Inspection Cases and Remarks
Inspection Cases and Remarks
Inspection Cases and Remarks
230KV Debrezite III line diff protection relay has signaling fail
alarm.
5 Modjo II In 230 KV line 2
Line diff relay has signaling fail alarm
Line distance relay has Gosse IED absent alarm.
BBP device relay has fiber com error alarm.
6 Debrezite II There is one siemens relay in incoming feeder relay which is replaced by
micom relay.
Debrezite III BB coupler diff relay(P741) relay cannot working
7
8 Adama I 132KV outgoing and incoming line protection relay display boards
cannot read. So they cannot get any information on the relay.
132/15 kV transformer P123 OC relay is not working.
9 Asela We cannot able to write data in 132/33/15 kV transformer 87T T60 GE
relay since its display is incorrect.
In 230KV Diredawa line-bus bar diff protection, Koka line-bus bar
10 Awash 7 diff protection; in 230/132KV trafo 1-bus bar protection; in
230/132KV trafo 2- bus bar protection relays date and time cannot
set.
One feeder relay not working.
11 Debre Birhan I P120 F50N3 relay is damaged which is found in 132/33/15 kV
transformer.
12 Debre Birhan II
13 Metehara
14 Ilala Geda
15 Adama II
16 Tulufa Mobile There are two feeder relays which are idle because of breaker failer.
17 Dukem II
18 Koye Abo FMR protection relay PCS-974 cannot extracted when we try to extract.
It says, it is not getting the driver.
19 Klinto
20 Ayat GIS Four outgoing feeders are not working since transformer 2 are not
working. So, the relays are idle.
21 Kotebe Old Two transformer differential relays P632 are not working.
22 Kotebe New In line 2 differential protection is not working.
132 kV sebeta line distance protection is not working. On transformer 1
23 Mekanisa P122 relay button is not working. On transformer 2 P123 relay button is
not working
On 15 kV feeders couplage relay is not working
24 Sebeta I 230 kV gibe 2 line two siemens relays are defective.
Since transformer 1 is damaged, there is no relay panel
25 Wergenu
26 Addis east I In 132/15 kV transformer, RET670 relay are not working
27 Addis east II (Bella) In 132 kV Addis north line P143 relay fail.
In 132/15 kV transformer 1 P143 relay fail.
In 132/15 kV transformer 2 P143 relay fail.
28 Minilik GIS
29 Addis North There is idle 132 kV line protection panel. Because of no CB and CT are
there in Minilik to Addis north line PCS-931 and PCS-902 protection
relays are idle as the substation manager said.
30 Shegolie In 132/15 kV transformer, RET670 relay is not working