Ba CC28 en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 34

Operation Manual

CC28
Transmitter for flammable gases and vapours

GfG GESELLSCHAFT FÜR GERÄTEBAU MBH▐ KLÖNNESTRASSE 99▐ D-44143 DORTMUND▐ TELEPHONE +49 / (0) 2 31 / 5 64 00 –0 ▐ FAX +49 / (0) 2 31 / 51 63 13
[email protected] ▐ WWW.GASDETECTION.BIZ▐ AMTSGERICHT DORTMUND HR B 2742▐ CERTIFIED AS PER DIN EN ISO 9001:2000▐ ATEX QM CERTIFICATE
Content
Page

For your Safety 5


Operational Hints 5
General Description 6
Detection Principle 6
Design 7
Mounting Position of Transmitter 8
Mounting 9
Installation of Electrical Connections 9
Putting in Operation 10
Detection Mode 11
Check and AutoCal Adjustment of Zeropoint (ZERO) 13
Check and AutoCal Adjustment of Sensitivity (SPAN) 14
Service Menu and Extended Service Menu 15
Sensor Replacement 21
Transmission Characteristics 22
Special Status and relevant Error Messages 23
Messages in detection mode 24
Messages in service mode and during calibration 24
Situation of Status LED’s and Output 25
Priority of displays and messages in detection mode 25
Putting into Operation and Maintenance 25
Service, Inspection, Calibration and Adjustments 26
Regular Function Tests 26
Repair 26
Function Restrictions depending on Oxygen Concentration 27
Display Irritation due to Sensor Poisons 27
Trouble Shooting 27
Lower Explosion Limits (LEL) of Gases subject to Function Test 27
Spare Part List 28
Accessories 28
Connection Diagram CC 28 - with 4 .. 20 mA Output 29
Terminal Diagram MWG CC28 30
Sensor specification 31
Technical Data 32
Annex 33
Internal Memory CC28 33
EC-Type Examination Certificate 34

Warning:
The supply voltage must never exceed
30 V DC, not even in case of voltage peaks !

-4-
For your Safety
According to § 3 of the law about technical working media, this manual points out the proper use of
the product and serves to prevent dangers. It must be carefully read by all individuals who have or
will have the responsibility for operating, using, servicing, maintaining and controlling this product.
Like any piece of complex equipment, this product will do the job designed to do, only, if it is
operated, used, serviced, maintained and controlled in accordance with GfG’s instructions.
The warranties made by GfG Gesellschaft für Gerätebau with respect to the product are voided, if it
is not operated, used, serviced, maintained and controlled as per GfG’s instructions. The above does
not alter statements regarding GfG Gesellschaft für Gerätebau's warranties and conditions of sale and
delivery.

Operational Hints
According to the relevant national regulations, gas warning instruments have to pass a function test,
done by a specialist, after having been installed but before put in operation. For Germany,
§ 56(2) "UVV Gase" (BGV B6 - formerly VBG 61) is applicable.
Before shipment, the transmitter has passed a function and display test, being calibrated with suitable
test gases. This does not, however, overrule the obligation of putting in operation with test gas
after the installation.
The transmitter CC28 (including CC28 D and CC28 DA) is approved for the use in explosion
endangered areas and is subject to an EC-Type Examination Certificate issued by EXAM BBG Prüf-
und Zertifizier GmbH, according to directive 94/9/EG (ATEX100a) with the following
Certificate: BVS 04 ATEX E 132 X
Labelling: ¯ II 2G EEx dem [ib] IIC T4 -20°C≤Ta≤+50°C

For the use in explosion endangered areas, with a measuring function for explosion protection, the
EXAM BBG Prüf- und Zertifizier GmbH issued an EC-type examination certificate for the transmitter
as per directive 94/9/EG.
Certificate: BVS 05 ATEX G 001 X
The test was based on the standards DIN EN 61779-1 "Electrical apparatus for detection and
measurement of combustible gases – General requirements and test methods" and DIN EN 61779-4
"Electrical apparatus for detection and mesurement of combustible gases – Requirements for the
operational behaviour of apparatus of group II with a detection range up to 100 % of the Lower
Explosion Limit" and the DIN EN 50271 „Electrical devices for the detection and measurement of
combustible gases, toxic gases or oxygen – Requirements and testing for warning devices using
software and/or digital technology“.
The EC-Type Examination Certificate BVS 05 ATEX G 001 X
! includes the following sensors, gases and detection ranges:
MK208-1, MK217-1, MK218-1 0 ... 100 %LEL CH4 (Methane), C3H8 (Propane)
0 ... 100 %LEL C2H4 (Ethylene), C3H8O (Isopropanol),
C3H6O (Aceton), C4H8O2 (Ethylacetate),
MK208-1, MK218-1 C6H14 (Hexane), C4H10O (Diethylether),
C9H20 (Nonane), C7H8 (Toluene)
MK217-1, MK218-1 0 ... 100 %LEL H2 (Hydrogen)
MK208-1, MK218-1 0 ... 4,00 %Vol. NH3 (Ammonia)

The functions marked (#) in this operation manual have not been part of the function and EC Type
Examination Certificate BVS 05 ATEX G 001 X.

-5-
General Description
A fixed gas monitoring system consists of a transmitter and a controller (GMA), which are connected
by means of cable. The transmitter converts the gas concentration into an electrical signal and
transmits it over the cable to the controller for further processing.
Compared to the transmitter CC28, the model CC28 D provides an additional display, while the
CC28 DA features a display and a visual and audible alarm.
The comprehensive electronics allow easy operation and maintenance and also increases the
operational safety and accuracy. The special features of the transmitter are:
• Indication of concentration at display or at remote control
• Adjustment by means of touch keys or remote control, without opening of casing
• Compensation of temperature effects.
• Ex-Approval for use at temperatures from -20 to +50°C
• Function Approval for use at temperatures see sensor specification
• Smart Sensor system – sensor replacement by means of plug-in, pre-calibrated sensor
• Permanent status display (operation/fault) at transmitter

Detection Principle
The CC28 is operated on the detection principle "catalytic combustion" (fig. 1). The gas/vapour-air
mixture enters the sensor chamber by diffusion through the sinter filter. Inside the sensor chamber
there are an active and a passive sensor filament. The heated active sensor burns (oxidizes) the
entering gas at its vatalytic layer. This increases the temperature at the sensor and results in a change
of the electrical resistance, which is the measure for the gas concentration. The passive (reference)
sensor is exposed to the same ambient conditions as the active (detection) filament and is used for
compensation of environmental effects (e.g. temperature changes).

Detection principle - Catalytic combustion

Passive element Sensor


Sinter metal chamber

Gas

Active element

Fig. 1

-6-
Design

CC28 D

Cable gland

Detection range

Display

Touch keys

Type label with date of production


e.g. SN:0504xxxx (05=year, 04=month)

Status display

Buzzer green yellow


(only for CC28 DA) Operation Fault

Sensor casing

Potential equalization

Alarm LEDs

Key for quick adjustment


(AutoZero key)
behind lock screw

Connection for
Remote Control

CC28 DA

The type label shows the transmitter type. The sensor enclosure includes the sensor and the sensor
card, which carries the components for the sensor circuitry. For adjustment of electrical zeropoint and
sensitivity you can use either the built-in display or the remote control RC2. A secured key at the left
side of the transmitter allows a quick zero setting. The electronics on the main p.c.board converts the
sensor signal into a linear output signal of 4 .. 20 mA.

-7-
Always connect the remote control RC2 only for servicing a transmitter without
! display.
The remote control RC2 may be used in explosion endangered areas.

They keys, functions and display of the


remote control RC2 are identical with
those of the transmitter.

Mounting Position of Transmitter

As per EN 50014 table 4 for devices of group II the casing has been tested with an
! impact energy of 4 Joule (low degree of mechanical danger). Protect the casing
against very hard impacts.

It is essential to exactly know the ambient conditions, which have to be taken into consideration
before deciding on the mounting position. To achieve representative measurement results, take care
of
• the room ventilation and
• the gas density.

Install the transmitter at a place where the gases pass the sensor even in case of bad ventilation. If
necessary, use a smoke cartridge to check.
If the transmitter has to be installed at a position, where flow rates can be >3.0m/s, a wind protection
is necessary.
Generally a gas supply to the transmitter from below (sensor side) should be avoided.
Should the gas flow come from below, however, the displayed value may increased beyond the
tolerance as per EN61779-4.
Most combustible gases and vapours are subject to a higher density than air, the transmitter is to be
installed close to the floor. For lighter gases, with a lower density than air, the transmitter is being
mounted close to the ceiling. A few gases have a density which is similar to that of air. For these
gases the transmitter should be mounted at the breathing height of approx. 1.5 m over the floor. The
following chart shows the relative density of some gases and vapours. More detailed information is
available on request.

Gas/Vapour relative gas density Recommended


compared with air mounting position
Hydrogen, methane and ammonia lighter close to ceiling
Ethylene, ethane, acetylene, methanol about same at breathing height
Propane, butane, hexane, nonane, propanol, heavier close to floor
toluene, ethyl acetate, aceton, diethyl ether, all
other organic solvents and fuel mixtures

Furthermore, take the following into consideration as well:


• Rain water, hose water, dripping water, condensate and
• dust in the atmosphere.

-8-
The transmitter is to a great extent protected against the ingress of water and dust (IP 64). Special
accessories are available to provide additional protection for very difficult conditions. Please contact
GfG for detailed information.

Warranty may be voided, if the sensor is exposed to ambient conditions which


! were unknown to GfG during planning, production or delivery.

Mounting
When deciding on the position for the transmitter, make sure that it is always accessible for service
and maintenance. The transmitter must be mounted with the sensor showing to the floor.
For connecting the transmitter to the controller refer to the connection diagram (page 28). For
mounting the transmitter remove the four special screws and take the casing top off. Fix the casing by
means of two screws.
The printed circuit board inside the casing is potted in epoxy resin (encapsulation "m"). The side-
mounted terminals (increased safety “e”) are used for connecting the controller.

Installation of Electrical Connections


Procurement of cable and electrical connections must be done by a specialist only, obeying the
applicable regulations. Always use shielded cable (e.g. LIYCY 3 x 1.5 mm2). The cross section of the
cable depends on the cable length. For short distances up to 200 m it may be sufficient to use
0.75 mm2 instead of 1.5 mm2. For longer distances the cross section must be 1.5 mm2. The cable
length must not be more than 1000 m.
The shield is fixed to the M16x1.5 screwing. In case the transmitter is mounted to an electrically
conductive background (e.g. steel grinder), a potential equalization is to be effected. If the transmitter
is installed in a room which is subject to Ex-regulations, make sure that only the transmitter is
installed in this area. The gas monitoring system resp. the mains supply and the controller must be
installed in the safe area.
The transmitter must be installed and opened in gas-free atmosphere only.
! The transmitter must only be opened when de-energized.

Terminal diagram Potential equalization

Pot. equalization min. 4 mm2


(at left side of casing) e.g. steel
grinder

Cable gland

1 2 3 4 Transmitter

Type label
24V Ground 4..20mA

Buzzer

GMA Controller
Sensor

-9-
In case the transmitter is not operated on a GMA controller, the operational voltage of the mains unit
must not exceed 30 V DC.
Fix the casing top with the four special screws after installation.
The user must make sure that even in case of failure the voltage at the

! transmitter terminals does not exceed the max. fault voltage Um indicated on
the type label.
Um = 250 V AC resp. Um = 45 V DC

Putting in Operation
The transmitter CC28 has passed quality control for correct operation and display before delivery.
The calibration was carried out with the appropriate test gases. Depending on transport, mounting
and ambient conditions however variations may occur. Therefore the gas warning system has to be
taken into operation and function checked by the manufacturer or by a professional which is
authorized by the manufacturer, according to BGV B6 (former VBG61-gases), resp. BG Chemie
guideline T 023.
After having been turned on, the unit needs a few minutes for:
• the self-test, checking the program and the working memory,
• entering and evaluating of transmitter parameters with simultaneous memory check,
• entering and evaluating of sensor parameters with simultaneous memory check,
• warming-up the sensor.

Within 6 seconds during the warm-up period the transmitter checks the memory first. The current
interface provides 0 mA and both the yellow and the green LED are lit. Then the output signal turns
to 1.6 mA, the fault LED lights up and the operation LED flashes slowly. The display reads LoAd,
then AdJ. Once this is completed, the display of the CC28 D and CC28 DA resp. of the remote
control RC2 at the CC28 reads the unit, the type of gas, the detection range, the alarm thresholds and
the calibration gas concentration one after the other. If the automatic reset of the ambiguity alarm is
activated, this is indicated last, and the fault LED flashes rapidly.
Once the warm-up is completed after 2 minutes, the CC28 turns to detection mode automatically.
During this period the display reads a countdown of the seconds from 120.
If a fault is recognized during this time, the transmiter turns to fault mode. The current interface
provides 1.2 mA and the display indicates a fault message (SYS ERR.). The status and fault LEDs are
lit constantly. The alarm LEDs and the display illumination will flash alternately.
Once the sensor has been replaced after a sensor fault (SENS ERR.), the transmitter is automatically
re-started. In case of sensor replacement adhere to the safety notes for electrical connections in
explosion endangered areas (see page 7).

Note:
After the initial putting into operation resp. after a sensor replacement it might be possible that the
value falls below or exceeds the detection range (____ resp. ----). In this case the zeropoint of the
transmitter must be corrected by starting the automatic zeropoint adjustment (ZERO).
Should SCAL ERR. occur (resettable), re-calibrate the sensor (SPAN) or, if necessary, enter the
service menu to adapt the detection range of the sensor to the hardware.

Allow a warm-up time of at least 30 minutes before you check the zeropoint. Once the warm-up is
completed, the display should read 0. Otherwise activate the (automatic) zeropoint adjustment
(AutoCal adjustment see page 11).

-10-
Detection Mode
In detection mode the display shows the current gas concentration.
The display reading is always identical with the display of the remote control connected!
The detection is provided by continuous monitoring. Exceeded thresholds (only for model CC28 DA)
and ambiguous sensor signals are recognized immediately and reported visually by the CC28.
Features of the electronics like parameter memory or sensor function are permanently monitored.
During trouble-free operation the green LED “ON“ is lit, the yellow fault LED is not lit.

To indicate that the CC28 is in detection mode the display alternates every minute to
! unit and type of gas.

Falling Below Detection Range


Values below the zeropoint are indicated as figures with negative sign. Depending on the
measurement value the current interface provides outputs between 4.0 and 2.8 mA.
Deviations of the detection range by – 7.5% or more are indicated by the permanently lit fault LED
and the display reading ____ alternating with the negative value. The current interface provides a
permanent output of 2.8 mA.
Deviations of the detection range by – 7.5% or more are indicated by the permanently lit fault LED
and the display reads permanently ____.
In case of deviations beyond the detection range of the transmitter circuitry the current interface
provides an output of 1.2 mA.
Exceeding Detection Range
Detection ranges which are exceeded between 100 % and 112 % are indicated by ---- in the
display, alternating with the measured value. Depending on the measurement value the current
interface provides outputs between 20 and 22 mA.
Should 112 % be exceeded, the unit activates the ambiguity alarm. The display flashes ---- and the
current interface provides an output of 22 mA.
Touch Keys
The functions of the touch keys at the transmitter and at the remote control is identical. The same
applies to the display at the CC28 D, CC28 DA and the remote control.
Check of Display, LED and Buzzer
Press briefly in detection mode to activate the check of the display and LEDs. All LEDs are
TEST

ZERO

activated for 2 seconds, and all segments of the display (8.8.8.8) are shown. For the CC28 DA the
alarm LEDs and the buzzer are activated additionally.
Display of Operational Parameters
During detection mode press key briefly for the automatic indication of the following operational
INFO

SPAN

parameters one after the other.


This order of readings will also appear after turning the transmitter on.
Display / Example Meaning of display
1a LEL Measuring unit (indication in % LEL)
1b UOL Measuring unit (indication in Vol.%)
2 CH4 Type of gas
3 SCAL 100 Detection range (full scale in “measuring unit”)
4 CL
MAS 80.0 Calibration gas concentration (value in “measuring unit”)
5 A1 20.0 Alarm threshold (value in “measuring unit”)
6 A2 40.0 Alarm threshold (value in “measuring unit”)
7 AM
"b. oN Automatic reset of ambiguity alarm (display reading only,
if „on“)

-11-
Value in “measuring unit” means that the displayed figure stands for either % LEL or Vol.%. Reading in
Vol.% applies only to the gas ammonia.
Alarm Threshold (only for type CC28 DA)
The CC28 DA provides two alarm thresholds. An alarm is triggered, if the gas concentration exceeds
the preset limit value (adjustment in service menu). Exceeded thresholds are indicated by means of
the LED bar over the display, the display illumination and a buzzer. When the first threshold (A1) is
exceeded, the display illumination and the LED bar are alternating in low frequency. The display
reads the currect measurement value and A1 alternately.
Exceeding the second threshold (A2) activates the display illumination, the LED bar and the buzzer
alternating in high frequency. The display reads the current measurement value and A2 alternately.
Resetting the threshold alarms can be done automatically or manually, i.e. non-latching or latching
alarms, depending on the function setting in the service menu.
The function of the buzzer is fixed and cannot be changed: Activation by alarm 2, automatic reset
when the concentration has fallen below the second threshold, always resettable.
Pressing key allows to reset a latching alarm, if the gas concentration has fallen below the alarm
QUIT

MENU

threshold.
Ambiguity Alarm
Due to the detection principle it might be possible that a very high gas concentration dissipates the
oxygen in the cell, thus resulting in a lack of oxidation and a reduced signal, although the sensor is
exposed to a gas concentration which is clearly above its detection range. For avoiding false signal
evaluation, the CC28 provides a warning from ambiguous sensor signals.
This alarm is triggered by exceeding of 112 % LEL and by recognition of a defined rise of signal
(Delta Alarm).
The ambiguity alarm is indicated by the fault LED flashing quickly. The CC28 DA additionally
activates the display illumination, the LED bar and the buzzer, alternating in high frequency. The
display also flashes ---- (also refer to Exceeding Detection Range).
On principal the ambiguity alarm is latching and can only be reset by pressing key (or by
QUIT

MENU

pressing the AutoZero key at models without display). The measurement value must be within the
detection range.

The transmitter cannot recognize when the danger of an explosive gas


mixture resp. of an even higher gas concentration has ended. The end of a
! gas hazard has to be checked with a portable detector which was already
turned on outside the hazardous area.

Should such an alarm be triggered by a high gas concentration, make sure to check ther zeropoint and
the sensitivity of the sensor, once the alarm was reset. Take into consideration that zeropoint and
sensitivity may vary considerably during the first few days.

Sensor Life
Catalytic combustion sensors are subject to a limited lifetime. The expected lifetime of the sensor
used in the CC28 for combustible gases is approx. 3 to 5 years, depending on operational conditions.
A few months before the lifetime expires, the transmitter indicates that the sensor has to be replaced
with the next service. The message is indicated by the fault LED flashing regularly and by the the
alternating reading of CHNL
M SENS and the measurement value. If the sensor is not being replaced
within the next few months, the transmitter turns off the detection mode, when the sensor is
exhausted. The current interface provides an output of 1.2 mA, the yellow fault LED lights up and
the green operational LED shortly flashes in intervals.
Fault
-12-
A fault of the transmitters is indicated by the constantly lit yellow fault LED, the current interface
provides 1.2 mA an error message is shown in the display (SYS ERR. or SENS ERR.).
Fault report is given, if:
• the sensor or the circuitry in the transmitter is defective;
• the sensor is missing;
• the self-test of the unit recognizes a failure.
For further causes see „Special Status and relevant Error Messages“ on page 21.
After the fault is cured, the yellow fault LED expires.

Check and AutoCal Adjustment of Zeropoint (ZERO)


A prerequisite for this check is atmospheric air without disturbing, resp. interfering gas components.
In polluted atmospheres you may alternatively use zero gas, which is free from combustible
components and interfering matters. Supply the zero gas to the sensor without pressure by means of
the flow adapter, at a flow rate of approx. 0.5 l/min.
Once the type of gas has been changed or the sensor has been replaced, the zeropoint must be
adjusted correctly. If the detection mode shows a deviation from 0 the zeropoint has to be corrected
as well. When the reading is constant the adjustment can be done using the AutoCal feature. The
AutoCal program automatically adjusts the zeropoint signal.
Conditions
The automatic zeropoint adjustment by means of the AutoZero key or with the standard access code
0011 is only possible, if the currently displayed value is max. 25 % LEL.
Expert users have the possibility to activate the zeropoint adjustment even for a display of 35 % LEL
by entering the access code 0055. This access code should only be used by trained safety personnel
of the customer.
Should the current zeropoint indication be higher than a value of 35 % LEL but it is for sure that this
value is not gas induced, the sub-menu info of the service menu indicates a temporarily valid (max.
1 hour) code (Code), which allows the activation of the zeropoint adjustment without any limitations.
Note:
If the last mentioned measure becomes necessary, this might be caused by a faulty sensor, which
should be replaced as soon as possible.
Execution
When the user presses the AutoZero key at a transmitter without display he cannot see whether the
measurement value is within the allowed tolerance band for zeroing (i.e. < 25 % LEL). Should the
measurement value be higher than 25 % LEL when the AutoZero key is pressed, the transmitter
remains in detection mode – to be identified by the fact that the fault LED is not lit. In this case the
zeropoint adjustment is only possible by means of the remote control.
For quick adjustment by means of the secured AutoZero key at the left side of the casing remove the
lock screw and press the key for at least 3 seconds. This switches the current output to 2.0 mA, the
fault LED flashes slowly, and step 3 below is started automatically.
When using the keypad at the display or at the remote control, follow the order below:
1. Press key for at least 3 seconds to activate the program.
TEST

ZERO

During the whole procedure the current interface provides 2.02 mA and the fault LED
flashes slowly.
The display shortly reads CodE.
2. Enter the numeric access code 0011 (resp. 0055). Use keys and to change the
TEST INFO

ZERO SPAN

figure at the current position, then confirm by means of key .


QUIT

MENU

-13-
3. After correct entering the display shows alternating the current measurement value and the
reading ZERo. When the measurement value remains constant for a defined time interval, the
display changes to read ZERo and ADJ for a few seconds, and the hardware internally
regulates its zeropoints. Once the regulation is completed successfully, the new zeropoint is
set, the AutoCal program is automatically terminated with the display reading SAUE, and the
transmitter returns to detection mode.
Notes:
If the current measurement value is beyond the allowed tolerances for the relevant access code, the
display reads fAi L shortly in step 3, and the transmitter returns to detection mode.
The AutoCal program can be shortened by long-term pressing key or the AutoZero key, while the
TEST

ZERO

measurement value is checked for constancy. Then the hardware starts to regulate/adjust the zeropoint
directly.
For leaving the AutoCal program without zeropoint adjustment, press key or the AutoZero key
TEST

ZERO

briefly. The display shortly reads ESC.

Once the quick adjustment is completed, remember to screw the lock screw
! and its gasket in again to its stop!

The following error message may occur during zeropoint adjustment:

Display Meaning Fault LED


CAL Gas signal is unstable.
ERR.2 flashing
CAL Zeropoint is beyond the allowed tolerance quickly
ERR.3 range.

All error message have to be confirmed with or with the AutoZero key at the left side of the
QUIT

MENU

casing. After confirmation the transmitter returns to detection mode without zeropoint adjustment.

Check and AutoCal Adjustment of Sensitivity (SPAN)


For calibration of a transmitter without display you need the remote control RC2.
Press key briefly to read the currently set calibration gas concentration as % LEL (for ammonia
INFO

SPAN

as Vol.%) of the parameter (CL MAS). The value of the test gas concentration should, if possible, be
20% above the main alarm threshold.

Many combustible gases are also toxic. Handling toxic gases requires special

! safety precautions.
TLVs give hints for hazards caused by toxic gases. For particularly toxic matters,
e.g. benzene or ethylene oxide, a reference gas is recommended for calibration.

For checking, resp. adjusting the display sensitivity (span) a calibration adapter has to be attached to
the sensor holder. Via this adapter the calibration gas can be supplied to the sensor at atmospheric
pressure with a flow of approx. 0.5 l/min., while the display has to be observed. Is there a deviation
between the displayed value and the actual calibration gas concentration a span calibration is
necessary. If the reading is constant the adjustment can be done using the AutoCal feature. The
AutoCal program automatically adjusts the measuring signal to the calibration gas. Follow the order
below:
→ Before a calibration is started, make sure that the sensor is free from calibration gas
(display 0).
-14-
1. Press key for at least 3 seconds to activate the AutoCal program. During the whole
INFO

SPAN

procedure the current interface provides 2.0 mA and, the fault LED flashes slowly. The
display shortly reads CodE.
2. Now enter the numeric access code 0011. Use keys and to change the figure at the
TEST INFO

ZERO SPAN

current position, and confirm by means of key .


QUIT

MENU

3. After correct entering, the display shows the current measurement value and the message
SPAN alternately. The transmitter now waits for a clear rise of concentration. When the
measurement value remains constant during a defined time interval (after a fixed time of
2 minutes), the value is used to update the sensitivity (display SAUE). This updates the
calibration data successfully. The transmitter, however, does not return to detection mode yet,
since the presently supplied test gas concentration would activate an alarm. The transmitter
remains in calibration mode until it recognizes a falling gas concentration and then a
stabilization of the display value. The display alternately reads ZERo and the current
measurement value. Once the value has stabilized, the transmitter returns to detection mode.
If the unit does not notice a reduced gas concentration resp. a stabilized measurement value, it
returns to detection mode after max. 3 minutes.
At any time the AutoCal program can be shortened by long-term pressing key . The display
INFO

SPAN

shortly reads SAUE and the measurement value is accepted directly as the sensitivity update.
To leave the AutoCal program without sensitivity adjustment, press key only briefly. The
INFO

SPAN

display shortly reads ESC.

The following error messages may occur during the adjustment:

Display Meaning Fault LED


CAL No rise of test gas concentration noted.
ERR.1
CAL Test gas signal is unstable. flashing
ERR.2 quickly
CAL Sensitivity is beyond the allowed tolerance
ERR.3 range.

The error messages have to be confirmed with key . The transmitter returns to detection mode
QUIT

MENU

without new calibration. The calibration procedure has to be repeated.

Service Menu and Extended Service Menu


Activation of service menu
The service menu allows to select and to change all important parameters of the CC28. Entering the
service menu interrupts the detection mode; the transmitter turns to service mode, and the alarms are
de-activated. The special status "Service" is indicated by the fault LED flashing slowly and by a
current output signal of 2.4 mA. If you do not hit any key within one minute, the transmitter
automatically leaves the service mode and returns to detection mode.
All parameters changed in the service menu refer to the currently set type
of gas !
! Should you wish to change type of gas and parameters, set the new type of gas first,
before parameter changes for this gas can become effective.

The service menu can be called in two different extensions.

-15-
The standard service menu is activated with code 1100 . It allows to adjust the calibration gas
concentration and, with model CC28 DA, all values which are related to alarms.
The extended service menu is activated with code 5050 . It allows to also change the type of gas,
full scale and ambiguity alarm. This code should only be used by specially trained safety personnel.
Activation of the extended service menu is only possible, if it has been authorized by GfG during the
basic setting of the transmitter.
For transmitters with function test (labelling BVS 05 ATEX G 001 X): The extended
service menu allows adjustments which may become the function test void !
! If the full scale value of 100 % LEL is changed to a different value, or if the gas is
changed from a certified gas (see page 3) to a non-certified one, the function test becomes
invalid.

When using the keypad at the display or at the remote control follow the order below:
1. Press key for at least 3 seconds. The transmitter turns to service mode. The display shortly
QUIT

MENU

reads CodE.
2. Enter the numeric code1100 (resp. 5050). Use keys and to change the figure at the
TEST INFO

ZERO SPAN

current position and confirm with key .


QUIT

MENU

3. After correct entering the menu display reads L


MAS. Use keys and to select the other
TEST INFO

ZERO SPAN

menu points.

To activate a selected menu point press key briefly. For parameter adjustment use keys
QUIT

MENU

and . For leaving the menu point briefly press key again.
TEST INFO QUIT

ZERO SPAN MENU

Display of Description Remark


INFO menu point

SPAN Indication of software version, serial number


iNFo and "Code" for ruling code
F2 Setting of alarm function 2

F1 Setting of alarm function 1

H2 Setting of hysteresis for alarm 2 only visible and


changeable for
H1 Setting of hysteresis for alarm 1 model CC28 DA
A2 Setting of alarm threshold 2

A1 Setting of alarm threshold 1

CL
MAS Setting of calibration gas concentration

AM"B. Setting of automatic reset for ambiguity alarm


Setting of full scale deflection changeable only in
SCAL extended menu.
Entry
L
MAS Change of gas
menu point
Leaving the service menu with storing of the
TEST SAUE changed parameters
ZERO Leaving the service menu without storing of
ESC the changed parameters

Menu point L
MAS – Change of type of gas (only possible in extended menu)
-16-
This function allows to select explicitly all parameters for different types of gas, which are stored in
the sensor. You can see only those gases which the sensor is scheduled for.
1. Activate of menu point L
MAS.
2. The display shows the presently set type of gas.
This reading can also be selscted in the standard service menu.
3. Use keys and to set the gas.
TEST INFO

ZERO SPAN

In the standard service menu the display shortly reads fAi L and then the presently set
type of gas (step 2).
4. Select the desired type of gas and confirm by pressing key briefly.
QUIT

MENU

5. The CC28 is re-starting (RSET) (only for selection of a different gas).

If the type of gas has been changed several times before the user returns to a gas which was already
parameterized before, the transmitter takes over those parameters which were stored by the user
before.

If the type of gas has been changed and after a restart, the stored standard parameters (see table on
page 30) are taken over for a type of gas which is selected for the first time.
When the type of gas was changed, the zeropoint has to be adjusted in any case by means of the
AutoCal function. The sensitivity of the sensor for the new gas is to be checked as well and to be
adjusted by means of the AutoCal function, if necessary.
The different gases will be indicated either as shown in the list below.

Display Gas Display Gas Display Gas

AcTN Aceton C7H8 Toluene i.BvT Iso-Butane

BvT. n-Butane CH4 Methane M"EAc Methyl acetate

BToL Butanol c.HEN Cyclohexane M"EoL Methanol

BToN 2-Butanon DEE. Diethyl ether M"iB. MIBK

C2H2 Acetylene DM"E. Dimethyl ether NH3 Ammonia

C2H4 Ethylene EtAc Ethyl acetate non. Nonane

C2H6 Ethane EToL Ethanol Oct. Octane

C3H4 Propine H2 Hydrogen PnT. Pentane

C3H6 Propylene HEN. Hexane ProL 2-Propanol

C3H8 Propane HPt. Heptane YLoL Xylene

C6H6 Benzene

Menu point SCAL – Adjustment of full scale deflection (only possible in extended menu)
The detection range can be set to 50, 75 or 100 % LEL. The detection range for ammonia (4 Vol.%)
cannot be changed.
Follow the 5 steps described below:
1. Activate menu point SCAL.
2. The display shows the presently set full scale value.
In the standard service menu the display reads "100" for 100 % LEL.
3. Use keys and for parameter adjustment.
TEST INFO

ZERO SPAN

-17-
In the standard service menu the display shortly reads fAi L and then the current value (step
2).
4. For leaving menu point SCAL press key briefly.
QUIT

MENU

5. If necessary, store the parameter (SAUE).

Notes:
The EC-Type Examination Certificate BVS 05 ATEX G 001 X is only valid for a detection range
with a full scale of 100 % LEL resp. 4.00 %Vol. NH3.
If the full scale value is changed from 100 % LEL to a different value, the function test becomes
invalid.
The change of the detection range is mainly a change of the current output. The standardized output
signal of 4 – 20 mA is used for the new, reduced detection range. The display indication does not
change. A detection range of 0 – 50 % LEL results in the figures from 0 to 50.0 in the display (i.e. the
reading remains at % LEL).
Overrange and underrange refer to a percentage of the detection range, i.e. with a detection range of
0 – 50 % LEL the ambiguity alarm is triggered at approx. 56 % LEL ! Alarm thresholds are indicated
in % LEL (not in % of detection range) !
After a reduction of the detection range make sure that the alarm thresholds are checked and, if
necessary, corrected. If alarm thresholds were adjusted to a value beyond the new full scale
deflection, they are automatically set to the current full scale value.
Should the circuitry recognize that the currently set detection range cannot be monitored any longer
(sensor too sensitive for the measurement circuit, see also SCAL ERR.), the display turns
automatically to the highest possible value when entering this menu point.

Menu point AM"B. – Adjustment of the automatic reset of the ambiguity alarm (only possible in
extended menu)

1. Activate menu point AM"B.


2. The display reads the presently set status (oN or oFF).
This display can also be retrieved in the standard service menu.
3. Use keys and for setting the parameter.
TEST INFO

ZERO SPAN

In the standard service menu the display shortly reads fAi L and then the current status (step
2).
4. Press key briefly to leave menu point AM"B. .
QUIT

MENU

5. If necessary, store the parameter (SAUE).

For the proper functioning of the automatic reset of the ambiguity alarm
! the zeropoint adjustment of the CC28 must have been done correctly.

Notes:
This function is only active for the gases methane, propane and hydrogen. Should adjustment
AM"B. oN be selected, but none of the above gases is measured, the display order does not include the
reading AM"B. after pressing the info key.
The activation of the automatic reset is blocked until the next zeropoint adjustment, if the sensor has
been replaced or if the type of gas has been changed in the extended service menu !
As Info the display reads: AM
"B. -oN- instead of AM"B. oN.
-18-
The final reset is only enabled after a zeropoint adjustment has been done with the sensor plugged in.

Menu point CL MAS – Adjustment of calibration gas concentration


The calibration gas concentration can be set within the range of 10 % – 105 % of the current
detection range, but never higher than 85 % LEL.
1. Use key to select menu point CL
MAS .
QUIT

MENU

2. The display reads the currently set value for the calibration gas concentration in % LEL (for
ammonia in Vol.%).
3. Use keys and to set the parameter.
TEST INFO

ZERO SPAN

4. Press key briefly to leave menu point CL


MAS .
QUIT

MENU

5. If necessary, store the parameter: Select menu point SAUE and confirm with .
QUIT

MENU

Menu point A1, A2 – Adjustment of alarm thresholds (only visible at model CC28 DA)
The alarm thresholds can be set throughout the detection range; A1, however, cannot be set to a
higher value than A2. Setting a threshold to 0 de-activates the alarm. A2 can only be set to 0 when
A1 was also set to 0 before.
1. Activate menu point A1 resp. A2.
2. The display reads the presently set value for the alarm threshold.
3. Use keys and to set the parameters .
TEST INFO

ZERO SPAN

4. Press key briefly to leave menu point A1 resp. A2 .


QUIT

MENU

5. If necessary, store the parameter (SAUE).


Notes:
The buzzer in model CC28 DA is always connected to alarm 2.

Menu point H1, H2 – Adjustment of hysteresis (only visible at model CC28 DA)
This function allows to adjust the hysteresis, i.e. the difference between activation and de-activation
of the alarm thresholds. The setting of the parameter is done in % LEL and is restricted to max. 5 %
LEL (for ammonia in Vol.%, max. 0.2 Vol.%).
Example:
At a CC28 with the detection range 0 .. 100 % LEL the hysteresis for alarm 1 was set to 4.0, i.e. the
alarm de-activation point for the alarm is 4 % LEL below the alarm threshold.
This results in the following alarm triggering:

Alarm 1 = 10 % LEL
Alarm activation ≥ 10 % LEL
Hysteresis H1 3 % LEL
Alarm de-activation ≤ 7 % LEL

1. Activate menu point H1 resp. H2.


2. The display reads the presently set value for the alarm hysteresis.
3. Use keys and to set the parameter.
TEST INFO

ZERO SPAN

4. Press key briefly to leave menu point H1 resp. H2 .


QUIT

MENU

5. If necessary, store the parameter (SAUE).

-19-
Menu point F1, F2 – Adjustment of alarm functions (only visible at model CC28 DA)

1. Activate menu point F1 resp. F2.


2. The display reads the presently set code for the alarm function.

Display Alarm for exceeded threshold ...


NS non-storing (= non-latching), not resettable (# at alarm 2)
SC storing (= latching), resettable when fallen below

3. Use keys and for setting the parameter.


TEST INFO

ZERO SPAN

4. Press key briefly to leave menu point F1 resp. F2 .


QUIT

MENU

5. If necessary, store the parameter (SAUE).


Note:
The buzzer function at model CC28 DA is fixed to: „Alarm for exceeded threshold, non-latching,
resettable even during existing alarm conditions“.
The EC-Type Examination Certificate BVS 05 ATEX G 001 X is valid at alarm 2 only if set to
„S C“ storing (=latching).

Menu point iNFo – Indication of sensor type (MK number), sensor serial number, software
version, serial number and code
1. Activate menu point iNFo.
2. One after the other the display reads the MK number (S.typ xxx), the sensor serial number
(S.nr xxxx), the software version (SoFT xxxx), the 8-digit serial number of the transmitter in
2 parts (F.nr- xxxx F.nr_ xxxx) and a code (CoDE xxxx).
The figure indicated as CoDE is a (only temprorarily valid) code, which allows the activation of the
zeropoint adjustment without any limitations (refer to Check and AutoCal Adjustment of Zeropoint).

Menu point ESC – Leaving the service menu without storing


1. Select menu point ESC.

1. 2. Press key briefly to leave the service menu without storing of parameter
QUIT

MENU

changes.

Menu point SAUE – Leaving the service menu with with storing

1. Select menu point SAUE.


2. Press key briefly to leave the service menu with storing of parameter changes.
QUIT

MENU

Notes:
When the type of gas is changed, confirming the menu point activates the storing immediately and
enables the parameters for this type of gas.
Apart from this exception you can change several parameters one after the other without storing in between.
One collective storing procedure at the end of the settings saves all parameters which have been changed in
the service menu.

-20-
Sensor Replacement
The sensors MK 208-1, MK 217-1 and MK 218-1 are supplied with an EEPROM which stores the
sensor data (serial number etc.), the calibration data and the adjustable types of gases. The sensors are
fit to the transmitter by means of a plug connector.
For replacing the sensor unscrew the allen screw side-mounted at the impact protection (see picture
on page 5 sensor casing). Open the Transmitter casing and use suitable tool to push the sensor
downward. The new sensor slides in the casing from below; the sensor label must show forward. The
transmitter provides a lock against rotation, which makes sure that the sensor always fits properly.
Once the sensor is locked in place, secure it with the allen screw. When opening the casing take note
of the safety measures in Ex areas (see page 7).
Once the sensor has been removed, the yellow fault LED lights up and the current output signal falls
to 1.2 mA. At model CC28 D and DA the display reads SENS ERR.1 , and at the CC28 DA the alarm
LEDs flash slowly.
When the new sensor has been fit, the transmitter does an automatic re-start. The display reads RSET
and then TEST (memory test; current output signal of 0 mA). Then the warm-up period is started:
The display reads LoAd , the green LED flashes and the current interface provides an output signal of
1.6 mA. If all data of the new sensor match the stored data for the measurement task, the transmitter
turns automatically from warm-up to detection mode. Since the hardware zeropoints of the different
sensors resp. sensor types may differ considerably, a sensor replacement must always be followed by
a zeropoint adjustment ZERo (see page 11). There are no restrictions for the first zeropoint
adjustment after a sensor replacement. Zeroing is even possible at values far beyond the detection
range (____ resp. ----).

Possible error messages CHEC L


MAS or CHEC SCAL
CHEC L MAS During the warm-up period the transmitter recognizes, if the new sensor is not specified
for the gas which is set as the measurement gas. The green LED turns from flashing slowly to a twin
flash (2 short flashes). The yellow fault LED remains lit, the current output still provides 1.6 mA, and
the display reads CHEC L MAS . If the transmitter is to detect that gas which has been set, the sensor is
to be replaced by a cell which is suitable for this gas (e.g. sensor MK 217-1 by sensor MK 208-1).
Should you want to use the new, different sensor anyway (e.g. as a preliminary solution), you may
press key (longer than 3 seconds) in fault status and enter the acces code 5050 to enter the
QUIT

MENU

extended service menu (see page 14/15); menu point L MAS (appears immediately after the code)
shows the types of gases the new sensor is specified for. If the user selects a type of gas and confirms
his choice by pressing key , the transmitter is converted to this gas and re-started. Then the
QUIT

MENU

zeropoint ZERo and the sensitivity SPAN have to be set for the new type of gas (see page 11-14).

CHEC SCAL New sensors, no matter for which gas, are always pre-set to the detection range of 0 –
100 % LEL. During the warm-up period the transmitter recognizes, if the detection range which was
set last, and the pre-setting of the sensor for the measurement gas do not match. The green LED turns
from flashing slowly to a twin flash (2 short flashes). The yellow fault LED remains lit, the current
interface still provides 1.6 mA, and the display reads CHEC SCAL . For check and, if required,
change of the detection range setting directly from the fault status, you may press key (longer
QUIT

MENU

than 3 seconds) and enter the code 1100 or 5050 to enter the service mode (see page 14/15), which
allows to do the adjustment under menu point SCAL. After leaving the menu with SAUE the warm-
up procedure is continued.
Example:
If the detection range SCAL was set to 50 % or 75 %, a new and unused sensor will cause the display
to read CHEC SCAL .

-21-
If the transmitter is set to 100%, but the fit sensor had already been used in another unit which was
set to 50 % or 75 %, the display will also read CHEC SCAL .
Notes:
After the sensor was put into operation for the very first time, or when the sensor has been replaced,
the transmitter may indicate an overrange resp. underrange (____ resp. ----). In this case the
automatic zeropoint adjustment (ZERO) has to be activated to correct the zeropoint.
Should SCAL ERR. occur (resettable), the sensor must be re-calibrated (SPAN) or, if necessary, the
detection range of the sensor must be adapted to the hardware in the service menu.
Allow a warm-up time of at least 30 minutes before you check the zeropoint. Once the warm-up is
completed, the display should have stabilized to read 0. Otherwise activate the (automatic) zeropoint
adjustment (Adjustment see page 11).

Once the sensor was replaced (no matter which service and adjustment interval is
being considered), you have to effect a complete service and adjustment according to
! DIN EN 50073 para. 6.4.3.

Check and adjustment of zeropoint and sensitivity is to be done as described (pages


11-14).

Transmission Characteristics
Depending on the type of gas the transmitter is subject to different transmission characteristics.
Different gases may show different response times. The transmission signal is always proportional to
the gas concentration

-22-
Special Status and relevant Error Messages
The table below describes those special status which cause the yellow fault LED to be lit
permanently. For a better diagnosis of a transmitter without display you should either read the error
messages below from the remote control RC2 or analyse the values from the current output.
green yellow
No Display
LED LED
Output Cause Action
01 "TEST" On On 0 mA Memory test when booting the system finishes automatically after 6
seconds
02 "Load" flashing On 1,6 mA Booting the system at start or after turns to sensor warm-up
Operational change of gas (see page 8) automatically
para.
" AdJ "
03 Countdown flashing On 1,6 mA Sensor warm-up period finishes automatically after 120
of seconds seconds.
10 "TEST" Off glows 0 mA Too low supply voltage increase supply voltage
flashing
11 "CHNL
M" flashing On 1,2 mA Sensor lifetime expired Replace sensor
"SENS" shortly
(single
flash)
12 "CHEC" Twin On 1,2 mA After sensor replacement: Replace sensor again or
"L flash Sensor is not specified for the gas select different gas; see page 19
MAS "
„Sensor Replacement“
13 "CHEC" Twin On 1,2 mA After sensor replacement: Check and, if necessary, change
"SCAL" flash Detection range setting of sensor and detection range SCAL
transmitter do not match for the gas See page 19 „Sensor Replacement“
14 " SYS " Off On 1,2 mA Fault during RAM access Re-start transmitter. If error is
"ERR.1" reported again, replace transmitter
15 " SYS " Off On 1,2 mA Fault during ROM access Re-start transmitter. If error is
"ERR.2" reported again, replace transmitter
16 " SYS " Off On 1,2 mA Fault during EEPROM access (internal) Re-start transmitter. If error is
"ERR.3" reported again, replace transmitter
17 " SYS " Off Off 1,2 mA Reserved Re-start transmitter. If error is
"ERR.4" reported again, replace transmitter
18 " SYS " " SYS " On 1,2 mA Fault during regulation of sensor voltage
"ERR.5" "ERR.5"
19 Off Off On 1,2 mA Fault during regulation of hardware Re-start transmitter. If error is
zeropoint reported again, replace transmitter
20 " SYS " Off On 1,2 mA Temperature measurement is not
"ERR.7" plausible
21 "SENS" "SENS" On 1,2 mA Sensor is missing
Fit sensor (automatic re-start)
"ERR.1" "ERR.1"
22 "SENS" Off On 1,2 mA Fault during EEPROM access (sensor) Replace sensor (automatic re-
"ERR.2" start)
23 "SENS" Off On 1,2 mA Wrong sensor/parameter memory
"ERR.3"
24 " ADv " Off On 1,2 mA Error A/D converter (sensor voltage) Re-start transmitter.
"ERR.1" If error is reported again, replace
transmitter.
25 " ADv " " ADv " On 1,2 mA Error A/D converter (NTC) Re-start transmitter.
"ERR.2" "ERR.2" If error is reported again, replace
transmitter.
26 " ADv " Off On 1,2 mA Error A/D converter (sensor current) Re-start transmitter.
"ERR.3" If error is reported again, replace
transmitter.

-23-
Messages in detection mode
green yellow
No Display Output Cause Action
LED LED
30 " ---- " On flashing 22 mA Gas concentration has exceeded Caution Explosion hazards!
permanent quickly detection range of transmitter Latching alarm. Measures see page
electronics. Ambiguity alarm! 9 and 10
31 " ---- " On flashing 22 mA Overrange (> 112 %) Caution Explosion hazards!
flashing quickly Ambiguity alarm! Latching alarm. Measures see page
9 and 10
32 Value On Off 20–22 mA Overrange Caution Explosion hazards!
alternating with (between 100 % and 112 %)
" ---- "
33 Value On Off 4–20 mA Gas concentration has reached resp. Reduce gas concentration!
alternating with exceeded the 2.alarm threshold. Latching alarm as standard.
" A2 "
34 Value On Off 4–20 mA Gas concentration haa reached resp. Reduce gas concentration!
alternating with exceeded the 1.alarm threshold. Non-latching alarm as standard.
" A1 "
35 Value On Off 4–20 mA Cautionary warning message: QUIT
Reset with
Hardware/sensor combination cannot
MENU
alternating with
a) Re-calibrate sensor (SPAN)
"SCAL" recognize full scale deflection
b) Adapt resp. Reduce detection
" ERR." range in service menu.
36 Value On flashing 4–20 mA Cautionary warning message: Replace sensor during next service
alternating with shortly End of sensor life within the next few
"CHNLM" (single months
"SENS" flash)
37 Value On Off 4–20 mA Normal detection mode
38 Value On Off 2.8–4 mA Detection range is deviated between
-7.5% and 0.0%
39 Value On On 2.8 mA Detection range is deviated between Adjust zeropoint
alternating with -8.0% and –25.0%
" ____ "
40 " ____ " On On 2.8 mA Detection range is deviated Adjust zeropoint and sensitivity
permanent < -25.0%
41 " ____ " On On 1.2 mA Measuring signal has fallen below Adjust zeropoint and sensitivity
permanent detection range of transmitter
electronics.

Messages in service mode and during calibration


42 Menu point On flashing 2.4 mA Service menu has been activated by Select menu point
keys or by remote control RC2 Will return to detection mode
automatically, if no entry is
made within 1 minute
43 "ZERo" On flashing 2.0 mA AutoCal-Adjustment of zeropoint in Will be completed automatically
process (activated by key pad, RC2 or after successful adjustment
by AutoCal-Key)
44 "SPAn" On flashing 2.0 mA Calibration activated by keys or RC2 Will be completed automatically
after successful adjustment
45 " CAL " On flashing 2.0 mA During AutoCal adjustment of QUIT
Reset with
quickly sensitivity no rise of calibration gas
MENU
"ERR.1" a) Check gas supply
concentration was recognized
b) Wait for request for adjust-
ment before supplying gas
46 " CAL " On flashing 2.0 mA During AutoCal adjustment no stable QUIT
Reset with
quickly zero gas resp. calibration gas
MENU
"ERR.2" Stabilize gas supply
concentration was recognized
47 " CAL " On flashing 2.0 mA The zero point resp. the sensitivity is QUIT
Reset with
quickly beyond the range of tolerance
MENU
"ERR.3" a) Check zero resp. calibration gas
and repeat procedure.
b) Eventually replace sensor.
-24-
In detection mode the messages listed in the second column are indicated alternating with the
measurement value. The readings described in No.33 and 34 are only applicable for model CC28
DA. The readings described in No.35 and 36 are cautionary warning messages. The transmitter
remains in detection mode, and there is no immediate action required by the user. The status
described in No.32 and 38 refer to a de facto extension of the detection range from 4–20 mA to the
range 2.8–22 mA, for showing measurement values „close“ to the original detection range. This
generates a tolerance range around the 4–20 mA signal, before a special status occurs.

Situation of Status LED’s and Output


The following table shows for a transmitter without display the different indications of the two status
LEDs and the output signals with their meanings.
For the zeropoint adjustment (if display > 25 % LEL), for adjustments to enter the service menu on a
transmitter without display the remote control RC2 is obligatory.
green LED yellow LED Output Desription see chapter...
On On 2,8 mA Page 21 „Messages in detection mode“ No.39, 40
On On 1,2 mA P.21 „Messages in detection mode“ No.41
On On 0 mA P.21 „Special Status and relevant Error Messages“ No.01
On flashing quickly 22 mA P.21 „Messages in detection mode“ No.30, 31
On flashing quickly 2,0 mA P.21 „Messages in service mode...“ No.45-47
On Flashing slowly 2,4 mA P.21 „Messages in service mode...“ No.42
On Flashing slowly 2,0 mA P.21 „Messages in service mode...“ No.43, 44
On Single flashes 4–20mA P.21 „Messages in detection mode“ No.36
On Off 20–22mA P.21 „Messages in detection mode“ No.32
On Off 4–20mA P.21 „Messages in detection mode“ No.(33, 34), 35, 37
On Off 2,8–4mA P.21 „Messages in detection mode“ No.38
flashing On 1,6 mA P.21 „Special Status and relevant Error Messages“ No.02, 03
Twin flash On 1,2 mA P.21 „Special Status and relevant Error Messages“ No.12, 13
Single flash On 1,2 mA P.21 „Special Status and relevant Error Messages“ No.11
Off On 1,2 mA P.21 „Special Status and relevant Error Messages“ No.14-26

Priority of displays and messages in detection mode


The displays of situations with low priority will be substituted for displays with higher priorities (the
situations with low priority will not be deleted).
Priority Situation Description see chapter...
Ambiguity Page 22 „Messages in detection mode“ No.30, 31
A/D converter fault P.21 „Special Status and relevant …“ No.24-26
(minor) overrange P.22 „Messages in detection mode“ No.32
Alarm2 P.22 „Messages in detection mode“ No.33
Alarm1 P.22 „Messages in detection mode“ No.34
Detection range deviation P.22 „Messages in detection mode“ No.38-40
„SCAL-Error“ (Warning) P.22 „Messages in detection mode“ No.35
Sensor Replacement (Warning) P.22 „Messages in detection mode“ No.36
System- and sensor errors (P. 21, 22 No. 11 und No. 14-23) will interrupt the detection mode with its
messages. In case of a prior ambiguity alarm the status LEDs and the output will still indicate it and
the new special status will be indicated only by the LCD display.

Putting into Operation and Maintenance


Make sure that DIN EN 50073 „Guideline for choice, installation, use and maintenance of apparatus
for detection and measurement of combustible gases or oxygen“ as well as the relevant national
regulations are adhered to. For Germany this means the "Explosion Protection Regulations",
guideline T023 (BGI 518) „Gas warning Apparatus for Explosion Protection – Use and Operation“
and UVV-Gase BGV B6 „Accident Prevention Regulations Gases“.
-25-
After installation and during the initial putting into operation gas warning equipment have to be
checked for function by an expert (see DIN EN 50073 section 6.4.1)
Maintenance comprises inspection, service, calibration and adjustment as well as the regular function
tests and repair.
A function test has to be effected before putting the transmitter into operation and at least once a
year. This test comprises:
• Check with alarm gas concentration
• Check of zeropoint and sensitivity (calibration)
• Response time
• Gas sampling system, gas processing (if any)
• Alarm signal activation
• Messaging devices for malfunctions
The test must be carried out by a specialist. The result must be noted in a written test report.

Service, Inspection, Calibration and Adjustments


Inspection shouls include a visual check of the gas warning equipment (for Germany see guideline
T 023, chapter 8.1).
• Mechanical damage
• Soiling by dust
• Condensate by moisture
• Protective devices for transmitter
• Diffusion inlet of transmitter
• Gas sampling system, gas processing system (if existing)
Service and inspection comprise all measures which are necessary to keep the original proper
working condition of the gas warning system. The inspection intervals must not exceed 4 months.
• Zeropoint
• Sensitivity with calibration gas
• Triggering of alarm thresholds
• Response time
• Messaging functions visually and audibly
• Failure messages
Service and inspection include a regular check and adjustment of sensitivity and zeropoint. The
proper functioning of the system is to be checked as well.
It is recommended to entrust GfG service with this task.

Regular Function Tests


Depending on the ambient conditions gas warning systems may behave differently. It is important,
therefore, to do a daily visual check particularly during the first few days after the initial putting into
operation.
In addition to the maintenance work the function of the gas warning system has to be checked in
regular intervals. This interval must not exceed 1 year (for Germany see guideline T023, chapter 8.5
and UVV-Gase §56)
Checks are to be effected by an expert, and the result have to be confirmed in writing.

Repair
Repair comprises all repair and replacement work. It must only be done by the manufacturer and by
persons who are authorised by the manufacturer – i.e. by GfG Gesellschaft für Gerätebau mbH. Only
original spare parts and original assemblies are allowed to be used, which are tested and authorised
by the manufacturer.

-26-
Function Restrictions depending on Oxygen Concentration
Take note, that the measurement of gas and/or vapour concentrations in the range up to 100 % LEL
cannot be done accurately, if simultaneously the oxygen concentration is less than 10 Vol. %. In this
case the pellistor suffers from a lack of oxygen necessary for the „catalytic combustion“.
The Ex approval is not valid for using the transmitter in oxygen enriched atmospheres with
concentrations of more than 25 Vol.% oxygen.

Display Irritation due to Sensor Poisons


Certain parameters, known as "sensor or catalyst poisons", may affect the signal behaviour of the
sensor. The "sensitivity", i.e. the capability to emit signals, is being reduced. Sensor poisons are e.g.
sulphur, lead and silicon vapours. Usually these components are found very rarely or in very low
concentrations only.
Please draw your special attention to any interfering gases, which might be present at your detection
place and which might affect the proper functioning of your gas monitoring system. Depending on
the type of gas and its concentration, this affect may result in failures like a more or less steady, long-
term loss of sensitivity or even to a sudden and considerable drop of sensitivity (see also
DIN EN 50073).

Trouble Shooting
Failure Cause Solution
Zeropoint cannot be adjusted Sensor is faulty Replace sensor
Sensitivity cannot be adjusted Sensor is faulty Replace sensor
Output current is fallen to 0 mA Fuse is blown Replace fuse
Line is interrupted Re-connect

Lower Explosion Limits (LEL) of Gases subject to Function Test


Gas Formula LEL as per EN 61779 LEL as per data base
Function test Chemsafe
Methane CH4 4.4 Vol% 4.4 Vol%
Propane C3H8 1.7 Vol% 1.7 Vol%
Hexane C6H14 1.0 Vol% 1.0 Vol%
Nonane C9H20 0.7 Vol% 0.7 Vol%
Toluene C6H5-CH3 1.1 Vol% 1.2 Vol%
Aceton CH3-CO-CH3 2.5 Vol% 2.5 Vol%
Hydrogen H2 4.0 Vol% 4.0 Vol%
Ethylene CH2=CH2 2.3 Vol% 2.4 Vol%
Diethyl ether C2H5-O-C2H5 1.7 Vol% 1.7 Vol%
Ethyl acetate CH3-COO-C2H5 2.2 Vol% 2.0 Vol%
Isopropanol CH3-CHOH-CH3 2.0 Vol% 2.0 Vol%
Ammonia NH3 15.0 Vol% 15.4 Vol%

-27-
Spare Part List

Part-No.
Cap and minor parts for 5 units 2800301
Casing top screws for 5 units 2800302
Casing bottom for CC28 2800303
Casing top with display for CC28 D and CC28 DA 2800304
Casing bottom without buzzer for CC28 and CC28 D 2800305
Casing bottom with buzzer for CC28 DA 2800306
Main module without alarm (Um=45V) for CC28 and CC28 D 2800307
Main module without alarm (Um=250V) for CC28 and CC28 D 2800308
Main module with alarm (Um=45V) for CC28 DA 2800309
Main module with alarm (Um=250V) for CC28 DA 2800310
Display module without alarm for CC28 D 2800311
Display module with alarm for CC28 DA 2800312
MK 208-1 Spare sensor for combustible gases 2800750
MK 217-1 Spare sensor for combustible gases 2800751
MK 218-1 Spare sensor for combustible gases on request

Accessories
Part No.
Remote control RC2 2800201

Calibration adapter (flow rate 0.5 l/min ±0.1 l/min) 2800202

Wind protection 2800204

Wheather protective casing (#) on request


Spare parts and accessories should be stored at an ambient temperature of 0 – 30°C. Storing time
should not exceed 5 years. For storage of spare sensors make sure that the ambient atmosphere is free
from aggressive media and sensor poisons.

-28-
Connection Diagram CC 28 - with 4 .. 20 mA Output

brown
1
green 2
3
white 4

Shield laid on
screwing
24 V GND 4 – 20mA
GMA101 5 1 2
GMA100 5 1 2 with motherboard
from 1997
GMA104 55 53 54 connection to
58 56 57 multiplexer
61 59 60
64 62 63
GMA301 5 1 2
GMA304 55 53 54 connection to
58 56 57 multiplexer
61 59 60
64 62 63
GMA41 28 29 30
GMA81 (A) 1 2 3
GMA43 19 20 21 connection of up to 3
22 23 24 transmitters
25 26 27
19 20 21 connection of up to 4
GMA44 and transmitters
22 23 24
GMA84 25 26 27
28 29 30
GMA88 19 20 21 connection of up to 8
: : : transmitters
40 41 42

For connection to the GMA … controller please refer to the operation manual of the relevant GMA.

According to EN 50014 table 4 for devices of group II the casing has been tested
! with an impact energy of 4 Joule (low degree of mechanical danger).
Protect the casing against very hard impacts.

-29-
Terminal Diagram MWG CC28

3 – wire connection

1
U= 15.0 V - 30.0 V *

2 CC28

R1 3
I = 4 - 20 mA
4

Max. load 150 Ohm

4 – wire connection

1
U= 15.0 V - 30.0 V *
2 CC28

3
R1
I = 4 - 20 mA
4

Max. load 150 Ohm

* A voltage exceeding the max. allowed value of 30 V


DC (even short-term voltage peaks)
will blow the protective fuse.

-30-
Sensor specification

MK208-1 Catalytic combustion sensor for combustible gases and vapors (according to EN 61779-4)
Response time t50: ≤ 5 s (CH4), ≤ 5 s (C3H8), *1 with wind protection: ≤ 8 s (CH4), ≤ 8 s (C3H8), *1
t90: ≤ 9 s (CH4), ≤10 s (C3H8), *1 with wind protection: ≤15 s (CH4), ≤17 s (C3H8), *1
Flow rate 0...6m/s: max. ±3% of detection range or ±10% of display (regarding to 0 m/s) *2, *4
Pressure 800...1100 hPa: max. ±3% of detection range or ±7% of display (regarding to 1000 hPa) *4
Humidity 5%...90% r.F.: max. ±5% of detection range or ±10% of display (regarding to 50% r.F. and 40°C) *4
Temperature -25...+55°C: max. ±5% of detection range or ±15% of display (regarding to 20°C) *4
Cross sensitivities Methane – Measuring range (#) *3 Propane – Measuring range *3 Nonane – Measuring range (#) *3 .
at 50%LEL: . . 0,35 %Vol. C9H20: = 100%
2,20 %Vol. CH4 : = 100% 0,85 %Vol. C3H8 : = 100% 2,00 %Vol. H2 : ca.328%
2,00 %Vol. H2 : ca.131% 2,00 %Vol. H2 : ca.160% 1,25 %Vol. C3H6O: ca.231%
1,25 %Vol. C3H6O: ca. 97% 1,25 %Vol. C3H6O: ca.111% 2,20 %Vol. CH4 : ca.224%
1,15 %Vol. C2H4 : ca. 96% 2,20 %Vol. CH4 : ca.107% 1,15 %Vol. C2H4 : ca.213%
0,85 %Vol. C3H8 : ca. 96% 1,15 %Vol. C2H4 : ca.101% 0,85 %Vol. C3H8 : ca.210%
1,10 %Vol. C4H8O2: ca. 92% 1,10 %Vol. C4H8O2: ca. 95% 1,10 %Vol. C4H8O2: ca.201%
1,00 %Vol. C3H8O: ca. 87% 1,00 %Vol. C3H8O: ca. 93% 1,00 %Vol. C3H8O: ca.193%
0,85 %Vol. C4H10O: ca. 87% 0,85 %Vol. C4H10O: ca. 87% 0,85 %Vol. C4H10O: ca.180%
0,50 %Vol. C6H14: ca. 74% 0,50 %Vol. C6H14: ca. 69% 0,50 %Vol. C6H14: ca.143%
0,55 %Vol. C7H8: ca. 72% 0,55 %Vol. C7H8: ca. 67% 0,55 %Vol. C7H8: ca.132%
at 2 %Vol NH3: 0,35 %Vol. C9H20: ca. 57% 0,35 %Vol. C9H20: ca. 49% 2,00 %Vol. NH3: ca.100%
2,00 %Vol. NH3: ca. 57% 2,00 %Vol. NH3: ca. 49%
Special notes: This sensor is not suitable for the detection of hydrogen and for the use in hydrogenous areas. The sensor responds to
hydrogen, but is only suitable for warning of this gas. Permanent exposure to hydrogen may result in a permanently
rising signal.
Expected lifetime: 5 years
MK217-1 Catalytic combustion sensor for combustible gases and vapors (according to EN 61779-4)
Response time t50: ≤ 5 s (CH4), ≤ 7 s (C3H8), *1 with wind protection: ≤ 9 s (CH4), ≤ 9 s (C3H8), *1
t90: ≤10 s (CH4), ≤12 s (C3H8), *1 with wind protection: ≤18 s (CH4), ≤21 s (C3H8), *1
Flow rate 0...6m/s: Max. ±3% of detection range or ±10% of display (regarding to 0 m/s) *2, *4
Pressure 800...1100 hPa: Max. ±3% of detection range or ±7% of display (regarding to 1000 hPa) *4
Humidity 5%...90% r.F.: Max. ±5% of detection range or ±15% of display (regarding to 50% r.F. and 40°C) *4
Temperature -10...+40°C: Max. ±5% of detection range or ±15% of display (regarding to 20°C) *4
Cross sensitivities Methane – Measuring range (#) *3 . Propane – Measuring range *3 . Hydrogen – Measuring range (#) *3
at 50%LEL: 2,20 %Vol. CH4 : = 100% 0,85 %Vol. C3H8 : = 100% 2,00 %Vol. H2: = 100%
2,00 %Vol. H2 : ca.115% 2,00 %Vol. H2 : ca.188% 2,20 %Vol. CH4 : ca. 86%
0,85 %Vol. C3H8 : ca. 65% 2,20 %Vol. CH4 : ca.162% 0,85 %Vol. C3H8 : ca. 53%
Special notes: When the sensor was exposed to a gas concentration which was considerably higher than 100%LEL, the zeropoint and
the sensitivity of the sensor have to be checked, once the gas concentration has disappeared.
Expected lifetime: 5 years
MK218-1 Catalytic combustion sensor for combustible gases and vapors (according to EN 61779-4)
Response time t50:
≤ 5 s (CH4), ≤ 6 s (C3H8), *1 mit Windschutz: ≤ 8 s (CH4), ≤12 s (C3H8), *1
t90:
≤ 9 s (CH4), ≤12 s (C3H8), *1 mit Windschutz: ≤18 s (CH4), ≤25 s (C3H8), *1
Flow rate 0...6m/s:Max. ±3% of detection range or ±10% of display (regarding to 0 m/s) *2, *4
Pressure 800...1100 hPa: Max. ±3% of detection range or ±7% of display (regarding to 1000 hPa) *4
Humidity 5%...90% r.F.: Max. ±5% of detection range or ±15% of display (regarding to 50% r.F. and 40°C) *4
Temperature -10...+50°C: Max. ±5% of detection range or ±15% of display (regarding to 20°C) *4
Cross sensitivities Methane – Measuring range (#) *3 . Propane – Measuring range *3 . Nonane – Measuring range (#) *3 .
at 50%LEL: 2,20 %Vol. CH4 : = 100% 0,85 %Vol. C3H8 : = 100% 0,35 %Vol. C9H20: = 100%
2,00 %Vol. H2 : ca.121% 2,00 %Vol. H2 : ca.195% 2,00 %Vol. H2 : ca.333%
1,15 %Vol. C2H4 : ca. 82% 2,20 %Vol. CH4 : ca.153% 2,20 %Vol. CH4 : ca.265%
0,85 %Vol. C3H8 : ca. 69% 1,15 %Vol. C2H4 : ca.120% 1,15 %Vol. C2H4 : ca.223%
1,10 %Vol. C4H8O2: ca. 64% 1,10 %Vol. C4H8O2: ca. 91% 0,85 %Vol. C3H8 : ca.182%
1,00 %Vol. C3H8O: ca. 63% 1,00 %Vol. C3H8O: ca. 90% 1,10 %Vol. C4H8O2: ca.172%
0,85 %Vol. C4H10O: ca. 62% 0,85 %Vol. C4H10O: ca. 89% 1,00 %Vol. C3H8O: ca.170%
0,55 %Vol. C7H8: ca. 58% 0,55 %Vol. C7H8: ca. 81% 0,85 %Vol. C4H10O: ca.167%
1,25 %Vol. C3H6O: ca. 54% 1,25 %Vol. C3H6O: ca. 78% 0,55 %Vol. C7H8: ca.152%
0,50 %Vol. C6H14: ca. 52% 0,50 %Vol. C6H14: ca. 73% 1,25 %Vol. C3H6O: ca.146%
0,35 %Vol. C9H20: ca. 40% 0,35 %Vol. C9H20: ca. 55% 0,50 %Vol. C6H14: ca.137%
at 2 %Vol NH3: 2,00 %Vol. NH3: ca. 45% 2,00 %Vol. NH3: ca. 60% 2,00 %Vol. NH3: ca.113%
Special notes: When the sensor was exposed to a gas concentration which was considerably higher than 100%LEL, the zeropoint and
the sensitivity of the sensor have to be checked, once the gas concentration has disappeared.
This sensor is not suitable for detection of aceton. The sensor responds to aceton, but is only suitable for warning of this
gas. Permanent exposure to aceton may result in a considerable loss of sensitivity.
Expected lifetime: 5 years
*1 For other gases longer response times are valid, especially for nonane.
*2 At flow rates >3 m/s a wind protection is necessary. Generally it should be avoided that the
gas is supplied to the transmitter from below (sensor side).
*3 The cross sensitivities can vary depending on sensor and are dependent on gas concentration and
age of sensor. Other combustible gases which are not listed, are expected to cause an increase of
signal.
*4 This specification is valid for methane and propane.

-31-
Technical Data
3

Transmitter CC28
Transmitter type: CC28 ; CC28 D and CC28 DA
Sensor type: MK 208-1 ; MK 217-1 and MK 218-1
Expected sensor life: 5 years - for normal industrial applications (see sensor specification)
Gas: Combustible gases and vapours,
e.g. Methane, Propane, Hexane, Nonane (see test report)
Detection range: e.g. 0 .. 100 % LEL (see test report)
Response time: see sensor specification
Alarm: only CC28 DA: visual and audible (90dB @ 10cm)
Detection principle: Catalytic combustion
Gas supply: Diffusion or
via flow adapter (flow rate 0.5±0.1 l/min)
Supply voltage: 15 .. 30 V DC
Max. supply current: 150 mA
Max. fault voltage: 250 V AC resp. 45 V DC (see type label)
Output current: 4 .. 20 mA (max. load 150 Ohm)
Climate Conditions
Short-term storage temperature: -25 .. +60°C
Recommended storage temperature: 0 .. +30°C
Operational temperature (ambient): -20 .. +50°C for use in Ex-hazardous areas
-25 .. +55°C for use in non-Ex areas
see Sensor specification in case of using of MK217 or MK218
Humidity range: 5 .. 90% r.h.
Atm. Pressure range: 800 .. 1100 hPa
Flow rate: 0 to 6 m/s (>3 m/s with wind protection, mounting position see page 6)
Climate Effect as per EN 61779
Pressure 800 .. 1100 hPa (1000 hPa) ± 5% of range or ±30% of display
Humidity 20% .. 90% r.h. (50%) ± 7% of range or ±15% of display
Temperature -25 .. +55°C (20°C) ±10% of range or ±20% of display
Flow rate 6 m/s (0 m/s) ± 5% of range or ±10% of display
Casing
Stability: Protect the casing against very hard impacts (> 4 J)
Casing material: anti-static compound
Dimensions: 100 x 167.5 x 55 mm (WxHxD) (H with sensor: 193 mm)
Weight: approx. 800 g ( with display )
Protection: IP 64
Cable gland: screwing M16 x 1.5 max. cross section 3 x 1.5 mm2
Cable type and length: LIYCY 3 x 0.75 mm2 for up to 200 m or
LIYCY 3 x 1.5 mm2 for up to 1000 m
Approvals and Certificates
Labelling: ¯ II 2G Y 0158
Ignition protection classification: EEx dem [ib] IIC T4 -20°C≤Ta≤+50°C
EC-Type Examination Certification: BVS 04 ATEX E 132 X (electrical Ex-Protection)
Function test: BVS 05 ATEX G 001 X (measuring function)
EMC test: EN 50270 : 1999
Radio shielding: Type class I
Interference resistance: Type class II

-32-
Annex
Internal Memory CC28
Every transmitter is pre-programmed with the data of the most important gases and their additional
parameters. In most cases, therefore, the user does not need to change the configuration. The
following information is stored in the internal memory of the transmitter:

Gas Formula Unit CGAS A1 A2 H1 H2 F1 F2


(test gas) (Alarm 1) (Alarm 2) (Hyst. A1) (Hyst. A2) (Funct. A1) (Funct. A2)
Methane CH4 %LEL 45.5 20.0 40.0 1.0 1.0 NS SC
Ethane C2H6 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Propane C3H8 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Butane C4H10 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Pentane C5H12 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Hexane C6H14 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Heptane C7H16 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Octane C8H18 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Nonane C9H20 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Iso-Butane (CH3)3CH %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Cyclohexane C6H12 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Ethylene (Ethene) H2C=CH2 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Propylene (Propene) H2C=CH–CH3 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Acetylene (Ethine) HC≡CH %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Propine HC≡C–CH3 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Hydrogen H2 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Benzene C6H6 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Toluene C6H5-CH3 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Xylene C6H4-(CH3)2 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Methanol CH3OH %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Ethanol C2H5OH %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Iso-Propanol (2-Propanol) CH3-CHOH-CH3 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
2-Butanol CH3-CHOH-C2H5 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Dimethyl ether CH3-O-CH3 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Diethyl ether C2H5-O-C2H5 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Aceton CH3-CO-CH3 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
2-Butanon (MEK) CH3-CO-C2H5 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Methyl acetate CH3-COO-CH3 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Ethyl acetate CH3-COO-C2H5 %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
Methylisobutylketone CH3-CO- %LEL 50.0 20.0 40.0 1.0 1.0 NS SC
(MIBK) CH(CH3)3
Ammonia (0 – 4 Vol.%) NH3 Vol.% 3.0 1.0 3.0 0.1 0.1 NS SC

If the transmitter is operated with a sensor for which no data are entered yet in this list, defined
settings are being used.
The user can adapt these settings individually and store them in the transmitter.

Worldwide Supplier of Gas GfG Gesellschaft für Gerätebau mbH


P.O.Box 440164, D-44390 Dortmund
Detection Solutions Phone: +49-(0)23156400 0
Fax: +49-(0)231-516313
Firmware Version 2.4.1 Edition 04.04.2007 E-Mail: [email protected]
Internet: www.gasdetection.biz
197-000.12_OM.doc We reserve the right of modification

-33-
EC-Type Examination Certificate

-34-
-35-
-36-

You might also like