Important Note: The current rating shown in the table by considering maximum possible conductor temperature and ambient conditions
for facilitating the heat dissipation. The current rating values depend on various conditions like type of circuits(1-phase/3-phase), method
of laying, ambient temperature, grouping of cables which have to be considered before cable selection and installation process.
The current rating values given in the table are based on following parameters:
1. Maximum conductor Temperature : 70°C
2. Ambient Temperature in air : 40°C
3. Thermal Resistivity of PVC : 650°C cm/W
The current rating given in the above table is based on above considerations but in actual practice the conditions may be different. First
determine the current rating on the bunching factor to form circuits 1-phase/3-phase. Then determine the current rating at different
condition. The following derating factors are to be multiplied with values given in the above table.
If the number of circuits exceed 4, they are installed in a horozantal plane. In all other cases, unless a more precise evaluation of current
rating has been made based on experimental work or calculated data the following factors are applicable:(In case of single core cables,
not applicable to 3-phase).