Panel Specification Clause 21

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

MAXPRO SPEC. No.: NSK2/OSBL/43/034_Rev.

4 PAGE 30 OF 31
21.0 TECHNICAL PARTICULARS AND DATA TO BE FILLED BY BIDDER (DG PCCs):

DESCRIPTION VENDOR TO FILL IN


A GENERAL
1 Make L&T / SCHNEIDER / SIEMENS
2 Enclosure material GI sheet
3 Type Single front, Modular,
Compartmentalized, Draw out type
4 Thickness of sheet metal 2 mm for load bearing members, 1.6
mm for non-load bearing members & 3
mm for Gland Plate
5 Paint Shade Siemens Grey (RAL-7032)
6 Cable entry
6.1 Incoming Bottom
6.2 Outgoing
B BUSBARS
1 Rated continuous current As shown on SLD
2 Busbar material As shown on SLD
3 Busbar size Vendor to indicate. Bus bar size shall
be same, uniform through out the
Switchboard
4 Ground bus size Not less than 50 x 6 mm Aluminium
5 Bus with insulating sleeves Yes
6 Clearances Ph/Ph, Ph/n & Vendor to specify
Ph/earth
7 Short circuit current rating As shown on SLD
8 Busbar support insulator make & Vendor to specify
voltage class
9 Final Temperature busbars 85 deg C
C ACB/MCCB
1 Make L&T / SIEMENS / SCHNEIDER
2 Voltage, frequency & poles 415V, 50 Hz, 3Ph, 3P with bolted
neutral
3 Rated current As per SLD
4 Short circuit withstand rating As shown on SLD
5 Rated ultimate short circuit Vendor to specify
current (Icu)
6 Rated service short circuit current Vendor to specify
(Ics)
7 Rated short circuit making current Vendor to specify
(Icm)
8 Total interrupting time (ms) Vendor to specify
9 Operating mechanism Manual, Quick Make & Quick Break
10 Trip - free feature Required
11 Provision for pad locking facility in Required

12 No. of auxiliary contacts Vendor to specify


D CURRENT TRANSFORMER
MAXPRO SPEC. No.: NSK2/OSBL/43/034_Rev.4 PAGE 31 OF 31
DESCRIPTION VENDOR TO FILL IN
1 Make KAPPA / AE
2 Type & services Epoxy cast resin
3 Voltage & frequency 415V, 50Hz
4 Ratio As required
5 Rated VA burden As required
6 Accuracy class As required
7 Short circuit current rating As shown on SLD
8 Class of Insulation Vendor to specify
9 Terminals type Bolted, Fixed type
E MINIATURE CIRCUIT BREAKER
1 Make L&T / SIEMENS / INDO ASIAN
2 Type Vendor to specify
3 Rated voltage Vendor to specify
4 Rated current As per SLD
5 Category of duty Vendor to specify
6 Rupturing capacity (Prospective
Vendor to specify
current)
7 Maximum let through current for
Vendor to specify
1 second
8 Time current characteristics Vendor to specify
F INDICATING INSTRUMENTS
1 Make L&T/Schneider-Conzerv / Rishabh /
Siemens
2 Size Min.96 mm x 96 mm
3 Type Vendor to specify
4 Range for Incoming & Outgoing Vendor to specify
G WIRING
1 Size 2.5 Sq.mm Copper Minimum for
power, 2.5 Sq.mm copper for CT
secondary and 1.5 Sq. mm for control
circuits
2 Insulation PVC
3 Voltage class 600/1100 V

You might also like