0102-Ss-E-Tqu-102 - Circuit Breaker For Line (1 Pole) Technical Particular Guarantee
0102-Ss-E-Tqu-102 - Circuit Breaker For Line (1 Pole) Technical Particular Guarantee
0102-Ss-E-Tqu-102 - Circuit Breaker For Line (1 Pole) Technical Particular Guarantee
1. Manufacturer - To be mentioned
2. Type of designation - To be mentioned
3. Type of circuit breaker Operating Mechanism - Spring Type
4. Standard - IEC-62271-100 and IEC-60376
5. Type of arc quenching medium - SF6
6. Number of phases - 3
7. Frequency Hz 50
8. Nominal voltage kV 150
9. Highest system voltage kV 170
10. Rated continuous current A 1250, 1600, 2000, 2500, 3150, 4000
11. Short time current rating (1 seconds) kA 31,5 or 40
12. Symmetrical short circuit (1 seconds, r.m.s.) at
highest system voltage kA 31,5 or 40
13. Short circuit making current 1 seconds, r.m.s.) at
highest system voltage
kA 80 or 100
14. Breaking capacity kA 31,5 or 40
15. Insulation class :
(......................................................) (..............................................)
DAFTAR ISIAN 3 : TECHNICAL PARTICULARS AND GUARANTEES
(......................................................) (..............................................)
DAFTAR ISIAN 3 : TECHNICAL PARTICULARS AND GUARANTEES
(......................................................) (..............................................)
DAFTAR ISIAN 3 : TECHNICAL PARTICULARS AND GUARANTEES
(......................................................) (..............................................)
DAFTAR ISIAN 3 : TECHNICAL PARTICULARS AND GUARANTEES
(......................................................) (..............................................)
DAFTAR ISIAN 3 : TECHNICAL PARTICULARS AND GUARANTEES
TPG V.3. 2 : 150 KV CIRCUIT BREAKER FOR TRAFO BAY AND COUPLE BAY
Manufacturer to be mentioned
Type Designation to be mentioned
1 Standard IEC 62271-100 and IEC 62271-1
2 Service condition refer to General Particulars of the site in Book B
3 Type of Circuit breaker Live Tank
4 Type of arc quenching medium SF6
5 Number of Phases phase 3
7 Rated voltage (Ur) kV rms 170
8 Rated frequency (Fr) Hz 50
9 Rated normal current (Ir) A rms ≥ (1250 or 2000 or 2500 or 4000)
10 Rated short-time withstand current (I th) kA rms 31,5 or 40 or 50
11 Rated peak withstand current (I p) kA peak ≥ 2,5 x I th
12 Rated duration of short circuit s ≥ 1
13 Rated insulation level :
Power frequency withstand voltage, dry for 1 minute
Phase to earth, between the phases and across the open
kV rms 325
breaker gap
Impulse withstand voltage (at 1,2/50 microsecond)
Phase to earth, between the phases and across the open
kV peak 750
breaker gap
Minimum Creepage distance (according to degree of
14
pollution)
a) Up to Heavy Pollution mm/kV 25
b) Very Heavy Pollution mm/kV 31
15 Operating Sequence And Operating Duty
- Nominal Sequence
(Not intended for rapid auto reclosing) O - 0.3s - CO - 180s - CO
- Out of phase O - CO
16 Rated making and breaking current to Normal/Reclose
- Making current kA peak ≥ 2,5 x I th
- Breaking current (symmetrical) kA rms 31,5 or 40 or 50
- % dc component % dc > 20
17 Breaking current under out of phase condition kA rms ≥ 25 % x I th
6 dari 26
(......................................................) (..............................................)
DAFTAR ISIAN 3 : TECHNICAL PARTICULARS AND GUARANTEES
TPG V.3. 2 : 150 KV CIRCUIT BREAKER FOR TRAFO BAY AND COUPLE BAY
MECHANISM
Manufacture
Type
24 Number of interrupters in series per phase pcs 1
25 Number of tripping coils per phase pcs 2
26 Number of closing coils per phase pcs 1
27 Operating mechanism :
- Type spring
- Number of stored energy operation 1 ( one for three phase)
28 Protection level of control cubicle IP54
29 Supply voltage :
- Control voltage Volt DC 110
- Tripping and closing Coils Volt DC 110
- Motor voltage Volt AC 230/400 V AC
- Heater Volt AC 230 VAC
30 Tolerance range for auxiliary supply voltage
- tripping coil % 85 to 110
- closing coil % 85 to 110
- motor % 85 to 110
31 Mechanical performance
7 dari 26
(......................................................) (..............................................)
DAFTAR ISIAN 3 : TECHNICAL PARTICULARS AND GUARANTEES
TPG V.3. 2 : 150 KV CIRCUIT BREAKER FOR TRAFO BAY AND COUPLE BAY
OTHERS
34 Discrepancy device N/A
35 Antipumping device Yes
36 Method of controling voltage distribution between break unit N/A
37 Method of Closing control N/A
38 Value of closing resistor Ohm N/A
39 Insertion time of closing resistor ms N/A
40 SF6 Pressure Indicator per set pcs 1
41 Counter to record number of operation per set pcs 1
Seismic acceleration constant consideration (according to
42 g 0,2 or 0,3
seismic map)
43 Leakage rate of SF6 gas per annum % ≤ 0.5
44 Contact resistance across main contacts per phase µ ohm < 100
Number of switch operations between two inspections for
45
changing the main-contacts :
- with rated continuous current to be mentioned
- with rated breaking current to be mentioned
47 Material of insulator Silicon Rubber or Porcelain
48 Minimum clearance in air :
- between phase mm 1800
- phase to earth mm 1500
- live conductor to ground level mm 3800
8 dari 26
(......................................................) (..............................................)
DAFTAR ISIAN 3 : TECHNICAL PARTICULARS AND GUARANTEES
TPG V.3. 2 : 150 KV CIRCUIT BREAKER FOR TRAFO BAY AND COUPLE BAY
9 dari 26
(......................................................) (..............................................)
#REF!
Manufacturer to be mentioned
Type Designation to be mentioned
1 Standard IEC 62271-100 and IEC 62271-1
2 Service condition refer to General Particulars of the site in Book B
3 Type of Circuit breaker Live Tank
4 Type of arc quenching medium SF6
5 Number of Phases phase 3
6 Rated voltage (Ur) kV rms 170
7 Rated frequency (Fr) Hz 50
8 Rated normal current (Ir)
a) up to twin conductors A rms ≥ 1600
b) quadruple conductors A rms ≥ 3150
9 Rated short-time withstand current (I th) kA rms 31,5 or 40 or 50
10 Rated peak withstand current (I p) kA peak ≥ 2,5 x I th
11 Rated duration of short circuit s ≥ 1
12 Rated Insulation Level :
Power frequency withstand voltage, dry for 1 minute
Phase to earth, between the phases and across the open
kV rms 325
breaker gap
Impulse withstand voltage (at 1,2/50 microsecond)
Phase to earth, between the phases and across the open
kV peak 750
breaker gap
13 Minimum Creepage distance (according to degree of pollution)
a) Up to Heavy Pollution mm/kV 25
b) Very Heavy Pollution mm/kV 31
14 Operating Sequence And Operating Duty
- Nominal Sequence
(rapid auto-reclosing/dead time) O - 0.3s - CO - 180s - CO
- Out of phase O - CO
15 Rated making and breaking current to Normal/Reclose
- Making current kA peak ≥ 2,5 x I th
- Breaking current (symmetrical) kA rms 31,5 or 40 or 50
- % dc component % dc > 20
10 dari 26
(......................................................) (..............................................)
#REF!
MECHANISM
Manufacture
Type
21 Number of interrupters in series per phase pcs 1
22 Number of tripping coils per phase pcs 2
23 Number of closing coils per phase pcs 1
24 Operating mechanism :
- Type spring-spring
- Number of stored energy operation 1 ( one per phase)
25 Protection level of control cubicle IP54
26 Supply voltage :
- Control voltage Volt DC 110
- Tripping and closing Coils Volt DC 110
- Motor voltage Volt AC 230/400 V AC
- Heater Volt AC 230 VAC
27 Tolerance range for auxiliary supply voltage
- tripping coil % 85 to 110
- closing coil % 85 to 110
BIDDER'S SIGNATURE MANUFACTURER'S SIGNATURE
11 dari 26
(......................................................) (..............................................)
#REF!
- motor % 85 to 110
28 Mechanical performance
1. Total break time (trip initiation to final arc extinction) ms ≤ 50
2. Opening time (trip initiation to contact separation) without
ms ≤ 30
current
3. Time interval between opening of interrupters of first and last
ms ≤4
phase
4. Time interval between opening of interupters of one phase ms N/A
5. Making time without current ms ≤ 100
6. Time interval between closure of interrupters of the first and
ms ≤ 10
last pole
7. Time interval between closure of interrupters of one phase ms N/A
8. Time from extinction of main arc to contact make ms ≤ 300
during auto-reclose duty
29 Number of auxiliary contacts (NO/NC) per pole pcs >8
OTHERS
30 Discrepancy device Yes
31 Antipumping device Yes
32 Method of controling voltage distribution between break unit N/A
33 Method of Closing control N/A
34 Value of closing resistor Ohm N/A
35 Insertion time of closing resistor ms N/A
36 SF6 Pressure Indicator per pole pcs 1
37 Counter to record number of operation per set pcs 3
Seismic acceleration constant consideration (according to
38 g 0,2 or 0,3
seismic map)
39 Leakage rate of SF6 gas per annum % ≤ 0.5
40 Contact resistance across main contacts per phase µ ohm < 100
Number of switch operations between two inspections for
41
changing the main-contacts :
- with rated continuous current to be mentioned
- with rated breaking current to be mentioned
42 Material of insulator Silicon Rubber or Porcelain
43 Minimum clearance in air :
- between phase mm 1800
- phase to earth mm 1500
- live conductor to ground level mm 3800
12 dari 26
(......................................................) (..............................................)
#REF!
13 dari 26
(......................................................) (..............................................)
#REF!
Manufacturer to be mentioned
Type Designation to be mentioned
1 Standard IEC 62271-100 AND IEC 62271-1
2 Service condition refer to General Particulars of the site in Book B
3 Type of Circuit breaker Live Tank
4 Type of arc quenching medium SF6
5 Number of Phases phase 3
6 Rated voltage (Ur) kV rms 170
7 Rated frequency (Fr) Hz 50
8 Rated normal current (Ir) A rms ≥ 1250
9 Rated short-time withstand current (I th) kA rms 31,5 or 40 or 50
10 Rated peak withstand current (I p) kA peak ≥ 2,5 x I th
11 Rated duration of short circuit s ≥ 1
12 Rated insulation level :
Power frequency withstand voltage, dry for 1 minute
Phase to earth, between the phases and across the open
kV rms 325
breaker gap
Impulse withstand voltage (at 1,2/50 microsecond)
Phase to earth, between the phases and across the open
kV peak 750
breaker gap
13 Minimum Creepage distance (according to degree of pollution)
a) Up to Heavy Pollution mm/kV 25
b) Very Heavy Pollution mm/kV 31
14 Operating Sequence And Operating Duty
- Nominal Sequence
(Not intended for rapid auto-reclosing) O - 0.3s - CO - 180s - CO
- Out of phase O - CO
15 Rated making and breaking current to Normal/Reclose
- Making current kA peak ≥ 2,5 x I th
- Breaking current (symmetrical) kA rms 31,5 or 40 or 50
- % dc component % dc > 20
16 Breaking current under out of phase condition kA rms ≥ 25 % x I th
17 Rated capacitive switching currents for Single capacitor A rms refer to IEC
14 dari 26
(......................................................) (..............................................)
#REF!
MECHANISM
Manufacture
Type
21 Number of interrupters in series per phase pcs 1
22 Number of tripping coils per phase pcs 2
23 Number of closing coils per phase pcs 1
24 Operating mechanism :
- Type spring-spring
- Number of stored energy operation 3 (one per phase)
25 Protection level of control cubicle IP54
26 Supply voltage :
- Control voltage Volt DC 110
- Tripping and closing Coils Volt DC 110
- Motor voltage Volt AC 230/400 V AC
- Heater Volt AC 230 VAC
27 Tolerance range for auxiliary supply voltage
- tripping coil % 85 to 110
- closing coil % 85 to 110
- motor % 85 to 110
28 Mechanical performance
1. Total break time (trip initiation to final arc extinction) ms ≤ 50
15 dari 26
(......................................................) (..............................................)
#REF!
OTHERS
30 Discrepancy device Yes
31 Antipumping device Yes
32 Method of controling voltage distribution between break unit N/A
33 Method of Closing control N/A
Value of closing resistor Ohm N/A
Insertion time of closing resistor ms N/A
34 SF6 Pressure Indicator per pole pcs 1
35 Counter to record number of operation per set pcs 3
Seismic acceleration constant consideration (according to
36 g 0,2 or 0,3
seismic map)
37 Leakage rate of SF6 gas per annum % ≤ 0.5
38 Contact resistance across main contacts per phase µ ohm < 100
Number of switch operations between two inspections for
39
changing the main-contacts :
- with rated continuous current times to be mentioned
- with rated breaking current times to be mentioned
40 Material of insulator Silicon Rubber or Porcelain
41 Minimum clearance in air :
- between phase mm 1800
- phase to earth mm 1500
- live conductor to ground level mm 3800
- live insulator to ground level mm 2300
16 dari 26
(......................................................) (..............................................)
0102-SS-E-TQU-102 : CIRCUIT BREAKER FOR LINE (1 POLE) TECHNICAL PARTICULAR GUARANTEE REV.00
NO DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE
Manufacturer to be mentioned
Type Designation to be mentioned
1 Standard IEC 62271-100 and IEC 62271-1
2 Service condition Outdoor, Tropical Area
3 Type of Circuit breaker Live Tank
4 Type of arc quenching medium SF6
5 Number of Phases phase 3 (Three) Single Phase
6 Rated voltage (Ur) kV rms 170
7 Rated frequency (Fr) Hz 50
8 Rated normal current (Ir) A rms ≥ 3150
9 Rated short-time withstand current (Ik) 40
a) System with 2 unit IBT 250 MVA parallel kA rms 31.5
b) System with 2 unit IBT 500 MVA parallel kA rms 40
c) Special case kA rms 50
10 Rated peak withstand current (Ip) kA peak ≥ 2,5 x Ik
11 Rated duration of short circuit s ≥ 1
12 Rated Insulation Level :
- Rated short-duration power frequency withstand voltage (Ud) kV rms 325
- Rated lightning impulse withstand voltage (Up) kV peak 750
13 Minimum Creepage distance (according to degree of pollution)
mm/
Very Heavy Pollution 31
kV
14 Operating Sequence And Operating Duty
- Nominal Sequence
17 of 26
(......................................................) (..............................................)
0102-SS-E-TQU-102 : CIRCUIT BREAKER FOR LINE (1 POLE) TECHNICAL PARTICULAR GUARANTEE REV.00
NO DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE
(rapid auto-reclosing/dead time) O - 0.3s - CO - 180s - CO
- Out of phase O - CO
18 of 26
(......................................................) (..............................................)
0102-SS-E-TQU-102 : CIRCUIT BREAKER FOR LINE (1 POLE) TECHNICAL PARTICULAR GUARANTEE REV.00
NO DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE
15 Rated making and breaking current to Normal/Reclose
- Making current kA peak ≥ 2,5 x I th
kA
- Breaking current (symmetrical) 40
rms
- % dc component % ≤ 20
16 Rated out of phase breaking current kA rms ≥ 25 % x Ik
17 Rated capacitive switching currents for Line charging or Cable charging A rms refer to IEC 62271-100 table 9
- circuit closed to ground µV To be Mentioned
- circuit breaker open, grounded terminal µV To be Mentioned
18 Classes
- Electrical endurance E1
- Transient Recovery Voltage refer to IEC 62271-100 table 26
- Mechanical endurance M2
- Restrike performance C2
19 Temperature rise at :
- Contacts in SF6 °C ≤ 65
- Connection, bolted or equivalent in SF6 °C ≤ 75
- Terminal °C ≤ 65
MECHANISM
Manufacture
Type
20 Number of interrupters in series per phase pcs 1
21 Number of tripping coils per phase pcs 2
19 of 26
(......................................................) (..............................................)
0102-SS-E-TQU-102 : CIRCUIT BREAKER FOR LINE (1 POLE) TECHNICAL PARTICULAR GUARANTEE REV.00
NO DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE
22 Number of closing coils per phase pcs 1
23 Operating mechanism :
20 of 26
(......................................................) (..............................................)
0102-SS-E-TQU-102 : CIRCUIT BREAKER FOR LINE (1 POLE) TECHNICAL PARTICULAR GUARANTEE REV.00
NO DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE
- Type motor-spring
- Number of operation mechanism 3 ( one per phase)
24 Protection level of control cubicle (minimum) IP54
25 Supply voltage :
Volt
- Control voltage 110
DC
Volt
- Tripping and closing Coils 110
DC
Volt
- Motor voltage 230/400 V AC
AC
Volt
- Heater 230 VAC
AC
26 Tolerance range for auxiliary supply voltage
- tripping coil % 70 to 110
- closing coil % 85 to 110
- motor % 85 to 110
27 Mechanical performance
1. Total break time (trip initiation to final arc extinction) ms ≤ 50
2. Opening time (trip initiation to contact separation) without current ms ≤ 40
3. Time interval between opening of interrupters of first and last phase ms ≤4
4. Time interval between opening of interupters of one phase ms N/A
5. Closing time without current ms ≤ 110
6. Time interval between closure of interrupters of the first and last pole ms ≤ 10
7. Time interval between closure of interrupters of one phase ms N/A
8. Time from extinction of main arc to contact make ms ≤ 300
during auto-reclose duty
28 Number of auxiliary contacts (NO/NC) per pole pcs >8
21 of 26
(......................................................) (..............................................)
0102-SS-E-TQU-102 : CIRCUIT BREAKER FOR LINE (1 POLE) TECHNICAL PARTICULAR GUARANTEE REV.00
NO DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE
OTHERS
29 Discrepancy device Yes
30 Antipumping device Yes
31 Method of controling voltage distribution between break unit N/A
32 Method of Closing control N/A
33 Value of closing resistor Ohm N/A
34 Insertion time of closing resistor ms N/A
35 SF6 Pressure Indicator per pole pcs 1
36 Counter to record number of operation per set pcs 3
37 Seismic acceleration constant consideration (according to seismic map) g Refer to SNI 1726:2019
38 Leakage rate of SF6 gas per annum % ≤ 0.5
39 Contact resistance across main contacts per phase µ ohm < 80
Number of switch operations between two inspections for changing the main-
40
contacts :
- with rated continuous current to be mentioned
- with rated breaking current to be mentioned
41 Material of insulator Silicon Rubber or Porcelain
42 Minimum clearance in air :
- between phase mm to be mentioned (refer to IEC 61936-1)
- phase to earth mm to be mentioned (refer to IEC 61936-1)
- live conductor to ground level mm to be mentioned (refer to IEC 61936-1)
- live insulator to ground level mm to be mentioned (refer to IEC 61936-1)
22 of 26
(......................................................) (..............................................)
#REF!
23 dari 26
(......................................................) (..............................................)
#REF!
MECHANISM
Manufacture
Type
21 Number of interrupters in series per phase pcs 1
22 Number of tripping coils per phase pcs 2
23 Number of closing coils per phase pcs 1
24 Operating mechanism :
- Type spring-spring
- Number of stored energy operation 3 (one per phase)
25 Protection level of control cubicle IP54
26 Supply voltage :
- Control voltage Volt DC 110
- Tripping and closing Coils Volt DC 110
- Motor voltage Volt DC/AC 110 V DC or 230 V AC
- Heater Volt AC 230 VAC
27 Tolerance range for auxiliary supply voltage
24 dari 26
(......................................................) (..............................................)
#REF!
OTHERS
30 Discrepancy device Yes
31 Antipumping device Yes
32 Method of controling voltage distribution between break unit N/A
33 Method of Closing control N/A
Value of closing resistor Ohm N/A
Insertion time of closing resistor ms N/A
34 SF6 Pressure Indicator per pole pcs 1
35 Counter to record number of operation per set pcs 6 3
36 Seismic acceleration constant consideration (according to seismic map) g 0,2 or 0,3
37 Leakage rate of SF6 gas per annum % ≤ 0.5
38 Contact resistance across main contacts per phase E1, E2 ≤ 60 to be mentioned
Number of switch operations between two inspections for changing the
39
main-contacts :
- with rated continuous current to be mentioned
- with rated breaking current to be mentioned
40 Material of insulator Polymer or Porcelain
BIDDER'S SIGNATURE MANUFACTURER'S SIGNATURE