Voltage Drop PDF

This document discusses calculating voltage drop and selecting the appropriate cable size for an electrical load. It provides details on the load of 120KW at 170 meters from the source with 415V voltage and 0.8 power factor. The permissible voltage drop is 5%. It then calculates correction factors for the buried cable in wet soil at 1 meter depth. Examining cables of 95 mm^2 and 120 mm^2, it determines that the 120 mm^2 cable meets all requirements of having sufficient current capacity and voltage drop under 5% for the single run needed.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
99 views5 pages

Voltage Drop PDF

This document discusses calculating voltage drop and selecting the appropriate cable size for an electrical load. It provides details on the load of 120KW at 170 meters from the source with 415V voltage and 0.8 power factor. The permissible voltage drop is 5%. It then calculates correction factors for the buried cable in wet soil at 1 meter depth. Examining cables of 95 mm^2 and 120 mm^2, it determines that the 120 mm^2 cable meets all requirements of having sufficient current capacity and voltage drop under 5% for the single run needed.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

CABLE SIZE & VOLTAGE DROP CALCULATION

Calculate Voltage Drop and Size of Cable for Below given data.
 Electrical Details: Electrical Load of 120KW,

Distance between Source and Load is 170 Meter,

System Voltage 415V Three Phase,

Power Factor is 0.8,

Permissible Voltage drop is 5%,

Demand Factor is 1,

 Cable Laying Detail: Cable is directed buried in Ground in trench at the depth of 1 meter.

Ground Temperature is approximate 35 Deg.

No of Cable per Trench is 1.

No of Run of Cable is 1 Run.

 Soil Details: Thermal Resistivity of Soil is not known.

Nature of Soil is Very Wet Soil.

Let’s Begin Calculation:


 Consumed Load= Total Load x Demand Factor

 Consumed Load in KW= 120 x 1 =120KW

 Consumed Load in KVA= KW / P.F.

 Consumed Load in KVA =120/0.8=150KVA

 Full Load Current = (KVAx1000) / (1.732xVoltage)

 Full Load Current= (150×1000) / (1.732×415) = 218Amp.

Calculating Correction Factor of Cable from Below data.


Temperature Correction Factor (K1) When Cable is in Air is.

Ground Temperature Correction Factor (K2):


Thermal Resistance Correction Factor (K4) for Soil (When Thermal Resistance of Soil is known):

Soil Correction Factor(K4) of Soil (When Thermal Resistance of Soil is not known):

Cable Depth Correction Factor (K5):


Cable Distance correction Factor (K6):

Cable Grouping Factor (No of Tray Factor) (K7):

 According to above Detail correction Factors are


 Ground Temperature Correction Factor (K2) =0.89
 Soil Correction Factor (K4) =1.21
 Cable Depth Correction Factor (K5) =1.0
 Cable Distance correction Factor (K6) =1.0
 Total De rating Factor= k1x k2 x k3 x K4 x K5 x K6 x K7
 Total De rating Factor= 1.07
Selection of Cable:
 For selection of Exact Cable following Conditions should be satisfied.

 (1) Cable De rating Amp should be higher than Full Load Current of Load.

 (2) Cable Voltage Drop should be less than Defined Voltage drop.

 (3) No of Run of Cable >= (Full Load current / Cable De rating Current).

 (4) Cable Short Circuit Capacity should be higher than System S.C Capacity at that Point.

Selection of Cable Case (1):


 Let’s Select 3.5Core 95 Sq.mm cable for Single run.

 Current Capacity of 95 Sq.mm cable is 200 Amp, Resistance=0.411 Ω / Km and

Reactance = 0.074 mho / Km

 Total De rating Current of 95 Sq.mm Cable = 200×1.07 = 214 Amp.

 Voltage Drop of Cable= (1.732x Current x (R cos Ǿ + J sin Ǿ) x Cable Lengthx100) / (Line Voltage
x No of Runx1000)

 Voltage Drop of Cable= (1.732x218 x (0.411×0.8 + 0.074×0.6) x 170x100) / (415x1x1000) = 5.77%

 Voltage Drop of Cable = 5.77%

 Here Voltage drop for 95 Sq.mm Cable (5.77%) is higher than Define Voltage drop (5%)
so either select higher size of cable or increase No. of Cable Runs.

 If we Select 2 Run of Cables (95 sq. mm) than Voltage drop is 2.88% which is within limit (5%) but to use
2 No’s. of cable of 95 Sq.mm Cable is not economical so It is necessary to use next higher size of Cable.

Selection of Cable Case (2):


 Let’s Select 3.5 Core 120 Sq.mm cable for Single run, S.C Capacity = 8.2KA.

 Current Capacity of 120 Sq.mm cable is 225 Amp, Resistance = 0.325 Ω / Km and

Reactance = 0.072 mho / Km

 Total De rating Current of 120 Sq.mm Cable= 225 × 1.07 =240.75 Amp.

 Voltage Drop of Cable= (1.732x218x(0.325 × 0.8 + 0.072 × 0.6) x 170 x 100) / (415x1 x 1000) = 4.68%
 Voltage Drop of Cable = 4.68%

 To decide 120 Sq.mm Cable, Cable selection condition should be checked.

 (1) Cable De rating Amp (240 Amp) is higher than Full Load Current of Load (218 Amp) = O.K

 (2) Cable Voltage Drop (4.68%) is less than Defined Voltage drop (5%) =O.K

 (3) No of Run of Cable (1) >= (218A / 240A =0.908) =O.K

 (4) Cable S.C Capacity (11.28KA) is higher than System S.C Capacity at that Point (8.93KA) = O.K

 120 Sq.mm Cable satisfied all three conditions, so it is advisable to use 3.5 Core 120
Sq.mm cable