Acu100 Io en 0413
Acu100 Io en 0413
Acu100 Io en 0413
wireless
system abax
User Manual
1471
acu100_en 04/13
IMPORTANT
The controller incorporates electronic components sensitive to electrostatic discharges. Prior
to installation, remove the electrostatic discharges and avoid touching the controller board
components in the process of installation.
Do not deform the controller antenna, as this may adversely affect the quality of radio
communication.
Hereby, SATEL sp. z o.o., declares that this device is in compliance with the essential
requirements and other relevant provisions of Directive 1999/5/EC. The declaration of
conformity may be consulted at www.satel.eu/ce
The SATEL Company sets itself an objective to continually enhance quality of its products,
which can entail changes to their technical specifications and software.
Information on the introduced modifications can be found on our web site.
Please visit us at:
http://www.satel.eu
New features of the ACU-100 controller with firmware version 4.02
Support for new wireless device:
– AMD-103 – wireless magnetic contact.
2 Two-way wireless system ABAX ACU-100
CONTENTS
1. General..............................................................................................................................4
2. Description of ACU-100 wireless system controller ...........................................................4
2.1 Electronics board ....................................................................................................................... 4
2.2 Functions of DIP-switches ......................................................................................................... 6
2.3 Control inputs............................................................................................................................. 7
2.4 Outputs ...................................................................................................................................... 8
2.5 Functional outputs...................................................................................................................... 8
3. Wireless devices interfacing with the controller .................................................................9
3.1 ACX-100 Input & output expansion module ............................................................................... 9
3.2 ACX-200 Hardwired zone / output expander ............................................................................. 9
3.3 ACX-201 Hardwired zone / output expander with power supply................................................ 9
3.4 APD-100 Wireless passive infrared detector ............................................................................. 9
3.5 APMD-150 Wireless dual motion detector ............................................................................... 10
3.6 AMD-100 Wireless magnetic detector ..................................................................................... 10
3.7 AMD-101 Dual channel wireless magnetic detector ................................................................ 10
3.8 AMD-102 Wireless magnetic contact with input for roller shutter detector............................... 10
3.9 AMD-103 Wireless magnetic contact ....................................................................................... 10
3.10 AGD-100 Wireless glass-break detector .............................................................................. 10
3.11 AFD-100 Wireless water flood detector ................................................................................... 11
3.12 AVD-100 Wireless vibration detector and magnetic contact .................................................... 11
3.13 ASD-100 Wireless smoke and heat detector ........................................................................... 11
3.14 ASD-110 Wireless smoke and heat detector ........................................................................... 11
3.15 ARD-100 Wireless reorientation detector ................................................................................ 11
3.16 ATD-100 Wireless temperature detector ................................................................................. 11
3.17 ASP-105 Wireless outdoor siren .............................................................................................. 12
3.18 ASP-205 Wireless indoor siren ................................................................................................ 12
3.19 APT-100 Bidirectional keyfob................................................................................................... 12
3.20 ASW-100 E 230 V AC Wireless controller ............................................................................... 12
3.21 ASW-100 F 230 V AC Wireless controller................................................................................ 12
3.22 ARF-100 Radio signal level tester ........................................................................................... 12
4. Installation .......................................................................................................................13
4.1 Installation of ACU-100 wireless system controller .................................................................. 13
4.2 Connecting LCD keypad to the controller ................................................................................ 13
4.3 Connecting computer to the controller ..................................................................................... 14
4.4 Connecting the ACX-100 input & output expansion modules .................................................. 15
4.5 Adding new wireless devices ................................................................................................... 16
4.5.1 DLOAD10 and DLOADX programs ................................................................................................... 16
4.5.2 LCD keypad connected to the controller ....................................................................................... 17
4.5.3 LCD keypad of INTEGRA alarm system / INTEGRA Plus ............................................................ 17
4.6 Removal of wireless devices.................................................................................................... 18
4.6.1 DLOAD10 and DLOADX programs ................................................................................................... 18
4.6.2 LCD keypad ................................................................................................................................... 18
5. Hardwired zone/output expanders in ABAX system ........................................................19
5.1.1 Configuration of ACX-200 or ACX-201 expander zones/outputs for ACU-100 controller operation
with INTEGRA, INTEGRA Plus or VERSA control panel .............................................................. 20
5.1.2 Configuration of ACX-200 expander zones/outputs for ACU-100 or ACX-201 controller operation
with CA-64 control panel................................................................................................................ 20
5.1.3 Configuration of ACX-200 or ACX-201 expander zones/outputs for ACU-100 controller operation
with other control panels................................................................................................................ 20
6. Wireless detectors in ABAX system.................................................................................21
ACU-100 SATEL 3
1. GENERAL
The ACU-100 controller allows communication between any alarm control panel and the
ABAX system wireless devices. It enables wire-operated security systems to be expanded by
addition of wireless devices. The ABAX system is based on two-way communication. All
messages sent by the devices are acknowledged, which ensures that the equipment status
information will reach the controller and allows online check of the devices for their presence
in the system. Configuration of parameters and testing of the wireless devices is performed
by radio, without the need to dismantle their housings. Coded communication between the
units takes place within the frequency band of 868.0 MHz – 868.6 MHz.
antenna.
DIP-switch package for setting an individual addresses of the device and to configure
some working parameters of the controller (see FUNCTIONS OF DIP-SWITCHES).
buzzer. It informs of occurrence of one of the problems signaled on functional outputs (it
does not apply to the controller interfacing with the INTEGRA, INTEGRA Plus or VERSA
series alarm control panels).
ACU-100 SATEL 5
CLK, DAT - communication bus. It enables direct connection to the control panel
communication bus (INTEGRA, INTEGRA Plus, VERSA, CA-64, CA-10)
or expansion of the system by adding the ACX-100 input/output expansion
modules.
DIP-switch number 1 2 3
Numerical value 1 2 4
(for switch in ON position)
Table 2.
The controller accepts up to 5 input/output expansion modules, hence if a higher value
is set on the DIP-switches, it will be also recognized as 5.
A, B, C, D – DIP-switches for setting the controller address in the same way as with the
CA-10 zone expanders. When in the ON position, the switch value is 1.
A1, A2, A3, A4, A5 – DIP-switches for setting the controller address. In order to determine the
controller address, add up the values set on individual DIP-switches as per Table 3.
DIP-switch number 1 2 3 4 5
Numerical value 1 2 4 8 16
(for switch in ON position)
Table 3.
x – unused DIP-switch
ACU-100 SATEL 7
COM CLK
AR1 DAT
+12V
COM +12V TMP TMP ITMP COM
ACU-100
TPR CON JAM LBA OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 COM AR1 AR2 AR3 AR4
1.1 kΩ
The control panel outputs which are to control the ACU-100 controller inputs should be
properly configured (their type, polarity, cutoff time, etc.). The type of wireless devices whose
operation is controlled by the input must be primarily taken into account.
To control operation of the wireless detectors, the control panel output can be programmed
e.g. as the ARM STATUS. Arming the control panel will switch the detectors into the active
mode, and disarming – into the passive mode (detector operating modes are described in
section WIRELESS DETECTORS IN ABAX SYSTEM). It should be remembered that
8 Two-way wireless system ABAX ACU-100
2.4 OUTPUTS
If the controller is working as an expander with the INTEGRA, INTEGRA Plus,
VERSA or CA-64 control panels, you are not required to know how the outputs
operate, because they need not be connected to the control panel (information
from wireless devices will be sent to the control panel via communication bus).
The PCB of the ACU-100 controller incorporates eight OC type outputs, to which wireless
devices are assigned. Any number of wireless devices can be assigned to one output. The
number of outputs can be increased by connecting the ACX-100 expansion modules to the
controller. The maximum number of outputs 48 (controller + 5 ACX-100 modules).
The output activates after receiving suitable information from a wireless device assigned to it,
the information depending on the device type:
the wireless detectors signal violations;
the ASP-105 siren inform of a discharged battery and a failure of +12 V DC external
power supply;
the ASP-205 sirens inform of battery discharge;
the ACX-200 and ACX-201 expanders signal zone violation;
the ASW-100 E and ASW-100 F controllers inform that the button was depressed in Mode
0 or the electric circuit was closed in Mode 1 and 2.
The outputs can be programmed as NO (normally open) or NC (normally shorted to ground).
All the outputs (of the controller and the ACX-100 modules connected to it) are being
programmed at the same time. Depending on how the outputs have been programmed,
activation of the output is indicated as follows:
LED assigned to the output comes ON (outputs programmed as the NO type);
LED assigned to the output comes OFF (outputs programmed as the NC type).
The outputs can be connected to the control panel zones.
3.8 AMD-102 WIRELESS MAGNETIC CONTACT WITH INPUT FOR ROLLER SHUTTER
DETECTOR
two reed switches
individually identified input for connecting a roller shutter detector or NC type detector
remote configuration of parameters
tamper contact
power supply: lithium battery, CR123A 3V
Note: The ATD-100 detector is only supported by the controller interfacing with the
INTEGRA (firmware version 1.09 or newer) or INTEGRA Plus control panel.
4. INSTALLATION
The ABAX two-way wireless system should be installed so as to ensure
a suitable level of radio signal from devices working together with the controller.
This will allow the communication problems to be avoided.
All electrical connections may only be made with power supply disconnected.
Before proceeding to the system installation you should plan the arrangement of all the
devices. The installation place for the controller should be chosen so that all devices to be
supervised by it are within its range. It is recommended that the controller and the wireless
devices be mounted at a high position, which will enable a better range of radio
communication to be reached, while avoiding a risk of incidental masking of the controller
and devices by people moving around the facility.
Before permanently mounting the system components, you should check the level of signal
received by the controller from individual devices. A helpful instrument for checking the signal
level is the SATEL-made ARF-100 tester. If the signal level from a particular unit is too low
(less than 40%), a change of the device position will be necessary. At times, it is sufficient to
move the device some ten to twenty centimeters to get a significant improvement of the
signal quality. Having reached the optimal level of radio signal from all devices, you can
proceed to permanently mounting them in position.
Several ACU-100 controllers can work within each other's range. Automatic synchronization
with the wireless systems already in use is always performed when the controller is switched
on, and after each operation of addition/removal of supported devices. The number of
wireless devices already working within the range of each other depends on the RESPONSE
PERIOD (see DESCRIPTION OF FUNCTIONS, OPTIONS AND COMMANDS) and can vary from 150 to
450. The higher the response frequency, the lower the number of devices that can work
within each other's range.
Recommendations for installation of particular wireless devices can be found in the manuals
delivered with respective devices.
12 34
1 - +KPD
2 - CKM
3 - DTM
4 - COM
12 34
Fig. 3. Sequence of wires in the plug connecting LCD keypad with controller.
1 – view of plug in the socket. 2 – view of plug from the pins side.
RTS CTS
COM COM 5
DSR DTR 4
8
RXD TXD 3
TXD RXD 2
5 43 21
Fig. 5. Connection of computer to the controller serial port. PIN5 plug is shown on the left.
DB-9 female plug is shown on the right, as seen from solder side.
If the DLOAD10 program fails to communicate with the computer after connection of the
RS-232 port, you should:
check that the option of programming by means of RS-232 port has been selected on the
controller DIP-switches;
check that the port through which the computer communicates with the controller has been
properly selected in the DLOAD10 program;
check that the cables connecting the computer with controller have been properly
connected.
ACU-100
TPR CON JAM LBA OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 COM AR1 AR2 AR3 AR4
0 1
ACX-100 ACX-100
A0 A0
A1 A1
A2 A2
DAT CLK COM 12V TMPTMP DAT CLK COM 12V TMPTMP
The ACU-100 controller communication bus can accept up to five ACX-100 input & output
expansion modules. The modules can only be connected when the controller is
configured as a wireless device module interfacing with any alarm control panel.
The modules should be connected to the controller bus in parallel. The connection can be
made by means of the unscreened straight-through cable (using the "twisted pair" type of
cable is not recommended). When connecting the modules, remember to set the correct
number of ACX-100 modules connected to the controller on the controller DIP-switches. Lack
of communication with the module will be signaled on the TPR output as tamper.
Each module connected to the bus must have a different address set from the range 0 to 4.
These addresses must correspond to the number of a next module, as shown in Table 4. If
one ACX-100 module is connected to the controller, it must have address 0 set, if two, one of
them must have address 0 set, and the other address 1, etc.
The numeration of control inputs and outputs of the expansion module in the system depends
on the address set in it (see: table 4).
The module TMP terminals must be connected to the control panel tamper circuit.
Consecutive module number Module address Control input numbers Output numbers
1 0 5–8 9–16
2 1 9–12 17–24
3 2 13–16 25–32
4 3 17–20 33–40
5 4 21–24 41–48
Table 4.
If an invalid serial number has been entered, you will be informed of it by a suitable
message. Then you should enter the correct serial number and repeat the above
mentioned step.
4. A confirmation message will be displayed that a new device has been added. In case of
the DLOADX program (version 1.09 or newer):
– suggested name for the zone/output assigned to the device will appear (the name is
editable);
– you can select for some devices whether it take one or two positions in the list of
devices (INTEGRA firmware version 1.09 or newer / INTEGRA Plus).
5. Click your mouse on the „OK” button to finish the procedure of new device addition. You
can cancel addition of the new device by pressing the „Abort” button. You can also add a
next wireless device by pressing the „Next” button.
Note: If the ACU-100 controller is connected as an expansion module to the CA-64,
INTEGRA or INTEGRA Plus control panel, the procedure of adding new wireless
devices to the system must be followed by the procedure of expander identification in
the control panel.
Note: Pressing any key instead of the key [1] will take you back to the selection list of
wireless devices.
The second position indicates the zone sensitivity. Using the keypad you can enter a value
from the 20ms to 5100ms range. Within the range of 20ms to 140ms, it is possible to enter
values every 20ms (20ms, 40ms, 60ms, etc.). The next value that can be entered is 300ms.
Within the range of 300ms to 5100ms, you can enter values every 200ms (300ms, 500ms,
700ms, etc.). If a number different from the above values is entered, it will be rounded up to
the next supported value (e.g. after entering 301, the next value to be entered is 500ms).
In order to configure the expander outputs, indicate the appropriate ACU-100 control inputs
which will control the expander outputs. The control inputs are to be connected to the suitably
programmed outputs of the alarm control panel.
The batteries ensure operation of the detectors for a period of about 3 years,
provided that they remain in the passive state for some portion of that period,
and the RESPONSE PERIOD is 12 seconds. A longer polling period (24 or 36
seconds) means extension of the battery life time. The battery life time in the
detectors switched permanently into the active mode is shorter than in those
which are periodically switched to the passive mode. However, if the specific
character of a detector or its installation place is such that the number of
violations is low, switching the detector permanently into the active mode will
not adversely affect the battery life time.
Depending on the controller operating configuration, the loss of +12 V DC voltage will:
– cause violation of the second zone occupied by the siren in the system (communication
through the bus with INTEGRA, INTEGRA Plus, VERSA, CA-64 or CA-10 control panels);
– activate the controller LBA output;
– activate the controller output assigned to the optical signaling (the second position
occupied by the siren on the list of devices).
Depending on the controller operating configuration, the low battery will:
– cause violation of the first zone occupied by the siren in the system (communication
through the bus with INTEGRA, INTEGRA Plus, VERSA, CA-64 or CA-10 control panels);
– activate the controller LBA output;
– activate the controller output assigned to the acoustic signaling (the first position occupied
by the siren on the list of devices).
ASP-205 – wireless indoor siren. You can program two types of signaling, defining for each
of them:
– maximum duration of signaling;
– type of acoustic signaling;
– whether optical signaling is to be enabled.
In order to check the radio signal level and find the optimum installation position for the
wireless device by means of the tester, do the following:
1. Install battery in the tester.
2. Add the tester to the wireless system (see: ADDING NEW WIRELESS DEVICES). If the
ACU-100 controller is used in conjunction with the CA-64, INTEGRA, INTEGRA Plus or
VERSA control panels, it is recommended that the ARF-100 tester be added as the last
wireless device (after the other devices to be installed in the ABAX system). This will
prevent creating an unnecessary gap due to unused zone after the tester is removed from
the system.
3. Using the designated button, select the power supply mode for the wireless device
which is to be installed and simulated by the tester.
4. Start the test mode in the controller. During response time, the level of radio signal
received by the tester from the controller will be displayed on the LED indicator. Press the
designated button to see the level of signal received by controller from the tester. The
signal level is always refreshed during the response time (which is signaled by 1 short
beep). If a higher update frequency is required, activate the dense polling mode by means
of the button. The signal level displayed on the LEDs will be refreshed every 2
seconds. Information update will be signaled by 2 short beeps.
Note: According to requirements of the EN50131 standard, the level of radio signals sent by
wireless devices is reduced during the test mode operation.
5. Find the optimum location to install the new wireless device.
6. Having completed the test, switch off the tester and remove it from the ABAX wireless
system.
Note: If not used, the tester will switch off automatically after 10 minutes.
Communication with the control panel is only effected by means of the communication bus.
This way is used for transmission of information on violations of detectors, tampers and
troubles of wireless devices, as well as for control of operation of wireless devices. Table 6
shows how the terminals of the controller communication bus should be connected to the
communication bus terminals of the INTEGRA / INTEGRA Plus alarm control panels.
COM CLK
+12V DAT
COM +12V TMP TMP ITMP COM
ACU-100
TPR CON JAM LBA OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 COM AR1 AR2 AR3 AR4
Fig. 8. Example of connecting the ACU-100 controller to the INTEGRA control panel.
Having connected the ACU-100 controller to the control panel, start the expander
identification function in the panel. In the process of addition or removal of the wireless
devices, it must be borne in mind that during controller identification the INTEGRA /
INTEGRA Plus series control panels register the zones and outputs by groups of 8.
Therefore, it is important at the registration of wireless devices in the controller to maintain
continuity, i.e. to avoid spaces in the list, which will eventually reduce the number of available
inputs in the panel. For example, if 9 wireless devices were initially registered in the
controller, but item 7 was later deleted from the list, the control panel will assign 2x8 zones to
the controller, although just 8 devices will be physically connected to it (see Table 7). In case
of devices which, in addition to zones, also take up outputs, it is recommended that they be
added to the system first, so as to maintain the continuity of using both the zones and the
outputs. Table 7 presents a situation in which the first output of the siren has found itself in
position 8, and the second output in position 9. As a result, 16 outputs have been reserved in
the system (the eight output in the first group of 8 outputs, and the first output in the second
group of 8 outputs).
28 Two-way wireless system ABAX ACU-100
Sometimes, it is impossible to avoid gaps on the list of zones/outputs. This is the case when
the number of zones/outputs actually used by the devices is not a multiple of 8. Avoiding the
gaps is difficult or even impossible when, due to the size of the premises, a number of
ACU-100 controllers are operating in the system.
Apart from assignment of zones and outputs to the controller, the panel will reserve for it an
address on the expander bus. For each group of 8 zones/outputs, 1 address is reserved on
the expander bus. The controller can take up from 1 to 6 addresses on the expander bus.
This should be taken into account at the system design stage and the sufficient number of
unoccupied addresses should be left for the controller. If, after new wireless devices are
added to the controller, it turns out that further addresses are needed, but they are occupied
by other devices, correct completion of the expander identification procedure will be
impossible. Then it will be necessary to change the addresses of devices connected to the
expander bus.
ACU-100 SATEL 29
The system zones to which wireless devices are assigned can be programmed as:
– NC, NO or EOL – depending on the type of device, the zone will provide information
about detector violation, power failure, etc.
– 2EOL/NC or 2EOL/NO – depending on the type of device, the zone will provide
information about detector violation, power failure, etc., and, additionally, about tampers.
Changing the wireless detectors from passive to active state takes place simultaneously with
arming the partition to which the zone with wireless detector belongs. After disarming, the
detectors will re-enter the passive state. It does not refer to the 24hr zones. The wireless
detectors assigned to those zones remain always in the active state. Additionally, the ALWAYS
ACTIVE option can be enabled for any wireless detector.
Do not program reversed polarity for the alarm system outputs to which
wireless devices are assigned, because these devices will function in reversed
mode (the inactive output will arm, and the active output will disarm).
Communication with the control panel is effected by means of the communication bus. This
way is used for transmission of information on violations of detectors and tampers of wireless
devices. Control of the detectors (changeover to active/passive state), sirens (triggering
alarm signal), 230 V AC controller (closing/opening the electric circuit) etc. is performed
through the control inputs of the ACU-100 controller. Suitably programmed outputs of the
alarm control panel should be connected to the control inputs.
Fig. 10 shows a configuration example of the ACU-100 controller working together with the
CA-64 control panel. The controller communication bus is connected to the second expander
bus of the control panel. The OUT9 panel low-current output has been programmed as type
42: POWER SUPPLY ON ARMED and connected to the AR1 controller control input. This input is
used to toggle the wireless detectors between their passive and active state. The OUT10
panel low-current output has been programmed as type 1: BURGLARY ALARM and connected to
the AR2 controller control input. This input triggers the wireless siren. In the presented
example, the controller information outputs (CON, JAM, LBA) remain unconnected. They can
be connected to the control panel inputs so as to obtain in this way information on troubles
related to operation of the wireless devices.
Having connected the ACU-100 controller to the control panel, start the expander
identification function in it.
When interacting with the CA-64 control panel, the ACU-100 controller makes 48 wireless
zones available to it. The zone numbers are assigned to the wireless devices registered in
the controller according to the following principle:
zone number = 16 + number of the wireless device on the list
30 Two-way wireless system ABAX ACU-100
+12V
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
CA-64 OUT16
COM
CK1 COM EX2 DT2 CK2 Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8 Z9 COM Z10 Z11 COM Z12 Z13 COM Z14 Z15 COM Z16
COM +12V TMP TMP ITMP COM
TPR CON JAM LBA OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 COM AR1 AR2 AR3 AR4
Fig. 10. Example of connecting the ACU-100 controller to the CA-64 control panel.
The system zones to which wireless devices are assigned can be programmed as:
– NC, NO or EOL – depending on the type of device, the zone will provide information
about detector violation, power failure, etc.
– 2EOL/NC or 2EOL/NO – depending on the type of device, the zone will provide
information about detector violation, power failure, etc., and, additionally, about tampers.
Connection of the controller to the CA-64 alarm control panel excludes the possibility to
connect to it the zone expanders (CA-64 E, CA-64 EPS and CA-64 ADR) as well as the
CA-64 PP zones & outputs expander with power supply.
Using the DIP-switches, set the suitable operating mode, address and programming mode of
the ACU-100 controller. To determine the operating mode you should take into account the
number of keypads installed in the system. Depending on the number of keypads, the
ACU-100 SATEL 31
controller makes it possible to expand the system by 2, 4 or 6 wireless zones (see Table 9),
the status of which (violations and tampers of the wireless devices assigned to these zones)
will be transmitted by means of the communication bus.
Number of keypads in the
Connection of CLK
11 12 13 14 15 16
output 11 output 12 output 13 output 14 output 15 output 16
1 CLK1 CLK2
in controller in controller in controller in controller in controller in controller
CLK1 zone in 2nd zone in 2nd output 13 output 14 output 15 output 16
2 CLK3
CLK2 keypad keypad in controller in controller in controller in controller
CLK1
zone in 2nd zone in 2nd zone in 3rd zone in 3rd output 15 output 16
3 CLK2 CLK4
keypad keypad keypad keypad in controller in controller
CLK3
Table 9.
CA-10
COM OUT4 COM +KPD DATA CLK1 CLK2 CLK3 CLK4 COM Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8
OUT2
OUT1
CLK
DAT
COM +12V TMP TMP ITMP COM
ACU-100
TPR CON JAM LBA OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 COM AR1 AR2 AR3 AR4
Fig. 12. Example of connecting the ACU-100 controller to the CA-10 control panel.
32 Two-way wireless system ABAX ACU-100
Control of the detectors (changeover to active/passive state), sirens (triggering alarm signal),
230 V AC controller (closing/opening the electric circuit) etc. is performed through the control
inputs of the ACU-100 controller. Suitably programmed outputs of the alarm control panel
should be connected to the control inputs. Additionally, it is possible to connect the first eight
outputs of the controller to the control panel zones. Thus the alarm control panel can receive
information from the wireless devices assigned to these outputs. Connecting the ACU-100
controller to the CA-10 control panel at the same time by means of communication bus and
control panel zones will enable the system to be expanded by up to 14 wireless zones.
Fig. 12 shows an example of configuration of the ACU-100 controller interacting with the
CA-10 control panel. One keypad is connected to the control panel, therefore the CLK
controller terminal is connected to the CLK2 panel terminal. The zones made available by the
ACU-100 controller to the control panel by means of the communication bus have in the
security system numbers from 11 to 16 (controller outputs from 11 to 16). These zones
should be programmed in the control panel as 2EOL/NO type. The controller outputs OUT1
and OUT2 have been connected, respectively, to the control panel zones Z1 and Z2 (thus,
the total number of wireless zones in the system will amount to 8).The control panel zones to
which the controller outputs have been connected should be configured as NO type. Still
available are the control panel zones from Z3 to Z8. You can connect to them wire-operated
devices or consecutive controller outputs as well as wireless devices assigned to them. The
OUT5 control panel low-current output has been programmed as type 35: POWER SUPPLY ON
ARMED MODE and connected to the AR1 controller control input. This input switches the
wireless detectors from passive to active state, and vice versa. The OUT6 control panel low-
current output has been programmed as type 01: BURGLARY ALARM and connected to the AR2
controller control input. This input triggers the wireless siren. In the presented example, the
controller information outputs (TPR, CON, JAM, LBA) have remained unconnected. These
outputs can be connected to the control panel zones so as to obtain in this way information
on problems connected with operation of wireless devices.
Communication with the control panel in this configuration is effected by means of controller
outputs and inputs. The controller outputs to which the wireless devices are assigned should
be connected to the control panel zones. Control of the detectors (changeover to
active/passive state), sirens (triggering alarm signal), 230 V AC controller (closing/opening
the electric circuit) etc. is performed through the control inputs of the ACU-100 controller.
Suitably programmed outputs of the alarm control panel should be connected to the control
inputs.
Shown in the example, Fig. 14, is the CA-6 alarm control panel of SATEL make, however it
can be any other panel as well. The controller outputs OUT1 to OUT5 are connected,
respectively, to the control panel zones Z1 to Z5 (preprogrammed as type NO). The TPR
output, which informs of tampers of wireless devices and controller (TMP terminals
ACU-100 SATEL 33
connected to COM and ITMP terminals), is connected to the Z6 panel zone, preprogrammed
as NO type, reaction type 24H AUDIBLE. The OUT4 panel low-current output has been
programmed as type 35: POWER SUPPLY ON ARMED MODE and connected to the AR1 controller
control input. This input toggles the wireless detectors between the passive and active state.
The OUT5 panel low-current output has been programmed as type BURGLARY ALARM
SIGNALING and connected to the AR2 controller control input. This input triggers the wireless
siren.
AR1
CA-6
COM OUT2 COM OUT3 COM +KPD DTA CLK CTL Z1 COM Z2 Z3 COM Z4 Z5 COM Z6
OUT5
OUT4
OUT3
OUT2
OUT1
TPR
COM +12V TMP TMP ITMP COM
ACU-100
TPR CON JAM LBA OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 COM AR1 AR2 AR3 AR4
Fig. 14. Example of connecting the ACU-100 controller to the CA-6 control panel.
2. Click on the button to open the window showing structure of the security system.
3. Select the "Hardware" tab, and then highlight the wireless system controller in the list of
devices.
4. Program the controller.
5. Having finished entering the new settings, save them in the controller by clicking on the
"Write" button (the and buttons in the main menu of DLOADX program are not
intended for reading/writing the settings of the controller and wireless devices supported
by it).
Fig. 15. Configuration of the ACU-100 controller working together with the INTEGRA control
panel in DLOADX program. Given under information on the module type and address is the
version of its firmware. The wireless devices have been registered in the controller as
recommended earlier in this manual: the devices which occupy both zones and outputs in the
system were added first, while the devices taking up zones only were added after them.
Fig. 16. DLOADX program window showing signal level and quality of controller
communication with wireless devices (ACU-100 controller working together with the
INTEGRA control panel).
Troubles of wireless devices (no communication, low battery level, jamming) can be read out
in the DLOADX program in the TROUBLES window.
Fig. 17. Activation of the ACU-100 controller support in the DLOAD10 program.
6. Having established communication, the program will compare identifiers in computer and
controller, and if they coincide, it will read data from the controller.
7. Configure the controller settings.
8. After completion of entering the new settings, save them in the controller by clicking on the
button.
A useful diagnostic tool in the DLOAD10 program is the level of signal currently received by
the controller in its working radio band, which is presented as a real time diagram. It
illustrates both the noise level and all registered at a particular moment signals from other
radio devices operating on the same frequency band. Presented in red color are signals from
wireless devices operated by the controller. To open the window showing the radio signal
level, click on the button. Also the level of radio signal received by the controller from
individual devices can be represented in a diagrammatic form.
Note: When the ACU-100 controller is connected to the INTEGRA / INTEGRA Plus control
panel, the options regarding configuration of wireless devices are not available in the
DLOAD10 program. Available are only diagnostic functions, including diagrams
illustrating the radio signal levels.
ACU-100
SATEL
Fig. 19. DLOAD10 program window with a diagram of the level of radio signal received by the
controller.
Notes:
When a new wireless device is added to the system, the input 1 is indicated by default as
the control input.
When the entered input number is higher than 24, the input to control the device will be
always active.
Outputs – wireless devices are assigned to particular controller outputs. This does not apply
to the CA-64 (it is possible to assign the devices to outputs, but the outputs will not be
used for communication with the control panel), INTEGRA, INTEGRA Plus and VERSA
control panels.
Note: When a new wireless device is being added to the system, it is by default assigned to
the output 1.
SETTINGS – calls submenu of the keypad connected to the computer.
Response period – the controller communicates with the wireless devices at specified time
intervals. During those periods the controller gathers information on the status of
devices and, if necessary, sends commands to the devices, e.g. switches the detectors
to their active/passive state, activates/deactivates the test mode, and changes
configuration of the devices. The response period may be 12, 24 or 36 seconds. The
rarer the communication between the controller and wireless devices, the more wireless
devices can work within each other's range. The maximum number of devices for 12s is
150, for 24s – 300, and for 36s – 450. Outside the response period, information on
tampers of the devices and violations of the detectors being in their active state is sent to
the controller.
Note: In the case of the AMD-103 detector, no communication takes place during polling.
Filter – it is possible to define the number of unanswered polls, after which "no
communication" will be reported. You may enter the values from the range of 0 to 50.
Entering the digit 0 will disable control of the device for presence in the system.
Higher sensitivity for jamming detection – if this option is enabled, the sensitivity of
detection of radio communication jamming is boosted. The option is available when the
controller is connected to the INTEGRA, INTEGRA Plus or VERSA control panel.
Note: In the case of the AMD-103 magnetic contact, the presence check is performed in
a different way than for the other ABAX system devices. If the value programmed for
the FILTER parameter differs from 0, the lack of presence will be reported if no
transmission from the AMD-103 magnetic contact is received within one hour.
Configuration – some wireless devices (e.g. APD-100 APMD-150, AGD-100, AVD-100 and
ASD-100 detectors, ASP-105 and ASP-205 sirens) make extra options available, which
can be configured by radio.
Problem signaling – activation of any of the controller functional outputs (TPR, CON, JAM
or LBA) can be indicated by LED or sound signal. This option is unavailable when the
controller interacts with INTEGRA, INTEGRA Plus or VERSA series control panels.
Input types – the control inputs can be programmed as NO (normally open) or NC (normally
closed). The parameter is not available if the controller is connected to the INTEGRA,
INTEGRA Plus or VERSA series control panels.
Output type – outputs of the controller and ACX-100 modules can be programmed as NO
(normally open) or NC (normally closed). The parameter is not available if the controller
is connected to the INTEGRA, INTEGRA Plus or VERSA series control panels.
Set defaults – this function, which is only available in the LCD keypad connected to the
controller, is used to restore the defaults.
TESTS – calls submenu of the keypad connected to the computer.
42 Two-way wireless system ABAX ACU-100
Signal level – this function, available in the LCD keypad, allows checking the level of signal
received from wireless devices. The signal level is presented in percentage form. In the
DLOAD10 program, the signal level is visualized graphically in on-line mode, with no
need for calling any function. In the DLOADX program, information on the signal level is
shown in the "Wireless device" window.
Communication state – this function, available in the LCD keypad connected to the
controller, allows you to check with which devices the communication is correct, or non-
existent, or was temporarily lost. In the DLOAD10 program, all the communication-related
information is shown in real time, with no need for calling any function. In the INTEGRA,
INTEGRA Plus or VERSA system LCD keypad, the information on possible lack of
communication is given in the user menu, TROUBLES submenu, and in the DLOADX
program, in the "Troubles" window.
Tamper state – this function, available in the LCD keypad connected to the controller, allows
you to check which of the wireless devices are or were tampered with. In the DLOAD10
program, all the tamper-related information is given on-line, with no need for calling any
function. In the INTEGRA, INTEGRA Plus or VERSA system LCD keypad, as well as in
the DLOADX program, it is possible to check the wireless device/controller for presence
of tamper by using the EVENTS function. Additionally, the information on possible
tampers of wireless devices can be found in the DLOADX program in the "Zones state".
Battery status – function is available in the LCD keypad connected to the controller.
Depending on the type of device, the low battery message may indicate:
– low battery (detectors);
– loss of 12 V DC supply (ASP-105 siren);
– loss of 18 V AC supply (ACX-201 expander);
– discharged battery (ASP-105 siren, ACX-201 expander);
– overload of AUX1 or AUX2 supply output (ACX-201 expander).
In the DLOAD10 program, information on the status of battery / power supply / storage
battery / supply outputs is given in on-line mode in the "Battery" column. In the
INTEGRA, INTEGRA Plus or VERSA system LCD keypad, information on low batteries
and other troubles is given in the user menu, TROUBLES submenu, and in the DLOADX
program, in the "Troubles" window.
Note: When low battery status is indicated, replace the battery within 2–3 weeks.
Jamming – this function, available in the LCD keypad connected to the controller, makes it
possible to check whether the wireless system operation is not jammed by any device,
which emits radio waves on the same frequency. If there was a jamming event,
information is given of the fact, stating how many times and what was its amplitude. In
the DLOAD10 program all the information on jamming is given in on-line mode, with no
need for calling any function. In the INTEGRA, INTEGRA Plus or VERSA system LCD
keypad, the information on possible jamming is given in the user menu, TROUBLES
submenu, and in the DLOADX program, in the "Troubles" window.
Test mode – activation of the test mode makes all the wireless devices indicate
communication with the controller by blinking LEDs. Detectors inform on violations and
tampers, using the LEDs. In the normal operating mode of the wireless devices, the
signaling on LEDs is "off" for energy-saving considerations. When in the test mode, the
tamper alarm signaling in sirens is disabled. After exiting the test mode, its actual
termination will take place at the next response period. The test mode will be
automatically exited 30 minutes after:
– it is started through the DLOADX program. If the WIRELESS DEVICES window is opened
during this time in the DLOADX program, the test mode duration will be extended (the
30-minute countdown will run from closing the window),
ACU-100 SATEL 43
– termination of the service mode in the INTEGRA, INTEGRA Plus or VERSA control
panel or the keypad connected to the controller,
– closing the DLOAD10 program.
Notes:
According to requirements of the EN50131 standard, the level of radio signals sent by
wireless devices is reduced during the test mode operation.
For the AMD-103 detector, entering the test mode remotely is not possible.
Clear memory – this command will erase the memory, where information on tampers of
wireless devices, low battery, and jamming is stored.
Restart communication test – the command, available in the DLOAD10 and DLOADX
programs only, which resets the communication test. The communication test consists
in monitoring the response cycle. If during a consecutive poll a device fails to establish
communication with the controller, the fact is registered and presented as impairment of
communication quality. The test is carried out in the on-line mode, and its results are
visualized as the Communication quality in percentage form.
Synchronization – the ACU-100 controller checks whether other wireless systems are
operating within its range, and if so, it adjusts the response time accordingly.
Synchronization is performed automatically on starting the controller and after each
operation of addition/removal of devices supported by it. Additionally, it can be started
manually with this command.
Supply voltage – function if the LCD keypad which allows the controller supply voltage level
to be checked. In the DLOAD10, DLOADX programs, the information on supply voltage is
provided in on-line mode, with no need for starting any function whatever.
In/Out module tampers – information on communication of the controller with the ACX-100
input/output expansion modules, available in the DLOAD10 program only. Lack of
communication is recognized as the module tamper.
Tamper alarm in partition [Expander tamper] – this option, available when the controller is
connected to the INTEGRA, INTEGRA Plus or VERSA control panel, makes it possible
to indicate the partition where alarm will be triggered in the event of controller tamper.
No blocking after 3 tampers – option available when interacting with the INTEGRA /
INTEGRA Plus series control panel. The controller generates alarm on opening the
tamper contact. Normally, if 3 consecutive tamper alarms are not cleared, signaling of
next tamper alarms will be blocked, which prevents the same events being repeatedly
saved in the control panel memory. The option allows the blocking to be disabled.
Always active – this option, available when interacting with the INTEGRA, INTEGRA Plus or
VERSA series control panel, allows the detector to be permanently switched to active
state.
Service end – this function ends the service mode in the keypad.
disabled, 1 – option enabled). For detectors with older firmware, enter a digit from 1 to 3,
which corresponds to the selected sensitivity (see: Table 10).
Number Detector sensitivity
1 low
2 medium
3 high
Table 10.
12.1.2 APMD-150 detector
Enter a 3-digit sequence:
1st digit – sensitivity of PIR sensor: from 1 to 4 (1 – minimum; 4 – maximum),
2nd digit – sensitivity of microwave sensor: from 1 to 8 (1 – minimum; 8 – maximum),
3rd digit – type of operation in the test mode: 0 (signaling violation after motion is detected by
both sensors), 1 (signaling violation after motion is detected by PIR sensor) or 2
(signaling violation after motion is detected by microwave sensor).
For example, entering the values 4-4-0 means that the PIR sensor sensitivity has been set to
4, the microwave sensor sensitivity also to 4, and in the test mode the detector will signal
violation (the LED will light up) after motion is sensed by both sensors.
12.1.3 AMD-100 and AMD-101 detectors
Enter the digit 0 (the lower reed switch) or 1 (the side reed switch) to select which of the two
reed switches is to be active.
12.1.4 AMD-102 detector
For the magnetic contact (the first position / the first zone occupied by the AMD-102
detector), enter the digit 0 (the lower reed switch) or 1 (the side reed switch) to select which
of the two reed switches is to be active.
For the roller shutter input (the second position / the second zone occupied by the AMD-102
detector), enter a sequence of two digits:
1st digit – number of pulses: from 1 to 8,
2nd digit – pulse validity: 0 (30 s), 1 (120 s), 2 (240 s) or 3 (unlimited duration – only
switching over the detector from passive into active mode will reset the pulse counter).
For example, entering the values 4-2 means that the zone will be violated after registering
4 pulses, and the maximum time that can elapse between the first and the last pulse can be
240 seconds.
12.1.5 AGD-100 detector
Enter a digit from 1 to 3 which corresponds to the selected sensitivity for the high-frequency
channel (see: Table 10).
12.1.6 AVD-100 detector
For the magnetic contact (the first position / the first zone occupied by the AVD-100 detector),
enter the digit 0 (the lower reed switch) or 1 (the side reed switch) to select which of the two
reed switches is to be active.
For the vibration detector (the second zone occupied by the AVD-100 detector), enter a 2-
digit sequence:
1st digit – sensitivity: from 1 to 8 (1 – minimum; 8 – maximum),
2nd digit – number of pulses: from 0 to 7.
For example, entering the values 4-6 means that sensitivity has been set to 4, and the
number of pulses to 6.
ACU-100 SATEL 45
For example, entering the values 2-0-1 means that the signaling will last 3 minutes, the
acoustic signaling has been disabled, and the optical signaling enabled.
12.1.12 ASW-100 E and ASW-100 F controllers
Enter a digit from the 0 to 2 range, which corresponds to the selected mode of operation.
– pulse validity: 30, 120 or 240 seconds, or unlimited duration (--- on the display) i.e. only
switching over the detector from passive in to active state will reset the pulse counter.
12.2.5 AGD-100 detector
The and keys enable sensitivity to be selected within the 1 to 3 range (see Table 10).
12.2.6 AVD-100 detector
After selecting the first position / the first zone occupied by the AVD-100, the and keys
allow you to indicate the active reed switch of the magnetic contact.
After selecting the second position / the second zone occupied by the AVD-100 detector, the
parameters of the vibration detector can be configured. The and keys allow you to
navigate between the parameters and the and keys to modify them. The following
should be programmed:
– sensitivity within the range from 1 to 8 (1 – minimum; 8 – maximum);
– number of pulses within the range from 0 to 7.
12.2.7 ASD-100 detector
The and keys allow you to navigate between the programmable detector parameters,
and the and keys to modify them. The following should be programmed:
– operating mode of the heat sensor: you can disable the sensor (the symbol displayed) or
select the detection class (A1, A2 or B) acc. to the standard EN 54-5;
– operating mode of the buzzer: you can disable the buzzer (the symbol displayed) or
select one of the three types of sound signaling;
– duration of alarm signaling by the buzzer/LED: 1, 3, 6 or 9 minutes.
12.2.8 ARD-100 detector
The and keys enable sensitivity to be selected within the range from 1 to 16 (1 –
minimum; 16 – maximum).
12.2.9 ATD-100 detector
Use the and keys to navigate between the programmable parameters of the detector.
Use the numeric keys to program the following:
– temperature: a value from the -30° C to 70° C range (with up to 0.5° accuracy) – to enter
the preceding “-” sign, press one of the numeric keys from 3 to 9;
– tolerance: a value from the 0.5° C to 10° C range (with up to 0.5° accuracy);
– threshold type: H (high) or L (low).
12.2.10 ASP-105 siren
After selecting the first position / the first zone occupied by the siren, define the parameters of
acoustic signaling. Use the and keys to navigate between the parameters and the
and keys to modify them. The following should be programmed:
– type of acoustic signaling: a choice out of four types is provided;
– maximum duration of signaling: 1, 3, 6 or 9 minutes.
12.2.11 ASP-205 siren
Signaling parameters can be independently selected for both positions / zones occupied by
the siren. Use the and keys to navigate between the parameters and the and keys
to modify them. The following should be programmed:
– operating mode of acoustic signaling: it can be disabled (the symbol displayed) or one
out of three types of acoustic signaling selected;
– maximum duration of signaling: 1, 3, 6 or 9 minutes;
48 Two-way wireless system ABAX ACU-100
– operating mode of optical signaling: it can be disabled (the symbol displayed) or enabled
(the symbol displayed). The LCD keypad of INTEGRA / INTEGRA Plus system allows
you to enable/disable the signaling by pressing any numerical key (the and keys
have no effect).
12.2.12 ASW-100 E and ASW-100 F controllers
Use the and keys to select the operating mode of the ASW-100 controller.
14. SPECIFICATIONS
Operating frequency band................................................................... 868.0 MHz ÷ 868.6 MHz
Number of supported wireless devices .................................................................................. 48
Range ..............................................................................................up to 500 m (in open area)
Supply voltage ................................................................................................... 12 V DC ±15%
Standby current consumption ........................................................................................140 mA
Maximum current consumption ......................................................................................140 mA
Outputs current-carrying capacity ....................................................................................50 mA
Security grade according to EN50131-3 ....................................................................... Grade 2
Environmental class according to EN50130-5 .........................................................................II
Operating temperature range............................................................................ -10 °C…+55 °C
Maximum humidity ..........................................................................................................93±3%
Complied with standards. EN 50130-4, EN 50130-5, EN 50131-1, EN 50131-3, EN 50131-5-3
Electronics board dimensions ............................................................................... 104 x 73 mm
Housing dimensions, OPU-1 A ................................................................... 126 x 158 x 32 mm
Weight............................................................................................................................... 222 g
Name of certification body........................................................................................Telefication
ACU-100 SATEL 49