The document calculates the load and sizing requirements for 8 branch circuits in a building. It first determines the load and wire sizing for general lighting and convenience outlets. It then calculates the load and wire sizing for other circuits including air conditioning, water pumps, water heaters and a cooking range. Finally, it determines the total load, ampacity required for the service entrance, wire sizing and circuit breaker rating.

Uploaded by

Marcelo Condino
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
98 views

Computation of Loads

The document calculates the load and sizing requirements for 8 branch circuits in a building. It first determines the load and wire sizing for general lighting and convenience outlets. It then calculates the load and wire sizing for other circuits including air conditioning, water pumps, water heaters and a cooking range. Finally, it determines the total load, ampacity required for the service entrance, wire sizing and circuit breaker rating.

Uploaded by

Marcelo Condino
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 7

COMPUTATION OF LOADS

A. GENERAL LIGHTING AND CONVENIENCE LOAD

BRANCH CIRCUIT NO. 1 - LIGHTING OUTLET

IFL = 100 WATTS X NO. OF OUTLETS


230V

IFL = 100 WATTS X 12 OUTLETS


230V

IFL = 1200 WATTS


230V

IFL = 5.22A

SIZE OF WIRE: USE 2-2.0MM^2 TW CU. STRANDED WIRE.


SIZE OF CONDUIT: USE 1-15MM DIAMETER PVC PIPE.
SIZE OF CIRCUIT BREAKER: USE 1-15AT, 50AF, 10KAIC, 2P, P.I,
@230V

BRANCH CIRCUIT NO. 2 - LIGHTING OUTLET

IFL = 100 WATTS X NO. OF OUTLETS


230V

IFL = 100 WATTS X 10 OUTLETS


230V

IFL = 1000 WATTS


230V
IFL = 4.35A

SIZE OF WIRE: USE 2-2.0MM^2 TW CU. STRANDED WIRE.


SIZE OF CONDUIT: USE 1-15MM DIAMETER PVC PIPE.
SIZE OF CIRCUIT BREAKER: USE 1-15AT, 50AF, 10KAIC, 2P, P.I,
@230V

BRANCH CIRCUIT NO. 3 - CONVENIENCE OUTLETS

IFL = 180 WATTS X NO. OF OUTLET X 2


230V

IFL = 180 WATTS X 8 OUTLETS X 2


230V

IFL = 2880 WATTS


230V

IFL - 12.52A

SIZE OF WIRE: USE 2-3.5MM^2 TW CU. STRANDED WIRE.


SIZE OF CONDUIT: USE 1-15MM DIAMETER PVC PIPE.
SIZE OF CIRCUIT BREAKER: USE 1-20AT, 50AF, 10KAIC, 2P, P.I,
@230V

BRANCH CIRCUIT NO. 4 - CONVENIENCE OUTLETS

IFL = 180 WATTS X NO. OF OUTLET X 2


230V

IFL = 180 WATTS X 8 OUTLETS X 2


230V
IFL = 2880 WATTS
230V

IFL - 12.52A

SIZE OF WIRE: USE 2-3.5MM^2 TW CU. STRANDED WIRE.


SIZE OF CONDUIT: USE 1-15MM DIAMETER PVC PIPE.
SIZE OF CIRCUIT BREAKER: USE 1-20AT, 50AF, 10KAIC, 2P, P.I,
@230V

APPLICATION OF DEMAND FACTOR

BRANCH CIRCUIT NO. 1 - 1200 WATTS


BRANCH CIRCUIT NO. 2 - 1000 WATTS
BRANCH CIRCUIT NO. 3 - 2880 WATTS
BRANCH CIRCUIT NO. 4 - 2880 WATTS
SUBTOTAL = 7960 WATTS

FIRST 3000VA @ 100% D.F = (3000VA) (100%) = 3000VA


REMAINING VA @ 35% DF = 7960VA - 3000VA = 4960VA
= (4960VA) (35%) = 1736 VA
TOTAL = 3000VA + 1736VA
= 4736VA

B. OTHER LOADS

BRANCH CIRCUIT NO. 5 - ACU

1-1.5HP ACU - 10A X 230V @100% DF = 2300VA

IFL = 2300VA
230V
IFL = 10A

SIZE OF WIRE: USE 2-3.5MM^2 AND 1-2.0MM^2 TW CU. STRANDED


WIRE.
SIZE OF CONDUIT: USE 1-15MM DIAMETER PVC PIPE.
SIZE OF CIRCUIT BREAKER: USE 1-30AT, 50AF ,10KAIC, 2P, P.I, @
230V.

BRANCH CIRCUIT NO. 6 - WATER PUMP

1-1HP ACU - 8A X 230V @100% DF = 1840VA

IFL = 1840VA
230V

IFL = 8A

SIZE OF WIRE: USE 2-3.5MM^2 AND 1-2.0MM^2 TW CU. STRANDED


WIRE.
SIZE OF CONDUIT: USE 1-15MM DIAMETER PVC PIPE.
SIZE OF CIRCUIT BREAKER: USE 1-30AT, 50AF ,10KAIC, 2P, P.I, @
230V.

BRANCH CIRCUIT NO. 7 - WATER HEATER

1-2.76KW WATER HEATER @100% DF = 2760VA

IFL = 2760VA
230V

IFL = 12A
SIZE OF WIRE: USE 2-3.5MM^2 AND 1-2.0MM^2 TW @ 60 ℃ CU.
STRANDED WIRE.
SIZE OF CONDUIT: USE 1-15MM DIAMETER PVC PIPE.
SIZE OF CIRCUIT BREAKER: USE 1-30AT, 50AF ,10KAIC, 2P, P.I, @
230V.
BRANCH CIRCUIT NO. 8 - COOKING RANGE

1-12000VA COOKING RANGE @80% DF = 9600VA

IFL = 9600VA
230V

IFL = 41.73A

SIZE OF WIRE: USE 2-8.0MM^2 AND 1-5.5MM^2 THHW @90 ℃ CU.


STRANDED WIRE.
SIZE OF CONDUIT: USE 1-20MM DIAMETER EMT PIPE.
SIZE OF CIRCUIT BREAKER: USE 1-60AT, 50AF ,10KAIC, 2P, P.I, @
230V.

TOTAL NET COMPUTED LOAD

GENERAL LIGHTING AND CONVENIENCE LOAD - 4736VA


BRANCH CIRCUIT NO. 5 - 2300VA
BRANCH CIRCUIT NO. 6 - 1840VA
BRANCH CIRCUIT NO. 7 - 2760VA
BRANCH CIRCUIT NO. 8 - 9600VA
TOTAL NET COMPUTED LOAD = 21236VA
AMPACITY OF SERVICE ENTRANCE

TOTAL CURRENT = 21236VA


230V

= 92.33A

AMPACITY OF SE = (125%) (HRM) + (TNCL - HRM)


230V

= 1.25 (2300VA) + 21236VA - 2300VA


230V

= 2875VA + 18936VA
230V

= 21811VA
230V

= 94.83A

SIZE OF WIRE: USE 2-30MM^2 and 1-22mm^2 THHW @90 ℃ CU.


STRANDED WIRE.
SIZE OF CONDUIT: USE 1-25MM DIAMETER IMC

CB RATING = (250%)(HRM) + (TNCL - HRM)


230V

= (2.5)(2300VA) + 21236VA - 2300VA


230V

= 5750VA + 18936VA
230V

= 24686VA
230V

= 107.33A

SIZE OF CIRCUIT BREAKER: USE 1-140AT, 200AF, 50KAIC, 2P , P.I @


230V