TI01102D/06/EN/05.

17 Products Solutions Services


71380242

Technical Information
Proline Promag P 100
Electromagnetic flowmeter

The flowmeter for highest medium temperatures with an ultra-compact


transmitter
Application Your benefits
• The bidirectional measuring principle is virtually • Versatile applications – wide variety of wetted materials
independent of pressure, density, temperature and viscosity • Energy-saving flow measurement – no pressure loss due to
• Dedicated to chemical and process applications with cross-section constriction
corrosive liquids and high medium temperatures • Maintenance-free – no moving parts
Device properties • Space‐saving transmitter – full functionality on smallest
• Nominal diameter: max. DN 600 (24") footprint
• All common Ex approvals • Time‐saving local operation without additional software and
• Liner made of PTFE or PFA hardware – integrated web server
• Robust, ultra-compact transmitter housing • Integrated verification – Heartbeat Technology
• Local display available
Proline Promag P 100

Table of contents

About this document . . . . . . . . . . . . . . . . . . . . . . . . 3 Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40


Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Medium temperature range . . . . . . . . . . . . . . . . . . . . . . 40
Conductivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Pressure-temperature ratings . . . . . . . . . . . . . . . . . . . . 41
Function and system design . . . . . . . . . . . . . . . . . . . 4
Pressure tightness . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Flow limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Measuring system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Pressure loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Equipment architecture . . . . . . . . . . . . . . . . . . . . . . . . . 6
System pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Vibrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Mechanical construction . . . . . . . . . . . . . . . . . . . . 46
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dimensions in SI units . . . . . . . . . . . . . . . . . . . . . . . . . 46
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dimensions in US units . . . . . . . . . . . . . . . . . . . . . . . . . 49
Operable flow range . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Input signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Measuring tube specification . . . . . . . . . . . . . . . . . . . . . 52
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Fitted electrodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Process connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Surface roughness . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Low flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Protocol-specific data . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Local display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Pin assignment, device plug . . . . . . . . . . . . . . . . . . . . . . 26 Service interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Certificates and approvals . . . . . . . . . . . . . . . . . . . 60
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . 29
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Power supply failure . . . . . . . . . . . . . . . . . . . . . . . . . . 29
C-Tick symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . 33
HART certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Certification PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . 61
Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
EtherNet/IP certification . . . . . . . . . . . . . . . . . . . . . . . . 61
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Certification PROFINET . . . . . . . . . . . . . . . . . . . . . . . . 61
Pressure Equipment Directive . . . . . . . . . . . . . . . . . . . . 61
Performance characteristics . . . . . . . . . . . . . . . . . . 35 Other standards and guidelines . . . . . . . . . . . . . . . . . . . 61
Reference operating conditions . . . . . . . . . . . . . . . . . . . 35
Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . 35
Ordering information . . . . . . . . . . . . . . . . . . . . . . . 62
Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Temperature measurement response time . . . . . . . . . . . . 36
Influence of ambient temperature . . . . . . . . . . . . . . . . . 36 Application packages . . . . . . . . . . . . . . . . . . . . . . . 62
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Heartbeat Technology . . . . . . . . . . . . . . . . . . . . . . . . . 62
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Mounting location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Inlet and outlet runs . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Device-specific accessories . . . . . . . . . . . . . . . . . . . . . . 63
Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Communication-specific accessories . . . . . . . . . . . . . . . . 63
Service-specific accessories . . . . . . . . . . . . . . . . . . . . . . 64
System components . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . 39
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Supplementary documentation . . . . . . . . . . . . . . . 64
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Standard documentation . . . . . . . . . . . . . . . . . . . . . . . . 64
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Supplementary device-dependent documentation . . . . . . . 65
Shock resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Impact resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . 65
Mechanical load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Electromagnetic compatibility (EMC) . . . . . . . . . . . . . . . 40

2 Endress+Hauser
Proline Promag P 100

About this document


Symbols used Electrical symbols

Symbol Meaning

Direct current

Alternating current

Direct current and alternating current

Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.

Protective Earth (PE)


A terminal which must be connected to ground prior to establishing any other
connections.
The ground terminals are situated inside and outside the device:
• Inner ground terminal: Connects the protectiv earth to the mains supply.
• Outer ground terminal: Connects the device to the plant grounding system.

Symbols for certain types of information

Symbol Meaning

Permitted
Procedures, processes or actions that are permitted.

Preferred
Procedures, processes or actions that are preferred.

Forbidden
Procedures, processes or actions that are forbidden.

Tip
Indicates additional information.

Reference to documentation.

A Reference to page.

Reference to graphic.

Visual inspection.

Symbols in graphics

Symbol Meaning

1, 2, 3, ... Item numbers

1. , 2. , 3. , … Series of steps

A, B, C, ... Views

A-A, B-B, C-C, ... Sections

Hazardous area
-
Safe area (non-hazardous area)
.
Flow direction

Endress+Hauser 3
Proline Promag P 100

Function and system design


Measuring principle Following Faraday's law of magnetic induction, a voltage is induced in a conductor moving through a
magnetic field.

Ue
I

v
B

I
L

A0028962

Ue Induced voltage
B Magnetic induction (magnetic field)
L Electrode spacing
I Current
v Flow velocity

In the electromagnetic measuring principle, the flowing medium is the moving conductor. The
voltage induced (Ue) is proportional to the flow velocity (v) and is supplied to the amplifier by means
of two measuring electrodes. The flow volume (Q) is calculated via the pipe cross-section (A). The DC
magnetic field is created through a switched direct current of alternating polarity.
Formulae for calculation
• Induced voltage Ue = B · L · v
• Volume flow  Q = A · v

4 Endress+Hauser
Proline Promag P 100

Measuring system The device consists of a transmitter and a sensor.


The device is available as a compact version:
The transmitter and sensor form a mechanical unit.

Transmitter

Promag 100 Device versions and materials:


Compact, aluminum, coated:
Aluminum, AlSi10Mg, coated
Configuration:
• Via operating tools (e.g. FieldCare, DeviceCare)
• Also for device version with 4-20 mA HART, pulse/frequency/switch
A0016693
output:
Via Web browser (e.g. Microsoft Internet Explorer)
• Also for device version with EtherNet/IP output:
– Via Web browser (e.g. Microsoft Internet Explorer)
– Via Add-on Profile Level 3 for automation system from Rockwell
Automation
– Via Electronic Data Sheet (EDS)
• Also for device version with PROFINET output:
– Via Web browser (e.g. Microsoft Internet Explorer)
– Via device master file (GSD)

Sensor

Promag P Nominal diameter range: DN 15 to 600 (½ to 24")


Materials:
• Sensor housing:
– Aluminum, AlSi10Mg, coated
– DN 15 to 300 (½ to 12"): aluminum, AlSi10Mg, coated
– DN 350 to 600 (14 to 24"): carbon steel with protective varnish
• Measuring tubes 1): stainless steel, 1.4301/1.4306
• Liner: PFA, PTFE
• Electrodes: stainless steel, 1.4435 (F316L); Alloy C22, 2.4602 (UNS
A0017703
N06022); platinum; tantalum; titanium
• Process connections: stainless steel, 1.4404 2)/1.4571/F316L 2);
carbon steel, A105/E250C 2)/S235JRG2/S275JR
• Seals: as per DIN EN 1514-1
• Ground disks: stainless steel, 1.4435 (316L); Alloy C22, 2.4602 (UNS
N06022); tantalum; titanium

1) For flanges made of carbon steel with Al/Zn protective coating (DN 15 to 300 (½ to 12")) or protective
varnish (DN 350 to 600 (14 to 24"))
2) With Al/Zn protective coating (DN 15 to 300 (½ to 12")) or protective varnish (DN 350 to 600 (14 to 24"))

Endress+Hauser 5
Proline Promag P 100

Equipment architecture
1
2 3 4 5

6
A0021560

1 Possibilities for integrating measuring devices into a system


1 Control system (e.g. PLC)
2 EtherNet/IP
3 PROFIBUS DP
4 PROFINET
5 Modbus RS485
6 4-20 mA HART, pulse/frequency/switch output
7 Non-hazardous area
8 Non-hazardous area and Zone 2/Div. 2

Safety IT security
We only provide a warranty if the device is installed and used as described in the Operating
Instructions. The device is equipped with security mechanisms to protect it against any inadvertent
changes to the device settings.
IT security measures in line with operators' security standards and designed to provide additional
protection for the device and device data transfer must be implemented by the operators themselves.

Input
Measured variable Direct measured variables
• Volume flow (proportional to induced voltage)
• Electrical conductivity

Calculated measured variables


• Mass flow
• Corrected volume flow

Measuring range Typically v = 0.01 to 10 m/s (0.03 to 33 ft/s) with the specified accuracy
Electrical conductivity: ≥ 5 μS/cm for liquids in general

Flow characteristic values in SI units


Nominal Recommended
Factory settings
diameter flow

Current output full scale


min./max. full scale value Pulse value 1) Low flow cut off
value 1)
(v ~ 0.3/10 m/s) (~ 2 pulse/s) (v ~ 0.04 m/s)
(v ~ 2.5 m/s)

[mm] [in] [dm3/min] [dm3/min] [dm3] [dm3/min]

15 ½ 4 to 100 25 0.2 0.5

25 1 9 to 300 75 0.5 1

6 Endress+Hauser
Proline Promag P 100

Nominal Recommended
Factory settings
diameter flow

Current output full scale


min./max. full scale value Pulse value 1) Low flow cut off
value 1)
(v ~ 0.3/10 m/s) (~ 2 pulse/s) (v ~ 0.04 m/s)
(v ~ 2.5 m/s)

[mm] [in] [dm3/min] [dm3/min] [dm3] [dm3/min]

32 – 15 to 500 125 1 2

40 1½ 25 to 700 200 1.5 3

50 2 35 to 1 100 300 2.5 5

65 – 60 to 2 000 500 5 8

80 3 90 to 3 000 750 5 12

100 4 145 to 4 700 1200 10 20

125 – 220 to 7 500 1850 15 30

150 6 20 to 600 m3/h 150 m3/h 0.03 m3 2.5 m3/h

200 8 35 to 1 100 m3/h 300 m3/h 0.05 m3 5 m3/h

250 10 55 to 1 700 m3/h 500 m3/h 0.05 m3 7.5 m3/h

300 12 80 to 2 400 m3/h 750 m3/h 0.1 m3 10 m3/h

350 14 110 to 3 300 m3/h 1 000 m3/h 0.1 m3 15 m3/h

400 16 140 to 4 200 m3/h 1 200 m3/h 0.15 m3 20 m3/h

450 18 180 to 5 400 m3/h 1 500 m3/h 0.25 m3 25 m3/h

500 20 220 to 6 600 m3/h 2 000 m3/h 0.25 m3 30 m3/h

600 24 310 to 9 600 m3/h 2 500 m3/h 0.3 m3 40 m3/h

1) HART only

Flow characteristic values in US units


Nominal Recommended
Factory settings
diameter flow

Current output full scale


min./max. full scale value Pulse value 1) Low flow cut off
value 1)
(v ~ 0.3/10 m/s) (~ 2 pulse/s) (v ~ 0.04 m/s)
(v ~ 2.5 m/s)
[in] [mm] [gal/min] [gal/min] [gal] [gal/min]

½ 15 1.0 to 27 6 0.1 0.15

1 25 2.5 to 80 18 0.2 0.25

1½ 40 7 to 190 50 0.5 0.75

2 50 10 to 300 75 0.5 1.25

3 80 24 to 800 200 2 2.5

4 100 40 to 1 250 300 2 4

6 150 90 to 2 650 600 5 12

8 200 155 to 4 850 1200 10 15

10 250 250 to 7 500 1500 15 30

12 300 350 to 10 600 2400 25 45

14 350 500 to 15 000 3600 30 60

16 400 600 to 19 000 4800 50 60

18 450 800 to 24 000 6000 50 90

Endress+Hauser 7
Proline Promag P 100

Nominal Recommended
Factory settings
diameter flow

Current output full scale


min./max. full scale value Pulse value 1) Low flow cut off
value 1)
(v ~ 0.3/10 m/s) (~ 2 pulse/s) (v ~ 0.04 m/s)
(v ~ 2.5 m/s)

[in] [mm] [gal/min] [gal/min] [gal] [gal/min]

20 500 1 000 to 30 000 7500 75 120

24 600 1 400 to 44 000 10500 100 180

1) HART only

To calculate the measuring range, use the Applicator sizing tool →  64

Recommended measuring range


"Flow limit" section →  44

Operable flow range Over 1000 : 1

Input signal External measured values


To increase the accuracy of certain measured variables or to calculate the corrected volume flow, the
automation system can continuously write different measured values to the measuring device:
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure
measuring device for absolute pressure, e.g. Cerabar M or Cerabar S)
• Medium temperature to increase accuracy (e.g. iTEMP)
• Reference density for calculating the corrected volume flow
Various pressure transmitters and temperature measuring devices can be ordered from Endress
+Hauser: see "Accessories" section →  64
It is recommended to read in external measured values to calculate the following measured variables:
Corrected volume flow

HART protocol
The measured values are written from the automation system to the measuring device via the HART
protocol. The pressure transmitter must support the following protocol-specific functions:
• HART protocol
• Burst mode

Digital communication
The measured values can be written from the automation system to the measuring via:
• PROFIBUS DP
• Modbus RS485
• EtherNet/IP
• PROFINET

Output
Output signal HART current output

Current output 4-20 mA HART (active)

Maximum output values • DC 24 V (no flow)


• 22.5 mA

Load 0 to 700 Ω

Resolution 0.38 µA

8 Endress+Hauser
Proline Promag P 100

Damping Adjustable: 0.07 to 999 s

Assignable measured • Volume flow


variables • Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Corrected conductivity
• Electronic temperature

Pulse/frequency/switch output

Function Can be set to pulse, frequency or switch output

Version Passive, open collector

Maximum input values • DC 30 V


• 25 mA

Voltage drop For 25 mA: ≤ DC 2 V

Pulse output

Pulse width Adjustable: 0.05 to 2 000 ms

Maximum pulse rate 10 000 Impulse/s

Pulse value Adjustable

Assignable measured • Volume flow


variables • Mass flow
• Corrected volume flow

Frequency output

Output frequency Adjustable: 0 to 10 000 Hz

Damping Adjustable: 0 to 999 s

Pulse/pause ratio 1:1

Assignable measured • Volume flow


variables • Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Corrected conductivity
• Temperature
• Electronic temperature

Switch output

Switching behavior Binary, conductive or non-conductive

Switching delay Adjustable: 0 to 100 s

Endress+Hauser 9
Proline Promag P 100

Number of switching Unlimited


cycles

Assignable functions • Off


• On
• Diagnostic behavior
• Limit value:
– Off
– Volume flow
– Mass flow
– Corrected volume flow
– Flow velocity
– Conductivity
– Corrected conductivity
– Totalizer 1-3
– Temperature
– Electronic temperature
• Flow direction monitoring
• Status
– Empty pipe detection
– Low flow cut off

PROFIBUS DP

Signal encoding NRZ code

Data transfer 9.6 kBaud…12 MBaud

Modbus RS485

Physical interface In accordance with EIA/TIA-485-A standard

Terminating resistor Integrated, can be activated via DIP switch on the transmitter electronics module

EtherNet/IP

Standards In accordance with IEEE 802.3

PROFINET

Standards In accordance with IEEE 802.3

Signal on alarm Depending on the interface, failure information is displayed as follows:

Current output 4 to 20 mA

4 to 20 mA
Failure mode Choose from:
• 4 to 20 mA in accordance with NAMUR recommendation NE 43
• 4 to 20 mA in accordance with US
• Min. value: 3.59 mA
• Max. value: 22.5 mA
• Freely definable value between: 3.59 to 22.5 mA
• Actual value
• Last valid value

10 Endress+Hauser
Proline Promag P 100

Pulse/frequency/switch output

Pulse output

Failure mode Choose from:


• Actual value
• No pulses

Frequency output

Failure mode Choose from:


• Actual value
• 0 Hz
• Defined value: 0 to 12 500 Hz

Switch output

Failure mode Choose from:


• Current status
• Open
• Closed

PROFIBUS DP

Status and alarm Diagnostics in accordance with PROFIBUS PA Profile 3.02


messages

Modbus RS485

Failure mode Choose from:


• NaN value instead of current value
• Last valid value

EtherNet/IP

Device diagnostics Device condition can be read out in Input Assembly

PROFINET

Device diagnostics According to "Application Layer protocol for decentralized periphery", Version 2.3

Local display

Plain text display With information on cause and remedial measures

Backlight Red backlighting indicates a device error.

Status signal as per NAMUR recommendation NE 107

Interface/protocol
• Via digital communication:
– HART protocol
– PROFIBUS DP
– Modbus RS485
– EtherNet/IP
– PROFINET
• Via service interface
CDI-RJ45 service interface

Endress+Hauser 11
Proline Promag P 100

Plain text display With information on cause and remedial measures

Additional information on remote operation →  55

Web server

Plain text display With information on cause and remedial measures

Light emitting diodes (LED)

Status information Status indicated by various light emitting diodes


The following information is displayed depending on the device version:
• Supply voltage active
• Data transmission active
• Device alarm/error has occurred
• EtherNet/IP network available
• EtherNet/IP connection established
• PROFINET network available
• PROFINET connection established
• PROFINET blinking feature

Low flow cut off The switch points for low flow cut off are user-selectable.

Protocol-specific data HART

Manufacturer ID 0x11

Device type ID 0x3A

HART protocol revision 7

Device description files Information and files under:


(DTM, DD) www.endress.com

HART load Min. 250 Ω

12 Endress+Hauser
Proline Promag P 100

Dynamic variables Read out the dynamic variables: HART command 3


The measured variables can be freely assigned to the dynamic variables.
Measured variables for PV (primary dynamic variable)
• Off
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Temperature
• Electronic temperature
Measured variables for SV, TV, QV (secondary, tertiary and quaternary
dynamic variable)
• Volume flow
• Mass flow
• Corrected volume flow
• Flow velocity
• Temperature
• Electronic temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3

Device variables Read out the device variables: HART command 9


The device variables are permanently assigned.
A maximum of 8 device variables can be transmitted:
• 0 = volume flow
• 1 = mass flow
• 2 = corrected volume flow
• 3 = flow velocity
• 4 = conductivity
• 5 = corrected conductivity
• 6 = temperature
• 7 = electronic temperature
• 8 = totalizer 1
• 9 = totalizer 2
• 10 = totalizer 3

PROFIBUS DP

Manufacturer ID 0x11

Ident number 0x1561

Profile version 3.02

Device description files (GSD, Information and files under:


DTM, DD) • www.endress.com
On the product page for the device: Documents/Software → Device drivers
• www.profibus.org

Output values Analog input 1 to 4


(from measuring device to • Volume flow
automation system) • Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Corrected conductivity
• Temperature
• Electronic temperature
Digital input 1 to 2
• Empty pipe detection
• Low flow cut off
• Verification status
Totalizer 1 to 3
• Volume flow
• Mass flow
• Corrected volume flow

Endress+Hauser 13
Proline Promag P 100

Input values Analog output 1 to 2 (fixed assignment)


(from automation system to • External temperature
measuring device) • External density
Digital output 1 to 2 (fixed assignment)
• Digital output 1: switch positive zero return on/off
• Digital output 2: start verification
Totalizer 1 to 3
• Totalize
• Reset and hold
• Preset and hold
• Stop
• Operating mode configuration:
– Net flow total
– Forward flow total
– Reverse flow total

Supported functions • Identification & Maintenance


Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur

Configuration of the device • DIP switches on the I/O electronics module


address • Via operating tools (e.g. FieldCare)

Modbus RS485

Protocol Modbus Applications Protocol Specification V1.1

Device type Slave

Slave address range 1 to 247

Broadcast address range 0

Function codes • 03: Read holding register


• 04: Read input register
• 06: Write single registers
• 08: Diagnostics
• 16: Write multiple registers
• 23: Read/write multiple registers

Broadcast messages Supported by the following function codes:


• 06: Write single registers
• 16: Write multiple registers
• 23: Read/write multiple registers

Supported baud rate • 1 200 BAUD


• 2 400 BAUD
• 4 800 BAUD
• 9 600 BAUD
• 19 200 BAUD
• 38 400 BAUD
• 57 600 BAUD
• 115 200 BAUD

Data transfer mode • ASCII


• RTU

Data access Each device parameter can be accessed via Modbus RS485.

 documentation
For Modbus register information, see "Description of device parameters"

14 Endress+Hauser
Proline Promag P 100

EtherNet/IP

Protocol • The CIP Networks Library Volume 1: Common Industrial Protocol


• The CIP Networks Library Volume 2: EtherNet/IP Adaptation of CIP

Communication type • 10Base-T


• 100Base-TX

Device profile Generic device (product type: 0x2B)

Manufacturer ID 0x49E

Device type ID 0x103A

Baud rates Automatic ¹⁰⁄₁₀₀ Mbit with half-duplex and full-duplex detection

Polarity Auto-polarity for automatic correction of crossed TxD and RxD pairs

Supported CIP connections Max. 3 connections

Explicit connections Max. 6 connections

I/O connections Max. 6 connections (scanner)

Configuration options for • DIP switches on the electronics module for IP addressing
measuring device • Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• Electronic Data Sheet (EDS) integrated in the measuring device

Configuration of the EtherNet • Speed: 10 MBit, 100 MBit, auto (factory setting)
interface • Duplex: half-duplex, full-duplex, auto (factory setting)

Configuration of the device • DIP switches on the electronics module for IP addressing (last octet)
address • DHCP
• Manufacturer-specific software (FieldCare)
• Add-on Profile Level 3 for Rockwell Automation control systems
• Web browser
• EtherNet/IP tools, e.g. RSLinx (Rockwell Automation)

Device Level Ring (DLR) No

Fix Input

RPI 5 ms to 10 s (factory setting: 20 ms)

Exclusive Owner Multicast Instance Size [byte]

Instance configuration: 0x68 398

O → T configuration: 0x66 56

T → O configuration: 0x64 32

Exclusive Owner Multicast Instance Size [byte]

Instance configuration: 0x69 -

O → T configuration: 0x66 56

T → O configuration: 0x64 32

Input only Multicast Instance Size [byte]

Instance configuration: 0x68 398

O → T configuration: 0xC7 -

T → O configuration: 0x64 32

Input only Multicast Instance Size [byte]

Instance configuration: 0x69 -

O → T configuration: 0xC7 -

T → O configuration: 0x64 32

Endress+Hauser 15
Proline Promag P 100

Input Assembly • Current device diagnostics


• Volume flow
• Mass flow
• Corrected volume flow
• Totalizer 1
• Totalizer 2
• Totalizer 3

Configurable Input

RPI 5 ms to 10 s (factory setting: 20 ms)

Exclusive Owner Multicast Instance Size [byte]

Instance configuration: 0x68 398

O → T configuration: 0x66 56

T → O configuration: 0x65 88

Exclusive Owner Multicast Instance Size [byte]

Instance configuration: 0x69 -

O → T configuration: 0x66 56

T → O configuration: 0x65 88

Input only Multicast Instance Size [byte]

Instance configuration: 0x68 398

O → T configuration: 0xC7 -

T → O configuration: 0x65 88

Input only Multicast Instance Size [byte]

Instance configuration: 0x69 -

O → T configuration: 0xC7 -

T → O configuration: 0x65 88

Configurable Input Assembly • Volume flow


• Corrected volume flow
• Mass flow
• Electronic temperature
• Totalizer 1 to 3
• Flow velocity
• Volume flow unit
• Corrected volume flow unit
• Mass flow unit
• Temperature unit
• Unit totalizer 1-3
• Flow velocity unit
• Verification result
• Verification status

 The range of options increases if the measuring device has one or


more application packages.

Fix Output

Output Assembly • Activation of reset totalizers 1-3


• Activation of reference density compensation
• Activation of temperature compensation
• Reset totalizers 1-3
• External density
• Density unit
• External temperature
• Activation verification
• Start verification

16 Endress+Hauser
Proline Promag P 100

Configuration

Configuration Assembly Only the most common configurations are listed below.
• Software write protection
• Mass flow unit
• Mass unit
• Volume flow unit
• Volume unit
• Corrected volume flow unit
• Corrected volume unit
• Density unit
• Reference density unit
• Temperature unit
• Pressure unit
• Length
• Totalizer 1-3:
– Assignment
– Unit
– Operating mode
– Failsafe mode
• Alarm delay

PROFINET

Protocol "Application layer protocol for decentral device periphery and distributed
automation", version 2.3

Conformity class B

Communication type 100 MBit/s

Device profile Application interface identifier 0xF600


Generic device

Manufacturer ID 0x11

Device type ID 0x843A

Device description files (GSD, Information and files under:


DTM) • www.endress.com
On the product page for the device: Documents/Software → Device drivers
• www.profibus.org

Baud rates Automatic 100 Mbit/s with full-duplex detection

Cycle times From 8 ms

Polarity Auto-polarity for automatic correction of crossed TxD and RxD pairs

Supported connections • 1 x AR (Application Relation)


• 1 x Input CR (Communication Relation)
• 1 x Output CR (Communication Relation)
• 1 x Alarm CR (Communication Relation)

Configuration options for • DIP switches on the electronics module, for device name assignment (last
measuring device part)
• Manufacturer-specific software (FieldCare, DeviceCare)
• Web browser
• Device master file (GSD), can be read out via the integrated Web server of
the measuring device

Configuration of the device • DIP switches on the electronics module, for device name assignment (last
name part)
• DCP protocol

Endress+Hauser 17
Proline Promag P 100

Output values Analog Input module (slot 1 to 10)


(from measuring device to • Volume flow
automation system) • Mass flow
• Corrected volume flow
• Flow velocity
• Conductivity
• Corrected conductivity
• Temperature
• Electronic temperature
Discrete Input module (slot 1 to 10)
• Empty pipe detection
• Low flow cut off
Diagnostics Input module (slot 1 to 10)
• Last diagnostics
• Current diagnosis
Totalizer 1 to 3 (slot 11 to 13)
• Volume flow
• Mass flow
• Corrected volume flow
Heartbeat Verification module (fixed assignment)
Verification status (slot 17)

Input values Analog Output module (fixed assignment)


(from automation system to • External density (slot 14)
measuring device) • External temperature (slot 15)
Discrete Output module (fixed assignment)
Activate/deactivate positive zero return (slot 16)
Totalizer 1 to 3 (slot 11 to 13)
• Totalize
• Reset and hold
• Preset and hold
• Stop
• Operating mode configuration:
– Net flow total
– Forward flow total
– Reverse flow total
Heartbeat Verification module (fixed assignment)
Start verification (slot 17)

Supported functions • Identification & Maintenance


Simple device identification via:
– Control system
– Nameplate
• Measured value status
The process variables are communicated with a measured value status
• Blinking feature via the local display for simple device identification and
assignment

Administration of software options


Input/output value Process variable Category Slot

Output value Mass flow Process variable 1…10

Volume flow

Corrected volume flow

Temperature

Conductivity

Corrected conductivity

Electronic temperature

Flow velocity

Current device diagnostics

Previous device diagnostics

18 Endress+Hauser
Proline Promag P 100

Input/output value Process variable Category Slot

Input/output value Totalizer Totalizer 11…13

Input value External density Process monitoring 14

External temperature 15

Flow override 16

Status verification Heartbeat Verification 1) 17

1) Only available with the "Heartbeat" application package.

Startup configuration
Startup configuration If startup configuration is enabled, the configuration of the most important
(NSU) device parameters is taken from the automation system and used.
The following configuration is taken from the automation system:
• Management
– Software revision
– Write protection
• System units
– Mass flow
– Mass
– Volume flow
– Volume
– Corrected volume flow
– Corrected volume
– Density
– Temperature
– Conductivity
• Sensor adjustment
• Process parameter
– Damping (flow, conductivity, temperature)
– Flow override
– Filter options
• Low flow cut off
– Assign process variable
– Switch-on/switch-off point
– Pressure shock suppression
• Empty pipe detection
– Assign process variable
– Limit values
– Response time
• External compensation
– Temperature source
– Density source
– Density value
• Diagnostic settings
• Diagnostic behavior for diverse diagnostic information

Endress+Hauser 19
Proline Promag P 100

Power supply
Terminal assignment Overview: housing version and connection versions

1 2 3

1.1 1.2 1.3 2.1 2.2 3.1 3.2

A
A0019825

A Housing version: compact, aluminum coated


1 Connection version: 4-20 mA HART, pulse/frequency/switch output
1.1 Signal transmission: pulse/frequency/switch output
1.2 Signal transmission: 4-20 mA HART
1.3 Supply voltage
2 Connection version: Modbus RS485, PROFIBUS DP
2.1 Signal transmission
2.2 Supply voltage
3 Connection version: EtherNet/IP and PROFINET
3.1 Signal transmission
3.2 Supply voltage

Transmitter

Connection version 4-20 mA HART with pulse/frequency/switch output


Order code for "Output", option B
Depending on the housing version, the transmitters can be ordered with terminals or device plugs.

Connection methods available


Order code Possible options for order code
"Housing" Power "Electrical connection"
Outputs
supply

Option A Terminals Terminals • Option A: coupling M20x1


• Option B: thread M20x1
• Option C: thread G ½"
• Option D: thread NPT ½"

Option A Device plugs Terminals • Option L: plug M12x1 + thread NPT ½"
(Verweisziel • Option N: plug M12x1 + coupling M20
existiert nicht, • Option P: plug M12x1 + thread G ½"
aber • Option U: plug M12x1 + thread M20
@y.link.required='
true')

20 Endress+Hauser
Proline Promag P 100

Connection methods available


Order code Possible options for order code
"Housing" Power "Electrical connection"
Outputs
supply

Option A Device plugs Device plugs Option Q: 2 x plug M12x1

Order code for "Housing":


Option A: compact, coated aluminum

24 +
_ 3
25

26 +
_ 2
27

1 L+
1
2 L_

A0016888

2 Terminal assignment 4-20 mA HART with pulse/frequency/switch output


1 Power supply: DC 24 V
2 Output 1: 4-20 mA HART (active)
3 Output 2: pulse/frequency/switch output (passive)

Terminal number
Order code
Power supply Output 1 Output 2
"Output"
2 (L-) 1 (L+) 27 (–) 26 (+) 25 (–) 24 (+)

Option B DC 24 V 4-20 mA HART (active) Pulse/frequency/switch


output (passive)

Order code for "Output":


Option B: 4-20 mA HART with pulse/frequency/switch output

Endress+Hauser 21
Proline Promag P 100

PROFIBUS DP connection version


For use in the non-hazardous area and Zone 2/Div. 2

Order code for "Output", option L


Depending on the housing version, the transmitters can be ordered with terminals or device plugs.

Connection methods available


Order code Possible options for order code
"Housing" Power "Electrical connection"
Output
supply

Option A Terminals Terminals • Option A: coupling M20x1


• Option B: thread M20x1
• Option C: thread G ½"
• Option D: thread NPT ½"

Option A Device plugs Terminals • Option L: plug M12x1 + thread NPT ½"
(Verweisziel • Option N: plug M12x1 + coupling M20
existiert nicht, • Option P: plug M12x1 + thread G ½"
aber • Option U: plug M12x1 + thread M20
@y.link.required='
true')

Option A Device plugs Device plugs Option Q: 2 x plug M12x1


(Verweisziel (Verweisziel
existiert nicht, existiert nicht,
aber aber
@y.link.required=' @y.link.required='
true') true')

Order code for "Housing":


Option A: compact, coated aluminum

26 B
27 A
2

1 L+
1
2 L_

A0022716

3 PROFIBUS DP terminal assignment


1 Power supply: DC 24 V
2 PROFIBUS DP

Terminal number

Order code Power supply Output


"Output"
2 (L-) 1 (L+) 26 (RxD/TxD-P) 27 (RxD/TxD-
N)

Option L DC 24 V B A

Order code for "Output":


Option L: PROFIBUS DP, for use in non-hazardous areas and Zone 2/Div. 2

22 Endress+Hauser
Proline Promag P 100

Modbus RS485 connection version


Order code for "Output", option M
Depending on the housing version, the transmitters can be ordered with terminals or device plugs.

Connection methods available


Order code Possible options for order code
"Housing" Power "Electrical connection"
Output
supply

Option A Terminals Terminals • Option A: coupling M20x1


• Option B: thread M20x1
• Option C: thread G ½"
• Option D: thread NPT ½"

Option A Device plugs Terminals • Option L: plug M12x1 + thread NPT ½"
(Verweisziel • Option N: plug M12x1 + coupling M20
existiert nicht, • Option P: plug M12x1 + thread G ½"
aber • Option U: plug M12x1 + thread M20
@y.link.required='
true')

Option A Device plugs Device plugs Option Q: 2 x plug M12x1


(Verweisziel (Verweisziel
existiert nicht, existiert nicht,
aber aber
@y.link.required=' @y.link.required='
true') true')

Order code for "Housing":


Option A: compact, coated aluminum

26 B
27 A
2

1 L+
1
2 L_

A0019528

4 Modbus RS485 terminal assignment


1 Power supply: DC 24 V
2 Modbus RS485

Terminal number
Order code
Power supply Output
"Output"
1 (L+) 2 (L-) 26 (B) 27 (A)

Option M DC 24 V Modbus RS485

Order code for "Output":


Option M: Modbus RS485

Endress+Hauser 23
Proline Promag P 100

Modbus RS485 connection version


For use in the intrinsically safe area. Connection via Safety Barrier Promass 100.

Order code for "Output", option M

24 Endress+Hauser
Proline Promag P 100

EtherNet/IP connection version


Order code for "Output", option N
Depending on the housing version, the transmitters can be ordered with terminals or device plugs.

Connection methods available


Order code Possible options for order code
"Housing" Power "Electrical connection"
Output
supply

Option A Device plugs Terminals • Option L: plug M12x1 + thread NPT ½"
(Verweisziel • Option N: plug M12x1 + coupling M20
existiert nicht, • Option P: plug M12x1 + thread G ½"
aber • Option U: plug M12x1 + thread M20
@y.link.required='
true')

Option A Device plugs Device plugs Option Q: 2 x plug M12x1


(Verweisziel (Verweisziel
existiert nicht, existiert nicht,
aber aber
@y.link.required=' @y.link.required='
true') true')

Order code for "Housing":


Option A: compact, coated aluminum

1 L+
1
2 L_

A0017054

5 EtherNet/IP terminal assignment


1 Power supply: DC 24 V
2 EtherNet/IP

Terminal number
Order code
Power supply Output
"Output"
2 (L-) 1 (L+) Device plug M12x1

Option N DC 24 V EtherNet/IP

Order code for "Output":


Option N: EtherNet/IP

Endress+Hauser 25
Proline Promag P 100

PROFINET connection version


Order code for "Output", option R
Depending on the housing version, the transmitters can be ordered with terminals or device plugs.

Connection methods available


Order code for Possible options for order code
"Housing" Power "Electrical connection"
Output
supply

Option A Device plugs Terminals • Option L: plug M12x1 + thread NPT ½"
→  26 • Option N: plug M12x1 + coupling M20
• Option P: plug M12x1 + thread G ½"
• Option U: plug M12x1 + thread M20

Option A Device plugs Device plugs Option Q: 2 x plug M12x1


→  26 →  26

Order code for "Housing":


Option A: compact, coated aluminum

1 L+
1
2 L_

A0017054

6 PROFINET terminal assignment


1 Power supply: DC 24 V
2 PROFINET

Terminal number
Order code for
Power supply Output
"Output"
2 (L-) 1 (L+) Device plug M12x1

Option R DC 24 V PROFINET

Order code for "Output":


Option R: PROFINET

Pin assignment, device plug Order codes for the M12x1 connectors, see the "Order code for electrical connection" column:
• 4-20 mA HART, pulse/frequency/switch output →  20
• PROFIBUS DP→  22
• Modbus RS485 →  23
• EtherNet/IP →  25
• PROFINET→  26

Supply voltage

For all connection versions (device side)

2 Pin Assignment

1 L+ DC 24 V

2 Not assigned
3 1
3 Not assigned
5 4 L- DC 24 V
4
A0016809
5 Grounding/shielding

26 Endress+Hauser
Proline Promag P 100

Coding Plug/socket

A Plug

The following is recommended as a socket:


• Binder, series 763, part no. 79 3440 35 05
• Alternatively: Phoenix part no. 1669767 SAC-5P-M12MS
– With the order code for "Output", option B: 4-20 mA HART, pulse/frequency/switch output
– With the order code for "Output", option N: EtherNet/IP
• When using the device in a hazardous location: Use a suitably certified socket.

4-20 mA HART with pulse/frequency/switch output

Device plug for signal transmission (device side)

2 Pin Assignment

1 + 4-20 mA HART (active)

2 - 4-20 mA HART (active)


1 3
3 + Pulse/frequency/switch output (passive)
5 4 - Pulse/frequency/switch output (passive)
4
A0016810
5 Grounding/shielding

Coding Plug/socket

A Socket

 •• When
Recommended plug: Binder, series 763, part no. 79 3439 12 05
using the device in a hazardous location, use a suitably certified plug.

PROFIBUS DP
For use in the non-hazardous area and Zone 2/Div. 2.

Device plug for signal transmission (device side)

2 Pin Assignment

1 Not assigned

2 A PROFIBUS DP
1 3
3 Not assigned
5 4 B PROFIBUS DP
4
A0016811
5 Grounding/shielding

Coding Plug/socket

B Socket

 •• When
Recommended plug: Binder, series 763, part no. 79 4449 20 05
using the device in a hazardous location, use a suitably certified plug.

MODBUS RS485

Device plug for signal transmission (device side)

2 Pin Assignment

1 Not assigned

2 A Modbus RS485
1 3
3 Not assigned
5 4 B Modbus RS485
4
A0016811
5 Grounding/shielding

Endress+Hauser 27
Proline Promag P 100

Coding Plug/socket

B Socket

 •• When
Recommended plug: Binder, series 763, part no. 79 4449 20 05
using the device in a hazardous location, use a suitably certified plug.

EtherNet/IP

Device plug for signal transmission (device side)

2 Pin Assignment

1 + Tx

2 + Rx
1 3
3 - Tx

4 - Rx
4
A0016812
Coding Plug/socket

D Socket

 Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
• When using the device in a hazardous location, use a suitably certified plug.

PROFINET

Device plug for signal transmission (device side)

2 Pin Assignment

1 + TD +

2 + RD +
1 3
3 - TD –

4 - RD –
4
A0016812
Coding Plug/socket

D Socket

 Recommended plug:
• Binder, series 763, part no. 99 3729 810 04
• Phoenix, part no. 1543223 SACC-M12MSD-4Q
• When using the device in a hazardous location, use a suitably certified plug.

Supply voltage The power unit must be tested to ensure it meets safety requirements (e.g. PELV, SELV).

Transmitter
For device version with all communication types: DC 20 to 30 V

Power consumption Transmitter

Maximum
Order code for "Output"
Power consumption

Option B: 4-20 mA HART with pulse/frequency/switch output 3.5 W

Option L: PROFIBUS DP 3.5 W

Option M: Modbus RS485 3.5 W

Option N: EtherNet/IP 3.5 W

Option R: PROFINET 3.5 W

28 Endress+Hauser
Proline Promag P 100

Current consumption Transmitter

Maximum Maximum
Order code for "Output"
Current consumption switch-on current

Option B: 4-20mA HART, pul./freq./switch output 145 mA 18 A (< 0.125 ms)

Option L: PROFIBUS DP 145 mA 18 A (< 0.125 ms)

Option M: Modbus RS485 90 mA 10 A (< 0.8 ms)

Option N: EtherNet/IP 145 mA 18 A (< 0.125 ms)

Option R: PROFINET 145 mA 18 A (< 0.125 ms)

Power supply failure • Totalizers stop at the last value measured.


• Depending on the device version, the configuration is retained in the device memory or in the
plug-in memory (HistoROM DAT).
• Configuration is retained in the plug-in memory (HistoROM DAT).
• Error messages (incl. total operated hours) are stored.

Electrical connection Connecting the transmitter

1 2
A0019824

A Housing version: compact, aluminum coated


1 Cable entry or device plug for signal transmission
2 Cable entry or device plug for supply voltage

• Terminal assignment→  20
• Pin assignment, device plug→  26
In the case of device versions with a connector, the transmitter housing does not need to be
opened to connect the signal cable or power supply cable.

Endress+Hauser 29
Proline Promag P 100

Connection examples

Current output 4 to 20 mA HART

1 2 3
4...20 mA

4 5
A0029055

7 Connection example for 4 to 20 mA HART current output (active)


1 Automation system with current input (e.g. PLC)
2 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications →  34
3 Connection for HART operating devices →  55
4 Resistor for HART communication (≥ 250 Ω): observe maximum load
5 Analog display unit: observe maximum load
6 Transmitter

1 2 3 4

4...20 mA

A0028762

8 Connection example for 4 to 20 mA HART current output (passive)


1 Automation system with current input (e.g. PLC)
2 Power supply
3 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications →  34
4 Analog display unit: observe maximum load
5 Transmitter

Pulse/frequency output

1 2

12345
A0028761

9 Connection example for pulse/frequency output (passive)


1 Automation system with pulse/frequency input (e.g. PLC)
2 Power supply
3 Transmitter: Observe input values

30 Endress+Hauser
Proline Promag P 100

Switch output

1 2

A0028760

 10 Connection example for switch output (passive)


1 Automation system with switch input (e.g. PLC)
2 Power supply
3 Transmitter: Observe input values

PROFIBUS DP

1 2 3

A A
4
B
B

A
4
B

A0028765

 11 Connection example for PROFIBUS DP, non-hazardous area and Zone 2/Div. 2
1 Control system (e.g. PLC)
2 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications
3 Transmitter

If baud rates > 1.5 MBaud an EMC cable entry must be used and the cable shield must continue
as far as the terminal wherever possible.

Endress+Hauser 31
Proline Promag P 100

Modbus RS485

1 2 3

A A
4
B
B

A
4
B

A0028765

 12 Connection example for Modbus RS485, non-hazardous area and Zone 2/Div. 2
1 Control system (e.g. PLC)
2 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable
specifications
3 Distribution box
4 Transmitter

EtherNet/IP

1 2 3 4

A0028767

 13 Connection example for EtherNet/IP


1 Control system (e.g. PLC)
2 Ethernet switch
3 Observe cable specifications
4 Device plug
5 Transmitter

PROFINET

1 2 3 4

A0016805

 14 Connection example for PROFINET


1 Control system (e.g. PLC)
2 Ethernet switch
3 Observe cable specifications
4 Device plug
5 Transmitter

32 Endress+Hauser
Proline Promag P 100

HART input

1 2 3 4

4...20 mA
+
5
-

-
+ 6

A0019828

 15 Connection example for HART input (burst mode) via current output (active)
1 Cable shield, observe cable specifications
2 Resistor for HART communication (≥ 250 Ω): observe maximum load
3 Connection for HART operating devices
4 Analog display unit
5 Transmitter
6 Sensor for external measured variable

1 2 3 4 5

4...20 mA
+
+ 6
-
-
-
+
-
7
+
4...20 mA

2 3 4 5
A0019830

 16 Connection example for HART input (master mode) via current output (active)
1 Automation system with current input (e.g. PLC).
Prerequisite: automation system with HART version 6, HART commands 113 and 114 can be processed.
2 Cable shield, observe cable specifications
3 Resistor for HART communication (≥ 250 Ω): observe maximum load
4 Connection for HART operating devices
5 Analog display unit
6 Transmitter
7 Sensor for external measured variable

Potential equalization Requirements


Please consider the following to ensure correct measurement:
• Same electrical potential for the medium and sensor
• Company-internal grounding concepts
• Pipe material and grounding
For devices intended for use in hazardous locations, please observe the guidelines in the
Ex documentation (XA).

Terminals Transmitter
Spring terminals for wire cross-sections0.5 to 2.5 mm2 (20 to 14 AWG)

Endress+Hauser 33
Proline Promag P 100

Cable entries • Cable gland: M20 × 1.5 with cable 6 to 12 mm (0.24 to 0.47 in)
• Thread for cable entry:
– M20
– G ½"
– NPT ½"

Cable specification Permitted temperature range


• The installation guidelines that apply in the country of installation must be observed.
• The cables must be suitable for the minimum and maximum temperatures to be expected.

Power supply cable


Standard installation cable is sufficient.

Signal cable

Current output 4 to 20 mA HART


A shielded cable is recommended. Observe grounding concept of the plant.

Pulse/frequency/switch output
Standard installation cable is sufficient.

PROFIBUS DP
The IEC 61158 standard specifies two types of cable (A and B) for the bus line which can be used for
every transmission rate. Cable type A is recommended.

Cable type A

Characteristic impedance 135 to 165 Ω at a measuring frequency of 3 to 20 MHz

Cable capacitance < 30 pF/m

Wire cross-section > 0.34 mm2 (22 AWG)

Cable type Twisted pairs

Loop resistance ≤110 Ω/km

Signal damping Max. 9 dB over the entire length of the cable cross-section

Shield Copper braided shielding or braided shielding with foil shield. When grounding
the cable shield, observe the grounding concept of the plant.

Modbus RS485
The EIA/TIA-485 standard specifies two types of cable (A and B) for the bus line which can be used
for every transmission rate. Cable type A is recommended.

Cable type A

Characteristic impedance 135 to 165 Ω at a measuring frequency of 3 to 20 MHz

Cable capacitance < 30 pF/m

Wire cross-section > 0.34 mm2 (22 AWG)

Cable type Twisted pairs

Loop resistance ≤110 Ω/km

Signal damping Max. 9 dB over the entire length of the cable cross-section

Shield Copper braided shielding or braided shielding with foil shield. When grounding
the cable shield, observe the grounding concept of the plant.

34 Endress+Hauser
Proline Promag P 100

EtherNet/IP
The standard ANSI/TIA/EIA-568-B.2 Annex specifies CAT 5 as the minimum category for a cable
used for EtherNet/IP. CAT 5e and CAT 6 are recommended.
For more information on planning and installing EtherNet/IP networks, please refer to the
"Media Planning and Installation Manual. EtherNet/IP" of ODVA Organization

PROFINET
Standard IEC 61156-6 specifies CAT 5 as the minimum category for a cable used for PROFINET. CAT
5e and CAT 6 are recommended.
For more information on planning and installing PROFINET networks, see: "PROFINET Cabling
and Interconnection Technology", Guideline for PROFINET

Performance characteristics
Reference operating • Error limits following DIN EN 29104, in future ISO 20456
conditions • Water, typically +15 to +45 °C (+59 to +113 °F); 0.5 to 7 bar (73 to 101 psi)
• Data as indicated in the calibration protocol
• Accuracy based on accredited calibration rigs according to ISO 17025

Maximum measured error Error limits under reference operating conditions


o.r. = of reading
Volume flow
• ±0.5 % o.r. ± 1 mm/s (0.04 in/s)
• Optional: ±0.2 % o.r. ± 2 mm/s (0.08 in/s)
Fluctuations in the supply voltage do not have any effect within the specified range.

[%]
2.5
2.0
0.5 %
1.5
0.2 %
1.0
0.5
0
0 1 2 4 6 8 10 [m/s]
v
0 5 10 15 20 25 30 32 [ft/s]
A0005531

 17 Maximum measured error in % o.r.

Electrical conductivity
Max. measured error not specified.

Accuracy of outputs
The output accuracy must be factored into the measured error if analog outputs are used, but
can be ignored for fieldbus outputs (e.g. Modbus RS485, EtherNet/IP).
The outputs have the following base accuracy specifications.

Current output

Accuracy Max. ±5 µA

Endress+Hauser 35
Proline Promag P 100

Pulse/frequency output
o.r. = of reading

Accuracy Max. ±50 ppm o.r. (over the entire ambient temperature range)

Repeatability o.r. = of reading


Volume flow
Max. ±0.1 % o.r. ± 0.5 mm/s (0.02 in/s)
Electrical conductivity
Max. ±5 % o.r.

Temperature measurement T90 < 15 s


response time

Influence of ambient Current output


temperature
o.r. = of reading

Temperature coefficient Max. ±0.005 % o.r./°C

Pulse/frequency output

Temperature coefficient No additional effect. Included in accuracy.

Installation
No special measures such as supports etc. are necessary. External forces are absorbed by the
construction of the device.

Mounting location
h

A0029343

Preferably install the sensor in an ascending pipe, and ensure a sufficient distance to the next pipe
elbow: h ≥ 2 × DN

Installation in down pipes


Install a siphon with a vent valve downstream of the sensor in down pipes whose length h ≥
5 m (16.4 ft). This precaution is to avoid low pressure and the consequent risk of damage to the
measuring tube. This measure also prevents the system losing prime.

36 Endress+Hauser
Proline Promag P 100

1
2

h
A0028981

 18 Installation in a down pipe


1 Vent valve
2 Pipe siphon
h Length of down pipe

Installation in partially filled pipes


A partially filled pipe with a gradient necessitates a drain-type configuration.

N
xD
³2
N
xD
³5

A0029257

For heavy sensors DN ≥ 350 (14")

A0016276

Orientation The direction of the arrow on the sensor nameplate helps you to install the sensor according to the
flow direction (direction of medium flow through the piping).

Orientation Recommendation

A Vertical orientation

A0015591

1)
B Horizontal orientation, transmitter at
top

A0015589

Endress+Hauser 37
Proline Promag P 100

Orientation Recommendation
2) 3)
C Horizontal orientation, transmitter at
bottom

A0015590

D Horizontal orientation, transmitter at


side
A0015592

1) Applications with low process temperatures may decrease the ambient temperature. To maintain the
minimum ambient temperature for the transmitter, this orientation is recommended.
2) Applications with high process temperatures may increase the ambient temperature. To maintain the
maximum ambient temperature for the transmitter, this orientation is recommended.
3) To prevent the electronics module from overheating in the case of a sharp rise in temperature (e.g. CIP- or
SIP processes), install the device with the transmitter component pointing downwards.

Horizontal
• Ideally, the measuring electrode plane should be horizontal. This prevents brief insulation of the
two measuring electrodes by entrained air bubbles.
• Empty pipe detection only works if the transmitter housing is pointing upwards as otherwise there
is no guarantee that the empty pipe detection function will actually respond to a partially filled or
empty measuring tube.

2 2

A0029344

1 EPD electrode for empty pipe detection


2 Measuring electrodes for signal detection
3 Reference electrode for potential equalization

Measuring devices with tantalum or platinum electrodes can be ordered without an EPD
electrode. In this case, empty pipe detection is performed via the measuring electrodes.

Inlet and outlet runs If possible, install the sensor upstream from fittings such as valves, T-pieces or elbows.
Observe the following inlet and outlet runs to comply with accuracy specifications:

≥ 5 × DN ≥ 2 × DN

A0028997

 19 Order code for "Design", option A "Insertion length short, ISO/DVGW until DN400, DN450-2000 1:1" and
order code for "Design", option B "Insertion length long, ISO/DVGW until DN400, DN450-2000 1:1.3"

38 Endress+Hauser
Proline Promag P 100

≥ 0 × DN

A0032859

 20 Order code for "Design", option C "Insertion length short ISO/DVGW until DN300, w/o inlet and outlet
runs, constricted meas.tube"

Adapters Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in larger-
diameter pipes. The resultant increase in the rate of flow improves measuring accuracy with very
slow-moving fluids.
The nomogram shown here can be used to calculate the pressure loss caused by reducers and
expanders:
• Calculate the ratio of the diameters d/D.
• From the nomogram read off the pressure loss as a function of flow velocity (downstream from
the reduction) and the d/D ratio.
The nomogram only applies to liquids with a viscosity similar to that of water.

100 [mbar]
8 m/s
7 m/s
6 m/s
5 m/s

4 m/s

3 m/s 10

max. 8° 2 m/s

d D
1 m/s 1

0.5 0.6 0.7 0.8 0.9 d/D


A0029002

Environment
Ambient temperature range Transmitter –40 to +60 °C (–40 to +140 °F)

Local display –20 to +60 °C (–4 to +140 °F), the readability of the display may be
impaired at temperatures outside the temperature range.

Sensor • Process connection material, carbon steel:


–10 to +60 °C (+14 to +140 °F)
• Process connection material, stainless steel:
–40 to +60 °C (–40 to +140 °F)

Liner Do not exceed or fall below the permitted temperature range of the liner .

Endress+Hauser 39
Proline Promag P 100

If operating outdoors:
• Install the measuring device in a shady location.
• Avoid direct sunlight, particularly in warm climatic regions.
• Avoid direct exposure to weather conditions.

Storage temperature The storage temperature corresponds to the operating temperature range of the measuring
transmitter and the appropriate measuring sensors.→  39
• Protect the measuring device against direct sunlight during storage in order to avoid unacceptably
high surface temperatures.
• Select a storage location where moisture cannot collect in the measuring device as fungus or
bacteria infestation can damage the liner.
• If protection caps or protective covers are mounted these should never be removed before
installing the measuring device.

Degree of protection Transmitter and sensor


• As standard: IP66/67, type 4X enclosure
• With the order code for "Sensor options", option CM: IP69 can also be ordered
• When housing is open: IP20, type 1 enclosure
• Display module: IP20, type 1 enclosure

Vibration resistance • Vibration, sinusoidal according to IEC 60068-2-6


– 2 to 8.4 Hz, 3.5 mm peak
– 8.4 to 2 000 Hz, 1 g peak
• Vibration broad-band random, according to IEC 60068-2-64
– 10 to 200 Hz, 0.003 g2/Hz
– 200 to 2 000 Hz, 0.001 g2/Hz
– Total: 1.54 g rms

Shock resistance Shock, half-sine according to IEC 60068-2-27


6 ms 30 g

Impact resistance Rough handling shocks according to IEC 60068-2-31

Mechanical load • Protect the transmitter housing against mechanical effects, such as shock or impact.
• Never use the transmitter housing as a ladder or climbing aid.

Electromagnetic • Depends on the communication protocol:


compatibility (EMC) – HART, PROFIBUS DP, EtherNet/IP:
As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21)
– Modbus RS485:
As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21)
– PROFINET: as per IEC/EN 61326
• Complies with emission limits for industry as per EN 55011 (Class A)
• Device version with PROFIBUS DP: Complies with emission limits for industry as per EN 50170
Volume 2, IEC 61784
The following applies for PROFIBUS DP: If baud rates > 1.5 MBaud, an EMC cable entry must be
used and the cable shield must continue as far as the terminal wherever possible.
Details are provided in the Declaration of Conformity.

Process
Medium temperature range • –20 to +150 °C (–4 to +302 °F) for PFA, DN 25 to 200 (1 to 8")
• –20 to +180 °C (–4 to +356 °F) for PFA high-temperature, DN 25 to 200 (1 to 8")
• –40 to +130 °C (–40 to +266 °F) for PTFE, DN 15 to 600 (½ to 24")

40 Endress+Hauser
Proline Promag P 100

TA [°F] [°C]
140 60

100 40

20 2 3

0 PFA
-20
1
PTFE
-40 -40
-40 -20 0 20 40 60 80 100 120 140 160 180 [°C]
TF
-40 0 100 200 300 360 [°F]
A0019742

TA Ambient temperature

TF Medium temperature

1 Gray area: the ambient and fluid temperature range of –10 to –40 °C (–14 to –40 °F) applies to stainless
flanges only

2 Hatched area: harsh environment and IP68 only up to +130 °C (+266 °F)

3 Dark-gray area: high-temperature version with insulation

Conductivity ≥ 5 μS/cm for liquids in general. Stronger filter damping is required for very low conductivity values.

Pressure-temperature The following pressure/temperature diagrams apply to all pressure-bearing parts of the device and
ratings not just the process connection. The diagrams show the maximum permissible medium pressure
depending on the specific medium temperature.

Process connection: flange according to EN 1092-1 (DIN 2501)

[psi] [bar]
600 40
PN 40
500 35
30
400
25
PN 25
300 20

200 15
PN 16
10
100 PN 10
5
PN 6
0 0
-40 -20 0 20 40 60 80 100 120 140 160 180 [°C]

-40 0 100 200 300 360 [°F]


A0029390-EN

 21 Process connection material: carbon steel, FE410WB/S235JRG2; Alloy C22, 2.4602 (UNS N06022)

Endress+Hauser 41
Proline Promag P 100

[psi] [bar]
600 40
PN 40
500 35
30
400
25
PN 25
300 20

200 15 PN 16
10
100 PN 10
5 PN 6
0 0
-40 -20 0 20 40 60 80 100 120 140 160 180 [°C]

-40 0 100 200 300 360 [°F]


A0029391-EN

 22 Process connection material: stainless steel, 1.4571 (F316L)

Process connection: flange according to ASME B16.5

[psi] [bar]
900 60
800
700 50 Class 300
600 40
500
30
400
300 20
200 Class 150
10
100
0 0
-40 -20 0 20 40 60 80 100 120 140 160 180 [°C]

-40 0 100 200 300 360 [°F]


A0029393-EN

 23 Process connection material: carbon steel, A105

[psi] [bar]
900 60
800
700 50
600 40
Class 300
500
30
400
300 20
200 Class 150
10
100
0 0
-40 -20 0 20 40 60 80 100 120 140 160 180 [°C]

-40 0 100 200 300 360 [°F]


A0029394-EN

 24 Process connection material: stainless steel, F316L

42 Endress+Hauser
Proline Promag P 100

Process connection: flange according to JIS B2220

[psi] [bar]
30
400

300 20
20K
200
10
100 10K

0 0
-40 -20 0 20 40 60 80 100 120 140 160 180 [°C]

-40 0 100 200 300 360 [°F]


A0029397-EN

 25 Process connection material: stainless steel, 1.0425 (F316L); carbon steel, S235JRG2/HII

Process connection: flange according to AS 2129 (Table E) or AS 4087 (PN 16)

[psi] [bar]
30
400

300 20

200
Table E
10
100

0 0
-40 -20 0 20 40 60 80 100 120 140 160 180 [°C]

-40 0 100 200 300 360 [°F]


A0029398-EN

 26 Process connection material: carbon steel, A105/S235JRG2/S275JR

Pressure tightness "–" = no specifications possible

Liner: PFA
Nominal diameter Limit values for absolute pressure in [mbar] ([psi]) for fluid temperatures:

[mm] [in] +25 °C (+77 °F) +80 °C (+176 °F) +100 to +180 °C
(+212 to +356 °F)

25 1 0 (0) 0 (0) 0 (0)

32 – 0 (0) 0 (0) 0 (0)

40 1½ 0 (0) 0 (0) 0 (0)

50 2 0 (0) 0 (0) 0 (0)

65 – 0 (0) – 0 (0)

80 3 0 (0) – 0 (0)

100 4 0 (0) – 0 (0)

125 – 0 (0) – 0 (0)

150 6 0 (0) – 0 (0)

200 8 0 (0) – 0 (0)

Endress+Hauser 43
Proline Promag P 100

Liner: PTFE
Nominal diameter Limit values for absolute pressure in [mbar] ([psi]) for fluid temperatures:

[mm] [in] +25 °C (+77 °F) +80 °C (+176 °F) +100 °C (+212 °F) +130 °C (+266 °F)

15 ½ 0 (0) 0 (0) 0 (0) 100 (1.45)

25 1 0 (0) 0 (0) 0 (0) 100 (1.45)

32 – 0 (0) 0 (0) 0 (0) 100 (1.45)

40 1½ 0 (0) 0 (0) 0 (0) 100 (1.45)

50 2 0 (0) 0 (0) 0 (0) 100 (1.45)

65 – 0 (0) – 40 (0.58) 130 (1.89)

80 3 0 (0) – 40 (0.58) 130 (1.89)

100 4 0 (0) – 135 (1.96) 170 (2.47)

125 – 135 (1.96) – 240 (3.48) 385 (5.58)

150 6 135 (1.96) – 240 (3.48) 385 (5.58)

200 8 200 (2.90) – 290 (4.21) 410 (5.95)

250 10 330 (4.79) – 400 (5.80) 530 (7.69)

300 12 400 (5.80) – 500 (7.25) 630 (9.14)

350 14 470 (6.82) – 600 (8.70) 730 (10.6)

400 16 540 (7.83) – 670 (9.72) 800 (11.6)

450 18

500 20 No negative pressure permitted!

600 24

Flow limit The diameter of the pipe and the flow rate determine the nominal diameter of the sensor. The
optimum velocity of flow is between 2 to 3 m/s (6.56 to 9.84 ft/s). Also match the velocity of flow
(v) to the physical properties of the fluid:
• v < 2 m/s (6.56 ft/s): for abrasive fluids (e.g. potter's clay, lime milk, ore slurry)
• v > 2 m/s (6.56 ft/s): for fluids producing buildup (e.g. wastewater sludge)
A necessary increase in the flow velocity can be achieved by reducing the sensor nominal
diameter.
For an overview of the full scale values for the measuring range, see the "Measuring range"
section →  6

Pressure loss • No pressure loss occurs if the sensor is installed in a pipe with the same nominal diameter.
• Pressure losses for configurations incorporating adapters according to DIN EN 545 →  39

44 Endress+Hauser
Proline Promag P 100

[psi] [mbar]
7 500

450 DN50 DN65


6
(2") (2½")
400
5 350 DN80
300 (3")
4
250
3
200

2 150
100
1
50
0 0
0 10 20 30 40 50 60 70 80 90 100 110 120 [m³/h]

0 50 100 150 200 250 300 350 400 450 500 [gal/min]
A0032667-EN

 27 Pressure loss DN 50 to 80 (2 to 3") in the case of order code for "Design", option C "Insertion length short
ISO/DVGW to DN300, without inlet/outlet runs, constricted meas.tube"

[psi] [mbar]
13 900
12
800 DN250
11 DN125 DN150 DN200 (10")
10 700 (5") (6") (8")
9 600 DN100
8 (4")
7 500
DN300
6 400 (12")
5
4 300
3 200
2
100
1
0 0
0 200 400 600 800 1000 1200 1400 1600 1800 [m³/h]

0 1000 2000 3000 4000 5000 6000 7000 8000 [gal/min]


A0032668-EN

 28 Pressure loss DN 100 to 300 (4 to 12") in the case of order code for "Design", option C "Insertion length
short ISO/DVGW to DN300, without inlet/outlet runs, constricted meas.tube"

System pressure

A0028777

Endress+Hauser 45
Proline Promag P 100

Never install the sensor on the pump suction side in order to avoid the risk of low pressure, and thus
damage to the liner.
Furthermore, install pulse dampers if reciprocating, diaphragm or peristaltic pumps are used.

• Information on the liner's resistance to partial vacuum →  43


• Information on the shock resistance of the measuring system →  40
• Information on the vibration resistance of the measuring system →  40

Vibrations

L
A0029004

 29 Measures to avoid device vibrations (L > 10 m (33 ft))

In the event of very strong vibrations, the pipe and sensor must be supported and fixed.
• Information on the shock resistance of the measuring system →  40
• Information on the vibration resistance of the measuring system →  40

Mechanical construction
Dimensions in SI units Compact version

B
A C D
E
G
F

K
H L
A0019491

Order code for "Housing", option A "Compact, coated aluminum"


DN A B C D E 1) 2) F G 1) 2) H K L 3)

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

15 136 147.5 93.5 54 197 84 281 120 94 200

25 136 147.5 93.5 54 197 84 281 120 94 200

32 136 147.5 93.5 54 197 84 281 120 94 200

40 136 147.5 93.5 54 197 84 281 120 94 200

50 136 147.5 93.5 54 197 84 281 120 94 200

46 Endress+Hauser
Proline Promag P 100

DN A B C D E 1) 2) F G 1) 2) H K L 3)

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

65 136 147.5 93.5 54 222 109 331 180 94 200

80 136 147.5 93.5 54 222 109 331 180 94 200

100 136 147.5 93.5 54 222 109 331 180 94 250

125 136 147.5 93.5 54 262 150 412 260 140 250

150 136 147.5 93.5 54 262 150 412 260 140 300

200 136 147.5 93.5 54 287 180 467 324 156 350

250 136 147.5 93.5 54 312 205 517 400 166 450

300 136 147.5 93.5 54 337 230 567 460 166 500

1) For order code for "Sensor option", option CG "Sensor extension neck": values + 110 mm
2) If using a display, order code for "Display; operation", option B: values + 28 mm
3) The length (L) is always the same, irrespective of the selected pressure rating.

B
A C D

E
G
F
K
H L
A0019493

DN A B C D E 1) 2) F G 1) 2) H K L 3)

[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]

350 136 147.5 93.5 54 399 282 681 564 290 550

400 136 147.5 93.5 54 425 308 733 616 290 600

450 136 147.5 93.5 54 450 333 783 666 290 650

500 136 147.5 93.5 54 476 359 835 717 290 650

600 136 147.5 93.5 54 528 411 939 821 290 780

1) For order code for "Sensor option", option CG "Sensor extension neck": values + 110 mm
2) If using a display, order code for "Display; operation", option B: values + 28 mm
3) The length (L) is always the same, irrespective of the selected pressure rating.

Endress+Hauser 47
Proline Promag P 100

Accessories

Ground disk for flange connection

DN £ 300 (12") DN ³ 350 (14")


ÆE
ÆE

D
D ÆB A
ÆB Æ ÆC
A ÆC
Æ

t t
A0003221

DN 1) A B C D E t

EN (DIN), JIS, AS 2) PFA, PTFE

[mm] [mm] [mm] [mm] [mm] [mm] [mm]

15 16 43 61.5 73 6.5 2

25 26 62 77.5 87.5 6.5 2

32 35 80 87.5 94.5 6.5 2

40 41 82 101 103 6.5 2

50 52 101 115.5 108 6.5 2

65 68 121 131.5 118 6.5 2

80 80 131 154.5 135 6.5 2

100 104 156 186.5 153 6.5 2

125 130 187 206.5 160 6.5 2

150 158 217 256 184 6.5 2

200 206 267 288 205 6.5 2

250 260 328 359 240 6.5 2


3)
300 312 375 413 273 6.5 2
4)
300 310 375 404 268 6.5 2
3)
350 343 433 479 365 9.0 2
3)
400 393 480 542 395 9.0 2
3)
450 439 538 583 417 9.0 2

500 3) 493 592 650 460 9.0 2

600 3) 593 693 766 522 9.0 2

1) Ground disks DN 15 to 250 (½ to 10") can be used for all available flange standards/pressure ratings.
2) For flanges to AS, only DN 25 and DN 50 are available.
3) PN 10/16
4) PN 25, JIS 10K/20K

48 Endress+Hauser
Proline Promag P 100

Dimensions in US units Dimensions in US units

B
A C D

E
G
F
K
H L
A0019491

Order code for "Housing", option A "Compact, coated aluminum"


DN A B C D E 1) 2) F G 1) 2) H K L 3)

[in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in]

½ 5.35 5.81 3.68 2.13 7.76 3.31 11.1 4.72 3.70 7.87

1 5.35 5.81 3.68 2.13 7.76 3.31 11.1 4.72 3.70 7.87

1½ 5.35 5.81 3.68 2.13 7.76 3.31 11.1 4.72 3.70 7.87

2 5.35 5.81 3.68 2.13 7.76 3.31 11.1 4.72 3.70 7.87

3 5.35 5.81 3.68 2.13 8.74 4.29 13.0 7.09 3.70 7.87

4 5.35 5.81 3.68 2.13 8.74 4.29 13.0 7.09 3.70 9.84

6 5.35 5.81 3.68 2.13 10.3 5.91 16.2 10.2 5.51 11.8

8 5.35 5.81 3.68 2.13 11.3 7.09 18.4 12.8 6.14 13.8

10 5.35 5.81 3.68 2.13 12.3 8.07 20.4 15.8 6.54 17.7

12 5.35 5.81 3.68 2.13 13.3 9.06 22.3 18.1 6.54 19.7

1) For order code for "Sensor option", option CG "Sensor extension neck": values + 4.33 in
2) If using a display, order code for "Display; operation", option B: values + 1.1 in
3) The length (L) is always the same, irrespective of the selected pressure rating.

Endress+Hauser 49
Proline Promag P 100

B
A C D

E
G
F
K
H L
A0019493

DN A B C D E 1) 2) F G 1) 2) H K L 3)

[in] [in] [in] [in] [in] [in] [in] [in] [in] [in] [in]

14 5.35 5.81 3.68 2.13 15.7 11.1 26.8 22.2 11.4 21.7

16 5.35 5.81 3.68 2.13 16.7 12.1 28.9 24.3 11.4 23.6

18 5.35 5.81 3.68 2.13 17.7 13.1 30.8 26.2 11.4 25.6

20 5.35 5.81 3.68 2.13 18.7 14.1 32.9 28.2 11.4 25.6

24 5.35 5.81 3.68 2.13 20.8 16.2 37.0 32.3 11.4 30.7

1) For high temperature version: values + 4.33 in


2) If using a display, order code for "Display; operation", option B: values + 1.1 in
3) The length (L) is always the same, irrespective of the selected pressure rating.

Accessories

Ground disk for flange connection

DN £ 300 (12") DN ³ 350 (14")


ÆE
ÆE
D
D

ÆB A
ÆB Æ ÆC
A ÆC
Æ

t t
A0003221

50 Endress+Hauser
Proline Promag P 100

DN 1) A B C D E t

ASME PFA, PTFE

[in] [in] [in] [in] [in] [in] [in]

½ 0.63 1.69 2.42 2.87 0.26 0.08

1 1.02 2.44 3.05 3.44 0.26 0.08

1½ 1.61 3.23 3.98 4.06 0.26 0.08

2 2.05 3.98 4.55 4.25 0.26 0.08

3 3.15 5.16 6.08 5.31 0.26 0.08

4 4.09 6.14 7.34 6.02 0.26 0.08

6 6.22 8.54 10.08 7.24 0.26 0.08

8 8.11 10.51 11.34 8.07 0.26 0.08

10 10.24 12.91 14.13 9.45 0.26 0.08

12 12.28 14.76 16.26 10.75 0.26 0.08

14 13.50 17.05 18.86 14.37 0.35 0.08

16 15.47 18.90 21.34 15.55 0.35 0.08

18 17.28 21.18 22.95 16.42 0.35 0.08

20 19.41 23.31 25.59 18.11 0.35 0.08

24 23.35 27.28 30.16 20.55 0.35 0.08

1) Ground disks can be used for all available pressure ratings.

Weight All values (weight exclusive of packaging material) refer to devices for standard pressure ratings.
Weight specifications including transmitter: order code for "Housing", option A "Compact, aluminum
coated".
Different values due to different transmitter versions:

Compact version
• Including the transmitter
• High-temperature version + 1.5 kg (3.31 lb)
• Weight specifications apply to standard pressure ratings and without packaging material.

Weight in SI units

Nominal diameter EN (DIN), AS 1) ASME JIS

[mm] [in] Pressure rating [kg] Pressure rating [kg] Pressure rating [kg]

15 ½ PN 40 4.5 Class 150 4.5 10K 4.5

25 1 PN 40 5.3 Class 150 5.3 10K 5.3

32 – PN 40 6 Class 150 – 10K 5.3

40 1½ PN 40 7.4 Class 150 7.4 10K 6.3

50 2 PN 40 8.6 Class 150 8.6 10K 7.3

65 – PN 16 10 Class 150 – 10K 9.1

80 3 PN 16 12 Class 150 12 10K 10.5

100 4 PN 16 14 Class 150 14 10K 12.7

125 – PN 16 19.5 Class 150 – 10K 19

150 6 PN 16 23.5 Class 150 23.5 10K 22.5

200 8 PN 10 43 Class 150 43 10K 39.9

250 10 PN 10 63 Class 150 73 10K 67.4

300 12 PN 10 68 Class 150 108 10K 70.3

Endress+Hauser 51
Proline Promag P 100

Nominal diameter EN (DIN), AS 1) ASME JIS

[mm] [in] Pressure rating [kg] Pressure rating [kg] Pressure rating [kg]

350 14 PN 10 103 Class 150 173 10K 79

400 16 PN 10 118 Class 150 203 10K 100

450 18 PN 10 159 Class 150 253 10K 128

500 20 PN 10 154 Class 150 283 10K 142

600 24 PN 10 206 Class 150 403 10K 188

1) For flanges to AS, only DN 25 and 50 are available.

Weight in US units

Nominal diameter ASME

[mm] [in] Pressure rating [lbs]

15 ½ Class 150 9.92

25 1 Class 150 11.7

40 1½ Class 150 16.3

50 2 Class 150 19.0

80 3 Class 150 26.5

100 4 Class 150 30.9

150 6 Class 150 51.8

200 8 Class 150 94.8

250 10 Class 150 161.0

300 12 Class 150 238.1

350 14 Class 150 381.5

400 16 Class 150 447.6

450 18 Class 150 557.9

500 20 Class 150 624.0

600 24 Class 150 888.6

Measuring tube specification Nominal Pressure rating Process connection internal diameter
diameter

EN ASME AS 2129 AS 4087 JIS PFA PTFE


(DIN)

[mm] [in] [bar] [psi] [bar] [bar] [bar] [mm] [in] [mm] [in]

15 ½ PN 40 Class 150 – – 20K – – 15 0.59

25 1 PN 40 Class 150 Table E – 20K 23 0.91 26 1.02

32 – PN 40 – – – 20K 32 1.26 35 1.38

40 1½ PN 40 Class 150 – – 20K 36 1.42 41 1.61

50 2 PN 40 Class 150 Table E PN 16 10K 48 1.89 52 2.05

65 – PN 16 – – – 10K 63 2.48 67 2.64

80 3 PN 16 Class 150 – – 10K 75 2.95 80 3.15

100 4 PN 16 Class 150 – – 10K 101 3.98 104 4.09

125 – PN 16 – – – 10K 126 4.96 129 5.08

150 6 PN 16 Class 150 – – 10K 154 6.06 156 6.14

200 8 PN 10 Class 150 – – 10K 201 7.91 202 7.95

52 Endress+Hauser
Proline Promag P 100

Nominal Pressure rating Process connection internal diameter


diameter

EN ASME AS 2129 AS 4087 JIS PFA PTFE


(DIN)

[mm] [in] [bar] [psi] [bar] [bar] [bar] [mm] [in] [mm] [in]

250 10 PN 10 Class 150 – – 10K – – 256 10.1

300 12 PN 10 Class 150 – – 10K – – 306 12.0

350 14 PN 10 Class 150 – – 10K – – 337 13.3

400 16 PN 10 Class 150 – – 10K – – 387 15.2

450 18 PN 10 Class 150 – – 10K – – 432 17.0

500 20 PN 10 Class 150 – – 10K – – 487 19.2

600 24 PN 10 Class 150 – – 10K – – 593 23.3

Materials Transmitter housing


• Order code for "Housing", option A "Compact, aluminum coated":
Aluminum, AlSi10Mg, coated
• Window material for optional local display (→  55):
For order code for "Housing", option A: glass

Cable entries/cable glands

3
A0020640

 30 Possible cable entries/cable glands


1 Female thread M20 × 1.5
2 Cable gland M20 × 1.5
3 Adapter for cable entry with internal thread G ½" or NPT ½"

Order code for "Housing", option A "Compact, coated aluminum"


The various cable entries are suitable for hazardous and non-hazardous areas.

Cable entry/cable gland Material

Cable gland M20 × 1.5 Nickel-plated brass

Adapter for cable entry with internal thread G ½"

Adapter for cable entry with internal thread NPT ½"

Device plug

Electrical connection Material

Plug M12x1 • Socket: Stainless steel, 1.4404 (316L)


• Contact housing: Polyamide
• Contacts: Gold-plated brass

Endress+Hauser 53
Proline Promag P 100

Sensor housing
• DN 15 to 300 (½ to 12"): coated aluminum AlSi10Mg
• DN 350 to 600 (14 to 24"): carbon steel with protective varnish

Measuring tubes
Stainless steel, 1.4301/304/1.4306/304L; for flanges made of carbon with Al/Zn protective coating
(DN 15 to 300 (½ to 12")) or protective varnish (DN 350 to 600 (14 to 24"))

Liner
• PFA
• PTFE

Process connections
EN 1092-1 (DIN 2501)
Stainless steel, 1.4571 (F316L); carbon steel, E250C 1)/S235JRG2/P245GH
ASME B16.5
Stainless steel, F316L; carbon steel, A105 1)
JIS B2220
Stainless steel, 1.0425 (F316L) 1); carbon steel, A105/A350 LF2
AS 2129 Table E
• DN 25 (1"): carbon steel, A105/S235JRG2
• DN 40 (1 ½"): carbon steel, A105/S275JR
AS 4087 PN 16
Carbon steel, A105/S275JR

Electrodes
Stainless steel, 1.4435 (F316L); Alloy C22, 2.4602 (UNS N06022); platinum; tantalum; titanium

Seals
As per DIN EN 1514-1, form IBC

Accessories

Ground disks
Stainless steel, 1.4435 (F316L); Alloy C22, 2.4602 (UNS N06022); tantalum; titanium

Fitted electrodes Measuring electrodes, reference electrodes and electrodes for empty pipe detection:
• Standard: stainless steel, 1.4435 (F316L); Alloy C22, 2.4602 (UNS N06022); tantalum, titanium
• Optional: only platinum measuring electrodes

Process connections • EN 1092-1 (DIN 2501): DN ≤ 300 (12") Form A, DN ≥ 350 (14") Form B; dimensions DN 65 PN 16
and only as per EN 1092-1
• ASME B16.5
• JIS B2220
• AS 2129 Table E
• AS 4087 PN 16
For information on the different materials used in the process connections →  54

Surface roughness Stainless steel electrodes, 1.4435 (F316L); Alloy C22, 2.4602 (UNS N06022); platinum; tantalum;
titanium:
≤ 0.3 to 0.5 µm (11.8 to 19.7 µin)
(All data relate to parts in contact with fluid)
Liner with PFA:
≤ 0.4 µm (15.7 µin)
(All data relate to parts in contact with fluid)

1) DN 15 to 300 (½ to 12") with Al/Zn protective coating; DN 350 to 600 (14 to 24") with protective varnish

54 Endress+Hauser
Proline Promag P 100

Operability
Operating concept Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnostics
• Expert level
Quick and safe commissioning
• Individual menus for applications
• Menu guidance with brief explanations of the individual parameter functions
Reliable operation
• Operation in the following languages:
– Via "FieldCare", "DeviceCare" operating tool:
English, German, French, Spanish, Italian, Chinese, Japanese
– Via integrated Web browser(only available for device versions with HART, PROFIBUS DP,
PROFINET and EtherNet/IP):
English, German, French, Spanish, Italian, Dutch, Portuguese, Polish, Russian, Turkish, Chinese,
Japanese, Bahasa (Indonesian), Vietnamese, Czech, Swedish, Korean
• Uniform operating philosophy applied to operating tools and Web browser
• If replacing the electronic module, transfer the device configuration via the plug-in memory
(HistoROM DAT) which contains the process and measuring device data and the event logbook. No
need to reconfigure.
For devices with Modbus RS485, the data recovery function is implemented without the plug-in
memory (HistoROM DAT).
Efficient diagnostics increase measurement availability
• Troubleshooting measures can be called up via the operating tools and web browser
• Diverse simulation options
• Status indicated by several light emitting diodes (LEDs) on the electronic module in the housing
compartment

Local display A local display is only available for device versions with the following communication protocols:
HART, PROFIBUS-DP, PROFINET, EtherNet/IP
The local display is only available with the following device order code:
Order code for "Display; operation", option B: 4-line; illuminated, via communication
Display element
• 4-line liquid crystal display with 16 characters per line.
• White background lighting; switches to red in event of device errors.
• Format for displaying measured variables and status variables can be individually configured.
• Permitted ambient temperature for the display: –20 to +60 °C (–4 to +140 °F). The readability of
the display may be impaired at temperatures outside the temperature range.

Remote operation Via HART protocol


This communication interface is available in device versions with a HART output.

Endress+Hauser 55
Proline Promag P 100

4 6 7

1 2 3 5
A0016948

 31 Options for remote operation via HART protocol


1 Control system (e.g. PLC)
2 Field Communicator 475
3 Computer with operating tool (e.g. FieldCare, AMS Device Manager, SIMATIC PDM)
4 Commubox FXA195 (USB)
5 Field Xpert SFX350 or SFX370
6 VIATOR Bluetooth modem with connecting cable
7 Transmitter

Via PROFIBUS DP network


This communication interface is available in device versions with PROFIBUS DP.

1 2

4 4 4
A0020903

 32 Options for remote operation via PROFIBUS DP network


1 Automation system
2 Computer with PROFIBUS network card
3 PROFIBUS DP network
4 Measuring device

Via EtherNet/IP network


This communication interface is available in device versions with EtherNet/IP.

56 Endress+Hauser
Proline Promag P 100

Star topology

1 2 3

5 5 5
A0032078

 33 Options for remote operation via EtherNet/IP network: star topology


1 Automation system, e.g. "RSLogix" (Rockwell Automation)
2 Workstation for measuring device operation: with Custom Add-On Profile for "RSLogix 5000" (Rockwell
Automation) or with Electronic Data Sheet (EDS)
3 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare) with COM DTM "CDI Communication TCP/IP"
4 Ethernet switch
5 Measuring device

Via PROFINET network


This communication interface is available in device versions with PROFINET.

Star topology

1 3 2

4 4 4
A0026545

 34 Options for remote operation via PROFINET network: star topology


1 Automation system, e.g. Simatic S7 (Siemens)
2 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
computer with operating tool (e.g. FieldCare, DeviceCare, SIMATIC PDM) with COM DTM "CDI Communication
TCP/IP"
3 Switch, e.g. Scalance X204 (Siemens)
4 Measuring device

Endress+Hauser 57
Proline Promag P 100

Service interface Via service interface (CDI-RJ45)


This communication interface is present in the following device version:
• Order code for "Output", option B: 4-20 mA HART, pulse/frequency/switch output
• Order code for "Output", option L: PROFIBUS DP
• Order code for "Output", option N: EtherNet/IP
• Order code for "Output", option R: PROFINET

HART

1
A0016926

 35 Connection for the order code for "Output", option B: 4-20 mA HART, pulse/frequency/switch output
1 Service interface (CDI -RJ45) of the measuring device with access to the integrated Web server
2 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with
"FieldCare" operating tool with COM DTM "CDI Communication TCP/IP"
3 Standard Ethernet connecting cable with RJ45 plug

PROFIBUS DP

1
A0021270

 36 Connection for order code for "Output", option L: PROFIBUS DP


1 Service interface (CDI -RJ45) of the measuring device with access to the integrated Web server
2 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with
"FieldCare" operating tool with COM DTM "CDI Communication TCP/IP"
3 Standard Ethernet connecting cable with RJ45 plug

58 Endress+Hauser
Proline Promag P 100

EtherNet/IP

1
A0016940

 37 Connection for order code for "Output", option N: EtherNet/IP


1 Service interface (CDI -RJ45) and EtherNet/IP interface of the measuring device with access to the integrated
Web server
2 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with
"FieldCare" operating tool with COM DTM "CDI Communication TCP/IP"
3 Standard Ethernet connecting cable with RJ45 plug

PROFINET

1
A0016940

 38 Connection for order code for "Output", option R: PROFINET


1 Service interface (CDI -RJ45) and PROFINET interface of the measuring device with access to the integrated
Web server
2 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or with
"FieldCare" operating tool with COM DTM "CDI Communication TCP/IP"
3 Standard Ethernet connecting cable with RJ45 plug

Via service interface (CDI)


This communication interface is present in the following device version:
Order code for "Output", option M: Modbus RS485

Endress+Hauser 59
Proline Promag P 100

Modbus RS485

2 1
A0030216

1 Service interface (CDI) of measuring device


2 Commubox FXA291
3 Computer with "FieldCare" operating tool with COM DTM "CDI Communication FXA291"

Certificates and approvals


CE mark The measuring system is in conformity with the statutory requirements of the applicable EU
Directives. These are listed in the corresponding EU Declaration of Conformity along with the
standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.

C-Tick symbol The measuring system meets the EMC requirements of the "Australian Communications and Media
Authority (ACMA)".

Ex approval The measuring device is certified for use in hazardous areas and the relevant safety instructions are
provided in the separate "Safety Instructions" (XA) document. Reference is made to this document on
the nameplate.
The separate Ex documentation (XA) containing all the relevant explosion protection data is
available from your Endress+Hauser sales center.

ATEX, IECEx
Currently, the following versions for use in hazardous areas are available:

Ex nA
Category Type of protection

II3G Ex nA IIC T6-T1 Gc

cCSAus
Currently, the following versions for use in hazardous areas are available:

NI
Category Type of protection

Class I Division 2 Groups ABCD NI (Non-incendive version), NIFW parameter 1)

1) Entity and NIFW parameter according to Control Drawings

60 Endress+Hauser
Proline Promag P 100

HART certification HART interface


The measuring device is certified and registered by the FieldComm Group. The measuring system
meets all the requirements of the following specifications:
• Certified according to HART 7
• The device can also be operated with certified devices of other manufacturers (interoperability)

Certification PROFIBUS PROFIBUS interface


The measuring device is certified and registered by the PNO (PROFIBUS User Organization
Organization). The measuring system meets all the requirements of the following specifications:
• Certified in accordance with PROFIBUS PA Profile 3.02
• The device can also be operated with certified devices of other manufacturers (interoperability)

EtherNet/IP certification The measuring device is certified and registered by the ODVA (Open Device Vendor Association).
The measuring system meets all the requirements of the following specifications:
• Certified in accordance with the ODVA Conformance Test
• EtherNet/IP Performance Test
• EtherNet/IP PlugFest compliance
• The device can also be operated with certified devices of other manufacturers (interoperability)

Certification PROFINET PROFINET interface


The measuring device is certified and registered by the PNO (PROFIBUS User Organization
Organization). The measuring system meets all the requirements of the following specifications:
• Certified according to:
– Test specification for PROFINET devices
– PROFINET Security Level 1 – Netload Class
• The device can also be operated with certified devices of other manufacturers (interoperability)

Pressure Equipment The devices can be ordered with or without a PED approval. If a device with a PED approval is
Directive required, this must be explicitly stated in the order. For devices with nominal diameters less than or
equal to DN 25 (1"), this is neither possible nor necessary.
• With the identification PED/G1/x (x = category) on the sensor nameplate, Endress+Hauser
confirms conformity with the "Essential Safety Requirements" specified in Appendix I of the
Pressure Equipment Directive 2014/68/EC.
• Devices bearing this marking (PED) are suitable for the following types of medium:
Media in Group 1 and 2 with a vapor pressure greater than, or smaller and equal
to0.5 bar (7.3 psi)
• Devices not bearing this marking (PED) are designed and manufactured according to good
engineering practice. They meet the requirements of Art. 4, Par. 3 of the Pressure Equipment
Directive 2014/68/EU. The range of application is indicated in tables 6 to 9 in Annex II of the
Pressure Equipment Directive 2014/68/EC.

Other standards and • EN 60529


guidelines Degrees of protection provided by enclosures (IP code)
• EN 61010-1
Safety requirements for electrical equipment for measurement, control and laboratory use -
general requirements
• IEC/EN 61326
Emission in accordance with Class A requirements. Electromagnetic compatibility (EMC
requirements).
• NAMUR NE 21
Electromagnetic compatibility (EMC) of industrial process and laboratory control equipment
• NAMUR NE 32
Data retention in the event of a power failure in field and control instruments with
microprocessors
• NAMUR NE 43
Standardization of the signal level for the breakdown information of digital transmitters with
analog output signal.
• NAMUR NE 53
Software of field devices and signal-processing devices with digital electronics

Endress+Hauser 61
Proline Promag P 100

• NAMUR NE 105
Specifications for integrating fieldbus devices in engineering tools for field devices
• NAMUR NE 107
Self-monitoring and diagnosis of field devices
• NAMUR NE 131
Requirements for field devices for standard applications

Ordering information
Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com -> Click "Corporate"
-> Select your country -> Click "Products" -> Select the product using the filters and search field ->
Open product page -> The "Configure" button to the right of the product image opens the Product
Configurator.
• From your Endress+Hauser Sales Center: www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as
measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop

Application packages
Many different application packages are available to enhance the functionality of the device. Such
packages might be needed to address safety aspects or specific application requirements.
The application packages can be ordered with the device or subsequently from Endress+Hauser.
Detailed information on the order code in question is available from your local Endress+Hauser sales
center or on the product page of the Endress+Hauser website: www.endress.com.

Cleaning Package Description

Electrode cleaning circuit The electrode cleaning circuit (ECC) function has been developed to have a solution
(ECC) for applications where magnetite (Fe3O4) deposits frequently occur (e.g. hot
water). Since magnetite is highly conductive this build up leads to measuring errors
and ultimately to the loss of signal. The application package is designed to AVOID
build up of highly conductive matter and thin layers (typical of magnetite).

Heartbeat Technology Package Description

Heartbeat Verification Heartbeat Verification


+Monitoring Meets the requirement for traceable verification to DIN ISO 9001:2008 Chapter
7.6 a) "Control of monitoring and measuring equipment".
• Functional testing in the installed state without interrupting the process.
• Traceable verification results on request, including a report.
• Simple testing process via local operation or other operating interfaces.
• Clear measuring point assessment (pass/fail) with high test coverage within the
framework of manufacturer specifications.
• Extension of calibration intervals according to operator's risk assessment.
Heartbeat Monitoring
Continuously supplies data, which are characteristic of the measuring principle, to
an external condition monitoring system for the purpose of preventive
maintenance or process analysis. These data enable the operator to:
• Draw conclusions - using these data and other information - about the impact
process influences (such as corrosion, abrasion, buildup etc.) have on the
measuring performance over time.
• Schedule servicing in time.
• Monitor the process or product quality, e.g. gas pockets.

62 Endress+Hauser
Proline Promag P 100

Accessories
Various accessories, which can be ordered with the device or subsequently from Endress+Hauser, are
available for the device. Detailed information on the order code in question is available from your
local Endress+Hauser sales center or on the product page of the Endress+Hauser website:
www.endress.com.

Device-specific accessories For the transmitter

Accessories Description

Ground cable Set, consisting of two ground cables for potential equalization.

For the sensor

Accessories Description

Ground disks Are used to ground the medium in lined measuring tubes to ensure proper
measurement.

 For details, see Installation Instructions EA00070D


Communication-specific Accessories Description
accessories
Commubox FXA195 For intrinsically safe HART communication with FieldCare via the USB interface.
HART
 For details, see "Technical Information" TI00404F
Commubox FXA291 Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser
Common Data Interface) and the USB port of a computer or laptop.

 For details, see the "Technical Information" document TI405C/07


HART Loop Converter Is used to evaluate and convert dynamic HART process variables to analog current
HMX50 signals or limit values.

 BA00371F
For details, see "Technical Information" TI00429F and Operating Instructions

Wireless HART adapter Is used for the wireless connection of field devices.
SWA70 The WirelessHART adapter can be easily integrated into field devices and existing
infrastructures, offers data protection and transmission safety and can be operated
in parallel with other wireless networks with minimum cabling complexity.

 For details, see Operating Instructions BA00061S


Fieldgate FXA320 Gateway for the remote monitoring of connected 4 to 20 mA measuring devices via
a Web browser.

 BA00053S
For details, see "Technical Information" TI00025S and Operating Instructions

Fieldgate FXA520 Gateway for the remote diagnostics and remote configuration of connected HART
measuring devices via a Web browser.

 For details, see "Technical Information" TI00025S and Operating Instructions


BA00051S

Field Xpert SFX350 Field Xpert SFX350 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
Fieldbus devices and can be used in non-hazardous areas.

 For details, see Operating Instructions BA01202S


Field Xpert SFX370 Field Xpert SFX370 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
Fieldbus devices and can be used in the non-hazardous area and in the hazardous
area.

 For details, see Operating Instructions BA01202S

Endress+Hauser 63
Proline Promag P 100

Service-specific accessories Accessories Description

Applicator Software for selecting and sizing Endress+Hauser measuring devices:


• Choice of measuring devices for industrial requirements
• Calculation of all the necessary data for identifying the optimum flowmeter: e.g.
nominal diameter, pressure loss, flow velocity and accuracy.
• Graphic illustration of the calculation results
• Determination of the partial order code, administration, documentation and
access to all project-related data and parameters over the entire life cycle of a
project.
Applicator is available:
• Via the Internet: https://wapps.endress.com/applicator
• As a downloadable DVD for local PC installation.

W@M W@M Life Cycle Management


Improved productivity with information at your fingertips. Data relevant to a plant
and its components is generated from the first stages of planning and during the
asset’s complete life cycle.
W@M Life Cycle Management is an open and flexible information platform with
online and on-site tools. Instant access for your staff to current, in-depth data
shortens your plant’s engineering time, speeds up procurement processes and
increases plant uptime.
Combined with the right services, W@M Life Cycle Management boosts
productivity in every phase. For more information, visit
www.endress.com/lifecyclemanagement

FieldCare FDT-based plant asset management tool from Endress+Hauser.


It can configure all smart field units in your system and helps you manage them. By
using the status information, it is also a simple but effective way of checking their
status and condition.

 For details, see Operating Instructions BA00027S and BA00059S


DeviceCare Tool for connecting and configuring Endress+Hauser field devices.

 For details, see Innovation brochure IN01047S


Commubox FXA291 Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser
Common Data Interface) and the USB port of a computer or laptop.

 For details, see "Technical Information" TI00405C


System components Accessories Description

Memograph M graphic The Memograph M graphic data manager provides information on all the relevant
data manager measured variables. Measured values are recorded correctly, limit values are
monitored and measuring points analyzed. The data are stored in the 256 MB
internal memory and also on a SD card or USB stick.

 BA00247R
For details, see "Technical Information" TI00133R and Operating Instructions

Supplementary documentation
For an overview of the scope of the associated Technical Documentation, refer to the following:
• The W@M Device Viewer : Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the
2-D matrix code (QR code) on the nameplate.

Standard documentation Brief Operating Instructions


Brief Operating Instructions containing all the important information for standard
commissioning is enclosed with the device.

64 Endress+Hauser
Proline Promag P 100

Operating Instructions

Measuring Documentation code


device
HART PROFIBUS DP Modbus RS485 EtherNet/IP PROFINET

Promag P 100 BA01172D BA01238D BA01176D BA01174D BA01422D

Description of device parameters

Measuring device Documentation code

HART PROFIBUS DP Modbus RS485 EtherNet/IP PROFINET

Promag 100 GP01038D GP01039D GP01040D GP01041D GP01042D

Supplementary device- Safety Instructions


dependent documentation
Contents Documentation code

ATEX/IECEx Ex nA XA01090D

Special Documentation

Contents Documentation code

Information on the Pressure Equipment Directive SD01056D

Modbus RS485 Register Information SD01148D

Heartbeat Technology SD01149D

Installation Instructions

Contents Comment

Installation instructions for spare part sets and accessories Documentation code: specified for each individual accessory .

Registered trademarks
HART®
Registered trademark of the FieldComm Group, Austin, Texas, USA
PROFIBUS®
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
Modbus®
Registered trademark of SCHNEIDER AUTOMATION, INC.
EtherNet/IP™
Trademark of ODVA, Inc.
PROFINET®
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
Microsoft®
Registered trademark of the Microsoft Corporation, Redmond, Washington, USA

Endress+Hauser 65
www.addresses.endress.com