CSC-160 Series Numerical Line Protection Equipment
CSC-160 Series Numerical Line Protection Equipment
Version:V1.01
Issued Date:2012.03
Note: the company keeps the right to perfect the instruction. If equipments do not agree with the
instruction at anywhere, please contact our company in time. We will provide you with corresponding
service.
1) The manual is applicable for CSC-160 series numerical line protectoion equipment.
2) Please read the manual carefully and set up, test and operate according to regulations in the manual.
If there is any special customization, please be subject to project manual and project data.
3) In order to prevent equipment from damaging, it is strictly prohibited to hot plug chips and
equipment on all socket components and contact print circuit board of the equipment.
4) Please use eligible testing apparatus and equipment to test and measure the relay.
5) If any abnormity happens to the equipment or maintenance is required, please contact service hot
line of our company in time.
1 OVERVIEW .............................................................................................................................................. 1
1.1 Application ....................................................................................................................................1
1.2 Features ..........................................................................................................................................1
1.3 protection functions configuration .....................................................................................................2
1.4 Deminsion ......................................................................................................................................5
1.6 Standard .........................................................................................................................................5
2 TECHNICAL SPECIFICATION .................................................................................................................. 6
2.1 Environmental condition................................................................................................................6
2.2 Electric insulation performance .....................................................................................................6
2.2.1 Dielectric Voltage test ......................................................................................................6
2.2.2 Insulation resistance .........................................................................................................6
2.2.3 Surge voltage test .............................................................................................................6
2.3 Mechanical performance................................................................................................................6
2.3.1 Vibration...........................................................................................................................6
2.3.2 Shock and bump ...............................................................................................................7
2.4 Electromagnetic compatibility .......................................................................................................7
2.4.1 Burst disturbance test .......................................................................................................7
2.4.2 Electrostatic discharge disturbance ..................................................................................7
2.4.3 Radio-frequency electromagnetic field disturbance .........................................................7
2.4.4 Fast transient disturbance .................................................................................................7
2.5 Safety performance ........................................................................................................................7
2.6 Thermal performance (overload ability) ........................................................................................7
2.7 Power consumption .......................................................................................................................7
2.8 Capacity of output contacts............................................................................................................8
2.9 Main technical parameters .............................................................................................................8
2.9.1 Rating parameters.............................................................................................................8
2.9.2 Setting range of AC circuit (within 10 percent error range) .............................................8
2.9.3 Current differential protection ..........................................................................................8
2.9.4 Distance protection...........................................................................................................8
2.9.5 Earth fault protection........................................................................................................8
2.9.6 Overcurrent protection .....................................................................................................9
2.9.7 Overload protection..........................................................................................................9
2.9.8 Low frequency load shedding ..........................................................................................9
2.9.9 Low voltage load shedding ..............................................................................................9
2.9.10 Three-phase reclosing ......................................................................................................9
2.9.11 the whole system operation time (including inherent operation time of relay) ................9
2.9.12 Fault locator error .............................................................................................................9
2.9.13 Fiber interface ..................................................................................................................9
2.10 Transport and storage...................................................................................................................10
3 PROTECTION PRINCIPLE ...................................................................................................................... 11
3.1 Structure of the protection program ............................................................................................. 11
3.2 Startup element ............................................................................................................................ 11
3.2.1 Phase current difference and zero sequence current abrupt startup element .................. 11
3.2.2 Zero sequence current startup element ........................................................................... 11
3.2.3 Over current startup element ..........................................................................................12
3.2.4 Power swing detection element ......................................................................................12
3.3 Current differential protection .....................................................................................................12
3.3.1 Function features ............................................................................................................12
3.3.2 Connection mode of current differential protection and communication system...........12
3.3.3 Startup element of current differential protection ..........................................................13
3.3.4 Operation characteristics of current differential protection............................................14
3.3.5 CT related discrimination of current differential protection ..........................................15
3.3.6 Connector of current differential protection ...................................................................16
3.3.7 Communication of current differential protection ..........................................................16
3.3.8 Illustration of frame checkout ........................................................................................18
3.3.9 Remote transmission and remote tripping function of current differential protection ...18
3.3.10 Testing method of current differential protection ...........................................................19
3.4 Pilot Distance and Pilot Zero Sequence Directioanl ........................................................................19
3.4.1 Blocking mode ....................................................................................................................19
3.4.1.1 Equipment send signal .....................................................................................................20
3.4.1.2 Equipment and Carrier .....................................................................................................20
3.4.1.3 Logic about pilot channel such as remote send signaland so on ......................................20
3.4.1.4 Pilot protection alarm.......................................................................................................21
3.4.2 Permissive mode .................................................................................................................21
3.4.2.1 Illustration of equipment sending signal ..........................................................................21
3.4.2.2 Three phase tripping to send signal..................................................................................22
3.4.2.3 Protection equipment alarm .............................................................................................22
3.4.3 Weak Infeed End (Permissive and blocking mode) ............................................................22
3.4.3.1 Specification about the operation logic when the weak source side do notstartup ..........22
3.4.3.2 Specification about operation logic when the weak source side protection startup .........22
3.4 Distance protection ......................................................................................................................23
3.4.1 Phase selector .................................................................................................................23
3.4.2 Distance component .......................................................................................................23
3.4.3 Asymmetric and symmetric fault starting component during power swing ...................25
3.4.4 Transitional fault ............................................................................................................25
3.4.5 Parallel line successive tripping function (only enable 300ms after startup) .................26
3.4.6 Asymmetric fault successive acceleration function .......................................................27
3.5 Overcurrent protectionafter VT failure ........................................................................................27
3.6 Earth fault protection ...................................................................................................................27
3.7 Overcurrent protection .................................................................................................................28
3.7.1 Operation conditions of overcurrent protection .............................................................28
3.7.2 Overcurrent directioncomponent....................................................................................28
3.7.3 Voltage blocking of overcurrent protection ....................................................................29
3.8 Overload protection .....................................................................................................................29
3.9 Low frequency load shedding ......................................................................................................29
3.10 Low voltage load shedding ..........................................................................................................30
3.11 Three phase auto-reclosing ..........................................................................................................30
3.12 Circuit breaker failure (CBF) startup current element .................................................................31
3.13 Inverse time characteristic protection ..........................................................................................31
3.14 Slow reclosing function ...............................................................................................................32
3.15 Abnormity detection and discrimination .....................................................................................32
3.15.1 CT failure supervision ....................................................................................................32
3.15.2 VT failure supervision (large current grounding system criterion) ................................32
3.15.3 VT failure supervisionof line reference voltage .............................................................33
3.15.4 Broken dection of control circuit ...................................................................................33
3.15.5 Circuit breaker status detection ......................................................................................33
3.15.6 3I0 polarity self-supervision ...........................................................................................33
3.15.7 Self-supervision of current and voltage phase sequence ................................................33
3.15.8 Self-supervision of protection equeipment.....................................................................33
3.16 Protection logic diagram ..............................................................................................................34
3.16.1 Logic diagram of current differential protection. ...........................................................34
3.16.2 Logic diagram of distance protection .............................................................................37
3.16.3 Logic diagram of earth fault protection..........................................................................38
3.16.4 Logci diagram of overcurrent and overloadprotection. ..................................................39
3.16.5 Logic diagram of low frequency load shedding .............................................................40
3.16.6 Chart of low voltage decrease load. ...............................................................................40
3.16.7 Logic diagram of three-phase reclosing with one shot...................................................40
1 Overview
1.1 Application
CSC-160 series numerical line protection equipment can be applicable for power transmission line
of large current grounding system with 110kV&below and neutral point directly grounding and
power transmission line of small current grounding system without neutral point grounding or
grounding through arc suppression coil.
1.2 Features
Hardware system with high performance, high reliability and vast resources
32 byte SCM applying integration of DSP and MCU and hardware system with high performance
guarantee the equipment to carry out real time calculation on all relays. It also keeps the advantage
of bus inside chips which is important to keep the high reliability of the equipment.
It applies bran-new front plug/pullcombination structure which keeps the advantage of convenient
maintenance while concurrently with advantage of strong and weak electricity separation and
strong electricity loop cabling directly from module of rear plug/pull style.
Large capacity fault record wave, compatible COMTRADE format records fault data of the whole
process and stored record wave data no less than 24 times. Complete event record and operated
report, no less than 2000 operated reports and 2000 operation records can be stored, moreover, the
recording data will not be lost after power disconnection.
Intelligentized design of all modules internal the equipment realizes real time self-supervision
completely of all modules of the equipment.
Analog sampling circuit applies dual A/D redundancy design and performs real time
self-supervision of analog sampling circuit.
Relay monitoring curciut applies new method which could detect integration of relay excitation
circuit coil and monitor status of output contact and realize monitoring and abnormity alarm of
relay status.
DI circuit detection applies new method. DI status is collected simultaneously through two
channels ofoptical coupling isolation and discriminated.
-1-
CSC-160 series numerical line protection equipment Manual
It can be applicable for systems of two ends, three ends(T connection) circuit, weak infeed end or
load side, circuit with loads fluctuating frequently, voltage recovery slowly to strat reclose for a
long time and so on.
At the same time, software modulization design can flexibly configure protection function so as to
meet different requirements of user and simplify setting management.
It applies large liquid crystal display (LCD) which could real time display information such as
current, voltage, power, frequency, status of connector, setting group and so on. The equipment
provides four shortcut keys which could realize “one-key” operation and facilitate operation of
field engineer.
The equipment can record operation process and kinds of calculation value of each element
equipped in the equipment. It can analyze the whole process of protection operation through
analysis software CSPC.
The equipment can provide two fast electric Ethernet interfaces (optical fiber Ethernet interface
available), LonWorks network interface and RS-485 interface. It can apply IEC60870-5-103
protocol or CSC2000 protocol of Sifang Corporation to realize communication of substation
automation system and protection information management system.
Current differential protection can configure two fiber communication interfaces and perform the
communication mode of one main and one standby of two channels to meet dual channel
switching requirement of regular wiring connection. It can also meet the requirement of three-ends
differential protection used for “T” connection transmission line.
Dedicated fiber communication mode: data interface transmission at the speed of 2Mbps.
Multiplexing communication mode: data (E1) interface transmission at speed of 2Mbps and data
(PCM) at the same direction interface transmission is available.
More advanced calculation formula dR/dt during system power swing to distinguish power swing
and fault occurrence during power swing fast and correctly which ensures to clear the internal
fault instantly when system power swing while blocking reliably for the external fault.
Different functions configuration of CSC-160 series different type please see the table 1 and table
2 which are typical configuration of the equipment. Users can select corresponding specification
according to practical requirement. If the system need to configure the protection function showed
-2-
CSC-160 series numerical line protection equipment Manual
in table 1-1 and 2-1, please indicate the requirement in the ordering.
Table 1 function configuration of solid grounding system line protection equipment
CSC-163T
Protection types CSC- CSC- CSC- CSC- CSC-
(applicable for T
Functions 161A 161B 162A 163A 163B
connection)
Current Differential(C/D) √ √ √
Pilot Distance(Pilot Z)
√
Pilot Zero Current(Pilot 3I0)
3 stages Ph-Ph Distance(Z_PP) √ √ √ √
3 stages Ph-E Distance(Z_PE) √ √ √ √
2 stages Over Current for VT
√ √ √ √
Fail(OC_VT Fail)
3 stages Over Current(O/C)
(with Directionalal Voltage √ √
Blocking)
4 stages Zero Sequence Current(3I0) √ √ √ √ √ √
Overload √ √ √ √ √ √
3-Ph Automatic Reclose(Reclose) √ √ √ √ √ √
Breaker Circuit Fault(CBF) √ √
-3-
CSC-160 series numerical line protection equipment Manual
Illustration:
In above figure, mark Z1 is applicable for single tripping coil while Z2 for double tripping coils.
Whether operation module and switch module are needed, please indicate in the order.
2) CSC-163T and CSC-167T is fiber double channel which can be used for two-end system
double channel redundancy hot backup or three-end system. CSC-163A, CSC-163B, CSC-167A
-4-
CSC-160 series numerical line protection equipment Manual
1.4 Deminsion
Dimension of case
Dimension of cutout
The equipment applies standard 19inch width and 4U height enclosure which complies with
IEC60297-3. The whole equipment is installed with built-in manner and then connected. Size of
opening hole for installation sees figure 2.
1.6 Standard
-5-
CSC-160 series numerical line protection equipment Manual
2 Technical specification
2) Relative humidity: month average largest relative humidity of the dampest month is 90
percent. At the same time, month average lowest temperature of the month is 25℃ and
without coagulated dew in surface;
4) Use location has no danger which endangers safety of the equipment such as fire, explosion,
and erosion and so on, also including vibration, shock and bump beyond regulation of the
instruction.
2.3.1 Vibration
The equipment can withstand level I vibration response and vibration endurance test regulated by
GB/T 11287(idt IEC60255-21-1).
-6-
CSC-160 series numerical line protection equipment Manual
The equipment complies with enclosure protection level regulated by national standard GB 16836
no lower than IP20, and the safety kind is I.
Thermal performance (overload ability) of the equipment complies with following regulations of
DL/T 478-2001:
1) Current circuit: continuously work at 2 times of rated current, 10s permitted at 10 times of
rated current and 1s permitted at 40 times of rated current;
2) Voltage circuit: continuously work at 1.2 times of rated voltage and 10s permitted at 1.4
times of rated voltage.
Power consumption of the equipment complies with following regulations of DL/T 478-2001:
2) Current circuit: when In=5A, no larger than 1VA/phase; when In=1A, no larger than
0.5VA/phase;
-7-
CSC-160 series numerical line protection equipment Manual
1) Capacity of tripping contact: for the DC inductive circuit with voltage no larger than 250V,
current no larger than 1A and time constant L/R as (5±0.75)ms, current permitted to work for long
time is no larger than 5A;
2) Capacity of other contacts: for the DC inductive circuit with voltage no larger than 250V,
current no larger than 0.5A and time constant L/R as (5±0.75)ms, contact cut capacity is 30W and
current permitted to work for long time is no larger than 3A.
2) AC voltage:
4) Frequency: 60Hz.
3) Current: 0.08 In ~30 In ( In presents CT secondary rated value(1A or5A), following the
same).
-8-
CSC-160 series numerical line protection equipment Manual
2.9.11 the whole system operation time (including inherent operation time of relay)
1) Operation time of differential protection: when 2 times of setting value, no longer than
30ms;
3) Operation time of phase to phase and phase to earth distance zone I: within 0.7 times of
setting value, it is no longer than 25ms;
4) Operation time of earth fault protection stage I: when 1.2 times of setting value, it is no
longer than 25ms;
5) Operation time of overcurrent stage I: when 1.2 times of setting value, it is no longer than
25ms.
For metallic faultt, it is no larger than ±2%. When larger arc resistance exists, fault locator error
will increase.
-9-
CSC-160 series numerical line protection equipment Manual
Sensitivity of Sending
Transmission line Light-wave Fiber
Fiber mode light level
length(km) length(nm) linker type
reception(dbm) (dbm)
<40 Single-mode 1310 -38 >-8 FC
40~60 Single-mode 1310 -38 >-4 FC
>60 Single-mode 1550 -38 >-3 SC
The equipment should be stored in a room at temperature -10℃~+40℃ and relative humidity no
larger than 80 percent and without dangers of erosion and easy to burn and explosive goods and so
on in the air around. During transportation, it should avoid violent vibration, shock and bump.
-10-
CSC-160 series numerical line protection equipment Manual
3 Protection principle
CSC-160 series protection equipment applies modularization design idea. For different type, only
functions configuration of each protection function module is different. Instruction of equipment
software is carried on according to function module. Following introduction function included in
CSC-160 series equipment.
Protection CPU software includes main program, sampling interruption program and fault process
interruption program.
As main program running normally, it will execute sampling interruption program once every
sampling interval time and distinguish collection of electric quantity, record wave and abrupt
startup and so on. Fault process interruption program fulfills discrimination of steady-state
quantity startup, protection logic, VT fail, CT fail, control circuit failure, UX phase and so on. If
the abnormity occurs, it will issue corresponding alarm signal and report. For severe alarm, it will
block protection output when sending signal, for common alarm, it will send signal and remind
running personnels of checking and handling.
Protection startup element is used to open protection power supply of tripping output relay and
start the protection fault process program.
3.2.1 Phase current difference and zero sequence current abrupt startup
element
Criterion: △I>IQD or △3I0>IQD (equipment with earth fault protection)
Where: △I=| |iK-iK-T|-|iK-T-iK-2T| |, means three different phases such as AB, BC and CA;
△ 3I0 means zero sequence abrupt current; IQD means startup setting.
When any abrupt quantity exceeds startup threshold for 3 times continuously, protection startup.
Abrupt current gained through this way can compensate unbalance current caused by frequency
change of power system.
It is a kind of startup element set to avoid inadequate sensitivity of phase current difference abrupt
startup element when long-distance fault or fault with large arc resistance happens. Criterion:
Zero sequence current >0.9*min(setting of earth fault protection stage I, II, III and IV), and the
element operated after 30ms.
-11-
CSC-160 series numerical line protection equipment Manual
It is a kind of startup element set to avoid inadequate sensitivity of abrupt startup element.
Criterion:
Any phase current>0.9*min (setting of overcurrent stage I, II and III), and the element operated
after 30ms.
It is a kind of element set to detect power swing under normal running status of the system.
Criterion: any phase current>setting of power swing current and lasting for 30ms.
2) CT failure blocking function. Unblocking can be set by control word after CT failure;
5) 2Mbps high speed communication interface and dedicated channel (2Mbps) can be applied.
It can multi-connect G.703 standard 64kbps same directioninterface and also multiplex 2Mbps (E1)
interface;
6) Dual channel redundancy function. The two channels can apply thecombination of
dedicated or complex, 64kbps or 2Mbps respectively;
7) Communication channel through protection can transfer the commands of “Tele-Trip” and
“Tele-Answer”;
9) Data communication among protections applies 32 bit CRC checkout which has strong
ability to resist error code;
10) Facilitate test and debugging: has the function of channel circle;
11) Applicable for two-side power supply system, eak sourcesystem and T connection.
-12-
CSC-160 series numerical line protection equipment Manual
Side M Side N
IMA? B? C CSC
IMA? B? C
CSC TXA series RXA
series current
current RXA TXA differentia
differential TXB RXB l
protection protection
equipment RXB INA? B? C Dedicated fiber INA? B? CTXB equipmen
Relay on side M with speed of 2M t side N
Relay on
Side M
RXB TXA
RXA
TXB
CSC series
current
differential
protection
RXA TXA
Communicatio Digital Communicatio
Digital
n interface transmission n interface
transmission Protector on
Protector on device device side N
side M
The startup element is used for protection startup on weak source side. Criteria as follows:
b) Any phase differential current is larger than setting of phase current differential;
c) Phase voltage or phase to phase voltage is lower than 0.6 times of rated value of
corresponding voltage.
-13-
CSC-160 series numerical line protection equipment Manual
If weak source side has no VT and can not provide voltage, protection on power side can select
function of “Start InterBlk Off” by control word. Therefore, protection on power side can not be
blocked by opposite-side startup element and trip fast.
The startup element is used to guarantee reliable startup of protection on remote fault sidewith
large resistance grounding and criteria are as follows:
b) Zero sequence differential current is larger than operation value: ID0 > I0Z;
c) Both of the local side and opposite side have abrupt voltage (ΔUф>8V or Δ3U0 >1.5V).
IDZ is the setting of “I_PH C/D” which is set according to larger than 2.5 times of capacitive
current. ICap is actually measured capacitive current when running normally.
In formula: I D0=│(ÌMA+ ÌMB +ÌMC) + (ÌNA+ ÌNB + ÌNC)│ is zero sequence differential current.
IB0 =│(ÌMA+ ÌMB +ÌMC) – (ÌNA+ ÌNB + ÌNC)│ is zero sequence restraining current.
-14-
CSC-160 series numerical line protection equipment Manual
ID0>I0Z 0.75
I D0>0.75IB0 I0Z
IB0
In the formula, I0Z is the setting of “I0 C/D” which is set according to sensitivity of internal high
resistance grounding fault;
Usually, grounding fault of line can be reflected correctly by phase current differential while zero
sequence current differential protection only operated as backup protection of grounding fault
through large arc resistance; therefore, tripping with delay time. The delay time can be set
(shortest 100ms). Operation of zero sequence current differential element can be set as permanent
tripping or three phase tripping by control word.
Configuration of current differential protection of three-side system is same with two-side system,
only difference is calculation method of differential current and restraining current:
I D0=│(ÌMA+ ÌMB +ÌMC) + (ÌNA+ ÌNB + ÌNC) + (ÌTA+ ÌTB + ÌTC)│ is for zero sequence differential
current.
IB0 =│(ÌMA+ ÌMB +ÌMC) – 〔 (ÌNA+ ÌNB + ÌNC) + (ÌTA+ ÌTB + ÌTC) 〕│ is for zero sequence restraining
current.
The formula supposes mode value of zero sequence current on side M is largest.
When CT transformation ratios on two sides of the line are different, the current on two sides can
be consistent according to “CT COMP Ratio” of setting. For equipment with larger CT primary
rated current, compensation factor is set as 1; compensation factor of other equipments is set as
the largest value of primary rated current divided by CT primary rated current on the side.
2) CT failure detection
CT fail detection please sees following illustration: section 3.15 “failure detection and
-15-
CSC-160 series numerical line protection equipment Manual
3) CT saturation detection
1) CSC-160 series current differential protection can apply following communication modes:
The equipment can set clock speed as “2Mbps” or “64kbps” through differential control bit.
The equipment can set clock mode as “Inner_Clock” or “external clock” through differential
control bit.
CSC-163/7A and CSC-163/7B is single channel and sets clock mode and speed of channel A.
CSC-163/7T is dual channels and sets clock modes and speeds of channel A and B respectively.
When applying dedicated fiber channel, settings of equipment on both sides are set as
“Inner_Clock”, i.e. using Inner_Clock of the equipment to send data and receiving clock is taken
from received data flow. In order to upgrade performance of differential protection, it is suggested
to apply speed of 2Mbps.
When protecting multiplexing PDH digital communication system 2Mbps (E1) interface, settings
of equipment on both sides should be set as “Inner_Clock”.
When protecting multiplexing PDH digital communication system 2Mbps (E1) interface, clock
mode setting of equipment is related with mapping manner of 2Mbps (E1) signal to VC12: when
VC12 applies asynchronous mapping manner, settings of equipment on both sides should be set as
-16-
CSC-160 series numerical line protection equipment Manual
“Inner_Clock”; when VC12 applies synchronous mapping manner, settings of equipment on both
sides should be set as “Outer_Clock”. See table 3.
Table 3 Clock setting of multiplexing 2Mbps (E1) interface
PDH SDH
Mapping manner of Asynchronous Synchronous mapping
VC12 mapping manner manner
Clock mode of
“Master-Master” “Master-Master” “Slave-Slave”
protection
When protection complexing digital communication system with the same direction interface
64kbps PCM, settings of equipment on both sides should be set as “Outer_Clock”. Both applying
system synchronization clock, i.e. both sending clock and receiving clock of data are taken from
received data flow. It demands clocks of primary equipment on both sides should be set according
to requirement shown in table 4, or it will produce periodic sliding poise. When multiplexing the
same direction interface 64kbps, clock of protection should be set as “Slave-Slave” mode.
Table 4 Clock setting when complexing the same direction interface 64kbps
PDH SDH
Mapping manner of Asynchronous Synchronous mapping
VC12 mapping manner manner
Clock mode of
“Slave-Slave” “Slave-Slave” “Slave-Slave”
protection
Clock mode of PCM “Master-Slave” “Master-Slave” “Slave-Slave”
Current differential protection can be set as “Master” (1) or “Slave” (0) by control word for
synchronization of protection sample.
Current differential protection on two sides should be set as “Master” on one side while “Slave”
on the other side; for three-side system, it must be set as “Master” on one side while “Slave” on
the other two sides. The setting has nothing to do with channel mode.
M Master side Slave side N
RELAY RELAY
t m1
Sending data on t n1
side M
t p1
t m2 t n2
t n*
td
t m3
t n3
t n3*
t p2
t m4
t n4
t m* Sending data on
side N
t m5
t n5
-17-
CSC-160 series numerical line protection equipment Manual
In order to ensure synchronization of protection samples on two sides, set as: one side of a
“Slave” sends one frame synchronization requiring command, including sample number;
“Master” returns a frame data after receiving command sent by “Slave”, including sample
number of “Master” and corresponding information, for example, time and so on; after
receiving corresponding data message from “Master”, “Slave” can calculate communication
transmission delay and sample time difference t of the two sides. According to deviation of
sample time, “Slave” can confirm adjustment times. Through several micro-adjustment of
protection on sample time untill t 0 , samples of equipment on two sides fully
synchronize.
The advantage of this synchronization method, when samples of equipment on both sides
synchronize and differential protection algorithm is finished, only need to unify sample
numbers of equipment on both sides to ensure the correctness of algorithm, without additional
compensation calculation for delay of communication. This is not only simple, but more
important is, the calculation process of differential protection algorithm independent of
communication transmission delay. This means differential equipment perform sample
synchronization by this means can adapt communication system when communication route
changes. The equipment can adapt transmission delay for 18ms caused by changes of
communication route and the synchronizations error is not larger than 1.
When protection works normally, protection on two sides (three sides) perform data
communication. Protection on receiving side checks received data by CRC redundant circle check
code after receiving a frame of data. When CRC checks that one frame of data is wrong, it will
abandon the frame of data which equals 3ms delay of protection operation. When the received
data is checked correctly by CRC, the frame of data will be effective which is available for
protection calculation.
2) Remote tripping
-18-
CSC-160 series numerical line protection equipment Manual
In order to make opposite protection tripping fast when fault occurs at bus and between
breaker and current transformer, the equipment provides a “DI_TELE_TRIP” DI terminal to
transmit operation signal of protection such as bus differential protection and circuit breaker
failure protection and so on.
When protection startup, the the DI of “DI_TELE_TRIP” is active, send signal to opposite. After
receiving “DI_TELE_TRIP” signal, the opposite will distinguish whether thecondition in setting is
met (startup or distance protection zoen II is in forward direction) and permanent tripping.
Setting “Chan Inf” control bit of the equipment as 1 and setting as “Master” and “Inner_Clock”,
butt joint RX and TX of the equipment by tail fiber, perform single equipment self-loop to
simulate internal fault.
In order to facilitate user carrying out the whole set of test with channel, the equipment
provides function of remote loopback test with channel.
After setting differential setting of equipment on both sides according to practical running
situation, placing “channel circle” control bit of equipment on side M on 1, switching
connector in maintenance status on side M, short circuit fault simulation can be performed in
the zone on side M. at this time, equipment N receives sample message from side M and then
transmits it to side M.
CSC-160 pilot protection includes Pilot Distance Phase to Phase, Pilot Distance Phase to Earth,
Pilot Zero Sequence Direction, and Distance polygon characteristic.
CSC-160 pilot protection is applicable for two channel mode: permissive mode and blocking
mode.
-19-
CSC-160 series numerical line protection equipment Manual
The equipment provides two delay times for confirming the channel signal, one is, each side is
permitted to stop signal till receiving signal for 5ms, two is, after local-side stopping signal, not
receiving the blocking signal for 8ms, the protection can operate.
To prevent the power reverse: to prevent mal-operation for loop power reverse, from reverse
direction to forward direction, to confirm stopping signal after 40ms delay time, after stopping
signal, the protection can trip if not receiving the blocking signal for 20ms.
If the remote sending signal is implemented by protection, remote sending signal, other relay
stopping signal, circuit breaker position stopping signal, channel self-checking manually and so on
are implemented by protection, carrier is contected with relay contacts of pilot sending signal,
relay contect contacts of carrier receiving signal output and alarm. Especially note, when the
control contacts of sending signal is opening, the carrier should stop signal immediately, which
need to be set for some type of carrier.
If the remote sending signal is implemented by carrier, carrier connect with the contacts of pilot
sending signal and stopping signal, the protection connect with receiving signal output of carrier.
After receiving opposite-side blocking signal, if local-side TWJ not operation, then sending signal
for 10s immediately, if local-side TWJ tripping, then send sending signal with time delay 160ms.
Especially note, if sending signal is implemented by protection, remove the carrier loop of remote
sending signal.
2) Channel test
Channel test manually: kick the channel test key, when the DI of channel checking is active,
local-side send sending signal, local-side stopping signal after 200ms (after opposite-side
protection receiving local-side signal, sending signal for 10s by remote sending signal logic),
local-side protection receiving opposite-side signal till 5s, local-side send a signal for 10s again
and channel test finished.
Channel test periodically: users can select the fixed time everyday to do the channel test
-20-
CSC-160 series numerical line protection equipment Manual
automatically by the control word, same as the channel test manually, but only for pilot protection
enabled.
Remote controlling channel check: for the integration automation station, remote controlling
checking for pilot channel can be performed through network.
When the DI of “BB/CBF OPTD”is active, relay stop signal immediately, regardless of theactive
time of DI, stopping signal for 160ms and then reture, and work well only when the protection
startup.
When relay do not startup, the DI of “CB OPEN” is active, after receiving opposite-side signal,
and after stopping signal for 160ms, sending a signal again. If the protectionstartup, three phase
circuit breaker position stopping signal is blocked automatically.
2) Receiving signal DI is active for a long time, report “Pilot RECV Err”;
3) In the process of channel self-checking, receiving signal has fault, report “Pilot CHAN Err”;
At the normal running station, each side protection separately send channel monitoring signal to
opposite-side protection. When the fault is discriminated as forward direction and internal fault,
the contacts of protection sending signal closed, channel equipment not sending signal but
permissive signal to permit opposite-side tripping. When the local-side receives opposite-side
permissive signal, and the internal fault is discriminated, start to trip.
-21-
CSC-160 series numerical line protection equipment Manual
When the DI of other relay operation to stop signal is active, relay sends a permissive signal for
160ms and then return, this work only when protection startup.
When the protection do not startup and the DI of “CB OPEN”is active, at the same time receiving
permissive signal from opposite-side, send permissive signal for 160ms. After relay startup,
remove three phase tripping to stop signal automatically.
2) Running normally, the DI of “blocking open” is active, report “Pilot Comm Alarm”.
When the weak infeed end function enabled, the equipment can meet the requirement below:
1) Power side protection can trip fast for internal fault, when the protection startup and meet the
condition of the weak infeed end, if the weak infeed end tripping function enabled, the weak side
protection can trip.
2) Applicable for permissive mode or blocking mode, achieve the weak infeed end function.
3.4.3.1 Specification about the operation logic when the weak source side do
notstartup
When the weak source side protection do not startup, weak source side feedback conditions as
below:
1) At least one phase voltage or phase to phase voltage is less than 0.5Un.
When meeting above conditions, weak source side protection stop signal (blocking mode) or send
signal (permissive mode), to ensure that power side protection can trip fast for internal fault.
3.4.3.2 Specification about operation logic when the weak source side
protection startup
The conditions of weak source side protection stop signal (blocking mode) or send signal
(permissive mode):
1) At least one phase voltage or phase to phase voltage is less than 0.5Un.
2) Protection does not trip for forward direction and reverse direction.
-22-
CSC-160 series numerical line protection equipment Manual
When meeting above conditions, weak source side protection stop signal (blocking mode) or send
signal (permissive mode). If the weak infeed end tripping function enabled, after weak source
sideconfirm the signal, the weak source side protection can trip.
When the different type of fault happens in different system, the characteristic of current and
voltage is different. For different characteristic of faults, various phase selection principles is
applied for the equipment to to meet the requirementof different system. At the fault initial stage
after abrupt current element startup, the abrupt current phase selector is applied. If the abrupt
current element does not startup or 20ms later of abrupt current element startup, the symmetric
component phase selector is adopted. When fault happens and characteristic of current is not clear,
combine with low voltage and impedance phase selector.
Distance protection of large current grounding system includes three zones of phase to phase
distance protection and three zones of phase to earth distance protection, and distance protection
of small current grounding system includes three zones of phase to phase distance protection.
Enable or disable each zone of distance protection is controlled by distance protection connector.
For the close-in short-circuit or three-phase short circuit, distance protection applies memory
voltage to distinguish the direction (voltage before fault happening shift two cycles to compare
with current after fault happens). For asymmetric fault, distance protection applies negative
sequence direction element to discriminate. Negative sequence direction component please see
figure 9.
-23-
CSC-160 series numerical line protection equipment Manual
3I2
Forward direction area of negative Forward
direction
sequence direction element is:
18°≤arg(3I2/3U2)≤180°
18° 3U2
reverse area of negative sequence
18°
direction element is:
Reverse
-162°≤arg(3I2/3U2)≤0° direction
Figure 9
Distance measurement component calculates impedance value of corresponding loop by real time
voltage and real time current. Impedance calculation applies combination of differential equation
and Fourier filter to calculation six kinds of impedances, i.e. ZA, ZB, ZC, ZAB, ZBC and ZCA.
dI
Algorithm for calculation of phase to phase impedance: U=L + RI, =AB; BC; CA
dt
d ( I K X 3I 0 )
Algorithm for calculation of grounding impedance: U=L +R (I+Kr3I0), =
dt
A; B; C
Operation characteristics of distance protection are polygon characteristics (see figure 10), where
independent setting R can meet different requirements of long and short lines, improve the ability
of short line of transition resistance and the ability of long line to avoid overload impedance.
Appropriate selection for upper border and declining angle of polygon can increase the ability of
the protection to avoid overreach in case of external fault.
Figure 10
Setting of small rectangle operateion zone is used to ensure reliability of distance protection
operation when close-in fault happens.
-24-
CSC-160 series numerical line protection equipment Manual
5
When XDZ≤ , equal to XDZ/2
In
Value of X
5 2 .5
When XDZ> , equal to (In=1A、5A)
In In
Value of R 8 times of the minimum between above value of X and
RDZ/4
5) Trip selection of distance protection
According to the requirement of system, “Z_PP Trip N_A/R On” and “3rUp Trip N_A/R On” can
be enabled. If phase to phase fault and fault in range of zone III happens, distance protection
issues permanenttripping command to avoid enlarging influence range of fault.
3.4.3 Asymmetric and symmetric fault starting component during power swing
Distance protection zone I and II of the equipment can be selected by control word with power
swing blocking or without power swing blocking. When selecting “with power swing blocking”,
zone I and II are only enabled within 150ms after startup of abrupt current startup element (zone II
is fixed). And later, distance protection zone I and II are enabled by asymmetric and symmetric
fault component.
|I0|>m1|I 1| or |I 2|>m2|I 1|
In order to avoid unwanted operation of protection caused by unbalance output of zero sequence
and negative sequence current when power swing system removed, protection operates with 50ms
delay.
-25-
CSC-160 series numerical line protection equipment Manual
3.4.5 Parallel line successive tripping function (only enable 300ms after
startup)
3.4.5.1 Parallel line successive tripping function with two-side source
It is performed by operation of distance zone III of adjacent line. See figure 11.
M L1 K1 N
AC DL1 DL2 AC
DL3 L2 DL4
Figure 11
Fault beginning with ZIII operation of DL3. When DL2 is opened by instantanous stage tripping, ZIII
of DL3 will return immediately and send an “acceleration signal” to ZII of DL1 at the same time. ZII
of DL1 receives “acceleration signal” and ZII acceleration operation to trip DL1 when the following
acceleration condition is met:
3) No acceleration signal received at the beginning of fault happen and then receiving
acceleration signal from another line of the same side;
4) The line ZII doesn’t return after a short 20ms delay when it meets condition 2).
3.4.5.2 Successive acceleration function of protection on load end for one side source of parallel line
Side M without power supply, which means load end. When the fault happens at location K, ZIII of
DL3 cannot operate; therefore, it can not meet the conditions of successive acceleration operation
mentioned above. But, the current change monitored by protection on load end before and after
tripping of opposite side DL2 to perform acceleration function. At the beginning of fault
occurrence, current direction of DL3 flows from line to bus, ZIII of DL3 can’t operate; after DL2
trips, the current monitored by protection of DL1 and DL3 will increase abruptly compared to fault
initial stage, according to the following criteria:
1) Parallel line successive acceleration connector enabled; control word bit “double line load
end” enabled;
3) No acceleration signal is received sent by another line (DL3) of the same side;
5) Another line (DL3) of the same side has current (threshold 0.1In);
6) ZII of the local side meets the conditions mentioned above and doesn’t return with 40ms
delay.
At this time, distance zone II of the local side will accelerate to operate and trip DL1.
-26-
CSC-160 series numerical line protection equipment Manual
A B C A B C
DL1 DL2
Ih
AC K2 AC
Figure 12
When asymmetric fault happens on location K2 of the line terminal, no-fault phase flow load
current Ih. After the acceleration protection of side N trips DL2, three-phase tripping DL2, no-fault
phase current Ih is removed. Therefore, protection of side M can apply current disappearance of
non-fault phase of the same side to confirm the CB of opposite breaker tripped to accelerate
operation of distance zone II of the same side to operate and trip DL1.
3) Current of one phase changes from with current (larger than 0.16In) when fault happens to
without current (smaller than 0.08In);
4) Distance zone II of the local side meets condition 2) and doesn’t return with short time
delay of 40ms.
At this time, distance zone II of the local side accelerates to operate and trip DL1.
Note: If distance zone II cooperates with distance zone II of next level line, the equipment should
disable the asymmetric fault successive acceleration function.
Distance protection will be disabled after VT failure, for the equipment equipped with distance
protection, two stages of overcurrent protection after VT failure is equipped. The protection
without direction and voltage blocking, in which is enabled automatically if the distance
protection connector is enabled after VT failure.
Earth fault protection includes four stages of earth fault protection and one stage of earth fault
acceleration protection (optional). Enable or disable the four stages of earth fault protection is
controlled by earth fault protection connector.
-27-
CSC-160 series numerical line protection equipment Manual
18°≤arg(3I0/3U0) ≤180°(figure 13), and 3I0> setting of earth fault stage I, II, III and Ⅳ
18°
18° 3U0
Figure 13
According to the requirement of system, “3rUp Trip N_A/R On” can be enabled by control word.
If enabled, earth fault protection stage III and Ⅳ will block reclosing function when operate.
Overcurrent protection includes three stages of overcurrent protection and one stage of overcurrent
acceleration (optional). Enable or disable three stages of overcurrent protection are controlled by
overcurrent connector.
According to demand of system, you can select “3rUp Trip N_A/R On”. At that time, overcurrent
stage III closes down reclose when operated.
2) Overcurrent element meets the voltage condition (with or without voltage blocking can be
enabled or disabled by control word);
Direction component I U
-28-
CSC-160 series numerical line protection equipment Manual
A IA UBC
B IB UCA
C IC UAB
Forward area
U
30°
Overload protection and overload tripping can be enabled or disabled by control word.
If overload tripping is not enabled, the protection will alarm according to “overload time” in
setting when overload current is larger than the setting. If overload tripping is enabled, the
protection will alarm overload with 30s and trip according to “overload time” in setting when
overloaded. The overload protection trip permanently and block reclosing function.
In addition, when current is larger than setting of power swing current setting for 30s, overload
alarms.
Enable or disable low frequency load shedding function is controlled by low frequency connector.
The component adopts UAB hardware frequency measurement method to calculate frequency,
operation precision reach to 0.02Hz, and the UBC software calculate frequency for monitoring.
Once the inconsistency of frequency measurement of software and hardware is detected, alarm to
remind the engineer with time delay confirmation, and block low frequency load shedding to
guarantee the reliability of low frequency load shedding operation. The operation conditions are as
follows:
2) Positive sequence voltage U1 > voltage blocking setting of low frequency load shedding,
-29-
CSC-160 series numerical line protection equipment Manual
3) df/dt < slipping difference blocking setting of low frequency loading shedding [distinguish
fault situation, electric machine reverse charge and active power vacancy, if blocked, need
frequency recovery (f > 59.5Hz) to enable low frequency load shedding];
4) Circuit breaker closed (TWJ distinguish) or has current (current of any phase larger than
0.1In, enabled or disabled by control word);
Low frequency operation when all conditions mentioned above are met and then permanently trip
and block reclosing. VT failure block the component till voltage recovers.
Enable or disable of low voltage load shedding is controlled by low voltage load shedding
connector.
Criteria are:
1) Current of any phase (IA, IB and IC) > 0.04In or circuit breaker is in closing status (TWJ
position distinguish);
2) UXX > 30V (all of the three line voltage must meet the condition), and negative sequence
voltage U2 < 5V;
Note: UXX is line voltage. The lower limit of 30V for the consideration that when voltage is lower
than 30%Un (line voltage is 100V), the system is collapsed. And also distinguishes from VT fail.
3) d(UKK)/dt < blocking setting of low voltage load shedding voltage sudden-change;
Voltage sudden-change blocking criterion is used to avoid mal-operationof low voltage load
shedding, under conditions such as fast decrease of bus voltage when short-circuit fault happens of
the system or voltage abnormity caused by load feedback and so on.
5) Time > max (time setting of low voltage load shedding, 100 ms).
Low voltage load sheding operates when all of the conditions mentioned above are met and then
permanently trips and block reclosing. The low voltage load shedding is disabled automatically q
when VT failure.
Enable or disable three--phase reclosing with one shot function is controlled by reclose connector.
Startup of reclosing: it can be started through protection and inconsistence of circuit breaker
-30-
CSC-160 series numerical line protection equipment Manual
position.
Reclosing function can only be enabled after “charge” finished to avoid many times reclosing.
One charge counter is set, applying the mode of fast discharge and delay charge. When the
discharge condition is not met, the counter will begin to count with charge time lasting for 15s.
While the discharge condition is met, charge counter resets. After charge of the equipment is
finished, liquid crystal of panel displays “charged”.
Reclosing mode can be selected by control word. Available modes are “No synchronization
check”, “Line without-voltage bus with voltage check”, “Bus without voltage line with voltage
check”, “Line and bus without voltage check”, “Synchronization check” and “Adjacent line with
current check”.
When reclosing with synchronization check, voltage on both sides nneed to be larger than 0.7
times of rated value of corresponding voltage. Angle difference of two sides is within range of
“reclose synchronization angle”.
When reclosing with no-voltage check, “Line without voltage bus with voltage check”, “Bus
without voltage line with voltage check” and “Line and bus without voltage check” can be
combined for using with “or” relation. Threshold of no-voltage is 0.3 times of rated value while
threshold with voltage is 0.7 times of rated value. If both line and bus have voltage, switch to
synchronization check automatically.
When reclosing withsynchronization check or test no-voltage check, the equipment must connect
with line reference voltage Ux. The magnitude and phase of line reference voltage Ux is identified
by protection automatically, without setting by user.
When reclosing with adjacent line with current check: when the line terminalof parallel line is not
equipped with line reference voltage equipment while can not get Ux, the equipment can connect
with one phase current Ix of adjacent line. Adjacent line with current is used as distinguish
condition for reclosing.
The circuit breaker failure startup current element can be enabled or disabled by control word.
When current of any phase is larger than the setting of CBF startup current, the CBF startup
current element operates. Contacts of CBF startup current relay and protection operation are
connected in series to start circuit breaker failure protection. Or contact of CBF startup current
relay is used for busbar protection to discriminate dead zone between CT and breaker.
Only need to set K, R and Iset to perform various types of inverse time characterisitc curves,
including standard inverse time characterisitc, extreme inverse time characterisitc, and very
inverse time characterisitc and so on.
-31-
CSC-160 series numerical line protection equipment Manual
K
T
Id R
( ) 1
Iset
Where: Id: short-circuit current
Reclosing start time is provided, which can be set (longest 6min can be set) for the situation that
when fault tripping to the protected line, protection whole system reset reclosing fails caused by
long time of voltage recovery with small substation on the other side of the system and cannot
meet the voltage requirement of synchronization check and no-voltage check in a short time.
2) When differential current of two normal sides is calculated larger than 0.15In for 12s, alarm
to report “differential current for long time”. If the current of CT failure phase is smaller than
0.06In at the same time, it is considered as CT fail.
. . .
1) Summation of three phase voltages is not zero and U A U B U C 7V. It is used to
2) Voltages of all three phase are smaller than 8V and current of any phase >0.04In or circuit
breaker closed (detect TWJ). It is use to detect voltage failure of three phase.
When conditions above are met, distance protection will be blocked immediately. After
confirmation for 1s, alarm and report “VT fail” or “VT three phase voltage failure”; when voltage
recover to be normal, report “VT recovery to normal” after 10s confirmation and then enable
distance protection.
-32-
CSC-160 series numerical line protection equipment Manual
-33-
CSC-160 series numerical line protection equipment Manual
Opposite = 1
startup
Start Y17
InterBLK
On
1 H9 &
Local side Y1
with current = 1
H8 Y2
local side with
abrupt voltage
Start differential
protection
Channel normal
&
Opposite differential
connector enabled
Differential
Y4
connector &
enabled
Startup of
local side Y3
=1
Weak infeed
end startup
H2
Remote calling
startup
&
In area of phase A
differential & &
Protection
Phase A CT failure Y5 operation
Y8
=1 =1
Y 20
In area of phase B
differential & H4
0
H3
Phase B CT failure Y6
Phase-to-
phase fault Phase-to-phase
permanent 1
In area of phase C tripping
differential &
Phase C CT failure Y7
& Zero 0
1
=1 difference = 1
Y9 & time Zero order
& differential
H5
In area of zero Y 10 permanent
sequence Y 17 tripping
differential
Operation
Block differential block
enabled after CT failure & reclosing
H7
The failure phase &
Y 12
differential component = 1
after CT failure Y 11
&
Closing in differential
Y 14
area
Receive opposite
remote tripping Remote tripping blocked by
startup component &
Local-side
startup
1
In distance zone II of Y 15
local side
TeleTrip Start On
1
Active DI of remote
transmission Transmit signal to
command opposite
In the figure:
-34-
CSC-160 series numerical line protection equipment Manual
If setting is “block differential protection after CT failure”: after CT failure of some phase, block
all phase separate differential components.
If setting is “no block differential protection after CT failure”: after CT failure, the failure phase is
distinguished according to “setting of phase separate differential protection after CT failure” and
healthy phase is distinguished according to “setting of phase separate differential”.
Illustrate as follows:
1) When the “remote send signal by protection” enabled in control word, the protection perform
the remote sending signal and so on.
Process: Local-side protection send a signal (opposite side protection send signal for 10s after
receiving signal by remote sending signal logic), local-side protection stop signal after 200ms,
local-side protection receive opposite-side signal for 5s, local-side protetion send signal again for
10s ,and channel check finished. If channel failure, issue alarm.
3) When receiving opposite-side blocking signal, if local-side TWJ do not operate, sending signal
for 10s.
4) When receiving opposite-side blocking signal, if local-side TWJ operate, sending signal with
160ms time delay.
Remote
ChanChk Test key
“1 ” ≥ 1
Pilot H1
Periodically 1 &
ChanChk T4 ≥1
channel
T2 0 5"
Y1 10" 0
200 0 & &
H2
T5 Y3 &
Y2
T3 Y4
Send signal
3 0
Receive signal
≥ 1
160 0 T6 H3 &
Stop signal
Y5
CB OPEN
-35-
CSC-160 series numerical line protection equipment Manual
≥1 Stop
Revese OPTD &
H10 signal
Positive OPTD Y14
T13 &
0 40
Y15
T14 T15
Pilot
& & 8~2
Receive 5 0
≥1 0
0 ≥1 operation
Y16
signal
H11 H12
Y1
7
≥1
H13
Weak infeed
&
T16 & tripping on
Weak infeed On
Y18 & 0~3
T17 150 0 0 0
Y20 8 0
Y19 1
T19 10 0
Figure 17 Logic diagram of pilot distance, pilot zero sequence direction element for
blocking mode
3.16.2.3 Permissive mode logic
Receive signal
&
CB OPEN &
Y30 160 0 Y31 Send signal
T30
Relay startup &
BB/CBF OPTD
Y33
Other protection 160 0
trip &
T31 T32
Line no 120 0 Y32
current
≥1
Reverse OPTD
& H30 Send signal
Positive OPTD
T34 Y35 &
0 40 Y36
Ph-Ph Fault
& T35
Unblock On & Y38 ≥1 5~2
T36 Y37 0 0
DI_ unblock H31
120 0 &
Receive Y39 ≥1
signal
Pilot trip
≥1
H32 H33
Weak infeed
&
Trip On
Y40 Weak T40
150 0 0~3 T38 & infeed Trip
T37 & 0 0 Y42 5 0
Low U OPTD T39 1
Y41
120 0
& ≥1
& H34
Y44
Y43
Figure 18 Logic diagram of pilot distance, pilot zero sequence direction for permissive mode
-36-
CSC-160 series numerical line protection equipment Manual
VT failure &
Y20
Distance connector
enabled
&
Ph-E distance zone I T1_PE
Y1
=1
Distance oepration
H1 (block reclosing when
Ph-Ph distance zone I & T1_PP manual closing and
Y2 autoreclosing)
=1
H6
&
Ph-E distance zone II & T2_PE 0
Y27
=1 Y3
H
& 3 =1
Ph-Ph distance zone II T2_PP
Y28 & Z_PP
Y4 H2
Trip N_A/ 1
& R On
Ph-E distance zone III Y21 T3_PE
0
&
Ph-Ph distance zone III Y22 T3_PP
=1
H12 1
3rUp Trip N_A/R On
=1
H4
& X Speed On
Reactance closing
Y5
A/R FastSpd Z2 On
Reclosing Distance operation
& (block reclosing)
Y6 =1
Distance zone I and II
without power swing H7
blocking A/R SPD Z3 On =1
& H5
Whitin 150ms after =1 Y7
startup
H9
Asymmetric start 1.5s Z3 SPD On
component &
=1 &
H8 Y16 Power 1.5s
Y8
DR/dt start component swing open
&
Asymmetric fault Y26
successive operation
enabled
Asymmetric fault &
successive operation Asymmetric
IA, IB and IC have Y12 fault operation
current first and then
disappear
No acceleration signal of
adjacent line received first
&
and then received
Within 300ms after Y13
startup &
Y27
Parallel line successive
operation Parallel line
Parallel line successive =1 successive
operation connector operation
H13
No acceleration signal of
adjacent line received
&
Phase current increase
more than 4 times Y14
Another line of the same
side has current
Load end of parallel line
enabled
Illustration as follows:
1) Enable or disable distance zone I, II and III is controlled by distance protection connector.
2) If “Z_PP Trip N_A/R On” is selected, phase to phase distance protection operate to block
reclosing.
If “3rUp Trip N_A/R On” is selected, zone III operate to block reclosing.
3) Acceleration after reclosing: can enable “A/R FastSpd Z2 On” without power swing blocking
and “X Speed On”. If “X Speed On” is enabled, measured reactance difference of original fault
phase after closing is within 12 percent from that before tripping and the fault impedance is within
distance zone II, protection acceleration operation.
4) Consider that maybe the power swing occur: can enable the function of “1.5s Z3 SPD On”.
5) Manual closing in distance zone III to prevent unwanted acceleration trip resulted from
impedance into distance zone III caused by inrush current when energizing non-loadedtransformer.
If of the value of secondary harmonic wave>20 percent of fundamental wave, distance zone III
-37-
CSC-160 series numerical line protection equipment Manual
6) If the impedance lies in distance zone I and II when manual closing, tripping with acceleration.
8) When distance protection connector is enabled, if VT failure, it will block distance protection
and enable two stages overcurrent protection after VT failure automatically. After VT recovery,
enable distance protection automatically.
Zero sequence 1
current
3I0_stage 3
Illustration as follows:
1) Enable or disable earth fault protection stage I, II, III and IV is controlled by zero sequence
connector.
2) When running normally and VT is normal, operation logic of earth fault protection please
see the above diagram.
3) If “3rUp Trip N_A/R On” is selected, stage III and IV trip and block reclosing.
4) When autoreclosing and manual closing onto fault, if earth fault stage I enabled with 100ms
time delay, it will trip with 100ms time delay.
If earth fault stage II, III and IV enabled with acceleration, they will accelerate to trip with 100ms
time delay.
When autoreclosing and manual closing onto fault, the earth fault protection will trip and block
reclosing.
5) When all stages of earth fault protection without direction, operation of earth fault
protection is without influence of VT failure.
6) When VT failure, earth fault protection with direction can select “VT_Fail 3I0_X DIR Off”
or “VT_Fail DIR 3I0_X Off” (enabled or disabled by control word, stage X presents stage I or II,
III and IV, following the same).
If “VT_Fail DIR 3I0_X Off” is selected, when VT fail, earth fault stage X switch into zero
sequence current and time delay of earth fault stage I operation is max(time setting of earth fault
-38-
CSC-160 series numerical line protection equipment Manual
stage I, 200ms). Delay time setting of earth fault stage II, III and IV is the corresponding time
setting., earth fault stage X trip permanently and block reclosing.
Illustrations as follows:
2) If “stage III and above permanent tripping” is selected, overcurrent stage III trips
permanently and block reclosing.
4) When overcurrent protection stage I, II and III without direction and voltage blocking,
operation without influence of VT failure.
When VT fail, overcurrent protection with direction and voltage blocking can switch into “disable
direction and voltage” or “disable stage with direction and voltage blocking” (enabled or disabled
by control word). If the overcurrent stage with direction selects “disable direction and voltage”,
the protection trip permanently and block reclosing.
5) Enable or disable overload protection and overload tripping is controlled by control word.
-39-
CSC-160 series numerical line protection equipment Manual
&
CB open
Y1
Low frequency current blocking enabled
& =1
max( IA,IB,IC)>0.1In Y2 H1
Low frequency
operation (block
reclosing)
T_LowFreq
VT failure
&
Low frequency load shedding
connector
Frequency<setting value of frequency
2) Voltage setting of low voltage decrease load is voltage of the line. Low voltage decrease
load sliding voltage block dU/dt is transformation ratio of line voltage.
CB open =1
Low voltage
VT failure operation (block
reclosing)
& T_LowVolt
min(UAB, UBC, UCA)>
30 V
d((|UAB|+|UBC|)/2)/dt < Y1
setting value of voltage change rate dU/dt
3) When six control words above are all set as 0, equipment defaults as no-check mode.
-40-
CSC-160 series numerical line protection equipment Manual
4) “A/R L_NV B_V On”, “A/R B_NV L_V On” and “A/R L_NV B_NV On” can be
combined to use. When they combines, their relation is logic or. For example, both “A/R B_NV
L_V On” and “A/R L_NV B_V On” are set as 1, it will reclose when “A/R B_NV L_V On” or
“A/R L_NV B_NV On” meets conditions. When both line and bus have voltage, it will switch into
synchronization check mode automatically.
5) When synchronization check or no-voltage check for reclosing, the equipment must be
connected with line reference Ux. The magnitude and phase of line voltage Ux is recognized by
protection automatically, without setting of user. If the the difference of magnitude and phase of
line reference Ux with Ux recognized by protection is large when running, the equipment will
report “Line UX Err”.
Reclosing enabled
DI for blocking
reclosing
Permanent tripping DI 1
Permanent tripping DI 2
Test DO H2
&
CB open >2s Y1
&
Y5
Protection startup
&
&
Y2
Protection =1
& Y6
operation
1 Y4
H
With TWJ &
Y3
Line without
current
A/R NO_CHK On
Asynchronization
-41-
CSC-160 series numerical line protection equipment Manual
-42-
CSC-160 series numerical line protection equipment Manual
2) Check whether the qualification certificate, auxiliary documents, accessories, spare parts of
equipment and so on are consistent with requirement of order and whether they are consistent and
well equipped with types, names and quantities regulated by packing list.
-43-
CSC-160 series numerical line protection equipment Manual
5 Setting
Setting list of CSC-160 series consists of equipment parameter and protection setting. Definitions
of equipment parameters of CSC-160 series are same. Protection setting contents of different type
equipments are different.
Setting spcification of CSC-160 series gathers as follow. Please refer to it according to specific
protection configuration and setting list selectively.
And please also refer to above illustration of function and logic diagram.
1) Equipment parameter
a) When “VT Fail Detect Off” is enabled, do not detect VT failure, in runing state it is must be
set as “0” (VT Fail Detect On).
b) For single tripping coil Z1 series, enable the control circuit 1 borken self-detection;
For double tripping coil Z2 series, both of the control circuit 1 broken self-detectionand control
circuit 2 broken self-detection can be enabled.
c) CT ratio: value of current transformer primary side/secondary side in primary power system
is mainly used to calculate distance from fault location to protection installation (type of distance
protection is available). Setting value is 1000 divided by practical CT ratio, for example, if CT
ratio is 800/5, then setting value is 800/(5*1000).
d) VT ratio: the value of voltage transformer primary side/secondary side in primary power
system is mainly used to calculate distance from fault location to protection installation (type of
distance protection is available). Setting value is 1000 divided by practical ratio, for example, if
VT ratio is 110/0.1, then setting value is 1100/1000=1.1.
The setting should guarantee the sensitivity of fault phase current under smallest running mode.
Considering that the equipment is equipped with zero sequence or overcurrent startup components,
usually, it is suggested to set as 0.2In.
a) When running normally, “Master” bit selected by differential protection should be 1 for one
end and 0 for other end, i.e. on one end is “Master” and while the other end is “Slave”.
b) When protection applies dedicated optical fiber channel, settings should be set as
“Inner_Clock” and communication speed is suggested to select 2Mbps.
When protection multiplexes digital communication system, setting please refers to relevant
illustration in section 3.3.7.1 current differential clock synchronization.
-44-
CSC-160 series numerical line protection equipment Manual
c) “Channel circle” function of differential protection is test function. When running normally,
it must be disabled, i.e. when running normally, corresponding control bits should be set as 0.
d) Setting of phase separate differential protection: it is set larger than 2.5 times of capacitive
current and checked according to the standard that the sensitivity of internal fault occurs in
smallest running mode. Equipment on all sides of line should be set to comply with the same
primary current converting to secondary.
For short line, because the capacitive current of the line is small and sensitivity of differential
protection is high, the setting of phase separate differential protection can be increased properly.
e) Setting of zero sequence differential protection: this setting is set according to avoid the
largest unbalance current when the external fault happens, and guarantee the sensitivity of internal
fault with large arc resistance grounding. Equipment on all sides of line should be set to comply
with the same primary current converting to secondary.
f) Time setting of zero sequence differential protection: it should be longer than 100ms.
g) Setting of phase separate differential protection after CT failure: this setting is set according
to avoid largest load current when normally running. Equipment on all sides of line should be set
to complyi with the same primary current converting to secondary.
Note: if “BLK C/D CT_Fail Off” is selected, if the external fault occur at failure phase
after CT fail, differential protection will operate according to “I_PH C/D CT Fail”
setting. Therefore, it will lose choice! So please set the setting item according to the
demand of system.
CT ratio compensation coefficient is set as largest value of primary rated current divided by
primary rated current of CT on the side.
For example: CT ratio on side M is 1200/1. CT ratio on side N is 800/5 and CT ratio on side T is
600/5. If the compensation coefficient on side M is set to 1, then that on side N is set to
800/1200=0.6667 and that on side T is set to 600/1200=0.5.
a) In control word, weak infeed endr function and weak infeed end to trip function only can be
used for weak infeed end, not power side.
b) Channel check time mode is XX.XX,if everyday check time is 16:30,so the setting 16.30 can
be set, different check time should be set for different equipment of two side.
c) Pilot distance protection can select “Z2_PP StopSig On” or “Z3_PP StopSig On” for stopping
signal threshold. When the phase to phase or phase to earth fault occur,comparing phase to phase
or phase to earth impendance with stopping signal threshold to discriminate the stopping signal
conditions.
d) Pilot zero sequence protection can select “3I0_2 StopSig On” or“3I0_3 StopSig On” or “3I0_4
StopSig On” for stopping signal threshold.
-45-
CSC-160 series numerical line protection equipment Manual
5) Distance protection
It is used for phase to phase distance zone I, II and III. When phase to phase fault happens, arc
resistance is not too large. So “R_PP” should no be too large.
It is used for phase to earth distance zone I, II and III. It should be considered comprehensively
according to avoid load impedance and the ability to clear phase to earth fault through large arc
resistance.
c) Please set the reactance setting according to the characteristic of impedance polygon.
In the formulas, R1 and X1 present positive sequence resistance and positive sequence reactance of
the line while R0 and X0 present zero sequence resistance and reactance of the line.
Setting of spower swing current is set according to avoid largest load with certain tolerance. It is
used to discriminate whether the power swing happens.
a) If the earth fault protection stage I, II, III and IV is enabled without direction, there is no
influence of VT fail.
b) If “VT_Fail 3I0_1 DIR Off” is selected, when VT fail, earth fault stage I with direction will
switch inot zero sequence overcurrent. Earth fault stage I will trip with time delay of max (time
setting of earth fault stage I, 200ms). Trip and block reclosing.
If “VT_Fail DIR 3I0_1 Off” is selected, when VT fail, earth fault stage I with direction function
-46-
CSC-160 series numerical line protection equipment Manual
disabled.
c) If “VT_Fail 3I0_234 DIR Off” is selected, when VT fail, earth fault stage II, III and IV with
direction will switch into zero sequence overcurrent. Earth fault stage II, III and IV will trip
according to corresponding time setting. Trip and block reclosing.
If “VT_Fail DIR 3I0_234 Off” is selected, when VT fail, earth fault stage II, III and IV with
direction function disabled.
d) Considering the demand of unbalance current produced when avoiding breaker closing: no
matter earth fault stage II, III and IV enabled with acceleration, after manual closing, they will
delay at least a fixed 100ms; when “SOTF 3I0_1 DE On” is enabled, earth fault stage I trip with
100ms delay time after manual closing.
7) Overcurrent protection
a) When overcurrent protection stage I, II and III without direction and voltage blocking,
operation will not be influenced by VT failure.
When VT fail, overcurrent protection stage with direction and voltage blocking can switch to
“VT_Fail DIR U_BLK Off” or “VT_Fail DIR U_BLK OC Off” (enabled or disabled by control
word). If overcurrent direction stage selects “VT_Fail DIR U_BLK Off”, after overcurrent
protection triping, it will block reclosing.
b) If the voltage blocking function of overcurrent for some stage is enabled, when any phase to
phase voltage is lower than the setting value, it will enable the stage of overcurrent protection.
8) Overload protection
a) Overload is enabled or disabled by control word. Current setting is set according to avoid
largest load with certain tolerance.
b) If the function of overload tripping is not enabled, alarm with time delay set in setting.
c) If the function of overload tripping is enabled, overload alarm time will be fixed as 30s. It
will trip according to overload time setting.
9) Reclosing function
a) A/R SYN Angle: angle difference between voltage of bus and line for synchronization
check mode.
b) “A/R L_NV B_V On”, “A/R B_NV L_V On” and “A/R L_NV B_NV On” can be
combined to use. When they combines, their relation is logic or.
NoFault Fast Reset On: when load changes frequently (such as electrified railway, large scale
smelting electric cooler and so on), the function can be enabled. Non-fault fast setting reset
function is only applicable for the condition of distance protection without power swing blocking.
-47-
CSC-160 series numerical line protection equipment Manual
Security settings listed in table means the recommended setting value of corresponding setting
when some function is not in use.
Note:
2) “Reactance value per km of line” in protection setting is primary value and other
settings are all set as secondary value.
Table 8
No. Name Description Range Unit
1 System ContWd System control word
2 CT Ratio CT ratio 0.01~10.0 None
System control word: setting by 16 bits binary, B.15 is highest bit,B.0 is lowest bit,every 4 bits
composing 1 hex, bit illustration see table 9.
Table 9
No. Name Description Write value
VT fail discrimination function 0,1
1 VT Fail Detect On
enabled (system mode)
VT fail discrimination function 0,1
2 VT Fail Detect Off
disabled(Test mode)
Control circuit 1 broken 0,1
3 ContCirc 2 Fail Detect On
discrimination function enabled
Control circuit 1 broken 0,1
4 ContCirc 2 Fail Detect Off
discriminationfunction disabled
Control circuit 2 broken 0,1
5 ContCirc 1 Fail Detect On
discrimination function enabled
Control circuit 2 broken 0,1
6 ContCirc 1 Fail Detect Off
discrimination function disabled
7 CT Rated 1A CT rated current is 1A 0,1
-48-
CSC-160 series numerical line protection equipment Manual
-49-
CSC-160 series numerical line protection equipment Manual
5.2.2.1 CSC-161A
CSC-161A functions including: distance protection, parallel line successive operation, earth fault
protection, overcurrent protection after VT fail, overload protection, three-phase reclosing.
CSC-161A setting list see table 10.
Table 10
4 R1/X1 0.00~10.00 No
6 R_PP , 0.05~125(In=1A) Ω
0.01~25(In=5A) 0
7 X1_PP , 0.05~125(In=1A) Ω
0.01~25(In=5A) 0
8 X2_PP , 0.05~125(In=1A) Ω
0.01~25(In=5A) 0
9 X3_PP , 0.05~125(In=1A) Ω
0.01~25(In=5A) 0
13 R_PE , 0.05~125(In=1A) Ω
0.01~25(In=5A) 0
14 X1_PE , 0.05~125(In=1A) Ω
0.01~25(In=5A) 0
15 X2_PE , 0.05~125(In=1A) Ω
0.01~25(In=5A) 0
16 X3_PE , 0.05~125(In=1A) Ω
0.01~25(In=5A) 0
20 Kx 0.00~7.99 No
21 Kr 0.00~7.99 No
-50-
CSC-160 series numerical line protection equipment Manual
CSC-161A control word see table 11. Write “1” means function enabled,write “0” means function
disenabled.
Table 11
5 X Speed On 0,1 0
-51-
CSC-160 series numerical line protection equipment Manual
20 Overload On 0,1 0
5.2.2.2 CSC-161B
CSC-161B functions including: earth fault protection, overcurrent protection, overload protection,
three-phase reclosing. CSC-161B setting list see table 12.
Table 12
-52-
CSC-160 series numerical line protection equipment Manual
CSC-161B control word see table 13. Write “1” means function enabled, write “0” means function
disenabled.
Table 13
-53-
CSC-160 series numerical line protection equipment Manual
21 Overload On 0,1 0
5.2.2.3 CSC-162A
CSC-162A functions including: pilot distance protection, pilot zero sequence direction protection,
distance protection, earth fault protection, over current after VT fail, overload protection,
three-phase reclosing. CSC-161B setting list see table 14.
Table 14
-54-
CSC-160 series numerical line protection equipment Manual
CSC-162A control word see table 15. Write “1” means function enabled, write “0” means function
disenabled.
Table 15
-55-
CSC-160 series numerical line protection equipment Manual
10 CHAN_CHK On 0,1 0
16 X Speed On 0,1 0
31 Overload On 0,1 0
33 CBF On 0,1 0
-56-
CSC-160 series numerical line protection equipment Manual
CSC-163A and CSC-163T functions including: current differential protection, distance protection,
earth fault protection, over current after VT fail, overload protection, three-phase reclosing; in
addition, CSC-163A include circuit breaker failure protection. CSC-163A and CSC-163T setting
list see table 16. CSC-163T is double channel.
Table 16
9 R1/X1 0.00~10.00 No /
-57-
CSC-160 series numerical line protection equipment Manual
25 Kx 0.00~7.99 No /
26 Kr 0.00~7.99 No /
CSC-163A and CSC-163T control word see table 17. Write “1” means function enabled, write “0”
means function disenabled.
Table 17
-58-
CSC-160 series numerical line protection equipment Manual
-59-
CSC-160 series numerical line protection equipment Manual
Note 1: the settings of circuit breaker failure only applied for CSC-163A.
5.2.2.5 CSC-163B
CSC-163B functions including: current differential protection, earth fault protection, over current
protection, overload protection, three-phase reclosing. CSC-163B setting list see table 18.
Table 18
-60-
CSC-160 series numerical line protection equipment Manual
CSC-163B control word see table 19. Write “1” means function enabled, write “0” means function
disabled.
Table 19
-61-
CSC-160 series numerical line protection equipment Manual
29 Overload On 0,1 0
5.2.2.6 CSC-166A
CSC-166A functions including: phase to phase distance protection, over current protection,
overload protection, low frequency load shedding protection, low voltage load shedding protection,
three-phase reclosing .CSC-166A setting list see table 20.
Table 20
4 R1/X1 0.00~10.00 No
6 R_PP ,0.05~125(In=1A)
0.01~25(In=5A) Ω 0
7 X1_PP ,0.05~125(In=1A)
0.01~25(In=5A) Ω 0
8 X2_PP ,0.05~125(In=1A)
0.01~25(In=5A) Ω 0
9 X3_PP ,0.05~125(In=1A)
0.01~25(In=5A) Ω 0
-62-
CSC-160 series numerical line protection equipment Manual
CSC-166A control word see table 21. Write “1” means function enabled, write “0” means function
disenabled.
Table 21
5 X Speed On 0,1 0
-63-
CSC-160 series numerical line protection equipment Manual
19 Overload On 0,1 0
21 2_PH CT 0,1 0
CSC-167A and CSC-167T functions including: current differential protection, phase to phase
distance protection, over current protection, overload protection, low frequency load shedding
protection, low voltage load shedding protection, three-phase reclosing. CSC-167A and CSC-167T
setting list see table 22. CSC-167T is double channel mode.
Table 22
4 ,0.1 ~30(In=1A)
I_PH C/D VT Fail 0.5 ~150(In=5A) A 150
-64-
CSC-160 series numerical line protection equipment Manual
7 R1/X1 0.00~10.00 No /
9 R_PP 0.01~25(In=5A),0.05~125(In=1A) Ω 0
10 X1_PP 0.01~25(In=5A),0.05~125(In=1A) Ω 0
11 X2_PP 0.01~25(In=5A),0.05~125(In=1A) Ω 0
12 X3_PP 0.01~25(In=5A),0.05~125(In=1A) Ω 0
CSC-167A and CSC-167T control word see table 23. Write “1” means function enabled, write “0”
means function disenabled.
Table 23
-65-
CSC-160 series numerical line protection equipment Manual
17 X Speed On 0,1 0
31 Overload On 0,1 0
-66-
CSC-160 series numerical line protection equipment Manual
5.2.2.8 CSC-167B
CSC-167B functions including: current differential protection, over current protection, overload
protection, low frequency load shedding protection, low voltage load shedding protection,
three-phase reclosing .CSC-167B setting list see table 24.
Table 24
-67-
CSC-160 series numerical line protection equipment Manual
CSC-167B control word see table 25. Write “1” means function enabled, write “0” means function
disenabled.
Table 25
18 Overload On 0,1 0
20 2_PH CT 0,1 0
-68-
CSC-160 series numerical line protection equipment Manual
When current differential protection, distance protection, earth fault protection, overcurrent
protection, parallel line successive operation, low frequency load shedding, low voltage load
shedding or reclosing is not in use, the corresponding connector can be disabled.
Note: CSC-160 series provide two modes of connector, i.e. serial connection of soft and hard
connector mode and hard connector mode (connector on screen), factory default configuration is
serial connection of soft and hard connector mode. If only soft connector needed, then enable the
corresponding hard connector on screen (connect +24V power supply). If only hard connector
needed, enable all corresponding connector or change factory default configuration by project
designer of our company.
Serial connection of soft and hard connector mode can enable or disable the soft connector via
monitoring background system.
Applying serial connection of soft and hard connector mode, the soft connector can be enabled or
disabled in menu OpConnt-OpSoftConnt.
In menu OpConnt-ViewConnt, the engineer can view the enabling situation of connector. The
first list is name of connector. The second is the status of soft connector and the third is status of
whole connector.
When overload protection and fault startup component are not in use, the engineer can set the
control bit which is used to enable or disable the function.
When phase separate differential and zero sequence differential protection is not in use, the
engineer can set the current as 30 In and time as 20s.
When some stage of earth fault or overcurrent protection is not in use, the engineer can set the
current as 30 In and time as 20s.
When some stage of distance protection is not in use, the engineer can set reactance to 0 or the
same with other zones and time to 20s.
In main menu “Setting”, the settings can be set: bay name, time synchronization mode,
-69-
CSC-160 series numerical line protection equipment Manual
communication address, SOE reset selection, selection of CSC-2000 protocol version, print setting,
password modification, mode of 103 function and so on. See table 26.
Table 26 Menu “equipment setting”
-70-
CSC-160 series numerical line protection equipment Manual
1) Operation specification: highly bright option is present setting, selecting by keys up and
down and confirming by key SET.
“√” presents selecting the setting, while “X” presents not selecting the setting.
-71-
CSC-160 series numerical line protection equipment Manual
6 Hardware
1 2 3 4 5 6 7
DO1
CPU
MASTER
AI DI
7-a 7-b
Power
Operation
DO2
3TE 6TE 10TE 4TE 5TE 8TE 4TE 20TE 4TE 4TE 4TE 7TE 5TE 2TE
Figure 26
Module position of CSC-16XXQZ2 equipment is same with the figure, but the difference is that,
operation module is dual tripping coil operation circuit. CSC-160 does not have No. 6-b socket
components.
Rear terminals of various modules please see appendix figures. Connection illustration is as
follows:
1) AI module
Figure of AI module .
X3端子定义
X3 AI Module
b a
1 IA' IA
2 IB' IB
3 IC' IC
4 IN' IN
5
6 空
Null
7
8 IX' IX
9 UX' UX
10 UC UB
11 UN UA
12 GND
Figure 27
-72-
CSC-160 series numerical line protection equipment Manual
'
I X and I X are current of adjacent line used for reclosing of adjacentline with current check
mode and parallel line successive operation functionload end mode. I X is polarity terminal.
U A , U B and U C are inputs of three-phase voltage.
'
U X and U X are line reference voltage used for reclosing with non-voltage check and
synchronization check components. They can be connected to any phase and phase to phase
voltage. The protection can distinguish non-voltage and synchronization condition automatically.
U X is polarity terminal.
Terminal X3-b12 and X3-a12 are shield places of equipment. They should connect to earth
reliably.
3) Communication module
X5 (Management socket
The equipment can also provide two 485 and two
component)
Ethernet ports. Figure of communication module
Not Used
1
Print Transmit 2 please see figure 28. The module provides one set
Print Receive 3 of GPS time synchronization terminal, 485
Print FND 4 network terminal (one set or two), LonWorks
485-2B
485-2A network terminal (one set or two) and two sets of
485-1B 以 Ethernet terminal (electric Ethernet or optic
Ethernet
485-1A
GPS
太 Ethernet).
GPSGND 网
User can config network terminal according to
LON-2A
LON-2B external communication requirement of
LONGND equipment, config one set or two some network
LON-1A terminals.
LON-1B
Not Used
LONGND terminal is shield place of LON
network. They should connect to earth reliably.
Figure 28
-73-
CSC-160 series numerical line protection equipment Manual
DI module
Definition of DI terminal please refers to appendix terminal figure of various types. In figures:
X6-c2 is positive terminal of power supply for DI and X6-c28 is negative terminal of power
supply for DI, which should connect with the +24V and -24V of power supply output.
Terminal X6-a4, X6-a6, X6-a8, X6-a10, X6-a12, X6-a14 and X6-a16 are terminals of protection
connector. Specific definitions please refer to terminal figure of corresponding types. When
protection running and the corresponding protection function is needed, please connect with
positive power supply.
Terminal X6-a18 is used to switch bus I voltage; terminal X6-a20 is used to switch bus II voltage;
they are used for display of panel LED bus I and bus II. If voltage switching is performed by
voltage switch module of the equipment, the two terminals do not need to be connected, but
connecting those internal chassis.
Terminal X6-a22 is used to block remote operation. When connecting with +24V, it is only
permitted to control locally.
Terminal X6-a24 is connector for maintainence. When connect with +24V, the protection is in test
status. The protection does not send message to monitoring background when the protection
testing. This connector must be disabled when running.
Terminal X6-c20 is “DI_TELE_TRIP” terminal. Connect with TJR, or primary difference, fault
operation contact on breaker control box to the terminal.
Terminal X6-c22 is acceleration signal of adjacent line input terminal with distance function. For
others, it is standby.
Terminal X6-c30 and X6-a30 is alarm I (non-latch). X6-c32 and X6-a32 is alarm I (Latch). When
alarm I, equipment will drive the two sets of contacts and block protection operation power
supply.
The module provides 16 sets of contact for output such as acceleration adjacent line, equipment
alarm, overload alarm and so on. See figure 31. Specific definitions please refer to rear terminal
figures of each equipment.
Terminal X7-ca14 and X7-ca16: for equipment CSC-163(167), they are two sets of alarm output
of optic fiber channel A (manual tripping), while for other equipment, they are manual closing
contact.
Terminal X7-ca18 and X7-ca20: for equipment CSC-163(167), they are two sets of alarm output
of optic fiber channel B (manual tripping) while for others equipment, they are manual closing
contact.
-74-
CSC-160 series numerical line protection equipment Manual
1J-1
2J-1 3J-1
X7-c2 X7-a2 X7-c6 X7-a6 X7-c10 X7-a10
X7-c4 X7-c8 X7-a8 X7-c12 X7-a12
X7-a4
1J-2 2J-2 3J-2
4J-1 4J-1
X7-c14 X7-a14 X7-c14 X7-a14 Open or close, different
Or module for different type
X7-c16 X7-a16 X7-c16 X7-a16
4J-2 4J-2
5J-1 5J-1
X7-c18 x7-a18 X7-c18 X7-a18
Open or close, different
Or
X7-c20 X7-a20 X7-c20 module for different type
X7-a20
5J-2 5J-2
Latch 6J-1 7J-1 8J-1
X7-c22 X7-a22 X7-c26 X7-a26 X7-c30 X7-a30
Figure 29
6) DO module 2
The output provided by the module please see figure 32. It provides protection output, closing,
central signal, and remote signal and so on. Specific definitions please refer to rear terminal figure
of each equipment.
Startup failure
exit(note) X8 - a14
X8 - c 14 Commom
BXJ2E Remote
CKJ1B LJC terminal of signal
Common remote signal Protection output
Central signal X8 - a18
terminal of signal
BXJ1B X8 - a16
central signal Protection output X8 - a20 Closing output
X8 - c 18 CXJ2E
X8 - c 16 signal signal
X8 - c 20 Closing output LJD
CXJ1F signal X8 - c 22 X8 - a22 Contact of
CBF current
ZJB Standby YTJC
X8 - c 28 X8 - a28 X8 - c 24 X8 - a24 Protection tripping 3
contact
ZJC FJC
X8 - c 30 X8 - a30Standby contact X8 - c 26 X8 - a26 Protection tripping 4
Figure 30
For Z1 signal tripping coil series, the second set of output is standby.
Terminal X8-c4 is protection tripping 1. Terminal X8-c6 is protection closing and terminal X8-c10
is protection tripping 2.
The three terminals mentioned above can monitor connection of protection output circuit 1,
closing circuit and protection output, corresponding DI displayed by MMI respectively: connector
of protection output 1, closing output and protection output 2. If the circuit is connected,
corresponding DI will be active. It can monitor whether closing circuit is connected with tripping
position; while on closing position, it can monitor whether tripping circuit is connected.
If the operation circuit in CSC-160 series equipment is applied, “To Trip Connector 1”, “To Trip
Connector 2”, “To Close Connector” and operation module of the equipment are connected well
-75-
CSC-160 series numerical line protection equipment Manual
(X8-a4 and X9-c30 short-connected, X8-a6 and X9-c22 short-connected, CSC-16XXQZ2 series
X8-c12 and X9-a30 short-connected). If the external control box needs to be connected, please
connect according to the definition of terminal.
“Circuit Breaker Failure 1” contact and “Circuit Breaker Failure 2”: when current is larger than
setting of fault startup current, “fault current relay contact”(X8-c22 and X8-a22) closed. However,
when the current is larger than setting of fault startup current and the protection operation, please
drive “startup fault output”(X8-c14 and X8-a14). Note: corresponding contact without fault
startup component is standby.
Operation module can be used for with the condition that tripping and closing current is less than
8A. If tripping and closing current is larger than 8A, please indicate in order.
Principle figure of single tripping coil please see appendix figure 1. Figure 33 is terminal
definition of CSC-16XXQZ1 and figure 36 is the corresponding contact figure of terminals.
2
4
6
8
-76-
CSC-160 series numerical line protection equipment Manual
X9 - a 10 HYJC
Low pressure
X9 - a 12 block closing
TYJC Forbid operation
central signal X9 - a 14 for voltage
common abnormity
terminal HWJ2C TWJ2C X9 - a Control
16 circuit broken
or power supply
TXJB failure
X9 - a 18 Tripping
HWJ1C
X9 - a20 X9 - a 22 Closing position
STJC
X9 - a24 X9 - a 26 Manual tripping
HWJ2B
X9 - a28 X9 - a 30 Closing position
Figure 32
Terminal X9-c2 and X9-a2 are output contacts of position non-corresponding fault sound.
Low pressure block reclosing, low pressure block reclosing and forbidding operation for voltage
abnormity are controlled by negative power; terminal X9-c12 is common terminal of low pressure
blocking which is connected well with CONTROL BUS- in the equipment.
Terminal X9-c16 is the terminal of “to closing coil” (prevent tripping externally).
X9-c18 is the terminal of “to closing coil” (prevent tripping internally). When preventing tripping
internally is needed, please make X9-c18 and X9-c20 shortconnected and X9-c18 connect to
closing coil.
Principle figure of dual tripping coil please see appendix figure 2. Figure 35 is terminal definition
of CSC-16XXQZ2 and figure 36 is corresponding contact figure of terminals.
-77-
CSC-160 series numerical line protection equipment Manual
2
4
6
8
X9 - a 4 X9 - a 6 Closing position
TWJ1B
X9 - a 8 Tripping position
1HWJ2C
X9 - a 20 Closing position
X9 - a 22
2HWJC
Figure 34
Terminal X9-c2 and X9-a2 are output contacts of position non-corresponding fault sound.
Low pressure block reclosing, low pressure block closing and forbidding operation for voltage
abnormity are controlled by negative power; terminal X9-c12 is common terminal of low pressure
blocking which is connected well with CONTROL BUS- in the equipment.
-78-
CSC-160 series numerical line protection equipment Manual
Terminal X9-c16 is the termian of “to closing coil” (prevent tripping externally).
X9-c18 is the terminal of “to closing coil” (prevent tripping internally). When preventing tripping
internally is needed, please make X9-c18 and X9-c20 short-connected and connect X9-c18 to
closing coil.
Figure 35
-79-
CSC-160 series numerical line protection equipment Manual
7 Human-machine operation
CSC-163A
RESET
QUIT SET
SIO
+ -
SIFANG
Figure 36
1) On left side of liquid crystal is <Run>, <Operated>, <Reclose>, <Bus I>, <Bus II>, <CB
Open>, <CB Close> and <Alarm> LED.
QUIT: pressing the key, the equipment will cancel present operation and return to previous menu;
pressing the key when system displays circularly, lock the present display screen. Pressing it
again, cancel the function of lock present screen.
Up, down, left and right: selection keys, used to select menu function instruction from crystal
liquid display. Keys up and down can move cursor while keys left and right can change contents.
3) Four shortcut keys and two functional keys on the bottom of liquid crystal:
“Report” Key: It is used to print the latest event report, and to page down in MainMenu--Settings
menu.
“SetValue” Key: It is used to print all the setting values in current setting group, and to page up
in MainMenu--Settings menu.
-80-
CSC-160 series numerical line protection equipment Manual
"Version "Key: It is used to print the equipment information and operating status.
7.3.1 DI information
Table 28
-81-
CSC-160 series numerical line protection equipment Manual
-82-
CSC-160 series numerical line protection equipment Manual
7.3.3 DO information
Table 30
-83-
CSC-160 series numerical line protection equipment Manual
-84-
CSC-160 series numerical line protection equipment Manual
-85-
CSC-160 series numerical line protection equipment Manual
-86-
CSC-160 series numerical line protection equipment Manual
-87-
CSC-160 series numerical line protection equipment Manual
-88-
CSC-160 series numerical line protection equipment Manual
Table 33
-89-
CSC-160 series numerical line protection equipment Manual
-90-
CSC-163 series digital line protector instruction
8 Appendix figures
power supply 24V+ TWJ1C Bridge plug1 Bridge plug 2
R24+ 12 9 QC1-17 QC1 QC2
Tripping position
K24+ COM
Block reclosing trip TGB 1 1
KM+ KM- Operation power HYGB R24+ KM+
c32 c4 2 2
supply QC1-9 QC1-21 Low air pressure block
STGB 3 3
closing
4 4
KGA TYGB IN1 XFG
HWGB R1 After closing position logic 5 5
QC1-27 Low air pressure block QC1-5 BHFG
6 6
Low air pressure tripping IN2
7 7
WBJD After closing auto reset with block closing YGB WBJB QC1-7
time delay 8 8
QC1-15 3 4 QC1-29 Position not IN3 BT1/
WBJA
Matter record
D2 9 9
corresponding(start QC1-9 BHT
reclosing) 10 10
TWGB Signal reset FGB TXJC IN4
KGB RWBJ1 RWBJ2 11 11
8 1 Position not corresponding QC1-5 7 8 QC1-13 QC1-11
The first set trip 12 12
relay IN5
13 13
QC1-13 ST
14 14
IN6
15 15
HBJC QC1-15
16 16
7 8 IN7 HZ/
TBJUA
17 17
TBJC QC1-17 HZ
18 18
7 8 IN8
R4 19 19
HBJB TBJUC Prevent tripping and QC1-19
RHBJ 20 20
5 6 4 3 1 8 closing lactched IN9 ZJ/
HBJA
TBJUE HWJ1B 21 21
QC1-21 KM-
22 22
5 6 COM1 5 8 HWJ1 IN10
a4 a6 Closing position 23 23
HYJB QC1-23
blocking
Position indication
pressure
Prevent
blocking
Closing
Closing
tripping
latched
output
24 24
HZ 3 4 4 1 4 TBJUB 2 HQ-1 IN11
Air
c22 c18 25 25
QC1-25
26 26
5 TBJUD 7 IN12
27 27
TWJ1B QC1-27
28 28
HQ-2 External prevent tripping 5 8 TWJ1 IN13
c16 a8 Tripping position 29 29
TWJ1A
and closing output QC1-29
TWJ2A
30 30
HWJ1C
TWGA HWJ2+
12 9 HWJ2- Closing
LD RTWJ1 RTWJ2 a20 a22 position(cooperate
1 16 1 16 TW
c20 Tripping position relay with PT switch)
HWJ2A
HWJ1A
XC Box terminal plug
Digital output
HWGA Low air pressure block
HD RHWJ1 RHWJ2 Closing position relay
1 16 1 16 COM2 6 HYJC 5 HYJ closing WBJ22 1 WBJ2'
a10 a12 c2 a2
Central signal
failure or loop TY 10 9 COM2
D failure c10 a10
TBJA
BCT 12 TWJ2C 9 SY
TXJA
c28 a16
KM-12 11 HYJ
c12 a12
TYJB
tripping startup
Air pressure
BHT 2 1 3 4 4 1 TQ FG 14 13 TYJ
blocking
c30 c26 c14 a14
Tripping
Output
output
Prevent
signal
1 2 HQ-2
16 15 SY
c16 a16
TXJB
STJB 5 6 TXJ Tripping HQ-1
18 17 TXJ
a18 c18 a18
3 4 TBJB
Manual Tripping
5 6 TW 20 19 HWJ2+
STJA
tripping self-latched c20 a20
STGA HZ 22 21 HWJ2-
RSTJ c22 a22
ST 8 1
c24 WBJC Position not ST 24 23 STJ+
Manual tripping relay corresponding(start fault c24 a24
WBJ2 6 5 WBJ2'
c2 a2 sound)
TQ 26 25 STJ-
c26 a26
TXJD
BCT28 27 COM3
c28 a28
STJC
FGA STJ+ 6 5 STJ- Manual output(blocking BHT30 29 HWJ2
D11 RTXJ a24 a26 standby self-switching in) c30 a30
FG 3 4 External signal reset
c14
KM+32 31 TWJ2
2 2 c32 a32
BHFG
Protection reset signal DI HWJ2B
YGA COM3 5 8 HWJ2
R11 R12 a28 a30
ZHY
c6 Low air pressure block Position output(standby)
closing
HYJA
TYJA
TWJ2B
5 8 TWJ2
a32
RYJ1 RYJ2 Low air
8 1 8 1
pressure,
zero voltage Low air
or SF6 air pressure
TYGA HYGA pressure block
TY HY abnormity closing
c10 c8 c12 general
blocking
-91-
CSC-163 series digital line protector instruction
WBJA
reset block reclosing YGB
Event record
D2 11 11
QC1-15 3 4 QC1-29 QC1-11
Position not corresponding 12 12
KGB TWGB IN5
RWBJ1 RWBJ2 1TXJC (start reclosing) 13 13
8 1 Position not corresponding Signal reset QC1-13 ST
FGB 14 14
relay QC1-5 7 8 QC1-13 IN6
The first set of tripping 15 15
QC1-15
2TXJC 16 16
IN7 HZ/
HBJC 2TBJC 17 17
7 8 QC1-11 QC1-17 HZ
The second set of tripping 18 18
7 8 7 8 IN8
TBJUA
1TBJC 19 19
JJGB QC1-19
20 20
7 8 QC1-23 IN9 ZJ/
HBJB R4 TBJUC 21 21
Prevent tripping and The second power supply QC1-21 KM-
RTBJU 22 22
5 6 4 3 1 8 closing latched failure IN10
HBJA
TBJUE 1HWJ1B 23 23
QC1-23
24 24
5 6 5 8 HWJ1 IN11 BT2+
Position indication
HYJB a6 25 25
QC1-25 KM2+
Air pressure
TBJUB 2 2HWJB Closing position 26 26
HZ 3 4 4 1 4 HQ-1 IN12
blocking
blocking
Prevent
tripping
Closing
latched
Closing
output
c22 c18 27 27
COM1 5 8 QC1-27
TBJUD 7 a4 TWJ1B 28 28
5 IN13 BT2/
29 29
TWJ1A
TWJ2A
closing output XC Box terminal plug
1HWJ1C
LD TWGA HWJ2+ 9 12 HWJ2- Closing position WBJ21 2 WBJ2'
RTWJ1 RTWJ2 a20 a22 c2 a2
1 16 1 16 TW (Cooperate with VT
c20
Tripping position relay switch) KM- 3 4 COM1
c4 a4
1HWJ2A
1HWJ1A
ZHY 5 6 HWJ1
HYJC c6 a6
COM2 6 5 HYJ
a10 a12
Low air pressure block HY 7 8 TWJ1
c8 a8
HD 1HWGA TYJ closing or tripping
R1HWJ1 R1HWJ2 Closing position relay a14
1 16 1 16 TY 9 10 COM2
TWJ2C 12 c10 a10
9
YY- 11 12 HYJ
c12 a12
Central signal
1TGA
R2 9 1HWJ2C12 SY Power supply failure or FG 13 14 TYJ
a16 loop failure c14 a14
9 2HWJC 12 HQ-215 16 1SY
Block reclosing tripping DI c16 a16
HQ-117 18 1TXJ
1TBJA
c18 a18
1TXJA
BCT D 1TXJB
c28
5 6 TXJ Tripping TW 19 20 HWJ2+
TYJB a18 c20 a20
BHT 2 1 3 4 4 1 TQ 2TXJB HZ 21 22 HWJ2-
Tripping
Prevent
pressure
c30 c26 c22 a22
tripping
blocking
startup
output
Output
5 6
signal
Air
1 2 ST 23 24 KM2-
c24 a24
STJB WBJC Position not corresponding 1TQ 25 26 2TQ
1TBJB WBJ2' c26 a26
3 4 WBJ2 6 5 (start fault sound)
Manual c2 a2
5 6 1BCT
27 28 2BCT
STJA
tripping Trip self-latched c28 a28
STGA 1BHT
29 30 2BHT
RSTJ c30 a30
ST 8 1
c24 Manual tripping KM+31 32 KM2+
c32 a32
1TXJD KM2+
2TXJD
a32
2JJ1A
External signal reset KM2-
a24 Second set of operation
power supply
FGA JJGA
FG D 3 4 3 4 RTXJ 1 8 R2JJ
c14 Signal reset DI
2HWJA
Power supply
HYJA
TYJA
2TGA
2TBJA
2TXJA
abnormity
TYGA HYGA 2BCT D
general a28
TY HY
c10 c8 blocking TYJC
Air pressure
2BHT 2 1 6 5 4 1 2TQ
Tripping
a30 a26
blocking
Prevent
Output
tripping
output
startup
signal
1 2
STJC
2 2JJ1B 4 YY-5 2JJ1C 7 Voltage power supply 6 5 2TBJB
c12
3 6 switch 5 6 Manual Tripping self-
tripping latched
-92-
CSC-163 series digital line protector instruction
1) CSC-16XXQZ2 equipment is dual tripping coil. In the figure, X8-C8 is Control Bus2+. X8-C10 is protection tripping 2 and X8-C12 is to connector
of protection trip 2.
2) Terminal definition of operation module (X9) of CSC-16XXQZ2 equipment is different with that of CSC-16XXQZ1. See section 7 CSC-16XXQZ2
terminal figure in part 6.2, connection illustration.
Note: corresponding connector will not in effect unless low frequency load shedding and low voltage decrease load function equipped or they will be standby
connector. So
-93-
CSC-163 series digital line protector instruction
1
2 2 2 2 2 2 IA' 1 IA
4 4 4 4 4 3 IB' 2 IB
6 6 6 6 6 4 IC' 3 IC
8 8 8 8 8 485-2B IN' 4 IN
Ethernet
485-2A 5
485-1B
6
485-1A
GPS
7
GPSGND IX' 8 IX
LON-2A UX' 9 UX
LON-2B UC UB
LONGND UN UA
LON-1A
LON-1B
-94-
CSC-163 series digital line protector instruction
1
2 2 2 2 2 2 IA' 1 IA
4 4 4 4 4 3 IB' 2 IB
6 6 6 6 6 4 IC' 3 IC
8 8 8 8 8 485-2B IN' 4 IN
Ethernet
485-2A 5
485-1B
6
485-1A
GPS
7
GPSGND IX' 8 IX
LON-2A UX' 9 UX
LON-2B UC UB
LONGND UN UA
LON-1A
LON-1B
-95-
CSC-163 series digital line protector instruction
1
2 2 2 2 2 2 IA' 1 IA
4 4 4 4 4 3 IB' 2 IB
6 6 6 6 6 4 IC' 3 IC
8 8 8 8 8 485-2B IN' 4 IN
Ethernet
485-2A 5
485-1B
6
485-1A
GPS
7
GPSGND IX' 8 IX
LON-2A UX' 9 UX
LON-2B UC UB
LONGND UN UA
LON-1A
LON-1B
-96-
CSC-163 series digital line protector instruction
1
2 2 2 2 2 2 IA' 1 IA
4 4 4 4 4 3 IB' 2 IB
6 6 6 6 6 4 IC' 3 IC
8 8 8 8 8 485-2B IN' 4 IN
Ethernet
485-2A 5
485-1B
6
485-1A
GPS
7
GPSGND IX' 8 IX
LON-2A UX' 9 UX
LON-2B UC UB
LONGND UN UA
LON-1A
LON-1B
-97-
CSC-160 series numerical line protection equipment manual
Setting list of CSC-160 series equipment consist of equipment parameter and protection setting.
Equipment parameter of CSC-160 series equipment is same, seeing section 9.1. Protection setting
of CSC-160 series is not same for different type equipment.
In the main menu “ProtSet”, you can make corresponding setting such as comparing the time
mode, communication address, print and so on. See section 9.4.
Protection setting illustration of CSC-160 series sees section 5.1 and “protection function enabled
or disabled description” sees section5.4.
Protection Settings:
-98-
CSC-160 series numerical line protection equipment manual
-99-
CSC-160 series numerical line protection equipment manual
-100-
CSC-160 series numerical line protection equipment manual
-101-
CSC-160 series numerical line protection equipment manual
-102-
CSC-160 series numerical line protection equipment manual
-103-
CSC-160 series numerical line protection equipment manual
11 Order Note
1) Equipment type, name and order quantity;
4) Operation operation within the equipment can be used in the condition that tripping and
closing current is smaller than 8A. If tripping and closing current is larger than 8A, please indicate.
And please indicate single tripping coil or dual tripping coils;
For dedicated fiber circuit, please indicate circuit length(km) while for multiplexing digital
channel, please indicate applying 64kbps or 2Mbps interface;
8) Requirement of screen;
-104-
Address: No. 9, Street 4, Shangdi Information Industry Base, Haiding, Beijing
http://www.sf-auto.com E-mail:[email protected]