Transient Over Voltages
Transient Over Voltages
It generally occurs for a very short duration of time (less than a cycle).
These over voltages have the potential to result in large financial losses each
year due to damaged equipment and lost production.
Surge suppressors are devices that conduct across the power line when some
voltage threshold is exceeded.
Typically they are used to absorb the energy in high frequency transients.
Transients can be classified into two categories:
1. Impulsive Transient
2. Oscillatory Transient
An oscillatory transient is a sudden, non–power frequency change in the
steady-state condition of voltage, current, or both, that includes both
positive and negative polarity values.
Some of the causes of transient over voltages on power systems are,
Lightning – either direct strokes or by induction from nearby strokes.
Switching of utility capacitor banks
Resonance and Ferro resonance conditions on long or lightly loaded circuits.
i) Lightning:
◦ Lightning strikes are the most common source of extreme transient over-
voltages,
◦ Lightning is a powerful source of impulsive transients.
◦ where total outage of an unprotected system can occur with damage to
cabling insulation through flashover potentially resulting in loss of life
through fire and electric shock.
This transient can propagate into the utility’s local power system,
pass through its distribution transformer, and enter into the end
user’s load facilities.
The capacitor switch contacts are closed at a
point near the system voltage peak. This is
common to all switching techniques because the
insulation across the switch contacts tends to
break down when the voltage across the switch is
at a maximum value.
The voltage across the capacitor at this instant is
zero.
The capacitor voltage cannot change
instantaneously and hence the system voltage at
the capacitor location is briefly pulled down to
zero and rises as the capacitor begins to charge
toward the system voltage.
At the monitoring location shown, the initial
change in voltage will not go completely to zero
because of the impedance between the
observation point and the switched capacitor.
However, the initial drop and subsequent ringing
transient that is indicative of a capacitor-
switching event will be observable to some
degree.
The overshoot will generate a transient between
1.0 and 2.0 pu depending on system damping. In
Utility capacitor-switching transients are
commonly in the 1.3- to 1.4-pu range
Example: A 2000-kVAR, 13.8-kV, Y-connected capacitor bank is connected at
the end of a 25-mile transmission line with an inductive reactance of 0.5 Ω per mile.
Find the natural frequency of the current that would be drawn during turn on:
.
The concept of Clamping devices are very simple. This device
behaves like a nonlinear resistors.
◦ Under normal voltage level, these devices withstand easily the system
voltage as electrical insulator and provide no conducting path to the
system current.
◦
◦ On occurrence of voltage surge in the system, these devices provide very
low impedance path for the excess charge of the surge to the ground
There are several types of lightning arresters
in general use. They differ only in
constructional details but operate on the
same principle, providing low resistance path
for the surges to the round.