Data sheet-ROOF AM HT
Data sheet-ROOF AM HT
Data sheet-ROOF AM HT
ROOF-AM 634 T
APPLICATIONS
ROOF-AM line is designed to extract large volumes of air in roof installations, without long ducts. For instance:
ventilation of industrial buildings (factories, warehouses etc.), stock farms and electrical equipments etc.
RANGE
This line consists of 7 sizes with impeller from 500 up to 1000 mm.
ADVANTAGES
This line is characterized by the wide round shaped nozzles in both inlet and outlet, warranty of reduced noise
level and high efficiency. Besides these fans allow the effective operation either in exhaust or supply duty.
Electric motor is easily accessible for wiring and maintenance operations, manufactured according to
international standards assuring reliability and the long-term economic recovery of the unit simply repairing or
replacing the motor itself.
CONSTRUCTION
⦁ Ring casing with double wide round shaped nozzle, and base resistant to the atmospheric agents.
⦁ Upper cover in techno-polymer resistant to the atmospheric agents.Protection grid on outlet side in
steel rod, manufactured according to UNI EN ISO 12499.
⦁ Inside protection grid (in lack of shutter or ducts). Impeller with high efficiency airfoil blades. Hub in
diecast aluminum alloy. Balancing according to UNI ISO 1940.
⦁ Variable pitch angle in still position.
⦁ Asynchronous electric motor, protection IP 55, Class F insulated, service S1, construction according to
IEC/EEC (UNEL-MEC) standard.
⦁ Arrangement 4 (impeller directly coupled to motor shaft).
TECHNICAL SPECIFICATIONS
ON REQUEST
ROOF-AM 634 T
FAN PERFORMANCE
300 Requested Point
250 Q 12.000 m³/h
Static Pressure (Pa)
200
Ps 60 Pa
Selected Point
150
Q 11.944 m³/h
100
Ps 59 Pa
50 Pd 69 Pa
0 Pt 129 Pa
1,6
Fan Speed 1425 rpm
1,4
Conditions 15 °C @ 0 m
1,2
1,22 kg/m³
Input Power (kW)
50
Total Efficiency (%)
40
30
20
10
0
0 2000 4000 6000 8000 10000 12000 14000 16000
Q - Vo lume Flo w (m³/h)
PERFORMANCE MODELS ARE PREPARED WITH GREAT CARE AND THE DATA ARE CHECKED FOR CORRECTNESS. HOWEVER, NO LIABILITY CAN BE ASSUMED FOR ANY INCORRECT OR INCOMPLETE
DATA.
Lw dB Lw dB(A) Lp dB(A)
Sound Po wer dB Sound Po wer dB(A) Sound Pres s ure dB(A)
110
@ 6m
100 63 Hz 79 52 26
90 125 Hz 88 71 45
80 250 Hz 90 81 54
70 500 Hz 91 87 61
60
inlet
1000 Hz 92 92 65
50
2000 Hz 89 90 63
40
30 4000 Hz 83 84 57
20 8000 Hz 74 72 46
10 Overall 97 95 69
0
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
AIR PERFORMANCE AND SOUND POWER LEVELS ARE WITHIN THE TOLERANCES ALLOWED BY THE DIN 24166 STANDARD FOR CLASS 2. HOWEVER, NO LIABILITY CAN BE ASSUMED FOR ANY
INCORRECT OR INCOMPLETE DATA.
TECHNICAL INFORMATION
Product Code CTBD Impeller Type Group-AxialRoof
Impeller Name ELEKTROVENT 13884 Air Volume 12.000 (11.944) m³/h
Static Pressure 60 (59) Pa Total Pressure 129 Pa
Outlet Velocity 10,64 m/s Fan Total Efficiency 30,5 %
Fan Static Efficiency 14,1 % Fan Input Power 1,40 kW
SFP 0,42 W/l/s Service Factor Override 0
Air Density 15 °C @ 0 m 1,22 kg/m³ Temperature Range -20°C / +50°C
ROOF-AM 634 T
MOTOR INFORMATION
Electrical Supply 400/3/50
Motor Rating 1.1 kW
Energy Class -
Full Load Current 2.7 A
Frame Size 90
Motor Poles 4
Motor Speed 1420 rpm
PERFORMANCE MODELS ARE PREPARED WITH GREAT CARE AND THE DATA ARE CHECKED FOR CORRECTNESS. HOWEVER, NO LIABILITY CAN BE ASSUMED FOR ANY INCORRECT OR INCOMPLETE