58 Pcs for Connetion to Dry Sprinkler Barrel (Please note

that the main lines are WET Lines so the flexible pipe will
be connected to a wet line from one side and a dry sprinkler
Victaulic® VicFlex™ Sprinkler Fittings
from the other side)

Series AH1 and AH1-CC Braided Flexible Hose 10.95

Series AH1 Series AH1-CC

1.0  PRODUCT DESCRIPTION

Available Sizes by Component


Series AH1 0.8"/DN20 ID Braided Hose: 31, 36, 48, 60, 72"/790, 914, 1220, 1525, 1830 mm. Note: length includes
adapter nipple and 5.75"/140 mm straight reducer.
Series AH1-CC 0.8"/DN20 ID Braided Hose: 31, 36, 48, 60, 72"/790, 914, 1219, 1525, 1830 mm. Note: length
includes captured coupling and 5.75"/140 mm straight reducer.
Connections
• From Branchline
• ¾”/20mm BSPT female thread (VdS only)
• 1”/25mm NPT or BSPT female
FEMALE Thread
THREAD
• 1”/25mm Grooved IGS (refer to Submittal 10.54 for additional IGS connections)
• No. 116 CPVC Adapter (1”/25mm Female CPVC Socket x 1”/25mm Grooved IGS)
• No. 142 Welded Outlet
• Style 922 Outlet-T
• Style 920N Mechanical-T Outlet
• No. 65 Grooved End of Run Fitting
• Hose Inlet
• 1”/25mm Grooved IGS
• 1”/25mm NPT or BSPT THREAD
MALE male thread
• ¾”/20mm BSPT male thread (VdS only)

ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.

System No. Location Spec Section Paragraph

Submitted By Date Approved Date

victaulic.com
10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.
1
victaulic.com

1.0  PRODUCT DESCRIPTION (CONTINUED)


• Sprinkler Reducer
• Sprinkler Connection: ½” and ¾”/15mm and 20mm NPT or BSPT
• Straight Lengths: 5.75”, 9”, 13”/140mm, 230mm, 330mm
• 90˚ Elbows
• Standard Short
• Low Profile Short
• Standard Long
• Low Profile Long
(Short elbows typically used with concealed sprinklers. Long elbows typically used with recessed pendent
sprinklers)

Brackets
• Style AB2 for suspended and hard-lid ceilings, allows for vertical sprinkler adjustment, and installation before
most ceiling tiles in place
• Style AB3 for surface mount applications, wood, metal and block walls or ceilings
• Style AB4 for hard-lid ceilings with hat furr ing channel grid systems, allows for vertical sprinkler adjustment
• Style AB5 for hard-lid ceilings, allows for vertical sprinkler adjustment
• Style AB7 for suspended and hard-lid ceilings
• Style AB7 Adjustable for suspended and hard-lid ceilings
• Style AB10 for Armstrong® TechZone™ ceilings
• Style AB11 for lay-in panel suspended t-grid ceilings or drywall suspended t-grid ceilings, allows for low profile
installations (use only with 90° low profile elbows)
• Style AB12 for suspended and hard-lid ceilings, allows for vertical sprinkler adjustment, and allows for low profile
installation down to 4"/100mm
• Style ABBA bracket for suspended, exposed, and hard-lid ceilings
• Style ABMM bracket for surface mount and stand off-mount applications, wood, metal and block walls, or ceilings
and hard-lid ceilings
• Strut channel and pipe clamp, not supplied by Victaulic
Maximum Working Temperature
• 225°F/107°C
• 150°F/65°C (No. 116 CPVC Adapter)
Maximum Working Pressure
• 200 psi/1375 kPa (FM Approval)
• 175 psi/1206 kPa (cULus Listed)
• 1600 kPa/232 psi (VdS/LPCB Approved)
• 1.4 MPa (CCC Approval)
• 175 psi/1206 kPa (No. 116 CPVC Adapter)
Minimum Bend Radius
• 7"/178 mm (FM/CCC Approval)
• 3"/76.2 mm (cULus Listed)
• 3"/76.2 mm (VdS/LPCB Approved)

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 2
victaulic.com

1.0  PRODUCT DESCRIPTION (CONTINUED)


Maximum Allowable Sprinkler K-Factors
• FM (½"/15mm reducer) K5.6/8,1 (S.I.), (¾"/20mm reducer) K14.0/20,2 (S.I.)
• cULus (½"/15mm reducer) K8.0/11,5 (S.I.), (¾"/20mm reducer) K14.0/20,2 (S.I.)
• VdS/LPCB (½"/15mm reducer) K5.6/8,1 (S.I.), (¾"/20mm reducer) K8.0/11,5 (S.I.)

2.0 CERTIFICATION/LISTINGS

LPS 1261: Issue 1.2


Cert/LPCB Ref. 1
 04l/02
104l/03

3.0  SPECIFICATIONS – MATERIAL


Series AH1
Flexible Hose: 300-series Stainless Steel
Collar/Weld Fitting: 300-series Stainless Steel
Gasket Seal: Victaulic EPDM
Isolation Ring: Nylon
Nut and Nipple: Carbon Steel, Zinc-Plated
Reducer (½ or ¾"): Carbon Steel, Zinc-Plated
Low Profile Elbows: Ductile Iron, Zinc-Plated
Brackets: Carbon Steel, Zinc-Plated
Series AH1-CC
Flexible Hose: 300-series Stainless Steel
Collar/Weld Fitting: 300-series Stainless Steel
Gasket Seal: Victaulic EPDM
Isolation Ring: Nylon
Coupling Retainer Ring: Polyethelene
Nut: Carbon Steel, Zinc-Plated
Reducer (½"/15 mm or ¾"/20 mm): Carbon Steel, Zinc-Plated
Low Profile Elbows: Ductile Iron, Zinc-Plated
Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade
65-45-15, is available upon special request.
Coupling Housing Coating:
• Orange enamel (North America, Asia Pacific).
• Red enamel (Europe).
• Hot dipped galvanized.
Gasket:1
Grade “E” EPDM (Type A)
FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of
Canada Limited, and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services
within the rated working pressure.
1 Services listed are General Service Guidelines only. It should be noted that there are services for which these gaskets are not compatible. Reference
should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not
compatible.

Bolts/Nut: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A 449
and physical requirements of ASTM A 183.
Linkage: CrMo Alloy Steel zinc electroplated per ASTM B633 Zn/Fe 5, Type III Finish.
No. 116 Adapter Fitting: CPVC and Brass
Seal: Victaulic EPDM

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 3
victaulic.com

4.0 DIMENSIONS
Product Details - Series AH1 Braided Hose

Item Description
1 Flexible Hose
2 2 Isolation Ring
5 1 6 7 3 4 8 3 Gasket
4 Nut
5 Branch Line Nipple
6 Braid
A 7 Collar/Weld Fitting
B 8 Reducer

Hose Length Dimensions

Hose Length A B
inches inches inches
mm mm mm
31 25.3 31.0
790 641 790
36 31.3 36.0
915 794 915
48 42.3 48.0
1220 1073 1220
60 54.3 60.0
1525 1378 1525
72 66.3 72.0
1830 1683 1830

Series AH1-CC

Item Description
1 Flexible Hose
5 2 Isolation Ring
2 3 4 3 Gasket
1 6 7 8
4 Nut
5 Style 108 Coupling
6 Braid
7 Collar/Weld Fitting
A 8 Reducer
B

Hose Length Dimensions

Hose Length A B
inches inches inches
mm mm mm
31 24.5 29.8
790 622 757
36 29.5 34.8
915 749 884
48 41.5 46.8
1220 1054 1189
60 53.5 58.8
1525 1359 1494
72 65.5 70.8
1830 1664 1798

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 4
victaulic.com

4.1  DIMENSIONS (CONTINUED)


Standard Reducer


4–

3–

2–

1–








5.75"/140 mm straight reducer

Optional Reducers

2.62"/
66.5 mm

2.62"/
66.5 mm

7.25"/
184.2 mm
5.50"/ 6.57"/
139.7 mm 166.9 mm 5.00"/
127.0 mm
9.0"/229 mm straight reducer 4.83"/ 3.25"/
122.7 mm 82.6 mm

13.0"/330 mm straight reducer Short 90° elbow reducer Long 90° elbow reducer
NOTE
• The Short 90° elbow reducer is typically used with concealed sprinklers while the longer 90 elbow is typically used in the installation of recessed pendent
sprinklers.
• FM/VdS Approved only.

Low Profile

5.25"/
4.59"/ 133 mm
3.50"/ 3.63"/ 116 mm
2.84"/ 89 mm 92 mm
1.88"/ 72 mm
48 mm

1.4"/ 1.4"/
36 mm 36 mm

Short 90° elbow reducer Long 90° elbow reducer


NOTE
• Style AB11: When low profiles elbows are with the Style AB11 bracket, the Low Profile Short Elbow is typically used with concealed sprinklers while the Low
Profile Long Elbow is typically used in the installation of recessed pendent sprinklers.

No. 116 CPVC Adapter


E to E

NOTES
• E to E is 3.0"/76.0 mm
• The No. 116 CPVC Adapters have 2 ft (0.6 m). EQL of 1" Schedule 40 pipe

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 5
victaulic.com

4.2 DIMENSIONS
Style AB2 3
• Suspended Ceilings
• Hard-Lid Ceilings

Item Description 2

1 24"/610 mm or 48"/1220 mm Square Bar


2 Patented Vertically Adjustable Center Bracket 1
3 End Bracket
NOTE
3
• Both sizes FM/VdS/LPCB approved, cULus listed

Style AB3
• Surface Mount Applications
• FM/LPCB Approved

Style AB4
1
• Hard-Lid Ceilings with Hat furring
channel grid system
2

Item Description 3
1 24"/610 mm or 48"/1220 mm Square Bar
2 Patented Vertically Adjustable Center Bracket
3 End Bracket for Hat Furring Channel
3
NOTE
• Both sizes FM/VdS/LPCB approved, cULus listed

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 6
victaulic.com

4.3 DIMENSIONS
VicFlex Brackets
Style AB5 3
• Hard-Lid Ceilings

Item Description
1 24"/610 mm or 48"/1220 mm Square Bar 2
2 Patented Vertically Adjustable Center Bracket
3 End Bracket
NOTE 1

• Both sizes FM/VdS/LPCB approved, cULus listed


3

Style AB7
• Suspended Ceilings 3

• Hard-Lid Ceilings

Item Description
2
1 24"/610 mm or 48"/1220 mm Square Bar
2 Patented 1-Bee2® Center Bracket
1
3 End Bracket
NOTE
• Both sizes FM/VdS/LPCB approved.

Style AB7 Adjustable


• Suspended Ceilings 3

• Hard-Lid Ceilings

Item Description 2

1 700 mm or 1400 mm Square Bar


2 Patented 1-Bee2® Center Bracket 1
3 End Bracket (adjustable)
NOTE
• Both sizes FM/VdS/LPCB approved.
3

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 7
victaulic.com

4.4 DIMENSIONS
VicFlex Brackets
Style AB10 3
2
• Suspended ceilings 1

• Armstrong® TechZone™ 3

Item Description
1 6"/152 mm Square Bar*
2 Patented 1-Bee2® Center Bracket
3 End Bracket
NOTE
• FM/VdS/LPCB approved, cULus listed.

Style AB11 3

• Suspended ceilings
• Hard-Lid ceilings

2
Item Description
1 24"/610 mm or 48"/1219 mm Square Bar
2 Patented 1-Bee2® Center Bracket 1
3 End Bracket
3
NOTE
• FM/VdS Approved, cULus listed.

Style AB12 2

• Suspended ceilings
• Hard-Lid ceilings

Item Description
1 Style AB12 Bracket Body 1
2 #2 Square Drive Set Screw
NOTE
• FM/VdS Approved.

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 8
victaulic.com

4.5 DIMENSIONS
VicFlex Brackets
Style ABBA 1

• Floor-above mount 3

• Cantilever mount
• Temporary mount in exposed ceilings
2

Item Description
1 Style ABBA Mounting Plate
2 Style ABBA Square Bar
Cap Screw, Serated Flange, M6 x 1 x 20,
3
T25 Torx Drive Recessed
5
4
4 Style ABMM Bracket Body
Cap Screw, Serated Flange, M6 x 1 x 15.24,
5
T25 Torx Drive Recessed

Style ABMM
• Surface mount 2

• Stand-off mount

Item Description
1 Style ABMM Bracket Body
1
Cap Screw, Serated Flange, M6 x 1 x 15.24,
2
T25 Torx Drive Recessed

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 9
victaulic.com

4.6 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB2 Bracket

R
See Table

L
Bracket Assembly
Style AB2

4.3"/ 23⁄8"/60.33 mm
111 mm
2"/50.80 mm

5/8"/15.9 mm
Typical
ceiling tile
1.7"/43 mm
Typical ceiling grid

Finished
surface

24"/610 mm or 48"/1219 mm
See note on Center
V2707 ¾"/19 MM MAX. RECESS V2707 MAX. EXTENSION

Hose Clearance Chart


Straight Reducer Long Elbow Short Elbow
V2707 V3802
¾" ½" V2707 V3802 V2707 V3802
Max Recess Max Recess ¾" Max Recess ½" Max Recess ¾" Max Recess ½" Max Recess
inches inches inches inches inches inches
mm mm mm mm mm mm
"R" Minimum 3.0 7.0

Bend Radius 76.2 177.8
"A" Minimum
Required 9.6 11.1 13.6 15.1 5.8 5.8
Installation 244 282 345 384 147 147
Space

NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 10
victaulic.com

4.7 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB2 Bracket

R
See chart
A
See Chart

Bracket
Assembly
#10 Screw Style AB2 211⁄16"/68 mm
1.8"/45 mm max. hole
23⁄8"/60 mm
min. hole

2" × 4"
Stud 3½"/
89 mm

Finished 5/8"/16 mm
ceiling Typical
Typical 16"/406 mm C/C drywall

V38 ½"/13 mm MAX. RECESS V38 MAX. EXTENSION

Hose Clearance Chart


Straight Reducer
V2707 V3802 V2709 V2707 V3802 V2709
¾" | 20 mm ½" | 13 mm ¾" | 20 mm ¾" | 20 mm ½" | 13 mm ¾" | 20 mm
Max Recess Max Recess Sidewall Max Recess Max Recess Sidewall
inches inches inches inches inches inches
mm mm mm mm mm mm
"R" Minimum 3.0 7.0
Bend Radius 80 175
"A" Minimum
Required 7.2 8.6 7.1 11.2 12.6 11.1
Installation 183 218 180 285 320 282
Space

Hose Clearance Chart


Long Elbow Short Elbow
V2707 V2709 V3802
¾" | 20 mm ¾" | 20 mm ½" | 13 mm
Max Recess Sidewall Max Recess
inches inches inches
mm mm mm
"R" Minimum

Bend Radius
"A" Minimum
Required 3.3 3.6 3.3
Installation 84 91 84
Space

NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 11
victaulic.com

4.8 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB4 Bracket

R
See chart

A
See Chart
Bracket assembly
Style AB4

4.1"/ 23⁄8"/60 mm
Typical Hat 104 mm max. hole
Channel 2"/51 mm
#10 Screw grid min. hole

7⁄8"/23 mm

Finished
ceiling 5⁄8"/16 mm
Typical drywall
Typical 16"/406 mm C/C

V27 ¾"/19 mm MAX. RECESS V27 MAX. EXTENSION

Hose Clearance Chart


Long Elbow Short Elbow
V2707 V3802
¾" ½" V2707 V3802 V2707 V3802
Max Recess Max Recess ¾" Max Recess ½" Max Recess ¾" Max Recess ½" Max Recess
inches inches inches inches inches inches
mm mm mm mm mm mm
"R" Minimum 3.0 3.0 7.0 7.0

Bend Radius 80 80 175 175
"A" Minimum
Required 9.8 11.2 13.8 15.2 8.0 5.9
Installation 249 285 351 386 203 150
Space

NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 12
victaulic.com

4.9 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB5 Bracket

R
See chart A
See chart

Bracket
assembly
Style AB5 2.3"/
57 mm

23⁄8"/60 mm
2" × 4" max. hole
metal stud 2"/51 mm
35⁄8"/
92 mm min. hole

Finished 5/8"/16 mm
ceiling Typ. Drywall
Typical 16"/406 mm C/C

V27 ¾"/19 mm MAX. RECESS V27 MAX. EXTENSION

Hose Clearance Chart

V2707 V3802 V2709 V2707 V3802 V2709


¾" | 20 mm ½" | 13 mm ¾" | 20 mm ¾" | 20 mm ½" | 13 mm ¾" | 20 mm
Max Recess Max Recess Sidewall Max Recess Max Recess Sidewall
inches inches inches inches inches inches
mm mm mm mm mm mm
"R" Minimum 3.0 7.0
Bend Radius 80 175
"A" Minimum
Required 7.0 8.7 7.1 11.0 12.7 11.1
Installation 178 221 180 279 323 282
Space

Hose Clearance Chart


Low-Profile
Long Elbow Long Elbow Short Elbow
V2707 V3802 V2709 V3802 V3802
¾" | 20 mm ½" | 13 mm ¾" | 20 mm ½" | 13 mm ½" | 13 mm
Max Recess Max Recess Sidewall Max Recess Max Recess
inches inches inches inches inches
mm mm mm mm mm
"R" Minimum

Bend Radius
"A" Minimum
Required 3.5 4.9 3.6 2.9 3.3
Installation 89 124 91 74 84
Space

NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 13
victaulic.com

4.10 DIMENSIONS
Clearances
Series AH2 Braided Hose and Style AB11 Bracket (LOW PROFILE SOLUTION)
23⁄8"/60 mm 211⁄16"/68 mm
Bracket max. hole max. hole
Assembly 2"/51 mm 23⁄8"/60 mm
A Style AB11 min. hole min. hole
See Chart 3.0"/
76 mm

1.7"/43 mm Finished
Typical 5/8"/15.9 mm ceiling face
ceiling grid Typical
ceiling tile
See Note 24"/610 mm or V27 V38
48"/1219 mm on center Pendent

Hose Clearance Chart


Low-Profile Low-Profile
Long Elbow Short Elbow
V2707 V3802
¾" | 20 mm ½" | 13 mm
Max Recess" Max Recess
inches inches
mm mm
"A" Minimum
Required 4.0 3.9
Installation 102 99
Space

NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 14
victaulic.com

4.11 DIMENSIONS
CLEARANCES ABOVE CEILING
Series AH1 Braided Hose and Style AB12 and ABBA Bracket
Suspended Ceiling Grid with Recessed Sprinkler Suspended Ceiling Grid with Recessed Sprinkler and
with Low Profile Short Elbow Straight 5.75"/140mm Reducer

Unfinished
Ceiling Face
11⁄8 inch/
29 mm

Nominal length
14"/355.6 mm

"A"
Unfinished See Table
11⁄8 inch/ Ceiling Face
29 mm 1⁄8 inch/
3 mm

1⁄8 inch/ "A"


3 mm See Table "B" See Table
"B" See Table

Finished Face of Finished Face of


5/8-inch/16-mm 5/8-inch/16-mm
Typical Ceiling Typical Ceiling

V2707 ½"/12.7 mm MAX. RECESS V2707 ¾"/19 mm MAX. RECESS

Low Profile Low Profile Standard Standard Standard


Dimension Short Elbow Long Elbow Short Elbow Long Elbow Straight Reducer
¾"/19mm ¾"/19mm ¾"/19mm ¾"/19mm ¾"/ 19mm
Recessed* Concealed Recessed Concealed Recessed Concealed Recessed Concealed Recessed Concealed
inches inches inches inches inches inches inches inches inches inches
mm mm mm mm mm mm mm mm mm mm
Minimum Required 4.0 5.5 5.6 7.2 5.9 7.5 7.7 9.3 15.0 16.6
A
Installation Space 101.6 139.7 142.2 182.9 149.9 190.5 195.6 236.2 381.0 421.6
Distance from Top of
0.5 2.0 1.5 1.5 1.5 1.5 3.0 3.0 3.0 3.0
B Typical Ceiling Tile to
12.7 50.8 38.1 38.1 38.1 38.1 76.2 76.2 76.2 76.2
Bottom of Gate

* Adjustability will be limited

NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.

4.12 DIMENSIONS

Style ABMM Bracket


Stand-off Dimensions
2.22"/
56 mm

2.94"/
3.93"/
75 mm 0.28"/
100 mm 3.94"/
100 mm 7 mm

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 15
victaulic.com

4.13 DIMENSIONS
BRANCHLINE CLEARANCES
Series AH1 Braided Hose with female threaded outlet Series AH1-CC Braided Hose with grooved outlet

R
See chart R
See chart

A A
See chart See chart

Female Threaded
Weld Outlet
No. 142
Grooved Weld Outlet

2"/50 mm
2"/50 mm

Hose Clearance Chart Hose Clearance Chart


Dimension Dimension
inches inches inches inches inches inches inches inches inches inches
mm mm mm mm mm mm mm mm mm mm
Minimum 3 4 5 6 7 Minimum 3 4 5 6 7
R R
Bend Radius 80 100 125 150 175 Bend Radius 80 100 125 150 175
9.4 10.4 11.4 12.4 13.41 8.1 9.1 10.1 11.1 12.1
A Min. A Min.
239 264 290 315 341 205 231 256 281 307

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 16
victaulic.com

4.14 DIMENSIONS
BRANCHLINE CLEARANCES
Series AH1 Braided Hose with Style 922 threaded outlet Series AH1-CC Braided Hose with Style 922 grooved outlet

R
See chart
R
See chart

A A
See chart See chart

Style 922 Threaded Style 922


Mechanical Tee Grooved
Outlet Mechanical Tee
Outlet

2"/50 mm 2"/50 mm

Hose Clearance Chart Hose Clearance Chart


Dimension Dimension
inches inches inches inches inches inches inches inches inches inches
mm mm mm mm mm mm mm mm mm mm
Minimum 3 4 5 6 7 Minimum 3 4 5 6 7
R R
Bend Radius 80 100 125 150 175 Bend Radius 80 100 125 150 175
9.4 10.4 11.4 12.4 13.4 7.7 8.7 9.7 10.7 11.7
A Min. A Min.
238 263 289 314 339 197 222 247 273 298

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 17
victaulic.com

4.15 DIMENSIONS
CLEARANCES ABOVE CEILING
Series AH1 Braided Hose and Style AB3 and ABMM Bracket
Surface Mount Application with Recessed Sprinkler

R
C

3¾"/
95.3 mm

B
A

23⁄8"/60 mm
max. hole
2"/51 mm
min. hole

Hose Clearances
Wall Thickness
"A"

4 6 8 10 2 4 6 8 10
100 150 200 250 50 100 150 200 250
Outlet Length 5.75 9 13 9 13 13 13 5.75 9 13 5.75 9 13 9 13 13 13
"B" 146.1 228.6 330.2 228.6 330.2 330.2 330.2 146.1 228.6 330.2 146.1 228.6 330.2 228.6 330.2 330.2 330.2
Hose 9.6 12.8 16.8 10.8 14.8 12.8 10.8 12.6 15.8 19.8 10.6 13.8 17.8 11.8 15.8 13.8 11.8
Clearance "C" 243 325 427 275 376 325 275 319 402 503 268 351 452 300 402 351 300
Bend Radius 7 8
"R" 175 200
NOTE
• Variations of ceiling grids, sprinkler heads, brackets, and hoses are permitted but may result in clearance differences from the figures above.
• See installation instructions for mounting screw type and size.

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 18
victaulic.com

5.0  PERFORMANCE – FRICTION LOSS DATA


Series AH1 and AH1-CC Braided Hose with Straight 5.75" Reducers
Style AB1, AB2, AB4, AB5 and AB10 Brackets

Maximum
Length of Equivalent Length Number of
Stainless Steel of 1"/33.7 mm 90° Bends at 3"/76.2 mm
Flexible Hose Outlet Size Sch. 40 Pipe (C=120) Bend Radius
inches
inches mm feet
mm type meters
½
52
15 3
15.8
31 Straight
775 ¾
55
20 3
16.8
Straight
½
63
15 4
19.2
36 Straight
900 ¾
66
20 4
20.1
Straight
½
78
15 4
23.8
48 Straight
1200 ¾
80
20 4
24.4
Straight
½
88
15 4
26.8
60 Straight
1500 ¾
90
20 4
27.4
Straight
½
112
15 5
34.1
72 Straight
1800 ¾
118
20 5
36.0
Straight

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 19
victaulic.com

5.0  PERFORMANCE – FRICTION LOSS DATA (CONTINUED)

Series AH1 Braided Hose with 90° Low Profile Elbows


Style AB11 VicFlex Bracket

Maximum
Equivalent Length Number of
of 1"/33.7 mm 90° Bends at 3"/76.2 mm
Hose Length Outlet Size Sch. 40 Pipe Bend Radius
inches inches feet
mm mm meters
½ 63
3
31 15 19.2
775 ¾ 65
3
20 19.8
½ 76
4
36 15 23.2
900 ¾ 76
4
20 23.2
½ 99
4
48 15 30.2
1200 ¾ 98
4
20 29.9
½ 108
4
60 15 32.9
1500 ¾ 102
4
20 31.1
½ 124
5
72 15 37.8
1800 ¾ 132
5
20 40.2

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 20
victaulic.com

5.0  PERFORMANCE – FRICTION LOSS DATA


Series AH1 Braided Hose Equivalent Length Design Guide
Equivalent length values at various numbers of 90 degree bends at 3"/76.2 mm center line bend radius
Length of
Stainless
Steel Flexible Outlet 1 2 3 4 5
Hose Size Bend Bends Bends Bends Bends
inches/mm inches/mm feet/meters feet/meters feet/meters feet/meters feet/meters
½"/15 32/9.8 42/12.8 52/15.9 N.A N.A
31/775
¾"/20 33/10.1 44/13.4 55/16.8 N.A N.A
½"/15 33/10.1 43/13.1 53/16.2 63/19.2 N.A
36/900
¾"/20 36/11.0 46/14.0 56/17.1 66/20.1 N.A
½"/15 46/14.0 57/17.4 68/20.7 78/23.8 N.A
48/1200
¾"/20 51/15.5 60/18.3 71/21.6 88/26.8 N.A
½"/15 56/17.1 67/20.4 77/23.5 88/26.8 N.A
60/1500
¾"/20 58/17.7 69/21.0 80/24.4 90/27.4 N.A
½"/15 69/21.0 79/24.1 91/27.7 102/31.1 112/34.1
72/1800
¾"/20 73/22.6 84/25.6 95/29.0 106/32.3 118/36.0
NOTES:
• Values for use with 5.75" straight reducers.
• The values in this table are provided by the manufacturer for reference only. For friction loss data in accordance with the UL Certification, please refer to page
17 of this publication.
How to use this Design Guide:
• For some systems, it may be advantageous for the designer to calculate the system hydraulics using shorter equivalent lengths associated with fewer than the
maximum allowable number of bends. In this case, the designer may select a design number of bends for the job and use the associated equivalent length
from the design guide to determine the system hydraulics.
• It is possible that the actual installed condition of some of the flexible drops may have more bends than the designer selected. When this happens, the design
guide may be used to find equivalent lengths based on the actual installed number of bends for particular sprinkler installations. The system hydraulics can be
recalculated using actual equivalent lengths to verify the performance of the system.

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 21
victaulic.com

5.0  PERFORMANCE – FRICTION LOSS DATA


Series AH1 and AH1-CC Braided Hose
Style AB1, AB2, AB3, AB4, AB5, AB7, AB7 Adj., AB8, AB10, AB12, ABBA and ABMM VicFlex Brackets

Maximum
Equivalent Number
Length of of 90° Bends
1"/33.7mm at 7"/178mm
Sch. 40 Pipe Bend Radius
inches/mm Imperial/S.I. inches/mm/type feet/meters
½"/15/Straight 53.8/16.4
31/775 5.6/8.1 2
½"/15/90˚ Elbow 53.8/16.4
½"/15/Straight 63.7/19.4
36/900 5.6/8.1 2
½"/15/90˚ Elbow 63.1/19.2
½"/15/Straight 87.9/26.8
48/1200 5.6/8.1 3
½"/15/90˚ Elbow 85.8/26.1
½"/15/Straight 112.2/34.1
60/1500 5.6/8.1 4
½"/15/90˚ Elbow 108.4/33.0
½"/15/Straight 136.5/41.6
72/1800 5.6/8.1 4
½"/15/90˚ Elbow 131.1/39.9
¾"/20/Straight 44.4/13.5
31/775 8.0/11.5 2
¾"/20/90˚ Elbow 47.6/14.5
¾"/20/Straight 55.6/16.9
36/900 8.0/11.5 2
¾"/20/90˚ Elbow 57.5/17.5
¾"/20/Straight 82.8/25.2
48/1200 8.0/11.5 3
¾"/20/90˚ Elbow 81.7/24.9
¾"/20/Straight 110.1/24.9
60/1500 8.0/11.5 4
¾"/20/90˚ Elbow 105.9/32.2
¾"/20/Straight 137.3/41.8
72/1800 8.0/11.5 4
¾"/20/90˚ Elbow 130.2/39.7
¾"/20/Straight 45.5/13.8
31/775 11.2/16.1 2
¾"/20/90˚ Elbow 47.1/14.3
¾"/20/Straight 66.3/20.2
36/900 11.2/16.1 2
¾"/20/90˚ Elbow 57.5/17.5
¾"/20/Straight 82.7/25.2
48/1200 11.2/16.1 3
¾"/20/90˚ Elbow 82.8/25.2
¾"/20/Straight 109.1/33.2
60/1500 11.2/16.1 4
¾"/20/90˚ Elbow 108.1/32.9
¾"/20/Straight 135.5/41.3
72/1800 11.2/16.1 4
¾"/20/90˚ Elbow 133.4/40.6
¾"/20/Straight 44.3/13.5
31/775 14.0/20.2 2
¾"/20/90˚ Elbow 46.4/14.1
¾"/20/Straight 55.5/16.9
36/900 14.0/20.2 2
¾"/20/90˚ Elbow 56.7/17.3
¾"/20/Straight 83.0/25.3
48/1200 14.0/20.2 3
¾"/20/90˚ Elbow 82.1/25.0
¾"/20/Straight 110.4/33.6
60/1500 14.0/20.2 4
¾"/20/90˚ Elbow 107.5/32.7
¾"/20/Straight 137.9/42.0
72/1800 14.0/20.2 4
¾"/20/90˚ Elbow 132.8/40.4
FM NOTES:
• Series AH1 has been tested and Approved by FM Global for use in wet, dry and preaction systems per NFPA 13, 13R, and 13D and FM data sheets 2-0, 2-5,
and 2-8. FM 1637 and Vds standards for safety include, but are not limited to, pressure cycling, corrosion resistance, flow characterisitics, vibration
resistance, leakage, mechanical and hydrostatic strength.
• EXAMPLE: A 48-inch hose installed with two 30° bends and two 90° bends is permitted and considered equivalent to the data in the table shown above. In
this example, the total number of degrees is 240°, which is less than the allowable 270°.

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 22
victaulic.com

5.0  PERFORMANCE – FRICTION LOSS DATA


Series AH1 Braided Hose with 90° Low Profile Elbows
Style AB5, AB11, AB12, ABBA and ABMM VicFlex Bracket

Maximum
Equivalent Number
Length of Length of of 90° Bends
Stainless Steel Outlet 1"/33.7mm at 7"/178mm
Flexible Hose K-Factor Size Sch. 40 Pipe Bend Radius
inches/mm Imperial/S.I. inches/mm feet/meters
31/775 5.6/8.1 ½"/15 49.0/14.9 2

36/900 5.6/8.1 ½"/15 58.5/17.8 2

48/1200 5.6/8.1 ½"/15 81.5/24.8 3

60/1500 5.6/8.1 ½"/15 104.4/31.8 4

72/1800 5.6/8.1 ½"/15 127.4/38.8 4

31/775 8.0/11.5 ¾"/20 47.6/14.5 2

36/900 8.0/11.5 ¾"/20 57.7/17.6 2

48/1200 8.0/11.5 ¾"/20 81.9/25.0 3

60/1500 8.0/11.5 ¾"/20 106.1/32.3 4

72/1800 8.0/11.5 ¾"/20 130.5/39.8 4

31/775 11.2/16.1 ¾"/20 48.6/14.8 2

36/900 11.2/16.1 ¾"/20 58.2/17.7 2

48/1200 11.2/16.1 ¾"/20 82.2/25.1 3

60/1500 11.2/16.1 ¾"/20 104.2/31.8 4

72/1800 11.2/16.1 ¾"/20 127.5/38.8 4

31/775 14.0/20.2 ¾"/20 47.9/14.6 2

36/900 14.0/20.2 ¾"/20 58.0/17.7 2

48/1200 14.0/20.2 ¾"/20 82.2/25.1 3

60/1500 14.0/20.2 ¾"/20 106.4/32.4 4

72/1800 14.0/20.2 ¾"/20 130.8/39.9 4

FM NOTES:
• Series AH1 has been tested and Approved by FM Global for use in wet, dry and preaction systems per NFPA 13, 13R, and 13D and FM data sheets 2-0, 2-5,
and 2-8. FM 1637 and Vds standards for safety include, but are not limited to, pressure cycling, corrosion resistance, flow characterisitics, vibration
resistance, leakage, mechanical and hydrostatic strength.
• Differences in equivalent lengths are due to varying test methods, per FM 1637 and VdS standards. Refer to these standards for additional information
regarding friction loss test methods.
• EXAMPLE: A 48-inch hose installed with two 30° bends and two 90° bends at a 7-inch bend radius is permitted and considered equivalent to the data in the
table shown above. In this example, the total number of degrees is 240°, which is less than the allowable 270°.

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 23
victaulic.com

5.0  PERFORMANCE – FRICTION LOSS DATA


Series AH1 and AH1-CC Braided Hose
Style AB1, AB2, AB4, AB5, AB7, AB7 Adj., AB8, AB10, AB11 and AB12 Brackets

Equivalent Length of Maximum Number


Length of steel pipe according to of 90º Bends
Stainless Steel Outlet EN 10255 DN 20 at 3"/76.2mm
Flexible Hose Size (26,9 x 2,65) Bend Radius
mm/inches mm/inches/type meters/feet meters/feet
15mm/½"/Straight
790/31 4.0/12.9 3
20 mm/¾"/Straight
15mm/½"/Straight
915/36 4.6/15.0 3
20 mm/¾"/Straight
15mm/½"/Straight
1220/48 6.1/20.0 3
20 mm/¾"/Straight
15mm/½"/Straight
1525/60 7.6/25.0 4
20 mm/¾"/Straight
15mm/½"/Straight
1830/72 9.2/30.0 4
20 mm/¾"/Straight
VDS CEILING MANUFACTURERS LIST

AB1, AB2, AB7, AB10, AB11, AB12 AB4 AB8


1. AMF No specific approval 1. Hilti
2. Armstrong 2. Knauf
3. Chicago Metallic 3. Lafarge
4. Dipling 4. Lindner
5. Durlum 5. Rigips
6. Geipel
7. Gema-Armstrong
8. Hilti
9. Knauf
10. Lafarge
11. Linder
12. Odenwald
13. Richter
14. Rigips
15. Rockfon Pagos
16. Suckow & Fischer
17. USG Donn

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 24
victaulic.com

5.0  PERFORMANCE – FRICTION LOSS DATA (continued)

Series AH1 and AH1-CC Braided Hose


Style AB1, AB2, AB3, AB4, AB5, AB7, AB8 and AB10 Brackets
LPS 1261: Issue 1.2
Cert/LPCB Ref. 1
 04l/02
104l/03

Equivalent Length Maximum Number


Length of of steel pipe according to of 90º Bends
Stainless Steel Outlet EN 10255 DN 25 at 3"/76.2mm
Flexible Hose Size (33,7 x 3,25) Bend Radius
mm/inches mm/inches/type meters/feet
15mm/½"/Straight
12.7/41.8 2
20 mm/¾"/Straight
790/31
15mm/½"/90º Elbow
13.6/44.6 2
20 mm/¾"/90º Elbow
15mm/½"/Straight
16.4/53.8 3
20 mm/¾"/Straight
915/36
15mm/½"/90º Elbow
16.9/55.4 3
20 mm/¾"/90º Elbow
15mm/½"/Straight
19.6/64.3 3
20 mm/¾"/Straight
1220/48
15mm/½"/90º Elbow
19.9/65.1 3
20 mm/¾"/90º Elbow
15mm/½"/Straight
24.0/78.8 3
20 mm/¾"/Straight
1525/60
15mm/½"/90º Elbow
24.5/80.2 3
20 mm/¾"/90º Elbow
15mm/½"/Straight
27.8/91.1 3
20 mm/¾"/Straight
1830/72
15mm/½"/90º Elbow
28.5/93.4 3
20 mm/¾"/90º Elbow

Series AH1 Flexible Hose Friction Loss Data

Equivalent Length
Length of Flexible Hose Straight Configuration Bend Configuration
mm meters meters
Model inches feet feet
790 4.78 5.80
AH1-31
31 15.7 19.0
915 5.59 10.15
AH1-36
36 18.3 33.3
1120 9.75 16.25
AH1-48
48 32.0 53.3
1525 12.15 22.94
AH1-60
60 39.9 75.3
1830 14.26 25.98
AH1-72
72 46.8 85.2

NOTE
• Friction loss data is in accordance with GB5135.16 tested at a flow rate of 114 liters per minute (30 gallons per minute).

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 25
victaulic.com

6.0 NOTIFICATIONS

WARNING

• Read and understand all instructions before attempting to install


any Victaulic products.
• Always verify that the piping system has been completely depressur-
ized and drained immediately prior to installation, removal, adjust-
ment, or maintenance of any Victaulic products.
• Wear safety glasses, hardhat, and foot protection.

• These products shall be used only in fire protection systems that are designed and installed in accordance with
current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent
standards, and in accordance with applicable building and fire codes. These standards and codes contain impor-
tant information regarding protection of systems from freezing temperatures, corrosion, mechanical damage, etc.
• The installer shall understand the use of this product and why it was specified for the particular application.
• The installer shall understand common industry safety standards and potential consequences of improper prod-
uct installation.

WARNING
• It is the responsibility of the system designer to verify suitability of 300-series stainless steel flexible hose for
use with the intended fluid media within the piping system and external environments.
• The effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate
on 300-series stainless steel flexible hose must be evaluated by the material specifier to confirm system life will
be acceptable for the intended service.
• It is the responsibility of the owner of a building or their authorized agent to provide the sprinkler system installer
with any knowledge that the water supply might be contaminated with or conducive to the development of micro-
biologically influenced corrosion (MIC), including as required by NFPA 13. Failure to identify adverse water quality
issues may affect the VicFlex product and void the manufacturer’s warranty.
Failure to follow these instructions could cause product failure, resulting in serious personal injury and/or
property damage.

Victaulic VicFlex Series AH1 and AH1-CC Flexible Sprinkler Fittings may be painted provided the paint is compatible
with stainless steel and zinc-plated carbon steel or ductile iron. Care should be taken to ensure the sprinkler and associated
escutcheon or coverplate are not painted.

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 26
victaulic.com

7.0  REFERENCE MATERIALS – CHARACTERISTICS


Flexible Hose In-Plane Bend Characteristics

One Bend Two Bends Three Bends

2X
2X Minimum Minimum
Minimum bend radius bend radius
bend radius

OR
Minimum OR
bend radius

90°
Minimum
bend radius Minimum
Minimum bend radius
bend radius
Minimum
bend radius

Minimum
bend radius

NOTE
• For out-of-plane (three-dimensional) bends, care must be taken to avoid imparting torque on the hose.

I-VicFlex-AB1-AB2-AB10
I-VicFlex-AB3
I-VicFlex-AB4
I-VicFlex-AB5
I-VicFlex-AB7
I-VicFlex-AB12
I-VicFlex-ABBA
I-VicFlex-ABMM
I-RES

User Responsibility for Product Selection and Suitability Note


Each user bears final responsibility for making a determination as to the suitability of This product shall be manufactured by Victaulic or to Victaulic specifications. All products
Victaulic products for a particular end-use application, in accordance with industry to be installed in accordance with current Victaulic installation/assembly instructions.
standards and project specifications, and the applicable building codes and related Victaulic reserves the right to change product specifications, designs and standard
regulations as well as Victaulic performance, maintenance, safety, and warning equipment without notice and without incurring obligations.
instructions. Nothing in this or any other document, nor any verbal recommendation, Installation
advice, or opinion from any Victaulic employee, shall be deemed to alter, vary, supersede, Reference should always be made to I-VICFLEX-AB1-AB2-AB10, I-VICFLEX-AB4-AB9,
or waive any provision of Victaulic Company's standard conditions of sale, installation I-VICFLEX-AB7, or I-VICFLEX-AB8 for the product you are installing. Handbooks are
guide, or this disclaimer. included with each shipment of Victaulic products for complete installation and assembly
Intellectual Property Rights data, and are available in PDF format on our website at www.victaulic.com.
No statement contained herein concerning a possible or suggested use of any material, Warranty
product, service, or design is intended, or should be constructed, to grant any license Refer to the Warranty section of the current Price List or contact Victaulic for details.
under any patent or other intellectual property right of Victaulic or any of its subsidaries or
affiliates covering such use or design, or as a recommendation for the use of such Trademarks
material, product, service, or design in the infringement of any patent or other intellectual Victaulic and all other Victaulic marks are the trademarks or registered trademarks of
property right. The terms “Patented” or “Patent Pending” refer to design or utility patents Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries.
or patent applications for articles and/or methods of use in the United States and/or other
countries.

10.95 8507 Rev M Updated 03/2021 © 2021 Victaulic Company. All rights reserved.

victaulic.com 27

You might also like