0% found this document useful (0 votes)
126 views8 pages

Cable Specification

This document contains specifications for several types of cables to be used for different purposes in a project for a client called Hari Om Papers Limited. It includes specifications for 1-pair and 12-pair cables for analog and digital signals, a 3-core cable for power distribution, and a 36-core cable for marshalling digital inputs. The cables have copper conductors, PVC insulation and sheathing, with varying numbers of pairs or cores and appropriate shielding, armouring, and specifications according to their intended use.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
126 views8 pages

Cable Specification

This document contains specifications for several types of cables to be used for different purposes in a project for a client called Hari Om Papers Limited. It includes specifications for 1-pair and 12-pair cables for analog and digital signals, a 3-core cable for power distribution, and a 36-core cable for marshalling digital inputs. The cables have copper conductors, PVC insulation and sheathing, with varying numbers of pairs or cores and appropriate shielding, armouring, and specifications according to their intended use.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

CLIENT: HARI OM PAPERS LIMITED

PROJECT: PM2 AUTOMATION

PVC INSULATED, PVC SHEATHED, COPPER CONDUCTOR, ARMOURED & OVERALL


SHIELDED, ATC BRAIDED, CABLE SUITABLE FOR 1.1 KV GRADE AS PER IS 1554 PART-I 1988

1. CABLE SPECIFICATION (FOR ANALOG SIGNALS)


Type : 1 Pair x 1.0 Sq. mm
Material : High Conductivity Electrolyte Grade Annealed Tinned

Copper Conductors As Per IS- 8130, 1984

Size : 1.0 Sq. mm


No. of Strands/Dia : 32/0.20 mm
INSULATION
Material : Extruded PVC Type ‘C’ 85 Deg C As Per IS: 5831 1984
Thickness (Nom) : 0.6 mm
No. of Pair : 1 Pair
Color Code : Orange & White
TWISTING : 10-12 TWIST/MTR
IDENTIFICATION : Printing in numerals at an interval of 250 mm on each Pair

PAIR SHIELDING - ALUMINIUM BACK MYLAR TAPE SHIELDING (OVERALL)


Material : Aluminum Backed Mylar Tape Along With Drain
Wire Which Is in continuous Contact With
Aluminum Side of Aluminum Backed Mylar Tape
Thickness : 50 microns
Overlapping : 25%
Coverage : 100%
Drain Wire : ATC, 0.5 Sq.mm, 7 Strand of 0.3 mm diameter.

OVERALL ATC BRAIDING


Material : ATC
Coverage : 90%

INNER SHEATH
Material : Extruded FR PVC Type ST-2 90 Deg C As Per IS: 5831 1984
Thickness : 0.3 mm

ARMOURING
Material : G.I. Wire As Per IS: 3975
Size : Round 0.9 mm
OUTER SHEATH
Material : Extruded FR PVC Type ST-2 90 Deg C As Per IS: 5831 1984
Thickness : 1.24 mm
Color : Blue

Quantity : 1800 Meter


PVC INSULATED, PVC SHEATHED, COPPER CONDUCTOR, ARMOURED & OVERALL
SHIELDED, CABLE SUITABLE FOR 1.1 KV GRADE AS PER IS 1554 PART-I 1988

1A. CABLE SPECIFICATION (FOR ANALOG SIGNALS) (ALTERNATE SPECIFICATION)


Size : 1 Pair x 1.0 Sq. mm
Material : High Conductivity Electrolyte Grade Annealed Tinned

Copper Conductors As Per IS- 8130, 1984

Size : 1.0 Sq. mm


No. of Strands/Dia : 32/0.20 mm
INSULATION
Material : Extruded PVC Type ‘C’ 85 Deg C As Per IS: 5831 1984
Thickness (Nom) : 0.6 mm
No. of Pair : 1 Pair
Color Code : Blue & White
TWISTING : 10-12 TWIST/MTR
IDENTIFICATION : Printing in numerals at an interval of 250 mm on each Pair

PAIR SHIELDING - ALUMINIUM BACK MYLAR TAPE SHIELDING (OVERALL)

Material : Aluminum Backed Mylar Tape Along With Drain


Wire Which Is in continuous Contact With
Aluminum Side of Aluminum Backed Mylar Tape
Thickness : 50 microns
Overlapping : 25%
Coverage : 100%
Drain Wire : ATC, 0.5 Sq.mm, 7 Strand of 0.3 mm diameter.

ARMOURING
Material : G.I. Wire As Per IS: 3975
Size : Round 0.9 mm

OUTER SHEATH
Material : Extruded FR PVC Type ST-2 90 Deg C As Per IS: 5831 1984
Thickness : 1.24 mm
Color : Blue

Quantity : 1800 Meter


PVC INSULATED, PVC SHEATHED, COPPER CONDUCTOR, ARMOURED, CABLE SUITABLE
FOR 1.1 KV GRADE AS PER IS 1554 PART-I 1988

2. CABLE SPECIFICATION (FOR DIGITAL SIGNALS)


Type : 1 Pair x 1.0 Sq. mm
Material : High Conductivity Electrolyte Grade Annealed Tinned

Copper Conductors As Per IS- 8130, 1984

Size : 1.0 Sq. mm


No. of Strands/Dia : 32/0.20 mm
INSULATION
Material : Extruded PVC Type ‘C’ 85 Deg C As Per IS: 5831 1984
Thickness (Nom) : 0.6 mm
No. of Pair : 1 Pair
Color Code : Blue & White
TWISTING : 10-12 TWIST/MTR
IDENTIFICATION : Printing in numerals at an interval of 250 mm on each Pair

INNER SHEATH
Material : Extruded FR PVC Type ST-2 90 Deg C As Per IS: 5831 1984
Thickness : 0.3 mm

ARMOURING
Material : G.I. Wire As Per IS: 3975
Size : Round 0.9 mm

OUTER SHEATH
Material : Extruded FR PVC Type ST-2 90 Deg C As Per IS: 5831 1984
Thickness : 1.24 mm
Color : Blue

Quantity : 100 Meter


PVC INSULATED, PVC SHEATHED, COPPER CONDUCTOR, ARMOURED & OVERALL SHIELDED, ATC
BRAIDED, CABLE SUITABLE FOR 1.1 KV GRADE AS PER IS 1554 PART-I 1988

3. CABLE SPECIFICATION (FOR AJB)


Type : 12 Pair x 1.0 Sq. mm
Material : High Conductivity Electrolyte Grade Annealed Tinned

Copper Conductors As Per IS- 8130, 1984

Size : 1.0 Sq. mm


No. of Strands/Dia : 32/0.20 mm
INSULATION
Material : Extruded PVC Type ‘C’ 85 Deg C As Per IS: 5831 1984
Thickness (Nom) : 0.6 mm
No. of Pair : 12 Pair
Color Code : Orange & White
TWISTING : 10-12 TWIST/MTR
IDENTIFICATION : Printing in numerals at an interval of 250 mm on each Pair

PAIR SHIELDING - ALUMINIUM BACK MYLAR TAPE SHIELDING (OVERALL)

Material : Aluminum Backed Mylar Tape Along With Drain


Wire Which Is in continuous Contact With
Aluminum Side of Aluminum Backed Mylar Tape
Thickness : 50 microns
Overlapping : 25%
Coverage : 100%
Drain Wire : ATC, 0.5 Sq.mm, 7 Strand of 0.3 mm diameter.

OVERALL ATC BRAIDING


Material : ATC
Coverage : 90%

INNER SHEATH
Material : Extruded FR PVC Type ST-2 90 Deg C As Per IS: 5831 1984
Thickness : 0.3 mm

ARMOURING
Material : G.I. Strip As Per IS: 3975
Size : Strip 4 x 0.8 mm
OUTER SHEATH
Material : Extruded FR PVC Type ST-2 90 Deg C As Per IS: 5831 1984
Thickness : 1.24 mm
Color : Blue

Quantity : 350 Meter


PVC INSULATED, PVC SHEATHED, COPPER CONDUCTOR, ARMOURED & OVERALL SHIELDED, ATC
BRAIDED, CABLE SUITABLE FOR 1.1 KV GRADE AS PER IS 1554 PART-I 1988

3A. CABLE SPECIFICATION (FOR AJB) (ALTERNATE SPECIFICATION)


Type : 12 Pair x 1.0 Sq. mm
Material : High Conductivity Electrolyte Grade Annealed Tinned

Copper Conductors As Per IS- 8130, 1984

Size : 1.0 Sq. mm


No. of Strands/Dia : 32/0.20 mm
INSULATION
Material : Extruded PVC Type ‘C’ 85 Deg C As Per IS: 5831 1984
Thickness (Nom) : 0.6 mm
No. of Pair : 12 Pair
Color Code : Orange & White
TWISTING : 10-12 TWIST/MTR
IDENTIFICATION : Printing in numerals at an interval of 250 mm on each Pair

PAIR SHIELDING - ALUMINIUM BACK MYLAR TAPE SHIELDING (OVERALL)

Material : Aluminum Backed Mylar Tape Along With Drain


Wire Which Is in continuous Contact With
Aluminum Side of Aluminum Backed Mylar Tape
Thickness : 50 microns
Overlapping : 25%
Coverage : 100%
Drain Wire : ATC, 0.5 Sq.mm, 7 Strand of 0.3 mm diameter.

ARMOURING
Material : G.I. Strip As Per IS: 3975
Size : Strip 4 x 0.8 mm
OUTER SHEATH
Material : Extruded FR PVC Type ST-2 90 Deg C As Per IS: 5831 1984
Thickness : 1.24 mm
Color : Blue

Quantity : 350 Meter


PVC INSULATED, PVC SHEATHED, COPPER CONDUCTOR, ARMOURED, CABLE SUITABLE FOR 1.1 KV
GRADE AS PER IS – 1554 PART – 1 1988.

4. CABLE SPECIFICATION (FOR POWER DISTRIBUTION)


Size : 3 Core x 1.5 Sq. mm
CONDUCTOR
Material : High Conductivity Electrolytic Grade Annealed Bare
Copper Conductor As Per IS 8130
No. of Strands/Dia : 30/0.25 mm
INSULATION
Material : Extruded PVC Type ‘A’ 70 Deg C As Per IS: 5831 1984

Thickness : 0.6 mm
No. of Core : 3 Core
Color Code : As Per IS Color Code

INNER SHEATH
MATERIAL : Extruded PVC Type ST-1 70 Deg C As Per IS: 5831 1984
Thickness : 0.3 mm

ARMOURING
Material : G. I. Wire/Strip As Per IS: 3975
Size : Round 1.4 mm/Strip 4 x 0.8 mm

OUTER SHEATH
MATERIAL : Extruded PVC Type ST-1 70 Deg C As Per IS: 5831 1984
Thickness : 1.24 mm
Color : Black

Quantity : 100 Meter


PVC INSULATED, PVC SHEATHED, COPPER CONDUCTOR, ARMOURED, CABLE SUITABLE FOR 1.1 KV
GRADE AS PER IS – 1554 PART – 1 1988.

5. CABLE SPECIFICATION (FOR MCC MARSHALLING TO DIGITAL INPUT)


Size : 36 Core x 1.0 Sq. mm
CONDUCTOR
Material : High Conductivity Electrolytic Grade Annealed Bare
Copper Conductor As Per IS 8130
No. of Strands/Dia : 32/0.20 mm
INSULATION
Material : Extruded PVC Type ‘A’ 70 Deg C As Per IS: 5831 1984

Thickness : 0.9 mm
No. of Core : 36 Core
Color Code : As Per IS Color Code

INNER SHEATH
MATERIAL : Extruded PVC Type ST-1 70 Deg C As Per IS: 5831 1984
Thickness : 0.3 mm

ARMOURING
Material : G.I. Strip As Per IS: 3975
Size : Strip 4 x 0.8 mm

OUTER SHEATH
MATERIAL : Extruded PVC Type ST-1 70 Deg C As Per IS: 5831 1984
Thickness : 1.24 mm
Color : Black

Quantity : 100 Meters (As per distance from MCC to PAC Panel)
PVC INSULATED, PVC SHEATHED, COPPER CONDUCTOR, ARMOURED, CABLE SUITABLE FOR 1.1 KV
GRADE AS PER IS – 1554 PART – 1 1988.

6. CABLE SPECIFICATION (FOR MCC MARSHALLING TO DIGITAL OUTPUT)


Size : 18 Core x 1.0 Sq. mm
CONDUCTOR
Material : High Conductivity Electrolytic Grade Annealed Bare
Copper Conductor As Per IS 8130
No. of Strands/Dia : 32/0.20 mm
INSULATION
Material : Extruded PVC Type ‘A’ 70 Deg C As Per IS: 5831 1984

Thickness : 0.9 mm
No. of Core : 18 Core
Color Code : As Per IS Color Code

INNER SHEATH
MATERIAL : Extruded PVC Type ST-1 70 Deg C As Per IS: 5831 1984
Thickness : 0.3 mm

ARMOURING
Material : G.I. Strip As Per IS: 3975
Size : Strip 4 x 0.8 mm

OUTER SHEATH
MATERIAL : Extruded PVC Type ST-1 70 Deg C As Per IS: 5831 1984
Thickness : 1.24 mm
Color : Black

Quantity : 100 Meters (As per distance from MCC to PAC Panel)