Product Manual 37807 (Revision NEW) : 723 Generator Control
Product Manual 37807 (Revision NEW) : 723 Generator Control
(Revision NEW)
Original Instructions
8280-576/-577
This publication may have been revised or updated since this copy was produced.
To verify that you have the latest revision, check manual 26311 , Revision Status &
Distribution Restrictions of Woodward Technical Publications, on the publications
Revisions page of the Woodward website:
www.woodward.com/publications
Revisions—Changes in this publication since the last revision are indicated by a black line
alongside the text.
Woodward reserves the right to update any portion of this publication at any time. Information provided by
Woodward is believed to be correct and reliable. However, no responsibility is assumed by Woodward unless
otherwise expressly undertaken.
Copyright © Woodward 2007
All Rights Reserved
Manual 37807 723 Generator Control 8280-576/-577
Contents
Woodward i
723 Generator Control 8280-576/-577 Manual 37807
Contents
ii Woodward
Manual 37807 723 Generator Control 8280-576/-577
Woodward iii
723 Generator Control 8280-576/-577 Manual 37807
iv Woodward
Manual 37807 723 Generator Control 8280-576/-577
Chapter 1.
General Information
Introduction
This manual describes the 723 Generator Control, part numbers 8280-576/-577
(High & Low Voltage Control).
Application
The control is intended for use in a variety of generator applications; for
auxiliary generators and diesel electric propulsion in the marine market, and for
island mode systems and for base loading against an infinite bus in the Power
Plant market.
The MW Control mode is especially useful for applications where the grid is
weak and large frequency excursions are expected. Under these
circumstances, operating in droop mode is not practical, as large variations in
load would be experienced, due to frequency shifts of the grid. In MW control,
the speed of the engine is maintained by the grid, and the load on the generator
remains constant throughout the frequency excursion.
Start and maximum fuel limiters are provided. A load limiter, enabled during KW
control, will provide load de-rating during frequency excursions. Additional
protection is offered to open the Grid Breaker or the Generator Breaker, should
the frequency excursion become too large.
The control can be adjusted/biased for synchronising the generator to the bus
by means of the Increase/Decrease contacts, or by the input provided for a
Woodward Unit Synchroniser (SPM-A or DSLC™ — Digital Synchroniser &
Load Control). The control may also be used for synchronising to the grid using
the second synchroniser input (System Synchroniser), for an SPM-A or DSLC.
One LON connection of the 723 may be connected to a DSLC, so that all of the
generator parameters may be monitored within the 723, and then also via the
Modbus.
One serial port (J3) is available for Modbus communications using RS-232,
RS-422, or RS-485. Engine and generator parameters can be monitored, and
certain control functions sent to the control via the Modbus.
Woodward 1
723 Generator Control 8280-576/-577 Manual 37807
Chapter 2.
723 DCS Installation
Declaration of Incorporation
In accordance with the EMC directive 89/336/EEC and its amendments, this
controlling device, manufactured by the Woodward Governor Company, is
applied solely as a component to be incorporated into an engine prime mover
system. Woodward Governor declares that this controlling device complies with
the requirements of EN50081-2 and EN50082-2 when put into service per the
installation and operating instructions outlined in the product manual.
Digital Synchroniser & Load Control (DSLC™) for synchronising the generator
phase & voltage to that of the power bus. The DSLC also provides dead bus
closure facility and has real power load sensing using harmonic filtering
algorithms (DSLC manual 02007).
Real Power Sensor (MW Transducer) for generator load monitoring (part
number 8272-394).
Power Consumption
40 W nominal
2 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Analogue Inputs (4)
4–20 mA or 1-5 Vdc
Storage Temperature
–55 to +105 °C (–67 to +221 °F)
Humidity
95% at 38 °C
EMI/RFI Susceptibility
US MIL-STD 461C (Parts 5 & 9)
Humidity
US MIL-STD 810D, Method 507.2, Procedure III
Mechanical Vibration
24–2000 Hz swept sine, 2.5 Gs constant acceleration, resonant dwells —
1 million cycles, total time—6 hours/axis
Mechanical Shock
US MIL-STD 810C, Method 526.2, Procedure I (basic design test). Procedure II
(transit drop test, packaged). Procedure V (bench handling).
Salt Spray
ASTM B 117-73
Location Considerations
Consider these requirements when selecting the mounting location:
Adequate ventilation for cooling;
Space for servicing and repair;
Protection from direct exposure to water or to a condensation-prone
environment;
Proximity to high-voltage or high-current devices, or devices which produce
electromagnetic interference;
Avoidance of vibration;
Selection of a location that will provide an operating temperature range of
40 to +70 °C (40 to +158 °F).
Woodward 3
723 Generator Control 8280-576/-577 Manual 37807
4 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Internal Jumpers
The 723 control has ten, two-position internal jumpers (JPR1 through JPR20)
located on the top of the printed circuit board. If it is necessary to change any
jumper to match the control requirements, and suits the nature of the software,
be sure to read Electrostatic Discharge Awareness (page iii).
Ensure that the power to the control is switched off, before removing the cover.
Using a small pair of tweezers, carefully remove the appropriate jumper and
replace it securely over the proper two connectors (see Figure 2-2).
Electrical Connections
Shielded Wiring
All shielded cable must be twisted conductor pairs. Do not attempt to tin the
braided shield. All signal lines should be shielded to prevent picking up stray
signals from adjacent equipment. Connect the shields to the nearest chassis
ground. Wire exposed beyond the shield should be as short as possible, not
exceeding 50 mm (2 inches). The other end of the shields must be left open and
insulated from any other conductor. DO NOT run shielded signal wires along
with other wires carrying large currents. See Woodward application note 50532,
EMI Control in Electronic Governing Systems for more information.
Where shielded cable is required, cut the cable to the desired length and
prepare the cable as instructed below.
1. Strip outer insulation from BOTH ENDS, exposing the braided or spiral
wrapped shield. DO NOT CUT THE SHIELD.
2. Using a sharp, pointed tool, carefully spread the strands of the shield.
3. Pull inner conductor(s) out of the shield. If the shield is the braided type,
twist it to prevent fraying.
Woodward 5
723 Generator Control 8280-576/-577 Manual 37807
6 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Run the power leads directly from the power source to the control. DO NOT
POWER OTHER DEVICES WITH LEADS COMMON TO THE CONTROL.
Avoid long wire lengths. Connect the positive (line) to terminal 1 and negative
(common) to terminal 2. A protection device such as a fuse or MCB (rated 4
Amps for low voltage control and 2 Amps for the High- Voltage control) should
be connected to prevent damage to the control. If the power source is a battery,
be sure the system includes an alternator or other battery-charging device.
Do NOT apply power to the control at this time. Applying power may
damage the control.
Woodward 7
723 Generator Control 8280-576/-577 Manual 37807
The number of gear teeth is used by the control to convert pulses from
the speed sensing device to engine rpm. To prevent possible serious
injury from an overspeeding engine, make sure the control is properly
programmed to convert the gear-tooth count into engine rpm.
Improper conversion could cause engine overspeed.
Use shielded twisted-pair wires to connect to terminals 15(+) & 16(–), 17(+) &
18(–), and 19(+) & 20(–). For an electrically isolated input device such as a 4 to
20 mA input analogue meter, the shield should be grounded at the control end
of the cable. For input to other devices, use the recommendation of the device
manufacturer.
The actuator wires connect to terminals 21(+) and 22(). Use shielded wires
with the shield connected to chassis at the control.
8 Woodward
Manual 37807 723 Generator Control 8280-576/-577
If the discrete input voltage (24 Vdc) is supplied from an external source,
connect the voltage source negative () to terminal 37. Then run the voltage
source positive (+) to the appropriate switch or relay contact and then to the
corresponding discrete input.
Analogue Inputs
KW Transducer (Terminals 41/42/43)
KW Reference (Terminals 44/45/46)
Unit Synchroniser (Terminals 47/48/49)
System Synchroniser/Charge Air Pressure (Terminals 50/51/52)
Use shielded twisted-pair cable to connect to terminals 42(+) & 43(–), 45(+) &
46(–), 48(+) & 49(–) and 51(+) & 52(–). Ensure that jumpers are installed
between terminals 41 & 42, 44 & 45 and 50 & 51.
For 4–20 mA inputs (jumper in), the internal burden resistance is 250 ohms.
Termination
For RS-422, termination should be located at the receiver when one or more
transmitters are connected to a single receiver. When a single transmitter is
connected to one or more receivers, termination should be at the receiver
farthest from the transmitter. Figure 2-5 is an example.
Woodward 9
723 Generator Control 8280-576/-577 Manual 37807
For RS-485, termination should be at each end of the cable. If termination can't
be located at the end of a cable, put it as close as possible to the ends. Figure
2-6 is an example.
If you don't know if a master can put its transmitter into a high-impedance state,
terminate the line as shown in Figure 2-5. It does not hurt to terminate the line
even when it's not needed as in the case of the HMI operator interface.
10 Woodward
Manual 37807 723 Generator Control 8280-576/-577
See Figures 2-5 through 2-8 for termination and cable connection examples.
Figure 2-5. 723 RS-232 Connection Figure 2-6. 723 RS-422 Connections
with Optional Termination at Receiver
Figure 2-7. 723 RS-485 Connections Figure 2-8. 723 RS-422 Connections
with Optional Termination with Optional Termination at
Transmitter
Woodward 11
723 Generator Control 8280-576/-577 Manual 37807
Figure 2-9. Preferred Multipoint Wiring using Shielded Twisted-pair Cable with
Separate Signal Ground Wire
12 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Woodward 13
723 Generator Control 8280-576/-577 Manual 37807
14 Woodward
Manual 37807 723 Generator Control 8280-576/-577
1. Visual inspection
A. Check the linkage between the actuator and fuel-metering device for
looseness or binding. Refer to the appropriate actuator manual, and
Manual 25070, Electric Governor Installation Guide for additional
information on linkage.
Check for grounds by measuring the resistance from all control terminals
to chassis. All terminals except terminals 2 and 38 should measure infinite
resistance (the resistance of terminals 2 and 38 depends on whether a
floating or grounded power source is used). If a resistance less than
infinite is obtained, remove the connections from each terminal one at a
time until the resistance is infinite. Check the line that was removed last to
locate the fault.
Woodward 15
723 Generator Control 8280-576/-577 Manual 37807
Chapter 3.
System Description
Engine Speed
Speed Sensing
The control has two speed sensing inputs, and may be configured for torsional
filtering, for smoother operation with soft couplings, or high signal select, giving
speed sensing redundancy should one signal fail. If the torsional filter has been
selected, the speed sensors should be positioned on either side of the coupling;
sensor #1 on the engine side, and sensor #2 on the generator side. If the high
signal select is utilised, then both speed sensing devices should be located on
the same speed sensing disc.
Each speed sensor input has a failed speed detection device, with an override
function, which is active during engine start-up. The Failed Spd Sensor #1 and
Failed Spd Sensor #2 LED’s located on the 723 control, give indication when
either input has failed. If a speed sensor fails, it will be switched out until the
fault is rectified, and then reset during the next engine start *F.
When the torsional filter is selected, failure of either speed sensor will result in
the activation of the Minor Alarm, and control will continue with one speed
signal. If the Generator CB Aux contact input is closed, the Propgain Multiplier
will be switched in to decrease the Proportional Gain value. If high signal select
is chosen, failure of a speed sensor will also give continued control with one
speed signal, and the Minor Alarm will be activated.
The option is available to disable the Minor Alarm if one speed sensor fails, for
situations where only one speed sensor is utilised. The Alarm LED on the front
panel of the 723 will still illuminate if no speed signal is sensed, but the Minor
Alarm will not activate.
Failure of both speed sensors will initiate a shutdown, whereby the control will
drive the actuator output to zero, and the Major Alarm will be activated.
If the engine has been shut down by the 723 control due to both
speed sensors failing, do NOT attempt to start the engine until the
faults have been located and rectified. Failure of the pickups can
only be detected whilst the engine is running, i.e. the signal must
already exist for the failure detection to operate. If the 723 cannot
detect engine speed during start-up, the actuator output will go to
maximum, possibly driving the engine into an overspeed condition.
The engine should be equipped with an additional overspeed
shutdown device that operates totally independently of this control,
to protect against runaway or damage to the engine, with possible
personal injury or loss of life.
16 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Speed Filtering
Each speed sensor input is fed through a low pass filter which should not need
adjustment, but may be used to filter out any undesirable frequencies on the
speed pickups.
If enabled, the torsional filter can be used to help prevent the control from
reacting to torsionals across a flexible coupling. This works by ‘averaging’ out
the speed sensing signals from either side of the coupling, although this can be
weighted more heavily to one side than the other, by adjusting the Sensor
Weight.
For systems with low frequency oscillatory modes due to engine and generator
inertias, and flexible couplings, which can become difficult to control, the
Notch/Band-Stop Filter is provided. This filter can reduce the signal
transmission through the control, by reducing the signal gain at the resonant
frequency, and hence preventing the control from reacting to these unwanted
frequencies.
If the Idle/Rated select contact is required, the Enable I/R Select parameter
should be set true. When the Run/Stop contact is put in the ‘run’ position, the
speed reference will be initially at Idle Speed. Once the engine has started, the
control will remain at idle, if the contact is in the idle position, or will ramp to
Rated Speed, at the Accel/Decel Rate, if/when the contact is closed. The idle-
to-rated ramp may be interrupted by either opening the Rated/Idle contact (and
so returning the reference back to Idle Speed at the Accel/Decel Rate), or by
momentarily closing either of the Increase or Decrease contacts (so freezing
the ramp).
The Idle/Rated contact input is only functional, whilst the Generator CB Aux
contact input is open.
Synchronising to a Bus
When the engine reaches Rated Speed, and has remained within the Ready to
Synch Limits for the Sync OK Delay Time, the control will issue a ‘Run’
command via the LON to the DSLC™. If the DSLC is not connected using the
LON, it will have to be enabled by the hardwired contact instead.
Woodward 17
723 Generator Control 8280-576/-577 Manual 37807
The Unit Synchroniser Input will bias the speed reference, based on the value
of the bipolar voltage input. Once the Generator CB Aux contact is closed, the
bias is either:
switched out until the Generator CB Aux input is opened, if isoch mode is
enabled.
last value locked in until the Generator CB Aux input is opened, if droop
mode is enabled.
Opening the Generator CB Aux contact input will set the speed reference
instantly to Rated Speed.
Opening the Parallel With Grid (if used) contact input will set the speed
reference instantly to Rated Speed.
Droop Control
To operate in Droop mode, the Isochronous/Droop contact input must be
open, and the Generator CB Aux contact closed.
The speed droop value is calculated based on the Droop percentage, and the
load on the engine. The engine load will be derived from the MW Transducer
input. Should this signal fail, the load will be determined based on the position
of the actuator output. Failure of the load signal input will activate the Minor
Alarm, which will be reset once the signal is healthy. The speed droop will
always be zero, whilst the CB Aux is open.
A ‘Droop Pulse’ function is provided to help prevent an engine being driven into
reverse power, when connected to a bus in droop mode. When the Generator
CB Aux contact is closed, the speed reference is immediately increased by the
Ref Bias Pulse. This will cause the generator to immediately take on load from
the other sets. This is a permanent bias, whilst the control remains in droop
mode. This function can be disabled by tuning the Ref Bias Pulse parameter to
zero.
Closure of the Increase contact will cause the speed reference to increase at
the Inc/Dec Rate #2, therefore causing the engine to take on load (if available).
Closure of the Decrease contact will cause the speed reference to decrease at
the Inc/Dec Rate #2, therefore causing the engine to shed load (if possible).
18 Woodward
Manual 37807 723 Generator Control 8280-576/-577
The first machine on-line will close it’s relay K4 contact on the load sharing lines
instantly, connecting to the system load sharing lines, in preparation for
isochronous load sharing with other units. Subsequent units selected to
isochronous will increase/decrease load softly, according to the Auto
Load/Unload Rates, until the load on the unit is within the defined LS Error %, of
the other unit(s) which are already isochronously load sharing. At this time, the
relay K4 will be closed to connect the load sharing lines to those of the other
unit(s). The error between the system load and each individual unit’s load will
then be monitored, and the Rated Speed reference biased accordingly, to
increase/decrease load, to achieve equal load sharing at Rated Speed.
The control provides a function for auto soft unloading of the engine. The
Unload contact should be closed (momentarily) when the control is in
isochronous load sharing. The engine load will then be ramped down at the
Auto Unload Rate, until the Unload Trip Level is reached, at which time, the
control will issue a Generator Breaker Open Command. This output will
remain active, until the Generator CB Aux contact is opened.
The Emergency Load Rate input may be enabled for fast ‘soft’
loading/unloading of the engine.
If it is necessary that a machine is required on-line more quickly than usual (i.e.
during an emergency situation), the contact should be closed, and once the
Generator CB Aux contact is closed, the control will load the engine at the
Emergency Load Rate, rather than the Auto Load Rate.
If the Unload function is used whilst the Emergency Load Rate contact is
closed, the engine will be unloaded at the Emergency Unload Rate.
The Emergency Load/Unload Rates may be disabled at any time, by opening
the contact.
Whilst the control is operating in isochronous load sharing, the droop reference
is continuously tracking, so that if the control is switched into droop mode, the
transfer will be bumpless.
Woodward 19
723 Generator Control 8280-576/-577 Manual 37807
MW Control
To operate in MW Control, the Generator CB Aux, Parallel With Grid (if used)
and MW Control contact inputs must be closed.
Switching into MW Control from Isochronous Load Sharing or Droop mode will
be bumpless. Once in MW Control, the MW reference can be adjusted by use of
the Increase/Decrease contact inputs. Closing the Increase contact raises the
MW reference towards the Maximum Load at the Raise Load Rate. Closing the
Decrease contact lowers the MW reference towards the Minimum Load at the
Lower Load Rate.
If the Select Int MW Ref parameter has been selected true in Configure, when
the control switches into kW Control mode, and digital mode is selected (use of
Increase/Decrease inputs to adjust load), the MW reference will automatically
ramp to the Internal MW Ref at the Int MW Ref Rate. It will then remain at this
level until the Increase/Decrease contact inputs are used to adjust the load, or if
the control is switched into Remote/Analogue mode.
If both the Increase and Decrease contacts are closed (or Remote Reference
selected via the Modbus), the MW reference will ramp to the level determined
by the 4–20 mA Remote Reference input (or Modbus Remote reference), at
the Auto Load Rate. Once this level has been reached, the reference will
continue to follow the input, at the Raise/Lower Load Rates. If the remote
reference input should fail (i.e. <2mA, >22mA), the MW reference will lock in the
last healthy value. The control will then respond to the Increase/Decrease
contacts, once the remote MW reference is de-selected.
If both the Increase and Decrease contacts are closed to select the remote
reference, opening only one of the contacts will NOT de-select the remote
reference. Both contacts must be opened to de-select the remote reference.
This is to prevent the reference being driven high or low in the event of a single
wire break.
Closing the Unload contact (momentarily) will cause the control to decrease the
MW reference until the Unload Trip Level is reached, at which time the control
will issue a Generator Breaker Open Command. This output will remain active
until the Generator CB Aux contact is opened, indicating that the breaker has
opened.
Failure of the 4–20 mA MW Transducer input (i.e. <1mA, >22mA) will switch
the control into droop mode, with load calculated based on the actuator output.
Once the fault is rectified, and the signal fault reset (either automatically or by
using the Modbus Reset), the control will load/unload back into MW Control.
If the Parallel With Grid contact is opened, with the control selected to
Isochronous, the load sharing lines relay K4 is closed immediately, to ensure
that all units will switch instantly to isochronous load sharing. In this case, the
transfer may not be completely bumpless, depending on the imported/exported
load, before the grid breaker was opened.
20 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Whilst operating in MW Control, provision is made for opening the Grid and
Generator Breakers in the event that the grid frequency has risen too high or
fallen too low. If the error between the Rated Speed and the actual engine
speed exceeds the Freq Error Set -point #1, the Open Grid Breaker
Command will be issued (if this hardware option has been chosen). If the error
exceeds the Freq Error Set point #2, the Generator Breaker Open Command
will be issued.
Direct MW Control:
The PID compares the measured MW to the MW reference, and adjusts the
actuator output accordingly.
Compensated MW Control:
The control is effectively in Droop mode. A dead band controller compares the
measured MW with the MW reference, and then will increase/decrease the
speed reference ramp, and hence increase/decrease the load on the engine.
Operating Modes
Whether the control is in Droop, Isochronous or MW Control mode, is
dependent on the status of certain contact inputs, and whether or not certain
analogue inputs are healthy. The table below indicates which mode of operation
the control will select, based on the status of the relevant digital and analogue
inputs.
Two sets of dynamics (Proportional Gain, Integral Gain & S.D.R) are provided:
Set #1 is active when the Generator CB Aux contact is open.
Set #2 is active when the Generator CB Aux contact is closed.
When the torsional filter is operational, if one of the speed sensors should fail,
the Proportional Gain is multiplied by the PropGain Multiplier, in order to attempt
to slow the control down, and prevent it responding to torsionals, for which the
torsional filter was enabled to help minimize.
22 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Direct MW Control
A single set of dynamics (Proportional Gain, Integral Gain & S.D.R.) for
operation in MW Control mode.
Actuator Hit
An ‘Actuator Hit’ function is provided for testing the dynamics of the control
during commissioning of the system. This function can be enabled in Configure
mode, and once the control has reset itself, the function is only available for a
30 minute period. When the appropriate parameter is toggled true using the
Operator Interface (HHT or PC-based), a tuneable value is subtracted from the
actuator output, for a tuneable period of time. This will enable the operator to
check that the dynamic settings are suitable. This is a better alternative to
physically disturbing the fuel rack to check the response of an engine, as it will
provide a consistent means of test.
The Run/Stop will only be effective for engine starting, provided that the engine
speed has fallen below 350Hz, and the Rundown Time period has elapsed.
Putting the Run/Stop contact will cause the control to limit the actuator output
to zero. If the Generator CB Aux is closed at this time, the control will also
issue a Generator Breaker Open Command.
Major Alarm
The Major Alarm will be activated:
if the Overspeed Trip level is exceeded
if both speed sensor inputs should fail
The relay contact will be opened continuously, unless the option for Pulse Alarm
is selected, in which case, the contact will be opened for the Pulse Alarm Time,
and will then be re-closed.
Minor Alarm
The Minor Alarm will be activated:
if one speed signal fails
if the MW Transducer input fails - below 1mA, above 22mA
if the MW Reference input fails - below 2mA, above 22mA
if the LON communications to the DSLC fail
if remote MW reference is selected using the Increase/Decrease contacts,
and a single signal is lost (wire-break)
if the Modbus serial communications have failed
if in MW Control, and the Frequency Limiter has come into effect
Rectification and reset of the fault, will reset the Minor Alarm.
Woodward 23
723 Generator Control 8280-576/-577 Manual 37807
In Configure mode, each input which is required via the Modbus instead, should
be individually selected.
DSLC
The 723 can be interface to the Woodward Digital Synchroniser & Load Control
(DSLC), via the LON (Local Operator Network), and via the Unit and/or Bus
Synchroniser inputs.
The only command given to the DSLC via the LON is the ‘Run’ synchroniser
command. However, via the LON, the 723 reads in all of the available generator
parameters, measured by the DSLC. These Boolean and analogue values can
be read via the 723 Modbus, or at the Operator Interface.
The speed bias from the DSLC should be fed into the Unit Synchroniser input
(or the Bus Synchroniser input if used).
The 723 may be configured so that the DSLC will control all load functions. In
this case, once the Generator CB Aux contact is closed, the 723 will be
switched into speed control mode (zero droop), with the speed reference biased
by the DSLC input (via the Unit Synchroniser input) in order to
increase/decrease actuator output to control the load on the engine.
Analogue Outputs
Through the 723 4–20 mA analogue outputs, it is possible to monitor any three
of the following:
Actuator Position (0–100%)
Engine Speed (rpm - 4mA & 20 mA set points configurable)
Engine Load (0–100%)
KW Reference (kW - 4mA & 20 mA set points configurable)
Speed Input #1 (rpm - 4mA & 20 mA set points configurable)
Speed Input #2 (rpm - 4mA & 20 mA set points configurable)
24 Woodward
Manual 37807 723 Generator Control 8280-576/-577
The analogue outputs are configured under the *ANALOG O/P CONFIG* menu
in Service.
Control Options
The following options are available with the 723 Generator Control:
Bus Synchroniser Input
Digital O/P #2 configurable for Minor Alarm (default) or Grid Breaker
Open Command - Configured using Operator Interface, all part numbers.
Digital I/P #8 configurable for Parallel With Grid (default) or Emergency
Load Rate - Configured using Operator Interface, all part numbers.
MW Control configurable as Direct (default) or Deadband - Configured
using Operator Interface, all part numbers.
Operator Interface
The parameters within the control may be configured and monitored using
either a Hand Held Programmer, or using the ServLink Server.
Woodward 25
723 Generator Control 8280-576/-577 Manual 37807
Chapter 4.
Configure/Service Value List
Introduction
Default
Configure Prompt Value Range Final Value
*SPEED SENSORS*
PULSE/REV #1 155 60 TO 360
MAXIMUM HZ #1 2500 500 TO 10000
PULSE/REV #2 155 60 TO 360
MAXIMUM HZ #2 2500 500 TO 10000
*ENGINE SPEED*
IDLE SPEED (rpm) 400.000 0.00 TO 2000.00
RATED SPEED (rpm) 750.000 0.00 TO 2000.00
OVERSPEED TRIP (rpm) 860.000 0.00 TO 2500.00
TORSIONAL FILTER? FALSE TRUE TO FALSE
*MW CONTROL*
REMOTE REF @ 4mA 0.000 0.00 TO 60.00
(MW)
REMOTE REF 20 mA (MW) 8.00 0.00 TO 60.00
SELECT INT kW REF FALSE TRUE TO FALSE
*FINAL DRIVER*
REVERSE ACTING? FALSE TRUE TO FALSE
ACTUATOR mA @ 0% 10.000 0.00 TO 200.00
ACTUATOR mA @ 100% 180.000 20.00 TO 200.00
ENABLE ACTUATOR HIT FALSE TRUE TO FALSE
STROKE ACTUATOR*F FALSE TRUE TO FALSE
*ENGINE LOAD*
RATED LOAD (MW) 6.52 0.00 TO 60.0
MW @ 4mA 0.000 -60 TO +60
MW @ 20 mA 8.00 0 TO 60
*CONFIGURE*
ENABLE SET POINTS TRUE TRUE TO FALSE
ENABLE CALIBRATION FALSE TRUE TO FALSE
26 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Default
Configure Prompt Value Range Final Value
*CONTROL OPTIONS*
GRID BRKR OPEN CMD? FALSE TRUE TO FALSE
EMERGENCY RATE I/P? FALSE TRUE TO FALSE
MW DEADBAND FALSE TRUE TO FALSE
CONTROL
ENABLE DSLC PM FALSE TRUE TO FALSE
ENABLE I/R SELECT FALSE TRUE TO FALSE
OPEN DI#1 TO RUN *F FALSE TRUE TO FALSE
DO#1 NC? *F FALSE TRUE TO FALSE
Failure to save set points prior to removing power from the control
will cause them to revert to the previously saved settings.
Default
Configure Prompt Value Range Final Value
*DISPLAY MENU*
ENGINE SPEED (rpm) (Monitor)
SPEED REFERENCE (rpm) (Monitor)
MW LOAD (Monitor)
ACTUATOR POSITION (%) (Monitor)
FUEL LIMIT (Monitor)
PID OUTPUT (Monitor)
ENGINE STOPPED (Monitor)
ENGINE RUNNING (Monitor)
READY TO SYNC (Monitor)
UNIT SYNC BIAS (Monitor)
SYS SYNC BIAS (Monitor)
DROOP BIAS (Monitor)
REF BEFORE BIAS (rpm) (Monitor)
GEN BREAKER CLOSED (Monitor)
ISOCHRONOUS MODE (Monitor)
% LOAD (Monitor)
LS LINES % (Monitor)
LOAD SHARE ERROR (Monitor)
KW CONTROL MODE (Monitor)
LOAD REFERENCE (MW) (Monitor)
REMOTE REF SELECTED (Monitor)
REMOTE REFERENCE (Monitor)
(MW)
MW LIMIT (Monitor)
Woodward 27
723 Generator Control 8280-576/-577 Manual 37807
Default
Configure Prompt Value Range Final Value
*MW DYNAMICS*
PROPORTIONAL GAIN 0.0100 0.01 TO 10.00
INTEGRAL GAIN (1/S) 1.300 0.01 TO 5.00
S.D.R. 20.000 0.01 TO 100.00
USE LOWER PROP BAND FALSE TRUE TO FALSE
*GAIN SLOPE* *F
LOAD BKPT #1 (%) 0.000 0.00 TO 110.00
MULTIPLIER #1 1.000 0.01 TO 10.00
LOAD BKPT #2 (%) 100.000 0.00 TO 110.00
MULTIPLIER #2 1.000 0.01 TO 10.00
*GAIN RATIO* *F
ERROR WINDOW #1 (rpm) 100.000 0.00 TO 110.00
GAIN RATIO #1 1.000 0.01 TO 10.00
ERROR WINDOW #2 (rpm) 10.000 0.00 TO 110.00
GAIN RATIO #2 2.000 0.01 TO 10.00
*DERIV DYNAMICS* *F
P DERIV BKPT #1 (rpm/s) 50.000 0.01 TO 500.00
P MULTIPLIER #1 1.000 0.01 TO 10.00
P DERIV BKPT #2 (rpm/s) 500.000 0.01 TO 500.00
P MULTIPLIER #2 2.000 0.01 TO 10.00
I DERIV BKPT #1 (rpm/s) 50.000 0.01 TO 500.00
I MULTIPLIER #1 1.000 0.01 TO 10.00
I DERIV BKPT #2 (rpm/s) 500.000 0.01 TO 500.00
I MULTIPLIER #2 1.000 0.01 TO 10.00
D DERIV BKPT #1 (rpm/s) 50.000 0.01 TO 500.00
D MULTIPLIER #1 1.000 0.01 TO 10.00
D DERIV BKPT #2 (rpm/s) 500.000 0.01 TO 500.00
D MULTIPLIER #2 1.000 0.01 TO 10.00
*ENGINE SPEED*
SPEED FILTER (Hz) 10.000 0.01 TO 16.00
FILTER FREQUENCY (Hz) 16.000 0.01 TO 16.00
FILTER Q FACTOR 0.707 0.707 TO 25.00
SENSOR WEIGHT 0.500 0.00 TO 1.00
ENGINE RUNNING (rpm) 150.000 0.00 TO 2500.00
TWO SPEED SENSORS? TRUE TRUE TO FALSE
DIS NOTCH FILTER FALSE TRUE TO FALSE
*SPEED REFERENCE*
MINIMUM SPEED (rpm) 700.000 0.00 TO 2000.00
MAXIMUM SPEED (rpm) 800.000 0.00 TO 2000.00
ACCEL/DECEL RATE 10.000 0.00 TO 2000.00
(rpm/s)
IDLE/RATED SWITCH 400.000 0.00 TO 2500.00
(rpm)
INC/DEC RATE #1 (rpm/s) 1.000 0.00 TO 2000.00
INC/DEC RATE #2 (rpm/s) 1.000 0.00 TO 2000.00
*START/STOP*
RUNDOWN TIME (s) 0.000 0.00 TO 300.00
PULSE/CONT ALARM? FALSE TRUE TO FALSE
ALARM PULSE TIME (s) 1.000 1.00 TO 30.00
BRKR OPEN CMD NC? FALSE TRUE TO FALSE
DIG O/P #2 NC? FALSE TRUE TO FALSE
28 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Default
Configure Prompt Value Range Final Value
*SYNCHRONISING*
RDY TO SYNC LIMITS 4.000 0.00 TO 20.00
(rpm)
SYNC OK DLY TIME (s) 2.000 0.00 TO 30.00
UNIT SYNCH GAIN 2.000 0.00 TO 100.00
REF BIAS PULSE (rpm) 0.000 0.00 TO 10.00
SYS SYNCH GAIN 2.000 0.00 TO 100.00
DISABLE UNIT SYNCH FALSE TRUE TO FALSE
*LOAD SHARING*
LS ERROR % 4.000 1.00 TO 100.00
LOAD GAIN 5.000 0.01 TO 100.00
AUTO LOAD RATE (kW/s) 50.000 0.00 TO 20000.00
EMERGENCY LOAD RATE 50.000 0.00 TO 20000.00
(kW/s)
AUTO UNLOAD RATE 5.000 0.00 TO 20000.00
(kW/s)
EMRGNCY UNLOAD RATE 50.000 0.00 TO 2000.00
(kW/s)
RE-LOAD TO ISOC? FALSE TRUE TO FALSE
*MW CONTROL*
AUTO LOAD RATE (kW/s) 30.00 0.00 TO 30000.00
AUTO UNLOAD RATE 50.000 0.00 TO 30000.00
(kW/s)
RAISE LOAD RATE (kW/s) 30.00 0.00 TO 30000.00
LOWER LOAD RATE 30.00 0.00 TO 30000.00
(kW/s)
ENABLE INSTANT RATE FALSE TRUE TO FALSE
INSTANT RATE WINDOW 300.00 0.00 TO 30000.00
(kW)
OVRD REMOTE IP FAIL FALSE TRUE TO FALSE
DEADBAND WINDOW 50.000 0.00 TO 1000.00
(kW)
D/B CTRL RAMP RATE 50.000 0.10 TO 5000.00
(kW/s)
INTERNAL MW REF RATE 1000 0.00 TO 30000
(kW) 3 0.00 TO 110.0
INTERNAL MW REF (%)
*ENGINE LOAD*
DROOP (%) 5.000 0.00 TO 15.00
FULL LOAD ACT % 80.000 0.00 TO 100.00
KW FILTER (Hz) 2.000 1.00 TO 10.00
LOAD FILTER (Hz) 2.000 1.00 TO 10.00
UNLOAD TRIP LEVEL (Kw) 100.000 -1000.00 TO
30000.00
OVRD LOAD I/P FAIL FALSE TRUE TO FALSE
Woodward 29
723 Generator Control 8280-576/-577 Manual 37807
Default
Configure Prompt Value Range Final Value
*FREQUENCY LIMITER*
BUS FREQUENCY 60.000 45.00 TO 65.00
MW LIMITER HZ #1 0.000 0.00 TO 60.00
MW LIMITER HZ #2 10.000 10.00 TO 60.00
MAXIMUM LOAD (1) (MW) 10.000 0.00 TO 50.00
MW LIMITER HZ #3 90.000 0.00 TO 100.00
MAXIMUM LOAD (2) (MW) 10.000 0.00 TO 50.00
MW LIMITER HZ #4 100.000 50.00 TO 100.00
FREQ ERROR SP#1 (Hz) 5.000 0.00 TO 10.00
FREQ ERROR SP#2 (Hz) 5.000 0.00 TO 10.00
TRIP DELAY (s) 0.100 0.00 TO 3.00
*FUEL LIMITERS*
START FUEL LIMIT X1 0.000 0.00 TO 2000.00
(rpm)
START FUEL LIMIT Y1 (%) 80.000 0.00 TO 100.00
START FUEL LIMIT X2 100.000 0.00 TO 2000.00
(rpm)
START FUEL LIMIT Y2 (%) 80.000 0.00 TO 100.00
START FUEL LIMIT X3 100.000 0.00 TO 2000.00
(rpm)
START FUEL LIMIT Y3 (%) 50.000 0.00 TO 100.00
START FUEL LIMIT X4 750.000 0.00 TO 2000.00
(rpm)
START FUEL LIMIT Y4 (%) 50.000 0.00 TO 100.00
MAXIMUM FUEL LIMIT (%) 100.000 0.00 TO 100.00
*FINAL DRIVER*
HIT ACTUATOR FALSE TRUE TO FALSE
ACTUATOR HIT PULSE 0.100 0.00 TO 2.00
ACTUATOR HIT VALUE 0.000 0.00 TO 100.00
STROKE ACTUATOR 0.000 0.00 TO 100.00
(%)*F
*CALIBRATION*
REMOTE I/P OFFSET 0.000 -10.00 TO 10.00
REMOTE I/P GAIN 1.000 0.00 TO 10.00
LOAD I/P OFFSET 0.000 -10.00 TO 10.00
LOAD I/P GAIN 1.000 0.00 TO 10.00
LS LINES OFFSET 0 0 TO 32767
LS LINES GAIN 21845 0 TO 32767
LS LOAD OFFSET 2028 0 TO 32767
LS LOAD GAIN 8083 0 TO 32767
30 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Default
Configure Prompt Value Range Final Value
*SERVLINK SETUP*
HARDWARE CONFIG 1 1 TO 2
BAUD RATE 9 1 TO 12
*MAJOR ALARM*
OVERSPEED (Monitor)
BOTH SPD SEN FAILED (Monitor)
*MINOR ALARM*
KW SENSOR FAILURE (Monitor)
REM REF FAILURE (Monitor)
SPEED SENSOR FAULT (Monitor)
MODBUS COMMS (Monitor)
KW LIMITING (Monitor)
Woodward 31
723 Generator Control 8280-576/-577 Manual 37807
Default
Configure Prompt Value Range Final Value
*DSLC ANALOGUES*
GEN A-PHASE VOLTAGE (Monitor)
(Volts)
GEN B-PHASE VOLTAGE (Monitor)
(Volts)
GEN C-PHASE VOLTAGE (Monitor)
(Volts)
BUS A-PHASE VOLTAGE (Monitor)
(Volts)
GEN A-PHASE CURRENT (Monitor)
(Amps)
GEN B-PHASE CURRENT (Monitor)
(Amps)
GEN C-PHASE CURRENT (Monitor)
(Amps)
POWER FACTOR (Monitor)
REAL POWER (kW) (Monitor)
REACTIVE POWER (kVAR) (Monitor)
APPARANT POWER (kVA) (Monitor)
GENERATOR (Monitor)
FREQUENCY (Hz)
BUS FREQUENCY (Hz) (Monitor)
*DSLC BOOLEANS*
DSLC ALARM OUTPUT (Monitor)
VOLTAGE LOWER (Monitor)
OUTPUT
VOLTAGE RAISE OUTPUT (Monitor)
BREAKER CLOSE O/P (Monitor)
SYNC TIMEOUT ACTIVE (Monitor)
SYNC RECLOSE ACTIVE (Monitor)
LOAD HIGH LIMIT (Monitor)
LOAD LOW LIMIT (Monitor)
VOLTAGE RANGE (Monitor)
VOLTAGE LOW LIMIT (Monitor)
VOLTAGE HIGH LIMIT (Monitor)
SS OFF (Monitor)
SS CHECK (Monitor)
SS PERMISSIVE (Monitor)
SS RUN (Monitor)
SS CLOSE TIMER (Monitor)
SS SYNC TIMER (Monitor)
SS SYNCHRONISED (Monitor)
SYNCH CHECK I/P (Monitor)
SYNCH PERM I/P (Monitor)
SYNCH RUN I/P (Monitor)
CB AUX I/P (Monitor)
VOLTS RAISE I/P (Monitor)
VOLTS LOWER I/P (Monitor)
32 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Maximum Hz #1 & #2 allows tuning of the speed sensing algorithm, to obtain the
optimum resolution for sensing speed. It is important that
the following instructions for tuning these parameters is
adhered to.
The Maximum Hz should be calculated based on both the
minimum and maximum controlling speeds:
Maximum Speed x Pulse/Rev x 1.3 = A
60
Minimum Speed x Pulse/Rev x 4 = B
60
If B > A then use A as the Maximum Hz. Calculate
separately for each speed sensor input, if Pulse/Rev #1 &
Pulse/Rev #2 are different.
If B < A then use B as the Maximum Hz, provided that B is
greater then 1.1 x Overspeed Trip Frequency. If not, then
contact Woodward Governor for further assistance.
*ENGINE SPEED*
*MW CONTROL*
Remote Ref @ 4mA, Remote is the MW reference required at 4mA and 20 mA by the
Ref @ 20 mA (MW) remote reference input.
Select Int kW Ref if selected true, will enable the use of an internal MW
reference value (if the remote reference is not selected.)
*FINAL DRIVER*
Reverse Acting? if selected true, will reverse the actuator output signal to
200-0 mA for 0–100%.
Actuator mA @ 100% sets the mA output required to the actuator at 100% control
(PID) output.
Woodward 33
723 Generator Control 8280-576/-577 Manual 37807
Enable Actuator Hit if selected true, will enable the function to hit the actuator
down by a certain amount, for a certain period of time. This
is for testing and proving the dynamic set-up of the control.
Once this parameter has been selected true, it will only
remain activated for 30 minutes. After this time, to re-enable
the function, the parameter will have to be re-set to true.
*ENGINE LOAD*
Slave Address sets the network address of the control. This will always be
set to 1 for Point-to-Point communications.
*CONFIGURE*
Enable Set Points if selected false, will prevent all Service set point menus
from being displayed, and therefore prevents adjustment.
This parameter would normally be set false, once the
control has been commissioned.
Start/Stop, Inc/Dec/Sel Remote, this menu is for configuring whether certain control inputs
Unload & Idle/Rated, are received via the standard hardware, or via the Modbus.
Droop/Isochronous, To select that they are received via the Modbus, set the
parameter true.
Select KW Control Emergency
Load Rate, Reset, Remote KW
Reference
*CONTROL OPTIONS*
Grid Brkr Open Cmd? if selected true, digital output #2 will be configured as the
Grid Breaker Open Command output, instead of the Minor
Alarm.
Emergency Rate I/P? if selected true, digital input #8 (H) will be configured as the
Emergency Load Rate selection input, instead of the
Parallel with Grid breaker status.
34 Woodward
Manual 37807 723 Generator Control 8280-576/-577
KW Deadband Control if selected true, kW control will be as compensated droop
via the speed reference (see description in system
description text).
Enable DSLC PM if selected true, disables the power management of the 723,
and allows the 723 to follow the ‘Unit Synchroniser’ input
after the breaker has closed. This will enable the DSLC to
handle the isochronous load sharing and base loading of
the system, without interference from the 723.
Enable I/R Select if selected true, allows the Unload contact input to be
utilised as an Idle/Rated contact whilst the CB Aux input is
open.
DO#1 NC? if true, digital output #1 will be normally closed, i.e. contact
will open when a major alarm occurs.
Service
*DISPLAY MENU*
Speed Reference (rpm) is the rpm reference, after the droop has been taken into account, if
in droop mode, or taking into account the error bias if in
isochronous mode.
Engine Running indicates that the engine speed is above the Engine Running speed
switch.
Ready To Sync indicates that the engine has reached Rated Speed and has
remained within the window for the required time.
Unit Sync Bias is the rpm bias from the unit synchroniser input.
Sys Sync Bias is the rpm bias from the system synchroniser input.
Ref Before Bias (rpm) is the rpm speed reference before any biases (synch or droop) are
taken into account.
Gen Breaker Closed indicates that the Generator CB Aux input is closed.
Woodward 35
723 Generator Control 8280-576/-577 Manual 37807
Isochronous Mode displays the status of the load sharing lines relay, which connects
the unit load sharing lines to the system load sharing lines. If true is
displayed, the control is in Isochronous mode.
Load Share Error is the error calculated between the % load on the load sharing
lines, and the % unit load.
Remote Ref Selected indicates that the remote MW reference has been selected.
Proportional Gain #1 PID proportional gain adjustment for the dynamics gain. Increasing
the P term increases the gain, a value for P that is too large will
cause oscillation, if P is too small the offset from a transient will be
too large.
Integral Gain #1 (1/s) PID integrator rate adjustment for the dynamics, affects kW
recovery rate after a transient. A value for I that is too small will
change the actuator current slowly and speed will take a long time
to return to set speed after a transient, giving overdamped
response. If I is too large the actuator current will move too fast and
speed will overshoot and response will be underdamped.
S.D.R. #1 PID derivative ratio adjustment for the dynamics, when the
Generator CB Aux input is open. Set the amount of derivative (or
lead) action the control will have. Increasing the derivative ratio
value above 1 will decrease the derivative function giving the
control a PI type action. A value too large will make the system less
responsive. A value too small will make the system oscillate, and
cannot be compensated for with the proportional gain or the
integrator rate.
Dyn Select Delay (s) is the delay period for switching from Dynamics #2 to Dynamics #1,
after the Generator CB Aux contact input is opened.
Dyn Select Delay (s) is the delay period for switching from Dynamics #2 to Dynamics #1,
after the Generator CB Aux contact input is opened.
36 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Enable Deriv Dyn If true, the Gain Ratio function will be switched out, and the
Derivative Dynamics function will be switched in. Both functions are
multiplying, and will work on whichever dynamics is switched in at
the time (#1 or #2). The Gain Ratio multiplies the Proportional Gain,
based on the speed error, whilst the Derivative Dynamics multiplies
all three PID terms (individually tuneable), based on the rate of
change of engine speed.
Example:
Proportional Gain #2 PID proportional gain adjustment for the dynamics gain, when the
Generator CB Aux input is closed. Increasing the P term increases
the gain, a value for P that is too large will cause oscillation, if P is
Integral Gain #2 (1/s) PID integrator rate adjustment for the dynamics, affects recovery
rate after a transient, when the Generator CB Aux input is closed. A
value for I that is too small will change the actuator current slowly
and speed will take a long time to return to set speed after a
transient, giving overdamped response. If I is too large the actuator
current will move too fast and speed will overshoot and response
will be underdamped.
SDR #2 PID derivative ratio adjustment for the dynamics, when the
Generator CB Aux input is closed. Set the amount of derivative (or
lead) action the control will have. Increasing the derivative ratio
value above 1 will decrease the derivative function giving the
control a PI type action. A value too large will make the system less
responsive. A value too small will make the system oscillate, and
cannot be compensated for with the proportional gain or the
integrator rate.
Propgain Multiplier This value of this parameter determines the value of gain in the
control, should a speed sensor fail when the torsional filter is
enabled, and the Generator CB Aux input closed. The purpose of
this parameter is to slow the PID down in the event of the torsional
filter being disabled, when a speed sensor fails. Gain Value =
Propgain Multiplier * Proportional
*KW DYNAMICS*
(For MW control)
Proportional Gain PID proportional gain adjustment for the dynamics gain, when in
MW control mode. Increasing the P term increases the gain, a
value for P that is too large will cause oscillation, if P is too small
the offset from a transient will be too large.
Woodward 37
723 Generator Control 8280-576/-577 Manual 37807
Integral Gain (1/s) PID integrator rate adjustment for the dynamics, affects recovery
rate after a transient, when in MW Control mode. A value for I that
is too small will change the actuator current slowly and speed will
take a long time to return to set speed after a transient, giving over
damped response. If I is too large the actuator current will move too
fast and speed will overshoot and response will be under damped.
Use Lower Prop. Band If selected true proportional value of kW dynamics is divided by 10
internally.
*GAIN SLOPE*
Load Bkpt #1 (%) This is the load breakpoint associated with 'Multiplier #1', for the
curve set up to calculate a proportional gain multiplier, which is
dependent on the engine load. At loads between points #1 & #2,the
multiplier is increased/decreased linearly between these two points.
For values of load at, or less than, breakpoint #1, the multiplier will
be 'Multiplier #1'.
Multiplier #1 This is the multiplier, associated with 'Load Bkpt #1', for the
calculation of the gain multiplier.
Load Bkpt #2 (%) This is the load breakpoint associated with 'Multiplier #2', for the
curve set up to calculate a proportional gain multiplier, which is
dependent on the engine load. At loads between points #1 & #2,
the multiplier is increased/decreased linearly between these two
points.
For values of load at, or greater than, breakpoint #2, the multiplier
will be 'Multiplier #2'.
Multiplier #2 This is the multiplier, associated with 'Load Bkpt #2', for the
calculation of the gain multiplier.
38 Woodward
Manual 37807 723 Generator Control 8280-576/-577
*GAIN RATIO*
Error Window #1 (rpm) This value is the magnitude of a speed error at which the control
automatically switches to fast response, whilst the Generator CB
Aux input is open. The control does not use the absolute value of
speed error, but ‘anticipated’ speed error to make this switch. This
method provides for quick switching to the low gain value when
recovering from the speed transient. This provides smoother
switching than if the absolute speed error was used for the window.
Gain Ratio #1 This sets the ratio of the gain setting at steady state to the gain
setting during transient conditions, whilst the Generator CB Aux
input is open. The Gain Ratio operates in conjunction with the Error
Window and Proportional Gain adjustments, by multiplying the
Proportional Gain set point by the Gain Ratio when the speed error
is greater than the Error Window. This makes the control dynamics
fast enough to minimize engine speed overshoot on start-up and to
reduce the magnitude of speed error when loads are changing. This
allows a lower gain at steady state for better stability and reduced
steady-state actuator linkage movement. The Gain Ratio function is
disabled, if the Derivative Dynamics are enabled, and vice versa.
Error Window #2 (rpm) This value is the magnitude of a speed error at which the control
automatically switches to fast response, whilst the Generator CB
Aux input is closed. The control does not use the absolute value of
speed error, but ‘anticipated’ speed error to make this switch. This
method provides for quick switching to the low gain value when
recovering from the speed transient. This provides smoother
switching than if the absolute speed error was used for the window.
Gain Ratio #2 This sets the ratio of the gain setting at steady state to the gain
setting during transient conditions, whilst the Generator CB Aux
input is closed. The Gain Ratio operates in conjunction with the
Error Window and Proportional Gain adjustments, by multiplying the
Proportional Gain set point by the Gain Ratio when the speed error
is greater than the Error Window. This makes the control dynamics
fast enough to minimize engine speed overshoot on start-up and to
reduce the magnitude of speed error when loads are changing. This
allows a lower gain at steady state for better stability and reduced
steady-state actuator linkage movement. The Gain Ratio function is
disabled, if the Derivative Dynamics are enabled, and vice versa.
Woodward 39
723 Generator Control 8280-576/-577 Manual 37807
*DERIV DYNAMICS*
P Deriv Bkpt #1 (rpm/s) This value is breakpoint #1 which relates to 'P Multiplier #1' of the
curve to determine the Proportional Gain multiplier, based on the
engine speed derivative (rate of change of speed). (rpm/s)
P Multiplier #1 This value is the multiplier #1 which relates to 'P Deriv Bkpt #1'of
the curve to determine the Proportional Gain multiplier, based on
the engine speed derivative (rate of change of speed).
P Deriv Bkpt #2 (rpm/s) This value is the breakpoint #2 which relates to 'P Multiplier #2'of
the curve to determine the Proportional Gain multiplier,
Based on the engine speed derivative (rate of change of speed).
(rpm/s)
Multiplier #2 This value is the multiplier #2 which relates to 'P Deriv Bkpt #2'of
the curve to determine the Proportional Gain multiplier, based on
the engine speed derivative (rate of change of speed).
I Deriv Bkpt #1 (rpm/s) This value is breakpoint #1 which relates to 'I Multiplier #1' of the
curve to determine the Integral Gain multiplier, based on the engine
speed derivative (rate of change of speed). (rpm/s)
I Multiplier #1 This value is the multiplier #1 which relates to 'I Deriv Bkpt #1' of
the curve to determine the Integral Gain multiplier, based on the
engine speed derivative (rate of change of speed).
I Deriv Bkpt #2 (rpm/s) This value is the breakpoint #2 which relates to 'I Multiplier #2' of
the curve to determine the Integral Gain multiplier, based on the
engine speed derivative (rate of change of speed). (rpm/s)
I Multiplier #2 This value is the multiplier #2 which relates to 'I Deriv Bkpt #2' of
the curve to determine the Integral Gain multiplier, based on the
engine speed derivative (rate of change of speed).
D Deriv Bkpt #1 (rpm/s) This value is breakpoint #1 which relates to 'D Multiplier #1' of the
curve to determine the S.D.R. multiplier, based on the engine
speed derivative (rate of change of speed). (rpm/s)
D Multiplier #1 This value is the multiplier #1 which relates to 'D Deriv Bkpt #1'of
the curve to determine the S.D.R. multiplier, based on the engine
speed derivative (rate of change of speed).
D Deriv Bkpt #2 (rpm/s) This value is the breakpoint #2 which relates to 'D Multiplier #2'of
the curve to determine the S.D.R. multiplier, based on the engine
speed derivative (rate of change of speed). (rpm/s)
D Multiplier #2 This value is the multiplier #2 which relates to 'D Deriv Bkpt #2'of
the curve to determine the S.D.R. multiplier, based on the engine
speed derivative (rate of change of speed).
*ENGINE SPEED*
Speed Filter (Hz) Normally, this value should not need to be adjusted, but can be
used to filter any undesirable frequencies on the speed pickups. If
tuned above 15.9Hz, the filter will automatically be disabled.
Filter Frequency (Hz) should be set to the resonant frequency of the speed signal which
requires filtering by the band-stop (notch) filter.
40 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Filter Q Factor adjusts the attenuation of the signal frequency, filtered by the band-
stop filter. The minimum value of 0.707 results in zero attenuation,
and as the value is increased, the attenuation is increased, and the
range of frequencies affected broadens.
Sensor Weight When using the torsional filter, it is possible to weight one speed
sensor input more heavily than the other. If this value is set
between 0.5 and 1, sensor #1 will be weighted more heavily then
sensor #2. Between 0 and 0.5, sensor #2 will be more heavily
weighted.
Engine Running (rpm) is the speed above which the engine is assumed to be running, for
monitoring purposes.
Two Speed Sensors? if selected false, the minor alarm relay will not be activated, should
a speed sensor input fail. The Alarm LED on the front of the 723
however, will still illuminate, as the failure is continuously detected.
The purpose of this parameter, is to prevent the minor alarm
activating, when only one speed pickup is used.
Dis Notch Filter if selected true will disable the Notch Filter.
*SPEED REFERENCE*
Minimum Speed (rpm) is the lowest rpm value to which the speed reference may be driven
by closing the Decrease Speed/Load contact input.
Maximum Speed (rpm) is the maximum value to which the speed reference may be driven
by closing the Increase Speed/Load contact input.
Accel/Decel Rate is the rate at which the speed reference ramps from Idle Speed to
(rpm/s) Rated Speed, and from Rated Speed to Idle Speed.
Idle/Rated Switch (rpm) The speed reference will start to ramp to the Rated Speed when
this switch speed is exceeded. It is recommended that this
parameter is tuned to a value slightly lower than the Idle Speed.
Inc/Dec Rate #1 (rpm/s) is the rate at which the speed reference is increased/decreased
using the Increase/Decrease contacts, when the Generator CB Aux
contact is open.
Inc/Dec Rate #2 (rpm/s) is the rate at which the speed reference is increased/decreased
using the Increase/Decrease contacts, when the Generator CB Aux
contact is closed.
*START/STOP*
Rundown Time (s) After a shutdown, this is the period for which the engine speed
must be below 350Hz, before the control will recognize the ‘run’
command.
Pulse/Cont Alarm? if selected true, the major alarm relay will de-energize for the Alarm
Pulse Time if a shutdown condition occurs. If false, the alarm will
remain latched, until the next ‘run’ command is received.
Woodward 41
723 Generator Control 8280-576/-577 Manual 37807
Alarm Pulse Time (s) If the above option is selected true, this is the period for which the
major alarm relay output is de-energized.
Brkr Open Cmd NC? if selected true will set the output relay for the Breaker Open
Command as normally energised, and so when the breaker open
command is issued by the control, the relay is de-energised and
hence the contact opened.
Dig O/P #2 NC? if selected true will set the Digital Relay Output #2 as normally
energised, and so when the function for this output is activated
(Minor Alarm or Open Grid Breaker) by the control, the relay is de-
energised and hence the contact opened.
*SYNCHRONISING*
Rdy To Sync Limits is the synchronising speed window that the engine speed must be
(rpm) within.
Sync OK Dly Time (s) is the time duration that the engine must be running within the
Unit Synch Gain Adjustment of this value will increase or decrease the effect of the
analogue unit synchroniser input to the speed reference.
Ref Bias Pulse (rpm) is the value added to the speed reference, instantly, when the
generator breaker is closed. This is for a droop system, to ensure
that the generator is not driven into reverse power as soon as the
breaker is closed.
Sys Synch Gain Adjustment of this value will increase or decrease the effect of the
analogue bus tie synchroniser input to the speed reference.
Disable Unit Synch Select true if not using a Woodward Analogue synchroniser for
synchronisation between the generator and the bus.
Disable Sys Synch Select true if not using a Woodward Analogue synchroniser for bus
synchronisation.
Sync Filter (Hz) is for filtering the unit synchroniser input to the control.
*LOAD SHARING*
Auto Load Rate (kW/s) is the rate at which load is increased when soft loading into
isochronous load sharing.
Emergency Load Rate is the rate at which load is increased when soft loading into
(kW/s) isochronous load sharing, with the Emergency Loading Rate
contact closed.
42 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Auto Unload Rate is the rate at which load is decreased when soft unloading into
(kW/s) isochronous load sharing, from droop control. Also when using the
Unload feature to shed load and open the generator breaker.
Emergency Unload Rate is the rate at which load is decreased when soft unloading into
(kW/s) isochronous load sharing, from droop control, with the Emergency
Loading Rate contact closed. Also using the Unload feature to shed
load, with the Emergency Loading Rate contact closed.
*MW CONTROL*
Auto Load Rate (kW/s) is the rate at which load is increased when soft loading into remote
kW control.
Auto Unload Rate is the rate at which load is decreased when the Unload function is
(kW/s) used to shed load and open the generator breaker.
Raise Load Rate (kW/s) is the rate at which the kW reference is increased when in kW
control.
Lower Load Rate (kW/s) is the rate at which the kW reference is decreased when in kW
control.
Enable Instant Rate if selected true, when using the remote kW reference, once the
error between the kW and the kW reference is within the window,
the kW reference will change instantly as the remote reference
changes, all ramp rates will be overridden. This is useful when the
remote reference input is utilised to adjust the kW reference to
control Import/Export levels.
Instant Rate Window is the window applied to the Instant Rate function above.
(kW)
Ovrd Remote I/P Fail if selected true, will override the failed signal detection of the
remote kW reference input. When the remote reference input is
disabled, it is not possible to select remote reference kW control.
Deadband Window (kW) If the kW error is within this window, and Deadband KW Control is
enabled, no action will be taken to correct the error.
D/B Ctrl Ramp Rate If Deadband KW Control is enabled, this is the rate at which the
(kW/s) speed reference is increased/decreased to control the MW level.
Int MW Ref Rate (kW/s) If the internal MW reference is selected, this is the rate at which the
reference is ramped to the ‘Internal MW Ref’ level.
Internal MW Ref (%) This is the level to which the MW reference will ramp, when the
control is switched into MW Control mode, and the remote
reference is not selected, if the option has been selected in
Configure.
Woodward 43
723 Generator Control 8280-576/-577 Manual 37807
*ENGINE LOAD*
Droop (%) is the % of rated speed by which the speed reference is drooped at
zero to full load.
KW Filter (Hz) is the filter value. This value should not need to be adjusted, but
can be used to filter any undesirable frequencies picked up by the
MW transducer.
Load Filter (Hz) is the filter value. This value should not need to be adjusted, but
can be used to filter the internally derived position feedback.
Unload Trip Level (kW) When the control is in isochronous load sharing or MW control
mode, and the Unload command is given, the load will be
decreased to this level before the generator breaker open
command is issued.
Ovrd Load I/P Fail if selected true, will override the failed signal detection of the MW
transducer input. When the load input is disabled, isochronous load
sharing is not possible, and droop control is based on the actuator
position.
*FREQUENCY
LIMITER*
Bus Frequency (Hz) selects the frequency of the bus, normally set at 50 or 60Hz.
KW Limiter Hz #1, #2, These tuneable set-up the curve for the frequency limiter. See
#3 & #4, Maximum Load diagram below:
1 & 2 (MW).
Freq Error SP#1 is the frequency error (difference between actual bus frequency and
normal bus frequency) above which the Grid Breaker Open
command is issued.
Freq Error SP#2 is the frequency error (difference between actual bus frequency and
normal bus frequency) above which the Generator Breaker Open
command is issued.
Trip Delay (s) is the period of delay between detection and breaker open
command, if Freq Error SP#2 is exceeded.
44 Woodward
Manual 37807 723 Generator Control 8280-576/-577
*FUEL LIMITERS*
Start Fuel Limit X1..X4 is the maximum % actuator output during engine start-up. This
(rpm), Start Fuel Limit should be set to value which gives optimum start characteristics,
Y1..Y4 (%) while minimizing smoke emissions due to over fuelling. A four point
curve is provided to allow different fuel limiting levels at different
speeds. e.g.
Maximum Fuel Limit (%) is the maximum % actuator output during normal engine operation.
This limit should normally be set just above the output at full load.
*FINAL DRIVER*
Hit Actuator, Actuator If the Actuator Hit has been enabled, when the Hit Actuator
Hit Pulse (s), Actuator parameter is tuned TRUE, the Actuator Hit Value will be subtracted
Hit Value (%) from the % actuator output, for a period of time (Actuator Hit Pulse).
This function is available for the purpose of testing and proving
dynamic set-up.
Stroke Actuator (%) If the configurable Stroke Actuator has been selected true, the
engine is stopped, and the Run/Stop contact is in the Stop
position, by adjusting this value, the actuator output can be
increased and decreased in order to calibrate an electric
actuator.
Load Rej Level (%) If the CB Aux contact is opened whilst the load is above this value,
the actuator will be forced to 0% for the Load Rej Period, as
determined by the curve set-up below.
Woodward 45
723 Generator Control 8280-576/-577 Manual 37807
Load Level 1..2 (%),
Rejection Period 1..2 (s)
Load Rej Level (%) If the Parallel with Grid contact is opened whilst the load is above
this value, the actuator will be forced to 0% for the Load Rej Period,
as determined by the curve set-up below.
Enable Load Rej if selected true, will enable the load rejection pulse function, caused
by the grid breaker opening.
*CALIBRATION*
46 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Load I/P Gain If it is necessary to calibrate the MW transducer input, adjustment
of this parameter will alter the gain.
LS Load Offset If it is necessary to calibrate load output to the load sharing lines,
adjustment of this parameter will alter the offset. To calibrate the
load output to the load sharing lines, contact
Woodward Governor for further information.
LS Load Gain If it is necessary to calibrate the load output to the load sharing
lines, adjustment of this parameter will alter the gain.
Air I/P Offset If it is necessary to calibrate the input, adjustment of this parameter
will alter the offset.
To calibrate the input, set the mA to zero, and ensure that the
control is measuring zero. If not, adjust the offset until it does. Then
set the mA input to 20 mA. Ensure that the control is measuring 20.
If not, adjust the gain until it does. Return the mA input to zero, and
check that the control is still measuring zero. If not, repeat the
calibration process.
Air I/P Gain If it is necessary to calibrate the input, adjustment of this parameter
will alter the gain.
An O/P #1 Offset This parameter is the offset term, for calibration of analogue
output #1 (terminals 15 & 16).If it is necessary to calibrate the
output, set the parameter' Analogue Output #1' (in menu *ANALOG
O/P CONFIG*) to 7.Then adjust the 'An O/P Calibration' term to
zero, and measure the current from output #1. If it is not zero, then
adjust the offset term. Then adjust the 'An O/P Calibration' term to
20, and check the current again. If it does not read 20, then adjust
the gain term. Return to zero, and check again, and work through
the calibration process again if necessary.
An O/P #1 Gain This parameter is the gain term, for calibration of analogue
output#1 (terminals 15 & 16).
An O/P #2 Offset This parameter is the offset term, for calibration of analogue
output #2 (terminals 17 & 18). If it is necessary to calibrate the
output, set the parameter' Analogue Output #2' (in menu *ANALOG
O/P CONFIG*) to 7.Then adjust the 'An O/P Calibration' term to
zero, and measure the current from output #2. If it is not zero, then
adjust the offset term. Then adjust the 'An O/P Calibration' term to
20, and check the current again. If it does not read 20, then adjust
the gain term. Return to zero, and check again, and work through
the calibration process again if necessary.
An O/P #2 Gain This parameter is the gain term, for calibration of analogue output
#2 (terminals 17 & 18).
Woodward 47
723 Generator Control 8280-576/-577 Manual 37807
An O/P #3 Offset This parameter is the offset term, for calibration of analogue
output #3 (terminals 19 & 20). If it is necessary to calibrate the
output, set the parameter 'Analogue Output #3' (in menu *ANALOG
O/P CONFIG*) to 7. Then adjust the 'An O/P Calibration' term to
zero, and measure the current from output #3. If it is not zero, then
adjust the offset term. Then adjust the 'An O/P Calibration' term to
20, and check the current again. If it does not read 20, then adjust
the gain term. Return to zero, and check again, and work through
the calibration process again if necessary.
An O/P #3 Gain This parameter is the gain term, for calibration of analogue output
#3 (terminals 19 & 20).
*MODBUS PORT
SETUP*
Baud Rate sets the desired baud rate, an integer number in the range 1 to 7 is
to be used representing: 1=1200, 2=1800, 3=2400, 4=4800,
5=9600, 6=19200, 7=38400. The preferred baud rate is 9600. If the
chosen baud rate is 38400, then both J2 and J3 must be set
identical.
Stop Bits sets the desired number of stop bits, an integer number in the
range 1 to 3 is to be used representing: 1=1, 2=1.5, 3=2
Enable Modbus Alms If set false, communications errors are ignored by the control.
*SERVLINK SETUP*
Baud Rate sets the desired baud rate, an integer number in the range 1 to 10
is to be used representing: 1=110, 2=300, 3=600, 4=1200, 5=1800,
6=2400, 7=4800, 8=9600, 9=19200, 10=38400. The preferred baud
rates are 9600 and 19200.
*DSLC COMMS
SETUP*
DSLC Service Pin must be toggled true/false when prompted, during LON binding
procedure. This should only be required during initial
commissioning.
48 Woodward
Manual 37807 723 Generator Control 8280-576/-577
DSLC Xmit Time is the time period between transmissions from the 723 to the DSLC.
Reset LON is available for manually re-setting the LON in the event that it
becomes necessary.
*ANALOG O/P
CONFIG*
Analogue Output #1..#3 These will select the parameters which are output through the three
analogue output channels of the 723. 1=Actuator Position,
2=Engine Speed, 3=Percentage Load, 4=KW Reference, 5=Speed
#1, 6=Speed #2.
Eng Speed O/P @4mA, are for scaling the parameters output via the analogue 4–20 mA
Eng Speed O/P @ 20 outputs.
mA, KW Ref O/P @
4mA, KW Ref O/P @ 20
mA, Speed 1 O/P
@4mA, Speed 1 O/P
@20 mA, Speed 2 O/P
@ 4mA, Speed 2 O/P @
20 mA
*MAJOR ALARM*
this menu will only be displayed, if a Major Alarm has occurred.
Overspeed if true, the engine speed has reached the Overspeed Trip level.
Both Spd Sen Failed if true, both speed sensors have failed, i.e. below the Low Set -
point.
*MINOR ALARM*
this menu will only be displayed, if a Minor Alarm has occurred.
KW Sensor Failure if true, the analogue load input has failed, i.e. below 1mA, above
22mA.
Rem Ref Failure if true, the analogue remote reference input has failed, below 2mA,
above 22mA
Speed Sensor Fault if true, a speed sensor has failed, i.e. below the 250Hz
Rem Sel Wire Break if true, following the selection of remote MW reference (closure of
both Increase & Decrease contacts), a single wire has been
disconnected or broken. Both contacts must be broken to de-select
remote kW reference.
DSLC Comms Fault if true, there has been a communications failure between the 723
and the DSLC.
*DSLC ANALOGUES*
this menu will display all of the necessary and relevant analogue
parameters, read in from the DSLC.
*DSLC BOOLEANS*
this menu will display all of the necessary and relevant Boolean
parameters, read in from the DSLC.
Woodward 49
723 Generator Control 8280-576/-577 Manual 37807
Failure to save set points prior to removing power from the control
will cause them to revert to the previously saved settings.
Boolean Reads
Address Description
1:0001 *MAJOR/SHUTDOWN ALARM*
1:0002 *MINOR ALARM*
1:0003
1:0004
1:0005
1:0006 OVERSPEED - SD
1:0007 BOTH SPEED SENSORS FAILED - SD
1:0008
1:0009
1:0010 KW SENSOR FAILURE - MINOR
1:0011 REMOTE REFERENCE FAILURE - MINOR
1:0012 SPEED SENSOR FAILURE - MINOR
1:0013 KW LIMITING - MINOR
1:0014 REMOTE SELECT, WIRE BREAK - MINOR
1:0015 DSLC COMMS FAULT
1:0016
1:0017
1:0018
1:0019 ENGINE STOPPED
1:0020 ENGINE RUNNING
1:0021 READY TO SYNCHRONISE
1:0022 GENERATOR BREAKER CLOSED
1:0023 ISOCHRONOUS MODE
1:0024 KW CONTROL MODE
1:0025 REMOTE REFERENCE SELECTED
1:0026
1:0027
1:0028
1:0029 DSLC ALARM OUTPUT
1:0030 DSLC VOLTAGE LOWER OUTPUT
50 Woodward
Manual 37807 723 Generator Control 8280-576/-577
1:0031 DSLC VOLTAGE RAISE OUTPUT
1:0032 DSLC BREAKER CLOSE OUTPUT
1:0033 DSLC SYNC TIMEOUT ACTIVE
1:0034 DSLC SYNC RECLOSE ACTIVE
1:0035 DSLC LOAD HIGH LIMIT
1:0036 DSLC LOAD LOW LIMIT
1:0037 DSLC VOLTAGE RANGE
1:0038 DSLC VOLTAGE LOW LIMIT
1:0039 DSLC VOLTAGE HIGH LIMIT
1:0040 DSLC SYNCH STATE OFF
1:0041 DSLC SYNCH STATE CHECK
1:0042 DSLC SYNCH STATE PERMISSIVE
1:0043 DSLC SYNCH STATE RUN
1:0044 DSLC SYNCH STATE CLOSE TIMER
1:0045 DSLC SYNCH STATE SYNC TIMER
1:0046 DSLC SYNCH STATE SYNCHRONISED
1:0047 DSLC SYNCH CHECK I/P
1:0048 DSLC SYNCH PERM I/P
1:0049 DSLC SYNCH RUN I/P
1:0050 DSLC CB AUX I/P
1:0051 DSLC VOLTS RAISE I/P
1:0052 DSLC VOLTS LOWER I/P
Analogue Reads
Address Description
3:0001 ENGINE SPEED (rpm)
3:0002 ENGINE SPEED #1 (rpm)
3:0003 ENGINE SPEED #2 (rpm)
3:0004 SPEED REFERENCE (rpm)
3:0005 KW LOAD
3:0006 ACTUATOR POSITION (%)
3:0007 FUEL LIMIT
3:0008 PID OUTPUT
3:0009 % LOAD
3:0010 LS LINES %
3:0011 LOAD SHARE ERROR
3:0012 LOAD REFERENCE (kW)
3:0013 REMOTE REFERENCE (kW)
3:0014 KW LIMIT
3:0015 UNIT SYNCH BIAS (rpm)
3:0016 SYSTEM SYNCH BIAS (rpm)
3:0017 DROOP BIAS (rpm)
3:0018 SPEED REFERENCE BEFORE BIASES
3:0019 CHARGE AIR PRESSURE (bar)
3:0020
3:0021
3:0022
Analogue Writes
Address Description
4:0001 Remote KW Reference (kW)
Woodward 51
723 Generator Control 8280-576/-577 Manual 37807
Chapter 5.
Application Programming
The GAP software allows the applications engineer to design the control system
logic with an integrated drawing package, which runs on a PC under the
Windows environment. Once the control software has been graphically entered,
the GAP/PC system automatically generates code which is loaded into the 723
to control the engine.
Similarly, just as the same blocks are re-used, the applications engineers using
the GAP software, build on a Woodward library of GAP software functions
which may be re-used from control to control, with little code generation and
testing time, and again, without introducing errors.
All changes and additions to the GAP software are generated, tested and
documented by an integrated team of software experts, so that the
improvement of the GAP software is an ongoing process. This process
minimizes the amount of time spent re-writing specific control functions, whilst
giving the applications engineer flexibility for design changes or special
requirements.
The timing requirements of the code generated by the GAP software have also
been rigidly defined and adhered to. Variable execution time blocks have been
avoided. The non-variability in the execution times of the blocks means that a
control that runs efficiently during testing, is currently exercising the entire
control program. The user does not have to worry that under an unanticipated
set of conditions, the processor will become overburdened, and will not have
enough time to complete its assigned tasks. Only with predictable execution
times, can a multi-tasking operating system have a guaranteed update rate.
Software tasks may be programmed to run every 10 ms, 20 ms, 40 ms and 80
52 Woodward
Manual 37807 723 Generator Control 8280-576/-577
ms. The GAP software guarantees that a task programmed to run every 10
milliseconds will run exactly every 10 milliseconds, regardless of what other
functions the control system is presently exercising.
The GAP system, because of its rigidly defined nature, allows Woodward to
exercise the same engineering change and revision control system procedures
used to control the manufacture of any control system part. This ISO 9001
approved engineering change system guarantees software compatibility, as well
as documentation that makes it possible to reproduce, diagnose, and repair
control logic bugs. If any bugs do escape, they will be well documented, and the
affected systems will be readily located and fixed.
Woodward 53
723 Generator Control 8280-576/-577 Manual 37807
Chapter 6.
Power Management Network
Network Architecture
A special Serial LonTalk® * Adapter (SLTA) is needed to make a network
‘binding’ between the DSLC™ and the 723 DCS.
*—LonTalk is a trademark of Echelon Corp.
Once a DSLC has been ‘bound’ to a 723, the DSLC is no longer able
to automatically communicate via the LON, to other DSLCs. If it is
required for the DSLCs to communicate with each other, as well as a
723, the whole network will have to be taken into consideration. Each
723 and DSLC on the network will have to be entered into a database,
and identified and bound individually, therefore becoming part of the
communicating network.
Hardware
The network consists of one channel of the 723 and a DSLC.
More information regarding the DSLC (Digital Synchronizer & Load Control)
may be found in the manual number 02007.
The DSLC communicates with the 723 through shielded twisted pair wiring. The
specifications for the system require that listed level V type cable be used. For
systems where more than one 723/DSLC pair are installed, the network may be
wired directly from unit to unit, as shown in Figure 6-1, or each unit may be
connected to the network via stubs as in Figure 6-2. The network must be
terminated at both ends; each end is terminated by placing a jumper between
terminals 24 & 25 (723), and/or 41 & 42 (DSLC). There is no polarity associated
with the network wiring.
For optimum EMC performance, the network cable shield should be landed at
each unit, and the exposed wire length limited to 25 mm. At each end, the outer
insulation should be stripped and the bare shield tie-wrapped to the chassis.
54 Woodward
Manual 37807 723 Generator Control 8280-576/-577
The cable used for the network will affect the overall system performance with
respect to distance, stub length, and total number of nodes supported on a
single channel. Echelon recommends the use of UL Level IV, 0.325 mm² (22
AWG) twisted pair cable for the network bus as defined in UL’s LAN Cable
Certification Program, UL document number 200–120 20 M/11/91.
Proper LonWorks network wiring is critical to assure that the network operates
correctly. Figure 6-3 illustrates an example typical system. The system may
include other LonWorks compatible devices, such as a DSLC, Digital
Synchronizer & Load Control. The following requirements must be met:
1. Use only recommended shielded twisted pair cabling for the LonWorks
network. Correct cable is available from Woodward, Belden, or other
suppliers providing an equivalent cable.
Belden
PO Box 1980
Richmond, IN 47375
(1) 317 983 5200
P/N Description
9207 PVC 0.52 mm² (20 AWG) shielded. NC Type CL2, CSA Cert. PCC FT 1.
89027 Teflon 0.52 mm² (20 AWG) shielded, Plenum version. NEC Type CMP,
CSA Cert. FT 4.
YR28867 PVC 0.325 mm² (22 AWG) shielded.
Woodward 55
723 Generator Control 8280-576/-577 Manual 37807
5. The network must be properly terminated at each end of the cable. Internal
components are provided in the 723 DCS & DSLC, which provide proper
network termination with the installation of a jumper on the controls at each
end of the cable. Intermediate nodes should not have the termination
jumper installed.
56 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Chapter 7.
Modbus Communication
The 723 Digital Control utilizes AEG-Modicon Inc’s MODBUS protocol. The
Modbus protocol determines how the master and slaves establish and break off
contact, how the sender and receiver are identified, how messages are
exchanged in an orderly manner, and how errors are detected. The protocol
also controls the query and response cycle which takes place between the
master and slave devices.
The protocol provides for one master and up to 247 slaves on a common line.
Each slave is assigned a fixed unique device address in the range of 1 to 247.
Only the master can initiate a transaction. A transaction consists of a message
from the master to one of the slaves and a response from that slave to the
master.
The control supports two modes of transmission for Modbus. The mode defines
the individual units of information within a message, and the numbering system
used to transmit the data. Only one mode of transmission may be used per
Modbus system; mixing of modes is not possible. The two transmission modes
are ASCII (American Standard Code for Information Interchange) and RTU
(Remote Terminal Unit). The modes are defined in Table 7-1. The 723 DCS
uses either the ASCII or the RTU transmission mode.
ASCII RTU
CODING SYSTEM HEXADECIMAL 8 BIT BINARY
BITS PER CHARACTER 7 8
PARITY EVEN, ODD, NONE EVEN, ODD, NONE
STOP BITS 1 OR 2 1 OR 2
DATA TRANSMITTED
4 BITS 8 BITS
PER CHARACTER
ERROR CHECKING LRC CRC
(LONGITUDINAL (CYCLICAL
REDUNDANCY CHECK) REDUNDANCY CHECK)
In RTU mode, the data is sent in 8-bit binary characters. In ASCII mode, each
RTU character is first divided into two 4-bit parts (high order and low order) and
then represented by their hexadecimal equivalent. The ASCII characters
representing the hexadecimal characters are used to construct the message.
ASCII mode uses twice as many characters as RTU mode. Additionally, in RTU
mode, message characters must be transmitted in a continuous stream. In
ASCII mode, breaks of up to 1 second can occur between characters.
There are two communication ports available in the 723. Both ports may be
configured for RS-232, RS-422 or RS-485 communications. If the
communication utilizes an RS-232 link, the distance between devices is limited
to a maximum distance of 15 meters (50 feet). It should be noted that the J3
port can communicate using either ASCII or RTU mode, whereas the J2 port is
only able to communicate using ASCII.
Woodward 57
723 Generator Control 8280-576/-577 Manual 37807
The data is passed between the Master and the 723 in the form of message
frames (see Table 7-2). On any single multi drop link, each slave address must
be unique.
The function code portion of the message frame tells the addressed slave what
function to perform. Table 7-3 and Figure 7-1 define and list the function codes
supported by the 723.
MODBUS
ADDRESS 0XXXX 1XXXX 3XXXX 4XXXX
0000
FFFF
FUNCTION 1, 5 & 15 2 4 3, 6 & 16
CODES
Table 7-6 shows typical Modbus frames for the various function codes. If a
slave detects an error in a message, it will not act on or respond to that
message. For any requested data that is undefined, the slave will respond with
a value of zero. The slave will respond with an exception response if it detects
illegal data in a message. Tables 7-4 and 7-5 list the exception errors displayed
by the 723 control.
58 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Code Name Meaning
1 Illegal Function The message function is not an allowable action
2 Illegal Data Address The message start address is not allowable address
9 Checksum Error The received message had an incorrect error check
code
10 Garbled Message The received message could not be decoded
Function Message
Code Type
SLAVE FUNCTION START NUMBER ERROR
1,2,3,4 Query ADDRESS CODE ADDRESS OF CHECK
POINTS
Query
SLAVE FUNCTION DATA ANALOGUE OR ERROR
5,6 or ADDRESS CODE ADDRESS DIGITAL VALUE CHECK
Response
SLAVE FUNCTION START NUMBER ANALOGUE OR ERROR
15,16 Query ADDRESS CODE ADDRESS OF DIGITAL DATA CHECK
POINTS
Woodward 59
723 Generator Control 8280-576/-577 Manual 37807
The Modbus communication ports in the 723 are custom programmed for each
application, and have unique Modbus addresses. The Modbus address listing
consists of Boolean Writes, Boolean Reads, Analogue Reads, and Analogue
Writes. The Boolean reads and writes are also referred to as input and holding
coils. The analogue reads and writes are also referred to as input registers and
holding registers.
All values that can be addressed by Modbus are considered to be discrete and
numeric. The discretes are a 1 bit binary, on or off value and the numerics are
16 bit values. Registers are interpreted by the 723 as signed 16 bit integers.
The maximum number of analogues in a single message is 59 for ASCII mode
and 118 for RTU mode. The maximum number of digitals in a single message is
944 for ASCII mode and 1888 for RTU mode.
60 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Chapter 8.
Set Point Programming
Introduction
This chapter contains information on how to enter control set points, using
either a Hand Held Programmer or a PC Interface, (whichever is provided for
the application).
The programmer screen is a four-line, back lighted LCD display. The display
permits you to look at two separate functions or menu items at the same time.
Use the “Up/Down Arrow” key to toggle between the two displayed items. The
BKSP and SPACE keys will scroll through the display to show the remainder of
a prompt if it is longer than the display screen's 19 characters.
The 723 has two sets of menus; the Service menus and the Configure menus.
The Service menus allow easy access and tuning while the engine is running.
The Configure menus may only be entered if the I/O is shutdown, and hence
the engine stopped.
Service Menus
To access the Service menus press the key. To move between menus, and
to move through set points within menus follow the instructions as for the
Configure menus. Also to return to the menu header, or to leave Service, follow
the Configure instructions.
62 Woodward
Manual 37807 723 Generator Control 8280-576/-577
To obtain an exact value, press the = key. Key in the required figure and press
ENTER.
This may only be done if the figure is within 10% of the existing
value, or for any adjustments made in Configure.
To save set points at any time, use the SAVE key. This will transfer all new set
point values into the EEPROM memory. The EEPROM retains all set points
when power is removed from the control.
PC Interface
A PC Interface may be provided for tuning parameters, instead of the Hand
Held Programmer. This will consist of the ServLink Server, which acts as the
interface between the PC and the 723. The hardware communication link is
configurable for RS-232 or RS-422 (RS-422 only if using the 723 J1 port), and
the communications protocol is the Woodward developed ServLink.
The Woodward Watch Window can be used to interface with the ServLink
Server, as a Means for displaying the Service & Configure tuneable/monitors,
with the ability for tuning the parameters. Watch Window also offers the ability
to upload the tuneable parameters from the control, into a file, and also to
download the parameters stored in the file, into a control (of the same
type/application).
With each application manual. a list of each of the tuneable parameters will be
provided along with a description of each. Also, a listing of each of the tuneable
with the default values and the range of adjustment will be included.
Watch Window
Watch Window is a tool for viewing and adjusting the parameters of the 723
Control. An application can be quickly and easily developed by the user, by
assembling a number of tabbed sheets, onto which are ‘dropped’, the
parameters that are required for monitoring/adjusting. Watch Window is made
up of three types of window; Main Window, ServLink Explorer and ServLink
Inspector.
Woodward 63
723 Generator Control 8280-576/-577 Manual 37807
Following is an example of Watch Window:
Main Window
The Main Window is the application controlling window, and provides the
standard menus for opening/closing/saving files, Cut/Copy/Paste of parameters,
and also for Adding /removing/renaming tabbed sheets to the application.
64 Woodward
Manual 37807 723 Generator Control 8280-576/-577
ServLink Explorer
The Explorer is used to browse the set of variables available through the
ServLink Server.
Each sheet contains a tree view. The tree view displays the names of the
categories and blocks in a control’s application program in a hierarchical
structure. The names at each level in the tree are listed in alphabetical order.
Watch Window, which is normally supplied, will display the Configure and
Service menus only.
Selected variables can be used in Copy & Paste or Drag & Drop operations in
order to add a variable to an Inspector. Variables can be selected using the
mouse (left click) or keyboard (arrow keys). Selecting categories or blocks
selects all of the fields underneath them.
Woodward 65
723 Generator Control 8280-576/-577 Manual 37807
ServLink Inspector
The Inspector is used to monitor and edit variables available through the
ServlLnk Server. The Inspector is composed of a set of tabbed sheets. Each
sheet contains a grid (the grid shown in the following example is reduced - other
fields headers are available to define which control a variable relates to, and if
relevant, which category and block name. Each sheet’s tab is labelled with a
user-definable name. The user has the ability to add and remove sheets using
menu items and/or tool bar buttons in the Main Window.
An icon to the left of the variable defines whether it is a monitor value, configure
tuneable or service tuneable (or debug tuneable if relevant):
Service Tuneable
Monitor Value
Configure Tuneable
One or more variables can be selected using the mouse (left click) or keyboard
(arrow keys).If the user wishes to select multiple variables, they can do so by
performing one of these sequences:
Select a variable, hold down the shift key, and arrow up or down until all of
the variables are selected.
Click on a variable, hold down the shift key, and click on the last variable in
the series that the user wishes to select.
Selected variables can be used in Cut, Copy & Paste or Drag & Drop operations
in order to add a variable to an Inspector. If the selected variable is tuneable or
configurable the status bar will display the minimum and maximum value for
that variable. If multiple variables are selected, the minimum and maximum will
not be displayed for any of the selected variables.
The Inspector can have its configuration saved and restored. The Inspector can
be closed by using the Main Window or by clicking the standard windows close
button.
66 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Chapter 9.
Product Support and Service Options
OEM or Packager Support: Many Woodward controls and control devices are
installed into the equipment system and programmed by an Original Equipment
Manufacturer (OEM) or Equipment Packager at their factory. In some cases, the
programming is password-protected by the OEM or packager, and they are the
best source for product service and support. Warranty service for Woodward
products shipped with an equipment system should also be handled through the
OEM or Packager. Please review your equipment system documentation for
details.
Woodward 67
723 Generator Control 8280-576/-577 Manual 37807
Replacement/Exchange: Replacement/Exchange is a premium program
designed for the user who is in need of immediate service. It allows you to
request and receive a like-new replacement unit in minimum time (usually within
24 hours of the request), providing a suitable unit is available at the time of the
request, thereby minimizing costly downtime.
This option allows you to call your Full-Service Distributor in the event of an
unexpected outage, or in advance of a scheduled outage, to request a
replacement control unit. If the unit is available at the time of the call, it can
usually be shipped out within 24 hours. You replace your field control unit with
the like-new replacement and return the field unit to the Full-Service Distributor.
Flat Rate Repair: Flat Rate Repair is available for many of the standard
mechanical products and some of the electronic products in the field. This
program offers you repair service for your products with the advantage of
knowing in advance what the cost will be.
Flat Rate Remanufacture: Flat Rate Remanufacture is very similar to the Flat
Rate Repair option, with the exception that the unit will be returned to you in
“like-new” condition. This option is applicable to mechanical products only.
When shipping the item(s), attach a tag with the following information:
return number;
name and location where the control is installed;
name and phone number of contact person;
complete Woodward part number(s) and serial number(s);
description of the problem;
instructions describing the desired type of repair.
Packing a Control
Use the following materials when returning a complete control:
protective caps on any connectors;
antistatic protective bags on all electronic modules;
packing materials that will not damage the surface of the unit;
at least 100 mm (4 inches) of tightly packed, industry-approved packing
material;
a packing carton with double walls;
a strong tape around the outside of the carton for increased strength.
Replacement Parts
When ordering replacement parts for controls, include the following information:
the part number(s) (XXXX-XXXX) that is on the enclosure nameplate;
the unit serial number, which is also on the nameplate.
68 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Engineering Services
Woodward’s Full-Service Distributors offer various Engineering Services for our
products. For these services, you can contact the Distributor by telephone or by
email.
Technical Support
Product Training
Field Service
You can also contact the Woodward Customer Service Department at one of
the following Woodward facilities to obtain the address and phone number of
the nearest facility at which you can obtain information and service.
For the most current product support and contact information, please visit our
website directory at www.woodward.com/directory.
Woodward 69
723 Generator Control 8280-576/-577 Manual 37807
Technical Assistance
If you need to contact technical assistance, you will need to provide the following
information. Please write it down here before contacting the Engine OEM, the Packager, a
Woodward Business Partner, or the Woodward factory:
General
Your Name
Site Location
Phone Number
Fax Number
Number of Cylinders
Type of Fuel (gas, gaseous, diesel,
dual-fuel, etc.)
Power Output Rating
Application (power generation, marine,
etc.)
Control/Governor Information
Control/Governor #1
Serial Number
Control/Governor #2
Serial Number
Control/Governor #3
Serial Number
Symptoms
Description
If you have an electronic or programmable control, please have the adjustment setting positions or
the menu settings written down and with you at the time of the call.
70 Woodward
Manual 37807 723 Generator Control 8280-576/-577
Woodward 71
We appreciate your comments about the content of our publications.
Send comments to: [email protected]
2012/9/Ballabgarh