User Manual Controller MAM 200
User Manual Controller MAM 200
USER MANUAL
Screw Compressor Manual
MAM-200
1 | 16
Operation Manual MAM-200
1. Basic Operation
1.1. Button explanation
1.2. Status Display and Operations
1.3. Calendar
1.4. Customer Parameter
1.5. Factory Parameter
1.6. Operating Authorization and Password
2. Controller Function and Technical Parameter
3. Model and Specification
3.1. Main Controller Model Description
3.2. Monitor Description
3.3. Power Consumption Table for Corresponding Motor
4. Installation
4.1. Mechanical Installation
4.2. Electrical Wiring Installation
5. Alarm Function
5.1. Monitor text
5.2. Controller Indicator
6. Controller Protection
6.1. Motor Protection
6.2. Protection for Air Temperature High
6.3. Protction of Air Compressor Reversal
6.4. Protection of Air Pressure High
6.5. Protection of Sensor Failure
7. Troubleshooting
7.1. This Fault Review
7.2. Common Failres and Causes
8. Electronic Diagram
2 | 16
Operation Manual MAM-200
1. Basic Operation
1.1 Button explanation
Start Button
· When compressor is at stop status, press this button to start the compressor
· When compressor is set as main (No.1) in block mode, press this button to start the
compressor and activate block mode function at the same time
Stop Button
· When the compressor is at running status, press this button to stop the compressor
· When compressor is set as main (No1) in block mode, press this button to stop compressor
and block mode as well
Set Button
· When the compressor is at setting mode, press this button after modification to confirm
and save the modified data
· Press this button after input password to verify the password
3 | 16
Operation Manual MAM-200
· When modifying data, press this button to decrease the data at current position
WELCOME USING
SCREW COMPRESSOR
RUN PARAMETER
CALENDAR
CUSTOMER PARAMETER
FACTORY PARAMETER
4 | 16
Operation Manual MAM-200
MOTORS CURRENT
CUR(A): R S T
COIL; ROTORS T
HOST: 00,0 00,0 00,0
TOTAL RUN TIME
FAN: 4,1 4,1 4,1
THIS RUN TIME
CUR (A): R S T
No black cursor appears in the last menu. Press “enter” to return to the previous menu or to the
main menu. If no operation at the current menu for a few seconds, controller will automatically
return to the main menu.
Use “Move down” button, “Move up” button, “Enter button” and “Return button” to check COIL,
ROTORS T, TOTAL RUN TIME, THIS RUN TIME, MAINTENANCE PARAMETER, HISTORY FAULT,
PRODUCTION DATE, NUM, THIS FAULT and return to previous menu.
1.3 Calendar
Check and set time for controller
2004-2-22
W0
12 : 46 : 59
Customer Parameter and Factory Parameter are not allowed to be modified in running and stop
delay status.
When modifying Customer Parameter please refer to run parameter modification method. The
modification process of LOADING P is showing as an example below:
Move the cursor to “CUSTOMER PARAMETER”, press “ENTER” to switch to the following menu:
5 | 16
Operation Manual MAM-200
SET P; T
SET TIME
OPERATION MODE
BLOCKING MODE
LOADING P: 00,65MPa
UNLOADING P: 00.80MPa
User can check the CUSTOMER PARAMETER in this menu or press to switch to the following
menu which requires an enter password.
ENTER PASSWORD
****
Note: Customer password can be set in CUSTOMER PARAMETER and FACTORY PARAMETER is
fixed as ________
In this menu the first data bit of password started blinking, press or to modify the
first bit of password. Press move the cursor to the next data bit, modif the second data of
password. In accordance with the above, modify the third and fourth data of password in
sequence, press “S” to confirm the input data and the menu will switch to the following menu
after verification:
LOADING P: 00,65MPa*
In the menu above press , the first data of LOADING P start to blink, user can press or
to modify the present data in accordance with the above method. Press to move to
next data bit and modify the target data in sequence. When finished press “S” to confirm and save
the data. Other CUSTOMER PARAMETER share the similar way for modification.
6 | 16
Operation Manual MAM-200
7 | 16
Operation Manual MAM-200
2.1 Digital input and output: 9 points of Digital input; 10 points of digital relay output
2.2 Analog input: 6 points of Pt100 temperature input, 1 point of 4 ̴20mA pressure signal
input, 11 group of three phases current inputs (CT provided)
2.5 Measurement:
2.5.1 AIR T: ‐20 ̴ 178°C; Accuracy: ± 1°C
2.5.2 Run time:0 ̴999999H
2.5.3 Current: 0 ̴ 999.9A
2.5.4 Pressure: 0 ̴ 1.60MPa, Accuracy: 0.01MPa
8 | 16
Operation Manual MAM-200
2.6 Phase sequence protection: When compressor is at stop mode and detects wrong phase,
respond time ≤ 2s
2.7 Motor protection: This controller has 5 basic protection function for motor and fan.
2.7.1 Block protection: After start. When operation current is equal to 4-8 times the set
current, respond time ≤ 0.2sec
2.7.2 Short circuit protection: When operation current is equal to 8 times the set current,
respond time ≤ 0.2sec
2.7.3 Phase lack protection: When any lack, the respond time equals to set time
2.7.4 Unbalance protection: When MAX-MIN ≥ SET*MIN/10, respond time is 5sec
2.7.5 Protection features of overload (time unit: second), see following table;
multiple = Iactual / Iset motor operates with delay time according to overload multiples
and operation time shown in following table when motor working current is higher
or equal to the set current from 1.2 times and 3.0 times
Iactual/Iset
2.9 Contact capacity of output relay: 250V, 5A: Contact endurance: 500.000 times
4. Installation
1. Indicator (IN)
10 | 16
Operation Manual MAM-200
The corresponding digital input terminal of 00, 01, 02, 03, 04, 05, 07 is 26, 25, 24, 23, 22,
21, 20, 19, 18
2. Indicator (OUT)
The corresponding digital output terminal of 00, 01, 02, 03, 04, 05, 06, 07, 08. 09 is 39,
40, 41, 42, 43, 46, 47, 49, 50, 51
3. Power Indicator: PWR indicator
4. Run indicator: RUN indicator
5. Error Indicator: ERR indicator
11 | 16
Operation Manual MAM-200
1, 2, 3 N/A 4, 5, 6 Terminal for fan CT2 input 7, 9 Input terminal for AIR T
8, 9 Input terminal for front rotor 10, 12 Inut terminal for AIR P 11 N/A
temperature
13, 15 Input terminal for rear rotor 14, 15 Input terminal for COIL 1 temperature 15, 16 Input terminal for COIL2 temperature
temperature
17, 15 Input terminal for COIL 3 18 High voltage ready 19 “Remote” on
temperature
20 “Remote” off 21 Differential pressure switch 22 Differential pressure switch for oil/air
for air filter separator
23 Differential pressure switch 24 Lack water 25 High voltage cabinet error
for oil filter
26 Emergency stop 27 24V output 28 24V output
29, Input terminal for phase 30, 31 N/A 33, 34 N/A
32,35 sequence
29, Input terminal for phase 30, 31 N/A 33, 34 N/A
32,35 sequence
36, 37, N/A 39 Output signal, start high 40 Output signal, stop high
38
41 High voltage pre-heater 42 Control valve 43 Control fan
on/off
44 Common terminal for output 45 N/A 46 Operation ready
control
47 Dryer 48 N/A 49 Run indicator
53 N/A 54 Terminal for ground 55, 56 220V power supply
connection
Note: 39 terminal: start high voltage cabinet. When turn on, it will close for 5sec and then open
40 terminal: stop high voltage cabinet. When turn off, it will close for 5sec and then open
Electromagnetism coil shall be connected nearest with RC snubber during wiring
5. Alarm Function
5.1 Monitor text
6. Controller Protection
13 | 16
Operation Manual MAM-200
When AIR T is above the AIR STOP T, the controller will send out the alarm to shut
down the machine and this fault displays AIR T HIGH.
When compressor stops and three phases sequence is not in order, this fault displays
PHASE REVERSAL and the controller cannot start the motor. Change the position of
any arbitrary two-phase power lines and check the rotation of motor.
When the AIR P is above the STOP P, the controller will send out the alarm to shut
down the machine and this fault displays AIR P HIGH.
When pressure sensor is disconnected, the controller will send out the alarm to shut
down the machine and this fault displays **SENSOR FAULT.
7. Troubleshooting
7.1 This Fault Review
Failure stop caused by the external parts of controllers may be removed by checking
this fault or history fault, method is shown as below.
Move the cursor to RUN PARA menu, then secondary menu will show:
MOTORS CURRENT
COIL; ROTORS T
Press
MANTENANCE PARAMETER
HISTORY FAULT
14 | 16
Operation Manual MAM-200
Move cursor to THIS FAULT and switch to the following error menu:
15 | 16
Operation Manual MAM-200
8. Electronic Diagram
Stand: 20.12.2016
TOLPEC GmbH
Kelterstrasse 59
DE-72669 Unterensingen
Tel.: +49 2054 8710150
e-mail: [email protected]
www.tolpec.com
16 | 16