Power JB SPECIFICATION

S.No Description Content Supplier Compliance (Y/N)


Power JB (tag to be provided later)
1 Name & Qty. Qty :- 12 nos. as per drawing
2 Suitable for voltage 400V AC, 60Hz, Three phase.
3 Bus bar rating As per drawing.
Bus bar 1. Suitable for 3 Phase four wire connection.
arrangement for incoming and
outgoing connections. 2.R, Y, B (for phases) ,Black (neutral) . Coloured heat shrinkable insulating
sleeves shall be provided on respective bus bar.

3.Direct access or accidental contact to bus bars and


primary connection shall not be possible.

4.Bus bar extension for each incoming and outgoing cable with disconnection
4 facility.
5 Material for bus bar Electrolytic copper
6 Bus bar size As per requirement.

1.The junction boxes shall be constructed from cold rolled


sheet of suitable thickness and shall be made water tight
enclosure by means of rubber gasket.

2.The junction boxes shall be designed for wall/stand


mounting and shall be complete with all necessary
provisions for fixing and shall be free from all wrap and
twist.

3.Access to all components and connection shall be


available from the front.

4.The front of junction boxes shall be in the form of hinged


7 Construction door.
Incoming cable entry shall be provided from left side with
suitable gland plates of minimum 2.5mm thickness for
following:
1. Incomer cable - as shown in the drawing.

Outgoing cable entry shall be provided from bottom with


suitable gland plates of minimum 2.5mm thickness for
following:
1.Outgoing cable - as shown in the drawing.

Sufficient space shall be provided for accommodating of


8 Cable entry incoming and outgoing cable and cable termination.
9 IP protection. IP55
10 Painting and surface finish. RAL 7004 (85 ) micron avg
JB shall be fabricated with 2.5 mm cold rolled sheet steel
enclosure.
Door cover shall be fabricated with 2.0 mm cold rolled
sheet steel enclosure.
11 Sheet material thickness.
Two nos. earthing terminal for connecting earthing flat of
12 Earthing points size 25mm x6mm Cu shall be provided.
1. The bus bar support shall be of moulded glass,
reinforced thermosetting plastics (or) Fiberglass
Reinforced Plastic (FRP) insulators.

13 Bus bar support insulator 2. Number of support per bus bar: As per requirement (03 minimum)

Each JB shall be of following dimension:-


1. Depth : To be provided by vendor
2.Height : To be provided by vendor
3.Width : To be provided by vendor
4. JB should have proper arrangement at back side for
mounting on C-channel with nut bolts.

14 Dimensional requirements of JB. GA dwg. to be provided by the vendor.


15 Anchor,bolt with nut washers and lock nut. To be provided as per requirement.
16 Corrosivity Category C4-M as per ISO 12944-2
17 Area Classification Safe
18 Design,Manufacturing & Test Standards IEC 61439, IEC 60947
4 runs :- (1 for each ph + 1 for neutral)
8 runs :-(2 for each ph + 2 for neutral)
28 runs :-(7 for each ph + 7 for neutral)
19 Cable data

30% Spare termination to be considerd.


load = 400kw 400V/60HZ,10 termination points of each phase are required,JB quantity =18pcs
load = 400kw 400V/60HZ,8 termination points of each phase are required ,JB quantity =34pcs
load = 400kw 400V/60HZ,4 termination points of each phase are required ,JB quantity =116pcs