Victaulic Flexible Hose Connecting To Dry Barrel Sprinkler
Victaulic Flexible Hose Connecting To Dry Barrel Sprinkler
Victaulic Flexible Hose Connecting To Dry Barrel Sprinkler
that the main lines are WET Lines so the flexible pipe will
be connected to a wet line from one side and a dry sprinkler
Victaulic® VicFlex™ Sprinkler Fittings
from the other side)
ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.
victaulic.com
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
1
victaulic.com
Brackets
• Style AB2 for suspended and hard-lid ceilings, allows for vertical sprinkler adjustment, and installation before
most ceiling tiles in place
• Style AB3 for surface mount applications, wood, metal and block walls or ceilings
• Style AB4 for hard-lid ceilings with hat furr ing channel grid systems, allows for vertical sprinkler adjustment
• Style AB5 for hard-lid ceilings, allows for vertical sprinkler adjustment
• Style AB7 for suspended and hard-lid ceilings
• Style AB7 Adjustable for suspended and hard-lid ceilings
• Style AB10 for Armstrong® TechZone™ ceilings
• Style AB11 for lay-in panel suspended t-grid ceilings or drywall suspended t-grid ceilings, allows for low profile
installations (use only with 90° low profile elbows)
• Style AB12 for suspended and hard-lid ceilings, allows for vertical sprinkler adjustment, and allows for low profile
installation down to 4"/100mm
• Style ABBA bracket for suspended, exposed, and hard-lid ceilings
• Style ABMM bracket for surface mount and stand off-mount applications, wood, metal and block walls, or ceilings
and hard-lid ceilings
• Strut channel and pipe clamp, not supplied by Victaulic
Maximum Working Temperature
• 225°F/107°C
• 150°F/65°C (No. 116 CPVC Adapter)
Maximum Working Pressure
• 200 psi/1375 kPa (FM Approval)
• 175 psi/1206 kPa (cULus Listed)
• 1600 kPa/232 psi (VdS/LPCB Approved)
• 1.4 MPa (CCC Approval)
• 175 psi/1206 kPa (No. 116 CPVC Adapter)
Minimum Bend Radius
• 7"/178 mm (FM/CCC Approval)
• 3"/76.2 mm (cULus Listed)
• 3"/76.2 mm (VdS/LPCB Approved)
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 2
victaulic.com
2.0 CERTIFICATION/LISTINGS
Bolts/Nut: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A 449
and physical requirements of ASTM A 183.
Linkage: CrMo Alloy Steel zinc electroplated per ASTM B633 Zn/Fe 5, Type III Finish.
No. 116 Adapter Fitting: CPVC and Brass
Seal: Victaulic EPDM
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 3
victaulic.com
4.0 DIMENSIONS
Product Details - Series AH1 Braided Hose
Item Description
1 Flexible Hose
2 2 Isolation Ring
5 1 6 7 3 4 8 3 Gasket
4 Nut
5 Branch Line Nipple
6 Braid
A 7 Collar/Weld Fitting
B 8 Reducer
Hose Length A B
inches inches inches
mm mm mm
31 25.3 31.0
790 641 790
36 31.3 36.0
915 794 915
48 42.3 48.0
1220 1073 1220
60 54.3 60.0
1525 1378 1525
72 66.3 72.0
1830 1683 1830
Series AH1-CC
Item Description
1 Flexible Hose
5 2 Isolation Ring
2 3 4 3 Gasket
1 6 7 8
4 Nut
5 Style 108 Coupling
6 Braid
7 Collar/Weld Fitting
A 8 Reducer
B
Hose Length A B
inches inches inches
mm mm mm
31 24.5 29.8
790 622 757
36 29.5 34.8
915 749 884
48 41.5 46.8
1220 1054 1189
60 53.5 58.8
1525 1359 1494
72 65.5 70.8
1830 1664 1798
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 4
victaulic.com
–
4–
–
3–
–
2–
–
1–
–
–
–
–
–
–
–
–
5.75"/140 mm straight reducer
Optional Reducers
2.62"/
66.5 mm
2.62"/
66.5 mm
7.25"/
184.2 mm
5.50"/ 6.57"/
139.7 mm 166.9 mm 5.00"/
127.0 mm
9.0"/229 mm straight reducer 4.83"/ 3.25"/
122.7 mm 82.6 mm
13.0"/330 mm straight reducer Short 90° elbow reducer Long 90° elbow reducer
NOTE
• The Short 90° elbow reducer is typically used with concealed sprinklers while the longer 90 elbow is typically used in the installation of recessed pendent
sprinklers.
• FM/VdS Approved only.
Low Profile
5.25"/
4.59"/ 133 mm
3.50"/ 3.63"/ 116 mm
2.84"/ 89 mm 92 mm
1.88"/ 72 mm
48 mm
1.4"/ 1.4"/
36 mm 36 mm
NOTES
• E to E is 3.0"/76.0 mm
• The No. 116 CPVC Adapters have 2 ft (0.6 m). EQL of 1" Schedule 40 pipe
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 5
victaulic.com
4.2 DIMENSIONS
Style AB2 3
• Suspended Ceilings
• Hard-Lid Ceilings
Item Description 2
Style AB3
• Surface Mount Applications
• FM/LPCB Approved
Style AB4
1
• Hard-Lid Ceilings with Hat furring
channel grid system
2
Item Description 3
1 24"/610 mm or 48"/1220 mm Square Bar
2 Patented Vertically Adjustable Center Bracket
3 End Bracket for Hat Furring Channel
3
NOTE
• Both sizes FM/VdS/LPCB approved, cULus listed
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 6
victaulic.com
4.3 DIMENSIONS
VicFlex Brackets
Style AB5 3
• Hard-Lid Ceilings
Item Description
1 24"/610 mm or 48"/1220 mm Square Bar 2
2 Patented Vertically Adjustable Center Bracket
3 End Bracket
NOTE 1
Style AB7
• Suspended Ceilings 3
• Hard-Lid Ceilings
Item Description
2
1 24"/610 mm or 48"/1220 mm Square Bar
2 Patented 1-Bee2® Center Bracket
1
3 End Bracket
NOTE
• Both sizes FM/VdS/LPCB approved.
• Hard-Lid Ceilings
Item Description 2
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 7
victaulic.com
4.4 DIMENSIONS
VicFlex Brackets
Style AB10 3
2
• Suspended ceilings 1
• Armstrong® TechZone™ 3
Item Description
1 6"/152 mm Square Bar*
2 Patented 1-Bee2® Center Bracket
3 End Bracket
NOTE
• FM/VdS/LPCB approved, cULus listed.
Style AB11 3
• Suspended ceilings
• Hard-Lid ceilings
2
Item Description
1 24"/610 mm or 48"/1219 mm Square Bar
2 Patented 1-Bee2® Center Bracket 1
3 End Bracket
3
NOTE
• FM/VdS Approved, cULus listed.
Style AB12 2
• Suspended ceilings
• Hard-Lid ceilings
Item Description
1 Style AB12 Bracket Body 1
2 #2 Square Drive Set Screw
NOTE
• FM/VdS Approved.
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 8
victaulic.com
4.5 DIMENSIONS
VicFlex Brackets
Style ABBA 1
• Floor-above mount 3
• Cantilever mount
• Temporary mount in exposed ceilings
2
Item Description
1 Style ABBA Mounting Plate
2 Style ABBA Square Bar
Cap Screw, Serated Flange, M6 x 1 x 20,
3
T25 Torx Drive Recessed
5
4
4 Style ABMM Bracket Body
Cap Screw, Serated Flange, M6 x 1 x 15.24,
5
T25 Torx Drive Recessed
Style ABMM
• Surface mount 2
• Stand-off mount
Item Description
1 Style ABMM Bracket Body
1
Cap Screw, Serated Flange, M6 x 1 x 15.24,
2
T25 Torx Drive Recessed
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 9
victaulic.com
4.6 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB2 Bracket
R
See Table
L
Bracket Assembly
Style AB2
4.3"/ 23⁄8"/60.33 mm
111 mm
2"/50.80 mm
5/8"/15.9 mm
Typical
ceiling tile
1.7"/43 mm
Typical ceiling grid
Finished
surface
24"/610 mm or 48"/1219 mm
See note on Center
V2707 ¾"/19 MM MAX. RECESS V2707 MAX. EXTENSION
NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 10
victaulic.com
4.7 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB2 Bracket
R
See chart
A
See Chart
Bracket
Assembly
#10 Screw Style AB2 211⁄16"/68 mm
1.8"/45 mm max. hole
23⁄8"/60 mm
min. hole
2" × 4"
Stud 3½"/
89 mm
Finished 5/8"/16 mm
ceiling Typical
Typical 16"/406 mm C/C drywall
NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 11
victaulic.com
4.8 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB4 Bracket
R
See chart
A
See Chart
Bracket assembly
Style AB4
4.1"/ 23⁄8"/60 mm
Typical Hat 104 mm max. hole
Channel 2"/51 mm
#10 Screw grid min. hole
7⁄8"/23 mm
Finished
ceiling 5⁄8"/16 mm
Typical drywall
Typical 16"/406 mm C/C
NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 12
victaulic.com
4.9 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB5 Bracket
R
See chart A
See chart
Bracket
assembly
Style AB5 2.3"/
57 mm
23⁄8"/60 mm
2" × 4" max. hole
metal stud 2"/51 mm
35⁄8"/
92 mm min. hole
Finished 5/8"/16 mm
ceiling Typ. Drywall
Typical 16"/406 mm C/C
NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 13
victaulic.com
4.10 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB11 Bracket (LOW PROFILE SOLUTION)
23⁄8"/60 mm 211⁄16"/68 mm
Bracket max. hole max. hole
Assembly 2"/51 mm 23⁄8"/60 mm
A Style AB11 min. hole min. hole
See Chart 3.0"/
76 mm
1.7"/43 mm Finished
Typical 5/8"/15.9 mm ceiling face
ceiling grid Typical
ceiling tile
See Note 24"/610 mm or V27 V38
48"/1219 mm on center Pendent
NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 14
victaulic.com
4.11 DIMENSIONS
CLEARANCES ABOVE CEILING
Series AH1 Braided Hose and Style AB12 and ABBA Bracket
Suspended Ceiling Grid with Recessed Sprinkler Suspended Ceiling Grid with Recessed Sprinkler and
with Low Profile Short Elbow Straight 5.75"/140mm Reducer
Unfinished
Ceiling Face
11⁄8 inch/
29 mm
Nominal length
14"/355.6 mm
"A"
Unfinished See Table
11⁄8 inch/ Ceiling Face
29 mm 1⁄8 inch/
3 mm
NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.
4.12 DIMENSIONS
2.94"/
3.93"/
75 mm 0.28"/
100 mm 3.94"/
100 mm 7 mm
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 15
victaulic.com
4.13 DIMENSIONS
BRANCHLINE CLEARANCES
Series AH1 Braided Hose with female threaded outlet Series AH1-CC Braided Hose with grooved outlet
R
See chart R
See chart
A A
See chart See chart
Female Threaded
Weld Outlet
No. 142
Grooved Weld Outlet
2"/50 mm
2"/50 mm
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 16
victaulic.com
4.14 DIMENSIONS
BRANCHLINE CLEARANCES
Series AH1 Braided Hose with Style 922 threaded outlet Series AH1-CC Braided Hose with Style 922 grooved outlet
R
See chart
R
See chart
A A
See chart See chart
2"/50 mm 2"/50 mm
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 17
victaulic.com
4.15 DIMENSIONS
CLEARANCES ABOVE CEILING
Series AH1 Braided Hose and Style AB3 and ABMM Bracket
Surface Mount Application with Recessed Sprinkler
R
C
3¾"/
95.3 mm
B
A
23⁄8"/60 mm
max. hole
2"/51 mm
min. hole
Hose Clearances
Wall Thickness
"A"
4 6 8 10 2 4 6 8 10
100 150 200 250 50 100 150 200 250
Outlet Length 5.75 9 13 9 13 13 13 5.75 9 13 5.75 9 13 9 13 13 13
"B" 146.1 228.6 330.2 228.6 330.2 330.2 330.2 146.1 228.6 330.2 146.1 228.6 330.2 228.6 330.2 330.2 330.2
Hose 9.6 12.8 16.8 10.8 14.8 12.8 10.8 12.6 15.8 19.8 10.6 13.8 17.8 11.8 15.8 13.8 11.8
Clearance "C" 243 325 427 275 376 325 275 319 402 503 268 351 452 300 402 351 300
Bend Radius 7 8
"R" 175 200
NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.
• See installation instructions for mounting screw type and size.
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 18
victaulic.com
Maximum
Length of Equivalent Length Number of
Stainless Steel of 1"/33.7 mm 90° Bends at 3"/76.2 mm
Flexible Hose Outlet Size Sch. 40 Pipe (C=120) Bend Radius
inches
inches mm feet
mm type meters
½
52
15 3
15.8
31 Straight
775 ¾
55
20 3
16.8
Straight
½
63
15 4
19.2
36 Straight
900 ¾
66
20 4
20.1
Straight
½
78
15 4
23.8
48 Straight
1200 ¾
80
20 4
24.4
Straight
½
88
15 4
26.8
60 Straight
1500 ¾
90
20 4
27.4
Straight
½
112
15 5
34.1
72 Straight
1800 ¾
118
20 5
36.0
Straight
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 19
victaulic.com
Maximum
Equivalent Length Number of
of 1"/33.7 mm 90° Bends at 3"/76.2 mm
Hose Length Outlet Size Sch. 40 Pipe Bend Radius
inches inches feet
mm mm meters
½ 63
3
31 15 19.2
775 ¾ 65
3
20 19.8
½ 76
4
36 15 23.2
900 ¾ 76
4
20 23.2
½ 99
4
48 15 30.2
1200 ¾ 98
4
20 29.9
½ 108
4
60 15 32.9
1500 ¾ 102
4
20 31.1
½ 124
5
72 15 37.8
1800 ¾ 132
5
20 40.2
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 20
victaulic.com
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 21
victaulic.com
Maximum
Equivalent Number
Length of of 90° Bends
1"/33.7mm at 7"/178mm
Sch. 40 Pipe Bend Radius
inches/mm Imperial/S.I. inches/mm/type feet/meters
½"/15/Straight 53.8/16.4
31/775 5.6/8.1 2
½"/15/90˚ Elbow 53.8/16.4
½"/15/Straight 63.7/19.4
36/900 5.6/8.1 2
½"/15/90˚ Elbow 63.1/19.2
½"/15/Straight 87.9/26.8
48/1200 5.6/8.1 3
½"/15/90˚ Elbow 85.8/26.1
½"/15/Straight 112.2/34.1
60/1500 5.6/8.1 4
½"/15/90˚ Elbow 108.4/33.0
½"/15/Straight 136.5/41.6
72/1800 5.6/8.1 4
½"/15/90˚ Elbow 131.1/39.9
¾"/20/Straight 44.4/13.5
31/775 8.0/11.5 2
¾"/20/90˚ Elbow 47.6/14.5
¾"/20/Straight 55.6/16.9
36/900 8.0/11.5 2
¾"/20/90˚ Elbow 57.5/17.5
¾"/20/Straight 82.8/25.2
48/1200 8.0/11.5 3
¾"/20/90˚ Elbow 81.7/24.9
¾"/20/Straight 110.1/24.9
60/1500 8.0/11.5 4
¾"/20/90˚ Elbow 105.9/32.2
¾"/20/Straight 137.3/41.8
72/1800 8.0/11.5 4
¾"/20/90˚ Elbow 130.2/39.7
¾"/20/Straight 45.5/13.8
31/775 11.2/16.1 2
¾"/20/90˚ Elbow 47.1/14.3
¾"/20/Straight 66.3/20.2
36/900 11.2/16.1 2
¾"/20/90˚ Elbow 57.5/17.5
¾"/20/Straight 82.7/25.2
48/1200 11.2/16.1 3
¾"/20/90˚ Elbow 82.8/25.2
¾"/20/Straight 109.1/33.2
60/1500 11.2/16.1 4
¾"/20/90˚ Elbow 108.1/32.9
¾"/20/Straight 135.5/41.3
72/1800 11.2/16.1 4
¾"/20/90˚ Elbow 133.4/40.6
¾"/20/Straight 44.3/13.5
31/775 14.0/20.2 2
¾"/20/90˚ Elbow 46.4/14.1
¾"/20/Straight 55.5/16.9
36/900 14.0/20.2 2
¾"/20/90˚ Elbow 56.7/17.3
¾"/20/Straight 83.0/25.3
48/1200 14.0/20.2 3
¾"/20/90˚ Elbow 82.1/25.0
¾"/20/Straight 110.4/33.6
60/1500 14.0/20.2 4
¾"/20/90˚ Elbow 107.5/32.7
¾"/20/Straight 137.9/42.0
72/1800 14.0/20.2 4
¾"/20/90˚ Elbow 132.8/40.4
FM NOTES:
• Series AH1 has been tested and Approved by FM Global for use in wet, dry and preaction systems per NFPA 13, 13R, and 13D and FM data sheets 2-0, 2-5,
and 2-8. FM 1637 and Vds standards for safety include, but are not limited to, pressure cycling, corrosion resistance, flow characterisitics, vibration
resistance, leakage, mechanical and hydrostatic strength.
• EXAMPLE: A 48-inch hose installed with two 30° bends and two 90° bends is permitted and considered equivalent to the data in the table shown above. In
this example, the total number of degrees is 240°, which is less than the allowable 270°.
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 22
victaulic.com
Maximum
Equivalent Number
Length of Length of of 90° Bends
Stainless Steel Outlet 1"/33.7mm at 7"/178mm
Flexible Hose K-Factor Size Sch. 40 Pipe Bend Radius
inches/mm Imperial/S.I. inches/mm feet/meters
31/775 5.6/8.1 ½"/15 49.0/14.9 2
FM NOTES:
• Series AH1 has been tested and Approved by FM Global for use in wet, dry and preaction systems per NFPA 13, 13R, and 13D and FM data sheets 2-0, 2-5,
and 2-8. FM 1637 and Vds standards for safety include, but are not limited to, pressure cycling, corrosion resistance, flow characterisitics, vibration
resistance, leakage, mechanical and hydrostatic strength.
• Differences in equivalent lengths are due to varying test methods, per FM 1637 and VdS standards. Refer to these standards for additional information
regarding friction loss test methods.
• EXAMPLE: A 48-inch hose installed with two 30° bends and two 90° bends at a 7-inch bend radius is permitted and considered equivalent to the data in the
table shown above. In this example, the total number of degrees is 240°, which is less than the allowable 270°.
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 23
victaulic.com
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 24
victaulic.com
Equivalent Length
Length of Flexible Hose Straight Configuration Bend Configuration
mm meters meters
Model inches feet feet
790 4.78 5.80
AH1-31
31 15.7 19.0
915 5.59 10.15
AH1-36
36 18.3 33.3
1120 9.75 16.25
AH1-48
48 32.0 53.3
1525 12.15 22.94
AH1-60
60 39.9 75.3
1830 14.26 25.98
AH1-72
72 46.8 85.2
NOTE
• Friction loss data is in accordance with GB5135.16 tested at a flow rate of 114 liters per minute (30 gallons per minute).
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 25
victaulic.com
6.0 NOTIFICATIONS
WARNING
• These products shall be used only in fire protection systems that are designed and installed in accordance with
current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent
standards, and in accordance with applicable building and fire codes. These standards and codes contain impor-
tant information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc.
• The installer shall understand the use of this product and why it was specified for the particular application.
• The installer shall understand common industry safety standards and potential consequences of improper prod-
uct installation.
WARNING
• It is the responsibility of the system designer to verify suitability of 300-series stainless steel flexible hose for
use with the intended fluid media within the piping system and external environments.
• The effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate
on 300-series stainless steel flexible hose must be evaluated by the material specifier to confirm system life will
be acceptable for the intended service.
• It is the responsibility of the owner of a building or their authorized agent to provide the sprinkler system installer
with any knowledge that the water supply might be contaminated with or conducive to the development of micro-
biologically influenced corrosion (MIC), including as required by NFPA 13. Failure to identify adverse water quality
issues may affect the VicFlex product and void the manufacturer’s warranty.
Failure to follow these instructions could cause product failure, resulting in serious personal injury and/or
property damage.
Victaulic VicFlex Series AH1 and AH1-CC Flexible Sprinkler Fittings may be painted provided the paint is compatible
with stainless steel and zinc-plated carbon steel or ductile iron. Care should be taken to ensure the sprinkler and associated
escutcheon or coverplate are not painted.
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 26
victaulic.com
2X
2X Minimum Minimum
Minimum bend radius bend radius
bend radius
OR
Minimum OR
bend radius
90°
Minimum
bend radius Minimum
Minimum bend radius
bend radius
Minimum
bend radius
Minimum
bend radius
NOTE
• For out-of-plane (three-dimensional) bends, care must be taken to avoid imparting torque on the hose.
I-VicFlex-AB1-AB2-AB10
I-VicFlex-AB3
I-VicFlex-AB4
I-VicFlex-AB5
I-VicFlex-AB7
I-VicFlex-AB12
I-VicFlex-ABBA
I-VicFlex-ABMM
I-RES
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
victaulic.com 27