Mn-Ut4500a 1
Mn-Ut4500a 1
Upconverters
Installation and Operation Manual
IMPORTANT NOTE: The information contained in this document supersedes all previously
published information regarding this product. Product specifications are subject to change
without prior notice.
Copyright © Comtech EF Data, 2013. All rights reserved. Printed in the USA.
Comtech EF Data, 2114 West 7th Street, Tempe, Arizona 85281 USA, 480.333.2200, FAX: 480.333.2161
This page is intentionally blank.
TABLE OF CONTENTS
TABLES .................................................................................................................................... X
FIGURES ................................................................................................................................... X
iii
UT-4500-A Series Upconverters Revision 1
Table of Contents MN-UT4500A
iv
UT-4500-A Series Upconverters Revision 1
Table of Contents MN-UT4500A
4.2 Getting Started: Preparing for the Firmware Download ...................................................... 4–2
v
UT-4500-A Series Upconverters Revision 1
Table of Contents MN-UT4500A
vi
UT-4500-A Series Upconverters Revision 1
Table of Contents MN-UT4500A
vii
UT-4500-A Series Upconverters Revision 1
Table of Contents MN-UT4500A
viii
UT-4500-A Series Upconverters Revision 1
Table of Contents MN-UT4500A
ix
UT-4500-A Series Upconverters Revision 1
Table of Contents MN-UT4500A
TABLES
Table 3-1. UT-4500-A Rear Panel External Connections .......................................................................... 3–2
Table 3-2. Ethernet M&C Interface Connector Pinout ............................................................................. 3–4
Table 3-3. P1 | RELAY Summary Fault Connector Pinout ........................................................................ 3–4
Table 3-4. J1 – 2-Wire EIA-485 Pinout ...................................................................................................... 3–5
Table 3-5. J1 – 4-Wire EIA-485 Pinout ...................................................................................................... 3–5
Table 3-6. J1 – EIA-232C Pinout ................................................................................................................ 3–5
Table 3-7. J3 | HSB Interface Connector Pinout ....................................................................................... 3–7
Table 3-8. DT-4500-A and UT-4500-A Available Switch Module Assemblies ........................................... 3–8
FIGURES
Figure 1-1. UT-4500-A Series Upconverters (UT-4505-A shown) ............................................................. 1–1
Figure 1-2. UT-4500-A Series Upconverter Physical Configuration .......................................................... 1–2
Figure 1-3. Typical Functional Block Diagram (UT-4512-A shown) ........................................................... 1–4
Figure 1-4. UT-4500-A Series Upconverter Dimensional Envelope .......................................................... 1–6
Figure 1-5. UT-4500-A Series Upconverter Front Panel............................................................................ 1–7
Figure 1-6. UT-4500-A Series Upconverter Rear Panel ............................................................................. 1–7
Figure 2-1. Unpacking and Inspecting the Shipment ................................................................................ 2–1
Figure 2-2. Installing into a Rack Enclosure .............................................................................................. 2–3
Figure 2-3. Installing the Optional Rear-Mounting Support Brackets Kit ................................................ 2–4
Figure 2-4. Optional Bearingless Rack Slide Installation (FP/SL000X)....................................................... 2–6
Figure 3-1. UT-4500-A Rear Panel (UT-4505-A with Receive Switch Module [RSM-XX] Shown).............. 3–1
Figure 3-2. IOM, RSM, and TSM Switch Modules ..................................................................................... 3–6
Figure 3-3. UT-4500-A Cabling Schematic (UT-4505-A with Receive Switch Module [RSM-XX] Shown) . 3–9
Figure 3-4. Standalone (Non-Redundant) Upconverter Configuration .................................................. 3–10
Figure 3-5. Standalone (Non-Redundant) Upconverter Configuration with Transmit Switch Module
(TSM-XX) ......................................................................................................................................... 3–10
Figure 5-1. UT-4500-A Front and Rear Panel Views.................................................................................. 5–1
Figure 6-1. Home | Home page ................................................................................................................ 6–9
Figure 6-2. Home | Contact page............................................................................................................ 6–10
Figure 6-3. Home | Support page ........................................................................................................... 6–11
Figure 6-4. Admin | Access page ............................................................................................................ 6–12
Figure 6-5. Admin | SNMP page ............................................................................................................. 6–14
Figure 6-6. Config | Converter page ....................................................................................................... 6–15
Figure 6-7. Config | Ref page .................................................................................................................. 6–17
Figure 6-8. Config | Pre-selects page ...................................................................................................... 6–18
Figure 6-9. Config | Utility page .............................................................................................................. 6–19
Figure 6-10. Config | Redundancy page.................................................................................................. 6–21
Figure 6-11. Status | Summary page ...................................................................................................... 6–22
Figure 6-12. Status | Faults page ............................................................................................................ 6–23
Figure B-1. 1:1 Redundant Configuration –Single Source IF Input with IOM-XX and TSM-XX Installed ... B–4
Figure B-2. 1:1 Redundant Configuration Diagram – Single Source RF Input with IOM-XX and TSM-XX
Installed ............................................................................................................................................ B–4
x
UT-4500-A Series Upconverters Revision 1
Table of Contents MN-UT4500A
Figure B-3. 1:1 Redundant Configuration Diagram – Single Source RF Input with IOM-XX and TSEQM-XX
Installed ............................................................................................................................................ B–4
Figure B-4. TSEQM Connection Locations................................................................................................. B–5
Figure B-5. 1:1 Redundant Configuration - Dual Source IF Input.............................................................. B–5
Figure B-6. 1:1 Redundant Configuration Diagram – Dual Source IF Input with IOM-XX and TSM-XX
Installed ............................................................................................................................................ B–5
Figure B-7. 1:N Redundant Configuration with IOM-XX and TSM-XX Installed ........................................ B–6
Figure B-8. 1:N Redundant Configuration Diagram with IOM-XX and TSM-XX Installed.......................... B–7
Figure B-9. Front Panel Displays ............................................................................................................... B–8
Figure B-10. System in Auto Redundant Mode......................................................................................... B–9
Figure B-11. Backup of Converter #1 ...................................................................................................... B–10
Figure B-12. Converter #1 in MANUAL, Others in AUTO ........................................................................ B–11
Figure B-13. Forced Backup of Converter #1 .......................................................................................... B–12
Figure B-14. Config | Redundancy page ................................................................................................. B–13
Figure C-1. Upconverter Signal and Interconnecting Cable Diagram (with Transmit Switch Module [TSM])
.......................................................................................................................................................... C–1
xi
UT-4500-A Series Upconverters Revision 1
Table of Contents MN-UT4500A
xii
PREFACE
Disclaimer
Comtech EF Data has reviewed this manual thoroughly to provide an easy-to-use guide to your
equipment. All statements, technical information, and recommendations in this manual and in
any guides or related documents are believed reliable, but the accuracy and completeness
thereof are not guaranteed or warranted, and they are not intended to be, nor should they be
understood to be, representations or warranties concerning the products described. Further,
Comtech EF Data reserves the right to make changes in the specifications of the products
described in this manual at any time without notice and without obligation to notify any person
of such changes.
If you have any questions regarding the equipment or the information in this manual, please
contact the Comtech EF Data Customer Support Department.
Comtech EF Data acknowledges that all trademarks are the property of the trademark owners.
xiii
UT-4500-A Series Upconverters Revision 1
Preface MN-UT4500A
A WARNING gives information about a possible hazard that MAY CAUSE DEATH
or SERIOUS INJURY.
A CAUTION gives information about a possible hazard that MAY CAUSE INJURY
or PROPERTY DAMAGE.
Metric Conversion
Metric conversion information is provided on the inside back cover of this manual as a means to
assist the operator in cross-referencing non-Metric to Metric conversions.
xiv
UT-4500-A Series Upconverters Revision 1
Preface MN-UT4500A
Electrical Installation
CONNECT THE UNIT TO A POWER SYSTEM THAT HAS SEPARATE GROUND, LINE AND
NEUTRAL CONDUCTORS. DO NOT CONNECT THE UNIT WITHOUT A DIRECT
CONNECTION TO GROUND.
Operating Environment
DO NOT OPERATE THE UNIT IN ANY OF THESE EXTREME OPERATING CONDITIONS:
• EXCESSIVE DUST.
• FLAMMABLE GASES.
xv
UT-4500-A Series Upconverters Revision 1
Preface MN-UT4500A
• Federal Communications Commission Federal Code of Regulation FCC Part 15, Subpart B.
TO ENSURE THAT THE UNIT COMPLIES WITH THESE STANDARDS, OBEY THESE
INSTRUCTIONS:
• Use coaxial cable that is of good quality for connections to the L-Band Type ‘N’ Rx (receive)
female connector.
• Use Type 'D' connectors that have back-shells with continuous metallic shielding.
Type ‘D’ cabling must have a continuous outer shield (either foil or braid, or both). The
shield must be bonded to the back-shell.
Symbol Description
<HAR> Type of power cord required for use in the European Community.
CAUTION: Double-pole/Neutral Fusing
! ACHTUNG: Zweipolige bzw. Neutralleiter-Sicherung
xvi
UT-4500-A Series Upconverters Revision 1
Preface MN-UT4500A
International Symbols
Symbol Definition Symbol Definition
Alternating Current Protective Earth
Fuse Chassis Ground
For additional symbols, refer to Warnings, Cautions and Notes listed earlier in this
Preface.
CE Mark
Comtech EF Data declares that the unit meets the necessary requirements for the CE Mark.
xvii
UT-4500-A Series Upconverters Revision 1
Preface MN-UT4500A
Warranty Policy
Comtech EF Data products are warranted against defects in material and workmanship for
a specific period from the date of shipment, and this period varies by product. In most
cases, the warranty period is two years. During the warranty period, Comtech EF Data will,
at its option, repair or replace products that prove to be defective. Repairs are warranted
for the remainder of the original warranty or a 90 day extended warranty, whichever is
longer. Contact Comtech EF Data for the warranty period specific to the product
purchased.
For equipment under warranty, the owner is responsible for freight to Comtech EF Data
and all related customs, taxes, tariffs, insurance, etc. Comtech EF Data is responsible for
the freight charges only for return of the equipment from the factory to the owner.
Comtech EF Data will return the equipment by the same method (i.e., Air, Express,
Surface) as the equipment was sent to Comtech EF Data.
All equipment returned for warranty repair must have a valid RMA number issued prior to
return and be marked clearly on the return packaging. Comtech EF Data strongly
recommends all equipment be returned in its original packaging.
Comtech EF Data Corporation’s obligations under this warranty are limited to repair or
replacement of failed parts, and the return shipment to the buyer of the repaired or
replaced parts.
Limitations of Warranty
The warranty does not apply to any part of a product that has been installed, altered,
repaired, or misused in any way that, in the opinion of Comtech EF Data Corporation,
would affect the reliability or detracts from the performance of any part of the product, or
is damaged as the result of use in a way or with equipment that had not been previously
approved by Comtech EF Data Corporation.
The warranty does not apply to any product or parts thereof where the serial number or
the serial number of any of its parts has been altered, defaced, or removed.
The warranty does not cover damage or loss incurred in transportation of the product.
The warranty does not cover replacement or repair necessitated by loss or damage from
any cause beyond the control of Comtech EF Data Corporation, such as lightning or other
natural and weather related events or wartime environments.
The warranty does not cover any labor involved in the removal and or reinstallation of
warranted equipment or parts on site, or any labor required to diagnose the necessity for
repair or replacement.
xviii
UT-4500-A Series Upconverters Revision 1
Preface MN-UT4500A
The warranty excludes any responsibility by Comtech EF Data Corporation for incidental
or consequential damages arising from the use of the equipment or products, or for any
inability to use them either separate from or in combination with any other equipment or
products.
A fixed charge established for each product will be imposed for all equipment returned for
warranty repair where Comtech EF Data Corporation cannot identify the cause of the
reported failure.
Exclusive Remedies
The remedies provided herein are the buyer’s sole and exclusive remedies. Comtech EF
Data shall not be liable for any direct, indirect, special, incidental, or consequential
damages, whether based on contract, tort, or any other legal theory.
xix
UT-4500-A Series Upconverters Revision 1
Preface MN-UT4500A
Getting Help
Review the Warranty Policy before contacting Comtech EF Data Technical Support or
Customer Service.
Contact Comtech EF Data Customer & Technical Support during normal business hours (Monday
through Friday, 8 A.M. to 5 P.M Mountain Standard Time (MST)):
For: Contact:
xx
UT-4500-A Series Upconverters Revision 1
Preface MN-UT4500A
• On the Comtech EF Data Home page: From the SUPPORT column at the bottom
of the page, select the RMA Request hyperlink;
OR
OR
Alternately:
3 Pack the product in its original shipping carton and protective packaging.
4 Ship the product back to Comtech EF Data. Shipping charges should be prepaid.
xxi
UT-4500-A Series Upconverters Revision 1
Preface MN-UT4500A
Notes:
xxii
Chapter 1. INTRODUCTION
1.1 Overview
Comtech EF Data’s UT-4500-A Series Upconverters (Figure 1-1) are designed for the
transmission of SCPC, DAMA and TDMA signals in communication systems or satellite uplink
data systems. The Upconverters can also be used in communications system applications with
full transponder HDTV and analog TV.
1–1
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
• Transmit Switch Module (not shown – installs into rear chassis slot)
1–2
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
1.2.1 Applications
The upconverter operates over the RF frequency range with a typical gain of 35 dB. The RF
output level is +10 dBm at 1 dB compression allowing the capability for longer cable runs to
compensate for splitting networks without adding options such as external line amplifiers.
The phase noise performance exceeds the Intelsat phase noise mask for IBS and IDR services by
more than 9 dB. This allows high capacity earth stations to add more demodulators and still
meet transmission standards. The close-in phase noise is also very low. This makes the
upconverter ideal for low bit rate digital circuits such as used in DAMA hub earth stations.
A detachable Input/Output Module (IOM) can be mounted in the rear of the upconverter chassis
for switching the RF output for single thread operations, or for testing the output of the unit.
The connectors for the IOM are located on the rear panel.
In applications where upconverters are "Daisy Chained" together to provide distributed online
protection switching to a backup upconverter, the IOM is replaced with a detachable Transmit
Switch Module (TSM). The TSM contains RF and IF transfer switches. Type N connectors are
provided for the RF loop, and 50 or 75 ohms BNC connectors are provided for the IF loop.
The "Daisy Chain" configuration is designed to chain the IF input and RF output of up to twelve
(12) online upconverters together through TSMs terminating in a backup upconverter. When a
fault occurs in an online upconverter, the TSM in the upconverter with the fault is commanded
to switch to the backup upconverter.
The backup upconverter performs the fault detection, self-reconfiguration and the logical
switching functions. If the backup upconverter has a fault, it will not attempt to perform the
protection-switching task. If the backup upconverter does not have a fault, it will assume the
frequency and attenuation of the faulted online upconverter, and compensate for the chain
losses.
The backup upconverter in the "Daisy Chain" communicates with the online upconverters
through a high speed (data interface) bus (HSB). When faults are detected, the backup
upconverter re-configures itself to replace the online upconverter with the fault. The backup
upconverter also uses the HSB to monitor configuration changes made to the online
upconverters by either remote control or front panel command inputs.
Changes in frequency, attenuation or polarity are entered into the backup table as they are
made, as well as information from new online units. The HSB does not interfere with the remote
control communications link for access to any of the converters in the "Daisy Chain".
1–3
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
The intermediate IF is 1220 MHz, which is mixed in the second stage mixer with 12780 to 13280
MHz synthesizer signal to provide an RF output frequency of 14000 to 1451X MHz in 125 KHz
fine tuning steps. The synthesizer is also locked to the 5/10 MHz reference oscillator. The second
mixer is located in the upconverter Signal Path Module, and the synthesizer consists of the
Coarse/Fine Step Module and Sum Loop Module.
Figure 1-3 depicts the operational schematic for a typical UT-4500-A Series Upconverter in single
thread (standalone) applications. For more information about the UT-4500-A’s use in redundant
applications, refer to Appendix B. REDUNDANT SYSTEM OPERATION.
Remote control inputs are provided through the EIA-232C or EIA-485 communications port on
the rear of the panel, or by local operator inputs through the keypad on the front panel.
1–4
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
Local operator input commands and the status of the upconverter are displayed on the front
panel Vacuum Fluorescent Display (VFD) on the front panel.
An upconverter fault is indicated by the LED indicator on the front panel. Specific fault
conditions are displayed on the VFD through local keypad input commands.
For: See:
• Rack installation and mounting Chapter 2. INSTALLATION
instructions
1–5
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
1–6
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
Figure 1-5 shows the typical front panel of the UT-4500-A Series Upconverters. This example
depicts a UT-4505-A Upconverter. All operator controls, indicators and displays for local and
remote operation are located on the front panel of the UT-4500-A. The front panel features
(from left):
• Two Test Point Sample Ports – The test point connections are used for monitoring the
RF input and the IF output. An SMA connector provides the RF output, and a BNC
connector provides the IF input. There is also an optional RF LO monitor available.
• Six Light-Emitting Diode (LED) Indicators – The LEDs indicate, in a summary fashion, the
status of the unit.
• Vacuum Fluorescent Display (VFD) – The VFD is an active display showing two lines of
24 characters each. Each configuration function, or operating mode, is shown on the
display when the operator enters a command using the keypad.
• Six-button Keypad – The keypad comprises six individual keyswitches. They have a
positive ‘click’ action, which provides tactile feedback.
• Prime Power Switch – The on/off prime power switch is located on the rear of the
chassis next to the prime power input connector. The power switch contains a filter and
1–7
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
dual fuse. The dual fuse is rated for 2 Amps. The UT-4500-A is provided with a six-foot
AC power cord.
• Exhaust Fan – The internally mounted exhaust fan vents through the rear panel for
chassis cooling.
1–8
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
Characteristic Specification
Group Delay Linear Group Delay 0.03 ns/MHz
Parabolic Delay 0.01 ns/MHz2
Group Delay Ripple 1.0 ns Peak-to-Peak
Phase Noise Parameter Limit (dBc/Hz) Typical (dBc/Hz)
100 Hz -80 -83
1 kHz -89 -92
10 kHz -95 -97
100 kHz -105 -109
1 MHz -120 -124
Remote Control (Rear Panel) Comm Port EIA-485 or EIA-232
1–9
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
1–10
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
Characteristic Specification
Remote Control (Rear Panel) Comm Port EIA-485 or EIA-232
LED Indicators Power On Green LED
(Front Panel) Transmit Yellow LED
Remote Yellow LED
On Line Yellow LED
Fault Red LED
Stored Fault Red LED
Test Points RF Sample Type ‘SMA’ Connector, -20 dBc Nominal
(Front Panel) IF Sample Type ‘BNC’ Connector, -20 dBc Nominal
Optional L.O. Sample
Power Voltage 90-250 VAC, Autoranging
Frequency 47-63 Hz
Dissipation 60 Watts
Power Option -48 VDC
Environmental Temperature 0-50°C (32-122° F)
Altitude 10,000 Feet MSL
Humidity 0-95% Relative
Physical Width 19 Inches (48.26 cm)
Height 1RU 1.75 Inches (4.44 cm)
Depth 22 Inches (55.88 cm)
Weight 15 Pounds (7.00 kg)
MTBF 49,740 hrs. (calculated)
>100,000 hrs. (field experience)
Summary Alarm Relay Closure Form C
1–11
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
1–12
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
Characteristic Specification
Remote Control (Rear Panel) Comm Port EIA-485 or EIA-232
LED Indicators Power On Green LED
(Front Panel) TRANSMIT Yellow LED
Remote Yellow LED
On Line Yellow LED
Fault Red LED
Stored Fault Red LED
Test Points RF Sample Type ‘SMA’ Connector, -20 dBc Nominal
(Front Panel) IF Sample Type ‘BNC’ Connector, -20 dBc Nominal
Optional L.O. Sample
Power Voltage 90-250 VAC Autoranging
Frequency 47-63 Hz
Dissipation 60 Watts
Power Option -48 VDC
Environmental Temperature 0-50°C (32-122° F)
Altitude 10,000 Feet MSL
Humidity 0-95% Relative
Physical Width 19 Inches (48.26 cm)
Height 1RU 1.75 Inches (4.44 cm)
Depth 22 Inches (55.88 cm)
Weight 15 Pounds (7.00 kg)
MTBF 49,740 hrs. (calculated)
>100,000 hrs. (field experience)
Summary Alarm Relay Closure Form C
1–13
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
1–14
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
Characteristic Specification
Remote Control (Rear Panel) Comm Port EIA-485 or EIA-232
LED Indicators Power On Green LED
(Front Panel) Transmit Yellow LED
Remote Yellow LED
On Line Yellow LED
Fault Red LED
Stored Fault Red LED
Test Points RF Sample Type ‘SMA’ Connector, -20 dBc Nominal
(Front Panel) IF Sample Type ‘BNC’ Connector, -20 dBc Nominal
Power Voltage 90-250 VAC Autoranging
Frequency 47-63 Hz
Dissipation 60 Watts
Environmental Temperature 0-50°C (32-122° F)
Altitude 10,000 Feet MSL
Humidity 0-95% Relative
Physical Width 19 Inches (48.26 cm)
Height 1RU 1.75 Inches (4.44 cm)
Depth 22 Inches (55.88 cm)
Weight 15 Pounds (7.00 kg)
Options -1 RF/IF Connector Module
-2 Transmit Switch Module
Summary Alarm Relay Closure Form C
1–15
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
1–16
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
Characteristic Specification
Test Points RF Sample Type ‘SMA’ Connector, -20 dBc Nominal
(Front Panel) IF Sample Type ‘BNC’ Connector, -20 dBc Nominal
Power Voltage 90-250 VAC Autoranging
Frequency 47-63 Hz
Dissipation 60 Watts
Environmental Temperature 0-50°C (32-122° F)
Altitude 10,000 Feet MSL
Humidity 0-95% Relative
Physical Width 19 Inches (48.26 cm)
Height 1RU 1.75 Inches (4.44 cm)
Depth 22 Inches (55.88 cm)
Weight 15 Pounds (7.00 kg)
Options -1 IO Module
-2 RF/IF Switch
Summary Alarm Relay Closure Form C
1–17
UT-4500A Series Upconverters Revision 1
Introduction MN-UT4500A
Notes:
1–18
Chapter 2. INSTALLATION
2–1
UT-4500-A Series Upconverters Revision 1
Installation MN-UT4500A
Step Task
o Air temperature inside the rack enclosure should never exceed 50°C
(122°F).
2–2
UT-4500-A Series Upconverters Revision 1
Installation MN-UT4500A
Feature Description
1 Custom Rack Enclosure
2 UT-4500-A Series Upconverter
3 Standard Rack Shelving
Rack Enclosure Threaded Front Mounting
4
Rail (typical)
5 Unit Front Panel
6 User-supplied Screws
Mount the UT-4500-A in its assigned position in the rack enclosure. Use, as required:
• User-supplied screws to secure the front panel to the rack enclosure threaded front
mounting rails;
• Comtech EF Data’s provided FP/SL0006 (26”) or FP/SL0008 (24”) Bearingless Rack Slide
Set (Figure 2-4).
2–3
UT-4500-A Series Upconverters Revision 1
Installation MN-UT4500A
Feature Description
1 Back of Unit
2 Rack Enclosure Threaded Rear Mounting Rail (typical)
Kit / Quantity
Item Part Number Description
KT/6228-2 KT/6228-3
1 2 2 HW/10-32SHLDR Shoulder Screw, #10
2 4 4 HW/10-32FLT Flat Washer, #10
3 2 2 HW/10-32SPLIT Lock Washer, #10
4 2 2 HW/10-32HEXNUT Hex Nut, #10
5 4 4 HW/10-32x1/2RK Bolt, #10, Rear Support Bracket
2 – FP/6138-2 Bracket, Rear Support – 4”
6
– 2 FP/6138-3 Bracket, Rear Support – 10”
Tools needed to install the KT/6228-2 (4”) or KT/6228-3 (10”) Bracket Kit (Figure 2-3):
2–4
UT-4500-A Series Upconverters Revision 1
Installation MN-UT4500A
Step Task
Use the #10 flat washers, #10 split washers, and #10 hex nuts to secure the #10
1 shoulder screws to the CDM-800 chassis through the rear right and left side mounting
slots.
Use the #10 rack bracket bolts to install the rear support brackets onto the rack
2
enclosure threaded rear mounting rails.
Mount the unit into the rack enclosure. Ensure that the shoulders of the #10 shoulder
3
screws properly engage into the rear support bracket slots.
2–5
UT-4500-A Series Upconverters Revision 1
Installation MN-UT4500A
Per Figure 2-4, install any of these optional bearingless rack slide sets as follows:
Step Procedure
Using the provided mounting hardware, install one slide onto each side of the UT-
1
4500-A chassis.
Using the provided mounting hardware, install the slide rail components into each
2
side of the rack cabinet.
Mount the unit into the equipment rack, ensuring that the slides properly engage
3
the cabinet-mounted slide rails.
Slide the converter into the rack cabinet until the front panel’s back surfaces
4
abut the rack cabinet’s front mounting rails.
Secure the converter to the rack cabinet front mounting rails using four user-
5
provided screws installed through the front panel mounting slots.
2–6
UT-4500-A Series Upconverters Revision 1
Installation MN-UT4500A
2–7
UT-4500-A Series Upconverters Revision 1
Installation MN-UT4500A
Notes:
2–8
Chapter 3. REAR PANEL
CONNECTORS
Table 3-1 summarizes these connectors, which provide all necessary external connections
between the upconverter and other equipment. Detailed information about each connector
follows.
Figure 3-1. UT-4500-A Rear Panel (UT-4505-A with Receive Switch Module [RSM-XX]
Shown)
3–1
UT-4500-A Series Upconverters Revision 1
Rear Panel Connectors MN-UT4500A
A standard, detachable, non-locking, 3-socket power cord (IEC-60320 style C13 plug) supplies
the Alternating Current (AC) power to the UT-4500-A.
AC Power Specifications
Input Power 75W maximum, less than 65W typical
Input Voltage 90-260VAC
Connector Type IEC-603320 Style C13/C14
Fuse Protection Use (2) T2.0A 20mm slow-blow fuses.
For continued operator safety, always replace the fuses with the correct type
and rating.
3–2
UT-4500-A Series Upconverters Revision 1
Rear Panel Connectors MN-UT4500A
DC Power Specifications
Input Power 75W maximum, less than 65W typical
Input Voltage 36 to 72 VDC
Connector Type 2-circuit Terminal Block
Fuse Protection Use (2) 3.15A 20mm slow-blow fuses.
For continued operator safety, always replace the fuses with the correct type
and rating.
3–3
UT-4500-A Series Upconverters Revision 1
Rear Panel Connectors MN-UT4500A
3–4
UT-4500-A Series Upconverters Revision 1
Rear Panel Connectors MN-UT4500A
Table 3-4. J1 – 2-Wire EIA-485 Pinout Table 3-5. J1 – 4-Wire EIA-485 Pinout
Pin # Description Pin # Description
1 GND; Ground 1 GND; Ground
2 2
3 3
4 +RX/TX; Signal 4 +TX; Signal
5 -RX/TX; Signal Complement 5 -TX; Signal Complement
6 6
7 7
8 +RX/TX; Signal 8 +RX; Signal
9 -RX/TX; Signal Complement 9 -RX; Signal Complement
Note: Pins 8 and 9 are the loop to the next
upconverter
Pin # Description
1
2 TD; Transmit Data
3 RD; Receive Data
4
5 GND; Ground
6
7
8
9
3–5
UT-4500-A Series Upconverters Revision 1
Rear Panel Connectors MN-UT4500A
3–6
UT-4500-A Series Upconverters Revision 1
Rear Panel Connectors MN-UT4500A
Note: This connection does not employ a “straight-through” cable assembly. Contact Comtech
EF Data for detailed wiring drawings when cabling between converters.
Pin # Description
1 Cntl_12
2 Cntl_10
3 Cntl_8
4 Cntl_6
5 Cntl_4
6 Cntl_2
7 Cntl_In
8 +14V Out
9 +14V In
10 Aux_3
11 Aux_1
12 -Rx/Tx
13 GND
14 Cntl_11
15 Cntl_9
16 Cntl_7
17 Cntl_5
18 Cntl_3
19 Cntl_1
20 +14V Out
21 +14V In
22 GND
23 Aux_2
24 GND
25 +Rx/Tx
3–7
UT-4500-A Series Upconverters Revision 1
Rear Panel Connectors MN-UT4500A
The tables that follow provide a quick reference to the available switch modules and their
switching type, operating band, connector type, etc. for the UT-4500-A Series Upconverters
and DT-4500-A Series Downconverters. Contact Comtech EF Data for details and specifications
for the specific system module(s).
RSM Assemblies
CEFD P/N Impedance Comments
AS/0101-4 75 Switching, Ku-Band, down
AS/0101-6 75 Switching, C-Band, Type ‘N’
AS/0101-7 50 Switching, C-Band, Type ‘N’
AS/0101-16 50 I/O, Type ‘SMA’
AS/0101-20 75 Receive Switch, C-Band, RSM2
AS/0101-26 50 RSM2, Type ‘N’
AS/0101-37 50 w/isolator, Type ‘SMA’
AS/0101-38 75 w/isolator
TSM Assemblies
CEFD P/N Impedance Comments
AS/0101-3 75 Switching, Ku-Band, up
AS/0101-5 75 Switching, C-Band, up, Type ‘N’
AS/0101-8 50 Switching, C-Band, up
AS/0101-17 50 Switching, IF & RF, Type ‘SMA’
AS/0101-18 75 Switching IF & RF w/isolator
AS/0101-22 75 UT-4514F-A w/isolator, Type ‘SMA’
AS/0101-27 50 UT-4514F-A w/isolator, Type ‘SMA’
AS/0101-28 50 UT-4518-A w/isolator, Type ‘SMA’
AS/0101-42 75 DT-4513-A w/isolator, Type ‘SMA’
AS/0101-43 50 UT-4514F-A w/isolator
3–8
UT-4500-A Series Upconverters Revision 1
Rear Panel Connectors MN-UT4500A
PSM Assemblies
CEFD P/N Impedance Comments
AS/0101-10 75 Switching, Type ‘N’
AS/0101-11 75 Switching, Type ‘SMA’
AS/0101-24 50 RF Switching, Type ‘N’
AS/0101-30 50 Type ‘SMA’
AS/0101-35 50 Type ‘SMA’ w/isolator
AS/0101-36 75 Type ‘SMA’ w/isolator
EQM Assemblies
CEFD P/N Impedance Comments
AS/0101-13 75 EQM for 1:1, C- and Ku-Bands
AS/0101-25 50 1:N IF & RF Switch, Type ‘SMA’
AS/0101-31 75 UT-4514F-A w/isolator
AS/0101-32 50 UT-4514F-A w/isolator
AS/0101-33 75 UT-4518F-A w/isolator
AS/0101-34 50 UT-4518F-A w/isolator
AS/0101-41 50 1:1 Switching
Figure 3-3. UT-4500-A Cabling Schematic (UT-4505-A with Receive Switch Module [RSM-XX]
Shown)
3–9
UT-4500-A Series Upconverters Revision 1
Rear Panel Connectors MN-UT4500A
Figure 3-4 shows a non-redundant configuration using with an IOM installed; Figure 3-5 shows
cabling accomplished with a TSM installed.
3–10
UT-4500-A Series Upconverters Revision 1
Rear Panel Connectors MN-UT4500A
3–11
UT-4500-A Series Upconverters Revision 1
Rear Panel Connectors MN-UT4500A
Notes:
3–12
Chapter 4. UPDATING FIRMWARE
4.1 Introduction
• Perform the update without opening the UT-4500-A by connecting the rear panel
10/100 Ethernet port to the Ethernet port of a user-supplied PC.
• Download the firmware update via the Internet to the user PC.
• Transfer the firmware update, via File Transfer Protocol (FTP), from the user PC to the
UT-4500-A.
4–1
UT-4500-A Series Upconverters Revision 1
Updating Firmware MN-UT4500A
Step Task
1 Identify the firmware number and version for download.
Using the unit front panel, the current unit M&C version can be viewed at the top-level
menu of the front panel display (press the [CLR] key several times to view). The firmware
information can also be found within the UTILITY FIRMWARE INFO IMAGE#1 or
IMAGE#2 menu branches. For more information, see Chapter 5. FRONT PANEL
OPERATION.
Using the 45xxA Web Server Interface, the firmware information can be found on the
CONFIG | UTILITY page. For more information, see Chapter 6. ETHERNET-BASED REMOTE
PRODUCT MANAGEMENT.
Using serial remote control, the firmware revision levels may be obtained with the
<1/FRM? query. For more information, see Appendix A. REMOTE CONTROL.
2 Create a temporary folder (directory) on an external PC:
• For Windows Explorer: Select File > New > Folder to create a new folder, then rename
it from “New Folder” to "temp" or another convenient, unused name. Assuming
"temp" works, a "c:\temp" folder should now be created.
Note: The drive letter c: is used in this example. Any valid writable drive letter can
be used.
• For Windows Command-line: Click [Start] on the Windows taskbar, then click the
“Run...” icon (or, depending on Windows OS versions prior to Windows 95, click the
“MS-DOS Prompt” icon from the Main Menu). Then, to open a Command-line
window…
o Alternately, from [Start], select All Programs > Accessories > Command Prompt.
At the Command-line prompt (c:\>), type “mkdir temp” or “md temp” (without quotes –
mkdir and md stand for make directory). This is the same as creating a new folder from
Windows Explorer. There should now be a "c:\temp" subdirectory created (where c: is the
drive letter used in this example).
There should now be a "temp" folder created and available for placement of the firmware file
download.
4–2
UT-4500-A Series Upconverters Revision 1
Updating Firmware MN-UT4500A
Step Task
1 Download the correct firmware file to this temporary folder:
About Firmware Numbers, File Versions, and Formats: The flashable files on the download
server are organized by product prefix; firmware number (verify that the correct firmware
number is known – see Step 1) and, where applicable, revision letter and release version.
The UT-4500-A firmware archive file hyperlink is F0000202x_V### (where ‘x’ denotes the
revision letter, and V### denotes the firmware version number). The downloadable files
are stored in two formats: *.exe (self-extracting) and *.zip (compressed). Some firewalls
will not allow the downloading of *.exe files. In this case, download the *.zip file instead.
For additional help with "zipped" file types, see PKZIP for Windows, WinZip, or ZipCentral
help files. PKZIP for DOS is not supported due to file naming conventions.
2 Extract a minimum of two files to the temporary folder on the PC:
4–3
UT-4500-A Series Upconverters Revision 1
Updating Firmware MN-UT4500A
Step Task
1 Connect the user PC to the UT-4500-A’s 10/100 Ethernet M&C via a hub or a switch, or
directly to the PC with a crossover cable.
2 Send a “ping” command to the unit to verify the connection and communication:
First, determine the IP address of the unit remotely or by using the UT-4500-A Front Panel:
a) From the PC, type "ftp xxx.xxx.xxx.xxx" where ‘xxx.xxx.xxx.xxx’ is the IP address of
the UT-4500-A.
b) Enter the Admin User Name (there will be no prompt for a password) to complete
login.
Type "put FW-0000202x.bin bulk:” to begin the file transfers. The destination “bulk:” must
be all lower-case. Approximately one minute is required to transfer the file.
5 Verify the file transfer:
a) The PC should report that the file transfer has occurred, and the display on the unit
will start reporting “Programming App Flash … Please wait”.
After a few minutes, the unit will display “Programming main FPGA … Please wait”.
b) Terminate the FTP session by typing "bye" and close the Command-line window.
c) Confirm that the new file was loaded by using the procedure in Step 1.
4–4
UT-4500-A Series Upconverters Revision 1
Updating Firmware MN-UT4500A
Step Task
6 Change the desired image to boot.
Use the ◄ ► arrow keys to change to the other image, then cycle power to reboot the
unit.
7 Verify the new firmware version has booted by observing the firmware version displayed
on the UT-4500-A front panel, for example:
UT_4514D-2
SW VER #.#.# SN#########
4–5
UT-4500-A Series Upconverters Revision 1
Updating Firmware MN-UT4500A
Notes:
4–6
0B
5.1 Introduction
The front panel features (from left): Two Test Point Sample Ports, Six Light-Emitting Diode (LED)
Indicators, a Vacuum Fluorescent Display (VFD); and a six-button keypad.
The Prime Power Switch, located on the rear panel, is an integral component of the IEC Line
Input (AC Power) Connector.
The function and behavior of the LED indicators, keypad, and VFD is described in detail in this
chapter. The keypad comprises six individual keyswitches. You can use the keypad and display
to fully control and monitor the operation of the UT-4500-A from the front panel. You enter
5–1
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
data via the keypad, and messages are displayed on the VFD. Nested menus display all available
options and prompt you to carry out a required action. The LEDs indicate, in a summary fashion,
the status of the unit.
Prior to turning on power to the unit, check to ensure that installation is complete, and verify
that the UT-4500-A is connected to the proper prime power source, RF Input, and IF Output.
For more information, see Chapter 2. INSTALLATION and Chapter 3. REAR PANEL
CONNECTORS.
Switch on the unit and verify the cooling fan is operational, the LED indicators illuminate as
expected, and the Vacuum Fluorescent Display is readable.
OUTPUT ENABLE Yellow Transmit function operating when the light is on.
ON LINE Yellow Operating on-line to transmit data when the light is on.
STORED FAULT Red Faults stored and logged when the light is on.
5–2
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
5.1.3 Keypad
The keypad comprises six individual keyswitches. They have a
positive ‘click’ action, which provides tactile feedback. The
function of the front panel keypad is as follows:
Use the ENTER key to select a displayed function or to execute a modem configuration change.
Use the CLEAR key to back out of a selection or to cancel a configuration change that has not been
executed since ENTER was last pressed. Pressing CLEAR generally returns the display to the
previous selection.
Use the ▲ ▼ arrow keys to move to the next selection or to move the cursor position. Most of
the menus (space permitting) include arrow key hints to guide operation.
(Up, Down)
Use the ◄ ► arrow keys primarily to change configuration data (numbers) at the current cursor
position. They may be used occasionally to scroll through a number of choices at the current cursor
(Left, Right) position. Most of the menus (space permitting) include arrow key hints to guide operation.
The keypad has an auto-repeat feature. Holding a key down for more than 1
second repeats the key action automatically at the rate of 15 keystrokes per
second. This is particularly useful when editing numeric fields with many digits,
such as frequency or data rate.
On most menu screens, you will observe a flashing solid block cursor, which blinks at a once-
per-second rate. This indicates the currently selected item, digit, or field. Where this solid block
cursor would obscure the item being edited (e.g., a numeric field) the cursor will automatically
change to an underline cursor.
If you were to display the same screen for weeks at a time, the display could become ‘burnt’
with this image. To prevent this, the unit has a ‘screen saver’ feature that activates after 1 hour.
The top line of the display will display the circuit ID, and the bottom line will display ‘Press
any key...’ The message moves from right to left across the screen, then wraps around.
Pressing any key will restore the previous screen.
5–3
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
UT_45XX –X
SW VER X.X.X SNXXXXXXXXX
This screen is displayed whenever power is first applied to the unit. When the prime power is
turned on, this VFD ‘splash’ display indicates the upconverter model number – e.g., ‘UT_4505 -
2’ – along with the version number of the firmware installed, and the serial number assigned for
the unit in use.
The opening screen may be accessed from any location within the UT-4500-A menu structure by
pressing the CLEAR key repeatedly. Otherwise, press any key to access the main menu.
The upconverter command menus are provided in a structured tree format designed for logical
access and execution of all control functions, and to prevent the execution of an invalid entry by
the operator.
The following table identifies each menu branch available from the main menu, its content
section in this chapter, and the functional description of each branch:
Use the ◄ ► arrow keys to select CONFIG, MONITOR, FAULTS, PRE-SELECTS, or UTILITY, and
then press ENTER.
5–4
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
Use the ◄ ► arrow keys to select from the submenu choices shown, and then press ENTER. Note
the following:
Typical for each parameter, use the ◄ ► arrow keys to first navigate to a parameter to edit, and
then use the ▲ ▼ arrow keys to edit the value of that digit or setting.
Freq (Frequency): Displays the current upconverter frequency in MHz, and allows the selection
of a new frequency channel between RFLow to RFHigh MHz in 125 KHz steps.
Atten (Attenuation): Displays the upconverter attenuation setting, and allows the selection of a
new setting from 0.00 to 25.00 dB in 0.25 dB steps. The default setting is 10.00 dB.
Tx: Use the ▲ ▼ arrow keys to set upconverter operation as On or Off. The default mode is Off.
5–5
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
On the top line: To set the Serial Mode, use the ▲ ▼ arrow keys to select RS-232 or
RS-485, and then press ENTER.
On the bottom line: To edit the Serial address, first use the ◄ ► arrow keys to navigate to
the digit to edit, and then use the ▲ ▼ arrow keys to edit the value of that digit. The valid
range of addresses is from 001 (default) to 255.
To edit the Baud Rate, first use the ◄ ► arrow keys to navigate to the parameter, and then
use the ▲ ▼ arrow keys to select a different baud rate. Available choices are 1200, 2400,
4800, 9600 (default), 19K2, and 38K4.
To edit the asynchronous character format, first use the ◄ ► arrow keys to navigate to the
parameter, and then use the ▲ ▼ arrow keys to select a different format. Available choices
(i.e., number of data bits; odd, even, or no parity; number of stop bits) are 8-N-1, 7-E-2, or
7-O-2.
On the bottom line: The unit MAC address is displayed here. This read-only menu shows
the. Once the MAC address has been noted, exit this menu by pressing ENTER or CLEAR.
On the top line: Use the ◄ ► arrow keys to select the parameter to configure – ADDRESS,
GATEWAY, or SNMP – and then press ENTER to continue.
5–6
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
To edit the IP Address and Range for the Ethernet M&C port for this unit: First, use the ◄ ►
arrow keys to select the digit to edit, and then use the ▲ ▼ arrow keys to edit the value of that
digit. Press ENTER when done.
To edit the IP Gateway Address for the Ethernet M&C port for this unit: First, use the ◄ ►
arrow keys to select the digit to edit, and then use the ▲ ▼ arrow keys to edit the value of that
digit. Press ENTER when done.
Use the ◄ ► arrow keys to select the parameter to configure: COMMUNITIES or TRAPS.
Use the ◄ ► arrow keys to select READ, WRITE, or TRAP, and then press ENTER.
You may view or edit the SNMP Read Community string. To edit, first use the ◄
► arrow keys to select the character to edit, and then use the ▲ ▼ arrow keys
to edit that character. Press ENTER when done.
5–7
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
You may view or edit the SNMP Write Community string. To edit, first use the ◄
► arrow keys to select the character to edit, and then use the ▲ ▼ arrow keys
to edit that character. Press ENTER when done.
You may view or edit the SNMP Trap Community string. To edit, first use the ◄
► arrow keys to select the character to edit, and then use the ▲ ▼ arrow keys
to edit that character. Press ENTER when done.
Use the ◄ ► arrow keys to select TRAPIP1, TRAPIP2, or VERSION, and then press
ENTER.
You may view or edit the Trap Destination’s IP Addresses. To edit, first use the ◄
► arrow keys to select the digit to edit, and then use the ▲ ▼ arrow keys to edit
the value of that digit. Press ENTER when done.
Note: If both Trap IP Addresses are 000.000.000.000, it means Traps are disabled.
Use the ▲ ▼ arrow keys to select the trap version – SNMPv1 or SNMPv2 – and
then press ENTER.
5–8
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
Redundancy: MODE
Otherwise:
Redundancy: MODE
Auto/Manual FORCE HSB
Use the ◄ ► arrow keys to select MODE, Auto/Manual, FORCE, or HSB (High Speed Bus), and
then press ENTER.
Note: If any submenu is selected from this menu branch when the unit is not in Local Mode
(i.e., the unit is in either Serial or Ethernet Remote Mode), the system prompts you to switch or
Local Mode as follows:
On the top line: First, use the ◄ ► arrow keys to navigate to the Redundancy Config
setting, and then use the ▲ ▼ arrow keys to set operation as On or Off.
On the bottom line: First, use the ◄ ► arrow keys to navigate to the Converter Selection
setting, and then use the ▲ ▼ arrow keys to toggle the upconverter operational preference
as #BU or #01. Note the following:
• With CONVERTER = #BU, the unit is set as the standby, or backup unit. This mode of
operation is indicated on the right-hand side of the bottom line as 1:01.
• With CONVERTER = #01, the unit is set as the primary operating unit. The mode of
operation is indicated on the right-hand side of the bottom line as POL=1.
5–9
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
Use this submenu to define backup as Automatic or Manual. This command provides for
automatic switching by the backup upconverter if both units are in the Redundancy Mode.
This command is only accepted by the backup upconverter. If a chain upconverter is set in
Manual Mode, the backup upconverter will log the occurrence and not act upon further
information from the upconverter until put into Automatic Mode.
On the top line: The unit in use and its Application ID (identification label) are displayed
here.
On the bottom line: First, use the ◄ ► arrow keys to navigate to the AUTO/MAN setting,
and then use the ▲ ▼ arrow keys to set toggle switchover as A (Automatic) or M (Manual).
On the top line: First, use the ◄ ► arrow keys to navigate to the OFFSET operational
threshold setting (i.e., the limit defined to automatically trigger switchover to the backup
unit), and then use the ▲ ▼ arrow keys to set that value in 0.25 dB increments.
On the bottom line: First, use the ◄ ► arrow keys to navigate to the ACTIVATE BACKUP
setting, and then use the ▲ ▼ arrow keys to set toggle switchover as NO (i.e., no backup
will occur at the defined operational threshold), or FORCE (i.e., switchover will take place
automatically if operation exceeds the predefined operational threshold.
Note that this submenu is operational only with a backup unit assigned, and with the
switchover set as Automatic. In the absence of a designated backup unit and/or switchover
set as Manual, the following message displays:
NO UNITS CURRENTLY
BACKED UP OR IN MANUAL
Press ENTER or CLEAR to return to the previous menus, and then reconfigure the system to
operate as intended.
In the "Daisy Chain" configuration, the backup upconverter communicates with the online
units through the high-speed interface bus (HSB). The backup upconverter is able to detect
5–10
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
faults and reconfigure itself to replace the faulted upconverter. The HSB interface is also
used in the backup Upconverter to monitor configuration changes made to an online
upconverter. Changes in frequency, gain, or polarity are immediately entered into the
backup table as well as information from new online units. The high-speed bus does not
interfere with the remote serial communication link access to any of the converters in the
chain.
The HSB (High Speed Bus) submenu is used to configure operation of the J3 HSB connector
provided on the optional Receive Switch Module (RSM) and Transmit Switch Module (TSM).
When an RSM or TSM is not configured for operation, the following message displays:
See Appendix B. REDUNDANT SYSTEM OPERATION for detailed information about use of the
front panel menus for redundancy configuration and operation.
Use the ▲ ▼ arrow keys to select Fault Recovery as Manual or Automatic, and then press
ENTER. The default operation is Auto.
When redundancy is not active, use the ▲ ▼ arrow keys to select Cold Start as Enabled or
Disabled, and then press ENTER. The default operation is Disabled.
Cold Start Mode, if enabled, mutes the upconverter output signal for a pre-determined time
after power is applied to the upconverter – 15 minutes – to ensure that the reference oscillator
is stable.
• You must be in Local or Remote Mode to use this command (default is Remote).
5–11
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
5.3.2 MONITOR
Three read-only information screens are provided to monitor a number of operating voltage,
temperature and tuning parameters. Use the ▲ ▼ arrow keys to page between screens.
The following examples are provided for informational purposes only – the data displayed here
for each parameter will vary depending on the operating conditions for the system in use:
15VDC=15.6V 14VDC=14.0V ▲
VCC=0.5V 5VDis=0.50V ▼
5.3.3 FAULTS
CURRENT STORED
Use the ◄ ► arrow keys to select CURRENT or STORED, and then press ENTER.
The following examples are provided for information purposes only – the data displayed here
will vary depending on the operating conditions for the system in use:
5–12
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
Conv Temperature = OK ▲
High Speed Bus = OK ▼
Use the ◄ ► arrow keys to select View or Clear-All, and then press ENTER.
No Stored Faults.
The faults log can store up to 100 faults. When a fault condition occurs, it is date- and time-
stamped, and stored in the faults log with a number assigned in the order received. The fault
information displays as per the following example:
When the fault condition clears, this is also recorded in the same fashion as the fault was
originally recorded, as shown per the following example:
The stored faults remain in memory until the CLEAR-ALL command is entered. When the
number of faults reaches 100, the 100th fault will display ER.
You may use the ▲ ▼ arrow key to scroll backwards or forwards through the faults log.
Use the ◄ ► arrow keys to choose No or Yes, and then press ENTER.
5–13
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
If Yes is selected, the faults log is cleared and you are returned to the previous menu. However,
if there are faults present on the unit at this time, they will be re-stamped and new log entries
will be generated.
5.3.4 PRE-SELECTS
#03 LOAD PROGRAM CLEAR ▲
03625.125 MHz 01.25 dB ▼
You may create (program) up to 32 operating configurations, and recall them as needed. If any
pre-selects exist, use the ▲ ▼ arrow keys browse through the available pre-selects (i.e., #01
through #32), and then press ENTER.
Note: Upon initial selection – i.e., prior to the creation of any pre-selects – this menu branch
appears as follows:
Use the ◄ ► arrow keys to select one of the following actions, and then press ENTER.
LOAD is operable when pre-selects have previously been programmed into the unit via the
PROGRAM submenu. Use the ◄ ► arrow keys to select No or Yes, and then press ENTER.
Select PROGRAM when it is desired to save an operational configuration for recall at a later
date.
On the top line, first use the ◄ ► arrow keys to navigate to the pre-select designator (#XX),
and then use the ▲ ▼ arrow keys to select a number from 01 to 32.
5–14
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
The read-only bottom line displays the operating parameters that will be stored into the
designated slot (via this submenu), and then recalled via the LOAD submenu.
Use the ◄ ► arrow keys to select No or Yes to clear a previously saved parameter from
memory. This will free up the slot for future pre-select programming needs. Press ENTER when
done.
5.3.5 UTILITY
TIME DISP FIRMWARE AID
REFOSC SLOPE LAMP-TEST
Use the ◄ ► arrow keys to select from the submenu choices shown, and then press ENTER. Note
the following:
To edit the time and date settings of the real-time clock, first use the ◄ ► arrow keys to select
the digit to be edited, and then use the ▲ ▼ arrow keys to change the value of that digit. Press
ENTER when done.
5–15
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
To edit the display brightness: Use the ▲ ▼ arrow keys to select a brightness value of 25%,
50%, 75%, or 100%. Press ENTER when the brightness is suitable.
The Application Identification (AID) command allows a free form message to be created. It is
intended to identify the satellite, either transponder, beam, destination or other aspects of the
application that may be significant to operations. The AID display alternates with the Equipment
type display by use of the CLEAR key. The default is "AID MESSAGE".
To edit the AID message: First, use the ◄ ► arrow keys to select No or Yes, and then press
ENTER. Then, to edit the Application ID string: For both the top and bottom lines of the display,
first use the ◄ ► arrow keys to select the character to edit, and then use the ▲ ▼ arrow keys
to edit that character.
A maximum of 24 characters are available on each line (48 characters in all), as follows:
UT-4500-A SERIES
48 CHAR MAX TST MESSAGE
Once the Application ID string is composed as per the above example, press ENTER.
The reference oscillator adjustment may be manipulated with this submenu. Use the ◄ ► arrow
keys to select the digit to edit, and then use the ▲ ▼ arrow keys to edit the value of that digit.
Press ENTER when done.
The default Reference Frequency tuning adjustment is 087, with allowable values from 0 to 255.
5–16
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
The upconverter slope adjustment may be manipulated with this submenu. Use the ◄ ► arrow
keys to select the digit to edit, and then use the ▲ ▼ arrow keys to edit the value of that digit.
Press ENTER when done.
The default upconverter slope adjustment is 0.0, with allowable values from 0.0 to 1.0.
To start the lamp test, use the ◄ ► arrow keys to select No or Yes, and then press ENTER. The
test begins with the following message:
The front panel will then run through a series of diagnostics: the LED array will cycle, and then the
VFD will generate a series of test patterns. The VFD will return to the previous menu upon
successful completion of the test.
Once the test has run, press CLEAR to return to the main menu. .
This series of submenus permits you to view information about the UT-4500-A internal
firmware. The upconverter can store two complete firmware images, and you can select which
image will be loaded the next time the unit reboots.
Firmware Images:
INFO SELECT
Use the ◄ ► arrow keys to select INFO or SELECT, and then press ENTER.
5–17
UT-4500-A Series Upconverters Revision 1
Front Panel Operation MN-UT4500A
Use the ◄ ► arrow keys to select BOOTROM, IMAGE#1 or IMAGE#2, and then press ENTER to
view the information.
The BOOTROM screen displays information similar to the example that follows:
Bootrom: FW-0000200
X.X.X MM/DD/YY
For IMAGE#1 and IMAGE#2, each image is further broken down as follows (where IMAGE#X
denotes IMAGE#1 or IMAGE#2):
Use the ◄ ► arrow keys to select Bulk, App, or FPGA, and then press ENTER. The screens display
information in a format similar to the examples that follow:
Bulk#X: FW-0000202
X.X.X MM/DD/YY
App#X: FW-0000203
X.X.X MM/DD/YY
FPGA#X: FW-0000204
X.X.X MM/DD/YY
The top line shows the Current Active Image. From the bottom line, use the ◄ ► arrow keys to
select the Next Reboot Image (i.e., the image that will be active the next time the unit is
rebooted) as #1 or #2. Press ENTER when done.
If the image selected is already designated as the Next Reboot Image, the following message
displays:
5–18
Chapter 6. ETHERNET-BASED
REMOTE PRODUCT
MANAGEMENT
6.1 Introduction
Ethernet-based remote management and control of the UT-4500-A is available using the rear
panel ‘10/100 ETHERNET’ port.
o The PC’s serial port is connected to the UT-4500-A rear panel ‘J1 |
COM1’ port with a user-supplied serial cable.
6–1
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
For SNMP, Telnet, or HTTP operation, the UT-4500-A must be configured with the
Ethernet control option. From the front panel, select CONFIG: REMOTE
ETHERNET. See Chapter 5. FRONT PANEL OPERATION for further information.
The user PC provides access to Ethernet-based remote Monitor and Control (M&C) of the
UT-4500-A through three separately operated protocols:
• 45xxA Telnet Interface. This requires use of a user-supplied terminal emulation program
such as HyperTerminal.
• 45xxA Web Server (HTTP) Interface. This requires a compatible user-supplied web
browser such as Internet Explorer.
• The SNMP Agent. This is the software that runs on the UT-4500-A. The 45xxA SNMP
Agent supports both SNMPv1 and SNMPv2c.
• The user-supplied Network Management System (NMS). This is the software that runs
on the manager.
6–2
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
MIB File/Name
(where ‘x’ is the Description
revision letter)
FW-0000235x.mib ComtechEFData MIB file gives the root tree for ALL Comtech EF Data products and
ComtechEFData consists of only the following OID:
Root MIB file Name: comtechEFData
Type: MODULE-IDENTITY
OID: 1.3.6.1.4.1.6247
Full path:
iso(1).org(3).dod(6).internet(1).private(4).enterprises(1).comtechEFData(6247)
Module: ComtechEFData
FW-0020205x.mib
MIB file consisting of all OID’s for management of the upconverter functions
UT-4500-A MIB file
FW-0020206x.mib
UT-4500-A Traps Trap MIB file for SNMPv1 traps common for UT-4500-A.
MIB file
In SNMP v1/v2c, the SNMP Community String is sent unencrypted in the SNMP
packets. Caution must be taken by the network administrator to ensure that SNMP
packets travel only over a secure and private network if security is a concern.
The UT-4500-A uses Community Strings as a password scheme that provides authentication
before gaining access to the UT-4500-A agent’s MIBs. They are used to authenticate users and
determine access privileges to the SNMP agent.
Type the SNMP Community String into the user-supplied MIB Browser or Network Node
Management software. You may define three Community Strings for SNMP access:
For proper SNMP operation, the UT-4500-A MIB files must be used with the
associated version of the UT-4500-A Series Upconverter M&C. Refer to the
UT-4500-A FW Release Notes for information on the required FW/SW compatibility.
6–3
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
fault occurs and when a fault clears. Which style of traps the UT-4500-A sends are configured
using the UT-4500-ASNMPTrapVersion OID.
Once logged into the Telnet interface as Administrator, you can access the standard remote
control interface defined in Appendix A. REMOTE CONTROL.
6–4
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
An example of login and remote command/query execution, when using HyperTerminal as the
interface, is shown here:
See Chapter 5. FRONT PANEL OPERATION or the Remote Commands Specifications tables found
in Appendix A. REMOTE CONTROL for detailed descriptions of many of the functions depicted
throughout Sect. 6.4.5 Web Server Page Descriptions.
The IP Address can be verified from the front panel menus: CONFIG: REMOTE
ETHERNET ADDRESS. See Chapter 5. FRONT PANEL OPERATION for
complete details about using this M&C interface.
To enable the Web Server Interface in the UT-4500-A using only a 100BaseTx remote interface
(this assumes you are running Microsoft Windows OS):
6–5
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
Failure to enter the correct User name and Password will return you to a blank login screen.
Type the User name and Password, and then click [OK].
Failure to enter the correct User name and Password will return you to the Login window.
Should you continue to specify an invalid User name or Password, the message “You do not have
security privilege to access this area.” displays. Otherwise, upon entry of the valid IP address and
login information 45xxA Web Server Interface “splash” page displays, similar to the example
shown here:
6–6
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
6.4.3.1 Navigation
The 45xxA Web Server Interface features navigation tabs located at
the top of each page. After you click a navigation tab, you may click
an available page hyperlink.
This manual uses a naming format for all Web pages to indicate the depth of navigation needed
to view the subject page: “Top Level Tab | Web page hyperlink”.
For example: “Home | Support” is interpreted to mean “first click the top-level ‘Home’
navigation tab; then, click the ‘Support’ page hyperlink.
This manual explains the purpose and operation for each Web page on a per-page, per-section
basis.
If you edit a field, make sure to click the action button before you leave the page.
If you go to another page without first clicking the action button, your changes are
not saved.
6–7
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
If you edit any field, make sure to click the action button before you leave the
page. If you go to another page without first clicking the action button, your
changes are not saved.
Support Pre-selects
Utility
Redundancy
6–8
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
6–9
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
6–10
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
For this page to operate correctly, the Administrator must define the SMTP server,
domain name, and destination on the Admin | Access page (see Sect. 6.4.5.2.1).
This page uses SMTP (Simple Mail Transport Protocol) to compose and send an e-mail message
to Comtech EF Customer Support ([email protected]). Use this communications
portal for questions about or problems with the unit.
Contact Information
Provide your contact information – Name, Company, Telephone and E-mail – to Comtech EF
Data here.
Problem Report
Use this section to compose the required message of up to a maximum of 256 characters.
After providing your Contact Information and composing your message in the Problem Report
section, click [Submit Email] to send the message.
6–11
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
The Admin pages are available only to users who have logged in using the
Administrator Name and Password.
Click the Admin tab, and then select the Access or SNMP hyperlink to continue.
Network Maintenance
• IP Gateway, IP Address/Range: Enter the desired IP Gateway Address and IP Address/
Range in these text boxes.
• MAC Address (read-only): The MAC is set at the factory to a guaranteed unique address that
cannot be modified by the user.
6–12
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
Click [Change IP Address] to save. Otherwise, click [Reset] to revert to the previously assigned IP
Gateway and IP Address/Range,
o Admin comtech/comtech
o Read/Write opcenter/1234
o These Name fields can be any alphanumeric combination with a maximum length of
10 characters.
• SMTP Server: Specify the mail server IP address from where you want to send the
e-mail.
• SMTP Domain Name / Destination: The Administrator can assign the SMTP Domain
Name and Destination. This is required if the e-mail feature of the Home | Support page
(Sect. 6.4.5.1.3) is to be used.
o For SMTP Domain Name, specify the domain of the e-mail server (usually found to
the right of the @ symbol in an e-mail address).
o For SMTP Domain Destination, specify the e-mail recipient name (usually found to
the left of the @ symbol in an e-mail address).
Click [Submit Access] to save. Otherwise, click [Reset] to revert to the previously assigned
System Account Access Information.
Webpage Timeout
To set an automatic timeout to safeguard access to an already logged-in unit, use the drop-
down list to set the time value as 5 minutes or 8 hours, and then click [Change].
The active session terminates if the unit remains idle (i.e., when no user activity occurs) beyond
the assigned Webpage Timeout. A valid user name and password is then required to resume the
45xxA Web Server Interface session.
6–13
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
SNMP
• Simple Network Management Operational Status: Use the drop-down list to select the
Simple Network Management operational setting as Enabled or Disabled.
• The SNMP Read and Write Community String fields can be any combination of characters
and a length of 0 - 20 characters:
o The factory default for the Read Community String parameter is public.
• Enable Authentication Trap: Use the drop-down list to select the Enable Authentication
Trap operational setting as Enabled or Disabled.
• The Administrator can assign up to two SNMP Trap IP addresses and one SNMP Trap
Community String. The SNMP Trap Community String field can be any combination of
characters and a length of 0 - 20 characters:
• Trap Version: Use the drop-down list to select the SNMP Trap Version as SNMPv1 or
SNMPv2c.
See Sect. 6.3 SNMP INTERFACE for details pertaining to the remaining configuration parameters
available on this page,
6–14
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
Click [Submit SNMP] to save. Otherwise, click [Reset] to revert to the previously assigned SNMP
designations.
Converter
• Frequency in MHz: Enter an operating RF Frequency; otherwise, this field will display as
N/A.
• Attenuation (dB): Enter a valid attenuation level (00.00 to 20.00 dB) in 0.25 dB steps.
6–15
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
Click [Change Configuration] to save. Otherwise, click [Reset] to revert to the previously
assigned parameters.
Mute
Use the drop-down list to select Configuration Mute Mode as On or Off, and then click [Change].
Fault Recovery
Use the drop-down list to select the Fault Recovery function as MANUAL or AUTOMATIC, and
then click [Change].
Serial
• Interface Type: Use the drop-down list to select the operating serial mode as RS-485 or
RS-232.
• Remote Address: Enter a valid remote control address from 0001 to 9999.
• Baud Rate: Use the drop-down list to select the operating baud rate as 100, 2400, 4800,
9600, 19200 or 38400 baud.
• Data bits – Parity – Stop Bits: Use the drop-down list to select the asynchronous character
format as:
6–16
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
Reference Oscillator
• External Reference Freq. (read-only): When an external reference oscillator is connected, its
operational value (i.e., 5 MHz or 10 MHz) is displayed here.
• Reference Tuning (VDC) (read-only): The currently defined Reference Frequency tuning
adjustment is displayed here.
• External Reference Lock (read-only): The External Reference Lock state is displayed here.
• Tuning Adjustment (0-255): Enter a numeric value for the reference oscillator tuning
voltage here. The default value is 087, with allowable values from 0 to 255.
6–17
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
Pre-Selects
You may create (program) up to 32 operating configurations, and recall them as needed.
Note: Upon initial selection – i.e., prior to the creation of any pre-selects – the Frequency and
Attenuation columns are populated with null values.
To program any pre-select (Numbers 01 through 32), enter an operating RF frequency (in MHz),
and an attenuation level from 00.00 to 20.00 dB in 0.25 dB steps. Click [Change Configuration]
to save (program) the pre-select for future selection (recall).
Load Pre-Select
Use the drop-down list to select (recall) a previously defined pre-select from memory, and then
click [Change].
6–18
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
Date
Enter a date in the form MM/DD/YY (where MM = month [01 to 12], DD = day [01 to 31], and YY
= year [00 to 99]).
Time
Enter a time in the form HH:MM:SS (where HH = hour [00 to 23], MM = minutes [00 to 59], and
SS = seconds [00 to 59]).
Circuit ID
Enter a Circuit ID string of up to 48 characters, and then click [Change CID] to save.
6–19
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
• Next Reboot Image: Use the drop-down list to select Image 1 or 2, and then click [Submit].
6–20
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
Click [Refresh] to update the page with its latest operating parameters.
6–21
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
Click the Status tab, and then select Summary or Faults hyperlink to continue.
Typical for all sections, when operating parameters are within acceptable limits for any item, the
STATUS indicates OK within a green box. If a fault condition exists, the message box changes to
red with the FAULT indicated accordingly.
Terminal Status Change will state YES if the unit identifies any configuration settings updates
since the last reboot. Click [Clear] to reset this monitoring feature (Terminal Status Change will
then state NO).
6–22
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
The unit returns and displays the five oldest stored faults in the alarm log. All faults that are read
from the log are automatically removed from the tally.
You can manage the Unread Stored Faults window as follows – select a choice, and then click
[Submit] to execute the window update:
• Read Next Five Faults: Select to display the next five unread stored faults in the log.
• Clear Fault Log: Select to clear all stored faults from the log.
• Initialize Faults Pointer: Select to reset the internal pointer to allow queries to start at
the beginning of the stored faults log.
6–23
UT-4500-A Series Upconverters Revision 1
Ethernet-based Remote Product Management MN-UT4500A
Notes:
6–24
Appendix A. REMOTE CONTROL
A.1 Introduction
This appendix describes the protocol and message command set for remote monitor and control
of Comtech EF Data’s UT-4500-A Series Upconverters.
In the other direction: On the other pair, each Target has a tri-state line driver connected; the
Controller has a line-receiver connected. All the line drivers are held in high-impedance mode
until one – and only one – Target transmits back to the Controller. Each Target has a unique
address; each time the Controller transmits, the address of the intended recipient Target is
included in a framed 'packet' of data. All of the Targets receive the packet, but only one (the
A–1
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
intended) will reply. The Target enables its output line driver and transmits its return data
packet back to the Controller in the other direction on the physically separate pair.
• Two differential pairs - one pair for Controller-to-Target, one pair for Target-to-Controller.
• Controller-to-Target pair has one line driver (Controller), and all Targets have line-receivers.
• Target-to-Controller pair has one line receiver (Controller), and all Targets have tri-state
drivers.
In this control network, all converters including the backup converter are paralleled on a
common EIA-485 cable. Both up and down converters can be mixed on the cable as long as each
converter has a unique physical address. Only one EIA-485 port is required on the system's
monitor and control computer. If a change is initiated directly to a converter in a redundancy
subsystem, the backup converter will detect the change via the High Speed Bus and update its
backup tables.
A–2
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
For EIA-232 control, a direct EIA-232 cable connection is made to each converter to be accessed.
If using an external Monitor and Control Computer, one EIA-232 port per converter is required.
This mode is commonly used with an ASCII terminal for bench testing.
To control by using the EIA-485 interface, one or more backup converters are connected to a
system's monitor and control computer or ASCII terminal with a common EIA-485 bus cable.
Both up and down backup converters may be mixed on the cable as long as each has a unique
device address. In order to indirectly address an online converter in the subsystem, a virtual
address must be provided. The virtual address corresponds to the converter's position in the
chain beginning with number 1. Virtual addressing is only recognized by a backup converter.
Only one EIA-485 port is required on the monitor and control computer.
To control by using the EIA-232 interface, one EIA-232 port on the monitor and control
computer is required for each backup converter. Virtual addressing must be established by
command. All converters including the backup converter must be in the Redundancy Mode.
A.4 Addresses
All converters are addressed in a command by the Device Address. The Device Address consists
of a physical address or a physical address plus a virtual address.
A–3
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Example: 10V3 (Addresses the third converter controlled by the backup converter whose
physical address is 10.)
A.4.3 IP Address
The IP address is a unique address on a network that supports Internet Protocol (i.e., IPv4). An
example of a network address using IPv4 is 192.168.1.4 (factory default IP address). This value
must be configured correctly to allow a Telnet session to control the unit.
All data is transmitted in framed packets. The Controller is assumed to be a PC or ASCII dumb
terminal that is in charge of the process of monitor and control. The Controller is the only device
that is permitted to initiate, at will, the transmission of data. Targets are only permitted to
transmit when they have been specifically instructed to do so by the Controller.
All bytes within a packet are printable ASCII characters, less than ASCII code 127. In this context,
the Carriage Return and Line Feed characters are considered printable.
All messages from Controller-to-Target require a response, with one exception: This will be either to
return data that has been requested by the Controller, or to acknowledge reception of an instruction
to change the configuration of the Target. The exception to this is when the Controller broadcasts a
message (such as Set Time/Date) using Address 0, when the Target is set to EIA-485 mode.
A–4
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
• Start Character
• Device Address
• Command or Response
Example: <3V12
A.6.3 Command
A Command is a variable length character string beginning with a forward slash “/”’ and
containing either an instruction or an instruction and data for a converter to act upon. If data is
passed by command it is appended to the instruction by an underscore “_”. If data is retrieved
by command underscore follows the instruction flagging the converter to supply data in a
response.
A–5
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Note: This appendix uses “/COM” for the generic case examples.
Example: >DEV/COM_xxx'cr''lf']
Following the "?" error symbol are two characters which are unique error symbols useful for
computer analysis. The two error symbols are followed by a text string explaining the error for
the convenience of a human operator. This appendix uses “ER” for the generic case examples
response.
Example: <DEV/COM_'cr'
Example: >DEV/COM_'cr''lf']
A–6
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
A.7.1.1 Time
Command Details
Set Time: <DEV/TIM_hh:mm:ss'cr'
Where:
hh=Hour
mm=Minutes
ss=Seconds
Confirmation: >DEV/TIM_hh:mm:ss'cr''lf']
Retrieve Time: <DEV/TIM_'cr'
Confirmation: >DEV/TIM_hh:mm:ss'cr''lf']
A.7.1.2 Date
Command Details
Set Date: <DEV/DAT_mm/dd/yy'cr’
Where:
mm=Month
dd=Day
yy=Year
Confirmation: >DEV/DAT_mm/dd/yy'cr'lf']
Retrieve Date: <DEV/DAT_'cr'
Confirmation: >DEV/DAT_mm/dd/yy'cr''lf']
Command Details
Set Time Protocol: <DEV/TPE_x'cr’
Where:
x=
0 Time protocol disabled
1 Time protocol enabled
Confirmation: >DEV/TPE_x'cr'lf']
Retrieve TPE: <DEV/TPE_'cr'
Confirmation: >DEV/TPE_x'cr''lf']
A–7
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Command Details
Set Time Protocol Server: <DEV/TPS_xxx.xxx.xxx.xxx'cr’
Where:
xxx.xxx.xxx.xxx is the Time server IP address.
Confirmation: >DEV/TPS_xxx.xxx.xxx.xxx'cr'lf']
Retrieve TPS: <DEV/TPS_'cr'
Confirmation: >DEV/TPS_xxx.xxx.xxx.xxx'cr''lf']
Command Details
Set Local / Remote <DEV/LRS_x'cr’
Status:
Where:
x=
0 for front panel control only (remote control disabled)
1 for serial remote control
2 for Ethernet control
3 for Ethernet and serial remote control
Confirmation: >DEV/LRS_x'cr'lf']
Retrieve LRS: <DEV/LRS_'cr'
Confirmation: >DEV/LRS_x'cr''lf']
Command Details
Retrieve MAC: <DEV/MAC_'cr'
Confirmation: >DEV/MAC_xx-xx-xx-xx-xx-xx'cr''lf']
Where:
xx=MAC address byte in hexadecimal
A–8
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
A.7.1.7 IP Address
Use the IPA command to set the IP address and network prefix for the 100BASE-TX Ethernet
management port. The factory default value is 192.168.1.4.24.
Command Details
Set IP Address: <DEV/IPA_aaa.bbb.ccc.ddd.yy'cr’
Where:
aaa = 0-223
bbb = 0-255
ccc = 0-255
ddd = 0-255, but they cannot all be zero.
yy is the Subnet Mask Length (range: 8 to 30)
Confirmation: >DEV/IPA_ aaa.bbb.ccc.ddd.yy'cr'lf']
Retrieve IP Address: <DEV/IPA_'cr'
Confirmation: >DEV/IPA_ aaa.bbb.ccc.ddd.yy'cr''lf']
A.7.1.8 IP Gateway
Use the IPG command to set the IP gateway address for the Ethernet management port. The
factory default value is 192.168.1.5.
Command Details
Set IP Gateway: <DEV/IPG_aaa.bbb.ccc.ddd'cr’
Where:
aaa = 0-223
bbb = 0-255
ccc = 0-255
ddd = 0-255, but they cannot all be zero.
Confirmation: >DEV/IPG_ aaa.bbb.ccc.ddd'cr'lf']
Retrieve IP Gateway: <DEV/IPG_'cr'
Confirmation: >DEV/IPG_ aaa.bbb.ccc.ddd'cr''lf']
Command Details
Set Physical Address: <DEV/SPA_xxx'cr' xxx = 1 to 255
Confirmation: >DEV/SPA_xxx'cr''lf']
Retrieve Phys. Addr: <DEV/SPA_'cr'
Confirmation: >DEV/SPA_xxx'cr''lf']
A–9
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Command Details
Set Baud Rate: <DEV/SBR_xxxx'cr' xxxx = 1200, 2400, 4800, 9600, 19K2, or 38K4
Confirmation: >DEV/SBR_xxxx'cr''lf']
Retrieve Baud Rate: <DEV/SBR_xxxx'cr'
Confirmation: >DEV/SBR_xxxx'cr''lf']
Command Details
Set Contrast: <DEV/CON_xx'cr' xx = 0 to 30
Confirmation: >DEV/CON_xx'cr''lf']
Retrieve Contrast: <DEV/CON_'cr'
Confirmation: >DEV/CON_xx'cr''lf']
Command Details
Set Brightness <DEV/LCD_xx'cr' xx = 0 to 30
Confirmation: >DEV/LCD_xx'cr''lf']
Retrieve Brightness: <DEV/LCD_'cr'
Confirmation: >DEV/LCD_xx'cr''lf']
Command Details
Set SSM: <DEV/SSM_x'cr'
Where:
x=0 to 5
Confirmation: >DEV/SSM_x'cr''lf']
Retrieve SSM: <DEV/SSM_'cr'
Confirmation: >DEV/SSM_x'cr''lf']
A–10
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Command Details
Set SST: <DEV/SST_xx'cr' xx = 00 to 99
Confirmation: >DEV/SST_xx'cr''lf']
Retrieve SST: <DEV/SST_'cr'
Confirmation: >DEV/SST_xx'cr''lf']
Command Details
Set VFD: <DEV/VFD_xxx'cr' xx = 000 to 100 (in 025 steps)
Confirmation: >DEV/VFD_xxx'cr''lf']
Retrieve VFD: <DEV/LCD_'cr'
Confirmation: >DEV/VFD_xxx'cr''lf']
Command Details
Set Oscillator: <DEV/SRO_xxx'cr' xxx = 0 to 255
Confirmation: >DEV/SRO_xxx'cr''lf']
Retrieve Tuning: <DEV/SRO_'cr'
Confirmation: >DEV/SRO_xxx'cr''lf']
Command Details
Set Slope Adjust: <DEV/SSA_xxx'cr' xxx = 0.0 to 1.0
Confirmation: >DEV/SSA_xxx'cr''lf']
Retrieve Slope Adjust: <DEV/SSA_'cr'
Confirmation: >DEV/SSA_xxx'cr''lf']
A–11
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Command Details
Retrieve Equipment Type: <DEV/RET_'cr'
Confirmation: >DEV/RET_xxxxxxxxxx yyyyyyy'cr’’lf']
xxxxxxxxxx = Model Number
yyyyyyy = Software Version.
Command Details
Retrieve Part Number: <DEV/PNM_'cr'
Confirmation: >DEV/PNM_xx…xx'cr’’lf']
Where:
xx…xx = up to 96 bytes of part number information
Command Details
Retrieve Firmware Information: <DEV/FRW_’cr’
Confirmation: >DEV/FRW_’cr’
BULK= FWnnnn-nr Ver=x.xx’cr’
M&C = FWnnnn-nr Ver=x.xx’cr’
FPGA= FWnnnn-nr Ver=x.xx’cr’’lf’]
Where: nnnn-n firmware number
r firmware revision
x.xx firmware version
Note: BULK, M&C, and FPGA have different firmware numbers,
revisions, and versions among each other.
A–12
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Command Details
Retrieve Firmware Information: <DEV/FRM_’cr’
Confirmation: >DEV/FRM_’cr’
Boot: ’cr’
FW-AAAAAAA B.B.BB DD/MM/YY’cr’
Bulk1: ’cr’
FW-AAAAAAA B.B.BB DD/MM/YY’cr’
FW-AAAAAAA B.B.BB DD/MM/YY’cr’
FW-AAAAAAA B.B.BB DD/MM/YY’cr’
Bulk2: ’cr’
FW-AAAAAAA B.B.BB DD/MM/YY’cr’
FW-AAAAAAA B.B.BB DD/MM/YY’cr’
FW-AAAAAAA B.B.BB DD/MM/YY’cr’’lf’]
Where:
FW-AAAAAAA = the firmware part number
B.B.BB = the version number
DD/MM/YY = Day/Month/Year firmware released
Command Details
Set Next FW Image: <DEV/IMG_x'cr' x = 1 to 2
Confirmation: >DEV/IMG_x'cr''lf']
Retrieve Active FW <DEV/IMG_'cr'
Image:
Confirmation: >DEV/IMG_x'cr''lf']
A–13
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
The message length corresponds to capability of the LCD and is 48 characters in total. The
second line begins at character 25, therefore, blanks must be used after line 1 information in
order to space to line 2. A carriage return ends the command. Trailing blanks will be generated
to fill the LCD field. The AID display will alternate with the Equipment type display by use of the
clear function key on the front panel. The default is "AID MESSAGE".
Command Details
Application ID: <DEV/AID_xxxxxxx ... xxxxx'cr'
Confirmation: >DEV/AID_'cr'
xxxxxxxxxxxxxxxxxxxxxxxx'cr'
xxxxxxxxxxxxxxxxxxxxxxxx'cr''lf']
Retrieve ID: <DEV/AID_'cr'
Confirmation: >DEV/AID_'cr'
xxxxxxxxxxxxxxxxxxxxxxxx'cr'
xxxxxxxxxxxxxxxxxxxxxxxx'cr''lf']
Command Details
Force Reboot: <DEV/FRB_YES'cr'
Confirmation: >DEV/FRB_YES'cr''lf']
A–14
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
A.7.2.1 Frequency
The default RF frequency of the unit is equal to its minimum operating frequency (RFLow).
Command Details
Set Frequency: <DEV/FRE_xxxxx.xxx'cr'
Confirmation: >DEV/FRE_xxxxx.xxx'cr''lf']
Retrieve Frequency: <DEV/FRE_'cr'
Confirmation: >DEV/FRE_xxxxx.xxx'cr''lf']
Note: For example, xxxx.xxx = 14000.000 to 14500.000 MHZ in 125 KHz steps for Model
UT-4514-A
A.7.2.2 Attenuator
The default attenuation value is 10.00 dB.
Command Details
Set Attenuator: <DEV/ATT_ yy.yy'cr'
Confirmation: >DEV/ATT_yy.yy'cr'lf']
Retrieve Attenuator: <DEV/ATT_'cr'
Confirmation: >DEV/ATT_ yy.yy'cr''lf']
Command Details
Set Cold Start: <DEV/CLD_xxx'cr' xxx = ON or OFF
Confirmation: >DEV/CLD_xxx'cr''lf']
Retrieve Status: <DEV/CLD_'cr'
Confirmation: >DEV/CLD_xxx'cr''lf']
A–15
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
A.7.2.4 Mute
The default RF mute state is ON (output is muted).
Command Details
Mute Output: <DEV/MUT_xxx'cr' xxx = ON or OFF
Confirmation: >DEV/MUT_xxx'cr''lf']
Retrieve Mute Status: <DEV/MUT_'cr'
Confirmation: >DEV/MUT_yyy'cr''lf']
yyy = ON/OFF/COLD
Command Details
Mute Mode: <DEV/CMM_xxx'cr' xxx = ON or OFF
Confirmation: >DEV/CMM_xxx'cr''lf']
Retrieve CMM Status: <DEV/CMM_'cr'
Confirmation: >DEV/CMM_xxx'cr''lf']
The default redundant mute mode state is OFF (backup unit’s output automatically unmutes
when a redundant switchover occurs).
Command Details
Set CRM: <DEV/CRM_xxx'cr' xxx = ON or OFF
Confirmation: >DEV/CRM_xxx'cr''lf']
Retrieve CRM: <DEV/CRM_'cr'
Confirmation: >DEV/CRM_xxx'cr''lf']
A–16
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Command Details
Set Fault Recovery: <DEV/AFR_xxx'cr' xxx = ON or 0FF
Confirmation: >DEV/AFR_xxx'cr''lf']
Retrieve Status: <DEV/AFR_'cr'
Confirmation: >DEV/AFR_xxx'cr''lf']
Command Details
Program Preset: <DEV/PGM_nn_xxxxx.xxx_yy.yy'cr'
Confirmation: >DEV/PGM_nn_xxxxx.xxx_yy.yy'cr''lf']
Command Details
Display Presets: <DEV/DPS_'cr'
Confirmation: >DEV/DPS_'cr'
P01 xxxxx.xxx yy.yy'cr'
to
P32 xxxxx.xxx yy.yy'cr''lf']
Where: xxxxx.xxx = Frequency
yy.yy= Attenuator
Note: Only programmed preset numbers are returned. If no preset(s) is programmed, “No Pre-
Selects Programmed” is returned.
A–17
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Command Details
Clear a Preset: <DEV/CLR_nn'cr'
Confirmation: >DEV/CLR_nn_Cleared'cr''lf']
Command Details
Select Preset: <DEV/SEL_nn'cr'
Confirmation: >DEV/SEL_nn_Selected'cr''lf']
A–18
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
A.7.3 Modes
There are two modes of operation that may intersect: Redundant Mode and Automatic Mode.
Polling on the high speed bus will not begin until the position assignments are made.
Command Details
Redundant Mode: <DEV/RED_xxx'cr' xxx = ON or OFF
Confirmation: >DEV/RED_xxx'cr''lf']
Redundant Status: <DEV/RED_'cr'
Confirmation: >DEV/RED_xxx'cr''lf']
Note: The primary units must all be configured properly in redundant mode before redundant
mode is enabled on the backup unit.
Each converter's chain position must be initialized including the backup converter. The following
redundancy initialization command is only allowed if Redundancy Mode has been selected.
Command Details
Initialize Command: <DEV/ICT_xx_yy'cr'
Confirmation: >DEV/ICT_xx_yy'cr''lf']
Initialize Status: <DEV/ICT_'cr'
Confirmation: >DEV/ICT_xx_yy'cr''lf']
xx = chain position = 01 to 12, or BU. Where BUselects the converter as the
backup.
yy = chain length for xx = BU (i.e. Backup converter) 01 to 12.
yy = unused if xx = 01 to 12 (i.e. chain converter)
Example 1: The following command assigns the converter chain position "1".
<DEV/ICT_01'cr'
>DEV/ICT_01'cr''lf']
Example 2: The following command assigns the receiving converter as the backup converter
in a 1:8 system.
<DEV/ICT_BU_08'cr'
>DEV/ICT_BU_08'cr''lf']
Important: It should be reiterated that only the converter physically located at the top of a
redundant rack should be assigned as the Backup unit. Likewise, assignment of chain positions in
a redundant rack should be made according to the physical allocation of each converter in the
rack (i.e. The top converter should be the Backup, the second converter should be assigned
chain position 1, the third converter position 2, etc.).
A–19
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Command Details
Automatic Mode: <DEV/SAM_xx_y'cr'
Confirmation: >DEV/SAM_xx_y'cr''lf']
Automatic Status: <DEV/SAM_xx_'cr'
Confirmation: >DEV/SAM_xx_y'cr''lf']
Where: xx = 01 to 12, converter number
y = A for Auto; M for Manual
Command Details
Initiate a Backup: <DEV/FBU_xx_y'cr'
Confirmation: >DEV/FBU_xx_y'cr''lf']
Where: xx = 01 to 12, converter number
y = ‘F’ to force a backup ‘N’ to remove a backup
Retrieve Backup Status: <DEV/FBU_'cr'
Confirmation: >DEV/FBU_xx_zzzzz'cr''lf']
Where: xx = 01 to 12, converter number. If zzzzz = NONE, converter
number is not displayed.
zzzzz = ‘NONE’ if no backup active
= ‘ACTIVE’ if an automatic backup has occurred
= ‘FORCED’ if a forced backup is active
A–20
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Note: If Redundancy OFF xx_yy_z = OFF, else if Redundancy ON and converter selected as
backup controller xx_yy_z = BU_yy where yy is the number of converters in the chain (i.e. 01 to
12), else if Redundancy ON and converter selected as a chain unit xx is the converter number (01
to 12), and z = A if Auto Mode or M if Manual Mode.
A–21
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Command Details
Summary Alarm: <DEV/SAS_'cr' xx = OK or FT
Confirmation: >DEV/SAS_xx'cr''lf']
A–22
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Command Details
Configuration Status: <DEV/TSC_'cr’
Confirmation: >DEV/TSC_nnn'cr''lf'] nnn=YES/NO
Notes:
1. If the converter is 1 kHz step size, this will be the number of 1 kHz steps above the base
frequency
2. If the converter is 0.1 -dB step size, this will be the number of 0.1 -dB steps above the
base frequency
3. If it is a backup converter, it is always ‘A’
A–23
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
A–24
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
A–25
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Where:
xx = stored fault number
yyyyyyyyyyy = fault description
hh:mm:ss = fault time
mm/dd/yy = fault date
A–26
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
A.7.6.4 Time-Outs
A time-out should be assumed if there is no response in 500 milliseconds. The station monitor
and control computer should try at least three times.
A–27
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Configuration Commands
Set Frequency <DEV/FRE_xxxxx.xxx'cr'
Set Attenuation <DEV/ATT_xx.xx'cr'
Select Cold Start Mode <DEV/CLD_xxx'cr'
Mute/Unmute Converter <DEV/MUT_xxx'cr'
Set Carrier Mute Mode <DEV/CMM_xxx'cr'
Set Redundant Mute Mode <DEV/CRM_xxx'cr'
Set Fault Recovery Mode <DEV/AFR_xxx'cr'
Set a Preset <DEV/PGM_nn_xxxxx.xxx_yy.yy'cr'
Get All Presets <DEV/DPS_'cr'
Clear a Preset <DEV/CLR_nn'cr'
Select a Preset <DEV/SEL_nn'cr'
A–28
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Status Commands
Retrieve Configuration Status <DEV/RCS_'cr'
Retrieve Maintenance Status <DEV/RMS_'cr'
Retrieve Utility Status <DEV/RUS_'cr'
Retrieve Alarm Status <DEV/RAS_'cr'
Summary Alarm Status <DEV/SAS_'cr'
Terminal Status Change <DEV/TSC_'cr'
Packed Configuration Status <DEV/PACRCS_'cr'
Packed Maintenance Status <DEV/PACRMS_'cr'
Packed Utility Status <DEV/PACRUS_'cr'
Packed Alarm Status <DEV/PACRAS_'cr'
A–29
UT-4500-A Series Upconverters Revision 1
Appendix A MN-UT4500A
Notes:
A–30
Appendix B. REDUNDANT
SYSTEM OPERATION
A High Speed Bus (HSB) provides the communications interface between the backup and online
upconverters to detect faults and reconfigure the subsystem to replace the failed upconverter.
When a faulted upconverter is removed from active operation, it is detached from the active
upconverter chain by separating the upconverter from its switch module, leaving the active
online upconverter chain intact through the switch module. The chain can be extended without
affecting the online upconverter operation.
The active "chained" upconverters in a redundancy subsystem can also be indirectly controlled
through the backup upconverter using the remote serial communication link – this capability is
discussed in Appendix A. REMOTE CONTROL.
B–1
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
For redundant "Daisy Chain" operations, the online upconverters are provided with a
detachable Transmit Switch Module (TSM) replacing the IOM.
Refer to Chapter 3. REAR PANEL CONNECTORS, Sect. 3.2.2.2 for quick reference tables for the
modules available to both the UT-4500-A Series Upconverters and the DT-4500-A Series
Downconverters.
B–2
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
o Single Source IF Input Configuration: The online upconverter uses an IF & RF transfer
switch to switch the IF input and RF output signals. A single switched IF input and RF
output is provided to and from the online upconverter. The transfer switches are
contained in the TSM installed in the online upconverter. When a fault occurs in the
online upconverter, the TSM is de-activated to switch out the online upconverter, and
switch the IF input and RF output to the backup upconverter. Figure B-1 depicts the
cable connections between the upconverters. Figure B-2 shows the block diagram of
this 1:1 redundant upconverter configuration.
o Dual Source IF Input Configuration: Two IF inputs – IF Input #1 (priority) and IF Input #2
– are switched in the TSM to provide redundant operation of the upconverters. The
upconverters provide two switched RF outputs – RF Output #1 (priority) and RF Output
#2. If Upconverter #1 faults, Upconverter #2 backs up the priority channel when IF Signal
#2 and RF Signal #2 are not operational. Figure B-5 depicts the cable connections
between the upconverters. Figure B-6 shows the block diagram of the 1:1 redundant,
dual source RF input, upconverter configuration.
o IF and RF switches in the TSM are used to switch the IF input and RF output of a faulted
online upconverter to the backup upconverter. The IF input and RF output to the
redundant upconverter subsystem is connected to online upconverter #N. Figure B-7
depicts the cable connections between the upconverters. Figure B-8 shows the block
diagram for this 1:N redundant "Daisy Chain" upconverter configuration.
B–3
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
Figure B-1. 1:1 Redundant Configuration –Single Source IF Input with IOM-XX and TSM-XX
Installed
Figure B-2. 1:1 Redundant Configuration Diagram – Single Source RF Input with IOM-XX
and TSM-XX Installed
Figure B-3. 1:1 Redundant Configuration Diagram – Single Source RF Input with IOM-XX and
TSEQM-XX Installed
B–4
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
Figure B-6. 1:1 Redundant Configuration Diagram – Dual Source IF Input with IOM-XX and
TSM-XX Installed
B–5
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
Figure B-7. 1:N Redundant Configuration with IOM-XX and TSM-XX Installed
B–6
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
Figure B-8. 1:N Redundant Configuration Diagram with IOM-XX and TSM-XX Installed
B–7
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
STATUS
POWER ON ON LINE
REDUNDANCY-CONFIG?-ON---
TRANSMIT FAULT
-CONVERTER-#-BU---1:03--
REMOTE STORED FAULT
STATUS
POWER ON ON LINE
REDUNDANCY-CONFIG?-ON---
TRANSMIT FAULT
-CONVERTER-#-01----POL-1
REMOTE STORED FAULT
STATUS
POWER ON ON LINE
REDUNDANCY-CONFIG?-ON---
TRANSMIT FAULT
-CONVERTER-#-02----POL-1
REMOTE STORED FAULT
STATUS
POWER ON ON LINE
REDUNDANCY-CONFIG?-ON---
TRANSMIT FAULT
-CONVERTER-#-03----POL-1
REMOTE STORED FAULT
B–8
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
high-speed bus fault will result. This fault should clear when configuration is completed. At this
point, control of the redundant system is performed from the backup upconverter.
Figure B-10 shows the system configured for automatic (A) operation. In this mode, failure of an
online upconverter will automatically cause a switchover to the redundant unit to occur. In the
field, the simplest way to test this mode is to turn off an online unit. The AUTO/MANUAL
selection is made in the upconverter. The online units will report their status as shown in Figure
B-10.
B–9
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
Figure B-11 depicts the front panel displays after power has been turned off on Upconverter #1.
Note the ON LINE LED is illuminated on the backup upconverter. This indicates that the backup
is now providing the frequency translation in place of the online unit. As soon as power is
restored, Upconverter #1 will come back online.
B–10
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
B–11
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
Figure B-13 shows the front panel displays after the backup has forced upconverter 1 offline.
Note that the ON LINE LED allows the user to tell whether the backup is currently active and
which upconverter is being bypassed.
B–12
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
Monitoring and configuration of redundancy operations is possible using the 45xxA Web Server
Interface. Click the Config tab, and then select the Redundancy hyperlink to continue.
Click [Refresh] to update the page with its latest operating parameters.
Online Status
This read-only section identifies the unit’s status as ONLINE or OFFLINE.
Redundancy Mode
Use the drop-down list to select Redundancy Mode as OFF or ON, and then click [Change].
Chain Position
Use the drop-down list to assign the unit’s Chain Position as the Backup Unit, or Unit 01 through
Unit 12.
B–13
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
• Chain Length (Backup Unit): Use the drop-down list to select N/A, or 1:1 through 1:12.
• Polarity (Primary Down Converter): Use the drop-down list to select N/A, Single, or Dual.
Forced Backup
Use the drop-down list to set the Forced Backup as NONE, or Unit 01 through Unit 12, and then
click [Change].
• Auto Mode: Use the drop-down list to select a unit’s switching mode as Manual or
Automatic.
• Offset: Enter an offset adjustment value here. See Sect. 0 for additional information.
Step Description
1 Connect a signal source to the input and a power meter or spectrum analyzer to the output of the first
online upconverter.
2 Record the output power.
3 Force a backup of the first online unit and adjust the offset until the output power matches what was
recorded in Step 2.
4 Restore the online unit and repeat for the other online units.
B–14
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
Step Description
1 Force backup of faulted unit.
2 Turn the power switch on the inline upconverter rear panel to OFF, and remove the power cord from the
upconverter. DO NOT disconnect the RF and IF cables from the TSM.
3 Unscrew the mounting screws on the TSM first, and then unscrew the rack mounting screws on the front
panel of the upconverter.
4 From the rear of the inline upconverter, hold the TSM and push the upconverter to the front of the rack until
TSM is free of the upconverter chassis.
5 Remove the inline upconverter from the front of the rack.
Step Description
1 Power up the new unit on the bench.
2 Configure the new unit for the correct redundancy settings (Redundant = ON, Address = match old unit).
3 Power off the new unit.
4 Remove existing personality module from the new unit.
5 Carefully install the new unit into the rack. The existing module in the rack will be plugged into the new unit.
6 Power up the new unit and un-force the backup.
To remove a “Backup” upconverter for repair, the following procedure must be used:
Step Description
1 Turn the power switch on the backup upconverter rear panel to OFF, and remove the
power cord from the upconverter. Disconnect the RF and IF cables from the IOM.
2 Unscrew the rack mounting screws on the front panel of the backup upconverter.
3 Remove the backup upconverter from the front of the rack.
B–15
UT-4500-A Series Upconverters Revision 1
Appendix B MN-UT4500A
Notes:
B–16
Appendix C. MAINTENANCE A ND
TROUBLESHOOTING
C.1 Overview
This appendix serves to assist operator and maintenance personnel in the checkout,
maintenance and troubleshooting of the UT-4500-A Series Upconverters.
Comtech EF Data recommends that spare replacement converters be used to replace converters
removed from the system for maintenance. Troubleshooting procedures are provided for fault
isolation to the module level.
The input and output signals, the interconnecting cables and the location of the modules are as
shown in Figure C-1.
Figure C-1. Upconverter Signal and Interconnecting Cable Diagram (with Transmit Switch
Module [TSM])
C–1
UT-4500-A Series Upconverters Revision 1
Appendix C MN-UT4500A
To prepare for checkout, review the rack mounting information provided in Chapter 2.
INSTALLATION. Operations via the front panel (i.e., use of the menu system, keypad, and VFD)
are explained in detail in Chapter 5. FRONT PANEL OPERATION.
C.2.2 Troubleshooting
Upconverter operating problems can be identified by first observing the LED status indicators on
the front panel. When a fault condition is indicated, or and marginal performance tolerance
condition exists, the specific fault or faults can be identified via the FAULTS menu branch,
accessible via front panel operation. See Sect. 5.3.3 FAULTS in Chapter 5. FRONT PANEL
OPERATION for more information about viewing current or stored faults.
Upconverter operational status screens are available via the MONITOR menu branch. See Sect.
5.3.2 MONITOR in Chapter 5. FRONT PANEL OPERATION for more information.
C–2
UT-4500-A Series Upconverters Revision 1
Appendix C MN-UT4500A
14 VDC: A fault ("FT") indicates a voltage level exceeding ± 10% of the power supply voltage.
The 14 VDC is developed in the modules. Check the output of the 15 VDC Power Supply
Module, check for other module faults, and check all connections. If the fault still exists, remove
the converter and return it to Comtech EF Data for repair.
VCC (+5 VDC): A fault ("FT") indicates a voltage level exceeding ± 10% of the power supply
voltage. The 5 VDC is developed in the modules. Check the output of the 15 VDC Power Supply
Module, check for other module faults, and check all connections. If the fault still exists, remove
the converter and return it to Comtech EF Data for repair.
Fine Loop Detect: A fault (“FT”) indicates that the fine loop is not locked. Check all connections to
the converter module to make sure they are secure. If the fault still exists, remove the Fine Step
Module and return it to Comtech EF Data for repair.
C–3
UT-4500-A Series Upconverters Revision 1
Appendix C MN-UT4500A
When installing an I/O Module into the converter rear panel, DO NOT use a
screwdriver to tighten the module mounting thumbscrews – these screws are
designed to be hand-tightened only.
C.3 Spares
Comtech EF Data recommends field maintenance replacement at the RF converter level, and
that the converter is returned to Comtech EF Data for repairs. However, for field replacement of
the converter modules, contact Comtech EF Data for the correct spares for and particular
converter.
C–4
METRIC CONVERSIONS
Units of Length
1 inch 25.4 2.54 1 0.0833 0.0278 0.0254 2.54 x 10-5 1.578 x 10-5
1 mile 1.609 x 106 1.609 x 105 6.336 x 104 5280 1760 1609 1.609 1
Temperature Conversions
Units of Weight