Control Net Modules
Control Net Modules
1734-ACNR, 1756-CN2, 1756-CN2R, 1756-CNB, 1756-CNBR, 1769-L32C, 1769-L35CR, 1784-PCC, 1784-PCIC, 1784-PCICS, 1784-PKTCS, 1788-CNC, 1788-CNCR, 1788-CNF, 1788-CNFR, 1794-ACN15, 1794-ACNR15, 1797-ACNR15
User Manual
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc., with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product. Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
ATTENTION
SHOCK HAZARD
Labels may be located on or inside the equipment, for example a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be located on or inside the equipment, for example a drive or motor, to alert people that surfaces may be dangerous temperatures.
Summary of Changes
Introduction
This release of this document contains updated information. Changes are designated by change bars in margin, as shown to the right.
The table below lists the new information included in this release of the ControlNet Modules in Logix5000 Control Systems user manual.
Information About Location New or Revised New
Summary of Changes
Notes:
Preface
This manual describes how you can use ControlNet with your Logix5000 controller. With this manual, you can learn how to communicate between your controller and various devices on the ControlNet network.
You should use this manual if you program applications that use ControlNet with one of the following Logix5000 controllers: CompactLogix controller ControlLogix controller FlexLogix controller PowerFlex 700S with DriveLogix controller SoftLogix5800 controller
You should also: have a basic understanding of networking concepts have a basic familiarity with the following software: RSLogix 5000 software RSLinx Classic software RSNetWorx for ControlNet software
Preface
Preface
Related Documentation
This table lists ControlNet products and documentation that may be valuable as you program your application.
Catalog Number 1756-CN2, 1756-CN2R 1756-CNB, 1756-CNBR 1769-L32C, 1769-L35CR 1784-PCC 1784-PCIC, 1784-PCICS 1784-PKTCS 1788-CNC, 1788-CNCR 1788-CNF, 1788-CNFR 1794-ACNR 1797-ACNR15 Title ControlLogix ControlNet Bridge Module Installation Instructions ControlLogix ControlNet Bridge Module Installation Instructions CompactLogix 1769-L32C, 1769-L35CR Controller Installation Instructions CompactLogix System User Manual ControlNet PCMCIA Communication Card Installation Instructions ControlNet Universal PCI Communication Interface Card Installation Instructions ControlNet Universal PCI Scanner Card Installation Instructions ControlNet Daughtercard Installation Instructions ControlNet Daughtercard Installation Instructions FLEX I/O ControlNet Adapter Module Installation Instructions ControlNet Ex Redundant Media Adapter Installation Instructions ControlNet Ex Coax Media System 1734-ACNR POINT I/O ControlNet Adapter Installation Instructions POINT I/O ControlNet Adapter User Manual Networks Series NetLinx Selection Guide 1786-RG6 and 1786-RG6F 1786 Series ControlNet Standard and High-flex Coax Cable Installation Instructions ControlNet Fiber Media Planning and Installation Guide ControlNet Media System Components List ControlNet Coax Media Planning and Installation Guide AC Drives, DC Drives Safety Guidelines - Application and Installation Publication Number 1756-IN602 1756-IN571 1769-IN070 1769-UM011 1784-IN034 1784-IN003 1784-IN042 1788-IN002 1788-IN005 1794-IN101 1797-5.14 1797-6.2.1 1734-IN582 1734-UM008 NETS-SG001 1786-IN009 CNET-IN001 AG-PA002 CNET-IN002 SGI-1.1
To view or download these publications, go to: http://www.rockwellautomation.com/literature To obtain a hard copy, contact your Rockwell Automation distributor or sales representative.
Preface
Notes:
Table of Contents
Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Summary of Changes
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . Summary of Changes-1 New and Revised Information . . . . . . . . . . . . . Summary of Changes-1 Purpose of This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Who Should Use This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . Information This Manuals Contains . . . . . . . . . . . . . . . . . . . . . Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preface-1 Preface-1 Preface-2 Preface-3
Preface
Chapter 1
Use This Chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Choose a ControlNet Communication Module . . . . . . . . . . . . . . . . . 1756-CN2, 1756-CN2R Overview ........................ 1756-CNB, 1756-CNBR Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . 1769-L32C, 1769-L35CR Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 1784-PCC Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1784-PCIC, 1784-PCICS, 1784-PKTCS Overview . . . . . . . . . . . . . . 1788-CNC, 1788-CNCR, 1788-CNF, 1788-CNFR Overview. . . . . . 1794-ACN15, 1794-ACNR15 Overview . . . . . . . . . . . . . . . . . . . . . . 1797-ACNR15 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1734-ACNR Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Use the ControlNet Communication Modules in a Control System. Bridge Across Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1-1 1-3 1-4 1-4 1-5 1-5 1-6 1-6 1-7 1-7 1-8 1-9
Table of Contents
Schedule the Network Offline . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13 Schedule the Network Online . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-19 Reschedule a ControlNet Network That Has Previously Been Scheduled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-23
Table of Contents
Message Type to Configure a MSG to Logix5000 Controller . . 6-8 Message Type to Configure a MSG to an SLC 500 Processor . . 6-9 Message Type to Configure a MSG to a PLC-5 Processor . . . 6-10 Communicate with PLC-5 or SLC 500 Processors . . . . . . . . . . . . . 6-12 Initiate MSGs from PLC-5 Processors to Logix5000 Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12 Map Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14 Stagger the Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16 Route PLC-5 Messages Between ControlNet Networks . . . . . . . . . 6-16 Route a ControlNet Message . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-17
Chapter 7 Communicate with PanelView and Use This Chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 RSView Products
Determine Connections to PanelView Terminals . . . . . . . . . . . . . . . Add a PanelView Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Organize Controller Data for a PanelView Terminal. . . . . . . . . . . . . Determine Connections to RSView Applications . . . . . . . . . . . . . . . 7-2 7-3 7-6 7-7
Table of Contents
1794-ACN15 and 1794-ACNR15 ControlNet FLEX I/O Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-21 1797-ACNR15 ControlNet FLEX Ex Redundant Media I/O Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23
Table of Contents
Use Redundant Media . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-17 Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-20 General Wiring Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-21 Order Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-23 General Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-23 Segment Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-23 Link Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-23
Index
Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . Backcover Installation Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Backcover
Table of Contents
Chapter
This chapter introduces the Logix5000 ControlNet communication modules and describes how you can use these modules in a control system:
For This Information Choose a ControlNet Communication Module 1756-CN2, 1756-CN2R Overview 1756-CNB, 1756-CNBR Overview 1769-L32C, 1769-L35CR Overview 1784-PCC Overview 1784-PCIC, 1784-PCICS, 1784-PKTCS Overview 1788-CNC, 1788-CNCR, 1788-CNF, 1788-CNFR Overview 1794-ACN15, 1794-ACNR15 Overview 1797-ACNR15 Overview 1734-ACNR Overview See Page 1-1 1-3 1-4 1-4 1-5 1-5 1-6 1-6 1-7 1-7
The remaining chapters in this publication describe how to configure and program the ControlNet communication modules. A listing of catalog numbers at the beginning of each chapter identifies the modules that support the feature described in that chapter.
The Logix5000 family offers several ControlNet communication modules. Select the module you need based on the ControlNet functions your application requires.
1-2
1756-CN2, 1756-CN2R 1756-CNB, 1756-CNBR 1769-L32C, 1769-L35CR 1784-PCC 1784-PCIC 1784-PCICS 1784-PKTCS(1) 1788-CNC, 1788-CNCR, 1788-CNF, 1788-CNFR 1794-ACN15, 1794-ACNR15 1797-ACNR15 1734-ACNR
(1) (2)
The module is a scanner (for example, the module can originate connections to remote I/O). When it functions as an I/O bridge, the module can (in conjunction with the controller) originate connections to remote I/O. When it functions as a messaging bridge, the module can function as a gateway from one network to another network or backplane without a controller program. To enable gateway functionality for the 1784-PCC card, RSLinx Gateway is required. When you use the CompactLogix 1769-L32C or 1769-L35CR controllers as a bridge from ControlNet to DeviceNet, you must use a 1769-SDN module in the local chassis. When it functions as an I/O adapter, the module can interface to I/O and serve as the target of a remote I/O connection from a controller.
(3)
(4)
(5)
The ControlNet communication modules: support messaging, produced/consumed tags and distributed I/O. share a common application layer with DeviceNet and EtherNet/IP. interface via RG-6 coaxial cable or 200/230 micron HCS (hard-clad silica) fiber optic cable. require no routing tables. support the use of coax and fiber repeaters for isolation and increased distance.
1-3
ControlLogix ControlNet communication modules bridge ControlNet links to route messages to devices on other networks. The modules also monitor and control I/O modules located remotely from the ControlLogix controller. The 1756-CN2 and 1756-CN2R modules are supported in the following software: RSLogix 5000 software version 15.01 The module can be used as a replacement for the 1756-CNB(R) when you select compatible keying for RSLogix 5000 software version 10 and later. RSNetWorx software version 6.
1756-CN2R shown
43605
You must install EDS files for earlier versions of RSNetWorx software. This module provides: high-speed I/O bridge functionality to manage distributed I/O modules. transfer of scheduled data via produced/consumed tags. unscheduled MSG instruction communication with other ControlNet nodes. messaging data for configuration and programming information, operator interfaces, upload/download. This module supports: adapter functionality for remote ControlLogix I/O modules. local communication network access through the network access port (NAP). redundant media (1756-CN2R only).
1-4
ControlLogix ControlNet communication modules bridge ControlNet links to route messages to devices on other networks. The modules also monitor and control I/O modules located remotely from the ControlLogix controller. This module provides: adapter functionality for remote ControlLogix I/O modules. messaging data for configuration and programming information, operator interfaces, upload/download. This module supports: I/O bridge functionality for applications requiring less performance than those applications that require the high-speed 1756-CN2(R). transfer of scheduled data via produced/consumed tags.
1756-CNBR shown
43605
unscheduled MSG instruction communication with other ControlNet nodes. local communication network access through the network access port (NAP). redundant media (1756-CNBR only).
The CompactLogix 1769-L32C and 1769-L35CR controllers have an integrated ControlNet port. This controller supports: transfer of scheduled data via produced/consumed tags. unscheduled MSG instruction communication with other ControlNet nodes. messaging data for configuration and programming information, operator interfaces, upload/download. local communication network access through the NAP. redundant media (1769-L35CR only).
1769-L35CR shown
43925
1-5
1784-PCC Overview
The 1784-PCC communication interface cards are personal computer memory card international association (PCMCIA) interface cards that enable laptop computers to communicate directly with other ControlNet products. These cards support: messaging data for configuration and programming information, operator interfaces, upload/download. unscheduled messaging communication with other ControlNet nodes. local communication network access through another ControlNet devices NAP. serves as a ControlNet traffic analyzer, catalog number 9220-WINTA.
43678
The 1784-PCIC, 1784-PCICS and 1784-PKTCS communication interface cards are peripheral component interconnect (PCI) open-bus interface cards that enable PCI local bus compatible computers to communicate directly with other ControlNet products. All of these cards support: unscheduled MSG instruction communication with other ControlNet nodes. messaging data for configuration and programming information, operator interfaces, upload/download. local communication network access through the NAP. redundant media.
The 1784-PCICS card also supports: I/O bridge functionality to manage distributed I/O modules. transfer of scheduled data via produced/consumed tags. a ControlNet I/O interface for the SoftLogix5800 controller. The 1784-PKTCS card also supports: I/O scanner functionality to manage distributed I/O modules as well as monitoring and configuration capabilities. transfer of scheduled data via produced/consumed tags. the IOLinx API for C++ and Visual Basic control applications. You cannot use the 1784-PKTCS card as a ControlNet I/O interface for the SoftLogix5800 controller.
1-6
The ControlNet communication card links the FlexLogix controller and PowerFlex 700S with DriveLogix controller to other devices on a ControlNet network. The ControlNet communication card also provides access for the FlexLogix controller to monitor and control I/O modules located remotely from the controller on the ControlNet network. These cards support: I/O bridge functionality to manage distributed I/O modules.
1788-CNCR shown
43679
transfer of scheduled data via produced/consumed tags. unscheduled MSG instruction communication with other ControlNet nodes. messaging data for configuration and programming information, operator interfaces, upload/download. local communication network access through the NAP - not available on the 1788-CNFR. redundant media (1788-CNCR and 1788-CNFR only). fiber media for optical isolation and increased noise immunity (1788-CNF and 1788-CNFR only) used in conjunction with the ControlNet short distance fiber repeaters. uses 200 micron cable (1786-FSxxx) with V-pin connectors and 1786-RPFS/RPA to connect to the network (1788-CNFR only).
The 1794-ACN15 and 1794-ACNR15 modules operate as adapters for FLEX I/O modules on a ControlNet network. This module supports: control of I/O within its chassisyou can connect up to 8 FLEX I/O modules to one 1794-ACN15 or 1794-ACNR15 module. unscheduled messaging data for configuration. local communication network access through the NAP.
control of individual I/O modules by different controllers. redundant media (1794-ACNR15 only).
1-7
1797-ACNR15 Overview
The 1797-ACNR15 modules operate as adapters for FLEX Ex I/O modules on a ControlNet network in an intrinsically safe environment. This module supports: control of I/O within its chassisyou can connect up to 8 FLEX Ex I/O modules to one 1797-ACNR15 module. unscheduled messaging data for configuration.
41411
1734-ACNR Overview
The 1734-ACNR module operates as an adapter for POINT I/O modules on a ControlNet network. This module supports: control of I/O within its chassis, with up to 63 POINT I/O modules connected to the adapter. unscheduled messaging data for configuration. local communication network access through the NAP. redundant media.
43248
The 1734-ACNR module appears as an I/O module, rather than as a ControlNet communication module, in RSLogix 5000the programming software for Logix5000 control systems. Additionally, the 1734-ACNR module is compatible with Logix5000 systems only; the module will not work with PLC or SLC controllers. For more information, see the 1734-ACNR user manual, publication 1734-UM008.
1-8
This figure shows how the different ControlNet modules can fit into a control system.
Figure 1.1 ControlNet Modules and the Control System Relationship
PC Running SoftLogix5800 Controller with 1784-PCICS Card Distributed I/O
For a redundant system you must use a 1756-CNB(R) communication module. The 1756-CN2(R) Series A module does not support redundancy. ControlNet 1794-ACN15 Adapter with 1794 I/O Modules CompactLogix 1769-L35CR Controller with Local 1769 I/O Modules
In this example:
IMPORTANT
If you are creating a ControlNet redundant system you will need to use a 1756-CNB module and refer to the ControlLogix Redundancy System User Manual, 1756-UM532. The 1756-CN2 Series A module does not support redundancy.
The controllers, for example CompactLogix, ControlLogix, FlexLogix, SoftLogix or PLC-5C can produce and consume tags among each other. The controllers can initiate MSG instructions that send/receive data or configure devices. The personal computer can upload/download projects to the controllers. The personal computer can configure devices on ControlNet, and it can configure the network itself.
1-9
Some ControlNet modules support the ability to bridge or route communication to and from different networks, depending on the capabilities of the platform and communication devices. With unscheduled communication, you have a bridge when you have a connection between communication devices on two separate networks. For example, the bridge device shown below has both ControlNet and DeviceNet connections so that Device 1 on ControlNet can communicate with Device 2 on DeviceNet through the bridge.
Device 1
Device 2
To use RSNetWorx software to configure and schedule a ControlNet network, we recommend that you either: connect to an EtherNet/IP network and bridge to a ControlNet network or use a 1784-PCC interface device to connect directly to a ControlNet network. Typically, this is a point-to-point connection between a Logix5000 controller and another device, such as a PanelView Plus operator terminal.
(2)
1-10
In this example, a workstation configures a drive on a DeviceNet network. The workstation bridges from ControlNet to DeviceNet to reach the drive.
Figure 1.2 Configure a Drive on a DeviceNet Network
Workstation PanelView Station
ControlNet Network
Drive
In this example, the bridge can be a ControlNet to DeviceNet bridging device, for example a 1788-CN2DN or a Logix5000 system with a ControlNet communication module and a DeviceNet communication module. This table describes how to use Logix5000 systems in this example.
Table 1.2 Example Bridges and Related Components If The Bridge Is CompactLogix system You Need These Components a CompactLogix 1769-L32C, or 1769-L35CR controller a 1769-SDN scanner ControlLogix system a 1756-CN2 module a 1756-CNB module a 1756-DNB module FlexLogix system a FlexLogix controller a 1788-CNx card a 1788-DNBO card SoftLogix system a SoftLogix controller a 1784-PCIC(S) card a 1784-PCIDS card
1-11
Keep in mind that you can only bridge messages across networks. You cannot bridge I/O connections from one network to another.
IMPORTANT
The CompactLogix and FlexLogix controllers performance degrades significantly if you use the controller as a bridge. Bridging over the FlexLogix controller should be targeted toward applications that are not real time dependent, for example RSLogix 5000 software program downloads.
In the Configure a Drive on a DeviceNet Network figure, status data can also be transferred from DeviceNet through the Logix5000 controller to a RSView32 operator interface. For a FlexLogix controller, map the data into the DeviceNet I/O image and then use RSLinx OPC from the PC to the Logix5000 controller over ControlNet. This avoids using the limited bridging resources of the FlexLogix controller. The example RSLinx software screen below shows how the EtherNet/IP bridge links to the ControlNet network:
EtherNet/IP Network
EtherNet/IP Bridge in 1794 System ControlNet Bridge in Same 1794 System ControlNet Network
You can bridge messages across multiple networks, but I/O Control is mostly restricted to being bridged across only one network. I/O Control from a ControlLogix controller over ControlNet to a scanner device is supported. You cannot go through a gateway chassis to control I/O, even though in some circumstances, RSLogix 5000 software accepts such a configuration in the I/O Configuration folder.
1-12
In a FlexLogix Controller 1788-CN(x) card 1788-DNBO card or 1788-CN(x) card one 1788-CN2DN module(2)
1788-CN(x) card 1788-ENBT card 1788-ENBT card 1788-CN(x) card 1788-ENBT card 1788-DNBO card or 1788-ENBT card one 1788-EN2DN module(3)
You can bridge from a ControlNet network to an Ethernet network and from an Ethernet network to a ControlNet via a SoftLogix virtual chassis. However, the products and methods you must use to do so are more detailed than can be effectively described in this table. For more information on how to bridge from one network to another via a SoftLogix virtual chassis, see the SoftLogix5800 System User Manual, publication number 1789-UM002. Can serve as a dedicated standalone bridge from ControlNet to DeviceNet. Can serve as a dedicated standalone bridge from EtherNet/IP to DeviceNet.
(2) (3)
Chapter
This chapter describes how to configure a personal computer to operate on a ControlNet network.
For This Information Connect a Computer to Any Network Configure the ControlNet Communication Driver in the RSLinx Software Connect a SoftLogix Controller to ControlNet See Page 2-2 2-3 2-5
You need to load a ControlNet communication driver for a personal computer to communicate with other devices on a ControlNet network. A personal computer needs this driver to: upload and download controller projects over ControlNet via RSLogix 5000 programming software. schedule the ControlNet network via RSNetWorx for ControlNet software. operate an HMI type application. Before you load a communication driver, make sure the: ControlNet communication card is already installed in the personal computer. personal computer is properly connected to the ControlNet network. For more information on how to install the ControlNet communication cards, use the installation instructions for each card. The respective installation instructions are listed in the table Related Documentation in the Preface.
2-2
To access a network, either: connect directly to the network or connect to a different network and browse (bridge) to the desired network. This requires no additional programming.
IMPORTANT
To use RSNetWorx software to configure and schedule a ControlNet network, either: connect to an EtherNet/IP network and bridge to the ControlNet network or use one of the laptop or desktop cards listed below to connect directly to the ControlNet network.
EtherNet/IP Network
Ethernet Card ControlNet Network Only lets you access devices on the DeviceNet network. DeviceNet Network
If you connect directly to a DeviceNet network, you can access only the devices on that network.
(1)
This module offers an RS-232 connection to standalone devices such as multi-vendor automation equipment, PCs, or modems.
(1)
This module offers an RS-232 connection to standalone devices such as multi-vendor automation equipment, PCs, or modems.
2-3
To configure the ControlNet communication driver for the personal computer (programming workstation):
IMPORTANT
Do not use these steps to configure a ControlNet communication driver for any application that uses a SoftLogix5800 controller. With the SoftLogix5800 controller, you can configure a ControlNet communication driver via the SoftLogix5800 Chassis Monitor. For more information on how to do this, see the section Connect a SoftLogix Controller to ControlNet.
2. Select a driver for ControlNet devices. In the example below, we choose the 1784-PCICS card. You can also connect your PC to a ControlNet network via the 1784-PCC card.
2-4
A. Name the driver. This example shows the default name AB_PCIC-1. B. Click OK.
4. After you create the driver, configure it to correspond to the ControlNet module within your computer.
A. If multiple cards are located in your computer, choose the correct one. B. Make sure you use the correct Network Address. C. Click OK.
The appearance of this screen varies widely depending on the type of card used.
The driver is now available and you can select the ControlNet port from Who Active in RSLogix 5000 programming software.
2-5
The SoftLogix5800 controller is a soft control solution that runs in a Microsoft Windows NT, Windows 2000, or Windows XP environment. When using this controller, you must install the SoftLogix5800 Chassis monitora virtual chassis that takes the place of hardware chassis used with other Logix5000 controllers. Before you can connect the SoftLogix system to the ControlNet network, you must create the 1784-PCIC, 1784-PCICS or 1784-PKTCS card as part of the SoftLogix chassis.
IMPORTANT
You can use only the 1784-PCIC, 1784-PCICS, or 1784-PKTCS cards to connect a SoftLogix controller to ControlNet.
A. Select the ControlNet card. B. Specify the virtual backplane slot number. C. Click OK.
3. Select the serial number of the ControlNet card you want. If you previously configured the card that you selected by serial number, the chassis monitor remembers the configuration from the last time you used the card (whether in the same or different slot).
A. If multiple cards are located in your computer, choose the serial number of the correct one. B. Click Next.
2-6
You can specify any slot number greater than 0 for the communication card. RSLinx software resides in slot 0. By creating the card in the virtual chassis, you configure the communication driver information needed by the SoftLogix controller. DO NOT use RSLinx software to install the ControlNet communication driver to the same card; installation through RSLinx software adds the potential for conflicting configuration between RSLinx software and the SoftLogix software chassis monitor. Instead, configure a Virtual Backplane driver in RSLinx software. After you add the card to the chassis monitor and configure a Virtual Backplane driver, you can browse the network by expanding the Virtual Backplane driver and then expanding the port on the desired ControlNet communication card. Browsing ControlNet through the Virtual Backplane driver provides the same functionality as the RSLinx software driver. The chassis monitor shows the 1784-PCICS card as a virtual module in the SoftLogix chassis. The LEDs on the virtual monitor emulate either a 1756-CN2R or a 1756-CNBR communication module.
Chapter
This chapter describes how to configure a ControlNet communication module to operate on a ControlNet network.
For This Information Set Up Your Computer to Connect to ControlNet Use RSLogix 5000 Software Add a Local ControlNet Module Add a Remote ControlNet Module Download the Project to the Logix5000 Controller Use RSNetWorx for ControlNet Software Schedule a ControlNet Network for the First Time Schedule the Network Offline Schedule the Network Online Reschedule a ControlNet Network That Has Previously Been Scheduled See Page 3-2 3-2 3-3 3-7 3-10 3-12 3-12 3-13 3-19 3-23
IMPORTANT
The example configuration process shown in this chapter uses a ControlLogix ControlNet Bridge module (1756-CNB) in a ControlLogix controller project. However, the overall configuration process (briefly described in the section Overview of the RSLogix 5000 Software Configuration Process) generally applies to any of the ControlNet communication modules covered by this manual.
To configure a ControlNet communication module to operate on the ControlNet network, you must: connect your computer to the RSLogix 5000 project via an RSLinx ControlNet software communication driver. add the ControlNet communication module to your RSLogix 5000 project. schedule the ControlNet network via RSNetWorx for ControlNet software.
3-2
You connect your personal computer to the ControlNet network via an RSLinx ControlNet software communication driver. You use the ControlNet communication driver to: upload and download controller projects using RSLogix 5000 software. schedule the ControlNet network via RSNetWorx for ControlNet software. For more information on how to connect a computer to the ControlNet network, see chapter Connect a Computer to the ControlNet Network.
Use RSLogix 5000 software to configure the I/O tree in your project.
There are some differences between configuring a local ControlNet communication module and a remote ControlNet communication module. Those differences are covered later in this chapter.
3-3
When you create a new RSLogix 5000 project with the CompactLogix 1769-L32C or 1769-L35CR controller, the Controller Organizer creates a ControlNet port in the local chassis. In this case, you do not need to add a separate local communication module.
2. Select the module type from the Select Module Type pop-up. The example below uses a 1756-CNB module.
3-4
This table lists the ControlNet communication modules available locally such as in the local chassis, computer, or controller with each Logix5000 controller.
Table 3.1 ControlNet Communication Modules Available Locally If You Are Using This Logix5000 Controller CompactLogix ControlLogix FlexLogix SoftLogix You Can Use This ControlNet Communication Module Locally 1769-L32C and 1769-L35CR controllers have a built-in ControlNet port 1756-CN2, 1756-CN2R 1756-CNB, 1756-CNBR 1788-CNC, 1788-CNCR, 1788-CNF, 1788-CNFR 1784-PCIC, 1784-PCICS, 1784-PKTCS
The example below shows configuration for a 1756-CNB module. However, depending on module-type such as a 1756, 1769, 1784, or 1788, there may be slight differences in how to configure a local ControlNet communication module. If you need help configuring a specific module, use online help in RSLogix 5000 software.
A. Name the module. B. Select the modules slot number. C. Select the modules minor revision level. D. Select an Electronic Keying level. For more information on choosing a keying level, see the table Electronic Keying Options. E. Click Next.
3-5
Then
When you test this portion of the system, clear the check box.
F. Click Finish. G. Determine if you want a major fault on the controller if the connection to the local communication module fails in Run Mode.
If You Want The Controller To fault (major fault) continue operating
(1)
Then Select the check box Leave the check box unchecked(1)
3-6
This table describes the keying options available in RSLogix 5000 software.
Table 3.2 Electronic Keying Options Keying Option Exact Match Definition When a controller establishes a connection with the ControlNet module, the following parameters must match or the inserted module will reject the connection: Vendor Product Type Catalog Number Major Revision Minor Revision Compatible Match When a controller establishes a connection with the ControlNet module, the inserted module decides whether it is compatible with the parameters listed above. Generally, all except Minor Revision must match or it will reject the connection.
TIP
We recommend using Compatible Match whenever possible. However, keep in mind that modules can emulate older revisions and, with major revision changes, the module only works to the level of the configuration. If a slot is configured for a module with major.minor revision of 1.7 and you insert a module with a major.minor revision of 2.3, the module works at the 1.7 level, with respect to module functions that are related to RSLogix 5000 software such as interface changes. However, bug fixes that are affected by the modules firmware, would work at the 2.3 revision level. If possible, we suggest you make sure configuration is updated to match the revision levels of all I/O modules. Failure to do so may not prevent the application from working but may defeat the purpose of upgrading your modules revision levels.
Disable Keying
When a controller establishes a connection with the ControlNet module, the inserted module attempts to accept the connection regardless of its type.
ATTENTION
Be extremely cautious when using the disable keying option; if used incorrectly, this option can lead to personal injury or death, property damage or economic loss.
Even if keying is disabled, a controller will not establish a connection if the slot is configured for one module type such as a communication module, and a module of another type such as an output module, is inserted in the slot.
3-7
2. Select the module type from the Select Module Type pop-up. You can connect any remote ControlNet communication module, to a local ControlNet communication module.
3-8
The example below shows configuration for a 1756-CNB module. However, depending on the remote module-type such as a 1734, 1756, 1769, 1784, 1788, or 1794, there are differences in how to configure a remote ControlNet communication module. If you need help configuring a specific module, use online help in RSLogix 5000 software.
A. Name the remote module. B. Select the remote modules Node. C. Select the remote Chassis Size. D. Select the Slot containing the remote module. E. Select a Comm Format. For more information on choosing a Comm Format, see the section Communication Format. F. Select the remote modules minor revision level.
G. Select an Electronic Keying level. For more information on choosing a keying level, see the table Electronic Keying Options.
H. Click Next.
I. Set the RPI rate. The RPI must be equal to or greater than the ControlNet Network Update Time (NUT). This parameter only applies if the module uses one of the Rack Optimized communication formats. J. Inhibit the module, if necessary.
Initially, do you want the module to communicate with the controller? Yes No
(1)
Then
K. Determine if you want a major fault on the controller if the connection to the PanelView fails in Run Mode.
If you want the controller to fault (major fault) continue operating
(1)
L. Click Finish.
Then Select the check box Leave the check box unchecked(1)
When you test this portion of the system, clear the check box.
3-9
Communication Format
The communication format determines: what configuration options are available - for example, if the module uses None, then you do not have to configure an RPI rate on the next screen. what type of data is transferred between the owner-controller and I/O connected via the communication module. what tags are generated when configuration is complete. the type of connection between the owner-controller and the I/O connected via the communication module. The communication format setting affects the Requested Packet Interval (RPI) rate on the next configuration screen. This table lists Communication Format choices.
Table 3.3 Communication Formats This Communication Format Choice Rack Optimized Means The communication module creates a rack image and returns I/O data in the rack image to the owner-controller. And Affects The RPI This Way You can specify an RPI that is: equal to or greater than the NUT.
Listen-Only Rack Optimized - Choice is not available on all ControlNet communication modules.
in the range permitted by RSLogix 5000 This option is available only for digital I/O modules. software, for example 2 - 750ms. Also keep in mind that diagnostic I/O modules will not return diagnostic data when you use this format. When you set the RPI for a remote ControlNet communication module, we recommend you use a The communication module creates a rack image rate that is a power of two times the NUT. and returns I/O input data in the rack image to the owner-controller. For example, if your NUT = 5ms, we recommend the following RPI values: The difference between this choice and Rack Optimized is that the I/O data in the rack image is NUT = 5m x 21 x 22 x 23 x 24 x 20 returned to a controller that does not control the outputs but is listening only to its input data. Optimal RPI 5ms 10ms 20ms 40ms 80ms
values
None
No RPI is required
Communication format does not apply to all ControlNet communication modules. For example, you do not choose a communication format when using the 1784-PCIC, 1784-PCICS nor 1788-CNx cards.
3-10
Before you your RSLogix5000 project configuration to your ControlNet Communication modules, consider whether you will schedule the ControlNet network offline or online. If you are going to schedule the network offline, complete the steps beginning in the section Schedule the Network Offline before downloading configuration. If you are going to schedule the network online, complete the steps beginning below and then move to the section Schedule the Network Online.
When you finish adding the local and remote ControlNet communication modules to your RSLogix 5000 project, you must download the new configuration to your Logix5000 controller. 1. Because you must schedule the ControlNet network (explained in the following section) before using the new configuration, switch your Logix5000 controller to Program mode in one of the following ways: Turn the controller keyswitch to PROG. Turn the controller keyswitch to REM and use RSLogix 5000 software to change the controller to Remote Program mode. 2. Use the Who Active button to begin the download process.
Click Who Active.
3-11
3. Use the Who Active pop-up screen to download the project to the controller.
A. Expand the tree until you find the correct driver. B. Select the controller to which you need to download configuration. In this example, the Logix5550 controller is connected via an RS-232 DF1 device. C. Click Download.
The window above uses a previously configured driver for the communication path to the controller. In this example, the computer is connected to the controllers RS-232 port, so the configuration is downloaded to the controller via RS-232 and DF-1 protocol. 4. Download the configuration.
Click Download.
Be aware, however, that before downloading configuration, the RSLogix 5000 software warns you of any implications the download has on your application.
3-12
You must use RSNetWorx for ControlNet software to schedule the network before the configured I/O devices in your application will become active. You must also reschedule the network if a change is made to an existing network that was already scheduled.
If you configure a keeper on one network and then use it on another network, the conflicting information can make it difficult to use RSNetWorx software to schedule the new network. In extreme cases it may be impossible to go online, more commonly you get many apparently irrelevant error messages about devices that existed on the old network but do not exist or are different on the new one. For more information on the network keeper, refer to the section Understanding the Network Keeper. For more information on how to reset valid keepers to an unconfigured state to resolve mismatches, see the RSNetWorx software online help. For more information on how to clear the memory or keeper information in a ControlNet communication module, refer to the Knowledgebase at http://support.rockwellautomation.com. You can schedule a ControlNet network either: offline or online. These options are covered in the following sections.
3-13
3-14
3. Because this is the first time you are scheduling the network, the file does not exist. When RSLogix 5000 software prompts you to create the new file, click Yes.
Click Yes.
This step creates the file that RSNetWorx for ControlNet software uses offline to browse and schedule network. 4. Launch RSNetWorx for ControlNet software to create the schedule.
A. Click on Schedule the ControlNet network. If you make this selection, RSNetWorx software automatically enable edits, create the schedule and disable edits. B. Click this button to launch the RSNetWork for ControlNet software.
3-15
5. The RSNetWorx for ControlNet software starts and creates a schedule that includes the devices in your RSLogix 5000 project. When the software prompts you to Optimize and re-write schedule for all connections, click OK.
Click OK.
Because you selected the Schedule the Network option in a previous step, RSNetWorx for ControlNet software automatically enables and disables edits before and after creating the schedule for the network respectively. 6. Enable Edits in the schedule.
TIP
We recommend that you return to the RSLogix 5000 software and save the project after you enable edits in the RSNetWorx for ControlNet software. Saving the file updates the network file in your RSLogix 5000 project.
7. To change the network properties from default settings to those that best fit your network, access the network properties.
A. Click Network. B. Click Properties.
3-16
The table Network Parameters for Scheduling the Network Offline describes the parameters used on this screen.
3-17
Table 3.4 Network Parameters for Scheduling the Network Offline Parameter Network Update Time (ms) Max. Scheduled Address Description The smallest user-configurable repetitive time cycle in milliseconds at which data can be sent on ControlNet. This is the node with the highest network address that can use scheduled time on a ControlNet link. I/O data is transferred during scheduled time. RSNetWorx for ControlNet software sets this value. We recommend that you do not change it. Max. Unscheduled Address Node with the highest network address that can use unscheduled time on a ControlNet link. Messaging data is transferred during unscheduled time. Nodes set at addresses higher than the maximum unscheduled node do not communicate on the network, for example they will not display in RSLinx software. Media Redundancy Network Name Designates if the network uses media redundancy User-defined name of the network
9. If necessary, change the media configuration. The default media configuration is sufficient in most cases. However, adjust the configuration if your network is longer or uses repeaters. If the media configuration does not accurately represent the maximum propagation delay between any two nodes, your network may experience errors.
This example shows the default media configuration of 1000m of RG6 coaxial cable.
3-18
11. Return to your RSLogix 5000 project to: a. save the project again. b. download configuration, as described in the section Download the Project to the Logix5000 Controller.
3-19
4. Go online.
Click Network > Online.
3-20
A. Expand the tree to find your communication path. B. Select your communication path. C. Click OK.
The window above uses a previously configured communication path to the controller. In this example, the computer is connected to the ControlNet network via a 1784-PCIC card. The driver was previously configured via RSLinx software, as described in the chapter Connect a Computer to the ControlNet Network. 6. Set the network to Single Browse Pass.
Select Network > Single Pass Browse.
7. Enable edits on the file. When you enable edits, the RSNetWorx for ControlNet software reads data in the ControlNet modules and builds a schedule for the network.
3-21
The table Network Parameters for Scheduling the Network Online describes the parameters used on this screen.
3-22
Table 3.5 Network Parameters for Scheduling the Network Online Parameter Network Update Time (ms) Max. Scheduled Address Description The smallest user-configurable repetitive time cycle in milliseconds at which data can be sent on ControlNet. This is the node with the highest network address that can use scheduled time on a ControlNet link. I/O data is transferred during scheduled time.RSNetWorx for ControlNet software sets this value. We recommend that you do not change it. Node with the highest network address that can use unscheduled time on a ControlNet link. Messaging data is transferred during unscheduled time. Nodes set at addresses higher than the maximum unscheduled node do not communicate on the network, for example they will not display in RSLinx software. Media Redundancy Network Name Designates if the network uses media redundancy on any of the network communication modules. User-defined name of the network
10. If necessary, change the media configuration. The default media configuration is sufficient in most cases. However, adjust the configuration if your network is longer or uses repeaters. If the media configuration does not accurately represent the maximum propagation delay between any two nodes, your network may experience errors.
This example shows the default media configuration of 1000m of RG6 coaxial cable.
11. Save the file. This will schedule and activate the network.
A. Select Optimize and re-write schedule for all connections. B. Click OK.
3-23
3. Go online.
A. Click Network. B. Click Online.
3-24
4. Enable edits on the file. When you enable edits, the RSNetWorx for ControlNet software reads data in the ControlNet modules and builds a schedule for the network.
5. Save the file. This will schedule and activate the network.
A. Select Optimize and re-write schedule for all connections. B. Click OK.
IMPORTANT
It is always preferable to optimize connections. However, in some cases involving multiple controllers, the Merge changes... option is available. This option lets controllers whose connections have not changed to continue uninterrupted operation. When you merge changes into the existing schedule, those controllers whose connections have not changed remain in Run mode rather than changing to Program mode.
Chapter
Control I/O
This chapter describes how a controller controls distributed I/O over ControlNet. The controller requires a communication module to connect to the network. Distributed I/O modules require an adapter to connect to the network.
For This Information Set Up the Hardware Set a Requested Packet Interval Select a Communication Format Add Local and Remote ControlNet Modules Add Distributed I/O Access Distributed I/O Validate Connections See Page 4-2 4-2 4-3 4-10 4-11 4-13 4-17
To control distributed I/O over ControlNet, you must: Add local and remote ControlNet communication modules to your RSLogix 5000 project. When you create a new RSLogix 5000 project with the CompactLogix 1769-L32C or 1769-L35CR controller, the Controller Organizer creates a ControlNet port in the local chassis. In this case, you do not need to add a separate local communication module. Add distributed I/O to your RSLogix 5000 project. Schedule the ControlNet network via RSNetWorx for ControlNet software. Use the I/O information in RSLogix 5000 software. You can also validate connections to distributed I/O when controlling it over ControlNet. This task is particularly useful when one or more of the connections are not working but is not required, especially when all connections appear to work normally.
4-2
Control I/O
In this example, the Logix5000 controller uses a ControlNet communication module in the local chassis to connect to the ControlNet network. The distributed (remote) I/O has a ControlNet adapter to connect it to the ControlNet network.
Data Distributed I/O ControlNet Adapter With I/O Modules
Programming Terminal
43611
Make sure: all wiring and cabling is properly connected. the communication driver (such as, AB-PCICS-1) is configured for the programming workstation.
When you configure an I/O module, you define the RPI for the module. The RPI specifies the period at which data updates over a connection. For example, an input module sends data to a controller at the RPI that you assign to the module. Configure the RPI in milliseconds. RPIs are only used for modules that produce or consume data. For example a local ControlNet communication module does not require an RPI because it is not a data-producing member of the system; it is used only as a bridge. In Logix5000 controllers, I/O values update at a period that you configure via the I/O configuration folder of the project. The values update asynchronously to the execution of logic. At the specified interval, the controller updates a value independently from the execution of logic.
Control I/O
4-3
When you configure a remote ControlNet communication module or an I/O module, you select a communication format. The communication format you choose determines the data structure for the tags that are associated with the module. Many I/O modules support different formats. Each format uses a different data structure. The communication format that you choose also determines: Direct or rack optimized connection Ownership of outputs For a remote ControlNet communication module, you must select one of the formats listed in the table Communication Formats.
Table 4.1 Communication Formats Use This Communication Format with a Remote ControlNet Communication Module None In These Scenarios
All of the remote I/O communicating with a controller via the remote ControlNet communication module use a Direct Connection communication format. The connection is used for scheduled peer interlocking. When I/O will be predominately direct connections. When multiple controllers control the outputs in the chassis
Rack optimized
Some or all of the remote I/O communicating with a controller via the remote ControlNet communication module use a Rack Optimized communication format. To minimize ControlNet bandwidth when using large volume of digital I/O. If only one controller will control the I/O.
Some or all of the remote I/O communicating with a controller via the remote ControlNet communication module use a Rack Optimized communication format. The connection is going to read inputs but is not going to be controlling outputs.
4-4
Control I/O
For I/O modules the available communication formats depend on the module type. This table describes the different communication formats for general module types.
Table 4.2 Communication Format for Module Types If You Have This Type of I/O Module digital module And Want a rack optimized connection a direct connection or to use specialty features of the module, such as diagnostics, timestamps, or electronic fuses or to only listen to data from the module analog module a direct connection or to use specialty features of the module, such as diagnostics, timestamps, or electronic fuses or to only listen to data from the module A Listen Only communication format that matches the data the I/O module is broadcasting to other controllers. A Listen Only communication format that matches the data the I/O module is broadcasting to other controllers. The data your controller needs from the I/O module. For example, if your application uses a 1756-OF6CI module in a remote chassis that must provide floating point output data, you should select the Float Data communication format. Select a Communication Format That Specifies Rack Optimization The data your controller needs from the I/O module. For example, if your application uses a 1756-IA16I module in a remote chassis that must provide timestamped input data, you should select the CST Timestamped Input Data communication format.
See the online help in RSLogix 5000 programming software for specific communication formats per I/O module.
Control I/O
4-5
A direct connection is any connection that does not use the Rack Optimization Comm Format. Rack optimized Connection Digital I/O modules only A rack optimized connection consolidates connection usage between the controller and all the digital I/O modules in the chassis (or DIN rail). Rather than having individual, direct connections for each I/O module, there is one connection for the entire chassis (or DIN rail). Anytime a remote chassis houses I/O modules that use rack optimized connections, the remote ControlNet communication module connecting these modules to their owner-controller must also use a rack optimized connection. However, you can mix direct and rack optimized connections to the same remote chassis. For example, if your remote chassis houses 6 digital I/O modules and your application requires that you use direct connections for 3 but rack optimized connections for the other others, you can select direct connections for the 3 that require them and rack optimized connections for the other 3. In this case, even though you must use a rack optimized connection for the remote ControlNet communication module the owner-controller still makes direct connections with the 3 I/O modules that are configured as such. You can only make up to 5 rack optimized connections to a single remote ControlNet communication module.
4-6
Control I/O
ControlNet Network
I/O I/O
ControlNet Adapter with Digital I/O Modules
I/O I/O
ControlNet Adapter with Analog I/O Modules
I/O I/O
ControlNet Adapter with Digital I/O Modules
In this example, the remote ControlNet adapter uses the None communication format.
TIP
If you have a high number of modules, direct connections to each module may not be feasible because the module supports a finite number of connections, and direct connections may require more resources than the module has available. In this case, use rack optimized connections (see the section Rack Optimized Connections for I/O Modules) to conserve connection use and network traffic.
Control I/O
4-7
ControlNet Network
I/O I/O
ControlNet Adapter with Digital I/O Modules
I/O I/O
ControlNet Adapter with Analog I/O Modules
I/O I/O
ControlNet Adapter with Digital I/O Modules
The rack optimized connection conserves connections, but can limit the status and diagnostic information that is available from the digital I/O modules. To increase the number of available connections, use a rack optimized connection to any remote adapter with multiple digital I/O modules that allow rack optimized connection, instead of direct connections to those I/O modules.
4-8
Control I/O
Ownership
In a Logix5000 system, modules multicast data. This means that multiple controllers can receive the same data at the same time from a single module. When you choose a communication format, you have to choose whether to establish an owner or listen-only relationship with the module.
Owner Controller The controller that creates the primary configuration and communication connection to a module. The owner controller writes configuration data and can establish a connection to the module. The owner controller is the only device that controls the outputs.
An owner connection is any connection that does not include Listen-Only in its Comm Format. Listen-only Connection An I/O connection where another controller owns/provides the configuration data for the I/O module. A controller using a listen-only connection only monitors the module. It does not write configuration data and can only maintain a connection to the I/O module only when the owner controller is actively controlling the I/O module.
listen-only connection
Control I/O
4-9
There is a noted difference in controlling input modules versus controlling output modules
Table 4.6 Module Ownership Control Controlling Input Modules This Ownership Owner Description The controller that establishes an owner connection to an input module configures that module. This configuring controller is the first controller to establish an owner connection. Once a controller owns and configures an input module, other controllers can establish owner connections to that module. This lets additional owners to continue to receive multicasted data if the original owner-controllers connection to the module breaks. All other additional owners must have the identical configuration data and identical communication format that the original owner controller has, otherwise the connection attempt is rejected. Listen-only Once a controller owns and configures an input module, other controllers can establish a listen-only connection to that module. These controllers can receive multicast data while another controller owns the module. If all owner controllers break their connections to the input module, all controllers with listen-only connections no longer receive multicast data. The controller that establishes an owner connection to an output module configures that module. Only one owner connection is allowed for an output module. If another controller attempts to establish an owner connection, the connection attempt is rejected. Once a controller owns and configures an output module, other controllers can establish listen-only connections to that module. These controllers can receive multicast data while another controller owns the module. If the owner controller breaks its connection to the output module, all controllers with listen-only connections no longer receive multicast data.
Output Modules
Owner
Listen-only
4-10
Control I/O
Before you can connect to and control distributed I/O, you must add local and remote ControlNet communication modules. The type of distributed I/O determines your choice of a remote ControlNet adapter. For more information, see the table Choose the Appropriate Remote Adapter.
Table 4.7 Choose the Appropriate Remote Adapter If The Distributed I/O Is 1756 ControlLogix I/O 1794 FLEX I/O 1797 FLEX Ex I/O 1734 POINT I/O Select This Remote Adapter 1756-CN2, 1756-CN2R 1756-CNB, 1756-CNBR 1794-ACN15, 1794-ACNR15 1797-ANCR 1734-ACNR Which You Configure Via RSLogix 5000 software
The figure Add Local and Remote ControlNet Modules to an RSLogix 5000 Project shows a brief series of screens used when adding local and remote ControlNet communication modules to an RSLogix 5000 project. For more detailed information on how to add local and remote ControlNet modules to your project, see the chapter Configure a ControlNet Module.
Figure 4.1 Add Local and Remote ControlNet Modules to an RSLogix 5000 Project
1. Add Local ControlNet Communication Module
Control I/O
4-11
To communicate with the I/O modules in your system, you add bridge, adapter, and I/O modules to the I/O Configuration folder of the controller. Within the I/O Configuration folder, you organize the modules into a hierarchy (tree/branch, parent/child).
Device
A. Add the local communication module (bridge). B. Add the remote adapter for the distributed I/O chassis or DIN rail. C. Add the distributed I/O module.
Do these steps to add distributed I/O to your RSLogix 5000 project: 1. Add the local and remote ControlNet communication modules as described in section Add Local and Remote ControlNet Modules or in the chapter Configure a ControlNet Module . 2. Add the distributed I/O module.
A. Right-click on the remote ControlNet communication module. B. Click New Module.
4-12
Control I/O
3. Configure the distributed I/O module. Depending on the distributed I/O type, the configuration screens differ. The example below shows screen for a 1794-IB16XOB16P/A digital combo module. For more information on configuring distributed I/O modules over ControlNet, see the modules individual technical documentation and the RSLogix 5000 software online help.
To Use the modules default configuration. Customize the configuration. Do This Specify the general information about the module, such as name, comm format, RPI and click Finish. Specify the general information about the module such as name, comm format, RPI. Then click Next to step through subsequent screens to configure such parameters as filter times and fault actions.
The Comm Format selection you make when you add distributed I/O modules is based on whether you want rack optimized or direct connections to each distributed I/O module. In general, use this table to select distributed I/O formats.
Control I/O
4-13
Table 4.8 Distributed I/O Formats If You Select This Format For The Remote Adapter Rack Optimization None Select This Format For The Distributed I/O Module Rack Optimization an appropriate direct-connection format
I/O information is presented as a structure of multiple fields that depend on the specific features of the I/O module. The name of the structure is based on the location of the I/O module in the system. Each I/O tag is automatically created when you configure the I/O module in RSLogix 5000 software. Each tag name follows this format: Location:SlotNumber:Type.MemberName.SubMemberName.Bit where:
Is Identifies network location LOCAL = local DIN rail or chassis ADAPTER_NAME = identifies remote adapter or bridge that you specify
SlotNumber Type
Slot number of I/O module location in its chassis Type of data I = input O = output C = configuration S = status
MemberName
Specific data from the I/O module; depends on the type of data the module can store. For example, Data and Fault are possible fields of data for an I/O module. Data is the common name for values that are sent to or received from I/O points. Specific data related to a MemberName. Specific point on the I/O module; depends on the size of the I/O module (0-31 for a 32-point module)
4-14
Control I/O
I/O information is available in the Controller Tags portion of your RSLogix 5000 project. You can monitor or edit the tags. The example screens below show how to access the Controller Tags and some sample tags.
Control I/O
4-15
The example below shows an I/O tree configured with a remote FLEX I/O adapter and four remote FLEX I/O modules. EXAMPLE
Example 1 Example 2 Example 3 Example 4 Example 5
The table Example Tag Names describes some of the tag names that appear for these modules. The tags listed are not a complete list of the tags created for each module type. For a full list of the tags created for each module when configured as shown the second column, see the tag monitor/editor portion of RSLogix 5000 software.
4-16
Control I/O
Table 4.9 Example Tag Names Example Example 1 Module remote 1794-ACN15 adapter FLEX_adapter Example Tag Names (automatically created by the software) FLEX_adapter:I FLEX_adapter:I.SlotStatusBits FLEX_adapter:I.Data FLEX_adapter:O FLEX_adapter:O.Data FLEX_adapter:0:C FLEX_adapter:0:C.Config FLEX_adapter:0:C.DelayTime_0 FLEX_adapter:0:I FLEX_adapter:1:C FLEX_adapter:1:C.SSData FLEX_adapter:1:O FLEX_adapter:1:O FLEX_adapter:2:C FLEX_adapter:2:C.Config1 FLEX_adapter:2:C.FilterCutoff0 FLEX_adapter:2:C.ReferenceJunction3 FLEX_adapter:2:C.FaultMode_0_3 FLEX_adapter:2:C.DataFormat11 FLEX_adapter:2:I FLEX_adapter:2:I.Fault FLEX_adapter:2:I.Ch0Data FLEX_adapter:2:I.Alarms FLEX_adapter:3:C FLEX_adapter:3:C.InputFilter FLEX_adapter:3:C.RTSInterval FLEX_adapter:3:C.Ch0InputCalibrate FLEX_adapter:3:I FLEX_adapter:3:I.Fault FLEX_adapter:3:I.RealTimeSample FLEX_adapter:3:O FLEX_adapter:3:O.SafeStateConfig0 FLEX_adapter:3:O.OutputEnable FLEX_adapter:3:O.Ch0OutputData
Example 2
Example 3
Example 4
Example 4
Control I/O
4-17
Validate Connections
Verify that the controller can communicate with the devices that you have just configured. Do these steps: 1. Determine if communications has been established with the devices. a. If a ! is NOT over the I/O Configuration folder, the controller can communicate with the device. Connections are valid. b. If a ! is over the I/O Configuration folder, the controller cannot communicate with the device. Go to step 2. 2. Identify any faults. Start looking for faults at the communication module and work down through the tree. In the example screen below, faults occurred at the remote 1756-CNB module and the I/O modules added below it.
4-18
Control I/O
3. Identify the fault code. If multiple faults appear on the screen, as shown above, identify the fault at the module that is highest in the I/O tree.
C. Click on the Connection tab. D. Identify the code for the fault. E. Use the Help button to access the online help and determine what the fault codes mean. For more information on fault codes, see step 4 on page 4-19.
Control I/O
4-19
4. If necessary, get the definition of the fault code from the online help.
A. Click Help. B. Click Contents
E. When the list of module fault codes appears, select the range for the code you just identified. F. Click Display.
5. Follow the recommendations for your fault code. 6. Return to the step: Determine if communications has been established with the devices.
4-20
Control I/O
Notes:
Chapter
This chapter describes how to interlock (produce and consume tags) controllers via a ControlNet network.
For This Information Terminology Set Up the Hardware Determine Connections for Produced and Consumed Tags Organize Tags for Produced or Consumed Data Adjust for Bandwidth Limitations Produce a Tag Consume a Tag Additional Steps for a PLC-5C or ControlNet Scanner Card See Page 5-1 5-2 5-3 5-3 5-6 5-7 5-9 5-12
Interlocking controllers is a method of sharing scheduled data between controllers. Methods of communicating with other controllers are listed below:
If The Data Needs regular, fast delivery at an interval that you specify Is sent when a specific condition occurs in your application Then Produce and consume a tag Execute a message (MSG) instruction See Chapter Produce and Consume Tags (Interlock Controllers) Peer-to-Peer Messaging
Terminology
A Logix5000 controller lets you produce (broadcast) and consume (receive) system-shared tags.
Term produced tag Definition A tag that a controller makes available for use by other controllers. Multiple controllers can simultaneously consume (receive) the data. A produced tag sends its data to one or more consumed tags (consumers) without using logic. The produced tag sends its data at the RPI of the fastest consuming tag.
consumed A tag that receives the data of a produced tag. The data type of the consumed tag tag must match the data type (including any array dimensions) of the produced tag. The RPI of the fastest consumed tag determines the period at which the produced tag is produced.
For two controllers to share produced or consumed tags, both controllers must be attached to the same ControlNet network.
1 Publication CNET-UM001C-EN-P - November 2005
5-2
In this example, the controller in the first chassis produces a tag that is consumed by the controller in the second chassis.
Data Chassis #2 Logix5000 Controller with ControlNet Communication Module
43611
The Logix5000 controller in the first chassis and in the second chassis can be any of the following, with their ControlNet communication modules: 1756 ControlLogix controller with a 1756-CN2 or 1756-CN2R communication module in the chassis 1756 ControlLogix controller with a 1756-CNB or 1756-CNBR communication module in the chassis 1769-L32C or 1769-L35CR CompactLogix controller 1789 SoftLogix controller with a 1784-PCICS or 1788-PKTCS communication card 1794 FlexLogix controller with a 1788-CNx ControlNet communication card PowerFlex 700S with DriveLogix controller and a 1788-CNx ControlNet communication card Non-Logix5000 controller or other device connected to ControlNet via a ControlNet scanner card. For more information refer to the section Additional Steps for a PLC-5C or ControlNet Scanner Card. Make sure that: the ControlNet communication modules are connected to a scheduled ControlNet network. all wiring and cabling is properly connected.
5-3
the communication driver (such as., AB-PCICS-1) is configured for the programming workstation. TIP If you are only sharing tags between ControlLogix controllers (the controllers are not controlling any I/O modules), you can set the communication format of the 1756-CN2(R) or the 1756-CNB(R) module in the remote chassis to None. This reduces connection usage and network traffic.
Logix controllers can produce (broadcast) and consume (receive) system-shared tags that are sent and received via the ControlNet communication module. Produced and consumed tags each require connections.
This Type of Tag produced Requires These Connections The produced tag requires two connections. The producing controller must have one connection for the produced tag and the first consumer and one more connection for each additional consumer (heartbeat). The heartbeat is a small scheduled packet the consumer sends to indicate that it is getting the produced data. As you increase the number of controllers that can consume a produced tag, you also reduce the number of connections the controller has available for other operations, like communication and I/O. consumed Each consumed tag requires one connection for the controller that is consuming the tag.
All ControlNet modules support at least 32 connections. Additionally, the total number of tags that can be produced or consumed is limited by the number of available connections. If the communication module uses all of its connections for I/O and other communication modules, no connections are left for produced and consumed tags.
5-4
This table describes each produced or consumed tag and the number of connections used.
Table 5.1 Produced and Consumed Tags and number of Connections This Controller CompactLogix FlexLogix PowerFlex 700S with DriveLogix ControlLogix 250 SoftLogix5800 This Communication Card ControlNet port on the CompactLogix controller 1788-CNx card in either: FlexLogix controller PowerFlex 700S with DriveLogix controller 1756-CN2 in the local chassis of a ControlLogix controller 1756-CNB in the local chassis of a ControlLogix controller 1784-PCICS card in a SoftLogix5800 controller Has This Many Connections Available 32 32 total ControlNet connections, 22 of which can be scheduled and used for producing and consuming tags number of consumers 100 64 - We recommend that you do not use more than 40 to 48 scheduled connections. 127 1 A Produced Tag Uses This Many Connections A Consumed Tag Uses This Many Connections 100 number of consumers + 1 1 Has This Many Connections Available A Produced Tag Uses This Many Connections A Consumed Tag Uses This Many Connections
5-5
This table describes the guideline to follow as you organize your tags for produced or consumed data (shared data).
Table 5.2 Guidelines for Produced or Consumed Data Tags
You can only produce and consume controller-scoped tags. You cannot produce or consume the following tag types: Alias Axis type BOOL Consumed I/O INT Message
Use one of these data types: DINT REAL array of DINTs or REALs user-defined Limit the size of the tag to 480 bytes. To share tags with a PLC-5C controller, use a user-defined data type.
To share other data types, create a user-defined data type that contains the required data. Use the same data type for the produced tag and corresponding consumed tag or tags.
If you must transfer more than 480 bytes, create logic to transfer the data in smaller packets or create multiple produce/consume tags. To produce This integers, BOOLs or combinations of both Then Create a user-defined data type that contains an array of INTs with an even number of elements, such as INT[2].
only one REAL value Use the REAL data type. more than one REAL Create a user-defined data type that contains an array of REALs. value consume integers Create a user-defined data type that contains the following members: Data type DINT Description Status BIT 0 = 0 PLC5 in PROG mode = 1 PLC5 in RUN mode INT[x], where x is the output size of the data from the PLC-5C controller. (If you are consuming only one INT, omit x.) Use the highest permissible RPI for your application. Data produced by a PLC-5C controller
If the controller consumes the tag over a ControlNet network, use a binary multiple of the ControlNet network update time (NUT). For example, if the NUT is 5 ms, use an RPI of 5, 10, 20, 40 ms.
5-6
Details If you are producing several tags for the same controller: Group the data into one or more user-defined data types. (This uses less connections than producing each tag separately.) Group the data according to similar update intervals. (To conserve network bandwidth, use a greater RPI for less critical data.) For example, you could create one tag for critical data and another tag for data that is not as critical.
When you share a tag over a ControlNet network, the tag must fit within the bandwidth of the network: As the number of connections over a ControlNet network increases, several connections, including produced or consumed tags, may need to share a network update time (NUT). A ControlNet node can transmit approximately 500 bytes of scheduled data in a single NUT. Depending on the size of your system, you may not have enough bandwidth on your ControlNet network for large tags. If a tag is too large for your ControlNet network, make one or more of the following adjustments.
Table 5.3 Tag Adjustments
Adjustment Increase the requested packet interval (RPI) of your connections Recommended method Reduce your network update time (NUT). For a ControlNet bridge module, CN2(R) or CNB(R) in a remote chassis, select the most efficient communication format for that chassis:
Description At higher RPIs, connections can take turns sending data during an update period.
At a faster NUT, less connections have to share an update period. Are most of the modules in the chassis non-diagnostic, digital I/O modules? Yes No Then select this communication format for the remote CN2 or CNB module: Rack Optimization None
The Rack Optimization format uses an additional 8 bytes for each slot in its chassis. Analog modules or modules that are sending or getting diagnostic, fuse, timestamp, or schedule data require direct connections and cannot take advantage of the rack optimized form. Selecting None frees up the 8 bytes per slot for other uses, such as produced or consumed tags. Separate the tag into two or more smaller tags. 1. Group the data according to similar update rates. For example, you could create one tag for data that is critical and another tag for data that is not as critical. 2. Assign a different RPI to each tag. Create logic to transfer the data in smaller sections (packets). For information on how to do this, see the Logix5000 Controllers Common Procedures Programming Manual, publication 1756-PM001.
5-7
Produce a Tag
A Logix5000 controller can only produce controller-scoped user-created tags in the local controllers tag structure. The Logix5000 controllers cannot produce I/O tags or tags aliased to I/O tags. Follow the steps below to produce a tag: 1. Open the RSLogix 5000 project that contains the tag that you want to produce.
IMPORTANT
You can only create produced tags when your RSLogix 5000 project is offline.
A. Type the name of the new tag in an available Tag Name field. B. Press Enter.
5-8
A. Choose the Produced Tag Type. B. Make sure the Data Type is one that the controller can produce A controller cannot produce a tag using the MSG [or INT] Data Type. C. Click on the Connection tab. D. Adjust the number of consumers. If you are unsure of the number of consumers, you can use a number higher than the actual number of consumers. However, unused connections are deducted from the number of connections your controller has available. E. Click OK.
IMPORTANT
When your Logix5000 controller produces a tag, any device that interfaces to ControlNet can consume the tag. However, when a non-Logix controller such as a PC using a 1784-PKTCS card, is consuming the tag produced by a Logix controller, you must perform additional tasks in RSNetWorx for ControlNet software. For more information, see the section Additional Steps for a PLC-5C or ControlNet Scanner Card.
5-9
Consume a Tag
Logix5000 controllers can only consume controller-scoped user-created tags from another controllers tag structure. The Logix5000 controllers cannot consume I/O tags or tags aliased to I/O tags. Follow the steps below to consume a tag:
IMPORTANT
You can only create consumed tags when your RSLogix 5000 project is offline.
1. Open the RSLogix 5000 project that contains the controller that you want to consume the produced tag. 2. Make the sure the controller producing the tag to be consumed is in the consuming controllers I/O configuration, as shown in the example below. Additionally, make sure the Communication Format for the remote ControlNet module is None.
Local ControlNet Module in Consuming Controllers Chassis Remote ControlNet Module Producing Controller
A. Type the name of the new tag in an available Tag Name field. B. Press Enter.
5-10
A. Choose the Consumed Tag Type. B. Make sure the Data Type and Data Style matches the Type and Style in the tag created in step 5 on page 5-8.
C. Click on the Connection tab. D. Choose the Producer, the producing controller, from the pull-down menu. The menu contains all possible paths to previously configured controllers in the I/O tree. E. Type in the name of the produced tag in the producing controller. F. Set the RPI. The consuming controller determines the rate at which the tag is produced. G. Click OK.
5-11
Your Logix5000 controller can consume a tag that was produced by any device that interfaces to ControlNet. However, when a non-Logix controller such as a PC using a 1784-PKTCS card, produces the tag that a Logix controller consumes, you must perform additional tasks in RSNetWorx for ControlNet. For more information, refer to the section Additional Steps for a PLC-5C or ControlNet Scanner Card.
5-12
Some devices connect to the ControlNet network via a ControlNet scanner and can use produced and consumed tags to share scheduled data with Logix5000 controllers. For example, you can connect a real-time control application, such as a Visual Basic application, to ControlNet through a 1784-PKTCS scanner card to exchange data with Logix5000 controllers. When you use produced and consumed tags to exchange data between Logix5000 controllers and a ControlNet scanner, you must also use the RSNetWorx Scanlist Configuration Tool to configure the scanner to produce and consume the data sent to and/or received from the Logix5000 controllers. The following ControlNet scanners require additional steps to exchange data with a Logix5000 controller via produced and consumed tags: PLC-5C controller 1784-PKTCS communication scanner card This card is used in a personal computer with a real-time control application and IOLinx or an HMI application and RSView ME. 2711P-RN15S communication scanner card This card is used in PanelView Plus and VersaView CE HMI terminals. 2711P-RN15C communication module This module is used in a PanelView Plus HMI terminal.
5-13
3. Enable edits.
5-14
5. Insert a Target for Connections on the ControlNet scanner that is producing the tag.
A. Right-click on the ControlNet scanner device. B. Click Insert Target for Connections....
6. When the Insert Target for Connections pop-up menu appears, make sure it is configured correctly.
A. Choose Send Data. B. Make sure the Produce Buffer ID equals the Remote Data, the tag name or instance value for the consumed tag in RSLogix 5000 software. C. Make sure the Output Size matches the consumed tags size. Note that the size on this screen is in 16-bit words.
5-15
3. Enable edits.
5-16
5. Insert a connection to the Logix5000 controller that will consume the tag that the ControlNet scanner produces.
6. When the Connection Properties pop-up menu appears, make sure the Connection tab is configured correctly.
A. Choose Receive Data. B. Type Tag in the Name field. C. Type the name of the Produced tag from the Logix5000 controllers RSLogix 5000 project in the Value field. If this name does not exactly match the name of the produced tag, the ControlNet scanner will not consume the tag. D. Make sure the Input Size matches the produced tags size. Note that the size on this screen is in 16-bit words and must be an even number.
5-17
When you are using a PLC-5C controller or a ControlNet scanner to consume tags, keep the following in mind about the Input Size field: If the scanner is consuming a DINT, in the Input Size field, enter two times the number of DINTs you need to read from the produced tag. For example, if the produced tag contains 10 DINTs, enter 20 for the Input size; the input size must be an even number. If the scanner is consuming REALs, in the Input Size field, enter two times the number of REALs you need to read from the produced tag. For example, if the produced tag contains 10 REALs, enter 20 for the Input size; the input size must be an even number. 7. Save the file. This will schedule the network.
5-18
The following example shows how to re-construct a REAL (floating point value) in the PLC-5C controller Re-construct a floating point value. This example takes two consumed integers that were originally a produced REAL, reverses the order of the integers and assembles them into a floating point value equal to the original REAL. The two MOV instructions reverse the order of the integers and move them to a new location. Because the destination of the COP instruction is a floating-point address, it takes two consecutive integers, for a total of 32 bits, and converts them to a single floating-point value. The length of a COP instruction is always multiplied by the size of the destination data type, so one in this example means one times the size of REAL, for example 32 bits. COP uses as many consecutive elements from the source file as necessary to satisfy this.
EXAMPLE
Consumed Integer Value A Stored Data Low 16 Bits of the Floating Point Word
Consumed Integer Value B Stored Data High 16 Bits of the Floating Point Word
Chapter
Peer-to-Peer Messaging
This chapter describes how to use MSG instructions to send data to and receive data from other modules on a ControlNet network.
For This Information Set Up the Hardware Guidelines for MSG Instructions Determine Connections for Messages Enter Message Logic Configure a Message Instruction Access Logix Data from a PLC-5 or SLC Processor Stagger the Messages Route PLC-5 Messages Between ControlNet Networks See Page 6-2 6-4 6-5 6-6 6-7 6-14 6-16 6-16
1788-CNx cards
is sent when a specific condition occurs in your application is sent at a slower rate than required by produced and consumed tags is sent to devices that only communicate with unscheduled data
6-2
Peer-to-Peer Messaging
In this example, the controller in the local chassis sends a message (using a MSG instruction) to another module (which can be a controller) on the ControlNet network.
Data
Remote Chassis
ControlNet
Programming Terminal
43611
The Logix5000 controller in the local chassis can be any of the following, with its ControlNet communication module: 1756 ControlLogix controller with a 1756-CN2 or 1756-CN2R communication module in the chassis 1756 ControlLogix controller with a 1756-CNB or 1756-CNBR communication module in the chassis 1769-L32C or 1769-L35CR CompactLogix controller 1789 SoftLogix controller with a 1784-PCIC, 1784-PCICS or 1784-PKTCS communication card 1794 FlexLogix controller with a 1788-CNx ControlNet communication card PowerFlex 700S with DriveLogix controller and a 1788-CNx ControlNet communication card
Peer-to-Peer Messaging
6-3
The destination for the message can be any of the following: PLCs, SLC or Logix5000 controllers on ControlNet or other networks I/O modules, such as ControlLogix analog module configuration data on ControlNet or other networks
IMPORTANT
The 1769-L32C and 1769-L35CR controllers can produce and consume tags over ControlNet to other Logix5000 controllers. However, Compact I/O that is local to the 1769-L32C and 1769-L35CR controller is not accessible to other Logix5000 controllers.
1771 block transfer modules Make sure that: the ControlNet communication modules are connected to a ControlNet network. all wiring and cabling is properly connected. the communication driver (such as, AB-PCICS-1) is configured for the programming workstation.
6-4
Peer-to-Peer Messaging
This table describes guidelines to use when working with message instructions.
Table 6.1 Guidelines for MSG Instructions Details Each MSG instruction requires its own control tag. This tag contains control elements for messages, for example: DN and EN, error codes and information to execute the message such as destination path and number of words to transfer. Data type = MESSAGE Scope = controller The tag cannot be part of an array or a user-defined data type.
2. Keep the source and/or destination data A MSG instruction can access only tags that are in the Controller Tags folder (controller at the controller scope. scope). 3. If your MSG is to a module that uses 16-bit integers, use a buffer of INTs in the MSG and DINTs throughout the project. If your message is to a module that uses 16-bit integers, such as a PLC-5 or SLC 500 controller, and it transfers integers (not REALs), use a buffer of INTs in the message and DINTs throughout the project. This increases the efficiency of your project because Logix5000 controllers execute more efficiently and use less memory when working with 32-bit integers (DINTs). 4. If you want to enable more than 16 MSGs at one time, use some type of management strategy. If you enable more than 16 MSGs at one time, some MSG instructions may experience delays in entering the queue. To guarantee the execution of each message, use one of these options: Enable each message in sequence. Enable the messages in smaller groups. Program a message to communicate with multiple modules. Program logic to coordinate the execution of messages. 5. Cache the connected MSGs that execute most frequently. Cache the connection for those MSG instructions that execute most frequently, up to the maximum number permissible for your controller revision. This optimizes execution time because the controller does not have to open a connection each time the message executes. 6. Keep the number of unconnected and uncached MSGs less than the number of unconnected buffers. The controller can have 10 - 40 unconnected outgoing buffers. The default number is 10. If all the unconnected buffers are in use when an instruction leaves the message queue, the instruction errors and does not transfer the data. You can increase the number of unconnected buffers to a maximum of 40.
For more information on programming MSG instructions, refer to the Logix5000 Controller General Instructions Reference Manual, publication 1756-RM003. The individual system user manuals for Logix5000 controllers also provide MSG examples unique to specific controller platforms.
Peer-to-Peer Messaging
6-5
Messages transfer data to other modules, such as other controllers, I/O modules or operator interfaces. Each message uses one connection, regardless of how many modules are in the message path. To conserve connections, you can configure one message to read from or write to multiple modules. Also, you configure multiple messages for the same path and use only 1 connection if only 1 message is active at a time; however, this requires that you write your ladder logic correctly to make sure only 1 message is active at any time. These connected messages can leave the connection open (cache) or close the connection when the message is done transmitting. The following table shows which messages use a connection and whether or not you can cache the connection:
Table 6.2 Message Connections and Communication Methods This Type of Message CIP data table read or write PLC2, PLC3, PLC5, or SLC (all types) Using this Communication Method CIP CIP CIP with Source ID DH+ CIP generic block-transfer read or write
(1)
CIP na
You can connect CIP generic messages, but for most applications we recommend you leave CIP generic messages unconnected.
6-6
Peer-to-Peer Messaging
To send or receive data from a ControlNet module via a message, you must program a MSG instruction in the local controllers logic. If the target module is configured in the I/O Configuration folder of the controller, you can browse to select the module. Otherwise, you can manually enter the message path in the MSG instruction.
Add the ControlNet Modules and Remote Devices to the Local Controllers I/O Configuration
Use Browse to select the target device of a MSG instruction and add that remote device to the I/O Configuration folder of the local controller. Within the I/O Configuration folder, you organize the local and remote devices into a hierarchy (tree/branch, parent/child).
For a Typical Local or Remote MSG Structure
Local Communication Module Remote Communication Module
Local Controller
Remote Controller
1. Add the local communication module for the local controller. Remember, the 1769-L35CR does not require that you add a local communication module. 2. Add the remote communication module for the remote controller. The communication format for the remote module should be None. 3. Add the remote controller. If the remote controller is added, you can browse to it as a destination when you configure the message instruction.
For more information on how to add ControlNet modules and remote devices to the local controllers I/O configuration, see the chapter Controlling I/O.
Peer-to-Peer Messaging
6-7
Enter a Message
Use relay ladder logic to enter a MSG instruction. Click MSG instruction. Enter a MSG instruction If user_bit and count_messages.EN = 0 (MSG instruction is not already enabled), then execute a MSG instruction that sends data to another controller. to configure the
EXAMPLE
TIP
We recommend an XIO of the MSG control block tag.en, for example: the count_messages.EN portion of the rung above, as an in series precondition for all message instructions Do not manipulate the control bits of a message instruction.
6-8
Peer-to-Peer Messaging
A. Choose a Message Type. B. Depending on the Message Type, you have additional parameters to configure. For more information on how to configure the various Message types, see the tables Message Type to Configure a MSG to Logix5000 Controller, Message Type to Configure a MSG to an SLC 500 Processor, and Message Type to Configure a MSG to a PLC-5 Processor.
The message instructions destination determines what specific information is used on the Configuration tab.
Table 6.4 Select a Message Type Table To Select a Message Type to Configure a MSG to Logix5000 Controller Message Type to Configure a MSG to an SLC 500 Processor Message Type to Configure a MSG to a PLC-5 Processor See Table Message Type to Configure a MSG to Logix5000 Controller Message Type to Configure a MSG to an SLC 500 Processor Message Type to Configure a MSG to a PLC-5 Processor
Peer-to-Peer Messaging
6-9
Table 6.5 Message Type to Configure a MSG to Logix5000 Controller If You Want To write (send) the data For This Item Message Type Source Tag Number of Elements Destination Element Type or Select CIP Data Table Write first element of the tag (controller-scoped) in this controller that contains the data number of elements to transfer first element of the tag for the data in the other controller
6-10
Peer-to-Peer Messaging
A. If you added the module for which the message instruction is sent to the I/O configuration tree, you can use the Browse button to choose the path. If you havent added the module, you can type the path in manually, as described below. B. Select a Communication Method.
4. Click OK. A manually entered path starts with the controllers connection to the backplane and follows a path as shown in the example below:
Peer-to-Peer Messaging
6-11
EXAMPLE
Communication path from a Logix5000 controller to a PLC5 controller over a ControlNet network
ControlNet Network Node Address = 7 5 5 5 0 C N 2 Node Address = 1
Message PLC5-C
Path = 1, 1, 2, 1
Where 1 1 2 1 Indicates connection to the backplane in local chassis slot number of 1756-CN2 module in local chassis connection to port 2 of the 1756-CN2 module (get on ControlNet) node address of remote PLC5
6-12
Peer-to-Peer Messaging
If the message is to a PLC-5 or SLC 500 processor and it reads or writes integers (not REALs), use a buffer of INTs in the message. Logix5000 controllers execute more efficiently and use less memory when working with 32-bit integers (DINTs). PLC-5 and SLC 500 processors require 16-bit integers. Use an INT buffer in the message and move the data to or from DINTs as needed. Use the DINTs in the rest of the program; this can decrease the program scan.
IMPORTANT
Logix5000 controllers can only send messages to SLC 500 processors over ControlNet if the SLC processor uses a KFC ControlNet communication card. However, an SLC cannot send messages to Logix5000 controllers over ControlNet at all.
The figure Configure the Message shows how to configure the message above.
Peer-to-Peer Messaging
6-13
G. Type the node number of the destination 1756-CN2 module. H. Type the backplane slot number of the Logix5000 controller. I. Select No for RSLinx Destination.
6-14
Peer-to-Peer Messaging
Map Tags
A Logix5000 controller stores tag names on the controller so that other devices can read or write data without having to know physical memory locations. Many products only understand PLC/SLC data tables formatting, so the Logix5000 controller offers a PLC/SLC mapping function that lets you map Logix tag names to memory locations.
IMPORTANT
The mapping function is particularly useful if your Logix5000 controller is communicating with a PLC-5C Series C/Revision L, Series D/Revision B, Series E/Revision A or earlier.
You have to map only the file numbers that will be referenced by READ/WRITE messages requested from other controllers; the other file numbers do not need to be mapped. For example, if another controller will send a READ message only to N7, you need to map that file. The mapping table is loaded into the controller and is used whenever a logical address accesses data. You can only access controller-scoped tags (global data). For each file that is referenced in a PLC-5 command, make a map entry: Type the PLC file number of the logical address. Type or select the Logix5000 controller-scoped (global) tag that supplies or receives data for the file number. (You can map multiple files to the same tag.) For PLC-2 commands, specify the tag that supplies or receives the data.
Peer-to-Peer Messaging
6-15
Follow these steps to map tags: 1. If the RSLogix 5000 project is online, go offline. You can only map tags when the project is offline. 2. Access the PLC/SLC Mapping screen.
A. Click Logic. B. Click Map PLC/SLC Messages.
A. Type the File Number. B. Type the corresponding Tag Name from the RSLogix 5000 project.
When mapping tags: Do not use file numbers 0, 1, and 2. These files are reserved for Output, Input, and Status files in a PLC-5 processor. Use PLC-5 mapping only for tag arrays of data type INT, DINT, or REAL. Attempting to map elements of system structures may produce undesirable effects. Use the PLC file identifier of N or B when accessing elements in an INT tag array.
6-16
Peer-to-Peer Messaging
As you add messages to your project, you may have to coordinate the execution of the messages. To avoid errors and assure that each message is processed, follow these rules:
Rule 1 Rule 2 Enable no more than 16 messages at one time (including block transfers). Enable no more than 10 of the following types of messages at one time: CIP data table reads or writes that are not cached CIP generic PLC-2, PLC-3, PLC-5, or SLC (all types) block transfer reads or writes that are not cached
If the number of messages in your application exceeds rules 1 and 2, then stagger the execution of your messages. Here are some options: Send each message in sequence. Send the messages in groups that are within the limits of rules 1 and 2. Program a message to communicate with multiple devices.
You can use ControlLogix communication modules to route a message between PLC-5 controllers that are on different networks, such as a bridged message. The following example depicts a ControlLogix chassis with two 1756-CN2 modules that route a message from one ControlNet network to a different ControlNet network. EXAMPLE Message from a PLC-5C on a ControlNet network to a PLC-5C on a different ControlNet network
C C N N 2 2
ControlNet Network A
Node 3
Node 2 P L C 5 C P L C 5 C
Node 1
Message
Peer-to-Peer Messaging
6-17
This section uses RSLogix 5 software, revision 3.x or greater and PLC-5C Series C/Revision M, Series D/Revision C, Series E/Revision B, Series F/Revision A or greater
1. Open the RSLogix 5 project for the PLC-5 controller that sends the message. 2. Display the set-up screen for the message.
6-18
Peer-to-Peer Messaging
5. Select the ControlLogix backplane row. 6. Press Insert to add a hop. 7. Configure the new hop.
A. Select 1756-CN2 or 1756-CNB. B. Type the ControlNet node number of the controller that receives the message.
Chapter
This chapter describes how a controller uses a ControlNet communication module to communicate with PanelView and RSView software products over a ControlNet network.
For This Information Determine Connections to PanelView Terminals Add a PanelView Terminal Organize Controller Data for a PanelView Terminal Determine Connections to RSView Applications See Page 7-2 7-3 7-6 7-7
In this example, the controller in the local chassis shares data with an HMI application on the ControlNet network. This application could be running any of the following: PanelView terminal PanelView Plus terminal workstation running an RSView 32 software workstation running an RSView Enterprise application, such as RSView Machine Edition software or RSView Supervisory Edition software
Data Local Chassis Logix5000 controller with ControlNet Communication Module HMI Terminal
7-2
The Logix5000 controller in the local chassis can be any of the following, with their ControlNet communication modules: 1756 ControlLogix controller with a 1756-CN2 or 1756-CN2R communication module in the chassis 1756 ControlLogix controller with a 1756-CNB or 1756-CNBR communication module in the chassis 1769-L32C or 1769-L35CR CompactLogix controller 1789 SoftLogix controller with a 1784-PCIC, 1784-PCICS or 1784-PKTCS communication card 1794 FlexLogix controller with a 1788-CNx ControlNet communication card PowerFlex 700S with DriveLogix controller and a 1788-CNx ControlNet communication card Make sure that: the ControlNet communication modules are connected to a scheduled ControlNet network. all wiring and cabling is properly connected.
How you establish communication between a PanelView or PanelView Plus terminal and a Logix5000 controller over ControlNet depends on how you want to use controller connections.
Terminal Type Type of Communication Scheduled (always connected) Unscheduled connected Unscheduled unconnected PanelView Standard PanelView Plus Supported Not supported Supported Supported in version 3.2 and greater Supported Not supported
A Logix controller supports up to 40 outgoing and 3 incoming unconnected buffers. This limited number of incoming unconnected buffers limits how many PanelView Standard terminals can request data from a controller.
7-3
We recommend the following when you use PanelView terminals with Logix5000 controllers over ControlNet: PanelView Standard terminals A maximum of 4 PanelView Standard terminals can request data from a Logix5000 controller. PanelView Plus terminals Because these terminals use unscheduled connections, the number of PanelView Plus terminals that can request data from a Logix5000 controller is dependent on the number of available unconnected buffers in the Logix5000 controller. A typical PanelView Plus application uses 5 unconnected buffers in a Logix5000 controller. With 32 unconnected buffers available at any time in a Logix5000 controller, a maximum of 6 PanelView Plus terminals can request data from a Logix5000 controller. Keep in mind, however, that if 6 PanelView Plus terminals are requesting data from a single Logix5000 controller, there are few unconnected buffers remaining for anything else. For scheduled connected communication, you must add the PanelView or PanelView Plus terminal to the I/O configuration tree for the controller project.
Adding a PanelView terminal is similar to adding distributed I/O. You add the local ControlNet communication module and then you add the terminal to that module. 1. If your application is online, go offline. 2. Select a New Module for the I/O Configuration.
7-4
3. Select the local ControlNet communication module type from the Select Module Type pop-up. The example below uses a 1788-CNC card.
The table ControlNet communication Modules Available Locally lists the ControlNet communication modules available locally (in the local chassis, computer or controller) with each Logix5000 controller.
Table 7.1 ControlNet communication Modules Available Locally If You Are Using This Logix5000 Controller CompactLogix ControlLogix FlexLogix SoftLogix You Can Use This ControlNet Communication Module Locally 1769-L32C, 1769-L35CR have a built-in ControlNet port 1756-CN2, 1756-CN2R 1756-CNB, 1756-CNBR 1788-CNC, 1788-CNCR, 1788-CNF, 1788-CNFR 1784-PCIC (unscheduled data only), 1784-PCICS, 1784-PKTCS (unscheduled data only)
For more information on how to configure ControlNet communication modules, see the chapter Configure a ControlNet Module.
Publication CNET-UM001C-EN-P - November 2005
7-5
7-6
Organize data for a PanelView or PanelView Plus terminal based on how the data is used.
For Data That Is Time-critical (scheduled data) PanelView terminals only Do This Use the I/O tags of the terminal. The terminal supports a maximum of 32 input tags and 32 output tags. The tags for this data were created when you added the PanelView terminal to the I/O configuration of the controller. They are similar to the tags of I/O modules. Create arrays to store the data: 1. For each screen, create a BOOL array with enough elements for the bit-level objects on the screen. For example, the BOOL[32] array gives you 32 bits for push buttons, indicators. 2. For each screen, create a DINT array with enough elements for the word-level objects on the screen. For example, the DINT[28] array, gives you 28 values for numeric entry controls, numeric displays.
7-7
To access the scheduled I/O tags of the PanelView terminal, use the following address format:
If The Terminal writes the data reads the data Then Use This Address name_of_terminal:I.Data[x].y name_of_terminal:O.Data[x].y
where:
This Address Variable name_of_terminal x y Is name of the instance in the I/O configuration of the controller element of the input (I) or output (O) structure. bit number within the input or output element
An RSView application is a self-contained, PC-based HMI that offers both local and distributed client/server systems. This HMI can view updated tag information in a Logix5000 controller via OPC connectivity available in RSLinx software. How you establish communication to an RSView software application depends on how you configure RSLinx software to collect tags from the controller. RSView 32 software uses RSLinx Classic software as a data server; RSView Enterprise software uses RSLinx Enterprise software as a data server. RSLinx Classic software and RSLinx Enterprise software each default to 4 read connections and 1 write connection per configured controller. You can modify your RSLinx Classic configuration as needed such as changing the number of read and write connections. However, the RSLinx Enterprise is not configurable. You can only use a configuration of 4 read connections and 1 write connection.
7-8
Notes:
Chapter
This chapter provides descriptions for status indicators used on the ControlNet communication modules and adapters and how to use those indicators to troubleshoot your application.
For This Information 1756-CN2 and 1756-CN2R ControlNet Communication Modules 1756-CNB and 1756-CNBR ControlNet Communication Modules 1769-L32C and 1769-L35CR CompactLogix Controllers 1784-PCIC, 1784-PCICS and 1784-PKTCS ControlNet PCI Cards 1788-CNC, 1788-CNCR, 1788-CNF and 1788-CNFR ControlNet Daughtercards 1794-ACN15 and 1794-ACNR15 ControlNet FLEX I/O Adapters 1797-ACNR15 ControlNet FLEX Ex Redundant Media I/O Adapter See Page 8-2 8-6 8-11 8-15 8-17 8-21 8-23
8-2
This figure shows the status indicators used on the 1756-CN2 and 1756-CN2R modules.
Figure 8.1 1756-CN2 and 1756-CN2R Status Indicators
1756-CN2 1756-CN2R
1. Check the power supply. 2. Check the cable connectors. 3. Make sure the module is firmly seated in the chassis. 4. If the indicator remains off, replace the module.
8-3
It Means
Modules network address is set to 00, an invalid ControlNet address. See footnote at end of table.
1. Optional Turn chassis power supply off. 2. Remove the module from the chassis. 3. Set the network address switches to a unique address (01 to 99) 4. Install the module in the chassis. 5. If off, turn chassis power supply on.
BPA# ERR
Module detected a different slot address from that latched when you cycled power. Excessive noise on the backplane causes this error. Too many CRC errors being generated by the multicast backplane receiver, so the backplane multicast receivers have been shut off. Hardware fault within the module.
BPRX ERR
The modules network address is the same as another modules on the link.
1. Turn chassis power supply off. (Optional) 2. Remove the module from the chassis. 3. Set the network address switches to a unique address (01-99). 4. Install the module in the chassis. 5. If off, turn chassis power supply on.
RACK ERR Flashing Red BOOT ROM UPDT SNGL KPR! Green OK INIT BW >MAX
Cannot read backplane EEPROM, or rack/slot address incorrect Module has invalid firmware. Flash update is in progress. Module detected that it has been connected to a Cnet 1.0 or 1.25 (single-keeper) network. Normal operation Module is initializing. Module is receiving too much network traffic and connections are timing out. The network bandwidth has been exceeded.
Replace the chassis. Update module firmware with ControlFlash Update Utility. None required. Update the firmware of module at node address 01 and reschedule the network. There is at least one connection to or through the module. No action required. No action required. None required (temporary condition). If this happens frequently, add another bridge module and split the traffic between them.
8-4
If the OK Indicator Is
It Means
None required, but we recommend that you either return switches to their original settings or replace the module, since this could indicate a latent hardware problem. No connections to or through the module. No action required Recheck configuration. Re-check your network cabling and make sure another node on the network is active (online).
Flashing Green
Normal operation. ControlNet configuration error. Network cabling error or no other active nodes on network.
(1)
If switches are set to 00 the display scrolls FAULT: ADDRESS SWITCHES = 00, ILLEGAL
When you connect the module to a ControlNet network using only the NAP, the LEDs are meaningless.
Steady - indicator is on continuously in the defined state. Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together). The two indicators are always in opposite states, out of phase. Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other). If both indicators flash, they must flash together, in phase.
8-5
This table describes the 1756-CN2 and 1756-CN2R network channel status indicators.
Table 8.2 1756-CN2 and 1756-CN2R Network Channel Status Indicators If Both Channel Status Indicators Are Off Steady red It Means No power Faulted module Take This Action Apply power. 1. Cycle power to the module. 2. If fault persists, contact your Rockwell Automation representative or distributor. Alternating red/green Alternating red/off If Either Channel Status Indicators Are Off Steady green Flashing green/off Self-test Incorrect node configuration It Means Channel disabled Normal operation Temporary network errors None Check network address and other ControlNet configuration parameters. Take This Action Program network for redundant media, if necessary. None None unit will self-correct or 1. Check media for broken cables, loose connectors, missing terminators. 2. If condition persists, refer to the ControlNet Coax Media Planning and Installation Manual, publication and CNET-IN002. Node is not configured to go online Flashing red/off Media fault Make sure the network keeper is present and working and the selected address is less or equal to the UMAX(1). 1. Check media for broken cables, loose connectors, missing terminators. 2. If condition persists, refer to the ControlNet Coax Media Planning and Installation Manual, publication and CNET-IN002 No other nodes present on network Flashing red/green Incorrect node address Add other nodes to the network. 1. Change the node address so that it is less than or equal to UMAX. 2. Stop and restart the PCIC/PCICS driver in RSLinx software. Incorrect network configuration
(1)
Reconfigure the ControlNet network so that UMAX is greater than or equal to the node address.
UMAX is the highest node address on a ControlNet network that can transmit data.
8-6
This figure shows the status indicators used on the 1756-CNB and 1756-CNBR modules.
Figure 8.2 1756-CNB and 1756-CNBR Status indicators
1756-CNB 1756-CNBR
1. Check the power supply. 2. Check the cable connectors. 3. Make sure the module is firmly seated in the chassis. 4. If the indicator remains off, replace the module.
8-7
It Means
Modules network address is set to 00, an invalid ControlNet address, or 99, an invalid ControlNet address if you are using redundant control. See footnote at end of table.
1. Optional Turn chassis power supply off. 2. Remove the module from the chassis. 3. Set the network address switches to a unique address (01-99, or 01-98 if redundant control) 4. Install the module in the chassis. 5. If off, turn chassis power supply on.
BPA# ERR
Module detected a different slot address from that latched in at power-up. Excessive noise on the backplane causes this error. Too many CRC errors being generated by the multicast backplane receiver, so the backplane multicast receivers have been shut off. Hardware fault within the module.
BPRX ERR
DUPL NODE
For a redundant system this may be a temporary For redundant systems only. wait 10 seconds; if condition during chassis switchover. Otherwise, the condition persists, do the following steps: the modules network address is the same as 1. Turn chassis power supply off. another modules on the link. (Optional) 2. Remove the module from the chassis. 3. Set the network address switches to a unique address (01-99). 4. Install the module in the chassis. 5. If off, turn chassis power supply on.
Cannot read backplane EEPROM, or rack/slot address incorrect CNB commanded to stop functioning by the redundancy module. This occurs when a non-redundancy compliant CNB is placed into a redundant secondary chassis. CNB waiting for the redundancy module to complete power-up.
Replace the chassis. Remove non-redundancy compliant CNB from redundant secondary chassis and replace with redundancy compliant CNB. None required.
WAIT RM
8-8
With This Module Status Display BOOT ROM UPDT SNGL KPR!
It Means
Module detected that it has been connected to a Cnet 1.0 or 1.25 (single-keeper) network. Normal operation
Update the firmware of module at node address 01 and reschedule the network. None required. In this case, at least one connection has been made to or through the module. None required. None required (temporary condition). If this happens frequently, add another module and split the traffic between them. None required. Check corresponding slot of primary chassis for type and revision of module. Check the type and revision of the module. Redundant system status. No action required.
Steady green
OK
INIT BW >MAX
Module is initializing. Module is receiving too much network traffic and connections are timing out. The network bandwidth has been exceeded. Secondary CNB is compatible with its partner. Secondary CNB is disqualified with no partner. CNB is primary with a disqualified secondary partner. CNB is primary with a qualifying secondary partner. CNB is primary with a qualified secondary partner. CNB is primary with no secondary partner. Secondary CNB is qualifying. Secondary CNB is qualified. Node address switch changed after power-up.
Check corresponding slot of secondary chassis for correct module. Redundant system status. No action required. None required, but we recommend that you either return switches to their original settings or replace the module, since this could indicate a latent hardware problem. Recheck configuration. Re-check your network cabling and make sure another node on the network is active (on line). None required. In this case, no connections have been made to or through the module.
Flashing green
ControlNet configuration error. Network cabling error or no other active nodes on network. Normal operation
8-9
With This Module Status Display SO_1 SO_2 SO_3 SN_1 SN_2 SN_3 ?Cpt !Cpt
It Means
Old primary switchover phase 1 in progress. Old primary switchover phase 2 in progress. Old primary switchover phase 3 in progress. New primary switchover phase 1 in progress. New primary switchover phase 2 in progress. New primary switchover phase 3 in progress. CNB has not determined if it is compatible. CNB has determined that it is not compatible.
If the display shows any message for more than three seconds, then the CNB module failed during transition from one redundancy phase to another. Replace one or both redundancy modules.
(1)
If switches are set to 00 the display scrolls FAULT: ADDRESS SWITCHES = 00, ILLEGAL If switches are set to 99 in a redundant chassis, the display scrolls: FAULT: ADDRESS SWITCHES = 99, ILLEGAL IN REDUNDANT SYSTEM
When you connect the module to a ControlNet network using only the NAP, the LEDs are meaningless.
Steady - indicator is on continuously in the defined state. Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together). The two indicators are always in opposite states, out of phase. Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other). If both indicators flash, they must flash together, in phase.
8-10
This table describes the 1756-CNB and 1756-CNBR network channel status indicators.
Table 8.4 .1756-CNB and 1756-CNBR Network Channel Status Indicators If Both Channel Status Indicators Are Off Steady red It Means No power Faulted module Take This Action Apply power. 1. Cycle power to the module. 2. If fault persists, contact your Rockwell Automation representative or distributor. Alternating red/green Alternating red/off Self-test One of the following: incorrect node configuration duplicate ControlNet node address If either channel status indicators are: Off Steady green Flashing green/off It means: Channel disabled Normal operation Temporary network errors Take this action: Program network for redundant media, if necessary. None 1. Check media for broken cables, loose connectors, missing terminators. 2. If condition persists, refer to the ControlNet Coax Media Planning and Installation Manual, publication and CNET-IN002 Node is not configured to go online Flashing red/off Media fault Make sure the network keeper is present and working and the selected address is less or equal to the UMAX(1). 1. Check media for broken cables, loose connectors, missing terminators. 2. If condition persists, refer to the ControlNet Coax Media Planning and Installation Manual, publication and CNET-IN002 No other nodes present on network Flashing red/green Incorrect node address Add other nodes to the network. 1. Change the node address so that it is less than or equal to UMAX. 2. Stop and restart the PCIC/PCICS driver in RSLinx software. Incorrect network configuration
(1)
None Check the node address and other ControlNet configuration parameters.
Reconfigure the ControlNet network so that UMAX is greater than or equal to the node address.
UMAX is the highest node address on a ControlNet network that can transmit data.
8-11
This figure shows the status indicators used on the 1769-L32C and 1769-L35CR CompactLogix controller.
Figure 8.3 1769-L32C and 1769-L35CR CompactLogix Controller Status Indicators
Network Channel A Status Indicator Network Channel B Status Indicator Module Status Indicator
43870
For information on how to use the module status indicator and the network channel status indicators, see the section Interpret Status Indicators. In addition to ControlNet status indicators, the 1769-L32C and 1769-L35CR controllers have controller, serial and CompactFlash indicators. For more information, the CompactLogix System User Manual, publication 1769-UM011.
8-12
Keep in mind that the Module Status indictor reflects the module state such as self-test, firmware update, or normal operation but no connection established. The network status indicators, A and B, reflect network status. Remember that the host is able to engage in local messaging with the card although it is detached from the network. Therefore, the Module Status LED is flashing green if the host has successfully started the card. Note, however, that until the host removes reset, all LEDs on the daughtercard will remain off. When you view the indicators, always view the Module Status indicator first to determine the state of the daughtercard. This information may help you to interpret the network status indicators. As a general practice, view all status indicators (Module Status and Network Status) together to gain a full understanding of the daughtercards status.
8-13
8-14
Flashing red/off
None Check the cards network address and other ControlNet configuration parameters.
UMAX is the highest node address on a ControlNet network that can transmit data.
8-15
This figure shows the status indicators used on the 1784-PCIC, 1784-PCICS and 1784-PKTCS cards.
Figure 8.4 1784-PCIC, 1784-PCICS and 1784-PKTCS Channel Status indicators
43609
The status indicators on the card give you information about the card and the ControlNet network when you are connected via the BNC connectors.
When you connect the module to a ControlNet network using only the NAP, the LEDs are meaningless.
Steady - indicator is on continuously in the defined state. Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together). The two indicators are always in opposite states, out of phase. Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other). If both indicators flash, they must flash together, in phase. This table describes the 1784-PCIC, -PCICS and -PKTCS network channel status indicators.
8-16
Table 8.7 1784-PCIC, 1784-PCICS and 1784-PKTCS Network Channel Status Indicators If Both Channel Status It Means Indicators Are Off No power 1784-PCIC(S) driver not started Take This Action Apply power. 1. Start RSLinx software.
Steady red
2. Verify that the appropriate driver has been configured properly in RSLinx software. 1784-PKTCS driver is not installed or the card is Install the driver and/or configure the card. not configured Faulted card 1. Check operating system event log for details of fault (if the PCs operating system supports an event log). 2. Cycle power to the PC. 3. Verify that you have firmly inserted the card into a PCI local bus expansion slot and that the expansion slot screw is tightened. 4. If fault persists, contact your Rockwell Automation representative or distributor. Channel disabled Program network for redundant media, if required Faulted card 1. Check operating system event log for details of fault (if the PCs operating system supports an event log). 2. Cycle power to the PC. 3. Verify that you have firmly inserted the card into a PCI local bus expansion slot and that the expansion slot screw is tightened. 4. If fault persists, contact your Rockwell Automation representative or distributor. Self-test None One of the following: Check cards node address and other ControlNet configuration parameters. incorrect node configuration duplicate ControlNet node address Normal operation Channel disabled Temporary network errors None Use RSNetWorx software to configure the ControlNet network for redundant media, if necessary. 1. Check media for broken cables, loose connectors, missing terminators. 2. If condition persists, refer to the ControlNet Coax Media Planning and Installation Manual, publication and CNET-IN002 1. Check media for broken cables, loose connectors, missing terminators. 2. If condition persists, refer to the ControlNet Coax Media Planning and Installation Manual, publication and CNET-IN002. Add other nodes to the network. 1. Change cards node address so that it is less than or equal to UMAX(1). 2. Stop and restart the cards driver in RSLinx software (1784-PCIC and 1784-PCICS only). Reconfigure the ControlNet network so that UMAX is greater than or equal to the cards node address.
Flashing red/off
Media fault
Flashing red/green
UMAX is the highest node address on a ControlNet network that can transmit data.
8-17
This figure shows the status indicators used on the 1788-CNC and 1788-CNCR cards.
Figure 8.5 1788-CNC, 1788-CNCR Status indicators
NAP I/O Status Indicator Module Status Indicator Node Address Switches
1788-CNC
Network Channel Status Indicators (A and B) NAP I/O Status Indicator Module Status Indicator Node Address Switches
1788-CNCR
31044
NAP Channel A connector I/O Status Indicator Module Status Indicator Node Address Switches
1788-CNF
3115
8-18
Keep in mind that the Module Status indictor reflects the module state. For example: self-test, firmware update, and normal operation but no connection established. The network status LEDs, A and B, reflect network status. Remember that the host is able to engage in local messaging with the card although it is detached from the network. Therefore, the Module Status LED is flashing green if the host has successfully started the card. Note, however, that until the host removes reset, all LEDs on the daughtercard will remain off. When you view the indicators, always view the Module Status indicator first to determine the state of the daughtercard. This information may help you to interpret the network status indicators. As a general practice, view all three status indicators (Module Status, I/O Status, and Network Status) together to gain a full understanding of the daughtercards status.
8-19
This table describes the 1788-CNC, 1788-CNCR and 1788-CNF module and I/O status indicators.
Table 8.8 1788-CNC, 1788-CNCR and 1788-CNF Module and I/O Status Indicators If The Module Status (MS) Indicator Is Off It Means Take This Action
Apply power. Make sure that the daughtercard is firmly seated in the slot. 1. Cycle power. 2. If the indicator remains off, replace the daughtercard or the host.
Steady red
Major fault
Flashing red
Minor fault Firmware update in progress Node address switch change The daughtercards node address switches may have been changed since power-up. I module firmware Duplicate node address The daughtercards node address duplicates that of another device.
No action required (firmware update in progress.) No action required (firmware update in progress.) Change the node address switches back to the original setting. The module will continue to operate properly. Update module firmware with ControlFlash Update utility. 1. Remove power. 2. Change the node address to a unique setting. 3. Reapply power.
None Establish connections, if necessary. Wait briefly to see if problem corrects itself. If problem persists, check the host. If the daughtercard cannot communicate with the host, the card may remain in self-test mode.
It Means
Take This Action This LED is on during the LED portion of the self-tests.
8-20
When you connect the module to a ControlNet network using only the NAP, the LEDs are meaningless.
Steady - indicator is on continuously in the defined state. Alternating - the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together). The two indicators are always in opposite states, out of phase. Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other). If both indicators flash, they must flash together, in phase. This table describes the 1788-CNC, 1788-CNCR, 1788-CNF and 1788-CNFR network channel status indicators.
Table 8.9 1788-CNC, 1788-CNCR, 1788-CNF and 1788-CNFR Network Channel Status Indicators If Both Channel Status It Means Indicators Are Off Steady green Flashing green/off Channel disabled Normal operation Temporary network errors Take This Action Program network for redundant media, if necessary. None 1. Check media for broken cables, loose connectors, missing terminators. 2. If condition persists, refer to the ControlNet Fiber Media Planning and Installation Manual, publication CNET-IN001 or the ControlNet Coax Media Planning and Installation Manual, publication CNET-IN002. Node is not configured to go online Flashing red/off Media fault Make sure the network keeper is present and working and the selected address is less or equal to the UMAX(1). 1. Check media for broken cables, loose connectors, missing terminators. 2. If condition persists, refer to the ControlNet Fiber Media Planning and Installation Manual, publication CNET-IN001 or the ControlNet Coax Media Planning and Installation Manual, publication CNET-IN002. No other nodes present on network Flashing red/green If Either Channel Status Indicators Are Off Steady red Incorrect network configuration It Means You should check the MS indicators Faulted card Add other nodes to the network. Reconfigure the ControlNet network so that UMAX is greater than or equal to the cards node address. Take This Action Check the MS indicators. 1. Cycle power. 2. If the fault persists, contact your Rockwell Automation representative or distributor. Alternating red/green Alternating red/off
(1)
None Check the cards network address and other ControlNet configuration parameters.
UMAX is the highest node address on a ControlNet network that can transmit data.
8-21
This figure shows the status indicators used on the 1794-ACN15 and 1794-ACNR15 modules.
Figure 8.6 1794-ACN15 and 1794-ACNR15 Status Indicators
43610
The modules use the following 2 status indicators: Comm - Communication status indicator for each channel; the 1794-ACN15 module has 1 Comm indicator, and the 1794-ANCR15 module has 2 Comm indicators Status - Module status indicator This table describes the 1794-ACN15 and 1794-ACNR15 communication status indicators.
Table 8.10 1794-ACN15 and 1794-ACNR15 Communication Status Indicators If Both Channel Status Indicators Are Off Steady green Flashing green/off It Means Channel disabled Normal operation Temporary network errors Take This Action Program network for redundant media, if necessary. None 1. Check media for broken cables, loose connectors, missing terminators. 2. If condition persists, refer to the ControlNet Coax Media Planning and Installation Manual, publication CNET-IN002. Node is not configured to go online Flashing red/off Media fault Make sure the network keeper is present and working and the selected address is less or equal to the UMAX(1). 1. Check media for broken cables, loose connectors, missing terminators. 2. If condition persists, refer to the ControlNet Coax Media Planning and Installation Manual, publication CNET-IN002. No other nodes present on network Flashing red/green Incorrect network configuration Add other nodes to the network. Reconfigure the ControlNet network so that UMAX is greater than or equal to the modules node address.
8-22
Take This Action Apply power. 1. Cycle power. 2. If the fault persists, contact your Rockwell Automation representative or distributor.
None Check the modules network address and other ControlNet configuration parameters.
UMAX is the highest node address on a ControlNet network that can transmit data.
This table describes the 1794-ACN15 and 1794-ACNR15 module status indicators.
Table 8.11 1794-ACN15 and 1794-ACNR15 Module Status Indicators If The Module Status Indicator Is: Off It Means Module not communicating due to a power supply fault or internal fault. Take This Action 1. Check the power supply. 2. Check the cable connectors. 3. Make sure the module is properly installed on the DIN rail. 4. If the indicator remains off, replace the module. Steady green Flashing green Steady red Connections established No connections established Major fault None Establish connections, if necessary. 1. Cycle power. 2. If the problem persists, replace the daughtercard. Flashing red I/O module removed Wrong I/O module inserted FLASH program update in progress Reinsert the module. Replace the wrong module with the correct module. Wait for the program update to finish.
8-23
This figure shows the status indicators used on the 1797-ACNR module.
Figure 8.7 1797-ACNR15 Status Indicators
The modules use the following 2 status indicators: Comm - Communication status indicator for each channel Status - Module status indicator This table describes the 1797-ACNR15 communication status indicators.
Table 8.12 1797-ACNR15 Communication Status Indicators If Both Channel Status Indicators Are Off Steady green Flashing green/off It Means Channel disabled Normal operation Temporary network errors Take This Action Program network for redundant media, if necessary. None 1. Check media for broken cables, loose connectors, missing terminators. 2. If condition persists, refer to the ControlNet Coax Media Planning and Installation Manual, publication CNET-IN002. Node is not configured to go online Flashing red/off Media fault Make sure the network keeper is present and working and the selected address is less or equal to the UMAX(1). 1. Check media for broken cables, loose connectors, missing terminators. 2. If condition persists, refer to the ControlNet Coax Media Planning and Installation Manual, publication CNET-IN002. No other nodes present on network Flashing red/green Incorrect network configuration Add other nodes to the network. Reconfigure the ControlNet network so that UMAX is greater than or equal to the modules node address.
8-24
Take This Action Apply power. 1. Cycle power. 2. If the fault persists, contact your Rockwell Automation representative or distributor.
None Check the modules network address and other ControlNet configuration parameters.
UMAX is the highest node address on a ControlNet network that can transmit data.
Appendix
ControlNet communication modules use connections to manage communication. A connection is a point-to-point communication mechanism that transfers data between a transmitter and a receiver. ControlNet communication modules use connections that transfer data from a Logix application running on one end-node to another device, such as a Logix application or I/O, running on another end-node.
ControlNet Connections
Connections are allocations of resources that provide faster more reliable communication between modules than unconnected messages. The ControlNet communication modules and adapters support both direct and rack-optimized connections to remote I/O adapters. Connected messaging supports the following example functions: Logix controller message transfer to Logix controller I/O or produced/consumed tag Program upload RSLinx DDE/OPC client PanelView polling of Logix controller
Rack-optimized
A-2
The Logix5000 controller supports 250 connections. But the limit of connections ultimately resides in the communication module you use for the connection. If a message path routes through a communication module or card, the connection related to the message also counts towards the connection limit of the communication module or card.
The controllers built-in ControlNet port effectively supports this many communication connections(1) 0-1 1-2 3-4 6-9 10 - 12 12 - 16 31
For each NUT/RPI combination, the number of connections supported is listed in a range. The lower number is the number of connections we recommend you make to maintain reasonable ControlNet port CPU utilization rates. The higher number is the maximum number of connections possible for that NUT/RPI combination.
Each module supports 31 unscheduled connections. Each module supports 128 unscheduled connections. Each module supports 128 unscheduled and 127 scheduled connections. Each module supports 128 unscheduled connections and 127 scanlist entries for scheduled connections.
A-3
Product 1788-CNx
Connected Messaging Limits Each module supports 32 connections, of which 22 connections can be scheduled connections. With these controllers, the number of end-node connections they effectively support is dependent on the applications NUT and RPI:
If the NUT and the RPI are each 5 ms 10 ms 20 ms 40 ms + The controllers support a maximum of this many connections 3 6 13 22
In the table above, with a NUT and RPI of 40 ms and greater, the ControlNet card supports 22 communications connections. In this case, the remaining 10 connections can be used for unscheduled connections. 1794-ACN15, 1794-ACNR15 and 1797-ANCR Each module supports a maximum 32 end-node connections for messages. With these cards, the number of end-node connections they support is dependent on the applications NUT:
At this NUT 2.0 - 2.99ms 3.0 - 3.99ms 4.0 - 7.99ms 8.0 - 100.0 The cards support this many end-node connections 3 12 20 32
A-4
Notes:
Appendix
ControlNet Overview
This chapter defines some basic ControlNet concepts and how the ControlNet network is used for control.
ControlNet is a real-time control network that provides high-speed transport of both time-critical I/O and interlocking data and messaging data, including upload/download of programming and configuration data on a single physical media link. The ControlNet networks highly efficient data transfer capability significantly enhances I/O performance and peer-to-peer communication in any system or application where it is used. ControlNet is highly deterministic and repeatable, and remains unaffected as devices are connected or disconnected from the network. This ensures dependable, synchronized, and coordinated real-time performance. The ControlNet network is most often used in these types of configurations: as the default network for the ControlLogix platform. as a substitute/replacement for the Remote I/O (RIO) network, because ControlNet handles large numbers of I/O points well. as a backbone to multiple distributed DeviceNet networks. as a peer interlocking network. instead of Data Highway Plus.
B-2
ControlNet Overview
ControlNet communication modules use a message-based protocol that implements a relative path to send a message from the producing module in a system to the consuming modules. This protocol also allows you to communicate between devices on ControlNet and DeviceNet or EtherNet/IP without writing additional application code. With unscheduled data the device where a message originates such as a Logix5000 controller, contains the path information that steers the message along the proper route to reach its consumers. A full explanation of unscheduled and scheduled data is available on page B-4. Since the producing module holds this information, other modules along the path simply pass this information; they do not need to store it. This has two significant benefits: You do not need to configure routing tables in the bridging module, which greatly simplifies maintenance and module replacement. You maintain full control over the route taken by each message, which enables you to select alternative paths for the same end module. Scheduled data in Logix-based systems use the producer/consumer networking model instead of a source/destination (master/slave) model. The producer/consumer model reduces network traffic and increases speed of transmission. In traditional I/O systems, controllers poll input modules to obtain their input status. In a Logix system digital input modules are not polled by a controller. Instead, they produce (multicast) their data either upon a change of state (COS) or periodically. The frequency of update depends upon the options chosen during configuration and where on the network the input module resides. The input module, therefore, is a producer of input data and the controller is a consumer of the data. The controller can also produce data for other controllers to consume. The produced and consumed data is accessible by multiple controllers over the Logix backplane and over the ControlNet network. This data exchange conforms to the producer/consumer model.
ControlNet Overview
B-3
A ControlNet links most important function is to transport time-critical control information, such as I/O data and control interlocking. Other information (non-time-critical messages such as program uploads and downloads) is also transported but does not interfere with time-critical messages because of ControlNets transmission of scheduled and unscheduled data. On a ControlNet link, information is transferred between nodes by establishing connections. Each message sent by a producer contains a Connection ID (CID). Nodes that have been configured to recognize the CID consume the message, therefore becoming consumers. Media access to the network is controlled by a time-slice access algorithm, Concurrent Time Domain Multiple Access (CTDMA), which regulates a nodes opportunity to transmit in each network update interval (NUI). You configure how often the NUI repeats by selecting a network update time (NUT) in milliseconds.
B-4
ControlNet Overview
Network Maintenance
ControlNet Overview
B-5
how often to produce the data for that module. For example, if you specify an RPI of 50ms, every 50ms the I/O module sends its data to the controller and/or the controller sends its data to the I/O module. Set the RPI only as fast as needed by the application. The RPI also determines the number of packets per second that the module will handle on a connection. Each module has a limit of how many packets it can handle per second. If you exceed this limit, the module cannot open any more connections. Keep in mind that the faster your RPI, the more network bandwidth used. So only set the RPI as fast as necessary to avoid draining the network bandwidth unnecessarily. For example, if your application uses a thermocouple module that has data change every 100ms, do not set the RPI for that node at 5ms because the network bandwidth is used for data transmissions that are mostly old data.
IMPORTANT
You cannot set the RPI to a rate faster than the NUT. The network cannot send data at a rate that is faster than NUT.
When you run RSNetWorx for ControlNet software an Actual Packet Interval (API) is calculated. The API is equal to or faster than the RPI.
B-6
ControlNet Overview
Table B.2 NUT Example Data Rates With this NUT 5ms And this multiple 1 2 4 8 16 32 64 128 The Module Can Send Data at this Rate 5ms 10ms 20ms 40ms 80ms 160ms 320ms 640ms
In our example, if you specify an RPI of 25ms, then the network produces an API of 20ms, which is the next fastest rate at which the module can send data. The module places the data on the network at every fourth network update interval to produce the 20ms API. Similarly, if you specify an RPI of 150ms, the network produces an API of 80ms.
RSNetWorx software must be run whenever a scheduled connection is added to, removed from, or changed in your system.
ControlNet Overview
B-7
B-8
ControlNet Overview
On a multi-keeper network, any keeper capable module can keep the network at any legal node address (01 to 99). The multi-keeper capable node with the lowest node address becomes the active keeper provided it is valid. It has been configured by RSNetWorx software and that configuration is the same as that of the first keeper that became active after the network was formed or reconfigured by RSNetWorx software. If the active keeper is taken off the network, a valid back-up keeper can take over for it and continue to act as keeper. As long as at least one valid multi-keeper device is present on the network, new scheduled connections can be established.
ControlNet Overview
B-9
To see a list of valid keeper devices on your network, do the following steps: 1. Go online in RSNetWorx for ControlNet software. 2. Access the Keeper Status for the network.
A. Click Network. B. Click Keeper Status.
The Keeper Status screen appears with a list of all nodes on the network and indications of whether the nodes are: Keeper Capable Nodes Active Keeper Valid Keepers The screen below shows an example of the Keeper Status screen.
B-10
ControlNet Overview
Default Parameters
When a ControlNet network is powered-up for the first time, it comes up with a default set of ControlNet parameters capable of sending only unscheduled data. The default set of network parameters in all ControlNet devices, is: Network Update Time (NUT) = 100ms Scheduled Maximum Node Address (SMAX) = 0 The SMAX is the highest network address of a node that can use the scheduled service. Unscheduled Maximum Node Address (UMAX) = 99 The UMAX is the highest network address of a node that can communicate on the ControlNet network. The UMAX must be set equal to or higher than the SMAX. Assumed maximum cable lengths and maximum number of repeaters With this default ControlNet network, you can have unscheduled communication between the various devices on the network by using such software packages as RSNetWorx for ControlNet, RSLogix5000 and RSLinx.
IMPORTANT
The ControlNet network should be configured using RSNetWorx for ControlNet software to improve performance. At a minimum, we recommend that the Unscheduled Maximum Node Address (UMAX) be set equal to the highest node address on the network. Leaving this parameter at the default value of 99 will waste bandwidth and reduce system performance. We also recommend setting the Scheduled Maximum Node Address (SMAX) to a value 3 or 4 above the highest scheduled node address to allow you to expand the network in the future.
ControlNet Overview
B-11
When planning a ControlNet network, you should consider the following: topology number of nodes distances connections
Topology
ControlNet supports a variety of topologies, including trunkline/dropline, star, tree, and ring redundancy. In its simplest form, ControlNet is a trunkline, to which you connect nodes with a tap and a 1-meter dropline, as shown in the figure Example ControlNet System Trunkline/Dropline Topology. Repeaters are required to create other topologies, as shown in the figures Example ControlNet System Star Topology (star) and Example ControlNet System Ring Topology (ring). TIP Coax repeaters are typically used in trunkline and star topologies. Refer to publication CNET-IN002, ControlNet Coax Media Planning and Installation Guide, for more specific information on coax topologies you can create. Using fiber media allows you to configure your network in trunkline and star topologies and is the only method of implementing ring redundancy. You can only use the 1786-RPFRL and 1786-RPFRXL repeaters in a ring. Refer to publication CNET-IN001, ControlNet Fiber Media Planning and Installation Guide, for more information on fiber media and topologies.
B-12
ControlNet Overview
Node Node
Node Node
43620
Node
Node
Node
Node
Node
Node
43621
ControlNet Overview
B-13
Node ControlNet Repeater Adapter and Fiber Ring Module tap with 1-meter Dropline
Node
Node
Node
Node
43622
B-14
ControlNet Overview
Number of Nodes
Each ControlNet network supports up to 99 nodes. Logix5000 controllers support multiple ControlNet networks, giving you the flexibility to add more nodes to your ControlNet network, or to boost performance.
Distances
In a ControlNet network, the maximum distance depends on the number of nodes on a segment; a segment is a section of trunk between 2 terminators. Use repeaters to add more segments or gain more distance. Use this figure to determine whether repeaters are required.
Maximum Allowable Segment Length = 1000m (3280ft) - 16.3m (53.4ft) X [Number of Taps - 2]
1000 (3280) Segment Length m (ft) Add a Repeater 750 (2460) 500 (1640) 250 (820) No Repeater Required
16
32
48
30014-M
Appendix
After reading this appendix, consult engineering drawings of your facility for specific information concerning the best location to install the ControlNet network.
IMPORTANT
The ControlNet cable system is a ground-isolated network. Proper selection of cable, connectors, accessories, and installation techniques are necessary to make sure it is not accidentally grounded. If conditions occur where other means are needed to ensure no metal to ground connections, items like blue tape can be used. Any accessories should have a dielectric rating of greater than 500 V.
C-2
The design of a ControlNet media system is a process of measurement and judgement. The objective is to select the ControlNet media that will serve as the foundation for the network operations. When designing a network for an application, you must address the following deciding factors to assure a steady control foundation: Application Requirements Media Needs ControlNet Media Components
Application Requirements
Application requirements are environmental factors that, if not considered in the network design, could limit or prevent network operation. Application requirements are important in making the following decisions: What type of cable is needed? What type of cable connectors are needed? The following application requirements should be factored into a network design as well: High ambient temperature EMF noise Flooding Hazardous environments
Media Needs
Media needs are the physical requirements of a network and are measured against the limitations of the media used. If the media needs are addressed without regarding the media limitations, then this oversight could result in a weak or unusable signal that could halt network operation. Media needs are important in making the following decisions: How much cable is needed? How is the programming device connected? The following media needs should be factored into a network design: Network length from first device to last device Ability to configure the network from any device connected to the network
C-3
Tap
Node
C-4
The number of taps you need depends on the number of devices you want to connect to the network. You need a tap for each node and fiber hub on a segment. If you plan to add nodes at a later date, you should consider ordering and installing the cable and connectors for these additional nodes when you install the initial network. This will minimize disruption to the network during operation.
IMPORTANT
A disconnected drop cable can cause noise on the network. Because of this, we recommend having only one unconnected drop cable per segment for maintenance purposes. Be sure to keep the dust cap on any unconnected drop cable. If your cable system requires more than one unconnected drop cable, unused drop cables should be terminated with a tap terminator, such as the 1786-TCAP.
TIP
If you are planning future installation of additional nodes, do not install the tap. Instead, install a BNC bullet connector. For more information on BNC connectors, see the section Determine What Type of Connectors You Need.
BNC Connector Kits Tap (1786-TPR, -TPS, -TPYR, -TPYS) (1797-TPR, -TPS, -TPYR, -TPYS
Dust Cap
Screws
For noise suppression, ferrite beads are molded on the drop cable.
41329
C-5
41330
1786-TCT2BD1
1786-TPS 1797-TPS
1786-TPYS 1797-TPYS
1786-TPR 1797-TPR
1786-TPYR 1797-TPYR
Programming devices in non-hazardous areas may be connected to the ControlNet cable system through a 1784-PCIC, 1784-PCICS or 1784-PCC communication card. The 1784-PCIC, 1784-PCICS and 1784-PKTCS cards connect to the network using a ControlNet tap.
Figure C.3 1784-PCICS Communication Card on Coax Media
Using a 1784-PCICS Communication Card on Coax Media Programming Terminal 1784-PCICS Node
41331
C-6
There are several types of RG-6 quad shield cable that may be appropriate for your installation, depending on the environmental factors associated with your application and installation site.
IMPORTANT
You should install all wiring for your ControlNet cable system in accordance with the regulations contained in the National Electric Code (or applicable country codes), state codes, and applicable municipal codes. All metal connectors must be insulated from the ground.
Table C.2 Determine Cable Types For Light industrial applications Heavy industrial applications High and low temperature applications, as well as corrosive areas (harsh chemicals), low smoke generation and low flame spread Festooning or flexing applications Moisture resistant applications; direct burial, with flooding compound, fungus resistant Use This Cable Type Standard-PVC CM-CL2 Lay-on Armoured and Interlocking Armour Plenum-FEP CMP-CL2P
C-7
A segment is comprised of several sections of trunk cable separated by taps between 75 terminators. The total cable length of a segment is equal to the sum of all of the trunk-cable sections.
Figure C.4 Taps and Trunk Cable Sections
Tap Tap Tap
IMPORTANT
When determining the cable length of trunk-cable sections, make sure you measure the actual cable path as it is routed in your network. Consider vertical dimensions as well as horizontal dimensions. You should always calculate the three-dimensional routing path distance when determining cable lengths. For intrinsically-safe applications, make sure to cover all exposed metal with either the intrinsically safe sheaths or other forms of insulation.
Select the shortest path for routing the cable to minimize the amount of cable you need. The specific details of planning such a cable route depends on the needs of your network.
C-8
The total allowable length of a segment containing standard RG-6 quad shield cable depends upon the number of taps in your segment. There is no minimum trunk-cable section length requirement. The maximum allowable total length of a segment is 1,000 m (3280 ft) with two taps connected. Each additional tap decreases the maximum length of the segment by 16.3 m (53 ft). The maximum number of taps allowed on a segment is 48 with a maximum length of 250 m (820 ft).
Maximum Allowable Segment Length = 1000 m (3280 ft) - 16.3 m (53.4 ft) X [number of taps - 2]
Segment Length m (ft)
32 16 Number of Taps
48
EXAMPLE
If your segment requires 10 taps, the maximum segment length is: 1000 m (3280 ft) - 16.3 m (53.5 ft) x [10 - 2] 1000 m (3280 ft) - 130.4 m (427.7 ft) = 869.6 m (2852.3 ft)
C-9
The amount of high-flex RG-6 cable you can use in a system is less than the amount of standard RG-6 cable due to higher attenuation, so you should keep high-flex cable use to a minimum. Use BNC bullet connectors to isolate areas that require high-flex RG-6 cable from areas that require standard RG-6 cable; this allows the high-flex RG-6 section to be replaced before flexture life is exceeded. An allowable total length of RG-6 flex cable segment in your application can be determined using the equation below. Each additional tap decreases the maximum length of the segment. The maximum number of taps allowed on a segment is 48. Each additional tap decreases the maximum length of the segment by different lengths depending on the attenuation of your high-flex cable.
(20.29 db - [Number of Taps in Segment * .32 db]) Cable Attenuation @ 10 MHz Per 304 m (1000 ft)
Cable attenuation is defined as the signal loss measured at 10 MHz per 1000 ft (304 m) of cable. EXAMPLE If your segment requires 3 taps using 1786-RG6F/B(1) cable, the maximum segment length is: (20.29 db - [3 X.32 db]) / (13.5 db/1000) (19.33 db) / (13.5 db/1000) = 1431.8 ft (436 m)
(1)
1786-RG6F/B cable has an attenuation of 13.5 db/1000 ft at 10 MHz. 1786-RG6 cable has an attenuation of 5.99 db/1000 ft at 10 MHz.
C-10
You can install repeaters on a segment to increase the total trunk-cable length or number of taps. This creates another segment. You need to install repeaters if your system requires more than 48 taps per segment, or a longer trunk cable than the specifications allow.
1000 (3280) 750 (2460) 500 (1640) 250 (820) Repeater Not Required Repeater Required
32
16
48
Number of Taps
The maximum number of addressable nodes per network is 99. Since repeaters do not require an address, they do not count against the total of 99. Repeaters do require a tap and, therefore, can affect the length of the segment.
Segment 1
Repeater
Segment 2
43623
C-11
You must use 75 trunk terminators (cat. nos. 1786-XT and 1797-XT) to terminate each segment for the ControlNet cable system. You need two XT terminators per segment because you need one for each end of the segment.
After you have determined how many segments will be in your network, multiply this number by two to figure out how many terminators you will need for your network. Be sure to cover the exposed metal using the intrinsically safe sheath provided with each terminator in order to comply with intrinsic safety standards. The 1786-XT and 1797-XT trunk terminators are the same mechanically and electrically. You can mix these terminators in non-intrinsically safe environments. However, you must only use the 1797-XT terminators in intrinsically safe environments to maintain your applications Ex rating.
20 repeaters in series; 48 Install Repeaters In A repeaters in parallel Combination Of Series And Parallel
IMPORTANT
C-12
Repeater B
Repeater C
Device 4 Device 5
Segment 4
Segment 3
Device 6
42306
For any given architecture, the highest number of repeaters that a message might travel through to get from any single node to another determines the number of repeaters in series.
C-13
Segment 1
42307
Segment 2
Segment 3
Device 1
Device 2
Device 3
Repeaters A and B are in parallel off of segment 1. This network also has a maximum of 2 repeaters in series because the highest number of repeaters a message can travel through between any two nodes is 2. For example: if a message travels from device 1 to device 2 or 3, it travels through 2 repeaters.
C-14
Repeater E
Repeater F
Device 2
Segment 1 Repeaters A, B and C are installed in series and connected to the repeaters in parallel via segment 6. Repeater A
Segment 2 Repeater B
Device 4
Device 5
Device 6
Segment 4
Segment 5
Segment 7
42308
This network has a maximum of 5 repeaters in series because the highest number of repeaters a message can travel through between any two nodes is 5. For example: if a message travels from device 1 or 2 to device 4, it travels through 5 repeaters.
C-15
Depending on the type of connection you need to make, you can select from multiple Rockwell Automation ControlNet connectors. The following are examples of connections you may need to make in your ControlNet application: IP20 BNC connections make ControlNet segments using copper coax media make water-tight (IP67), ruggedized TNC connections make pre-made, short-distance fiber media connections make connections to devices in your network in a hazardous environment isolate a ControlNet segment from a hazardous area to a non-hazardous area To see a full list of the connectors available for these and any other connections in your ControlNet application, see the NetLinx Selection Guide, publication number NETS-SG001.
EXAMPLE
In this example, ControlNet cable: enters and exits the panel enclosure from the side using isolated-bulkhead connectors contains two adjacent taps connected by a barrel connector reserves one future tap location with a bullet connector makes a sharp bend with a right angle connector
Panel wall Bullet Connector Cable Enters and Exits From the Side Isolated Bulkhead Connectors
Barrel Connector
Taps
20091-m
C-16
ATTENTION
Do not let any metallic surfaces on the BNC connectors, plugs, or optional accessories touch grounded metallic surfaces. This contact could cause noise on the network. All exposed metal must be covered with either intrinsically safe blue sheaths or another form of sufficient insulation.
IMPORTANT
If you are installing a bullet connector for future tap installations, count the bullet as one of the tap allotments on your segment (and decrease the maximum allowable cable length by 16.3 m [53.5 ft]). This helps you avoid reconfiguring your network when you install the tap.
C-17
You can run a second trunk cable between your ControlNet nodes for redundant media. With redundant media, nodes send signals on two separate segments. The receiving node compares the quality of the two signals and accepts the better signal to permit use of the best signal. This also provides a backup cable should one cable fail. Trunk cables on a redundant cable link are defined by the segment number and the redundant trunk-cable letter. Actual ControlNet products are labeled with these icons (the shaded icon representing redundant media). In this figure, the redundant cable trunk cable is trunk cable B.
Figure C.8 Redundant Media
Trunk Cable A =
Trunk Cable B =
Node Node
Node
43629
C-18
Observe these guidelines when planning a redundant media system in a hazardous area. Route the two trunk cables (trunk cable A and trunk cable B) differently to reduce the chance of both cables being damaged at the same time. Each node on a redundant-cable link must support redundant coax connections and be connected to both trunk cables at all times. Any nodes connected to only one side of a redundant-cable link will result in media errors on the unconnected trunk cable. Install the cable system so that the trunk cables at any physical device location can be easily identified and labeled with the appropriate icon or letter. Each redundant ControlNet device is labeled so you can connect it to the corresponding trunk cable. Both trunk cables (trunk cable A and trunk cable B) of a redundant-cable link must have identical configurations. Each segment must contain the same number of taps, nodes and repeaters. Connect nodes and repeaters in the same relative sequence on both trunk cables. Each side of a redundant-cable link may contain different lengths of cable. The total difference in length between the two trunk cables of a redundant-cable link must not exceed 800m (2640 ft).
C-19
Figure C.9
Segment 1 Terminators Trunk Cable B = Trunk Cable A = Terminators
Repeater B
Node
Node Repeater A
Node
Node
Trunk Cable B =
Trunk Cable A = Terminators Segment 2 To use redundant media, all nodes must support redundant media. Terminators
43630
IMPORTANT
Make sure you do not mix A and B cable connections in a redundant operations. A node supporting redundant trunk-cable connections will function even if trunk cable A is connected to the B connector on the node and vice-versa. However, this makes cable fault indications (on the hardware or in software) difficult to interpret and makes locating a bad cable segment extremely difficult. When in redundant cable mode, each node independently decides whether to use channel A or channel B. This decision is based on error counters internal to each node. Redundant cabling is only valid if there is only one fault on the network. In other words, if you have a proper redundant cabling system and you remove node 3 on trunk A and node 4 on trunk B the system will not operate correctly because a double failure has occurred.
C-20
Application Considerations
The guidelines in this section coincide with the guidelines for the installation of electrical equipment to minimize electrical noise inputs to controllers from external sources in IEEE standard 518-1982. When planning your cable system there are certain installation considerations depending on your application. There are three categories of conductors:
Table C.3 Conductor Categories Category 1 Includes ac power lines high-power digital ac I/O lines high-power digital dc I/O lines power connections (conductors) from motion drives to motors 2 analog I/O lines and dc power lines for analog circuits low-power digital ac/dc I/O lines low-power digital I/O lines ControlNet communication cables 3 low-voltage dc power lines communication cables to connect between system components within the same enclosure
ATTENTION
These guidelines apply only to noise coupling. Intrinsic safety requirements for cable mounting are of the highest priority.
C-21
Category-1 conductors of less than 20 A ac power lines of 20 A or more, up to 100 KVA ac power lines greater than 100 KVA Category-1 conductors of less than 20 A ac power lines of 20 A or more, up to 100 KVA ac power lines greater than 100 KVA
C-22
Surge Suppression
Transient electromagnetic interference (emi) can be generated whenever inductive loads such as relays, solenoids, motor starters, or motors are operated by hard contacts such as push-button or selector switches. These wiring guidelines assume you guard your system against the effects of transient emi by using surge-suppressors to suppress transient emi at its source. Inductive loads switched by solid-state output devices alone do not require surge suppression. However, inductive loads of ac output modules that are in series or parallel with hard contacts require surge-suppression to protect the module output circuits as well as to suppress transient emi.
Ferrite Beads
Ferrite beads can provide additional suppression of transient emi. Fair-Rite Products Corporation manufactures a ferrite bead (part number 2643626502) which can be slipped over category-2 and category-3 (RG-6 type trunk cable) conductors. You can secure them with heat-shrink tubing or tie-wraps. A cable transient emi induced onto the cable can be suppressed by a ferrite bead located near the end of the cable. The ferrite bead will suppress the emi before it enters the equipment connected to the end of the cable.
C-23
Order Components
Now that you are ready to begin ordering components, use these guidelines to help you select components.
General Planning
The ControlNet cable system is isolated from earth and must be protected from inadvertent ground connections.
Segment Planning
all connections to the trunk cable require a tap taps may be installed at any location on the trunk cable tap drop-cable length must not be changed (fixed at 1 meter) maximum number of taps = 48, with 250 m (820 ft) of standard RG6 trunk cable maximum trunk-cable length of standard RG6 trunk cable = 1000 m (3280 ft), with 2 taps 75 trunk terminators are required on both ends of a segment one tap with an unconnected drop cable may be installed for maintenance purposes use ControlNet tap terminators (1786-TCAP) for all other unconnected drop cables use BNC bullet connectors at future tap locations do not mix redundant and non-redundant nodes when redundant cabling is desired avoid high noise environments when routing cables
Link Planning
maximum of 99 nodes (excluding repeaters) repeaters require a tap but are not counted as nodes they are included in the number of devices allowed per segment (48) repeaters may be installed at any tap location along a segment there can only be one path between any two points on a link the configuration of both sides of a redundant segment must be the same the total cable difference between the two sides of a redundant link can not exceed 800 m (2640 ft)
C-24
Notes:
Appendix
Use this appendix to monitor and control I/O devices that are wired to 1771 I/O modules when a: 1756-CN2(R) or the 1756-CNB(R) module connects the local chassis to a ControlNet network. 1771-ACN(R)15 adapter connects the 1771 I/O modules to the same ControlNet network.
ControlLogix Chassis with 1756-CN2(R) Module 1771-ACN(R)15 Adapter
42518
ControlNet Network
If you have not already done so in a previous procedure, do the following preliminary task: Add the Local 1756-CN2(R) or 1756-CNB(R) Module To complete this procedure, do the following tasks: Add the 1771-ACN(R)15 Module Communicate with Block Transfer Modules, using either of these procedures: Read or Write Data To or From a Block Transfer Module Via a Message Instruction Address I/O
D-2
Add the Local 1756-CN2(R) or 1756-CNB(R) Module Add the 1771-ACN(R)15 Module
For more information on how to do this, see the section Add Local and Remote ControlNet Modules in the chapter Control I/O.
To transfer discrete data between remote 1771 I/O and the ControlLogix controller in the local chassis (via the 1756-CN2(R), 1756-CNB(R) module), you need to add a remote 1771-ACN(R)15 ControlNet adapter to the I/O configuration. 1. Add the 1771-ACN(R)15 module.
D-3
A. Name the module. B. Select a Comm Format. For more information on choosing a Comm Format, see section Communication Format. C. Select the modules Revision level.
E. Select the modules node number on ControlNet. F. Select the Input Size. G. Select the Output Size. H. Click Next.
D. Select an Electronic Keying level. For more information on choosing a keying level, see table Electronic Keying Options.
I. Set the RPI rate. The RPI must be equal to or greater than the NUT. This parameter only applies if the module uses one of the Rack Optimized communication formats. J. Inhibit the module, if necessary.
Initially, do you want the module to communicate with the controller? Yes No
(1)
Then
K. Determine if you want a major fault on the controller if the connection to the PanelView fails in Run Mode.
If You Want The Controller To fault (major fault) continue operating
(1)
L. Click Finish.
Then Select the check box Leave the check box unchecked(1)
When you test this portion of the system, clear the check box.
D-4
Read or Write Data To or From a Block Transfer Module Via a Message Instruction
Use this procedure to transfer data to or from a module that requires block transfers. Use an INT buffer in the message and move the data into or out of the buffer as needed because DINTs can increase the program scan.
D-5
A. Select a Block Transfer Read message type. B. Select the number of elements to read. In this case, the number of elements is the number of INTs to read. C. Select the tag to hold the data that is read.
D. Use the Browse button to select a path for the message. To use this method, you must make sure the remote 1771 adapter was added to your projects I/O configuration. E. Select ControlNet. F. Cache the connection if 16 or fewer devices require the block transfer instructions. If more than 16 devices require the block transfer instructions, determine whether this message is for one of the 16 devices that require the most frequent updates and follow the guidelines below: If the device for this message is among the 16 requiring most frequent updates, cache the connection. If not, do not cache the connection, leave the box unchecked. For more information on caching connections, see section Guidelines for Caching Message Connections. G. Set the physical slot location in the 1771 chassis.
D-6
D-7
A. Select a Block Transfer Write message type. B. Select the tag where the data is written from; the tag should be INT. C. Select the number of elements to write.
D. Use the Browse button to select a path for the message. To use this method, you must make sure the remote 1771 adapter was added to your projects I/O configuration. E. Select ControlNet. F. Cache the connection if 16 or fewer devices require the block transfer instructions. If more than 16 devices require the block transfer instructions, determine whether this message is for one of the 16 devices that require the most frequent updates and follow the guidelines below: If the device for this message is among the 16 requiring most frequent updates, cache the connection. If not, do not cache the connection, leave the box unchecked. For more information on caching connections, see section Guidelines for Caching Message Connections. G. Set the physical slot location in the 1771 chassis.
D-8
Address I/O
To monitor or control discrete 1771 I/O devices, assign the tag name of the device to an instruction in your logic: For step-by-step instructions on how to enter logic and tag names, refer to the Logix5000 Controllers Common Procedures, publication 1756-PM001. All the data for I/O modules is at the controller scope. As you assign addresses, click Controller Scoped Tags to see the I/O tags. Use the following table to select the address of an I/O device:
For a Digital Device Use This Address name:type.Data[group].bit Where name Is the name of the remote I/O adapter, such as the user-defined remote_1771_adapter in the previous examples Use the name for the rack that contains the module to which this device is wired. Use the name from the I/O configuration folder of the controller. type type of device: If input output group bit Then I O
group number of the module to which this device is wired point (bit) number to which this device is wired
D-9
EXAMPLE
4 1771-ACN Remote_1771 (Remote_1771_adapter is the name assigned to the adapter) Input Device Group 2 Bit 0
Remote_1771:I.Data[2].0
42435
D-10
Notes:
Index
Numerics
1734-ACNR module additional documentation Preface-3 overview 1-7 1756-CN2, 1756-CN2R modules additional documentation Preface-3 overview 1-3 troubleshooting 8-28-5 1756-CNB, 1756-CNBR modules additional documentation Preface-3 overview 1-4 troubleshooting 8-68-10 1769-L32C, 1769-L35CR controllers additional documentation Preface-3 overview 1-4 troubleshooting 8-118-14 1784-PCC card additional documentation Preface-3 overview 1-5 1784-PCIC, 1784-PCICS, 1784-PKTCS cards additional documentation Preface-3 overview 1-5 troubleshooting 8-158-16 1788-CN(x) cards additional documentation Preface-3 overview 1-6 troubleshooting 8-178-20 1794-ACN15, 1794-ACNR15 modules additional documentation Preface-3 overview 1-6 troubleshooting 8-218-22 1797-ACNR15 module additional documentation Preface-3 overview 1-7 troubleshooting 8-238-24 determining how many taps your network needs C-4C-5 determining how many trunk terminators your network needs C-11
C-14
determining if your network needs repeaters C-10 determining what type of cable your network needs C-6 determining what type of connectors your network needs C-15 redundant media C-17C-19 caching message connections 6-5 capacity distance B-14 number of nodes B-14 of a ControlNet network B-11B-14 chassis monitor 1784-PCICS card 2-6 communication format 3-9, 4-34-9 listen-only rack optimized 3-9 rack optimized 3-9, 4-44-7 selecting in RSLogix 5000 3-8 Communication Module 1-2 configuring a ControlNet module 3-1 downloading configuration 3-103-11 using RSLogix 5000 3-23-11 configuring ControlNet communications driver in RSLinx 2-32-4 connecting a computer to the ControlNet network 2-12-6 connecting a SoftLogix controller to ControlNet 2-52-6 connections bridged A-1 connected messaging limits A-2 determining for messages 6-5 determining for produced and consumed tags 5-3 direct connections 4-54-6, A-1 listen-only connections 4-84-9 rack-optimized scheduled connections unconnected messaging limits A-3 use over ControlNet A-1A-3 validating connections 4-174-19 connectors determining what type your network needs C-15C-16 consumed tags 5-15-18
Publication CNET-UM001C-EN-P - November 2005
C-16
3-24
A
actual packet interval B-5
B
bandwidth limitations with produced and consumed tags 5-6 bridging messages across networks
1-91-11
A-1
C
cable requirements C-1C-23 determining cable section lengths C-7
C-9
Index
as they affect network update time 5-6 bandwidth limitations 5-6 determining connections 5-3 for non-Logix5000 controllers 5-12 organizing tag data 5-5 controlling I/O over ControlNet 4-1 accessing distributed I/O data 4-13
selecting a communication format 4-3 validating connections 4-174-19 inhibiting the connection to a ControlNet module 3-5 interlocking controllers See produced tags or consumed tags
4-9
adding distributed I/O to an RSLogix 5000 project 4-114-13 controlling 1771 I/O D-1D-9 requested packet interval 4-2 validating connections 4-174-19 ControlNet overview B-1B-14
L
listen-only connections 4-84-9 listen-only rack optimized communication format 3-9
M
message instructions 6-16-18 caching message connections 6-5 configuring a MSG to a Logix5000 controller 6-8 configuring a MSG to a PLC-5 processor
D
data types in produced or consumed tags 5-5 direct connections 4-54-6 direct scheduled connections A-1 distributed I/O accessing data 4-134-16 adding to an RSLogix 5000 project 4-11
6-10
4-13
E
electronic keying compatible match 3-6 disable keying 3-6 exact match 3-6 setting in RSLogix 5000 3-8, D-3
configuring a MSG to an SLC 500 processor 6-9 configuring in RSLogix 5000 6-76-10 determining connections 6-5 guidelines 6-4 mapping Logix tag names to memory locations from PLC/SLC data tables 6-146-15 message types block-transfer read or write 6-5 CIP data table read or write 6-5 CIP generic 6-5 PLC2, PLC3, PLC5 or SLC (all types)
6-5
I
I/O accessing distributed I/O data in RSLogix 5000 4-134-16 adding distibuted I/O to an RSLogix 5000 controlling over ControlNet 4-14-19 direct connections 4-54-6 listen-only connections 4-84-9 ownership in a Logix5000 system 4-8 rack optimized connections 4-44-7
programming instruction in controllers logic 6-66-7 receiving MSGs from PLC-5 or SLC 500 processors 6-12 routing PLC-5 messages between ControlNet networks 6-16 staggering messages 6-16
6-18
4-114-13
N
network keeper B-8 network update time B-4 as it affects produced and consumed tags maintenance portion B-4 scheduled portion B-4
4-9
5-6
Index
O
overview 1734-ACNR module 1-7 1756-CN2, 1756-CN2R modules 1-3 1756-CNB, 1756-CNBR modules 1-4 1769-L32C, 1769-L35CR controllers 1-4 1784-PCC card 1-5 1784-PCIC, 1784-PCICS, 1784-PKTCS cards 1-5 1788-CNC, 1788-CNCR, 1788-CNF, 1788-CNFR cards 1-6 1794-ACN15, 1794-ACNR15 modules 1797-ACNR15 module 1-7 of ControlNet communication modules
when organizing produced and consumed tag data 5-5 routing PLC-5 messages between ControlNet networks 6-166-18 RSLinx configuring ControlNet communications driver 2-32-4 RSLogix 5000 accessing distributed I/O data 4-13
4-16
adding distributed I/O to an RSLogix 5000 project 4-114-13 communication format 3-83-9, 4-3 configuring a ControlNet module 3-2 configuring a message instruction 6-7 creating a produced tag 5-75-8 downloading configuration 3-103-11 programming message instructions in a controllers logic 6-66-7 RSLogix5 routing ControlNet messages 6-17
4-9
1-6
3-11 6-10
1-11-12
of the RSLogix 5000 configuration process 3-2 ownership in a Logix5000 system 4-8 listen-only connection 4-84-9 owner-controller 4-84-9
4-9
6-18
P
peer-to-peer messaging See message instructions produced tags 5-15-18 as they affect network update time 5-6 bandwidth limitations 5-6 creating in RSLogix 5000 5-75-8 determining connections 5-3 for non-Logix5000 controllers 5-12 organizing tag data 5-5
S
scheduling a ControlNet network 3-12
3-24, B-6
T
tags See produced tags or consumed tags taps determining how many your network needs C-4C-5 terminators determining how many your network needs C-11C-14 topology example system ring B-13 example system star B-12 example system trunkline/dropline B-12 of a ControlNet network B-11B-14 troubleshooting ControlNet communication modules 8-1
R
rack optimized communication format
3-9, 4-44-7
related documentation. See documentation repeaters C-11C-14 for a ControlNet network C-10 installing in a series C-12 installing in combination of series and parallel C-14 installing in parallel C-13 requested packet interval 4-2, B-4 setting in RSLogix 5000 3-8, D-3
8-24
Index
8-5
8-10
1784-PCIC, 1784-PCICS, 1784-PKTCS cards 8-158-16 1788-CN(x) cards 8-178-20 1794-ACN15, 1794-ACNR15 modules 1797-ACNR15 module 8-238-24
8-118-14
8-218-22
Please complete the sections below. Where applicable, rank the feature (1=needs improvement, 2=satisfactory, and 3=outstanding).
Overall Usefulness 1 2 3 How can we make this publication more useful for you?
Can we add more information to help you? procedure/step example explanation illustration guideline definition feature other
Other Comments
Your Name Your Title/Function Location/Phone Would you like us to contact you regarding your comments? ___No, there is no need to contact me ___Yes, please call me ___Yes, please email me at _______________________ ___Yes, please contact me via _____________________ Return this form to: Rockwell Automation Technical Communications, 1 Allen-Bradley Dr., Mayfield Hts., OH 44124-9705 Fax: 440-646-3525 Email: [email protected]
PN 957988-68957782-91
Other Comments
PLEASE REMOVE
ControlLogix, RSLogix 5000, RSView, RSNetWorx, RSNetWorx for ControlNet, and RSLinx software are trademarks of Rockwell Automation, Inc. ControlNet is a trademark of ControlNet International, Ltd. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running: United States Outside United States 1.440.646.3223 Monday Friday, 8am 5pm EST Please contact your local Rockwell Automation representative for any technical support issues.
PN 957988-68
Copyright 2005 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
User Manual