Polaris Cable QAP As Per IS 694
Polaris Cable QAP As Per IS 694
Polaris Cable QAP As Per IS 694
(Cu / Alu) 2) Tensile Test (for Alu) Tensile Testing M/c 10% As per IS - 8130 As per IS - 8130
3) Wrapping Test (for Alu) Self Device 10% As per IS - 8130 As per IS - 8130
The conductor should be Confirms to the
4) Surface finish Visual 10%
smooth. requirement
5) Annealing Test (for copper) Tensile Testing M/c 10% As per IS - 8130 As per IS - 8130
2) Tensile strength & Elongation Review M.T.C 100% As per IS - 5831 As per IS - 5831
1
5) Spark test ( On Line) On line sparke tester 100% As per IS - 694 As per IS - 694
Each setting & twice in a
6) Diameter Check Vernier Calliper As per IS - 694 As per IS - 694
shift
Start and end of each
Should be smooth & free from Should be smooth & free
7) Surface finish Visual setting & twice during the
porosity from porosity
processing for that setting
Conductor should show Conductor should show
8) Continuity of Conductor Continuity tester 100%
continuity continuity
C. Tests on cores Random check for each
1) Thickness of Insulation Vernier Calliper As per IS - 694 As per IS - 694
in Laboratory size & colour
3) Tensile strength & Elongation Tensile testing m/c - Do - As per IS - 694 As per IS - 694
4) Insulation resistance & Volume One for each size &
Insulation tester As per IS - 694 As per IS - 694
resistivity colour(if changes)
D. Printing /
Visual Check Visual 100% As per IS - 694 As per IS - 694
Embossing
E. Laying up 1) Number / Sequence of cores Visual Each setting As per IS - 694 As per IS - 694
Confirms to the
4) Lay Length Meter Scale Each setting As per requirement
requirement
Conductor should show Conductor should show
5) Continuity of conductors Continuity tester 100%
continuity continuity
F. Outer Sheath Confirms to the
1) Type of PVC Visual check of grade Random As per requirement
Extrusion requirement
2) Thichness of Outer sheath Vernier calliper / microscope Each setting As per IS - 694 As per IS - 694
3) Overall Diameter Vernier calliper Each setting As per IS - 694 As per IS - 694
4) Colour of sheath Visual Check on each Drum As per IS - 694 As per IS - 694
5) Embossing / Sequential Marking Visual Check on each Drum As per IS - 694 As per IS - 694
Confirms to the
6) Cable Length Visual Check on each Drum As per requirement
requirement
7) Surface Quality Visual Check on each Drum Smooth surface Smooth surface
9) High Voltage Test High voltage tester 100% As per IS - 694 As per IS - 694
2
III. FINISHED CABLE INSPECTION
Electrical /Digital micro ohm
A. Routine Tests 1) Conductor Resistance As per IS - 694 As per IS - 694 As per IS - 694
Meter
2) High Voltage Test High voltage tester As per IS - 694 As per IS - 694 As per IS - 694
B.Acceptance Tests 1) Annealing test on Copper Tensile testing m/c As per IS - 694 As per IS - 694 As per IS - 694
4) Wrapping test for Aluminium Self Device As per IS - 694 As per IS - 694 As per IS - 694
5)Thickness of Insulation / Shesth measurment As per IS - 694 As per IS - 694 As per IS - 694
9) High Voltage Test at room temp High voltage tester As per IS - 694 As per IS - 694 As per IS - 694
10) Flammability Test Flammability Chamber As per IS - 694 As per IS - 694 As per IS - 694
C. Type Tests 1) Annealing test on Copper Tensile testing m/c One Sample Per Lot As per IS - 694 As per IS - 694
2) Tensile test for Aluminium Tensile testing m/c One Sample Per Lot As per IS - 694 As per IS - 694
3) Wrapping test for Aluminium Self Device One Sample Per Lot As per IS - 694 As per IS - 694
5) Thickness of Insulation / Sheath measurment One Sample Per Lot As per IS - 694 As per IS - 694
15) Flammability Test Flammability Chamber One Sample Per Lot As per IS - 694 As per IS - 694
Note: All Routine and Acceptance Tests can be carried out in the presence of Inspection agencies. Type tests can however only be reviewed..
Submitted By:
M/S POLARIS CABLES & WIRES PVT. LTD