Tecna
Tecna
INSTRUCTIONS AND
INSTALLATION MANUAL
S.p.A
Via Meucci, 27 - 40024 Castel S. Pietro Terme – Bologna ITALY
Pho. +390516954411 – Fax +390516954490 – http://www.tecna.net
DISTRIBUTOR:
DOCUMENT NUMBER: MAN 4214
2/36
Installation Manual FIELD BUS S.p.A.
TABLE OF CONTENTS:
3/36
S.p.A. FIELD BUS Installation Manual
is a registered trademark.
4/36
Installation Manual FIELD BUS S.p.A.
CHAPTER 1 – INTRODUCTION
Field Bus
The connection between the control unit and the Field Bus module will be guaranteed through the CAN interface
and the CAN serial communication cable, which has to satisfy the requirement of appropriate length.
The choice of the cable to be used will be established according to the customer’s specifications.
5/36
S.p.A. FIELD BUS Installation Manual
All the internal adjustments relevant to the network address selection, to the field bus data
transfer speed as well as to the operative functioning mode have to be carried out and
completed before the switching on of the control board.
When both the S1-3 and S1-4 selectors are set on OFF, the Bridge can be connected to any supported control
unit without further configurations. Thanks to the Field Bus it will be possible to control the inputs as well as the
outputs of the control unit but it won’t be possible to carry the programming phase out.
6/36
Installation Manual FIELD BUS S.p.A.
* Should the Bridge be connected to an INVERTER, properly setting the S1-3 and S1-4 selectors, it would
be possible to carry also this very control unit programming out by means of the Field Bus.
For this mode of operation, it is also necessary to properly amend the selectors on the
boards of the INVERTER as it is shown below.
Adjust the selector SW1 which is on the board 50280 of the inverter on the address 1 instead of 2.
Adjust the selectors on the board 50256 of the inverter on the address 1 instead of 2.
7/36
S.p.A. FIELD BUS Installation Manual
8/36
Installation Manual FIELD BUS S.p.A.
The interface must be switched on and off simultaneously with the control unit that it is
connected to. It is suggested to supply the two devices with the same power transformer.
PIN DESCRIPTION
1 24Vac / 24VDC
2 GND
3 24Vac / 24VDC
9/36
S.p.A. FIELD BUS Installation Manual
Cyclic communication
Acyclic communication
During a cyclic communication session, the inserted data will be those ones that are read and written in a
continuous way, and it is the case of the welding control unit I/O signals.
During an acyclic communication session, the transmitted data will be those ones whose recall is relatively not
very frequent, such as for example the working programme parameters or those data relevant to the different
kinds of menu present on the reference unit, status words or welding data.
Both these data typologies are classified as ADIs and they are allocated in a dedicated memory space.
it is possible:
to use the digital or physical inputs of the control unit in order to carry welding cycles out;
to read the control unit status (after a FAIL condition only);
to read the data relevant to the last carried out welding cycle.
but it is not possible to access the programming parameters of the control unit itself.
It is possible:
to read the control unit’s status (after a FAIL condition only);
to read the data relevant to the last carried out welding cycle;
to perform the programming of the control unit’s functioning parameters
but it is not possible to modify the digital inputs status, except for the REQUESTED STATUS and ENABLE
commands. If the ENABLE input is deactivated (logic “0”), the control unit will use the physical inputs; at the
same time, during the STOP phase the physical inputs status will remain ignored.
As a consequence, it is not possible to perform welding cycles when the control unit is set on STOP.
After having programmed the control unit's operating parameters, the entered data are
saved in it only on switching from the STOP status to the RUN status. If power is cut to
the control unit before then, data associated with the relevant programming will be lost
and the control unit will remain configured with previously stored data.
In order to perform the switching between the two control unit’s functioning states, it is necessary to change the
REQUIRED STATUS input status till the CURRENTLY STATUS output assumes a logic value equal to the value
of the REQUIRED STATUS input. As long as the input and the output do not have the same value, the
control unit’s functioning status remains the one shown on the CURRENTLY STATUS.
10/36
Installation Manual FIELD BUS S.p.A.
ADI DESCRIPTION
0 Cyclic ADI
Reading and writing access always permitted.
10 Control Status
Only reading access always permitted.
17 Programming menu ID to be accessed
Reading and Writing access permitted when the control unit is set on STOP only
18 Number of the affected weld programme
Reading and Writing access permitted when the control unit is set on STOP only
19 Not implemented
Only Reading access permitted when the control unit is set on STOP only
20 Welds data
Only Reading access permitted when the control unit is set on RUN only
100 Data relative to selected ID menu
Reading and Writing access permitted when the control unit is set on STOP only
The data modified in the previously recalled menu are saved in the control unit:
every time a menu is recalled through the 17 ADI;
after the switching from the STOP functioning status to the RUN status.
Every time a menu is recalled through the 17 ADI, the data which have been modified in the previously recalled
menu are saved in the control unit. The data relevant to a menu are saved in the control unit after the switching
from the STOP functioning status to the RUN status also.
In order to access the programming menu (ID 30) of the welding parameters, it is necessary to use the 18 ADI
for selecting the program that has to be available starting from the ADI whose address is 100.
In order to access the programming menu (ID 30) of the welding parameters, it is necessary to use also the 18
ADI. After the selection of the menu type to be worked on through the 17 ADI, it is necessary to write in the 18
ADI which program you want to operate on; after writing the programme number, the data relevant to the
required programme will be available starting from the ADI whose address is 100.
The data saving relevant to the modified programming parameters happens as follows:
through the 17 ADI when it is required the access to a different menu in comparison with the planned
menu;
through the 18 ADI when it is required the access to a welding program which is different in comparison
with the currently charged on the acyclic ADI one;
in the switching from the STOP status to a RUN status.
11/36
S.p.A. FIELD BUS Installation Manual
The inputs and outputs marked with (*) are digital repetitions of physical input signals present on the control unit.
Should more information relevant to the use of these lines be required, it is advisable to refer to the control unit’s
manual.
when the input ENABLE is equal to “1” the control unit ignores the physical inputs present on the control
board and relies its functioning on the status of the logical inputs, which have been received via Bus
Field.
The input REQUESTED STATUS indicates the control unit’s status which is requested by the Master. In case
further information concerning this function is required, it is advisable to consult paragraph 3.1 – CONTROL
UNIT’S STATUS.
The RESTART input command is considered by the control unit during the switching on only and it is ignored
afterwards.
The ERROR RESET command resets possible further error conditions that the control unit could face. The input
is active when the control unit’s status is set on RUN whilst it is ignored when it is set on STOP. Also, the input
START does not have to be active. In order to reset the errors, it is necessary to switch the input from 0 to 1
and back to 0 afterwards; when this operation has been completed, the ADIs relevant to the control status will be
updated.
The DRESSING RESET command produces the signal of electrodes’s carried out dressing after the DRESSING
ALARM has been enabled by the control unit.
The input is active when the control unit’s status is set on RUN whilst it is ignored when it is set on STOP. Also,
the input START does not have to be active. In order to produce the signal of carried out DRESSING, it is
necessary to switch the input from 0 to 1 and back to 0 afterwards.
The ELECTRODES RESET command produces the signal of electrodes’s carried out replacement, after the
ELECTRODES REPLACEMENT ALARM output has been enabled by the control unit.
The input is active when the control unit is set on RUN whilst it is ignored when it is set on STOP. Also the input
START does not have to be active.
In order to produce the signal of carried out replacement, it is necessary to switch the input from 0 to 1 and back
to 0 afterwards.
12/36
Installation Manual FIELD BUS S.p.A.
The following table shows the lists relevant to the inputs and outputs present on the control units.
TE550 / TE553
BYTE 0
BIT 7 START input (*) Active when set on RUN only
BIT 6 AUX input (*) Active when set on RUN only
BIT 5 DOUBLE STROKE input (*) Active when set on RUN only
BIT 4 START 2 input (*) Active when set on RUN only
BIT 3 RIC 1 input (*) Active when set on RUN only
BIT 2 RIC 2 input (*) Active when set on RUN only
BIT 1 RIC 3 input (*) Active when set on RUN only
BIT 0 RIC 4 input (*) Active when set on RUN only
BYTE 1
BIT 7 # Not mapped
BIT 6 RIC 5 input (*) Active when set on RUN only
BIT 5 # Not mapped
BIT 4 # Not mapped
BIT 3 ELECTRODES RESET command Active when set on RUN only
BIT 2 ERRORS RESET command Active when set on RUN only
BIT 1 WELD – NO WELD input (*) Active when set on RUN only
BIT 0 DRESSING RESET command Active when set on RUN only
BYTE 2
BIT 2 RESTART input (*) Active when set on RUN only
BIT 1 REQUESTED STATUS command Active when set on RUN and STOP
BIT 0 ENABLE command Active when set on RUN and STOP
TE560
BYTE 0
BIT 7 START input (*) Active when set on RUN only
BIT 6 AUX input (*) Active when set on RUN only
BIT 5 OPEN input (*) Active when set on RUN only
BIT 4 START 2 input (*) Active when set on RUN only
BIT 3 RIC 1 input (*) Active when set on RUN only
BIT 2 RIC 2 input (*) Active when set on RUN only
BIT 1 EXT. RIC 1 input (*) Active when set on RUN only
BIT 0 EXT. RIC 2 input (*) Active when set on RUN only
BYTE 1
BIT 7 EXT. RIC 4 input (*) Active when set on RUN only
BIT 6 EXT. RIC 5 input (*) Active when set on RUN only
BIT 5 SAFETY input (*) Active when set on RUN only
BIT 4 EXT. RIC 3 Input (*) Active when set on RUN only
BIT 3 ELECTRODES RESET command Active when set on RUN only
BIT 2 ERRORS RESET command Active when set on RUN only
BIT 1 WELD – NO WELD input (*) Active when set on RUN only
BIT 0 DRESSING RESET command Active when set on RUN only
BYTE 2
BIT 2 RESTART input (*) Active when set on RUN only
BIT 1 REQUIRED STATUS command Active when set on RUN and STOP
BIT 0 ENABLE command Active when set on RUN and STOP
13/36
S.p.A. FIELD BUS Installation Manual
TE700
BYTE 0
BIT 7 START input (*) Active when set on RUN only
BIT 6 AUX input (*) Active when set on RUN only
BIT 5 DOUBLE STROKE input (*) Active when set on RUN only
BIT 4 START 2 input (*) Active when set on RUN only
BIT 3 RIC 1 input (*) Active when set on RUN only
BIT 2 RIC 2 input (*) Active when set on RUN only
BIT 1 RIC 3 input (*) Active when set on RUN only
BIT 0 RIC 4 input (*) Active when set on RUN only
BYTE 1
BIT 7 RIC 6 input (*) Active when set on RUN only
BIT 6 RIC 5 input (*) Active when set on RUN only
BIT 5 RIC 8 input (*) Active when set on RUN only
BIT 4 RIC 7 input (*) Active when set on RUN only
BIT 3 SPOTS COUNTER RESET command Active when set on RUN only
BIT 2 ERRORS RESET command Active when set on RUN only
BIT 1 WELD – NO WELD input (*) Active when set on RUN only
BIT 0 DRESSING RESET command Active when set on RUN only
BYTE 2
BIT 2 RESTART input (*) Active when set on RUN only
BIT 1 REQUIRED STATUS command Active when set on RUN and STOP
BIT 0 ENABLE command Active when set on RUN and STOP
INVERTER 1500R
BYTE 0
BIT 7 START input (*) Active when set on RUN only
BIT 6 WELD – NO WELD input (*) Active when set on RUN only
BIT 5 WELD 2 – RIC 5 input (*) Active when set on RUN only
BIT 4 RIC 1 input (*) Active when set on RUN only
BIT 3 RIC 2 input (*) Active when set on RUN only
BIT 2 RIC 3 input (*) Active when set on RUN only
BIT 1 RIC 4 input (*) Active when set on RUN only
BIT 0 SPOTS COUNTER RESET 1 input (*) Active when set on RUN only
BYTE 1
BIT 7 SPOTS COUNTER RESET 2 input (*) Active when set on RUN only
BIT 6 SPOTS COUNTER RESET 3 input (*) Active when set on RUN only
BIT 5 SPOTS COUNTER RESET 4 input (*) Active when set on RUN only
BIT 4 ERRORS RESET command Active when set on RUN only
BIT 3 DRESSING RESET 1 command Active when set on RUN only
BIT 2 DRESSING RESET 2 command Active when set on RUN only
BIT 1 DRESSING RESET 3 command Active when set on RUN only
BIT 0 DRESSING RESET 4 command Active when set on RUN only
BYTE 2
BIT 7 RIC 6 input (*) Active when set on RUN only
BIT 6 RIC 7 input (*) Active when set on RUN only
BIT 5 RIC 8 input (*) Active when set on RUN only
BIT 4 # Not mapped
BIT 3 # Not mapped
BIT 2 # Not mapped
BIT 1 REQUIRED STATUS command Active when set on RUN and STOP
BIT 0 ENABLE command Active when set on RUN and STOP
14/36
Installation Manual FIELD BUS S.p.A.
The outputs status is modified every time an output changes its status; furthermore it is
constantly updated every time the ADIs relevant to the control units' outputs are written.
The CURRENT STATUS output indicates the control unit’s status. For more information with regards to this
function, it is worthwhile to consult the paragraph 3.1 – CONTROL UNIT STATUS.
The logical output PLC_SINC represents a synchronism signal which has been sent outgoing from the control
unit during a welding cycle. As for the LOCK signal, it is activated during the PRE-WELDING phase (if it exists),
during the SLOPE UP and WELD phases and it is deactivated before the HOLD time.
This signal is present both when the control unit is set on WELD and when it is set on NO WELD.
The two logical outputs LOCK and END represent respectively the functions of INTERBLOCK and CYCLE END
for the relative control unit.
The signal LOCK is present when the control unit is set on WELD only, whilst the signal END is always present
at the end of any welding cycle.
The TERM- FLUX output reproduces the physical input status of the thermostat and/or the protection fluxostat.
The WELD READY indicates the moment (when shifting to the descent front) when all the data relevant to the
just performed welding are available.
The FAIL output is usually disabled during the normal functioning of the control unit and it activates only when it
occurs that particular circumstances prevent the control from proper functioning.
15/36
S.p.A. FIELD BUS Installation Manual
TE700
BYTE 3
BIT 7 PLC_SYNC output
BIT 6 WRONG (*)output
BIT 5 INVERTER READY output (*)
BIT 4 TERM – FLUX output (*)
BIT 3 EMERGENCY output (*)
BIT 2 EV1 output (*)
BIT 1 EV2 output (*)
BIT 0 EV3 output (*)
BYTE 4
BIT 7 EV4 output (*)
BIT 6 AUX3 output (*)
BIT 5 END LIFE output (*)
BIT 4 PRE WARNING output (*)
BIT 3 LOCK-END output
BIT 2 #
BIT 1 #
BIT 0 #
BYTE 5
BIT 2 WELD READY output
BIT 1 CURRENT STATUS output
BIT 0 FAIL output
INVERTER 1500R
BYTE 3
BIT 7 PLC SYNC output
BIT 6 WRONG output (*)
BIT 5 READY output (*)
BIT 4 H2O VALVE output (*)
BIT 3 THERMOSTAT output (*)
BIT 2 EMERGENCY output (*)
BIT 1 LOCK
BIT 0 #
BYTE 5
BIT 2 WELD READY output
BIT 1 CURRENT STATUS output
BIT 0 FAIL output
Slot number Id. DP Ordination number / Identification Address Input Address Output
1 160 Output 1 byte 256
2 160 Output 1 byte 257
3 160 Output 1 byte 258
4 144 Input 1 byte 256
5 144 Input 1 byte 257
6 144 Input 1 byte 258
7 144 Input 1 byte 259
8 144 Input 1 byte 260
9 144 Input 1 byte 261
16/36
Installation Manual FIELD BUS S.p.A.
ADI 10:
It contains the control unit’s operating status instructions, its size is 1 byte and its values vary between 0 and
255. It is equal to 0 when the control unit works properly.
TE550
ADI MEANING RANGE CONVERSION FACTOR
10 Functioning status 0 - 250 1 open relay 1
(Error code) 2 closed relay 1
3 open relay 2
4 closed relay 2
5 defect on both relays
6 crc inner memory
7 network synchronism failure
8 out of limits 50-60 network frequency
9 short- circuited solenoid valve
101 emergency failure
102 thermostat or fluxostat
103 current alarm
104 spots max number - electrodes replacement
105 solenoid valves over-temperature
106 min current limit
107 max current limit
108 min conduction limit
109 max conduction limit
110 reached energy in min time
111 not reached energy in max time
112 current signal failure
113 electrodes voltage failure
114 off the scale current
115 off the scale voltage
116 finished spots – electrodes dressing
117 worn electrodes – use new ones
118 released start – not finished spot
119 position sensor zero procedure
120 position sensor quote fail
121 position sensor modified structure
122 position sensor fail communication
123 non programmable position sensor
124 min thickness limit
125 max thickness limit
126 min indentation limit
127 max indentation limit
128 position sensor not found
129 pressure sensor’s measurement
17/36
S.p.A. FIELD BUS Installation Manual
TE560
ADI MEANING RANGE CONVERSION FACTOR
10 Functioning Status 0 - 250 1 open relay 1
( Error code) 2 closed relay 1
3 open relay 2
4 closed relay 2
5 defect on both relays
6 crc inner memory
7 network synchronism failure
8 out of limits 50-60 network frequency
9 short- circuited solenoid valve
101 emergency failure
102 thermostat or fluxostat
103 current alarm
104 spots max number – electrodes replacement
105 solenoid valves over-temperature
106 min current limit
107 max current limit
108 min conduction limit
109 max conduction limit
110 reached energy in the min time
111 not reached Energy in the max time
112 current signal failure
113 electrodes voltage failure
114 off the scale current
115 off the scale voltage
116 finished spots – electrodes dressing
117 worn electrodes – use new ones
118 released start – not finished spot
119 position sensor zero procedure
18/36
Installation Manual FIELD BUS S.p.A.
19/36
S.p.A. FIELD BUS Installation Manual
TE553
ADI MEANING RANGE CONVERSION FACTOR
10 Functioning Status 0 - 250 1 open relay 1
( Error code) 2 closed relay 1
3 open relay 2
4 closed relay 2
5 defect on both relays
6 crc inner memory
7 network synchronism failure
8 out of limits 50-60 network frequency
9 short- circuited solenoid valve
101 emergency failure
102 thermostat or fluxostat
103 current alarm
104 spots max number – electrodes replacement
105 solenoid valves over-temperature
106 min current limit
107 max current limit
108 min conduction limit
109 max conduction limit
110 reached energy in the min time
111 not reached energy in the max time
112 current signal failure
113 electrodes voltage failure
114 off the scale current
115 off the scale voltage
116 finished spots – electrodes dressing
117 worn electrodes – use new ones
118 released start – not finished spot
119 diodes protection
120 aux 3 input
121 position sensor zero procedure
122 position sensor quote fail
123 position sensor modified structure
124 position sensor fail communication
125 non programmable position sensor
126 min thickness limit
127 max thickness limit
128 min indentation limit
129 max indentation limit
130 position sensor not found
200 energy modality - min > max time
201 min > max current limit
202 min > max conduction limit
203 total impulses number > maximum welding time
204 not programmable if active dressings
205 not programmable if active stepper
20/36
Installation Manual FIELD BUS S.p.A.
TE700
ADI MEANING RANGE CONVERSION FACTOR
10 Functioning Status See Inverter see Inverter
11 Inverter 0 Status See Inverter see Inverter
12 Inverter 1 Status See Inverter see Inverter
13 Inverter 2 Status See Inverter see Inverter
21/36
S.p.A. FIELD BUS Installation Manual
INVERTER 1500R
ADI MEANING RANGE CONVERSION FACTOR
10 Functioning Status 0-2 0 resettable error
(Error Code) 1 non resettable error
2 Wait “Ready reset” from the Inverter
11 Inverter Status 0 0-2 0 Error occurred in NO- WELD
(Work condition) 1 Error occurred in WELD
2 Status being modified
12 Inverter Status 1 1–4 1 (1 – 4)
(Tool Number)
13 Inverter Status 2 1 – 35 1 failed charge – thermostat failure
(Error Code) 2 CRC EEPROM Error
3 START signal at the end of the charge
4 IGBT driver error
5 thermostat failure
6 control unit’s welding record failure at the end of the welding
cycle
7 primary current measurement failure
8 secondary current measurement failure
9 electrodes voltage measurement failure
10 diodes active thermic protection
11 transformer active thermic protection
12 reached energy before the min time
13 non reached energy in the max time
14 finished stepper
15 necessity to perform the diodes dressing
16 necessity to replace the caps
17 NSPOTMAX reached
18 damaged Rogowsky
19 fail communication
20 Fail init sensore di posizione
21 non consistent program with hardware configuration -
position sensor failure
22 position sensor zero procedure failure
23 position sensor’s communication fail
24 Fail - quote measurement – negative quote
25 Fail - thickness lower than the min limit
26 Fail – greater than the max limit
27 Fail - DYNAMIC mode
28 Fail - not carried out R compensation
29 Fail - initial R less than the min. limit
30 Fail - initial R over max. limit
31 non consistent welding mode with ENE or DYNAMIC
32 reached displacement before min T
33 reached displacement after max T
34 Mains pressure lower than the min limit
35 Mains pressure greater than the max limit
22/36
Installation Manual FIELD BUS S.p.A.
ADI 20:
It contains the data relevant to the last welding cycle which has been carried out by the control unit; in case the
information are not read by the Master before the following welding cycle is performed, these information will be
overwritten with the new data provided by the control unit. They are 16 bit unsigned integers.
TE550
ADI MEANING RANGE CONVERSION FACTOR MEASUREMENT UNIT
20 Program number 1 - 250 1 (1 – 250) -
21 Cycles 0 - 995 10 (0 – 99,5) ~
22 Current 0 - 18000 100 (0 – 180,00) KA
23 Degrees 0 - 180 1 (0 – 180) °
24 Energy 0 - 60000 1 (0 – 60000) J
25 Spots 0 - 65000 1 (0 – 65000) -
26 Limits 0 - 12 0 no set up limits -
1 min. I limit
2 ok I limit
3 max. I limit
4 min. degrees limit
5 ok degrees limit
6 max. degrees limit
7 ok energy limit
8 Energy limit max. time
9 Energy limit min. time
10 ok indentation limit
11 max indentation limit
12 low indentation limit
27 Thickness 0 - 65534 1000 (0 – 65,534) mm
28 Indentation 0 - 9999 1000 (0 – 9,999) mm
29 Pressure 0 - 100 10 (0 – 10,0) Bar
23/36
S.p.A. FIELD BUS Installation Manual
TE560
ADI MEANING RANGE CONVERSION FACTOR MEASUREMENT UNIT
20 Program number 1 - 250 1 (1 – 250) -
21 cycles 0 - 995 10 (0 – 99,5) ~
22 Current 0 - 9000 100 (0 – 90,00) KA
23 degrees 0 - 180 1 (0 – 180) °
24 Energy 0 - 60000 1 (0 – 60000) J
25 Spots 0 - 65000 1 (0 – 65000) -
26 Limits 0-9 0 No set up limits -
1 min. I limit
2 ok I limit
3 max. I limit
4 min. degrees limit
5 ok degrees limit
6 max. degrees limit
7 ok Energy limit
8 max. T Energy limit
9 min. T Energy limit
27 Thickness 0 - 65534 1000 (0 – 65,534) mm
28 Indentation 0 - 9999 1000 (0 – 9,999) mm
29 Pressure 0 - 100 10 (0 – 10,0) Bar
24/36
Installation Manual FIELD BUS S.p.A.
TE553
ADI MEANING RANGE CONVERSION FACTOR MEASUREMENT
UNIT
20 Program number 1 - 250 1 (1 – 250) -
21 Cycles 0 - 995 10 (0 – 99,5) ~
22 current 0 - 2000 10 (0 – 200.0) KA
23 Energy 0 - 60000 1 (0 – 60000) J
24 Spots 0 - 65000 1 (0 – 65000) -
25 Limits 0-9 0 no set up limits -
1 min. I limit
2 ok I limit
3 max. I limit
4 min. degrees limit
5 ok degrees limit
6 max. degrees limit
7 ok Energy limit
8 max T Energy limit
9 min T Energy limit
26 Thickness 0 - 65534 1000 (0 – 65,534) mm
27 Indentation 0 - 9999 1000 (0 – 9,999) mm
4 low current
5 high current
6 OK current
7 low RO
8 high RO
9 OK RO
10 low secondary voltage
11 high secondary voltage
12 OK secondary voltage
13 low power
14 high power
15 OK power
16 low Energy
17 high Energy
18 OK Energy
19 low indentation
20 high indentation
21 OK indentation
22 low end R
23 high end R
24 OK end R
42 Power 0 - 60000 100 (0 - 600.00) KW
43 Voltage 0 - 2000 100 (0 - 20.00) V
44 Thermal level 0 - 1000 10 (0 - 100.0) %
45 End Resistance 0 - 60000 10 (0 - 6000.0) uOhm
46 Currently Incremental Step 1-7 1 (1 - 7) -
47 Incremental step number 1-7 1 (1 - 7) -
48 Incremental stepper 1 0 - 2000 10 (0 - 200.0) %
49 Incremental Ending 1 0 - 200 1 (0 - 200) %
50 Incremental stepper 2 0 - 2000 10 (0 - 200.0) %
51 Incremental Ending 2 0 - 200 1 (0 - 200) %
52 Dressing limits 0-4 0 deactivated Dressing -
1 ending life electrodes warning
2 Warning dressing
3 Dressing
4 ending life electrodes
53 Spots dressing 0 - 60000 1 (0 - 60000) -
54 Dressing current position 0 - 60000 1 (0 - 60000) -
55 Thickness 0 - 60000 1000 (0 - 60.000) mm
56 Indentation 0 - 60000 10000 (0 – 6.0000) mm
57 Initial resistance 0 - 60000 1 (0 - 60000) uOhm
26/36
Installation Manual FIELD BUS S.p.A.
SETUP MENU – ID 1:
INVERTER 1500R
MEASUREMEN
ADI MEANING RANGE CONVERSION FACTOR
T UNIT
100 Inverter size 50 – 4000 1 (50 – 4000) A
101 TA turns 500 – 2000 1 (500 – 2000) -
102 Operating frequency 1–4 1 1000 Hz
2 2000
3 3000
4 4000
103 Adjustment type 1-2 1 secondary adjustment -
2 primary adjustment
104 External Set point 1-3 1 Deactivated -
2 activated on current profile
3 external sensor pressure input
105 The voltage to electrodes 1-2 1 Deactivated -
2 activated
106 Tansformer primary 1-2 1 Deactivated -
thermal current 2 60000 A
107 Transformer thermal Time 1–2 1 Deactivated -
Constant 2 60000 sec
108 Diods thermal Protection 1–7 1 Deactivated -
2 2 * 56DN
3 4 * 56DN
4 8 * 56DN
5 2 * 65DN
6 4 * 65DN
7 8 * 65DN
109 Rogowsky Test 1–2 1 Deactivated -
2 Activated
110 Welding Transformers 1-4 1 (1 – 4) -
Number
111 Transformer 1 turn 1 - 200 1 (1 – 200) -
112 Transformer 1 max. 200 - 20000 100 (2.00 – 200.00) KA
current
113 Transformer 2 turn 1 - 200 1 (1 – 200) -
114 Transformer 2 max 200 - 20000 100 (2.00 – 200.00) KA
current
115 Transformer 3 turn 1 - 200 1 (1 – 200) -
116 Transformer 3 max 200 - 20000 100 (2.00 – 200.00) KA
current
117 Transformer 4 turn 1 - 200 1 (1 – 200) -
118 Transformer 4 max 200 - 20000 100 (2.00 – 200.00) KA
current
119 Autoretain 1–2 1 Activated -
2 Deactivated
27/36
S.p.A. FIELD BUS Installation Manual
STEPPER MENU – ID 3:
INVERTER 1500R
ADI MEANING RANGE CONVERSION FACTOR MEASUREMENT
UNIT
100 Tool number 1–4 1 (1 – 4) -
101 Welding parameter stepper - 1–3 1 no stepper -
tool 1 2 L1 law stepper
3 L2 law stepper
102 Welding time stepper - tool 1 1–3 1 no stepper -
2 L1 law stepper
3 L2 law stepper
103 Quote stepper - tool 1 1–3 1 no stepper -
2 L1 law stepper
3 L2 law stepper
104 Tot. incremental steps - tool 1 1–7 1 (1 – 7) -
105 Spots 1 tool 1 0 – 10000 1 (0 – 10000) -
106 Spots 2 tool 1 0 – 5000 1 (0 – 5000) -
107 Spots 3 tool 1 0 – 5000 1 (0 – 5000) -
108 Spots 4 tool 1 0 – 5000 1 (0 – 5000) -
109 Spots 5 tool 1 0 – 5000 1 (0 – 5000) -
110 Spots 6 tool 1 0 – 5000 1 (0 – 5000) -
111 Spots 7 tool 1 0 – 5000 1 (0 – 5000) -
112 Stepper 1 law 1 tool 1 0 – 50 1 (0 – 50) %
113 Stepper 1 law 2 tool 1 0 – 50 1 (0 – 50) %
114 Stepper 2 law 1 tool 1 0 – 50 1 (0 – 50) %
115 Stepper 2 law 2 tool 1 0 – 50 1 (0 – 50) %
116 Stepper 3 law 1 tool 1 0 – 50 1 (0 – 50) %
117 Stepper 3 law 2 tool 1 0 – 50 1 (0 – 50) %
118 Stepper 4 law 1 tool 1 0 – 50 1 (0 – 50) %
119 Stepper 4 law 2 tool 1 0 – 50 1 (0 – 50) %
120 Stepper 5 law 1 tool 1 0 – 50 1 (0 – 50) %
121 Stepper 5 law 2 tool 1 0 – 50 1 (0 – 50) %
122 Stepper 6 law 1 tool 1 0 – 50 1 (0 – 50) %
123 Stepper 6 law 2 tool 1 0 – 50 1 (0 – 50) %
28/36
Installation Manual FIELD BUS S.p.A.
30/36
Installation Manual FIELD BUS S.p.A.
INVERTER 1500R
ADI MEANING RANGE CONVERSION FACTOR MEASUREMENT
UNIT
100 tool Number 1–4 1 (1 – 4) -
101 Dressing tool 1 1–2 1 Deactivated -
2 Activated
102 Dressing number - tool 1 1–7 1 (1 – 7) -
103 Dressing Spots - tool 1 1 – 999 1 (1 – 999) -
104 Dressing stepper - tool 1 1 – 99 1 (1 – 99) %
105 dressing pre-warning spots - tool 1 0 – 25 1 (0 – 25) -
106 Electrodes pre- warning spots - 0 – 999 1 (0 – 999) -
tool 1
107 Dressing Offset - tool 1 0 – 99 1 (0 – 99) %
108 Dressing tool 2 1–2 1 Deactivated -
2 Activated
109 Dressing number- tool 2 1–7 1 (1 – 7) -
110 Dressing spots- tool 2 1 – 999 1 (1 – 999) -
111 Dressing stepper - tool 2 1 – 99 1 (1 – 99) %
112 Dressing pre warning spots - tool 2 0 – 25 1 (0 – 25) -
113 Electrodes pre warning spots - tool 0 – 999 1 (0 – 999) -
2
114 Dressing Offset - tool 2 0 – 99 1 (0 – 99) %
115 Dressing tool 3 1–2 1 Deactivated -
2 Activated
116 Dressing number tool 3 1–7 1 (1 – 7) -
117 Dressing spots tool 3 1 – 999 1 (1 – 999) -
118 Dressing stepper tool 3 1 – 99 1 (1 – 99) %
119 Dressing pre warning spots - tool 3 0 – 25 1 (0 – 25) -
120 Electrodes pre warning spots - tool 0 – 999 1 (0 – 999) -
3
121 Dressing Offset - tool 3 0 – 99 1 (0 – 99) %
122 Dressing tool 4 1–2 1 Deactivated -
2 Activated
123 Dressing stepper - tool 4 1–7 1 (1 – 7) -
124 Dressing Spots- tool 4 1 – 999 1 (1 – 999) -
125 Dressing stepper - tool 4 1 – 99 1 (1 – 99) %
126 Dressing pre warning spots - tool 4 0 – 25 1 (0 – 25) -
127 Electrodes pre warning spots - 0 – 999 1 (0 – 999) -
tool 4
128 Dressing Offset - tool 4 0 – 99 1 (0 – 99) %
31/36
S.p.A. FIELD BUS Installation Manual
INVERTER 1500R
MEASUREMEN
ADI MEANING RANGE CONVERSION FACTOR
T UNIT
100 Programme Number 1 – 301 1 (1 – 301) -
101 Working mode 1–6 1 IK -
2 RO
3 VEK
4 PWK
5 ENE
6 DYN
102 Control mode 1–6 1 NO -
2 CURR
3 RO
4 VE
5 PW
6 ENE
103 Not implemented - - -
104 Pre welding time 0 – 1000 1 (0 – 1000) ms
105 Pre welding current 30 – 20000 100 (0.30 – 200.00) KA
106 Pre welding Ro 50 – 1000 10 (5.0 – 100.0) %
107 Pre welding V 20 – 2000 100 (0.20 – 20.00) V
108 Pre welding P 20 – 60000 100 (0.20 – 600.00) KW
109 Not implemented - - -
110 Not implemented - - -
111 Cold time 1 0 – 1000 1 (0 – 1000) ms
112 slope up time 0 – 1000 1 (0 – 1000) ms
113 Welding time 1 1 – 1000 1 (1 – 1000) ms
114 Min welding time 1 1 – 1000 1 (1 – 1000) ms
115 Max welding time 1 1 – 1000 1 (1 – 1000) ms
116 Welding current 1 30 - 20000 100 (0.30 – 200.00) KA
117 Welding Ro 1 50 - 1000 10 (5.0 – 100.0) %
118 Welding V 1 20 – 2000 100 (0.20 – 20.00) V
119 Welding P 1 20 – 60000 100 (0.20 – 600.00) KW
120 Welding energy 1 0 - 60000 1 (0 – 60000) J
121 Quality R 0-3 0 Deactivated -
1 Pre check
2 Post check
3 Pre + Post check
122 Welding Imax 1 200 - 20000 100 (2.00 – 200.00) KA
123 Cold time 2 0 - 1000 1 (0 – 1000) ms
124 Impulses number 0-9 1 (0 – 9) -
125 Welding time 2 0 - 1000 1 (0 – 1000) ms
126 Welding current 2 30 - 20000 100 (0.30 – 200.00) KA
127 Welding Ro 2 50 - 1000 10 (5.0 – 100.0) %
128 Welding V 2 20 – 2000 100 (0.20 – 20.00) V
32/36
Installation Manual FIELD BUS S.p.A.
All the parameters are 16 bit unsigned integers. For more details relevant to the parameters meaning, please
refer to the control unit manual.
33/36
S.p.A. FIELD BUS Installation Manual
INVERTER 1500R
ADI MEANING RANGE CONVERSION FACTOR MEASUREMENT
UNIT
100 Position sensor 1–2 1 Deactivated -
2 Activated
101 set up sensors number 1–4 1 (1 – 4) -
102 SN 1 sensor 1 0 – 9999 1 (0 – 9999) -
103 SN 2 sensor 1 0 – 9999 1 (0 – 9999) -
104 ID sensor 1 100 – 200 1 (100 – 200) -
105 Delay sensor 1 0 – 1000 1 (0 – 1000) ms
106 SN 1 sensor 2 0 – 9999 1 (0 – 9999) -
107 SN 2 sensor 2 0 – 9999 1 (0 – 9999) -
108 ID sensor 2 100 – 200 1 (100 – 200) -
109 Delay sensor 2 0 – 1000 1 (0 – 1000) ms
110 SN 1 sensor 3 0 – 9999 1 (0 – 9999) -
111 SN 2 sensor 3 0 – 9999 1 (0 – 9999) -
112 ID sensor 3 100 – 200 1 (100 – 200) -
113 Delay sensor 3 0 – 1000 1 (0 – 1000) ms
114 SN 1 sensor 4 0 – 9999 1 (0 – 9999) -
115 SN 2 sensor 4 0 – 9999 1 (0 – 9999) -
116 ID sensor 4 100 – 200 1 (100 – 200) -
117 Delay sensor 4 0 – 1000 1 (0 – 1000) ms
34/36
Installation Manual FIELD BUS S.p.A.
35/36
S.p.A. FIELD BUS Installation Manual
CONSUMPTION: 0,1A
36/36