BMS IO Summary

This document provides an I/O summary for an HVAC system with details on 17 I/O points for 7 air handling units. It lists the quantity, type of I/O, cable details, vendors and scope of work between the BMS DDC and client. Key I/Os include on/off command, run status, temperature and humidity monitoring for supply and return air, valve modulation control signal, VFD control signal and feedbacks for speed, frequency, current, voltage, power, and run time. The vendors will provide sensors, actuators and install cabling while the client will provide holes and terminals for integration.

Uploaded by

Royal Aircon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
192 views1 page

BMS IO Summary

This document provides an I/O summary for an HVAC system with details on 17 I/O points for 7 air handling units. It lists the quantity, type of I/O, cable details, vendors and scope of work between the BMS DDC and client. Key I/Os include on/off command, run status, temperature and humidity monitoring for supply and return air, valve modulation control signal, VFD control signal and feedbacks for speed, frequency, current, voltage, power, and run time. The vendors will provide sensors, actuators and install cabling while the client will provide holes and terminals for integration.

Uploaded by

Royal Aircon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

DOCUMENT : BMS I/O SUMMARY FOR HVAC

I/O DETAILS CABLE DETAILS VENDORS CLIENT'S


Sl.NO PARTICULARS QTY
AI DI AO DO Soft Type Runs Tag From To Scope of Work Scope of Work
I HVAC
B AHU 07
BMS DDC shall provide potential free (N.O.) AHU panel shall accept potential free (N.O.)
1 On/Off Command 07 2 Core 07 AHU-ONOF-CMD DDC AHU Panel contact to AHU panel. contact from BMS DDC.
Supply, Installation, Testing & Commissionig of Provision of 8mm dia hole at suitable location for
2 Run Status 07 2 Core 07 AHU-RUN-STS Air DPS DDC Air Diff. Pressure Switch (DPS). pressure pickup tube installation.
BMS DDC shall accept potential free (N.O.) AHU panel shall provide potential free (N.O.)
3 Auto Manual status 07 AHU-A/M-STS AHU Panel DDC contact from AHU panel. contact to BMS DDC.
4 Core 07
BMS DDC shall accept potential free (N.O.) AHU panel shall provide potential free (N.O.)
4 Trip Status 07 AHU-TRIP-STS AHU Panel DDC contact from AHU panel. contact to BMS DDC.

Supply, Installation, Testing & Commissionig of Provision of 8mm dia hole at suitable location for
5 Filter status 14 2 Core 14 AHU-FLTR-STS Air DPS DDC Air Diff. Pressure Switch (DPS). pressure pickup tube installation.

Duct Temp Supply, Installation, Testing & Commissioning of Provision of 1/4" hole to be made on the side of
6 Supply Air Temperature & RH Monitoring 05 2 Core 05 AHU-SA-TEMP DDC
Sensor Duct Temp Sensor. duct for Duct Temp Sensor probe insertion.
7 Return Air Temperature & RH Monitoring 05 2 Core 05 AHU-RA-TEMP Duct Temp Supply, Installation, Testing & Commissioning of Provision of 1/4" hole to be made on the side of
DDC
Sensor Duct Temp Sensor. duct for Duct Temp Sensor probe insertion.
BMS DDC shall provide 0-10 Vdc signal output
Valve Valve Actuator shall accept 0-10Vdc signal for 0-
8 Valve Modulation 0 4 Core 0 AHU-VLV-MOD DDC for 0-100% valve open to Valve Actuator. 24Vac
Actuator 100% valve open from BMS DDC.
supply to valve actuator.
BMS DDC shall provide 0-10 Vdc signal output AHU VFD shall accept 0-10Vdc signal for 0-
9 VFD control Signal 07 2 Core 07 AHU-VFD-CTR DDC AHU VFD for 0-100% speed to AHU VFD. 100% VFD speed from BMS DDC
VFD modulation using diff press transmitter
Supply, Installation, Testing & Commissioning of Provision of 8mm dia hole at suitable location for
10 (Location of Diff. pressure sensor to be in SA 07 4 Core 07 AHU-DP Air DPT DDC
Air Diff. Pressure Transmitter (DPT). pressure pickup tubes installation.
Duct within AHU room itself)
I/O DETAILS CABLE DETAILS VENDOR CLIENT'S
Sl.NO PARTICULARS QTY
AI DI AO DO Soft Type Runs Tag From To Scope of Work Scope of Work
11 VFD soft integration 06
12 AHU's VFD Speed Feedback 07 Shall provide - 1) VFD Modbus RTU RS-485 wire
1) Supply, Installation, Testing & Commissioning
13 AHU's VFD Frequency 07 terminals.
of Modbus RS485 Integrator.
14 AHU's VFD Current 07 1 (Daisy 2) VFD Modbus register mapping list.
2 Core VFD-COMM DDC AHU VFD 2) Communication Cable laying from integrator to
15 AHU's VFD Voltage 07 Chain) 3) VFD Configuration as per site requirement.
VFDs in daisy chain.
16 AHU's VFD Power 07 4) Demonstrate VFD communication in open
17 AHU's VFD Run Time 07 3) VFD point data mapping into BMS Software.
Modbus software like MODSCAN at site.