ARAMCO QC Question Instrumentation
ARAMCO QC Question Instrumentation
SOME ABBREVIATIONS:
QCP Quality Control Plan
ITP Inspection Test Plan
TQ Technical Query
SAEP Saudi Aramco Engineering Procedure
1
Instrumentation | QA/QC Notes
SAES Saudi Aramco Engineering Standard
SAIC Saudi Aramco Inspection Checklist
SATIP Saudi Aramco Typical Inspection Plan
SATR Saudi Aramco Test Report
SASD Saudi Aramco Standard Drawing
SAIP Saudi Aramco Inspection Personal
SAMSS Saudi Aramco Materials System Specification
SASO Saudi Arabian Standards Organization
AWC Armor Wire Cable
NEC National Electrical Code
NACE National American Corrosion Engineers
SCADA Supervisory Control and Data Equation
ANSI American National Standards Institute
ASTM American Society for Testing and Materials
ASME American Society of Mechanical Engineers
BS British Standards
IEEE Institute of Electrical and Electronic Engineers
ICEA Insulated Cable Engineers Associations
IEC International Electrotechnical Commission
NEMA National Electrical Manufactures Associations
NFPA National Fire Protection Association
ATEX Atmospheres Explosibles
FM Factory Mutual
IP Ingress Protection
UL Underwriters Laboratories
ITC Instrument Tray Cable
PLTC Power Limited Tray Cable
PVC Polyvinyl Chloride
XLPE Cross Linked Polyethylene
XLPO Cross Linked Polyolefin
HDP High Density Polyethylene
RTD Resistance Temperature Detector
SWA Still Wire Armored
MICC Mineral Insulation Copper Conductor
PILC Paper Insulation Copper Conductor
FOC Fiber Optical Cable
OTDR Optical Time Domain Reflectometer
RTA Request for Technical Approval
MTC Material Test Certificate
Group 3: Multipair / Triad, Unshielded or without overall shield thickness 0.022 mm.
2
Instrumentation | QA/QC Notes
Communication Wire: Not required if required shall be manufacturer’s standard size, Insulation same as primary
insulation – Orange Color.
Group 5: Thermocouple Extension wire conductor – solid thermocouple extension wire as per ANSI MC 96.1
Conductor Size: # 16 AWG for singal pair, # 18 AWG for Multipair.
Color Code: ANSI MC 96.1(Temperature Measurement Thermocouple), (Yellow and Red) Negative shall be
Red color and magnetic
Terminal Block: As per minimum thickness of terminal block shall be 5 mm or higher with Spring type terminal
block are not acceptable, Terminal block shall be fire retardant halogen free, High strength
material such as polyamide on equivalent in accordance with UL94.
Lugs: Drawing / Color Codes / Ferruling will be done for easy identification with use of lugs. Lugs are two types.
One is crimping type and the other one is soldering type.
Type of Lugs: (1) Shanap Type (2) Pin Type (3) Ring Type (4) U Type
Thread Type: ET (Equal Thread), BSP (British Standard Pitch), NPT (National Pipe Thread).
COLOR CODE:
AC Supply: Phase Black
Neutral White
Ground Green or Green with yellow tracer
TYPE OF THERMOCOUPLE:
3
Instrumentation | QA/QC Notes
Pulling tension of FOC = 600 Pounds.
Fir Resisting: (CI: Circuit Integrity) Flame Retardant, for transmission of analog or digital signal to instrument
and control systems.
Insulation: Silicon Rubber
Armor: Zinc Coated round steel.
RE: Instrument Cable
2G: Insulation of Silicon
SI: Collective Screen
H: Inner Jacket of LSZH
SWA: Round Steel Wire Armor
I/W: Outer Jacket of heat resistant PVC
FL: Reduced Flame Propagation
CI: Circuit Integrity
FB: Field Bus Cable
Y: Outer sheath of PVC
2X: Insulation of XLPE
PIMF: Pair Screen
HVAC: Heating Ventilation & Air Conditioning.
ISDN: Integrated Service Digital Network
LASER: Light Amplification by Stimulated.
Cable Shield: Prevent Electromagnetic Electrostatic Interference from being endued into the inner wire
conductor.
Design and installation of power and wiring system for instrumentation shall be in accordance with NFPA 70
and NEC.
Fireproofing of cable in fire hazardous area shall be in accordance with SAES-B-006.
Shielded cables shall be used as required to reduce electrostatic noise. The shield shall be grounded at one
point only.
Field Bus Cable shall Comply with IEC 61158-2 (Type A)
Cable Insulation thickness 0.38 mm PLTC/ITC
TC Cable thickness 0.64 mm
Light blue color coding shall be used to identify intrinsically safe wiring the preferred practice is to specify
intrinsically safe interconnecting cable with blue outer jacket. Alternative blue sleeweves slipped over the
jacket.
At all the points of termination may used to identify I.S. wiring.
If used for connections of equipment to ground rods or ground grid to be minimum 25 mm2 (# 4 AWG).
Intrinsically safe system shall be used in zone 0 hazardous area.
Thermal send have to use in trench before started send bedding.
For Extension wires having insulation color as per ANSI MC96.1 (American National Standard Institute). The
negative wire is always RED colored as per ANSI.
CABLE GLAND:
For Hazardous & Non Hazardous locations shall be in accordance with BS 6121 or BS 50262.
Cable Gland: Cable glands are used to protect Mechanical damage. To give earth continuity and for
entering it a junction box & MCC etc. For PILC (Paper Insulation Copper Conductor) cables lead
covered are used because in refinery, hydrocarbon gases will damage the PVC insulation, for this
purpose lead cover is used, for these purpose plumbing type glands are used.
4
Instrumentation | QA/QC Notes
In Explosion proof areas double compression glands are used to avoid these gasses entering in the
electric at apparatus.
FASTENER TORQUE VALUE:
M8 14 ~ 16 NM
M10 26 ~ 33 NM
M12 45 ~ 58 NM
SIZING OF CABLE:
0.75 mm2 18 AWG
1.0 mm2 17 AWG
1.5 mm2 16 AWG
2.5 mm2 14 AWG
4.0 mm2 12 AWG
6.0 mm2 10 AWG
10 mm2 08 AWG
16 mm2 05 AWG
25 mm2 04 AWG
35 mm2 02 AWG
50 mm2 1/0 AWG
70 mm2 2/0 AWG
120 mm2 4/0 AWG
GROUNDING SYSTEM:
Ground rods 2.4 meter minimum length.
Cathode protection material is used galvanized steel.
Individual Ground rod maximum resistance should be 2.5 Ohm.
For copper or copper jacketed steel rods is a minimum of 16 mm2 in diameter or 19 mm2 in diameters.
Earth Tester is used for measuring of earthling system.
Underground wire for grounding to wire connections shall be cadweld or thermoweld. Compression
connector shall not be used.
Shields wires shall be grounded only at the one point for the signal cables.
Shields and armor of power cables shall be grounded at both ends.
If used for connections of equipment to ground rods or ground grid be minimum 25 mm2 (# 4 AWG).
Metallic cable trays shall be bonded at both end points and a minimum of every 25 Meter to the local
ground grid.
If buried / used for grids or interconnections of ground rods to be minimum 70 mm2 (2/0AWG).
Be copper or copper jacketed steel or galvanized steel or copper jacketed steel shall meet the
requirements of UL 476 (Underwriters Laboratories).
Power Applications: Metal cable trays must be grounded and eclectically continuous systems as per
NEC article 318.
Non-Power Applications: Cable tray systems containing conductors outside the scope of NEC Article
250 (such as communications, data, signal cables, etc.)
TRAY INSTALLATION:
Cable Tray Installation: The publication is intended as practical guide for the proper installation of cable system.
Cable tray systems design and Installation shall comply with NEC Article – 392 & 318,
NEMA VE1, NEME VE2 and NEMA FG 1 and follow safe practices as described in
NFPA 70E.
5
Instrumentation | QA/QC Notes
TIPS FOR CABLE TRAY INSTALLATION:
Cable tray specification shall be per NEMA VE1 the tray shall be per NEMA VE2.
The distance between consecutive rungs shall not exceed 229 mm (9 Inch).
Cable Ties for Vertical Application shall be provided every 18 inch (after one rung).
Cable Tied for Horizontal application shall be provided every 27 inch (after two rungs).
Unless otherwise noted, the support interval shall be not more than 2.4 meters as per NEMA VE1.
For the Vertical Application cable ties must be 316SS with PVC coated.
The open gap between tray/conduit to the instrument maximum 350 mm.
The cable tray system shall be installation with manufactures standards fittings.
Such as Clamps, Splicer Plates, Connector, Hangers, Reducer Plates, Grounding Brackets Blind, Nut
Bolts, Washers etc.
The channel cable tray material shall be copper free aluminum (Aluminum with max of 0.4% copper).
Channel cable tray width shall be 3, 4, or 6 inches with a minimum loading depth of 1 ¼ inch.
Non metallic cable tray permitted in corrosive area. Non metallic cable trays shall be made of flame
retardant material.
Level 1: High to Medium susceptibility analog signals of less than 50V and discrete instrument signal of less than
30V.
6
Instrumentation | QA/QC Notes
Level 2: Low susceptibility switching signal greater than 30V, analog signals grater then 50 V and 120 ~ 240 AC
feeder less than 20 Amps.
Level 3: Power AC and DC buses of 0 ~ 1000 V with currents of 20 ~ 800 Amps.
Tray to Tray Spacing in mm:
NSL 1 2 3
1 0 150 650
Tray to Tray:
Level 1 to Level 2 gap should be 150 mm
Level 2 to Level 3 gap should be 500 mm
Level 1 to Level 3 gap should be 650 mm
Tray to Conduits:
Level 1 to Level 2 gap should be 100 mm
Level 2 to Level 3 gap should be 350 mm
Level 1 to Level 3 gap should be 450 mm
Conduit to Conduit:
Level 1 to Level 2 gap should be 75 mm
Level 2 to Level 3 gap should be 225 mm
Level 1 to Level 3 gap should be 300 mm
DUCT BANKS:
Consist of either hot dip galvanized rigid steel or PVC conduit, incase in concrete.
75 mm of concrete from the outside surface of the duck bank to any conduit or reinforcing steel.
Fabricated spacers shall be used at intervals not exceeding 2.4 Meter.
The spacers shall provide a minimum conduit separation of 50 mm for 2 inch conduit.
For equipment, devices, or appropriates certified as intrinsically safe, only those that are certified are
category EEx or AEx “ia” shall be used.
All metal cable trays, enclosures used for intrinsically safe wiring shall be grounded to the plant grounding
system with a min of # 4AWG copper wire with green insulation.
Cable Tray material shall be galvanized, carbon steel in indoor air condition area.
Bare copper cable does not used in or on aluminum cable tray.
CONDUIT INSTALLATION:
Conduit fittings and accessories include conduits and pull boxes:
Conduit cover and gaskets
Conduit Seal
Conduit Unions and Couplings
Factory Elbows
Drain
Breathers
Plugs
Conduit Connectors reducers
Expansion fittings
Straps and Clamps
Bushing
Cable and duct seal, etc.
7
Instrumentation | QA/QC Notes
TIPS FOR CONDUIT INSTALLATION:
Conduit Expansion fitting shall be provided in indoor 30 Meter.
Conduit Puller J/B shall be provided every 25 Meter.
Pull Box to Pull Box maximum bends acceptable in 360 degree without 90 degree bend.
Support (Bending) does not occur NEC-344
Pull & JB are Installed & Securely fixed as per NEC-314.28
All connection of conduit shall be made by the pipe thread with engagement of at least 5 threads in the
effective threaded portion.
The connection part shall be painted by the zinc primer.
When EYS and EZS Series (Explosion proof Conduit Sealing Fittings only).
Tips: 1- Sealing fittings are used to seal cables in conduit entering enclosures; a conduit union shall be
installed between the sealing fittings and the enclosure.
2- Restrict the passage of gases, vapors or flames from one portion of the electrical installation to another
at atmospheric pressure and normal ambient temperatures.
3- Limit explosions to the sealed off enclosure.
4- Limit pre-compression or pressure "piling" in conduit systems
When EYD and EZD Series (Explosion proof conduit sealing fittings with drain).
Tips: 1- Drain to provide continuous, automatic drainage of condensate.
2- Large openings with threaded closures to provide easy access to conduit hubs for making dams.
3- Integral bushings to protect conductor insulation from damage.
4- Taper tapped hubs to ensure ground continuity.
NPT type accordance with UL34E 34997 or CSA (Canadian Standard) LR 9795.
Seal fitting shall not be less than ⅝ inch.
Sealing compound shall be 35 C to 85 oF.
o
Seals are provided in conduit & cable system to minimize the passage of gases and vapors and prevent
the passage of flame from one portion the electrical installation the conduit.
Bushings: Where a conduit enters a box, fittings or other enclosure a bushing shall be
provided to protect the wire from abrasion.
BENDS:
Number in one run: There shall not be more than the equivalent of four quarter bends (360 degree total)
between pull point to point.
Mandrel Testing: Testing of underground duct bank and bend radius of conduit is 90 degree.
When union cannot be avoided in underground conduit installation, unions shall be protected with heat shrinkable
sleeves.
Conduit and cable sealing shall be installed in accordance with NEC-505.10.
Conduit seals shall be installed within 450 mm (18 inches) from the enclosure.
PB: Pull Box
8
Instrumentation | QA/QC Notes
RGS: Rigid Galvanized Steel.
Split Conduits: Split conduit Installation shall be used to repair existing conduits which contains existing cable
these conduits shall be installed in accordance with the manufacturer’s recommendations or
NEMA TCB2 User manual for the installation of order ground plastic conduits.
We can use maximum bend in one conduit (Point to Point) 360 degree, but we have to avoid 90 degree
bend or sharp bends.
If there is sharp bend so we can perform Mineral Test.
Direct buried conduits (Underground) shall be threaded, rigid steel per accordance ANSI C80.1 and
addition it shall be hot dip galvanized and PVC coated as per NEMA RN1 (minimum thickness of PVC 1
mm) or PVC conduit type DB-120 (Minimum elasticity 500-000 PSI) as per NEMA TC6 & TC8 type.
Concrete incase conduit shall be threaded, rigid steel as per ANSI C80.1 and in addition it shall be hot dip
galvanized.
Conduit Installed exposed (not embedded in walls) above grounding in outdoor industrial facilities shall be
threaded rigid steel per ANSI C80.1 and in addition it shall be hot dip galvanized.
Conduit above ground in severe corrosive environments shall be as threaded, rigid steel as per
ANSI C80.1, in addition shall be factory PVC Coated (minimum thickness of PVC 1 mm) as per
NEMA RN-1.
Electrical Metallic Tubing (EMT) is acceptable only in non-hazardous indoor locations. EMT shall
comply with the requirement of ANSI C80.3
Intermediate metal conduit (IMC) is prohibited.
The Minimum conduit size shall be ¾ inch, except for instrumentation wiring inside building.
Conduit and threaded conduit fitting shall have tapered (NPT) threads in accordance with
ANSI / ASME B1.20.1
ANSI C80.1 Rigid Steel Conduit-Zinc Coated
ANSI C80.3 Electrical Metallic Tubing - Zinc Coated (for indoor only)
Process Piping shall be used to support conduits.
Flexible conduit: shall be used at instrument end of the conduit to provide isolation from vibration
against thermal expansion of the rigid conduit systems.
Conduit sealing shall only be poured at temp between 35 oF to 85 oF
The sealing compound shall provide a seal against passage of gas or vapors through the seal fittings.
The minimum thickness of the sealing compound shall not be less than ⅝ Inch.
Conduit seal fitting plug is painted with red color and non poured seal fitting are painted with green color.
Gap selling of expansion splice palate 25 mm (gap max)
50 oF or 10 oC gap is 9.5 mm (Standard)
The minimum depth of burial requirements for underground installations shall be as per:
Direct Buried Direct Buried Duct Bank & Direct Buried
System Voltage
Cable PVC Rigid Steel
600V & Below 610 mm 460 mm 460 mm
600V to 35 KV 920 mm 610 mm 460 mm
Over 35 KV 1070 mm 760 mm 460 mm
9
Instrumentation | QA/QC Notes
Impulse lines for remote device should be as short as possible, 3 feet for close-coupled transmitters and
preferable not more than 20 feet (6 meters). For liquid measurement the lines should slope down at least 1 inch
per foot from the orifice taps.
Tubing: Stainless steel tubing shall seamless, annealed, minimum wall thick 1.24 mm as per ASTM A269 Gras
IP – 316L.
ENCLOSURES:
Indoors and Outdoors Plant Area:
Indoors: With in the Perimeter of the Process Unit (NEMA 250 / NEMA ICS6)
Outdoor: Out side the Perimeter of Process Area (IP54)
Severe Corrosive Environment (Industrial Area) NEMA Type 4X or IP66.
Non Industrial Area IP34.
Name Plate Shall is attached to the cabinets using stainless screws.
Indoor Cabinets shall be made of metal.
The Cabinet shall be a NEMA Type 1 as per NEMA 250 and NEMA ICS6.
10
Instrumentation | QA/QC Notes
NEMA ICS6: Enclosures for Industrial Controls and System.
The Max Door Width shall be 900 mm (36 Inch)
The Marshalling cabinets from the front surface to the surface of rear terminal block, shall not be more
than 46 cm (18 Inch)
A minimum of prime, undercoat & finishing coat of enamel or polish is required.
Interior cabined color shall be white or of light color such as light gray off.
Name plate for cabinets and panels letter height and spacing shall follow ISA RP 60.6
Name Plate shall be made from laminate Plastic, white – Black – White (Information engraved into the
black core) with white surface.
Area classification
Symbol for equipment built to American
Standards
Type(s) of protection designation
TYPE OF PROTECTION:
Zone ‘0’ – Ex ‘ia’ and Ex ‘s’ (Specifically certified for use in Zone ‘0’).
Zone ‘1’ – Any type of protection suitable for Zone-0 and Ex‘d’, Ex ‘b’, Ex ‘p’, Ex ‘e’.
Zone ‘2’ – Any type of protection suitable for Zone–0 or Zone-1 and Ex ‘N’ or ‘n’, Ex ‘o’, Ex ‘q’.
Designation Technique Zone
Ex ‘d’ Flame proof or Explosion proof 1
Ex ‘e’ Increased Safety 1
Ex ‘N’ or ‘n’ None Sparking 2
Ex ‘ia’ Intrinsic Safety 0
11
Instrumentation | QA/QC Notes
Ex ‘ib’ Intrinsic Safety 1
Ex ‘p’ Pressurization 1
Ex ‘o’ Oil Immersion 1
Ex ‘q’ Sand or Powder filled 1
Ex ‘s’ Special Protection 0
GAS GROUP:
12
Instrumentation | QA/QC Notes
Class III - Ignitable fibers or flying are present.
A location where a hazardous concentration of gases or vapors exists approximately
Division 1 Zone 0
10 ~ 100 % of the time (subject to interpretation as above).
A location where a hazardous concentration of gases or vapors exists approximately
Division 1 Zone 1
1 ~10 % of the time (subject to interpretation as above).
A location where a hazardous concentration of gases or vapors exists approximately
Division 2 Zone 2
0.1 ~ 1 % of the time (subject to interpretation as above).
Group A Group IIC A hazardous atmosphere containing acetylene or other similar gases or vapors.
Group B Group IIC A hazardous atmosphere containing hydrogen or other similar gases or vapors.
Group C Group IIB A hazardous atmosphere containing ethylene or other similar gases or vapors.
Group D Group IIA A hazardous atmosphere containing pentane or other similar gases or vapor.
Group E - A hazardous atmosphere containing metal dust, such as aluminum.
Group F - A hazardous atmosphere containing carbon black, coal, or coke dust.
Q: What does “BASEEFA” stand for …..?
A: British approval service for electrical equipment in flammable atmospheres.
Q: Explain the meaning of: (a) Zone 0 (b) Zone 1 (c) Zone 2 (d) Non-Hazardous.
A: (a) - In which an explosive gas-air mixture is continuously present or present for long period.
(b) - In which as explosive gas air mixture is likely to occur under normal operation.
(c) - In which an explosive gas-air mixture is not likely to occur in normal operation and if it occurs it exist only
for short time.
(d) - An area which by implication is any area not classified as zone 0, 1 or 2.
i.e. control or switch room that is pressurized (HVAC) or an area that has no hydrocarbon inventory.
Q: Explain the type of protected equipment is required in the flowing zones: (a) Zone 0 (b) Zone 1 (c) Zone 2
A: (a) – Ex-ia, Ex-s: Must be specifically certified for zone 0 use.
(b) – Any type of equipment suitable for zone 0, Ex-ib, Ex-d, Ex-p, Ex-e.
(c) – Any type of equipment suitable for zone 0 and 1, Ex-n, Ex-o, Ex-q.
EQUIPMENT CLASSIFICATION:
13
Instrumentation | QA/QC Notes
Q: Explain the type meaning of Ex-o.
A: Oil Immersion.
Q: Explain the type meaning of Ex-m.
A: Encapsulation / hermetically sealed.
INGRESS RATINGS:
Q: Explain the meaning of “INGRESS PROTECTION”
A: The appliances ability to keep out solids and liquids, IE Dust, Sand and Water. The first number indicates the
protection against solids and the second number indicates the protection against liquids.
Q: Is it allowable to modify an EEx “d” gland to fit and entry in an EEx “d” enclosure..?
A: No.
Q: State the minimum amount of threads needed to be installed on an Ex‘d’ cable gland..?
A: (1) – 5 full threads (minimum length 8 mm) for gas group 2B apparatus.
(2) – 6 full threads (minimum length 9.5 mm) for gas group 2C apparatus.
T1 = 450 oC
T2 = 300 oC
T3 = 200 oC
T4 = 135 oC
T5 = 100 oC
T6 = 085 oC
INSTRUMENTATION QUESTION AND ANSWER
1. What is QA/QC?
Ans: QA/QC means, “Quality Assurance / Quality Control” The purpose of this (QA/QC) is to establish
the sequence of requirement for the quality of material, quality of works, its inspection, and records.
5. What is non-conformity?
Ans: Non-conformity “Non-fulfillment of requirement”. (Complete failure of a system, or controls, which
result in completely unsatisfactory goods or services being provided).
14
Instrumentation | QA/QC Notes
7. Who are the responsible for Quality?
Ans: Everybody within all organization.
15
Instrumentation | QA/QC Notes
Hold Point: Work can’t be executed without client inspection.
15. What is difference between hazardous and non-hazardous Areas?
Ans: Hazardous: A hazardous location is defined as an area where a potential for fire or explosion
exists due to the presence of flammable gases, liquids or vapors, combustible dusts or fibers and
flying in sufficient quantities to produce an explosion or ignitable mixture.
Non-hazardous: An area where non risk of presence of any kinds exposition.
16. What are different kinds of certification?
Ans: Weather Proof.
Dust Proof
Water Tight
Explosion Proof
Flame Proof
Intrinsic Safety Proof etc
17. What is ISO? Explain some of its standards?
Ans: ISO means International Standard Organization, Some are them they are as below;
ISO: 9001, ISO: 9002, ISO: 9003, etc.
18. What are zone classifications? Give a brief?
Ans: Zone classification is to define the area of hazards, they are as below;
Zone – 0: A zone in which explosions gas/air mixture is continuously present or present for
extended periods, during normal operation.
Zone – 1: A zone in which an explosive gas/air mixture is likely to occur in normal operation.
Zone – 2: A zone in which an explosive gas/air mixture is likely to occur in normal operation.
Zone – 10: A zone in which an explosive dust atmosphere is present continuously or for extended
periods of time.
Zone – 11: A zone in which there is a likelihood that explosive atmospheres my occur for short
periods due to unsettled to unsettled dust layers.
Class II: Location in which the presence of combustible dust are in the air in sufficient quantity to
ignite or explode.
Class II conductive/non conductive dust is divided into three below.
Group E: Presence of metal dusts (aluminum, magnesium and chemical dust etc)
Group F: Presence of black carbon, charcoal, coal or coke dust etc.
Group G: presence of non-conductive dust (foam, starch, combustible plastics etc.)
Class III: Location in which easily ignitable fiber / flying are present but are not likely to be in
suspension in air in quantities sufficient to produce ignitable mixture.
Division – 1: The hazards are present continuously or periodically under normal operation
condition.
Division – 2: The Hazards are only presents during accidental or abnormal condition.
16
Instrumentation | QA/QC Notes
Ans: A digital logic circuit with one or more input voltage but only one output voltage.
25. What is Microprocessor control system? Give a brief of PLC, DCS and SCADA?
Ans: Computer based control process system is called microprocessor control system. The brief of PLC,
DCS and SCADA are as following:
PLC: Programmable Logic Control System.
PLC’s are used in practice with the aim of achieving a higher degree of availability or fault
tolerance. The types are as follow.
Fault Tolerant: 1 out of 2 system objective: Reduce the probability of losses of production by
switching to a standby system.
Fail Safe: 2 out of 2 system objective: Protect life, the environment and investment by safely
disconnecting to a secure “off” position.
DCS: Distribute Control System.
SCADA: Supervisory Control and Data Acquisition.
27. What are inspection points for field instruments with impulse tubing?
Ans: Materials inspection as per approved spec material, type and size, Installation as per Hook-up,
check line route to avoid any obstruction, check tube bending, and check tube support,
compression fitting or ferrules, and then pressure test (hydrostatic test) shall be done.
29. What are inspection points for Junction Box and Marshalling cabinets?
Ans: Material Inspection, type, size as per approved specification, installation hook up for frame, bracket
or stands, fixed properly means shaking free, Name Plate, and tag no.
30. What are standards methods or ferrules addressing to and from a Junction Box?
Ans: For to side only terminal’s address required which shall be close to terminal either side and
complete information shall be of from side after or before as per left and right side.
17
Instrumentation | QA/QC Notes
C: Level 2 – Minimum requirements, pre-inspection meetings, one or more unspecified “in
progress” surveillance visits.
D: Level 3 – Same as level 2, except that “in progress” surveillance inspection shall be in regular
basis.
E: Level 4 – Resident Inspection Continuously monitor the work.
Level of Inspection for construction phase:
A: Hold Point (H): The inspection activities will not proceed without the presence of inspection.
B: Witness Point (W): Inspection activities can be proceeding after issuing RFI.
C: Review (R): Verification of documentation (NMR) on its correctness as per spec and approved
drawings.
D: Surveillance (S): Inspection has right to conduct random inspection of works.
E: Inspection (I) / Perform (P) / Test (T): construction can be proceeding to next phase without
client inspection.
34. What is ITP’s? What are Hold and Witness Point?
Ans: ITP mean Inspection and Test Plan, details of work scope and required types of inspections.
Hold Point (H): is the level of inspection that client inspection must require through RFI and can’t
be preceded until inspection is done by client.
Witness Point (W): is the level of inspection that inspection activity can be preceded without client
inspection or if client is not available as per RFI Timing.
39. What is the specialty rather characteristics of loop check? How do you come to know that loop check is
completed
Ans: a. Loop check is a clear blue print of a successful system functioning (activity wise),
b. This emphasis the serviceability of each instrument installed either in field or inside the building,
c. This exposes also the limitation of some systems functioning as per the attached filled punch list,
d. One of the ready documents for final hand over of a project on completion,
e. It is always two team’s operation-one will be on field and the other will be in the control room,
After every successful completion of loop check it is marked with Red Colored Label bearing the
date of the loop check and the witnessing parties initial.
18
Instrumentation | QA/QC Notes
42. What are the responsibilities of QC Inspector?
Ans: The following are the phenomenal responsibilities which any QC Inspector is supposed to execute
at the time of carrying out any inspection.
a. Well versed with the technology for which the inspection is carried out.
b. Should have the reasoning capability to analysis the method.
c. Should have thorough knowledge about the procedure to be adopted for inspection i.e. adopted
standards.
d. Should be able to convey the irregularities found to the concerned authorities.
e. Should be absolute sincere about the job execution.
f. Should be vigilant all the time.
43. What should be the attitude of a QC Inspector while carrying out an Inspection activity?
Ans: Following are the characteristics of a perfect inspector:
a. Should never compromise with the quality at the time of performing inspection.
b. Should be sincere towards performing the responsibilities.
c. Should be punctual.
d. Should be exemplary in approach while carrying out inspection.
e. Should have the capabilities to convince the authorities about the irregularities with
knowledgeable representation.
44. What are the requirements for carrying out installation inspection of any instruments and receiving
inspection of the said equipment?
Ans: Following are the requirements at the time of execution of an inspection.
a. Instrument data sheet.
b. Test Instrument Certificate.
c. Vendor instruction manual.
d. Test Instrument instruction manual.
47. What is Schedule ‘Q’ and how many appendices are there in schedule ‘Q’?
Ans: Schedule ‘Q’ is the guidelines for the method application related to quality including the distribution
of manpower (quality field oriented) and the quality process execution including quality control and
quality assurance.
It has got six appendices covering all the process implementations related to execution of project
performance with the focus towards maintainability of quality control and quality assurance.
48. What are the linked documentations carried out related to QC activity for oil & gas construction project?
Ans: a. Application for inspection from construction department after completion of every activity.
b. Production of drawing based on the planning.
c. Method application priority wise.
d. Procurement of item and equipments required for the execution of the project.
19
Instrumentation | QA/QC Notes
50. What are QCP, QMP and ITP?
Ans: QCP – Quality Control Procedure, QMP – Quality Management Procedure, ITP – Inspection and
Test Plan.
52. What do you know about NEC, NEMA VE1, NEMA VE2, NEMA RN?
Ans: NEC – National Electrical Code earlier used to be published under the statutory body of NFPA
since 1897, from 2005 edition it is categorized as an internationally accepted method inspection
procedure guidelines covering all most all the field related to Electrical, Instrumentation and
Communication Engineering.
NEMA VE1 – National electrical manufacture association VE1
NEMA VE2– Deals with cable tray installation specification
53. What are the articles refereed during carrying out the following activities?
(1) Grounding. (2) Installation of cable Tray. (3) Fire alarm System Installation. (4) Installation Instrument
Cable Tray etc,
Ans: (1) Grounding Article 250 (Chapter IX for instrumentation), (2) Installation of cable tray Article 392,
(3) Fire Alarm System Art 760, Installation of instrument cable tray art 727.
55. What would be the thickness of the top layer of a Duct Bank and color?
Ans: 5 mm and Red Dye.
56. What is the purpose of using paint/dye on top layer?
Ans: To give an anticorrosive protection, top layer painting is provided.
57. What are types of conduits used in electrical and instrumentation wiring circuits?
Ans: Rigid Metallic Conduit (RMC), Intermediate Metallic Conduit (IMC), Rigid Nonmetallic Conduit
(RNC).
58. What are the differences between a JB (Junction Box) and Terminal Box?
Ans: The purpose of JB (Junction Box) is used as a linkage between one or more inlet and one or more
outlet. Whether terminal box has inlet on or more but out let may be one for earthen or it may not
be. JB can be used in between the routing for providing support and extra opening but TB is used
as Termination means at the end of the routing.
20
Instrumentation | QA/QC Notes
clear evidence of the all completed job. It is always signed by QC to ensure the maintainability of
the quality aspect of the job performed.
65. How are the hazardous and non hazardous areas classified?
Ans: Hazardous and non hazardous areas are classified according to the classifications and zones.
66. What is the Expansion joint? What should be the standard gap maintained in expansion joint?
Ans: It I the breathing space provided to accommodate the expansion of horizontal cable tray to suit with
different climatic condition by maintaining a standard length wise distribution.
According to NEMA VE2 it is after every 20 meter with a spacing (expansion joint) of 25 mm to be
maintained. It sometimes differs, but should not be more for the horizontal length of the cable try.
71. What is the minimum thickness of concrete from outside surface of the duct bank to any conduit or
reinforcing steel?
Ans: 75 mm
72. What is mean by Guwat and Guwa, where it is applicable for use?
Ans: You can use in conduit installation for lighting purpose.
Guwat: With terminal block.
Guwa: Withought Terminal block.
73. How the Metallic and PVC conduit entering from below of any equipment like switchgear control cabinets
and similar enclosures sitting?
Ans: The metallic conduit shall be cut and threaded 50mm above finished grade level and a threaded
insulated grounding bushing shall installed, also PVC conduit shall be cut flush with finished grade
level and shall have its inner edge filed to a smooth radius.
74. What type of sealing is used for all ducts inside all manholes and hands holes where permitted inside
hydrocarbon handling plants?
21
Instrumentation | QA/QC Notes
Ans: All ducts shall be sealed with 3M scotch cast brand 4416 cable duct sealing kits or other methods
approved by the electrical standards committee chairman.
76. What should be done, when union cannot be avoided in underground conduit installation?
Ans: Unions shall be protected with heat-shrinkable sleeves.
79. What is the minimum conduit size excepted for instrumentation wiring inside building?
Ans: ¾ Inch.
80. What is the minimum conduit size excepted for prefabricated skids and in-industrial area?
Ans: ½ Inch.
82. What are the conduit fittings for outdoor rigid steel conduit and liquid tight flexible metal (LFMC)?
Ans: Shall be cast or forged steel, cast iron or malleable iron either hot-dip galvanized (preferably)
electroplated.
84. What is the minimum distance from main door to marshaling panel?
Ans: Minimum shall be 3 meter from main door to marshaling panel.
88. What shall be minimum acceptable insulation resistance of instrument cable during Megger Test?
Ans: 100 Mega ohms
90. What shall be the maximum acceptable attention value of fiber during OTDR test?
Ans: 0.5Db/Km or less for wave length of 1310 nm and 0.3Db/Km or less .for wave length of 1550nm.
91. What shall be the maximum pulling tension of FOC?
Ans: 600 Pounds.
92. What is name of fieldbus communicator?
Ans: FBT6 (Fieldbus Transducer 6)
93. What is the Principle of Bimetal Thermometer?
22
Instrumentation | QA/QC Notes
Ans: Different Metal of Different Coefficient.
94. What is the color coding for accepted instrument or rejected instruments?
Ans:
Blue - Pre-installation Test (Calibrated)
White - Test Fail (written message may be added giving reason failure)
Red - Pre-commissioned
Green - Cable Test (Megger)
Yellow - Pressure Test
95. How do you calculate new factor from new range using old factor and old range?
Ans:
23
Instrumentation | QA/QC Notes
Ans:
24
Instrumentation | QA/QC Notes
LRV = Elevation – Suppuration
URV = Range – Suppuration + Elevation
Suppuration Calculation:
Span = Range – Suppuration = 100% {Range = 27.422}
LRV = Suppuration = 0% {Suppuration = 30.316}
URV = Span = 100 % Span / 4 = 25 %
0% -30.316
25% -23.460
50% -16.605
75% -9.749
100% -2.894
Elevation Calculation:
Span = Range + Elevation = 100% {Range = 5.814}
LVR = Span = 100% {Elevation = .971}
URV = Elevation = 0% Span / 4 = 25%
0% 0.971
25% 2.424
50% 3.878
75% 5.331
100% 6.785
ELECTRICAL QUESTION AND ANSWER
H. T. Motors?
Motors working with voltage 3.3KV and above are HT motors. This motor normally used for high loads are the
operating current can be reduced. Normally these motors are connected. These motors are having some special
cooling arrangements like forced air cooling, condenser type cooling in which water is circulated to cool the
temperature inside. Instead of a ball bearing, sleeve bearing are also used. For cooling the bearing, separate oil is
used.
Over Current relay, Ground fault relay: These are intended for detecting faults in the electric system connected
with the Transformer. A fault in the Transformer results in the function of these relays, which is always
accompanied by the actuation of protective devices of the Transformer.
Illumination: The illumination is defined as the luminous flux received per unit area.
Overload Relay Setting: Overload protection given for almost all motors. The overload relay setting will be of
110% in general.
25
Instrumentation | QA/QC Notes
Starting Current: Starting current of a induction motor generally will be 6 times the rated current.
Single Phase: One of the supply lines gates disconnected due to rupturing of fuse or open circuit in one of the
three supply connection. In such cases the motor continues to run on a single phase supply of 440V. If the rotor is
locked to its rated full load, it will draw excessive currents on single phasing. The windings get overheated and
damage is caused.
Megger Value: The insulation resistance value of the winding of the motor shall be checked periodically during
preventive maintenance.
For 3.3 KV motor the IR value shall be checked with 1 KV Megger.
For 11 KV motor the IR value shall be checked with 5 KV Megger.
Winding Resistance: The winding resistance of the motor shall be checked during preventive maintenance with
the bridge. The winding resistance of the three windings should be equal.
Earthing:
Generally earthing means non-current carrying metallic part of electrical equips should be earthed to avoid danger
to human life.
Grid Resistance: Grid resistance means in a industry or building the no. of earth pits joined parallel together to
get a minimum earth resistance value and the value should be less than 1.0 Ohms acceptable in the industry.
Pit Resistance: Individual pit resistance can vary according to the solid resistance and the value can be 5 Ohms
or more than that. But to get a minimum value all the pits should connect in parallel as grid.
Earth Pits: Earth pits are generally used by using charcoal, salt and G. I. pipe of 3 meters in length and 40 mm
diameter.
Another type of earth pits is plate earth electrode and mesh type electrode with copper or GI strip brought out.
Another type in gulf generally used is the solid rod of copper driven straightway into to earth to get minimum value
by driving to a depth of max 6 meters.
Earth Megger: For measuring the earth resistance earth Megger is used and the diagram given below how to
measure the earth resistance.
Safe Earth Resistance: Generally earth resistance of the total grid should be less than 1.0 Ohms which is
acceptable for safe operation in industries.
Ammeter: Load current is measured through ammeter only. In AC lower range are directly can be read through
ammeter kept in series. For larger current transformer are uses for measuring the current.
In DC Power current is measured through a shunt resistance.
Wattmeter: For measuring the power consumed by the circuit (any type of feeder) wattmeter is used and the unit
is in KWH.
Avometer: This AVO meter is used for checking the electrical circuits measuring voltage, current, resistance and
electronic components etc.
26
Instrumentation | QA/QC Notes
Shunt Resistance: In DC circuit is measured through this shunt resistance.
Transducer: They are used to change one varying parameter into other form energy. Like voltage to current to
pneumatic signals etc.
Bus Coupler: Where two different bus sections connected through an breaker (ACB or VCB or OCB) so that both
bus section supply can have an alternative feeding arrangement.
2. Why the oil samples test shall be taken from the transformer?
Ans: To check the conductivity, analyses and characteristics of the oil.
6. What is the symmetrical interrupting current rating fuse on the HV –side of transformers?
Ans: The symmetrical interrupting current rating of a fuse shall not be less than max symmetrical sub
transient fault current.
7. Find out the full load current of a Single Phase motor 220 volt 600 watts?
Ans: I = P/V = 600/220= 2.727 Ans.
10. How do you check whether the winding of a motor is good or bad?
Ans: WR (Winding Resistance), IR (Insulation Resistance).
27
Instrumentation | QA/QC Notes
11. Why should ground all electrical equipment?
Ans: To prevent the earth fault.
12. What are the two method of winding connection in 3-Phase motors?
Ans: Star Winding & Delta Winding.
14. What is the paint name which is the used in grounding cable?
Ans: Vetomens Paints.
16. If the IR value of the motor winding is very low what would you do to improve it?
Ans: Motor need over hauling.
17. What is the name of the test equipment used to measure the following?
Ans:
Current: Ammeter
Voltage: Voltmeter
Resistance: Ohm
Insulation Resistance: Megger
18. What is the different between primary and secondary cell?
Ans: Primary Cell is Anode (+)
Secondary cell cathode (-)
19. If the current is 15A what will be the size of the cable?
Ans: 6 mm2 or 10 mm2
20. What is the max speed obtained by 3 phase induction motor with normal state supply?
Ans:
28
Instrumentation | QA/QC Notes
25. What is the breather, Details about the Silica Get?
Ans: It is a small container, contains silica gel and oil. It absorbs the moisture from the atmospheric air
and allows the fresh air to the conservator.
26. What is the meant by short circuit braking current?
Ans: The rated short circuit breaking current of a circuit breaker is the highest value of short circuit
current which a circuit breaker is capable of breaking under specified condition of transient recovery
voltage and power frequency voltage. Expressed in K. A. RMS at contact separation
28. What is range of low voltage and medium voltage and high voltage?
Ans: Low Voltage: 110 ~ 380 VAC
Medium Voltage: 489 ~13.8 KV
High Voltage: 14.6 ~115 KV
29. What is the different between star and delta connection with types of motor?
Ans:
29
Instrumentation | QA/QC Notes
31. Why does control valve operate at IS psi?
Ans: On higher pressure the actuator sizes becomes bigger in area. The actual force produced by the
actuator.
Force = Pressure x Area.
= 15 psi x Area, If Area = 15"
Force produced = 15 psi x 25 in2 = 375 pounds.
Actual force acting on a control valve = 375 pounds.
Pressure Conversions:
1 PSI = 27.74”H2O
1Kg/cm2 = 14.223 PSI
1 Bar = 0.145 PSI
Kg/cm2 = 10000 mm of H2O
1 Bar = 1.0197 Kg/cm2
1 Kg/cm2 = 0.98 Bar
1 Torr = 1 mm of Hg
Common Things:
Type of Lugs: (1) Shanap Type (2) Pin Type (3) Ring Type (4) U Type
Gland Size: ½” ¾” 1”1½” 2”
Thread Type: ET (Equal Thread), BSP (British Standard Pitch), NPT (National Pipe Pitch).
Electrical:
LT – (Low Tension) – 50VAC ~ 230VAC
HT – (High Tension) – 320VAC ~460VAC
MCC – (Main Control Connection) or (Motor Control Center)
PCC – Power Control Connection
Vibration Meter (Monarch instrument Model Examiner 1000) Using to get the Vibration (mm/s)
Sound Level Meter (Extech Instrument Model 407703) Using to get the noise (dB) of motor in 3 locations:
1. Drive end.
2. Non drive end.
3. Winding.
NB: The Duration of the no load run is 4 Hrs, Every 30mm needed to get a reading.
30
Instrumentation | QA/QC Notes
Used to test the contact resistance of bas bars, breakers etc..?
Digital Earth Tester (Model: 4105A).
Portable Double Bridge (Model: 2769).
Using for winding resistance tests of voltage transformer, current transformer, etc..?
DC Dielectric Test Set (Biddle Model 220123).
Used to test the insulation resistance of cables, bus bars, breakers, VT’s, ct’s, etc…?
Digital Multimeter Model: 77iii
Programma (Freja 300)
Relay test unit for: (transformer management relay, feeder management relay, motor management relay, also used to test
the ATS of switchgear, ammeters and voltmeters
Torque wrench (model 64-046).
Power Clamp Meter (Model: Unites 93510).
True RMS AC/DC clamp meter (Tektronix Model: DCM910)
Relay Test Unit (Programma Model Sverker 750)
1. Please explain the required equipments, Tools and Consumables for Cable Pulling?
Ans:
31
Instrumentation | QA/QC Notes
5) Mark 81G e) Differential Protection
Ans:
6. Please write the name of termination tools for cable (more than 5 items)?
Ans:
7. Please draw the typical 3-wire control circuit with two start-stop push button starters?
Ans:
8. Please draw the simple forward reversing starter control circuit using “Either-or” Interlock?
Ans:
12. What is the different between guide clamp and holding clamp?
Ans:
32
Instrumentation | QA/QC Notes