At some distance from the terminals, depending upon wire size, the L-N fault current is lower than the L-L fault current. The 1.5 multiplier is an approximation and will theoretically vary from 1.33 to 1.67. These figures are based on change in turns ratio between primary and secondary, infinite source available, zero feet from terminals of transformer, and 1.2 x %X and 1.5 x %R for L-N vs. L-L resistance and reactance values. Begin L-N calculations at transformer secondary terminals, then proceed point-to-point.
Step 5. Calculate "M" (multiplier) or take from Table 2. 1 1 +f Calculate the available short circuit symmetrical RMS current at the point of fault. Add motor contribution, if applicable. M= I S.C. sym. RMS = IS.C. x M Step 6A. Motor short circuit contribution, if significant, may be added at all fault locations throughout the system. A practical estimate of motor short circuit contribution is to multiply the total motor current in amps by 4. Values of 4 to 6 are commonly accepted.
Step 2.
Find the transformer multiplier. See Notes 1 and 2 100 Multiplier = *% Z transformer Step 6.
* Note 1. Get %Z from nameplate or Table 1. Transformer impedance (Z) helps to determine what the short circuit current will be at the transformer secondary. Transformer impedance is determined as follows: The transformer secondary is short circuited. Voltage is increased on the primary until full load current flows in the secondary. This applied voltage divided by the rated primary voltage (times 100) is the impedance of the transformer. Example: For a 480 Volt rated primary, if 9.6 volts causes secondary full load current to flow through the shorted secondary, the transformer impedance is 9.6/480 = .02 = 2%Z. * Note 2. In addition, UL (Std. 1561) listed transformers 25kVA and larger have a 10% impedance tolerance. Short circuit amps can be affected by this tolerance. Therefore, for high end worst case, multiply %Z by .9. For low end of worst case, multiply %Z by 1.1. Transformers constructed to ANSI standards have a 7.5% impedance tolerance (twowinding construction). Step 3. Determine by formula or Table 1 the transformer letthrough short-circuit current. See Notes 3 and 4. Note 3. Utility voltages may vary 10% for power and 5.8% for 120 Volt lighting services. Therefore, for highest short circuit conditions, multiply values as calculated in step 3 by 1.1 or 1.058 respectively. To find the lower end worst case, multiply results in step 3 by .9 or .942 respectively. Note 4. Motor short circuit contribution, if significant, may be added at all fault locations throughout the system. A practical estimate of motor short circuit contribution is to multiply the total motor current in amps by 4. Values of 4 to 6 are commonly accepted. Step 4. Calculate the "f" factor. 3 Faults 1 Line-to-Line (L-L) Faults See Note 5 & Table 3 1 Line-to-Neutral (L-N) Faults See Note 5 & Table 3 1.732 x L x I 3 f= C x n x E L-L 2 x L x I L-L f= C x n x EL-L 2 x L x I L-N f= C x n x EL-N
IS.C. secondary
IS.C. primary
IS.C. secondary
f=
Where: L = length (feet) of conductor to the fault. C = constant from Table 4 of C values for conductors and Table 5 of C values for busway. n = Number of conductors per phase (adjusts C value for parallel runs) I = Available short-circuit current in amperes at beginning of circuit. E = Voltage of circuit. Note 5. The L-N fault current is higher than the L-L fault current at the secondary terminals of a single-phase center-tapped transformer. The short-circuit current available (I) for this case in Step 4 should be adjusted at the transformer terminals as follows: At L-N center tapped transformer terminals, IL-N = 1.5 x IL-L at Transformer Terminals.
f=
Step B.
Step C.
Calculate the short-circuit current at the secondary of the transformer. (See Note under Step 3 of "Basic Point-toPoint Calculation Procedure".) I S.C. secondary = Vprimary Vsecondary x M x I S.C. primary
193
Fault X1
Step 1. If.l. = 1500 x 1000 = 1804A 480 x 1.732
Fault X2
Step 4. Use IS.C.sym RMS @ Fault X1 to calculate f f= 1.732 x 50 x 49,803 = .4050 22,185 x 480 1 = .7117 1 + .4050
Step 2. Step 3.
Multiplier = 100 = 28.57 3.5 IS.C.=1804 x 28.57 = 51,540A IS.C. motor contrib = 4 x 1,804* = 7,216A Itotal S.C. sym RMS = 51,504 + 7,216 = 58,720A Step 5. Step 6.
M=
IS.C. sym RMS = 49,803 x .7117 = 35,445A Isym motor contrib = 4 x 1,804* = 7,216A Itotal S.C. sym RMS = 35,445 + 7,216 = 42,661A
(fault X2)
Step 4.
Step 5. Step 6.
M=
IS.C.sym RMS = 51,540 x .9663 = 49,803A IS.C.motor contrib = 4 x 1,804* = 7,216A ItotalS.C. sym RMS = 49,803 + 7,216 = 57,019A
( fault X1)
*Assumes 100% motor load. If 50% of this load was from motors, IS.C. motor contrib. = 4 x 1,804 x .5 = 3608A
System B
Available Utility Infinite Assumption 1000 KVA Transformer, 480V, 3, 3.5%Z If.l.= 1203A
One-Line Diagram
Fault X1
Step 1. If.l. = 1000 x 1000 = 1203A 480 x 1.732 Multiplier = 100 = 28.57 3.5
Fault X2
Step 4. f = 1.732 x 20 x 33,215 = .1049 2 x 11,424 x 480 M= 1 = .905 1 + .1049
Step 2. Step 3.
Step 5. Step 6.
Step 4.
Fault X3
1600A Switch KRP-C-1500SP Fuse Fault X1 400A Switch LPS-RK-350SP Fuse 1
M=
1 = .9664 1 + .0348
RMS
Step A.
f=
30,059 x 480 x 1.732 x 1.2 = 1.333 100,000 x 225 1 = .4286 1 + 1.333 480 x .4286 x 30,059 = 29,731A 208
I S.C.sym
Step C.
194
A B C Primary Secondary
Short Circuit
1.5 times full winding %R on full winding basis. 1.2 times full winding %X on full winding basis. Note: %R and %X multipliers given in Impedance Data for Single Phase Transformers Table may be used, however, calculations must be adjusted to indicate transformer kVA/2.
3. The impedance of the cable and two-pole switches on the system must be considered both-ways since the current flows to the fault and then returns to the source. For instance, if a line-to-line fault occurs 50 feet from a transformer, then 100 feet of cable impedance must be included in the calculation. The calculations on the following pages illustrate 1 fault calculations on a singlephase transformer system. Both line-to-line and line-to-neutral faults are considered.
L1 N Short Circuit L2
50 Feet
195
196
Note: UL Listed transformers 25 kVA and greater have a 10% tolerance on their impedance nameplate. This table has been reprinted from IEEE Std 242-1986 (R1991), IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems, Copyright 1986 by the Institute of Electrical and Electronics Engineers, Inc. with the permission of the IEEE Standards Department.
. Impedance Data for Single-Phase and Three-Phase TransformersSupplement
kVA 1 10 15 3 %Z 1.2 1.3 75 1.11 150 1.07 225 1.12 300 1.11 333 1.9 500 1.24 500 2.1 These represent actual transformer installations. Suggested X/R Ratio for Calculation 1.1 1.1 1.5 1.5 1.5 1.5 4.7 1.5 5.5 nameplate ratings taken from field
UL listed transformers 25 KVA or greater have a 10% impedance toler ance. Short-circuit amps shown in Table 1 reflect 10% condition. Transformers constructed to ANSI standards have a 7.5% impedance tolerance (two-winding construction). For example, a 10% increase in system voltage will result in a 10% greater available short-circuit currents than as shown in Table 1.
Note: UL Listed transformers 25kVA and greater have a 10% tolerance on their impedance nameplate.
197
Nonmagnetic 600V 5kV 389 617 982 1559 1555 2430 2418 3826 3789 4811 4745 6044 5926 7493 7307 9317 9034 11424 10878 13923 13048 16673 15351 18594 17121 20868 18975 22737 20526 24297 21786 26706 23277 28033 25204 29735 26453 31491 28083 237 376 599 952 1482 2350 2961 3730 4678 5838 7301 9110 11174 12862 14923 16813 18506 21391 23451 25976 28779 951 1479 2342 2945 3702 4632 5766 7153 8851 10749 12343 14183 15858 17321 19503 21718 23702 26109
15kV 2407 3753 4679 5809 7109 8590 10319 12360 14347 15866 17409 18672 19731 21330 22097 23408 24887 1476 2333 2929 3673 4580 5646 6986 8627 10387 11847 13492 14955 16234 18315 19635 21437 23482
15kV 2415 3779 4726 5828 7189 8708 10500 12613 14813 16466 18319 19821 21042 23126 24897 26933 29320 1478 2339 2941 3693 4618 5717 7109 8751 10642 12115 13973 15541 16921 19314 21349 23750 26608
Nonmagnetic 600V 5kV 389 617 982 1560 1558 2433 2428 3838 3823 4833 4803 6087 6023 7579 7507 9473 9373 11703 11529 14410 14119 17483 17020 19779 19352 22525 21938 24904 24126 26916 26044 30096 28712 32154 31258 34605 33315 37197 35749 237 376 599 952 1482 2353 2966 3740 4699 5876 7373 9243 11409 13236 15495 17635 19588 23018 25708 29036 32938 952 1481 2350 2959 3725 4682 5852 7329 9164 11277 13106 15300 17352 19244 22381 25244 28262 31920
15kV 2421 3798 4762 5958 7364 9053 11053 13462 16013 18001 20163 21982 23518 25916 27766 29735 31959 1479 2344 2949 3709 4646 5771 7202 8977 10969 12661 14659 16501 18154 20978 23295 25976 29135
Note: These values are equal to one over the impedance per foot and based upon resistance and reactance values found in IEEE Std 241-1990 (Gray Book), IEEE Recommended Practice for Electric Power Systems in Commerical Buildings & IEEE Std 242-1986 (Buff Book), IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems. Where resistance and reac tance values differ or are not available, the Buff Book values have been used. The values for reactance in determining the C Value at 5 KV & 15 KV are from the Gray Book only (Values for 14-10 AWG at 5 kV and 14-8 AWG at 15 kV are not available and values for 3 AWG have been approximated).
198
Look under the column applying to the type of current and power factor for the figure nearest, but not above your result you have the size of wire needed.
Example Copper in 180 feet of steel conduit3 phase, 40 amp Ioad at 80% power factorVolt loss from local code equals 5.5 volts. Multiply feet by amperes by 1 180 x 40 x 1 = 7200. #/phase 1 Divide permissible volt loss multiplied by 1,000,000 by this number: 5.5 x 1,000,000 = 764. 7200
Select number from Table, three-phase at 80% power factor, that is nearest but not greater than 764. This number is 745 which indicates the size of wire needed: 6 AWG.
Line-to-Neutral
For line to neutral voltage drop on a 3 phase system, divide the three phase value by 1.73. For line to neutral voltage drop on a single phase system, divide single phase value by 2.
(90C Wire) .96 .91 .87 .82 .76 .71 .58 .41
Open Wiring
The volt loss for open wiring installations depends on the separation between conductors. The volt loss is approximately equal to that for conductors in nonmagnetic conduit. 310.15 offers a method to calculate conductor ampacity.
199
60%
Steel Conduit
NonMagnetic Conduit (Lead Covered Cables or Installation in Fibre or Other NonMagnetic Conduit, Etc.)
14 12 10 8 6 4 3 2 1 0 00 000 0000 250 300 350 400 500 600 750 1000 14 12 10 8 6 4 3 2 1 0 00 000 0000 250 300 350 400 500 600 750 1000
20* 25* 30 40 55 70 85 95 110 125 145 165 195 215 240 260 280 320 335 400 455 20* 25* 30 40 55 70 85 95 110 125 145 165 195 215 240 260 280 320 335 400 455
6140 3860 2420 1528 982 616 490 388 308 244 193 153 122 103 86 73 64 52 43 34 26 6140 3464 2420 1528 982 616 470 388 308 244 193 153 122 103 86 73 64 52 43 34 26
5369 3464 2078 1350 848 536 433 346 277 207 173 136 109 93 77 67 60 50 43 36 31 5369 3464 2078 1350 848 536 433 329 259 207 173 133 107 90 76 65 57 46 39 32 25
4887 3169 1918 1264 812 528 434 354 292 228 196 162 136 123 108 98 91 81 75 68 62 4876 3158 1908 1255 802 519 425 330 268 220 188 151 127 112 99 89 81 71 65 58 51
4371 2841 1728 1148 745 491 407 336 280 223 194 163 140 128 115 106 99 90 84 78 72 4355 2827 1714 1134 731 479 395 310 255 212 183 150 128 114 103 94 87 77 72 65 59
3848 2508 1532 1026 673 450 376 312 264 213 188 160 139 129 117 109 103 94 89 84 78 3830 2491 1516 1010 657 435 361 286 238 199 174 145 125 113 104 95 89 80 76 70 63
3322 2172 1334 900 597 405 341 286 245 200 178 154 136 128 117 109 104 96 92 88 82 3301 2153 1316 882 579 388 324 259 219 185 163 138 121 110 102 94 89 82 77 72 66
6200 4000 2400 1560 980 620 500 400 320 240 200 158 126 108 90 78 70 58 50 42 36 6200 4000 2400 1560 980 620 500 380 300 240 200 154 124 104 88 76 66 54 46 38 30
5643 3659 2214 1460 937 610 501 409 337 263 227 187 157 142 125 113 105 94 86 79 72 5630 3647 2203 1449 926 599 490 381 310 254 217 175 147 129 114 103 94 82 75 67 59
5047 3281 1995 1326 860 568 470 388 324 258 224 188 162 148 133 122 114 104 97 91 84 5029 3264 1980 1310 845 553 456 358 295 244 211 173 148 132 119 108 100 90 83 76 68
4444 2897 1769 1184 777 519 434 361 305 246 217 184 161 149 135 126 118 109 103 97 90 4422 2877 1751 1166 758 502 417 330 275 230 201 167 145 131 120 110 103 93 87 80 73
3836 2508 1540 1040 690 468 394 331 283 232 206 178 157 148 135 126 120 111 106 102 95 3812 2486 1520 1019 669 448 375 300 253 214 188 159 140 128 118 109 103 94 90 83 77
* The overcurrent protection for conductor types marked with an (*) shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper; or 15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied. Figures are L-L for both single-phase and three-phase. Three-phase figures are average for the three-phase.
200
60%
Steel Conduit
NonMagnetic Conduit (Lead Covered Cables or Installation in Fibre or Other NonMagnetic Conduit, Etc.)
12 10 8 6 4 3 2 1 0 00 000 0000 250 300 350 400 500 600 750 1000 12 10 8 6 4 3 2 1 0 00 000 0000 250 300 350 400 500 600 750 1000
20* 25 30 40 55 65 75 85 100 115 130 150 170 190 210 225 260 285 320 375 20* 25 30 40 55 65 75 85 100 115 130 150 170 190 210 225 260 285 320 375
6360 4000 2520 1616 1016 796 638 506 402 318 259 200 169 141 121 106 85 71 56 42 6360 4000 2520 1616 1016 796 638 506 402 318 252 200 169 141 121 106 85 71 56 42
5542 3464 2251 1402 883 692 554 433 346 277 225 173 148 124 109 95 77 65 53 43 5542 3464 2251 1402 883 692 554 433 346 277 225 173 147 122 105 93 74 62 50 39
5039 3165 2075 1310 840 668 541 432 353 290 241 194 173 150 135 122 106 95 84 73 5029 3155 2065 1301 831 659 532 424 344 281 234 186 163 141 125 114 96 85 73 63
4504 2836 1868 1188 769 615 502 405 334 277 234 191 173 152 139 127 112 102 92 82 4490 2823 1855 1175 756 603 490 394 322 266 223 181 160 140 125 116 100 90 79 70
3963 2502 1656 1061 692 557 458 373 310 260 221 184 168 150 138 127 113 105 96 87 3946 2486 1640 1045 677 543 443 360 296 247 209 171 153 136 123 114 100 91 82 73
3419 2165 1441 930 613 497 411 338 284 241 207 174 161 145 134 125 113 106 98 89 3400 2147 1423 912 596 480 394 323 268 225 193 160 145 130 118 111 98 91 82 75
6400 4000 2600 1620 1020 800 640 500 400 320 260 200 172 144 126 110 90 76 62 50 6400 4000 2600 1620 1020 800 640 500 400 320 260 200 170 142 122 108 86 72 58 46
5819 3654 2396 1513 970 771 625 499 407 335 279 224 200 174 156 141 122 110 97 85 5807 3643 2385 1502 959 760 615 490 398 325 270 215 188 163 144 132 111 98 85 73
5201 3275 2158 1372 888 710 580 468 386 320 270 221 200 176 160 146 129 118 107 95 5184 3260 2142 1357 873 696 566 455 372 307 258 209 185 162 145 134 115 104 92 81
4577 2889 1912 1225 799 644 529 431 358 301 256 212 194 173 159 146 131 121 111 100 4557 2871 1894 1206 782 627 512 415 342 285 241 198 177 157 142 132 115 106 94 85
3948 2500 1663 1074 708 574 475 391 328 278 239 201 186 168 155 144 130 122 114 103 3926 2480 1643 1053 668 555 456 373 310 260 223 185 167 150 137 128 114 105 95 86
* The overcurrent protection for conductor types marked with an (*) shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper; or 15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied. Figures are L-L for both single-phase and three-phase. Three-phase figures are average for the three-phase.
201
Glossary
Common Electrical Terminology
Ohm
The unit of measure for electric resistance. An ohm is the amount of resistance that will allow one amp to flow under a pressure of one volt.
Semiconductor Fuses
Fuses used to protect solid-state devices. See High Speed Fuses.
Short-Circuit
Can be classified as an overcurrent which exceeds the normal full load current of a circuit by a factor many times (tens, hundreds or thousands greater). Also characteristic of this type of overcurrent is that it leaves the normal current carrying path of the circuit it takes a short cut around the load and back to the source.
Ohms Law
The relationship between voltage, current, and resistance, expressed by the equation E = IR, where E is the voltage in volts, I is the current in amps, and R is the resistance in ohms.
Overcurrent
A condition which exists on an electrical circuit when the normal load current is exceeded. Overcurrents take on two separate characteristics overloads and shortcircuits.
Single-Phasing
That condition which occurs when one phase of a three-phase system opens, either in a low voltage (secondary) or high voltage (primary) distribution system. Primary or secondary single-phasing can be caused by any number of events. This condition results in unbalanced currents in polyphase motors and unless protective measures are taken, causes overheating and failure.
Overload
Can be classified as an overcurrent which exceeds the normal full load current of a circuit. Also characteristic of this type of overcurrent is that it does not leave the normal current carrying path of the circuit that is, it flows from the source, through the conductors, through the load, back through the conductors, to the source again.
Threshold Current
The symmetrical RMS available current at the threshold of the current-limiting range, where the fuse becomes current-limiting when tested to the industry standard. This value can be read off of a peak let-through chart where the fuse curve intersects the A - B line. A threshold ratio is the relationship of the threshold current to the fuses continuous current rating.
Time-Delay Fuse
A fuse with a built-in delay that allows temporary and harmless inrush currents to pass without opening, but is so designed to open on sustained overloads and short-circuits.
Resistive Load
An electrical load which is characteristic of not having any significant inrush current. When a resistive load is energized, the current rises instantly to its steady-state value, without first rising to a higher value.
Voltage Rating
The maximum open circuit voltage in which a fuse can be used, yet safely interrupt an overcurrent. Exceeding the voltage rating of a fuse impairs its ability to clear an overload or short-circuit safely.
RMS Current
The RMS (root-mean-square) value of any periodic current is equal to the value of the direct current which, flowing through a resistance, produces the same heating effect in the resistance as the periodic current does.
Withstand Rating
The maximum current that an unprotected electrical component can sustain for a specified period of time without the occurrence of extensive damage.
Electrical Formulas
To Find Single-Phase Two-Phase Three-Phase Direct Current
Amperes when kVA is known Amperes when horsepower is known Amperes when kilowatts are known Kilowatts Kilovolt-Amperes Horsepower Watts
kVA 1000 kVA 1000 E2 E 1.73 HP 746 HP 746 E 2 % eff. pf E 1.73 % eff. pf kW 1000 kW 1000 E 2 pf E 1.73 pf I E 2 pf I E 1.73 pf 1000 1000 IE2 I E 1.73 1000 1000 I E 2 % eff. pf I E 1.73 % eff. pf 746 746 I E 2 pf I E 1.73 pf Energy Efficiency = Load Horsepower 746 Load Input kVA 1000 Power Factor = pf = Power Consumed = W or kW = cos Apparent Power VA kVA
kW = Kilowatts pf = Power Factor kVA = Kilovolt-Amperes
Not Applicable HP 746 E % eff. kW 1000 E IE 1000 Not Applicable I E % eff. 746 EI
I = Amperes HP = Horsepower
216