time delay for sub-harmonic current based backup over current
protection. Thermal capabilities of the loading resistor or neutral grounding transformer should be considered while
setting this delay.
• SH STATOR GND Vsupv: The 20 Hz source can be monitored using this voltage supervision. This setting in pu pro-
vides the voltage level below which if the sub-harmonic voltage phasor magnitude remains for a period of 10 seconds,
the SH STATOR GND TRB OP operand will be asserted. One per-unit value of voltage is the auxiliary VT nominal sec-
ondary voltage setting or the equivalent primary voltage if used in primary. A typical setting of 1 V is suggested. How-
ever, when the neutral grounding transformer’s load resistance is less than 0.5 ohms, the use of voltage supervision is
not recommended.
• SH STATOR GND Isupv: The 20 Hz source can be monitored using this current supervision. This setting in per-unit
values provides the current level below which if the sub-harmonic current phasor magnitude remains for a period of 10
seconds, the SH STATOR GND TRB OP operand will be asserted. One per-unit current is the sensitive ground CT sec-
ondary rating setting or the primary rating if used in primary. A typical setting of 0.002 pu (=10 mA in secondary) is rec-
ommended with the provided 5 A secondary CT.
The logic for the sub-harmonic stator ground fault feature is shown below.

SETTINGS
Function
5
= Enabled
Block SETTING SETTING
= Off Stage 1 Pickup Stage 1 Pickup Delay
AND RUN TPKP FLEXLOGIC OPERANDS
ACTUAL VALUE COMPARATOR Rg ≤ Pickup SH STATOR GND STG1 OP
Tracking Frequency 15 Hz < f < 25 Hz 0
SH STATOR GND STG1 PKP
SH STATOR GND STG1 DPO
SETTINGS CALCULATE SETTING SETTING
Function Stage 2 Pickup Stage 2 Pickup Delay
= <Rs> RUN TPKP FLEXLOGIC OPERANDS
Function
Rg ≤ Pickup SH STATOR GND STG2 OP
= <Rp> 0
Calculate SH STATOR GND STG2 PKP
resistance SH STATOR GND STG2 DPO
ACTUAL VALUES
SETTING SETTING
Vaux (SH)
Ground OC Pickup Ground OC Delay
Ignd (SH)
RUN TPKP FLEXLOGIC OPERANDS
Ignd ≥ Pickup SH STATOR GND OC OP
0
SH STATOR GND OC PKP
SH STATOR GND OC DPO
SETTING
Current Supervision
RUN
Ignd ≤ Pickup
TIMER
10 sec. FLEXLOGIC OPERANDS
SETTING OR SH STATOR GND TRB OP
0
Voltage Supervision SH STATOR GND TRB PKP
RUN SH STATOR GND TRB DPO
Vx ≤ Pickup

ACTUAL VALUES
Stator Ground Resistance
SH Injection Amps
SH Injection Volts
830009A1.CDR

Figure 5–118: SUB-HARMONIC STATOR GROUND FAULT LOGIC

GE Multilin G60 Generator Protection System 5-209


5.6 GROUPED ELEMENTS 5 SETTINGS

e) APPLICATION CONSIDERATIONS FOR SUB-HARMONIC STATOR GROUND FAULT DETECTOR


The following special application considerations must be followed when employing sub-harmonic injection based 100% sta-
tor ground protection.
1. A generator with wye-grounded primary VT will provide a path for the injected 20 Hz signal to flow through the ground.
Thus the voltage measured using this VT will have both the fundamental and 20 Hz components superimposed at all
times.
2. Special algorithms address impact of this 20 Hz component on the aux over voltage element, which is normally used
for 95% ground fault protection by measuring NGT secondary voltage.
3. There are applications where a wye-grounded primary VT is normally used on the bus side of a generator breaker and
a neutral over voltage is used to detect ground faults on the bus duct or cable, etc. In such applications, after careful
analysis on the sensitivity of setting levels, this function may be blocked (if required) when the generator is online,
since the sub-harmonic injection based protection covers this zone. In such applications, it is recommended that this
function be blocked when the generator is online since the sub-harmonic injection based protection covers this zone.
4. The third harmonic based stator ground fault protection elements should not be used while using the sub-harmonic
injection based stator ground protection.
5. It is recommended that phase-phase voltages be used in G60 for the synchrocheck function rather than phase-to-
ground voltages under applications where a single voltage is being connected to one of the auxiliary VT channels of
G60 device.
6. The current from the CT in the secondary of the NGT fed to the sensitive ground input of G60 shall only be used for
sub-harmonic based stator ground protection and not for any other protection element such as ground over current or
neutral directional overcurrent.

5.6.17 FIELD GROUND FAULT PROTECTION


5
a) MAIN MENU
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ FIELD GROUND PROTECTION

„ FIELD GROUND „ FIELD


See page 5–212.
„ PROTECTION „ GROUND
„ FIELD
MESSAGE See page 5–214.
„ CURRENT

A block diagram of the field ground detection scheme using the G60 and the GPM-F is shown below. The field winding of a
synchronous generator is represented electrically by the impedance ZF = ZF1 + ZF2. Under normal conditions the field cir-
cuit is ungrounded. The capacitance CF is the stray capacitance of the field, distributed along the field winding. This capac-
itance represents the only path for current to flow to ground under normal conditions.

dcmA

IFLD
UR -series
G60 device Hall-effect CT

RS485 CF
communications Field IG
ground RG ZF1 VFLD Exciter
module
ZF2

830751A3.CDR

Figure 5–119: FIELD GROUND FAULT DETECTION


The resistance RG represents a breakdown of the field winding insulation providing a resistive path to ground through the
field grounding brush. The insulation failure can occur anywhere, so the impedances ZF1 and ZF2 are unknown. The fault
impedance RG is also unknown. The purpose of the field ground detector is to measure this resistance.

5-210 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

Measurement of RG is accomplished by injecting a voltage, VINJ and measuring the resulting current, IG. The measurement
algorithm must be capable of discriminating between capacitive current due to CF (which can be significant) and resistive
current due to a fault. The exciter voltage, VFLD is a DC value with a small ripple such that the impedance of the field is
essentially resistive. The current IFLD is a DC current with a range of tens, hundreds, or thousands of amps.
IEXC RC IEXC

ZF1 ZF1

RG RG
LOC VEXC LOC VEXC

ZF2 ZF2

RCL RC

IG1, IG2 IG1, IG2

VINJ1, VINJ2 VINJ1, VINJ2

Single-point injection Double-point injection


830752A2.CDR

Figure 5–120: EQUIVALENT CIRCUIT, SINGLE-POINT AND DOUBLE-POINT INJECTION


Referring to the single-point injection circuit, the magnitude of IFLD makes it evident that VINJ cannot have a significant
impact on the voltage drop across ZF2. Therefore if two values (VINJ1 and VINJ2) are injected the following equations can be
written:
5
V INJ1 = I G1 R G + I G1 R CL V F2
(EQ 5.43)
V INJ2 = I G2 R G + I G2 R CL V F2

Where IG1 is the current flowing due to VINJ1 and IG2 is the current flowing due to VINJ2. Solving for RG we get:
( V INJ1 – V INJ2 ) – ( I G1 – I G2 ) × R CL
R G = -----------------------------------------------------------------------------------------
- (EQ 5.44)
I G1 – I G2

For the double-point injection circuit, RCL is defined as:


RC
R CL = ------- (EQ 5.45)
2
The VINJ voltage is therefore composed of a square wave to create two levels of injection. Once the value of RG is known it
can be substituted into the VINJ equation above to determine VF2. If the VFLD voltage (refer to the single-point injection cir-
cuit) is known through measurement then the location of the fault is simply VF2 / VFLD. This gives the location of the fault as
percentage of field winding from negative terminal in case of single point injection. If double point injection is used, fault
location cannot be determined. The relay displays an invalid fault location for approximately 10% for such conditions. The
fault location cannot be determined if the field voltage is zero (that is, when the generator is not running). The fault location
is displayed only when the measured field ground resistance is less than 500 KΩ. Refer to Field Ground Module Instruction
Manual for details of wiring and installation.
GROUND UNDERCURRENT:
A brush lift-off condition will prevent the field ground detector from operating. This is detected by calculating the RMS value
of the ground current. It will normally have a nonzero value due to the capacitance of the field winding. A drop in this signal
indicates an open circuit in the injection path and the field ground under current feature detects this condition.

GE Multilin G60 Generator Protection System 5-211


5.6 GROUPED ELEMENTS 5 SETTINGS

FIELD CURRENT MONITORING:


The G60 can monitor the field current via a Hall effect transducer that produces a 4 to 20 mA output. This device must be
wired to a dcmA input of the G60 or a Brick in HardFiber system. Note that the relay must be configured with a transducer
input card for the former case. Assignment of this signal to the field ground function allows the user to detect a field over-
current or undercurrent condition. The maximum and minimum settings configured for scaling of this dcmA input shall be
used to get the per-unit values of field current.

b) FIELD GROUND
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö FIELD GROUND PROTECTION ÖØ FIELD GROUND

„ FIELD FIELD GROUND Range: Disabled, Enabled


„ GROUND FUNCTION: Disabled
FIELD GROUND INJECTION Range: 0.1 to 3.0 Hz in steps of 0.1
MESSAGE
FREQUENCY: 1.0 Hz
INJ CONNECTION TYPE: Range: Single Point, Double Point
MESSAGE
Single Point
FIELD GROUND STG1 Range: 1 to 500 kΩ in steps of 1
MESSAGE
PICKUP: 20 kΩ
FIELD GROUND STG1 Range: 0.1 to 600.0 s in steps of 0.1
MESSAGE
DELAY: 10.0 s
FIELD GROUND STG2 Range: 1 to 500 kΩ in steps of 1
MESSAGE
PICKUP: 5 kΩ
5 MESSAGE
FIELD GROUND STG2 Range: 0.1 to 600.0 s in steps of 0.1
DELAY: 3.0 s
FIELD GROUND UC Range: 0.05 to 100.00 mA in steps of 0.1
MESSAGE
PICKUP: 1.00 mA
FIELD GROUND UC Range: 0.10 to 600.00 s in steps of 0.1
MESSAGE
DELAY: 1.0 s
FIELD GROUND BLK: Range: FlexLogic™ operand
MESSAGE
Off
FIELD GROUND Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
FIELD GROUND Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The following settings are available for the field ground fault detector function.
• FIELD GROUND INJECTION FREQUENCY: This setting specifies the frequency of the signal to be injected into the
field winding for detecting ground faults. The injection frequency selection will depend on the value of field winding
capacitance to ground. The following simple formula can be used to set the injection frequency when the field winding
capacitance is known in μF.

F inj = 2.5
-------- (EQ 5.46)
CF

5-212 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

Where CF is in microfarads. Some example injection frequency settings are given in the table below for various field
winding capacitance values. For field winding capacitances greater than 10 μF, resistance measurements will be less
accurate.
Table 5–25: EXAMPLE INJECTION FREQUENCY SETTINGS
CF FINJ
1 μF 2.50 Hz
2 μF 1.50 Hz
3 μF 0.83 Hz
4 μF 0.63 Hz
5 μF 0.50 Hz
6 μF 0.42 Hz
7 μF 0.36 Hz
8 μF 0.31 Hz
9 μF 0.28 Hz
10 μF 0.25 Hz

• INJ CONNECTION TYPE: Field ground protection can be implemented by injecting a low frequency signal either into
both positive and negative terminals of the field winding or only into the negative terminal of the field winding. Refer to
the instruction manual of the field ground module for wiring difference between single point and double point injections.
For single point injection, the G60 provides the feature of fault location. In case of a field ground fault, the G60 displays
the location of the fault in the field winding as a percentage of the winding from the negative terminal. If the preference
is to keep the injection symmetrical into the field winding, then double point injection has to be done but the fault loca-
tion feature is not available. This setting has to match the type of connection on the field ground module.
• FIELD GROUND STG1 PICKUP: If the measured ground resistance is less than the value specified by this setting, 5
then the stage 1 element will pickup. Normally stage 1 is used to raise alarms and typical settings may fall in the range
of 10 to 40 kΩ.
• FIELD GROUND STG1 DELAY: This setting specifies a time delay for stage 1. Typical settings are in the range of 10
to 15 seconds. This delay will have to be added to the operating time of the element to obtain the overall delay.
• FIELD GROUND STG2 PICKUP: If the measured ground resistance is less than the value specified by this setting,
then the stage 2 element will pickup. Normally stage 2 is used to raise trip signals and typical settings may fall in the
range of 2 to 5 kΩ.
• FIELD GROUND STG2 DELAY: This setting specifies a time delay for stage 2. Typical settings are in the range of 3 to
5 seconds. This delay will have to be added to the operating time of the element to obtain the overall delay.
• FIELD GROUND UC PICKUP: This setting specifies the ground undercurrent level below which a brush open condi-
tion shall be detected. A brush lift-off condition will prevent the field ground detector from operating. This is detected by
calculating the RMS value of the ground current. It will normally have a non-zero value due to the capacitance of the
field winding. A drop in this signal indicates an open circuit in the injection path. To set this value, the ground current in
a healthy operating condition preferably with zero field voltage should be recorded from G60 actual values display
(performed during commissioning). Configure this setting to be 60 to 70% of that normal value.
• FIELD GROUND UC DELAY: This setting specifies a time delay for field ground undercurrent element. Typical settings
are in the range of 20 to 30 seconds. This delay will have to be added to the operating time of the element to obtain the
overall delay.
• FIELD GROUND FUNCTION BLK: This setting selects a FlexLogic™ operand to block the field ground function.

GE Multilin G60 Generator Protection System 5-213


5.6 GROUPED ELEMENTS 5 SETTINGS

The field ground fault detector function logic is shown below.

COMMAND TO GPM-F
SETTINGS Block 0.1 to 3.0 Hz Injection
Function
= Enabled
Block SETTING SETTING
= Off Stage 1 Pickup Stage 1 Pickup Delay
AND RUN TPKP FLEXLOGIC OPERANDS
Rg ≤ Pickup EIELD GND STG1 OP
0
EIELD GND STG1 PKP
EIELD GND STG1 DPO

SETTING SETTING
Stage 2 Pickup Stage 2 Pickup Delay
RUN TPKP FLEXLOGIC OPERANDS
Rg ≤ Pickup EIELD GND STG2 OP
0
EIELD GND STG2 PKP
EIELD GND STG2 DPO

SETTING SETTING
Ground UC Pickup Ground UC Delay
RUN TPKP FLEXLOGIC OPERANDS
Ig_RMS ≤ Pickup FIELD GND INJ UC OP
0
FIELD GND INJ UC PKP
FIELD GND INJ UC DPO

ACTUAL VALUES
Field Ground Resistance
Field Ground Current
Injected Voltage
From Fault Location
injection Field Voltage
unit
TIMER
5 sec. SELF-TEST MESSAGE
GPM-F failure GPM-F FAILURE
5 sec.

5
830010A2.CDR

Figure 5–121: FIELD GROUND FAULT DETECTOR FUNCTION LOGIC

c) FIELD CURRENT
PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö FIELD GROUND PROTECTION ÖØ FIELD CURRENT

„ FIELD FIELD CURRENT Range: Disabled, Enabled


„ CURRENT FUNCTION: Disabled
FIELD CURRENT ORIGIN: Range: Off, dcmA 1, dcmA 2,..., dcmA 24, TRD1,
MESSAGE TRD2,..., TRD8
Off
FIELD OVER CURRENT Range: 0.05 to 1.00 pu in steps of 0.01
MESSAGE
PICKUP: 0.80 pu
FIELD OVER CURRENT Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 1.00 s
FIELD UNDER CURRENT Range: 0.05 to 1.00 pu in steps of 0.01
MESSAGE
PICKUP: 0.20 pu
FIELD UNDER CURRENT Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 1.00 s
FIELD CURRENT BLK: Range: FlexLogic™ operand
MESSAGE
Off
FIELD CURRENT Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
FIELD CURRENT Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The following settings are available for the field current fault detector function.
• FIELD CURRENT ORIGIN: This setting selects the dcmA input to be used for the field current protection element. A
dcmA input can be selected from up to 24 possible inputs, depending on the number of installed transducer modules.

5-214 G60 Generator Protection System GE Multilin


5 SETTINGS 5.6 GROUPED ELEMENTS

In a HardFiber G60 device, this setting can point to one of the TRD inputs mapped to a Brick dcmA input. In both
cases, the minimum and maximum scaling settings of that transducer input are used to perform the per-unit conver-
sion. The unit setting shall be configured as “Amps” if the transducer input is used.
These minimum and maximum settings are set as per the Hall sensor current rating. The per-unit computation is
scaled to a base equal to the maximum value setting, with a zero per-unit value corresponding to zero in the unit sys-
tem used by the maximum value setting. For example, in the case where the maximum value setting is 100 A, a trip
level of 75 A is achieved by setting the operate level at 0.75 pu, regardless of the range (for example, 4 to 20 mA, 0 to
20 mA etc.) and regardless of the minimum value setting.
• FIELD OVER CURRENT PICKUP: This setting specifies the field current level above which the overcurrent element
picks up.
• FIELD OVER CURRENT DELAY: This setting specifies a time delay for the overcurrent element. This delay is added
to the operating time of the element to obtain the overall delay.
• FIELD UNDER CURRENT PICKUP: This setting specifies the field current level above which the undercurrent ele-
ment picks up.
• FIELD UNDER CURRENT DELAY: This setting specifies a time delay for undercurrent element. This delay is added to
the operating time of the element to obtain the overall delay.
• FIELD CURRENT BLK: This setting allows the user to select a FlexLogic™ operand to block the field ground function.
The field current fault detector function logic is shown below.
SETTINGS
Function SETTING SETTING
= Enabled Field OC Pickup Field OC Delay
Block AND RUN TPKP FLEXLOGIC OPERANDS
= Off IFLD ≥ Pickup FIELD OC OP
0
FIELD OC PKP
FIELD OC DPO 5
SETTING SETTING
Field UC Pickup Field UC Delay
RUN TPKP FLEXLOGIC OPERANDS
IFLD ≤ Pickup FIELD UC OP
0
FIELD UC PKP
FIELD UC DPO

SETTINGS
Field Current Origin ACTUAL VALUE
= <Value> Field Current
830011A1.CDR

Figure 5–122: FIELD CURRENT FAULT DETECTOR FUNCTION LOGIC

GE Multilin G60 Generator Protection System 5-215


5.7 CONTROL ELEMENTS 5 SETTINGS

5.7CONTROL ELEMENTS 5.7.1 OVERVIEW

Control elements are generally used for control rather than protection. See the Introduction to Elements section at the
beginning of this chapter for further information.

5.7.2 TRIP BUS

PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ TRIP BUS ÖØ TRIP BUS 1(6)

„ TRIP BUS 1 TRIP BUS 1 Range: Enabled, Disabled


„ FUNCTION: Disabled
TRIP BUS 1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
TRIP BUS 1 PICKUP Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.00 s
TRIP BUS 1 RESET Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
DELAY: 0.00 s
TRIP BUS 1 INPUT 1: Range: FlexLogic™ operand
MESSAGE
Off
TRIP BUS 1 INPUT 2: Range: FlexLogic™ operand
MESSAGE
Off

5 TRIP BUS 1 INPUT 16: Range: FlexLogic™ operand
MESSAGE
Off
TRIP BUS 1 Range: Enabled, Disabled
MESSAGE
LATCHING: Disabled
TRIP BUS 1 RESET: Range: FlexLogic™ operand
MESSAGE
Off
TRIP BUS 1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
TRIP BUS 1 Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled

The trip bus element allows aggregating outputs of protection and control elements without using FlexLogic™ and assign-
ing them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip condition-
ing such as latch, delay, and seal-in delay are available.
The easiest way to assign element outputs to a trip bus is through the EnerVista UR Setup software A protection summary
is displayed by navigating to a specific protection or control protection element and checking the desired bus box. Once the
desired element is selected for a specific bus, a list of element operate-type operands are displayed and can be assigned
to a trip bus. If more than one operate-type operand is required, it may be assigned directly from the trip bus menu.

5-216 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

Figure 5–123: TRIP BUS FIELDS IN THE PROTECTION SUMMARY


The following settings are available.
• TRIP BUS 1 BLOCK: The trip bus output is blocked when the operand assigned to this setting is asserted.
• TRIP BUS 1 PICKUP DELAY: This setting specifies a time delay to produce an output depending on how output is
used.
• TRIP BUS 1 RESET DELAY: This setting specifies a time delay to reset an output command. The time delay should be 5
set long enough to allow the breaker or contactor to perform a required action.
• TRIP BUS 1 INPUT 1 to TRIP BUS 1 INPUT 16: These settings select a FlexLogic™ operand to be assigned as an
input to the trip bus.
• TRIP BUS 1 LATCHING: This setting enables or disables latching of the trip bus output. This is typically used when
lockout is required or user acknowledgement of the relay response is required.
• TRIP BUS 1 RESET: The trip bus output is reset when the operand assigned to this setting is asserted. Note that the
RESET OP operand is pre-wired to the reset gate of the latch, As such, a reset command the front panel interface or via
communications will reset the trip bus output.

SETTINGS
TRIP BUS 1 INPUT 1
SETTINGS
= Off
TRIP BUS 1 PICKUP
TRIP BUS 1 INPUT 2
DELAY
= Off Non-volatile,
TRIP BUS 1 RESET
OR set-dominant
***

DELAY
AND S TPKP FLEXLOGIC OPERAND
TRIP BUS 1 INPUT 16 TRIP BUS 1 OP
Latch
= Off TRST
R

SETTINGS
TRIP BUS 1 FLEXLOGIC OPERAND
FUNCTION
TRIP BUS 1 PKP
= Enabled
TRIP BUS 1 BLOCK AND
= Off

SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
OR

FLEXLOGIC OPERAND
RESET OP 842023A1.CDR

Figure 5–124: TRIP BUS LOGIC

GE Multilin G60 Generator Protection System 5-217


5.7 CONTROL ELEMENTS 5 SETTINGS

5.7.3 SETTING GROUPS

PATH: SETTINGS ÖØ CONTROL ELEMENTS Ö SETTINGS GROUPS

„ SETTING GROUPS SETTING GROUPS Range: Disabled, Enabled


„ FUNCTION: Disabled
SETTING GROUPS BLK: Range: FlexLogic™ operand
MESSAGE
Off
GROUP 2 ACTIVATE ON: Range: FlexLogic™ operand
MESSAGE
Off
GROUP 3 ACTIVATE ON: Range: FlexLogic™ operand
MESSAGE
Off

GROUP 6 ACTIVATE ON: Range: FlexLogic™ operand
MESSAGE
Off
GROUP 1 NAME: Range: up to 16 alphanumeric characters
MESSAGE

GROUP 2 NAME: Range: up to 16 alphanumeric characters


MESSAGE

5 MESSAGE
GROUP 6 NAME: Range: up to 16 alphanumeric characters

SETTING GROUP Range: Disabled, Enabled


MESSAGE
EVENTS: Disabled

The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the GROUPED
ELEMENTS settings menu. The faceplate Settings In Use LEDs indicate which active group (with a non-flashing energized
LED) is in service.
The SETTING GROUPS BLK setting prevents the active setting group from changing when the FlexLogic™ parameter is set to
"On". This can be useful in applications where it is undesirable to change the settings under certain conditions, such as the
breaker being open.
The GROUP 2 ACTIVATE ON to GROUP 6 ACTIVATE ON settings select a FlexLogic™ operand which, when set, will make the
particular setting group active for use by any grouped element. A priority scheme ensures that only one group is active at a
given time – the highest-numbered group which is activated by its ACTIVATE ON parameter takes priority over the lower-
numbered groups. There is no activate on setting for group 1 (the default active group), because group 1 automatically
becomes active if no other group is active.
The SETTING GROUP 1 NAME to SETTING GROUP 6 NAME settings allows to user to assign a name to each of the six settings
groups. Once programmed, this name will appear on the second line of the GROUPED ELEMENTS Ö SETTING GROUP 1(6)
menu display.
The relay can be set up via a FlexLogic™ equation to receive requests to activate or de-activate a particular non-default
settings group. The following FlexLogic™ equation (see the figure below) illustrates requests via remote communications
(for example, VIRTUAL INPUT 1 ON) or from a local contact input (for example, CONTACT IP 1 ON) to initiate the use of a par-
ticular settings group, and requests from several overcurrent pickup measuring elements to inhibit the use of the particular
settings group. The assigned VIRTUAL OUTPUT 1 operand is used to control the “On” state of a particular settings group.

5-218 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

1 VIRT IP 1 ON (VI1)
OR (2)
2 CONT IP 1 ON (H5A)

3 OR (2)
AND (3) = VIRT OP 1 (VO1)
4 PHASE TOC1 PKP

5 NOT

6 PHASE TOC2 PKP

7 NOT

8 AND (3)

9 = VIRT OP 1 (VO1)

10 END
842789A1.CDR

Figure 5–125: EXAMPLE FLEXLOGIC™ CONTROL OF A SETTINGS GROUP

5.7.4 SELECTOR SWITCH

PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ SELECTOR SWITCH Ö SELECTOR SWITCH 1(2)

„ SELECTOR SWITCH 1 SELECTOR 1 FUNCTION: Range: Disabled, Enabled


„ Disabled
SELECTOR 1 FULL Range: 1 to 7 in steps of 1
MESSAGE
RANGE: 7 5
SELECTOR 1 TIME-OUT: Range: 3.0 to 60.0 s in steps of 0.1
MESSAGE
5.0 s
SELECTOR 1 STEP-UP: Range: FlexLogic™ operand
MESSAGE
Off
SELECTOR 1 STEP-UP Range: Time-out, Acknowledge
MESSAGE
MODE: Time-out
SELECTOR 1 ACK: Range: FlexLogic™ operand
MESSAGE
Off
SELECTOR 1 3BIT A0: Range: FlexLogic™ operand
MESSAGE
Off
SELECTOR 1 3BIT A1: Range: FlexLogic™ operand
MESSAGE
Off
SELECTOR 1 3BIT A2: Range: FlexLogic™ operand
MESSAGE
Off
SELECTOR 1 3BIT Range: Time-out, Acknowledge
MESSAGE
MODE: Time-out
SELECTOR 1 3BIT ACK: Range: FlexLogic™ operand
MESSAGE
Off
SELECTOR 1 POWER-UP Range: Restore, Synchronize, Sync/Restore
MESSAGE
MODE: Restore
SELECTOR 1 TARGETS: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
SELECTOR 1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

GE Multilin G60 Generator Protection System 5-219


5.7 CONTROL ELEMENTS 5 SETTINGS

The selector switch element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic.
The element provides for two control inputs. The step-up control allows stepping through selector position one step at a
time with each pulse of the control input, such as a user-programmable pushbutton. The three-bit control input allows set-
ting the selector to the position defined by a three-bit word.
The element allows pre-selecting a new position without applying it. The pre-selected position gets applied either after time-
out or upon acknowledgement via separate inputs (user setting). The selector position is stored in non-volatile memory.
Upon power-up, either the previous position is restored or the relay synchronizes to the current three-bit word (user set-
ting). Basic alarm functionality alerts the user under abnormal conditions; for example, the three-bit control input being out
of range.
• SELECTOR 1 FULL RANGE: This setting defines the upper position of the selector. When stepping up through avail-
able positions of the selector, the upper position wraps up to the lower position (position 1). When using a direct three-
bit control word for programming the selector to a desired position, the change would take place only if the control word
is within the range of 1 to the SELECTOR FULL RANGE. If the control word is outside the range, an alarm is established
by setting the SELECTOR ALARM FlexLogic™ operand for 3 seconds.
• SELECTOR 1 TIME-OUT: This setting defines the time-out period for the selector. This value is used by the relay in
the following two ways. When the SELECTOR STEP-UP MODE is “Time-out”, the setting specifies the required period of
inactivity of the control input after which the pre-selected position is automatically applied. When the SELECTOR STEP-
UP MODE is “Acknowledge”, the setting specifies the period of time for the acknowledging input to appear. The timer is
re-started by any activity of the control input. The acknowledging input must come before the SELECTOR 1 TIME-OUT
timer expires; otherwise, the change will not take place and an alarm will be set.
• SELECTOR 1 STEP-UP: This setting specifies a control input for the selector switch. The switch is shifted to a new
position at each rising edge of this signal. The position changes incrementally, wrapping up from the last (SELECTOR 1

5 FULL RANGE) to the first (position 1). Consecutive pulses of this control operand must not occur faster than every
50 ms. After each rising edge of the assigned operand, the time-out timer is restarted and the SELECTOR SWITCH 1:
POS Z CHNG INITIATED target message is displayed, where Z the pre-selected position. The message is displayed for
the time specified by the FLASH MESSAGE TIME setting. The pre-selected position is applied after the selector times out
(“Time-out” mode), or when the acknowledging signal appears before the element times out (“Acknowledge” mode).
When the new position is applied, the relay displays the SELECTOR SWITCH 1: POSITION Z IN USE message. Typically,
a user-programmable pushbutton is configured as the stepping up control input.
• SELECTOR 1 STEP-UP MODE: This setting defines the selector mode of operation. When set to “Time-out”, the
selector will change its position after a pre-defined period of inactivity at the control input. The change is automatic and
does not require any explicit confirmation of the intent to change the selector's position. When set to “Acknowledge”,
the selector will change its position only after the intent is confirmed through a separate acknowledging signal. If the
acknowledging signal does not appear within a pre-defined period of time, the selector does not accept the change
and an alarm is established by setting the SELECTOR STP ALARM output FlexLogic™ operand for 3 seconds.
• SELECTOR 1 ACK: This setting specifies an acknowledging input for the stepping up control input. The pre-selected
position is applied on the rising edge of the assigned operand. This setting is active only under “Acknowledge” mode of
operation. The acknowledging signal must appear within the time defined by the SELECTOR 1 TIME-OUT setting after the
last activity of the control input. A user-programmable pushbutton is typically configured as the acknowledging input.
• SELECTOR 1 3BIT A0, A1, and A2: These settings specify a three-bit control input of the selector. The three-bit con-
trol word pre-selects the position using the following encoding convention:

A2 A1 A0 POSITION
0 0 0 rest
0 0 1 1
0 1 0 2
0 1 1 3
1 0 0 4
1 0 1 5
1 1 0 6
1 1 1 7

5-220 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

The “rest” position (0, 0, 0) does not generate an action and is intended for situations when the device generating the
three-bit control word is having a problem. When SELECTOR 1 3BIT MODE is “Time-out”, the pre-selected position is
applied in SELECTOR 1 TIME-OUT seconds after the last activity of the three-bit input. When SELECTOR 1 3BIT MODE is
“Acknowledge”, the pre-selected position is applied on the rising edge of the SELECTOR 1 3BIT ACK acknowledging
input.
The stepping up control input (SELECTOR 1 STEP-UP) and the three-bit control inputs (SELECTOR 1 3BIT A0 through A2)
lock-out mutually: once the stepping up sequence is initiated, the three-bit control input is inactive; once the three-bit
control sequence is initiated, the stepping up input is inactive.
• SELECTOR 1 3BIT MODE: This setting defines the selector mode of operation. When set to “Time-out”, the selector
changes its position after a pre-defined period of inactivity at the control input. The change is automatic and does not
require explicit confirmation to change the selector position. When set to “Acknowledge”, the selector changes its posi-
tion only after confirmation via a separate acknowledging signal. If the acknowledging signal does not appear within a
pre-defined period of time, the selector rejects the change and an alarm established by invoking the SELECTOR BIT
ALARM FlexLogic™ operand for 3 seconds.

• SELECTOR 1 3BIT ACK: This setting specifies an acknowledging input for the three-bit control input. The pre-
selected position is applied on the rising edge of the assigned FlexLogic™ operand. This setting is active only under
the “Acknowledge” mode of operation. The acknowledging signal must appear within the time defined by the SELEC-
TOR TIME-OUT setting after the last activity of the three-bit control inputs. Note that the stepping up control input and
three-bit control input have independent acknowledging signals (SELECTOR 1 ACK and SELECTOR 1 3BIT ACK, accord-
ingly).
• SELECTOR 1 POWER-UP MODE: This setting specifies the element behavior on power up of the relay.
When set to “Restore”, the last position of the selector (stored in the non-volatile memory) is restored after powering up
the relay. If the position restored from memory is out of range, position 0 (no output operand selected) is applied and
an alarm is set (SELECTOR 1 PWR ALARM).
5
When set to “Synchronize” selector switch acts as follows. For two power cycles, the selector applies position 0 to the
switch and activates SELECTOR 1 PWR ALARM. After two power cycles expire, the selector synchronizes to the position
dictated by the three-bit control input. This operation does not wait for time-out or the acknowledging input. When the
synchronization attempt is unsuccessful (that is, the three-bit input is not available (0,0,0) or out of range) then the
selector switch output is set to position 0 (no output operand selected) and an alarm is established (SELECTOR 1 PWR
ALARM).

The operation of “Synch/Restore” mode is similar to the “Synchronize” mode. The only difference is that after an
unsuccessful synchronization attempt, the switch will attempt to restore the position stored in the relay memory. The
“Synch/Restore” mode is useful for applications where the selector switch is employed to change the setting group in
redundant (two relay) protection schemes.
• SELECTOR 1 EVENTS: If enabled, the following events are logged:

EVENT NAME DESCRIPTION


SELECTOR 1 POS Z Selector 1 changed its position to Z.
SELECTOR 1 STP ALARM The selector position pre-selected via the stepping up control input has not been
confirmed before the time out.
SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed
before the time out.

GE Multilin G60 Generator Protection System 5-221


5.7 CONTROL ELEMENTS 5 SETTINGS

The following figures illustrate the operation of the selector switch. In these diagrams, “T” represents a time-out setting.

pre-existing changed to 4 with changed to 1 with changed to 2 with a changed to 7 with


position 2 a pushbutton a 3-bit input pushbutton a 3-bit input

STEP-UP

T T

3BIT A0

3BIT A1

3BIT A2
T T

POS 1

POS 2

POS 3

POS 4

POS 5

5 POS 6

POS 7

BIT 0

BIT 1

BIT 2

STP ALARM

BIT ALARM

ALARM
842737A1.CDR

Figure 5–126: TIME-OUT MODE

5-222 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

pre-existing changed to 4 with changed to 1 with changed to 2 with


position 2 a pushbutton a 3-bit input a pushbutton

STEP-UP

ACK

3BIT A0

3BIT A1

3BIT A2

3BIT ACK

POS 1

POS 2

POS 3

POS 4

POS 5

POS 6

POS 7
5
BIT 0

BIT 1

BIT 2

STP ALARM

BIT ALARM

ALARM

842736A1.CDR

Figure 5–127: ACKNOWLEDGE MODE


APPLICATION EXAMPLE
Consider an application where the selector switch is used to control setting groups 1 through 4 in the relay. The setting
groups are to be controlled from both user-programmable pushbutton 1 and from an external device via contact inputs 1
through 3. The active setting group shall be available as an encoded three-bit word to the external device and SCADA via
output contacts 1 through 3. The pre-selected setting group shall be applied automatically after 5 seconds of inactivity of
the control inputs. When the relay powers up, it should synchronize the setting group to the three-bit control input.
Make the following changes to setting group control in the SETTINGS ÖØ CONTROL ELEMENTS Ö SETTING GROUPS menu:
SETTING GROUPS FUNCTION: “Enabled” GROUP 4 ACTIVATE ON: “SELECTOR 1 POS 4"
SETTING GROUPS BLK: “Off” GROUP 5 ACTIVATE ON: “Off”
GROUP 2 ACTIVATE ON: “SELECTOR 1 POS 2" GROUP 6 ACTIVATE ON: “Off”
GROUP 3 ACTIVATE ON: “SELECTOR 1 POS 3"
Make the following changes to selector switch element in the SETTINGS ÖØ CONTROL ELEMENTS ÖØ SELECTOR SWITCH Ö
SELECTOR SWITCH 1 menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3:

GE Multilin G60 Generator Protection System 5-223


5.7 CONTROL ELEMENTS 5 SETTINGS

SELECTOR 1 FUNCTION: “Enabled” SELECTOR 1 3BIT A0: “CONT IP 1 ON”


SELECTOR 1 FULL-RANGE: “4” SELECTOR 1 3BIT A1: “CONT IP 2 ON”
SELECTOR 1 STEP-UP MODE: “Time-out” SELECTOR 1 3BIT A2: “CONT IP 3 ON”
SELECTOR 1 TIME-OUT: “5.0 s” SELECTOR 1 3BIT MODE: “Time-out”
SELECTOR 1 STEP-UP: “PUSHBUTTON 1 ON” SELECTOR 1 3BIT ACK: “Off”
SELECTOR 1 ACK: “Off” SELECTOR 1 POWER-UP MODE: “Synchronize”

Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the following
changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUTS menu:
OUTPUT H1 OPERATE: “SELECTOR 1 BIT 0"
OUTPUT H2 OPERATE: “SELECTOR 1 BIT 1"
OUTPUT H3 OPERATE: “SELECTOR 1 BIT 2"
Finally, assign configure user-programmable pushbutton 1 by making the following changes in the SETTINGS Ö PRODUCT
SETUP ÖØ USER-PROGRAMMABLE PUSHBUTTONS Ö USER PUSHBUTTON 1 menu:

PUSHBUTTON 1 FUNCTION: “Self-reset”


PUSHBUTTON 1 DROP-OUT TIME: “0.10 s”

The logic for the selector switch is shown below:

SETTINGS
SELECTOR 1 FULL RANGE:

SELECTOR 1 STEP-UP MODE:

SELECTOR 1 3BIT MODE:

SELECTOR 1 TIME-OUT: ACTUAL VALUE


SETTINGS
SELECTOR 1 POSITION

5 SELECTOR 1 FUNCTION:
Enabled = 1
SELECTOR 1 POWER-UP MODE:
RUN
SELECTOR 1 STEP-UP: FLEXLOGIC™ OPERANDS
Off = 0 step up SELECTOR 1 POS 1
2
SELECTOR 1 ACK: 1 SELECTOR 1 POS 2
3
Off = 0 acknowledge SELECTOR 1 POS 3
SELECTOR 1 3BIT A0: 4
SELECTOR 1 POS 4
three-bit control input

Off = 0 SELECTOR 1 POS 5


ON
SELECTOR 1 3BIT A1: 7 5
SELECTOR 1 POS 6
Off = 0 6
SELECTOR 1 POS 7
SELECTOR 1 3BIT A2:
Off = 0 FLEXLOGIC™ OPERANDS
SELECTOR 1 3BIT ACK:
SELECTOR 1 STP ALARM
Off = 0 3-bit acknowledge
SELECTOR 1 BIT ALARM
3-bit position out
OR

SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
842012A2.CDR

Figure 5–128: SELECTOR SWITCH LOGIC

5-224 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

5.7.5 UNDERFREQUENCY

PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ UNDERFREQUENCY Ö UNDERFREQUENCY 1(6)

„ UNDERFREQUENCY 1 UNDFREQ 1 FUNCTION: Range: Disabled, Enabled


„ Disabled
UNDERFREQ 1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
UNDERFREQ 1 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SRC 1
UNDERFREQ 1 MIN Range: 0.10 to 1.25 pu in steps of 0.01
MESSAGE
VOLT/AMP: 0.10 pu
UNDERFREQ 1 PICKUP: Range: 20.00 to 65.00 Hz in steps of 0.01
MESSAGE
59.50 Hz
UNDERFREQ 1 PICKUP Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 2.000 s
UNDERFREQ 1 RESET Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY : 2.000 s
UNDERFREQ 1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
UNDERFREQ 1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled 5
There are six identical underfrequency elements, numbered from 1 through 6.
The steady-state frequency of a power system is a certain indicator of the existing balance between the generated power
and the load. Whenever this balance is disrupted through the loss of an important generating unit or the isolation of part of
the system from the rest of the system, the effect will be a reduction in frequency. If the control systems of the system gen-
erators do not respond fast enough, the system may collapse. A reliable method to quickly restore the balance between
load and generation is to automatically disconnect selected loads, based on the actual system frequency. This technique,
called “load-shedding”, maintains system integrity and minimize widespread outages. After the frequency returns to normal,
the load may be automatically or manually restored.
The UNDERFREQ 1 SOURCE setting is used to select the source for the signal to be measured. The element first checks for a
live phase voltage available from the selected source. If voltage is not available, the element attempts to use a phase cur-
rent. If neither voltage nor current is available, the element will not operate, as it will not measure a parameter below the
minimum voltage/current setting.
The UNDERFREQ 1 MIN VOLT/AMP setting selects the minimum per unit voltage or current level required to allow the underfre-
quency element to operate. This threshold is used to prevent an incorrect operation because there is no signal to measure.
This UNDERFREQ 1 PICKUP setting is used to select the level at which the underfrequency element is to pickup. For example,
if the system frequency is 60 Hz and the load shedding is required at 59.5 Hz, the setting will be 59.50 Hz.
SETTING

UNDERFREQ 1 FUNCTION:

Disabled = 0
Enabled = 1

SETTING SETTING SETTING


UNDERFREQ 1 UNDERFREQ 1
UNDERFREQ 1 BLOCK: PICKUP : PICKUP DELAY :
AND RUN FLEXLOGIC OPERANDS
Off = 0 UNDERFREQ 1
UNDERFREQ 1 PKP
RESET DELAY :
SETTING UNDERFREQ 1 DPO
SETTING tPKP
UNDERFREQ 1 0 < f ≤ PICKUP tRST UNDERFREQ 1 OP
UNDERFREQ 1 SOURCE: ACTUAL VALUES MIN VOLT / AMP:
Level ≥ Minimum
VOLT / AMP
Frequency 827079A8.CDR

Figure 5–129: UNDERFREQUENCY SCHEME LOGIC

GE Multilin G60 Generator Protection System 5-225


5.7 CONTROL ELEMENTS 5 SETTINGS

5.7.6 OVERFREQUENCY

PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ OVERFREQUENCY Ö OVERFREQUENCY 1(4)

„ OVERFREQUENCY 1 OVERFREQ 1 FUNCTION: Range: Disabled, Enabled


„ Disabled
OVERFREQ 1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
OVERFREQ 1 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SRC 1
OVERFREQ 1 PICKUP: Range: 20.00 to 65.00 Hz in steps of 0.01
MESSAGE
60.50 Hz
OVERFREQ 1 PICKUP Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.500 s
OVERFREQ 1 RESET Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
DELAY : 0.500 s
OVERFREQ 1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
OVERFREQ 1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

There are four overfrequency elements, numbered 1 through 4.


5 A frequency calculation for a given source is made on the input of a voltage or current channel, depending on which is
available. The channels are searched for the signal input in the following order: voltage channel A, auxiliary voltage chan-
nel, current channel A, ground current channel. The first available signal is used for frequency calculation.
The steady-state frequency of a power system is an indicator of the existing balance between the generated power and the
load. Whenever this balance is disrupted through the disconnection of significant load or the isolation of a part of the sys-
tem that has a surplus of generation, the effect will be an increase in frequency. If the control systems of the generators do
not respond fast enough, to quickly ramp the turbine speed back to normal, the overspeed can lead to the turbine trip. The
overfrequency element can be used to control the turbine frequency ramp down at a generating location. This element can
also be used for feeder reclosing as part of the "after load shedding restoration".
The OVERFREQ 1 SOURCE setting selects the source for the signal to be measured. The OVERFREQ 1 PICKUP setting selects
the level at which the overfrequency element is to pickup.
SETTING

OVERFREQ 1 FUNCTION:

Disabled = 0
SETTING
Enabled = 1
OVERFREQ 1 PICKUP : SETTING
SETTING OVERFREQ 1 PICKUP
AND RUN DELAY :
OVERFREQ 1 BLOCK: FLEXLOGIC OPERANDS
OVERFREQ 1 RESET
OVERFREQ 1 PKP
DELAY :
Off = 0 OVERFREQ 1 DPO
tPKP
tRST OVERFREQ 1 OP
SETTING f ≥ PICKUP
OVERFREQ 1 SOURCE:

Frequency 827832A5.CDR

Figure 5–130: OVERFREQUENCY SCHEME LOGIC

5-226 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

5.7.7 FREQUENCY RATE OF CHANGE

PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ FREQUENCY RATE OF CHANGE Ö FREQUENCY RATE OF CHANGE 1(4)

„ FREQUENCY RATE FREQ RATE 1 Range: Disabled, Enabled


„ OF CHANGE 1 FUNCTION: Disabled
FREQ RATE 1 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SRC 1
FREQ RATE 1 TREND: Range: Increasing, Decreasing, Bi-directional
MESSAGE
Decreasing
FREQ RATE 1 PICKUP: Range: 0.10 to 15.00 Hz/sec in steps of 0.01
MESSAGE
0.50 Hz/sec
FREQ RATE 1 OV SUPV Range: 0.100 to 3.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.700 pu
FREQ RATE 1 OC SUPV Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
PICKUP: 0.200 pu
FREQ RATE 1 MIN Range: 20.00 to 80.00 Hz in steps of 0.01
MESSAGE
FREQUENCY: 45.00 Hz
FREQ RATE 1 MAX Range: 20.00 to 80.00 Hz in steps of 0.01
MESSAGE
FREQUENCY: 65.00 Hz
FREQ RATE 1 PICKUP Range: 0 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.000 s 5
FREQ RATE 1 RESET Range: 0 to 65.535 s in steps of 0.001
MESSAGE
DELAY: 0.000 s
FREQ RATE 1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
FREQ RATE 1 TARGET: Range: Self-Reset, Latched, Disabled
MESSAGE
Self-Reset
FREQ RATE 1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

Four (4) independent rate of change of frequency elements are available. The element responds to rate of change of fre-
quency with voltage, current and frequency supervision.
• FREQ RATE 1 TREND: This setting allows configuring the element to respond to increasing or decreasing frequency,
or to frequency change in either direction.
• FREQ RATE 1 PICKUP: This setting specifies an intended df ⁄ dt pickup threshold. For applications monitoring a
decreasing trend, set FREQ RATE 1 TREND to “Decreasing” and specify the pickup threshold accordingly. The operating
condition is: – df ⁄ dt > Pickup .
For applications monitoring an increasing trend, set FREQ RATE 1 TREND to “Increasing” and specify the pickup thresh-
old accordingly. The operating condition is: df ⁄ dt > Pickup .
For applications monitoring rate of change of frequency in any direction set FREQ RATE 1 TREND to “Bi-Directional” and
specify the pickup threshold accordingly. The operating condition is: abs ( df ⁄ dt ) > Pickup
• FREQ RATE 1 OV SUPV PICKUP: This setting defines minimum voltage level required for operation of the element.
The supervising function responds to the positive-sequence voltage. Overvoltage supervision should be used to pre-
vent operation under specific system conditions such as faults.
• FREQ RATE 1 OC SUPV PICKUP: This setting defines minimum current level required for operation of the element.
The supervising function responds to the positive-sequence current. Typical application includes load shedding. Set
the pickup threshold to zero if no overcurrent supervision is required.

GE Multilin G60 Generator Protection System 5-227


5.7 CONTROL ELEMENTS 5 SETTINGS

• FREQ RATE 1 MIN FREQUENCY: This setting defines minimum frequency level required for operation of the element.
The setting may be used to effectively block the feature based on frequency. For example, if the intent is to monitor an
increasing trend but only if the frequency is already above certain level, this setting should be set to the required fre-
quency level.
• FREQ RATE 1 MAX FREQUENCY: This setting defines maximum frequency level required for operation of the ele-
ment. The setting may be used to effectively block the feature based on frequency. For example, if the intent is to mon-
itor a decreasing trend but only if the frequency is already below certain level (such as for load shedding), this setting
should be set to the required frequency level.
If the signal source assigned to the frequency rate of change element is only set to auxiliary VT, then the minimum
voltage supervision is 3 V.
NOTE

SETTINGS
SETTING
FREQ RATE 1 FUNCTION:
FREQ RATE 1 OV SUPV
Enabled = 1 PICKUP:
AND

FREQ RATE 1 BLOCK: RUN


Off
| V_1 | > PICKUP
SETTINGS
SETTING SETTINGS
FREQ RATE 1 PICKUP
DELAY:
SETTING FREQ RATE 1 OC SUPV FREQ RATE 1 TREND:
PICKUP: FREQ RATE 1 RESET
FREQ RATE 1 SOURCE: DELAY:
FREQ RATE 1 PICKUP:
RUN
tPKP FLEXLOGIC OPERANDS
AND

Pos seq voltage (V_1) RUN


Pos seq current (I_1) | I_1 | >PICKUP FREQ RATE 1 OP
Frequency (F) df/dt > PICKUP tRST
FREQ RATE 1 DPO
SETTINGS
FREQ RATE 1 PKP
FREQ RATE 1 MIN

5 FREQUENCY:

FREQ RATE 1 MAX


FREQUENCY:
RUN

F > MIN & F < MAX

RUN

Calculate df/dt
832023A2.CDR

Figure 5–131: FREQUENCY RATE OF CHANGE SCHEME LOGIC

5-228 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

5.7.8 FREQUENCY OUT-OF-BAND ACCUMULATION

a) GENERAL SETTINGS
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ FREQUENCY OOB ACCUMULATION

„ FREQUENCY OOB FREQ OOB ACCUM Range: SRC 1, SRC 2, SRC 3, SRC 4
„ ACCUMULATION SOURCE: SRC 1
FREQ OOB ACCUM MIN Range: 0.10 to 1.25 pu in steps of 0.01
MESSAGE
VOLT/AMP: 0.10 pu
FREQ ACCUM BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
FREQ OOB ACCUM Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
FREQ OOB ACCUM Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled
„ FREQUENCY OOB
MESSAGE See following section.
„ ACCUMULATOR 1
„ FREQUENCY OOB
MESSAGE See following section.
„ ACCUMULATOR 2

„ FREQUENCY OOB
MESSAGE See following section.
„ ACCUMULATOR 7 5
The turbine portion of a generator is designed to operate in a narrow frequency range around the nominal, typically ±5%.
As the turbine overspeeds (typically due to load rejection) or coasts down, the turbine will pass through operating frequen-
cies where the turbine blades find stimulus at their natural frequencies. Blade vibrations at these natural frequencies result
is stress on the blades that is accumulated and can result in cracking in some parts of the blade structure, most likely the tie
wires or blade covers. Though typically not catastrophic, the stress can change the vibration behavior of the blade so that
they can have natural resonances closer to the normal operating frequency. This element will provide diagnostic informa-
tion and alarms to the customer based on the accumulated off-nominal frequency operation time of a turbine over several
frequency bands and can then be used to schedule maintenance or other actions as desired by the customer.
The available setting of an upper and lower frequency for each band enables the user to overlap bands of frequencies in
the accumulation function. The accumulation function in any band can be blocked as desired. For example, accumulation
may be blocked during an out-of-service condition as set via an input to the relay.
The following settings are available and apply to all accumulators.
• FREQ OOB ACCUM SOURCE: This setting selects the source for the signal to be measured. The element first checks
for a live phase voltage available from the selected source. If voltage is not available, the element attempts to use a
phase current. If neither voltage nor current is available, the element will not operate, as it will not measure a parame-
ter below the minimum voltage/current setting.
• FREQ OOB ACCUM MIN VOLT/AMP: This setting specifies the minimum per-unit positive-sequence voltage or cur-
rent level required to allow the frequency out-of-band accumulators to operate. This threshold is used to prevent an
incorrect accumulation when operating quantity is too low.
• FREQ ACCUM BLOCK: This setting selects a FlexLogic™ operand to block out-of-band frequency accumulation in all
bands. This is typically required to avoid unnecessary accumulation when relay testing is being performed.

GE Multilin G60 Generator Protection System 5-229


5.7 CONTROL ELEMENTS 5 SETTINGS

b) ACCUMULATORS 1 TO 7
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ FREQUENCY OOB ACCUMULATION Ö FREQUENCY OOB ACCUMULATOR 1(7)

„ FREQUENCY OOB FREQ ACCUM 1 Range: Enabled, Disabled


„ ACCUMULATOR 1 FUNCTION: Disabled
FREQ ACCUM 1 UPPER Range: 20.00 to 70.00 Hz in steps of 0.01
MESSAGE
FREQ 60.00 Hz
FREQ ACCUM 1 LOWER Range: 20.00 to 70.00 Hz in steps of 0.01
MESSAGE
FREQ 60.00 Hz
FREQ ACCUM 1 TIME Range: 1 to 65535 s in steps of 1
MESSAGE
LIMIT: 200 s
FREQ ACCUM 1 TIME Range: 0 to 65535 s in steps of 1
MESSAGE
PRESET: 0 s

Seven frequency out-of-band accumulators are available. The following settings are available for each accumulator.
• FREQ ACCUM 1 FUNCTION: This setting enables and disabled a particular frequency band.
• FREQ ACCUM 1 UPPER FREQ: This setting specifies the upper frequency value, in Hz, below which band 1 values
start to accumulate. This upper frequency value must be greater than the lower frequency value.
• FREQ ACCUM 1 LOWER FREQ: This setting specifies the lower frequency value, in Hz, above which band 1 values
start to accumulate. This lower frequency value must be less than the upper frequency value.
• FREQ ACCUM 1 TIME LIMIT: This value specifies the accumulation time, in seconds, at which the overfrequency
accumulation band exceeds the overfrequency accumulation limit and operates.
5 • FREQ ACCUM 1 TIME PRESET: This setting allows the user to either transfer accumulated frequency time of opera-
tion values from a previous hardware platform to a new platform, or, given that some knowledge of the operation of the
turbine is known, to start accumulation at a user-specified value.

SETTING
SETTINGS SETTINGS
FREQ ACCUM BLOCK
FREQ ACCUM 1 UPPER FREQ ACCUM 1 TIME
= Off FREQ LIMIT
FREQ ACCUM 1 LOWER FREQ ACCUM 1 TIME
SETTING SETTING AND
FREQ PRESET
FREQ OOB ACCUM FREQ OOB ACCUM MIN AND RUN RUN
Accumulating
SOURCE VOLT/AMP
fLOWER < f ≤ f UPPER tACCUM > tLIMIT
= Volt/amp mag V/A > MINIMUM
= Frequency
ACTUAL VALUE
FLEXLOGIC OPERANDS
SETTING FREQ OOB BAND 1 FREQ OOB BAND 1 OP
FREQ ACCUM 1 ACCUMULATION
FUNCTION FREQ OOB BAND 1 DPO
= Enabled FREQ OOB BAND 1 PKP

FLEXLOGIC OPERANDS
COMMANDS FREQ OOB BAND 2 OP
RESET FREQ OOB FREQ OOB BAND 3 OP FLEXLOGIC OPERAND
ACCUMULATORS FREQ OOB BAND 4 OP OR FREQ OOB ACCUM OP
PRESET FREQ OOB FREQ OOB BAND 5 OP
ACCUMULATORS FREQ OOB BAND 6 OP
FREQ OOB BAND 7 OP

FLEXLOGIC OPERANDS
FREQ OOB BAND 2 PKP
FLEXLOGIC OPERAND
FREQ OOB BAND 3 PKP
OR FREQ OOB ACCUM PKP
FREQ OOB BAND 4 PKP
FREQ OOB BAND 5 PKP
FREQ OOB BAND 6 PKP
FREQ OOB BAND 7 PKP 830008A1.CDR

Figure 5–132: FREQUENCY OUT-OF-BAND ACCUMULATION LOGIC

5-230 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

5.7.9 SYNCHROCHECK

a) SETTINGS
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ SYNCHROCHECK Ö SYNCHROCHECK 1(2)

„ SYNCHROCHECK 1 SYNCHK1 FUNCTION: Range: Disabled, Enabled


„ Disabled
SYNCHK1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
SYNCHK1 V1 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SRC 1
SYNCHK1 V2 SOURCE: Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SRC 2
SYNCHK1 MAX VOLT Range: 0 to 400000 V in steps of 1
MESSAGE
DIFF: 10000 V
SYNCHK1 MAX ANGLE Range: 0 to 100° in steps of 1
MESSAGE
DIFF: 30°
SYNCHK1 MAX FREQ Range: 0.00 to 2.00 Hz in steps of 0.01
MESSAGE
DIFF: 1.00 Hz
SYNCHK1 MAX FREQ Range: 0.00 to 0.10 Hz in steps of 0.01
MESSAGE
HYSTERESIS: 0.06 Hz

MESSAGE
SYNCHK1 DEAD SOURCE Range: None, LV1 and DV2, DV1 and LV2, DV1 or DV2,
DV1 Xor DV2, DV1 and DV2
5
SELECT: LV1 and DV2
SYNCHK1 DEAD V1 Range: 0.00 to 1.25 pu in steps of 0.01
MESSAGE
MAX VOLT: 0.30 pu
SYNCHK1 DEAD V2 Range: 0.00 to 1.25 pu in steps of 0.01
MESSAGE
MAX VOLT: 0.30 pu
SYNCHK1 LIVE V1 Range: 0.00 to 1.25 pu in steps of 0.01
MESSAGE
MIN VOLT: 0.70 pu
SYNCHK1 LIVE V2 Range: 0.00 to 1.25 pu in steps of 0.01
MESSAGE
MIN VOLT: 0.70 pu
SYNCHK1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
SYNCHK1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

The are two identical synchrocheck elements available, numbered 1 and 2.


The synchronism check function is intended for supervising the paralleling of two parts of a system which are to be joined
by the closure of a circuit breaker. The synchrocheck elements are typically used at locations where the two parts of the
system are interconnected through at least one other point in the system.
Synchrocheck verifies that the voltages (V1 and V2) on the two sides of the supervised circuit breaker are within set limits
of magnitude, angle and frequency differences. The time that the two voltages remain within the admissible angle differ-
ence is determined by the setting of the phase angle difference ΔΦ and the frequency difference ΔF (slip frequency). It can
be defined as the time it would take the voltage phasor V1 or V2 to traverse an angle equal to 2 × ΔΦ at a frequency equal
to the frequency difference ΔF. This time can be calculated by:
1
T = -------------------------------
- (EQ 5.47)
360°
------------------ × ΔF
2 × ΔΦ

GE Multilin G60 Generator Protection System 5-231


5.7 CONTROL ELEMENTS 5 SETTINGS

where: ΔΦ = phase angle difference in degrees; ΔF = frequency difference in Hz.


If one or both sources are de-energized, the synchrocheck programming can allow for closing of the circuit breaker using
undervoltage control to by-pass the synchrocheck measurements (dead source function).
• SYNCHK1 V1 SOURCE: This setting selects the source for voltage V1 (see NOTES below).
• SYNCHK1 V2 SOURCE: This setting selects the source for voltage V2, which must not be the same as used for the
V1 (see NOTES below).
• SYNCHK1 MAX VOLT DIFF: This setting selects the maximum primary voltage difference in volts between the two
sources. A primary voltage magnitude difference between the two input voltages below this value is within the permis-
sible limit for synchronism.
• SYNCHK1 MAX ANGLE DIFF: This setting selects the maximum angular difference in degrees between the two
sources. An angular difference between the two input voltage phasors below this value is within the permissible limit
for synchronism.
• SYNCHK1 MAX FREQ DIFF: This setting selects the maximum frequency difference in ‘Hz’ between the two sources.
A frequency difference between the two input voltage systems below this value is within the permissible limit for syn-
chronism.
• SYNCHK1 MAX FREQ HYSTERESIS: This setting specifies the required hysteresis for the maximum frequency differ-
ence condition. The condition becomes satisfied when the frequency difference becomes lower than SYNCHK1 MAX
FREQ DIFF. Once the Synchrocheck element has operated, the frequency difference must increase above the SYNCHK1
MAX FREQ DIFF + SYNCHK1 MAX FREQ HYSTERESIS sum to drop out (assuming the other two conditions, voltage and
angle, remain satisfied).
• SYNCHK1 DEAD SOURCE SELECT: This setting selects the combination of dead and live sources that will by-pass
synchronism check function and permit the breaker to be closed when one or both of the two voltages (V1 or/and V2)
5 are below the maximum voltage threshold. A dead or live source is declared by monitoring the voltage level. Six
options are available:
None: Dead Source function is disabled
LV1 and DV2: Live V1 and Dead V2
DV1 and LV2: Dead V1 and Live V2
DV1 or DV2: Dead V1 or Dead V2
DV1 Xor DV2: Dead V1 exclusive-or Dead V2 (one source is Dead and the other is Live)
DV1 and DV2: Dead V1 and Dead V2
• SYNCHK1 DEAD V1 MAX VOLT: This setting establishes a maximum voltage magnitude for V1 in 1 ‘pu’. Below this
magnitude, the V1 voltage input used for synchrocheck will be considered “Dead” or de-energized.
• SYNCHK1 DEAD V2 MAX VOLT: This setting establishes a maximum voltage magnitude for V2 in ‘pu’. Below this
magnitude, the V2 voltage input used for synchrocheck will be considered “Dead” or de-energized.
• SYNCHK1 LIVE V1 MIN VOLT: This setting establishes a minimum voltage magnitude for V1 in ‘pu’. Above this mag-
nitude, the V1 voltage input used for synchrocheck will be considered “Live” or energized.
• SYNCHK1 LIVE V2 MIN VOLT: This setting establishes a minimum voltage magnitude for V2 in ‘pu’. Above this mag-
nitude, the V2 voltage input used for synchrocheck will be considered “Live” or energized.
NOTES ON THE SYNCHROCHECK FUNCTION:
1. The selected sources for synchrocheck inputs V1 and V2 (which must not be the same source) may include both a
three-phase and an auxiliary voltage. The relay will automatically select the specific voltages to be used by the synch-
rocheck element in accordance with the following table.

NO. V1 OR V2 V2 OR V1 AUTO-SELECTED AUTO-SELECTED VOLTAGE


(SOURCE Y) (SOURCE Z) COMBINATION
SOURCE Y SOURCE Z
1 Phase VTs and Phase VTs and Phase Phase VAB
Auxiliary VT Auxiliary VT
2 Phase VTs and Phase VT Phase Phase VAB
Auxiliary VT
3 Phase VT Phase VT Phase Phase VAB

5-232 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

NO. V1 OR V2 V2 OR V1 AUTO-SELECTED AUTO-SELECTED VOLTAGE


(SOURCE Y) (SOURCE Z) COMBINATION
SOURCE Y SOURCE Z
4 Phase VT and Auxiliary VT Phase Auxiliary V auxiliary
Auxiliary VT (as set for Source z)
5 Auxiliary VT Auxiliary VT Auxiliary Auxiliary V auxiliary
(as set for selected sources)

The voltages V1 and V2 will be matched automatically so that the corresponding voltages from the two sources will be
used to measure conditions. A phase to phase voltage will be used if available in both sources; if one or both of the
Sources have only an auxiliary voltage, this voltage will be used. For example, if an auxiliary voltage is programmed to
VAG, the synchrocheck element will automatically select VAG from the other source. If the comparison is required on a
specific voltage, the user can externally connect that specific voltage to auxiliary voltage terminals and then use this
"Auxiliary Voltage" to check the synchronism conditions.
If using a single CT/VT module with both phase voltages and an auxiliary voltage, ensure that only the auxiliary voltage
is programmed in one of the sources to be used for synchrocheck.
Exception: Synchronism cannot be checked between Delta connected phase VTs and a Wye con-
nected auxiliary voltage.
NOTE

2. The relay measures frequency and Volts/Hz from an input on a given source with priorities as established by the con-
figuration of input channels to the source. The relay will use the phase channel of a three-phase set of voltages if pro-
grammed as part of that source. The relay will use the auxiliary voltage channel only if that channel is programmed as
part of the Source and a three-phase set is not.

GE Multilin G60 Generator Protection System 5-233


5.7 CONTROL ELEMENTS 5 SETTINGS

FLEXLOGIC OPERAND
AND SYNC1 V2 ABOVE MIN

FLEXLOGIC OPERAND
AND SYNC1 V1 ABOVE MIN

FLEXLOGIC OPERAND
AND SYNC1 V1 BELOW MAX

SETTINGS
FLEXLOGIC OPERAND
Function
AND SYNC1 V2 BELOW MAX
Enabled = 1
Disabled = 0
AND
Block
Off = 0
AND
FLEXLOGIC OPERANDS
AND SYNC1 DEAD S OP
AND SYNC1 DEAD S DPO

SETTING
Dead Source Select FLEXLOGIC OPERANDS
AND OR OR SYNC1 CLS OP
None
LV1 and DV2 SYNC1 CLS DPO
DV1 and LV2
AND
DV1 or DV2
DV1 xor DV2
DV1 and DV2
AND
SETTING
Dead V1 Max Volt

V1 ≤ Maximum
XOR

SETTING
Dead V2 Max Volt
OR
V2 ≤ Maximum

5 SETTING
Live V1 Min Volt
AND
V1 ≥ Minimum

SETTING
Live V2 Min Volt
AND
V2 ≥ Minimum

SETTING
CALCULATE Max Volt Diff
SETTING Magnitude V1 Calculate
ΔV ≤ Maximum
V1 Source Angle Φ1 I V1 – V2 I = ΔV
= SRC 1 Frequency F1 FLEXLOGIC OPERANDS
AND SYNC1 SYNC OP
SETTING
SYNC1 SYNC DPO
Max Angle Diff
Calculate
ΔΦ ≤ Maximum
I Φ1 – Φ2 I = ΔΦ

SETTINGS SYNCHROCHECK 1
CALCULATE Max Freq Diff
SETTING Magnitude V2 Freq Hysteresis
V2 Source Angle Φ2 Calculate
ΔF ≤ Maximum
= SRC 2 Frequency F2 I F1 – F2 I = ΔF
ACTUAL VALUE
Synchrocheck 1 ΔV
Synchrocheck 1 ΔΦ
Synchrocheck 1 ΔF
827076AB.CDR

Figure 5–133: SYNCHROCHECK SCHEME LOGIC

5-234 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

b) SPECIAL APPLICATION OF THE SYNCHROCHECK ELEMENT


The synchrocheck element is intended for applications where the potential sources are located on either side of the breaker
to be closed. It can also be used in cases where a power transformer is located between the two potential sources by com-
pensating for the power transformer phase shift with the auxiliary VT connection to the G60 and the auxiliary VT connection
setting, as shown in the following example.

a A

System nominal b 52 System nominal


Vpp = 13.8 kV B
Vpp = 230 kV

c
C

14400 : 120 138000 : 69

~5a ~5c ~6a ~6c ~7a ~7c ~8a ~8c

Phase VT input Auxiliary VT input

UR-series device
5
843808A2.CDR

Figure 5–134: SYNCHROCHECK APPLIED ACROSS A TRANSFORMER


In this example, the phase voltage VT input is programmed as “Delta” with a secondary setting of 120 volts and a ratio of
13800 V/ 120 V = 115. The auxiliary VT connection is selected to be VAB since this vector is in phase with VA on the trans-
former primary. The secondary setting is 69 volts and the auxiliary VT ratio is calculated as 13800 V / 69 V = 200. Note that
the metered values for the auxiliary VT will now reflect the AB voltage of the secondary side of the transformer.

GE Multilin G60 Generator Protection System 5-235


5.7 CONTROL ELEMENTS 5 SETTINGS

5.7.10 DIGITAL ELEMENTS

PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ DIGITAL ELEMENTS Ö DIGITAL ELEMENT 1(48)

„ DIGITAL ELEMENT 1 DIGITAL ELEMENT 1 Range: Disabled, Enabled


„ FUNCTION: Disabled
DIG ELEM 1 NAME: Range: 16 alphanumeric characters
MESSAGE
Dig Element 1
DIG ELEM 1 INPUT: Range: FlexLogic™ operand
MESSAGE
Off
DIG ELEM 1 PICKUP Range: 0.000 to 999999.999 s in steps of 0.001
MESSAGE
DELAY: 0.000 s
DIG ELEM 1 RESET Range: 0.000 to 999999.999 s in steps of 0.001
MESSAGE
DELAY: 0.000 s
DIG ELEMENT 1 Range: Disabled, Enabled
MESSAGE
PICKUP LED: Enabled
DIG ELEM 1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
DIGITAL ELEMENT 1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
DIGITAL ELEMENT 1 Range: Disabled, Enabled

5 MESSAGE
EVENTS: Disabled

There are 48 identical digital elements available, numbered 1 to 48. A digital element can monitor any FlexLogic™ operand
and present a target message and/or enable events recording depending on the output operand state. The digital element
settings include a name which will be referenced in any target message, a blocking input from any selected FlexLogic™
operand, and a timer for pickup and reset delays for the output operand.
• DIGITAL ELEMENT 1 INPUT: Selects a FlexLogic™ operand to be monitored by the digital element.
• DIGITAL ELEMENT 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set to "0".
• DIGITAL ELEMENT 1 RESET DELAY: Sets the time delay to reset. If a reset delay is not required, set to “0”.
• DIGITAL ELEMENT 1 PICKUP LED: This setting enables or disabled the digital element pickup LED. When set to
“Disabled”, the operation of the pickup LED is blocked.

SETTING
DIGITAL ELEMENT 01
FUNCTION:
Disabled = 0 SETTINGS
Enabled = 1 DIGITAL ELEMENT 01
SETTING PICKUP DELAY:
DIGITAL ELEMENT 01 DIGITAL ELEMENT 01 FLEXLOGIC OPERANDS
SETTING
NAME: RESET DELAY:
DIGITAL ELEMENT 01 DIG ELEM 01 DPO
AND RUN tPKP
INPUT: DIG ELEM 01 PKP
Off = 0 DIG ELEM 01 OP
INPUT = 1 tRST
SETTING
DIGITAL ELEMENT 01
BLOCK:
827042A1.VSD
Off = 0

Figure 5–135: DIGITAL ELEMENT SCHEME LOGIC


CIRCUIT MONITORING APPLICATIONS:
Some versions of the digital input modules include an active voltage monitor circuit connected across form-A contacts. The
voltage monitor circuit limits the trickle current through the output circuit (see technical specifications for form-A).

5-236 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

As long as the current through the voltage monitor is above a threshold (see technical specifications for form-A), the “Cont
Op 1 VOn” FlexLogic™ operand will be set (for contact input 1 – corresponding operands exist for each contact output). If
the output circuit has a high resistance or the DC current is interrupted, the trickle current will drop below the threshold and
the “Cont Op 1 VOff” FlexLogic™ operand will be set. Consequently, the state of these operands can be used as indicators
of the integrity of the circuits in which form-A contacts are inserted.
EXAMPLE 1: BREAKER TRIP CIRCUIT INTEGRITY MONITORING
In many applications it is desired to monitor the breaker trip circuit integrity so problems can be detected before a trip oper-
ation is required. The circuit is considered to be healthy when the voltage monitor connected across the trip output contact
detects a low level of current, well below the operating current of the breaker trip coil. If the circuit presents a high resis-
tance, the trickle current will fall below the monitor threshold and an alarm would be declared.
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact which is open when the
breaker is open (see diagram below). To prevent unwanted alarms in this situation, the trip circuit monitoring logic must
include the breaker position.
UR-series device
with form-A contacts

H1a
I

H1b DC–

V DC+
H1c 52a Trip coil
5
I = current monitor
V = voltage monitor 827073A2.CDR

Figure 5–136: TRIP CIRCUIT EXAMPLE 1


Assume the output contact H1 is a trip contact. Using the contact output settings, this output will be given an ID name; for
example, “Cont Op 1". Assume a 52a breaker auxiliary contact is connected to contact input H7a to monitor breaker status.
Using the contact input settings, this input will be given an ID name, for example, “Cont Ip 1", and will be set “On” when the
breaker is closed. The settings to use digital element 1 to monitor the breaker trip circuit are indicated below (EnerVista UR
Setup example shown):

The PICKUP DELAY setting should be greater than the operating time of the breaker to avoid nuisance
alarms.
NOTE

GE Multilin G60 Generator Protection System 5-237


5.7 CONTROL ELEMENTS 5 SETTINGS

EXAMPLE 2: BREAKER TRIP CIRCUIT INTEGRITY MONITORING


If it is required to monitor the trip circuit continuously, independent of the breaker position (open or closed), a method to
maintain the monitoring current flow through the trip circuit when the breaker is open must be provided (as shown in the fig-
ure below). This can be achieved by connecting a suitable resistor (see figure below) across the auxiliary contact in the trip
circuit. In this case, it is not required to supervise the monitoring circuit with the breaker position – the BLOCK setting is
selected to “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown).

UR-series device
with form-A contacts

5 H1a
Values for resistor “R”
Power supply Resistance Power
I
24 V DC 1000 Ω 2W
H1b DC– 30 V DC 5000 Ω 2W
48 V DC 10000 Ω 2W
V DC+
110 V DC 25000 Ω 5W
H1c 52a Trip coil
125 V DC 25000 Ω 5W
R
250 V DC 50000 Ω 5W
Bypass
I = current monitor resistor
V = voltage monitor 827074A3.CDR

Figure 5–137: TRIP CIRCUIT EXAMPLE 2


The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and
solid-state contact with voltage monitoring.
NOTE

5-238 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

5.7.11 DIGITAL COUNTERS

PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ DIGITAL COUNTERS Ö COUNTER 1(8)

„ COUNTER 1 COUNTER 1 Range: Disabled, Enabled


„ FUNCTION: Disabled
COUNTER 1 NAME: Range: 12 alphanumeric characters
MESSAGE
Counter 1
COUNTER 1 UNITS: Range: 6 alphanumeric characters
MESSAGE

COUNTER 1 PRESET: Range: –2,147,483,648 to +2,147,483,647


MESSAGE
0
COUNTER 1 COMPARE: Range: –2,147,483,648 to +2,147,483,647
MESSAGE
0
COUNTER 1 UP: Range: FlexLogic™ operand
MESSAGE
Off
COUNTER 1 DOWN: Range: FlexLogic™ operand
MESSAGE
Off
COUNTER 1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
CNT1 SET TO PRESET: Range: FlexLogic™ operand
MESSAGE
Off 5
COUNTER 1 RESET: Range: FlexLogic™ operand
MESSAGE
Off
COUNT1 FREEZE/RESET: Range: FlexLogic™ operand
MESSAGE
Off
COUNT1 FREEZE/COUNT: Range: FlexLogic™ operand
MESSAGE
Off

There are 8 identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions from
Logic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of an
external contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter.
• COUNTER 1 UNITS: Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted.
The units label will appear in the corresponding actual values status.
• COUNTER 1 PRESET: Sets the count to a required preset value before counting operations begin, as in the case
where a substitute relay is to be installed in place of an in-service relay, or while the counter is running.
• COUNTER 1 COMPARE: Sets the value to which the accumulated count value is compared. Three FlexLogic™ output
operands are provided to indicate if the present value is ‘more than (HI)’, ‘equal to (EQL)’, or ‘less than (LO)’ the set
value.
• COUNTER 1 UP: Selects the FlexLogic™ operand for incrementing the counter. If an enabled UP input is received
when the accumulated value is at the limit of +2,147,483,647 counts, the counter will rollover to –2,147,483,648.
• COUNTER 1 DOWN: Selects the FlexLogic™ operand for decrementing the counter. If an enabled DOWN input is
received when the accumulated value is at the limit of –2,147,483,648 counts, the counter will rollover to
+2,147,483,647.
• COUNTER 1 BLOCK: Selects the FlexLogic™ operand for blocking the counting operation. All counter operands are
blocked.

GE Multilin G60 Generator Protection System 5-239


5.7 CONTROL ELEMENTS 5 SETTINGS

• CNT1 SET TO PRESET: Selects the FlexLogic™ operand used to set the count to the preset value. The counter will
be set to the preset value in the following situations:
1. When the counter is enabled and the CNT1 SET TO PRESET operand has the value 1 (when the counter is enabled
and CNT1 SET TO PRESET operand is 0, the counter will be set to 0).
2. When the counter is running and the CNT1 SET TO PRESET operand changes the state from 0 to 1 (CNT1 SET TO
PRESET changing from 1 to 0 while the counter is running has no effect on the count).
3. When a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the value
1 (when a reset or reset/freeze command is sent to the counter and the CNT1 SET TO PRESET operand has the
value 0, the counter will be set to 0).
• COUNTER 1 RESET: Selects the FlexLogic™ operand for setting the count to either “0” or the preset value depending
on the state of the CNT1 SET TO PRESET operand.
• COUNTER 1 FREEZE/RESET: Selects the FlexLogic™ operand for capturing (freezing) the accumulated count value
into a separate register with the date and time of the operation, and resetting the count to “0”.
• COUNTER 1 FREEZE/COUNT: Selects the FlexLogic™ operand for capturing (freezing) the accumulated count value
into a separate register with the date and time of the operation, and continuing counting. The present accumulated
value and captured frozen value with the associated date/time stamp are available as actual values. If control power is
interrupted, the accumulated and frozen values are saved into non-volatile memory during the power down operation.

SETTING
COUNTER 1 FUNCTION:
Disabled = 0
SETTINGS
Enabled = 1
COUNTER 1 NAME:

5 SETTING
COUNTER 1 UP:
AND COUNTER 1 UNITS:
COUNTER 1 PRESET:
RUN
Off = 0 SETTING
FLEXLOGIC
COUNTER 1 COMPARE: OPERANDS
SETTING
CALCULATE Count more than Comp. COUNTER 1 HI
COUNTER 1 DOWN: VALUE Count equal to Comp. COUNTER 1 EQL
Off = 0 Count less than Comp. COUNTER 1 LO

SETTING
COUNTER 1 BLOCK:
Off = 0 SET TO PRESET VALUE

SETTING SET TO ZERO


ACTUAL VALUE
CNT 1 SET TO PRESET: COUNTER 1 ACCUM:
Off = 0
AND

SETTING AND ACTUAL VALUES


COUNTER 1 RESET:
COUNTER 1 FROZEN:
Off = 0
OR STORE DATE & TIME Date & Time
SETTING
COUNT1 FREEZE/RESET:
Off = 0
OR
827065A1.VSD
SETTING
COUNT1 FREEZE/COUNT:
Off = 0

Figure 5–138: DIGITAL COUNTER SCHEME LOGIC

5-240 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

5.7.12 MONITORING ELEMENTS

a) MAIN MENU
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTS

„ MONITORING „ VT FUSE FAILURE 1


See page 5–241.
„ ELEMENTS „
„ VT FUSE FAILURE 2
MESSAGE See page 5–241.
„
„ VT FUSE FAILURE 3
MESSAGE See page 5–241.
„
„ VT FUSE FAILURE 4
MESSAGE See page 5–241.
„
„ THERMAL OVERLOAD
MESSAGE See page 5–243.
„ PROTECTION

b) VT FUSE FAILURE
PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTS ÖØ VT FUSE FAILURE 1(4)

„ VT FUSE FAILURE 1 VT FUSE FAILURE 1 Range: Disabled, Enabled


„ FUNCTION: Disabled

Every signal source includes a fuse failure scheme.


The VT fuse failure detector can be used to raise an alarm and/or block elements that may operate incorrectly for a full or 5
partial loss of AC potential caused by one or more blown fuses. Some elements that might be blocked (via the BLOCK input)
are distance, voltage restrained overcurrent, and directional current.
There are two classes of fuse failure that may occur:
• Class A: loss of one or two phases.
• Class B: loss of all three phases.
Different means of detection are required for each class. An indication of class A failures is a significant level of negative-
sequence voltage, whereas an indication of class B failures is when positive sequence current is present and there is an
insignificant amount of positive sequence voltage. These noted indications of fuse failure could also be present when faults
are present on the system, so a means of detecting faults and inhibiting fuse failure declarations during these events is pro-
vided. Once the fuse failure condition is declared, it will be sealed-in until the cause that generated it disappears.
An additional condition is introduced to inhibit a fuse failure declaration when the monitored circuit is de-energized; positive-
sequence voltage and current are both below threshold levels.
The function setting enables and disables the fuse failure feature for each source.

GE Multilin G60 Generator Protection System 5-241


5.7 CONTROL ELEMENTS 5 SETTINGS

AND
Reset-dominant
OR SET

FAULT
Latch
AND

RESET
SETTING
Function
Disabled = 0
Enabled = 1
AND
COMPARATORS
SOURCE 1 Run
V_2 V_2 > 0.1 pu

V_1 Run OR OR SET


I_1 V_1 < 0.05 pu FUSE
FAIL
Run AND
I_1 > 0.075 pu

Run AND
TIMER
V_1 < 0.80 pu
2 cycles
FLEXLOGIC OPERANDS
Run AND
I_1 < 0.05 pu Latch SRC1 VT FUSE FAIL OP
20 cycles
SRC1 VT FUSE FAIL DPO
FLEXLOGIC OPERANDS
SRC1 50DD OP
OPEN POLE OP
The OPEN POLE OP operand is applicable
AND
to the D60, L60, and L90 only.
RESET
OR
Reset-dominant
AND

FLEXLOGIC OPERAND

5 AND SRC1 VT FUSE FAIL VOL LOSS


827093AM.CDR

Figure 5–139: VT FUSE FAIL SCHEME LOGIC

5-242 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

c) THERMAL OVERLOAD PROTECTION


PATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ MONITORING ELEMENTS ÖØ THERMAL OVERLOAD PROTECTION ÖØ THERMAL
PROTECTION 1(2)

„ THERMAL THERMAL PROTECTION 1 Range: Disabled, Enabled


„ PROTECTION 1 FUNCTION: Disabled
THERMAL PROTECTION 1 Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
SOURCE: SRC1
THERMAL PROTECTION 1 Range: 0.20 to 3.00 pu in steps of 0.01
MESSAGE
BASE CURR: 0.80 pu
THERMAL PROTECTION 1 Range: 1.00 to 1.20 in steps of 0.05
MESSAGE
k FACTOR: 1.10
THERM PROT 1 TRIP Range: 0 to 1000 min. in steps of 1
MESSAGE
TIME CONST: 45 min.
THERM PROT 1 RESET Range: 0 to 1000 min. in steps of 1
MESSAGE
TIME CONST: 45 min.
THERM PROT 1 MINIM Range: 0 to 1000 min. in steps of 1
MESSAGE
RESET TIME: 20 min.
THERM PROT 1 RESET: Range: FlexLogic™ operand
MESSAGE
Off
THERM PROT 1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off 5
THERMAL PROTECTION 1 Range: Self-reset, Latched, Disabled
MESSAGE
TARGET: Self-reset
THERMAL PROTECTION 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

The thermal overload protection element corresponds to the IEC 255-8 standard and is used to detect thermal overload
conditions in protected power system elements. Choosing an appropriate time constant element can be used to protect dif-
ferent elements of the power system. The cold curve characteristic is applied when the previous averaged load current over
the last 5 cycles is less than 10% of the base current. If this current is greater or equal than 10% than the base current, then
the hot curve characteristic is applied.
The IEC255-8 cold curve is defined as follows:

⎛ I
2 ⎞
t op = τ op × ln ⎜ -------------------------
-⎟ (EQ 5.48)
⎝ I – ( kI B ) ⎠
2 2

The IEC255-8 hot curve is defined as follows:


2 2
⎛ I – Ip ⎞
t op = τ op × ln ⎜ -------------------------
-⎟ (EQ 5.49)
⎝ I 2 – ( kI B ) 2⎠

In the above equations,


• top = time to operate.
• τop = thermal protection trip time constant.
• I = measured overload RMS current.
• Ip = measured load RMS current before overload occurs.
• k= IEC 255-8 k-factor applied to IB, defining maximum permissible current above nominal current.
• IB = protected element base (nominal) current.

GE Multilin G60 Generator Protection System 5-243


5.7 CONTROL ELEMENTS 5 SETTINGS

The reset time of the thermal overload protection element is also time delayed using following formula:
2
⎛ ( kI B ) ⎞
t rst = τ rst × ln ⎜ ----------------------------
-⎟ + T min (EQ 5.50)
⎝ I – ( kI B ) ⎠
2 2

In the above equation,


• τrst = thermal protection trip time constant.
• Tmin is a minimum reset time setting

100

Tmin = 10

10

τrst = 30
τop = 30

5
t (min)

0.1

0.01
0.1 1 10 100
I / Ipkp
827724A1.CDR

Figure 5–140: IEC 255-8 SAMPLE OPERATE AND RESET CURVES


The thermal overload protection element estimates accumulated thermal energy E using the following equations calculated
each power cycle. When current is greater than the pickup level, In > k × IB, element starts increasing the thermal energy:
Δt -
E n = E n – 1 + -------------- (EQ 5.51)
t op ( In )

When current is less than the dropout level, In > 0.97 × k × IB, the element starts decreasing the thermal energy:

5-244 G60 Generator Protection System GE Multilin


5 SETTINGS 5.7 CONTROL ELEMENTS

Δt -
E n = E n – 1 – -------------- (EQ 5.52)
t rst ( In )

In the above equations,


• Δt is the power cycle duration.
• n is the power cycle index.
• top(In) is the trip time calculated at index n as per the IEC255-8 cold curve or hot curve equations.
• trst(In) is the reset time calculated at index n as per the reset time equation.
• In is the measured overload RMS current at index n.
• En is the accumulated energy at index n.
• En – 1 is the accumulated energy at index n – 1.
The thermal overload protection element removes the THERMAL PROT 1 OP output operand when E < 0.05. In case of
emergency, the thermal memory and THERMAL PROT 1 OP output operand can be reset using THERM PROT 1 RESET setting.
All calculations are performed per phase. If the accumulated energy reaches value 1 in any phase, the thermal overload
protection element operates and only resets when energy is less than 0.05 in all three phases.

Table 5–26: TYPICAL TIME CONSTANTS


PROTECTED EQUIPMENT TIME CONSTANT MINIMUM RESET TIME
Capacitor bank 10 minutes 30 minutes
Overhead line 10 minutes 20 minutes
Air-core reactor 40 minutes 30 minutes
Busbar 60 minutes 20 minutes 5
Underground cable 20 to 60 minutes 60 minutes

The logic for the thermal overload protection element is shown below.

SETTINGS
Function
Enabled = 1
Block AND
Off = 0

SETTINGS FLEXLOGIC OPERAND


SETTING Base Current AND THERMAL PROT 1 PKP
Source K Factor
IA RMS IA > k × Ib SETTING
IB RMS IB > k × Ib OR Trip Time Constant
IC RMS IC > k × Ic RUN

E > 0.1 S FLEXLOGIC OPERAND


Latch THERMAL PROT 1 OP
R
Reset-dominant

SETTINGS
Reset Time Constant
Minimum Reset Time
RUN

E < 0.1

SETTING
Reset
Off = 0 Reset E to 0 827013A1.CDR

Figure 5–141: THERMAL OVERLOAD PROTECTION SCHEME LOGIC

GE Multilin G60 Generator Protection System 5-245


5.8 INPUTS/OUTPUTS 5 SETTINGS

5.8INPUTS/OUTPUTS 5.8.1 CONTACT INPUTS

PATH: SETTINGS ÖØ INPUTS/OUTPUTS Ö CONTACT INPUTS

„ CONTACT INPUTS
„

„ CONTACT INPUT H5a


„

CONTACT INPUT H5a ID: Range: up to 12 alphanumeric characters


MESSAGE
Cont Ip 1

CONTACT INPUT H5a Range: 0.0 to 16.0 ms in steps of 0.5


MESSAGE
DEBNCE TIME: 2.0 ms

CONTACT INPUT H5a Range: Disabled, Enabled


MESSAGE
EVENTS: Disabled

„ CONTACT INPUT xxx


„

„ CONTACT INPUT
„ THRESHOLDS

Ips H5a,H5c,H6a,H6c Range: 17, 33, 84, 166 Vdc


MESSAGE

5 THRESHOLD: 33 Vdc

Ips H7a,H7c,H8a,H8c Range: 17, 33, 84, 166 Vdc


MESSAGE
THRESHOLD: 33 Vdc

Ips xxx,xxx,xxx,xxx Range: 17, 33, 84, 166 Vdc


MESSAGE
THRESHOLD: 33 Vdc

The contact inputs menu contains configuration settings for each contact input as well as voltage thresholds for each group
of four contact inputs. Upon startup, the relay processor determines (from an assessment of the installed modules) which
contact inputs are available and then display settings for only those inputs.
An alphanumeric ID may be assigned to a contact input for diagnostic, setting, and event recording purposes. The CON-
TACT IP X On” (Logic 1) FlexLogic™ operand corresponds to contact input “X” being closed, while CONTACT IP X Off corre-
sponds to contact input “X” being open. The CONTACT INPUT DEBNCE TIME defines the time required for the contact to
overcome ‘contact bouncing’ conditions. As this time differs for different contact types and manufacturers, set it as a maxi-
mum contact debounce time (per manufacturer specifications) plus some margin to ensure proper operation. If CONTACT
INPUT EVENTS is set to “Enabled”, every change in the contact input state will trigger an event.

A raw status is scanned for all Contact Inputs synchronously at the constant rate of 0.5 ms as shown in the figure below.
The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user-
settable debounce time in order for the G60 to validate the new contact state. In the figure below, the debounce time is set
at 2.5 ms; thus the 6th sample in a row validates the change of state (mark no. 1 in the diagram). Once validated (de-
bounced), the contact input asserts a corresponding FlexLogic™ operand and logs an event as per user setting.
A time stamp of the first sample in the sequence that validates the new state is used when logging the change of the con-
tact input into the Event Recorder (mark no. 2 in the diagram).
Protection and control elements, as well as FlexLogic™ equations and timers, are executed eight times in a power system
cycle. The protection pass duration is controlled by the frequency tracking mechanism. The FlexLogic™ operand reflecting
the debounced state of the contact is updated at the protection pass following the validation (marks no. 3 and 4 on the fig-
ure below). The update is performed at the beginning of the protection pass so all protection and control functions, as well
as FlexLogic™ equations, are fed with the updated states of the contact inputs.

5-246 G60 Generator Protection System GE Multilin


5 SETTINGS 5.8 INPUTS/OUTPUTS

The FlexLogic™ operand response time to the contact input change is equal to the debounce time setting plus up to one
protection pass (variable and depending on system frequency if frequency tracking enabled). If the change of state occurs
just after a protection pass, the recognition is delayed until the subsequent protection pass; that is, by the entire duration of
the protection pass. If the change occurs just prior to a protection pass, the state is recognized immediately. Statistically a
delay of half the protection pass is expected. Owing to the 0.5 ms scan rate, the time resolution for the input contact is
below 1msec.
For example, 8 protection passes per cycle on a 60 Hz system correspond to a protection pass every 2.1 ms. With a con-
tact debounce time setting of 3.0 ms, the FlexLogic™ operand-assert time limits are: 3.0 + 0.0 = 3.0 ms and 3.0 + 2.1 = 5.1
ms. These time limits depend on how soon the protection pass runs after the debouncing time.
Regardless of the contact debounce time setting, the contact input event is time-stamped with a 1 μs accuracy using the
time of the first scan corresponding to the new state (mark no. 2 below). Therefore, the time stamp reflects a change in the
DC voltage across the contact input terminals that was not accidental as it was subsequently validated using the debounce
timer. Keep in mind that the associated FlexLogic™ operand is asserted/de-asserted later, after validating the change.
The debounce algorithm is symmetrical: the same procedure and debounce time are used to filter the LOW-HIGH (marks
no.1, 2, 3, and 4 in the figure below) and HIGH-LOW (marks no. 5, 6, 7, and 8 below) transitions.
VOLTAGE
INPUT

USER-PROGRAMMABLE THRESHOLD

6
2 1 3 5
Time stamp of the first
TM
Time stamp of the first At this time, the The FlexLogic scan corresponding to the
scan corresponding to
the new validated state is
logged in the SOE record
new (HIGH)
contact state is
validated
operand is going to
be asserted at this
protection pass
new validated state is
logged in the SOE record
At this time, the new
(LOW) contact state is
validated
5
7
RAW CONTACT

The FlexLogicTM
operand is going to be
STATE

de-asserted at this
protection pass
DEBOUNCE TIME
(user setting)

4
The FlexLogicTM operand
DEBOUNCE TIME
The FlexLogicTM operand changes reflecting the
SCAN TIME (user setting)
changes reflecting the validated contact state
FLEXLOGICTM

(0.5 msec) validated contact state


OPERAND

PROTECTION PASS
(8 times a cycle controlled by the
frequency tracking mechanism)
842709A1.cdr

Figure 5–142: INPUT CONTACT DEBOUNCING MECHANISM AND TIME-STAMPING SAMPLE TIMING
Contact inputs are isolated in groups of four to allow connection of wet contacts from different voltage sources for each
group. The CONTACT INPUT THRESHOLDS determine the minimum voltage required to detect a closed contact input. This
value should be selected according to the following criteria: 17 for 24 V sources, 33 for 48 V sources, 84 for 110 to 125 V
sources and 166 for 250 V sources.
For example, to use contact input H5a as a status input from the breaker 52b contact to seal-in the trip relay and record it in
the Event Records menu, make the following settings changes:
CONTACT INPUT H5A ID: "Breaker Closed (52b)"
CONTACT INPUT H5A EVENTS: "Enabled"

Note that the 52b contact is closed when the breaker is open and open when the breaker is closed.

GE Multilin G60 Generator Protection System 5-247


5.8 INPUTS/OUTPUTS 5 SETTINGS

5.8.2 VIRTUAL INPUTS

PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ VIRTUAL INPUTS Ö VIRTUAL INPUT 1(64)

„ VIRTUAL INPUT 1 VIRTUAL INPUT 1 Range: Disabled, Enabled


„ FUNCTION: Disabled
VIRTUAL INPUT 1 ID: Range: Up to 12 alphanumeric characters
MESSAGE
Virt Ip 1
VIRTUAL INPUT 1 Range: Self-Reset, Latched
MESSAGE
TYPE: Latched
VIRTUAL INPUT 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

There are 64 virtual inputs that can be individually programmed to respond to input signals from the keypad (via the COM-
MANDS menu) and communications protocols. All virtual input operands are defaulted to “Off” (logic 0) unless the appropri-
ate input signal is received.
If the VIRTUAL INPUT x FUNCTION is to “Disabled”, the input will be forced to off (logic 0) regardless of any attempt to alter the
input. If set to “Enabled”, the input operates as shown on the logic diagram and generates output FlexLogic™ operands in
response to received input signals and the applied settings.
There are two types of operation: self-reset and latched. If VIRTUAL INPUT x TYPE is “Self-Reset”, when the input signal tran-
sits from off to on, the output operand will be set to on for only one evaluation of the FlexLogic™ equations and then return
to off. If set to “Latched”, the virtual input sets the state of the output operand to the same state as the most recent received
input.
5 The self-reset operating mode generates the output operand for a single evaluation of the FlexLogic™
equations. If the operand is to be used anywhere other than internally in a FlexLogic™ equation, it will
NOTE
likely have to be lengthened in time. A FlexLogic™ timer with a delayed reset can perform this function.

SETTING
VIRTUAL INPUT 1
FUNCTION:
Disabled=0
Enabled=1 S
AND
Latch
“Virtual Input 1 to ON = 1”
SETTING
“Virtual Input 1 to OFF = 0” R VIRTUAL INPUT 1 ID:
AND
SETTING (Flexlogic Operand)
OR
Virt Ip 1
VIRTUAL INPUT 1
TYPE:
Latched AND
Self - Reset 827080A2.CDR

Figure 5–143: VIRTUAL INPUTS SCHEME LOGIC

5-248 G60 Generator Protection System GE Multilin


5 SETTINGS 5.8 INPUTS/OUTPUTS

5.8.3 CONTACT OUTPUTS

a) DIGITAL OUTPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUTS Ö CONTACT OUTPUT H1

„ CONTACT OUTPUT H1 CONTACT OUTPUT H1 ID Range: Up to 12 alphanumeric characters


„ Cont Op 1
OUTPUT H1 OPERATE: Range: FlexLogic™ operand
MESSAGE
Off
OUTPUT H1 SEAL-IN: Range: FlexLogic™ operand
MESSAGE
Off
CONTACT OUTPUT H1 Range: Disabled, Enabled
MESSAGE
EVENTS: Enabled

Upon startup of the relay, the main processor will determine from an assessment of the modules installed in the chassis
which contact outputs are available and present the settings for only these outputs.
An ID may be assigned to each contact output. The signal that can OPERATE a contact output may be any FlexLogic™
operand (virtual output, element state, contact input, or virtual input). An additional FlexLogic™ operand may be used to
SEAL-IN the relay. Any change of state of a contact output can be logged as an Event if programmed to do so.

For example, the trip circuit current is monitored by providing a current threshold detector in series with some Form-A con-
tacts (see the trip circuit example in the Digital elements section). The monitor will set a flag (see the specifications for
Form-A). The name of the FlexLogic™ operand set by the monitor, consists of the output relay designation, followed by the
name of the flag; for example, CONT OP 1 ION.
In most breaker control circuits, the trip coil is connected in series with a breaker auxiliary contact used to interrupt current 5
flow after the breaker has tripped, to prevent damage to the less robust initiating contact. This can be done by monitoring
an auxiliary contact on the breaker which opens when the breaker has tripped, but this scheme is subject to incorrect oper-
ation caused by differences in timing between breaker auxiliary contact change-of-state and interruption of current in the
trip circuit. The most dependable protection of the initiating contact is provided by directly measuring current in the tripping
circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in.
This can be realized in the G60 using the CONT OP 1 ION FlexLogic™ operand to seal-in the contact output as follows:
CONTACT OUTPUT H1 ID: “Cont Op 1"
OUTPUT H1 OPERATE: any suitable FlexLogic™ operand
OUTPUT H1 SEAL-IN: “Cont Op 1 IOn”
CONTACT OUTPUT H1 EVENTS: “Enabled”

b) LATCHING OUTPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUTS Ö CONTACT OUTPUT H1a

„ CONTACT OUTPUT H1a OUTPUT H1a ID Range: Up to 12 alphanumeric characters


„ L-Cont Op 1
OUTPUT H1a OPERATE: Range: FlexLogic™ operand
MESSAGE
Off
OUTPUT H1a RESET: Range: FlexLogic™ operand
MESSAGE
Off
OUTPUT H1a TYPE: Range: Operate-dominant, Reset-dominant
MESSAGE
Operate-dominant
OUTPUT H1a EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

GE Multilin G60 Generator Protection System 5-249


5.8 INPUTS/OUTPUTS 5 SETTINGS

The G60 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such
they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop-
ulates the setting menu accordingly. On power up, the relay reads positions of the latching contacts from the hardware
before executing any other functions of the relay (such as protection and control features or FlexLogic™).
The latching output modules, either as a part of the relay or as individual modules, are shipped from the factory with all
latching contacts opened. It is highly recommended to double-check the programming and positions of the latching con-
tacts when replacing a module.
Since the relay asserts the output contact and reads back its position, it is possible to incorporate self-monitoring capabili-
ties for the latching outputs. If any latching outputs exhibits a discrepancy, the LATCHING OUTPUT ERROR self-test error is
declared. The error is signaled by the LATCHING OUT ERROR FlexLogic™ operand, event, and target message.
• OUTPUT H1a OPERATE: This setting specifies a FlexLogic™ operand to operate the ‘close coil’ of the contact. The
relay will seal-in this input to safely close the contact. Once the contact is closed and the RESET input is logic 0 (off),
any activity of the OPERATE input, such as subsequent chattering, will not have any effect. With both the OPERATE and
RESET inputs active (logic 1), the response of the latching contact is specified by the OUTPUT H1A TYPE setting.

• OUTPUT H1a RESET: This setting specifies a FlexLogic™ operand to operate the ‘trip coil’ of the contact. The relay
will seal-in this input to safely open the contact. Once the contact is opened and the OPERATE input is logic 0 (off), any
activity of the RESET input, such as subsequent chattering, will not have any effect. With both the OPERATE and RESET
inputs active (logic 1), the response of the latching contact is specified by the OUTPUT H1A TYPE setting.
• OUTPUT H1a TYPE: This setting specifies the contact response under conflicting control inputs; that is, when both the
OPERATE and RESET signals are applied. With both control inputs applied simultaneously, the contact will close if set to
“Operate-dominant” and will open if set to “Reset-dominant”.

Application Example 1:

5 A latching output contact H1a is to be controlled from two user-programmable pushbuttons (buttons number 1 and 2). The
following settings should be applied.
Program the Latching Outputs by making the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUT-
PUTS Ö CONTACT OUTPUT H1a menu (assuming an H4L module):

OUTPUT H1a OPERATE: “PUSHBUTTON 1 ON”


OUTPUT H1a RESET: “PUSHBUTTON 2 ON”

Program the pushbuttons by making the following changes in the PRODUCT SETUP ÖØ USER-PROGRAMMABLE PUSHBUT-
TONS ÖØ USER PUSHBUTTON 1 and USER PUSHBUTTON 2 menus:

PUSHBUTTON 1 FUNCTION: “Self-reset” PUSHBUTTON 2 FUNCTION: “Self-reset”


PUSHBTN 1 DROP-OUT TIME: “0.00 s” PUSHBTN 2 DROP-OUT TIME: “0.00 s”

Application Example 2:
A relay, having two latching contacts H1a and H1c, is to be programmed. The H1a contact is to be a Type-a contact, while
the H1c contact is to be a Type-b contact (Type-a means closed after exercising the operate input; Type-b means closed
after exercising the reset input). The relay is to be controlled from virtual outputs: VO1 to operate and VO2 to reset.
Program the Latching Outputs by making the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUT-
PUTS Ö CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):

OUTPUT H1a OPERATE: “VO1” OUTPUT H1c OPERATE: “VO2”


OUTPUT H1a RESET: “VO2” OUTPUT H1c RESET: “VO1”

Since the two physical contacts in this example are mechanically separated and have individual control inputs, they will not
operate at exactly the same time. A discrepancy in the range of a fraction of a maximum operating time may occur. There-
fore, a pair of contacts programmed to be a multi-contact relay will not guarantee any specific sequence of operation (such
as make before break). If required, the sequence of operation must be programmed explicitly by delaying some of the con-
trol inputs as shown in the next application example.

Application Example 3:
A make before break functionality must be added to the preceding example. An overlap of 20 ms is required to implement
this functionality as described below:

5-250 G60 Generator Protection System GE Multilin


5 SETTINGS 5.8 INPUTS/OUTPUTS

Write the following FlexLogic™ equation (EnerVista UR Setup example shown):

Both timers (Timer 1 and Timer 2) should be set to 20 ms pickup and 0 ms dropout.
Program the Latching Outputs by making the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUT-
PUTS Ö CONTACT OUTPUT H1a and CONTACT OUTPUT H1c menus (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1” OUTPUT H1c OPERATE: “VO2”
OUTPUT H1a RESET: “VO4” OUTPUT H1c RESET: “VO3”

Application Example 4:
A latching contact H1a is to be controlled from a single virtual output VO1. The contact should stay closed as long as VO1
is high, and should stay opened when VO1 is low. Program the relay as follows.
Write the following FlexLogic™ equation (EnerVista UR Setup example shown):
5

Program the Latching Outputs by making the following changes in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUT-
PUTS Ö CONTACT OUTPUT H1a menu (assuming an H4L module):
OUTPUT H1a OPERATE: “VO1”
OUTPUT H1a RESET: “VO2”

5.8.4 VIRTUAL OUTPUTS

PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ VIRTUAL OUTPUTS Ö VIRTUAL OUTPUT 1(96)

„ VIRTUAL OUTPUT 1 VIRTUAL OUTPUT 1 ID Range: Up to 12 alphanumeric characters


„ Virt Op 1
VIRTUAL OUTPUT 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

There are 96 virtual outputs that may be assigned via FlexLogic™. If not assigned, the output will be forced to ‘OFF’ (Logic
0). An ID may be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the
FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings
would be programmed as follows:

GE Multilin G60 Generator Protection System 5-251


5.8 INPUTS/OUTPUTS 5 SETTINGS

VIRTUAL OUTPUT 1 ID: "Trip"


VIRTUAL OUTPUT 1 EVENTS: "Disabled"

5.8.5 REMOTE DEVICES

a) REMOTE INPUTS/OUTPUTS OVERVIEW


Remote inputs and outputs provide a means of exchanging digital state information between Ethernet-networked devices.
The IEC 61850 GSSE (Generic Substation State Event) and GOOSE (Generic Object Oriented Substation Event) stan-
dards are used.
The IEC 61850 specification requires that communications between devices be implemented on Ethernet.
For UR-series relays, Ethernet communications is provided on all CPU modules except type 9E.
NOTE

The sharing of digital point state information between GSSE/GOOSE equipped relays is essentially an extension to Flex-
Logic™, allowing distributed FlexLogic™ by making operands available to/from devices on a common communications net-
work. In addition to digital point states, GSSE/GOOSE messages identify the originator of the message and provide other
information required by the communication specification. All devices listen to network messages and capture data only from
messages that have originated in selected devices.
IEC 61850 GSSE messages are compatible with UCA GOOSE messages and contain a fixed set of digital points. IEC
61850 GOOSE messages can, in general, contain any configurable data items. When used by the remote input/output fea-
ture, IEC 61850 GOOSE messages contain the same data as GSSE messages.
Both GSSE and GOOSE messages are designed to be short, reliable, and high priority. GOOSE messages have additional
advantages over GSSE messages due to their support of VLAN (virtual LAN) and Ethernet priority tagging functionality.
The GSSE message structure contains space for 128 bit pairs representing digital point state information. The IEC 61850
specification provides 32 “DNA” bit pairs that represent the state of two pre-defined events and 30 user-defined events. All
5 remaining bit pairs are “UserSt” bit pairs, which are status bits representing user-definable events. The G60 implementation
provides 32 of the 96 available UserSt bit pairs.
The IEC 61850 specification includes features that are used to cope with the loss of communication between transmitting
and receiving devices. Each transmitting device will send a GSSE/GOOSE message upon a successful power-up, when
the state of any included point changes, or after a specified interval (the default update time) if a change-of-state has not
occurred. The transmitting device also sends a ‘hold time’ which is set greater than three times the programmed default
time required by the receiving device.
Receiving devices are constantly monitoring the communications network for messages they require, as recognized by the
identification of the originating device carried in the message. Messages received from remote devices include the mes-
sage time allowed to live. The receiving relay sets a timer assigned to the originating device to this time interval, and if it
has not received another message from this device at time-out, the remote device is declared to be non-communicating, so
it will use the programmed default state for all points from that specific remote device. If a message is received from a
remote device before the time allowed to live expires, all points for that device are updated to the states contained in the
message and the hold timer is restarted. The status of a remote device, where “Offline” indicates non-communicating, can
be displayed.
The remote input/output facility provides for 32 remote inputs and 64 remote outputs.

b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES


In a G60 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each
GOOSE message is programmed in the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö
GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ FIXED GOOSE ÖØ GOOSE ID setting.

Likewise, the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE mes-
sage is programmed in the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE
CONFIGURATION Ö TRANSMISSION ÖØ GSSE ÖØ GSSE ID setting.

In G60 releases previous to 5.0x, these name strings were represented by the RELAY NAME setting.

5-252 G60 Generator Protection System GE Multilin


5 SETTINGS 5.8 INPUTS/OUTPUTS

c) REMOTE DEVICES: ID OF DEVICE FOR RECEIVING GSSE MESSAGES


PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ REMOTE DEVICES Ö REMOTE DEVICE 1(16)

„ REMOTE DEVICE 1 REMOTE DEVICE 1 ID: Range: up to 20 alphanumeric characters


„ Remote Device 1
REMOTE DEVICE 1 Range: 0 to 16383 in steps of 1
MESSAGE
ETYPE APPID: 0
REMOTE DEVICE 1 Range: Fixed, GOOSE 1 through GOOSE 16
MESSAGE
DATASET: Fixed

Remote devices are available for setting purposes. A receiving relay must be programmed to capture messages from only
those originating remote devices of interest. This setting is used to select specific remote devices by entering (bottom row)
the exact identification (ID) assigned to those devices.
The REMOTE DEVICE 1 ETYPE APPID setting is only used with GOOSE messages; they are not applicable to GSSE mes-
sages. This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre-
sponding settings on the sending device.
The REMOTE DEVICE 1 DATASET setting provides for the choice of the G60 fixed (DNA/UserSt) dataset (that is, containing
DNA and UserSt bit pairs), or one of the configurable datasets.
Note that the dataset for the received data items must be made up of existing items in an existing logical node. For this rea-
son, logical node GGIO3 is instantiated to hold the incoming data items. GGIO3 is not necessary to make use of the
received data. The remote input data item mapping takes care of the mapping of the inputs to remote input FlexLogic™
operands. However, GGIO3 data can be read by IEC 61850 clients.

5.8.6 REMOTE INPUTS 5


PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ REMOTE INPUTS Ö REMOTE INPUT 1(32)

„ REMOTE INPUT 1 REMOTE INPUT 1 ID: Range: up to 12 alphanumeric characters


„ Remote Ip 1
REMOTE IN 1 DEVICE: Range: Remote Device 1 to Remote device 16
MESSAGE
Remote Device 1
REMOTE IN 1 ITEM: Range: None, DNA-1 to DNA-32, UserSt-1 to UserSt-32,
MESSAGE Config Item 1 to Config Item 32
None
REMOTE IN 1 DEFAULT Range: On, Off, Latest/On, Latest/Off
MESSAGE
STATE: Off
REMOTE IN 1 Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

Remote Inputs that create FlexLogic™ operands at the receiving relay are extracted from GSSE/GOOSE messages origi-
nating in remote devices. Each remote input can be selected from a list consisting of: DNA-1 through DNA-32, UserSt-1
through UserSt-32, and Dataset Item 1 through Dataset Item 32. The function of DNA inputs is defined in the IEC 61850
specification and is presented in the IEC 61850 DNA Assignments table in the Remote outputs section. The function of
UserSt inputs is defined by the user selection of the FlexLogic™ operand whose state is represented in the GSSE/GOOSE
message. A user must program a DNA point from the appropriate FlexLogic™ operand.
Remote input 1 must be programmed to replicate the logic state of a specific signal from a specific remote device for local
use. This programming is performed via the three settings shown above.
The REMOTE INPUT 1 ID setting allows the user to assign descriptive text to the remote input. The REMOTE IN 1 DEVICE setting
selects the remote device which originates the required signal, as previously assigned to the remote device via the setting
REMOTE DEVICE (16) ID (see the Remote devices section). The REMOTE IN 1 ITEM setting selects the specific bits of the
GSSE/GOOSE message required.
The REMOTE IN 1 DEFAULT STATE setting selects the logic state for this point if the local relay has just completed startup or
the remote device sending the point is declared to be non-communicating. The following choices are available:

GE Multilin G60 Generator Protection System 5-253


5.8 INPUTS/OUTPUTS 5 SETTINGS

• Setting REMOTE IN 1 DEFAULT STATE to “On” value defaults the input to logic 1.
• Setting REMOTE IN 1 DEFAULT STATE to “Off” value defaults the input to logic 0.
• Setting REMOTE IN 1 DEFAULT STATE to “Latest/On” freezes the input in case of lost communications. If the latest state is
not known, such as after relay power-up but before the first communication exchange, the input will default to logic 1.
When communication resumes, the input becomes fully operational.
• Setting REMOTE IN 1 DEFAULT STATE to “Latest/Off” freezes the input in case of lost communications. If the latest state is
not known, such as after relay power-up but before the first communication exchange, the input will default to logic 0.
When communication resumes, the input becomes fully operational.
For additional information on GSSE/GOOOSE messaging, refer to the Remote devices section in this chap-
ter.
NOTE

5.8.7 REMOTE DOUBLE-POINT STATUS INPUTS

PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ REMOTE DPS INPUTS Ö REMOTE DPS INPUT 1(5)

„ REMOTE DPS INPUT 1 REM DPS IN 1 ID: Range: up to 12 alphanumeric characters


„ RemDPS Ip 1
REM DPS IN 1 DEV: Range: Remote Device 1 to Remote device 16
MESSAGE
Remote Device 1
REM DPS IN 1 ITEM: Range: None, Dataset Item 1 to Dataset Item 32
MESSAGE
None

5 MESSAGE
REM DPS IN 1
EVENTS: Disabled
Range: Enabled, Disabled

Remote double-point status inputs are extracted from GOOSE messages originating in the remote device. Each remote
double point status input must be programmed to replicate the logic state of a specific signal from a specific remote device
for local use. This functionality is accomplished with the five remote double-point status input settings.
• REM DPS IN 1 ID: This setting assigns descriptive text to the remote double-point status input.
• REM DPS IN 1 DEV: This setting selects a remote device ID to indicate the origin of a GOOSE message. The range is
selected from the remote device IDs specified in the Remote devices section.
• REM DPS IN 1 ITEM: This setting specifies the required bits of the GOOSE message.
The configurable GOOSE dataset items must be changed to accept a double-point status item from a GOOSE dataset
(changes are made in the SETTINGS ÖØ COMMUNICATION ÖØ IEC 61850 PROTOCOL ÖØ GSSE/GOOSE CONFIGURATION ÖØ
RECEPTION ÖØ CONFIGURABLE GOOSE Ö CONFIGIGURABLE GOOSE 1(16) Ö CONFIG GSE 1 DATASET ITEMS menus). Dataset
items configured to receive any of “GGIO3.ST.IndPos1.stV” to “GGIO3.ST.IndPos5.stV” will accept double-point status
information that will be decoded by the remote double-point status inputs configured to this dataset item.
The remote double point status is recovered from the received IEC 61850 dataset and is available as through the RemDPS
Ip 1 BAD, RemDPS Ip 1 INTERM, RemDPS Ip 1 OFF, and RemDPS Ip 1 ON FlexLogic™ operands. These operands can then be
used in breaker or disconnect control schemes.

5.8.8 REMOTE OUTPUTS

a) DNA BIT PAIRS


PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ REMOTE OUTPUTS DNA BIT PAIRS Ö REMOTE OUPUTS DNA- 1(32) BIT PAIR

„ REMOTE OUTPUTS DNA- 1 OPERAND: Range: FlexLogic™ operand


„ DNA- 1 BIT PAIR Off
DNA- 1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

5-254 G60 Generator Protection System GE Multilin


5 SETTINGS 5.8 INPUTS/OUTPUTS

Remote outputs (1 to 32) are FlexLogic™ operands inserted into GSSE/GOOSE messages that are transmitted to remote
devices on a LAN. Each digital point in the message must be programmed to carry the state of a specific FlexLogic™ oper-
and. The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted.

Table 5–27: IEC 61850 DNA ASSIGNMENTS


DNA IEC 61850 DEFINITION FLEXLOGIC™ OPERAND
1 Test IEC 61850 TEST MODE
2 ConfRev IEC 61850 CONF REV

b) USERST BIT PAIRS


PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ REMOTE OUTPUTS UserSt BIT PAIRS Ö REMOTE OUTPUTS UserSt- 1(32) BIT PAIR

„ REMOTE OUTPUTS UserSt- 1 OPERAND: Range: FlexLogic™ operand


„ UserSt- 1 BIT PAIR Off
UserSt- 1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote devices. Each digital point in the
message must be programmed to carry the state of a specific FlexLogic™ operand. The setting above is used to select the
operand which represents a specific UserSt function (as selected by the user) to be transmitted.
The following setting represents the time between sending GSSE/GOOSE messages when there has been no change of
state of any selected digital point. This setting is located in the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ IEC 61850 PROTO-
COL ÖØ GSSE/GOOSE CONFIGURATION settings menu.

DEFAULT GSSE/GOOSE Range: 1 to 60 s in steps of 1 5


UPDATE TIME: 60 s

For more information on GSSE/GOOSE messaging, refer to Remote Inputs/Outputs Overview in the
Remote Devices section.
NOTE

5.8.9 RESETTING

PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ RESETTING

„ RESETTING RESET OPERAND: Range: FlexLogic™ operand


„ Off

Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition
has cleared until a RESET command is received to return these latches (not including FlexLogic™ latches) to the reset
state. The RESET command can be sent from the faceplate Reset button, a remote device via a communications channel,
or any programmed operand.
When the RESET command is received by the relay, two FlexLogic™ operands are created. These operands, which are
stored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each cre-
ate the RESET OP FlexLogic™ operand. Each individual source of a RESET command also creates its individual operand
RESET OP (PUSHBUTTON), RESET OP (COMMS) or RESET OP (OPERAND) to identify the source of the command. The setting
shown above selects the operand that will create the RESET OP (OPERAND) operand.

GE Multilin G60 Generator Protection System 5-255


5.8 INPUTS/OUTPUTS 5 SETTINGS

5.8.10 DIRECT INPUTS AND OUTPUTS

a) DIRECT INPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ DIRECT INPUTS Ö DIRECT INPUT 1(32)

„ DIRECT INPUT 1 DIRECT INPUT 1 Range: up to 12 alphanumeric characters


„ NAME: Dir Ip 1
DIRECT INPUT 1 Range: 1 to 16
MESSAGE
DEVICE ID: 1
DIRECT INPUT 1 Range: 1 to 32
MESSAGE
BIT NUMBER: 1
DIRECT INPUT 1 Range: On, Off, Latest/On, Latest/Off
MESSAGE
DEFAULT STATE: Off
DIRECT INPUT 1 Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled

These settings specify how the direct input information is processed. The DIRECT INPUT 1 NAME setting allows the user to
assign a descriptive name to the direct input. The DIRECT INPUT 1 DEVICE ID represents the source of direct input 1. The
specified direct input is driven by the device identified here.
The DIRECT INPUT 1 BIT NUMBER is the bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
identified as DIRECT INPUT 1 BIT NUMBER. This corresponds to the direct output number of the sending device.
The DIRECT INPUT 1 DEFAULT STATE represents the state of the direct input when the associated direct device is offline. The
following choices are available:
5 • Setting DIRECT INPUT 1 DEFAULT STATE to “On” value defaults the input to Logic 1.
• Setting DIRECT INPUT 1 DEFAULT STATE to “Off” value defaults the input to Logic 0.
• Setting DIRECT INPUT 1 DEFAULT STATE to “Latest/On” freezes the input in case of lost communications. If the latest
state is not known, such as after relay power-up but before the first communication exchange, the input will default to
Logic 1. When communication resumes, the input becomes fully operational.
• Setting DIRECT INPUT 1 DEFAULT STATE to “Latest/Off” freezes the input in case of lost communications. If the latest
state is not known, such as after relay power-up but before the first communication exchange, the input will default to
Logic 0. When communication resumes, the input becomes fully operational.

b) DIRECT OUTPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ DIRECT OUTPUTS Ö DIRECT OUTPUT 1(32)

„ DIRECT OUTPUT 1 DIRECT OUT 1 NAME: Range: up to 12 alphanumeric characters


„ Dir Out 1
DIRECT OUT 1 OPERAND: Range: FlexLogic™ operand
MESSAGE
Off
DIRECT OUTPUT 1 Range: Enabled, Disabled
MESSAGE
EVENTS: Disabled

The DIRECT OUT 1 NAME setting allows the user to assign a descriptive name to the direct output. The DIR OUT 1 OPERAND is
the FlexLogic™ operand that determines the state of this direct output.

c) APPLICATION EXAMPLES
The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued
below to illustrate usage of the direct inputs and outputs.

5-256 G60 Generator Protection System GE Multilin


5 SETTINGS 5.8 INPUTS/OUTPUTS

EXAMPLE 1: EXTENDING INPUT/OUTPUT CAPABILITIES OF A G60 RELAY


Consider an application that requires additional quantities of digital inputs or output contacts or lines of programmable logic
that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such
as the C30, to satisfy the additional inputs/outputs and programmable logic requirements. The two IEDs are connected via
single-channel digital communication cards as shown below.

TX1
UR IED 1
RX1

TX1
UR IED 2
RX1

Figure 5–144: INPUT AND OUTPUT EXTENSION VIA DIRECT INPUTS AND OUTPUTS
Assume contact input 1 from UR IED 2 is to be used by UR IED 1. The following settings should be applied (Direct Input 5
and bit number 12 are used, as an example):
UR IED 1: DIRECT INPUT 5 DEVICE ID = “2” UR IED 2: DIRECT OUT 12 OPERAND = “Cont Ip 1 On”
DIRECT INPUT 5 BIT NUMBER = “12”

The Cont Ip 1 On operand of UR IED 2 is now available in UR IED 1 as DIRECT INPUT 5 ON.
EXAMPLE 2: INTERLOCKING BUSBAR PROTECTION
A simple interlocking busbar protection scheme can be accomplished by sending a blocking signal from downstream
devices, say 2, 3 and 4, to the upstream device that monitors a single incomer of the busbar, as shown in the figure below.
5

UR IED 1 BLOCK

UR IED 2 UR IED 3 UR IED 4

842712A1.CDR

Figure 5–145: SAMPLE INTERLOCKING BUSBAR PROTECTION SCHEME


Assume that Phase Instantaneous Overcurrent 1 is used by Devices 2, 3, and 4 to block Device 1. If not blocked, Device 1
would trip the bus upon detecting a fault and applying a short coordination time delay.
The following settings should be applied (assume Bit 3 is used by all 3 devices to sent the blocking signal and Direct Inputs
7, 8, and 9 are used by the receiving device to monitor the three blocking signals):
UR IED 2: DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"

UR IED 3: DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"

UR IED 4: DIRECT OUT 3 OPERAND: "PHASE IOC1 OP"

UR IED 1: DIRECT INPUT 7 DEVICE ID: "2"


DIRECT INPUT 7 BIT NUMBER: "3"
DIRECT INPUT 7 DEFAULT STATE: select "On" for security, select "Off" for dependability

DIRECT INPUT 8 DEVICE ID: "3"


DIRECT INPUT 8 BIT NUMBER: "3"
DIRECT INPUT 8 DEFAULT STATE: select "On" for security, select "Off" for dependability

GE Multilin G60 Generator Protection System 5-257


5.8 INPUTS/OUTPUTS 5 SETTINGS

DIRECT INPUT 9 DEVICE ID: "4"


DIRECT INPUT 9 BIT NUMBER: "3"
DIRECT INPUT 9 DEFAULT STATE: select "On" for security, select "Off" for dependability
Now the three blocking signals are available in UR IED 1 as DIRECT INPUT 7 ON, DIRECT INPUT 8 ON, and DIRECT INPUT 9
ON. Upon losing communications or a device, the scheme is inclined to block (if any default state is set to “On”), or to trip
the bus on any overcurrent condition (all default states set to “Off”).
EXAMPLE 2: PILOT-AIDED SCHEMES
Consider a three-terminal line protection application shown in the figure below.

UR IED 1 UR IED 2

UR IED 3
842713A1.CDR

Figure 5–146: THREE-TERMINAL LINE APPLICATION


Assume the Hybrid Permissive Overreaching Transfer Trip (Hybrid POTT) scheme is applied using the architecture shown
below. The scheme output operand HYB POTT TX1 is used to key the permission.
5
TX1 RX1 RX2
UR IED 1 UR IED 2
RX1 TX1 TX2

RX1
UR IED 3
TX1
842714A1.CDR

Figure 5–147: SINGLE-CHANNEL OPEN-LOOP CONFIGURATION


In the above architecture, Devices 1 and 3 do not communicate directly. Therefore, Device 2 must act as a ‘bridge’. The fol-
lowing settings should be applied:
UR IED 1: DIRECT OUT 2 OPERAND: "HYB POTT TX1"
DIRECT INPUT 5 DEVICE ID: "2"
DIRECT INPUT 5 BIT NUMBER: "2" (this is a message from IED 2)
DIRECT INPUT 6 DEVICE ID: "2"
DIRECT INPUT 6 BIT NUMBER: "4" (effectively, this is a message from IED 3)
UR IED 3: DIRECT OUT 2 OPERAND: "HYB POTT TX1"
DIRECT INPUT 5 DEVICE ID: "2"
DIRECT INPUT 5 BIT NUMBER: "2" (this is a message from IED 2)
DIRECT INPUT 6 DEVICE ID: "2"
DIRECT INPUT 6 BIT NUMBER: "3" (effectively, this is a message from IED 1)
UR IED 2: DIRECT INPUT 5 DEVICE ID: "1"
DIRECT INPUT 5 BIT NUMBER: "2"
DIRECT INPUT 6 DEVICE ID: "3"
DIRECT INPUT 6 BIT NUMBER: "2"

5-258 G60 Generator Protection System GE Multilin


5 SETTINGS 5.8 INPUTS/OUTPUTS

DIRECT OUT 2 OPERAND: "HYB POTT TX1"


DIRECT OUT 3 OPERAND: "DIRECT INPUT 5" (forward a message from 1 to 3)
DIRECT OUT 4 OPERAND: "DIRECT INPUT 6" (forward a message from 3 to 1)
Signal flow between the three IEDs is shown in the figure below:

UR IED 1 UR IED 2
DIRECT OUT 2 = HYB POTT TX1 DIRECT INPUT 5
DIRECT INPUT 5 DIRECT OUT 2 = HYB POTT TX1
DIRECT INPUT 6 DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 6

UR IED 3 DIRECT INPUT 5


DIRECT INPUT 6
DIRECT OUT 2 = HYB POTT TX1

842717A1.CDR

Figure 5–148: SIGNAL FLOW FOR DIRECT INPUT AND OUTPUT – EXAMPLE 3
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 should be ANDed in FlexLogic™ and the resulting operand configured as the permission to trip (HYB POTT
RX1 setting).

5.8.11 TELEPROTECTION INPUTS AND OUTPUTS

a) OVERVIEW
5
The relay provides sixteen teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and sixteen
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only, num-
bered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by assigning
FlexLogic™ operands to be sent via the selected communications channel. This allows the user to create distributed pro-
tection and control schemes via dedicated communications channels. Some examples are directional comparison pilot
schemes and direct transfer tripping. It should be noted that failures of communications channels will affect teleprotection
functionality. The teleprotection function must be enabled to utilize the inputs.

b) TELEPROTECTION INPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ TELEPROTECTION Ö TELEPROT INPUTS

„ TELEPROT INPUTS TELEPROT INPUT 1-1 Range: Off, On, Latest/Off, Latest/On
„ DEFAULT: Off
TELEPROT INPUT 1-2 Range: Off, On, Latest/Off, Latest/On
MESSAGE
DEFAULT: Off

TELEPROT INPUT 1-16 Range: Off, On, Latest/Off, Latest/On


MESSAGE
DEFAULT: Off
TELEPROT INPUT 2-1 Range: Off, On, Latest/Off, Latest/On
MESSAGE
DEFAULT: Off
TELEPROT INPUT 2-2 Range: Off, On, Latest/Off, Latest/On
MESSAGE
DEFAULT: Off

TELEPROT INPUT 2-16 Range: Off, On, Latest/Off, Latest/On


MESSAGE
DEFAULT: Off

GE Multilin G60 Generator Protection System 5-259


5.8 INPUTS/OUTPUTS 5 SETTINGS

Setting the TELEPROT INPUT ~~ DEFAULT setting to “On” defaults the input to logic 1 when the channel fails. A value of “Off”
defaults the input to logic 0 when the channel fails.
The “Latest/On” and “Latest/Off” values freeze the input in case of lost communications. If the latest state is not known,
such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for “Latest/On”
and logic 0 for “Latest/Off”.

c) TELEPROTECTION OUTPUTS
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ TELEPROTECTION ÖØ TELEPROT OUTPUTS

„ TELEPROT OUTPUTS TELEPROT OUTPUT 1-1: Range: FlexLogic™ operand


„ Off
TELEPROT OUTPUT 1-2: Range: FlexLogic™ operand
MESSAGE
Off

TELEPROT OUTPUT 1-16: Range: FlexLogic™ operand


MESSAGE
Off
TELEPROT OUTPUT 2-1: Range: FlexLogic™ operand
MESSAGE
Off
TELEPROT OUTPUT 2-2: Range: FlexLogic™ operand
MESSAGE
Off

5 MESSAGE
TELEPROT OUTPUT 2-16:
Off
Range: FlexLogic™ operand

As the following figure demonstrates, processing of the teleprotection inputs/outputs is dependent on the number of com-
munication channels and terminals. On two-terminal two-channel systems, they are processed continuously on each chan-
nel and mapped separately per channel. Therefore, to achieve redundancy, the user must assign the same operand on
both channels (teleprotection outputs at the sending end or corresponding teleprotection inputs at the receiving end). On
three-terminal two-channel systems, redundancy is achieved by programming signal re-transmittal in the case of channel
failure between any pair of relays.

5-260 G60 Generator Protection System GE Multilin


5 SETTINGS 5.8 INPUTS/OUTPUTS

UR-1 UR-2
ACTUAL VALUES SETTING
CHANNEL 1 STATUS: TELEPROT INPUT 1-1
DEFAULT:
SETTING (same for 1-2...1-16)
TELEPROT OUTPUT 1-1:
(same for 1-2...1-16) On FLEXLOGIC OPERAND
Fail
Off (Flexlogic Operand) Off TELEPRO INPUT 1-1 On
OK OR
(same for 1-2...1-16)

SETTING ACTUAL VALUES


TELEPROT INPUT 1-1 CHANNEL 1 STATUS:
DEFAULT:
Communication channel #1
(same for 1-2...1-16) (Teleprotection I/O Enabled) SETTING
FLEXLOGIC OPERAND TELEPROT OUTPUT 1-1:
On (same for 1-2...1-16)
TELEPRO INPUT 1-1 On Fail
Off
(same for 1-2...1-16) OR OK Off (Flexlogic Operand)

UR-2 or UR-3
ACTUAL VALUES SETTING
CHANNEL 2 STATUS: TELEPROT INPUT 2-1
DEFAULT:
SETTING (same for 2-2...2-16)
TELEPROT OUTPUT 2-1:
(same for 1-2...1-16) On FLEXLOGIC OPERAND
Fail
Off TELEPRO INPUT 2-1 On
Off (Flexlogic Operand) OK OR
(same for 2-2...2-16)

SETTING ACTUAL VALUES


CHANNEL 2 STATUS:
TELEPROT INPUT 2-1 Communication channel #2
DEFAULT:
(same for 1-2...1-16) (On 3-terminal system or 2-terminal SETTING
FLEXLOGIC OPERAND
with redundant channel)
TELEPROT OUTPUT 2-1:
On (same for 2-2...2-16)
TELEPRO INPUT 2-1 On Fail
Off
(same for 1-2...1-16) OR OK Off (Flexlogic Operand)

842750A2.CDR

Figure 5–149: TELEPROTECTION INPUT/OUTPUT PROCESSING

5.8.12 IEC 61850 GOOSE ANALOGS


5
PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ IEC 61850 GOOSE ANALOGS ÖØ GOOSE ANALOG INPUT 1(32)

„ GOOSE ANALOG ANALOG 1 DEFAULT: Range: –1000000.000 to 1000000.000 in steps of 0.001


„ INPUT 1 1000.000
ANALOG 1 DEFAULT Range: Default Value, Last Known
MESSAGE
MODE: Default Value
GOOSE ANALOG 1 Range: up to 4 alphanumeric characters
MESSAGE
UNITS:
GOOSE ANALOG 1 PU: Range: 0.000 to 1000000000.000 in steps of 0.001
MESSAGE
1.000

The IEC 61850 GOOSE analog inputs feature allows the transmission of analog values between any two UR-series
devices. The following settings are available for each GOOSE analog input.
• ANALOG 1 DEFAULT: This setting specifies the value of the GOOSE analog input when the sending device is offline
and the ANALOG 1 DEFAULT MODE is set to “Default Value”.This setting is stored as an IEEE 754 / IEC 60559 floating
point number. Because of the large range of this setting, not all possible values can be stored. Some values may be
rounded to the closest possible floating point number.
• ANALOG 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE analog input remains at the last received value. When the sending device is offline and this setting value is
“Default Value”, then the value of the GOOSE analog input is defined by the ANALOG 1 DEFAULT setting.
• GOOSE ANALOG 1 UNITS: This setting specifies a four-character alphanumeric string that can is used in the actual
values display of the corresponding GOOSE analog input value.
• GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna-
log™ values in other G60 features, such as FlexElements™. The base factor is applied to the GOOSE analog input
FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.

GE Multilin G60 Generator Protection System 5-261


5.8 INPUTS/OUTPUTS 5 SETTINGS

Table 5–28: GOOSE ANALOG INPUT BASE UNITS


ELEMENT BASE UNITS
dcmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
FREQUENCY fBASE = 1 Hz
FREQUENCY RATE OF CHANGE df/dtBASE = 1 Hz/s
PHASE ANGLE ϕBASE = 360 degrees (see the UR angle referencing convention)
POWER FACTOR PFBASE = 1.00
RTDs BASE = 100°C
SENSITIVE DIR POWER PBASE = maximum value of 3 × VBASE × IBASE for the +IN and –IN inputs of the sources
(Sns Dir Power) configured for the sensitive power directional element(s).
SOURCE CURRENT IBASE = maximum nominal primary RMS value of the +IN and –IN inputs
SOURCE ENERGY EBASE = 10000 MWh or MVAh, respectively
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER PBASE = maximum value of VBASE × IBASE for the +IN and –IN inputs
SOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputs
STATOR DIFFERENTIAL IBASE = maximum primary RMS value of the +IN and –IN inputs
CURRENT (CT primary for source currents, and bus reference primary current for bus differential currents)
(Stator Diff Iar, Ibr, and Icr)
STATOR GROUND 3RD VBASE = Primary auxiliary voltage of the STATOR GROUND SOURCE
HARMONIC VOLTAGES
(Stator Gnd Vn/V0 3rd)

5 STATOR RESTRAINING
CURRENT
IBASE = maximum primary RMS value of the +IN and –IN inputs
(CT primary for source currents, and bus reference primary current for bus differential currents)
(Stator Diff Iad, Ibd, and Icd)
SYNCHROCHECK VBASE = maximum primary RMS value of all the sources related to the +IN and –IN inputs
(Max Delta Volts)
VOLTS PER HERTZ BASE = 1.00 pu

The GOOSE analog input FlexAnalog™ values are available for use in other G60 functions that use FlexAnalog™ values.

5.8.13 IEC 61850 GOOSE INTEGERS

PATH: SETTINGS ÖØ INPUTS/OUTPUTS ÖØ IEC 61850 GOOSE UINTEGERS ÖØ GOOSE UINTEGER INPUT 1(16)

„ GOOSE UINTEGER UINTEGER 1 DEFAULT: Range: 0 to 429496295 in steps of 1


„ INPUT 1 1000
UINTEGER 1 DEFAULT Range: Default Value, Last Known
MESSAGE
MODE: Default Value

The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger™ values between any two UR-
series devices. The following settings are available for each GOOSE uinteger input.
• UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device is
offline and the UINTEGER 1 DEFAULT MODE is set to “Default Value”.This setting is stored as a 32-bit unsigned integer
number.
• UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is
“Default Value”, then the value of the GOOSE uinteger input is defined by the UINTEGER 1 DEFAULT setting.
The GOOSE integer input FlexInteger™ values are available for use in other G60 functions that use FlexInteger™ values.

5-262 G60 Generator Protection System GE Multilin


5 SETTINGS 5.9 TRANSDUCER INPUTS AND OUTPUTS

5.9TRANSDUCER INPUTS AND OUTPUTS 5.9.1 DCMA INPUTS

PATH: SETTINGS ÖØ TRANSDUCER I/O ÖØ DCMA INPUTS Ö DCMA INPUT H1(W8)

„ DCMA INPUT H1 DCMA INPUT H1 Range: Disabled, Enabled


„ FUNCTION: Disabled
DCMA INPUT H1 ID: Range: up to 20 alphanumeric characters
MESSAGE
DCMA Ip 1
DCMA INPUT H1 Range: 6 alphanumeric characters
MESSAGE
UNITS: μA
DCMA INPUT H1 Range: 0 to –1 mA, 0 to +1 mA, –1 to +1 mA, 0 to 5 mA,
MESSAGE 0 to 10mA, 0 to 20 mA, 4 to 20 mA
RANGE: 0 to -1 mA
DCMA INPUT H1 MIN Range: –9999.999 to +9999.999 in steps of 0.001
MESSAGE
VALUE: 0.000
DCMA INPUT H1 MAX Range: –9999.999 to +9999.999 in steps of 0.001
MESSAGE
VALUE: 0.000

Hardware and software is provided to receive signals from external transducers and convert these signals into a digital for-
mat for use as required. The relay will accept inputs in the range of –1 to +20 mA DC, suitable for use with most common
transducer output ranges; all inputs are assumed to be linear over the complete range. Specific hardware details are con-
tained in chapter 3.
Before the dcmA input signal can be used, the value of the signal measured by the relay must be converted to the range
and quantity of the external transducer primary input parameter, such as DC voltage or temperature. The relay simplifies
this process by internally scaling the output from the external transducer and displaying the actual primary parameter.
5
dcmA input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels
with the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay will automatically generate configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclu-
sive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel of
a type 5F transducer module installed in slot H.
The function of the channel may be either “Enabled” or “Disabled”. If “Disabled”, no actual values are created for the chan-
nel. An alphanumeric “ID” is assigned to each channel; this ID will be included in the channel actual value, along with the
programmed units associated with the parameter measured by the transducer, such as volts, °C, megawatts, etc. This ID is
also used to reference the channel as the input parameter to features designed to measure this type of parameter. The
DCMA INPUT H1 RANGE setting specifies the mA DC range of the transducer connected to the input channel.

The DCMA INPUT H1 MIN VALUE and DCMA INPUT H1 MAX VALUE settings are used to program the span of the transducer in
primary units. For example, a temperature transducer might have a span from 0 to 250°C; in this case the DCMA INPUT H1
MIN VALUE value is “0” and the DCMA INPUT H1 MAX VALUE value is “250”. Another example would be a watts transducer with
a span from –20 to +180 MW; in this case the DCMA INPUT H1 MIN VALUE value would be “–20” and the DCMA INPUT H1 MAX
VALUE value “180”. Intermediate values between the min and max values are scaled linearly.

GE Multilin G60 Generator Protection System 5-263


5.9 TRANSDUCER INPUTS AND OUTPUTS 5 SETTINGS

5.9.2 RTD INPUTS

PATH: SETTINGS ÖØ TRANSDUCER I/O ÖØ RTD INPUTS Ö RTD INPUT H1(W8)

„ RTD INPUT H1 RTD INPUT H1 Range: Disabled, Enabled


„ FUNCTION: Disabled
RTD INPUT H1 ID: Range: Up to 20 alphanumeric characters
MESSAGE
RTD Ip 1
RTD INPUT H1 TYPE: Range: 100Ω Nickel, 10Ω Copper, 100Ω Platinum,
MESSAGE
100Ω Nickel 120Ω Nickel

RTD INPUT H1 Range: None, Stator, Bearing, Ambient, Group 1,


MESSAGE Group 2
APPLICATION: Bearing
RTD INPUT H1 ALARM Range: 1 to 249°C in steps of 1
MESSAGE
TEMPERATURE: 130°C
RTD INPUT H1 ALARM Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PKP DELAY: 0.00 s
RTD INPUT H1 TRIP Range: 1 to 249°C in steps of 1
MESSAGE
TEMPERATURE: 130°C
RTD INPUT H1 TRIP Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PKP DELAY: 0.00 s
RTD INPUT H1 TRIP Range: 0.00 to 600.00 s in steps of 0.01

5 MESSAGE
RST DELAY: 0.00 s
RTD INPUT H1 TRIP Range: None, Group, RTD Inp H1, RTD Inp H2,...,
MESSAGE RTD Inp W8
VOTING: None
RTD INPUT H1 OPEN: Range: None, Alarm, Block
MESSAGE
None
RTD INPUT H1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
RTD INPUT H1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
RTD INPUT H1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

The RTD inputs convert values of input resistance into temperature for further operations. These channels are intended to
be connected to any of the RTD types in common use. Specific hardware details are contained in chapter 3.
RTD input channels are arranged in a manner similar to CT and VT channels. The user configures individual channels with
the settings shown here.
The channels are arranged in sub-modules of two channels, numbered from 1 through 8 from top to bottom. On power-up,
the relay will automatically generate configuration settings for every channel, based on the order code, in the same general
manner that is used for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclu-
sive, which is used as the channel number. The relay generates an actual value for each available input channel.
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel of
a type 5C transducer module installed in the first available slot.
• RTD INPUT H1 FUNCTION: The function of the channel may be either “Enabled” or “Disabled”. If set to “Disabled”,
there will not be an actual value created for the channel.
• RTD INPUT H1 ID: An alphanumeric ID is assigned to the channel. This ID will be included in the channel actual val-
ues. It is also used to reference the channel as the input parameter to features designed to measure this type of
parameter.

5-264 G60 Generator Protection System GE Multilin


5 SETTINGS 5.9 TRANSDUCER INPUTS AND OUTPUTS

• RTD INPUT H1 TYPE: This setting specifies the RTD type. Four different RTD types are available: 100 Ω Nickel, 10 Ω
Copper, 100 Ω Platinum, and 120 Ω Nickel. Refer the table below for reference temperature values for each type.

Table 5–29: RTD TEMPERATURE VS. RESISTANCE


TEMPERATURE RESISTANCE (IN OHMS)
°C °F 100 OHM PT 120 OHM NI 100 OHM NI 10 OHM CU
(DIN 43760)
–50 –58 80.31 86.17 71.81 7.10
–40 –40 84.27 92.76 77.30 7.49
–30 –22 88.22 99.41 82.84 7.88
–20 –4 92.16 106.15 88.45 8.26
–10 14 96.09 113.00 94.17 8.65
0 32 100.00 120.00 100.00 9.04
10 50 103.90 127.17 105.97 9.42
20 68 107.79 134.52 112.10 9.81
30 86 111.67 142.06 118.38 10.19
40 104 115.54 149.79 124.82 10.58
50 122 119.39 157.74 131.45 10.97
60 140 123.24 165.90 138.25 11.35
70 158 127.07 174.25 145.20 11.74
80 176 130.89 182.84 152.37 12.12
90 194 134.70 191.64 159.70 12.51
100 212 138.50 200.64 167.20 12.90 5
110 230 142.29 209.85 174.87 13.28
120 248 146.06 219.29 182.75 13.67
130 266 149.82 228.96 190.80 14.06
140 284 153.58 238.85 199.04 14.44
150 302 157.32 248.95 207.45 14.83
160 320 161.04 259.30 216.08 15.22
170 338 164.76 269.91 224.92 15.61
180 356 168.47 280.77 233.97 16.00
190 374 172.46 291.96 243.30 16.39
200 392 175.84 303.46 252.88 16.78
210 410 179.51 315.31 262.76 17.17
220 428 183.17 327.54 272.94 17.56
230 446 186.82 340.14 283.45 17.95
240 464 190.45 353.14 294.28 18.34
250 482 194.08 366.53 305.44 18.73

• RTD INPUT H1 APPLICATION: This setting allows each individual RTD to be assigned to a group application. This is
useful for applications that require group measurement for voting. A value of “None” specifies that the RTD will operate
individually and not part of any RTD group. All RTDs programmed to “Stator” are used for RTD biasing of the G60 ther-
mal model. Common groups are provided for rotating machines applications such as ambient, bearing, group 1, or
group 2. If the RTD INPUT H1 TRIP VOTING setting value is “Group”, then it is allowed to issue a trip if N – 1 RTDs from the
same group also pick up, where N is the number of enabled RTDs from the group.
• RTD INPUT H1 ALARM TEMPERATURE: This setting specifies the temperature pickup level for the alarm stage.
• RTD INPUT H1 ALARM PKP DELAY: This setting specifies time delay for the alarm stage until the output can be
asserted.
• RTD INPUT H1 TRIP TEMPERATURE: This setting specifies the temperature pickup level for the trip stage.
• RTD INPUT H1 TRIP PKP DELAY: This setting specifies time delay for the trip stage until the output can be asserted.

GE Multilin G60 Generator Protection System 5-265


5.9 TRANSDUCER INPUTS AND OUTPUTS 5 SETTINGS

• RTD INPUT H1 TRIP RST DELAY: This setting specifies the reset delay to seal-in the trip signal.
• RTD INPUT H1 TRIP VOTING: This setting allows securing trip signal by voting with other RTDs. A value of “None”
indicates that element operates individually and no voting takes place.
A value of “Group” indicates that element is allowed to issue a trip if N – 1 of other RTDs of the same group pick up as
well (where N is the number of enabled RTDs from the group). For example, if three RTDs are assigned to the same
group, there should be at least one additional RTD of the same group picked up to issue a trip command.
The “RTD Inp H1” through “RTD Inp W8” values indicate that element is allowed to issue a trip if the corresponding
peer RTD is also picked up.
• RTD INPUT H1 OPEN: This setting allows monitoring an open RTD sensor circuit. If this functionality is not required,
then a value of “None” will disable monitoring and assertion of output operands.
If set to “Alarm”, the monitor will set an alarm when a broken sensor is detected.
If set to “Block”, the monitor will set an alarm and simultaneously block RTD operation when a broken sensor is
detected.
If targets are enabled, a message will appear on the display identifying the broken RTD. If this feature is used, it is rec-
ommended that the alarm be programmed as latched so that intermittent RTDs are detected and corrective action may
be taken.
• RTD INPUT H1 BLOCK: This setting is used to block RTD operation.

SETTINGS
RTD INPUT H1 FUNCTION
= Enabled
RTD INPUT H1 BLOCK AND To other RTDs for voting
Off = 0

5 SETTINGS
SETTINGS
RTD INPUT H1 TRIP
PKP DELAY SETTINGS
SETTINGS RTD INPUT H1 TRIP RTD INPUT H1 TRIP RTD INPUT H1
RTD INPUT H1 ID TEMPERATURE RST DELAY APPLICATION
= RTD Inp H1 RTD INPUT H1 ALARM RTD INPUT H1 ALARM RTD INPUT H1 TRIP
TEMPERATURE PKP DELAY VOTING
RTD INPUT H1 TYPE
RUN TPKP FLEXLOGIC OPERAND
Resistance to Voting logic RTD Ip TRIP OP
temperature > TRIP PICKUP TDPO
temperature conversion
RUN TPKP
AND temperature > ALARM PICKUP From other RTDs for voting FLEXLOGIC OPERANDS
0
RTD Ip ALARM OP
SETTING
RTD Ip TRIP PKP
RTD INPUT H1 OPEN
Block RTD Ip TRIP DPO
RUN
Alarm RTD Ip ALARM PKP
R ³ 250°C OR
None RTD Ip ALARM DPO
RUN RTD Ip OPEN
RTD Ip SHORTED
R £ –50°C
833019A2.CDR

Figure 5–150: RTD INPUT PROTECTION LOGIC

5.9.3 RRTD INPUTS

a) MAIN MENU
PATH: SETTINGS ÖØ TRANSDUCER I/O ÖØ RRTD INPUTS

„ RRTD INPUTS „ RRTD 1


See page 5-267.
„ „
„ RRTD 2
MESSAGE See page 5-267.
„

„ RRTD 12
MESSAGE See page 5-267.
„

Menus are available to configure each of the remote RTDs.

5-266 G60 Generator Protection System GE Multilin


5 SETTINGS 5.9 TRANSDUCER INPUTS AND OUTPUTS

It is recommended to use the G60 to configure the RRTD parameters. If the RRTDPC software is used to change the
RRTD settings directly (the application and type settings), then one of the following two operations is required for changes
to be reflected in the G60.
• Cycle power to G60.
• Break then re-establish the communication link between the RRTD unit and the G60. This will cause the RRTD COMM
FAIL operand to be asserted then de-asserted.

b) REMOTE RTDS 1 THROUGH 12


PATH: SETTINGS ÖØ TRANSDUCER I/O ÖØ RRTD INPUTS ÖØ RRTD RTD 1(12)

„ RRTD 1 RRTD 1 FUNCTION: Range: Disabled, Enabled


„ Disabled
RRTD 1 ID: Range: Up to 20 alphanumeric characters
MESSAGE
RRTD 1
RRTD 1 TYPE: Range: 100 Ω Nickel, 10 Ω Copper, 100 Ω Platinum,
MESSAGE 120 Ω Nickel
100 Ω Nickel
RRTD 1 Range: None, Stator, Bearing, Ambient, Group 1,
MESSAGE Group 2
APPLICATION: Bearing
RRTD 1 ALARM Range: 1 to 200°C in steps of 1
MESSAGE
TEMPERATURE: 130°C
RRTD 1 ALARM Range: 5 to 600 s in steps of 5
MESSAGE
PKP DELAY: 5 s
RRTD 1 TRIP Range: 1 to 200°C in steps of 1
5
MESSAGE
TEMPERATURE: 130°C
RRTD 1 TRIP Range: 5 to 600 s in steps of 5
MESSAGE
PKP DELAY: 5 s
RRTD 1 TRIP Range: 5 to 600 s in steps of 5
MESSAGE
RST DELAY: 5 s
RRTD 1 TRIP VOTING: Range: None, Group, Remote RTD 1, Remote RTD 2,...,
MESSAGE Remote RTD 12
None
RRTD 1 OPEN: Range: None, Alarm, Block
MESSAGE
None
RRTD 1 BLOCK: Range: FlexLogic™ operand
MESSAGE
Off
RRTD 1 TARGET: Range: Self-reset, Latched, Disabled
MESSAGE
Self-reset
RRTD 1 EVENTS: Range: Disabled, Enabled
MESSAGE
Disabled

The remote RTD inputs convert values of input resistance into temperature for further operations. These inputs are
intended to be connected to any of the RTD types in common use. Specific hardware details are contained in chapter 3.
On power up, the G60 reads and saves all application and type settings from the RRTD. This synchronizes the RRTD and
G60. Any changes to RRTD settings (function, application, or type) from the G60 interface are immediately reflected in the
RRTD. The following rules are followed.
• If the RRTD 1 FUNCTION setting is “Enabled”, then the RRTD 1 APPLICATION setting value will be written to RRTD device.
• If the RRTD 1 FUNCTION setting is “Disabled”, then RRTD1 APPLICATION setting value is set as “None”.
• If the RRTD 1 APPLICATION or RRTD 1 TYPE settings are changes, then these settings are immediately written to the
RRTD device.

GE Multilin G60 Generator Protection System 5-267


5.9 TRANSDUCER INPUTS AND OUTPUTS 5 SETTINGS

• If the RRTD 1 APPLICATION setting is “Group 1” or “Group 2”, then a value of “Other” is written to the RRTD device.
An RRTD actual value of –43°C implies that the RRTD 1 FUNCTION setting is “Enabled” but the corresponding RRTD 1 APPLI-
CATION setting is “None”.

If the RRTD communication link with the G60 is broken, then the last temperature actual values are retained until the RRTD
communication failure is detected. When this occurs, a RRTD COMM FAILURE self-test alarm and target message is gen-
erated, and an event is logged in the event recorder and the temperature actual values reset to 0. When the link is re-estab-
lished, the RRTD 1 APPLICATION and RRTD 1 TYPE settings are read from the RRTD to re-synchronize the device.
• RRTD 1 FUNCTION: This setting enables and disables the remote RTD. If set to “Disabled”, no actual value is created
for the remote RTD.
• RRTD 1 ID: This setting is used to assign alphanumeric ID is assigned to the remote RTD. This ID will be included in
the remote RTD actual values. It is also used to reference the remote RTD input to features using the remote RTD.
• RRTD 1 TYPE: This setting specifies the remote RTD type. Four different RTD types are available: 100 Ω Nickel, 10 Ω
Copper, 100 Ω Platinum, and 120 Ω Nickel.
The RRTD converts resistance to temperature as per the values in the following table. The G60 reads the RTD temper-
atures from the RRTD once every five seconds and applies protection accordingly. The RRTDs can be used to provide
RTD bias in the existing thermal model.

Table 5–30: RTD TEMPERATURE VS. RESISTANCE


TEMPERATURE RESISTANCE (IN OHMS)
°C °F 100 OHM PT 120 OHM NI 100 OHM NI 10 OHM CU
(DIN 43760)
–40 –40 84.27 92.76 79.13 7.49
5 –30 –22 88.22 99.41 84.15 7.88
–20 –4 92.16 106.15 89.23 8.26
–10 14 96.09 113 94.58 8.65
0 32 100 120 100 9.04
10 50 103.9 127.17 105.6 9.42
20 68 107.79 134.52 111.2 9.81
30 86 111.67 142.06 117.1 10.19
40 104 115.54 149.79 123 10.58
50 122 119.39 157.74 129.1 10.97
60 140 123.24 165.9 135.3 11.35
70 158 127.07 174.25 141.7 11.74
80 176 130.89 182.84 148.3 12.12
90 194 134.7 191.64 154.9 12.51
100 212 138.5 200.64 161.8 12.9
110 230 142.29 209.85 168.8 13.28
120 248 146.06 219.29 176 13.67
130 266 149.82 228.96 183.3 14.06
140 284 153.58 238.85 190.9 14.44
150 302 157.32 248.95 198.7 14.83
160 320 161.04 259.3 206.6 15.22
170 338 164.76 269.91 214.8 15.61
180 356 168.47 280.77 223.2 16
190 374 172.46 291.96 231.6 16.39
200 392 175.84 303.46 240 16.78

An RRTD open condition is detected when actual RRTD resistance is greater than 1000 ohms and RRTD open is dis-
played as “250°C” in the G60.

5-268 G60 Generator Protection System GE Multilin


5 SETTINGS 5.9 TRANSDUCER INPUTS AND OUTPUTS

An RRTD short condition is detected when actual RRTD temperature is less than –40°C and RRTD short is displayed
as is “–50°C”. in the G60.
• RRTD 1 APPLICATION: This setting allows each remote RTD to be assigned to a group application. This is useful for
applications that require group measurement for voting. A value of “None” specifies that the remote RTD will operate
individually and not part of any RTD group. All remote RTDs programmed to “Stator” are used for RTD biasing of the
G60 thermal model. Common groups are provided for rotating machines applications such as ambient, bearing, group
1, or group 2. If the REMOTE RTD 1 TRIP VOTING setting value is “Group”, then it is allowed to issue a trip if N – 1 RTDs
from the same group also pick up, where N is the number of enabled RTDs from the group.
• RRTD 1 ALARM TEMPERATURE: This setting specifies the temperature pickup level for the alarm stage. The range
of 1 to 200°C differs from the existing RTD settings to correspond to the range of the RRTD unit.
• RRTD 1 ALARM PKP DELAY: This setting specifies time delay for the alarm stage until the output can be asserted.
The range of 5 to 600 seconds differs from the existing RTD settings to correspond to the range of the RRTD unit.
• RRTD 1 TRIP TEMPERATURE: This setting specifies the temperature pickup level for the trip stage. The range of 1 to
200°C differs from the existing RTD settings to correspond to the range of the RRTD unit.
• RRTD 1 TRIP PKP DELAY: This setting specifies time delay for the trip stage until the output can be asserted. The
range of 5 to 600 seconds differs from the existing RTD settings to correspond to the range of the RRTD unit.
• RRTD 1 TRIP RST DELAY: This setting specifies the reset delay to seal-in the trip signal.
• RRTD 1 TRIP VOTING: This setting allows securing trip signal by voting with other RTDs. A value of “None” indicates
that element operates individually and no voting takes place.
A value of “Group” indicates that element is allowed to issue a trip if N – 1 of other RTDs of the same group pick up as
well (where N is the number of enabled RTDs from the group). For example, if three RTDs are assigned to the same
group, there should be at least one additional RTD of the same group picked up to issue a trip command.
The “Remote RTD 1” through “Remote RTD 12” values indicate that element is allowed to issue a trip if the corre- 5
sponding peer RTD is also picked up.
• RRTD 1 OPEN: This setting allows monitoring an open remote RTD sensor circuit. If this functionality is not required,
then a value of “None” will disable monitoring and assertion of output operands.
If set to “Alarm”, the monitor will set an alarm when a broken sensor is detected.
If set to “Block”, the monitor will set an alarm and simultaneously block remote RTD operation when a broken sensor is
detected.
If targets are enabled, a message will appear on the display identifying the broken RTD. If this feature is used, it is rec-
ommended that the alarm be programmed as latched so that intermittent RTDs are detected and corrective action may
be taken.
• RRTD 1 BLOCK: This setting is used to block remote RTD operation.

GE Multilin G60 Generator Protection System 5-269


5.9 TRANSDUCER INPUTS AND OUTPUTS 5 SETTINGS

SETTINGS
Function
Enabled = 1
Block AND
Off = 0

SETTING To other remote RTDs


ID for voting
= RRTD 1

SETTINGS
SETTINGS Trip Pickup Delay SETTINGS
AND
Trip Temperature Trip Reset Delay Application
SETTING
Alarm Temperature Alarm Pickup Delay Trip Voting
Type
RUN TPKP FLEXLOGIC OPERAND
Temperature read Voting logic REMOTE RTD 1 TRIP OP
temperature > Trip Pickup TDPO
from RRTD
RUN TPKP
temperature > Alarm Pickup From other remote FLEXLOGIC OPERANDS
0 RTDs for voting
RRTD 1 ALARM OP
SETTING
RRTD 1 TRIP PKP
Open
Block RRTD 1 TRIP DPO
RUN
Alarm RRTD 1 ALARM PKP
R > 1000 ohms OR
None RRTD 1 ALARM DPO
RUN RRTD 1 OPEN
RRTD 1 SHORTED
T £ –40°C
833026A1.CDR

Figure 5–151: REMOTE RTD INPUT PROTECTION LOGIC

5.9.4 DCMA OUTPUTS

PATH: SETTINGS ÖØ TRANSDUCER I/O ÖØ DCMA OUTPUTS Ö DCMA OUTPUT H1(W8)


5 „ DCMA OUTPUT H1 DCMA OUTPUT H1 Range: Off, any analog actual value parameter
„ SOURCE: Off
DCMA OUTPUT H1 Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
MESSAGE
RANGE: –1 to 1 mA
DCMA OUTPUT H1 Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
MIN VAL: 0.000 pu
DCMA OUTPUT H1 Range: –90.000 to 90.000 pu in steps of 0.001
MESSAGE
MAX VAL: 1.000 pu

Hardware and software is provided to generate dcmA signals that allow interfacing with external equipment. Specific hard-
ware details are contained in chapter 3. The dcmA output channels are arranged in a manner similar to transducer input or
CT and VT channels. The user configures individual channels with the settings shown below.
The channels are arranged in sub-modules of two channels, numbered 1 through 8 from top to bottom. On power-up, the
relay automatically generates configuration settings for every channel, based on the order code, in the same manner used
for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as
the channel number.
Both the output range and a signal driving a given output are user-programmable via the following settings menu (an exam-
ple for channel M5 is shown).
The relay checks the driving signal (x in equations below) for the minimum and maximum limits, and subsequently re-
scales so the limits defined as MIN VAL and MAX VAL match the output range of the hardware defined as RANGE. The follow-
ing equation is applied:

⎧ I min if x < MIN VAL



I out = ⎨ I max if x > MAX VAL (EQ 5.53)

⎩ k ( x – MIN VAL ) + I min otherwise

5-270 G60 Generator Protection System GE Multilin


5 SETTINGS 5.9 TRANSDUCER INPUTS AND OUTPUTS

where: x is a driving signal specified by the SOURCE setting


Imin and Imax are defined by the RANGE setting
k is a scaling constant calculated as:
I max – I min
k = ------------------------------------------------
- (EQ 5.54)
MAX VAL – MIN VAL

The feature is intentionally inhibited if the MAX VAL and MIN VAL settings are entered incorrectly, e.g. when MAX VAL – MIN
VAL< 0.1 pu. The resulting characteristic is illustrated in the following figure.

Imax
OUTPUT CURRENT

Imin
DRIVING SIGNAL
MIN VAL MAX VAL 842739A1.CDR

Figure 5–152: DCMA OUTPUT CHARACTERISTIC


The dcmA output settings are described below. 5
• DCMA OUTPUT H1 SOURCE: This setting specifies an internal analog value to drive the analog output. Actual values
(FlexAnalog parameters) such as power, current amplitude, voltage amplitude, power factor, etc. can be configured as
sources driving dcmA outputs. Refer to Appendix A for a complete list of FlexAnalog parameters.
• DCMA OUTPUT H1 RANGE: This setting allows selection of the output range. Each dcmA channel may be set inde-
pendently to work with different ranges. The three most commonly used output ranges are available.
• DCMA OUTPUT H1 MIN VAL: This setting allows setting the minimum limit for the signal that drives the output. This
setting is used to control the mapping between an internal analog value and the output current. The setting is entered
in per-unit values. The base units are defined in the same manner as the FlexElement™ base units.
• DCMA OUTPUT H1 MAX VAL: This setting allows setting the maximum limit for the signal that drives the output. This
setting is used to control the mapping between an internal analog value and the output current. The setting is entered
in per-unit values. The base units are defined in the same manner as the FlexElement™ base units.
The DCMA OUTPUT H1 MIN VAL and DCMA OUTPUT H1 MAX VAL settings are ignored for power factor base units (i.e. if
the DCMA OUTPUT H1 SOURCE is set to FlexAnalog value based on power factor measurement).
NOTE

Three application examples are described below.


EXAMPLE: POWER MONITORING
A three phase active power on a 13.8 kV system measured via UR-series relay source 1 is to be monitored by the dcmA H1
output of the range of –1 to 1 mA. The following settings are applied on the relay: CT ratio = 1200:5, VT secondary 115, VT
connection is delta, and VT ratio = 120. The nominal current is 800 A primary and the nominal power factor is 0.90. The
power is to be monitored in both importing and exporting directions and allow for 20% overload compared to the nominal.
The nominal three-phase power is:

P = 3 × 13.8 kV × 0.8 kA × 0.9 = 17.21 MW (EQ 5.55)

The three-phase power with 20% overload margin is:


P max = 1.2 × 17.21 MW = 20.65 MW (EQ 5.56)

GE Multilin G60 Generator Protection System 5-271


5.9 TRANSDUCER INPUTS AND OUTPUTS 5 SETTINGS

The base unit for power (refer to the FlexElements section in this chapter for additional details) is:
P BASE = 115 V × 120 × 1.2 kA = 16.56 MW (EQ 5.57)

The minimum and maximum power values to be monitored (in pu) are:
20.65 MW = – 1.247 pu, maximum power = 20.65 MW- = 1.247 pu
minimum power = –------------------------------ -------------------------- (EQ 5.58)
16.56 MW 16.56 MW
The following settings should be entered:
DCMA OUTPUT H1 SOURCE: “SRC 1 P”
DCMA OUTPUT H1 RANGE: “–1 to 1 mA”
DCMA OUTPUT H1 MIN VAL: “–1.247 pu”
DCMA OUTPUT H1 MAX VAL: “1.247 pu”

With the above settings, the output will represent the power with the scale of 1 mA per 20.65 MW. The worst-case error for
this application can be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or ± 0.005 × ( 1 – ( – 1 ) ) × 20.65 MW = ± 0.207 MW
• ±1% of reading error for the active power at power factor of 0.9
For example at the reading of 20 MW, the worst-case error is 0.01 × 20 MW + 0.207 MW = 0.407 MW.
EXAMPLE: CURRENT MONITORING
The phase A current (true RMS value) is to be monitored via the H2 current output working with the range from 4 to 20 mA.
The CT ratio is 5000:5 and the maximum load current is 4200 A. The current should be monitored from 0 A upwards, allow-
ing for 50% overload.
The phase current with the 50% overload margin is:
5 I max = 1.5 × 4.2 kA = 6.3 kA (EQ 5.59)

The base unit for current (refer to the FlexElements section in this chapter for additional details) is:
I BASE = 5 kA (EQ 5.60)

The minimum and maximum power values to be monitored (in pu) are:

minimum current = 0 kA- = 0 pu, maximum current = 6.3 kA- = 1.26 pu


----------- ---------------- (EQ 5.61)
5 kA 5 kA
The following settings should be entered:
DCMA OUTPUT H2 SOURCE: “SRC 1 Ia RMS”
DCMA OUTPUT H2 RANGE: “4 to 20 mA”
DCMA OUTPUT H2 MIN VAL: “0.000 pu”
DCMA OUTPUT H2 MAX VAL: “1.260 pu”

The worst-case error for this application could be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or ± 0.005 × ( 20 – 4 ) × 6.3 kA = ± 0.504 kA
• ±0.25% of reading or ±0.1% of rated (whichever is greater) for currents between 0.1 and 2.0 of nominal
For example, at the reading of 4.2 kA, the worst-case error is max(0.0025 × 4.2 kA, 0.001 × 5 kA) + 0.504 kA = 0.515 kA.
EXAMPLE: VOLTAGE MONITORING
A positive-sequence voltage on a 400 kV system measured via source 2 is to be monitored by the dcmA H3 output with a
range of 0 to 1 mA. The VT secondary setting is 66.4 V, the VT ratio setting is 6024, and the VT connection setting is
“Delta”. The voltage should be monitored in the range from 70% to 110% of nominal.
The minimum and maximum positive-sequence voltages to be monitored are:
400 kV 400 kV
V min = 0.7 × ------------------- = 161.66 kV, V max = 1.1 × ------------------- = 254.03 kV (EQ 5.62)
3 3
The base unit for voltage (refer to the FlexElements section in this chapter for additional details) is:

5-272 G60 Generator Protection System GE Multilin


5 SETTINGS 5.9 TRANSDUCER INPUTS AND OUTPUTS

V BASE = 0.0664 kV × 6024 = 400 kV (EQ 5.63)

The minimum and maximum voltage values to be monitored (in pu) are:

minimum voltage = 161.66 kV- = 0.404 pu, maximum voltage = 254.03 kV- = 0.635 pu
-------------------------- -------------------------- (EQ 5.64)
400 kV 400 kV
The following settings should be entered:
DCMA OUTPUT H3 SOURCE: “SRC 2 V_1 mag”
DCMA OUTPUT H3 RANGE: “0 to 1 mA”
DCMA OUTPUT H3 MIN VAL: “0.404 pu”
DCMA OUTPUT H3 MAX VAL: “0.635 pu”

The limit settings differ from the expected 0.7 pu and 1.1 pu because the relay calculates the positive-sequence quantities
scaled to the phase-to-ground voltages, even if the VTs are connected in “Delta” (refer to the Metering conventions section
in chapter 6), while at the same time the VT nominal voltage is 1 pu for the settings. Consequently the settings required in
this example differ from naturally expected by the factor of 3 .
The worst-case error for this application could be calculated by superimposing the following two sources of error:
• ±0.5% of the full scale for the analog output module, or ± 0.005 × ( 1 – 0 ) × 254.03 kV = ± 1.27 kV
• ±0.5% of reading
For example, under nominal conditions, the positive-sequence reads 230.94 kV and the worst-case error is
0.005 x 230.94 kV + 1.27 kV = 2.42 kV.

GE Multilin G60 Generator Protection System 5-273


5.10 TESTING 5 SETTINGS

5.10TESTING 5.10.1 TEST MODE

PATH: SETTINGS ÖØ TESTING Ö TEST MODE

„„ SETTINGS TEST MODE Range: Disabled, Isolated, Forcible


„„ TESTING FUNCTION: Disabled
TEST MODE FORCING: Range: FlexLogic™ operand
MESSAGE
On

The G60 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and
the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face-
plate by a Test Mode LED indicator.
The test mode may be in any of three states: disabled, isolated, or forcible.
In the “Disabled” mode, G60 operation is normal and all test features are disabled.
In the “Isolated” mode, the G60 is prevented from performing certain control actions, including tripping via contact outputs.
All relay contact outputs, including latching outputs, are disabled. Channel tests and phasor measurement unit tests remain
usable on applicable UR-series models.
In the “Forcible” mode, the operand selected by the TEST MODE FORCING setting controls the relay inputs and outputs. If the
test mode is forcible, and the operand assigned to the TEST MODE FORCING setting is “Off”, the G60 inputs and outputs oper-
ate normally. If the test mode is forcible, and the operand assigned to the TEST MODE FORCING setting is “On”, the G60 con-
tact inputs and outputs are forced to the values specified in the following sections. Forcing may be controlled by manually
changing the operand selected by the TEST MODE FORCING setting between on and off, or by selecting a user-programma-
ble pushbutton, contact input, or communication-based input operand. Channel tests and phasor measurement unit tests

5 remain usable on applicable UR-series models.


Communications based inputs and outputs remain fully operational in test mode. If a control action is programmed
using direct inputs and outputs or remote inputs and outputs, then the test procedure must take this into account.
NOTE

When in “Forcible” mode, the operand selected by the TEST MODE FORCING setting dictates further response of the G60 to
testing conditions. To force contact inputs and outputs through relay settings, set TEST MODE FORCING to “On”. To force con-
tact inputs and outputs through a user-programmable condition, such as FlexLogic™ operand (pushbutton, digital input,
communication-based input, or a combination of these), set TEST MODE FORCING to the desired operand. The contact input
or output is forced when the selected operand assumes a logic 1 state.
The G60 remains fully operational in test mode, allowing for various testing procedures. In particular, the protection and
control elements, FlexLogic™, and communication-based inputs and outputs function normally.
The only difference between the normal operation and the test mode is the behavior of the input and output contacts. The
contact inputs can be forced to report as open or closed or remain fully operational, whereas the contact outputs can be
forced to open, close, freeze, or remain fully operational. The response of the digital input and output contacts to the test
mode is programmed individually for each input and output using the force contact inputs and force contact outputs test
functions described in the following sections.
The test mode state is indicated on the relay faceplate by a combination of the Test Mode LED indicator, the In-Service LED
indicator, and by the critical fail relay, as shown in the following table.

5-274 G60 Generator Protection System GE Multilin


5 SETTINGS 5.10 TESTING

Table 5–31: TEST MODE OPERATION


TEST MODE TEST MODE IN-SERVICE TEST MODE CRITICAL INPUT AND OUTPUT BEHAVIOR
FUNCTION FORCING LED LED FAIL
OPERAND RELAY
Disabled No effect Unaffected Off Unaffected Contact outputs and inputs are under normal
operation. Channel tests and PMU tests not
operational (where applicable).
Isolated No effect Off On De- Contact outputs are disabled and contact inputs
energized are operational. Channel tests and PMU tests
are also operational (where applicable).
Forcible On (logic 1) Off Flashing De- Contact inputs and outputs are controlled by the
energized force contact input and force contact output
functions. Channel tests and PMU tests are
operational (where applicable).
Off (logic 0) Off Flashing De- Contact outputs and inputs are under normal
energized operation. Channel tests and PMU tests are also
operational (where applicable).

The TEST MODE FUNCTION setting can only be changed by a direct user command. Following a restart, power up, settings
upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a G60 that has been
placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING
setting and the force contact input and force contact output settings all revert to their default states.

5.10.2 FORCE CONTACT INPUTS

PATH: SETTINGS ÖØ TESTING ÖØ FORCE CONTACT INPUTS

„ FORCE CONTACT FORCE Cont Ip 1 Range: Disabled, Open, Closed 5


„ INPUTS :Disabled
FORCE Cont Ip 2 Range: Disabled, Open, Closed
MESSAGE
:Disabled

FORCE Cont Ip xx Range: Disabled, Open, Closed


MESSAGE
:Disabled

The relay digital inputs (contact inputs) could be pre-programmed to respond to the test mode in the following ways:
• If set to “Disabled”, the input remains fully operational. It is controlled by the voltage across its input terminals and can
be turned on and off by external circuitry. This value should be selected if a given input must be operational during the
test. This includes, for example, an input initiating the test, or being a part of a user pre-programmed test sequence.
• If set to “Open”, the input is forced to report as opened (Logic 0) for the entire duration of the test mode regardless of
the voltage across the input terminals.
• If set to “Closed”, the input is forced to report as closed (Logic 1) for the entire duration of the test mode regardless of
the voltage across the input terminals.
The force contact inputs feature provides a method of performing checks on the function of all contact inputs. Once
enabled, the relay is placed into test mode, allowing this feature to override the normal function of contact inputs. The Test
Mode LED will be on, indicating that the relay is in test mode. The state of each contact input may be programmed as “Dis-
abled”, “Open”, or “Closed”. All contact input operations return to normal when all settings for this feature are disabled.

GE Multilin G60 Generator Protection System 5-275


5.10 TESTING 5 SETTINGS

5.10.3 FORCE CONTACT OUTPUTS

PATH: SETTINGS ÖØ TESTING ÖØ FORCE CONTACT OUTPUTS

„ FORCE CONTACT FORCE Cont Op 1 Range: Disabled, Energized, De-energized, Freeze


„ OUTPUTS :Disabled
FORCE Cont Op 2 Range: Disabled, Energized, De-energized, Freeze
MESSAGE
:Disabled

FORCE Cont Op xx Range: Disabled, Energized, De-energized, Freeze


MESSAGE
:Disabled

The relay contact outputs can be pre-programmed to respond to the test mode.
If set to “Disabled”, the contact output remains fully operational. If operates when its control operand is logic 1 and will
resets when its control operand is logic 0. If set to “Energized”, the output will close and remain closed for the entire dura-
tion of the test mode, regardless of the status of the operand configured to control the output contact. If set to “De-ener-
gized”, the output will open and remain opened for the entire duration of the test mode regardless of the status of the
operand configured to control the output contact. If set to “Freeze”, the output retains its position from before entering the
test mode, regardless of the status of the operand configured to control the output contact.
These settings are applied two ways. First, external circuits may be tested by energizing or de-energizing contacts. Sec-
ond, by controlling the output contact state, relay logic may be tested and undesirable effects on external circuits avoided.
Example 1: Initiating test mode through user-programmable pushbutton 1

5 For example, the test mode can be initiated from user-programmable pushbutton 1. The pushbutton will be programmed as
“Latched” (pushbutton pressed to initiate the test, and pressed again to terminate the test). During the test, digital input 1
should remain operational, digital inputs 2 and 3 should open, and digital input 4 should close. Also, contact output 1 should
freeze, contact output 2 should open, contact output 3 should close, and contact output 4 should remain fully operational.
The required settings are shown below.
To enable user-programmable pushbutton 1 to initiate the test mode, make the following changes in the SETTINGS ÖØ
TESTING Ö TEST MODE menu: TEST MODE FUNCTION: “Enabled” and TEST MODE INITIATE: “PUSHBUTTON 1 ON”

Make the following changes to configure the contact inputs and outputs. In the SETTINGS ÖØ TESTING ÖØ FORCE CONTACT
INPUTS and FORCE CONTACT OUTPUTS menus, set:

FORCE Cont Ip 1: “Disabled”, FORCE Cont Ip 2: “Open”, FORCE Cont Ip 3: “Open”, and FORCE Cont Ip 4: “Closed”
FORCE Cont Op 1: “Freeze”, FORCE Cont Op 2: “De-energized”, FORCE Cont Op 3: “Energized”,
and FORCE Cont Op 4: “Disabled”
Example 2: Initiating a test from user-programmable pushbutton 1 or through remote input 1
In this example, the test can be initiated locally from user-programmable pushbutton 1 or remotely through remote input 1.
Both the pushbutton and the remote input will be programmed as “Latched”. Write the following FlexLogic™ equation:

Set the user-programmable pushbutton as latching by changing SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE
PUSHBUTTONS Ö USER PUSHBUTTON 1 Ö PUSHBUTTON 1 FUNCTION to “Latched”. To enable either pushbutton 1 or remote
input 1 to initiate the Test mode, make the following changes in the SETTINGS ÖØ TESTING Ö TEST MODE menu:
TEST MODE FUNCTION: “Enabled” and TEST MODE INITIATE: “VO1”

5-276 G60 Generator Protection System GE Multilin


5 SETTINGS 5.10 TESTING

5.10.4 PHASOR MEASUREMENT UNIT TEST VALUES

PATH: SETTINGS ÖØ TESTING ÖØ PMU TEST VALUES Ö PMU 1 TEST VALUES

„ PMU 1 PMU 1 TEST Range: Enabled, Disabled


„ TEST VALUES FUNCTION: Disabled
PMU 1 VA TEST Range: 0.00 to 700.00 kV in steps of 0.01
MESSAGE
MAGNITUDE: 500.00 kV
PMU 1 VA TEST Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
ANGLE: 0.00°
PMU 1 VB TEST Range: 0.00 to 700.00 kV in steps of 0.01
MESSAGE
MAGNITUDE: 500.00 kV
PMU 1 VB TEST Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
ANGLE: –120.00°
PMU 1 VC TEST Range: 0.00 to 700.00 kV in steps of 0.01
MESSAGE
MAGNITUDE: 500.00 kV
PMU 1 VC TEST Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
ANGLE: 120.00°
PMU 1 VX TEST Range: 0.00 to 700.00 kV in steps of 0.01
MESSAGE
MAGNITUDE: 500.00 kV
PMU 1 VX TEST Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
ANGLE: 0.00° 5
PMU 1 IA TEST Range: 0.000 to 9.999 kA in steps of 0.001
MESSAGE
MAGNITUDE: 1.000 kA
PMU 1 IA TEST Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
ANGLE: –10.00°
PMU 1 IB TEST Range: 0.000 to 9.999 kA in steps of 0.001
MESSAGE
MAGNITUDE: 1.000 kA
PMU 1 IB TEST Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
ANGLE: –130.00°
PMU 1 IC TEST Range: 0.000 to 9.999 kA in steps of 0.001
MESSAGE
MAGNITUDE: 1.000 kA
PMU 1 IC TEST Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
ANGLE: 110.00°
PMU 1 IG TEST Range: 0.000 to 9.999 kA in steps of 0.001
MESSAGE
MAGNITUDE: 0.000 kA
PMU 1 IG TEST Range: –180.00 to 180.00° in steps of 0.05
MESSAGE
ANGLE: 0.00°
PMU 1 TEST Range: 20.000 to 60.000 Hz in steps of 0.001
MESSAGE
FREQUENCY: 60.000 Hz
PMU 1 TEST Range: –10.000 to 10.000 Hz/s in steps of 0.001
MESSAGE
df/dt: 0.000 Hz/s

The relay must be in test mode to use the PMU test mode. That is, the TESTING Ö TEST MODE FUNCTION setting must be
“Enabled” and the TESTING ÖØ TEST MODE INITIATE initiating signal must be “On”.

GE Multilin G60 Generator Protection System 5-277


5.10 TESTING 5 SETTINGS

During the PMU test mode, the physical channels (VA, VB, VC, VX, IA, IB, IC, and IG), frequency, and rate of change of fre-
quency are substituted with user values, while the symmetrical components are calculated from the physical channels. The
test values are not explicitly marked in the outgoing data frames. When required, it is recommended to use the user-pro-
grammable digital channels to signal the C37.118 client that test values are being sent in place of the real measurements.

5-278 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.1 OVERVIEW

6 ACTUAL VALUES 6.1OVERVIEW 6.1.1 ACTUAL VALUES MAIN MENU

„„ ACTUAL VALUES „ CONTACT INPUTS


See page 6-4.
„„ STATUS „
„ VIRTUAL INPUTS
See page 6-4.
„
„ REMOTE INPUTS
See page 6-4.
„
„ REMOTE DPS INPUTS
See page 6-5.
„
„ TELEPROTECTION
See page 6-5.
„ INPUTS
„ CONTACT OUTPUTS
See page 6-5.
„
„ VIRTUAL OUTPUTS
See page 6-6.
„
„ REMOTE DEVICES
See page 6-6.
„ STATUS
„ REMOTE DEVICES
See page 6-6.
„ STATISTICS
„ DIGITAL COUNTERS
See page 6-7.
„
„ SELECTOR SWITCHES
See page 6-7.
„
„ FLEX STATES
See page 6-7.
6
„
„ ETHERNET
See page 6-7.
„
„ DIRECT INPUTS
See page 6-8.
„
„ DIRECT DEVICES
See page 6-8.
„ STATUS
„ IEC 61850
See page 6-9.
„ GOOSE UINTEGERS
„ EGD PROTOCOL
See page 6-9.
„ STATUS
„ TELEPROT CH TESTS
See page 6-10.
„
„ ETHERNET SWITCH
See page 6-10.
„

„„ ACTUAL VALUES „ STATOR


See page 6-14.
„„ METERING „ DIFFERENTIAL
„ SOURCE SRC 1
See page 6-14.
„

GE Multilin G60 Generator Protection System 6-1


6.1 OVERVIEW 6 ACTUAL VALUES

„ SOURCE SRC 2
„
„ SOURCE SRC 3
„
„ SOURCE SRC 4
„
„ SYNCHROCHECK
See page 6-19.
„
„ TRACKING FREQUENCY
See page 6-20.
„
„ FREQUENCY RATE
See page 6-20.
„ OF CHANGE
„ FREQUENCY OOB
See page 6-20.
„ ACCUMULATION
„ FLEXELEMENTS
See page 6-21.
„

„ IEC 61850
See page 6-22.
„ GOOSE ANALOGS

„ SENSITIVE
See page 6-22.
„ DIRECTIONAL POWER
„ STATOR
See page 6-22.
„ GROUND
„ SUB-HARMONIC
See page 6-23.
„ STATOR GROUND

6 „ FIELD
„ GROUND
See page 6-23.

„ VOLTS PER HERTZ 1


See page 6-23.
„
„ VOLTS PER HERTZ 2
See page 6-23.
„
„ RESTRICTED GROUND
See page 6-23.
„ FAULT CURRENTS
„ PHASOR MEASUREMENT
See page 6-24.
„ UNIT
„ TRANSDUCER I/O
See page 6-25.
„ DCMA INPUTS
„ TRANSDUCER I/O
See page 6-25.
„ RTD INPUTS

„„ ACTUAL VALUES „ USER-PROGRAMMABLE


See page 6-26.
„„ RECORDS „ FAULT REPORTS
„ EVENT RECORDS
See page 6-26.
„
„ OSCILLOGRAPHY
See page 6-26.
„

6-2 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.1 OVERVIEW

„ DATA LOGGER
See page 6-27.
„
„ PMU RECORDS
See page 6-27.
„

„„ ACTUAL VALUES „ MODEL INFORMATION


See page 6-28.
„„ PRODUCT INFO „
„ FIRMWARE REVISIONS
See page 6-28.
„

GE Multilin G60 Generator Protection System 6-3


6.2 STATUS 6 ACTUAL VALUES

6.2STATUS
For status reporting, ‘On’ represents Logic 1 and ‘Off’ represents Logic 0.

NOTE

6.2.1 CONTACT INPUTS

PATH: ACTUAL VALUES Ö STATUS Ö CONTACT INPUTS

„ CONTACT INPUTS Cont Ip 1 Range: On, Off


„ Off
Cont Ip 2 Range: On, Off
MESSAGE
Off

Cont Ip xx Range: On, Off


MESSAGE
Off

The present status of the contact inputs is shown here. The first line of a message display indicates the ID of the contact
input. For example, ‘Cont Ip 1’ refers to the contact input in terms of the default name-array index. The second line of the
display indicates the logic state of the contact input.

6.2.2 VIRTUAL INPUTS

PATH: ACTUAL VALUES Ö STATUS ÖØ VIRTUAL INPUTS

„ VIRTUAL INPUTS Virt Ip 1 Range: On, Off


„ Off
Virt Ip 2 Range: On, Off
MESSAGE
Off

6 Virt Ip 64 Range: On, Off
MESSAGE
Off

The present status of the 64 virtual inputs is shown here. The first line of a message display indicates the ID of the virtual
input. For example, ‘Virt Ip 1’ refers to the virtual input in terms of the default name. The second line of the display indicates
the logic state of the virtual input.

6.2.3 REMOTE INPUTS

PATH: ACTUAL VALUES Ö STATUS ÖØ REMOTE INPUTS

„ REMOTE INPUTS REMOTE INPUT 1 Range: On, Off


„ STATUS: Off
REMOTE INPUT 2 Range: On, Off
MESSAGE
STATUS: Off

REMOTE INPUT 32 Range: On, Off


MESSAGE
STATUS: Off

The present state of the 32 remote inputs is shown here.


The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which
case the value shown is the programmed default state for the remote input.

6-4 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.2 STATUS

6.2.4 REMOTE DOUBLE-POINT STATUS INPUTS

PATH: ACTUAL VALUES Ö STATUS ÖØ REMOTE DPS INPUTS

„ REMOTE DPS INPUTS REMOTE DPS INPUT 1 Range: On, Off, Intermediate, Bad
„ STATUS: Bad
REMOTE DPS INPUT 2 Range: On, Off, Intermediate, Bad
MESSAGE
STATUS: Bad

REMOTE DPS INPUT 5 Range: On, Off, Intermediate, Bad


MESSAGE
STATUS: Bad

The present state of the remote double-point status inputs is shown here. The actual values indicate if the remote double-
point status inputs are in the on (close), off (open), intermediate, or bad state.

6.2.5 TELEPROTECTION INPUTS

PATH: ACTUAL VALUES Ö STATUS ÖØ TELEPROTECTION INPUTS

„ TELEPROTECTION TELEPROTECTION Range: Off, On


„ INPUTS INPUT 1-1: Off
TELEPROTECTION Range: Off, On
MESSAGE
INPUT 1-2: Off

TELEPROTECTION Range: Off, On


MESSAGE
INPUT 1-16: Off
TELEPROTECTION Range: Off, On
MESSAGE
INPUT 2-1: Off
TELEPROTECTION Range: Off, On 6
MESSAGE
INPUT 2-2: Off

TELEPROTECTION Range: Off, On


MESSAGE
INPUT 2-16: Off

The present state of teleprotection inputs from communication channels 1 and 2 are shown here. The state displayed will
be that of corresponding remote output unless the channel is declared failed.

6.2.6 CONTACT OUTPUTS

PATH: ACTUAL VALUES Ö STATUS ÖØ CONTACT OUTPUTS

„ CONTACT OUTPUTS Cont Op 1 Range: On, Off, VOff, VOn, IOn, IOff
„ Off
Cont Op 2 Range: On, Off, VOff, VOn, IOn, IOff
MESSAGE
Off

Cont Op xx Range: On, Off, VOff, VOn, IOn, IOff


MESSAGE
Off

The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.

GE Multilin G60 Generator Protection System 6-5


6.2 STATUS 6 ACTUAL VALUES

For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff,
On, IOn, and VOn. For form-C contact outputs, the state is displayed as Off or On.
NOTE

6.2.7 VIRTUAL OUTPUTS

PATH: ACTUAL VALUES Ö STATUS ÖØ VIRTUAL OUTPUTS

„ VIRTUAL OUTPUTS Virt Op 1 Range: On, Off


„ Off
Virt Op 2 Range: On, Off
MESSAGE
Off

Virt Op 96 Range: On, Off


MESSAGE
Off

The present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtual
output. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of the
display indicates the logic state of the virtual output, as calculated by the FlexLogic™ equation for that output.

6.2.8 REMOTE DEVICES

a) STATUS
PATH: ACTUAL VALUES Ö STATUS ÖØ REMOTE DEVICES STATUS

„ REMOTE DEVICES All REMOTE DEVICES Range: Yes, No


„ STATUS ONLINE: No
REMOTE DEVICE 1 Range: Online, Offline
MESSAGE
STATUS: Offline

6 MESSAGE
REMOTE DEVICE 2
STATUS: Offline
Range: Online, Offline

REMOTE DEVICE 16 Range: Online, Offline


MESSAGE
STATUS: Offline

The present state of the programmed remote devices is shown here. The ALL REMOTE DEVICES ONLINE message indicates
whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required
remote device is not online.

b) STATISTICS
PATH: ACTUAL VALUES Ö STATUS ÖØ REMOTE DEVICES STATISTICS Ö REMOTE DEVICE 1(16)

„ REMOTE DEVICE 1 REMOTE DEVICE 1


„ StNum: 0
REMOTE DEVICE 1
MESSAGE
SqNum: 0

Statistical data (two types) for up to 16 programmed remote devices is shown here.
The StNum number is obtained from the indicated remote device and is incremented whenever a change of state of at
least one DNA or UserSt bit occurs. The SqNum number is obtained from the indicated remote device and is incremented
whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented.

6-6 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.2 STATUS

6.2.9 DIGITAL COUNTERS

PATH: ACTUAL VALUES Ö STATUS ÖØ DIGITAL COUNTERS Ö DIGITAL COUNTERS Counter 1(8)

„ DIGITAL COUNTERS Counter 1 ACCUM:


„ Counter 1 0
Counter 1 FROZEN:
MESSAGE
0
Counter 1 FROZEN:
MESSAGE
YYYY/MM/DD HH:MM:SS
Counter 1 MICROS:
MESSAGE
0

The present status of the eight digital counters is shown here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label will also appear). Also included, is the date and
time stamp for the frozen count. The COUNTER 1 MICROS value refers to the microsecond portion of the time stamp.

6.2.10 SELECTOR SWITCHES

PATH: ACTUAL VALUES Ö STATUS ÖØ SELECTOR SWITCHES

„ SELECTOR SWITCHES SELECTOR SWITCH 1 Range: Current Position / 7


„ POSITION: 0/7
SELECTOR SWITCH 2 Range: Current Position / 7
MESSAGE
POSITION: 0/7

The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.

6.2.11 FLEX STATES


6
PATH: ACTUAL VALUES Ö STATUS ÖØ FLEX STATES

„ FLEX STATES PARAM 1: Off Range: Off, On


„ Off
PARAM 2: Off Range: Off, On
MESSAGE
Off

PARAM 256: Off Range: Off, On


MESSAGE
Off

There are 256 FlexState bits available. The second line value indicates the state of the given FlexState bit.

6.2.12 ETHERNET

PATH: ACTUAL VALUES Ö STATUS ÖØ ETHERNET

„ ETHERNET ETHERNET PRI LINK Range: Fail, OK


„ STATUS: OK
ETHERNET SEC LINK Range: Fail, OK
MESSAGE
STATUS: OK

These values indicate the status of the primary and secondary Ethernet links.

GE Multilin G60 Generator Protection System 6-7


6.2 STATUS 6 ACTUAL VALUES

6.2.13 DIRECT INPUTS

PATH: ACTUAL VALUES Ö STATUS ÖØ DIRECT INPUTS

„ DIRECT INPUTS AVG MSG RETURN


„ TIME CH1: 0 ms
UNRETURNED MSG
MESSAGE
COUNT CH1: 0
CRC FAIL COUNT
MESSAGE
CH1: 0
AVG MSG RETURN
MESSAGE
TIME CH2: 0 ms
UNRETURNED MSG
MESSAGE
COUNT CH2: 0
CRC FAIL COUNT
MESSAGE
CH2: 0
DIRECT INPUT 1:
MESSAGE
On
DIRECT INPUT 2:
MESSAGE
On

DIRECT INPUT 32:


MESSAGE
On

The AVERAGE MSG RETURN TIME is the time taken for direct output messages to return to the sender in a direct input/output
ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last
ten messages. There are two return times for dual-channel communications modules.
6 The UNRETURNED MSG COUNT values (one per communications channel) count the direct output messages that do not
make the trip around the communications ring. The CRC FAIL COUNT values (one per communications channel) count the
direct output messages that have been received but fail the CRC check. High values for either of these counts may indicate
on a problem with wiring, the communication channel, or one or more relays. The UNRETURNED MSG COUNT and CRC FAIL
COUNT values can be cleared using the CLEAR DIRECT I/O COUNTERS command.

The DIRECT INPUT 1 to DIRECT INPUT (32) values represent the state of each direct input.

6.2.14 DIRECT DEVICES STATUS

PATH: ACTUAL VALUES Ö STATUS ÖØ DIRECT DEVICES STATUS

„ DIRECT DEVICES DIRECT DEVICE 1 Range: Offline, Online


„ STATUS STATUS: Offline
DIRECT DEVICE 2 Range: Offline, Online
MESSAGE
STATUS: Offline

DIRECT DEVICE 16 Range: Offline, Online


MESSAGE
STATUS: Offline

These actual values represent the state of direct devices 1 through 16.

6-8 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.2 STATUS

6.2.15 IEC 61850 GOOSE INTEGERS

PATH: ACTUAL VALUES ÖØ STATUS ÖØ IEC 61850 GOOSE UINTEGERS

„ IEC 61850 UINT INPUT 1


„ GOOSE UINTEGERS 0
UINT INPUT 2
MESSAGE
0

UINT INPUT 16
MESSAGE
0

The G60 Generator Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.

The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received
via IEC 61850 GOOSE messages sent from other devices.

6.2.16 EGD PROTOCOL STATUS

a) FAST EXCHANGE
PATH: ACTUAL VALUES Ö STATUS ÖØ EGD PROTOCOL STATUS Ö PRODUCER STATUS Ö FAST EXCHANGE 1

„ FAST EXCHANGE 1 FAST EXCHANGE 1


„ SIGNATURE: 0
FAST EXCHANGE 1
MESSAGE
DATA LENGTH: 0

These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size
6
for the fast EGD exchange is displayed.

b) SLOW EXCHANGE
PATH: ACTUAL VALUES Ö STATUS ÖØ EGD PROTOCOL STATUS Ö PRODUCER STATUS ÖØ SLOW EXCHANGE 1(2)

„ SLOW EXCHANGE 1 SLOW EXCHANGE 1


„ SIGNATURE: 0
SLOW EXCHANGE 1
MESSAGE
DATA LENGTH: 0

These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size
for the slow EGD exchanges are displayed.

GE Multilin G60 Generator Protection System 6-9


6.2 STATUS 6 ACTUAL VALUES

6.2.17 TELEPROTECTION CHANNEL TESTS

PATH: ACTUAL VALUES Ö STATUS ÖØ TELEPROT CH TESTS

„ TELEPROT CH TESTS CHANNEL 1 Range: n/a, FAIL, OK


„ STATUS: n/a
CHANNEL 1 LOST Range: 1 to 65535 in steps of 1
MESSAGE
PACKETS: 1
CHANNEL 2 Range: n/a, FAIL, OK
MESSAGE
STATUS: n/a
CHANNEL 2 LOST Range: 1 to 65535 in steps of 1
MESSAGE
PACKETS: 1
VALIDITY OF CHANNEL Range: n/a, FAIL, OK
MESSAGE
CONFIGURATION: FAIL

The status information for two channels is shown here.


• CHANNEL 1 STATUS: This represents the receiver status of each channel. If the value is “OK”, teleprotection is
enabled and data is being received from the remote terminal; If the value is “FAIL”, teleprotection enabled and data is
not being received from the remote terminal. If “n/a”, teleprotection is disabled.
• CHANNEL 1 LOST PACKETS: Data is transmitted to the remote terminals in data packets at a rate of two packets per
cycle. The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the
COMMANDS ÖØ CLEAR RECORDS menu.

• VALIDITY OF CHANNEL CONFIGURATION: This value displays the current state of the communications channel
identification check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the
“FAIL” message will be displayed. The “N/A” value appears if the local relay ID is set to a default value of “0”, the chan-
nel is failed, or if the teleprotection inputs/outputs are not enabled.

6.2.18 ETHERNET SWITCH


6
PATH: ACTUAL VALUES Ö STATUS ÖØ ETHERNET SWITCH

„ ETHERNET SWITCH SWITCH 1 PORT Range: FAIL, OK


„ STATUS: OK
SWITCH 2 PORT Range: FAIL, OK
MESSAGE
STATUS: OK

SWITCH 6 PORT Range: FAIL, OK


MESSAGE
STATUS: OK
SWITCH MAC ADDRESS: Range: standard MAC address format
MESSAGE
00A0F40138FA

These actual values appear only if the G60 is ordered with an Ethernet switch module (type 2S or 2T). The status informa-
tion for the Ethernet switch is shown in this menu.
• SWITCH 1 PORT STATUS to SWITCH 6 PORT STATUS: These values represents the receiver status of each port on
the Ethernet switch. If the value is “OK”, then data is being received from the remote terminal; If the value is “FAIL”,
then data is not being received from the remote terminal or the port is not connected.
• SWITCH MAC ADDRESS: This value displays the MAC address assigned to the Ethernet switch module.

6-10 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.3 METERING

6.3METERING 6.3.1 METERING CONVENTIONS

a) UR CONVENTION FOR MEASURING POWER AND ENERGY


The following figure illustrates the conventions established for use in UR-series relays.

PER IEEE CONVENTIONS


Generator
PARAMETERS AS SEEN
G BY THE UR RELAY

Voltage +Q
VCG

WATTS = Positive IC
PF = Lead PF = Lag
VARS = Positive
PF = Lag IA
VAG -P +P
Current
IB IA
PF = Lag PF = Lead
UR RELAY
VBG -Q
M LOAD
- 1
Inductive Resistive S=VI
Generator

VCG
+Q
Voltage

PF = Lead PF = Lag
WATTS = Positive
IA
VARS = Negative IC
PF = Lead VAG -P +P
IA
Current
PF = Lag PF = Lead
IB
UR RELAY
VBG -Q

LOAD S=VI
-

Inductive
Resistive

Resistive
2
6
M LOAD

VCG +Q
Voltage
PF = Lead PF = Lag
IB
IA
WATTS = Negative
VAG
VARS = Negative -P +P
PF = Lag
IA
IC PF = Lag PF = Lead
Current
VBG
-Q
UR RELAY

G S=VI
- 3
Generator

Resistive

LOAD

VCG
+Q
Voltage IB
PF = Lead PF = Lag
WATTS = Negative IA
VARS = Positive VAG -P +P
PF = Lead
IC
IA
Current
PF = Lag PF = Lead

VBG -Q
UR RELAY

G 827239AC.CDR
- 4
S=VI
Generator

Figure 6–1: FLOW DIRECTION OF SIGNED VALUES FOR WATTS AND VARS

GE Multilin G60 Generator Protection System 6-11


6.3 METERING 6 ACTUAL VALUES

b) UR CONVENTION FOR MEASURING PHASE ANGLES


All phasors calculated by UR-series relays and used for protection, control and metering functions are rotating phasors that
maintain the correct phase angle relationships with each other at all times.
For display and oscillography purposes, all phasor angles in a given relay are referred to an AC input channel pre-selected
by the SETTINGS ÖØ SYSTEM SETUP ÖØ POWER SYSTEM ÖØ FREQUENCY AND PHASE REFERENCE setting. This setting
defines a particular AC signal source to be used as the reference.
The relay will first determine if any “Phase VT” bank is indicated in the source. If it is, voltage channel VA of that bank is
used as the angle reference. Otherwise, the relay determines if any “Aux VT” bank is indicated; if it is, the auxiliary voltage
channel of that bank is used as the angle reference. If neither of the two conditions is satisfied, then two more steps of this
hierarchical procedure to determine the reference signal include “Phase CT” bank and “Ground CT” bank.
If the AC signal pre-selected by the relay upon configuration is not measurable, the phase angles are not referenced. The
phase angles are assigned as positive in the leading direction, and are presented as negative in the lagging direction, to
more closely align with power system metering conventions. This is illustrated below.

-270o

-225o -315o

positive
angle
direction

-180o 0o
UR phase angle
reference

-135o -45o

6 -90o 827845A1.CDR

Figure 6–2: UR PHASE ANGLE MEASUREMENT CONVENTION

c) UR CONVENTION FOR MEASURING SYMMETRICAL COMPONENTS


The UR-series of relays calculate voltage symmetrical components for the power system phase A line-to-neutral voltage,
and symmetrical components of the currents for the power system phase A current. Owing to the above definition, phase
angle relations between the symmetrical currents and voltages stay the same irrespective of the connection of instrument
transformers. This is important for setting directional protection elements that use symmetrical voltages.
For display and oscillography purposes the phase angles of symmetrical components are referenced to a common refer-
ence as described in the previous sub-section.
WYE-CONNECTED INSTRUMENT TRANSFORMERS:
• ABC phase rotation: • ACB phase rotation:
1 1
V_0 = --- ( V AG + V BG + V CG ) V_0 = --- ( V AG + V BG + V CG )
3 3
1 1 2
2
V_1 = --- ( V AG + aV BG + a V CG ) V_1 = --- ( V AG + a V BG + aV CG )
3 3
1 1 2
2
V_2 = --- ( V AG + a V BG + aV CG ) V_2 = --- ( V AG + aV BG + a V CG )
3 3

The above equations apply to currents as well.

6-12 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.3 METERING

DELTA-CONNECTED INSTRUMENT TRANSFORMERS:


• ABC phase rotation: • ACB phase rotation:

V_0 = N/A V_0 = N/A


1 ∠– 30 ° 1 ∠30° 2
2
V_1 = -------------------- ( V AB + aV BC + a V CA ) V_1 = ----------------- ( V AB + a V BC + aV CA )
3 3 3 3
∠ 1 ∠– 30 ° 2
1 30° 2
V_2 = ----------------- ( V AB + a V BC + aV CA ) V_2 = -------------------- ( V AB + aV BC + a V CA )
3 3 3 3

The zero-sequence voltage is not measurable under the Delta connection of instrument transformers and is defaulted to
zero. The table below shows an example of symmetrical components calculations for the ABC phase rotation.
Table 6–1: SYMMETRICAL COMPONENTS CALCULATION EXAMPLE
SYSTEM VOLTAGES, SEC. V * VT RELAY INPUTS, SEC. V SYMM. COMP, SEC. V
CONN.
VAG VBG VCG VAB VBC VCA F5AC F6AC F7AC V0 V1 V2
13.9 76.2 79.7 84.9 138.3 85.4 WYE 13.9 76.2 79.7 19.5 56.5 23.3
∠0° ∠–125° ∠–250° ∠–313° ∠–97° ∠–241° ∠0° ∠–125° ∠–250° ∠–192° ∠–7° ∠–187°
UNKNOWN (only V1 and V2 84.9 138.3 85.4 DELTA 84.9 138.3 85.4 N/A 56.5 23.3
can be determined) ∠0° ∠–144° ∠–288° ∠0° ∠–144° ∠–288° ∠–54° ∠–234°

* The power system voltages are phase-referenced – for simplicity – to VAG and VAB, respectively. This, however, is a
relative matter. It is important to remember that the G60 displays are always referenced as specified under SETTINGS
ÖØ SYSTEM SETUP ÖØ POWER SYSTEM ÖØ FREQUENCY AND PHASE REFERENCE.
The example above is illustrated in the following figure.

SYSTEM VOLTAGES SYMMETRICAL


COMPONENTS
UR phase angle

6
reference

1
UR phase angle

A
reference

WYE VTs

C
B
0
2
U
re R ph
fe a
re se
nc a
e ng
le

A U
1
re R ph
fe a
re se
nc a
e ng
DELTA VTs le

C
B
2
827844A1.CDR

Figure 6–3: MEASUREMENT CONVENTION FOR SYMMETRICAL COMPONENTS

GE Multilin G60 Generator Protection System 6-13


6.3 METERING 6 ACTUAL VALUES

6.3.2 STATOR DIFFERENTIAL

PATH: ACTUAL VALUES ÖØ METERING ÖØ STATOR DIFFERENTIAL Ö STATOR DIFFERENTIAL

„ STATOR STATOR DIFF OPERATE


„ DIFFERENTIAL Iad: 0.00 A
STATOR DIFF RESTRAIN
MESSAGE
Iar: 0.00 A
STATOR DIFF OPERATE
MESSAGE
Ibd: 0.00 A
STATOR DIFF RESTRAIN
MESSAGE
Iar: 0.00 A
STATOR DIFF OPERATE
MESSAGE
Icd: 0.00 A
STATOR DIFF RESTRAIN
MESSAGE
Icr: 0.00 A

The phasors of differential and restraint currents are displayed in primary amperes.

6.3.3 SOURCES

a) MAIN MENU
PATH: ACTUAL VALUES ÖØ METERING ÖØ SOURCE SRC1

„ SOURCE SRC 1 „ PHASE CURRENT


See page 6–15.
„ „ SRC 1
„ GROUND CURRENT
MESSAGE See page 6–15.
„ SRC 1
6 MESSAGE
„ PHASE VOLTAGE
See page 6–16.
„ SRC 1
„ AUXILIARY VOLTAGE
MESSAGE See page 6–16.
„ SRC 1
„ POWER
MESSAGE See page 6–17.
„ SRC 1
„ ENERGY
MESSAGE See page 6–18.
„ SRC 1
„ FREQUENCY
MESSAGE See page 6–18.
„ SRC 1
„ CURRENT HARMONICS
MESSAGE See page 6–18.
„ SRC 1
„ VOLTAGE HARMONICS
MESSAGE See page 6–19.
„ SRC 1

This menu displays the metered values available for each source.
Metered values presented for each source depend on the phase and auxiliary VTs and phase and ground CTs assignments
for this particular source. For example, if no phase VT is assigned to this source, then any voltage, energy, and power val-
ues will be unavailable.

6-14 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.3 METERING

b) PHASE CURRENT METERING


PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 Ö PHASE CURRENT

„ PHASE CURRENT SRC 1 RMS Ia: 0.000


„ SRC 1 b: 0.000 c: 0.000 A
SRC 1 RMS Ia:
MESSAGE
0.000 A
SRC 1 RMS Ib:
MESSAGE
0.000 A
SRC 1 RMS Ic:
MESSAGE
0.000 A
SRC 1 RMS In:
MESSAGE
0.000 A
SRC 1 PHASOR Ia:
MESSAGE
0.000 A 0.0°
SRC 1 PHASOR Ib:
MESSAGE
0.000 A 0.0°
SRC 1 PHASOR Ic:
MESSAGE
0.000 A 0.0°
SRC 1 PHASOR In:
MESSAGE
0.000 A 0.0°
SRC 1 ZERO SEQ I0:
MESSAGE
0.000 A 0.0°
SRC 1 POS SEQ I1:
MESSAGE
0.000 A 0.0°

MESSAGE
SRC 1 NEG SEQ I2:
0.000 A 0.0°
6
The metered phase current values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).

c) GROUND CURRENT METERING


PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ GROUND CURRENT

„ GROUND CURRENT SRC 1 RMS Ig:


„ SRC 1 0.000 A
SRC 1 PHASOR Ig:
MESSAGE
0.000 A 0.0°
SRC 1 PHASOR Igd:
MESSAGE
0.000 A 0.0°

The metered ground current values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).

GE Multilin G60 Generator Protection System 6-15


6.3 METERING 6 ACTUAL VALUES

d) PHASE VOLTAGE METERING


PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 Ö PHASE VOLTAGE

„ PHASE VOLTAGE SRC 1 RMS Vag:


„ SRC 1 0.00 V
SRC 1 RMS Vbg:
MESSAGE
0.00 V
SRC 1 RMS Vcg:
MESSAGE
0.00 V
SRC 1 PHASOR Vag:
MESSAGE
0.000 V 0.0°
SRC 1 PHASOR Vbg:
MESSAGE
0.000 V 0.0°
SRC 1 PHASOR Vcg:
MESSAGE
0.000 V 0.0°
SRC 1 RMS Vab:
MESSAGE
0.00 V
SRC 1 RMS Vbc:
MESSAGE
0.00 V
SRC 1 RMS Vca:
MESSAGE
0.00 V
SRC 1 PHASOR Vab:
MESSAGE
0.000 V 0.0°
SRC 1 PHASOR Vbc:
MESSAGE
0.000 V 0.0°

6 MESSAGE
SRC 1 PHASOR Vca:
0.000 V 0.0°
SRC 1 ZERO SEQ V0:
MESSAGE
0.000 V 0.0°
SRC 1 POS SEQ V1:
MESSAGE
0.000 V 0.0°
SRC 1 NEG SEQ V2:
MESSAGE
0.000 V 0.0°

The metered phase voltage values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).

e) AUXILIARY VOLTAGE METERING


PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ AUXILIARY VOLTAGE

„ AUXILIARY VOLTAGE SRC 1 RMS Vx:


„ SRC 1 0.00 V
SRC 1 PHASOR Vx:
MESSAGE
0.000 V 0.0°

The metered auxiliary voltage values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was
programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).

6-16 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.3 METERING

f) POWER METERING
PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ POWER

„ POWER SRC 1 REAL POWER


„ SRC 1 3φ: 0.000 W
SRC 1 REAL POWER
MESSAGE
φa: 0.000 W
SRC 1 REAL POWER
MESSAGE
φb: 0.000 W
SRC 1 REAL POWER
MESSAGE
φc: 0.000 W
SRC 1 REACTIVE PWR
MESSAGE
3φ: 0.000 var
SRC 1 REACTIVE PWR
MESSAGE
φa: 0.000 var
SRC 1 REACTIVE PWR
MESSAGE
φb: 0.000 var
SRC 1 REACTIVE PWR
MESSAGE
φc: 0.000 var
SRC 1 APPARENT PWR
MESSAGE
3φ: 0.000 VA
SRC 1 APPARENT PWR
MESSAGE
φa: 0.000 VA
SRC 1 APPARENT PWR
MESSAGE
φb: 0.000 VA

MESSAGE
SRC 1 APPARENT PWR
φc: 0.000 VA
6
SRC 1 POWER FACTOR
MESSAGE
3φ: 1.000
SRC 1 POWER FACTOR
MESSAGE
φa: 1.000
SRC 1 POWER FACTOR
MESSAGE
φb: 1.000
SRC 1 POWER FACTOR
MESSAGE
φc: 1.000

The metered values for real, reactive, and apparent power, as well as power factor, are displayed in this menu. The "SRC
1" text will be replaced by whatever name was programmed by the user for the associated source (see SETTINGS ÖØ SYS-
TEM SETUP ÖØ SIGNAL SOURCES).

GE Multilin G60 Generator Protection System 6-17


6.3 METERING 6 ACTUAL VALUES

g) ENERGY METERING
PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ ENERGY

„ ENERGY SRC 1 POS WATTHOUR:


„ SRC 1 0.000 Wh
SRC 1 NEG WATTHOUR:
MESSAGE
0.000 Wh
SRC 1 POS VARHOUR:
MESSAGE
0.000 varh
SRC 1 NEG VARHOUR:
MESSAGE
0.000 varh

The metered values for real and reactive energy are displayed in this menu. The "SRC 1" text will be replaced by whatever
name was programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
Because energy values are accumulated, these values should be recorded and then reset immediately prior to changing
CT or VT characteristics.

h) FREQUENCY METERING
PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ FREQUENCY

„ FREQUENCY SRC 1 FREQUENCY:


„ SRC 1 0.00 Hz

The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES).
SOURCE FREQUENCY is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the SYSTEM SETUP ÖØ POWER SYSTEM settings). The signal used for frequency estimation is low-pass filtered. The
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
6
i) CURRENT HARMONICS AND THD METERING
PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ CURRENT HARMONICS

„ CURRENT HARMONICS SRC 1 THD Ia: 0.0


„ SRC 1 Ib: 0.0 Ic: 0.0%
SRC 1 2ND Ia: 0.0
MESSAGE
Ib: 0.0 Ic: 0.0%
SRC 1 3RD Ia: 0.0
MESSAGE
Ib: 0.0 Ic: 0.0%

SRC 1 25TH Ia: 0.0


MESSAGE
Ib: 0.0 Ic: 0.0%

The metered current harmonics values are displayed in this menu. The "SRC 1" text will be replaced by whatever name
was programmed by the user for the associated source (see SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES). Current
harmonics are measured for each source for the total harmonic distortion (THD) and 2nd to 25th harmonics per phase.

6-18 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.3 METERING

j) VOLTAGE HARMONICS AND THD METERING


PATH: ACTUAL VALUES ÖØ METERING Ö SOURCE SRC 1 ÖØ VOLTAGE HARMONICS

„ VOLTAGE HARMONICS SRC 1 THD Va: 0.0


„ SRC 1 Vb: 0.0 Vc: 0.0%
SRC 1 2ND Va: 0.0
MESSAGE
Vb: 0.0 Vc: 0.0%
SRC 1 3RD Va: 0.0
MESSAGE
Vb: 0.0 Vc: 0.0%

SRC 1 25TH Va: 0.0


MESSAGE
Vb: 0.0 Vc: 0.0%

The metered current harmonics values are displayed in this menu. The “SRC 1” text will be replaced by the programmed
name for the associated source (see the SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES menu).
To extract the 2nd to 25th voltage harmonics, each harmonic is computed on a per-phase basis, where:
N = 64 is the number of samples per cycle
ω0 = 2πf is the angular frequency based on the system frequency (50 or 60 Hz)
k = 1, 2,..., N – 1 is the index over one cycle for the Fast Fourier Transform (FFT)
m is the last sample number for the sliding window
h = 1, 2,..., 25 is the harmonic number
The short-time Fourier transform is applied to the unfiltered signal:
2
F real ( m, h ) = ---- ∑ ( f ( m – k ) ⋅ cos ( h ⋅ ω 0 ⋅ t ( k ) ) )
N
k
2
F imag ( m, h ) = ---- ∑ ( f ( m – k ) ⋅ sin ( h ⋅ ω 0 ⋅ t ( k ) ) ) (EQ 6.1)
N
k

F ampl ( m, h ) =
2
F real ( m, h ) + F imag ( m, h )
2 6
The harmonics are a percentage of the fundamental signal obtained as a ratio of harmonic amplitude to fundamental ampli-
tude multiplied by 100%. The total harmonic distortion (THD) is the ratio of the total harmonic content to the fundamental:

2 2 2
THD = F 2 + F 3 + … + F 25 (EQ 6.2)

Voltage harmonics are calculated only for Wye connected phase VTs. Ensure the SYSTEM SETUP Ö AC INPUTS ÖØ
VOLTAGE BANK F5 ÖØ PHASE VT XX CONNECTION setting is “Wye” to enable voltage harmonics metering.
NOTE

6.3.4 SYNCHROCHECK

PATH: ACTUAL VALUES ÖØ METERING ÖØ SYNCHROCHECK Ö SYNCHROCHECK 1(2)

„ SYNCHROCHECK 1 SYNCHROCHECK 1 DELTA


„ VOLT: 0.000 V
SYNCHROCHECK 1 DELTA
MESSAGE
PHASE: 0.0°
SYNCHROCHECK 1 DELTA
MESSAGE
FREQ: 0.00 Hz

The actual values menu for synchrocheck 2 is identical to that of synchrocheck 1. If a synchrocheck function setting is "Dis-
abled", the corresponding actual values menu item will not be displayed.

GE Multilin G60 Generator Protection System 6-19


6.3 METERING 6 ACTUAL VALUES

6.3.5 TRACKING FREQUENCY

PATH: ACTUAL VALUES ÖØ METERING ÖØ TRACKING FREQUENCY

„ TRACKING FREQUENCY TRACKING FREQUENCY:


„ 60.00 Hz

The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE setting in the SETTINGS ÖØ SYSTEM SETUP ÖØ POWER SYSTEM menu. Refer to the
Power System section of chapter 5 for additional details.

6.3.6 FREQUENCY RATE OF CHANGE

PATH: ACTUAL VALUES ÖØ METERING ÖØ FREQUENCY RATE OF CHANGE

„ FREQUENCY RATE FREQUENCY RATE OF


„ OF CHANGE CHANGE 1: 0.00 Hz/s
FREQUENCY RATE OF
MESSAGE
CHANGE 2: 0.00 Hz/s
FREQUENCY RATE OF
MESSAGE
CHANGE 3: 0.00 Hz/s
FREQUENCY RATE OF
MESSAGE
CHANGE 4: 0.00 Hz/s

The metered frequency rate of change for the frequency rate of change elements is shown here.

6.3.7 FREQUENCY OUT-OF-BAND ACCUMULATION

PATH: ACTUAL VALUES ÖØ METERING ÖØ FREQUENCY OOB ACCUMULATION

6 „ FREQUENCY OOB
„ ACCUMULATION
FREQUENCY OOB BAND 1
ACCUMULATION: 0.0%
FREQUENCY OOB BAND 2
MESSAGE
ACCUMULATION: 0.0%

FREQUENCY OOB BAND 7
MESSAGE
ACCUMULATION: 0.0%

The frequency out-of-band accumulation metered values are displayed to the nearest percent as a ratio of the present
accumulation to the user-specified limit. Note that this value can be greater than 100%.

6-20 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.3 METERING

6.3.8 FLEXELEMENTS™

PATH: ACTUAL VALUES ÖØ METERING ÖØ FLEXELEMENTS Ö FLEXELEMENT 1(16)

„ FLEXELEMENT 1 FLEXELEMENT 1
„ OpSig: 0.000 pu

The operating signals for the FlexElements™ are displayed in pu values using the following definitions of the base units.

Table 6–2: FLEXELEMENT™ BASE UNITS


dcmA BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
FIELD CURRENT IBASE = maximum value setting defined for the specific transducer input configured
FIELD GROUND CURRENT IBASE = 5 mA
FIELD GROUND FAULT BASE = 100%
LOCATION
FIELD GROUND INJECTED VBASE = 15 V
VOLTAGE
FIELD GROUND RESISTANCE RBASE = 250 KΩ
FIELD VOLTAGE VBASE = 500 V
FREQUENCY fBASE = 1 Hz
FREQUENCY RATE OF CHANGE df/dtBASE = 1 Hz/s
PHASE ANGLE ϕBASE = 360 degrees (see the UR angle referencing convention)
POWER FACTOR PFBASE = 1.00
RTDs BASE = 100°C
SENSITIVE DIR POWER PBASE = maximum value of 3 × VBASE × IBASE for the +IN and –IN inputs of the sources
(Sns Dir Power) configured for the sensitive power directional element(s).
SOURCE CURRENT IBASE = maximum nominal primary RMS value of the +IN and –IN inputs
SOURCE ENERGY
(Positive and Negative Watthours,
EBASE = 10000 MWh or MVAh, respectively
6
Positive and Negative Varhours)
SOURCE POWER PBASE = maximum value of VBASE × IBASE for the +IN and –IN inputs
SOURCE VOLTAGE VBASE = maximum nominal primary RMS value of the +IN and –IN inputs
STATOR DIFFERENTIAL IBASE = maximum primary RMS value of the +IN and –IN inputs
CURRENT (CT primary for source currents, and bus reference primary current for bus differential currents)
(Stator Diff Iar, Ibr, and Icr)
STATOR GROUND 3RD VBASE = Primary auxiliary voltage of the STATOR GROUND SOURCE
HARMONIC VOLTAGES
(Stator Gnd Vn/V0 3rd)
STATOR GROUND RESISTANCE RBASE = 10 KΩ
STATOR GROUND SUB- VBASE = nominal secondary voltage of auxiliary VT for the stator ground source
HARMONIC VOLTAGE
STATOR GROUND SUB- IBASE = ground CT primary current of stator ground source
HARMONIC CURRENT
STATOR RESTRAINING IBASE = maximum primary RMS value of the +IN and –IN inputs
CURRENT (CT primary for source currents, and bus reference primary current for bus differential currents)
(Stator Diff Iad, Ibd, and Icd)
SYNCHROCHECK VBASE = maximum primary RMS value of all the sources related to the +IN and –IN inputs
(Max Delta Volts)
VOLTS PER HERTZ BASE = 1.00 pu

GE Multilin G60 Generator Protection System 6-21


6.3 METERING 6 ACTUAL VALUES

6.3.9 IEC 61580 GOOSE ANALOG VALUES

PATH: ACTUAL VALUES ÖØ METERING ÖØ IEC 61850 GOOSE ANALOGS

„ IEC 61850 ANALOG INPUT 1


„ GOOSE ANALOGS 0.000
ANALOG INPUT 2
MESSAGE
0.000
ANALOG INPUT 3
MESSAGE
0.000

ANALOG INPUT 32
MESSAGE
0.000

The G60 Generator Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.

The IEC 61850 GGIO3 analog input data points are displayed in this menu. The GGIO3 analog data values are received
via IEC 61850 GOOSE messages sent from other devices.

6.3.10 SENSITIVE DIRECTIONAL POWER

PATH: ACTUAL VALUES ÖØ METERING ÖØ SENSITIVE DIRECTIONAL POWER

„ SENSITIVE DIRECTIONAL POWER 1


„ DIRECTIONAL POWER 3Φ: 0.000 W
DIRECTIONAL POWER 2
6 MESSAGE
3Φ: 0.000 W

The effective operating quantities of the sensitive directional power elements are displayed here. The display may be useful
to calibrate the feature by compensating the angular errors of the CTs and VTs with the use of the RCA and CALIBRATION
settings.

6.3.11 STATOR GROUND

PATH: ACTUAL VALUES ÖØ METERING ÖØ STATOR GROUND

„ STATOR GROUND STATOR GND 3RD HARM


„ VN: 0.000 V
STATOR GND 3RD HARM
MESSAGE
VN+V0: 0.000 V
STATOR GND 3RD HARM
MESSAGE
V0: 0.000 V

Magnitudes of the third harmonic components of the machine neutral point voltage (VN), the zero-sequence voltage at the
machine terminals (V0), and in the vector sum of the neutral point voltage and zero-sequence voltage (VN + V0) are avail-
able for display. The values are calculated for a signal source specified under the stator ground settings menu.
These readings may be useful when selecting a pickup and supervision setting for the 100% stator ground and third har-
monic neutral undervoltage protection elements.

6-22 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.3 METERING

6.3.12 SUB-HARMONIC STATOR GROUND

PATH: ACTUAL VALUES ÖØ METERING ÖØ SUB-HARMONIC STATOR GROUND

„ SUB-HARMONIC SH INJECTION VOLTS


„ STATOR GROUND 0.000 V
SH INJECTION AMPS
MESSAGE
0.000 A
SH CURRENT ANGLE
MESSAGE

STATOR GND. RESIST:
MESSAGE
> 500.000 kΩ

Actual values related to sub-harmonic stator ground protection are displayed in this menu.

6.3.13 FIELD GROUND

PATH: ACTUAL VALUES ÖØ METERING ÖØ FIELD GROUND

„ FIELD FIELD GROUND RESIST


„ GROUND 500 kΩ
FIELD VOLTAGE
MESSAGE
0.0 V
INJECTED VOLTAGE
MESSAGE
0.000 V
FAULT LOCATION
MESSAGE
–10%
FIELD GROUND
MESSAGE
CURRENT: 0.00 mA 6
FIELD CURRENT:
MESSAGE
0.000 A

Actual values related to field ground protection are displayed in this menu.

6.3.14 VOLTS PER HERTZ

PATH: ACTUAL VALUES ÖØ METERING ÖØ VOLTS PER HERTZ 1(2)

„ VOLTS PER HERTZ 1 VOLTS PER HERTZ 1:


„ 0.000 pu

The volts per hertz actual values are displayed in this menu.

6.3.15 RESTRICTED GROUND FAULT

PATH: ACTUAL VALUES ÖØ METERING ÖØ RESTRICTED GROUND FAULT CURRENTS Ö RESTRICTED GROUND FAULT 1(4)

„ RESTRICTED RGF 1 DIFF Igd:


„ GROUND FAULT 1 0.000 A
RGF 1 RESTR Igr:
MESSAGE
0.000 A

The differential and restraint current values for the restricted ground fault element are displayed in this menu.

GE Multilin G60 Generator Protection System 6-23


6.3 METERING 6 ACTUAL VALUES

6.3.16 PHASOR MEASUREMENT UNIT

PATH: ACTUAL VALUES ÖØ METERING ÖØ PHASOR MEASUREMENT UNIT Ö PMU 1(4)

„ PMU 1 PMU 1 VA: Range: Va or Vab per VT bank connection


„ 0.0000 kV, 0.00°
PMU 1 VB: Range: Va or Vab per VT bank connection
MESSAGE
0.0000 kV, 0.00°
PMU 1 VC: Range: Va or Vab per VT bank connection
MESSAGE
0.0000 kV, 0.00°
PMU 1 VX:
MESSAGE
0.0000 kV, 0.00°
PMU 1 V1:
MESSAGE
0.0000 kV, 0.00°
PMU 1 V2:
MESSAGE
0.0000 kV, 0.00°
PMU 1 V0: Range: Substituted with zero if delta-connected VTs.
MESSAGE
0.0000 kV, 0.00°
PMU 1 IA:
MESSAGE
0.0000 kA, 0.00°
PMU 1 IB:
MESSAGE
0.0000 kA, 0.00°
PMU 1 IC:
MESSAGE
0.0000 kA, 0.00°
PMU 1 IG:
MESSAGE
0.0000 kA, 0.00°
6 PMU 1 I1:
MESSAGE
0.0000 kA, 0.00°
PMU 1 I2:
MESSAGE
0.0000 kA, 0.00°
PMU 1 I0:
MESSAGE
0.0000 kA, 0.00°
PMU 1 FREQUENCY:
MESSAGE
0.0000 Hz
PMU 1 df/dt:
MESSAGE
0.0000 Hz/s
PMU 1 CONFIG CHANGE Range: 0 to 65535
MESSAGE
COUNTER: 0

The above actual values are displayed without the corresponding time stamp as they become available per the recording
rate setting. Also, the recording post-filtering setting is applied to these values.

6-24 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.3 METERING

6.3.17 TRANSDUCER INPUTS AND OUTPUTS

PATH: ACTUAL VALUES ÖØ METERING ÖØ TRANSDUCER I/O DCMA INPUTS Ö DCMA INPUT xx

„ DCMA INPUT xx DCMA INPUT xx


„ 0.000 mA

Actual values for each dcmA input channel that is enabled are displayed with the top line as the programmed channel ID
and the bottom line as the value followed by the programmed units.
PATH: ACTUAL VALUES ÖØ METERING ÖØ TRANSDUCER I/O RTD INPUTS Ö RTD INPUT xx

„ RTD INPUT xx RTD INPUT xx


„ -50 °C

Actual values for each RTD input channel that is enabled are displayed with the top line as the programmed channel ID and
the bottom line as the value.

GE Multilin G60 Generator Protection System 6-25


6.4 RECORDS 6 ACTUAL VALUES

6.4RECORDS 6.4.1 USER-PROGRAMMABLE FAULT REPORTS

PATH: ACTUAL VALUES ÖØ RECORDS Ö USER-PROGRAMMABLE FAULT REPORT

„ USER-PROGRAMMABLE NEWEST RECORD


„ FAULT REPORT NUMBER: 0
LAST CLEARED DATE:
MESSAGE
2002/8/11 14:23:57
LAST REPORT DATE:
MESSAGE
2002/10/09 08:25:27

This menu displays the user-programmable fault report actual values. See the User-Programmable Fault Report section in
chapter 5 for additional information on this feature.

6.4.2 EVENT RECORDS

PATH: ACTUAL VALUES ÖØ RECORDS ÖØ EVENT RECORDS

„ EVENT RECORDS EVENT: XXXX


„ RESET OP(PUSHBUTTON)

EVENT: 3 EVENT 3
MESSAGE
POWER ON DATE: 2000/07/14
EVENT: 2 EVENT 3
MESSAGE
POWER OFF TIME: 14:53:00.03405
EVENT: 1
MESSAGE Date and Time Stamps
EVENTS CLEARED

6 The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological order
from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record is
added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the
event trigger. Refer to the COMMANDS Ø CLEAR RECORDS menu for clearing event records.

6.4.3 OSCILLOGRAPHY

PATH: ACTUAL VALUES ÖØ RECORDS ÖØ OSCILLOGRAPHY

„ OSCILLOGRAPHY FORCE TRIGGER? Range: No, Yes


„ No
NUMBER OF TRIGGERS:
MESSAGE
0
AVAILABLE RECORDS:
MESSAGE
0
CYCLES PER RECORD:
MESSAGE
0.0
LAST CLEARED DATE:
MESSAGE
2000/07/14 15:40:16

This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
CYCLES PER RECORD value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog-
raphy section of chapter 5 for additional details.
A trigger can be forced here at any time by setting “Yes” to the FORCE TRIGGER? command. Refer to the COMMANDS ÖØ
CLEAR RECORDS menu for information on clearing the oscillography records.

6-26 G60 Generator Protection System GE Multilin


6 ACTUAL VALUES 6.4 RECORDS

6.4.4 DATA LOGGER

PATH: ACTUAL VALUES ÖØ RECORDS ÖØ DATA LOGGER

„ DATA LOGGER OLDEST SAMPLE TIME:


„ 2000/01/14 13:45:51
NEWEST SAMPLE TIME:
MESSAGE
2000/01/14 15:21:19

The OLDEST SAMPLE TIME represents the time at which the oldest available samples were taken. It will be static until the log
gets full, at which time it will start counting at the defined sampling rate. The NEWEST SAMPLE TIME represents the time the
most recent samples were taken. It counts up at the defined sampling rate. If the data logger channels are defined, then
both values are static.
Refer to the COMMANDS ÖØ CLEAR RECORDS menu for clearing data logger records.

6.4.5 PHASOR MEASUREMENT UNIT RECORDS

PATH: ACTUAL VALUES Ö RECORDS ÖØ PMU RECORDS

„ PMU NUMBER OF TRIGGERS: Range: 0 to 65535 in steps of 1


„ RECORDS 0
„ PMU 1
MESSAGE See below.
„ RECORDING

The number of triggers applicable to the phasor measurement unit recorder is indicated by the NUMBER OF TRIGGERS value.
The status of the phasor measurement unit recorder is indicated as follows:
PATH: ACTUAL VALUES Ö RECORDS ÖØ PMU RECORDS Ö PMU 1 RECORDING

„ PMU 1 PMU 1 FORCE TRIGGER: Range: No, Yes


„ RECORDING Yes

MESSAGE
PUM 1 AVAILABLE Range: 0 to 65535 in steps of 1 6
RECORDS: 0
PUM 1 SECONDS Range: 0 to 6553.5 in steps of 0.1
MESSAGE
PER RECORD: 0.0
PUM 1 LAST CLEARED: Range: date and time in format shown
MESSAGE
2005/07/14 015:40:16

GE Multilin G60 Generator Protection System 6-27


6.5 PRODUCT INFORMATION 6 ACTUAL VALUES

6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION

PATH: ACTUAL VALUES ÖØ PRODUCT INFO Ö MODEL INFORMATION

„ MODEL INFORMATION ORDER CODE LINE 1: Range: standard GE multilin order code format;
„ G60-E00-HCH-F8G-H6B example order code shown

ORDER CODE LINE 2: Range: standard GE multilin order code format


MESSAGE

ORDER CODE LINE 3: Range: standard GE multilin order code format


MESSAGE

ORDER CODE LINE 4: Range: standard GE multilin order code format


MESSAGE

SERIAL NUMBER: Range: standard GE multilin serial number format


MESSAGE

ETHERNET MAC ADDRESS Range: standard Ethernet MAC address format


MESSAGE
000000000000
MANUFACTURING DATE: Range: YYYY/MM/DD HH:MM:SS
MESSAGE
0
PMU FEATURE ACTIVE: Range: Yes, No
MESSAGE
No
CT/ VT ADVANCED DIAG Range: Yes, No
MESSAGE
ACTIVE: No
OPERATING TIME: Range: opearting time in HH:MM:SS
MESSAGE
0:00:00
LAST SETTING CHANGE: Range: YYYY/MM/DD HH:MM:SS
MESSAGE
1970/01/01 23:11:19
6
The order code, serial number, Ethernet MAC address, date and time of manufacture, and operating time are shown here.

6.5.2 FIRMWARE REVISIONS

PATH: ACTUAL VALUES ÖØ PRODUCT INFO ÖØ FIRMWARE REVISIONS

„ FIRMWARE REVISIONS G60 Relay Range: 0.00 to 655.35


„ REVISION: 5.9x Revision number of the application firmware.

MODIFICATION FILE Range: 0 to 65535 (ID of the MOD FILE)


MESSAGE Value is 0 for each standard firmware release.
NUMBER: 0
BOOT PROGRAM Range: 0.00 to 655.35
MESSAGE Revision number of the boot program firmware.
REVISION: 3.01
FRONT PANEL PROGRAM Range: 0.00 to 655.35
MESSAGE Revision number of faceplate program firmware.
REVISION: 0.08
COMPILE DATE: Range: Any valid date and time.
MESSAGE Date and time when product firmware was built.
2004/09/15 04:55:16
BOOT DATE: Range: Any valid date and time.
MESSAGE Date and time when the boot program was built.
2004/09/15 16:41:32

The shown data is illustrative only. A modification file number of 0 indicates that, currently, no modifications have been
installed.

6-28 G60 Generator Protection System GE Multilin


7 COMMANDS AND TARGETS 7.1 COMMANDS

7 COMMANDS AND TARGETS 7.1COMMANDS 7.1.1 COMMANDS MENU

COMMANDS

Ø
„„ COMMANDS
MESSAGE
„„ VIRTUAL INPUTS
„„ COMMANDS
MESSAGE
„„ CLEAR RECORDS
„„ COMMANDS
MESSAGE
„„ SET DATE AND TIME
„„ COMMANDS
MESSAGE
„„ PMU ONE-SHOT

The commands menu contains relay directives intended for operations personnel. All commands can be protected from
unauthorized access via the command password; see the Security section of chapter 5 for details. The following flash mes-
sage appears after successfully command entry:

COMMAND
EXECUTED

7.1.2 VIRTUAL INPUTS

PATH: COMMANDS Ö VIRTUAL INPUTS

„„ COMMANDS Virt Ip 1 Range: Off, On


„„ VIRTUAL INPUTS Off
Virt Ip 2 Range: Off, On
Off

MESSAGE
Virt Ip 64
Off
Range: Off, On
7
The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The
second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1).

GE Multilin G60 Generator Protection System 7-1


7.1 COMMANDS 7 COMMANDS AND TARGETS

7.1.3 CLEAR RECORDS

PATH: COMMANDS ÖØ CLEAR RECORDS

„„ COMMANDS CLEAR USER FAULT Range: No, Yes


„„ CLEAR RECORDS REPORTS? No
CLEAR EVENT RECORDS? Range: No, Yes
No
CLEAR OSCILLOGRAPHY? Range: No, Yes
No
CLEAR DATA LOGGER? Range: No, Yes
No
CLEAR ENERGY? Range: No, Yes
No
CLEAR UNAUTHORIZED Range: No, Yes
ACCESS? No
CLEAR DIRECT I/O Range: No, Yes. Valid only for units with Direct Input/
COUNTERS? No Output module.

CLEAR TELEPROTECT Range: No, Yes


COUNTERS? No
CLEAR FREQ OOB Range: No, Yes
ACCUMULATORS? No
PRESET FREQ OOB Range: No, Yes
ACCUMULATORS? No
CLEAR ALL RELAY Range: No, Yes
RECORDS? No

This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-
mand setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to “No”.

7.1.4 SET DATE AND TIME

7 PATH: COMMANDS ÖØ SET DATE AND TIME

„„ COMMANDS SET DATE AND TIME: (YYYY/MM/DD HH:MM:SS)


„„ SET DATE AND TIME 2000/01/14 13:47:03

The date and time can be entered here via the faceplate keypad only if the IRIG-B or SNTP signal is not in use. The time
setting is based on the 24-hour clock. The complete date, as a minimum, must be entered to allow execution of this com-
mand. The new time will take effect at the moment the ENTER key is clicked.

7-2 G60 Generator Protection System GE Multilin


7 COMMANDS AND TARGETS 7.1 COMMANDS

7.1.5 RELAY MAINTENANCE

PATH: COMMANDS ÖØ RELAY MAINTENANCE

„„ COMMANDS PERFORM LAMPTEST? Range: No, Yes


„„ RELAY MAINTENANCE No
UPDATE ORDER CODE? Range: No, Yes
No
SERVICE COMMAND: Range: 0, 101
0

This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are activated
by changing a command setting to “Yes” and pressing the ENTER key. The command setting will then automatically revert
to “No”. The service command is activated by entering a numerical code and pressing the ENTER key.
The PERFORM LAMPTEST command turns on all faceplate LEDs and display pixels for a short duration. The UPDATE
ORDER CODE command causes the relay to scan the backplane for the hardware modules and update the order code to
match. If an update occurs, the following message is shown.
UPDATING...
PLEASE WAIT
There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER
CODE NOT UPDATED message will be shown.

The SERVICE COMMAND is used to perform specific G60 service actions. Presently, there is only one service action avail-
able. Code “101” is used to clear factory diagnostic information stored in the non-volatile memory. If a code other than “101”
is entered, the command will be ignored and no actions will be taken. Various self-checking diagnostics are performed in
the background while the G60 is running, and diagnostic information is stored on the non-volatile memory from time to time
based on the self-checking result. Although the diagnostic information is cleared before the G60 is shipped from the factory,
the user may want to clear the diagnostic information for themselves under certain circumstances. For example, it may be
desirable to clear diagnostic information after replacement of hardware. Once the diagnostic information is cleared, all self-
checking variables are reset to their initial state and diagnostics will restart from scratch.

GE Multilin G60 Generator Protection System 7-3


7.1 COMMANDS 7 COMMANDS AND TARGETS

7.1.6 PHASOR MEASUREMENT UNIT ONE-SHOT

PATH: COMMANDS ÖØ PMU ONE-SHOT

„„ COMMANDS PMU ONE-SHOT Range: Enabled, Disabled


„„ PMU ONE-SHOT FUNCTION: Disabled
PMU ONE-SHOT Range: 0 to nominal frequency – 1 in steps of 1
SEQUENCE NUMBER: 0
PMU ONE-SHOT TIME: Range: 24h time format
2005/06/14 7:58:35

This feature allows pre-scheduling a PMU measurement at a specific point in time. This functionality can be used to test for
accuracy of the PMU, and for manual collection of synchronized measurements through the system, as explained below.
When enabled, the function continuously compares the present time with the pre-set PMU ONE-SHOT TIME. When the two
times match, the function compares the present sequence number of the measured synchrophasors with the pre-set PMU
ONE-SHOT SEQUENCE NUMBER. When the two numbers match, the function freezes the synchrophasor actual values and
the corresponding protocol data items for 30 seconds. This allows manual read-out of the synchrophasor values for the pre-
set time and pre-set sequence number (via the faceplate display, supported communication protocols such as Modbus or
DNP, and the EnerVista UR Setup software).
When freezing the actual values the function also asserts a PMU ONE-SHOT OP FlexLogic™ operand. This operand may be
configured to drive an output contact and trigger an external measuring device such as a digital scope with the intent to ver-
ify the accuracy of the PMU under test.
With reference to the figure below, the PMU one-shot function (when enabled) controls three FlexLogic™ operands:
• The PMU ONE-SHOT EXPIRED operand indicates that the one-shot operation has been executed, and the present time
is at least 30 seconds past the scheduled one-shot time.
• The PMU ONE-SHOT PENDING operand indicates that the one-shot operation is pending; that is, the present time is
before the scheduled one-shot time.
• The PMU ONE-SHOT OP operand indicates the one-shot operation and remains asserted for 30 seconds afterwards.
When the function is disabled, all three operands are de-asserted. The one-shot function applies to all logical PMUs of a
given G60 relay.

Figure 7–1: PMU ONE-SHOT FLEXLOGIC™ OPERANDS


TESTING ACCURACY OF THE PMU:
The one-shot feature can be used to test accuracy of the synchrophasor measurement. GPS-synchronized tests sets per-
form a similar function to PMUs: instead of measuring the phasor from physical signals with respect to the externally pro-
vided time reference, they produce the physical signals with respect to the externally provided time reference, given the
desired phasor values. Therefore the GPS-synchronized test sets cannot be automatically assumed more accurate then
the PMUs under test. This calls for a method to verify both the measuring device (PMU) and the source of signal (test set).
With reference to the figure below, the one-shot feature could be configured to trigger a high-accuracy scope to capture
both the time reference signal (rising edge of the 1 pps signal of the IRIG-B time reference), and the measured waveform.
The high-accuracy high-sampling rate record of the two signals captured by the scope can be processed using digital tools
to verify the magnitude and phase angle with respect to the time reference signal. As both the time reference and the mea-

7-4 G60 Generator Protection System GE Multilin


7 COMMANDS AND TARGETS 7.1 COMMANDS

sured signals are raw inputs to the PMU under test, their independently captured record, processed using third-party soft-
ware, is a good reference point for accuracy calculations. Such a record proves useful when discussing the test results, and
should be retained as a part of the testing documentation.
Note that the PMU under such test does not have to be connected to a real GPS receiver as the accuracy is measured with
respect to the timing reference provided to the PMU and not to the absolute UTC time. Therefore a simple IRIG-B genera-
tor could be used instead. Also, the test set does not have to support GPS synchronization. Any stable signal source can
be used. If both the PMU under test and the test set use the timing reference, they should be driven from the same IRIG-B
signal: either the same GPS receiver or IRIG-B generator. Otherwise, the setpoints of the test set and the PMU measure-
ments should not be compared as they are referenced to different time scales.

Figure 7–2: USING THE PMU ONE-SHOT FEATURE TO TEST SYNCHROPHASOR MEASUREMENT ACCURACY
COLLECTING SYNCHRONIZED MEASUREMENTS AD HOC:
The one-shot feature can be used for ad hoc collection of synchronized measurements in the network. Two or more PMU
can be pre-scheduled to freeze their measurements at the same time. When frozen the measurements could be collected
using EnerVista UR Setup or a protocol client.

GE Multilin G60 Generator Protection System 7-5


7.2 TARGETS 7 COMMANDS AND TARGETS

7.2TARGETS 7.2.1 TARGETS MENU

TARGETS

Ø
DIGITAL ELEMENT 1: Displayed only if targets for this element are active.
MESSAGE Example shown.
LATCHED
DIGITAL ELEMENT 48: Displayed only if targets for this element are active.
MESSAGE Example shown.
LATCHED

MESSAGE

The status of any active targets will be displayed in the targets menu. If no targets are active, the display will read NO
ACTIVE TARGETS:

7.2.2 TARGET MESSAGES

When there are no active targets, the first target to become active will cause the display to immediately default to that mes-
sage. If there are active targets and the user is navigating through other messages, and when the default message timer
times out (i.e. the keypad has not been used for a determined period of time), the display will again default back to the tar-
get message.
The range of variables for the target messages is described below. Phase information will be included if applicable. If a tar-
get message status changes, the status with the highest priority will be displayed.

Table 7–1: TARGET MESSAGE PRIORITY STATUS


PRIORITY ACTIVE STATUS DESCRIPTION
1 OP element operated and still picked up
2 PKP element picked up and timed out
3 LATCHED element had operated but has dropped out

If a self test error is detected, a message appears indicating the cause of the error. For example UNIT NOT PROGRAMMED
indicates that the minimal relay settings have not been programmed.
7
7.2.3 RELAY SELF-TESTS

a) DESCRIPTION
The relay performs a number of self-test diagnostic checks to ensure device integrity. The two types of self-tests (major and
minor) are listed in the tables below. When either type of self-test error occurs, the Trouble LED Indicator will turn on and a
target message displayed. All errors record an event in the event recorder. Latched errors can be cleared by pressing the
RESET key, providing the condition is no longer present.
Major self-test errors also result in the following:
• The critical fail relay on the power supply module is de-energized.
• All other output relays are de-energized and are prevented from further operation.
• The faceplate In Service LED indicator is turned off.
• A RELAY OUT OF SERVICE event is recorded.

7-6 G60 Generator Protection System GE Multilin


7 COMMANDS AND TARGETS 7.2 TARGETS

b) MAJOR SELF-TEST ERROR MESSAGES


The major self-test errors are listed and described below.

MODULE FAILURE___:
Contact Factory (xxx)

• Latched target message: Yes.


• Description of problem: Module hardware failure detected.
• How often the test is performed: Module dependent.
• What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod-
ule (for example, F8L).

INCOMPATIBLE H/W:
Contact Factory (xxx)
• Latched target message: Yes.
• Description of problem: One or more installed hardware modules is not compatible with the G60 order code.
• How often the test is performed: Module dependent.
• What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod-
ule (for example, F8L).

EQUIPMENT MISMATCH:
with 2nd line detail
• Latched target message: No.
• Description of problem: The configuration of modules does not match the order code stored in the G60.
• How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every five sec-
onds.
• What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If
the problem persists, contact the factory.

FLEXLOGIC ERROR:
with 2nd line detail 7
• Latched target message: No.
• Description of problem: A FlexLogic™ equation is incorrect.
• How often the test is performed: The test is event driven, performed whenever FlexLogic™ equations are modified.
• What to do: Finish all equation editing and use self tests to debug any errors.

UNIT NOT PROGRAMMED:


Check Settings
• Latched target message: No.
• Description of problem: The PRODUCT SETUP ÖØ INSTALLATION Ö RELAY SETTINGS setting indicates the G60 is not pro-
grammed.
• How often the test is performed: On power up and whenever the PRODUCT SETUP ÖØ INSTALLATION Ö RELAY SETTINGS
setting is altered.
• What to do: Program all settings and then set PRODUCT SETUP ÖØ INSTALLATION Ö RELAY SETTINGS to “Programmed”.

GE Multilin G60 Generator Protection System 7-7


7.2 TARGETS 7 COMMANDS AND TARGETS

c) MINOR SELF-TEST ERROR MESSAGES


Most of the minor self-test errors can be disabled. Refer to the settings in the User-programmable self-tests section in the
Settings chapter for additional details.

IEC 61850 DATA SET:


LLN0 GOOSE# Error
• Latched target message: No.
• Description of problem: A data item in a configurable GOOSE data set is not supported by the G60 order code.
• How often the test is performed: On power up.
• What to do: Verify that all the items in the GOOSE data set are supported by the G60. The EnerVista UR Setup soft-
ware will list the valid items. An IEC61850 client will also show which nodes are available for the G60.

IEC 61850 DATA SET:


LLN0 BR# Error
• Latched target message: No.
• Description of problem: A data item in a configurable report data set is not supported by the G60 order code.
• How often the test is performed: On power up.
• What to do: Verify that all the items in the configurable report data set are supported by the G60. The EnerVista UR
Setup software will list the valid items. An IEC61850 client will also show which nodes are available for the G60.

MAINTENANCE ALERT:
Replace Battery
• Latched target message: Yes.
• Description of problem: The battery is not functioning.
• How often the test is performed: The battery is monitored every five seconds. The error message is displayed after 60
seconds if the problem persists.
• What to do: Replace the battery located in the power supply module (1H or 1L).

MAINTENANCE ALERT:
7 Direct I/O Ring Break
• Latched target message: No.
• Description of problem: Direct input and output settings are configured for a ring, but the connection is not in a ring.
• How often the test is performed: Every second.
• What to do: Check direct input and output configuration and wiring.

MAINTENANCE ALERT:
ENET MODULE OFFLINE
• Latched target message: No.
• Description of problem: The G60 has failed to detect the Ethernet switch.
• How often the test is performed: Monitored every five seconds. An error is issued after five consecutive failures.
• What to do: Check the G60 device and switch IP configuration settings. Check for incorrect UR port (port 7) settings on
the Ethernet switch. Check the power to the switch.

MAINTENANCE ALERT:
ENET PORT # OFFLINE

7-8 G60 Generator Protection System GE Multilin


7 COMMANDS AND TARGETS 7.2 TARGETS

• Latched target message: No.


• Description of problem: The Ethernet connection has failed for the specified port.
• How often the test is performed: Every five seconds.
• What to do: Check the Ethernet port connection on the switch.

MAINTENANCE ALERT:
**Bad IRIG-B Signal**

• Latched target message: No.


• Description of problem: A bad IRIG-B input signal has been detected.
• How often the test is performed: Monitored whenever an IRIG-B signal is received.
• What to do: Ensure the following:
– The IRIG-B cable is properly connected.
– Proper cable functionality (that is, check for physical damage or perform a continuity test).
– The IRIG-B receiver is functioning.
– Check the input signal level (it may be less than specification).
If none of these apply, then contact the factory.

MAINTENANCE ALERT:
Port ## Failure

• Latched target message: No.


• Description of problem: An Ethernet connection has failed.
• How often the test is performed: Monitored every five seconds.
• What to do: Check Ethernet connections. Port 1 is the primary port and port 2 is the secondary port.

MAINTENANCE ALERT:
SNTP Failure

• Latched target message: No.


• Description of problem: The SNTP server is not responding.
7
• How often the test is performed: Every 10 to 60 seconds.
• What to do: Check SNTP configuration and network connections.

MAINTENANCE ALERT:
4L Discrepancy

• Latched target message: No.


• Description of problem: A discrepancy has been detected between the actual and desired state of a latching contact
output of an installed type “4L” module.
• How often the test is performed: Upon initiation of a contact output state change.
• What to do: Verify the state of the output contact and contact the factory if the problem persists.

MAINTENANCE ALERT:
GGIO Ind xxx oscill

• Latched target message: No.


• Description of problem: A data item in a configurable GOOSE data set is oscillating.

GE Multilin G60 Generator Protection System 7-9


7.2 TARGETS 7 COMMANDS AND TARGETS

• How often the test is performed: Upon scanning of each configurable GOOSE data set.
• What to do: The “xxx” text denotes the data item that has been detected as oscillating. Evaluate all logic pertaining to
this item.

DIRECT I/O FAILURE:


COMM Path Incomplete

• Latched target message: No.


• Description of problem: A direct device is configured but not connected.
• How often the test is performed: Every second.
• What to do: Check direct input and output configuration and wiring.

REMOTE DEVICE FAIL:


COMM Path Incomplete

• Latched target message: No.


• Description of problem: One or more GOOSE devices are not responding.
• How often the test is performed: Event driven. The test is performed when a device programmed to receive GOOSE
messages stops receiving. This can be from 1 to 60 seconds, depending on GOOSE packets.
• What to do: Check GOOSE setup.

TEMP MONITOR:
OVER TEMPERATURE

• Latched target message: Yes.


• Description of problem: The ambient temperature is greater than the maximum operating temperature (+80°C).
• How often the test is performed: Every hour.
• What to do: Remove the G60 from service and install in a location that meets operating temperature standards.

UNEXPECTED RESTART:
Press “RESET” key
• Latched target message: Yes.
7 • Description of problem: Abnormal restart from modules being removed or inserted while the G60 is powered-up, when
there is an abnormal DC supply, or as a result of internal relay failure.
• How often the test is performed: Event driven.
• What to do: Contact the factory.

d) EXTERNAL DEVICE SELF-TEST ERROR MESSAGES


The major self-test errors are listed and described below.

GPM-F FAILURE:
TROUBLE 01
• Latched target message: No.
• Description of problem: The G60 detects loss of communication with the field ground module on the RS485 link.
• How often the test is performed: Every five seconds.
• What to do: Check the field ground module and its RS485 connection to G60.

7-10 G60 Generator Protection System GE Multilin


7 COMMANDS AND TARGETS 7.2 TARGETS

GPM-F FAILURE:
TROUBLE 02

• Latched target message: No.


• Description of problem: The field ground module reports trouble with injected low frequency signal voltage level or fre-
quency.
• How often the test is performed: Every second.
• What to do: Verify that the injection voltage actual value in the G60 is around 15 V. If the message remains, cycle
power the field ground module. If the problem persists, then contact the factory.

GPM-F FAILURE:
TROUBLE 03

• Latched target message: No.


• Description of problem: Field ground module reports trouble with its circuitry.
• How often the test is performed: Every second.
• What to do: Verify that the actual values in G60 are within accepted values. Cycle power to the field ground module. If
the problem remains, then contact the factory.

GPM-F FAILURE:
TROUBLE 04
• Latched target message: No.
• Description of problem: The setting for field ground module injection frequency does not match the injection frequency
reported by the module.
• How often the test is performed: Every second.
• What to do: The field ground module may be connected to another G60 through its alternate RS485 port and it might
be receiving another frequency setting. Please ensure both G60 devices connected to the same field ground module
have the same injection frequency setting.

GPM-F FAILURE:
TROUBLE 05

• Latched target message: No. 7


• Description of problem: The hardware revision of the field ground module is not supported by the present revision of
G60. Please contact the factory.
• How often the test is performed: Every second.
• What to do: Check the hardware revision of the field ground module in the G60 actual values and contact the factory.

GPM-F FAILURE:
TROUBLE 06
• Latched target message: No.
• Description of problem: The firmware revision of the field ground module is not supported by the present revision of
G60 device. Please contact the factory.
• How often the test is performed: Every second.
• What to do: Check the firmware revision of the field ground module in the G60 actual values and contact the factory.

GE Multilin G60 Generator Protection System 7-11


7.2 TARGETS 7 COMMANDS AND TARGETS

7-12 G60 Generator Protection System GE Multilin


8 SECURITY 8.1 PASSWORD SECURITY

8 SECURITY 8.1PASSWORD SECURITY 8.1.1 OVERVIEW

Two levels of password security are provided via the ACCESS LEVEL setting: command and setting. The factory service level
is not available and intended for factory use only.
The following operations are under command password supervision:
• Changing the state of virtual inputs.
• Clearing the event records.
• Clearing the oscillography records.
• Changing the date and time.
• Clearing energy records.
• Clearing the data logger.
• Clearing the user-programmable pushbutton states.
The following operations are under setting password supervision:
• Changing any setting.
• Test mode operation.
The command and setting passwords are defaulted to “0” when the relay is shipped from the factory. When a password is
set to “0”, the password security feature is disabled.
The G60 supports password entry from a local or remote connection.
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear
communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the G60, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password must be used.
The PASSWORD ACCESS EVENTS settings allows recording of password access events in the event recorder.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command ses-
sions are initiated by the user through the EnerVista UR Setup software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic™ operands.
• ACCESS LOC SETG OFF: Asserted when local setting access is disabled.
• ACCESS LOC SETG ON: Asserted when local setting access is enabled.
• ACCESS LOC CMND OFF: Asserted when local command access is disabled.
• ACCESS LOC CMND ON: Asserted when local command access is enabled.
• ACCESS REM SETG OFF: Asserted when remote setting access is disabled.
8
• ACCESS REM SETG ON: Asserted when remote setting access is enabled.
• ACCESS REM CMND OFF: Asserted when remote command access is disabled.
• ACCESS REM CMND ON: Asserted when remote command access is enabled.
The appropriate events are also logged in the Event Recorder as well. The FlexLogic™ operands and events are updated
every five seconds.
A command or setting write operation is required to update the state of all the remote and local security operands
shown above.
NOTE

GE Multilin G60 Generator Protection System 8-1


8.1 PASSWORD SECURITY 8 SECURITY

8.1.2 PASSWORD SECURITY MENU

PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY

„ SECURITY ACCESS LEVEL: Range: Restricted, Command, Setting,


„ Restricted Factory Service (for factory use only)

„ CHANGE LOCAL
MESSAGE See page 8–2.
„ PASSWORDS
„ ACCESS
MESSAGE See page 8–3.
„ SUPERVISION
„ DUAL PERMISSION
MESSAGE See page 8–4.
„ SECURITY ACCESS
PASSWORD ACCESS Range: Disabled, Enabled
MESSAGE
EVENTS: Disabled

8.1.3 LOCAL PASSWORDS

PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ CHANGE LOCAL PASSWORDS

„ CHANGE LOCAL CHANGE COMMAND Range: No, Yes


„ PASSWORDS PASSWORD: No
CHANGE SETTING Range: No, Yes
MESSAGE
PASSWORD: No
ENCRYPTED COMMAND Range: 0 to 9999999999
MESSAGE Note: ---------- indicates no password
PASSWORD: ----------
ENCRYPTED SETTING Range: 0 to 9999999999
MESSAGE Note: ---------- indicates no password
PASSWORD: ----------

Proper password codes are required to enable each access level. A password consists of 1 to 10 numerical characters.
When a CHANGE COMMAND PASSWORD or CHANGE SETTING PASSWORD setting is programmed to “Yes” via the front panel
interface, the following message sequence is invoked:
1. ENTER NEW PASSWORD: ____________.
2. VERIFY NEW PASSWORD: ____________.
3. NEW PASSWORD HAS BEEN STORED.
To gain write access to a “Restricted” setting, program the ACCESS LEVEL setting in the main security menu to “Setting” and
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access will be allowed. Accessibility automatically reverts to the “Restricted” level according
to the access level timeout setting values.
8 If an entered password is lost (or forgotten), consult the factory with the corresponding ENCRYPTED PASSWORD.
If the setting and command passwords are identical, then this one password allows access to both com-
mands and settings.
NOTE

8-2 G60 Generator Protection System GE Multilin


8 SECURITY 8.1 PASSWORD SECURITY

8.1.4 REMOTE PASSWORDS

The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the
Settings > Product Setup > Password Security menu item to open the remote password settings window.

Figure 8–1: REMOTE PASSWORD SETTINGS WINDOW


Proper passwords are required to enable each command or setting level access. A command or setting password consists
of 1 to 10 numerical characters and are initially programmed to “0”. The following procedure describes how the set the com-
mand or setting password.
1. Enter the new password in the Enter New Password field.
2. Re-enter the password in the Confirm New Password field.
3. Click the Change button. This button will not be active until the new password matches the confirmation password.
4. If the original password is not “0”, then enter the original password in the Enter Password field and click the Send
Password to Device button.

5. The new password is accepted and a value is assigned to the ENCRYPTED PASSWORD item.

If a command or setting password is lost (or forgotten), consult the factory with the corresponding Encrypted Password 8
value.

8.1.5 ACCESS SUPERVISION

PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ ACCESS SUPERVISION

„ ACCESS „ ACCESS LEVEL


„ SUPERVISION „ TIMEOUTS
INVALID ATTEMPTS Range: 2 to 5 in steps of 1
MESSAGE
BEFORE LOCKOUT: 3
PASSWORD LOCKOUT Range: 5 to 60 minutes in steps of 1
MESSAGE
DURATION: 5 min

GE Multilin G60 Generator Protection System 8-3


8.1 PASSWORD SECURITY 8 SECURITY

The following access supervision settings are available.


• INVALID ATTEMPTS BEFORE LOCKOUT: This setting specifies the number of times an incorrect password can be
entered within a three-minute time span before lockout occurs. When lockout occurs, the LOCAL ACCESS DENIED or
REMOTE ACCESS DENIED FlexLogic™ operands are set to “On”. These operands are returned to the “Off” state upon
expiration of the lockout.
• PASSWORD LOCKOUT DURATION: This setting specifies the time that the G60 will lockout password access after
the number of invalid password entries specified by the INVALID ATTEMPS BEFORE LOCKOUT setting has occurred.
The G60 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing
a password-protected level of the relay (either settings or commands), the UNAUTHORIZED ACCESS FlexLogic™ operand is
asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be
used to protect against both unauthorized and accidental access attempts.
The UNAUTHORIZED ACCESS operand is reset with the COMMANDS ÖØ CLEAR RECORDS ÖØ RESET UNAUTHORIZED
ALARMS command. Therefore, to apply this feature with security, the command level should be password-protected. The
operand does not generate events or targets.
If events or targets are required, the UNAUTHORIZED ACCESS operand can be assigned to a digital element programmed
with event logs or targets enabled.
The access level timeout settings are shown below.
PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ ACCESS SUPERVISION Ö ACCESS LEVEL TIMEOUTS

„ ACCESS LEVEL COMMAND LEVEL ACCESS Range: 5 to 480 minutes in steps of 1


„ TIMEOUTS TIMEOUT: 5 min
SETTING LEVEL ACCESS Range: 5 to 480 minutes in steps of 1
MESSAGE
TIMEOUT: 30 min

These settings allow the user to specify the length of inactivity required before returning to the restricted access level. Note
that the access level will set as restricted if control power is cycled.
• COMMAND LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.
• SETTING LEVEL ACCESS TIMEOUT: This setting specifies the length of inactivity (no local or remote access)
required to return to restricted access from the command password level.

8.1.6 DUAL PERMISSION SECURITY ACCESS

PATH: SETTINGS Ö PRODUCT SETUP Ö SECURITY ÖØ DUAL PERMISSION SECURITY ACCESS

„ DUAL PERMISSION LOCAL SETTING AUTH: Range: selected FlexLogic™ operands (see below)
„ SECURITY ACCESS On
REMOTE SETTING AUTH: Range: FlexLogic™ operand
MESSAGE
On
8 MESSAGE
ACCESS AUTH Range: 5 to 480 minutes in steps of 1
TIMEOUT: 30 min.

The dual permission security access feature provides a mechanism for customers to prevent unauthorized or unintended
upload of settings to a relay through the local or remote interfaces interface.
The following settings are available through the local (front panel) interface only.
• LOCAL SETTING AUTH: This setting is used for local (front panel or RS232 interface) setting access supervision.
Valid values for the FlexLogic™ operands are either “On” (default) or any physical “Contact Input ~~ On” value.
If this setting is “On“, then local setting access functions as normal; that is, a local setting password is required. If this
setting is any contact input on FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing
the local setting password to gain setting access.

8-4 G60 Generator Protection System GE Multilin


8 SECURITY 8.1 PASSWORD SECURITY

If setting access is not authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the UNAUTHORIZED ACCESS message is displayed on the front panel.
• REMOTE SETTING AUTH: This setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to pro-
viding the remote setting password to gain setting access.
• ACCESS AUTH TIMEOUT: This setting represents the timeout delay for local setting access. This setting is applicable
when the LOCAL SETTING AUTH setting is programmed to any operand except “On”. The state of the FlexLogic™ oper-
and is continuously monitored for an off-to-on transition. When this occurs, local access is permitted and the timer pro-
grammed with the ACCESS AUTH TIMEOUT setting value is started. When this timer expires, local setting access is
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the time-
out is restarted. The status of this timer is updated every 5 seconds.
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the Settings > Product
Setup > Security menu item to display the security settings window.

The Remote Settings Authorization setting is used for remote (Ethernet or RS485 interfaces) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required). If this setting is “Off”, then remote setting access is blocked even if the correct remote setting password is pro-
vided. If this setting is any other FlexLogic™ operand, then the operand must be asserted (set as on) prior to providing the
remote setting password to gain setting access.
The Access Authorization Timeout setting represents the timeout delay remote setting access. This setting is applicable
when the Remote Settings Authorization setting is programmed to any operand except “On” or “Off”. The state of the
FlexLogic™ operand is continuously monitored for an off-to-on transition. When this occurs, remote setting access is per-
mitted and the timer programmed with the Access Authorization Timeout setting value is started. When this timer
expires, remote setting access is immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™
operand is detected, the timeout is restarted. The status of this timer is updated every 5 seconds.

GE Multilin G60 Generator Protection System 8-5


8.2 SETTINGS SECURITY 8 SECURITY

8.2SETTINGS SECURITY 8.2.1 SETTINGS TEMPLATES

Setting file templates simplify the configuration and commissioning of multiple relays that protect similar assets. An exam-
ple of this is a substation that has ten similar feeders protected by ten UR-series F60 relays.
In these situations, typically 90% or greater of the settings are identical between all devices. The templates feature allows
engineers to configure and test these common settings, then lock them so they are not available to users. For example,
these locked down settings can be hidden from view for field engineers, allowing them to quickly identify and concentrate
on the specific settings.
The remaining settings (typically 10% or less) can be specified as editable and be made available to field engineers install-
ing the devices. These will be settings such as protection element pickup values and CT and VT ratios.
The settings template mode allows the user to define which settings will be visible in EnerVista UR Setup. Settings tem-
plates can be applied to both settings files (settings file templates) and online devices (online settings templates). The func-
tionality is identical for both purposes.
The settings template feature requires that both the EnerVista UR Setup software and the G60 firmware are at ver-
sions 5.40 or higher.
NOTE

a) ENABLING THE SETTINGS TEMPLATE


The settings file template feature is disabled by default. The following procedure describes how to enable the settings tem-
plate for UR-series settings files.
1. Select a settings file from the offline window of the EnerVista UR Setup main screen.
2. Right-click on the selected device or settings file and select the Template Mode > Create Template option.
The settings file template is now enabled and the file tree displayed in light blue. The settings file is now in template editing
mode.
Alternatively, the settings template can also be applied to online settings. The following procedure describes this process.
1. Select an installed device from the online window of the EnerVista UR Setup main screen.
2. Right-click on the selected device and select the Template Mode > Create Template option.

The software will prompt for a template password. This password is required to use the template feature and must be
at least four characters in length.
8 3. Enter and re-enter the new password, then click OK to continue.
The online settings template is now enabled. The device is now in template editing mode.

b) EDITING THE SETTINGS TEMPLATE


The settings template editing feature allows the user to specify which settings are available for viewing and modification in
EnerVista UR Setup. By default, all settings except the FlexLogic™ equation editor settings are locked.
1. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Select the Template Mode > Edit Template option to place the device in template editing mode.
3. Enter the template password then click OK.
4. Open the relevant settings windows that contain settings to be specified as viewable.

8-6 G60 Generator Protection System GE Multilin


8 SECURITY 8.2 SETTINGS SECURITY

By default, all settings are specified as locked and displayed against a grey background. The icon on the upper right of
the settings window will also indicate that EnerVista UR Setup is in EDIT mode. The following example shows the
phase time overcurrent settings window in edit mode.

Figure 8–2: SETTINGS TEMPLATE VIEW, ALL SETTINGS SPECIFIED AS LOCKED


5. Specify which settings to make viewable by clicking on them.
The setting available to view will be displayed against a yellow background as shown below.

Figure 8–3: SETTINGS TEMPLATE VIEW, TWO SETTINGS SPECIFIED AS EDITABLE


6. Click on Save to save changes to the settings template.
7. Proceed through the settings tree to specify all viewable settings.

c) ADDING PASSWORD PROTECTION TO A TEMPLATE


8
It is highly recommended that templates be saved with password protection to maximize security.
The following procedure describes how to add password protection to a settings file template.
1. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen.
2. Selecting the Template Mode > Password Protect Template option.

GE Multilin G60 Generator Protection System 8-7


8.2 SETTINGS SECURITY 8 SECURITY

The software will prompt for a template password. This password must be at least four characters in length.

3. Enter and re-enter the new password, then click OK to continue.


The settings file template is now secured with password protection.
When templates are created for online settings, the password is added during the initial template creation step. It
does not need to be added after the template is created.
NOTE

d) VIEWING THE SETTINGS TEMPLATE


Once all necessary settings are specified for viewing, users are able to view the settings template on the online device or
settings file. There are two ways to specify the settings view with the settings template feature:
• Display only those settings available for editing.
• Display all settings, with settings not available for editing greyed-out.
Use the following procedure to only display settings available for editing.
1. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Apply the template by selecting the Template Mode > View In Template Mode option.
3. Enter the template password then click OK to apply the template.
Once the template has been applied, users will only be able to view and edit the settings specified by the template. The
effect of applying the template to the phase time overcurrent settings is shown below.

8
Phase time overcurrent window with template applied via
the Template Mode > View In Template Mode command.
The template specifies that only the Pickup and Curve
Phase time overcurrent settings window without template applied.
settings be available.
842858A1.CDR

Figure 8–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND

8-8 G60 Generator Protection System GE Multilin


8 SECURITY 8.2 SETTINGS SECURITY

Viewing the settings in template mode also modifies the settings tree, showing only the settings categories that contain
editable settings. The effect of applying the template to a typical settings tree view is shown below.

Typical settings tree view without template applied. Typical settings tree view with template applied via
the Template Mode > View In Template Mode
command.
842860A1.CDR

Figure 8–5: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE SETTINGS COMMAND
Use the following procedure to display settings available for editing and settings locked by the template.
1. Select an installed device or a settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Apply the template by selecting the Template Mode > View All Settings option.
3. Enter the template password then click OK to apply the template.
Once the template has been applied, users will only be able to edit the settings specified by the template, but all settings
will be shown. The effect of applying the template to the phase time overcurrent settings is shown below.

Phase time overcurrent settings window without template applied. Phase time overcurrent window with template applied via
the Template Mode > View All Settings command.
8
The template specifies that only the Pickup and Curve
settings be available.
842859A1.CDR

Figure 8–6: APPLYING TEMPLATES VIA THE VIEW ALL SETTINGS COMMAND

e) REMOVING THE SETTINGS TEMPLATE


It may be necessary at some point to remove a settings template. Once a template is removed, it cannot be reapplied and
it will be necessary to define a new settings template.
1. Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen.
2. Select the Template Mode > Remove Settings Template option.
3. Enter the template password and click OK to continue.

GE Multilin G60 Generator Protection System 8-9


8.2 SETTINGS SECURITY 8 SECURITY

4. Verify one more time that you wish to remove the template by clicking Yes.

The EnerVista software will remove all template information and all settings will be available.

8.2.2 SECURING AND LOCKING FLEXLOGIC™ EQUATIONS

The UR allows users to secure parts or all of a FlexLogic™ equation, preventing unauthorized viewing or modification of
critical FlexLogic™ applications. This is accomplished using the settings template feature to lock individual entries within
FlexLogic™ equations.
Secured FlexLogic™ equations will remain secure when files are sent to and retrieved from any UR-series device.

a) LOCKING FLEXLOGIC™ EQUATION ENTRIES


The following procedure describes how to lock individual entries of a FlexLogic™ equation.
1. Right-click the settings file or online device and select the Template Mode > Create Template item to enable the set-
tings template feature.
2. Select the FlexLogic > FlexLogic Equation Editor settings menu item.
By default, all FlexLogic™ entries are specified as viewable and displayed against a yellow background. The icon on
the upper right of the window will also indicate that EnerVista UR Setup is in EDIT mode.
3. Specify which entries to lock by clicking on them.
The locked entries will be displayed against a grey background as shown in the example below.

Figure 8–7: LOCKING FLEXLOGIC™ ENTRIES IN EDIT MODE


4. Click on Save to save and apply changes to the settings template.
5. Select the Template Mode > View In Template Mode option to view the template.
6. Apply a password to the template then click OK to secure the FlexLogic™ equation.

8-10 G60 Generator Protection System GE Multilin


8 SECURITY 8.2 SETTINGS SECURITY

Once the template has been applied, users will only be able to view and edit the FlexLogic™ entries not locked by the tem-
plate. The effect of applying the template to the FlexLogic™ entries in the above procedure is shown below.

Typical FlexLogic™ entries without template applied. Typical FlexLogic™ entries locked with template via
the Template Mode > View In Template Mode command.
842861A1.CDR

Figure 8–8: LOCKING FLEXLOGIC ENTRIES THROUGH SETTING TEMPLATES


The FlexLogic™ entries are also shown as locked in the graphical view (as shown below) and on the front panel display.

8
Figure 8–9: SECURED FLEXLOGIC™ IN GRAPHICAL VIEW

b) LOCKING FLEXLOGIC™ EQUATIONS TO A SERIAL NUMBER


A settings file and associated FlexLogic™ equations can also be locked to a specific UR serial number. Once the desired
FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific
serial number.
1. Select the settings file in the offline window.
2. Right-click on the file and select the Edit Settings File Properties item.

GE Multilin G60 Generator Protection System 8-11


8.2 SETTINGS SECURITY 8 SECURITY

The following window is displayed.

Figure 8–10: TYPICAL SETTINGS FILE PROPERTIES WINDOW


3. Enter the serial number of the G60 device to lock to the settings file in the Serial # Lock field.
The settings file and corresponding secure FlexLogic™ equations are now locked to the G60 device specified by the serial
number.

8.2.3 SETTINGS FILE TRACEABILITY

A traceability feature for settings files allows the user to quickly determine if the settings in a G60 device have been
changed since the time of installation from a settings file. When a settings file is transfered to a G60 device, the date, time,
and serial number of the G60 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor-
mation can be compared with the G60 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the G60
device or obtained from the G60 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.

1 SETTINGS FILE TRANSFERRED


TO UR-SERIES DEVICE

The serial number and last setting change date


are stored in the UR-series device.

The serial number of the UR-series device and the file transfer
date are added to the settings file when settings files
are transferred to the device.

Compare transfer dates in the settings file and the


SERIAL NUMBER AND TRANSFER DATE
2
UR-series device to determine if security
has been compromised. SENT BACK TO ENERVISTA AND
ADDED TO SETTINGS FILE. 842864A1.CDR

Figure 8–11: SETTINGS FILE TRACEABILITY MECHANISM


With respect to the above diagram, the traceability feature is used as follows.

8-12 G60 Generator Protection System GE Multilin


8 SECURITY 8.2 SETTINGS SECURITY

1. The transfer date of a setting file written to a G60 is logged in the relay and can be viewed via EnerVista UR Setup or
the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
2. Comparing the dates stored in the relay and on the settings file at any time in the future will indicate if any changes
have been made to the relay configuration since the settings file was saved.

a) SETTINGS FILE TRACEABILITY INFORMATION


The serial number and file transfer date are saved in the settings files when they sent to an G60 device.
The G60 serial number and file transfer date are included in the settings file device definition within the EnerVista UR Setup
offline window as shown in the example below.

Traceability data in settings


file device definition

842863A1.CDR

Figure 8–12: DEVICE DEFINITION SHOWING TRACEABILITY DATA


This information is also available in printed settings file reports as shown in the example below.

Traceability data
in settings report

842862A1.CDR
8
Figure 8–13: SETTINGS FILE REPORT SHOWING TRACEABILITY DATA

GE Multilin G60 Generator Protection System 8-13


8.2 SETTINGS SECURITY 8 SECURITY

b) ONLINE DEVICE TRACEABILITY INFORMATION


The G60 serial number and file transfer date are available for an online device through the actual values. Select the Actual
Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the
example below.

Traceability data in online


device actual values page

842865A1.CDR

Figure 8–14: TRACEABILITY DATA IN ACTUAL VALUES WINDOW


This infomormation if also available from the front panel display through the following actual values:
ACTUAL VALUES ÖØ PRODUCT INFO Ö MODEL INFORMATION ÖØ SERIAL NUMBER
ACTUAL VALUES ÖØ PRODUCT INFO Ö MODEL INFORMATION ÖØ LAST SETTING CHANGE

c) ADDITIONAL TRACEABILITY RULES


The following additional rules apply for the traceability feature
• If the user changes any settings within the settings file in the offline window, then the traceability information is
removed from the settings file.
• If the user creates a new settings file, then no traceability information is included in the settings file.
• If the user converts an existing settings file to another revision, then any existing traceability information is removed
from the settings file.
• If the user duplicates an existing settings file, then any traceability information is transferred to the duplicate settings
file.

8-14 G60 Generator Protection System GE Multilin


8 SECURITY 8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM

8.3ENERVISTA SECURITY MANAGEMENT SYSTEM 8.3.1 OVERVIEW

The EnerVista security management system is a role-based access control (RBAC) system that allows a security adminis-
trator to easily manage the security privileges of multiple users. This allows for access control of URPlus-series devices by
multiple personnel within a substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The
EnerVista security management system is disabled by default to allow the administrator direct access to the EnerVista soft-
ware after installation. It is recommended that security be enabled before placing the device in service.

8.3.2 ENABLING THE SECURITY MANAGEMENT SYSTEM

The EnerVista security management system is disabled by default. This allows access to the device immediately after
installation. When security is disabled, all users are granted administrator access.
1. Select the Security > User Management menu item to open the user management configuration window.

2. Check the Enable Security box in the lower-left corner to enable the security management system.
Security is now enabled for the EnerVista UR Setup software. It will now be necessary to enter a username and password
upon starting the software.

8.3.3 ADDING A NEW USER

The following pre-requisites are required to add new users to the EnerVista security management system.
• The user adding the new user must have administrator rights.
• The EnerVista security management system must be enabled.
8
The following procedure describes how to add new users.
1. Select the Security > User Management menu item to open the user management configuration window.
2. Enter a username in the User field. The username must be between 4 and 20 characters in length.

GE Multilin G60 Generator Protection System 8-15


8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY

3. Select the user access rights by checking one or more of the fields shown.

The access rights are described in the following table


Table 8–1: ACCESS RIGHTS SUMMARY
FIELD DESCRIPTION
Delete Entry Checking this box will delete the user when exiting the user management configuration window.
Actual Values Checking this box allows the user to read actual values.
Settings Checking this box allows the user to read setting values.
Commands Checking this box allows the user to execute commands.
Event Recorder Checking this box allows the user to use the digital fault recorder.
FlexLogic Checking this box allows the user to read FlexLogic™ values.
Update Info Checking this box allows the user to write to any function to which they have read privileges. When any of
the Settings, Event Recorder, and FlexLogic boxes are checked by themselves, the user is granted read
access. When any of these are checked in conjunction with the Update Info box, they are granted read and
write access. The user will not be granted write access to functions that are not checked, even if the Update
Info field is checked.
Admin When this box is checked, the user will become an EnerVista URPlus Setup administrator, therefore
receiving all of the administrative rights. Exercise caution when granting administrator rights.

4. Click OK to add the new user to the security management system.

8.3.4 MODIFYING USER PRIVILEGES

The following pre-requisites are required to modify user privileges in the EnerVista security management system.
8 • The user modifying the privileges must have administrator rights.
• The EnerVista security management system must be enabled.
The following procedure describes how to modify user privileges.
1. Select the Security > User Management menu item to open the user management configuration window.
2. Locate the username in the User field.

8-16 G60 Generator Protection System GE Multilin


8 SECURITY 8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM

3. Modify the user access rights by checking or clearing one or more of the fields shown.

The access rights are described in the following table


Table 8–2: ACCESS RIGHTS SUMMARY
FIELD DESCRIPTION
Delete Entry Checking this box will delete the user when exiting the user management configuration window.
Actual Values Checking this box allows the user to read actual values.
Settings Checking this box allows the user to read setting values.
Commands Checking this box allows the user to execute commands.
Event Recorder Checking this box allows the user to use the digital fault recorder.
FlexLogic Checking this box allows the user to read FlexLogic™ values.
Update Info Checking this box allows the user to write to any function to which they have read privileges. When any of
the Settings, Event Recorder, and FlexLogic boxes are checked by themselves, the user is granted read
access. When any of these are checked in conjunction with the Update Info box, they are granted read and
write access. The user will not be granted write access to functions that are not checked, even if the Update
Info field is checked.
Admin When this box is checked, the user will become an EnerVista URPlus Setup administrator, therefore
receiving all of the administrative rights. Exercise caution when granting administrator rights.

4. Click OK to save the changes to user to the security management system.

GE Multilin G60 Generator Protection System 8-17


8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY

8-18 G60 Generator Protection System GE Multilin


9 THEORY OF OPERATION 9.1 PHASE DISTANCE THROUGH POWER TRANSFORMERS

9 THEORY OF OPERATION 9.1PHASE DISTANCE THROUGH POWER TRANSFORMERS 9.1.1 DESCRIPTION

As a Wye-Delta transformer introduces discontinuity for the zero-sequence circuit, the ground distance protection cannot
be applied, except special circumstances, to respond to faults behind the transformer.
The phase distance elements, however, could be developed so that both accurate reach and correct fault phase identifica-
tion is retained for faults behind the power transformer as seen from the relaying point. Without appropriate compensation,
the relay's reach would depend on a type of fault, creating considerable difficulties in applying the relay.
The G60 provides for any location of the VTs and CTs with respect to the involved power transformer and the direction of
any given zone.
In the following equations, the VT and CT locations are referenced as “None” if the transformer is not present between the
CT/VT and the intended reach point. Otherwise, the location is to be selected as a type of a transformer as seen from the
VT/CT position towards the intended reach point. The following figure explains the adopted rules.

(a) (b)
delta wye, 330o lag delta wye, 330o lag

Z3 Z3

Z3 XFRM VOL CONNECTION = None Z3 XFRM VOL CONNECTION = Yd1


Z3 XFRM CUR CONNECTION = None Z3 XFRM CUR CONNECTION = None

Z1 Z1

Z1 XFRM VOL CONNECTION = Dy11 Z1 XFRM VOL CONNECTION = None


Z1 XFRM CUR CONNECTION = Dy11 Z1 XFRM CUR CONNECTION = Dy11

(c) (e)
delta wye, 330o lag

L1 L2

Z3 Zone 3
Zone 1
Z3 XFRM VOL CONNECTION = None
Z3 XFRM CUR CONNECTION = Yd1 ZL1 ZT ZL2

Z1

Z1 XFRM VOL CONNECTION = Dy11


Z1 XFRM CUR CONNECTION = None
830717A1.CDR

Figure 9–1: APPLICATIONS OF THE “PHS DIST XFMR VOL/CUR CONNECTION” SETTINGS

GE Multilin G60 Generator Protection System 9-1


9.1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION

Table 9–1: PHASE DISTANCE INPUT SIGNALS FOR DELTA-WYE TRANSFORMERS


TRANSFORMER LOOP CURRENT VOLTAGE
CONNECTION TRANSFORMATION TRANSFORMATION
None AB IA – IB V AB
BC IB – IC V BC
CA IC – IA V CA
Dy1 AB 1-
3I A ------ ( V AB – V CA )
3
BC 1-
3I B ------ ( V BC – V AB )
3
CA 1-
3I C ------ ( V CA – V BC )
3
Dy3 AB 1
I AB_21P = – 3I C V AB_21P = ------- ( V BC – V CA )
3
BC 1
I BC_21P = – 3I A V BC_21P = ------- ( V CA – V AB )
3
CA 1
I CA_21P = – 3I B V CA_21P = ------- ( V AB – V BC )
3
Dy5 AB 1
I AB_21P = – 3I B V AB_21P = ------- ( V BC – V AB )
3
BC 1
I BC_21P = – 3I C V BC_21P = ------- ( V CA – V BC )
3
CA 1
I CA_21P = – 3I A V CA_21P = ------- ( V AB – V CA )
3
Dy7 AB 1
I AB_21P = – 3I A V AB_21P = ------- ( V CA – V AB )
3
BC 1
I BC_21P = – 3I B V BC_21P = ------- ( V AB – V BC )
3
CA 1
I CA_21P = – 3I C V CA_21P = ------- ( V BC – V CA )
3
Dy9 AB 1
I AB_21P = – 3I C V AB_21P = ------- ( V CA – V BC )
3
BC 1
I BC_21P = – 3I A V BC_21P = ------- ( V AB – V CA )
3
CA 1
I CA_21P = – 3I B V CA_21P = ------- ( V BC – V AB )
3
9 Dy11 AB
I AB_21P = – 3I B 1
V AB_21P = ------- ( V AB – V BC )
3
BC 1
I BC_21P = – 3I C V BC_21P = ------- ( V BC – V CA )
3
CA 1
I CA_21P = – 3I A V CA_21P = ------- ( V CA – V AB )
3

9-2 G60 Generator Protection System GE Multilin


9 THEORY OF OPERATION 9.1 PHASE DISTANCE THROUGH POWER TRANSFORMERS

Table 9–2: PHASE DISTANCE INPUT SIGNALS FOR WYE-DELTA TRANSFORMERS


TRANSFORMER LOOP CURRENT VOLTAGE
CONNECTION TRANSFORMATION TRANSFORMATION
Yd1 AB 1
I AB_21P = ------- ( 2I A – I B – I C ) V AB_21P = 3V A
3
BC 1
I BC_21P = ------- ( 2I B – I A – I C ) V BC_21P = 3V B
3
CA 1
I CA_21P = ------- ( 2I C – I A – I B ) V CA_21P = 3V C
3
Yd3 AB 1
I AB_21P = ------- ( I A + I B – 2I C ) V AB_21P = – 3V C
3
BC 1
I BC_21P = ------- ( I B + I C – 2I A ) V BC_21P = – 3V A
3
CA 1
I CA_21P = ------- ( I A + I C – 2I B ) V CA_21P = – 3V B
3
Yd5 AB 1
I AB_21P = ------- ( 2I B – I A – I C ) V AB_21P = 3V B
3
BC 1
I BC_21P = ------- ( 2I C – I A – I B ) V BC_21P = 3V C
3
CA 1
I CA_21P = ------- ( 2I A – I B – I C ) V CA_21P = 3V A
3
Yd7 AB 1
I AB_21P = ------- ( I B + I C – 2I A ) V AB_21P = – 3V A
3
BC 1
I BC_21P = ------- ( I A + I C – 2I B ) V BC_21P = – 3V B
3
CA 1
I CA_21P = ------- ( I A + I B – 2I C ) V CA_21P = – 3V C
3
Yd9 AB 1
I AB_21P = ------- ( 2I C – I A – I B ) V AB_21P = 3V C
3
BC 1
I BC_21P = ------- ( 2I A – I B – I C ) V BC_21P = 3V A
3
CA 1
I CA_21P = ------- ( 2I B – I A – I C ) V CA_21P = 3V B
3
Yd11 AB 1
I AB_21P = ------- ( I A + I C – 2I B ) V AB_21P = – 3V B
3
BC 1
I BC_21P = ------- ( I A + I B – 2I C ) V BC_21P = – 3V C

CA
3
9
1
I CA_21P = ------- ( I B + I C – 2I A ) V CA_21P = – 3V A
3

GE Multilin G60 Generator Protection System 9-3


9.1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION

Equations from the “Current Transformation” and “Voltage Transformation” columns are used to derive inputs to the three
(AB, BC, and CA) phase distance elements. For example, if the CTs are located at the delta side of the Delta-Wye 11 trans-
former, and a given zone is set to look through the transformer into the system connected to the Wye winding, the CT loca-
tion setting for that zone shall be set to Dy11 and the relay would use – 3I B instead of a traditional I A – I B for the AB
phase distance element.
The current supervision pickup setting applies to the currents specified in the “Current Transformation” columns.
A distance zone originates at the location of the VTs (regardless of the location of the CTs). For more information on set-
tings please refer to Chapter 9: Application of Settings.

9.1.2 EXAMPLE

Consider the system shown below:

150 MVA, 10%


13.8kV/315kV
delta wye, 330° lag
AB
ZL = 30.11Ω∠85°

H X

VT = 13.8kV/120V VT = 315kV/120V
CT = 8000:5 CT = 300:5
0.688Ω∠85°

2.57Ω∠88.4°

837727A2.CDR

Figure 9–2: SAMPLE SYSTEM CONFIGURATION


Normally, in order to respond to the fault shown in the figure, a distance relay shall be applied at the relaying point X. The
relay input signals at this location are shown in the following table.

INPUT PRIMARY SECONDARY


VA 100.4 kV ∠–7.32° 38.25 V ∠–7.32°
VB 97.23 kV ∠–53.4° 37.04 V ∠–53.4°
VC 181.8 kV ∠–150.0° 69.26 V ∠–150.0°
IA 1.288 kA ∠–27.6° 21.47 A ∠–27.6°
IB 1.288 kA ∠152.4° 21.47 A ∠152.4°
IC 0 0

If installed at the location X, the relay would use the following input signals for its phase AB distance element:
V = VAB = 77.402 kV ∠57.5° primary or 29.49 V ∠57.5° secondary
I = IA – IB = 2.576 kA ∠–27.6° primary or 42.93 A ∠–27.6° secondary
9 And consequently it would see an apparent impedance of:
Zapp = V / I = 30.05 Ω ∠85° primary or 0.687 Ω ∠85° secondary

9-4 G60 Generator Protection System GE Multilin


9 THEORY OF OPERATION 9.1 PHASE DISTANCE THROUGH POWER TRANSFORMERS

If applied at location H, the relay sees the following input signals:

INPUT PRIMARY SECONDARY


VA 7.584 kV ∠–5.59° 69.95 V ∠–5.59°
VB 6.269 kV ∠–120.1° 54.52 V ∠–120.1°
VC 7.751 kV ∠125.5° 65.84 V ∠125.5°
IA 16.976 kA ∠–27.6° 10.61 A ∠–27.6°
IB 33.952 kA ∠152.4° 21.22 A ∠152.4°
IC 16.976 kA ∠–27.6° 10.61 A ∠–27.6°

The relay is set as follows:


XFMR VOL CONNECTION = “Dy11”
XFMR CUR CONNECTION = “Dy11”

Consequently, the following signals are applied to the phase AB distance element:
1
V = ------- V AB – V BC = 10.861 kV ∠59.9° primary or 94.45 V ∠59.9° secondary (EQ 9.1)
3

I = – 3I B = 58.860 kA ∠– 27.6° primary or 36.75 A ∠– 27.6° secondary (EQ 9.2)

This results in the following apparent impedance:


94.45 kV ∠59.9°- = 2.570 Ω ∠87.5° secondary
Z app = V
---- = --------------------------------------------- (EQ 9.3)
I 36.75 kA ∠– 27.6 °
The above value is a correct measure of the distance from the VT location to the fault. For relay location 2, this certainly
includes the positive-sequence impedance of the transformer:
2
10 ( 13.8 kV )
Z T ( at 13.8 kV ) = ---------- × ---------------------------- = 0.127Ω ∠90°
100 150 MVA
(EQ 9.4)
13.8 2
Z L ( at 13.8 kV ) = 30.11 × ⎛ -----------⎞ = 0.05779Ω ∠85°
⎝ 315 ⎠

Thus, 0.127 Ω ∠90° + 0.05779 Ω ∠85° = 0.1847 Ω ∠88.4° primary side or 2.569 Ω ∠88.4° on the secondary side.
The above example illustrates how the relay maintains correct reach for fault behind power transformers. When installed at
X, the relay shall be set to 0.687 Ω ∠85° secondary in order to reach to the fault shown in the figure. When installed at H,
the relay shall be set to 2.569 Ω ∠88.4° to ensure exactly same coverage.
See Chapter 9: Application of Settings for more information on setting calculations.

GE Multilin G60 Generator Protection System 9-5


9.1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION

9-6 G60 Generator Protection System GE Multilin


10 APPLICATION OF SETTINGS 10.1 SETTING EXAMPLE

10 APPLICATION OF SETTINGS 10.1SETTING EXAMPLE 10.1.1 DESCRIPTION

This section provides an example of the settings required for an example system configuration. Consider the generator pro-
tection system shown below:
GENERATOR:
211.765 MVA, 18 kV, ABC GSU: TX LINE:
x’d = 0.216 pu 200 MVA 138 kV
xd = 1.967 pu 18 : 138 kV Z1 = 15 + j75 ohm
2
I2T capability = 10 X1 = 10%
I2 capability = 8%
Motoring Power = 22000 kW X2
H2

X1 H0

X3 H1 H3

8000 : 5 A 8000 : 5 A X1 H1
A
A
B X2 H2 Power
52G 52 B
C X3 H3 system
C
H0

18900 : 120 V
12000 : 240 V
Yd1
R
M1a

M1b

M2a

M2b

M3a

M3b

M4a

M4b
M1c

M2c

M3c

M4c

F5a

F6a

F7a

F8a

F1a

F1b

F2a

F2b

F3a

F3b

F4a

F4b
F5c

F6c

F7c

F8c

F1c

F2c

F3c

F4c
VX
VB

VC
VA

VX

IG5

IG1
VB

VC

IG
IG5

IG1

VA
IG

IA5

IA1

IB

IC
IA

IC5

IC1
IA5

IA1

IB5

IB1
IB

IC
IA

IC5

IC1
IB5

IB1

“+”

CURRENT INPUTS VOLTAGE INPUTS CURRENT INPUTS


8H 8F

Inlet valve 52b


H5a CONTACT INPUT H5a DIGITAL INPUTS/OUTPUTS 6G I H1a
H5c CONTACT INPUT H5c H1
V
H1b Trip generator breaker
H6a CONTACT INPUT H6a H1c
H6c CONTACT INPUT H6c I H2a
H5b COMMON H5b H2
V
H2b Trip field breaker
H2c
H7a CONTACT INPUT H7a
I H3a
H7c CONTACT INPUT H7c
H8a CONTACT INPUT H8a
H3
V
H3b Trip turbine
H3c
H8c CONTACT INPUT H8c I H4a
H7b COMMON H7b
H4
V
H4b Alarm
H8b SURGE H4c

GE Consumer & Industrial


“–” Multilin
G60 Generator Management Relay

830712A7.CDR

Figure 10–1: G60 SAMPLE SYSTEM

10.1.2 SYSTEM SETUP

Ideally, the CTs should be selected so the generator nominal current is 80 to 85% of CT primary. The following settings are
entered for the example system. The M5 bank and the ground CT input on each of the groups are unused in this example.
The nominal current is given by:
6
S nom 212 × 10 VA - = 6800 A
I nom = --------------------
- = ----------------------------------------- (EQ 10.1)
3
3V nom 3 × 18 × 10 V

Make the following settings changes in EnerVista UR Setup (or alternately, via the front panel through the SYSTEM SETUP Ö
AC INPUTS Ö CURRENT BANK F1 and the SYSTEM SETUP Ö AC INPUTS ÖØ CURRENT BANK M1 menus).

10

GE Multilin G60 Generator Protection System 10-1


10.1 SETTING EXAMPLE 10 APPLICATION OF SETTINGS

For the example system, the voltage settings are calculated as follows:
18000 V- ---------------------
120 V -
PHASE VT SECONDARY = --------------------- × = 66 V (EQ 10.2)
3 18900 V

18900 V- = 157.5
PHASE VT RATIO = --------------------- (EQ 10.3)
120 V
12000 V
NEUTRAL VT RATIO = ---------------------- = 50 (EQ 10.4)
240 V
Enter the following values through EnerVista UR Setup (or alternately, through the front panel SETTINGS ÖØ SYSTEM SETUP
Ö AC INPUTS ÖØ VOLTAGE BANK F5 Ö menu):

10.1.3 POWER SYSTEM

Frequency tracking should always be enabled for generator applications. Make the following power system parameters
changes via EnerVista UR Setup or through the SETTINGS ÖØ SYSTEM SETUP ÖØ POWER SYSTEM ÖØ VOLTAGE BANK F5 Ö
menu:

10.1.4 SIGNAL SOURCES

Two sources are required for this application example. The “LINE” source uses the phase and auxiliary VT inputs and the
CT input wired to the generator output CT. The “NEUTRL” source uses the phase VT inputs and the CT input wired to the
generator neutral CT. Including the phase VT inputs for both sources allows the user to choose the location of elements that
use both voltage and current. Elements using the auxiliary VT input are assigned to the “NEUTRL” source.
Make the following changes through EnerVista UR Setup or through the SETTINGS ÖØ SYSTEM SETUP ÖØ SOURCE 1 and
the SETTINGS ÖØ SYSTEM SETUP ÖØ SOURCE 2 menus:

10

10-2 G60 Generator Protection System GE Multilin


10 APPLICATION OF SETTINGS 10.1 SETTING EXAMPLE

10.1.5 STATOR DIFFERENTIAL

The “LINE” and “NEUTRL” sources are both required for the stator differential element. The minimum pickup can usually be
set as low as 0.05 pu (corresponding to 0.25 A secondary or 400 A primary in this example). Set the STATOR DIFF SLOPE 1
setting to accommodate for CT errors; a setting of 10% is adequate in most instances. Set the STATOR DIFF SLOPE 2 setting
to accommodate for errors due to CT saturation; a setting of 80% is recommended for most applications. The STATOR DIFF
BREAK 1 setting must be greater than the maximum load expected for the machine. The STATOR DIFF BREAK 2 setting should
be set at the level where CT saturation is expected to occur.
Make the following parameter changes in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS ÖØ SET-
TING GROUP 1 ÖØ STATOR DIFFERENTIAL Ö menu:

10.1.6 GENERATOR UNBALANCE

Stage 1 of the generator unbalance element is typically used to trip the generator. In this example, the I2 capability of the
machine is 8% and the I22T capability is 10. The generator nominal current is:
I nom primary
- = 6800 A- = 0.85 pu
I nom ( pu ) = -------------------------------- ------------------ (EQ 10.5)
CT primary 8000 A
The minimum operate time of stage 1 will be set to 0.25 seconds, the maximum operating time will be 10 minutes, and the
reset time will be set to 4 minutes.
Stage 2 is typically set lower than stage 1 with a time delay to prevent nuisance alarms for external faults that are normally
cleared by system protection. For the application example, the pickup setting is:
Pickup = 70% × I 2 capability = 0.70 × 8% = 5.6% (EQ 10.6)

Source 2 will be chosen for this element. The settings are as follows:

10

GE Multilin G60 Generator Protection System 10-3


10.1 SETTING EXAMPLE 10 APPLICATION OF SETTINGS

10.1.7 LOSS OF EXCITATION

For the example system, we have the following values:


2 2
base kV CT ratio ( 18 kV ) 1600
Z b ( sec ) = --------------------------- × --------------------- = ------------------------------------ × --------------- = 15.54 Ω (EQ 10.7)
base MVA VT ratio 211.765 MVA 157.5

X d ′(sec) = X d ′ × Z b (sec) = 0.216 × 15.54 Ω = 3.36 Ω (EQ 10.8)

X d ( sec ) = X d × Z b ( sec ) = 1.967 × 15.54 Ω = 30.57 Ω (EQ 10.9)

Z b ( sec ) + X d ′(sec)
- = 15.54Ω + 3.36Ω- = 9.45 Ω
CENTER 1 = ------------------------------------------------ ------------------------------------------ (EQ 10.10)
2 2

Z b ( sec ) Ω- = 7.77 Ω
RADIUS 1 = -------------------- = 15.54
--------------------- (EQ 10.11)
2 2

PICKUP DELAY 1 = 0.06 seconds (EQ 10.12)

X d ( sec ) + X d ′(sec) 30.57Ω + 3.36Ω


CENTER 2 = ------------------------------------------------- = ------------------------------------------- = 16.97 Ω (EQ 10.13)
2 2

X d ( sec ) Ω- = 15.28 Ω
- = 30.57
RADIUS 2 = -------------------- --------------------- (EQ 10.14)
2 2
The voltage supervision setting will be determined by a system study and may be disabled on either element if required. VT
fuse failure should supervise this element.
The choice of source is not critical for this application. The NEUTRL source is chosen for the following setting changes.
Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP
1 ÖØ LOSS OF EXCITATION menu:

10.1.8 REVERSE POWER

The reverse power element should be set at ½ the rated motoring power. The pickup is calculated as follows:
1 Rated Motoring Power (primary watts)
S min = --- × -------------------------------------------------------------------------------------------------------------------------------------------------------------------------- (EQ 10.15)
2 3 × Phase CT Primary × Phase VT Ratio × Phase VT Secondary
6
1 22 × 10 W
For the example system: S min = --- × --------------------------------------------------------------------- = 0.044 pu
2 3 × 8000 A × 157.5 × 66 V

10

10-4 G60 Generator Protection System GE Multilin


10 APPLICATION OF SETTINGS 10.1 SETTING EXAMPLE

To prevent maloperation for power swings the element is typically time delayed by 20 to 30 seconds. For sequential tripping
applications the time delay will be 2 to 3 seconds. The element may be blocked when the generator is offline. The line
source will be used for this application. Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ
GROUPED ELEMENTS ÖØ SETTING GROUP 1 ÖØ SENSITIVE DIRECTIONAL POWER Ö DIRECTIONAL POWER 1 menu:

Sequential tripping logic can be implemented in FlexLogic™ as follows:

54 DIR POWER 1 STG2 OP


AND(2) = SEQ TRIP (VO9)
55 INLET VALVE OFF(H8A)

56 AND(2)

57 = SEQ TRIP (VO9)


830731A1.CDR

Figure 10–2: SEQUENTIAL TRIPPING FLEXLOGIC™

10.1.9 SYSTEM BACKUP OVERCURRENT

System backup protection is implemented using a phase time overcurrent element with voltage restraint enabled. The
NEUTRL source will be chosen for this element. The pickup of this element should be set at a safe margin above the max-
imum load expected on the machine.
Generator Nominal Current 6800
PICKUP = 1.5 × ------------------------------------------------------------------------ = 1.5 × ------------- = 1.275 pu (EQ 10.16)
CT Primary 8000
The selection of all standard curves (and FlexCurves™) is allowed for easy coordination with system relaying. For the
example system, an IEEE extremely inverse curve will be used and a setting will be chosen such that the operate time for a
three phase fault on the high side of the transformer is 0.75 seconds. For simplicity, the power system contribution is not
considered.
211.765
Transformer Impedance = 0.10 × --------------------- = 0.106 pu on machine base (EQ 10.17)
200

Impedance to Fault = 0.216 + 0.106 = 0.322 pu (EQ 10.18)

1 6800
Fault Current = V
---- = --------------- × ------------- = 2.64 pu (EQ 10.19)
X 0.322 8000

Transformer Impedance 10.6


Fault Voltage = Nominal Voltage × ---------------------------------------------------------------- = 18 kV × ----------- = 5.93 kV (EQ 10.20)
Total Impedance 32.2

Fault Voltage - = 5.93 kV- = 0.329


Pickup Reduction = ----------------------------------------------------------------------- ------------------- (EQ 10.21)
Generator Nominal Voltage 18 kV
The equation for an IEEE extremely inverse curve is as follows:

A -+B
--------------------------------------------------------------------------------------
T = TDM × ⎛ --------------------------------------------------------------------
⎝ I pickup × Pickup Reduction⎠
I p
-⎞ – 1 (EQ 10.22) 10

GE Multilin G60 Generator Protection System 10-5


10.1 SETTING EXAMPLE 10 APPLICATION OF SETTINGS

where A = 28.2, B = 0.1217, and p = 2. Solving for TDM, we have:


0.75
TDM = ------------------------------------------------------------------------------
- = 0.88 (EQ 10.23)
28.2
------------------------------------------------------ + 0.1217
2
⎛ -----------------------------------
2.64 -⎞
⎝ 1.275 × 0.329⎠ – 1

Since this element will coordinate with system protections a timed reset is chosen. The element must be blocked for a VT
fuse failure. The neutral source will be chosen. Make the following changes in EnerVista UR Setup or through the SETTINGS
ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP 1 ÖØ PHASE CURRENT Ö PHASE TOC1 menu:

10.1.10 BACKUP DISTANCE

This function provides time-delayed protection for system faults that have not been cleared by system protections and to
provide backup protection for stator faults.
The “Line” source will be used in this example to permit the application of a forward and reverse zone. The memory dura-
tion will be left at the default setting (10 cycles).
Zone 1 will look forward and cover the GSU and the transmission line leaving the station. Zone 3 will look in the reverse
direction and cover the stator winding. Zone 2 will not be used in this example. Both the VTs and the CTs are located on the
low voltage side of the GSU. The transformer vector diagram (see figure 9-1) shows this transformer to be Yd1. Conse-
quently, due to the location of instrument transformers, Dy11 is chosen for both the XFMR VOL CONNECTION and XFMR CUR
CONNECTION settings. There are no transformers in the reverse direction. Therefore “None” is chosen for both of the zone 3
transformer connection settings. The reach of the zone 1 element will be set at 120% of impedance of the GSU and the
transmission line. In the instance that there are multiple lines and/or multiple generators, the zone 1 reach must be
increased to compensate for the infeed effect.
2 2
VL ( 18 )
Transformer impedance = X T × --------------- = j0.1 × -------------- = j0.162 primary ohms (EQ 10.24)
MVA T 200

2 2
VL ( 18 )
Line impedance = X L × ------2- = ( 15 + j75 ) × ----------------2- = 0.255 + j1.276 primary ohms (EQ 10.25)
VH ( 138 )

CT ratio
Zone 1 reach = 1.2 × ( Transformer impedance + Line impedance ) × ---------------------
VT ratio
(EQ 10.26)
1600
= 1.2 × ( j0.162 + 0.255 + j1.276 ) × --------------- = 17.8 ∠80° secondary ohms
157.5

10

10-6 G60 Generator Protection System GE Multilin


10 APPLICATION OF SETTINGS 10.1 SETTING EXAMPLE

The zone 3 reach will be set at 120% of the generator transient reactance. The time delay of this element should be com-
pared to the generator decrement curve to verify the adequacy of this setting.
2 2
VL ( 18 )
Generator impedance = X d × ---------------- = j1.967 × -------------- = j3.01 primary ohms (EQ 10.27)
MVA G 211

CT ratio
Zone 3 reach = 1.2 × Generator impedance × ---------------------
VT ratio
(EQ 10.28)
1600
= 1.2 × j3.01 × --------------- = j36.68 secondary ohms
157.5
An mho shape has been chosen for this example. Therefore, the quadrilateral settings are left at their default values. Make
the following changes in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP 1 ÖØ
DISTANCE Ö PHASE DISTANCE Z1(3) menus:

10.1.11 STATOR GROUND FAULT

a) AUXILIARY OVERVOLTAGE
Stator ground fault protection is implemented with an overvoltage element connected at the generator neutral resistor. The
auxiliary overvoltage element will be used in this example. The auxiliary voltage input has previously been assigned to the
NEUTRL source. In this example the element will be set to protect 97% of the stator against ground faults.

Nominal Phase – Ground Voltage 18000 ⁄ 3


PICKUP = 0.03 × ---------------------------------------------------------------------------------------- = 0.03 × ---------------------------- = 0.026 pu (EQ 10.29)
Ground VT Primary 12000

10

GE Multilin G60 Generator Protection System 10-7


10.1 SETTING EXAMPLE 10 APPLICATION OF SETTINGS

The time delay should be longer than the longest normal clearing time for faults outside the generator zone. If the phase
VTs are wye-connected then this element should also be coordinated with VT secondary fuses to prevent false operations
for VT secondary ground faults. For the sample system a time delay of 1 second will be used. Make the following changes
in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1 ÖØ VOLTAGE ELEMENTS ÖØ
AUXILIARY OV1 menu:

b) 100% STATOR GROUND


The auxiliary voltage input is required for both the 100% stator ground and the third harmonic neutral undervoltage ele-
ments. Therefore the NEUTRL source will be assigned for these elements. Make the following changes in the SETTINGS
ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP 1 ÖØ STATOR GROUND menu
STATOR GROUND SOURCE: "SRC 2" (the "NEUTRL" source)
This 100% stator ground element provides ground fault protection for the neutral end of the stator winding. The element
has two stages. In this application, stage 1 is used to trip the machine and stage 2 is used for alarm purposes. Set the
pickup to 0.15 for both stages to provide adequate overlap with the auxiliary overvoltage element. Set stage 1 to 0.375 V
secondary (this value may be increased for security in particularly noisy environments). Stage 2 is typically set at 0.3 V sec-
ondary. The supervision settings are expressed in per unit of the NOMINAL PHASE VT SECONDARY setting. The time delay
settings are 5 seconds and 1 second for the Stage 1 and Stage 2 elements respectively.

STG1 SUPV = 0.375 V- = 0.0057 pu , STG2 SUPV = 0.300 V- = 0.0045 pu


-------------------- -------------------- (EQ 10.30)
66 V 66 V
Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP
1 ÖØ STATOR GROUND Ö 100% STATOR GROUND menu:

10

10-8 G60 Generator Protection System GE Multilin


10 APPLICATION OF SETTINGS 10.1 SETTING EXAMPLE

c) THIRD HARMONIC NEUTRAL UNDERVOLTAGE


If the phase VTs are delta connected then third harmonic voltage cannot be measured and the 100% stator ground element
cannot be used. In this case the third harmonic neutral undervoltage element can be used. Field measurements should be
taken over the entire operating range of the machine to determine the variation of the third harmonic voltage as shown
below:

Third harmonic
neutral voltage

Megawatts

830733A1.CDR

Figure 10–3: THIRD HARMONIC NEUTRAL UNDERVOLTAGE FIELD MEASUREMENTS


The element is accurate for levels as low as 0.25 volts, secondary. In this case, the pickup setting will be:

PICKUP = 0.25 V- = 0.001 pu


---------------- (EQ 10.31)
240 V
The third harmonic will dip below the pickup setting between 85 and 105 megawatts. The element should be blocked over
this range. A margin of 5% should be added to the relay settings. The values for maximum and minimum power will be:
6
105 × 10
Max Power = 1.05 × --------------------------------------------------------- = 0.441 pu (EQ 10.32)
3 × 8000 × 157.5 × 66
6
85 × 10
Min Power = 0.95 × --------------------------------------------------------- = 0.323 pu (EQ 10.33)
3 × 8000 × 157.5 × 66
Voltage supervision will be given a setting of 0.8 pu in order to prevent maloperation during a sustained undervoltage con-
dition. A time delay of 5 seconds will be applied. If required, the element may be blocked when the machine is offline. Make
the following changes in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP 1 ÖØ
STATOR GROUND Ö 3RD HARM NTRL UNDERVOLTAGE menu:

10

GE Multilin G60 Generator Protection System 10-9


10.1 SETTING EXAMPLE 10 APPLICATION OF SETTINGS

10.1.12 OVEREXCITATION

This protection should be set to coordinate with the manufacturers excitation capability curves. For example system, the
combined generator/GSU limit curve is shown below:

Time (seconds)

Volts per hertz (p.u.)


Combined generator/GSU Volts per Volts per
limit curve hertz 1 hertz 2

830734A1.CDR

Figure 10–4: GENERATOR/GSU LIMIT CURVE


Program the volts per hertz 1 element with an inverse characteristic (curve A), a pickup of 1.05, and a TDM of 40. Program
the volts per hertz 2 element with a definite time characteristic, a pickup of 1.23, and a time delay of 2 seconds. Both ele-
ments will issue a trip. The volts per hertz 1 pickup will be used to generate an alarm. Either source may be assigned in this
example. Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS ÖØ SET-
TING GROUP 1 ÖØ VOLTAGE ELEMENTS Ö VOLTS/HZ 1(2) menus:

10

10-10 G60 Generator Protection System GE Multilin


10 APPLICATION OF SETTINGS 10.1 SETTING EXAMPLE

10.1.13 INPUTS/OUTPUTS

The following inputs and outputs will be used in this example. Make the following changes in EnerVista UR Setup or
through the SETTINGS ÖØ INPUTS/OUTPUTS Ö CONTACT INPUTS Ö CONTACT INPUT H7a(H7c) menus:

Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ VIRTUAL OUTPUTS Ö
VIRTUAL OUTPUT 1(4) menus:

Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUTS Ö
CONTACT OUTPUT H1(H4) menus:

10

GE Multilin G60 Generator Protection System 10-11


10.1 SETTING EXAMPLE 10 APPLICATION OF SETTINGS

10.1.14 FREQUENCY

The pickup and delay settings are dependent on operating practices and system characteristics. In this example, two over-
frequency and two underfrequency elements will be used. The elements will be blocked when offline. Underfrequency will
initiate a trip. Overfrequency will alarm only. Either source may be assigned.
Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ CONTROL ELEMENTS ÖØ UNDERFRE-
QUENCY Ö UNDERFREQUENCY 1(2) and the SETTINGS ÖØ CONTROL ELEMENTS ÖØ OVERFREQUENCY Ö OVERFREQUENCY 1(2)
menus:

10.1.15 ACCIDENTAL ENERGIZATION

In this example, the ACCDNT ENRG ARMING MODE is selected as “UV and Offline”. The ACCDNT ENRG OC PICKUP setting
should be set at ½ the minimum expected fault current. In this case, 1.0 pu (8000 A primary) is selected. In cases where it
is possible to re-energize the machine through its auxiliary transformer, a lower setting may be required. The undervoltage
pickup setting must be set above the maximum expected fault voltage.
Make the following changes in EnerVista UR Setup or through the SETTINGS ÖØ GROUPED ELEMENTS ÖØ SETTING GROUP
1 ÖØ ACCIDENTAL ENERGIZATION menu:

10

10-12 G60 Generator Protection System GE Multilin


10 APPLICATION OF SETTINGS 10.1 SETTING EXAMPLE

10.1.16 FLEXLOGIC™

The following logic as given as an example only. The logic for each specific application will be dependant on system design,
protection philosophies, and operating practices.

5 sec.
1 SEQ TRIP ON (VO9) 33 VOLTS PER HERTZ 1 PKP
0 sec.

2 STATOR DIFF OP 34 TIMER 1

3 PHASE TOC1 OP 35 GEN UNBAL STG2 OP OR(4) = ALARM (VO4)

4 GEN UNBAL STG1 OP 36 OVERFREQ ON (VO6)

5 LOSS EXCIT OP 37 STATOR GND STG2 OP

6 DIR POWER 1 STG 1 OP OR(11) = GEN BKR TRIP (VO1) 38 OR(4)

7 OVEREXCIT ON (VO7) 39 = ALARM (VO4)

8 UNDERFREQ ON (VO5)

9 AUX OV1 OP
40 UNDERFREQ 1 OP
OR(2) = UNDERFREQ (VO5)
10 STATOR GND STG1 OP
41 UNDERFREQ 2 OP

11 ACCDNT ENRG OP
42 OR(2)

12 OR(11)
43 = UNDERFREQ (VO5)

13 = GEN BKR TRIP (VO1)

44 OVERFREQ 1 OP
14 SEQ TRIP ON (VO9) OR(2) = OVERFREQ (VO6)
45 OVERFREQ 2 OP
15 STATOR DIFF OP
46 OR(2)
16 LOSS EXCIT OP
47 = OVERFREQ (VO6)
17 DIR POWER STG1 OP OR(7) = FLD BKR TRIP (VO2)

18 OVEREXCIT ON (VO7)
48 VOLTS PER HERTZ 1 OP
19 AUX OV1 OP OR(2) = OVEREXCIT (VO7)
49 VOLTS PER HERTZ 2 OP
20 STATOR GND STG1 OP
50 OR(2)
21 OR(7)
51 = OVEREXCIT (VO7)
22 = FLD BKR TRIP (VO2)

52 OFFLINE OFF(H7C) = ONLINE (VO8)

23 STATOR DIFF OP
53 = ONLINE (VO8)
24 LOSS EXCIT OP

25 DIR POWER 1 STG1 OP


54 DIR POWER 1 STG2 OP
26 ONLINE ON (VO8) AND(2) = SEQ TRIP (VO9)
AND(2) OR(6) = TURBINE TRIP (VO3) 55 INLET VALVE OFF(H8A)
27 OVEREXCIT ON (VO7)
56 AND(2)
28 AND(2)
57 = SEQ TRIP (VO9)
29 AUX OV1 OP

30 STATOR GND STG1 OP


58 END
31 OR(6) 830732A1.CDR

32 = TURBINE TRIP (VO3)

Figure 10–5: APPLICATION EXAMPLE FLEXLOGIC™

10

GE Multilin G60 Generator Protection System 10-13


10.2 PHASE DISTANCE THROUGH POWER TRANSFORMERS 10 APPLICATION OF SETTINGS

10.2PHASE DISTANCE THROUGH POWER TRANSFORMERS 10.2.1 OVERVIEW

a) APPLICATION DESCRIPTION
Phase distance elements of the G60 could be set to respond to faults beyond any three-phase power transformer. The
relay guarantees accurate reach and targeting for any phase fault. Moreover, the current and voltage transformers may be
located independently on different sides of the transformer.
The following setting rules apply to this feature:
1. A given distance zone is terminated by location of the VTs, not the CTs.
2. Consequently, the positive-sequence impedance of a transformer must be included in the reach setting only if the
transformer is located between the potential source and the intended reach point.
3. The current signals require compensation if the transformer is located between the CTs and the intended reach point.
If this is the case the CT connection setting shall be set to transformer connection and vector group as seen from the
CTs toward the reach point. Otherwise, the CT connection setting shall be set to "None".
4. The voltage signals require compensation if the transformer is located between the VTs and the intended reach point.
If this is the case the VT connection setting shall be set to transformer connection and vector group as seen from the
VTs toward the reach point. Otherwise, the VT connection setting shall be set to "None".
5. The reach setting is entered in secondary ohms and as such must take into account location and ratios of VTs and CTs
as well as voltage ratio of the involved power transformer.
The following equations explain the setting rules. Consider two applications as shown in the figure below:

(a)
ZH ZT ZX

H X

Z3 Z1

(b)
ZH ZT ZX

H X

Z3 Z1

830718A1.CDR

Figure 10–6: PHASE DISTANCE PROTECTION LOOKING THROUGH A POWER TRANSFORMER


where: ZX = intended reach impedance for Zone 1 (primary ohms)
ZH = intended reach impedance for Zone 3 (primary ohms)
ZT = positive-sequence impedance of the transformer
VX, VH = transformer rated voltages
nCT = transformation ratio of the CTs
nVT = transformation ratio of the VTs
Z1: Z1 reach setting (secondary ohms)
10 Z3: Zone 3 reach setting (secondary ohms)

10-14 G60 Generator Protection System GE Multilin


10 APPLICATION OF SETTINGS 10.2 PHASE DISTANCE THROUGH POWER TRANSFORMERS

b) ZONE 1 SETTING IN APPLICATION (A)


As the transformer is located between the potential source and the reach point for Zone 1, the reach impedance must
include the positive-sequence impedance of the transformer. In addition, the primary impedance must be re-calculated for
the voltage level of the VTs and CTs, and eventually, re-calculated to secondary quantities:
V H 2 n CT
Z 1 = ( Z T ( at X ) + Z x ) × ⎛ -------⎞ × --------- (EQ 10.34)
⎝ V X⎠ n VT

c) ZONE 3 SETTING IN APPLICATION (A)


As the transformer is not located between the potential source and the reach point for Zone 3, the reach impedance must
not include the positive-sequence impedance of the transformer. Because both VTs and CTs are located on the same side
as the intended reach point, no correction for the transformer ratio is required. The primary impedance must be only re-cal-
culated to secondary quantities:
n CT
Z 3 = Z H × --------- (EQ 10.35)
n VT

d) ZONE 1 SETTING IN APPLICATION (B)


As the transformer is not located between the potential source and the reach point for Z1, the reach impedance must not
include the positive-sequence impedance of the transformer. The CTs are located on the other side of the transformer, thus
transformer ratio must be included:
VH n CT
Z 1 = Z X × ⎛⎝ -------⎞⎠ × --------- (EQ 10.36)
VX n VT

e) ZONE 3 SETTING IN APPLICATION (B)


As the transformer is located between the potential source and the reach point for Zone 3, the reach impedance must
include the positive-sequence impedance of the transformer. The VTs are located on the other side of the transformer, thus
transformer ratio must be included:
VX n CT
Z 3 = ( Z T ( at H ) + Z H ) × ⎛⎝ -------⎞⎠ × --------- (EQ 10.37)
VH n VT

10.2.2 EXAMPLE

Given the following for the system shown in the previous section:
ZX = 30 Ω ∠85° (intended reach of Zone 1)
ZH = 0.06 Ω ∠88° (intended reach of Zone 3)
nCT = 8000:5 = 1600 (located at H)
nVT = 315000:120 = 2625 (located at X)
Transformer: 13.8/315 kV, 150 MVA, 10%, delta/wye, 315 kV side lagging 30°
Transformer impedance:
2
10 ( 13.8 )
Z T ( at H ) = ---------- × ------------------- = 0.127Ω ∠90° (EQ 10.38)
100 150
The Zone 1 settings are:
13.8 1600
Z 1 = 30 × ----------- × ------------- = 0.8011Ω ∠85° (EQ 10.39)
315 2625
PHS DIST Z1 REACH: "0.80"
PHS DIST Z1 RCA: "85"
PHS DIST Z1 XMFR VOL CONNECTION: "None"
PHS DIST Z1 XMFR CUR CONNECTION: "Dy1" 10

GE Multilin G60 Generator Protection System 10-15


10.2 PHASE DISTANCE THROUGH POWER TRANSFORMERS 10 APPLICATION OF SETTINGS

The Zone 3 settings are:


315 1600
Z 3 = ( 0.127 ∠90° + 0.006 ∠88° ) × ----------- × ------------- = 2.601Ω ∠89.4° (EQ 10.40)
13.8 2625
PHS DIST Z3 REACH: "2.60"
PHS DIST Z3 RCA: "89"
PHS DIST Z3 XMFR VOL CONNECTION: "Yd11"
PHS DIST Z3 XMFR CUR CONNECTION: "None"

10

10-16 G60 Generator Protection System GE Multilin


11 COMMISSIONING 11.1 TESTING

11 COMMISSIONING 11.1TESTING 11.1.1 TESTING UNDERFREQUENCY AND OVERFREQUENCY ELEMENTS

Underfreqency and overfrequency protection requires techniques with subtle testing implications. Whereas most protection
11
is designed to detect changes from normal to fault conditions that occur virtually instantaneously, power system inertia
requires frequency protection to pickup while the frequency is changing slowly. Frequency measurement is inherently sen-
sitive to noise, making high precision in combination with high speed challenging for both relays and test equipment.
Injection to a particular G60 frequency element must be to its configured source and to the channels the source uses for
frequency measurement. For frequency measurement, a source will use the first quantity configured in the following order:
1. Phase voltages.
2. Auxiliary voltage.
3. Phase currents.
4. Ground current.
For example, if only auxiliary voltage and phase currents are configured, the source will use the auxiliary voltage, not the
phase voltages or any of the currents.
When phase voltages or phase currents are used, the source applies a filter that rejects the zero-sequence component. As
such, the same signal must not be injected to all three phases, or the injected signal will be completely filtered out. For an
underfrequency element using phase quantities, the phase A signal must be above the MIN VOLT/AMP setting value. There-
fore, either inject into phase A only, or inject a balanced three-phase signal.
Frequency

Injection frequency

Source frequency

Tracking frequency

Pickup
frequency

Relay conditioning time

Source frequency calculation delay

Time
Underfrequency element detection time

Underfrequency element pickup


set “pickup delay”

Underfrequency element operate


831771A1.CDR

Figure 11–1: TYPICAL UNDERFREQUENCY ELEMENT TEST TIMING


The static accuracy of the frequency threshold may be determined by slowly adjusting the frequency of the injected signal
about the set pickup. If the G60 frequency metering feature is used to determine the injected frequency, the metering accu-
racy should be verified by checking it against a known standard (for example, the power system).
To accurately measure the time delay of a frequency element, a test emulating realistic power system dynamics is required.
The injected frequency should smoothly ramp through the set threshold, with the ramp starting frequency sufficiently out-
side the threshold so the relay becomes conditioned to the trend before operation. For typical interconnected power sys-
tems, the recommended testing ramp rate is 0.20 Hz/s.

GE Multilin G60 Generator Protection System 11-1


11.1 TESTING 11 COMMISSIONING

The desired delay time is the interval from the point the frequency crosses the set threshold to the point the element oper-
ates. Some test sets can measure only the time from the ramp start to element operation, necessitating the subtraction of
11 the pre-threshold ramp time from the reading. For example, with a ramp rate of 0.20 Hz/s, start the ramp 0.20 Hz before the
threshold and subtract 1 second from test set time reading of ramp start to relay operation.
Note that the G60 event records only show the “pickup delay” component, a definite time timer. This is exclusive of the time
taken by the frequency responding component to pickup.
The G60 oscillography can be used to measure the time between the calculated source frequency crossing the threshold
and element operation; however, this method omits the delay in the calculated source frequency. The security features of
the source frequency measurement algorithm result in the calculated frequency being delayed by 2 to 4 cycles (or longer
with noise on the input). In addition, oscillography resolution is 0.004 Hz, which at 0.20 Hz/s corresponds to a delay of
20 ms. The tracking frequency should not be used in timing measurements, as its algorithm involves phase locking, which
purposely sets its frequency high or low to allow the G60 sample clock to catch-up or wait as necessary to reach synchro-
nism with the power system.

11-2 G60 Generator Protection System GE Multilin


APPENDIX A A.1 PARAMETER LISTS

AppendicesAPPENDIX A FlexAnalog and FlexInteger ParametersA.1Parameter Lists A.1.1 FLEXANALOG ITEMS

A
Table A–1: FLEXANALOG DATA ITEMS (Sheet 1 of 23)
ADDRESS FLEXANALOG NAME UNITS DESCRIPTION
5728 Stator Diff Iad Amps Stator differential phase A current (Iad)
5730 Stator Rest Iar Amps Stator restraint phase A current (Iar)
5732 Stator Diff Ibd Amps Stator differential phase B current (Ibd)
5734 Stator Rest Ibr Amps Stator restraint phase B current (Ibr)
5736 Stator Diff Icd Amps Stator differential phase C current (Icd)
5738 Stator Rest Icr Amps Stator restraint phase C current (Icr)
5744 Stator Gnd Vn 3rd Volts Stator ground Vn third harmonic voltage
5746 Stator Gnd Vn+V0 3rd Volts Stator ground Vn+V0 third harmonic voltage
5748 Stator Gnd V0 3rd Volts Stator ground V0 third harmonic voltage
5760 Sns Dir Power 1 Watts Sensitive directional power 1 actual value
5762 Sns Dir Power 2 Watts Sensitive directional power 2 actual value
5792 RGF 1 Igd Mag Amps Restricted ground fault 1 differential ground current magnitude
5794 RGF 1 Igr Mag Amps Restricted ground fault 1 restricted ground current magnitude
5796 RGF 2 Igd Mag Amps Restricted ground fault 2 differential ground current magnitude
5798 RGF 2 Igr Mag Amps Restricted ground fault 2 restricted ground current magnitude
5800 RGF 3 Igd Mag Amps Restricted ground fault 3 differential ground current magnitude
5802 RGF 3 Igr Mag Amps Restricted ground fault 3 restricted ground current magnitude
5804 RGF 4 Igd Mag Amps Restricted ground fault 4 differential ground current magnitude
5806 RGF 4 Igr Mag Amps Restricted ground fault 4 restricted ground current magnitude
5808 RGF 5 Igd Mag Amps Restricted ground fault 5 differential ground current magnitude
5810 RGF 5 Igr Mag Amps Restricted ground fault 5 restricted ground current magnitude
5812 RGF 6 Igd Mag Amps Restricted ground fault 6 differential ground current magnitude
5814 RGF 6 Igr Mag Amps Restricted ground fault 6 restricted ground current magnitude
5856 Freq Rate 1 Value Hz/s Frequency rate of change 1 actual value
5860 Freq Rate 2 Value Hz/s Frequency rate of change 2 actual value
5864 Freq Rate 3 Value Hz/s Frequency rate of change 3 actual value
5868 Freq Rate 4 Value Hz/s Frequency rate of change 4 actual value
6144 SRC 1 Ia RMS Amps Source 1 phase A current RMS
6146 SRC 1 Ib RMS Amps Source 1 phase B current RMS
6148 SRC 1 Ic RMS Amps Source 1 phase C current RMS
6150 SRC 1 In RMS Amps Source 1 neutral current RMS
6152 SRC 1 Ia Mag Amps Source 1 phase A current magnitude
6154 SRC 1 Ia Angle Degrees Source 1 phase A current angle
6155 SRC 1 Ib Mag Amps Source 1 phase B current magnitude
6157 SRC 1 Ib Angle Degrees Source 1 phase B current angle
6158 SRC 1 Ic Mag Amps Source 1 phase C current magnitude
6160 SRC 1 Ic Angle Degrees Source 1 phase C current angle
6161 SRC 1 In Mag Amps Source 1 neutral current magnitude
6163 SRC 1 In Angle Degrees Source 1 neutral current angle
6164 SRC 1 Ig RMS Amps Source 1 ground current RMS
6166 SRC 1 Ig Mag Degrees Source 1 ground current magnitude
6168 SRC 1 Ig Angle Amps Source 1 ground current angle
6169 SRC 1 I_0 Mag Degrees Source 1 zero-sequence current magnitude
6171 SRC 1 I_0 Angle Amps Source 1 zero-sequence current angle
6172 SRC 1 I_1 Mag Degrees Source 1 positive-sequence current magnitude

GE Multilin G60 Generator Protection System A-1


A.1 PARAMETER LISTS APPENDIX A

Table A–1: FLEXANALOG DATA ITEMS (Sheet 2 of 23)

A ADDRESS
6174
FLEXANALOG NAME
SRC 1 I_1 Angle
UNITS
Amps
DESCRIPTION
Source 1 positive-sequence current angle
6175 SRC 1 I_2 Mag Degrees Source 1 negative-sequence current magnitude
6177 SRC 1 I_2 Angle Amps Source 1 negative-sequence current angle
6178 SRC 1 Igd Mag Degrees Source 1 differential ground current magnitude
6180 SRC 1 Igd Angle Amps Source 1 differential ground current angle
6208 SRC 2 Ia RMS Amps Source 2 phase A current RMS
6210 SRC 2 Ib RMS Amps Source 2 phase B current RMS
6212 SRC 2 Ic RMS Amps Source 2 phase C current RMS
6214 SRC 2 In RMS Amps Source 2 neutral current RMS
6216 SRC 2 Ia Mag Amps Source 2 phase A current magnitude
6218 SRC 2 Ia Angle Degrees Source 2 phase A current angle
6219 SRC 2 Ib Mag Amps Source 2 phase B current magnitude
6221 SRC 2 Ib Angle Degrees Source 2 phase B current angle
6222 SRC 2 Ic Mag Amps Source 2 phase C current magnitude
6224 SRC 2 Ic Angle Degrees Source 2 phase C current angle
6225 SRC 2 In Mag Amps Source 2 neutral current magnitude
6227 SRC 2 In Angle Degrees Source 2 neutral current angle
6228 SRC 2 Ig RMS Amps Source 2 ground current RMS
6230 SRC 2 Ig Mag Degrees Source 2 ground current magnitude
6232 SRC 2 Ig Angle Amps Source 2 ground current angle
6233 SRC 2 I_0 Mag Degrees Source 2 zero-sequence current magnitude
6235 SRC 2 I_0 Angle Amps Source 2 zero-sequence current angle
6236 SRC 2 I_1 Mag Degrees Source 2 positive-sequence current magnitude
6238 SRC 2 I_1 Angle Amps Source 2 positive-sequence current angle
6239 SRC 2 I_2 Mag Degrees Source 2 negative-sequence current magnitude
6241 SRC 2 I_2 Angle Amps Source 2 negative-sequence current angle
6242 SRC 2 Igd Mag Degrees Source 2 differential ground current magnitude
6244 SRC 2 Igd Angle Amps Source 2 differential ground current angle
6272 SRC 3 Ia RMS Amps Source 3 phase A current RMS
6274 SRC 3 Ib RMS Amps Source 3 phase B current RMS
6276 SRC 3 Ic RMS Amps Source 3 phase C current RMS
6278 SRC 3 In RMS Amps Source 3 neutral current RMS
6280 SRC 3 Ia Mag Amps Source 3 phase A current magnitude
6282 SRC 3 Ia Angle Degrees Source 3 phase A current angle
6283 SRC 3 Ib Mag Amps Source 3 phase B current magnitude
6285 SRC 3 Ib Angle Degrees Source 3 phase B current angle
6286 SRC 3 Ic Mag Amps Source 3 phase C current magnitude
6288 SRC 3 Ic Angle Degrees Source 3 phase C current angle
6289 SRC 3 In Mag Amps Source 3 neutral current magnitude
6291 SRC 3 In Angle Degrees Source 3 neutral current angle
6292 SRC 3 Ig RMS Amps Source 3 ground current RMS
6294 SRC 3 Ig Mag Degrees Source 3 ground current magnitude
6296 SRC 3 Ig Angle Amps Source 3 ground current angle
6297 SRC 3 I_0 Mag Degrees Source 3 zero-sequence current magnitude
6299 SRC 3 I_0 Angle Amps Source 3 zero-sequence current angle
6300 SRC 3 I_1 Mag Degrees Source 3 positive-sequence current magnitude
6302 SRC 3 I_1 Angle Amps Source 3 positive-sequence current angle

A-2 G60 Generator Protection System GE Multilin


APPENDIX A A.1 PARAMETER LISTS

Table A–1: FLEXANALOG DATA ITEMS (Sheet 3 of 23)


ADDRESS FLEXANALOG NAME UNITS DESCRIPTION A
6303 SRC 3 I_2 Mag Degrees Source 3 negative-sequence current magnitude
6305 SRC 3 I_2 Angle Amps Source 3 negative-sequence current angle
6306 SRC 3 Igd Mag Degrees Source 3 differential ground current magnitude
6308 SRC 3 Igd Angle Amps Source 3 differential ground current angle
6336 SRC 4 Ia RMS Amps Source 4 phase A current RMS
6338 SRC 4 Ib RMS Amps Source 4 phase B current RMS
6340 SRC 4 Ic RMS Amps Source 4 phase C current RMS
6342 SRC 4 In RMS Amps Source 4 neutral current RMS
6344 SRC 4 Ia Mag Amps Source 4 phase A current magnitude
6346 SRC 4 Ia Angle Degrees Source 4 phase A current angle
6347 SRC 4 Ib Mag Amps Source 4 phase B current magnitude
6349 SRC 4 Ib Angle Degrees Source 4 phase B current angle
6350 SRC 4 Ic Mag Amps Source 4 phase C current magnitude
6352 SRC 4 Ic Angle Degrees Source 4 phase C current angle
6353 SRC 4 In Mag Amps Source 4 neutral current magnitude
6355 SRC 4 In Angle Degrees Source 4 neutral current angle
6356 SRC 4 Ig RMS Amps Source 4 ground current RMS
6358 SRC 4 Ig Mag Degrees Source 4 ground current magnitude
6360 SRC 4 Ig Angle Amps Source 4 ground current angle
6361 SRC 4 I_0 Mag Degrees Source 4 zero-sequence current magnitude
6363 SRC 4 I_0 Angle Amps Source 4 zero-sequence current angle
6364 SRC 4 I_1 Mag Degrees Source 4 positive-sequence current magnitude
6366 SRC 4 I_1 Angle Amps Source 4 positive-sequence current angle
6367 SRC 4 I_2 Mag Degrees Source 4 negative-sequence current magnitude
6369 SRC 4 I_2 Angle Amps Source 4 negative-sequence current angle
6370 SRC 4 Igd Mag Degrees Source 4 differential ground current magnitude
6372 SRC 4 Igd Angle Amps Source 4 differential ground current angle
6656 SRC 1 Vag RMS Volts Source 1 phase AG voltage RMS
6658 SRC 1 Vbg RMS Volts Source 1 phase BG voltage RMS
6660 SRC 1 Vcg RMS Volts Source 1 phase CG voltage RMS
6662 SRC 1 Vag Mag Volts Source 1 phase AG voltage magnitude
6664 SRC 1 Vag Angle Degrees Source 1 phase AG voltage angle
6665 SRC 1 Vbg Mag Volts Source 1 phase BG voltage magnitude
6667 SRC 1 Vbg Angle Degrees Source 1 phase BG voltage angle
6668 SRC 1 Vcg Mag Volts Source 1 phase CG voltage magnitude
6670 SRC 1 Vcg Angle Degrees Source 1 phase CG voltage angle
6671 SRC 1 Vab RMS Volts Source 1 phase AB voltage RMS
6673 SRC 1 Vbc RMS Volts Source 1 phase BC voltage RMS
6675 SRC 1 Vca RMS Volts Source 1 phase CA voltage RMS
6677 SRC 1 Vab Mag Volts Source 1 phase AB voltage magnitude
6679 SRC 1 Vab Angle Degrees Source 1 phase AB voltage angle
6680 SRC 1 Vbc Mag Volts Source 1 phase BC voltage magnitude
6682 SRC 1 Vbc Angle Degrees Source 1 phase BC voltage angle
6683 SRC 1 Vca Mag Volts Source 1 phase CA voltage magnitude
6685 SRC 1 Vca Angle Degrees Source 1 phase CA voltage angle
6686 SRC 1 Vx RMS Volts Source 1 auxiliary voltage RMS
6688 SRC 1 Vx Mag Volts Source 1 auxiliary voltage magnitude

GE Multilin G60 Generator Protection System A-3


A.1 PARAMETER LISTS APPENDIX A

Table A–1: FLEXANALOG DATA ITEMS (Sheet 4 of 23)

A ADDRESS
6690
FLEXANALOG NAME
SRC 1 Vx Angle
UNITS
Degrees
DESCRIPTION
Source 1 auxiliary voltage angle
6691 SRC 1 V_0 Mag Volts Source 1 zero-sequence voltage magnitude
6693 SRC 1 V_0 Angle Degrees Source 1 zero-sequence voltage angle
6694 SRC 1 V_1 Mag Volts Source 1 positive-sequence voltage magnitude
6696 SRC 1 V_1 Angle Degrees Source 1 positive-sequence voltage angle
6697 SRC 1 V_2 Mag Volts Source 1 negative-sequence voltage magnitude
6699 SRC 1 V_2 Angle Degrees Source 1 negative-sequence voltage angle
6720 SRC 2 Vag RMS Volts Source 2 phase AG voltage RMS
6722 SRC 2 Vbg RMS Volts Source 2 phase BG voltage RMS
6724 SRC 2 Vcg RMS Volts Source 2 phase CG voltage RMS
6726 SRC 2 Vag Mag Volts Source 2 phase AG voltage magnitude
6728 SRC 2 Vag Angle Degrees Source 2 phase AG voltage angle
6729 SRC 2 Vbg Mag Volts Source 2 phase BG voltage magnitude
6731 SRC 2 Vbg Angle Degrees Source 2 phase BG voltage angle
6732 SRC 2 Vcg Mag Volts Source 2 phase CG voltage magnitude
6734 SRC 2 Vcg Angle Degrees Source 2 phase CG voltage angle
6735 SRC 2 Vab RMS Volts Source 2 phase AB voltage RMS
6737 SRC 2 Vbc RMS Volts Source 2 phase BC voltage RMS
6739 SRC 2 Vca RMS Volts Source 2 phase CA voltage RMS
6741 SRC 2 Vab Mag Volts Source 2 phase AB voltage magnitude
6743 SRC 2 Vab Angle Degrees Source 2 phase AB voltage angle
6744 SRC 2 Vbc Mag Volts Source 2 phase BC voltage magnitude
6746 SRC 2 Vbc Angle Degrees Source 2 phase BC voltage angle
6747 SRC 2 Vca Mag Volts Source 2 phase CA voltage magnitude
6749 SRC 2 Vca Angle Degrees Source 2 phase CA voltage angle
6750 SRC 2 Vx RMS Volts Source 2 auxiliary voltage RMS
6752 SRC 2 Vx Mag Volts Source 2 auxiliary voltage magnitude
6754 SRC 2 Vx Angle Degrees Source 2 auxiliary voltage angle
6755 SRC 2 V_0 Mag Volts Source 2 zero-sequence voltage magnitude
6757 SRC 2 V_0 Angle Degrees Source 2 zero-sequence voltage angle
6758 SRC 2 V_1 Mag Volts Source 2 positive-sequence voltage magnitude
6760 SRC 2 V_1 Angle Degrees Source 2 positive-sequence voltage angle
6761 SRC 2 V_2 Mag Volts Source 2 negative-sequence voltage magnitude
6763 SRC 2 V_2 Angle Degrees Source 2 negative-sequence voltage angle
6784 SRC 3 Vag RMS Volts Source 3 phase AG voltage RMS
6786 SRC 3 Vbg RMS Volts Source 3 phase BG voltage RMS
6788 SRC 3 Vcg RMS Volts Source 3 phase CG voltage RMS
6790 SRC 3 Vag Mag Volts Source 3 phase AG voltage magnitude
6792 SRC 3 Vag Angle Degrees Source 3 phase AG voltage angle
6793 SRC 3 Vbg Mag Volts Source 3 phase BG voltage magnitude
6795 SRC 3 Vbg Angle Degrees Source 3 phase BG voltage angle
6796 SRC 3 Vcg Mag Volts Source 3 phase CG voltage magnitude
6798 SRC 3 Vcg Angle Degrees Source 3 phase CG voltage angle
6799 SRC 3 Vab RMS Volts Source 3 phase AB voltage RMS
6801 SRC 3 Vbc RMS Volts Source 3 phase BC voltage RMS
6803 SRC 3 Vca RMS Volts Source 3 phase CA voltage RMS
6805 SRC 3 Vab Mag Volts Source 3 phase AB voltage magnitude

A-4 G60 Generator Protection System GE Multilin


APPENDIX A A.1 PARAMETER LISTS

Table A–1: FLEXANALOG DATA ITEMS (Sheet 5 of 23)


ADDRESS FLEXANALOG NAME UNITS DESCRIPTION A
6807 SRC 3 Vab Angle Degrees Source 3 phase AB voltage angle
6808 SRC 3 Vbc Mag Volts Source 3 phase BC voltage magnitude
6810 SRC 3 Vbc Angle Degrees Source 3 phase BC voltage angle
6811 SRC 3 Vca Mag Volts Source 3 phase CA voltage magnitude
6813 SRC 3 Vca Angle Degrees Source 3 phase CA voltage angle
6814 SRC 3 Vx RMS Volts Source 3 auxiliary voltage RMS
6816 SRC 3 Vx Mag Volts Source 3 auxiliary voltage magnitude
6818 SRC 3 Vx Angle Degrees Source 3 auxiliary voltage angle
6819 SRC 3 V_0 Mag Volts Source 3 zero-sequence voltage magnitude
6821 SRC 3 V_0 Angle Degrees Source 3 zero-sequence voltage angle
6822 SRC 3 V_1 Mag Volts Source 3 positive-sequence voltage magnitude
6824 SRC 3 V_1 Angle Degrees Source 3 positive-sequence voltage angle
6825 SRC 3 V_2 Mag Volts Source 3 negative-sequence voltage magnitude
6827 SRC 3 V_2 Angle Degrees Source 3 negative-sequence voltage angle
6848 SRC 4 Vag RMS Volts Source 4 phase AG voltage RMS
6850 SRC 4 Vbg RMS Volts Source 4 phase BG voltage RMS
6852 SRC 4 Vcg RMS Volts Source 4 phase CG voltage RMS
6854 SRC 4 Vag Mag Volts Source 4 phase AG voltage magnitude
6856 SRC 4 Vag Angle Degrees Source 4 phase AG voltage angle
6857 SRC 4 Vbg Mag Volts Source 4 phase BG voltage magnitude
6859 SRC 4 Vbg Angle Degrees Source 4 phase BG voltage angle
6860 SRC 4 Vcg Mag Volts Source 4 phase CG voltage magnitude
6862 SRC 4 Vcg Angle Degrees Source 4 phase CG voltage angle
6863 SRC 4 Vab RMS Volts Source 4 phase AB voltage RMS
6865 SRC 4 Vbc RMS Volts Source 4 phase BC voltage RMS
6867 SRC 4 Vca RMS Volts Source 4 phase CA voltage RMS
6869 SRC 4 Vab Mag Volts Source 4 phase AB voltage magnitude
6871 SRC 4 Vab Angle Degrees Source 4 phase AB voltage angle
6872 SRC 4 Vbc Mag Volts Source 4 phase BC voltage magnitude
6874 SRC 4 Vbc Angle Degrees Source 4 phase BC voltage angle
6875 SRC 4 Vca Mag Volts Source 4 phase CA voltage magnitude
6877 SRC 4 Vca Angle Degrees Source 4 phase CA voltage angle
6878 SRC 4 Vx RMS Volts Source 4 auxiliary voltage RMS
6880 SRC 4 Vx Mag Volts Source 4 auxiliary voltage magnitude
6882 SRC 4 Vx Angle Degrees Source 4 auxiliary voltage angle
6883 SRC 4 V_0 Mag Volts Source 4 zero-sequence voltage magnitude
6885 SRC 4 V_0 Angle Degrees Source 4 zero-sequence voltage angle
6886 SRC 4 V_1 Mag Volts Source 4 positive-sequence voltage magnitude
6888 SRC 4 V_1 Angle Degrees Source 4 positive-sequence voltage angle
6889 SRC 4 V_2 Mag Volts Source 4 negative-sequence voltage magnitude
6891 SRC 4 V_2 Angle Degrees Source 4 negative-sequence voltage angle
7168 SRC 1 P Watts Source 1 three-phase real power
7170 SRC 1 Pa Watts Source 1 phase A real power
7172 SRC 1 Pb Watts Source 1 phase B real power
7174 SRC 1 Pc Watts Source 1 phase C real power
7176 SRC 1 Q Vars Source 1 three-phase reactive power
7178 SRC 1 Qa Vars Source 1 phase A reactive power

GE Multilin G60 Generator Protection System A-5


A.1 PARAMETER LISTS APPENDIX A

Table A–1: FLEXANALOG DATA ITEMS (Sheet 6 of 23)

A ADDRESS
7180
FLEXANALOG NAME
SRC 1 Qb
UNITS
Vars
DESCRIPTION
Source 1 phase B reactive power
7182 SRC 1 Qc Vars Source 1 phase C reactive power
7184 SRC 1 S VA Source 1 three-phase apparent power
7186 SRC 1 Sa VA Source 1 phase A apparent power
7188 SRC 1 Sb VA Source 1 phase B apparent power
7190 SRC 1 Sc VA Source 1 phase C apparent power
7192 SRC 1 PF --- Source 1 three-phase power factor
7193 SRC 1 Phase A PF --- Source 1 phase A power factor
7194 SRC 1 Phase B PF --- Source 1 phase B power factor
7195 SRC 1 Phase C PF --- Source 1 phase C power factor
7200 SRC 2 P Watts Source 2 three-phase real power
7202 SRC 2 Pa Watts Source 2 phase A real power
7204 SRC 2 Pb Watts Source 2 phase B real power
7206 SRC 2 Pc Watts Source 2 phase C real power
7208 SRC 2 Q Vars Source 2 three-phase reactive power
7210 SRC 2 Qa Vars Source 2 phase A reactive power
7212 SRC 2 Qb Vars Source 2 phase B reactive power
7214 SRC 2 Qc Vars Source 2 phase C reactive power
7216 SRC 2 S VA Source 2 three-phase apparent power
7218 SRC 2 Sa VA Source 2 phase A apparent power
7220 SRC 2 Sb VA Source 2 phase B apparent power
7222 SRC 2 Sc VA Source 2 phase C apparent power
7224 SRC 2 PF --- Source 2 three-phase power factor
7225 SRC 2 Phase A PF --- Source 2 phase A power factor
7226 SRC 2 Phase B PF --- Source 2 phase B power factor
7227 SRC 2 Phase C PF --- Source 2 phase C power factor
7232 SRC 3 P Watts Source 3 three-phase real power
7234 SRC 3 Pa Watts Source 3 phase A real power
7236 SRC 3 Pb Watts Source 3 phase B real power
7238 SRC 3 Pc Watts Source 3 phase C real power
7240 SRC 3 Q Vars Source 3 three-phase reactive power
7242 SRC 3 Qa Vars Source 3 phase A reactive power
7244 SRC 3 Qb Vars Source 3 phase B reactive power
7246 SRC 3 Qc Vars Source 3 phase C reactive power
7248 SRC 3 S VA Source 3 three-phase apparent power
7250 SRC 3 Sa VA Source 3 phase A apparent power
7252 SRC 3 Sb VA Source 3 phase B apparent power
7254 SRC 3 Sc VA Source 3 phase C apparent power
7256 SRC 3 PF --- Source 3 three-phase power factor
7257 SRC 3 Phase A PF --- Source 3 phase A power factor
7258 SRC 3 Phase B PF --- Source 3 phase B power factor
7259 SRC 3 Phase C PF --- Source 3 phase C power factor
7264 SRC 4 P Watts Source 4 three-phase real power
7266 SRC 4 Pa Watts Source 4 phase A real power
7268 SRC 4 Pb Watts Source 4 phase B real power
7270 SRC 4 Pc Watts Source 4 phase C real power
7272 SRC 4 Q Vars Source 4 three-phase reactive power

A-6 G60 Generator Protection System GE Multilin


APPENDIX A A.1 PARAMETER LISTS

Table A–1: FLEXANALOG DATA ITEMS (Sheet 7 of 23)


ADDRESS FLEXANALOG NAME UNITS DESCRIPTION A
7274 SRC 4 Qa Vars Source 4 phase A reactive power
7276 SRC 4 Qb Vars Source 4 phase B reactive power
7278 SRC 4 Qc Vars Source 4 phase C reactive power
7280 SRC 4 S VA Source 4 three-phase apparent power
7282 SRC 4 Sa VA Source 4 phase A apparent power
7284 SRC 4 Sb VA Source 4 phase B apparent power
7286 SRC 4 Sc VA Source 4 phase C apparent power
7288 SRC 4 PF --- Source 4 three-phase power factor
7289 SRC 4 Phase A PF --- Source 4 phase A power factor
7290 SRC 4 Phase B PF --- Source 4 phase B power factor
7291 SRC 4 Phase C PF --- Source 4 phase C power factor
7552 SRC 1 Frequency Hz Source 1 frequency
7553 SRC 2 Frequency Hz Source 2 frequency
7554 SRC 3 Frequency Hz Source 3 frequency
7555 SRC 4 Frequency Hz Source 4 frequency
8064 SRC 1 Va THD --- Source 1 phase A voltage total harmonic distortion (THD)
8065 SRC 1 Va Harm[0] Volts Source 1 phase A voltage second harmonic
8066 SRC 1 Va Harm[1] Volts Source 1 phase A voltage third harmonic
8067 SRC 1 Va Harm[2] Volts Source 1 phase A voltage fourth harmonic
8068 SRC 1 Va Harm[3] Volts Source 1 phase A voltage fifth harmonic
8069 SRC 1 Va Harm[4] Volts Source 1 phase A voltage sixth harmonic
8070 SRC 1 Va Harm[5] Volts Source 1 phase A voltage seventh harmonic
8071 SRC 1 Va Harm[6] Volts Source 1 phase A voltage eighth harmonic
8072 SRC 1 Va Harm[7] Volts Source 1 phase A voltage ninth harmonic
8073 SRC 1 Va Harm[8] Volts Source 1 phase A voltage tenth harmonic
8074 SRC 1 Va Harm[9] Volts Source 1 phase A voltage eleventh harmonic
8075 SRC 1 Va Harm[10] Volts Source 1 phase A voltage twelfth harmonic
8076 SRC 1 Va Harm[11] Volts Source 1 phase A voltage thirteenth harmonic
8077 SRC 1 Va Harm[12] Volts Source 1 phase A voltage fourteenth harmonic
8078 SRC 1 Va Harm[13] Volts Source 1 phase A voltage fifteenth harmonic
8079 SRC 1 Va Harm[14] Volts Source 1 phase A voltage sixteenth harmonic
8080 SRC 1 Va Harm[15] Volts Source 1 phase A voltage seventeenth harmonic
8081 SRC 1 Va Harm[16] Volts Source 1 phase A voltage eighteenth harmonic
8082 SRC 1 Va Harm[17] Volts Source 1 phase A voltage nineteenth harmonic
8083 SRC 1 Va Harm[18] Volts Source 1 phase A voltage twentieth harmonic
8084 SRC 1 Va Harm[19] Volts Source 1 phase A voltage twenty-first harmonic
8085 SRC 1 Va Harm[20] Volts Source 1 phase A voltage twenty-second harmonic
8086 SRC 1 Va Harm[21] Volts Source 1 phase A voltage twenty-third harmonic
8087 SRC 1 Va Harm[22] Volts Source 1 phase A voltage twenty-fourth harmonic
8088 SRC 1 Va Harm[23] Volts Source 1 phase A voltage twenty-fifth harmonic
8089 SRC 1 Vb THD --- Source 1 phase B voltage total harmonic distortion (THD)
8090 SRC 1 Vb Harm[0] Volts Source 1 phase B voltage second harmonic
8091 SRC 1 Vb Harm[1] Volts Source 1 phase B voltage third harmonic
8092 SRC 1 Vb Harm[2] Volts Source 1 phase B voltage fourth harmonic
8093 SRC 1 Vb Harm[3] Volts Source 1 phase B voltage fifth harmonic
8094 SRC 1 Vb Harm[4] Volts Source 1 phase B voltage sixth harmonic
8095 SRC 1 Vb Harm[5] Volts Source 1 phase B voltage seventh harmonic

GE Multilin G60 Generator Protection System A-7


A.1 PARAMETER LISTS APPENDIX A

Table A–1: FLEXANALOG DATA ITEMS (Sheet 8 of 23)

A ADDRESS
8096
FLEXANALOG NAME
SRC 1 Vb Harm[6]
UNITS
Volts
DESCRIPTION
Source 1 phase B voltage eighth harmonic
8097 SRC 1 Vb Harm[7] Volts Source 1 phase B voltage ninth harmonic
8098 SRC 1 Vb Harm[8] Volts Source 1 phase B voltage tenth harmonic
8099 SRC 1 Vb Harm[9] Volts Source 1 phase B voltage eleventh harmonic
8100 SRC 1 Vb Harm[10] Volts Source 1 phase B voltage twelfth harmonic
8101 SRC 1 Vb Harm[11] Volts Source 1 phase B voltage thirteenth harmonic
8102 SRC 1 Vb Harm[12] Volts Source 1 phase B voltage fourteenth harmonic
8103 SRC 1 Vb Harm[13] Volts Source 1 phase B voltage fifteenth harmonic
8104 SRC 1 Vb Harm[14] Volts Source 1 phase B voltage sixteenth harmonic
8105 SRC 1 Vb Harm[15] Volts Source 1 phase B voltage seventeenth harmonic
8106 SRC 1 Vb Harm[16] Volts Source 1 phase B voltage eighteenth harmonic
8107 SRC 1 Vb Harm[17] Volts Source 1 phase B voltage nineteenth harmonic
8108 SRC 1 Vb Harm[18] Volts Source 1 phase B voltage twentieth harmonic
8109 SRC 1 Vb Harm[19] Volts Source 1 phase B voltage twenty-first harmonic
8110 SRC 1 Vb Harm[20] Volts Source 1 phase B voltage twenty-second harmonic
8111 SRC 1 Vb Harm[21] Volts Source 1 phase B voltage twenty-third harmonic
8112 SRC 1 Vb Harm[22] Volts Source 1 phase B voltage twenty-fourth harmonic
8113 SRC 1 Vb Harm[23] Volts Source 1 phase B voltage twenty-fifth harmonic
8114 SRC 1 Vc THD --- Source 1 phase C voltage total harmonic distortion (THD)
8115 SRC 1 Vc Harm[0] Volts Source 1 phase C voltage second harmonic
8116 SRC 1 Vc Harm[1] Volts Source 1 phase C voltage third harmonic
8117 SRC 1 Vc Harm[2] Volts Source 1 phase C voltage fourth harmonic
8118 SRC 1 Vc Harm[3] Volts Source 1 phase C voltage fifth harmonic
8119 SRC 1 Vc Harm[4] Volts Source 1 phase C voltage sixth harmonic
8120 SRC 1 Vc Harm[5] Volts Source 1 phase C voltage seventh harmonic
8121 SRC 1 Vc Harm[6] Volts Source 1 phase C voltage eighth harmonic
8122 SRC 1 Vc Harm[7] Volts Source 1 phase C voltage ninth harmonic
8123 SRC 1 Vc Harm[8] Volts Source 1 phase C voltage tenth harmonic
8124 SRC 1 Vc Harm[9] Volts Source 1 phase C voltage eleventh harmonic
8125 SRC 1 Vc Harm[10] Volts Source 1 phase C voltage twelfth harmonic
8126 SRC 1 Vc Harm[11] Volts Source 1 phase C voltage thirteenth harmonic
8127 SRC 1 Vc Harm[12] Volts Source 1 phase C voltage fourteenth harmonic
8128 SRC 1 Vc Harm[13] Volts Source 1 phase C voltage fifteenth harmonic
8129 SRC 1 Vc Harm[14] Volts Source 1 phase C voltage sixteenth harmonic
8130 SRC 1 Vc Harm[15] Volts Source 1 phase C voltage seventeenth harmonic
8131 SRC 1 Vc Harm[16] Volts Source 1 phase C voltage eighteenth harmonic
8132 SRC 1 Vc Harm[17] Volts Source 1 phase C voltage nineteenth harmonic
8133 SRC 1 Vc Harm[18] Volts Source 1 phase C voltage twentieth harmonic
8134 SRC 1 Vc Harm[19] Volts Source 1 phase C voltage twenty-first harmonic
8135 SRC 1 Vc Harm[20] Volts Source 1 phase C voltage twenty-second harmonic
8136 SRC 1 Vc Harm[21] Volts Source 1 phase C voltage twenty-third harmonic
8137 SRC 1 Vc Harm[22] Volts Source 1 phase C voltage twenty-fourth harmonic
8138 SRC 1 Vc Harm[23] Volts Source 1 phase C voltage twenty-fifth harmonic
8139 SRC 2 Va THD --- Source 2 phase A voltage total harmonic distortion (THD)
8140 SRC 2 Va Harm[0] Volts Source 2 phase A voltage second harmonic
8141 SRC 2 Va Harm[1] Volts Source 2 phase A voltage third harmonic
8142 SRC 2 Va Harm[2] Volts Source 2 phase A voltage fourth harmonic

A-8 G60 Generator Protection System GE Multilin


APPENDIX A A.1 PARAMETER LISTS

Table A–1: FLEXANALOG DATA ITEMS (Sheet 9 of 23)


ADDRESS FLEXANALOG NAME UNITS DESCRIPTION A
8143 SRC 2 Va Harm[3] Volts Source 2 phase A voltage fifth harmonic
8144 SRC 2 Va Harm[4] Volts Source 2 phase A voltage sixth harmonic
8145 SRC 2 Va Harm[5] Volts Source 2 phase A voltage seventh harmonic
8146 SRC 2 Va Harm[6] Volts Source 2 phase A voltage eighth harmonic
8147 SRC 2 Va Harm[7] Volts Source 2 phase A voltage ninth harmonic
8148 SRC 2 Va Harm[8] Volts Source 2 phase A voltage tenth harmonic
8149 SRC 2 Va Harm[9] Volts Source 2 phase A voltage eleventh harmonic
8150 SRC 2 Va Harm[10] Volts Source 2 phase A voltage twelfth harmonic
8151 SRC 2 Va Harm[11] Volts Source 2 phase A voltage thirteenth harmonic
8152 SRC 2 Va Harm[12] Volts Source 2 phase A voltage fourteenth harmonic
8153 SRC 2 Va Harm[13] Volts Source 2 phase A voltage fifteenth harmonic
8154 SRC 2 Va Harm[14] Volts Source 2 phase A voltage sixteenth harmonic
8155 SRC 2 Va Harm[15] Volts Source 2 phase A voltage seventeenth harmonic
8156 SRC 2 Va Harm[16] Volts Source 2 phase A voltage eighteenth harmonic
8157 SRC 2 Va Harm[17] Volts Source 2 phase A voltage nineteenth harmonic
8158 SRC 2 Va Harm[18] Volts Source 2 phase A voltage twentieth harmonic
8159 SRC 2 Va Harm[19] Volts Source 2 phase A voltage twenty-first harmonic
8160 SRC 2 Va Harm[20] Volts Source 2 phase A voltage twenty-second harmonic
8161 SRC 2 Va Harm[21] Volts Source 2 phase A voltage twenty-third harmonic
8162 SRC 2 Va Harm[22] Volts Source 2 phase A voltage twenty-fourth harmonic
8163 SRC 2 Va Harm[23] Volts Source 2 phase A voltage twenty-fifth harmonic
8164 SRC 2 Vb THD --- Source 2 phase B voltage total harmonic distortion (THD)
8165 SRC 2 Vb Harm[0] Volts Source 2 phase B voltage second harmonic
8166 SRC 2 Vb Harm[1] Volts Source 2 phase B voltage third harmonic
8167 SRC 2 Vb Harm[2] Volts Source 2 phase B voltage fourth harmonic
8168 SRC 2 Vb Harm[3] Volts Source 2 phase B voltage fifth harmonic
8169 SRC 2 Vb Harm[4] Volts Source 2 phase B voltage sixth harmonic
8170 SRC 2 Vb Harm[5] Volts Source 2 phase B voltage seventh harmonic
8171 SRC 2 Vb Harm[6] Volts Source 2 phase B voltage eighth harmonic
8172 SRC 2 Vb Harm[7] Volts Source 2 phase B voltage ninth harmonic
8173 SRC 2 Vb Harm[8] Volts Source 2 phase B voltage tenth harmonic
8174 SRC 2 Vb Harm[9] Volts Source 2 phase B voltage eleventh harmonic
8175 SRC 2 Vb Harm[10] Volts Source 2 phase B voltage twelfth harmonic
8176 SRC 2 Vb Harm[11] Volts Source 2 phase B voltage thirteenth harmonic
8177 SRC 2 Vb Harm[12] Volts Source 2 phase B voltage fourteenth harmonic
8178 SRC 2 Vb Harm[13] Volts Source 2 phase B voltage fifteenth harmonic
8179 SRC 2 Vb Harm[14] Volts Source 2 phase B voltage sixteenth harmonic
8180 SRC 2 Vb Harm[15] Volts Source 2 phase B voltage seventeenth harmonic
8181 SRC 2 Vb Harm[16] Volts Source 2 phase B voltage eighteenth harmonic
8182 SRC 2 Vb Harm[17] Volts Source 2 phase B voltage nineteenth harmonic
8183 SRC 2 Vb Harm[18] Volts Source 2 phase B voltage twentieth harmonic
8184 SRC 2 Vb Harm[19] Volts Source 2 phase B voltage twenty-first harmonic
8185 SRC 2 Vb Harm[20] Volts Source 2 phase B voltage twenty-second harmonic
8186 SRC 2 Vb Harm[21] Volts Source 2 phase B voltage twenty-third harmonic
8187 SRC 2 Vb Harm[22] Volts Source 2 phase B voltage twenty-fourth harmonic
8188 SRC 2 Vb Harm[23] Volts Source 2 phase B voltage twenty-fifth harmonic
8189 SRC 2 Vc THD --- Source 2 phase C voltage total harmonic distortion (THD)

GE Multilin G60 Generator Protection System A-9


A.1 PARAMETER LISTS APPENDIX A

Table A–1: FLEXANALOG DATA ITEMS (Sheet 10 of 23)

A ADDRESS
8190
FLEXANALOG NAME
SRC 2 Vc Harm[0]
UNITS
Volts
DESCRIPTION
Source 2 phase C voltage second harmonic
8191 SRC 2 Vc Harm[1] Volts Source 2 phase C voltage third harmonic
8192 SRC 2 Vc Harm[2] Volts Source 2 phase C voltage fourth harmonic
8193 SRC 2 Vc Harm[3] Volts Source 2 phase C voltage fifth harmonic
8194 SRC 2 Vc Harm[4] Volts Source 2 phase C voltage sixth harmonic
8195 SRC 2 Vc Harm[5] Volts Source 2 phase C voltage seventh harmonic
8196 SRC 2 Vc Harm[6] Volts Source 2 phase C voltage eighth harmonic
8197 SRC 2 Vc Harm[7] Volts Source 2 phase C voltage ninth harmonic
8198 SRC 2 Vc Harm[8] Volts Source 2 phase C voltage tenth harmonic
8199 SRC 2 Vc Harm[9] Volts Source 2 phase C voltage eleventh harmonic
8200 SRC 2 Vc Harm[10] Volts Source 2 phase C voltage twelfth harmonic
8201 SRC 2 Vc Harm[11] Volts Source 2 phase C voltage thirteenth harmonic
8202 SRC 2 Vc Harm[12] Volts Source 2 phase C voltage fourteenth harmonic
8203 SRC 2 Vc Harm[13] Volts Source 2 phase C voltage fifteenth harmonic
8204 SRC 2 Vc Harm[14] Volts Source 2 phase C voltage sixteenth harmonic
8205 SRC 2 Vc Harm[15] Volts Source 2 phase C voltage seventeenth harmonic
8206 SRC 2 Vc Harm[16] Volts Source 2 phase C voltage eighteenth harmonic
8207 SRC 2 Vc Harm[17] Volts Source 2 phase C voltage nineteenth harmonic
8208 SRC 2 Vc Harm[18] Volts Source 2 phase C voltage twentieth harmonic
8209 SRC 2 Vc Harm[19] Volts Source 2 phase C voltage twenty-first harmonic
8210 SRC 2 Vc Harm[20] Volts Source 2 phase C voltage twenty-second harmonic
8211 SRC 2 Vc Harm[21] Volts Source 2 phase C voltage twenty-third harmonic
8212 SRC 2 Vc Harm[22] Volts Source 2 phase C voltage twenty-fourth harmonic
8213 SRC 2 Vc Harm[23] Volts Source 2 phase C voltage twenty-fifth harmonic
8214 SRC 3 Va THD --- Source 3 phase A voltage total harmonic distortion (THD)
8215 SRC 3 Va Harm[0] Volts Source 3 phase A voltage second harmonic
8216 SRC 3 Va Harm[1] Volts Source 3 phase A voltage third harmonic
8217 SRC 3 Va Harm[2] Volts Source 3 phase A voltage fourth harmonic
8218 SRC 3 Va Harm[3] Volts Source 3 phase A voltage fifth harmonic
8219 SRC 3 Va Harm[4] Volts Source 3 phase A voltage sixth harmonic
8220 SRC 3 Va Harm[5] Volts Source 3 phase A voltage seventh harmonic
8221 SRC 3 Va Harm[6] Volts Source 3 phase A voltage eighth harmonic
8222 SRC 3 Va Harm[7] Volts Source 3 phase A voltage ninth harmonic
8223 SRC 3 Va Harm[8] Volts Source 3 phase A voltage tenth harmonic
8224 SRC 3 Va Harm[9] Volts Source 3 phase A voltage eleventh harmonic
8225 SRC 3 Va Harm[10] Volts Source 3 phase A voltage twelfth harmonic
8226 SRC 3 Va Harm[11] Volts Source 3 phase A voltage thirteenth harmonic
8227 SRC 3 Va Harm[12] Volts Source 3 phase A voltage fourteenth harmonic
8228 SRC 3 Va Harm[13] Volts Source 3 phase A voltage fifteenth harmonic
8229 SRC 3 Va Harm[14] Volts Source 3 phase A voltage sixteenth harmonic
8230 SRC 3 Va Harm[15] Volts Source 3 phase A voltage seventeenth harmonic
8231 SRC 3 Va Harm[16] Volts Source 3 phase A voltage eighteenth harmonic
8232 SRC 3 Va Harm[17] Volts Source 3 phase A voltage nineteenth harmonic
8233 SRC 3 Va Harm[18] Volts Source 3 phase A voltage twentieth harmonic
8234 SRC 3 Va Harm[19] Volts Source 3 phase A voltage twenty-first harmonic
8235 SRC 3 Va Harm[20] Volts Source 3 phase A voltage twenty-second harmonic
8236 SRC 3 Va Harm[21] Volts Source 3 phase A voltage twenty-third harmonic

A-10 G60 Generator Protection System GE Multilin


APPENDIX A A.1 PARAMETER LISTS

Table A–1: FLEXANALOG DATA ITEMS (Sheet 11 of 23)


ADDRESS FLEXANALOG NAME UNITS DESCRIPTION A
8237 SRC 3 Va Harm[22] Volts Source 3 phase A voltage twenty-fourth harmonic
8238 SRC 3 Va Harm[23] Volts Source 3 phase A voltage twenty-fifth harmonic
8239 SRC 3 Vb THD --- Source 3 phase B voltage total harmonic distortion (THD)
8240 SRC 3 Vb Harm[0] Volts Source 3 phase B voltage second harmonic
8241 SRC 3 Vb Harm[1] Volts Source 3 phase B voltage third harmonic
8242 SRC 3 Vb Harm[2] Volts Source 3 phase B voltage fourth harmonic
8243 SRC 3 Vb Harm[3] Volts Source 3 phase B voltage fifth harmonic
8244 SRC 3 Vb Harm[4] Volts Source 3 phase B voltage sixth harmonic
8245 SRC 3 Vb Harm[5] Volts Source 3 phase B voltage seventh harmonic
8246 SRC 3 Vb Harm[6] Volts Source 3 phase B voltage eighth harmonic
8247 SRC 3 Vb Harm[7] Volts Source 3 phase B voltage ninth harmonic
8248 SRC 3 Vb Harm[8] Volts Source 3 phase B voltage tenth harmonic
8249 SRC 3 Vb Harm[9] Volts Source 3 phase B voltage eleventh harmonic
8250 SRC 3 Vb Harm[10] Volts Source 3 phase B voltage twelfth harmonic
8251 SRC 3 Vb Harm[11] Volts Source 3 phase B voltage thirteenth harmonic
8252 SRC 3 Vb Harm[12] Volts Source 3 phase B voltage fourteenth harmonic
8253 SRC 3 Vb Harm[13] Volts Source 3 phase B voltage fifteenth harmonic
8254 SRC 3 Vb Harm[14] Volts Source 3 phase B voltage sixteenth harmonic
8255 SRC 3 Vb Harm[15] Volts Source 3 phase B voltage seventeenth harmonic
8256 SRC 3 Vb Harm[16] Volts Source 3 phase B voltage eighteenth harmonic
8257 SRC 3 Vb Harm[17] Volts Source 3 phase B voltage nineteenth harmonic
8258 SRC 3 Vb Harm[18] Volts Source 3 phase B voltage twentieth harmonic
8259 SRC 3 Vb Harm[19] Volts Source 3 phase B voltage twenty-first harmonic
8260 SRC 3 Vb Harm[20] Volts Source 3 phase B voltage twenty-second harmonic
8261 SRC 3 Vb Harm[21] Volts Source 3 phase B voltage twenty-third harmonic
8262 SRC 3 Vb Harm[22] Volts Source 3 phase B voltage twenty-fourth harmonic
8263 SRC 3 Vb Harm[23] Volts Source 3 phase B voltage twenty-fifth harmonic
8264 SRC 3 Vc THD --- Source 3 phase C voltage total harmonic distortion (THD)
8265 SRC 3 Vc Harm[0] Volts Source 3 phase C voltage second harmonic
8266 SRC 3 Vc Harm[1] Volts Source 3 phase C voltage third harmonic
8267 SRC 3 Vc Harm[2] Volts Source 3 phase C voltage fourth harmonic
8268 SRC 3 Vc Harm[3] Volts Source 3 phase C voltage fifth harmonic
8269 SRC 3 Vc Harm[4] Volts Source 3 phase C voltage sixth harmonic
8270 SRC 3 Vc Harm[5] Volts Source 3 phase C voltage seventh harmonic
8271 SRC 3 Vc Harm[6] Volts Source 3 phase C voltage eighth harmonic
8272 SRC 3 Vc Harm[7] Volts Source 3 phase C voltage ninth harmonic
8273 SRC 3 Vc Harm[8] Volts Source 3 phase C voltage tenth harmonic
8274 SRC 3 Vc Harm[9] Volts Source 3 phase C voltage eleventh harmonic
8275 SRC 3 Vc Harm[10] Volts Source 3 phase C voltage twelfth harmonic
8276 SRC 3 Vc Harm[11] Volts Source 3 phase C voltage thirteenth harmonic
8277 SRC 3 Vc Harm[12] Volts Source 3 phase C voltage fourteenth harmonic
8278 SRC 3 Vc Harm[13] Volts Source 3 phase C voltage fifteenth harmonic
8279 SRC 3 Vc Harm[14] Volts Source 3 phase C voltage sixteenth harmonic
8280 SRC 3 Vc Harm[15] Volts Source 3 phase C voltage seventeenth harmonic
8281 SRC 3 Vc Harm[16] Volts Source 3 phase C voltage eighteenth harmonic
8282 SRC 3 Vc Harm[17] Volts Source 3 phase C voltage nineteenth harmonic
8283 SRC 3 Vc Harm[18] Volts Source 3 phase C voltage twentieth harmonic

GE Multilin G60 Generator Protection System A-11


A.1 PARAMETER LISTS APPENDIX A

Table A–1: FLEXANALOG DATA ITEMS (Sheet 12 of 23)

A ADDRESS
8284
FLEXANALOG NAME
SRC 3 Vc Harm[19]
UNITS
Volts
DESCRIPTION
Source 3 phase C voltage twenty-first harmonic
8285 SRC 3 Vc Harm[20] Volts Source 3 phase C voltage twenty-second harmonic
8286 SRC 3 Vc Harm[21] Volts Source 3 phase C voltage twenty-third harmonic
8287 SRC 3 Vc Harm[22] Volts Source 3 phase C voltage twenty-fourth harmonic
8288 SRC 3 Vc Harm[23] Volts Source 3 phase C voltage twenty-fifth harmonic
8289 SRC 4 Va THD --- Source 4 phase A voltage total harmonic distortion (THD)
8290 SRC 4 Va Harm[0] Volts Source 4 phase A voltage second harmonic
8291 SRC 4 Va Harm[1] Volts Source 4 phase A voltage third harmonic
8292 SRC 4 Va Harm[2] Volts Source 4 phase A voltage fourth harmonic
8293 SRC 4 Va Harm[3] Volts Source 4 phase A voltage fifth harmonic
8294 SRC 4 Va Harm[4] Volts Source 4 phase A voltage sixth harmonic
8295 SRC 4 Va Harm[5] Volts Source 4 phase A voltage seventh harmonic
8296 SRC 4 Va Harm[6] Volts Source 4 phase A voltage eighth harmonic
8297 SRC 4 Va Harm[7] Volts Source 4 phase A voltage ninth harmonic
8298 SRC 4 Va Harm[8] Volts Source 4 phase A voltage tenth harmonic
8299 SRC 4 Va Harm[9] Volts Source 4 phase A voltage eleventh harmonic
8300 SRC 4 Va Harm[10] Volts Source 4 phase A voltage twelfth harmonic
8301 SRC 4 Va Harm[11] Volts Source 4 phase A voltage thirteenth harmonic
8302 SRC 4 Va Harm[12] Volts Source 4 phase A voltage fourteenth harmonic
8303 SRC 4 Va Harm[13] Volts Source 4 phase A voltage fifteenth harmonic
8304 SRC 4 Va Harm[14] Volts Source 4 phase A voltage sixteenth harmonic
8305 SRC 4 Va Harm[15] Volts Source 4 phase A voltage seventeenth harmonic
8306 SRC 4 Va Harm[16] Volts Source 4 phase A voltage eighteenth harmonic
8307 SRC 4 Va Harm[17] Volts Source 4 phase A voltage nineteenth harmonic
8308 SRC 4 Va Harm[18] Volts Source 4 phase A voltage twentieth harmonic
8309 SRC 4 Va Harm[19] Volts Source 4 phase A voltage twenty-first harmonic
8310 SRC 4 Va Harm[20] Volts Source 4 phase A voltage twenty-second harmonic
8311 SRC 4 Va Harm[21] Volts Source 4 phase A voltage twenty-third harmonic
8312 SRC 4 Va Harm[22] Volts Source 4 phase A voltage twenty-fourth harmonic
8313 SRC 4 Va Harm[23] Volts Source 4 phase A voltage twenty-fifth harmonic
8314 SRC 4 Vb THD --- Source 4 phase B voltage total harmonic distortion (THD)
8315 SRC 4 Vb Harm[0] Volts Source 4 phase B voltage second harmonic
8316 SRC 4 Vb Harm[1] Volts Source 4 phase B voltage third harmonic
8317 SRC 4 Vb Harm[2] Volts Source 4 phase B voltage fourth harmonic
8318 SRC 4 Vb Harm[3] Volts Source 4 phase B voltage fifth harmonic
8319 SRC 4 Vb Harm[4] Volts Source 4 phase B voltage sixth harmonic
8320 SRC 4 Vb Harm[5] Volts Source 4 phase B voltage seventh harmonic
8321 SRC 4 Vb Harm[6] Volts Source 4 phase B voltage eighth harmonic
8322 SRC 4 Vb Harm[7] Volts Source 4 phase B voltage ninth harmonic
8323 SRC 4 Vb Harm[8] Volts Source 4 phase B voltage tenth harmonic
8324 SRC 4 Vb Harm[9] Volts Source 4 phase B voltage eleventh harmonic
8325 SRC 4 Vb Harm[10] Volts Source 4 phase B voltage twelfth harmonic
8326 SRC 4 Vb Harm[11] Volts Source 4 phase B voltage thirteenth harmonic
8327 SRC 4 Vb Harm[12] Volts Source 4 phase B voltage fourteenth harmonic
8328 SRC 4 Vb Harm[13] Volts Source 4 phase B voltage fifteenth harmonic
8329 SRC 4 Vb Harm[14] Volts Source 4 phase B voltage sixteenth harmonic
8330 SRC 4 Vb Harm[15] Volts Source 4 phase B voltage seventeenth harmonic

A-12 G60 Generator Protection System GE Multilin


APPENDIX A A.1 PARAMETER LISTS

Table A–1: FLEXANALOG DATA ITEMS (Sheet 13 of 23)


ADDRESS FLEXANALOG NAME UNITS DESCRIPTION A
8331 SRC 4 Vb Harm[16] Volts Source 4 phase B voltage eighteenth harmonic
8332 SRC 4 Vb Harm[17] Volts Source 4 phase B voltage nineteenth harmonic
8333 SRC 4 Vb Harm[18] Volts Source 4 phase B voltage twentieth harmonic
8334 SRC 4 Vb Harm[19] Volts Source 4 phase B voltage twenty-first harmonic
8335 SRC 4 Vb Harm[20] Volts Source 4 phase B voltage twenty-second harmonic
8336 SRC 4 Vb Harm[21] Volts Source 4 phase B voltage twenty-third harmonic
8337 SRC 4 Vb Harm[22] Volts Source 4 phase B voltage twenty-fourth harmonic
8338 SRC 4 Vb Harm[23] Volts Source 4 phase B voltage twenty-fifth harmonic
8339 SRC 4 Vc THD --- Source 4 phase C voltage total harmonic distortion (THD)
8340 SRC 4 Vc Harm[0] Volts Source 4 phase C voltage second harmonic
8341 SRC 4 Vc Harm[1] Volts Source 4 phase C voltage third harmonic
8342 SRC 4 Vc Harm[2] Volts Source 4 phase C voltage fourth harmonic
8343 SRC 4 Vc Harm[3] Volts Source 4 phase C voltage fifth harmonic
8344 SRC 4 Vc Harm[4] Volts Source 4 phase C voltage sixth harmonic
8345 SRC 4 Vc Harm[5] Volts Source 4 phase C voltage seventh harmonic
8346 SRC 4 Vc Harm[6] Volts Source 4 phase C voltage eighth harmonic
8347 SRC 4 Vc Harm[7] Volts Source 4 phase C voltage ninth harmonic
8348 SRC 4 Vc Harm[8] Volts Source 4 phase C voltage tenth harmonic
8349 SRC 4 Vc Harm[9] Volts Source 4 phase C voltage eleventh harmonic
8350 SRC 4 Vc Harm[10] Volts Source 4 phase C voltage twelfth harmonic
8351 SRC 4 Vc Harm[11] Volts Source 4 phase C voltage thirteenth harmonic
8352 SRC 4 Vc Harm[12] Volts Source 4 phase C voltage fourteenth harmonic
8353 SRC 4 Vc Harm[13] Volts Source 4 phase C voltage fifteenth harmonic
8354 SRC 4 Vc Harm[14] Volts Source 4 phase C voltage sixteenth harmonic
8355 SRC 4 Vc Harm[15] Volts Source 4 phase C voltage seventeenth harmonic
8356 SRC 4 Vc Harm[16] Volts Source 4 phase C voltage eighteenth harmonic
8357 SRC 4 Vc Harm[17] Volts Source 4 phase C voltage nineteenth harmonic
8358 SRC 4 Vc Harm[18] Volts Source 4 phase C voltage twentieth harmonic
8359 SRC 4 Vc Harm[19] Volts Source 4 phase C voltage twenty-first harmonic
8360 SRC 4 Vc Harm[20] Volts Source 4 phase C voltage twenty-second harmonic
8361 SRC 4 Vc Harm[21] Volts Source 4 phase C voltage twenty-third harmonic
8362 SRC 4 Vc Harm[22] Volts Source 4 phase C voltage twenty-fourth harmonic
8363 SRC 4 Vc Harm[23] Volts Source 4 phase C voltage twenty-fifth harmonic
9216 Synchchk 1 Delta V Volts Synchrocheck 1 delta voltage
9218 Synchchk 1 Delta F Hz Synchrocheck 1 delta frequency
9219 Synchchk 1 Delta Phs Degrees Synchrocheck 1 delta phase
9220 Synchchk 2 Delta V Volts Synchrocheck 2 delta voltage
9222 Synchchk 2 Delta F Hz Synchrocheck 2 delta frequency
9223 Synchchk 2 Delta Phs Degrees Synchrocheck 2 delta phase
9536 PMU 1 Va Mag Volts Phasor measurement unit 1 phase A voltage magnitude
9538 PMU 1 Va Angle Degrees Phasor measurement unit 1 phase A voltage angle
9539 PMU 1 Vb Mag Volts Phasor measurement unit 1 phase B voltage magnitude
9541 PMU 1 Vb Angle Degrees Phasor measurement unit 1 phase B voltage angle
9542 PMU 1 Vc Mag Volts Phasor measurement unit 1 phase C voltage magnitude
9544 PMU 1 Vc Angle Degrees Phasor measurement unit 1 phase C voltage angle
9545 PMU 1 Vx Mag Volts Phasor measurement unit 1 auxiliary voltage magnitude
9547 PMU 1 Vx Angle Degrees Phasor measurement unit 1 auxiliary voltage angle

GE Multilin G60 Generator Protection System A-13


A.1 PARAMETER LISTS APPENDIX A

Table A–1: FLEXANALOG DATA ITEMS (Sheet 14 of 23)

A ADDRESS
9548
FLEXANALOG NAME
PMU 1 V1 Mag
UNITS
Volts
DESCRIPTION
Phasor measurement unit 1 positive-sequence voltage magnitude
9550 PMU 1 V1 Angle Degrees Phasor measurement unit 1 positive-sequence voltage angle
9551 PMU 1 V2 Mag Volts Phasor measurement unit 1 negative-sequence voltage magnitude
9553 PMU 1 V2 Angle Degrees Phasor measurement unit 1 negative-sequence voltage angle
9554 PMU 1 V0 Mag Volts Phasor measurement unit 1 zero-sequence voltage magnitude
9556 PMU 1 V0 Angle Degrees Phasor measurement unit 1 zero-sequence voltage angle
9557 PMU 1 Ia Mag Amps Phasor measurement unit 1 phase A current magnitude
9559 PMU 1 Ia Angle Degrees Phasor measurement unit 1 phase A current angle
9560 PMU 1 Ib Mag Amps Phasor measurement unit 1 phase B current magnitude
9562 PMU 1 Ib Angle Degrees Phasor measurement unit 1 phase B current angle
9563 PMU 1 Ic Mag Amps Phasor measurement unit 1 phase C current magnitude
9565 PMU 1 Ic Angle Degrees Phasor measurement unit 1 phase C current angle
9566 PMU 1 Ig Mag Amps Phasor measurement unit 1 ground current magnitude
9568 PMU 1 Ig Angle Degrees Phasor measurement unit 1 ground current angle
9569 PMU 1 I1 Mag Amps Phasor measurement unit 1 positive-sequence current magnitude
9571 PMU 1 I1 Angle Degrees Phasor measurement unit 1 positive-sequence current angle
9572 PMU 1 I2 Mag Amps Phasor measurement unit 1 negative-sequence current magnitude
9574 PMU 1 I2 Angle Degrees Phasor measurement unit 1 negative-sequence current angle
9575 PMU 1 I0 Mag Amps Phasor measurement unit 1 zero-sequence current magnitude
9577 PMU 1 I0 Angle Degrees Phasor measurement unit 1 zero-sequence current angle
9578 PMU 1 Freq Hz Phasor measurement unit 1 frequency
9580 PMU 1 df dt Hz/s Phasor measurement unit 1 rate of change of frequency
9581 PMU 1 Conf Ch --- Phasor measurement unit 1 configuration change counter
10240 SRC 1 Ia THD --- Source 1 phase A current total harmonic distortion
10241 SRC 1 Ia Harm[0] Amps Source 1 phase A current second harmonic
10242 SRC 1 Ia Harm[1] Amps Source 1 phase A current third harmonic
10243 SRC 1 Ia Harm[2] Amps Source 1 phase A current fourth harmonic
10244 SRC 1 Ia Harm[3] Amps Source 1 phase A current fifth harmonic
10245 SRC 1 Ia Harm[4] Amps Source 1 phase A current sixth harmonic
10246 SRC 1 Ia Harm[5] Amps Source 1 phase A current seventh harmonic
10247 SRC 1 Ia Harm[6] Amps Source 1 phase A current eighth harmonic
10248 SRC 1 Ia Harm[7] Amps Source 1 phase A current ninth harmonic
10249 SRC 1 Ia Harm[8] Amps Source 1 phase A current tenth harmonic
10250 SRC 1 Ia Harm[9] Amps Source 1 phase A current eleventh harmonic
10251 SRC 1 Ia Harm[10] Amps Source 1 phase A current twelfth harmonic
10252 SRC 1 Ia Harm[11] Amps Source 1 phase A current thirteenth harmonic
10253 SRC 1 Ia Harm[12] Amps Source 1 phase A current fourteenth harmonic
10254 SRC 1 Ia Harm[13] Amps Source 1 phase A current fifteenth harmonic
10255 SRC 1 Ia Harm[14] Amps Source 1 phase A current sixteenth harmonic
10256 SRC 1 Ia Harm[15] Amps Source 1 phase A current seventeenth harmonic
10257 SRC 1 Ia Harm[16] Amps Source 1 phase A current eighteenth harmonic
10258 SRC 1 Ia Harm[17] Amps Source 1 phase A current nineteenth harmonic
10259 SRC 1 Ia Harm[18] Amps Source 1 phase A current twentieth harmonic
10260 SRC 1 Ia Harm[19] Amps Source 1 phase A current twenty-first harmonic
10261 SRC 1 Ia Harm[20] Amps Source 1 phase A current twenty-second harmonic
10262 SRC 1 Ia Harm[21] Amps Source 1 phase A current twenty-third harmonic
10263 SRC 1 Ia Harm[22] Amps Source 1 phase A current twenty-fourth harmonic

A-14 G60 Generator Protection System GE Multilin


APPENDIX A A.1 PARAMETER LISTS

Table A–1: FLEXANALOG DATA ITEMS (Sheet 15 of 23)


ADDRESS FLEXANALOG NAME UNITS DESCRIPTION A
10264 SRC 1 Ia Harm[23] Amps Source 1 phase A current twenty-fifth harmonic
10273 SRC 1 Ib THD --- Source 1 phase B current total harmonic distortion
10274 SRC 1 Ib Harm[0] Amps Source 1 phase B current second harmonic
10275 SRC 1 Ib Harm[1] Amps Source 1 phase B current third harmonic
10276 SRC 1 Ib Harm[2] Amps Source 1 phase B current fourth harmonic
10277 SRC 1 Ib Harm[3] Amps Source 1 phase B current fifth harmonic
10278 SRC 1 Ib Harm[4] Amps Source 1 phase B current sixth harmonic
10279 SRC 1 Ib Harm[5] Amps Source 1 phase B current seventh harmonic
10280 SRC 1 Ib Harm[6] Amps Source 1 phase B current eighth harmonic
10281 SRC 1 Ib Harm[7] Amps Source 1 phase B current ninth harmonic
10282 SRC 1 Ib Harm[8] Amps Source 1 phase B current tenth harmonic
10283 SRC 1 Ib Harm[9] Amps Source 1 phase B current eleventh harmonic
10284 SRC 1 Ib Harm[10] Amps Source 1 phase B current twelfth harmonic
10285 SRC 1 Ib Harm[11] Amps Source 1 phase B current thirteenth harmonic
10286 SRC 1 Ib Harm[12] Amps Source 1 phase B current fourteenth harmonic
10287 SRC 1 Ib Harm[13] Amps Source 1 phase B current fifteenth harmonic
10288 SRC 1 Ib Harm[14] Amps Source 1 phase B current sixteenth harmonic
10289 SRC 1 Ib Harm[15] Amps Source 1 phase B current seventeenth harmonic
10290 SRC 1 Ib Harm[16] Amps Source 1 phase B current eighteenth harmonic
10291 SRC 1 Ib Harm[17] Amps Source 1 phase B current nineteenth harmonic
10292 SRC 1 Ib Harm[18] Amps Source 1 phase B current twentieth harmonic
10293 SRC 1 Ib Harm[19] Amps Source 1 phase B current twenty-first harmonic
10294 SRC 1 Ib Harm[20] Amps Source 1 phase B current twenty-second harmonic
10295 SRC 1 Ib Harm[21] Amps Source 1 phase B current twenty-third harmonic
10296 SRC 1 Ib Harm[22] Amps Source 1 phase B current twenty-fourth harmonic
10297 SRC 1 Ib Harm[23] Amps Source 1 phase B current twenty-fifth harmonic
10306 SRC 1 Ic THD --- Source 1 phase C current total harmonic distortion
10307 SRC 1 Ic Harm[0] Amps Source 1 phase C current second harmonic
10308 SRC 1 Ic Harm[1] Amps Source 1 phase C current third harmonic
10309 SRC 1 Ic Harm[2] Amps Source 1 phase C current fourth harmonic
10310 SRC 1 Ic Harm[3] Amps Source 1 phase C current fifth harmonic
10311 SRC 1 Ic Harm[4] Amps Source 1 phase C current sixth harmonic
10312 SRC 1 Ic Harm[5] Amps Source 1 phase C current seventh harmonic
10313 SRC 1 Ic Harm[6] Amps Source 1 phase C current eighth harmonic
10314 SRC 1 Ic Harm[7] Amps Source 1 phase C current ninth harmonic
10315 SRC 1 Ic Harm[8] Amps Source 1 phase C current tenth harmonic
10316 SRC 1 Ic Harm[9] Amps Source 1 phase C current eleventh harmonic
10317 SRC 1 Ic Harm[10] Amps Source 1 phase C current twelfth harmonic
10318 SRC 1 Ic Harm[11] Amps Source 1 phase C current thirteenth harmonic
10319 SRC 1 Ic Harm[12] Amps Source 1 phase C current fourteenth harmonic
10320 SRC 1 Ic Harm[13] Amps Source 1 phase C current fifteenth harmonic
10321 SRC 1 Ic Harm[14] Amps Source 1 phase C current sixteenth harmonic
10322 SRC 1 Ic Harm[15] Amps Source 1 phase C current seventeenth harmonic
10323 SRC 1 Ic Harm[16] Amps Source 1 phase C current eighteenth harmonic
10324 SRC 1 Ic Harm[17] Amps Source 1 phase C current nineteenth harmonic
10325 SRC 1 Ic Harm[18] Amps Source 1 phase C current twentieth harmonic
10326 SRC 1 Ic Harm[19] Amps Source 1 phase C current twenty-first harmonic

GE Multilin G60 Generator Protection System A-15


A.1 PARAMETER LISTS APPENDIX A

Table A–1: FLEXANALOG DATA ITEMS (Sheet 16 of 23)

A ADDRESS
10327
FLEXANALOG NAME
SRC 1 Ic Harm[20]
UNITS
Amps
DESCRIPTION
Source 1 phase C current twenty-second harmonic
10328 SRC 1 Ic Harm[21] Amps Source 1 phase C current twenty-third harmonic
10329 SRC 1 Ic Harm[22] Amps Source 1 phase C current twenty-fourth harmonic
10330 SRC 1 Ic Harm[23] Amps Source 1 phase C current twenty-fifth harmonic
10339 SRC 2 Ia THD --- Source 2 phase A current total harmonic distortion
10340 SRC 2 Ia Harm[0] Amps Source 2 phase A current second harmonic
10341 SRC 2 Ia Harm[1] Amps Source 2 phase A current third harmonic
10342 SRC 2 Ia Harm[2] Amps Source 2 phase A current fourth harmonic
10343 SRC 2 Ia Harm[3] Amps Source 2 phase A current fifth harmonic
10344 SRC 2 Ia Harm[4] Amps Source 2 phase A current sixth harmonic
10345 SRC 2 Ia Harm[5] Amps Source 2 phase A current seventh harmonic
10346 SRC 2 Ia Harm[6] Amps Source 2 phase A current eighth harmonic
10347 SRC 2 Ia Harm[7] Amps Source 2 phase A current ninth harmonic
10348 SRC 2 Ia Harm[8] Amps Source 2 phase A current tenth harmonic
10349 SRC 2 Ia Harm[9] Amps Source 2 phase A current eleventh harmonic
10350 SRC 2 Ia Harm[10] Amps Source 2 phase A current twelfth harmonic
10351 SRC 2 Ia Harm[11] Amps Source 2 phase A current thirteenth harmonic
10352 SRC 2 Ia Harm[12] Amps Source 2 phase A current fourteenth harmonic
10353 SRC 2 Ia Harm[13] Amps Source 2 phase A current fifteenth harmonic
10354 SRC 2 Ia Harm[14] Amps Source 2 phase A current sixteenth harmonic
10355 SRC 2 Ia Harm[15] Amps Source 2 phase A current seventeenth harmonic
10356 SRC 2 Ia Harm[16] Amps Source 2 phase A current eighteenth harmonic
10357 SRC 2 Ia Harm[17] Amps Source 2 phase A current nineteenth harmonic
10358 SRC 2 Ia Harm[18] Amps Source 2 phase A current twentieth harmonic
10359 SRC 2 Ia Harm[19] Amps Source 2 phase A current twenty-first harmonic
10360 SRC 2 Ia Harm[20] Amps Source 2 phase A current twenty-second harmonic
10361 SRC 2 Ia Harm[21] Amps Source 2 phase A current twenty-third harmonic
10362 SRC 2 Ia Harm[22] Amps Source 2 phase A current twenty-fourth harmonic
10363 SRC 2 Ia Harm[23] Amps Source 2 phase A current twenty-fifth harmonic
10372 SRC 2 Ib THD --- Source 2 phase B current total harmonic distortion
10373 SRC 2 Ib Harm[0] Amps Source 2 phase B current second harmonic
10374 SRC 2 Ib Harm[1] Amps Source 2 phase B current third harmonic
10375 SRC 2 Ib Harm[2] Amps Source 2 phase B current fourth harmonic
10376 SRC 2 Ib Harm[3] Amps Source 2 phase B current fifth harmonic
10377 SRC 2 Ib Harm[4] Amps Source 2 phase B current sixth harmonic
10378 SRC 2 Ib Harm[5] Amps Source 2 phase B current seventh harmonic
10379 SRC 2 Ib Harm[6] Amps Source 2 phase B current eighth harmonic
10380 SRC 2 Ib Harm[7] Amps Source 2 phase B current ninth harmonic
10381 SRC 2 Ib Harm[8] Amps Source 2 phase B current tenth harmonic
10382 SRC 2 Ib Harm[9] Amps Source 2 phase B current eleventh harmonic
10383 SRC 2 Ib Harm[10] Amps Source 2 phase B current twelfth harmonic
10384 SRC 2 Ib Harm[11] Amps Source 2 phase B current thirteenth harmonic
10385 SRC 2 Ib Harm[12] Amps Source 2 phase B current fourteenth harmonic
10386 SRC 2 Ib Harm[13] Amps Source 2 phase B current fifteenth harmonic
10387 SRC 2 Ib Harm[14] Amps Source 2 phase B current sixteenth harmonic
10388 SRC 2 Ib Harm[15] Amps Source 2 phase B current seventeenth harmonic
10389 SRC 2 Ib Harm[16] Amps Source 2 phase B current eighteenth harmonic

A-16 G60 Generator Protection System GE Multilin


APPENDIX A A.1 PARAMETER LISTS

Table A–1: FLEXANALOG DATA ITEMS (Sheet 17 of 23)


ADDRESS FLEXANALOG NAME UNITS DESCRIPTION A
10390 SRC 2 Ib Harm[17] Amps Source 2 phase B current nineteenth harmonic
10391 SRC 2 Ib Harm[18] Amps Source 2 phase B current twentieth harmonic
10392 SRC 2 Ib Harm[19] Amps Source 2 phase B current twenty-first harmonic
10393 SRC 2 Ib Harm[20] Amps Source 2 phase B current twenty-second harmonic
10394 SRC 2 Ib Harm[21] Amps Source 2 phase B current twenty-third harmonic
10395 SRC 2 Ib Harm[22] Amps Source 2 phase B current twenty-fourth harmonic
10396 SRC 2 Ib Harm[23] Amps Source 2 phase B current twenty-fifth harmonic
10405 SRC 2 Ic THD --- Source 2 phase C current total harmonic distortion
10406 SRC 2 Ic Harm[0] Amps Source 2 phase C current second harmonic
10407 SRC 2 Ic Harm[1] Amps Source 2 phase C current third harmonic
10408 SRC 2 Ic Harm[2] Amps Source 2 phase C current fourth harmonic
10409 SRC 2 Ic Harm[3] Amps Source 2 phase C current fifth harmonic
10410 SRC 2 Ic Harm[4] Amps Source 2 phase C current sixth harmonic
10411 SRC 2 Ic Harm[5] Amps Source 2 phase C current seventh harmonic
10412 SRC 2 Ic Harm[6] Amps Source 2 phase C current eighth harmonic
10413 SRC 2 Ic Harm[7] Amps Source 2 phase C current ninth harmonic
10414 SRC 2 Ic Harm[8] Amps Source 2 phase C current tenth harmonic
10415 SRC 2 Ic Harm[9] Amps Source 2 phase C current eleventh harmonic
10416 SRC 2 Ic Harm[10] Amps Source 2 phase C current twelfth harmonic
10417 SRC 2 Ic Harm[11] Amps Source 2 phase C current thirteenth harmonic
10418 SRC 2 Ic Harm[12] Amps Source 2 phase C current fourteenth harmonic
10419 SRC 2 Ic Harm[13] Amps Source 2 phase C current fifteenth harmonic
10420 SRC 2 Ic Harm[14] Amps Source 2 phase C current sixteenth harmonic
10421 SRC 2 Ic Harm[15] Amps Source 2 phase C current seventeenth harmonic
10422 SRC 2 Ic Harm[16] Amps Source 2 phase C current eighteenth harmonic
10423 SRC 2 Ic Harm[17] Amps Source 2 phase C current nineteenth harmonic
10424 SRC 2 Ic Harm[18] Amps Source 2 phase C current twentieth harmonic
10425 SRC 2 Ic Harm[19] Amps Source 2 phase C current twenty-first harmonic
10426 SRC 2 Ic Harm[20] Amps Source 2 phase C current twenty-second harmonic
10427 SRC 2 Ic Harm[21] Amps Source 2 phase C current twenty-third harmonic
10428 SRC 2 Ic Harm[22] Amps Source 2 phase C current twenty-fourth harmonic
10429 SRC 2 Ic Harm[23] Amps Source 2 phase C current twenty-fifth harmonic
10438 SRC 3 Ia THD --- Source 3 phase A current total harmonic distortion
10439 SRC 3 Ia Harm[0] Amps Source 3 phase A current second harmonic
10440 SRC 3 Ia Harm[1] Amps Source 3 phase A current third harmonic
10441 SRC 3 Ia Harm[2] Amps Source 3 phase A current fourth harmonic
10442 SRC 3 Ia Harm[3] Amps Source 3 phase A current fifth harmonic
10443 SRC 3 Ia Harm[4] Amps Source 3 phase A current sixth harmonic
10444 SRC 3 Ia Harm[5] Amps Source 3 phase A current seventh harmonic
10445 SRC 3 Ia Harm[6] Amps Source 3 phase A current eighth harmonic
10446 SRC 3 Ia Harm[7] Amps Source 3 phase A current ninth harmonic
10447 SRC 3 Ia Harm[8] Amps Source 3 phase A current tenth harmonic
10448 SRC 3 Ia Harm[9] Amps Source 3 phase A current eleventh harmonic
10449 SRC 3 Ia Harm[10] Amps Source 3 phase A current twelfth harmonic
10450 SRC 3 Ia Harm[11] Amps Source 3 phase A current thirteenth harmonic
10451 SRC 3 Ia Harm[12] Amps Source 3 phase A current fourteenth harmonic
10452 SRC 3 Ia Harm[13] Amps Source 3 phase A current fifteenth harmonic

GE Multilin G60 Generator Protection System A-17


A.1 PARAMETER LISTS APPENDIX A

Table A–1: FLEXANALOG DATA ITEMS (Sheet 18 of 23)

A ADDRESS
10453
FLEXANALOG NAME
SRC 3 Ia Harm[14]
UNITS
Amps
DESCRIPTION
Source 3 phase A current sixteenth harmonic
10454 SRC 3 Ia Harm[15] Amps Source 3 phase A current seventeenth harmonic
10455 SRC 3 Ia Harm[16] Amps Source 3 phase A current eighteenth harmonic
10456 SRC 3 Ia Harm[17] Amps Source 3 phase A current nineteenth harmonic
10457 SRC 3 Ia Harm[18] Amps Source 3 phase A current twentieth harmonic
10458 SRC 3 Ia Harm[19] Amps Source 3 phase A current twenty-first harmonic
10459 SRC 3 Ia Harm[20] Amps Source 3 phase A current twenty-second harmonic
10460 SRC 3 Ia Harm[21] Amps Source 3 phase A current twenty-third harmonic
10461 SRC 3 Ia Harm[22] Amps Source 3 phase A current twenty-fourth harmonic
10462 SRC 3 Ia Harm[23] Amps Source 3 phase A current twenty-fifth harmonic
10471 SRC 3 Ib THD --- Source 3 phase B current total harmonic distortion
10472 SRC 3 Ib Harm[0] Amps Source 3 phase B current second harmonic
10473 SRC 3 Ib Harm[1] Amps Source 3 phase B current third harmonic
10474 SRC 3 Ib Harm[2] Amps Source 3 phase B current fourth harmonic
10475 SRC 3 Ib Harm[3] Amps Source 3 phase B current fifth harmonic
10476 SRC 3 Ib Harm[4] Amps Source 3 phase B current sixth harmonic
10477 SRC 3 Ib Harm[5] Amps Source 3 phase B current seventh harmonic
10478 SRC 3 Ib Harm[6] Amps Source 3 phase B current eighth harmonic
10479 SRC 3 Ib Harm[7] Amps Source 3 phase B current ninth harmonic
10480 SRC 3 Ib Harm[8] Amps Source 3 phase B current tenth harmonic
10481 SRC 3 Ib Harm[9] Amps Source 3 phase B current eleventh harmonic
10482 SRC 3 Ib Harm[10] Amps Source 3 phase B current twelfth harmonic
10483 SRC 3 Ib Harm[11] Amps Source 3 phase B current thirteenth harmonic
10484 SRC 3 Ib Harm[12] Amps Source 3 phase B current fourteenth harmonic
10485 SRC 3 Ib Harm[13] Amps Source 3 phase B current fifteenth harmonic
10486 SRC 3 Ib Harm[14] Amps Source 3 phase B current sixteenth harmonic
10487 SRC 3 Ib Harm[15] Amps Source 3 phase B current seventeenth harmonic
10488 SRC 3 Ib Harm[16] Amps Source 3 phase B current eighteenth harmonic
10489 SRC 3 Ib Harm[17] Amps Source 3 phase B current nineteenth harmonic
10490 SRC 3 Ib Harm[18] Amps Source 3 phase B current twentieth harmonic
10491 SRC 3 Ib Harm[19] Amps Source 3 phase B current twenty-first harmonic
10492 SRC 3 Ib Harm[20] Amps Source 3 phase B current twenty-second harmonic
10493 SRC 3 Ib Harm[21] Amps Source 3 phase B current twenty-third harmonic
10494 SRC 3 Ib Harm[22] Amps Source 3 phase B current twenty-fourth harmonic
10495 SRC 3 Ib Harm[23] Amps Source 3 phase B current twenty-fifth harmonic
10504 SRC 3 Ic THD --- Source 3 phase C current total harmonic distortion
10505 SRC 3 Ic Harm[0] Amps Source 3 phase C current second harmonic
10506 SRC 3 Ic Harm[1] Amps Source 3 phase C current third harmonic
10507 SRC 3 Ic Harm[2] Amps Source 3 phase C current fourth harmonic
10508 SRC 3 Ic Harm[3] Amps Source 3 phase C current fifth harmonic
10509 SRC 3 Ic Harm[4] Amps Source 3 phase C current sixth harmonic
10510 SRC 3 Ic Harm[5] Amps Source 3 phase C current seventh harmonic
10511 SRC 3 Ic Harm[6] Amps Source 3 phase C current eighth harmonic
10512 SRC 3 Ic Harm[7] Amps Source 3 phase C current ninth harmonic
10513 SRC 3 Ic Harm[8] Amps Source 3 phase C current tenth harmonic
10514 SRC 3 Ic Harm[9] Amps Source 3 phase C current eleventh harmonic
10515 SRC 3 Ic Harm[10] Amps Source 3 phase C current twelfth harmonic

A-18 G60 Generator Protection System GE Multilin


APPENDIX A A.1 PARAMETER LISTS

Table A–1: FLEXANALOG DATA ITEMS (Sheet 19 of 23)


ADDRESS FLEXANALOG NAME UNITS DESCRIPTION A
10516 SRC 3 Ic Harm[11] Amps Source 3 phase C current thirteenth harmonic
10517 SRC 3 Ic Harm[12] Amps Source 3 phase C current fourteenth harmonic
10518 SRC 3 Ic Harm[13] Amps Source 3 phase C current fifteenth harmonic
10519 SRC 3 Ic Harm[14] Amps Source 3 phase C current sixteenth harmonic
10520 SRC 3 Ic Harm[15] Amps Source 3 phase C current seventeenth harmonic
10521 SRC 3 Ic Harm[16] Amps Source 3 phase C current eighteenth harmonic
10522 SRC 3 Ic Harm[17] Amps Source 3 phase C current nineteenth harmonic
10523 SRC 3 Ic Harm[18] Amps Source 3 phase C current twentieth harmonic
10524 SRC 3 Ic Harm[19] Amps Source 3 phase C current twenty-first harmonic
10525 SRC 3 Ic Harm[20] Amps Source 3 phase C current twenty-second harmonic
10526 SRC 3 Ic Harm[21] Amps Source 3 phase C current twenty-third harmonic
10527 SRC 3 Ic Harm[22] Amps Source 3 phase C current twenty-fourth harmonic
10528 SRC 3 Ic Harm[23] Amps Source 3 phase C current twenty-fifth harmonic
10537 SRC 4 Ia THD --- Source 4 phase A current total harmonic distortion
10538 SRC 4 Ia Harm[0] Amps Source 4 phase A current second harmonic
10539 SRC 4 Ia Harm[1] Amps Source 4 phase A current third harmonic
10540 SRC 4 Ia Harm[2] Amps Source 4 phase A current fourth harmonic
10541 SRC 4 Ia Harm[3] Amps Source 4 phase A current fifth harmonic
10542 SRC 4 Ia Harm[4] Amps Source 4 phase A current sixth harmonic
10543 SRC 4 Ia Harm[5] Amps Source 4 phase A current seventh harmonic
10544 SRC 4 Ia Harm[6] Amps Source 4 phase A current eighth harmonic
10545 SRC 4 Ia Harm[7] Amps Source 4 phase A current ninth harmonic
10546 SRC 4 Ia Harm[8] Amps Source 4 phase A current tenth harmonic
10547 SRC 4 Ia Harm[9] Amps Source 4 phase A current eleventh harmonic
10548 SRC 4 Ia Harm[10] Amps Source 4 phase A current twelfth harmonic
10549 SRC 4 Ia Harm[11] Amps Source 4 phase A current thirteenth harmonic
10550 SRC 4 Ia Harm[12] Amps Source 4 phase A current fourteenth harmonic
10551 SRC 4 Ia Harm[13] Amps Source 4 phase A current fifteenth harmonic
10552 SRC 4 Ia Harm[14] Amps Source 4 phase A current sixteenth harmonic
10553 SRC 4 Ia Harm[15] Amps Source 4 phase A current seventeenth harmonic
10554 SRC 4 Ia Harm[16] Amps Source 4 phase A current eighteenth harmonic
10555 SRC 4 Ia Harm[17] Amps Source 4 phase A current nineteenth harmonic
10556 SRC 4 Ia Harm[18] Amps Source 4 phase A current twentieth harmonic
10557 SRC 4 Ia Harm[19] Amps Source 4 phase A current twenty-first harmonic
10558 SRC 4 Ia Harm[20] Amps Source 4 phase A current twenty-second harmonic
10559 SRC 4 Ia Harm[21] Amps Source 4 phase A current twenty-third harmonic
10560 SRC 4 Ia Harm[22] Amps Source 4 phase A current twenty-fourth harmonic
10561 SRC 4 Ia Harm[23] Amps Source 4 phase A current twenty-fifth harmonic
10570 SRC 4 Ib THD --- Source 4 phase B current total harmonic distortion
10571 SRC 4 Ib Harm[0] Amps Source 4 phase B current second harmonic
10572 SRC 4 Ib Harm[1] Amps Source 4 phase B current third harmonic
10573 SRC 4 Ib Harm[2] Amps Source 4 phase B current fourth harmonic
10574 SRC 4 Ib Harm[3] Amps Source 4 phase B current fifth harmonic
10575 SRC 4 Ib Harm[4] Amps Source 4 phase B current sixth harmonic
10576 SRC 4 Ib Harm[5] Amps Source 4 phase B current seventh harmonic
10577 SRC 4 Ib Harm[6] Amps Source 4 phase B current eighth harmonic
10578 SRC 4 Ib Harm[7] Amps Source 4 phase B current ninth harmonic

GE Multilin G60 Generator Protection System A-19


A.1 PARAMETER LISTS APPENDIX A

Table A–1: FLEXANALOG DATA ITEMS (Sheet 20 of 23)

A ADDRESS
10579
FLEXANALOG NAME
SRC 4 Ib Harm[8]
UNITS
Amps
DESCRIPTION
Source 4 phase B current tenth harmonic
10580 SRC 4 Ib Harm[9] Amps Source 4 phase B current eleventh harmonic
10581 SRC 4 Ib Harm[10] Amps Source 4 phase B current twelfth harmonic
10582 SRC 4 Ib Harm[11] Amps Source 4 phase B current thirteenth harmonic
10583 SRC 4 Ib Harm[12] Amps Source 4 phase B current fourteenth harmonic
10584 SRC 4 Ib Harm[13] Amps Source 4 phase B current fifteenth harmonic
10585 SRC 4 Ib Harm[14] Amps Source 4 phase B current sixteenth harmonic
10586 SRC 4 Ib Harm[15] Amps Source 4 phase B current seventeenth harmonic
10587 SRC 4 Ib Harm[16] Amps Source 4 phase B current eighteenth harmonic
10588 SRC 4 Ib Harm[17] Amps Source 4 phase B current nineteenth harmonic
10589 SRC 4 Ib Harm[18] Amps Source 4 phase B current twentieth harmonic
10590 SRC 4 Ib Harm[19] Amps Source 4 phase B current twenty-first harmonic
10591 SRC 4 Ib Harm[20] Amps Source 4 phase B current twenty-second harmonic
10592 SRC 4 Ib Harm[21] Amps Source 4 phase B current twenty-third harmonic
10593 SRC 4 Ib Harm[22] Amps Source 4 phase B current twenty-fourth harmonic
10594 SRC 4 Ib Harm[23] Amps Source 4 phase B current twenty-fifth harmonic
10603 SRC 4 Ic THD --- Source 4 phase C current total harmonic distortion
10604 SRC 4 Ic Harm[0] Amps Source 4 phase C current second harmonic
10605 SRC 4 Ic Harm[1] Amps Source 4 phase C current third harmonic
10606 SRC 4 Ic Harm[2] Amps Source 4 phase C current fourth harmonic
10607 SRC 4 Ic Harm[3] Amps Source 4 phase C current fifth harmonic
10608 SRC 4 Ic Harm[4] Amps Source 4 phase C current sixth harmonic
10609 SRC 4 Ic Harm[5] Amps Source 4 phase C current seventh harmonic
10610 SRC 4 Ic Harm[6] Amps Source 4 phase C current eighth harmonic
10611 SRC 4 Ic Harm[7] Amps Source 4 phase C current ninth harmonic
10612 SRC 4 Ic Harm[8] Amps Source 4 phase C current tenth harmonic
10613 SRC 4 Ic Harm[9] Amps Source 4 phase C current eleventh harmonic
10614 SRC 4 Ic Harm[10] Amps Source 4 phase C current twelfth harmonic
10615 SRC 4 Ic Harm[11] Amps Source 4 phase C current thirteenth harmonic
10616 SRC 4 Ic Harm[12] Amps Source 4 phase C current fourteenth harmonic
10617 SRC 4 Ic Harm[13] Amps Source 4 phase C current fifteenth harmonic
10618 SRC 4 Ic Harm[14] Amps Source 4 phase C current sixteenth harmonic
10619 SRC 4 Ic Harm[15] Amps Source 4 phase C current seventeenth harmonic
10620 SRC 4 Ic Harm[16] Amps Source 4 phase C current eighteenth harmonic
10621 SRC 4 Ic Harm[17] Amps Source 4 phase C current nineteenth harmonic
10622 SRC 4 Ic Harm[18] Amps Source 4 phase C current twentieth harmonic
10623 SRC 4 Ic Harm[19] Amps Source 4 phase C current twenty-first harmonic
10624 SRC 4 Ic Harm[20] Amps Source 4 phase C current twenty-second harmonic
10625 SRC 4 Ic Harm[21] Amps Source 4 phase C current twenty-third harmonic
10626 SRC 4 Ic Harm[22] Amps Source 4 phase C current twenty-fourth harmonic
10627 SRC 4 Ic Harm[23] Amps Source 4 phase C current twenty-fifth harmonic
13504 DCMA Inputs 1 Value mA dcmA input 1 actual value
13506 DCMA Inputs 2 Value mA dcmA input 2 actual value
13508 DCMA Inputs 3 Value mA dcmA input 3 actual value
13510 DCMA Inputs 4 Value mA dcmA input 4 actual value
13512 DCMA Inputs 5 Value mA dcmA input 5 actual value
13514 DCMA Inputs 6 Value mA dcmA input 6 actual value

A-20 G60 Generator Protection System GE Multilin


APPENDIX A A.1 PARAMETER LISTS

Table A–1: FLEXANALOG DATA ITEMS (Sheet 21 of 23)


ADDRESS FLEXANALOG NAME UNITS DESCRIPTION A
13516 DCMA Inputs 7 Value mA dcmA input 7 actual value
13518 DCMA Inputs 8 Value mA dcmA input 8 actual value
13520 DCMA Inputs 9 Value mA dcmA input 9 actual value
13522 DCMA Inputs 10 Value mA dcmA input 10 actual value
13524 DCMA Inputs 11 Value mA dcmA input 11 actual value
13526 DCMA Inputs 12 Value mA dcmA input 12 actual value
13528 DCMA Inputs 13 Value mA dcmA input 13 actual value
13530 DCMA Inputs 14 Value mA dcmA input 14 actual value
13532 DCMA Inputs 15 Value mA dcmA input 15 actual value
13534 DCMA Inputs 16 Value mA dcmA input 16 actual value
13536 DCMA Inputs 17 Value mA dcmA input 17 actual value
13538 DCMA Inputs 18 Value mA dcmA input 18 actual value
13540 DCMA Inputs 19 Value mA dcmA input 19 actual value
13542 DCMA Inputs 20 Value mA dcmA input 20 actual value
13544 DCMA Inputs 21 Value mA dcmA input 21 actual value
13546 DCMA Inputs 22 Value mA dcmA input 22 actual value
13548 DCMA Inputs 23 Value mA dcmA input 23 actual value
13550 DCMA Inputs 24 Value mA dcmA input 24 actual value
13552 RTD Inputs 1 Value --- RTD input 1 actual value
13553 RTD Inputs 2 Value --- RTD input 2 actual value
13554 RTD Inputs 3 Value --- RTD input 3 actual value
13555 RTD Inputs 4 Value --- RTD input 4 actual value
13556 RTD Inputs 5 Value --- RTD input 5 actual value
13557 RTD Inputs 6 Value --- RTD input 6 actual value
13558 RTD Inputs 7 Value --- RTD input 7 actual value
13559 RTD Inputs 8 Value --- RTD input 8 actual value
13560 RTD Inputs 9 Value --- RTD input 9 actual value
13561 RTD Inputs 10 Value --- RTD input 10 actual value
13562 RTD Inputs 11 Value --- RTD input 11 actual value
13563 RTD Inputs 12 Value --- RTD input 12 actual value
13564 RTD Inputs 13 Value --- RTD input 13 actual value
13565 RTD Inputs 14 Value --- RTD input 14 actual value
13566 RTD Inputs 15 Value --- RTD input 15 actual value
13567 RTD Inputs 16 Value --- RTD input 16 actual value
13568 RTD Inputs 17 Value --- RTD input 17 actual value
13569 RTD Inputs 18 Value --- RTD input 18 actual value
13570 RTD Inputs 19 Value --- RTD input 19 actual value
13571 RTD Inputs 20 Value --- RTD input 20 actual value
13572 RTD Inputs 21 Value --- RTD input 21 actual value
13573 RTD Inputs 22 Value --- RTD input 22 actual value
13574 RTD Inputs 23 Value --- RTD input 23 actual value
13575 RTD Inputs 24 Value --- RTD input 24 actual value
13576 RTD Inputs 25 Value --- RTD input 25 actual value
13577 RTD Inputs 26 Value --- RTD input 26 actual value
13578 RTD Inputs 27 Value --- RTD input 27 actual value
13579 RTD Inputs 28 Value --- RTD input 28 actual value
13580 RTD Inputs 29 Value --- RTD input 29 actual value

GE Multilin G60 Generator Protection System A-21


A.1 PARAMETER LISTS APPENDIX A

Table A–1: FLEXANALOG DATA ITEMS (Sheet 22 of 23)

A ADDRESS
13581
FLEXANALOG NAME
RTD Inputs 30 Value
UNITS
---
DESCRIPTION
RTD input 30 actual value
13582 RTD Inputs 31 Value --- RTD input 31 actual value
13583 RTD Inputs 32 Value --- RTD input 32 actual value
13584 RTD Inputs 33 Value --- RTD input 33 actual value
13585 RTD Inputs 34 Value --- RTD input 34 actual value
13586 RTD Inputs 35 Value --- RTD input 35 actual value
13587 RTD Inputs 36 Value --- RTD input 36 actual value
13588 RTD Inputs 37 Value --- RTD input 37 actual value
13589 RTD Inputs 38 Value --- RTD input 38 actual value
13590 RTD Inputs 39 Value --- RTD input 39 actual value
13591 RTD Inputs 40 Value --- RTD input 40 actual value
13592 RTD Inputs 41 Value --- RTD input 41 actual value
13593 RTD Inputs 42 Value --- RTD input 42 actual value
13594 RTD Inputs 43 Value --- RTD input 43 actual value
13595 RTD Inputs 44 Value --- RTD input 44 actual value
13596 RTD Inputs 45 Value --- RTD input 45 actual value
13597 RTD Inputs 46 Value --- RTD input 46 actual value
13598 RTD Inputs 47 Value --- RTD input 47 actual value
13599 RTD Inputs 48 Value --- RTD input 48 actual value
24459 Active Setting Group --- Current setting group
32768 Tracking Frequency Hz Tracking frequency
34752 RRTD RTD 1 Value °C Remote RTD input 1 actual value
34753 RRTD RTD 2 Value °C Remote RTD input 2 actual value
34754 RRTD RTD 3 Value °C Remote RTD input 3 actual value
34755 RRTD RTD 4 Value °C Remote RTD input 4 actual value
34756 RRTD RTD 5 Value °C Remote RTD input 5 actual value
34757 RRTD RTD 6 Value °C Remote RTD input 6 actual value
34758 RRTD RTD 7 Value °C Remote RTD input 7 actual value
34759 RRTD RTD 8 Value °C Remote RTD input 8 actual value
34760 RRTD RTD 9 Value °C Remote RTD input 9 actual value
34761 RRTD RTD 10 Value °C Remote RTD input 10 actual value
34762 RRTD RTD 11 Value °C Remote RTD input 11 actual value
34763 RRTD RTD 12 Value °C Remote RTD input 12 actual value
39425 FlexElement 1 Value --- FlexElement™ 1 actual value
39427 FlexElement 2 Value --- FlexElement™ 2 actual value
39429 FlexElement 3 Value --- FlexElement™ 3 actual value
39431 FlexElement 4 Value --- FlexElement™ 4 actual value
39433 FlexElement 5 Value --- FlexElement™ 5 actual value
39435 FlexElement 6 Value --- FlexElement™ 6 actual value
39437 FlexElement 7 Value --- FlexElement™ 7 actual value
39439 FlexElement 8 Value --- FlexElement™ 8 actual value
39441 FlexElement 9 Value --- FlexElement™ 9 actual value
39443 FlexElement 10 Value --- FlexElement™ 10 actual value
39445 FlexElement 11 Value --- FlexElement™ 11 actual value
39447 FlexElement 12 Value --- FlexElement™ 12 actual value
39449 FlexElement 13 Value --- FlexElement™ 13 actual value
39451 FlexElement 14 Value --- FlexElement™ 14 actual value

A-22 G60 Generator Protection System GE Multilin


APPENDIX A A.1 PARAMETER LISTS

Table A–1: FLEXANALOG DATA ITEMS (Sheet 23 of 23)


ADDRESS FLEXANALOG NAME UNITS DESCRIPTION A
39453 FlexElement 15 Value --- FlexElement™ 15 actual value
39455 FlexElement 16 Value --- FlexElement™ 16 actual value
43808 Volts Per Hertz 1 V/Hz Volts per hertz 1 actual value
43809 Volts Per Hertz 2 V/Hz Volts per hertz 2 actual value
45584 GOOSE Analog In 1 --- IEC 61850 GOOSE analog input 1
45586 GOOSE Analog In 2 --- IEC 61850 GOOSE analog input 2
45588 GOOSE Analog In 3 --- IEC 61850 GOOSE analog input 3
45590 GOOSE Analog In 4 --- IEC 61850 GOOSE analog input 4
45592 GOOSE Analog In 5 --- IEC 61850 GOOSE analog input 5
45594 GOOSE Analog In 6 --- IEC 61850 GOOSE analog input 6
45596 GOOSE Analog In 7 --- IEC 61850 GOOSE analog input 7
45598 GOOSE Analog In 8 --- IEC 61850 GOOSE analog input 8
45600 GOOSE Analog In 9 --- IEC 61850 GOOSE analog input 9
45602 GOOSE Analog In 10 --- IEC 61850 GOOSE analog input 10
45604 GOOSE Analog In 11 --- IEC 61850 GOOSE analog input 11
45606 GOOSE Analog In 12 --- IEC 61850 GOOSE analog input 12
45608 GOOSE Analog In 13 --- IEC 61850 GOOSE analog input 13
45610 GOOSE Analog In 14 --- IEC 61850 GOOSE analog input 14
45612 GOOSE Analog In 15 --- IEC 61850 GOOSE analog input 15
45614 GOOSE Analog In 16 --- IEC 61850 GOOSE analog input 16
61449 PMU Num Triggers --- Phasor measurement unit recording number of triggers

GE Multilin G60 Generator Protection System A-23


A.1 PARAMETER LISTS APPENDIX A

A.1.2 FLEXINTEGER ITEMS

A
Table A–2: FLEXINTEGER DATA ITEMS
ADDRESS FLEXINTEGER NAME UNITS DESCRIPTION
9736 PMU 1 SOC seconds PMU 1 SOC timestamps
9738 PMU 1 FRACSEC seconds PMU 1 FRACSEC timestamps
9740 PMU 1 STAT --- PMU 1 STAT flags
9968 GOOSE UInt Input 1 --- IEC61850 GOOSE UInteger input 1
9970 GOOSE UInt Input 2 --- IEC61850 GOOSE UInteger input 2
9972 GOOSE UInt Input 3 --- IEC61850 GOOSE UInteger input 3
9974 GOOSE UInt Input 4 --- IEC61850 GOOSE UInteger input 4
9976 GOOSE UInt Input 5 --- IEC61850 GOOSE UInteger input 5
9978 GOOSE UInt Input 6 --- IEC61850 GOOSE UInteger input 6
9980 GOOSE UInt Input 7 --- IEC61850 GOOSE UInteger input 7
9982 GOOSE UInt Input 8 --- IEC61850 GOOSE UInteger input 8
9984 GOOSE UInt Input 9 --- IEC61850 GOOSE UInteger input 9
9986 GOOSE UInt Input 10 --- IEC61850 GOOSE UInteger input 10
9988 GOOSE UInt Input 11 --- IEC61850 GOOSE UInteger input 11
9990 GOOSE UInt Input 12 --- IEC61850 GOOSE UInteger input 12
9992 GOOSE UInt Input 13 --- IEC61850 GOOSE UInteger input 13
9994 GOOSE UInt Input 14 --- IEC61850 GOOSE UInteger input 14
9996 GOOSE UInt Input 15 --- IEC61850 GOOSE UInteger input 15
9998 GOOSE UInt Input 16 --- IEC61850 GOOSE UInteger input 16

A-24 G60 Generator Protection System GE Multilin


APPENDIX B B.1 MODBUS RTU PROTOCOL

APPENDIX B MODBUS COMMUNICATIONSB.1MODBUS RTU PROTOCOL B.1.1 INTRODUCTION

The UR-series relays support a number of communications protocols to allow connection to equipment such as personal
computers, RTUs, SCADA masters, and programmable logic controllers. The Modicon Modbus RTU protocol is the most
basic protocol supported by the UR. Modbus is available via RS232 or RS485 serial links or via ethernet (using the Mod-
bus/TCP specification). The following description is intended primarily for users who wish to develop their own master com-
munication drivers and applies to the serial Modbus RTU protocol. Note that:
• The UR always acts as a slave device, meaning that it never initiates communications; it only listens and responds to B
requests issued by a master computer.
• For Modbus®, a subset of the Remote Terminal Unit (RTU) protocol format is supported that allows extensive monitor-
ing, programming, and control functions using read and write register commands.

B.1.2 PHYSICAL LAYER

The Modbus® RTU protocol is hardware-independent so that the physical layer can be any of a variety of standard hard-
ware configurations including RS232 and RS485. The relay includes a faceplate (front panel) RS232 port and two rear ter-
minal communications ports that may be configured as RS485, fiber optic, 10Base-T, or 10Base-F. Data flow is half-duplex
in all configurations. See chapter 3 for details on communications wiring.
Each data byte is transmitted in an asynchronous format consisting of 1 start bit, 8 data bits, 1 stop bit, and possibly 1 parity
bit. This produces a 10 or 11 bit data frame. This can be important for transmission through modems at high bit rates (11 bit
data frames are not supported by many modems at baud rates greater than 300).
The baud rate and parity are independently programmable for each communications port. Baud rates of 300, 1200, 2400,
4800, 9600, 14400, 19200, 28800, 33600, 38400, 57600, or 115200 bps are available. Even, odd, and no parity are avail-
able. Refer to the Communications section of chapter 5 for further details.
The master device in any system must know the address of the slave device with which it is to communicate. The relay will
not act on a request from a master if the address in the request does not match the relay’s slave address (unless the
address is the broadcast address – see below).
A single setting selects the slave address used for all ports, with the exception that for the faceplate port, the relay will
accept any address when the Modbus® RTU protocol is used.

B.1.3 DATA LINK LAYER

Communications takes place in packets which are groups of asynchronously framed byte data. The master transmits a
packet to the slave and the slave responds with a packet. The end of a packet is marked by dead-time on the communica-
tions line. The following describes general format for both transmit and receive packets. For exact details on packet format-
ting, refer to subsequent sections describing each function code.

Table B–1: MODBUS PACKET FORMAT


DESCRIPTION SIZE
SLAVE ADDRESS 1 byte
FUNCTION CODE 1 byte
DATA N bytes
CRC 2 bytes
DEAD TIME 3.5 bytes transmission time

• SLAVE ADDRESS: This is the address of the slave device that is intended to receive the packet sent by the master
and to perform the desired action. Each slave device on a communications bus must have a unique address to prevent
bus contention. All of the relay’s ports have the same address which is programmable from 1 to 254; see chapter 5 for
details. Only the addressed slave will respond to a packet that starts with its address. Note that the faceplate port is an
exception to this rule; it will act on a message containing any slave address.
A master transmit packet with slave address 0 indicates a broadcast command. All slaves on the communication link
take action based on the packet, but none respond to the master. Broadcast mode is only recognized when associated
with function code 05h. For any other function code, a packet with broadcast mode slave address 0 will be ignored.

GE Multilin G60 Generator Protection System B-1


B.1 MODBUS RTU PROTOCOL APPENDIX B

• FUNCTION CODE: This is one of the supported functions codes of the unit which tells the slave what action to per-
form. See the Supported Function Codes section for complete details. An exception response from the slave is indi-
cated by setting the high order bit of the function code in the response packet. See the Exception Responses section
for further details.
• DATA: This will be a variable number of bytes depending on the function code. This may include actual values, set-
tings, or addresses sent by the master to the slave or by the slave to the master.
• CRC: This is a two byte error checking code. The RTU version of Modbus® includes a 16-bit cyclic redundancy check
B (CRC-16) with every packet which is an industry standard method used for error detection. If a Modbus slave device
receives a packet in which an error is indicated by the CRC, the slave device will not act upon or respond to the packet
thus preventing any erroneous operations. See the CRC-16 Algorithm section for details on calculating the CRC.
• DEAD TIME: A packet is terminated when no data is received for a period of 3.5 byte transmission times (about 15 ms
at 2400 bps, 2 ms at 19200 bps, and 300 µs at 115200 bps). Consequently, the transmitting device must not allow gaps
between bytes longer than this interval. Once the dead time has expired without a new byte transmission, all slaves
start listening for a new packet from the master except for the addressed slave.

B.1.4 CRC-16 ALGORITHM

The CRC-16 algorithm essentially treats the entire data stream (data bits only; start, stop and parity ignored) as one contin-
uous binary number. This number is first shifted left 16 bits and then divided by a characteristic polynomial
(11000000000000101B). The 16-bit remainder of the division is appended to the end of the packet, MSByte first. The
resulting packet including CRC, when divided by the same polynomial at the receiver will give a zero remainder if no trans-
mission errors have occurred. This algorithm requires the characteristic polynomial to be reverse bit ordered. The most sig-
nificant bit of the characteristic polynomial is dropped, since it does not affect the value of the remainder.
A C programming language implementation of the CRC algorithm will be provided upon request.

Table B–2: CRC-16 ALGORITHM


SYMBOLS: --> data transfer
A 16 bit working register
Alow low order byte of A
Ahigh high order byte of A
CRC 16 bit CRC-16 result
i,j loop counters
(+) logical EXCLUSIVE-OR operator
N total number of data bytes
Di i-th data byte (i = 0 to N-1)
G 16 bit characteristic polynomial = 1010000000000001 (binary) with MSbit dropped and bit order reversed
shr (x) right shift operator (th LSbit of x is shifted into a carry flag, a '0' is shifted into the MSbit of x, all other bits
are shifted right one location)

ALGORITHM: 1. FFFF (hex) --> A


2. 0 --> i
3. 0 --> j
4. Di (+) Alow --> Alow
5. j + 1 --> j
6. shr (A)
7. Is there a carry? No: go to 8; Yes: G (+) A --> A and continue.
8. Is j = 8? No: go to 5; Yes: continue
9. i + 1 --> i
10. Is i = N? No: go to 3; Yes: continue
11. A --> CRC

B-2 G60 Generator Protection System GE Multilin


APPENDIX B B.2 MODBUS FUNCTION CODES

B.2MODBUS FUNCTION CODES B.2.1 SUPPORTED FUNCTION CODES

Modbus® officially defines function codes from 1 to 127 though only a small subset is generally needed. The relay supports
some of these functions, as summarized in the following table. Subsequent sections describe each function code in detail.

FUNCTION CODE MODBUS DEFINITION GE MULTILIN DEFINITION


HEX DEC
03 3 Read holding registers Read actual values or settings
B
04 4 Read holding registers Read actual values or settings
05 5 Force single coil Execute operation
06 6 Preset single register Store single setting
10 16 Preset multiple registers Store multiple settings

B.2.2 READ ACTUAL VALUES OR SETTINGS (FUNCTION CODE 03/04H)

This function code allows the master to read one or more consecutive data registers (actual values or settings) from a relay.
Data registers are always 16-bit (two-byte) values transmitted with high order byte first. The maximum number of registers
that can be read in a single packet is 125. See the Modbus memory map table for exact details on the data registers.
Since some PLC implementations of Modbus only support one of function codes 03h and 04h. The G60 interpretation
allows either function code to be used for reading one or more consecutive data registers. The data starting address will
determine the type of data being read. Function codes 03h and 04h are therefore identical.
The following table shows the format of the master and slave packets. The example shows a master device requesting
three register values starting at address 4050h from slave device 11h (17 decimal); the slave device responds with the val-
ues 40, 300, and 0 from registers 4050h, 4051h, and 4052h, respectively.

Table B–3: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE


MASTER TRANSMISSION SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX) PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11 SLAVE ADDRESS 11
FUNCTION CODE 04 FUNCTION CODE 04
DATA STARTING ADDRESS - high 40 BYTE COUNT 06
DATA STARTING ADDRESS - low 50 DATA #1 - high 00
NUMBER OF REGISTERS - high 00 DATA #1 - low 28
NUMBER OF REGISTERS - low 03 DATA #2 - high 01
CRC - low A7 DATA #2 - low 2C
CRC - high 4A DATA #3 - high 00
DATA #3 - low 00
CRC - low 0D
CRC - high 60

GE Multilin G60 Generator Protection System B-3


B.2 MODBUS FUNCTION CODES APPENDIX B

B.2.3 EXECUTE OPERATION (FUNCTION CODE 05H)

This function code allows the master to perform various operations in the relay. Available operations are shown in the Sum-
mary of operation codes table below.
The following table shows the format of the master and slave packets. The example shows a master device requesting the
slave device 11h (17 decimal) to perform a reset. The high and low code value bytes always have the values “FF” and “00”
respectively and are a remnant of the original Modbus definition of this function code.
B
Table B–4: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE
MASTER TRANSMISSION SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX) PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11 SLAVE ADDRESS 11
FUNCTION CODE 05 FUNCTION CODE 05
OPERATION CODE - high 00 OPERATION CODE - high 00
OPERATION CODE - low 01 OPERATION CODE - low 01
CODE VALUE - high FF CODE VALUE - high FF
CODE VALUE - low 00 CODE VALUE - low 00
CRC - low DF CRC - low DF
CRC - high 6A CRC - high 6A

Table B–5: SUMMARY OF OPERATION CODES FOR FUNCTION 05H


OPERATION DEFINITION DESCRIPTION
CODE (HEX)
0000 NO OPERATION Does not do anything.
0001 RESET Performs the same function as the faceplate RESET key.
0005 CLEAR EVENT RECORDS Performs the same function as the faceplate CLEAR EVENT RECORDS menu
command.
0006 CLEAR OSCILLOGRAPHY Clears all oscillography records.
1000 to 103F VIRTUAL IN 1 to 64 ON/OFF Sets the states of Virtual Inputs 1 to 64 either “ON” or “OFF”.

B.2.4 STORE SINGLE SETTING (FUNCTION CODE 06H)

This function code allows the master to modify the contents of a single setting register in an relay. Setting registers are
always 16 bit (two byte) values transmitted high order byte first. The following table shows the format of the master and
slave packets. The example shows a master device storing the value 200 at memory map address 4051h to slave device
11h (17 dec).

Table B–6: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE


MASTER TRANSMISSION SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX) PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11 SLAVE ADDRESS 11
FUNCTION CODE 06 FUNCTION CODE 06
DATA STARTING ADDRESS - high 40 DATA STARTING ADDRESS - high 40
DATA STARTING ADDRESS - low 51 DATA STARTING ADDRESS - low 51
DATA - high 00 DATA - high 00
DATA - low C8 DATA - low C8
CRC - low CE CRC - low CE
CRC - high DD CRC - high DD

B-4 G60 Generator Protection System GE Multilin


APPENDIX B B.2 MODBUS FUNCTION CODES

B.2.5 STORE MULTIPLE SETTINGS (FUNCTION CODE 10H)

This function code allows the master to modify the contents of a one or more consecutive setting registers in a relay. Setting
registers are 16-bit (two byte) values transmitted high order byte first. The maximum number of setting registers that can be
stored in a single packet is 60. The following table shows the format of the master and slave packets. The example shows
a master device storing the value 200 at memory map address 4051h, and the value 1 at memory map address 4052h to
slave device 11h (17 decimal).
B
Table B–7: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE
MASTER TRANSMISSION SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX) PACKET FORMAT EXMAPLE (HEX)
SLAVE ADDRESS 11 SLAVE ADDRESS 11
FUNCTION CODE 10 FUNCTION CODE 10
DATA STARTING ADDRESS - hi 40 DATA STARTING ADDRESS - hi 40
DATA STARTING ADDRESS - lo 51 DATA STARTING ADDRESS - lo 51
NUMBER OF SETTINGS - hi 00 NUMBER OF SETTINGS - hi 00
NUMBER OF SETTINGS - lo 02 NUMBER OF SETTINGS - lo 02
BYTE COUNT 04 CRC - lo 07
DATA #1 - high order byte 00 CRC - hi 64
DATA #1 - low order byte C8
DATA #2 - high order byte 00
DATA #2 - low order byte 01
CRC - low order byte 12
CRC - high order byte 62

B.2.6 EXCEPTION RESPONSES

Programming or operation errors usually happen because of illegal data in a packet. These errors result in an exception
response from the slave. The slave detecting one of these errors sends a response packet to the master with the high order
bit of the function code set to 1.
The following table shows the format of the master and slave packets. The example shows a master device sending the
unsupported function code 39h to slave device 11.

Table B–8: MASTER AND SLAVE DEVICE PACKET TRANSMISSION EXAMPLE


MASTER TRANSMISSION SLAVE RESPONSE
PACKET FORMAT EXAMPLE (HEX) PACKET FORMAT EXAMPLE (HEX)
SLAVE ADDRESS 11 SLAVE ADDRESS 11
FUNCTION CODE 39 FUNCTION CODE B9
CRC - low order byte CD ERROR CODE 01
CRC - high order byte F2 CRC - low order byte 93
CRC - high order byte 95

GE Multilin G60 Generator Protection System B-5


B.3 FILE TRANSFERS APPENDIX B

B.3FILE TRANSFERS B.3.1 OBTAINING RELAY FILES VIA MODBUS

a) DESCRIPTION
The UR relay has a generic file transfer facility, meaning that you use the same method to obtain all of the different types of
files from the unit. The Modbus registers that implement file transfer are found in the "Modbus File Transfer (Read/Write)"
and "Modbus File Transfer (Read Only)" modules, starting at address 3100 in the Modbus Memory Map. To read a file from
the UR relay, use the following steps:
B 1. Write the filename to the "Name of file to read" register using a write multiple registers command. If the name is shorter
than 80 characters, you may write only enough registers to include all the text of the filename. Filenames are not case
sensitive.
2. Repeatedly read all the registers in "Modbus File Transfer (Read Only)" using a read multiple registers command. It is
not necessary to read the entire data block, since the UR relay will remember which was the last register you read. The
"position" register is initially zero and thereafter indicates how many bytes (2 times the number of registers) you have
read so far. The "size of..." register indicates the number of bytes of data remaining to read, to a maximum of 244.
3. Keep reading until the "size of..." register is smaller than the number of bytes you are transferring. This condition indi-
cates end of file. Discard any bytes you have read beyond the indicated block size.
4. If you need to re-try a block, read only the "size of.." and "block of data", without reading the position. The file pointer is
only incremented when you read the position register, so the same data block will be returned as was read in the pre-
vious operation. On the next read, check to see if the position is where you expect it to be, and discard the previous
block if it is not (this condition would indicate that the UR relay did not process your original read request).
The UR relay retains connection-specific file transfer information, so files may be read simultaneously on multiple Modbus
connections.

b) OTHER PROTOCOLS
All the files available via Modbus may also be retrieved using the standard file transfer mechanisms in other protocols (for
example, TFTP or MMS).

c) COMTRADE, OSCILLOGRAPHY, AND DATA LOGGER FILES


Oscillography and data logger files are formatted using the COMTRADE file format per IEEE PC37.111 Draft 7c (02 Sep-
tember 1997). The files may be obtained in either text or binary COMTRADE format.

d) READING OSCILLOGRAPHY FILES


Familiarity with the oscillography feature is required to understand the following description. Refer to the Oscillography sec-
tion in Chapter 5 for additional details.
The Oscillography Number of Triggers register is incremented by one every time a new oscillography file is triggered (cap-
tured) and cleared to zero when oscillography data is cleared. When a new trigger occurs, the associated oscillography file
is assigned a file identifier number equal to the incremented value of this register; the newest file number is equal to the
Oscillography_Number_of_Triggers register. This register can be used to determine if any new data has been captured by
periodically reading it to see if the value has changed; if the number has increased then new data is available.
The Oscillography Number of Records register specifies the maximum number of files (and the number of cycles of data
per file) that can be stored in memory of the relay. The Oscillography Available Records register specifies the actual num-
ber of files that are stored and still available to be read out of the relay.
Writing “Yes” (i.e. the value 1) to the Oscillography Clear Data register clears oscillography data files, clears both the Oscil-
lography Number of Triggers and Oscillography Available Records registers to zero, and sets the Oscillography Last
Cleared Date to the present date and time.
To read binary COMTRADE oscillography files, read the following filenames:
OSCnnnn.CFG and OSCnnn.DAT
Replace “nnn” with the desired oscillography trigger number. For ASCII format, use the following file names
OSCAnnnn.CFG and OSCAnnn.DAT

B-6 G60 Generator Protection System GE Multilin


APPENDIX B B.3 FILE TRANSFERS

e) READING DATA LOGGER FILES


Familiarity with the data logger feature is required to understand this description. Refer to the Data Logger section of Chap-
ter 5 for details. To read the entire data logger in binary COMTRADE format, read the following files.
datalog.cfg and datalog.dat
To read the entire data logger in ASCII COMTRADE format, read the following files.
dataloga.cfg and dataloga.dat
To limit the range of records to be returned in the COMTRADE files, append the following to the filename before writing it:
B
• To read from a specific time to the end of the log: <space> startTime
• To read a specific range of records: <space> startTime <space> endTime
• Replace <startTime> and <endTime> with Julian dates (seconds since Jan. 1 1970) as numeric text.

f) READING EVENT RECORDER FILES


To read the entire event recorder contents in ASCII format (the only available format), use the following filename:
EVT.TXT
To read from a specific record to the end of the log, use the following filename:
EVTnnn.TXT (replace nnn with the desired starting record number)
To read from a specific record to another specific record, use the following filename:
EVT.TXT xxxxx yyyyy (replace xxxxx with the starting record number and yyyyy with the ending record number)

B.3.2 MODBUS PASSWORD OPERATION

The G60 supports password entry from a local or remote connection.


Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the faceplate RS232 connection. Remote access is defined as any access to settings or commands via any rear com-
munications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the G60, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password must be used.
The command password is set up at memory location 4000. Storing a value of “0” removes command password protection.
When reading the password setting, the encrypted value (zero if no password is set) is returned. Command security is
required to change the command password. Similarly, the setting password is set up at memory location 4002. These are
the same settings and encrypted values found in the SETTINGS Ö PRODUCT SETUP Ö PASSWORD SECURITY menu via the
keypad. Enabling password security for the faceplate display will also enable it for Modbus, and vice-versa.
To gain command level security access, the command password must be entered at memory location 4008. To gain setting
level security access, the setting password must be entered at memory location 400A. The entered setting password must
match the current setting password setting, or must be zero, to change settings or download firmware.
Command and setting passwords each have a 30 minute timer. Each timer starts when you enter the particular password,
and is re-started whenever you use it. For example, writing a setting re-starts the setting password timer and writing a com-
mand register or forcing a coil re-starts the command password timer. The value read at memory location 4010 can be used
to confirm whether a command password is enabled or disabled (a value of 0 represents disabled). The value read at mem-
ory location 4011 can be used to confirm whether a setting password is enabled or disabled.
Command or setting password security access is restricted to the particular port or particular TCP/IP connection on which
the entry was made. Passwords must be entered when accessing the relay through other ports or connections, and the
passwords must be re-entered after disconnecting and re-connecting on TCP/IP.

GE Multilin G60 Generator Protection System B-7


B.4 MEMORY MAPPING APPENDIX B

B.4MEMORY MAPPING B.4.1 MODBUS MEMORY MAP

Table B–9: MODBUS MEMORY MAP (Sheet 1 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
Product Information (Read Only)
0000 UR Product Type 0 to 65535 --- 1 F001 0
B 0002 Product Version
Product Information (Read Only -- Written by Factory)
0 to 655.35 --- 0.01 F001 1

0010 Serial Number --- --- --- F203 “0”


0020 Manufacturing Date 0 to 4294967295 --- 1 F050 0
0022 Modification Number 0 to 65535 --- 1 F001 0
0040 Order Code --- --- --- F204 “Order Code x”
0090 Ethernet MAC Address --- --- --- F072 0
0093 Reserved (13 items) --- --- --- F001 0
00A0 CPU Module Serial Number --- --- --- F203 (none)
00B0 CPU Supplier Serial Number --- --- --- F203 (none)
00C0 Ethernet Sub Module Serial Number (8 items) --- --- --- F203 (none)
Self Test Targets (Read Only)
0200 Self Test States (2 items) 0 to 4294967295 0 1 F143 0
Front Panel (Read Only)
0204 LED Column n State, n = 1 to 10 (10 items) 0 to 65535 --- 1 F501 0
0220 Display Message --- --- --- F204 (none)
0248 Last Key Pressed 0 to 47 --- 1 F530 0 (None)
Keypress Emulation (Read/Write)
0280 Simulated keypress -- write zero before each keystroke 0 to 42 --- 1 F190 0 (No key -- use
between real keys)
Virtual Input Commands (Read/Write Command) (64 modules)
0400 Virtual Input 1 State 0 to 1 --- 1 F108 0 (Off)
0401 Virtual Input 2 State 0 to 1 --- 1 F108 0 (Off)
0402 Virtual Input 3 State 0 to 1 --- 1 F108 0 (Off)
0403 Virtual Input 4 State 0 to 1 --- 1 F108 0 (Off)
0404 Virtual Input 5 State 0 to 1 --- 1 F108 0 (Off)
0405 Virtual Input 6 State 0 to 1 --- 1 F108 0 (Off)
0406 Virtual Input 7 State 0 to 1 --- 1 F108 0 (Off)
0407 Virtual Input 8 State 0 to 1 --- 1 F108 0 (Off)
0408 Virtual Input 9 State 0 to 1 --- 1 F108 0 (Off)
0409 Virtual Input 10 State 0 to 1 --- 1 F108 0 (Off)
040A Virtual Input 11 State 0 to 1 --- 1 F108 0 (Off)
040B Virtual Input 12 State 0 to 1 --- 1 F108 0 (Off)
040C Virtual Input 13 State 0 to 1 --- 1 F108 0 (Off)
040D Virtual Input 14 State 0 to 1 --- 1 F108 0 (Off)
040E Virtual Input 15 State 0 to 1 --- 1 F108 0 (Off)
040F Virtual Input 16 State 0 to 1 --- 1 F108 0 (Off)
0410 Virtual Input 17 State 0 to 1 --- 1 F108 0 (Off)
0411 Virtual Input 18 State 0 to 1 --- 1 F108 0 (Off)
0412 Virtual Input 19 State 0 to 1 --- 1 F108 0 (Off)
0413 Virtual Input 20 State 0 to 1 --- 1 F108 0 (Off)
0414 Virtual Input 21 State 0 to 1 --- 1 F108 0 (Off)
0415 Virtual Input 22 State 0 to 1 --- 1 F108 0 (Off)
0416 Virtual Input 23 State 0 to 1 --- 1 F108 0 (Off)
0417 Virtual Input 24 State 0 to 1 --- 1 F108 0 (Off)
0418 Virtual Input 25 State 0 to 1 --- 1 F108 0 (Off)
0419 Virtual Input 26 State 0 to 1 --- 1 F108 0 (Off)
041A Virtual Input 27 State 0 to 1 --- 1 F108 0 (Off)
041B Virtual Input 28 State 0 to 1 --- 1 F108 0 (Off)

B-8 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 2 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
041C Virtual Input 29 State 0 to 1 --- 1 F108 0 (Off)
041D Virtual Input 30 State 0 to 1 --- 1 F108 0 (Off)
041E Virtual Input 31 State 0 to 1 --- 1 F108 0 (Off)
041F Virtual Input 32 State 0 to 1 --- 1 F108 0 (Off)
0420 Virtual Input 33 State 0 to 1 --- 1 F108 0 (Off)
0421 Virtual Input 34 State 0 to 1 --- 1 F108 0 (Off) B
0422 Virtual Input 35 State 0 to 1 --- 1 F108 0 (Off)
0423 Virtual Input 36 State 0 to 1 --- 1 F108 0 (Off)
0424 Virtual Input 37 State 0 to 1 --- 1 F108 0 (Off)
0425 Virtual Input 38 State 0 to 1 --- 1 F108 0 (Off)
0426 Virtual Input 39 State 0 to 1 --- 1 F108 0 (Off)
0427 Virtual Input 40 State 0 to 1 --- 1 F108 0 (Off)
0428 Virtual Input 41 State 0 to 1 --- 1 F108 0 (Off)
0429 Virtual Input 42 State 0 to 1 --- 1 F108 0 (Off)
042A Virtual Input 43 State 0 to 1 --- 1 F108 0 (Off)
042B Virtual Input 44 State 0 to 1 --- 1 F108 0 (Off)
042C Virtual Input 45 State 0 to 1 --- 1 F108 0 (Off)
042D Virtual Input 46 State 0 to 1 --- 1 F108 0 (Off)
042E Virtual Input 47 State 0 to 1 --- 1 F108 0 (Off)
042F Virtual Input 48 State 0 to 1 --- 1 F108 0 (Off)
0430 Virtual Input 49 State 0 to 1 --- 1 F108 0 (Off)
0431 Virtual Input 50 State 0 to 1 --- 1 F108 0 (Off)
0432 Virtual Input 51 State 0 to 1 --- 1 F108 0 (Off)
0433 Virtual Input 52 State 0 to 1 --- 1 F108 0 (Off)
0434 Virtual Input 53 State 0 to 1 --- 1 F108 0 (Off)
0435 Virtual Input 54 State 0 to 1 --- 1 F108 0 (Off)
0436 Virtual Input 55 State 0 to 1 --- 1 F108 0 (Off)
0437 Virtual Input 56 State 0 to 1 --- 1 F108 0 (Off)
0438 Virtual Input 57 State 0 to 1 --- 1 F108 0 (Off)
0439 Virtual Input 58 State 0 to 1 --- 1 F108 0 (Off)
043A Virtual Input 59 State 0 to 1 --- 1 F108 0 (Off)
043B Virtual Input 60 State 0 to 1 --- 1 F108 0 (Off)
043C Virtual Input 61 State 0 to 1 --- 1 F108 0 (Off)
043D Virtual Input 62 State 0 to 1 --- 1 F108 0 (Off)
043E Virtual Input 63 State 0 to 1 --- 1 F108 0 (Off)
043F Virtual Input 64 State 0 to 1 --- 1 F108 0 (Off)
Digital Counter States (Read Only Non-Volatile) (8 modules)
0800 Digital Counter 1 Value -2147483647 to --- 1 F004 0
2147483647
0802 Digital Counter 1 Frozen -2147483647 to --- 1 F004 0
2147483647
0804 Digital Counter 1 Frozen Time Stamp 0 to 4294967295 --- 1 F050 0
0806 Digital Counter 1 Frozen Time Stamp us 0 to 4294967295 --- 1 F003 0
0808 ...Repeated for Digital Counter 2
0810 ...Repeated for Digital Counter 3
0818 ...Repeated for Digital Counter 4
0820 ...Repeated for Digital Counter 5
0828 ...Repeated for Digital Counter 6
0830 ...Repeated for Digital Counter 7
0838 ...Repeated for Digital Counter 8
FlexStates (Read Only)
0900 FlexState Bits (16 items) 0 to 65535 --- 1 F001 0
Element States (Read Only)
1000 Element Operate States (64 items) 0 to 65535 --- 1 F502 0

GE Multilin G60 Generator Protection System B-9


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 3 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
User Displays Actuals (Read Only)
1080 Formatted user-definable displays (16 items) --- --- --- F200 (none)
Modbus User Map Actuals (Read Only)
1200 User Map Values (256 items) 0 to 65535 --- 1 F001 0
Element Targets (Read Only)

B 14C0
14C1
Target Sequence
Number of Targets
0 to 65535
0 to 65535
---
---
1
1
F001
F001
0
0
Element Targets (Read/Write)
14C2 Target to Read 0 to 65535 --- 1 F001 0
Element Targets (Read Only)
14C3 Target Message --- --- --- F200 “.”
Digital Input/Output States (Read Only)
1500 Contact Input States (6 items) 0 to 65535 --- 1 F500 0
1508 Virtual Input States (8 items) 0 to 65535 --- 1 F500 0
1510 Contact Output States (4 items) 0 to 65535 --- 1 F500 0
1518 Contact Output Current States (4 items) 0 to 65535 --- 1 F500 0
1520 Contact Output Voltage States (4 items) 0 to 65535 --- 1 F500 0
1528 Virtual Output States (6 items) 0 to 65535 --- 1 F500 0
1530 Contact Output Detectors (4 items) 0 to 65535 --- 1 F500 0
Remote Input/Output States (Read Only)
1540 Remote Device States 0 to 65535 --- 1 F500 0
1542 Remote Input States (4 items) 0 to 65535 --- 1 F500 0
1550 Remote Devices Online 0 to 1 --- 1 F126 0 (No)
1551 Remote Double-Point Status Input 1 State 0 to 3 --- 1 F605 3 (Bad)
1552 Remote Double-Point Status Input 2 State 0 to 3 --- 1 F605 3 (Bad)
1553 Remote Double-Point Status Input 3 State 0 to 3 --- 1 F605 3 (Bad)
1554 Remote Double-Point Status Input 4 State 0 to 3 --- 1 F605 3 (Bad)
1555 Remote Double-Point Status Input 5 State 0 to 3 --- 1 F605 3 (Bad)
Platform Direct Input/Output States (Read Only)
15C0 Direct input states (6 items) 0 to 65535 --- 1 F500 0
15C8 Direct outputs average message return time 1 0 to 65535 ms 1 F001 0
15C9 Direct outputs average message return time 2 0 to 65535 ms 1 F001 0
15CA Direct inputs/outputs unreturned message count - Ch. 1 0 to 65535 --- 1 F001 0
15CB Direct inputs/outputs unreturned message count - Ch. 2 0 to 65535 --- 1 F001 0
15D0 Direct device states 0 to 65535 --- 1 F500 0
15D1 Reserved 0 to 65535 --- 1 F001 0
15D2 Direct inputs/outputs CRC fail count 1 0 to 65535 --- 1 F001 0
15D3 Direct inputs/outputs CRC fail count 2 0 to 65535 --- 1 F001 0
Ethernet Fibre Channel Status (Read/Write)
1610 Ethernet primary fibre channel status 0 to 2 --- 1 F134 0 (Fail)
1611 Ethernet secondary fibre channel status 0 to 2 --- 1 F134 0 (Fail)
Data Logger Actuals (Read Only)
1618 Data logger channel count 0 to 16 channel 1 F001 0
1619 Time of oldest available samples 0 to 4294967295 seconds 1 F050 0
161B Time of newest available samples 0 to 4294967295 seconds 1 F050 0
161D Data logger duration 0 to 999.9 days 0.1 F001 0
Stator Differential Actuals (Read Only)
1660 Generator Differential Iad 0 to 999999.999 A 0.001 F060 0
1662 Generator Restraint Iar 0 to 999999.999 A 0.001 F060 0
1664 Generator Differential Ibd 0 to 999999.999 A 0.001 F060 0
1666 Generator Restraint Ibr 0 to 999999.999 A 0.001 F060 0
1668 Generator Differential Icd 0 to 999999.999 A 0.001 F060 0
166A Generator Restraint Icr 0 to 999999.999 A 0.001 F060 0
166C Stator Differential CT Primary 0 to 50000 --- 1 F060 1

B-10 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 4 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
Stator Ground Actuals (Read Only)
1670 Stator Ground Vn 3rd 0 to 999999.999 V 0.001 F060 0
1672 Stator Ground Vn V0 3rd 0 to 999999.999 V 0.001 F060 0
1674 Stator Ground V0 3rd 0 to 999999.999 V 0.001 F060 0
Sensitive Directional Power Actuals (Read Only) (2 modules)
1680 Sensitive Directional Power 1 Power -2147483647 to 2147483647 W 1 F060 0 B
1682 Sensitive Directional Power 2 Power -2147483647 to 2147483647 W 1 F060 0
Restricted Ground Fault Currents (Read Only) (6 modules)
16A0 Differential Ground Current Magnitude 0 to 999999.999 A 0.001 F060 0
16A2 Restricted Ground Current Magnitude 0 to 999999.999 A 0.001 F060 0
16A4 ...Repeated for Restricted Ground Fault 2
16A8 ...Repeated for Restricted Ground Fault 3
16AC ...Repeated for Restricted Ground Fault 4
16B0 ...Repeated for Restricted Ground Fault 5
16B4 ...Repeated for Restricted Ground Fault 6
Frequency Rate of Change Actuals (Read Only) (4 modules)
16E0 Frequency Rate of Change 1 -327.67 to 327.67 Hz/s 0.01 F002 0
16E1 Reserved (3 items) 0 to 65535 --- 1 F001 0
16E4 ...Repeated for Frequency Rate of Change 2
16E8 ...Repeated for Frequency Rate of Change 3
16EC ...Repeated for Frequency Rate of Change 4
Source Current (Read Only) (6 modules)
1800 Source 1 Phase A Current RMS 0 to 999999.999 A 0.001 F060 0
1802 Source 1 Phase B Current RMS 0 to 999999.999 A 0.001 F060 0
1804 Source 1 Phase C Current RMS 0 to 999999.999 A 0.001 F060 0
1806 Source 1 Neutral Current RMS 0 to 999999.999 A 0.001 F060 0
1808 Source 1 Phase A Current Magnitude 0 to 999999.999 A 0.001 F060 0
180A Source 1 Phase A Current Angle -359.9 to 0 degrees 0.1 F002 0
180B Source 1 Phase B Current Magnitude 0 to 999999.999 A 0.001 F060 0
180D Source 1 Phase B Current Angle -359.9 to 0 degrees 0.1 F002 0
180E Source 1 Phase C Current Magnitude 0 to 999999.999 A 0.001 F060 0
1810 Source 1 Phase C Current Angle -359.9 to 0 degrees 0.1 F002 0
1811 Source 1 Neutral Current Magnitude 0 to 999999.999 A 0.001 F060 0
1813 Source 1 Neutral Current Angle -359.9 to 0 degrees 0.1 F002 0
1814 Source 1 Ground Current RMS 0 to 999999.999 A 0.001 F060 0
1816 Source 1 Ground Current Magnitude 0 to 999999.999 A 0.001 F060 0
1818 Source 1 Ground Current Angle -359.9 to 0 degrees 0.1 F002 0
1819 Source 1 Zero Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
181B Source 1 Zero Sequence Current Angle -359.9 to 0 degrees 0.1 F002 0
181C Source 1 Positive Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
181E Source 1 Positive Sequence Current Angle -359.9 to 0 degrees 0.1 F002 0
181F Source 1 Negative Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
1821 Source 1 Negative Sequence Current Angle -359.9 to 0 degrees 0.1 F002 0
1822 Source 1 Differential Ground Current Magnitude 0 to 999999.999 A 0.001 F060 0
1824 Source 1 Differential Ground Current Angle -359.9 to 0 degrees 0.1 F002 0
1825 Reserved (27 items) --- --- --- F001 0
1840 ...Repeated for Source 2
1880 ...Repeated for Source 3
18C0 ...Repeated for Source 4
1900 ...Repeated for Source 5
1940 ...Repeated for Source 6
Source Voltage (Read Only) (6 modules)
1A00 Source 1 Phase AG Voltage RMS V F060 0
1A02 Source 1 Phase BG Voltage RMS V F060 0

GE Multilin G60 Generator Protection System B-11


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 5 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
1A04 Source 1 Phase CG Voltage RMS V F060 0
1A06 Source 1 Phase AG Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A08 Source 1 Phase AG Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A09 Source 1 Phase BG Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A0B Source 1 Phase BG Voltage Angle -359.9 to 0 degrees 0.1 F002 0

B 1A0C
1A0E
Source 1 Phase CG Voltage Magnitude
Source 1 Phase CG Voltage Angle
0 to 999999.999
-359.9 to 0
V
degrees
0.001
0.1
F060
F002
0
0
1A0F Source 1 Phase AB or AC Voltage RMS 0 to 999999.999 V 0.001 F060 0
1A11 Source 1 Phase BC or BA Voltage RMS 0 to 999999.999 V 0.001 F060 0
1A13 Source 1 Phase CA or CB Voltage RMS 0 to 999999.999 V 0.001 F060 0
1A15 Source 1 Phase AB or AC Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A17 Source 1 Phase AB or AC Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A18 Source 1 Phase BC or BA Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A1A Source 1 Phase BC or BA Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A1B Source 1 Phase CA or CB Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A1D Source 1 Phase CA or CB Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A1E Source 1 Auxiliary Voltage RMS V F060 0
1A20 Source 1 Auxiliary Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A22 Source 1 Auxiliary Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A23 Source 1 Zero Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A25 Source 1 Zero Sequence Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A26 Source 1 Positive Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A28 Source 1 Positive Sequence Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A29 Source 1 Negative Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
1A2B Source 1 Negative Sequence Voltage Angle -359.9 to 0 degrees 0.1 F002 0
1A2C Reserved (20 items) --- --- --- F001 0
1A40 ...Repeated for Source 2
1A80 ...Repeated for Source 3
1AC0 ...Repeated for Source 4
1B00 ...Repeated for Source 5
1B40 ...Repeated for Source 6
Source Power (Read Only) (6 modules)
1C00 Source 1 Three Phase Real Power -1000000000000 to W 0.001 F060 0
1000000000000
1C02 Source 1 Phase A Real Power -1000000000000 to W 0.001 F060 0
1000000000000
1C04 Source 1 Phase B Real Power -1000000000000 to W 0.001 F060 0
1000000000000
1C06 Source 1 Phase C Real Power -1000000000000 to W 0.001 F060 0
1000000000000
1C08 Source 1 Three Phase Reactive Power -1000000000000 to var 0.001 F060 0
1000000000000
1C0A Source 1 Phase A Reactive Power -1000000000000 to var 0.001 F060 0
1000000000000
1C0C Source 1 Phase B Reactive Power -1000000000000 to var 0.001 F060 0
1000000000000
1C0E Source 1 Phase C Reactive Power -1000000000000 to var 0.001 F060 0
1000000000000
1C10 Source 1 Three Phase Apparent Power -1000000000000 to VA 0.001 F060 0
1000000000000
1C12 Source 1 Phase A Apparent Power -1000000000000 to VA 0.001 F060 0
1000000000000
1C14 Source 1 Phase B Apparent Power -1000000000000 to VA 0.001 F060 0
1000000000000
1C16 Source 1 Phase C Apparent Power -1000000000000 to VA 0.001 F060 0
1000000000000
1C18 Source 1 Three Phase Power Factor -0.999 to 1 --- 0.001 F013 0
1C19 Source 1 Phase A Power Factor -0.999 to 1 --- 0.001 F013 0

B-12 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 6 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
1C1A Source 1 Phase B Power Factor -0.999 to 1 --- 0.001 F013 0
1C1B Source 1 Phase C Power Factor -0.999 to 1 --- 0.001 F013 0
1C1C Reserved (4 items) --- --- --- F001 0
1C20 ...Repeated for Source 2
1C40 ...Repeated for Source 3
1C60 ...Repeated for Source 4 B
1C80 ...Repeated for Source 5
1CA0 ...Repeated for Source 6
Source Energy (Read Only Non-Volatile) (6 modules)
1D00 Source 1 Positive Watthour 0 to 1000000000000 Wh 0.001 F060 0
1D02 Source 1 Negative Watthour 0 to 1000000000000 Wh 0.001 F060 0
1D04 Source 1 Positive Varhour 0 to 1000000000000 varh 0.001 F060 0
1D06 Source 1 Negative Varhour 0 to 1000000000000 varh 0.001 F060 0
1D08 Reserved (8 items) --- --- --- F001 0
1D10 ...Repeated for Source 2
1D20 ...Repeated for Source 3
1D30 ...Repeated for Source 4
1D40 ...Repeated for Source 5
1D50 ...Repeated for Source 6
Energy Commands (Read/Write Command)
1D60 Energy Clear Command 0 to 1 --- 1 F126 0 (No)
Source Frequency (Read Only) (6 modules)
1D80 Frequency for Source 1 --- Hz --- F003 0
1D82 Frequency for Source 2 --- Hz --- F003 0
1D84 Frequency for Source 3 --- Hz --- F003 0
1D86 Frequency for Source 4 --- Hz --- F003 0
1D88 Frequency for Source 5 --- Hz --- F003 0
1D8A Frequency for Source 6 --- Hz --- F003 0
1F80 Source 1 Va THD 0 to 99.9 --- 0.1 F001 0
1F81 Source 1 Va Harmonics - 2nd to 25th (24 items) 0 to 99.9 --- 0.1 F001 0
1F99 Source 1 Vb THD 0 to 99.9 --- 0.1 F001 0
1F9A Source 1 Vb Harmonics - 2nd to 25th (24 items) 0 to 99.9 --- 0.1 F001 0
1FB2 Source 1 Vc THD 0 to 99.9 --- 0.1 F001 0
1FB3 Source 1 Vc Harmonics - 2nd to 25th (24 items) 0 to 99.9 --- 0.1 F001 0
1FCB ...Repeated for Source 2
2016 ...Repeated for Source 3
2061 ...Repeated for Source 4
Passwords Unauthorized Access (Read/Write Command)
2230 Reset Unauthorized Access 0 to 1 --- 1 F126 0 (No)
Synchrocheck Actuals (Read Only) (2 modules)
2400 Synchrocheck 1 Delta Voltage -1000000000000 to V 1 F060 0
1000000000000
2402 Synchrocheck 1 Delta Frequency 0 to 655.35 Hz 0.01 F001 0
2403 Synchrocheck 1 Delta Phase 0 to 179.9 degrees 0.1 F001 0
2404 ...Repeated for Synchrocheck 2
Phasor Measurement Unit actual values (Read Only) (4 modules)
2540 PMU 1 Phase A Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2542 PMU Unit 1 Phase A Voltage Angle -359.9 to 0 ° 0.1 F002 0
2543 PMU 1 Phase B Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2545 PMU 1 Phase B Voltage Angle -359.9 to 0 ° 0.1 F002 0
2546 PMU 1 Phase C Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2548 PMU 1 Phase C Voltage Angle -359.9 to 0 ° 0.1 F002 0
2549 PMU 1 Auxiliary Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
254B PMU 1 Auxiliary Voltage Angle -359.9 to 0 ° 0.1 F002 0

GE Multilin G60 Generator Protection System B-13


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 7 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
254C PMU 1 Positive Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
254E PMU 1 Positive Sequence Voltage Angle -359.9 to 0 ° 0.1 F002 0
254F PMU 1 Negative Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0
2551 PMU 1 Negative Sequence Voltage Angle -359.9 to 0 ° 0.1 F002 0
2552 PMU 1 Zero Sequence Voltage Magnitude 0 to 999999.999 V 0.001 F060 0

B 2554
2555
PMU 1 Zero Sequence Voltage Angle
PMU 1 Phase A Current Magnitude
-359.9 to 0
0 to 999999.999 A
° 0.1
0.001
F002
F060
0
0
2557 PMU 1 Phase A Current Angle -359.9 to 0 ° 0.1 F002 0
2558 PMU 1 Phase B Current Magnitude 0 to 999999.999 A 0.001 F060 0
255A PMU 1 Phase B Current Angle -359.9 to 0 ° 0.1 F002 0
255B PMU 1 Phase C Current Magnitude 0 to 999999.999 A 0.001 F060 0
255D PMU 1 Phase C Current Angle -359.9 to 0 ° 0.1 F002 0
255E PMU 1 Ground Current Magnitude 0 to 999999.999 A 0.001 F060 0
2560 PMU 1 Ground Current Angle -359.9 to 0 ° 0.1 F002 0
2561 PMU 1 Positive Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
2563 PMU 1 Positive Sequence Current Angle -359.9 to 0 ° 0.1 F002 0
2564 PMU 1 Negative Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
2566 PMU 1 Negative Sequence Current Angle -359.9 to 0 ° 0.1 F002 0
2567 PMU 1 Zero Sequence Current Magnitude 0 to 999999.999 A 0.001 F060 0
2569 PMU 1 Zero Sequence Current Angle -359.9 to 0 ° 0.1 F002 0
256A PMU 1 Frequency 2 to 90 Hz 0.001 F003 0
256C PMU 1 df/dt -327.67 to 327.67 Hz/s 0.01 F002 0
256D PMU 1 Configuration Change Counter 0 to 655.35 0.01 F001 0
256E Reserved (4 items) 0 to 1 --- 1 F001 0
Phasor measurement unit integer values (read only actual value registers)
2608 PMU 1 SOC timestamp 0 to 4294967295 seconds 1 F003 0
260A PMU 1 FRAMESEC timestamp 0 to 4294967295 seconds 1 F003 0
260C PMU 1 STAT flags 0 to 4294967295 --- 1 F003 0
Remote double-point status inputs (read/write setting registers)
2620 Remote double-point status input 1 device 1 to 32 --- 1 F001 1
2621 Remote double-point status input 1 item 0 to 128 --- 1 F156 0 (None)
2622 Remote double-point status input 1 name 1 to 64 --- 1 F205 "Rem Ip 1"
2628 Remote double-point status input 1 events 0 to 1 --- 1 F102 0 (Disabled)
2629 ... Repeated for double-point status input 2
2632 ... Repeated for double-point status input 3
263B ... Repeated for double-point status input 4
2644 ... Repeated for double-point status input 5
IEC 61850 GGIO5 configuration (read/write setting registers)
26B0 IEC 61850 GGIO5 uinteger input 1 operand --- --- --- F612 0
26B1 IEC 61850 GGIO5 uinteger input 2 operand --- --- --- F612 0
26B2 IEC 61850 GGIO5 uinteger input 3 operand --- --- --- F612 0
26B3 IEC 61850 GGIO5 uinteger input 4 operand --- --- --- F612 0
26B4 IEC 61850 GGIO5 uinteger input 5 operand --- --- --- F612 0
26B5 IEC 61850 GGIO5 uinteger input 6 operand --- --- --- F612 0
26B6 IEC 61850 GGIO5 uinteger input 7 operand --- --- --- F612 0
26B7 IEC 61850 GGIO5 uinteger input 8 operand --- --- --- F612 0
26B8 IEC 61850 GGIO5 uinteger input 9 operand --- --- --- F612 0
26B9 IEC 61850 GGIO5 uinteger input 10 operand --- --- --- F612 0
26BA IEC 61850 GGIO5 uinteger input 11 operand --- --- --- F612 0
26BB IEC 61850 GGIO5 uinteger input 12 operand --- --- --- F612 0
26BC IEC 61850 GGIO5 uinteger input 13 operand --- --- --- F612 0
26BD IEC 61850 GGIO5 uinteger input 14 operand --- --- --- F612 0
26BE IEC 61850 GGIO5 uinteger input 15 operand --- --- --- F612 0
26BF IEC 61850 GGIO5 uinteger input 16 operand --- --- --- F612 0

B-14 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 8 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
IEC 61850 received integers (read only actual values)
26F0 IEC 61850 received uinteger 1 0 to 4294967295 --- 1 F003 0
26F2 IEC 61850 received uinteger 2 0 to 4294967295 --- 1 F003 0
26F4 IEC 61850 received uinteger 3 0 to 4294967295 --- 1 F003 0
26F6 IEC 61850 received uinteger 4 0 to 4294967295 --- 1 F003 0
26F8 IEC 61850 received uinteger 5 0 to 4294967295 --- 1 F003 0 B
26FA IEC 61850 received uinteger 6 0 to 4294967295 --- 1 F003 0
26FC IEC 61850 received uinteger 7 0 to 4294967295 --- 1 F003 0
26FE IEC 61850 received uinteger 8 0 to 4294967295 --- 1 F003 0
2700 IEC 61850 received uinteger 9 0 to 4294967295 --- 1 F003 0
2702 IEC 61850 received uinteger 10 0 to 4294967295 --- 1 F003 0
2704 IEC 61850 received uinteger 11 0 to 4294967295 --- 1 F003 0
2706 IEC 61850 received uinteger 12 0 to 4294967295 --- 1 F003 0
2708 IEC 61850 received uinteger 13 0 to 4294967295 --- 1 F003 0
270A IEC 61850 received uinteger 14 0 to 4294967295 --- 1 F003 0
270C IEC 61850 received uinteger 15 0 to 4294967295 --- 1 F003 0
270E IEC 61850 received uinteger 16 0 to 4294967295 --- 1 F003 0
Source Current THD And Harmonics (Read Only) (6 modules)
2800 Ia THD for Source 1 0 to 99.9 --- 0.1 F001 0
2801 Ia Harmonics for Source 1 - 2nd to 25th (24 items) 0 to 99.9 --- 0.1 F001 0
2821 Ib THD for Source 1 0 to 99.9 --- 0.1 F001 0
2822 Ib Harmonics for Source 1 - 2nd to 25th (24 items) 0 to 99.9 --- 0.1 F001 0
283A Reserved (8 items) 0 to 0.1 --- 0.1 F001 0
2842 Ic THD for Source 1 0 to 99.9 --- 0.1 F001 0
2843 Ic Harmonics for Source 1 - 2nd to 25th (24 items) 0 to 99.9 --- 0.1 F001 0
285B Reserved (8 items) 0 to 0.1 --- 0.1 F001 0
2863 ...Repeated for Source 2
28C6 ...Repeated for Source 3
2929 ...Repeated for Source 4
Expanded FlexStates (Read Only)
2B00 FlexStates, one per register (256 items) 0 to 1 --- 1 F108 0 (Off)
Expanded Digital Input/Output states (Read Only)
2D00 Contact Input States, one per register (96 items) 0 to 1 --- 1 F108 0 (Off)
2D80 Contact Output States, one per register (64 items) 0 to 1 --- 1 F108 0 (Off)
2E00 Virtual Output States, one per register (96 items) 0 to 1 --- 1 F108 0 (Off)
Expanded Remote Input/Output Status (Read Only)
2F00 Remote Device States, one per register (16 items) 0 to 1 --- 1 F155 0 (Offline)
2F80 Remote Input States, one per register (64 items) 0 to 1 --- 1 F108 0 (Off)
Oscillography Values (Read Only)
3000 Oscillography Number of Triggers 0 to 65535 --- 1 F001 0
3001 Oscillography Available Records 0 to 65535 --- 1 F001 0
3002 Oscillography Last Cleared Date 0 to 400000000 --- 1 F050 0
3004 Oscillography Number Of Cycles Per Record 0 to 65535 --- 1 F001 0
Oscillography Commands (Read/Write Command)
3005 Oscillography Force Trigger 0 to 1 --- 1 F126 0 (No)
3011 Oscillography Clear Data 0 to 1 --- 1 F126 0 (No)
3012 Oscillography Number of Triggers 0 to 32767 --- 1 F001 0
User Programmable Fault Report Commands (Read/Write Command)
3060 User Fault Report Clear 0 to 1 --- 1 F126 0 (No)
User Programmable Fault Report Actuals (Read Only)
3070 Newest Record Number 0 to 65535 --- 1 F001 0
3071 Cleared Date 0 to 4294967295 --- 1 F050 0
3073 Report Date (10 items) 0 to 4294967295 --- 1 F050 0

GE Multilin G60 Generator Protection System B-15


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 9 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
User Programmable Fault Report (Read/Write Setting) (2 modules)
3090 Fault Report 1 Fault Trigger 0 to 65535 --- 1 F300 0
3091 Fault Report 1 Function 0 to 1 --- 1 F102 0 (Disabled)
3092 Fault Report 1 Prefault Trigger 0 to 65535 --- 1 F300 0
3093 Fault Report Analog Channel 1 (32 items) 0 to 65536 --- 1 F600 0

B 30B3
30B8
Fault Report 1 Reserved (5 items)
...Repeated for Fault Report 2
--- --- --- F001 0

Modbus file transfer (read/write)


3100 Name of file to read --- --- --- F204 (none)
Modbus file transfer values (read only)
3200 Character position of current block within file 0 to 4294967295 --- 1 F003 0
3202 Size of currently-available data block 0 to 65535 --- 1 F001 0
3203 Block of data from requested file (122 items) 0 to 65535 --- 1 F001 0
Event recorder actual values (read only)
3400 Events Since Last Clear 0 to 4294967295 --- 1 F003 0
3402 Number of Available Events 0 to 4294967295 --- 1 F003 0
3404 Event Recorder Last Cleared Date 0 to 4294967295 --- 1 F050 0
Event recorder commands (read/write)
3406 Event Recorder Clear Command 0 to 1 --- 1 F126 0 (No)
DCMA Input Values (Read Only) (24 modules)
34C0 DCMA Inputs 1 Value -9999999 to 9999999 --- 1 F004 0
34C2 DCMA Inputs 2 Value -9999999 to 9999999 --- 1 F004 0
34C4 DCMA Inputs 3 Value -9999999 to 9999999 --- 1 F004 0
34C6 DCMA Inputs 4 Value -9999999 to 9999999 --- 1 F004 0
34C8 DCMA Inputs 5 Value -9999999 to 9999999 --- 1 F004 0
34CA DCMA Inputs 6 Value -9999999 to 9999999 --- 1 F004 0
34CC DCMA Inputs 7 Value -9999999 to 9999999 --- 1 F004 0
34CE DCMA Inputs 8 Value -9999999 to 9999999 --- 1 F004 0
34D0 DCMA Inputs 9 Value -9999999 to 9999999 --- 1 F004 0
34D2 DCMA Inputs 10 Value -9999999 to 9999999 --- 1 F004 0
34D4 DCMA Inputs 11 Value -9999999 to 9999999 --- 1 F004 0
34D6 DCMA Inputs 12 Value -9999999 to 9999999 --- 1 F004 0
34D8 DCMA Inputs 13 Value -9999999 to 9999999 --- 1 F004 0
34DA DCMA Inputs 14 Value -9999999 to 9999999 --- 1 F004 0
34DC DCMA Inputs 15 Value -9999999 to 9999999 --- 1 F004 0
34DE DCMA Inputs 16 Value -9999999 to 9999999 --- 1 F004 0
34E0 DCMA Inputs 17 Value -9999999 to 9999999 --- 1 F004 0
34E2 DCMA Inputs 18 Value -9999999 to 9999999 --- 1 F004 0
34E4 DCMA Inputs 19 Value -9999999 to 9999999 --- 1 F004 0
34E6 DCMA Inputs 20 Value -9999999 to 9999999 --- 1 F004 0
34E8 DCMA Inputs 21 Value -9999999 to 9999999 --- 1 F004 0
34EA DCMA Inputs 22 Value -9999999 to 9999999 --- 1 F004 0
34EC DCMA Inputs 23 Value -9999999 to 9999999 --- 1 F004 0
34EE DCMA Inputs 24 Value -9999999 to 9999999 --- 1 F004 0
RTD Input Values (Read Only) (48 modules)
34F0 RTD Input 1 Value -32768 to 32767 °C 1 F002 0
34F1 RTD Input 2 Value -32768 to 32767 °C 1 F002 0
34F2 RTD Input 3 Value -32768 to 32767 °C 1 F002 0
34F3 RTD Input 4 Value -32768 to 32767 °C 1 F002 0
34F4 RTD Input 5 Value -32768 to 32767 °C 1 F002 0
34F5 RTD Input 6 Value -32768 to 32767 °C 1 F002 0
34F6 RTD Input 7 Value -32768 to 32767 °C 1 F002 0
34F7 RTD Input 8 Value -32768 to 32767 °C 1 F002 0
34F8 RTD Input 9 Value -32768 to 32767 °C 1 F002 0

B-16 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 10 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
34F9 RTD Input 10 Value -32768 to 32767 °C 1 F002 0
34FA RTD Input 11 Value -32768 to 32767 °C 1 F002 0
34FB RTD Input 12 Value -32768 to 32767 °C 1 F002 0
34FC RTD Input 13 Value -32768 to 32767 °C 1 F002 0
34FD RTD Input 14 Value -32768 to 32767 °C 1 F002 0
34FE RTD Input 15 Value -32768 to 32767 °C 1 F002 0 B
34FF RTD Input 16 Value -32768 to 32767 °C 1 F002 0
3500 RTD Input 17 Value -32768 to 32767 °C 1 F002 0
3501 RTD Input 18 Value -32768 to 32767 °C 1 F002 0
3502 RTD Input 19 Value -32768 to 32767 °C 1 F002 0
3503 RTD Input 20 Value -32768 to 32767 °C 1 F002 0
3504 RTD Input 21 Value -32768 to 32767 °C 1 F002 0
3505 RTD Input 22 Value -32768 to 32767 °C 1 F002 0
3506 RTD Input 23 Value -32768 to 32767 °C 1 F002 0
3507 RTD Input 24 Value -32768 to 32767 °C 1 F002 0
3508 RTD Input 25 Value -32768 to 32767 °C 1 F002 0
3509 RTD Input 26 Value -32768 to 32767 °C 1 F002 0
350A RTD Input 27 Value -32768 to 32767 °C 1 F002 0
350B RTD Input 28 Value -32768 to 32767 °C 1 F002 0
350C RTD Input 29 Value -32768 to 32767 °C 1 F002 0
350D RTD Input 30 Value -32768 to 32767 °C 1 F002 0
350E RTD Input 31 Value -32768 to 32767 °C 1 F002 0
350F RTD Input 32 Value -32768 to 32767 °C 1 F002 0
3510 RTD Input 33 Value -32768 to 32767 °C 1 F002 0
3511 RTD Input 34 Value -32768 to 32767 °C 1 F002 0
3512 RTD Input 35 Value -32768 to 32767 °C 1 F002 0
3513 RTD Input 36 Value -32768 to 32767 °C 1 F002 0
3514 RTD Input 37 Value -32768 to 32767 °C 1 F002 0
3515 RTD Input 38 Value -32768 to 32767 °C 1 F002 0
3516 RTD Input 39 Value -32768 to 32767 °C 1 F002 0
3517 RTD Input 40 Value -32768 to 32767 °C 1 F002 0
3518 RTD Input 41 Value -32768 to 32767 °C 1 F002 0
3519 RTD Input 42 Value -32768 to 32767 °C 1 F002 0
351A RTD Input 43 Value -32768 to 32767 °C 1 F002 0
351B RTD Input 44 Value -32768 to 32767 °C 1 F002 0
351C RTD Input 45 Value -32768 to 32767 °C 1 F002 0
351D RTD Input 46 Value -32768 to 32767 °C 1 F002 0
351E RTD Input 47 Value -32768 to 32767 °C 1 F002 0
351F RTD Input 48 Value -32768 to 32767 °C 1 F002 0
Expanded Direct Input/Output Status (Read Only)
3560 Direct Device States, one per register (8 items) 0 to 1 --- 1 F155 0 (Offline)
3570 Direct Input States, one per register (96 items) 0 to 1 --- 1 F108 0 (Off)
Frequency out-of-band accumulation actual values (read only)
37A0 Frequency OOB Accumulator Band 1 Accumulation 0.0 to 999.9 % 0.1 F001 0
37A1 Frequency OOB Accumulator Band 2 Accumulation 0.0 to 999.9 % 0.1 F001 0
37A2 Frequency OOB Accumulator Band 3 Accumulation 0.0 to 999.9 % 0.1 F001 0
37A3 Frequency OOB Accumulator Band 4 Accumulation 0.0 to 999.9 % 0.1 F001 0
37A4 Frequency OOB Accumulator Band 5 Accumulation 0.0 to 999.9 % 0.1 F001 0
37A5 Frequency OOB Accumulator Band 6 Accumulation 0.0 to 999.9 % 0.1 F001 0
37A6 Frequency OOB Accumulator Band 7 Accumulation 0.0 to 999.9 % 0.1 F001 0
Frequency out-of-band accumulation commands (read/write)
37A7 Reset Frequency Out-Of-Band Accumulators 0 to 1 --- 1 F126 0 (No)
37A8 Preset Frequency Out-Of-Band Accumulators 0 to 1 --- 1 F126 0 (No)

GE Multilin G60 Generator Protection System B-17


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 11 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
Passwords (Read/Write Command)
4000 Command Password Setting 0 to 4294967295 --- 1 F003 0
Passwords (Read/Write Setting)
4002 Setting Password Setting 0 to 4294967295 --- 1 F003 0
Passwords (Read/Write)

B 4008
400A
Command Password Entry
Setting Password Entry
0 to 4294967295
0 to 4294967295
---
---
1
1
F003
F003
0
0
Passwords (read only actual values)
4010 Command password status 0 to 1 --- 1 F102 0 (Disabled)
4011 Setting password status 0 to 1 --- 1 F102 0 (Disabled)
Passwords (read/write settings)
4012 Control password access timeout 5 to 480 minutes 1 F001 5
4013 Setting password access timeout 5 to 480 minutes 1 F001 30
4014 Invalid password attempts 2 to 5 --- 1 F001 3
4015 Password lockout duration 5 to 60 minutes 1 F001 5
4016 Password access events 0 to 1 --- 1 F102 0 (Disabled)
4017 Local setting authorization 1 to 65535 --- 1 F300 1
4018 Remote setting authorization 0 to 65535 --- 1 F300 1
4019 Access authorization timeout 5 to 480 minutes 1 F001 30
User Display Invoke (Read/Write Setting)
4040 Invoke and Scroll Through User Display Menu Operand 0 to 65535 --- 1 F300 0
LED Test (Read/Write Setting)
4048 LED Test Function 0 to 1 --- 1 F102 0 (Disabled)
4049 LED Test Control 0 to 65535 --- 1 F300 0
Preferences (Read/Write Setting)
404F Language 0 to 3 --- 1 F531 0 (English)
4050 Flash Message Time 0.5 to 10 s 0.1 F001 10
4051 Default Message Timeout 10 to 900 s 1 F001 300
4052 Default Message Intensity 0 to 3 --- 1 F101 0 (25%)
4053 Screen Saver Feature 0 to 1 --- 1 F102 0 (Disabled)
4054 Screen Saver Wait Time 1 to 65535 min 1 F001 30
4055 Current Cutoff Level 0.002 to 0.02 pu 0.001 F001 20
4056 Voltage Cutoff Level 0.1 to 1 V 0.1 F001 10
Remote RTD Communications (Read/Write Setting)
407A RRTD Slave Address 1 to 254 --- 1 F001 254
407B RRTD Baud Rate 0 to 4 --- 1 F602 4 (19200)
407D COM2 Selection 0 to 1 --- 1 F601 0 (RS485)
Communications (Read/Write Setting)
407E COM1 minimum response time 0 to 1000 ms 10 F001 0
407F COM2 minimum response time 0 to 1000 ms 10 F001 0
4080 Modbus Slave Address 1 to 254 --- 1 F001 254
4083 RS485 Com1 Baud Rate 0 to 11 --- 1 F112 8 (115200)
4084 RS485 Com1 Parity 0 to 2 --- 1 F113 0 (None)
4085 RS485 Com2 Baud Rate 0 to 11 --- 1 F112 8 (115200)
4086 RS485 Com2 Parity 0 to 2 --- 1 F113 0 (None)
4087 IP Address 0 to 4294967295 --- 1 F003 56554706
4089 IP Subnet Mask 0 to 4294967295 --- 1 F003 4294966272
408B Gateway IP Address 0 to 4294967295 --- 1 F003 56554497
408D Network Address NSAP --- --- --- F074 0
409A DNP Channel 1 Port 0 to 4 --- 1 F177 0 (None)
409B DNP Channel 2 Port 0 to 4 --- 1 F177 0 (None)
409C DNP Address 0 to 65519 --- 1 F001 1
409D Reserved 0 to 1 --- 1 F001 0
409E DNP Client Addresses (2 items) 0 to 4294967295 --- 1 F003 0

B-18 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 12 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
40A3 TCP Port Number for the Modbus protocol 1 to 65535 --- 1 F001 502
40A4 TCP/UDP Port Number for the DNP Protocol 1 to 65535 --- 1 F001 20000
40A5 TCP Port Number for the HTTP (Web Server) Protocol 1 to 65535 --- 1 F001 80
40A6 Main UDP Port Number for the TFTP Protocol 1 to 65535 --- 1 F001 69
40A7 Data Transfer UDP Port Numbers for the TFTP Protocol 0 to 65535 --- 1 F001 0

40A9
(zero means “automatic”) (2 items)
DNP Unsolicited Responses Function 0 to 1 --- 1 F102 0 (Disabled)
B
40AA DNP Unsolicited Responses Timeout 0 to 60 s 1 F001 5
40AB DNP unsolicited responses maximum retries 1 to 255 --- 1 F001 10
40AC DNP unsolicited responses destination address 0 to 65519 --- 1 F001 1
40AD Ethernet operation mode 0 to 1 --- 1 F192 0 (Half-Duplex)
40AE DNP current scale factor 0 to 8 --- 1 F194 2 (1)
40AF DNP voltage scale factor 0 to 8 --- 1 F194 2 (1)
40B0 DNP power scale factor 0 to 8 --- 1 F194 2 (1)
40B1 DNP energy scale factor 0 to 8 --- 1 F194 2 (1)
40B2 DNP power scale factor 0 to 8 --- 1 F194 2 (1)
40B3 DNP other scale factor 0 to 8 --- 1 F194 2 (1)
40B4 DNP current default deadband 0 to 65535 --- 1 F001 30000
40B6 DNP voltage default deadband 0 to 65535 --- 1 F001 30000
40B8 DNP power default deadband 0 to 65535 --- 1 F001 30000
40BA DNP energy default deadband 0 to 65535 --- 1 F001 30000
40BE DNP other default deadband 0 to 65535 --- 1 F001 30000
40C0 DNP IIN time synchronization bit period 1 to 10080 min 1 F001 1440
40C1 DNP message fragment size 30 to 2048 --- 1 F001 240
40C2 DNP client address 3 0 to 4294967295 --- 1 F003 0
40C4 DNP client address 4 0 to 4294967295 --- 1 F003 0
40C6 DNP client address 5 0 to 4294967295 --- 1 F003 0
40C8 DNP number of paired binary output control points 0 to 32 --- 1 F001 0
40C9 DNP TCP connection timeout 10 to 65535 --- 1 F001 120
40CA Reserved (22 items) 0 to 1 --- 1 F001 0
40E0 TCP port number for the IEC 60870-5-104 protocol 1 to 65535 --- 1 F001 2404
40E1 IEC 60870-5-104 protocol function 0 to 1 --- 1 F102 0 (Disabled)
40E2 IEC 60870-5-104 protocol common address of ASDU 0 to 65535 --- 1 F001 0
40E3 IEC 60870-5-104 protocol cyclic data transmit period 1 to 65535 s 1 F001 60
40E4 IEC 60870-5-104 current default threshold 0 to 65535 --- 1 F001 30000
40E6 IEC 60870-5-104 voltage default threshold 0 to 65535 --- 1 F001 30000
40E8 IEC 60870-5-104 power default threshold 0 to 65535 --- 1 F001 30000
40EA IEC 60870-5-104 energy default threshold 0 to 65535 --- 1 F001 30000
40EC IEC 60870-5-104 power default threshold 0 to 65535 --- 1 F001 30000
40EE IEC 60870-5-104 other default threshold 0 to 65535 --- 1 F001 30000
40F0 IEC 60870-5-104 client address (5 items) 0 to 4294967295 --- 1 F003 0
4104 IEC 60870-5-104 redundancy port 0 to 1 --- 1 F126 0 (No)
4005 Reserved (59 items) 0 to 1 --- 1 F001 0
4140 DNP object 1 default variation 1 to 2 --- 1 F001 2
4141 DNP object 2 default variation 1 to 3 --- 1 F001 2
4142 DNP object 20 default variation 0 to 3 --- 1 F523 0 (1)
4143 DNP object 21 default variation 0 to 3 --- 1 F524 0 (1)
4144 DNP object 22 default variation 0 to 3 --- 1 F523 0 (1)
4145 DNP object 23 default variation 0 to 3 --- 1 F523 0 (1)
4146 DNP object 30 default variation 1 to 5 --- 1 F001 1
4147 DNP object 32 default variation 0 to 5 --- 1 F525 0 (1)
Ethernet switch (Read/Write Setting)
4148 Ethernet switch IP address 0 to 4294967295 --- 1 F003 3232235778
414A Ethernet switch Modbus IP port number 1 to 65535 --- 1 F001 502

GE Multilin G60 Generator Protection System B-19


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 13 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
414B Ethernet switch Port 1 Events 0 to 1 --- 1 F102 0 (Disabled)
414C Ethernet switch Port 2 Events 0 to 1 --- 1 F102 0 (Disabled)
414D Ethernet switch Port 3 Events 0 to 1 --- 1 F102 0 (Disabled)
414E Ethernet switch Port 4 Events 0 to 1 --- 1 F102 0 (Disabled)
414F Ethernet switch Port 5 Events 0 to 1 --- 1 F102 0 (Disabled)

B 4150 Ethernet switch Port 6 Events


Ethernet switch (Read Only Actual Values)
0 to 1 --- 1 F102 0 (Disabled)

4151 Ethernet switch MAC address --- --- 1 F072 0


4154 Ethernet switch Port 1 Status 0 to 2 --- 1 F134 0 (Fail)
4155 Ethernet switch Port 2 Status 0 to 2 --- 1 F134 0 (Fail)
4156 Ethernet switch Port 3 Status 0 to 2 --- 1 F134 0 (Fail)
4157 Ethernet switch Port 4 Status 0 to 2 --- 1 F134 0 (Fail)
4158 Ethernet switch Port 5 Status 0 to 2 --- 1 F134 0 (Fail)
4159 Ethernet switch Port 6 Status 0 to 2 --- 1 F134 0 (Fail)
415A Switch Firmware Version 0.00 to 99.99 --- 0.01 F001 0
Simple Network Time Protocol (Read/Write Setting)
4168 Simple Network Time Protocol (SNTP) function 0 to 1 --- 1 F102 0 (Disabled)
4169 Simple Network Time Protocol (SNTP) server IP address 0 to 4294967295 --- 1 F003 0
416B Simple Network Time Protocol (SNTP) UDP port number 1 to 65535 --- 1 F001 123
Data Logger Commands (Read/Write Command)
4170 Data Logger Clear 0 to 1 --- 1 F126 0 (No)
Data Logger (Read/Write Setting)
4181 Data Logger Channel Settings (16 items) --- --- --- F600 0
4191 Data Logger Mode 0 to 1 --- 1 F260 0 (continuous)
4192 Data Logger Trigger 0 to 65535 --- 1 F300 0
4193 Data Logger Rate 15 to 3600000 ms 1 F003 60000
Clock (Read/Write Command)
41A0 Real Time Clock Set Time 0 to 235959 --- 1 F050 0
Clock (Read/Write Setting)
41A2 SR Date Format 0 to 4294967295 --- 1 F051 0
41A4 SR Time Format 0 to 4294967295 --- 1 F052 0
41A6 IRIG-B Signal Type 0 to 2 --- 1 F114 0 (None)
41A7 Clock Events Enable / Disable 0 to 1 --- 1 F102 0 (Disabled)
41A8 Time Zone Offset from UTC –24 to 24 hours 0.5 F002 0
41A9 Daylight Savings Time (DST) Function 0 to 1 --- 1 F102 0 (Disabled)
41AA Daylight Savings Time (DST) Start Month 0 to 11 --- 1 F237 0 (January)
41AB Daylight Savings Time (DST) Start Day 0 to 6 --- 1 F238 0 (Sunday)
41AC Daylight Savings Time (DST) Start Day Instance 0 to 4 --- 1 F239 0 (First)
41AD Daylight Savings Time (DST) Start Hour 0 to 23 --- 1 F001 2
41AE Daylight Savings Time (DST) Stop Month 0 to 11 --- 1 F237 0 (January)
41AF Daylight Savings Time (DST) Stop Day 0 to 6 --- 1 F238 0 (Sunday)
41B0 Daylight Savings Time (DST) Stop Day Instance 0 to 4 --- 1 F239 0 (First)
41B1 Daylight Savings Time (DST) Stop Hour 0 to 23 --- 1 F001 2
Oscillography (Read/Write Setting)
41C0 Oscillography Number of Records 1 to 64 --- 1 F001 5
41C1 Oscillography Trigger Mode 0 to 1 --- 1 F118 0 (Auto. Overwrite)
41C2 Oscillography Trigger Position 0 to 100 % 1 F001 50
41C3 Oscillography Trigger Source 0 to 65535 --- 1 F300 0
41C4 Oscillography AC Input Waveforms 0 to 4 --- 1 F183 2 (16 samples/cycle)
41D0 Oscillography Analog Channel n (16 items) 0 to 65535 --- 1 F600 0
4200 Oscillography Digital Channel n (63 items) 0 to 65535 --- 1 F300 0
Trip and Alarm LEDs (Read/Write Setting)
4260 Trip LED Input FlexLogic Operand 0 to 65535 --- 1 F300 0
4261 Alarm LED Input FlexLogic Operand 0 to 65535 --- 1 F300 0

B-20 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 14 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
User Programmable LEDs (Read/Write Setting) (48 modules)
4280 FlexLogic™ Operand to Activate LED 0 to 65535 --- 1 F300 0
4281 User LED type (latched or self-resetting) 0 to 1 --- 1 F127 1 (Self-Reset)
4282 ...Repeated for User-Programmable LED 2
4284 ...Repeated for User-Programmable LED 3
4286 ...Repeated for User-Programmable LED 4 B
4288 ...Repeated for User-Programmable LED 5
428A ...Repeated for User-Programmable LED 6
428C ...Repeated for User-Programmable LED 7
428E ...Repeated for User-Programmable LED 8
4290 ...Repeated for User-Programmable LED 9
4292 ...Repeated for User-Programmable LED 10
4294 ...Repeated for User-Programmable LED 11
4296 ...Repeated for User-Programmable LED 12
4298 ...Repeated for User-Programmable LED 13
429A ...Repeated for User-Programmable LED 14
429C ...Repeated for User-Programmable LED 15
429E ...Repeated for User-Programmable LED 16
42A0 ...Repeated for User-Programmable LED 17
42A2 ...Repeated for User-Programmable LED 18
42A4 ...Repeated for User-Programmable LED 19
42A6 ...Repeated for User-Programmable LED 20
42A8 ...Repeated for User-Programmable LED 21
42AA ...Repeated for User-Programmable LED 22
42AC ...Repeated for User-Programmable LED 23
42AE ...Repeated for User-Programmable LED 24
42B0 ...Repeated for User-Programmable LED 25
42B2 ...Repeated for User-Programmable LED 26
42B4 ...Repeated for User-Programmable LED 27
42B6 ...Repeated for User-Programmable LED 28
42B8 ...Repeated for User-Programmable LED 29
42BA ...Repeated for User-Programmable LED 30
42BC ...Repeated for User-Programmable LED 31
42BE ...Repeated for User-Programmable LED 32
42C0 ...Repeated for User-Programmable LED 33
42C2 ...Repeated for User-Programmable LED 34
42C4 ...Repeated for User-Programmable LED 35
42C6 ...Repeated for User-Programmable LED 36
42C8 ...Repeated for User-Programmable LED 37
42CA ...Repeated for User-Programmable LED 38
42CC ...Repeated for User-Programmable LED 39
42CE ...Repeated for User-Programmable LED 40
42D0 ...Repeated for User-Programmable LED 41
42D2 ...Repeated for User-Programmable LED 42
42D4 ...Repeated for User-Programmable LED 43
42D6 ...Repeated for User-Programmable LED 44
42D8 ...Repeated for User-Programmable LED 45
42DA ...Repeated for User-Programmable LED 46
42DC ...Repeated for User-Programmable LED 47
42DE ...Repeated for User-Programmable LED 48
Installation (Read/Write Setting)
43E0 Relay Programmed State 0 to 1 --- 1 F133 0 (Not Programmed)
43E1 Relay Name --- --- --- F202 “Relay-1”

GE Multilin G60 Generator Protection System B-21


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 15 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
User Programmable Self Tests (Read/Write Setting)
4441 User Programmable Detect Ring Break Function 0 to 1 --- 1 F102 1 (Enabled)
4442 User Programmable Direct Device Off Function 0 to 1 --- 1 F102 1 (Enabled)
4443 User Programmable Remote Device Off Function 0 to 1 --- 1 F102 1 (Enabled)
4444 User Programmable Primary Ethernet Fail Function 0 to 1 --- 1 F102 0 (Disabled)

B 4445
4446
User Programmable Secondary Ethernet Fail Function
User Programmable Battery Fail Function
0 to 1
0 to 1
---
---
1
1
F102
F102
0 (Disabled)
1 (Enabled)
4447 User Programmable SNTP Fail Function 0 to 1 --- 1 F102 1 (Enabled)
4448 User Programmable IRIG-B Fail Function 0 to 1 --- 1 F102 1 (Enabled)
4449 User Programmable Ethernet Switch Fail Function 0 to 1 --- 1 F102 0 (Disabled)
CT Settings (Read/Write Setting) (6 modules)
4480 Phase CT 1 Primary 1 to 65000 A 1 F001 1
4481 Phase CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
4482 Ground CT 1 Primary 1 to 65000 A 1 F001 1
4483 Ground CT 1 Secondary 0 to 1 --- 1 F123 0 (1 A)
4484 ...Repeated for CT Bank 2
4488 ...Repeated for CT Bank 3
448C ...Repeated for CT Bank 4
4490 ...Repeated for CT Bank 5
4494 ...Repeated for CT Bank 6
VT Settings (Read/Write Setting) (3 modules)
4500 Phase VT 1 Connection 0 to 1 --- 1 F100 0 (Wye)
4501 Phase VT 1 Secondary 50 to 240 V 0.1 F001 664
4502 Phase VT 1 Ratio 1 to 24000 :1 1 F060 1
4504 Auxiliary VT 1 Connection 0 to 6 --- 1 F166 1 (Vag)
4505 Auxiliary VT 1 Secondary 50 to 240 V 0.1 F001 664
4506 Auxiliary VT 1 Ratio 1 to 24000 :1 1 F060 1
4508 ...Repeated for VT Bank 2
4510 ...Repeated for VT Bank 3
Source Settings (Read/Write Setting) (6 modules)
4580 Source 1 Name --- --- --- F206 “SRC 1"
4583 Source 1 Phase CT 0 to 63 --- 1 F400 0
4584 Source 1 Ground CT 0 to 63 --- 1 F400 0
4585 Source 1 Phase VT 0 to 63 --- 1 F400 0
4586 Source 1 Auxiliary VT 0 to 63 --- 1 F400 0
4587 ...Repeated for Source 2
458E ...Repeated for Source 3
4595 ...Repeated for Source 4
459C ...Repeated for Source 5
45A3 ...Repeated for Source 6
Power System (Read/Write Setting)
4600 Nominal Frequency 25 to 60 Hz 1 F001 60
4601 Phase Rotation 0 to 1 --- 1 F106 0 (ABC)
4602 Frequency And Phase Reference 0 to 5 --- 1 F167 0 (SRC 1)
4603 Frequency Tracking Function 0 to 1 --- 1 F102 1 (Enabled)
4604 Reverse Phase Rotation 0 to 65535 --- 1 F300 0
Breaker control (read/write settings)
4700 Breaker 1 function 0 to 1 --- 1 F102 0 (Disabled)
4701 Breaker 1 name --- --- --- F206 “Bkr 1"
4704 Breaker 1 mode 0 to 1 --- 1 F157 0 (3-Pole)
4705 Breaker 1 open 0 to 65535 --- 1 F300 0
4706 Breaker 1 close 0 to 65535 --- 1 F300 0
4707 Breaker 1 phase A / three-pole closed 0 to 65535 --- 1 F300 0
4708 Breaker 1 phase B closed 0 to 65535 --- 1 F300 0

B-22 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 16 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
4709 Breaker 1 phase C closed 0 to 65535 --- 1 F300 0
470A Breaker 1 external alarm 0 to 65535 --- 1 F300 0
470B Breaker 1 alarm delay 0 to 65535 s 0.001 F003 0
470D Breaker 1 pushbutton control 0 to 1 --- 1 F102 0 (Disabled)
470E Breaker 1 manual close recall time 0 to 65535 s 0.001 F003 0
4710 Breaker 1 out of service 0 to 65535 --- 1 F300 0 B
4711 Breaker 1 block open 0 to 65535 --- 1 F300 0
4712 Breaker 1 block close 0 to 65535 --- 1 F300 0
4713 Breaker 1 phase A / three-pole opened 0 to 65535 --- 1 F300 0
4714 Breaker 1 phase B opened 0 to 65535 --- 1 F300 0
4715 Breaker 1 phase C opened 0 to 65535 --- 1 F300 0
4716 Breaker 1 operate time 0 to 65535 s 0.001 F001 70
4717 Breaker 1 events 0 to 1 --- 1 F102 0 (Disabled)
4718 Reserved --- --- --- --- ---
4719 ...Repeated for breaker 2
4732 ...Repeated for breaker 3
474B ...Repeated for breaker 4
Synchrocheck (Read/Write Setting) (2 modules)
47A0 Synchrocheck 1 Function 0 to 1 --- 1 F102 0 (Disabled)
47A1 Synchrocheck 1 V1 Source 0 to 5 --- 1 F167 0 (SRC 1)
47A2 Synchrocheck 1 V2 Source 0 to 5 --- 1 F167 1 (SRC 2)
47A3 Synchrocheck 1 Maximum Voltage Difference 0 to 400000 V 1 F060 10000
47A5 Synchrocheck 1 Maximum Angle Difference 0 to 100 degrees 1 F001 30
47A6 Synchrocheck 1 Maximum Frequency Difference 0 to 2 Hz 0.01 F001 100
47A7 Synchrocheck 1 Dead Source Select 0 to 5 --- 1 F176 1 (LV1 and DV2)
47A8 Synchrocheck 1 Dead V1 Maximum Voltage 0 to 1.25 pu 0.01 F001 30
47A9 Synchrocheck 1 Dead V2 Maximum Voltage 0 to 1.25 pu 0.01 F001 30
47AA Synchrocheck 1 Live V1 Minimum Voltage 0 to 1.25 pu 0.01 F001 70
47AB Synchrocheck 1 Live V2 Minimum Voltage 0 to 1.25 pu 0.01 F001 70
47AC Synchrocheck 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
47AD Synchrocheck 1 Events 0 to 1 --- 1 F102 0 (Disabled)
47AE Synchrocheck 1 Block 0 to 65535 --- 1 F300 0
47AF Synchrocheck 1 Frequency Hysteresis 0 to 0.1 Hz 0.01 F001 6
47B0 ...Repeated for Synchrocheck 2
Flexcurves A and B (Read/Write Settings)
4800 FlexCurve A (120 items) 0 to 65535 ms 1 F011 0
48F0 FlexCurve B (120 items) 0 to 65535 ms 1 F011 0
Modbus User Map (Read/Write Setting)
4A00 Modbus Address Settings for User Map (256 items) 0 to 65535 --- 1 F001 0
User Displays Settings (Read/Write Setting) (16 modules)
4C00 User-Definable Display 1 Top Line Text --- --- --- F202 ““
4C0A User-Definable Display 1 Bottom Line Text --- --- --- F202 ““
4C14 Modbus Addresses of Display 1 Items (5 items) 0 to 65535 --- 1 F001 0
4C19 Reserved (7 items) --- --- --- F001 0
4C20 ...Repeated for User-Definable Display 2
4C40 ...Repeated for User-Definable Display 3
4C60 ...Repeated for User-Definable Display 4
4C80 ...Repeated for User-Definable Display 5
4CA0 ...Repeated for User-Definable Display 6
4CC0 ...Repeated for User-Definable Display 7
4CE0 ...Repeated for User-Definable Display 8
4D00 ...Repeated for User-Definable Display 9
4D20 ...Repeated for User-Definable Display 10
4D40 ...Repeated for User-Definable Display 11

GE Multilin G60 Generator Protection System B-23


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 17 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
4D60 ...Repeated for User-Definable Display 12
4D80 ...Repeated for User-Definable Display 13
4DA0 ...Repeated for User-Definable Display 14
4DC0 ...Repeated for User-Definable Display 15
4DE0 ...Repeated for User-Definable Display 16

B User Programmable Pushbuttons (Read/Write Setting) (12 modules)


4E00 User Programmable Pushbutton 1 Function 0 to 2 --- 1 F109 2 (Disabled)
4E01 User Programmable Pushbutton 1 Top Line --- --- --- F202 (none)
4E0B User Programmable Pushbutton 1 On Text --- --- --- F202 (none)
4E15 User Programmable Pushbutton 1 Off Text --- --- --- F202 (none)
4E1F User Programmable Pushbutton 1 Drop-Out Time 0 to 60 s 0.05 F001 0
4E20 User Programmable Pushbutton 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
4E21 User Programmable Pushbutton 1 Events 0 to 1 --- 1 F102 0 (Disabled)
4E22 User Programmable Pushbutton 1 LED Operand 0 to 65535 --- 1 F300 0
4E23 User Programmable Pushbutton 1 Autoreset Delay 0 to 600 s 0.05 F001 0
4E24 User Programmable Pushbutton 1 Autoreset Function 0 to 1 --- 1 F102 0 (Disabled)
4E25 User Programmable Pushbutton 1 Local Lock 0 to 65535 --- 1 F300 0
4E26 User Programmable Pushbutton 1 Message Priority 0 to 2 --- 1 F220 0 (Disabled)
4E27 User Programmable Pushbutton 1 Remote Lock 0 to 65535 --- 1 F300 0
4E28 User Programmable Pushbutton 1 Reset 0 to 65535 --- 1 F300 0
4E29 User Programmable Pushbutton 1 Set 0 to 65535 --- 1 F300 0
4E2A ...Repeated for User Programmable Pushbutton 2
4E54 ...Repeated for User Programmable Pushbutton 3
4E7E ...Repeated for User Programmable Pushbutton 4
4EA8 ...Repeated for User Programmable Pushbutton 5
4ED2 ...Repeated for User Programmable Pushbutton 6
4EFC ...Repeated for User Programmable Pushbutton 7
4F26 ...Repeated for User Programmable Pushbutton 8
4F50 ...Repeated for User Programmable Pushbutton 9
4F7A ...Repeated for User Programmable Pushbutton 10
4FA4 ...Repeated for User Programmable Pushbutton 11
4FCE ...Repeated for User Programmable Pushbutton 12
Flexlogic (Read/Write Setting)
5000 FlexLogic™ Entry (512 items) 0 to 65535 --- 1 F300 16384
RTD Inputs (Read/Write Setting) (48 modules)
5400 RTD Input 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5401 RTD Input 1 ID --- --- --- F205 “RTD Ip 1“
5407 RTD Input 1 Type 0 to 3 --- 1 F174 0 (100 ohm Platinum)
5407 RTD Input 1 Application 0 to 5 --- 1 F550 0 (None)
5407 RTD Input 1 Alarm Temperature 1 to 249 °C 1 F001 130
5407 RTD Input 1 Alarm Pickup Delay 0 to 600 s 0.01 F001 0
540B RTD Input 1 Trip Temperature 1 to 249 °C 1 F001 130
540C RTD Input 1 Trip Pickup Delay 0 to 600 s 0.01 F001 0
540D RTD Input 1 Trip Reset Delay 0 to 600 s 0.01 F001 0
540E RTD Input 1 Trip Voting 0 to 48 --- 1 F551 0
540F RTD Input 1 Open 0 to 2 --- 1 F552 0 (None)
5410 RTD Input 1 Block 0 to 65535 --- 1 F300 0
5411 RTD Input 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5412 RTD Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5413 ...Repeated for RTD Input 2
5426 ...Repeated for RTD Input 3
5439 ...Repeated for RTD Input 4
544C ...Repeated for RTD Input 5
545F ...Repeated for RTD Input 6

B-24 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 18 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
5472 ...Repeated for RTD Input 7
5485 ...Repeated for RTD Input 8
5498 ...Repeated for RTD Input 9
54AB ...Repeated for RTD Input 10
54BE ...Repeated for RTD Input 11
54D1 ...Repeated for RTD Input 12 B
54E4 ...Repeated for RTD Input 13
54F7 ...Repeated for RTD Input 14
550A ...Repeated for RTD Input 15
551D ...Repeated for RTD Input 16
5530 ...Repeated for RTD Input 17
5543 ...Repeated for RTD Input 18
5556 ...Repeated for RTD Input 19
5569 ...Repeated for RTD Input 20
557C ...Repeated for RTD Input 21
558F ...Repeated for RTD Input 22
55A2 ...Repeated for RTD Input 23
55B5 ...Repeated for RTD Input 24
55C8 ...Repeated for RTD Input 25
55DB ...Repeated for RTD Input 26
55EE ...Repeated for RTD Input 27
5601 ...Repeated for RTD Input 28
5614 ...Repeated for RTD Input 29
5627 ...Repeated for RTD Input 30
563A ...Repeated for RTD Input 31
564D ...Repeated for RTD Input 32
5660 ...Repeated for RTD Input 33
5673 ...Repeated for RTD Input 34
5686 ...Repeated for RTD Input 35
5699 ...Repeated for RTD Input 36
56AC ...Repeated for RTD Input 37
56BF ...Repeated for RTD Input 38
56D2 ...Repeated for RTD Input 39
56E5 ...Repeated for RTD Input 40
56F8 ...Repeated for RTD Input 41
570B ...Repeated for RTD Input 42
571E ...Repeated for RTD Input 43
5731 ...Repeated for RTD Input 44
5744 ...Repeated for RTD Input 45
5757 ...Repeated for RTD Input 46
576A ...Repeated for RTD Input 47
577D ...Repeated for RTD Input 48
Flexlogic Timers (Read/Write Setting) (32 modules)
5800 FlexLogic™ Timer 1 Type 0 to 2 --- 1 F129 0 (millisecond)
5801 FlexLogic™ Timer 1 Pickup Delay 0 to 60000 --- 1 F001 0
5802 FlexLogic™ Timer 1 Dropout Delay 0 to 60000 --- 1 F001 0
5803 Reserved (5 items) 0 to 65535 --- 1 F001 0
5808 ...Repeated for FlexLogic™ Timer 2
5810 ...Repeated for FlexLogic™ Timer 3
5818 ...Repeated for FlexLogic™ Timer 4
5820 ...Repeated for FlexLogic™ Timer 5
5828 ...Repeated for FlexLogic™ Timer 6
5830 ...Repeated for FlexLogic™ Timer 7
5838 ...Repeated for FlexLogic™ Timer 8

GE Multilin G60 Generator Protection System B-25


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 19 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
5840 ...Repeated for FlexLogic™ Timer 9
5848 ...Repeated for FlexLogic™ Timer 10
5850 ...Repeated for FlexLogic™ Timer 11
5858 ...Repeated for FlexLogic™ Timer 12
5860 ...Repeated for FlexLogic™ Timer 13

B 5868
5870
...Repeated for FlexLogic™ Timer 14
...Repeated for FlexLogic™ Timer 15
5878 ...Repeated for FlexLogic™ Timer 16
5880 ...Repeated for FlexLogic™ Timer 17
5888 ...Repeated for FlexLogic™ Timer 18
5890 ...Repeated for FlexLogic™ Timer 19
5898 ...Repeated for FlexLogic™ Timer 20
58A0 ...Repeated for FlexLogic™ Timer 21
58A8 ...Repeated for FlexLogic™ Timer 22
58B0 ...Repeated for FlexLogic™ Timer 23
58B8 ...Repeated for FlexLogic™ Timer 24
58C0 ...Repeated for FlexLogic™ Timer 25
58C8 ...Repeated for FlexLogic™ Timer 26
58D0 ...Repeated for FlexLogic™ Timer 27
58D8 ...Repeated for FlexLogic™ Timer 28
58E0 ...Repeated for FlexLogic™ Timer 29
58E8 ...Repeated for FlexLogic™ Timer 30
58F0 ...Repeated for FlexLogic™ Timer 31
58F8 ...Repeated for FlexLogic™ Timer 32
Phase Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5900 Phase Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5901 Phase Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5902 Phase Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5903 Phase Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5904 Phase Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5905 Phase Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5906 Phase Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5907 Phase Time Overcurrent 1 Voltage Restraint 0 to 1 --- 1 F102 0 (Disabled)
5908 Phase TOC 1 Block For Each Phase (3 items) 0 to 65535 --- 1 F300 0
590B Phase Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
590C Phase Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
590D Reserved (3 items) 0 to 1 --- 1 F001 0
5910 ...Repeated for Phase Time Overcurrent 2
5920 ...Repeated for Phase Time Overcurrent 3
5930 ...Repeated for Phase Time Overcurrent 4
5940 ...Repeated for Phase Time Overcurrent 5
5950 ...Repeated for Phase Time Overcurrent 6
Phase Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5A00 Phase Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5A01 Phase Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5A02 Phase Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5A03 Phase Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5A04 Phase Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5A05 Phase IOC1 Block For Phase A 0 to 65535 --- 1 F300 0
5A06 Phase IOC1 Block For Phase B 0 to 65535 --- 1 F300 0
5A07 Phase IOC1 Block For Phase C 0 to 65535 --- 1 F300 0
5A08 Phase Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5A09 Phase Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5A0A Reserved (6 items) 0 to 1 --- 1 F001 0

B-26 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 20 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
5A10 ...Repeated for Phase Instantaneous Overcurrent 2
5A20 ...Repeated for Phase Instantaneous Overcurrent 3
5A30 ...Repeated for Phase Instantaneous Overcurrent 4
5A40 ...Repeated for Phase Instantaneous Overcurrent 5
5A50 ...Repeated for Phase Instantaneous Overcurrent 6
5A60 ...Repeated for Phase Instantaneous Overcurrent 7 B
5A70 ...Repeated for Phase Instantaneous Overcurrent 8
5A80 ...Repeated for Phase Instantaneous Overcurrent 9
5A90 ...Repeated for Phase Instantaneous Overcurrent 10
5AA0 ...Repeated for Phase Instantaneous Overcurrent 11
5AB0 ...Repeated for Phase Instantaneous Overcurrent 12
Neutral Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5B00 Neutral Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5B01 Neutral Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5B02 Neutral Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5B03 Neutral Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5B04 Neutral Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5B05 Neutral Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5B06 Neutral Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5B07 Neutral Time Overcurrent 1 Block 0 to 65535 --- 1 F300 0
5B08 Neutral Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5B09 Neutral Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5B0A Reserved (6 items) 0 to 1 --- 1 F001 0
5B10 ...Repeated for Neutral Time Overcurrent 2
5B20 ...Repeated for Neutral Time Overcurrent 3
5B30 ...Repeated for Neutral Time Overcurrent 4
5B40 ...Repeated for Neutral Time Overcurrent 5
5B50 ...Repeated for Neutral Time Overcurrent 6
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5C00 Neutral Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5C01 Neutral Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5C02 Neutral Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5C03 Neutral Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5C04 Neutral Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5C05 Neutral Instantaneous Overcurrent 1 Block 0 to 65535 --- 1 F300 0
5C06 Neutral Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5C07 Neutral Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5C08 Reserved (8 items) 0 to 1 --- 1 F001 0
5C10 ...Repeated for Neutral Instantaneous Overcurrent 2
5C20 ...Repeated for Neutral Instantaneous Overcurrent 3
5C30 ...Repeated for Neutral Instantaneous Overcurrent 4
5C40 ...Repeated for Neutral Instantaneous Overcurrent 5
5C50 ...Repeated for Neutral Instantaneous Overcurrent 6
5C60 ...Repeated for Neutral Instantaneous Overcurrent 7
5C70 ...Repeated for Neutral Instantaneous Overcurrent 8
5C80 ...Repeated for Neutral Instantaneous Overcurrent 9
5C90 ...Repeated for Neutral Instantaneous Overcurrent 10
5CA0 ...Repeated for Neutral Instantaneous Overcurrent 11
5CB0 ...Repeated for Neutral Instantaneous Overcurrent 12
Ground Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5D00 Ground Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5D01 Ground Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5D02 Ground Time Overcurrent 1 Input 0 to 1 --- 1 F122 0 (Phasor)
5D03 Ground Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000

GE Multilin G60 Generator Protection System B-27


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 21 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
5D04 Ground Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)
5D05 Ground Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 100
5D06 Ground Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)
5D07 Ground Time Overcurrent 1 Block 0 to 65535 --- 1 F300 0
5D08 Ground Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)

B 5D09
5D0A
Ground Time Overcurrent 1 Events
Reserved (6 items)
0 to 1
0 to 1
---
---
1
1
F102
F001
0 (Disabled)
0
5D10 ...Repeated for Ground Time Overcurrent 2
5D20 ...Repeated for Ground Time Overcurrent 3
5D30 ...Repeated for Ground Time Overcurrent 4
5D40 ...Repeated for Ground Time Overcurrent 5
5D50 ...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5E00 Ground Instantaneous Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
5E01 Ground Instantaneous Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5E02 Ground Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 1000
5E03 Ground Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 0
5E04 Ground Instantaneous Overcurrent 1 Reset Delay 0 to 600 s 0.01 F001 0
5E05 Ground Instantaneous Overcurrent 1 Block 0 to 65535 --- 1 F300 0
5E06 Ground Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
5E07 Ground Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
5E08 Reserved (8 items) 0 to 1 --- 1 F001 0
5E10 ...Repeated for Ground Instantaneous Overcurrent 2
5E20 ...Repeated for Ground Instantaneous Overcurrent 3
5E30 ...Repeated for Ground Instantaneous Overcurrent 4
5E40 ...Repeated for Ground Instantaneous Overcurrent 5
5E50 ...Repeated for Ground Instantaneous Overcurrent 6
5E60 ...Repeated for Ground Instantaneous Overcurrent 7
5E70 ...Repeated for Ground Instantaneous Overcurrent 8
5E80 ...Repeated for Ground Instantaneous Overcurrent 9
5E90 ...Repeated for Ground Instantaneous Overcurrent 10
5EA0 ...Repeated for Ground Instantaneous Overcurrent 11
5EB0 ...Repeated for Ground Instantaneous Overcurrent 12
Frequency Out-Of-Band Accumulation (Read/Write Setting)
5F40 Frequency Out-Of-Band Accumulation Block 0 to 65535 --- 1 F300 0
5F41 Frequency Out-Of-Band Accumulation Events 0 to 1 --- 1 F102 0 (Disabled)
5F42 Frequency Out-Of-Band Accumulator 1 Function 0 to 1 --- 1 F102 0 (Disabled)
5F43 Frequency Out-Of-Band Accumulator 2 Function 0 to 1 --- 1 F102 0 (Disabled)
5F44 Frequency Out-Of-Band Accumulator 3 Function 0 to 1 --- 1 F102 0 (Disabled)
5F45 Frequency Out-Of-Band Accumulator 4 Function 0 to 1 --- 1 F102 0 (Disabled)
5F46 Frequency Out-Of-Band Accumulator 5 Function 0 to 1 --- 1 F102 0 (Disabled)
5F47 Frequency Out-Of-Band Accumulator 6 Function 0 to 1 --- 1 F102 0 (Disabled)
5F48 Frequency Out-Of-Band Accumulator 7 Function 0 to 1 --- 1 F102 0 (Disabled)
5F49 Frequency Out-Of-Band Accumulator 1 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F4A Frequency Out-Of-Band Accumulator 2 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F4B Frequency Out-Of-Band Accumulator 3 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F4C Frequency Out-Of-Band Accumulator 4 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F4D Frequency Out-Of-Band Accumulator 5 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F4E Frequency Out-Of-Band Accumulator 6 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F4F Frequency Out-Of-Band Accumulator 7 Lower Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F50 Frequency OOB Accumulation Minimum Volts/Amps 0.10 to 1.25 pu 0.01 F001 10
5F51 Frequency Out-Of-Band Accumulation Source 0 to 5 --- 1 F167 0 (SRC 1)
5F52 Frequency Out-Of-Band Accumulation Target 0 to 2 --- 1 F109 0 (Self-reset)
5F53 Frequency Out-Of-Band Accumulator 1 Time Limit 1 to 65535 s 1 F001 200

B-28 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 22 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
5F54 Frequency Out-Of-Band Accumulator 2 Time Limit 1 to 65535 s 1 F001 200
5F55 Frequency Out-Of-Band Accumulator 3 Time Limit 1 to 65535 s 1 F001 200
5F56 Frequency Out-Of-Band Accumulator 4 Time Limit 1 to 65535 s 1 F001 200
5F57 Frequency Out-Of-Band Accumulator 5 Time Limit 1 to 65535 s 1 F001 200
5F58 Frequency Out-Of-Band Accumulator 6 Time Limit 1 to 65535 s 1 F001 200
5F59 Frequency Out-Of-Band Accumulator 7 Time Limit 1 to 65535 s 1 F001 200 B
5F5A Frequency Out-Of-Band Accumulator 1 Time Preset 0 to 65535 s 1 F001 0
5F5B Frequency Out-Of-Band Accumulator 2 Time Preset 0 to 65535 s 1 F001 0
5F5C Frequency Out-Of-Band Accumulator 3 Time Preset 0 to 65535 s 1 F001 0
5F5D Frequency Out-Of-Band Accumulator 4 Time Preset 0 to 65535 s 1 F001 0
5F5E Frequency Out-Of-Band Accumulator 5 Time Preset 0 to 65535 s 1 F001 0
5F5F Frequency Out-Of-Band Accumulator 6 Time Preset 0 to 65535 s 1 F001 0
5F60 Frequency Out-Of-Band Accumulator 7 Time Preset 0 to 65535 s 1 F001 0
5F61 Frequency Out-Of-Band Accumulator 1 Upper Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F62 Frequency Out-Of-Band Accumulator 2 Upper Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F63 Frequency Out-Of-Band Accumulator 3 Upper Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F64 Frequency Out-Of-Band Accumulator 4 Upper Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F65 Frequency Out-Of-Band Accumulator 5 Upper Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F66 Frequency Out-Of-Band Accumulator 6 Upper Frequency 20.00 to 70.00 Hz 0.01 F001 6000
5F67 Frequency Out-Of-Band Accumulator 7 Upper Frequency 20.00 to 70.00 Hz 0.01 F001 6000
Setting Groups (Read/Write Setting)
5F80 Setting Group for Modbus Comms (0 means group 1) 0 to 5 --- 1 F001 0
5F81 Setting Groups Block 0 to 65535 --- 1 F300 0
5F82 FlexLogic to Activate Groups 2 through 6 (5 items) 0 to 65535 --- 1 F300 0
5F89 Setting Group Function 0 to 1 --- 1 F102 0 (Disabled)
5F8A Setting Group Events 0 to 1 --- 1 F102 0 (Disabled)
Setting Groups (Read Only)
5F8B Current Setting Group 0 to 5 --- 1 F001 0
Setting Group Names (Read/Write Setting)
5F8C Setting Group 1 Name --- --- --- F203 (none)
5F94 Setting Group 2 Name --- --- --- F203 (none)
5F9C Setting Group 3 Name --- --- --- F203 (none)
5FA4 Setting Group 4 Name --- --- --- F203 (none)
5FAC Setting Group 5 Name --- --- --- F203 (none)
5FB4 Setting Group 6 Name --- --- --- F203 (none)
Stator Differential (Read/Write Grouped Setting)
6470 Stator Differential Function 0 to 1 --- 1 F102 0 (Disabled)
6471 Stator Differential Pickup 0.05 to 1 pu 0.001 F001 100
6472 Stator Differential Slope 1 1 to 100 % 1 F001 10
6473 Stator Differential Slope 2 1 to 100 % 1 F001 80
6474 Stator Differential Break 1 1 to 1.5 pu 0.01 F001 115
6475 Stator Differential Break 2 1.5 to 30 pu 0.01 F001 800
6476 Stator Differential Block 0 to 65535 --- 1 F300 0
6477 Stator Differential Targets 0 to 2 --- 1 F109 0 (Self-reset)
6478 Stator Differential Events 0 to 1 --- 1 F102 0 (Disabled)
6479 Stator Differential Line End Source 0 to 5 --- 1 F167 0 (SRC 1)
647A Stator Differential Neutral End Source 0 to 5 --- 1 F167 0 (SRC 1)
Negative Sequence Overvoltage (Read/Write Grouped Setting)
64A0 Negative Sequence Overvoltage Function 0 to 1 --- 1 F102 0 (Disabled)
64A1 Negative Sequence Overvoltage Source 0 to 5 --- 1 F167 0 (SRC 1)
64A2 Negative Sequence Overvoltage Pickup 0 to 1.25 pu 0.001 F001 300
64A3 Negative Sequence Overvoltage Pickup Delay 0 to 600 s 0.01 F001 50
64A4 Negative Sequence Overvoltage Reset Delay 0 to 600 s 0.01 F001 50
64A5 Negative Sequence Overvoltage Block 0 to 65535 --- 1 F300 0

GE Multilin G60 Generator Protection System B-29


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 23 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
64A6 Negative Sequence Overvoltage Target 0 to 2 --- 1 F109 0 (Self-reset)
64A7 Negative Sequence Overvoltage Events 0 to 1 --- 1 F102 0 (Disabled)
Overfrequency (Read/Write Setting) (4 modules)
64D0 Overfrequency 1 Function 0 to 1 --- 1 F102 0 (Disabled)
64D1 Overfrequency 1 Block 0 to 65535 --- 1 F300 0

B 64D2
64D3
Overfrequency 1 Source
Overfrequency 1 Pickup
0 to 5
20 to 65
---
Hz
1
0.01
F167
F001
0 (SRC 1)
6050
64D4 Overfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 500
64D5 Overfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 500
64D6 Overfrequency 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
64D7 Overfrequency 1 Events 0 to 1 --- 1 F102 0 (Disabled)
64D8 Reserved (4 items) 0 to 1 --- 1 F001 0
64DC ...Repeated for Overfrequency 2
64E8 ...Repeated for Overfrequency 3
64F4 ...Repeated for Overfrequency 4
Power Swing Detect (Read/Write Grouped Setting)
65C0 Power Swing Detect Function 0 to 1 --- 1 F102 0 (Disabled)
65C1 Power Swing Detect Source 0 to 5 --- 1 F167 0 (SRC 1)
65C2 Power Swing Detect Mode 0 to 1 --- 1 F513 0 (Two Step)
65C3 Power Swing Detect Supervision 0.05 to 30 pu 0.001 F001 600
65C4 Power Swing Detect Forward Reach 0.1 to 500 ohms 0.01 F001 5000
65C5 Power Swing Detect Forward RCA 40 to 90 degrees 1 F001 75
65C6 Power Swing Detect Reverse Reach 0.1 to 500 ohms 0.01 F001 5000
65C7 Power Swing Detect Reverse RCA 40 to 90 degrees 1 F001 75
65C8 Power Swing Detect Outer Limit Angle 40 to 140 degrees 1 F001 120
65C9 Power Swing Detect Middle Limit Angle 40 to 140 degrees 1 F001 90
65CA Power Swing Detect Inner Limit Angle 40 to 140 degrees 1 F001 60
65CB Power Swing Detect Delay 1 Pickup 0 to 65.535 s 0.001 F001 30
65CC Power Swing Detect Delay 1 Reset 0 to 65.535 s 0.001 F001 50
65CD Power Swing Detect Delay 2 Pickup 0 to 65.535 s 0.001 F001 17
65CE Power Swing Detect Delay 3 Pickup 0 to 65.535 s 0.001 F001 9
65CF Power Swing Detect Delay 4 Pickup 0 to 65.535 s 0.001 F001 17
65D0 Power Swing Detect Seal In Delay 0 to 65.535 s 0.001 F001 400
65D1 Power Swing Detect Trip Mode 0 to 1 --- 1 F514 0 (Delayed)
65D2 Power Swing Detect Block 0 to 65535 --- 1 F300 0
65D3 Power Swing Detect Target 0 to 2 --- 1 F109 0 (Self-reset)
65D4 Power Swing Detect Event 0 to 1 --- 1 F102 0 (Disabled)
65D5 Power Swing Detect Shape 0 to 1 --- 1 F085 0 (Mho Shape)
65D6 Power Swing Detect Quad Forward Middle 0.1 to 500 ohms 0.01 F001 6000
65D7 Power Swing Detect Quad Forward Outer 0.1 to 500 ohms 0.01 F001 7000
65D8 Power Swing Detect Quad Reverse Middle 0.1 to 500 ohms 0.01 F001 6000
65D9 Power Swing Detect Quad Reverse Outer 0.1 to 500 ohms 0.01 F001 7000
65DA Power Swing Detect Outer Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DB Power Swing Detect Outer Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DC Power Swing Detect Middle Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DD Power Swing Detect Middle Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DE Power Swing Detect Inner Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DF Power Swing Detect Inner Left Blinder 0.1 to 500 ohms 0.01 F001 10000
Accidental Energization (Read/Write Grouped Setting)
6660 Accidental Energization Function 0 to 1 --- 1 F102 0 (Disabled)
6661 Accidental Energization Source 0 to 5 --- 1 F167 0 (SRC 1)
6662 Accidental Energization Arming Mode 0 to 1 --- 1 F193 0 (UV AND OFFLINE)
6663 Accidental Energization OC Pickup 0 to 3 --- 0.001 F003 300
6665 Accidental Energization UV Pickup 0 to 3 --- 0.001 F003 500

B-30 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 24 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
6667 Accidental Energization Offline 0 to 65535 --- 1 F300 0
6668 Accidental Energization Block 0 to 65535 --- 1 F300 0
6669 Accidental Energization Target 0 to 2 --- 1 F109 0 (Self-reset)
666A Accidental Energization Events 0 to 1 --- 1 F102 0 (Disabled)
666B Reserved (5 items) 0 to 65535 --- 1 F001 0
Loss of Excitation (Read/Write Grouped Setting) B
6680 Loss Of Excitation Function 0 to 1 --- 1 F102 0 (Disabled)
6681 Loss Of Excitation Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
6682 Loss Of Excitation Center 1 0.1 to 300 ohm 0.01 F001 1000
6683 Loss Of Excitation Radius 1 0.1 to 300 ohm 0.01 F001 800
6684 Loss Of Excitation UV Supervision Enable 1 0 to 1 --- 1 F102 1 (Enabled)
6685 Loss Of Excitation Pickup Delay 1 0 to 65.535 s 0.001 F001 50
6686 Loss Of Excitation Center 2 0.1 to 300 ohm 0.01 F001 1200
6687 Loss Of Excitation Radius 2 0.1 to 300 ohm 0.01 F001 1000
6688 Loss Of Excitation UV Supervision Enable 2 0 to 1 --- 1 F102 1 (Enabled)
6689 Loss Of Excitation Pickup Delay 2 0 to 65.535 s 0.001 F001 500
668A Loss Of Excitation UV Supervision 0 to 1.25 pu 0.001 F001 700
668B Loss Of Excitation Block 0 to 65535 --- 1 F300 0
668C Loss Of Excitation Target 0 to 2 --- 1 F109 0 (Self-reset)
668D Loss Of Excitation Events 0 to 1 --- 1 F102 0 (Disabled)
668E Reserved (5 items) 0 to 65535 --- 1 F001 0
Sensitive Directional Power (Read/Write Grouped Setting) (2 modules)
66A0 Sensitive Directional Power 1 Function 0 to 1 --- 1 F102 0 (Disabled)
66A1 Sensitive Directional Power 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
66A2 Sensitive Directional Power 1 RCA 0 to 359 degrees 1 F001 0
66A3 Sensitive Directional Power 1 Calibration 0 to 0.95 degrees 0.05 F001 0
66A4 Sensitive Directional Power 1 STG1 SMIN -1.2 to 1.2 pu 0.001 F002 100
66A5 Sensitive Directional Power 1 STG1 Delay 0 to 600 s 0.01 F001 50
66A6 Sensitive Directional Power 1 STG2 SMIN -1.2 to 1.2 pu 0.001 F002 100
66A7 Sensitive Directional Power 1 STG2 Delay 0 to 600 s 0.01 F001 2000
66A8 Sensitive Directional Power 1 Block --- --- --- F001 0
66A9 Sensitive Directional Power 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
66AA Sensitive Directional Power 1 Events 0 to 1 --- 1 F102 0 (Disabled)
66AB Reserved (5 items) 0 to 65535 --- 1 F001 0
66B0 ...Repeated for Sensitive Directional Power 2
Third Harmonic Neutral Undervoltage (Read/Write Grouped Setting)
6730 Third Harmonic Neutral Undervoltage Function 0 to 1 --- 1 F102 0 (Disabled)
6731 Third Harmonic Neutral Undervoltage Pickup 0 to 30 pu 0.0001 F003 3000
6733 Third Harmonic Neutral Undervoltage Delay 0 to 600 s 0.01 F001 0
6734 Third Harmonic Neutral Undervoltage Max Power 0 to 30 pu 0.001 F003 200
6736 Third Harmonic Neutral Undervoltage Min Power 0 to 30 pu 0.001 F003 200
6738 Third Harmonic Neutral Undervoltage Volt Supervision 0 to 1.25 pu 0.001 F001 500
6739 Third Harmonic Neutral Undervoltage Block 0 to 65535 --- 1 F300 0
673A Third Harmonic Neutral Undervoltage Target 0 to 2 --- 1 F109 0 (Self-reset)
673B Third Harmonic Neutral Undervoltage Events 0 to 1 --- 1 F102 0 (Disabled)
673C Reserved (4 items) 0 to 65535 --- 1 F001 0
Generator Unbalance (Read/Write Grouped Setting)
6740 Generator Unbalance Function 0 to 1 --- 1 F102 0 (Disabled)
6741 Generator Unbalance Source 0 to 5 --- 1 F167 0 (SRC 1)
6742 Generator Unbalance Source 0 to 1.25 pu 0.001 F001 800
6743 Generator Unbalance Stage 1 Pickup 0 to 100 % 0.01 F001 800
6744 Generator Unbalance Stage 1 K value 0 to 100 --- 0.01 F001 100
6745 Generator Unbalance Stage 1 Tmin 0 to 50 s 0.001 F001 250
6746 Generator Unbalance Stage 1 Tmax 0 to 1000 s 0.1 F001 6000

GE Multilin G60 Generator Protection System B-31


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 25 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
6747 Generator Unbalance Stage 1 K Reset 0 to 1000 s 0.1 F001 2400
6748 Generator Unbalance Stage 2 Pickup 0 to 100 % 0.01 F001 300
6749 Generator Unbalance Stage 2 Pickup Delay 0 to 1000 s 0.1 F001 50
674A Generator Unbalance Block 0 to 65535 --- 1 F300 0
674B Generator Unbalance Target 0 to 2 --- 1 F109 0 (Self-reset)

B 674C
674D
Generator Unbalance Events
Reserved (3 items)
0 to 1
0 to 65535
---
---
1
1
F102
F001
0 (Disabled)
0
Stator Ground Source (Read/Write Grouped Setting)
6750 Stator Ground Source 0 to 5 --- 1 F167 0 (SRC 1)
Stator Ground (Read/Write Grouped Setting)
6780 Stator Ground Function 0 to 1 --- 1 F102 0 (Disabled)
6781 Stator Ground Stage 1 Pickup 0 to 0.900 pu 0.001 F001 150
6782 Stator Ground Stage 1 Pickup Delay 0 to 600 s 0.01 F001 100
6783 Stator Ground Stage 1 Supervision 0.001 to 0.100 pu 0.0001 F001 57
6784 Stator Ground Stage 2 Pickup 0 to 0.900 pu 0.001 F001 150
6785 Stator Ground Stage 2 Pickup Delay 0 to 600 s 0.01 F001 0
6786 Stator Ground Stage 2 Supervision 0.001 to 0.100 pu 0.0001 F001 45
6787 Stator Ground Block --- --- --- F001 0
6788 Stator Ground Target 0 to 2 --- 1 F109 0 (Self-reset)
6789 Stator Ground Event 0 to 1 --- 1 F102 0 (Disabled)
678A Reserved (5 items) 0 to 65535 --- 1 F001 0
Split Phase Protection (Read/Write Grouped Setting)
67A0 Split Phase Protection Function 0 to 1 --- 1 F102 0 (Disabled)
67A1 Split Phase Protection Source 0 to 5 --- 1 F167 0 (SRC1)
67A2 Split Phase Protection Load Source 0 to 5 --- 1 F167 0 (SRC1)
67A3 Split Phase Protection Phase A Pickup 0.020 to 1.500 pu 0.001 F001 200
67A4 Split Phase Protection Phase A Offset 0 to 1 pu 0.001 F001 0
67A5 Split Phase Protection Phase A Slope 0 to 100 % 0.1 F001 0
67A6 Split Phase Protection Phase B Pickup 0.020 to 1.500 pu 0.001 F001 200
67A7 Split Phase Protection Phase B Offset 0 to 1 pu 0.001 F001 0
67A8 Split Phase Protection Phase B Slope 0 to 100 % 0.1 F001 0
67A9 Split Phase Protection Phase C Pickup 0.020 to 1.500 pu 0.001 F001 200
67AA Split Phase Protection Phase C Offset 0 to 1 pu 0.001 F001 0
67AB Split Phase Protection Phase C Slope 0 to 100 % 0.1 F001 0
67AC Split Phase Protection Minimum Load 0 to 1 pu 0.01 F001 0
67AD Split Phase Protection Mode 0 to 1 --- 1 F225 0 (Over)
67AE Split Phase Protection Delay 0 to 65.535 s 0.001 F001 0
67AF Split Phase Protection Block 0 to 65535 --- 1 F300 0
67B0 Split Phase Protection Target 0 to 2 --- 1 F109 0 (Self-Reset)
67B1 Split Phase Protection Events 0 to 1 --- 1 F102 0 (Disabled)
67B2 Reserved (6 items) 0 to 65535 --- 1 F001 0
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000 Phase Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7001 Phase Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7002 Phase Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7003 Phase Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)
7004 Phase Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7005 Phase Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
7006 Phase Undervoltage 1 Block 0 to 65535 --- 1 F300 0
7007 Phase Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7008 Phase Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7009 Phase Undervoltage 1 Measurement Mode 0 to 1 --- 1 F186 0 (Phase to Ground)
700A Reserved (6 items) 0 to 1 --- 1 F001 0
7013 ...Repeated for Phase Undervoltage 2

B-32 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 26 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
Phase Overvoltage (Read/Write Grouped Setting)
7040 Phase Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7041 Phase Overvoltage 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7042 Phase Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7043 Phase Overvoltage 1 Delay 0 to 600 s 0.01 F001 100
7044 Phase Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100 B
7045 Phase Overvoltage 1 Block 0 to 65535 --- 1 F300 0
7046 Phase Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7047 Phase Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7048 Reserved (8 items) 0 to 1 --- 1 F001 0
Distance (Read/Write Grouped Setting)
7060 Distance Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7061 Memory Duration 5 to 25 cycles 1 F001 10
7062 Force Self-Polarization 0 to 65535 --- 1 F300 0
7062 Force Memory Polarization 0 to 65535 --- 1 F300 0
Phase Distance (Read/Write Grouped Setting) (5 modules)
7070 Phase Distance Zone 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7071 Phase Distance Zone 1 Current Supervision 0.05 to 30 pu 0.001 F001 200
7072 Phase Distance Zone 1 Reach 0.02 to 500 ohms 0.01 F001 200
7073 Phase Distance Zone 1 Direction 0 to 2 --- 1 F154 0 (Forward)
7074 Phase Distance Zone 1 Comparator Limit 30 to 90 degrees 1 F001 90
7075 Phase Distance Zone 1 Delay 0 to 65.535 s 0.001 F001 0
7076 Phase Distance Zone 1 Block 0 to 65535 --- 1 F300 0
7077 Phase Distance Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7078 Phase Distance Zone 1 Events 0 to 1 --- 1 F102 0 (Disabled)
707A Phase Distance Zone 1 RCA 30 to 90 degrees 1 F001 85
707B Phase Distance Zone 1 DIR RCA 30 to 90 degrees 1 F001 85
707C Phase Distance Zone 1 DIR Comp Limit 30 to 90 degrees 1 F001 90
7081 Phase Distance Zone 1 Volt Limit 0 to 5 pu 0.001 F001 0
7082 Phase Distance Zone 1 Transformer Voltage Connection 0 to 12 --- 1 F153 0 (None)
7083 Phase Distance Zone 1 Transformer Current Connection 0 to 12 --- 1 F153 0 (None)
7084 Phase Distance Zone 1 Rev Reach 0.02 to 500 ohms 0.01 F001 200
7085 Phase Distance Zone 1 Rev Reach RCA 30 to 90 degrees 1 F001 85
7086 Reserved (10 items) --- --- --- F001 0
7090 ...Repeated for Phase Distance Zone 2
70B0 ...Repeated for Phase Distance Zone 3
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7260 Phase Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7261 Phase Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7262 Phase Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 0
7263 Phase Directional Overcurrent 1 ECA 0 to 359 --- 1 F001 30
7264 Phase Directional Overcurrent 1 Pol V Threshold 0 to 3 pu 0.001 F001 700
7265 Phase Directional Overcurrent 1 Block Overcurrent 0 to 1 --- 1 F126 0 (No)
7266 Phase Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7267 Phase Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7268 Reserved (8 items) 0 to 1 --- 1 F001 0
7270 ...Repeated for Phase Directional Overcurrent 2
Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7280 Neutral Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7281 Neutral Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7282 Neutral Directional Overcurrent 1 Polarizing 0 to 2 --- 1 F230 0 (Voltage)
7283 Neutral Directional Overcurrent 1 Forward ECA -90 to 90 ° Lag 1 F002 75
7284 Neutral Directional Overcurrent 1 Forward Limit Angle 40 to 90 degrees 1 F001 90
7285 Neutral Directional Overcurrent 1 Forward Pickup 0.002 to 30 pu 0.001 F001 50

GE Multilin G60 Generator Protection System B-33


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 27 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
7286 Neutral Directional Overcurrent 1 Reverse Limit Angle 40 to 90 degrees 1 F001 90
7287 Neutral Directional Overcurrent 1 Reverse Pickup 0.002 to 30 pu 0.001 F001 50
7288 Neutral Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7289 Neutral Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 0
728A Neutral Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)

B 728B
728C
Neutral Directional Overcurrent 1 Polarizing Voltage
Neutral Directional Overcurrent 1 Op Current
0 to 1
0 to 1
---
---
1
1
F231
F196
0 (Calculated V0)
0 (Calculated 3I0)
728D Neutral Directional Overcurrent 1 Offset 0 to 250 ohms 0.01 F001 0
728E Neutral Directional Overcurrent 1 Pos Seq Restraint 0 to 0.5 --- 0.001 F001 63
728F Reserved 0 to 1 --- 1 F001 0
7290 ...Repeated for Neutral Directional Overcurrent 2
Negative-sequence directional overcurrent (read/write grouped settings) (2 modules)
72A0 Negative Sequence Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)
72A1 Negative Sequence Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
72A2 Negative Sequence Directional Overcurrent 1 Type 0 to 1 --- 1 F179 0 (Neg Sequence)
72A3 Neg Sequence Directional Overcurrent 1 Forward ECA 0 to 90 ° Lag 1 F002 75
72A4 Neg Seq Directional Overcurrent 1 Forward Limit Angle 40 to 90 degrees 1 F001 90
72A5 Neg Sequence Directional Overcurrent 1 Forward Pickup 0.015 to 30 pu 0.05 F001 5
72A6 Neg Seq Directional Overcurrent 1 Reverse Limit Angle 40 to 90 degrees 1 F001 90
72A7 Neg Sequence Directional Overcurrent 1 Reverse Pickup 0.015 to 30 pu 0.05 F001 5
72A8 Negative Sequence Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
72A9 Negative Sequence Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 0
72AA Negative Sequence Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)
72AB Negative Sequence Directional Overcurrent 1 Offset 0 to 250 ohms 0.01 F001 0
72AC Neg Seq Directional Overcurrent 1 Pos Seq Restraint 0 to 0.5 --- 0.001 F001 63
72AD Reserved (3 items) 0 to 1 --- 1 F001 0
72B0 ...Repeated for Neg Seq Directional Overcurrent 2
dcmA Inputs (Read/Write Setting) (24 modules)
7300 dcmA Inputs 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7301 dcmA Inputs 1 ID --- --- --- F205 “DCMA I 1"
7307 Reserved 1 (4 items) 0 to 65535 --- 1 F001 0
730B dcmA Inputs 1 Units --- --- --- F206 “mA”
730E dcmA Inputs 1 Range 0 to 6 --- 1 F173 6 (4 to 20 mA)
730F dcmA Inputs 1 Minimum Value -9999.999 to 9999.999 --- 0.001 F004 4000
7311 dcmA Inputs 1 Maximum Value -9999.999 to 9999.999 --- 0.001 F004 20000
7313 Reserved (5 items) 0 to 65535 --- 1 F001 0
7318 ...Repeated for dcmA Inputs 2
7330 ...Repeated for dcmA Inputs 3
7348 ...Repeated for dcmA Inputs 4
7360 ...Repeated for dcmA Inputs 5
7378 ...Repeated for dcmA Inputs 6
7390 ...Repeated for dcmA Inputs 7
73A8 ...Repeated for dcmA Inputs 8
73C0 ...Repeated for dcmA Inputs 9
73D8 ...Repeated for dcmA Inputs 10
73F0 ...Repeated for dcmA Inputs 11
7408 ...Repeated for dcmA Inputs 12
7420 ...Repeated for dcmA Inputs 13
7438 ...Repeated for dcmA Inputs 14
7450 ...Repeated for dcmA Inputs 15
7468 ...Repeated for dcmA Inputs 16
7480 ...Repeated for dcmA Inputs 17
7498 ...Repeated for dcmA Inputs 18
74B0 ...Repeated for dcmA Inputs 19

B-34 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 28 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
74C8 ...Repeated for dcmA Inputs 20
74E0 ...Repeated for dcmA Inputs 21
74F8 ...Repeated for dcmA Inputs 22
7510 ...Repeated for dcmA Inputs 23
7528 ...Repeated for dcmA Inputs 24
Disconnect switches (read/write settings) B
7540 Disconnect switch 1 function 0 to 1 --- 1 F102 0 (Disabled)
7541 Disconnect switch 1 name --- --- --- F206 “SW 1"
7544 Disconnect switch 1 mode 0 to 1 --- 1 F157 0 (3-Pole)
7545 Disconnect switch 1 open 0 to 65535 --- 1 F300 0
7546 Disconnect switch 1 block open 0 to 65535 --- 1 F300 0
7547 Disconnect switch 1 close 0 to 65535 --- 1 F300 0
7548 Disconnect switch 1 block close 0 to 65535 --- 1 F300 0
7549 Disconnect switch 1 phase A / three-pole closed 0 to 65535 --- 1 F300 0
754A Disconnect switch 1 phase A / three-pole opened 0 to 65535 --- 1 F300 0
754B Disconnect switch 1 phase B closed 0 to 65535 --- 1 F300 0
754C Disconnect switch 1 phase B opened 0 to 65535 --- 1 F300 0
754D Disconnect switch 1 phase C closed 0 to 65535 --- 1 F300 0
754E Disconnect switch 1 phase C opened 0 to 65535 --- 1 F300 0
754F Disconnect switch 1 operate time 0 to 65535 s 0.001 F001 70
7550 Disconnect switch 1 alarm delay 0 to 65535 s 0.001 F003 0
7552 Disconnect switch 1 events 0 to 1 --- 1 F102 0 (Disabled)
7553 Reserved (2 items) --- --- --- --- ---
7555 ...Repeated for disconnect switch 2
756A ...Repeated for disconnect switch 3
757F ...Repeated for disconnect switch 4
7594 ...Repeated for disconnect switch 5
75A9 ...Repeated for disconnect switch 6
75BE ...Repeated for disconnect switch 7
75D3 ...Repeated for disconnect switch 8
75E8 ...Repeated for disconnect switch 9
75FD ...Repeated for disconnect switch 10
7612 ...Repeated for disconnect switch 11
7627 ...Repeated for disconnect switch 12
763C ...Repeated for disconnect switch 13
7651 ...Repeated for disconnect switch 14
7666 ...Repeated for disconnect switch 15
767B ...Repeated for disconnect switch 16
Thermal Overload Protecttion (Read/Write Settings)
7738 Thermal Protection 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7739 Thermal Protection 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
773A Thermal Protection 1 Base Current 0.2 to 3 pu 0.01 F001 80
773B Thermal Protection 1 K Factor 1 to 1.2 --- 0.05 F001 110
773C Thermal Protection 1 Trip Time Constant 0 to 1000 min. 1 F001 45
773D Thermal Protection 1 Reset Time Constant 0 to 1000 min. 1 F001 45
773E Thermal Protection 1 Minimum Reset Time 0 to 1000 min. 1 F001 20
773F Thermal Protection 1 Reset 0 to 65535 --- 1 F300 0
7740 Thermal Protection 1 Block 0 to 65535 --- 1 F300 0
7741 Thermal Protection 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7742 Thermal Protection 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7743 Reserved (2 items) --- --- --- F001 0
7745 Repeated for Thermal Protection 2
Phasor Measurement Unit Power Trigger (Read/Write Setting)
7860 PMU 1 Power Trigger Function 0 to 1 --- 1 F102 0 (Disabled)

GE Multilin G60 Generator Protection System B-35


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 29 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
7861 PMU 1 Power Trigger Active 0.25 to 3 pu 0.001 F001 1250
7862 PMU 1 Power Trigger Reactive 0.25 to 3 pu 0.001 F001 1250
7863 PMU 1 Power Trigger Apparent 0.25 to 3 pu 0.001 F001 1250
7864 PMU 1 Power Trigger Pickup Time 0 to 600 s 0.01 F001 10
7865 PMU 1 Power Trigger Dropout Time 0 to 600 s 0.01 F001 100

B 7866
7869
PMU 1 Power Trigger Block (3 items)
PMU 1 Power Trigger Target
0 to 65535
0 to 2
---
---
1
1
F300
F109
0
0 (Self-reset)
786A PMU 1 Power Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
786B ...Repeated for PMU 2
7876 ...Repeated for PMU 3
7881 ...Repeated for PMU 4
Phasor Measurement Unit Voltage Trigger (Read/Write Setting)
788C PMU 1 Voltage Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
788D PMU 1 Voltage Trigger Low Voltage 0.25 to 1.25 pu 0.001 F001 800
788E PMU 1 Voltage Trigger High Voltage 0.75 to 1.75 pu 0.001 F001 1200
788F PMU 1 Voltage Trigger Pickup Time 0 to 600 s 0.01 F001 10
7890 PMU 1 Voltage Trigger Dropout Time 0 to 600 s 0.01 F001 100
7891 PMU 1 Voltage Trigger Block (3 items) 0 to 65535 --- 1 F300 0
7894 PMU 1 Voltage Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
7895 PMU 1 Voltage Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit One-shot Command (Read/Write Setting)
78B4 PMU One-shot Function 0 to 1 --- 1 F102 0 (Disabled)
78B5 PMU One-shot Sequence Number 0 to 59 --- 1 F001 1
78B6 PMU One-shot Time 0 to 235959 --- 1 F050 0
Phasor Measurement Unit Test Values (Read/Write Setting)
78B8 PMU 1 Test Function 0 to 1 --- 1 F102 0 (Disabled)
78B9 PMU 1 Phase A Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
78BB PMU 1 Phase A Voltage Test Angle -180 to 180 ° 0.05 F002 0
78BC PMU 1 Phase B Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
78BE PMU 1 Phase B Voltage Test Angle -180 to 180 ° 0.05 F002 -120
78BF PMU 1 Phase C Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
78C1 PMU 1 Phase C Voltage Test Angle -180 to 180 ° 0.05 F002 120
78C2 PMU 1 Auxiliary Voltage Test Magnitude 0 to 700 kV 0.01 F003 50000
78C4 PMU 1 Auxiliary Voltage Test Angle -180 to 180 ° 0.05 F002 0
78C5 PMU 1 Phase A Current Test Magnitude 0 to 9.999 kA 0.001 F004 1000
78C7 PMU 1 Phase A Current Test Angle -180 to 180 ° 0.05 F002 -10
78C8 PMU 1 Phase B Current Test Magnitude 0 to 9.999 kA 0.001 F004 1000
78CA PMU 1 Phase B Current Test Angle -180 to 180 ° 0.05 F002 -130
78CB PMU 1 Phase C Current Test Magnitude 0 to 9.999 kA 0.001 F003 1000
78CD PMU 1 Phase C Current Test Angle -180 to 180 ° 0.05 F002 110
78CE PMU 1 Ground Current Test Magnitude 0 to 9.999 kA 0.001 F004 0
78D0 PMU 1 Ground Current Test Angle -180 to 180 ° 0.05 F002 0
78D1 PMU 1 Test Frequency 20 to 70 Hz 0.001 F003 60000
78D3 PMU 1 Test df/dt -10 to 10 Hz/s 0.001 F002 0
Phasor Measurement Unit Recorder Configuration Counter Command (Read/Write Command)
7928 PMU 1 Recorder Clear Configuration Counter 0 to 1 --- 1 F126 0 (No)
Phasor Measurement Unit Recording Values (Read Only)
792C PMU 1 Available Records 0 to 65535 --- 1 F001 0
792D PMU 1 Second Per Record 0 to 6553.5 --- 0.1 F001 0
792F PMU 1 Last Cleared Date 0 to 400000000 --- 1 F050 0
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
7940 PMU Network Reporting Function 0 to 1 --- 1 F102 0 (Disabled)
7941 PMU Network Reporting ID Code 1 to 65534 --- 1 F001 1
7942 PMU Network Reporting Rate 0 to 11 --- 1 F544 3 (10/sec.)

B-36 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 30 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
7943 PMU Network Reporting Style 0 to 1 --- 1 F546 0 (Polar)
7944 PMU Network Reporting Format 0 to 1 --- 1 F547 0 (Integer)
7945 PMU Network PDC Control 0 to 1 --- 1 F102 0 (Disabled)
7946 PMU TCP port number 1 to 65535 --- 1 F001 4712
7947 PMU UDP port number 1 1 to 65535 --- 1 F001 4713
7948 PMU UDP port number 2 1 to 65535 --- 1 F001 4714 B
Phasor Measurement Unit Basic Configuration (Read/Write Setting)
7949 PMU 1 Function 0 to 1 --- 1 F102 0 (Disabled)
794A PMU 1 IDcode 1 to 65534 --- 1 F001 1
794B PMU 1 STN --- --- --- F203 “GE-UR-PMU”
7953 PMU 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7954 PMU 1 Post-Filter 0 to 3 --- 1 F540 1 (Symm-3-point)
Phasor Measurement Unit Calibration (Read/Write Setting)
7979 PMU 1 Va Calibration Angle -5 to 5 ° 0.05 F002 0
797A PMU 1 Vb Calibration Angle -5 to 5 ° 0.05 F002 0
797B PMU 1 Vc Calibration Angle -5 to 5 ° 0.05 F002 0
797C PMU 1 Vx Calibration Angle -5 to 5 ° 0.05 F002 0
797D PMU 1 Ia Calibration Angle -5 to 5 ° 0.05 F002 0
797E PMU 1 Ib Calibration Angle -5 to 5 ° 0.05 F002 0
797F PMU 1 Ic Calibration Angle -5 to 5 ° 0.05 F002 0
7980 PMU 1 Ig Calibration Angle -5 to 5 ° 0.05 F002 0
7981 PMU 1 Sequence Voltage Shift Angle -180 to 180 ° 30 F002 0
7982 PMU 1 Sequence Current Shift Angle -180 to 180 ° 30 F002 0
Phasor Measurement Unit Triggering (Read/Write Setting)
79A1 PMU 1 User Trigger 0 to 65535 --- 1 F300 0
Phasor Measurement Unit Current Trigger (Read/Write Setting)
79A5 PMU 1 Current Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
79A6 PMU 1 Current Trigger Pickup 0.1 to 30 pu 0.001 F001 1800
79A7 PMU 1 Current Trigger Pickup Time 0 to 600 s 0.01 F001 10
79A8 PMU 1 Current Trigger Dropout Time 0 to 600 s 0.01 F001 100
79A9 PMU 1 Current Trigger Block (3 items) 0 to 65535 --- 1 F300 0
79AC PMU 1 Current Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
79AD PMU 1 Current Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
79C9 PMU 1 df/dt Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
79CA PMU 1 df/dt Trigger Raise 0.1 to 15 Hz/s 0.01 F001 25
79CB PMU 1 df/dt Trigger Fall 0.1 to 15 Hz/s 0.01 F001 25
79CC PMU 1 df/dt Trigger Pickup Time 0 to 600 s 0.01 F001 10
79CD PMU 1 df/dt Trigger Dropout Time 0 to 600 s 0.01 F001 100
79CE PMU 1 df/dt Trigger Block (3 items) 0 to 65535 --- 1 F300 0
79D1 PMU 1 df/dt Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
79D2 PMU 1 df/dt Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
79D3 ...Repeated for PMU 2
79DD ...Repeated for PMU 3
79E7 ...Repeated for PMU 4
Field Current Protection Settings (Read/Write Setting)
7A60 Field Current Function 0 to 1 --- 1 F102 0 (Disabled)
7A61 Field Current Origin 0 to 48 --- 1 F151 0 (None)
7A62 Field Current OC Pickup 0.05 to 1 pu 0.01 F001 80
7A63 Field Current OC Delay 0 to 600 s 0.01 F001 100
7A64 Field Current UC Pickup 0.05 to 1 pu 0.01 F001 20
7A65 Field Current UC Delay 0 to 600 s 0.01 F001 100
7A66 Reserved --- --- --- F001 0
7A67 Field Current Target 0 to 2 --- 1 F109 0 (Self-reset)

GE Multilin G60 Generator Protection System B-37


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 31 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
7A68 Field Current Events 0 to 1 --- 1 F102 0 (Disabled)
Field Ground Protection Settings (Read/Write Setting)
7A6A Field Ground Function 0 to 1 --- 1 F102 0 (Disabled)
7A6B Field Ground Injection Frequency 0.1 to 3 Hz 0.01 F001 100
7A6C Field Ground Inj Connection Type 0 to 1 --- 1 F613 0 (Single Point)

B 7A6D
7A6E
Field Ground STG1 Pickup
Field Ground STG1 Delay
1 to 500
0.1 to 600
kohms
s
1
0.1
F001
F001
20
100
7A6F Field Ground STG2 Pickup 1 to 500 kohms 1 F001 5
7A70 Field Ground STG2 Delay 0.1 to 600 s 0.1 F001 30
7A71 Field Ground UC Pickup 0.05 to 100 mA 0.01 F001 100
7A72 Field Ground UC Delay 0.1 to 600 s 0.01 F001 100
7A73 Field Ground Block 0 to 65535 --- 1 F300 0
7A74 Field Ground Target 0 to 2 --- 1 F109 0 (Self-reset)
7A75 Field Ground Events 0 to 1 --- 1 F102 0 (Disabled)
User Programmable Pushbuttons (Read/Write Setting) (16 modules)
7B60 User Programmable Pushbutton 1 Function 0 to 2 --- 1 F109 2 (Disabled)
7B61 User Programmable Pushbutton 1 Top Line --- --- --- F202 (none)
7B6B User Programmable Pushbutton 1 On Text --- --- --- F202 (none)
7B75 User Programmable Pushbutton 1 Off Text --- --- --- F202 (none)
7B7F User Programmable Pushbutton 1 Drop-Out Time 0 to 60 s 0.05 F001 0
7B80 User Programmable Pushbutton 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7B81 User Programmable Pushbutton 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7B82 User Programmable Pushbutton 1 LED Operand 0 to 65535 --- 1 F300 0
7B83 User Programmable Pushbutton 1 Autoreset Delay 0 to 600 s 0.05 F001 0
7B84 User Programmable Pushbutton 1 Autoreset Function 0 to 1 --- 1 F102 0 (Disabled)
7B85 User Programmable Pushbutton 1 Local Lock 0 to 65535 --- 1 F300 0
7B86 User Programmable Pushbutton 1 Message Priority 0 to 2 --- 1 F220 0 (Disabled)
7B87 User Programmable Pushbutton 1 Remote Lock 0 to 65535 --- 1 F300 0
7B88 User Programmable Pushbutton 1 Reset 0 to 65535 --- 1 F300 0
7B89 User Programmable Pushbutton 1 Set 0 to 65535 --- 1 F300 0
7B8A User Programmable Pushbutton 1 Hold 0 to 10 s 0.1 F001 1
7B8B ...Repeated for User Programmable Pushbutton 2
7BB6 ...Repeated for User Programmable Pushbutton 3
7BE1 ...Repeated for User Programmable Pushbutton 4
7C0C ...Repeated for User Programmable Pushbutton 5
7C37 ...Repeated for User Programmable Pushbutton 6
7C62 ...Repeated for User Programmable Pushbutton 7
7C8D ...Repeated for User Programmable Pushbutton 8
7CB8 ...Repeated for User Programmable Pushbutton 9
7CE3 ...Repeated for User Programmable Pushbutton 10
7D0E ...Repeated for User Programmable Pushbutton 11
7D39 ...Repeated for User Programmable Pushbutton 12
7D64 ...Repeated for User Programmable Pushbutton 13
7D8F ...Repeated for User Programmable Pushbutton 14
7DBA ...Repeated for User Programmable Pushbutton 15
7DE5 ...Repeated for User Programmable Pushbutton 16
Underfrequency (Read/Write Setting) (6 modules)
7E10 Underfrequency Function 0 to 1 --- 1 F102 0 (Disabled)
7E11 Underfrequency 1 Block 0 to 65535 --- 1 F300 0
7E12 Underfrequency 1 Minimum Current 0.1 to 1.25 pu 0.01 F001 10
7E13 Underfrequency 1 Pickup 20 to 65 Hz 0.01 F001 5950
7E14 Underfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 2000
7E15 Underfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 2000
7E16 Underfrequency 1 Source 0 to 5 --- 1 F167 0 (SRC 1)

B-38 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 32 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
7E17 Underfrequency 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7E18 Underfrequency 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7E19 Reserved (8 items) 0 to 1 --- 1 F001 0
7E21 ...Repeated for Underfrequency 2
7E32 ...Repeated for Underfrequency 3
7E43 ...Repeated for Underfrequency 4 B
7E54 ...Repeated for Underfrequency 5
7E65 ...Repeated for Underfrequency 6
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00 Neutral Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F01 Neutral Overvoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F02 Neutral Overvoltage 1 Pickup 0 to 3.00 pu 0.001 F001 300
7F03 Neutral Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 100
7F04 Neutral Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7F05 Neutral Overvoltage 1 Block 0 to 65535 --- 1 F300 0
7F06 Neutral Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7F07 Neutral Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7F08 Neutral Overvoltage 1 Curves 0 to 3 --- 1 F116 0 (Definite Time)
7F09 Reserved (8 items) 0 to 65535 --- 1 F001 0
7F10 ...Repeated for Neutral Overvoltage 2
7F20 ...Repeated for Neutral Overvoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7F30 Auxiliary Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F31 Auxiliary Overvoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F32 Auxiliary Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 300
7F33 Auxiliary Overvoltage 1 Pickup Delay 0 to 600 s 0.01 F001 100
7F34 Auxiliary Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7F35 Auxiliary Overvoltage 1 Block 0 to 65535 --- 1 F300 0
7F36 Auxiliary Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7F37 Auxiliary Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7F38 Reserved (8 items) 0 to 65535 --- 1 F001 0
7F40 ...Repeated for Auxiliary Overvoltage 2
7F50 ...Repeated for Auxiliary Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 modules)
7F60 Auxiliary Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7F61 Auxiliary Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7F62 Auxiliary Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 700
7F63 Auxiliary Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7F64 Auxiliary Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)
7F65 Auxiliary Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
7F66 Auxiliary Undervoltage 1 Block 0 to 65535 --- 1 F300 0
7F67 Auxiliary Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7F68 Auxiliary Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7F69 Reserved (7 items) 0 to 65535 --- 1 F001 0
7F70 ...Repeated for Auxiliary Undervoltage 2
7F80 ...Repeated for Auxiliary Undervoltage 3
Frequency (Read Only)
8000 Tracking Frequency --- Hz --- F001 0
EGD Fast Production Status (Read Only)
83E0 EGD Fast Producer Exchange 1 Signature 0 to 65535 --- 1 F001 0
83E1 EGD Fast Producer Exchange 1 Configuration Time 0 to 4294967295 --- --- F003 0
83E3 EGD Fast Producer Exchange 1 Size 0 to 65535 --- 1 F001 0
EGD Slow Production Status (Read Only) (2 modules)
83F0 EGD Slow Producer Exchange 1 Signature 0 to 65535 --- 1 F001 0

GE Multilin G60 Generator Protection System B-39


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 33 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
83F1 EGD Slow Producer Exchange 1 Configuration Time 0 to 4294967295 --- --- F003 0
83F3 EGD Slow Producer Exchange 1 Size 0 to 65535 --- 1 F001 0
83F4 ...Repeated for module number 2
EGD Fast Production (Read/Write Setting)
8400 EGD Fast Producer Exchange 1 Function 0 to 1 --- 1 F102 0 (Disabled)

B 8401
8403
EGD Fast Producer Exchange 1 Destination
EGD Fast Producer Exchange 1 Data Rate
0 to 4294967295
50 to 1000
---
ms
1
50
F003
F001
0
1000
8404 EGD Fast Producer Exchange 1 Data Item 1 (20 items) 0 to 65535 --- 1 F001 0
8418 Reserved (80 items) --- --- --- F001 0
EGD Slow Production (Read/Write Setting) (2 modules)
8500 EGD Slow Producer Exchange 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8501 EGD Fast Producer Exchange 1 Destination 0 to 4294967295 --- 1 F003 0
8503 EGD Slow Producer Exchange 1 Data Rate 500 to 1000 ms 50 F001 1000
8504 EGD Slow Producer Exchange 1 Data Item 1 (50 items) 0 to 65535 --- 1 F001 0
8536 Reserved (50 items) --- --- --- F001 0
8568 ...Repeated for EGD Exchange 2
Remote RTD inputs (Read/Write Grouped Setting) (12 modules)
86D0 Remote RTD 1 Function 0 to 1 --- 1 F102 0 (Disabled)
86D1 Remote RTD 1 ID --- --- --- F205 "RRTD 1"
86D7 Remote RTD 1 Type 0 to 3 --- 1 F174 0 (100 ohm Platinum)
86D8 Remote RTD 1 Application 0 to 5 --- 1 F550 0 (None)
86D9 Remote RTD 1 Alarm Temperature 1 to 200 °C 1 F001 130
86DA Remote RTD 1 Alarm Pickup Delay 5 to 600 seconds 5 F001 5
86DB Remote RTD 1 Trip Temperature 1 to 200 °C 1 F001 130
86DC Remote RTD 1 Trip Pickup Delay 5 to 600 seconds 5 F001 5
86DD Remote RTD 1 Trip Reset Delay 5 to 600 seconds 5 F001 5
86DE Remote RTD 1 Trip Voting 0 to 13 --- 1 F603 0 (None)
86DF Remote RTD 1 Block 0 to 65535 --- 1 F300 0
86E0 Remote RTD 1 Open 0 to 2 --- 1 F552 0 (None)
86E1 Remote RTD 1 Target 0 to 2 --- 1 F109 0 (Self-Reset)
86E2 Remote RTD 1 Events 0 to 1 --- 1 F102 0 (Disabled)
86E3 Repeatead for remote RTD input 2
86F6 Repeatead for remote RTD input 3
8709 Repeatead for remote RTD input 4
871C Repeatead for remote RTD input 5
872F Repeatead for remote RTD input 6
8742 Repeatead for remote RTD input 7
8755 Repeatead for remote RTD input 8
8768 Repeatead for remote RTD input 9
877B Repeatead for remote RTD input 10
878E Repeatead for remote RTD input 11
87A1 Repeatead for remote RTD input 12
Remote RTD inputs (Read Only Actual Values)
87C0 Remote RTD 1 Value 0 to 200 °C 1 F002 0
87C1 Remote RTD 2 Value 0 to 200 °C 1 F002 0
87C2 Remote RTD 3 Value 0 to 200 °C 1 F002 0
87C3 Remote RTD 4 Value 0 to 200 °C 1 F002 0
87C4 Remote RTD 5 Value 0 to 200 °C 1 F002 0
87C5 Remote RTD 6 Value 0 to 200 °C 1 F002 0
87C6 Remote RTD 7 Value 0 to 200 °C 1 F002 0
87C7 Remote RTD 8 Value 0 to 200 °C 1 F002 0
87C8 Remote RTD 9 Value 0 to 200 °C 1 F002 0
87C9 Remote RTD 10 Value 0 to 200 °C 1 F002 0
87CA Remote RTD 11 Value 0 to 200 °C 1 F002 0

B-40 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 34 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
87CB Remote RTD 12 Value 0 to 200 °C 1 F002 0
FlexState Settings (Read/Write Setting)
8800 FlexState Parameters (256 items) --- --- --- F300 0
Digital Elements (Read/Write Setting) (48 modules)
8A00 Digital Element 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8A01 Digital Element 1 Name --- --- --- F203 “Dig Element 1“ B
8A09 Digital Element 1 Input 0 to 65535 --- 1 F300 0
8A0A Digital Element 1 Pickup Delay 0 to 999999.999 s 0.001 F003 0
8A0C Digital Element 1 Reset Delay 0 to 999999.999 s 0.001 F003 0
8A0E Digital Element 1 Block 0 to 65535 --- 1 F300 0
8A0F Digital Element 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
8A10 Digital Element 1 Events 0 to 1 --- 1 F102 0 (Disabled)
8A11 Digital Element 1 Pickup LED 0 to 1 --- 1 F102 1 (Enabled)
8A12 Reserved (2 items) --- --- --- F001 0
8A14 ...Repeated for Digital Element 2
8A28 ...Repeated for Digital Element 3
8A3C ...Repeated for Digital Element 4
8A50 ...Repeated for Digital Element 5
8A64 ...Repeated for Digital Element 6
8A78 ...Repeated for Digital Element 7
8A8C ...Repeated for Digital Element 8
8AA0 ...Repeated for Digital Element 9
8AB4 ...Repeated for Digital Element 10
8AC8 ...Repeated for Digital Element 11
8ADC ...Repeated for Digital Element 12
8AF0 ...Repeated for Digital Element 13
8B04 ...Repeated for Digital Element 14
8B18 ...Repeated for Digital Element 15
8B2C ...Repeated for Digital Element 16
8B40 ...Repeated for Digital Element 17
8B54 ...Repeated for Digital Element 18
8B68 ...Repeated for Digital Element 19
8B7C ...Repeated for Digital Element 20
8B90 ...Repeated for Digital Element 21
8BA4 ...Repeated for Digital Element 22
8BB8 ...Repeated for Digital Element 23
8BCC ...Repeated for Digital Element 24
8BE0 ...Repeated for Digital Element 25
8BF4 ...Repeated for Digital Element 26
8C08 ...Repeated for Digital Element 27
8C1C ...Repeated for Digital Element 28
8C30 ...Repeated for Digital Element 29
8C44 ...Repeated for Digital Element 30
8C58 ...Repeated for Digital Element 31
8C6C ...Repeated for Digital Element 32
8C80 ...Repeated for Digital Element 33
8C94 ...Repeated for Digital Element 34
8CA8 ...Repeated for Digital Element 35
8CBC ...Repeated for Digital Element 36
8CD0 ...Repeated for Digital Element 37
8CE4 ...Repeated for Digital Element 38
8CF8 ...Repeated for Digital Element 39
8D0C ...Repeated for Digital Element 40
8D20 ...Repeated for Digital Element 41

GE Multilin G60 Generator Protection System B-41


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 35 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
8D34 ...Repeated for Digital Element 42
8D48 ...Repeated for Digital Element 43
8D5C ...Repeated for Digital Element 44
8D70 ...Repeated for Digital Element 45
8D84 ...Repeated for Digital Element 46

B 8D98
8DAC
...Repeated for Digital Element 47
...Repeated for Digital Element 48
Trip Bus (Read/Write Setting)
8E00 Trip Bus 1 Function 0 to 1 --- 1 F102 0 (Disabled)
8E01 Trip Bus 1 Block --- --- --- F300 0
8E02 Trip Bus 1 Pickup Delay 0 to 600 s 0.01 F001 0
8E03 Trip Bus 1 Reset Delay 0 to 600 s 0.01 F001 0
8E04 Trip Bus 1 Input 1 0 to 65535 --- 1 F300 0
8E05 Trip Bus 1 Input 2 0 to 65535 --- 1 F300 0
8E06 Trip Bus 1 Input 3 0 to 65535 --- 1 F300 0
8E07 Trip Bus 1 Input 4 0 to 65535 --- 1 F300 0
8E08 Trip Bus 1 Input 5 0 to 65535 --- 1 F300 0
8E09 Trip Bus 1 Input 6 0 to 65535 --- 1 F300 0
8E0A Trip Bus 1 Input 7 0 to 65535 --- 1 F300 0
8E0B Trip Bus 1 Input 8 0 to 65535 --- 1 F300 0
8E0C Trip Bus 1 Input 9 0 to 65535 --- 1 F300 0
8E0D Trip Bus 1 Input 10 0 to 65535 --- 1 F300 0
8E0E Trip Bus 1 Input 11 0 to 65535 --- 1 F300 0
8E0F Trip Bus 1 Input 12 0 to 65535 --- 1 F300 0
8E10 Trip Bus 1 Input 13 0 to 65535 --- 1 F300 0
8E11 Trip Bus 1 Input 14 0 to 65535 --- 1 F300 0
8E12 Trip Bus 1 Input 15 0 to 65535 --- 1 F300 0
8E13 Trip Bus 1 Input 16 0 to 65535 --- 1 F300 0
8E14 Trip Bus 1 Latching 0 to 1 --- 1 F102 0 (Disabled)
8E15 Trip Bus 1 Reset 0 to 65535 --- 1 F300 0
8E16 Trip Bus 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
8E16 Trip Bus 1 Events 0 to 1 --- 1 F102 0 (Disabled)
8E18 Reserved (8 items) --- --- --- F001 0
8E20 ...Repeated for Trip Bus 2
8E40 ...Repeated for Trip Bus 3
8E60 ...Repeated for Trip Bus 4
8E80 ...Repeated for Trip Bus 5
8EA0 ...Repeated for Trip Bus 6
FlexElement (Read/Write Setting) (16 modules)
9000 FlexElement™ 1 Function 0 to 1 --- 1 F102 0 (Disabled)
9001 FlexElement™ 1 Name --- --- --- F206 “FxE 1”
9004 FlexElement™ 1 InputP 0 to 65535 --- 1 F600 0
9005 FlexElement™ 1 InputM 0 to 65535 --- 1 F600 0
9006 FlexElement™ 1 Compare 0 to 1 --- 1 F516 0 (LEVEL)
9007 FlexElement™ 1 Input 0 to 1 --- 1 F515 0 (SIGNED)
9008 FlexElement™ 1 Direction 0 to 1 --- 1 F517 0 (OVER)
9009 FlexElement™ 1 Hysteresis 0.1 to 50 % 0.1 F001 30
900A FlexElement™ 1 Pickup -90 to 90 pu 0.001 F004 1000
900C FlexElement™ 1 DeltaT Units 0 to 2 --- 1 F518 0 (Milliseconds)
900D FlexElement™ 1 DeltaT 20 to 86400 --- 1 F003 20
900F FlexElement™ 1 Pickup Delay 0 to 65.535 s 0.001 F001 0
9010 FlexElement™ 1 Reset Delay 0 to 65.535 s 0.001 F001 0
9011 FlexElement™ 1 Block 0 to 65535 --- 1 F300 0
9012 FlexElement™ 1 Target 0 to 2 --- 1 F109 0 (Self-reset)

B-42 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 36 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
9013 FlexElement™ 1 Events 0 to 1 --- 1 F102 0 (Disabled)
9014 ...Repeated for FlexElement™ 2
9028 ...Repeated for FlexElement™ 3
903C ...Repeated for FlexElement™ 4
9050 ...Repeated for FlexElement™ 5
9064 ...Repeated for FlexElement™ 6 B
9078 ...Repeated for FlexElement™ 7
908C ...Repeated for FlexElement™ 8
90A0 ...Repeated for FlexElement™ 9
90B4 ...Repeated for FlexElement™ 10
90C8 ...Repeated for FlexElement™ 11
90DC ...Repeated for FlexElement™ 12
90F0 ...Repeated for FlexElement™ 13
9104 ...Repeated for FlexElement™ 14
9118 ...Repeated for FlexElement™ 15
912C ...Repeated for FlexElement™ 16
dcmA Outputs (Read/Write Setting) (24 modules)
9300 dcmA Output 1 Source 0 to 65535 --- 1 F600 0
9301 dcmA Output 1 Range 0 to 2 --- 1 F522 0 (–1 to 1 mA)
9302 dcmA Output 1 Minimum –90 to 90 pu 0.001 F004 0
9304 dcmA Output 1 Maximum –90 to 90 pu 0.001 F004 1000
9306 ...Repeated for dcmA Output 2
930C ...Repeated for dcmA Output 3
9312 ...Repeated for dcmA Output 4
9318 ...Repeated for dcmA Output 5
931E ...Repeated for dcmA Output 6
9324 ...Repeated for dcmA Output 7
932A ...Repeated for dcmA Output 8
9330 ...Repeated for dcmA Output 9
9336 ...Repeated for dcmA Output 10
933C ...Repeated for dcmA Output 11
9342 ...Repeated for dcmA Output 12
9348 ...Repeated for dcmA Output 13
934E ...Repeated for dcmA Output 14
9354 ...Repeated for dcmA Output 15
935A ...Repeated for dcmA Output 16
9360 ...Repeated for dcmA Output 17
9366 ...Repeated for dcmA Output 18
936C ...Repeated for dcmA Output 19
9372 ...Repeated for dcmA Output 20
9378 ...Repeated for dcmA Output 21
937E ...Repeated for dcmA Output 22
9384 ...Repeated for dcmA Output 23
938A ...Repeated for dcmA Output 24
Direct Input/Output Names (Read/Write Setting) (96 modules)
9400 Direct Input 1 Name 0 to 96 --- 1 F205 “Dir Ip 1”
9406 Direct Output 1 Name 1 to 96 --- 1 F205 “Dir Out 1”
940C ...Repeated for Direct Input/Output 2
9418 ...Repeated for Direct Input/Output 3
9424 ...Repeated for Direct Input/Output 4
9430 ...Repeated for Direct Input/Output 5
943C ...Repeated for Direct Input/Output 6
9448 ...Repeated for Direct Input/Output 7
9454 ...Repeated for Direct Input/Output 8

GE Multilin G60 Generator Protection System B-43


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 37 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
9460 ...Repeated for Direct Input/Output 9
946C ...Repeated for Direct Input/Output 10
9478 ...Repeated for Direct Input/Output 11
9484 ...Repeated for Direct Input/Output 12
9490 ...Repeated for Direct Input/Output 13

B 949C
94A8
...Repeated for Direct Input/Output 14
...Repeated for Direct Input/Output 15
94B4 ...Repeated for Direct Input/Output 16
94C0 ...Repeated for Direct Input/Output 17
94CC ...Repeated for Direct Input/Output 18
94D8 ...Repeated for Direct Input/Output 19
94E4 ...Repeated for Direct Input/Output 20
94F0 ...Repeated for Direct Input/Output 21
94FC ...Repeated for Direct Input/Output 22
9508 ...Repeated for Direct Input/Output 23
9514 ...Repeated for Direct Input/Output 24
9520 ...Repeated for Direct Input/Output 25
952C ...Repeated for Direct Input/Output 26
9538 ...Repeated for Direct Input/Output 27
9544 ...Repeated for Direct Input/Output 28
9550 ...Repeated for Direct Input/Output 29
955C ...Repeated for Direct Input/Output 30
9568 ...Repeated for Direct Input/Output 31
9574 ...Repeated for Direct Input/Output 32
IEC 61850 received integers (read/write setting registers)
9910 IEC61850 GOOSE UInteger 1 default value 0 to 429496295 --- 1 F003 1000
9912 IEC61850 GOOSE UInteger input 1 mode 0 to 1 --- 1 F491 0 (Default Value)
9913 ...Repeated for IEC61850 GOOSE UInteger 2
9916 ...Repeated for IEC61850 GOOSE UInteger 3
9919 ...Repeated for IEC61850 GOOSE UInteger 4
991C ...Repeated for IEC61850 GOOSE UInteger 5
991F ...Repeated for IEC61850 GOOSE UInteger 6
9922 ...Repeated for IEC61850 GOOSE UInteger 7
9925 ...Repeated for IEC61850 GOOSE UInteger 8
9928 ...Repeated for IEC61850 GOOSE UInteger 9
992B ...Repeated for IEC61850 GOOSE UInteger 10
992E ...Repeated for IEC61850 GOOSE UInteger 11
9931 ...Repeated for IEC61850 GOOSE UInteger 12
9934 ...Repeated for IEC61850 GOOSE UInteger 13
9937 ...Repeated for IEC61850 GOOSE UInteger 14
993A ...Repeated for IEC61850 GOOSE UInteger 15
993D ...Repeated for IEC61850 GOOSE UInteger 16
FlexElement Actuals (Read Only) (16 modules)
9A01 FlexElement™ 1 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A03 FlexElement™ 2 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A05 FlexElement™ 3 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A07 FlexElement™ 4 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A09 FlexElement™ 5 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A0B FlexElement™ 6 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A0D FlexElement™ 7 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A0F FlexElement™ 8 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A11 FlexElement™ 9 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A13 FlexElement™ 10 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A15 FlexElement™ 11 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0

B-44 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 38 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
9A17 FlexElement™ 12 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A19 FlexElement™ 13 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A1B FlexElement™ 14 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A1D FlexElement™ 15 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
9A1F FlexElement™ 16 Actual -2147483.647 to 2147483.647 --- 0.001 F004 0
Teleprotection Inputs/Outputs (Read/Write Settings) B
9B00 Teleprotection Function 0 to 1 --- 1 F102 0 (Disabled)
9B01 Teleprotection Number of Terminals 2 to 3 --- 1 F001 2
9B02 Teleprotection Number of Channels 1 to 2 --- 1 F001 1
9B03 Teleprotection Local Relay ID 0 to 255 --- 1 F001 0
9B04 Teleprotection Terminal 1 ID 0 to 255 --- 1 F001 0
9B05 Teleprotection Terminal 2 ID 0 to 255 --- 1 F001 0
9B06 Reserved (10 items) 0 to 1 --- --- F001 0
9B10 Teleprotection Input 1-n Default States (16 items) 0 to 3 --- 1 F086 0 (Off)
9B30 Teleprotection Input 2-n Default States (16 items) 0 to 3 --- 1 F086 0 (Off)
9B50 Teleprotection Output 1-n Operand (16 items) 0 to 65535 --- 1 F300 0
9B70 Teleprotection Output 2-n Operand (16 items) 0 to 65535 --- 1 F300 0
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9B90 Teleprotection Clear Lost Packets 0 to 1 --- 1 F126 0 (No)
Teleprotection Channel Tests (Read Only)
9B91 Teleprotection Channel 1 Status 0 to 2 --- 1 F134 1 (OK)
9B92 Teleprotection Channel 1 Number of Lost Packets 0 to 65535 --- 1 F001 0
9B93 Teleprotection Channel 2 Status 0 to 2 --- 1 F134 1 (OK)
9B94 Teleprotection Channel 2 Number of Lost Packets 0 to 65535 --- 1 F001 0
9B95 Teleprotection Network Status 0 to 2 --- 1 F134 2 (n/a)
9BA0 Teleprotection Channel 1 Input States 0 to 1 --- 1 F500 0
9BA1 Teleprotection Channel 2 Input States 0 to 1 --- 1 F500 0
9BB0 Teleprotection Input 1 States, 1 per register (16 items) 0 to 1 --- 1 F108 0 (Off)
9BC0 Teleprotection Input 2 States, 1 per register (16 items) 0 to 1 --- 1 F108 0 (Off)
VT Fuse Failure (Read/Write Setting) (6 modules)
A040 VT Fuse Failure Function 0 to 1 --- 1 F102 0 (Disabled)
A041 ...Repeated for module number 2
A042 ...Repeated for module number 3
A043 ...Repeated for module number 4
A044 ...Repeated for module number 5
A045 ...Repeated for module number 6
Selector switch actual values (read only)
A210 Selector switch 1 position 1 to 7 --- 1 F001 0
A211 Selector switch 2 position 1 to 7 --- 1 F001 1
Selector switch settings (read/write, 2 modules)
A280 Selector 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A281 Selector 1 Range 1 to 7 --- 1 F001 7
A282 Selector 1 Timeout 3 to 60 s 0.1 F001 50
A283 Selector 1 Step Up 0 to 65535 --- 1 F300 0
A284 Selector 1 Step Mode 0 to 1 --- 1 F083 0 (Time-out)
A285 Selector 1 Acknowledge 0 to 65535 --- 1 F300 0
A286 Selector 1 Bit0 0 to 65535 --- 1 F300 0
A287 Selector 1 Bit1 0 to 65535 --- 1 F300 0
A288 Selector 1 Bit2 0 to 65535 --- 1 F300 0
A289 Selector 1 Bit Mode 0 to 1 --- 1 F083 0 (Time-out)
A28A Selector 1 Bit Acknowledge 0 to 65535 --- 1 F300 0
A28B Selector 1 Power Up Mode 0 to 2 --- 1 F084 0 (Restore)
A28C Selector 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A28D Selector 1 Events 0 to 1 --- 1 F102 0 (Disabled)

GE Multilin G60 Generator Protection System B-45


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 39 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
A28E Reserved (10 items) --- --- 1 F001 0
A298 ...Repeated for Selector 2
DNP/IEC Points (Read/Write Setting)
A300 DNP/IEC 60870-5-104 Binary Input Points (256 items) 0 to 65535 --- 1 F300 0
A400 DNP/IEC 60870-5-104 Analog Input Points (256 items) 0 to 65535 --- 1 F300 0

B Volts Per Hertz (Read/Write Grouped Setting) (2 modules)


A580 Volts Per Hertz 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A581 Volts Per Hertz 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
A582 Volts Per Hertz 1 Pickup 0.8 to 4 pu 0.01 F001 80
A583 Volts Per Hertz 1 Curves 0 to 7 --- 1 F240 0 (Definite Time)
A584 Volts Per Hertz 1 TD Multiplier 0.05 to 600 --- 0.01 F001 100
A585 Volts Per Hertz 1 Block 0 to 65535 --- 1 F300 0
A586 Volts Per Hertz 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A587 Volts Per Hertz 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A588 Volts Per Hertz 1 T Reset 0 to 1000 s 0.1 F001 10
A589 Volts Per Hertz 1 Voltage Mode 0 to 1 --- 1 F186 0 (Phase-to-Ground)
A58A ...Repeated for Volts Per Hertz 2
Volts Per Hertz Actuals (Read Only) (2 modules)
A5A0 Volts Per Hertz 1 0 to 65.535 pu 0.001 F001 0
A5A1 Volts Per Hertz 2 0 to 65.535 pu 0.001 F001 0
Flexcurves C and D (Read/Write Setting)
A600 FlexCurve C (120 items) 0 to 65535 ms 1 F011 0
A680 FlexCurve D (120 items) 0 to 65535 ms 1 F011 0
Non Volatile Latches (Read/Write Setting) (16 modules)
A700 Non-Volatile Latch 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A701 Non-Volatile Latch 1 Type 0 to 1 --- 1 F519 0 (Reset Dominant)
A702 Non-Volatile Latch 1 Set 0 to 65535 --- 1 F300 0
A703 Non-Volatile Latch 1 Reset 0 to 65535 --- 1 F300 0
A704 Non-Volatile Latch 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A705 Non-Volatile Latch 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A706 Reserved (4 items) --- --- --- F001 0
A70A ...Repeated for Non-Volatile Latch 2
A714 ...Repeated for Non-Volatile Latch 3
A71E ...Repeated for Non-Volatile Latch 4
A728 ...Repeated for Non-Volatile Latch 5
A732 ...Repeated for Non-Volatile Latch 6
A73C ...Repeated for Non-Volatile Latch 7
A746 ...Repeated for Non-Volatile Latch 8
A750 ...Repeated for Non-Volatile Latch 9
A75A ...Repeated for Non-Volatile Latch 10
A764 ...Repeated for Non-Volatile Latch 11
A76E ...Repeated for Non-Volatile Latch 12
A778 ...Repeated for Non-Volatile Latch 13
A782 ...Repeated for Non-Volatile Latch 14
A78C ...Repeated for Non-Volatile Latch 15
A796 ...Repeated for Non-Volatile Latch 16
Digital Counter (Read/Write Setting) (8 modules)
A800 Digital Counter 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A801 Digital Counter 1 Name --- --- --- F205 “Counter 1"
A807 Digital Counter 1 Units --- --- --- F206 (none)
A80A Digital Counter 1 Block 0 to 65535 --- 1 F300 0
A80B Digital Counter 1 Up 0 to 65535 --- 1 F300 0
A80C Digital Counter 1 Down 0 to 65535 --- 1 F300 0

B-46 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 40 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
A80D Digital Counter 1 Preset –2147483647 to --- 1 F004 0
2147483647
A80F Digital Counter 1 Compare –2147483647 to --- 1 F004 0
2147483647
A811 Digital Counter 1 Reset 0 to 65535 --- 1 F300 0
A812 Digital Counter 1 Freeze/Reset 0 to 65535 --- 1 F300 0
A813 Digital Counter 1 Freeze/Count 0 to 65535 --- 1 F300 0 B
A814 Digital Counter 1 Set To Preset 0 to 65535 --- 1 F300 0
A815 Reserved (11 items) --- --- --- F001 0
A820 ...Repeated for Digital Counter 2
A840 ...Repeated for Digital Counter 3
A860 ...Repeated for Digital Counter 4
A880 ...Repeated for Digital Counter 5
A8A0 ...Repeated for Digital Counter 6
A8C0 ...Repeated for Digital Counter 7
A8E0 ...Repeated for Digital Counter 8
Frequency Rate of Change (Read/Write Setting) (4 modules)
A900 Frequency Rate of Change 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A901 Frequency Rate of Change 1 OC Supervision 0 to 30 pu 0.001 F001 200
A902 Frequency Rate of Change 1 Min 20 to 80 Hz 0.01 F001 4500
A903 Frequency Rate of Change 1 Max 20 to 80 Hz 0.01 F001 6500
A904 Frequency Rate of Change 1 Pickup Delay 0 to 65.535 s 0.001 F001 0
A905 Frequency Rate of Change 1 Reset Delay 0 to 65.535 s 0.001 F001 0
A906 Frequency Rate of Change 1 Block 0 to 65535 --- 1 F300 0
A907 Frequency Rate of Change 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A908 Frequency Rate of Change 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A909 Frequency Rate of Change 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
A90A Frequency Rate of Change 1 Trend 0 to 2 --- 1 F224 0 (Increasing)
A90B Frequency Rate of Change 1 Pickup 0.1 to 15 Hz/s 0.01 F001 50
A90C Frequency Rate of Change 1 OV Supervision 0.1 to 3 pu 0.001 F001 700
A90D Frequency Rate of Change 1 Reserved (3 items) 0 to 1 --- 1 F001 0
A910 ...Repeated for Frequency Rate of Change 2
A920 ...Repeated for Frequency Rate of Change 3
A930 ...Repeated for Frequency Rate of Change 4
Restricted Ground Fault (Read/Write Grouped Setting) (6 modules)
A960 Restricted Ground Fault 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A961 Restricted Ground Fault 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
A962 Restricted Ground Fault 1 Pickup 0.005 to 30 pu 0.001 F001 80
A963 Restricted Ground Fault 1 Slope 0 to 100 % 1 F001 40
A964 Restricted Ground Fault 1 Delay 0 to 600 s 0.01 F001 0
A965 Restricted Ground Fault 1 Reset Delay 0 to 600 s 0.01 F001 0
A966 Restricted Ground Fault 1 Block --- --- --- F001 0
A967 Restricted Ground Fault 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A968 Restricted Ground Fault 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A969 ...Repeated for Restricted Ground Fault 2
A972 ...Repeated for Restricted Ground Fault 3
A97B ...Repeated for Restricted Ground Fault 4
A984 ...Repeated for Restricted Ground Fault 5
A98D ...Repeated for Restricted Ground Fault 6
IEC 61850 received analog settings (read/write)
AA00 IEC 61850 GOOSE analog 1 default value –1000000 to 1000000 --- 0.001 F060 1000
AA02 IEC 61850 GOOSE analog input 1 mode 0 to 1 --- 1 F491 0 (Default Value)
AA03 IEC 61850 GOOSE analog input 1 units --- --- --- F207 (none)
AA05 IEC 61850 GOOSE analog input 1 per-unit base 0 to 999999999.999 --- 0.001 F060 1
AA07 ...Repeated for IEC 61850 GOOSE analog input 2

GE Multilin G60 Generator Protection System B-47


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 41 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
AA0E ...Repeated for IEC 61850 GOOSE analog input 3
AA15 ...Repeated for IEC 61850 GOOSE analog input 4
AA1C ...Repeated for IEC 61850 GOOSE analog input 5
AA23 ...Repeated for IEC 61850 GOOSE analog input 6
AA2A ...Repeated for IEC 61850 GOOSE analog input 7

B AA31
AA38
...Repeated for IEC 61850 GOOSE analog input 8
...Repeated for IEC 61850 GOOSE analog input 9
AA3F ...Repeated for IEC 61850 GOOSE analog input 10
AA46 ...Repeated for IEC 61850 GOOSE analog input 11
AA4D ...Repeated for IEC 61850 GOOSE analog input 12
AA54 ...Repeated for IEC 61850 GOOSE analog input 13
AA5B ...Repeated for IEC 61850 GOOSE analog input 14
AA62 ...Repeated for IEC 61850 GOOSE analog input 15
AA69 ...Repeated for IEC 61850 GOOSE analog input 16
IEC 61850 XCBR configuration (read/write settings)
AB24 Operand for IEC 61850 XCBR1.ST.Loc status 0 to 65535 --- 1 F300 0
AB25 Command to clear XCBR1 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB26 Operand for IEC 61850 XCBR2.ST.Loc status 0 to 65535 --- 1 F300 0
AB27 Command to clear XCBR2 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB28 Operand for IEC 61850 XCBR3.ST.Loc status 0 to 65535 --- 1 F300 0
AB29 Command to clear XCBR3 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB2A Operand for IEC 61850 XCBR4.ST.Loc status 0 to 65535 --- 1 F300 0
AB2B Command to clear XCBR4 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB2C Operand for IEC 61850 XCBR5.ST.Loc status 0 to 65535 --- 1 F300 0
AB2D Command to clear XCBR5 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB2E Operand for IEC 61850 XCBR6.ST.Loc status 0 to 65535 --- 1 F300 0
AB2F Command to clear XCBR6 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
IEC 61850 LN name prefixes (read/write settings)
AB30 IEC 61850 logical node LPHD1 name prefix 0 to 65534 --- 1 F206 (none)
AB33 IEC 61850 logical node PIOCx name prefix (72 items) 0 to 65534 --- 1 F206 (none)
AC0B IEC 61850 logical node PTOCx name prefix (24 items) 0 to 65534 --- 1 F206 (none)
AC53 IEC 61850 logical node PTUVx name prefix (13 items) 0 to 65534 --- 1 F206 (none)
AC7A IEC 61850 logical node PTOVx name prefix (10 items) 0 to 65534 --- 1 F206 (none)
AC98 IEC 61850 logical node PDISx name prefix (10 items) 0 to 65534 --- 1 F206 (none)
ACB6 IEC 61850 logical node RBRFx name prefix (24 items) 0 to 65534 --- 1 F206 (none)
ACFE IEC 61850 logical node RPSBx name prefix 0 to 65534 --- 1 F206 (none)
AD01 IEC 61850 logical node RRECx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD13 IEC 61850 logical node MMXUx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD25 IEC 61850 logical node GGIOx name prefix (5 items) 0 to 65534 --- 1 F206 (none)
AD34 IEC 61850 logical node RFLOx name prefix (5 items) 0 to 65534 --- 1 F206 (none)
AD43 IEC 61850 logical node XCBRx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD55 IEC 61850 logical node PTRCx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD67 IEC 61850 logical node PDIFx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD73 IEC 61850 logical node MMXNx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
ADE2 IEC 61850 logical node CSWIx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AE3C IEC 61850 logical node XSWIx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
IEC 61850 XSWI configuration (read/write settings)
AECF Operand for IEC 61850 XSWI1.ST.Loc status 0 to 65535 --- 1 F300 0
AED0 Command to clear XSWI1 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AED1 Repeated for IEC 61850 XSWI2
AED3 Repeated for IEC 61850 XSWI3
AED5 Repeated for IEC 61850 XSWI4
AED7 Repeated for IEC 61850 XSWI5
AED9 Repeated for IEC 61850 XSWI6

B-48 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 42 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
AEDB Repeated for IEC 61850 XSWI7
AEDD Repeated for IEC 61850 XSWI8
AEDF Repeated for IEC 61850 XSWI9
AEE1 Repeated for IEC 61850 XSWI10
AEE3 Repeated for IEC 61850 XSWI11
AEE5 Repeated for IEC 61850 XSWI12 B
AEE7 Repeated for IEC 61850 XSWI13
AEE9 Repeated for IEC 61850 XSWI14
AEEB Repeated for IEC 61850 XSWI15
AEED Repeated for IEC 61850 XSWI16
AEEF Repeated for IEC 61850 XSWI17
AEF1 Repeated for IEC 61850 XSWI18
AEF3 Repeated for IEC 61850 XSWI19
AEF5 Repeated for IEC 61850 XSWI20
AEF7 Repeated for IEC 61850 XSWI21
AEF9 Repeated for IEC 61850 XSWI22
AEFB Repeated for IEC 61850 XSWI23
AEFD Repeated for IEC 61850 XSWI24
IEC 61850 GGIO4 general analog configuration settings (read/write)
AF00 Number of analog points in GGIO4 4 to 32 --- 4 F001 4
IEC 61850 GGIO4 analog input points configuration settings (read/write)
AF10 IEC 61850 GGIO4 analog input 1 value --- --- --- F600 0
AF11 IEC 61850 GGIO4 analog input 1 deadband 0.001 to 100 % 0.001 F003 100000
AF13 IEC 61850 GGIO4 analog input 1 minimum –1000000000000 to --- 0.001 F060 0
1000000000000
AF15 IEC 61850 GGIO4 analog input 1 maximum –1000000000000 to --- 0.001 F060 1000000
1000000000000
AF17 ...Repeated for IEC 61850 GGIO4 analog input 2
AF1E ...Repeated for IEC 61850 GGIO4 analog input 3
AF25 ...Repeated for IEC 61850 GGIO4 analog input 4
AF2C ...Repeated for IEC 61850 GGIO4 analog input 5
AF33 ...Repeated for IEC 61850 GGIO4 analog input 6
AF3A ...Repeated for IEC 61850 GGIO4 analog input 7
AF41 ...Repeated for IEC 61850 GGIO4 analog input 8
AF48 ...Repeated for IEC 61850 GGIO4 analog input 9
AF4F ...Repeated for IEC 61850 GGIO4 analog input 10
AF56 ...Repeated for IEC 61850 GGIO4 analog input 11
AF5D ...Repeated for IEC 61850 GGIO4 analog input 12
AF64 ...Repeated for IEC 61850 GGIO4 analog input 13
AF6B ...Repeated for IEC 61850 GGIO4 analog input 14
AF72 ...Repeated for IEC 61850 GGIO4 analog input 15
AF79 ...Repeated for IEC 61850 GGIO4 analog input 16
AF80 ...Repeated for IEC 61850 GGIO4 analog input 17
AF87 ...Repeated for IEC 61850 GGIO4 analog input 18
AF8E ...Repeated for IEC 61850 GGIO4 analog input 19
AF95 ...Repeated for IEC 61850 GGIO4 analog input 20
AF9C ...Repeated for IEC 61850 GGIO4 analog input 21
AFA3 ...Repeated for IEC 61850 GGIO4 analog input 22
AFAA ...Repeated for IEC 61850 GGIO4 analog input 23
AFB1 ...Repeated for IEC 61850 GGIO4 analog input 24
AFB8 ...Repeated for IEC 61850 GGIO4 analog input 25
AFBF ...Repeated for IEC 61850 GGIO4 analog input 26
AFC6 ...Repeated for IEC 61850 GGIO4 analog input 27
AFCD ...Repeated for IEC 61850 GGIO4 analog input 28
AFD4 ...Repeated for IEC 61850 GGIO4 analog input 29

GE Multilin G60 Generator Protection System B-49


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 43 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
AFDB ...Repeated for IEC 61850 GGIO4 analog input 30
AFE2 ...Repeated for IEC 61850 GGIO4 analog input 31
AFE9 ...Repeated for IEC 61850 GGIO4 analog input 32
IEC 61850 Logical Node Name Prefixes (Read/Write Setting)
AB30 IEC 61850 Logical Node LPHD1 Name Prefix 0 to 65534 --- 1 F206 (None)

B AB33
AC0B
IEC 61850 Logical Node PIOCx Name Prefix (72 items)
IEC 61850 Logical Node PTOCx Name Prefix (24 items)
0 to 65534
0 to 65534
---
---
1
1
F206
F206
(None)
(None)
AC53 IEC 61850 Logical Node PTUVx Name Prefix (12 items) 0 to 65534 --- 1 F206 (None)
AC77 IEC 61850 Logical Node PTOVx Name Prefix (8 items) 0 to 65534 --- 1 F206 (None)
AC8F IEC 61850 Logical Node PDISx Name Prefix (10 items) 0 to 65534 --- 1 F206 (None)
ACAD IEC 61850 Logical Node RRBFx Name Prefix (24 items) 0 to 65534 --- 1 F206 (None)
ACF5 IEC 61850 Logical Node RPSBx Name Prefix 0 to 65534 --- 1 F206 (None)
ACF8 IEC 61850 Logical Node RRECx Name Prefix (6 items) 0 to 65534 --- 1 F206 (None)
AD0A IEC 61850 Logical Node MMXUx Name Prefix (6 items) 0 to 65534 --- 1 F206 (None)
AD1C IEC 61850 Logical Node GGIOx Name Prefix (4 items) 0 to 65534 --- 1 F206 (None)
AD28 IEC 61850 Logical Node RFLOx Name Prefix (5 items) 0 to 65534 --- 1 F206 (None)
AD37 IEC 61850 Logical Node XCBRx Name Prefix (2 items) 0 to 65534 --- 1 F206 (None)
AD3D IEC 61850 Logical Node PTRCx Name Prefix (2 items) 0 to 65534 --- 1 F206 (None)
AD43 IEC 61850 Logical Node PDIFx Name Prefix (4 items) 0 to 65534 --- 1 F206 (None)
AD4F IEC 61850 Logical Node MMXNx Name Prefix (37 items) 0 to 65534 --- 1 F206 (None)
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
B01C Default GOOSE/GSSE Update Time 1 to 60 s 1 F001 60
B01D IEC 61850 GSSE Function (GsEna) 0 to 1 --- 1 F102 1 (Enabled)
B013 IEC 61850 GSSE ID --- --- --- F209 “GSSEOut”
B03F IEC 61850 GOOSE Function (GoEna) 0 to 1 --- 1 F102 0 (Disabled)
B040 IEC 61850 GSSE Destination MAC Address --- --- --- F072 0
B043 IEC 61850 Standard GOOSE ID --- --- --- F209 “GOOSEOut”
B064 IEC 61850 Standard GOOSE Destination MAC Address --- --- --- F072 0
B067 IEC 61850 GOOSE VLAN Transmit Priority 0 to 7 --- 1 F001 4
B068 IEC 61850 GOOSE VLAN ID 0 to 4095 --- 1 F001 0
B069 IEC 61850 GOOSE ETYPE APPID 0 to 16383 --- 1 F001 0
B06A Reserved (2 items) 0 to 1 --- 1 F001 0
IEC 61850 Server Configuration (Read/Write Settings/Commands)
B06C TCP Port Number for the IEC 61850 / MMS Protocol 1 to 65535 --- 1 F001 102
B06D IEC 61850 Logical Device Name --- --- --- F213 “IECName”
B07D IEC 61850 Logical Device Instance --- --- --- F213 “LDInst”
B08D IEC 61850 LPHD Location --- --- --- F204 “Location”
B0B5 Include non-IEC 61850 Data 0 to 1 --- 1 F102 0 (Disabled)
B06B IEC 61850 Server Data Scanning Function 0 to 1 --- 1 F102 0 (Disabled)
B0B7 Reserved (15 items)
IEC 61850 MMXU Deadbands (Read/Write Setting) (6 modules)
B0C0 IEC 61850 MMXU TotW Deadband 1 0.001 to 100 % 0.001 F003 10000
B0C2 IEC 61850 MMXU TotVAr Deadband 1 0.001 to 100 % 0.001 F003 10000
B0C4 IEC 61850 MMXU TotVA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0C6 IEC 61850 MMXU TotPF Deadband 1 0.001 to 100 % 0.001 F003 10000
B0C8 IEC 61850 MMXU Hz Deadband 1 0.001 to 100 % 0.001 F003 10000
B0CA IEC 61850 MMXU PPV.phsAB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0CC IEC 61850 MMXU PPV.phsBC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0CE IEC 61850 MMXU PPV.phsCA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0D0 IEC 61850 MMXU PhV.phsADeadband 1 0.001 to 100 % 0.001 F003 10000
B0D2 IEC 61850 MMXU PhV.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0D4 IEC 61850 MMXU PhV.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0D6 IEC 61850 MMXU A.phsA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0D8 IEC 61850 MMXU A.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000

B-50 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 44 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
B0DA IEC 61850 MMXU A.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0DC IEC 61850 MMXU A.neut Deadband 1 0.001 to 100 % 0.001 F003 10000
B0DE IEC 61850 MMXU W.phsA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0E0 IEC 61850 MMXU W.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0E2 IEC 61850 MMXU W.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0E4 IEC 61850 MMXU VAr.phsA Deadband 1 0.001 to 100 % 0.001 F003 10000 B
B0E6 IEC 61850 MMXU VAr.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0E8 IEC 61850 MMXU VAr.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0EA IEC 61850 MMXU VA.phsA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0EC IEC 61850 MMXU VA.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0EE IEC 61850 MMXU VA.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0F0 IEC 61850 MMXU PF.phsA Deadband 1 0.001 to 100 % 0.001 F003 10000
B0F2 IEC 61850 MMXU PF.phsB Deadband 1 0.001 to 100 % 0.001 F003 10000
B0F4 IEC 61850 MMXU PF.phsC Deadband 1 0.001 to 100 % 0.001 F003 10000
B0F6 ...Repeated for Deadband 2
B12C ...Repeated for Deadband 3
B162 ...Repeated for Deadband 4
B198 ...Repeated for Deadband 5
B1CE ...Repeated for Deadband 6
IEC 61850 Configurable Report Settings (Read/Write Setting)
B290 IEC 61850 configurable reports dataset items (64 items) 0 to 848 --- 1 F615 0 (None)
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
B500 Number of Status Indications in GGIO1 8 to 128 --- 8 F001 8
B501 IEC 61850 GGIO1 Indication operands (128 items) --- --- 1 F300 0
IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules)
B5A0 IEC 61850 Configurable GOOSE Function 0 to 1 --- 1 F102 0 (None)
B5A1 IEC 61850 Configurable GOOSE ID --- --- --- F209 “GOOSEOut_x_”
B5C2 Configurable GOOSE Destination MAC Address --- --- --- F072 0
B5C5 IEC 61850 Configurable GOOSE VLAN Transmit Priority 0 to 7 --- 1 F001 4
B5C6 IEC 61850 Configurable GOOSE VLAN ID 0 to 4095 --- 1 F001 0
B5C7 IEC 61850 Configurable GOOSE ETYPE APPID 0 to 16383 --- 1 F001 0
B5C8 IEC 61850 Configurable GOOSE ConfRev 1 to 4294967295 --- 1 F003 1
B5CA IEC 61850 Configurable GOOSE Retransmission Curve 0 to 3 --- 1 F611 3 (Relaxed)
B5CB Configurable GOOSE dataset items for transmission 0 to 542 --- 1 F616 0 (None)
(64 items)
B60B ...Repeated for Module 2
B676 ...Repeated for Module 3
B6E1 ...Repeated for Module 4
B74C ...Repeated for Module 5
B7B7 ...Repeated for Module 6
B822 ...Repeated for Module 7
B88D ...Repeated for Module 8
IEC 61850 Configurable GOOSE Reception (Read/Write Setting) (8 modules)
B900 Configurable GOOSE dataset items for reception 0 to 32 --- 1 F233 0 (None)
(32 items)
B940 ...Repeated for Module 2
B980 ...Repeated for Module 3
B9C0 ...Repeated for Module 4
BA00 ...Repeated for Module 5
BA40 ...Repeated for Module 6
BA80 ...Repeated for Module 7
BAC0 ...Repeated for Module 8
Contact Inputs (Read/Write Setting) (96 modules)
BB00 Contact Input 1 Name --- --- --- F205 “Cont Ip 1“
BB06 Contact Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)

GE Multilin G60 Generator Protection System B-51


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 45 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
BB07 Contact Input 1 Debounce Time 0 to 16 ms 0.5 F001 20
BB08 ...Repeated for Contact Input 2
BB10 ...Repeated for Contact Input 3
BB18 ...Repeated for Contact Input 4
BB20 ...Repeated for Contact Input 5

B BB28
BB30
...Repeated for Contact Input 6
...Repeated for Contact Input 7
BB38 ...Repeated for Contact Input 8
BB40 ...Repeated for Contact Input 9
BB48 ...Repeated for Contact Input 10
BB50 ...Repeated for Contact Input 11
BB58 ...Repeated for Contact Input 12
BB60 ...Repeated for Contact Input 13
BB68 ...Repeated for Contact Input 14
BB70 ...Repeated for Contact Input 15
BB78 ...Repeated for Contact Input 16
BB80 ...Repeated for Contact Input 17
BB88 ...Repeated for Contact Input 18
BB90 ...Repeated for Contact Input 19
BB98 ...Repeated for Contact Input 20
BBA0 ...Repeated for Contact Input 21
BBA8 ...Repeated for Contact Input 22
BBB0 ...Repeated for Contact Input 23
BBB8 ...Repeated for Contact Input 24
BBC0 ...Repeated for Contact Input 25
BBC8 ...Repeated for Contact Input 26
BBD0 ...Repeated for Contact Input 27
BBD8 ...Repeated for Contact Input 28
BBE0 ...Repeated for Contact Input 29
BBE8 ...Repeated for Contact Input 30
BBF0 ...Repeated for Contact Input 31
BBF8 ...Repeated for Contact Input 32
BC00 ...Repeated for Contact Input 33
BC08 ...Repeated for Contact Input 34
BC10 ...Repeated for Contact Input 35
BC18 ...Repeated for Contact Input 36
BC20 ...Repeated for Contact Input 37
BC28 ...Repeated for Contact Input 38
BC30 ...Repeated for Contact Input 39
BC38 ...Repeated for Contact Input 40
BC40 ...Repeated for Contact Input 41
BC48 ...Repeated for Contact Input 42
BC50 ...Repeated for Contact Input 43
BC58 ...Repeated for Contact Input 44
BC60 ...Repeated for Contact Input 45
BC68 ...Repeated for Contact Input 46
BC70 ...Repeated for Contact Input 47
BC78 ...Repeated for Contact Input 48
BC80 ...Repeated for Contact Input 49
BC88 ...Repeated for Contact Input 50
BC90 ...Repeated for Contact Input 51
BC98 ...Repeated for Contact Input 52
BCA0 ...Repeated for Contact Input 53
BCA8 ...Repeated for Contact Input 54

B-52 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 46 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
BCB0 ...Repeated for Contact Input 55
BCB8 ...Repeated for Contact Input 56
BCC0 ...Repeated for Contact Input 57
BCC8 ...Repeated for Contact Input 58
BCD0 ...Repeated for Contact Input 59
BCD8 ...Repeated for Contact Input 60 B
BCE0 ...Repeated for Contact Input 61
BCE8 ...Repeated for Contact Input 62
BCF0 ...Repeated for Contact Input 63
BCF8 ...Repeated for Contact Input 64
BD00 ...Repeated for Contact Input 65
BD08 ...Repeated for Contact Input 66
BD10 ...Repeated for Contact Input 67
BD18 ...Repeated for Contact Input 68
BD20 ...Repeated for Contact Input 69
BD28 ...Repeated for Contact Input 70
BD30 ...Repeated for Contact Input 71
BD38 ...Repeated for Contact Input 72
BD40 ...Repeated for Contact Input 73
BD48 ...Repeated for Contact Input 74
BD50 ...Repeated for Contact Input 75
BD58 ...Repeated for Contact Input 76
BD60 ...Repeated for Contact Input 77
BD68 ...Repeated for Contact Input 78
BD70 ...Repeated for Contact Input 79
BD78 ...Repeated for Contact Input 80
BD80 ...Repeated for Contact Input 81
BD88 ...Repeated for Contact Input 82
BD90 ...Repeated for Contact Input 83
BD98 ...Repeated for Contact Input 84
BDA0 ...Repeated for Contact Input 85
BDA8 ...Repeated for Contact Input 86
BDB0 ...Repeated for Contact Input 87
BDB8 ...Repeated for Contact Input 88
BDC0 ...Repeated for Contact Input 89
BDC8 ...Repeated for Contact Input 90
BDD0 ...Repeated for Contact Input 91
BDD8 ...Repeated for Contact Input 92
BDE0 ...Repeated for Contact Input 93
BDE8 ...Repeated for Contact Input 94
BDF0 ...Repeated for Contact Input 95
BDF8 ...Repeated for Contact Input 96
Contact Input Thresholds (Read/Write Setting)
BE00 Contact Input n Threshold, n = 1 to 24 (24 items) 0 to 3 --- 1 F128 1 (33 Vdc)
Virtual Inputs (Read/Write Setting) (64 modules)
BE30 Virtual Input 1 Function 0 to 1 --- 1 F102 0 (Disabled)
BE31 Virtual Input 1 Name --- --- --- F205 “Virt Ip 1“
BE37 Virtual Input 1 Programmed Type 0 to 1 --- 1 F127 0 (Latched)
BE38 Virtual Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)
BE39 Reserved (3 items) --- --- --- F001 0
BE3C ...Repeated for Virtual Input 2
BE48 ...Repeated for Virtual Input 3
BE54 ...Repeated for Virtual Input 4
BE60 ...Repeated for Virtual Input 5

GE Multilin G60 Generator Protection System B-53


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 47 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
BE6C ...Repeated for Virtual Input 6
BE78 ...Repeated for Virtual Input 7
BE84 ...Repeated for Virtual Input 8
BE90 ...Repeated for Virtual Input 9
BE9C ...Repeated for Virtual Input 10

B BEA8
BEB4
...Repeated for Virtual Input 11
...Repeated for Virtual Input 12
BEC0 ...Repeated for Virtual Input 13
BECC ...Repeated for Virtual Input 14
BED8 ...Repeated for Virtual Input 15
BEE4 ...Repeated for Virtual Input 16
BEF0 ...Repeated for Virtual Input 17
BEFC ...Repeated for Virtual Input 18
BF08 ...Repeated for Virtual Input 19
BF14 ...Repeated for Virtual Input 20
BF20 ...Repeated for Virtual Input 21
BF2C ...Repeated for Virtual Input 22
BF38 ...Repeated for Virtual Input 23
BF44 ...Repeated for Virtual Input 24
BF50 ...Repeated for Virtual Input 25
BF5C ...Repeated for Virtual Input 26
BF68 ...Repeated for Virtual Input 27
BF74 ...Repeated for Virtual Input 28
BF80 ...Repeated for Virtual Input 29
BF8C ...Repeated for Virtual Input 30
BF98 ...Repeated for Virtual Input 31
BFA4 ...Repeated for Virtual Input 32
BFB0 ...Repeated for Virtual Input 33
BFBC ...Repeated for Virtual Input 34
BFC8 ...Repeated for Virtual Input 35
BFD4 ...Repeated for Virtual Input 36
BFE0 ...Repeated for Virtual Input 37
BFEC ...Repeated for Virtual Input 38
BFF8 ...Repeated for Virtual Input 39
C004 ...Repeated for Virtual Input 40
C010 ...Repeated for Virtual Input 41
C01C ...Repeated for Virtual Input 42
C028 ...Repeated for Virtual Input 43
C034 ...Repeated for Virtual Input 44
C040 ...Repeated for Virtual Input 45
C04C ...Repeated for Virtual Input 46
C058 ...Repeated for Virtual Input 47
C064 ...Repeated for Virtual Input 48
C070 ...Repeated for Virtual Input 49
C07C ...Repeated for Virtual Input 50
C088 ...Repeated for Virtual Input 51
C094 ...Repeated for Virtual Input 52
C0A0 ...Repeated for Virtual Input 53
C0AC ...Repeated for Virtual Input 54
C0B8 ...Repeated for Virtual Input 55
C0C4 ...Repeated for Virtual Input 56
C0D0 ...Repeated for Virtual Input 57
C0DC ...Repeated for Virtual Input 58
C0E8 ...Repeated for Virtual Input 59

B-54 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 48 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
C0F4 ...Repeated for Virtual Input 60
C100 ...Repeated for Virtual Input 61
C10C ...Repeated for Virtual Input 62
C118 ...Repeated for Virtual Input 63
C124 ...Repeated for Virtual Input 64
Virtual Outputs (Read/Write Setting) (96 modules) B
C130 Virtual Output 1 Name --- --- --- F205 “Virt Op 1 “
C136 Virtual Output 1 Events 0 to 1 --- 1 F102 0 (Disabled)
C137 Reserved --- --- --- F001 0
C138 ...Repeated for Virtual Output 2
C140 ...Repeated for Virtual Output 3
C148 ...Repeated for Virtual Output 4
C150 ...Repeated for Virtual Output 5
C158 ...Repeated for Virtual Output 6
C160 ...Repeated for Virtual Output 7
C168 ...Repeated for Virtual Output 8
C170 ...Repeated for Virtual Output 9
C178 ...Repeated for Virtual Output 10
C180 ...Repeated for Virtual Output 11
C188 ...Repeated for Virtual Output 12
C190 ...Repeated for Virtual Output 13
C198 ...Repeated for Virtual Output 14
C1A0 ...Repeated for Virtual Output 15
C1A8 ...Repeated for Virtual Output 16
C1B0 ...Repeated for Virtual Output 17
C1B8 ...Repeated for Virtual Output 18
C1C0 ...Repeated for Virtual Output 19
C1C8 ...Repeated for Virtual Output 20
C1D0 ...Repeated for Virtual Output 21
C1D8 ...Repeated for Virtual Output 22
C1E0 ...Repeated for Virtual Output 23
C1E8 ...Repeated for Virtual Output 24
C1F0 ...Repeated for Virtual Output 25
C1F8 ...Repeated for Virtual Output 26
C200 ...Repeated for Virtual Output 27
C208 ...Repeated for Virtual Output 28
C210 ...Repeated for Virtual Output 29
C218 ...Repeated for Virtual Output 30
C220 ...Repeated for Virtual Output 31
C228 ...Repeated for Virtual Output 32
C230 ...Repeated for Virtual Output 33
C238 ...Repeated for Virtual Output 34
C240 ...Repeated for Virtual Output 35
C248 ...Repeated for Virtual Output 36
C250 ...Repeated for Virtual Output 37
C258 ...Repeated for Virtual Output 38
C260 ...Repeated for Virtual Output 39
C268 ...Repeated for Virtual Output 40
C270 ...Repeated for Virtual Output 41
C278 ...Repeated for Virtual Output 42
C280 ...Repeated for Virtual Output 43
C288 ...Repeated for Virtual Output 44
C290 ...Repeated for Virtual Output 45
C298 ...Repeated for Virtual Output 46

GE Multilin G60 Generator Protection System B-55


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 49 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
C2A0 ...Repeated for Virtual Output 47
C2A8 ...Repeated for Virtual Output 48
C2B0 ...Repeated for Virtual Output 49
C2B8 ...Repeated for Virtual Output 50
C2C0 ...Repeated for Virtual Output 51

B C2C8
C2D0
...Repeated for Virtual Output 52
...Repeated for Virtual Output 53
C2D8 ...Repeated for Virtual Output 54
C2E0 ...Repeated for Virtual Output 55
C2E8 ...Repeated for Virtual Output 56
C2F0 ...Repeated for Virtual Output 57
C2F8 ...Repeated for Virtual Output 58
C300 ...Repeated for Virtual Output 59
C308 ...Repeated for Virtual Output 60
C310 ...Repeated for Virtual Output 61
C318 ...Repeated for Virtual Output 62
C320 ...Repeated for Virtual Output 63
C328 ...Repeated for Virtual Output 64
C330 ...Repeated for Virtual Output 65
C338 ...Repeated for Virtual Output 66
C340 ...Repeated for Virtual Output 67
C348 ...Repeated for Virtual Output 68
C350 ...Repeated for Virtual Output 69
C358 ...Repeated for Virtual Output 70
C360 ...Repeated for Virtual Output 71
C368 ...Repeated for Virtual Output 72
C370 ...Repeated for Virtual Output 73
C378 ...Repeated for Virtual Output 74
C380 ...Repeated for Virtual Output 75
C388 ...Repeated for Virtual Output 76
C390 ...Repeated for Virtual Output 77
C398 ...Repeated for Virtual Output 78
C3A0 ...Repeated for Virtual Output 79
C3A8 ...Repeated for Virtual Output 80
C3B0 ...Repeated for Virtual Output 81
C3B8 ...Repeated for Virtual Output 82
C3C0 ...Repeated for Virtual Output 83
C3C8 ...Repeated for Virtual Output 84
C3D0 ...Repeated for Virtual Output 85
C3D8 ...Repeated for Virtual Output 86
C3E0 ...Repeated for Virtual Output 87
C3E8 ...Repeated for Virtual Output 88
C3F0 ...Repeated for Virtual Output 89
C3F8 ...Repeated for Virtual Output 90
C400 ...Repeated for Virtual Output 91
C408 ...Repeated for Virtual Output 92
C410 ...Repeated for Virtual Output 93
C418 ...Repeated for Virtual Output 94
C420 ...Repeated for Virtual Output 95
C428 ...Repeated for Virtual Output 96
Mandatory (Read/Write Setting)
C430 Test Mode Function 0 to 1 --- 1 F245 0 (Disabled)
C431 Force VFD and LED 0 to 1 --- 1 F126 0 (No)
C432 Test Mode Forcing 0 to 65535 --- 1 F300 1

B-56 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 50 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
Clear commands (read/write)
C433 Clear All Relay Records Command 0 to 1 --- 1 F126 0 (No)
Contact Outputs (Read/Write Setting) (64 modules)
C440 Contact Output 1 Name --- --- --- F205 “Cont Op 1"
C446 Contact Output 1 Operation 0 to 65535 --- 1 F300 0
C447 Contact Output 1 Seal In 0 to 65535 --- 1 F300 0 B
C448 Latching Output 1 Reset 0 to 65535 --- 1 F300 0
C449 Contact Output 1 Events 0 to 1 --- 1 F102 1 (Enabled)
C44A Latching Output 1 Type 0 to 1 --- 1 F090 0 (Operate-dominant)
C44B Reserved --- --- --- F001 0
C44C ...Repeated for Contact Output 2
C458 ...Repeated for Contact Output 3
C464 ...Repeated for Contact Output 4
C470 ...Repeated for Contact Output 5
C47C ...Repeated for Contact Output 6
C488 ...Repeated for Contact Output 7
C494 ...Repeated for Contact Output 8
C4A0 ...Repeated for Contact Output 9
C4AC ...Repeated for Contact Output 10
C4B8 ...Repeated for Contact Output 11
C4C4 ...Repeated for Contact Output 12
C4D0 ...Repeated for Contact Output 13
C4DC ...Repeated for Contact Output 14
C4E8 ...Repeated for Contact Output 15
C4F4 ...Repeated for Contact Output 16
C500 ...Repeated for Contact Output 17
C50C ...Repeated for Contact Output 18
C518 ...Repeated for Contact Output 19
C524 ...Repeated for Contact Output 20
C530 ...Repeated for Contact Output 21
C53C ...Repeated for Contact Output 22
C548 ...Repeated for Contact Output 23
C554 ...Repeated for Contact Output 24
C560 ...Repeated for Contact Output 25
C56C ...Repeated for Contact Output 26
C578 ...Repeated for Contact Output 27
C584 ...Repeated for Contact Output 28
C590 ...Repeated for Contact Output 29
C59C ...Repeated for Contact Output 30
C5A8 ...Repeated for Contact Output 31
C5B4 ...Repeated for Contact Output 32
C5C0 ...Repeated for Contact Output 33
C5CC ...Repeated for Contact Output 34
C5D8 ...Repeated for Contact Output 35
C5E4 ...Repeated for Contact Output 36
C5F0 ...Repeated for Contact Output 37
C5FC ...Repeated for Contact Output 38
C608 ...Repeated for Contact Output 39
C614 ...Repeated for Contact Output 40
C620 ...Repeated for Contact Output 41
C62C ...Repeated for Contact Output 42
C638 ...Repeated for Contact Output 43
C644 ...Repeated for Contact Output 44
C650 ...Repeated for Contact Output 45

GE Multilin G60 Generator Protection System B-57


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 51 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
C65C ...Repeated for Contact Output 46
C668 ...Repeated for Contact Output 47
C674 ...Repeated for Contact Output 48
C680 ...Repeated for Contact Output 49
C68C ...Repeated for Contact Output 50

B C698
C6A4
...Repeated for Contact Output 51
...Repeated for Contact Output 52
C6B0 ...Repeated for Contact Output 53
C6BC ...Repeated for Contact Output 54
C6C8 ...Repeated for Contact Output 55
C6D4 ...Repeated for Contact Output 56
C6E0 ...Repeated for Contact Output 57
C6EC ...Repeated for Contact Output 58
C6F8 ...Repeated for Contact Output 59
C704 ...Repeated for Contact Output 60
C710 ...Repeated for Contact Output 61
C71C ...Repeated for Contact Output 62
C728 ...Repeated for Contact Output 63
C734 ...Repeated for Contact Output 64
Reset (Read/Write Setting)
C750 FlexLogic™ operand which initiates a reset 0 to 65535 --- 1 F300 0
Control Pushbuttons (Read/Write Setting) (7 modules)
C760 Control Pushbutton 1 Function 0 to 1 --- 1 F102 0 (Disabled)
C761 Control Pushbutton 1 Events 0 to 1 --- 1 F102 0 (Disabled)
C762 ...Repeated for Control Pushbutton 2
C764 ...Repeated for Control Pushbutton 3
C766 ...Repeated for Control Pushbutton 4
C768 ...Repeated for Control Pushbutton 5
C76A ...Repeated for Control Pushbutton 6
C76C ...Repeated for Control Pushbutton 7
Clear Records (Read/Write Setting)
C771 Clear User Fault Reports operand 0 to 65535 --- 1 F300 0
C772 Clear Event Records operand 0 to 65535 --- 1 F300 0
C773 Clear Oscillography operand 0 to 65535 --- 1 F300 0
C774 Clear Data Logger operand 0 to 65535 --- 1 F300 0
C77D Clear Energy operand 0 to 65535 --- 1 F300 0
C77F Clear Unauthorized Access operand 0 to 65535 --- 1 F300 0
C781 Clear Platform Direct Input/Output Statistics operand 0 to 65535 --- 1 F300 0
C782 Reserved (13 items) --- --- --- F001 0
Force Contact Inputs/Outputs (Read/Write Settings)
C7A0 Force Contact Input x State (96 items) 0 to 2 --- 1 F144 0 (Disabled)
C800 Force Contact Output x State (64 items) 0 to 3 --- 1 F131 0 (Disabled)
Direct Inputs/Outputs (Read/Write Setting)
C880 Direct Device ID 1 to 16 --- 1 F001 1
C881 Direct I/O Channel 1 Ring Configuration Function 0 to 1 --- 1 F126 0 (No)
C882 Platform Direct I/O Data Rate 64 to 128 kbps 64 F001 64
C883 Direct I/O Channel 2 Ring Configuration Function 0 to 1 --- 1 F126 0 (No)
C884 Platform Direct I/O Crossover Function 0 to 1 --- 1 F102 0 (Disabled)
Direct input/output commands (Read/Write Command)
C888 Direct input/output clear counters command 0 to 1 --- 1 F126 0 (No)
Direct inputs (Read/Write Setting) (96 modules)
C890 Direct Input 1 Device Number 0 to 16 --- 1 F001 0
C891 Direct Input 1 Number 0 to 96 --- 1 F001 0
C892 Direct Input 1 Default State 0 to 3 --- 1 F086 0 (Off)

B-58 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 52 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
C893 Direct Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)
C894 ...Repeated for Direct Input 2
C898 ...Repeated for Direct Input 3
C89C ...Repeated for Direct Input 4
C8A0 ...Repeated for Direct Input 5
C8A4 ...Repeated for Direct Input 6 B
C8A8 ...Repeated for Direct Input 7
C8AC ...Repeated for Direct Input 8
C8B0 ...Repeated for Direct Input 9
C8B4 ...Repeated for Direct Input 10
C8B8 ...Repeated for Direct Input 11
C8BC ...Repeated for Direct Input 12
C8C0 ...Repeated for Direct Input 13
C8C4 ...Repeated for Direct Input 14
C8C8 ...Repeated for Direct Input 15
C8CC ...Repeated for Direct Input 16
C8D0 ...Repeated for Direct Input 17
C8D4 ...Repeated for Direct Input 18
C8D8 ...Repeated for Direct Input 19
C8DC ...Repeated for Direct Input 20
C8E0 ...Repeated for Direct Input 21
C8E4 ...Repeated for Direct Input 22
C8E8 ...Repeated for Direct Input 23
C8EC ...Repeated for Direct Input 24
C8F0 ...Repeated for Direct Input 25
C8F4 ...Repeated for Direct Input 26
C8F8 ...Repeated for Direct Input 27
C8FC ...Repeated for Direct Input 28
C900 ...Repeated for Direct Input 29
C904 ...Repeated for Direct Input 30
C908 ...Repeated for Direct Input 31
C90C ...Repeated for Direct Input 32
Platform Direct Outputs (Read/Write Setting) (96 modules)
CA10 Direct Output 1 Operand 0 to 65535 --- 1 F300 0
CA11 Direct Output 1 Events 0 to 1 --- 1 F102 0 (Disabled)
CA12 ...Repeated for Direct Output 2
CA14 ...Repeated for Direct Output 3
CA16 ...Repeated for Direct Output 4
CA18 ...Repeated for Direct Output 5
CA1A ...Repeated for Direct Output 6
CA1C ...Repeated for Direct Output 7
CA1E ...Repeated for Direct Output 8
CA20 ...Repeated for Direct Output 9
CA22 ...Repeated for Direct Output 10
CA24 ...Repeated for Direct Output 11
CA26 ...Repeated for Direct Output 12
CA28 ...Repeated for Direct Output 13
CA2A ...Repeated for Direct Output 14
CA2C ...Repeated for Direct Output 15
CA2E ...Repeated for Direct Output 16
CA30 ...Repeated for Direct Output 17
CA32 ...Repeated for Direct Output 18
CA34 ...Repeated for Direct Output 19
CA36 ...Repeated for Direct Output 20

GE Multilin G60 Generator Protection System B-59


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 53 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
CA38 ...Repeated for Direct Output 21
CA3A ...Repeated for Direct Output 22
CA3C ...Repeated for Direct Output 23
CA3E ...Repeated for Direct Output 24
CA40 ...Repeated for Direct Output 25

B CA42
CA44
...Repeated for Direct Output 26
...Repeated for Direct Output 27
CA46 ...Repeated for Direct Output 28
CA48 ...Repeated for Direct Output 29
CA4A ...Repeated for Direct Output 30
CA4C ...Repeated for Direct Output 31
CA4E ...Repeated for Direct Output 32
Direct Input/Output Alarms (Read/Write Setting)
CAD0 Direct Input/Output Channel 1 CRC Alarm Function 0 to 1 --- 1 F102 0 (Disabled)
CAD1 Direct I/O Channel 1 CRC Alarm Message Count 100 to 10000 --- 1 F001 600
CAD2 Direct Input/Output Channel 1 CRC Alarm Threshold 1 to 1000 --- 1 F001 10
CAD3 Direct Input/Output Channel 1 CRC Alarm Events 0 to 1 --- 1 F102 0 (Disabled)
CAD4 Reserved (4 items) 1 to 1000 --- 1 F001 10
CAD8 Direct Input/Output Channel 2 CRC Alarm Function 0 to 1 --- 1 F102 0 (Disabled)
CAD9 Direct I/O Channel 2 CRC Alarm Message Count 100 to 10000 --- 1 F001 600
CADA Direct Input/Output Channel 2 CRC Alarm Threshold 1 to 1000 --- 1 F001 10
CADB Direct Input/Output Channel 2 CRC Alarm Events 0 to 1 --- 1 F102 0 (Disabled)
CADC Reserved (4 items) 1 to 1000 --- 1 F001 10
CAE0 Direct I/O Ch 1 Unreturned Messages Alarm Function 0 to 1 --- 1 F102 0 (Disabled)
CAE1 Direct I/O Ch 1 Unreturned Messages Alarm Msg Count 100 to 10000 --- 1 F001 600
CAE2 Direct I/O Ch 1 Unreturned Messages Alarm Threshold 1 to 1000 --- 1 F001 10
CAE3 Direct I/O Ch 1 Unreturned Messages Alarm Events 0 to 1 --- 1 F102 0 (Disabled)
CAE4 Reserved (4 items) 1 to 1000 --- 1 F001 10
CAE8 Direct IO Ch 2 Unreturned Messages Alarm Function 0 to 1 --- 1 F102 0 (Disabled)
CAE9 Direct I/O Ch 2 Unreturned Messages Alarm Msg Count 100 to 10000 --- 1 F001 600
CAEA Direct I/O Ch 2 Unreturned Messages Alarm Threshold 1 to 1000 --- 1 F001 10
CAEB Direct I/O Channel 2 Unreturned Messages Alarm Events 0 to 1 --- 1 F102 0 (Disabled)
CAEC Reserved (4 items) --- --- 1 F001 10
Remote Devices (Read/Write Setting) (16 modules)
CB00 Remote Device 1 GSSE/GOOSE Application ID --- --- --- F209 “Remote Device 1“
CB21 Remote Device 1 GOOSE Ethernet APPID 0 to 16383 --- 1 F001 0
CB22 Remote Device 1 GOOSE Dataset 0 to 16 --- 1 F184 0 (Fixed)
CB23 Remote Device 1 in PMU Scheme 0 to 1 --- 1 F126 0 (No)
CB24 ...Repeated for Device 2
CB48 ...Repeated for Device 3
CB6C ...Repeated for Device 4
CB90 ...Repeated for Device 5
CBB4 ...Repeated for Device 6
CBD8 ...Repeated for Device 7
CBFC ...Repeated for Device 8
CC20 ...Repeated for Device 9
CC44 ...Repeated for Device 10
CC68 ...Repeated for Device 11
CC8C ...Repeated for Device 12
CCB0 ...Repeated for Device 13
CCD4 ...Repeated for Device 14
CCF8 ...Repeated for Device 15
CD1C ...Repeated for Device 16

B-60 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 54 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
Remote Inputs (Read/Write Setting) (64 modules)
CFA0 Remote Input 1 Device 1 to 16 --- 1 F001 1
CFA1 Remote Input 1 Item 0 to 64 --- 1 F156 0 (None)
CFA2 Remote Input 1 Default State 0 to 3 --- 1 F086 0 (Off)
CFA3 Remote Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)
CFA4 Remote Input 1 Name 1 to 64 --- 1 F205 “Rem Ip 1” B
CFAA ...Repeated for Remote Input 2
CFB4 ...Repeated for Remote Input 3
CFBE ...Repeated for Remote Input 4
CFC8 ...Repeated for Remote Input 5
CFD2 ...Repeated for Remote Input 6
CFDC ...Repeated for Remote Input 7
CFE6 ...Repeated for Remote Input 8
CFF0 ...Repeated for Remote Input 9
CFFA ...Repeated for Remote Input 10
D004 ...Repeated for Remote Input 11
D00E ...Repeated for Remote Input 12
D018 ...Repeated for Remote Input 13
D022 ...Repeated for Remote Input 14
D02C ...Repeated for Remote Input 15
D036 ...Repeated for Remote Input 16
D040 ...Repeated for Remote Input 17
D04A ...Repeated for Remote Input 18
D054 ...Repeated for Remote Input 19
D05E ...Repeated for Remote Input 20
D068 ...Repeated for Remote Input 21
D072 ...Repeated for Remote Input 22
D07C ...Repeated for Remote Input 23
D086 ...Repeated for Remote Input 24
D090 ...Repeated for Remote Input 25
D09A ...Repeated for Remote Input 26
D0A4 ...Repeated for Remote Input 27
D0AE ...Repeated for Remote Input 28
D0B8 ...Repeated for Remote Input 29
D0C2 ...Repeated for Remote Input 30
D0CC ...Repeated for Remote Input 31
D0D6 ...Repeated for Remote Input 32
Remote Output DNA Pairs (Read/Write Setting) (32 modules)
D220 Remote Output DNA 1 Operand 0 to 65535 --- 1 F300 0
D221 Remote Output DNA 1 Events 0 to 1 --- 1 F102 0 (Disabled)
D222 Reserved (2 items) 0 to 1 --- 1 F001 0
D224 ...Repeated for Remote Output 2
D228 ...Repeated for Remote Output 3
D22C ...Repeated for Remote Output 4
D230 ...Repeated for Remote Output 5
D234 ...Repeated for Remote Output 6
D238 ...Repeated for Remote Output 7
D23C ...Repeated for Remote Output 8
D240 ...Repeated for Remote Output 9
D244 ...Repeated for Remote Output 10
D248 ...Repeated for Remote Output 11
D24C ...Repeated for Remote Output 12
D250 ...Repeated for Remote Output 13
D254 ...Repeated for Remote Output 14

GE Multilin G60 Generator Protection System B-61


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 55 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
D258 ...Repeated for Remote Output 15
D25C ...Repeated for Remote Output 16
D260 ...Repeated for Remote Output 17
D264 ...Repeated for Remote Output 18
D268 ...Repeated for Remote Output 19

B D26C
D270
...Repeated for Remote Output 20
...Repeated for Remote Output 21
D274 ...Repeated for Remote Output 22
D278 ...Repeated for Remote Output 23
D27C ...Repeated for Remote Output 24
D280 ...Repeated for Remote Output 25
D284 ...Repeated for Remote Output 26
D288 ...Repeated for Remote Output 27
D28C ...Repeated for Remote Output 28
D290 ...Repeated for Remote Output 29
D294 ...Repeated for Remote Output 30
D298 ...Repeated for Remote Output 31
D29C ...Repeated for Remote Output 32
Remote Output UserSt Pairs (Read/Write Setting) (32 modules)
D2A0 Remote Output UserSt 1 Operand 0 to 65535 --- 1 F300 0
D2A1 Remote Output UserSt 1 Events 0 to 1 --- 1 F102 0 (Disabled)
D2A2 Reserved (2 items) 0 to 1 --- 1 F001 0
D2A4 ...Repeated for Remote Output 2
D2A8 ...Repeated for Remote Output 3
D2AC ...Repeated for Remote Output 4
D2B0 ...Repeated for Remote Output 5
D2B4 ...Repeated for Remote Output 6
D2B8 ...Repeated for Remote Output 7
D2BC ...Repeated for Remote Output 8
D2C0 ...Repeated for Remote Output 9
D2C4 ...Repeated for Remote Output 10
D2C8 ...Repeated for Remote Output 11
D2CC ...Repeated for Remote Output 12
D2D0 ...Repeated for Remote Output 13
D2D4 ...Repeated for Remote Output 14
D2D8 ...Repeated for Remote Output 15
D2DC ...Repeated for Remote Output 16
D2E0 ...Repeated for Remote Output 17
D2E4 ...Repeated for Remote Output 18
D2E8 ...Repeated for Remote Output 19
D2EC ...Repeated for Remote Output 20
D2F0 ...Repeated for Remote Output 21
D2F4 ...Repeated for Remote Output 22
D2F8 ...Repeated for Remote Output 23
D2FC ...Repeated for Remote Output 24
D300 ...Repeated for Remote Output 25
D304 ...Repeated for Remote Output 26
D308 ...Repeated for Remote Output 27
D30C ...Repeated for Remote Output 28
D310 ...Repeated for Remote Output 29
D314 ...Repeated for Remote Output 30
D318 ...Repeated for Remote Output 31
D31C ...Repeated for Remote Output 32

B-62 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 56 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
IEC 61850 GGIO2 Control Configuration (Read/Write Setting) (64 modules)
D320 IEC 61850 GGIO2.CF.SPCSO1.ctlModel Value 0 to 2 --- 1 F001 2
D321 IEC 61850 GGIO2.CF.SPCSO2.ctlModel Value 0 to 2 --- 1 F001 2
D322 IEC 61850 GGIO2.CF.SPCSO3.ctlModel Value 0 to 2 --- 1 F001 2
D323 IEC 61850 GGIO2.CF.SPCSO4.ctlModel Value 0 to 2 --- 1 F001 2
D324 IEC 61850 GGIO2.CF.SPCSO5.ctlModel Value 0 to 2 --- 1 F001 2 B
D325 IEC 61850 GGIO2.CF.SPCSO6.ctlModel Value 0 to 2 --- 1 F001 2
D326 IEC 61850 GGIO2.CF.SPCSO7.ctlModel Value 0 to 2 --- 1 F001 2
D327 IEC 61850 GGIO2.CF.SPCSO8.ctlModel Value 0 to 2 --- 1 F001 2
D328 IEC 61850 GGIO2.CF.SPCSO9.ctlModel Value 0 to 2 --- 1 F001 2
D329 IEC 61850 GGIO2.CF.SPCSO10.ctlModel Value 0 to 2 --- 1 F001 2
D32A IEC 61850 GGIO2.CF.SPCSO11.ctlModel Value 0 to 2 --- 1 F001 2
D32B IEC 61850 GGIO2.CF.SPCSO12.ctlModel Value 0 to 2 --- 1 F001 2
D32C IEC 61850 GGIO2.CF.SPCSO13.ctlModel Value 0 to 2 --- 1 F001 2
D32D IEC 61850 GGIO2.CF.SPCSO14.ctlModel Value 0 to 2 --- 1 F001 2
D32E IEC 61850 GGIO2.CF.SPCSO15.ctlModel Value 0 to 2 --- 1 F001 2
D32F IEC 61850 GGIO2.CF.SPCSO16.ctlModel Value 0 to 2 --- 1 F001 2
D330 IEC 61850 GGIO2.CF.SPCSO17.ctlModel Value 0 to 2 --- 1 F001 2
D331 IEC 61850 GGIO2.CF.SPCSO18.ctlModel Value 0 to 2 --- 1 F001 2
D332 IEC 61850 GGIO2.CF.SPCSO19.ctlModel Value 0 to 2 --- 1 F001 2
D333 IEC 61850 GGIO2.CF.SPCSO20.ctlModel Value 0 to 2 --- 1 F001 2
D334 IEC 61850 GGIO2.CF.SPCSO21.ctlModel Value 0 to 2 --- 1 F001 2
D335 IEC 61850 GGIO2.CF.SPCSO22.ctlModel Value 0 to 2 --- 1 F001 2
D336 IEC 61850 GGIO2.CF.SPCSO23.ctlModel Value 0 to 2 --- 1 F001 2
D337 IEC 61850 GGIO2.CF.SPCSO24.ctlModel Value 0 to 2 --- 1 F001 2
D338 IEC 61850 GGIO2.CF.SPCSO25.ctlModel Value 0 to 2 --- 1 F001 2
D339 IEC 61850 GGIO2.CF.SPCSO26.ctlModel Value 0 to 2 --- 1 F001 2
D33A IEC 61850 GGIO2.CF.SPCSO27.ctlModel Value 0 to 2 --- 1 F001 2
D33B IEC 61850 GGIO2.CF.SPCSO28.ctlModel Value 0 to 2 --- 1 F001 2
D33C IEC 61850 GGIO2.CF.SPCSO29.ctlModel Value 0 to 2 --- 1 F001 2
D33D IEC 61850 GGIO2.CF.SPCSO30.ctlModel Value 0 to 2 --- 1 F001 2
D33E IEC 61850 GGIO2.CF.SPCSO31.ctlModel Value 0 to 2 --- 1 F001 2
D33F IEC 61850 GGIO2.CF.SPCSO32.ctlModel Value 0 to 2 --- 1 F001 2
D340 IEC 61850 GGIO2.CF.SPCSO33.ctlModel Value 0 to 2 --- 1 F001 2
D341 IEC 61850 GGIO2.CF.SPCSO34.ctlModel Value 0 to 2 --- 1 F001 2
D342 IEC 61850 GGIO2.CF.SPCSO35.ctlModel Value 0 to 2 --- 1 F001 2
D343 IEC 61850 GGIO2.CF.SPCSO36.ctlModel Value 0 to 2 --- 1 F001 2
D344 IEC 61850 GGIO2.CF.SPCSO37.ctlModel Value 0 to 2 --- 1 F001 2
D345 IEC 61850 GGIO2.CF.SPCSO38.ctlModel Value 0 to 2 --- 1 F001 2
D346 IEC 61850 GGIO2.CF.SPCSO39.ctlModel Value 0 to 2 --- 1 F001 2
D347 IEC 61850 GGIO2.CF.SPCSO40.ctlModel Value 0 to 2 --- 1 F001 2
D348 IEC 61850 GGIO2.CF.SPCSO41.ctlModel Value 0 to 2 --- 1 F001 2
D349 IEC 61850 GGIO2.CF.SPCSO42.ctlModel Value 0 to 2 --- 1 F001 2
D34A IEC 61850 GGIO2.CF.SPCSO43.ctlModel Value 0 to 2 --- 1 F001 2
D34B IEC 61850 GGIO2.CF.SPCSO44.ctlModel Value 0 to 2 --- 1 F001 2
D34C IEC 61850 GGIO2.CF.SPCSO45.ctlModel Value 0 to 2 --- 1 F001 2
D34D IEC 61850 GGIO2.CF.SPCSO46.ctlModel Value 0 to 2 --- 1 F001 2
D34E IEC 61850 GGIO2.CF.SPCSO47.ctlModel Value 0 to 2 --- 1 F001 2
D34F IEC 61850 GGIO2.CF.SPCSO48.ctlModel Value 0 to 2 --- 1 F001 2
D350 IEC 61850 GGIO2.CF.SPCSO49.ctlModel Value 0 to 2 --- 1 F001 2
D351 IEC 61850 GGIO2.CF.SPCSO50.ctlModel Value 0 to 2 --- 1 F001 2
D352 IEC 61850 GGIO2.CF.SPCSO51.ctlModel Value 0 to 2 --- 1 F001 2
D353 IEC 61850 GGIO2.CF.SPCSO52.ctlModel Value 0 to 2 --- 1 F001 2
D354 IEC 61850 GGIO2.CF.SPCSO53.ctlModel Value 0 to 2 --- 1 F001 2

GE Multilin G60 Generator Protection System B-63


B.4 MEMORY MAPPING APPENDIX B

Table B–9: MODBUS MEMORY MAP (Sheet 57 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
D355 IEC 61850 GGIO2.CF.SPCSO54.ctlModel Value 0 to 2 --- 1 F001 2
D356 IEC 61850 GGIO2.CF.SPCSO55.ctlModel Value 0 to 2 --- 1 F001 2
D357 IEC 61850 GGIO2.CF.SPCSO56.ctlModel Value 0 to 2 --- 1 F001 2
D358 IEC 61850 GGIO2.CF.SPCSO57.ctlModel Value 0 to 2 --- 1 F001 2
D359 IEC 61850 GGIO2.CF.SPCSO58.ctlModel Value 0 to 2 --- 1 F001 2

B D35A
D35B
IEC 61850 GGIO2.CF.SPCSO59.ctlModel Value
IEC 61850 GGIO2.CF.SPCSO60.ctlModel Value
0 to 2
0 to 2
---
---
1
1
F001
F001
2
2
D35C IEC 61850 GGIO2.CF.SPCSO61.ctlModel Value 0 to 2 --- 1 F001 2
D35D IEC 61850 GGIO2.CF.SPCSO62.ctlModel Value 0 to 2 --- 1 F001 2
D35E IEC 61850 GGIO2.CF.SPCSO63.ctlModel Value 0 to 2 --- 1 F001 2
Remote Device Status (Read Only) (16 modules)
D380 Remote Device 1 StNum 0 to 4294967295 --- 1 F003 0
D382 Remote Device 1 SqNum 0 to 4294967295 --- 1 F003 0
D384 ...Repeated for Remote Device 2
D388 ...Repeated for Remote Device 3
D38C ...Repeated for Remote Device 4
D390 ...Repeated for Remote Device 5
D394 ...Repeated for Remote Device 6
D398 ...Repeated for Remote Device 7
D39C ...Repeated for Remote Device 8
D3A0 ...Repeated for Remote Device 9
D3A4 ...Repeated for Remote Device 10
D3A8 ...Repeated for Remote Device 11
D3AC ...Repeated for Remote Device 12
D3B0 ...Repeated for Remote Device 13
D3B4 ...Repeated for Remote Device 14
D3B8 ...Repeated for Remote Device 15
D3BC ...Repeated for Remote Device 16
D3C0 ...Repeated for Remote Device 17
D3C4 ...Repeated for Remote Device 18
D3C8 ...Repeated for Remote Device 19
D3CC ...Repeated for Remote Device 20
D3D0 ...Repeated for Remote Device 21
D3D4 ...Repeated for Remote Device 22
D3D8 ...Repeated for Remote Device 23
D3DC ...Repeated for Remote Device 24
D3E0 ...Repeated for Remote Device 25
D3E4 ...Repeated for Remote Device 26
D3E8 ...Repeated for Remote Device 27
D3EC ...Repeated for Remote Device 28
D3F0 ...Repeated for Remote Device 29
D3F4 ...Repeated for Remote Device 30
D3F8 ...Repeated for Remote Device 31
D3FC ...Repeated for Remote Device 32
Phasor Measurement Unit Communication (Read/Write Setting)
D400 PMU 1 Communication Port 1 Type 0 to 3 --- 1 F545 0 (Network)
D401 PMU 1 Communication Port 2 Type 0 to 3 --- 1 F545 0 (Network)
D402 PMU 1 Communication Port 3 Type 0 to 3 --- 1 F545 0 (Network)
D403 PMU 1 Port 1 PHS-x (14 items) 0 to 14 --- 1 F543 1 (Va)
D411 PMU 1 Port 2 PHS-x (14 items) 0 to 14 --- 1 F543 1 (Va)
D41F PMU 1 Port 3 PHS-x (14 items) 0 to 14 --- 1 F543 1 (Va)
D42D PMU 1 Communication Port 1 PHS-x Name (14 items) --- --- --- F203 “GE-UR-PMU-PHS 1”
D49D PMU 1 Port 2 PHS-x Name (14 items) --- --- --- F203 “GE-UR-PMU-PHS 1”
D50D PMU 1 Port 3 PHS-x Name (14 items) --- --- --- F203 “GE-UR-PMU-PHS 1”

B-64 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Table B–9: MODBUS MEMORY MAP (Sheet 58 of 58)


ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT
D57D PMU 1 Port 1 A-CH-x (8 items) 0 to 65535 --- 1 F600 0
D585 PMU 1 Port 2 A-CH-x (8 items) 0 to 65535 --- 1 F600 0
D58D PMU 1 Port 3 A-CH-x (8 items) 0 to 65535 --- 1 F600 0
D595 PMU 1 Port 1 A-CH-x Name (8 items) --- --- --- F203 “AnalogChannel 1”
D5D5 PMU 1 Port 2 A-CH-x Name (8 items) --- --- --- F203 “AnalogChannel 1”
D615 PMU 1 Port 3 A-CH-x Name (8 items) --- --- --- F203 “AnalogChannel 1” B
D655 PMU 1 Port 1 D-CH-x (16 items) 0 to 65535 --- 1 F300 0
D665 PMU 1 Port 2 D-CH-x (16 items) 0 to 65535 --- 1 F300 0
D675 PMU 1 Port 3 D-CH-x (16 items) 0 to 65535 --- 1 F300 0
D685 PMU 1 Port 1 D-CH-x Name (16 items) --- --- --- F203 “Dig Channel 1”
D705 PMU 1 Port 2 D-CH-x Name (16 items) --- --- --- F203 “Dig Channel 1”
D785 PMU 1 Port 3 D-CH-x Name (16 items) --- --- --- F203 “Dig Channel 1”
D705 PMU 1 Port 1 D-CH-x Normal State (16 items) 0 to 1 --- 1 F108 0 (Off)
D715 PMU 1 Port 2 D-CH-x Normal State (16 items) 0 to 1 --- 1 F108 0 (Off)
D725 PMU 1 Port 3 D-CH-x Normal State (16 items) 0 to 1 --- 1 F108 0 (Off)
Phasor Measurement Unit Recording Command (Read/Write Command)
E4D4 PMU 1 Recording Clear Command 0 to 1 --- 1 F126 0 (No)
E4D5 PMU 1 Recording Force Trigger 0 to 1 --- 1 F126 0 (No)
Phasor Measurement Unit Recording (Read/Write Setting)
E4DC PMU 1 Recording Rate 0 to 10 --- 1 F544 3 (10/sec.)
E4DD Reserved --- --- 1 F001 0
E4DE PMU 1 No Of Timed Records 1 to 128 --- 1 F001 3
E4DF PMU 1 Trigger Mode 0 to 1 --- 1 F542 0 (Auto Overwrite)
E4E0 PMU 1 Timed Trigger Position 1 to 50 % 1 F001 10
E4E1 Reserved --- --- 1 F001 0
E4E2 PMU 1 Record PHS-1 (14 items) 0 to 14 --- 1 F543 1 (Va)
E4F0 PMU 1 Record PHS-x Name (14 items) --- --- --- F203 GE-UR-PMU-PHS 1
E560 PMU 1 Record A-CH-x (8 items) 0 to 65535 --- 1 F600 0
E568 PMU 1 Record A-CH-x Name (8 items) --- --- --- F203 AnalogChannel 1
E5A8 PMU 1 Record D-CH-x (16 items) 0 to 65535 --- 1 F300 0
E5B8 PMU 1 Record D-CH-x Name (16 items) --- --- --- F203 Dig Channel 1
Phasor Measurement Unit Frequency Trigger (Read/Write Setting)
EB00 PMU 1 Frequency Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
EB01 PMU 1 Frequency Trigger Low Frequency 20 to 70 Hz 0.01 F001 4900
EB02 PMU 1 Frequency Trigger High Frequency 20 to 70 Hz 0.01 F001 6100
EB03 PMU 1 Frequency Trigger Pickup Time 0 to 600 s 0.01 F001 10
EB04 PMU 1 Frequency Trigger Dropout Time 0 to 600 s 0.01 F001 100
EB05 PMU 1 Frequency Trigger Block (3 items) 0 to 65535 --- 1 F300 0
EB08 PMU 1 Frequency Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
EB09 PMU 1 Frequency Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Setting file template values (read only)
ED00 FlexLogic™ displays active 0 to 1 --- 1 F102 1 (Enabled)
ED01 Reserved (6 items) --- --- --- --- ---
ED07 Last settings change date 0 to 4294967295 --- 1 F050 0
ED09 Template bitmask (750 items) 0 to 65535 --- 1 F001 0
Phasor Measurement Unit Records (Read Only)
EFFF PMU Recording Number of Triggers 0 to 65535 samples 1 F001 0

GE Multilin G60 Generator Protection System B-65


B.4 MEMORY MAPPING APPENDIX B

B.4.2 DATA FORMATS

F001 F040
UR_UINT16 UNSIGNED 16 BIT INTEGER UR_UINT48 48-BIT UNSIGNED INTEGER

B F002
UR_SINT16 SIGNED 16 BIT INTEGER
F050
UR_UINT32 TIME and DATE (UNSIGNED 32 BIT INTEGER)
Gives the current time in seconds elapsed since 00:00:00 January
1, 1970.
F003
UR_UINT32 UNSIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register. F051
Low order word is stored in the second register. UR_UINT32 DATE in SR format (alternate format for F050)
First 16 bits are Month/Day (MM/DD/xxxx). Month: 1=January,
2=February,...,12=December; Day: 1 to 31 in steps of 1
F004
Last 16 bits are Year (xx/xx/YYYY): 1970 to 2106 in steps of 1
UR_SINT32 SIGNED 32 BIT INTEGER (2 registers)
High order word is stored in the first register/
Low order word is stored in the second register. F052
UR_UINT32 TIME in SR format (alternate format for F050)
First 16 bits are Hours/Minutes (HH:MM:xx.xxx).
F005
Hours: 0=12am, 1=1am,...,12=12pm,...23=11pm;
UR_UINT8 UNSIGNED 8 BIT INTEGER
Minutes: 0 to 59 in steps of 1
Last 16 bits are Seconds (xx:xx:.SS.SSS): 0=00.000s,
F006 1=00.001,...,59999=59.999s)
UR_SINT8 SIGNED 8 BIT INTEGER

F060
F011 FLOATING_POINT IEEE FLOATING POINT (32 bits)
UR_UINT16 FLEXCURVE DATA (120 points)
A FlexCurve is an array of 120 consecutive data points (x, y) which
F070
are interpolated to generate a smooth curve. The y-axis is the user
HEX2 2 BYTES - 4 ASCII DIGITS
defined trip or operation time setting; the x-axis is the pickup ratio
and is pre-defined. Refer to format F119 for a listing of the pickup
ratios; the enumeration value for the pickup ratio indicates the off-
F071
set into the FlexCurve base address where the corresponding time HEX4 4 BYTES - 8 ASCII DIGITS
value is stored.

F072
F012
HEX6 6 BYTES - 12 ASCII DIGITS
DISPLAY_SCALE DISPLAY SCALING
(unsigned 16-bit integer)
MSB indicates the SI units as a power of ten. LSB indicates the F073
number of decimal points to display. HEX8 8 BYTES - 16 ASCII DIGITS
Example: Current values are stored as 32 bit numbers with three
decimal places and base units in Amps. If the retrieved value is
F074
12345.678 A and the display scale equals 0x0302 then the dis-
HEX20 20 BYTES - 40 ASCII DIGITS
played value on the unit is 12.35 kA.

F083
F013
ENUMERATION: SELECTOR MODES
POWER_FACTOR (SIGNED 16 BIT INTEGER)
0 = Time-Out, 1 = Acknowledge
Positive values indicate lagging power factor; negative values
indicate leading.
F084
ENUMERATION: SELECTOR POWER UP
0 = Restore, 1 = Synchronize, 2 = Sync/Restore

B-66 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

F085 F106
ENUMERATION: POWER SWING SHAPE ENUMERATION: PHASE ROTATION
0 = Mho Shape, 1 = Quad Shape 0 = ABC, 1 = ACB

F086 F108
ENUMERATION: DIGITAL INPUT DEFAULT STATE ENUMERATION: OFF/ON
0 = Off, 1 = On, 2= Latest/Off, 3 = Latest/On 0 = Off, 1 = On B
F090 F109
ENUMERATION: LATCHING OUTPUT TYPE ENUMERATION: CONTACT OUTPUT OPERATION
0 = Operate-dominant, 1 = Reset-dominant 0 = Self-reset, 1 = Latched, 2 = Disabled

F100 F110
ENUMERATION: VT CONNECTION TYPE ENUMERATION: CONTACT OUTPUT LED CONTROL
0 = Wye; 1 = Delta 0 = Trip, 1 = Alarm, 2 = None

F101 F111
ENUMERATION: MESSAGE DISPLAY INTENSITY ENUMERATION: UNDERVOLTAGE CURVE SHAPES
0 = 25%, 1 = 50%, 2 = 75%, 3 = 100% 0 = Definite Time, 1 = Inverse Time

F102 F112
ENUMERATION: DISABLED/ENABLED ENUMERATION: RS485 BAUD RATES
0 = Disabled; 1 = Enabled
bitmask value bitmask value bitmask value
0 300 4 9600 8 115200
F103 1 1200 5 19200 9 14400
ENUMERATION: CURVE SHAPES 2 2400 6 38400 10 28800
3 4800 7 57600 11 33600
bitmask curve shape bitmask curve shape
0 IEEE Mod Inv 9 IAC Inverse
1 IEEE Very Inv 10 IAC Short Inv F113
2 IEEE Ext Inv 11 I2t ENUMERATION: PARITY
3 IEC Curve A 12 Definite Time 0 = None, 1 = Odd, 2 = Even
4 IEC Curve B 13 FlexCurve™ A
5 IEC Curve C 14 FlexCurve™ B
F114
6 IEC Short Inv 15 FlexCurve™ C
ENUMERATION: IRIG-B SIGNAL TYPE
7 IAC Ext Inv 16 FlexCurve™ D
0 = None, 1 = DC Shift, 2 = Amplitude Modulated
8 IAC Very Inv

F115
F104
ENUMERATION: BREAKER STATUS
ENUMERATION: RESET TYPE
0 = Auxiliary A, 1 = Auxiliary B
0 = Instantaneous, 1 = Timed, 2 = Linear

F116
F105
ENUMERATION: NEUTRAL OVERVOLTAGE CURVES
ENUMERATION: LOGIC INPUT
0 = Definite Time, 1 = FlexCurve™ A, 2 = FlexCurve™ B,
0 = Disabled, 1 = Input 1, 2 = Input 2
3 = FlexCurve™ C

GE Multilin G60 Generator Protection System B-67


B.4 MEMORY MAPPING APPENDIX B

F117 F123
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS ENUMERATION: CT SECONDARY
0 = 1×72 cycles, 1 = 3×36 cycles, 2 = 7×18 cycles, 3 = 15×9 cycles 0 = 1 A, 1 = 5 A

F118 F124
ENUMERATION: OSCILLOGRAPHY MODE ENUMERATION: LIST OF ELEMENTS
B 0 = Automatic Overwrite, 1 = Protected
bitmask element
0 Phase Instantaneous Overcurrent 1
F119 1 Phase Instantaneous Overcurrent 2
ENUMERATION: FLEXCURVE™ PICKUP RATIOS 2 Phase Instantaneous Overcurrent 3
3 Phase Instantaneous Overcurrent 4
mask value mask value mask value mask value
4 Phase Instantaneous Overcurrent 5
0 0.00 30 0.88 60 2.90 90 5.90
5 Phase Instantaneous Overcurrent 6
1 0.05 31 0.90 61 3.00 91 6.00
6 Phase Instantaneous Overcurrent 7
2 0.10 32 0.91 62 3.10 92 6.50
7 Phase Instantaneous Overcurrent 8
3 0.15 33 0.92 63 3.20 93 7.00
8 Phase Instantaneous Overcurrent 9
4 0.20 34 0.93 64 3.30 94 7.50
9 Phase Instantaneous Overcurrent 10
5 0.25 35 0.94 65 3.40 95 8.00
10 Phase Instantaneous Overcurrent 11
6 0.30 36 0.95 66 3.50 96 8.50
11 Phase Instantaneous Overcurrent 12
7 0.35 37 0.96 67 3.60 97 9.00
16 Phase Time Overcurrent 1
8 0.40 38 0.97 68 3.70 98 9.50
17 Phase Time Overcurrent 2
9 0.45 39 0.98 69 3.80 99 10.00
18 Phase Time Overcurrent 3
10 0.48 40 1.03 70 3.90 100 10.50
19 Phase Time Overcurrent 4
11 0.50 41 1.05 71 4.00 101 11.00
20 Phase Time Overcurrent 5
12 0.52 42 1.10 72 4.10 102 11.50
21 Phase Time Overcurrent 6
13 0.54 43 1.20 73 4.20 103 12.00
24 Phase Directional Overcurrent 1
14 0.56 44 1.30 74 4.30 104 12.50
25 Phase Directional Overcurrent 2
15 0.58 45 1.40 75 4.40 105 13.00
32 Neutral Instantaneous Overcurrent 1
16 0.60 46 1.50 76 4.50 106 13.50
33 Neutral Instantaneous Overcurrent 2
17 0.62 47 1.60 77 4.60 107 14.00
34 Neutral Instantaneous Overcurrent 3
18 0.64 48 1.70 78 4.70 108 14.50
35 Neutral Instantaneous Overcurrent 4
19 0.66 49 1.80 79 4.80 109 15.00
36 Neutral Instantaneous Overcurrent 5
20 0.68 50 1.90 80 4.90 110 15.50
37 Neutral Instantaneous Overcurrent 6
21 0.70 51 2.00 81 5.00 111 16.00
38 Neutral Instantaneous Overcurrent 7
22 0.72 52 2.10 82 5.10 112 16.50
39 Neutral Instantaneous Overcurrent 8
23 0.74 53 2.20 83 5.20 113 17.00
40 Neutral Instantaneous Overcurrent 9
24 0.76 54 2.30 84 5.30 114 17.50
41 Neutral Instantaneous Overcurrent 10
25 0.78 55 2.40 85 5.40 115 18.00
42 Neutral Instantaneous Overcurrent 11
26 0.80 56 2.50 86 5.50 116 18.50
43 Neutral Instantaneous Overcurrent 12
27 0.82 57 2.60 87 5.60 117 19.00
48 Neutral Time Overcurrent 1
28 0.84 58 2.70 88 5.70 118 19.50
49 Neutral Time Overcurrent 2
29 0.86 59 2.80 89 5.80 119 20.00
50 Neutral Time Overcurrent 3
51 Neutral Time Overcurrent 4
F120 52 Neutral Time Overcurrent 5
ENUMERATION: DISTANCE SHAPE 53 Neutral Time Overcurrent 6
0 = Mho, 1 = Quad 56 Neutral Directional Overcurrent 1
57 Neutral Directional Overcurrent 2
60 Negative Sequence Directional Overcurrent 1
F122
61 Negative Sequence Directional Overcurrent 2
ENUMERATION: ELEMENT INPUT SIGNAL TYPE
64 Ground Instantaneous Overcurrent 1
0 = Phasor, 1 = RMS 65 Ground Instantaneous Overcurrent 2
66 Ground Instantaneous Overcurrent 3

B-68 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

bitmask element bitmask element


67 Ground Instantaneous Overcurrent 4 336 Setting Group
68 Ground Instantaneous Overcurrent 5 337 Reset
69 Ground Instantaneous Overcurrent 6 344 Overfrequency 1
70 Ground Instantaneous Overcurrent 7 345 Overfrequency 2
71 Ground Instantaneous Overcurrent 8 346 Overfrequency 3
72 Ground Instantaneous Overcurrent 9 347 Overfrequency 4
73 Ground Instantaneous Overcurrent 10 352 Underfrequency 1 B
74 Ground Instantaneous Overcurrent 11 353 Underfrequency 2
75 Ground Instantaneous Overcurrent 12 354 Underfrequency 3
80 Ground Time Overcurrent 1 355 Underfrequency 4
81 Ground Time Overcurrent 2 356 Underfrequency 5
82 Ground Time Overcurrent 3 357 Underfrequency 6
83 Ground Time Overcurrent 4 388 Selector 1
84 Ground Time Overcurrent 5 389 Selector 2
85 Ground Time Overcurrent 6 390 Control pushbutton 1
86 Restricted Ground Fault 1 391 Control pushbutton 2
87 Restricted Ground Fault 2 392 Control pushbutton 3
88 Restricted Ground Fault 3 393 Control pushbutton 4
89 Restricted Ground Fault 4 394 Control pushbutton 5
90 Restricted Ground Fault 5 395 Control pushbutton 6
91 Restricted Ground Fault 6 396 Control pushbutton 7
101 Opposite Phase Rotation 400 FlexElement™ 1
125 Generator Unbalance 401 FlexElement™ 2
140 Auxiliary Undervoltage 1 402 FlexElement™ 3
144 Phase Undervoltage 1 403 FlexElement™ 4
145 Phase Undervoltage 2 404 FlexElement™ 5
148 Auxiliary Overvoltage 1 405 FlexElement™ 6
152 Phase Overvoltage 1 406 FlexElement™ 7
154 Compensated Overvoltage 1 407 FlexElement™ 8
156 Neutral Overvoltage 1 408 FlexElement™ 9
160 Phase Distance Zone 1 409 FlexElement™ 10
161 Phase Distance Zone 2 410 FlexElement™ 11
162 Phase Distance Zone 3 411 FlexElement™ 12
190 Power Swing Detect 412 FlexElement™ 13
210 Volt per Hertz 1 413 FlexElement™ 14
211 Volt per Hertz 2 414 FlexElement™ 15
214 Sensitive Directional Power 1 415 FlexElement™ 16
215 Sensitive Directional Power 2 420 Non-volatile Latch 1
221 100% Stator Ground 421 Non-volatile Latch 2
222 Split Phase Protection 422 Non-volatile Latch 3
224 SRC1 VT Fuse Failure 423 Non-volatile Latch 4
225 SRC2 VT Fuse Failure 424 Non-volatile Latch 5
226 SRC3 VT Fuse Failure 425 Non-volatile Latch 6
227 SRC4 VT Fuse Failure 426 Non-volatile Latch 7
228 SRC5 VT Fuse Failure 427 Non-volatile Latch 8
229 SRC6 VT Fuse Failure 428 Non-volatile Latch 9
265 Stator Differential 429 Non-volatile Latch 10
296 Accidental Energization 430 Non-volatile Latch 11
300 Loss Of Excitation 431 Non-volatile Latch 12
311 Phasor measurement unit one-shot 432 Non-volatile Latch 13
312 Synchrocheck 1 433 Non-volatile Latch 14
313 Synchrocheck 2 434 Non-volatile Latch 15
330 Third harmonic neutral undervoltage 435 Non-volatile Latch 16

GE Multilin G60 Generator Protection System B-69


B.4 MEMORY MAPPING APPENDIX B

bitmask element bitmask element


530 Frequency Rate of Change 1 733 Digital Element 42
531 Frequency Rate of Change 2 734 Digital Element 43
532 Frequency Rate of Change 3 735 Digital Element 44
533 Frequency Rate of Change 4 736 Digital Element 45
544 Digital Counter 1 737 Digital Element 46
545 Digital Counter 2 738 Digital Element 47
B 546 Digital Counter 3 739 Digital Element 48
547 Digital Counter 4 740 Phasor Measurement Unit 1 Frequency
548 Digital Counter 5 746 Phasor Measurement Unit 1 Voltage
549 Digital Counter 6 752 Phasor Measurement Unit 1 Current
550 Digital Counter 7 758 Phasor Measurement Unit 1 Power
551 Digital Counter 8 764 PMU 1 Rate of Change of Frequency
692 Digital Element 1 770 Phasor Measurement Unit 1
693 Digital Element 2 842 Trip Bus 1
694 Digital Element 3 843 Trip Bus 2
695 Digital Element 4 844 Trip Bus 3
696 Digital Element 5 845 Trip Bus 4
697 Digital Element 6 846 Trip Bus 5
698 Digital Element 7 847 Trip Bus 6
699 Digital Element 8 849 RTD Input 1
700 Digital Element 9 850 RTD Input 2
701 Digital Element 10 851 RTD Input 3
702 Digital Element 11 852 RTD Input 4
703 Digital Element 12 853 RTD Input 5
704 Digital Element 13 854 RTD Input 6
705 Digital Element 14 855 RTD Input 7
706 Digital Element 15 856 RTD Input 8
707 Digital Element 16 857 RTD Input 9
708 Digital Element 17 858 RTD Input 10
709 Digital Element 18 859 RTD Input 11
710 Digital Element 19 860 RTD Input 12
711 Digital Element 20 861 RTD Input 13
712 Digital Element 21 862 RTD Input 14
713 Digital Element 22 863 RTD Input 15
714 Digital Element 23 864 RTD Input 16
715 Digital Element 24 865 RTD Input 17
716 Digital Element 25 866 RTD Input 18
717 Digital Element 26 867 RTD Input 19
718 Digital Element 27 868 RTD Input 20
719 Digital Element 28 869 RTD Input 21
720 Digital Element 29 870 RTD Input 22
721 Digital Element 30 871 RTD Input 23
722 Digital Element 31 872 RTD Input 24
723 Digital Element 32 873 RTD Input 25
724 Digital Element 33 874 RTD Input 26
725 Digital Element 34 875 RTD Input 27
726 Digital Element 35 876 RTD Input 28
727 Digital Element 36 877 RTD Input 29
728 Digital Element 37 878 RTD Input 30
729 Digital Element 38 879 RTD Input 31
730 Digital Element 39 880 RTD Input 32
731 Digital Element 40 881 RTD Input 33
732 Digital Element 41 882 RTD Input 34

B-70 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

bitmask element bitmask element


883 RTD Input 35 971 Breaker 4
884 RTD Input 36 991 Remote RTD Input 1
885 RTD Input 37 992 Remote RTD Input 2
886 RTD Input 38 993 Remote RTD Input 3
887 RTD Input 39 994 Remote RTD Input 4
888 RTD Input 40 995 Remote RTD Input 5
889 RTD Input 41 996 Remote RTD Input 6 B
890 RTD Input 42 997 Remote RTD Input 7
891 RTD Input 43 998 Remote RTD Input 8
892 RTD Input 44 999 Remote RTD Input 9
893 RTD Input 45 1000 Remote RTD Input 10
894 RTD Input 46 1001 Remote RTD Input 11
895 RTD Input 47 1002 Remote RTD Input 12
896 RTD Input 48 1012 Thermal overload protection 1
900 User-Programmable Pushbutton 1 1013 Thermal overload protection 2
901 User-Programmable Pushbutton 2
902 User-Programmable Pushbutton 3
F125
903 User-Programmable Pushbutton 4
ENUMERATION: ACCESS LEVEL
904 User-Programmable Pushbutton 5
0 = Restricted; 1 = Command, 2 = Setting, 3 = Factory Service
905 User-Programmable Pushbutton 6
906 User-Programmable Pushbutton 7
907 User-Programmable Pushbutton 8 F126
908 User-Programmable Pushbutton 9 ENUMERATION: NO/YES CHOICE
909 User-Programmable Pushbutton 10 0 = No, 1 = Yes
910 User-Programmable Pushbutton 11
911 User-Programmable Pushbutton 12
F127
912 User-Programmable Pushbutton 13
ENUMERATION: LATCHED OR SELF-RESETTING
913 User-Programmable Pushbutton 14
914 User-Programmable Pushbutton 15 0 = Latched, 1 = Self-Reset
915 User-Programmable Pushbutton 16
916 Frequency out-of-band accumulation 1 F128
917 Frequency out-of-band accumulation 2 ENUMERATION: CONTACT INPUT THRESHOLD
920 Disconnect switch 1
0 = 17 V DC, 1 = 33 V DC, 2 = 84 V DC, 3 = 166 V DC
921 Disconnect switch 2
922 Disconnect switch 3
923 Disconnect switch 4 F129
ENUMERATION: FLEXLOGIC TIMER TYPE
924 Disconnect switch 5
925 Disconnect switch 6 0 = millisecond, 1 = second, 2 = minute
926 Disconnect switch 7
927 Disconnect switch 8
F130
928 Disconnect switch 9 ENUMERATION: SIMULATION MODE
929 Disconnect switch 10
0 = Off. 1 = Pre-Fault, 2 = Fault, 3 = Post-Fault
930 Disconnect switch 11
931 Disconnect switch 12
932 Disconnect switch 13 F131
933 Disconnect switch 14 ENUMERATION: FORCED CONTACT OUTPUT STATE
934 Disconnect switch 15 0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze
935 Disconnect switch 16
968 Breaker 1
F133
969 Breaker 2
ENUMERATION: PROGRAM STATE
970 Breaker 3
0 = Not Programmed, 1 = Programmed

GE Multilin G60 Generator Protection System B-71


B.4 MEMORY MAPPING APPENDIX B

Bitmask Error
F134
15 Latching Output Discrepancy
ENUMERATION: PASS/FAIL
16 Ethernet Switch Fail
0 = Fail, 1 = OK, 2 = n/a 17 Maintenance Alert 01
18 SNTP Failure

F135 19 ---
ENUMERATION: GAIN CALIBRATION 20 Primary Ethernet Fail
B 0 = 0x1, 1 = 1x16 21 Secondary Ethernet Fail
22 Temperature Monitor
23 Process Bus Trouble
F136 24 Brick Trouble
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS
25 Field RTD Trouble
0 = 31 x 8 cycles, 1 = 15 x 16 cycles, 2 = 7 x 32 cycles 26 Field TDR Trouble
3 = 3 x 64 cycles, 4 = 1 x 128 cycles 27 Remote Device Offline
28 Direct Device Offline

F137 29 Direct Input/Output Ring Break


ENUMERATION: USER-PROGRAMMABLE PUSHBUTTON 30 Any Minor Error
FUNCTION 31 Any Major Error
0 = Disabled, 1 = Self-Reset, 2 = Latched 32 IEC 61850 Data Set
33 ---
34 ---
F138
35 ---
ENUMERATION: OSCILLOGRAPHY FILE TYPE
36 Watchdog Error
0 = Data File, 1 = Configuration File, 2 = Header File 37 Low On Memory
38 ---

F140 43 Module Failure 01


ENUMERATION: CURRENT, SENS CURRENT, VOLTAGE, 44 Module Failure 02
DISABLED 45 Module Failure 03
0 = Disabled, 1 = Current 46 A, 2 = Voltage 280 V, 46 Module Failure 04
3 = Current 4.6 A, 4 = Current 2 A, 5 = Notched 4.6 A, 47 Module Failure 05
6 = Notched 2 A 48 Module Failure 06
49 Module Failure 07
50 Module Failure 08
F141
ENUMERATION: SELF TEST ERRORS 51 Module Failure 09
52 Incompatible Hardware
Bitmask Error 53 Module Failure 10
0 Any Self Tests 54 Module Failure 11
1 IRIG-B Failure 55 Module Failure 12
2 Port 1 Offline
3 Port 2 Offline
4 Port 3 Offline F142
ENUMERATION: EVENT RECORDER ACCESS FILE TYPE
5 Port 4 Offline
6 Port 5 Offline 0 = All Record Data, 1 = Headers Only, 2 = Numeric Event Cause
7 Port 6 Offline
8 RRTD Communcations Failure
F143
9 Voltage Monitor UR_UINT32: 32 BIT ERROR CODE (F141 specifies bit number)
10 FlexLogic Error Token
A bit value of 0 = no error, 1 = error
11 Equipment Mismatch
12 Process Bus Failure
13 Unit Not Programmed F144
14 System Exception ENUMERATION: FORCED CONTACT INPUT STATE
0 = Disabled, 1 = Open, 2 = Closed

B-72 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

bitmask definition
F145
33 System Integrity Recovery 06
ENUMERATION: ALPHABET LETTER
34 System Integrity Recovery 07
bitmask type bitmask type bitmask type bitmask type
0 null 7 G 14 N 21 U
F151
1 A 8 H 15 O 22 V ENUMERATION: RTD SELECTION
2 B 9 I 16 P 23 W
3 C 10 J 17 Q 24 X
bitmask
0
RTD#
NONE
bitmask
17
RTD#
RTD 17
bitmask
33
RTD#
RTD 33
B
4 D 11 K 18 R 25 Y
1 RTD 1 18 RTD 18 34 RTD 34
5 E 12 L 19 S 26 Z
2 RTD 2 19 RTD 19 35 RTD 35
6 F 13 M 20 T
3 RTD 3 20 RTD 20 36 RTD 36
4 RTD 4 21 RTD 21 37 RTD 37
F146 5 RTD 5 22 RTD 22 38 RTD 38
ENUMERATION: MISCELLANEOUS EVENT CAUSES 6 RTD 6 23 RTD 23 39 RTD 39
7 RTD 7 24 RTD 24 40 RTD 40
bitmask definition
8 RTD 8 25 RTD 25 41 RTD 41
0 Events Cleared
9 RTD 9 26 RTD 26 42 RTD 42
1 Oscillography Triggered
10 RTD 10 27 RTD 27 43 RTD 43
2 Date/time Changed
11 RTD 11 28 RTD 28 44 RTD 44
3 Default Settings Loaded
12 RTD 12 29 RTD 29 45 RTD 45
4 Test Mode Forcing On
13 RTD 13 30 RTD 30 46 RTD 46
5 Test Mode Forcing Off
14 RTD 14 31 RTD 31 47 RTD 47
6 Power On
15 RTD 15 32 RTD 32 48 RTD 48
7 Power Off
16 RTD 16
8 Relay In Service
9 Relay Out Of Service
10 Watchdog Reset F152
11 Oscillography Clear ENUMERATION: SETTING GROUP
12 Reboot Command 0 = Active Group, 1 = Group 1, 2 = Group 2, 3 = Group 3
13 Led Test Initiated 4 = Group 4, 5 = Group 5, 6 = Group 6
14 Flash Programming
15 Fault Report Trigger
F153
16 User Programmable Fault Report Trigger
ENUMERATION: DISTANCE TRANSFORMER CONNECTION
17 ---
bitmask type bitmask type bitmask type
18 Reload CT/VT module Settings
0 None 5 Dy9 10 Yd7
19 ---
1 Dy1 6 Dy11 11 Yd9
20 Ethernet Port 1 Offline
2 Dy3 7 Yd1 12 Yd11
21 Ethernet Port 2 Offline
3 Dy5 8 Yd3
22 Ethernet Port 3 Offline
4 Dy7 9 Yd5
23 Ethernet Port 4 Offline
24 Ethernet Port 5 Offline
25 Ethernet Port 6 Offline
F154
26 Test Mode Isolated ENUMERATION: DISTANCE DIRECTION
27 Test Mode Forcible
0 = Forward, 1 = Reverse, 2 = Non-Directional
28 Test Mode Disabled
29 Temperature Warning On
30 Temperature Warning Off F155
31 Unauthorized Access ENUMERATION: REMOTE DEVICE STATE
32 System Integrity Recovery 0 = Offline, 1 = Online

GE Multilin G60 Generator Protection System B-73


B.4 MEMORY MAPPING APPENDIX B

F156 F167
ENUMERATION: REMOTE INPUT BIT PAIRS ENUMERATION: SIGNAL SOURCE
0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4,
bitmask value bitmask value
4 = SRC 5, 5 = SRC 6
0 NONE 35 UserSt-3
1 DNA-1 36 UserSt-4
2 DNA-2 37 UserSt-5 F168
B 3 DNA-3 38 UserSt-6 ENUMERATION: INRUSH INHIBIT FUNCTION
4 DNA-4 39 UserSt-7 0 = Disabled, 1 = Adapt. 2nd, 2 = Trad. 2nd
5 DNA-5 40 UserSt-8
6 DNA-6 41 UserSt-9
F170
7 DNA-7 42 UserSt-10
ENUMERATION: LOW/HIGH OFFSET and GAIN
8 DNA-8 43 UserSt-11 TRANSDUCER INPUT/OUTPUT SELECTION
9 DNA-9 44 UserSt-12
0 = LOW, 1 = HIGH
10 DNA-10 45 UserSt-13
11 DNA-11 46 UserSt-14
12 DNA-12 47 UserSt-15 F171
13 DNA-13 48 UserSt-16 ENUMERATION: TRANSDUCER CHANNEL INPUT TYPE
14 DNA-14 49 UserSt-17 0 = dcmA IN, 1 = Ohms IN, 2 = RTD IN, 3 = dcmA OUT,
15 DNA-15 50 UserSt-18 4 = RRTD IN
16 DNA-16 51 UserSt-19
17 DNA-17 52 UserSt-20
F172
18 DNA-18 53 UserSt-21 ENUMERATION: SLOT LETTERS
19 DNA-19 54 UserSt-22
20 DNA-20 55 UserSt-23 bitmask slot bitmask slot bitmask slot bitmask slot

21 DNA-21 56 UserSt-24 0 F 4 K 8 P 12 U

22 DNA-22 57 UserSt-25 1 G 5 L 9 R 13 V

23 DNA-23 58 UserSt-26 2 H 6 M 10 S 14 W

24 DNA-24 59 UserSt-27 3 J 7 N 11 T 15 X

25 DNA-25 60 UserSt-28
26 DNA-26 61 UserSt-29
F173
27 DNA-27 62 UserSt-30 ENUMERATION: DCMA INPUT/OUTPUT RANGE
28 DNA-28 63 UserSt-31
29 DNA-29 64 UserSt-32 bitmask dcmA input/output range

30 DNA-30 65 Dataset Item 1 0 0 to –1 mA

31 DNA-31 66 Dataset Item 2 1 0 to 1 mA

32 DNA-32 67 Dataset Item 3 2 –1 to 1 mA

33 UserSt-1 ↓ ↓ 3 0 to 5 mA

34 UserSt-2 96 Dataset Item 32 4 0 to 10 mA


5 0 to 20 mA
6 4 to 20 mA
F157
ENUMERATION: BREAKER MODE
0 = 3-Pole, 1 = 1-Pole F174
ENUMERATION: TRANSDUCER RTD INPUT TYPE
0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel,
F159 2 = 100 Ohm Nickel, 3 = 10 Ohm Copper
ENUMERATION: BREAKER AUX CONTACT KEYING
0 = 52a, 1 = 52b, 2 = None
F175
ENUMERATION: PHASE LETTERS
F166 0 = A, 1 = B, 2 = C
ENUMERATION: AUXILIARY VT CONNECTION TYPE
0 = Vn, 1 = Vag, 2 = Vbg, 3 = Vcg, 4 = Vab, 5 = Vbc, 6 = Vca

B-74 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

F176 F184
ENUMERATION: SYNCHROCHECK DEAD SOURCE SELECT ENUMERATION: REMOTE DEVICE GOOSE DATASET

bitmask synchrocheck dead source value GOOSE dataset


0 None 0 Off
1 LV1 and DV2 1 GooseIn 1
2 DV1 and LV2 2 GooseIn 2
3 DV1 or DV2 3 GooseIn 3 B
4 DV1 Xor DV2 4 GooseIn 4
5 DV1 and DV2 5 GooseIn 5
6 GooseIn 6
7 GooseIn 7
F177
8 GooseIn 8
ENUMERATION: COMMUNICATION PORT
9 GooseIn 9
0 = None, 1 = COM1-RS485, 2 = COM2-RS485,
10 GooseIn 10
3 = Front Panel-RS232, 4 = Network - TCP, 5 = Network - UDP
11 GooseIn 11
12 GooseIn 12
F178 13 GooseIn 13
ENUMERATION: DATA LOGGER RATES 14 GooseIn 14
0 = 1 sec, 1 = 1 min, 2 = 5 min, 3 = 10 min, 4 = 15 min, 15 GooseIn 15
5 = 20 min, 6 = 30 min, 7 = 60 min, 8 = 15 ms, 9 = 30 ms, 16 GooseIn 16
10 = 100 ms, 11 = 500 ms

F185
F179 ENUMERATION: PHASE A,B,C, GROUND SELECTOR
ENUMERATION: NEGATIVE SEQUENCE DIRECTIONAL
OVERCURRENT TYPE 0 = A, 1 = B, 2 = C, 3 = G

0 = Neg Sequence, 1 = Zero Sequence


F186
ENUMERATION: MEASUREMENT MODE
F180
ENUMERATION: PHASE/GROUND 0 = Phase to Ground, 1 = Phase to Phase

0 = PHASE, 1 = GROUND
F190
ENUMERATION: SIMULATED KEYPRESS
F181
ENUMERATION: ODD/EVEN/NONE bitmsk keypress bitmsk keypress
0 = ODD, 1 = EVEN, 2 = NONE 0 --- 23 Reset
use between real keys
24 User 1
1 1 25 User 2
F183
2 2 26 User 3
ENUMERATION: AC INPUT WAVEFORMS
3 3 27 User-programmable key 1

bitmask definition 4 4 28 User-programmable key 2

0 Off 5 5 29 User-programmable key 3

1 8 samples/cycle 6 6 30 User-programmable key 4

2 16 samples/cycle 7 7 31 User-programmable key 5

3 32 samples/cycle 8 8 32 User-programmable key 6

4 64 samples/cycle 9 9 33 User-programmable key 7


10 0 34 User-programmable key 8
11 Decimal Point 35 User-programmable key 9
12 Plus/Minus 36 User-programmable key 10
13 Value Up 37 User-programmable key 11
14 Value Down 38 User-programmable key 12
15 Message Up 43 User-programmable key 13
16 Message Down 44 User-programmable key 14

GE Multilin G60 Generator Protection System B-75


B.4 MEMORY MAPPING APPENDIX B

bitmsk keypress bitmsk keypress


F205
17 Message Left 45 User-programmable key 15
TEXT12: 12-CHARACTER ASCII TEXT
18 Message Right 46 User-programmable key 16
19 Menu 47 User 4 (control pushbutton)
20 Help 48 User 5 (control pushbutton) F206
21 Escape 49 User 6 (control pushbutton) TEXT6: 6-CHARACTER ASCII TEXT
22 --- 50 User 7 (control pushbutton)
B F207
TEXT4: 4-CHARACTER ASCII TEXT
F192
ENUMERATION: ETHERNET OPERATION MODE
0 = Half-Duplex, 1 = Full-Duplex F208
TEXT2: 2-CHARACTER ASCII TEXT

F193
ENUMERATION: ACCIDENTAL ENERG. ARMING MODE F213
0 = UV and Offline, 1 = UV or Offline TEXT32: 32-CHARACTER ASCII TEXT

F194 F220
ENUMERATION: PUSHBUTTON MESSAGE PRIORITY
ENUMERATION: DNP SCALE
0 = 0.01, 1 = 0.1, 2 = 1, 3 = 10, 4 = 100, 5 = 1000, 6 = 10000, value priority
7 = 100000, 8 = 0.001 0 Disabled
1 Normal

F196 2 High Priority


ENUMERATION: NEUTRAL DIRECTIONAL OVERCURRENT
OPERATING CURRENT
F222
0 = Calculated 3I0, 1 = Measured IG ENUMERATION: TEST ENUMERATION
0 = Test Enumeration 0, 1 = Test Enumeration 1
F199
ENUMERATION: DISABLED/ENABLED/CUSTOM
F224
0 = Disabled, 1 = Enabled, 2 = Custom ENUMERATION: RATE TREND FOR FREQ RATE OF CHANGE
0 = Increasing, 1 = Decreasing, 2 = Bidirectional
F200
TEXT40: 40-CHARACTER ASCII TEXT
F225
20 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB ENUMERATION: SPLIT PHASE PROTECTION MODE
0 = Over, 1 = Over-Under
F201
TEXT8: 8-CHARACTER ASCII PASSCODE
F226
4 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB ENUMERATION: REMOTE INPUT/OUTPUT TRANSFER
METHOD

F202 0 = None, 1 = GSSE, 2 = GOOSE


TEXT20: 20-CHARACTER ASCII TEXT
10 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB F227
ENUMERATION: RELAY SERVICE STATUS

F203 0 = Unknown, 1 = Relay In Service, 2 = Relay Out Of Service


TEXT16: 16-CHARACTER ASCII TEXT

F230
F204 ENUMERATION: DIRECTIONAL POLARIZING
TEXT80: 80-CHARACTER ASCII TEXT 0 = Voltage, 1 = Current, 2 = Dual

B-76 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

value GOOSE dataset item


F231
293 MMXU1.MX.PF.phsC.cVal.mag.f
ENUMERATION: POLARIZING VOLTAGE
294 MMXU2.MX.TotW.mag.f
0 = Calculated V0, 1 = Measured VX 295 MMXU2.MX.TotVAr.mag.f
296 MMXU2.MX.TotVA.mag.f

F232 297 MMXU2.MX.TotPF.mag.f


ENUMERATION: CONFIGURABLE GOOSE DATASET ITEMS 298 MMXU2.MX.Hz.mag.f
FOR TRANSMISSION 299 MMXU2.MX.PPV.phsAB.cVal.mag.f B
300 MMXU2.MX.PPV.phsAB.cVal.ang.f
value GOOSE dataset item
301 MMXU2.MX.PPV.phsBC.cVal.mag.f
0 None
302 MMXU2.MX.PPV.phsBC.cVal.ang.f
1 GGIO1.ST.Ind1.q
303 MMXU2.MX.PPV.phsCA.cVal.mag.f
2 GGIO1.ST.Ind1.stVal
304 MMXU2.MX.PPV.phsCA.cVal.ang.f
3 GGIO1.ST.Ind2.q
305 MMXU2.MX.PhV.phsA.cVal.mag.f
4 GGIO1.ST.Ind2.stVal
306 MMXU2.MX.PhV.phsA.cVal.ang.f
↓ ↓
307 MMXU2.MX.PhV.phsB.cVal.mag.f
255 GGIO1.ST.Ind128.q
308 MMXU2.MX.PhV.phsB.cVal.ang.f
256 GGIO1.ST.Ind128.stVal
309 MMXU2.MX.PhV.phsC.cVal.mag.f
257 MMXU1.MX.TotW.mag.f
310 MMXU2.MX.PhV.phsC.cVal.ang.f
258 MMXU1.MX.TotVAr.mag.f
311 MMXU2.MX.A.phsA.cVal.mag.f
259 MMXU1.MX.TotVA.mag.f
312 MMXU2.MX.A.phsA.cVal.ang.f
260 MMXU1.MX.TotPF.mag.f
313 MMXU2.MX.A.phsB.cVal.mag.f
261 MMXU1.MX.Hz.mag.f
314 MMXU2.MX.A.phsB.cVal.ang.f
262 MMXU1.MX.PPV.phsAB.cVal.mag.f
315 MMXU2.MX.A.phsC.cVal.mag.f
263 MMXU1.MX.PPV.phsAB.cVal.ang.f
316 MMXU2.MX.A.phsC.cVal.ang.f
264 MMXU1.MX.PPV.phsBC.cVal.mag.f
317 MMXU2.MX.A.neut.cVal.mag.f
265 MMXU1.MX.PPV.phsBC.cVal.ang.f
318 MMXU2.MX.A.neut.cVal.ang.f
266 MMXU1.MX.PPV.phsCA.cVal.mag.f
319 MMXU2.MX.W.phsA.cVal.mag.f
267 MMXU1.MX.PPV.phsCA.cVal.ang.f
320 MMXU2.MX.W.phsB.cVal.mag.f
268 MMXU1.MX.PhV.phsA.cVal.mag.f
321 MMXU2.MX.W.phsC.cVal.mag.f
269 MMXU1.MX.PhV.phsA.cVal.ang.f
322 MMXU2.MX.VAr.phsA.cVal.mag.f
270 MMXU1.MX.PhV.phsB.cVal.mag.f
323 MMXU2.MX.VAr.phsB.cVal.mag.f
271 MMXU1.MX.PhV.phsB.cVal.ang.f
324 MMXU2.MX.VAr.phsC.cVal.mag.f
272 MMXU1.MX.PhV.phsC.cVal.mag.f
325 MMXU2.MX.VA.phsA.cVal.mag.f
273 MMXU1.MX.PhV.phsC.cVal.ang.f
326 MMXU2.MX.VA.phsB.cVal.mag.f
274 MMXU1.MX.A.phsA.cVal.mag.f
327 MMXU2.MX.VA.phsC.cVal.mag.f
275 MMXU1.MX.A.phsA.cVal.ang.f
328 MMXU2.MX.PF.phsA.cVal.mag.f
276 MMXU1.MX.A.phsB.cVal.mag.f
329 MMXU2.MX.PF.phsB.cVal.mag.f
277 MMXU1.MX.A.phsB.cVal.ang.f
330 MMXU2.MX.PF.phsC.cVal.mag.f
278 MMXU1.MX.A.phsC.cVal.mag.f
331 MMXU3.MX.TotW.mag.f
279 MMXU1.MX.A.phsC.cVal.ang.f
332 MMXU3.MX.TotVAr.mag.f
280 MMXU1.MX.A.neut.cVal.mag.f
333 MMXU3.MX.TotVA.mag.f
281 MMXU1.MX.A.neut.cVal.ang.f
334 MMXU3.MX.TotPF.mag.f
282 MMXU1.MX.W.phsA.cVal.mag.f
335 MMXU3.MX.Hz.mag.f
283 MMXU1.MX.W.phsB.cVal.mag.f
336 MMXU3.MX.PPV.phsAB.cVal.mag.f
284 MMXU1.MX.W.phsC.cVal.mag.f
337 MMXU3.MX.PPV.phsAB.cVal.ang.f
285 MMXU1.MX.VAr.phsA.cVal.mag.f
338 MMXU3.MX.PPV.phsBC.cVal.mag.f
286 MMXU1.MX.VAr.phsB.cVal.mag.f
339 MMXU3.MX.PPV.phsBC.cVal.ang.f
287 MMXU1.MX.VAr.phsC.cVal.mag.f
340 MMXU3.MX.PPV.phsCA.cVal.mag.f
288 MMXU1.MX.VA.phsA.cVal.mag.f
341 MMXU3.MX.PPV.phsCA.cVal.ang.f
289 MMXU1.MX.VA.phsB.cVal.mag.f
342 MMXU3.MX.PhV.phsA.cVal.mag.f
290 MMXU1.MX.VA.phsC.cVal.mag.f
343 MMXU3.MX.PhV.phsA.cVal.ang.f
291 MMXU1.MX.PF.phsA.cVal.mag.f
344 MMXU3.MX.PhV.phsB.cVal.mag.f
292 MMXU1.MX.PF.phsB.cVal.mag.f
345 MMXU3.MX.PhV.phsB.cVal.ang.f

GE Multilin G60 Generator Protection System B-77


B.4 MEMORY MAPPING APPENDIX B

value GOOSE dataset item value GOOSE dataset item


346 MMXU3.MX.PhV.phsC.cVal.mag.f 399 MMXU4.MX.VA.phsA.cVal.mag.f
347 MMXU3.MX.PhV.phsC.cVal.ang.f 400 MMXU4.MX.VA.phsB.cVal.mag.f
348 MMXU3.MX.A.phsA.cVal.mag.f 401 MMXU4.MX.VA.phsC.cVal.mag.f
349 MMXU3.MX.A.phsA.cVal.ang.f 402 MMXU4.MX.PF.phsA.cVal.mag.f
350 MMXU3.MX.A.phsB.cVal.mag.f 403 MMXU4.MX.PF.phsB.cVal.mag.f
351 MMXU3.MX.A.phsB.cVal.ang.f 404 MMXU4.MX.PF.phsC.cVal.mag.f
B 352 MMXU3.MX.A.phsC.cVal.mag.f 405 MMXU5.MX.TotW.mag.f
353 MMXU3.MX.A.phsC.cVal.ang.f 406 MMXU5.MX.TotVAr.mag.f
354 MMXU3.MX.A.neut.cVal.mag.f 407 MMXU5.MX.TotVA.mag.f
355 MMXU3.MX.A.neut.cVal.ang.f 408 MMXU5.MX.TotPF.mag.f
356 MMXU3.MX.W.phsA.cVal.mag.f 409 MMXU5.MX.Hz.mag.f
357 MMXU3.MX.W.phsB.cVal.mag.f 410 MMXU5.MX.PPV.phsAB.cVal.mag.f
358 MMXU3.MX.W.phsC.cVal.mag.f 411 MMXU5.MX.PPV.phsAB.cVal.ang.f
359 MMXU3.MX.VAr.phsA.cVal.mag.f 412 MMXU5.MX.PPV.phsBC.cVal.mag.f
360 MMXU3.MX.VAr.phsB.cVal.mag.f 413 MMXU5.MX.PPV.phsBC.cVal.ang.f
361 MMXU3.MX.VAr.phsC.cVal.mag.f 414 MMXU5.MX.PPV.phsCA.cVal.mag.f
362 MMXU3.MX.VA.phsA.cVal.mag.f 415 MMXU5.MX.PPV.phsCA.cVal.ang.f
363 MMXU3.MX.VA.phsB.cVal.mag.f 416 MMXU5.MX.PhV.phsA.cVal.mag.f
364 MMXU3.MX.VA.phsC.cVal.mag.f 417 MMXU5.MX.PhV.phsA.cVal.ang.f
365 MMXU3.MX.PF.phsA.cVal.mag.f 418 MMXU5.MX.PhV.phsB.cVal.mag.f
366 MMXU3.MX.PF.phsB.cVal.mag.f 419 MMXU5.MX.PhV.phsB.cVal.ang.f
367 MMXU3.MX.PF.phsC.cVal.mag.f 420 MMXU5.MX.PhV.phsC.cVal.mag.f
368 MMXU4.MX.TotW.mag.f 421 MMXU5.MX.PhV.phsC.cVal.ang.f
369 MMXU4.MX.TotVAr.mag.f 422 MMXU5.MX.A.phsA.cVal.mag.f
370 MMXU4.MX.TotVA.mag.f 423 MMXU5.MX.A.phsA.cVal.ang.f
371 MMXU4.MX.TotPF.mag.f 424 MMXU5.MX.A.phsB.cVal.mag.f
372 MMXU4.MX.Hz.mag.f 425 MMXU5.MX.A.phsB.cVal.ang.f
373 MMXU4.MX.PPV.phsAB.cVal.mag.f 426 MMXU5.MX.A.phsC.cVal.mag.f
374 MMXU4.MX.PPV.phsAB.cVal.ang.f 427 MMXU5.MX.A.phsC.cVal.ang.f
375 MMXU4.MX.PPV.phsBC.cVal.mag.f 428 MMXU5.MX.A.neut.cVal.mag.f
376 MMXU4.MX.PPV.phsBC.cVal.ang.f 429 MMXU5.MX.A.neut.cVal.ang.f
377 MMXU4.MX.PPV.phsCA.cVal.mag.f 430 MMXU5.MX.W.phsA.cVal.mag.f
378 MMXU4.MX.PPV.phsCA.cVal.ang.f 431 MMXU5.MX.W.phsB.cVal.mag.f
379 MMXU4.MX.PhV.phsA.cVal.mag.f 432 MMXU5.MX.W.phsC.cVal.mag.f
380 MMXU4.MX.PhV.phsA.cVal.ang.f 433 MMXU5.MX.VAr.phsA.cVal.mag.f
381 MMXU4.MX.PhV.phsB.cVal.mag.f 434 MMXU5.MX.VAr.phsB.cVal.mag.f
382 MMXU4.MX.PhV.phsB.cVal.ang.f 435 MMXU5.MX.VAr.phsC.cVal.mag.f
383 MMXU4.MX.PhV.phsC.cVal.mag.f 436 MMXU5.MX.VA.phsA.cVal.mag.f
384 MMXU4.MX.PhV.phsC.cVal.ang.f 437 MMXU5.MX.VA.phsB.cVal.mag.f
385 MMXU4.MX.A.phsA.cVal.mag.f 438 MMXU5.MX.VA.phsC.cVal.mag.f
386 MMXU4.MX.A.phsA.cVal.ang.f 439 MMXU5.MX.PF.phsA.cVal.mag.f
387 MMXU4.MX.A.phsB.cVal.mag.f 440 MMXU5.MX.PF.phsB.cVal.mag.f
388 MMXU4.MX.A.phsB.cVal.ang.f 441 MMXU5.MX.PF.phsC.cVal.mag.f
389 MMXU4.MX.A.phsC.cVal.mag.f 442 MMXU6.MX.TotW.mag.f
390 MMXU4.MX.A.phsC.cVal.ang.f 443 MMXU6.MX.TotVAr.mag.f
391 MMXU4.MX.A.neut.cVal.mag.f 444 MMXU6.MX.TotVA.mag.f
392 MMXU4.MX.A.neut.cVal.ang.f 445 MMXU6.MX.TotPF.mag.f
393 MMXU4.MX.W.phsA.cVal.mag.f 446 MMXU6.MX.Hz.mag.f
394 MMXU4.MX.W.phsB.cVal.mag.f 447 MMXU6.MX.PPV.phsAB.cVal.mag.f
395 MMXU4.MX.W.phsC.cVal.mag.f 448 MMXU6.MX.PPV.phsAB.cVal.ang.f
396 MMXU4.MX.VAr.phsA.cVal.mag.f 449 MMXU6.MX.PPV.phsBC.cVal.mag.f
397 MMXU4.MX.VAr.phsB.cVal.mag.f 450 MMXU6.MX.PPV.phsBC.cVal.ang.f
398 MMXU4.MX.VAr.phsC.cVal.mag.f 451 MMXU6.MX.PPV.phsCA.cVal.mag.f

B-78 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

value GOOSE dataset item value GOOSE dataset item


452 MMXU6.MX.PPV.phsCA.cVal.ang.f 505 GGIO4.MX.AnIn27.mag.f
453 MMXU6.MX.PhV.phsA.cVal.mag.f 506 GGIO4.MX.AnIn28.mag.f
454 MMXU6.MX.PhV.phsA.cVal.ang.f 507 GGIO4.MX.AnIn29.mag.f
455 MMXU6.MX.PhV.phsB.cVal.mag.f 508 GGIO4.MX.AnIn30.mag.f
456 MMXU6.MX.PhV.phsB.cVal.ang.f 509 GGIO4.MX.AnIn31.mag.f
457 MMXU6.MX.PhV.phsC.cVal.mag.f 510 GGIO4.MX.AnIn32.mag.f
458 MMXU6.MX.PhV.phsC.cVal.ang.f 511 GGIO5.ST.UIntIn1.q B
459 MMXU6.MX.A.phsA.cVal.mag.f 512 GGIO5.ST.UIntIn1.stVal
460 MMXU6.MX.A.phsA.cVal.ang.f 513 GGIO5.ST.UIntIn2.q
461 MMXU6.MX.A.phsB.cVal.mag.f 514 GGIO5.ST.UIntIn2.stVal
462 MMXU6.MX.A.phsB.cVal.ang.f 515 GGIO5.ST.UIntIn3.q
463 MMXU6.MX.A.phsC.cVal.mag.f 516 GGIO5.ST.UIntIn3.stVal
464 MMXU6.MX.A.phsC.cVal.ang.f 517 GGIO5.ST.UIntIn4.q
465 MMXU6.MX.A.neut.cVal.mag.f 518 GGIO5.ST.UIntIn4.stVal
466 MMXU6.MX.A.neut.cVal.ang.f 519 GGIO5.ST.UIntIn5.q
467 MMXU6.MX.W.phsA.cVal.mag.f 520 GGIO5.ST.UIntIn5.stVal
468 MMXU6.MX.W.phsB.cVal.mag.f 521 GGIO5.ST.UIntIn6.q
469 MMXU6.MX.W.phsC.cVal.mag.f 522 GGIO5.ST.UIntIn6.stVal
470 MMXU6.MX.VAr.phsA.cVal.mag.f 523 GGIO5.ST.UIntIn7.q
471 MMXU6.MX.VAr.phsB.cVal.mag.f 524 GGIO5.ST.UIntIn7.stVal
472 MMXU6.MX.VAr.phsC.cVal.mag.f 525 GGIO5.ST.UIntIn8.q
473 MMXU6.MX.VA.phsA.cVal.mag.f 526 GGIO5.ST.UIntIn8.stVal
474 MMXU6.MX.VA.phsB.cVal.mag.f 527 GGIO5.ST.UIntIn9.q
475 MMXU6.MX.VA.phsC.cVal.mag.f 528 GGIO5.ST.UIntIn9.stVal
476 MMXU6.MX.PF.phsA.cVal.mag.f 529 GGIO5.ST.UIntIn10.q
477 MMXU6.MX.PF.phsB.cVal.mag.f 530 GGIO5.ST.UIntIn10.stVal
478 MMXU6.MX.PF.phsC.cVal.mag.f 531 GGIO5.ST.UIntIn11.q
479 GGIO4.MX.AnIn1.mag.f 532 GGIO5.ST.UIntIn11.stVal
480 GGIO4.MX.AnIn2.mag.f 533 GGIO5.ST.UIntIn12.q
481 GGIO4.MX.AnIn3.mag.f 534 GGIO5.ST.UIntIn12.stVal
482 GGIO4.MX.AnIn4.mag.f 535 GGIO5.ST.UIntIn13.q
483 GGIO4.MX.AnIn5.mag.f 536 GGIO5.ST.UIntIn13.stVal
484 GGIO4.MX.AnIn6.mag.f 537 GGIO5.ST.UIntIn14.q
485 GGIO4.MX.AnIn7.mag.f 538 GGIO5.ST.UIntIn14.stVal
486 GGIO4.MX.AnIn8.mag.f 539 GGIO5.ST.UIntIn15.q
487 GGIO4.MX.AnIn9.mag.f 540 GGIO5.ST.UIntIn15.stVal
488 GGIO4.MX.AnIn10.mag.f 541 GGIO5.ST.UIntIn16.q
489 GGIO4.MX.AnIn11.mag.f 542 GGIO5.ST.UIntIn16.stVal
490 GGIO4.MX.AnIn12.mag.f
491 GGIO4.MX.AnIn13.mag.f
F233
492 GGIO4.MX.AnIn14.mag.f
ENUMERATION: CONFIGURABLE GOOSE DATASET ITEMS
493 GGIO4.MX.AnIn15.mag.f FOR RECEPTION
494 GGIO4.MX.AnIn16.mag.f
495 GGIO4.MX.AnIn17.mag.f value GOOSE dataset item

496 GGIO4.MX.AnIn18.mag.f 0 None

497 GGIO4.MX.AnIn19.mag.f 1 GGIO3.ST.Ind1.q

498 GGIO4.MX.AnIn20.mag.f 2 GGIO3.ST.Ind1.stVal

499 GGIO4.MX.AnIn21.mag.f 3 GGIO3.ST.Ind2.q

500 GGIO4.MX.AnIn22.mag.f 4 GGIO3.ST.Ind2.stVal

501 GGIO4.MX.AnIn23.mag.f ↓ ↓

502 GGIO4.MX.AnIn24.mag.f 127 GGIO1.ST.Ind64q

503 GGIO4.MX.AnIn25.mag.f 128 GGIO1.ST.Ind64.stVal

504 GGIO4.MX.AnIn26.mag.f 129 GGIO3.MX.AnIn1.mag.f

GE Multilin G60 Generator Protection System B-79


B.4 MEMORY MAPPING APPENDIX B

value GOOSE dataset item value GOOSE dataset item


130 GGIO3.MX.AnIn2.mag.f 183 GGIO3.ST.UIntIn9.stVal
131 GGIO3.MX.AnIn3.mag.f 184 GGIO3.ST.UIntIn10.q
132 GGIO3.MX.AnIn4.mag.f 185 GGIO3.ST.UIntIn10.stVal
133 GGIO3.MX.AnIn5.mag.f 186 GGIO3.ST.UIntIn11.q
134 GGIO3.MX.AnIn6.mag.f 187 GGIO3.ST.UIntIn11.stVal
135 GGIO3.MX.AnIn7.mag.f 188 GGIO3.ST.UIntIn12.q
B 136 GGIO3.MX.AnIn8.mag.f 189 GGIO3.ST.UIntIn12.stVal
137 GGIO3.MX.AnIn9.mag.f 190 GGIO3.ST.UIntIn13.q
138 GGIO3.MX.AnIn10.mag.f 191 GGIO3.ST.UIntIn13.stVal
139 GGIO3.MX.AnIn11.mag.f 192 GGIO3.ST.UIntIn14.q
140 GGIO3.MX.AnIn12.mag.f 193 GGIO3.ST.UIntIn14.stVal
141 GGIO3.MX.AnIn13.mag.f 194 GGIO3.ST.UIntIn15.q
142 GGIO3.MX.AnIn14.mag.f 195 GGIO3.ST.UIntIn15.stVal
143 GGIO3.MX.AnIn15.mag.f 196 GGIO3.ST.UIntIn16.q
144 GGIO3.MX.AnIn16.mag.f 197 GGIO3.ST.UIntIn16.stVal
145 GGIO3.MX.AnIn17.mag.f
146 GGIO3.MX.AnIn18.mag.f
F237
147 GGIO3.MX.AnIn19.mag.f
ENUMERATION: REAL TIME CLOCK MONTH
148 GGIO3.MX.AnIn20.mag.f
149 GGIO3.MX.AnIn21.mag.f value month
150 GGIO3.MX.AnIn22.mag.f 0 January
151 GGIO3.MX.AnIn23.mag.f 1 February
152 GGIO3.MX.AnIn24.mag.f 2 March
153 GGIO3.MX.AnIn25.mag.f 3 April
154 GGIO3.MX.AnIn26.mag.f 4 May
155 GGIO3.MX.AnIn27.mag.f 5 June
156 GGIO3.MX.AnIn28.mag.f 6 July
157 GGIO3.MX.AnIn29.mag.f 7 August
158 GGIO3.MX.AnIn30.mag.f 8 September
159 GGIO3.MX.AnIn31.mag.f 9 October
160 GGIO3.MX.AnIn32.mag.f 10 November
161 GGIO3.ST.IndPos1.stVal 11 December
162 GGIO3.ST.IndPos2.stVal
163 GGIO3.ST.IndPos3.stVal
F238
164 GGIO3.ST.IndPos4.stVal
ENUMERATION: REAL TIME CLOCK DAY
165 GGIO3.ST.IndPos5.stVal
166 GGIO3.ST.UIntIn1.q value day
167 GGIO3.ST.UIntIn1.stVal 0 Sunday
168 GGIO3.ST.UIntIn2.q 1 Monday
169 GGIO3.ST.UIntIn2.stVal 2 Tuesday
170 GGIO3.ST.UIntIn3.q 3 Wednesday
171 GGIO3.ST.UIntIn3.stVal 4 Thursday
172 GGIO3.ST.UIntIn4.q 5 Friday
173 GGIO3.ST.UIntIn4.stVal 6 Saturday
174 GGIO3.ST.UIntIn5.q
175 GGIO3.ST.UIntIn5.stVal
F239
176 GGIO3.ST.UIntIn6.q
ENUMERATION: REAL TIME CLOCK DAYLIGHT SAVINGS
177 GGIO3.ST.UIntIn6.stVal
TIME START DAY INSTANCE
178 GGIO3.ST.UIntIn7.q
179 GGIO3.ST.UIntIn7.stVal value instance
180 GGIO3.ST.UIntIn8.q 0 First
181 GGIO3.ST.UIntIn8.stVal 1 Second
182 GGIO3.ST.UIntIn9.q 2 Third

B-80 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

value instance [42] AND (2 to 16 inputs)


[44] NOR (2 to 16 inputs)
3 Fourth
[46] NAND (2 to 16 inputs)
4 Last
[48] TIMER (1 to 32)
[50] ASSIGN VIRTUAL OUTPUT (1 to 96)
[52] SELF-TEST ERROR (see F141 for range)
F240
[56] ACTIVE SETTING GROUP (1 to 6)
ENUMERATION: V/HZ CURVES
[62] MISCELLANEOUS EVENTS (see F146 for range)
0 = Definite Time, 1 = Inverse A, 2 = Inverse B, 3 = Inverse C,
4 = FlexCurve™ A, 5 = FlexCurve™ B, 6 = FlexCurve™ C,
[64 to 127] ELEMENT STATES
B
7 = FlexCurve™ D
F400
UR_UINT16: CT/VT BANK SELECTION
F254 bitmask bank selection
ENUMERATION: TEST MODE FUNCTION
0 Card 1 Contact 1 to 4

Value Function 1 Card 1 Contact 5 to 8

0 Disabled 2 Card 2 Contact 1 to 4

1 Isolated 3 Card 2 Contact 5 to 8

2 Forcible 4 Card 3 Contact 1 to 4


5 Card 3 Contact 5 to 8

F260
ENUMERATION: DATA LOGGER MODE F491
ENUMERATION: ANALOG INPUT MODE
0 = Continuous, 1 = Trigger
0 = Default Value, 1 = Last Known

F300
UR_UINT16: FLEXLOGIC™ BASE TYPE (6-bit type)
F500
The FlexLogic™ BASE type is 6 bits and is combined with a 9 bit UR_UINT16: PACKED BITFIELD
descriptor and 1 bit for protection element to form a 16 bit value.
First register indicates input/output state with bits 0 (MSB) to 15
The combined bits are of the form: PTTTTTTDDDDDDDDD,
(LSB) corresponding to input/output state 1 to 16. The second reg-
where P bit if set, indicates that the FlexLogic™ type is associated
ister indicates input/output state with bits 0 to 15 corresponding to
with a protection element state and T represents bits for the BASE
input/output state 17 to 32 (if required) The third register indicates
type, and D represents bits for the descriptor.
input/output state with bits 0 to 15 corresponding to input/output
The values in square brackets indicate the base type with P prefix state 33 to 48 (if required). The fourth register indicates input/out-
[PTTTTTT] and the values in round brackets indicate the descrip- put state with bits 0 to 15 corresponding to input/output state 49 to
tor range. 64 (if required).
[0] Off(0) – this is boolean FALSE value The number of registers required is determined by the specific
[0] On (1) – this is boolean TRUE value data item. A bit value of 0 = Off and 1 = On.
[2] CONTACT INPUTS (1 to 96)
[3] CONTACT INPUTS OFF (1 to 96)
[4] VIRTUAL INPUTS (1 to 64) F501
[6] VIRTUAL OUTPUTS (1 to 96) UR_UINT16: LED STATUS
[10] CONTACT OUTPUTS VOLTAGE DETECTED (1 to 64)
[11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1 to 64) Low byte of register indicates LED status with bit 0 representing
the top LED and bit 7 the bottom LED. A bit value of 1 indicates
[12] CONTACT OUTPUTS CURRENT DETECTED (1 to 64)
the LED is on, 0 indicates the LED is off.
[13] CONTACT OUTPUTS CURRENT OFF DETECTED (1 to 64)
[14] REMOTE INPUTS (1 to 32)
[28] INSERT (via keypad only)
F502
[32] END
[34] NOT (1 INPUT) BITFIELD: ELEMENT OPERATE STATES
[36] 2 INPUT XOR (0) Each bit contains the operate state for an element. See the F124
[38] LATCH SET/RESET (2 inputs) format code for a list of element IDs. The operate bit for element ID
[40] OR (2 to 16 inputs) X is bit [X mod 16] in register [X/16].

GE Multilin G60 Generator Protection System B-81


B.4 MEMORY MAPPING APPENDIX B

F504 F514
BITFIELD: 3-PHASE ELEMENT STATE ENUMERATION: POWER SWING TRIP MODE
bitmask element state 0 = Delayed, 1 = Early
0 Pickup
1 Operate
F515
2 Pickup Phase A
ENUMERATION ELEMENT INPUT MODE
B 3
4
Pickup Phase B
Pickup Phase C
0 = Signed, 1 = Absolute

5 Operate Phase A
6 Operate Phase B F516
7 Operate Phase C ENUMERATION ELEMENT COMPARE MODE
0 = Level, 1 = Delta

F505
BITFIELD: CONTACT OUTPUT STATE F517
0 = Contact State, 1 = Voltage Detected, 2 = Current Detected ENUMERATION: ELEMENT DIRECTION OPERATION
0 = Over, 1 = Under

F507
BITFIELD: COUNTER ELEMENT STATE F518
0 = Count Greater Than, 1 = Count Equal To, 2 = Count Less Than ENUMERATION: FLEXELEMENT™ UNITS
0 = Milliseconds, 1 = Seconds, 2 = Minutes

F508
BITFIELD: DISTANCE ELEMENT STATE F519
bitmask distance element state ENUMERATION: NON-VOLATILE LATCH
0 Pickup 0 = Reset-Dominant, 1 = Set-Dominant
1 Operate
2 Pickup AB
F522
3 Pickup BC
ENUMERATION: TRANSDUCER DCMA OUTPUT RANGE
4 Pickup CA
5 Operate AB 0 = –1 to 1 mA; 1 = 0 to 1 mA; 2 = 4 to 20 mA
6 Operate BC
7 Operate CA F523
8 Timed ENUMERATION: DNP OBJECTS 20, 22, AND 23 DEFAULT
9 Operate IAB VARIATION
10 Operate IBC
bitmask default variation
11 Operate ICA
0 1
1 2
F509 2 5
BITFIELD: SIMPLE ELEMENT STATE 3 6

0 = Operate
F524
ENUMERATION: DNP OBJECT 21 DEFAULT VARIATION
F511
BITFIELD: 3-PHASE SIMPLE ELEMENT STATE
bitmask Default Variation
0 = Operate, 1 = Operate A, 2 = Operate B, 3 = Operate C 0 1
1 2
2 9
F513
ENUMERATION: POWER SWING MODE 3 10

0 = Two Step, 1 = Three Step

B-82 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

F525 F543
ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION ENUMERATION: PMU PHASORS

bitmask default variation value phasor value phasor


0 1 0 Off 8 Ig
1 2 1 Va 9 V_1
2 3 2 Vb 10 V_2
3 4 3 Vc 11 V_0 B
4 5 4 Vx 12 I_1
5 7 5 Ia 13 I_2
6 Ib 14 I_0
7 Ic
F530
ENUMERATION: FRONT PANEL INTERFACE KEYPRESS
value keypress value keypress value keypress F544
0 None 15 3 33 User PB 3 ENUMERATION: PMU RECORDING/REPORTING RATE
1 Menu 16 Enter 34 User PB 4
value rate value rate
2 Message Up 17 Message 35 User PB 5
Down 0 1/second 6 15/second

3 7 ~
18 0 ~
36 User PB 6 1 2/second 7 20second

4 8 19 Decimal 37 User PB 7 2 4/second 8 25/second

5 9 20 +/– 38 User PB 8 3 5/second 9 30/second

6 Help 21 Value Up 39 User PB 9 4 10/second 10 50/second

7 Message Left 22 Value Down 40 User PB 10 5 12/second 11 60/second

8 4 23 Reset 41 User PB 11
9 5 24 User 1 42 User PB 12
F545
10 6 25 User 2 44 User 4 ENUMERATION: PMU COM PORT TYPE
11 Escape 26 User 3 45 User 5
0 = Network, 1 = RS485, 2 = Dir Comm Ch1, 3 = Dir Comm Ch2,
12 Message 31 User PB 1 46 User 6 4 = GOOSE, 5 = None
Right
13 1 32 User PB 2 47 User 7
14 2 F546
ENUMERATION: PMU REPORTING STYLE
0 = Polar, 1 = Rectangular
F531
ENUMERATION: LANGUAGE
0 = English, 1 = French, 2 = Chinese, 3 = Russian F547
ENUMERATION: PMU REPORTING FORMAT
0 = Integer, 1 = Floating
F540
ENUMERATION: PMU POST-FILTER
0 = None, 1 = Symm-3-Point, 2 = Symm-5-Point, F550
3 = Symm-7-Point, 4 = Class M, 5 = Class P ENUMERATION: RTD INPUT APPLICATION

Enumeration RTD input application


F542 0 None
ENUMERATION: PMU TRIGGERING MODE 1 Stator
0 = Automatic Overwrite, 1 = Protected 2 Bearing
3 Ambient
4 Group 1
5 Group 2

GE Multilin G60 Generator Protection System B-83


B.4 MEMORY MAPPING APPENDIX B

F551 F603
ENUMERATION: RTD TRIP VOTING ENUMERATION: RRTD TRIP VOTING

Enumeration RTD trip voting Enumeration RRTD trip voting


0 None 0 None
1 Group 1 Group
2 RTD Input 1 2 Remote RTD 1
B 3 RTD Input 2 3 Remote RTD 2
4 RTD Input 3 4 Remote RTD 3
5 RTD Input 4 5 Remote RTD 4
6 RTD Input 5 6 Remote RTD 5
7 RTD Input 6 7 Remote RTD 6
8 RTD Input 7 8 Remote RTD 7
9 RTD Input 8 9 Remote RTD 8
10 RTD Input 9 10 Remote RTD 9
11 RTD Input 10 11 Remote RTD 10
12 RTD Input 11 12 Remote RTD 11
13 RTD Input 12 13 Remote RTD 12

F552 F605
ENUMERATION: RTD INPUT OPEN ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT
STATUS
Enumeration RTD open
0 None Enumeration Remote DPS input status

1 Alarm 0 Intermediate

2 Block 1 Off
2 On
3 Bad
F600
UR_UINT16: FLEXANALOG PARAMETER
Corresponds to the Modbus address of the value used when this F606
parameter is selected. Only certain values may be used as Flex- ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT
Analogs (basically all metering quantities used in protection).
Enumeration Remote double-point status input
0 None
F601 1 Remote input 1
ENUMERATION: COM2 PORT USAGE 2 Remote input 2
3 Remote input 3
Enumeration COM2 port usage
↓ ↓
0 RS485
64 Remote input 64
1 RRTD

F611
F602
ENUMERATION: GOOSE RETRANSMISSION SCHEME
ENUMERATION: RRTD BAUD RATE
Enumeration Configurable GOOSE retransmission scheme
Enumeration RRTD baud rate
0 Heartbeat
0 1200 bps
1 Aggressive
1 2400 bps
2 Medium
2 4800 bps
3 Relaxed
3 9600 bps
4 19200 bps
F612
UR_UINT16: FLEXINTEGER PARAMETER
This 16-bit value corresponds to the Modbus address of the
selected FlexInteger paramter. Only certain values may be used
as FlexIntegers.

B-84 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Enumeration IEC 61850 report dataset items


F613
42 PIOC7.ST.Op.general
ENUMERATION: FIELD GROUND MODULE INJECTION
43 PIOC8.ST.Str.general
CONNECTION TYPE
44 PIOC8.ST.Op.general
Enumeration Connection type 45 PIOC9.ST.Str.general
0 Single point 46 PIOC9.ST.Op.general
1 Double point 47 PIOC10.ST.Str.general
48 PIOC10.ST.Op.general B
49 PIOC11.ST.Str.general
F615
ENUMERATION: IEC 61850 REPORT DATASET ITEMS 50 PIOC11.ST.Op.general
51 PIOC12.ST.Str.general
Enumeration IEC 61850 report dataset items 52 PIOC12.ST.Op.general
0 None 53 PIOC13.ST.Str.general
1 PDIF1.ST.Str.general 54 PIOC13.ST.Op.general
2 PDIF1.ST.Op.general 55 PIOC14.ST.Str.general
3 PDIF2.ST.Str.general 56 PIOC14.ST.Op.general
4 PDIF2.ST.Op.general 57 PIOC15.ST.Str.general
5 PDIF3.ST.Str.general 58 PIOC15.ST.Op.general
6 PDIF3.ST.Op.general 59 PIOC16.ST.Str.general
7 PDIF4.ST.Str.general 60 PIOC16.ST.Op.general
8 PDIF4.ST.Op.general 61 PIOC17.ST.Str.general
9 PDIS1.ST.Str.general 62 PIOC17.ST.Op.general
10 PDIS1.ST.Op.general 63 PIOC18.ST.Str.general
11 PDIS2.ST.Str.general 64 PIOC18.ST.Op.general
12 PDIS2.ST.Op.general 65 PIOC19.ST.Str.general
13 PDIS3.ST.Str.general 66 PIOC19.ST.Op.general
14 PDIS3.ST.Op.general 67 PIOC20.ST.Str.general
15 PDIS4.ST.Str.general 68 PIOC20.ST.Op.general
16 PDIS4.ST.Op.general 69 PIOC21.ST.Str.general
17 PDIS5.ST.Str.general 70 PIOC21.ST.Op.general
18 PDIS5.ST.Op.general 71 PIOC22.ST.Str.general
19 PDIS6.ST.Str.general 72 PIOC22.ST.Op.general
20 PDIS6.ST.Op.general 73 PIOC23.ST.Str.general
21 PDIS7.ST.Str.general 74 PIOC23.ST.Op.general
22 PDIS7.ST.Op.general 75 PIOC24.ST.Str.general
23 PDIS8.ST.Str.general 76 PIOC24.ST.Op.general
24 PDIS8.ST.Op.general 77 PIOC25.ST.Str.general
25 PDIS9.ST.Str.general 78 PIOC25.ST.Op.general
26 PDIS9.ST.Op.general 79 PIOC26.ST.Str.general
27 PDIS10.ST.Str.general 80 PIOC26.ST.Op.general
28 PDIS10.ST.Op.general 81 PIOC27.ST.Str.general
29 PIOC1.ST.Str.general 82 PIOC27.ST.Op.general
30 PIOC1.ST.Op.general 83 PIOC28.ST.Str.general
31 PIOC2.ST.Str.general 84 PIOC28.ST.Op.general
32 PIOC2.ST.Op.general 85 PIOC29.ST.Str.general
33 PIOC3.ST.Str.general 86 PIOC29.ST.Op.general
34 PIOC3.ST.Op.general 87 PIOC30.ST.Str.general
35 PIOC4.ST.Str.general 88 PIOC30.ST.Op.general
36 PIOC4.ST.Op.general 89 PIOC31.ST.Str.general
37 PIOC5.ST.Str.general 90 PIOC31.ST.Op.general
38 PIOC5.ST.Op.general 91 PIOC32.ST.Str.general
39 PIOC6.ST.Str.general 92 PIOC32.ST.Op.general
40 PIOC6.ST.Op.general 93 PIOC33.ST.Str.general
41 PIOC7.ST.Str.general 94 PIOC33.ST.Op.general

GE Multilin G60 Generator Protection System B-85


B.4 MEMORY MAPPING APPENDIX B

Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
95 PIOC34.ST.Str.general 148 PIOC60.ST.Op.general
96 PIOC34.ST.Op.general 149 PIOC61.ST.Str.general
97 PIOC35.ST.Str.general 150 PIOC61.ST.Op.general
98 PIOC35.ST.Op.general 151 PIOC62.ST.Str.general
99 PIOC36.ST.Str.general 152 PIOC62.ST.Op.general
100 PIOC36.ST.Op.general 153 PIOC63.ST.Str.general
B 101 PIOC37.ST.Str.general 154 PIOC63.ST.Op.general
102 PIOC37.ST.Op.general 155 PIOC64.ST.Str.general
103 PIOC38.ST.Str.general 156 PIOC64.ST.Op.general
104 PIOC38.ST.Op.general 157 PIOC65.ST.Str.general
105 PIOC39.ST.Str.general 158 PIOC65.ST.Op.general
106 PIOC39.ST.Op.general 159 PIOC66.ST.Str.general
107 PIOC40.ST.Str.general 160 PIOC66.ST.Op.general
108 PIOC40.ST.Op.general 161 PIOC67.ST.Str.general
109 PIOC41.ST.Str.general 162 PIOC67.ST.Op.general
110 PIOC41.ST.Op.general 163 PIOC68.ST.Str.general
111 PIOC42.ST.Str.general 164 PIOC68.ST.Op.general
112 PIOC42.ST.Op.general 165 PIOC69.ST.Str.general
113 PIOC43.ST.Str.general 166 PIOC69.ST.Op.general
114 PIOC43.ST.Op.general 167 PIOC70.ST.Str.general
115 PIOC44.ST.Str.general 168 PIOC70.ST.Op.general
116 PIOC44.ST.Op.general 169 PIOC71.ST.Str.general
117 PIOC45.ST.Str.general 170 PIOC71.ST.Op.general
118 PIOC45.ST.Op.general 171 PIOC72.ST.Str.general
119 PIOC46.ST.Str.general 172 PIOC72.ST.Op.general
120 PIOC46.ST.Op.general 173 PTOC1.ST.Str.general
121 PIOC47.ST.Str.general 174 PTOC1.ST.Op.general
122 PIOC47.ST.Op.general 175 PTOC2.ST.Str.general
123 PIOC48.ST.Str.general 176 PTOC2.ST.Op.general
124 PIOC48.ST.Op.general 177 PTOC3.ST.Str.general
125 PIOC49.ST.Str.general 178 PTOC3.ST.Op.general
126 PIOC49.ST.Op.general 179 PTOC4.ST.Str.general
127 PIOC50.ST.Str.general 180 PTOC4.ST.Op.general
128 PIOC50.ST.Op.general 181 PTOC5.ST.Str.general
129 PIOC51.ST.Str.general 182 PTOC5.ST.Op.general
130 PIOC51.ST.Op.general 183 PTOC6.ST.Str.general
131 PIOC52.ST.Str.general 184 PTOC6.ST.Op.general
132 PIOC52.ST.Op.general 185 PTOC7.ST.Str.general
133 PIOC53.ST.Str.general 186 PTOC7.ST.Op.general
134 PIOC53.ST.Op.general 187 PTOC8.ST.Str.general
135 PIOC54.ST.Str.general 188 PTOC8.ST.Op.general
136 PIOC54.ST.Op.general 189 PTOC9.ST.Str.general
137 PIOC55.ST.Str.general 190 PTOC9.ST.Op.general
138 PIOC55.ST.Op.general 191 PTOC10.ST.Str.general
139 PIOC56.ST.Str.general 192 PTOC10.ST.Op.general
140 PIOC56.ST.Op.general 193 PTOC11.ST.Str.general
141 PIOC57.ST.Str.general 194 PTOC11.ST.Op.general
142 PIOC57.ST.Op.general 195 PTOC12.ST.Str.general
143 PIOC58.ST.Str.general 196 PTOC12.ST.Op.general
144 PIOC58.ST.Op.general 197 PTOC13.ST.Str.general
145 PIOC59.ST.Str.general 198 PTOC13.ST.Op.general
146 PIOC59.ST.Op.general 199 PTOC14.ST.Str.general
147 PIOC60.ST.Str.general 200 PTOC14.ST.Op.general

B-86 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
201 PTOC15.ST.Str.general 254 PTUV1.ST.Op.general
202 PTOC15.ST.Op.general 255 PTUV2.ST.Str.general
203 PTOC16.ST.Str.general 256 PTUV2.ST.Op.general
204 PTOC16.ST.Op.general 257 PTUV3.ST.Str.general
205 PTOC17.ST.Str.general 258 PTUV3.ST.Op.general
206 PTOC17.ST.Op.general 259 PTUV4.ST.Str.general
207 PTOC18.ST.Str.general 260 PTUV4.ST.Op.general B
208 PTOC18.ST.Op.general 261 PTUV5.ST.Str.general
209 PTOC19.ST.Str.general 262 PTUV5.ST.Op.general
210 PTOC19.ST.Op.general 263 PTUV6.ST.Str.general
211 PTOC20.ST.Str.general 264 PTUV6.ST.Op.general
212 PTOC20.ST.Op.general 265 PTUV7.ST.Str.general
213 PTOC21.ST.Str.general 266 PTUV7.ST.Op.general
214 PTOC21.ST.Op.general 267 PTUV8.ST.Str.general
215 PTOC22.ST.Str.general 268 PTUV8.ST.Op.general
216 PTOC22.ST.Op.general 269 PTUV9.ST.Str.general
217 PTOC23.ST.Str.general 270 PTUV9.ST.Op.general
218 PTOC23.ST.Op.general 271 PTUV10.ST.Str.general
219 PTOC24.ST.Str.general 272 PTUV10.ST.Op.general
220 PTOC24.ST.Op.general 273 PTUV11.ST.Str.general
221 PTOV1.ST.Str.general 274 PTUV11.ST.Op.general
222 PTOV1.ST.Op.general 275 PTUV12.ST.Str.general
223 PTOV2.ST.Str.general 276 PTUV12.ST.Op.general
224 PTOV2.ST.Op.general 277 PTUV13.ST.Str.general
225 PTOV3.ST.Str.general 278 PTUV13.ST.Op.general
226 PTOV3.ST.Op.general 279 RBRF1.ST.OpEx.general
227 PTOV4.ST.Str.general 280 RBRF1.ST.OpIn.general
228 PTOV4.ST.Op.general 281 RBRF2.ST.OpEx.general
229 PTOV5.ST.Str.general 282 RBRF2.ST.OpIn.general
230 PTOV5.ST.Op.general 283 RBRF3.ST.OpEx.general
231 PTOV6.ST.Str.general 284 RBRF3.ST.OpIn.general
232 PTOV6.ST.Op.general 285 RBRF4.ST.OpEx.general
233 PTOV7.ST.Str.general 286 RBRF4.ST.OpIn.general
234 PTOV7.ST.Op.general 287 RBRF5.ST.OpEx.general
235 PTOV8.ST.Str.general 288 RBRF5.ST.OpIn.general
236 PTOV8.ST.Op.general 289 RBRF6.ST.OpEx.general
237 PTOV9.ST.Str.general 290 RBRF6.ST.OpIn.general
238 PTOV9.ST.Op.general 291 RBRF7.ST.OpEx.general
239 PTOV10.ST.Str.general 292 RBRF7.ST.OpIn.general
240 PTOV10.ST.Op.general 293 RBRF8.ST.OpEx.general
241 PTRC1.ST.Tr.general 294 RBRF8.ST.OpIn.general
242 PTRC1.ST.Op.general 295 RBRF9.ST.OpEx.general
243 PTRC2.ST.Tr.general 296 RBRF9.ST.OpIn.general
244 PTRC2.ST.Op.general 297 RBRF10.ST.OpEx.general
245 PTRC3.ST.Tr.general 298 RBRF10.ST.OpIn.general
246 PTRC3.ST.Op.general 299 RBRF11.ST.OpEx.general
247 PTRC4.ST.Tr.general 300 RBRF11.ST.OpIn.general
248 PTRC4.ST.Op.general 301 RBRF12.ST.OpEx.general
249 PTRC5.ST.Tr.general 302 RBRF12.ST.OpIn.general
250 PTRC5.ST.Op.general 303 RBRF13.ST.OpEx.general
251 PTRC6.ST.Tr.general 304 RBRF13.ST.OpIn.general
252 PTRC6.ST.Op.general 305 RBRF14.ST.OpEx.general
253 PTUV1.ST.Str.general 306 RBRF14.ST.OpIn.general

GE Multilin G60 Generator Protection System B-87


B.4 MEMORY MAPPING APPENDIX B

Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
307 RBRF15.ST.OpEx.general 360 CSWI7.ST.Pos.stVal
308 RBRF15.ST.OpIn.general 361 CSWI8.ST.Loc.stVal
309 RBRF16.ST.OpEx.general 362 CSWI8.ST.Pos.stVal
310 RBRF16.ST.OpIn.general 363 CSWI9.ST.Loc.stVal
311 RBRF17.ST.OpEx.general 364 CSWI9.ST.Pos.stVal
312 RBRF17.ST.OpIn.general 365 CSWI10.ST.Loc.stVal
B 313 RBRF18.ST.OpEx.general 366 CSWI10.ST.Pos.stVal
314 RBRF18.ST.OpIn.general 367 CSWI11.ST.Loc.stVal
315 RBRF19.ST.OpEx.general 368 CSWI11.ST.Pos.stVal
316 RBRF19.ST.OpIn.general 369 CSWI12.ST.Loc.stVal
317 RBRF20.ST.OpEx.general 370 CSWI12.ST.Pos.stVal
318 RBRF20.ST.OpIn.general 371 CSWI13.ST.Loc.stVal
319 RBRF21.ST.OpEx.general 372 CSWI13.ST.Pos.stVal
320 RBRF21.ST.OpIn.general 373 CSWI14.ST.Loc.stVal
321 RBRF22.ST.OpEx.general 374 CSWI14.ST.Pos.stVal
322 RBRF22.ST.OpIn.general 375 CSWI15.ST.Loc.stVal
323 RBRF23.ST.OpEx.general 376 CSWI15.ST.Pos.stVal
324 RBRF23.ST.OpIn.general 377 CSWI16.ST.Loc.stVal
325 RBRF24.ST.OpEx.general 378 CSWI16.ST.Pos.stVal
326 RBRF24.ST.OpIn.general 379 CSWI17.ST.Loc.stVal
327 RFLO1.MX.FltDiskm.mag.f 380 CSWI17.ST.Pos.stVal
328 RFLO2.MX.FltDiskm.mag.f 381 CSWI18.ST.Loc.stVal
329 RFLO3.MX.FltDiskm.mag.f 382 CSWI18.ST.Pos.stVal
330 RFLO4.MX.FltDiskm.mag.f 383 CSWI19.ST.Loc.stVal
331 RFLO5.MX.FltDiskm.mag.f 384 CSWI19.ST.Pos.stVal
332 RPSB1.ST.Str.general 385 CSWI20.ST.Loc.stVal
333 RPSB1.ST.Op.general 386 CSWI20.ST.Pos.stVal
334 RPSB1.ST.BlkZn.stVal 387 CSWI21.ST.Loc.stVal
335 RREC1.ST.Op.general 388 CSWI21.ST.Pos.stVal
336 RREC1.ST.AutoRecSt.stVal 389 CSWI22.ST.Loc.stVal
337 RREC2.ST.Op.general 390 CSWI22.ST.Pos.stVal
338 RREC2.ST.AutoRecSt.stVal 391 CSWI23.ST.Loc.stVal
339 RREC3.ST.Op.general 392 CSWI23.ST.Pos.stVal
340 RREC3.ST.AutoRecSt.stVal 393 CSWI24.ST.Loc.stVal
341 RREC4.ST.Op.general 394 CSWI24.ST.Pos.stVal
342 RREC4.ST.AutoRecSt.stVal 395 CSWI25.ST.Loc.stVal
343 RREC5.ST.Op.general 396 CSWI25.ST.Pos.stVal
344 RREC5.ST.AutoRecSt.stVal 397 CSWI26.ST.Loc.stVal
345 RREC6.ST.Op.general 398 CSWI26.ST.Pos.stVal
346 RREC6.ST.AutoRecSt.stVal 399 CSWI27.ST.Loc.stVal
347 CSWI1.ST.Loc.stVal 400 CSWI27.ST.Pos.stVal
348 CSWI1.ST.Pos.stVal 401 CSWI28.ST.Loc.stVal
349 CSWI2.ST.Loc.stVal 402 CSWI28.ST.Pos.stVal
350 CSWI2.ST.Pos.stVal 403 CSWI29.ST.Loc.stVal
351 CSWI3.ST.Loc.stVal 404 CSWI29.ST.Pos.stVal
352 CSWI3.ST.Pos.stVal 405 CSWI30.ST.Loc.stVal
353 CSWI4.ST.Loc.stVal 406 CSWI30.ST.Pos.stVal
354 CSWI4.ST.Pos.stVal 407 GGIO1.ST.Ind1.stVal
355 CSWI5.ST.Loc.stVal 408 GGIO1.ST.Ind2.stVal
356 CSWI5.ST.Pos.stVal 409 GGIO1.ST.Ind3.stVal
357 CSWI6.ST.Loc.stVal 410 GGIO1.ST.Ind4.stVal
358 CSWI6.ST.Pos.stVal 411 GGIO1.ST.Ind5.stVal
359 CSWI7.ST.Loc.stVal 412 GGIO1.ST.Ind6.stVal

B-88 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
413 GGIO1.ST.Ind7.stVal 466 GGIO1.ST.Ind60.stVal
414 GGIO1.ST.Ind8.stVal 467 GGIO1.ST.Ind61.stVal
415 GGIO1.ST.Ind9.stVal 468 GGIO1.ST.Ind62.stVal
416 GGIO1.ST.Ind10.stVal 469 GGIO1.ST.Ind63.stVal
417 GGIO1.ST.Ind11.stVal 470 GGIO1.ST.Ind64.stVal
418 GGIO1.ST.Ind12.stVal 471 GGIO1.ST.Ind65.stVal
419 GGIO1.ST.Ind13.stVal 472 GGIO1.ST.Ind66.stVal B
420 GGIO1.ST.Ind14.stVal 473 GGIO1.ST.Ind67.stVal
421 GGIO1.ST.Ind15.stVal 474 GGIO1.ST.Ind68.stVal
422 GGIO1.ST.Ind16.stVal 475 GGIO1.ST.Ind69.stVal
423 GGIO1.ST.Ind17.stVal 476 GGIO1.ST.Ind70.stVal
424 GGIO1.ST.Ind18.stVal 477 GGIO1.ST.Ind71.stVal
425 GGIO1.ST.Ind19.stVal 478 GGIO1.ST.Ind72.stVal
426 GGIO1.ST.Ind20.stVal 479 GGIO1.ST.Ind73.stVal
427 GGIO1.ST.Ind21.stVal 480 GGIO1.ST.Ind74.stVal
428 GGIO1.ST.Ind22.stVal 481 GGIO1.ST.Ind75.stVal
429 GGIO1.ST.Ind23.stVal 482 GGIO1.ST.Ind76.stVal
430 GGIO1.ST.Ind24.stVal 483 GGIO1.ST.Ind77.stVal
431 GGIO1.ST.Ind25.stVal 484 GGIO1.ST.Ind78.stVal
432 GGIO1.ST.Ind26.stVal 485 GGIO1.ST.Ind79.stVal
433 GGIO1.ST.Ind27.stVal 486 GGIO1.ST.Ind80.stVal
434 GGIO1.ST.Ind28.stVal 487 GGIO1.ST.Ind81.stVal
435 GGIO1.ST.Ind29.stVal 488 GGIO1.ST.Ind82.stVal
436 GGIO1.ST.Ind30.stVal 489 GGIO1.ST.Ind83.stVal
437 GGIO1.ST.Ind31.stVal 490 GGIO1.ST.Ind84.stVal
438 GGIO1.ST.Ind32.stVal 491 GGIO1.ST.Ind85.stVal
439 GGIO1.ST.Ind33.stVal 492 GGIO1.ST.Ind86.stVal
440 GGIO1.ST.Ind34.stVal 493 GGIO1.ST.Ind87.stVal
441 GGIO1.ST.Ind35.stVal 494 GGIO1.ST.Ind88.stVal
442 GGIO1.ST.Ind36.stVal 495 GGIO1.ST.Ind89.stVal
443 GGIO1.ST.Ind37.stVal 496 GGIO1.ST.Ind90.stVal
444 GGIO1.ST.Ind38.stVal 497 GGIO1.ST.Ind91.stVal
445 GGIO1.ST.Ind39.stVal 498 GGIO1.ST.Ind92.stVal
446 GGIO1.ST.Ind40.stVal 499 GGIO1.ST.Ind93.stVal
447 GGIO1.ST.Ind41.stVal 500 GGIO1.ST.Ind94.stVal
448 GGIO1.ST.Ind42.stVal 501 GGIO1.ST.Ind95.stVal
449 GGIO1.ST.Ind43.stVal 502 GGIO1.ST.Ind96.stVal
450 GGIO1.ST.Ind44.stVal 503 GGIO1.ST.Ind97.stVal
451 GGIO1.ST.Ind45.stVal 504 GGIO1.ST.Ind98.stVal
452 GGIO1.ST.Ind46.stVal 505 GGIO1.ST.Ind99.stVal
453 GGIO1.ST.Ind47.stVal 506 GGIO1.ST.Ind100.stVal
454 GGIO1.ST.Ind48.stVal 507 GGIO1.ST.Ind101.stVal
455 GGIO1.ST.Ind49.stVal 508 GGIO1.ST.Ind102.stVal
456 GGIO1.ST.Ind50.stVal 509 GGIO1.ST.Ind103.stVal
457 GGIO1.ST.Ind51.stVal 510 GGIO1.ST.Ind104.stVal
458 GGIO1.ST.Ind52.stVal 511 GGIO1.ST.Ind105.stVal
459 GGIO1.ST.Ind53.stVal 512 GGIO1.ST.Ind106.stVal
460 GGIO1.ST.Ind54.stVal 513 GGIO1.ST.Ind107.stVal
461 GGIO1.ST.Ind55.stVal 514 GGIO1.ST.Ind108.stVal
462 GGIO1.ST.Ind56.stVal 515 GGIO1.ST.Ind109.stVal
463 GGIO1.ST.Ind57.stVal 516 GGIO1.ST.Ind110.stVal
464 GGIO1.ST.Ind58.stVal 517 GGIO1.ST.Ind111.stVal
465 GGIO1.ST.Ind59.stVal 518 GGIO1.ST.Ind112.stVal

GE Multilin G60 Generator Protection System B-89


B.4 MEMORY MAPPING APPENDIX B

Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
519 GGIO1.ST.Ind113.stVal 572 MMXU2.MX.TotW.mag.f
520 GGIO1.ST.Ind114.stVal 573 MMXU2.MX.TotVAr.mag.f
521 GGIO1.ST.Ind115.stVal 574 MMXU2.MX.TotVA.mag.f
522 GGIO1.ST.Ind116.stVal 575 MMXU2.MX.TotPF.mag.f
523 GGIO1.ST.Ind117.stVal 576 MMXU2.MX.Hz.mag.f
524 GGIO1.ST.Ind118.stVal 577 MMXU2.MX.PPV.phsAB.cVal.mag.f
B 525 GGIO1.ST.Ind119.stVal 578 MMXU2.MX.PPV.phsAB.cVal.ang.f
526 GGIO1.ST.Ind120.stVal 579 MMXU2.MX.PPV.phsBC.cVal.mag.f
527 GGIO1.ST.Ind121.stVal 580 MMXU2.MX.PPV.phsBC.cVal.ang.f
528 GGIO1.ST.Ind122.stVal 581 MMXU2.MX.PPV.phsCA.cVal.mag.f
529 GGIO1.ST.Ind123.stVal 582 MMXU2.MX.PPV.phsCA.cVal.ang.f
530 GGIO1.ST.Ind124.stVal 583 MMXU2.MX.PhV.phsA.cVal.mag.f
531 GGIO1.ST.Ind125.stVal 584 MMXU2.MX.PhV.phsA.cVal.ang.f
532 GGIO1.ST.Ind126.stVal 585 MMXU2.MX.PhV.phsB.cVal.mag.f
533 GGIO1.ST.Ind127.stVal 586 MMXU2.MX.PhV.phsB.cVal.ang.f
534 GGIO1.ST.Ind128.stVal 587 MMXU2.MX.PhV.phsC.cVal.mag.f
535 MMXU1.MX.TotW.mag.f 588 MMXU2.MX.PhV.phsC.cVal.ang.f
536 MMXU1.MX.TotVAr.mag.f 589 MMXU2.MX.A.phsA.cVal.mag.f
537 MMXU1.MX.TotVA.mag.f 590 MMXU2.MX.A.phsA.cVal.ang.f
538 MMXU1.MX.TotPF.mag.f 591 MMXU2.MX.A.phsB.cVal.mag.f
539 MMXU1.MX.Hz.mag.f 592 MMXU2.MX.A.phsB.cVal.ang.f
540 MMXU1.MX.PPV.phsAB.cVal.mag.f 593 MMXU2.MX.A.phsC.cVal.mag.f
541 MMXU1.MX.PPV.phsAB.cVal.ang.f 594 MMXU2.MX.A.phsC.cVal.ang.f
542 MMXU1.MX.PPV.phsBC.cVal.mag.f 595 MMXU2.MX.A.neut.cVal.mag.f
543 MMXU1.MX.PPV.phsBC.cVal.ang.f 596 MMXU2.MX.A.neut.cVal.ang.f
544 MMXU1.MX.PPV.phsCA.cVal.mag.f 597 MMXU2.MX.W.phsA.cVal.mag.f
545 MMXU1.MX.PPV.phsCA.cVal.ang.f 598 MMXU2.MX.W.phsB.cVal.mag.f
546 MMXU1.MX.PhV.phsA.cVal.mag.f 599 MMXU2.MX.W.phsC.cVal.mag.f
547 MMXU1.MX.PhV.phsA.cVal.ang.f 600 MMXU2.MX.VAr.phsA.cVal.mag.f
548 MMXU1.MX.PhV.phsB.cVal.mag.f 601 MMXU2.MX.VAr.phsB.cVal.mag.f
549 MMXU1.MX.PhV.phsB.cVal.ang.f 602 MMXU2.MX.VAr.phsC.cVal.mag.f
550 MMXU1.MX.PhV.phsC.cVal.mag.f 603 MMXU2.MX.VA.phsA.cVal.mag.f
551 MMXU1.MX.PhV.phsC.cVal.ang.f 604 MMXU2.MX.VA.phsB.cVal.mag.f
552 MMXU1.MX.A.phsA.cVal.mag.f 605 MMXU2.MX.VA.phsC.cVal.mag.f
553 MMXU1.MX.A.phsA.cVal.ang.f 606 MMXU2.MX.PF.phsA.cVal.mag.f
554 MMXU1.MX.A.phsB.cVal.mag.f 607 MMXU2.MX.PF.phsB.cVal.mag.f
555 MMXU1.MX.A.phsB.cVal.ang.f 608 MMXU2.MX.PF.phsC.cVal.mag.f
556 MMXU1.MX.A.phsC.cVal.mag.f 609 MMXU3.MX.TotW.mag.f
557 MMXU1.MX.A.phsC.cVal.ang.f 610 MMXU3.MX.TotVAr.mag.f
558 MMXU1.MX.A.neut.cVal.mag.f 611 MMXU3.MX.TotVA.mag.f
559 MMXU1.MX.A.neut.cVal.ang.f 612 MMXU3.MX.TotPF.mag.f
560 MMXU1.MX.W.phsA.cVal.mag.f 613 MMXU3.MX.Hz.mag.f
561 MMXU1.MX.W.phsB.cVal.mag.f 614 MMXU3.MX.PPV.phsAB.cVal.mag.f
562 MMXU1.MX.W.phsC.cVal.mag.f 615 MMXU3.MX.PPV.phsAB.cVal.ang.f
563 MMXU1.MX.VAr.phsA.cVal.mag.f 616 MMXU3.MX.PPV.phsBC.cVal.mag.f
564 MMXU1.MX.VAr.phsB.cVal.mag.f 617 MMXU3.MX.PPV.phsBC.cVal.ang.f
565 MMXU1.MX.VAr.phsC.cVal.mag.f 618 MMXU3.MX.PPV.phsCA.cVal.mag.f
566 MMXU1.MX.VA.phsA.cVal.mag.f 619 MMXU3.MX.PPV.phsCA.cVal.ang.f
567 MMXU1.MX.VA.phsB.cVal.mag.f 620 MMXU3.MX.PhV.phsA.cVal.mag.f
568 MMXU1.MX.VA.phsC.cVal.mag.f 621 MMXU3.MX.PhV.phsA.cVal.ang.f
569 MMXU1.MX.PF.phsA.cVal.mag.f 622 MMXU3.MX.PhV.phsB.cVal.mag.f
570 MMXU1.MX.PF.phsB.cVal.mag.f 623 MMXU3.MX.PhV.phsB.cVal.ang.f
571 MMXU1.MX.PF.phsC.cVal.mag.f 624 MMXU3.MX.PhV.phsC.cVal.mag.f

B-90 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
625 MMXU3.MX.PhV.phsC.cVal.ang.f 678 MMXU4.MX.VA.phsB.cVal.mag.f
626 MMXU3.MX.A.phsA.cVal.mag.f 679 MMXU4.MX.VA.phsC.cVal.mag.f
627 MMXU3.MX.A.phsA.cVal.ang.f 680 MMXU4.MX.PF.phsA.cVal.mag.f
628 MMXU3.MX.A.phsB.cVal.mag.f 681 MMXU4.MX.PF.phsB.cVal.mag.f
629 MMXU3.MX.A.phsB.cVal.ang.f 682 MMXU4.MX.PF.phsC.cVal.mag.f
630 MMXU3.MX.A.phsC.cVal.mag.f 683 MMXU5.MX.TotW.mag.f
631 MMXU3.MX.A.phsC.cVal.ang.f 684 MMXU5.MX.TotVAr.mag.f B
632 MMXU3.MX.A.neut.cVal.mag.f 685 MMXU5.MX.TotVA.mag.f
633 MMXU3.MX.A.neut.cVal.ang.f 686 MMXU5.MX.TotPF.mag.f
634 MMXU3.MX.W.phsA.cVal.mag.f 687 MMXU5.MX.Hz.mag.f
635 MMXU3.MX.W.phsB.cVal.mag.f 688 MMXU5.MX.PPV.phsAB.cVal.mag.f
636 MMXU3.MX.W.phsC.cVal.mag.f 689 MMXU5.MX.PPV.phsAB.cVal.ang.f
637 MMXU3.MX.VAr.phsA.cVal.mag.f 690 MMXU5.MX.PPV.phsBC.cVal.mag.f
638 MMXU3.MX.VAr.phsB.cVal.mag.f 691 MMXU5.MX.PPV.phsBC.cVal.ang.f
639 MMXU3.MX.VAr.phsC.cVal.mag.f 692 MMXU5.MX.PPV.phsCA.cVal.mag.f
640 MMXU3.MX.VA.phsA.cVal.mag.f 693 MMXU5.MX.PPV.phsCA.cVal.ang.f
641 MMXU3.MX.VA.phsB.cVal.mag.f 694 MMXU5.MX.PhV.phsA.cVal.mag.f
642 MMXU3.MX.VA.phsC.cVal.mag.f 695 MMXU5.MX.PhV.phsA.cVal.ang.f
643 MMXU3.MX.PF.phsA.cVal.mag.f 696 MMXU5.MX.PhV.phsB.cVal.mag.f
644 MMXU3.MX.PF.phsB.cVal.mag.f 697 MMXU5.MX.PhV.phsB.cVal.ang.f
645 MMXU3.MX.PF.phsC.cVal.mag.f 698 MMXU5.MX.PhV.phsC.cVal.mag.f
646 MMXU4.MX.TotW.mag.f 699 MMXU5.MX.PhV.phsC.cVal.ang.f
647 MMXU4.MX.TotVAr.mag.f 700 MMXU5.MX.A.phsA.cVal.mag.f
648 MMXU4.MX.TotVA.mag.f 701 MMXU5.MX.A.phsA.cVal.ang.f
649 MMXU4.MX.TotPF.mag.f 702 MMXU5.MX.A.phsB.cVal.mag.f
650 MMXU4.MX.Hz.mag.f 703 MMXU5.MX.A.phsB.cVal.ang.f
651 MMXU4.MX.PPV.phsAB.cVal.mag.f 704 MMXU5.MX.A.phsC.cVal.mag.f
652 MMXU4.MX.PPV.phsAB.cVal.ang.f 705 MMXU5.MX.A.phsC.cVal.ang.f
653 MMXU4.MX.PPV.phsBC.cVal.mag.f 706 MMXU5.MX.A.neut.cVal.mag.f
654 MMXU4.MX.PPV.phsBC.cVal.ang.f 707 MMXU5.MX.A.neut.cVal.ang.f
655 MMXU4.MX.PPV.phsCA.cVal.mag.f 708 MMXU5.MX.W.phsA.cVal.mag.f
656 MMXU4.MX.PPV.phsCA.cVal.ang.f 709 MMXU5.MX.W.phsB.cVal.mag.f
657 MMXU4.MX.PhV.phsA.cVal.mag.f 710 MMXU5.MX.W.phsC.cVal.mag.f
658 MMXU4.MX.PhV.phsA.cVal.ang.f 711 MMXU5.MX.VAr.phsA.cVal.mag.f
659 MMXU4.MX.PhV.phsB.cVal.mag.f 712 MMXU5.MX.VAr.phsB.cVal.mag.f
660 MMXU4.MX.PhV.phsB.cVal.ang.f 713 MMXU5.MX.VAr.phsC.cVal.mag.f
661 MMXU4.MX.PhV.phsC.cVal.mag.f 714 MMXU5.MX.VA.phsA.cVal.mag.f
662 MMXU4.MX.PhV.phsC.cVal.ang.f 715 MMXU5.MX.VA.phsB.cVal.mag.f
663 MMXU4.MX.A.phsA.cVal.mag.f 716 MMXU5.MX.VA.phsC.cVal.mag.f
664 MMXU4.MX.A.phsA.cVal.ang.f 717 MMXU5.MX.PF.phsA.cVal.mag.f
665 MMXU4.MX.A.phsB.cVal.mag.f 718 MMXU5.MX.PF.phsB.cVal.mag.f
666 MMXU4.MX.A.phsB.cVal.ang.f 719 MMXU5.MX.PF.phsC.cVal.mag.f
667 MMXU4.MX.A.phsC.cVal.mag.f 720 MMXU6.MX.TotW.mag.f
668 MMXU4.MX.A.phsC.cVal.ang.f 721 MMXU6.MX.TotVAr.mag.f
669 MMXU4.MX.A.neut.cVal.mag.f 722 MMXU6.MX.TotVA.mag.f
670 MMXU4.MX.A.neut.cVal.ang.f 723 MMXU6.MX.TotPF.mag.f
671 MMXU4.MX.W.phsA.cVal.mag.f 724 MMXU6.MX.Hz.mag.f
672 MMXU4.MX.W.phsB.cVal.mag.f 725 MMXU6.MX.PPV.phsAB.cVal.mag.f
673 MMXU4.MX.W.phsC.cVal.mag.f 726 MMXU6.MX.PPV.phsAB.cVal.ang.f
674 MMXU4.MX.VAr.phsA.cVal.mag.f 727 MMXU6.MX.PPV.phsBC.cVal.mag.f
675 MMXU4.MX.VAr.phsB.cVal.mag.f 728 MMXU6.MX.PPV.phsBC.cVal.ang.f
676 MMXU4.MX.VAr.phsC.cVal.mag.f 729 MMXU6.MX.PPV.phsCA.cVal.mag.f
677 MMXU4.MX.VA.phsA.cVal.mag.f 730 MMXU6.MX.PPV.phsCA.cVal.ang.f

GE Multilin G60 Generator Protection System B-91


B.4 MEMORY MAPPING APPENDIX B

Enumeration IEC 61850 report dataset items Enumeration IEC 61850 report dataset items
731 MMXU6.MX.PhV.phsA.cVal.mag.f 784 GGIO4.MX.AnIn28.mag.f
732 MMXU6.MX.PhV.phsA.cVal.ang.f 785 GGIO4.MX.AnIn29.mag.f
733 MMXU6.MX.PhV.phsB.cVal.mag.f 786 GGIO4.MX.AnIn30.mag.f
734 MMXU6.MX.PhV.phsB.cVal.ang.f 787 GGIO4.MX.AnIn31.mag.f
735 MMXU6.MX.PhV.phsC.cVal.mag.f 788 GGIO4.MX.AnIn32.mag.f
736 MMXU6.MX.PhV.phsC.cVal.ang.f 789 XSWI1.ST.Loc.stVal
B 737 MMXU6.MX.A.phsA.cVal.mag.f 790 XSWI1.ST.Pos.stVal
738 MMXU6.MX.A.phsA.cVal.ang.f 791 XSWI2.ST.Loc.stVal
739 MMXU6.MX.A.phsB.cVal.mag.f 792 XSWI2.ST.Pos.stVal
740 MMXU6.MX.A.phsB.cVal.ang.f 793 XSWI3.ST.Loc.stVal
741 MMXU6.MX.A.phsC.cVal.mag.f 794 XSWI3.ST.Pos.stVal
742 MMXU6.MX.A.phsC.cVal.ang.f 795 XSWI4.ST.Loc.stVal
743 MMXU6.MX.A.neut.cVal.mag.f 796 XSWI4.ST.Pos.stVal
744 MMXU6.MX.A.neut.cVal.ang.f 797 XSWI5.ST.Loc.stVal
745 MMXU6.MX.W.phsA.cVal.mag.f 798 XSWI5.ST.Pos.stVal
746 MMXU6.MX.W.phsB.cVal.mag.f 799 XSWI6.ST.Loc.stVal
747 MMXU6.MX.W.phsC.cVal.mag.f 800 XSWI6.ST.Pos.stVal
748 MMXU6.MX.VAr.phsA.cVal.mag.f 801 XSWI7.ST.Loc.stVal
749 MMXU6.MX.VAr.phsB.cVal.mag.f 802 XSWI7.ST.Pos.stVal
750 MMXU6.MX.VAr.phsC.cVal.mag.f 803 XSWI8.ST.Loc.stVal
751 MMXU6.MX.VA.phsA.cVal.mag.f 804 XSWI8.ST.Pos.stVal
752 MMXU6.MX.VA.phsB.cVal.mag.f 805 XSWI9.ST.Loc.stVal
753 MMXU6.MX.VA.phsC.cVal.mag.f 806 XSWI9.ST.Pos.stVal
754 MMXU6.MX.PF.phsA.cVal.mag.f 807 XSWI10.ST.Loc.stVal
755 MMXU6.MX.PF.phsB.cVal.mag.f 808 XSWI10.ST.Pos.stVal
756 MMXU6.MX.PF.phsC.cVal.mag.f 809 XSWI11.ST.Loc.stVal
757 GGIO4.MX.AnIn1.mag.f 810 XSWI11.ST.Pos.stVal
758 GGIO4.MX.AnIn2.mag.f 811 XSWI12.ST.Loc.stVal
759 GGIO4.MX.AnIn3.mag.f 812 XSWI12.ST.Pos.stVal
760 GGIO4.MX.AnIn4.mag.f 813 XSWI13.ST.Loc.stVal
761 GGIO4.MX.AnIn5.mag.f 814 XSWI13.ST.Pos.stVal
762 GGIO4.MX.AnIn6.mag.f 815 XSWI14.ST.Loc.stVal
763 GGIO4.MX.AnIn7.mag.f 816 XSWI14.ST.Pos.stVal
764 GGIO4.MX.AnIn8.mag.f 817 XSWI15.ST.Loc.stVal
765 GGIO4.MX.AnIn9.mag.f 818 XSWI15.ST.Pos.stVal
766 GGIO4.MX.AnIn10.mag.f 819 XSWI16.ST.Loc.stVal
767 GGIO4.MX.AnIn11.mag.f 820 XSWI16.ST.Pos.stVal
768 GGIO4.MX.AnIn12.mag.f 821 XSWI17.ST.Loc.stVal
769 GGIO4.MX.AnIn13.mag.f 822 XSWI17.ST.Pos.stVal
770 GGIO4.MX.AnIn14.mag.f 823 XSWI18.ST.Loc.stVal
771 GGIO4.MX.AnIn15.mag.f 824 XSWI18.ST.Pos.stVal
772 GGIO4.MX.AnIn16.mag.f 825 XSWI19.ST.Loc.stVal
773 GGIO4.MX.AnIn17.mag.f 826 XSWI19.ST.Pos.stVal
774 GGIO4.MX.AnIn18.mag.f 827 XSWI20.ST.Loc.stVal
775 GGIO4.MX.AnIn19.mag.f 828 XSWI20.ST.Pos.stVal
776 GGIO4.MX.AnIn20.mag.f 829 XSWI21.ST.Loc.stVal
777 GGIO4.MX.AnIn21.mag.f 830 XSWI21.ST.Pos.stVal
778 GGIO4.MX.AnIn22.mag.f 831 XSWI22.ST.Loc.stVal
779 GGIO4.MX.AnIn23.mag.f 832 XSWI22.ST.Pos.stVal
780 GGIO4.MX.AnIn24.mag.f 833 XSWI23.ST.Loc.stVal
781 GGIO4.MX.AnIn25.mag.f 834 XSWI23.ST.Pos.stVal
782 GGIO4.MX.AnIn26.mag.f 835 XSWI24.ST.Loc.stVal
783 GGIO4.MX.AnIn27.mag.f 836 XSWI24.ST.Pos.stVal

B-92 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Enumeration IEC 61850 report dataset items Enumeration GOOSE dataset items
837 XCBR1.ST.Loc.stVal 36 GGIO1.ST.Ind18.stVal
838 XCBR1.ST.Pos.stVal 37 GGIO1.ST.Ind19.q
839 XCBR2.ST.Loc.stVal 38 GGIO1.ST.Ind19.stVal
840 XCBR2.ST.Pos.stVal 39 GGIO1.ST.Ind20.q
841 XCBR3.ST.Loc.stVal 40 GGIO1.ST.Ind20.stVal
842 XCBR3.ST.Pos.stVal 41 GGIO1.ST.Ind21.q
843 XCBR4.ST.Loc.stVal 42 GGIO1.ST.Ind21.stVal B
844 XCBR4.ST.Pos.stVal 43 GGIO1.ST.Ind22.q
845 XCBR5.ST.Loc.stVal 44 GGIO1.ST.Ind22.stVal
846 XCBR5.ST.Pos.stVal 45 GGIO1.ST.Ind23.q
847 XCBR6.ST.Loc.stVal 46 GGIO1.ST.Ind23.stVal
848 XCBR6.ST.Pos.stVal 47 GGIO1.ST.Ind24.q
48 GGIO1.ST.Ind24.stVal
49 GGIO1.ST.Ind25.q
F616
50 GGIO1.ST.Ind25.stVal
ENUMERATION: IEC 61850 GOOSE DATASET ITEMS
51 GGIO1.ST.Ind26.q
Enumeration GOOSE dataset items 52 GGIO1.ST.Ind26.stVal
0 None 53 GGIO1.ST.Ind27.q
1 GGIO1.ST.Ind1.q 54 GGIO1.ST.Ind27.stVal
2 GGIO1.ST.Ind1.stVal 55 GGIO1.ST.Ind28.q
3 GGIO1.ST.Ind2.q 56 GGIO1.ST.Ind28.stVal
4 GGIO1.ST.Ind2.stVal 57 GGIO1.ST.Ind29.q
5 GGIO1.ST.Ind3.q 58 GGIO1.ST.Ind29.stVal
6 GGIO1.ST.Ind3.stVal 59 GGIO1.ST.Ind30.q
7 GGIO1.ST.Ind4.q 60 GGIO1.ST.Ind30.stVal
8 GGIO1.ST.Ind4.stVal 61 GGIO1.ST.Ind31.q
9 GGIO1.ST.Ind5.q 62 GGIO1.ST.Ind31.stVal
10 GGIO1.ST.Ind5.stVal 63 GGIO1.ST.Ind32.q
11 GGIO1.ST.Ind6.q 64 GGIO1.ST.Ind32.stVal
12 GGIO1.ST.Ind6.stVal 65 GGIO1.ST.Ind33.q
13 GGIO1.ST.Ind7.q 66 GGIO1.ST.Ind33.stVal
14 GGIO1.ST.Ind7.stVal 67 GGIO1.ST.Ind34.q
15 GGIO1.ST.Ind8.q 68 GGIO1.ST.Ind34.stVal
16 GGIO1.ST.Ind8.stVal 69 GGIO1.ST.Ind35.q
17 GGIO1.ST.Ind9.q 70 GGIO1.ST.Ind35.stVal
18 GGIO1.ST.Ind9.stVal 71 GGIO1.ST.Ind36.q
19 GGIO1.ST.Ind10.q 72 GGIO1.ST.Ind36.stVal
20 GGIO1.ST.Ind10.stVal 73 GGIO1.ST.Ind37.q
21 GGIO1.ST.Ind11.q 74 GGIO1.ST.Ind37.stVal
22 GGIO1.ST.Ind11.stVal 75 GGIO1.ST.Ind38.q
23 GGIO1.ST.Ind12.q 76 GGIO1.ST.Ind38.stVal
24 GGIO1.ST.Ind12.stVal 77 GGIO1.ST.Ind39.q
25 GGIO1.ST.Ind13.q 78 GGIO1.ST.Ind39.stVal
26 GGIO1.ST.Ind13.stVal 79 GGIO1.ST.Ind40.q
27 GGIO1.ST.Ind14.q 80 GGIO1.ST.Ind40.stVal
28 GGIO1.ST.Ind14.stVal 81 GGIO1.ST.Ind41.q
29 GGIO1.ST.Ind15.q 82 GGIO1.ST.Ind41.stVal
30 GGIO1.ST.Ind15.stVal 83 GGIO1.ST.Ind42.q
31 GGIO1.ST.Ind16.q 84 GGIO1.ST.Ind42.stVal
32 GGIO1.ST.Ind16.stVal 85 GGIO1.ST.Ind43.q
33 GGIO1.ST.Ind17.q 86 GGIO1.ST.Ind43.stVal
34 GGIO1.ST.Ind17.stVal 87 GGIO1.ST.Ind44.q
35 GGIO1.ST.Ind18.q 88 GGIO1.ST.Ind44.stVal

GE Multilin G60 Generator Protection System B-93


B.4 MEMORY MAPPING APPENDIX B

Enumeration GOOSE dataset items Enumeration GOOSE dataset items


89 GGIO1.ST.Ind45.q 142 GGIO1.ST.Ind71.stVal
90 GGIO1.ST.Ind45.stVal 143 GGIO1.ST.Ind72.q
91 GGIO1.ST.Ind46.q 144 GGIO1.ST.Ind72.stVal
92 GGIO1.ST.Ind46.stVal 145 GGIO1.ST.Ind73.q
93 GGIO1.ST.Ind47.q 146 GGIO1.ST.Ind73.stVal
94 GGIO1.ST.Ind47.stVal 147 GGIO1.ST.Ind74.q
B 95 GGIO1.ST.Ind48.q 148 GGIO1.ST.Ind74.stVal
96 GGIO1.ST.Ind48.stVal 149 GGIO1.ST.Ind75.q
97 GGIO1.ST.Ind49.q 150 GGIO1.ST.Ind75.stVal
98 GGIO1.ST.Ind49.stVal 151 GGIO1.ST.Ind76.q
99 GGIO1.ST.Ind50.q 152 GGIO1.ST.Ind76.stVal
100 GGIO1.ST.Ind50.stVal 153 GGIO1.ST.Ind77.q
101 GGIO1.ST.Ind51.q 154 GGIO1.ST.Ind77.stVal
102 GGIO1.ST.Ind51.stVal 155 GGIO1.ST.Ind78.q
103 GGIO1.ST.Ind52.q 156 GGIO1.ST.Ind78.stVal
104 GGIO1.ST.Ind52.stVal 157 GGIO1.ST.Ind79.q
105 GGIO1.ST.Ind53.q 158 GGIO1.ST.Ind79.stVal
106 GGIO1.ST.Ind53.stVal 159 GGIO1.ST.Ind80.q
107 GGIO1.ST.Ind54.q 160 GGIO1.ST.Ind80.stVal
108 GGIO1.ST.Ind54.stVal 161 GGIO1.ST.Ind81.q
109 GGIO1.ST.Ind55.q 162 GGIO1.ST.Ind81.stVal
110 GGIO1.ST.Ind55.stVal 163 GGIO1.ST.Ind82.q
111 GGIO1.ST.Ind56.q 164 GGIO1.ST.Ind82.stVal
112 GGIO1.ST.Ind56.stVal 165 GGIO1.ST.Ind83.q
113 GGIO1.ST.Ind57.q 166 GGIO1.ST.Ind83.stVal
114 GGIO1.ST.Ind57.stVal 167 GGIO1.ST.Ind84.q
115 GGIO1.ST.Ind58.q 168 GGIO1.ST.Ind84.stVal
116 GGIO1.ST.Ind58.stVal 169 GGIO1.ST.Ind85.q
117 GGIO1.ST.Ind59.q 170 GGIO1.ST.Ind85.stVal
118 GGIO1.ST.Ind59.stVal 171 GGIO1.ST.Ind86.q
119 GGIO1.ST.Ind60.q 172 GGIO1.ST.Ind86.stVal
120 GGIO1.ST.Ind60.stVal 173 GGIO1.ST.Ind87.q
121 GGIO1.ST.Ind61.q 174 GGIO1.ST.Ind87.stVal
122 GGIO1.ST.Ind61.stVal 175 GGIO1.ST.Ind88.q
123 GGIO1.ST.Ind62.q 176 GGIO1.ST.Ind88.stVal
124 GGIO1.ST.Ind62.stVal 177 GGIO1.ST.Ind89.q
125 GGIO1.ST.Ind63.q 178 GGIO1.ST.Ind89.stVal
126 GGIO1.ST.Ind63.stVal 179 GGIO1.ST.Ind90.q
127 GGIO1.ST.Ind64.q 180 GGIO1.ST.Ind90.stVal
128 GGIO1.ST.Ind64.stVal 181 GGIO1.ST.Ind91.q
129 GGIO1.ST.Ind65.q 182 GGIO1.ST.Ind91.stVal
130 GGIO1.ST.Ind65.stVal 183 GGIO1.ST.Ind92.q
131 GGIO1.ST.Ind66.q 184 GGIO1.ST.Ind92.stVal
132 GGIO1.ST.Ind66.stVal 185 GGIO1.ST.Ind93.q
133 GGIO1.ST.Ind67.q 186 GGIO1.ST.Ind93.stVal
134 GGIO1.ST.Ind67.stVal 187 GGIO1.ST.Ind94.q
135 GGIO1.ST.Ind68.q 188 GGIO1.ST.Ind94.stVal
136 GGIO1.ST.Ind68.stVal 189 GGIO1.ST.Ind95.q
137 GGIO1.ST.Ind69.q 190 GGIO1.ST.Ind95.stVal
138 GGIO1.ST.Ind69.stVal 191 GGIO1.ST.Ind96.q
139 GGIO1.ST.Ind70.q 192 GGIO1.ST.Ind96.stVal
140 GGIO1.ST.Ind70.stVal 193 GGIO1.ST.Ind97.q
141 GGIO1.ST.Ind71.q 194 GGIO1.ST.Ind97.stVal

B-94 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Enumeration GOOSE dataset items Enumeration GOOSE dataset items


195 GGIO1.ST.Ind98.q 248 GGIO1.ST.Ind124.stVal
196 GGIO1.ST.Ind98.stVal 249 GGIO1.ST.Ind125.q
197 GGIO1.ST.Ind99.q 250 GGIO1.ST.Ind125.stVal
198 GGIO1.ST.Ind99.stVal 251 GGIO1.ST.Ind126.q
199 GGIO1.ST.Ind100.q 252 GGIO1.ST.Ind126.stVal
200 GGIO1.ST.Ind100.stVal 253 GGIO1.ST.Ind127.q
201 GGIO1.ST.Ind101.q 254 GGIO1.ST.Ind127.stVal B
202 GGIO1.ST.Ind101.stVal 255 GGIO1.ST.Ind128.q
203 GGIO1.ST.Ind102.q 256 GGIO1.ST.Ind128.stVal
204 GGIO1.ST.Ind102.stVal 257 MMXU1.MX.TotW.mag.f
205 GGIO1.ST.Ind103.q 258 MMXU1.MX.TotVAr.mag.f
206 GGIO1.ST.Ind103.stVal 259 MMXU1.MX.TotVA.mag.f
207 GGIO1.ST.Ind104.q 260 MMXU1.MX.TotPF.mag.f
208 GGIO1.ST.Ind104.stVal 261 MMXU1.MX.Hz.mag.f
209 GGIO1.ST.Ind105.q 262 MMXU1.MX.PPV.phsAB.cVal.mag.f
210 GGIO1.ST.Ind105.stVal 263 MMXU1.MX.PPV.phsAB.cVal.ang.f
211 GGIO1.ST.Ind106.q 264 MMXU1.MX.PPV.phsBC.cVal.mag.f
212 GGIO1.ST.Ind106.stVal 265 MMXU1.MX.PPV.phsBC.cVal.ang.f
213 GGIO1.ST.Ind107.q 266 MMXU1.MX.PPV.phsCA.cVal.mag.f
214 GGIO1.ST.Ind107.stVal 267 MMXU1.MX.PPV.phsCA.cVal.ang.f
215 GGIO1.ST.Ind108.q 268 MMXU1.MX.PhV.phsA.cVal.mag.f
216 GGIO1.ST.Ind108.stVal 269 MMXU1.MX.PhV.phsA.cVal.ang.f
217 GGIO1.ST.Ind109.q 270 MMXU1.MX.PhV.phsB.cVal.mag.f
218 GGIO1.ST.Ind109.stVal 271 MMXU1.MX.PhV.phsB.cVal.ang.f
219 GGIO1.ST.Ind110.q 272 MMXU1.MX.PhV.phsC.cVal.mag.f
220 GGIO1.ST.Ind110.stVal 273 MMXU1.MX.PhV.phsC.cVal.ang.f
221 GGIO1.ST.Ind111.q 274 MMXU1.MX.A.phsA.cVal.mag.f
222 GGIO1.ST.Ind111.stVal 275 MMXU1.MX.A.phsA.cVal.ang.f
223 GGIO1.ST.Ind112.q 276 MMXU1.MX.A.phsB.cVal.mag.f
224 GGIO1.ST.Ind112.stVal 277 MMXU1.MX.A.phsB.cVal.ang.f
225 GGIO1.ST.Ind113.q 278 MMXU1.MX.A.phsC.cVal.mag.f
226 GGIO1.ST.Ind113.stVal 279 MMXU1.MX.A.phsC.cVal.ang.f
227 GGIO1.ST.Ind114.q 280 MMXU1.MX.A.neut.cVal.mag.f
228 GGIO1.ST.Ind114.stVal 281 MMXU1.MX.A.neut.cVal.ang.f
229 GGIO1.ST.Ind115.q 282 MMXU1.MX.W.phsA.cVal.mag.f
230 GGIO1.ST.Ind115.stVal 283 MMXU1.MX.W.phsB.cVal.mag.f
231 GGIO1.ST.Ind116.q 284 MMXU1.MX.W.phsC.cVal.mag.f
232 GGIO1.ST.Ind116.stVal 285 MMXU1.MX.VAr.phsA.cVal.mag.f
233 GGIO1.ST.Ind117.q 286 MMXU1.MX.VAr.phsB.cVal.mag.f
234 GGIO1.ST.Ind117.stVal 287 MMXU1.MX.VAr.phsC.cVal.mag.f
235 GGIO1.ST.Ind118.q 288 MMXU1.MX.VA.phsA.cVal.mag.f
236 GGIO1.ST.Ind118.stVal 289 MMXU1.MX.VA.phsB.cVal.mag.f
237 GGIO1.ST.Ind119.q 290 MMXU1.MX.VA.phsC.cVal.mag.f
238 GGIO1.ST.Ind119.stVal 291 MMXU1.MX.PF.phsA.cVal.mag.f
239 GGIO1.ST.Ind120.q 292 MMXU1.MX.PF.phsB.cVal.mag.f
240 GGIO1.ST.Ind120.stVal 293 MMXU1.MX.PF.phsC.cVal.mag.f
241 GGIO1.ST.Ind121.q 294 MMXU2.MX.TotW.mag.f
242 GGIO1.ST.Ind121.stVal 295 MMXU2.MX.TotVAr.mag.f
243 GGIO1.ST.Ind122.q 296 MMXU2.MX.TotVA.mag.f
244 GGIO1.ST.Ind122.stVal 297 MMXU2.MX.TotPF.mag.f
245 GGIO1.ST.Ind123.q 298 MMXU2.MX.Hz.mag.f
246 GGIO1.ST.Ind123.stVal 299 MMXU2.MX.PPV.phsAB.cVal.mag.f
247 GGIO1.ST.Ind124.q 300 MMXU2.MX.PPV.phsAB.cVal.ang.f

GE Multilin G60 Generator Protection System B-95


B.4 MEMORY MAPPING APPENDIX B

Enumeration GOOSE dataset items Enumeration GOOSE dataset items


301 MMXU2.MX.PPV.phsBC.cVal.mag.f 354 MMXU3.MX.A.neut.cVal.mag.f
302 MMXU2.MX.PPV.phsBC.cVal.ang.f 355 MMXU3.MX.A.neut.cVal.ang.f
303 MMXU2.MX.PPV.phsCA.cVal.mag.f 356 MMXU3.MX.W.phsA.cVal.mag.f
304 MMXU2.MX.PPV.phsCA.cVal.ang.f 357 MMXU3.MX.W.phsB.cVal.mag.f
305 MMXU2.MX.PhV.phsA.cVal.mag.f 358 MMXU3.MX.W.phsC.cVal.mag.f
306 MMXU2.MX.PhV.phsA.cVal.ang.f 359 MMXU3.MX.VAr.phsA.cVal.mag.f
B 307 MMXU2.MX.PhV.phsB.cVal.mag.f 360 MMXU3.MX.VAr.phsB.cVal.mag.f
308 MMXU2.MX.PhV.phsB.cVal.ang.f 361 MMXU3.MX.VAr.phsC.cVal.mag.f
309 MMXU2.MX.PhV.phsC.cVal.mag.f 362 MMXU3.MX.VA.phsA.cVal.mag.f
310 MMXU2.MX.PhV.phsC.cVal.ang.f 363 MMXU3.MX.VA.phsB.cVal.mag.f
311 MMXU2.MX.A.phsA.cVal.mag.f 364 MMXU3.MX.VA.phsC.cVal.mag.f
312 MMXU2.MX.A.phsA.cVal.ang.f 365 MMXU3.MX.PF.phsA.cVal.mag.f
313 MMXU2.MX.A.phsB.cVal.mag.f 366 MMXU3.MX.PF.phsB.cVal.mag.f
314 MMXU2.MX.A.phsB.cVal.ang.f 367 MMXU3.MX.PF.phsC.cVal.mag.f
315 MMXU2.MX.A.phsC.cVal.mag.f 368 MMXU4.MX.TotW.mag.f
316 MMXU2.MX.A.phsC.cVal.ang.f 369 MMXU4.MX.TotVAr.mag.f
317 MMXU2.MX.A.neut.cVal.mag.f 370 MMXU4.MX.TotVA.mag.f
318 MMXU2.MX.A.neut.cVal.ang.f 371 MMXU4.MX.TotPF.mag.f
319 MMXU2.MX.W.phsA.cVal.mag.f 372 MMXU4.MX.Hz.mag.f
320 MMXU2.MX.W.phsB.cVal.mag.f 373 MMXU4.MX.PPV.phsAB.cVal.mag.f
321 MMXU2.MX.W.phsC.cVal.mag.f 374 MMXU4.MX.PPV.phsAB.cVal.ang.f
322 MMXU2.MX.VAr.phsA.cVal.mag.f 375 MMXU4.MX.PPV.phsBC.cVal.mag.f
323 MMXU2.MX.VAr.phsB.cVal.mag.f 376 MMXU4.MX.PPV.phsBC.cVal.ang.f
324 MMXU2.MX.VAr.phsC.cVal.mag.f 377 MMXU4.MX.PPV.phsCA.cVal.mag.f
325 MMXU2.MX.VA.phsA.cVal.mag.f 378 MMXU4.MX.PPV.phsCA.cVal.ang.f
326 MMXU2.MX.VA.phsB.cVal.mag.f 379 MMXU4.MX.PhV.phsA.cVal.mag.f
327 MMXU2.MX.VA.phsC.cVal.mag.f 380 MMXU4.MX.PhV.phsA.cVal.ang.f
328 MMXU2.MX.PF.phsA.cVal.mag.f 381 MMXU4.MX.PhV.phsB.cVal.mag.f
329 MMXU2.MX.PF.phsB.cVal.mag.f 382 MMXU4.MX.PhV.phsB.cVal.ang.f
330 MMXU2.MX.PF.phsC.cVal.mag.f 383 MMXU4.MX.PhV.phsC.cVal.mag.f
331 MMXU3.MX.TotW.mag.f 384 MMXU4.MX.PhV.phsC.cVal.ang.f
332 MMXU3.MX.TotVAr.mag.f 385 MMXU4.MX.A.phsA.cVal.mag.f
333 MMXU3.MX.TotVA.mag.f 386 MMXU4.MX.A.phsA.cVal.ang.f
334 MMXU3.MX.TotPF.mag.f 387 MMXU4.MX.A.phsB.cVal.mag.f
335 MMXU3.MX.Hz.mag.f 388 MMXU4.MX.A.phsB.cVal.ang.f
336 MMXU3.MX.PPV.phsAB.cVal.mag.f 389 MMXU4.MX.A.phsC.cVal.mag.f
337 MMXU3.MX.PPV.phsAB.cVal.ang.f 390 MMXU4.MX.A.phsC.cVal.ang.f
338 MMXU3.MX.PPV.phsBC.cVal.mag.f 391 MMXU4.MX.A.neut.cVal.mag.f
339 MMXU3.MX.PPV.phsBC.cVal.ang.f 392 MMXU4.MX.A.neut.cVal.ang.f
340 MMXU3.MX.PPV.phsCA.cVal.mag.f 393 MMXU4.MX.W.phsA.cVal.mag.f
341 MMXU3.MX.PPV.phsCA.cVal.ang.f 394 MMXU4.MX.W.phsB.cVal.mag.f
342 MMXU3.MX.PhV.phsA.cVal.mag.f 395 MMXU4.MX.W.phsC.cVal.mag.f
343 MMXU3.MX.PhV.phsA.cVal.ang.f 396 MMXU4.MX.VAr.phsA.cVal.mag.f
344 MMXU3.MX.PhV.phsB.cVal.mag.f 397 MMXU4.MX.VAr.phsB.cVal.mag.f
345 MMXU3.MX.PhV.phsB.cVal.ang.f 398 MMXU4.MX.VAr.phsC.cVal.mag.f
346 MMXU3.MX.PhV.phsC.cVal.mag.f 399 MMXU4.MX.VA.phsA.cVal.mag.f
347 MMXU3.MX.PhV.phsC.cVal.ang.f 400 MMXU4.MX.VA.phsB.cVal.mag.f
348 MMXU3.MX.A.phsA.cVal.mag.f 401 MMXU4.MX.VA.phsC.cVal.mag.f
349 MMXU3.MX.A.phsA.cVal.ang.f 402 MMXU4.MX.PF.phsA.cVal.mag.f
350 MMXU3.MX.A.phsB.cVal.mag.f 403 MMXU4.MX.PF.phsB.cVal.mag.f
351 MMXU3.MX.A.phsB.cVal.ang.f 404 MMXU4.MX.PF.phsC.cVal.mag.f
352 MMXU3.MX.A.phsC.cVal.mag.f 405 MMXU5.MX.TotW.mag.f
353 MMXU3.MX.A.phsC.cVal.ang.f 406 MMXU5.MX.TotVAr.mag.f

B-96 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Enumeration GOOSE dataset items Enumeration GOOSE dataset items


407 MMXU5.MX.TotVA.mag.f 460 MMXU6.MX.A.phsA.cVal.ang.f
408 MMXU5.MX.TotPF.mag.f 461 MMXU6.MX.A.phsB.cVal.mag.f
409 MMXU5.MX.Hz.mag.f 462 MMXU6.MX.A.phsB.cVal.ang.f
410 MMXU5.MX.PPV.phsAB.cVal.mag.f 463 MMXU6.MX.A.phsC.cVal.mag.f
411 MMXU5.MX.PPV.phsAB.cVal.ang.f 464 MMXU6.MX.A.phsC.cVal.ang.f
412 MMXU5.MX.PPV.phsBC.cVal.mag.f 465 MMXU6.MX.A.neut.cVal.mag.f
413 MMXU5.MX.PPV.phsBC.cVal.ang.f 466 MMXU6.MX.A.neut.cVal.ang.f B
414 MMXU5.MX.PPV.phsCA.cVal.mag.f 467 MMXU6.MX.W.phsA.cVal.mag.f
415 MMXU5.MX.PPV.phsCA.cVal.ang.f 468 MMXU6.MX.W.phsB.cVal.mag.f
416 MMXU5.MX.PhV.phsA.cVal.mag.f 469 MMXU6.MX.W.phsC.cVal.mag.f
417 MMXU5.MX.PhV.phsA.cVal.ang.f 470 MMXU6.MX.VAr.phsA.cVal.mag.f
418 MMXU5.MX.PhV.phsB.cVal.mag.f 471 MMXU6.MX.VAr.phsB.cVal.mag.f
419 MMXU5.MX.PhV.phsB.cVal.ang.f 472 MMXU6.MX.VAr.phsC.cVal.mag.f
420 MMXU5.MX.PhV.phsC.cVal.mag.f 473 MMXU6.MX.VA.phsA.cVal.mag.f
421 MMXU5.MX.PhV.phsC.cVal.ang.f 474 MMXU6.MX.VA.phsB.cVal.mag.f
422 MMXU5.MX.A.phsA.cVal.mag.f 475 MMXU6.MX.VA.phsC.cVal.mag.f
423 MMXU5.MX.A.phsA.cVal.ang.f 476 MMXU6.MX.PF.phsA.cVal.mag.f
424 MMXU5.MX.A.phsB.cVal.mag.f 477 MMXU6.MX.PF.phsB.cVal.mag.f
425 MMXU5.MX.A.phsB.cVal.ang.f 478 MMXU6.MX.PF.phsC.cVal.mag.f
426 MMXU5.MX.A.phsC.cVal.mag.f 479 GGIO4.MX.AnIn1.mag.f
427 MMXU5.MX.A.phsC.cVal.ang.f 480 GGIO4.MX.AnIn2.mag.f
428 MMXU5.MX.A.neut.cVal.mag.f 481 GGIO4.MX.AnIn3.mag.f
429 MMXU5.MX.A.neut.cVal.ang.f 482 GGIO4.MX.AnIn4.mag.f
430 MMXU5.MX.W.phsA.cVal.mag.f 483 GGIO4.MX.AnIn5.mag.f
431 MMXU5.MX.W.phsB.cVal.mag.f 484 GGIO4.MX.AnIn6.mag.f
432 MMXU5.MX.W.phsC.cVal.mag.f 485 GGIO4.MX.AnIn7.mag.f
433 MMXU5.MX.VAr.phsA.cVal.mag.f 486 GGIO4.MX.AnIn8.mag.f
434 MMXU5.MX.VAr.phsB.cVal.mag.f 487 GGIO4.MX.AnIn9.mag.f
435 MMXU5.MX.VAr.phsC.cVal.mag.f 488 GGIO4.MX.AnIn10.mag.f
436 MMXU5.MX.VA.phsA.cVal.mag.f 489 GGIO4.MX.AnIn11.mag.f
437 MMXU5.MX.VA.phsB.cVal.mag.f 490 GGIO4.MX.AnIn12.mag.f
438 MMXU5.MX.VA.phsC.cVal.mag.f 491 GGIO4.MX.AnIn13.mag.f
439 MMXU5.MX.PF.phsA.cVal.mag.f 492 GGIO4.MX.AnIn14.mag.f
440 MMXU5.MX.PF.phsB.cVal.mag.f 493 GGIO4.MX.AnIn15.mag.f
441 MMXU5.MX.PF.phsC.cVal.mag.f 494 GGIO4.MX.AnIn16.mag.f
442 MMXU6.MX.TotW.mag.f 495 GGIO4.MX.AnIn17.mag.f
443 MMXU6.MX.TotVAr.mag.f 496 GGIO4.MX.AnIn18.mag.f
444 MMXU6.MX.TotVA.mag.f 497 GGIO4.MX.AnIn19.mag.f
445 MMXU6.MX.TotPF.mag.f 498 GGIO4.MX.AnIn20.mag.f
446 MMXU6.MX.Hz.mag.f 499 GGIO4.MX.AnIn21.mag.f
447 MMXU6.MX.PPV.phsAB.cVal.mag.f 500 GGIO4.MX.AnIn22.mag.f
448 MMXU6.MX.PPV.phsAB.cVal.ang.f 501 GGIO4.MX.AnIn23.mag.f
449 MMXU6.MX.PPV.phsBC.cVal.mag.f 502 GGIO4.MX.AnIn24.mag.f
450 MMXU6.MX.PPV.phsBC.cVal.ang.f 503 GGIO4.MX.AnIn25.mag.f
451 MMXU6.MX.PPV.phsCA.cVal.mag.f 504 GGIO4.MX.AnIn26.mag.f
452 MMXU6.MX.PPV.phsCA.cVal.ang.f 505 GGIO4.MX.AnIn27.mag.f
453 MMXU6.MX.PhV.phsA.cVal.mag.f 506 GGIO4.MX.AnIn28.mag.f
454 MMXU6.MX.PhV.phsA.cVal.ang.f 507 GGIO4.MX.AnIn29.mag.f
455 MMXU6.MX.PhV.phsB.cVal.mag.f 508 GGIO4.MX.AnIn30.mag.f
456 MMXU6.MX.PhV.phsB.cVal.ang.f 509 GGIO4.MX.AnIn31.mag.f
457 MMXU6.MX.PhV.phsC.cVal.mag.f 510 GGIO4.MX.AnIn32.mag.f
458 MMXU6.MX.PhV.phsC.cVal.ang.f 511 GGIO5.ST.UIntIn1.q
459 MMXU6.MX.A.phsA.cVal.mag.f 512 GGIO5.ST.UIntIn1.stVal

GE Multilin G60 Generator Protection System B-97


B.4 MEMORY MAPPING APPENDIX B

Enumeration GOOSE dataset items Enumeration GOOSE dataset items


513 GGIO5.ST.UIntIn2.q 566 PDIS8.ST.Op.general
514 GGIO5.ST.UIntIn2.stVal 567 PDIS9.ST.Str.general
515 GGIO5.ST.UIntIn3.q 568 PDIS9.ST.Op.general
516 GGIO5.ST.UIntIn3.stVal 569 PDIS10.ST.Str.general
517 GGIO5.ST.UIntIn4.q 570 PDIS10.ST.Op.general
518 GGIO5.ST.UIntIn4.stVal 571 PIOC1.ST.Str.general
B 519 GGIO5.ST.UIntIn5.q 572 PIOC1.ST.Op.general
520 GGIO5.ST.UIntIn5.stVal 573 PIOC2.ST.Str.general
521 GGIO5.ST.UIntIn6.q 574 PIOC2.ST.Op.general
522 GGIO5.ST.UIntIn6.stVal 575 PIOC3.ST.Str.general
523 GGIO5.ST.UIntIn7.q 576 PIOC3.ST.Op.general
524 GGIO5.ST.UIntIn7.stVal 577 PIOC4.ST.Str.general
525 GGIO5.ST.UIntIn8.q 578 PIOC4.ST.Op.general
526 GGIO5.ST.UIntIn8.stVal 579 PIOC5.ST.Str.general
527 GGIO5.ST.UIntIn9.q 580 PIOC5.ST.Op.general
528 GGIO5.ST.UIntIn9.stVal 581 PIOC6.ST.Str.general
529 GGIO5.ST.UIntIn10.q 582 PIOC6.ST.Op.general
530 GGIO5.ST.UIntIn10.stVal 583 PIOC7.ST.Str.general
531 GGIO5.ST.UIntIn11.q 584 PIOC7.ST.Op.general
532 GGIO5.ST.UIntIn11.stVal 585 PIOC8.ST.Str.general
533 GGIO5.ST.UIntIn12.q 586 PIOC8.ST.Op.general
534 GGIO5.ST.UIntIn12.stVal 587 PIOC9.ST.Str.general
535 GGIO5.ST.UIntIn13.q 588 PIOC9.ST.Op.general
536 GGIO5.ST.UIntIn13.stVal 589 PIOC10.ST.Str.general
537 GGIO5.ST.UIntIn14.q 590 PIOC10.ST.Op.general
538 GGIO5.ST.UIntIn14.stVal 591 PIOC11.ST.Str.general
539 GGIO5.ST.UIntIn15.q 592 PIOC11.ST.Op.general
540 GGIO5.ST.UIntIn15.stVal 593 PIOC12.ST.Str.general
541 GGIO5.ST.UIntIn16.q 594 PIOC12.ST.Op.general
542 GGIO5.ST.UIntIn16.stVal 595 PIOC13.ST.Str.general
543 PDIF1.ST.Str.general 596 PIOC13.ST.Op.general
544 PDIF1.ST.Op.general 597 PIOC14.ST.Str.general
545 PDIF2.ST.Str.general 598 PIOC14.ST.Op.general
546 PDIF2.ST.Op.general 599 PIOC15.ST.Str.general
547 PDIF3.ST.Str.general 600 PIOC15.ST.Op.general
548 PDIF3.ST.Op.general 601 PIOC16.ST.Str.general
549 PDIF4.ST.Str.general 602 PIOC16.ST.Op.general
550 PDIF4.ST.Op.general 603 PIOC17.ST.Str.general
551 PDIS1.ST.Str.general 604 PIOC17.ST.Op.general
552 PDIS1.ST.Op.general 605 PIOC18.ST.Str.general
553 PDIS2.ST.Str.general 606 PIOC18.ST.Op.general
554 PDIS2.ST.Op.general 607 PIOC19.ST.Str.general
555 PDIS3.ST.Str.general 608 PIOC19.ST.Op.general
556 PDIS3.ST.Op.general 609 PIOC20.ST.Str.general
557 PDIS4.ST.Str.general 610 PIOC20.ST.Op.general
558 PDIS4.ST.Op.general 611 PIOC21.ST.Str.general
559 PDIS5.ST.Str.general 612 PIOC21.ST.Op.general
560 PDIS5.ST.Op.general 613 PIOC22.ST.Str.general
561 PDIS6.ST.Str.general 614 PIOC22.ST.Op.general
562 PDIS6.ST.Op.general 615 PIOC23.ST.Str.general
563 PDIS7.ST.Str.general 616 PIOC23.ST.Op.general
564 PDIS7.ST.Op.general 617 PIOC24.ST.Str.general
565 PDIS8.ST.Str.general 618 PIOC24.ST.Op.general

B-98 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Enumeration GOOSE dataset items Enumeration GOOSE dataset items


619 PIOC25.ST.Str.general 672 PIOC51.ST.Op.general
620 PIOC25.ST.Op.general 673 PIOC52.ST.Str.general
621 PIOC26.ST.Str.general 674 PIOC52.ST.Op.general
622 PIOC26.ST.Op.general 675 PIOC53.ST.Str.general
623 PIOC27.ST.Str.general 676 PIOC53.ST.Op.general
624 PIOC27.ST.Op.general 677 PIOC54.ST.Str.general
625 PIOC28.ST.Str.general 678 PIOC54.ST.Op.general B
626 PIOC28.ST.Op.general 679 PIOC55.ST.Str.general
627 PIOC29.ST.Str.general 680 PIOC55.ST.Op.general
628 PIOC29.ST.Op.general 681 PIOC56.ST.Str.general
629 PIOC30.ST.Str.general 682 PIOC56.ST.Op.general
630 PIOC30.ST.Op.general 683 PIOC57.ST.Str.general
631 PIOC31.ST.Str.general 684 PIOC57.ST.Op.general
632 PIOC31.ST.Op.general 685 PIOC58.ST.Str.general
633 PIOC32.ST.Str.general 686 PIOC58.ST.Op.general
634 PIOC32.ST.Op.general 687 PIOC59.ST.Str.general
635 PIOC33.ST.Str.general 688 PIOC59.ST.Op.general
636 PIOC33.ST.Op.general 689 PIOC60.ST.Str.general
637 PIOC34.ST.Str.general 690 PIOC60.ST.Op.general
638 PIOC34.ST.Op.general 691 PIOC61.ST.Str.general
639 PIOC35.ST.Str.general 692 PIOC61.ST.Op.general
640 PIOC35.ST.Op.general 693 PIOC62.ST.Str.general
641 PIOC36.ST.Str.general 694 PIOC62.ST.Op.general
642 PIOC36.ST.Op.general 695 PIOC63.ST.Str.general
643 PIOC37.ST.Str.general 696 PIOC63.ST.Op.general
644 PIOC37.ST.Op.general 697 PIOC64.ST.Str.general
645 PIOC38.ST.Str.general 698 PIOC64.ST.Op.general
646 PIOC38.ST.Op.general 699 PIOC65.ST.Str.general
647 PIOC39.ST.Str.general 700 PIOC65.ST.Op.general
648 PIOC39.ST.Op.general 701 PIOC66.ST.Str.general
649 PIOC40.ST.Str.general 702 PIOC66.ST.Op.general
650 PIOC40.ST.Op.general 703 PIOC67.ST.Str.general
651 PIOC41.ST.Str.general 704 PIOC67.ST.Op.general
652 PIOC41.ST.Op.general 705 PIOC68.ST.Str.general
653 PIOC42.ST.Str.general 706 PIOC68.ST.Op.general
654 PIOC42.ST.Op.general 707 PIOC69.ST.Str.general
655 PIOC43.ST.Str.general 708 PIOC69.ST.Op.general
656 PIOC43.ST.Op.general 709 PIOC70.ST.Str.general
657 PIOC44.ST.Str.general 710 PIOC70.ST.Op.general
658 PIOC44.ST.Op.general 711 PIOC71.ST.Str.general
659 PIOC45.ST.Str.general 712 PIOC71.ST.Op.general
660 PIOC45.ST.Op.general 713 PIOC72.ST.Str.general
661 PIOC46.ST.Str.general 714 PIOC72.ST.Op.general
662 PIOC46.ST.Op.general 715 PTOC1.ST.Str.general
663 PIOC47.ST.Str.general 716 PTOC1.ST.Op.general
664 PIOC47.ST.Op.general 717 PTOC2.ST.Str.general
665 PIOC48.ST.Str.general 718 PTOC2.ST.Op.general
666 PIOC48.ST.Op.general 719 PTOC3.ST.Str.general
667 PIOC49.ST.Str.general 720 PTOC3.ST.Op.general
668 PIOC49.ST.Op.general 721 PTOC4.ST.Str.general
669 PIOC50.ST.Str.general 722 PTOC4.ST.Op.general
670 PIOC50.ST.Op.general 723 PTOC5.ST.Str.general
671 PIOC51.ST.Str.general 724 PTOC5.ST.Op.general

GE Multilin G60 Generator Protection System B-99


B.4 MEMORY MAPPING APPENDIX B

Enumeration GOOSE dataset items Enumeration GOOSE dataset items


725 PTOC6.ST.Str.general 778 PTOV8.ST.Op.general
726 PTOC6.ST.Op.general 779 PTOV9.ST.Str.general
727 PTOC7.ST.Str.general 780 PTOV9.ST.Op.general
728 PTOC7.ST.Op.general 781 PTOV10.ST.Str.general
729 PTOC8.ST.Str.general 782 PTOV10.ST.Op.general
730 PTOC8.ST.Op.general 783 PTRC1.ST.Tr.general
B 731 PTOC9.ST.Str.general 784 PTRC1.ST.Op.general
732 PTOC9.ST.Op.general 785 PTRC2.ST.Tr.general
733 PTOC10.ST.Str.general 786 PTRC2.ST.Op.general
734 PTOC10.ST.Op.general 787 PTRC3.ST.Tr.general
735 PTOC11.ST.Str.general 788 PTRC3.ST.Op.general
736 PTOC11.ST.Op.general 789 PTRC4.ST.Tr.general
737 PTOC12.ST.Str.general 790 PTRC4.ST.Op.general
738 PTOC12.ST.Op.general 791 PTRC5.ST.Tr.general
739 PTOC13.ST.Str.general 792 PTRC5.ST.Op.general
740 PTOC13.ST.Op.general 793 PTRC6.ST.Tr.general
741 PTOC14.ST.Str.general 794 PTRC6.ST.Op.general
742 PTOC14.ST.Op.general 795 PTUV1.ST.Str.general
743 PTOC15.ST.Str.general 796 PTUV1.ST.Op.general
744 PTOC15.ST.Op.general 797 PTUV2.ST.Str.general
745 PTOC16.ST.Str.general 798 PTUV2.ST.Op.general
746 PTOC16.ST.Op.general 799 PTUV3.ST.Str.general
747 PTOC17.ST.Str.general 800 PTUV3.ST.Op.general
748 PTOC17.ST.Op.general 801 PTUV4.ST.Str.general
749 PTOC18.ST.Str.general 802 PTUV4.ST.Op.general
750 PTOC18.ST.Op.general 803 PTUV5.ST.Str.general
751 PTOC19.ST.Str.general 804 PTUV5.ST.Op.general
752 PTOC19.ST.Op.general 805 PTUV6.ST.Str.general
753 PTOC20.ST.Str.general 806 PTUV6.ST.Op.general
754 PTOC20.ST.Op.general 807 PTUV7.ST.Str.general
755 PTOC21.ST.Str.general 808 PTUV7.ST.Op.general
756 PTOC21.ST.Op.general 809 PTUV8.ST.Str.general
757 PTOC22.ST.Str.general 810 PTUV8.ST.Op.general
758 PTOC22.ST.Op.general 811 PTUV9.ST.Str.general
759 PTOC23.ST.Str.general 812 PTUV9.ST.Op.general
760 PTOC23.ST.Op.general 813 PTUV10.ST.Str.general
761 PTOC24.ST.Str.general 814 PTUV10.ST.Op.general
762 PTOC24.ST.Op.general 815 PTUV11.ST.Str.general
763 PTOV1.ST.Str.general 816 PTUV11.ST.Op.general
764 PTOV1.ST.Op.general 817 PTUV12.ST.Str.general
765 PTOV2.ST.Str.general 818 PTUV12.ST.Op.general
766 PTOV2.ST.Op.general 819 PTUV13.ST.Str.general
767 PTOV3.ST.Str.general 820 PTUV13.ST.Op.general
768 PTOV3.ST.Op.general 821 RBRF1.ST.OpEx.general
769 PTOV4.ST.Str.general 822 RBRF1.ST.OpIn.general
770 PTOV4.ST.Op.general 823 RBRF2.ST.OpEx.general
771 PTOV5.ST.Str.general 824 RBRF2.ST.OpIn.general
772 PTOV5.ST.Op.general 825 RBRF3.ST.OpEx.general
773 PTOV6.ST.Str.general 826 RBRF3.ST.OpIn.general
774 PTOV6.ST.Op.general 827 RBRF4.ST.OpEx.general
775 PTOV7.ST.Str.general 828 RBRF4.ST.OpIn.general
776 PTOV7.ST.Op.general 829 RBRF5.ST.OpEx.general
777 PTOV8.ST.Str.general 830 RBRF5.ST.OpIn.general

B-100 G60 Generator Protection System GE Multilin


APPENDIX B B.4 MEMORY MAPPING

Enumeration GOOSE dataset items Enumeration GOOSE dataset items


831 RBRF6.ST.OpEx.general 884 RREC4.ST.AutoRecSt.stVal
832 RBRF6.ST.OpIn.general 885 RREC5.ST.Op.general
833 RBRF7.ST.OpEx.general 886 RREC5.ST.AutoRecSt.stVal
834 RBRF7.ST.OpIn.general 887 RREC6.ST.Op.general
835 RBRF8.ST.OpEx.general 888 RREC6.ST.AutoRecSt.stVal
836 RBRF8.ST.OpIn.general 889 CSWI1.ST.Loc.stVal
837 RBRF9.ST.OpEx.general 890 CSWI1.ST.Pos.stVal B
838 RBRF9.ST.OpIn.general 891 CSWI2.ST.Loc.stVal
839 RBRF10.ST.OpEx.general 892 CSWI2.ST.Pos.stVal
840 RBRF10.ST.OpIn.general 893 CSWI3.ST.Loc.stVal
841 RBRF11.ST.OpEx.general 894 CSWI3.ST.Pos.stVal
842 RBRF11.ST.OpIn.general 895 CSWI4.ST.Loc.stVal
843 RBRF12.ST.OpEx.general 896 CSWI4.ST.Pos.stVal
844 RBRF12.ST.OpIn.general 897 CSWI5.ST.Loc.stVal
845 RBRF13.ST.OpEx.general 898 CSWI5.ST.Pos.stVal
846 RBRF13.ST.OpIn.general 899 CSWI6.ST.Loc.stVal
847 RBRF14.ST.OpEx.general 900 CSWI6.ST.Pos.stVal
848 RBRF14.ST.OpIn.general 901 CSWI7.ST.Loc.stVal
849 RBRF15.ST.OpEx.general 902 CSWI7.ST.Pos.stVal
850 RBRF15.ST.OpIn.general 903 CSWI8.ST.Loc.stVal
851 RBRF16.ST.OpEx.general 904 CSWI8.ST.Pos.stVal
852 RBRF16.ST.OpIn.general 905 CSWI9.ST.Loc.stVal
853 RBRF17.ST.OpEx.general 906 CSWI9.ST.Pos.stVal
854 RBRF17.ST.OpIn.general 907 CSWI10.ST.Loc.stVal
855 RBRF18.ST.OpEx.general 908 CSWI10.ST.Pos.stVal
856 RBRF18.ST.OpIn.general 909 CSWI11.ST.Loc.stVal
857 RBRF19.ST.OpEx.general 910 CSWI11.ST.Pos.stVal
858 RBRF19.ST.OpIn.general 911 CSWI12.ST.Loc.stVal
859 RBRF20.ST.OpEx.general 912 CSWI12.ST.Pos.stVal
860 RBRF20.ST.OpIn.general 913 CSWI13.ST.Loc.stVal
861 RBRF21.ST.OpEx.general 914 CSWI13.ST.Pos.stVal
862 RBRF21.ST.OpIn.general 915 CSWI14.ST.Loc.stVal
863 RBRF22.ST.OpEx.general 916 CSWI14.ST.Pos.stVal
864 RBRF22.ST.OpIn.general 917 CSWI15.ST.Loc.stVal
865 RBRF23.ST.OpEx.general 918 CSWI15.ST.Pos.stVal
866 RBRF23.ST.OpIn.general 919 CSWI16.ST.Loc.stVal
867 RBRF24.ST.OpEx.general 920 CSWI16.ST.Pos.stVal
868 RBRF24.ST.OpIn.general 921 CSWI17.ST.Loc.stVal
869 RFLO1.MX.FltDiskm.mag.f 922 CSWI17.ST.Pos.stVal
870 RFLO2.MX.FltDiskm.mag.f 923 CSWI18.ST.Loc.stVal
871 RFLO3.MX.FltDiskm.mag.f 924 CSWI18.ST.Pos.stVal
872 RFLO4.MX.FltDiskm.mag.f 925 CSWI19.ST.Loc.stVal
873 RFLO5.MX.FltDiskm.mag.f 926 CSWI19.ST.Pos.stVal
874 RPSB1.ST.Str.general 927 CSWI20.ST.Loc.stVal
875 RPSB1.ST.Op.general 928 CSWI20.ST.Pos.stVal
876 RPSB1.ST.BlkZn.stVal 929 CSWI21.ST.Loc.stVal
877 RREC1.ST.Op.general 930 CSWI21.ST.Pos.stVal
878 RREC1.ST.AutoRecSt.stVal 931 CSWI22.ST.Loc.stVal
879 RREC2.ST.Op.general 932 CSWI22.ST.Pos.stVal
880 RREC2.ST.AutoRecSt.stVal 933 CSWI23.ST.Loc.stVal
881 RREC3.ST.Op.general 934 CSWI23.ST.Pos.stVal
882 RREC3.ST.AutoRecSt.stVal 935 CSWI24.ST.Loc.stVal
883 RREC4.ST.Op.general 936 CSWI24.ST.Pos.stVal

GE Multilin G60 Generator Protection System B-101


B.4 MEMORY MAPPING APPENDIX B

Enumeration GOOSE dataset items Enumeration GOOSE dataset items


937 CSWI25.ST.Loc.stVal 990 XSWI21.ST.Pos.stVal
938 CSWI25.ST.Pos.stVal 991 XSWI22.ST.Loc.stVal
939 CSWI26.ST.Loc.stVal 992 XSWI22.ST.Pos.stVal
940 CSWI26.ST.Pos.stVal 993 XSWI23.ST.Loc.stVal
941 CSWI27.ST.Loc.stVal 994 XSWI23.ST.Pos.stVal
942 CSWI27.ST.Pos.stVal 995 XSWI24.ST.Loc.stVal
B 943 CSWI28.ST.Loc.stVal 996 XSWI24.ST.Pos.stVal
944 CSWI28.ST.Pos.stVal 997 XCBR1.ST.Loc.stVal
945 CSWI29.ST.Loc.stVal 998 XCBR1.ST.Pos.stVal
946 CSWI29.ST.Pos.stVal 999 XCBR2.ST.Loc.stVal
947 CSWI30.ST.Loc.stVal 1000 XCBR2.ST.Pos.stVal
948 CSWI30.ST.Pos.stVal 1001 XCBR3.ST.Loc.stVal
949 XSWI1.ST.Loc.stVal 1002 XCBR3.ST.Pos.stVal
950 XSWI1.ST.Pos.stVal 1003 XCBR4.ST.Loc.stVal
951 XSWI2.ST.Loc.stVal 1004 XCBR4.ST.Pos.stVal
952 XSWI2.ST.Pos.stVal 1005 XCBR5.ST.Loc.stVal
953 XSWI3.ST.Loc.stVal 1006 XCBR5.ST.Pos.stVal
954 XSWI3.ST.Pos.stVal 1007 XCBR6.ST.Loc.stVal
955 XSWI4.ST.Loc.stVal 1008 XCBR6.ST.Pos.stVal
956 XSWI4.ST.Pos.stVal
957 XSWI5.ST.Loc.stVal
958 XSWI5.ST.Pos.stVal
959 XSWI6.ST.Loc.stVal
960 XSWI6.ST.Pos.stVal
961 XSWI7.ST.Loc.stVal
962 XSWI7.ST.Pos.stVal
963 XSWI8.ST.Loc.stVal
964 XSWI8.ST.Pos.stVal
965 XSWI9.ST.Loc.stVal
966 XSWI9.ST.Pos.stVal
967 XSWI10.ST.Loc.stVal
968 XSWI10.ST.Pos.stVal
969 XSWI11.ST.Loc.stVal
970 XSWI11.ST.Pos.stVal
971 XSWI12.ST.Loc.stVal
972 XSWI12.ST.Pos.stVal
973 XSWI13.ST.Loc.stVal
974 XSWI13.ST.Pos.stVal
975 XSWI14.ST.Loc.stVal
976 XSWI14.ST.Pos.stVal
977 XSWI15.ST.Loc.stVal
978 XSWI15.ST.Pos.stVal
979 XSWI16.ST.Loc.stVal
980 XSWI16.ST.Pos.stVal
981 XSWI17.ST.Loc.stVal
982 XSWI17.ST.Pos.stVal
983 XSWI18.ST.Loc.stVal
984 XSWI18.ST.Pos.stVal
985 XSWI19.ST.Loc.stVal
986 XSWI19.ST.Pos.stVal
987 XSWI20.ST.Loc.stVal
988 XSWI20.ST.Pos.stVal
989 XSWI21.ST.Loc.stVal

B-102 G60 Generator Protection System GE Multilin


APPENDIX C C.1 OVERVIEW

APPENDIX C IEC 61850 COMMUNICATIONSC.1OVERVIEW C.1.1 INTRODUCTION

The IEC 61850 standard is the result of electric utilities and vendors of electronic equipment to produce standardized com-
munications systems. IEC 61850 is a series of standards describing client/server and peer-to-peer communications, sub-
station design and configuration, testing, environmental and project standards. The complete set includes:
• IEC 61850-1: Introduction and overview
• IEC 61850-2: Glossary
• IEC 61850-3: General requirements
• IEC 61850-4: System and project management
• IEC 61850-5: Communications and requirements for functions and device models
• IEC 61850-6: Configuration description language for communication in electrical substations related to IEDs
• IEC 61850-7-1: Basic communication structure for substation and feeder equipment - Principles and models
C
• IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract communication service
interface (ACSI)
• IEC 61850-7-3: Basic communication structure for substation and feeder equipment – Common data classes
• IEC 61850-7-4: Basic communication structure for substation and feeder equipment – Compatible logical node classes
and data classes
• IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO 9506-1 and ISO 9506-2)
and to ISO/IEC 8802-3
• IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over serial unidirectional multi-
drop point to point link
• IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over ISO/IEC 8802-3
• IEC 61850-10: Conformance testing
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended that all those involved with
any IEC 61850 implementation obtain this document set.

C.1.2 COMMUNICATION PROFILES

IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper (application) layer for transfer
of real-time data. This protocol has been in existence for several of years and provides a set of services suitable for the
transfer of data within a substation LAN environment. Actual MMS protocol services are mapped to IEC 61850 abstract ser-
vices in IEC 61850-8-1.
The G60 relay supports IEC 61850 server services over both TCP/IP and TP4/CLNP (OSI) communication protocol stacks.
The TP4/CLNP profile requires the G60 to have a network address or Network Service Access Point (NSAP) to establish a
communication link. The TCP/IP profile requires the G60 to have an IP address to establish communications. These
addresses are located in the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK menu. Note that the G60
supports IEC 61850 over the TP4/CLNP or TCP/IP stacks, and also operation over both stacks simultaneously. It is possi-
ble to have up to five simultaneous connections (in addition to DNP and Modbus/TCP (non-IEC 61850) connections).
• Client/server: This is a connection-oriented type of communication. The connection is initiated by the client, and com-
munication activity is controlled by the client. IEC 61850 clients are often substation computers running HMI programs
or SOE logging software. Servers are usually substation equipment such as protection relays, meters, RTUs, trans-
former tap changers, or bay controllers.
• Peer-to-peer: This is a non-connection-oriented, high speed type of communication usually between substation equip-
ment such as protection relays. GSSE and GOOSE are methods of peer-to-peer communication.
• Substation configuration language (SCL): A substation configuration language is a number of files used to describe
the configuration of substation equipment. Each configured device has an IEC Capability Description (ICD) file. The
substation single line information is stored in a System Specification Description (SSD) file. The entire substation con-
figuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the combination of the individ-
ual ICD files and the SSD file.

GE Multilin G60 Generator Protection System C-1


C.2 SERVER DATA ORGANIZATION APPENDIX C

C.2SERVER DATA ORGANIZATION C.2.1 OVERVIEW

IEC 61850 defines an object-oriented approach to data and services. An IEC 61850 physical device can contain one or
more logical device(s). Each logical device can contain many logical nodes. Each logical node can contain many data
objects. Each data object is composed of data attributes and data attribute components. Services are available at each
level for performing various functions, such as reading, writing, control commands, and reporting.
Each G60 IED represents one IEC 61850 physical device. The physical device contains one logical device, and the logical
device contains many logical nodes. The logical node LPHD1 contains information about the G60 IED physical device. The
logical node LLN0 contains information about the G60 IED logical device.

C.2.2 GGIO1: DIGITAL STATUS VALUES

C The GGIO1 logical node is available in the G60 to provide access to as many 128 digital status points and associated time-
stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status
points for access by clients.
It is intended that clients use GGIO1 in order to access digital status values from the G60. Configuration settings are pro-
vided to allow the selection of the number of digital status indications available in GGIO1 (8 to 128), and to allow the choice
of the G60 FlexLogic™ operands that drive the status of the GGIO1 status indications. Clients can utilize the IEC 61850
buffered and unbuffered reporting features available from GGIO1 in order to build sequence of events (SOE) logs and HMI
display screens. Buffered reporting should generally be used for SOE logs since the buffering capability reduces the
chances of missing data state changes. Unbuffered reporting should generally be used for local status display.

C.2.3 GGIO2: DIGITAL CONTROL VALUES

The GGIO2 logical node is available to provide access to the G60 virtual inputs. Virtual inputs are single-point control
(binary) values that can be written by clients. They are generally used as control inputs. GGIO2 provides access to the vir-
tual inputs through the IEC 61850 standard control model (ctlModel) services:
• Status only.
• Direct control with normal security.
• SBO control with normal security.
Configuration settings are available to select the control model for each point. Each virtual input used through GGIO2
should have its VIRTUAL INPUT 1(64) FUNCTION setting programmed as “Enabled” and its corresponding GGIO2 CF SPSCO1(64)
CTLMODEL setting programmed to the appropriate control configuration.

C.2.4 GGIO3: DIGITAL STATUS AND ANALOG VALUES FROM RECEIVED GOOSE DATA

The GGIO3 logical node is available to provide access for clients to values received via configurable GOOSE messages.
The values of the digital status indications and analog values in GGIO3 originate in GOOSE messages sent from other
devices.

C.2.5 GGIO4: GENERIC ANALOG MEASURED VALUES

The GGIO4 logical node provides access to as many as 32 analog value points, as well as associated timestamps and
quality flags. The data content must be configured before the data can be used. GGIO4 provides analog values for access
by clients.
It is intended that clients use GGIO4 to access generic analog values from the G60. Configuration settings allow the selec-
tion of the number of analog values available in GGIO4 (4 to 32) and the choice of the FlexAnalog™ values that determine
the value of the GGIO4 analog inputs. Clients can utilize polling or the IEC 61850 unbuffered reporting feature available
from GGIO4 in order to obtain the analog values provided by GGIO4.

C-2 G60 Generator Protection System GE Multilin


APPENDIX C C.2 SERVER DATA ORGANIZATION

C.2.6 MMXU: ANALOG MEASURED VALUES

A limited number of measured analog values are available through the MMXU logical nodes.
Each MMXU logical node provides data from a G60 current and voltage source. There is one MMXU available for each
configurable source (programmed in the SETTINGS ÖØ SYSTEM SETUP ÖØ SIGNAL SOURCES menu). MMXU1 provides data
from G60 source 1, and MMXU2 provides data from G60 source 2.
MMXU data is provided in two forms: instantaneous and deadband. The instantaneous values are updated every time a
read operation is performed by a client. The deadband values are calculated as described in IEC 61850 parts 7-1 and 7-3.
The selection of appropriate deadband settings for the G60 is described in chapter 5 of this manual.
IEC 61850 buffered and unbuffered reporting capability is available in all MMXU logical nodes. MMXUx logical nodes pro-
vide the following data for each source:
• MMXU1.MX.TotW: three-phase real power
• MMXU1.MX.TotVAr: three-phase reactive power
C
• MMXU1.MX.TotVA: three-phase apparent power
• MMXU1.MX.TotPF: three-phase power factor
• MMXU1.MX.Hz: frequency
• MMXU1.MX.PPV.phsAB: phase AB voltage magnitude and angle
• MMXU1.MX.PPV.phsBC: phase BC voltage magnitude and angle
• MMXU1.MX.PPV.phsCA: Phase CA voltage magnitude and angle
• MMXU1.MX.PhV.phsA: phase AG voltage magnitude and angle
• MMXU1.MX.PhV.phsB: phase BG voltage magnitude and angle
• MMXU1.MX.PhV.phsC: phase CG voltage magnitude and angle
• MMXU1.MX.A.phsA: phase A current magnitude and angle
• MMXU1.MX.A.phsB: phase B current magnitude and angle
• MMXU1.MX.A.phsC: phase C current magnitude and angle
• MMXU1.MX.A.neut: ground current magnitude and angle
• MMXU1.MX.W.phsA: phase A real power
• MMXU1.MX.W.phsB: phase B real power
• MMXU1.MX.W.phsC: phase C real power
• MMXU1.MX.VAr.phsA: phase A reactive power
• MMXU1.MX.VAr.phsB: phase B reactive power
• MMXU1.MX.VAr.phsC: phase C reactive power
• MMXU1.MX.VA.phsA: phase A apparent power
• MMXU1.MX.VA.phsB: phase B apparent power
• MMXU1.MX.VA.phsC: phase C apparent power
• MMXU1.MX.PF.phsA: phase A power factor
• MMXU1.MX.PF.phsB: phase B power factor
• MMXU1.MX.PF.phsC: phase C power factor

C.2.7 PROTECTION AND OTHER LOGICAL NODES

The following list describes the protection elements for all UR-series relays. The G60 relay will contain a subset of protec-
tion elements from this list.
• PDIF: bus differential, transformer instantaneous differential, transformer percent differential, current differential

GE Multilin G60 Generator Protection System C-3


C.2 SERVER DATA ORGANIZATION APPENDIX C

• PDIS: phase distance, ground distance


• PIOC: phase instantaneous overcurrent, neutral instantaneous overcurrent, ground instantaneous overcurrent, nega-
tive-sequence instantaneous overcurrent.
• PTOC: phase time overcurrent, neutral time overcurrent, ground time overcurrent, negative-sequence time overcur-
rent, neutral directional overcurrent, negative-sequence directional overcurrent
• PTUV: phase undervoltage, auxiliary undervoltage, third harmonic neutral undervoltage
• PTOV: phase overvoltage, neutral overvoltage, auxiliary overvoltage, negative sequence overvoltage
• RBRF: breaker failure
• RREC: autoreclosure
• RPSB: power swing detection

C • RFLO: fault locator


• XCBR: breaker control
• XSWI: circuit switch
• CSWI: switch controller
The protection elements listed above contain start (pickup) and operate flags. For example, the start flag for PIOC1 is
PIOC1.ST.Str.general. The operate flag for PIOC1 is PIOC1.ST.Op.general. For the G60 protection elements, these flags
take their values from the pickup and operate FlexLogic™ operands for the corresponding element.
Some protection elements listed above contain directional start values. For example, the directional start value for PDIS1 is
PDIS1.ST.Str.dirGeneral. This value is built from the directional FlexLogic™ operands for the element.
The RFLO logical node contains the measurement of the distance to fault calculation in kilometers. This value originates in
the fault locator function.
The XCBR logical node is directly associated with the breaker control feature.
• XCBR1.ST.Loc: This is the state of the XCBR1 local/remote switch. A setting is provided to assign a FlexLogic™ oper-
and to determine the state. When local mode is true, IEC 61850 client commands will be rejected.
• XCBR1.ST.Opcnt: This is an operation counter as defined in IEC 61850. Command settings are provided to allow the
counter to be cleared.
• XCBR1.ST.Pos: This is the position of the breaker. The breaker control FlexLogic™ operands are used to determine
this state.
– Intermediate state (00) is indicated when the BREAKER 1 OPEN and BREAKER 1 CLOSED operands are both On.
– Off state (01) is indicated when the BREAKER 1 OPEN operand is On.
– On state (10) is indicated when the BREAKER 1 CLOSED operand is On.
– Bad state (11) is indicated when the BREAKER 1 OPEN and BREAKER 1 CLOSED operands are Off.
• XCBR1.ST.BlkOpn: This is the state of the block open command logic. When true, breaker open commands from IEC
61850 clients will be rejected.
• XCBR1.ST.BlkCls: This is the state of the block close command logic. When true, breaker close commands from IEC
61850 clients will be rejected.
• XCBR1.CO.Pos: This is where IEC 61850 clients can issue open or close commands to the breaker. SBO control with
normal security is the only supported IEC 61850 control model.
• XCBR1.CO.BlkOpn: This is where IEC 61850 clients can issue block open commands to the breaker. Direct control
with normal security is the only supported IEC 61850 control model.
• XCBR1.CO.BlkCls: This is where IEC 61850 clients can issue block close commands to the breaker. Direct control
with normal security is the only supported IEC 61850 control model.

C-4 G60 Generator Protection System GE Multilin


APPENDIX C C.3 SERVER FEATURES AND CONFIGURATION

C.3SERVER FEATURES AND CONFIGURATION C.3.1 BUFFERED/UNBUFFERED REPORTING

IEC 61850 buffered and unbuffered reporting is provided in the GGIO1 logical nodes (for binary status values) and MMXU1
to MMXU6 (for analog measured values). Report settings can be configured using the EnerVista UR Setup software, sub-
station configurator software, or via an IEC 61850 client. The following items can be configured:
• TrgOps: Trigger options. The following bits are supported by the G60:
– Bit 1: data-change
– Bit 4: integrity
– Bit 5: general interrogation
• OptFlds: Option Fields. The following bits are supported by the G60:
– Bit 1: sequence-number
– Bit 2: report-time-stamp
C
– Bit 3: reason-for-inclusion
– Bit 4: data-set-name
– Bit 5: data-reference
– Bit 6: buffer-overflow (for buffered reports only)
– Bit 7: entryID (for buffered reports only)
– Bit 8: conf-revision
– Bit 9: segmentation
• IntgPd: Integrity period.
• BufTm: Buffer time.

C.3.2 FILE TRANSFER

MMS file services are supported to allow transfer of oscillography, event record, or other files from a G60 relay.

C.3.3 TIMESTAMPS AND SCANNING

The timestamp values associated with all IEC 61850 data items represent the time of the last change of either the value or
quality flags of the data item. To accomplish this functionality, all IEC 61850 data items must be regularly scanned for data
changes, and the timestamp updated when a change is detected, regardless of the connection status of any IEC 61850 cli-
ents. For applications where there is no IEC 61850 client in use, the IEC 61850 SERVER SCANNING setting can be pro-
grammed as “Disabled”. If a client is in use, this setting should be programmed as “Enabled” to ensure the proper
generation of IEC 61850 timestamps.

C.3.4 LOGICAL DEVICE NAME

The logical device name is used to identify the IEC 61850 logical device that exists within the G60. This name is composed
of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of
the two character strings programmed in the IEDNAME and LD INST settings. The default values for these strings are “IED-
Name” and “LDInst”. These values should be changed to reflect a logical naming convention for all IEC 61850 logical
devices in the system.

C.3.5 LOCATION

The LPHD1 logical node contains a data attribute called location (LPHD1.DC.PhyNam.location). This is a character string
meant to describe the physical location of the G60. This attribute is programmed through the LOCATION setting and its
default value is “Location”. This value should be changed to describe the actual physical location of the G60.

GE Multilin G60 Generator Protection System C-5


C.3 SERVER FEATURES AND CONFIGURATION APPENDIX C

C.3.6 LOGICAL NODE NAME PREFIXES

IEC 61850 specifies that each logical node can have a name with a total length of 11 characters. The name is composed of:
• A five or six-character name prefix.
• A four-character standard name (for example, MMXU, GGIO, PIOC, etc.).
• A one or two-character instantiation index.
Complete names are of the form xxxxxxPIOC1, where the xxxxxx character string is configurable. Details regarding the
logical node naming rules are given in IEC 61850 parts 6 and 7-2. It is recommended that a consistent naming convention
be used for an entire substation project.

C.3.7 CONNECTION TIMING

C A built-in TCP/IP connection timeout of two minutes is employed by the G60 to detect ‘dead’ connections. If there is no data
traffic on a TCP connection for greater than two minutes, the connection will be aborted by the G60. This frees up the con-
nection to be used by other clients. Therefore, when using IEC 61850 reporting, clients should configure report control
block items such that an integrity report will be issued at least every 2 minutes (120000 ms). This ensures that the G60 will
not abort the connection. If other MMS data is being polled on the same connection at least once every 2 minutes, this tim-
eout will not apply.

C.3.8 NON-IEC 61850 DATA

The G60 relay makes available a number of non-IEC 61850 data items. These data items can be accessed through the
“UR” MMS domain. IEC 61850 data can be accessed through the standard IEC 61850 logical device. To access the non-
IEC data items, the INCLUDE NON-IEC DATA setting must be “Enabled”.

C.3.9 COMMUNICATION SOFTWARE UTILITIES

The exact structure and values of the supported IEC 61850 logical nodes can be seen by connecting to a G60 relay with an
MMS browser, such as the “MMS Object Explorer and AXS4-MMS” DDE/OPC server from Sisco Inc.

C-6 G60 Generator Protection System GE Multilin


APPENDIX C C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE

C.4GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE C.4.1 OVERVIEW

IEC 61850 specifies two types of peer-to-peer data transfer services: Generic Substation State Events (GSSE) and Generic
Object Oriented Substation Events (GOOSE). GSSE services are compatible with UCA 2.0 GOOSE. IEC 61850 GOOSE
services provide virtual LAN (VLAN) support, Ethernet priority tagging, and Ethertype Application ID configuration. The sup-
port for VLANs and priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be given
a higher priority than standard Ethernet traffic, and they can be separated onto specific VLANs. Because of the additional
features of GOOSE services versus GSSE services, it is recommended that GOOSE be used wherever backwards com-
patibility with GSSE (or UCA 2.0 GOOSE) is not required.
Devices that transmit GSSE and/or GOOSE messages also function as servers. Each GSSE publisher contains a “GSSE
control block” to configure and control the transmission. Each GOOSE publisher contains a “GOOSE control block” to con-
figure and control the transmission. The transmission is also controlled via device settings. These settings can be seen in
the ICD and/or SCD files, or in the device configuration software or files.
IEC 61850 recommends a default priority value of 4 for GOOSE. Ethernet traffic that does not contain a priority tag has a
C
default priority of 1. More details are specified in IEC 61850 part 8-1.
IEC 61850 recommends that the Ethertype Application ID number be configured according to the GOOSE source. In the
G60, the transmitted GOOSE Application ID number must match the configured receive Application ID number in the
receiver. A common number may be used for all GOOSE transmitters in a system. More details are specified in IEC 61850
part 8-1.

C.4.2 GSSE CONFIGURATION

IEC 61850 Generic Substation Status Event (GSSE) communication is compatible with UCA GOOSE communication.
GSSE messages contain a number of double point status data items. These items are transmitted in two pre-defined data
structures named DNA and UserSt. Each DNA and UserSt item is referred to as a ‘bit pair’. GSSE messages are transmit-
ted in response to state changes in any of the data points contained in the message. GSSE messages always contain the
same number of DNA and UserSt bit pairs. Depending the on the configuration, only some of these bit pairs may have val-
ues that are of interest to receiving devices.
The GSSE FUNCTION, GSSE ID, and GSSE DESTINATION MAC ADDRESS settings are used to configure GSSE transmission.
GSSE FUNCTION is set to “Enabled” to enable the transmission. If a valid multicast Ethernet MAC address is entered for the
GSSE DESTINATION MAC ADDRESS setting, this address will be used as the destination MAC address for GSSE messages. If
a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the G60 will use the source Ether-
net MAC address as the destination, with the multicast bit set.

C.4.3 FIXED GOOSE

The G60 supports two types of IEC 61850 Generic Object Oriented Substation Event (GOOSE) communication: fixed
GOOSE and configurable GOOSE. All GOOSE messages contain IEC 61850 data collected into a dataset. It is this dataset
that is transferred using GOOSE message services. The dataset transferred using the G60 fixed GOOSE is the same data
that is transferred using the GSSE feature; that is, the DNA and UserSt bit pairs. The FlexLogic™ operands that determine
the state of the DNA and UserSt bit pairs are configurable via settings, but the fixed GOOSE dataset always contains the
same DNA/UserSt data structure. Upgrading from GSSE to GOOSE services is simply a matter of enabling fixed GOOSE
and disabling GSSE. The remote inputs and outputs are configured in the same manner for both GSSE and fixed GOOSE.
It is recommended that the fixed GOOSE be used for implementations that require GOOSE data transfer between UR-
series IEDs. Configurable GOOSE may be used for implementations that require GOOSE data transfer between UR-series
IEDs and devices from other manufacturers.

C.4.4 CONFIGURABLE GOOSE

The configurable GOOSE feature allows for the configuration of the datasets to be transmitted or received from the G60.
The G60 supports the configuration of eight (8) transmission and reception datasets, allowing for the optimization of data
transfer between devices.

GE Multilin G60 Generator Protection System C-7


C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE APPENDIX C

Items programmed for dataset 1 and 2 will have changes in their status transmitted as soon as the change is detected.
Dataset 1 should be used for high-speed transmission of data that is required for applications such as transfer tripping,
blocking, and breaker fail initiate. At least one digital status value needs to be configured in dataset 1 to enable transmis-
sion of all data configured for dataset 1. Configuring analog data only to dataset 1 will not activate transmission.
Items programmed for datasets 3 through 8 will have changes in their status transmitted at a maximum rate of every
100 ms. Datasets 3 through 8 will regularly analyze each data item configured within them every 100 ms to identify if any
changes have been made. If any changes in the data items are detected, these changes will be transmitted through a
GOOSE message. If there are no changes detected during this 100 ms period, no GOOSE message will be sent.
For all datasets 1 through 8, the integrity GOOSE message will still continue to be sent at the pre-configured rate even if no
changes in the data items are detected.
The GOOSE functionality was enhanced to prevent the relay from flooding a communications network with GOOSE mes-
sages due to an oscillation being created that is triggering a message.
C The G60 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be
caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station
components. If erroneously oscillation is detected, the G60 will stop sending GOOSE messages from the dataset for a min-
imum period of one second. Should the oscillation persist after the one second time-out period, the G60 will continue to
block transmission of the dataset. The G60 will assert the MAINTENANCE ALERT: GGIO Ind XXX oscill self-test error mes-
sage on the front panel display, where XXX denotes the data item detected as oscillating.
The configurable GOOSE feature is recommended for applications that require GOOSE data transfer between UR-series
IEDs and devices from other manufacturers. Fixed GOOSE is recommended for applications that require GOOSE data
transfer between UR-series IEDs.
IEC 61850 GOOSE messaging contains a number of configurable parameters, all of which must be correct to achieve the
successful transfer of data. It is critical that the configured datasets at the transmission and reception devices are an exact
match in terms of data structure, and that the GOOSE addresses and name strings match exactly. Manual configuration is
possible, but third-party substation configuration software may be used to automate the process. The EnerVista UR Setup-
software can produce IEC 61850 ICD files and import IEC 61850 SCD files produced by a substation configurator (refer to
the IEC 61850 IED configuration section later in this appendix).
The following example illustrates the configuration required to transfer IEC 61850 data items between two devices. The
general steps required for transmission configuration are:
1. Configure the transmission dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
The general steps required for reception configuration are:
1. Configure the reception dataset.
2. Configure the GOOSE service settings.
3. Configure the data.
This example shows how to configure the transmission and reception of three IEC 61850 data items: a single point status
value, its associated quality flags, and a floating point analog value.
The following procedure illustrates the transmission configuration.
1. Configure the transmission dataset by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION ÖØ
IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLE
GOOSE 1 ÖØ CONFIG GSE 1 DATASET ITEMS settings menu:

– Set ITEM 1 to “GGIO1.ST.Ind1.q” to indicate quality flags for GGIO1 status indication 1.
– Set ITEM 2 to “GGIO1.ST.Ind1.stVal” to indicate the status value for GGIO1 status indication 1.
The transmission dataset now contains a set of quality flags and a single point status Boolean value. The reception
dataset on the receiving device must exactly match this structure.
2. Configure the GOOSE service settings by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION
ÖØ IEC 61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION Ö TRANSMISSION ÖØ CONFIGURABLE GOOSE Ö CONFIGU-
RABLE GOOSE 1 settings menu:

C-8 G60 Generator Protection System GE Multilin


APPENDIX C C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE

– Set CONFIG GSE 1 FUNCTION to “Enabled”.


– Set CONFIG GSE 1 ID to an appropriate descriptive string (the default value is “GOOSEOut_1”).
– Set CONFIG GSE 1 DST MAC to a multicast address (for example, 01 00 00 12 34 56).
– Set the CONFIG GSE 1 VLAN PRIORITY; the default value of “4” is OK for this example.
– Set the CONFIG GSE 1 VLAN ID value; the default value is “0”, but some switches may require this value to be “1”.
– Set the CONFIG GSE 1 ETYPE APPID value. This setting represents the Ethertype application ID and must match the
configuration on the receiver (the default value is “0”).
– Set the CONFIG GSE 1 CONFREV value. This value changes automatically as described in IEC 61850 part 7-2. For
this example it can be left at its default value.
3. Configure the data by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION ÖØ IEC 61850 PROTO-
COL Ö GGIO1 STATUS CONFIGURATION settings menu:
– Set GGIO1 INDICATION 1 to a FlexLogic™ operand used to provide the status of GGIO1.ST.Ind1.stVal (for example,
C
a contact input, virtual input, a protection element status, etc.).
The G60 must be rebooted (control power removed and re-applied) before these settings take effect.
The following procedure illustrates the reception configuration.
1. Configure the reception dataset by making the following changes in the PRODUCT SETUP ÖØ COMMUNICATION ÖØ IEC
61850 PROTOCOL Ö GSSE/GOOSE CONFIGURATION ÖØ RECEPTION ÖØ CONFIGURABLE GOOSE Ö CONFIGURABLE GOOSE
1 ÖØ CONFIG GSE 1 DATASET ITEMS settings menu:

– Set ITEM 1 to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.
– Set ITEM 2 to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.
The reception dataset now contains a set of quality flags, a single point status Boolean value, and a floating point ana-
log value. This matches the transmission dataset configuration above.
2. Configure the GOOSE service settings by making the following changes in the INPUTS/OUTPUTS ÖØ REMOTE DEVICES
ÖØ REMOTE DEVICE 1 settings menu:
– Set REMOTE DEVICE 1 ID to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.
– Set REMOTE DEVICE 1 ETYPE APPID to match the Ethertype application ID from the transmitting device. This is “0” in
the example above.
– Set the REMOTE DEVICE 1 DATASET value. This value represents the dataset number in use. Since we are using
configurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.
3. Configure the data by making the following changes in the INPUTS/OUTPUTS ÖØ REMOTE INPUTS ÖØ REMOTE INPUT 1
settings menu:
– Set REMOTE IN 1 DEVICE to “GOOSEOut_1”.
– Set REMOTE IN 1 ITEM to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point status
item to remote input 1.
Remote input 1 can now be used in FlexLogic™ equations or other settings. The G60 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.

C.4.5 ETHERNET MAC ADDRESS FOR GSSE/GOOSE

Ethernet capable devices each contain a unique identifying address called a Media Access Control (MAC) address. This
address cannot be changed and is unique for each Ethernet device produced worldwide. The address is six bytes in length
and is usually represented as six hexadecimal values (for example, 00 A0 F4 01 02 03). It is used in all Ethernet frames as
the ‘source’ address of the frame. Each Ethernet frame also contains a destination address. The destination address can
be different for each Ethernet frame depending on the intended destination of the frame.

GE Multilin G60 Generator Protection System C-9


C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE APPENDIX C

A special type of destination address called a multicast address is used when the Ethernet frame can be received by more
than one device. An Ethernet MAC address is multicast when the least significant bit of the first byte is set (for example, 01
00 00 00 00 00 is a multicast address).
GSSE and GOOSE messages must have multicast destination MAC addresses.
By default, the G60 is configured to use an automated multicast MAC scheme. If the G60 destination MAC address setting
is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina-
tion MAC will be the same as the local MAC address, but with the multicast bit set. Thus, if the local MAC address is 00 A0
F4 01 02 03, then the destination MAC address will be 01 A0 F4 01 02 03.

C.4.6 GSSE ID AND GOOSE ID SETTINGS

GSSE messages contain an identifier string used by receiving devices to identify the sender of the message, defined in IEC
C 61850 part 8-1 as GsID. This is a programmable 65-character string. This string should be chosen to provide a descriptive
name of the originator of the GSSE message.
GOOSE messages contain an identifier string used by receiving devices to identify the sender of the message, defined in
IEC 61850 part 8-1 as GoID. This programmable 65-character string should be a descriptive name of the originator of the
GOOSE message. GOOSE messages also contain two additional character strings used for identification of the message:
DatSet - the name of the associated dataset, and GoCBRef - the reference (name) of the associated GOOSE control block.
These strings are automatically populated and interpreted by the G60; no settings are required.

C-10 G60 Generator Protection System GE Multilin


APPENDIX C C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

C.5IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP C.5.1 OVERVIEW

The G60 can be configured for IEC 61850 via the EnerVista UR Setup software as follows.
1. An ICD file is generated for the G60 by the EnerVista UR Setup software that describe the capabilities of the IED.
2. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven-
dors) for system configuration.
3. The result is saved to a SCD file, which is then imported back to EnerVista UR Setup to create one or more settings
file(s). The settings file(s) can then be used to update the relay(s) with the new configuration information.
The configuration process is illustrated below.

Creating ICD (GE Multilin)

IEC 61850 related Process of Process of Process of


C
configuration for the creating ICD creating ICD creating ICD
IED (UR-series) IED (GSSE/GOOSE, (vendor 2) (vendor 3) (vendor N)
OR server, logical node
prefixes, MMXU
Setting files EnerVista deadbands, GGIO2
(.URS) UR Setup control, etc.)

ICD file 2 ICD file 3 ICD file N


ICD file 1

Import
System
specification data SSD file
System specification tool

System configurator

System Configuration
(network, cross-
communications, IED setting
modification, etc.)

SCD file

Updating IED with new configuration (GE Multilin)

EnerVista UR Setup

Vendor specific tool Vendor specific tool Vendor specific tool


for updating new for updating new for updating new
configuration to IED configuration to IED configuration to IED
URS 1 URS 2 URS X (vendor 2) (vendor 3) (vendor N)

Write settings Write settings file


file to device to other devices

Vendor relay 2 Vendor relay 3 Vendor relay N


UR relay 1 UR relay 2 UR relay X

Ethernet

842790A1.CDR

Figure 0–1: IED CONFIGURATION PROCESS


The following acronyms and abbreviations are used in the procedures describing the IED configuration process for IEC
61850:
• BDA: Basic Data Attribute, that is not structured
• DAI: Instantiated Data Attribute
• DO: Data Object type or instance, depending on the context

GE Multilin G60 Generator Protection System C-11


C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP APPENDIX C

• DOI: Instantiated Data Object


• IED: Intelligent Electronic Device
• LDInst: Instantiated Logical Device
• LNInst: Instantiated Logical Node
• SCL: Substation Configuration Description Language. The configuration language is an application of the Extensible
Markup Language (XML) version 1.0.
• SDI: Instantiated Sub DATA; middle name part of a structured DATA name
• UR: GE Multilin Universal Relay series
• URI: Universal Resource Identifier
• URS: UR-series relay setting file
C • XML: Extensible Markup Language
The following SCL variants are also used:
• ICD: IED Capability Description
• CID: Configured IED Description
• SSD: System Specification Description
• SCD: Substation Configuration Description
The following IEC related tools are referenced in the procedures that describe the IED configuration process for IEC 61850:
• System configurator or Substation configurator: This is an IED independent system level tool that can import or
export configuration files defined by IEC 61850-6. It can import configuration files (ICD) from several IEDs for system
level engineering and is used to add system information shared by different IEDs. The system configuration generates
a substation related configuration file (SCD) which is fed back to the IED configurator (for example, EnerVista UR
Setup) for system related IED configuration. The system configurator should also be able to read a system specifica-
tion file (SSD) to use as base for starting system engineering, or to compare it with an engineered system for the same
substation.
• IED configurator: This is a vendor specific tool that can directly or indirectly generate an ICD file from the IED (for
example, from a settings file). It can also import a system SCL file (SCD) to set communication configuration parame-
ters (that is, required addresses, reception GOOSE datasets, IDs of incoming GOOSE datasets, etc.) for the IED. The
IED configurator functionality is implemented in the GE Multilin EnerVista UR Setup software.

C.5.2 CONFIGURING IEC 61850 SETTINGS

Before creating an ICD file, the user can customize the IEC 61850 related settings for the IED. For example, the IED name
and logical device instance can be specified to uniquely identify the IED within the substation, or transmission GOOSE
datasets created so that the system configurator can configure the cross-communication links to send GOOSE messages
from the IED. Once the IEC 61850 settings are configured, the ICD creation process will recognize the changes and gener-
ate an ICD file that contains the updated settings.
Some of the IED settings will be modified during they system configuration process. For example, a new IP address may be
assigned, line items in a Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be
changed. While all new configurations will be mapped to the G60 settings file when importing an SCD file, all unchanged
settings will preserve the same values in the new settings file.
These settings can be configured either directly through the relay panel or through the EnerVista UR Setup software (pre-
ferred method). The full list of IEC 61850 related settings for are as follows:
• Network configuration: IP address, IP subnet mask, and default gateway IP address (access through the Settings >
Product Setup > Communications > Network menu tree in EnerVista UR Setup).
• Server configuration: IED name and logical device instance (access through the Settings > Product Setup > Com-
munications > IEC 61850 > Server Configuration menu tree in EnerVista UR Setup).
• Logical node prefixes, which includes prefixes for all logical nodes except LLN0 (access through the Settings > Prod-
uct Setup > Communications > IEC 61850 > Logical Node Prefixes menu tree in EnerVista UR Setup).

C-12 G60 Generator Protection System GE Multilin


APPENDIX C C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

• MMXU deadbands, which includes deadbands for all available MMXUs. The number of MMXUs is related to the num-
ber of CT/VT modules in the relay. There are two MMXUs for each CT/VT module. For example, if a relay contains two
CT/VT modules, there will be four MMXUs available (access through the Settings > Product Setup > Communica-
tions > IEC 61850 > MMXU Deadbands menu tree in EnerVista UR Setup).
• GGIO1 status configuration, which includes the number of status points in GGIO1 as well as the potential internal map-
pings for each GGIO1 indication. However only the number of status points will be used in the ICD creation process
(access through the Settings > Product Setup > Communications > IEC 61850 > GGIO1 Status Configuration
menu tree in EnerVista UR Setup).
• GGIO2 control configuration, which includes ctlModels for all SPCSOs within GGIO2 (access through the Settings >
Product Setup > Communications > IEC 61850 > GGIO2 Control Configuration menu tree in EnerVista UR
Setup).
• Configurable transmission GOOSE, which includes eight configurable datasets that can be used for GOOSE transmis-
sion. The GOOSE ID can be specified for each dataset (it must be unique within the IED as well as across the whole
substation), as well as the destination MAC address, VLAN priority, VLAN ID, ETYPE APPID, and the dataset items.
C
The selection of the dataset item is restricted by firmware version; for version 5.9x, only GGIO1.ST.Indx.stVal and
GGIO1.ST.Indx.q are valid selection (where x is between 1 to N, and N is determined by number of GGIO1 status
points). Although configurable transmission GOOSE can also be created and altered by some third-party system con-
figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly
within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com-
munications > IEC 61850 > GSSE/GOOSE Configuration > Transmission > Tx Configurable GOOSE menu tree
in EnerVista UR Setup).
• Configurable reception GOOSE, which includes eight configurable datasets that can be used for GOOSE reception.
However, unlike datasets for transmission, datasets for reception only contains dataset items, and they are usually cre-
ated automatically by process of importing the SCD file (access through the Settings > Product Setup > Communi-
cations > IEC 61850 > GSSE/GOOSE Configuration > Reception > Rx Configurable GOOSE menu tree in
EnerVista UR Setup).
• Remote devices configuration, which includes remote device ID (GOOSE ID or GoID of the incoming transmission
GOOSE dataset), ETYPE APPID (of the GSE communication block for the incoming transmission GOOSE), and
DATASET (which is the name of the associated reception GOOSE dataset). These settings are usually done automat-
ically by process of importing SCD file (access through the Settings > Inputs/Outputs > Remote Devices menu tree
in EnerVista UR Setup).
• Remote inputs configuration, which includes device (remote device ID) and item (which dataset item in the associated
reception GOOSE dataset to map) values. Only the items with cross-communication link created in SCD file should be
mapped. These configurations are usually done automatically by process of importing SCD file (access through the
Settings > Inputs/Outputs > Remote Inputs menu tree in EnerVista UR Setup).

C.5.3 ABOUT ICD FILES

The SCL language is based on XML, and its syntax definition is described as a W3C XML Schema. ICD is one type of SCL
file (which also includes SSD, CID and SCD files). The ICD file describes the capabilities of an IED and consists of four
major sections:
• Header
• Communication
• IEDs
• DataTypeTemplates

GE Multilin G60 Generator Protection System C-13


C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP APPENDIX C

The root file structure of an ICD file is illustrated below.

SCL

Header (id, version, revision, toolID, nameStructure)

Communication

IED (name, type, manufacture, configVersion)

DataTypeTemplates
842795A1.CDR

Figure 0–2: ICD FILE STRUCTURE, SCL (ROOT) NODE


The Header node identifies the ICD file and its version, and specifies options for the mapping of names to signals
C The Communication node describes the direct communication connection possibilities between logical nodes by means of
logical buses (sub-networks) and IED access ports. The communication section is structured as follows.

Communication

SubNetwork (name)

ConnectedAP (iedName, apName)

Address

P (type)

Text

Other P elements

GSE (IdInst, cbName)

Address

P (type)

Text

Other GSE elements Other P elements


842796A1.CDR

Figure 0–3: ICD FILE STRUCTURE, COMMUNICATIONS NODE


The SubNetwork node contains all access points which can (logically) communicate with the sub-network protocol and
without the intervening router. The ConnectedAP node describes the IED access point connected to this sub-network. The
Address node contains the address parameters of the access point. The GSE node provides the address element for stat-
ing the control block related address parameters, where IdInst is the instance identification of the logical device within the
IED on which the control block is located, and cbName is the name of the control block.
The IED node describes the (pre-)configuration of an IED: its access points, the logical devices, and logical nodes instanti-
ated on it. Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with
its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD
since it only describes one IED.

C-14 G60 Generator Protection System GE Multilin


APPENDIX C C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

IED (name, type, manufacture, configVersion)

Services

DynAssoication GetDataSetValue ReadWrite ConfLogControl (max)

GetDirectory SetDataSetValue TimerActivatedControl GSEDir

GetDateObjectDefinition DataSetDirectory ConfReportControl (max) GOOSE (max)

DataObjectDirectory ConfDataSet (max, maxAttributes) GetCBValues GSSE (max)

AccessPoint (name)

Server

Authentication (none) C
LDevice (inst)

LN0 (InType, InClass, inst)

DataSet (name)

FCDA (fc, doName, daName, IdInst, prefix, InClass, InInst)

Other FCDA elements

Other DataSet elements

ReportControl (name, datSet, intgPd, rptID, confRev, buffered)

TrgOps (dchg) OptFields (seqNum) RptEnabled

Other ReportControl elements

DOI (name)

SDI (name) DAI (name)


Val Text

Other DOI elements SDI (name)


DAI (name)
GSEControl (name, datSet, type, confRev, appID) Val Text

Other GSEControl elements

LN (InType, InClass, prefix, inst)

DataSet (name)

FCDA (IdInst, prefix, InClass, InInst, doName, fc)

Other FCDA elements

Other DataSet elements

ReportControl (name, datSet, intgPd, rptID, confRev, buffered)

TrgOps (dchg) OptFields (seqNum) RptEnabled

Other ReportControl elements

DOI (name)

SDI (name) DAI (name)


Val Text

Other DOI elements SDI (name)


DAI (name)
Val Text
Other LN elements

Other LDevice elements


842797A1.CDR

Figure 0–4: ICD FILE STRUCTURE, IED NODE

GE Multilin G60 Generator Protection System C-15


C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP APPENDIX C

The DataTypeTemplates node defines instantiable logical node types. A logical node type is an instantiable template of the
data of a logical node. A LnodeType is referenced each time that this instantiable type is needed with an IED. A logical
node type template is built from DATA (DO) elements, which again have a DO type, which is derived from the DATA classes
(CDC). DOs consist of attributes (DA) or of elements of already defined DO types (SDO). The attribute (DA) has a func-
tional constraint, and can either have a basic type, be an enumeration, or a structure of a DAType. The DAType is built from
BDA elements, defining the structure elements, which again can be BDA elements of have a base type such as DA.

DataTypeTemplates

LNodeType (id, InClass)

DO (name, type)

Other DO elements

C Other LNodeType elements

DOType (id, cdc)

SDO (name, type) DA (name, fc, bType, type) Val Text

Other SDO elements Other DA elements

Other DOType elements

DAType (id)

BDA (name, bType, type)

Other BDA elements

Other DAType elements

EnumType (id)

EnumVal (ord) Text

Other EnumVal elements

Other EnumType elements


842798A1.CDR

Figure 0–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE

C-16 G60 Generator Protection System GE Multilin


APPENDIX C C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

C.5.4 CREATING AN ICD FILE WITH ENERVISTA UR SETUP

An ICD file can be created directly from a connected G60 IED or from an offline G60 settings file with the EnerVista UR
Setup software using the following procedure:
1. Right-click the connected UR-series relay or settings file and select Create ICD File.

2. The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click
OK to generate the file.
The time to create an ICD file from the offline G60 settings file is typically much quicker than create an ICD file directly from
the relay.

C.5.5 ABOUT SCD FILES

System configuration is performed in the system configurator. While many vendors (including GE Multilin) are working their
own system configuration tools, there are some system configurators available in the market (for example, Siemens DIGSI
version 4.6 or above and ASE Visual SCL Beta 0.12).
Although the configuration tools vary from one vendor to another, the procedure is pretty much the same. First, a substation
project must be created, either as an empty template or with some system information by importing a system specification
file (SSD). Then, IEDs are added to the substation. Since each IED is represented by its associated ICD, the ICD files are
imported into the substation project, and the system configurator validates the ICD files during the importing process. If the
ICD files are successfully imported into the substation project, it may be necessary to perform some additional minor steps
to attach the IEDs to the substation (see the system configurator manual for details).
Once all IEDs are inserted into the substation, further configuration is possible, such as:
• Assigning network addresses to individual IEDs.
• Customizing the prefixes of logical nodes.
• Creating cross-communication links (configuring GOOSE messages to send from one IED to others).
When system configurations are complete, the results are saved to an SCD file, which contains not only the configuration
for each IED in the substation, but also the system configuration for the entire substation. Finally, the SCD file is passed
back to the IED configurator (vendor specific tool) to update the new configuration into the IED.
The SCD file consists of at least five major sections:

GE Multilin G60 Generator Protection System C-17


C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP APPENDIX C

• Header.
• Substation.
• Communication.
• IED section (one or more).
• DataTypeTemplates.
The root file structure of an SCD file is illustrated below.

SCL

Header (id, version, revision, toolID, nameStructure)

C Substation

Communication

IED Section (IED 1)

IED Section (IED 2)

Other IED Sections

DataTypeTemplates
842791A1.CDR

Figure 0–6: SCD FILE STRUCTURE, SCL (ROOT) NODE


Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to
signals.
The Substation node describes the substation parameters:

Substation
PowerSystemResource

EquipmentContainer Power Transformer

GeneralEquipment

EquipmentContainer

VoltageLevel Bay

Voltage

PowerSystemResource

Function SubFunction

GeneralEquipment
842792A1.CDR

Figure 0–7: SCD FILE STRUCTURE, SUBSTATION NODE

C-18 G60 Generator Protection System GE Multilin


APPENDIX C C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

The Communication node describes the direct communication connection possibilities between logical nodes by means of
logical buses (sub-networks) and IED access ports. The communication section is structured as follows.

Communication

SubNetwork (name)

ConnectedAP (IED 1)

Address

P (type)

Text

Other P elements

GSE (IdInst, cbName) C


Address

P (type)

Other GSE elements Text

Other P elements

ConnectedAP (IED 2)

Address

P (type)

Text

Other P elements

GSE (IdInst, cbName)

Address

P (type)

Text

Other P elements
Other GSE elements

Other ConnectedAP elements


842793A1.CDR

Figure 0–8: SCD FILE STRUCTURE, COMMUNICATIONS NODE


The SubNetwork node contains all access points which can (logically) communicate with the sub-network protocol and
without the intervening router. The ConnectedAP node describes the IED access point connected to this sub-network. The
Address node contains the address parameters of the access point. The GSE node provides the address element for stat-
ing the control block related address parameters, where IdInst is the instance identification of the logical device within the
IED on which the control block is located, and cbName is the name of the control block.

GE Multilin G60 Generator Protection System C-19


C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP APPENDIX C

The IED Section node describes the configuration of an IED.

IED Section (IED 1)

AccessPoint (name)

Server

Authentication (none)

LDevice (inst)

LN0 (InType, InClass, inst)

DataSet elements

C ReportControl elements

DOI elements

Inputs

ExtRef (iedName, ldInst, prefix, lnClass, lnInst, doName, daName, intAddr)

Other ExtRef elements

GSEControl elements
842794A1.CDR

Figure 0–9: SCD FILE STRUCTURE, IED NODE

C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP

The following procedure describes how to update the G60 with the new configuration from an SCD file with the EnerVista
UR Setup software.
1. Right-click anywhere in the files panel and select the Import Contents From SCD File item.

2. Select the saved SCD file and click Open.

C-20 G60 Generator Protection System GE Multilin


APPENDIX C C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP

3. The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and
name for the URS (UR-series relay settings) file.
If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set-
tings file for each IED.
4. After the URS file is created, modify any settings (if required).
5. To update the relay with the new settings, right-click on the settings file in the settings tree and select the Write Set-
tings File to Device item.
6. The software will prompt for the target device. Select the target device from the list provided and click Send. The new
settings will be updated to the selected device.

GE Multilin G60 Generator Protection System C-21


C.6 ACSI CONFORMANCE APPENDIX C

C.6ACSI CONFORMANCE C.6.1 ACSI BASIC CONFORMANCE STATEMENT

SERVICES SERVER/ UR-FAMILY


PUBLISHER
CLIENT-SERVER ROLES
B11 Server side (of Two-party Application-Association) c1 Yes
B12 Client side (of Two-party Application-Association) ---
SCSMS SUPPORTED
B21 SCSM: IEC 61850-8-1 used Yes
B22 SCSM: IEC 61850-9-1 used
B23 SCSM: IEC 61850-9-2 used

C B24 SCSM: other


GENERIC SUBSTATION EVENT MODEL (GSE)
B31 Publisher side O Yes
B32 Subscriber side --- Yes
TRANSMISSION OF SAMPLED VALUE MODEL (SVC)
B41 Publisher side O
B42 Subscriber side ---

c1: shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
NOTE M: Mandatory

C.6.2 ACSI MODELS CONFORMANCE STATEMENT

SERVICES SERVER/ UR-FAMILY


PUBLISHER
IF SERVER SIDE (B11) SUPPORTED
M1 Logical device c2 Yes
M2 Logical node c3 Yes
M3 Data c4 Yes
M4 Data set c5 Yes
M5 Substitution O
M6 Setting group control O
REPORTING
M7 Buffered report control O Yes
M7-1 sequence-number
M7-2 report-time-stamp
M7-3 reason-for-inclusion
M7-4 data-set-name
M7-5 data-reference
M7-6 buffer-overflow
M7-7 entryID
M7-8 BufTm
M7-9 IntgPd
M7-10 GI
M8 Unbuffered report control O Yes
M8-1 sequence-number
M8-2 report-time-stamp
M8-3 reason-for-inclusion

C-22 G60 Generator Protection System GE Multilin


APPENDIX C C.6 ACSI CONFORMANCE

SERVICES SERVER/ UR-FAMILY


PUBLISHER
M8-4 data-set-name
M8-5 data-reference
M8-6 BufTm
M8-7 IntgPd
M8-8 GI
Logging O
M9 Log control O
M9-1 IntgPd
M10 Log O
M11 Control M Yes
IF GSE (B31/32) IS SUPPORTED C
GOOSE O Yes
M12-1 entryID
M12-2 DataReflnc
M13 GSSE O Yes
IF SVC (B41/B42) IS SUPPORTED
M14 Multicast SVC O
M15 Unicast SVC O
M16 Time M Yes
M17 File transfer O Yes

c2: shall be "M" if support for LOGICAL-NODE model has been declared
c3: shall be "M" if support for DATA model has been declared
NOTE c4: shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has been declared
c5: shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory

C.6.3 ACSI SERVICES CONFORMANCE STATEMENT

In the table below, the acronym AA refers to Application Associations (TP: Two Party / MC: Multicast). The c6 to c10 entries
are defined in the notes following the table.

SERVICES AA: TP/MC SERVER/ UR FAMILY


PUBLISHER
SERVER (CLAUSE 6)
S1 ServerDirectory TP M Yes
APPLICATION ASSOCIATION (CLAUSE 7)
S2 Associate M Yes
S3 Abort M Yes
S4 Release M Yes
LOGICAL DEVICE (CLAUSE 8)
S5 LogicalDeviceDirectory TP M Yes
LOGICAL NODE (CLAUSE 9)
S6 LogicalNodeDirectory TP M Yes
S7 GetAllDataValues TP M Yes
DATA (CLAUSE 10)
S8 GetDataValues TP M Yes
S9 SetDataValues TP O Yes
S10 GetDataDirectory TP M Yes
S11 GetDataDefinition TP M Yes

GE Multilin G60 Generator Protection System C-23


C.6 ACSI CONFORMANCE APPENDIX C

SERVICES AA: TP/MC SERVER/ UR FAMILY


PUBLISHER
DATA SET (CLAUSE 11)
S12 GetDataSetValues TP M Yes
S13 SetDataSetValues TP O
S14 CreateDataSet TP O
S15 DeleteDataSet TP O
S16 GetDataSetDirectory TP O Yes
SUBSTITUTION (CLAUSE 12)
S17 SetDataValues TP M
SETTING GROUP CONTROL (CLAUSE 13)
S18 SelectActiveSG TP O
C S19 SelectEditSG TP O
S20 SetSGValues TP O
S21 ConfirmEditSGValues TP O
S22 GetSGValues TP O
S23 GetSGCBValues TP O
REPORTING (CLAUSE 14)
BUFFERED REPORT CONTROL BLOCK (BRCB)
S24 Report TP c6 Yes
S24-1 data-change (dchg) Yes
S24-2 qchg-change (qchg)
S24-3 data-update (dupd)
S25 GetBRCBValues TP c6 Yes
S26 SetBRCBValues TP c6 Yes
UNBUFFERED REPORT CONTROL BLOCK (URCB)
S27 Report TP c6 Yes
S27-1 data-change (dchg) Yes
S27-2 qchg-change (qchg)
S27-3 data-update (dupd)
S28 GetURCBValues TP c6 Yes
S29 SetURCBValues TP c6 Yes
LOGGING (CLAUSE 14)
LOG CONTROL BLOCK
S30 GetLCBValues TP M
S31 SetLCBValues TP M
LOG
S32 QueryLogByTime TP M
S33 QueryLogByEntry TP M
S34 GetLogStatusValues TP M
GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 14.3.5.3.4)
GOOSE-CONTROL-BLOCK
S35 SendGOOSEMessage MC c8 Yes
S36 GetReference TP c9
S37 GetGOOSEElementNumber TP c9
S38 GetGoCBValues TP O Yes
S39 SetGoCBValues TP O Yes
GSSE-CONTROL-BLOCK
S40 SendGSSEMessage MC c8 Yes
S41 GetReference TP c9

C-24 G60 Generator Protection System GE Multilin


APPENDIX C C.6 ACSI CONFORMANCE

SERVICES AA: TP/MC SERVER/ UR FAMILY


PUBLISHER
S42 GetGSSEElementNumber TP c9
S43 GetGsCBValues TP O Yes
S44 SetGsCBValues TP O Yes
TRANSMISSION OF SAMPLE VALUE MODEL (SVC) (CLAUSE 16)
MULTICAST SVC
S45 SendMSVMessage MC c10
S46 GetMSVCBValues TP O
S47 SetMSVCBValues TP O
UNICAST SVC
S48 SendUSVMessage MC c10
S49 GetUSVCBValues TP O C
S50 SetUSVCBValues TP O
CONTROL (CLAUSE 16.4.8)
S51 Select O Yes
S52 SelectWithValue TP O
S53 Cancel TP O Yes
S54 Operate TP M Yes
S55 Command-Termination TP O
S56 TimeActivated-Operate TP O
FILE TRANSFER (CLAUSE 20)
S57 GetFile TP M Yes
S58 SetFile TP O
S59 DeleteFile TP O
S60 GetFileAttributeValues TP M Yes
TIME (CLAUSE 5.5)
T1 Time resolution of internal clock 20
(nearest negative power of 2 in
seconds)
T2 Time accuracy of internal clock
T3 supported TimeStamp resolution 20
(nearest value of 2–n in seconds,
accoridng to 5.5.3.7.3.3)

c6: shall declare support for at least one (BRCB or URCB)


c7: shall declare support for at least one (QueryLogByTime or QueryLogAfter)
NOTE c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage)
c9: shall declare support if TP association is available
c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage)

GE Multilin G60 Generator Protection System C-25


C.7 LOGICAL NODES APPENDIX C

C.7LOGICAL NODES C.7.1 LOGICAL NODES TABLE

The UR-series of relays supports IEC 61850 logical nodes as indicated in the following table. Note that the actual instantia-
tion of each logical node is determined by the product order code. For example. the logical node “PDIS” (distance protec-
tion) is available only in the D60 Line Distance Relay.

Table C–1: IEC 61850 LOGICAL NODES (Sheet 1 of 3)


NODES UR-FAMILY
L: SYSTEM LOGICAL NODES
LPHD: Physical device information Yes
LLN0: Logical node zero Yes
P: LOGICAL NODES FOR PROTECTION FUNCTIONS
C PDIF: Differential Yes
PDIR: Direction comparison ---
PDIS: Distance Yes
PDOP: Directional overpower ---
PDUP: Directional underpower ---
PFRC: Rate of change of frequency ---
PHAR: Harmonic restraint ---
PHIZ: Ground detector ---
PIOC: Instantaneous overcurrent Yes
PMRI Motor restart inhibition ---
PMSS: Motor starting time supervision ---
POPF: Over power factor ---
PPAM: Phase angle measuring ---
PSCH: Protection scheme ---
PSDE: Sensitive directional earth fault ---
PTEF: Transient earth fault ---
PTOC: Time overcurrent Yes
PTOF: Overfrequency ---
PTOV: Overvoltage Yes
PTRC: Protection trip conditioning Yes
PTTR: Thermal overload Yes
PTUC: Undercurrent ---
PTUV: Undervoltage Yes
PUPF: Underpower factor ---
PTUF: Underfrequency ---
PVOC: Voltage controlled time overcurrent ---
PVPH: Volts per Hz ---
PZSU: Zero speed or underspeed ---
R: LOGICAL NODES FOR PROTECTION RELATED FUNCTIONS
RDRE: Disturbance recorder function ---
RADR: Disturbance recorder channel analogue ---
RBDR: Disturbance recorder channel binary ---
RDRS: Disturbance record handling ---
RBRF: Breaker failure Yes
RDIR: Directional element ---
RFLO: Fault locator Yes
RPSB: Power swing detection/blocking Yes
RREC: Autoreclosing Yes

C-26 G60 Generator Protection System GE Multilin


APPENDIX C C.7 LOGICAL NODES

Table C–1: IEC 61850 LOGICAL NODES (Sheet 2 of 3)


NODES UR-FAMILY
RSYN: Synchronism-check or synchronizing ---
C: LOGICAL NODES FOR CONTROL
CALH: Alarm handling ---
CCGR: Cooling group control ---
CILO: Interlocking ---
CPOW: Point-on-wave switching ---
CSWI: Switch controller Yes
G: LOGICAL NODES FOR GENERIC REFERENCES
GAPC: Generic automatic process control ---
GGIO: Generic process I/O
GSAL: Generic security application
Yes
---
C
I: LOGICAL NODES FOR INTERFACING AND ARCHIVING
IARC: Archiving ---
IHMI: Human machine interface ---
ITCI: Telecontrol interface ---
ITMI: Telemonitoring interface ---
A: LOGICAL NODES FOR AUTOMATIC CONTROL
ANCR: Neutral current regulator ---
ARCO: Reactive power control ---
ATCC: Automatic tap changer controller ---
AVCO: Voltage control ---
M: LOGICAL NODES FOR METERING AND MEASUREMENT
MDIF: Differential measurements ---
MHAI: Harmonics or interharmonics ---
MHAN: Non phase related harmonics or interharmonic ---
MMTR: Metering ---
MMXN: Non phase related measurement Yes
MMXU: Measurement Yes
MSQI: Sequence and imbalance ---
MSTA: Metering statistics ---
S: LOGICAL NODES FOR SENSORS AND MONITORING
SARC: Monitoring and diagnostics for arcs ---
SIMG: Insulation medium supervision (gas) ---
SIML: Insulation medium supervision (liquid) ---
SPDC: Monitoring and diagnostics for partial discharges ---
X: LOGICAL NODES FOR SWITCHGEAR
XCBR: Circuit breaker Yes
XSWI: Circuit switch Yes
T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS
TCTR: Current transformer ---
TVTR: Voltage transformer ---
Y: LOGICAL NODES FOR POWER TRANSFORMERS
YEFN: Earth fault neutralizer (Peterson coil) ---
YLTC: Tap changer ---
YPSH: Power shunt ---
YPTR: Power transformer ---

GE Multilin G60 Generator Protection System C-27


C.7 LOGICAL NODES APPENDIX C

Table C–1: IEC 61850 LOGICAL NODES (Sheet 3 of 3)


NODES UR-FAMILY
Z: LOGICAL NODES FOR FURTHER POWER SYSTEM EQUIPMENT
ZAXN: Auxiliary network ---
ZBAT: Battery ---
ZBSH: Bushing ---
ZCAB: Power cable ---
ZCAP: Capacitor bank ---
ZCON: Converter ---
ZGEN: Generator ---
ZGIL: Gas insulated line ---

C ZLIN: Power overhead line


ZMOT: Motor
---
---
ZREA: Reactor ---
ZRRC: Rotating reactive component ---
ZSAR: Surge arrestor ---
ZTCF: Thyristor controlled frequency converter ---
ZTRC: Thyristor controlled reactive component ---

C-28 G60 Generator Protection System GE Multilin


APPENDIX D D.1 IEC 60870-5-104

APPENDIX D IEC 60870-5-104 COMMUNICATIONSD.1IEC 60870-5-104 D.1.1 INTEROPERABILITY DOCUMENT

This document is adapted from the IEC 60870-5-104 standard. For ths section the boxes indicate the following: 4 – used in
standard direction; … – not used; „ – cannot be selected in IEC 60870-5-104 standard.
1. SYSTEM OR DEVICE:
… System Definition
… Controlling Station Definition (Master)
4 Controlled Station Definition (Slave)
2. NETWORK CONFIGURATION:
„ Point-to-Point „ Multipoint
„ Multiple Point-to-Point „ Multipoint Star
3. PHYSICAL LAYER
Transmission Speed (control direction):
Unbalanced Interchange Unbalanced Interchange Balanced Interchange Circuit
Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:
if >1200 bits/s: D
„ 100 bits/sec. „ 2400 bits/sec. „ 2400 bits/sec.
„ 200 bits/sec. „ 4800 bits/sec. „ 4800 bits/sec.
„ 300 bits/sec. „ 9600 bits/sec. „ 9600 bits/sec.
„ 600 bits/sec. „ 19200 bits/sec.
„ 1200 bits/sec. „ 38400 bits/sec.
„ 56000 bits/sec.
„ 64000 bits/sec.
Transmission Speed (monitor direction):
Unbalanced Interchange Unbalanced Interchange Balanced Interchange Circuit
Circuit V.24/V.28 Standard: Circuit V.24/V.28 Recommended X.24/X.27:
if >1200 bits/s:
„ 100 bits/sec. „ 2400 bits/sec. „ 2400 bits/sec.
„ 200 bits/sec. „ 4800 bits/sec. „ 4800 bits/sec.
„ 300 bits/sec. „ 9600 bits/sec. „ 9600 bits/sec.
„ 600 bits/sec. „ 19200 bits/sec.
„ 1200 bits/sec. „ 38400 bits/sec.
„ 56000 bits/sec.
„ 64000 bits/sec.

4. LINK LAYER
Link Transmission Procedure: Address Field of the Link:
„ Balanced Transmision „ Not Present (Balanced Transmission Only)
„ Unbalanced Transmission „ One Octet
„ Two Octets
„ Structured
„ Unstructured
Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard

GE Multilin G60 Generator Protection System D-1


D.1 IEC 60870-5-104 APPENDIX D

When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low priority) with the
indicated causes of transmission:
„ The standard assignment of ADSUs to class 2 messages is used as follows:

„ A special assignment of ADSUs to class 2 messages is used as follows:

5. APPLICATION LAYER
Transmission Mode for Application Data:
Mode 1 (least significant octet first), as defined in Clause 4.10 of IEC 60870-5-4, is used exclusively in this companion
stanadard.
Common Address of ADSU:
„ One Octet
4 Two Octets
Information Object Address:
„ One Octet 4 Structured

D „ Two Octets 4 Unstructured


4 Three Octets
Cause of Transmission:
„ One Octet
4 Two Octets (with originator address). Originator address is set to zero if not used.
Maximum Length of APDU: 253 (the maximum length may be reduced by the system.
Selection of standard ASDUs:
For the following lists, the boxes indicate the following: 4 – used in standard direction; … – not used; „ – cannot be
selected in IEC 60870-5-104 standard.
Process information in monitor direction
4 <1> := Single-point information M_SP_NA_1
„ <2> := Single-point information with time tag M_SP_TA_1
… <3> := Double-point information M_DP_NA_1
„ <4> := Double-point information with time tag M_DP_TA_1
… <5> := Step position information M_ST_NA_1
„ <6> := Step position information with time tag M_ST_TA_1
… <7> := Bitstring of 32 bits M_BO_NA_1
„ <8> := Bitstring of 32 bits with time tag M_BO_TA_1
… <9> := Measured value, normalized value M_ME_NA_1
„ <10> := Measured value, normalized value with time tag M_NE_TA_1
… <11> := Measured value, scaled value M_ME_NB_1
„ <12> := Measured value, scaled value with time tag M_NE_TB_1
4 <13> := Measured value, short floating point value M_ME_NC_1
„ <14> := Measured value, short floating point value with time tag M_NE_TC_1
4 <15> := Integrated totals M_IT_NA_1
„ <16> := Integrated totals with time tag M_IT_TA_1
„ <17> := Event of protection equipment with time tag M_EP_TA_1
„ <18> := Packed start events of protection equipment with time tag M_EP_TB_1
„ <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1
… <20> := Packed single-point information with status change detection M_SP_NA_1

D-2 G60 Generator Protection System GE Multilin


APPENDIX D D.1 IEC 60870-5-104

… <21> := Measured value, normalized value without quantity descriptor M_ME_ND_1

4 <30> := Single-point information with time tag CP56Time2a M_SP_TB_1


… <31> := Double-point information wiht time tag CP56Time2a M_DP_TB_1
… <32> := Step position information with time tag CP56Time2a M_ST_TB_1
… <33> := Bitstring of 32 bits with time tag CP56Time2a M_BO_TB_1
… <34> := Measured value, normalized value with time tag CP56Time2a M_ME_TD_1
… <35> := Measured value, scaled value with time tag CP56Time2a M_ME_TE_1
… <36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1
4 <37> := Integrated totals with time tag CP56Time2a M_IT_TB_1
… <38> := Event of protection equipment with time tag CP56Time2a M_EP_TD_1
… <39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1
… <40> := Packed output circuit information of protection equipment with time tag CP56Time2a M_EP_TF_1

Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the set
<30> to <40> are used.
Process information in control direction
4 <45> := Single command C_SC_NA_1
D
… <46> := Double command C_DC_NA_1
… <47> := Regulating step command C_RC_NA_1
… <48> := Set point command, normalized value C_SE_NA_1
… <49> := Set point command, scaled value C_SE_NB_1
… <50> := Set point command, short floating point value C_SE_NC_1
… <51> := Bitstring of 32 bits C_BO_NA_1

4 <58> := Single command with time tag CP56Time2a C_SC_TA_1


… <59> := Double command with time tag CP56Time2a C_DC_TA_1
… <60> := Regulating step command with time tag CP56Time2a C_RC_TA_1
… <61> := Set point command, normalized value with time tag CP56Time2a C_SE_TA_1
… <62> := Set point command, scaled value with time tag CP56Time2a C_SE_TB_1
… <63> := Set point command, short floating point value with time tag CP56Time2a C_SE_TC_1
… <64> := Bitstring of 32 bits with time tag CP56Time2a C_BO_TA_1

Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
System information in monitor direction
4 <70> := End of initialization M_EI_NA_1

System information in control direction


4 <100> := Interrogation command C_IC_NA_1
4 <101> := Counter interrogation command C_CI_NA_1
4 <102> := Read command C_RD_NA_1
4 <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1
„ <104> := Test command C_TS_NA_1
4 <105> := Reset process command C_RP_NA_1
„ <106> := Delay acquisition command C_CD_NA_1
4 <107> := Test command with time tag CP56Time2a C_TS_TA_1

GE Multilin G60 Generator Protection System D-3


D.1 IEC 60870-5-104 APPENDIX D

Parameter in control direction


… <110> := Parameter of measured value, normalized value PE_ME_NA_1
… <111> := Parameter of measured value, scaled value PE_ME_NB_1
4 <112> := Parameter of measured value, short floating point value PE_ME_NC_1
… <113> := Parameter activation PE_AC_NA_1

File transfer
… <120> := File Ready F_FR_NA_1
… <121> := Section Ready F_SR_NA_1
… <122> := Call directory, select file, call file, call section F_SC_NA_1
… <123> := Last section, last segment F_LS_NA_1
… <124> := Ack file, ack section F_AF_NA_1
… <125> := Segment F_SG_NA_1
… <126> := Directory (blank or X, available only in monitor [standard] direction) C_CD_NA_1

Type identifier and cause of transmission assignments


D (station-specific parameters)
In the following table:
•Shaded boxes are not required.
•Black boxes are not permitted in this companion standard.
•Blank boxes indicate functions or ASDU not used.
•‘X’ if only used in the standard direction
TYPE IDENTIFICATION CAUSE OF TRANSMISSION

REQUEST BY GROUP <N> COUNTER REQ

UNKNOWN INFORMATION OBJECT ADDR

UNKNOWN INFORMATION OBJECT ADDR


UNKNOWN COMMON ADDRESS OF ADSU
INTERROGATED BY GROUP <NUMBER>
RETURN INFO CAUSED BY LOCAL CMD

UNKNOWN CAUSE OF TRANSMISSION


UNKNOWN TYPE IDENTIFICATION
DEACTIVATION CONFIRMATION
ACTIVATION CONFIRMATION

ACTIVATION TERMINATION
REQUEST OR REQUESTED
BACKGROUND SCAN
PERIODIC, CYCLIC

FILE TRANSFER
SPONTANEOUS

DEACTIVATION
ACTIVATION
INITIALIZED

20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
<1> M_SP_NA_1 X X X X X
<2> M_SP_TA_1
<3> M_DP_NA_1
<4> M_DP_TA_1
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1

D-4 G60 Generator Protection System GE Multilin


APPENDIX D D.1 IEC 60870-5-104

TYPE IDENTIFICATION CAUSE OF TRANSMISSION

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR

UNKNOWN INFORMATION OBJECT ADDR


REQUEST BY GROUP <N> COUNTER REQ
INTERROGATED BY GROUP <NUMBER>
RETURN INFO CAUSED BY LOCAL CMD

UNKNOWN CAUSE OF TRANSMISSION


UNKNOWN TYPE IDENTIFICATION
DEACTIVATION CONFIRMATION
ACTIVATION CONFIRMATION

ACTIVATION TERMINATION
REQUEST OR REQUESTED
BACKGROUND SCAN
PERIODIC, CYCLIC

FILE TRANSFER
SPONTANEOUS

DEACTIVATION
ACTIVATION
INITIALIZED
20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41
<10> M_ME_TA_1 D
<11> M_ME_NB_1
<12> M_ME_TB_1
<13> M_ME_NC_1 X X X X
<14> M_ME_TC_1
<15> M_IT_NA_1 X X
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 X X X
<31> M_DP_TB_1
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1
<35> M_ME_TE_1
<36> M_ME_TF_1
<37> M_IT_TB_1 X X
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X
<46> C_DC_NA_1
<47> C_RC_NA_1
<48> C_SE_NA_1
<49> C_SE_NB_1
<50> C_SE_NC_1
<51> C_BO_NA_1
<58> C_SC_TA_1 X X X X X
<59> C_DC_TA_1
<60> C_RC_TA_1

GE Multilin G60 Generator Protection System D-5


D.1 IEC 60870-5-104 APPENDIX D

TYPE IDENTIFICATION CAUSE OF TRANSMISSION

UNKNOWN COMMON ADDRESS OF ADSU

UNKNOWN INFORMATION OBJECT ADDR

UNKNOWN INFORMATION OBJECT ADDR


REQUEST BY GROUP <N> COUNTER REQ
INTERROGATED BY GROUP <NUMBER>
RETURN INFO CAUSED BY LOCAL CMD

UNKNOWN CAUSE OF TRANSMISSION


UNKNOWN TYPE IDENTIFICATION
DEACTIVATION CONFIRMATION
ACTIVATION CONFIRMATION

ACTIVATION TERMINATION
REQUEST OR REQUESTED
BACKGROUND SCAN
PERIODIC, CYCLIC

FILE TRANSFER
SPONTANEOUS

DEACTIVATION
ACTIVATION
INITIALIZED
20 37
NO. MNEMONIC 1 2 3 4 5 6 7 8 9 10 11 12 13 to to 44 45 46 47
36 41

D <61>
<62>
C_SE_TA_1
C_SE_TB_1
<63> C_SE_TC_1
<64> C_BO_TA_1
<70> M_EI_NA_1*) X
<100> C_IC_NA_1 X X X X X
<101> C_CI_NA_1 X X X
<102> C_RD_NA_1 X
<103> C_CS_NA_1 X X X
<104> C_TS_NA_1
<105> C_RP_NA_1 X X
<106> C_CD_NA_1
<107> C_TS_TA_1
<110> P_ME_NA_1
<111> P_ME_NB_1
<112> P_ME_NC_1 X X X
<113> P_AC_NA_1
<120> F_FR_NA_1
<121> F_SR_NA_1
<122> F_SC_NA_1
<123> F_LS_NA_1
<124> F_AF_NA_1
<125> F_SG_NA_1
<126> F_DR_TA_1*)

6. BASIC APPLICATION FUNCTIONS


Station Initialization:
4 Remote initialization
Cyclic Data Transmission:
4 Cyclic data transmission
Read Procedure:
4 Read procedure

D-6 G60 Generator Protection System GE Multilin


APPENDIX D D.1 IEC 60870-5-104

Spontaneous Transmission:
4 Spontaneous transmission
Double transmission of information objects with cause of transmission spontaneous:
The following type identifications may be transmitted in succession caused by a single status change of an information
object. The particular information object addresses for which double transmission is enabled are defined in a project-
specific list.
… Single point information: M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, and M_PS_NA_1
… Double point information: M_DP_NA_1, M_DP_TA_1, and M_DP_TB_1
… Step position information: M_ST_NA_1, M_ST_TA_1, and M_ST_TB_1
… Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project)
… Measured value, normalized value: M_ME_NA_1, M_ME_TA_1, M_ME_ND_1, and M_ME_TD_1
… Measured value, scaled value: M_ME_NB_1, M_ME_TB_1, and M_ME_TE_1
… Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1
Station interrogation:
4 Global D
4 Group 1 4 Group 5 4 Group 9 4 Group 13
4 Group 2 4 Group 6 4 Group 10 4 Group 14
4 Group 3 4 Group 7 4 Group 11 4 Group 15
4 Group 4 4 Group 8 4 Group 12 4 Group 16

Clock synchronization:
4 Clock synchronization (optional, see Clause 7.6)

Command transmission:
4 Direct command transmission
… Direct setpoint command transmission
4 Select and execute command
… Select and execute setpoint command
4 C_SE ACTTERM used
4 No additional definition
4 Short pulse duration (duration determined by a system parameter in the outstation)
4 Long pulse duration (duration determined by a system parameter in the outstation)
4 Persistent output

4 Supervision of maximum delay in command direction of commands and setpoint commands


Maximum allowable delay of commands and setpoint commands: 10 s
Transmission of integrated totals:
4 Mode A: Local freeze with spontaneous transmission
4 Mode B: Local freeze with counter interrogation
4 Mode C: Freeze and transmit by counter-interrogation commands
4 Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously

4 Counter read
4 Counter freeze without reset

GE Multilin G60 Generator Protection System D-7


D.1 IEC 60870-5-104 APPENDIX D

4 Counter freeze with reset


4 Counter reset

4 General request counter


4 Request counter group 1
4 Request counter group 2
4 Request counter group 3
4 Request counter group 4
Parameter loading:
4 Threshold value
… Smoothing factor
… Low limit for transmission of measured values
… High limit for transmission of measured values
Parameter activation:
D … Activation/deactivation of persistent cyclic or periodic transmission of the addressed object
Test procedure:
… Test procedure
File transfer:
File transfer in monitor direction:
… Transparent file
… Transmission of disturbance data of protection equipment
… Transmission of sequences of events
… Transmission of sequences of recorded analog values
File transfer in control direction:
… Transparent file
Background scan:
… Background scan
Acquisition of transmission delay:
„ Acquisition of transmission delay

Definition of time outs:


PARAMETER DEFAULT REMARKS SELECTED
VALUE VALUE
t0 30 s Timeout of connection establishment 120 s
t1 15 s Timeout of send or test APDUs 15 s
t2 10 s Timeout for acknowlegements in case of no data messages t2 < t1 10 s
t3 20 s Timeout for sending test frames in case of a long idle state 20 s

Maximum range of values for all time outs: 1 to 255 s, accuracy 1 s


Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w):
PARAMETER DEFAULT REMARKS SELECTED
VALUE VALUE
k 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs
w 8 APDUs Latest acknowledge after receiving w I-format APDUs 8 APDUs

D-8 G60 Generator Protection System GE Multilin


APPENDIX D D.1 IEC 60870-5-104

Maximum range of values k: 1 to 32767 (215 – 1) APDUs, accuracy 1 APDU


Maximum range of values w: 1 to 32767 APDUs, accuracy 1 APDU
Recommendation: w should not exceed two-thirds of k.
Portnumber:
PARAMETER VALUE REMARKS
Portnumber 2404 In all cases

RFC 2200 suite:


RFC 2200 is an official Internet Standard which describes the state of standardization of protocols used in the Internet
as determined by the Internet Architecture Board (IAB). It offers a broad spectrum of actual standards used in the Inter-
net. The suitable selection of documents from RFC 2200 defined in this standard for given projects has to be chosen
by the user of this standard.
4 Ethernet 802.3
… Serial X.21 interface
… Other selection(s) from RFC 2200 (list below if selected)

D.1.2 IEC 60870-5-104 POINT LIST


D
The IEC 60870-5-104 data points are configured through the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP /
menu. Refer to the Communications section of Chapter 5 for additional details.
IEC104 POINT LISTS

GE Multilin G60 Generator Protection System D-9


D.1 IEC 60870-5-104 APPENDIX D

D-10 G60 Generator Protection System GE Multilin


APPENDIX E E.1 DEVICE PROFILE DOCUMENT

APPENDIX E DNP COMMUNICATIONSE.1DEVICE PROFILE DOCUMENT E.1.1 DNP V3.00 DEVICE PROFILE

The following table provides a ‘Device Profile Document’ in the standard format defined in the DNP 3.0 Subset Definitions
Document.

Table E–1: DNP V3.00 DEVICE PROFILE (Sheet 1 of 3)

(Also see the IMPLEMENTATION TABLE in the following section)

Vendor Name: General Electric Multilin

Device Name: UR Series Relay

Highest DNP Level Supported: Device Function:


For Requests: Level 2 … Master
For Responses: Level 2 4 Slave

Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
Binary Inputs (Object 1)
Binary Input Changes (Object 2)
Binary Outputs (Object 10)
Control Relay Output Block (Object 12)
Binary Counters (Object 20)
E
Frozen Counters (Object 21)
Counter Change Event (Object 22)
Frozen Counter Event (Object 23)
Analog Inputs (Object 30)
Analog Input Changes (Object 32)
Analog Deadbands (Object 34)
Time and Date (Object 50)
File Transfer (Object 70)
Internal Indications (Object 80)

Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted: 292 Transmitted: configurable up to 2048
Received: 292 Received: 2048

Maximum Data Link Re-tries: Maximum Application Layer Re-tries:


4 None 4 None
… Fixed at 3 … Configurable
… Configurable

Requires Data Link Layer Confirmation:


4 Never
… Always
… Sometimes
… Configurable

GE Multilin G60 Generator Protection System E-1


E.1 DEVICE PROFILE DOCUMENT APPENDIX E

Table E–1: DNP V3.00 DEVICE PROFILE (Sheet 2 of 3)

Requires Application Layer Confirmation:


… Never
… Always
4 When reporting Event Data
4 When sending multi-fragment responses
… Sometimes
… Configurable

Timeouts while waiting for:


Data Link Confirm: 4 None … Fixed at ____ … Variable … Configurable
Complete Appl. Fragment: 4 None … Fixed at ____ … Variable … Configurable
Application Confirm: … None 4 Fixed at 10 s … Variable … Configurable
Complete Appl. Response: 4 None … Fixed at ____ … Variable … Configurable

Others:
Transmission Delay: No intentional delay
Need Time Interval: Configurable (default = 24 hrs.)
Select/Operate Arm Timeout: 10 s
Binary input change scanning period: 8 times per power system cycle
Analog input change scanning period: 500 ms

E Counter change scanning period:


Frozen counter event scanning period:
500 ms
500 ms
Unsolicited response notification delay: 100 ms
Unsolicited response retry delay configurable 0 to 60 sec.

Sends/Executes Control Operations:


WRITE Binary Outputs 4 Never … Always … Sometimes … Configurable
SELECT/OPERATE … Never 4 Always … Sometimes … Configurable
DIRECT OPERATE … Never 4 Always … Sometimes … Configurable
DIRECT OPERATE – NO ACK … Never 4 Always … Sometimes … Configurable

Count > 1 4 Never … Always … Sometimes … Configurable


Pulse On … Never … Always 4 Sometimes … Configurable
Pulse Off … Never … Always 4 Sometimes … Configurable
Latch On … Never … Always 4 Sometimes … Configurable
Latch Off … Never … Always 4 Sometimes … Configurable

Queue 4 Never … Always … Sometimes … Configurable


Clear Queue 4 Never … Always … Sometimes … Configurable

Explanation of ‘Sometimes’: Object 12 points are mapped to UR Virtual Inputs. The persistence of Virtual Inputs is
determined by the VIRTUAL INPUT X TYPE settings. Both “Pulse On” and “Latch On” operations perform the same func-
tion in the UR; that is, the appropriate Virtual Input is put into the “On” state. If the Virtual Input is set to “Self-Reset”,
it will reset after one pass of FlexLogic™. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off”
operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate
Virtual Input into the “On” state.

E-2 G60 Generator Protection System GE Multilin


APPENDIX E E.1 DEVICE PROFILE DOCUMENT

Table E–1: DNP V3.00 DEVICE PROFILE (Sheet 3 of 3)

Reports Binary Input Change Events when no Reports time-tagged Binary Input Change Events when no
specific variation requested: specific variation requested:
… Never … Never
4 Only time-tagged 4 Binary Input Change With Time
… Only non-time-tagged … Binary Input Change With Relative Time
… Configurable … Configurable (attach explanation)

Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:


… Never 4 Never
4 Configurable … When Device Restarts
… Only certain objects … When Status Flags Change
… Sometimes (attach explanation)
4 ENABLE/DISABLE unsolicited Function No other options are permitted.
codes supported

Default Counter Object/Variation: Counters Roll Over at:


… No Counters Reported … No Counters Reported
… Configurable (attach explanation) … Configurable (attach explanation)
4 Default Object: 20 4 16 Bits (Counter 8)
Default Variation: 1 4 32 Bits (Counters 0 to 7, 9)
4 Point-by-point list attached … Other Value: _____
4 Point-by-point list attached E
Sends Multi-Fragment Responses:
4 Yes
… No

GE Multilin G60 Generator Protection System E-3


E.1 DEVICE PROFILE DOCUMENT APPENDIX E

E.1.2 IMPLEMENTATION TABLE

The following table identifies the variations, function codes, and qualifiers supported by the G60 in both request messages
and in response messages. For static (non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07, or 08, will be
responded with qualifiers 00 or 01. Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or
28. For change-event objects, qualifiers 17 or 28 are always responded.

Table E–2: IMPLEMENTATION TABLE (Sheet 1 of 4)


OBJECT REQUEST RESPONSE
OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER FUNCTION QUALIFIER
NO. NO. CODES (DEC) CODES (HEX) CODES (DEC) CODES (HEX)
1 0 Binary Input (Variation 0 is used to request 1 (read) 00, 01 (start-stop)
default variation) 22 (assign class) 06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
1 Binary Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
2 Binary Input with Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
2 0 Binary Input Change (Variation 0 is used to 1 (read) 06 (no range, or all)
request default variation) 07, 08 (limited quantity)
1 Binary Input Change without Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited quantity) 130 (unsol. resp.)
E 2 Binary Input Change with Time 1 (read) 06 (no range, or all)
07, 08 (limited quantity)
129 (response
130 (unsol. resp.)
17, 28 (index)

3 Binary Input Change with Relative Time 1 (read) 06 (no range, or all)
07, 08 (limited quantity)
10 0 Binary Output Status (Variation 0 is used to 1 (read) 00, 01(start-stop)
request default variation) 06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
12 1 Control Relay Output Block 3 (select) 00, 01 (start-stop) 129 (response) echo of request
4 (operate) 07, 08 (limited quantity)
5 (direct op) 17, 28 (index)
6 (dir. op, noack)
20 0 Binary Counter 1 (read) 00, 01(start-stop)
(Variation 0 is used to request default 7 (freeze) 06(no range, or all)
variation) 8 (freeze noack) 07, 08(limited quantity)
9 (freeze clear) 17, 28(index)
10 (frz. cl. noack)
22 (assign class)
1 32-Bit Binary Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
7 (freeze) 06 (no range, or all) 17, 28 (index)
8 (freeze noack) 07, 08 (limited quantity) (see Note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
22 (assign class)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default varia-
tions for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5
for details. This optimizes the class 0 poll data size.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3: Cold restarts are implemented the same as warm restarts – the G60 is not restarted, but the DNP process is restarted.

E-4 G60 Generator Protection System GE Multilin


APPENDIX E E.1 DEVICE PROFILE DOCUMENT

Table E–2: IMPLEMENTATION TABLE (Sheet 2 of 4)


OBJECT REQUEST RESPONSE
OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER FUNCTION QUALIFIER
NO. NO. CODES (DEC) CODES (HEX) CODES (DEC) CODES (HEX)
20 2 16-Bit Binary Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
cont’d 7 (freeze) 06 (no range, or all) 17, 28 (index)
8 (freeze noack) 07, 08 (limited quantity) (see Note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
22 (assign class)
5 32-Bit Binary Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
7 (freeze) 06 (no range, or all) 17, 28 (index)
8 (freeze noack) 07, 08 (limited quantity) (see Note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
22 (assign class)
6 16-Bit Binary Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
7 (freeze) 06 (no range, or all) 17, 28 (index)
8 (freeze noack) 07, 08 (limited quantity) (see Note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
22 (assign class)
21 0 Frozen Counter 1 (read) 00, 01 (start-stop)
(Variation 0 is used to request default 22 (assign class) 06 (no range, or all)
variation) 07, 08 (limited quantity)
17, 28 (index)
1 32-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index) E
2 16-Bit Frozen Counter 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
9 32-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
10 16-Bit Frozen Counter without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
22 0 Counter Change Event (Variation 0 is used 1 (read) 06 (no range, or all)
to request default variation) 07, 08 (limited quantity)
1 32-Bit Counter Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited quantity) 130 (unsol. resp.)
2 16-Bit Counter Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited quantity) 130 (unsol. resp.)
5 32-Bit Counter Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited quantity) 130 (unsol. resp.)
6 16-Bit Counter Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited quantity) 130 (unsol. resp.)
23 0 Frozen Counter Event (Variation 0 is used 1 (read) 06 (no range, or all)
to request default variation) 07, 08 (limited quantity)
1 32-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited quantity) 130 (unsol. resp.)
2 16-Bit Frozen Counter Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited quantity) 130 (unsol. resp.)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default varia-
tions for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5
for details. This optimizes the class 0 poll data size.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3: Cold restarts are implemented the same as warm restarts – the G60 is not restarted, but the DNP process is restarted.

GE Multilin G60 Generator Protection System E-5


E.1 DEVICE PROFILE DOCUMENT APPENDIX E

Table E–2: IMPLEMENTATION TABLE (Sheet 3 of 4)


OBJECT REQUEST RESPONSE
OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER FUNCTION QUALIFIER
NO. NO. CODES (DEC) CODES (HEX) CODES (DEC) CODES (HEX)
23 5 32-Bit Frozen Counter Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
cont’d 07, 08 (limited quantity) 130 (unsol. resp.)
6 16-Bit Frozen Counter Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited quantity) 130 (unsol. resp.)
30 0 Analog Input (Variation 0 is used to request 1 (read) 00, 01 (start-stop)
default variation) 22 (assign class) 06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
1 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
2 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
3 32-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
4 16-Bit Analog Input without Flag 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)

E 5 short floating point 1 (read)


22 (assign class)
00, 01 (start-stop)
06(no range, or all)
129 (response) 00, 01 (start-stop)
17, 28 (index)
07, 08(limited quantity) (see Note 2)
17, 28(index)
32 0 Analog Change Event (Variation 0 is used 1 (read) 06 (no range, or all)
to request default variation) 07, 08 (limited quantity)
1 32-Bit Analog Change Event without Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited quantity) 130 (unsol. resp.)
2 16-Bit Analog Change Event without Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited quantity) 130 (unsol. resp.)
3 32-Bit Analog Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited quantity) 130 (unsol. resp.)
4 16-Bit Analog Change Event with Time 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
07, 08 (limited quantity) 130 (unsol. resp.)
5 short floating point Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited quantity) 130 (unsol. resp.)
7 short floating point Analog Change Event 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited quantity) 130 (unsol. resp.)
34 0 Analog Input Reporting Deadband 1 (read) 00, 01 (start-stop)
(Variation 0 is used to request default 06 (no range, or all)
variation) 07, 08 (limited quantity)
17, 28 (index)
1 16-bit Analog Input Reporting Deadband 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – see Note 1) 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
2 (write) 00, 01 (start-stop)
07, 08 (limited quantity)
17, 28 (index)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default varia-
tions for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5
for details. This optimizes the class 0 poll data size.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3: Cold restarts are implemented the same as warm restarts – the G60 is not restarted, but the DNP process is restarted.

E-6 G60 Generator Protection System GE Multilin


APPENDIX E E.1 DEVICE PROFILE DOCUMENT

Table E–2: IMPLEMENTATION TABLE (Sheet 4 of 4)


OBJECT REQUEST RESPONSE
OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER FUNCTION QUALIFIER
NO. NO. CODES (DEC) CODES (HEX) CODES (DEC) CODES (HEX)
34 2 32-bit Analog Input Reporting Deadband 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
cont’d 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
2 (write) 00, 01 (start-stop)
07, 08 (limited quantity)
17, 28 (index)
3 Short floating point Analog Input Reporting 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Deadband 06 (no range, or all) 17, 28 (index)
07, 08 (limited quantity) (see Note 2)
17, 28 (index)
50 1 Time and Date 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default – see Note 1) 2 (write) 06 (no range, or all) 17, 28 (index)
07 (limited qty=1) (see Note 2)
08 (limited quantity)
17, 28 (index)
52 2 Time Delay Fine 129 (response) 07 (limited quantity)
(quantity = 1)
60 0 Class 0, 1, 2, and 3 Data 1 (read) 06 (no range, or all)
20 (enable unsol)
21 (disable unsol)
22 (assign class)
1 Class 0 Data 1 (read) 06 (no range, or all)
22 (assign class)
2
3
Class 1 Data
Class 2 Data
1 (read)
20 (enable unsol)
06 (no range, or all)
07, 08 (limited quantity) E
4 Class 3 Data 21 (disable unsol)
22 (assign class)
70 0 File event - any variation 1 (read) 06 (no range, or all)
07, 08 (limited quantity)
22 (assign class) 06 (no range, or all)
2 File authentication 29 (authenticate) 5b (free format) 129 (response) 5b (free format)
3 File command 25 (open) 5b (free format)
27 (delete)
4 File command status 26 (close) 5b (free format) 129 (response) 5b (free format)
30 (abort) 130 (unsol. resp.)
5 File transfer 1 (read) 5b (free format) 129 (response) 5b (free format)
2 (write) 130 (unsol. resp.)
6 File transfer status 129 (response) 5b (free format)
130 (unsol. resp.)
7 File descriptor 28 (get file info.) 5b (free format) 129 (response) 5b (free format)
130 (unsol. resp.)
80 1 Internal Indications 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(index =7)
2 (write) 00 (start-stop)
(see Note 3) (index =7)
--- No Object (function code only) 13 (cold restart)
see Note 3
--- No Object (function code only) 14 (warm restart)
--- No Object (function code only) 23 (delay meas.)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The default varia-
tions for object types 1, 2, 20, 21, 22, 23, 30, and 32 are selected via relay settings. Refer to the Communications section in Chapter 5
for details. This optimizes the class 0 poll data size.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respec-
tively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change-
event objects, qualifiers 17 or 28 are always responded.)
Note 3: Cold restarts are implemented the same as warm restarts – the G60 is not restarted, but the DNP process is restarted.

GE Multilin G60 Generator Protection System E-7


E.2 DNP POINT LISTS APPENDIX E

E.2DNP POINT LISTS E.2.1 BINARY INPUT POINTS

The DNP binary input data points are configured through the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT
LISTS Ö BINARY INPUT / MSP POINTS menu. Refer to the Communications section of Chapter 5 for additional details. When a
freeze function is performed on a binary counter point, the frozen value is available in the corresponding frozen counter
point.

BINARY INPUT POINTS


Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read), 22 (assign class)
Static Variation reported when variation 0 requested: 2 (Binary Input with status), Configurable
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable
Change Event Scan Rate: 8 times per power system cycle
Change Event Buffer Size: 500
Default Class for All Points: 1

E-8 G60 Generator Protection System GE Multilin


APPENDIX E E.2 DNP POINT LISTS

E.2.2 BINARY AND CONTROL RELAY OUTPUT

Supported Control Relay Output Block fields: Pulse On, Pulse Off, Latch On, Latch Off, Paired Trip, Paired Close.

BINARY OUTPUT STATUS POINTS


Object Number: 10
Request Function Codes supported: 1 (read)
Default Variation reported when Variation 0 requested: 2 (Binary Output Status)
CONTROL RELAY OUTPUT BLOCKS
Object Number: 12
Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, noack)

Table E–3: BINARY/CONTROL OUTPUTS Table E–3: BINARY/CONTROL OUTPUTS


POINT NAME/DESCRIPTION POINT NAME/DESCRIPTION
0 Virtual Input 1 32 Virtual Input 33
1 Virtual Input 2 33 Virtual Input 34
2 Virtual Input 3 34 Virtual Input 35
3 Virtual Input 4 35 Virtual Input 36
4 Virtual Input 5 36 Virtual Input 37
5 Virtual Input 6 37 Virtual Input 38
6 Virtual Input 7 38 Virtual Input 39
7 Virtual Input 8 39 Virtual Input 40
E
8 Virtual Input 9 40 Virtual Input 41
9 Virtual Input 10 41 Virtual Input 42
10 Virtual Input 11 42 Virtual Input 43
11 Virtual Input 12 43 Virtual Input 44
12 Virtual Input 13 44 Virtual Input 45
13 Virtual Input 14 45 Virtual Input 46
14 Virtual Input 15 46 Virtual Input 47
15 Virtual Input 16 47 Virtual Input 48
16 Virtual Input 17 48 Virtual Input 49
17 Virtual Input 18 49 Virtual Input 50
18 Virtual Input 19 50 Virtual Input 51
19 Virtual Input 20 51 Virtual Input 52
20 Virtual Input 21 52 Virtual Input 53
21 Virtual Input 22 53 Virtual Input 54
22 Virtual Input 23 54 Virtual Input 55
23 Virtual Input 24 55 Virtual Input 56
24 Virtual Input 25 56 Virtual Input 57
25 Virtual Input 26 57 Virtual Input 58
26 Virtual Input 27 58 Virtual Input 59
27 Virtual Input 28 59 Virtual Input 60
28 Virtual Input 29 60 Virtual Input 61
29 Virtual Input 30 61 Virtual Input 62
30 Virtual Input 31 62 Virtual Input 63
31 Virtual Input 32 63 Virtual Input 64

GE Multilin G60 Generator Protection System E-9


E.2 DNP POINT LISTS APPENDIX E

E.2.3 COUNTERS

The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21). When a freeze function is per-
formed on a Binary Counter point, the frozen value is available in the corresponding Frozen Counter point.

BINARY COUNTERS
Static (Steady-State) Object Number: 20
Change Event Object Number: 22
Request Function Codes supported: 1 (read), 7 (freeze), 8 (freeze noack), 9 (freeze and clear),
10 (freeze and clear, noack), 22 (assign class)
Static Variation reported when variation 0 requested: 1 (32-Bit Binary Counter with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter Change Event without time)
Change Event Buffer Size: 10
Default Class for all points: 3
FROZEN COUNTERS
Static (Steady-State) Object Number: 21
Change Event Object Number: 23
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter with Flag)
E Change Event Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter Event without time)
Change Event Buffer Size: 10
Default Class for all points: 3

Table E–4: BINARY AND FROZEN COUNTERS


POINT NAME/DESCRIPTION
INDEX
0 Digital Counter 1
1 Digital Counter 2
2 Digital Counter 3
3 Digital Counter 4
4 Digital Counter 5
5 Digital Counter 6
6 Digital Counter 7
7 Digital Counter 8
8 Oscillography Trigger Count
9 Events Since Last Clear

A counter freeze command has no meaning for counters 8 and 9. G60 Digital Counter values are represented as 32-bit
integers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative
counter values.

E-10 G60 Generator Protection System GE Multilin


APPENDIX E E.2 DNP POINT LISTS

E.2.4 ANALOG INPUTS

The DNP analog input data points are configured through the PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ DNP / IEC104 POINT
LISTS Ö ANALOG INPUT / MME POINTS menu. Refer to the Communications section of Chapter 5 for additional details.
It is important to note that 16-bit and 32-bit variations of analog inputs are transmitted through DNP as signed numbers.
Even for analog input points that are not valid as negative values, the maximum positive representation is 32767 for 16-bit
values and 2147483647 for 32-bit values. This is a DNP requirement.
The deadbands for all Analog Input points are in the same units as the Analog Input quantity. For example, an Analog Input
quantity measured in volts has a corresponding deadband in units of volts. This is in conformance with DNP Technical Bul-
letin 9809-001: Analog Input Reporting Deadband. Relay settings are available to set default deadband values according to
data type. Deadbands for individual Analog Input Points can be set using DNP Object 34.

Static (Steady-State) Object Number: 30


Change Event Object Number: 32
Request Function Codes supported: 1 (read), 2 (write, deadbands only), 22 (assign class)
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input)
Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time)
Change Event Scan Rate: defaults to 500 ms
Change Event Buffer Size: 256
Default Class for all Points: 2
E

GE Multilin G60 Generator Protection System E-11


E.2 DNP POINT LISTS APPENDIX E

E-12 G60 Generator Protection System GE Multilin


APPENDIX F F.1 CHANGE NOTES

APPENDIX F MISCELLANEOUSF.1CHANGE NOTES F.1.1 REVISION HISTORY

Table F–1: REVISION HISTORY


MANUAL P/N G60 REVISION RELEASE DATE ECO
1601-0110-B1 2.8x 27 September 2001 URG-001
1601-0110-B2 2.9x 03 December 2001 URG-002
1601-0110-B3 2.9x 23 January 2001 URG-003
1601-0110-C1 3.0x 02 July 2002 URG-004
1601-0110-C2 3.1x 30 August 2002 URG-005
1601-0110-C3 3.0x 18 November 2002 URG-006
1601-0110-C4 3.1x 18 November 2002 URG-007
1601-0110-C5 3.1x 16 January 2003 URG-008
1601-0110-C6 3.0x 27 January 2003 URG-009
1601-0110-C7 3.1x 27 January 2003 URG-010
1601-0110-C8 3.0x 11 February 2003 URG-011
1601-0110-C9 3.1x 11 February 2003 URG-013
1601-0110-D1 3.2x 11 February 2003 URG-012
1601-0110-D2 3.2x 02 June 2003 URX-084
1601-0110-E1 3.3x 01 May 2003 URX-080
1601-0110-E2 3.3x 29 May 2003 URX-083
1601-0110-F1 3.4x 10 December 2003 URX-111
1601-0110-F2 3.4x 30 January 2004 URX-115
1601-0110-G1 4.0x 23 March 2004 URX-123
1601-0110-G2 4.0x 17 May 2004 URX-136
1601-0110-H1 4.2x 30 June 2004 URX-145
1601-0110-H2 4.2x 23 July 2004 URX-151
1601-0110-J1 4.4x 15 September 2004 URX-156 F
1601-0110-K1 4.6x 15 February 2005 URX-176
1601-0110-L1 4.8x 05 August 2005 URX-202
1601-0110-M1 4.9x 15 December 2005 URX-208
1601-0110-M2 4.9x 27 February 2006 URX-214
1601-0110-N1 5.0x 31 March 2006 URX-217
1601-0110-N2 5.0x 26 May 2006 URX-220
1601-0110-P1 5.2x 23 October 2006 URX-230
1601-0110-P2 5.2x 24 January 2007 URX-232
1601-0110-R1 5.4x 01 July 2007 URX-242
1601-0110-R2 5.4x 31 August 2007 URX-246
1601-0110-R3 5.4x 17 October 2007 URX-251
1601-0110-S1 5.5x 7 December 2007 URX-253
1601-0110-S2 5.5x 22 February 2008 URX-258
1601-0110-S3 5.5x 12 March 2008 URX-260
1601-0110-T1 5.6x 27 June 2008 08-0390
1601-0110-U1 5.7x 29 May 2009 09-0938
1601-0110-U2 5.7x 30 September 2009 09-1165
1601-0110-V1 5.8x 29 May 2010 09-1457
1601-0110-V2 5.8x 04 January 2011 11-2237
1601-0110-W1 5.9x 12 January 2011 11-2227

GE Multilin G60 Generator Protection System F-1


F.1 CHANGE NOTES APPENDIX F

F.1.2 CHANGES TO THE G60 MANUAL

Table F–2: MAJOR UPDATES FOR G60 MANUAL REVISION W1


PAGE PAGE CHANGE DESCRIPTION
(V2) (W1)
Title Title Update Manual part number to 1601-0110-W1

2- 2-10 Update Updated PROTECTION ELEMENTS specifications section

--- 3-64 Update Added INITIAL SETUP OF THE ETHERNET SWITCH MODULE section

4-3 4-3 Update Updated USING SETTING FILES section

5-18 5-22 Update Updated IEC 61850 PROTOCOL section


5-40 5-42 Update Updated OSCILLOGRAPHY section
5-54 5-57 Update Updated USER-DEFINABLE DISPLAYS section
5-72 5-75 Update Updated BREAKERS section
5-76 5-79 Update Updated DISCONNECT SWITCHES section
5-86 5-89 Update Updated PHASOR MEASUREMENT UNIT section
5-104 5-107 Update Updated FLEXLOGIC OPERANDS table
5-187 5-191 Update Updated VOLTS PER HERTZ section
5-205 5-210 Update Updated APPLICATION CONSIDERATIONS FOR SUB-HARMONIC STATOR GROUND FAULT
DETECTOR section
--- 5-243 Add Added THERMAL OVERLOAD PROTECTION section
5-244 5-253 Update Updated REMOTE INPUTS section

B-9 B-9 Update Updated MODBUS MEMORY MAP section

C-3 C-3 Update Updated PROTECTION AND OTHER LOGICAL NODES section

F Table F–3: MAJOR UPDATES FOR G60 MANUAL REVISION V2


PAGE PAGE CHANGE DESCRIPTION
(V1) (V2)
Title Title Update Manual part number to 1601-0110-V2

2-3 2-3 Update Updated ORDERING section

3-25 3-25 Update Updated RS485 PORTS section

5-200 5-200 Update Updated THIRD HARMONIC NEUTRAL UNDERVOLTAGE section


5-230 5-230 Update Updated SPECIAL APPLICATION OF THE SYNCHROCHECK ELEMENT section

Table F–4: MAJOR UPDATES FOR G60 MANUAL REVISION V1 (Sheet 1 of 2)


PAGE PAGE CHANGE DESCRIPTION
(U2) (V1)
Title Title Update Manual part number to 1601-0110-V1

2-1 2-1 Update Updated OVERVIEW section


2-3 2-3 Update Updated ORDERING section
2-7 2-7 Update Updated REPLACEMENT MODULES section
2-10 2-10 Update Updated PROTECTION ELEMENTS specifications section
2-15 2-15 Update Updated METERING specifications section
--- 2-19 Add Added FIELD AND STATOR GROUND MODULES specifications section

3-10 3-10 Update Updated TYPICAL WIRING section

F-2 G60 Generator Protection System GE Multilin


APPENDIX F F.1 CHANGE NOTES

Table F–4: MAJOR UPDATES FOR G60 MANUAL REVISION V1 (Sheet 2 of 2)


PAGE PAGE CHANGE DESCRIPTION
(U2) (V1)
3-23 3-24 Update Updated CPU COMMUNICATION PORTS section
--- 3-41 Add Added FIELD AND STATOR GROUND MODULES section
3-41 3-62 Update Updated MANAGED ETHERNET SWITCH MODULE HARDWARE section

4-28 4-28 Update Updated INVALID PASSWORD ENTRY section

5-10 5-10 Update Updated ACCESS SUPERVISION section


5-15 5-15 Update Updated SERIAL PORTS section
5-22 5-22 Update Updated IEC 61850 PROTOCOL section
5-103 5-104 Update Updated FLEXLOGIC OPERANDS table
5-119 5-119 Update Updated FLEXELEMENTS™ section
5-124 5-124 Update Updated SETTING GROUP section
5-169 5-169 Update Updated NEGATIVE-SEQUENCE DIRECTIONAL OVERCURRENT section
5-172 5-174 Update Updated GENERATOR UNBALANCE section
5-195 5-197 Update Updated STATOR GROUND section
--- 5-202 Add Added SUB-HARMONIC STATOR GROUND FAULT section
--- 5-205 Add Added APPLICATION CONSIDERATIONS FOR SUB-HARMONIC STATOR GROUND FAULT
DETECTOR section
--- 5-205 Add Added FIELD GROUND FAULT PROTECTION section
5-215 5-225 Update Updated FREQUENCY OUT-OF-BAND ACCUMULATORS 1 TO 7 section

6-14 6-14 Update Updated SOURCES section


6-19 6-21 Update Updated FLEXELEMENTS™ section

--- 7-10 Add Added EXTERNAL DEVICE SELF-TEST ERROR MESSAGES section

A-1 A-1 Update Updated FLEXANALOG ITEMS section

B-8 B-8 Update Updated MODBUS MEMORY MAP section F


C-3 C-3 Update Updated PROTECTION AND OTHER LOGICAL NODES section

Table F–5: MAJOR UPDATES FOR G60 MANUAL REVISION U2 (Sheet 1 of 2)


PAGE PAGE CHANGE DESCRIPTION
(U1) (U2)
Title Title Update Manual part number to 1601-0110-U2

1-1 1-1 Update Updated INSPECTION CHECKLIST section

2-1 2-1 Update Updated OVERVIEW section


2-14 2-14 Update Updated USER-PROGRAMMABLE ELEMENTS specifications section
2-19 2-20 Update Updated ENVIRONMENTAL specifications section
2-20 2-21 Update Updated TYPE TESTS specifications section
2-20 2-22 Update Updated APPROVALS specifications section

4-14 4-14 Update Updated LED INDICATORS section

5-22 5-22 Update Updated IEC 61850 PROTOCOL section


5-75 5-75 Update Updated DISCONNECT SWITCHES section
5-158 5-158 Update Updated NEUTRAL DIRECTIONAL OVERCURRENT section
5-169 5-169 Update Updated NEGATIVE-SEQUENCE DIRECTIONAL OVERCURRENT section
5-212 5-212 Update Updated FREQUENCY RATE OF CHANGE section
5-226 5-226 Update Updated VT FUSE FAILURE section

GE Multilin G60 Generator Protection System F-3


F.1 CHANGE NOTES APPENDIX F

Table F–5: MAJOR UPDATES FOR G60 MANUAL REVISION U2 (Sheet 2 of 2)


PAGE PAGE CHANGE DESCRIPTION
(U1) (U2)
C-7 C-7 Update Updated CONFIGURABLE GOOSE section

Table F–6: MAJOR UPDATES FOR G60 MANUAL REVISION U1 (Sheet 1 of 2)


PAGE PAGE CHANGE DESCRIPTION
(T1) (U1)
Title Title Update Manual part number to 1601-0110-U1

2-1 2-1 Update Updated OVERVIEW section


2-9 2-9 Update Updated PROTECTION ELEMENTS section for changes to underfrequency, overfrequency, rate
of change of frequency, 100% stator ground, and restricted ground fault specifications, and new
remote RTD specification
2-13 2-13 Update Updated MONITORING specifications section
2-14 2-14 Update Updated INPUTS specifications section
2-18 2-18 Update Updated ENVIRONMENTAL specifications section
2-19 2-19 Update Updated TYPE TESTS specifications section

3-2 3-2 Update Updated VERTICAL UNITS sub-section


3-13 3-14 Update Updated CONTACT INPUTS AND OUTPUTS section

4-1 4-1 Update Updated USING SETTINGS FILES section

5-8 5-8 Update Updated SECURITY section


5-15 5-15 Update Updated SERIAL PORTS sub-section
5-21 5-22 Update Updated IEC 61850 PROTOCOL sub-section
5-37 5-39 Update Updated OSCILLOGRAPHY section
5-65 5-67 Update Updated POWER SYSTEM section
5-69 5-71 Update Updated BREAKERS section
F 5-73 5-75 Update Updated DISCONNECT SWITCHES section
--- 5-90 Add Added USER TRIGGERING sub-section
5-101 5-103 Update Updated FLEXLOGIC OPERANDS table
5-123 5-126 Update Updated PHASE DISTANCE sub-section
5-147 5-151 Update Updated PHASE INSTANTANEOUS OVERCURRENT section
5-153 5-158 Update Updated NEUTRAL DIRECTIONAL OVERCURRENT section
5-160 5-165 Update Updated RESTRICTED GROUND FAULT section
5-164 5-169 Update Updated NEGATIVE-SEQUENCE DIRECTIONAL OVERCURRENT section
5-176 5-181 Update Updated PHASE OVERVOLTAGE section
5-191 5-196 Update Updated 100% STATOR GROUND section
5-211 5-216 Update Updated SYNCHROCHECK section
--- 5-220 Add Added APPLICATION OF THE SYNCHROCHECK ELEMENT sub-section
5-215 5-221 Update Updated DIGITAL ELEMENTS section
5-220 5-226 Update Updated VT FUSE FAILURE section
5-224 5-230 Update Updated CONTACT OUTPUTS section
--- 5-242 Add Added IEC 61850 GOOSE ANALOGS section
--- 5-243 Add Added IEC 61850 GOOSE INTEGERS section
--- 5-247 Add Added RRTD INPUTS section

--- 6-9 Add Added IEC 61850 GOOSE INTEGERS section


6-21 6-21 Update Updated STATOR GROUND section
6-24 6-24 Update Updated PHASOR MEASUREMENT UNIT RECORDS section

7-2 7-3 Update Updated RELAY MAINTENANCE section

F-4 G60 Generator Protection System GE Multilin


APPENDIX F F.1 CHANGE NOTES

Table F–6: MAJOR UPDATES FOR G60 MANUAL REVISION U1 (Sheet 2 of 2)


PAGE PAGE CHANGE DESCRIPTION
(T1) (U1)
7-7 7-8 Update Updated MINOR SELF-TEST ERRORS section

--- 8-1 Add Added SECURITY chapter

A-1 A-1 Update Updated FLEXANALOG ITEMS section


--- A-11 Add Added FLEXINTEGER ITEMS section

B-8 B-8 Update Updated MODBUS MEMORY MAP section


B-63 B-65 Update Updated DATA FORMATS section

Table F–7: MAJOR UPDATES FOR G60 MANUAL REVISION T1


PAGE PAGE CHANGE DESCRIPTION
(S3) (T1)
Title Title Update Manual part number to 1601-0110-T1

2-2 2-2 Update Updated ORDERING section

--- 3-13 Add Added PROCESS BUS MODULES section

--- 5-11 Add Added DUAL PERMISSION SECURITY ACCESS section


5-20 5-21 Update Updated IEC 61850 PROTOCOL section
--- 5-63 Add Added REMOTE RESOURCES section
5-98 5-101 Update Updated FLEXLOGIC OPERANDS table
--- 5-229 Add Added REMOTE DOUBLE-POINT STATUS INPUTS section
5-240 5-244 Update Updated TEST MODE section

--- 6-4 Add Added REMOTE DOUBLE-POINT STATUS INPUTS section

B-8 B-8 Update Updated MODBUS MEMORY MAP section


F
Table F–8: MAJOR UPDATES FOR G60 MANUAL REVISION S3
PAGE PAGE CHANGE DESCRIPTION
(S2) (S3)
Title Title Update Manual part number to 1601-0110-S3

2-15 2-15 Update Updated COMMUNICATIONS specifications section


2-16 2-16 Update Updated INTER-RELAY COMMUNICATIONS specifications section

3-7 3-7 Update Updated REAR TERMINAL LAYOUT section


--- 3-46 Add Added ETHERNET SWITCH SELF-TEST ERRORS section

7-6 7-7 Update Updated MINOR SELF-TEST ERROR MESSAGES section

B-8 B-8 Update Update MODBUS MEMORY MAP section

GE Multilin G60 Generator Protection System F-5


F.1 CHANGE NOTES APPENDIX F

Table F–9: MAJOR UPDATES FOR G60 MANUAL REVISION S2


PAGE PAGE CHANGE DESCRIPTION
(S1) (S2)
Title Title Update Manual part number to 1601-0110-S2

3-40 3-40 Update Updated MANAGED ETHERNET SWITCH OVERVIEW section


3-40 3-40 Update Updated MANAGED ETHERNET SWITCH MODULE HARDWARE section
--- 3-43 Add Added UPLOADING G60 SWITCH MODULE FIRMWARE sub-section
--- 3-43 Add Added SELECTING THE PROPER SWITCH FIRMWARE VERSION sub-section

Table F–10: MAJOR UPDATES FOR G60 MANUAL REVISION S1


PAGE PAGE CHANGE DESCRIPTION
(R3) (S1)
Title Title Update Manual part number to 1601-0110-S1

2-2 2-2 Update Updated ORDERING section


2-4 2-4 Update Updated REPLACEMENT MODULES section
2-13 2-13 Update Updated OUTPUTS specifications section
2-14 2-15 Update Updated COMMUNICATIONS specifications section

3-35 3-36 Update Updated IEEE C37.94 INTERFACE section


--- 3-40 Add Added MANAGED ETHERNET SWITCH MODULES section

--- 4-23 Add Added BREAKER CONTROL section

5-8 5-8 Update Updated PASSWORD SECURITY section (now titled SECURITY)
--- 5-32 Add Added ETHERNET SWITCH sub-section
5-42 5-43 Update Updated USER-PROGRAMMABLE PUSHBUTTONS section
5-60 5-63 Update Updated SIGNAL SOURCES section
F --- 5-66 Add Added BREAKERS section
--- 5-70 Add Added DISCONNECT SWITCHES section
5-87 5-98 Update Updated FLEXLOGIC OPERANDS table

--- 6-9 Add Added ETHERNET SWITCH section


--- 6-24 Add Added PHASOR MEASUREMENT UNIT RECORDS section

B-8 B-8 Update Update MODBUS MEMORY MAP section for revision 5.5x

Table F–11: MAJOR UPDATES FOR G60 MANUAL REVISION R3


PAGE PAGE CHANGE DESCRIPTION
(R2) (R3)
Title Title Update Manual part number to 1601-0110-R3

--- 4-4 Add Added EXTENDED ENERVISTA UR SETUP FEATURES section

6-23 6-23 Update Updated MODEL INFORMATION section

Table F–12: MAJOR UPDATES FOR G60 MANUAL REVISION R2


PAGE PAGE CHANGE DESCRIPTION
(R1) (R2)
Title Title Update Manual part number to 1601-0110-R2

F-6 G60 Generator Protection System GE Multilin


APPENDIX F F.1 CHANGE NOTES

Table F–13: MAJOR UPDATES FOR G60 MANUAL REVISION R1


PAGE PAGE CHANGE DESCRIPTION
(P2) (R1)
Title Title Update Manual part number to 1601-0110-R1

2-2 2-2 Update Updated ORDERING section


2-7 2-7 Update Updated PROTECTION ELEMENTS specifications section

3-1 3-1 Update Updated PANEL CUTOUT section


3-4 3-5 Update Updated MODULE WITHDRAWAL AND INSERTION section

4-4 4-4 Update Updated FACEPLATE section


4-5 4-5 Update Updated LED INDICATORS section
4-7 4-8 Update Updated CUSTOM LABELING OF LEDS section
4-12 4-20 Update Updated ENTERING INITIAL PASSWORDS section

5-8 5-8 Update Updated PASSWORD SECURITY section


5-34 5-35 Update Updated USER-PROGRAMMABLE LEDS section
5-38 5-39 Update Updated CONTROL PUSHBUTTONS section
5-39 5-40 Update Updated USER-PROGRAMMABLE PUSHBUTTONS section
5-45 5-47 Update Updated DIRECT INPUTS AND OUTPUTS section
--- 5-67 Add Added PHASOR MEASUREMENT UNIT section
5-65 5-84 Update Updated FLEXLOGIC™ OPERANDS table
--- 5-203 Add Added TRIP BUS section
5-194 5-221 Update Updated RTD INPUTS section
--- 5-229 Add Added PHASOR MEASUREMENT UNIT TEST VALUES section

--- 6-19 Add Added PHASOR MEASUREMENT UNIT section

--- 7-3 Add Added PHASOR MEASUREMENT UNIT ONE-SHOT section


7-3 7-5 Update Updated RELAY SELF-TESTS section F
A-1 A-1 Update Updated FLEXANALOG PARAMETERS table

B-7 B-7 Update Updated MODBUS PASSWORD OPERATION section


B-8 B-8 Update Updated MODBUS MEMORY MAP section

--- C-2 Add Added GGIO4: GENERIC ANALOG MEASURED VALUES section
C-7 C-7 Update Updated CONFIGURABLE GOOSE section

Table F–14: MAJOR UPDATES FOR G60 MANUAL REVISION P2 (Sheet 1 of 2)


PAGE PAGE CHANGE DESCRIPTION
(P1) (P2)
Title Title Update Manual part number to 1601-0110-P2

2-2 2-2 Update Updated ORDERING section


2-7 2-7 Update Updated PROTECTION ELEMENTS specifications section

3-20 3-20 Update Updated CPU MODULE COMMUNICATIONS WIRING diagram to 842765A2

5-139 5-139 Update Updated NEGATIVE-SEQUENCE OVERVOLTAGE SCHEME LOGIC diagram to 827839A3

6-16 6-16 Update Updated TRACKING FREQUENCY section


--- 6-18 Add Added IEC 61850 GOOSE ANALOG VALUES section

7-4 7-4 Update Updated SELF-TEST ERROR MESSAGES table

GE Multilin G60 Generator Protection System F-7


F.1 CHANGE NOTES APPENDIX F

Table F–14: MAJOR UPDATES FOR G60 MANUAL REVISION P2 (Sheet 2 of 2)


PAGE PAGE CHANGE DESCRIPTION
(P1) (P2)
A-1 A-1 Update Updated FLEXANALOG PARAMETERS table

Table F–15: MAJOR UPDATES FOR G60 MANUAL REVISION P1


PAGE PAGE CHANGE DESCRIPTION
(N2) (P1)
Title Title Update Manual part number to 1601-0110-P1

2-2 2-2 Update Updated ORDERING section

3-30 3-30 Update Updated TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, 3-TERMINAL APPLICATION
drawing to 831022A3

5-14 5-14 Update Updated DNP PROTOCOL sub-section


5-18 5-18 Update Updated IEC 61850 PROTOCOL sub-section
5-63 5-65 Update Updated FLEXLOGIC™ OPERANDS table
5-135 5-137 Update Updated PHASE OVERVOLTAGE sub-section

B-8 B-8 Update Updated MODBUS MEMORY MAP section

C-1 C-1 Update Updated Appendix C: IEC 61850 COMMUNICATIONS

E-1 E-1 Update Updated DNP V3.00 DEVICE PROFILE section


E-4 E-4 Update Updated DNP IMPLEMENTATION TABLE section
E-8 E-8 Update Updated BINARY INPUT POINTS section
E-10 E-10 Update Updated COUNTERS section

F-8 G60 Generator Protection System GE Multilin


APPENDIX F F.2 ABBREVIATIONS

F.2ABBREVIATIONS F.2.1 STANDARD ABBREVIATIONS

A..................... Ampere FREQ..............Frequency


AC .................. Alternating Current FSK.................Frequency-Shift Keying
A/D ................. Analog to Digital FTP .................File Transfer Protocol
AE .................. Accidental Energization, Application Entity FxE .................FlexElement™
AMP ............... Ampere FWD................Forward
ANG ............... Angle
ANSI............... American National Standards Institute G .....................Generator
AR .................. Automatic Reclosure GE...................General Electric
ASDU ............. Application-layer Service Data Unit GND................Ground
ASYM ............. Asymmetry GNTR..............Generator
AUTO ............. Automatic GOOSE...........General Object Oriented Substation Event
AUX................ Auxiliary GPS ................Global Positioning System
AVG................ Average
HARM .............Harmonic / Harmonics
BER................ Bit Error Rate HCT ................High Current Time
BF................... Breaker Fail HGF ................High-Impedance Ground Fault (CT)
BFI.................. Breaker Failure Initiate HIZ ..................High-Impedance and Arcing Ground
BKR................ Breaker HMI .................Human-Machine Interface
BLK ................ Block HTTP ..............Hyper Text Transfer Protocol
BLKG.............. Blocking HYB ................Hybrid
BPNT.............. Breakpoint of a characteristic
BRKR ............. Breaker I.......................Instantaneous
I_0...................Zero Sequence current
CAP................ Capacitor I_1...................Positive Sequence current
CC .................. Coupling Capacitor I_2...................Negative Sequence current
CCVT ............. Coupling Capacitor Voltage Transformer IA ....................Phase A current
CFG................ Configure / Configurable IAB ..................Phase A minus B current
.CFG............... Filename extension for oscillography files IB ....................Phase B current
CHK................ Check IBC..................Phase B minus C current
CHNL ............. Channel IC ....................Phase C current
CLS ................ Close ICA..................Phase C minus A current
CLSD.............. Closed ID ....................Identification
CMND ............ Command IED..................Intelligent Electronic Device
CMPRSN........ Comparison IEC..................International Electrotechnical Commission
CO.................. Contact Output IEEE................Institute of Electrical and Electronic Engineers
COM............... Communication IG ....................Ground (not residual) current
COMM............ Communications Igd...................Differential Ground current
COMP ............ Compensated, Comparison IN ....................CT Residual Current (3Io) or Input
CONN............. Connection INC SEQ .........Incomplete Sequence
CONT ............. Continuous, Contact INIT .................Initiate
CO-ORD......... Coordination INST................Instantaneous
CPU................ Central Processing Unit
CRC ............... Cyclic Redundancy Code
INV..................Inverse
I/O ...................Input/Output
F
CRT, CRNT .... Current IOC .................Instantaneous Overcurrent
CSA................ Canadian Standards Association IOV..................Instantaneous Overvoltage
CT .................. Current Transformer IRIG ................Inter-Range Instrumentation Group
CVT ................ Capacitive Voltage Transformer ISO..................International Standards Organization
IUV..................Instantaneous Undervoltage
D/A ................. Digital to Analog
DC (dc)........... Direct Current K0 ...................Zero Sequence Current Compensation
DD .................. Disturbance Detector kA....................kiloAmpere
DFLT .............. Default kV....................kiloVolt
DGNST........... Diagnostics
DI.................... Digital Input LED.................Light Emitting Diode
DIFF ............... Differential LEO.................Line End Open
DIR ................. Directional LFT BLD .........Left Blinder
DISCREP ....... Discrepancy LOOP..............Loopback
DIST ............... Distance LPU.................Line Pickup
DMD ............... Demand LRA.................Locked-Rotor Current
DNP................ Distributed Network Protocol LTC .................Load Tap-Changer
DPO ............... Dropout
DSP................ Digital Signal Processor M.....................Machine
dt .................... Rate of Change mA ..................MilliAmpere
DTT ................ Direct Transfer Trip MAG................Magnitude
DUTT.............. Direct Under-reaching Transfer Trip MAN................Manual / Manually
MAX ................Maximum
ENCRMNT ..... Encroachment MIC .................Model Implementation Conformance
EPRI............... Electric Power Research Institute MIN .................Minimum, Minutes
.EVT ............... Filename extension for event recorder files MMI.................Man Machine Interface
EXT ................ Extension, External MMS ...............Manufacturing Message Specification
MRT ................Minimum Response Time
F ..................... Field MSG................Message
FAIL................ Failure MTA ................Maximum Torque Angle
FD .................. Fault Detector MTR ................Motor
FDH................ Fault Detector high-set MVA ................MegaVolt-Ampere (total 3-phase)
FDL ................ Fault Detector low-set MVA_A............MegaVolt-Ampere (phase A)
FLA................. Full Load Current MVA_B............MegaVolt-Ampere (phase B)
FO .................. Fiber Optic MVA_C............MegaVolt-Ampere (phase C)

GE Multilin G60 Generator Protection System F-9


APPENDIX F F.2 ABBREVIATIONS

MVAR ............. MegaVar (total 3-phase) SAT .................CT Saturation


MVAR_A......... MegaVar (phase A) SBO ................Select Before Operate
MVAR_B......... MegaVar (phase B) SCADA ...........Supervisory Control and Data Acquisition
MVAR_C ........ MegaVar (phase C) SEC ................Secondary
MVARH .......... MegaVar-Hour SEL .................Select / Selector / Selection
MW................. MegaWatt (total 3-phase) SENS ..............Sensitive
MW_A ............ MegaWatt (phase A) SEQ ................Sequence
MW_B ............ MegaWatt (phase B) SIR..................Source Impedance Ratio
MW_C ............ MegaWatt (phase C) SNTP ..............Simple Network Time Protocol
MWH .............. MegaWatt-Hour SRC ................Source
SSB.................Single Side Band
N..................... Neutral SSEL...............Session Selector
N/A, n/a .......... Not Applicable STATS.............Statistics
NEG ............... Negative SUPN..............Supervision
NMPLT ........... Nameplate SUPV ..............Supervise / Supervision
NOM............... Nominal SV ...................Supervision, Service
NSAP ............. Network Service Access Protocol SYNC..............Synchrocheck
NTR................ Neutral SYNCHCHK....Synchrocheck
O .................... Over T......................Time, transformer
OC, O/C ......... Overcurrent TC ...................Thermal Capacity
O/P, Op........... Output TCP.................Transmission Control Protocol
OP .................. Operate TCU ................Thermal Capacity Used
OPER ............. Operate TD MULT ........Time Dial Multiplier
OPERATG...... Operating TEMP..............Temperature
O/S ................. Operating System TFTP...............Trivial File Transfer Protocol
OSI ................. Open Systems Interconnect THD ................Total Harmonic Distortion
OSB................ Out-of-Step Blocking TMR ................Timer
OUT................ Output TOC ................Time Overcurrent
OV .................. Overvoltage TOV ................Time Overvoltage
OVERFREQ ... Overfrequency TRANS............Transient
OVLD ............. Overload TRANSF .........Transfer
TSEL...............Transport Selector
P..................... Phase TUC ................Time Undercurrent
PC .................. Phase Comparison, Personal Computer TUV.................Time Undervoltage
PCNT ............. Percent TX (Tx)............Transmit, Transmitter
PF................... Power Factor (total 3-phase)
PF_A .............. Power Factor (phase A) U .....................Under
PF_B .............. Power Factor (phase B) UC...................Undercurrent
PF_C .............. Power Factor (phase C) UCA ................Utility Communications Architecture
PFLL............... Phase and Frequency Lock Loop UDP ................User Datagram Protocol
PHS................ Phase UL ...................Underwriters Laboratories
PICS............... Protocol Implementation & Conformance UNBAL............Unbalance
Statement UR...................Universal Relay
PKP ................ Pickup
PLC ................ Power Line Carrier
URC ................Universal Recloser Control
.URS ...............Filename extension for settings files
F
POS................ Positive UV...................Undervoltage
POTT.............. Permissive Over-reaching Transfer Trip
PRESS ........... Pressure V/Hz ................Volts per Hertz
PRI ................. Primary V_0 .................Zero Sequence voltage
PROT ............. Protection V_1 .................Positive Sequence voltage
PSEL .............. Presentation Selector V_2 .................Negative Sequence voltage
pu ................... Per Unit VA ...................Phase A voltage
PUIB............... Pickup Current Block VAB.................Phase A to B voltage
PUIT ............... Pickup Current Trip VAG ................Phase A to Ground voltage
PUSHBTN ...... Pushbutton VARH ..............Var-hour voltage
PUTT.............. Permissive Under-reaching Transfer Trip VB ...................Phase B voltage
PWM .............. Pulse Width Modulated VBA.................Phase B to A voltage
PWR............... Power VBG ................Phase B to Ground voltage
VC...................Phase C voltage
QUAD............. Quadrilateral VCA ................Phase C to A voltage
VCG ................Phase C to Ground voltage
R..................... Rate, Reverse VF ...................Variable Frequency
RCA................ Reach Characteristic Angle VIBR ...............Vibration
REF ................ Reference VT ...................Voltage Transformer
REM ............... Remote VTFF...............Voltage Transformer Fuse Failure
REV................ Reverse VTLOS ............Voltage Transformer Loss Of Signal
RI.................... Reclose Initiate
RIP ................. Reclose In Progress WDG ...............Winding
RGT BLD........ Right Blinder WH..................Watt-hour
ROD ............... Remote Open Detector w/ opt ..............With Option
RST ................ Reset WRT................With Respect To
RSTR ............. Restrained
RTD................ Resistance Temperature Detector X .....................Reactance
RTU................ Remote Terminal Unit XDUCER.........Transducer
RX (Rx) .......... Receive, Receiver XFMR..............Transformer

s ..................... second Z......................Impedance, Zone


S..................... Sensitive

GE Multilin G60 Generator Protection System F-10


APPENDIX F F.3 WARRANTY

F.3WARRANTY F.3.1 GE MULTILIN WARRANTY

GE MULTILIN RELAY WARRANTY


General Electric Multilin Inc. (GE Multilin) warrants each relay it manufactures to be free from
defects in material and workmanship under normal use and service for a period of 24 months from
date of shipment from factory.

In the event of a failure covered by warranty, GE Multilin will undertake to repair or replace the relay
providing the warrantor determined that it is defective and it is returned with all transportation
charges prepaid to an authorized service centre or the factory. Repairs or replacement under war-
ranty will be made without charge.

Warranty shall not apply to any relay which has been subject to misuse, negligence, accident,
incorrect installation or use not in accordance with instructions nor any unit that has been altered
outside a GE Multilin authorized factory outlet.

GE Multilin is not liable for special, indirect or consequential damages or for loss of profit or for
F
expenses sustained as a result of a relay malfunction, incorrect application or adjustment.

For complete text of Warranty (including limitations and disclaimers), refer to GE Multilin Standard
Conditions of Sale.

GE Multilin G60 Generator Protection System F-11


F.3 WARRANTY APPENDIX F

F-12 G60 Generator Protection System GE Multilin


Index

INDEX

BLOCK SETTING ............................................................... 5-5


Numerics BREAKER CONTROL
control of 2 breakers ...................................................... 4-24
100% STATOR GROUND description ..................................................................... 4-23
see also entry for STATOR GROUND dual breaker logic ................................................. 5-77, 5-78
FlexLogic™ operands .................................................. 5-107 FlexLogic™ operands ................................................... 5-108
logic ............................................................................ 5-204 Modbus registers .......................................................... B-22
Modbus registers ........................................................... B-32 settings ......................................................................... 5-75
settings ....................................................................... 5-202 BREAKER-AND-A-HALF SCHEME ...................................... 5-6
specifications ................................................................ 2-12 BRIGHTNESS .................................................................. 5-12
10BASE-F
communications options ................................................. 3-24
description .................................................................... 3-27
interface ........................................................................ 3-37 C
redundant option ........................................................... 3-24 C37.94 COMMUNICATIONS ........................... 3-38, 3-39, 3-41
settings ......................................................................... 5-17 C37.94SM COMMUNICATIONS ........................................ 3-40
CE APPROVALS .............................................................. 2-25
CHANGES TO MANUAL ............................... F-5, F-6, F-7, F-8
A CHANNEL COMMUNICATION .......................................... 3-31
CHANNEL TESTS ............................................................ 6-10
ABBREVIATIONS ............................................................... F-9 CHANNELS
AC CURRENT INPUTS ................................... 2-17, 3-13, 5-70 banks ................................................................... 5-70, 5-71
AC VOLTAGE INPUTS .............................................2-17, 3-14 CIRCUIT MONITORING APPLICATIONS ......................... 5-236
ACCIDENTAL ENERGIZATION CLEANING ....................................................................... 2-25
FlexLogic™ operands .................................................. 5-107 CLEAR RECORDS .................................................... 5-14, 7-2
logic ............................................................................ 5-197 CLEAR RELAY RECORDS
Modbus registers ........................................................... B-30 Modbus registers .......................................................... B-58
settings ....................................................................... 5-196 settings ......................................................................... 5-14
specifications ................................................................ 2-13 CLOCK
ACTIVATING THE RELAY ........................................1-17, 4-27 setting date and time ........................................................ 7-2
ACTIVE SETTING GROUP ............................................. 5-128 settings ......................................................................... 5-40
ACTUAL VALUES COMMANDS MENU ............................................................ 7-1
metering ........................................................................ 6-11 COMMUNICATIONS
product information ........................................................ 6-28 10BASE-F ................................................... 3-24, 3-27, 5-17
status .............................................................................. 6-4 channel ......................................................................... 3-31
ALARM LEDs ................................................................... 5-48 connecting to the UR ............................................... 1-8, 1-15
ANSI DEVICE NUMBERS ................................................... 2-1 CRC-16 error checking .................................................... B-2
APPARENT POWER ................................................2-16, 6-17 dnp .........................................................................5-18, E-1
APPLICATION EXAMPLES EGD .............................................................................. 5-37
breaker trip circuit integrity .......................................... 5-238 G.703 ............................................................................ 3-33
contact inputs .............................................................. 5-247 half duplex ...................................................................... B-1
sensitive directional power ........................................... 5-199 HTTP ............................................................................. 5-35
APPROVALS ................................................................... 2-25 IEC 60870-5-104 protocol............................................... 5-36
ARCHITECTURE ........................................................... 5-105 IEC 61850 ................................................................... 5-252
AUXILIARY OVERVOLTAGE inter-relay communications ............................................. 2-23
FlexLogic™ operands .................................................. 5-107 Modbus .................................................. 5-17, 5-39, B-1, B-3
logic ............................................................................ 5-190 Modbus registers .......................................................... B-18
Modbus registers ........................................................... B-39 network ......................................................................... 5-17
settings ....................................................................... 5-190 overview ........................................................................ 1-16
specifications ................................................................ 2-12 RS232 ........................................................................... 3-24
AUXILIARY UNDERVOLTAGE RS485 ......................................................... 3-24, 3-26, 5-16
FlexLogic™ operands .................................................. 5-107 settings ............................. 5-17, 5-18, 5-23, 5-36, 5-37, 5-39
logic ............................................................................ 5-189 specifications ........................................................ 2-22, 2-23
Modbus registers ........................................................... B-39 UCA/MMS .................................................................... 5-254
settings ....................................................................... 5-189 web server ..................................................................... 5-35
specifications ................................................................ 2-11 COMTRADE ............................................................... B-6, B-7
AUXILIARY VOLTAGE CHANNEL ..................................... 3-14 CONDUCTED RFI ............................................................ 2-24
AUXILIARY VOLTAGE METERING ................................... 6-16 CONTACT INFORMATION .................................................. 1-1
CONTACT INPUTS
actual values ................................................................... 6-4
dry connections ............................................................. 3-21
B FlexLogic™ operands ................................................... 5-114
Modbus registers ............................... B-10, B-15, B-51, B-53
BANKS ............................................................. 5-6, 5-70, 5-71
settings ....................................................................... 5-246
BATTERY FAILURE ........................................................... 7-8
specifications ................................................................. 2-17
BINARY INPUT POINTS ..................................................... E-8
thresholds ................................................................... 5-246
BINARY OUTPUT POINTS ................................................. E-9
wet connections ............................................................. 3-21
BLOCK DIAGRAM .............................................................. 1-3

GE Multilin G60 Generator Protection System i


INDEX

CONTACT OUTPUTS DIFFERENTIAL


actual values ................................................................... 6-5 stator ......................................................... 2-10, 5-145, 6-14
FlexLogic™ operands .................................................. 5-114 DIGITAL COUNTERS
Modbus registers .........................................B-10, B-15, B-57 actual values ................................................................... 6-7
settings ....................................................................... 5-249 FlexLogic™ operands ................................................... 5-108
CONTROL ELEMENTS ................................................... 5-216 logic ............................................................................ 5-240
CONTROL POWER Modbus registers .................................................... B-9, B-46
description..................................................................... 3-13 settings ........................................................................ 5-239
specifications ................................................................. 2-19 DIGITAL ELEMENTS
CONTROL PUSHBUTTONS application example ...................................................... 5-237
FlexLogic™ operands .................................................. 5-107 FlexLogic™ operands ................................................... 5-108
Modbus registers ...........................................................B-58 logic ............................................................................ 5-236
settings ......................................................................... 5-49 Modbus registers ........................................................... B-41
specifications ................................................................. 2-15 settings ........................................................................ 5-236
COUNTERS DIGITAL OUTPUTS
actual values ................................................................... 6-7 see entry for CONTACT OUTPUTS
settings ....................................................................... 5-239 DIMENSIONS ............................................................. 3-1, 3-2
CRC ALARM .................................................................... 5-65 DIRECT DEVICES
CRC-16 ALGORITHM ........................................................ B-2 actual values ................................................................... 6-8
CRITICAL FAILURE RELAY ..................................... 2-19, 3-12 Modbus registers ........................................................... B-17
CSA APPROVAL .............................................................. 2-25 settings ........................................................................ 5-256
CT BANKS DIRECT I/O
settings ......................................................................... 5-70 see also DIRECT INPUTS and DIRECT OUTPUTS
CT INPUTS ...................................................... 3-14, 5-6, 5-70 application example ........................................... 5-257, 5-258
CT WIRING ...................................................................... 3-14 configuration examples ........................ 5-59, 5-62, 5-65, 5-66
CURRENT BANK ............................................................. 5-70 settings ..............................................5-59, 5-65, 5-66, 5-256
CURRENT HARMONICS ......................................... 2-16, 6-19 DIRECT INPUTS
CURRENT METERING actual values ................................................................... 6-8
actual values ................................................................. 6-15 application example ........................................... 5-257, 5-258
Modbus registers ...........................................................B-11 clearing counters ............................................................. 7-2
specifications ................................................................. 2-16 FlexLogic™ operands ................................................... 5-114
CURVES Modbus registers ....................... B-10, B-17, B-43, B-58, B-60
definite time.......................................................5-152, 5-184 settings ........................................................................ 5-256
FlexCurves™ ...................................................... 5-82, 5-152 specifications .................................................................2-17
I2T .............................................................................. 5-152 DIRECT INPUTS/OUTPUTS
IAC ............................................................................. 5-151 error messages ............................................................... 7-8
IEC ............................................................................. 5-150 DIRECT OUTPUTS
IEEE ........................................................................... 5-149 application example ........................................... 5-257, 5-258
inverse time undervoltage ............................................ 5-184 clearing counters ............................................................. 7-2
types ........................................................................... 5-148 Modbus registers ....................... B-10, B-43, B-58, B-59, B-60
settings ........................................................................ 5-256
DIRECTIONAL OVERCURRENT
see PHASE, GROUND, and NEUTRAL DIRECTIONAL entries
D DIRECTIONAL POLARIZATION ...................................... 5-158
DIRECTIONAL POWER
DATA FORMATS, MODBUS .............................................B-66
see entry for SENSITIVE DIRECTIONAL POWER
DATA LOGGER
DISCONNECT SWITCH
clearing .................................................................. 5-14, 7-2
FlexLogic™ operands ................................................... 5-113
Modbus .......................................................................... B-7
logic ..............................................................................5-81
Modbus registers ..................................................B-10, B-20
Modbus registers ........................................................... B-35
settings ......................................................................... 5-44
settings ..........................................................................5-79
specifications ................................................................. 2-15
DISPLAY ........................................................ 1-16, 4-23, 5-12
via COMTRADE .............................................................. B-6
DISTANCE
DATE ................................................................................. 7-2
mho characteristic ............................................. 5-131, 5-132
DCMA INPUTS ................................................................. 6-25
Modbus registers ........................................................... B-33
Modbus registers ..................................................B-16, B-34
phase ................................................................. 2-10, 5-130
settings ....................................................................... 5-263
settings ........................................................................ 5-129
specifications ................................................................. 2-17
DISTURBANCE DETECTOR
DCMA OUTPUTS
internal ..........................................................................5-73
description..................................................................... 3-23
Modbus registers ........................................................... B-28
Modbus registers ...........................................................B-43
DNA-1 BIT PAIR ............................................................. 5-254
settings ....................................................................... 5-270
DNP COMMUNICATIONS
specifications ................................................................. 2-19
binary counters ............................................................. E-10
DEFINITE TIME CURVE .......................................5-152, 5-184
binary input points ........................................................... E-8
DESIGN ............................................................................. 1-3
binary output points ......................................................... E-9
DEVICE ID ..................................................................... 5-252
control relay output blocks ............................................... E-9
DEVICE PROFILE DOCUMENT ......................................... E-1
device profile document ................................................... E-1
DIELECTRIC STRENGTH ................................................. 3-12
frozen counters ............................................................. E-10

ii G60 Generator Protection System GE Multilin


INDEX

implementation table ....................................................... E-4


Modbus registers ........................................................... B-18 F
settings ......................................................................... 5-18
DUPLEX, HALF .................................................................. B-1 F485 ................................................................................ 1-16
FACEPLATE ............................................................... 3-1, 3-2
FACEPLATE PANELS ............................................. 4-13, 4-23
FAST FORM-C RELAY ..................................................... 2-19
E FAST TRANSIENT TESTING ............................................ 2-24
EGD PROTOCOL FAX NUMBERS .................................................................. 1-1
actual values .......................................................... 6-9, 6-27 FEATURES ........................................................................ 2-1
Modbus registers .................................................. B-39, B-40 FIELD GROUND FAULT
settings ......................................................................... 5-37 Modbus registers ................................................. B-37, B-38
ELECTROSTATIC DISCHARGE ....................................... 2-24 settings ............................................................ 5-212, 5-214
ELEMENTS ....................................................................... 5-4 specifications ................................................................. 2-12
ENERGY METERING FIELD GROUND FAULT DETECTOR
actual values ................................................................. 6-18 FlexLogic™ operands ................................................... 5-108
Modbus registers ........................................................... B-13 FIRMWARE REVISION ..................................................... 6-28
specifications ................................................................ 2-16 FIRMWARE UPGRADES .................................................... 4-2
ENERGY METERING, CLEARING ............................. 5-14, 7-2 FLASH MESSAGES .......................................................... 5-12
ENERVISTA UR SETUP FLEX STATE PARAMETERS
creating a site list ............................................................ 4-1 actual values .......................................................... 6-7, 6-20
event recorder ................................................................. 4-2 Modbus registers ................................................. B-15, B-41
firmware upgrades ........................................................... 4-2 settings ......................................................................... 5-56
installation ...................................................................... 1-5 specifications ................................................................. 2-14
introduction ..................................................................... 4-1 FLEXCURVES™
oscillography ................................................................... 4-2 equation ...................................................................... 5-152
overview ......................................................................... 4-1 Modbus registers ................................................. B-23, B-46
requirements ................................................................... 1-5 settings ......................................................................... 5-82
EQUATIONS specifications ................................................................. 2-14
definite time curve ............................................. 5-152, 5-184 table .............................................................................. 5-82
FlexCurve™ ................................................................ 5-152 FLEXELEMENTS™
I²t curves ..................................................................... 5-152 actual values ................................................................. 6-21
IAC curves .................................................................. 5-151 direction ...................................................................... 5-125
IEC curves .................................................................. 5-150 FlexLogic™ operands ................................................... 5-109
IEEE curves ................................................................ 5-149 hysteresis .................................................................... 5-125
EQUIPMENT MISMATCH ERROR ...................................... 7-7 Modbus registers ................................................. B-42, B-44
ETHERNET pickup ......................................................................... 5-125
actual values ................................................................... 6-7 scheme logic ............................................................... 5-124
configuration ................................................................... 1-8 settings .................................................. 5-123, 5-124, 5-127
error messages ............................................................... 7-9 specifications ................................................................. 2-14
Modbus registers ........................................................... B-10 FLEXLOGIC
quick connect ................................................................ 1-10 locking to a serial number ....................................... 4-9, 8-11
settings ......................................................................... 5-17 FLEXLOGIC™
ETHERNET SWITCH editing with EnerVista UR Setup ....................................... 4-2
actual values ................................................................. 6-10 equation editor ............................................................. 5-122
configuration .........................................................3-68, 3-69 error messages ................................................................ 7-7
hardware ....................................................................... 3-63 evaluation .................................................................... 5-117
Modbus registers .................................................. B-19, B-20 example ........................................................... 5-105, 5-117
overview ....................................................................... 3-63 example equation ......................................................... 5-218
saving setting files ......................................................... 3-69 gate characteristics ...................................................... 5-116
settings ......................................................................... 5-39 locking equation entries .......................................... 4-8, 8-10
uploading setting files .................................................... 3-70 Modbus registers .......................................................... B-24
EVENT CAUSE INDICATORS ...................................4-15, 4-16 operands .......................................................... 5-106, 5-107
EVENT RECORDER operators ..................................................................... 5-116
actual values ................................................................. 6-26 rules ............................................................................ 5-116
clearing .................................................................. 5-14, 7-2 security .................................................................. 4-8, 8-10
Modbus ........................................................................... B-7 specifications ................................................................. 2-14
Modbus registers ........................................................... B-16 timers .......................................................................... 5-122
specifications ................................................................ 2-15 worksheet .................................................................... 5-118
via EnerVista software ..................................................... 4-2 FLEXLOGIC™ EQUATION EDITOR ................................ 5-122
EVENTS SETTING ............................................................. 5-5 FLEXLOGIC™ TIMERS
EXCEPTION RESPONSES ................................................. B-5 Modbus registers .......................................................... B-25
EXCITATION, LOSS OF settings ....................................................................... 5-122
see entry for LOSS OF EXCITATION FORCE CONTACT INPUTS ............................................ 5-275
FORCE CONTACT OUTPUTS ......................................... 5-276
FORCE TRIGGER ............................................................ 6-26
FORM-A RELAY
high impedance circuits .................................................. 3-16

GE Multilin G60 Generator Protection System iii


INDEX

outputs .........................................................3-15, 3-16, 3-21


specifications ................................................................. 2-19 I
FORM-C RELAY
outputs ................................................................. 3-15, 3-21 I2T CURVES .................................................................. 5-152
specifications ................................................................. 2-19 IAC CURVES .................................................................. 5-151
FREQUENCY METERING IEC 60870-5-104 PROTOCOL
actual values ................................................................. 6-18 interoperability document ................................................. D-1
Modbus registers ...........................................................B-13 Modbus registers ........................................................... B-19
settings ......................................................................... 5-72 settings ..........................................................................5-36
specifications ................................................................. 2-16 IEC 61850 GOOSE ANALOGS
FREQUENCY OUT-OF-BAND ACCUMULATION settings ........................................................................ 5-261
actual values ................................................................. 6-20 IEC 61850 GOOSE UINTEGERS
clearing ........................................................................... 7-2 settings ........................................................................ 5-262
FlexLogic™ operands .................................................. 5-109 IEC 61850 PROTOCOL
Modbus registers ...........................................................B-17 device ID ..................................................................... 5-253
settings .............................................................5-229, 5-230 DNA2 assignments ....................................................... 5-255
specifications ................................................................. 2-13 error messages ............................................................... 7-9
FREQUENCY RATE OF CHANGE Modbus registers .............. B-47, B-48, B-49, B-50, B-51, B-63
FlexLogic™ operands .................................................. 5-109 remote device settings .................................................. 5-252
Modbus registers ..................................................B-11, B-47 remote inputs ............................................................... 5-253
settings ....................................................................... 5-227 settings ..........................................................................5-22
FREQUENCY TRACKING ........................................ 5-72, 6-20 UserSt-1 bit pair ........................................................... 5-255
FREQUENCY, NOMINAL .................................................. 5-72 IEC CURVES .................................................................. 5-150
FUNCTION SETTING ......................................................... 5-5 IED ................................................................................... 1-2
FUSE ............................................................................... 2-18 IED SETUP ....................................................................... 1-5
FUSE FAILURE IEEE C37.94 COMMUNICATIONS ................... 3-38, 3-39, 3-41
see VT FUSE FAILURE IEEE CURVES ................................................................ 5-149
IMPORTANT CONCEPTS .................................................. 1-4
IN SERVICE INDICATOR ...........................................1-17, 7-6
INCOMPATIBLE HARDWARE ERROR ................................ 7-7
G INPUTS
G.703 .................................................... 3-32, 3-33, 3-34, 3-37 AC current ............................................................ 2-17, 5-70
GE TYPE IAC CURVES .................................................. 5-151 AC voltage ............................................................ 2-17, 5-71
GENERATOR UNBALANCE contact inputs .......................................... 2-17, 5-246, 5-275
FlexLogic™ operands .................................................. 5-109 dcmA inputs .......................................................... 2-17, 3-23
logic ............................................................................ 5-178 direct inputs ...................................................................2-17
Modbus registers ...........................................................B-31 IRIG-B .................................................................. 2-17, 3-28
settings ....................................................................... 5-177 remote inputs ................................. 2-17, 5-252, 5-253, 5-254
specifications ................................................................. 2-11 RTD inputs ............................................................ 2-17, 3-23
GPM-F FAILURE ERROR ................................................. 7-10 virtual .......................................................................... 5-248
GROUND CURRENT METERING ...................................... 6-15 INSPECTION CHECKLIST ................................................. 1-1
GROUND IOC INSTALLATION
FlexLogic™ operands .................................................. 5-109 communications .............................................................3-25
logic ............................................................................ 5-168 CT inputs .............................................................. 3-13, 3-14
Modbus registers ...........................................................B-28 RS485 ...........................................................................3-26
settings ....................................................................... 5-168 settings ..........................................................................5-67
GROUND TIME OVERCURRENT INSTANTANEOUS OVERCURRENT
see entry for GROUND TOC see PHASE, GROUND, and NEUTRAL IOC entries
GROUND TOC INTELLIGENT ELECTRONIC DEVICE ................................ 1-2
FlexLogic™ operands .................................................. 5-109 INTER-RELAY COMMUNICATIONS ..................................2-23
logic ............................................................................ 5-167 INTRODUCTION ................................................................ 1-2
Modbus registers ...........................................................B-27 INVERSE TIME UNDERVOLTAGE .................................. 5-184
settings ....................................................................... 5-167 IOC
specifications ................................................................. 2-10 see PHASE, GROUND, and NEUTRAL IOC entries
GROUPED ELEMENTS .................................................. 5-128 IP ADDRESS ....................................................................5-17
GSSE ................................................ 5-253, 5-254, 5-255, 6-6 IRIG-B
connection .....................................................................3-28
error messages ............................................................... 7-9
settings ..........................................................................5-40
H specifications ........................................................ 2-17, 2-19
ISO-9000 REGISTRATION ................................................2-25
HALF-DUPLEX .................................................................. B-1
HARMONIC CONTENT ..................................................... 6-18
HARMONICS
actual values ................................................................. 6-18 K
HARMONICS METERING
specifications ................................................................. 2-16 KEYPAD .................................................................. 1-17, 4-23
HTTP PROTOCOL ........................................................... 5-35

iv G60 Generator Protection System GE Multilin


INDEX

MODEL INFORMATION .................................................... 6-28


L MODIFICATION FILE NUMBER ........................................ 6-28
MODULE FAILURE ERROR ................................................ 7-7
LAMPTEST ........................................................................ 7-3 MODULES
LANGUAGE ..................................................................... 5-12 communications ............................................................. 3-25
LASER MODULE ............................................................. 3-31 CT ................................................................................. 3-14
LATCHING OUTPUTS CT/VT ..................................................................... 3-13, 5-6
application example ........................................... 5-250, 5-251 direct inputs/outputs ....................................................... 3-31
error messages ............................................................... 7-9 insertion ................................................................... 3-6, 3-7
settings ....................................................................... 5-249 order codes ..................................................................... 2-7
specifications ................................................................ 2-19 power supply ................................................................. 3-12
LED INDICATORS ........................ 4-14, 4-15, 4-16, 4-22, 5-48 transducer I/O ................................................................ 3-23
LED TEST VT ................................................................................. 3-14
FlexLogic™ operand .................................................... 5-114 withdrawal ................................................................ 3-6, 3-7
settings ......................................................................... 5-46 MONITORING ELEMENTS .............................................. 5-241
specifications ................................................................ 2-15 MOUNTING ................................................................. 3-1, 3-2
LINK POWER BUDGET .................................................... 2-23
LOGIC GATES ............................................................... 5-116
LOSS OF EXCITATION
characteristics ............................................................. 5-195 N
FlexLogic™ operands .................................................. 5-109 NAMEPLATE ...................................................................... 1-1
logic ............................................................................ 5-196 NEGATIVE SEQUENCE DIRECTIONAL OC
Modbus registers ........................................................... B-31 Modbus registers .......................................................... B-34
settings ............................................................. 5-194, 5-195 NEGATIVE SEQUENCE DIRECTIONAL OVERCURRENT
specifications ................................................................ 2-14 characteristics ............................................................. 5-175
LOST PASSWORD ...................................... 5-9, 5-10, 8-2, 8-3 FlexLogic™ operands ................................................... 5-109
logic ............................................................................ 5-176
settings ............................................................ 5-173, 5-176
M specifications ................................................................. 2-11
NEGATIVE SEQUENCE OVERVOLTAGE
MAINTENANCE COMMANDS ............................................. 7-3 FlexLogic™ operands ................................................... 5-109
MANUFACTURING DATE ................................................. 6-28 logic ............................................................................ 5-188
MEMORY MAP DATA FORMATS ...................................... B-66 Modbus registers .......................................................... B-29
MEMORY VOLTAGE LOGIC ........................................... 5-130 settings ....................................................................... 5-188
MENU HEIRARCHY .................................................1-17, 4-25 specifications ................................................................. 2-12
MENU NAVIGATION ....................................... 1-17, 4-24, 4-25 NEUTRAL DIRECTIONAL OC
METERING Modbus registers .......................................................... B-33
conventions ...........................................................6-11, 6-12 NEUTRAL DIRECTIONAL OVERCURRENT
current .......................................................................... 2-16 FlexLogic™ operands ................................................... 5-109
frequency ...................................................................... 2-16 logic ............................................................................ 5-166
harmonics ..................................................................... 2-16 polarization .................................................................. 5-164
power ............................................................................ 2-16 settings ....................................................................... 5-162
THD .............................................................................. 2-16 specifications ................................................................. 2-11
voltage .......................................................................... 2-16 NEUTRAL INSTANTANEOUS OVERCURRENT
METERING CONVENTIONS ............................................. 6-12 see entry for NEUTRAL IOC
MHO DISTANCE CHARACTERISTIC .............................. 5-131 NEUTRAL IOC
MODBUS FlexLogic™ operands ................................................... 5-109
data logger ...............................................................B-6, B-7 logic ............................................................................ 5-161
event recorder ................................................................. B-7 Modbus registers .......................................................... B-27
exception responses ........................................................ B-5 settings ....................................................................... 5-161
execute operation ............................................................ B-4 specifications ................................................................. 2-10
flex state parameters ..................................................... 5-57 NEUTRAL OVERVOLTAGE
function code 03/04h ....................................................... B-3 FlexLogic™ operands ................................................... 5-109
function code 05h ............................................................ B-4 logic ............................................................................ 5-187
function code 06h ............................................................ B-4 Modbus registers .......................................................... B-39
function code 10h ............................................................ B-5 settings ....................................................................... 5-187
introduction ..................................................................... B-1 specifications ................................................................. 2-12
memory map data formats .............................................. B-66 NEUTRAL TIME OVERCURRENT
obtaining files .................................................................. B-6 see entry for NEUTRAL TOC
oscillography ................................................................... B-6 NEUTRAL TOC
passwords ....................................................................... B-7 FlexLogic™ operands ................................................... 5-109
read/write settings/actual values ...................................... B-3 logic ............................................................................ 5-160
settings .................................................................5-17, 5-39 Modbus registers .......................................................... B-27
store multiple settings ...................................................... B-5 settings ....................................................................... 5-160
store single setting .......................................................... B-4 specifications ................................................................. 2-10
supported function codes ................................................. B-3 NON-VOLATILE LATCHES
user map ..................................................... 5-39, B-10, B-23 FlexLogic™ operands ................................................... 5-109

GE Multilin G60 Generator Protection System v


INDEX

Modbus registers ...........................................................B-46 PASSWORDS


settings ....................................................................... 5-127 changing ........................................................................4-28
specifications ................................................................. 2-14 for settings templates ............................................... 4-5, 8-7
NSAP ADDRESS .............................................................. 5-17 lost password ................................... 4-28, 5-9, 5-10, 8-2, 8-3
Modbus ........................................................................... B-7
Modbus registers .................................................. B-13, B-18
overview ........................................................................1-18
O security .................................................................... 5-8, 8-1
settings .................................................................... 5-8, 8-1
ONE SHOTS .................................................................. 5-116
PC SOFTWARE
OPERATING TEMPERATURE .......................................... 2-23
see entry for ENERVISTA UR SETUP
OPERATING TIMES ......................................................... 2-10
PERMISSIVE FUNCTIONS .............................................. 5-183
ORDER CODES ............................. 2-4, 2-5, 2-6, 2-7, 6-28, 7-3
PER-UNIT QUANTITY ........................................................ 5-4
ORDER CODES, UPDATING .............................................. 7-3
PHASE ANGLE METERING ..............................................6-12
ORDERING ............................................ 2-3, 2-4, 2-5, 2-6, 2-7
PHASE CURRENT METERING .........................................6-15
OSCILLATORY TRANSIENT TESTING ............................. 2-24
PHASE DIRECTIONAL OC
OSCILLOGRAPHY
Modbus registers ........................................................... B-33
actual values ................................................................. 6-26
PHASE DIRECTIONAL OVERCURRENT
clearing .................................................................. 5-14, 7-2
FlexLogic™ operands ................................................... 5-110
Modbus .......................................................................... B-6
logic ............................................................................ 5-159
Modbus registers ..................................................B-15, B-20
phase A polarization ..................................................... 5-157
settings ......................................................................... 5-42
settings ............................................................. 5-157, 5-158
specifications ................................................................. 2-15
specifications .................................................................2-11
via COMTRADE .............................................................. B-6
PHASE DISTANCE
via EnerVista software ..................................................... 4-2
FlexLogic™ operands ................................................... 5-110
OSI NETWORK ADDRESS ............................................... 5-17
logic ............................................................................ 5-136
OST ...................................................................... 2-13, 5-139
Modbus registers ........................................................... B-33
OUT-OF-STEP TRIPPING ..................................... 2-13, 5-139
op scheme ...................................................................5-134
OUTPUTS
settings ........................................................................ 5-130
contact outputs ............................................................ 5-249
specifications .................................................................2-10
control power ................................................................. 2-19
PHASE INSTANTANEOUS OVERCURRENT
critical failure relay ........................................................ 2-19
see entry for PHASE IOC
Fast Form-C relay .......................................................... 2-19
PHASE IOC
Form-A relay ....................................... 2-19, 3-15, 3-16, 3-21
FlexLogic™ operands ................................................... 5-110
Form-C relay ................................................2-19, 3-15, 3-21
logic ............................................................................ 5-156
IRIG-B ........................................................................... 2-19
Modbus registers ........................................................... B-26
latching outputs .................................................. 2-19, 5-249
specifications .................................................................2-10
remote outputs ..................................................5-254, 5-255
PHASE MEASUREMENT UNIT
virtual outputs .............................................................. 5-251
OVERCURRENT CURVE TYPES .................................... 5-148
see entry for SYNCHROPHASOR
PHASE OVERVOLTAGE
OVERCURRENT CURVES
FlexLogic™ operands ................................................... 5-110
definite time................................................................. 5-152
logic ............................................................................ 5-186
FlexCurves™ ............................................................... 5-152
Modbus registers ........................................................... B-33
I2T .............................................................................. 5-152
settings ........................................................................ 5-186
IAC ............................................................................. 5-151
specifications .................................................................2-12
IEC ............................................................................. 5-150
PHASE ROTATION ...........................................................5-72
IEEE ........................................................................... 5-149
PHASE TIME OVERCURRENT
OVERFREQUENCY
see entry for PHASE TOC
FlexLogic™ operands .................................................. 5-110
PHASE TOC
logic ............................................................................ 5-226
FlexLogic™ operands ................................................... 5-110
settings ....................................................................... 5-226
logic ............................................................................ 5-154
specifications ................................................................. 2-13
Modbus registers ........................................................... B-26
OVERFRQUENCY
settings ........................................................................ 5-153
Modbus registers ...........................................................B-30
specifications .................................................................2-10
OVERVOLTAGE
PHASE UNDERVOLTAGE
auxiliary ............................................................. 2-12, 5-190
FlexLogic™ operands ................................................... 5-111
negative sequence ....................................................... 5-188
logic ............................................................................ 5-185
negative-sequence ......................................................... 2-12
Modbus registers ........................................................... B-32
neutral ................................................................ 2-12, 5-187
settings ........................................................................ 5-185
phase ................................................................. 2-12, 5-186
specifications .................................................................2-11
PHASOR MEASUREMENT UNIT
actual values ..................................................................6-27
P PHONE NUMBERS ............................................................ 1-1
PMU
PANEL CUTOUT ......................................................... 3-1, 3-2 see entry for SYNCHROPHASOR
PARITY ........................................................................... 5-16 POWER METERING
PASSWORD SECURITY .............................. 5-9, 5-10, 8-2, 8-3 Modbus registers ........................................................... B-12
FlexLogic operands ...................................................... 5-115 specifications .................................................................2-16

vi G60 Generator Protection System GE Multilin


INDEX

values ........................................................................... 6-17 REPLACEMENT MODULES .................................. 2-7, 2-8, 2-9


POWER SUPPLY RESETTING ........................................................ 5-115, 5-255
description .................................................................... 3-12 RESTRICTED GROUND FAULT
low range ...................................................................... 2-18 actual values ................................................................. 6-23
specifications ................................................................ 2-18 FlexLogic™ operands ................................................... 5-111
POWER SWING BLOCKING ................................... 2-13, 5-138 Modbus registers ................................................. B-11, B-47
POWER SWING DETECT settings ....................................................................... 5-169
FlexLogic™ operands .................................................. 5-111 specifications ................................................................. 2-10
logic .................................................................. 5-143, 5-144 REVISION HISTORY ..........................................................F-1
Modbus registers ........................................................... B-30 RF IMMUNITY .................................................................. 2-24
settings ............................................................. 5-137, 5-141 RFI, CONDUCTED ........................................................... 2-24
specifications ................................................................ 2-13 RMS CURRENT ............................................................... 2-16
POWER SYSTEM RMS VOLTAGE ................................................................ 2-16
Modbus registers ........................................................... B-22 RRTD INPUTS
PREFERENCES settings ....................................................................... 5-266
Modbus registers ........................................................... B-18 RS232
PROCESS BUS configuration .................................................................... 1-9
overview ....................................................................... 3-15 specifications ................................................................. 2-22
PRODUCT INFORMATION ........................................ 6-28, B-8 wiring ............................................................................ 3-24
PRODUCT SETUP ...................................................... 5-8, 8-2 RS422
PRODUCTION TESTS ..................................................... 2-24 configuration .................................................................. 3-35
PROTECTION ELEMENTS ................................................. 5-4 timing ............................................................................ 3-36
PU QUANTITY ................................................................... 5-4 two-channel application .................................................. 3-35
PUSHBUTTONS, USER-PROGRAMMABLE with fiber interface ......................................................... 3-37
see USER-PROGRAMMBLE PUSHBUTTONS RS485
communications ............................................................. 3-24
configuration .................................................................... 1-7
description ..................................................................... 3-26
R specifications ................................................................. 2-22
RTD INPUTS
REACTIVE POWER .................................................2-16, 6-17
actual values ................................................................. 6-25
REAL POWER .........................................................2-16, 6-17
Modbus registers ................................................. B-16, B-24
REAL TIME CLOCK
settings ............................................................ 5-264, 5-267
Modbus registers ........................................................... B-20
specifications ................................................................. 2-17
settings ......................................................................... 5-40
RTD PROTECTION
REAR TERMINAL ASSIGNMENTS ..................................... 3-8
FlexLogic™ operands ................................................... 5-111
RECLOSER CURVES ............................................ 5-85, 5-152
specifications ................................................................. 2-14
REDUNDANT 10BASE-F .................................................. 3-24
RELAY ACTIVATION ....................................................... 4-27
RELAY ARCHITECTURE ................................................ 5-105
RELAY MAINTENANCE ..................................................... 7-3 S
RELAY NAME .................................................................. 5-68
RELAY NOT PROGRAMMED ........................................... 1-17 SALES OFFICE .................................................................. 1-1
REMOTE DEVICES SCAN OPERATION ............................................................ 1-4
actual values ................................................................... 6-6 SELECTOR SWITCH
device ID ..................................................................... 5-253 actual values ................................................................... 6-7
error messages ............................................................. 7-10 application example ..................................................... 5-223
FlexLogic™ operands .................................................. 5-115 FlexLogic™ operands ................................................... 5-112
Modbus registers ................................ B-10, B-15, B-60, B-64 logic ............................................................................ 5-224
settings ....................................................................... 5-252 Modbus registers .......................................................... B-45
statistics ......................................................................... 6-6 settings ....................................................................... 5-219
REMOTE DPS INPUTS specifications ................................................................. 2-15
actual values ................................................................... 6-5 timing ............................................................... 5-222, 5-223
settings ....................................................................... 5-254 SELF-TESTS
REMOTE INPUTS description ....................................................................... 7-6
actual values ................................................................... 6-4 error messages ................................................................ 7-8
FlexLogic™ operands .................................................. 5-114 FlexLogic™ operands ................................................... 5-115
Modbus registers ......................................... B-10, B-15, B-61 Modbus registers ............................................................ B-8
settings ....................................................................... 5-253 SENSITIVE DIRECTIONAL POWER
specifications ................................................................ 2-17 actual values ................................................................. 6-22
REMOTE OUTPUTS FlexLogic™ operands ................................................... 5-108
DNA-1 bit pair ............................................................. 5-254 logic ............................................................................ 5-200
Modbus registers .................................................. B-61, B-62 Modbus registers ................................................. B-11, B-31
UserSt-1 bit pair .......................................................... 5-255 settings ............................................................ 5-198, 5-200
REMOTE RTD INPUTS specifications ................................................................. 2-11
Modbus registers ........................................................... B-40 SENSTIVE DIRECTIONAL POWER
REMOTE RTD PROTECTION characteristic ............................................................... 5-199
FlexLogic™ operands .................................................. 5-111 SERIAL NUMBER ............................................................. 6-28

GE Multilin G60 Generator Protection System vii


INDEX

SERIAL PORTS SYMMETRICAL COMPONENTS METERING .....................6-12


Modbus registers ...........................................................B-18 SYNCHROCHECK
settings ......................................................................... 5-16 actual values .................................................. 6-9, 6-19, 6-22
SETTING GROUPS .......................... 5-112, 5-128, 5-218, B-29 FlexLogic™ operands ................................................... 5-113
SETTINGS TEMPLATES logic ............................................................................ 5-234
description................................................................ 4-4, 8-6 Modbus registers .................................................. B-13, B-23
editing ...................................................................... 4-4, 8-6 settings ............................................................. 5-231, 5-232
enabling ................................................................... 4-4, 8-6 specifications .................................................................2-13
Modbus registers ...........................................................B-65 SYNCHROPHASORS
password protection .................................................. 4-5, 8-7 actual values ..................................................................6-24
removing .................................................................. 4-7, 8-9 commands ...................................................................... 7-4
viewing ..................................................................... 4-6, 8-8 FlexLogic™ operands ........................................ 5-110, 5-111
SETTINGS, CHANGING ................................................... 4-26 network connection ...................................................... 5-104
SIGNAL SOURCES phase measurement unit triggering .................................5-94
description....................................................................... 5-5 phasor measurement configuration .................................5-90
metering ........................................................................ 6-15 phasor measurement unit ...............................................5-89
settings ......................................................................... 5-73 phasor measurement unit calibration ...............................5-91
SIGNAL TYPES .................................................................. 1-3 phasor measurement unit communications ......................5-92
SINGLE LINE DIAGRAM .............................................. 2-1, 2-2 phasor measurement unit recording .............................. 5-101
SITE LIST, CREATING ....................................................... 4-1 test values ...................................................................5-277
SNTP PROTOCOL SYSTEM FREQUENCY .....................................................5-72
error messages ................................................................ 7-9 SYSTEM SETUP ..............................................................5-70
Modbus registers ...........................................................B-20
settings ......................................................................... 5-37
SOFTWARE
installation ....................................................................... 1-5 T
see entry for ENERVISTA UR SETUP
TARGET MESSAGES ........................................................ 7-6
SOFTWARE ARCHITECTURE ............................................ 1-4
TARGET SETTING ............................................................ 5-5
SOFTWARE, PC
TARGETS MENU ............................................................... 7-6
see entry for EnerVista UR Setup
TCP PORT NUMBER ........................................................5-35
SOURCE FREQUENCY .................................................... 6-18
TELEPROTECTION
SOURCE TRANSFER SCHEMES .................................... 5-183
actual values ................................................................... 6-5
SOURCES
clearing counters ............................................................. 7-2
description....................................................................... 5-5
FlexLogic™ operands ................................................... 5-113
example use of .............................................................. 5-74
logic ............................................................................ 5-261
metering ........................................................................ 6-15
Modbus registers ........................................................... B-45
Modbus registers ...........................................................B-22
overview ...................................................................... 5-259
settings ................................................................ 5-72, 5-73
settings .................................................... 5-67, 5-259, 5-260
SPECIFICATIONS ............................................................ 2-10
specifications .................................................................2-18
SPLIT PHASE PROTECTION
TEMPERATURE MONITOR .................................... 5-115, 7-10
FlexLogic™ operands .................................................. 5-112
TERMINALS ...................................................................... 3-8
logic ............................................................................ 5-182
TESTING
Modbus registers ...........................................................B-32
force contact inputs ...................................................... 5-275
settings ....................................................................... 5-179
force contact outputs .................................................... 5-276
specifications ................................................................. 2-11
lamp test ......................................................................... 7-3
ST TYPE CONNECTORS ................................................. 3-27
self-test error messages .................................................. 7-6
STANDARD ABBREVIATIONS ............................................F-9
synchrophasors ............................................................ 5-277
STATOR DIFFERENTIAL
THD
actual values ................................................................. 6-14
Modbus registers ........................................................... B-15
characteristic ............................................................... 5-145
THD METERING ............................................. 2-16, 6-18, 6-19
description................................................................... 5-145
analog channel correspondence ......................................5-44
FlexLogic™ operands .................................................. 5-112
THERMAL OVERLOAD PROTECTION
logic ............................................................................ 5-146
Modbus registers ........................................................... B-35
Modbus registers ..................................................B-10, B-29
settings ........................................................................ 5-243
settings ....................................................................... 5-145
specifications .................................................................2-14
specifications ................................................................. 2-10
THIRD HARMONIC NEUTRAL UNDERVOLTAGE
STATOR GROUND
FlexLogic™ operands ................................................... 5-107
see also entry for 100% STATOR GROUND
logic ............................................................................ 5-206
actual values ................................................................. 6-22
Modbus registers ........................................................... B-31
Modbus registers ..................................................B-11, B-32
settings ........................................................................ 5-205
settings ....................................................................... 5-201
specifications .................................................................2-12
STATUS INDICATORS ............................................ 4-14, 4-16
TIME ................................................................................. 7-2
STORAGE TEMPERATURE .............................................. 2-23
TIME OVERCURRENT
SUB-HARMONIC STATOR GROUND FAULT
see PHASE, NEUTRAL, and GROUND TOC entries
FlexLogic™ operands .................................................. 5-112
TIMERS ......................................................................... 5-122
settings ....................................................................... 5-207
TOC
specifications ................................................................. 2-12
ground ......................................................................... 5-167
SURGE IMMUNITY .......................................................... 2-24

viii G60 Generator Protection System GE Multilin


INDEX

neutral ........................................................................ 5-160 Modbus registers ................................................. B-24, B-38


phase .......................................................................... 5-153 settings ......................................................................... 5-51
specifications ................................................................ 2-10 specifications ................................................................. 2-15
TRACEABILITY USER-PROGRAMMABLE SELF TESTS
data .................................................... 4-11, 4-12, 8-13, 8-14 Modbus registers .......................................................... B-22
overview ...............................................................4-10, 8-12 settings ......................................................................... 5-49
rules .....................................................................4-12, 8-14 USERST-1 BIT PAIR ...................................................... 5-255
TRACKING FREQUENCY ........................................ 6-20, B-39
TRANSDUCER I/O
actual values ................................................................. 6-25
settings ........................................ 5-263, 5-264, 5-266, 5-267 V
specifications ................................................................ 2-17
VAR-HOURS ........................................................... 2-16, 6-18
wiring ............................................................................ 3-23
VIBRATION TESTING ...................................................... 2-24
TRIP BUS
VIRTUAL INPUTS
FlexLogic™ operands .................................................. 5-113
actual values ................................................................... 6-4
Modbus registers ........................................................... B-42
commands ....................................................................... 7-1
settings ....................................................................... 5-216
FlexLogic™ operands ................................................... 5-114
TRIP LEDs ...................................................................... 5-48
logic ............................................................................ 5-248
TROUBLE INDICATOR ............................................. 1-17, 7-6
Modbus registers ................................................... B-8, B-53
settings ....................................................................... 5-248
VIRTUAL OUTPUTS
U actual values ................................................................... 6-6
FlexLogic™ operands ................................................... 5-114
UL APPROVAL ................................................................ 2-25 Modbus registers .......................................................... B-55
UNAUTHORIZED ACCESS settings ....................................................................... 5-251
commands .................................................................... 5-14 VOLTAGE BANKS ............................................................ 5-71
resetting .......................................................................... 7-2 VOLTAGE DEVIATIONS ................................................... 2-24
UNDERFREQUENCY VOLTAGE ELEMENTS ................................................... 5-184
FlexLogic™ operands .................................................. 5-113 VOLTAGE HARMONICS ................................................... 6-19
logic ............................................................................ 5-225 VOLTAGE METERING
Modbus registers ........................................................... B-38 Modbus registers .......................................................... B-11
settings ....................................................................... 5-225 specifications ................................................................. 2-16
specifications ................................................................ 2-13 values ........................................................................... 6-16
UNDERVOLTAGE VOLTAGE RESTRAINT CHARACTERISTIC ..................... 5-153
auxiliary ........................................................................ 2-11 VOLTS PER HERTZ
phase .................................................................. 2-11, 5-185 actual values ................................................................. 6-23
third harmonic neutral .......................................... 2-12, 5-205 curves ......................................................................... 5-192
UNDERVOLTAGE CHARACTERISTICS .......................... 5-184 FlexLogic™ operands ................................................... 5-113
UNEXPECTED RESTART ERROR .................................... 7-10 logic ............................................................................ 5-192
UNIT NOT PROGRAMMED ....................................... 5-68, 7-7 Modbus registers .......................................................... B-46
UNPACKING THE RELAY .................................................. 1-1 settings ....................................................................... 5-191
UNRETURNED MESSAGES ALARM ................................. 5-66 specifications ................................................................. 2-12
UPDATING ORDER CODE ................................................. 7-3 VT FUSE FAILURE
URPC logic ............................................................................ 5-242
see entry for ENERVISTA UR SETUP Modbus registers .......................................................... B-45
USER-DEFINABLE DISPLAYS settings ....................................................................... 5-241
example ........................................................................ 5-59 VT INPUTS ...................................................... 3-14, 5-6, 5-71
invoking and scrolling .................................................... 5-57 VT WIRING ...................................................................... 3-14
Modbus registers .................................................. B-18, B-23 VTFF
settings .................................................................5-57, 5-59 FlexLogic™ operands ................................................... 5-112
specifications ................................................................ 2-15 see VT FUSE FAILURE
USER-PROGRAMMABLE FAULT REPORT
actual values ................................................................. 6-26
clearing .................................................................. 5-14, 7-2
Modbus registers ........................................................... B-15 W
settings ......................................................................... 5-41
WARRANTY .....................................................................F-11
USER-PROGRAMMABLE LEDs
WATT-HOURS ........................................................ 2-16, 6-18
custom labeling ............................................................. 4-22
WEB SERVER PROTOCOL .............................................. 5-35
defaults ......................................................................... 4-16
WEBSITE ........................................................................... 1-1
description ............................................................4-15, 4-16
Modbus registers ........................................................... B-21
settings ......................................................................... 5-48
specifications ................................................................ 2-14 Z
USER-PROGRAMMABLE PUSHBUTTONS
FlexLogic™ operands .................................................. 5-115 ZERO SEQUENCE CORE BALANCE ................................ 3-14

GE Multilin G60 Generator Protection System ix


INDEX