PowerLogic™ ION9000 - METSEION92040
PowerLogic™ ION9000 - METSEION92040
PowerLogic™ ION9000 - METSEION92040
Specifications
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range PowerLogic
Complementary
Power quality analysis EN 50160 compliance checking
conforming to IEEE 519 harmonic limit
conforming to IEC 61000-4-30: class A compliance reporting
conforming to IEEE 519 compliance reporting
waveform capture
total demand distortion
total harmonic distortion
up to the 63rd harmonic
up to the 127th harmonic with software
disturbance direction detection
dip, swell and transient
half cycle data acquisition
transient detection (20 µs)
Network frequency 50 Hz
Feb 8, 2023 1
60 Hz
Type of network 3P + N + E
Memory capacity 2 GB
2
Feb 8, 2023
Cybersecurity Syslog protocol support
Robust security logs
Port hardening
Enable/disable communication ports
Hardware metrology lock
Width 160 mm
Depth 135.3 mm
Height 160 mm
Environment
Electromagnetic compatibility EMC immunity conforming to IEC 62052-11
EMC immunity conforming to IEC 61326-1
EMC immunity conforming to IEC 61000-6-5
Electrostatic discharge immunity test conforming to IEC 61000-4-2
Immunity to radiated fields conforming to IEC 61000-4-3
Immunity to fast transients conforming to IEC 61000-4-4
Surge immunity test conforming to IEC 61000-4-5
Immunity to conducted disturbances conforming to IEC 61000-4-6
Immunity to magnetic fields at network frequency conforming to IEC 61000-4-8
Immunity to conducted disturbances - test level: 2...150 kHz conforming to CLC/TR 50579
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Immunity to impulse waves conforming to IEC 61000-4-12
Conducted and radiated emissions conforming to EN 55011
Conducted and radiated emissions class B conforming to EN 55032
Conducted and radiated emissions class B conforming to FCC part 15
Conducted and radiated emissions class B conforming to ICES-003
Surge withstand conforming to ANSI C37.90.1
Surge withstand conforming to IEEE C37.90.1
Feb 8, 2023 3
IEC 61000-4-15
IEC 61000-4-30
IEC 61010-1
IEC 61326-1
IEC 61557-12
IEC 61850
IEC 62052-11
IEC 62052-31
IEC 62053-22
IEC 62053-23
IEC 62053-24
IEC 62586
UL 61010-1
Packing Units
Unit Type of Package 1 PCE
Offer Sustainability
Sustainable offer status Green Premium product
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
Recommended replacement(s)
4
Feb 8, 2023