NYCHA - Astoria Houses Heat Plan

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Queens-Staten Island

Heating Action Plan – Individual Action Plan


Astoria

DEVELOPMENT INFO CAPITAL INVESTMENTS


• BMS & Apartment Temperature Controls [From July
# of Buildings 22 2019 to Anticipated Completion of May 2020, 65%
Completed]
# of Apartments 1,104
OPERATIONS INVESTMENTS
Total Population 2,942
• Boiler Repairs [Completed]
• Conduit and Electrical Piping Replacement [From
% of Population Over 62 15%
September 2019 to Anticipated Completion of
December 2019, 75% Completed]
Self Identified Mobility
428 • Electrical Supply Replacement (Burner) [From
Impaired Population
September 2019 to Anticipated Completion of
December 2019, 75% Completed]
ASSET SUMMARY • Feedwater Pipe Replacement [Completed]
• Feedwater Regulator [Completed]
Plant Configuration Dual Fuel • Low Water Cut Out [Completed]
• Underground Steam and Condensate Return Lines
# of Boilers 4 [Completed]
• Water Column Replacement [Completed]
Distribution System Two-Pipe
OUTAGES
ASSET CONDITION 2017/2018 Heating Outages 25
2017/2018 Average Restoration Time (Hours) 23.0
Boiler Age 29 years
2018/2019 Heating Outages 9
Boiler PNA Condition 2018/2019 Average Restoration Time (Hours) 7.7
5
Rating
HEATING STAFF BREAKDOWN
MAJOR CHALLENGES Cluster -
Heating Administrator
Management
Cluster Superintendent
Astoria Houses is a third-party location managed by Third Party Management/Property
George S. Hall (GSH). The boilers at this location have Frontline Personnel
Management
outlived its life expectancy. These boilers are small and
make it difficult to provide enough heat during cold spells. Permanent Affordability Commitment
There is a mobile boiler at Astoria Houses to support in-
house boilers. Together (PACT)
Astoria is not currently in the PACT conversion pipeline.

POTENTIAL ALTERNATIVE HEATED COMMUNITY SPACES


On-site
Hellenic American Neighborhood Action Committee (HANAC), 4-05 Astoria Boulevard
NYCHA, 4-05 Astoria Boulevard
Off-site
Not Applicable
*The Office of Emergency Management (OEM) and the Emergency Services Department (ESD) coordinate with the MTA to provide warming buses and transportation to the warming centers.*

As of Nov-2019 Content Subject To Change


Queens-Staten Island
Heating Action Plan – Individual Action Plan
Astoria

MOBILE BOILER CONNECTION DETAILS


Location of installation (DOT alternate side parking rules) 3-04 27th Avenue (NYCHA Grounds-Dump Site)

Boiler type Kewanee

Boiler burner Preferred

Number of boilers 4

Internal heating system Steam

Horsepower per boiler 350 hp

Internal system horsepower 1,350 hp

Number of in-ground oil tanks 2

In-ground oil tank capacity 23,790

Number of oil transfer pumps on-site 3

Number of oil transfer pumps operational 2

Oil operation follow-ups Pump#1 - OOO

Scaffolding size and staging Connection Platform: 12'H x 5'W, Bridging: 12'H x 3'W x 30'L

Electrical feed location Boiler room main panel (needs dedicated disconnect panel)

Building amperage/voltage 200 amp/ 208 volt

Electrical materials needed 3 Phase 50' length - 4/0 AWG cable

Steam inlet access point Main header (needs blank installed)

Steam connection inlet diameter 10"

Requires welding for steam connection Yes

(1) 90-degree elbow, (1) 20'L x 12" ID Steel Braided Hose, (1)
Plumbing materials needed for steam connection
10'L x 12" ID Steel Braided Hose

Make-up feed water access point 2" Tap on condensate line

Plumbing materials needed for make-up feedwater


(2) 100'L x 1" Rubber Hose
connection

As of Nov-2019 Content Subject To Change