0% found this document useful (0 votes)
118 views

Stringing Chart

This document summarizes the geometry, properties, and sag calculations for a span of ACSR wire. It includes the span length of 350m, attachment height of 0m, ground elevation of 0m, and initial sag of 6.00693m at the center of the span. It also provides the material properties and stress-strain coefficients for the 54/7 strands Bison ACSR wire used in the calculations. Charts show the predicted sag and tension at temperatures from 5 to 90 degrees C.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
118 views

Stringing Chart

This document summarizes the geometry, properties, and sag calculations for a span of ACSR wire. It includes the span length of 350m, attachment height of 0m, ground elevation of 0m, and initial sag of 6.00693m at the center of the span. It also provides the material properties and stress-strain coefficients for the 54/7 strands Bison ACSR wire used in the calculations. Charts show the predicted sag and tension at temperatures from 5 to 90 degrees C.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Span Geometry and Properties

Project Name 'c:\users\public\documents\pls\pls_pole\examples\Untitled.ult'


Wire Properties 'C:\Users\Public\Documents\PLS\pls_cadd\examples\cables\bison_acsr.wir'
Span Horizontal Projection 350 (m)
Span Vertical Projection 0 (m)
Average Attachment Height Above Ground 0 (m)
Ground Elevation 0 (m)
Ruling Span 350 (m) (same as span horizontal projection)
Sagging Wire Temperature 32 (deg C)
Sagging Wire Condition 'Initial'
Sagging Method 'Horizontal-Tension'
Sagging Horizontal Component of Tension 36100 (N)
Sagging Catenary Constant 2550.14 (m) (equivalent to input sagging tension)
Sagging Mid Span Sag 6.00693 (m) (equivalent to input sagging tension)
Sagging Wire Slack 0.2748 (m) (equivalent to input sagging tension)
Graphics above show wire displayed for sagging temperature/condition, and ACSR_MAX TEMP Initial.
Graphics above have wire sag labeled for .

K&A Engineering Consulting Page 1/4


Cable Data Report
Name and description: bison_acsr.wir 54/7 Strands BISON ACSR British - Adapted from 1970's Publicly Available Data
Cable model: Nonlinear cable model (separate polynomials for initial and creep behavior for inner and outer materials).
Cross section area 430.515268 (mm^2)
Weight per unit length 14.1561 (N/m)
Outside diameter 26.9748 (mm)
Ultimate tension 121436 (N)
Outer strands modulus of elasticity 441.264 (MPa/100)
Outer strands thermal expansion coefficient 0.002304 (/100 deg)
Core strands modulus of elasticity 217.184 (MPa/100)
Core strands thermal expansion coefficient 0.001152 (/100 deg)
Test temperature at which stress-strain and creep data below applies 21.1111 (deg C)
Outer strands stress-strain polynomial coefficients: -3.25846 365.227 -358.214 94.5959 42.3199 (MPa/100)
Outer strands creep polynomial coefficients: -0.245453 145.536 -74.455 10.1353 8.56327 (MPa/100)
Core strands stress-strain polynomial coefficients: 0.952854 196.405 111.231 -362.491 198.941 (MPa/100)
Core strands creep polynomial coefficients: 0.952854 196.405 -74.455 -362.491 198.941 (MPa/100)
Bimetallic conductor model: Limited Compres., compression limited to 68947.4 (MPa)

K&A Engineering Consulting Page 2/4


Stringing Chart Report

Weather case for final after creep ACSR_MAX TEMP, Equivalent to 9.3 (deg C) temperature increase
Weather case for final after load ACSR_EDT_FW, Equivalent to 7.5 (deg C) temperature increase
Results below for condition 'Initial RS'
Calculations done using actual span lengths and vertical projections

Span Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Mid Left Span
Length Span Span Span Span Span Span Span Span Span Span Span Span Span Span Span Span Span Span Struct Vertical
Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Sag Number Projection
5 C 10 C 15 C 20 C 25 C 30 C 35 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C 75 C 80 C 85 C 90 C
(m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m) (m)
350.0 5.21 5.34 5.49 5.63 5.79 5.94 6.10 6.27 6.43 6.60 6.78 6.95 7.13 7.31 7.49 7.67 7.85 8.04 0.00

Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz Horiz
Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension Tension
5 C 10 C 15 C 20 C 25 C 30 C 35 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C 75 C 80 C 85 C 90 C
(N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N) (N)
41633 40570 39519 38482 37474 36497 35537 34610 33717 32844 32008 31192 30416 29680 28967 28279 27617 26990

K&A Engineering Consulting Page 3/4