AMF2 0+ver01
AMF2 0+ver01
AMF2 0+ver01
AMF2.0
ENKO Electronic Control Systems - IZMIR / TURKIYE www.enkoelektronik.com
AMF2.0 offers all necessary control AMF2.0 is a full Automatic Mains Failure unit intended to be used for Main features:
functions for single Generator/ single Gen-Set applications. The controller can be used with single or
Mains applications. three phase mains systems. Full automatic mains fail-
ure control functions
Full Generator control functions can be implemented through the unit
program menu. The unit has a configuration parameter menu which Full control and protection
can be accessed from the front panel. All engine parameters can be of engine and alternator
monitored and full engine protection is provided.
Digital display for monitor-
Cranking can be achieved manual or automatic, depending on the ing voltages and frequency
selected operation mode. Start of engine is detected automatically
Automatic control of MCB
and crank relay is controlled accordingly.
and GCB relays
The alternator values are also monitored and all values are measured Automatic and Test opera-
and calculated as True RMS values, avoiding false voltage measure- tion options
ments due to high load harmonic contents, hence ensuring reliable
operation. The AC voltage inputs are suitable up to 500Vac. 4 configurable input and
Efficient and sim- output ports for peripheral
ple control for AMF2.0 is designed to fulfill all the required functions to control the control
single GenSet load. Mains is monitored on all three phases and protection limits are
Configuration menu with
applications programmable through the menu. There are three operation modes
which the user can select from. Controller will control the load accord-
44 parameters
ing to the selected mode. Digital calibration on
measuring inputs
All the measurement calibration can be made through the program
Engine control and Mains side
menu and there is no need for any trimmer adjustments. The unit Small housing for space
parameter controls are available
menu is protected with two-stage password, allowing user and experi- saving applications
and can be configured through the
enced technician to reach appropriate menu parts.
unit’s program menu.
Technical specifications:
3 PHASE TRUE RMS MAINS √
VOLTAGE MEASUREMENT
UTILITY
DC power supply: 9-35Vdc
SINGLE PHASE TRUE RMS √
GENERATOR VOLTAGE
Operating temperature: -35°C to +70°C
MEASUREMENT
Relative humidity: 20%rH to 99%rH, non condens-
PREHEAT FUNCTION BEFORE √
MAINS
ing TRANSFORMER
IGNITON
AC voltage measurement: 20Vac to 500Vac phase to phase
3 PH VOLTAGE
Frequency measurement: 1.0Hz to 99.9Hz, ±0.1Hz
WIDE OPERATING TEMPERA- √
TURE RANGE
MCB CONTROL
LOAD
UTILITY GENERATOR
MCB GCB
R R S T N U
S V DIESEL
G ENGINE
T W
N Mp
1 2 3 4 6 5 8 7
GCB contact
MCB contact
19 18 11 10 9 12 13 14 15 16 17
Input common
Emergency
Auxiliary input
Stop solenoid
Fuel solenoid
charge
Alarm relay
Crank relay
D+WL
protect)
crank
Mechanical dimensions
Typical connection diagram is AMF2.0 controller plastic housing is
shown and this is one of possible designed according to DIN norms.
applications among many. The Mechanical dimensions are shown in
system is shown in 3 phase the drawing.
connection but can also be applied
for single phase systems. Plastic housing is made of NORYL
(PPO) which provides high tempera-
The configurable inputs and ture resistance and good mechanical
outputs can be programmed in stability. The electrical characteris-
order to adopt the controller to tics of the housing is excellent.
more specific applications. The
controller is suitable for 12/24Vdc The front panel is designed to com-
systems. ply with IP52 protection class. Em-
bossed Lexan is used for front pan-
Care should be taken in order to el, which provides easy control of
connect the negative terminal of the buttons and clear reading of the
the battery to the gen-set chassis. digital values. It also provides long
life for operation.