0% found this document useful (0 votes)
282 views5 pages

Apc Amc2 4

The AMC2 is an access controller that can control up to eight entrances and interfaces. It can connect to up to four ID card readers and has inputs and outputs to control doors, gates, and other access points. It stores authorization data and transaction logs locally on a compact flash card.

Uploaded by

Dixon Flores
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
282 views5 pages

Apc Amc2 4

The AMC2 is an access controller that can control up to eight entrances and interfaces. It can connect to up to four ID card readers and has inputs and outputs to control doors, gates, and other access points. It stores authorization data and transaction logs locally on a compact flash card.

Uploaded by

Dixon Flores
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Engineered Solutions - AMC2 - Access Modular Controller

AMC2 - Access Modular Controller

u Intelligent access manager for one to eight


entrances

u A maximum of four interfaces include the reader


power supply

u Standard 2 GB Compact Flash

u LCD display for displaying information

u A maximum of eight input and output contacts

The AMC2 (Access Modular Controller) is used as an independent authorization on access points, takes
access controller in the access control systems: access decisions, controls closing/opening elements
• BISACE (Access Engine) from version 2.0 onward and registers movement events.
• AMS (Access Management System)
• APE (Access Professional Edition). System overview

The device controls a group of one to eight access 1


points. These access points, also known as entrances,
can be:
• doors
2 2 2 2
• gates
• barriers
• turn stiles
3 3
• revolving doors
• mantraps 4 4
• ID card, PIN and biometric readers 3 3
• door opening elements
• sensors.
1 Host computer 2 AMC2
The AMC2 can control a maximum of eight ID readers
(depending on the reader type) and fully processes 3 Card reader 4 Communication and power
the access logic at the assigned entrances. supply
The controller can be connected to the host system
The analog inputs have a status recognition of the through one of the following interfaces, depending on
connected lines. the type of installation:
With RS485 operation, a maximum of eight access
The relay outputs activate the door opening elements controllers can be connected to one party line.
and/or generate the security activation and signaling. The communication between the host system and the
controller via RS485 is encrypted with up to AES256,
The AMC2 stores all necessary information in a depending on the firmware version used.
battery-buffered memory and a compact flash storage In the communication chain of a system, the access
element. Thus, even when the unit is offline, it checks controller is integrated between the host system and
the peripheral devices.
Engineered Solutions - AMC2 - Access Modular Controller 2|5

Functions • 4 and 7 for AC.


• 5 and 7 for battery.
• Storing downloaded data as listed below:
• 6 and 7 for DC.
– Master data Otherwise, these pins will short-circuit.
– Authorizations
– Access models Quantity restrictions
– Display texts • Follow the Access Engine installation and
configuration instructions regarding the maximum
– Reader configurations number of access controllers on one access control
• Interpretation of transaction data from reader: system.
– Authorization check • The maximum number of cards that a controller can
store is 400,000, depending on the access host
– Host request
system and the license used. For further
– PIN code information, refer to the datasheets of the BIS/ACE
• Control/monitoring: and AMS access control systems.
– Denial or door release
– Switching alarm Connections to the ID card readers

– Door statuses Wiegand interfaces


The AMC2 2WCF has two connections for connecting
– Reader operation statuses
a maximum of two ID card readers.
– Internal alarm statuses The AMC2 4WCF has four connections for connecting
• Messages to Access Engine: a maximum of four ID card readers.
The element interfaces of the ID card reader and the
– Host requests
door control are divided into groups, each with reader
– Transaction data for storing interface, two input and two output contacts.
– Error and malfunction messages The following definitions apply to the Wiegand
interfaces:
– Alarm messages
• 10-wire interface (including shield).
• Power supply for:
• Maximum cable length of 158 m (500 ft) to the ID
– Readers card reader.
– Door openers RS485 interfaces
– Contact current feeds The AMC2 4R4CF has four connections for connecting
a maximum of eight ID card readers, using secure
Regulatory information OSDPv2 protocol. The interfaces are divided into two
buses. A maximum of eight readers can be connected
Region Regulatory compliance/quality marks to one interface.
Countries of Eurasian EAC RS485 interface definition:
Customs Union • 2-wire interface: Using the 10-pin pluggable
connector.
Region Regulatory compliance/quality marks • Maximum length of the bus: 1200 m.
• Transfer rates: 9.6 kbit/s.
Poland CNBOP AMC2 4WCF

CNBOP AMC2 4R4CF Reader and door models


The AMC2 controls the connected reader through
USA UL UL 294; Refer to Ordering Information predefined door models.
Door models control in accordance with the relevant
FCC Part 15 Class B; Refer to Ordering security requirements:
Information • Number and usage of the readers connected to the
AMC2, such as input and output readers, input
Installation/configuration notes readers, buttons.
Power supply • Number and application type of the AMC inputs,
An external power supply (10 to 30 V DC) for the such as door status, output button, revolving door
AMC2 is connected to the pin 1 (positive) and 3 position.
(negative). When using an uninterruptible power • Number and usage of AMC outputs, such as door
supply (UPS), the relevant UPS output relay can be opener, mantrap contact, signal light switching.
connected to the pins:
Engineered Solutions - AMC2 - Access Modular Controller 3|5

The maximum number of entrances to be managed by Capacity


one AMC2 is ultimately defined by the door models
used and their requirements regarding readers and Number of analog inputs • AMC2-2WCF: 4
inputs/outputs. • AMC2-4WCF: 8
• AMC2-4R4CF: 8
Voltage equalization: grounding
• Potential differences can be compensated through Number of relay outputs • AMC2-2WCF: 4
the protective grounding with a jumper. • AMC2-4WCF: 8
• A line (shield, equipotential bonding line) with
• AMC2-4R4CF: 8
protective ground can only be connected in one
position.
Connectivity
• For further instructions, see the operating manual.
Host interface • RS485 (2- or 4- wire); opto-
Contacts decoupled
Inputs • Ethernet 10/100BaseT (TCP/IP)
The eight analog inputs can be used as digital or with RJ45
analog contacts. For analog use, resistance values can
be specified that make it possible to carry out a Reader interfaces • AMC2-2WCF: 2 Wiegand
further check for cable breaks and short-circuits. • AMC2-4WCF: 4 Wiegand
Relay outputs • AMC2-4R4CF: 4 RS485; 2-wire,
The relay outputs offer the following functions: opto-coupled, 9,600 Bd
• The outputs can operate with potential free
contacts for external power supply (dry mode). Electrical
• The outputs can operate using the internal voltage
of power supply (wet mode). Power supply 10 to 30 VDC, max. 60 VA
• Only ohm resistive loads can be connected to the Available for external devices: 55 VA
relay.
• Inductive loads must be bypassed through recovery Environmental
diodes. These diodes (1N4004) are enclosed.
Operating temperature (°C) 0 °C – 45 °C
General instructions
• AMC2 and related equipment should be mounted in Operating temperature (°F) 32 ºF - 113 ºF
a "secured area".
• Detailed connection conditions are specified in the IP rating IP30
operating manual.
• After purchase, primary AC power must be done by Mechanical
a licensed electrician.
Color White
Technical specifications

Hardware Dimension (H x W x D) (mm) 232 mm x 90 mm x 63 mm

Components and features • Integrated Microcontroller Dimension (H x W x D) (in) 9.13 in x 3.54 in x 2.48 in

• 512 kB-EPROM/FLASH Material Base: PPO (UL 94 V-0)


• 256 kB-SRAM Upper: Polycarbonate (UL 94 V-0)

• Serial EEPROM Mounting type Rail-mounted


• RTC
Weight (g) 503 g - 540 g
• Pluggable 2 GB Compact Flash
Weight (lb) 1.1 lb - 1.19 lb
• Battery for SRAM and RTC

• Reset button Operation


• Host address can be set via DIP
Protection Tamper switch
switch
Engineered Solutions - AMC2 - Access Modular Controller 4|5

Ordering information API-AMC2-16ION Standalone controller for BIS with


OPC
APC-AMC2-2WCF Door controller WI, 2 readers Standalone controller with inputs and outputs only.
Two Wiegand interfaces for up to 2 card readers, Compatible with BIS in combination with OPC Server
network connection to the host system and Compact only.
Flash memory (2 GB). Host data transfer encrypted. Order number API-AMC2-16ION | F.01U.013.384
F.01U.407.657: CE certification. F.01U.371.285: CE and
APS-PSU-60 Power supply unit
UL certification.
A power supply unit with an integrated battery charging
Order number APC-AMC2-2WCF | F.01U.407.657
device, that supports 12 V/7 Ah, 12 V/14 Ah and 24 V/7
F.01U.371.285
Ah batteries, with selectable 12 VDC or 24 VDC voltage
APC-AMC2-4WCF Door controller Wiegand with CF output.
card Order number APS-PSU-60 | F.01U.282.970
Four Wiegand interfaces for up to 4 card readers,
D126 Battery, 12V 7Ah
network connection to the host system and Compact
A rechargeable sealed lead‑acid power supply used as a
Flash memory (2 GB). Host data transfer encrypted.
secondary power supply or in auxiliary or ancillary
F.01U.407.651: CE certification. F.01U.027.201: CE and
functions.
UL certification.
Order number D126 | 4.998.125.825
Order number APC-AMC2-4WCF | F.01U.407.651
F.01U.027.201 AEC-AMC2-UL01 AMC enclosure with 1 DIN rail
Compliant with UL294 system certification for AMC2.
APC-AMC2-4R4CF Door controller RS485 with CF card
Order number AEC-AMC2-UL01 | F.01U.330.018
Four RS-485 interfaces for up to 8 card readers, network
connection to the host system and Compact Flash AEC-AMC2-UL02 AMC enclosure with 2 DIN rails
memory (2 GB). Host data transfer encrypted. Reader Compliant with UL294 system certification for AMC2.
data transfer encrypted according to reader capabilities. Order number AEC-AMC2-UL02 | F.01U.330.017
F.01U.407.653: CE certification. F.01U.027.206: CE and AEC-PANEL19-UPS Fitting panel, 19", 2 DIN rails
UL certification. Mounting plate with two DIN rails, a battery bracket, and
Order number APC-AMC2-4R4CF | F.01U.407.653 screw sockets for the power supply to mount into 19”
F.01U.027.206 racks.
Order number AEC-PANEL19-UPS | F.01U.066.193
Accessories
AEC-PANEL19-4DR Fitting panel, 19", 4 DIN rails
API-AMC2-4WE Door controller Wiegand extension
Mounting plate with four DIN rails for 19” racks to
The extension module AMC2 4W-EXT is equipped with
connect max. four AMC2 devices.
four Wiegand type reader-interfaces plus eight inputs
Order number AEC-PANEL19-4DR | F.01U.066.194
and eight outputs. Hence with the AMC2 4W-EXT it is
possible to double the number of readers on an AMC2 ACX-RAIL-400 DIN rail 400mm
4W from 4 to 8. F.01U.407.652: CE certification. Mounting rail (400 mm) for mounting the AMC2
F.01U.011.593: CE and UL certification. component (controller and PSU) when the metal housing
Order number API-AMC2-4WE | F.01U.407.652 is not used.
F.01U.011.593 Order number ACX-RAIL-400 | F.01U.510.954
API-AMC2-8IOE Extention board with 8-input 8-output ACX-RAIL-250 DIN rail 250mm
8 input/output extension board, up to three per AMC, Mounting rail (250 mm) for mounting the AMC2
can be combined with the AMC2 16I-EXT and the AMC2 component when the metal housing is not used.
16I-16O-EXT. F.01U.407.654: CE certification. Order number ACX-RAIL-250 | F.01U.510.935
F.01U.027.200: CE and UL certification.
Order number API-AMC2-8IOE | F.01U.407.654 Services
F.01U.027.200 EWE-AMCCTR-IW 12 mths wrty ext. AMC Reader
Controller
API-AMC2-16IOE Extention board with 16-input 16-
12 months warranty extension
output
Order number EWE-AMCCTR-IW | F.01U.364.824
16 input/output extension board, up to three per AMC,
can be combined with the AMC2 16I-EXT and the AMC2
8I-8O-EXT. F.01U.407.655: CE certification.
F.01U.013.385: CE and UL certification.
Order number API-AMC2-16IOE | F.01U.407.655
F.01U.013.385
API-AMC2-16IE Extention board with 16-input
16 input extension board, up to three per AMC, can be
combined with the AMC2 16I-16O-EXT and the AMC2
8I-8O-EXT. F.01U.407.656: CE certification.
F.01U.045.514: CE and UL certification.
Order number API-AMC2-16IE | F.01U.407.656
F.01U.045.514
Engineered Solutions - AMC2 - Access Modular Controller 5|5

Represented by:

Europe, Middle East, Africa: Germany: North America: Asia-Pacific:


Bosch Security Systems B.V. Bosch Sicherheitssysteme GmbH Bosch Security Systems, LLC Robert Bosch (SEA) Pte Ltd, Security Systems
P.O. Box 80002 Robert-Bosch-Ring 5 130 Perinton Parkway 11 Bishan Street 21
5600 JB Eindhoven, The Netherlands 85630 Grasbrunn Fairport, New York, 14450, USA Singapore 573943
Phone: + 31 40 2577 284 Tel.: +49 (0)89 6290 0 Phone: +1 800 289 0096 Phone: +65 6571 2808
www.boschsecurity.com/xc/en/contact/ Fax:+49 (0)89 6290 1020 Fax: +1 585 223 9180 Fax: +65 6571 2699
www.boschsecurity.com [email protected] [email protected] www.boschsecurity.com/xc/en/contact/
www.boschsecurity.com www.boschsecurity.com www.boschsecurity.com

Data subject to change without notice | 202210171623 | V6 | October 17, 2022 © Bosch Security Systems 2022

You might also like