Instrumentation Lab Manual-24-37
Instrumentation Lab Manual-24-37
Instrumentation and
Measurement Lab
Page 1
Objectives:
✓ To get familiarized with the different types of electrical wiring standards and cables.
✓ To learn about basic working principle and application of a megger.
Equipment Required:
✓ Megger (manual type) [Qty = 1]
✓ Wires to be tested
Theory:
Part 1: Electrical Wiring Standards and Cables:
The wiring of a building consists of interconnections between associated devices such as
switches, meters, light fittings and other electrical load. Early electrical systems used single
conductor wires. These days, electrical wiring is done with multi-core cables because of their
convenience of use. The mostly commonly used metal for wires is copper, due to its efficiency
as a conductor. The wire also comes in aluminum and aluminum clad with copper, but these
are not efficient in conducting current. Wires and cables are rated by the circuit voltage,
current, temperature and environmental conditions (moisture, sunlight, oil, chemicals) in
which they can be used.
Wiring safety codes vary by country and the International Electro-Technical
Commission (IEC) is attempting to standardize wiring amongst member countries. The
standard wire gauge (SWG) and American wire gauge (AWG) are wire gauge systems,
which are used to represent the thickness of the wire in jump rings. Wire size standards are
important as they provide an ease to remember numerical chart of commonly used wire sizes.
The problem with standards is that they are not compatible with each other.
Figure 2.1
When it comes to the actual cable sizes, the two are actually not equivalent in size. In
general, an SWG wire would be bigger than an AWG wire of the same gauge. For example,
with a gauge value of 1, an SWG wire would have a diameter of 0.3 inches, while an AWG
wire would have a diameter of 0.2893. The size of the wire is quite important not only
because it adds to the strength of the wire, but because it directly correlates to the amount of
Page 2
current, it can carry. If you use a wire, that is too small for the current to pass, the wire would
eventually heat up and lead to fires. AWG system of measurements is in inches whereas
AWG is different from the SWG system which uses the metric system of measuring. When
looking at the Table 2.1, there are slight differences in the calculations between the two
systems. Especially relevant is the difference that can be seen between the 12 and 24 gauges.
These are very common sizes of wire and the chart shows a very drastic difference amongst
the size measurements.
Table 2.1
Electric Cables:
The generation, transmission, and distribution of power involve electrical apparatus and
components to carry electrical energy from its generating site to where it is utilized. An
important part of this power system is the cable system that is used exclusively to carry
power from the main substations to secondary substations at load centers. A cable is an
Page 3
assemblage of two or more wires running side by side and bonded, twisted or braided
together to form a single assembly. The assembly is used for transmission of electrical power.
Structure/Composition of Electric Cables:
The structure of cables consists of following parts.
i. Conductor
ii. Insulation
iii. Lead Sheath
iv. Bedding
v. Armouring
vi. Serving
Page 4
2. Insulation:
Insulation is a protective covering around the cable, which prevents it from damage
caused due to water, oil and other chemicals. Moreover, it prevents the leakage of current and
damages due to bending.
Page 5
4. Bedding:
Bedding is provided to protect the metallic sheath from corrosion and from mechanical
damage during handling. It is a fibrous material like jute or hessian tape.
5. Armouring:
It consists of two or more layers of galvanized steel wire or steel tape, which is applied
over bedding. The purpose is to protect the cable from mechanical injury while laying or
handling it.
Page 6
Classification of Cables:
Cables can be classified into following categories:
i. Power cables
ii. Networking cables
1. Power Cables:
A power cable is an assembly of two or more electrical conductors, usually held together
with an overall sheath. The assembly is used for transmission of electrical power. Power
cables may be installed as permanent wiring within buildings, buried in the ground, run
overhead, or exposed.
Classification of Power Cables:
The classification of these cables can be done on the basis of several criteria.
a. On basis of voltages
b. On basis of core
c. On basis of armouring
A. Classification of power cables on basis of voltages:
Following are the types of power cable on basis of voltages:
i. Low tension cables: It can transmit voltages up to 1-kV.
ii. High tension cables: It can transmit voltages up to 11-kV.
iii. Super tension cables: It can transmit voltages from 22-kV to 33-kV.
iv. Extra high tension cables: It can transmit voltages 33-kV to 66-kV.
v. Extra super voltage cables: These cables are used for applications with voltage
requirement above 132-kV.
B. Classification of power cables on basis of cores:
i. Single Core Cable:
Single core cables are made up of a single conductor covered by PVC insulation. The
conductor is made of mostly copper or aluminum. These are widely used for domestic
purposes.
Page 7
ii. Double (2) Core Cable:
In two core cable, two conductors are covered by PVC insulation. The cable only has two
cores being live and neutral. This type of cable is used to connect small appliances which are
double insulated and need no earth.
Page 8
why, these cable is often used for external use. These cables are widely used for underground
cabling purposes.
Page 9
together. It is also used for connecting computers in local area networks is widely used in
cable broadband.
Page 10
electric current through device, while we are testing. The equipment is basically used for
verifying the electrical insulation resistance of insulators, electric wires and cables, motor and
generator windings etc. Similarly, the open and short circuit tests of electric wiring and
windings can also be carried out using megger. Not necessary it shows us exact area of
electrical puncture, but shows the amount of leakage current and level of moisture within
electrical equipment/winding/system.
Insulation Resistance (IR):
The insulation resistance depends upon the temperature, humidity, moisture, cleanliness,
age, test voltage, and duration of its application. It also get impacted negatively due to the
presence of electrical and mechanical stress, so it becomes very necessary to check the
insulation resistance of equipment/wiring at a constant regular interval to avoid any electrical
shock or fatal measure. There are two major types of a megger including automatic
(electronic) and manual type (hand operated) meggers. In a manual type megger, testing
voltage is produced by hand operated DC generator whereas battery/electronic voltage
charger is provided in electronic megger for same purpose. In this lab session, we will study
and use manual type megger (as shown in Figure 2.17) to find the insulation resistance.
Page 11
3. Wire Leads: Two wire leads are provided which can be connected to the electrical
system which needs to be checked.
Construction of a Manual type Megger:
Figure 2.18 shows the construction of a manual type megger. The important construction
features of manual type megger consist of following parts:
i. Deflecting and Control coil: These are connected parallel to the generator, mounted at
right angle to each other and maintain polarities in such a way to produced torque in
opposite direction.
ii. Permanent Magnets: Produce magnetic field to deflect pointer with North-South pole
magnet.
iii. Pointer: One end of the pointer connected with coil another end deflects on scale from
infinity to zero.
iv. Scale: A scale is provided in front-top of the megger from range ‘zero’ to ‘infinity’, enable
us to read the value.
v. D.C Generator or Battery connection: Testing voltage is produced by hand operated DC
generator for manual operated megger. Battery / electronic voltage charger is provided for
automatic type megger for same purpose.
vi. Pressure coil resistance and Current coil resistance: Protect instrument from any
damage because of low external electrical resistance under test.
Figure 2.18
Page 12
It consists of a hand-driven DC generator and a direct reading ohm meter. There are two
coils; pressure coil (control) and current coil (deflecting). Both the coils are fixed together at
some angle. They are free to rotate about a common axis between the poles of a permanent
magnet. The coils are connected in the circuit through flexible leads (or ligaments), which
exerts no restoring torque on the moving system. The current (or deflecting) coil is connected
in series with a resistance R1 between the generator terminal and the test line terminal. The
deflecting circuit resistance R1 limits the current and controls the range of the instrument.
The pressure (or control) coil is connected across the generator terminals in series with a
compensating coil and protection resistance (or control circuit resistance) R2. Compensating
coil is connected to obtain better scale proportions. A guard ring is provided to shunt leakage
current over the test terminals or within the instrument itself. The terminal “G” known as
guard terminal is provided by means of which the guard ring can be connected to a guard
wire on the insulation under test. The test voltage generated by the generator is usually 250V,
500V or 1000V. Meggers of 250V are used for medium voltage appliances and those of
higher voltage like 1-kV, 2.5-kV, etc. for high voltage appliances. The test leads or prongs
should have proper insulation and should be handled with care to avoid shock.
Working of a Megger:
Before making connections, the two leads should be touched together, and the crank
handle turned gently at a slow speed the pointer should indicate zero resistance. Paint,
enamel, dirt, etc. should be removed from the surface where the “earth” terminal of the
megger is connected. The resistance under test is connected between test terminals (L and G),
the generator handle is then steadily turned at a uniform speed till the pointer gives a steady
reading. The working of a megger insulation tester can be fully understood from the
following steps:
i. When the test terminals are open, the resistance to be measured is infinite. In case the
generator handle is rotated, the generated voltage sends current through the potential coil
and no current flows through the current coil. Therefore, the moving system rotates in
such a direction that the pointer rests at the “infinity” end of the scale.
ii. If the test terminals are short-circuited, and the generator is operated, it sends a large
current through the current coil, and a very small current flow through the potential coil.
Therefore, the resultant torque so produced turns the pointer to the “zero” end of the
scale.
iii. If the unknown resistance to be measured is connected between test terminals, a
considerable amount of current flows in both the coils. The actual position taken up by
the pointer depends upon the ratio of currents in the two coils i.e., upon the unknown
resistance.
Page 13
iv. A test voltage of 500V or 1000V is generated by hand operated generator and a constant
voltage source is maintained to test the insulation having low resistance.
v. Two pressure coils are rotated in the anticlockwise direction, whereas the current coil is
rotated in the clockwise direction.
vi. With the unknown resistance connected in the circuit, the moving coil pointer becomes
stable.
vii. The pressure coil and current coil balance the pointer and set it in the middle of the scale.
The deflection of pointer is directly proportional to the voltage applied to the external
circuit and the ration of currents in the two coils i.e. Unknown resistance.
viii. With an increase of potential voltage across the external circuit, the deflection of the
pointer increases; and with an increase of current, the deflection of pointer decrease so
the resultant torque on the movement is directly proportional to the potential difference
and inversely proportional to the resistance.
a. When the external circuit is open, torque due to voltage coil will be maximum and the
pointer will read “infinity”. When there is short circuit the pointer will read “0”.
Meaning of “Zero” and “Infinity” reading:
When a magger is showing “zero” value while measuring insulation resistance, it is an
indication of insulation failure or short circuit whereas, when it is showing “infinity” reading,
it means that the unknown insulation resistance, which is being measured, has very high
value.
Procedure:
a. Take a piece of electric wire having good quality insulation and measure its insulation
resistance using manual type (hand operated) megger as instructed by your teacher.
Comment on your observations regarding megger’s reading.
b. Take a piece of electric wire having bad or damaged insulation and measure its
insulation resistance using manual type megger as instructed by your teacher. Comment
on your observations regarding megger’s reading.
Page 14