Control System Technology
Control System Technology
1
Utility Department
Training Unit
(IIM- 18)
Prepared by: p
^ Utility T r a i n i n g Unit n
^ ((2009)) D
-\ P
CONTROL SYSTEM TECHNOLOGY
Page
1. Control elements 1
1.1 process 1
1.2 measurement 2
1.3 evaluation 2
3. Controllers
3.1 proportional controller responses 21
3.2 proportional plus reset control 27
3.3 proportional plus reset plus rate control 30
3.4 objectives for good process control ^ ^40
3.5 preliminary steps for controller tuning 44
3.6 tuning proportional responses 47
3.7 tuning reset and rate responses 52
3.8 trial and error tuning methods 59
3.9 auto manual switching 70
4. Multielement control
4.1 ratio control loops 73'
4.2 cascade control loops 80
4.3 override control loops 90
1.1 Process :
A process is a physical or chemical change of matter or a conversion of
energy. Some examples of process are:
heating - cooling - mixing - smelting - separating - distilling - melting
- filling and emptying - casting - cooking - evaporating - refining.
1.2 Measurement
Z
FLUfD INLET
K
CONTROL FLUID
VALVE OUTLET
FIGURE 1-
Basic process control example (level).
UPSETS OR DISTURBANCES
MANIPULATED
HI CONTROLLED
VARIABLE VARIABLE
PROCESS
FINAL CONTROL
SENSOR
ELEMENT
RECORDER
INDICATOR
ALARMS
INTERLOCKS
3
2 T H E C L O S E D LOOP
4-
2.3 FACTORS OF PROCESS CONTROL
K» ¥ The basic factors of process control and some of the terminology used in process
sfe'.-: ' control.
2.5 T Y P E S OF SIGNALS
d
7'The four basic modes of control.
§f?The operating principle of two-position control.
W
Wk Control Modes
• two-position control
Two-Position Control
PREVIEW
REVIEW
Controllers
TWO-POSITION
CONTROLLER
STEAM
TRAP
V
In a process using two-position control, the value of TEMP
the controlled variable will fluctuate. In the pre- MAX. t
vious example, the temperature would repeatedly
rise and fall. Since a balance could not be main-
tained between heat input and heat output, the
SET POINT
temperature would never stabilize at a specified
value.
MIN. 1 !
VALVE
OPEN
CLOSED-L
VALVE
OPEN
CLOSED J-
HOW A FEEDBACK CONTROL SYSTEM WORKS
(3 r
2--- ^ r-
Controlled
Variable
Oscillations Caused by Process Lags
Set Point
Dead
Time
Time
Howeve*
What is meant by the term proportional band.
Proportional Band
Proportional Gain
Input Output Increasing the proportional gain means that one unit
of input change will result in more than one unit of
output change. For example, a proportional gain of
2 means that one unit of input change results in
two units of output change.
Decreasing the proportional gain means that it will input Output
take more than one unit of input change to produce
one unit of output change. For example, a propor-
tional gain of 1/2 means that it will take two units
of input change to produce one unit of output
change.
0
Proportional Gain = P r o p o r t }° n a , B a n d
Sensitivity
Time
Set
Pofnt
Time
r
Time
2$'
A low proportional, band setting produces a curve in
which the oscillations grow in size as time progresses.
This type of curve is very unstable. A curve of this
type would also be produced by a very high setting
of proportional gain.
Controlled
Variable
Time
3- 2 PROPORTIONAL-PLUS-RESET CONTROL
Temperature
Position of Final
Control Element Initial Position
Offset
Measured
Set Point
Variable
Proportional-Plus-Reset • Control
Position ol Final
Control Element
At Initial Position
Measured
Variable Sel Point
Process Load
Load Change
Time
f
3,3 • DERIVATIVE CONTROL?
Derivative Control
30
Derivative control compensates for lags in the
process by reacting to the rate at which the meas-
ured variable is deviating from the set point. With
derivative control, the controller action is similar
to an on-off controller during the initial phase of a
process change and then returns to normal propor-
tional-plus-reset control. This causes the controller
Derivative control may also output to begin responding immediately to process
be called rate control, changes to correct for the deviation and prevent
pre-act control, or hyper overshoot. This immediate response would not be
control. possible with proportional-plus-reset control because
of the wide proportional band setting and slow
reset action that is required to avoid excessive
cycling. Derivative control is based on the time/
rate of the deviation rather than the quantity of
the deviation. So derivative control is calibrated
in time, or frequency, just like the reset adjustment.
TO MEASUREMENT POINTER
2s: A A NOZZLE
C Q
- o
DERIVATIVE LINEARIZING
ASPIRATOR -AIR SUPPLY
RESTRICTOR RELAY
MEASUREMENT IN
TO MEASUREMENT
BELLOWS IN AUTOMATIC
CONTROL UNIT
b. CHANGE IN MEASUREMENT
TIME
Automatic Control Unit (C) restore the balance of forces (again ignoring reset
action). The 130 Series Controller has a proportional
The automatic control unit design is based upon band continuously adjustable from 5 to 500 percent,
the classic force-balance principle. Four bellows - corresponding to 20 to 0. 2 gain.
for set-point signal, measurement signal, proportional
feedback and reset feedback - bear upon a floating
disc, with two of the bellows on each side of a fulcrum.
The forces multiplied by the respective distances from
the fulcrum (the summation of moments) equal zero
to keep the floating disc in equilibrium. The floating A
disc acts as a flapper of a conventional flapper-nozzle
detector system. The system is Illustrated in Figure 12.
3H
r
O P T I M U M CONTROLLER SETTINGS
0>
8
o o
10
CO
-j CD
O
o
(
O
c: O
o LU
o
c
r—
O
r—
UJ
J—
"a o «8 CO
00 o o>
i3 Q) t o ^
SO
UJ o o I ! 3 5—
6
CO o i- D
z: g
o o o o £~2 a. §
C U D
O o
a. 2 -+-'
00 c c
UJ o
or X to
a
GO
to o
o—
O
V) CO o
u_ o O
£
o
o
«
a> CD—
o CO en
0) o 'o
o -a c
r— a "° o » .
>•> cn <u
"O
a
UJ
o 1 = "O D ~ cu ™ <
u_ a o 33 b O O c
o
Lu 00 o_
UJ
o
"D
O -M 1_
§^ S—
I— CO UJ
CD
,2 a.
-M
o «
5(0 O a - So
.a
or (0 8 3£E . 2 «5 *
<0 CO c m—
-C
CO
o
r—
_a> c
_o S
c o £ i=
'w -5 c 8 5 <n 8 -TJ O o
o .£ = 2 £-g «
o I I a c .c o c o I o
> au
> aL:> to <D
a. a
X o 00 c fc o ow UJ
u.
UJ Lu
O U
o I
CO
LU
i
CD
o a_
UJ
Q
35
5,1
1. Beam.
2. Fulcrum.
3. Noz2le.
Uec&Jiement Oulpul
Supply
RELAY
' RELAY
RELAY
RELAY
Fig. 4. Proportional Controller after
increase in flow rote.
3<S
B
MV FB S P aI
RELAY
Fig. 5. Proportional Controller after
fall In flow rote.
a t= 4b
Set S 9
MV
Set
a Rosel
Adjustable
Reatrictor
FB
RELAY
Rest!
TV
c b
it
RELAY
Summary
There is a need to summarise the different conventional control modes that have
been presented and Table 1 gives the basic description of those available. Table 2
illustrates the response functions i.e., to different changes in the input error
signal. Table 3 gives a summary of the basic characteristics of these controllers.
One Mode
P Proportional m = K! e
Integral ( r e s e t ) m = y fe dt
Two Mode
Proportional — p i u s -
Pi integral m = K (e e + \je d t )
Proportional — p l u s -
PD derivative m = K (e e + T
c ^ e)
Three Mode
Proportional—plus— m = K (e e + ^ / e dt
PID integrol-plus—
derivative + T.&e)
Table 1. C o n v e n t i o n a l C o n t r o l l e r Modes.
Summary (continued)
Two-Position :
Inexpensive
Extremely simple
Proportional :
Simple
Inherently stable when properly tuned
Easy to tune
Experiences offset at steady state
Proportion-plus-reset :
No offset
Better dynamic response than reset alone
Possibilities exist for instability due to lag introduced
Proportional-plus-rate
Stable
Less offset than proportional alone (use of higher Kc possible)
Reduces lags, i.e. more rapid response
Proportional-plus-reset-plus-rate
Most complex
Most expensive
Rapid response
No offset
Difficult to tune
Best control if properly tuned
PI — -
PD
PID
Table 3.
3.4- OBJECTIVES FOR GOOD PROCESS CONTROL
How the one-quarter decay ratio curve can be used as a guideline for good process
control.
Time
L
i'Z
Other Guidelines for Good Control
How to calculate the proper setting for proportional band or proportional gain for a
proportional controller.
Follow the manufacturer's • Eliminate the reset and derivative modes from
procedure for tuning t the controller, i f they are present. This
out reset and derivative procedure varies somewhat from one controller
action. to another. In general, the procedure involves
turning the reset and derivative adjustments to
the setting that will minimize their effect.
Time
L|9
• Watch the response shown on the recorder. I f
the process starts to dampen out, continue to
decrease the proportional band setting (or
increase the proportional gain setting) gradually
until sustained oscillations occur in the process
reaction curve. I f the process reaction curve
produces oscillations that increase in amplitude,
gradually increase the proportional band (or
decrease the proportional gain) until sustained
oscillations occur.
Time
• PB = PB X 2
U
Proportional Band.
SO
7
• K = S
c u X 0.5
Proportional Gain.
Time
r~
/
How to calculate the proper proportional and reset settings for a two-mode controller.
Offset
Controllers are adjusted Many controllers have an adjustment for reset. Two
for either reset time or common types of reset adjustments are called reset
reset rate. time and reset rate. Although both adjustments
have the effect of continuing corrective action to
eliminate offset, the settings are not equivalent. As
with proportional band and proportional gain, reset
time and reset rate are inversely related to each
other. Increasing the reset time has the same effect
as decreasing the reset rate.
.05 20.0
.1 10.0
Reset Time -
Reset Rate
.2 5.0
.5 2.0
1.0 1.0 .
Reset rate =
Reset Time
2.0 .5
5.0 .2
10.0 .1
Ultimate Period
The following formulas can be used to determine Use the proper formula for
the proper settings for two-mode controllers. the controller you are
- tuning.
• PB = PB X 2.2 U
Proportional Band.
o K = S c u X 0.45
Proportional Gain.
Tj refers to the reset time. P u refers to the
value of Ultimate Period.
R
• i ~ —
1
u
Rj refers to the reset rate, P u refers to the
value of Ultimate Period.
/
TUNING DERIVATIVE RESPONSE
1. How the addition of derivative mode to a controller can improve control in some
processes.
Derivative Control
r
In order to eliminate overshoot, some processes
require a quick initial response to a process
disturbance. Adding derivative response to a
controller can improve the initial response of the
controller and help bring the process back to the set Derivative control is also
point more quickly. called rate control.
S'6
Calculating Proportional-Plus-Derivative Settings
• PB = PB U X 1.7
• K c = S u X 0.6
Calculating Proportional-Plus-Reset-Plus-Derivative
Settings
proportional band or j u
proportional gain. » K = S X 0.6
c u
The corresponding formulas for reset response on
three-mode controllers are:
s
T R I A L AND ERROR TUNING - PART I
How to tune the proportional mode o f a controller by the trial and error method.
>
Time
J \ J
sustained oscillatipns.
T
A proportional band setting that is too low is
slow in returning to stability. The curve
produced will oscillate before it becomes stable,
or it may continue to oscillate and not stabilize.
How to tune the derivative mode by the trial and error method.
How to tune the reset mode by the trial and error method.
A properly-tuned proportional-plus-derivative
controller will produce a one-quarter decay ratio
curve. The process should stabilize faster than with
a proportional-only controller. This increased
response reduces the number of oscillations on a
a process reaction curve. The size o f the initial
peak on the curve will be smaller than the initial
peak on the curve of a properly-tuned proportional-
only controller. In the example, the solid line
represents the general characteristics of a properly-
tuned proportional-plus-derivative controller. The
dotted line represents the general characteristics of
a properly-tuned proportional-only controller.
Time
r~
Tuning Derivative by Trial and Error
• Make a small set point change and observe the Hold the change so you can
process response on the chart recorder. accurately analyze the
process response curve.
A
i i
may appear to trail toward the set point after it
stops oscillating. This type of curve would^be^ —
produced by a reset time setting that was too high.
SelF oint
A properly-tuned proportional-plus-reset-plus-
derivative controller will produce a one-quarter decay
ratio curve in response to a set point change. The
curve will exhibit the speeded-up response and small
initial peak of derivative control. The addition of
reset changes the curve by reducing or eliminating
offset.
&2
OPTIMUM CONTROLLER SETTINGS
PRESSURE
* Most lags are in the control system. * Gain near 1, fast reset controllers.
» Nonlinear (square). * Derivative of no volue.
* Noisy. * Linear valve.
Liquid
PRESSURE
* No dead time. controllers.
* Linear, no noise. * Reset seldom necessary.
* SimpSe process. * Derivative unnecessary •
Gas * Valve characteristic relatively unimportant.
PRESSURE
* Dead time possible. * Settings vary.
* Slow compered to other pressure * Equal percentage valves.
processes.
Vapour * Linear, no noise.
* Change the value of the set point until it equal the value of measured
variable (process variable)
* Keep the control stables i.e. the output of the controller to the final
control element keep the process almost stable.
* Keep your eye on the output of the controller during switching to auto
(The output must not change)
AUrOC
' LOSE --^ MAN'CLOSE
AUTOMATIC AUTOMATIC
BALANCING UNJl BALANCING UNIT
\ I 3 ARE I 1 3 Aftg
PNEUMATIC tOOIC U W I S AUTOMATIC CONTROL SECTION PNEUMATIC LOGIC UNITS AUTOMATIC CONTROL SECTION
THUMBWHEEL THUMBWHEEL
OUTPUT INOICAIOH
OUTPUT 1NOICAIOH
Daianceless, Dumpless Transfer fE) units, is zero. It holds the pneumatic logic units in
the position shown in Figure 15, These logic units
Transfer between automatic and manual control connect the output of the automatic control unit to
is a one-step operation that consists of moving the tire final operator and pneumatically deactivate the
switch to the desired mode of operation. There arc automatic balancing unit described below.
no indicators to balance or pointers to match.
With tile transfer switch in the MANUAL position,
As shown In Figure 15, with the transfer switch the operation is as shown in Figure 16, The output of
in the A U T O M A T I C position, the selector lever in the manual control relay is the controller output!
the manual unit has been moved away from the The switch also sends full air supply signal to the
adjusting wheel to permit the lever and flapper to three pneumatic logic switches. Two of the switches
float freely. The flapper will now follow die pressure are closed and one opened by this signal as shown In
in the manual control bellows which is now the auto- the diagram.
matic control unit output. Thus, the flapper bellows
combination Is balanced at the automatic control 'Flie output of the automatic control unit is discon-
unit output level. When the transfer switch is later nected from the output of the controller. The reset re-
moved to manual, the selector lever Is clamped by stricior is bypassed, and the reset bellows is disconnected
the manual adjustment wheel at the existing output
from the proportional bellows. The input signals to the
level. The transfer is thus smooth and balanceless
from automatic to manual operation. The output automatic balancing unit shown are the automatic control
will be frozen at the last automatic output value of unit output D and the manual control output A. D i a -
the controller. Since the selector lever is mechanically phragm B provides the balancing pressure and C Is the
clamped in this position, the output cannot drift and output to the control unit reset bellows.
will remain constant until adjusted by the operator.
In automatic control, the output of the manual The automatic balancing unit is a simple integrating
controller relay is dead ended in die switch with controller consisting of a single pivoted diaphragm with
the air supply shut off to prevent any air consumption. four air pressure compartments.
The switching signal, sent to the pneumatic logic
7
l e ) MEASUREMENT* S E T POINT I b)MEASUREMENT< SET POINT
TIME
AUTOMATlC-TO-MANUAL TflflNSFER
(LA5T AUTOMATIC CONTROL OUTPUT
HELD UNTIL. ADJUSTED)
TIME »- TIME
MANUAL-TO-AUTOMATIC T R A N S F E R
If either the measurement or the set point to response will be injected into the output upon transfer
the automatic control unit changes, die output of to assure a quick recovery. Reset action will then
the automatic control unit must also change, because smoothly ramp the process to the new set point without
it is operating as a proportional only control unit, overshoot.
When the change in pressure in the proportional
bellows is sensed by the balancing unit, the output of If the output of die manual control unit changes,
the unit will change the pressure in the reset bellows then a similar action occurs to force the automatic
of the controller. This in turn will cause the output control unit output to equal the manual control unit
of the control unit to change. Tins change will con- output.
tinue until the pressure in the proportional feedback •
bellows once again equals the output of the manual When a transfer is made from, manual to automatic
control relay or the supply pressure limits arc reached. (see Figure 17), the output will remain at the level
determined by die operator when in manual. If the
The difference between the set point and measure- measurement input is equal to the set point, as shown
ment bellows is being balanced by the difference be- in Figure 17(a), the output remains Constant until
tween the reset and proportional bellows. If the supply corrective action is required. If die measurement does
pressure is reached, the proportional bellows will not equal die set point at the moment of transfer, as
stabilize at a pressure which differs from the output of illustrated In Figure 17(b), the output will ramp from
the manual unit. This condition can only exist when the level of manual operation to the level necessary
a narrow proportional band or a high- or low-level manual to make the measurement equal to set point as a func-
output are being used and a large difference between tion of the reset rate of the controller.
measurement and set point exists. Some proportional
4 1
r
w
p R A
4-S ™ CONTROL
§
I
Ratio Control
$$'
Wild Stream Ratio Control
Stream A - Uncontrolled
Ratio Controller
• 7 ^
Flow Transmitter
Stream 8
Information about the two flow rates is sent to the
ratio controller. The ratio controller is designed to
"maintain the ratio between the two streams. The
flow rates are compared to determine the actual
ratio between them. The ratio controller then
compares the actual ratio to the set point of the
controller. The set point of the controller is the
desired ratio between the two streams. The set
point is set by the ratio relay inside the controller.
Adjustments can be made to achieve the desired
ratio.
Stream A
Flow Controller
Flow
Transmitter
0
Ralio Controller
1
Vr
Ratio >
Relay
Flow 7
Transmitter
Stream B
The ratio relay sets Information about the flow rate in both streams is
the set point. The set sent to the ratio controller. The ratio controller
point is the desired compares the actual ratio between the flow rates of
ratio. the two streams to the set point. The flow rate
in Stream B is adjusted to maintain the desired ratio.
This is because the flow rate in Stream A is fairly
constant.
Tuning Ratio Control Systems
The preceding pages have dealt with single variable control loops- one controlled variable, one
manipulated variable. In multiple-variable control, the manipulated variable is a function of a
combination of controlled variables. The four commonly encountered multiple-variable loops
are, ratio, cascade, feed forward, and override.
Ratio
In ratio control, the controlled variable is
the ratio of the two measured variables. Wild flow
Control is effected by adjusting one of the (FX2
variables-the controlled variable- to follow
in proportion to a second- the wild variable-
The proportionality constant is the ratio.
Examples of the ratio control systems include
Ratioing reactant flows in chemical processes,
Air-to-fuel ratio in boilers, and simple blending
of fluid streams.
Ratio relays are nothing more than manually-adjustable gain devices, and the ratio
setting is the true set point of the system. If flow measurements are with
differential pressure transmitters, the actual linear ratio setting must be the square
of the required ratio.
The wild flow is not necessarily uncontrolled- it is only wild as the ratio is
concerned. For instance, in air to fuel ratio control in boilers, the wild fuel flow is
controlled by another system, based on steam demand. It is actually the controlled
flow in another ratio system. As shown
Ratio systems are not limited to two components; one wild flow can adjust several
controlled flows, each with separate ratio relays and individual controllers. A
variation of this system permits all components in a blend to be set as percentages
of the required total flow, which can be set by a master pacing signal
steam
fuel
air
In the paper stock blending system shown, the stock chest level controller paces
the flow rate of all components by adjusting individual components flow set points
through ratio relays. Each ratio set points, through ratio relays. Each ratio is set to
the required percentage of that component in the total blend.
4-*&. CASCADE CONTROL - PART I
j
Controller Transmitter For example, a single feedback temperature control
loop might control the temperature of water in a
tank. A coil containing hot water is used to heat
the water in the tank. The control loop consists of
a temperature sensor and transmitter, a temperature
controller, and a control valve.
Control
Valve
I f the water temperature in the coil drops, the
temperature of the tank water will eventually fall.
It takes time to transfer the heat from the coil to
the tank water. Therefore, the change in the tank
water temperature will not be immediate.
Hot Water
In a cascade control system, the output of the The primary controller sets
primary controller does not go to the final control the set point on the
element. The output of the primary controller sets secondary controller.
the set point on the secondary controller. Changing
the output of the primary controller changes the
set point of the secondary controller.
How cascade control can improve process response to a disturbance or load change.
The primary controller may The settings on the primary controller that provide
have one, two, or three good control may be more conservative than you
modes. would expect. This is because the primary and
secondary loops interact. Therefore, the primary
loop is usually tuned by the trial and error method.
If the Ziegler-Nichols formulas are used to calculate
settings, the cascade system may overreact to a
disturbance or load change.
r~
j
: ; : ;
rv'-'V?,''The oulput of tempemtur^ controller' TC-j adjusts the'-r;-::-^H:t K:'-;- J?jk j' V^^A• ^N*^ 'j Ha : ; V '.?
& '&v;*£^
:
in the^batch',reaclpf'control s y s t e n v p . - - .
Fig. 42:' This' is the essence' of cascade control. .The .
:
v;:" " primary variab1e-batchfiemperature--is controlled by'
!
, Slave t ,. .
$^^ ^-the'w^ bui*tibt;,by directly adjusting the • p'V
.2^ M • wish:-:
cooling water valve.'. Instead, it manipulates the set-
'/.: >;.•. point of the slave or secondary controller, which in turn
v;' . supplies jacket water, at; Jhe .asked-for . temperature. .; ; i > , .!.. , : j .:.. r. . . . CoeEng woierH
.. There are two controlled vanables, one manipulated y ^ : : :
K^;. " ' o ^ - v f ; - j y , . .| :
H[:-'<- variable, arid.one independent set-points' : ' .' . Fig". 42-Casca'de^Control of Batch Reactor
4^^?^ ^: ':5>,:;^' ; \.'v'" :
X ' ? . ' ' . : ^'"^^";V:-""-^;V<;^^^^/" f
' Cascade control has two functions: • '•". ,'. V . ; ' ^•••.•'- : ,v
t?.\ "'•
: : :: ; ; ;i 1 i :
Jr ^^; ' -''-'"' ' "r; -:!V :-S ; '-:' ^ U : ^ ^ / ; .v-^;' v ^ ' f e ^ \
1
^Reduce the. effect on the total control system of lhe ' ;
' AV - - - v V. :-
;
v.jv...
T' ' '. '^'"x" • -'••;;'. - v ; -;V '•.'.•'•"'•;"''-'••-": •
; , / >
: f
dynamic elements .in the secondary loop (in Fig. 42,'.' ' ' "-'-' : ;
•'•''v'^^- » !
Correct' for 'disturbances'-which occur within the >ppocEss
:
'DYNAMICS^ •DYNAM1C5S
secondary, loop before they affect the master loopr- ' -••-..-,-vi -i:.<\\
.'• (Such as cooling water temperature changes.)
^ '
•
;;
10
' ' •' The major.time 'constant musthot be in the slave loop.' • ••
Siove
y; This reduces the ratio of major to secondary dynamic '• — < ' Jockel V Loop
• •••'
v-,.-:,;,;-..:...; elements and will degrade control, '^y-'^
•"><:';: -•<-••:• : :
-'
;>/;.,..".. Be careful when making flow the slave variable. If the
• . ; .• ^ '>.-,:•
>-'i -i-^i-
\- •ir>v.".;,"'.
' V •
0.1
^:r. :--j;:,i. overall process is linear with flow, yoti.introduce a non-
J w
'."'.11M'
F
• . ....
4.7 OVERRIDE CONTROL
High Low
pressure Pressure
fluid users
source
High
pressure
users
(priority)
j
In this example PRC1 have override control over PRC2 and
commands it to close the valve completely should the high pressure
side falls below the set point.
5 commissioning control system
2. Transmission checks.
5. Alarms checks.
6. Trip checks.
7. Start on manual.
8. Transfer to auto.
9. Check stability.
5\
6. Spec 200 Electronic Process Control Systems
Spec 200 equipment consist of two parts
1. nest mounted system electronics
2. Operator interface functions
The nest mounted systems contains all the electronic modules like
- input and output components
- Control components
- Signal processing components
- Signal distribution components
- Power distribution
SIGNAL
OISTRI8UTION
Operator interface contains modules like
- Indicator display stations
- Recorder display stations ALARMS
- Control display stations
- Manual display display stations
- Annunciator subsystems CONTROL
SIGNAL
PROCESSING
OUTPUTS
DISPLAY
INPUTS
Current to
Voltage converter to Control
Station to Recorder
Power
supply
PI signal
Controller distribution
3-15 psi
I/P
FCE
Computet
FCE
Multiplexer
FCE FCE
Supervisory Control
Conlroller
FCE MUX
Conlroller Conlroller
FCE FCE
Micro
Compuler
Loop 1
Data Bus
Micro
Computer
Loop 2
Micro
Computer
Loop 4
Distributed P r o c e s s C o n t r o l
Host Computers
Micro Host
Compuler Compuler
Loop 3
Micro
Compuler
Loop i
Data Bus
Micro
Computer
Loop 2
Micro
Compuler
Loop 4
/ 00
T R O U B L E SHOOTING
Trouble shooting is the process of
Determining the cause of the problem
Making repairs
Finding ways to prevent the problem from occurring
in the future.
Locating a problem
1. Determine how the system works
Understand how the instrument loop works
Understand the P&ID giving information such as
system design, tolerances and operating range
Look at the sample record of the initial calibration.
Check from the operation i f any changes have been
made.
2. Identifying symptoms
Talk to the operator who discovered the problem.
Observe i f the system is operating according to ranges
and tolerances.
Compare recent chart record with that of initial
calibration
/
1
Input section
Flow sensor element — orifice plate
Flow transmitter
Square root extractor
Transmission lines
Output section
Control valve
Positioner
Transmission lines
Controller
Input mechanism
Output mechanism
Automatic control mechanism