0574 - CR240-80

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Greenhouse - Condensate Return

Pressure Loss Calculator - Version 1605.34.17.65


8 May 2020, 8:11 AM
Calculation Reference - 00001 - PLC - 36/2020
Registered User - Leonine International

Site Location Chapais, Quebec, Canada


Fluid type Condensate - pumped
Pressure 595 kPa abs 86.3 psia
Temperature 100 °C 212 °F
Atmospheric Pressure 95 kPa 13.8 psi
Gauge Pressure 500 kPag 72.5 psig
Fluid Density 958.2 kg/m³ 59.8 lb/ft³

Effective
Item Line tag/identification Fitting type Mass flow Size Elevation Quantity No: of pipe
length
[kg/hour] DN [m] Diameters [m]
1 SL001 - 125 Pipe- Carbon steel 12,304 80 0 341.0m 1 341.000
2 SL001 - 125 Bend LR r/D=2.0 12,304 80 0 23 1 1.840
3 L-001 Eq. T: Branch-Barrelx1 12,304 80 0 10 70 56.000
4 SL-001 Gate valve- open 12,304 80 0 2 7 1.120
5 SL-001 Reducer- eccentric 12,304 80 27 1 7 0.560
6 ILVA Flow meter Flow meter - ILVA 12,304 80 0 1 1 0.080
7 CL-001 Disk check valve- open 12,304 80 0 2 500 80.000
8 Deaerator Spray Nozzle DP Vessel 12,304 80 0 1 1 0.080
9 DA Operating Pressure (7 psig) Vessel 12,304 50 0 1 1 0.050
10 CL-001 Pipe- Carbon steel 6,150 50 0 2.0m 1 2.000
11 CL-001 Bend LR r/D=1.5 6,150 50 0 4 14 2.800
12 CL-001 Gate valve- open 6,150 50 0 1 7 0.350
13 CL-001 Disk check valve- open 6,150 50 0 1 500 25.000
Greenhouse - Condensate Return
Pressure Loss Calculator - Version 1605.34.17.65
8 May 2020, 8:11 AM
Calculation Reference - 00001 - PLC - 36/2020
Registered User - Leonine International

Site Location Chapais, Quebec, Canada


Fluid type Condensate - pumped
Pressure 595 kPa abs 86.3 psia
Temperature 100 °C 212 °F
Atmospheric Pressure 95 kPa 13.8 psi
Gauge Pressure 500 kPag 72.5 psig
Fluid Density 958.2 kg/m³ 59.8 lb/ft³

Results
Volume Pressure Exit Exit Percentage
Item Size - Fitting Flow Velocity Drop Pressure Pressure DP
DN m³/hour m/s Pa kPa a kPa g %
1 80, Pipe- Carbon steel 12.8 0.8 28,289 566.7 471.7 7.2
2 80, Bend LR r/D=2.0 12.8 0.8 153 566.6 471.6 0.0
3 80, Eq. T: Branch-Barrelx1 12.8 0.8 4,330 562.3 467.2 1.1
4 80, Gate valve- open 12.8 0.7 74 562.2 467.2 0.0
5 80, Reducer- eccentric 12.8 0.8 46 562.1 467.1 0.0
6 80, Flow meter - ILVA 12.8 0.7 17,845 544.3 449.3 4.6
7 80, Disk check valve- open 12.8 0.7 5,301 539.0 444.0 1.3
8 80, Vessel 12.8 0.7 24,200 514.8 419.8 6.2
9 50, Vessel 12.8 1.8 48,300 466.5 371.5 12.4
10 50, Pipe- Carbon steel 6.4 0.8 244 466.2 371.2 0.0
11 50, Bend LR r/D=1.5 6.4 0.8 341 465.9 370.9 0.0
12 50, Gate valve- open 6.4 0.9 68 465.8 370.8 0.0
13 50, Disk check valve- open 6.4 0.9 4,845 461.0 366.0 1.2

Total Net Elevation 253,806 65.4


Total Line Pressure Drop 134,036 34.6
Total Pressure Drop 387,843 100.0
Exit Pressure 207.0 112.0

ASPE, 2016- 1:240 down in the direction of flow


Spirax Sarco 'The Steam and Condensate Loop Book' recommends slope 1:70 for condensate lines
Marshall, 2017- not less than 1:70
Ian Flemming, Optimizing Steam Systems, PTQ Q2 2010- 150mm/10m (1:66.7)
Steam Specialty Sales Engineering Guide- 1:100

Pump head 41.3 m WG


Margin 20% 49.6 m WG

You might also like