Annular Seal Area Protection of Open Top Floating Roof Tanks. “Top of Seal” method with
foam dam, utilizing fixed discharge outlets (foam chambers).
Tanks with Foam Dams < 24” High - Maximum spacing is every 40 linear ft.
Tanks with Foam Dams 24” high or Greater- Maximum spacing is every 80 linear ft.
Example Calculation for an 120’ Diameter Tank with 24” High Foam Dams:
07012007
• Minimum Application Density of Foam Solution is 0.3 gpm per Sq. Ft.
07012007
NFPA 11 recommends the following minimums for supplementary foam hose streams to protect the diked area from small
spills or fires. Minimum flow rates are based on 50 gpm per handline.