The PD8 power distribution module converts a single AC or DC power input into eight individually fused outputs. It has a 28VAC or 28VDC maximum input that can provide up to 12 amps total. Each of the eight outputs is individually fused at 3.5 amps and has overcurrent protection. The module has a power switch, input and output LED indicators, and mounts in an enclosure.

Uploaded by

Tv Chacon Chacon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
296 views1 page

Altronix - PD8

The PD8 power distribution module converts a single AC or DC power input into eight individually fused outputs. It has a 28VAC or 28VDC maximum input that can provide up to 12 amps total. Each of the eight outputs is individually fused at 3.5 amps and has overcurrent protection. The module has a power switch, input and output LED indicators, and mounts in an enclosure.

Uploaded by

Tv Chacon Chacon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PD8

Power Distribution Module


Overview:
Altronix PD8 power distribution module converts a single AC or DC input into eight (8) individually fused outputs.

Specifications:
Input:
• 28VAC or 28VDC max., up to 12A.
• Main fuse rated @ 5A/250V.
Outputs:
• Eight (8) individually fused outputs (fuses are rated at 3.5A; up to 5A fuses may be used).
• Surge suppression.
Fuse Ratings:
• Fuses are rated @ 3.5A/250V.
Visual Indicators:
• Power output LED indicator.
Additional Features:
• Power ON / OFF switch.
Board Dimensions (L x W x H, approximate):
5.25” x 3.25” x 1” (133.4mm x 82.6mm x 25.4mm).

Installation Instructions:
1. Mount PD8 in the desired location/enclosure.
2. Connect the desired power supply output to terminals marked [INPUT] (Fig. 1a).
Note: If using DC voltage, left terminal is NEG. (-) and right terminal is POS. (+) (Fig. 1a).
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
All terminals with common suffix P “1P, 2P...” are the same polarity.
4. Set power switch [SW1] to the OFF position.
5. Connect each device to the terminal pairs 1 to 8, marked [1P-1N] through [8P - 8N].
6. Output fuses rated at 3.5A/250V (Replacement fuses can be rated at up to 5.0A).
7. Set power switch [SW1] to the ON position.
Fig. 1

1 2 3 4 5 6 7 8 SW1

OFF
1 2 3 4 5 P6 7 8 SW1
Fig. 1a
OFF

ON

P D1

FUSED POWE R OUTPUTS LED


ON

D1 R1

FUSED POWER OUTPUTS R1 LED

N INPUT
N COMMON POWER INPUT
OUTP UTS N P S
COMMON POWER OUTPUTS N P S
Neg. (---) Pos. (+)

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty | Made in U.S.A.
IIPD8 - Rev. 111704 F02Q MEMBER