E 071882 R0 Comments

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

Clarify the scope of re approval.

No load
schedules submitted.
All schedules to be submitted in PDF
format not Excel.
Submit the drawing in a proper format
can not be processed.
AREA: DUBAI U.A.E : AL SATWA

PROJECT: REESIDENTIAL & COMMERCIAL BUILDING DUBAI -AL SATWA DETAILS OF CONNECTED LOAD & MAXIMUM DEMAND & Kwh METERING PLOT NO: 3342846

ECC CONNECTED LOAD (KW) PROPOSED TYPE & No. OF kWh METERS
PROTECTION RATING PHASE CABLE CONDUCTOR
REMARKS
NO.CORES & 1 - PH 3- PH
PANEL REFERENCE 4P/TP MCCB ACB SIZE R.PH Y.PH B.PH TOTAL LV / HV CT (3)
COMPOSITION SIZE (1) (2)

AMPS AMPS mm2 mm2 KW KW KW KW

2500 1 NO.2500/5A CT
INCOMER TR-01/MDB-01 TP BY DEWA 2X1C:300 426.33 437.19 437.94 1301.46 1
[email protected] INTEGRAL METER

2500 1 NO.2500/5A CT
INCOMER TR-02/MDB-02 TP BY DEWA 2X1C:300 443.25 435.56 443.73 1322.54 1
[email protected] INTEGRAL METER

MDB CONNECTED TO DEWA INCOMER TOTAL CONNECTED LOAD(DUTY& STANDBY LOAD) 869.58 872.75 881.67 2624.00

TOTAL DEMAND LOAD 739.14 741.84 749.42 2230.40 0 2


DEMAND FACTOR= 0.85
EXPECTED MAX DEMAND LOAD: 2230.40 KW

OWNER:
LEAD DESIGN CONSULTANT:
PLOT NO: 3342846 REESIDENTIAL & COMMERCIAL BUILDING DUBAI -AL
MEP CONSULTANT:
SATWA
DUBAI MUNICIPALITY STAMP

NORTH DIR

NOTES:

MAIN CONSULTANT :

B+G+3+ROOF COMMERCIAL AND


PROJECT RESIDENTIAL BUILDING
(MERAAS PLOT AT AL SATWA)

· M M ABDULLA AHMAD MOHAMMAD


OWNER
BIN FAHAD ALMHEIRI
· MDB-1
FORM 4b, TYPE 6, TTA,
ELS

FAULT LEVEL 50kA FOR 1Sec


FUSES MASTER
· RYB1 RYB2 RYB3 RYB5 RYB6 RYB7 RYB8
DEVELOPER MERAAS ESTATES (L.L.C)
BUSBARS: RYB4
RATED NOMINAL A A A V OC ACH
CURRENT: 2500Amps 230/400V,
400 kVAR CAPACITOR
· 50Hz 3-PHASE R Y B VSS
BMS
SC
EF
HST
PF
BANK PANEL-1 BLOCK PLOT LOCATION
· PMU
SURGE PROTECTION
ACTUAL CONNECTED LOAD = 1301.46 kW
DEMAND FACTOR= 0.85 MODULE. 3342846 AL SATWA (334)
MAXIMUM DEMAND LOAD= 1106.24 kW

· EARTHING BAR

MDB-1
2x1C 150 sq.mm Cu.
CABLE Y/G AS ECC DRAWING TITLE
MIN. 6M APART

EARTH EARTH

· PIT PIT

TRF. NO.1
PROVISION FOR MOBILE
GENERATOR
1500 KVA

ELECTRICAL SCHEMATIC-1
· BY DEWA

· ARCHITECT ENG WISSAM DRAWING NO.

·
REGISTRATION NO.
STRUCTURAL
7095

ENG FADI
EP - 10-008
· ENGINEER
ELECTRICAL
REGISTRATION NO. 46609

SCALE DATE DRAWN JOB NO.


N.T.S SEPTEMBER-2021 AMIR 19-DXB-221
DUBAI MUNICIPALITY STAMP

NORTH DIR

NOTES:

ELS ELS ELS ELS ELS ELS ELS

MAIN CONSULTANT :

250 KVA
PRIME RATED
GEN. SET

G B+G+3+ROOF COMMERCIAL AND


PROJECT RESIDENTIAL BUILDING
(MERAAS PLOT AT AL SATWA)

· ABDULLA AHMAD MOHAMMAD


OWNER
BIN FAHAD ALMHEIRI
·
MASTER
· MDB-2 DEVELOPER MERAAS ESTATES (L.L.C)
FORM 4b, TYPE 6, TTA,
FAULT LEVEL 50kA FOR 1Sec
FUSES

· BUSBARS: RYB1 RYB2 RYB3 RYB4 RYB5 RYB6 RYB7 RYB8 RYB9 BLOCK PLOT LOCATION
· RATED NOMINAL A A A V OC ACH
CURRENT: 2500Amps 230/400V,
50Hz 3-PHASE R Y B VSS SC HST 400 kVAR CAPACITOR 3342846 AL SATWA (334)
BMS EF PF
BANK PANEL-1
· ACTUAL CONNECTED LOAD = 1322.54 kW
PMU
SURGE PROTECTION
DEMAND FACTOR= 0.85
MAXIMUM DEMAND LOAD= 1124.16 kW
MODULE.
DRAWING TITLE
EARTHING BAR

· MDB-2
2x1C 150 sq.mm Cu.
CABLE Y/G AS ECC
MIN. 6M APART

EARTH
PIT
EARTH
PIT
ELECTRICAL SCHEMATIC-2
· PROVISION FOR MOBILE
TRF. NO.2
1500 KVA
GENERATOR

BY DEWA

· ARCHITECT ENG WISSAM DRAWING NO.

·
REGISTRATION NO.
STRUCTURAL
7095

ENG FADI
EP - 10-009
· ENGINEER
ELECTRICAL
REGISTRATION NO. 46609

SCALE DATE DRAWN JOB NO.


N.T.S SEPTEMBER-2021 AMIR 19-DXB-221
DUBAI MUNICIPALITY STAMP

CORRIDOR
FIRST FLR. LVL.
CORRIDOR +4.65m F.F.L
NORTH DIR

MDB-2
ELECTRICAL
ROOM 400A
TP
300A
TP
MCCB MCCB
CABLE CHAMBER
MAIN BREAKER
CABLE CHAMBER
MOBILE GENERATOR
CABLE CHAMBER
CAPACITOR BANK CAPACITOR BANK
40A 300A

NOTES:

BUSBAR CHAMBER
TP
CB-2
TP
MCCB MCCB

2500A TP
ACB
2500A TP
ACB 1000A TP
400A
TP
MCCB
400A
TP
MCCB (GATE LEVEL)
±0.00 GR.F.F.L
ACB 300A
400A
TP
TP
MCCB
SPARE MCCB

ELECTRICAL RM ELECTRICAL RM LV ROOM


GROUND FLOOR ELECTRICAL ROOM DETAIL
SECTION: B-B RAMP
SECTION: C-C
SECTION: A-A SECTION: A-A

CORRIDOR
FIRST FLR. LVL. FIRST FLR. LVL. FIRST FLR. LVL.
CORRIDOR +4.65m F.F.L +4.65m F.F.L +4.65m F.F.L
CB-2
CB-1

MDB-2

SMDB ESMDB-S
400A 300A
TP TP RETAIL-2

MDB-2

MDB-1
MCCB MCCB
CABLE CHAMBER
MAIN BREAKER
CABLE CHAMBER CABLE CHAMBER
MOBILE GENERATOR CAPACITOR BANK CAPACITOR BANK
40A 300A
BUSBAR CHAMBER

TP
CB-2
TP
MCCB MCCB

LV ROOM 2500A TP 2500A TP


400A
TP
MCCB
400A
TP
MCCB (GATE LEVEL) ATS (GATE LEVEL) (GATE LEVEL)
MDB-2
MDB-1

1000A TP

LV ROOM
ACB ACB

±0.00 GR.F.F.L ±0.00 GR.F.F.L ±0.00 GR.F.F.L


ACB 300A
400A
TP
TP
MCCB
SPARE MCCB

LV ROOM LV ROOM
SECTION: C-C
RAMP
SECTION: A-A SECTION: B-B
ATS MAIN CONSULTANT :

GROUND LV ROOM DETAIL

FIRST FLR. LVL.


+4.65m F.F.L

B+G+3+ROOF COMMERCIAL AND


ELECTRICAL PROJECT RESIDENTIAL BUILDING
ROOM (MERAAS PLOT AT AL SATWA)

ABDULLA AHMAD MOHAMMAD


OWNER
(GATE LEVEL) BIN FAHAD ALMHEIRI
±0.00 GR.F.F.L
ELECTRICAL RM ELECTRICAL RM LV ROOM MASTER
DEVELOPER MERAAS ESTATES (L.L.C)
BASEMENT FLOOR ELECTRICAL ROOM DETAIL
SECTION: D-D BLOCK PLOT LOCATION
SECTION: A-A SECTION: B-B
3342846 AL SATWA (334)

DRAWING TITLE

ELECTRICAL ROOM DETAILS-1

ARCHITECT ENG WISSAM DRAWING NO.

REGISTRATION NO.
STRUCTURAL
7095
EP-10-010
ENG FADI
ENGINEER
ELECTRICAL
REGISTRATION NO. 46609

SCALE DATE DRAWN JOB NO.


N.T.S
1:100 SEPTEMBER-2021 AMIR 19-DXB-221
DUBAI MUNICIPALITY STAMP

ROOF DECK ROOF DECK


ROOF DECK

ELECTRICAL NORTH DIR


ROOM

ELECT
ROOM
ELECTRICAL RM ELECTRICAL RM
NOTES:
ROOF FLOOR ELECTRICAL ROOM DETAIL SECTION: B-B
SECTION: A-A SECTION: C-C

ELECTRICAL
ROOM
ELECT
ROOM
ELECTRICAL RM ELECTRICAL RM

SECTION: B-B
THIRD FLOOR ELECTRICAL ROOM DETAIL SECTION: A-A SECTION: C-C

MAIN CONSULTANT :

ELECTRICAL
ROOM
ELECT
ROOM
ELECTRICAL RM ELECTRICAL RM
B+G+3+ROOF COMMERCIAL AND
PROJECT RESIDENTIAL BUILDING
SECOND FLOOR ELECTRICAL ROOM DETAIL SECTION: B-B
SECTION: A-A SECTION: C-C (MERAAS PLOT AT AL SATWA)

ABDULLA AHMAD MOHAMMAD


OWNER
BIN FAHAD ALMHEIRI

MASTER
DEVELOPER MERAAS ESTATES (L.L.C)

BLOCK PLOT LOCATION


3342846 AL SATWA (334)

DRAWING TITLE

ELECTRICAL ELECTRICAL ROOM DETAILS-2


ROOM
ELECT
ROOM ARCHITECT ENG WISSAM DRAWING NO.

ELECTRICAL RM ELECTRICAL RM REGISTRATION NO.


STRUCTURAL
7095
EP-10-011
ENG FADI
ENGINEER
ELECTRICAL
REGISTRATION NO. 46609

FIRST FLOOR ELECTRICAL ROOM DETAIL SECTION: B-B


SECTION: A-A SECTION: C-C SCALE DATE DRAWN JOB NO.
N.T.S
1:100 SEPTEMBER-2021 AMIR 19-DXB-221

You might also like