Characteristics
Product data sheet
ATV630U55N4
380...480V - IP21/UL type 1
variable speed drive ATV630 - 5.5kW/7.5HP -
1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
range of product Altivar Process ATV600
product or component Variable speed drive
type
product specific applica- Process and utilities
tion
device short name ATV630
variant Standard version
product destination Synchronous motors
Asynchronous motors
mounting mode Wall mount
EMC filter Integrated conforming to EN/IEC 61800-3 category
C3 with 150 m motor cable maxi
Integrated conforming to EN/IEC 61800-3 category
C2 with 50 m motor cable maxi
IP degree of protection IP21 conforming to IEC 60529
IP21 conforming to IEC 61800-5-1
degree of protection UL type 1 conforming to UL 508C
type of cooling Forced convection
supply frequency 50...60 Hz (- 5...5 %)
network number of 3 phases
phases
[Us] rated supply 380...480 V (- 15...10 %)
voltage
motor power kW 5.5 kW (normal duty)
4 kW (heavy duty)
motor power hp 5 hp (heavy duty)
7.5 hp (normal duty)
line current 10.4 A at 380 V (normal duty)
8 A at 380 V (heavy duty)
9.1 A at 480 V (normal duty)
7.2 A at 480 V (heavy duty)
prospective line Isc 50 kA
apparent power 6 kVA at 480 V (heavy duty)
7.6 kVA at 480 V (normal duty)
continuous output cur- 12.7 A at 4 kHz (normal duty)
rent 9.3 A at 4 kHz (heavy duty)
maximum transient cur- 14 A during 60 s (normal duty)
rent 14 A during 60 s (heavy duty)
asynchronous motor Variable torque standard
control profile Constant torque standard
Optimized torque mode
synchronous motor con- Permanent magnet motor
trol profile
output frequency 0.0001...0.5 kHz
nominal switching fre- 4 kHz
quency
switching frequency 2...12 kHz adjustable
4...12 kHz with derating factor
safety function STO (safe torque off) SIL 3
discrete input logic 16 preset speeds
2
communication port pro- Modbus serial
tocol Ethernet
Modbus TCP
option card Slot A : communication module for CANopen SUB-
D9
Slot A : communication module for CANopen daisy
chain RJ45
Slot A/slot B : digital and analog I/O extension mod-
ule
Slot A : communication module for Profibus DP V1
Slot A : communication module for Modbus TCP/
EtherNet/IP
Slot A : communication module for Ethernet IP/Mod-
bus TCP/MD-Link
Slot A : communication module for Profinet
Slot A/slot B : output relay extension module
Slot A : communication module for CANopen screw
terminals
Slot A : communication module for DeviceNet
Complementary
output voltage <= power supply voltage
permissible temporary current boost 1.5 x In for 60 s (heavy duty)
1.1 x In for 60 s (normal duty)
motor slip compensation Adjustable
Can be suppressed
Automatic whatever the load
Not available in permanent magnet motor law
acceleration and deceleration ramps S, U or customized
Linear adjustable separately from 0.01 to 9000 s
braking to standstill By DC injection
protection type Drive : line supply phase loss
Motor : thermal protection
Drive : thermal protection
Drive : motor phase break
Drive : overspeed
Drive : short-circuit protection
Drive : overload of output voltage
Motor : motor phase break
Drive : overvoltages on the DC bus
Drive : overheating
Drive : safe torque off
Drive : line supply undervoltage
Drive : overcurrent between output phases and earth
Motor : safe torque off
Drive : line supply overvoltage
Drive : break on the control circuit
frequency resolution Analog input : 0.012/50 Hz
Display unit : 0.1 Hz
electrical connection Control : removable screw terminals 0.5...1.5 mm² (AWG 20...AWG 16)
Motor : screw terminal 4...6 mm² (AWG 12...AWG 10)
Line side : screw terminal 2.5...6 mm² (AWG 14...AWG 10)
type of connector RJ45 (on the remote graphic terminal) for Modbus serial
RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
physical interface 2-wire RS 485 for Modbus serial
transmission frame RTU for Modbus serial
transmission rate 10/100 Mbit/s for Ethernet IP/Modbus TCP
4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
exchange mode Half duplex, full duplex, autonegotiation for Ethernet/Modbus TCP
data format 8 bits, configurable odd, even or no parity for Modbus serial
type of polarization No impedance for Modbus serial
number of addresses 1...247 for Modbus serial
method of access Slave for Modbus TCP
supply Internal supply for reference potentiometer (1 to 10 kOhm) : 10.5 V DC +/- 5 %
current <= 10 mA (overload and short-circuit protection)
External supply for digital inputs : 24 V DC (19...30 V) current <= 1.25 mA (over-
load and short-circuit protection)
Internal supply for digital inputs and STO : 24 V DC (21...27 V) current <= 200
mA (overload and short-circuit protection)
3
local signalling 4 LEDs dual colour for communication module status
1 LED red for presence of voltage
3 LEDs dual colour for embedded communication status
3 LEDs for local diagnostic
width 144 mm
height 350 mm
depth 203 mm
product weight 4.7 kg
analogue input number 3
analogue input type Software-configurable voltage AI1, AI2, AI3 : 0...10 V DC impedance 30 kOhm,
resolution 12 bits
Software-configurable current AI1, AI2, AI3 : 0...20 mA impedance 250 Ohm, res-
olution 12 bits
discrete input number 8
discrete input type Programmable as pulse input DI5, DI6 0...30 kHz : 24 V DC <= 30 V
Safe torque off STOA, STOB : 24 V DC <= 30 V impedance > 2.2 kOhm
Programmable DI1...DI6 : 24 V DC <= 30 V impedance 3.5 kOhm
input compatibility Discrete input STOA, STOB : level 1 PLC conforming to EN/IEC 61131-2
Discrete input DI1...DI6 : level 1 PLC conforming to EN/IEC 61131-2
Discrete input DI5, DI6 : level 1 PLC conforming to IEC 65A-68
discrete input logic STOA, STOB, positive logic (source) : , < 5 V (state 0), > 11 V (state 1)
DI5, DI6, positive logic (source) : , < 0.6 V (state 0), > 2.5 V (state 1)
DI1...DI6, negative logic (sink) : , > 16 V (state 0), < 10 V (state 1)
DI1...DI6, positive logic (source) : , < 5 V (state 0), > 11 V (state 1)
analogue output number 2
analogue output type Software-configurable current AO1, AO2 : 0...20 mA, resolution 10 bits
Software-configurable voltage AO1, AO2 : 0...10 V DC impedance 470 Ohm, res-
olution 10 bits
sampling duration Discrete input DI5, DI6 : 5 ms (+/- 1 ms)
Discrete input DI1...DI4 : 2 ms (+/- 0.5 ms)
Analog output AO1 : 10 ms (+/- 1 ms)
Analog input AI1, AI2, AI3 : 5 ms (+/- 0.1 ms)
accuracy Analog input AI1, AI2, AI3 : +/- 0.6 % for a temperature variation 60 °C
Analog output AO1, AO2 : +/- 1 % for a temperature variation 60 °C
linearity error Analog input AI1, AI2, AI3 : +/- 0.15 % of maximum value
Analog output AO1, AO2 : +/- 0.2 %
relay output number 3
relay output type Configurable relay logic R1 : fault relay NO/NC electrical durability 100000 cycles
Configurable relay logic R2 : sequence relay NO electrical durability 100000
cycles
Configurable relay logic R3 : sequence relay NO electrical durability 100000
cycles
refresh time Relay output R1, R2, R3 : 5 ms (+/- 0.5 ms)
minimum switching current Relay output R1, R2, R3 : 5 mA at 24 V DC
maximum switching current Relay output R1, R2, R3 on inductive load (cos phi = 0.4 and L/R = 7 ms) : 2 A at
30 V DC
Relay output R1, R2, R3 on resistive load (cos phi = 1) : 3 A at 250 V AC
Relay output R1, R2, R3 on inductive load (cos phi = 0.4 and L/R = 7 ms) : 2 A at
250 V AC
Relay output R1, R2, R3 on resistive load (cos phi = 1) : 3 A at 30 V DC
isolation Between power and control terminals
IP degree of protection IP21
Environment
insulation resistance > 1 mOhm at 500 V DC for 1 minute to earth
noise level 54.5 dB conforming to 86/188/EEC
power dissipation in W 36 W (natural convection) at 380 V switching frequency 4 kHz
145 W (forced convection) at 380 V switching frequency 4 kHz
volume of cooling air 38 m3/h
operating position Vertical +/- 10 degree
THDI <= 48 % full load conforming to IEC 61000-3-12
4
electromagnetic compatibility Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 level 4
1.2/50 µs - 8/20 µs surge immunity test conforming to IEC 61000-4-5 level 3
Radiated radio-frequency electromagnetic field immunity test conforming to IEC
61000-4-3 level 3
Conducted radio-frequency immunity test conforming to IEC 61000-4-6 level 3
Electrostatic discharge immunity test conforming to IEC 61000-4-2 level 3
pollution degree 2 conforming to EN/IEC 61800-5-1
vibration resistance 1.5 mm peak to peak (f = 2...13 Hz) conforming to IEC 60068-2-6
1 gn (f = 13...200 Hz) conforming to IEC 60068-2-6
shock resistance 15 gn during 11 ms conforming to IEC 60068-2-27
relative humidity 5...95 % without condensation conforming to IEC 60068-2-3
ambient air temperature for operation -15...50 °C without derating
50...60 °C with derating factor
ambient air temperature for storage -40...70 °C
operating altitude 1000...4800 m with current derating 1 % per 100 m
<= 1000 m without derating
environmental characteristic Dust pollution resistance class 3S3 EN/IEC 60721-3-3
Chemical pollution resistance class 3C3 EN/IEC 60721-3-3
standards EN/IEC 61800-3 environment 1 category C2
EN/IEC 61800-3
IEC 60721-3
UL 508C
IEC 61508
IEC 13849-1
EN/IEC 61800-5-1
IEC 61000-3-12
EN/IEC 61800-3 environment 2 category C3
product certifications TÜV
REACH
ATEX zone 2/22
CSA
ATEX INERIS
DNV-GL
UL
marking CE
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1444 - Schneider Electric declaration of conformity-
Schneider Electric declaration of conformity
REACh
Reference contains SVHC above the threshold - go to CaP for more details Go
to CaP for more details
Product environmental profile
Available Product Environmental
Product end of life instructions
Available End Of Life Manual
5
Product data sheet ATV630U55N4
Dimensions Drawings
Dimensions
6
Product data sheet ATV630U55N4
Mounting and Clearance
Clearances
X1 X2 X3
● Mount the device in a vertical position (±10°). This is required for cooling the device.
● Do not mount the device close to heat sources.
● Leave sufficient free space so that the air required for cooling purposes can circulate from the bottom to the top of the drive.
Mounting Types
7
Mounting Type B: Side by Side IP20
8
Product data sheet ATV630U55N4
Connections and Schema
Single or Three-Phase Power Supply with Upstream Breaking via Line Contactor
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance
with standard IEC/EN 60204-1
(1) Use digital output R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
KM1 :Line Contactor
Q2, Circuit breakers
Q3 :
S1, Pushbuttons
S2 :
T1 : Transformer for control part
Single or Three-Phase Power Supply with Downstream Breaking via Switch Disconnector
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance
with standard IEC/EN 60204-1
(1) Use digital output R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
Q1 : Switch disconnector
9
(1) Safe Torque Off
(2) Analog Output
(3) Digital Input
(4) Reference potentiometer
(5) Analog Input
A1 : ATV6.. Drive
R1A, Fault relay
R1B,
R1C :
R2A, Sequence relay
R2C :
R3A, Sequence relay
R3C :
Sensor Connection
It is possible to connect either 1 or 3 sensors on terminals AI2 or AI3.
The switch is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
● Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
● Set the switch to Ext if using PLC outputs with NPN transistors.
Switch Set to SRC (Source) Position Using the Output Power Supply for the Digital Inputs
10
Switch Set to SRC (Source) Position and Use of an External Power Supply for the DIs
Switch Set to SK (Sink) Position Using the Output Power Supply for the Digital Inputs
Switch Set to EXT Position Using an External Power Supply for the DIs
11
Product data sheet ATV630U55N4
Performance Curves
Derating Curves
12